Carrier 50RLP User Manual

Aquazone™ System Control Panel
Water Source Heat Pump Units
Installation Instructions
50RLP
CONTENTS
SAFETY CONSIDERATIONS GENERAL Aquazone System Control Panel Functionality Stand-Alone Systems CCN Systems Using PremierLink™ Controls COMPONENTS Aquazone System Control Panel Hardware Water Source Heat Pumps with
PremierLink Controller Hardware
Field-Supplied Hardware
for Stand-Alone Systems
Field-Supplied Hardware for CCN Applications INSTALLATION
Inspection Mounting Location Mounting Wiring Install Thermostat, Sensors and Switches Install Loop Water Supply and Return
Temperature Sensors Install Loop Water Pressure Sensor Install Loop Water Flow Switch Connect to CCN Communication Bus
START-UP LID Power Up Display Log On to the LID Display Change the Default Password Set the Clock Configure Schedules Program Set Points Check System Parameters Display Alarm History Configure the Custom Programming Selections Set the Aquazone System Control Panel
Controller Address Log Off from Controller LID Operation Sequence of Operation
• HEAT REJECTION
• H EAT ADDITION
• WATER CIRCULATION
CONFIGURATION Hardware Points Software Points Loop Supply Water Set Point System Pressure Set Point Global Dictionary Heat Pump Default Configuration Cool Source Default Configuration Heat Source Default Configuration Occupancy Configuration Screen Network Time Schedule Holiday Schedules
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-14
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-20
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21-27
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
IMPORTANT: Read the ent ire instruction manual before starting installation.
. . . . . .2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
. . . . . . . .2
. . . . . . . . . .2
. . . . . . . . . . . . . . . . . .7
. . . . . . . . . . . . . . . . . . . . . . . . . .8
. . . . . .9
. . . . . . . . . .13
. . . . . . . . . . . . . . . . . . . . . . . . . . . .13
. . . . . . . . . . . . . . . .13
. . . . . . . . . . . . . . . . . . . . .13
. . . . . . . . . . . . . .14
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
. . . . . . . . . . . . . . . . . . . . . . . . . .14
. . . . . . . . . . . . . . . . . . . . . .15
. . . . . . . . . . . . . . . . . . . . . . . . . .16
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
. . . . .16
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
. . . . . . . . . . . . . . . . . . . . . . .24
. . . . . . . . . . . . . . . . . . . . . . . . .24
. . . . . . . . . . . . . . . . . . .26
. . . . . . . . . . . . . . . . .26
. . . . . . . . . . . . . . . . .26
. . . . . . . . . . . . . . . . . .26
. . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Page
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions. All other operations should be performed by trained service personnel. When working on air-conditioning equip­ment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Improper installation, adjustment, alteration, service, main­tenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The quali­fied installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individ­ual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and the National El ectrical Code (NEC) for special installation requirements.
Understand the signal words — DANGER, WARNING, and CAUTION. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards that could result in personal injury or death. CAUTION is used to identify unsafe practices, which would result in minor personal injury or product and property damage.
Recognize safety information. This is the safety-alert symbol ( ). When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Electrical shock can cause personal injury or death. Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Turn off accessory heater power if applicable.
GENERAL
IMPORTANT: The installation of water source heat pump units and all associated components, parts, and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsi­bility of the installing contractor to determine and comply with ALL applicable codes and regulations.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 5 a 5 a
PC 111 Catalog No. 535-00077 Printed in U.S.A. Form 50RLP-1SI Pg 1 1-03 Replaces: New
The Aquazone™ System Control Panel is a single packaged system control panel for use with Aquazone water source heat pumps (WSHPs) in stand-alone or direct digital control applications using the Carrier Comfort Network (CCN). The Aquazone system control panel controls and monitors the operation of the water source heat pumps, the ancillary heat rejection, the heat addition, and the system pumps to coordi­nate entire system operation. The Aquazone System Control Panel is used with the following units: 50HQL, KQA, KQD, RDS, RHC, RHR, RHS, RTG, RVC, RVR, RVS, RWS, VQA, VQD.
The Aquazone system control panel includes a pre­programmed 6400 main logic comfort controller as the central processing unit. The Aquazone system control panel is compat­ible for use in boiler/tower (water loop) or geothermal (ground loop, ground water) water source heat pump arrangements.
Other system hardware components are specified in the 50RLP model nomenclature. Components can be added to cus­tomize the Aquazone System Control Panel for the specific type of functionality desired, including staged heat rejection and addition, dual or variable speed pump operation, and stand­alone or CCN installations. See Fig. 1.
Aquazone System Control Panel Functional­ity —
Functionality includes the ability to control up to two water-circulating pumps and monitor water temperature to initiate up to eight stages of cooling tower and/or boiler opera­tion. The system control panel has the capability to work with variable speed pumping arrangements for maximum energy efficiency. In addition, the panel provides system control for both stand-alone and DDC water source heat pump systems (units installed with a factory-mounted PremierLink™ CCN controller).
Stand-Alone Systems —
trol strategy, non-communicating Aquazone water source heat pump thermostats are utilized to initiate the operation of individual water source heat pump equipment for eac h zone. The Aquazone System Control Panel can be ordered with the appropriate hardware to accommodate and initiate scheduled control of either 10 or 18 zones of WSHP units in stand-alone operation. See Fig. 2.
In a stand-alone type of con-
CCN Systems Using PremierLink Controls —
To implement a direct digital control type of water source heat pump system strategy , individual WSHP units are ordered with a factory-installed PremierLink controller. The Aquazone sys­tem control panel has been pre-programmed to w ork specifi­cally with th e Pr e m ie r L in k co ntroller to trans f er a n d c o ntrol all modes of cooling/heating operation, transmit unit number, zone temperature, zone temperature set points, discharge air temperature, fan status, stages of heating, stages of cooling, leaving water temperature, and alarm status information. See Fig. 3.
COMPONENTS
Aquazone System Control Panel Hardware —
The 50RLP Aquazone System Control Panel package consists of the following hardware. See Fig. 4.
ENCL OS U RE — The Aquazone system control panel enclo­sure is constructed of perforated 16-gage steel and finished in a gray powder-coated finish. The panel has a height of 42 in., a width of 30 in. and a depth of 7 inches.
PROC ESSO R — The central processing units for the Aqua­zone system control panel are Carrier 6400 Comfort Control­lers. The Comfort Controller provides general purpose HVAC control and monitoring capability in a stand-alone or network environment using closed-loop, direct digital control. The 6400 Comfort Controller has been pre-programmed to work in either stand-alone or CCN water source heat pump system installa­tions. Specifications for the 6400 Comfort Controller may be found in the Comfort Controller literature.
PUMP CON TROL RELAYS — For both stand-alone and CCN systems (based on the type of pumping operation required) the Aquazone system control panel can be orde red with a combination of multi-voltage control relays to provide start/stop or lead/lag operation for single or dual pumps. The combination desired is specified in the 50RLP model nomen­clature in digit 8. See Fig. 1.
50RLP 0 0 0 0
Unit 50RLP – Aquazone System Control Panel
System Heat Rejection 0 – 2-Stage Card (2 Stages of Cooling Tower Operation) 1 – 4-Stage Card (4 Stages of Cooling Tower Operation) 2 – 2- and 4-Stage Cards (6 Stages of Cooling Tower Operation) 3 – Two 4-Stage Cards (8 Stages of Cooling Tower Operation) 4 – No Card, Variable Speed Cooling Tower Operation
*Option is utilized with Aquazone Thermostat for each WSHP unit.
†Option is utilized with PremierLink DDC control option on individual WSHP units.
**Accepts signals from a variable frequency device.
Fig. 1 Model Number Nomenclature
WSHP Zone Operation 0 – 10 Relays, Control 10 Zones for Stand-Alone WSHP Units* 1 – 18 Relays, Control 18 Zones for Stand-Alone WSHP Units* 2 – No Relays, Carrier Comfort Network (CCN) System†
System Pumping Operation 0 – Both Relays, Start/Stop or Lead/Lag Operation for Single or
Dual Pumps
1 – No Relays, Variable Frequency Pump Operation**
System Heat Addition 0 – 2-Stage Card (2 Stages of Boiler Operation) 1 – 4-Stage Card (4 Stages of Boiler Operation) 2 – 2 and 4-Stage Cards (6 Stages of Boiler Operation) 3 – Two 4-Stage Cards (8 Stages of Boiler Operation) 4 – No Card, Modulating Valve Operation for Steam or
Hot Water
2
COOLING TOWER
BOILER
EXPANSION TANK
AIR SEPARATOR
PUMP
WSHP
FLOW
SENSOR
TEMP.
SENSOR
T-S TAT
AQUAZONE
SYSTEM
CONTROL
PANEL
LEGEND
Control Wiring Loop Water Piping
Fig. 2 Typical Stand-Alone WSHP System
If variable frequency drives are utilized for system pumps, no pump control relays are specified. Each relay contains a red light-emitting diode (LED), which indicates the relay coil is energized. The pump control relays are located in the upper left hand corner of the system control panel. See Fig. 4. Wiring is shown in Fig. 5A-5C. Specifications for the pump control relays are as follows:
Voltage Input: 24 vdc @ 15 mA, 14 vac @ 30 mA,
115 vac @ 20 mA, 230 vac @ 20 mA.
Contact Rating: 10 A res. @ 115 vac,
7 A res. @ 230 vac/28 vdc,
1
N.O.:
/6 hp @ 115 vac. T emperature Range: –60 F to 185 F Indication: LED Enclosure: 18 ga. metal back Dimensions: 5.125-in. x 3.125-in. x 2.5-in.
(HxWxD) or 5.125-in. x 9.5-in. x
2.5-in. (HxWxD)
OUTPUT TRANSDUCERS — For both stand-alone and CCN systems (based on the stages of heat addition or rejection required) the Aquazone™ system control panel can be ordered with a combination of 2-stage and 4-stage output transducers to provide 2, 4, 6, or 8 stages. The combination desired i s speci­fied in the 50RLP model nomenclature in digit 6 to specify heat rejection stages and digit 7 to specify heat addition stages. See Fig. 1. If variable speed cooling tower fan operation and/or
WSHP
T-S TAT
WSHP
T-S TAT
WSHP
T-S TAT
modulating valve operation for steam or water a re utilized, no output transducer card is specified. The output transducer is a solid-state multi-stage device used for staging control from a single analog signal. Output transducers are located in the upper left hand corner of the Aquazone System Control Panel underneath the pump control relays. See Fig. 4. Specificat ions for the pump control relays are as follows:
Supply Voltage: 24 vac ± 10% @ 100 mA,
24 vdc ± 10% @ 50 mA Input Signal: 4-20 mA Output: 2 SPDT relays for 2-stage,
4 SPDT relays for 4-stage. Relay rating: 5A @ 120 vac Accuracy & repeatability: ± 1% Set point adjustment: 25-turn potentiometers Input impedance: 250 W (mA input), 10 kW
(V input) T emperature Range: 32 F to 158 F Humidity Limit: 5 to 95% relative humidity
non-condensing Dimensions: 3.25-in. x 3.5-in. x 1.375-in.
(HxWxD) for 2-stage, 3.25-in. x
5.5-in. x 1.375-in. (HxWxD)
for 4-stage Relay Differential: 0.5 mA or 0.375 V.
3
ZONE 2
ZONE 1
ROOM SENSOR
S
S
WSHP 2
WSHP 1
PREMIERLINK
WSHP CONTROLLER
PREMIERLINK
WSHP CONTROLLER
FAN(S)
SPRAY PUMP
STAGE 2
STAGE 1
MAIN
STANDBY
LOOP TEMP
VENTILATION FAN
COMPUTER
COMPUTER
–PC ACCESS
LOCAL
REMOTE
TOWER
BOILER
PUMPS
LT
TELEPHONE
LINE
AQUAZONE SYSTEM
LCP
LOOP CONTROL PANEL (CARRIER COMFORT CONTROLLER)
CARRIER COMFORT NETWORK BLDG.
