Improperinstallation,adjustment,alteration,service,
maintenance, or use can cause explosion, fire, electrical
shock or other conditions which may cause personal injury
or property damage. Consult a qualified installer, service
agency, or your distributor or branch for information or
assistance. The qualified installer or agency must use
factory--authorized kits or accessories when modifying this
product. Refer to the individual instructions packaged with
the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloths for brazing operations and
have a fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions attached to
the unit. Consult local building codes and appropriate
national electrical codes (in USA, ANSI/NFPA70, National
Electrical Code (NEC); in Canada, CSA C22.1) for special
requirements.
It is important to recognize safety information. This is the
safety--alert symbol
unit and in instructions or manuals, be alert to the
potential for personal injury.
. When you see this symbol on the
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
Before performing service or maintenance operations
on unit, always turn off main power switch to unit and
install lock(s) and lockout tag(s). Unit may have more
than one power switch.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
Puronr (R--410A) refrigerant systems operate at
higher pressures than standard R--22 systems. Do not
use R--22 service equipment or components on Puron
refrigerant equipment.
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could cause personal
injury or death.
Relieve pressure and recover all refrigerant before
system repair or final unit disposal.
Wear safety glasses and gloves when handling
refrigerants. Keep torches and other ignition sources
away from refrigerants and oils.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal
injury.
Sheet metal parts may have sharp edges or burrs. Use
care and wear appropriate protective clothing, safety
glasses and gloves when handling parts and servicing
air conditioning equipment.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the
safety--alert symbol. DANGER identifies the most serious
hazards which will result in severe personal injury or death.
WARNING signifies hazards which could result in personal
injury or death. CAUTION is used to identify unsafe
practices, which may result in minor personal injury or
product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation,
reliability, or operation.
2
Page 3
Vertical Connections / Economizer
50TC--*16
Horizontal Connections / Economizer
Fig. 1 -- Unit Dimensional Drawing – 16 Size Unit
3
C10770
Page 4
50TC--*16
Fig. 1 -- Unit Dimensional Drawing – 16 Size Unit (cont.)
INSTALLATION
Jobsite Survey
Complete the following checks before installation.
1. Consult local building codes and the NEC (National
Electrical Code) ANSI/NFPA 70 for special installation requirements.
2. Determine unit location (from project plans) or select
unit location.
3. Check for possible overhead obstructions which may
interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (curb
or other) that provides for at least the minimum clearances
required for safety. This includes the clearance to
combustible surfaces, unit performance and service access
below, around and above unit as specified in unit
drawings. See Fig. 2.
NOTE: Consider also the effect of adjacent units.
Unit may be installed directly on wood flooring or on Class
A, B, or C roof--covering material when roof curb is used
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents, relief valves, or other sources of
contaminated air.
C10858
18”
(457)
*
42"
(1067)
Required bottom condensate drain connection.
*
Otherwise, 36” (914mm) for condensate connection.
42"
(1067)
42"
(1067)
C09897
Fig. 2 -- Service Clearance Dimensional Drawing
Although unit is weatherproof, avoid locations that permit
water from higher level runoff and overhangs to fall onto
the unit.
Select a unit mounting system that provides adequate
height to allow for removal and disposal of frost and ice
that will form during the heating--defrost mode as well as
allow installation of condensate trap per requirements.
RefertoStep9—InstallExternalCondensate Trap and
Line – for required trap dimensions.
4
Page 5
Roof Mount —
Checkbuildingcodesforweightdistribution
requirements. Unit operating weight is shown in Table 1.
Step 3 — Inspect Unit
Inspect unit for transportation damage. File any claim
with transportation agency.
Table 1 – Operating Weights
50TC*D16
COMPONENTUNITS LB (KG)
Base Unit1305 (593)
Economizer
Vertical100 (45)
Horizontal115 (52)
H u m id i --- M i Z erRSystem62 (28)
Powered Outlet32 (15)
Curb
14---in/356 mm180 (82)
24---in/610 mm235 (107)
Step 2 — Plan for Sequence of Unit Installation
The support method used for this unit will dictate different
sequences for the steps of unit installation. For example,
on curb--mounted units, some accessories must be
installed on the unit before the unit is placed on the curb.
Review the following for recommended sequences for
installation steps.
Curb--mounted installation —
Install curb
Install field--fabricated ductwork inside curb
Complete installation of the factory--installed
thru--the--base service connection option
Prepare bottom condensate drain connection to suit
planned condensate line routing (refer to Step 9 for
details)
Rig and place unit
Install outdoor air hood
Install condensate line trap and piping
Make electrical connections
Install other accessories
Pad--mounted installation —
Prepare pad and unit supports
Check and tighten the bottom condensate drain
connection plug
Rig and place unit
Convert unit to side duct connection arrangement
Install field--fabricated ductwork at unit duct openings
Install outdoor air hood
Install condensate line trap and piping
Make electrical connections
Install other accessories
Frame--mounted installation —
Frame--mounted applications generallyfollow the
sequence for a curb installation. Adapt as required to
suit specific installation plan.
Confirm before installation of unit that voltage, amperage
and circuit protection requirements listed on unit data
plate agree with power supply provided.
Step 4 — Provide Unit Support
Roof Curb Mount —
Accessory roof curb details and dimensions are shown in
Fig. 3. Assemble and install accessory roof curb in
accordance with instructions shipped with the curb.
NOTE:The gasketing of the unit to the roof curb is
critical for a watertight seal. Install gasket supplied with
the roof curb as shown in Fig. 5. Improperly applied
gasket can also result in air leaks and poor unit
performance.
Curb should be level. This is necessary for unit drain to
function properly. Unit leveling tolerances are show in
Fig. 4. Refer to Accessory Roof Curb Installation
Instructions for additional information as required.
Install insulation, cant strips, roofing felt, and counter
flashing as shown. Ductwork must be attached to curb and
not to the unit.
IMPORTANT:
If the unit’s electric and control wiring is to be routed
through the basepan and the unit is equipped with the
factory--installed Thru--the--Base service option see the
following section:
S Factory--Option Thru--Base Connections
on page 15
If using the field--installed Thru--the--Base accessory
follow the instructions provided with the accessory kit.
NOTE: If electrical connection is not going to occur at
this time, tape or otherwise cover the fittings so that
moisture does not get into the building or conduit in the
interim.
Slab Mount (Horizontal Units Only) —
Provide a level concrete slab that extends a minimum of
6 in. (150 mm) beyond unit cabinet. Install a gravel apron
in front of condenser coil air inlet to prevent grass and
foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb
if required.
Alternate Unit Support
(InLieuofCurborSlabMount)—
A non--combustible sleeper rail can be used in the unit curb
support area. If sleeper rails cannot be used, support the long
sides of the unit with a minimum of 3 equally spaced 4--in. x
4--in. (102 mm x 102 mm) pads on each side.
50TC--*16
5
Page 6
50TC--*16
Fig. 3 -- Roof Curb Details
6
C10772
Page 7
!
WARNING
C
A
B
Fig. 4 -- Unit Leveling Tolerances
MAXIMUM ALLOWABLE
DIFFERENCE IN. (MM)
A-B
0.5” (13)
B-C
1.0” (25)
A-C
1.0” (25)
C10001
Step 5 — Field Fabricate Ductwork
Cabinet return-air static pressure (a negative condition)
shall not exceed 0.35 in. wg (87 Pa) with economizer or
0.45 in. wg (112 Pa) without economizer.
For vertical ducted applications, secure all ducts to roof curb
and building structure. Do not connect ductwork to unit.
Fabricate supply ductwork so that the cross sectional
dimensions are equal to or greater than the unit supply
duct opening dimensions for the first 18 in. (458 mm) of
duct length from the unit basepan.
Insulate and weatherproof all external ductwork, joints,
and roof openings with counter flashing and mastic in
accordance with applicable codes.
Ducts passing through unconditioned spaces must be
insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with
applicable fire codes.
For Units with Accessory Electric Heaters —
All installations require a minimumclearance to
combustible surfaces of 1--in (25 mm) from duct for first
12--in (305 mm) away from unit.
Outlet grilles must not lie directly below unit discharge.
NOTE:A 90--degree elbow must be provided in the
ductwork to comply with UL (Underwriters Laboratories)
code for use with electric heat.
PERSONAL INJURY HAZARD
Failure to follow this warning could cause personal
injury.
For vertical supply and return units, tools or parts could
drop into ductwork and cause an injury. Install a
90--degree turn in the return ductwork between the unit
and the conditioned space. If a 90--degree elbow cannot
be installed, then a grille of sufficient strength and
density should be installed to prevent objects from
falling into theconditioned space. Due to electric
heater, supply duct will require 90--degree elbow.
!
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in damage
to roofing materials.
Membrane roofs can be cut by sharp sheet metal
edges. Be careful when placing any sheet metal parts
on such roof.
CAUTION
Step 6 — Rig and Place Unit
When the unit is ready to be rigged and no longer will be
lifted by a fork truck, the wood protector under the basepan
must be removed. Remove 4 screws from each base rail.
Wood protector will drop to the ground. See instructions on
the unit base rails.
Keep unit upright and do not drop. Spreader bars are
required. Rollers may be used to move unit across a roof.
Level by using unit frame as a reference. See Table 1 and
Fig. 5 for additional information.
Lifting holes are provided in base rails as shown in Fig. 5.
Refer to rigging instructions on unit.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in
equipment damage.
All panels must be in place when rigging. Unit is not
designed for handling by fork truck.
CAUTION
50TC--*16
Before setting the unit onto the curb, recheck gasketing on
curb.
7
Page 8
“B”
914 - 1371
( 36” - 54” )
“C”
PLACE ALL SEAL STRIP IN PLACE BEFORE PLACING
UNIT ON ROOF CURB.
“A”
SEE DETAIL “A”
MAX WEIGHT
LBKGINMMINMMINMM
50TC--*16
UNIT
50TC---D162010912116.0294557.5146159.51510
NOTES:
1. SPREADER BARS REQUIRED — Top damage will occur if spreader bars are not used.
2. Dimensions in ( ) are in millimeters.
3. Hook rigging shac k les through holes in base rail, as shown in detail “ A.” Holes in base rails are centered around
the unit center of gravi t y. Use wood en top to prevent rigging st rap s from damaging unit.
PositioningonCurb—
For full perimeter curbs CRRFCURB074A00 and 075A00,
the clearance between the roof curb and the front and rear
1
base rails should be
the curb and the end base rails should be
/4in (6.4 mm). The clearance between
1
/2in (13 mm). For
retrofit applications with curbs CRRFCURB003A01 and
4A01, the unit should be position as shown in Fig. 6.
5
Maintain the 15.5 in (394 mm) and 8
5
clearances and allow the 22
/16in (567 mm) dimension to
/8in (220 mm)
float if necessary.
DUCT END
ABC
Fig. 5 -- Rigging Details
DIMENSIONS
DETAIL “A”
Original
Position
C10774
New Position
(moved 12.5 in.)
C10003
Fig. 6 -- Retrofit Installation Dimensions
If the alternative condensate drain location through the
bottom of the unit is used in conjunction with a retrofit
curb, the hole in the curb must be moved 12.5 in (320
mm) towards the duct end of the unit. (See Fig. 7.)
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
C10904
Fig. 7 -- Alternative Condensate Drain Hole Positions
IMPORTANT:
If the unit has the factory--installed Thru--the--Base
option, make sure to complete installation of the option
before placing the unit on the roof curb.
See the following section:
S Factory--Option Thru--Base Connections
on page 15
NOTE: If electrical connections is not going to occur at
this time, tape or otherwise cover the fittings so that
moisture does not get into the building or conduit in the
interim.
Remove all shipping materials and top skid. Remove extra
center post from the condenser end of the unit so that the
condenser end of the unit matches Fig. 17 -- 19. Recycle
or dispose of all shipping materials.
8
Page 9
Step 7 — Convert to Horizontal and Connect
Ductwork (when required)
Unit is shipped in the vertical duct configuration. Unit
without factory--installed economizer or return air smoke
detector option may be field--converted to horizontal ducted
configuration using accessory CRDUCTCV001A00. To
convert to horizontal configuration, remove screws from side
duct opening covers and remove covers.
