Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance
functions of replacing filters. All other operations should
be performed by trained service personnel. When working
on air-conditioning equipment, observe precautions in the
literature, tags and labels attached to the unit, and other safety
precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
Before performing service or maintenance operations on
unit, turn off main power swit ch to unit. Electrical shock
could cause personal injury.
IMPORTANT: Units have high ambient operating lim-
its. If limits are exceede d, the units will automatically
lock the compressor out of operation. Manual r eset will
be required to restart the compressor.
INSTALLATION
Step 1 — Provide Unit Support
ROOF CURB — Assemble or install accessory roof curb in
accordance with instructions shipped with this accessory. See
Fig. 1. Install insulation, cant strips, roofing, and counter flashing as shown. Ductwork can be installed to roof curb before
unit is set in place. Curb must be level. This is necessary to
permit unit drain to function properly. Unit leveling tolerance is
1
/16 in. per linear ft in any direction. Refer to Accessory
±
Roof Curb Installation Instructions for additional information
as required. When accessory roof curb i s used, unit may be
installed on class A, B, or C roof covering material.
IMPOR TANT: The gasketing of the unit to the roof curb
is critical for a watertight seal. Install gasket with the
roof curb as shown in Fig. 1. Improperly applied gasket
can also result in air leaks and poor unit performance.
ALTERNATE UNIT SUPPORT — When a curb cannot be
used, install unit on a noncombustible surface. Support unit
with sleepers, using unit curb support area. If sleepers cannot
be used, support long sides of unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Ta b 1b 6 b
PC 111Catalog No. 535-00092Printed in U.S.A.Form 50HG-7SIPg 111-03Replaces: 50HG-3SI
Fig. 1 — Roof Curb Details
2
Step 2 — Remove Shipping Rails —
Remove shipping rails prior to lowering unit onto roof curb. See Fig. 2. The
rails are attached to the unit at both the return end and condenser end. Remove the screws from both ends of each rail. Be
careful not to drop the rails onto any surface that could be damaged. Discard the rails. It is important to replace the screws into
the unit to avoid any air or water leakage.
Do not allow the shipping rail to drop on the roof surface.
Damage to the roof surface may result.
Step 3 — Rig and Place Unit —
Inspect unit for transportation damage. See Table 1 for physical data. File any claim
with transportation agency.
All panels must be in place when rigging. Unit is not
designed for handling by fork truck. Damage to unit can
result.
Do not drop unit; keep upright. Use spreader bars over unit
to prevent sling or cable damage. Rollers may be used to move
unit across a roof. Level by using unit frame as a refere nce;
leveling tolerance is ±
1
/16 in. per linear ft in any direction. See
Fig. 3 for additional information. Unit rigging weight is shown
in Fig. 3.
Four lifting holes are provided in the unit base rails as
shown in Fig. 3. Refer to rigging instructions on unit.
POSITIONING — Maintain clearance, per Fig. 4, around and
above unit to provide minimum distance from combustible
materials, proper airflow, and service access.
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
ROOF MOUNT — Check building codes for weight distribu-
tion requirements. Unit operating weight is shown in Table 1.
INSTALLATION ONTO CURB — The 50HG units are
designed to fit on either the accessory full perimeter curb or
onto existing 48/50TJ,HJ or 48/50DP,DR curbs. In either case,
correct placement of the unit onto th e curb is critical to operating performance. To aid in correct positioning,
3
/8-in. diameter
locating holes have been added to the unit base rails. When
placing the unit, these holes should line up with the roof curb
edge as shown in Fig. 5 and 6, to assure proper duct opening
alignment. Select the alignment holes suited for the curb being
used. For installation on the HJ/TJ/DP/DR curb use the alignment holes located approximately 20 in. from the end of t he
base rail on the return end of the unit. For placement on the HG
curb, use the alignment holes located approximately 2-in. from
the end of the base rail on the return end of the unit. See labels
on the side of the unit for more details.
SHIPPING RAILS
Fig. 2 — Shipping Rail Removal
3
Fig. 3 — Rigging Details
4
Fig. 4 — Base Unit Dimensions
5
Table 1 — Physical Data
UNIT 50HG014016020
VOLTAGE
NOMINAL CAPACITY (Tons)
OPERATING WEIGHT (lb)
50 SERIES (Cooling Only)
COMPRESSOR
Quantity
Number of Refrigerant Circuits
Oil (ounces) Ckt A...Ckt B...Ckt C
REFRIGERANT TYPE
Expansion Device
Operating Charge (lb)
Circuit A
Circuit B
Circuit C
CONDENSER COIL
Rows...Fins/inch
TotalFacearea(sq.ft)
CONDENSER FAN
Nominal Cfm (Total, all fans)
Quantity...Diameter (in.)
