Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical
shock or other condi tions which may cause personal
injury or property damage. Consult a qualified installer,
service agency, or your distributor or branch for
information or assistance. The qualified installer or
agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual
instructions packaged with the kits or accessories when
installing.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloths for brazing operations and
have a fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions attached to
the unit. Consult local building codes and appropriate
nationalelectricalcodes (in USA, ANSI/NFPA70,
National Electrical Code (NEC); in Canada, CSA C22.1)
for special requirements.
It is important to recognize safety inform ation. This is the
safety--alert symbol
unit and in instructions or manuals, be alert to the
potential for personal injury.
. When you see thi s symbol on the
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the
safety--alert symbol. DANGER identifies the most serious
hazards which will result in seve re personal injury or
death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify
unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced
installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
Before performing service or maintenance operations
on unit, always turn off main power switch to unit and
install lockout tag. Unit may have more than one
power switch.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
Puronr (R--410A) refrigerant systems operate at
higher pressures than standard R--22 systems. Do not
50TCQA
use R--22 service equipment or components on Puron
refrigerant equipment.
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could cause personal
injury or death.
Relieve pressure and recover all refrigerant before
system repair or final unit disposal.
Wear safety glasses and gloves when handling
refrigerants. Keep torches and other ignition sources
away from refrigerants and oils.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal
injury.
Sheet metal parts may have sharp edges or burrs. Use
care and wear appropri ate protective clothing, safety
glasses and gloves when handling parts and servicing
heat pump units.
2
Vertical Connections / Economizer
50TCQA
Horizontal Connections / Economizer
Fig. 1 -- Unit Dimensional Drawing – 04 — 07 Size Units
3
C09001
50TCQA
Jobsite Survey
Fig. 1 -- Unit Dimensional Drawing – 04 — 07 Size Unit (cont.)
INSTALLATION
18” (457)
C09002
1
Complete the following checks before installation.
1. Consult local building codes and the NEC (National
Electrical Code) ANSI/NFPA 70 for special installation requirements.
2. Determi ne unit location (from project plans) or select
unit location.
3. Check for possible overhead obstructions which may
interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (curb
or other) that provides for the minimum clearances
required for safety. This includes the clearance to
combustible surfaces, unit performance and service access
below, around and above unit as specified in unit
drawings. See Fig. 2.
NOTE: Consider also the effect of adjacent units.
Unit may be installed directly on wood flooring or on Class
A, B, or C roof--covering material when roof curb is used.
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated
air.
Although unit is weatherproof, avoid locations that permit
water from higher level runoff and overhangs to fall onto
the unit.
Select a unit mounting system that provides adequate
height to allow for removal and disposal of frost and ice
that will form durring the heating--defrost mode as well as
allow installation of condensate trap per requirements.
RefertoStep9—InstallExternalCondensate Trap and
Line – for required trap dimensions.
4
Roof mount —
Checkbuildingcodesforweightdistribution
requirements. Unit operat ing weight is shown in Table 1.
Step 3 — Inspect unit
Inspect unit for transportation damage. File any claim
with transportation agency.
Step 2 — Plan for Sequence of Unit Installation
The support method used for this unit wil l dictate different
sequences for the steps of unit installation. For exampl e,
on curb--mounted units, some accessories must be
installed on the unit before the unit is placed on the curb.
Review t he following for recommended sequences for
installation steps.
(affects curb and unit) (refer to accessory installation
instructions for details)
Prepare bottom condensate drain connection to suit
planned condensat e line routing (refer to Step 9 for
details)
Rig and place unit
Install outdoor air hood
Install condensate line trap and piping
Make electrical connections
Install other accessories
Pad--mounted installation —
Prepare pad and unit supports
Check and tighten the bottom condensate drain
connection plug
Rig and place unit
Convert unit to side duct connection arrangement
Install field--fabricated ductwork at unit duct openings
Install outdoor air hood
Install condensate line trap and piping
Make electrical connections
Install other accessories
Frame--mounted installation —
Frame--mountedapplications generally follow the
sequence for a curb installation. Adapt as required to
suit specific installation plan.
