Carrier 50HQ User Manual

Number One AirConditioninq Maker
^^2 Divisiort of
Carrier Corporation
Carrier Parkway • Syracuse NY 13221
i
-
Water-Source Heat Pumps
SAFETY CONSIDERATIONS...................................1
INSTALLATION........................................................1-5
Step 1 — Check Equipment and
Jobsite .......................................................................1
• UNPACKAGE UNIT
• INSPECT EQUIPMENT
• COMPLETE OR CONSIDER THESE SYSTEM REQUIREMENTS
Step 2 — Connect Supply Ductwork Step 3 — Make Piping Connections
• CONNECT WATER SUPPLY AND RETURN LINES
• INSTALL BALANCING VALVES
.....................
......................
Page
2 3
INDEX
Page
• MAKE CONDENSATE DRAIN LINE CONNECTION
Step 4 — Make Electrical Connections... 4
• INSTALL A BRANCH CIRCUIT DISCONNECT PER NEC
• BRING POWER LEADS INTO UNIT
• CONNECT GROUND LEAD TO GROUND LUG IN SPLICE BOX
• SET FAN MOTOR SPEED
• CONNECT CONTROL POWER WIRING
START-UP
SERVICE....................................................................7
..................................................................
6
SAFETY CONSIDERATIONS
Installation and servicing of air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and quali fied service personnel should install, repair or
service air conditioning equipment.
Untrained personnel can perform basic mainten ance functions of cleaning coils and cleaning and
replacing filters. All other operations should be performed by trained service personnel. When working on air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and*, work gloves. Use quenching cloth for brazing operations. Have fire extinguishers available for all brazing operations.
WARNING: Before performing service or maintenance operaiions on system, turn off main pow'er switch to indoor unit and outdoor unit. Electrical shock could cause personal injury.
INSTALLATION
Step 1 — Check Equipment and Jobsite
UNPACKAGE UNIT — Move to final location.
INSPECT EQUIPMENT — File claim with ship
ping company if shipment is damaged or incomplete.
COMPLETE OR CONSIDER THESE SYSTEM REQUIREMENTS before installation:
a.
Consult local building codes and National Elec trical Code (NEC) for special installation requirements.
Consider type of water source. Ensure there is an adequate supply of water at temperature of 60 F to 90 F with minimum pressure of 20 psig.
c.
Provide sufficient space for water piping, con densate drain, wiring and servicing unit. See Fig. 1. (Units installed in confined areas may have to be removed for major servicing such as compressor or fan motor replacement.)
d.
Provide a minimum 6-in. clearance between return air filter and adjacent wall.
e.
Mount unit on floor or solid platform. (The 50HQ units can be suspended from ceiling. See “f’ below.) To reduce sound transmission, especially when unit is located in a closet or utility room having louvered doors, the follow ing acoustical treatment is recommended: place an isolation pad under unit. Pad must be same size as unit base. Construct a 1-in. fiberglass sound shield in front of unit.
© Carrier Corporation 1981
Form 50HQ.VQ-2SI
f. 50HQ units include a'sus'pehsion package for
ceiling installation. To attach hanging brackets, install 4 bolts (5 /16 - 18-3/8 in. Ig) thru bracket into the 4 weld nuts located on bottom of unit. Insert the threaded rod thru rubber grommet, located in hanging bracket, and attach with flat washer and double nut. See Fig. 3.
Step 2 — Connect Supply Ductwork — Supply
air duct flange is shipped inside unit. Remove flange from shipping location and install on unit supply air opening. Connect supply air ductwork to unit supply air duct connection flange. Refer to Fig. 1 and 2 and Table 1 and 2 for connection size and location. If necessary, refer to Carrier System
Design Manual, Part 2, for system air duct design.
^ Table 1 — Installation Data — 50VQ (See Fig. 1.)
MODEL 50VQ OPER WT (lb)
DIMENSIONS (ft-in.)
SUPPLY DUCT CONN.
(ft-in.) F 0-9-7/16
FILTER (1)
Size (in.)
014
_5
A B C D E
G 1-1-3/8
018
240“^
022
260 270
027
1-9-3/16 1-9-3/16 3-2-5/16 0-5-7/8 0-1-3/16
21 X 21
When E-e'dignihg and installing ductwork, consider tfie following:
a. Size duct for 350 to 450 cfm per ton of cooling
capacity. b. Avoid abrupt duct size increases and reductions. c. Use flexible connectors between ductwork and
unit to prevent transmission of vibration. d. Ducts passing thru an unconditioned space must
be insulated and covered with vapor barrier in
accordance with the latest issue of SMACNA
(Sheet Metal and Air Conditioning Contractor’s
National Association) and NESCA (National
Environmental Systems Contractor’s Associa tion) minimum installation standards for resi dential heating and air conditioning systems.
033
290
Replaceable Media
042
320 320
048 060
0-6-13/16
0-10-1/2 1-1-1/16 1-0
350
2-5-3/8
2-3 4-0 0-8
0-5-1/2
1-4
38 X 22
080
380
0-6-1/16
Return Air