Discardthesupplyductcover.Installaccessory
CRDUCTCV001A00 to cover the vertical supply duct
opening. Use the return duct cover removed from the end
panel to cover the vertical return duct opening.
Field--supplied flanges should be attached to horizontal
duct openings and all ductwork should be secured to the
flanges. Insulate and weatherproof all external ductwork,
joints, and roof or building openings with counter flashing
and mastic in accordance with applicable codes.
Do not cover or obscure visibility to the unit’s informative
data plate when insulating horizontal ductwork.
FILTER ACCESS PANEL
INDOOR COIL ACCESS PANEL
C10004
Fig. 9 -- Typical Access Panel Locations
50TC--*16
Fig. 8 -- Horizontal Conversion Panels
Step 8 — Install Outside Air Hood
Economizer Hood Removal and Setup -Factory Option —
1. The hood is shipped in knock--down form and located
in the return air compartment. It is attached to the
economizer using two plastic tie--wraps.
2. To gain access to the hood, remove the filter access
panel. (See Fig. 9.)
3. Locate and cut the (2) plastic tie--wraps, being careful
to not damage any wiring. (See Fig. 10.)
4. Carefully lift the hood assembly through the filter
access opening and assemble per the steps outlined in
Economizer Hood and Two–Position Hood on page 10.
Remove Hood Parts
Cut Plastic Ties
(2) Places
Economizer
C06108
C10005
Fig. 10 -- Economizer Hood Package Location
Two Position Damper Hood Removal and Setup -Factory Option —
1. The hood is shipped in knock--down form and
assembled to a metal support tray using plastic stretch
wrap. Located in the return air compartment, the
assembly’s metal tray is attached to the basepan and
also attached to the damper using two plastic
tie--wraps.
2. To gain access to the hood, remove the filter access
panel. (See Fig. 9.)
3. Locate the (2) screws holding the metal tray to the
basepan and remove. In order to remove the screws, it
may be necessary to remove the panel underneath the
two--position damper. Remove the two screws. Locate
and cut the (2) plastic tie--wraps securing the
assembly to the damper. (See Fig. 11.) Be careful to
not damage any wiring or cut tie--wraps securing any
wiring.
9
Page 10
4. Carefully lift the hood assembly (with metal tray)
through the filter access opening and assemble per the
steps outlined in Economizer Hood and Two–PositionHood, below.
5. If removed, reattach the panel under the damper.
Hood Parts
Plastic Tie Wrap
Qty (2)
screws provided to attach the hood sides to the hood
top. Use screws provided to attach the hood sides to
the unit. See Fig. 13.
Economizer Hood and Two--Position Hood —
NOTE: If the power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be
used and must be discarded. Save the aluminum filter for
use in the power exhaust hood assembly.
1. The indoor coil access panel will be used as the top of
the hood. If the panel is still attached to the unit, remove the screws along the sides and bottom of the
panel. See Fig. 12.
SIDE
PAN EL
RAIN DEFLECTORS
C10006
HOOD DIVIDER
C10008
Fig. 13 -- Economizer Hood Construction
3. Remove the shipping tape holding the economizer
barometric relief damper in place.
4. Insert the hood divider between the hood sides. See
Fig. 13 and 14. Secure hood divider with 3 screws on
each hood side. The hood divider is also used as the
bottom filter rack for the aluminum filter.
5. Attach the post that separates the filters with the
screws provided.
6. Open the filter clips which are located underneath the
hood top. Insert the aluminum filters into the bottom
filter rack (hood divider). Push the filter into position
past the open filter clips. Close the filter clips to lock
the filters into place. See Fig. 14.
DIVIDER
OUTSIDE
AIR
TOP
PAN EL
INDOOR
COIL
ACCESS
PAN EL
C10007
INDOOR
COIL
ACCESS
PAN EL
CAULK
HERE
Fig. 12 -- Indoor Coil Access Panel Relocation
2. Swing out indoor coil access panel and insert the
hood sides under the panel (hood top). Be careful notto lift the panel too far as it might fall out. Use the
HOOD
CLEANABLE
ALUMINUM
FILTER
BAROMETRIC
RELIEF
FILTER
Fig. 14 -- Economizer Filter Installation
7. Install the two rain deflectors on the edge of the hood
topasshowninFig.12.
8. Caulk the ends of the joint between the unit top panel
and the hood top as shown in Fig. 12.
9. Replace the filter access panel.
10
FILTER
CLIP
C10009
Page 11
Step 9 — Install External Condensate Trap and
Line
The unit has one3/4-in. condensate drain connection on
the end of the condensate pan and an alternate connection
on the bottom. See Fig. 15. Unit airflow configuration
does not determine which drain connection to use. Either
drain connection can be used with vertical or horizontal
applications.
When using the standard side drain connection, ensure the
red plug in the alternate bottom connection is tight. Do
this before setting the unit in place. The red drain pan can
be tightened with a
To use the alternate bottom drain connection, remove the
red drain plug from the bottom connection (use a
square socket drive extension) and install it in the side
drain connection.
CONDENSATE PAN (SIDE VIEW)
STANDARD
SIDE DRAIN
Fig. 15 -- Condensate Drain Pan (Side View)
1
/2--in. square socket drive extension.
1
/2-- i n .
DRAIN
PLUG
(FACTORY-INSTALLED)
ALTERNATE
BOTTOM DRAIN
C08021
Step 10 — Make Electrical Connections
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground may
consist of electrical wire connected to unit ground lug in
control compartment, or conduit approved for electrical
ground when installed in accordance with NEC (National
Electrical Code); ANSI/NFPA 70, latest edition (in
Canada, Canadian Electrical Code CSA [Canadian
Standards Association] C22.1), and local electrical codes.
NOTE:Field--supplied wiring shall conform with the
limitations of minimum 63_F(33_C) rise.
Field Power Supply —
For those units without through--the--curb power, conduit
must be used to route the main power from the condenser
end, via the power entry in the corner post of the unit (see
Figs. 17, 18 and 19) to either the factory option disconnect
or the bottom of the control box. 1” conduit is provided
wrapped around compressor. A second conduit is provided
with factory installed powered convenience outlet. For those
units that require conduit larger than 1”, it must be field
supplied. Figs. 17, 18 and 19 show the various wire routings.
50TC--*16
The piping for the condensate drain and external trap can
be completed after the unit is in place. See Fig. 16.
MINIMUM PITCH
1” (25mm) PER
10’ (3m) OF LINE
TO ROOF
DRAIN
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4” (102) trap is recommended.
BASE RAIL
OPEN
VENT
2˝ (51) MIN
DRAIN PLUG
SEE NOTE
ROOF
CURB
C08022
Fig. 16 -- Condensate Drain Piping Details
All units must have an external trap for condensate
drainage. Install a trap at least 4-in. (102 mm) deep and
protect against freeze-up. If drain line is installed
downstream from the external trap, pitch the line away
from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do
not use a pipe size smaller than the unit connection
3
/4-in.).
(
C10010
Fig. 17 -- Conduit into Factory Option Disconnect
11
C10011
Fig. 18 -- Conduit into Control Box
Page 12
Fig. 19 -- Conduit into Single Point Box
If the field disconnect is larger than 100A, it must be
attached to the unit using accessory CRDISBKT001A00
— disconnect switch bracket — (see Fig. 20). Follow the
instructions provided with this accessory. For smaller field
1
disconnects, be sure to use
50TC--*16
disconnect directly to the end panel, following the
/2” screws to mount the
instructions on the Field Disconnect Warning label (see
Fig. 21). In either case, set the disconnect vertical location
on the unit so that a 90_ fitting can be used to connect the
conduit to the disconnect.
C10012
C10854
Fig. 21 -- Mounting Position for Field Disconnects
(up to 100A)
Field power wires are connected to the unit at line--side
pressure lugs at the main terminal block (TB1) or at
factory--installed option non--fused disconnect switch.
Max wire size is #2 AWG (copper only). (See Fig. 23)
NOTE:TEST LEADS -- Unit may be equipped with
short leads (pigtails) on the field line connection points off
the optional disconnect switch. These leads are for factory
run--test purposes only; remove and discard before
connecting field power wires to unit connection points.
Make field power connections directly to line connection
pressure lugs only.
!
WARNING
C10853
Fig. 20 -- Mounting Position for Field Disconnects
(over 100A)
FIRE HAZARD
Failureto follow thiswarning could resultin
intermittent operation or performance satisfaction.
Do not connect aluminum wire between disconnect
switch and air conditioning unit. Use only copper
wire.(SeeFig.22.)
ELECTRIC
DISCONNECT
SWITCH
COPPER
WIRE ONLY
ALUMINUM
WIRE
A93033
Fig. 22 -- Disconnect Switch and Unit
12
Page 13
All Units —
Units with Factory--Installed Disconnect —
All field wiring must comply with the NEC and local
requirements.
Size wire based on MCA (Minimum Circuit Amps) on the
unit informative plate. See Fig. 23 and the unit label
diagram for power wiring connections to the unit power
terminal blocks and equipment ground. Maximum wire
size is 2/0 AWG per pole.
Provide a ground--fault and short--circuit over--current
protection device (fuse or breaker) per NEC Article 440
(or local codes). Refer to unit informative data plate for
MOCP (Maximum Over--current Protection) device size.
Voltage to compressor terminals during operation must be
within voltage range indicated on unit nameplate. See
Table 9. On 3--phase units, voltages between phases must
be balanced within 2% and the current within 10%. Use
the formula shown in the legend for Table 9 (see Note 2
on page 46) to determine the percent of voltage
imbalance.
All units except 208/230-v units are factory wired for the
voltage shown on the nameplate. If the 208/230-v unit is
to be connected to a 208-v power supply, the control
transformer must be rewired by moving the black wire
1
with the
connection and moving it to the 200-v
/4-in. female spade connector from the 230--v
1
/4-in. male
terminal on the primary side of the transformer. Refer to
unit label diagram for additional information.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
Operation on improper line voltage or excessive phase
imbalance constitutes abuse and may cause damage to
electricalcomponents.Suchoperationwould
invalidate any applicable Carrier warranty.
NOTE: Check all factory and field electrical connections
for tightness.
Units Without Factory--Installed Disconnect —
When installing units, provide a disconnect switch of
adequate size per NEC (National Electrical Code).
Disconnect sizing data is provided on the unit informative
plate. Locate on unit cabinet or within sight of the unit per
national or local codes. Do not cover unit informative
plate if mounting the disconnect on the unit cabinet.
The factory--installed option disconnect switch is located
in a weatherproof enclosure located under the main
control box. The manual switch handle is accessible
through an opening in the access panel. Discard the
factory test leads (see Fig. 23). The factory disconnect is
an 80A disconnect.
Units Without Disconnect Option
TB1
111213
Disconnect
per
NEC
L1
L2L3
208/230-3-60
460-3-60
575-3-60
Units With Disconnect Option
L1
L2
L3
2
Optional
Disconnect
4
Switch
6
Disconnect factory test leads; discard.
1
3
5
Factory
Wiring
C10015
Fig. 23 -- Power Wiring Connections
Convenience Outlets —
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units with convenience outlet circuits may use
multiple disconnects. Check convenience outlet for
power status before opening unit for service. Locate
its disconnect switch, if appropriate, and open it.
Lock--out and tag--out this switch, if necessary.
Two types of convenience outlets are offered on the
50TC--D16 : non--powered and unit--powered. Both types
provide a 125--volt GFCI (ground--fault circuit--interrupter)
duplex receptacle rated at 15--A behind a hinged waterproof
access cover, located on the panel beneath the control box.
See Fig. 24.
50TC--*16
13
Page 14
Pwd-CO
Fuse
Switch
Pwd-CO
Transformer
50TC--*16
Convenience
Outlet
GFCI
Disconnect
Access Panel
Fig. 24 -- Convenience Outlet Location
Non--powered type: This typerequiresthe field
installation of a general--purpose 125--volt 15--A circuit
powered from a source elsewhere in the building. Observe
national and local codes when selecting wire size and
conduit requirements, fuse or breaker requirements and
disconnect switch size and location. Route 125--v power
supply conductors into the bottom of the utility box
containing the duplex receptacle.
