Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or
other conditions which may cause personal injury or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The
qualified installer or agency must use factory-authorized kits or
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500077-01Printed in U.S.A.Form 50HQP-C1SIPg 111-10Replaces: New
Page 2
accessories when modifying this product. Refer to the
individual instructions packaged with the kits or accessories
when installing.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for brazing operations. Have fire
extinguisher available. Read these instructions thoroughly and
follow all warnings or cautions attached to the unit. Consult
local building codes and the National Electrical Code (NEC)
for special installation requirements.
Understand the signal words — DANGER, WARNING,
and CAUTION. DANGER identifies the most serious hazards
which will result in severe personal injury or death. WARNING signifies hazards that could result in personal injury or
death. CAUTION is used to identify unsafe practices, which
would result in minor personal injury or product and property
damage.
Recognize safety information. This is the safety-alert
symbol (). When you see this symbol on the unit and in
instructions or manuals, be alert to the potential for personal
injury.
WARNING
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work
is completed.
CAUTION
This system uses R-410A, which has higher pressures than
R-22 and other refrigerants. No other refrigerant may be
used in this system. Suction tubing design pressure is
3068 kPa and liquid tubing design pressure is 4522 kPa.
Failure to use gage set, hoses, and recovery systems
designed to handle R-410A refrigerant may result in personal injury and equipment damage. If unsure about equipment, consult the equipment manufacturer.
GENERAL
This Installation and Start-Up Instructions literature is for
Aquazone™ water source heat pump systems with Puron refrigerant.
Water source heat pumps (WSHPs) are single-package horizontally and vertically mounted units with electronic controls
designed for year-round cooling and heating.
IMPORTANT: The installation of water source heat pump
units and all associated components, parts, and accessories
which make up the installation shall be in accordance with
the regulations of ALL authorities having jurisdiction and
MUST conform to all applicable codes. It is the responsibility of the installing contractor to determine and comply
with ALL applicable codes and regulations.
INSTALLATION
Step 1 — Check Jobsite —
maintenance instructions are provided with each unit. Before
unit start-up, read all manuals and become familiar with the
unit and its operation. Thoroughly check out the system before
operation. Complete the inspections and instructions listed
below to prepare a unit for installation. See Table 1 for unit
physical data.
Horizontal units are designed for indoor installation only.
Be sure to allow adequate space around the unit for servicing.
Installation, operation and
See Fig. 1 for overall unit dimensions. Refer to Fig. 2 for an example of a typical horizontal installation.
CAUTION
To avoid equipment damage, do not use these units as a
source of heating or cooling during the construction process. The mechanical components and filters used in these
units quickly becomes clogged with construction dirt and
debris which may cause system damage.
Step 2 — Check Unit — Upon receipt of shipment at
the jobsite, carefully check the shipment against the bill of
lading. Make sure all units have been received. Inspect the carton or crating of each unit, and inspect each unit for damage.
Ensure the shipping company makes proper notation of any
shortages or damage on all copies of the freight bill. Concealed
damage not discovered during unloading must be reported to
the shipping company within 15 days of receipt of shipment.
NOTE: It is the responsibility of the purchaser to file all
necessary claims with the shipping company.
1. Verify unit is correct model for entering water temperature of job.
2. Be sure that the location chosen for unit installation provides ambient temperatures maintained above freezing.
Well water applications are especially susceptible to
freezing.
3. Be sure the installation location is isolated from sleeping
areas, private offices and other acoustically sensitive
spaces.
NOTE: A sound control accessory package may be used
to help eliminate sound in sensitive spaces.
4. Check local codes to be sure a secondary drain pan is not
required under the unit.
5. Be sure unit is mounted at a height sufficient to provide
an adequate slope of the condensate lines. If an appropriate slope cannot be achieved, a field-supplied condensate
pump may be required.
6. Provide sufficient space for duct connection.
7. Provide adequate clearance for filter replacement and
drain pan cleaning. Do not allow piping, conduit, etc. to
block filter access.
8. Provide sufficient access to allow maintenance and
servicing of the fan and fan motor, compressor and coils.
Removal of the entire unit from the closet should not be
necessary.
9. Provide an unobstructed path to the unit within the closet
or mechanical room. Space should be sufficient to allow
removal of unit if necessary.
10. Provide ready access to water valves and fittings, and
screwdriver access to unit side panels, discharge collar,
and all electrical connections.
11. Where access to side panels is limited, pre-removal of the
control box side mounting screws may be necessary for
future servicing.
STORAGE — If the equipment is not needed for immediate
installation upon its arrival at the jobsite, it should be left in its
shipping carton and stored in a clean, dry area of the building
or in a warehouse. Units must be stored in an upright position
at all times. If carton stacking is necessary, stack units a
maximum of 3 high. Do not remove any equipment from its
shipping package until it is needed for installation.
PROTECTION — Once the units are properly positioned on
the jobsite, they must be covered with either a shipping carton,
vinyl film, or an equivalent protective covering. Open ends of
pipes stored on the jobsite must be capped. This precaution is
2
Page 3
especially important in areas where painting, plastering, or
spraying of fireproof material, etc. is not yet complete. Foreign
material that is allowed to accumulate within the units can prevent proper start-up and necessitate costly clean-up operations.
Before installing any of the system components, be sure to
examine each pipe, fitting, and valve, and remove any dirt or
foreign material found in or on these components.
CAUTION
3. Verify that the unit’s refrigerant tubing is free of kinks or
dents, and that it does not touch other unit components.
4. Inspect all electrical connections. Be sure connections are
clean and tight at their terminations.
5. Loosen compressor bolts until the compressor rides freely
on springs. Remove shipping restraints.
6. Remove the four 6 mm (
1
/4 in.) shipping bolts from compressor support plate (two bolts on each side) to maximize vibration and sound alternation.
DO NOT store or install units in corrosive environments or
CAUTION
in locations subject to temperature or humidity extremes
(e.g., attics, garages, rooftops, etc.). Corrosive conditions
and high temperature or humidity can significantly reduce
performance, reliability, and service life. Always move
Failure to remove shipping brackets from spring-mounted
compressors will cause excessive noise and could cause
component failure due to added vibration.
units in an upright position. Tilting units on their sides may
cause equipment damage.
7. Remove any blower support cardboard from inlet of the
blower.
INSPECT UNIT — To prepare the unit for installation, complete the procedures listed below:
1. Compare the electrical data on the unit nameplate with
ordering and shipping information to verify that the
correct unit has been shipped.
8. Locate and verify any accessory kit located in compressor
and/or blower section.
9. Remove any access panel screws that may be difficult to
remove once unit is installed.
2. Do not remove the packaging until the unit is ready for
installation.
Table 1 — Physical Data — 50HQP072-120 Units
UNIT 50HQP072096120
COMPRESSOR QUANTITY*Scroll
Number of Circuits (Compressors)2
Factory Charge HFC-410A (kg) per circuit1.702.152.27
BLOWER MOTOR
Blower Motor Quantity1
Standard Motor (kW)0.751.492.24
BLOWER
No. of Blowers1
Blower Wheel Size D x W (cm)30.48 x 30.48
WATER CONNECTION SIZE
FPT (in.) [mm]1
COAX VOLUME
Volume (liters)6.136.859.08
CONDENSATE CONNECTION SIZE
FPT (in.) [mm]
AIR COIL DATA
Air Coil Dimensions H x W (cm)50.8 x 137.1650.8 x 162.56
Air Coil Total Face Area (sq m) 0.700.83
Air Coil Tube Size (cm)0.953
Air Coil Fin Spacing (fins per cm)5.5
Air Coil Number of Rows3
MISCELLANEOUS DATA
Filter Standard - Throwaway (qty) (cm)†40.64 x 50.80 x 2.54
Weight - Operating (kg)265.8292.1316.6
Weight - Packaged (kg)283.9310.3334.8
*All units have grommet and spring compressor mountings, and
2.2 mm and 3.5 mm electrical knockouts.
†51 mm filters are available as field-installed accessory.
1
/4 [31.8]11/2 [38.1]
3
/4 [19.1]
NOTE: Use the lowest maximum pressure rating when multiple
options are combined:
OPTIONMAXIMUM PRESSURE (kPa)
Base Unit3100
3
Page 4
a50-8531
Fig. 1 — Unit Dimensions
HANGER BRACKET DIMENSIONS
221cm
2.54cm
PLAN VIEW
TOP
10.8cm
86.6cm
FRONT
CONTROL BOX
U
T
S
V
3.3cm
condensate
LEFT RETURN LEFT VIEW-
AIR COIL SIDE
LEFT RETURN END DISCHARGE
CBP
EAP
BSP
CAP
CAP
FRONT
E
D
F
G
CAP
CBP
CAP
EAP
BSP
FRONT
FRONT
CONTROL BOX
PLAN VIEW
TOP
V
S
U
RIGHT RETURN RIGHT VIEW-
AIR COIL SIDE
RIGHT RETURN END DISCHARGE
3.3cm
condensate drain
3
LEFT RETURN STRAIGHT DISCHARGE
CAP
CAP
FRONT
BSP
A
EAP
CBP
B
C
O
P
Q
R
K
M
F
G
E
D
BSP
RIGHT RETURN STRAIGHT DISCHARGE
1
EAP
2CAP
CAP
2
FRONT
CBP
1
5
4
SERVICE ACCESS
3’ (91 cm.) TYPICAL
ALL CONFIGURATIONS
NOTES:
1. All dimensions in centimeters, unless indicated.
2. Access is required for all removable panels and installer should
take care to comply with all building codes and allow adequate
clearance.
3. Water inlet and outlet connections are available on either side of
the unit. Plugs are shipped loose in a plastic bag tied to the water
leg in front of the unit. Installer must plug unused connection.
4. Condensate drain connection is on end opposite of comressor.
5. Electrical access is available on either side of the front of the unit.
6. Electrical box is on right side but can be field-converted to left.
LEGEND
BSP — Blower Service Panel
CAP — Control Access Panel
CBP — Control Box Panel
EAP — Expansion Valve Access Panel
BSP — Blower Service Panel
CAP — Control Access Panel
CBP — Control Box Panel
EAP — Expansion Valve Access Panel
NOTES:
1. Access is required for all removable panels and installer should
take care to comply with all building codes and allow adequate
clearance.
2. Water inlet and outlet connections are available on either side of
the unit. Plugs are shipped loose in a plastic bag tied to the water
leg in front of the unit. Installer must plug unused connection.
3. Condensate drain connection is on end opposite of compressor.
4. Electrical access is available on either side of the front of the unit.
5. Electrical box is on right side but can be field-converted to left.
a50-8534
should be considered when choosing a location for a WSHP:
• Units are for indoor use only.
• Locate in areas where ambient temperatures are between
4.4 C and 37.8 C and relative humidity is no greater than
75%.
• Provide sufficient space for water, electrical and duct
connections.
• Locate unit in an area that allows for easy access and
removal of filter and access panels.
• Allow enough space for service personnel to perform
maintenance.
• Provisions must be made for return air to freely enter the
space if unit needs to be installed in a confined area such
as a closet.
NOTE: Correct placement of the horizontal unit can play an
important part in minimizing sound problems. Since ductwork is normally applied to these units, the unit can be placed
so that the principal sound emission is outside the occupied
space in sound-critical applications. A fire damper may be required by the local code if a fire wall is penetrated.
Step 4 — Mount Unit — Units should be mounted us-
ing the factory-installed hangers. See Fig. 3. Proper attachment
of hanging rods to building structure is critical for safety. See
Fig. 2. Rod attachments must be able to support the weight of
the unit. See Table 1 for unit operating weights.
Step 5 — Install Duct System — The duct system
should be sized to handle the design airflow quietly.
NOTE: Depending on the unit, the fan wheel may have a shipping support installed at the factory. This must be removed
before operating unit.
SOUND ATTENUATION — To eliminate the transfer of
vibration to the duct system, a flexible connector is recommended for both discharge and return air duct connections on
metal duct systems. The supply and return plenums should include internal duct liner of fiberglass or be made of duct board
construction to maximize sound attenuation of the blower.