Confirm before installation of unit that voltage, ampera ge
and circuit protection requirements listed on unit data
plate agree with power supply provided.
Step 4 — Provide Unit Support
Roof Curb Mount —
Accessory roof curb details and dimensions are shown in
Fig. 3. Assemble and install accessory roof curb in
accordance with instructions shipped with the curb.
NOTE:The gasketing of the unit to the roof curb is
critical for a watertight seal. Install gasket supplied with
the roof curb as shown in Fig. 3. Improperly applied
gasket can also result in air leaks and poor unit
performance.
Curb should be level. This is necessary for unit drain to
function properly. Unit leveling toleranc es ar e show in
Fig. 4. Refer to Accessory Roof Curb Installation
Instructions for additional information as required.
Install insulation, cant strips, roofing felt, and counter
flashing as shown. Ductwork must be attached to curb and
not to the unit. The accessory thru--the--base power package
must be installed before the unit is set on the roof curb.
If electric and control wiring is to be routed through the
basepan, attach the accessory thru--the --base service
connections to the basepan in accordance with the
accessory installation instructions.
Slab Mount (Horizontal Units Only) —
Provide a level concrete slab that extends a minimum of
6 in. (150 mm) beyond unit cabinet. Install a gravel apron
in front of condenser coi l air inlet to prevent grass and
foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb
if required.
Alternate Unit Support (In Lieu of Curb or Slab
Mount) —
A non--combustible sleeper rail can be used in the unit curb
support area. If sleeper rails cannot be used, support the long
sides of the unit with a minimum of 3 equally spaced 4--in. x
4--in. (102 mm x 102 mm) pads on each side.
50TCQA
Table 1 – Operating Weights
50TCQAUNITS LB (KG)
ComponentA04A05A06A07
Base Unit505 (229)510 (231)590 (268)630 (286)
Economizer
Vertical80 (36)80 (36)80 (36)80 (36)
Horizontal105 (48)105 (48)105 (48)105 (48)
Powered Outlet32 (15)32 (15)32 (15)32 (15)
Curb
14---in/356 mm110 (50)110 (50)110 (50)110 (50)
24---in/610 mm145 (66)145 (66)145 (66)145 (66)
5
ROOFCURB
ACCESSORY
CRRFCURB001A02
CRRFCURB002A02
1’ - 2”
[356]
2’ - 0”
[610]
UNIT SIZE
50TCQA04-07
50TCQA
Fig. 3 -- Roof Curb Details
6
C08548
MAXIMUM ALLOWABLE
DIFFERENCE IN. (MM)
A-B
0.5” (13)
1.0” (25)
Fig. 4 -- Unit Leveling Tolerances
Step 5 — Field Fabricate Ductwork
B-C
A-C
1.0” (25)
C06110
should be ducted through the roof deck to comply with
applicable fire codes.
Forunitswithaccessoryelectricheaters:Horizontal
applications require a minimum clearance to combustible
surfaces of 1--in (25 mm) from duct for first 12--in (305 mm)
away from unit. V ertical applications do not require a
minimum clearance.
Minimum clearance is not required around ductwork.
Step 6 — Rig and Place Unit
Keep unit upright and do not drop. Spreader bars are not
required if top crating is left on unit. Rollers may be used to
move unit across a roof. Level by using unit frame as a
reference. See Table 1 and Fig. 5 for additional information.
Cabinet return-air static pressure (a nega tive condition)
shall not exceed 0.35 in. wg (87 Pa) with economizer or
0.45 in. wg (112 Pa) without economizer.
For vertical ducted applicat ions, secure all ducts to roof
curb and building structure. Do not connect ductwork to
unit.
Insulate and weatherproof all external ductwork, joi nts,
and roof openings with counter flashing and mastic in
accordance with applicable codes.
Ducts passing through unconditioned spaces must be
insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
Lifting holes are provided in base rails as shown in Fig. 5.
