Single-Package Rooftop Heat Pump Units
Installation, Start-Up and
Service Instructions
50HJQ008-012
CONTENTS
Page
SAFETY CONSIDERATIONS ...................... 1
INSTALLATION ................................ 1-38
Step 1 -- Provide Unit Support ................... 1
• ROOF CURB
• SLAB MOUNT
• ALTERATE UNIT SUPPORT
Step 2 -- Field Fabricate Ductwork ............... 2
Step 3 -- Install Condensate Drain Line and
External Trap .................................... 2
Step 4 -- Rig and Place Unit ..................... 2
• POSITIONING
Step 5 -- Make Electrical Connections ........... 7
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
• DEFROST BOARD
• HEAT ANTICIPATOR SETTINGS
Step 6 -- Adjust Factory-Installed Options ...... 13
• DISCONNECT SWITCH
• CONVENIENCE OUTLET
• NOVAR CONTROLS
• MANUAL OUTDOOR-AIR DAMPER
• PREMIERLINK TM CONTROL
• ENTHALPY SENSORS AND CONTROL
• OPTIONAL ECONOMI$ER IV AND ECONOMI$ER2
• ECONOMISER IV STANDARD SENSORS
• ECONOMISER IV CONTROL MODES
Step 7 -- Adjust Indoor-Fan Speed .............. 25
PRE-START-UP .................................. 39
START-UP .................................... 39-42
SERVICE ..................................... 42-44
TROUBLESHOOTING ......................... 45-48
INDEX ........................................... 49
START-UP CHECKLIST ........................ CL-I
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filtet.s. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precau-
tions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguisher available for all brazing operations.
Before performing service or maintenance operations on
unit, turn off main power switch to unit and install lockout
tag. Ensute voltage listed on unit information plate agrees
with electrical supply to rite unit. Electrical shock could
cause serious personal injury.
INSTALLATION
Unit is shipped in the vertical configuration. To convert to
hotizont_dconfiguration, remove side duct opening covers. Us-
ing the same screws, install covers on vertical duct openings
with the insulation-side down. Seals around duct openings
must be tight.
Step 1 -- Provide Unit Support
ROOF CURB -- Assemble and inst_dlthe accessoty roof curb
in accordance with instructions shipped with the curb. See
Fig. 1. Install insulation, cant strips, roofing felt, and counter
flashing as shown. Ductwork must be attached to the curb. If
electric or control power is to be routed through the basepan,
attach the accessory thru-the-bottom service connections to the
basepan in accor&mce with the accessory installation instruc-
tions. Connections must be installed before the unit is set on
roof curb.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electtic_d compo-
nents. Only trained and qualified service personnel should
install, repair, or service ai>conditioning equipment.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500017-01 Printed in U.S.A, Form 50HJQ-17SI Pg 1 9-05 Replaces: 50HJQ-14SI
critical for watertightness. Install gasket supplied with the
roof curb as shown in Fig. 1. hnproperly applied gasket can
I IMPORTANT: The gasketing of the unit to the roof curb is I
also result in air leaks and poor unit performance.
I
The roof curb should be level. Unit leveling tolerances am
shown in Fig. 2. This is necessmy for unit drain to function
properly. Refer to Accessory Roof Curb Installation Instruc-
tions for additional information, as required.
SLAB MOUNT (Horizontal Units Only) -- Provide a level
concrete slab that extends a minimum of 6 in. beyond file unit's
cabinet. Inst_fll a gravel apron in front of the condenser coil air
inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
ALTERNATE UNIT SUPPORT -- When the curb or adapter
cannot be used, support unit with sleepers using unit curb or
a&Tter support area. If sleepers cannot be used, support
the long sides of the unit with a minimum of 3 equally spaced
4-in. x 4-in. pads on each side.
Step 2 -- Field Fabricate Ductwork -- On vertic;d
discharge units, secure all ducts to the roof curb and building
structure. Do not connect ductwork to the unit. For horizontal
applications, field-supplied flanges should be attached to hori-
zontal discharge openings and all ductwork attached to the
flanges. Insulate and weatherproof all external ductwork,
joints, and roof openings with counter flashing and mastic in
accor&mce with applicable codes.
Ducts passing through an unconditioned space must be in-
sulated and covered with a vapor barriel:
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with applica-
ble fire codes.
A minimum clearance is not required around ductwork.
Cabinet return-air static pressure (a negative condition) should
not exceed 0.35 in. wg with economizer, or 0.45 in. wg without
economizer.
Step 3 -- Install Condensate Drain Line and
External Trap -- Condensate di'ain connections ;ue
located at the bottom and end of the unit. Unit discharge
connections do not determine the use of drain connections; use
either drain connection in vertic_d or horizontal applications.
When using the standmd end diain connection, make sure
the plug (Red) in the _dternate bottom connection is tight before
installing the unit.
To use the bottom drain connection for a roof curb installa-
tion, relocate the factory-installed plug (Red) from the bottom
connection to the end connection. Tile center di'ain plug looks
like a star connection, but can be removed with a I/2 in. socket
drive extension. See Fig. 3. The piping for the condensate di'ain
and external trap can be completed after the unit is in place.
All units must have an extern_fl trap for condensate di'ain-
age. [nstall a trap at least 4-in. deep and protect it against
freeze-up. If the drain line is installed downstream from the ex-
tern_d trap, pitch the line away from the unit at 1 in. per 10 ft of
run. Do not use a pipe size smaller than the unit connection
(314in.). See Fig. 4.
Step 4 -- Rig and Place Unit --Inspect the unit for
transportation damage. File any claim with the transportation
agency. Keep the unit upright and do not diop. Spreader bars
are not required if top crating is left on the unit. Rollers may be
used to move the unit across a roof. Level by using the unit
frame as a reference. See Table 1 and Fig. 5 for additional
information. Operating weight is shown in Table 1 and Fig. 5.
Lifting holes are provided in the base rails as shown in
Fig. 5 and 6. Refer to the rigging instructions on file unit.
POSITIONING --Maintain clearance m'ound and above the
unit to provide proper airflow and service access. See Fig. 6.
Position the unit on the roof curb so that the following
clearances are maintained: %-in. clearance between roof
curb and base rails on each side and in duct end of unit;
3s/16-in. clearance between the roof curb and outdoor coil
end of the unit (see Fig. 1, section C-C).
Do not install the unit indoor._. Do not locate the unit's air
inlet near exhaust vents or other soumes of contaminated all:
Although the unit is weatherproof, gumd against water from
higher level runoff and overhangs.
After the unit is in position, remove the polyethylene ship-
ping wrapper and rigging skid.
CONNECTOR ! B I C DRAIN GAS POWER .......
PKG. ACCY, I I I HOLE I I IL'UR/HUL I POWER
......... l-- -I -- I- -- - --I .... "$s ..... I ..... I--
CRB-TM-P-WR001-A0-11 I I , 3/4" _/4_"[_19]_N_P_ ,
i = I ACCESSORY
C_RB_TM2_WEO£2_AO_I,, , . [LCLN£Ti_lW'j_.7], ,
CRBTMPWROO3A01 [827] [583] [44.5] 127NPT /4" [19] NPT [12.7] NPT [12.7]NPT
CRBTMPWROO4AOOI I I I 3/4" I 1V4"[31.7] I I
2'-87/16" 1'-1015/16" 13/4" 1/2" 3 1/2" 1/2"
--I-- .J -- L. ....... I ..... I--
_i_It9_1_NP_T.
