Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical
shock or other condi tions which may cause personal
injury or property damage. Consult a qualified installer,
service agency, or your distributor or branch for
information or assistance. The qualified installer or
agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual
instructions packaged with the kits or accessories when
installing.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloths for brazing operations and
have a fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions attached to
the unit. Consult local building codes and appropriate
nationalelectricalcodes (in USA, ANSI/NFPA70,
National Electrical Code (NEC); in Canada, CSA C22.1)
for special requirements.
It is important to recognize safety inform ation. This is the
safety--alert symbol
unit and in instructions or manuals, be alert to the
potential for personal injury.
. When you see thi s symbol on the
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the
safety--alert symbol. DANGER identifies the most serious
hazards which will result in seve re personal injury or
death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify
unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced
installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
Before performing service or maintenance operations
on unit, always turn off main power switch to unit and
install lockout tag. Unit may have more than one
power switch.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
Puronr (R--410A) refrigerant systems operate at
higher pressures than standard R--22 systems. Do not
50TCQA
use R--22 service equipment or components on Puron
refrigerant equipment.
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could cause personal
injury or death.
Relieve pressure and recover all refrigerant before
system repair or final unit disposal.
Wear safety glasses and gloves when handling
refrigerants. Keep torches and other ignition sources
away from refrigerants and oils.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal
injury.
Sheet metal parts may have sharp edges or burrs. Use
care and wear appropri ate protective clothing, safety
glasses and gloves when handling parts and servicing
heat pump units.
2
Vertical Connections / Economizer
50TCQA
Horizontal Connections / Economizer
Fig. 1 -- Unit Dimensional Drawing – 04 — 07 Size Units
3
C09001
50TCQA
Jobsite Survey
Fig. 1 -- Unit Dimensional Drawing – 04 — 07 Size Unit (cont.)
INSTALLATION
18” (457)
C09002
1
Complete the following checks before installation.
1. Consult local building codes and the NEC (National
Electrical Code) ANSI/NFPA 70 for special installation requirements.
2. Determi ne unit location (from project plans) or select
unit location.
3. Check for possible overhead obstructions which may
interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (curb
or other) that provides for the minimum clearances
required for safety. This includes the clearance to
combustible surfaces, unit performance and service access
below, around and above unit as specified in unit
drawings. See Fig. 2.
NOTE: Consider also the effect of adjacent units.
Unit may be installed directly on wood flooring or on Class
A, B, or C roof--covering material when roof curb is used.
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated
air.
Although unit is weatherproof, avoid locations that permit
water from higher level runoff and overhangs to fall onto
the unit.
Select a unit mounting system that provides adequate
height to allow for removal and disposal of frost and ice
that will form durring the heating--defrost mode as well as
allow installation of condensate trap per requirements.
RefertoStep9—InstallExternalCondensate Trap and
Line – for required trap dimensions.
4
Roof mount —
Checkbuildingcodesforweightdistribution
requirements. Unit operat ing weight is shown in Table 1.
Step 3 — Inspect unit
Inspect unit for transportation damage. File any claim
with transportation agency.
Step 2 — Plan for Sequence of Unit Installation
The support method used for this unit wil l dictate different
sequences for the steps of unit installation. For exampl e,
on curb--mounted units, some accessories must be
installed on the unit before the unit is placed on the curb.
Review t he following for recommended sequences for
installation steps.
(affects curb and unit) (refer to accessory installation
instructions for details)
Prepare bottom condensate drain connection to suit
planned condensat e line routing (refer to Step 9 for
details)
Rig and place unit
Install outdoor air hood
Install condensate line trap and piping
Make electrical connections
Install other accessories
Pad--mounted installation —
Prepare pad and unit supports
Check and tighten the bottom condensate drain
connection plug
Rig and place unit
Convert unit to side duct connection arrangement
Install field--fabricated ductwork at unit duct openings
Install outdoor air hood
Install condensate line trap and piping
Make electrical connections
Install other accessories
Frame--mounted installation —
Frame--mountedapplications generally follow the
sequence for a curb installation. Adapt as required to
suit specific installation plan.
Confirm before installation of unit that voltage, ampera ge
and circuit protection requirements listed on unit data
plate agree with power supply provided.
Step 4 — Provide Unit Support
Roof Curb Mount —
Accessory roof curb details and dimensions are shown in
Fig. 3. Assemble and install accessory roof curb in
accordance with instructions shipped with the curb.
NOTE:The gasketing of the unit to the roof curb is
critical for a watertight seal. Install gasket supplied with
the roof curb as shown in Fig. 3. Improperly applied
gasket can also result in air leaks and poor unit
performance.
Curb should be level. This is necessary for unit drain to
function properly. Unit leveling toleranc es ar e show in
Fig. 4. Refer to Accessory Roof Curb Installation
Instructions for additional information as required.
Install insulation, cant strips, roofing felt, and counter
flashing as shown. Ductwork must be attached to curb and
not to the unit. The accessory thru--the--base power package
must be installed before the unit is set on the roof curb.
If electric and control wiring is to be routed through the
basepan, attach the accessory thru--the --base service
connections to the basepan in accordance with the
accessory installation instructions.
Slab Mount (Horizontal Units Only) —
Provide a level concrete slab that extends a minimum of
6 in. (150 mm) beyond unit cabinet. Install a gravel apron
in front of condenser coi l air inlet to prevent grass and
foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb
if required.
Alternate Unit Support (In Lieu of Curb or Slab
Mount) —
A non--combustible sleeper rail can be used in the unit curb
support area. If sleeper rails cannot be used, support the long
sides of the unit with a minimum of 3 equally spaced 4--in. x
4--in. (102 mm x 102 mm) pads on each side.
50TCQA
Table 1 – Operating Weights
50TCQAUNITS LB (KG)
ComponentA04A05A06A07
Base Unit505 (229)510 (231)590 (268)630 (286)
Economizer
Vertical80 (36)80 (36)80 (36)80 (36)
Horizontal105 (48)105 (48)105 (48)105 (48)
Powered Outlet32 (15)32 (15)32 (15)32 (15)
Curb
14---in/356 mm110 (50)110 (50)110 (50)110 (50)
24---in/610 mm145 (66)145 (66)145 (66)145 (66)
5
ROOFCURB
ACCESSORY
CRRFCURB001A02
CRRFCURB002A02
1’ - 2”
[356]
2’ - 0”
[610]
UNIT SIZE
50TCQA04-07
50TCQA
Fig. 3 -- Roof Curb Details
6
C08548
MAXIMUM ALLOWABLE
DIFFERENCE IN. (MM)
A-B
0.5” (13)
1.0” (25)
Fig. 4 -- Unit Leveling Tolerances
Step 5 — Field Fabricate Ductwork
B-C
A-C
1.0” (25)
C06110
should be ducted through the roof deck to comply with
applicable fire codes.
Forunitswithaccessoryelectricheaters:Horizontal
applications require a minimum clearance to combustible
surfaces of 1--in (25 mm) from duct for first 12--in (305 mm)
away from unit. V ertical applications do not require a
minimum clearance.
Minimum clearance is not required around ductwork.
Step 6 — Rig and Place Unit
Keep unit upright and do not drop. Spreader bars are not
required if top crating is left on unit. Rollers may be used to
move unit across a roof. Level by using unit frame as a
reference. See Table 1 and Fig. 5 for additional information.
Cabinet return-air static pressure (a nega tive condition)
shall not exceed 0.35 in. wg (87 Pa) with economizer or
0.45 in. wg (112 Pa) without economizer.
For vertical ducted applicat ions, secure all ducts to roof
curb and building structure. Do not connect ductwork to
unit.
Insulate and weatherproof all external ductwork, joi nts,
and roof openings with counter flashing and mastic in
accordance with applicable codes.
Ducts passing through unconditioned spaces must be
insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
Lifting holes are provided in base rails as shown in Fig. 5.
Refer to rigging instructions on unit.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in
equipment damage.
All panels must be in place when rigging. Unit is not
designed for handling by fork truck.
Before setting the unit onto the curb, recheck gasketing on
curb.
50TCQA
NOTES:
C06005
UNIT
50TCQA0475534374.38188936.2592133.38848
50TCQA0576034574.38188936.2592133.38848
50TCQA0684038174.38188935.6390541.381051
50TCQA0788039974.38188937.2594641.381051
1. Dimensions in ( ) are in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the
unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.
MAX WEIGHT
LBKGINMMINMMINMM
ABC
DIMENSIONS
Fig. 5 -- Rigging Details
7
PositioningonCurb—
Position unit on roof curb so that the following clearances
are maintained:
1
/4in. (6.4 mm) clearance between the
roof curb and the base rail inside the front and rear, 0.0 in.
clearance between the roof curb and the base rail inside on
the duct end of the unit. This will result in the distance
between the roof curb and the base rail inside on the
condenser end of the unit being approximately equal to
Fig. 3, section C--C.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
After unit is in position, remove the compressor access
panel. Holding the blocking between compressors with
one hand, cut the strapping. Carefully remove the
blocking without damaging tubing, wiring, or controls.
Remove the strapping and replace the access panel.
Remove all shipping mate rials and top skid. Recycle or
dispose of all shipping materials.
50TCQA
Step 7 — Convert to Horizontal and Connect
Ductwork (when required)
Unit is shipped in the vertical duct configuration. Unit
without factory--installed economizer or return air smoke
detector option may be field--converted to horizontal
ductedconfiguration.Toconverttohorizontal
configuration, remove screws from side duct opening
covers and remove covers. Using the same screws, install
covers on vertical duct openings with the insulation--side
down. Seals around duct openings must be tight. See
Fig. 6.
Step 8 — Install Outside Air Hood
Economizer Hood Removal and Setup -- Factory
Option
1. The hood is shipped in knock--down form and
located in the return air compartment. It is attached
to the economizer using two plastic tie --wraps.
2. To gain access to t he hood, remove the filter access
panel. (See Fig. 7.)
3. Locate and cut the (2) plastic tie--wraps, being
careful to not damage any wiring. (See Fig. 8.)
4. Carefully lift the hood assembly through the filter
access opening and assemble per the steps outlined
in Economizer Hood and Two–Position Hood on
page 10.
FILTER ACCESS PANEL
COMPRESSOR
ACCESS PANEL
OUTDOOR-AIR OPENING AND
INDOOR COIL ACCESS PANEL
Fig. 7 -- Typical Access Panel Locations
C06023
C06108
Fig. 6 -- Horizontal Conversion Panels
Field--supplied flanges should be attached to horizontal
duct openings and all ductwork should be secured to the
flanges. Insulate and weatherproof all external ductwork,
joints, and roof or building openings with counter flashing
and mastic in accordance with applicable codes.
