Carrier 50HJ004, 50HE003-006 User Manual

Page 1
50HJ004---007 50HE003---006 Single ---Package Rooftop Electric Cooling Units w it h Optional Electric Heat
Installation Instructions
TABLE OF CONTENTS
Page
INSTALLATION 1..................................
Step 1--Provide Unit Support 2......................
ROOF CURB 2................................
SLAB MOUNT 2..............................
ALTERNATE UNIT SUPPORT 2.................
Step 2--Field Fabricate Ductwork 2...................
Step 3--Install External Trap for Condensate Drain 2.......
Step 4--Rig and Place Unit 4.........................
POSITIONING 4..............................
Step 5 — Make Electrical Connections 8................
FIELD POWER SUPPLY 8......................
FIELD CONTROL WIRING 8....................
HEAT ANTICIPATOR SETTINGS 8...............
Step 6 — Adjust Factory-Installed Options 29...........
COBRAENERGY RECOVERY UNITS 29.......
HUMIDI-MIZERADAPTIVE
DEHUMIDIFICATION SYSTEM 29..............
DISCONNECT SWITCH 29.....................
MANUAL OUTDOOR-AIR DAMPER 29..........
CONVENIENCE OUTLET 29...................
NOVAR CONTROLS 29........................
PREMIERLINKCONTROL 31.................
OPTIONAL ECONOMI$ER IV AND
ECONOMI$ER2 34............................
ECONOMI$ER IV STANDARD SENSORS 35......
ECONOMI$ER IV CONTROL MODES 36.........
Step 7 — Adjust Evaporator-Fan Speed 41..............
PRE--START--UP 58..................................
START--UP 58.......................................
SERVICE 62........................................
TROUBLESHOOTING 67.............................
START--UP CHECKLIST 72...........................

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
Recognize safety information. This is the safety--alert symbol
. When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which ma y result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability,or operation.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on unit, turn off main power switch to unit and install lockout tag. Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate.
WARNING

INSTALLATION

Unit is shipped in the vertical discharge configuration. To convert to horizontal discharge application, remove duct opening covers. Using the same screws, install covers on duct openings in basepan of unit with insulation-side down. Seals around openings must be tight. (See Fig. 1.)
1
Page 2
Step 1 Provide Unit Support
Curb
Roof
Assemble and install accessory roof curb in accordance with instructions shipped with curb. (See Fig. 2.) Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb, not to the unit. If electric control power or gas service is to be routed through the basepan, attach the accessory thru-the-bottom service connections to the basepan in accordance with the accessory installation instructions. Connections must be installed before unit is set on roof curb.
50HE,HJ
Fig. 1 --- Horizontal Conversion Panels
IMPORTANT: The gasketing of the unit to the roof curb is critical
for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 2. Improperly applied gasket can resul t in air leaks and poor unit performance.
Curb should be level. Unit leveling tolerances are shown in Fig.
3. This is necessary for unit drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
Slab Mount (Horizontal Units Only)
Provide a level concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of condenser-coil air inlet to prevent grass and foliage from obstructing airflow.
C06108
NOTE: Horizontal units may be installed on a roof curb if required.
Alternate Unit
Support
When the curb or adapter cannot be used, support unit with sleeper rails using unit curb or adapter support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
Step 2 Field Fabricate Ductwork
Secure all ducts to roof curb and building structure on vertical discharge units. Do not connect ductwork to unit. For horizontal applications, field-supplied isolation flanges should be attached to horizontal discharge openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork. Cabinet return-air static pressure (a negative condition) shall not exceed
0.35 in. wg with economizer or 0.45 in. wg without economizer.
Step 3 —Install External Trap for Condensate Drain
Condensate drain connections are located on the bottom and side of the unit. Unit discharge connections do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications.
When using the standard side drain connection, ensure the plug (Red) in the alternate bottom connection is tight before installing the unit.
To use the bottom drain connection for a roof curb installation, relocate the factory-installed plug (Red) from the bottom connection to the side connection. The center drain plug looks like a star connection, however it can be removed with a
1
/2-in. socket drive extension. (See Fig. 4.) The piping for the condensate drain and external trap can be completed after the unit is in place.
All units must have an external trap for condensate drainage. Install a trap 4-in. deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection (
3
/4in.). (See Fig. 5.)
2
Page 3
1-4 [406]
DALT
DRAIN
HOLE
13/4
[44.5]
GAS POWER CONTROL
3
/4
[19] NPT
1
/2
[12.7] NPT
3
/4
[19] NPT
CONNECTOR
PKG. ACCY.
CRBTMPWR001A01 CRBTMPWR002A01 1
CRBTMPWR003A01
BC
11
/16
1-9
[551]
CRBTMPWR004A01
3
/4 [19] NPT
1
/4 [31.7]
3
/4 [19] NPT
1
/4 [31.7]
1
1
/2
[12.7]
ACCESSORY
POWER
1
/2
[12.7]
ROOF CURB
ACCESSORY
CRRFCURB001A01
CRRFCURB002A01
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance: 4 ft on each side.
1-2 [356]
2-0 [610]
A
UNIT SIZE
50HJ004-007 50HE003-006
7. Direction of airflow.
8. Connector packages CRBTMPWR001A01 and 002A01 are for thru-the-curb type gas. Packages CRBTMPWR003A01 and 004A01 are for thru-the-bottom type gas conne ctions.
50HE,HJ
Fig. 2 --- Roof Curb Details
3
C06155
Page 4
Step 4 Rig and Place Unit
Inspect unit for transportation damage, and file any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit, and rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1, 2 and Fig. 6 for additional information. Operating weight is shown in Table 1, 2 and Fig. 6.
Lifting holes are provided in base rails as shown in Fig. 7. Refer to rigging instructions on unit.
!
PERSONAL INJURY AND PROPERTY DAMAGE HAZARD
WARNING
Failure to follow this warning could result in personal injury, death and property damage.
All panels must be in place when rigging and lifting.
50HE,HJ
Positioning
Maintain clearance around and above unit to provide minimum distance from combustible materials, proper airflow, and service access. (See Fig. 7, 8 and 9.)
Position unit on roof curb so that the following clearances are maintained:
1
/4in. clearance between the roof curb and the base rail inside the front and rear, 0.0 in. clearance between the roof curb and the base rail inside on the duct end of the unit. This will result in the distance between the roof curb and the base rail inside on the condenser end of the unit being approximately equal to Fig. 2, section C-C.
Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contaminated air.
CONDENSATE PAN (SIDE VIEW)
HORIZONTAL DRAIN OUTLET
NOTE: Drain plug is shown in factory-installed position.
DRAIN PLUG
C06003
Fig. 4 --- Condensate Drain Connection
NOTE: Trap should be deep enough to offset maximum unit static difference. A 4-in. trap is recommended.
C06004
Fig. 5 --- Condensate Drain Piping Details
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B B-C A-C
0.5 1.0 1.0
Fig. 3 --- Unit Leveling Tolerances
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
After unit is in position, remove polyethylene shipping wrapper and top crating.
C06110
4
Page 5
NOTES:
1. Place unit on curb as close as possible to the duct end.
2. Dimension in ( ) is in millimeters.
3. Hook rigging shackles through holes in base rail as shown in detail "A." Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.
4. Weights include base unit without economizer. See Table 1 for unit operating weights with accessory economizer.
5. Weights include base unit without the Humidi-MiZer
Humidi-MiZer system.
TM
adaptive dehumidification system. See Table 1 for unit operating weights with the
C06111
Fig. 6 --- Rigging Details
50HE,HJ
UNIT
50HE
003 435 197 73.69 1872 35.50 902 33.31 847 004 445 202 73.69 1872 35.50 902 33.31 847 005 465 211 73.69 1872 35.50 902 33.31 847 006 520 236 73.69 1872 35.50 902 33.31 847
UNIT
50HJ
004 530 240 73.69 1872 35.50 902 33.31 847 005 540 245 73.69 1872 35.50 902 33.31 847 006 560 254 73.69 1872 35.50 902 33.31 847 007 635 288 73.69 1872 35.50 902 33.31 847
OPERATING
WEIGHT
lb kg in. mm in. mm in. mm
OPERATING
WEIGHT
lb kg in. mm in. mm in. mm
“A” “B” “C”
“A” “B” “C”
DIMENSIONS
DIMENSIONS
!
PERSONAL INJURY AND PROPERTY DAMAGE HAZARD
WARNING
Failure to follow this warning could result in personal injury, death and property damage.
All panels must be in place when rigging and lifting.
Fig. 7 --- Roof Curb Alignment
C06208
5
Page 6
C06156
50HE,HJ
Fig. 8 --- 50HJ004--007 Base Unit Dimensions
6
Page 7
C06157
50HE,HJ
Fig. 9 --- 50HE003--006 Base Unit Dimensions
7
Page 8
Step 5 Make Electrical Connections
!
WARNING
ELECTRICAL SHOCK HAZARD
Failur e to follow this warning could res ul t in personal injury or death,
Unit cabi net must have an uninterrupted, unbroke n electrical ground to minimize the possibility of personal injury if an electr i cal fault should occur. This ground may consist of el ectri cal wire connected to unit ground lug in control compa rtment, or conduit approved for electr i cal ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA (National Fire Protection Association), latest edition, and local electrical codes. Do
not use gas piping as an ele ctrical ground.
Field Power Supply
All units except 208/230-v units are factory wired for the voltage
50HE,HJ
shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by disconnecting the black wire from the 230-v 1/4--in. terminal on the transformer and connecting it to the 200-v 1/4--in. terminal from the transformer.
Refer to unit label diagram for additional information. Pigtails are provided for field service. Use factory-supplied splices or UL (Underwriters’ Laboratories) approved copper connector.
When installing units, provide a disconnect per NEC. All field wiring must comply with NEC and local
requirements. Install field wiring as follows:
1. Install conduit through side panel openings. For units without electric heat, install conduit between disconnect and control box.
2. Install power lines to terminal connections as shown in Fig. 12.
3. For units with electric heat, refer to Accessory Electric Heat Installation Instructions.
During operation, voltage to compressor terminals must bewithin range indicated on unit nameplate (also see Table 3 and 4). On 3--phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in Table 3 and 4, Note 2, to determine the percentage of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation invalidates any applicable Carrier warranty.
NOTE: If accessory thru-the-bottom connections and roof curb are used, refer to the Thru-the-Bottom Accessory Installation Instructions for information on wiring the unit.
Field Control W
iring
Install a Carrier-approved accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature in accordance with thermostat installation instructions.
Route thermostat cable or equivalent single leads of colored wire from subbase terminals through connector on unit to low-voltage connections (shown in Fig. 10 and 11).
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gauge) insulated wire (35_Cminimum).For50to75ft,use no. 16 AWG insulated wire (35_C minimum). For over 75 ft, use no. 14 AWG insulated wire (35_C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.
1. Connect thermostat wires to screw terminals of lowvoltage terminal board.
2. Pass the control wires through the hole provided in the control box.
3. Some models may be equipped with a raceway built into the corner post on the left side of control box (See Fig.
13.) This raceway provides the required clearance between high--voltage and low voltage wiring. For models without a raceway, ensure to provide the NEC required clearance between high--voltage and low--voltage wiring.
Heat Anticipator
Settings
Set heat anticipator settings at 0.8 amp for first stage and 0.3 for second stage heating.
W1
W2
IPD/X
R
G
Y1
Y2
C
WIRE CONNECTIONS TO LOW-VOLTAGE SECTION
C06008
COOL STAGE 1
FAN
HEAT STAGE 1
COOL STAGE 2
HEAT STAGE 2
24 VAC HOT
24 VAC COM
N/A
OUTDOOR AIR
SENSOR
THERMOSTATDIPSWITCH SETTINGS
ON OFF
A
LEGEND
NOTE: Under lined letter indicates active thermostat output when configured for A/C operation.
B
C
Field Wiring
Y1/W2
G
W/W1
Y/Y2
O/W2
R
C
S1
S2
D
Fig. 10 --- Low--Voltage connections With or
Without Economizer or Two--Position Damper
CONTROL
CONNECTION
BOARD
24 VAC
R
RMTOCC
G
CMPSAFE
Y2
FSD
W1
SFS
NOT USED
C
C
X
X
THERMOSTAT CONTROL
CONNECTION
BOARD
R
Y1
Y2
W1
W2
G
C
R
Y1
Y2
W1
W2
G
C
X
C06009
Fig. 11 --- Low--Voltage Connections
(Units with PremierLinkt Controls)
8
Page 9
Table 1—Physical Data 50HJ
BASE UNIT 50HJ 004 005 006 007
NOMINAL CAPACITY OPERATING WEIGHT (lb)
Unit Humidi-MiZerAdaptive Dehumidification System EconoMi$er IV Roof Cur b
COMPRESSOR
Quantity Oil (oz)
REFRIGERANT TYPE
Expansion Device Operating Charge (lb-oz)
Standard Unit Unit With Humidi-Mizer Adaptive Dehu midification System
CONDENSER FAN
Quantity...Diameter (in.) Nominal C f m Motor Hp...Rpm Watts Input (Total)
CONDENSER COIL
Rows...Fins/in. Tot a l Face Area (s q ft )
EVAPORATOR COIL
Standard Unit
Rows...Fins/in. Tot a l Face Area (s q ft )
Unit with Humidi-Mizer Adaptive Dehu midification System
Rows...Fins/in. Tot a l Face Area (s q ft )
EVAPORATOR FAN
Quantity...Size (in.) Nominal C f m Maximum Continuous Bhp Std
Hi-Static
Motor Frame Size Std
Hi-Static
Fan Rpm Range Std
Hi-Static
Motor Bearing Type Maximum Fan Rpm Motor Pulley Pitch Diameter A/B (in.)
Hi-Static
Nominal Motor Shaft Diameter (in.) Std
Hi-Static
Fan Pulley Pitch D iameter (in.) Std
Hi-Static
Belt — Type...Length (in.) Std
Hi-Static
Pulley Center Line Distance (in.) Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full
Turns from Closed Position
Hi-Static
Hi-Static
Factory Setting — Full Turns Open Std
Hi-Static
Factory Speed Setting (rpm) Std
Hi-Static
Fan Shaft Diameter at Pulley (in.)
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief Cutout Reset (Auto.)
LOSS -OF-CHARG E/LOW-PRESSURE
SWITCH (Liquid LIne) (psig) Cutout Reset (Auto.)
FREEZE PROTECTION THERMOSTAT
Opens (F)
Closes (F) OUTDOOR-AIR INLET SCREENS RETURN-AIR FILTERS
Quantity...Size (in.)
Std
Std
Std
3 4 5 6
435 445 465 540
15 23 25 29 50 50 50 50
115 115 115 115
Scroll
1 1 1 1
42 53 50 60
R-22
AcutrolMetering Device
5-8 10-2 10-0 12- 8
12-5 18-8 20-5 23-14
Propeller
1...22 1...22 1...22 1...22 3500 3500 4100 4100
1
/8...825
1
/8...825
1
/4...1100
1
/4...1100
180 180 320 320
Enhanced Copper Tubes, Aluminum Lanced Fins
1...17 2...17 2...17 2...17
14.6 16.5 16.5 21.3 Enhanced Copper Tubes, Aluminum Double-Wavy Fins
2...15 2...15 4...15 4...15
5.5 5.5 5.5 7.3
1...17 2...17 2...17 2...17
3.9 3.9 3.9 5.2 Centrifugal Type, Belt Drive
1...10 x 10 1...10 x 10 1...10 x 10 1...10 x 10 1200 1600 2000 2400
1.20
2.40 48 56
680-1044
1075-1455
1.20 1.30/2.40* 2.40
2.40 2.90 2.90 48 56 56 56 56 56
770-1185 1035-1460/1035 ---1460* 1120-1585
1075-1455 1300-1685 1300-1685
Ball Ball Ball Ball
2100 2100 2100 2100
1.9/2.9
2.8/3.8
1/
2
5
/
8
4.5
4.5
1...A...36
1...A...39
1.9/2.9 2.4/3.4 2.4/3.4
2.8/3.8 3.4/4.4 3.4/3.4
1
/
2
5
/
8
4.0 4.0 3.7
5
/
8
7/
8
5 7
4.5 4.5 4.5
1...A...36 1....4...40 1...A...38
1...A...39 1...A...40 1...A...40
10.0-12.4 10.0-12.4 14.7-15.5 14.7-15.5 65 65
5 6 3
1
3
826
1233
5
/
/
2
8
70 75 95 65 60 60
5 6 5 6 5 5 3 3 3
31/
2
936 1248 1304
1233 1396 1396
5
/
8
31/
2
5
/
8
31/
5
450 50
428 320
7 3
22  5
30 45
Cleanable. Screen quantity and size varies with option selected.
Throwaway
2...16 x 25 x 2
2...16 x 16 x 2
50HE,HJ
/
8
/
8
2
/
8
LEGEND
Bhp — Brake Horsepower
*Single phase/three phase.
9
Page 10
Table 2—Physical Data 50HE
BASE UNIT 50HE 003 004 005 006
NOMINAL CAPACITY OPERATING WEIGHT (lb)
Unit Humidi-MiZerAdaptive Dehumidification System EconoMi$er IV Roof Cur b
COMPRESSOR
Quantity Oil (oz)
REFRIGERANT TYPE
Expansion Device Operating Charge (lb-oz)
Standard Unit Unit With Humidi-Mizer Adaptive Dehu midification System
CONDENSER FAN
Quantity...Diameter (in.) Nominal C f m Motor Hp...Rpm Watts Input (Total)
CONDENSER COIL
Rows...Fins/in. Tot a l Face Area (s q ft )
50HE,HJ
EVAPORATOR COIL
Standard Unit
Rows...Fins/in. Tot a l Face Area (s q ft )
Unit with Humidi-Mizer Adaptive Dehu midification System
Rows...Fins/in. Tot a l Face Area (s q ft )
EVAPORATOR FAN
Quantity...Size (in.) Nominal C f m Maximum Continuous Bhp Std
Motor Frame Size Std
Motor Rpm Fan Rpm Range Std
Motor Bearing Type Maximum Fan Rpm Motor Pulley Pitch Diameter A/B (in.)
Nominal Motor Shaft Diameter (in.) Std
Fan Pulley Pitch D iameter (in.) Std
Belt — Type...Length (in.) Std
Pulley Center Line Distance (in.) Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full
Turns from Closed Position
Factory Setting — Full Turns Open Std
Factory Speed Setting (rpm) Std
Fan Shaft Diameter at Pulley (in.)
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief Cutout Reset (Auto.)
LOSS -OF-CHARG E/LOW-PRESSURE
SWITCH (Liquid LIne) (psig) Cutout Reset (Auto.)
FREEZE PROTECTION THERMOSTAT
Opens (F)
Closes (F) OUTDOOR-AIR INLET SCREENS RETURN-AIR FILTERS
Quantity...Size (in.)
Hi-Static
Hi-Static
Hi-Static
Std
Hi-Static
Hi-Static
Hi-Static
Hi-Static
Std
Hi-Static
Std
Hi-Static
Hi-Static
Hi-Static
2 3 4 5
435 445 465 635
13 15 23 25 50 50 50 50
115 115 115 115
Scroll
1 1 1 1
25 42 56 53
R-22
AcutrolMetering Device
5 --- 3 7 --- 1 1 8 --- 8 12---11
1 0 --- 2 14 --- 0 14 --- 13 21 --- 0
Propeller
1...22 1...22 1...22 1...22 3000 3500 3500 4100
1
/8...825
1
/8...825
1
/8...825
180 180 180 320
Enhanced Copper Tubes, Aluminum Lanced Fins
1...17 1...17 2...17 2...17
14.6 14.6 16.5 16.5 Enhanced Copper Tubes, Aluminum Double-Wavy Fins
2...15 2...15 2...15 4...15
4.2 5.5 5.5 5.5
1...17 1...17 2...17 2...17
3.5 3.9 3.9 3.9 Centrifugal Type, Belt Drive
1...10 x 10 1...10 x 10 1...10 x 10 1...10 x 10 800 1200 1600 2000
0.58
1.20 1.20 1.30/2.40*
2.40 2.40 2.90
48
48 48 48/56* 56 56 56
1620 1620 1620 1725
400-1000
680-1044 770-1185 1035-1460
1075-1455 1075-1455 1300-1685
Ball Ball Ball Ball
1620 2100 2100 2100
2.4/3.2
5
/
8
7
/
8
4.0
4.5
1...A...36
1.9/2.9 1.9/2.0 2.4/3.4
2.8/3.8 2.8/3.8 3.4/4.4
1/
2
5
/
8
4.5 4.0 4.0
1
/
2
5
/
8
4.5 4.0 4.5
1...A...36 1...A...36 1....4...40
1...A...39 1...A...39 1...A...40
10.0---12.4 10.0-12.4 10.0-12.4 14.7-15.5
60
65 70 75 65 65 60
5
5 5 6 6 6 5 3 3 3
31/
2
826 936 1248
1233 1233 1396
5
/
8
31/
2
5
/
8
756
5
3
/
8
450 50
428 320
7 3
22  5
30 45
Cleanable. Screen quantity and size varies with option selected.
Throwaway
2...16 x 25 x 2
1
/4...1100
5
/
5
/
31/
5
/
8 8
2
8
LEGEND
Bhp — Brake Horsepower
*Single phase/three phase.
***These units do NOT meet the California low NOx requirements.
†††California SCAQMD compliant low NOxmodels have combustion products that a re
controlled to 40 nanograms per joule or less.