MASTER CONTROL PANEL
MCP
R
T
M
(CARRIER COMFORT CONTROLLER)
REPEATER: INTERFACE PC TO NETWORK
TELINK WITH MODEM CONTROLLER
DATA COLLECTION
LOADSHED
COMFORT CONTROLLER
TENANT BILLING
LIGHTS
EQUIPMENT
D.C.
L
E
L.S.
CC6400
T.B.
BLDG./SYST. MANAGEMENT
Fig. 3 CCN Water Source Heat Pump System with PremierLink Controllers
4
g
g
g
g
y
FLT SEQ
FLT SEQ
MODE
A
MODE
A
FLT SEQ
A
A
MODE
A
FLT SEQ
A
MODE
A
A
HOA
Pump 1
Pump 2
B
C
B
Cool Sta
B
C
B
Cool Stages 2
B
C
B
Heat Sta
B
C
B
Heat Sta
Processor Input/Output 1 Input/Output 2
Low Volta
e
Zone Thermostat
Control Rela
UCS-421
MODE
INPUT
FLT SEQ
TYPE
H3
MODE
D
UCS-421
D
UCS-421
D
CH
V
H4
H5
MA
24V
INPUT
CHAIN
SIGNAL
POWER
OUTPUT
COMMON
INPUT TYPE
H3
CH
V
H4
H5
MA
24V
INPUT
CHAIN
SIGNAL
POWER
OUTPUT
COMMON
INPUT
TYPE
H3
CH
V
H4
H5
MA
24V
INPUT
CHAIN
SIGNAL
POWER
OUTPUT
COMMON
D
C
es 1
MODE
FLT SEQ
D
C
FLT SEQ
D
C
s
es 1
UCS-421
MODE
INPUT
FLT SEQ
TYPE
H3
D
C
CH
V
H4
H5
MA
24V
INPUT
CHAIN
D
SIGNAL
POWER
OUTPUT
COMMON
es 2
POWER SWITCH
CONVENIENCE OUTLET
PANDUCT® WIRING DUCT
Transformer 1 Transformer 2
CONDUIT
Fig. 4 Aquazone System Control Panel
Trans former 3
5
COMPLETE C CONTROL
(IN WSHP)
RYW OGC
SYSTEM ZONE RELAYS (1-18)
NO
R
W1
G
THERMOSTAT
Y1
W2
Fig. 5A System Zone Relay Wiring
(Aquazone System Control Panel Used to
Control a Single Thermostat)
PANEL 24 VAC POWER
Y2
X1
H
FIRE
FREEZE,
ETC.
SWITCH S-1
C
Fig. 5C Control Relay Wiring for Pump
Start/Stop or Cooling Tower Fan
O
A
TP WIRES
L
(+)
(-)
TO COMFORT CONTROLLER
STARTER
COIL
M
CONTROL RELAY OR STAGING CARD
OL
X2
s
N
TO OTHER WSHP COMPLETE C CONTROLS AND THERMOSTATS
H
SYSTEM ZONE
RELAYS
(1-18)
Fig. 5B System Zone Relay Wiring
(Aquazone System Control Panel Used to Control Multiple Thermostats)
COMPLETE C CONTROL
RYW OGC
TYPICAL FIELD-INSTALLED RELAYS (ONE PER WSHP)
(IN WSHP)
G
R
W1
THERMOSTAT
Y1
W2
Y2
C
ZONE THERMOSTAT CONTROL RELAYS — A unique feature of the Aquazone system control panel is the capability to add zone ther mostat contr ol rela ys. T his feat ure is used w hen th e Aquazone system control panel i s utilized in a st and-alone type of installation. Eithe r a set of 10 or 18 relays can be selected from the 50RLP model nomenclat ure in digi t 9 to control ei the r 10 or 18 zones, respectively. If selected in the model nomencl a­ture, zone control relays are located on the right hand side of the system control panel. See Fig. 4. See Fig. 5A-5C for wiring.
CONTROL TRANSFORMERS — Control transformers are supplied with the Aquazone system control panel and are wired to the power switch and convenience outlet. The control transformers provide power to the nominal 24 VAC circuit in Aquazone system control panel. The contractor will supply the
primary power to the power switch and conve nience outlet in the field. Transformers include a manual reset button for reset­ting the circuit breaker. Control transformers are located on the bottom half of the system control panel. Specifications for the control transformers are as follows:
Primary: 120/208/240 vac Secondary: 24 vac Frequency: 60 Hz
MOUNTING RAILS AND WIRING DUCT — All exposed panel wiring is low voltage. Line voltage wiring to the control transformers, control circuits for pumps, cooling tower fans, and boilers is factory-installed in conduit, using wiring duct, and on mounting rails.
6
POWER RECEPTACLE — A power receptacle is provided in the Aquazone™ system control panel and is located in the bottom left corner. Specifications for the power receptacle are as follows:
Power: 120 vac Rating: 15A @ 120 vac for receptacles
15A @ 120 vac for switch 250 V for fuse
WATER TEMPERATURE SENSORS — Two water tem­perature sensors and thermowells have been provided with the Aquazone system control panel. The first sensor is utilized to read loop supply water temperature, such that the system control panel can adjust heat rejection and heat addition equipment to maintain the loop temperature based on user input. The second sensor may be installed to monitor return loop water temperature. The active sensing element is a highly stable precision thermistor material accurate to within ± 0.36 F. The temperature range of the sensor is 10 F to 230 F.
WATER PRESSURE SENSOR — A water pressure sensor is provided with the Aquazone system control panel with variable speed pumping only , and is utilized to operate variable frequen­cy drives for system pumps. The water sensor senses system pressure and the pressure is sent to the system control panel. The Aquazone system control panel speeds up or slows down the variable frequency drive to control the pump in order to keep the system at the correct pressure.
When a variable frequency drive is used for system pump­ing, the Aquazone water source heat pumps are typically furnished with a factory or field-mounted solenoid valve that allows water to flow though the heat pump. When solenoid valves open, the system pressure drops, which results in the variable frequency drive speeding up to allow the pump to
provide more water. When solenoid valves close, the system pressure rises, which results in the variable frequency drive slowing down to allow the pump to provide less water.
WATER FLOW SWITCH — A factory-provided wat er flow switch is included with the Aquazone system control panel and must be field-installed in the water loop piping. The flow switch is connected to the control panel by a cable with a watertight connector. This device uses a triac output that cannot be connected directly to the Main Base Board. Therefore, a control relay is used to signal the Main Base Board that loop water flow is detected. The switch contains a fifteen-turn adjustment potentiometer, to be used to adjust the set point in a range of 3 to 60 cm/sec. The factory set point is 20 cm/sec.
The potentiometer switch may be adjusted down to zero velocity (no flow) or above 60 cm/sec, however operation in those ranges may not be linear or reliable.
Water Source Heat Pumps with PremierLink Controller Hardware
tion is implemented, a factory-mounted PremierLink controller is provided with the water source heat pump units. The package from the factory includes the PremierLink controller, supply air temperature sensor , and leavi ng water t emperatur e sensor.
PREMIERLIN K CONTROLLER — PremierLink controllers can be provided with any Aquazone water source heat pump product by selecting this option in the model nomenclature. See Fig. 6.
The PremierLink controller is provided with the Complete C
unit controller . F actory sup plied wiring is i llustrated in F ig. 7.
When a CCN system installa-
Fig. 6 PremierLink Control Module
7
Carrier’s diagnostic standard tier display tools such as Navigator™ or Scrolling Marquee can be used with the PremierLink™ controller. Access is available via an RJ-11 connection or a 3-wire connection to the communication bus. Computers equipped with Carrier user interface software such as Service Tool, ComfortVIEW™, or ComfortWORKS® software are used to int erface with the system. W hen used as part of the CCN, other devices such as the CCN data transfer, Linkage Thermostat, or system control panel comfort controller can read data from or write data to the PremierLink Controller.
SUPPLY AIR TEMP ERATURE SENSOR — A factory­installed supply air temperature sensor is provided with the PremierLink controller. Wiring of the temperature sensor is shown in Fig. 7. The sensor is a 10 kohm thermistor, which is protected by a stainless steel housing probe. Probe is
1
/4-inch in diameter and 1.5-in. long. Wire is 22 AWG (American Wire Gage), 7/30 copper wire, PVC white, 2 conductor type.
LEAVING WATER TEMPERATURE SENSOR — A factory­installed leaving water temperature sensor is provided with PremierLink controller. Wiring of the temperature sensor is shown in Fig. 7. The sensor is a 10 kohm thermistor is protect­ed by a stainless steel housing probe. Probe is
1
/4-inch. in diam­eter and 1.5-in. long. Wire is 22 AWG , 7/30 copper wi re, PVC white, 2 conductor type.
Field-Supplied Hardware for Stand-Alone Sys­tems
stand-alone configuration, individual Aquazone thermostats (or compatible equivalent) are required for water source heat pump units.
AQUAZONE THERMOSTAT — A field-supplied Carrier thermostat is required to maintain space temperature for stand­alone water source heat pump installations. There are five different Aquazone thermostats available for stand-alone appli­cations. See Table 1.
T o utilize the Aquazone™ system control panel in a
LEGEND
CR LW T SAT SPT
NOTE: Reversing valve is on in Cooling mode.
Control Relay Leaving Water Temperature Sensor Supply Air Temperature Sensor Space Temperature Sensor
J6
S P T
J5
L
S A
W
T
T
PREMIER
LINK
J8
PWR
J1
CMPSAFE
PWR
HS1/EXH/RVS
CMP1
FAN
J4
CR
CR
COMPLETE
C
CONTROL
Y
W
O
G
R
C
AL1
AL2
A
Fig. 7 PremierLink Controller Applications with Complete C Control
8
Table 1 Aquazone Thermostats
ORDERING
NUMBER
50QE900-220WS
50QE900-220LA
50QE900-NPWS
50QE900-511WS
50QE900-250FS
THERMOSTAT TYPE FUNCTIONS
Aquazone 7-Day Programmable 2 stages heating, 2 stages cooling, auto changeover
Fahrenheit and Celsius temperature scales
Carrier
AUTO
®
Pm
COOL
HEAT
4 settings per day 24 vac Backlit LCD Keypad 5-minute compressor protection NEVERLOST memory 3 security levels
Aquazone Light Activated, 7-Day Programmable
2 stages heating, 2 stages cooling, auto changeover
4 settings per day
Carrier
AUTO
®
Pm
COOL
HEAT
24 vac
Keypad lockout
5-minute compressor protection
Occupied with lights on, unoccupied with lights off
NEVERLOST memory
3 security levels
Aquazone Non-programmable 2 stages heating, 2 stages cooling, auto changeover
5-minute built-in compressor protection
R
Locking cover included Fahrenheit and Celsius temperature scales
AUTO
COOL
HEAT
Large display Keypad lockout Backlit display or B terminal NEVERLOST memory Dual set point with adjustable deadband Back plate with terminals
Aquazone 5-1-1 day programmable 2 stages heating, 2 stages cooling, auto changeover
5-minute built-in compressor protection
R
Keypad lockout and locking cover included Fahrenheit and Celsius temperature scales
AUTO
COOL
HEAT
4 settings per day Backlit and configurable display O or B terminal NEVERLOST memory Dual set point with adjustable deadband Self prompting program
Aquazone Flush Mount, 7-Day Programmable 2 stages heating, 2 stages cooling, auto changeover
4 settings per day, Holiday/vacation programming Self prompting program with copy command locking
cover plate with tamperproof screws Fahrenheit and Celsius temperature scales Set point limiting Mounts flush to the wall NEVERLOST memory Dual set point with adjustable deadband and B terminal Remote sensor capability (sold separately): Wireless,
(33CSRFS-RC transmitter and 33CSRFS-RE receiver), wired with override (33CSCEN-WB), duct mounted (33CSSEN-DS)
Field-Supplied Hardware For CCN Applica­tions
the water source heat pump unit is configurable with a variety of Carrier space temperature sensors.