Do not cover or obscure visibility to the unit’s informative
data plate when insulating horizontal ductwork.
Remove Hood Parts
Cut Plastic Ties
(2) Places
Economizer
C08633
Fig. 8 -- Economizer Wiring
8
Two Position Damper Hood Removal and Setup -Factory Option
1. The hood is shipped in knock--down form and
assembled to a metal support tray using plastic
stretchwrap.Locatedinthereturnair
compartment, the assembly’s metal tray is attached
to the basepan and also attached to the damper
using two plastic tie--wraps.
2. To gain access to t he hood, remove the filter access
panel. (See Fig. 7.)
3. Locate the (2) screws holding the metal tray to the
basepan and remove. Locate and cut the (2) plastic
tie--wraps securing the assembly to the damper. (See
Fig. 9.) Be careful to not damage any wiring or cut
tie--wraps securing any wiring.
4. Carefull y lift the hood assembly (with metal tray)
through the filter access opening and assemble per
the steps outlined in Economizer Hood andTwo–Position Hood on page 10.
Hood Parts
50TCQA
Plastic Tie Wrap
Qty (2)
Fig. 9 -- Damper Assembly
Screws for Metal Tray
Qty (2)
C08639
9
Economizer Hood and Two--Position Hood —
NOTE: If the power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be
used and must be discarded. Save the aluminum filter for
use in the power exhaust hood assembly.
1. The indoor coil access panel will be used as the top of
the hood. Remove the screws along t he sides and bottom of the indoor coil access panel. See Fig. 10.
SIDE
PANEL
50TCQA
CAULK
INDOOR
COIL
ACCESS
PANEL
HERE
Fig. 10 -- Indoor Coil Access Panel Relocation
2. Swing out indoor coil access panel and insert the
hood sides under the panel (hood top). Use the screws
provided to attach the hood sides to the hood top. Use
screws provided to attach the hood sides to the unit.
See Fig. 11.
INDOOR COIL
ACCESS PANEL
TOP
SIDE
PANEL
INDOOR
COIL
ACCESS
PANEL
TOP
PANEL
C06025
filter rack (hood divider). Push the filter into position
past the open filter clips. Close the filter clips to lock
the filter into place. See Fig. 12.
DIVIDER
OUTSIDE
AIR
HOOD
CLEANABLE
BAROMETRIC
RELIEF
ALUMINUM
FILTER
FILTER
FILTER
CLIP
C08634
Fig. 12 -- Economizer Filter Installation
6. Caulk the ends of the joint between the unit top panel
and the hood top.
7. Replace the filter access panel.
Step 9 — Install External Condensate Trap and
Line
The unit has one3/4-in. condensate drain connection on
the end of the condensate pan and an alternate connection
on the bottom. See Fig. 13. Unit airflow configuration
does not determine which drain connection to use. Either
drain connection can be used with vertical or horizontal
applications.
When using the standard side drain connection, ensure the
red plug in the alternate bottom connection is tight. Do
this before setting the unit in place. The red drain pan can
be tightened with a
1
/2--in. square socket drive extension.
LEFT
HOOD
SIDE
19 1/16”
B
(483mm)
HOOD DIVIDER
SCREW
33 3/8”
(848mm)
C06026
Fig. 11 -- Economizer Hood Construction
3. Remove the shippi ng tape holding the economizer barometric relief damper in place.
4. Insert the hood divider between the hood sides. See
Fig. 11 and 12. Secure hood divider with 2 screws on
each hood side. T he hood divider is also used as the
bottom filter rack for the aluminum filter.
5. Open the filter clips which are located underneath the
hood top. Insert the aluminum filter into the bottom
To use the alternate bottom drain connection, remove the
red drain plug from the bottom connection (use a1/2-- i n .
square socket drive extension) and install it in the side
drain connection.
CONDENSATE PAN (SIDE VIEW)
STANDARD
SIDE DRAIN
DRAIN
PLUG
(FACTORY-INSTALLED)
ALTERNATE
BOTTOM DRAIN
C08021
Fig. 13 -- Condensate Drain Pan (Side View)
The piping for the condensate drain and external trap can
be completed after the unit is in place. See Fig. 14.
10
MINIMUM PITCH
1” (25mm) PER
10’ (3m) OF LINE
TO ROOF
DRAIN
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4” (102) trap is recommended.
BASE RAIL
OPEN
VENT
2˝ (51) MIN
DRAIN PLUG
SEE NOTE
ROOF
CURB
C08022
Fig. 14 -- Condensate Drain Piping Details
All units must have an external trap for condensate
drainage. Install a trap at least 4-in. (102 mm) deep and
protect against freeze-up. If drain line is installed
downstream from the external t rap, pitch the line away
from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do
not use a pipe size smaller than the unit connection
3
/4-in.).
(
Step 10 — Make Electrical Connections
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning coul d result in personal
injury or death.
Do not use gas piping as an electrical ground. Unit
cabinetmusthaveanuninterrupted,unbroken
electrical ground to minimize the possibility of
personal injury if an electrical fault should occur. This
ground may consist of electrical wire connected to
unit ground lug in control compartment, or conduit
approved for electrical ground when installed in
accordance with NEC (National Electrical Code);
ANSI/NFPA 70, latest edition (in Canada, Canadian
ElectricalCodeCSA[CanadianStandards
Association] C22.1), and local electrical codes.
NOTE: Check all factory and field electrical connections
for tightness. Field--supplied wiring shall conform with
the limitations of 63_F(33_C) rise.
Field Power Supply —
If equipped with optional Powered Convenience Outlet :
The power source leads to the convenience outlet’s
transformer primary are not factory connected. Installer
must connect these leads according to required operation
of the convenience outlet. If an always--energized
convenience outlet operation is desired, connect the
source leads to the line side of the unit--mounted
disconnect. (Check with local codes to ensure this m ethod
is acceptable in your area.) If a de--energize via unit
disconnect switch operation of the convenience outlet is
desired, connect the source leads to the load side of the
unit disconnect. On a unit without a unit--mounted
disconnect, connect the source leads to compressor
contactor C and indoor fan contactor IFC pressure lugs
with unit field power leads.
All units except 208/230-v unit s are factory wired for the
voltage shown on the nameplate. If the 208/230-v unit is
to be connected to a 208-v power supply, the control
transformer must be rewired by moving the black wire
1
with the
connection and moving it to the 208-v
/4-in. female spade connector from the 230--v
1
/4-in. male
terminal on the primary side of the transformer. Refer to
unit label diagram for additional information. Field power
wires will be connected line--side pressure lugs on the
power terminal bl ock or at factory--installed option
non--fused disconnect.
Field power wires are connected to the unit at line--side
pressure lugs on compressor contactor C and indoor fan
contactor IFC or terminal board (see wiring diagram label
forcontrolboxcomponentarrangement)orat
factory--installed option non--fused disconnect switch.
Max wire size is #2 AWG (copper only). (See Fig. 16)
NOTE:TEST LEADS -- Unit may be equipped with
short leads (pigtails) on the field line connection points on
contactor C or optional disconnect switch. These leads are
for factory run--test purposes only; remove and discard
before connecting field power wires to unit connection
points. Make field power connections directly to line
connection pressure lugs only.
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in
intermittent operation or performance satisfaction.
Do not connect aluminum wire between disconnect
switch and furnace. Use only copper wire.
(See Fig. 15.)
ELECTRIC
DISCONNECT
SWITCH
COPPER
WIRE ONLY
ALUMINUM
WIRE
A93033
Fig. 15 -- Disconnect Switch and Unit
Units Without Factory--Installed Disconnect —
When installing units, provide a disconnect switch per
NEC (National Electrical Code) of adequate size.
Disconnect sizing data is provided on the unit informative
plate. Locate on unit cabinet or within sight of the unit per
national or local codes. Do not cover unit informative
plate if mounting the disconnect on the unit cabinet.
50TCQA
11
Units with Factory--Installed Disconnect —
Convenience Outlets —
The factory--installed option disconnect switch is located
in a weatherproof enclosure loc ated under the main
control box. The manual switch handle is accessible
through an opening in the access panel. Discard the
factory test leads (see Fig. 16).
Units Without Disconnect Option
IFC
(3 Phase
Indoor Motor)
C
111313
Disconnect
per
NEC
L1
L2L3
208/230-1-60
208/230-3-60
50TCQA
460-3-60
575-3-60
(1 Phase Indoor Motor
TB
and 1 Phase Unit)
Units With Disconnect Option
L1
L2
L3
2
4
6
Optional
Disconnect
Switch
1
3
5
Factory
Wiring
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning coul d result in personal
injury or death.
Units with convenience outlet circuits may use
multiple disconnects. Check convenience outlet for
power status before opening unit for service. Locate
its disconnect switch, if appropriate, and open it.
Tag--out this switch, if necessary.
Two types of convenience outlets are offered on 50TCQA
models: Non--powered and unit--powered. Both types
providea125--voltGFCI(ground--fault
circuit--interrupter) duplex receptacle rated at 15-- A
behind a hinged waterproof access cover, located on the
end panel of the unit. See Fig. 17.
Pwd-CO
Convenience
Outlet
GFCI
Pwd-CO
Fuse
Switch
Transformer
Disconnect factory test leads; discard.
C09011
Fig. 16 -- Power Wiring Connections
All units --
All field wiring must comply with NEC and all local
codes. Size wire based on MCA (Minimum Circuit Amps)
on the unit i nformative plate. See Fig. 16 and the unit
label diagram for power wiring connections to the unit
power terminal blocks and equipment ground. Maximum
wire size is #2 ga AWG per pole.
Provide a ground--fault and short--c ircuit ove r--current
protection device (fuse or breaker) per NEC Article 440
(or local codes). Refer to unit informative data plate for
MOCP (Maximum Over--current Protection) device size.
All field wiring must comply with the NEC and local
requirements.
Control Box
Access Panel
C08128
Fig. 17 -- Convenience Outlet Location
Installing Weatherproof Cover –
Aweatherproofwhile-in-usecoverforthe
factory-installed convenience outlets is now required by
UL standards. This cover cannot be factory-mounted due
its depth; it must be installed at unit installation. For
shipment, t he convenience outlet is covered with a blank
cover plate.
The weatherproof cover kit is shipped in the unit’s control
box. The kit includes the hinged cover, a backing plate
and gasket.
DISCONNECTALLPOWERTOUNITAND
CONVENIENCE OUTLET.
Remove the blank cover plate at the convenience outlet;
discard the blank cover.
Loosen the two screws at the GFCI duplex outlet, until
1
approximately
/2-in (13 mm) under screw heads are
exposed. Press the gasket over the screw heads. Slip the
backing plate over the screw heads at the keyhole slots
and align with the gasket; tighten the two screws until
snug (do not over-tighten).