10
Page 11
208/230-1-60
208/230-3-60
460-3-60
(SIZES 006 AND 007)
50HE,HJ
575-3-60
(SIZES 006 AND 007)
208/230-3-60
(SIZES 004 AND 005)
LEGEND
C—Contactor COMP — Compressor IFC Indoor (Evaporator) Fan Contactor NEC National Electrical Code TB Terminal Block
LOW VOLTAGE CONNECTIONS
INTEGRATED GAS UNIT CONTROLLER (IGC)
575-3-60
(SIZES 004 AND 005)
460-3-60
(SIZES 004 AND 005)
Fig. 12 --- Power Wiring Connections
C06158
Fig. 13 --- Field Control Wiring Raceway
C06125
11
Page 12
FLA LRA
MOCP**
FLA MC A
kW†
50HE,HJ
Actual
ELECTRI C H EAT POWER SUPPLY * DISCONNECT SIZE
NONE —/ — —/— 16.3/16.3 20/20 16/16 69/69
or B00
001A00 3.3/ 4.0 15.9/18.3 22.4/25.4 25/30 21/23 69/69
--- --- --- A 0 0
CRHEATER
IFM
FLA
NONE —/ — —/— 22.3/22.3 25/25 21/21 73/73
002A00 4.9/ 5.8 23.5/27.1 31.8/36.4 35/40 29/33 69/69
001A00 3.3/ 4.0 15.9/18.3 27.4/30.4 30/35 26/29 73/73
003B00 6.5/ 8.0 31.4/36.3 41.8/47.8 45/50 38/44 69/69
004B00 7.9/ 9.6 37.9/43.8 49.9/57.2 50/60 46/53 69/69
NONE —/ — —/— 25.6/25.6 30/30 25/25 101/101
002A00 4.9/ 5.8 23.5/27.1 36.8/41.4 40/45 35/39 73/73
001A00 3.3/ 4.0 15.9/18.3 26.0/29.0 30/30 25/27 101/101
003B00 6.5/ 8.0 31.4/36.3 46.8/52.8 50/60 44/50 73/73
002A00 4.9/ 5.8 23.5/27.1 35.5/40.0 40/40 33/37 101/101
004B00 7.9/ 9.6 37.9/43.8 54.9/62.2 60/70 51/58 73/73
003B00 6.5/ 8.0 31.4/36.3 45.4/51.4 50/60 42/47 101/101
004B00 7.9/ 9.6 37.9/43.8 53.5/60.8 60/70 49/56 101/101
002,002 9.8/11.6 46.9/54.2 64.8/73.8 70/80 60/68 101/101
NONE —/ — —/— 31.6/31.6 35/35 30/30 106/106
001A00 3.3/ 4.0 15.9/18.3 31.6/34.0 35/35 30/32 106/106
002A00 4.9/ 5.8 23.5/27.1 40.5/45.0 45/45 38/42 106/106
003B00 6.5/ 8.0 31.4/36.3 50.4/56.4 60/60 47/53 106/106
004B00 7.9/ 9.6 37.9/43.8 58.5/65.8 60/70 55/61 106/106
002,002 9.8/11.6 46.9/54.2 69.8/78.8 70/80 65/73 106/106
NONE —/ — —/— 18.5/18.5 25/25 18/18 90/90
001A00 3.3/ 4.0 9.2/10.6 18.5/19.4 25/25 18/18 90/90
002A00 4.9/ 5.8 13.6/15.6 23.1/25.7 25/30 21/24 90/90
NONE —/ — —/— 24.5/24.5 30/30 24/24 95/95
005A00 12/14.7 33.4/38.5 47.8/54.2 50/60 44/50 90/90
001A00 3.3/ 4.0 9.2/10.6 24.5/24.5 30/30 24/24 95/95
003B00 6.5/ 8.0 18.1/20.9 28.8/32.3 30/35 26/30 90/90
004B00 7.9/ 9.6 21.9/25.3 33.5/37.7 35/40 31/35 90/90
002A00 4.9/ 5.8 13.6/15.6 28.1/30.7 30/35 27/29 95/95
NONE —/ — —/— 19.4/19.4 25/25 19/19 120/120
005A00 12/14.7 33.4/38.5 52.8/59.2 60/60 50/55 95/95
001A00 3.3/ 4.0 9.2/10.6 19.4/20.5 25/25 19/19 120/120
003B00 6.5/ 8.0 18.1/20.9 33.8/37.3 35/40 32/35 95/95
004B00 7.9/ 9.6 21.9/25.3 38.5/42.7 40/45 36/40 95/95
002A00 4.9/ 5.8 13.6/15.6 24.2/26.8 30/30 22/25 120/120
003B00 6.5/ 8.0 18.1/20.9 29.9/33.4 35/35 28/31 120/120
004B00 7.9/ 9.6 21.9/25.3 34.6/38.8 35/40 32/36 120/120
005A00 12/14.7 33.4/38.5 48.9/55.4 50/60 45/51 120/120
NONE —/ — —/— 25.4/25.4 30/30 25/25 124/124
001A00 3.3/ 4.0 9.2/10.6 25.4/25.5 30/30 25/25 124/124
002A00 4.9/ 5.8 13.6/15.6 29.2/31.8 35/35 28/30 124/124
003B00 6.5/ 8.0 18.1/20.9 34.9/38.4 40/40 33/36 124/124
004B00 7.9/ 9.6 21.9/25.3 39.6/43.8 40/45 37/41 124/124
005A00 12/14.7 33.4/38.5 53.9/60.4 60/70 51/56 124/124
NONE 9.0 15.0 9.0 46.0
006A00 5.5 7.2 11.8 15.0 11.0 46.0
NONE 11.7 15.0 11.0 48.0
007A00 8.1 10.6 16.0 20.0 15.0 46.0
008A00 10.6 13.8 20.0 25.0 18.0 46.0
009A00 12.9 16.8 23.8 25.0 22.0 46.0
006A00 5.5 7.2 15.1 20.0 13.0 48.0
007A00 8.1 10.6 19.4 20.0 17.0 48.0
008A00 10.6 13.8 23.4 25.0 21.0 48.0
009A00 12.9 16.8 27.2 30.0 24.0 48.0
Table 3—Electrical Data--50HE
Min Max QTY RLA LRA QTY FLA
VOLTAGE RANGE COMPRESSOR (each) OUTDOOR FAN
CONV
IFM
Nominal
V --- P h --- H z
UNIT SI ZE
NO 187 254 1 10.9 63.0 1 0.7 2.0
OUTLET
TYPE
003
YES 187 254 1 10.9 63.0 1 0.7 2.0
208/230--- 1 --- 60 STD
(2 tons)
NO 187 254 1 16.0 88.0 1 0.7 4.9
YES 187 254 1 16.0 88.0 1 0.7 4.9
208/230--- 1 --- 60 STD
NO 187 254 1 10.3 77.0 1 0.7 4.9
YES 187 254 1 10.3 77.0 1 0.7 4.9
STD
004
NO 187 254 1 10.3 77.0 1 0.7 5.8
208/230--- 3 --- 60
(3 tons)
YES 187 254 1 10.3 77.0 1 0.7 5.8
HS
NO 414 508 1 5.1 39.0 1 0.4 2.2
YES 414 508 1 5.1 39.0 1 0.4 2.2
4 6 0 --- 3 --- 6 0 STD
12
Page 13
FLA LRA
MOCP**
FLA MC A
kW†
Actual
ELECTRI C H EAT POWER SUPPLY * DISCONNECT SIZE
50HE,HJ
NONE 9.4 15.0 9.0 60.0
or B00
006A00 5.5 7.2 12.3 15.0 11.0 60.0
--- --- --- A 0 0
CRHEATER
IFM
FLA
NONE 12.1 15.0 12.0 62.0
007A00 8.1 10.6 16.5 20.0 15.0 60.0
008A00 10.6 13.8 20.5 25.0 19.0 60.0
009A00 12.9 16.8 24.3 25.0 22.0 60.0
006A00 5.5 7.2 15.6 20.0 14.0 63.0
NONE 7.6 10 7 35
NONE 7.7 10 8 40
007A00 8.1 10.6 19.9 20.0 18.0 63.0
008A00 10.6 13.8 23.9 25.0 21.0 63.0
009A00 12.9 16.8 27.7 30.0 25.0 63.0
NONE 7.7 10 8 48
1 0.4 2.0
1 0.4 2.6
31.0
31.0
Table 3 — Electrical Data--50HE (cont)
518 632 1 4.2 31.0 1 0.4 1.9
518 632 1 4.2
Min Max QTY RLA LRA QTY FLA
VOLTAGE RANGE COMPRESSOR (each) OUTDOOR FAN
518 632 1 4.2
CONV
IFM
Nominal
V --- P h --- H z
UNIT SI ZE
NO 414 508 1 5.1 39.0 1 0.4 2.6
OUTLET
TYPE
4 6 0 --- 3 --- 6 0 HS
YES 414 508 1 5.1 39.0 1 0.4 2.6
004
NO
NO
NO
YES NONE 9.7 15 9 36
YES NONE 9.8 15 10 42
YES NONE 9.8 15 10 49
HS
STD
(3 tons)
Mi$er
Humidi-
5 7 5 --- 3 --- 6 0
13
Page 14
50HE,HJ
Actual kW{ FLA MCA MOCP** FL A LRA
ELECTRI C H EAT POWER SUPPLY DISCONNECT SIZE
B00
NONE —/— —/— 32.7/32.7 40/40 32/ 32 130/130
001A00 3.3/ 4.0 15.9/18.3 32.7/32.7 40/40 32/32 130/130
003B00 6.5/ 8.0 31.4/36.3 45.4/51.4 50/ 60 42/47 130/130
--- --- A 0 0 o r
CRHEATER
IFM
FLA
Table 3 — Electrical Data--50HE (cont)
COMPRESSOR (each) OUTDOOR FAN
002,002 9.8/ 11.6 46.9/54.2 64.8/73.8 70/80 60/68 130/130
003,003 13.1/ 16 62.8/72.5 84.7/96.8 90/100 78/89 130/130
004,004 16.0/ 19.3 75.8/87.5 100.9/115.5 110/125 93/106 130/130
NONE —/— —/— 38.7/38.7 45/45 37/ 37 135/135
001A00 3.3/ 4.0 15.9/18.3 38.7/38.7 45/45 37/37 135/135
003B00 6.5/ 8.0 31.4/36.3 50.4/56.4 60/ 60 47/53 135/135
002,002 9.8/ 11.6 46.9/54.2 69.8/78.8 70/80 65/73 135/135
003,003 13.1/ 16 62.8/72.5 89.7/101.8 90/110 83/ 95 135/135
004,004 16.0/ 19.3 75.8/87.5 105.9/120.5 110/125 98/112 135/ 135
NONE —/— —/— 24.0/24.0 30/30 24/ 24 110/110
002A00 4.9/ 5.8 13.6/15.6 24.0/25.7 30/30 24/24 110/110
003B00 6.5/ 8.0 18.1/20.9 28.8/32.3 30/ 35 26/30 110/110
005A00 12/ 14.7 33.4/38.5 47.8/54.2 50/60 44/50 110/110
004,004 16/ 19.3 43.8/50.5 60.8/69.3 70/70 56/64 110/ 110
NONE —/— —/— 30.0/30.0 35/35 29/ 29 115/115
002A00 4.9/ 5.8 13.6/15.6 30.0/30.7 35/35 29/29 115/115
003B00 6.5/ 8.0 18.1/20.9 33.8/37.3 35/ 40 32/35 115/115
005A00 12/ 14.7 33.4/38.5 52.8/59.2 60/60 50/55 115/115
004,004 16/ 19.3 43.8/50.5 65.8/74.3 70/80 62/69 115/ 115
NONE —/— —/— 24.9/24.9 30/30 25/ 25 140/140
002A00 4.9/ 5.8 13.6/15.6 24.9/26.8 30/30 25/25 140/140
003B00 6.5/ 8.0 18.1/20.9 29.9/33.4 35/ 35 28/31 140/140
005A00 12/ 14.7 33.4/38.5 48.9/55.4 50/60 45/51 140/140
004,004 16/ 19.3 43.8/50.5 62.0/70.4 70/80 57/65 140/ 140
NONE —/— —/— 30.9/30.9 35/35 30/ 30 145/145
002A00 4.9/ 5.8 13.6/15.6 30.9/31.8 35/35 30/30 145/145
003B00 6.5/ 8.0 18.1/20.9 34.9/38.4 40/ 40 33/36 145/145
005A00 12/ 14.7 33.4/38.5 53.9/60.4 60/70 51/56 145/145
004,004 16/ 19.3 43.8/50.5 67.0/75.4 70/80 63/70 145/ 145
NONE 11.9 15.0 12.0 53.0
006A00 5.5 7.2 11.9 15.0 12.0 53.0
NONE 14.6 20.0 14.0 55.0
008A00 10.6 13.8 20.0 25.0 18.0 53.0
009A00 12.9 16.8 23.8 25.0 22.0 53.0
006A00 5.5 7.2 15.1 20.0 14.0 55.0
008,008 21.1 27.7 37.3 40.0 34.0 53.0
NONE 12.3 15.0 12.0 67.0
008A00 10.6 13.8 23.4 25.0 21.0 55.0
009A00 12.9 16.8 27.2 30.0 24.0 55.0
006A00 5.5 7.2 12.3 15.0 12.0 67.0
008,008 21.1 27.7 40.7 45.0 37.0 55.0
NONE 15.0 20.0 15.0 69.0
008A00 10.6 13.8 20.5 25.0 19.0 67.0
009A00 12.9 16.8 24.3 25.0 22.0 67.0
006A00 5.5 7.2 15.6 20.0 15.0 70.0
008,008 21.1 27.7 37.8 40.0 35.0 67.0
NONE 10.1 15 10 44
NONE 10.2 15 10 50
008A00 10.6 13.8 23.9 25.0 21.0 70.0
009A00 12.9 16.8 27.7 30.0 25.0 70.0
008,008 21.1 27.7 41.2 45.0 37.0 70.0
NONE 10.3 15 10 55
RANGE
VOLTAGE
Min Max QTY RL A LRA QTY FLA
CONV
OUTLET
IFM
TYPE
NOMINAL
V --- P H --- H z
SIZE
UNIT
NO 197 254 1 21.0 115.0 1 1.5 4.9
YES 197 254 1 21.0 115.0 1 1.5 4.9
208/230--- 1 --- 60 STD
NO 187 254 1 14.1 95.0 1 1.5 4.9
YES 187 254 1 14.1 95.0 1 1.5 4.9
STD
NO 187 254 1 14.1 95.0 1 1.5 5.8
208/230--- 3 --- 60
HS
005
YES 187 254 1 14.1 95.0 1 1.5 5.8
(4 tons)
NO 414 508 1 7.1 45.0 1 0.8 2.2
YES 414 508 1 7.1 45.0 1 0.8 2.2
STD
NO 414 508 1 7.1 45.0 1 0.8 2.6
HS
4 6 0 --- 3 --- 6 0
518 632 1 6.1 38.0 1 0.6 1.9
518 632 1 6.1 38.0 1 0.6 2.0
518 632 1 6.1 38.0 1 0.8 2.6
NO
NO
STD
NO
YES NONE 12.3 15 12 45
YES NONE 12.4 15 12 52
YES NONE 12.5 15 12 57
HS
Mi$er
Humidi-
5 7 5 --- 3 --- 6 0
YES 414 508 1 7.1 45.0 1 0.8 2.6
14
Page 15
50HE,HJ
Actual kW{ FLA MCA MOCP** FLA LRA
ELECTRI C H EAT POWER SUPPLY DISCONNECT SIZE
B00
NONE —/— —/— 39.4/39.4 50/50 38/38 187/ 187
002A00 4.9/ 5.8 23.5/27.1 39.4/42.1 50/50 38/39 187/187
003B00 6.5/ 8.0 31.4/36.3 47.5/53.6 50/60 44/49 187/187
--- --- A 0 0 o r
CRHEATER
IFM
FLA
Table 3 — Electrical Data--50HE (cont)
COMPRESSOR (each) OUTDOOR FAN
02,002 8.7/ 11.6 46.9/54.2 66.9/76.0 70/80 62/70 187/187
003,003 13.0/ 16.0 62.8/72.5 86.8/98.9 90/100 80/91 187/187
004,004 15.8/ 19.3 75.8/87.5 103.0/117.6 60/50 95/ 108 187/187
NONE —/— —/— 45.4/45.4 60/50 44/44 191/ 191
002A00 4.9/ 5.8 23.5/27.1 45.4/47.1 60/60 44/44 191/191
003B00 6.5/ 8.0 31.4/36.3 52.5/58.6 80/90 49/55 191/191
02,002 8.7/ 11.6 46.9/54.2 71.9/81.0 100/110 67/75 191/191
003,003 13.0/ 16.0 62.8/72.5 91.8/103.9 110/125 85/96 191/191
004,004 15.8/ 19.3 75.8/87.5 108.0/122.6 90/ 100 100/114 191/191
002A00 4.9/ 5.8 13.6/15.6 28.9/28.9 35/35 28/28 168/168
004B00 7.9/ 9.6 21.9/25.3 34.6/38.8 35/40 32/36 168/168
005A00 12.0/ 14.7 33.4/38.5 48.9/55.4 50/60 45/51 168/168
004,004 15.8/ 19.3 43.8/50.5 62.0/70.4 70/80 57/65 168/168
004,005 19.9/ 24.3 55.2/63.8 76.3/86.9 80/90 70/80 168/168
NONE —/— —/— 34.9/34.9 40/40 34/34 173/ 173
002A00 4.9/ 5.8 13.6/15.6 34.9/34.9 40/40 34/34 173/173
004B00 7.9/ 9.6 21.9/25.3 39.6/43.8 40/45 37/41 173/173
005A00 12.0/ 14.7 33.4/38.5 53.9/60.4 60/70 51/56 173/173
004,004 15.8/ 19.3 43.8/50.5 67.0/75.4 70/80 63/70 173/173
004,005 19.9/ 24.3 55.2/63.8 81.3/91.9 90/100 76/86 173/173
NONE —/— —/— 30.6/30.6 35/35 30/30 187/ 187
002A00 4.9/ 5.8 13.6/15.6 30.6/30.6 35/35 30/30 187/187
004B00 7.9/ 9.6 21.9/25.3 36.7/40.9 40/45 34/38 187/187
005A00 12.0/ 14.7 33.4/38.5 51.1/57.5 60/60 47/53 187/187
004,004 15.8/ 19.3 43.8/50.5 64.1/72.5 70/80 59/67 187/187
004,005 19.9/ 24.3 55.2/63.8 78.4/89.1 80/90 72/82 187/187
NONE —/— —/— 36.6/36.6 40/40 36/36 192/ 192
002A00 4.9/ 5.8 13.6/15.6 36.6/36.6 40/40 36/36 192/192
004B00 7.9/ 9.6 21.9/25.3 41.7/45.9 45/50 39/43 192/192
005A00 12.0/ 14.7 33.4/38.5 56.1/62.5 60/70 53/58 192/192
004,004 15.8/ 19.3 43.8/50.5 69.1/77.5 70/80 65/72 192/192
004,005 19.9/ 24.3 55.2/63.8 83.4/94.1 90/100 78/87 192/192
RANGE
VOLTAGE
Min Max QTY RL A LRA QTY FLA
CONV
OUTLET
IFM
TYPE
NOMINAL
V --- P H --- H z
SIZE
UNIT
NO 187 254 1 25.0 150.0 1 1.5 6.6
YES 187 254 1 25.0 150.0 1 1.5 6.6
208/230--- 1 --- 60 STD
NO 187 254 1 17.3 123.0 1 1.5 5.8
006
YES 187 254 1 17.3 123.0 1 1.5 5.8
STD
(tons)
NO 187 254 1 17.3 123.0 1 1.5 7.5
208/230--- 3 --- 60
YES 187 254 1 17.3 123.0 1 1.5 7.5
HS
15
Page 16
50HE,HJ
Actual kW{ FLA MCA MOCP** FLA LRA
ELECTRI C H EAT POWER SUPPLY DISCONNECT SIZE
B00
NONE 13.9 20.0 14.0 92.0
006A00 5.5 7.2 13.9 20.0 14.0 92.0
008A00 10.6 13.8 20.5 25.0 19.0 92.0
--- --- A 0 0 o r
CRHEATER
IFM
FLA
Table 3 — Electrical Data--50HE (cont)
COMPRESSOR (each) OUTDOOR FAN
NONE 16.6 20.0 16.0 94.0
009A00 12.9 16.8 24.3 25.0 22.0 92.0
006A00 5.5 7.2 16.6 20.0 16.0 95.0
008,008 21.1 27.7 37.8 40.0 35.0 92.0
008A00 10.6 13.8 23.9 25.0 21.0 95.0
008,009 23.4 30.1 40.8 45 38 92
NONE 14.7 20.0 14.0 101.0
009A00 12.9 16.8 27.7 30.0 25.0 95.0
006A00 5.5 7.2 14.7 20.0 14.0 102.0
008,008 21.1 27.7 41.2 45.0 37.0 95.0
008A00 10.6 13.8 21.5 25.0 20.0 102.0
008,009 23.4 30.1 44.2 45 40 95
NONE 17.4 20.0 17.0 104.0
009A00 12.9 16.8 25.3 30.0 23.0 102.0
006A00 5.5 7.2 17.4 20.0 17.0 104.0
008,009 23.4 30.1 41.8 45 38 102
008A00 10.6 13.8 24.9 25.0 22.0 104.0
008,008 21.1 27.7 38.8 40.0 36.0 102.0
NONE 11.5 15 11 65
NONE 12.3 15 12 74
009A00 12.9 16.8 28.7 30.0 26.0 104.0
008,008 21.1 27.7 42.2 45.0 38.0 104.0
008,009 23.4 30.1 45.2 50 41 104
NONE 12.2 15 12 78
RANGE
VOLTAGE
Min Max QTY RL A LRA QTY FLA
CONV
OUTLET
IFM
TYPE
NOMINAL
V --- P H --- H z
SIZE
UNIT
NO 414 508 1 8.4 70.0 1 0.8 2.6
YES 414 508 1 8.4 70.0 1 0.8 2.6
STD
006
NO 414 508 1 8.4 70.0 1 0.8 3.4
4 6 0 --- 3 --- 6 0
(tons)
YES 414 508 1 8.4 70.0 1 0.8 3.4
HS
NO
518 632 1 7.1 53.0 1 0.6 2.0
YES NONE 13.6 15 13 67
STD
NO
006
518 632 1 7.1 53.0 1 0.6 2.8
HS
5 7 5 --- 3 --- 6 0
518 632 1 7.1 53.0 1 0.8 3.4
NO
YES NONE 14.4 20 14 76
YES NONE 14.4 20 14 80
Mi$er
Humidi-
HACR --- Heating, Air Conditioning an d Refrigeration
IFM --- Indoor (Evaporator) Fan Motor
LRA --- Locked Rotor Amps
MCA --- Mini mum Ci rcuit Am ps
MOCP --- Maxi mum Ov ercurrent Protectio n
NEC --- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA --- Rated Load Amps
* The values listed in this table do not include power exhaust. See power exhaust table for power exhaust requirements.
** Fuse or HACR breaker
FLA ---Full Load Amps
(tons)
{ Heater capacity (kW) is based on h eater voltage of 240v, 480v or 575v. If power distribution voltage to un it varies from rated heater voltage, h eater kW will v ary acc ordingly
NOTES:
16
Page 17
FLA LRA
MOCP**
FLA MCA
kW†
Actual
ELECTRI C H EAT POWER SUPPLY * DISCONNECT SIZE
—/ — —/ — 25.6/ 25.6 30/ 30 25/ 25 101/ 101
001 3.3/ 4.0 15.9/ 18.3 26.0/ 29.0 30/ 30 25/ 27 101/ 101
002 4.9/ 5.8 23.5/ 27.1 35.5/ 40.0 40/ 40 33/ 37 101/ 101
B00
--- --- A 0 0 o r
CRHEATER
FLA
IFM
003 6.5/ 8.0 31.4/ 36.3 45.4/ 51.4 50/ 50 42/ 47 101/ 101
004 7.9/ 9.6 37.9/ 43.1 53.5/ 60.0 60/ 60 49/ 55 101/ 101
002+002 9.8/ 11.6 46.9/ 54.2 64.8/ 73.8 70/ 80 60/ 68 101/ 101
—/ — —/ — 31.6/ 31.6 35/ 35 30/ 30 106/ 106
001 3.3/ 4.0 15.9/ 18.3 31.6/ 34.0 35/ 35 30/ 32 106/ 106
002 4.9/ 5.8 23.5/ 27.1 40.5/ 45.0 45/ 45 38/ 42 106/ 106
003 6.5/ 8.0 31.4/ 36.3 50.4/ 56.4 60/ 60 47/ 53 106/ 106
004 7.9/ 9.6 37.9/ 43.1 58.5/ 65.0 60/ 70 55/ 61 106/ 106
002+002 9.8/ 11.6 46.9/ 54.2 69.8/ 78.8 70/ 80 65/ 73 106/ 106
—/ — —/ — 18.5/ 18.5 25/ 25 18/ 18 90/ 90
001 3.3/ 4.0 9.2/ 10.6 18.5/ 19.4 25/ 25 18/ 18 90/ 90
002 4.9/ 5.8 13.6/ 15.6 23.1/ 25.7 25/ 30 21/ 24 90/ 90
—/ — —/ — 24.5/ 24.5 30/ 30 24/ 24 95/ 95
003 6.5/ 8.0 18.1/ 20.9 28.8/ 32.3 30/ 35 26/ 30 90/ 90
004 7.9/ 9.6 21.9/ 25.3 33.5/ 37.7 35/ 40 31/ 35 90/ 90
001 3.3/ 4.0 9.2/ 10.6 24.5/ 24.5 30/ 30 24/ 24 95/ 95
002 4.9/ 5.8 13.6/ 15.6 28.1/ 30.7 30/ 35 27/ 29 95/ 95
002+002 9.8/ 14.7 33.4/ 38.5 47.8/ 54.2 50/ 60 44/ 50 90/ 90
—/ — —/ — 19.4/ 19.4 25/ 25 19/ 19 120/ 120
003 6.5/ 8.0 18.1/ 20.9 33.8/ 37.3 35/ 40 32/ 35 95/ 95
004 7.9/ 9.6 21.9/ 25.3 38.5/ 42.7 35/ 45 36/ 40 95/ 95
001 3.3/ 4.0 9.2/ 10.6 19.4/ 20.5 25/ 25 19/ 19 120/ 120
002 4.9/ 5.8 13.6/ 15.6 24.2/ 26.8 30/ 30 22/ 25 120/ 120
002+002 9.8/ 14.7 33.4/ 38.5 52.8/ 59.2 50/ 60 50/ 55 95/ 95
003 6.5/ 8.0 18.1/ 20.9 29.9/ 33.4 35/ 35 28/ 31 120/ 120
004 7.9/ 9.6 21.9/ 25.3 34.6/ 38.8 35/ 40 32/ 36 120/ 120
002+002 9.8/ 14.7 33.4/ 38.5 48.9/ 55.4 50/ 60 45/ 51 120/ 120
—/ — —/ — 25.4/ 25.4 30/ 30 25/ 25 124/ 124
001 3.3/ 4.0 9.2/ 10.6 25.4/ 25.5 30/ 30 25/ 25 124/ 124
002 4.9/ 5.8 13.6/ 15.6 29.2/ 31.8 35/ 35 28/ 30 124/ 124
003 6.5/ 8.0 18.1/ 20.9 34.9/ 38.4 40/ 40 33/ 36 124/ 124
004 7.9/ 9.6 21.9/ 25.3 39.6/ 43.8 40/ 45 37/ 41 124/ 124
002+002 9.8/ 14.7 33.4/ 38.5 53.9/ 60.4 60/ 70 51/ 56 124/ 124
50HE,HJ
Table 4—Electrical Data--50HJ
COMPRESSOR (each) OUTDOOR FAN
RANGE
VOLTAGE
Min Max QTY RLA LRA QTY FLA
CONV
OUTLET
IFM TYPE
NOMINAL
V --- P H --- H z
SIZE
UNIT
NO 187 254 1 16 88 1 0.7 4.9
YES 187 254 1 16 88 1 0.7 4.9
208/230--- 1 --- 60 STD
NO 187 254 1 10.3 77 1 0.7 4.9
004
YES 187 254 1 10.3 77 1 0.7 4.9
STD
(3 tons)
NO 187 254 1 10.3 77 1 0.7 5.8
208/230--- 3 --- 60
YES 187 254 1 10.3 77 1 0.7 5.8
HS
17
Page 18
FLA LRA
MOCP**
50HE,HJ
FLA MCA
kW†
Actual
ELECTRI C H EAT POWER SUPPLY * DISCONNECT SIZE
9.0 20 9 46
006 5.5 7.2 11.8 20 11 46
B00
--- --- A 0 0 o r
CRHEATER
FLA
IFM
11.7 20 11 48
007 8.1 10.6 16.0 20 15 46
008 10.6 13.8 20.0 25 18 46
009 12.9 16.8 23.8 25 22 46
006 5.5 7.2 15.1 20 13 48
9.4 20 9 60
007 8.1 10.6 18.7 20 17 48
008 10.6 13.8 22.7 25 21 48
009 12.9 16.8 26.5 30 24 48
006 5.5 7.2 12.3 20 11 60
12.1 20 12 62
007 8.1 10.6 16.5 20 15 60
008 10.6 13.8 20.5 25 19 60
009 12.9 16.8 24.3 25 22 60
006 5.5 7.2 15.6 20 14 63
007 8.1 10.6 19.2 20 18 63
008 10.6 13.8 23.2 25 21 63
009 12.9 16.8 27.0 30 25 63
Table 4 — Electrical Data--50HJ (cont)
COMPRESSOR (each) OUTDOOR FAN
RANGE
VOLTAGE
Min Max QTY RLA LRA QTY FLA
CONV
OUTLET
IFM TYPE
NOMINAL
V --- P H --- H z
SIZE
UNIT
NO 414 508 1 5.1 39 1 0.4 2.2
YES 414 508 1 5.1 39 1 0.4 2.2
STD
NO 414 508 1 5.1 39 1 0.4 2.6
HS
4 6 0 --- 3 --- 6 0
004
(3 tons)
NO 518 632 1 4.2 31 1 0.4 1.9 7.3 20 7 36
NO 518 632 1 4.2 31 1 0.4 2.0 7.7 10 8 40
STD
NO 518 632 1 4.2 31 1 0.4 2.6 7.7 10 8 48
YES 518 632 1 4.2 31 1 0.4 1.9 9.5 20 9 30
YES 518 632 1 4.2 31 1 0.4 2.0 9.8 15 10 42
YES 518 632 1 4.2 31 1 0.4 2.6 9.8 15 10 50
HS
Mi$er
Humidi-
5 7 5 --- 3 --- 6 0
YES 414 508 1 5.1 39 1 0.4 2.6
18
Page 19
50HE,HJ
Actual kW{ FLA MCA MOCP** FLA LRA
ELECTRI C H EAT POWER SUPPLY DISCONNECT SIZE
—/— —/— 35.2/ 35.2 45/ 45 34/ 34 139/ 139
001 3.3/ 4.0 15.9/ 18.3 35.2/ 35.2 45/ 45 34/ 34 139/ 139
003 6.5/ 8.0 31.4/ 36.3 45.4/ 51.4 50/ 60 42/ 47 139/ 139
B00
--- --- A 0 0 o r
CRHEATER
IFM
FLA
002+002 9.8/ 11.6 46.9/ 54.2 64.8/ 73.8 70/ 80 60/ 68 139/ 139
003+003 13.1/ 16 62.8/ 72.5 84.7/ 96.8 90/ 100 78/ 89 139/ 139
004+004 16.0/ 19.3 75.8/ 87.5 100.9/ 115.5 110/ 125 93/ 106 139/ 139
—/— —/— 41.2/ 41.2 50/ 50 39/ 39 144/ 144
001 3.3/ 4.0 15.9/ 18.3 41.2/ 41.2 50/ 50 39/ 39 144/ 144
003 6.5/ 8.0 31.4/ 36.3 50.4/ 56.4 60/ 60 47/ 53 144/ 144
002+002 9.8/ 11.6 46.9/ 54.2 69.8/ 78.8 70/ 80 65/ 73 144/ 144
003+003 13.1/ 16 62.8/ 72.5 89.7/ 101.8 90/ 100 83/ 95 144/ 144
004+004 16.0/ 19.3 75.8/ 87.5 105.9/ 120.5 110/ 125 98/ 112 144/ 144
—/— —/— 22.5/ 22.5 30/ 30 22/ 22 106/ 106
002 4.9/ 5.8 13.6/ 15.6 23.1/ 25.7 30/ 30 22/ 24 106/ 106
003 6.5/ 8 18.1/ 20.9 28.8/ 32.3 30/ 35 26/ 30 106/ 106
005 12/ 14.7 33.4/ 38.5 47.8/ 54.2 50/ 60 44/ 50 106/ 106
004+004 16/ 19.3 43.8/ 50.5 60.8/ 59.3 70/ 70 56/ 64 106/ 106
—/— —/— 28.5/ 28.5 35/ 35 27/ 27 111/ 111
002 4.9/ 5.8 13.6/ 15.6 28.5/ 30.7 35/ 35 27/ 29 111/ 111
003 6.5/ 8 18.1/ 20.9 33.8/ 37.3 35/ 40 32/ 35 111/ 111
005 12/ 14.7 33.4/ 38.5 52.8/ 59.2 60/ 60 50/ 55 111/ 111
004+004 16/ 19.3 43.8/ 50.5 65.8/ 74.3 70/ 80 62/ 69 111/ 111
—/— —/— 23.4/ 23.4 30/ 30 23/ 23 136/ 136
002 4.9/ 5.8 13.6/ 15.6 24.2/ 26.8 30/ 30 23/ 25 136/ 136
003 6.5/ 8 18.1/ 20.9 29.9/ 33.4 35/ 35 28/ 31 136/ 136
005 12/ 14.7 33.4/ 38.5 48.9/ 55.4 50/ 60 45/ 51 136/ 136
004+004 16/ 19.3 43.8/ 50.5 62.0/ 70.4 70/ 80 57/ 65 136/ 136
—/— —/— 29.4/ 29.4 35/ 35 29/ 29 140/ 140
002 4.9/ 5.8 13.6/ 15.6 29.4/ 31.8 35/ 35 29/ 30 140/ 140
003 6.5/ 8 18.1/ 20.9 34.9/ 38.4 40/ 40 33/ 36 140/ 140
005 12/ 14.7 33.4/ 38.5 53.9/ 60.4 60/ 70 51/ 56 140/ 140
