Carrier 50HC14 User Manual

Page 1
WeatherMaster
50HC14
Single Package Rooftop Cooling Only Unit
®
with Puron
(R-410A) Refrigerant
Installation Instructions
50HC units for installation in the United States contain use of Carrier's Staged Air Volume (SAV™) 2-speed indoor fan control system. This complies with the U.S. Department of Energy (DOE) efficiency standard of
2018. 50HC units for installation outside the United States may or may not contain use of the SAV 2-speed indoor fan control system as they are not required to comply with the U.S. Department of Energy (DOE) efficiency standard of 2018. For specific details on operation of the Carrier SAV 2-speed indoor fan system refer to the Variable Frequency Drive (VFD) Factory-Installed Option 2-Speed Motor Control Installation, Setup, and Troubleshooting manual.
®

CONTENTS

Page
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . 1-6
Rated Indoor Airflow (cfm) . . . . . . . . . . . . . . . . . . . . . . ..2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-63
Step 1 — Plan for Unit Location . . . . . . . . . . . . . . . . . . 6
Step 2 — Plan for Sequence of Unit Installation . 6
Step 3 — Inspect Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Step 4 — Provide Unit Support. . . . . . . . . . . . . . . . . . . 7
Step 5 — Field Fabricate Ductwork. . . . . . . . . . . . . . . 9
Step 6 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 9
Step 7 — Convert to Horizontal and Connect
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Step 8 — Install Outside Air Hood . . . . . . . . . . . . . . . 11
Step 9 — Install External Condensate Trap and
Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Step 10 — Make Electrical Connections . . . . . . . . . 13
Electric Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Single Point Boxes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Humidi-MiZer EconoMi$er
Low Ambient Control (Factory Option) . . . . . . . . . 37
Staged Air Volume (SAV) with Variable Frequency
Drive (Factory Option) . . . . . . . . . . . . . . . . . . . . . . . 37
ComfortLink Controls (Factory Option) . . . . . . . . . 37
PremierLink Controller (Factory Option) . . . . . . . . 42
Supply Air Temperature Sensor . . . . . . . . . . . . . . . . . 45
Field Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Economizer Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
RTU Open Control System . . . . . . . . . . . . . . . . . . . . . . 52
Field Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Communication Wiring — Protocols . . . . . . . . . . . . 58
Local Access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Outdoor Air Enthalpy Control . . . . . . . . . . . . . . . . . . . 60
Smoke Detectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Step 11 — Adjust Factory-Installed Options. . . . . 62
Step 12 — Install Accessories. . . . . . . . . . . . . . . . . . . 62
Pre-Start and Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
START-UP CHECKLIST . . . . . . . . . . . . . . . . . CL-1, CL-2
®
System Control Connections . . . . 22
®
X (Factory-Installed Option) . . . . . . . 24

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, main­tenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The quali­fied installer or agency must use factory-authorized kits or ac­cessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Con­sult local building codes and appropriate national electrical codes (in USA, ANSI/NFPA 70, National Electrical Code (NEC); in Canada, CSA C22.1) for special requirements.
It is important to recognize safety information. This is the safety-alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for per­sonal injury.
Understand the signal words DANGER, WARNING, CAU­TION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signi­fies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may re­sult in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in en­hanced installation, reliability, or operation.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on unit, always turn off main power switch to unit and install lock(s) and lockout tag(s). Unit may have more than one power switch.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500157-01 Printed in U.S.A. Form 50HC-14-02SI Pg 1 12-17 Replaces: 50HC-14-01SI
Page 2
WARNING
CAUTION
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury, death and/or equipment damage.
®
Puron
(R-410A) refrigerant systems operate at higher pressures than standard R-22 systems. Do not use R-22 ser­vice equipment or components on Puron refrigerant equip­ment.
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could cause personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrig­erants and oils.
CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing air-conditioning equipment.
Rated Indoor Airflow (cfm) — The table below lists
the rated indoor airflow used for the AHRI efficiency rating for the units covered in this document.
MODEL NUMBER
50HC*D/E/G14 4375
FULL LOAD AIRFLOW
(CFM)
2
Page 3
50HCBD14A2A6A0A3B0
Cooling Tons
14 - 12.5 ton
1
Example:
Position: 2 3 4 5 6 7 8 9
10
11 12 13 14 15 16 17 18
Heat Options
- - None (Field Installed Accessory) A = Low Electric Heat B = Medium Electric Heat C = High Electric Heat
Sens or Options
A = None B = RA Smoke Detector C = SA Smoke Detector D = RA + SA Smoke Detector E = CO
2
F = RA Smoke Detector and CO
2
G = SA Smoke Detector and CO
2
H = RA + SA Smoke Detector and CO
2
Indoor Fan Options
1 = Standard Static Option - Belt Dirve 2 = Medium Static Option - Belt Drive C = High Static Option with High Efficency Motor - Belt Drive
Coil Options (RTPF) (Outdoor - Indoor - Hail Guard)
A = Al/Cu - Al/Cu B = Precoat Al/Cu - Al/Cu C = E-coat Al/Cu - Al/Cu D = E-coat Al/Cu - E-coat Al/Cu E = Cu/Cu - Al/Cu F = Cu/Cu - Cu/Cu M = Al/Cu -Al/Cu — Louvered Hail Guard N = Precoat Al/Cu - Al/Cu — Louvered Hail Guard P = E-coat Al/Cu - Al/Cu — Louvered Hail Guard Q = E-coat Al/Cu - E-coat Al/Cu — Louvered Hail Guard R = Cu/Cu - Al/Cu — Louvered Hail Guard S = Cu/Cu - Cu/Cu — Louvered Hail Guard
Voltage
1 = 575/3/60 5 = 208-230/3/60 6 = 460/3/60
Design Revision
A = Factory Design Revision
Base Unit Controls
0 = Electro-mechanical Controls Can be used with W7212 EconoMi$er IV (Non-Fault Detection and Diagnostic) 1 = PremierLink Controller 2 = RTU Open Multi-Protocol Controller 6 = Electro-mechanical with 2-speed fan and W7220 Econo controller Controls. Can be used with W7220 EconoMi$er X (with Fault Detection and Diagnostic) D = ComfortLink Controls
Intake / Exhaust Options
A = None B = Temperature Economizer w/ Barometric Relief F = Enthalpy Economizer w/ Barometric Relief K = 2-Position Damper U = Low Leak Temperature Economizer w/ Barometric Relief W = Low Leak Enthalpy Economizer w/ Barometric Relief
Service Options
0 = None 1 = Unpowered Convenience Outlet 2 = Powered Convenience Outlet 3 = Hinged Panels 4 = Hinged Panels and Unpowered Convenience Outlet 5 = Hinged Panels and Powered Convenience Outlet C = Foil Faced Insulation D = Foil Faced Insulation with Unpowered Convenience Outlet E = Foil Faced Insulation with Powered Convenience Outlet F = Foil Faced Insulation & Hinged Panels G = Foil Faced Insulation & Hinged Panels with Unpowered Convenience Outlet H = Foil Faced Insulation & Hinged Panels with Powered Convenience Outlet
Factory Assigned
0 = Standard 1 = LTL
Electrical Options
A = None B = HACR Breaker C = Non-Fused Disconnect D = Thru-The-Base Connections E = HACR and Thru-The-Base Connections F = Non-Fused Disconnect and Thru-The-Base Connections G = 2-Speed Indoor Fan (VFD) Controller H = 2-Speed Fan Controller (VFD) and HACR J = 2-Speed Fan Controller (VFD) and Non-Fused Disconnect K = 2-Speed Fan Controller (VFD) and Thru-The-Base Connections L = HACR w/ Thru-The-Base & 2-Speed Fan Controller (VFD) M = 2-Speed Fan Controller (VFD) with Non-Fused Disconnect and Thru-The-Base Connections
Refrig. Syste ms Options
D = Two stage cooling models E = Two stage cooling models with Humidi-MiZer G = Two stage cooling models with MotorMaster Low Ambient Controller
Model Series - WeatherMaster
®
HC - High Efficiency
Unit Heat Type
50 - Electric Heat Packaged Rooftop
Fig. 1 — 50HC 14 Model Number Nomenclature (Example)
3
Page 4
Fig. 2 — Unit Dimensional Drawing — 14 Size Unit
4
Page 5
HORIZONTAL ECONOMIZER
VERTICAL ECONOMIZER
Fig. 2 — Unit Dimensional Drawing — 14 Size Unit (cont)
5
Page 6
NOTE: Unit not designed to have overhead obstruction. Contact Application Engineering for guidance on any application planning overhead obstruction or for vertical clearances.
LOCATION DIMENSION CONDITION
A
48-in. (1219 mm) 18-in. (457 mm) 18-in. (457 mm) 12-in. (305 mm)
Unit disconnect is mounted on panel No disconnect, convenience outlet option Recommended service clearance Minimum clearance
B
42-in. (1067 mm) 36-in. (914 mm)
Surface behind servicer is grounded (e.g., metal, masonry wall) Surface behind servicer is electrically non-conductive (e.g., wood, fiberglass)
C
36-in. (914 mm) 18-in. (457 mm)
Side condensate drain is used Minimum clearance
D
42-in. (1067 mm) 36-in. (914 mm)
Surface behind servicer is grounded (e.g., metal, masonry wall, another unit) Surface behind servicer is electrically non-conductive (e.g., wood, fiberglass)
C
D
B
A
Fig. 3 — Service Clearance Dimensional Drawing

INSTALLATION

Jobsite Survey —
installation.
1. Consult local building codes and the NEC (National Electrical Code) ANSI/NFPA 70 for special installation requirements.
2. Determine unit location (from project plans) or select unit location.
3. Check for possible overhead obstructions which may in­terfere with unit lifting or rigging.
Complete the following checks before
Step 1 — Plan for Unit Location — Select a loca-
tion for the unit and its support system (curb or other) that pro­vides for at least the minimum clearances required for safety. This includes the clearance to combustible surfaces, unit per­formance and service access below, around and above unit as specified in unit drawings. See Fig. 3.
NOTE: Consider also the effect of adjacent units.
Unit may be installed directly on wood flooring or on Class
A, B, or C roof-covering material when roof curb is used.
Do not install unit in an indoor location. Do not locate air in­lets near exhaust vents, relief valves, or other sources of con­taminated air.
Although unit is weatherproof, avoid locations that permit water from higher level runoff and overhangs to fall onto the unit.
6
Select a unit mounting system that provides adequate height to allow installation of condensate trap per requirements. Refer to Step 9 — Install External Condensate Trap and Line for re­quired trap dimensions.
ROOF MOUNT — Check building codes for weight distri­bution requirements. Unit operating weight is shown in Table 1.
Table 1 — Operating Weights
50HC**14
COMPONENT UNITS LB (KG)
Base Unit
Economizer
Vertical
Horizontal
Humidi-MiZer System
Powered Outlet
Curb
14-in. (356 mm)
24-in. (610 mm)
1360 (617)
103 (47)
242 (110)
90 (41)
35 (16)
180 (82)
255 (116)
Step 2 — Plan for Sequence of Unit Installa­tion —
ferent sequences for the steps of unit installation. For example, on curb-mounted units, some accessories must be installed on the unit before the unit is placed on the curb. Review the fol­lowing for recommended sequences for installation steps.
The support method used for this unit will dictate dif-
Page 7

CURB-MOUNTED INSTALLATION

Install curb Install field-fabricated ductwork inside curb
Install accessory thru-base service connection package (af­fects curb and unit) (refer to accessory installation instructions for details)
Prepare bottom condensate drain connection to suit planned condensate line routing (refer to Step 9 for details)
Rig and place unit
Install outdoor air hood
Install condensate line trap and piping
Make electrical connections
Install other accessories

PAD-MOUNTED INSTALLATION

Prepare pad and unit supports
Check and tighten the bottom condensate drain connection plug
Rig and place unit
Convert unit to side duct connection arrangement
Install field-fabricated ductwork at unit duct openings
Install outdoor air hood
Install condensate line trap and piping
Make electrical connections
Install other accessories
FRAME-MOUNTED INSTALLATION — Frame-mount­ed applications generally follow the sequence for a curb instal­lation. Adapt as required to suit specific installation plan.
Step 3 — Inspect Unit — Inspect unit for transporta-
tion damage. File any claim with transportation agency.
Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.
On units with hinged panel option, check to be sure all latches are snug and in closed position.
Locate the carton containing the outside air hood parts; see Fig. 11 and 12. Do not remove carton until unit has been rigged and located in final position.

Step 4 — Provide Unit Support

ROOF CURB MOUNT — Accessory roof curb details and dimensions are shown in Fig. 4. Assemble and install accesso­ry roof curb in accordance with instructions shipped with the curb.
NOTE: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 4. Improperly applied gasket can also result in air leaks and poor unit performance.
Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are show in Fig. 5. Refer to Accessory Roof Curb Installation Instructions for ad­ditional information as required.
7
Page 8
Fig. 4 — Roof Curb Details
8
Page 9
MAXIMUM ALLOWABLE DIFFERENCE IN. (MM)
A-B B-C A-C
0.5" (13) 1.0" (25) 1.0" (25)
A
B
C
Fig. 5 — Unit Leveling Tolerances
Install insulation, cant strips, roofing felt, and counter flash­ing as shown. Ductwork must be attached to curb and not to the unit.
IMPORTANT: If the unit’s electric and control wiring is to be routed through the basepan and the unit is equipped with the factory-installed Thru-the-Base service option see the following sections:
• Factory-Option Thru-Base Connections on page 19 If using the field-installed Thru-the-Base accessory follow
the instructions provided with the accessory kit.
NOTE: If electrical connection is not going to occur at this time, tape or otherwise cover the fittings so that moisture does not get into the building or conduit in the interim.
SLAB MOUNT (HORIZONTAL UNITS ONLY) — Pro­vide a level concrete slab that extends a minimum of 6 in. (150 mm) beyond unit cabinet. Install a gravel apron in front of con­denser coil air inlet to prevent grass and foliage from obstruct­ing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR SLAB MOUNT) — A non-combustible sleeper rail can be
used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. (102 mm x 102 mm) pads on each side.

