Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or
other conditions which may cause personal injury or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The
qualified installer or agency must use factory-authorized kits or
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500077-01Printed in U.S.A.Form 50HQP-C1SIPg 111-10Replaces: New
accessories when modifying this product. Refer to the
individual instructions packaged with the kits or accessories
when installing.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for brazing operations. Have fire
extinguisher available. Read these instructions thoroughly and
follow all warnings or cautions attached to the unit. Consult
local building codes and the National Electrical Code (NEC)
for special installation requirements.
Understand the signal words — DANGER, WARNING,
and CAUTION. DANGER identifies the most serious hazards
which will result in severe personal injury or death. WARNING signifies hazards that could result in personal injury or
death. CAUTION is used to identify unsafe practices, which
would result in minor personal injury or product and property
damage.
Recognize safety information. This is the safety-alert
symbol (). When you see this symbol on the unit and in
instructions or manuals, be alert to the potential for personal
injury.
WARNING
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work
is completed.
CAUTION
This system uses R-410A, which has higher pressures than
R-22 and other refrigerants. No other refrigerant may be
used in this system. Suction tubing design pressure is
3068 kPa and liquid tubing design pressure is 4522 kPa.
Failure to use gage set, hoses, and recovery systems
designed to handle R-410A refrigerant may result in personal injury and equipment damage. If unsure about equipment, consult the equipment manufacturer.
GENERAL
This Installation and Start-Up Instructions literature is for
Aquazone™ water source heat pump systems with Puron refrigerant.
Water source heat pumps (WSHPs) are single-package horizontally and vertically mounted units with electronic controls
designed for year-round cooling and heating.
IMPORTANT: The installation of water source heat pump
units and all associated components, parts, and accessories
which make up the installation shall be in accordance with
the regulations of ALL authorities having jurisdiction and
MUST conform to all applicable codes. It is the responsibility of the installing contractor to determine and comply
with ALL applicable codes and regulations.
INSTALLATION
Step 1 — Check Jobsite —
maintenance instructions are provided with each unit. Before
unit start-up, read all manuals and become familiar with the
unit and its operation. Thoroughly check out the system before
operation. Complete the inspections and instructions listed
below to prepare a unit for installation. See Table 1 for unit
physical data.
Horizontal units are designed for indoor installation only.
Be sure to allow adequate space around the unit for servicing.
Installation, operation and
See Fig. 1 for overall unit dimensions. Refer to Fig. 2 for an example of a typical horizontal installation.
CAUTION
To avoid equipment damage, do not use these units as a
source of heating or cooling during the construction process. The mechanical components and filters used in these
units quickly becomes clogged with construction dirt and
debris which may cause system damage.
Step 2 — Check Unit — Upon receipt of shipment at
the jobsite, carefully check the shipment against the bill of
lading. Make sure all units have been received. Inspect the carton or crating of each unit, and inspect each unit for damage.
Ensure the shipping company makes proper notation of any
shortages or damage on all copies of the freight bill. Concealed
damage not discovered during unloading must be reported to
the shipping company within 15 days of receipt of shipment.
NOTE: It is the responsibility of the purchaser to file all
necessary claims with the shipping company.
1. Verify unit is correct model for entering water temperature of job.
2. Be sure that the location chosen for unit installation provides ambient temperatures maintained above freezing.
Well water applications are especially susceptible to
freezing.
3. Be sure the installation location is isolated from sleeping
areas, private offices and other acoustically sensitive
spaces.
NOTE: A sound control accessory package may be used
to help eliminate sound in sensitive spaces.
4. Check local codes to be sure a secondary drain pan is not
required under the unit.
5. Be sure unit is mounted at a height sufficient to provide
an adequate slope of the condensate lines. If an appropriate slope cannot be achieved, a field-supplied condensate
pump may be required.
6. Provide sufficient space for duct connection.
7. Provide adequate clearance for filter replacement and
drain pan cleaning. Do not allow piping, conduit, etc. to
block filter access.
8. Provide sufficient access to allow maintenance and
servicing of the fan and fan motor, compressor and coils.
Removal of the entire unit from the closet should not be
necessary.
9. Provide an unobstructed path to the unit within the closet
or mechanical room. Space should be sufficient to allow
removal of unit if necessary.
10. Provide ready access to water valves and fittings, and
screwdriver access to unit side panels, discharge collar,
and all electrical connections.