004+004 16/ 19.3 43.8/ 50.5 67.0/ 75.4 70/ 80 63/ 70 140/ 140
10.6 20 10 53
006 5.5 7.2 11.8 20 11 54
13.3 20 13 55
008 10.6 13.8 20.0 25 18 54
009 12.9 16.8 23.8 25 22 54
006 5.5 7.2 15.1 20 13 56
008+008 21.1 27.7 37.3 40 34 54
11.0 20 11 67
008 10.6 13.8 22.7 25 21 56
009 12.9 16.8 26.5 30 24 56
006 5.5 7.2 12.3 20 11 68
008+008 21.1 27.7 40.0 45 37 56
13.7 20 13 70
008 10.6 13.8 20.5 25 19 68
009 12.9 16.8 24.3 25 22 68
006 5.5 7.2 15.6 20 14 70
008 10.6 13.8 23.2 25 21 70
008+008 21.1 27.7 37.8 40 35 68
009 12.9 16.8 27.0 30 25 70
008+008 21.1 27.7 40.5 45 37 70
Table 4 — Electrical Data--50HJ (cont)
Min Max QTY RLA LRA QTY FLA
VOLTAGE RANGE COMPRESSOR (EACH) OUTDOOR FAN
CONV
OUTLET
IFM TYPE
NOMINAL
V --- P H --- H z
SIZE
UNIT
NO 197 254 1 23.7 126 1 0.7 4.9
YES 197 254 1 23.7 126 1 0.7 4.9
208/230--- 1 --- 60 STD
NO 187 254 1 13.5 93 1 0.7 4.9
YES 187 254 1 13.5 93 1 0.7 4.9
STD
NO 187 254 1 13.5 93 1 0.7 5.8
208/230--- 3 --- 60
HS
005
YES 187 254 1 13.5 93 1 0.7 5.8
(4 ton)
NO 414 508 1 6.4 46.5 1 0.4 2.2
YES 414 508 1 6.4 46.5 1 0.4 2.2
STD
NO 414 508 1 6.4 46.5 1 0.4 2.6
HS
4 6 0 --- 3 --- 6 0
NO 518 632 1 6.4 40 1 0.4 1.9 10.3 15 10 45
NO 518 632 1 6.4 40 1 0.4 2.0 10.4 15 10 52
STD
NO 518 632 1 6.4 4 1 0.4 2.6 10.4 15 10 57
YES 518 632 1 6.4 40 1 0.4 1.9 12.5 15 12 47
YES 518 632 1 6.4 40 1 0.4 2.0 12.6 15 12 53
YES 518 632 1 6.4 4 1 0.4 2.6 12.6 15 12 59
ER
HS
HUMIDIZ-
5 7 5 --- 3 --- 6 0
YES 414 508 1 6.4 46.5 1 0.4 2.6
19
Page 20
50HE,HJ
Actual kW{ FLA MCA MOCP** FLA LRA
ELECTRI C H EAT POWER SUPPLY DISCONNECT SIZE
—/— —/— 46.3/ 46.3 60/ 60 45/ 45 216/ 216
002 4.9/ 5.8 23.5/ 27.1 46.3/ 46.3 60/ 60 45/ 45 216/ 216
B00
--- --- A 0 0 o r
CRHEATER
IFM
FLA
003 6.5/ 8.0 31.4/ 36.3 50.3/ 56.3 60/ 60 46/ 52 216/ 216
002+002 8.7/ 11.6 46.9/ 54.2 69.7/ 78.7 70/ 80 64/ 72 216/ 216
003+003 13.0/ 16.0 62.8/ 72.5 49.5/ 101.6 90/ 110 82/ 93 216/ 216
004+004 15.8/ 19.3 75.8/ 87.5 105.8/ 120.4 110/ 125 97/ 111 216/ 216
—/— —/— 52.3/ 52.3 60/ 60 50/ 50 221/ 221
002 4.9/ 5.8 23.5/ 27.1 52.3/ 52.3 60/ 60 50/ 50 221/ 221
003 6.5/ 8.0 31.4/ 36.3 55.3/ 61.3 60/ 70 52/ 57 221/ 221
002+002 8.7/ 11.6 46.9/ 54.2 74.7/ 83.7 80/ 90 70/ 78 221/ 221
003+003 13.0/ 16.0 62.8/ 72.5 94.5/ 106.6 100/ 110 88/ 99 221/ 221
004+004 15.8/ 19.3 75.8/ 87.5 110.8/ 125.4 125/ 150 103/ 116 221/ 221
—/— —/— 28.9/ 28.9 35/ 35 28/ 28 168/ 168
002 4.9/ 5.8 13.6/ 15.6 28.9/ 28.9 35/ 35 28/ 28 168/ 168
004 7.9/ 9.6 21.9/ 25.3 34.6/ 38.8 35/ 35 32/ 36 168/ 168
005 12.0/ 14.7 33.4/ 38.5 48.9/ 55.4 50/ 50 45/ 51 168/ 168
004+004 15.8/ 19.3 43.8/ 50.5 62/ 70.4 70/ 70 57/ 65 168/ 168
004+005 19.9/ 24.3 55.2/ 63.8 76.3/ 86.9 80/ 80 70/ 80 168/ 168
—/— —/— 34.9/ 34.9 40/ 40 34/ 34 173/ 173
002 4.9/ 5.8 13.6/ 15.6 34.9/ 34.9 40/ 40 34/ 34 173/ 173
004 7.9/ 9.6 21.9/ 25.3 39.6/ 43.8 40/ 40 37/ 41 173/ 173
005 12.0/ 14.7 33.4/ 38.5 53.9/ 60.4 60/ 70 51/ 56 173/ 173
004+004 15.8/ 19.3 43.8/ 50.5 67/ 75.4 70/ 80 63/ 70 173/ 173
004+005 19.9/ 24.3 55.2/ 63.8 81.3/ 91.9 90/ 100 76/ 86 173/ 173
—/— —/— 30.6/ 30.6 35/ 35 30/ 30 187/ 187
002 4.9/ 5.8 13.6/ 15.6 30.6/ 30.6 35/ 35 30/ 30 187/ 187
004 7.9/ 9.6 21.9/ 25.3 36.7/ 40.9 40/ 45 34/ 38 187/ 187
005 12.0/ 14.7 33.4/ 38.5 51.1/ 57.5 60/ 60 47/ 53 187/ 187
004+004 15.8/ 19.3 43.8/ 50.5 64.1/ 72.5 70/ 80 59/ 67 187/ 187
004+005 19.9/ 24.3 55.2/ 63.8 78.4/ 89.1 80/ 90 72/ 82 187/ 187
—/— —/— 36.6/ 36.6 40/ 40 36/ 36 192/ 192
002 4.9/ 5.8 13.6/ 15.6 36.6/ 36.6 40/ 40 36/ 36 192/ 192
004 7.9/ 9.6 21.9/ 25.3 41.7/ 45.9 45/ 50 39/ 43 192/ 192
005 12.0/ 14.7 33.4/ 38.5 56.6/ 62.5 60/ 70 53/ 58 192/ 192
004+004 15.8/ 19.3 43.8/ 50.5 69.1/ 77.5 70/ 80 65/ 72 192/ 192
004+005 19.9/ 24.3 55.2/ 63.8 83.4/ 94.1 90/ 100 78/ 87 192/ 192
14.7 20 14 84
006 5.5 7.2 14.7 20 10 84
17.4 20 17 86
008 10.6 13.8 20.5 25 19 84
009 12.9 16.8 24.3 25 22 84
006 5.5 7.2 17.4 20 17 87
008+008 21.1 27.7 37.8 40 35 84
008+009 23.4 30.1 40.8 45 38 84
15.5 20 15 93
008 10.6 13.8 23.2 25 21 87
009 12.9 16.8 27.0 30 25 87
006 5.5 7.2 15.5 20 15 94
008+008 21.1 27.7 40.5 45 37 87
008+009 23.4 30.1 43.5 45 40 87
18.2 20 18 96
008 10.6 13.8 21.5 25 20 94
009 12.9 16.8 25.3 30 23 94
006 5.5 7.2 18.2 20 18 96
008 10.6 13.8 24.2 25 22 96
008+008 21.1 27.7 38.8 40 36 94
009 12.9 16.8 28.0 30 26 96
008+009 23.4 30.1 41.8 45 38 94
008+008 21.1 27.7 41.5 45 38 96
008+009 23.4 30.1 44.5 45 41 96
Table 4 — Electrical Data--50HJ (cont)
Min Max QTY RLA LRA QTY FLA
VOLTAGE RANGE COMPRESSOR (EACH) OUTDOOR FAN
CONV
OUTLET
IFM TYPE
NOMINAL
V --- P H --- H z
SIZE
UNIT
NO 187 254 1 28.8 169 1 1.5 8.8
YES 187 254 1 28.8 169 1 1.5 8.8
208/230--- 1 --- 60 STD
NO 187 254 1 17.3 123 1 1.5 5.8
YES 187 254 1 17.3 123 1 1.5 5.8
STD
NO 187 254 1 17.3 123 1 1.5 7.5
208/230--- 3 --- 60
HS
006
YES 187 254 1 17.3 123 1 1.5 7.5
(5 ton)
NO 414 508 1 9 62 1 0.8 2.6
YES 414 508 1 9 62 1 0.8 2.6
STD
NO 414 508 1 9 62 1 0.8 3.4
HS
4 6 0 --- 3 --- 6 0
NO 518 632 1 7.1 50 1 0.6 2.0 11.5 15 11 63
NO 518 632 1 7.1 50 1 0.6 2.8 12.3 15 12 72
YES 518 632 1 7.1 50 1 0.6 2.0 13.6 15 13 64
STD
HS
5 7 5 --- 3 --- 6 0
NO 518 632 1 7.1 50 1 0.6 3.4 12.2 15 12 76
YES 518 632 1 7.1 50 1 0.6 2.8 14.4 15 14 73
YES 518 632 1 7.1 50 1 0.6 3.4 14.4 20 14 77
ER
HUMIDIZ-
YES 414 508 1 9 62 1 0.8 3.4
20
Page 21
FLA LRA
MOCP**
50HE,HJ
FLA MCA
kW†
Actual
ELECTRI C H EAT POWER SUPPLY * DISCONNECT SIZE
—/— —/— 32.8/ 32.8 40/ 40 32/ 32 200/ 200
002 4.9/ 5.8 13.6/ 15.6 32.8/ 32.8 40/ 40 32/ 32 200/ 200
004 7.9/ 9.6 21.9/ 25.3 34.6/ 38.8 40/ 40 32/ 36 200/ 200
B00
CRHEATER
--- --- --- A0 0 o r
IFM
FLA
005 12.0/ 14.7 33.4/ 38.5 48.9/ 55.4 50/ 50 45/ 51 200/ 200
004+004 15.8/ 19.3 43.8/ 50.5 62.0/ 70.4 70/ 80 57/ 65 200/ 200
004+005 19.9/ 24.3 55.2/ 63.8 76.3/ 86.9 80/ 90 70/ 80 200/ 200
—/— —/— 38.8/ 38.8 45/ 45 37/ 37 205/ 205
002 4.9/ 5.8 13.6/ 15.6 38.8/ 38.8 45/ 45 37/ 37 205/ 205
004 7.9/ 9.6 21.9/ 25.3 39.6/ 43.8 45/ 45 37/ 41 205/ 205
005 12.0/ 14.7 33.4/ 38.5 53.9/ 60.4 60/ 70 51/ 56 205/ 205
004+004 15.8/ 19.3 43.8/ 50.5 67.0/ 75.4 70/ 80 63/ 70 205/ 205
004+005 19.9/ 24.3 55.2/ 63.8 76.3/ 86.9 90/ 100 76/ 86 205/ 205
—/— —/— 34.5/ 34.5 40/ 40 34/ 34 219/ 219
002 4.9/ 5.8 13.6/ 15.6 34.5/ 34.5 40/ 40 34/ 34 219/ 219
004 7.9/ 9.6 21.9/ 25.3 36.7/ 40.9 40/ 45 34/ 38 219/ 219
005 12.0/ 14.7 33.4/ 38.5 51.1/ 57.5 60/ 60 47/ 53 219/ 219
004+004 15.8/ 19.3 43.8/ 50.5 64.1/ 72.5 70/ 80 59/ 67 219/ 219
004+005 19.9/ 24.3 55.2/ 63.8 78.4/ 89.1 80/ 90 72/ 82 219/ 219
—/— —/— 40.5/ 40.5 45/ 45 39/ 39 224/ 224
002 4.9/ 5.8 13.6/ 15.6 40.5/ 40.5 45/ 45 39/ 39 224/ 224
004 7.9/ 9.6 21.9/ 25.3 41.7/ 45.9 45/ 50 39/ 43 224/ 224
005 12.0/ 14.7 33.4/ 38.5 56.1/ 62.5 60/ 70 53/ 58 224/ 224
004+004 15.8/ 19.3 43.8/ 50.5 69.1/ 77.5 70/ 80 65/ 72 224/ 224
004+005 19.9/ 24.3 55.2/ 63.8 83.4/ 94.1 90/ 100 78/ 87 224/ 224
15.2 20 15 97
006 5.5 7.2 15.2 20 15 97
008 10.6 13.8 20.5 25 19 97
17.9 20 17 99
009 12.9 16.8 24.3 25 22 97
006 5.5 7.2 17.9 20 17 99
008+008 21.1 27.7 37.8 40 35 97
008 10.6 13.8 23.2 25 21 99
008+009 23.4 30.7 41.6 45 38 97
16.0 20 16 106
009 12.9 16.8 27.0 30 25 99
006 5.5 7.2 16.0 20 16 107
008+008 21.1 27.7 40.5 45 37 99
008 10.6 13.8 21.5 25 20 107
008+009 23.4 30.7 44.3 45 41 99
009 12.9 16.8 25.3 30 23 107
008+008 21.1 27.7 38.8 40 36 107
008+009 23.4 30.7 42.6 45 39 107
18.7 25 18 108
006 5.5 7.2 18.7 25 18 109
008 10.6 13.8 24.2 25 22 109
009 12.9 16.8 28.0 30 26 109
008+008 21.1 27.7 41.5 45 38 109
008+009 23.4 30.7 45.3 50 42 109
Table 4 — Electrical Data--50HJ (cont)
COMPRESSOR (each) OUTDOOR FAN
RANGE
VOLTAGE
Min Max QTY RLA LRA QTY FLA
CONV
OUTLET
NO 187 254 1 20.5 156 1 1.4 5.8
YES 187 254 1 20.5 156 1 1.4 5.8
NO 187 254 1 20.5 156 1 1.4 7.5
YES 187 254 1 20.5 156 1 1.4 7.5
NO 414 508 1 9.6 75 1 0.6 2.6
YES 414 508 1 9.6 75 1 0.6 2.6
NO 414 508 1 9.6 75 1 0.6 3.4
NO 518 632 1 7.7 56 1 0.6 2.0 11.5 15 11 63
NO 518 632 1 7.7 56 1 0.6 2.8 12.3 15 12 72
YES 414 508 1 9.6 75 1 0.6 3.4
NO 518 632 1 7.7 56 1 0.6 3.4 12.2 15 12 76
YES 518 632 1 7.7 56 1 0.6 2.0 13.6 15 13 64
YES 518 632 1 7.7 56 1 0.6 2.8 14.4 20 14 73
YES 518 632 1 7.7 56 1 0.6 3.4 14.4 20 14 77
IFM
TYPE
NOMINAL
V --- P H --- H z
SIZE
UNIT
STD
208/230--- 3 --- 60
HS
007
STD
4 6 0 --- 3 --- 6 0
(6 ton)
HS
STD
HS
ER
HUMI-
DIMIZ-
5 7 5 --- 3 --- 6 0
21
Page 22
50HE,HJ
Actual kW{ FLA MCA MOCP** FLA LRA
ELECTRI C H EAT POWER SUPPLY* DISCONNECT SIZE
—/— —/— 38.2/ 38.2 45/ 45 40/ 40 242/ 242
017 7.8/ 9.6 21.7/ 25.0 38.2/ 40.6 45/ 45 40/ 40 242/ 242
010 12.0/ 14.7 33.4/ 38.5 51.1/ 57.5 60/ 60 47/ 53 242/ 242
B00
--- --- A 0 0 o r
CRHEATER
IFM
FLA
011 18.6/ 22.8 51.7/ 59.7 74.0/ 84.0 80/ 90 68/ 77 242/ 242
012 24.0/ 29.4 66.7/ 77.0 92.8/ 105.6 100/ 110 85/ 97 242/ 242
012+017 31.8/ 38.9 88.4/ 102.0 119.9/ 136.9 125/ 150 110/ 126 242/ 242
—/— —/— 44.2/ 44.2 50/ 50 46/ 46 247/ 247
017 7.8/ 9.6 21.7/ 25.0 44./ 45.6 50/ 50 46/ 46 247/ 247
010 12.0/ 14.7 33.4/ 38.5 56.1/ 62.5 60/ 70 53/ 58 247/ 247
011 18.6/ 22.8 51.7/ 59.7 79.0/ 89.0 80/ 90 74/ 83 247/ 247
012 24.0/ 29.4 66.7/ 77.0 97.8/ 110.6 100/ 125 91/ 103 247/ 247
012+017 31.8/ 38.9 88.4/ 102.0 124.9/ 141.9 125/ 150 116/ 131 247/ 247
—/— —/— 41.3/ 41.3 45/ 45 44/ 44 267/ 267
017 7.8/ 9.6 21.7/ 25.0 41.3/ 44.5 50/ 50 44/ 44 267/ 267
010 12.0/ 14.7 33.4/ 38.5 54.9/ 61.4 60/ 70 51/ 56 267/ 267
011 18.6/ 22.8 51.7/ 59.7 77.9/ 87.8 80/ 90 72/ 81 267/ 267
012 24.0/ 29.4 66.7/ 77.0 96.6/ 109.5 100/ 110 89/ 101 267/ 267
012+017 31.8/ 38.9 88.4/ 102.0 123.7/ 140.8 125/ 150 114/ 129 267/ 267
—/— —/— 47.3/ 47.3 50/ 50 49/ 49 271/ 271
017 7.8/ 9.6 21.7/ 25.0 47.3/ 49.5 60/ 60 49/ 49 271/ 271
010 12.0/ 14.7 33.4/ 38.5 59.9/ 66.4 70/ 70 56/ 62 271/ 271
011 18.6/ 22.8 51.7/ 59.7 82.9/ 92.8 90/ 100 77/ 86 271/ 271
012 24.0/ 29.4 66.7/ 77.0 101.6/ 114.5 110/ 125 94/ 106 271/ 271
012+017 31.8/ 38.9 88.4/ 102.0 128.7/ 145.8 150/ 150 119/ 135 271/ 271
19.2 20 20 121
016 12.8 16.7 25.1 20 23 121
013 15.2 19.8 29.1 20 27 121
014 25.5 33.4 46.0 50 42 121
015 30.3 39.7 53.9 60 50 121
014+016 38.3 50.2 66.9 70 62 121
21.9 20 23 123
016 12.8 16.7 28.5 20 26 123
013 15.2 19.8 31.8 35 29 123
014 25.5 33.4 48.7 50 45 123
015 30.3 39.7 56.6 60 52 123
014+016 38.3 50.2 69.6 70 64 123
20.6 20 22 133
016 12.8 16.7 26.9 20 25 134
013 15.2 19.8 30.8 35 28 134
014 25.5 33.4 47.8 50 44 134
015 30.3 39.7 55.6 60 51 134
014+016 38.3 50.2 68.7 70 63 134
23.3 20 24 135
016 12.8 16.7 30.3 35 27 136
013 15.2 19.8 33.5 35 31 136
014 25.5 33.4 50.5 60 46 136
015 30.3 39.7 58.3 60 54 136
014+016 38.3 50.2 71.4 80 66 136
Table 4 — Electrical Data--50HJ (cont)
Min Max QTY RLA LRA QTY FLA
VOLTAGE RANGE COMPRESSOR (each) OUTDOOR FAN
CONV
OUTLET
NO 187 254 2 12.4 88 2 1.4 7.5
YES 187 254 2 12.4 88 2 1.4 7.5
NO 187 254 2 12.4 88 2 1.4 10.6
YES 187 254 2 12.4 88 2 1.4 10.6
NO 414 508 2 6.4 44 2 0.7 3.4
YES 414 508 2 6.4 44 2 0.7 3.4
NO 414 508 2 6.4 44 2 0.7 4.8
YES 414 508 2 6.4 44 2 0.7 4.8
IFM
TYPE
NOMINAL
V --- P H --- H z
SIZE
UNIT
STD
208/230--- 3 --- 60
HS
008
STD
(7.5
ton)
HS
4 6 0 --- 3 --- 6 0
22
Page 23
50HE,HJ
Actual kW{ FLA MCA MOCP** FLA LRA
ELECTRI C H EAT POWER SUPPLY* DISCONNECT SIZE
14.8 20 16 91
17.0 20 18 93
15.3 20 16 101
17.5 20 18 103
15.8 20 17 104
018 17.0 16.4 23.9 25 22 91
019 34.0 32.7 44.4 45 41 91
018 17.0 16.4 26.6 30 24 93
019 34.0 32.7 44.4 45 43 93
018 17.0 16.4 24.6 25 23 101
019 34.0 32.7 45.0 50 42 101
018 17.0 16.4 27.2 30 25 103
B00
--- --- A 0 0 o r
CRHEATER
IFM
FLA
019 34.0 32.7 45.0 50 44 103
Table 4 — Electrical Data--50HJ (cont)
018 17.0 16.4 25.5 30 23 104
019 34.0 32.7 45.7 50 42 104
17.9 20 19 106
018 17.0 16.4 27.9 30 25 106
019 34.0 32.7 45.7 50 44 106
VOLTAGE RANGE COMPRESSOR (each) OUTDOOR FAN
Min Max QTY RLA LRA QTY FLA
CONV
OUTLET
IFM
TYPE
NOMINAL
V --- P H --- H z
SIZE
UNIT
NO 518 632 2 4.8 34 2 0.6 2.8
STD
NO 518 632 2 4.8 34 2 0.6 3.3
YES 518 632 2 4.8 34 2 0.6 2.8
HS
5 7 5 --- 3 --- 6 0
008
(7.5
NO 518 632 2 4.8 34 2 0.7 4.8
YES 518 632 2 4.8 34 2 0.6 3.3
ton)
YES 518 632 2 4.8 34 2 0.7 4.8
ER
HUMI-
DIMIZ-
23
Page 24
50HE,HJ
Actual kW{ FLA MCA MOCP** FLA LRA
ELECTRI C H EAT POWER SUPPLY DISCONNECT SIZE
—/ — —/ — 40.2/ 40.2 45/ 45 42/ 42 276/ 276
017 7.8/ 9.6 21.7/ 25.0 40.2/ 40.6 45/ 45 42/ 42 276/ 276
010 12.0/ 14.7 33.4/ 38.5 51.1/ 57.5 60/ 60 47/ 53 276/ 276
B00
--- --- A 0 0 o r
CRHEATER
IFM
FLA
011 18.6/ 22.8 51.7/ 59.7 74.0/ 84.0 80/ 90 68/ 77 276/ 276
012 24.0/ 29.4 66.7/ 77.0 92.8/ 105.6 100/ 110 85/ 97 276/ 276
012+017 31.8/ 38.9 88.4/ 102.0 119.9/ 136.9 110/ 150 110/ 126 276/ 276
—/ — —/ — 46.2/ 46.2 50/ 50 48/ 48 281/ 281
017 7.8/ 9.6 21.7/ 25.0 46.2/ 46.2 50/ 50 48/ 48 281/ 281
010 12.0/ 14.7 33.4/ 38.5 56.1/ 62.5 60/ 70 53/ 58 281/ 281
011 18.6/ 22.8 51.7/ 59.7 79.0/ 89.0 80/ 90 74/ 83 281/ 281
012 24.0/ 29.4 66.7/ 77.0 97.8/ 110.6 100/ 125 91/ 103 281/ 281
012+017 31.8/ 38.9 88.4/ 102.0 124.9/ 141.9 125/ 150 116/ 131 281/ 281
—/ — —/ — 43.3/ 43.3 50/ 50 46/ 46 301/ 301
017 7.8/ 9.6 21.7/ 25.0 43.3/ 44.5 50/ 50 46/ 46 301/ 301
010 12.0/ 14.7 33.4/ 38.5 54.9/ 61.4 60/ 70 51/ 56 301/ 301
011 18.6/ 22.8 51.7/ 59.7 77.9/ 87.8 80/ 90 72/ 81 301/ 301
012 24.0/ 29.4 66.7/ 77.0 96.6/ 109.5 100/ 110 89/ 101 301/ 301
012+017 31.8/ 38.9 88.4/ 102.0 123.7/ 140.8 125/ 150 114/ 129 301/ 301
—/ — —/ — 49.3/ 49.3 60/ 60 51/ 51 305/ 305
017 7.8/ 9.6 21.7/ 25.0 49.3/ 49.5 60/ 60 51/ 51 305/ 305
010 12.0/ 14.7 33.4/ 38.5 59.9/ 66.4 70/ 70 56/ 62 305/ 305
011 18.6/ 22.8 51.7/ 59.7 82.9/ 92.8 90/ 100 77/ 86 305/ 305
012 24.0/ 29.4 66.7/ 77.0 101.6/ 114.5 110/ 125 94/ 106 305/ 305
012+017 31.8/ 38.9 88.4/ 102.0 128.7/ 145.8 150/ 150 119/ 135 305/ 305
21.5 30 23 143
016 12.8 16.7 25.1 30 23 143
013 15.2 19.8 29.1 30 27 143
014 25.5 33.4 46.0 50 42 143
015 30.3 39.7 53.9 60 50 143
014+016 38.3 50.2 66.9 70 62 143
24.2 30 25 145
016 12.8 16.7 28.5 30 26 145
013 15.2 19.8 31.8 35 29 145
014 25.5 33.4 48.7 50 45 145
015 30.3 39.7 56.6 60 52 145
014+016 38.3 50.2 69.6 70 64 145
22.9 30 24 155
016 12.8 16.7 26.9 30 25 156
013 15.2 19.8 30.8 35 28 156
014 25.5 33.4 47.8 50 44 156
015 30.3 39.7 55.6 60 51 156
014+016 38.3 50.2 68.7 70 63 156
25.6 30 27 157
016 12.8 16.7 30.3 35 27 158
013 15.2 19.8 33.5 35 31 158
014 25.5 33.4 50.5 60 46 158
015 30.3 39.7 58.3 60 54 158
014+016 38.3 50.2 71.4 80 66 158
Table 4 — Electrical Data--50HJ (cont)
Min Max QTY RLA LRA QTY FLA
VOLTAGE RANGE COMPRESSOR (each) OUTDOOR FAN
CONV
OUTLET
NO 187 254 2 13.4 105 2 1.4 7.5
NO 187 254 2 13.4 105 2 1.4 10.6
YES 187 254 2 13.4 105 2 1.4 7.5
YES 187 254 2 13.4 105 2 1.4 10.6
NO 414 508 2 7.4 55 2 0.7 3.4
YES 414 508 2 7.4 55 2 0.7 3.4
NO 414 508 2 7.4 55 2 0.7 4.8
YES 414 508 2 7.4 55 2 0.7 4.8
IFM
TYPE
NOMINAL
V --- P H --- H z
SIZE
UNIT
STD
208/230--- 3 --- 60
HS
009
STD
4 6 0 --- 3 --- 6 0
(8.5
ton)
HS
24
Page 25
50HE,HJ
Actual kW{ FLA MCA MOCP** FLA LRA
ELECTRI C H EAT POWER SUPPLY DISCONNECT SIZE
18.4 25 19 111
20.6 25 21 113
18.9 25 20 121
21.1 25 22 123
19.4 25 20 124
018 17.0 16.4 23.9 25 22 111
019 34.0 32.7 44.4 45 41 111
018 17.0 16.4 26.6 30 24 113
019 34.0 32.7 44.4 45 43 113
018 17.0 16.4 24.6 25 23 121
019 34.0 32.7 45.0 50 41 121
018 17.0 16.4 27.9 30 25 123
B00
--- --- A 0 0 o r
CRHEATER
IFM
FLA
019 34.0 32.7 45.0 50 43 123
Table 4 — Electrical Data--50HJ (cont)
018 17.0 16.4 25.2 30 23 124
019 34.0 32.7 45.7 50 42 124
21.5 25 22 126
018 17.0 16.4 27.9 30 25 126
019 34.0 32.7 48.3 50 44 126
VOLTAGE RANGE COMPRESSOR (each) OUTDOOR FAN
Min Max QTY RLA LRA QTY FLA
CONV
OUTLET
IFM
TYPE
NOMINAL
V --- P H --- H z
SIZE
UNIT
NO 518 632 2 6.4 44 2 0.6 2.8
STD
NO 518 632 2 6.4 44 2 0.6 3.3
YES 518 632 2 6.4 44 2 0.6 2.8
HS
5 7 5 --- 3 --- 6 0
009
(8.5
NO 518 632 2 6.4 44 2 0.7 3.3
YES 518 632 2 6.4 44 2 0.6 3.3
ton)
YES 518 632 2 6.4 44 2 0.7 3.3
ER
HUMI-
DIMIZ-
25
Page 26
50HE,HJ
Actual kW{ FL A MCA MOCP** FLA LRA
ELECTRI C H EAT POWER SUPPLY DISCONNECT SIZE
—/ — —/ — 53.0/ 53.0 60/ 60 56/ 56 341/ 341
017 7.8/ 9.6 21.7/ 25.0 53.0/ 53.0 60/ 60 56/ 56 341/ 341
010 12.0/ 14.7 33.4/ 38.5 54.9/ 61.4 60/ 70 56/ 56 341/ 341
B00
--- --- A 0 0 o r
CRHEATER
IFM
FLA
012 24.0/ 29.4 66.7/ 77.0 96.6/ 109.5 100/ 110 89/ 101 341/ 341
012+017 31.8/ 38.9 88.4/ 102.0 123.7/ 140.8 125/ 150 114/ 129 341/ 341
012+010 37.5/ 45.9 104.2/ 104.2 143.5/ 133.5 150/ 150 132/ 151 341/ 341
—/ — —/ — 59.0/ 59.0 70/ 70 61/ 61 345/ 345
017 7.8/ 9.6 21./ 25.0 59.0/ 59.0 70/ 70 61/ 61 345/ 345
010 12.0/ 14.7 33.4/ 38.5 59.9/ 66.4 70/ 70 61/ 62 345/ 345
012 24.0/ 29.4 66.7/ 77.0 101.6/ 114.5 110/ 125 94/ 106 345/ 345
012+017 31.8/ 38.9 88.4/ 102.0 128.7/ 145.8 150/ 150 119/ 135 345/ 345
012+010 37.5/ 45.9 104.2/ 120.3 148.5/ 137.5 150/ 150 138/ 156 345/ 345
—/ — —/ — 57.4/ 57.4 70/ 70 61/ 61 364/ 364
017 7.8/ 9.6 21.7/ 25.0 57.4/ 57.4 70/ 70 62/ 62 364/ 364
010 12.0/ 14.7 33.4/ 38.5 60.4/ 66.9 70/ 80 61/ 62 364/ 364
012 24.0/ 29.4 66.7/ 77.0 102.1/ 115.0 110/ 125 94/ 106 364/ 364
012+017 31.8/ 38.9 88.4/ 102.0 129.2/ 146.3 150/ 150 119/ 135 364/ 364
012+010 37.5/ 45.9 104.2/ 120.3 149.0/ 139.0 150/ 175 137/ 156 364/ 364
—/ — —/ — 63.4/ 63.4 70/ 70 66/ 66 369/ 369
017 7.8/ 9.6 21./ 25.0 63.4/ 63.4 70/ 70 66/ 66 369/ 369
010 12.0/ 14.7 33.4/ 38.5 65.4/ 71.9 80/ 80 66/ 67 369/ 369
012 24.0/ 29.4 66.7/ 77.0 107.1/ 120.0 110/ 125 99/ 111 369/ 369
012+017 31.8/ 38.9 88.4/ 102.0 134.2/ 151.3 150/ 175 124/ 140 369/ 369
012+010 37.5/ 45.9 104.2/ 120.3 154.0/ 143.0 175/ 175 143/ 161 369/ 369
24.9 30 26 170
016 12.8 16.7 26.9 30 26 171
013 15.2 19.8 30.8 35 28 171
015 30.3 39.7 55.6 60 51 171
014+016 38.3 50.2 68.7 70 63 171
015+013 45.9 60.1 66.1 80 75 171
27.6 30 29 172
016 12.8 16.7 30.3 35 29 173
013 15.2 19.8 33.5 35 31 173
015 30.3 39.7 58.3 60 54 173
014+016 38.3 50.2 71.4 80 66 173
015+013 45.9 60.1 70.1 80 77 173
27.5 30 29 182
016 12.8 16.7 30.1 35 29 182
13 15.2 19.8 34.1 40 31 182
15 30.3 39.7 58.9 60 54 182
014+016 38.3 50.2 71.9 80 66 182
015+013 45.9 60.1 69.4 80 78 182
30.2 35 32 184
016 12.8 16.7 33.5 40 32 184
013 15.2 19.8 36.8 40 34 184
015 30.3 39.7 61.6 70 57 184
014+016 38.3 50.2 74.6 80 69 184
015+013 45.9 60.1 73.4 80 80 184
Table 4 — Electrical Data--50HJ (cont)
COMPRESSOR (each) OUTDOOR FAN
RANGE
VOLTAGE
Min Max QTY RLA LRA QTY FLA
OUT-
CONV
IFM
LET
TYPE
NO 187 254 2 17.6 125 2 1.4 10.6
YES 187 254 2 17.6 125 2 1.4 10.6
STD
NO 187 254 2 17.6 125 2 1.4 15
YES 187 254 2 17.6 125 2 1.4 15
HS
NO 414 508 2 8.3 62.5 2 0.7 4.8
YES 414 508 2 8.3 62.5 2 0.7 4.8
STD
NO 414 508 2 8.3 62.5 2 0.7 7.4
YES 414 508 2 8.3 62.5 2 0.7 7.4
HS
NOMINAL
V --- P H --- H z
SIZE
UNIT
208/230--- 3 --- 60
012
(10 ton)
4 6 0 --- 3 --- 6 0
26
Page 27
50HE,HJ
Actual kW{ FL A MCA MOCP** FLA LRA
ELECTRI C H EAT POWER SUPPLY DISCONNECT SIZE
18.7 25 20 133
B00
--- --- A 0 0 o r
CRHEATER
IFM
FLA
18 17.0 16.4 24.6 25 23 133
019 34.0 32.7 45.0 50 41 133
018+019 51.0 49.1 53.2 60 60 133
20.8 25 22 135
018 17.0 16.4 27.2 30 25 135
019 34.0 32.7 45.0 50 43 135
018+019 51.0 49.1 55.8 60 62 135
21.0 25 22 139
018 17.0 16.4 27.4 30 25 139
019 34.0 32.7 47.9 50 44 139
018+019 51.0 49.1 56.1 70 63 139
23.1 25 24 141
018 17.0 16.4 30.1 35 27 141
019 34.0 32.7 47.9 60 46 141
018+019 51.0 49.1 58.7 70 65 141