Fig. 1 — Dimensions and Connections — 50VQ

Table 2'— Installation Data — 50HQ (See Fig. 2.)
I
MODEL 50HQ OPERwfob)
"dimensions (ft-in.)
_E
"supply duct conn.
(ft-in.) F
_ _ G
ACCESSORY FILTER (1)
Size (in.)
014
220
A B
C
D
018 022 027 033
195 210 220
3-10-1/2 1-10-5/16 1- 5-15/16 0- 3-7/8
11/16
1- 1-3/8
0- 9^-7/16
17 x23
230
042 048
250 300
0- 3-7/8
Replaceable Media
060
325
4- 0
1-11
2- 0
0-2-9/16
0-3-3/16
1-7-7/8
37 X 23
080
360
0-3-1/16
1-0
Fig. 2 — Dimensions and Connections — 50HQ

Step 3 — Make Piping Connections

CONNECT WATER SUPPLY AND RETURN LINES to water inlet and outlet pipe connections shown in Fig. 4 and 5. Use flexible hose for water line to reduce possible vibration and improve unit serviceability. Make sure hoses or pipes are suitable for system water pressure and sized for proper flow rate.
CAUTION; improper heat exchanger water flow due to piping, valving or improper pump operation is hazardous to units.
For water flow and temperature data refer to
Start-Up section, page 6.
CAUTION: Galvanized pipe or fittings are not
recommended for use with these units due to
possible electrolysis.
nut
BRACKET
Fig. 3 — Suspension Kit
Installation — 50HQ
Table 3 — Electrical Data
UNIT MODEL
50HQ,VQ
014 018 022 027 033 042 048 060
033 042 048 060 080
033 042 36 5 048 060 49 0 104 080 69 0 11 4
FLA — Full Load Amps LRA — Locked Rotor Amps RLA — Rated Load Amps
V/PH/HZ
208-230/1/60 253
208-230/3/60 253 187 80 0
460/3/60 508
OPERATING
VOLTAGE
Max
Min LRA RLA
197
187
414
INSTALL BALANCING VALVES (with shutofO in water supply and return lines for water flow adjustment and a means of water shutoff, if neces sary, when servicing unit. When multiple units are connected in parallel, valves permit removal of one unit without interrupting water flow to other units.
MAKE CONDENSATE DRAIN LINE CON NECTION to female pipe connection provided on unit. Fig. 4 and 5. Install a trap in condensate line as close as possible to unit. Trap must be at least 3 in. deep and not higher than the bottom of unit con densate drain opening. Pitch condensate line to open drain or sump. Insulate a condensate drain line located above a living area.
50HQ Units Only — If a secondary drain is re quired, remove plastic cap from secondary drain connection, located in bottom of unit, and connect drain so that discharge is obvious to maintenance personnel.
Step 4 — Make Electrical Connections — Field
wiring must comply with local and national fire, safety and electrical codes. Voltage to unit must be
within the operating voltage range indicated on
nameplate or in Table 3. On 3-phase units, phases
must be balanced within 2%.
Operation of unit on improper line voltage or with excessive phase imbalance constitutes abuse and is not covered by Carrier Warranty.
INSTALL A BRANCH CIRCUIT DISCONNECT
PER NEC of adequate size to handle unit starting current. Locate disconnect within sight of and readily accessible from the unit, per Section 440-14 of National Electrical Code (NEC).
BRING POWER LEADS INTO UNIT — Extend
leads from disconnect per NEC thru hole provided
(Fig. 1 and 2) into line wiring splice box. Fig. 6.
COMPRESSOR
37 5 53 0 65 0 13 3 66 0 88 0 23 3
100 0
94 0 23 9
150 0 35,3
87 0 13 8 2 5
100 0 136 0 20 6
137 0 20 7
30 0 60 35 0 8 2
9 6
134 16 2 27 7
18 5
16 8 3 9 24 9
6.9
FAN
FLA
7 12.7 9
1.5 18 1 30 1 7 22 0 35 2 5 31.6 3 2 34 33 4 60
4.5
3 2 4 5
6 2 32 1 1 1
1 6 10 2 20 12 3 2 6 31 17 4
MINIMUM
CIRCUIT
AMPS AMPS
17.7
37 8
48.6 19 8 30
26 3 30 6
8 9
15 3 25
MAXIMUM
FUSE
CONNECT GROUND LEAD TO GROUND LUG IN SPLICE BOX for safety. Connect power wiring. See Fig. 6. Splice line power leads to yellow and black pigtails on single-phase units or yellow pigtails on 3-phase units. Use wire nuts. Tape each connection.
Unit transformer on 208-230-volt units is factory wired for 230/24-volt operation. For 208/24-volt operation, remove black (230-v) transformer lead from unit contactor and connect red (208-v) lead to contactor. Cap unused transformer lead.
SET FAN MOTOR SPEED — Set fan motor for high-, medium- or low-speed operation as follows:
1. Remove unit fan section access panel.
2. Locate Molex fan speed selector block on fan
housing. Fig. 7. Selector block receptacle 1 is high fan speed, receptacle 2 is medium fan speed and receptacle 3 is low fan speed. Yellow and black fan motor power leads from control box are connected to selector block receptacle C and
1. Yellow lead is common, black lead is speed-
change lead.
3. To change fan motor speed, remove black lead from selector block receptacle and plug it into
desired receptacle. Receptacle 4 is not used.
CAUTION: For proper utiit operation, set unit fan motor speed for air quantity witbin range shown in Table 4.
Set Fan Motor Speed on 460-Volt Units — Two­speed fan motor is factory wired for high-speed oper ation. (Yellow and black power leads from control box are connected to the yellow and black fan motor leads.) Change fan motor to low speed by wiring as follows:
1. Splice the violet and black fan motor leads together.
20 30
50 60
60
40 40 45 45
15 15 15
25
L
i
WATER WATER
I Supply Air
‘ Return Air
Fig. 4 — Water Piping — 50VQ
BALANCING VALVES (2) WITH SHUTOFF
50HQ0I4,018,022,027, 033,042
pply Air
I Return Air
Fig. 5 — Water Piping — 50HQ
5
2. Splice yellow and black power leads from eontrol box to yellow and red motor leads. (Yellow-to­yellow and black-to-red.)
CONNECT CONTROL POWER WIRING (24-v) — Power leads are brought thru 1/2-in. hole pro vided in unit, Fig. 1 and 2. Extend leads to control wiring terminal board located on top of control box,
Fig. 7. Connect leads to terminal board as shown
in Fig. 6.
Use Carrier-specified room thermostat and sub
base for proper unit operation. Be sure that field-
installed jumper wire is connected between subbase terminals W and Y. Set thermostat heat anticipator at 1.0 amp for 1-phase units and 0.50 amp for 3-phase units.
FAN SPEED SELECTOR BLOCK (MOLEX PLUG)
COMPRESSOR
Fig. 7 — Typical Component Arrangement
(50HQ014-042 Shown)
—^YEL —
-TUyel
_iT^YEL
GROUND
œilug
50HQ.VQ HEAT PUMP CONTROL BOX
1-PHASE CONN. TO DISCON NECT­PER NEC
GROUND LEAD
—^YEL —
—^BLK —
,__.GROUND
—TSlLUG
50HQ.VQ HEAT PUMP CONTROL BOX
I-PHASE
3-PHASE CONN. TO DISCONNECT­PER NEC
GROUND LEAD
Fig. 6 — Line Power Connections