Installing the WSHP unit to uninsulated ductwork in an unconditioned space is not recommended since it will sweat and
adversely affect the unit’s performance.
included in the supply and return air ducts, provided system
performance is not adversely impacted. The blower speed can
be also changed in the field to reduce air noise or excessive airflow, provided system performance is not adversely impacted.
5
To reduce air noise, at least one 90-degree elbow could be
Page 6
EXISTING DUCT SYSTEM — If the unit is connected to
3/8" [10MM] THREADED
ROD (FIELD SUPPLIED)
VIBRATION ISOLATOR
(FACTORY SUPPLIED)
WASHER
(FIELD SUPPLIED)
DOUBLE HEX NUTS
(FIELD SUPPLIED)
a50-6260e8535
Fig. 3 — Hanger Brackets
a50-6260ef8536
Fig. 4 — Horizontal Unit Pitch
*3/4" IPT
Trap Depth
1.5" [38mm]
Min 1.5"
[38mm]
1/4" per foot
(21mm per m)
drain slope
3/4" PVC or
Copper by others
Vent
Fig. 5 — Trap Condensate Drain
a50-6260e8537
existing ductwork, consider the following:
• Verify that the existing ducts have the proper capacity to
handle the unit airflow. If the ductwork is too small,
larger ductwork should be installed.
• Check existing ductwork for leaks and repair as
necessary.
NOTE: Local codes may require ventilation air to enter the
space for proper indoor air quality. Hard-duct ventilation may
be required for the ventilating air supply. If hard ducted ventilation is not required, be sure that a proper air path is provided
for ventilation air to unit to meet ventilation requirement of the
space.
Step 6 — Install Condensate Piping Drain
INSTALLATION — Slope the unit toward the drain at a
1 cm per 50 cm pitch. See Fig. 4. If it is not possible to meet the
required pitch, a condensate pump should be installed at the
unit to pump condensate to building drain.
Install condensate trap at each unit with the top of the trap
positioned below the unit condensate drain connection as
shown in Fig. 5. Design the depth of the trap (water-seal) based
upon the amount of ESP (external static pressure) capability of
the blower (where 2 in. wg of ESP capability requires 2 in. of
trap depth). As a general rule, 38 mm trap depth is the minimum. Each unit must be installed with its own individual trap
and connection to the condensate line (main) or riser.
Units are not internally trapped, therefore an external trap is
necessary. Each unit must be installed with its own individual
trap and means to flush or blowout the condensate drain line.
Do not install units with a common trap or vent. For typical
condensate connections see Fig. 5.
NOTE: Never use a pipe size smaller than the connection.
VENTING — A vent should be installed in the condensate
line of any application which may allow dirt or air to collect in
the line. Consider the following:
• Always install a vent where an application requires a
long horizontal run.
• Always install a vent where large units are working
against higher external static pressure and to allow
proper drainage for multiple units connected to the same
condensate main.
• Be sure to support the line where anticipated sagging
from the condensate or when “double trapping” may
occur.
• If condensate pump is present on unit, be sure drain connections have a check valve to prevent back flow of condensate into other units.
1/4” Pitch for
Drainage
Drain Connection
Step 7 — Field Convert Air Discharge — Hori-
zontal units can be field converted between straight (side) and
back (end) discharge.
NOTE: It is not possible to field convert return air between left
or right return models due to the necessity of refrigeration copper piping changes.
Field conversion must be completed on the ground. If the
unit is already hung it should be taken down for the field conversion. Place in a well-lighted area. Conversion should only
be attempted by a qualified service technician.
SIDE TO BACK DISCHARGE CONVERSION
1. Remove back panel and side access panel. See Fig. 6.
2. Loosen 2 motor slide nuts, raise motor slide assembly and
remove belt and motor sheave. See Fig. 7.
3. Remove blower sheave. Remove motor bolts and carefully remove motor. See Fig. 8.
4. Remove 2 motor clips and reattach to opposite side. See
Fig. 9.
5. Unbolt (3 per side) complete housing assembly. See
Fig. 9.
6. Rotate complete assembly into new position. Locate over
mounting holes in base, reattach using 3 bolts per side.
6
Pitch Toward
Drain
Page 7
REMOVE BLOWER PANEL
AND ACCESS PANEL
RETURN AIR
FRONT
Fig. 6 — Removing Panels
a50-8538
MOTOR SLIDE NUTS
Fig. 7 — Removing Belt
a50-8539
REMOVE MOTOR
AND BLOWER SHEAVE
ADJUSTING BOLT
REMOVE 4
MOTOR BOLTS
Fig. 8 — Removing Motor
a50-8540
MOTOR CLIPS
BOLTS
Fig. 9 — Removing Blower Assembly
a50-8541
7. Mount motor, motor sheave, blower sheave and belt.
8. Replace panels from Step 1.
BACK TO SIDE DISCHARGE CONVERSION — If the
discharge is changed from back to side, use the above instructions. Note that figures will be reversed.
LEFT OR RIGHT RETURN UNITS — It is not possible to
field convert return air between left or right return units due to
the necessity of refrigeration copper piping changes. However,
the conversion process of side to back or back to side discharge
for either right or left return configuration is the same. In some
cases, it may be possible to rotate the entire unit 180 degrees if
the return air connection needs to be on the opposite side. Note
that rotating the unit will move the piping to the other end of
the unit.
Step 8 — Install Piping Connections — Depend-
ing on the application, there are 3 types of WSHP piping systems to choose from: water loop, ground-water and ground loop.
Refer to the Carrier System Design Manual for additional information.
pipe thread fittings for water connections to prevent annealing
and out-of-round leak problems which are typically associated
with high temperature brazed connections. Refer to Table 1 for
connection sizes. When making piping connections, consider
the following:
• A backup wrench must be used when making screw con-
Make sure wires are not pinched and not over sharp edges. Adjust motor downward to tighten belt. Raise or lower
motor slide assembly with adjusting bolt and retighten the
2 slide nuts. Check for correct tension. Rewire motor (at
contactor) for correct rotation. Spin blower wheel to ensure wheel is not obstructed.
All WSHP units utilize low temperature soldered female
nections to unit to prevent internal damage to piping.
• Insulation may be required on piping to avoid condensation in the case where fluid in loop piping operates at
temperatures below dew point of adjacent air.
• Piping systems that contain steel pipes or fittings may
be subject to galvanic corrosion. Dielectric fittings may
be used to isolate the steel parts of the system to avoid
galvanic corrosion.
• Do not allow hoses to rest against structural building
components. Compressor vibration may be transmitted
through the hoses to the structure, causing unnecessary
noise complaints.
Figure 10 shows a typical supply/return hose kit assembly.
WATER LOOP APPLICATIONS — Water loop applications
usually include a number of units plumbed to a common piping system. Maintenance to any of these units can introduce air
into the piping system. Therefore, air elimination equipment
comprises a major portion of the mechanical room plumbing.
The flow rate is usually set between 2.41 and 3.23 L/m per
kW of cooling capacity. For proper maintenance and servicing,
pressure-temperature (P/T) ports are necessary for temperature
and flow verification.
In addition to complying with any applicable codes, consid-
er the following for system piping:
• Piping systems utilizing water temperatures below
10 C require 13 mm closed cell insulation on all piping
surfaces to eliminate condensation.
7
Page 8
Step 9 — Install Field Power Supply Wiring
RIB CRIMPED
LENGTH
(2 FT [0.6M] LENGTH STANDARD)
SWIVEL
BRASS
FITTING
BRASS
FITTING
EPT
Fig. 10 — Supply/Return Hose Kit
WARNING
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work
is completed.
• All plastic to metal threaded fittings should be avoided
due to the potential to leak. Use a flange fitted substitute.
• Teflon tape thread sealant is recommended to minimize
internal fouling of the heat exchanger.
• Use backup wrench. Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• The piping system should be flushed prior to operation to
remove dirt and foreign materials from the system.
GROUND-LOOP APPLICATIONS — Temperatures between –3.9 and 43.3 C and a cooling capacity of 2.41 to
3.23 L/s per kW of flow per ton are recommended. In
addition to complying with any applicable codes, consider
the following for system piping:
• Piping materials should be limited to only polyethylene
fusion in the buried sections of the loop.
• Galvanized or steel fittings should not be used at any
time due to corrosion.
• All plastic to metal threaded fittings should be avoided
due to the potential to leak. Use a flange fitted substitute.
• Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• Pressure-temperature (P/T) plugs should be used to measure flow of pressure drop.
GROUND-WATER APPLICATIONS — Typical groundwater piping is shown in Fig. 11. In addition to complying
with any applicable codes, consider the following for system piping:
• Install shut-off valves for servicing.
• Install pressure-temperature plugs to measure flow and
temperature.
• Boiler drains and other valves should be connected using
a “T” connector to allow acid flushing for the heat
exchanger.
• Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• Use PVC SCH80 or copper piping material.
NOTE: PVC SCH40 should not be used due to system high
pressure and temperature extremes.
Water Supply and Quantity
— Check water supply. Water
supply should be plentiful and of good quality. See Table 2 for
water quality guidelines.
IMPORTANT: Failure to comply with the above required
water quality and quantity limitations and the closedsystem application design requirements may cause damage
to the tube-in-tube heat exchanger that is not the responsibility of the manufacturer.
CAUTION
Use only copper conductors for field-installed electrical
wiring. Unit terminals are not designed to accept other
types of conductors.
All field-installed wiring, including the electrical ground,
MUST comply with the National Electrical Code (NEC,
U.S.A.) as well as applicable local codes. In addition, all field
wiring must conform to the Class II temperature limitations described in the NEC.
Refer to unit wiring diagrams Fig. 12-16 for fuse sizes and a
schematic of the field connections which must be made by the
installing (or electrical) contractor.
Consult the unit wiring diagram located on the inside of the
compressor access panel to ensure proper electrical hookup.
The installing (or electrical) contractor must make the field
connections when using field-supplied disconnect.
Operating voltage must be the same voltage and phase as
shown in electrical data shown in Tables 3A and 3B.
Make all final electrical connections with a length of flexible conduit to minimize vibration and sound transmission to
the building.
POWER CONNECTION — Line voltage connection is
made by connecting the incoming line voltage wires to the
L side of the power block terminal. See Fig. 17. See Tables
3A and 3B for correct wire and maximum overcurrent protection sizing. See Table 4 for low voltage VA ratings.
SUPPLY VOLTAGE — Operating voltage to unit must be
within voltage range indicated on unit nameplate.
On 3-phase units, voltages under load between phases must
be balanced within 2%. Use the following formula to determine the percentage voltage imbalance:
% Voltage Imbalance
= 100 x
Example: Supply voltage is 420-3-50.
max voltage deviation from average voltage
average voltage
AB = 425 volts
BC = 422 volts
AC = 417 volts
Average Voltage =
425 + 422 + 417
1264
=
3
3
In all applications, the quality of the water circulated
through the heat exchanger must fall within the ranges listed in
the Water Quality Guidelines table. Consult a local water treatment firm, independent testing facility, or local water authority
for specific recommendations to maintain water quality within
the published limits.
= 421
Determine maximum deviation from average voltage:
(AB) 425 – 421 = 4 v
(BC) 422 – 421 = 1 v
(AC) 421 – 418 = 3 v
Maximum deviation is 4 v.
8
Page 9
Determine percent voltage imbalance.
PressureTemperature
Plugs
Boiler
Drains
Strainer – Field-Installed Accessory
(16 to 20 mesh recommended for
filter sediment)
This amount of phase imbalance is satisfactory as it is
below the maximum allowable 2%.
Operation on improper line voltage or excessive phase
imbalance constitutes abuse and may cause damage to electrical components.
NOTE: If more than 2% voltage imbalance is present, contact
local electric utility.
EXTERNAL LOOP POWER CONNECTION — If the unit
is to be connected to an external loop pump or flow controller,
connect the pump to the loop pump terminal block PB1. The
maximum power handling is 4 amps at 240 volts. The pumps
will automatically cycle as required by the unit.
420-VOLT OPERATION — All 380/420 volt units are factory
wired for 380 volts. The transformers may be switched to
420-volt operation (as illustrated on the wiring diagram) by
disconnecting the VIO lead at L1 and attaching the BRN lead
to L1. Close open end of VIO lead.