11. Where access to side panels is limited, pre-removal of the
control box side mounting screws may be necessary for
future servicing.
STORAGE — If the equipment is not needed for immediate
installation upon its arrival at the jobsite, it should be left in its
shipping carton and stored in a clean, dry area of the building
or in a warehouse. Units must be stored in an upright position
at all times. If carton stacking is necessary, stack units a
maximum of 3 high. Do not remove any equipment from its
shipping package until it is needed for installation.
PROTECTION — Once the units are properly positioned on
the jobsite, they must be covered with either a shipping carton,
vinyl film, or an equivalent protective covering. Open ends of
pipes stored on the jobsite must be capped. This precaution is
2
especially important in areas where painting, plastering, or
spraying of fireproof material, etc. is not yet complete. Foreign
material that is allowed to accumulate within the units can prevent proper start-up and necessitate costly clean-up operations.
Before installing any of the system components, be sure to
examine each pipe, fitting, and valve, and remove any dirt or
foreign material found in or on these components.
CAUTION
3. Verify that the unit’s refrigerant tubing is free of kinks or
dents, and that it does not touch other unit components.
4. Inspect all electrical connections. Be sure connections are
clean and tight at their terminations.
5. Loosen compressor bolts until the compressor rides freely
on springs. Remove shipping restraints.
6. Remove the four 6 mm (
1
/4 in.) shipping bolts from compressor support plate (two bolts on each side) to maximize vibration and sound alternation.
DO NOT store or install units in corrosive environments or
CAUTION
in locations subject to temperature or humidity extremes
(e.g., attics, garages, rooftops, etc.). Corrosive conditions
and high temperature or humidity can significantly reduce
performance, reliability, and service life. Always move
Failure to remove shipping brackets from spring-mounted
compressors will cause excessive noise and could cause
component failure due to added vibration.
units in an upright position. Tilting units on their sides may
cause equipment damage.
7. Remove any blower support cardboard from inlet of the
blower.
INSPECT UNIT — To prepare the unit for installation, complete the procedures listed below:
1. Compare the electrical data on the unit nameplate with
ordering and shipping information to verify that the
correct unit has been shipped.
8. Locate and verify any accessory kit located in compressor
and/or blower section.
9. Remove any access panel screws that may be difficult to
remove once unit is installed.
2. Do not remove the packaging until the unit is ready for
installation.
Table 1 — Physical Data — 50HQP072-120 Units
UNIT 50HQP072096120
COMPRESSOR QUANTITY*Scroll
Number of Circuits (Compressors)2
Factory Charge HFC-410A (kg) per circuit1.702.152.27
BLOWER MOTOR
Blower Motor Quantity1
Standard Motor (kW)0.751.492.24
BLOWER
No. of Blowers1
Blower Wheel Size D x W (cm)30.48 x 30.48
WATER CONNECTION SIZE
FPT (in.) [mm]1
COAX VOLUME
Volume (liters)6.136.859.08
CONDENSATE CONNECTION SIZE
FPT (in.) [mm]
AIR COIL DATA
Air Coil Dimensions H x W (cm)50.8 x 137.1650.8 x 162.56
Air Coil Total Face Area (sq m) 0.700.83
Air Coil Tube Size (cm)0.953
Air Coil Fin Spacing (fins per cm)5.5
Air Coil Number of Rows3
MISCELLANEOUS DATA
Filter Standard - Throwaway (qty) (cm)†40.64 x 50.80 x 2.54
Weight - Operating (kg)265.8292.1316.6
Weight - Packaged (kg)283.9310.3334.8
*All units have grommet and spring compressor mountings, and
2.2 mm and 3.5 mm electrical knockouts.
†51 mm filters are available as field-installed accessory.
