Carrier 50HG014-028 User Manual

Single Package Rooftop Units
Electric Cooling with Electric Heat Option
Installation Instructions
50HG014-028
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
Step 1 — Provide Unit Support. . . . . . . . . . . . . . . . . . . 1
•ROOF CURB
• ALTERNATE UNIT SUPPORT
Step 2 — Remove Shipping Rails . . . . . . . . . . . . . . . . 3
Step 3 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 3
• POSITIONING
• ROOF MOUNT
• INSTALLATION ONTO CURB
Step 4 — Field Fabricate Ductwork . . . . . . . . . . . . . . . 8
Step 5 — Make Unit Duct Connections . . . . . . . . . . . 8
Step 6 — Trap Condensate Drain . . . . . . . . . . . . . . . . . 9
Step 7 — Make Electrical Connections . . . . . . . . . . . 9
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
Step 8 — Install Outdoor-Air Hood . . . . . . . . . . . . . . 20
Step 9 — Position Optional Power Exhaust
or Barometric Relief Damper Hood. . . . . . . . . . . . 22
Step 10 — Non-Fused Disconnect. . . . . . . . . . . . . . . 22
Step 11 — Install All Accessories . . . . . . . . . . . . . . . 23
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance functions of replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
Before performing service or maintenance operations on unit, turn off main power swit ch to unit. Electrical shock could cause personal injury.
IMPORTANT: Units have high ambient operating lim-
its. If limits are exceede d, the units will automatically
lock the compressor out of operation. Manual r eset will
be required to restart the compressor.
INSTALLATION
Step 1 — Provide Unit Support
ROOF CURB — Assemble or install accessory roof curb in accordance with instructions shipped with this accessory. See Fig. 1. Install insulation, cant strips, roofing, and counter flash­ing as shown. Ductwork can be installed to roof curb before unit is set in place. Curb must be level. This is necessary to permit unit drain to function properly. Unit leveling tolerance is
1
/16 in. per linear ft in any direction. Refer to Accessory
± Roof Curb Installation Instructions for additional information as required. When accessory roof curb i s used, unit may be installed on class A, B, or C roof covering material.
IMPOR TANT: The gasketing of the unit to the roof curb
is critical for a watertight seal. Install gasket with the
roof curb as shown in Fig. 1. Improperly applied gasket
can also result in air leaks and poor unit performance. ALTERNATE UNIT SUPPORT — When a curb cannot be
used, install unit on a noncombustible surface. Support unit with sleepers, using unit curb support area. If sleepers cannot be used, support long sides of unit with a minimum of 3 equal­ly spaced 4-in. x 4-in. pads on each side.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 1b 6 b
PC 111 Catalog No. 535-00092 Printed in U.S.A. Form 50HG-7SI Pg 1 11-03 Replaces: 50HG-3SI
Fig. 1 Roof Curb Details
2
Step 2 Remove Shipping Rails
Remove ship­ping rails prior to lowering unit onto roof curb. See Fig. 2. The rails are attached to the unit at both the return end and condens­er end. Remove the screws from both ends of each rail. Be careful not to drop the rails onto any surface that could be dam­aged. Discard the rails. It is important to replace the screws into the unit to avoid any air or water leakage.
Do not allow the shipping rail to drop on the roof surface. Damage to the roof surface may result.
Step 3 Rig and Place Unit
Inspect unit for trans­portation damage. See Table 1 for physical data. File any claim with transportation agency.
All panels must be in place when rigging. Unit is not designed for handling by fork truck. Damage to unit can result.
Do not drop unit; keep upright. Use spreader bars over unit to prevent sling or cable damage. Rollers may be used to move unit across a roof. Level by using unit frame as a refere nce; leveling tolerance is ±
1
/16 in. per linear ft in any direction. See Fig. 3 for additional information. Unit rigging weight is shown in Fig. 3.
Four lifting holes are provided in the unit base rails as
shown in Fig. 3. Refer to rigging instructions on unit. POSITIONING Maintain clearance, per Fig. 4, around and
above unit to provide minimum distance from combustible materials, proper airflow, and service access.
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs. ROOF MOUNT Check building codes for weight distribu-
tion requirements. Unit operating weight is shown in Table 1. INSTALLATION ONTO CURB The 50HG units are
designed to fit on either the accessory full perimeter curb or onto existing 48/50TJ,HJ or 48/50DP,DR curbs. In either case, correct placement of the unit onto th e curb is critical to operat­ing performance. To aid in correct positioning,
3
/8-in. diameter locating holes have been added to the unit base rails. When placing the unit, these holes should line up with the roof curb edge as shown in Fig. 5 and 6, to assure proper duct opening alignment. Select the alignment holes suited for the curb being used. For installation on the HJ/TJ/DP/DR curb use the align­ment holes located approximately 20 in. from the end of t he base rail on the return end of the unit. For placement on the HG curb, use the alignment holes located approximately 2-in. from the end of the base rail on the return end of the unit. See labels on the side of the unit for more details.