ROOF CURB I I
ACCESSORY I "A" I UNIT SIZE
"CRRF_U-RB0_3AOTII_ '---2'r[3_ 6_ I- - .........
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels: 1-in. thick polyurethane foam,
1s/4 Ib density.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: 16-gage steel.
5. Attach ductwork to curb (flanges of duct rest on
curb).
6. Service clearance 4 ft on each side.
7. _ Direction of airflow.
8. Connector packages CRBTMPWROO1A01 and
2A01 are for thru-the-curb gas type. Packages
CRBTMPWROO3A01 and 4A01 are for the thru-
the-bottom type gas connections.
O" €"
[76]
0' €"
E7C]
1" 31/4" I
[38?3
[11]
(COLT CEACC)
O' O 7/15"
C" 0 1/4"[?]
[113_
I
CUPPLY AIR l
OPENING "C"
I
I
[786]
2" 6 15/1Gj
O'
[763
4' 0 13/16"
[1240]
I- D-
/
GASKET
(SUPPLIED WITH CURB;
DUCT
[FIELD SUPPLIED)
TYPICAL (4) S[OES
O" 7/15"
(FIELD SUPPLIED)
FLACB NG;
€" € €/€"
O" O 7/15"
(BOLT BEADS)
O' 0 7/1G"
(BO_TAEACC]
[11]
[IOO6]
RIGID INCULAT[ON
(FIELD CUPPLIED)
I
#
B [€4]
o' 2 1/8"
1" 8 3/16"
[513]
ClN5IOE)
(FIELD CUPPLIED) o
OPENING FOR CACEPAN
ENTRY CERVICE (CEE NOTE _€)
[290]
O' 4 5/16"
[llO]
INSIDE)
SECTION "C C"
CCALE 1=4
CEE NOTE #2
€/15"
HEAD OF BOLT TO BE ON
INSIDE OF FLANGE
O" 1 7/8"
[48]
_ (Ty p _/]AEL_ iOBRNERC )
4;
CUPPLY A[R
VIEW
"A-A"
O" l"
[25]
RETURN
R
I
SEE VIEW
4" 1 3/4"
[1264]
Fig. 1 -- Roof Curb Details
TYP
2 3/€ °
[51]
3]
I
I
I
I
I
G" G"
[1CC1]
NOTE= CAMCRIDGEPORT "CURE LOCK" CORNER
FACTEN[NG DEVICE IC ACCEPTABLE
ALTERNATE CONSTRUCT)ON,
MINIMUM PITCH
ONE IN PER
lOFT ()F LINE
RA,LI itF
IIII
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B I B-C A-C
0.5 I 1.0 1.0
Fig. 2 -- Unit Leveling Tolerances
HORIZONTAL DRAIN PLUG
DRAIN OUTLET
NOTE:Drain plug is shown in factory-installed position.
Fig. 3 -- Condensate Drain Pan
(Side View)
91 4-1 371 CLOSE TO THIS ENDAS POSSIBLE
(36"-54") _,
T OOF
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4-in. trap is recommended.
POSITION ALL SEAL STRIPS
IN PLACE BEFORE INSTALLING
UNIT ON ROOF CURB AS
SEE DETAIL DUCT END
DRAIN PLUG
Fig. 4- Condensate Drain Piping Details
"DETAIL A"
T
SEE
NOTE
.._ROOF
CURB
NOTES:
1. Dimension in ( ) is inches. Dimensions outside ( ) are millimeters. 50HJQ
2. Hook rigging shackles through holes in base rail, as shown in UNIT
detail "A." Holes in base rails are centered around the unit cen- SIZE
ter of gravity. Use wooden top skid when rigging to prevent rig-
ging straps from damaging unit. 008
3. Unit weights do not include economizer. See Table 1 for econo- 009
mizer weights. 012
All panels must be in place when rigging. Unit is not designed for
handling by a fork truck. Damage to unit may result.
Fig. 5 -- Rigging Details
OPERATING
WEIGHT
Ib kg
870 395
1000 454
1000 454
_,A _,
in. mm
77.42 1966.5
77.42 1966.5
77.42 1966.5
in. mm
41.5 1054
41.5 1054
41.5 1054
,,C _,
in. mm
42,12 1070
42,12 1070
42,12 1070
Table1-- Physical Data
50HJQ UNIT SIZE
NOMINAL CAPACITY (tons)
OPERATING WEIGHT (Ib)
Unit
EconoMiSer IV
Roof Curb
COMPRESSOR
Quantity
Oil (oz) (each compr)
REFRIGERANT TYPE
Operating Charge (Ib)
Circuit 1
Circuit 2
OUTDOOR FAN
Quantity...Diameter (in.)
Nominal Cfm
Motor Hp...Rpm
OUTDOOR COIL
Rows...Fins/in.
Total Face Area (sq ft)
INDOOR FAN
Quantity...Size (in.)
Type Drive
Nominal Cfm
Maximum Continuous Bhp
Motor Frame Size
Nominal Rpm
Fan Rpm Range
Motor Bearing Type
Maximum Allowable Rpm
Motor Pulley Pitch Diameter MiniMax (in.)
Nominal Motor Shaft Diameter (in.)
Fan Pulley Pitch Diameter (in.)
Belt, Quantity...Type...Length (in.)
Pulley Center Line Distance (in.)
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full
Turns from Closed Position
Factory Setting
Factory Speed Setting (rpm)
Fan Shaft Diameter at Pulley (in.)
INDOOR COIL
Rows...Fins/in.
Total Face Area (sq ft)
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief
Cutout
Reset (Auto.)
LOSS-OF-CHARGE/LOW-PRESSURE SWITCH (Liquid Line) (psig)
Cutout
Reset (Auto.)
FREEZE PROTECTION THERMOSTAT
Opens (F)
Closes (F)
OUTDOOR-AIR INLET SCREEN
RETURN-AIR FILTERS
Ouantity...Size (in.)
LEGEND
Bhp -- Brake Horsepower
Standard
High-Static
Standard
High-Static
Standard
High-Static
Standard
High-Static
Standard
High-Static
Standard
High-Static
Standard
High-Static
Standard
High-Static
Standard
High-Static
Standard
High-Static
Standard
High-Static
Standard
High-Static
Standard
High-Static
Standard
High-Static
Standard
High-Static
008 009 012
71/2 81/2 10
870 1000 1000
75 75 75
223 223 223
Scroll
2 I 2 I 257 70 57
R-22
9.5 11.0 10.7
9.5 11.O 10.8
2...22 2...22 I 2...22
6500 6500 I 65001/4...1100 1/4..,1100 1/4.,.1100
Enhanced Copper Tubes, Aluminum Fins, AcutroF M Metering Device
2...17 I 2...17 I 2...1720.5 25.1 25.1
1...15 x 15 1...15 x 15 1...15 x 15
1...15 x 15 1...15 x 15 1...15 x 15
Belt Belt Belt
Belt Belt Belt
3000 3400 4000
2.90 2,90 3,70
3.70 3.70 5.25
56 56 56
56 56 56
1725 1725 1725
1725 1725 1725
730-950 840-1085 860-1080
860-1080 860-1080 830-1130
Ball Ball Ball
1300 1300 1300
3.4/4.4 3.4/4.4 4.0/5,0
4.0/5.0 4.0/5.0 2.8/3,8
7/8 7/8 7/8
7/8 7/8 7/8
6.0 7.0 8.0
8.0 8.0 5.8
1...A...51 1...A...51 1...A...53
1...A...53 1...A...53 1...BX...48
16,75-19,25 16,75-19,25 15.85-17.50
16.75-19.25 16.75-19.25 15.85-17,50
45 45 45
45 45 60
5 5 5
5 5 6
5 5 5
5 5 5
730 840 860
860 860 887
1 1 1
Enhanced Copper Tubes, Aluminum Double-Wavy Fins,
3...15 I 4...15 I 4...156.9 11.1 11.1
Cleanable. Screen size and quantity vary by option selected.