START-UP

Water Flow and Temperature Data
1. Consider design water flow rates for efficient operation. See Table 4 for permissible water flow range.
2. Ensure that water temperature entering unit is between 60 F minimum and 90 F maximum. If water temperature below 60 F must be used, insulate supply line and install a secondary drain pan under the unit to remove condensate from heat exchanger and internal plumbing.
CAUTION: Water temperature outside specified temperature rartge may cause
damage to mût Do not jumper low temperar ture switch in order to use ethytene giycoi.
3. Ensure that supply water is clean and air is purged from system. Air in supply water causes scaling in heat exchanger. Foreign material in water and/or excessive velocity of water can cause damage to tubing.
To Start Unit — Ensure that air filter is in place on
unit filter flanges provided. Do not operate unit without filter in place. Adjust the thermostat as follows;
1. Set selector switch at OFF.
2. Turn on main disconnect switch to unit.
3. Set fan switch as desired (ON or AUTO.).
4. Set thermostat dial at desired temperature.
5. Set selector switch at HEAT or COOL. Check system refrigerant charge. See Service,
Refrigerant Charging on page 7.
Unit Single-Phase Compressors Equipped
With a Compressor Start Thermistor (PTC De
— When supply voltage is within limits indi
vice)
cated on nameplate and compressor will not start, check the thermistor with an ohmmeter.
If the PTC is good, and the compressor does not start, disconnect the PTC from the starting circuit and give unit a temporary capacitanee boost. Refer to Carrier Standard Service Techniques Manual, Chapter 2, for details on capacitance boost pro cedure. If unit does not start with capacitance boost, compressor may be defective. If unit does start, check starting capability with PTC assistance. If questionable, remove PTC, add start capacitor and start relay per start kit installation instructions.
WARNING: Capadtance boost or iastallatioa of start capacitor and start relay should be per formed by trained personnel. Improper pro­cedure could cause personal injurj' or equipment damage.

Unit Controls and Safety Devices

HIGH-PRESSURE RELIEF VALVE (except 50HQ,VQ0I4) is located in compressor. Relief valve opens at a pressure differential of approximately
550 psi between suction (low side) and discharge
(high side) to allow pressure equalization.
CURRENT AND TEMPERATURE SENSITIVE OVERLOAD (linebreak) — Internal on all com
pressors except on 50HQ,VQ014 which has external
shell mounted overload. Overload resets auto matically when internal compressor motor tempera ture drops to a safe level (overloads may require up to 45 minutes to reset). When an internal overload is suspected of being open, eheck by using an ohm-
I
meter or continuity tester. If necessary, refer to Carrier Standard Service Techniques Manual,
Chapter 2, for complete instructions. HIGH-PRESSURE SWITCH closes and shuts
compressor off if discharge pressure rises above 395
psig. Switch opens at 295 psig. FREEZE-UP PROTECTION — Two controls are
used to prevent unit from operating if water approaches freezing temperature:
1. Low water temperature cutout (LWTC) shuts unit off and energizes lockout relay if water temperature reaches 37 F.
2. Lockout relay locks itself in energized position and prevents unit from starting.
The unit can be restored to heating operation if
the water temperature rises to 42 F, where the
LWTC will reset, and if the thermostat circuit is
interrupted either by lowering the thermostat
setting or by moving system switch to OFF or COOL. Thermostat may then be readjusted to normal set point.
HEAT PUMP CIRCUITS, shown in Fig. 8, are refrigerant and water flow diagrams for heating and cooling cycles.

SERVICE

Refrigerant Charging — Unit refrigerant system
is factory charged. When recharging is necessary
during heating or cooling season, weigh in total
charge indicated in Table 4. Remove any refrigerant remaining in system before recharging. If system has lost complete charge, evacuate system to 500 microns (29.7 in. vacuum) before recharging. Service port connections are provided on high and low sides of refrigerant system for evacuation and charging. (See Fig. 8 for service port location.)
Dial-a-charge charging cylinder is an accurate device used to recharge systems by weight. These cylinders are available at refrigeration supply firms.
To check and/or adjust refrigerant charge during
cooling season, use correct Cooling Cycle Charging
^ Chart (Fig. 9, 11, 13, 15,17,19,21,22,23) or Carrier
Chargemaster® charging device (Carrier Part No. 38GC680004). Charging charts or Chargemaster may also be used as alternate methods of recharging system. Charging methods are described below.
To cheek system operation during heating cycle, use correct Heating Cycle Operation Check Chart (Fig. 10, 12, 14, 16, 18, 20). These charts indicate whether a correct relationship exists between unit
operating pressures and water temperature leaving heat exchanger. If pressure and water temperature lines do not intersect on chart, the system refrigerant charge may not be correct or other system abnor malities may exist. Do not use Operation Check Charts to adjust refrigerant charge. Weigh charge into system.
COOLING CYCLE HEATING CYCLE