Motor Hp...Rpm
Watts input (Total)
EVAPORATOR COIL
Rows...Fins/inch
TotalFacearea(sq.ft)
EVAPORATOR FAN
Quantity...Size
Typ e Drive
Nominal Cfm
Std Motor Hp
Alt Motor Hp
Motor Nominal Rpm
Std Maximum Continuous Bhp
Std Maximum Continuous Watts
Alt Maximum Continuous Bhp
Alt Maximum Continuous Watts
Motor Frame SizeStandard
Motor Frame SizeAlternate
Fan Drive Rpm RangeStd motor/Std drive
Motor Bearing Type
Maximum Allowable Rpm
Motor Pulley Pitch DiameterStd motor/Std drive
Motor Shaft Diameter (in.)Standard
Motor Shaft Diameter (in.)Alternate
Belt, Quantity...Type...Length (in.)Std motor/Std drive
Pulley center line distance (in.)
Speed change per full turn of moveable
pulley flange (rpm)Std motor/Std drive
Moveable pulley maximum (full turns
from closed position)
Factory Pulley Setting
(turns from closed position)
Fan Shaft Diameter (in.)
Factory Speed Setting (rpm)
HIGH PRESSURE SWITCHES (psig)
Cutout
Reset (Auto)
OUTDOOR AIR INLET SCREENS
Quantity...Size (in.)
RETURN AIR FILTERS
Quantity...Size (in.)
Std motor/Alt drive
Alt motor/Std drive
Alt motor/Alt drive
Std motor/Alt drive
Alt motor/Std drive
Alt motor/Alt drive
Std motor/Alt drive
Alt motor/Std drive
Alt motor/Alt drive
Std motor/Alt drive
Alt motor/Std drive
Alt motor/Alt drive
Quantity
Number of Refrigerant Circuits
Oil (ounces) Ckt A...Ckt B...Ckt C
REFRIGERANT TYPE
Expansion Device
Operating Charge (lb)
Circuit A
Circuit B
Circuit C
CONDENSER COIL
Rows...Fins/inch
TotalFaceArea(sq.ft)
CONDENSER FAN
Nominal Cfm (Total, all fans)
Quantity...Diameter (in.)
Motor Hp...Rpm
Watts input (Total)
EVAPORATOR COIL
Rows...Fins/inch
TotalFaceArea(sq.ft)
EVAPORATOR FAN
Quantity...Size
Typ e Dri ve
Nominal Cfm
Std Motor Hp
Alt Motor Hp
Motor Nominal Rpm
Std Maximum Continuous Bhp
Std Maximum Continuous Watts
Alt Maximum Continuous Bhp
Alt Maximum Continuous Watts
Motor Frame SizeStandard
Motor Frame SizeAlternate
Fan Drive Rpm RangeStd motor/Std drive
Motor Bearing Type
Maximum Allowable Rpm
Motor Pulley Pitch DiameterStd motor/Std drive
Motor Shaft Diameter (in.)Standard
Motor Shaft Diameter (in.)Alternate
Belt, Quantity...Type...Length (in.)Std motor/Std drive
Pulley center line distance (in.)
Speed change per full turn of moveable
pulley flange (rpm)Std motor/Std drive
Moveable pulley maximum (full turns
from closed position)
Factory Pulley Setting
(turns from closed position)
Fan Shaft Diameter (in.)
Factory Speed Setting (rpm)
HIGH PRESSURE SWITCHES (psig)
Cutout
Reset (Auto)
OUTDOOR AIR INLET SCREENS
Quantity...Size (in.)
RETURN AIR FILTERS
Quantity...Size (in.)