4..,16x20x2 I 4...20x20x2 I 4._20x20x2
Propeller
Centrifugal Type
Acutrol Metering Device
625
428
32O
7_+3
22_+5
3O
45
Throwaway
UNIT HEIGHT HEIGHT W/ P E. WEIGHT CORNER WEIGHT (A) CORNER WEIGHT (B) CORNER WEIGHT (C) CORNER WEIGHT (D) "N"
5OHJQOO8 870 395 3 1 1 BSI 9 198 90 183 83 237 108 252 114 2' 0 7/8" 532
SOHJQOO9,012 lOOO 231 105 214 97 269 122 285 130 2" 10 7/8" 885
NOTES=
1. DIMENSIONS IN [ ] ARE iN MILLIMETERS.
2. _CENTER OF GRAVITY.
3. _ DIRECTION OF AIR FLOW.
4. DUCTWORK TO BE ATTACHED TO ACCESSORY ROOF CURB ONLY.
5. MINIMUM CLEARANCE (LOCAL CODES OR JURISDICTION MAY
PREVAIL):
o. BOTTOM TO COMBUSTIBLE SURFACES (WHEN NOT USING CURB)
O INCHES, ON HORIZONTAL DISCHARGE UNITS HITH ELECTRIC
HEAT 1 INCH CLEARANCE TO DUCTWORK FOR 1 FOOT.
b. OUTDOOR COIL, FOR PROPER AIR FLOW, 35 INCHES
ONE SIDE, 12 INCHES THE DTHER. THE SIDE GETTING THE
CREATER CLEARANCE 15 OPTIONAL.
c. OVERHEAD, 50 INCHES TO ASSURE PROPER OUTDOOR FAN
OPERATION.
d. BETWEEN UNITS, CONTROL BOX SIDE, 42 IN. PER NEC.
e. BETWEEN UNIT AND UNGROUNDED SURFACES, CONTROL BOX
SIDE, 35 IN. PER NEC.
F. BETWEEN UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, CONTROL BOX SIDE, 42 IN. PER NEC.
9- HORIZONTAL SUPPLY AND RETURN END, 0 INCHES WHEN THE
ALTERNATE CONDENSATE DRAIN IS USED.
5. WITH THE EXCEPTION OF THE CLEARANCE FOR THE OUTDOOR
COIL AS STATED IN NOTES 5u, b, AND c, A REMOVABLE
FENCE OR BARRICADE REQUIRES NO CLEARANCE.
7. UNITS MAY BE INSTALLED ON COMBUSTIBLE FLOORS MADE
FROM HOOD OR CLASS A, B, OR C ROOF COVERING MATERIAL.
8.
THE VERTICAL CENTER OF GRAVITY [5 1" 7 1/2" FOR
OOB , 2' 0"[510] FOR 009 AND 012 UP FROM THE BOTTOH OF THE
BASE RAILI
I 3Z8"
DIA. [35] FIELD POWER SUPPLY HOLE
5TO. UNIT ECONOMIZER IV HERT ECON IV
LB 45KG4 LBT_ KG4_ LBiS KG LB KG LB KG LB KG LB KG FT IN. MM
SIZES
" "F ?
OF UNIT
BOTTOM
O" 4_9/16"
[llB]
0" 2 9/18 "_"
[55] TYP
i
OUTDOOR COIL L C 2['510913/8"
_,_ r--m \ EC
"
LEFT SIDE DISCONNECTLOCATION
FILTER/ECONOMIZER ACCE55 PANEL
OUTDOOR COIL
CORNER "A'_
4" 9 3/4"
[1467]
LEFT
SIDE
CORNER "D "_
-- D.EI 4HB.
B [B7]
OUTSIDE AIR
s S
REAR
3'[%91] ECONOMISER IV HOOD I_/I0 1/4" [555]
/_'I"f-_INDOOR I 11403
ALT. CONDENSATE I I
II IN BASEPAN
_O DRAIN OPENING
II ' ? 1/21_SEE NOTE #E
SEE BOTTOM POWER
CHART (ELEC, ONLY)
F/ ECONOMISER IVAND [BO]
POWER EXHAUST
O" 3 1/8"
[79] _
I RETURN AIR OPENING I l" O 5/B _
, VERTICAL _ [320]
_ _ RETURN AIR
I SUPPLy I
AIR I
I I
I I
I I
(_B1.B_ FRONT
_3' 4 1/4"_
El022]
CONTROL BOX/ BLOWER AND ELECTRIC
COMPRESSOR ACCESS PANEL HEAT ACCESB PANEL
7' 3 3/8"
[2219]
FORK TRUCK SLOTS
INDOOR FAN MOTOR.
[20B]
O' 0 3/8"
[IO] _
O" 2 1/4" [573
(TYP B PLACE5)
FRONT
CORNER "B"
ECONOMIGER IV
(_50_RIGHT SIDE
SUPPLY AIR
' 5 ?/16"
[79]
CORNER "C"
SUPPLY AIR \ I I
I HORIZONTAL I [635]
OF PANEL _'BAROMETRIC RELIEF D[SCHAGE
OHTSIDE 8 __ 1_
SUPPLY AIR / RETURN AIR
Fig. 6 -- Base Unit Dimensions
• jr "K"
3" 5 5/18" 1050 2' 9 11/16" 856
FT IN. MM B' 0 3/8 _ MM4" 1 5/18" FT IN.
THESEHOLES REQ'D FOR USE
WITH ACCESSORYPACKAGES
O" 7 5/1 G"
[lB5]
[719]
OPENING I 2" 1"
3" l" ll/16
[940] El 78] El 44]
1253 924
BOTTOMPOWERCHART=
CRBTMPWROO1A01,2A01
2" I"
O" 4 ° ECONOMISER IV
[I01] H/ POWER EXHAH5T
1" O 5/B"
[320] FILTER ACCE55 PANEL
I
I RETURN
AIR
IDPENING
I
ZONTAL
I
I
I OUTSIDE AIR
FILTER ACCE5S PANEL
(DISPOSABLE FILTERS)
BLOCKOFF
PANEL
RIGHT SIDE
LE 5TD. CONDENSATE DRAIN
r-----n
VIEW S S
O" [O OO]
VERTICAL
FILTERS)
I
Step 5 -- Make Electrical Connections
Unit cabinet must have an uninterrupted, unbroken electri-
cal ground to minimize the possibility of personal inju U if
an electrical fault should occm_ This ground may consist of
electrical wire connected to unit ground lug in control com-
partment, or conduit approved for electrical ground when
installed in actor&race with NEC (National Electrical
Code) ANSI (American Nation_d Standiu_ds Institute)/
NFPA (Natiomd Fire Protection Association) 70 latest revi-
sion and local electric_d codes. Failure to follow this warn-
ing could result in the installer being liable for persomd
inju U of others.