1
/4 [31.8]11/2 [38.1]
3
/4 [19.1]
NOTE: Use the lowest maximum pressure rating when multiple
options are combined:
OPTIONMAXIMUM PRESSURE (kPa)
Base Unit3100
3
a50-8531
Fig. 1 — Unit Dimensions
HANGER BRACKET DIMENSIONS
221cm
2.54cm
PLAN VIEW
TOP
10.8cm
86.6cm
FRONT
CONTROL BOX
U
T
S
V
3.3cm
condensate
LEFT RETURN LEFT VIEW-
AIR COIL SIDE
LEFT RETURN END DISCHARGE
CBP
EAP
BSP
CAP
CAP
FRONT
E
D
F
G
CAP
CBP
CAP
EAP
BSP
FRONT
FRONT
CONTROL BOX
PLAN VIEW
TOP
V
S
U
RIGHT RETURN RIGHT VIEW-
AIR COIL SIDE
RIGHT RETURN END DISCHARGE
3.3cm
condensate drain
3
LEFT RETURN STRAIGHT DISCHARGE
CAP
CAP
FRONT
BSP
A
EAP
CBP
B
C
O
P
Q
R
K
M
F
G
E
D
BSP
RIGHT RETURN STRAIGHT DISCHARGE
1
EAP
2CAP
CAP
2
FRONT
CBP
1
5
4
SERVICE ACCESS
3’ (91 cm.) TYPICAL
ALL CONFIGURATIONS
NOTES:
1. All dimensions in centimeters, unless indicated.
2. Access is required for all removable panels and installer should
take care to comply with all building codes and allow adequate
clearance.
3. Water inlet and outlet connections are available on either side of
the unit. Plugs are shipped loose in a plastic bag tied to the water
leg in front of the unit. Installer must plug unused connection.
4. Condensate drain connection is on end opposite of comressor.
5. Electrical access is available on either side of the front of the unit.
6. Electrical box is on right side but can be field-converted to left.
LEGEND
BSP — Blower Service Panel
CAP — Control Access Panel
CBP — Control Box Panel
EAP — Expansion Valve Access Panel
BSP — Blower Service Panel
CAP — Control Access Panel
CBP — Control Box Panel
EAP — Expansion Valve Access Panel
NOTES:
1. Access is required for all removable panels and installer should
take care to comply with all building codes and allow adequate
clearance.
2. Water inlet and outlet connections are available on either side of
the unit. Plugs are shipped loose in a plastic bag tied to the water
leg in front of the unit. Installer must plug unused connection.
3. Condensate drain connection is on end opposite of compressor.
4. Electrical access is available on either side of the front of the unit.
5. Electrical box is on right side but can be field-converted to left.
a50-8534
should be considered when choosing a location for a WSHP:
• Units are for indoor use only.
• Locate in areas where ambient temperatures are between
4.4 C and 37.8 C and relative humidity is no greater than
75%.
• Provide sufficient space for water, electrical and duct
connections.
• Locate unit in an area that allows for easy access and
removal of filter and access panels.
• Allow enough space for service personnel to perform
maintenance.
• Provisions must be made for return air to freely enter the
space if unit needs to be installed in a confined area such
as a closet.
NOTE: Correct placement of the horizontal unit can play an
important part in minimizing sound problems. Since ductwork is normally applied to these units, the unit can be placed
so that the principal sound emission is outside the occupied
space in sound-critical applications. A fire damper may be required by the local code if a fire wall is penetrated.
Step 4 — Mount Unit — Units should be mounted us-
ing the factory-installed hangers. See Fig. 3. Proper attachment
of hanging rods to building structure is critical for safety. See
Fig. 2. Rod attachments must be able to support the weight of
the unit. See Table 1 for unit operating weights.
Step 5 — Install Duct System — The duct system
should be sized to handle the design airflow quietly.
NOTE: Depending on the unit, the fan wheel may have a shipping support installed at the factory. This must be removed
before operating unit.
SOUND ATTENUATION — To eliminate the transfer of
vibration to the duct system, a flexible connector is recommended for both discharge and return air duct connections on
metal duct systems. The supply and return plenums should include internal duct liner of fiberglass or be made of duct board
construction to maximize sound attenuation of the blower.
Installing the WSHP unit to uninsulated ductwork in an unconditioned space is not recommended since it will sweat and
adversely affect the unit’s performance.
included in the supply and return air ducts, provided system
performance is not adversely impacted. The blower speed can
be also changed in the field to reduce air noise or excessive airflow, provided system performance is not adversely impacted.
5
To reduce air noise, at least one 90-degree elbow could be
EXISTING DUCT SYSTEM — If the unit is connected to
3/8" [10MM] THREADED
ROD (FIELD SUPPLIED)
VIBRATION ISOLATOR
(FACTORY SUPPLIED)
WASHER
(FIELD SUPPLIED)
DOUBLE HEX NUTS
(FIELD SUPPLIED)
a50-6260e8535
Fig. 3 — Hanger Brackets
a50-6260ef8536
Fig. 4 — Horizontal Unit Pitch
*3/4" IPT
Trap Depth
1.5" [38mm]
Min 1.5"
[38mm]
1/4" per foot
(21mm per m)
drain slope
3/4" PVC or
Copper by others
Vent
Fig. 5 — Trap Condensate Drain
a50-6260e8537
existing ductwork, consider the following:
• Verify that the existing ducts have the proper capacity to
handle the unit airflow. If the ductwork is too small,
larger ductwork should be installed.