9
Page 10
Table 2 — Water Quality Guidelines
CONDITION
Scaling Potential — Primary Measurement
Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below.
pH/Calcium
Hardness Method
Index Limits for Probable Scaling Situations (Operation outside these limits is not recommended.)
Scaling indexes should be calculated at 150 F for direct use and HWG applications, and at 90 F for indirect HX use. A monitoring plan should be
implemented.
Ryznar Stability Index
Langelier Saturation Index
Iron Fouling
2+
(Ferrous)
Iron Fe
(Bacterial Iron Potential)
Iron Fouling
Corrosion Prevention††
pH
Hydrogen Sulfide (H
Ammonia Ion as Hydroxide,
Chloride, Nitrate and Sulfate
Compounds
S)
2
Maximum Chloride LevelsMaximum allowable at maximum water temperature.
Erosion and Clogging
Particulate Size and Erosion
Brackish
LEGEND
HWG — Hot Water Generator
HX— Heat Exchanger
N/A— Design Limits Not Applicable Considering Recirculating
NR— Application Not Recommended
SS— Stainless Steel
*Heat exchanger materials considered are copper, cupronickel, 304 SS (stainless
steel), 316 SS, titanium.
†Closed recirculating system is identified by a closed pressurized piping system.
**Recirculating open wells should observe the open recirculating design
considerations.
Potable Water
HX
MATERIAL*
CLOSED RECIRCULATING†OPEN LOOP AND RECIRCULATING WELL**
AllN/ApH < 7.5 and Ca Hardness, <100 ppm
AllN/A
AllN/A
AllN/A
AllN/A
All
6 - 8.5
Monitor/treat as needed.
If >7.5 minimize steel pipe use.
Based upon 150 F HWG and direct well, 85 F indirect well HX.
2+
If Fe
(ferrous) >0.2 ppm with pH 6 - 8, O2<5 ppm check for iron bacteria.
If <–0.5 minimize steel pipe use.
Above this level deposition will occur.
Minimize steel pipe below 7 and no open tanks with pH <8.
6.0 - 7.5
–0.5 to +0.5
<0.2 ppm (Ferrous)
<0.5 ppm of Oxygen
6 - 8.5
<0.5 ppm
At H
S>0.2 ppm, avoid use of copper and cupronickel piping or HXs.
<10 ppm (<1 ppm “sand free” for reinjection) of particles and a maximum velocity of 6
fps. Filtered for maximum 800 micron size. Any particulate that is not removed can
potentially clog components.
Use cupronickel heat exchanger when concentrations of calcium or sodium chloride
are greater than 125 ppm are present. (Seawater is approximately 25,000 ppm.)
2
Copper alloy (bronze or brass) cast components are okay to <0.5 ppm.
Rotten egg smell appears at 0.5 ppm level.
<0.5 ppm
50 F (10 C)75 F (24 C)100 F (38 C)
<20 ppmNRNR
††If the concentration of these corrosives exceeds the maximum allowable level,
then the potential for serious corrosion problems exists.
Sulfides in the water quickly oxidize when exposed to air, requiring that no agitation
occur as the sample is taken. Unless tested immediately at the site, the sample will
require stabilization with a few drops of one Molar zinc acetate solution, allowing
accurate sulfide determination up to 24 hours after sampling. A low pH and high
alkalinity cause system problems, even when both values are within ranges shown.
The term pH refers to the acidity, basicity, or neutrality of the water supply. Below
7.0, the water is considered to be acidic. Above 7.0, water is considered to be basic.
Neutral water contains a pH of 7.0.
NOTE: To convert ppm to grains per gallon, divide by 17. Hardness in mg/l is equivalent to ppm.
10
Page 11
BC— Blower Contactor
CB— Circuit Breaker
CC— Compressor Contactor
CO— Sensor, Condensate Overflow
DPP— Dual Point Power
FP1— Sensor, Water Coil Freeze Protection
FP2— Sensor, Air Coil Freeze Protection
HP— High-Pressure Switch
HPWR — High-Pressure Water Relay
JW3— Clippable Field Selection Jumper
LOC— Loss of Charge Pressure Switch
PDB— Power Distribution Block
RVS— Reversing Valve Solenoid
TRANS — Tr a n sf o r me r
TXV— Thermostatic Expansion Valve
Factory Line Voltage Wiring
Factory Low Voltage Wiring
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC (National Electrical
Code, U.S.A.) and local codes.
3. 380/420-v transformers will be connected for 380-v operation. For
420-v operation, disconnect VIO lead at L1, and attach BRN lead
to L1. Close open end of VIO lead.
4. FPI thermistor provides freeze protection for WATER. When using
ANTIFREEZE solutions, cut JW3 jumper.
5. Typical heat pump thermostat wiring shown. Refer to thermostat
installation instructions for wiring to the unit. Thermostat wiring
must be “Class 1” and voltage rating equal to or greater than unit
supply voltage.
6. 24-v alarm signal shown. For dry alarm contact, cut JW1 jumper
and dry contact will be available between AL1 and AL2.
7. Transformer secondary ground via Complete C board standoffs
and screws to control box. (Ground available from top two standoffs as shown.)
8. Suffix 1 designates association with lead compressor. Suffix 2
with lag compressor.
9. For dual point power (DPP) option, blower wire will connect to
other PBD.
LEGEND
Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
Optional Wiring
Relay/Contactor Coil
Thermistor
Condensate Pan
Circuit Breaker
Ground
Solenoid Coil
Relay Contacts - N.O.
Relay Contacts - N.C.
Temperature Switch
Switch - Low Pressure
Switch - High Pressure
Wire Nut
Fig. 12 — 50HQP072-120 Units — Typical Control Wiring with Complete C Control
Complete C
Complete C1
Complete C
Complete C2
Complete C2
Complete C1
11
Page 12
Fig. 13 — 50HQP072-120 Units — Typical Control Wiring with Deluxe D Control
See legend and notes on page 11.
Deluxe D1
Deluxe D
Deluxe D2
Deluxe D
Deluxe D2
Deluxe D1
12
Page 13
Y
W
O
G
R
C
AL1
AL2
A
CR
CMP1
FAN
PWR
HS1/EXH/RVS
PREMIER
LINK
CR
COMPLETE
C
CONTROL
J4
J6
J5
J8
J1
PWR
S
P
S
A
L
W
CMPSAFE
T
T
T
Y1
G
R
C
AL1
CMP1
FAN
PWR
PREMIER
LINK
DELUXE
D
CONTROL
J4
J8
J1
PWR
CMPSAFE
HS2
HS1
CMP2
Y2
W1
O/W2
J6
J5
S
P
T
S
A
T
L
W
T
Fig. 14 — Premierlink™ Controller Applications Wiring with Complete C Control
LEGEND
NOTE: Reversing valve is on in Cooling
mode.
CR — Control Relay
LWT — Leaving Water Temperature Sensor
SAT — Supply Air Temperature Sensor
SPT — Space Temperature Sensor
Fig. 15 — Premierlink Controller Applications Wiring with Deluxe D Control
LEGEND
NOTE: Reversing valve is on in Cooling
mode.
LWT — Leaving Water Temperature Sensor
SAT — Supply Air Temperature Sensor
SPT — Space Temperature Sensor
13
Page 14
Table 3A — Electrical Data — 50HQP072-120 Standard Units
NOTE: Low voltage connector may be removed for easy installation.
Remaining VA for Accessories*
Units with Complete C
Units with Deluxe D
* Standard transformer is 75 VA.
18 - 39
12 - 33
Complete C 2Complete C 1
POWER
BLOCK
14
Page 15
Step 10 — Install Field Control Wiring
a50-6268tf.tif
AQUAZONE CONTROL (Complete C Control Shown)
Fig. 18 — Typical Aquazone™ Control Board
Jumper Locations
TYPICAL
WATER
VALVE
C
A
24 VAC
TERMINAL STRIP P2
Fig. 19 — Typical Aquazone Accessory Wiring
(Control D Shown)
THERMOSTAT
Compressor-Stage 1
Reversing Valve
Fan
24Vac Hot
Y1
Y2
O
G
R
Y
O
G
R
CompleteC 1
Y
O
G
R
24Vac Com
C
C
Compressor-Stage 2
C
AL
AL
AL
CompleteC 2
Fig. 20 — Thermostat Wiring to Complete C Board
THERMOSTAT
Compressor-Stage 1
Reversing Valve
Fan
24Vac Hot
Y1
Y2
O
G
R
O
G
R
Deluxe D 1
Y
O
G
R
24Vac Com
C
C
Compressor-Stage 2
C
AL1
AL1
AL
Y1
Y2
COM 2
COM 2
Deluxe D 2
Fig. 21 — Thermostat Wiring to Deluxe D Board
THERMOSTAT CONNECTIONS — The thermostat should
be wired directly to the Aquazone™ control board. See
Fig. 18 and 19.
The thermostat should be located on an interior wall in a
larger room, away from supply duct drafts. DO NOT locate the
thermostat in areas subject to sunlight, drafts or on external
walls. The wire access hole behind the thermostat may in certain cases need to be sealed to prevent erroneous temperature
measurement.
Position the thermostat back plate against the wall so that it
appears level and so the thermostat wires protrude through the
middle of the back plate. Mark the position of the back plate
mounting holes and drill holes with a
plied anchors and secure plate to the wall. Thermostat wire
must be 18 AWG (American Wire Gage) wire. Wire the appropriate thermostat as shown in Fig. 20 and 21 to the low voltage
terminal strip on the Complete C or Deluxe D control board.
Most heat pump thermostats will work with a Carrier unit,
provided the thermostat has the correct number of heating and
cooling stages.
WATER FREEZE PROTECTION — The Aquazone control
allows the field selection of source fluid freeze protection
points through jumpers. The factory setting of jumper JW3
(FP1) is set for water at –1.1 C. In earth loop applications,
jumper JW3 should be clipped to change the setting to –12.2 C
when using antifreeze in colder earth loop applications. See
Fig. 18.
AIR COIL FREEZE PROTECTION — The air coil freeze
protection jumper JW2 (FP2) is factory set for –1.1 C and
should not need adjusting.
ACCESSORY CONNECTIONS — Terminal labeled A on
the control is provided to control accessory devices such as
water valves, electronic air cleaners, humidifiers, etc. This signal operates with the compressor terminal. See Fig. 19. Refer
to the specific unit wiring schematic for details.
NOTE: The A terminal should only be used with 24 volt
signals — not line voltage signals.
3
/16-in. bit. Install sup-
WATER SOLENOID VALVES — Water solenoid valves may
be used on variable flow systems and ground water installations. A typical well water control valve wiring which can
limit waste water in a lockout condition is shown in Fig. 18. A
slow closing valve may be required to prevent water hammer.
When using a slow closing valve, special wiring conditions
need to be considered. The valve takes approximately 60 seconds to open (very little water will flow before 45 seconds) and
it activates the compressor only after the valve is completely
opened by closing its end switch. When wired as shown, the
valve will have the following operating characteristics:
1. Remain open during a lockout.
2. Draw approximately 25 to 35 VA through the “Y” signal
of the thermostat.
IMPORTANT: The use of a slow-closing water solenoid
valve can overheat the anticipators of electromechanical
thermostats. Only use relay based electronic thermostats.
15
Page 16
PRE-START-UP
System Checkout —
follow the system checkout procedure outlined below before
starting up the system. Be sure:
1. Voltage is within the utilization range specifications of the
unit compressor and fan motor and voltage is balanced
for 3-phase units.
2. Fuses, breakers and wire are correct size.
3. Low voltage wiring is complete.
4. Piping and system flushing is complete.
5. Air is purged from closed loop system.
6. System is balanced as required. Monitor if necessary.
7. Isolation valves are open.
8. Water control valves or loop pumps are wired.
9. Condensate line is open and correctly pitched.
10. Transformer switched to lower voltage tap if necessary.
11. Blower rotates freely — shipping support is removed.
12. Blower speed is on correct setting.
13. Air filter is clean and in position.
14. Service/access panels are in place.
15. Return-air temperature is 4.4 to 26.7 C for heating and
10.0 to 43.3 C for cooling.