Fig. 8 — Refrigerant and Water Flow Diagrams — 50HQ,VQ

Table 4 — Service Data
UNIT 50HQ.VQ
R-22 CHG (Ib-oz)»
Refrig Control
FAN
Diameter (in. Nom) 10 Width (in. Nom) Range Cfm 400-600 500-700 600-800 750-1000 950-1200 1225-1575 Motor Hp 1/8 1/8 1/6 1/6 1/4 Motor Rpm
(3-speed)
HEAT EXCHANGER
WATER FLOW RATE
(Gpm)
‘Factory refrigerant charge
014 018
1-8 1-13
7
2 5-5 3-6 4-8 4 5-9
10
7 7 7 7 7 8
022
2-2 2-6
10 10
027
033 042 048 060
2-6 2-14 4-3
Capillary Tube
Centrifugal — Direct Drive
10
1075 Nominal
5-10
COOLING CYCLE CHARGING CHART METHOD
1. Operate unit a minimum of 10 minutes before checking charge, and after each charge adjustment.
2. Measure suction pressure by attaching a gage to unit suction service port (Schrader Fitting).
3. Measure discharge pressure by attaching a gage to unit discharge service port (Schrader Fitting).
4. Using a sling psychrometer, measure wet-bulb
temperature of air entering unit.
5. Refer to correct Charging Chart. Locate on
curves where unit discharge pressure line and indoor air wet-bulb temperature line intersect.
6. From intersect point, project horizontally left to
ISO 200 250 300
COMPRESSOR DISCHARGE PRESSURE @ SERVICE PORT (PSIG)
chart suction pressure line. Compare chart suction pressure to unit suction pressure (step 2).
7. If unit suction pressure is lower than chart pres
Fig. 10 — Heating Cycle Operation
Check Chart (R-22) — 50HQ.VQ014
sure, add refrigerant to unit until chart pressure is reached. If unit suction pressure is higher than chart pressure, remove refrigerant until chart pressure is reached.
11
1/3
6-12 8-16
10 10
1400-1800 1750-2250
1/2 3/4
5-3 6-8
10
2300-3000
11-21
080
12
9
1
1000
14-28
ISO 200 250 300
COMPRESSOR DISCHARGE PRESSURE ® SERVICE PORT(PSIG)
Fig. 9 — Cooling Cycle Charging Chart
(R-22) — 50HQ,VQ014
COMPRESSOR DISCHARGE PRESSURE @ SERVICE PORT (PSIG)
Fig. 11 — Cooling Cycle Charging Chart
(R-22) — 50HQ.VQ018
Fig. 12 — Heating Cycle Operation
Check Chart (R-22) — 50HQ,VQ018
Fig. 15 — Cooling Cycle Charging Chart
(R-22) — 50HQ,VQ027
COMPRESSOR DISCHARGE PRESSURE ® SERVICE PORT(PSIG)
Fig. 13 — Cooling Cycle Charging Chart
(R-22) — 50HQ,VQ022
Fig. 14 — Heating Cycle Operation
Check Chart (R-22) — 50HQ,VQ022
Fig. 16 — Heating Cycle Operation
Check Chart (R-22) — 50HQ,VQ027
COMPRESSOR DISCHARGE PRESSURE® SERVICE PORT (PSIG)
Fig. 17 — Cooling Cycle Charging Chart
(R-22) — 50HQ.VQ033
COMPRESSOR DISCHARGE PRESSURE@SERVICE PORT(PSIG)
a
2 no
ISO 200 250 300
COMPRESSOR DISCHARGE PRESSURE ©SERVICE PORT(PSIG)
m
Fig. 18 — Heating Cycle Operation Check Chart (R-22) — 50HQ,VQ033
COMPRESSOR DISCHARGE PRESSURE® SERVICE PORT(PSIG)
Fig. 19 — Cooling Cycle Charging Chart
(R-22) — 50HQ,VQ042
Fig. 21 — Cooling Cycle Charging Chart
(R-22) - 50HQ.VQ048
Fig. 22 — Cooling Cycle Charging Chart
(R-22) — 50HQ,VQ060
Fig. 20 — Heating Cycle Operation
Check Chart (R-22) — 50HQ,VQ042
COMPRESSOR DISCHARGE PRESSURE ©SERVICE PORT(PSIG)
Fig. 23 — Cooling Cycle Charging Chart
(R-22) — 50HQ.VQ080
10
CHARGEMASTER® DEVICE OPERATION — Operate unit 10 minutes before using Charge­master. Ensure unit indoor fan section access panel is in place for proper Chargemaster operation.