21.2 25 23 146
018 17.0 16.4 27.8 30 26 146
019 34.0 32.7 48.3 50 44 146
018+019 51.0 49.1 56.5 70 63 146
23.4 25 25 148
018 17.0 16.4 30.5 50 28 148
019 34.0 32.7 50.9 60 46 148
018+019 51.0 49.1 59.1 70 65 148
Table 4 — Electrical Data--50HJ (cont)
COMPRESSOR (each) OUTDOOR FAN
RANGE
VOLTAGE
OUT-
CONV
IFM
Min Max QTY RLA LRA QTY FLA
NO 518 632 2 6.3 50 2 0.6 3.3
LET
TYPE
YES 518 632 2 6.3 50 2 0.6 3.3
STD
NO 518 632 2 6.3 50 2 0.6 5.6
HS
518 632 2 6.3 50 2 0.6 5.6
YES
NO 518 632 2 6.3 50 2 0.7 7.4
YES 518 632 2 6.3 50 2 0.7 7.4
ER
HUMI-
DIMIZ-
NOMINAL
V --- P H --- H z
SIZE
UNIT
012
5 7 5 --- 3 --- 6 0
(10 ton)
27
Page 28
50HE,HJ
Actual kW{ FLA MCA MOCP** FLA LRA
ELECTRI C H EAT POWER SUPPLY DISCONNECT SIZE
—/ — —/ — 60.6/ 60.6 70/ 70 64/ 64 426/426
017 7.8/ 9.6 21.7// 25.0 60.6/ 60.6 70/ 70 64/ 64 426/426
010 12.0/ 14.7 33.4/ 38.5 60.4/ 66.9 70/ 70 64/ 64 426/426
B00
--- --- A 0 0 O R
CRHEATER
IFM
FLA
012 24.0/ 29.4 66.7/ 77.0 102.1/ 115.0 110/ 125 94/ 106 426/426
012+017 31.8/ 38.9 88.4/ 102.0 129.2/ 146.3 150/ 150 119/ 135 426/426
012+010 37.5/ 45.9 104.2/ 120.3 149.0/ 139.0 150/ 175 137/ 156 426/426
—/ — —/ — 66.6/ 66.6 70/ 70 70/ 70 431/431
016 7.8/ 9.6 21.7/ 25.0 66.6/ 66.6 70/ 70 70/ 70 431/431
013 12.0/ 14.7 33.4/ 38.5 65.4/ 71.9 80/ 80 70/ 70 431/431
015 24.0/ 29.4 66.7/ 77.0 107.1/ 120.0 110/ 125 99/ 111 431/431
014+016 31.8/ 38.9 88.4/ 102.0 134.2/ 151.3 150/ 175 124/ 140 431/431
015+013 37.5/ 45.9 104.2/ 120.3 154.0/ 143.0 175/ 175 143/ 161 431/431
29.1 35 31 197
016 12.8 16.7 30.1 35 31 197
013 15.2 19.8 34.1 40 31 197
015 30.3 39.7 58.9 60 54 197
014+016 38.3 50.2 71.9 80 66 197
015+013 45.9 60.1 69.4 80 78 197
31.8 35 33 199
016 12.8 16.7 33.5 40 33 199
013 15.2 19.8 36.8 40 34 199
015 30.3 39.7 61.6 70 57 199
014+016 38.3 50.2 74.6 80 69 199
015+013 45.9 60.1 73.4 80 80 199
23.5 30 25 147
018 17.0 16.4 27.4 30 25 147
019 34.0 32.7 47.9 50 44 147
018+019 51.0 49.1 56.1 70 63 147
25.6 30 27 149
018 17.0 16.4 30.1 35 27 149
019 34.0 32.7 47.9 50 46 149
018+019 51.0 49.1 58.7 70 65 149
23.7 30 25 154
18 17.0 16.4 27.8 35 26 154
019 34.0 32.7 48.3 50 44 154
018+019 51.0 49.1 56.5 70 63 154
25.9 35 27 155
18 17.0 16.4 30.5 40 28 155
019 34.0 32.7 50.9 60 46 155
018+019 51.0 49.1 59.1 80 65 155
Table 4 — Electrical Data--50HJ (cont)
COMPRESSOR (each) OUTDOOR FAN
RANGE
VOLTAGE
Min Max QTY RLA LRA QTY FLA
CONV
OUTLET
IFM
TYPE
NO 187 254 2 19 156 2 1.4 15
YES 187 254 2 19 156 2 1.4 15
NO 414 508 2 9 70 2 0.7 7.4
YES 414 508 2 9 70 2 0.7 7.4
NO 518 632 2 7.4 54 2 0.6 5.6
YES 518 632 2 7.4 54 2 0.6 5.6
STD
NO 518 632 2 7.4 54 2 0.7 7.4
YES 518 632 2 7.4 54 2 0.7 7.4
ER
HUMI-
DIMIZ-
NOMINAL
V --- P H --- H z
UNIT SI ZE
208/230--- 3 --- 60 STD
4 6 0 --- 3 --- 6 0 STD
014
(12.5
5 7 5 --- 3 --- 6 0
tons)
HACR --- Heating, Air Conditioning an d Refrigeration
IFM --- Indoor (Evaporator) Fan Motor
LRA --- Locked Rotor Amps
MCA --- Mini mum Ci rcuit Am ps
MOCP --- Maxi mum Ov ercurrent Protectio n
NEC --- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA --- Rated Load Amps
* The values listed in this table do not include power exhaust. See power exhaust table for power exhaust requirements.
** Fuse or HACR breaker
FLA ---Full Load Amps
{ Heater capacity (kW) is based on h eater voltage of 240v, 480v or 575v. If power distribution voltage to un it varies from rated heater voltage, h eater kW will v ary acc ordingly
NOTES:
28
Page 29
Step 6 Adjust Factory-Installed Options
Energy Recovery Units
Cobra
Please refer to the supplement provided for information on installing and operating the factory optional COBRA Energy Recovery Units. These units are equipped with a factory--installed energy recovery unit and have different installation and operation procedures than the standard unit.
Humidi--Mizer
Adaptive Dehumidification
System
Humidi--MiZer system operation can be controlled by field installation of a Carrier--approved humidistat. (See Fig. 14.)
NOTE: A light commercial Thermidistatdevice (Fig. 15) can be used instead of the humidistat if desired. The Thermidistat device includes a thermostat and a humidistat. The humidistat is normally used in applications where a temperature sensor is already provided (units with PremierLinkcontrol).
% RELATIVE HUMIDITY
C06126
Fig. 14 --- Accessory Field--Installed Humidistat
C06127
Fig. 15 --- Light Commercial thermidistat Device
To install the humidistat:
1. Route humidistat cable through hole provided in unit control box.
2. Some models may be equipped with a raceway built into the corner post on the left side of control box (See Fig.
13.) This raceway provides the required clearance between high--voltage and low voltage wiring. For models without a raceway, ensure to provide the NEC required clearance between high--voltage and low--voltage wiring.
3. Use a wire nut to connect humidistat cable into low­voltage wiring as shown in Fig. 16.
To install Thermidistat device:
1. Route Thermidistat cable through hole provided in unit control box.
2. Some models may be equipped with a raceway built into the corner post on the left side of control box (See Fig.
13.) This raceway provides the required clearance between high--voltage and low voltage wiring. For models without a raceway, ensure to provide the NEC required clearance between high--voltage and low--voltage wiring.
3. A field-supplied relay must be installed between the thermidistat and the Humidi-Mizer circuit (recommended relay: HN612KK324). (See Fig. 17.) The relay coil is connected between the DEHUM output and C (common) of the unit. The relay controls the Humidi-MiZer solenoid valve and must be wired between the Humidi-MiZer fuse and the low-pressure switch. Refer to the installation instructions included with the Carrier Light Commercial Thermidistat device for more information.
Disconnect
Switch
The optional disconnect switch is non --fused. The switch has the capability of being locked in place for safety purposes.
Manual Outdoor
Damper
The outdoor--air hood and screen are attached to the basepan at the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for building. Record amount for use in Step 8.
2. Remove and save outdoor air opening panel and screws. (See Fig. 18.)
3. Remove evaporator coil access panel. Separate hood and screen from basepan by removing the 4 screws securing them. Save all screws.
4. Replace evaporator coil access panel.
5. Place hood on front of outdoor air opening panel. See Fig. 19 for hood details. Secure top of hood with the
4screwsremovedinStep3.(SeeFig.20.)
6. Remove and save 6 screws (3 on each side) from sides of the manual outdoor-air damper.
7. Align screw holes on hood with screw holes on side of manual outdoor-air damper. (See Fig. 19 and 20.) Secure hood with 6 screws from Step 6.
8. Adjust minimum position setting of the damper blade by adjusting the manual outdoor-air adjustment screws on the front of the damper blade. (See Fig. 18.) Slide blade vertically until it is in the appropriate position determined by Fig. 21. Tighten screws.
9. Remove and save screws currently on sides of hood. Insert screen. Secure screen to hood using the screws. (See Fig. 20.)
Convenience
Outlet
An optional convenience outlet provides power for rooftop use. For maintenance personnel safety, the convenience outlet power is off when the unit disconnect is off. Adjacent unit outlets may be used for service tools.
Novar Contr
ols
Optional Novar controls (ETM 3051) are available for replacement or new construction jobs.
50HE,HJ
29
Page 30
LEGEND
CB Circuit Breaker CR Cooling Relay DHR Dehumidify Relay DSV Discharge Solenoid Valve HR Heater Relay LPS Low Pressure Switch LSV Liquid Solenoid Valve LTLO Low Temperature Lockout
Field Splice
50HE,HJ
Terminal (Unmarked)
Splice
Factory Wiring
Field Control Wiring
Field Power Wiring
C06128
Fig. 16 --- Typical Humidi--MiZert Adaptive Dehumidification System
Humidistat Wiring (208/230--V Unit Shown)
LCT
R
C Y1 Y2
G W1 W2
DEHUM
OC
TSTAT WIRES
LEGEND
CB Circuit Breaker LCT — Light Commercial Thermidistat™ Device LLSV — Liquid Line Solenoid Valve LTLO — Low Temperature Lockout
Fig. 17 --- Typical Rooftop Unit with Humidi--Mizer
Adaptive Dehumidification System with Thermidistat Device
OUTDOOR AIR OPENING PANEL
3 SCREWS (SIDE)
R1
R1
ROOF TOP UNIT
R
C Y1 Y2
G
W1 W2
PINK
PINK
CB
3.2 AMPS
LTLO
HUMIDI-MIZER SYSTEM
RED
PINK
24 V
FROM HUMIDI-MIZER SYSTEM LLSV
C06129
Fig. 18 --- Damper Panel with Manual Outdoor--Air
Damper Installed
C06130
C06013
Fig. 19 --- Outdoor--Air Hood Details
30
Page 31
C06131
Fig. 20 --- Outdoor-- Air Damper With
Hood Attached
C06132
Fig. 21 --- Outdoor-- Air Damper Position Setting
Premierlink
Control
The PremierLink controller is compatible with Carrier Comfort NetworkR (CCN) devices. This control is designed to allow users the access and ability to change factory--defined settings, thus expanding the function of the standard unit control board. Carrier’s diagnostic standard tier display tools such as Navigatort or Scrolling Marquee can be used with the PremierLink controller.
The PremierLink controller (see Fig. 22 and 23) requires the use of a Carrier electronic thermostat or a CCN connection for time broadcast to initiate its internal timeclock. This is necessary for broadcast of time of day functions (occupied/unoccupied). No sensors are supplied with the field--mounted PremierLink control. The factory--installed PremierLink control includes only the supply-- air temperature (SAT) sensor and the outdoor air temperature (OAT) sensor as standard. An indoor air quality (CO2) sensor can be added as an option. Refer to Table 5 for sensor usage. Refer to Fig. 24 for PremierLink controller wiring. The PremierLink control may be mounted in the control panel or an area below the control panel.
NOTE: PremierLink controller versions 1.3 and later are shipped in Sensor mode. If used with a thermostat, the PremierLink controller must be configured to Thermostat mode.
Install the Supply Air Temperature (SAT) Sensor
When the unit is supplied with a factory--mounted PremierLink control, the supply--air temperature (SAT) sensor (33ZCSENSAT) is factory--supplied and wired. The wiring is routed from the PremierLink control over the control box, through a grommet, into the fan section, down along the back side of the fan, and along the fan deck over to the supply--air opening.
The SAT probe is wire--tied to the supply--air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re--position the sensor in the flange of the supply-- air opening or in the supply air duct (as required by local codes). Drill or punch a 1/2-- in. hole in the flange or duct. Use two field--supplied, self--drilling screws to secure the sensor probe in a horizontal orientation.
NOTE: The sensor must be mounted in the discharge airstream downstream of the cooling coil and any heating devices. Be sure the probe tip does not come in contact with any of the unit or heat surfaces.
Outdoor Air T emperature Sensor (OAT)
When the unit is supplied with a factory-mounted PremierLink control, the outdoor-air temperature sensor (OAT) is factory-supplied and wired.
Install the Indoor Air Quality (CO
Mount the optional indoor air quality (CO
)Sensor
2
) sensor according to
2
manufacturer specifications. A separate field-supplied transformer must be used to power the
sensor.
CO
2
Wire the CO
sensor to the COM and IAQI terminals of J5 on the
2
PremierLink controller. Refer to the PremierLink Installation, Start-up, and Configuration Instructions for detailed wiring and configuration information.
Enthalpy Sensors and Control
The enthalpy control (HH57AC077) is supplied as a field-installed accessory to be used with the EconoMi$er2 damper control option. The outdoor air enthalpy sensor is part of the enthalpy control. The separate field-installed accessory return air enthalpy sensor (HH57AC078) is required for differential enthalpy control.
NOTE: The enthalpy control must be set to the “D” setting for differential enthalpy control to work properly.
The enthalpy control receives the indoor and return enthalpy from the outdoor and return air enthalpy sensors and provides a dry contact switch input to the PremierLink controller. Locate the controller in place of an existing economizer controller or near the actuator. The mounting plate may not be needed if existing bracket is used.
A closed contact indicates that outside air is preferred to the return air. An open contact indicates that the economizer should remain at minimum position.
Outdoor Air Enthalphy Sensor/Enthalpy Controller (HH57AC077)
T o wire the outdoor air enthal py sensor, perform the following (See Fig. 25 and 26):
NOTE: The outdoor air sensor can be removed from the back of the enthalpy controller and mounted remotely.
50HE,HJ
31
Page 32
Table 5—PremierLinkSensor Usage
APPLICATION
OUTDOOR AIR
TEMPERATURE SENSOR
RETURN AIR
TEMPERATURE SENSOR
OUTDOOR AIR
ENTHALPY SENSOR
Dry Bulb
Tem p e r a tu r e w i t h
PremierLink* (PremierLink
I n c l u d e d ---
CRTEMPSN001A00
requires 4-20 mA
Actuator)
Differential Dry Bulb
Tem p e r a tu r e w i t h
PremierLink* (PremierLink
requires 4-20 mA
I n c l u d e d ---
CRTEMPSN001A00
R e q u i r e d ---
33ZCT55SPT
or Equivalent
Actuator)
Single Enthalpy with
PremierLink* (PremierLink
requires 4-20 mA
Actuator)
I n c l u d e d ---
Not Used
R e q u i r e d ---
HH57AC077
or Equivalent
Differential Enthalpy
50HE,HJ
with PremierLink*
(PremierLink
requires 4-20 mA
I n c l u d e d ---
Not Used
Actuator)
*PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT and Outdoor Air Temperature sensor C RTEMPSN001A00
— Included with factory-installed PremierLink control; field-supplied and field-installed with field-installed PremierLink control.
NOTES:
1. CO
Sensors (Optional):
2
33ZCSENCO2 — Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor. 33ZCASPCO2 — Aspirator box used for duct-mounted CO 33ZCT55CO2 — Space temperature and CO 33ZCT56CO2 — Space temperature and CO
2. All units include the following Standard Sensors: Outdoor-Air Sensor — 50HJ 540569 — Opens at 67_F, c l o s e s a t 5 2 _F, not adjustable. Mixed-Air Sensor — HH97AZ001 — (PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT and Outdoor Air Temperature Sensor CRTEMPSN001A00) Compressor Lockout Sensor — 50HJ540570 — Opens at 35_F, c l o s e s a t 5 0 _F.
room sensor with override.
2
room sensor with override and set point.
2
room sensor.
2
R e q u i r e d --­HH57AC077
or Equivalent
RETURN AIR
ENTHALPY SENSOR
R e q u i r e d --­HH57AC078
or Equivalent
Fig. 22 --- PremierLink Controller
32
C06016
Page 33
PREMIERLINK CONTROL
HINGED DOOR PANEL
50HE,HJ
C06017
Fig. 23 --- PremierLinktController (Installed)
OAT
PNK
VIO
YEL
BLU
BLK
RED
BLU
YEL
WHT
7
6
11
10
8
2
3
4
1
5
9
12
TR
SR
2
OUTDOOR AIR
ENTHALPY SENSOR
Economi$er2
4 - 20mA
RED
BRN
PNK
7
VIO
6
11
10
8
2
3
4
Power Exhaust/Energy Recycler
1
GRA
5
ORN
9
PNK
12
TR1
+
3
GRAY
RED
SAT
Space Temp./ Set
Point Adjustment
Indoor Air
Quality Sensor
Outdoor Air
Quality Sensor
GRAY
BLK
S
RETURN AIR
ENTHALPY
SENSOR
BLK
RED
RMTOCC
CMPSAFE
FSD
SFS
CCN
Com
+
m.
TB-2
1
2
3
4
5
6
7
8
TB-3
1
2
3
4
5
6
7
8
BLU
BRN
BLK
BRN
RED
BRN
BLU
ORN
GRN
YEL
BLU
WHT
PNK
RED
WHT
BLK
VIO
BRN
BRN
ORN
RED
BLU
LEGEND
GRA
PNK
BRN
BRN
GRN
YEL
BLU
WHT
PNK
BLK
BLU
GRA
GRA
PNK
BLK
ANAL OG
0-20mAIN
DISCRETE
PWR
BRN
J6
J5
J4
J1
COMMS — Communications OAT Outdoor Air Temperature Sensor PWR Power RTU Rooftop Unit SAT Supply Air Temperature Sensor TB Terminal Block
Fig. 24 --- Typical PremierLink Control Wiring
J2
COMMS
RED
BRN
J9
0-20 mA
TB-1
1
2
3
W1
4
5
W2
6
7
8
RTU Terminal
Board
HK50AA0
39
PremierLink
J7
PP/MP
WHT
R
RED
Y1
GRA
Y2
ORN
ORN
PNK
G
WHT
C
X
GRA
Relays
J8
PNK
ORNORN
ORN
RED
C06018
33
Page 34
1. Use a 4-conductor, 18 or 20 AWG cable to connect the
A
enthalpy control to the PremierLinkcontroller and power transformer.
2. Connect the following 4 wires from the wire harness
BRACKET
HH57AC077 ENTHALPY CONTROL AND OUTDOOR AIR ENTHALPY SENSOR
located in rooftop unit to the enthalpy controller:
a. Connect the BRN wire to the 24 vac terminal (TR1) on
enthalpy control and to pin 1 on 12-pin harness.
b. Connect the RED wire to the 24 vac GND terminal (TR)
on enthalpy sensor and to pin 4 on 12-pin harness.
c. Connect the GRAY/ORN wire to J4-2 on PremierLink
controller and to terminal (3) on enthalpy sensor.
d. Connect the GRAY/RED wire to J4-1 on PremierLink
HH57AC078 ENTHALPY SENSOR (USED WITH ENTHALPY CONTROL FOR DIFFERENTIAL ENTHALPY OPERATION)
C7400A1004
+
controller and to terminal (2) on enthalpy sensor.
NOTE: If installing in a Carrier rooftop, use the two gray wires provided from the control section to the economizer to connect PremierLinkcontrollertoterminals2and3onenthalpysensor.
MOUNTING PLATE
Return Air Enthalphy Sensor
Mount the return-air enthalpy sensor (HH57AC078) in the
50HE,HJ
return-air duct. The return air sensor is wired to the enthalpy controller (HH57AC077). The outdoor enthalpy changeover set point is set at the controller.
ENTHALPY CONTROLLER
B
TR TR1
C
A
D
SO
SR
2
LED
NOTES:
1. Remove factory-installed jumper across SR and + before connecting wires from return air sensor.
2. Switches shown in high outdoor air enthalpy state. Terminals 2 and 3 close on low outdoor air enthalpy relative to indoor air enthalpy.
3. Remove sensor mounted on back of control and locate in outside air­stream.
RED BRN
BLK
+
+
3
1
RED
GRAY/ORN
GRAY/RED
WIRE HARNESS IN UNIT
(OUTDOOR
S
AIR
+
ENTHALPY
SENSOR)
S
(RETURN AIR
ENTHALPY
+
SENSOR)
C06019
Fig. 25 --- Outdoor and Return Air Sensor Wiring
Connections for Differential Enthalpy Control
To wire the return air enthalpy sensor, perform the following (See Fig. 25):
1. Use a 2--conductor, 18 or 20 AWG, twisted pair cable to connect the return air enthalpy sensor to the enthalpy controller.
2. At the enthalpy control remove the factory-installed resistor from the (SR) and (+) terminals.
3. Connect the field-supplied RED wire to (+) spade connector on the return air enthalpy sensor and the (SR+) terminal on the enthalpy controller. Connect the BLK wire to (S) spade connector on the return air enthalpy sensor and the (SR) terminal on the enthalpy controller.
Fig. 26 --- Differential Enthalpy Control,
Sensor and Mounting Plate (33AMKITENT006)
ECONOMI$ER IV CONTROLLER
WIRING HARNESS
CTUATOR
OUTSIDE AIR TEMPERATURE SENSOR
LOW AMBIENT SENSOR
Fig. 27 --- EconoMi$er IV Component Locations
ECONOMI$ER2 PLUG
OUTDOOR AIR HOOD
HOOD SHIPPING BRACKET
C06020
C06021
BAROMETRIC RELIEF DAMPER
GEAR DRIVEN DAMPER
C06022
Fig. 28 --- EconoMi$er2 Component Locations
Optional Economi$er IV and
Economi$er2
See Fig. 27 for EconoMi$er IV component locations. See Fig. 28 for EconoMi$e r2 component locati ons.
34
Page 35
NOTE: These instructions are for installing the optional EconoMi$er IV and EconoMi$er2 only. Refer to the accessory EconoMi$er IV or EconoMi$er2 installation instructions when field installing an EconoMi$er IV or EconoMi$er2 accessory.