Step 5 — Field Fabricate Ductwork

NOTE: Cabinet return-air static pressure (a negative condition) shall not exceed 0.35 in. wg (87 Pa) with economizer or 0.45 in. wg (112 Pa) without economizer.
For vertical ducted applications, secure all ducts to roof curb and building structure. Do not connect ductwork to unit.
Fabricate supply ductwork so that the cross sectional di­mensions are equal to or greater than the unit supply duct open­ing dimensions for the first 18 in. (458 mm) of duct length from the unit basepan.
Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through unconditioned spaces must be insu­lated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applica­ble fire codes.
FOR UNITS WITH ACCESSORY OR OPTIONAL ELEC­TRIC HEATERS — All installations require a minimum
clearance to combustible surfaces of 1-in. (25 mm) from duct for first 12-in. (305 mm) away from unit.
Outlet grilles must not lie directly below unit discharge. NOTE: A 90-degree elbow must be provided in the ductwork
to comply with UL (Underwriters Laboratories) code for use with electric heat.
WARNING
PERSONAL INJURY HAZARD
Failure to follow this warning could cause personal injury. For vertical supply and return units, tools or parts could
drop into ductwork and cause an injury. Install a 90-degree turn in the return ductwork between the unit and the condi­tioned space. If a 90-degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space. Due to electric heater, supply duct will require 90-degree elbow.
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in damage to roof­ing materials.
Membrane roofs can be cut by sharp sheet metal edges. Be careful when placing any sheet metal parts on such roof.
Step 6 — Rig and Place Unit — When the unit is
ready to be rigged and no longer will be lifted by a fork truck, the wood protector under the basepan must be removed. Re­move 4 screws from each base rail. Wood protector will drop to the ground. See instructions on the unit base rails.
Keep unit upright and do not drop. Spreader bars are re­quired. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 and Fig. 6 for additional information.
Lifting holes are provided in base rails as shown in Fig. 6. Refer to rigging instructions on unit.
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment dam­age.
All panels must be in place when rigging. Unit is not designed for handling by fork truck when panels or pack­aging are removed.
Before setting the unit onto the curb, recheck gasketing on curb.
9
Page 10
NOTES:
1. SPREADER BARS REQUIRED — Top damage will occur if spreader bars are not used.
2. Dimensions in ( ) are in millimeters.
3. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.
UNIT
MAX
WEIGHT
DIMENSIONS
ABC
lb kg in. mm in. mm in. mm
50HC**14 2105 957 116.0 2945 62.5 1590 59.5 1510
DETAIL “A”
PLACE ALL SEAL STRIP IN PLACE BEFORE PLACING UNIT ON ROOF CURB.
DUCT END
SEE DETAIL “A”
(914 - 1371)
36" - 54"
“B”
“A”
“C”
Fig. 6 — Rigging Details
POSITIONING ON CURB — For full perimeter curbs CRRFCURB074A00 and 075A00, the clearance between the roof curb and the front and rear base rails should be (6.4 mm). The clearance between the curb and the end base rails should be
1
/2 in. (13 mm). For retrofit applications with
1
/4 in.
curbs CRRFCURB003A01 and 4A01, the unit should be posi­tioned as shown in Fig. 7. Maintain the 15.5 in. (394 mm) and
5
8
/8 in. (220 mm) clearances and allow the 225/16 in. (567 mm)
dimension to float if necessary.
Fig. 7 — Retrofit Installation Dimensions
If the alternative condensate drain location through the bot­tom of the unit is used in conjunction with a retrofit curb, the hole in the curb must be moved 12.5 in. (320 mm) towards the end of the unit. (See Fig. 8.)
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Original Position
Fig. 8 — Alternative Condensate Drain Hole
Positions
IMPORTANT: If the unit has the factory-installed Thru­the-Base option, make sure to complete installation of the option before placing the unit on the roof curb. See the fol­lowing section:
• Factory-Option Thru-Base Connections on page 19
NOTE: If electrical connections are not going to occur at this time, tape or otherwise cover the fittings so that moisture does not get into the building or conduit in the interim.
Remove all shipping materials and top skid. Remove extra center post from the condenser end of the unit so that the con­denser end of the unit matches Fig. 18-20. Recycle or dispose of all shipping materials.
10
New Position (moved 12.5 in.)
Page 11
Step 7 — Convert to Horizontal and Connect
FILTER ACCESS PANEL
INDOOR COIL ACCESS PANEL
Ductwork (When Required) —
vertical duct configuration. Unit without factory-installed economizer or return air smoke detector option may be field­converted to horizontal ducted configuration using accessory CRDUCTCV002A00. To convert to horizontal configuration, remove screws from side duct opening covers and remove cov­ers. See Fig. 9.
Unit is shipped in the
Fig. 10 — Typical Access Panel Locations
Fig. 9 — Horizontal Conversion Panels
Discard the supply duct cover. Install accessory CRDUCTCV002A00 to cover the vertical supply duct open­ing. Use the return duct cover removed from the end panel to cover the vertical return duct opening.
Field-supplied flanges should be attached to horizontal duct openings and all ductwork should be secured to the flanges. In­sulate and weatherproof all external ductwork, joints, and roof or building openings with counter flashing and mastic in accor­dance with applicable codes.
Do not cover or obscure visibility to the unit’s informative data plate when insulating horizontal ductwork.

Step 8 — Install Outside Air Hood

ECONOMIZER HOOD REMOVAL AND SETUP FACTORY OPTION

1. The hood is shipped in knock-down form and located in the return air compartment. It is attached to the economiz­er using two plastic tie-wraps.
2. To gain access to the hood, remove the filter access panel. (See Fig. 10.)
3. Locate and cut the (2) plastic tie-wraps, being careful to not damage any wiring. (See Fig. 11.)
4. Carefully lift the hood assembly through the filter access opening and assemble per the steps outlined in Econo­mizer Hood and Two-Position Hood on page 12.
Remove Hood Parts
Cut Plastic Ties (2) Places
Economizer
Fig. 11 — Economizer Hood Package Location

TWO POSITION DAMPER HOOD REMOVAL AND SETUP — FACTORY OPTION

1. The hood is shipped in knock-down form and assembled to a metal support tray using plastic stretch wrap. Located in the return air compartment, the assembly’s metal tray is attached to the basepan and also attached to the damper using two plastic tie-wraps.
2. To gain access to the hood, remove the filter access panel. (See Fig. 10.)
3. Locate the (2) screws holding the metal tray to the base­pan and remove. In order to remove the screws, it may be necessary to remove the panel underneath the two-posi­tion damper. Remove the two screws. Locate and cut the (2) plastic tie-wraps securing the assembly to the damper. (See Fig. 12.) Be careful to not damage any wiring or cut tie-wraps securing any wiring.
4. Carefully lift the hood assembly (with metal tray) through the filter access opening and assemble per the steps out­lined in Economizer Hood and Two-Position Hood on page 12.
11
Page 12
5. If removed, reattach the panel under the damper.
Hood Parts
Plastic Tie Wrap Qty (2)
Screws for Metal Tray Qty (2)
TOP PAN EL
INDOOR COIL ACCESS PANEL
SCREW
HOOD DIVIDER
LEFT HOOD SIDE
Fig. 12 — Two-Position Damper Hood Package
Location
ECONOMIZER HOOD AND TWO-POSITION HOOD NOTE: If the power exhaust accessory is to be installed on the
unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust hood assembly.
1. The indoor coil access panel will be used as the top of the hood. If the panel is still attached to the unit, remove the screws along the sides and bottom of the panel. See Fig. 13.
2. Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Be careful not to lift the panel too far as it might fall out. Use the screws provided to attach the hood sides to the hood top. Use screws pro­vided to attach the hood sides to the unit. See Fig. 14.
3. Remove the shipping tape holding the economizer baro­metric relief damper in place.
4. Insert the hood divider between the hood sides. See Fig. 14 and 15. Secure hood divider with 3 screws on each hood side. The hood divider is also used as the bot­tom filter rack for the aluminum filter.
5. Attach the post that separates the filters with the screws provided.
6. Open the filter clips which are located underneath the hood top. Insert the aluminum filters into the bottom filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filters into place. See Fig. 15.
7. Install the two rain deflectors on the edge of the hood top as shown in Fig. 13.
8. Caulk the ends of the joint between the unit top panel and the hood top as shown in Fig. 13.
9. Replace the filter access panel.
12
SIDE PAN EL
RAIN DEFLECTORS
TOP PAN EL
INDOOR COIL ACCESS PAN EL
INDOOR COIL ACCESS PAN EL
CAULK HERE
Fig. 13 — Indoor Coil Access Panel Relocation
Fig. 14 — Economizer Hood Construction
DIVIDER
OUTSIDE AIR
HOOD
CLEANABLE ALUMINUM FILTER
BAROMETRIC RELIEF
FILTER
Fig. 15 — Economizer Filter Installation
FILTER CLIP
Page 13
Step 9 — Install External Condensate Trap
DRAIN (FACTORY-INSTALLED)
PLUG
CONDENSATE PAN (SIDE VIEW)
STANDARD SIDE DRAIN
ALTERNATE BOTTOM DRAIN
NOTE: Trap should be deep enough to offset maximum unit static difference. A 4 in. (102 mm) trap is recommended.
MINIMUM PITCH 1˝ (25 mm) PER 1 (3 m) OF LINE
BASE RAIL
OPEN VENT
TO ROOF DRAIN
DRAIN PLUG
ROOF CURB
SEE NOTE
3˝(76 mm)
MIN
and Line —
nection on the end of the condensate pan and an alternate con­nection on the bottom. See Fig. 16. Unit airflow configuration does not determine which drain connection to use. Either drain connection can be used with vertical or horizontal applications.
Fig. 16 — Condensate Drain Pan (Side View)
When using the standard side drain connection, ensure the red plug in the alternate bottom connection is tight. Do this be­fore setting the unit in place. The red drain pan can be tightened
1
with a
/2-in. square socket drive extension.
To use the alternate bottom drain connection, remove the red drain plug from the bottom connection (use a socket drive extension) and install it in the side drain connec­tion.
The piping for the condensate drain and external trap can be completed after the unit is in place. See Fig. 17.
All units must have an external trap for condensate drain­age. Install a trap at least 4-in. (102 mm) deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do not use a pipe size smaller than the unit connection (
The unit has one 3/4-in. condensate drain con-
1
/2-in. square
3
/4-in.).

Step 10 — Make Electrical Connections

WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Unit cabinet must have an uninterrupted, unbroken electri­cal ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control com­partment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code); ANSI/NFPA 70, latest edition (in Canada, Cana­dian Electrical Code CSA [Canadian Standards Associa­tion] C22.1), and local electrical codes.
NOTE: Field-supplied wiring shall conform with the limita­tions of minimum 63°F (3°C) rise.
FIELD POWER SUPPLY For those units without through-the-curb power, conduit must be used to route the main power from the condenser end, via the power entry in the corner post of the unit (see Fig. 18-20) to either the factory op­tion disconnect or the bottom of the control box. 1-in. conduit is provided wrapped around compressor. A second conduit is provided with factory installed powered convenience outlet. For those units that require conduit larger than 1-in., it must be field supplied. Figures 18-20 show the wire routings.
If the field disconnect is larger than 100A, it must be at­tached to the unit using accessory CRDISBKT001A00 — dis­connect switch bracket (see Fig. 21). Follow the instructions provided with this accessory. For smaller field disconnects, be sure to use end panel (see Fig. 22). In either case, set the disconnect verti­cal location on the unit so that a 90 degree fitting can be used to connect the conduit to the disconnect.
1
/2-in. screws to mount the disconnect directly to the
Fig. 17 — Condensate Drain Piping Details
Fig. 18 — Conduit into Factory Option Non-Fused
Disconnect or HACR
13
Page 14
Fig. 19 — Conduit into Control Box
Fig. 22 — Mounting Position for Field Disconnects
(up to 100A)
Field power wires are connected to the unit at line-side pres­sure lugs at the main terminal block (TB1) or at factory­installed option non-fused disconnect switch or HACR, or field or factory-installed Single Point box for electric heat. Refer to Table 2 for maximum wire size at connection lugs. Use copper wire only. See Fig. 23.
Table 2 — Connection Lug Min/Max Wire Sizes
Fig. 20 — Conduit into Single Point Box
Fig. 21 — Mounting Position for Field Disconnects
(over 100A)
MINIMUM MAXIMUM TB1 in unit control box #14 #1 Terminal/Fuse block in
Single Point Box for Electric Heat
80A Disconnect Option #14 #4 100A Disconnect Option #8 1/0 200A Disconnect Option #4 300 kcmil 25A HACR Option #14 1/0 30A HACR Option #14 1/0 35A HACR Option #14 1/0 40A HACR Option #14 1/0 50A HACR Option #14 1/0 60A HACR Option #14 1/0 70A HACR Option #14 1/0 80A HACR Option #14 1/0 90A HACR Option #14 1/0 100A HACR Option #14 1/0 110A HACR Option #4 300 kcmil 125A HACR Option #4 300 kcmil 150A HACR Option #4 300 kcmil 175A HACR Option #4 300 kcmil 200A HACR Option #4 300 kcmil
#8 3/0
NOTE: TEST LEADS — Unit may be equipped with short leads (pigtails) on the field line connection points off the op­tional non-fused disconnect switch or HACR. These leads are for factory run-test purposes only; remove and discard before connecting field power wires to unit connection points. Make field power connections directly to line con­nection pressure lugs only.
14
Page 15
Units Without Single Point Box, Disconnect or HACR Option
Units With Disconnect or HACR Option
L1
L2
L3
2
4
6
1
5
Optional
Disconnect
Switch
or HACR
Disconnect factory test leads; discard.
Factory Wiring
3
Equip GR Lug
Ground
(GR)
Units With Electric Heat Option with Single Point Box
and Without Disconnect or HACR Option
L1
L2
L3
Single Point Box
Factory Wiring
Equip GR
Lug
Ground (GR)
Terminal Block
— OR —
L1
L2
L3
Single Point Box
Factory Wiring
Equip GR
Lug
Ground (GR)
Fuse/Terminal Block
Fuse
Fuse
Fuse
Disconnect
per
NEC
11 1 2 13
L1 L2 L3
TB1
208/230-3-60
460-3-60 575-3-60
Ground
(GR)
Equip
GR Lug
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or property damage intermittent operation or performance satisfaction.
Do not connect aluminum wire between disconnect switch and air conditioning unit. Use only copper wire. (See Fig. 24.)
ELECTRIC
DISCONNECT
SWITCH
COPPER
WIRE ONLY
ALUMINUM
WIRE
Fig. 24 — Disconnect Switch and Unit
ALL UNITS — All field wiring must comply with NEC and all local requirements.
Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 23 and the unit label diagram for power wiring connections to the unit power terminal blocks and equipment ground. Refer to Table 2 for maximum wire size at connection lugs.
Provide a ground-fault and short-circuit over-current protec­tion device (fuse or breaker) per NEC Article 440 (or local codes). Refer to unit informative data plate for MOCP (Maxi­mum Over-current Protection) device size.
NOTE: Units ordered with factory installed HACR do not need an additional ground-fault and short-circuit over-current protection device unless local codes require.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate. On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the following formula to de­termine the percent of voltage imbalance.
% Voltage imbalance
= 100 x
Example: Supply voltage is 230-3-60.
max voltage deviation from average voltage
average voltage
AB = 224 v BC = 231 v AC = 226 v
Fig. 23 — Power Wiring Connections
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 227 (BC) 231 (AC) 227
224 = 3 v
227 = 4 v 226 = 1 v
Maximum deviation is 4 v.
224 + 231 + 226
681
=
3
=
227
3
15
Page 16
Determine percent of voltage imbalance.
4
226
% Voltage Imbalance = 100 x
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immedi­ately.
All units except 208/230-v units are factory wired for the
voltage shown on the nameplate. If the 208/230-v unit is to be
connected to a 208-v power supply, the control transformer must be rewired by moving the black wire with the male spade connector from the 230-v connection and moving it to the 200-v
1
/4-in. male terminal on the primary side of the
1
/4-in. fe-
transformer. Refer to unit label diagram for additional
information.
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.
NOTE: Check all factory and field electrical connections for tightness.
UNITS WITHOUT FACTORY-INSTALLED NON-FUSED DISCONNECT OR HACR — When installing units, provide
a disconnect switch of adequate size per NEC (National Elec­trical Code). Disconnect sizing data is provided on the unit in­formative plate. Locate on unit cabinet or within sight of the unit per national or local codes. Do not cover unit informative plate if mounting the disconnect on the unit cabinet.
UNITS WITH FACTORY-INSTALLED NON-FUSED DISCONNECT OR HACR — The factory-installed option non-fused disconnect switch (NFD) is located in a weather-
proof enclosure located under the main control box. The manu­al switch handle is shipped in the disconnect or HACR enclo­sure. Assemble the shaft and handle to the switch or HACR at this point. Discard the factory test leads (see Fig. 23). The fac­tory disconnect is a 200A disconnect on 230-3-60 units and a 100A disconnect on 460-3-60 and 575-3-60 units. On units with factory installed non-fused disconnect, without factory in­stalled electric heat, the factory supplied load side wires may be of insufficient size for accessory electric heat applications. If so, remove the load side factory wiring. Re-size wires per unit nameplate data provided with accessory electric heat.
Fig. 25 — Location of Non-Fused Disconnect
Enclosure
To field install the NFD shaft and handle:
1. Remove the unit front panel (see Fig. 2).
2. Remove (3) hex screws on the NFD enclosure - (2) on the face of the cover and (1) on the bottom.
3. Remove the front cover of the NFD enclosure.
4. Make sure the NFD shipped from the factory is at OFF position (the arrow on the black handle knob is at OFF).
5. Insert the shaft with the cross pin on the top of the shaft in the horizontal position.
6. Measure the tip of the shaft to the top surface of the point­er to be 3.75 to 3.88 in. (95 to 99 mm) for 80A and 100A NFD and 3.43 to 3.56 in. (87 to 90 mm) for 200A NFD.
7. Tighten the locking screw to secure the shaft to the NFD.
8. Turn the handle to the OFF position with red arrow point­ing at OFF.
9. Install the handle on to the painted cover horizontally with the red arrow pointing to the left.
10. Secure the handle to the painted cover with (2) screws and lock washers supplied.
11. Engaging the shaft into the handle socket, re-install (3) hex screws on the NFD enclosure.
12. Re-install the unit front panel.
16
Page 17
Fig. 26 — Handle and Shaft Assembly for NFD
6. Tighten the locking screw to secure the shaft to the HACR.
7. Turn the handle to the OFF position with red arrow point­ing at OFF.
8. Install the handle on to the painted cover horizontally with the red arrow pointing to the left.
9. Secure the handle to the painted cover with (2) screws and lock washers supplied.
10. Engaging the shaft into the handle socket, re-install (3) hex screws on the HACR enclosure.
11. Re-install the unit front panel.
Fig. 27 — Location of HACR Enclosure
To field install the HACR shaft and handle:
1. Remove the unit front panel (see Fig. 2).
2. Remove (3) hex screws on the HACR enclosure - (2) on the face of the cover and (1) on bottom.
3. Remove the front cover of the HACR enclosure.
4. Make sure the HACR shipped from the factory is at OFF position (the white arrow pointing at OFF).
5. Insert the shaft all the way with the cross pin on the top of the shaft in the horizontal position.
Fig. 28 — Handle and Shaft Assembly for HACR