16. Air coil is clean.
17. Control field selected settings are correct.
AIR COIL — To obtain maximum performance, the air coil
should be cleaned before starting the unit. A ten percent
solution of dishwasher detergent and water is recommended
for both sides of the coil. Rinse thoroughly with water.
When the installation is complete,
Airflow and External Static Pressure — The
50HQP units are available with standard, low, and high-static
factory-installed options. These options will substitute a different blower drive sheave for each static range. In addition, certain static ranges may require the optional large fan motor.
SHEAVE ADJUSTMENT — The 50HQP units are supplied
with a variable sheave drive on the fan motor to adjust for differing airflows at various ESP (external static pressure) conditions. See Tables 5-7 for unit airflows. When fully closed, the
sheave will produce the highest static capability (higher rpm).
To adjust sheave position, follow the procedure outlined
below:
1. Loosen belt tension and remove belt.
2. Loosen set screw on fan motor.
3. Open sheave to desired position.
4. Retighten set screw and replace belt.
NOTE: Set belt tension as outlined below.
BELT TENSION ADJUSTMENT — An overly loose belt
will, upon starting motor, produce a slippage “squeal” and
cause premature belt failure and or intermittent airflow. An
overly tight belt can cause premature motor or blower bearing failure. To adjust the belt tension, follow the procedure
outlined below:
1. Remove belt from motor sheave.
2. Lift motor assembly.
3. Loosen the
5
/16-in. hex nuts on the grommet motor adjustment bolts (2 per bolt). To increase the belt tension loosen
the top hex nut. To decrease the belt tension loosen the
bottom hex nut.
4. Turn the bolts by hand to the desired position then tighten
5
the
/16-in. hex nuts (2 per bolt).
5. Lower the motor assembly.
6. Install the belt.
7. The belt tension can be adjusted by using one of the following methods:
a. Tighten until belt deflects approximately 13 mm
with very firm finger pressure.
b. Grasp belt midway between two pulleys and twist
for a 90-degreerotation.
NOTE: Adjusting less than 90 degrees will over-
tighten the belt and adjusting more than 90degrees
will loosen belt.
c. Set proper belt tension to 32 to 36 kg.
NOTE: The motor position should not need adjustment. Motor
sheave position is at mid position of each sheave. For example,
the motor sheave is 2.5 turns open on a 5-turn sheave. The belt
tension adjustment can also be accomplished by turning the
5
/16-in. hex nuts to the desired position.
NOTE: Available airflows for all units are shown in
Tables 5-7.
——Operation Not Recommended
BkW — Brake Kilowatts
ESP — External Static Pressure
RPM — Revolutions Per Minute
A—Units with Standard Rpm/Standard Motor Option
B—Units with Low Rpm/Standard Motor Option
C—Units with High Rpm/Standard Motor Option
1. A = Standard Rpm/Standard Motor, B = Low Rpm/Standard Motor, C =
High Rpm/Standard Motor.
2. Unit factory shipped with standard static sheave and drive at 2.5 turns
open. Other speed require field selection.
3. For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based
on sea level conditions.
4. All airflow is rated at lowest voltage if unit is dual voltage rated, i.e., 380V
for 380/420V units.
——Operation Not Recommended
BkW — Brake Kilowatts
ESP — External Static Pressure
RPM — Revolutions Per Minute
A—Units with Standard Static/Standard Motor Option
B—Units with Low Static/Standard Motor Option
C—Units with High Static/Standard Motor Option
EXTERNAL STATIC PRESSURE (Pa)
1. A = Standard Rpm/Standard Motor, B = Low Rpm/Standard Motor, C =
High Rpm/Standard Motor.
2. Unit factory shipped with standard static sheave and drive at 2.5 turns
open. Other speed require field selection.
3. For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based
on sea level conditions.
4. All airflow is rated at lowest voltage if unit is dual voltage rated, i.e., 380V
for 380/420V units.
——Operation Not Recommended
BkW — Brake Kilowatts
ESP — External Static Pressure
RPM — Revolutions Per Minute
A—Units with Standard Static/Standard Motor Option
B—Units with Low Static/Standard Motor Option
C—Units with High Static/Standard Motor Option
1. A = Standard Rpm/Standard Motor, B = Low Rpm/Standard Motor, C =
High Rpm/Standard Motor.
2. Unit factory shipped with standard static sheave and drive at 2.5 turns
open. Other speed require field selection.
3. For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based
on sea level conditions.
4. All airflow is rated at lowest voltage if unit is dual voltage rated, i.e., 380V
for 380/420V units.
——Operation Not Recommended
BkW — Brake Kilowatts
ESP — External Static Pressure
RPM — Revolutions Per Minute
A—Units with Standard Static/Standard Motor Option
B—Units with Low Static/Standard Motor Option
C—Units with High Static/Standard Motor Option
1. A = Standard Rpm/Standard Motor, B = Low Rpm/Standard Motor, C =
High Rpm/Standard Motor.
2. Unit factory shipped with standard static sheave and drive at 2.5 turns
open. Other speed require field selection.
3. For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based
on sea level conditions.
4. All airflow is rated at lowest voltage if unit is dual voltage rated, i.e., 380V
for 380/420V units.
5. Airflow in l/s with wet coil and clean filter.
FIELD SELECTABLE INPUTS
Jumpers and DIP (dual in-line package) switches on the
control board are used to customize unit operation and can be
configured in the field.
IMPORTANT: Jumpers and DIP switches should only be
clipped when power to control board has been turned off.
Complete C Control Jumper Settings (See
Fig. 12)
WATER COIL FREEZE PROTECTION (FP1) LIMIT
SETTING — Select jumper 3, (JW3-FP1 Low Temp) to
choose FP1 limit of –12.2 C or –1.1 C. To select –1.1 C as the
limit, DO NOT clip the jumper. To select –12.2 C as the limit,
clip the jumper.
AIR COIL FREEZE PROTECTION (FP2) LIMIT SETTING — Select jumper 2 (JW2-FP2 Low Temp) to choose
FP2 limit of –12.2 C or –1.1 C. To select –1.1 C as the limit,
DO NOT clip the jumper. To select –12.2 C as the limit, clip
the jumper.
ALARM RELAY SETTING — Select jumper 1 (JW1-AL2
Dry) for connecting alarm relay terminal (AL2) to 24 vac (R) or
to remain as a dry contact (no connection). To connect AL2 to
R, do not clip the jumper. To set as dry contact, clip the jumper.
Complete C Control DIP Switches — The Com-
plete C Control has 1 DIP switch block with five switches. See
Fig. 12.
PERFORMANCE MONITOR (PM) — DIP switch 1 will
enable or disable this feature. To enable the PM, set the switch
to ON. To disable the PM, set the switch to OFF.
STAGE 2 — DIP switch 2 will enable or disable compressor
delay. Set DIP switch to OFF for stage 2 in which the compressor will have a 3-second delay before energizing.
NOTE: The alarm relay will not cycle during Test mode if
switch is set to OFF, stage 2.
DIP SWITCH 3 — not used.
DIP SWITCH 4 — not used.
DIP SWITCH 5 — DIP switch 5 is used to initiate 1 or 3 tries
for the FP1 fault. If water freeze protection for the water coil
then DIP switch 5 can be set to lockout on the FP1 fault after
one try.
Deluxe D Control Jumper Settings (See
Fig. 13)
WATER COIL FREEZE PROTECTION (FP1) LIMIT
SETTING — Select jumper 3, (JW3-FP1 Low Temp) to
choose FP1 limit of –12.2 C or –1.1 C. To select –1.1 C as the
limit, DO NOT clip the jumper. To select –12.2 C as the limit,
clip the jumper.
20
Page 21
AIR COIL FREEZE PROTECTION (FP2) LIMIT SETTING — Select jumper 2 (JW2-FP2 Low Temp) to choose
FP2 limit of –12.2 C or –1.1 C. To select –1.1 C as the limit,
DO NOT clip the jumper. To select –12.2 C as the limit, clip
the jumper.
ALARM RELAY SETTING — Select jumper 4 (JW4-AL2
Dry) for connecting alarm relay terminal (AL2) to 24 vac (R) or
to remain as a dry contact (no connection). To connect AL2 to
R, do not clip the jumper. To set as dry contact, clip the jumper.
LOW PRESSURE SETTING — The Deluxe D Control can
be configured for Low Pressure Setting (LP). Select jumper 1
(JW1-LP Norm Open) for choosing between low pressure input normally opened or closed. To configure for normally
closed operation, do not clip the jumper. To configure for normally open operation, clip the jumper.
Deluxe D Control DIP Switches — The Deluxe D
Control has 2 DIP switch blocks. Each DIP switch block has 8
switches and is labeled either S1 or S2 on the circuit board. See
Fig. 13.
DIP SWITCH BLOCK 1 (S1) — This set of switches offers
the following options for Deluxe D Control configuration:
Performance Monitor (PM)
able performance monitor. To enable the PM, set the switch to
ON. To disable the PM, set the switch to OFF.
Compressor Relay Staging Operation
or disable compressor relay staging operation. The compressor
relay can be set to turn on with stage 1 or stage 2 call from the
thermostat. This setting is used with dual stage units (units with
2 compressors and 2 Deluxe D controls) or in master/slave applications. In master/slave applications, each compressor and
fan will stage according to its switch 2 setting. If switch is set to
stage 2, the compressor will have a 3-second delay before energizing during stage 2 demand.
NOTE: If DIP switch is set for stage 2, the alarm relay will not
cycle during Test mode.
Heating/Cooling Thermostat Type
tion of thermostat type. Heat pump or heat/cool thermostats
can be selected. Select OFF for heat/cool thermostats. When in
heat/cool mode, Y1 is used for cooling stage 1, Y2 is used for
cooling stage 2, W1 is used for heating stage 1 and O/W2 is
used for heating stage 2. Select ON for heat pump applications.
In heat pump mode, Y1 used is for compressor stage 1, Y2 is
used for compressor stage 2, W1 is used for heating stage 3 or
emergency heat, and O/W2 is used for RV (heating or cooling)
depending upon switch 4 setting.
O/B Thermostat Type
pump O/B thermostats. O is cooling output. B is heating output. Select ON for heat pumps with O output. Select OFF for
heat pumps with B output.
Dehumidification Fan Mode
of normal or dehumidification fan mode. Select OFF for dehumidification mode. The fan speed relay will remain OFF during cooling stage 2. Select ON for normal mode. The fan speed
relay will turn on during cooling stage 2 in normal mode.
Switch 6
— Not used.
Boilerless Operation
erless operation and works in conjunction with switch 8. In
boilerless operation mode, only the compressor is used for
heating when FP1 is above the boilerless changeover temperature set by switch 8 below. Select ON for normal operation or
select OFF for boilerless operation.
Boilerless Changeover Temperature
vides selection of boilerless changeover temperature set point.
Select OFF for set point of 10.0 C or select ON for set point
of 4.4 C.
If switch 8 is set for 10.0 C, then the compressor will be
used for heating as long as the FP1 is above 10.0 C. The
— Set switch 1 to enable or dis-
— Switch 2 will enable
— Switch 3 provides selec-
— Switch 4 provides selection for heat
— Switch 5 provides selection
— Switch 7 provides selection of boil-
— Switch 8 on S1 pro-
compressor will not be used for heating when the FP1 is below
10.0 C and the compressor will operate in emergency heat
mode, staging on EH1 and EH2 to provide heat. If a thermal
switch is being used instead of the FP1 thermistor, only the
compressor will be used for heating mode when the FP1 terminals are closed. If the FP1 terminals are open, the compressor is
not used and the control goes into emergency heat mode.
DIP SWITCH BLOCK 2 (S2) — This set of DIP switches is
used to configure accessory relay options. See Fig. 13.
Switches 1 to 3
— These DIP switches provide selection of
Accessory 1 relay options. See Table 8 for DIP switch
combinations.
Switches 4 to 6
— These DIP switches provide selection
of Accessory 2 relay options. See Table 9 for DIP switch
combinations.
