Carrier 50RTG User Manual

Rooftop Water Source Heat Pump Units
Installation, Start-Up, and
Service Instructions
TM
50RTG
CONTENTS
Page
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Step 1 — Check Jobsite . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 2 — Check Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
• STORAGE
• PROTECTION
• INSPECT UNIT
Step 3 — Location of Unit . . . . . . . . . . . . . . . . . . . . . . . . 3
Step 4 — Mounting the Unit . . . . . . . . . . . . . . . . . . . . . . 6
Step 5 — Condensate Drain . . . . . . . . . . . . . . . . . . . . . . 6
Step 6 — Piping Connections . . . . . . . . . . . . . . . . . . . . 6
• WATER LOOP APPLICATIONS
• GROUND-WATER APPLICATIONS
• GROUND-LOOP APPLICATIONS
Step 7 — Electrical Wiring. . . . . . . . . . . . . . . . . . . . . . . . 7
• SUPPLY VOLT AGE
• 208-VOLT OPERATION
• BLOWER SELECTION
Step 8 — Low Voltage Wiring. . . . . . . . . . . . . . . . . . . . 14
• THERMOSTAT CONNECTIONS
• WATER FREEZE PROTECTION
• AIR COIL FREEZE PROTECTION
• ACCESSORY CONNECTIONS
• WATER SOLENOID VALVES
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14,15
System Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
FIELD SELECTABLE INPUTS . . . . . . . . . . . . . . . .15,16
D Control Accessory Relay Configurations . . . . . 16
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-18
Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Scroll Compressor Rotation. . . . . . . . . . . . . . . . . . . . . 17
Unit Start-Up Cooling Mode . . . . . . . . . . . . . . . . . . . . . 17
Unit Start-Up Heating Mode . . . . . . . . . . . . . . . . . . . . . 17
Flow Regulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Cooling Tower/Boiler Systems . . . . . . . . . . . . . . . . . . 18
Ground Coupled, Closed Loop and Plateframe
Heat Exchanger Well Systems . . . . . . . . . . . . . . . . 18
Page
OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Power Up Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Units with Aquazone™ Complete C Control . . . . . 19
Units with Aquazone Deluxe D Control . . . . . . . . . . 19
SYSTEM TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19,20
Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Retry Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Aquazone Deluxe D Control LED Indicators . . . . . 20
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-22
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Wat er Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Condensate Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . 21
Refrigerant System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Condensate Drain Cleaning . . . . . . . . . . . . . . . . . . . . . 21
Air Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Condenser Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Checking System Charge . . . . . . . . . . . . . . . . . . . . . . . 22
Refrigerant Charging. . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Air Coil Fan Motor Removal . . . . . . . . . . . . . . . . . . . . . 22
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . 22-25
Thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Control Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . CL-1, CL-2
IMPORTANT: Read the entire instruction manual before starting installation.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precau­tions in the li terature, t ags and labe ls attached to the uni t, and other safety precautions that may apply.
Improper installation, adjustment, alteration, service, main­tenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individ­ual instructions packaged with the kits or accessories when installing.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 5 a 5 a
PC 111 Catalog No. 535-004 Printed in U.S.A. Form 50R-2SI Pg 1 8-02 Replaces: New
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and the National Electrical Code (NEC) for special installation requirements.
Understand the signal words — DANGER, WARNING, and CAUTION. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARN­ING signifies hazards that could result in personal injury or death. CAUTION is used to identify unsafe practices , which would result in minor personal injury or product and property damage.
Recognize safety information. This is the safety-alert symbol ( ). When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Electrical shock can cause personal injury or death. Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Turn off accessory heater power if applicable.
GENERAL
This Installati on and Start-Up Instructions liter ature is for Aquazone™ Rooftop W ater Source Heat Pump systems.
Rooftop Water Source Heat Pumps (WSHP) are single­package outdoor units with electronic controls desi gned for year-round cooling and heat ing.
IMPORTANT: The installation of water source heat pump units and all associated components, parts, and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsi­bility of the installing contractor to determine and comply with ALL applicable codes and regulations.
INSTALLATION
Step 1 Check Jobsite
maintenance instructions are provided with each unit. Before unit start-up, read all manuals and becom e familiar with the unit and its operation. Thoroughly check out the system before operation. Complete the inspections and instructions listed below to prepare a unit for installation. See Ta ble 1 f or u nit physical data.