1. Tape Chargemaster feeler bulb to unit suction line. Insulate bulb. Ensure suction line is clean
for good contact with bulb.
2. Connect refrigerant drum to Chargemaster inlet port with drum in position for vapor charging.
3. Connect Chargemaster outlet port (loosely) to unit suction line Schrader valve.
4. Crack valves on refrigerant drum and Charge­master to purge lines from drum to suction line Schrader valve. After purging lines, close valve on Chargemaster only. Tighten Chargemaster connection at suction line Schrader valve.
5. Measure unit leaving water temperature.
6. Read evaporator temperature at red needle
position on Chargemaster temperature gage and
suction line temperature at black needle
position.
CAUTiON: Do not read evaporator tempera ture with Chargemaster valve open.
7. Enter 50HQ,VQ Chargemaster Charging Chart, Table 5, at unit leaving water temperature (step
5) and evaporator temperature (step 6). (Do not
use standard charging chart on cover of Charge­master.) Eind the suction line temperature
required for correct system charge. If actual suction line temperature (step 6) is higher than table value, the system is undercharged. If suc tion line temperature is lower than table value, the system is overcharged.
Example: At leaving water temperature of 93 F and evaporator temperature of 41 F, the system is correctly charged at 50 F (±2F) suction line temperature.
8. Add charge by slowly opening Chargemaster valve. If necessary, reduce charge by bleeding at
liquid line Schrader valve. Check outdoor air and evaporator temperature during procedure. If they change, refer back to Chargemaster Charging Chart for new value.
Correct use of Chargemaster ensures that an optimum refrigerant charge is in system when conditions and system components are normal.
However, the Chargemaster does not solve or fix system abnormalities. It indicates correct charge for condition of system. It does not make correc tions for dirty filters, slow fans, or other abnormal conditions. This charging device ensures that a correct relationship exists between leaving water temperature, evaporator temperature, and suction line temperature on a specific system.
Table 6 — Compressor Data
UNIT
50HQ,VQ
014 018 022 027 033 042 048 PC4616AD 060
033 042 048 060 080
033 042 048 060 080
V/PH
208/230-1
208/230-3 PY4616AD
460/3
PRODUCTION
COMPRESSOR
AJ55Ì3F AB5519F
MD2023FE MD2423FE MD3423FE MD4023FE
PC6416AG MF3423FE
MF4023FE PY6416AF
PY7716AF 72 MH3423FE 42
MH4023FE 42 PH4616AD 72 PH6416AF 72 PH7716AF
OIL
RECHARGE
(oz)
24 32 42 42 42 42 72 72
42 42 72 72
72
Table 5 — Chargemaster Charging Chart
UNIT
LEAVING
WATER
TEMP
(F)
69 46 75 81 87 93
99 105 112 117 123
’Saturated evaporator temperature which is the equivalent tem
perature of pressure taken at unit suction service valve
30 33 36 39
45 47
EVAPORATOR TEMP (F)*
41 44 47 50
Suction Line Temp (F)
49 51
46
54 57 59 61 53 55 58
50 49 51 48 50 52 46
48 47 49 45 47 50
54 56
54 56
50 53
51
46 49
47 52 55
45
46 50
64
60 57 63
62 55 57 61 54 56 61 64
56
53 53 55 59 62
53 55 56
53
65
60 63
57 61