SP A CE TEMPERATURE SENSOR (SPT) — A field-supplied Carrier space temperature sensor i s required to mai ntain spac e temperature in sensor mode. There are three sensors ava ilable for this application: the 33ZCT55SPT Space Temperature Sensor with Override Button, the 33ZCT56SPT Space Temperature Sensor with Override Button and Set Point Adjustment, and the 33ZCT58SPT T58 Communicating Room
The factory-installed PremierLink™ controller for
Sensor with Override Button, Set Point Adjustment, and Manual fan control.
INDOOR AIR QUALITY CO quality sensor is required for CO
SENSOR — An indoor air
2
level monitoring. Three
2
different CO2 sensors are available for this application: the 33ZCSENCO2 sensor is an indoor, wall-mounted sensor with an LED display, the 33ZCT55CO2 sensor is an indoor, wall-mounted sensor without display (also includes a space temperature sensor with override button), the 33ZCT56CO2 sensor is an indoor, wall-mounted sensor without display (also includes a space temperature sensor with override button and temperature offset).
9
INSTALLATION
Inspection
fects that may have occurred during shipping. If there is any damage, contact your local representative before proceeding.
Mounting Location
panel should be located indoors. Be sure the location preve nts moisture and rain from coming into contact with the internal hardware. Avoid areas where excessive moisture, corrosive fumes, or vapors are present. The ambient temperature range at the location should be between 32 to 125 F. Do not install the Aquazone system control panel in electrical interference or high radio frequency areas. Select a location which will be safe from water damage and allow sufficient access for service and
Inspect the package contents for visual de-
The Aquazone™ system control
wiring. For proper service of the Aquazone system control panel, the following service clearances are recommended:
Height: 54 in. Width: 42 in. Depth: 36 in.
Mounting
Mount the Aquazone system control panel to a wall with screws or bolts (not provided). Attach through the mounting holes provided in enclosure. Provide clearance to open key-locked access door. Refer to the mounting sheet in­cluded with the Aquazone system control panel for additional detailed mounting instructions.
Wiring
The Aquazone System Control Panel inputs and
outputs are shown in Table 2.
Table 2 Aquazone System Control Panel Inputs and Outputs
PARAMETER POWER INPUT/OUTPUT TERMINAL
Processor Module
Loop Water Flow 24 vdc Input FLOW System Supply Water Temp. 10 K thermistor Input SSWT System Return Water Temp. 10 K thermistor Input SRWT System Differential Pressure 4-20 mA Input SDP Remote Occupied Mode 24 vdc Input RMTOCC System Shut Down 24 vdc Input ALLSYS Override Input for Zones 1 & 2 24 vdc Input OVRIZ1, OVRIZ2 Pump Number 1 & 2 Speeds 4-20 mA Output PUMP1, PUMP2 Cooling Tower 1 & 2 Speed/Level 4-20 mA Output CTL1, CTL2 Heat Source 1 & 2 Speed/Level 4-20 mA Output BLRL1, BLRL2 System Enable for Zone 1 & 2 24 vdc Output SYSZ1, SYSZ2
First Optional I/O Module
Override Input for Zone 3 to 10 24 vdc Input OVRIZ3 OVRI Z10 System Enable for Zone 3 to 10 24 vdc Input SYSZ3 SYSZ10
Second Optional I/O Module
Override Input for Zone 11 to 18 24 vdc Input OVRIZ11 OVRIZ18 System Enable for Zone 11 to 18 24 vdc Input SYSZ11 SYSZ18
Pump Control
Occupancy Schedule 1 to 18 Logic Internal Parameter Network Global Schedule 65 to 82 Logic Internal Parameter Override Input 1 to 18 Logic Input OVRIZ1 OVRIZ1 8 System Enable Outputs Logic Output SYSZ1 SYSZ18 Remote Occupied Mode Logic Input RMTOCC System Differential Pressure Logic Input SDP System Differential Pressure Set point Logic User Configuration Loop Water Flow Logic Input FLOW Control Type Logic User Configuration Pump Number 1 & 2 Speeds Logic Output PUMP1, PUMP2 Shut Down Command Logic Output ALLSYS
Heat Rejection Control
System Supply Water Temp. Logic Input SSWT System Return Water Temp. Logic Input SRWT System Loop Temperature Set points Logic User Configuration Fluid Cooler/Tower Control Logic User Configuration Loop Water Flow Logic Input FLOW Cooling Tower 1 & 2 Speed/Level Logic Output CTL1, CTL2
Heat Addition Control
System Supply Water Temp. Logic Input SSWT System Return Water Temp. Logic Input SRWT System Loop Temperature Set points Logic User Configuration Boiler Control Type Logic User Configuration Loop Water Flow Logic Input FLOW Boiler 1 & 2 Speed/Level Logic Output BLRL1, BLRL2
10
PREMIERLINK™ CONTROLLER INPUTS AND OUT­PUTS — When PremierLi nk controllers are factory mounted with water source heat pump equipment to implement a CCN system installation, the inputs and outputs are shown in T able 3.
CONNECT POWER — The Aquazone™ system control panel requires an uninterrupted 110-v, single-phase, 60 Hz power supply. All field wiring must comply with all local and national fire, safety and electrical codes. It is recommended that the power supply be separate from the power source supplying the water source heat pumps. The Aquazone system control panel is internally fused and a power switch is located
Table 3 PremierLink Controller Inputs and Outputs
INPUTS POWER TERMINAL(S) SPACE TEMPERATURE (SPT) SET POINT ADJUSTMENT (STO) SUPPLY AIR TEMPERATURE (SAT) LEAVING WATER TEMPERATURE IAQ SENSOR (IAQI) REMOTE TIME CLOCK (RMTOCC) COMPRESSOR LOCKOUT (CMPSAFE) FIRE SHUTDOWN (FSD) SUPPLY FAN STATUS (SFS) NOT USED
OUTPUTS POWER TERMINALS FAN (SF) COOL STAGE 1 (CMP1) COOL STAGE 2 (CMP2) HEAT STAGE 1 (HS1) HEAT STAGE 2 (HS2) HEAT 3/EXHAUST/REVERSING VALVE (HS3/EXH/RVS)
inside the enclosure. Supply power to the Aquazone system control panel through the convenience outlet in the bottom left hand corner of the Aquazone system control panel. Do not apply power until all connections have been made and voltage supply has been verified. Ground in accordance with NEC and local electrical codes. Connect the dedicated ground wire to the position in relationship to the main supply line and use shield cable to protect from any electrical interference.
CONTROL WIRING — Low voltage wiring for the Aqua­zone system control panel is shown in Fig. 8.
AI (10 K Thermistor) J6-7, J6-6 AI (10 K Thermistor) J6-5, J6-6 AI (10 K Thermistor) J6-3, J6-4 AI (10 K Thermistor) J6-1, J6-2 (4-20 mA) J5-5, J5-6 DI (24 vac) J4-11, J4-12 DI (24 vac) J4-9, J4-10 DI (24 vac) J4-7, J4-8 DI (24 vac) J4-5, J4-6
——
DO Relay (24 vac, 1A) J8-18 DO Relay (24 vac, 1A) J8-15 DO Relay (24 vac, 1A) J8-12 DO Relay (24 vac, 1A) J8-9 DO Relay (24 vac, 1A) J8-6 DO Relay (24 vac, 1A) J8-3
LEGEND
AI DI DO
Analog Input Digital Input Digital Output
11
SYSZ18
2345 1678
45
PCB1
SW1
12345678
SW2
12345678
SW3
12345678
SW4
12345678
SW5
1
2
SW6
1
2
RED
PCB2
SW1
1
2345678
SW2
12345678
SW3
12345678
SW4
12345678
SW5
1 234
SW6
1 234
PCB2
RED
PCB3
SW1
1 2345678
SW2
1
2345678
SW3
1
2345678
SW4
12345678
SW5
1 234
SW6
1 234
AB
GRN
1
J2
2
BLK
3
RED
16 15 14 13 12 11 10
9
J4
8
1
7
0
6
INT
5
EXT
4
4-20mA
3
OTHER
2
0-10VDC
1
4-20mA
18
DO
34
17
AO
16
DO
34
15
AO
14 13 12 11 10
J3
9 8 7 6 5 4 3
J7
2
123
1
BLK
WHT
1
123
2
J7
3
J2
16 15 14 13 12 11 10
9
J4
8 7
1
0
6 5
INT
EXT
4 3
4-20mA
2
OTHER
1
0-10VDC
4-20mA
18
DO
17
AO
16
DO
15
AO
14 13 12 11 10
J3
9 8 7 6 5 4
To
3 2
J7
1
BLK
WHT
1
123
2
J7
J2
3
16 15 14 13 12 11 10
9
J4
8 7
1
0
6 5
INT
EXT
4 3
4-20mA
2
OTHER
1
0-10VDC
4-20mA
18
DO
17
AO
16
DO
15
AO
14 13 12 11 10
J3
9 8 7 6 5 4 3 2 1
GRN
BRN RED
GRN
BRN RED
TB1
+
-
TB3
TB2
TB5
TB4
78 OVRZ 2
56 OVRZ1
34 ALLSYS
12 RMTOCC
SDP
SRWT
SSWT
64 FLOW
78 OVRZ 10
56 OVRZ9
34 OVRZ8
12 OVRZ 7
78 OVRZ 6
56 OVRZ5
34 OVRZ4
12 OVRZ 3
78 OVRZ 18
56 OVRZ 17
34 OVRZ 16
12 OVRZ 15
78 OVRZ 14
56 OVRZ 13
34 OVRZ 12
12 OVRZ 11
8
SYSZ1
7
SYSZ2
7
AB
Fig. 8 Typical Aquazone System Control Panel
C
D
E
Loop PanelLOW VOLTAGE CONTROL WIRING
TBP
1
RED
8
24 VAC
Common
Signal
Input
Chan
Output
24 VAC
Common
Signal
Input
Chan
BLRL1
Output
CTL2
2
24 VAC
Common
CB1
BLU
FLOW
1
Signal
Input
Chan
Output
CTL1
8
FLOW
7
24 VAC
Common
OFF
AUTO
T1
24 V
Signal
Input
Chan
Output
BLRL2
RED
SW
PUMP2
ON
OFF
AUTO
TBP
RED
3
BLU
TBP
RED
5
BLU
C
CB2
CB3
D
SW
PUMP1
ON
RED
T2
24 V
SYSZ10
7
7 8SYSZ9
7 8SYSZ8
7 8SYSZ7
7
SYSZ6
7 8SYSZ5
7 8SYSZ4
7 8SYSZ3
T3
24 V
7
SYSZ18
7 8
SYSZ17
7 8
SYSZ16
7 8
SYSZ15
SYSZ14
7
7 8
SYSZ13
7 8
SYSZ12
7 8
SYSZ11
GRN
TBP
YB
YEL
BLK
2345 1678
BRN
GRN
X2X1
YEL
8
BRN
BRN
BRN
BRN
8
BRN
BRN
BRN
BRN
BRN
GRN
X2X1
YEL
8
BRN
45
BRN
BRN
BRN
8
BRN
BRN
BRN
BRN
E
12
ALLSYS BLRL1 BLRL2 CB CTL1 CTL2 FLOW OVRIZ1 OVRIZ2 OVRIZ3 OVRIZ4 OVRIZ5 OVRIZ6 OVRIZ7 OVRIZ8 OVRIZ9 OVRIZ10 OVRIZ11
System Heat Source 1 Speed/Level Heat Source 2 Speed/Level Circuit Breaker Cooling Tower 1 Speed/Level Cooling Tower 2 Speed/Level Loop Water Flow Override Input for Zone 1 Override Input for Zone 2 Override Input for Zone 3 Override Input for Zone 4 Override Input for Zone 5 Override Input for Zone 6 Override Input for Zone 7 Override Input for Zone 8 Override Input for Zone 9 Override Input for Zone 10 Override Input for Zone 11
OVR IZ 12 OVR IZ 13 OVR IZ 14 OVR IZ 15 OVR IZ 16 OVR IZ 17 OVR IZ 18 PCB PUMP1 PUMP2 RMTOCC SDP SRWT SSWT SYSZ1 SYSZ2 SYSZ3 SYSZ4
LEGEND FOR FIG. 8
Override Input for Zone 12 Override Input for Zone 13 Override Input for Zone 14 Override Input for Zone 15 Override Input for Zone 16 Override Input for Zone 17 Override Input for Zone 18 Comfort Controller Circuit Board Pump Number 1 Pump Number 2 Remote Occupied Mode System Differential Pressure System Return Water Temperature System Supply Water Temperature System for Zone 1 System for Zone 2 System for Zone 3 System for Zone 4
SYSZ5 SYSZ6 SYSZ7 SYSZ8 SYSZ9 SYSZ10 SYSZ11 SYSZ12 SYSZ13 SYSZ14 SYSZ15 SYSZ16 SYSZ17 SYSZ18 T TB TBP
System for Zone 5 System for Zone 6 System for Zone 7 System for Zone 8 System for Zone 9 System for Zone 10 System for Zone 11 System for Zone 12 System for Zone 13 System for Zone 14 System for Zone 15 System for Zone 16 System for Zone 17 System for Zone 18 Transformer Terminal Block Terminal Block or Pin Connector
Install Thermostat, Sensors and Switches
In all installations, the loop supply water temperature sensor and water flow switch must be installed in the field. The water pressure sensor is used to sense water system pressure to operate in conjunction with pump variable frequency drives. A thermostat is used in stand-alone systems. A space tempera­ture sensor is used in conjunction with water source heat pumps provided with PremierLink™ controllers. Refer to the accessory installation instructions literature provided with each accessory that is used for accessory installation instructions.