Auto Dehumidification Mode or High Fan Mode
— Switch 7
provides selection of auto dehumidification fan mode or high
fan mode. In auto dehumidification fan mode the fan speed
relay will remain off during cooling stage 2 if terminal H is
active. In high fan mode, the fan enable and fan speed relays
will turn on when terminal H is active. Set the switch to ON for
auto dehumidification fan mode or to OFF for high fan mode.
Switch 8
— Not used.
Table 8 — DIP Switch Block S2 —
Accessory 1 Relay Options
ACCE SSORY 1
RELAY OPTIONS
Cycle with FanOnOnOn
Digital NSBOffOnOn
Water Valve — Slow OpeningOnOffOn
OADOnOnOff
LEGEND
NSB — Night Setback
OAD — Outside Air Damper
NOTE: All other DIP switch combinations are invalid.
DIP SWITCH POSITION
123
Table 9 — DIP Switch Block S2 —
Accessory 2 Relay Options
ACCE SSORY 2
RELAY OPTIONS
Cycle with FanOnOnOn
Digital NSBOffOnOn
Water Valve — Slow OpeningOnOffOn
OADOnOnOff
LEGEND
NSB — Night Setback
OAD — Outside Air Damper
NOTE: All other switch combinations are invalid.
DIP SWITCH POSITION
456
Deluxe D Control Accessory Relay Configurations —
ble for both Deluxe D controls only:
CYCLE WITH FAN — In this configuration, the relay will be
ON any time the Fan Enable relay is on.
CYCLE WITH COMPRESSOR — In this configuration, the
relay will be ON any time the Compressor relay is on.
DIGITAL NIGHT SET BACK (NSB) — In this configura-
tion, the relay will be ON if the NSB input is connected to
ground C.
NOTE: If there are no relays configured for digital NSB, then
the NSB and override (OVR) inputs are automatically configured for mechanical operation.
The following accessory relay settings are applica-
21
Page 22
MECHANICAL NIGHT SET BACK — When NSB input is
connected to ground C, all thermostat inputs are ignored. A
thermostat set back heating call will then be connected to the
OVR input. If OVR input becomes active, then the Deluxe D
control will enter Night Low Limit (NLL) staged heating
mode. The NLL staged heating mode will then provide heating
during the NSB period.
WATER VALVE (SLOW OPENING) — If relay is configured for Water Valve (slow opening), the relay will start 60 seconds prior to starting compressor relay.
OUTSIDE AIR DAMPER (OAD) — If relay is configured
for OAD, the relay will normally be ON any time the Fan
Enable relay is energized. The relay will not start for 30 minutes following a return to normal mode from NSB, when NSB
is no longer connected to ground C. After 30 minutes, the relay
will start if the Fan Enable is set to ON.
START-UP
CAUTION
To avoid equipment damage, DO NOT leave system filled
in a building without heat during the winter unless antifreeze is added to system water. Condenser coils never
fully drain by themselves and will freeze unless winterized
with antifreeze.
Use the procedure outlined below to initiate proper unit
start-up.
NOTE: This equipment is designed for indoor installation only.
WARNING
When the disconnect switch is closed, high voltage is present in some areas of the electrical panel. Exercise caution
when working with the energized equipment.
Operating Limits
ENVIRONMENT — This equipment is designed for indoor
installation ONLY. Extreme variations in temperature, humidity and corrosive water or air will adversely affect the unit performance, reliability and service life.
POWER SUPPLY — A voltage variation of ± 10% of nameplate utilization voltage is acceptable.
UNIT STARTING CONDITIONS — All units can start and
operate in an ambient of 7.2 C with entering-air at 10.0/7.2 C
(db/wb), entering water at –1.1 C and with both air and water at
the flow rates used. All other conditions are the same as shown
in Table 10.
NOTE: These operating conditions are not normal or continuous operating conditions. It is assumed that such a start-up is
for the purpose of bringing the building space up to occupancy
temperature.
Air Coil Cleaning — To obtain maximum performance,
the air coil should be cleaned before start-up. A 10% solution
of dishwasher detergent and water is recommended for both
sides of the coil. A thorough water rinse should follow. Ultraviolet based anti-bacterial systems may damage e-coated air
coils.
Start Up System
1. Restore power to system.
2. Turn thermostat fan position to ON. Blower should start.
3. Balance airflow at registers.
4. Adjust all valves to the full open position and turn on the
line power to all heat pump units.
5. Operate unit in the cooling cycle. Room temperature
should be approximately 7.2 to 43.3 C dry bulb. Loop
water temperature entering the heat pumps should be
between 10.0 and 43.3 C.
NOTE: Three factors determine the operating limits of a
unit: (1) entering-air temperature, (2) water temperature and
(3) ambient temperature. Whenever any of these factors are
at a minimum or maximum level, the other two factors must
be at a normal level to ensure proper unit operation. See
Table 10. Extreme variations in temperature and humidity and/
or corrosive water or air will adversely affect unit performance, reliability, and service life.
Table 10 — Operating Limits
AIR LIMITSCOOLING (C) HEATING (C)
Minimum Ambient Air db74
Rated Ambient Air db2720
Maximum Ambient Air db4329
Minimum Entering Air db/wb16/1010
Rated Entering Air db/wb27/1920
Maximum Entering Air db/wb35/2427
WATER LIMITS
Minimum Entering Water–1–6.7
Normal Entering Water10 to 43–1 to 21
Maximum Entering Water4932
Normal Water Flow1.6 to 3.2 L/m per kW
LEGEND
db — Dry Bulb
wb — Wet Bulb
Scroll Compressor Rotation — It is important to be
certain compressor is rotating in the proper direction. To
determine whether or not compressor is rotating in the proper
direction:
1. Connect service gages to suction and discharge pressure
fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge
pressure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge
pressure does not rise to normal levels:
1. Turn off power to the unit. Install disconnect tag.
2. Reverse any two of the unit power leads.
3. Reapply power to the unit and verify pressures are correct.
The suction and discharge pressure levels should now move
to their normal start-up levels.
When the compressor is rotating in the wrong direction, the
unit makes an elevated level of noise and does not provide
cooling.
After a few minutes of reverse operation, the scroll compressor internal overload protection will open, thus activating
the unit lockout. This requires a manual reset. To reset, turn the
thermostat on and then off.
NOTE: There is a 5-minute time delay before the compressor
will start.
Unit Start-Up in Cooling Mode
1. Adjust the unit thermostat to the warmest position.
Slowly reduce the thermostat position until the compressor activates.
2. Check for cool air delivery at unit grille a few minutes
after the unit has begun to operate.
3. Verify that the compressor is on and that the water flow
rate is correct by measuring pressure drop through the
heat exchanger using pressure/temperature plugs. Check
the elevation and cleanliness of the condensate lines; any
dripping could be a sign of a blocked line. Be sure the
condensate trap includes a water seal.
22
Page 23
4. Check the temperature of both supply and discharge
water.
5. Air temperature drop across the coil should be checked
when compressor is operating. Air temperature drop
should be between –9.4 and –3.9 C.
Unit Start-Up in Heating Mode
NOTE: Operate the unit in heating cycle after checking the
cooling cycle. Allow 5 minutes between tests for the pressure
or reversing valve to equalize.
1. Turn thermostat to lowest setting and set thermostat
switch to HEAT position.
2. Slowly turn the thermostat to a higher temperature until
the compressor activates.
3. Check for warm air delivery at the unit grille within a few
minutes after the unit has begun to operate.
4. Check the temperature of both supply and discharge
water.
5. Air temperature rise across the coil should be checked
when compressor is operating. Air temperature rise
should be between –6.7 and –1.1 C after 15 minutes at
load.
6. Check for vibration, noise and water leaks.
Flow Regulation — Flow regulation can be accom-
plished by two methods. Most water control valves have a flow
adjustment built into the valve. By measuring the pressure drop
through the unit heat exchanger, the flow rate can be determined using Table 11. Adjust the water control valve until the
flow of 0.09 to 0.13 L/s is achieved. Since the pressure constantly varies, two pressure gages may be needed in some
applications.
An alternative method is to install a flow control device.
These devices are typically an orifice of plastic material designed to allow a specified flow rate that are mounted on the
outlet of the water control valve. Occasionally these valves
produce a velocity noise that can be reduced by applying
some back pressure. To accomplish this, slightly close the
leaving isolation valve of the well water setup.
WARNING
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until
flushing is completed.
Table 11 — Coaxial Water Pressure Drop
50HQP
UNIT
SIZE
072
096
120
L/s
0.6 8.3 6.2 3.4 2.1
0.9 22.8 19.114.512.4
1.3 42.7 36.529.026.2
0.8 45.4 14.511.7 9.0
1.1 68.1 36.531.024.8
1.5 90.9 64.154.545.5
0.9 56.8 27.622.115.2
1.4 85.2 59.349.637.9
1.9113.6100.083.467.6
PRESSURE DROP (kPa)
–1 C10 C21 C32 C
Flushing — Once the piping is complete, final purging and
loop charging is needed. A flush cart pump of at least 1.5 hp is
needed to achieve adequate flow velocity in the loop to purge
air and dirt particles from the loop. Flush the loop in both directions with a high volume of water at a high velocity. Cleaning
and flushing the piping system is the single most important step
to ensure proper start-up and continued efficient operation of
the system. Follow the steps below to properly flush the loop:
1. Verify power is off.
2. Install the system with the supply hose connected directly
to the return riser valve. Use a single length of flexible
hose.
3. Open all air vents. Fill the system with water. DO NOT
allow system to overflow. Bleed all air from the system.
Pressurize and check the system for leaks and repair as
appropriate.
4. Verify that all strainers are in place. Carrier recommends
a strainer with a no. 20 stainless steel wire mesh. Start the
pumps, and systematically check each vent to ensure that
all air is bled from the system.
5. Verify that make-up water is available. Adjust makeup
water as required to replace the air which was bled from
the system. Check and adjust the water/air level in the expansion tank.
6. Set the boiler to raise the loop temperature to approximately 30 C. Open a drain at the lowest point in the system. Adjust the make-up water replacement rate to equal
the rate of bleed.
7. Refill the system and add trisodium phosphate in a proportion of approximately 0.5 kg per 750 L of water (or
other equivalent approved cleaning agent). Reset the boiler to raise the loop temperature to 38 C. Circulate the solution for a minimum of 8 to 24 hours. At the end of this
period, shut off the circulating pump and drain the solution. Repeat system cleaning if desired.
8. When the cleaning process is complete, remove the shortcircuited hoses. Reconnect the hoses to the proper supply,
and return the connections to each of the units. Refill the
system and bleed off all air.
9. Test the system pH with litmus paper. The system water
should be in the range of pH 6.0 to 8.5 (see Table 2). Add
chemicals, as appropriate to maintain neutral pH levels.
10. When the system is successfully cleaned, flushed, refilled
and bled, check the main system panels, safety cutouts
and alarms. Set the controls to properly maintain loop
temperatures.
DO NOT use “Stop Leak” or similar chemical agent in
this system. Addition of chemicals of this type to the loop
water will foul the heat exchanger and inhibit unit operation.
11. Restore power.
Antifreeze may be added before, during or after the
flushing process. However, depending on when it is added
in the process, it can be wasted. Refer to the Antifreeze section for more detail.
Loop static pressure will fluctuate with the seasons. Pressures will be higher in the winter months than during the
warmer months. This fluctuation is normal and should be
considered when charging the system initially. Run the unit
in either heating or cooling for several minutes to condition
the loop to a homogenous temperature.
When complete, perform a final flush and pressurize the
loop to a static pressure of 275 to 345 kPa for winter months
or 100 to 140 kPa for summer months.
After pressurization, be sure to remove the plug from the
end of the loop pump motor(s) to allow trapped air to be
discharged and to ensure the motor housing has been flooded. Be sure the loop flow center provides adequate flow
through the unit by checking pressure drop across the heat
exchanger.
NOTE: Carrier strongly recommends all piping connections,
both internal and external to the unit, be pressure tested by an
appropriate method prior to any finishing of the interior space
23
Page 24
or before access to all connections is limited. Test pressure
may not exceed the maximum allowable pressure for the unit
and all components within the water system. Carrier will not
be responsible or liable for damages from water leaks due to
inadequate or lack of a pressurized leak test, or damages
caused by exceeding the maximum pressure rating during
installation.