To avoid equipment damage, do not use these units as a source of heating or cooling during the construction process. The mechanical components and filters used in these units quickly becomes clogged with construction dirt and debris whic h may cause system dam age.
Step 2 Check Unit
the jobsite, carefully check the shipment against the bill of lading. Make sure all units have been received. Inspect the car­ton or crating of each unit, and inspect each unit for damage. Ensure the shipping company makes proper notation of any shortages or damage on all copies of the freight bill. Concealed
Installation, operation and
Upon receipt of shipment at
damage not discovered during unloading must be reported to the shipping company within 15 days of receipt of shipment.
NOTE: It is the responsibility of the purchaser to file all necessary claims with the shipping company.
1. Verify unit is correct model for entering water tempera­ture of job.
2. Be sure to provide freeze protection for piping, as re­quired. Well water applications are espec ially susceptible to freezing.
3. Be sure the installation location is isolated from sleeping areas, private offices and other acoustically sensitive spaces.
4. Check local codes to be sure a secondary drain pan is not required under the unit.
5. Be sure unit is mounted at a height sufficient to provide an adequate slope of the condensate l ines. If an appropri­ate slope cannot be achieved, a field-supplied condensate pump may be required.
6. Provide sufficient space fo r duct connection.
7. Provide adequate clearance for filter replacement and drain pan cleaning. Do not allow piping, conduit, etc. to block filter access.
8. Provide sufficient access to allow maintenance and servicing of the fan and fan motor, compressor and coils.
9. Provide an unobstructed path to the unit. Space should be sufficient to allow removal of unit if necessary.
10. Provide ready access to water valves and fittings, and screwdriver access to unit side panels, discharge collar, and all electrical connections.
11. Where access to side panels is limited, pre-removal of the control box side mounting screws may be necessary for future servicing.
STORA GE — If the equi pment is not installed immediately upon its arrival at the jobsite, it should be left in its shipping carton and stored in a clean, dry area of the building or in a warehouse. Units must be stored in an upright position at all times. If unit stacking is necessary, stack 50RTG03-10 units a maximum of 2 high. Do not stack units larger than 50RTG10. Do not remove any equipment from its shipping package until it is needed.
PROT ECT ION — Onc e the units are properly positioned on the jobsite, they must be covered with either a shipping carton, vinyl film, or an equivalent protective covering. Open ends of pipes stored on the jobsite must be capped. This precaution is especially important in areas where painting, plastering, or spraying of fireproof material, etc. is not yet complete. Foreign material that is allowed to accumulate within the units can pre­vent proper start-up and necessitate costly clean-up operations.
Before installing any of the system components, be sure to examine each pipe, fitting, and valve, and remove any dirt or foreign material found in or on these components.
DO NOT store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life. Always move units in an upright position. Tilting units on their sides may cause equipment damage.
2
INSP EC T UNIT — To prepare the unit for installation, com­plete the procedures listed below:
1. Compare the electrical data on the unit nameplate with ordering and shipping information to verify that the correct unit has been shipped.
2. Verify that the unit is the correct model for the enteri ng water temperature of the job.
3. Do not remove the packaging until the unit is ready for installatio n.
4. Verify that the refrigerant tubing is free of kinks or dents, and that it does not touch other unit components.
5. Inspect all electrical connections. Be sure connections are clean and tight at the terminals.
6. Compressors are internally spring-mounted. Compressors equipped with external spring vibration isolators must have bolts loosened and shipping clamps removed.
7. Remove any blower support cardboard from inlet of the blower if present.
8. Locate and verify any accessory kit located in compressor section.
9. Remove any access panel screws that may be difficult to remove once unit is installed.
Step 3 Location of Unit
The following guide­lines should be considered when choosing a location for WSHP. Refer to Fig. 1 and 2 for unit dimensional data:
• Provide sufficient space for water, electrical and duct
connections
• Locate unit in an area that allows for easy access and
removal of filter and access panels
• Allow enough space for service personnel to perform
maintenance
Table 1 Physical Data Aquazone 50RTG03-20 Units
UNIT 50RTG 03 04 05 07 08 10 12 15 20 OPERATING WEIGHT (lb) 735 785 835 880 1080 1125 1175 1770 1960 SHIPPING WEIGHT (lb) 750 800 850 900 1100 1150 1200 1800 2000 REFRIGERANT TO AIR HEAT EXCHANGER
Face Area (sq ft) 5 5 5 7.5 9.3 9.3 10.5 20 20 Rows Deep 233333344 Copper Tube Size (in.)