NOTE: All thermostats, sensors, and switches are field­installed accessories.
Install Loop Water Supply and Return Tem­perature Sensors
sor in the main water supply, located before the water source heat pumps. Install the water loop return sensor in the return water piping from the water source heat pumps. The sensors must be inserted fully into an immersion well ( provided). Seal immersion well threads with tape and install into pipe tee or re­ducing fitting. The well screws into a Thredolet fitting) furnished by the installing contractor. Screw the sensor into the well via the nate wiring with butt splice or soldering. Wire nuts are not rec­ommended. Use full 8 ft of lead length provided to avoid mois­ture migration up the wire. Wire the supply sensor to terminals SSWT. Wire the return sensor to terminals SRWT. See Fig. 8. Sensors may be located in any position in relationship to the main supply line. Use shield cable to protect from any electri­cal interference.
Install Loop Water Pressure Sensor
pressure sensor on the discharge side of the circulating pump(s) in a common supply main so that total system pressure rather than individual pump(s) flow is detected. The pr essure sensor must be placed in a vertical position and must match the actual water flow direction with flow switch direction indicators. Seal the switch fitting with Teflon tape and insert in a
Install the water loop supply sen-
1
/2-in. NPT saddle (or
1
/8-in. NPT brass fitting. Termi-
Install the
1
/4-in.
standard pipe tee (Thredolet fitting) or reducing fitting, with at least three pipe diameters straight run upstream and down­stream of the switch. Wire sensor to terminals SDP. See Fig. 8.
Install Loop Water Flow Switch
Install the loop water flow switch on the discharge side of the circulating pump(s) in a common supply main so that total system flow rather than individual pump(s) flow is detected. The flow switch must be placed in a vertical position and must match the actual water flow direction with flow switches direction indica­tors. Seal the switch fitting with Teflon tape and insert in a stan­dard pipe tee or reducing fitting, with at least three pipe diame­ters straight run upstream and downstream of the switch.
Electrical connection can be made to the switc h. Two wires should be run to the switch for 24 VAC power. The switch is supplied with wire leads for connection to the FLOW terminal. When power is supplied to the device, a warm-up period is initiated. During this period, the right green LED will be lit. Each LED to the left is successively lit until the farthest left red LED is lit. Each LED will be turned off when the next is lit. The warm-up period may take up to 30 seconds.
When flow is detected, a red LED at the far left will be lit. With increasing flow, successive red LEDs will be lit. When the switch determines sufficient flow is present, the amber LED lights indicating the output has closed. This is not an indi­cation of minimum flow. As flow increases, the first green LED will be lit. Each successive green LED indicates greater flow. The switch closure does not indicate minimum flow for the machine. With one green LED lit, minor fluctuations in water flow may cause nuisance alarms. Additional green LEDs indicate higher flow rates, and can avoid the nuisance alarms. The switch is calibrated to light the amber LED at a fluid velocity of 0.8 ft/sec (0.24 m/sec). The flow rate will depend on the nozzle size. See Table 4. See Table 5 for Water Flow Switch Troubleshooting. If the water flow switch is not work­ing correctly, refer to Table 5.
SIZE
4 5 6 8
Table 4 Loop Water Flow Switch LED Display
SCHEDULE 40 PIPE
O.D. (in.) Wall Thickness (in.) I.D. (in.) Area (Ft
4.5 .237 4.026 0.09 32
5.563 .258 5.047 0.14 50
6.625 .28 6.065 0.20 72
8.625 .322 7.981 0.35 125
2
)GPM
13
Table 5 Water Flow Switch Troubleshooting
ENTER
PROBLEM SOLUTION
No display or output from the flow sensor
Flow sensor indicates zero flow when flow is present
Flow Sensor indicates flow when no flow is present
Check for 24 VAC across pins 1 and 3. These are small pins and caution should be used when measuring the voltage in the harness so as not to damage the connector.
Check flow switch pin connections for damage. Check for air in the chilled water system. Check for 24 vac across pins 1 and 3. These are small pins and caution should be used
when measuring the voltage in the harness so as not to damage the connector. Check for fouling on the sensor switch, which could inhibit the dissipation of heat from the probe. Consider replacing the flow switch. The switch might be out of calibration,
the internal heater may have been damaged by extreme temperatures, pressure or vibration, or mechanical damage to the tip of the device may have occurred.
Check for 24 vac across pins 1 and 3. These are small pins and caution should be used when measuring the voltage in the harness so as not to damage the connector. Low voltage can lead to less heat generated by the internal heater.
Consider replacing the flow switch. The switch might be out of calibration, the internal heater may have been damaged by extreme temperatures, pressure or vibration, or mechanical damage to the tip of the device may have occurred.
Connect to CCN Communication Bus
The Aquazone™ system control panel primary controller connects to the bus in a daisy chain arrangement. Negative pins on each component must be connected to respective negative pins and likewise positive pins on each component must be connected to respective positive pins. The controller signal pins must be wired to the signal ground pins. Wiring connections for CCN must be made at the 3-pi n pl ug. See Fig . 9.
At any baud (9600, 19200, 38400 baud), the number of controllers is limited to 239 devices maximum. Bus length may not exceed 4000 ft, with no more than 60 total devices on any 1000-ft section. Optically isolated RS-485 repeaters are required every 1000 ft.
NOTE: Carrier device default is 9600 baud. COMMUNICATION BUS WIRE SPECIFICATIONS —
The CCN Communication Bus wiring is field-supplied and field-installed. It consists of shielded three-conductor cable with drain (ground) wire. The cable selected must be identical to the CCN Communication Bus wire used for the entire network. See Table 6 for recommended cable.
Table 6 Recommended Cables
MANUFACTURER CABLE PART NO.
Alpha American Belden Columbia
2413 or 5463
A22503
8772
02525
NOTE: Conductors and drain wire must be at least 20 AW G (American Wire Gage), stranded, and tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of –20 C to 60 C is required.
The communication bus shields must be tied together at each system element. If the communication bus is entirely within one building, the resulting continuous shield must be connected to ground at only one single point. If the communi­cation bus cable exits from one building and enters another building, the shields must be connected to the grounds at a lightning suppressor in each building (one point only).
START-UP
LID Power Up Display
the Aquazone System Control panel, the red LED on the top front of the processor module will flash at a rapid pace (about twice a second) for the first 20 seconds. This rapid flash will then be replaced by a slower pace of about once per second.
The green LED below the red LED will start flashing. This LED indicates input/output communications for accessory input output modules and t he LID di spla y.
The first six red LEDs on the controller will light.
The yellow LED will flash when the controller is broadcast­ing CCN messages to a laptop or other computer.
The LID display will show the controller identification, time and date as shown below.
Aquazone System
hh:mm mm-dd-yy
Log On to the LID Display
display of the Aquazone System Control panel, perform the following procedure:
1. Press 3 and then . The LID display will show: Controller Password
2. Press . The LID display will show: Log in to Controller Enter Password NOTE: The LID display has two modes: Edit mode and Status/Maintenance mode. If the LID display is in Edit mode, then the display will only show the word “pass­word.” Press the key to toggle to the Status mode.
3. Key in the password and press . NOTE: The default password is 1111.
4. The LID display will show: Log in to Controller Logged In
SET
EXPN/EDIT
When power is applied to
To Log On to the LID
ENTER
14
CLEAR
NOTE: Do not bundle power and communication wiring with sensor and device wiring.
Fig. 9 Connection to CCN Bus
Change the Default Password
To change the
default password, perform the following procedure: NOTE: The password must have already been entered to per-
form this procedure.
1. Press 3 and then . The LID display will show:
SET
Controller Password
2. Press . The LID display will show:
ENTER Log in to Controller Enter Password
3. Press . The LID display will show:
EXPN/EDIT Password 1111
4. Enter the new password (up to 8 digits) and press ENTER
. The LID display will show: Password (New Password)
5. Press to leave the password screen and return to
CLEAR
the default display screen.
Set the Clock
The user must be logged in to set the
clock. To set the clock, perform the following procedure:
1. Press 1 and then . The LID display will show:
SET
Set Clock
2. Press . The LID display will show:
ENTER No Maintenance NOTE: There is no maintenance informat ion regarding
setting the clock.
3. Press . The LID display will show:
EXPN/EDIT Time 00:00
4. Enter the time. The time is entered in military time (for example 14.59 for 2.59 pm). Press the button. The LID display will show:
Day of W eek 1
5. Enter the day of week. The numbers 1 through 7 corre­spond to the days of the week (1 = MON, 2 = TUE, 3 = WED, 4 = THUR, 5 = FRI, 6 = SAT, 7 = SUN). Press
. The LID display will show:
Month 1
6. Enter the number of the corresponding month (1 through
12). Press . The LID display will show: Day
1
7. Enter the day of the month. Press . The LID display will show:
Year 95
8. Enter the last two digits of the current year. Press . The LID display will show:
Update Clock No
9. Press 1 and then to change display to a YES.
ENTER
Press . The clock will be updated. Press
ENTER
twice to view the default display and the clock
should update to the input time and date.