CONVENIENCE OUTLETS

WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Units with convenience outlet circuits may use multiple disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it. Lock-out and tag-out this switch, if necessary.
Two types of convenience outlets are offered on the 50HC**14 models: non-powered and unit-powered. Both types provide a 125-volt GFCI (ground-fault circuit-interrupt­er) duplex receptacle rated at 15-A behind a hinged waterproof access cover, located on the panel beneath the control box. See Fig. 29.
Non-powered type: This type requires the field installation of a general-purpose 125-volt 15-A circuit powered from a source elsewhere in the building. Observe national and local codes when selecting wire size and conduit requirements, fuse or breaker requirements and disconnect switch size and location. Route 125-v power supply conductors into the bottom of the utility box containing the duplex receptacle.
17
Page 18
UNIT
VOLTAGE
CONNECT ASPRIMARY
CONNECTIONS
TRANSFORMER
TERMINALS
208,230 240
L1: RED +YEL
L2: BLU + GRA
H1 + H3 H2 + H4
460 480
L1: RED
Splice BLU + YEL
L2: GRA
H1
H2 + H3
H4
575 600
L1: RED
L2: GRA
H1 H2
Pwd-CO
Fuse
Switch
Convenience
Outlet
GFCI
Disconnect
Access Panel
Fig. 29 — Convenience Outlet Location
Unit-powered type: A unit-mounted transformer is facto­ry-installed to stepdown the main power suppl voltage to the unit to 115-v at the duplex receptacle. This option also includes a manual switch with fuse, located in a utility box and mounted on a bracket behind the convenience outlet; access is through the unit’s control box access panel. See Fig. 29.
The primary leads to the convenience outlet transformer are not factory-connected. Selection of primary power source is a customer-option. If local codes permit, the transformer primary leads can be connected at the line-side terminals on the unit­mounted non-fused disconnect; this will provide service power to the unit when the unit disconnect switch is open. Other con­nection methods will result in the convenience outlet circuit be­ing de-energized when the unit disconnect switch is open. See Fig. 31. On a unit without a unit-mounted disconnect, connect the source leads to the main terminal block (TB1).
If the convenience outlet transformer is connected to the line side of a field disconnect, the conduit provided with the unit must be used to protect the wire as they are routed from the transformer to the field disconnect. The end of the conduit with the straight connector attaches to the field disconnect. The oth­er end does not need to connect to the transformer; however, the conduit must be routed so that all wiring is either in the con­duit or behind the access panel.
If the convenience outlet transformer is connected to the line side of the factory disconnect option, route the wires through the web bushing located on the bottom of the discon­nect box. For the load side wiring to the factory option discon­nect, route the wires through the hole on the right side of the disconnect. Be sure to create a drip loop at least 6-in. long.
Test the GFCI receptacle by pressing the TEST button on the face of the receptacle to trip and open the receptacle. Check for proper grounding wires and power line phasing if the GFCI receptacle does not trip as required. Press the RESET button to clear the tripped condition.
Pwd-CO
Transformer
NOTICE/AVIS
Convenience Outlet Utilization
Maximum Intermittent Use 15 - Amps
Maximum Continuous Use 8 - Amps
Observe a 50% limit on the circuit
Loading above 8 - Amps
Utilisation de la prise utilitaire
Usage intermittent maximum 15 - Amps
Usage continu maximum 8 - Amps
Observez une limite de 50% sur le circuit
Chargement au-dessus de 8 - Amps
Fig. 30 — Convenience Utilization Notice
Fig. 31 — Unit Powered Convenience Outlet Wiring
Fuse on power type: The factory fuse is a Bussman “Fuse­tron” T-15, non-renewable screw-in (Edison base) type plug fuse.
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Using unit-mounted convenience outlets: Units with unit­mounted convenience outlet circuits will often require that two disconnects be opened to de-energize all power to the unit. Treat all units as electrically energized until the con­venience outlet power is also checked and de-energization is confirmed. Observe National Electrical Code Article 210, Branch Circuits, for use of convenience outlets.
Installing Weatherproof Cover: A weatherproof while-in­use cover for the factory-installed convenience outlets is now required by UL standards. This cover cannot be factory-mount-
18
2.050HE501288
Page 19
ed due its depth; it must be installed at unit installation. For shipment, the convenience outlet is covered with a blank cover plate.
The weatherproof cover kit is shipped in the unit’s control box. The kit includes the hinged cover, a backing plate and gas­ket.
DISCONNECT ALL POWER TO UNIT AND CONVE­NIENCE OUTLET. LOCK-OUT AND TAG-OUT ALL POWER.
Remove the blank cover plate at the convenience outlet; dis­card the blank cover.
Loosen the two screws at the GFCI duplex outlet, until ap­proximately
1
/2-in. (13 mm) under screw heads are exposed. Press the gasket over the screw heads. Slip the backing plate over the screw heads at the keyhole slots and align with the gasket; tighten the two screws until snug (do not over-tighten).
Mount the weatherproof cover to the backing plate as shown in Fig. 32. Remove two slot fillers in the bottom of the cover to permit service tool cords to exit the cover. Check for full closing and latching.
COVER – WHILE-IN-USE WEATHERPROOF
RECEPTACLE NOT SHOWN
Fig. 33 — HACR Caution Label
FACTORY OPTION THRU-BASE CONNECTIONS — This service connection kit consists of a
head connector and a 1
1
/2-in. electrical bulkhead connector,
1
/2-in. electrical bulk-
connected to an “L” bracket covering the embossed (raised) section of the unit basepan in the condenser section. See Fig. 34. The control wires to pass through the basepan. The 1
1
/2-in. bulkhead connector enables the low-voltage
1
/2-in. electri­cal bulkhead connector allows the high-voltage power wires to pass through the basepan.
BASE PLATE FOR GFCI RECEPTACLE
Fig. 32 — Weatherproof Cover Installation
HACR — The amp rating of the HACR factory-installed op­tion is based on the size, voltage, indoor motor and other elec­trical options of the unit as shipped from the factory. If field-in­stalled accessories are added or changed in the field (i.e., power exhaust), the HACR may no longer be of the proper amp rating and therefore will need to be removed from the unit. See unit nameplate and label on factory-installed HACR for the amp rating of the HACR that was shipped with the unit from the factory. See unit nameplates for the proper fuse, HACR or maximum over-current protection device required on the unit with field-installed accessories.
1
/2” ELECTRICAL BULKHEAD CONNECTOR
11/2” ELECTRICAL BULKHEAD CONNECTOR
Fig. 34 — Thru-the Base Option, Shipping
Position
1. Remove the “L” bracket assembly from the unit.
2. Remove connector plate assembly from the “L” bracket and discard the “L” bracket, but retain the washer head screws and the gasket (located between the “L” bracket and the connector plate assembly).
NOTE: Take care not to damage the gasket, as it is reused in the following step.
3. Place the gasket over the embossed area in the basepan, aligning the holes in the gasket to the holes in the base­pan. See Fig. 35.
4. Install the connector plate assembly to the basepan using 8 of the washer head screws.
NOTE: If electrical connections are not going to occur at this time, tape or otherwise cover the fittings so that moisture does not get into the building or conduit in the interim.
19
Page 20
GASKET
CONNECTOR PLATE ASSEMBLY
NOTES:
1. Typical multi-function marking. Follow manufacturer’s configu­ration instructions to select Y2. Do not configure for O output.
2. W2 connection not required on units without electric heating.
Field Wiring
cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.
Typical

Thermostat

Connections
Central
Terminal
Board
X
Fig. 35 — Installing Thru-the Base Option
Check tightness of connector lock nuts before connecting
electrical conduits.
Field-supplied and field-installed liquid-tight conduit con­nectors and conduit may be attached to the connectors on the basepan. Pull correctly rated high voltage and low voltage through appropriate conduits. Connect the power conduit to the internal disconnect (if unit is so equipped) or to the external disconnect (through unit side panel). Remove one of the two knockouts located on the bottom left side of the unit control box. Use this hole for the control conduit.

UNITS WITHOUT THRU-BASE CONNECTIONS

1. Install power wiring conduit through side panel openings. Install conduit between disconnect and control box.
2. Install power lines to terminal connections as shown in Fig. 23.
FIELD CONTROL WIRING — The 50HC**14 unit re­quires an external temperature control device. This device can be a thermostat (field-supplied) or a PremierLink™ controller (available as factory-installed option or as field-installed acces­sory, for use on a Carrier Comfort Network
®
or as a stand alone control) or the RTU Open Controller for Building Management Systems using non-CCN protocols (RTU Open controller is available as a factory-installed option only).
THERMOSTAT — Select a Carrier-approved accessory thermostat. When electric heat is installed in the 50HC unit, the thermostat must be capable of energizing the G terminal (to en­ergize the Indoor Fan Contactor) whenever there is a space call for heat (energizing the W1 terminal). The accessory thermo­stats listed on the unit price pages can provide this signal but they are not configured to enable this signal as shipped.
Install the accessory thermostat according to installation in-
structions included with the accessory.
Locate the thermostat accessory on a solid wall in the condi­tioned space to sense average temperature in accordance with the thermostat installation instructions.
If the thermostat contains a logic circuit requiring 24-v pow­er, use a thermostat cable or equivalent single leads of different colors with minimum of seven leads. If the thermostat does not require a 24-v source (no “C” connection required), use a ther­mostat cable or equivalent with minimum of six leads. Check the thermostat installation instructions for additional features which might require additional conductors in the cable.
For wire runs up to 50 ft (15 m), use no. 18 AWG (Ameri­can Wire Gage) insulated wire (35°C minimum). For 50 to 75 ft (15 to 23 m), use no. 16 AWG insulated wire (35°C mini­mum). For over 75 ft (23 m), use no. 14 AWG insulated wire (35°C minimum). All wire sizes larger than no. 18 AWG
C
G
W2
W1
O/B/Y2
(Note 1)
Y1
R
Note 1: Typical multi-function marking. Follow manufacturer’s configuration instructions to select Y2. Do not configure for O output.
Note 2: W2 connection not required on units without electric heating.
Field Wiring
(Note 2)
C
G
W2
W1
Y2
Y1
R
T H E R M O S T A T
Fig. 36 — Typical Low-Voltage Control
Connections
UNIT WITHOUT THRU-BASE CONNECTION KIT — Pass the thermostat control wires through the bushing on the
unit end panel. Route the wire through the snap-in wire tie and up to the web bushing near the control box. Route the wire through the bushing and into the bottom left side of the control box after removing one of the two knockouts in the corner of the box. Using a connector at the control box to protect the wire as it passes into the control box. Pull the wires over to the terminal strip at the upper left corner of the Central Terminal Board (CTB). Use the connector at the control box and the wire tie to take up any slack in the thermostat wire to ensure that it will not be damaged by contact with the condenser coil. See Fig. 37.
NOTE: If thru-the-bottom connections accessory is used, refer to the accessory installation instructions for information on routing power and control wiring.
Fig. 37 — Thermostat Wire Routing
20
Page 21
HEATER MOUNTING BRACKET
HEATER MODULE (LOCATION 2)
HEATER MODULE (LOCATION 1)
SINGLE POINT BOX MOUNTING SCREW
SINGLE POINT BOX
HEATER COVERS
MANUAL RESET LIMIT SWITCH
DISCONNECT MOUNTING LOCATION
AL
LIED
P A
M
O DE
L
NO
.
ER I
A L
N O.
C O
R P .
O
D
2 2
. 2
3
1 2 3
ISTED
AIR NDITIONING UIP
ACCESS 346
N
.
P /
N
2-
5
6 1
0­4
RE
V
1 1
13
2 1
2 3
CONTROL BOX
BUSHING
SINGLE POINT BOX MOUNTING SCREWS
FOAM BUSHING
DRIP BOOT BRACKET MOUNTING SCREWS
HEATER RELAYS
POWER WIRES
HEATER MOUNTING SCREWS
Fig. 38 — Typical Component Location
HEAT ANTICIPATOR SETTINGS — Set heat anticipator settings at 0.14 amp for the first stage and 0.14 amp for second­stage heating, when available.
Electric Heaters — The 50HC-*14 units may be
equipped with factory or field-installed electric heaters. The heaters are modular in design, with heater frames holding open coil resistance wires strung through ceramic insulators, line­break limit switches and a control contactor. One or two heater modules may be used in a unit.
Heater modules are installed in the compartment below the indoor (supply) fan outlet. Access is through the indoor access panel. Heater modules slide into the compartment on tracks along the bottom of the heater opening. See Fig. 38.
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
Not all available heater modules and single point boxes may be used in every unit. Use only those heater modules that are UL listed for use in a specific size unit. Refer to the label on the unit cabinet for the list of approved heaters and single point boxes.
Single Point Boxes — When heaters are installed,
power wiring to both heaters and the rest of the unit is connect­ed via the single point box accessory, which will be installed directly under the unit control box, just to the left of the parti­tion separating the indoor section (with electric heaters) from the outdoor section. The single point box has a hinged access cover. See Fig. 39. The single point box also includes pigtails to complete the wiring between the single point box and the unit’s main control box terminals. The pigtails will already be connected into the unit’s main control box on units with factory installed electric heat. Refer to the accessory heater and Single
Point Box installation instructions for details on tap connec­tions for field installed electric heat accessory.
Fig. 39 — Typical Single Point Installation
HEATER AND SUPPLEMENTARY FUSES — When the unit MOCP device value exceeds 60-A, unit-mounted supple­mentary fuses are required for each heater circuit. These fuses are included in accessory Single Point Boxes, with power dis­tribution and fuse blocks.
All fuses on 50HC-*14 units are 60-A. (Note that all heaters are qualified for use with a 60-A fuse, regardless of actual heat­er ampacity, so only 60-A fuses are necessary.)
HEATER LOW-VOLTAGE CONTROL CONNEC­TIONS — One or two heaters can be installed in the unit. Use the wiring procedure listed below for each heater as determined by the number of stages in the heater.
Single Stage Heaters: Single-stage heaters will have an or­ange and a brown control wire. Connect these to the orange and brown wires located on TB4. See Fig. 40.
21
Page 22
NOTE:
Optional Outdoor Temperature Control at One Heater Stage –
Move heater wire to this terminal and
connect outdoor temperature switch between 2nd and 3rd terminals.
W2 UseW1 Use
VIO
12
CONTROL BOARD
8
CONTROL BOARD
R Use C Use
VIO
% RELATIVE HUMIDITY
®
Fig. 40 — Single Stage Heaters: TB4 Wiring
Connections
Two Stage Heaters: Two-stage heaters will have orange, violet, red and brown wires. The orange and the purple are the control wires and the red and brown wires feed the safety cir­cuit. Connect both the orange and the purple wires to the or­ange wire locations of TB4. Connect the red and brown wires to red and brown wires on TB4. If more than one heater is in­stalled, repeat the wiring procedure for the second heater. The 3 locations across the top of TB4 do allow a switch to be in­stalled in series with some of the heaters in order to add addi­tional heater control. See Fig. 41.
NOTE: The low voltage wiring will already be completed on units with factory installed electric heat.
4. Use the connector and the wire tie to reduce any slack in the humidistat cable to ensure that it will not be damaged by contact with the condenser coil (see Fig. 37).
5. Use wire nuts to connect humidistat cable to two PINK leads in the low-voltage wiring as shown in Fig. 44).
To connect the Thermidistat device (33CS2PPRH-01):
1. Route the Thermidistat multi-conductor thermostat cable (field-supplied) through the bushing in the unit’s louvered end panel (see Fig. 37).
2. Route the cable through the snap-in wire tie and up to the web bushing near the control box
3. Feed the cable through the bushing and into the bottom left side of the control box after removing one of the two knockouts in the corner of the box. Use a connector to protect the cable as it enters the control box.
4. Use the connector and the wire tie to reduce any slack in the thermostat cable to ensure that it will not be damaged by contact with the condenser coil (see Fig. 37).
5. The Thermidistat has dry contacts at terminals D1 and D2 for dehumidification operation (see Fig. 45). The dry con­tacts must be wired between CTB terminal R and the PINK lead to the LTLO switch with field-supplied wire nuts. Refer to the installation instructions included with the Carrier Edge Pro Thermidistat device for more infor­mation.
Fig. 41 — Two Stage Heaters: TB4 Wiring
Connections
Humidi-MiZer® System Control Connections
HUMIDI-MIZER — SPACE RH CONTROLLER NOTE: The Humidi-MiZer system is a factory-installed
option.
The Humidi-MiZer dehumidification system requires a field-supplied and installed space relative humidity control de­vice. This device may be a separate humidistat control (contact closes on rise in space RH above control setpoint) or a combi­nation thermostat-humidistat control device such as Carrier’s
®
Pro Thermidistat with isolated contact set for dehumidi-
Edge fication control. The humidistat is normally used in applica­tions where a temperature control is already provided (units with PremierLink™ control).
To connect the Carrier humidistat (HL38MG029):
1. Route the humidistat 2-conductor cable (field-supplied) through the bushing in the unit’s louvered end panel (see Fig. 37).
2. Route the cable through the snap-in wire tie and up to the web bushing near the control box.
3. Feed the cable through the bushing and into the bottom left side of the control box after removing one of the two knockouts in the corner of the box. Use a connector to protect the cable as it enters the control box.
Fig. 42 — Accessory Field-Installed Humidistat
Fig. 43 — Edge Pro Thermidistat
22
Page 23
Fig. 44 — Typical Humidi-MiZer
®
Adaptive Dehumidification System Humidistat Wiring
23
Page 24
Fig. 45 — Typical Rooftop Unit with Humidi-MiZer Adaptive Dehumidification System with
Rc
Rh
W1
G
Y2
C
O/W2/B
Y1
OAT RR
S
S
RTN
HUM
D1 D2
V+ Vg
X
*
C
G
W2
W1
Y2
Y1
R
Edge Programable Thermostat
Unit CTB
THERMOSTAT
*Connection not required.
Humidi-MiZer™ FIOP