C10857
If the convenience outlet transformer is connected to the
line side of the factory disconnect option, route the wires
through the web bushing located on the bottom of the
disconnect box. For the load side wiring to the factory
option disconnect, route the wires through the hole on the
right side of the disconnect. Be sure to create a drip loop
at least 6” long.
NOTICE/AVIS
Convenience Outlet Utilization
Maximum Intermittent Use 15 - Amps
Maximum Continuous Use 8 - Amps
Observe a 50% limit on the circuit
Loading above 8 - Amps
Utilisation de la prise utilitaire
Usage intermittent maximum 15 - Amps
Usage continu maximum 8 - Amps
Observez une limite de 50% sur le circuit
Chargement au-dessus de 8 - Amps
Fig. 25 -- Convenience Outlet Utilization Notice
Test the GFCI receptacle by pressing the TEST button on
the face of the receptacle to trip and open the receptacle.
Check for proper grounding wires and power line phasing
if the GFCI receptacle does not trip as required. Press the
RESET button to clear the tripped condition.
2.050HE501288
C10077
Unit--powered type: A unit--mounted transformer is
factory--installed to stepdown the main power supply
voltage to the unit to 115--v at the duplex receptacle. This
option also includes a manual switch with fuse, located in
a utility box and mounted on a bracket behind the
convenience outlet; access is through the panel beneath
the control box. See Fig. 24.
The primary leads to the convenience outlet transformer
are not factory--connected. Selection of primary power
source is a customer--option. If local codes permit, the
transformer primary leads can be connected at the
line--side terminals on the unit--mounted non--fused
disconnect switch; this will provide service power to the
unit when the unit disconnect switch is open. Other
connection methods will result in the convenience outlet
circuit being de--energized when the unit disconnect
switch is open. See Fig. 26. On a unit without a
unit--mounted disconnect, connect the source leads to the
main terminal block (TB1).
If the convenience outlet transformer is connected to the
line side of a field disconnect, the conduit provided with
the unit must be used to protect the wire as they are routed
from the transformer to the field disconnect. The end of
the conduit with the straight connector attaches to the
field disconnect. The other end does not need to connect
to the transformer; however, the conduit must be routed so
that all wiring is either in the conduit or behind the access
panel.
C08283
UNIT
VOLTAGE
208,
230
460480
575600
CONNECT
AS
240
PRIMARY
CONNECTIONS
L1: RED +YEL
L2: BLU + GRA
L1: RED
Splice BLU + YEL
L2: GRA
L1: RED
L2: GRA
TRANSFORMER
TERMINALS
H1 + H3
H2 + H4
H1
H2 + H3
H4
H1
H2
Fig. 26 -- Unit Powered Convenience Outlet Wiring
Fuse on power type: The factory fuse is a Bussman
“Fusetron” T--15, non--renewable screw--in (Edison base)
type plug fuse.
14
Page 15
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Using unit--mounted convenience outlets: Units with
unit--mounded convenience outlet circuits will often
require that two disconnects be opened to de--energize
all power to the unit. Treat all units as electrically
energized until the convenience outlet power is also
checked and de--energization is confirmed. Observe
National Electrical Code Article 210, Branch Circuits,
for use of convenience outlets.
InstallingWeatherproofCover:Aweatherproof
while-in-use cover for the factory-installed convenience
outlets is now required by UL standards. This cover
cannot be factory-mounted due its depth; it must be
installedatunitinstallation.Forshipment,the
convenience outlet is covered with a blank cover plate.
The weatherproof cover kit is shipped in the unit’s control
box. The kit includes the hinged cover, a backing plate
and gasket.
DISCONNECTALLPOWERTOUNITAND
CONVENIENCE OUTLET. LOCK--OUT AND TAG--OUT
ALL POWER.
Remove the blank cover plate at the convenience outlet;
discard the blank cover.
Loosen the two screws at the GFCI duplex outlet, until
1
approximately
/2-in (13 mm) under screw heads are
exposed. Press the gasket over the screw heads. Slip the
backing plate over the screw heads at the keyhole slots
and align with the gasket; tighten the two screws until
snug (do not over-tighten).
Mount the weatherproof cover to the backing plate as
shown in Fig. 27. Remove two slot fillers in the bottom of
the cover to permit service tool cords to exit the cover.
Check for full closing and latching.
COVER – WHILE-IN-USE
WEATHERPROOF
RECEPTACLE
NOT INCLUDED
Factory--Option Thru--Base Connections —
This service connection kit consists of a1/2--in electrical
1
bulkhead connector and a 1
/2--in electrical bulkhead
connector, connected to an “L” bracket covering the
embossed (raised) section of the unit basepan in the
1
condenser section. See Fig. 28. The
/2--in bulkhead
connector enables the low--voltage control wires to pass
1
through the basepan. The 1
/2--in electrical bulkhead
connector allows the high--voltage power wires to pass
through the basepan.
1
/2” ELECTRICAL
BULKHEAD
CONNECTOR
11/2” ELECTRICAL
BULKHEAD
CONNECTOR
C10907
Fig. 28 -- Thru--the--Base Option, Shipping Position
1. Remove the “L” bracket assembly from the unit.
2. Remove connector plate assembly from the “L”
bracket and discard the “L” bracket, but retain the
washer head screws and the gasket (located between
the “L” bracket and the connector plate assembly).
NOTE:Take care not to damage the gasket, as it is
reused in the following step.
3. Place the gasket over the embossed area in the
basepan, aligning the holes in the gasket to the holes
in the basepan. See Fig. 29.
4. Install the connector plate assembly to the basepan
using 8 of the washer head screws.
NOTE: If electrical connections are not going to occur at
this time, tape or otherwise cover the fittings so that
moisture does not get into the building or conduit in the
interim.
CONNECTOR
PLATE
ASSEMBLY
50TC--*16
BASE PLATE FOR
GFCI RECEPTACLE
Fig. 27 -- Weatherproof Cover Installation
GASKET
C10908
Fig. 29 -- Installing Thru--the--Base Option
C09022
Check tightness of connector lock nuts before connecting
electrical conduits.
15
Page 16
Field--suppliedandfield--installedliquidtightconduit
connectors and conduit may be attached to the connectors on
the basepan. Pull correctly rated high voltage and low
voltage wires through appropriate conduits. Connect the
power conduit to the internal disconnect (if unit is so
equipped) or to the external disconnect (through unit side
panel). Remove one of the two knockouts located on the
bottom left side of the unit control box. Use this hole for the
control conduit.
Units without Thru--Base Connections —
1. Install power wiring conduit through side panel openings. Install conduit between disconnect and control
box.
2. Install power lines to terminal connections as shown
in Fig. 23.
Field Control Wiring —
Typical
Thermostat
Connections
C
G
W2
W1
O/B/Y2
(Note 1)
Y1
R
(Note 2)
Terminal
X
C
G
W2
W1
Y2
Y1
R
Central
Board
T
H
E
R
M
O
S
T
A
T
The 50TC--16D requires an external temperature control
device. This device can be a thermostat (field--supplied)
50TC--*16
or a PremierLink controller (available as factory--installed
option or as field--installed accessory, for use on a Carrier
Comfort Network or as a stand alone control) or the RTU
Open Controller for Building Management Systems using
non--CCN protocols (RTU Open is available as a
factory--installed option only).
Thermostat —
Select a Carrier--approved accessory thermostat. When
electric heat is installed in the 50HC unit, the thermostat
must be capable of energizing the G terminal (to energize
the Indoor Fan Contactor) whenever there is a space call
for heat (energizing the W1 terminal). The accessory
thermostats listed on the unit price pages can provide this
signal but they are not configured to enable this signal as
shipped.
Install the accessory thermostat according to installation
instructions included with the accessory.
Locate the thermostat accessory on a solid wall in the
conditioned space to sense average temperature in
accordance with the thermostat installation instructions.
Note 1: Typical multi-function marking. Follow manufacturer’s configuration
instructions to select Y2. Do not configure for O output.
Note 2: W connection(s) not required on units without electric heating.
Field Wiring
C10909
Fig. 30 -- Typical Low--Voltage Control Connections
Unit without Thru--Base Connection Kit —
Pass the thermostat control wires through the bushing on the
unit end panel. Route the wire through the snap--in wire tie
and up to the web bushing near the control box. Route the
wire through the bushing and into the bottom left side of the
control box after removing one of the two knockouts in the
corner of the box. Use a connector at the control box to
protect the wire as it passes into the control box. Pull the
wires over to the terminal strip at the upper left corner of the
Central Terminal Board (CTB). Use the connector at the
control box and the wire tie to take up any slack in the
thermostat wire to ensure that it will not be damaged by
contact with the condenser coil. See Fig. 31.
If the thermostat contains a logic circuit requiring 24--v
power, use a thermostat cable or equivalent single leads of
different colors with minimum of seven leads. If the
thermostat does not require a 24--v source (no “C”
connection required), use a thermostat cable or equivalent
with minimum of six leads. Check the thermostat
installation instructions for additional features which
might require additional conductors in the cable.
For wire runs up to 50 ft. (15 m), use no. 18 AWG
(American Wire Gage) insulated wire (35_C minimum). For
50 to 75 ft. (15 to 23 m), use no. 16 AWG insulated wire
(35_C minimum). For over 75 ft. (23 m), use no. 14 AWG
insulated wire (35_C minimum). All wire sizes larger than
no. 18 AWG cannot be directly connected to the thermostat
and will require a junction box and splice at the thermostat.
C10018
Fig. 31 -- Thermostat Wire Routing
NOTE:If thru--the--bottom connections accessory is
used, refer to the accessory installation instructions for
information on routing power and control wiring.
16
Page 17
DISCONNECT
MOUNTING
LOCATION
SINGLE
POINT BOX
HEATER
COVERS
MANUAL RESET
LIMIT SWITCH
SINGLE POINT
BOX
MOUNTING
SCREW
Fig. 32 -- Typical Component Location
Heat Anticipator Settings —
Set heat anticipator settings at 0.14 amp for the first stage
and 0.14 amp for second--stage heating, when available.
Electric Heaters
50TC--D16 units may be equipped with field--installed
accessory electric heaters. The heaters are modular in design.
One or two heater modules may be used in a unit.
Heater modules are installed in the compartment below the
indoor (supply) fan outlet. Access is through the indoor
access panel. Heater modules slide into the compartment on
tracks along the bottom of the heater opening. See Fig. 32.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
Not all available heater modules and single point
boxes may be used in every unit. Use only those
heater modules that are UL listed for use in a specific
size unit. Refer to the label on the unit cabinet for the
list of approved heaters and single point boxes.
Single Point Boxes
When heaters are installed, power wiring to both heaters
and the rest of the unit is connected via the single point
box accessory, which will be installed directly under the
unit control box, just to the left of the partition separating
the indoor section (with electric heaters) from the outdoor
section. The single point box has a hinged access cover.
See Fig. 33. The single point box also includes tap
conductors to complete the wiring between the single
point box and the unit’s main control box terminals. Refer
HEATER
MODULE
(LOCATION 1)
HEATER
MODULE
(LOCATION 2)
HEATER
MOUNTING
BRACKET
C10029
to the accessory heater and Single Point Box installation
instructions for details on tap connections.
CONTROL
BOX
BUSHING
SINGLE
POINT BOX
MOUNTING
SCREWS
DRIP BOOT
BRACKET
MOUNTING
SCREWS
POWER
WIRES
FOAM
BUSHING
HEATER
RELAYS
HEATER
MOUNTING
SCREWS
2
1
1
1
2
13
3
21
23
11
13
A
L
LIE
D
P
A
C
O
R
P
.
MO
DE
L
NO
.
O
D
ERI
A
L
N
O.
2
2
.
2
ISTED
AIR
NDITIONING
1
2
3
UIP
ACCESS
346N
.
3
P
/ N
2-
5
6
10-
REV
4
C08136
Fig. 33 -- Typical Single Point Installation
Heater and Supplementary Fuses —
When the unit MOCP device value exceeds 60--A,
unit--mounted supplementary fuses are required for each
heater circuit. These fuses are included in accessory
Single Point Boxes, with power distribution and fuse
blocks.