Refer to rigging instructions on unit.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in
equipment damage.
All panels must be in place when rigging. Unit is not
designed for handling by fork truck.
Before setting the unit onto the curb, recheck gasketing on
curb.
50TCQA
NOTES:
C06005
UNIT
50TCQA0475534374.38188936.2592133.38848
50TCQA0576034574.38188936.2592133.38848
50TCQA0684038174.38188935.6390541.381051
50TCQA0788039974.38188937.2594641.381051
1. Dimensions in ( ) are in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the
unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.
MAX WEIGHT
LBKGINMMINMMINMM
ABC
DIMENSIONS
Fig. 5 -- Rigging Details
7
PositioningonCurb—
Position unit on roof curb so that the following clearances
are maintained:
1
/4in. (6.4 mm) clearance between the
roof curb and the base rail inside the front and rear, 0.0 in.
clearance between the roof curb and the base rail inside on
the duct end of the unit. This will result in the distance
between the roof curb and the base rail inside on the
condenser end of the unit being approximately equal to
Fig. 3, section C--C.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
After unit is in position, remove the compressor access
panel. Holding the blocking between compressors with
one hand, cut the strapping. Carefully remove the
blocking without damaging tubing, wiring, or controls.
Remove the strapping and replace the access panel.
Remove all shipping mate rials and top skid. Recycle or
dispose of all shipping materials.
50TCQA
Step 7 — Convert to Horizontal and Connect
Ductwork (when required)
Unit is shipped in the vertical duct configuration. Unit
without factory--installed economizer or return air smoke
detector option may be field--converted to horizontal
ductedconfiguration.Toconverttohorizontal
configuration, remove screws from side duct opening
covers and remove covers. Using the same screws, install
covers on vertical duct openings with the insulation--side
down. Seals around duct openings must be tight. See
Fig. 6.
Step 8 — Install Outside Air Hood
Economizer Hood Removal and Setup -- Factory
Option
1. The hood is shipped in knock--down form and
located in the return air compartment. It is attached
to the economizer using two plastic tie --wraps.
2. To gain access to t he hood, remove the filter access
panel. (See Fig. 7.)
3. Locate and cut the (2) plastic tie--wraps, being
careful to not damage any wiring. (See Fig. 8.)
4. Carefully lift the hood assembly through the filter
access opening and assemble per the steps outlined
in Economizer Hood and Two–Position Hood on
page 10.
FILTER ACCESS PANEL
COMPRESSOR
ACCESS PANEL
OUTDOOR-AIR OPENING AND
INDOOR COIL ACCESS PANEL
Fig. 7 -- Typical Access Panel Locations
C06023
C06108
Fig. 6 -- Horizontal Conversion Panels
Field--supplied flanges should be attached to horizontal
duct openings and all ductwork should be secured to the
flanges. Insulate and weatherproof all external ductwork,
joints, and roof or building openings with counter flashing
and mastic in accordance with applicable codes.
Do not cover or obscure visibility to the unit’s informative
data plate when insulating horizontal ductwork.
Remove Hood Parts
Cut Plastic Ties
(2) Places
Economizer
C08633
Fig. 8 -- Economizer Wiring
8
Two Position Damper Hood Removal and Setup -Factory Option
1. The hood is shipped in knock--down form and
assembled to a metal support tray using plastic
stretchwrap.Locatedinthereturnair
compartment, the assembly’s metal tray is attached
to the basepan and also attached to the damper
using two plastic tie--wraps.
2. To gain access to t he hood, remove the filter access
panel. (See Fig. 7.)
3. Locate the (2) screws holding the metal tray to the
basepan and remove. Locate and cut the (2) plastic
tie--wraps securing the assembly to the damper. (See
Fig. 9.) Be careful to not damage any wiring or cut
tie--wraps securing any wiring.
4. Carefull y lift the hood assembly (with metal tray)
through the filter access opening and assemble per
the steps outlined in Economizer Hood andTwo–Position Hood on page 10.