Antifreeze — In areas where entering loop temperatures
drop below 4.4 C or where piping will be routed through areas
subject to freezing, antifreeze is needed.
Alcohols and glycols are commonly used as antifreeze
agents. Freeze protection should be maintained to 8.3° C below
the lowest expected entering loop temperature. For example, if
the lowest expected entering loop temperature is –1.1 C, the
leaving loop temperature would be –5.6 to –3.9 C. Therefore,
the freeze protection should be at –9.4 C (–1.1 C – 8.3 C =
–9.4 C).
IMPORTANT: All alcohols should be pre-mixed and
pumped from a reservoir outside of the building or introduced under water level to prevent alcohols from fuming.
Calculate the total volume of fluid in the piping system. See
Table 12. Use the percentage by volume in Table 13 to determine the amount of antifreeze to use. Antifreeze concentration
should be checked from a well mixed sample using a hydrometer to measure specific gravity.
FREEZE PROTECTION SELECTION — The –1.1 C FP1
factory setting (water) should be used to avoid freeze damage
to the unit.
Once antifreeze is selected, the JW3 jumper (FP1) should
be clipped on the control to select the low temperature
(antifreeze –12.2 C) set point to avoid nuisance faults.
Cooling Tower/Boiler Systems — These systems
typically use a common loop maintained at 15.6 C to 32.2 C.
The use of a closed circuit evaporative cooling tower with a
secondary heat exchanger between the tower and the water
loop is recommended. If an open type cooling tower is
used continuously, chemical treatment and filtering will be
necessary.
Table 12 — Approximate Fluid Volume (L)
per 30 M of Pipe
PIPEDIAMETER (in.) [mm] VOLUME (gal.) [L]
Copper1 [25.4]4.1 [15.5]
Rubber Hose1 [25.4]3.9 [14.8]
Polyethylene
LEGEND
IPS— Internal Pipe Size
SCH — Schedule
SDR — Standard Dimensional Ratio
NOTE: Volume of heat exchanger is approximately 3.78 liters.
Table 13 — Antifreeze Percentages by Volume
ANTIFREEZE
Methanol (%)25211610
100% USP Food Grade
Propylene Glycol (%)
Ethanol (%)29252014
1.25 [31.8]6.4 [24.2]
1.5 [38.1]9.2 [34.8]
3
/4 IPS SDR112.8 [10.6]
1 IPS SDR114.5 [17.0]
1
1
/4 IPS SDR118.0 [30.8]
1
/2 IPS SDR1110.9 [41.3]
2 IPS SDR1118.0 [68.1]
1
1
/4 IPS SCH408.3 [31.4]
1
/2 IPS SCH4010.9 [41.3]
1
2 IPS SCH4017.0 [64.4]
MINIMUM TEMPERATURE FOR FREEZE
–12.2–9.4–6.7–3.9
PROTECTION (C)
38302215
Ground Coupled, Closed Loop and Plateframe
Heat Exchanger Well Systems —
allow water temperatures from –1.1 to 43.3 C. The external
loop field is divided up into 51 mm polyethylene supply and
return lines. Each line has valves connected in such a way
that upon system start-up, each line can be isolated for flushing using only the system pumps. Air separation should be
located in the piping system prior to the fluid re-entering the
loop field.
These systems
OPERATION
Power Up Mode —
the inputs, terminals and safety controls are checked for
normal operation.
NOTE: The compressor will have a 5-minute anti-short
cycle upon power up.
The unit will not operate until all
Units with Aquazone™ Complete C Control
STANDBY — Y and W terminals are not active in Standby
mode, however the O and G terminals may be active, depending on the application. The compressor will be off.
COOLING — Y and O terminals are active in Cooling
mode. After power up, the first call to the compressor will
initiate a 5 to 80 second random start delay and a 5-minute
anti-short cycle protection time delay. After both delays are
complete, the compressor is energized.
NOTE: On all subsequent compressor calls the random start
delay is omitted.
HEATING STAGE 1 — Terminal Y is active in heating
stage 1. After power up, the first call to the compressor will
initiate a 5 to 80 second random start delay and a 5-minute
anti-short cycle protection time delay. After both delays are
complete, the compressor is energized.
NOTE: On all subsequent compressor calls the random start
delay is omitted.
HEATING STAGE 2 — To enter Stage 2 mode, terminal W
is active (Y is already active). Also, the G terminal must be
active or the W terminal is disregarded. The compressor relay will remain on and EH1 is immediately turned on. EH2
will turn on after 10 minutes of continual stage 2 demand.
NOTE: EH2 will not turn on (or if on, will turn off) if FP1
temperature is greater than 7.2 C and FP2 is greater than
43.3 C.
EMERGENCY HEAT — In emergency heat mode, termi-
nal W is active while terminal Y is not. Terminal G must be
active or the W terminal is disregarded. EH1 is immediately
turned on. EH2 will turn on after 5 minutes of continual
emergency heat demand.
Units with Aquazone Deluxe D Control
STANDBY/FAN ONLY — The compressor will be off.
The Fan Enable, Fan Speed, and reversing valve (RV) relays
will be on if inputs are present. If there is a Fan 1 demand,
the Fan Enable will immediately turn on. If there is a Fan 2
demand, the Fan Enable and Fan Speed will immediately
turn on.
NOTE: DIP switch 5 on S1 does not have an effect upon
Fan 1 and Fan 2 outputs.
HEATING STAGE 1 — In Heating Stage 1 mode, the Fan
Enable and Compressor relays are turned on immediately.
Once the demand is removed, the relays are turned off and
the control reverts to Standby mode. If there is a master/
slave or dual compressor application, all compressor relays
and related functions will operate per their associated DIP
switch 2 setting on S1.
HEATING STAGE 2 — In Heating Stage 2 mode, the Fan
Enable and Compressor relays are remain on. The Fan
Speed relay is turned on immediately and turned off
24
Page 25
immediately once the demand is removed. The control reverts to Heating Stage 1 mode. If there is a master/slave or
dual compressor application, all compressor relays and related functions will operate per their associated DIP switch
2 setting on S1.
HEATING STAGE 3 — In Heating Stage 3 mode, the Fan
Enable, Fan Speed and Compressor relays remain on. The
EH1 output is turned on immediately. With continuing Heat
Stage 3 demand, EH2 will turn on after 10 minutes. EH1
and EH2 are turned off immediately when the Heating Stage
3 demand is removed. The control reverts to Heating Stage
2 mode.
Output EH2 will be off if FP1 is greater than 7.2 C AND
FP2 (when shorted) is greater than 43.3 C during Heating
Stage 3 mode. This condition will have a 30-second
recognition time. Also, during Heating Stage 3 mode, EH1,
EH2, Fan Enable, and Fan Speed will be ON if G input is
not active.
EMERGENCY HEAT — In Emergency Heat mode, the
Fan Enable and Fan Speed relays are turned on. The EH1
output is turned on immediately. With continuing Emergency Heat demand, EH2 will turn on after 5 minutes. Fan Enable and Fan Speed relays are turned off after a 60-second
delay. The control reverts to Standby mode.
Output EH1, EH2, Fan Enable, and Fan Speed will be
ON if the G input is not active during Emergency Heat
mode.
COOLING STAGE 1 — In Cooling Stage 1 mode, the Fan
Enable, compressor and RV relays are turned on immediately. If configured as stage 2 (DIP switch set to OFF) then the
compressor and fan will not turn on until there is a stage 2
demand. The Fan Enable and compressor relays are turned
off immediately when the Cooling Stage 1 demand is removed. The control reverts to Standby mode. The RV relay
remains on until there is a heating demand. If there is a master/slave or dual compressor application, all compressor relays and related functions will track with their associated
DIP switch 2 on S1.
COOLING STAGE 2 — In Cooling Stage 2 mode, the Fan
Enable, compressor and RV relays remain on. The Fan
Speed relay is turned on immediately and turned off once
the Cooling Stage 2 demand is removed. The control reverts
to Cooling Stage 1 mode. If there is a master/slave or dual
compressor application, all compressor relays and related
functions will track with their associated DIP switch 2 on
S1.
NIGHT LOW LIMIT (NLL) STAGED HEATING — In
NLL staged Heating mode, the override (OVR) input becomes active and is recognized as a call for heating and the
control will immediately go into a Heating Stage 1 mode.
With an additional 30 minutes of NLL demand, the control
will go into Heating Stage 2 mode. With another additional
30 minutes of NLL demand, the control will go into Heating
Stage 3 mode.
SYSTEM TEST
System testing provides the ability to check the control
operation. The control enters a 20-minute Test mode by momentarily shorting the test pins. All time delays are increased 15 times.
Test Mode — To enter Test mode on Complete C or De-
luxe D controls, cycle the fan 3 times within 60 seconds. The
LED (light-emitting diode) will flash a code representing the
last fault when entering the Test mode. The alarm relay will
also power on and off during Test mode. See Tables 14-16. To
exit Test mode, short the terminals for 3 seconds or cycle the
power 3 times within 60 seconds.
NOTE: The Deluxe D control has a flashing code and alarm
relay cycling code that will both have the same numerical
label. For example, flashing code 1 will have an alarm relay
cycling code 1. Code 1 indicates the control has not faulted
since the last power off to power on sequence.
Retry Mode — In Retry mode, the status LED will start to
flash slowly to signal that the control is trying to recover from
an input fault. The control will stage off the outputs and try to
again satisfy the thermostat used to terminal Y. Once the thermostat input calls are satisfied, the control will continue normal
operation.
NOTE: If 3 consecutive faults occur without satisfying the
thermostat input call to terminal Y, the control will go into
lockout mode. The last fault causing the lockout is stored in
memory and can be viewed by entering Test mode.
Aquazone™ Deluxe D Control LED Indicators —
STATUS LED — Status LED indicates the current status or
mode of the Deluxe D control. The Status LED light is green.
TEST LED — Test LED will be activated any time the Deluxe D control is in Test mode. The Test LED light is yellow.
FAULT LED — Fault LED light is red. The fault LED will
always flash a code representing the last fault in memory. If
there is no fault in memory, the fault LED will flash code 1 on
the and appear as 1 fast flash alternating with a 10-second
pause. See Table 16.
Flashing Code 1 Test Mode — No fault in memoryCycling Code 1
Flashing Code 2 Test Mode — HP Fault in memoryCycling Code 2
Flashing Code 3 Test Mode — LP Fault in memoryCycling Code 3
Flashing Code 4 Test Mode — FP1 Fault in memoryCycling Code 4
Flashing Code 5 Test Mode — FP2 Fault in memoryCycling Code 5
Flashing Code 6 Test Mode — CO Fault in memoryCycling Code 6
Flashing Code 7
Flashing Code 8Test Mode — PM in memoryCycling Code 8
Flashing Code 9
CO — Condensate Overflow
FP — Freeze Protection
HP — High Pressure
LED — Light-Emitting Diode
LP — Low Pressure
PM — Performance Monitor
NOTES:
1. Slow flash is 1 flash every 2 seconds.
2. Fast flash is 2 flashes every 1 second.
3. EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes followed
There are 3 LED indicators on the Deluxe D control:
Table 14 — Complete C Control Current LED
Status and Alarm Relay Operations
LED STATUSDESCRIPTION OF OPERATIONALARM RELAY
Normal ModeOpen
On
Off
Slow Flash
Fast FlashLockoutClosed
LEGEND
by a 10-second pause. This sequence will repeat continually until the
fault is cleared.
Normal Mode with
PM Warning
Complete C Control is
non-functional
Fault RetryOpen
Over/Under Voltage Shutdown
Test Mode — Over/Under
shutdown in memory
Test Mode — FP1/FP2
Swapped fault in memory
Cycle
(closed 5 sec.,
Open 25 sec.)