15
Configure Schedules
ALGO
ENTER
ENTER
CLEAR
perform the following procedure:
1. Press 1 and then . The LID display will show: Occupancy Algorithm
2. Press . The LID display will show:
3. There are 18 occupancy algorithms: OCCPC01 to
4. Press . If the LID display shows “MODE 0”
5. Press . The LID display will show:
6. Press the button. The LID display will show:
7. Input the Occupancy Start time for this period.
8. Press the to input the Occupied To time for period 1.
9. Input the days and times for periods 2 through 8 as
10. Press clear to leave the occupancy programming.
ENTER Occupancy 01 OCCPC01
OCCPC18. There is one algorithm for each of the 18 zone relay outputs. Use the up and down arrows to select the desired schedule to modify then press
ENTER Time Schedule Enter to select
ENTER then the user is in Maintenance mode and the LID display is showing the maintenance information for the occupan­cy schedule. Press to enter the configura­tion mode. The LID display will show:
Manual Override Hours 0 hours This is the first configuration for each occupancy algo-
rithm and is used to put the schedule in or out of occupan­cy override for the number of hours entered.
Period 1: Day of week 00000000 The eight digits represent if this period should apply to
certain days of the week or holidays. The digits represent M, Tu, W, Th, F, Sa, Su, and Hol, respectively. Enter a series of 0s or 1s with a 1 corresponding to the days that this period should apply to and a 0 for the days that this schedule should not apply to. As an example, entering 11111000 would make the schedule apply to days Mon­day through Friday and not apply to Saturday, Sunday, or Holidays.
Period 1 occupied from 00:00
NOTE: 12.00 represents 12:00 pm.
required.
SCHD
. The LID display will show:
Program Set Points
form the following procedure:
1. Press 2 and then . The LID display will show: Setpoint Schedule
2. Press . The LID display will show:
3. Press .
4. If “No maintenance” is displayed, pres s t o
ENTER Loop W ater Supply SETPT01
ENTER
view the set point information. The LID display will show:
Occupied Lo Setpoint
60.00
SCHD
To configure the schedules,
EXPN/EDIT
To program the set points, per-
EXPN/EDIT
This set point is the Loop Low Water Temperat ure set point.
5. Press . The LID display will show: Occupied Hi Setpoint
90.00 This set point is the Loop High Water Temperature set
point. The down or up arrow will also display the Unoccupi ed
Low and High Temperature set points. These values should be kept the same as the occupied values.
6. The system pressure set point (SETPT02) is used for controlling variable speed pumps. This can be accessed by pressing the down or up arrow when SETPT01 is on the display.
7. Pressing the button will take the user out of the set point configuration mode.
Check System Parameters
parameters, press the button. The LID display will show: “Hardware Points”. Pr ess to view the hard­ware points. The user can navigate up and down through the points with the up and down arrows.
Press 2 and to display the software points. The user can navigate up and down through the points with the up and down arrows.
Refer to the Configuration section for a listing of the hard­ware and software points.
Display Alarm History
there are alarms, the user can view the alarm history by pressing the button. The LID display will show “Alarm History.” Press . The LID display will show the date and type of alarm.
As an example, if the LID display shows:
ALARM — 10:55 11-27-02
SSWT
That display indicates that on 11/27/02 at 10:55 the system Supply W ater Temperature sensor went into an alarm condition.
The user can view other stored alarms by pressing the up and down arrows. The five most recent alarms are stored.
CLEAR
To check system
STAT
ENTER
STAT
If the controller is indicating
HIST
ENTER
Configure the Custom Programming Selec­tions
perform the following procedure:
1. Press 37 . The LID display will show:
2. Press . The LID display will show:
3. Press if the display indicates “No Data.” Press
4. Press 1 and then to change to variable speed
5. Use the down and up arrows to select the other configura-
To configure the custom programming selections,
Custom Program
Global Dictionary AQUAZONE
then press . Press again.
The LID display should now show: PUMPS 0=ON/OFF, 1 = VFD
0.00
pumping (if required).
tion parameters as required. See the Configuration section for an explanation of the configuration parameters.
EXPN/EDIT ENTER
ENTER
16
Set the Aquazone System Control Panel
-
Controller Address
Aquazone System Control panel controller, perform the following procedure:
1. Press 7 and then . Press and then EXPN/EDIT
.
2. Type in the CCN element number and press .
3. Press the button. Type in the CCN bus number and
press .
ENTER
Log Off from Controller
zone System Control panel controller Press 3 and then . Press . Press the button and then press 1. Press
ENTER
ENTER
to log off.
LID Operation
CCN operator interface that gives the user the capability to view and modify all configuration and service data for the Aquazone System Control Panel Controller. The LID also gives the user the capability to override all point display and maintenance data.
MENU STRUCTURE — The LID operates on a hierarchy of four levels (menus).
The top level contains the LID’s major functions. Each function has a corresponding key on the LID. For an explana­tion of each function key, refer to Table 7.
The second level separates the major functions (items) into types with corresponding type numbers that can be used for quick access.
The third level gives the user the capability t o access each occurrence of an item. For example, the application may require two DO — Analog Comparison algorithms. Thus, the Aquazone System Control Panel Controller would have two occurrences of the DO — Analog Comparison algorithm.
The fourth level gives the user the capability to access main­tenance and configuration data associated with the selected occurrence of the item.
Table 7 LID Function Keys
To set the address of the
SRVC ENTER
ENTER
To log off from the Aqua-
SET
The Local Interface Device (LID) is a
DEFAULT SC RE EN — Figure 10 shows a LID. This screen provides the user with the 24-character controller name and the controller’s current time, date, and alarm status. This screen appears when the LID is powered up and communicating with the Aquazone System Control Panel Controller or there is no keyboard activity for10 minutes.
KEYPAD AND DISPLAY — The LID consists of a keypad with 8 function keys, 4 operative keys, 12 numeric keys (0 to 9, ., and -) and a two-line, alphanumeric l iquid crystal display (LCD). Each line on the LCD can display up to 24 characters. See Fig. 10.
T able 8 below defines t he purpose of the LID’s operative keys.
Table 8 Operative Keys
OPERATIVE
KEYS
CLEAR
ENTER
Clear performs three operations:
Cancels a data entry before the user presses Enter, thus leaving the current value unchanged.
Returns a forced point to automatic control.
Redisplays the previous menu level.
Enter performs two operations:
Selects the displayed item, thus displaying either its maintenance or configuration data, depending on whether the user is in the Status mode or the Edit mode.
Accepts the value entered in a configuration decision as new configuration data or as a forc e.
Down arrow displays the next configured item or decision. When the last configured item or decision is displayed, the LID re-displays the first configured item or decision. For example, when the user presses the down arrow key while viewing the last configuration decision of an algorithm, the LID re-displays the first configuration decision.
Up arrow Displays the previous configured item or decision.
USE
Table 9 below defines the purpose of the LID’s numeric keys.
Table 9 Numeric Keys
OPERATIVE
KEYS
LEGEND
AO DO
Analog Output Digital Output
USE
Status gives access to maintenance values and configuration data for points.
Alarm gives access to maintenance and configuration data for alarms.
History gives access to maintenance and configuration data for history system functions.
Service gives access to maintenance and configuration data for service system functions.
Setup gives access to configuration data for setup system functions.
Schedule gives access to maintenance and configuration data for schedules.
Algorithm gives access to maintenance and configuration data for AO, DO, and global algorithms. It also gives access to BEST custom programs.
Edit gives the capability to switch from Status mode to Edit (configuration) mode for the selected item. (EXPN is not used in conjunction with the Aquazone System Control Panel Controller.)
++
OPERATIVE
KEYS
Numeric keys
Performs two operations:
Separates items, such as an algorithm from its occurrence or hours from minutes.
Serves as a decimal point in numeric values.
Performs two operations:
Negates the value of numeric keys.
Clears current data entry value any time it is
not the first key pressed during the data entry sequence.
USE
VIEWING MODES — The user can view items in either the Status (maintenance) mode or the Edit (configuration) mode.
Status Mode
— When the user first powers up the LID, it displays the Aquazone System Control Panel Controller items in the Status (maintenance) mode. The user may view the current value or status of an item in the Sta tus mode without actually logging on to the Aquazone System Control Panel Controller. Knowing the current values or status of items can be useful when troubleshooting. For example, the user could determine if a point was forced.
NOTE: Not all items have maintenance data. If the item you select does not have maintenance data, the LID will display “No maintenance.”
17
EXPN/EDIT
6
EXPN/EDIT
FUNCTION KEYS
STAT
SET
EXPN
EDIT
SCHD
3
2
1
5
4
6
TEST
SRVC
ALRM
HIST ALGO
FUNCTION KEYS
OPERATIVE KEYS
7
NUMERIC KEYS
Fig. 10 Typical LID Device
Access Items in the Status Mode
— The user can access
maintenance data in the Status mode in two ways:
Pressing the appropriate function key (i.e., )
ALRM once to access a category (i.e., alarms) and then continu­ing to press that key ( ) to scroll thr ough all the
ALRM items in that category (i.e., Limit Alarm, Setpoint Alarm, Discrete Alarm, First Out Alarm, Runtime Alarm, and Number of Starts Alarm). Press
ENTER
display the first maintenance decision.
Scrolling by repeatedly pressing the function key,
NOTE: displays the name of all the items in that category, whether or not they are actually configured.
the up or down arrow,
displays only the configured items
Scrolling by pressing
within that category.
Pressing the appropriate LID numeric key (i.e., 2) and the appropriate function key (i.e., ) to directly
ALRM access an item without having to scroll through all the items in that category. Press to display the first
ENTER
maintenance decision.
Edit Mode
— Because the LID first displays items in the Status mode when it is powered up, the user must log on to the connected Aquazone™ System Control Panel Controller and press the key to switch to the Edit mode.
EXPN/EDIT
While in the Edit mode, the user ca n cha nge the configura­tion of items. For example, the user could change the value of an algorithm’s configuration decision.
NOTE: Not all items have configuration data. If the item selected does not have configuration data, pressing the
EXPN/EDIT
key will have no effect. The LID will display
“No configuration.”
8
9
.
0
Access Items in the Edit Mode
CLEAR
ENTER
OPERATIVE KEYS
— The two ways to access items in the Edit mode are th e same as in the Status mode, except for an additional step — pressing the key .
EXPN/EDIT
The user can access configuration data in the Edit mode in
two ways:
Pressing the appropriate function key (i.e., ) once
to access a category (i.e., ala rms), pressing
to
and then continuing to press that key ( ) to scroll
ALRM
EXPN/EDIT
ALRM through all the items in that category (i.e., Limit Alarm, Setpoint Alarm, Discrete Alarm, First Out Alarm, Runtime Alarm, and Number of Starts Alar m ) .
Scrolling by repeatedly pressing the function key,
NOTE: displays the name of all the items in that category, whether or not they are actually configured.
the up or down arrow,
displays only the configured items
Scrolling by pressing
within that category.
Pressing the appropriate LID numeric key (i.e., 2), the appropriate function key (i.e., ), and
ALRM
to directly access an item without having
to scroll through all the items in that category.
QUICK ACCESS IN EITHER STATUS OR EDIT MODE — Use T able 10 on next page as a reference to directly
access Aquazone System Control Panel Controller items using a LID in either the Status or Edit modes. For example, to access maintenance data for the AO — Heating VAV algorithm, press
, , and . To access configuration data for
ALGO ENTER
the AO — Heating VAV algorithm, press , ,
, and
ENTER
.
If the database consisted of two
6 AL G O
AO — Heating VAV algorithms, to access the second one, press ,
ENTER
(decimal),
6 . 2 ALGO EXPN/EDIT
, , , and
.
18
Table 10 Quick Access Chart
LID
NUM.