EconoMi$er® X (Factory-Installed Option)

PRODUCT DESCRIPTION — The EconoMi$er X system is an expandable economizer control system, which includes a W7220 economizer module (controller) with an LCD and key­pad (See Fig. 46). The W7220 can be configured with optional sensors.
Fig. 46 — W7220 Economizer Module
The W7220 economizer module can be used as a stand­alone economizer module wired directly to a commercial set­back space thermostat and sensors to provide outside air dry­bulb economizer control.
The W7220 economizer module can be connected to op­tional sensors for single or differential enthalpy control. The W7220 economizer module provides power and communica­tions for the sensors.
The W7220 economizer module automatically detects sensors by polling to determine which sensors are present. If a
®
Edge
Pro Thermidistat Device
24
sensor loses communications after it has been detected, the W7220 economizer controller indicates a device fail error on its LCD.
SYSTEM COMPONENTS — The EconoMi$er X system in­cludes an economizer module, 20k mixed air sensor, damper actuator, and either a 20k outdoor air temperature sensor or S­Bus enthalpy sensors.
Economizer Module
— The module is the core of the EconoMi$er X system. The module is mounted in the unit’s control box, and includes the user interface for the system. The W7220 economizer module provides the basic inputs and out­puts to provide simple economizer control. When used with the optional sensors, the economizer module provides more ad­vanced economizer functionality.
S-Bus Enthalpy Control Sensors
— The sensor is a combi­nation temperature and humidity sensor which is powered by and communicates on the S-Bus. Up to three sensors may be configured with the W7220 economizer module.
CO
Sensor (optional) — The sensor can be added for De-
2
mand Controlled Ventilation (DCV).

SPECIFICATIONS

W7220 Economizer Module
— The module is designed for use with 2 to 10 Vdc or bus communicating actuator. The mod­ule includes terminals for CO
sensor, Mixed Air sensor, and
2
an Outdoor Dry Bulb sensor. Enthalpy and other options are available with bus sensors.
User Interface
— Provides status for normal operation, setup parameters, checkout tests, and alarm and error conditions with a 2-line 16 character LCD display and four button keypad.
Electrical
Rated Voltage — 20 to 30 Vac RMS, 50/60 Hz Transformer — 100 va maximum system input Nominal Power Consumption (at 24 Vac, 60 Hz) — 11.5
VA without sensors or actuators
Page 25
NA
AUX2-
OCC
E-GND
EXH1
AUX1-O
Y2-
Y1-
Y2-O
Y1-O
C
R
50048848-002
Rev. A
NA
A2
OCC
EX
A1
Y2I
Y2O
Y1I
Y1O
C
R
Cert Product
California Title 24, Part 6
HJW10
www.energy.ca.gov
MAT
MAT
OAT
OAT
S-BUS
S-BUS
IAQ 2-10
IAQ COM
IAQ 24V
ACT 2-10
ACT CO M
ACT 24V
MA MA
OA OA
SB SB
SB SB
SB SB
V C R
V C R
NA
50040839-001
Rev. G
Relay Digital Output Rating at 30 Vac (maximum power
from Class 2 input only) — 1.5A run:
3.5A inrush at 0.45PF (200,000 cycles) or
7.5A inrush at 0.45PF (100,000 cycles) External Sensors Power Output — 21 Vdc ± 5% at 48mA
IMPORTANT: All inputs and outputs must be Class 2 wiring.
INPUTS Sensors NOTE: A Mixed Air (MA) analog sensor is required on all
W7220 units; either an Outdoor Air (OA) sensor for dry bulb change over or an OA bus sensor for outdoor enthalpy change over is required in addition to the MA sensor. An additional Return Air (RA) bus sensor can be added to the system for dif­ferential enthalpy or dry bulb changeover. For differential dry bulb changeover a 20k ohm sensor is required in the OA and a bus sensor in the RA. DIP switch on RA bus sensor must be set in the RA position.
Dry Bulb Temperature (optional) and Mixed Air (required), 20k NTC
2-wire (18 to 22 AWG); Temperature range -40 to 150 F (-40 to 65 C) Temperature accuracy -0 F/+2 F
Temperature and Humidity, C7400S1000 (optional)
S-Bus; 2-wire (18 to 22 AWG) Temperature: range -40 to 150 F (-40 to 65 C) Temperature accuracy -0 F/+2 F Humidity: range 0 to 100% RH with 5% accuracy.
NOTE: Up to three (3) S-Bus sensors may be connected to the W7220 economizer module. For outdoor air (OA), return air (RA) and discharge (supply) air (DA).
4 Binary Inputs — 1-wire 24 Vac + common GND (see page 27 for wiring details).
24 Vac power supply — 20 to 30 Vac 50/60Hz; 100 VA Class 2 transformer.

OUTPUTS

Actuator Signal: 2k ohm; bus two-wire output for bus communicating actuators.
Exhaust fan, Y1, Y2 and AUX1 O:
All Relay Outputs (at 30 Vac): Running: 1.5A maximum Inrush: 7.5A maximum