12
Mount the weatherproof cover to the backing plate as
shown in Fig. 18. Remove two slot fillers in the bottom of
the cover to permit service tool cords to exit the cover.
Check for full closing and latching.
the face of the receptacle to trip and open the receptacle.
Check for proper grounding wires and power line phasing
if the GFCI receptacle does not trip as required. Press the
RESET button to clear the tripped condition.
COVER – WHILE-IN-USE
WEATHERPROOF
RECEPTACLE
NOT INCLUDED
BASE PLATE FOR
GFCI RECEPTACLE
C09022
Fig. 18 -- Weatherproof Cover Installation
Non--powered type: Thistype requires thefield
installation of a general--purpose 125--volt 15--A circuit
powered from a source elsewhere in the building. Observe
national and local codes when selecting wire size, fuse or
breaker requirements and disconnect switch size and
location. Route 125--v power supply conductors into the
bottom of the utility box containing the duplex receptacle.
Unit--powered type: A unit--mounted transformer is
factory--installed to stepdown the main power supply
voltage to the unit to 115--v at the duplex receptacle. This
option also includes a manual switch with fuse, located in
a utility box and mounted on a bracket behind the
convenience outlet; access is through the unit’s control
box access panel. See Fig. 17.
The primary leads to the convenience outlet transformer
are not factory-- connected. Selection of primary power
source is a customer--option. If local codes permit, the
transformer primary leads can be connected at the
line--side terminals on the unit--mounted non--fused
disconnect or HACR breaker switch; this will provide
service power to the unit when the unit disconnect switch
or HACR switch is open. Other conne ction methods will
result in the convenience outlet circuit being de--energized
when the unit disconnect or HACR switch is open. See
Fig. 19.
Duty Cycle: the unit--powered conveni ence outlet has a
duty cycle limitation. The transformer is intended to
provide power on an intermittent basis for service tools,
lamps, etc; it is not intended to provide 15--amps loading
for continuous duty loads (such as electric heaters for
overnight use). Observe a 50% limit on circuit loading
above 8--amps (i.e., limit loads exceeding 8--amps to 30
minutes of operation every hour).
Test the GFCI receptacle by pressing the TEST button on
C08283
UNIT
VOLTAGE
208,
230
460480
575600
CONNECTASPRIMARY
240
CONNECTIONS
L1: RED +YEL
L2: BLU + GRA
L1: RED
Splice BLU +
YEL
L2: GRA
L1: RED
L2: GRA
TRANSFORMER
TERMINALS
H1 + H3
H2 + H4
H1
H2 + H3
H4
H1
H2
Fig. 19 -- Powered Convenience Outlet Wiring
Using unit--mounted convenience outlets: Units with
unit--mounded convenience outlet circuits will often
require that two disconnects be opened to de--energize all
power to the unit. Treat all units as electrically energized
until the convenience outlet power is also checked and
de--energization is confirmed. Observe National Electrical
Code Article 210, Branch Circuits, for use of convenience
outlets.
Fuse on power type: The factory fuse is a Bussman
“Fusetron” T--15, non--renewable screw--in (Edison base)
type plug fuse.
Factory--Option Thru--Base Connections —
1
This service connection kit consists of a
3
bulkhead connector and a
/4--in electrical bulkhead
/2--in electrical
connector, all factory--installed in the embossed (raised)
section of the unit basepan in the condenser section. The
1
/2--in bulkhead c onnector ena bles the low--voltage control
wires to pass through the basepan. The
3
/4--in electrical
bulkhead connector al lows the high--voltage power wires
to pass through the basepan. See Fig. 20.
Check tightness of connector lock nuts before connecting
electrical conduits.
50TCQA
13
LOW VOLTAGE
CONDUIT
CONNECTOR
HIGH VOLTAGE
CONDUIT
CONNECTOR
Fig. 20 -- Thru-- Base Connection Fittings
Field--supplied and field--installed liquidtight conduit
connectors and conduit may be attached to the connectors
on the basepan. Pull correctly rated high voltage and low
voltage through appropriate conduits. Connect the power
50TCQA
conduit to the internal disconnect (if unit is so equipped)
or to the external disconnect (through unit side panel). A
hole must be field cut in the main control box bottom on
the left side so the 24--v control connections can be made.
Connect the control power conduit to the unit control box
at this hole.
Units without Thru--Base Connections —
1. Install power wiring conduit through side panel openings. Install conduit between disconnect and control
box.
2. Install power li nes to terminal connections as shown
in Fig. 16.
All Units —
Voltage to compressor terminals during operation must be
within voltage range indicated on unit nameplate. See
Table 10. On 3--phase units, voltages betwee n phases must
be balanced within 2% and the current within 10%. Use
the formula shown in the legend for Table 10, Note 2 (see
page 44) to determine the percent of voltage imbalance.
Operation on improper line voltage or excessive phase
imbalance constitutes abuse and may cause damage to
electrical components. Such operation would invalidate
any applicable Carrier warranty.
Field Control Wiring —
C08637
control the reversing valve operation. If using an
electronic thermostat, configure it for “non--heat pump”
operation. Locate the thermostat accessory on a solid wall
in the conditioned space to sense average temperature in
accordance with the thermostat installation instructions.
If the thermostat contains a logic circuit requiring 24--v
power, use a thermostat cable or equivalent single leads of
different colors with minimum of seven leads. If the
thermostat does not require a 24--v source (no “C”
connection required), use a thermostat cable or equivalent
with minimum of six leads. Check the thermostat
installation instructions for additional features which
might require additional conductors in the cable.
For wire runs up to 50 ft. (15 m), use no. 18 AWG
(American Wire Gage) insulated wire (35_C minimum).
For50to75ft.(15to23m),useno.16AWGinsulated
wire (35_C minimum). For over 75 ft. (23 m), use no. 14
AWG insulate d wire (35_C minimum). All wire sizes
larger than no. 18 AWG cannot be directly connected to
the thermostat and will require a junction box and splice
at the thermostat.
Terminal
X
C
G
W2
W1
Y2
Y1
R
Central
Board
T
H
E
R
M
O
S
T
A
T
C09012
Typical
Thermostat
Connections
C
G
W2
W1
O/B/Y2
(Note 1)
Y1
R
Note 1: Typical multi-function marking. Follow manufacturer’s configuration
instructions to select Y2. Do not configure for O output.
Note 2: W2 connection not required on units without electric heating.
Field Wiring
(Note 2)
Fig. 21 -- Typical Low--Voltage Control Connections
The 50TCQA unit requires an external temperature
control device.This device can be a thermostat
(field--supplied) or a PremierLink controller (available as
factory--installed option or as field--installed accessory, for
use on a Carrier Comfort Network or as a stand alone
control) or theRTU--MP Controller for Building
ManagementSystemsusingnon--CCNprotocols
(RTU--MP is available as a factory--installed option only).
Thermostat —
InstallaCarrier-- approvedaccessory2stage
Cooling/Heating thermostat according to installation
instructions included with the accessory. The 50TCQ
models do not require a thermostat with an O function to
Unit without thru--base connection kit —
Pass the thermostat control wires through the hole
provided in the corner post; then feed the wires through
the raceway built into the corner post to the control box.
Pull the wires over to the terminal strip on the upper--left
corner of the Central Terminal Board (CTB). See Fig. 22.
NOTE:If thru--the--bottom connections accessory is
used, refer to the accessory installation instructions for
information on routing power and control wiring.
Heat Anticipator Settings —
Set heat anticipator settings at 0.14 amp for the first stage
and 0.14 amp for second--stage heating, when available.
14
RACEWAY
DISCONNECT MOUNTING
LOCATION
HOLE IN END PANEL (HIDDEN)
Fig. 22 -- Field Control Wiring Raceway
C08027
UNIT BLOCK-OFF
PAN EL
Fig. 23 -- Typical Access Panel Location
Not all available heater m odules may be used in every
OUTDOOR
ACCESS PANEL
unit. Use only those heater modules that are UL listed for
Electric Heaters
50TCQ units may be equipped with field--installed
accessory electric heaters. The heaters are modular in
design, with heater frames holding open coil resistance
wires strung through ceramic insulators, line--break limit
switches and a c ontrol contactor. One or two heater
modules may be used in a unit.
Heater module s are installed in the compartment below
the indoor (supply) fan outlet. Access is through the
use in a specific size unit. Refer to the label on the unit
cabinet for the list of approved heaters.
Unit heaters are marked with Heater Model Numbers. But
heaters are ordered as and shipped in cartons marked with
a corresponding heater Sales Package part number. See
Table 2 for correlation between heater Model Number and
Sales Package part number.
NOTE: The value in position 9 of the part number differs
between the sales package part number (value is 1 or 3)
and a bare heater model number (value is 0).
indoor access panel. Heater modules slide into the
compartment on tracks along the bottom of the heater
opening. See Fig. 23, Fig. 24 and Fig. 25.
Table 2 – Heater Model Number
Bare Heater Model NumberCRHEATER001A00
INDOOR
ACCESS
PAN EL
C08133
50TCQA
Heater Sales Package PNO
Includes:
Bare Heater
Carton and packing materials
Installation sheet
CRHEATER101A00
DISCONNECT
MOUNTING
LOCATION
MAIN
CONTROL
BOX
EMT OR RIGID CONDUIT
(FIELD-SUPPLIED)
BRACKET AND
CONDUIT
DRIP BOOT
SINGLE
POINT BOX
SINGLE POINT
BOX
MOUNTING
SCREW
CONTROL WIRE TERMINAL BLOCK
HEATER
MODULE
(LOCATION 1)
CENTER
POST
HEATER
MODULE
(LOCATION 2)
MANUAL RESET
LIMIT SWITCH
HEATER
COVERS
HEATER
MOUNTING
BRACKET
C08134
Fig. 24 -- Typical Component Location
15
Fig. 25 -- Typical Module Installation
TRACK
FLANGE
C08135
CONTROL
BOX
2
1
1
1
2
13
3
BUSHING
SINGLE
POINT BOX
MOUNTING
SCREWS
DRIP BOOT
BRACKET
MOUNTING
SCREWS
POWER
WIRES
FOAM
BUSHING
HEATER
RELAYS
HEATER
MOUNTING
SCREWS
Fig. 26 -- Typical Single Point Installation
21
23
11
13
A
L
L
I
E
D
P
A
C
O
R
P
.
MO
D
E
L
N
O
.
O
D
ER
I
A
L
N
O.
2
2
.
2
ISTED
AI
R
NDITIONING
1
2
3
UIP
ACCESS
3
4
6
N
.
3
P
/
N
2-
5
6
10-
REV
4
C08136
50TCQA
Single Point Boxes and Supplementary Fuses — When
the unit MOCP device value exceeds 60--A, unit--mounted
supplementary fuses are required for each heater circuit.