• Check existing ductwork for leaks and repair as
necessary.
NOTE: Local codes may require ventilation air to enter the
space for proper indoor air quality. Hard-duct ventilation may
be required for the ventilating air supply. If hard ducted ventilation is not required, be sure that a proper air path is provided
for ventilation air to unit to meet ventilation requirement of the
space.
Step 6 — Install Condensate Piping Drain
INSTALLATION — Slope the unit toward the drain at a
1 cm per 50 cm pitch. See Fig. 4. If it is not possible to meet the
required pitch, a condensate pump should be installed at the
unit to pump condensate to building drain.
Install condensate trap at each unit with the top of the trap
positioned below the unit condensate drain connection as
shown in Fig. 5. Design the depth of the trap (water-seal) based
upon the amount of ESP (external static pressure) capability of
the blower (where 2 in. wg of ESP capability requires 2 in. of
trap depth). As a general rule, 38 mm trap depth is the minimum. Each unit must be installed with its own individual trap
and connection to the condensate line (main) or riser.
Units are not internally trapped, therefore an external trap is
necessary. Each unit must be installed with its own individual
trap and means to flush or blowout the condensate drain line.
Do not install units with a common trap or vent. For typical
condensate connections see Fig. 5.
NOTE: Never use a pipe size smaller than the connection.
VENTING — A vent should be installed in the condensate
line of any application which may allow dirt or air to collect in
the line. Consider the following:
• Always install a vent where an application requires a
long horizontal run.
• Always install a vent where large units are working
against higher external static pressure and to allow
proper drainage for multiple units connected to the same
condensate main.
• Be sure to support the line where anticipated sagging
from the condensate or when “double trapping” may
occur.
• If condensate pump is present on unit, be sure drain connections have a check valve to prevent back flow of condensate into other units.
1/4” Pitch for
Drainage
Drain Connection
Step 7 — Field Convert Air Discharge — Hori-
zontal units can be field converted between straight (side) and
back (end) discharge.
NOTE: It is not possible to field convert return air between left
or right return models due to the necessity of refrigeration copper piping changes.
Field conversion must be completed on the ground. If the
unit is already hung it should be taken down for the field conversion. Place in a well-lighted area. Conversion should only
be attempted by a qualified service technician.
SIDE TO BACK DISCHARGE CONVERSION
1. Remove back panel and side access panel. See Fig. 6.
2. Loosen 2 motor slide nuts, raise motor slide assembly and
remove belt and motor sheave. See Fig. 7.
3. Remove blower sheave. Remove motor bolts and carefully remove motor. See Fig. 8.
4. Remove 2 motor clips and reattach to opposite side. See
Fig. 9.
5. Unbolt (3 per side) complete housing assembly. See
Fig. 9.
6. Rotate complete assembly into new position. Locate over
mounting holes in base, reattach using 3 bolts per side.
6
Pitch Toward
Drain
REMOVE BLOWER PANEL
AND ACCESS PANEL
RETURN AIR
FRONT
Fig. 6 — Removing Panels
a50-8538
MOTOR SLIDE NUTS
Fig. 7 — Removing Belt
a50-8539
REMOVE MOTOR
AND BLOWER SHEAVE
ADJUSTING BOLT
REMOVE 4
MOTOR BOLTS
Fig. 8 — Removing Motor
a50-8540
MOTOR CLIPS
BOLTS
Fig. 9 — Removing Blower Assembly
a50-8541
7. Mount motor, motor sheave, blower sheave and belt.
8. Replace panels from Step 1.
BACK TO SIDE DISCHARGE CONVERSION — If the
discharge is changed from back to side, use the above instructions. Note that figures will be reversed.
LEFT OR RIGHT RETURN UNITS — It is not possible to
field convert return air between left or right return units due to
the necessity of refrigeration copper piping changes. However,
the conversion process of side to back or back to side discharge
for either right or left return configuration is the same. In some
cases, it may be possible to rotate the entire unit 180 degrees if
the return air connection needs to be on the opposite side. Note
that rotating the unit will move the piping to the other end of
the unit.