ENVIRONMENTAL

Operating Temperature:
-40 to 150 F (-40 to 65 C). Exception of display operation down to -4 F with full
recovery at -4 F from exposure to -40 F Storage Temperature
-40 to 150 F (-40 to 65 C)
Shipping Temperature:
-40 to 150 F (- 40 to 65 C)
Relative Humidity:
5% to 95% RH non-condensing
2-10 Vdc; minimum actuator impedance is
:
ECONOMIZER MODULE WIRING DETAILS — Use Fig. 47 and Tables 3 and 4 to locate the wiring terminals for the Economizer module.
NOTE: The four terminal blocks are removable. You can slide out each terminal block, wire it, and then slide it back into place.
Fig. 47 — W7220 Wiring Terminals
Table 3 — Economizer Module - Left Hand
Terminal Blocks
LABEL TYPE DESCRIPTION
Top Left Terminal Block
MAT MAT
OAT OAT
S-BUS S-BUS
IAQ 2-10 2-10 vdc
IAQ COM COM Air Quality Sensor Common
IAQ 24V 24 vac Air Quality Sensor 24 vac Source
ACT 2-10 2-10 vdc Damper Actuator Output (2-10 vdc)
ACT COM COM Damper Actuator Output Common
ACT 24v 24 vac Damper Actuator 24 vac Source
20k NTC and COM
20k NTC and COM
S-BUS (Sylk Bus)
Bottom Left Terminal Block
Mixed Air Temperature Sensor (Polarity Insensitive Connection)
Outdoor Air Temperature Sensor (Polarity Insensitive Connection)
Enthalpy Control Sensor (Polarity Insensitive Connection)
Air Quality Sensor Input (e.g. CO sensor)
2
25
Page 26
Table 4 — Economizer Module - Right Hand
DIP Switch Label
DIP Switches (3)
S-Bus 2 Pin Side Connector
S-Bus Terminals (1 and 2)
Terminal Blocks
LABEL TYPE DESCRIPTION
Top Right Terminal Blocks
AUX2 I 24 vac IN The first terminal is not used.
Shut Down (SD) or HEAT (W)
OCC 24 vac IN
E-GND E-GND Occupied/Unoccupied Input
EXH1
AUX1 O
Y2-I 24 vac IN
Y2-O
Y1-I 24 vac IN
Y1-O
C COM 24 vac Common
R 24 vac 24 vac Power (hot)
24 vac OUT
24 vac OUT
Bottom Right Terminal Blocks
24 vac OUT
24 vac OUT
Conventional only and Heat Pump Changeover (O-B) in Heat Pump mode.
Exhaust Fan 1 Output
Programmable: Exhaust fan 2 output or ERV or System alarm output
Y2 in - Cooling Stage 2 Input from space thermostat
Y2 out - Cooling Stage 2 Output to stage 2 mechanical cooling
Y1 in - Cooling Stage 2 Input from space thermostat
Y1 out - Cooling Stage 2 Output to stage 2 mechanical cooling
S-BUS SENSOR WIRING — The labels on the sensors and controller are color coded for ease of installation. Orange la­beled sensors can only be wired to orange terminals on the con­troller. Brown labeled sensors can only be wired to S-bus (brown) terminals. Use Fig. 48 and Table 5 to locate the wiring terminals for each S-Bus sensor.
Use Fig. 48 and Table 5 to locate the wiring terminals for
each enthalpy control sensor.
Table 5 — HH57AC081 Sensor Wiring
Terminations
TERMINAL
NUMBER LABEL
1 S-BUS S-BUS
2 S-BUS S-BUS
TYPE DESCRIPTION
S-BUS
Communications
(Enthalpy Control
Sensor Bus)
S-BUS
Communications
(Enthalpy Control
Sensor Bus)
Use Fig. 48 and Table 6 to set the DIP switches for the
desired use of the sensor.
Table 6 — HH57AC081 Sensor DIP Switch
DIP SWITCH POSITIONS FOR SWITCHES 1, 2, AND 3
USE
DA OFF ON OFF
RA ON OFF OFF
OA OFF OFF OFF
123
NOTE: When a S-Bus sensor is connected to an existing net­work, it will take 60 minutes for the network to recognize and auto-configure itself to use the new sensor.
During the 60 minute setup period, no alarms for sensor failures (except SAT) will be issued and no economizing func­tion will be available.
SENSOR WIRING — When using a CO2 sensor the
CO
2
black and brown common wires are internally connected and only one is connected to “IAQ COM” on the W7220. Use the power from the W7220 to power the CO
sensor OR make sure
2
the ground for the power supplies are common. See Fig. 49 for CO
sensor wiring.
2
CO2 SENSOR
L1 (HOT) L2
1
24V
ANALOG
OUT
+
RED
BLACK
YELLOW
BROWN
ORANGE
GREEN
Fig. 48 — S-Bus Sensor DIP Switches
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 49 — CO
Sensor Wiring
2
INTERFACE OVERVIEW — This section describes how to use the Economizer’s user interface for:
• Keypad and menu navigation
• Settings and parameter changes
• Menu structure and selection USER INTERFACE — The user interface consists of a 2-line
LCD display and a 4-button keypad on the front of the econo­mizer controller.
KEYPAD — The four navigation buttons (see Fig. 50) are used to scroll through the menus and menu items, select menu items, and to change parameter and configuration settings.
To use the keypad when working with menus:
Press the (Up arrow) button to move to the previous
menu.
Press the (Down arrow) button to move to the next
menu.
26
Page 27
Press the (Enter) button to display the first item in the currently displayed menu.
Fig. 50 — W7220 Controller Navigation Buttons
Press the (Menu Up/Exit) button to exit a menu’s item and return to the list of menus. To use the keypad when working with Setpoints, System and Advanced Settings, Checkout tests and Alarms:
1. Navigate to the desired menu.
2. Press the (Enter) button to display the first item in the cur­rently displayed menu.
3. Use the and buttons to scroll to the desired parame­ter.
4. Press the (Enter) button to display the value of the cur­rently displayed item.
5. Press the button to increase (change) the displayed pa­rameter value.
6. Press the button to decrease (change) the displayed pa­rameter value.
NOTE: When values are displayed, pressing and holding the or button causes the display to automatically increment.
7. Press the (Enter) button to accept the displayed value and store it in nonvolatile RAM.
8. “CHANGE STORED” displays.
9. Press the (Enter) button to return to the current menu pa­rameter.
10. Press the (Menu Up/Exit) button to return to the previous menu.
MENU STRUCTURE — Table 7 illustrates the complete hi­erarchy of menus and parameters for the EconoMi$er
®
X sys-
tem.
The Menus in display order are:
• STATUS
•SETPOINTS
• SYSTEM SETUP
• ADVANCED SETUP
• CHECKOUT
•ALARMS
IMPORTANT: Table 7 illustrates the complete hierar­chy. Your menu parameters may be different depending on your configuration.
For example if you do not have a DCV (CO
) sensor,
2
then none of the DCV parameters appear and only MIN POS will display. If you have a CO
sensor, the DCV MIN
2
and DCV MAX will appear AND if you have 2 speed fan DCV MIN (high and low speed) and DCV MAX (high and low speed will appear).
NOTE: Some parameters in the menus use the letters MA or MAT, indicating a mixed air temperature sensor location before the cooling coil. This unit application has the control sensor located after the cooling coil, in the fan section, where it is designated as (Cooling) Supply Air Temperature or SAT sensor.
SETUP AND CONFIGURATION — Before being placed into service, the W7220 Economizer module must be setup and configured for the installed system.
IMPORTANT: During setup, the economizer module is live at all times.
The setup process uses a hierarchical menu structure that is easy to use. Press the and arrow buttons to move forward and backward through the menus and press the button to select and confirm setup item changes.
TIME-OUT AND SCREENSAVER — When no buttons have been pressed for 10 minutes, the LCD displays a screen saver, which cycles through the Status items. Each Status items displays in turn and cycles to the next item after 5 seconds.
27
Page 28
MENU PARAMETER
ECONO AVAIL NO YES/NO
ECONOMIZING NO YES/NO
OCCUPIED NO YES/NO
HEAT PUMP N/A
COOL Y1—IN OFF ON/OFF
COOL Y1—OUT OFF ON/OFF
COOL Y2—IN OFF ON/OFF
COOL Y2—OUT OFF ON/OFF
MA TEMP _ _ . _ F 0 to 140 F
STATUS
DA TEMP _ _ . _ F 0 to 140 F
OA TEMP _ _ . _ F -40 to 140 F
OA HUM _ _ % 0 to 100%
RA TEMP _ _ . _ F 0 to 140 F
RA HUM _ _ % 0 to 100%
IN CO2 _ _ _ ppm 0 TO 2000 ppm
DCV STATUS N/A ON/OFF
DAMPER OUT 2.0v 2.0 TO 10.0v Displays voltage output to the damper actuator.
ACT POS N/A 0 to 100% Displays actual position of outdoor air damper actuator
Table 7 — Menu Structure
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND INCREMENT
COOL HEAT
NOTES
FIRST STAGE COOLING DEMAND (Y1–IN) YES = economizing available; the system can use outside air for free cooling when required
FIRST STAGE COOLING RELAY OUTPUT YES = outside air being used for 1 stage cooling
OCCUPIED YES = OCC signal received from space thermostat or unitary controller YES = 24 Vac on terminal OCC NO = 0 Vac on terminal OCC
HEAT PUMP MODE Displays COOL or HEAT when system is set to heat pump (Non-conventional)
FIRST STAGE COOLING DEMAND (Y1-IN) Y1–I signal from space thermostat or unitary controller for cooling stage
1. ON = 24 Vac on terminal Y1–I OFF = 0 Vac on terminal Y1–I
FIRST STAGE COOLING RELAY OUTPUT Cool stage 1 Relay Output to stage 1 mechanical cooling (Y1–OUT terminal)
SECOND STAGE COOLING DEMAND (Y2–IN) Y2–I signal from space thermostat our unitary controller for second stage cooling. ON = 24 Vac on terminal Y2–I OFF = 0 Vac on terminal Y2–I
SECOND STAGE COOLING RELAY OUTPUT Cool Stage 2 Relay Output to mechanical cooling (Y2–OUT terminal)
SUPPLY AIR TEMPERATURE, Cooling Mode Displays value of measured mixed air from MAT sensor. Displays _ _ . _ F if not connected, short or out-of-range.
DISCHARGE AIR TEMPERATURE, after Heating section Displays when Discharge Air sensor is connected and displays mea­sured discharge temperature. Displays _ _ . _F if sensor sends invalid value, if not connected, short or out-of-range.
OUTSIDE AIR TEMP Displays measured value of outdoor air temperature. Displays _ _ . _F if sensor sends invalid value, short or out-of-range.
OUTSIDE AIR RELATIVE HUMIDITY Displays measured value of outdoor humidity from OA sensor. Displays _ _% if not connected short, or out-of-range.
RETURN AIR TEMPERATURE Displays measured value of return air temperature from RAT sensor. Displays _ _ . _ F if sensor sends invalid value, if not connected, short or out-of-range
RETURN AIR RELATIVE HUMIDITY Displays measured value of return air humidity from RA sensor. Displays _ _% if sensor sends invalid value, if not connected, short or out-of-range
SPACE/RETURN AIR CO Displays value of measured CO2 from CO2 sensor. Invalid if not con­nected, short or out-of-range
DEMAND CONTROLLED VENTILATION STATUS Displays ON if above setpoint and OFF if below setpoint, and ONLY if a CO
sensor is connected.
2
2
28
Page 29
MENU PARAMETER
ACT COUNT N/A 1 to 65535 Displays number of times actuator has cycled.
ACTUATOR N/A OK/Alarm (on Alarm
EXH1 OUT OFF ON/OFF EXHAUST STAGE 1 RELAY OUTPUT
EXH2 OUT OFF ON/OFF EXHAUST STAGE 2 RELAY OUTPUT
STATUS (CONT)
ERV OFF ON/OFF ENERGY RECOVERY VENTILATOR
MECH COOL ON or HEAT STAGES ON
FAN SPEED N/A LOW or HIGH SUPPLY FAN SPEED
W (HEAT ON) N/A ON/OFF HEAT DEMAND STATUS
MAT SET 53F
LOW T LOCK 32F
DRYBLB SET 63F
ENTH CURVE ES3
DCV SET 1100ppm
MIN POS 2.8 V 2 to 10 Vdc
VENTMAX With 2-speed fan units VENTMAX L (low speed fan) and VENTMAX H (high speed fan) settings are required
SETPOINTS
VENTMIN With 2-speed fan units VENTMIN L (low speed fan) and VENTMIN H (high speed fan) set
ERV OAT SP 32°F
EXH1 SET With 2-speed fan units Exh1 L (low speed fan) and Exh1 H (high speed fan) settings are required
EXH2 SET With 2-speed fan units Exh2 L (low speed fan) and Exh2 H (high speed fan) settings are required
Table 7 — Menu Structure (cont)
PARAMETER
DEFAULT
VALUE
0 0, 1, or 2 Displays stage of mechanical cooling that is active.
2.8 V
2.25 V
50%
75%
PARAMETER
RANGE AND INCREMENT
menu)
38 to 65 F; increment by 1
-45 to 80 F; increment by 1
48 to 80 F; increment by 1
ES1,ES2,ES3,ES4, or ES5
500 to 2000ppm; increment by 100
2 to 10 Vdc
100 to 9990 cfm; increment by 10
2 to 10 Vdc
2 to 10 Vdc or 100 to 9990 cfm increment by 10
100 to 9990 cfm; increment by 10
2 to 10 Vdc
0 to 50 F; increment by 1
0 to 100%;increment by 1
0 to 100%; increment by 1
NOTES
1 cycles equals 180 deg. of actuator movement in any direction.
Displays ERROR if voltage or torque is below actuator range.
Output of EXH1 terminal: ON = relay closed OFF = relay open
Output of AUX terminal; displays only if AUX = EXH2
Output of AUX terminal; displays only if AUX = ERV
Displays the stage of heat pump heating that is active.
Displays speed setting of fan on a 2-speed fan unit.
Displays status of heat demand on a 2-speed fan unit.
SUPPLY AIR SETPOINT Setpoint determines where the economizer will modulate the OA damper to maintain the mixed air temperature.
COMPRESSOR LOW TEMPERATURE LOCKOUT Setpoint determines outdoor temperature when the mechanical cooling cannot be turned on. Commonly referred to as the Compressor lockout.
OA DRY BULB TEMPERATURE CHANGEOVER SETPOINT Setpoint determines where the economizer will assume outdoor air tem­perature is good for free cooling; e.g.; at 63 F unit will economize at 62 F and below and not economize at 64 F and above. There is a 2 F dead­band.
ENTHALPY CHANGEOVER CURVE Enthalpy boundary “curves” for economizing using single enthalpy.
DEMAND CONTROLLED VENTILATION Displays only if CO Ventilation of space. Above the setpoint, the OA dampers will modulate open to bring in additional OA to maintain a space ppm level below the setpoint.
VENTILATION MINIMUM POSITION Displays ONLY if a CO
DCV MAXIMUM DAMPER POSITION Displays only if a CO max cfm) setpoint. Displays 2 to 10 V if <3 sensors (RA,OA, and MA). In AUTO mode dampers controlled by CFM.
If OA, MA, RA, and CO is set to AUTO mode, the OA dampers are controlled by CFM and dis­plays from 100 to 9990 CFM.
With 2-speed fan units VENT L (low speed fan) and MIN POS H (high speed fan) settings are required. Default for VENTMAX L is 3.2V and VENTMAX H is 2.8V
DCV MINIMUM DAMPER POSITION Displays only if a CO cfm) setpoint. Displays 2 to 10 V if <3 sensors (RA, OA, and MA). Va is only set if DCV is used. This is the ventilation for less than maximum occupancy of the space. In AUTO mode dampers controlled by CFM.
If OA, MA, RA, and CO is set to AUTO mode, the OA dampers are controlled by CFM and dis­plays from 100 to 9990 CFM.
With 2-speed fan units VENTMIN L (low speed fan) and MIN POS H (high speed fan) settings are required. Default for VENTMIN L is 3.2V and VENTMIN H is 2.8V
ENERGY RECOVERY VENTILATOR UNIT OUTDOOR AIR TEM­PERATURE SETPOINT Only when AUX1 O = ERV
EXHAUST FAN STAGE 1 SETPOINT Setpoint for OA damper position when exhaust fan 1 is powered by the economizer. With 2-speed fan units Exh1 L (low speed fan) and Exh1 H (high speed fan) settings are required. Default for Exh1 L is 65% and Exh1 H is 50%
EXHAUST FAN STAGE 2 SETPOINT Setpoint for OA damper position when exhaust fan 2 is powered by the economizer. Only used when AUX1 O is set to EHX2. With 2-speed fan units Exh2 L (low speed fan) and Exh2 H (high speed fan) settings are required. Default for Exh2 L is 80% and Exh2 H is 75%
sensor is connected. Setpoint for Demand Control
2
sensor is NOT connected.
2
sensor is connected. Used for Vbz (ventilation
2
sensors are connected and DCV CAL ENABLE
2
sensor is connected. Used for Ba (ventilation min
2
sensors are connected and DCV CAL ENABLE
2
29
Page 30
MENU PARAMETER
INSTALL 01/01/10 N/A Display order = MM/DD/YY
UNITS DEG F F or C Sets economizer controller in degrees Fahrenheit or Celsius
EQUIPMENT CONV Conventional or HP CONV = conventional;
AUX2 IN W SD/W or HP(O)/
FAN SPEED 2 speed 1 speed/2 speed Sets the economizer controller for operation of 1 speed or 2 speed sup-
SYSTEM SETUP
FAN CFM 5000cfm 100 to 15000 cfm;
AUX1 OUT NONE NONE
OCC INPUT INPUT or ALWAYS OCCUPIED MODE BY EXTERNAL SIGNAL
FACTORY DEFAULT NO NO or YES Resets all set points to factory defaults when set to YES. LCD
MA LO SET 45°F 35 to 55 F;
FREEZE POS CLO CLO or MIN FREEZE PROTECTION DAMPER POSITION
CO2 ZERO 0ppm 0 to 500 ppm;
CO2 SPAN 2000ppm 1000 to 3000 ppm;
STG3 DLY 2.0h 0 min, 5 min, 15 min,
ADVANCED
SETUP
SD DMPR POS CLO CLO or OPN Indicates shutdown signal from space thermostat or unitary controller.
DA LO ALM 45 F (7 C) 35 to 65 F; (2 to
DA HI ALM 80 F (27 C) 70 to 180 F; (21 to
DCVCAL ENA MAN MAN (manual) AUTO Turns on the DCV automatic control of the dampers. Resets ventilation
Table 7 — Menu Structure (cont)
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND INCREMENT
HP(B)
increment by 100
ERV EXH2 SYS
Incremented by 1
Increment by 10
Increment by 10
then 15 min intervals. Up to 4 hrs or OFF
18 C) Incremented by 5 deg.
82 C) Incremented by 5 deg.
0
Setting order = DD, MM, then YY.
HP O/B = Enable Heat Pump mode. Use AUX2 I for Heat Pump input from thermostat or controller. See Menu Note 7.
In CONV mode: SD + Enables configuration of shutdown (default); W = Informs controller that system is in heating mode. NOTE: If using 2-speed fan mode, you must program CONV mode for W. Shutdown is not available in 2-speed fan mode. See Menu Note 7. In HP O/B mode: HP(O) = energize heat pump on Cool (default); HP(B) = energize heat pump on heat.
ply fan. NOTE: 2-speed fan option also needs Heat (W1) programmed in AUX 2 In. See Menu Note 7.
UNIT DESIGN AIRFLOW (CFM) Enter only if using DCVAL ENA = AUTO The value is dounf on the nameplate label for the specific unit.
Select OUTPUT for AUX1 O relay
• NONE = not configured (output is not used)
• ERV = Energy Recovery Ventilator
• EXH2 = second damper position relay closure for second exhaust fan
• SYS = use output as an alarm signal
When using a setback thermostat with occupancy out (24 vac), the 24 vac is input “INPUT” to the OCC terminal. If no occupancy output from the thermostat then change program to “ALWAYS” OR add a jumper from terminal R to OCC terminal.
flash YES and change to NO but all parameters will change to the fac­tory default values. NOTE: RECHECK AUX2 IN and FANTYPE for required 2-speed values.
SUPPLY AIR TEMPERATURE LOW LIMIT Temperature to achieve Freeze Protection (close damper and alarm if temperature falls below setup value).
Damper position when freeze protection is active (closed or MIN POS).
CO
CO
COOLING STAGE 3 DELAY Delay after stage 2 cool has been active. Turns on 2 when economizer is 1 Allows three stages of cooling, 1 economizer and 2 mechanical. OFF = no Stage 3 cooling
When controller receives 24 Vac input on the SD terminal in conven­tional mode, the OA damper will open if programmed for OPN and OA damper will close if programmed for CLO. All other controls, e.g., fans, etc. will shut off.
Used for alarm for when the DA air temperature is too low. Set lower range of alarm, below this temperature the alarm will show on the dis­play.
Used for alarm for when the DA air temperature is too high. Set upper range of alarm, above this temperature the alarm will show on the dis­play.
based on the RA, OA, and MA sensor conditions. Requires all 3 RA, OA, and MA sensors.
NOTES
ppm level to match CO2 sensor start level.
2
ppm span to match CO2 sensor.
2
st
stage and mechanical cooling is 2
will
nd
stage of cooling
nd
stage.
briefly
30
Page 31
MENU PARAMETER
MAT T CAL 0.0°F±2.5
OAS T CAL 0.0°F±2.5
OA H CAL 0% RH ±10% RH OUTSIDE AIR HUMIDITY CALIBRATION
ADVANCED
SETUP (CONT)
CHECKOUT
ALARMS
RA T CAL 0.0°F±2.5
RA H CAL 0% RH ±10% RH RETURN AIR HUMIDITY CALIBRATION
DA T CAL 0.0°F±2.5
2SP FAN DELAY 5 Minutes 0 to 20 minutes in 1