Compressor Removal

See Table 6 for compressor information and Fig. 7 for component location. Follow safety codes, and wear safety glasses and work gloves. Have quenching cloth available (step 7).
56
CAUTION: Copper tubing and aluminum fins
are used in unit coils. Do not overbeat or place
excessive strain on tubing or dam^e may result.
1. Shut off power to unit. Failure to do so may result in electrical shock. Remove unit com pressor section access panels. Fig. 1 and 5.
2. Remove refrigerant from unit using refrigerant removal methods described in Carrier Standard
Service Techniques Manual, Chapter 1.
3. Remove core from suction and discharge line
Schrader valves.
11
4. Disconnect compressor wiring at compressor terminal box.
5. Using a tubing cutter, cut suction and dis charge lines at convenient place near com pressor for easy reassembly to new compressor with copper slip couplings.
CAUTION: Excessive movement of copper
lines at compressor may cause a break where lines connect to coil.
6. Remove compressor holddown bolts and lift
compressor out.
7. Carefully unbraze suction and discharge line piping stubs from compressor. If oil vapor in piping stubs ignites, use quenching cloth.
8. Braze piping stubs (removed in step 7) on new compressor.
9. Clean system.
10. Install new compressor in unit. Braze suction and discharge lines to compressor piping stubs (at points where cut, step 5) using field­supplied copper couplings. Ensure compressor holddown bolts are in place. Connect wiring.
11. Evacuate and recharge unit.
CAUTION; Before performing recommended maintenance, be sure main power switch to unit is turned off.