No. Fins per Inch 12 12 12 12 12 12 12 12 12 REFRIGERANT CHARGE R-22/Ckt (oz) 52 68 86 132 68 86 88 141 160 NUMBER OF CIRCUITS 111122222 BLOWER DATA
Diameter (qty-in.) 1-10 1-10 1-10 1-12 1-15 1-15 1-15 2-15 2-15
Width (in.) 6 6 10 11 11 11 11 11 11 FILTER DATA
Size (in.) 16 x 20 16 x 20 16 x 20 16 x 20 16 x 20 16 x 20 16 x 20 16 x 20 16 x 20
Quantity 4444666106
3
/
3
8
/
3
8
/
3
8
/
3
8
/
3
8
/
3
8
/
3
8
/
8
3
/
8
3
OUTSIDE AIR
OPENING
D
AIR
OUTSIDE
NOTES:
AIR
RETURN
AIR
FLOW
.
8
/
1
AIR
RETURN
1" FPT
CONDENSATE DRAIN
C
TOP
AIR
SUPPLY
and specification of each product at the time of order may be changed with-
out notice.
1. All dimensions are in inches.
2. Carrier works continuously to improve its products. As a result, the design
3. Assembly tolerances ±
9-13/16
VIEW
SIDE
AIR
SUPPLY
VIEW
F
5-13/16
E
DIMENSIONS (in.)
Water
Outside Air
UNITS
50RTG
4
/
3
In/Out (FPT)
Opening Size
ABCDEF
03/04 39.52 43.90 81.00 12.32 4.692 6.614 12.57 x 30.00
PIPE CHASE
4
4
2
/
/
/
1
1
1
ELECTRICAL &
Fig. 1 50RTG Dimensional Data
B
FRONT
VIEW
A
05 39.52 43.90 81.00 12.32 4.692 6.614 12.57 x 30.00 1
07 39.52 43.90 81.00 12.32 4.692 6.614 12.57 x 30.00 1
08 45.40 49.90 91.07 16.48 5.692 6.614 18.95 x 36.00 1
10/12 45.40 49.90 91.07 16.48 5.692 6.614 18.95 x 36.00 1
15/20 50.62 88.00 91.07 16.48 4.543 6.566 18.95 x 74.00 2
4
RETURN AIR
TRANSITION
SUPPLY AIR
TRANSITION
E
(TYP)
J
3.000 3.000
(TYP)
REQUIREMENTS
BY CONTRACTOR'S
HEIGHT DETERMINED
K
3-7/8"
TO THE NOTED DIMENSIONS. THIS IS TO ALLOW
CLEARANCE FOR MOUNTING UNIT TO CURB.
F
ROOF DECK/ROOFING
FLASHING
14.00 (REF)
ROOF CURB ASSEMBLY DETAILS
(FIELD SUPPLIED)
TRANSITION DETAIL
G
H
IMPORTANT NOTE: WHEN INSTALLING CURB, FLASHING MUST CONFORM
BASE PAN OF UNIT
CURB WALL
STRUCTURAL SUPPORT
C
B
A
23.000
Fig. 2 50RTG Roof Curb Dimensional Data
14-15/16
Return Air Transition Supply Air Transition
DIMENSIONS (in.)
GH J K GH J K
ABCEF
ROOF CURB
50RTGACURBCAAA 35.25 72.25 18.00 1.50 12.50 22.00 16.00 39.25 33.25 27.00 21.00 39.25 33.25
50RTGACURBBAAA 41.25 82.25 21.00 1.50 12.50 25.00 19.00 45.25 39.25 27.00 21.00 45.25 39.25
Return Air
Supply
Air
50RTGACURBAAAA 78.875 82.25 21.00 5.00 9.00 25.00 19.00 82.875 76.875 27.00 21.00 82.875 76.875
2.00 TYP.
14.00 (REF)
5
Step 4 Mounting the Unit
For proper opera­tion, units must be mounted on a roof curb as shown in Fig. 3. Follow these guidelines when installing the roof curb:
1. Set unit on curb.
2. Align unit so that its return and supply air direction match the return and supply air opening in the roof curb frame.