Hood Parts
50TCQA
Plastic Tie Wrap
Qty (2)
Fig. 9 -- Damper Assembly
Screws for Metal Tray
Qty (2)
C08639
9
Economizer Hood and Two--Position Hood —
NOTE: If the power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be
used and must be discarded. Save the aluminum filter for
use in the power exhaust hood assembly.
1. The indoor coil access panel will be used as the top of
the hood. Remove the screws along t he sides and bottom of the indoor coil access panel. See Fig. 10.
SIDE
PANEL
50TCQA
CAULK
INDOOR
COIL
ACCESS
PANEL
HERE
Fig. 10 -- Indoor Coil Access Panel Relocation
2. Swing out indoor coil access panel and insert the
hood sides under the panel (hood top). Use the screws
provided to attach the hood sides to the hood top. Use
screws provided to attach the hood sides to the unit.
See Fig. 11.
INDOOR COIL
ACCESS PANEL
TOP
SIDE
PANEL
INDOOR
COIL
ACCESS
PANEL
TOP
PANEL
C06025
filter rack (hood divider). Push the filter into position
past the open filter clips. Close the filter clips to lock
the filter into place. See Fig. 12.
DIVIDER
OUTSIDE
AIR
HOOD
CLEANABLE
BAROMETRIC
RELIEF
ALUMINUM
FILTER
FILTER
FILTER
CLIP
C08634
Fig. 12 -- Economizer Filter Installation
6. Caulk the ends of the joint between the unit top panel
and the hood top.
7. Replace the filter access panel.
Step 9 — Install External Condensate Trap and
Line
The unit has one3/4-in. condensate drain connection on
the end of the condensate pan and an alternate connection
on the bottom. See Fig. 13. Unit airflow configuration
does not determine which drain connection to use. Either
drain connection can be used with vertical or horizontal
applications.
When using the standard side drain connection, ensure the
red plug in the alternate bottom connection is tight. Do
this before setting the unit in place. The red drain pan can
be tightened with a
1
/2--in. square socket drive extension.
LEFT
HOOD
SIDE
19 1/16”
B
(483mm)
HOOD DIVIDER
SCREW
33 3/8”
(848mm)
C06026
Fig. 11 -- Economizer Hood Construction
3. Remove the shippi ng tape holding the economizer barometric relief damper in place.
4. Insert the hood divider between the hood sides. See
Fig. 11 and 12. Secure hood divider with 2 screws on
each hood side. T he hood divider is also used as the
bottom filter rack for the aluminum filter.
5. Open the filter clips which are located underneath the
hood top. Insert the aluminum filter into the bottom
To use the alternate bottom drain connection, remove the
red drain plug from the bottom connection (use a1/2-- i n .
square socket drive extension) and install it in the side
drain connection.
CONDENSATE PAN (SIDE VIEW)
STANDARD
SIDE DRAIN
DRAIN
PLUG
(FACTORY-INSTALLED)
ALTERNATE
BOTTOM DRAIN
C08021
Fig. 13 -- Condensate Drain Pan (Side View)
The piping for the condensate drain and external trap can
be completed after the unit is in place. See Fig. 14.
10
MINIMUM PITCH
1” (25mm) PER
10’ (3m) OF LINE
TO ROOF
DRAIN
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4” (102) trap is recommended.
BASE RAIL
OPEN
VENT
2˝ (51) MIN
DRAIN PLUG
SEE NOTE
ROOF
CURB
C08022
Fig. 14 -- Condensate Drain Piping Details
All units must have an external trap for condensate
drainage. Install a trap at least 4-in. (102 mm) deep and
protect against freeze-up. If drain line is installed
downstream from the external t rap, pitch the line away
from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do
not use a pipe size smaller than the unit connection
3
/4-in.).
(
Step 10 — Make Electrical Connections
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning coul d result in personal
injury or death.