These fuses are included in accessory Single Point Boxes,
with power distribution and fuse blocks. The single point
box will be installed directly under the unit control box,
just to the left of the partition separating the indoor
section (with electric heaters) from t he outdoor section.
The Single Point Box has a hinged access cover. See
Fig. 26. The Single Point Box also includes pigtails to
complete the wiring between the Single Point Box and the
unit’s main control box terminals. Refer to the accessory
heater and Single Point Box installation instructions for
details on tap connections.
DEFROST
BOARD
E-HEAT
P3-3
All fuses on 50TCQ units are 60--A. (Note that all heaters
are qualified for use with a 60--A fuse, regardless of actual
heater ampacity, so only 60--A fuses are necessary.)
Single Point Boxes without Fuses — Refer to accessory
heater and Single Point Box installation instructions for
details on tap connections.
Low--VoltageControlConnections—Runthe
low--voltage control leads from the heater module(s) -VIO and BRN (two of each if two modules are installed;
identify for Module #1) -- to the 4--pole terminal board
TB4 located on the heater bulkhead to the left of Heater
#1. Connect the VIO leads from Heater #1 and Heater #2
to terminal TB4--1. Connect the BRN leads to terminal
TB4--3. See Fig. 27.
ORN
BRN
ORNBRN
TB4
Field
Connections
13
VIOBRN BRN
VIO
Elec Htr
VIOHR2
VIOBRN
BRN
HR1
HR1: On Heater 1 in Position #1
HR2: On Heater 2 in Position #2 (if installed)
Fig. 27 -- Accessory Electric Heater Control Connections
16
C09013
PremierLinkt (Factory--Option) —
50TCQA
C08199
Fig. 28 -- PremierLink Controller
The PremierLink controller (see Fig. 28) is compatible
with Carrier Comfort Networkr (CCN) devices. This
control is designed to allow users the access and ability to
change factory--defined settings, thus expanding the
function of the standard unit control board. CCN service
access tools include System Pilot (TM), Touch Pilot (TM)
and Service Tool. (Standard tier display t ools Navigatort
and Scrolling Marquee are not suitable for use with latest
PremierLink controller (Version 2.x).)
The PremierLink control is factory--mounted in the
50TCQ unit’s main control box to the left of t he Central
Terminal Board (CTB). Factory wiring is completed
through harnesses connected to the CTB thermostat . Field
connections are made at a 16--pole terminal block (TB1)
located on the bottom shelf of the unit control box in front
of the PremierLink controller. The factory--installed
PremierLink control includes the supply--air temperature
(SAT) sensor. The outdoor air temperature (OAT) sensor is
included in the FIOP/accessory EconoMi$ert2 package.
The PremierLink controller requires the use of a Carrier
electronic thermostat or a CCN connection for time
broadcast to initiate its internal timeclock. This is
necessary for broadcast of time of day functions
(occupied/unoccupied).
NOTE:PremierLink controller is shipped in Sensor
mode. To be used with a thermostat, the PremierLink
controller must be configured to Thermosta t mode. Refer
to PremierLink Configuration instructions for Operating
Mode.
SupplyAirTemperature(SAT)Sensor—On
FIOP--equipped 50TCQ unit, the unit is supplied with a
supply--air temperature (SAT) sensor (33ZCSENSAT).
This sensor is a tubular probe type, approx 6--inche s
(12.7 mm) in length. It is a nominal 10--k ohm thermistor.
The SAT is factory-- wired. The SAT probe is wire-- tied to
the supply--air opening (on the horizontal opening end) in
its shipping position. Remove the sensor for installation.
Re--position the sensor in the flange of the supply--air
opening or in the supply air duct (as required by local
1
codes). Drill or punch a
/2--in. hole in the flange or duct.
Use two field--supplied, self--drilling screws to secure the
sensor probe in a horizontal orientation. See Fig. 29.
SUPPLY AIR
TEMPERATURE
SENSOR
SUPPLY AIR
RETURN AIR
ROOF
CURB
C08200
Fig. 29 -- Typical Mounting Location for Supply Air
Temperature (SAT) Sensor on Small Rooftop Units
NOTE:Refer to Form 33CS--58SI for complete
PremierLink configuration, operat ing sequences and
troubleshooting information. Have a copy of this manual
available at unit start--up.
NOTE: The sensor must be mounted in the discharge
airstream downstream of the cooling coil and any heating
devices. Be sure the probe tip does not come in contact
with any of the unit’s heater surfaces.
17
50TCQA
Fig. 30 -- PremierLink Wiring Schematic
18
C09014
Outdoor Air Temperature (OAT) Sensor — The OAT is
factory--mountedintheEconoMi$er2(FIOPor
accessory). It is a nominal 10k ohm thermistor attached to
an eyelet mounting ring.
EconoMi$er2 — T he PremierLink control is used with
EconoMi$er2 (option or accessory) for outdoor air
management. The damper position is controlled directly
by the PremierLink control; EconoMi$er2 has no internal
logic device.
Outdoor air management functions can be enhanced with
field-- installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors)
Space CO
Outdoor air CO
sensor
2
sensor
2
Refer to Table 3 for accessory part numbers.
Field connections — Field connections for accessory
sensor and input devices are made at the 16--pole terminal
block (TB1) locat ed on the control box bottom shelf in
front of the PremierLink control (See Fig. 30). Some input
devices also require a 24--vac signal source; connect at
CTB terminal R at “THERMOSTAT” connection strip for
this signal source. See connections figures on following
pages for fiel d connection locations (and for continued
connections at the PremierLink board inputs).
Table 4 provides a summary of field connections for units
equipped with Space Sensor. Table 5 provides a summary
of field c onnections for units equipped with Space
Thermostat.
Connect T--55 -- See Fig. 31 for typical T--55 internal
connections. Connect the T--55 SEN terminals to TB1
terminals 1 and 3 (see Fig. 32).
TB1PL
SENJ6-7
SEN
1
3
J6-6
C08212
Fig. 32 -- PremierLink T--55 Sensor
Connect T--56--See Fig.33 for T--56 internal
connections. Install a jumper between SEN and SET
terminals as illustrated. Connect T--56 terminals to TB1
terminals 1, 3 and 5 (see Fig. 34).
45
SEN
61
RED(+)
WHT(GND)
BLK(-)
SET
BLK
(T56)
BRN (GND)
BLU (SPT)
CCN COM
SENSOR WIRING
JUMPER
TERMINALS
AS SHOWN
2
3
SW1
50TCQA
SpaceSensors--ThePremierLinkcontrolleris
factory--shipped configured for Space Sensor Mode. A
Carrier T--55 or T--56 space sensor must be used. T --55
space temperature sensor provides a signal of space
temperature to the PremierLink control. T--56 provides
same space temperature signal plus it allows for
adjustment of space temperature setpoints from the face of
the sensor by the occupants.
2
SW1
3
45
SEN
61
RED(+)
WHT(GND)
BLK(-)
BRN (GND)
BLU (SPT)
CCN COM
SENSOR WIRING
C08201
Fig. 31 -- T--55 Space Temperature Sensor Wiring
CoolWarm
C08202
Fig. 33 -- T--56 Internal Connections
TB1PL
SENJ6-7
SEN
Jumper
1
TB1
3
PL
J6-6
SET
SET
5
J6-5
C08213
Fig. 34 -- PremierLink T--56 Sensor
Connect Thermostat — A 7--wire thermostat connection
requires a 24--v power source and a common connection.
Use the R and C terminals on the CTB’s THERMOSTAT
connection strip for these. Connect the thermostat’s Y1,
Y2, W1, W2 and G terminals to PremierLink TB1 as
shown in Fig. 35.
If the 50TCQ unit is equipped with factory--installed
smoke detector(s), disconnect the factory BLU lead at
TB1--6 (Y2) before connecting the thermostat. Identi f y the
BLU lead originating at CTB--DDC--1; disconnect at
TB1-- 6 and tape off. Confirm that the second BLU lead at
TB1-- 6 remains connected to PremierLink J4-- 8.
19
SPACE
THERMOSTAT
CTB
THERMOSTAT
R
R
TB1
GJ4-12
Y1
Y2
W1
W2
C
2
4
6
8
10
C
CTB
THERMOSTAT
Fig. 35 -- Space Thermostat Connections
50TCQA
OUTDOOR AIR
APPLICATION
Differential Dry Bulb
Tem p era t u re wi t h
PremierLink
(PremierLink requires
4 --- 2 0 m A A c t u a to r)
Single Enthalpy with
PremierLink
(PremierLink requires
4 --- 2 0 m A A ct ua t o r )
Differential Enthalpy
with PremierLink
(PremierLink requires
4 --- 2 0 m A A ct ua t o r )
NOTES:
CO
Sensors (Optional):
2
33ZCSENCO2 --- Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.
33ZCASPCO2 --- Aspirator box used for duct --- mounted CO
33ZCT55CO2 --- Space temperature and CO
33ZCT56CO2 --- Space temperature and CO
TEMPERATURE
SENSOR
I nc lu d e d ---
CRTEMPSN001A00
I nc lu d e d ---
Not Used
I nc lu d e d ---
Not Used
Table 3 – PremierLink Sensor Usage
RETURN AIR
TEMPERATURE
SENSOR
R eq u i r e d ---
33ZCT55SPT
or equivalent
---
---
room sensor.
room sensor with override.
2
room sensor with override and setpoint.