KEY
1 AOAdaptive Control Hardware Points Alarm History Function Definition Limit Set Clock Occupancy 2 AOCooling CV Software Points Analog Point Trace Channel Definition Setpoint Real Time Clock Setpoint 3 AOCooling VAV Temperature Input Discrete Point Trace System Definition Discrete Controller Password Holiday 4 AOFan Tracking Milliamp Input Consumable Channel Setpoint Definition First out N/A S/W Setpoint 5 AOHeating CV Custom Milliamp Input Internal Consumable Database Control Runtime N/A Network Time 6 AOHeating VAV Voltage Input Runtime Channel Comfort Controller # of starts N/A N/A 7 AOHumidity Control Custom Voltage Input N/A CCN Control N/A N/A N/A 8 AOMixed Air CV w/IAQ Sensed Discrete Input N/A LID Preferences N/A N/A N/A
9 AOMixed Air VAV w/IAQ Latched Discrete Input N/A N/A N/A N/A N/A 10 AOPermissive Interlock Pulsed Discrete Input N/A N/A N/A N/A N/A 11 AOReset Milliamp Output N/A N/A N/A N/A N/A 12 AOShared Transducer Custom Milliamp Output N/A N/A N/A N/A N/A 13 AOStatic Pressure Voltage Output N/A N/A N/A N/A N/A 14 DOAnalog Custom Voltage Output N/A N/A N/A N/A N/A 15 DODX-Staging VAV Discrete Output N/A N/A N/A N/A N/A 16 DOElectric Heat CV Stepper Motor Output N/A N/A N/A N/A N/A 17 DOElectric Heat VAV Discrete Software Point N/A N/A N/A N/A N/A 18 DOEnthalpy Comparison Analog Software Point N/A N/A N/A N/A N/A 19 DOInterlock Network Data Out N/A N/A N/A N/A N/A 20 DOLighting Control Network Data In N/A N/A N/A N/A N/A 21 DOPermissive Interlock N/A N/A N/A N/A N/A N/A 22 DOPump Control N/A N/A N/A N/A N/A N/A 23 DOProp Thermo N/A N/A N/A N/A N/A N/A 24 DOProp Ther mo 2 Pipe N/A N/A N/A N/A N/A N/A 25 DOProp Ther mo 4 Pipe N/A N/A N/A N/A N/A N/A 26 DOStaged Thermostat N/A N/A N/A N/A N/A N/A 27 DOStaging Control N/A N/A N/A N/A N/A N/A 28 DOTime Clock N/A N/A N/A N/A N/A N/A 29 DOTime Clock w/Check N/A N/A N/A N/A N/A N/A 30 AOSS Schedule N/A N/A N/A N/A N/A N/A 31 Network Broadcast N/A N/A N/A N/A N/A N/A 32 Linkage/AOSS Schedule N/A N/A N/A N/A N/A N/A 33 NTFC w/Enthalpy Check N/A N/A N/A N/A N/A N/A 34 Sensor Group N/A N/A N/A N/A N/A N/A 35 WSM Air Source N/A N/A N/A N/A N/A N/A 36 WSM Cool Source N/A N/A N/A N/A N/A N/A 37 Custom Program N/A N/A N/A N/A N/A N/A
LEGEND NOTES:
AO Analog Output AOSS Adaptive Optimal Start/Stop CV Constant Volume DO Digital Output IAQ Indoor Air Quality N/A Not Available NTFC Nighttime Free Cooling VAV Variable Air Volume WSM Water System Manager
Algorithms
(ALGO)
Status (STAT)
LID FUNCTION KEYS
History
(HIST)
1. If in the Edit mode and wish to switch to the Status mode, press
or press
2. Not all available selections will have items to select in sublevels.
Service (SRVC)
EXPN/EDIT
Alarm
(ALRM)
again.
Setup
(SET)
Schedules
(SCHD)
CLEAR
19
Sequence of Operation
HEAT RE JECTIO N — When the system pumps are operat ­ing and there is flow to the system, heat rejection control compares the system supply water temperature to the hi gh set point in the system loop temperature set points.
If the system supply water temperature approaches the high set point, the controller commands the heat rejection outputs to hold the system supply water temperature as close as possible to the high set point.
If the system return water temperature drops below the system high water temperature set point minus a hysteresis value the heat rejection, outputs are disabled.
When the cooling tower output control type is set to “variable,” the heat rejection outputs are calculated using a PID calculation based on the system high temperature water set point. Both outputs will modulate together.
When the heat rejection control type is set to “staged,” the outputs will be modulated in a lead/lag configuration. The modulating signal of the lead output will control a transducer of two or four stages.
When the lead output is at 100% and the set point is not being maintained, the lag output will be modulated to produc e staging from another two or four stage output transducer.
The value output by each analog output is determined by a PID calculation of leaving water temperature versus the system high leaving water temperature set point.
In the event that the system high water temperature set point cannot be maintained and is exceeded by a defined Hysteresis, the heat rejection outputs will go to maximum output, the system water source heat pumps will stop cooling, and the system pumps will circulate water until the system tempera­tures are returned to the normal range. System cooling will then be allowed to continue.
HEAT ADDITI ON — When the system pumps are operating and there is flow to the system, boiler control compares the system supply water temperature to the low set point in t he system loop temperature set points.
If the system supply water temperature approaches the low set point, then the controller commands the boile r outputs to hold the system supply water temperature as close as possible to the low set point .
If the system return water temperature rises above the system low water temperature set point plus a Hysteresis value, the boiler outputs are disabled.
When the boiler output control type is “variable,” the boiler outputs will be calculated using a PID calculation based on the system low temperature water set point. Both outputs will modulate together.
When the boiler control type is set to “staged,” the outputs are modulated in a lead lag configuration. The modulating signal of the lead output controls a transducer (two or four stages).
When the lead output is at 100% and the set point is not being maintained, the lag output modulates to produce staging from another two or four stage output transducer.
The value output by each analog output i s determined by a PID calculation of leaving water temperature versus the system low leaving wa ter temp eratu re se t poi nt.
In the event that the system low water temperature set point cannot be maintained and is exceeded by a defined Hysteresis, the boiler outputs will go to maximum output, the system water source heat pumps will stop heating, and the system pumps will circulate water until the system temperatures are returned to the normal range. System heating will then be allowed to continue.
WATER CIR CULATION — When operational mode is de­termined by one of the 18 occupancy schedules, one of the 18 network or global schedules, or occupancy overrides, then the system pumps are put in operational mode. Also, if one of t he system enable outputs is forced on, then the system pumps are put in operational mode.
If the remote occupancy input is detected, then the pumps are put in operational mode and all 18 schedules overridden to on. This energizes all 18 system enable outputs.
The pump control type is configured as either variable flow or constant flow . When the pumps are in operational mode, the pump speed output values are determined in one of two ways:
1. In constant flow mode, the desired output (one or two) is ramped to 100% to turn the pumps on in a lead/lag fashion, based on run time.
2. In variable flow mode, both outputs are determined by a Proportional Integral Derivative (PID) calculation, which controls the system pressure set point.
Whenever the runtime of the lead pump exceeds the runtime of the lag pump by 50 hours or more, then the pump with the lesser runtime will become the lead pump.
If the lead pump output is at 100% and the loop water flow input detects no flow, then the lag pump will be put to 100% to start the lag pump. Both outputs will stay at 100% as an indica­tor that the lead pump did not start.
At each subsequent start-up, the lead pump will be tried again. If both pumps are commanded to 100% and no flow is detected, then the pumps will be forced off. To restart the sys­tem, a pump must be energized manually or the flow switch must be overridden to indicate flow. The lead pump will start if there is a demand for system circulation.
In the event that the pumps have been commanded to provide water flow but either the flow switch does not indicate flow or the differential pressure sensor does not indicate pres­sure is present, then the controller assumes that the pumps have failed and commands the water source heat pumps to turn off cooling or heat. The system fans will continue to circulate the air.
In the event of a system shutdown command, the controller commands the water source heat pumps to turn off all cooling and heat sources and circulating fans.
20
CONFIGURATION
The Aquazone™ System Control Panel contains a Comfort Controller 6400 programmed using the standard algorithms and enhanced by BEST++™ custom programming. The BEST++ Templates for some of the programs have been removed to prevent field alterations. For other programs, the templates are included to allow for jobsite customization. For basic information about the algorithms please refer to the Comfort Controller Overview and Configuration manual (808-891). Default configurations are listed later in this section.
Hardware Points
T able 1 1 and 12.
Table 11 Hardware Points 1 to 32 (HWP01-32)
DESCRIPTION VALUE NAME
Loop Water Flow
System Supply Water Temp
System Return Water Temp
System Diff. Pressure
Remote Occupancy Mode
System
Override Input Zone 1
Override Input Zone 2
Pump Number 1 Speed
Pump Number 2 Speed
Cooling Tower 1 Level
Cooling Tower 2 Level
Boiler 1 Level
Boiler 2 Level
System for Zone 1
System for Zone 2
Override Input Zone 3
Override Input Zone 4
Override Input Zone 5
Override Input Zone 6
Override Input Zone 7
Override Input Zone 8
Override Input Zone 9
Override Input Zone 10
System for Zone 3
System for Zone 4
System for Zone 5
System for Zone 6
System for Zone 7
System for Zone 8
System for Zone 9
System for Zone 10
Table 12 Hardware Points 33 to 64 (HWP33-64)
DESCRIPTION VALUE NAME
Override Input Zone 11
Override Input Zone 12
Override Input Zone 13
Override Input Zone 14
Override Input Zone 15
Override Input Zone 16
Override Input Zone 17
Override Input Zone 18
System for Zone 11
System for Zone 12
System for Zone 13
System for Zone 14
System for Zone 15
System for Zone 16
System for Zone 17
System for Zone 18
The hardware points are shown in
Ye s F L O W
60.3 dF SSWT
51.0 dF SRWT
0.00 PSIG SDP Off RMTOCC Enable ALLSYS On OVRIZ1 On OVRIZ2
100.0% PUMP1
0.0% PUMP2
0.0% CTL1
0.0% CTL2
83.2% BLRL1
0.0% BLRL2 Enable SYSZ1 Enable SYSZ2 Off OVRIZ3 Off OVRIZ4 Off OVRIZ5 Off OVRIZ6 Off OVRIZ7 Off OVRIZ8 Off OVRIZ9 Off OVRIZ10 Disable SYSZ3 Disable SYSZ4 Disable SYSZ5 Disable SYSZ6 Disable SYSZ7 Disable SYSZ8 Disable SYSZ9 Disable SYSZ10
Off OVRIZ11 Off OVRIZ12 Off OVRIZ13 Off OVRIZ14 Off OVRIZ15 Off OVRIZ16 Off OVRIZ17 Off OVRIZ18 Disable SYSZ11 Disable SYSZ12 Disable SYSZ13 Disable SYSZ14 Disable SYSZ15 Disable SYSZ16 Disable SYSZ17 Disable SYSZ18
LOOP WATE R FLOW SWITCH — This discrete input is used to provide a signal that one of the loop water pumps is on. If both pumps have been commanded to run and no water flow is detected, then the system water source heat pumps will run in the fan only mode for DDC (Direct Digital Control) coordinated heat pump controllers, while the system relays for thermostat systems will be turned of f.
Loop W ater Flow Switch:
Display Units Discrete ASCII Default V alue No Display Range Yes/No Network Access Read/Write
SYSTEM SUPPLY WATER TEMPERATURE — The sys­tem supply water temperature is the temperature of the wat er being pumped to the system of water source heat pumps. The temperature is measured by a 10K Thermistor (MCI). This output and sensor is required for proper function of t he loop and heat pumps.