Std motor/Alt drive
Alt motor/Std drive
Alt motor/Alt drive
Std motor/Alt drive
Alt motor/Std drive
Alt motor/Alt drive
Std motor/Alt drive
Alt motor/Std drive
Alt motor/Alt drive
Std motor/Alt drive
Alt motor/Std drive
Alt motor/Alt drive
LEGEND
Bhp —
TXV —
Brake Horsepower
Thermostatic Expansion Valve
208/230
and 460
575ALL
202025
218721872446
33 2
33 2
72...72...7272...72...72110...110...NA
TXVTXVTXV
13.813.823.9
13.913.921.5
15.515.5NA
2...172...172...17
57.7857.7866.67
14,00014,00021,000
4...224...226...22
1
/4...1100
140014002100
4...154...154...15
23.3323.3327.22
2...15x112...15x112...15x11
BeltBeltBelt
8000800010,000
557
1
/
7
2
172517251725
5.755.758.63
429042906438
8.638.6311.50
643864388579
S184T184TS213T
S213TS213TS215T
658-808658-808799-965
794-974794-974939-1152
949-1145949-1145945-1187
1126-13281126-13281152-1366
BallBallBall
140014001400
4.3-5.34.3-5.35.4-6.6
4.3-5.34.3-5.34.2-5.2
5.4-6.65.4-6.64.2-5.2
5.5-6.55.5-6.55.2-6.2
1
/
1
8
3
/
1
8
1...BX...461...BX...461...BX...50
1...BX...421...BX...422...AX...38
1...BX...461...BX...462...BX...38
1...BX...421...BX...422...BX...38
10.0-12.210.0-12.29.6-12.0
252528
303036
333340
343436
66 6
33 3
3
/
1
16
733733882
426426426
320320320
R-22
1
/4...1100
Face Split
71/
2
11/
8
13/
8
13/
16
1
/4...1100
13/
3...20x253...20x253...20x25
9...16x259...16x259...20x25
13/
13/
1
/
2
10
8
8
16
7
ALIGNMENT
HOLE
(IN BASE RAIL)
EDGE FLANGE
Fig. 5 — Alignment Hole Details
ALIGNMENT
HOLE SHOULD
LINE UP WITH
ROOF CURB
EDGE FLANGE
HORIZONTAL APPLICATIONS — Horizontal units are
shipped with outer panels that allow for side by side horizontal
duct connections. If specified during ordering, the unit will be
shipped with the vertical duct openings blocked off from the
factory, ready for side supply installation. If the horizontal
option was not specified at time of ordering the unit, a fieldinstalled accessory kit is required to convert the vertical unit
into a horizontal supply configuration.
Installation of the duct block-off covers should be completed prior to placing the unit unless sufficient side clearance is
available. A minimum of 66-in. is required between the unit
and any obstruction to install the duct block-off covers. Side
supply duct dimensions and locations are shown on Fig. 4.
Connect ductwork to horizontal duct flange connections on
side of unit.
ALIGNMENT
HOLES FOR
HJ, TJ, DP, DR
CURB-BOTH
SIDES
SUPPLY
OPENING
CURB
SUPPLY
OPENING
ALIGNMENT
HOLES FOR HG
CURB-BOTH
SIDES
RETURN
OPENING
CURB
RETURN
OPENING
ROOF CURB
Fig. 6 — Alignment Hole Location
Step 4 — Field Fabricate Ductwork —
Secure all
ducts to building structure. Use flexible duct connectors between unit and ducts as required. Insulate and weatherproof all
external ductwork, joints, and roof openings with counter
flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be in-
sulated and covered with a vapor barrier.
Step 5 — Make Unit Duct Connections
VERTICAL CONFIGURATION — Unit is shipped for thruthe-bottom duct connections. Ductwork openings are shown in
Fig. 1 and 4. Duct connections for vertical supply and return
configuration are shown in Fig. 7. Field fabricat ed concentric
ductwork may be connected as shown in Fig. 8 and 9. The unit
is designed to attach the ductwork to the roof curb. Do not
attach duct directly to the unit basepans.
Unit basepans must be supported under the unit and around
duct openings in order to prevent air leakage.
ECONOMIZER
SEE
NOTE
AIR
IN
NOTE: Do not drill in this area; damage to basepan may result in
water leak.
SEE
NOTE
AIR
OUT
Fig. 7 — Air Distribution —
Vertical Supply and Return
ECONOMIZER
For vertical supply and return units, tools or parts could
drop into ductwork and cause an injury. Install a 90-degree
turn in the return ductwork between the unit and the conditioned space. If a 90-degree elbow cannot be installed, then
a grille of sufficient strength a nd density should be in stalled
to prevent objects from falling into the conditioned space.
Units with electric heat require a 1-in. clearance for the first
24 in. of ductwork. Outlet grilles must not lie directly below
unit discharge.
NOTE: A 90-degree elbow must be provided in the supply
ductwork to comply with UL (Underwriters’ Laboratories)
codes for use with electric heat.
AIR OUT
SEE
NOTE
SEE
NOTE
AIR OUT
NOTE: Do not drill in this area; damage to basepan may result in
water leak.
AIR IN
Fig. 8 — Air Distribution — Concentric Duct
8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.