FIELD POWER SUPPLY -- All units except 208/230-v units
are factory-wired for the voltage shown on the unit nameplate.
If the 208/230-v unit will be connected to a 208-v power sup-
ply, the transformer must be rewired by disconnecting the
black wire fiom the 230-v l/4-in, male spade temrinal on the
transformer and connecting it to the 200-v l/4-in, m_de spade
terminal fiom the transformel_
Refer to the unit label diagram for additional infommtion.
Pigtails are provided for field wire connections. Use facto U-
supplied splices or a UL (Underwriters' Laboratories) ap-
proved copper/aluminum connectol:
When inst_dling units, provide a disconnect per the NEC.
All field wiring must comply with the NEC and local re-
quirements. In Canada, electrical connections must be made in
accor&mce with CSA (Canadian Stan&_rds Association) C22.1
Canadian Electric_d Code Part One.
Inst_dl field wiring as follows:
1. Inst_dl conduit through the unit's side panel openings. For
units without electric heat, install conduit between the
disconnect and control box.
2. Inst_dl power lines to terminal connections as shown in
Fig. 7.
3. For units with electric heat, refer to Table 2 and
Accessory Installation Instructions.
During operation, voltage to compressor terminals must
be within the range indicated on the unit nameplate (see
Tables 3A-3D). On 3-phase units, voltages between phases
must be balanced within 2%, and the current within 10%. Use
the formula shown in Tables 3A-3D, Note 2 on page 11 to
determine the percentage of voltage imbalance. Operation on
iml)rOl)er line voltage or (_rcessive phase imbalance constitutes
abuse and may cause damage to electrical components. Such
ol)eration invalidaws an)" applicable Carrier warrant).'.
BLK
FIELD POWER SUPPLY
I I I
I DISCONNECTII,'IN]
[ PER NEC
TO COMP 2
T
BLU ORN
C -- Contactor
COMP- Compressor
IFC -- Indoor Fan Contactor
NEC -- National Electrical Code
[ll.rG-] Equipment Grounding Plug
-- Factory Wiring
Fig. 7-- Power Wiring Connections
LEGEND
Splice Connection
(Factory Supplied)
Field Wiring
Table 2 -- Electric Heating Capacities
50HJQ VOLTAGE ACCESSORY HEATER
UNIT (60 Hz) kW PART NUMBER POINT BOX PART NO.
SIZE CRSINGLE---A00
7.8/ 9.6/10.4 117 007
208/230/240 12.0/14.7/18.0 110 007
(3 phase) 16.6/22.6/24.8 111 009
008 31.8/39.0/42.4" 112,117 013
(71/2Tons) 12.6/13.9 116 008
460/480 15.2/16.5 113 008
(3 phase) 38.4/33.0 115 008
208/230/240 18.6/22.8/24.8 111 015
(3 phase) 24.0/29.4/32.0 112 015
009 31.8/39.0/42.4" 112,117 017
(81/2Tons) 12.8/13.9 116 011
460/480 25.6/27.8 114 014
(3 phase) 30.4/33.0 115 014
208/230/240 24.0/29.4/32.0 112 015
(3 phase) 31.8/39.0/42.4" 112,117 017
012 37.6/46.2/50.0" 112,110 017
(10 Tons) 15.2/16.5 113 011
460/480 30.4/33. O 115 014
(3 phase) 38.4/41.7" 114,116 016
*Two heater packages required to provide kW indicated.
NOTES:
1. The rated heater voltage is 240 and 480 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.
2. To determine heater kW at voltages other than those shown in table, use the following formula:
Heater kWnew= Heater kW rated x (unit power distribution voltage/rated heater voltage) 2
As an example:
For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v
kWnew= 16 kW (215/240) 2
kWnew= 12.8 kW (rating at 218 v)
24.0/29.4/32.0 112 009
25.6/27.8 114 008
38.4/41.7" 114,116 --
7.8/ 9.6/10.4 117 012
12.0/14.7/16.0 110 012
15.2/16.5 113 011
38.4/41.7" 114,116 016
7.8/ 9.6/10.4 117 012
12.0/14.7/16.0 110 012
25.6/27.8 114 014
46.0/50.0" 115,113 016
ACCESSORY ACCESSORY SINGLE
CRHEATER---A00
Table 3A -- Electrical Data -- Standard Motor Units Without Electrical Convenience Outlet
50HJQ
UNIT
SIZE
O08
(7112 Tons)
009
(8112Tons)
012
(10 Tons)
NOMINAL VOLTAGE COMPRESSOR OFM IFM ELECTRIC HEAT*
VOLTAGE RANGE (each) (each)
(V-Ph-Hz) Min Max RLA LRA FLA FLA kW** FLA
208/230-3-60 187 254 12.4 88.0 1.4 7.5 12.0/16.0 33.3/ 38.5
460-3-60 414 508 6.4 44.0 0.7 3.4 16.5 19.8
208/230-3-60 187 254 13.9 105 1.4 7.5 12.0/16.0 33.3/ 38.5
460-3-60 414 508 7.9 55.0 0.7 3.4 16.5 19.8
208/230-3-60 187 254 19.3 123.0 1.4 10.6 12.0/16.0 33.3/ 38.5
460-3-60 414 508 10.0
62.0 0.7 4.8 27,8 33.4
78/10.4 217/ 250
18.6/24.8 51.6/ 59,7
24.0/32.0 66.6/ 77.0
31.8/42.4 88.3/102.0
13.9 16.7
27.8 33.4
33.0 39,7
41.7 50.2
7.8/10.4 21.7/ 25,0
18.6/24.8 51.6/ 59,7
24.0/32.0 66.6/ 77.0
31.8/42.4 88.3/102.0
13.9 16.7
27,8 33.4
33.0 39,7
41.7 50.2
7.8/10.4 21.7/ 25.0
24.0/32.0 66.6/ 77.0
31,8/42,4 88.3/102,0
37.6/50.0 104.4/120.3
16,5 19.8
33.0 39,7
41,7 50,2
50.0 60.1
POWER SUPPLY
MCA
38.2/ 38.2
65.3/ 69.5
79.8/ 86.3
102.7/112.8
121.5/134.5
148.6/165.7
19,2
40.1
44.0
61.0
68.8
82.0
41.3/ 41.3
68.4/ 72.5
82.9/ 89.4
105.8/115.9
124.5/137.5
151.7/168.8
22.3
43,2
47.0
64.0
71.9
85.0
56.8/ 56.8
84.0/ 88.1
98.5/105.0
140.1/153.1
167.2/184.3
187.3/177.1
28.7
53,5
70.5
78.3
91.5
88.8
MINIMUM UNIT
DISCONNECT
SIZEt
MOCP FLA LRA
40/ 40tt 40/ 40 242/242
70/ 70tt 65/ 69 264/267
80/ 90 79/ 85 275/281"**
110/125 100/109 294/302"**
125/150 117/129
150/175 142/158
2Oft 20
451t 39
45ft 43
70 59
70 66
90 78
45/ 45it 43/43
70/ 80tt 68/72
90/ 90 82/88
110/125 103/112
125/150 120/132
175/175 145/161
25ft 23
45ft 43
5Oft 46
70 62
80 69
90 81
60/ 6Oft 60/ 60
90/ 90 85/ 89
100/110 98/104
150/175 136/148 403/414***
175/200 161/177 425/439"**
200/200 180/198 441/457"**
30tt 30 170
60tf 53 189
80 69 203
80 76 209
100 88 220***
100 99 230***
309/319***
330/344"**
121
138
141
155
161
171
276/276
298/301
309/315"**
328/336"**
343/353"**
364/378"**
143
160
163
177
183
193
337/337
358/362"**
370/375"**
Table 3B -- Electrical Data -- Standard Motor Units With Electrical Convenience Outlet
50HJQ
UNIT
SIZE
OO8
(7112 Tons)
009
(8112Tons)
012
(10 Tons)
NOTE: See legend and notes on page 11.