SHIPPING RAILS
Fig. 2 Shipping Rail Removal
3
Fig. 3 Rigging Details
4
Fig. 4 Base Unit Dimensions
5
Table 1 Physical Data
UNIT 50HG 014 016 020
VOLTAGE
NOMINAL CAPACITY (Tons) OPERATING WEIGHT (lb)
50 SERIES (Cooling Only) COMPRESSOR
Quantity Number of Refrigerant Circuits Oil (ounces) Ckt A...Ckt B...Ckt C
REFRIGERANT TYPE
Expansion Device Operating Charge (lb)
Circuit A Circuit B Circuit C
CONDENSER COIL
Rows...Fins/inch TotalFacearea(sq.ft)
CONDENSER FAN
Nominal Cfm (Total, all fans) Quantity...Diameter (in.) Motor Hp...Rpm Watts input (Total)
EVAPORATOR COIL
Rows...Fins/inch TotalFacearea(sq.ft)
EVAPORATOR FAN
Quantity...Size Typ e Drive Nominal Cfm Std Motor Hp Alt Motor Hp Motor Nominal Rpm Std Maximum Continuous Bhp Std Maximum Continuous Watts Alt Maximum Continuous Bhp Alt Maximum Continuous Watts Motor Frame Size Standard Motor Frame Size Alternate Fan Drive Rpm Range Std motor/Std drive
Motor Bearing Type Maximum Allowable Rpm Motor Pulley Pitch Diameter Std motor/Std drive
Motor Shaft Diameter (in.) Standard Motor Shaft Diameter (in.) Alternate Belt, Quantity...Type...Length (in.) Std motor/Std drive
Pulley center line distance (in.) Speed change per full turn of moveable
pulley flange (rpm) Std motor/Std drive
Moveable pulley maximum (full turns
from closed position)
Factory Pulley Setting
(turns from closed position) Fan Shaft Diameter (in.) Factory Speed Setting (rpm)
HIGH PRESSURE SWITCHES (psig)
Cutout Reset (Auto)
OUTDOOR AIR INLET SCREENS
Quantity...Size (in.)
RETURN AIR FILTERS
Quantity...Size (in.)
Std motor/Alt drive Alt motor/Std drive Alt motor/Alt drive
Std motor/Alt drive Alt motor/Std drive Alt motor/Alt drive
Std motor/Alt drive Alt motor/Std drive Alt motor/Alt drive
Std motor/Alt drive Alt motor/Std drive Alt motor/Alt drive
LEGEND
Brake Horsepower
Bhp
Thermostatic Expansion Valve
TXV
208/230 and 460
575
208/230 and 460
575
208/230 and 460
12.5 12.5 15 15 17.5 17.5
2017 2017 2111 2111 2139 2139
2 2 3333 2 2 3333
72...72...NA 72...72...NA 68...68...68 68...68...68 68...68...72 68...68...72
TXV TXV TXV TXV TXV TXV
19.6 19.6 13.2 13.2 13.1 13.1
18.3 18.3 12.2 12.2 12.7 12.7 NA NA 15.4 15.4 15.2 15.2
2...17 2...17 2...17 2...17 2...17 2...17
57.78 57.78 57.78 57.78 57.78 57.78
14,000 14,000 14,000 14,000 14,000 14,000
4...22 4...22 4...22 4...22 4...22 4...22
1
/4...1100
1400 1400 1400 1400 1400 1400
3...15 3...15 3...15 3...15 3...15 3...15
23.33 23.33 23.33 23.33 23.33 23.33
2...15x11 2...15x11 2...15x11 2...15x11 2...15x11 2...15x11 Belt Belt Belt Belt Belt Belt
5000 5000 6000 6000 7000 7000
3.7 3 3.7 3 5 5 55557
1725 1725 1725 1725 1725 1725
4.25 3.45 4.25 3.45 5.75 5.75
3171 2574 3171 2574 4290 4290
5.75 5.75 5.75 5.75 8.63 8.63
4290 4290 4290 4290 6438 6438
56HZ 56H 56HZ 56H S184T 184T