All fuses on 50TC--*16 units are 60--A. (Note that all
heaters are qualified for use with a 60--A fuse, regardless
of actual heater ampacity, so only 60--A fuses are
necessary.)
17
50TC--*16
Page 18
Heater Low--Voltage Control Connections —
One or two heaters can be installed in the unit. Use the
wiring procedure listed below for each heater as
determined by the number of stages in the heater.
Single Stage Heaters: Single--stage heaters will have an
orange and a brown control wire. Connect these to the
orange and brown wires located on TB4.
LCTB
CONTL
BOARD
Two Stage Heaters: Two--stage heaters will have orange,
purple, red and brown wires. The orange and the purple are
the control wires and the red and brown wires feed the
safety circuit. Connect both the orange and the purple wires
to the orange wire locations of TB4. Connect the red and
brown wires to red and brown wires on TB4. If more than
one heater is installed, repeat the wiring procedure for the
second heater. The 3 locations across the top of TB4 do
allow a switch to be installed in series with some of the
heaters in order to add additional heater control.
50TC--*16
2
3
12
Field
Connections
VIO
ORN
BRN
TB4
BRN
BRN
BRN
ORN
13
VIO
VIO
2
VIO
Elec Htr
VIO
HR2
BRN
VIO
HR1
HR1: On Heater 1 in Position #1
HR2: On Heater 2 in Position #2 (if installed)
Fig. 34 -- Accessory Electric Heater Control Connections
18
BRN
C08331
Page 19
Humidi--MiZerRControl Connections
Humidi--MiZer – Space RH Controller —
NOTE: The Humidi--MiZer is a factory installed option.
The Humidi--MiZer dehumidification system requires a
field--supplied and --installed space relative humidity
control device. This device may be a separate humidistat
control (contact closes on rise in space RH above control
setpoint) or a combination thermostat--humidistat control
device such as Carrier’s EDGE
isolated contact set for dehumidification control. The
humidistat is normally used in applications where a
temperature control is already provided (units with
PremierLinkt control).
To connect the Carrier humidistat (HL38MG029):
1. Route the humidistat 2--conductor cable (field--supplied)
through the bushing the unit’s louvered end panel (see
Fig. 31).
2. Route the cable through the snap--in wire tie and up to
the web bushing near the control box.
3. Feed the cable through the bushing and into the
bottom left side of the control box after removing one
of the two knockouts in the corner of the box. Use a
connector to protect the cable as it enters the control
box.
4. Use the connector and the wire tie to reduce any slack
in the humidistat cable to ensure that it will not be
damaged by contact with the condenser coil (see Fig.
31).
5. Use wire nuts to connect humidistat cable to two
PINK leads in the low–voltage wiring as shown in
Fig. 37.
To connect the Thermidistat device (33CS2PPRH--01):
1. Route the Thermidistat multi--conductor thermostat
cable (field--supplied) through the bushing the unit’s
louvered end panel (see Fig. 31).
2. Route the cable through the snap--in wire tie and up to
the web bushing near the control box.
3. Feed the cable through the bushing and into the
bottom left side of the control box after removing one
of the two knockouts in the corner of the box. Use a
connector to protect the cable as it enters the control
box.
4. Use the connector and the wire tie to reduce any
slack in the thermostat cable to ensure that it will
not be damaged by contact with the condenser coil
(see Fig. 31).
5. The Thermidistat has dry contacts at terminals D1
and D2 for dehumidification operation (see Fig. 38).
The dry contacts must be wired between CTB
terminal R and the PINK lead to the LTLO switch
with field--supplied wire nuts. Refer to the installation
instructionsincludedwiththeCarrierEdge
Thermidistat device (Form 33CS--65SI or latest) for
more information.
R
Pro Thermidistat with
% RELATIVE HUMIDITY
C09295
Fig. 35 -- Accessory Field--Installed Humidistat
50TC--*16
®
C09296
Fig. 36 -- EDGE Pro Thermidistat
19
Page 20
50TC--*16
HUMIDISTAT
Fig. 37 -- Typical Humidi--MiZerRAdaptive Dehumidification System Humidistat Wiring
EDGE Pro THERMIDISTAT
Rc
Rh
W1
G
Y2
C
O/W2/B
Y1
OAT
RRS
SRTN
HUM
D1
D2
V+
Vg
Humidi-MiZer™ FIOP
Unit CTB
THERMOSTAT
X*
C
G
W2
W1
Y2
Y1
R
C11208
*Connection not required.
Fig. 38 -- Typical Rooftop Unit with Humidi--MiZer Adaptive Dehumidification System
with EDGE Pro Thermidistat Device
20
C09298
Page 21
PremierLinkt (Factory Option)
50TC--*16
C08199
Fig. 39 -- PremierLink Controller
NOTE:Refer to Form 33CS--67SI for complete
PremierLink configuration, operating sequences and
troubleshooting information. Have a copy of this manual
available at unit start--up.
The PremierLink controller (see Fig. 39) is compatible
with Carrier Comfort Networkr (CCN) devices. This
control is designed to allow users the access and ability to
change factory--defined settings, thus expanding the
function of the standard unit control board. CCN service
access tools include System Pilot (TM), Touch Pilot (TM)
and Service Tool. (Standard tier display tools Navigatort
and Scrolling Marquee are not suitable for use with latest
PremierLink controller (Version 2.x).)
The PremierLink control is factory--mounted in the
50TC--D16 unit’s main control box to the left of the
Central Terminal Board (CTB). Factory wiring is
completed through harnesses connected to the CTB. Field
connections are made at a 16--pole terminal block (TB3)
located on the bottom shelf of the unit control box in front
of the PremierLink controller. The factory--installed
PremierLink control includes the supply--air temperature
(SAT) sensor. The outdoor air temperature (OAT) sensor is
included in the FIOP/accessory EconoMi$ert2 package.
(See page 40 for accessory enthalpy controls.)
The PremierLink controller requires the use of a Carrier
electronic thermostat or a CCN connection for time
broadcast to initiate its internal timeclock. This is
necessary for broadcast of time of day functions
(occupied/unoccupied).
NOTE: PremierLink controller is shipped in Sensor mode.
To be used with a thermostat, the PremierLink controller
must be configuredto Thermostat mode.Refer to
PremierLink Configuration instructions for Operating Mode.
Fig. 42 -- PremierLink Wiring Schematic with Humidi--MiZer
23
R
C11210
Page 24
Supply Air Temperature (SAT) Sensor —
On FIOP--equipped 50TC--D16 units, the unit is supplied
with a supply--air temperature (SAT) sensor (33ZCSENSAT).
This sensor is a tubular probe type, approx 6--inches (152
mm) in length. It is a nominal 10--k ohm thermistor.
NOTE:The sensor must be mounted in the discharge
airstream downstream of the cooling coil and any heating
devices. Be sure the probe tip does not come in contact
with any of the unit’s heater surfaces.
Outdoor Air Temperature (OAT) Sensor —
The SAT is factory--wired. The SAT probe is wire--tied to
the supply--air opening (on the horizontal opening end) in
its shipping position. Remove the sensor for installation.
Re--position the sensor in the flange of the supply--air
opening or in the supply air duct (as required by local
1
codes). Drill or punch a
/2--in. hole in the flange or duct.
Use the template provided in the unit control box. Use two
field--supplied, self--drilling screws to secure the sensor
probe in a horizontal orientation. See Fig. 43.
50TC--*16
SUPPLY AIR
TEMPERATURE
SENSOR
SUPPLY AIR
RETURN AIR
Fig. 43 -- Typical Mounting Location for Supply Air
Temperature (SAT) Sensor on Small Rooftop Units
ROOF
CURB
C10020
The OAT is factory--mounted in the EconoMi$er2 (FIOP
or accessory). It is a nominal 10k ohm thermistor attached
to an eyelet mounting ring.
EconoMi$er2 —
The PremierLink control is used with EconoMi$er2
(option or accessory) for outdoor air management. The
damper position is controlled directly by the PremierLink
control; EconoMi$er2 has no internal logic device.
Outdoor air management functions can be enhanced with
field--installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors)
Space CO
Outdoor air CO
sensor
2
sensor
2
Refer to Table 2 for accessory part numbers.
Field Connections
Field connections for accessory sensor and input devices
are made at the 16--pole terminal block (TB3) located
beneath the PremierLink control (See Figs. 41 and 42).
Some input devices also require a 24--vac signal source;
connect at CTB terminalR at “THERMOSTAT”
connection strip for this signal source. See connections
figures on following pages for field connection locations
(and for continued connections at the PremierLink board
inputs). Route wires to control box as indicated in Fig. 31.
NOTE:Refer to Form 33CS--67SI (or latest) for
complete PremierLink configuration, operating sequences
and troubleshooting information. Have a copy of this
Table 3 provides a summary of field connections for units
equipped with Space Sensor. Table 4 provides a summary of
field connections for units equipped with Space Thermostat.
manual available at unit set--up.
Table 2 – PremierLink Sensor Usage
OUTDOOR A I R
APPLICATION
Differential Dry Bulb
Temperatur e w i t h
PremierLink
(PremierLink requires
4 --- 2 0 m A A c tu a t o r)
Single Enthalpy with
PremierLink
(PremierLink requires
4 --- 2 0 m A A c tu a t or)
Differential Enthalpy
with PremierLink
(PremierLink requires
4 --- 2 0 m A A c tu a t or)
NOTES:
CO
Sensors (Optional):
2
33ZCSENCO2 --- Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.
33ZCASPCO2 --- Aspirator box used for duct---mounted CO
33ZCT55CO2 --- Space temperature and CO
33ZCT56CO2 --- Space temperature and CO
TEMPERATURE
SENSOR
I n clu d ed ---
CRTEMPSN001A00
I n clu d ed ---
Not Used
I n clu d ed ---
Not Used
room sensor with override.
2
room sensor with override and setpoint.
2
RETURN AIR
TEMPERATURE
SENSOR
R e qu i r ed ---
33ZCT55SPT
or equivalent
---
---
room sensor.
2
24
OUTDOOR A I R
ENTHALPY SENSOR
------
R e qu i r es ---
33CSENTHSW
R e qu i r es ---
33CSENTHSW
or equivalent
RETURN AIR
ENTHALPY SENSOR
---
R e qu i r es ---
33CSENTSEN
or equivalent
Page 25
Table 3 – Space Sensor Mode
TB3 TERMINALFIELD CONNECTIONINPUT SIGNAL
1T5 5 --- S EN / T 56 --- S E NAnalog (10k thermistor)
2RMTOCCDiscrete, 24VAC
3T5 5 --- S EN / T 56 --- S E NAnalog (10k thermistor)
4CMPSAFEDiscrete, 24VAC
5T56--- SETAnalog (10k thermistor)
6FSDDiscrete, 24VAC
7LOOP---PWRAnalog, 24VDC
8SPSDiscrete, 24VAC
9IAQ ---SENA na l o g, 4 --- 2 0 mA
10FILTERDiscrete, 24VAC
11I A Q --- C O M / O A Q --- C O M/ R H --- CO MA n al o g , 4 --- 20 m A
12CCN + (RED)Digital,,5VDC
13OAQ ---SEN/RH---SENA n al o g , 4 --- 20 m A
14CCN Gnd (WHT)Digital, 5VDC
15AUX OUT(Power Exhaust)(Output)Discrete 24VAC
16CCN --- (BLK)Digital, 5VDC
LEGEND:
T 5 5--- S p a ce Te m p e r a tu r e S e ns o rF S D --- F i re S h u td o w n
T 5 6--- S p a ce Te m p e r a tu r e S e ns o rI A Q --- I n do o r A i r Qu a l ity ( C O
CCN--- Carrier Comfort Network (communication bus)OAQ --- Outdoor Air Quality (CO
C M P SA F E--- C om p r e ss o r S a fe t yR H --- R e l a t iv e H u m id i t y
F I L T E R--- D i rt y F i l te r S w i t chS F S --- S u p p ly Fa n S t a t u s
50TC--*16
)
2
)
2
Table 4 – Thermostat Mode
TB3 TERMINALFIELD CONNECTIONINPUT SIGNAL
1RAT SENAnalog (10k thermistor)
2GDiscrete, 24VAC
3RAT SENAnalog (10k thermistor)
4Y1Discrete, 24VAC
5
6Y2Discrete, 24VAC
7LOOP---PWRAnalog, 24VDC
8W1Discrete, 24VAC
9I A Q --- S E NAnalog, 4 - -- 20mA
10W2Discrete, 24VAC
11I A Q --- C O M / O A Q --- C O M/ R H --- CO MAnalog, 4---20mA
The PremierLink controller is factory--shipped configured for
Space Sensor Mode. A Carrier T--55 or T--56 space sensor
must be used. T--55 space temperature sensor provides a
signal of space temperature to the PremierLink control. T--56
provides same space temperature signal plus it allows for
adjustment of space temperature setpoints from the face of
the sensor by the occupants.