1. To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. (See Fig. 29.)
2. The box with the economizer hood components is shipped in the compartment behind the economizer. The EconoMi$er IV controller is mounted on top of the EconoMi$er IV in the position shown in Fig. 24. The optional EconoMi$er2 with 4 to 20 mA actuator signal control does not include the EconoMi$er IV controller. To remove the component box from its shipping position, remove the screw holding the hood box bracket to the top of the economizer. Slide the hood box out of the unit. (See Fig. 30.)
IMPORTANT: If the power exhaust accessory is to be installed on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust hood assembly.
3. The indoor coil access panel will be used as the top of the hood. Remove the screws along the sides and bottom of the indoor coil access panel. (See Fig. 31.)
4. Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use screws provided to attach the hood sides to the unit. (See Fig. 32.)
5. Remove the shipping tape holding the economizer barometric relief damper in place.
6. Insert the hood divider between the hood sides. (See Fig. 32 and 33.) Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter.
7. Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bottom filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filter into place. (See Fig. 33.)
8. Caulk the ends of the joint between the unit top panel and the hood top. (See Fig. 31.)
9. Replace the filter access panel.
10. Install all EconoMi$er IV accessories. EconoMi$er IV wiring is shown in Fig. 34. EconoMi$er2 wiring is shown in Fig. 35.
Barometric flow capacity is shown in Fig. 36. Outdoor air leakage is shown in Fig. 37. Return air pressure drop is shown in Fig. 38.
FILTER ACCESS PANEL
x
o
B
d
o
o
H
Fig. 30 --- Hood Box Removal
SIDE PANEL
CAULK
INDOOR COIL ACCESS PANEL
HERE
Fig. 31 --- Indoor Coil Access Panel Relocation
INDOOR COIL ACCESS PANEL
LEFT HOOD SIDE
B
19 1/16”
SCREW
33 3/8”
HOOD BOX BRACKET
TOP SIDE PANEL
INDOOR COIL ACCESS PANEL
TOP PANEL
C06024
50HE,HJ
C06025
COMPRESSOR ACCESS PANEL
OUTDOOR-AIR OPENING AND INDOOR COIL ACCESS PANEL
Fig. 29 --- Typical Access Panel Locations
C06023
HOOD DIVIDER
Fig. 32 --- Outdoor-- Air Hood Construction
Economi$er IV Standard
Sensors
Outdoor Air T emperature (OAT) Sensor
The outdoor air temperature sensor (HH57AC074) is a 10 to 20 mA device used to measure the outdoor-air tempera t ure. The outdoor-air tempe rature is used to dete rmine when the EconoMi $er IV can be used for free cooling. The sens or is fact or y-installed on the EconoMi$e r IV in the outdoor airst ream. (See Fig. 27.) The operating range of temperature measurement is 40_ to 100_F.
35
C06026
Page 36
Supply Air Temperature (SAT) Sensor
R
The supply air temperature sensor is a 3 K thermistor located at the inlet of the indoor fan. (See Fig. 39.) This sensor is factory installed. The operating range of temperature measurement is 0 to 158_F. See Table 6 for sensor temperature/resistance values.
Table 6—Supply Air Sensor Temperature/
Resistance Values
Economi$er IV Control
IMPORTANT: The optional EconoMi $er2 does not include a
controller. The EconoMi$er2 is operated by a 4 to 20 mA from an existing field-supplied controller (such as PremierLink control ). See Fig. 35 for wiring informa tion.
Determine the EconoMi$er IV control mode before set up of the control. Some modes of operation may require different sensors. Refer to Table 7. The EconoMi$er IV is supplied from
Modes
signal
the factory with a supply-- air temperature sensor and an outdoor--
TEMPERATURE (F) RESISTANCE (ohms)
–58 –40 –22
–4 14 32 50 68 77 86
50HE,HJ
104 122 140 158 176 185 194 212 230 248 257 266 284 302
17 1/4”
200,250 100,680
53,010 29,091 16,590
9,795 5,970 3,747 3,000 2,416 1,597 1,080
746 525 376 321 274 203 153 116 102
89 70 55
air temperature sensor. This allows for operation of the EconoMi$er IV with outdoor air dry bulb changeover control. Additional accessories can be added to allow for different types of changeover control and operation of the EconoMi$er IV and unit.
Table7—Economi$erIVSensorUsage
APPLICATION
Outdoor Air
Dry Bulb
Differential
Dry Bulb
Single Enthalpy HH57AC078
Differential
Enthalpy
CO2for DCV
Control using a
Wall-Mounted
Sensor
CO
2
CO2for DCV
Control using a
Duct-Mounted
Sensor
CO
2
*CRENTDIF004A00 a nd CRTEMPSN002A00 accessories are used on many
different base units. As such, these kits may contain parts that will not be
needed for installation. † 33ZCSENCO2 is an accessory CO ** 33ZCASPCO2 is an accessory aspirator box required for duct-mounted
applications. †† CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2
and 33ZCASPCO2 accessories.
ECONOMI$ER IV WITH OUTDOOR AIR
33ZCSENCO2†
33ZCASPCO2**
DRY BULB SENSOR
Accessories Required
None. The outdoor air dry bulb sensor
is factory installed.
CRTEMPSN002A00*
HH57AC078
and
CRENTDIF004A00*
33ZCSENCO2
O
and
sensor.
2
CRCBDIOX005A00††
R
Outdoor Dry Bulb Changeover
The standard controller is shipped from the factory configured for
DIVIDER
OUTSIDE AIR
HOOD
CLEANABLE
BAROMETRIC RELIEF
ALUMINUM FILTER
FILTER
FILTE CLIP
C06027
Fig. 33 --- Filter Installation
The temperature sensor looks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
Outdoor Air Lockout Sensor
The Economi$er IV is equipped with an ambient temperature lockout switch located in the outdoor air stream which is used to lockout the compressors below a 42_F ambient temperature. (See Fig. 27.)
outdoor dry bulb changeover control. The outdoor--air and supply-- air temperature sensors are included as standard. For this control mode, the outdoor temperature is compared to an adjustable set point selected on the control. If the outdoor-air temperature is above the set point, the EconoMi$er IV will adjust the outdoor-air dampers to minimum position. If the outdoor air temperature is below the set point, the position of the outdoor air dampers will be controlled to provide free cooling using outdoor air. When in this mode, the LED next to the free cooling set point potentiometer will be on. The changeover temperature set point is controlled by the free cooling set point potentiometer located on the control. (See Fig. 40.) The scale on the potentiometer is A, B, C, and D. See Fig. 41 for the corresponding temperature changeover values.
Differential Dry Bulb Control
For differential dry bulb control the standard outdoor dry bulb sensor is used in conjunction with an additional accessory dry bulb sensor (part number CRTEMPSN002A00). The accessory sensor must be mounted in the return airstream. (See Fig. 42.) Wiring is provided in the EconoMi$er IV wiring harness. (See Fig. 33.)
In this mode of operation, the outdoor-air temperature is compared to the return-air temperature and the lower temperature airstream is used for cooling. When using this mode of changeover control, turn the enthalpy setpoint potentiometer fully clockwise to the D setting. (See Fig. 40.)
36
Page 37
DCV— Demand Controlled Ventilation
p
IAQ — Indoor Air Quality LA — Low Ambient Lockout Device OAT — Outdoor-Air Temperature POT— Potentiometer RAT— Return-Air Temperature
LEGEND
FOR OCCUPANCY CONTROL REPLACE JUMPER WITH FIELD-SUPPLIED TIME CLOCK
Potentiometer Defaults Settings: Power Exhaust Middle Minimum Pos. Fully Closed DCV Max. Middle DCV Set Middle Enthalpy C Setting
Fig. 34 --- EconoMi$er IV Wiring
NOTES:
1. 620 ohm, 1 watt 5% resistor should be removed only when using differential enthalpy or dry bulb.
2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power supply, it cannot have the secondary of the transformer grounded.
3. For field-installed remote minimum position POT, remove black wire jumper between P and P1 and set control minimum position POT to the minimum
osition.
50HE,HJ
C06028
BLACK
4
3
5
BLUE
500 OHM RESISTOR
VIOLET
NOTE 1
PINK
RUN
OUTPUT
-
+
2
YELLOW
WHITE
NOTE 3
50HJ540573
ACTUATOR ASSEMBLY
DIRECT DRIVE
ACTUATOR
NOTES:
1. Switch on actuator must be in run position for economizer to operate.
2. PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sensor or HH57A077 enthalpy sensor.
3. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.
OPTIONAL CO
SENSOR4-20mA
2
8
6
7
RED
1
10
11
9
12
ECONOMISER2 PLUG
Fig. 35 --- EconoMi$er2 with 4 to 20 mA Control Wiring
C06029
Outdoor Enthalpy Changeover
For enthalpy control, accessory enthalpy sensor (part number HH57AC078) is required. Replace the standard outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. (See Fig. 27.) When the outdoor air enthalpy rises above the outdoor enthalpy changeover set point, the outdoor-air damper moves to its minimum position. The outdoor
enthalpy changeover set point is set with the outdoor enthalpy set point potentiometer on the EconoMi$er IV controller. The set points are A, B, C, and D. (See Fig. 43.) The factory-installed 620-ohm jumper must be in place across terminals SR and SR+ on the EconoMi$er IV controller. (See Fig. 27 and 44.)
37
Page 38
Differential Enthalphy Control
For differential enthalpy control, the EconoMi$er IV controller uses two enthalpy sensors (HH57AC078 and CRENTDIF004A00), one in the outside air and one in the return air duct. The EconoMi$er IV controller compares the outdoor air enthalpy to the return air enthalpy to determine EconoMi$er IV use. The controller selects the lower enthalpy air (return or outdoor) for cooling. For example, when the outdoor air has a lower enthalpy than the return air, the EconoMi$er IV opens to bring in outdoor air for free cooling.
2500
2000
SUPPLY AIR TEMPERATURE SENSOR MOUNTING LOCATION
SUPPLY AIR TEMPERATURE SENSOR
1500
1000
500
FLOW IN CUBIC FEET PER MINUTE (cfm)
0
0.05
STATIC PRESSURE (in. wg)
0.15
0.25
C06030
50HE,HJ
Fig. 39 --- Supply Air Sensor Location
C06033
Fig. 36 --- Barometric Flow Capacity
30
25
20
15
10
5
0
0.13 0.20 0. 22 0.25 0.30 0.35 0.40 0.45 0.5 0
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
Fig. 37 --- Outdoor-- Air Damper Leakage
C06031
Fig. 40 --- EconoMi$er IV Controller Potentiometer
and LED Locations
Replace the standard outside air d ry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. (See Fig. 27.) Mount the return air enthalpy sensor in the return air duct. (See Fig. 42.) Wiring is provided in the EconoMi$er IV
C06034
wiring harness. (See Fig. 34.) The outdoor enthalpy changeover
6000
5000
4000
3000
2000
1000
0
0.05 0.10 0.15 0. 20 0.25 0.30 0. 35
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
Fig. 38 --- Return--Air Pressure Drop
C06032
set point is set with the outdoor enthalpy set point potentiometer on the EconoMi$er IV controller. When using this mode of changeover control, turn the enthalpy setpoint potentiometer fully clockwise to the D setting.
Indoor Air Quality (IAQ) Sensor Input
The IAQ input can be used for demand control ventilation control based on the level of CO
measured in the space or return air
2
duct. Mount the accessory IAQ sensor according to manufacturer
specifications. The IAQ sensor should be wired to the AQ and AQ1 terminals of the controller. Adjust the DCV potentiometers to correspond to the DCV voltage output of the indoor air quality sensor at the user-determined set point. (See Fig. 45.)
If a separate field-supplied transformer is used to power the IAQ sensor, the sensor must not be grounded or the EconoMi$er IV control board will be damaged.
Exhaust Set Point Adjustment
The exhaust set point will determine when the exhaust fan runs based on damper position (if accessory power exhaust is installed). The set point is modified with the Exhaust Fan Set Point (EXH SET) potentiometer. (See Fig. 40.) The set point represents the damper position above which the exhaust fans will be turned on. When there is a call for exhaust, the EconoMi$er IV controller provides a 45 15 second delay before exhaust fan
38
Page 39
activation to allow the dampers to open. This delay allows the damper to reach the appropriate position to avoid unnecessary fan overload.
Minimum Position Control
There is a minimum damper position potentiometer on the EconoMi$er IV controller. (See Fig. 40.) The minimum damper position maintains the minimum airflow into the building during the occupied period.
When using demand ventilation, the minimum damper position represents the minimum ventilation position for VOC (volatile organic compound) ventilation requirements. The maximum demand ventilation position is used for fully occupied ventilation.
When demand ventilation control is not being used, the minimum position potentiometer should be used to set the occupied ventilation position. The maximum demand ventilation position should be turned fully clockwise.
Adjust the minimum position potentiometer to allow the minimum amount of outdoor air, as required by local codes, to enter the building. Make minimum position adjustments with at least 10_F temperature difference between the outdoor and return-air temperatures.
To determine the minimum position setting, perform the following procedure:
1. Calculate the appropriate mixed air temperature using the following formula:
OA
(T
Ox
100 100
+(TR
)
RA
x
)=T
M
Thermostats
The EconoMi$er IV control works with conventional thermostats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage
1), W2 (heat stage 2), and G (fan). The EconoMi$er IV control does not support space temperature sensors. Connections are made at the thermostat terminal connection board located in the main control box.
19
LED ON
mA
14
18
17
16
15
13
12
11
10
9
40
LED OFF
45
D
50
60
55
DEGREES FAHRENHEIT
LED ON
C
LED OFF
65
70
LED ON
LED OFF
75
B
LED ON
A
LED OFF
100
90
95
85
80
C06035
Fig. 41 --- Outside Air Temperature
Changeover Set Points
ECONOMI$ER IV CONTROLLER
ECONOMI$ER IV
50HE,HJ
TO= Outdoor-Air Temperature OA = Percent of Outdoor Air
= Return-Air Tem perature
T
R
RA = Percent of Return Air
= Mixed-Air Temperature
T
M
As an example, if local codes require 10% outdoor air during occupied conditions, outdoor-air temperature is 60_F, a n d return-air temperature is 75_F.
(60 x .10) + (75 x .90) = 73.5_F
2. Disconnect the supply air sensor from terminals T and T1.
3. Ensure that the factory-installed jumper is in place across terminals P and P1. If remote damper positioning is being used, make sure that the terminals are wired according to Fig. 34 and that the minimum position potentiometer is turned fully clockwise.
4. Connect 24 vac across terminals TR and TR1.
5. Carefully adjust the minimum position potentiometer until the measured supply air temperature matches the calculated value.
6. Reconnect the mixed air sensor to terminals T and T1.
Remote control of the EconoMi$er IV damper is desirable when requiring additional temporary ventilation. If a field-supplied remote potentiometer (Honeywell part number S963B1128) is wired to the EconoMi$er IV controller, the minimum position of the damper can be controlled from a remote location.
To control the minimum damper position remotely, remove the factory-installed jumper on the P and P1 terminals on the EconoMi$er IV controller. Wire the field-supplied potentiometer to the P and P1 terminals on the EconoMi$er IV controller. (See Fig. 44.)
Damper Mo vement
Damper movement from full open to full closed (or vice versa)
1
/2minutes.
takes 2
GROMMET
RETURN AIR SENSOR
RETURN DUCT (FIELD-PROVIDED)
C06036
Fig. 42 --- Return Air T emperature or Enthalpy
Sensor Mounting Location
Occupancy Control
The factory default configuration for the EconoMi$er IV control is occupied mode. Occupied mode is provided by the black jumper from terminal TR to terminal N. When unoccupied mode is desired, install a field-supplied timeclock function in place of the jumper between TR and N. (See Fig. 34.) When the timeclock contacts are closed, the EconoMi$er IV control will be in occupied mode. When the timeclock contacts are open (removing the 24-v signal from terminal N), the EconoMi$er IV will be in unoccupied mode.
39
Page 40
85
(29)90(32)95(35)
46
65
(18)
4
4
42
40
70
(21)
0
0
1
80
(27)
75
(24)
0
9
80
70
0
6
50
0
4
CONTROL
50HE,HJ
2
1
CURVE
A B C D
1
4
1
CONTROL POINT
APPROX.
2
8
1
6
deg. F (deg. C)
AT 50% RH
73 (23) 70 (21) 67 (19) 63 (17)
4
3
32
30
28
ENTHALPY BTU PER POUND DRY AIR
26
4
2
2
2
0
55
(13)
50
C
(10)
45
D
(7) 40 (4)
35
(2)
3
(16)
B
8
3
6
60
A
100
105
(38)
RELATIVE HUMIDITY (%)
30
20
110
(41)
(43)
0
1
35
40
45
50
55
60
(2)
(4)
(10)
(7)
APPROXIMATE DRY BULB TEMPERATURE--degrees F (degrees C)
(13)
(16)
(18)
65
Fig. 43 --- Enthalpy Changeover Set Points
Demand Controlled Ventilation (DCV)
When using the EconoMi$er IV for demand controlled ventilation, there are some equipment selection criteria which should be considered. When selecting the heat capacity and cool capacity of the equipment, the maximum ventilation rate must be evaluated for design conditions. The maximum damper position must be calculated to provide the desired fresh air.
Typically the maximum ventilation rate will be about 5 to 10% more than the typical cfm required per person, using normal outside air design criteria.
A proportional anticipatory strategy should be taken with the following conditions: a zone with a large area, varied occupancy, and equipment that cannot exceed the required ventilation rate at design conditions. Exceeding the required ventilation rate means the equipment can condition air at a maximum ventilation rate that is greater than the required ventilation rate for maximum occupancy. A proportional-anticipatory strategy will cause the fresh air supplied to increase as the room CO even though the CO the CO
level reaches the set point, the damper will be at
2
set point has not been reached. By the time
2
level increases
2
maximum ventilation and should maintain the set point. In order to have the CO
sensor control the economizer damper in
2
this manner, first determine the damper voltage output for minimum or base ventilation. Base ventilation is the ventilation required to remove contaminants during unoccupied periods. The following equation may be used to determine the percent of outside-air entering the building for a given damper position. For best results there should be at least a 10 degree difference in outside and return-air temperatures.
(21)
A
B
C
D
105
70
75
80
(24)
(27)
85
(29)90(32)95(35)
OA
(T
Ox
100 100
+(TR
)
100 (38)
(41)
110
(43)
RA
x
)=T
HIGH LIMIT CURVE
M
C06037
TO= Outdoor-Air Temperature OA = Percent of Outdoor Air
= Return-Air Tem perature
T
R
RA = Percent of Return Air
= Mixed-Air Temperature
T
M
Once base ventilation has been determined, set the minimum damper position potentiometer to the correct position.
The same equation can be used to determine the occupied or maximum ventilation rate to the building. For example, an output of 3.6 volts to the actuator provides a base ventilation rate of 5% and an output of 6.7 volts provides the maximum ventilation rate of 20% (or base plus 15 cfm per person). Use Fig. 42 to determine the maximum setting of the CO
sensor. For example,
2
a 1100 ppm set point relates to a 15 cfm per person design. Use the 1100 ppm curve on Fig. 45 to find the point when the CO
2
sensor output will be 6.7 volts. Line up the point on the graph with the left side of the chart to determine that the range configuration for the CO EconoMi$er IV controller will output the 6.7 volts from the CO
sensor should be 1800 ppm. The
2
2
sensor to the actuator when the CO2concentration in the space is at 1100 ppm. The DCV set point may be left at 2 volts since the
sensor voltage will be ignored by the EconoMi$er IV
CO
2
controller until it rises above the 3.6 volt setting of the minimum position potentiometer.
Once the fully occupied damper position has been determined, set the maximum damper demand control ventilation potentiometer to this position. Do not set to the maximum position as this can result in over-ventilation to the space and potential high-humidity levels.
40
Page 41
N1
P1
T1
AQ1
SO+
SR+
EXH
2V 10V
EXH
Open
2V 10V
DCV
2V 10V
Free Cool
B
A
DCV
DCV
C
D
Set
Min Pos
Max
Set
N
P
T
AQ
SO
SR
TR1
TR
24
24 Vac
Vac
COM
HOT
_
+
12
3
EF1
EF
5
4
C06038
Fig. 44 --- EconoMi$er IV Control
CO SENSOR MAX RANGE SETTING
6000
5000
4000
3000
2000
1000
RANGE CONFIGURATION (ppm)
0
2
800 ppm 900 ppm 1000 ppm 1100 ppm
2345678
DAMPER VOLTAGE FOR MAX VENTILATION RATE
C06039
Fig. 45 --- CO2Sensor Maximum Range Setting
Sensor Configuration
CO
2
The CO
sensor has preset standard voltage settings that can be
2
selected anytime after the sensor is powered up. (See Table 8.) Use setting 1 or 2 for Carrier equipment. (See Table 8.)
1. Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number. (See Tab l e 8 . )
4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.
The custom settings of the CO
sensor can be changed anytime
2
after the sensor is energized. Follow the steps below to change the non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD menu and press Enter.
4. Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached.
5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode to continue to the next variable.
Dehumidification of Fresh Air with DCV Control
Information from ASHRAE indicates that the largest humidity load on any zone is the fresh air introduced. For some applications, a device such as a 62AQ energy recovery unit is added to reduce the moisture content of the fresh air being brought into the building when the enthalpy is high. In most cases, the normal heating and cooling processes are more than adequate to remove the humidity loads for most commercial applications.
If normal rooftop heating and cooling operation is not adequate for the outdoor humidity level, an energy recovery unit and/or a dehumidification option should be considered.
Step 7 Adjust Evaporator--Fan Speed
Adjust evaporator-fan speed to meet jobsite conditions. Tables 9 and 10 show fan rpm at motor pulley settings for the
50HE003--006 and 50HJ004-- 007 units. Tables 11 and 14 show maximum amp draw of belt-drive motor. Table 13 shows sound data. Refer to Tables 15-34 for performance data. See Table 35 for accessory static pressure drop. See Fig. 47 for the Humidi-MiZer system static pressure drops.
For units with electric heating, required minimum cfm is 900 for 50HJ004; 1200 for 50HJ005; 1500 for 50HJ006 and 1800 for 50HJ007.
Belt Drive
Motors
Fan motor pulleys are factory set for speed shown in Table 1. Check pulley alignment and belt tension prior to start-up.
To change fan speed:
1. Shut off the unit power supply and tag disconnect.
2. Loosen the belt by loosening the fan motor mounting nuts. (See Fig. 47.)
3. Loosen movable pulley flange setscrew (See Fig. 48).
4. Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. Increasing fan speed increases load on motor. Do not exceed maximum speed specified in Table 1.
5. Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See T able 1 for speed change for each full turn of pulley flange.)
6. Adjust belt tension and align fan and motor pulleys per guidance below.
NOTE: Once the required flange position is determined for the correct blower rpm, it is recommended (but not required) that the variable pitch pulley be replaced with a corresponding size fixed sheave pulley.
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from mount­ing.
To adjust belt tension:
1. Loosen fan motor mounting nuts.
2. Slide motor mounting plate away from fan scroll for proper belt tension (
1
/2-in.deflectionwith7to10lbof
force).
3. Tighten motor mounting nuts.
4. Adjust bolt and tighten nut to secure motor in fixed position.
50HE,HJ
41
Page 42
Table 8—CO
Sensor Standard Settings
2
SETTING EQUIPMENT OUTPUT
1
Interface w/Standard
2
Building Control System
3
4
5
Economizer
6
7
Health & Safety Proportional
8
Parkin g/ Air In ta kes/
9
Loading Docks
50HE,HJ
LEGEND ppm — Parts Per Million
0.35
0.3
0.25
VENTILATION
RATE
(cfm/Person)
Proportional Any
Proportional Any
Exponential Any
Proportional 15
Proportional 20
Exponential 15
Exponential 20
Proportional
ANALOG OUTPUT
0-10V
4-20 mA
2-10V
7-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
CO
CONTROL RANGE
2
(ppm)
0-2000 1000 50
0-2000 1000 50
0-2000 1100 50
0-1100 1100 50
0- 900 900 50
0-1100 1100 50
0- 900 900 50
0-9999 5000 500
0-2000 700 50
OPTIONAL
RELAY SETPOINT
(ppm)
RELAY
HYSTERESIS
(ppm)
DELTA P IN. WG
0.2
0.15
0.1
0.05
4&5ton
6 ton
3 ton
0
0
1000
2000
3000
4000
5000
6000
C06133
Fig. 46 --- Humidi--MiZert Adaptive Dehumidification System Static Pressure Drop (in. wg)
Fig. 47 --- Belt Drive Motor Mounting
C06134
C06041
Fig. 48 --- Evaporator--Fan Pulley Adjustment
42
Page 43
Table 9—50HJ and 50he Fan Rpm at Motor Pulley Setting With Standard Motor*
UNIT 50HJ 50HE
003 004 005 006 007
*Approximate fan rpm shown (standard motor/drive).
0
936 906 876 846 816 786 756 726 696 666 639 — 1044 1008 971 935 898 862 826 789 753 716 680 — 1185 1144 1102 1061 1019 978 936 895 853 812 770 — 1460 1425 1389 1354 1318 1283 1248 1212 1177 1141 1106 1070 1035 1585 1538 1492 1445 1399 1352 1305 1259 1212 1166 1119
1
/
2
Table 10—50HJ, 50HE Fan Rpm at Motor Pulley Setting With High-Static Motor*
UNIT
004 005 006 007
*Approximate fan rpm shown (h igh-static motor/drive).
0
1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075 1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075 1685 1589 1557 1525 1493 1460 1428 1396 1364 1332 1300 — 1685 1589 1557 1525 1493 1460 1428 1396 1364 1332 1300
1
/
2
1 11/
Table 11—Evaporator-Fan Motor Data — Standard Motor
UNIT 50HJ 50HE
003
004
005
006
007
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
ALL 0.58 580 2.0 75.0
Single 1.20 1000 208/230 4.9
Three 1.20 1000
Single 1.20 1000 208/230 4.9
Three 1.20 1000
Single 1.30 1650 208/230 9.2
Three 2.40 2120
Three 2.40 2120
1 11/
2
2 21/
MOTOR PULLEY TURNS OPEN
2
2 21/
2
3 31/
MOTOR PULLEY TURNS OPEN
2
3 31/
MAXIMUM
OPERATING WATTS*
4 41/
2
2
4 41/
2
2
5 51/
5 51/
2
6
2
6
50HE,HJ
UNIT VOLTAGE
208/230 4.9
460 2.2 575 2.2
208/230 4.9
460 2.2 575 2.2
208/230 6.7
460 3.0 575 3.0
208/230 6.7
460 3.0 575 3.0
MAXIMUM
AMP DRAW
LEGEND Bhp — Brake Horsepower *Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using the
fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
Table 12—Evaporator-Fan Motor Data — High-Static Motors
UNIT 50HJ 50HE
004
005
006
007
LEGEND Bhp — Brake Horsepower *Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using the
fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
Three 2.40 2120
Three 2.40 2120
Three 2.90 2615
Three 2.90 2615
UNIT VOLTAGE
208/230 6.7
460 3.0 575 3.0
208/230 6.7
460 3.0 575 3.0
208/230 8.6
460 3.9 575 3.9
208/230 8.6
460 3.9 575 3.9
MAXIMUM
AMP DRAW
43
Page 44
Table 13—Accessory/FIOP Electric Heaters Static Pressure Drop (in. wg) — 50HJ004-007 and 50HE003--006
COMPONENT
1HeaterModule 0.03 0.05
2 Heater Modules 0.14 0.15
600 900 1200 1400 1600 1800 2000 2200 2400 2600
0.07 0.09 0.09 0.10 0.11 0.11 0.12 0.13
0.16 0.16 0.16 0.17 0.17 0.17 0.18 0.18
CFM
Table 14—Accessory/FIOP EconoMi$er IV and EconoMi$er2 Static Pressure* (in. wg) — 50HJ004-007 and 50HE003 --006
COMPONENT
Vertical EconoMi$er IV and EconoMi$er2 0.01 0.02 0.035 Horizontal EconoMi$er IV and EconoMi$er2 --- --- ---
LEGEND FIOP --- F a c t o r y --- I n s t a l l e d O p t i o n *The static pressure must be added to external static pressure. The sum and the indoor entering-air cfm should be used in conjunction with the Fan Performance
tables to determine indoor blower rpm and watts.