2
2
ENTHALPY SENSOR
PL
J4-10
J4-8
J4-6
J4-4
C08119
OUTDOOR AIR
------
R eq u i r e s ---
HH57AC077
or equivalent
R eq u i r e s ---
HH57AC077
or equivalent
RETURN AIR
ENTHALPY SENSOR
---
R eq u i r e s ---
HH57AC078
or equivalent
20
Table 4 – Space Sensor Mode
TB1 TERMINALFIELD CONNECTIONINPUT SIGNAL
1T5 5 --- S E N/ T 5 6 --- S E NAnalog (10k thermistor)
2RMTOCCDiscrete, 24VAC
3T5 5 --- S E N/ T 5 6 --- S E NAnalog (10k thermistor)
4CMPSAFEDiscrete, 24VAC
5T56 --- SETAnalog (10k thermistor)
6FSDDiscrete, 24VAC
7LOOP---PWRAnalog, 24VDC
8SPSDiscrete, 24VAC
9IAQ --- SENA na lo g, 4 --- 2 0 m A
10FILTERDiscrete, 24VAC
11I A Q --- C O M / O A Q --- C O M / R H --- C O MA na lo g, 4 --- 2 0 m A
12CCN + (RED)Digital,,5VDC
13OAQ---SEN/RH --- SENA na lo g, 4 --- 2 0 m A
14CCN Gnd (WHT)Digital, 5VDC
15AUX OUT(Power Exhaust)(Output)Discrete 24VAC
16CCN --- (BLK)Digital, 5VDC
LEGEND:
T 5 5--- S p a c e Te m p e r a t u r e S e n s o rFS D --- F i r e S h u t d ow n
T 5 6--- S p a c e Te m p e r a t u r e S e n s o rIA Q --- I n d o o r A i r Q u a l it y ( C O
CCN--- Carrier Comfort Network (communication bus)OAQ --- Outdoor Air Quality (CO
C M P S A F E--- C o m p r e s s o r S a f e t yRH --- R e l a t iv e H u m i d i t y
F I LT E R--- D i r t y F i l t e r S w i t c hSF S --- S u p p l y Fa n S t a t u s
50TCQA
)
2
)
2
Table 5 – Thermostat Mode
TB1 TERMINALFIELD CONNECTIONINPUT SIGNAL
1RAT SENAnalog (10k thermistor)
2GDiscrete, 24VAC
3RAT SENAnalog (10k thermistor)
4Y1Discrete, 24VAC
5
6Y2Discrete, 24VAC
7LOOP---PWRAnalog, 24VDC
8W1Discrete, 24VAC
9I A Q --- S E NAnalog, 4 - --20mA
10W2Discrete, 24VAC
11I A Q --- C O M / O A Q --- C O M / R H --- C O MAnalog, 4 --- 20mA
12CCN + (RED)Digital, 5VDC
13O A Q --- S E N / R H --- S E NAnalog, 4 ---20mA
If the 50TCQ unit has an economizer system and
free--cooling operation is required, a sensor representing
Return AirTemperature mustalso beconnected
(field--supplied and installed). This sensor may be a T--55
Space Sensor (see Fig. 31) installed in the space or in the
return duct, or it may be sensor PNO 33ZCSENSAT,
installed in the return duct. Connect this sensor to TB1--1
and TB1--3 per Fig. 32.
Configure the unit for Thermostat Mode — Connect to the
CCN bus using a CCN service tool and navigate to
PremierLink Configuration screen for Operating Mode.
Default setting is Sensor Mode (value 1). Change the
value to 0 to reconfigure the controller for Thermostat
Mode.
Return Air Enthalpy Sensor — Mount the return--air
enthalpy sensor (33CSENTSEN) in the return--air section
of the economizer. The return air sensor is wired to the
enthalpy controller (33CSENTHSW). See Fig. 37.
24V
– 4-20
Main
+ VDC
Out
GND
LOW
RED
BLK
GRA
ESL
ECONO
MOTOR
When the PremierLink is configured for T hermostat
Mode, these functions are not available: Fire Shutdown
(FSD), Remote Occupied (RMTOCC), Compressor Safety
(CMPSAFE), Supply Fan Status (SFS), and Filter Pressure
Switch (FILTER).
50TCQA
Economizer controls —
Outdoor Air Enthalpy Control (PNO 33CSENTHSW) --
The enthalpy control (33CSENTHSW) is available as a
field--installed accessory to be used with the EconoMi$er2
damper system. The outdoor ai r entha lpy sensor is part of
the enthalpycontrol.(Theseparatefield--installed
accessory return air enthalpy sensor (33CSENTSEN) is
required for differential enthalpy control. See Fig. 36.)
Locate the enthalpy control in the economizer next to the
Actuator Motor. Locate two GRA leads in the factory
harness and connect the gray lead labeled “ESL” to the
terminal labeled “LOW”. See Fig. 36. Connect the
enthalpy control power input terminals to economizer
actuator power leads RED (connect to 24V) and BLK
(connect to GND).
Enthalpy
Switch
24V
GND
LOW
RED
BLK
GRA
ESL
7
ECONO
MOTOR
CTB
ECON
+ 24-36
VDC In
– 4-20 Main
Out
C09027
Fig. 37 -- Outside and Return Air Enthalpy Sensor
Wiring
To wire the return air enthalpy sensor, perform the
following:
1. Use a 2--conductor, 18 or 20 AWG, twisted pair c able
to connect the return air enthalpy sensor to the enthalpy controller.
2. Connect the field--supplied RED wire to (+) spade
connector on the return air enthalpy sensor and the
(+) terminal on the enthalpy controller. Connect the
BLK wire to (--) spade connector on the return air enthalpy sensor and the (--) terminal on the enthalpy
controller.
Indoor Air Quality (CO
sensor) — The indoor air quality
2
sensor accessory monitors space carbon dioxide (CO
levels. This information is used to monitor IAQ levels.
Several types of sensors are available, for wall mounting
in the space or in return duct, with and without LCD
display, and in combination with space temperature
sensors. Sensors use infrared technology to measure the
levels of CO
The CO
present in the space air.
2
sensors are all fac tory set for a range of 0 to
2
2000 ppm and a linear mA output of 4 to 20. Refer to the
instructions supplied with the CO
sensor for electrical
2
requirements and terminal locations. See Fig. 38 for
typical CO
sensor wiring schematic.
2
)
2
Factory Wiring Harness
C09026
Fi g. 36 -- Enthalpy Switch (33CSENTHSW) Connections
The outdoor enthalpy changeover setpoint is set at the
enthalpy controller.
Differential Enthalpy Control — Differential enthalpy
control is provided by sensing and comparing the outside
air and return air enthalpy conditions. Install t he outdoor
air enthalpy control as described above. Add a nd install a
return air enthalpy sensor.
22
HG
+
24 VAC
OR
-
24 VDC
2
1
J3J4
Refer to Form 33CS--58SI, PremierLi nk Installation,
Start--up, and Configuration Instructions, for detailed
configuration information
Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus
weatherproof enclosure) — The outdoor air CO
designed to monitor carbon di oxide (CO
2
sensor is
2
) levels in the
outside ventilation air and interface with the ventilation
+
0-10VDC
-
SIG COM
+
4-20mA
ALARM
NC
COM
RELAY
}
CONTACTS
NO
5
1
4
32
7
6
8
damper in an HVAC system. The OAQ sensor is packaged
with an outdoor cover. See Fig. 40. The outdoor air CO
sensor must be located in the economizer outside air hood.
2
C08635
Fig. 38 -- Indoor/Outdoor Air Quality (CO2)Sensor
(33ZCSENCO2) -- Typical Wiring Diagram
To accurately monitor the quality of the air in the
conditioned air space, locate the sensor near a return--air
grille (if present) so it senses the concentration of CO
leaving the space. The sensor should be mounted in a
location to avoid direct breath contact.
Do not mount the IAQ sensor in drafty areas such as near
supply ducts, open windows, fans, or over heat sources.
Allow at least 3 ft (0.9 m) between the sensor and any
corner. Avoid mounting the sensor where it is influenced
by the supply air; the sensor gives inaccurate readings if
the supply air is blown directly onto the sensor or if the
supply air does not have a chance to mix with the room air
before it is drawn into the return airstream.
Wiring the Indoor Air Quality Sensor —
For each sensor, use two 2--conductor 18 AWG (American
Wire Gage) twisted--pair cables (unshielded) to connect
the separate isolated 24 vac power source to the sensor
and to connect the sensor to the control board terminals.
2
COVER REMOVEDSIDE VIEW
Fig. 40 -- Outdoor Air Quality Sensor Cover
Wiring the Outdoor Air CO
Sensor — A dedicated power
2
supply is required for this sensor. A two--wire cable is
required to wire the dedicated power supply for the sensor.
The two wires should be connected to the power supply
and terminals 1 and 2.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
OAQ sensor. See Fig. 38. Connect t he 4 to 20 mA
terminal to the TB1--13 terminal of the 50TCQ. Connect
the SIG COM terminal to the TB1--11 terminal of the
50TCQA. See Fig. 41.
50TCQA
C07135
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
sensor. See Fig. 38. Connect the 4--20 mA terminal to
terminal TB1--9 and connect the SIG COM terminal to
terminal TB1--11. See Fig. 39.
IAQ Sensor
SENJ5-5
COM
24 VAC
TB1
9
TB1
11
PL
J5-3
C08636
Fig. 39 -- Indoor CO2Sensor (33ZCSENCO2)
Connections
OAQ Sensor/RH Sensor
SENJ5-2
COM
24 VAC
TB1
13
TB1
11
PL
J5-3
C08275
Fig. 41 -- Outdoor CO2Sensor Connections
Smoke Detector/Fire Shutdown (FSD) — This function is
available only when PremierLink is c onfigured for
(Space) Sensor Mode. The unit is factory--wired for
PremierLink FSDoperation whenPremierLinkis
factory--installed.
23
On 50TCQ units equipped with factory--instal led Smoke
Detector(s), the smoke detector controller implements the
unit shutdown through its NC contact set connected to the
unit’s CTB input. The FSD function is initiated via the
smoke detector’s Alarm NO contact set. The PremierLink
communicates the smoke detector’s tripped status to the
CCN building control. See Fig. 30, the PremierLink
wiring schematic.
Filter Status Switch — This function is available only
when PremierLink is configured for (Space) Sensor Mode.
PremierLink control can monitor return filter status in two
ways: By monitoring a field--supplied/installed filter
pressure switch or via supply fan runtime hours.
Using switch input: Install the dirty filter pressure switch
according to switch manufacturer’s instructions, to
measure pressure drop across the unit’s return filters.
Connect one side of the switch’s NO contact set to CTB’s
THERMOSTAT-- R terminal. Connect the other side of the
50TCQA
NO contact set to TB1-- 10. Setpoint for Dirty Filter is set
at the switch. See Fig. 42.
Fan (Pressure) Switch (NO, close on rise in pressure)
CTB
Thermostat
R
TB1
8
PL
J4-6
C08118
Fig. 43 -- PremierLink Wiring Fan Pressure Switch
Connection
Remote Occupied Switch — The PremierLink control
permits a remote timeclock to override the control’s
on--board occupancy schedule a nd place the unit into
Occupied mode. This function may also provide a “Door
Switch” time delay function that will terminate cooling
and heating functions after a 2--20 minute delay.
Connect one side of the NO contact set on the timeclock
to CTB’s THERMOSTAT--R terminal. Connect the other
side of the timeclock contact to the unit’s TB1--2 terminal.
Filter Switch (NO, close on rising pressure (high drop))
CTB
Thermostat
R
TB1
10
PL
J4-4
C08216
Fig. 42 -- PremierLink Filter Switch Connection
When the filter switch’s NO contact set closes as filter
pressure drop increases (indicating dirt--laden filters), the
input signal to PremierLink causes the filter status point to
read “DIRTY”.
Using Filter Timer Hours: Refer to Form 33CS-- 58SI for
instructions on using the PremierLink Configuration
screens and on unit alarm sequence.