Open
Open
(Closed after
15 minutes)
Cycling Code 7
Cycling Code 9
25
Page 26
Table 15 — Complete C Control LED Code and
Fault Descriptions
LED
CODE
1No fault in memoryThere has been no fault since the last power-down to power-up sequence
2High-Pressure SwitchHP open instantly
3Low-Pressure SwitchLP open for 30 continuous seconds before or during a call (bypassed for first 60 seconds)
4Freeze Protection Coax — FP1FP1 below Temp limit for 30 continuous seconds (bypassed for first 60 seconds of operation)
5Freeze Protection Air Coil — FP2FP2 below Temp limit for 30 continuous seconds (bypassed for first 60 seconds of operation)
6Condensate overflowSense overflow (grounded) for 30 continuous seconds
7
(Autoreset)
FP — Freeze Protection
HP — High Pressure
LED — Light-Emitting Diode
LP — Low Pressure
PM — Performance Monitor
Over/Under Voltage Shutdown"R" power supply is <19VAC or >30VAC
8PM WarningPerformance Monitor Warning has occurred.
9FP1 and FP2 Thermistors are swapped FP1 temperature is higher than FP2 in heating/test mode, or FP2 temperature is higher than FP1 in cooling/
LEGEND
FAULTDESCRIPTION
test mode.
Table 16 — Aquazone™ Deluxe D Control Current LED Status and Alarm Relay Operations
DESCRIPTION
Normal ModeOnOffFlash Last Fault Code in MemoryOpen
Normal Mode with PMOnOffFlashing Code 8
Deluxe D Control is
non-functional
Test Mode—OnFlash Last Fault Code in MemoryCycling Appropriate Code
Night SetbackFlashing Code 2—Flash Last Fault Code in Memory—
ESDFlashing Code 3—Flash Last Fault Code in Memory—
Invalid T-stat InputsFlashing Code 4—Flash Last Fault Code in Memory—
No Fault in MemoryOnOffFlashing Code 1Open
1. If there is no fault in memory, the Fault LED will flash code 1.
2. Codes will be displayed with a 10-second Fault LED pause.
3. Slow flash is 1 flash every 2 seconds.
4. Fast flash is 2 flashes every 1 second.
5. EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes followed by a 10-second pause. This sequence will repeat continually
until the fault is cleared.
SERVICE
Perform the procedures outlined below periodically, as
indicated.
IMPORTANT: When a compressor is removed from this
unit, system refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, the refrigerant
lines of the compressor must be sealed after it is removed.
IMPORTANT: All refrigerant discharged from this unit
must be recovered without exception. Technicians must follow industry accepted guidelines and all local, state and federal statutes for the recovery and disposal of refrigerants.
IMPORTANT: To avoid the release of refrigerant into the
atmosphere, the refrigerant circuit of this unit must only be
serviced by technicians which meet local, state and federal
proficiency requirements.
IMPORTANT: To prevent injury or death due to electrical
shock or contact with moving parts, open unit disconnect
switch before servicing unit.
26
Page 27
Filters — Filters must be clean for maximum performance.
Fig. 22 — Gravity Flow Method
a50-8586
Inspect filters every month under normal operating conditions.
replace when necessary.
IMPORTANT: Units should never be operated without a filter.
Washable, high efficiency, electrostatic filters, when dirty,
can exhibit a very high pressure drop for the fan motor and reduce air flow, resulting in poor performance. It is especially important to provide consistent washing of these filters (in the opposite direction of the normal air flow) once per month using a
high pressure wash.
Water Coil — Keep all air out of the water coil. Check
open loop systems to be sure the well head is not allowing air
to infiltrate the water line. Always keep lines airtight.
DIRECT GROUND WATER APPLICATIONS — If the
system is installed in an area with a known high mineral content (125 ppm or greater) in the water, it is best to establish a
periodic maintenance schedule with the owner so the coil can
be checked regularly.
Should periodic coil cleaning be necessary, use standard
coil cleaning procedures, which are compatible with the heat
exchanger material and copper water lines. Generally, the more
water flowing through the unit, the less chance for scaling.
Therefore, 1.6 L/m per kW is recommended as a minimum
flow. Minimum flow rate for entering water temperatures below 10.0 C is 2.2 L/m per kW.
ALL OTHER WATER LOOP APPLICATIONS — Generally, water coil maintenance is not needed for closed loop systems. However, if the piping is known to have high dirt or debris content, it is best to establish a periodic maintenance
schedule with the owner so the water coil can be checked regularly. Dirty installations are typically the result of deterioration
of iron or galvanized piping or components in the system.
Open cooling towers requiring heavy chemical treatment and
mineral buildup through water use can also contribute to higher
maintenance. Should periodic coil cleaning be necessary, use
standard coil cleaning procedures, which are compatible with
both the heat exchanger material and copper water lines. Generally, the more water flowing through the unit, the less chance
for scaling. However, flow rates over 3.9 L/m per kW can produce water (or debris) velocities that can erode the heat exchanger wall and ultimately produce leaks.
IMPORTANT: To avoid fouled machinery and extensive
unit clean-up, DO NOT operate units without filters in
place. DO NOT use equipment as a temporary heat source
during construction.
Condensate Drain Pans — Check condensate drain
pans for algae growth twice a year. If algae growth is apparent,
consult a water treatment specialist for proper chemical treatment. The application of an algaecide every three months will
typically eliminate algae problems in most locations.
Refrigerant System — Verify air and water flow rates
are at proper levels before servicing. To maintain sealed circuitry integrity, do not install service gages unless unit operation
appears abnormal.
Condensate Drain Cleaning — Clean the drain line
and unit drain pan at the start of each cooling season. Check
flow by pouring water into drain. Be sure trap is filled to maintain an air seal.
Air Coil Cleaning — Remove dirt and debris from evap-
orator coil as required by condition of the coil. Clean coil with
a stiff brush, vacuum cleaner, or compressed air. Use a fin
comb of the correct tooth spacing when straightening mashed
or bent coil fins.
Condenser Cleaning — Water-cooled condensers may
require cleaning of scale (water deposits) due to improperly
maintained closed-loop water systems. Sludge build-up may
need to be cleaned in an open water tower system due to
induced contaminants.
Local water conditions may cause excessive fouling or
pitting of tubes. Condenser tubes should therefore be cleaned at
least once a year, or more often if the water is contaminated.
Proper water treatment can minimize tube fouling and
pitting. If such conditions are anticipated, water treatment
analysis is recommended. Refer to the Carrier System Design
Manual, Part 5, for general water conditioning information.
CAUTION
Follow all safety codes. Wear safety glasses and rubber
gloves when using inhibited hydrochloric acid solution.
Observe and follow acid manufacturer’s instructions. Failure to follow these safety precautions could result in personal injury or equipment or property damage.
Clean condensers with an inhibited hydrochloric acid solution. The acid can stain hands and clothing, damage concrete,
and, without inhibitor, damage steel. Cover surroundings to
guard against splashing. Vapors from vent pipe are not harmful,
but take care to prevent liquid from being carried over by the
gases.
Warm solution acts faster, but cold solution is just as effective if applied for a longer period.
GRAVITY FLOW METHOD — Do not add solution faster
than vent can exhaust the generated gases.
When condenser is full, allow solution to remain overnight,
then drain condenser and flush with clean water. Follow acid
manufacturer’s instructions. See Fig. 22.
FORCED CIRCULATION METHOD — Fully open vent
pipe when filling condenser. The vent may be closed when
condenser is full and pump is operating. See Fig. 23.
Regulate flow to condenser with a supply line valve. If
pump is a nonoverloading type, the valve may be fully closed
while pump is running.
FILL CONDENSER WITH
CLEANING SOLUTION. DO
NOT ADD SOLUTION
MORE RAPIDLY THAN
VENT CAN EXHAUST
GASES CAUSED BY
CHEMICAL ACTION.
VENT
PIPE
1.0 TO 1.2 m
PAI L
1-IN.
(25 mm)
PIPE
1.5 m APPROX
FUNNEL
PAI L
CONDENSER
27
Page 28
Refrigerant Charging
Fig. 23 — Forced Circulation Method
SUCTION
PUMP
SUPPORT
TANK
FINE MESH
SCREEN
RETURN
GAS VENT
PUMP
PRIMING
CONN.
GLOBE
VALV ES
SUPPLY
1-IN.
(25 mm)
PIPE
CONDENSER
REMOVE WATER
REGULATING VALVE
WARNING
To prevent personal injury, wear safety glasses and gloves
when handling refrigerant. Do not overcharge system —
this can cause compressor flooding.
NOTE: Do not vent or depressurize unit refrigerant to atmosphere. Remove and recover refrigerant following accepted
practices.
Air Coil Fan Motor Removal
CAUTION
Before attempting to remove fan motors or motor mounts,
place a piece of plywood over evaporator coils to prevent
coil damage.
For average scale deposit, allow solution to remain in condenser overnight. For heavy scale deposit, allow 24 hours.
Drain condenser and flush with clean water. Follow acid manufacturer’s instructions.
Compressor — Conduct annual amperage checks to in-
sure that amp draw is no more than 10% greater than indicated
on the serial plate data.
Fan Motors — All units have lubricated fan motors. Fan
motors should never be lubricated unless obvious, dry operation is suspected. Periodic maintenance oiling is not recommended, as it will result in dirt accumulating in the excess oil
and cause eventual motor failure. Conduct annual dry operation check and amperage check to ensure amp draw is no more
than 10% greater than indicated on serial plate data.
Belt — Check that the belt is tight. Retighten if needed. Re-
place if it is split or cracked.
Air Coil — The air coil must be cleaned to obtain maximum
performance. Check once a year under normal operating conditions and, if dirty, brush or vacuum clean. Care must be taken
not to damage the aluminum fins while cleaning.
Checking System Charge — Units are shipped with
full operating charge. If recharging is necessary:
1. Insert thermometer bulb in insulating rubber sleeve on
liquid line near filter drier. Use a digital thermometer for
all temperature measurements. DO NOT use a mercury
or dial-type thermometer.
2. Connect pressure gage to discharge line near compressor.
3. After unit conditions have stabilized, read head pressure
on discharge line gage.
NOTE: Operate unit a minimum of 15 minutes before
checking charge.
4. From standard field-supplied Pressure-Temperature chart
for R-410A, find equivalent saturated condensing
temperature.
5. Read liquid line temperature on thermometer; then
subtract from saturated condensing temperature. The difference equals subcooling temperature.
Motor power wires need to be disconnected from motor
terminals before motor is removed from unit.
1. Shut off unit main power supply.
2. Loosen bolts on mounting bracket so that fan belt can be
removed.
3. Loosen and remove the 2 motor mounting bracket bolts
on left side of bracket.
4. Slide motor/bracket assembly to extreme right and lift out
through space between fan scroll and side frame. Rest
motor on a high platform such as a step ladder. Do not
allow motor to hang by its power wires.
Blower Fan Sheaves — Factory-supplied drives are
pre-aligned and tensioned, however, it is recommended that the
belt tension and alignment be checked before starting the unit.
Always check the drive alignment after adjusting belt tension.
Sheave and belt information is shown in Table 17.
Each factory-assembled fan, shaft, and drive sheave assembly is precision aligned and balanced. If excessive unit
vibration occurs after field replacement of sheaves, the unit
should be rebalanced. To change the drive ratio, follow the
steps in the Blower Fan Performance Adjustment section.
After 1 to 3 minutes of operation, check the belt tension.
Also check tension frequently during the first 24 hours of operation and adjust if necessary. Periodically check belt tension
throughout the run-in period, which is normally the initial
72 hours of operation.
ALIGNMENT — Make sure that fan shafts and motor shafts
are parallel and level. The most common causes of misalignment are nonparallel shafts and improperly located sheaves.
Where shafts are not parallel, belts on one side are drawn tighter and pull more than their share of the load. As a result, these
belts wear out faster, requiring the entire set to be replaced before it has given maximum service. If misalignment is in the
sheave, belts enter and leave the grooves at an angle, causing
excessive belt and sheave wear.
Shaft Alignment
distance between the shafts at 3 or more locations. If the distances are equal, then the shafts are parallel.