3. Run both the return and supply loop piping, as well as the electrical supply line, through the pipe chase provided in the curb.
Step 5 Condensate Drain
1. Install a condensate trap at each unit with the top of the trap positioned below the unit condensate drain connection.
2. Design the length of the trap (water seal) based on the amount of positive or negative pressure on the drain pan. As a rule, 1 in. of trap is required for eac h inch of nega­tive pressure on the unit.
Note that condensate is allowed to drain onto the roof.
Step 6 Piping Connections
application, there are 3 types of WSHP piping systems to choose from: water loop, ground-water and ground loop. Refer to Piping Section of Carrier System Design Manual for addi­tional information.
All WSHP units use low temperature soldered female pipe thread fittings for water connections to prevent annealing and out-of-round leak problems which are typically associated with high temperature brazed connections. Refer to Table 1 for con­nection sizes. When making piping connections, consider the following:
• Use a backup wrench when making screw connections to
unit to prevent internal damage to piping.
• Ins ulat ion may b e re quir ed on pipin g t o avoi d co nden sa-
tion in the case where fluid in loop piping operates at
temperatures below dew point of adjacent air.
• Piping systems that contain steel pipes or fittings may
be subject to galvanic corrosion. Dielectric fittings may
be used to isolate the steel parts of the system to avoid
galvanic corrosion.
Depending on the
50 RTG UNIT
WA TER LOOP APPLICATIONS — Water loop applications usually include a number of units plumbed to a common pip­ing system. Maintenance to any of these units can introduce air into the piping system. Therefore, air elimination equipment comprises a major portion of the mechanical room plumbing.
The flow rate is usually set between 2.25 and 3 gpm per ton of cooling capacity. For proper maintenance and servicing, pressure-temperature (P/T) ports are necessary for temperat ure and flow verification.
In addition to complying with any applicable codes, consid­er the following for system piping:
• Piping systems utilizing water temperatures below
50 F require
1
/2-in. closed cell insulation on all pipi ng
surfaces to eliminate condensation.
• All plastic to me tal threaded fittings should be avoided
due to the potential to leak. Use a flange fitted substitute.
• Teflon tape thread sealant is recommended to minimize
internal fouling of the heat exchanger.
• Use backup wrench. Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• The piping system should be flushed prior to operation to
remove dirt and foreign materials from the system. GROUND-WATER APPLICATIONS — In addition to com-
plying with any applicable codes, consider the following for system piping:
• Install shut-off valves for servici ng.
• Install pressure-temperature plugs to measure flow and
temperature.
• Boiler drains and other valves should be connected using
a “T” connector to allow acid flushing for the heat
exchanger.
• Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• Use PVC SCH80 or copper piping material. NOTE: PVC SCH40 should not be used due to system high
pressure and temperature extremes. Water Supply and Quantity
— Check water supply. Water supply should be plentiful and of good quality. See Table 2 for water quality guidelines.
IMPORTANT: Failure to comply with the above required water quality and quantity limitations and the closed­system application design requirements may cause damage to the tube-in-tube heat exchanger that is not the responsi­bility of the manufacturer.
GASKET
CURB
Fig. 3 50RTG Curb Installation
FLASHING
ROOF
In all applications, the quality of the water circulated through the heat exchanger must fall within the ranges listed in the Water Quality Guidelines table. Consult a local water treat­ment firm, independent testing facility, or local water authority for specific recommendations to maintain water quality within the published limits.
GROUND-LOO P APPL ICATIONS — Te mp erat ure s b etw een 25 to 110 F and a cooling capacity of 2.25 to 3 gpm of fl ow per ton is recommended. In addition to complying with any appli­cable codes, consider the following for system piping:
• Piping materials should be limited to only polyethylene
fusion in the buried sections of the loop.
• Galvanized or steel fittings should not be used at any
time due to corrosion.
• All plastic to me tal threaded fittings should be avoided
due to the potential to leak. Use a flange fitted substitute.
• Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• Pressure-temperature (P/T) plugs should be used to mea-
sure flow of pressure drop.
6
Step 7 Electrical Wiring
To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.
Use only copper conductors for field-installed electrical wiring. Unit terminals are not designed to accept other types of conductors.