2
SW1
3
45
SEN
61
RED(+)
WHT(GND)
BLK(-)
BRN (GND)
BLU (SPT)
CCN COM
SENSOR WIRING
TB3PL
SENJ6-7
SEN
Jumper
1
TB3
3
PL
J6-6
SET
SET
5
J6-5
C10022
Fig. 47 -- PremierLink T--56 Sensor
Connect Thermostat —
A 7--wire thermostat connection requires a 24--v power
source and a common connection. Use the R and C
terminals on the CTB’s THERMOSTAT connection strip
for these. Connect the thermostat’s Y1, Y2, W1, W2 and
G terminals to PremierLink TB3 as shown in Fig. 48.
50TC--*16
Fig. 44 -- T--55 Space Temperature Sensor Wiring
Connect T--55: See Fig. 44 for typical T--55 internal
connections. Connect the T--55 SEN terminals to TB3
terminals 1 and 3 (see Fig. 45).
TB3PL
SENJ6-7
SEN
1
3
Fig. 45 -- PremierLink T--55 Sensor
Connect T--56: See Fig. 46 for T--56 internal connections.
Install a jumper between SEN and SET terminals as
illustrated. Connect T--56 terminals to TB3 terminals 1, 3
and 5 (see Fig. 47).
2
SW1
3
45
SEN
61
RED(+)
WHT(GND)
BLK(-)
SET
BRN (GND)
BLU (SPT)
BLK
(T56)
CCN COM
SENSOR WIRING
JUMPER
TERMINALS
AS SHOWN
J6-6
C08201
C10023
If the 50TC--D16 unit is equipped with factory--installed
smoke detector(s), disconnect the factory BLU lead at
TB3--6 (Y2) before connecting the thermostat. Identify the
BLU lead originating at CTB--DDC--1; disconnect at
TB3--6 and tape off. Confirm that the second BLU lead at
TB3--6 remains connected to PremierLink J4--8.
SPACE
THERMOSTAT
R
GJ4-12
Y1
Y2
W1
W2
C
CTB
THERMOSTAT
R
TB3
2
4
6
8
10
C
THERMOSTAT
PL
J4-10
J4-8
J4-6
J4-4
CTB
C10283
Fig. 48 -- Space Thermostat Connections
If the 50TC--D16 unit has an economizer system and
free--cooling operation is required, a sensor representing
Return AirTemperature mustalsobe connected
(field--supplied and installed). This sensor may be a T--55
Space Sensor (see Fig. 44) installed in the space or in the
return duct, or it may be sensor PNO 33ZCSENSAT,
installed in the return duct. Connect this sensor to TB3--1
and TB3--3 per Fig. 45.
Configure the unit for Thermostat Mode —
Connect to the CCN bus using a CCN service tool and
navigate to PremierLink Configuration screen for Operating
Mode. Default setting is Sensor Mode (value 1). Change the
value to 0 to reconfigure the controller for Thermostat Mode.
CoolWarm
Fig. 46 -- T--56 Internal Connections
C08202
When the PremierLink is configured for Thermostat
Mode, these functions are not available: Fire Shutdown
(FSD), Remote Occupied (RMTOCC), Compressor Safety
(CMPSAFE), Supply Fan Status (SFS), and Filter Pressure
Switch (FILTER).
26
Page 27
Economizer Controls
Indoor Air Quality (CO2sensor) —
The indoor air quality sensor accessory monitors space
carbon dioxide (CO
monitor IAQ levels. Several types of sensors are available,
for wall mounting in the space or in return duct, with and
without LCD display, and in combination with space
temperature sensors. Sensors use infrared technology to
measure the levels of CO
The CO
sensors are all factory set for a range of 0 to
2
2000 ppm and a linear mA output of 4 to 20. Refer to the
instructions supplied with the CO
requirements and terminal locations. See Fig. 49 for
typical CO
sensor wiring schematic.
2
To accurately monitor the quality of the air in the
conditioned air space, locate the sensor near a return--air
grille (if present) so it senses the concentration of CO
leaving the space. The sensor should be mounted in a
location to avoid direct breath contact.
Do not mount the IAQ sensor in drafty areas such as near
supply ducts, open windows, fans, or over heat sources.
Allow at least 3 ft (0.9 m) between the sensor and any
corner. Avoid mounting the sensor where it is influenced
by the supply air; the sensor gives inaccurate readings if
the supply air is blown directly onto the sensor or if the
supply air does not have a chance to mix with the room air
before it is drawn into the return airstream.
) levels. This information is used to
2
present in the space air.
2
sensor for electrical
2
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
sensor. See Fig. 49. Connect the 4--20 mA terminal to
terminal TB3--9 and connect the SIG COM terminal to
terminal TB3--11. See Fig. 50.
IAQ Sensor
SENJ5-5
COM
24 VAC
TB3
9
TB3
11
Fig. 50 -- Indoor CO2Sensor (33ZCSENCO2)
Connections
Refer to Form 33CS--67SI, PremierLink Installation,
Start--up, and Configuration Instructions, for detailed
configuration information
Outdoor Air Quality Sensor
2
(PNO 33ZCSENCO2 plus weatherproof enclosure) —
The outdoor air CO
dioxide (CO
) levels in the outside ventilation air and
2
sensor is designed to monitor carbon
2
interface with the ventilation damper in an HVAC system.
The OAQ sensor is packaged with an outdoor cover. See
Fig. 51. The outdoor air CO
sensor must be located in the
2
economizer outside air hood.
PL
J5-3
C10284
50TC--*16
+
0-10VDC
-
SIG COM
+
4-20mA
ALARM
NC
COM
RELAY
}
CONTACTS
NO
24 VAC
HG
OR
+
-
24 VDC
2
1
J3J4
5
1
4
32
7
6
8
C08635
Fig. 49 -- Indoor/Outdoor Air Quality (CO2)Sensor
(33ZCSENCO2) -- Typical Wiring Diagram
Wiring the Indoor Air Quality Sensor: For each sensor,
use two 2--conductor 18 AWG (American Wire Gage)
twisted--pair cables (unshielded) to connect the separate
isolated 24 vac power source to the sensor and to connect
the sensor to the control board terminals.
COVER REMOVEDSIDE VIEW
C07135
Fig. 51 -- Outdoor Air Quality Sensor Cover
Wiring the Outdoor Air CO
Sensor: A dedicated
2
power supply is required for this sensor. A two--wire cable
is required to wire the dedicated power supply for the
sensor. The two wires should be connected to the power
supply and terminals 1 and 2.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
OAQ sensor. See Fig. 49. Connect the 4 to 20 mA
terminal to the TB3--13 terminal of the 50TC--D16.
Connect the SIG COM terminal to the TB3--11 terminal of
the 50TC--D16. See Fig. 52.
27
Page 28
IAQ Sensor
SENJ5-2
COM
24 VAC
TB3
13
TB3
11
Fig. 52 -- Outdoor CO2Sensor Connections
Space Relative Humidity Sensor or Humidistat
Connections —
SpaceRelativeHumidity Sensor connections:The
accessory space relative humidity sensor (33ZCSENSRH-01)
is installed on an interior wall to measure the relative
humidity of the air within the occupied space.
The use of a standard 2 X 4 inch electrical box to
accommodate the wiring is recommended for installation.
The sensor can be mounted directly on the wall, if
acceptable by local codes.
50TC--*16
!
CAUTION
PL
J5-3
C10285
MOUNTING
HOLES
Io
Gnd
Vin
Vo
SW2
123456
ON
WIRING
OPENING
C11084
Fig. 53 -- Space Relative Humidity Sensor Installation
TB3-7
UNIT DAMAGE HAZARD
Failure to follow this caution may result in
permanent damage to the sensor.
DO NOT clean or touch the sensing element with
chemical solvents as they can permanently damage the
sensor.
!
CAUTION
UNIT PERFORMANCE HAZARD
Failure to follow this caution will result in inaccurate
sensor readings.
DO NOT mount the sensor in drafty areas such as near
heating or air--conditioning ducts, open windows, fans,
or over heat sources such as baseboard heaters,
radiators, or wall--mounted dimmers. Sensors mounted
in those areas will produce inaccurate readings.
If the sensor is installed directly on a wall service, install the
humidity sensor using 2 screws and 2 hollow wall anchors
(field supplied). Do not over tighten screws. See Fig. 53.
The sensor must be mounted vertically on the wall. The
Carrier logo should be orientated correctly when the
sensor is properly mounted.
Avoid corner locations. Allow at least 4 ft between the
sensor and any corner. Airflow near corners tends to be
reduced, resulting in erratic sensor readings. The sensor
should be vertically mounted approximately 5 ft up from
the floor, beside the space temperature sensor.
For wiring distances up to 500 feet, use a 3--conductor, 18
or 20 AWG cable. ACCN communication cable can be
used, although the shield is not required. The shield must
be removed from the sensor end of the cable if this cable
is used. See Fig. 54 for wiring details.
TB3-13
RED
BLACK
IoVoVin Gnd
C11085
Fig. 54 -- Space Relative Humidity Sensor Connection
The power for the sensor is provided by the PremierLink
control on terminal J5--4 (+33 to +35vdc).
To wire the sensor:
1. At the sensor, remove 4 inches of the jacket from the
cable. Strip
or. Route the cable through the wire clearance opening in the center of the sensor. See Fig. 53.
2. Connect a field--supplied BLACK wire to the sensor
screw terminal marked Vin.
3. Connect a field--supplied RED wire into the sensor
screw terminal marked Io.
4. Connect the field--supplied RED wire from the sensor
to TB3--13.
5. Connect the field--supplied BLACK wire from the
sensor to TB3--7.
Humidistat connections: A humidistat can not be directly
connected to the PremierLink controller. Follow the
instructions on pages 19 & 20 to connect a humidistat or a
thermostat as an electromechanical device.
1
/4inch of insulation from each conduct-
28
Page 29
Smoke Detector/Fire Shutdown (FSD) —
This function is available only when PremierLink is
configured for (Space) Sensor Mode. The unit is
factory--wired for PremierLink FSD operation when
PremierLink is factory--installed.
On 50TC--D16 units equipped with factory--installed
SmokeDetector(s),thesmokedetectorcontroller
implements the unit shutdown through its NC contact set
connected to the unit’s CTB input. The FSD function is
initiated via the smoke detector’s Alarm NO contact set.
The PremierLink communicates the smoke detector’s
tripped status to the CCN building control. See See Figs.
41 and 42, the PremierLink wiring schematics.
Filter Status Switch —
Connect one side of the switch’s NO contact set to CTB’s
THERMOSTAT--R terminal. Connect the other side of the
NO contact set to TB3--8. Setpoint for Supply Fan Status
is set at the switch. See Fig. 56.
Fan (Pressure) Switch (NO, close on rise in pressure)
CTB
Thermostat
R
TB3
8
PL
J4-6
C10287
Fig. 56 -- PremierLink Wiring Fan Pressure Switch
Connection
This function is available only when PremierLink is
configured for (Space) Sensor Mode.
PremierLink control can monitor return filter status in two
ways: By monitoring a field--supplied/installed filter
pressure switch or via supply fan runtime hours.