Supply Fan Status Switch — The PremierLink control can
monitorsupplyfanoperationthrougha
field-- supplied/installed differential pressure switch. This
sequence will prevent (or interrupt) operation of unit
cooling, heating and economizer functions until the
pressure switch contacts are closed indicating proper
supply fan operation.
Remote Occupied
Time Clock
CTB
Thermostat
R
TB1
2
PL
J4-12
C08214
Fig. 44 -- PremierLink Wiring Remote Occupied
Refer to Form 33CS--58SI for additional information on
configuring the PremierLink control for Door Switch
timer function.
Power Exhaust (output) -- Connect the accessory Power
Exhaust contactor coils(s) per Fig. 45.
Space Relative Humidity Sensor — The RH sensor is not
used with 50TCQ models at this time.
Power Exhaust
PEC
TAN
TB1
15
PL
J8-3
CTB
THERMOSTAT
GRA
C
C08120
Fig. 45 -- PremierLink Power Exhaust Output
Connection
Install the differential pressure switch in the supply fan
section according to switch manufacturer’s instructions.
Arrange the switch contact to be open on no flow and to
close as pressure rises indicating fan operation.
Connect one side of the switch’s NO contact set to CTB’s
THERMOSTAT-- R terminal. Connect the other side of the
NO contact set to TB1--8. Setpoint for Supply Fan Status
is set at the switch. See Fig. 43.
CCN Communication Bus — The PremierLink controller
connects to the bus in a daisy chain arrangement.
Negative pins on each component must be connected to
respective negative pins, and likewise, positive pins on
each component must be connected to respective positive
pins. The controller signal pins must be wired to the signal
ground pins. Wiring connections for CCN must be made
at the 3--pin plug.
24
At any baud (9600, 19200, 38400 baud), the number of
controllers is limited to 239 devices maximum. Bus length
may not exceed 4000 ft, with no more than 60 total
devices on any 1000--ft section. Optically isolated RS--485
repeaters are required every 1000 ft.
NOTE: Carrier device default is 9600 band.
COMMUNICATION BUS WIRE SPECIFICATIONS —
The CCN Communi cation Bus wiring is field--supplied
and field--installed. It consists of shielded 3--conductor
cable with drain (ground) wire. The cable selected must
be identical to the CCN Communication Bus wire used for
the entire network.
See Table 6 for recommended cable.
Connecting CCN bus:
NOTE: When connecting the communication bus cable,
a color codesystemforthe entirenetwork i s
recommended to simplif y installation and checkout. See
Table 7 for the recommended color code.
Table 7 – Color Code Recommendations
SIGNAL TYPE
+Red1
GroundWhite2
---Black3
CCN BUS WIRE
COLOR
CCN PLUG PIN
NUMBER
Table 6 – Recommended Cables
MANUFACTURERCABLE PART NO.
Alpha2413 or 5463
AmericanA22503
Belden8772
Columbia02525
NOTE: Conduc tors and drain wire must be at l east 20
AWG, stranded, and tinned copper. Individual conductors
must be insulated with PVC, PVC/nylon, vinyl, Teflon, or
polyethylene. An aluminum/polyester 100% foil shield
and an outer jacket of PVC, PVC/nylon, chrome vinyl, or
Teflon with a minimum operating temperature range of
-- 2 0 _Cto60_C is required. Do not run communication
wire in the same conduit as or next to any AC voltage
wiring.
The communication bus shields must be tied together at
each system element. If the communication bus is entirely
within one building, the resulting c ontinuous shield must
be connecte d to ground at only one single point. If the
communication bus cable exits from one building and
enters another building, the shields must be connected to
the grounds at a lightning suppressor in each building (one
point only).
Connect the CCN (+) lead (typically RED) to the unit’s
TB1--12 terminal. Connect the CCN (ground) lea d
(typically WHT) to the unit’s TB1-- 14 terminal. Connect
the CCN (--) lead (typically BLK) to the unit’s TB1--16
terminal. See Fig. 46.
CCN Bus
+ (RED)
GND (WHT)
– (BLK)
TB1
12
TB1
14
TB1
16
PL
J2-1
J2-2
J2-3
C08276
Fig. 46 -- PremierLink CCN Bus Connections
50TCQA
25
RTU--MP control system
The RTU--MP controller, see Fig. 47, provides expanded
stand--aloneoperation oftheHVAC systemplus
connection a nd control through communication with
several Building Automation Systems (BAS) through
popular third--party network systems. The available
network systems are BACnet MP/TP, Modbus and
Johnson J2. Communication with LonWorks is also
possible by adding an accessory interface card to the
RTU--MP. Selection of the communication protocol and
baud rate are made at on--board DIP switches.
50TCQA
The RTU--MP control is factory--mounted in the 50TCQ
unit’s main control box, to the left of the CTB. See
Fig. 48. Factory wiring is completed through ha rnesses
connected to the CTB. Field connections for RTU--MP
sensors will be made at the Phoenix connectors on the
RTU--MP board. The factory--installed RTU--MP control
includes the supply--air temperature (SAT ) sensor. The
outdoor air temperature (OAT) sensor is included in the
FIOP/accessory EconoMi$er2 package.
Refer to Table 8, RTU--MP Controller Inputs and Outputs
for locations of all connections to the RTU--MP board.
Fig. 47 -- RTU--MP Multi--Protocol Control Board
Fig. 48 -- 50TCQ Control Box Component Locations
26
C07129
C08652
50TCQA
Fig. 49 -- RTU--MP System Control Wiring Diagram
27
C09015
Table 8 – RTU--MP Controller Inputs and Outputs
POINT NAME
Space Temperature SensorsptsensAI (10K Thermistor)J 2 0 --- 1 , 2
Supply Air TemperaturesatAI (10K Thermistor)J2 --- 1, 2
Local Outside Air Temperature SensoroatsensAI (10K Thermistor)J2---3, 4
Space Temperature Offset PotsptopotAI (100K Potentiometer)J 2 0 --- 3
Indoor Air QualityiaqA I ( 4 --- 2 0 m a )J4---2, 3
Outdoor Air QualityoaqA I ( 4 --- 2 0 ma )J4 --- 5, 6
Safety Chain FeedbacksafetyDI (24 VAC)J1---9
Compressor SafetycompstatDI (24 VAC)J1 --- 2
Fire ShutdownfiredownDI (24 VAC)J 1 --- 1 0
Enthalpy SwitchenthalpyDI (24 VAC)J2---6, 7
Humidistat Input StatushumstatDI (24 VAC)J5---7, 8
Space Relative HumiditysprhAI (4 --- 2 0 m a)
50TCQA
Outside Air Relative HumidityoarhA I ( 4 --- 2 0 m a )
LEGEND
AI --- A n a l o g I n p u t
AO --- A n a lo g O u t p u t
DI --- D i s c r e t e I n p u t
DO --- Discrete Output
* These inputs (if installed) take the place of the default input on the specific channel according to schematic.
P a r a l l e l p i n s J 5 --- 1 = J 2 --- 6 , J 5 --- 3 = J 1 --- 1 0 , J 5 --- 5 = J 1 --- 2 a r e u s ed f o r f i e l d --- i n s t a ll a t i o n .
BACnet OBJECT
NAME
INPUTS
CONFIGURABLE INPUTS*
OUTPUTS
TYPE OF I/O
CONNECTION PIN
NUMBERS
J 4 --- 2 , 3 or J 4 --- 5 ,6
J5--- 1,2 or J5 --- 3,4 or
J5 5,6 or J5 ---7,8
The RTU--MP controller requires the use of a Carrier
space sensor. A standard thermostat cannot be used with
the R TU--MP system.
SupplyAirTemperature(SAT)Sensor--On
FIOP--equipped 50TCQ unit, the unit is supplied with a
supply--air temperature (SAT) sensor (33ZCSENSAT).
This sensor is a tubular probe type, approx 6--inches (12.7
mm) in length. It is a nominal 10--k ohm thermistor.
The SAT is factory-- wired. The SAT probe is wire-- tied to
the supply--air opening (on the horizontal opening end) in
its shipping position. Remove the sensor for installation.
Re--position the sensor in the flange of the supply--air
opening or in the supply air duct (as required by local
1
codes). Drill or punch a
/2--in. hole in the flange or duct.
Use two field--supplied, self--drilling screws to secure the
sensor probe in a horizontal orientation. See Fig. 29.
Outdoor Air Temperature (OAT) Sensor -- T he OAT is
factory--mountedintheEconoMi$er2(FIOPor
accessory). It is a nominal 10k ohm thermistor attached to
an eyelet mounting ring.
EconoMi$er2 -- The RTU--MP cont rol is used with
EconoMi$er2 (option or accessory) for outdoor air
management. The damper position is controlled directly
by the RTU--MP control; EconoMi$er2 has no internal
logic device.
Outdoor air management functions can be enhanced with
field-- installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors)
Space CO
Outdoor air CO
sensor
2
sensor
2
Field Connections -- Field connections for accessory
sensors and input devices are made the RTU--MP, at plugs
J1, J2, J4, J5, J11 and J20. All field control wiring that
connects to the RTU--MP must be routed through the
raceway built into the corner post as shown in Fig. 22.
28
The raceway provides the UL required clearance between
high-- and low--voltage wiring. Pass the control wires
through the hole provided in the corner post, then feed the
wires thorough the raceway to the RTU--MP. Connect to
the wires to the removable Phoenix connectors and then
reconnect the connectors to the board.
Space Temperature (SPT) Sensors
ORSET SEN
BRN (COM)
BLK (STO)
BLU (SPT)
SENSOR
WIRING
A field --supplied Carrier space temperature sensor is
required with the RTU--MP to monitor space temperature.
There are 3 sensors available for this application:
S 33ZCT55SPT, space temperature sensor with override
button
S 33ZCT56SPT, space temperature sensor with override
button and setpoint adjustment
S 33ZCT59SPT, space temperature sensor with LCD
(liquid crystal display) screen, overri de button, and
setpoint adjustment
Use 20 gauge wire to connect the sensor t o the controller.
The wire is suitable for distances of up to 500 ft. Use a
three--conductor shielded cable for the sensor and setpoint
adjustment connections. Ifthe setpoint a djustment
(slidebar) is not required, then an unshielded, 18 or 20
gauge, two--conductor, twisted pair c able ma y be used.
Connect T--55 -- See Fig. 31 for typical T--55 internal
connections. Connectthe T--55 SEN terminals to
RTU--MP J20--1 and J20--2. See Fig. 50.
SEN
SEN
J20-1
J20-2
C08460
Fig. 50 -- RTU--MP T--55 Sensor Connecti ons
Connect T--56--See Fig.33 for T--56 internal
connections. Install a jumper between SEN and SET
terminals as illustrated. Connect T--56 t erminals to
RTU--MP J20--1, J20--2 and J20--3 per Fig. 51.