600 800 1000
1250 1500 1750 2000 2250 2500 2750 3000
0.045 0.065 0.08 0.12 0.145 0.175 0.22 0.255 — 0.1 0.125 0.15 0.18 0.225 0.275
CFM
Table 14 — Evaporator-Fan Motor Efficiency
50HE,HJ
*Single-phase/3-phase. NOTE: Convert watts to bhp using the following formula:
bhp =
MOTOR 50HJ EFFICIENCY
003,004,005
006 007
watts input x motor efficiency
746
75
74/84*
84
GENERAL FAN PERFORMANCE NOTES
1. Values include losses for filters, unit casing, and wet coils. See Table 13 and 14 and Fig. 46 for accessory/FIOP static pressure information.
2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Table 11 and 12 on this page for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify.
4. Interpolation is permissible. Do not extrapolate.
5. Performance includes clean filter and wet coil.
Table 15—Fan Performance 50HE003 — Vertical Discharge Units; Standard Motor (Belt Drive)**
AIRFLOW
(Cfm)
600 700 800 900
1000
0.1 0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
500 0.08 531 0.08 607 0.14 713 0.21 788 0.29 529 0.09 567 0.09 633 0.16 739 0.24 816 0.32 547 0.1 592 0.12 660 0.19 761 0.27 845 0.37 570 0.13 620 0.14 691 0.22 793 0.32 870 0.42 599 0.15 650 0.16 717 0.26 818 0.36 894 0.47
EXTERNAL STATIC PRESSURE (in. wg)
Rpm Bhp
902 0.41 937 0.47 957 0.53 981 0.58
878 0.37
44
Page 45
Table 16—Fan Performance 50HJ004, 50HE004 — Vertical Discharge Units; Standard Motor
(Belt Drive)*
AIRFLOW
CFM
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg
900 566 0.14 142 690 0.23 228 791 0.32 320 879 0.42 418 957 0.52 522 1000 598 0.17 173 718 0.27 267 817 0.37 366 903 0.47 471 981 0.58 581 1100 632 0.21 210 748 0.31 311 844 0.42 418 929 0.53 530 1006 0.65 646 1200 666 0.25 252 778 0.36 361 873 0.48 476 956 0.60 594 1031 0.72 718 1300 701 0.30 300 809 0.42 418 902 0.54 540 983 0.67 665 1057 0.80 796 1400 737 0.36 355 842 0.48 481 932 0.61 610 1012 0.75 744 1085 0.89 881 1500 774 0.42 417 875 0.55 551 962 0.69 689 1041 0.83 830 1112 0.98 974
AIRFLOW
CFM
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
900 1029 0.63 630 1095 0.75 742 1157 0.86 859 1216 0.99 980 1272 1.11 1105 1000 1052 0.70 695 1118 0.82 814 1179 0.94 937 1237 1.07 1064 1293 1.20 1195 1100 1076 0.77 767 1141 0.90 892 1202 1.03 1021 1260 1.16 1154 1200 1100 0.85 845 1165 0.98 977 1225 1.12 1112 1300 1126 0.94 930 1189 1.07 1069 1400 1152 1.03 1023 1215 1.17 1168 1500 1179 1.13 1123
NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See general fan performance notes.
LEGEND
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 680 to 1044 rpm. All other rpms require field-supplied
drive.
Table 17—Fan Performance 50HJ004, 50he004 — Vertical Discharge Units; High-Static Motor
(Belt Drive)*
50HE,HJ
AIRFLOW
CFM
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
900 566 0.14 142 690 0.23 228 791 0.32 320 879 0.42 418 957 0.52 522 1000 598 0.17 173 718 0.27 267 817 0.37 366 903 0.47 471 981 0.58 581 1100 632 0.21 210 748 0.31 311 844 0.42 418 929 0.53 530 1006 0.65 646 1200 666 0.25 252 778 0.36 361 873 0.48 476 956 0.60 594 1031 0.72 718 1300 701 0.30 300 809 0.42 418 902 0.54 540 983 0.67 665 1057 0.80 796 1400 737 0.36 355 842 0.48 481 932 0.61 610 1012 0.75 744 1085 0.89 881 1500 774 0.42 417 875 0.55 551 962 0.69 689 1041 0.83 830 1112 0.98 974
AIRFLOW
CFM
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
900 1029 0.63 630 1095 0.75 742 1157 0.86 859 1216 0.99 980 1272 1.11 1105 1000 1052 0.70 695 1118 0.82 814 1179 0.94 937 1237 1.07 1064 1293 1.20 1195 1100 1076 0.77 767 1141 0.90 892 1202 1.03 1021 1260 1.16 1154 1314 1.30 1291 1200 1100 0.85 845 1165 0.98 977 1225 1.12 1112 1282 1.26 1252 1337 1.40 1395 1300 1126 0.94 930 1189 1.07 1069 1249 1.22 1211 1306 1.36 1356 1360 1.51 1506 1400 1152 1.03 1023 1215 1.17 1168 1274 1.32 1317 1330 1.48 1469 1384 1.63 1625 1500 1179 1.13 1123 1241 1.28 1275 1300 1.44 1431 1355 1.60 1590 1408 1.76 1752
NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See general fan performance notes.
LEGEND
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 680 to 1044 rpm. All other rpms require field-supplied
drive.
45
Page 46
Table 18—Fan Performance 50HJ005, 50HE005 — Vertical Discharge Units; Standard Motor
(Belt Drive)*
AIRFLOW
CFM
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
1200 666 0.25 252 778 0.36 361 873 0.48 476 956 0.60 594 1031 0.72 718 1300 701 0.30 300 809 0.42 418 902 0.54 540 983 0.67 665 1057 0.80 796 1400 737 0.36 355 842 0.48 481 932 0.61 610 1012 0.75 744 1085 0.89 881 1500 774 0.42 417 875 0.55 551 962 0.69 689 1041 0.83 830 1112 0.98 974 1600 811 0.49 487 909 0.63 629 994 0.78 774 1071 0.93 923 1141 1.08 1076 1700 849 0.57 565 943 0.72 715 1026 0.87 869 1101 1.03 1025 1170 1.19 1185 1800 887 0.65 651 978 0.81 810 1059 0.98 972 1133 1.14 1136 1900 926 0.75 746 1014 0.92 914 1092 1.09 1084 2000 965 0.86 852 1050 1.03 1028
AIRFLOW
CFM
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
1200 1100 0.85 845 1165 0.98 977 1225 1.12 1112
50HE,HJ
1300 1126 0.94 930 1189 1.07 1069 1400 1152 1.03 1023 1215 1.17 1168 1500 1179 1.13 1123 1600 1700 1800 1900 2000
NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See general fan performance notes.
LEGEND
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 770 to 1185 rpm. All other rpms require field-supplied
drive.
Table 19—Fan Performance 50HJ005, 50HE005 — Vertical Discharge Units; High-Static Motor
(Belt Drive)*
AIRFLOW
CFM
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
1200 666 0.25 252 778 0.36 361 873 0.48 476 956 0.60 594 1031 0.72 718 1300 701 0.30 300 809 0.42 418 902 0.54 540 983 0.67 665 1057 0.80 796 1400 737 0.36 355 842 0.48 481 932 0.61 610 1012 0.75 744 1085 0.89 881 1500 774 0.42 417 875 0.55 551 962 0.69 689 1041 0.83 830 1112 0.98 974 1600 811 0.49 487 909 0.63 629 994 0.78 774 1071 0.93 923 1141 1.08 1076 1700 849 0.57 565 943 0.72 715 1026 0.87 869 1101 1.03 1025 1170 1.19 1185 1800 887 0.65 651 978 0.81 810 1059 0.98 972 1133 1.14 1136 1200 1.31 1304 1900 926 0.75 746 1014 0.92 914 1092 1.09 1084 1164 1.26 1257 1231 1.44 1432 2000 965 0.86 852 1050 1.03 1028 1127 1.21 1206 1197 1.39 1387 1262 1.58 1570
AIRFLOW
CFM
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1.2 1.4 1.6 1.8 2.0
1200 1100 0.85 845 1165 0.98 977 1225 1.12 1112 1282 1.26 1252 1337 1.40 1395 1300 1126 0.94 930 1189 1.07 1069 1249 1.22 1211 1306 1.36 1356 1360 1.51 1506 1400 1152 1.03 1023 1215 1.17 1168 1274 1.32 1317 1330 1.48 1469 1384 1.63 1625 1500 1179 1.13 1123 1241 1.28 1275 1300 1.44 1431 1355 1.60 1590 1408 1.76 1752 1600 1206 1.24 1231 1268 1.40 1391 1326 1.56 1553 1381 1.73 1719 1433 1.90 1888 1700 1235 1.36 1349 1295 1.52 1515 1352 1.69 1685 1407 1.87 1858 1459 2.04 2034 1800 1264 1.48 1475 1323 1.66 1649 1380 1.84 1826 1434 2.02 2006 1485 2.20 2189 1900 1293 1.62 1611 1352 1.80 1792 1408 1.99 1976 1461 2.17 2163 1512 2.37 2353 2000 1324 1.77 1756 1381 1.96 1945 1436 2.15 2137 1489 2.34 2332
NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See general fan performance notes.
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
LEGEND
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require field-supplied
drive.
46
Page 47
Table 20—Fan Performance 50HJ006, 50HE006 Single-Phase — Vertical Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
CFM
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
1500 790 0.40 353 897 0.53 471 991 0.68 600 1075 0.83 739 1152 1.00 888 1600 828 0.46 412 931 0.60 536 1022 0.75 670 1104 0.92 813 1180 1.09 966 1700 866 0.54 478 966 0.68 608 1054 0.84 747 1134 1.01 895 1208 1.19 1053 1800 905 0.62 551 1001 0.77 687 1087 0.94 832 1165 1.11 985 1238 1.29 1148 1900 944 0.71 633 1037 0.87 774 1120 1.04 925 1197 1.22 1084 2000 983 0.81 723 1073 0.98 870 1154 1.16 1026 2100 1023 0.92 821 1110 1.10 975 1189 1.28 1137 2200 1063 1.05 929 1147 1.23 1089 2300 1104 1.18 1046 2400 2500
AIRFLOW
CFM
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
1500 1224 1.18 1045 1600 1250 1.27 1128 1700 1800 1900 2000 2100 2200 2300 2400 2500
NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 1.30.
3. See general fan performance notes.
LEGEND
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1035 to 1460 rpm. All other rpms require field-supplied
drive.
50HE,HJ
47
Page 48
Table 21—Fan Performance 50HJ006, 50he006 Three-Phase — Vertical Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
CFM
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
1500 790 0.40 353 897 0.53 471 991 0.68 600 1075 0.83 739 1152 1.00 888 1600 828 0.46 412 931 0.60 536 1022 0.75 670 1104 0.92 813 1180 1.09 966 1700 866 0.54 478 966 0.68 608 1054 0.84 747 1134 1.01 895 1208 1.19 1053 1800 905 0.62 551 1001 0.77 687 1087 0.94 832 1165 1.11 985 1238 1.29 1148 1900 944 0.71 633 1037 0.87 774 1120 1.04 925 1197 1.22 1084 1268 1.41 1251 2000 983 0.81 723 1073 0.98 870 1154 1.16 1026 1229 1.34 1190 1299 1.53 1362 2100 1023 0.92 821 1110 1.10 975 1189 1.28 1137 1262 1.47 1306 1330 1.67 1483 2200 1063 1.05 929 1147 1.23 1089 1224 1.41 1256 1295 1.61 1431 1362 1.82 1614 2300 1104 1.18 1046 1185 1.37 1212 1260 1.56 1386 1329 1.76 1567 1395 1.98 1754 2400 1145 1.32 1174 1223 1.52 1346 1296 1.72 1526 1364 1.93 1712 1428 2.15 1905 2500 1185 1.48 1311 1262 1.68 1490 1333 1.89 1676 1399 2.10 1868 1462 2.33 2067
AIRFLOW
CFM
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
1500 1224 1.18 1045 1291 1.36 1212 1354 1.56 1387 1414 1.77 1570 1472 1.98 1761
50HE,HJ
1600 1250 1.27 1128 1316 1.46 1299 1379 1.66 1478 1438 1.87 1664 1495 2.09 1858 1700 1278 1.37 1219 1343 1.57 1394 1405 1.77 1576 1463 1.99 1766 1520 2.21 1964 1800 1306 1.48 1318 1370 1.69 1497 1431 1.90 1683 1489 2.11 1877 1545 2.34 2078 1900 1335 1.61 1426 1398 1.81 1609 1458 2.03 1799 1515 2.25 1997 2000 1364 1.74 1542 1427 1.95 1730 1486 2.17 1925 1542 2.39 2126 2100 1395 1.88 1668 1456 2.09 1860 1514 2.32 2060 2200 1426 2.03 1804 1486 2.25 2001 2300 1457 2.19 1949 2400 1489 2.37 2106 2500
NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See general fan performance notes.
LEGEND
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1035 to 1460 rpm. All other rpms require field-supplied
drive.
48
Page 49
Table 22—Fan Performance 50HJ006, 50HE006 — Vertical Discharge Units; High-Static Motor
(Belt Drive)*
AIRFLOW
CFM
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
1500 790 0.40 353 897 0.53 471 991 0.68 600 1075 0.83 739 1152 1.00 888 1600 828 0.46 412 931 0.60 536 1022 0.75 670 1104 0.92 813 1180 1.09 966 1700 866 0.54 478 966 0.68 608 1054 0.84 747 1134 1.01 895 1208 1.19 1053 1800 905 0.62 551 1001 0.77 687 1087 0.94 832 1165 1.11 985 1238 1.29 1148 1900 944 0.71 633 1037 0.87 774 1120 1.04 925 1197 1.22 1084 1268 1.41 1251 2000 983 0.81 723 1073 0.98 870 1154 1.16 1026 1229 1.34 1190 1299 1.53 1362 2100 1023 0.92 821 1110 1.10 975 1189 1.28 1137 1262 1.47 1306 1330 1.67 1483 2200 1063 1.05 929 1147 1.23 1089 1224 1.41 1256 1295 1.61 1431 1362 1.82 1614 2300 1104 1.18 1046 1185 1.37 1212 1260 1.56 1386 1329 1.76 1567 1395 1.98 1754 2400 1145 1.32 1174 1223 1.52 1346 1296 1.72 1526 1364 1.93 1712 1428 2.15 1905 2500 1185 1.48 1311 1262 1.68 1490 1333 1.89 1676 1399 2.10 1868 1462 2.33 2067
AIRFLOW
CFM
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
1500 1224 1.18 1045 1291 1.36 1212 1354 1.56 1387 1414 1.77 1570 1472 1.98 1761 1600 1250 1.27 1128 1316 1.46 1299 1379 1.66 1478 1438 1.87 1664 1495 2.09 1858 1700 1278 1.37 1219 1343 1.57 1394 1405 1.77 1576 1463 1.99 1766 1520 2.21 1964 1800 1306 1.48 1318 1370 1.69 1497 1431 1.90 1683 1489 2.11 1877 1545 2.34 2078 1900 1335 1.61 1426 1398 1.81 1609 1458 2.03 1799 1515 2.25 1997 1570 2.48 2202 2000 1364 1.74 1542 1427 1.95 1730 1486 2.17 1925 1542 2.39 2126 1596 2.63 2335 2100 1395 1.88 1668 1456 2.09 1860 1514 2.32 2060 1570 2.55 2265 1623 2.79 2478 2200 1426 2.03 1804 1486 2.25 2001 1543 2.48 2204 1598 2.72 2415 2300 1457 2.19 1949 1516 2.42 2151 1573 2.66 2360 1627 2.90 2574 2400 1489 2.37 2106 1547 2.60 2312 1603 2.84 2526 2500 1522 2.56 2272 1579 2.80 2484
NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See general fan performance notes.
LEGEND
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-supplied
drive.
50HE,HJ
49
Page 50
Table 23—Fan Performance 50HJ007 — Vertical Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
CFM
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
1800 907 0.63 558 1006 0.80 708 1092 0.97 860 1169 1.14 1015 1239 1.32 1174 1900 945 0.72 638 1042 0.90 796 1126 1.08 956 1201 1.26 1119 1271 1.45 1285 2000 984 0.82 727 1078 1.00 892 1160 1.19 1060 1235 1.39 1230 1303 1.58 1403 2100 1024 0.93 823 1115 1.12 997 1195 1.32 1173 1268 1.52 1350 1335 1.72 1531 2200 1063 1.05 929 1152 1.25 1111 1230 1.46 1294 1302 1.67 1480 1368 1.88 1668 2300 1103 1.18 1044 1189 1.39 1234 1266 1.60 1425 1337 1.82 1618 1402 2.04 1814 2400 1143 1.32 1168 1227 1.54 1367 1302 1.76 1566 1371 1.99 1767 1435 2.22 1970 2500 1183 1.47 1303 1265 1.70 1510 1339 1.93 1717 1406 2.17 1926 2600 1224 1.63 1448 1303 1.87 1663 1375 2.12 1878 1442 2.36 2095 2700 1264 1.81 1604 1342 2.06 1828 1412 2.31 2051 2800 1305 1.99 1772 1381 2.26 2003 2900 1346 2.20 1951 3000
AIRFLOW
50HE,HJ
CFM
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
1800 1304 1.51 1337 1365 1.69 1503 1422 1.88 1674 1477 2.08 1848 1528 2.28 2025 1900 1335 1.64 1454 1395 1.83 1627 1452 2.03 1804 1506 2.23 1984 2000 1366 1.78 1580 1426 1.98 1760 1482 2.19 1943 1535 2.40 2130 2100 1398 1.93 1715 1457 2.14 1901 1512 2.35 2091 2200 1430 2.09 1858 1488 2.31 2052 2300 1462 2.27 2012 2400 2500 2600 2700 2800 2900 3000
NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See general fan performance notes.
LEGEND
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1120 to 1585 rpm. All other rpms require field-supplied
drive.
50
Page 51
Table 24—Fan Performance 50HJ007 — Vertical Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
CFM
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
1800 907 0.63 558 1006 0.80 708 1092 0.97 860 1169 1.14 1015 1239 1.32 1174 1900 945 0.72 638 1042 0.90 796 1126 1.08 956 1201 1.26 1119 1271 1.45 1285 2000 984 0.82 727 1078 1.00 892 1160 1.19 1060 1235 1.39 1230 1303 1.58 1403 2100 1024 0.93 823 1115 1.12 997 1195 1.32 1173 1268 1.52 1350 1335 1.72 1531 2200 1063 1.05 929 1152 1.25 1111 1230 1.46 1294 1302 1.67 1480 1368 1.88 1668 2300 1103 1.18 1044 1189 1.39 1234 1266 1.60 1425 1337 1.82 1618 1402 2.04 1814 2400 1143 1.32 1168 1227 1.54 1367 1302 1.76 1566 1371 1.99 1767 1435 2.22 1970 2500 1183 1.47 1303 1265 1.70 1510 1339 1.93 1717 1406 2.17 1926 1470 2.41 2136 2600 1224 1.63 1448 1303 1.87 1663 1375 2.12 1878 1442 2.36 2095 1504 2.60 2313 2700 1264 1.81 1604 1342 2.06 1828 1412 2.31 2051 1478 2.56 2275 1539 2.82 2501 2800 1305 1.99 1772 1381 2.26 2003 1450 2.52 2235 1514 2.78 2467 2900 1346 2.20 1951 1420 2.47 2191 1488 2.74 2431 3000 1387 2.41 2142 1459 2.69 2391
AIRFLOW
CFM
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
1800 1304 1.51 1337 1365 1.69 1503 1422 1.88 1674 1477 2.08 1848 1528 2.28 2025 1900 1335 1.64 1454 1395 1.83 1627 1452 2.03 1804 1506 2.23 1984 1557 2.44 2168 2000 1366 1.78 1580 1426 1.98 1760 1482 2.19 1943 1535 2.40 2130 1586 2.61 2319 2100 1398 1.93 1715 1457 2.14 1901 1512 2.35 2091 1565 2.57 2284 1616 2.79 2481 2200 1430 2.09 1858 1488 2.31 2052 1543 2.53 2249 1596 2.76 2449 2300 1462 2.27 2012 1520 2.49 2212 1574 2.72 2416 2400 1495 2.45 2175 1552 2.68 2383 2500 1529 2.64 2349 1585 2.89 2564 2600 1562 2.85 2533 2700 2800 2900 3000
NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See general fan performance notes.
LEGEND
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-supplied
drive.
50HE,HJ
Table 25—Fan Performance 50HE003 — Horizontal Discharge Units; Standard Motor (Belt Drive)**
AIRFLOW
(Cfm)
600 700 800 900
1000
0.1 0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
490 0.08 521 0.08 597 0.14 703 0.21 788 0.29 519 0.09 557 0.09 623 0.16 729 0.24 816 0.32 537 0.1 582 0.12 650 0.19 751 0.27 845 0.37 560 0.13 610 0.14 681 0.22 783 0.32 870 0.42 589 0.15 640 0.16 707 0.26 808 0.36 894 0.47
EXTERNAL STATIC PRESSURE (in. wg)
Rpm Bhp
868 0.37
892 0.41 927 0.47 947 0.53 971 0.58
51
Page 52
Table 26—Fan Performance 50HJ004, 50HE004 — Horizontal Discharge Units; Standard Motor
(Belt Drive)*
AIRFLOW
CFM
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
900 554 0.14 134 681 0.22 222 783 0.32 316 870 0.42 416 947 0.53 523 1000 583 0.16 163 707 0.26 257 808 0.36 358 894 0.47 465 971 0.58 578 1100 612 0.20 195 735 0.30 298 834 0.41 406 919 0.52 519 995 0.64 638 1200 643 0.23 233 762 0.35 344 860 0.46 459 944 0.58 579 1020 0.71 705 1300 674 0.28 276 791 0.40 395 887 0.52 517 970 0.65 645 1045 0.78 777 1400 706 0.33 324 820 0.45 451 914 0.59 582 997 0.72 717 1071 0.86 857 1500 738 0.38 379 849 0.52 515 942 0.66 653 1024 0.80 796 1097 0.95 942
AIRFLOW
CFM
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
900 1017 0.64 635 1082 0.76 753 1143 0.88 876 1200 1.01 1004 1254 1.14 1136 1000 1041 0.70 696 1105 0.82 820 1166 0.95 948 1223 1.09 1081 1100 1065 0.77 763 1129 0.90 892 1189 1.03 1026 1245 1.17 1165 1200 1089 0.84 835 1153 0.98 971 1212 1.12 1111
50HE,HJ
1300 1114 0.92 915 1177 1.06 1056 1400 1139 1.01 1000 1202 1.15 1149 1500 1164 1.10 1093
NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See general fan performance notes.
LEGEND
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 680 to 1044 rpm. All other rpms require field-supplied
drive.
Table 27—Fan Performance 50HJ004, 50HE004 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
CFM
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
900 554 0.14 134 681 0.22 222 783 0.32 316 870 0.42 416 947 0.53 523 1000 583 0.16 163 707 0.26 257 808 0.36 358 894 0.47 465 971 0.58 578 1100 612 0.20 195 735 0.30 298 834 0.41 406 919 0.52 519 995 0.64 638 1200 643 0.23 233 762 0.35 344 860 0.46 459 944 0.58 579 1020 0.71 705 1300 674 0.28 276 791 0.40 395 887 0.52 517 970 0.65 645 1045 0.78 777 1400 706 0.33 324 820 0.45 451 914 0.59 582 997 0.72 717 1071 0.86 857 1500 738 0.38 379 849 0.52 515 942 0.66 653 1024 0.80 796 1097 0.95 942
AIRFLOW
CFM
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1.2 1.4 1.6 1.8 2.0
900 1017 0.64 635 1082 0.76 753 1143 0.88 876 1200 1.01 1004 1254 1.14 1136 1000 1041 0.70 696 1105 0.82 820 1166 0.95 948 1223 1.09 1081 1276 1.23 1219 1100 1065 0.77 763 1129 0.90 892 1189 1.03 1026 1245 1.17 1165 1299 1.32 1308 1200 1089 0.84 835 1153 0.98 971 1212 1.12 1111 1269 1.26 1256 1322 1.41 1404 1300 1114 0.92 915 1177 1.06 1056 1236 1.21 1202 1292 1.36 1353 1346 1.52 1508 1400 1139 1.01 1000 1202 1.15 1149 1261 1.31 1301 1316 1.47 1457 1369 1.63 1618 1500 1164 1.10 1093 1227 1.25 1248 1285 1.41 1407 1341 1.58 1570 1394 1.75 1736
NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See general fan performance notes.
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
LEGEND
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require field-supplied
drive.
52
Page 53
Table 28—Fan Performance 50HJ005, 50he005 — Horizontal Discharge Units; Standard Motor
(Belt Drive)*
AIRFLOW
CFM
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
1200 643 0.23 233 762 0.35 344 860 0.46 459 944 0.58 579 1020 0.71 705 1300 674 0.28 276 791 0.40 395 887 0.52 517 970 0.65 645 1045 0.78 777 1400 706 0.33 324 820 0.45 451 914 0.59 582 997 0.72 717 1071 0.86 857 1500 738 0.38 379 849 0.52 515 942 0.66 653 1024 0.80 796 1097 0.95 942 1600 771 0.44 440 879 0.59 584 971 0.74 731 1051 0.89 881 1124 1.04 1035 1700 804 0.51 507 910 0.66 661 1000 0.82 816 1079 0.98 974 1151 1.14 1136 1800 837 0.59 582 941 0.75 745 1029 0.91 909 1107 1.08 1075 1900 871 0.67 665 972 0.84 837 1059 1.02 1010 1136 1.19 1184 2000 906 0.76 756 1004 0.94 938 1089 1.12 1119
AIRFLOW
CFM
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
1200 1089 0.84 835 1153 0.98 971 1212 1.12 1111 1300 1114 0.92 915 1177 1.06 1056 1400 1139 1.01 1000 1202 1.15 1149 1500 1164 1.10 1093 1600 1190 1.20 1193 1700 1800 1900 2000
NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See general fan performance notes.
LEGEND
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 770 to 1185 rpm. All other rpms require field-supplied
drive.
50HE,HJ
Table 29—Fan Performance 50HJ005, 50HE005 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
CFM
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
1200 643 0.23 233 762 0.35 344 860 0.46 459 944 0.58 579 1020 0.71 705 1300 674 0.28 276 791 0.40 395 887 0.52 517 970 0.65 645 1045 0.78 777 1400 706 0.33 324 820 0.45 451 914 0.59 582 997 0.72 717 1071 0.86 857 1500 738 0.38 379 849 0.52 515 942 0.66 653 1024 0.80 796 1097 0.95 942 1600 771 0.44 440 879 0.59 584 971 0.74 731 1051 0.89 881 1124 1.04 1035 1700 804 0.51 507 910 0.66 661 1000 0.82 816 1079 0.98 974 1151 1.14 1136 1800 837 0.59 582 941 0.75 745 1029 0.91 909 1107 1.08 1075 1178 1.25 1244 1900 871 0.67 665 972 0.84 837 1059 1.02 1010 1136 1.19 1184 1206 1.37 1361 2000 906 0.76 756 1004 0.94 938 1089 1.12 1119 1165 1.31 1301 1234 1.49 1486
AIRFLOW
CFM
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1.2 1.4 1.6 1.8 2.0
1200 1089 0.84 835 1153 0.98 971 1212 1.12 1111 1269 1.26 1256 1322 1.41 1404 1300 1114 0.92 915 1177 1.06 1056 1236 1.21 1202 1292 1.36 1353 1346 1.52 1508 1400 1139 1.01 1000 1202 1.15 1149 1261 1.31 1301 1316 1.47 1457 1369 1.63 1618 1500 1164 1.10 1093 1227 1.25 1248 1285 1.41 1407 1341 1.58 1570 1394 1.75 1736 1600 1190 1.20 1193 1252 1.36 1355 1311 1.53 1520 1366 1.70 1690 1418 1.87 1863 1700 1217 1.31 1301 1278 1.48 1470 1336 1.65 1642 1391 1.83 1818 1443 2.01 1998 1800 1244 1.42 1417 1305 1.60 1593 1362 1.78 1772 1416 1.97 1955 1468 2.15 2141 1900 1271 1.55 1541 1331 1.73 1724 1388 1.92 1911 1442 2.11 2101 1494 2.31 2294 2000 1298 1.68 1674 1358 1.87 1865 1415 2.07 2059 1468 2.27 2256
NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See general fan performance notes.
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
LEGEND
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require field-supplied
drive.