Using switch input: Install the dirty filter pressure switch
according to switch manufacturer’s instructions, to
measure pressure drop across the unit’s return filters.
Connect one side of the switch’s NO contact set to CTB’s
THERMOSTAT--R terminal. Connect the other side of the
NO contact set to TB3--10. Setpoint for Dirty Filter is set
at the switch. See Fig. 55.
Filter Switch (NO, close on rising pressure (high drop))
CTB
Thermostat
R
TB3
10
PL
J4-4
C10286
Fig. 55 -- PremierLink Filter Switch Connection
When the filter switch’s NO contact set closes as filter
pressure drop increases (indicating dirt--laden filters), the
input signal to PremierLink causes the filter status point to
read “DIRTY”.
Using Filter Timer Hours: Refer to Form 33CS--67SI for
instructions on using the PremierLink Configuration
screens and on unit alarm sequence.
Supply Fan Status Switch —
The PremierLink control can monitor supply fan operation
through a field--supplied/installed differential pressure
switch. This sequence will prevent (or interrupt) operation
of unit cooling, heating and economizer functions until
the pressure switch contacts are closed indicating proper
supply fan operation.
Remote Occupied Switch —
The PremierLink control permits a remote timeclock to
override the control’s on--board occupancy schedule and
place the unit into Occupied mode. This function may also
provide a “Door Switch” time delay function that will
terminate cooling and heating functions after a 2--20 minute
delay.
Connect one side of the NO contact set on the timeclock
to CTB’s THERMOSTAT--R terminal. Connect the other
side of the timeclock contact to the unit’s TB3--2 terminal.
Remote Occupied
Time Clock
LCTB
Thermostat
R
TB3
2
PL
J4-12
C10288
Fig. 57 -- PremierLink Wiring Remote Occupied
Refer to Form 33CS--67SI for additional information on
configuring the PremierLink control for Door Switch
timer function.
Power Exhaust (output) —
Connect the accessory Power Exhaust contactor coils(s)
per Fig. 58.
Power Exhaust
PEC
GRA
TAN
TB3
15
CTB
THERMOSTAT
C
PL
J8-3
C10289
Fig. 58 -- PremierLink Power Exhaust Output
Connection
50TC--*16
Install the differential pressure switch in the supply fan
section according to switch manufacturer’s instructions.
Arrange the switch contact to be open on no flow and to
close as pressure rises indicating fan operation.
29
Page 30
CCN Communication Bus —
The PremierLink controller connects to the bus in a daisy
chain arrangement. Negative pins on each component
must be connected to respective negative pins, and
likewise, positive pins on each component must be
connected to respective positive pins. The controller
signal pins must be wired to the signal ground pins.
Wiring connections for CCN must be made at the 3--pin
plug.
At any baud (9600, 19200, 38400 baud), the number of
controllers is limited to 239 devices maximum. Bus length
may not exceed 4000 ft, with no more than 60 total
devices on any 1000--ft section. Optically isolated RS--485
repeaters are required every 1000 ft.
NOTE: Carrier device default is 9600 band.
Communications Bus Wire Specifications -- The CCN
CommunicationBuswiringisfield--suppliedand
field--installed. It consists of shielded 3--conductor cable
with drain (ground) wire. The cable selected must be
50TC--*16
identical to the CCN Communication Bus wire used for
the entire network.
The communication bus shields must be tied together at
each system element. If the communication bus is entirely
within one building, the resulting continuous shield must
be connected to ground at only one single point. If the
communication bus cable exits from one building and
enters another building, the shields must be connected to
the grounds at a lightning suppressor in each building (one
point only).
Connecting CCN Bus:
NOTE: When connecting the communication bus cable,
acolor codesystemfortheentirenetwork is
recommended to simplify installation and checkout. See
Table 6 for the recommended color code.
Table 6 – Color Code Recommendations
SIGNAL TYPE
+Red1
GroundWhite2
---Black3
CCN BUS WIRE
COLOR
CCN PLUG PIN
NUMBER
See Table 5 for recommended cable.
Table 5 – Recommended Cables
MANUFACTURERCABLE PART NO.
Alpha2413 or 5463
AmericanA22503
Belden8772
Columbia02525
NOTE:Conductors and drain wire must be at least 20
AWG, stranded, and tinned copper. Individual conductors
must be insulated with PVC, PVC/nylon, vinyl, Teflon, or
polyethylene. An aluminum/polyester 100% foil shield and
an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon
with a minimum operating temperature range of --20_Cto
60_C is required. Do not run communication wire in the
same conduit as or next to any AC voltage wiring.
Connect the CCN (+) lead (typically RED) to the unit’s
TB3--12 terminal. Connect the CCN (ground) lead
(typically WHT) to the unit’s TB3--14 terminal. Connect
the CCN (--) lead (typically BLK) to the unit’s TB3--16
terminal. See Fig. 59.
CCN Bus
PL
J2-1
J2-2GND (WHT)
J2-3– (BLK)16
C10290
+ (RED)
TB3
12
TB3
14
TB3
Fig. 59 -- PremierLink CCN Bus Connections
30
Page 31
RTU Open Control System
The RTU Open control is factory--mounted in the
50TC--D16 unit’s main control box, to the left of the CTB.
See Fig. 61. Factory wiring is completed through
harnesses connected to the CTB. Field connections for
RTU Open sensors will be made at the Phoenix connectors
on the RTU Open board. The factory--installed RTU Open
control includes the supply--air temperature (SAT) sensor.
The outdoor air temperature (OAT) sensor is included in
the FIOP/accessory EconoMi$er2 package.
The RTU Open controller is an integrated component of the
Carrier rooftop unit. Its internal application programming
provides optimum performance and energy efficiency. RTU
Open enables the unit to run in 100% stand--alone control
mode, Carrier’s I--Vu Open network, or a Third Party
Building AutomationSystem (BAS). On--boardDIP
switches allow you to select your protocol (and baud rate) of
choice among the four most popular protocols in use today:
BACnet, Modbus, Johnson N2 and LonWorks. (See Fig. 60.)
Refer to Table 7, RTU Open Controller Inputs and Outputs
for locations of all connections to the RTU Open board.
50TC--*16
Fig. 60 -- RTU--Open Multi--Protocol Control Board
Fig. 61 -- 50TC--D16 Control Box Component Locations
31
C10811
C11194
Page 32
50TC--*16
Fig. 62 -- RTU Open System Control Wiring Diagram
32
C11211
Page 33
50TC--*16
Fig. 63 -- RTU--Open System Control Wiring Diagram with Humidi--MiZer
Space Relative Humidityspace_rhA I (4 --- 2 0 m a)
Supply Fan Status*sfan_statusDI (24 VAC)
Filter Status*filter_statusDI (24 VAC)
Door Contact Input*door_contact_statusDI (24 VAC)
LEGEND
AI --- A n a l o g In p u t
AO --- A n a l o g Ou tput
DI --- D i s crete I n p u t
DO --- Discrete Output
* These inputs (if installed) take the place of the default input on the specific channel according to schematic.
Paral l e l pi n s J5 --- 1 = J2 --- 6, J 5 --- 3 = J1 --- 1 0 , J 5 --- 5 = J 1 --- 2 ar e u s e d f or f i e l d --- in stall a tion.
BACnet OBJECT
NAME
DEDICATED INPUTS
CONFIGURABLE INPUTS
TYPE OF I/O
OUTPUTS
CONNECTION PIN
NUMBER(S)
J 4 --- 2 o r J 4 --- 5Outdoor Air CO2oaqAI (4 --- 20 ma )
J 5 --- 1 o r J 5 --- 3 o r
J55orJ5---7
The RTU Open controller requires the use of a Carrier
space sensor. A standard thermostat cannot be used with
the RTU Open system.
Supply Air Temperature (SAT) Sensor —
On FIOP--equipped 50TC--D16 unit, the unit is supplied with
a supply--air temperature (SAT) sensor (33ZCSENSAT). This
sensor is a tubular probe type, approx 6--inches (12.7 mm) in
length. It is a nominal 10--k ohm thermistor.
The SAT is factory--wired. The SAT probe is wire--tied to
the supply--air opening (on the horizontal opening end) in
its shipping position. Remove the sensor for installation.
Re--position the sensor in the flange of the supply--air
opening or in the supply air duct (as required by local
1
codes). Drill or punch a
/2--in. hole in the flange or duct.
Use two field--supplied, self--drilling screws to secure the
sensor probe in a horizontal orientation. See Fig. 43.
Outdoor Air Temperature (OAT) Sensor —
The OAT is factory--mounted in the EconoMi$er2 (FIOP
or accessory). It is a nominal 10k ohm thermistor attached
to an eyelet mounting ring.
EconoMi$er2 —
The RTU Open control is used with EconoMi$er2 (option
or accessory) for outdoor air management. The damper
position is controlled directly by the RTU Open control;
EconoMi$er2 has no internal logic device.
Outdoor air management functions can be enhanced with
field--installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors)
Space CO
Outdoor air CO
sensor
2
sensor
2
Field Connections
Field connections for accessory sensors and input devices
are made the RTU Open, at plugs J1, J2, J4, J5, J11 and
J20. All field control wiring that connects to the RTU
Open must be routed as shown in Fig. 31. This routing
provides the UL required clearance between high--and
low--voltage wiring. Connect to the wires to the
removable Phoenix connectors and then reconnect the
connectors to the board.
34
Page 35
Space Temperature (SPT) Sensors —
There are two types of SPT sensors available from Carrier,
resistive input non-communicating (T55, T56, and T59)
and Rnet communicating (SPS, SPPL, SPP, and SPPF)
sensors. Each type has a variety of options consisting of:
timed override button, set point adjustment, a LCD
screen, and communication tie in. Space temperature can
be also be written to from a building network or zoning
system. However, it is still recommended that return air
duct sensor be installed to allow stand-alone operation for
back-up. Refer to the configuration section for details on
controller configurations associated with space sensors.
Field connections to T--55, T--56 and T--59 are provided as
examples.
S 33ZCT55SPT, space temperature sensor with override
button (T--55)
S 33ZCT56SPT, space temperature sensor with override
button and setpoint adjustment (T--56)
S 33ZCT59SPT, space temperature sensor with LCD
(liquid crystal display) screen, override button, and
setpoint adjustment (T--59)
Connect T--59: The T--59 space sensor requires a
separate, isolated power supply of 24 VAC. See Fig. 66
for internal connections at the T--59. Connect the SEN
terminal (BLU) to RTU Open J20--1. Connect the COM
terminal (BRN) to J20--2. Connect the SET terminal (STO
or BLK) to J20--3.
BLK (STO)
BRN (COM)
BLU (SPT)
ORSETSEN
OPB COM- PWR+
24 VAC
J20-3
J20-2
J20-1
SENSOR
WIRING
POWER
WIRING
50TC--*16
Use 20 gauge wire to connect the sensor to the controller.
The wire is suitable for distances of up to 500 ft. Use a
three--conductor shielded cable for the sensor and setpoint
adjustmentconnections. Ifthe setpointadjustment
(slidebar) is not required, then an unshielded, 18 or 20
gauge, two--conductor, twisted pair cable may be used.
Connect T--55: See Fig. 44 for typical T--55 internal
connections. Connect the T--55 SEN terminals to RTU Open
J20--1 and J20--2. See Fig. 64.
SEN
SEN
J20-1
J20-2
C08460
Fig. 64 -- RTU Open T--55 Sensor Connections
Connect T--56: See Fig. 46 for T--56 internal connections.
Install a jumper between SEN and SET terminals as
illustrated. Connect T--56 terminals to RTU Open J20--1,
J20--2 and J20--3 per Fig. 65.
SENJ20-1
NOTE: Must use a separate isolated transformer.
C10291
Fig. 66 -- Space Temperature Sensor Typical Wiring
(33ZCT59SPT)
Indoor Air Quality (CO
sensor) —
2
The indoor air quality sensor accessory monitors space
carbon dioxide (CO
) levels. This information is used to
2
monitor IAQ levels. Several types of sensors are available,
for wall mounting in the space or in return duct, with and
without LCD display, and in combination with space
temperature sensors. Sensors use infrared technology to
measure the levels of CO
The CO
sensors are all factory set for a range of 0 to
2
present in the space air.