Step 8 — Install Piping Connections — Depend-
ing on the application, there are 3 types of WSHP piping systems to choose from: water loop, ground-water and ground loop.
Refer to the Carrier System Design Manual for additional information.
pipe thread fittings for water connections to prevent annealing
and out-of-round leak problems which are typically associated
with high temperature brazed connections. Refer to Table 1 for
connection sizes. When making piping connections, consider
the following:
• A backup wrench must be used when making screw con-
Make sure wires are not pinched and not over sharp edges. Adjust motor downward to tighten belt. Raise or lower
motor slide assembly with adjusting bolt and retighten the
2 slide nuts. Check for correct tension. Rewire motor (at
contactor) for correct rotation. Spin blower wheel to ensure wheel is not obstructed.
All WSHP units utilize low temperature soldered female
nections to unit to prevent internal damage to piping.
• Insulation may be required on piping to avoid condensation in the case where fluid in loop piping operates at
temperatures below dew point of adjacent air.
• Piping systems that contain steel pipes or fittings may
be subject to galvanic corrosion. Dielectric fittings may
be used to isolate the steel parts of the system to avoid
galvanic corrosion.
• Do not allow hoses to rest against structural building
components. Compressor vibration may be transmitted
through the hoses to the structure, causing unnecessary
noise complaints.
Figure 10 shows a typical supply/return hose kit assembly.
WATER LOOP APPLICATIONS — Water loop applications
usually include a number of units plumbed to a common piping system. Maintenance to any of these units can introduce air
into the piping system. Therefore, air elimination equipment
comprises a major portion of the mechanical room plumbing.
The flow rate is usually set between 2.41 and 3.23 L/m per
kW of cooling capacity. For proper maintenance and servicing,
pressure-temperature (P/T) ports are necessary for temperature
and flow verification.
In addition to complying with any applicable codes, consid-
er the following for system piping:
• Piping systems utilizing water temperatures below
10 C require 13 mm closed cell insulation on all piping
surfaces to eliminate condensation.
7
Step 9 — Install Field Power Supply Wiring
RIB CRIMPED
LENGTH
(2 FT [0.6M] LENGTH STANDARD)
SWIVEL
BRASS
FITTING
BRASS
FITTING
EPT
Fig. 10 — Supply/Return Hose Kit
WARNING
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work
is completed.
• All plastic to metal threaded fittings should be avoided
due to the potential to leak. Use a flange fitted substitute.
• Teflon tape thread sealant is recommended to minimize
internal fouling of the heat exchanger.
• Use backup wrench. Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• The piping system should be flushed prior to operation to
remove dirt and foreign materials from the system.
GROUND-LOOP APPLICATIONS — Temperatures between –3.9 and 43.3 C and a cooling capacity of 2.41 to
3.23 L/s per kW of flow per ton are recommended. In
addition to complying with any applicable codes, consider
the following for system piping:
• Piping materials should be limited to only polyethylene
fusion in the buried sections of the loop.
• Galvanized or steel fittings should not be used at any
time due to corrosion.
• All plastic to metal threaded fittings should be avoided
due to the potential to leak. Use a flange fitted substitute.
• Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• Pressure-temperature (P/T) plugs should be used to measure flow of pressure drop.
GROUND-WATER APPLICATIONS — Typical groundwater piping is shown in Fig. 11. In addition to complying
with any applicable codes, consider the following for system piping:
• Install shut-off valves for servicing.
• Install pressure-temperature plugs to measure flow and
temperature.
• Boiler drains and other valves should be connected using
a “T” connector to allow acid flushing for the heat
exchanger.
• Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• Use PVC SCH80 or copper piping material.
NOTE: PVC SCH40 should not be used due to system high
pressure and temperature extremes.
Water Supply and Quantity
— Check water supply. Water
supply should be plentiful and of good quality. See Table 2 for
water quality guidelines.
IMPORTANT: Failure to comply with the above required
water quality and quantity limitations and the closedsystem application design requirements may cause damage
to the tube-in-tube heat exchanger that is not the responsibility of the manufacturer.
CAUTION
Use only copper conductors for field-installed electrical
wiring. Unit terminals are not designed to accept other
types of conductors.