NOMINAL VOLTAGE COMPRESSOR OFM
VOLTAGE RANGE (each) (each) IFM ELECTRIC HEAT*
(V-Ph-Hz) Min Max RLA LRA FLA FLA kW** FLA
208/230-3-60 187 254 12.4
460-3-60 414 508 6.4
208/230-3-60 187 254 13.9 105
460-3-60 414 508 7.9 55.0
208/230-3-60 187 254 19.3 123.0
460-3-60 414 508 10.0 62.0
88.0 1.4 7.5 12.0/16.0 33.3/ 38.5
44.0 0.7 3.4 16.5 19.8
1.4 7.5 12.0/16.0 33.3/ 38.5
0.7 3.4 16.5 19.8
1.4 10.6 12.0/16.0 33.3/ 38.5
0.7 4.8 27.8 33.4
7.8/10.4 21.7/ 25.0
18.6/24.8 51.6/ 59.7
24.0/32.0 66.6/ 77.0
31.8/42.4 88.3/102.0
13.9 16.7
27.8 33.4
33.0 39.7
41.7 50.2
7.8/10.4 21.7/ 25.0
18.6/24.8 51.6/ 59.7
24.0/32.0 66.6/ 77.0
31.8/42.4 88.3/102.0
13.9 16.7
27.8 33.4
33.0 39.7
41.7 50.2
7.8/10.4 21.7/ 25.0
24.0/32.0 66.6/ 77.0
31.8/42.4 88.3/102.0
37.6/50.0 104.4/120.3
16.5 19.8
33.0 39.7
41,7 50.2
50.0 60.1
POWER SUPPLY
MCA
43,0/ 43.0
70.1/ 74.3
84,6/ 91.1
107.5/117.6
126.3/139.3
153.4/170.5
21.4
42.3
46.1
63.1
71.0
84.1
46.1/ 46.1
73.2/ 77.3
87.7/ 94.2
110.6/120.7
129.3/142.3
156.5/173.6
24.5
45.3
49.2
66.2
74.1
87.2
61.6/ 61.6
88.8/ 92.9
103.3/109.8
144.9/157.9
172.0/189.1
192.1/181.9
30.9
55.6
72.6
80.5
93.6
91.0
MINIMUM UNIT
DISCONNECT
SIZEt
MOCP FLA LRA
45/ 45tt 46/ 46 247/247
80/ 80 71/ 75 269/272
90/100 84/ 90 280/285"**
110/125 105/115 298/307"**
150/150 122/134 313/324"**
175/175 147/163 335/349"**
25¢t 23 123
45ft 42 140
5Oft 46 143
70 61 157
80 68 163
90 80 174
50/ 50tt 49/ 49 281/281
80/ 80 74/ 78 303/306
90/100 87/ 93 314/319"**
125/125 108/118 332/341 ***
150/150 126/138 347/358"**
175/175 151/166 369/383"**
25it 26 145
5Oft 45 162
5Oft 49 165
70 64 179
80 72 185
90 84 196
70/ 70 65/ 65 341/341
90/1 O0 90/ 94 363/366"**
110/110 104/110 375/380"**
150/175 142/154 408/418***
175/200 167/183 430/443"**
200/200 185/204 446/462"**
35tt 33 172
60tf 55 191
80 71 205
90 78 211
100 90 222***
100 102 232***
50HJQ
UNIT
SIZE
O08
(7412Tons)
009
(8412Tons)
012
(10 Tons)
Table 30 -- Electrical Data -- High-Static Motor Units Without Electrical Convenience Outlet
NOMINAL VOLTAGE COMPRESSOR OFM IFM ELECTRIC HEAT*
VOLTAGE RANGE (each) (each)
(V-Ph-Hz)
208/230-3-60 187 254 12.4
460-3-60 414 508 6.4
208/230-3-60 187 254 13.9 105
460-3-60 414 508 7.9 55.0
208/230-3-60 187 254 19.3 123.0
460-3-60 414 508 10.0 62.0
Min Max RLA LRA FLA FLA kW** FLA
88.0 1.4 10.6 12.0/16.0 33.3/ 38.5
44.0 0.7 4.8 16.5 19.8
1.4 10.6 12.0/16.0 33.3/ 38.5
0.7 4.8 16.5 19.8
1.4 15.0 12.0/16.0 33.3/ 38.5
0,7 7,4 27.8 33.4
7.8/10.4 21.7/ 25.0
18.6/24.8 51.6/ 59,7
24.0/32.0 66.6/ 77.0
31.8/42.4 88.3/102.0
13.9 16.7
27.8 33.4
33.0 39.7
41.7 50.2
7.8/10.4 21.7/ 25.0
18.6/24.8 51.6/ 59,7
24.0/32.0 66.6/ 77.0
31.8/42.4 88.3/102.0
13.9 16.7
27.8 33.4
33.0 39.7
41.7 50.2
7.8/10.4 21.7/ 25.0
24.0/32.0 66.6/ 77.0
31,8/42.4 88.3/102.0
37.5/50.0 104.4/120.3
16.5 19.8
33,0 39.7
41.7 50.2
50,0 60,1
POWER SUPPLY
MCA
41 3/ 41.3
68.4/ 72.6
82.9/ 89.4
105.8/115.9
124.6/137.6
151.7/168.8
20.6
41.5
45.4
62,4
70.2
83.4
44.4/ 44.4
71.5/ 75.6
86.0/ 92.5
108.9/119,0
127.6/140.6
154.8/171.9
23.7
44.6
48.4
65.4
73.3
86.4
61.2/ 61.2
88.4/ 92.5
102.9/109.4
144.5/157.5
171.6/188.7
191.7/181.5
31.3
56.1
73.1
80.9
94.1
96.4
MOCP FLA LRA
45/ 45tt 44/ 44 267/267
70/ 80 69/ 73 288/292
90/ 90 82/ 88 300/305"**
110/125 103/113 318/336"**
125/150 121/132 333/344"**
175/175 145/169 355/369"**
251-1- 22 134
451-1- 41 150
501-1- 45 153
70 60 167
80 68 173
90 80 184
45/ 451-1- 47/ 47 301/301
80/ 80 72/ 76 322/326
90/100 85/ 91 334/339"**
110/125 106/116 352/360"**
150/150 124/136 367/378"**
175/175 149/164 38_403"**
251-1- 25 156
451-1- 44 172
501-1- 48 175
70 63 189
80 71 195
90 83 206
70/ 70 65/ 65 360/360
90/100 90/ 94 382/385"**
110/110 103/109 39_399"**
150/175 141/153 42_437"**
175_00 166/182 44_462"**
200_00 185_03 464/480"**
351-1- 33 181
601-1- 56 201
80 72 215
90 79 221
100 91 231"**
100 102 241"**
MINIMUM UNIT
DISCONNECT
SIZEt
Table 3D -- Electrical Data -- High-Static Motor Units With Electrical Convenience Outlet
50HJQ
UNIT
SIZE
O08
(7412Tons)
009
(8412Tons)
012
(10 Tons)
NOTE: See legend and notes on page 11.