SENJ20-1
OPB COM- PWR+
POWER
24 VAC
NOTE: Must use a separate isolated transformer.
WIRING
C07132
Fig. 52 -- Space Temperature Sensor T ypical Wiring
(33ZCT59SPT)
Economizer controls —
Outdoor Air Enthalpy Control (PNO HH57AC077) --
The enthalpy control (HH57AC077) is available a s a
field--installed accessory to be used with the EconoMi$er2
damper system. The outdoor ai r entha lpy sensor is part of
the enthalpycontrol.(Theseparatefield--installed
accessory return air enthalpy sensor (HH57AC078) is
required for differential enthalpy control. See “Return AirEnthalpy Sensor”below.)
Locate the enthalpy control in the economizer hood.
Locate two GRA leads in the factory harness and connect
these leads to enthalpy control sensors 2 and 3. See
Fig. 36. Conne ct the enthalpy control power input
terminals to economizer actuator power leads RED
(connect to TR) and BLK (connect to TR1).
The outdoor enthalpy changeover setpoint is set at the
enthalpy controller.
Differential Enthalpy Control — Differential enthalpy
control is provided by sensing and comparing the outside
air and return air enthalpy conditions. Install t he outdoor
air enthalpy control as described above. Add a nd install a
return air enthalpy sensor.
50TCQA
SEN
Jumper
SET
SET
J20-2
J20-3
C08461
Fig. 51 -- RTU--MP T--56 Sensor Connecti ons
Connect T--59 -- The T--59 space sensor requires a
separate, isolated power supply of 24 VAC. See Fig. 51
for internal conne ctions at the T--59. Connect the SEN
terminal (BLU) to RTU--MP J20-- 1. Connect the COM
terminal (BRN) to J20--2. Connect the SET terminal (STO
or BLK) to J20--3.
Return Air Enthalpy Sensor — Mount the return--air
enthalpy sensor (HH57AC078) in the return--air duct. The
return air sensor is wired to the enthalpy controller
(HH57AC077). See Fig. 37.
To wire the return air enthalpy sensor, perform the
following:
1. Use a 2--conductor, 18 or 20 AWG, twisted pair c able
to connect the return air enthalpy sensor to the enthalpy controller.
2. At the enthalpy control remove the factory--installed
resistor from the (SR) and (+) terminals.
3. Connect the field--supplied RED wire to (+) spade
connector on the return air enthalpy sensor and the
(SR+) terminal on the enthalpy controller. Connect
the BLK wire to (S) spade connector on the return a ir
29
enthalpy sensor and the (SR) terminal on the enthalpy
controller.
NOTE:The enthalpy control must be set to the “D”
setting for differential enthalpy control to work properly.
Indoor Air Quality (CO
sensor accessory monitors space carbon dioxide (CO
sensor) — The indoor air quality
2
2
levels. This information is used to monitor IAQ levels.
Several types of sensors are available, for wall mounting
in the space or in return duct, with and without LCD
display, and in combination with space temperature
sensors. Sensors use infrared technology to measure the
levels of CO
The CO
present in the space air.
2
sensors are all fac tory set for a range of 0 to
2
2000 ppm and a linear mA output of 4 to 20. Refer to the
instructions supplied with the CO
sensor for electrical
2
requirements and terminal locations. See Fig. 38 for
typical CO
sensor wiring schematic.
2
with an outdoor cover. See Fig. 40. The outdoor air CO
sensor must be located in the economizer outside air hood.
Wiring the Outdoor Air CO
Sensor — A dedicated power
2
supply is required for this sensor. A two--wire cable is
required to wire the dedicated power supply for the sensor.
The two wires should be connected to the power supply
)
and terminals 1 and 2.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
OAQ sensor. See Fig. 38. Connect t he 4 to 20 mA
terminal to RTU--MP J4--5. Connect the SIG COM
terminal to RTU--MP J4--6.
OAQ Sensor/RH Sensor
SEN
2
J4-5
To accurately monitor the quality of the air in the
50TCQA
conditioned air space, locate the sensor near a return--air
grille (if present) so it senses the concentration of CO
leaving the space. The sensor should be mounted in a
location to avoid direct breath contact.
Do not mount the IAQ sensor in drafty areas such as near
supply ducts, open windows, fans, or over heat sources.
Allow at least 3 ft (0.9 m) between the sensor and any
corner. Avoid mounting the sensor where it is influenced
by the supply air; the sensor gives inaccurate readings if
the supply air is blown directly onto the sensor or if the
supply air does not have a chance to mix with the room air
before it is drawn into the return airstream.
Wiring the Indoor Air Quality Sensor —
For each sensor, use two 2--conductor 18 AWG (American
Wire Gage) twisted--pair cables (unshielded) to connect
the separate isolated 24 vac power source to the sensor
and to connect the sensor to the control board terminals.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
sensor. See Fig. 38. Connect the 4--20 mA terminal to
RTU--MP J4--2 and connect the SIG COM terminal to
RTU--MP J4--3. See Fig. 53.
IAQ Sensor
SEN
COM
24 VAC
Fig. 53 -- RTU--MP / Indoor CO2Sensor
(33ZCSENCO2) Connections
Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus
weatherproof enclosure) — The outdoor air CO
designed to monitor carbon di oxide (CO
) levels in the
2
outside ventilation air and interface with the ventilation
damper in an HVAC system. The OAQ sensor is packaged
J4-2
J4-3
sensor is
2
C08462
COM
2
24 VAC
Fig. 54 -- RTU--MP / Outdoor CO2Sensor
(33ZCSENCO2) Connections
On 50TCQ units equipped with factory--instal led Smoke
Detector(s), the smoke detector controller implements the
unit shutdown through its NC contact set connected to the
unit’s CTB input. The FSD function is initiated via the
smoke detector’s Alarm NO contact set. The RTU--MP
controller communicates the smoke detector’s tripped
status to the BAS building control. See Fig. 30, the
PremierLink wiring schematic.
TheFireShutdownSwitchconfigura tion,
→
MENU
Config→Inputs→input5,identifiesthe
normally open status of this input when there is no fire
alarm.
Connecting Discrete Inputs
Status
Filter
The filter status accessory is a field--installed accessory.
This accessory detects plugged filters. When installing
this accessory, the unit must be configured for filter status
→
by setting MENU
Config→Inputs→input3,5,8,or9
to Filter Status and normally open (N/O) or normally
closed (N/C). Input 8 or 9 is recommended for easy of
installation. Refer to Fig. 47 and Fig. 49 for wire
terminations at J5.
Fan Status
The fan status accessory is a field --installed accessory.
This accessory detects when the indoor fan is blowing air.
When installing this accessory, the unit must be
configuredforfanstatusbysetting
→
MENU
Status and normally open (N/O) or normally closed (N/C).
Input 8 or 9 is recommended for easy of installation. Refer
to Fig. 47 and Fig. 49 for wire terminations at J5.
Config→Inputs→input3,5,8,or9to Fan
J4-6
C08463
30
Remote Occupancy
The remote occupancy accessory is a field --installed
accessory. This accessory overrides the unoccupied mode
and puts the unit in occupied mode. When installing this
accessory, the unit must be configured for remote
→
occupancy by setting MENU
Config→Inputs→input 3,
5, 8, or 9 to Remote Occupancy and normally open (N/O)
or normally closed (N/C).
→
Also set MENU
Schedules→occupancy source to DI
on/off. Input 8 or 9 is recommended for easy of
installation. Refer to Fig. 47 and Table 8 for wire
terminations at J5.
Power Exhaust (output)
Connect the accessory Power Exhaust contactor coil(s) per
Fig. 55.
Power Exhaust
PEC
TAN
J11-3
CTB
THERMOSTAT
GRA
Fig. 55 -- RTU--MP Power Exhaust Connections
C
C08464
Space Relative Humidity Sensor -- The RH sensor is not
used with 50TCQ models at this time.
Communication Wiring -- Protocols
General
Protocols are the communication languages spoken by
control devices. The main purpose of a protocol is to
communicate information in the most efficient method
possible. Different protocols exist to provide different
kinds of information for different applications. In the BAS
application, many different protocols are used, depending
on manufacturer. Protocols do not change the function of
a controller; just make the front end user different.
The RTU--MP can be set to communicate on four different
protocols: BACnet, Modbus, N2, and LonWorks. Switch 3
(SW3) on the board is used to set protocol and baud rate.
Switches 1 and 2 (SW1 and SW2) are used to set the
board’s network address. See Fig. 56 for the switch setting
per protocol. The 3rd party connection to the RTU--MP is
through plug J19.
NOTE: Power must be cycled after changing the SW1--3
switch settings.
Refer to t he RTU--MP 3rd Party Integration Guide for
more detailed information on protocols, 3rd party wiring,
and networking.
50TCQA
SW3 Protocol Selection
PROTOCOLDS8DS7DS6DS5DS4DS3DS2DS1
BACnet MS/TP
(Master)
Modbus
(Slave)
N2
(Slave)
LonWorksUnusedONONOFFONOFFOFFOFF
NOTE:
DS = Dip Switch
BACnet MS/TP SW3 example shown
BAUD RATEDS2DS1
9600OFFOFF
19,200ONOFF
38,400OFFON
76,800ONON
UnusedOFFOFFOFFONOFFSelect Baud Select Baud
UnusedOFFOFFONONOFFSelect Baud Select Baud
UnusedOFFOFFOFFONONOFFOFF
Baud Rate Selections
Fig. 56 -- RTU--MP SW3 Dip Switch Settings
C07166
31
Local Access
BACview6Handheld
The BACview6is a keypad/display interface used to
connect to the RTU--MP to access the control information,
read sensor values, and test the RTU, see Fig. 57. This is
an accessory interface that does not come with the MP
controller and can only be used at the unit. Connect the
BACview
are 2 password protected levels in the display (User and
Admin). The user password is defaulted to 0000 but can
be changed. The Admin password is 1111 and cannot be
changed. There is a 10 minute auto logout if a screen is
idle. See Form 48--50H--T--2T, Appendix A for navigation
and screen content.
50TCQA
6
to the RTU--MP’s J12 local access port. There
Virtual BACview
Virtual BACview is a freeware computer program that
6
functions as the BACview
Handheld. The USB Li nk
interface (USB--L) is required to connect a computer to
the RTU--MP board. The link cable connects a USB port
to the J12 local access port. This program functions and
operates identical to the handheld.
RTU--MP Troubleshooting
Communication
The LEDs indicate if the controller is speaking to the
devices on the network. The LEDs should reflect
communication traffic based on the baud rate set. The
higher the baud rate the more solid the LEDs will appear.
LEDs
Fig. 57 -- BACview6Handheld Connections
32
C07170
Table 9 – LEDs
The LEDs on the RTU--MP show the status of certain functions
If this LED is on...Status is...