All field installed wiring, including the electrical ground, MUST comply with the National Electrical Code (NEC) as well as applicable local codes. In addition, all field wiring must conform to the Class II temperature limitations described in the NEC.
Refer to unit wiring diagram Fig. 4 for a schematic of the field connections which must be made by the installing (or electrical) contractor.
Consult the unit wiring diagram located on the inside of the compressor access panel to ensure proper electrical hookup. The installing (or electrical) contractor must make the field connections when using field-supplied disconnect.
Operating voltage must be the same voltage and phase as shown in Electrical Data shown in T able 3.
Make all final electrical connections with a length of flexi­ble conduit to minimize vibration and sound transmission to the building.
SUPPLY VOLTAGE — Operating voltage to unit must be within voltage range indicated on unit nameplate.
On 3-phase units, voltages under load between phases must be balanced within 2%. Use the following formula to deter­mine the percentage voltage imbalance:
% Voltage Imbalance
= 100 x Example: Supply voltage is 460-3-60.
max voltage deviation from average voltage
average voltage
AB = 452 volts BC = 464 volts AC = 455 volts
A verage Voltage =
452 + 464 + 455
1371
=
3
3
= 457 Determine maximum deviation from average voltage: (AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v
Maximum deviation is 7 v. Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is
below the maximum allowable 2%.
Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electri­cal components.
NOTE: If more than 2% voltage imbalance is present, contact local electric utility.
208-VOLT OPERATION — A ll 208-230 volt units are factory wired for 208 volts. The transformers may be switched to 230-volt operation (as illustrated on the wiring diagram) by switching the red (208 volt) wire with t he orange (230 volt) wire at the L1 terminal.
BLOW E R SEL EC TI O N — All water source heat pumps are factory set with the appropriate motor and sheave combination to achieve the desired airflow performance. Performance is selected by matching the desired performance with the appro­priate region in Tables 4-12. Per the table notes, regions desig­nated by A, B, C and D represent motor drive options.
NOTE: Factory-installed sheaves are field adjustable. Refer to T ables 4-12 for adjustment points.
Table 2 — Water Quality Guidelines
CONDITION ACCEPTABLE LEVEL pH Total Hardness Iron Oxides Iron Bacteria Corrosion*
Brackish
*If the concentration of these corrosives exceeds the maximum allowable level, then the potential for serious corrosion
problems exists.
†Sulfides in the water quickly oxidize when exposed to air, requiring that no agitation occur as the sample is taken.
Unless tested immediately at the site, the sample will require stabilization with a few drops of one Molar zinc acetate solution, allowing accurate sulfide determination up to 24 hours after sampling. A low pH and high alkalinity cause sys­tem problems, even when both values are within ranges shown. The term pH refers to the acidity, basicity, or neutrality of the water supply. Below 7.0, the water is considered to be acidic. Above 7.0, water is considered to be basic. Neutral water contains a pH of 7.0.
NOTE: To conver t ppm to grains per gallon, divide by 17. Hardness in mg/l is equivalent to ppm.
7 to 9 range for copper. Cupro-nickel may be used in the 5 to 9 range. Calcium and magnesium carbonate should not exceed 20 grains per gallon (350 ppm). Less than 1 ppm. No level allowable.
Ammonia, Ammonium Hydroxide 0.5 ppm Cu Ammonium Chloride, Ammonium Nitrate 0.5 ppm Cu Ammonium Sulfate 0.5 ppm Cu Chlorine/Chlorides 0.5 ppm CuNi Hydrogen Sulfide† None Allowable
Use Cupro-nickel heat exchanger when concentrations of calcium or sodium chloride are greater than 125 ppm are present. (Seawater is approximately 25,000 ppm.)
Max Allowable Level Coaxial Metal
7
50RTG03-07 WITH ECONOMIZER AND COMPLETE C CONTROLLER
Ground
24V
L1
L2
L3
SEE NOTE 7
BLU
CB
C
YEL
R
Y
P1
Y
W
O
G
R
C
AL1 AL2
A
GRY
Alarm Relay
BR
Disconnect
OR CB
(Optional)
GRY
BC
BRG
Test Pins
FP1 FP2
JW1
SEE NOTE 6
Power Supply
Refer to Data Plate
Use copper conductors only.