NOMINAL VOLTAGE COMPRESSOR OFM IFM ELECTRIC HEAT*
VOLTAGE RANGE (each) (each)
(V-Ph-Hz)
208/230-3-60 187 254 12.4
460-3-60 414 508 6.4
208/230-3-60 187 254 13.9 105
460-3-60 414 508 7.9 55.0
208/230-3-60 187 254 19.3 123.0
460-3-60 414 508 10.0 62.0
Min Max RLA LRA FLA FLA kW** FLA
88.0 1.4 10.6 12.0/16.0 33.3/ 38.5
44.0 0.7 4.8 16.5 19.8
1.4 10.6 12.0/16.0 33.3/ 38.5
0.7 4.8 16.5 19.8
1.4 15.0 12.0/16.0 33.3/ 38.5
0.7 7.4 27.8 33.4
7.8/10.4 21.7/ 25.0
18.6/24.8 51.6/ 59.7
24.0/32.0 66.6/ 77.0
31.8/42.4 88.3/102.0
13.9 16.7
27.8 33.4
33.0 39.7
41.7 50.2
7.8/10.4 21.7/ 25.0
18.6/24.8 51.6/ 59.7
24.0/32.0 66.6/ 77.0
31.8/42.4 88.3/102.0
13.9 16.7
27.8 33.4
33.0 39.7
41.7 50.2
7.8/10.4 21.7/ 25.0
24.0/32.0 66.6/ 77.0
31,8/42.4 88.3/102.0
37.5/50.0 104.4/120.3
16.5 19.8
33.0 39.7
41.7 50.2
50.0 60.1
POWER SUPPLY
MCA
461/ 46.1
73.2/ 77.4
87,7/ 94.2
110.6/120.7
129.4/142.4
156.5/173.6
22.8
43.7
47.5
64.5
72.4
85.5
49.2/ 49.2
76.3/ 80.4
90.8/ 97.3
113.7/123.8
132.4/145.4
159.6/176.7
25.9
46.7
50.6
67.6
75.5
88.6
66.0/ 66.0
93.2/ 97.3
107.7/114.2
149.3/162.3
176.4/193.5
196.5/186.3
33.5
58.2
75.2
83.1
96.2
93.6
MINIMUM UNIT
DISCONNECT
SEE1-
MOCP FLA LRA
50/ 501-1- 49/ 49 271/271
80/ 80 74/ 78 293/296
90/100 88/ 94 305/310"**
125/125 109/118 323/331"**
150/150 126/138 338/348"**
175/175 159/167 360/373"**
251-1- 24 136
451-1- 44 152
501-1- 47 155
70 63 169
80 70 175
90 82 186"**
50/ 501-1- 53/ 53 305/305
80/ 90 78/ 81 327/330
100/100 91/ 97 339_44"**
125/125 112/121 357_65"**
150/150 129/141 372_82"**
175_00 154/170 394/407"**
301-1- 27 158
501-1- 47 174
601-1- 50 177
70 66 191
80 73 197
90 85 208***
70/ 70 70/ 70 365/365
100/100 95/ 99 387_90"**
110/125 109/115 398/403"**
150/175 147/159 431/442"**
200_00 172/188 453/467"**
200_00 190_09 469/485"**
351-1- 36 183
601-1- 58 203
80 74 217
90 81 223***
100 93 234***
100 105 243***
]0
LEGEND AND NOTES FOR TABLES 3A-3D
LEGEND
FLA -- Full Load Amps
HACR -- Heating, Air Conditioning
IFM -- Indoor-Fan Motor
LRA -- Locked Rotor Amps
MCA -- Minimum Circuit Amps
MOCP -- Maximum Overcurrent
NEC -- National Electrical Code
OFM -- Outdoor-Fan Motor
RLA -- Rated LoadAmps
*Heaters are field installed only.
1-Minimum unit disconnect size is used to determine minimum dis-
connect per NEC.
**Heater capacity (kW) is based on heater voltage of 208 v, 240 v,
480 v. If power distribution voltage to unit varies from rated heater
voltage, heater kW will vary accordingly.
1-1-Fuseor HACR circuit breaker.
***Factory-installed disconnect is not available for these units when
electric heat package is installed.
NOTES:
1. In compliance with NEC requirements for multimotor and com-
2. Unbalanced 3-Phase Supply Voltage
and Refrigeration
Protection
bination load and equipment (refer to NEC Articles 430 and
440), the overcurrent protective device for the unit shall be fuse
or HACR breaker.
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percent of voltage imbalance.
% Voltage Imbalance
= 100 x max voltage deviation from average voltage
average voltage
Example: Supply voltage is 460-3-60.
A B C
Determine maximum deviation from average voltage:
(AB) 457 - 452 = 5 v
(BC) 464 - 457 = 7 v
(AC) 457 - 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance:
% Voltage Imbalance = 100 x --
This amount of phase imbalance is satisfactory as it is below
the maximum allowable 2%.
than 2%, contact your local electric utility company immediately.
I IMPORTANT: If the supply voltage phase imbalance is more I
3. Non-fused disconnect switch cannot be used when rooftop unit
electrical ratings exceed 80 amps.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage = 3
1371
3
= 457
7
457
= 1.53%
I
]!
HELD CONTROL WIRING -- Install a Carrier-approved
accessory thennostat assembly according to the installation
instructions included with the accessory. Locate file thermostat
assembly on a solid wall in the conditioned space to sense
average temperature in accor&mce with thermostat installa-
tion instructions.
NOTE: If using a Carrier electronic thermostat, set the thenno-
star configuration for "non-heat pump operation." This family
of products does not require an O temfinal to energize the
reversing valve.
Route the thermostat cable or equivalent single leads of col-
ored wire from the subbase termimds to the low-voltage con-
nections on the unit (shown in Fig. 8A and 8B) as described in
Steps 1 fllrough 4 below.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gage) insukited wire (35 C minimum). For 51 to 75 1l, use
no. 16 AWG insukited wire (35 C minimum). For over 75 fi, use
no. 14 AWG insukited wire (35 C minimum). All wire larger
than no. 18 AWG cannot be directly connected to the thermostat
and will require ajunction box and splice at the thermostat.
