Carrier 50RQ900291 User Manual

Number One AirConditbning Maker
e
Division of Carrier Corporal io

installation Instructions

Accessory Emergency Heat
Package 50RQ900291
Single-Package Heat Pumps

50P§-

006,008,010

INSTALLATION

General —The accessory emergency heat package
may be installed on any 50RQ,PQ unit. The package consists of a control box assembly con taining the following components'
1 Emergency Heat Terminal Block HY84FC117 1 Heater Relay (HR-1) HN61KK324 1 Heater Relay (HR-2) HN61KL016 1 Outdoor Air Thermostat (OAT.) HH22QA040
One or 2 additional outdoor thermostats may be installed if required. Mount additional thermo­stat(s) in the control box as follows:
f. Remove control box cover.
2. Remove thermostat barrier (See Fig. 1).
FIELD CONTROL WIRING
SEALTITE CONDUIT
THERMOSTAT BARRIER
OUTDOOR AIR THERMOSTAT LOCATION
NO N02 N0 3
EMERGENCY HEAT CONTROL BOX
____
CAPILLARIES
COMPRESSOR ACCESS PANEL CORNER POST
Fig. 1 — Accessory Emergency Heat
Control Box Installation
3. Attach additional thermostat(s) to barrier using field supplied 8-32 machine screws. Using field supplied wire, connect the additional thermo­stat(s) to control box components as shown in Fig. 2.
4. Replace barrier in control box.
5. Using screws taped to control box mounting plate, secure control box to compressor access panel corner post (see Fig. 1 and 3).
6. Using field supplied wire, connect the control box to the conditioned space and base unit. For
50RQ,PQ006 units, wire in accordance with Fig. 4, for 50RQ,PQ008/010 units, wire in
accordance with Fig. 5. Enclose wiring in
field-supplied conduit as required. Conduit to be “Sealtite” or equal. There are 2 conduit connection holes in bottom of control box.
Use 1 hole for wiring entering the control box from the conditioned space and the other for all wiring leaving the control box to the base unit. (Note: A portion of the wiring is routed in
1 hole and directly out the other and is not connected to the control box terminal block). See Fig. 1 and Fig. 3.
Outdoor Thermostat(s) — A 3-ft capillary tube
connects the thermostat bulb to the thermostat body. If space is available inside of control box and
control box is not in direct sunlight, capillary tubes
may be left in box. For best performance, locate
capillary tube(s) outside of box. Pull 1- to 2-in. of capillary tubing thru the rubber grommet in bottom of control box, neatly bend tubing and locate under control box. Bulb(s) must not be in direct sunlight. Bulb(s) must be in a shaded location to sense true outdoor temperature. Shield bulb(s) with suitable field supplied material if required. An outdoor thermostat is required for each stage of heat. This instruction covers 2 stages of heat for the 50RQ,PQ units. Three stages of heat are available for 39 Kw heat only. If 3 stages of heat are required, contact the Carrier represent ative for appropriate installation instructions.
Refer to building heat load calculations for
correct thermostat setting
© Carrier Corporation 1977
Form 50RQ-6SI
EMERGENCY HEAT CONTROL BOX
FOR CONTROL BOX CONNECTIONS TO THERMOSTAT AND BASE UNIT REFER TO FIG. 4 AND 5.
^ iC
HR — Heater Relay OAT — Outdoor Air Thermostat TB - Ter minal Block
_______
Factory Wiring
_______
Field Wiring

Fig. 2 — Schematic Diagram, Accessory Emergency Heat Control Box, 50RQ,PQ

Outdoor Thermostat Setting — Set the outdoor
□ Terminal Block Connections (Marked)
Component Connections (Marked)
O Component Connections (Unmarked)
Field Splice
thermostat temperature indicating dial for each individual installation. If more than 1 thermostat is used, set additional thermostats in sequence to allow additional strip heaters to come on as the outdoor temperature lowers. Before heaters can come on (except during defrost cycle):
1. The outdoor temperature must be below the setting of the outdoor thermostat.
2. The room temperature must be 2 F below the setting of the room thermostat so that the contacts on the second step of the thermostat can close. An outdoor thermostat setting that is higher than necessary results in excess operating costs; too low a setting prevents heaters from coming on when they are needed.
• On completion of outdoor thermostat setting, replace cover on the control box.
Emergency Heat Operation — If a safety device is
tripped, the compressor locks out thru the oper ation of the Signal-LOC^ivi circuit. When this occurs, the indicator light comes on at the room thermostat.
The switch at the room thermostat can then be moved to EMERGENCY HEAT, bypassing the compressor and the outdoor thermostat(s) The second stage of heating at the room thermostat then activates the resistance heaters to satisfy space requirements — regardless of outdoor temperature. If desired, the compressor can be manually locked out by setting the thermostat to EMERGENCY HEAT. Under either condition — a tripped safety device or manual lockout, the indicator light at the thermostat is illuminated.
Loading...
+ 2 hidden pages