DAMPER MINIMUM POSI­TION
DAMPER OPEN N/A N/A Position damper to the full open position.
DAMPER CLOSE N/A N/A Positions damper to the fully closed position
CONNECT Y1–O N/A N/A Closes the Y1-O relay (Y1-O)
CONNECT Y2–O N/A N/A Closes the Y2-O relay (Y2-O)
CONNECT AUX1-O N/A N/A Energizes the AUX output. If Aux setting is:
CONNECT EXH1 N/A N/A Closes the power exhaust fan 2 relay (EXH1)
Alarms display only when they are active. The menu title “ALARMS(#)” includes the number of active alarms in parenthesis ( ). When using SYLK
bus sensors, “SYLK” will appear on the screen, and when using 20k OA temperature sensors, “SENS T” will appear on the screen
MA T SENS ERR N/A N/A SUPPLY AIR TEMPERATURE SENSOR ERROR
CO2 SENS ERR N/A N/A CO
OA SYLK T ERR N/A N/A OUTSIDE AIR S-BUS SENSOR ERROR
OA SYLK H ERR N/A N/A
RA SYLK T ERR N/A N/A RETURN AIR S-BUS SENSOR ERROR
RA SYLK H ERR N/A N/A
DA SYLK T ERR N/A N/A DISCHARGE AIR S-BUS SENSOR ERROR
OA SENS T ERR N/A N/A OUTSIDE AIR TEMPERATURE SENSOR ERROR
ACT ERROR N/A N/A ACTUATOR ERROR
FREEZE ALARM N/A N/A Check if outdoor temperature is below the LOW Temp Lockout on set-
Table 7 — Menu Structure (cont)
PARAMETER
DEFAULT
VALUE
N/A N/A The checkout for the damper minimum position is based on the system.
PARAMETER
RANGE AND INCREMENT
F SUPPLY AIR TEMPERATURE CALIBRATION
F OUTSIDE AIR TEMPERATURE CALIBRATION
F RETURN AIR TEMPERATURE CALIBRATION
F DISCHARGE AIR TEMPERATURE CALIBRATION
minute increments
Allows for the operator to adjust for an out of calibration temperature sensor.
Allows for the operator to adjust for an out of calibration temperature sensor.
Allows for operator to adjust for an out of calibration humidity sensor.
Allows for the operator to adjust for an out of calibration temperature sensor.
Allows for operator to adjust for an out of calibration humidity sensor.
Allows for the operator to adjust for an out of calibration temperature sensor.
TIME DELAY ON 2nd STAGE ECONOMIZING When in economizing mode this is the delay for the high speed fan to try to satisfy the call for second stage cooling before the first stage mechan­ical cooling is enabled.
See Table 8.
Exhaust fan contacts enable during the DAMPER OPEN test. Make sure you pause in the mode to allow exhaust contacts to energize due to the delay in the system.
• NONE — not action taken
• ERV — 24 Vac out. Turns on or signals an ERV that the conditions are not good for economizing but are for ERV operation.
• SYS — 24 Vac out. Issues a system alarm
Mixed air sensor has failed or become disconnected - check wiring then replace sensor if the alarm continues.
SENSOR ERROR
2
CO
sensor has failed, gone out of range or become disconnected -
2
check wiring then replace sensor if the alarm continues.
Outdoor air enthalpy sensor has failed or become disconnected - check wiring then replace sensor if the alarm continues.
Return air enthalpy sensor has failed or become disconnected - check wiring then replace sensor if the alarm continues.
Discharge air sensor has failed or become disconnected - check wiring then replace sensor if the alarm continues.
Outdoor air temperature sensor has failed or become disconnected ­check wiring then replace if the alarm continues.
Actuator has failed or become disconnected - check for stall, over volt­age, under voltage and actuator count. Replace actuator if damper is movable and supply voltage is between 21.6 V and 26.4 V. Check actu­ator count on STATUS menu.
point menu. Check if Mixed air temperature on STATUS menu is below the Lo Setpoint on Advanced menu. When conditions are back in normal range then the alarm will go away.
NOTES
31
Page 32
MENU PARAMETER
SHUTDOWN ACTIVE N/A N/A AUX2 IN is programmed for SHUTDOWN and 24 V has been applied to
DMP CAL RUNNING N/A N/A DAMPER CALIBRATION ROUTINE RUNNING
ALARMS
(CONT)
DA SENS ALM N/A N/A DISCHARGE AIR TEMPERATURE SENSOR ALARM
SYS ALARM N/A N/A When AUX1-0 is set to SYS and there is any alarm (e.g., failed sensors,
ACT UNDER V N/A N/A ACTUATOR VOLTAGE LOW
ACT OVER V N/A N/A ACTUATOR VOLTAGE HIGH
ACT STALLED N/A N/A ACTUATOR STALLED
Table 7 — Menu Structure (cont)
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND INCREMENT
AUX2 IN terminal.
If DCV Auto enable has been programmed, when the W7220 is complet­ing a calibration on the dampers, this alarm will display. Wait until the calibration is completed and the alarm and RA sensors for DCV calibration; set up in the Advanced setup menu.
Discharge air temperature is out of the range set in the ADVANCED SETUP Menu. Check the temperature of the discharge air.
etc.), the AUX1-0 terminal has 24 Vac out.
Voltage received by actuator is above expected range.
Voltage received by actuator is below expected range.
Actuator stopped before achieving commanded position.
NOTES
will
go away. Must have OA, MA
LEGEND
CLO — Compressor Lockout ERV — Energy Recovery Ventilator LCD — Liquid Crystal Display MA Mixed Air MAT — Mixed Air Temperature N/A Not Applicable OA Outdoor Air OAT — Outdoor Air Temperature OCC — Occupied RA Return Air RAT — Return Air Temperature RTU — Rooftop Unit SYS — System
NOTES:
1. Table 7 illustrates the complete hierarchy. Your menu parame­ters may be different depending on your configuration. For example if you do not have a DCV (CO the DCV parameters appear.
2. When values are displayed, pressing and holding the or button causes the display to automatically increment.
3. ERV Operation: When in cooling mode AND the conditions are NOT OK for economizing - the ERV terminal will be energized. In the Heating mode, the ERV terminal will be energized when
) sensor, then none of
2
the OA is below the ERV OAT setpoint in the setpoint menu.
For damper minimum position settings and checkout menu readings, see Table 8. For dry bulb operation with a 1 speed in­door fan, with or without DCV, see Tables 9 and 10. For enthal­py operation with a 1 speed indoor fan, with or without DCV, see Tables 11 and 12. For dry bulb operation with a 2 speed in­door fan, with or without DCV, see Tables 13 and 14. For en­thalpy operation with a 2 speed indoor fan, with or without DCV, see Tables 15 and 16.
4. STATUS —> OCCUPIED — The factory-standard Occupancy signal originates with a thermostat or other controller call for indoor fan operation at CTB terminal G. This signal passes through the Central Terminal Board’s OCCUPIED jumper JMP1 to the ECONO connector and to the W7220’s OCC input termi­nal. An external timeclock or relay is required to implement an Occupancy schedule on the economizer damper position.
5. STATUS —> MA TEMP, SETPOINTS —> MAT SET — The W7220 menu parameters and labels include designations MA, MAT and Mixed Air for the economizer cooling control sensor. On these rooftop units, the economizer control sensor is located downstream of the evaporator/indoor coil in the supply fan section where this sensor is designated as Supply Air Tem­perature (SAT) sensor.
6. SETPOINTS —> DRYBLB SET — This point is not displayed if a Return Air (differential) temperature sensor or an Outdoor Air enthalpy sensor is connected.
7. SYSTEM SETUP parameters must be configured as noted for 2-Speed unit operation:
EQUIPMENT = CONV AUX2 IN = W FAN SPEED = 2SPEED
32
Page 33
Table 8 — Damper Minimum Position Settings and Readings on Checkout Menu
DEMAND CONTROLLED
VENTILATION
SENSOR)
(CO
2
NO
YES
FAN SPEED SETPOINTS CHECKOUT
1
2
1
2
MIN POS VMAX–HS
N/A N/A MIN POS H VMAX–HS MIN POS L VMAX–LS
VENT MIN VMAX–HS
VENT MAX VMAX–HS
VENT MIN H VMAX–HS
VENT MAX H VMAX–LS
VENT MIN L N/A VENT MAX L N/A
Table 9 — Dry Bulb Operation No DCV (CO
DEMAND
CONTROLLED
VENTILATION (DCV)
NONE NO
NONE YES
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have not been satisfied.
OUTSIDE AIR
GOOD TO
ECONOMIZE
Y1-I Y2-I
OFF OFF HIGH 0v/Off 0v/Off MIN POS Closed
ON OFF HIGH 24v/On 0v/Off MIN POS Closed
ON ON HIGH 24v/On 24v/On MIN POS Closed
OFF OFF HIGH 0v/Off 0v/Off MIN POS Closed
ON OFF HIGH 0v/Off 0v/Off
ON ON HIGH 24v/On 0v/Off*
FAN
SPEED
Y1-O Y2-O OCCUPIED UNOCCUPIED
Sensor) — 1 Speed Fan
2
MIN POS to Full
Open
MIN POS to Full
Open
Closed to Full-Open
Closed to Full-Open
Table 10 — Dry Bulb Operation With DCV (CO2 Sensor) — 1 Speed Fan
DEMAND
CONTROLLED
VENTILATION (DCV)
Below CO
Above CO
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have not been satisfied.
2
2
Set
Set
OUTSIDE AIR
GOOD TO
ECONOMIZE
No
Yes
No
Yes
Y1-I Y2-I
OFF OFF HIGH 0v/Off 0v/Off VENTMIN Closed
ON OFF HIGH 24v/On 0v/Off VENTMIN Closed
ON ON HIGH 24v/On 24v/On VENTMIN Closed
OFF OFF HIGH 0v/Off 0v/Off VENTMIN Closed
ON OFF HIGH 0v/Off 0v/Off
ON ON HIGH 24v/On 0v/Off
OFF OFF HIGH 0v/Off 0v/Off
ON OFF HIGH 24v/On 0v/Off
ON ON HIGH 24v/On 24v/On
OFF OFF HIGH 0v/Off 0v/Off
ON OFF HIGH 0v/Off 0v/Off
ON ON HIGH 24v/On 0v/Off*
FAN
SPEED
Y1-O Y2-O OCCUPIED UNOCCUPIED
VENTMIN to
Full-Open
VENTMIN to
Full-Open
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
Full-Open
VENTMIN to
Full-Open
Closed to Full-Open
Closed to Full-Open
Closed
Closed
Closed
Closed
Closed to Full-Open
Closed to Full-Open
33
Page 34
Table 11 — Enthalpy Operation No DCV (CO
DEMAND
CONTROLLED
VENTILATION (DCV)
NONE NO
NONE YES
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have not been satisfied.
OUTSIDE AIR
GOOD TO
ECONOMIZE
Y1-I Y2-I
OFF OFF HIGH 0v/Off 0v/Off MIN POS Closed
ON OFF HIGH 24v/On 0v/Off MIN POS Closed
ON ON HIGH 24v/On 24v/On MIN POS Closed
OFF OFF HIGH 0v/Off 0v/Off MIN POS Closed
ON OFF HIGH 0v/Off 0v/Off
ON ON HIGH 24v/On 0v/Off*
FAN
SPEED
Y1-O Y2-O OCCUPIED UNOCCUPIED
Sensor) — 1 Speed Fan
2
MIN POS to Full
Open
MIN POS to Full
Open
Closed to Full-Open
Closed to Full-Open
Table 12 — Enthalpy Operation With DCV (CO2 Sensor) — 1 Speed Fan
DEMAND
CONTROLLED
VENTILATION (DCV)
Below CO
Above CO
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have not been satisfied.
2
2
Set
Set
OUTSIDE AIR
GOOD TO
ECONOMIZE
No
Yes
No
Yes
Y1-I Y2-I
OFF OFF HIGH 0v/Off 0v/Off VENTMIN Closed
ON OFF HIGH 24v/On 0v/Off VENTMIN Closed
ON ON HIGH 24v/On 24v/On VENTMIN Closed
OFF OFF HIGH 0v/Off 0v/Off VENTMIN Closed
ON OFF HIGH 0v/Off 0v/Off
ON ON HIGH 24v/On 0v/Off
OFF OFF HIGH 0v/Off 0v/Off
ON OFF HIGH 24v/On 0v/Off
ON ON HIGH 24v/On 24v/On
OFF OFF HIGH 0v/Off 0v/Off
ON OFF HIGH 0v/Off 0v/Off
ON ON HIGH 24v/On 0v/Off*
FAN
SPEED
Y1-O Y2-O OCCUPIED UNOCCUPIED
VENTMIN to
Full-Open
VENTMIN to
Full-Open
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
Full-Open
VENTMIN to
Full-Open
Closed to Full-Open
Closed to Full-Open
Closed
Closed
Closed
Closed
Closed to Full-Open
Closed to Full-Open
Table 13 — Dry Bulb Operation No DCV (CO2 Sensor) — 2 Speed Fan
DEMAND
CONTROLLED
VENTILATION (DCV)
NONE NO
NONE YES
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have not been satisfied.
OUTSIDE AIR
GOOD TO
ECONOMIZE
Y1-I Y2-I
OFF OFF LOW 0v/Off 0v/Off MIN POS Closed
ON OFF LOW 24v/On 0v/Off MIN POS Closed
ON ON HIGH 24v/On 24v/On MIN POS Closed
OFF OFF LOW 0v/Off 0v/Off MIN POS Closed
ON OFF LOW 0v/Off 0v/Off
ON ON HIGH 24v/On 0v/Off*
FAN
SPEED
Y1-O Y2-O OCCUPIED UNOCCUPIED
MIN POS to Full
Open
MIN POS to Full
Open
Closed to Full-Open
Closed to Full-Open
34
Page 35
DEMAND
CONTROLLED
VENTILATION (DCV)
Table 14 — Dry Bulb Operation With DCV (CO
OUTSIDE AIR
GOOD TO
ECONOMIZE
Y1-I Y2-I
FAN
SPEED
Y1-O Y2-O OCCUPIED UNOCCUPIED
Sensor) — 2 Speed Fan
2
OFF OFF LOW 0v/Off 0v/Off VENTMIN Closed
No
ON OFF LOW 24v/On 0v/Off VENTMIN Closed
ON ON HIGH 24v/On 24v/On VENTMIN Closed
Below CO
2
Set
Yes
No
Above CO
Set
2
Yes
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have not been satisfied.
OFF OFF LOW 0v/Off 0v/Off VENTMIN Closed
ON OFF LOW 0v/Off 0v/Off
ON ON HIGH 24v/On 0v/Off
OFF OFF LOW 0v/Off 0v/Off
ON OFF LOW 24v/On 0v/Off
ON ON HIGH 24v/On 24v/On
OFF OFF LOW 0v/Off 0v/Off
ON OFF LOW 0v/Off 0v/Off
ON ON HIGH 24v/On 0v/Off*
VENTMIN to
Full-Open
VENTMIN to
Full-Open
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
Full-Open
VENTMIN to
Full-Open
Closed to Full-Open
Closed to Full-Open
Closed
Closed
Closed
Closed
Closed to Full-Open
Closed to Full-Open
Table 15 — Enthalpy Operation No DCV (CO2 Sensor) — 2 Speed Fan
DEMAND
CONTROLLED
VENTILATION (DCV)
NO CO
SENSOR
2
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have not been satisfied.
OUTSIDE AIR
GOOD TO
ECONOMIZE
NO
YES
Y1-I Y2-I
FAN
SPEED
Y1-O Y2-O OCCUPIED UNOCCUPIED
OFF OFF LOW 0v/Off 0v/Off MIN POS Closed
ON OFF LOW 24v/On 0v/Off MIN POS Closed
ON ON HIGH 24v/On 24v/On MIN POS Closed
OFF OFF LOW 0v/Off 0v/Off MIN POS Closed
ON OFF LOW 0v/Off 0v/Off
ON ON HIGH 24v/On 0v/Off*
MIN POS to Full
Open
MIN POS to Full
Open
Closed to Full-Open
Closed to Full-Open
Table 16 — Enthalpy Operation With DCV (CO2 Sensor) — 2 Speed Fan
DEMAND
CONTROLLED
VENTILATION (DCV)
Below CO
Above CO
2
2
Set
Set
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have not been satisfied.
OUTSIDE AIR
GOOD TO
ECONOMIZE
No
Yes
No
Yes
Y1-I Y2-I
FAN
SPEED
Y1-O Y2-O OCCUPIED UNOCCUPIED
OFF OFF LOW 0v/Off 0v/Off VENTMIN Closed
ON OFF LOW 24v/On 0v/Off VENTMIN Closed
ON ON HIGH 24v/On 24v/On VENTMIN Closed
OFF OFF LOW 0v/Off 0v/Off VENTMIN Closed
ON OFF LOW 0v/Off 0v/Off
ON ON HIGH 24v/On 0v/Off
OFF OFF LOW 0v/Off 0v/Off
ON OFF LOW 24v/On 0v/Off
ON ON HIGH 24v/On 24v/On
OFF OFF LOW 0v/Off 0v/Off
ON OFF LOW 0v/Off 0v/Off
ON ON HIGH 24v/On 0v/Off*
VENTMIN to
Full-Open
VENTMIN to
Full-Open
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
Full-Open
VENTMIN to
Full-Open
Closed to Full-Open
Closed to Full-Open
Closed
Closed
Closed
Closed
Closed to Full-Open
Closed to Full-Open
35
Page 36
Fig. 51 — Single Enthalpy Curve Boundaries
ECONOMIZING
AVAILABLE
NOT AVAILABLE
ENTHA
LPY
RA HUM (%RH)
RA TEMP
TEMPERATURE
ABSOLUTE HUMIDITY
ES5
ES4
ES3
ES2 ES1
HL
P1 (T,RH)
P2 (T,RH)
SINGLE ENTHALPY
DUAL ENTHALPY
HIGH LIMIT
Table 17 — Single Enthalpy and Dual Enthalpy High Limit Curves
ENTHALPY
CURVE
ES1 80 60 28.0 80 36.8 66.3 80.1 ES2 75 57 26.0 75 39.6 63.3 80.0 ES3 70 54 24.0 70 42.3 59.7 81.4 ES4 65 51 22.0 65 44.8 55.7 84.2 ES5 60 48 20.0 60 46.9 51.3 88.5
HL 86 66 32.4 86 38.9 72.4 80.3
TEMP. DRY
BULB (F)
TEMP.
DEWPOINT (F)
ENTHALPY SETTINGS — When the OA temperature, en­thalpy and dew point are below the respective setpoints, the Outdoor Air can be used for economizing. Fig. 51 shows the new single enthalpy boundaries in the W7220. There are 5 boundaries (setpoints ES1 through ES5), which are defined by dry bulb temperature, enthalpy and dew point.
Refer to Table 17 for ENTH CURVE setpoint values.
The W7220 calculates the enthalpy and dew point using the OA temperature and humidity input from the OA enthalpy sen­sor. When the OA temperature, OA humidity and OA dew point are all below the selected boundary, the economizer sets the economizing mode to YES, economizing is available.
When all of the OA conditions are above the selected boundary, the conditions are not good to economize and the mode is set to NO.
Fig. 51 shows the 5 current boundaries. There is also a high limit boundary for differential enthalpy. The high limit bound­ary is ES1 when there are no stages of mechanical cooling en­ergized and HL (high limit) when a compressor stage is ener­gized.
Table 17 provides the values for each boundary limit. TWO-SPEED FAN OPERATION — The W7220 controller
has the capability to work with a system using a 2-speed supply fan. The W7220 does not control the supply directly but uses the following input status to determine the speed of the supply fan and controls the OA damper to the required position, see Table 18.
STATE FAN SPEED
Table 18 — Fan Speed
OCC Low
Y1 Low Y2 High
W High
ENTHALPY
(btu/lb/da)
POINT P1 POINT P2
TEMP. (F)
HUMIDITY
(%RH)
TEMP. (F)
HUMIDITY
(%RH)
The W (heating mode) is not controlled by the W7220 but it requires the status to know where to position the OA damper for minimum position for the fan speed.
The 2 speed fan delay is available when the system is pro­grammed for 2 speed fan (in the System Setup menu item). The 2 speed fan delay is defaulted to 5 minutes and can be changed in the Advanced Setup menu item. When the unit has a call for Y1 In and in the free cooling mode and there is a call for Y2 In, the 2-speed fan delay starts and the OA damper will modulate 100% open, the supply fan should be set to high speed by the unit controller.
After the delay one of two actions will happen:
• The Y2 In call will be satisfied with the damper 100%
open and fan on high speed and the call will turn off
OR
• If the call for additional cooling in the space has not been
satisfied then the first stage of mechanical cooling will
be enabled through Y1 Out or Y2 Out. CHECKOUT — Inspect all wiring connections at the
economizer module’s terminals, and verify compliance with the installation wiring diagrams.
For checkout, review the Status of each configured parame­ter and perform the Checkout tests.
NOTE: For information about menu navigation and use of the keypad see Interface Overview on page 26.
36
Page 37
WARNING
Failure to follow this warning could result in personal injury, property damage, or death.
Before performing service or maintenance operations on unit, always turn off main power switch to unit and install lock(s) and lockout tag(s). Unit may have more than one power switch. Ensure electrical service to rooftop unit agrees with voltage an amperage listed on the unit rating plate.
If any wiring changes are required, first be sure to re­move power from the Economizer module before starting work. Pay particular attention to verifying the power con­nection (24 Vac).
Power Up apply power.
Initial Menu Display plays on the first line and economizer W7220 on the second line. After a brief pause, the revision of the software appears on the first line and the second line will be blank.
Power Loss (Outage or Brownout) vanced settings are restored after any power loss or interrup­tion.
NOTE: All settings are stored in non-volatile flash memory. Status
rameter values for the various devices and sensors configured. NOTE: For information about menu navigation and use of the
keypad see Interface Overview on page 26.
Checkout Tests test the damper operation and any configured outputs. Only items that are configured are shown in the Checkout menu.
the keypad see Interface Overview on page 26.
1. Scroll to the desired test in the Checkout menu using
2. Press the button to select the item.
3. RUN? appears.
4. Press the button to start the test.
5. The unit pauses and then displays IN PROGRESS.
6. When the test is complete, DONE appears.
7. When all desired parameters have been tested, press the
stallation or at any time during the operation of the system as a test that the system is operable.
— After the W7220 module is mounted and wired,
— On initial start up, Honeywell dis-
— All setpoints and ad-
— Use the Status menu (see Table 7) to check the pa-
— Use the Checkout menu (on page 31) to
NOTE: For information about menu navigation and use of
To perform a Checkout test:
the and buttons.
(Menu Up) button to end the test.
The Checkout tests can all be performed at the time of in-