2
2000 ppm and a linear mA output of 4 to 20. Refer to the
instructions supplied with the CO
sensor for electrical
2
requirements and terminal locations. See Fig. 49 for
typical CO
sensor wiring schematic.
2
To accurately monitor the quality of the air in the
conditioned air space, locate the sensor near a return--air
grille (if present) so it senses the concentration of CO
leaving the space. The sensor should be mounted in a
location to avoid direct breath contact.
2
SEN
Jumper
SET
SET
J20-2
J20-3
Fig. 65 -- RTU Open T--56 Sensor Connections
C08461
Do not mount the IAQ sensor in drafty areas such as near
supply ducts, open windows, fans, or over heat sources.
Allow at least 3 ft (0.9 m) between the sensor and any
corner. Avoid mounting the sensor where it is influenced
by the supply air; the sensor gives inaccurate readings if
the supply air is blown directly onto the sensor or if the
supply air does not have a chance to mix with the room air
before it is drawn into the return airstream.
35
Page 36
Wiring the Indoor Air Quality Sensor: For each sensor,
use two 2--conductor 18 AWG (American Wire Gage)
twisted--pair cables (unshielded) to connect the separate
isolated 24 vac power source to the sensor and to connect
the sensor to the control board terminals.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
sensor. See Fig. 49. Connect the 4--20 mA terminal to
RTU Open J4--2 and connect the SIG COM terminal to
RTU Open J4--3. See Fig. 67.
IAQ Sensor
4-20mA
SIG COM
24 VAC
50TC--*16
Fig. 67 -- RTU Open / Indoor CO2Sensor
(33ZCSENCO2) Connections
Outdoor Air Quality Sensor0
(PNO 33ZCSENCO2 plus weatherproof enclosure) —
The outdoor air CO
dioxide (CO
) levels in the outside ventilation air and
2
sensor is designed to monitor carbon
2
interface with the ventilation damper in an HVAC system.
The OAQ sensor is packaged with an outdoor cover. See
Fig. 51. The outdoor air CO
sensor must be located in the
2
economizer outside air hood.
Wiring the Outdoor Air CO
Sensor: A dedicated
2
power supply is required for this sensor. A two--wire cable
is required to wire the dedicated power supply for the
sensor. The two wires should be connected to the power
supply and terminals 1 and 2.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
OAQ sensor. See Fig. 49. Connect the 4 to 20 mA
terminal to RTU Open J4--5. Connect the SIG COM
terminal to RTU Open J4--6. See Fig. 68.
J4-2
J4-3
C10738
Space Relative Humidity Sensor or Humidistat —
Humidi--MiZer
R
Control Wiring: In units equipped
with the Humidi--MiZer option there are two pink (PNK)
wires loose in the control box used to control the
dehumidification function of the unit. These pink wires
are meant to be tied to a space humidistat or thermidistat
on an electromechanical unit. On RTU Open equipped
units these pink wires must be connected to J11--7 & 8 to
allow the Open board to operate the dehumidification
function for the unit. Disconnect the J11 Phoenix style
connector from the board and use the plug screws to
secure the pink wires in pins 7 and 8, reconnect the plug
to the board at J11.
Relative Humidity Sensors (Space or Duct Mounted):
The accessory space humidity sensor (33ZCSENSRH-01)
or duct humidity sensor (33ZCSENDRH-01) is used to
measure the relative humidity of air within the space or
return air duct. The RH reading is used to control the
Humidi--MiZer option of the rooftop unit. For wiring
distances up to 500 ft (152 m), use a 3--conductor, 18 or
20 AWG shielded cable. The shield must be removed
from the sensor end of the cable and grounded at the unit
end. The current loop power for sensor is provided by the
RTU Open controller as 24vdc. Refer to the instructions
suppliedwiththeRHsensor fortheelectrical
requirementsandterminallocations.RTUOpen
configurations must be changed after adding an RH
sensor. See Fig. 69 and 70 for typical RH sensor wiring.
S J4--1 or J4--4 = 24vdc loop power
S J4--2 or J4--5 = 4--20mA signal input
NOTE: The factory default for dehumidification control
is normally open humidistat.
MOUNTING
HOLES
Io
Gnd
Vin
Vo
WIRING
OPENING
OAQ Sensor/RH Sensor
4-20mA
SIG COM
24 VAC
Fig. 68 -- RTU Open / Outdoor CO2Sensor
(33ZCSENCO2) Connections
J4-5
J4-6
C10739
SW2
123456
ON
Vin - J4-1 or J4-4 24Vdc
Io - J4-2 or J4-5 -20mA output
Fig. 69 -- Space Relative Humidity Sensor Typical Wiring
36
C11087
Page 37
J4-1 or J4-4 + 24 VDC Supply Voltage
J4-2 or J4-5 (-) 4 to 20 mA Current Loop Output
to RTU-OPEN
4-20 VAC GND 0-5V
mA or or
VDC 0-10V
SPAN
Relative Humidity Sensor
(Polarized Male Connector)
Humidistat: The accessory humidistat provides the RTU
Open insight to the relative humidity in the space. The
humidistat reads the RH level in the space and compares it
to its setpoint to operate a dry contact. The humidistat is a
dedicated input on the configurable input 9 and tells the
RTU Open when the RH level is HIGH or LOW. The
normal condition for humidity is LOW. A normally open
humidistatis the factory defaultcontrol forthe
Humidi--MiZer
R
option.
To wire in the field:
S J5--8 = 24 VAC source for dry contact
S J5--7 = Signal input
Smoke Detector/Fire Shutdown (FSD) —
On 50TC--D16 units equipped with factory--installed
SmokeDetector(s),thesmokedetectorcontroller
implements the unit shutdown through its NC contact set
connected to the unit’s CTB input. The FSD function is
initiated via the smoke detector’s Alarm NO contact set.
The RTU Open controller communicates the smoke
detector’s tripped status to the BAS building control. See
Figs. 62 and 63, the RTU Open System Control Wiring
Diagrams.
TheFireShutdownSwitchconfiguration,
→
MENU
Config→Inputs→input 5, identifies the normally
open status of this input when there is no fire alarm.
field--installed accessory. This accessory detects plugged
filters. When installing this accessory, the unit must be
configuredforfilterstatusbysetting
→
MENU
Config→Inputs→input3,5,8,or9to Filter
Status and normally open (N/O) or normally closed (N/C).
Input 8 or 9 is recommended for easy of installation. Refer
to Fig. 60 and Fig. 62 or Fig. 63 for wire terminations at
J5.
C10839
Fan Status: The fan status accessory is a field--installed
accessory. This accessory detects when the indoor fan is
blowing air. When installing this accessory, the unit must
beconfiguredforfanstatusbysetting
→
MENU
Config→Inputs→input3,5,8,or9to Fan
Status and normally open (N/O) or normally closed (N/C).
Input 8 or 9 is recommended for easy of installation. Refer
to Fig. 60 and Fig. 62 or Fig. 63 for wire terminations at
J5.
Remote Occupancy: The remote occupancy accessory is
a field--installed accessory. This accessory overrides the
unoccupied mode and puts the unit in occupied mode.
When installing this accessory, the unit must be
configuredforremoteoccupancybysetting
→
MENU
Config→Inputs→input3,5,8,or9to Remote
Occupancy and normally open (N/O) or normally closed
(N/C).
→
Also set MENU
Schedules→occupancy source to DI
on/off. Input 8 or 9 is recommended for easy of
installation. Refer to Fig. 60 and Table 7 for wire
terminations at J5.
Power Exhaust (output): The relay used by the RTU
Open board to control power exhaust is a dry contact
which means it does not have 24vac. This 24vac must be
connected to the relay to allow it to operate the power
exhaust relay in the PE accessory. A 24vac source must be
provided to J11--2 on the RTU Open control board. This
can be provided by the unit’s transformer from various
sources. The “R” terminal on the unit’s low voltage
terminal board (LVTB) is a logical source. Refer to Fig. 60
and Fig. 62 or Fig. 63 for wire terminations at J11.
50TC--*16
37
Page 38
Communication Wiring -- Protocols
The RTU Open can be set to communicate on four
different protocols: BACnet, Modbus, N2, and LonWorks.
General —
Protocols are the communication languages spoken by
control devices. The main purpose of a protocol is to
communicate information in the most efficient method
possible. Different protocols exist to provide different
kinds of information for different applications. In the BAS
application, many different protocols are used, depending
on manufacturer. Protocols do not change the function of
a controller; just make the front end user different.
Switch 3 (SW3) on the board is used to set protocol and
baud rate. Switches 1 and 2 (SW1 and SW2) are used to
set the board’s network address. See Fig. 71 and 72 for
protocol switch settings and address switches. The 3rd
party connection to the RTU Open is through plug J19.
See Fig. 73 for wiring.
NOTE: Power must be cycled after changing the SW1--3
switch settings.
Refer to the RTU Open Controller Integration Guide
(Catalog No. 11--808--428--01) for more detailed information
on protocols, 3rd party wiring, and networking.
SW3 Protoco l Selection
PROTOCOLDS8DS7DS6DS5DS4DS3DS2DS1
BACnet MS/TP
(Master)
Modbus
50TC--*16
(Slave)
N2
(Slave)
LonWorksUnusedONONOFFONOFFOFFOFF
NOTE:
DS = Dip Switch
BACnet MS/TP SW3 example shown
UnusedOFFOFFOFFONOFFSelect BaudSelect Baud
UnusedOFFOFFONONOFFSelect Baud Select Baud
UnusedOFFOFFOFFONONOFFOFF
Baud Rate Selections
BAUD RATEDS2DS1
9600OFFOFF
19,200ONOFF
38,400OFFON
76,800ONON
Fig. 71 -- RTU Open SW3 Dip Switch Settings
Fig. 72 -- RTU Open Address Switches
C07166
C10815
38
Fig. 73 -- Network Wiring
C10816
Page 39
Local Access —
BACview6Handheld: The BACview
6
is a keypad/display
interface used to connect to the RTU Open to access the
control information, read sensor values, and test the RTU,
see Fig. 74. This is an accessory interface that does not
come with the RTU Open controller and can only be used
6
at the unit. Connect the BACview
to the RTU Open J12
local access port. There are 2 password protected levels in
the display (User and Admin). The user password is
defaulted to 0000 but can be changed. The Admin
password is 1111 and cannot be changed. There is a 10
minute auto logout if a screen is idle. See Form
48--50HCTQ--01T, Appendix A for navigation and screen
content.
Virtual BACview: Virtual BACview is a freeware computer
program that functions as the BACview
6
Handheld. The
USB Link interface (USB--L) is required to connect a
computer to the RTU Open board. The link cable connects
a USB port to the J12 local access port. This program
functions and operates identically to the handheld.
RTU Open Troubleshooting —
Communication LEDs: The LEDs indicate if the
controller is speaking to the devices on the network. The
LEDs should reflect communication traffic based on the
baud rate set. The higher the baud rate the more solid the
LEDs will appear.
50TC--*16
Cable
Access Port
P1P1
J12
P5P5
BACview
Fig. 74 -- BACview6Handheld Connections
Protocol Selector
RTU Open
6
Local Access Cable
C10812
39
Page 40
Table 8 – LEDs
The LEDs on the RTU Open Control Board (see Fig. 60) show the status of certain functions:
If this LED is on...Status is...
PowerRTU Open has power
RxRTU Open is receiving data from the network segment
TxRTU Open is transmitting data over the network segment
DO#The digital output is active
The Run and Error LEDs indicate control module and network status
If Run LED shows...
And Error LED shows...Status is...
2 flashes per secondOffNormal
2 flashes per second
2 flashes per second
2 flashes per second
2 flashes per secondOn
50TC--*16
2flashes,
alternating with Run LED
3flashes,
then off
4flashes,
then pause
Five minute auto --- restart delay after system error
Control module has just been formatted
Two or more devices on this network have the
same ARC156 network address
Exec halted after frequent system errors or
control programs halted
5 flashes per secondOnExec start- --up aborted, Boot is running
5 flashes per secondOffFirmware transfer in progress, Boot is running
7 flashes per second
14 flashes per second
7 flashes per second, alternating with
Run LED
14 flashes per second,
alternating with Run LED
Ten second recovery period after brownout
Brownout
Failure. Try the following solutions:
STurnRTUOpenoff,thenon.