Sheave Alignment
1. To check the location of the fixed sheaves on the shafts,
use a straightedge or a piece of string. If the sheaves are
properly aligned, the string will touch them at the points
indicated by the arrows in Fig. 24. Rotate each sheave a
half revolution to determine whether the sheave is wobbly or the drive shaft is bent. Correct any misalignment.
2. With sheaves aligned, tighten cap screws evenly and
progressively.
— Check shaft alignment by measuring the
28
Page 29
NOTE: There should be a 3 to 6 mm gap between the
Fig. 24 — Sheave Alignment
a50-7135tf
BELT SPAN
LB FORCE
DEFLECTION
Fig. 25 — Fan Belt Tension
a50-7136ef
mating part hub and the bushing flange. If the gap is
closed, the bushing is probably the wrong size.
3. With taper-lock bushed hubs, be sure the bushing bolts
are tightened evenly to prevent side-to-side pulley wobble. Check by rotating sheaves and rechecking sheave
alignment. When substituting field-supplied sheaves for
factory-supplied sheaves, only the motor sheave should
be changed.
Blower Fan Performance Adjustment — The
unit is supplied with variable sheave drive on the fan motor to
adjust for differing airflows at various ESP conditions. Select
an airflow requirement on the left side of the table, then move
horizontally to right under the required ESP for the sheave
turns open, rpm and horsepower for that condition. Fully
closed, the sheave will produce the highest static capability
(higher rpm).
To change fan speeds from factory settings:
1. Shut off unit power supply.
2. Remove belt from motor sheave.
3. Lift motor assembly.
4. Loosen the
5
/16-in. hex nuts on the grommet motor adjustment bolts (2 per bolt). To increase the belt tension loosen
the top hex nut. To decrease the belt tension loosen the
bottom hex nut.
5. Turn the bolts by hand to the desired position then tighten
5
the
/16-in. hex nuts ( 2 per bolt).
6. Lower the motor assembly.
7. Install the belt.
8. Tension the belt per section below.
9. Restore power to the unit.
BELT TENSION ADJUSTMENT — Using a gage, apply
4 lb of force to the center of the belt and adjust the tension until
a deflection of
1
/64-in. is achieved for every inch of shaft center
distance. See Fig. 25.
Ideal belt tension is the lowest value under which belt slip
will not occur at peak load conditions.
UNIT SIZE
50HQP
BLOWER SHEAVEBK67 X 1BK85 X 1BK67 X 1
072
096
120
*Airflow configurations J, K, N, and P.
†Airflow configurations Q, T, U, and V.
**Airflow configurations W, X, Z, and 1.
MOTOR SHEAVE1VP34 X 7/81VP34 X 7/81VP44 X 7/8
BLOWER SHEAVEBK67 X 1BK77 X 1BK62 X 1
MOTOR SHEAVE 1VP40 X 7/81VP34 X 7/81VP44 X 7/8
BLOWER SHEAVEBK67 X 1BK67 X 1BK67 X 1
MOTOR SHEAVE1VP44 X 7/81VP34 X 7/81VP50 X 7/8
Table 17 — Blower Sheave and Belt Specifications
COMPONENT
MOTOR HP111
BELTB X 46B X 50B X 48
MOTOR HP222
BELTB X 46B X 48B X 46
MOTOR HP333
BELTB X 48B X 46B X 48
A* B† C**
29
DRIVE PACKAGE
Page 30
TROUBLESHOOTING
Fig. 26 — Thermistor Nominal Resistance
a50-8163
LEGEND
Fig. 27 — FP1 and FP2 Thermistor Location
COAX — Coaxial Heat Exchanger
Airflow
Refrigerant Liquid Line Flow
SUCTIO N
COMPRESSOR
DISCHARGE
COAX
EXP ANSION
VA LV E
FP 2
FP 1
LIQUI D
LIN E
WA TER IN
WA TER OUT
CONDENSA TE
OVERFLO W
(CO)
AIR COI L
FREEZ E
PROTECTIO N
WA TE R
COI L
PROTECTIO N
THERMIST OR
( °C)
( °C)
AI R
COI L
AIRFLOW
AIRFLO W
When troubleshooting problems with a WSHP, see
Table 18.
Thermistor — A thermistor may be required for single-
phase units where starting the unit is a problem due to low
voltage. See Fig. 26 for thermistor nominal resistance.
Control Sensors — The control system employs 2 nom-
inal 10,000 ohm thermistors (FP1 and FP2) that are used for
freeze protection. Be sure FP1 is located in the discharge fluid
and FP2 is located in the air discharge. See Fig. 27.
90.0
80.0
70.0
60.0
50.0
40.0
30.0
Resistance (kOhm)
20.0
10.0
0.0
-17.7-6.64.415.626.737.848.960.0
Temperature (C)
30
Page 31
Table 18 — Troubleshooting
FAULTHEATING COOLINGPOSSIBLE CAUSESOLUTION
Main Power ProblemsXXGreen Status LED OffCheck line voltage circuit breaker and disconnect.
Check for line voltage between L1 and L2 on the contactor.
Check for 24-vac between R and C on controller.
Check primary/secondary voltage on transformer.
HP Fault — Code 2
High Pressure
XReduced or no airflow in
XAir temperature out of range
XXOvercharged with refrigerant Check superheat/subcooling vs. typical operating condition.
XXBad HP switchCheck switch continuity and operation. Replace.
LP Fault — Code 3
Low Pressure/Loss of
Charge
FP1 Fault — Code 4
Water Freeze Protection
FP2 Fault — Code 5
Air Coil Freeze
Protection
Condensate Fault —
Code 6
Over/Under Voltage —
Code 7
(Auto Resetting)
Performance Monitor —
Code 8
No Fault Code ShownXXCompressor overloadCheck and replace if necessary.
Unit Short CyclesXXDirty air filterCheck and clean air filter.
Only Fan RunsXXThermostat positionEnsure thermostat set for heating or cooling operation.
LEGEND
FP— Freeze Protection
HP — High Pressure
LED — Light-Emitting Diode
LP— Low Pressure
RV— Reversing Valve
XXInsufficient chargeCheck for refrigerant leaks.
XCompressor pump down at
XReduced or no water flow in
XInadequate antifreeze level Check antifreeze density with hydrometer.
XImproper freeze protect set-
XWater temperature out of
XXBad thermistorCheck temperature and impedance correlation.
XXBad thermistorCheck temperature and impedance correlation.
XXBlocked drainCheck for blockage and clean drain.
XXImproper trapCheck trap dimensions and location ahead of vent.
XXUnder voltageCheck power supply and 24-vac voltage before and during operation.
XXOver voltageCheck power supply voltage and 24 vac before and during operation.
XHeating mode FP2>
XXControl boardReset power and check operation.
XXUnit in Test modeReset power or wait 20 minutes for auto exit.
XXUnit selectionUnit may be oversized for space. Check sizing for actual load of space.
XXCompressor overloadCheck and replace if necessary.
XXUnit locked outCheck for lockout codes. Reset power.
XXCompressor overloadCheck compressor overload. Replace if necessary.
XXThermostat wiringCheck Y and W wiring at heat pump. Jumper Y and R for compressor
XReduced or no water flow in
cooling
XWater temperature out of
range in cooling
heating
in heating
start-up
heating
ting (
–1.1 Cvs –12.2 C)
range
XReduced or no airflow in
cooling
XAir temperature out of range Too much cold vent air. Bring entering-air temperature within design
XImproper freeze protect set-
ting (–1.1 Cvs –12.2 C)
XPoor drainageCheck for piping slope away from unit.
XMoisture on sensorCheck for moisture shorting to air coil.
XCooling mode FP1> 51.7 C
OR FP2< 4.4 C
Check pump operation or valve operation/setting.
Check water flow adjust to proper flow rate.
Bring water temperature within design parameters.
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
Dirty air coil — construction dust, etc. Perform preventative mainte-
nance; Clean air coil.
High external static. Check duct design and downstream interference.
Bring return-air temperature within design parameters.
Check charge and start-up water flow.
Check pump operation or water valve operation/setting.
Plugged strainer or filter. Clean or replace.
Check water flow adjust to proper flow rate.
Clip JW3 jumper for antifreeze (–12.2 C) use.
Bring water temperature within design parameters.
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
High external static. Check duct design and downstream interference.
parameters.
Normal airside applications will require –1.1 C only.
Check slope of unit toward outlet.
Poor venting. Check vent location.
Check power supply wire size.
Check compressor starting.
Check 24-vac and unit transformer tap for correct power supply voltage.
Check 24-vac and unit transformer tap for correct power supply voltage.
51.7 C Check for poor airflow or overcharged unit.
Check for poor water flow or airflow.
operation in Test mode.
31
Page 32
Table 18 — Troubleshooting (cont)
FAULTHEATING COOLINGPOSSIBLE CAUSESOLUTION
Only Compressor RunsXXThermostat wiringCheck G wiring at heat pump. Jumper G and R for fan operation.
Check Y and W wiring at heat pump. Jumper Y and R for compressor
XXFan motor relayJumper G and R for fan operation. Check for line voltage across BR
Unit Does Not Operate in
Cooling
Insufficient Capacity/
Not Cooling or Heating
Properly
High Head PressureXReduced or no airflow in
Low Suction PressureXReduced water flow in
Low Discharge Air
Temperature in Heating
High HumidityXToo high airflowCheck blower.
LEGEND
FP— Freeze Protection
HP — High Pressure
LED — Light-Emitting Diode
LP— Low Pressure
RV— Reversing Valve
XXFan motorCheck for line voltage at motor. Check capacitor.
XXDir ty filterReplace or clean.
XReduced or no airflow in
XXLeaky ductworkCheck supply and return-air temperatures at the unit and at distant
XXLow refrigerant chargeCheck superheat and subcooling.
XXRestricted metering device Check superheat and subcooling. Replace.
XXThermostat improperly
XXUnit undersizedRecheck loads and sizing check sensible cooling load and heat pump
XXScaling in water heat
XXInlet water too hot or coldCheck load, loop sizing, loop backfill, ground moisture.
XAir temperature out of range
XXUnit overchargedCheck superheat and subcooling. Reweigh in charge.
XXNon-condensables in
XXRestricted metering device Check superheat and subcooling. Replace.
XWater temperature out of
XXInsufficient chargeCheck for refrigerant leaks.
XToo high airflowCheck blower.
XPoor performanceSee ‘Insufficient Capacity’ above.
XReversing valveSet for cooling demand and check 24-vac on RV coil and at control.
XThermostat setupCheck for ‘O’ RV setup not ‘B’.
XThermostat wiringCheck O wiring at heat pump. Jumper O and R for RV coil.
heating
XReduced or no airflow in
cooling
XDefective reversing valvePerform RV touch test.
located
exchanger
heating
XReduced or no water flow in
cooling
XInlet water too hotCheck load, loop sizing, loop backfill, ground moisture.
in heating
XScaling in water heat
exchanger
system
heating
range
XReduced airflow in coolingCheck for dirty air filter and clean or replace.
XAir temperature out of range Too much cold vent air. Bring entering air temperature within design
XUnit oversizedRecheck loads and sizing check sensible cooling load and heat pump
operation in Test mode.
contacts.
Check fan power enable relay operation (if present).
If RV is stuck, run high pressure up by reducing water flow and while
operating engage and disengage RV coil voltage to push valve.
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
High external static. Check duct design and downstream interference.
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
High external static. Check duct design and downstream interference.
duct registers if significantly different, duct leaks are present.
Check location and for air drafts behind thermostat.
capacity.
Perform scaling check and clean if necessary.
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
High external static. Check duct design and downstream interference.
Check pump operation or valve operation/setting.
Check water flow adjust to proper flow rate.
Bring return-air temperature within design parameters.
Perform scaling check and clean if necessary.
Vacuum system and reweigh in charge.
Check pump operation or water valve operation/setting.
Plugged strainer or filter. Clean or replace.
Check water flow adjust to proper flow rate.
Bring water temperature within design parameters.
Check fan motor operation and airflow restrictions.
High external static. Check duct design and downstream interference.
parameters.
capacity.
32
Page 33
Page 34
Copyright 2010 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500077-01Printed in U.S.A.Form 50HQP-C1SIPg 3411-10Replaces: New