Lubrication

COMPRESSOR contains factory oil charge. Re place oil when lost. See Table 6 for oil recharge. If necessary, refer to Carrier Standard Service Tech niques Manual, Chapter 1, pages 1-21, for oil recharging procedure. Use Carrier PP33-1, Texaco Capella B or Suniso 3G oil.
FAN MOTOR BEARINGS are prelubricated for 3 years heavy-duty or 5 years normal-duty service.
Cleaning Coil and Condensate Pan — Clean
and inspect coil, condensate pan and drain before each cooling season.
1. Remove coil section access panels and slide air filter out of filter flanges.
2. Disconnect condensate drain line at pan drain connection.
3. Use vacuum cleaner nozzle to clean the face of coil.
4. Clean condensate drain trap with a bottle brush.
Clean condensate pan.
5. Hold pail under condensate pan drain connec tion and flush pan out with clean water. Ensure
water flows freely thru condensate drain. Do not overflow pan.
6. Reconnect condensate drain line.
7. Install access panel and air filter.
Indoor Fan Wheel should be centered in housing.
To adjust fan, loosen setscrew holding fan to motor shaft. Adjust fan and retighten setscrew.
50VQ INDOOR BLOWER ASSEMBLY REMOVAL
1. Remove fan section access panel.
2. Remove power wires from Molex plug.
3. Place a spacer beneath blower housing for support.
4. Remove blower assembly mounting bracket. (Rear flange on top of blower housing and screws now hold blower assembly in place.)
5. Support blower housing at bottom and remove
spacer. Tilt blower assembly downward and lift out of unit.
50HQ INDOOR BLOWER ASSEMBLY REMOVAL
1. Remove top cover (Fig. 2).
2. Remove power wires from Molex connector (Fig. 7).
3. Remove blower assembly mounting screws from
base unit (Fig. 2).
4. Lift blower assembly out of unit.