Do not use gas piping as an electrical ground. Unit
cabinetmusthaveanuninterrupted,unbroken
electrical ground to minimize the possibility of
personal injury if an electrical fault should occur. This
ground may consist of electrical wire connected to
unit ground lug in control compartment, or conduit
approved for electrical ground when installed in
accordance with NEC (National Electrical Code);
ANSI/NFPA 70, latest edition (in Canada, Canadian
ElectricalCodeCSA[CanadianStandards
Association] C22.1), and local electrical codes.
NOTE: Check all factory and field electrical connections
for tightness. Field--supplied wiring shall conform with
the limitations of 63_F(33_C) rise.
Field Power Supply —
If equipped with optional Powered Convenience Outlet :
The power source leads to the convenience outlet’s
transformer primary are not factory connected. Installer
must connect these leads according to required operation
of the convenience outlet. If an always--energized
convenience outlet operation is desired, connect the
source leads to the line side of the unit--mounted
disconnect. (Check with local codes to ensure this m ethod
is acceptable in your area.) If a de--energize via unit
disconnect switch operation of the convenience outlet is
desired, connect the source leads to the load side of the
unit disconnect. On a unit without a unit--mounted
disconnect, connect the source leads to compressor
contactor C and indoor fan contactor IFC pressure lugs
with unit field power leads.
All units except 208/230-v unit s are factory wired for the
voltage shown on the nameplate. If the 208/230-v unit is
to be connected to a 208-v power supply, the control
transformer must be rewired by moving the black wire
1
with the
connection and moving it to the 208-v
/4-in. female spade connector from the 230--v
1
/4-in. male
terminal on the primary side of the transformer. Refer to
unit label diagram for additional information. Field power
wires will be connected line--side pressure lugs on the
power terminal bl ock or at factory--installed option
non--fused disconnect.
Field power wires are connected to the unit at line--side
pressure lugs on compressor contactor C and indoor fan
contactor IFC or terminal board (see wiring diagram label
forcontrolboxcomponentarrangement)orat
factory--installed option non--fused disconnect switch.
Max wire size is #2 AWG (copper only). (See Fig. 16)
NOTE:TEST LEADS -- Unit may be equipped with
short leads (pigtails) on the field line connection points on
contactor C or optional disconnect switch. These leads are
for factory run--test purposes only; remove and discard
before connecting field power wires to unit connection
points. Make field power connections directly to line
connection pressure lugs only.
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in
intermittent operation or performance satisfaction.
Do not connect aluminum wire between disconnect
switch and furnace. Use only copper wire.
(See Fig. 15.)
ELECTRIC
DISCONNECT
SWITCH
COPPER
WIRE ONLY
ALUMINUM
WIRE
A93033
Fig. 15 -- Disconnect Switch and Unit
Units Without Factory--Installed Disconnect —
When installing units, provide a disconnect switch per
NEC (National Electrical Code) of adequate size.
Disconnect sizing data is provided on the unit informative
plate. Locate on unit cabinet or within sight of the unit per
national or local codes. Do not cover unit informative
plate if mounting the disconnect on the unit cabinet.
50TCQA
11
Units with Factory--Installed Disconnect —
Convenience Outlets —
The factory--installed option disconnect switch is located
in a weatherproof enclosure loc ated under the main
control box. The manual switch handle is accessible
through an opening in the access panel. Discard the
factory test leads (see Fig. 16).
Units Without Disconnect Option
IFC
(3 Phase
Indoor Motor)
C
111313
Disconnect
per
NEC
L1
L2L3
208/230-1-60
208/230-3-60
50TCQA
460-3-60
575-3-60
(1 Phase Indoor Motor
TB
and 1 Phase Unit)
Units With Disconnect Option
L1
L2
L3
2
4
6
Optional
Disconnect
Switch
1
3
5
Factory
Wiring
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning coul d result in personal
injury or death.
Units with convenience outlet circuits may use
multiple disconnects. Check convenience outlet for
power status before opening unit for service. Locate
its disconnect switch, if appropriate, and open it.
Tag--out this switch, if necessary.