All field-installed wiring, including the electrical ground,
MUST comply with the National Electrical Code (NEC,
U.S.A.) as well as applicable local codes. In addition, all field
wiring must conform to the Class II temperature limitations described in the NEC.
Refer to unit wiring diagrams Fig. 12-16 for fuse sizes and a
schematic of the field connections which must be made by the
installing (or electrical) contractor.
Consult the unit wiring diagram located on the inside of the
compressor access panel to ensure proper electrical hookup.
The installing (or electrical) contractor must make the field
connections when using field-supplied disconnect.
Operating voltage must be the same voltage and phase as
shown in electrical data shown in Tables 3A and 3B.
Make all final electrical connections with a length of flexible conduit to minimize vibration and sound transmission to
the building.
POWER CONNECTION — Line voltage connection is
made by connecting the incoming line voltage wires to the
L side of the power block terminal. See Fig. 17. See Tables
3A and 3B for correct wire and maximum overcurrent protection sizing. See Table 4 for low voltage VA ratings.
SUPPLY VOLTAGE — Operating voltage to unit must be
within voltage range indicated on unit nameplate.
On 3-phase units, voltages under load between phases must
be balanced within 2%. Use the following formula to determine the percentage voltage imbalance:
% Voltage Imbalance
= 100 x
Example: Supply voltage is 420-3-50.
max voltage deviation from average voltage
average voltage
AB = 425 volts
BC = 422 volts
AC = 417 volts
Average Voltage =
425 + 422 + 417
1264
=
3
3
In all applications, the quality of the water circulated
through the heat exchanger must fall within the ranges listed in
the Water Quality Guidelines table. Consult a local water treatment firm, independent testing facility, or local water authority
for specific recommendations to maintain water quality within
the published limits.
= 421
Determine maximum deviation from average voltage:
(AB) 425 – 421 = 4 v
(BC) 422 – 421 = 1 v
(AC) 421 – 418 = 3 v
Maximum deviation is 4 v.
8
Determine percent voltage imbalance.
PressureTemperature
Plugs
Boiler
Drains
Strainer – Field-Installed Accessory
(16 to 20 mesh recommended for
filter sediment)
This amount of phase imbalance is satisfactory as it is
below the maximum allowable 2%.
Operation on improper line voltage or excessive phase
imbalance constitutes abuse and may cause damage to electrical components.
NOTE: If more than 2% voltage imbalance is present, contact
local electric utility.
EXTERNAL LOOP POWER CONNECTION — If the unit
is to be connected to an external loop pump or flow controller,
connect the pump to the loop pump terminal block PB1. The
maximum power handling is 4 amps at 240 volts. The pumps
will automatically cycle as required by the unit.
420-VOLT OPERATION — All 380/420 volt units are factory
wired for 380 volts. The transformers may be switched to
420-volt operation (as illustrated on the wiring diagram) by
disconnecting the VIO lead at L1 and attaching the BRN lead
to L1. Close open end of VIO lead.
9
Table 2 — Water Quality Guidelines
CONDITION
Scaling Potential — Primary Measurement
Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below.
pH/Calcium
Hardness Method
Index Limits for Probable Scaling Situations (Operation outside these limits is not recommended.)
Scaling indexes should be calculated at 150 F for direct use and HWG applications, and at 90 F for indirect HX use. A monitoring plan should be
implemented.
Ryznar Stability Index
Langelier Saturation Index
Iron Fouling
2+
(Ferrous)
Iron Fe
(Bacterial Iron Potential)
Iron Fouling
Corrosion Prevention††
pH
Hydrogen Sulfide (H
Ammonia Ion as Hydroxide,
Chloride, Nitrate and Sulfate
Compounds
S)
2
Maximum Chloride LevelsMaximum allowable at maximum water temperature.
Erosion and Clogging
Particulate Size and Erosion
Brackish
LEGEND
HWG — Hot Water Generator
HX— Heat Exchanger
N/A— Design Limits Not Applicable Considering Recirculating
NR— Application Not Recommended
SS— Stainless Steel
*Heat exchanger materials considered are copper, cupronickel, 304 SS (stainless
steel), 316 SS, titanium.
†Closed recirculating system is identified by a closed pressurized piping system.
**Recirculating open wells should observe the open recirculating design
considerations.