Indoor Fan and Motor Removal

1. Remove blower assembly from unit.
2. Remove Molex plug from bracket on fan
housing.
3. Loosen setscrew holding fan to motor shaft.
4. Loosen motor mounting band and remove
motor.
5. Remove fan cutoff plate from blower housing
outlet.
6. Remove fan wheel from blower housing outlet.
Clean Indoor Fan Wheel — When coil is cleaned,
remove caked-on dirt from fan wheel and housing with brush; remove grease with mild solvent. When replacing blower assembly, make sure fan wheel is centered in housing.
Return Air Filter — Replace filter media 4 times a
year. For other types of filters, refer to filter manu facturer’s instructions as required.
CAUTION; Nev«r operate unit W3tltcwi.t a filter as coil wilt plug and damage to fan motor may result.
Heat Exchanger — If excessive discharge pressure
is experienced with normal water flow, the heat exchanger tubes may be fouled and require cleaning.
Contact a local water treatment firm for details on
chemical cleaning.
12
^ TROUBLESHOOTING CHART
PROBLEM
ENTIRE UNIT DOES NOT RUN
BLOWER OPERATES BUT COMPRESSOR DOES NOT
UNIT OFF ON LOW
WATER TEMPERA TURE CONTROL
UNIT SHORT CYCLES
CAUSE
Blown fuse
Broken or loose wires
Voltage supply low
Transformer Thermostat
Voltage supply low
Thermostat Wiring
High-pressure controls
Defective capacitor
Seized compressor
Compressor overload open
Compressor motor grounded
Compressor windings open
Low water temperature cutout open (LWTC)
Water temperature too low
on heating
Low water temperature switch
Wiring and controls
Compressor overload
CORRECTION
Replace fuse or reset circuit breaker.
Repiace or tighten the wires. If voltage is below minimum voltage specified on dataplate, contact
local power company Check 24-volt transformer for burnout or voltage less than 18 volts Set thermostat on COOL and lowest temperature setting, unit
should run Set thermostat on HEAT and highest temperature setting, unit should run. Set fan to ON, fan should run If unit does not run in all 3 cases, the thermostat could be wired incorrectly, or faulty To ensure faulty or miswired thermostat, disconnect thermostat wires at unit and jumper between R, Y, G and W ter
minals and unit should run
If voltage is below minimum voltage specified on the dataplate, contact local power company
Check setting, calibration and wiring.
Check for loose or broken wires at compressor, capacitor or contactor. ___ The unit could be off on the high-pressure cutout control. Reset the
thermostat to OFF After a few minutes, turn to COOL If the com
pressor runs, unit was off on high pressure (See Problems for
possible causes )
If the unit still fails to run, check for faulty pressure switch by jumpering the high-pressure control
Check capacitor or Start Thermistor (PTC). If defective, remove,
replace and revise correctly.
Try a start capacitor in parallel with the run capacitor momentarily.
If the compressor starts but the problem reoccurs on starting, install an auxiliary start kit The hard start kit is comprised of a recommended start relay and correctly sized capacitor If the
compressor still does not start, replace the compressor
In all cases, an external or internal temperature sensitive com pressor overload is used If the compressor dome is too hot to
touch, the overload will not reset until the compressor cools down.
If the compressor is cool and the overload does not reset, there
may be a defective or open overload If the overload is external,
replace the overload, otherwise, replace the compressor Internal winding grounded to the compressor shell. Replace the
compressor
Check continuity of the compressor windings with anohmmeter If
the windings are open, replace the compressor. The unit could be off on the LWTC Reset the thermostat to OFF.
After a few minutes, turn to HEAT If the compressor runs, unit was
off on LWTC (see Problems for possible causes). Lack«,of or inadequate water flow
Entering water too cold. Scaled or plugged heat exchanger ____ _
Check for defective or improperly calibrated low water temperature switch
Loose connections in the wiring or the control contactors defective Defective compressor overload, check and replace if necessary If
the compressor runs too hot, it may be due to the deficient refrig
erant charge
_____ ______
____________________
_
13
TROUBLESHOOTING CHART (cont)
PROBLEM
INSUFFICIENT COOLING OR
HEATING
NOISY OPERATION
CAUSE
Unit undersized
Loss of conditioned air by leaks
Thermostat
Airflow
Refrigerant charge
Compressor
Reversing valve
Operating pressure Refrigerant system
Compressor
Blower and blower motor
Contactors
Rattles and vibrations
Airborne noises and
other sounds
CORRECTION
Recalculate heat gains or losses for space to be conditioned. If excessive, rectify by adding insulation, shading, etc.
Check for leaks in ductwork or introduction of ambient air thru doors and windows
Improperly located thermostat (e g near kitchen sensing in
accurately the comfort level in living areas).
Lack of adequate airflow or improper distribution of air. _ _ Low on refrigerant charge causing inefficient operation. Check for defective compressor. If discharge pressure is too low
and suction pressure is too high, compressor is not pumping properly. Replace compressor.
Defective reversing valve creating bypass of refrigerant from dis charge to suction side of compressor
Incorrect operating pressure (See chart.) Check strainer and capillary tubes for possible restrictions to flow
of refrigerant
The refrigerant system may be contaminated with moisture, non-
condensables, and particles _ ^
Dehydrate, evacuate and recharge the system. Make sure the compressor is not in direct contact with the base or
sides of the cabinet The holddown bolts used for shipping should
be loosened so that the compressor is floating free on its isolator mounts. Excessive noise will occur if the compressor has a broken
valve or loose discharge tube. Replace the compressor
Blower wheel hitting the casing Adjust for clearance and align ment Bent blower, check and replace if damaged Loose blower
wheel on shaft Check and tighten Defective bearings, check and
replace
A clattering or humming noise in the contactor could be due to
control voltage less than 18 volts. Check for low supply voltage, low transformer output or extra long runs of thermostat wires If the contactor contacts or coil is defective, repair or replace
Check for loose screws, panels or internal components Tighten and secure. Copper piping could be hitting the metal surfaces Carefully readjust by bending slightly
Undersized ductwork will cause high airflow velocities and noisy operation. Excessive water thru the water-cooled heat exchanger will cause a rattling sound Throttle back on the water flow ensuring adequate flow for good operation but eliminating the noise
____________________________
__
_ _ _ _
______________
_____________
_
_______ _
_
_____ _
_
_____ ________
_
For replacement items use Carrier Specified Parts.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
Tab 5a 5a
4
Form 50HQ,VQ-2SI Supersedes 50HQ,VQ-1 SI PrintedinUSA 9-81 PC 111 Catalog No 535-029
Loading...