Two types of convenience outlets are offered on 50TCQA
models: Non--powered and unit--powered. Both types
providea125--voltGFCI(ground--fault
circuit--interrupter) duplex receptacle rated at 15-- A
behind a hinged waterproof access cover, located on the
end panel of the unit. See Fig. 17.
Pwd-CO
Convenience
Outlet
GFCI
Pwd-CO
Fuse
Switch
Transformer
Disconnect factory test leads; discard.
C09011
Fig. 16 -- Power Wiring Connections
All units --
All field wiring must comply with NEC and all local
codes. Size wire based on MCA (Minimum Circuit Amps)
on the unit i nformative plate. See Fig. 16 and the unit
label diagram for power wiring connections to the unit
power terminal blocks and equipment ground. Maximum
wire size is #2 ga AWG per pole.
Provide a ground--fault and short--c ircuit ove r--current
protection device (fuse or breaker) per NEC Article 440
(or local codes). Refer to unit informative data plate for
MOCP (Maximum Over--current Protection) device size.
All field wiring must comply with the NEC and local
requirements.
Control Box
Access Panel
C08128
Fig. 17 -- Convenience Outlet Location
Installing Weatherproof Cover –
Aweatherproofwhile-in-usecoverforthe
factory-installed convenience outlets is now required by
UL standards. This cover cannot be factory-mounted due
its depth; it must be installed at unit installation. For
shipment, t he convenience outlet is covered with a blank
cover plate.
The weatherproof cover kit is shipped in the unit’s control
box. The kit includes the hinged cover, a backing plate
and gasket.
DISCONNECTALLPOWERTOUNITAND
CONVENIENCE OUTLET.
Remove the blank cover plate at the convenience outlet;
discard the blank cover.
Loosen the two screws at the GFCI duplex outlet, until
1
approximately
/2-in (13 mm) under screw heads are
exposed. Press the gasket over the screw heads. Slip the
backing plate over the screw heads at the keyhole slots
and align with the gasket; tighten the two screws until
snug (do not over-tighten).
12
Mount the weatherproof cover to the backing plate as
shown in Fig. 18. Remove two slot fillers in the bottom of
the cover to permit service tool cords to exit the cover.
Check for full closing and latching.
the face of the receptacle to trip and open the receptacle.
Check for proper grounding wires and power line phasing
if the GFCI receptacle does not trip as required. Press the
RESET button to clear the tripped condition.
COVER – WHILE-IN-USE
WEATHERPROOF
RECEPTACLE
NOT INCLUDED
BASE PLATE FOR
GFCI RECEPTACLE
C09022
Fig. 18 -- Weatherproof Cover Installation
Non--powered type: Thistype requires thefield
installation of a general--purpose 125--volt 15--A circuit
powered from a source elsewhere in the building. Observe
national and local codes when selecting wire size, fuse or
breaker requirements and disconnect switch size and
location. Route 125--v power supply conductors into the
bottom of the utility box containing the duplex receptacle.
Unit--powered type: A unit--mounted transformer is
factory--installed to stepdown the main power supply
voltage to the unit to 115--v at the duplex receptacle. This
option also includes a manual switch with fuse, located in
a utility box and mounted on a bracket behind the
convenience outlet; access is through the unit’s control
box access panel. See Fig. 17.
The primary leads to the convenience outlet transformer
are not factory-- connected. Selection of primary power
source is a customer--option. If local codes permit, the
transformer primary leads can be connected at the
line--side terminals on the unit--mounted non--fused
disconnect or HACR breaker switch; this will provide
service power to the unit when the unit disconnect switch
or HACR switch is open. Other conne ction methods will
result in the convenience outlet circuit being de--energized
when the unit disconnect or HACR switch is open. See
Fig. 19.
Duty Cycle: the unit--powered conveni ence outlet has a
duty cycle limitation. The transformer is intended to
provide power on an intermittent basis for service tools,
lamps, etc; it is not intended to provide 15--amps loading
for continuous duty loads (such as electric heaters for
overnight use). Observe a 50% limit on circuit loading
above 8--amps (i.e., limit loads exceeding 8--amps to 30
minutes of operation every hour).