1. If the unit is mounted on the roof curb and an accessory
thin-the-curb service plate connection is used, route the
wire through connection plate.
2. Pass control wires through the hole provided on the unit
(see connection D in the Connection Sizes table in
Fig. 6).
3. Feed wire through the raceway built into the comer post to
the 24-v bmrier located on the left side of the control box.
See Fig. 9. The raceway provides the UL lequiled clear-
ance between the high-voltage and low-voltage wiring.
m
COOL STAGE 1 Y1/W2 - - - i
FAN G -
HEAT STAGE 1 W/W1- - _ I _
COOL STAGE 2 Y/Y2- - - F -
HEAT STAGE 2 O/W2 - _ i _ -I-
24 VAC HOT R-
24 VAC COM C-
N/A
OUTDOOR AIR $1
SENSOR $2
- R
I
- G
I
I
Y1
- Y2
W1
, W2
- C
IPD/X
WIRE
CONNECTIONS
-TO
LOW-VOLTAGE
SECTION
4. Connect the thermostat wires to the screw terminals of
the low-voltage connector (see Fig. 8A and 8B).
NOTE: If the unit is mounted on a roof curb and the electrical
power will be run up "thru-the-bottom," use accessory kit
CRBTMPWR002A00. This kit, av_dlable from your local dis-
tributor, ensures a reliable watertight connection. Refer to the
accessory installation instructions for information on power
wiring. Refer to Fig. 6 for drilling holes in the basepan.
DEFROST BOARD -- The defrost board timer cycle is fac-
tory set to 30 minutes. To chtmge the cycle time, remove the
wire from the defrost board connected to the 30 minute quick-
connect. See Fig. 10. Connect the wire to the 50 or 90 minute
quick-connects on the defrost board, depending on the desired
defmst time.
HEAT ANTICIPATOR SETTINGS -- For units with electric
heat, set heat anticipator settings as shown in Table 4.
CONNECTION
BOARD
DISCONNECT
SWITCH
(OPTIONAL)
COMPRESSOR
NO. 1
NO. 2
RACEWAY
OPTIONAL
CONVENIENCE'
OUTLET
HOLEIN
END
i
Fig. 9 -- Field Control Wiring Raceway
THERMOSTAT DIPSWITCH SETTINGS LEGEND
O_F [] [] [] [] FieldWiring
A B C D
NOTE: Underlined letter indicates active thermostat output when
configuredfor A/C operation.
Fig. 8A- Low-Voltage Connections With or
Without Economizer or Two-Position Damper
CONTROL THERMOSTAT CONTROL
CONNECTION CONNECTION
BOARD BOARD
/_R_R )_ 24 vAC _ll _ (FLIP
{[::_[) RMTOOC 7ii (,[?_'5 ,/[_J[>
CMPSAFE7 i" <_
< Y27 ESD I 1 <[_i) <_!)
(Wl)_ SFS _ 1
NOT USED ;
=,
1 1
c
(g2_x <x)
Fig. 8B -- Low Voltage Connections
(Units with PremierLink Controls)
TM
12
OF2_ _OF1
P1
QUICK CONNECTS
FOR DEFROST TIMER
oI]
30 50 90
Fig. 10 -- Defrost Board
I]
[1I-1
UNIT
50HJQ
*kW is based on 240 v.
Heater
kW*
10.4, 16.0
32.0, 24.8
42.4, 50.0
Table 4 -- Heat Anticipator Settings
208/230
Configuration
2-Stage
1-Stage Stage 1 Stage 2
0.3 NA NA
0.6 0.3 0.3
0.9 0.6 0.3
UNIT VOLTAGE
Heater
kW
13.9, 16.5
27.8, 33.0
41.7, 50.0
1-Stage
0.3
0.6
46O
Configuration
2-Stage
Stage 1 Stage 2
NA NA
0.3 0.3
Step 6 -- Adjust Factory-Installed Options
DISCONNECT SWITCH -- The optional disconnect switch
is non-fused. The switch can be locked in place for safety
purposes.
CONVENIENCE OUTLET -- An optiomd convenience out-
let provides power for rooftop use. For maintenance personnel
safety, the convenience outlet power is off when the unit dis-
connect is off. Adjacent unit outlets may be used for service
tools. An optional "Hot Outlet" is available from file factory as
a speci_d order item.
NOVAR CONTROLS -- Option_d Novar controls (ETM 3051 )
ale available for leplacement or new construction jobs.
MANUAL OUTDOOR-AIR DAMPER -- The outdoor-air
hood and screen me attached to the basepan at the bottom of
the unit (for shipping).
Assemblys.:
1. Determine the amount of ventilation required for the
building. Record the amount for use in Step 8.
2. Remove the filter access panel by raising the panel and
swinging the panel bottom outward. The panel is now
disengaged from the track and can be removed. No tools
are requiled to remove the filter access panel. Remove the
outdoor-air opening panel. Save the panels and screws.
See Fig. 11.
3. Separate file hood and screen from the basepan by remov-
ing file screws and brackets securing them. Save all
screws and discmd the brackets.
4. Replace the outdoor air opening panel.
5. Place the hood on the front of the outdoor air opening
panel. See Fig. 12 for hood details. Secure the top of the
hood with the 6 screws removed in Step 3. See Fig. 13.
6. Remove and save the 8 screws (4 on each side) from the
sides of the manual outdoor-air &tmpel:
7. Align the screw holes on the hood with the screw holes
on the side of manual outdoor-air dampel: See Fig. 12 and
13. Secure the hood with 8 screws fiom Step 6.
8. Adjust the minimum position setting of the &tmper blade
by adjusting the manual outdoor-air adjustment screws on
file front of the &tmper blade. See Fig. 11. Slide the blade
vertically until it is in file appropriate position determined
by Fig. 14. Tighten the screws.
9. Remove and save the screws currently on the sides of
hood. Insert the screen. Secure the screen to the hood
using the screws. See Fig. 13.
10. Replace the filter access panel. Ensure that the filter ac-
cess panel slides along the tracks and is securely engaged.
ADJUSTMENT
SCREWS
DAMPER
BLADE
Fig. 11 -- Damper Panel with Manual
Outdoor-Air Damper Installed
13
HOOD TOP SCREWS
(HIDDEN) _.,
SCREWS
(SCREEN HOLDERS)
HOOD SIDES AND TOP-
ASSEMBLED
HOOD
SIDE
Fig. 12 -- Outdoor-Air Hood Details
SCREW
HOLES
(TOP)
HOOD
HOOD
SCREEN
LOCATION
(SCREEN
NOT
SHOWN)
Fig. 13- Optional Manual Outdoor-Air
Damper with Hood Attached
1.0
0.8 / /
LU
rr
0,6
60
PREMIERLINK TM CONTROL -- The PmmierLink control-
let is compatible with Career Comfort Network® (CCN)
devices. This control is designed to allow users the access and
ability to change factory-defined settings, thus expanding the
function of file standiu'd unit control board. Career's diagnostic
standard tier display tools such as Navigator TM or Scrolling
Marquee can be used with the PremierLink controller.