S184T 184T S184T 184T S213T S213T 485-613 472-619 618-789 609-778 658-808 658-808 618-789 609-778 485-613 472-619 794-974 794-974
778-1021 778-1021 778-1021 778-1021 949-1145 949-1145
1000-1227 1000-1227 1000-1227 1000-1227 1126-1328 1126-1328
Ball Ball Ball Ball Ball Ball
1400 1400 1400 1400 1400 1400
3.7-4.7 3.1-4.1 3.4-4.4 3.4-4.4 4.3-5.3 4.3-5.3
3.4-4.4 3.4-4.4 3.7-4.7 3.1-4.1 4.3-5.3 4.3-5.3
3.1-4.1 3.1-4.1 3.1-4.1 3.1-4.1 5.4-6.6 5.4-6.6
4.3-5.3 4.3-5.3 4.3-5.3 4.3-5.3 5.5-6.5 5.5-6.5
7
/
8
1
/
1
8
1...BX...51 1...BX...48 1...A...45 1...A...45 1...BX...46 1...BX...46
1...A...45 1...A...45 1...BX...51 1...BX...48 1...BX...42 1...BX...42
1...BX...38 1...BX...38 1...BX...38 1...BX...38 1...BX...46 1...BX...46
1...B...38 1...B...38 1...B...38 1...B...38 1...BX...42 1...BX...42
11.3-12.3 11.3-12.3 11.3-12.3 11.3-12.3 10.0-12.2 10.0-12.2
21 25 29 28 25 25 29 28 21 25 30 30 41 41 41 41 33 33 38 38 38 38 34 34
6 6 6666
3 3 3333
3
/
1
16
549 546 704 694 733 733
426 426 426 426 426 426 320 320 320 320 320 320
1
/4...1100
7
/
8
11/
13/
16
8
R-22
1
/4...11001/4...11001/4...11001/4...1100
Face Split
1
/
2
7
/
8
11/
8
13/
16
7
/
8
11/
8
13/
16
13/
11/ 13/
8
8
16
3...20x25 3...20x25 3...20x25 3...20x25 3...20x25 3...20x25
9...16x25 9...16x25 9...16x25 9...16x25 9...16x25 9...16x25
575
71/
11/ 13/
13/
2
8
8
16
6
Table 1 Physical Data (cont)
UNIT 50HG 024 028
VOLTAGE
NOMINAL CAPACITY (Tons) OPERATING WEIGHT (lb)
50 SERIES (Cooling Only) COMPRESSOR
Quantity Number of Refrigerant Circuits Oil (ounces) Ckt A...Ckt B...Ckt C
REFRIGERANT TYPE
Expansion Device Operating Charge (lb)
Circuit A Circuit B Circuit C
CONDENSER COIL
Rows...Fins/inch TotalFaceArea(sq.ft)
CONDENSER FAN
Nominal Cfm (Total, all fans) Quantity...Diameter (in.) Motor Hp...Rpm Watts input (Total)
EVAPORATOR COIL
Rows...Fins/inch TotalFaceArea(sq.ft)
EVAPORATOR FAN
Quantity...Size Typ e Dri ve Nominal Cfm Std Motor Hp Alt Motor Hp Motor Nominal Rpm Std Maximum Continuous Bhp Std Maximum Continuous Watts Alt Maximum Continuous Bhp Alt Maximum Continuous Watts Motor Frame Size Standard Motor Frame Size Alternate Fan Drive Rpm Range Std motor/Std drive
Motor Bearing Type Maximum Allowable Rpm Motor Pulley Pitch Diameter Std motor/Std drive
Motor Shaft Diameter (in.) Standard Motor Shaft Diameter (in.) Alternate Belt, Quantity...Type...Length (in.) Std motor/Std drive
Pulley center line distance (in.) Speed change per full turn of moveable
pulley flange (rpm) Std motor/Std drive
Moveable pulley maximum (full turns
from closed position)
Factory Pulley Setting
(turns from closed position) Fan Shaft Diameter (in.) Factory Speed Setting (rpm)
HIGH PRESSURE SWITCHES (psig)
Cutout Reset (Auto)
OUTDOOR AIR INLET SCREENS
Quantity...Size (in.)
RETURN AIR FILTERS
Quantity...Size (in.)