TROUBLESHOOTING

Alarms
— The economizer module provides alarm messages
that display on the 2-line LCD. NOTE: Upon power up, the module waits 60 minutes before
checking for alarms. This allows time for all the configured devices (e.g. sensors, actuator) to become operational. The exception is the SAT sensor which will alarm immediately.
If one or more alarms are present and there has been no key­pad activity for at least 5 minutes, the Alarms menu displays and cycles through the active alarms.
You can also navigate to the Alarms menu at any time. Clearing Alarms
the cause has been removed (e.g. replaced faulty sensor) the alarm can be cleared from the display.
To clear an alarm, perform the following:
1. Navigate to the desired alarm.
2. Press the button.
3. ERASE? displays.
4. Press the button.
5. ALARM ERASED displays.
6. Press the (Menu up/Exit) button to complete the action
and return to the previous menu. NOTE: If the alarm still exists after you clear it, it is redis-
played within 5 seconds.
— Once the alarm has been identified and
CAUTION
Failure to follow this caution may result in damage to equipment. Be sure to allow enough time for compressor start-up and shutdown between checkout tests so that you do not short-cycle the compressors.
Low Ambient Control (Factory Option) — If the
unit comes with Electro-Mechanical (EM) control, then no ad­justment is necessary.
If the unit comes with PremierLink™ or RTU Open control option, then refer to its installation control manual for details on adjusting “Cooling Lock-Out” setting and configure for your specific job requirements.
Staged Air Volume (SAV™) with Variable Fre­quency Drive (Factory Option) —
operating 50HC 2 stage cooling units equipped with the facto­ry-installed Staged Air Volume option, refer to the Variable Frequency Drive (VFD) Installation, Start-Up and Service In­structions.
For details on
ComfortLink Controls (Factory Option) — For
details on operating 50HC units equipped with the factory-in­stalled ComfortLink controls option, refer to Controls, Start­Up, Operation and Troubleshooting for 48/50HC 04-28 Single Package Rooftop Unit with ComfortLink Controls.
37
Page 38
Fig. 52 — 50HC14 Control Box Component Locations with ComfortLink Controls
38
Page 39
Fig. 53 — 50HC14 ComfortLink Control Wiring Diagram
39
Page 40
Fig. 54 — 50HC14 ComfortLink Power Wiring Diagram
40
Page 41
Fig. 55 — 50HC14 ComfortLink with Humidi-MiZer
41
®
Power Wiring Diagram
Page 42

PremierLink™ Controller (Factory Option)

Fig. 56 — PremierLink™ Controller
The PremierLink controller (see Fig. 56) is compatible with Carrier Comfort Network signed to allow users the access and ability to change factory­defined settings, thus expanding the function of the standard unit control board. CCN service access tools include System Pilot™, Touch Pilot™ and Service Tool. (Standard tier display tools Navigator™ and Scrolling Marquee are not suitable for use with latest PremierLink controller (Version 2.x).)
The PremierLink controller is factory-mounted in the 50HC**14 unit’s main control box to the left of the Central Terminal Board (CTB) (see Fig. 57). Factory wiring is com­pleted through harnesses connected to the CTB thermostat. Field connections are made at a 16-pole terminal block (TB3) located on the bottom shelf of the unit control box in front of
®
(CCN) devices. This control is de-
the PremierLink controller. The factory-installed PremierLink controller includes the supply-air temperature (SAT) sensor. The outdoor air temperature (OAT) sensor is included in the FIOP/accessory EconoMi$er 2 package.
The PremierLink controller requires the use of a Carrier electronic thermostat or a CCN connection for time broadcast to initiate its internal timeclock. This is necessary for broadcast of time of day functions (occupied/unoccupied).
NOTE: PremierLink controller is shipped in Sensor mode. To be used with a thermostat, the PremierLink controller must be configured to Thermostat mode. Refer to Premier­Link Configuration instructions for Operating Mode.
Fig. 57 — 50HC**14 Control Box Component Locations — PremierLink Controller Location
42
Page 43
Fig. 58 — PremierLink Wiring Schematic
43
Page 44
Fig. 59 — PremierLink™ Wiring Schematic with Humidi-MiZer
44
®
System Option
Page 45
Supply Air Temperature (SAT) Sensor — On
FIOP-equipped 50HC**14 units, the unit is supplied with a supply-air temperature (SAT) sensor (33ZCSENSAT). This sensor is a tubular probe type, approx 6-inches (152 mm) in length. It is a nominal 10k ohm thermistor.
The SAT is factory-wired. The SAT probe is wire-tied to the supply-air opening (on the horizontal opening end) in its ship­ping position. Remove the sensor for installation. Re-position the sensor in the flange of the supply-air opening or in the sup­ply air duct (as required by local codes). Drill or punch a hole in the flange or duct. Use the template provided in the unit control box. Use two field-supplied, self-drilling screws to se­cure the sensor probe in a horizontal orientation. See Fig. 60.
SUPPLY AIR TEMPERATURE SENSOR
SUPPLY AIR
RETURN AIR
Fig. 60 — Typical Mounting Location for Supply
Air Temperature (SAT) Sensor on Small Rooftop
Units
Table 19 — PremierLink Controller Sensor Usage
1
/2-in.
ROOF CURB
NOTE: Refer to PremierLink Controller Installation, Start-up, and Configuration Instructions for complete PremierLink con­troller configuration, operating sequences and troubleshooting information. Have a copy of this manual available at unit set­up.
NOTE: The sensor must be mounted in the discharge airstream downstream of the cooling coil and any heating devices. Be sure the probe tip does not come in contact with any of the unit’s heater surfaces.
OUTDOOR AIR TEMPERATURE (OAT) SENSOR — The OAT is factory-mounted in the EconoMi$er2 (FIOP or accessory). It is a nominal 10k ohm thermistor attached to an eyelet mounting ring.
ECONOMI$ER2 — The PremierLink controller is used with EconoMi$er2 (option or accessory) for outdoor air manage­ment. The damper position is controlled directly by the Pre­mierLink controller; EconoMi$er2 has no internal logic device.
Outdoor air management functions can be enhanced with
field-installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors) Space CO Outdoor air CO
sensor
2
sensor
2
Refer to Table 19 for accessory part numbers.
Field Connections — Field connections for accessory
sensor and input devices are made at the 16-pole terminal block (TB3) located beneath the PremierLink controller (See Fig. 58). Some input devices also require a 24-vac signal source; connect at CTB terminal R at “THERMOSTAT” con­nection strip for this signal source. See connections figures on following pages for field connection locations (and for contin­ued connections at the PremierLink controller board inputs). Route wires to control box as indicated in Fig. 37.
Table 20 provides a summary of field connections for units equipped with Space Sensor. Table 21 provides a summary of field connections for units equipped with Space Thermostat.
APPLICATION
Differential Dry Bulb Temperature
with PremierLink (PremierLink
requires 4-20 mA Actuator)
Single Enthalpy with PremierLink
(PremierLink requires 4-20mA
Differential Enthalpy with
PremierLink (PremierLink requires
NOTES: CO
Sensors (Optional):
2
33ZCSENCO2 — Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor. 33ZCASPCO2 — Aspirator box used for duct-mounted CO sensor.
Actuator)
4-20mA Actuator)
OUTDOOR AIR
TEMPERATURE
SENSOR
Included —
CRTEMPSN001A00
Included — Not Used
Included — Not Used
room
2
RETURN AIR
TEMPERATURE
SENSOR
Required —
33ZCT55SPT or
equivalent
33ZCT55CO2 — Space temperature and CO override. 33ZCT56CO2 — Space temperature and CO2 room sensor with override and setpoint.
OUTDOOR AIR
ENTHALPY SENSOR
——
Requires —
33CSENTHSW
Requires —
33CSENTHSW or
equivalent
RETURN AIR
ENTHALPY SENSOR
Requires —
33CSENTSEN or
equivalent
room sensor with
2
45
Page 46
Table 20 — Space Sensor Mode
TB3 TERMINAL FIELD CONNECTION INPUT SIGNAL
1 T55—SEN/T56—SEN Analog (10k thermistor) 2 RMTOCC Discrete, 24VAC 3 T55—SEN/T56—SEN Analog (10k thermistor) 4 CMPSAFE Discrete, 24VAC 5 T56—SET Analog (10k thermistor) 6 FSD Discrete, 24VAC 7 LOOP—PWR Analog, 24VDC 8 SPS Discrete, 24VAC
9 IAQ—SEN Analog, 4-20mA 10 FILTER Discrete, 24VAC 11 IAQ—COM/OAQ—COM/RH—COM Analog, 4-20mA 12 CCN + (RED) Digital, 5VDC 13 OAQ—SEN/RH—SEN Analog, 4-20mA 14 CCN Gnd (WHT) Digital, 5VDC 15 AUX OUT(Power Exhaust) (Output) Discrete 24VAC 16 CCN —(BLK) Digital, 5VDC
LEGEND
CCN Carrier Comfort Network (communication bus) CMPSAFE — Compressor Safety FILTER Filter Switch FSD Fire Shutdown IAQ Indoor Air Quality (CO OAQ Outdoor Air Quality (CO2) RH Relative Humidity SFS Supply Fan Status T55 Space Temperature Sensor T56 Space Temperature Sensor
)
2
Table 21 — Thermostat Mode
TB3 TERMINAL FIELD CONNECTION INPUT SIGNAL
1 RAT SEN Analog (10k thermistor)
2 G Discrete, 24VAC
3 RAT SEN Analog (10k thermistor)
4 Y1 Discrete, 24VAC
5 ——
6 Y2 Discrete, 24VAC
7 LOOP—PWR Analog, 24VDC
8 W1 Discrete, 24VAC
9 IAQ—SEN Analog, 4-20mA 10 W2 Discrete, 24VAC 11 IAQ—COM/OAQ—COM/RH—COM Analog, 4-20mA 12 CCN + (RED) Digital, 5VDC 13 OAQ—SEN/RH—SEN Analog, 4-20mA 14 CCN Gnd (WHT) Digital, 5VDC 15 AUX OUT (Power Exhaust) (Output) Discrete 24VAC 16 CCN — (BLK) Digital, 5VDC
LEGEND
CCN Carrier Comfort Network (communication bus) G—Thermostat Fan IAQ Indoor Air Quality (CO OAQ Outdoor Air Quality (CO RAT Return Air Temperature RH Relative Humidity W1 Thermostat Heat Stage 1 W2 Thermostat Heat Stage 2 Y1 Thermostat Cool Stage 1
)
2
)
2
Y2 Thermostat Cool Stage 2
46
Page 47
SPACE SENSORS — The PremierLink™ controller is
2
3
45
61
SW1
SEN
BRN (GND) BLU (SPT)
RED(+)
WHT(GND)
BLK(-)
CCN COM
SENSOR WIRING
SEN J6-7
J6-6
1
3
TB3 PL
SEN
2
3
45
61
SW1
SEN
SET
Cool Warm
BRN (GND)
BLU (SPT)
RED(+)
WHT(GND)
BLK(-)
CCN COM
SENSOR WIRING
JUMPER TERMINALS AS SHOWN
BLK (T56)
factory-shipped configured for Space Sensor Mode. A Carrier T-55 or T-56 space sensor must be used. T-55 space tempera­ture sensor provides a signal of space temperature to the Pre­mierLink controller. T-56 provides same space temperature sig­nal plus it allows for adjustment of space temperature setpoints from the face of the sensor by the occupants.
Fig. 63 — T-56 Internal Connections
TB3 PL
SEN J6-7
1
Fig. 61 — T-55 Space Temperature Sensor Wiring
Connect T-55
— See Fig. 61 for typical T-55 internal connec­tions. Connect the T-55 SEN terminals to TB3 terminals 1 and 3 (see Fig. 62).
Fig. 62 — PremierLink Controller T-55 Sensor
Connect T-56
— See Fig. 63 for T-56 internal connections. In­stall a jumper between SEN and SET terminals as illustrated. Connect T-56 terminals to TB3 terminals 1, 3 and 5 (see Fig. 64).
PL
J6-6
SEN
TB3
3
Jumper
SET
SET
5
J6-5
Fig. 64 — PremierLink Controller T-56 Sensor
CONNECT THERMOSTAT — A 7-wire thermostat con­nection requires a 24-v power source and a common connec­tion. Use the R and C terminals on the CTBT’s THERMO­STAT connection strip for these. Connect the thermostat’s Y1, Y2, W1, W2 and G terminals to PremierLink TB3 as shown in Fig. 65.
If the 50HC**14 unit is equipped with factory-installed smoke detector(s), disconnect the factory BLU lead at TB3-6 (Y2) before connecting the thermostat. Identify the BLU lead originating at CTB-DDC-1; disconnect at TB3-6 and tape off. Confirm that the second BLU lead at TB3-6 remains connected to PremierLink J4-8.
47
Page 48
8
7
6
5
4
3 2
1
2
1
HG
24 VAC
OR
24 VDC
NC
ALARM RELAY CONTACTS
COM NO
}
0-10VDC SIG COM 4-20mA
+
+
-
+
-
J3 J4
SEN J5-5
J5-3
COM
9
11
TB3
TB3
IAQ Sensor
PL
24 VAC
SPACE
THERMOSTAT
R
GJ4-12
Y1
Y2
W1
W2
C
CTB
THERMOSTAT
R
TB3
2
4
6
8
10
C
PL
J4-10
J4-8
J4-6
J4-4
CTB
THERMOSTAT
Fig. 65 — Space Thermostat Connections
If the 50HC**14 unit has an economizer system and free­cooling operation is required, a sensor representing Return Air Temperature must also be connected (field-supplied and in­stalled). This sensor may be a T-55 Space Sensor (see Fig. 61) installed in the space or in the return duct, or it may be sensor P/N 33ZCSENSAT, installed in the return duct. Connect this sensor to TB3-1 and TB3-3 per Fig. 62.
CONFIGURE THE UNIT FOR THERMOSTAT MODE — Connect to the CCN bus using a CCN service tool and navigate to PremierLink Configuration screen for Operat-
ing Mode. Default setting is Sensor Mode (value 1). Change the value to 0 to reconfigure the controller for Thermostat Mode.
When the PremierLink controller is configured for Thermo­stat Mode, these functions are not available: Fire Shutdown (FSD), Remote Occupied (RMTOCC), Compressor Safety (CMPSAFE), Supply Fan Status (SFS), and Filter Pressure Switch (FILTER).