The PremielLink controller (see Fig. 15A and 15B) requires
the use of a Carrier electronic thermostat or a CCN connection
for time broadcast to initiate its intermfl fimeclock. This is
necessary for broadcast of time of &ty functions (occupied/
unoccupied). No sensors me supplied with the field-mounted
PremierLink control. The factory-installed PremierLink con-
trol includes only the supply-air sensor (SAT) and the outdoor
air temperature sensor (OAT) as standard. An indoor air quality
(CO2) sensor can be added as an option. Refer to Table 5 for
sensor usage. Refer to Fig. 16 for PmmierLink controller wir-
ing. The PremierLink control may be mounted in file control
panel or an area below the control panel.
NOTE: PmmierLink controller versions 1.3 and later am
shipped in Sensor mode. If used with a thermostat, the
PmmierLink controller must be configured to Themlostat
mode.
Install the Supply Air Temperature Sensor (SAT) -- When
the unit is supplied with a factory-mounted PremierLink con-
trol, the supply-air temperature (SAT) sensor (33ZCSENSAT)
is factory-supplied and wired. The wiring is routed from file
PmmierLink control over the control box, through a grommet,
into the fan section, down _flong the back side of the fan, and
along the fan deck over to the supply-air opening.
The SAT probe is wire-tied to the supply-air opening (on the
horizontal opening end) in its shipping position. Remove the
sensor for installation. Re-position the sensor in file flange of
the supply-air opening or in file supply air duct (as lequimd by
loc_fl codes). Drill or punch a 1/2-in. hole in the flange or duct.
Use two field-supplied, self-drilling screws to secure the sensor
probe in a horizontal orientation.
NOTE: The sensor must be mounted in the dischmge airstmam
downstream of file cooling coil and any heating devices. Be
sum the probe tip does not come in contact wifll any of the unit
or heat surfaces.
Outdoor Air Temperature Sensor (OAT) -- When the unit is
supplied with a factory-mounted PremierLink control, the
outdoor-_dr temperature sensor (OAT) is factory-supplied and
wimdi
Install the Indoor Air Quality (CO_ Sensor -- Mount the
optional indoor air quality (Ci2)2) sensor according to manufac-
turer specifications.
A separate field-supplied transformer must be used to pow-
er the CO2 sensor:
Wile the CO2 sensor to the COM and IAQI terminals of J5
on the PremierLink controllec Refer to the PremierLink Instal-
lation, Start-up, and Configuration Instructions for detailed
wiring and configuration information.
# 0.4 /
0 2 4 8 10 12
OUTDOOR AIRFLOW (cfm x 100)
Fig. 14 -- Outdoor Air Damper Position Setting
14
HVAC SENSOR INPUTS
SPACE TEMP
SET POINT
SUPPLY AIR TEMP
OUTDOOR TEMP -_.
INDOOR AIR QUALITY
OUTDOOR AIR QUALITY
DUAL MODE SENSOR/STAT
0 0 €
am" _f_
................ _ .- J
_ _ _ut N_ber 33C_pP_=_K
.-_c_]_ PremzerLznk .....
COMP SAFETY (Y1) J
FIRE SHUTDOWN (Y2) Z
SUPPLY FAN STATUS (Wl)
NOT USED (W2) J
ENTHALPY STATUS (ENTH) Z
PREMIERLINK
CONTROL
tb-_- i I-_ @H, _r:-ar-_ _ _ _ " "
, 7°1.o lqo_,.'_°,,= ..I ,.-.._ I I _
--' "C'ITTIT I'
.......................... J _ P_ N _ *.-_ _N Y_ _ _ _ O_ _ED
/ t / t "4 "-4 \
CCN/LEN
PORT
Fig. 15A -- PremierLink TM Controller
NAVIGATOR 4-20MA INDOOR COMPR HEAT EXHAUST
PORT ECONOMIZER FAN MOTOR 1 & 2 LOW/HIGH RVSVALVE
OUTPUTS
HINGED
DOOR
PANEL
Fig. 15B -- PremierLink Controller (Installed)
15
Table 5- PremierLink TM Sensor Usage
APPLICATION TEMPERATURE SENSOR TEMPERATURE SENSOR ENTHALPY SENSOR ENTHALPY SENSOR
Dry Bulb
Temperature with
PremierLink* Included --
(PremierLink HH79NZ017
requires 4-20 mA
Actuator)
Differential Dry Bulb
Temperature with Required --
PremierLink* Included -- 33ZCT55SPT -- --
(PremierLink HH79NZ017
requires 4-20 mA or Equivalent
Actuator)
Single Enthalpy with
PremierLink*
(PremierLink Included -- _ Required -- _
requires 4-20 mA
Actuator)
Differential Enthalpy
with PremierLink*
(PremierLink Included -- _ Required -- Required --
requires 4-20 mA
Actuator)
*PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT and
Outdoor Air Temperature sensor HH79NZ017 -- included with factory-installed PremierLink control
field-supplied and field-installed with field-installed PremierLink control.
NOTES:
1. CO2 Sensors (Optional):
33ZCSENCO2 -- Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.
33ZCASPCO2 -- Aspirator box used for duct-mounted CO2 room sensor.
33ZCT55CO2 -- Space temperature and CO2 room sensor with override.
33ZCT56CO2 -- Space temperature and CO2 room sensor with override and set point.
2. All units include the following Standard Sensors:
Outdoor-Air Sensor -- 50HJ540569 -- Opens at 67 F, closes at 52 F, not adjustable.
Mixed-Air Sensor -- HH97AZ001 -- (PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT
and Outdoor Air Temperature Sensor HH79NZ017)
Compressor Lockout Sensor -- 50HJ540570 -- Opens at 35 F, closes at 50 R
OUTDOOR AIR RETURN AIR OUTDOOR AIR RETURN AIR
Not Used HH57AC077
Not Used HH57AC077 HH57AC078
............. BLK
iiiii-°L°
PNK
YEL
RED
BLU
YEL
WHT
HK50AA039]
VIO
6
10
2 ¸
3 ¸
EconomiSer2
4 - 20mA
i VlO
Power Exhaust'Energy Recycle r
SpaceTemp/ Set i
PointAd}ustment
]ndoofAk
Oua]_y Sensor
Outdoor Air
Quality Sensor
6_
i_ ii1
8 (_ ............. ORN
YEL
BLU
PNK I
RED
7 <I_
8r]rh
COMMS -- Communications
OAT
PWR
RTU
SAT
TB
WNT
k_U]
BLK
LEGEND
-- Outdoor Air Temperature Sensor
-- Power
-- Rooftop Unit
-- Supply Air Temperature Sensor
-- Terminal Block
PremierLink
J9 J7 J8
O-20 mA PPIMP Relays
TB- 1
_ED
t SII_ R
2 /ll _Y1
i
3 _/I _Y2
5 SIIhW2
6 /I]\GG
\J[/
<JJ
\JL/
\ HJ
RE_ '
ORN '" _ i
ORN ' '
PNK ,,
Wm
7 S j--, C
8_X
<IL;
RTU Terminal
Board
RED
Fig. 16 -- Typical PremierLink Controls Wiring
16