PowerThe RTU MP has power
RxThe RTU MP is receiving data from the network segment
TxThe RTU MP is transmitting data over the network segment
DO#The digital output is active
The Run and Error LEDs indicate control module and network status
If Run LED shows...
2 flashes per secondOffNormal
2 flashes per second
2 flashes per second
2 flashes per second
2 flashes per secondOn
5 flashes per secondOnExec start ---up aborted, Boot is running
5 flashes per secondOffFirmware transfer in progress, Boot is running
7 flashes per second
14 flashes per second
OnOn
NOTE:Refer to Form 48-- 50H--T--2T for complete
configuration of RTU-- MP, operating sequences and
troubleshooting information. Refer to RTU--MP 3rd PartyIntegration Guide for details on configuration and
troubleshooting of connected networks. Have a copy of
these manuals available at unit start--up.
And Error LED shows...Status is...
2flashes,
alternating with Run LED
3flashes,
then off
4flashes,
then pause
7 flashes per second, alternating with
Run LED
14 flashes per second,
alternating with Run LED
Five minute auto --- restart delay after system error
Control module has just been formatted
Two or more devices on this network have the
same ARC156 network address
Exec halted after frequent system errors or
control programs halted
Ten second recovery period after brownout
Brownout
Failure. Try the following solutions:
STurn the RTU ---MP off, then on.
SF or ma t t h e R T U --- M P.
SDownload memory to the RTU---MP.
SReplace the RTU--- MP.
System
The smoke detector system consists of a four--wire
controller and one or two sensors. Its primary function is
to shut down the rooftop unit in order to prevent smoke
from circulating throughout the building. It is not to be
used as a life saving device.
50TCQA
SMOKE DETECTORS
Smoke detectors are available as factory--installed options
on 50TCQ models. Smoke detectors may be specified for
Supply Air only or for Return Air without or with
economizer or in combination of Supply Air and Ret urn
Air. Return Air smoke detectors are arranged for vertical
return configurations only. All components necessary for
operation are factory--provided and mounted. The unit is
factory--configuredforimmediatesmokedetector
shutdown operation; additional wiring or modifications to
unit terminal board may be necessary to complete the unit
and smoke detector configuration to meet project
requirements.
Units equipped with factory--opt ional Return Air smoke
detectors require a relocation of the sensor module at unit
installation. See “Completing Installation of Return Air
Smoke Sensor:” on page 35 for details.
Controller
The controller (see Fig. 58) includes a controller housing,
a printed circuit board, and a clear plastic cover. The
controller can be connected to one or two compatible duct
smoke sensors. The clear plastic cover is secured to the
housing with a single captive screw for easy access to the
wiring terminals. The controller has three LEDs (for
Power, Trouble and Alarm) and a manual test/reset button
(on the cover face).
Sensor
The sensor (see Fig. 59) includes a plastic housing, a
printed circuit board, a clear plastic cover, a sampling
tube inlet and an exhaust tube. The sampling tube (when
used) and exhaust tube are attached during installation.
The sampling tube varies in length depending on the size
of the rooftop unit. The clear plastic cover permits visual
inspections without having to disassemble the sensor. The
cover attaches to the sensor housing using four captive
screws and forms an airtight chamber around the sensing
electronics. Each sensor includes a harness with an RJ45
33
terminal for connecting to the controller. Each sensor has
four LEDs (for Power, Trouble, Alarm and Dirty) and a
manual test/reset button (on the left--side of the housing).
Duct smoke sensor
Exhaust tube
Duct smoke sensor
controller
Conduit nuts
(supplie d by installer)
Conduit s upport plate
Terminal block cover
Troub le
Power
Tes t / r e s e t
switch
Cover gasket
(ordering option)
50TCQA
Controll er housing
and electronics
Conduit c ouplings
(supplie d by installer)
Alarm
Fastener
(2X)
Fig. 58 -- Controller Assembly
Air is introduced to the duct smoke detector sensor’s
sensing chamber through a sampling tube that extends into
the HVAC duct and is directed back into the ventilation
system through a (shorter) exhaust tube. The difference in
air pressure between the two tubes pulls the sampled air
through the sensing chamber. Whe n a sufficient amount of
smoke is detected in the sensing chamber, the sensor
signals an alarm state and the controller automatically
takes the appropriate action to shut down fans and
blowers, change over air ha ndling systems, notify the fire
alarm control panel, etc.
Controll er cover
C08208
See
Detail A
Detail A
Intake
gasket
Plug
TSD-CO2
(ordering option)
Sampling tube
(ordered separately)
Magnetic
test/reset
switch
Exhaust gasket
Coupling
Alarm
Troub le
Sensor housing
and electro nics
Power
Dirty
Cover gasket
(ordering option)
Sensor cover
C08209
Fig. 59 -- Smoke Detector Sensor
Smoke Detector Locations
Supply Air — The Supply Air smoke detector sensor is
located to the left of the unit’s indoor (supply) fan. See
Fig. 60. Access is through the fan access panel. There is
no sampling tube used at this location. The sampling tube
inlet extends through the side plate of the fan housing
(into a high pressure area). The controller is located on a
bracket to the right of the return filter, accessed through
the lift--off filter panel.
The sensor uses a process called differential sensing to
prevent gradual environmental changes from triggeri ng
false alarms. A rapid change in environmental conditions,
such as smoke from a fire, causes the sensor to signal an
alarm state but dust and debris accumulated over time
does not.
For installations using two sensors, the duct smoke
detector does not differentiate which sensor signals an
alarm or trouble condition.
Smoke Detector Sensor
C08245
Fig. 60 -- Typical Supply Air Smoke Detector Sensor
Location
Return Air without Economizer — The sampling tube is
located across the return air opening on the unit basepan.
See Fig. 61. The holes in the sampling tube face
34
downward, into the return air stream. The sampling tube is
connected via tubing to the return air sensor that is
mounted on a bracket high on the partition between return
filter and controller location. (This sensor is shipped in a
flat--mounting location. Installation requires that this
sensor be relocated to its operating location and the tubing
to the sampling tube be connected. See “CompletingInstallation of Return Air Smoke Sensor:” for details.)
Return Air Detector module
(shipping position shown)*
Controller module
Return Air Detector Sampling Tube
*RA detector must be moved from shipping position to operating position by installer
C07307
Fig. 61 -- Typical Return Air Detector Location
Return Air with Economizer — The sampling tube is
inserted through the side plates of the economizer
housing, placing it across the return air opening on the
unit basepan. See Fig. 61. The holes in the sampling tube
face downward, into the return air stream. The sampling
tube is connected via tubing to the return air sensor that is
mounted on a bracket high on the partition between return
filter and controller location. (This sensor is shipped in a
flat--mounting location. Installation requires that this
sensor be relocated to its operating location and the tubing
to the sampling tube be connected. See the following
installation procedure.)
Completing Installation of Return Air Smoke
Sensor:
1. Unscrew the two screws holding the Return Air
Sensor detector plate. See Fig. 63. Save the scr ews.
2. Remove the Re turn Air Sensor and its detector plate.
3. Rotate the detector plate so the sensor is facing outwards and the sampling tube connection is on the bottom. See Fig. 64.
4. Screw the sensor and detector plate into its operating
position using screws from Step 1. Make sure the
sampling tube connection is on the bottom and the exhaust tube is on the top. See Fig. 64.
5. Connect the flexible tube on the sampling inlet to the
sampling tube on the basepan.
Screws
50TCQA
Flexible
Exhaust Tubes
Sample Tube
C08126
Fig. 63 -- Return Air Detector Shipping Position
Return Air
Sampling Tube
Fig. 62 -- Return Air Sampling Tube Location
C08127
Fig. 64 -- Return Air Sensor Operating Position
Additional Application Data — Refer to Catalog No.
HKRNKA--1XA for discussions on additional control
features of these smoke detectors including multiple unit
coordination.
CO--- Convenient outlet
DISC--- Disconnect
FLA--- Full load amps
IFM--- Indoor fan motor
LRA--- Locked rotor amps
MCA--- Minimum circuit amps
MOCP--- Maximum over current protection
P E--- P o w e r e x h a u s t
UNPWR CO--- Unpowered convenient outlet
NOTES:
1. In compliance with NEC requirements for multimotor and
combination load equipment (refer to NEC Articles 430 and
440), the overcurrent protective device for the unit shall be
fuse or HACR breaker. Canadian units may be fuse or circuit
breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance.
% Voltage Imbalance = 100 x
50TCQA
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 230-3-60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance= 100 x
This amount of p hase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
(224 + 231 + 226)
=227
= 1.76%
3
=
4
227
681
3
Economizer2 Position Damper
Fig. 65 -- EconoMi$ert IV Wiring
Step 11 — Adjust Factory--Installed Options
Smoke Detectors —
Smoke detector(s) will be connected at the Central
Terminal Board (CTB), at terminals marked “Smoke
Shutdown”. Remove jumper JMP 3 when ready to
energize unit.
Unit Without Economizer or
2 Position Damper
C08631
EconoMi$er IV Occupancy Switch —
Refer to Fig. 65 for general EconoMi$er IV wiring.
External occupancy control is managed through a
connection on the Central Terminal Board.
If external occupancy control is desired, connect a time
clock or remotely controlled switch (closed for Occupied,
open for Unoccupied sequence) at terminals marked
OCCUPANCY on CTB. Remove or cut jumper JMP 2 to
complete the installation.
44
Step 12 — Install Accessories
Available accessories include:
Roof Curb
Thru--base connection kit (must be installed before unit
is set on curb)
Manual outside air damper
Two--Position motorized outside air damper
EconoMi$er IV (with control and integrated barometric
relief)
EconoMi$er2 (without control/for external signal and
integrated barometric relief)
Power Exhaust
Differential dry--bulb sensor (EconoMi$er IV)
Outdoor enthalpy sensor
Differential enthalpy sensor
Time Guard II compressor anti--cycle control
Outdoor coil hail guard
Outdoor coil protector grille
Head pressure control
Programmable setback thermostat
Electrical/Mechanical thermostat and subbase
Thermidistatt device
Humidistat
Electric Heaters
Single Point kits
Thermostat / Sensors
CO
sensor
2
DDC interface (PremierLink)
Louvered hail guard
Phase monitor control
Refer to separate installation instructions for information
on installing these accessories.
Pre--Start and Start--Up
This completes the mechanical installation of the unit.
Refer to the unit’s Service Manual for detailed Pre--Start
and Start--up instructions.
50TCQA
45
50TCQA
46
50TCQA
47
50TCQA
Copyright 2009 Ca rrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231Printed in U.S.A.Edition Date: 02/10/09
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
48
Catalog No: 50TCQ---01SI
Replaces: NEW
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.