Test the GFCI receptacle by pressing the TEST button on
C08283
UNIT
VOLTAGE
208,
230
460480
575600
CONNECTASPRIMARY
240
CONNECTIONS
L1: RED +YEL
L2: BLU + GRA
L1: RED
Splice BLU +
YEL
L2: GRA
L1: RED
L2: GRA
TRANSFORMER
TERMINALS
H1 + H3
H2 + H4
H1
H2 + H3
H4
H1
H2
Fig. 19 -- Powered Convenience Outlet Wiring
Using unit--mounted convenience outlets: Units with
unit--mounded convenience outlet circuits will often
require that two disconnects be opened to de--energize all
power to the unit. Treat all units as electrically energized
until the convenience outlet power is also checked and
de--energization is confirmed. Observe National Electrical
Code Article 210, Branch Circuits, for use of convenience
outlets.
Fuse on power type: The factory fuse is a Bussman
“Fusetron” T--15, non--renewable screw--in (Edison base)
type plug fuse.
Factory--Option Thru--Base Connections —
1
This service connection kit consists of a
3
bulkhead connector and a
/4--in electrical bulkhead
/2--in electrical
connector, all factory--installed in the embossed (raised)
section of the unit basepan in the condenser section. The
1
/2--in bulkhead c onnector ena bles the low--voltage control
wires to pass through the basepan. The
3
/4--in electrical
bulkhead connector al lows the high--voltage power wires
to pass through the basepan. See Fig. 20.
Check tightness of connector lock nuts before connecting
electrical conduits.
50TCQA
13
LOW VOLTAGE
CONDUIT
CONNECTOR
HIGH VOLTAGE
CONDUIT
CONNECTOR
Fig. 20 -- Thru-- Base Connection Fittings
Field--supplied and field--installed liquidtight conduit
connectors and conduit may be attached to the connectors
on the basepan. Pull correctly rated high voltage and low
voltage through appropriate conduits. Connect the power
50TCQA
conduit to the internal disconnect (if unit is so equipped)
or to the external disconnect (through unit side panel). A
hole must be field cut in the main control box bottom on
the left side so the 24--v control connections can be made.
Connect the control power conduit to the unit control box
at this hole.
Units without Thru--Base Connections —
1. Install power wiring conduit through side panel openings. Install conduit between disconnect and control
box.
2. Install power li nes to terminal connections as shown
in Fig. 16.
All Units —
Voltage to compressor terminals during operation must be
within voltage range indicated on unit nameplate. See
Table 10. On 3--phase units, voltages betwee n phases must
be balanced within 2% and the current within 10%. Use
the formula shown in the legend for Table 10, Note 2 (see
page 44) to determine the percent of voltage imbalance.
Operation on improper line voltage or excessive phase
imbalance constitutes abuse and may cause damage to
electrical components. Such operation would invalidate
any applicable Carrier warranty.
Field Control Wiring —
C08637
control the reversing valve operation. If using an
electronic thermostat, configure it for “non--heat pump”
operation. Locate the thermostat accessory on a solid wall
in the conditioned space to sense average temperature in
accordance with the thermostat installation instructions.
If the thermostat contains a logic circuit requiring 24--v
power, use a thermostat cable or equivalent single leads of
different colors with minimum of seven leads. If the
thermostat does not require a 24--v source (no “C”
connection required), use a thermostat cable or equivalent
with minimum of six leads. Check the thermostat
installation instructions for additional features which
might require additional conductors in the cable.
For wire runs up to 50 ft. (15 m), use no. 18 AWG
(American Wire Gage) insulated wire (35_C minimum).
For50to75ft.(15to23m),useno.16AWGinsulated
wire (35_C minimum). For over 75 ft. (23 m), use no. 14
AWG insulate d wire (35_C minimum). All wire sizes
larger than no. 18 AWG cannot be directly connected to
the thermostat and will require a junction box and splice
at the thermostat.