RED (208V)
VIO or BLK/RED
(460V)
BLU
or
BLK
SEE
NOTE 3
ORG
230V
Compressor
Y
Cooling
O
Fan
G
24 V A C
R
Common
C
Alarm
L
Typical T-stat
SEE NOTE 5
LEGEND
AL Alarm Relay Contacts BC Blower Mtr Contactor CB Circuit Breaker CC Compressor Contactor ECR Economizer Relay EH1 Auxiliary Heat Stage 1 EH2 Auxiliary Heat Stage 2 ES Enthalpy Sensor FP1 Sensor, Water Coil Freeze Protection FP2 Sensor, Air Coil Freeze Protection HP High Pressure Switch JW1 Jumper, Alarm Mode LAR Low Ambient Relay LOC Loss-of-Charge Pressure Switch MAS Mixed Air Sensor NEC National Electrical Code OAT Outside Air Thermostat
BRN
SEE NOTE 4
BLK
BLK
BLK
4
CCG
LAR
BRN
Compressor Relay
Dip Switch
Off On
L1
L2
L3
Power
Distribution
Block
3
CC
PM
1 2
Not Used
Status
G
LED
YEL
C
Microprocessor
Control Logic
PM Performance Monitor P1 Field Wiring Terminal Block RVS Reversing Valve Solenoid
Relay Contactor Coil
Solenoid Coil
Thermistor
Ground
Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
HP
LOC
FP1
FP2
RV
CO
CO
24V DC
EH1 EH2
BLK
BLK
BLK
BLK
BLK
BLK
P2
P3
1
2 3
4 5
6 7
8 9
10
12
SEE NOTE 7
Not Used
115V / 1PH
L1
BLK
L2
BLK
L3
BLK
CC
BLK
BLK
BLK
BC
BRN
VIO
BRN
TR1
TR S
RED RED BLU BRN GRY GRY VIO VIO BRN ORG
T1
T2
T3
Compressor
Blower Motor
ES
-
+
+
4
YEL
8
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. 208/230 v transformers will be connected for 208 v operations. For 230 v operations, discon­nect Red lead at L1, and attach Orange lead to L1. Close open end of Red Lead with insulating tape.
4. FP1 jumper provides freeze protection for WATER. When using ANTI-FREEZE solutions, cut FP1 jumper.
5. Typical ther mostat wiring shown. Refer to thermo­stat Installation Instructions for wiring to the unit.
6. 24 v alarm signal shown. For dry alarm contact, cut JW1 jumper and dry contact will be available between AL1 and AL2.
7. Transformer secondary ground via Complete C board standoffs and screws to control box. (Ground available from top two standoffs as shown.)
Logic Module
(Damper Actuator)
BLUGRY
600 150
Ohm Ohm
+2
5
S
RO
2
BLK
YEL
3
YEL
6
OAT
R
7
WHT TAN
ECR
BRN
HP
LOC
FP1
FP2
RVS
BRN
ECR
WHT GRN
Field
BLK
Wiring
GFI
(Optional)
MAS
GRY BRN
134TT1P
CC
B
BRN
LAR
ORG
P1
Fig. 4 Typical Aquazone Complete C Control Wiring
8
Table 3 50RTG Electrical Data
UNIT
50RTG
03
04
05
07
08
10
12
15
20
LEGEND
FLA Full Load Amps HACR Heating, Air Conditioning and Refrigeration LRA Lock Rotor Amps RLA Rated Load Amps
NOTE: Contact factory for oversize blower motor electrical data.