NOTE:Refer to Catalog No. 48--50HCTQ--01T for
complete configuration of RTU Open operating sequences
and troubleshooting information. Refer to RTU OpenController Integration Guide (Catalog No. 11--808--428--01)
for details on configuration and troubleshooting of connected
networks. Have a copy of these manuals available at unit
start--up.
Differential Enthalpy Control —
Differential enthalpy control is provided by sensing and
comparing the outside air and return air enthalpy conditions.
Install the outdoor air enthalpy control as described above.
Add and install a return air enthalpy sensor.
Return Air Enthalpy Sensor —
Outdoor Air Enthalpy Control
(PNO 33CSENTHSW)
The enthalpy control (33CSENTHSW) is available as a
field--installed accessory to be used with the EconoMi$er2
damper system. The outdoor air enthalpy sensor is part of
theenthalpycontrol.(Theseparatefield--installed
accessory return air enthalpy sensor (33CSENTSEN) is
required for differential enthalpy control. See Fig. 75.)
Locate the enthalpy control in the economizer next to the
Actuator Motor. Locate two GRA leads in the factory
harness and connect the gray lead labeled “ESL” to the
terminal labeled “LOW”. See Fig. 75. Connect the
enthalpy control power input terminals to economizer
actuator power leads RED (connect to 24V) and BLK
(connect to GND).
The outdoor enthalpy changeover setpoint is set at the
enthalpy controller.
Mount the return--air enthalpy sensor (33CSENTSEN) in the
return--air section of the economizer. The return air sensor is
wired to the enthalpy controller (33CSENTHSW). See
Fig. 75.
– 4-20
Main
+ VDC
Out
Outside Air
Enthalpy Switch
+ 24-36
VDC In
– 4-20 Main
Out
24V
GND
LOW
RED
BLK
GRA
Return Air
Enthalpy
Sensor
PL6-1 (24-V)
PL6-4 (COM)
CTB ECON
7
(P’LINK: to J4-2) or
(RTU Open: to J2-6)
C11161
Fig. 75 -- Outside and Return Air Enthalpy Sensor
Wiring
40
Page 41
To wire the return air enthalpy sensor, perform the
following:
1. Use a 2--conductor, 18 or 20 AWG, twisted pair cable
to connect the return air enthalpy sensor to the enthalpy controller.
2. Connect the field--supplied RED wire to (+) spade connector on the return air enthalpy sensor and the (+) terminal on the enthalpy controller. Connect the BLK wire
to (--) spade connector on the return air enthalpy sensor
and the (--) terminal on the enthalpy controller.
Smoke Detectors
Smoke detectors are available as factory--installed options on
50TC--D16 units. Smoke detectors may be specified for
Supply Air only or for Return Air without or with
economizer or in combination of Supply Air and Return Air.
Return Air smoke detectors are arranged for vertical return
configurations only. All components necessary for operation
arefactory--providedandmounted.Theunitis
factory--configured for immediate smoke detector shutdown
operation; additional wiring or modifications to unit terminal
board may be necessary to complete the unit and smoke
detector configuration to meet project requirements.
Controll er housing
and electronics
Conduit c ouplings
(supplie d by installer)
Alarm
Duct smoke sensor
controller
Fastener
(2X)
Conduit nuts
(supplie d by installer)
Conduit s upport plate
Terminal block cover
(ordering option)
Troub le
Power
Test/reset
switch
Cover gasket
Controll er cover
50TC--*16
Units equipped with factory--optional Return Air smoke
detectors require a relocation of the sensor module at unit
installation. See “Completing Installation of Return Air
Smoke Sensor:” on page 43 for details.
System —
The smoke detector system consists of a four--wire
controller and one or two sensors. Its primary function is
to shut down the rooftop unit in order to prevent smoke
from circulating throughout the building. It is not to be
used as a life saving device.
Controller —
The controller (see Fig. 76) includes a controller housing,
a printed circuit board, and a clear plastic cover. The
controller can be connected to one or two compatible duct
smoke sensors. The clear plastic cover is secured to the
housing with a single captive screw for easy access to the
wiring terminals. The controller has three LEDs (for
Power, Trouble and Alarm) and a manual test/reset button,
all located on the cover face.
Sensor Module —
The sensor module (see Fig. 77) includes a plastic housing, a
printed circuit board, a clear plastic cover, a sampling tube
inlet and an exhaust tube. The sampling tube (when used)
and exhaust tube are attached during installation. The
sampling tube varies in length depending on the size of the
rooftop unit. The clear plastic cover permits visual
inspections without having to disassemble the sensor. The
cover attaches to the sensor housing using four captive
screws and forms an airtight chamber around the sensing
electronics. Each sensor includes a harness with an RJ45
terminal for connecting to the controller. Each sensor has
four LEDs (for Power, Trouble, Alarm and Dirty) and a
manual test/reset button (on the left--side of the housing).
Fig. 76 -- Controller Assembly
Duct smoke sensor
Exhaust tube
See
Detail A
Detail A
Intake
gasket
Plug
TSD-CO2
(ordering option)
Sampling tube
(ordered separately)
Magnetic
test/reset
switch
Exhaust gasket
Coupling
Alarm
Troub le
Sensor housing
and electro nics
Power
Dirty
Fig. 77 -- Smoke Detector Sensor Module
Cover gasket
(ordering option)
C08208
Sensor cover
C08209
41
Page 42
Air is introduced to the duct smoke detector sensor’s
sensing chamber through a sampling tube that extends into
the HVAC duct and is directed back into the ventilation
system through a (shorter) exhaust tube. The difference in
air pressure between the two tubes pulls the sampled air
through the sensing chamber. When a sufficient amount of
smoke is detected in the sensing chamber, the sensor
signals an alarm state and the controller automatically
takes the appropriate action to shut down fans and
blowers, change over air handling systems, notify the fire
alarm control panel, etc.
The sensor uses a process called differential sensing to
prevent gradual environmental changes from triggering
false alarms. A rapid change in environmental conditions,
such as smoke from a fire, causes the sensor to signal an
alarm state but dust and debris accumulated over time
does not.
For installations using two sensors, the duct smoke
detector does not differentiate which sensor signals an
alarm or trouble condition.
50TC--*16
Smoke Detector Locations
Supply Air —
The Supply Air smoke detector sensor is located to the
left of the unit’s indoor (supply) fan. See Fig. 78. Access
is through the left side blower access panel. There is no
sampling tube used at this location. The sampling tube
inlet extends through the side plate of the fan housing
(into a high pressure area). The controller is located on a
bracket to the right of the return filter, accessed through
the lift--off filter panel.
Return Air without Economizer —
The sampling tube is located across the return air opening
on the unit basepan. See Fig. 81. The holes in the
sampling tube face downward, into the return air stream.
The sampling tube is connected via tubing to the return air
sensor that is mounted on a bracket high on the partition
between return filter and controller location. (This sensor
is shipped in a flat--mounting location. Installation
requires that this sensor be relocated to its operating
location and the tubing to the sampling tube be connected.
See “Completing Installation of Return Air Smoke
Sensor:” for details.)
Return Air with Economizer —
The sampling tube is inserted through the side plates of
the economizer housing, placing it across the return air
opening on the unit basepan. See Fig. 79. The holes in the
sampling tube face downward, into the return air stream.
The sampling tube is connected via tubing to the return air
sensor that is mounted on a bracket high on the partition
between return filter and controller location. (This sensor
is shipped in a flat--mounting location. Installation
requires that this sensor be relocated to its operating
location and the tubing to the sampling tube be connected.
See the following installation procedure.)
Flexible
Exhaust Tube
Smoke Detector Sensor
C08245
Fig. 78 -- Typical Supply Air Smoke Detector Sensor
Location
Return Air
Sampling Tube
C10330
Fig. 79 -- Return Air Sampling Tube Location
42
Page 43
Completing Installation of Return Air Smoke Sensor:
r
1. Unscrew the two screws holding the Return Air
Sensor detector plate. See Fig. 80. Save the screws.
2. Remove the Return Air Sensor and its detector plate.
3. Rotate the detector plate so the sensor is facing outwards and the sampling tube connection is on the bottom. See Fig. 81.
4. Screw the sensor and detector plate into its operating
position using screws from Step 1. Make sure the
sampling tube connection is on the bottom and the exhaust tube is on the top. See Fig. 81.
5. Connect the flexible tube on the sampling inlet to the
sampling tube on the basepan.
Controlle
Screws
Flexible
Exhaust
Tubes
Sampling Tube
Fig. 80 -- Return Air Detector Shipping Position
C10331
Sampling Tube
C10332
Fig. 81 -- Return Air Sensor Operating Position
Additional Application Data —
Refer to Catalog No. HKRNKA--1XA for discussions on
additional control features of these smoke detectors
including multiple unit coordination.
50TC--*16
43
Page 44
50TC--*16
Table 9 – Unit Wire/Fuse or HACR Breaker Sizing Data
BRKR--- Circuit breaker
CO--- Convenience outlet
DISC--- Disconnect
FLA--- Full load amps
IFM--- Indoor fan motor
LRA--- Locked rotor amps
MCA--- Minimum circuit amps
P E--- P o we r e x ha u s t
PWRD CO--- Powered convenient outlet
UNPWR CO-- - Unpowered convenient outlet
NOTES:
1. In compliance with NEC requirements for multimotor and
combination load equipment (refer to NEC Articles 430 and
440), the overcurrent protective device for the unit shall be
fuse or HACR breaker. Canadian units may be fuse or circuit
breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance.
% Voltage Imbalance = 100 x
50TC--*16
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 230-3-60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance= 100 x
This amount of p hase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
(224 + 231 + 226)
=227
= 1.76%
3
=
4
227
681
3
Economizer2 Position Damper
Fig. 82 -- EconoMi$ert IV Wiring
Step 11 — Adjust Factory--Installed Options
Smoke Detectors —
Smoke detector(s) will be connected at the Central
Terminal Board (CTB, at terminals marked “Smoke
Shutdown”. Remove jumper JMP 3 when ready to
energize unit.
Unit Without Economizer or
2 Position Damper
C10333
EconoMi$er IV Occupancy Switch —
Refer to Fig. 82 for general EconoMi$er IV wiring.
External occupancy control is managed through a
connection on the Central Terminal Board.
If external occupancy control is desired, connect a time
clock or remotely controlled switch (closed for Occupied,
open for Unoccupied sequence) at terminals marked
OCCUPANCY on CTB. Remove or cut jumper JMP 2 to
complete the installation.
46
Page 47
Step 12 — Install Accessories
Available accessories include:
Roof Curb (must be installed before unit)
Thru--base connection kit (must be installed before unit
is set on curb)
Manual outside air damper
Two--Position motorized outside air damper
EconoMi$er IV (with control and integrated barometric
relief)
EconoMi$er2 (without control/for external signal and
integrated barometric relief)
Barometric relief
Power Exhaust
Differential dry--bulb sensor (EconoMi$er IV)
Outdoor enthalpy sensor
Differential enthalpy sensor
Time Guard II compressor anti--cycle control
Outdoor coil protector grille
Head pressure control
Programmable setback thermostat
Electrical/Mechanical thermostat and subbase
Thermidistatt device
Humidistat
Electric Heaters
Single Point kits
Thermostat / Sensors
CO
sensor
2
DDC interface (PremierLink)
Louvered hail guard
Phase monitor control
Refer to separate installation instructions for information
on installing these accessories.
Pre--Start and Start--Up
This completes the mechanical installation of the unit.
Refer to the unit’s Service Manual for detailed Pre--Start
and Start--up instructions.
50TC--*16
47
Page 48
50TC--*16
Copyright 2011 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231Printed in U.S.A.Edition Date: 05/11
Manufacturer reserves the right to change, at any ti me, specifications and designs without notice and without obligations.
48
Catalog No: 50TC--- 14SI
Replaces: 50TC--- 11SI
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.