System Supply W ater Temperature:
Display Units degrees F (degrees C) Default Value –40.0 Display Range –40.0-245.0 Network Access Read/Write
SYSTEM RETURN WATER TEMPERATURE — The sys­tem return wate r temperature is the temperatu re of the water returning from the system of water source heat pumps. This temperature measured by a 10K Thermistor (MCI). This output and sensor is provided for informational purpose and indicates the average load caused by the normal operation of the heat pumps.
System Return Water Temperature:
Display Units degrees F (degrees C) Default Value –40.0 Display Range –40.0-245.0 Network Access Read/Write
SYSTEM WATER PRESSURE — This sensor is used to measure the pressure of the supply water to the system of water source heat pumps. This sensor should be located
2
/3 of the way down the supply water distribution piping or in a location that will provide a good reference of the supply water pressure. This sensor is used to control the speed of variable frequency drives pumping water to the water source heat pumps. Each water source heat pump may be equipped with a two position isolation valve that may be closed when the compressors are not energized in order to reduce the quantity of water being pumped through the system.
System Water Pressure: Display Units in. wg
Default V alue 0.0 Display Range 0.0-5.0 Network Access Read/Write
21
REMOTE O CCUPANCY — This input is used to provide an external clock input to enable all 18 of the local schedules, start the loop pumps, and enable loop temperature control.
Remote Occupancy:
Display Units Discrete ASCII Default Value Disable Display Range Enable/Disable Network Access Read/Write
SYSTEM/SHUT DOWN — This discrete input is used to provide a signal from the fire alarm panel that will shut dow n the Aquazone™ System Control Panel, disable the system zone relays, and send out a command to shut down the water source heat pumps.
System/Shut Down:
Display Units Discrete ASCII Default Value Enable Display Range EmStop/Enable Network Access Read/Write
OVERRID E INPUT FOR ZO NE 1- 18 — These inputs are used to sense an external dry contact that override/enable each of the 18 local schedules, start the loop pumps, and enable loop temperature control.
Override Input for Zone 1-18
Display Units Discrete ASCII Default Value Disable Display Range Enable/Disable Network Access Read/Write
PUMP NUMBER 1 — When the Aquazone System Control Panel is configured for variable speed pumping, this point displays the speed of Pump 1, as determined by a PID loop set to control supply water pressure. When the Aquazone system control panel is configured for constant flow this point will display 0% when the pump is OFF and 100% when the pump is on.
Pump Number 1
Display Units % Default V alue 0 Display range 0-100 Network Access Read/Write
PUMP NUMBER 2 — When the Aquazone system control panel is configured for variable speed pumping, this point displays the speed of Pump 2, as determined by a PID loop set to control supply water pressure. When the Aquazone system control panel is configured for constant flow this point will display 0% when the pump is OFF and 100% when the pump is on.
Pump Number 2
Display Units % Default V alue 0 Display range 0-100 Network Access Read/Write
NUMBER O F STAGES — Table 13 is used with the follow­ing four points to determine the number of stages that should be active for the percent output displayed and the hardware installed with the Aquazone system control panel. When the outputs are configured for staging the second output will ramp up when the first output has reached 100%. While the second output is controlling the temperature the first will be held at 100%. When the second output ramps down to zero percent the first output will resume temperature control.
Table 13 Total Number of Stages
TOTAL NUMBER OF STAGES 2
Output Displayed
Stage Activated
Stage Deactivated
TOTAL NUMBER OF STAGES 4
Output Displayed
Stage Activated
Stage Deactivated
20 25 45 50 70 75 95 100
1 2 3 4
1 2 3 4
45 50 95 100
1 2
1 2
COOLING TOWER 1 SPEED/LEVEL — When the Aqua­zone system control panel is configured for variable speed cooling tower control, this point displays the speed of tower fan 1. When the Aquazone system control panel is equi pped for staged output, this point displays the percent of stages commanded. The actual number of stages active will be determined by the staging cards ordered with the Aquazone system control panel. See Table 13. The value displayed is determined by a PID (proportional/integral/derivative) loop set to control the supply-water temperature at the Occupied high set point.
Cooling T ower 1 Speed/Level
Display Units % Default V alue 0 Display range 0-100 Network Access Read/Write
COOLING TOWER 2 SPEED/LEVEL — When the Aqua­zone system control panel is configured for variable speed cooling tower control, this point displays the speed of tower fan
2. When the Aquazone system control panel is equipped for staged output, this point displays the percent of stages com­manded. The actual number of stages active will be determined by the staging cards ordered with the Aquazone system control panel. See Table 13. The value displayed is determined by a PID loop set to control the supply water temperature at the Occupied high set point.
Cooling T ower 2 Speed/Level
Display Units % Default V alue 0 Display range 0-100 Network Access Read/Write
HEAT SOURCE 1 SPEED/LEVEL — When the Aquazone system control panel is configured for modulating heat source, this point displays the percent open or percent heat capacity re­quested. When the Aquazone system control panel is equipped for staged output, this point displays the percent of stages com­manded. The actual number of stages active will be determined by the staging cards ordered with the Aquazone system control panel. See Table 13. The value displayed is determined by a PID loop set to control the supply water temperature at the Oc­cupied Low set point.
Heat Source 1 Speed/Level
Display Units % Default V alue 0 Display range 0-100 Network Access Read/Write
22
HEAT SOURCE 2 SPEED/LEVEL — When the Aquazone™ system control panel is configured for modulating heat source, this point displays the percent open or percent heat capacity requested. When the Aquazone system control panel is equipped for staged output, this point displays the percent of stages commanded. The actual number of stages active will be determined by the staging cards ordered with the Aquazone system control panel. See Table 8. The value displayed is determined by a PID loop set to control the supply water temperature at the Occupied Low set point.
Heat Source 2 Speed/Level
Display Units % Default V alue 0 Display range 0 100 Network Access Read/Write
SYSTEM FOR ZONE 1-1 8 — These Outputs are is used to enable a group of thermostats by energizing and deenergizing the associ at ed zon e r ela ys .
System for Zone 1-18
Display Units Discrete ASCII Default V alue Off Display Range On/Off Network Access Read/Write
Software Points
The software points are shown in
T able 14.
Table 14 Software Points 65 to 96 (SWP65-96)
DESCRIPTION VALUE NAME
Outside Air Temperature Lead Pump Const. Flow Variable Speed Pumping Cooling Tower 1 Cooling Tower 2 Heat Control 1 Heat Control 2 Pump 1 Run Time Pump 2 Run Time
94.94 dF OAT
1.00 LEAD Disable VSPC Disable COOLT1 Disable COOLT2 Enable HEATC1 Disable HEATC2
253.00 HOURS PUMP1RT
250.00 HOURS PUMP2RT
OUTSIDE AIR TEMPERATURE — This software point is included to receive an Outside Air Broadcast. If the system is set up with Outside Air Broadcast, a control force will be displayed on the OAT point of all system controllers. For systems with factory-installed PremierLink™ controllers, the individual unit leaving water temperature sensors are connected to the OAT point. When OAT broadcast is enabled, the leaving water temperature sensors connected to the PremierLink controllers may be displayed temporarily by removing the Outside Air Broadcast force. The Outside Air Broadcast will be refreshed the next time the outside-air temperature is broadcast.
Outside Air Temperature:
Display Units degrees F (degrees C) Default Value –40.0 Display Range –40.0-245.0 Network Access Read/Write
LEAD PUMP CONSTANT FLOW — When the Aquazone system control panel is configured for constant flow, this point displays the current lead pump. This point may be forced to keep the lead pump the same for more than the maximum hours difference required for pump rotation. When the pump runtime hours difference becomes greater than the maximum number configured the pump runtime hours for both pumps will reset to zero.
For example, the default maximum hours difference for rotation is 50 hours. If the Lead Pump was forced to 2, so that pump 2 is the lead pump, then the pump 2 runtime hours will accumulate until the difference between the pump 1 and pump 2 runtime hours becomes greater than 50. The both will reset to zero and pump 2 will start accumulating again.
Lead Pump Constant Flow:
Display Units Numeric Default V alue 1 Display Range 1 or 2 Network Access Read/Write
VARIABLE SPEED PUMPING — If the Aquazone system control panel is configured for variable speed pumping, this point will indicate when the pumps are requested to be running.
Variable Speed Pumping:
Display Units Discrete ASCII Default V alue Disable Display Range Enable/Disable Network Access Read/Write
COOLING TOW ER 1 — This point indicates when the first cooling output is requested to control loop temperature.
Cooling T ower 1
Display Units Discrete ASCII Default V alue Disable Display Range Enable/Disable Network Access Read/Write
COOLING TOWER 2 — This point indicates w hen the sec­ond cooling output is requested to control loop temperature.
Cooling T ower 2
Display Units Discrete ASCII Default V alue Disable Display Range Enable/Disable Network Access Read/Write
HEAT CONTROL 1 — This point indicates when the first heat output is requested to control loop temperature.
Heat Control 1
Display Units Discrete ASCII Default V alue Disable Display Range Enable/Disable Network Access Read/Write
HEAT CONTROL 2 — This point indicates when t h e second heat output is requested to control loop temperature.
Heat Control 2
Display Units Discrete ASCII Default V alue Disable Display Range Enable/Disable Network Access Read/Write
PUMP 1 RUN TIM E — This point displays the number of hours that the pump has run. When the maximum number of hours is exceeded (9999 hours), both pumps run time hours will reset to 0.
Pump 1 Run Time
Display Units Numeric Default V alue 0 Display Range 0 to 9999 Network Access Read/Write
23
PUMP 2 RUN TIME — This point displays the number of hours that the pump has run. When the maximum number of hours is exceeded (9999 hours), both pumps run time hours will reset to 0.
Pump 2 Run Time
Display Units Numeric Default V alue 0 Display Range 0 to 9999 Network Access Read/Write
Loop Supply Water Set Point
The low set point is the low limit the supply water temperature may drop down to before the heat source will be activated to m aintain the Loop Supply water temperature. The high set point is the high limit the supply water may rise to before the cooling source w ill be activated to maintain the loop supply water temperature. See Table 15. Set points can also be modified with slide bars in the ComfortVIEW™ software. See Fig. 11.
Table 15 Loop Supply Water (SETPT01)
DESCRIPTION VALUE NAME
Occupied Lo Setpoint Occupied Hi Setpoint Unoccupied Lo Setpoint Unoccupied Hi Setpoint
60.00 df OccLow
90.00 df OccHgh
60.00 df UnOccLow
90.00 df UnOccHgh
Occupied High:
Configuration Units PSIG Configuration Range –9999.9 to 9999.9 Default Value 10.0
Unoccupied Low:
Configuration Units PSIG Configuration Range –9999.9 to 9999.9 Default Value 10.0
Unoccupied High:
Configuration Units PSIG Configuration Range –9999.9 to 9999.9 Default Value 10.0
Global Dictionary
The Global Dictionary table is
shown in T able 17.
Table 17 Global Dictionary (AQUAMASC)
DESCRIPTION VALUE NAME
PUMPS 0=ON/OFF,1=VFD Pump Rotation Hours TOWERS 0=STAGED,1=VFD HEAT 0=STAGED,1=MOD/VFD Sched Bcst 0=N,1=Y
0.00 PUMP_CFG
50.00 ROT_TIME
0.00 COOL_CFG
0.00 HEAT_CFG
0.00 GLOBAL
Occupied Low:
Configuration Units degrees F (degrees C) Configuration Range –40.0 to 245.0 Default Value 60.0
Occupied High:
Configuration Units degrees F (degrees C) Configuration Range –40.0 to 245.0 Default Value 90.0
Unoccupied Low:
Configuration Units degrees F (degrees C) Configuration Range –40.0 to 245.0 Default Value 60.0
Unoccupied High:
Configuration Units degrees F (degrees C) Configuration Range –40.0 to 245.0 Default Value 90.0
System Pressure Set Point
This set point defines the system pressure that the variable speed pumps will operate when the Aquazone™ system control panel is configured for variable speed pumping. See Table 16. Set points can also be modified with slide bars in the ComfortVIEW softwa re. See Fig. 12.