53
Page 54
Table 30—Fan Performance 50HJ006, 50HE006 Single-Phase — Horizontal Discharge Units;
Standard Motor (Belt Drive)*
AIRFLOW
CFM
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
1500 724 0.33 295 837 0.45 402 937 0.59 524 1028 0.74 660 1111 0.91 808 1600 757 0.39 343 866 0.51 455 962 0.65 580 1050 0.81 719 1132 0.98 870 1700 790 0.45 398 894 0.58 514 988 0.72 643 1074 0.88 784 1154 1.06 938 1800 823 0.52 458 924 0.65 579 1015 0.80 712 1099 0.96 857 1177 1.14 1013 1900 857 0.59 525 955 0.73 650 1043 0.89 787 1125 1.05 936 1201 1.23 1096 2000 892 0.67 599 986 0.82 729 1072 0.98 870 1151 1.15 1022 2100 927 0.77 680 1017 0.92 815 1101 1.08 960 1178 1.26 1116 2200 962 0.87 769 1050 1.02 909 1131 1.19 1059 2300 997 0.97 865 1082 1.14 1010 2400 1033 1.09 970 1115 1.26 1120 2500 1069 1.22 1084
AIRFLOW
CFM
50HE,HJ
1500 1188 1.09 970 1261 1.29 1143 1600 1208 1.16 1033
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
1700 1229 1.24 1103 1800 1900 2000 2100 2200 2300 2400 2500
NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 1.30.
3. See general fan performance notes.
LEGEND
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1035 to 1460 rpm. All other rpms require field-supplied
drive.
54
Page 55
Table 31—Fan Performance 50HJ006, 50HE006 Three-Phase — Horizontal Discharge Units;
Standard Motor (Belt Drive)*
AIRFLOW
CFM
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
1500 724 0.33 295 837 0.45 402 937 0.59 524 1028 0.74 660 1111 0.91 808 1600 757 0.39 343 866 0.51 455 962 0.65 580 1050 0.81 719 1132 0.98 870 1700 790 0.45 398 894 0.58 514 988 0.72 643 1074 0.88 784 1154 1.06 938 1800 823 0.52 458 924 0.65 579 1015 0.80 712 1099 0.96 857 1177 1.14 1013 1900 857 0.59 525 955 0.73 650 1043 0.89 787 1125 1.05 936 1201 1.23 1096 2000 892 0.67 599 986 0.82 729 1072 0.98 870 1151 1.15 1022 1226 1.33 1185 2100 927 0.77 680 1017 0.92 815 1101 1.08 960 1178 1.26 1116 1251 1.44 1283 2200 962 0.87 769 1050 1.02 909 1131 1.19 1059 1206 1.37 1218 1277 1.56 1389 2300 997 0.97 865 1082 1.14 1010 1161 1.31 1165 1235 1.50 1329 1304 1.69 1503 2400 1033 1.09 970 1115 1.26 1120 1192 1.44 1279 1264 1.63 1448 1332 1.83 1625 2500 1069 1.22 1084 1149 1.39 1239 1223 1.58 1403 1293 1.77 1576 1360 1.98 1757
AIRFLOW
CFM
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STTIC PRESSURE (in. wg)
1500 1188 1.09 970 1261 1.29 1143 1330 1.49 1327 1395 1.71 1523 1457 1.95 1729 1600 1208 1.16 1033 1279 1.36 1208 1347 1.57 1394 1412 1.79 1590 1474 2.02 1797 1700 1229 1.24 1103 1299 1.44 1280 1366 1.65 1468 1429 1.88 1665 1490 2.11 1873 1800 1250 1.33 1181 1319 1.53 1360 1385 1.74 1549 1448 1.97 1748 1508 2.20 1957 1900 1273 1.43 1266 1341 1.63 1447 1405 1.84 1638 1467 2.07 1839 1527 2.31 2050 2000 1296 1.53 1359 1363 1.74 1542 1427 1.95 1736 1488 2.18 1939 2100 1320 1.64 1459 1386 1.85 1646 1448 2.07 1842 1508 2.30 2047 2200 1345 1.77 1568 1409 1.98 1758 1471 2.20 1956 2300 1371 1.90 1686 1434 2.11 1878 1494 2.34 2080 2400 1397 2.04 1812 1459 2.26 2008 2500 1424 2.19 1948
NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See general fan performance notes.
LEGEND
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1035 to 1460 rpm. All other rpms require field-supplied
drive.
50HE,HJ
55
Page 56
Table 32—Fan Performance 50HJ006, 50HE006 — Horizontal Discharge Units;
HIGH--STATIC Motor (Belt Drive)*
AIRFLOW
CFM
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
1500 724 0.33 295 837 0.45 402 937 0.59 524 1028 0.74 660 1111 0.91 808 1600 757 0.39 343 866 0.51 455 962 0.65 580 1050 0.81 719 1132 0.98 870 1700 790 0.45 398 894 0.58 514 988 0.72 643 1074 0.88 784 1154 1.06 938 1800 823 0.52 458 924 0.65 579 1015 0.80 712 1099 0.96 857 1177 1.14 1013 1900 857 0.59 525 955 0.73 650 1043 0.89 787 1125 1.05 936 1201 1.23 1096 2000 892 0.67 599 986 0.82 729 1072 0.98 870 1151 1.15 1022 1226 1.33 1185 2100 927 0.77 680 1017 0.92 815 1101 1.08 960 1178 1.26 1116 1251 1.44 1283 2200 962 0.87 769 1050 1.02 909 1131 1.19 1059 1206 1.37 1218 1277 1.56 1389 2300 997 0.97 865 1082 1.14 1010 1161 1.31 1165 1235 1.50 1329 1304 1.69 1503 2400 1033 1.09 970 1115 1.26 1120 1192 1.44 1279 1264 1.63 1448 1332 1.83 1625 2500 1069 1.22 1084 1149 1.39 1239 1223 1.58 1403 1293 1.77 1576 1360 1.98 1757
AIRFLOW
CFM
50HE,HJ
1500 1188 1.09 970 1261 1.29 1143 1330 1.49 1327 1395 1.71 1523 1457 1.95 1729 1600 1208 1.16 1033 1279 1.36 1208 1347 1.57 1394 1412 1.79 1590 1474 2.02 1797
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
1700 1229 1.24 1103 1299 1.44 1280 1366 1.65 1468 1429 1.88 1665 1490 2.11 1873 1800 1250 1.33 1181 1319 1.53 1360 1385 1.74 1549 1448 1.97 1748 1508 2.20 1957 1900 1273 1.43 1266 1341 1.63 1447 1405 1.84 1638 1467 2.07 1839 1527 2.31 2050 2000 1296 1.53 1359 1363 1.74 1542 1427 1.95 1736 1488 2.18 1939 1546 2.42 2151 2100 1320 1.64 1459 1386 1.85 1646 1448 2.07 1842 1508 2.30 2047 1566 2.55 2262 2200 1345 1.77 1568 1409 1.98 1758 1471 2.20 1956 1530 2.44 2164 1587 2.68 2380 2300 1371 1.90 1686 1434 2.11 1878 1494 2.34 2080 1553 2.58 2290 1609 2.83 2509 2400 1397 2.04 1812 1459 2.26 2008 1518 2.49 2213 1576 2.73 2425 2500 1424 2.19 1948 1484 2.42 2147 1543 2.65 2355 1599 2.89 2571
NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See general fan performance notes.
LEGEND
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-supplied
drive.
Table 33—Fan Performance 50HJ007 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
CFM
1800 822 0.51 455 927 0.66 589 1018 0.82 728 1100 0.98 873 1174 1.15 1024
1900 855 0.59 520 957 0.74 659 1046 0.91 805 1127 1.08 956 1200 1.25 1113 2000 889 0.66 591 988 0.83 737 1075 1.00 888 1154 1.18 1045 1226 1.36 1208 2100 923 0.75 668 1019 0.92 821 1104 1.10 979 1182 1.29 1142 1253 1.48 1310 2200 957 0.85 753 1051 1.03 912 1134 1.21 1077 1210 1.40 1245 1280 1.60 1419 2300 992 0.95 845 1083 1.14 1011 1164 1.33 1182 1239 1.53 1357 1308 1.73 1537 2400 1026 1.06 945 1115 1.26 1118 1195 1.46 1295 1268 1.66 1476 1336 1.87 1662 2500 1061 1.19 1053 1148 1.39 1233 1226 1.59 1416 1297 1.81 1604 1364 2.02 1796 2600 1097 1.32 1169 1181 1.53 1356 1257 1.74 1546 1327 1.96 1740 1393 2.18 1938 2700 1132 1.46 1294 1214 1.67 1487 1289 1.90 1684 1358 2.12 1885 1422 2.35 2089 2800 1168 1.61 1428 1247 1.83 1629 1320 2.06 1832 1388 2.30 2039 2900 1204 1.77 1572 1281 2.00 1779 1353 2.24 1989 3000 1240 1.94 1725 1315 2.18 1939
AIRFLOW
CFM
1800 1244 1.33 1182 1308 1.51 1345 1369 1.70 1513 1427 1.90 1687 1483 2.10 1867 1900 1268 1.44 1275 1332 1.63 1443 1393 1.82 1617 1450 2.02 1796 1505 2.23 1979 2000 1294 1.55 1376 1357 1.74 1549 1417 1.95 1727 1474 2.15 1911 1528 2.36 2100 2100 1320 1.67 1483 1382 1.87 1662 1441 2.08 1845 1498 2.29 2034 2200 1346 1.80 1598 1408 2.01 1782 1466 2.22 1971 2300 1372 1.94 1721 1434 2.15 1911 1491 2.37 2105 2400 1400 2.09 1852 1460 2.31 2047 2500 1427 2.24 1992 2600 2700 2800 2900 3000
NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See general fan performance notes.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
LEGEND
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1120 to 1585 rpm. All other rpms require field-supplied
drive.
56
Page 57
Table 34—Fan Performance 50HJ007 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
CFM
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
1800 822 0.51 455 927 0.66 589 1018 0.82 728 1100 0.98 873 1174 1.15 1024 1900 855 0.59 520 957 0.74 659 1046 0.91 805 1127 1.08 956 1200 1.25 1113 2000 889 0.66 591 988 0.83 737 1075 1.00 888 1154 1.18 1045 1226 1.36 1208 2100 923 0.75 668 1019 0.92 821 1104 1.10 979 1182 1.29 1142 1253 1.48 1310 2200 957 0.85 753 1051 1.03 912 1134 1.21 1077 1210 1.40 1245 1280 1.60 1419 2300 992 0.95 845 1083 1.14 1011 1164 1.33 1182 1239 1.53 1357 1308 1.73 1537 2400 1026 1.06 945 1115 1.26 1118 1195 1.46 1295 1268 1.66 1476 1336 1.87 1662 2500 1061 1.19 1053 1148 1.39 1233 1226 1.59 1416 1297 1.81 1604 1364 2.02 1796 2600 1097 1.32 1169 1181 1.53 1356 1257 1.74 1546 1327 1.96 1740 1393 2.18 1938 2700 1132 1.46 1294 1214 1.67 1487 1289 1.90 1684 1358 2.12 1885 1422 2.35 2089 2800 1168 1.61 1428 1247 1.83 1629 1320 2.06 1832 1388 2.30 2039 1452 2.53 2249 2900 1204 1.77 1572 1281 2.00 1779 1353 2.24 1989 1419 2.48 2202 1482 2.72 2419 3000 1240 1.94 1725 1315 2.18 1939 1385 2.43 2156 1451 2.68 2376
AIRFLOW
CFM
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1.2 1.4 1.6 1.8 2.0
1800 1244 1.33 1182 1308 1.51 1345 1369 1.70 1513 1427 1.90 1687 1483 2.10 1867 1900 1268 1.44 1275 1332 1.63 1443 1393 1.82 1617 1450 2.02 1796 1505 2.23 1979 2000 1294 1.55 1376 1357 1.74 1549 1417 1.95 1727 1474 2.15 1911 1528 2.36 2100 2100 1320 1.67 1483 1382 1.87 1662 1441 2.08 1845 1498 2.29 2034 1552 2.51 2227 2200 1346 1.80 1598 1408 2.01 1782 1466 2.22 1971 1522 2.44 2165 1575 2.66 2363 2300 1372 1.94 1721 1434 2.15 1911 1491 2.37 2105 1547 2.59 2304 1600 2.82 2507 2400 1400 2.09 1852 1460 2.31 2047 1517 2.53 2247 1572 2.76 2451 2500 1427 2.24 1992 1487 2.47 2192 1543 2.70 2398 2600 1455 2.41 2140 1514 2.64 2346 1570 2.88 2557 2700 1483 2.59 2297 1541 2.83 2509 2800 1512 2.77 2463 2900 1541 2.97 2640 3000
NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See general fan performance notes.
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
LEGEND
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-supplied
drive.
50HE,HJ
57
Page 58
PRE-START-UP
!
FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD
Failur e to follow this warning could res ul t in personal injury, death, and/or propert y damage.
1. Follow recogniz ed safe t y practices and wear protective goggles when checking or servicing a refrige rant syste m.
2. Do not operate the compres sor or provide any electr ic power to the unit unless the compressor termina l cover is in place and secured.
3. Do not remove the compres sor terminal cover until all electrical sources are disconnected and tagged with lockout tags.
4. Relie ve all pressure from the system before touching or disturbing anyt hi ng inside the te rminal box if a refrigerant leak is suspected around the compre ssor terminals. Use accepted methods to recover the
50HE,HJ
refrigerant.
5. Never attempt to repair a soldered connection while the refrigerant system is under pressure.
6. Do not use a torch to rem ove any component. The system contains oil and refr igerant under pressure. To remove a component, wear protective goggles and proceed as follows:
a. Shut off electrical power to the unit and tag
b. Recover refrigerant to relieve all pressure
c. Cut component connection tubing with a
d. Carefully unsweat the remaining tubing
Proceed as follows to inspect and prepare the unit for initial start-up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING, CAUTION, and INFORMATION labels attached to, or shipped with, unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages such as
broken lines, loose parts, or disconnected wires, etc.
b. Inspectfor oil at allrefrigeranttubing connections and on
unit base. Detecting oil generally indicates a refrigerant leak. Leak-test all refrigerant tubing connections using electronic leak detector, halide torch, or liquid-soap solution.
c. Inspect all field-wiring and factory-wiring connections.
Be sure that connections are completed and tight. Be sure that wires are not in contact with refrigerant tubing or sharp edges.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin comb.
4. Verify the following conditions:
a. Make sure that condenser-fan blade are correctly
positioned in fan orifice.See Condenser-Fan Adjustment section for more details.
b. Make sure that air filter(s) is in place.
c. Make sure that condensate drain trap is filled with water
to ensure proper drainage.
WARNING
disconnect.
from the system using both high-pressure
and low-pressure ports.
tubing cutter, and remove the component
from the unit.
stubs when necessary. Oil can ignite when
exposed to a torch flame.
d. Make sure that all tools and miscellaneous loose parts
have been removed.

START-UP

Step 1 Unit Preparation
Make sure that the unit has been installed in accordance with installation instructions and applicable codes.
Step 2 Return--Air Filters
Make sure the correct filters are installed in the unit (See Table 1). Do not operate the unit without return-air filters.
Step 3 Outdoor--Air Inlet Screens
Outdoor-air inlet screen(s) must be in place before operating the unit.
Step 4 Compressor Mounting
Compressors are internally spring mounted. Do not loosen or remove the compressor holddown bolts.
Step 5 Internal Wiring
Check all electrical connections in unit control boxes; tighten them as required.
Step 6 Refrigerant Service Ports
Each unit system has 4 Schrader--type service ports: one on the suction line, one on the liquid line, and 2 on the compressor discharge line. Be sure that caps on the ports are tight.
Step 7 High Flow Valves
Two high flow refrigerant valves are located on the hot gas tube coming out of the compressor and the suction tubes. Large black plastic caps distinguish these valves with O--rings located inside the caps. No field access to these valves is available at this time. Ensure the plastic caps are in place and tight or the possibility of refrigerant leakage could occur.
Step 8 Compressor Rotation
On 3-phase units be certain that the compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the proper direction:
1. Connect the service gauges to suction and discharge pressure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pressure does not rise to normal levels:
1. Note that the indoor fan (006 and 007 three-phase units only) is probably also rotating in the wrong direction.
2. Turn off power to the unit and tag disconnect.
3. Reverse any two of the unit power leads.
4. Turn on power to the unit and energize the compressor.
The suction and discharge pressure levels should now move to their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direction, the unit makes more noise and does not provide cooling.
Step 9 Cooling
Set the space thermostat to the OFF position. Set the system selector switch at COOL position and the fan switch at AUTO position. Adjust the thermostat to a setting below room temperature. The compressor starts when contactor closes.
Check cooling effects at a setting below room temperature. Check the unit charge. Refer to Refrigerant Charge section.
Reset the thermostat at a position above room temperature. The compressor will shut off.
To Shut Off Unit -- Set the system selector switch at OFF position. Resetting the thermostat at a position above room temperature shuts off the unit temporarily until the space temperature exceeds the thermostat setting. Units are equipped
58
Page 59
with a Cycle-LOCprotection device. The unit shuts down on any safety trip and remains off; an indicator light on the thermostat comes on. Check the reason for the safety trip.
Compressor restart is accomplished by manual reset at the thermostat by turning the selector switch to OFF position and then to ON position.
Step 10 Heating
To start unit, turn on main power supply. Set system selector switch at HEAT position and set thermostat at
a setting above room temperature. Set fan at AUTO position. First stage of thermostat energizes the first--stage electric heater
elements; second stage energizes second--stage electric heater elements, if installed. Check heating effects at air supply grille(s).
If electric heaters do not energize, reset limit switch (located on evaporator-- fan scroll) by pressing button located between terminals on the switch.
TO SHUT OFF UNIT -- Set system selector switch at OFF position. Resetting thermostat at a position below room temperature temporarily shuts unit off until space temperature falls below thermostat setting.
Step 11 Safety Relief
A soft solder joint at the suction line fitting provides pressure relief under abnormal temperature and pressure conditions.
Step 12 Ventilation (Continuous Fan)
Set fan and system selector switches at ON and OFF positions, respectively. Evaporator fan operates continuously to provide constant air circulation.
Step 13 Operating Sequence
Cooling -- Units Without
When thermostat calls for cooling, terminals G and Y1 are energized. The indoor-fan contactor (IFC), reversing valve solenoid (RVS) and compressor contactor are energized and indoor-fan motor, compressor, and outdoor fan starts. The outdoor fan motor runs continuously while unit is cooling.
Heating -- Units Without
When the thermostat calls for heating, terminal W1 will be energized with 24v. The IFC and heater contactor no. 1 (HC1) are energized.
Cooling -- Units With Economi$er
When free cooling is not available, the compressors will be controlled by the zone thermostat. When free cooling is available, the outdoor-air damper is modulated by the EconoMi$er IV control to provide a 50_ to 55_F supply-air temperature into the zone. As the supply-air temperature fluctuates above 55_ or below 50_F, the dampers will be modulated (open or close) to bring the supply-air temperature back within the set point limits.
Integrated EconoMi$er IV operation on single-stage units requires a 2-stage thermostat (Y1 and Y2).
For EconoMi$er IV operation, there must be a thermostat call for the fan (G). This will move the damper to its minimum position during the occupied mode.
If the increase in cooling capacity causes the supply--air temperature to drop below 45_F, then the outdoor--air damper position will be fully closed. If the supply--air temperature continues to fall, the outdoor-- air damper will close. Control returns to normal once the supply--air temperature rises above 48_F.
If optional power exhaust is installed, as the outdoor--air damper opens and closes, the power exhaust fans will be energized and deenergized.
If field--installed accessory CO EconoMi$er IV control, a demand controlled ventilation strategy will begin to operate. As the CO above the CO will be increased proportionally. As the CO
set point, the minimum position of the damper
2
Economizer
Economizer
IV
sensors are connected to the
2
level in the zone increases
2
level decreases
2
because of the increase in fresh air, the outdoor--air damper will be proportionally closed. Damper position will follow the higher demand condition from DCV mode or free cooling mode.
Damper movement from full closed to full open (or vice versa) will take between 1--1/2 and 2--1/2 minutes.
If free cooling can be used as determined from the appropriate changeover command (switch, dry bulb, enthalpy curve, differential dry bulb, or differential enthalpy), a call for cooling (Y1 closes at the thermostat) will cause the control to modulate the dampers open to maintain the supply air temperature set point at 50_ to 55_ F.
As the supply air temperature drops below the set point range of 50_ to 55_ F, the control will modulate the outdoor--air dampers closed to maintain the proper supply--air temperature.
Heating -- Units With Economi$er
When the room temperature calls for heat, the heating controls are energized as described in the Heating, Units Without Economizer section. When the thermostat is satisfied, the economizer damper moves to the minimum position.
Cooling -- Units With Economi$er2, Premierlink and a
Thermostat
When free cooling is not available, the compressors will be controlled by the PremierLink control in response to the Y1 and Y2 inputs from the thermostat.
The PremierLink control will use the following information to determine if free cooling is available:
IV
t Control
S Indoor fan has been on for at least 30 seconds. S The SPT, SAT, and OAT inputs must have valid
readings.
S OAT must be less than 75_F. S OAT must be less than SPT. S Enthalpy must be LOW (may be jumpered if an
enthalpy sensor not available).
S Economizer position is NOT forced.
Pre-cooling occurs when there is no call from the thermostat except G. Pre-cooling is defined as the economizer modulates to provide 70_F supply air.
When free cooling is available the PremierLink control will control the compressors and economizer to provide a supply-air temperature determined to meet the Y1 and Y2 calls from the thermostat using the following three routines. The three control routines are based on OAT.
The 3 routines are based on OAT where: SASP = Supply Air Set Point DXCTLO = Direct Expansion Cooling Lockout Set Point PID = Proportional Integral Routine 1 (OAT < DXCTLO)
S Y1 energized – economizer maintains a SASP =
(SATLO1 + 3).
S Y2 energized – economizer maintains a SASP =
(SATLO2 + 3).
Routine 2 (DXCTLO<OAT<68_F)
S If only Y1 energized, the economizer maintains a
SASP = (SATLO1 + 3).
S If SAT > SASP + 5 and economizer position > 80%,
economizer will go to minimum position for 3 minutes or until SAT > 68_F.
S First stage of mechanical cooling will be energized. S Integrator resets. S Economizer opens again and controls to current SASP
after stage one on for 90 seconds.
59
50HE,HJ
Page 60
S With Y1 and Y2 energized Economizer maintains an
SASP = SATLO2 + 3.
S If SAT > SASP + 5 and economizer position >80%,
economizer will go to minimum position for 3 minutes or until SAT > 68_F.
S If compressor one is on then second stage of
mechanical cooling will be energized; otherwise the first stage will be energized.
S Integrator resets.
75
74
73 72
71
70
69
SPACE TEMPERATURE
68
TEMPERATURE CONTROL
SET POINT
TEMPERATURE
TIME
S Economizer opens again and controls to SASP after
stage one on for 90 seconds.
Routine 3 (OAT > 68)
S Economizer is opened 100%. S Compressors1and2arecycledbasedonY1andY2
using minimum on and off times and watching the supply air temperature as compared to SATLO1 and SATLO2 set points.
50HE,HJ
If optional power exhaust is installed, as the outdoor-air damper opens and closes, the power exhaust fans will be energized and deenergized.
If field-installed accessory CO
sensors are connected to the
2
PremierLinkcontrol, a PID-controlled demand ventilation strategy will begin to operate. As the CO increases above the CO
set point, the minimum position of the
2
damper will be increased proportionally. As the CO
level in the zone
2
2
level decreases because of the increase in fresh air, the outdoor-air damper will be proportionally closed.
Heating -- Units With Economi$er2 Premierlink Control a
Thermostat
and
When the thermostat calls for heating, terminal W1 is energized. The PremierLink control will move the economizer damper to the minimum position if there is a call for G and closed if there is a call for W1 without G. The IFC and heater contactor no. 1 (HC1) are energized. When the thermostat is satisfied and W1 is deenergized, the IFM stops after a 45 --second time--off delay unless G is still maintained.
Cooling -- Units With Economi$er2, Premierlink Control a Room
Sensor
and
When free cooling is not available, the compressors will be controlled by the PremierLink controller using a PID Error reduction calculation as indicated by Fig 49.
The PremierLink controller will use the following information to determine if free cooling is available:
S Indoor fan has been on for at least 30 seconds. S The SPT, SAT, and OAT inputs must have valid
readings.
S OAT must be less than 75_F. S OAT must be less than SPT. S Enthalpy must be LOW (may be jumpered if and
enthalpy sensor is not available).
S Economizer position is NOT forced.
NOTE: PremierLink control performs smart staging of 2 stages of DX cooling and up to 3 stages of heat.
C06042
Fig. 49 --- DX Cooling Temperature
Control Example
TEMPERATURE CONTROL
75
74
73 72
71
70
69
SPACE TEMPERATURE
68
TIME
COOL SETPOINT
TEMPERATURE HEAT SETPOINT
C06043
Fig. 50 --- Economizer T emperature
Control Example
When free cooling is available, the outdoor-air damper is positioned through the use of a Proportional Integral (PID) control process to provide a calculated supply-air temperature into the zone. The supply air will maintain the space temperature between the heating and cooling set points as indicated in Fig. 50.
The PremierLink control will integrate the compressors stages with the economizer based on similar logic as the three routines listed in the previous section. The SASP will float up and down based on the error reduction calculations that compare space temperature and space set point.
When outside-air temperature conditions require the economizer to close for a compressor stage-up sequence, the economizer control integrator is reset to zero after the stage-up sequence is completed. This prevents the supply-air temperature from dropping too quickly and creating a freeze condition that would make the compressor turn off prematurely.
The high space set point is used for DX (direct expansion) cooling control, while the economizer space set point is a calculated value between the heating and cooling set points. The economizer set point will always be at least one degree below the cooling set point, allowing for a smooth transition from mechanical cooling with economizer assist, back to economizer cooling as the cooling set point is achieved. The compressors may be used for initial cooling then the PremierLink controller will modulate the economizer using an error reduction calculation to hold the space temperature between the heating and cooling set points. (See Fig. 50.)
The controller uses the following conditions to determine economizer cooling:
S Enthalpy is Low S SAT reading is available S OAT reading is available
60
Page 61
S SPT reading is available S OAT ± SPT S Economizer Position is NOT forced
If any of the above conditions are not met, the economizer submaster reference (ECSR) is set to maximum limit and the damper moves to minimum position. The operating sequence is complete. The ECSR is recalculated every 30 seconds.
If an optional power exhaust is installed, as the outdoor-air damper opens and closes, the power exhaust fans will be energized and deenergized.
If field-installed accessory CO PremierLinkcontrol, a PID-controlled demand ventilation strategy will begin to operate. As the CO increases above the CO damper will be increased proportionally. As the CO decreases because of the increase in fresh air, the outdoor-air damper will be proportionally closed.
Heating -- Unit With Economi$er2, Premierlink Control a Room
Every 40 seconds the controller will calculate the required heat stages (maximum of 3) to maintain Supply-Air Temperature (SAT) if the following qualifying conditions are met:
Sensor
2
sensors are connected to the
2
level in the zone
set point, the minimum position of the
2
level
2
and
S Indoor fan has been on for at least 30 seconds. S COOL mode is not active. S OCCUPIED, TEMP. COMPENSATED START or
HEAT mode is active.
S SAT reading is available. S Fire shutdown mode is not active.
If all of the above conditions are met, the number of heat stages is calculated; otherwise the required number of heat stages will be set to 0.
If the PremierLink controller determines that heat stages are required, the economizer damper will be moved to minimum position if occupied and closed if unoccupied.
Staging should be as follows: If Heating PID STAGES=2
S HEA T STAGES=1 (50% capacity) will energize HS1 S HEAT STAGES=2 (100% capacity) will energize HS2
If Heating PID STAGES=3 and AUXOUT = HS3
S HEA T STAGES=1 (33% capacity) will energize HS1 S HEA T STAGES=2 (66% capacity) will energize HS2 S HEAT STAGES=3 (100% capacity) will energize HS3
Units With Humidi-Mizer Dehumidification
Normal Design Operation
When the rooftop operates under the normal sequence of operation, the compressors will cycle to maintain indoor conditions. (See Fig. 51.)
The Humidi-MiZer adaptive dehumidification system includes a factory-installed Motormasterlow ambient control to keep the head and suction pressure high, allowing normal design cooling mode operation down to 0F.