Std motor/Alt drive Alt motor/Std drive Alt motor/Alt drive
Std motor/Alt drive Alt motor/Std drive Alt motor/Alt drive
Std motor/Alt drive Alt motor/Std drive Alt motor/Alt drive
Std motor/Alt drive Alt motor/Std drive Alt motor/Alt drive
LEGEND
Bhp TXV
Brake Horsepower Thermostatic Expansion Valve
208/230 and 460
575 ALL
20 20 25
2187 2187 2446
33 2 33 2
72...72...72 72...72...72 110...110...NA
TXV TXV TXV
13.8 13.8 23.9
13.9 13.9 21.5
15.5 15.5 NA
2...17 2...17 2...17
57.78 57.78 66.67
14,000 14,000 21,000
4...22 4...22 6...22
1
/4...1100
1400 1400 2100
4...15 4...15 4...15
23.33 23.33 27.22
2...15x11 2...15x11 2...15x11 Belt Belt Belt
8000 8000 10,000
557
1
/
7
2
1725 1725 1725
5.75 5.75 8.63 4290 4290 6438
8.63 8.63 11.50
6438 6438 8579 S184T 184T S213T S213T S213T S215T
658-808 658-808 799-965 794-974 794-974 939-1152
949-1145 949-1145 945-1187
1126-1328 1126-1328 1152-1366
Ball Ball Ball
1400 1400 1400
4.3-5.3 4.3-5.3 5.4-6.6
4.3-5.3 4.3-5.3 4.2-5.2
5.4-6.6 5.4-6.6 4.2-5.2
5.5-6.5 5.5-6.5 5.2-6.2
1
/
1
8
3
/
1
8
1...BX...46 1...BX...46 1...BX...50
1...BX...42 1...BX...42 2...AX...38
1...BX...46 1...BX...46 2...BX...38
1...BX...42 1...BX...42 2...BX...38
10.0-12.2 10.0-12.2 9.6-12.0
25 25 28 30 30 36 33 33 40 34 34 36
66 6
33 3
3
/
1
16
733 733 882
426 426 426 320 320 320
R-22
1
/4...1100
Face Split
71/
2
11/
8
13/
8
13/
16
1
/4...1100
13/
3...20x25 3...20x25 3...20x25
9...16x25 9...16x25 9...20x25
13/ 13/
1
/
2
10
8
8
16
7
ALIGNMENT
HOLE
(IN BASE RAIL)
EDGE FLANGE
Fig. 5 Alignment Hole Details
ALIGNMENT
HOLE SHOULD
LINE UP WITH
ROOF CURB
EDGE FLANGE
HORIZONTAL APPLICATIONS Horizontal units are shipped with outer panels that allow for side by side horizontal duct connections. If specified during ordering, the unit will be shipped with the vertical duct openings blocked off from the factory, ready for side supply installation. If the horizontal option was not specified at time of ordering the unit, a field­installed accessory kit is required to convert the vertical unit into a horizontal supply configuration.
Installation of the duct block-off covers should be complet­ed prior to placing the unit unless sufficient side clearance is available. A minimum of 66-in. is required between the unit and any obstruction to install the duct block-off covers. Side supply duct dimensions and locations are shown on Fig. 4. Connect ductwork to horizontal duct flange connections on side of unit.
ALIGNMENT HOLES FOR
HJ, TJ, DP, DR
CURB-BOTH
SIDES
SUPPLY
OPENING
CURB SUPPLY OPENING
ALIGNMENT
HOLES FOR HG
CURB-BOTH
SIDES
RETURN
OPENING
CURB RETURN OPENING
ROOF CURB
Fig. 6 Alignment Hole Location
Step 4 Field Fabricate Ductwork
Secure all ducts to building structure. Use flexible duct connectors be­tween unit and ducts as required. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be in-
sulated and covered with a vapor barrier.
Step 5 Make Unit Duct Connections
VERTICAL CONFIGURATION Unit is shipped for thru­the-bottom duct connections. Ductwork openings are shown in Fig. 1 and 4. Duct connections for vertical supply and return configuration are shown in Fig. 7. Field fabricat ed concentric ductwork may be connected as shown in Fig. 8 and 9. The unit is designed to attach the ductwork to the roof curb. Do not attach duct directly to the unit basepans.
Unit basepans must be supported under the unit and around
duct openings in order to prevent air leakage.
ECONOMIZER
SEE NOTE
AIR
IN
NOTE: Do not drill in this area; damage to basepan may result in water leak.
SEE NOTE
AIR
OUT
Fig. 7 Air Distribution Vertical Supply and Return
ECONOMIZER
For vertical supply and return units, tools or parts could drop into ductwork and cause an injury. Install a 90-degree turn in the return ductwork between the unit and the condi­tioned space. If a 90-degree elbow cannot be installed, then a grille of sufficient strength a nd density should be in stalled to prevent objects from falling into the conditioned space.
Units with electric heat require a 1-in. clearance for the first 24 in. of ductwork. Outlet grilles must not lie directly below unit discharge.
NOTE: A 90-degree elbow must be provided in the supply ductwork to comply with UL (Underwriters Laboratories) codes for use with electric heat.
AIR OUT
SEE NOTE
SEE NOTE
AIR OUT
NOTE: Do not drill in this area; damage to basepan may result in water leak.
AIR IN
Fig. 8 Air Distribution Concentric Duct
8
Loading...
+ 16 hidden pages