Table 16 System Pressure (SETPT02)
DESCRIPTION VALUE NAME
Occupied Lo Setpoint Occupied Hi Setpoint Unoccupied Lo Setpoint Unoccupied Hi Setpoint
10.00 PSIG OccLow
10.00 PSIG OccHgh
10.00 PSIG UnOccLow
10.00 PSIG UnOccHgh
Occupied Low:
Configuration Units PSIG Configuration Range –9999.9 to 9999.9 Default Value 10.0
PUMP CONTRO L TYPE — This configuration determines how the pump outputs will be controlled. If the pump relays were ordered with the Aquazone system control panel, then the pump control type should be set to 0. If the pump outputs will control variable speed pumps, then the configuration should be set to 1. When variable speed control is selected, both outputs will control simultaneously.
Pump Control T ype:
Configuration Units None Configuration Range 0 or 1 Default Value 0
PUMP ROTATION HOURS — When the pump control type is set to 0 (on/off), this configuration is used to set the maxi­mum number of hours the lead pump may accumulate beyond the numbers of hours accumulated for the lag pump. When this difference in hours is reached, the lead pump will change to the pump with the lesser number of accumulated run hours.
Pump Rotation Hours:
Configuration Units HOURS Configuration Range 0 to 9999 Default Value 50.0
TOWER/COOLING SOURCE CONTROL TYPE — This configuration determines how the tower outputs will be con­trolled. If panels were ordered with the stage output tr ansducers, then tower control type should be set to 0. If the tower outputs will control variable speed tower fans, then the configuration should be set to 1.
Variable speed configuration will control both outputs si-
multaneously.
T ower/Cooling Source Control Type:
Configuration Units None Configuration Range 0 or 1 Default V alue 0
24
Fig. 11 Loop Supply Water Set Point Screen
Fig. 12 System Pressure Set Point Screen
BOILER/HEAT SOURCE CONTROL TYPE — This con­figuration determines how the tower outputs will be controlled. If panels were ordered with the stage output transducers, then tower control type should be set to 0. If the tower outputs will control variable speed tower fans, then the configuration should be set to 1.
Variable speed configuration will control both outputs
simultaneous ly.
Boiler/Heat Source Control Type:
Configuration Units None Configuration Range 0 or 1 Default Value 0
GLOBAL SCHEDULE BROADCAST — If des i red, the schedules 1 through 18 in the Aquazone™ system control panel may be reconfigured to be schedules 65 through 82 (so that they may be used as global schedules). If this is done, this configuration must be set to 1. Local inputs for overriding zones 1 to 18 or the remote occupancy input will then affect the global schedules 65 through 82. In this condition local override of individual PremierLink™ controllers will not occur since the comfort controller does not respond to the command from any PremierLink controller to override a global schedule. It is recommended to allow the PremierLink controllers to broad­cast global schedules.
25
The loop controller comes pre-configured with local schedules 1 through 18. It is also pre-configured with network schedules 65 through 82 in order to receive global schedules broadcast from PremierLink™ controllers or other networked controllers. See Network Time Schedule section. This is the recommended method for using global schedu les since a PremierLink controller (when set up to broadcast a global schedule) will respond to a schedule override request from another PremierLink controller that it is broadcasting the global schedule. This allows all PremierLink controllers following the same global schedule to enter occupancy override as a group.
Global Schedule Broadcast:
Configuration Units None Configuration Range 0 or 1 Default Value 0
Heat Pump Default Configuration
The heat pump
default configuration table is shown in Table 18.
Table 18 Pump 1 Spee
DESCRIPTION VALUE NAME
Analog Output Point
Status Point
Time Schedule
Setpoint Schedule
Reset Point
Reset
Start Reset Value
Stop Reset Value Control Point PID_Master_Loop
Proportional Gain
Integral Gain
Derivative Gain
Disabled Output Value
Minimum Output Value
Maximum Output Value
Starting Value
Block Iteration Rate Powe r on Delay
*User configured.
Cool Source Default Configuration
d (
PUMP_1)
PUMP1 Name* VSPC Name* OCCPC00 Name* SETPT02 Name* TEMP_I00 Name*
–40.00 PSIG StrtRst
245.00 PSIG StopRst SDP Name*
2.0 KP
1.0 KI
0.0 KD
0.0% DsblOut
10.0% MinOut
100.0% MaxOut
35.0% StartVal 10 sec BlkRate
0 sec PowerUp
The cool
source default configuration table is shown in Table 19.
Table 19 Cooling Tower 1 (COOLT_1)
DESCRIPTION VALUE NAME
Analog Output Point Status Point Time Schedule Setpoint Schedule Reset Point Reset
Start Reset Value
Stop Reset Value Control Point PID_Master_Loop
Proportional Gain
Integral Gain
Derivative Gain
Disabled Output Value
Minimum Output Value
Maximum Output Value
Starting Value
Block Iteration Rate Power on Delay
*User configured.
Heat Source Default Configuration
CTL1 Name* COOLT1 Name* OCCPC00 Name* SETPT01 Name* SRWT Name*
40.00 dF StrtRst39.00 dF StopRst
SSWT Name*
3.0 KP1.5 KI
0.0 KD
0.0% DsblOut
0.0% MinOut
100.0% MaxOut
0.0% StartVal 10 sec BlkRate
0 sec PowerUp
The heat
source default configuration table is shown in Table 20.
Table 20 Heating Control 1 (HEAT_1)
DESCRIPTION VALUE NAME
Analog Output Point Status Point Time Schedule Setpoint Schedule Reset Point Reset
Start Reset Value
Stop Reset Value Control Point PID_Master_Loop
Proportional Gain
Integral Gain
Derivative Gain
Disabled Output Value
Minimum Output Value
Maximum Output Value
Starting Value
Block Iteration Rate Power on Delay
*User configured.
Occupancy Configuration Screen
BLRL1 Name* HEATC1 Name* OCCPC00 Name* SETPT01 Name* TEMP_I00 Name*
–40.00 dF StrtRst
245.00 dF StopRst SSWT Name*
3.0 KP
1.5 KI
0.0% KD
0.0% DsblOut
0.0% MinOut
100.0% MaxOut
0.0% StartVal 10 sec BlkRate
0 sec PowerUp
The Occu­pancy Configuration Screen is used to configure the occupancy schedule. See Table 21.
MANUAL OVERRIDE HOURS — The Manual Override Hours point is used to command a timed override by entering the number of hours the override will be in effect. If the occu­pancy schedule is occupied when this number is downloaded, the current occupancy period will be extended by the num ber of hours downloaded.
If the current occupancy period is unoccupied when the occupancy override is initiated, the mode w ill change to oc cu­pied for the duration of the number of hours downloaded. If the occupancy override is due to end after the start of the next occupancy period, the mode will transition from occupancy override to occupied without becoming unoccupied and the occupancy override timer will be reset.
An active occupancy override or a pending occupancy override may be canceled by downloading a zero to this configuration. Once a number other than zero has been down­loaded to this configuration, any subsequent downloads of any value other than zero will be ignored by the controller.
Manual Override Hours: Units hours
Range 0 to 4 Default V alue 0
OCCUPANCY SCHEDULE — For flexibility of scheduling, the occupancy programming is broken into eight separate peri­ods. For each period the schedule contains the following fields: Day of W eek, Occupied From, and Occupied T o.
DAY OF WEEK — The Day of Week configuration consists of eight fields corresponding to the seven days of the week and a holiday field in the following order: Monday, Tuesday, W ednesday, Thursday, Friday, Saturday, Sunday, Holiday.
It is displayed as:
M T W Th Fr Sa Su Hol 0 0 0 0 0 0 0 0
If a 1 is configured in the corresponding place for a certain day of the week, the related “Occupied from” and “O ccupied to” times for that period will take effect on that day of the week. If a 1 is placed in the holiday field, the related times will take effect on a day configured as a holiday. A zero means the schedule period will not apply to that day.
Day of week: Range 0 or 1
Default Values 11111111 for period 1,
00000000 for the rest of the periods
26
OCCUPIED FROM — This field is used to configure the hour and minute, in military time, that the mode for the PremierLink™ controller will switch to occupied.
Occupied From: Units Hours:Minutes
Range 00:00 to 24:00
(Minutes 00 to 59)
Default Value 00:00
OCCUPIED TO — This field is used to configure the hour and minute, in military time, that the mode for the PremierLink controller switches from occupied to unoccupied.
Occupied To: Units Hours:Minutes
Range 00:00 to 24:00
(Minutes 00 to 59)
Default Value 24:00
Table 21 Occupancy Schedule (OCCPC01)
DESCRIPTION VALUE NAME
Time Schedule Manual Override Hours Period 1: Day of Week Period 1: Occupied from Period 1: Occupied to Period 2: Day of Week Period 2: Occupied from Period 2: Occupied to Period 3: Day of Week Period 3: Occupied from Period 3: Occupied to Period 4: Day of Week Period 4: Occupied from Period 4: Occupied to Period 5: Day of Week Period 5: Occupied from Period 5: Occupied to Period 6: Day of Week Period 6: Occupied from Period 6: Occupied to Period 7: Day of Week Period 7: Occupied from Period 7: Occupied to Period 8: Day of Week Period 8: Occupied from Period 8: Occupied to Push Button Override Thermostat Override Time Delay Timed Override Duration Power on Delay
*User configured.
0 hours Ovrd
00000000 DOW1
00:00 Occ1 24:00 UnOcc1
00000000 DOW2
00:00 Occ2 24:00 UnOcc2
00000000 DOW3
00:00 Occ3 24:00 UnOcc3
00000000 DOW4
00:00 Occ4 24:00 UnOcc4
00000000 DOW5
00:00 Occ5 24:00 UnOcc5
00000000 DOW6
00:00 Occ6 24:00 UnOcc6
00000000 DOW7
00:00 Occ7 24:00 UnOcc7
00000000 DOW8
00:00 Occ8 24:00 UnOcc8
LATCHI00 Name*
TEMP_I00 Name* 5 min Value* 5 min Value* 0 sec PowerUp
Network Time Schedule
The network time schedule allows the occupancy schedule in another device on the CCN to control the Aquazone™ system control panel’s occupancy state.
Each time the occupancy schedule on the controlling device changes to occupied, the controlling device broadcasts an occupancy flag over the CCN. To receive an occupancy flag, a network time created. Up to 18 network time schedules are configured. The schedules are sequentially named OCCPC65E to OCCPC82E, however Service Tool or Building Supervisor software can be used to modify the names up to OCCPC99E.
Holiday Schedules
A Holiday schedule allows the user the capability to specify days of the year (holidays) on which the Aquazone system control panel will follow the holiday time schedule instead of the normal time schedule for that day. Holiday time schedules are normally used to program a weekday in unoccupied mode for the entire day since the building will be empty during a holiday.
There are 16 different holiday schedules that can be created. Holiday schedules can also last more than one day, as long as the days are consecutive.
Holiday schedules must be configured on the time and date broadcaster element on the CCN. If the Comfort Controller on the Aquazone system control panel is the broadcaster, it will send holiday status to all other system elements on the CCN. If the Comfort Controller is not the broadcaster, do not configure the holiday schedules for it, as they will not be used.
To configure a holiday schedule, ente r a “1” i n th e Holiday column of the Day of Week point of the Occupancy schedule.
27
Copyright 2003 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 5 a 5 a
PC 111 Catalog No. 535-00077 Printed in U.S.A. Form 50RLP-1SI Pg 28 1-03 Replaces: New
Loading...