Subcooling Mode
When subcooling mode is initiated, this will energize (close) the liquid line solenoid valve (LLSV) forcing the hot liquid refrigerant to enter into the subcooling coil. (See Fig. 52.)
As the hot liquid refrigerant passes through the subcooling/ reheat dehumidification coil, it is exposed to the cold supply airflow coming through the evaporator coil. The liquid is further
Adaptive
System
subcooled to a temperature approaching the evaporator leaving-air temperature. The liquid then enters a thermostatic expansion valve (TXV) where the liquid drops to a lower pressure. The TXV does not have a pressure drop great enough to change the liquid to a 2-phase fluid, so the liquid then enters the Acutroldevice at the evaporator coil.
The liquid enters the evaporator coil at a temperature lower than in standard cooling operation. This lower temperature increases the latent capacity of the rooftop unit. The refrigerant passes through the evaporator and is turned into a vapor. The air passing over the evaporator coil will become colder than during normal operation. However, as this same air passes over the subcooling coil, it will be slightly warmed, partially reheating the air.
Subcooling mode operates only when the outside air temperature is warmer than 40_F. A factory-installed temperature switch located in the condenser section will lock out subcooling mode when the outside temperature is cooler than 40_F.
The scroll compressors are equipped with crankcase heaters to provide protection for the compressors due to the additional refrigerant charge required by the subcooling/reheat coil.
When in subcooling mode, there is a slight decrease in system total gross capacity (5% less), a lower gross sensible capacity (20% less), and a greatly increased latent capacity (up to 40% more).
C06135
Fig. 51 --- Humidi--MiZer Normal
Design Cooling Operation
C06136
Fig. 52 --- Humidi--MiZer Subcooling
Mode Operation
50HE,HJ
61
Page 62
4. Clean coil using a commercial coil cleaner or dishwasher detergent in a pressurized spray canister. Wash both sides of coil and flush with clean water. For best results, back-flush toward return-air section to remove foreign material. Flush condensate pan after completion.
5. Reinstall economizer and filters.
6. Reconnect wiring.
7. Replace access panels.
Condenser
Inspect coil monthly. Clean condenser coil annually, and as required by location and outdoor air conditions.
One--Row Coil
Wash coil with commercial coil cleaner. It is not necessary to remove top panel.
2-Row Coils
C06137
Fig. 53 --- Humidi--Mizert Hot Gas
Reheat Mode Operation
Clean coil as follows:
50HE,HJ
Hot Gas Reheat Mode
When the humidity levels in the space require humidity control, a hot gas solenoid valve (specific to hot gas reheat mode only) will open to bypass a portion of hot gas refrigerant around the condenser coil. (See Fig. 53.)
This hot gas will mix with liquid refrigerant leaving the condenser coil and flow to the subcooling/reheat dehumidification coil. Now the conditioned air coming off the evaporator will be cooled and dehumidified, but will be warmed to neutral conditions (72_Fto75_F) by the subcooling/reheat dehumidification coil.
The net effect of the rooftop when in hot gas reheat mode is to provide nearly all latent capacity removal from the space when sensible loads diminish (when outdoor temperature conditions are moderate). When in hot gas reheat mode, the unit will operate to provide mostly latent capacity and extremely low sensible heat ratio capability.
Similar to the subcooling mode of operation, hot gas reheat mode operates only when the outside air temperature is warmer than 40_F. Below this temperature, a factory installed outside air temperature switch will lockout this mode of operation.
See Table 36 for the Humidi-Mizer adaptive dehumidification system sequence of operation.
Coil
1. Turn off unit power and tag disconnect.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. (See Fig. 54.) To hold top panel open, place coil corner post between top panel and center post. (See Fig. 55.)
C06044
Fig. 54 --- Cleaning Condenser Coil

SERVICE

!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
When sevicing unit, shut off all electrical power to unit and install lockout tag.
Step 1 Cleaning
Inspect unit interior at the beginning of heating and cooling season and as operating conditions require.
Evaporator
1. Turn unit power off, tag disconnect. Remove evaporator coil access panel.
2. If economizer or two-position damper is installed, remove economizer by disconnecting Molex plug and removing mounting screws.
3. Slide filters out of unit.
WARNING
Coil
C06045
Fig. 55 --- Propping Up Top Panel
62
Page 63
Table 35—Humidi-Mizer Adaptive Dehumidification System Sequence of Operation and
System Response — Single Compressor Unit (50HE003--006, 50HJ004-007)
THERMOSTAT INPUT ECONOMIZER FUNCTION 48HE, HJ UNIT OPERATION
H Y1 Y2 OAT. < Economizer Set Point Economizer Comp. 1 Subcooling Mode Hot Gas Reheat Mode
Off — On On On No Off On Yes No
On On Off No Off On Yes No On On On Yes On On Yes No On On Off Yes On On No Yes On Off Off No Off On No Yes
NOTE: On a thermostat call for W1, all cooling and dehumidification will be off.
LEGEND
OAT --- Outdoor Air Temperature
Normal Operation
Fan Motor
Bearings
Fan motor bearings are permanently lubricated. No further lubrication is required. No lubrica tion of condenser- fan or evaporator- fan motors is requir ed.
Evaporator Fan Belt
Adjustment
Inspect evaporator fan belt for wear, proper belt tension, and pulley alignment as conditions require or at the beginning of each heating and air conditioning season. Refer to Step 7 -- Adjust Evaporator Fan Speed for adjustment and alignment procedures.
Step 3 Condenser--Fan Adjustment
Shut off unit power supply. Remove condenser-fan assembly (grille, motor, motor cover, and fan) and loosen fan hub setscrews. Adjust fan height as shown in Fig. 57. Tighten setscrews and replace condenser-fan assembly.
50HE,HJ
C06046
Fig. 56 --- Separating Coil Sections
4. Remove device holding coil sections together at return end of condenser coil. Carefully separate the outer coil section 3 to 4 in. from the inner coil section. (See Fig. 57.)
5. Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner.
6. Secure the sections together. Reposition the outer coil section and remove the coil corner post from between the top panel and center post. Install the coil corner and center posts. Replace all screws.
Condensate
Drain
Check and clean each year at the start of the cooling season. In winter, keep the drain dry or protect it against freeze-up.
Filters
Clean or replace at the start of each heating and cooling season, or more often if operating conditions require it. Replacement filters must be the same dimensions as the original filters.
Outdoor--Air Inlet Scr
een
Clean the screen with steam or hot water and a mild detergent. Do not use disposable filters in place of screens.
Step 2 Lubrication
essor
Compr
The compressor is charged with the correct amount of oil at the factory.
UNIT FAN HEIGHT (in.) — “A”
003-006 AND 007 ( 208/230 v) 2.75
007 (460 v) 3.50
C06138
Fig. 57 --- Condenser--Fan Adjustment
Step 4 EconoMi$er IV Adjustment
Refer to Optional EconoMi$er IV and EconoMi$er2 section.
Step 5 Refrigerant Charge
Amount of refrigerant charge is listed on unit nameplate (also refer to Table 1). Refer to HVAC Servicing Procedures literature available at your local distributor and the following procedures.
Unit panels must be in place when unit is operating during charging procedure. Unit must operate a minimum of 10 minutes before checking or adjusting refrigerant charge.
Charge
No
Use standard evacuating techniques. After evacuating system to 500 microns, weigh in the specified amount of refrigerant. (Refer to Table 1 and unit information plate.)
63
Page 64
Low Charge
Cooling
Using Cooling Charging Charts, Fig. 58 --61, vary refrigerant until the conditions of the charts are met. Note the charging charts are different from type normally used. Charts are based on charging the units to the correct superheat for the various operating conditions. Accurate pressure gage and temperature sensing device are required. Connect the pressure gauge to the service port on the suction line. Mount the temperature sensing device on the suction line and insulate it so that outdoor ambient temperature does not affect the reading. Indoor-air cfm must be within the normal operating range of the unit. An accurate superheat, thermocouple--type or thermistor-- type thermometer, and a gauge manifold are required when using the superheat charging method for evaluating the unit charge. Do not use mercury or small dial--type thermometers because they are not adequate for this type of measurement.
50HE,HJ
C06140
Fig. 59 --- Cooling Charging Chart,
Standard 50HJ005
C06139
Fig. 58 --- Cooling Charging Chart,
Standard 50HJ004
Humidi--Mizer
System Charging
The system charge for units with the Humidi-MiZer adaptive dehumidification system is greater than that of the standard unit alone. The charge for units with this option is indicated on the unit nameplate drawing. Also refer to Fig. 62-65. To charge
systems using the Humidi-MiZer adaptive dehumidification system, fully evacuate, recover, and recharge the system to the nameplate specified charge level. To check or adjust refrigerant charge on systems using the Humidi-MiZer adaptive dehumidification system, charge per Fig. 62-65.
C06141
Fig. 60 --- Cooling Charging Chart,
Standard 50HJ006
64
Page 65
50HE,HJ
C06142
Fig. 61 --- Cooling Charging Chart,
Standard 50HJ007
C06143
Fig. 62 --- Cooling Charging Chart, 50HJ004 with
Optional Humidi--MiZer Adaptive Dehumidification System
C06144
Fig. 63 --- Cooling Charging Chart, 50HJ005 with
Optional Humidi--MiZer Adaptive Dehumidification System
NOTE: When using the charging charts, it is important that only
the subcooling/reheat dehumidification coil liquid line solenoid valve be energized. The subcooling/reheat dehumidification coil liquid line solenoid valve MUST be energized to use the charging charts and the outdoor motor speed controller jumpered to run the fanatfullspeed.
The charts reference a liquid pressure (psig) and temperature at a point between the condenser coil and the subcooling/reheat dehumidification coil. A tap is provided on the unit to measure liquid pressure entering the subcooling/reheat dehumidification coil.
IMPORTANT: The subcooling mode charging charts (Fig. 62--65) are to be used ONLY with units having the Humidi--MiZer adaptive dehumidification system. DO NOT use standard charge (Fig. 58--61) for units with Humidi-- MiZer system, and DO NOT use Fig. 62--65 for standard units.
65
Page 66
If a charging device is used, temperature and pressure readings must be accomplished using the charging charts.
698.0
648.0
598.0
548.0
498.0
448.0
FC
125 52
115 4 6
105 41 95 35 85 29 75 24
C06148
Suction Line Pressure (kpa)
50HE -- 2 TO N CHARGING CHART
Suction Line Temperature (deg C)
5.5 10.5 15.5 20.5 25.5
105.0
100.0
95.0
90.0
85.0
80.0
75.0
Suction Line Pressure (psig)
70.0
65.0 42 52 62 72
SuctionLineTemp(degF)
50HE,HJ
C06145
Fig. 64 --- Cooling Charging Chart, 50HJ005 with
Fig. 66 --- Cooling Charging Chart,
Standard 50HE003
Optional Humidi--MiZer Adaptive Dehumidification System
50HE -- 3 TON CHARGING CHART
SuctionLine Temperature (deg C)
6.1 11.1 16.1 21.1
FC 115 4 6 105 41 95 35 85 29 75 24
C06146
Fig. 65 --- Cooling Charging Chart, 50HJ007 with
Optional Humidi--MiZer Adaptive Dehumidification System
To Use Cooling Charging Chart, Standard
Unit
Take the outdoor ambient temperature and read the suction pressure gage. Refer to charts to determine what suction temperature should be. If suction temperature is high, add refrigerant. If suction temperature is low, carefully recover some of the charge. Recheck the suction pressure as charge is adjusted.
Example (Fig. 57):
Outdoor Temperature 75F.........................
Suction Pressure 70 psig...........................
Suction Temperature should be 48F..................
(Suction temperature may vary  5F.)
95.0
85.0
75.0
SuctionLine Pressure (psig)
65.0 43 48 53 58 63 68 73 78
SuctionLineTemp(degF)
Fig. 67 --- Cooling Charging Chart,
Standard 50HE004
50HE -- 4 TON CHARGING CHART
5.6 10.6 15.6 20.6 25.6
97.0
87.0
77.0
Suction Line Pressure (psig)
67.0 42 47 52 57 62 67 72 77
Suction Line Temperature (deg C)
SuctionLineTemp(degF)
Fig. 68 --- Cooling Charging Chart,
Standard 50HE005
648.2
598.2
548.2
498.2
448.2
115 46
105 41 95 35 85 29 75 24
692.0
642.0
592.0
542.0
492.0
SuctionLine Pressure (kpa)
C06149
FC
Suction Line Pressure (kpa)
C06150
66
Page 67
50HE -- 5 TO N CHARGING CHART
Suction Line Temperature (deg C)
0.0 5.0 10.0 15.0 20.0 25.0
115.0
105.0
95.0
85.0
75.0
Suction Line Pressure (psig)
65.0
55.0 42 47 52 57 62 67 72 77
SuctionLineTemp(degF)
FC 115 4 6 105 41
95 35 85 29 75 24
810.0
710.0
610.0
510.0
410.0
310.0
Suction Line Pressure (kpa)
C06151
Fig. 69 --- Cooling Charging Chart,
Standard 50HE006
To Use Cooling Charging Charts, Units W Humidi--Mizer
Adaptive Dehumidification System
ith
Refer to charts (Fig. 62-65) to determine the proper leaving condenser pressure and temperature.
Example (Fig. 62):
Leaving Condenser Pressure 250 psig.................
Leaving Condenser Temperature 105_F...............
NOTE: When using the charging charts, it is important that only the subcooling/reheat dehumidification coil liquid line solenoid valve be energized. The subcooling/reheat dehumidification coil liquid line solenoid valve MUST be energized to use the charging charts and the outdoor motor speed controller jumpered to run the fanatfullspeed.
IMPORTANT: Refer to Troubleshooting Tables for additional information.
Step 6 Replacement Parts
A complete list of replacement parts may be obtained from any Carrier distributor upon request.

TROUBLESHOOTING

Step 1 Unit Troubleshooting
Refer to Tables 34-38 for unit troubleshooting details.
Step 2 Economi$er IV Troubleshooting
See Table 39 for EconoMi$er IV logic. A functional view of the EconoMi$er IV is shown in Fig. 67.
Typical settings, sensor ranges, and jumper positions are also shown. An EconoMi$er IV simulator program is available from Carrier to help with EconoMi$er IV training and troubleshooting.
Economi$er IV Pr
This procedure is used to prepare the EconoMi$er IV for troubleshooting. No troubleshooting or testing is done by performing the following procedure.
NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm resistor, and a 5.6 kilo-ohm resistor which are not supplied with the EconoMi$er IV.
IMPORTANT: Be sure to record the positions of all potentiometers before starting troubleshooting.
1. Disconnect power at TR and TR1. All LEDs should be off. Exhaust fan contacts should be open.
2. Disconnect device at P and P1.
3. Jumper P to P1.
eparation
4. Disconnect wires at T and T1. Place 5.6 kilo-ohm resistor across T and T1.
5. Jumper TR to 1.
6. Jumper TR to N.
7. If connected, remove sensor from terminals S
O
Connect 1.2 kilo-ohm 4074EJM checkout resistor across terminals S
8. Put 620-ohm resistor across terminals S
O
and +.
and +.
R
9. Set minimum position, DCV set point, and exhaust potentiometers fully CCW (counterclockwise).
10. Set DCV maximum position potentiometer fully CW (clockwise).
11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.
Differential
Enthalpy
To check differential enthalpy:
1. Make sure EconoMi$er IV preparation procedure has been performed.
2. Place 620-ohm resistor across S
3. Place 1.2 kilo-ohm resistor across S
O
and +.
and +. The Free
R
Cool LED should be lit.
4. Remove 620-ohm resistor across S
and +. The Free Cool
O
LED should turn off.
5. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
Enthalpy
Single
To check single enthalpy:
1. Make sure EconoMi$er IV preparation procedure has been performed.
2. Set the enthalpy potentiometer to A (fully CCW). The Free Cool LED should be lit.
3. Set the enthalpy potentiometer to D (fully CW). The Free Cool LED should turn off.
4. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
DCV (Demand Controlled Ventilation) and Power
Exhaust
To check DCV and Power Exhaust:
1. Make sure EconoMi$er IV preparation procedure has been performed.
2. Ensure terminals AQ and AQ1 are open. The LED for both DCV and Exhaust should be off. The actuator should be fully closed.
3. Connect a 9-v battery to AQ (positive node) and AQ1 (negative node). The LED for both DCV and Exhaust should turn on. The actuator should drive to between 90 and 95% open.
4. Turn the Exhaust potentiometer CW until the Exhaust LED turns off. The LED should turn off when the potentiometer is approximately 90%. The actuator should remain in position.
5. Turn the DCV set point potentiometer CW until the DCV LED turns off. The DCV LED should turn off when the potentiometer is approximately 9 v. The actuator should drive fully closed.
6. Turn the DCV and Exhaust potentiometers CCW until the Exhaust LED turns on. The exhaust contacts will close 30 to 120 seconds after the Exhaust LED turns on.
7. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
and +.
50HE,HJ
67
Page 68
DCV Minimum and Maximum
To check the DCV minimum and maximum position:
1. Make sure EconoMi$er IV preparation procedure has been performed.
2. Connect a 9-v battery to AQ (positive node) and AQ1 (negative node). The DCV LED should turn on. The actuator should drive to between 90 and 95% open.
3. Turn the DCV Maximum Position potentiometer to midpoint. The actuator should drive to between 20 and 80% open.
4. Turn the DCV Maximum Position potentiometer to fully CCW. The actuator should drive fully closed.
5. Turn the Minimum Position potentiometer to midpoint. The actuator should drive to between 20 and 80% open.
6. Turn the Minimum Position Potentiometer fully CW. The actuator should drive fully open.
7. Remove the jumper from TR and N. The actuator should drive fully closed.
50HE,HJ
8. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
Supply--Air
Input
Position
Economi$er IV Troubleshooting
This procedure is used to return the EconoMi$er IV to operation. No troubleshooting or testing is done by performing the following procedure.
1. Disconnect power at TR and TR1.
2. Set enthalpy potentiometer to previous setting.
3. Set DCV maximum position potentiometer to previous setting.
4. Set minimum position, DCV set point, and exhaust potentiometers to previous settings.
5. Remove 620-ohm resistor from terminals S
6. Remove 1.2 kilo-ohm checkout resistor from terminals S and +. If used, reconnect sensor from terminals SOand +.
7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
9. Remove 5.6 kilo-ohm resistor from T and T1. Reconnect wires at T and T1.
10. Remove jumper from P to P1. Reconnect device at P and P1.
11. Apply power (24 vac) to terminals TR and TR1.
Completion
and +.
R
O
To check supply-air input:
1. Make sure EconoMi$er IV preparation procedure has been performed.
2. Set the Enthalpy potentiometer to A. The Free Cool LED turns on. The actuator should drive to between 20 and 80% open.
3. Remove the 5.6 kilo-ohm resistor and jumper T to T1. The actuator should drive fully open.
4. Remove the jumper across T and T1. The actuator should drive fully closed.
5. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
68
Page 69
Table 36—Cooling Service Analysis
Compressor and Condenser Fan Will Not Start.
Compressor Will Not Start But Condenser Fan Runs.
CompressorCycles(OtherThan Normally Satisfying Thermostat).
Compressor Operates Continuously.
Excessive Head Pressure.
Head Pressure Too Low.
Excessive Suction Pressure.
Suction Pressure Too Low.
Evaporator Fan Will Not Shut Off.
PROBLEM CAUSE REMEDY
Power failure. Call power company. Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker. Defective thermostat, contactor, transformer, or
control relay. Insufficient line voltage. Determine cause and correct. Incorrect or faulty wiring. Check wiring diagram and rewire correctly. Thermostat setting too high. Lower thermostat setting below room temperature. Faulty wiring or loose connections in compres-
sor circuit. Compressor motor burned out, seized, or in-
ternal overload open. Defective run/start capacitor, overload, start
relay. One leg of 3-phase power dead. Replace fuse or reset circuit breaker. Determine
Refrigerant overcharge or undercharge. Recover refrigerant, evacuate system, and recharge
Defective compressor. Replace and determine cause. Insufficient line voltage. Determine cause and correct. Blocked condenser. Determine cause and correct. Defective run/start capacitor, overload, or start
relay. Defective thermostat. Replace thermostat. Faulty condenser-fan motor or capacitor. Replace. Restriction in refrigerant system. Locate restriction and remove. Dirty air filter. Replace filter. Unit undersized for load. Decrease load or increase unit size. Thermostat set too low. Reset thermostat. Low refrigerant charge. Locate leak, repair, and recharge. Leaking valves in compressor. Replace compressor. Air in system. Recover refrigerant, evacuate system, and recharge. Condenser coil dirty or restricted. Clean coil or remove restriction. Dirty air filter. Replace filter. Dirty condenser coil. Clean coil. Refrigerant overcharged. Recover excess refrigerant. Air in system. Recover refrigerant, evacuate system, and recharge. Condenser air restricted or air short-cycling. Determine cause and correct. Low refrigerant charge. Check for leaks, repair, and recharge. Compressor valves leaking. Replace compressor. Restrictioninliquidtube. Remove restriction. High heat load. Check for source and eliminate. Compressor valves leaking. Replace compressor. Refrigerant overcharged. Recover excess refrigerant. Dirty air filter. Replace filter. Low refrigerant charge. Check for leaks, repair, and recharge. Metering device or low side restricted. Remove source of restriction. Insufficient evaporator airflow. Increase air quantity. Check filter and replace if neces-
Temperature too low in conditioned area. Reset thermostat. Outdoor ambient below 25 F. Install low- a mbient kit. Time off delay not finished. Wait for 30-second off delay.
Replace component.
Check wiring and repair or replace.
Determine cause. Replace compressor.
Determine cause and replace.
cause.
to nameplate.
Determine cause and replace.
sary.
50HE,HJ
69
Page 70
Table 37—Humidi-MiZer Adaptive Dehumidification System Subcooling Mode Service Analysis
Subcooling Mode (Liquid Reheat) Will Not Energize.
Low System Capacity. Low refrigerant ch arge or frosted evaporator coil. 1. Check charge amount. Charge per Fig. 59-62.
Loss of Compressor Superheat Conditions with Subcooling/Reheat Dehumidification Coil Energized.
No power to control transformer from evaporator-fan motor.
No power from control transformer to liquid line solenoid valve.
Liquid line solenoid valve will not operate. 1. Solenoid coil defective; replace.
Liquid line solenoid valve will not open. Valve is stuck closed; replace valve.
Thermostatic expansion valve (TXV). 1. Check TXV bulb mounting, and secure tightly to suc-
Check power source and evaporator-fan relay. Ensure all wire connections are tight.
1. Fuse open; check fuse. Ensure continuity of wiring.
2. Low-pressure switch open. Cycle unit off and allow low-pressure switch to reset. Replace switch if it will not close.
3. Transformer bad; check transformer.
2. Solenoid valve stuck open; replace.
2. Evaporator coil frosted; check and replace low-pres­sure switch if necessary.
tion line.
2. Replace TXV if stuck open or closed.
Table 38—Humidi-MiZer Adaptive Dehumidification System Hot Gas Reheat Mode Service Analysis
PROBLEM CAUSE REMEDY
50HE,HJ
Reheat Mode Will Not Energize. No power to control transformer from
Loss of Compressor Superheat Conditions with Subcooling/Reheat Dehumidification Coil Energized.
Excessive Superheat. Liquid line solenoid valve will not operate. Valve is stuck, replace valve.
PROBLEM CAUSE REMEDY
evaporator-fan motor. No power from control transformer to hot gas
line solenoid valve
Hot gas line solenoid valve will not operate. 1. Solenoid coil defective; replace.
Low refrigerant charge or frosted evaporator coil. 1. Check charge amount. Charge per Fig. 59-62.
Thermostatic expansion valve (TXV). 1. Check TXV bulb mounting, and secure tightly to suc-
Hot gas line solenoid valve will not close. Valve is stuck; replace valve.
Check power source and evaporator-fan relay. Ensure all wire connections are tight.
1. Fuse open; check fuse. Ensure continuity of wiring.
2. Low-pressure switch open. Cycle unit off and allow low-pressure switch to reset. Replace switch if it will not close.
3. Transformer bad; check transformer.
2. Solenoid valve stuck closed; replace.
2. Evaporator coil frosted; check and replace low-pres­sure switch if necessary.
tion line.
2. Replace TXV if stuck open or closed.
Table 39—EconoMi$er IV Input/Output Logic
INPUTS OUTPUTS
Demand Control
Ventilation (DCV)
Below set (DCV LED Off)
High (Free Cooling LED Off)
Enthalpy*
Outdoor Return
Low On On On On Minimum position Closed
Y1 Y2
On Off On Off
Off Off Off Off Low (Free Cooling LED On)
High On On On Off Modulating** (between min.
On Off Off Off
Off Off Off Off Minimum position Closed
Above set (DCV LED On)
High (Free Cooling LED Off)
Low On On On On Modulating†† (between min.
On Off On Off
Off Off Off Off Low (Free Cooling LED On)
High On On On Off Modulating*** Modulating†††
On Off Off Off
Off Off Off Off
*For single enthalpy control, the module compares outdoor enthalpy to the ABCD set point. †Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied). **Modulation is based on the supply-air sensor signal. ††Modulation is based on the DCV signal. ***Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum position (DCV) or fully open (sup-
ply-air signal).
†††Modulation is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV) or fully open (supply-airsig-
nal).
Compressor NTerminal†
Stage1Stage
2
position and full-open)
position and DCV maximum)
Occupied Unoccupied
Damper
Modulating** (between closed and full-open)
Modulating†† (between closed and DCV maximum)
70
Page 71
Fig. 70 --- EconoMi$er IV Functional View
50HE,HJ
C06053
71
Page 72

START-UP CHECKLIST

(Remove and Store in Job File)
I. PRELIMINARY INFORMATION
MODEL NO.: SERIAL NO.:
DA TE: TECHNICIAN:
II. PRE-START-UP (insert checkmark in box as each item is completed)
j VERIFY THA T JOBSITE VOL T AGE AGREES WITH VOLT AGE LISTED ON RATING PLA TE
j VERIFY THA T ALL PACKAGING MATERIALS HAVE BEEN REMOVED FROM UNIT
j REMOVE ALL SHIPPING HOLDDOWN BOL TS AND BRACKETS PER INST ALLA TION INSTRUCTIONS
j VERIFY THA T CONDENSA TE CONNECTION IS INSTALLED PER INST A LLATION INSTRU CTIO NS
j CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
j CHECK GAS PIPING FOR LEAKS
j CHECK THA T RETURN (INDOOR) AIR FIL TERS ARE CLEAN AND IN PLACE
50HE,HJ
j VERIFY THAT UN IT INSTALLA TI ON IS LEVEL
j CHECK FAN WHEELS AND PROP ELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW
TIGHTNESS
j CHECK TO ENSURE THAT ELECTRICAL WIRING IS NOT IN CONTA CT WITH REFRIGERANT LINES
OR SHARP METAL EDGES
j CHECK PULLEY ALIGNM ENT AND BEL T TENSIO N PER INSTA LLATION INSTRU CTIO NS
III. START-UP
ELECTRICAL
SUPPL Y VOL T AGE L1-L2 L2-L3
L3-L1 COMPRESSOR AMPS L1 L2 L3 INDOOR-FAN AMPS L1 L2 L3
TEMPERATURES
OUTDOOR-AIR TEMPERA TURE
RETURN-A IR TEMPERATURE
COOLING SUPPLY AIR
DB
DB WB
DB WB
PRESSURES (Cooling Mode)
REFRIGERANT SUCTION
REFRIGERANT DISCHARGE
PSIG F
PSIG F
j VERIFY THA T 3-PHASE FAN MOTOR AND BLOWER ARE ROTATING IN CORRECT DIRECTION. IF THEY
ARE NOT ROT ATING IN CORRECT DIRECTION, LOCKING COLLAR MUST BE RE--TIGHTENED AFTER CORRECTING DIRECTION OF ROTATION
j VERIFY THAT 3-PHASE SCROLL COMPRESS OR IS ROTATING IN THE CORRECT DIRECTION
j VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS
GENERAL
j SET ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO MATCH JOB REQUIREMEN TS
(IF EQUIPPED)
Copyright 2006 Carrier Corp. S 7310 W. Morris St. S Indianapolis,IN 46231
Manufacturer reserv es the right to change, at any time, specifications and designs without notice and without oblig ations.
Printed in U.S.A. Edition Date:09/06
72
Catalog No:50H-- 1SI
Replaces:50HJ--31SI
Loading...