Terminal
X
C
G
W2
W1
Y2
Y1
R
Central
Board
T
H
E
R
M
O
S
T
A
T
C09012
Typical
Thermostat
Connections
C
G
W2
W1
O/B/Y2
(Note 1)
Y1
R
Note 1: Typical multi-function marking. Follow manufacturer’s configuration
instructions to select Y2. Do not configure for O output.
Note 2: W2 connection not required on units without electric heating.
Field Wiring
(Note 2)
Fig. 21 -- Typical Low--Voltage Control Connections
The 50TCQA unit requires an external temperature
control device.This device can be a thermostat
(field--supplied) or a PremierLink controller (available as
factory--installed option or as field--installed accessory, for
use on a Carrier Comfort Network or as a stand alone
control) or theRTU--MP Controller for Building
ManagementSystemsusingnon--CCNprotocols
(RTU--MP is available as a factory--installed option only).
Thermostat —
InstallaCarrier-- approvedaccessory2stage
Cooling/Heating thermostat according to installation
instructions included with the accessory. The 50TCQ
models do not require a thermostat with an O function to
Unit without thru--base connection kit —
Pass the thermostat control wires through the hole
provided in the corner post; then feed the wires through
the raceway built into the corner post to the control box.
Pull the wires over to the terminal strip on the upper--left
corner of the Central Terminal Board (CTB). See Fig. 22.
NOTE:If thru--the--bottom connections accessory is
used, refer to the accessory installation instructions for
information on routing power and control wiring.
Heat Anticipator Settings —
Set heat anticipator settings at 0.14 amp for the first stage
and 0.14 amp for second--stage heating, when available.
14
RACEWAY
DISCONNECT MOUNTING
LOCATION
HOLE IN END PANEL (HIDDEN)
Fig. 22 -- Field Control Wiring Raceway
C08027
UNIT BLOCK-OFF
PAN EL
Fig. 23 -- Typical Access Panel Location
Not all available heater m odules may be used in every
OUTDOOR
ACCESS PANEL
unit. Use only those heater modules that are UL listed for
Electric Heaters
50TCQ units may be equipped with field--installed
accessory electric heaters. The heaters are modular in
design, with heater frames holding open coil resistance
wires strung through ceramic insulators, line--break limit
switches and a c ontrol contactor. One or two heater
modules may be used in a unit.
Heater module s are installed in the compartment below
the indoor (supply) fan outlet. Access is through the
use in a specific size unit. Refer to the label on the unit
cabinet for the list of approved heaters.
Unit heaters are marked with Heater Model Numbers. But
heaters are ordered as and shipped in cartons marked with
a corresponding heater Sales Package part number. See
Table 2 for correlation between heater Model Number and
Sales Package part number.
NOTE: The value in position 9 of the part number differs
between the sales package part number (value is 1 or 3)
and a bare heater model number (value is 0).
indoor access panel. Heater modules slide into the
compartment on tracks along the bottom of the heater
opening. See Fig. 23, Fig. 24 and Fig. 25.
Table 2 – Heater Model Number
Bare Heater Model NumberCRHEATER001A00
INDOOR
ACCESS
PAN EL
C08133
50TCQA
Heater Sales Package PNO
Includes:
Bare Heater
Carton and packing materials
Installation sheet
CRHEATER101A00
DISCONNECT
MOUNTING
LOCATION
MAIN
CONTROL
BOX
EMT OR RIGID CONDUIT
(FIELD-SUPPLIED)
BRACKET AND
CONDUIT
DRIP BOOT
SINGLE
POINT BOX
SINGLE POINT
BOX
MOUNTING
SCREW
CONTROL WIRE TERMINAL BLOCK
HEATER
MODULE
(LOCATION 1)
CENTER
POST
HEATER
MODULE
(LOCATION 2)
MANUAL RESET
LIMIT SWITCH
HEATER
COVERS
HEATER
MOUNTING
BRACKET
C08134
Fig. 24 -- Typical Component Location
15
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.