Potable Water
HX
MATERIAL*
CLOSED RECIRCULATING†OPEN LOOP AND RECIRCULATING WELL**
AllN/ApH < 7.5 and Ca Hardness, <100 ppm
AllN/A
AllN/A
AllN/A
AllN/A
All
6 - 8.5
Monitor/treat as needed.
If >7.5 minimize steel pipe use.
Based upon 150 F HWG and direct well, 85 F indirect well HX.
2+
If Fe
(ferrous) >0.2 ppm with pH 6 - 8, O2<5 ppm check for iron bacteria.
If <–0.5 minimize steel pipe use.
Above this level deposition will occur.
Minimize steel pipe below 7 and no open tanks with pH <8.
6.0 - 7.5
–0.5 to +0.5
<0.2 ppm (Ferrous)
<0.5 ppm of Oxygen
6 - 8.5
<0.5 ppm
At H
S>0.2 ppm, avoid use of copper and cupronickel piping or HXs.
<10 ppm (<1 ppm “sand free” for reinjection) of particles and a maximum velocity of 6
fps. Filtered for maximum 800 micron size. Any particulate that is not removed can
potentially clog components.
Use cupronickel heat exchanger when concentrations of calcium or sodium chloride
are greater than 125 ppm are present. (Seawater is approximately 25,000 ppm.)
2
Copper alloy (bronze or brass) cast components are okay to <0.5 ppm.
Rotten egg smell appears at 0.5 ppm level.
<0.5 ppm
50 F (10 C)75 F (24 C)100 F (38 C)
<20 ppmNRNR
††If the concentration of these corrosives exceeds the maximum allowable level,
then the potential for serious corrosion problems exists.
Sulfides in the water quickly oxidize when exposed to air, requiring that no agitation
occur as the sample is taken. Unless tested immediately at the site, the sample will
require stabilization with a few drops of one Molar zinc acetate solution, allowing
accurate sulfide determination up to 24 hours after sampling. A low pH and high
alkalinity cause system problems, even when both values are within ranges shown.
The term pH refers to the acidity, basicity, or neutrality of the water supply. Below
7.0, the water is considered to be acidic. Above 7.0, water is considered to be basic.
Neutral water contains a pH of 7.0.
NOTE: To convert ppm to grains per gallon, divide by 17. Hardness in mg/l is equivalent to ppm.
10
BC— Blower Contactor
CB— Circuit Breaker
CC— Compressor Contactor
CO— Sensor, Condensate Overflow
DPP— Dual Point Power
FP1— Sensor, Water Coil Freeze Protection
FP2— Sensor, Air Coil Freeze Protection
HP— High-Pressure Switch
HPWR — High-Pressure Water Relay
JW3— Clippable Field Selection Jumper
LOC— Loss of Charge Pressure Switch
PDB— Power Distribution Block
RVS— Reversing Valve Solenoid
TRANS — Tr a n sf o r me r
TXV— Thermostatic Expansion Valve
Factory Line Voltage Wiring
Factory Low Voltage Wiring
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC (National Electrical
Code, U.S.A.) and local codes.
3. 380/420-v transformers will be connected for 380-v operation. For
420-v operation, disconnect VIO lead at L1, and attach BRN lead
to L1. Close open end of VIO lead.
4. FPI thermistor provides freeze protection for WATER. When using
ANTIFREEZE solutions, cut JW3 jumper.
5. Typical heat pump thermostat wiring shown. Refer to thermostat
installation instructions for wiring to the unit. Thermostat wiring
must be “Class 1” and voltage rating equal to or greater than unit
supply voltage.
6. 24-v alarm signal shown. For dry alarm contact, cut JW1 jumper
and dry contact will be available between AL1 and AL2.
7. Transformer secondary ground via Complete C board standoffs
and screws to control box. (Ground available from top two standoffs as shown.)
8. Suffix 1 designates association with lead compressor. Suffix 2
with lag compressor.
9. For dual point power (DPP) option, blower wire will connect to
other PBD.
LEGEND
Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
Optional Wiring
Relay/Contactor Coil
Thermistor
Condensate Pan
Circuit Breaker
Ground
Solenoid Coil
Relay Contacts - N.O.
Relay Contacts - N.C.
Temperature Switch
Switch - Low Pressure
Switch - High Pressure
Wire Nut
Fig. 12 — 50HQP072-120 Units — Typical Control Wiring with Complete C Control
Complete C
Complete C1
Complete C
Complete C2
Complete C2
Complete C1
11
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.