POWER SUPPLY
Voltage Hz Ph RLA LRA QTY HP FLA QTY
208/230 60 3 10.7 63.0 1 1 3.6 1 25 Amp 17.0
460 60 3 5.0 31.0 1 1 1.8 1 15 Amp 8.1
208/230 60 3 13.9 88.0 1 1 3.6 1 30 Amp 21.0
460 60 3 6.4 44.0 1 1 1.8 1 15 Amp 9.8 575 60 3 5.3 34.0 1 1 1.6 1 15 Amp 8.2
208/230 60 3 20.0 123.0 1 1 3.6 1 45 Amp 28.6
460 60 3 7.5 49.5 1 1 1.8 1 15 Amp 11.2 575 60 3 6.4 40.0 1 1 1.6 1 15 Amp 9.6
208/230 60 3 20.7 156.0 1 2 6.2 1 50 Amp 32.1
460 60 3 10.0 70.0 1 2 3.1 1 25 Amp 15.6 575 60 3 8.2 54.0 1 2 2.3 1 20 Amp 12.6
208/230 60 3 13.9 88.0 2 2 6.2 1 50 Amp 37.5
460 60 3 6.4 44.0 2 2 3.1 1 20 Amp 17.5 575 60 3 5.3 34.0 2 2 2.3 1 15 Amp 14.2
208/230 60 3 20.0 123.0 2 2 6.2 1 70 Amp 51.2
460 60 3 7.5 49.5 2 2 3.1 1 25 Amp 20.0 575 60 3 6.4 40.0 2 2 2.3 1 20 Amp 16.7
208/230 60 3 19.3 123.0 2 3 9.2 1 70 Amp 52.6
460 60 3 10.0 62.0 2 3 4.3 1 35 Amp 26.8 575 60 3 7.8 50.0 2 3 3.4 1 25 Amp 21.0
208/230 60 3 20.7 156.0 2 3 9.2 1 70 Amp 55.8
460 60 3 10.0 70.0 2 3 4.3 1 35 Amp 26.8 575 60 3 8.2 54.0 2 3 3.4 1 30 Amp 21.9
208/230 60 3 33.3 232.0 2 5 13.2 1 125 Amp 88.1
460 60 3 17.0 116.0 2 5 6.6 1 60 Amp 44.9 575 60 3 12.8 97.0 2 5 5.6 1 45 Amp 34.4
COMPRESSOR
(each)
BLOWER
MOTOR
MAX. FUSE
OR HACR
BREAKER
MINIMUM
CIRCUIT
AMPACITY
Table 4 50RTG03 Blower Performance
SCFM
AIRFLOW
975
1050
1125
1200
1275
1350
1425
LEGEND
BHP Brake Horsepower SCFM Standard Cubic Feet Per Minute
NOTES:
1. Fan BHP includes drive losses.
2. Region “A” is standard drive package.
3. Regions “B” and “C” require optional drive packages.
4. For applications requiring higher static pressures, contact your local representative.
BHP 0.12 0.14 0.17 0.19 0.21 0.23 0.26 0.29 0.31 0.33
RPM 550 609 667 724 779 833 885 933 980 1024
Turns Out 5.0 3.5 4.5 3.5 2.5 1.5 1.0 0.0 2.0 1.5
BHP 0.14 0.17 0.19 0.22 0.24 0.26 0.30 0.32 0.35 0.37
RPM 580 636 691 745 798 849 898 946 991 1035
Turns Out 4.0 3.0 4.0 3.0 2.5 1.5 0.5 0.0 2.0 1.5
BHP 0.18 0.20 0.23 0.25 0.28 0.31 0.33 0.36 0.39 0.42
RPM 619 670 721 772 821 870 917 963 1008 1051
Turns Out 3.5 4.5 3.5 3.0 2.0 1.0 0.5 2.5 2.0 1.0
BHP 0.22 0.24 0.26 0.29 0.32 0.35 0.37 0.41 0.44 0.46
RPM 658 705 752 799 846 892 937 982 1025 1066
Turns Out 4.5 4.00 3.00 2.5 1.5 1.0 0.0 2.0 1.5 1.0
BHP 0.26 0.29 0.31 0.33 0.36 0.40 0.42 0.45 0.48 0.52
RPM 688 732 777 822 867 911 954 997 1038 1079
Turns Out 4.0 3.5 2.5 2.0 1.5 0.5 2.5 2.0 1.5 1.0
BHP 0.29 0.32 0.35 0.39 0.41 0.44 0.47 0.51 0.54 0.57
RPM 721 764 807 850 893 935 976 1017 1057 1096
Turns Out 3.5 3.0 2.5 1.5 1.0 0.0 2.0 1.4 1.0 0.5
BHP 0.4 0.40 0.42 0.44 0.46 0.50 0.53 0.56 0.61 0.64
RPM 763 803 843 883 923 963 1003 1041 1080 1118
Turns Out 3.0 2.5 1.5 1.0 0.5 2.5 2.0 1.5 1.0 0.5
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
B
EXTERNAL STATIC PRESSURE (in. wg)
A
C
9
Loading...
+ 19 hidden pages