Economizer Controls

INDOOR AIR QUALITY (CO2) SENSOR — The indoor air quality sensor accessory monitors space carbon dioxide (CO
) levels. This information is used to monitor IAQ levels.
2
Several types of sensors are available, for wall mounting in the space or in return duct, with and without LCD display, and in combination with space temperature sensors. Sensors use infra­red technology to measure the levels of CO
present in the
2
Fig. 66 — Indoor/Outdoor Air Quality (CO
(33ZCSENCO2)
Do not mount the IAQ sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources. Allow at least 3 ft (0.9 m) between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the re­turn airstream.
Wiring the Indoor Air Quality Sensor two 2-conductor 18 AWG (American Wire Gage) twisted-pair cables (unshielded) to connect the separate isolated 24 vac power source to the sensor and to connect the sensor to the con­trol board terminals.
To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. See Fig. 66. Connect the 4-20 mA terminal to terminal TB3-9 and connect the SIG COM terminal to terminal TB3-11. See Fig. 67.
space air.
The CO
sensors are all factory set for a range of 0 to 2000
2
ppm and a linear mA output of 4 to 20. Refer to the instructions supplied with the CO
sensor for electrical requirements and
2
terminal locations. See Fig. 66 for typical CO2 sensor wiring schematic.
To accurately monitor the quality of the air in the condi-
Fig. 67 — Indoor CO
tioned air space, locate the sensor near a return-air grille (if present) so it senses the concentration of CO space. The sensor should be mounted in a location to avoid di­rect breath contact.
leaving the
2
Refer to PremierLink Controller Installation, Start-up, and Configuration Instructions, for detailed configuration informa­tion.
OUTDOOR AIR QUALITY SENSOR (P/N 33ZCSENCO2 PLUS WEATHERPROOF ENCLOSURE) — The outdoor
air CO
sensor is designed to monitor carbon dioxide (CO2)
2
levels in the outside ventilation air and interface with the venti­lation damper in an HVAC system. The OAQ sensor is pack­aged with an outdoor cover. See Fig. 68. The outdoor air CO sensor must be located in the economizer outside air hood.
48
Typical Wiring Diagram
For each sensor, use
Sensor (33ZCSENCO2)
2
2
Connections
) Sensor
2
Page 49
COVER REMOVED SIDE VIEW
SEN J5-2
J5-3
COM
13
11
TB3
TB3
OAQ Sensor
PL
24 VAC
Fig. 68 — Outdoor Air Quality Sensor Cover
Wiring the Outdoor Air CO
Sensor A dedicated power
2
supply is required for this sensor. A two-wire cable is required to wire the dedicated power supply for the sensor. The two wires should be connected to the power supply and terminals 1 and 2.
To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the OAQ sen­sor. See Fig. 66. Connect the 4 to 20 mA terminal to the TB3­13 terminal of the 50HC**14. Connect the SIG COM terminal to the TB3-11 terminal of the 50HC**14. See Fig. 69.
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in permanent dam­age to the sensor.
DO NOT clean or touch the sensing element with chemical solvents as they can permanently damage the sensor.
IMPORTANT: UNIT PERFORMANCE HAZARD Failure to follow this caution will result in inaccurate
sensor readings. DO NOT mount the sensor in drafty areas such as near
heating or air-conditioning ducts, open windows, fans, or over heat sources such as baseboard heaters, radiators, or wall-mounted dimmers. Sensors mounted in those areas will produce inaccurate readings.
If the sensor is installed directly on a wall service, install the humidity sensor using 2 screws and 2 hollow wall anchors (field supplied). Do not over tighten screws. See Fig. 70.
MOUNTING HOLES
Io
Gnd
Vin
Vo
WIRING OPENING
Fig. 69 — Outdoor CO
Sensor Connections
2
SPACE RELATIVE HUMIDITY SENSOR OR HUMIDI­STAT CONNECTIONS
Space Relative Humidity Sensor connections
The acces­sory space relative humidity sensor (33ZCSENSRH-01) is in­stalled on an interior wall to measure the relative humidity of the air within the occupied space.
The use of a standard 2 X 4 inch electrical box to accommo­date the wiring is recommended for installation. The sensor can be mounted directly on the wall, if acceptable by local codes.
SW2
123456
ON
Fig. 70 — Space Relative Humidity Sensor
Installation
The sensor must be mounted vertically on the wall. The Carrier logo should be orientated correctly when the sensor is properly mounted.
Avoid corner locations. Allow at least 4 ft between the sen­sor and any corner. Airflow near corners tends to be reduced, resulting in erratic sensor readings. The sensor should be verti­cally mounted approximately 5 ft up from the floor, beside the space temperature sensor.
For wiring distances up to 500 feet, use a 3-conductor, 18 or 20 AWG cable. A CCN communication cable can be used, al­though the shield is not required. The shield must be removed from the sensor end of the cable if this cable is used. See Fig. 71 for wiring details.
49
Page 50
Io VoVin Gnd
BLACK
RED
BRN
BLU
R
TB3
J4-4
PL
Filter Switch (NO, close on rising pressure (high drop))
CTB
Thermostat
10
R
TB3
J4-6
PL
Fan (Pressure) Switch (NO, close on rise in pressure)
CTB
Thermostat
8
Fig. 71 — Space Relative Humidity Sensor
Connection
The power for the sensor is provided by the PremierLink™
controller on terminal J5-4 (+33 to +35vdc).
To wire the sensor:
1. At the sensor, remove 4 inches of the jacket from the ca­ble. Strip
1
/4 inch of insulation from each conductor. Route the cable through the wire clearance opening in the center of the sensor. See Fig. 70.
2. Connect a field-supplied BLACK wire to the sensor screw terminal marked Vin.
3. Connect a field-supplied RED wire into the sensor screw terminal marked Io.
4. Connect the field-supplied RED wire from the sensor to TB3-13.
5. Connect the field-supplied BLACK wire from the sensor to TB3-7.
Humidistat connections: A humidistat can not be directly connected to the PremierLink controller. Follow the instruc­tions on pages 22-24 to connect a humidistat or a thermostat as an electromechanical device.
SMOKE DETECTOR/FIRE SHUTDOWN (FSD) — This function is available only when the PremierLink controller is configured for (Space) Sensor Mode. The unit is factory-wired for PremierLink FSD operation when the PremierLink control­ler is factory-installed.
On 50HC**14 units equipped with factory-installed Smoke Detector(s), the smoke detector controller implements the unit shutdown through its NC contact set connected to the unit’s CTB input. The FSD function is initiated via the smoke detec­tor’s Alarm NO contact set. The PremierLink controller com­municates the smoke detector’s tripped status to the CCN building control. See Fig. 58, typical PremierLink controller wiring schematic.
FILTER STATUS SWITCH — This function is available only when the PremierLink controller is configured for (Space) Sensor Mode.
PremierLink controller can monitor return filter status in two ways: By monitoring a field-supplied/installed filter pres­sure switch or via supply fan runtime hours.
Using switch input:
pressure drop across the unit’s return filters. Connect one side of the switch’s NO contact set to CTB’s THERMOSTAT-R ter-
according to switch manufacturer’s instructions, to measure
minal. Connect the other side of the NO contact set to TB3-10. Setpoint for Dirty Filter is set at the switch. See Fig. 72.
— Install the dirty filter pressure switch
Fig. 72 — PremierLink Controller Filter Switch
Connection
When the filter switch’s NO contact set closes as filter pres­sure drop increases (indicating dirt-laden filters), the input sig­nal to the PremierLink controller causes the filter status point to read “DIRTY.”
Using Filter Timer Hours
Refer to the PremierLink Con­troller Installation, Start-up, and Configuration Instructions for instructions on using the PremierLink Configuration screens and on unit alarm sequence.
SUPPLY FAN STATUS SWITCH — The PremierLink controller can monitor supply fan operation through a field­supplied/installed differential pressure switch. This sequence will prevent (or interrupt) operation of unit cooling, heating and economizer functions until the pressure switch contacts are closed indicating proper supply fan operation.
Install the differential pressure switch in the supply fan sec­tion according to switch manufacturer’s instructions. Arrange the switch contact to be open on no flow and to close as pres­sure rises indicating fan operation.
Connect one side of the switch’s NO contact set to CTB’s THERMOSTAT-R terminal. Connect the other side of the NO contact set to TB3-8. Setpoint for Supply Fan Status is set at the switch. See Fig. 73.
Fig. 73 — PremierLink Controller Wiring Fan
Pressure Switch Connection
REMOTE OCCUPIED SWITCH — The PremierLink con­troller permits a remote timeclock to override the control’s on­board occupancy schedule and place the unit into Occupied mode. This function may also provide a “Door Switch” time delay function that will terminate cooling and heating functions after a 2 to 20 minute delay.
Connect one side of the NO contact set on the timeclock to CTB’s THERMOSTAT-R terminal. Connect the other side of the timeclock contact to the unit’s TB3-2 terminal (see Fig. 74).
Remote Occupied
Time Clock
LCTB
Thermostat
R
TB3
2
PL
J4-12
Fig. 74 — PremierLink Controller Wiring Remote
Occupied
50
Page 51
Refer to the PremierLink™ Controller Installation, Start-up,
J8-3
15
C
TB3
PL
PEC
TAN
Power Exhaust
CTB
THERMOSTAT
GRA
CCN Bus
J2-1
J2-2GND (WHT)
12
14
TB3
J2-3– (BLK) 16
TB3
TB3
PL
+ (RED)
and Configuration Instructions for additional information on configuring the PremierLink controller for Door Switch timer function.
POWER EXHAUST (OUTPUT) — Connect the accessory Power Exhaust contactor coil(s) per Fig. 75.
Fig. 75 — PremierLink Controller Power Exhaust
Output Connection
CCN COMMUNICATION BUS — The PremierLink con­troller connects to the bus in a daisy chain arrangement. Nega­tive pins on each component must be connected to respective negative pins, and likewise, positive pins on each component must be connected to respective positive pins. The controller signal pins must be wired to the signal ground pins. Wiring connections for CCN must be made at the 3-pin plug.
At any baud (9600, 19200, 38400 baud), the number of con­trollers is limited to 239 devices maximum. Bus length may not exceed 4000 ft, with no more than 60 total devices on any 1000-ft section. Optically isolated RS-485 repeaters are re­quired every 1000 ft.
NOTE: Carrier device default is 9600 baud.
Communications Bus Wire Specifications
The CCN Communication Bus wiring is field-supplied and field­installed. It consists of shielded 3-conductor cable with drain (ground) wire. The cable selected must be identical to the CCN Communication Bus wire used for the entire network.
See Table 22 for recommended cable.
Table 22 — Recommended Cables
NOTE: Conductors and drain wire must be at least 20 AWG, stranded, and tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyeth­ylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of –20°C to 60°C is required. Do not run communication wire in the same conduit as or next to any AC voltage wiring.
The communication bus shields must be tied together at each system element. If the communication bus is entirely within one building, the resulting continuous shield must be connected to ground at only one single point. If the communi­cation bus cable exits from one building and enters another building, the shields must be connected to the grounds at a lightning suppressor in each building (one point only).
Connecting CCN Bus NOTE: When connecting the communication bus cable, a
color code system for the entire network is recommended to simplify installation and checkout. See Table 23 for the recom­mended color code.
Table 23 — Color Code Recommendations
SIGNAL TYPE
+ Red 1
GROUND White 2
Black 3
CCN BUS WIRE
COLOR
CCN PLUG PIN
NUMBER
Connect the CCN (+) lead (typically RED) to the unit’s TB3-12 terminal. Connect the CCN (ground) lead (typically WHT) to the unit’s TB3-14 terminal. Connect the CCN (–) lead (typically BLK) to the unit’s TB3-16 terminal. See Fig. 76.
MANUFACTURER CABLE PART NO.
Alpha 2413 or 5463
American A22503
Belden 8772
Columbia 02525
Fig. 76 — PremierLink Controller CCN Bus
Connections
51
Page 52
RTU Open Controller System — The RTU Open
J4
J2J1
J5 J5
J22
J17
J19
J14
J11
J22
J3
J13
J12
J15
J20
Network Comm
Configurable - Input_8
24 VAC
Configurable - Input_5
24 VAC
Configurable - Input_3
24 VAC
Input_9 (Humidistat)
24 VAC
24 VAC
Input _8 (Enthalpy)
AO-1 (ECON)
Gnd
(OAT)
Gnd
(SAT)
Input_5 (SMK)
Input_4 (R)
BO-5 (Y1)
BO-4 (Y2)
BO-3 (W1)
BO-2 (W2)
BO-1 (G)
Gnd
Input_3 (X)
24 VAC IN
+24 VDC
Input_2 (CO2/RH)
Gnd
+24 VDC
Input_1 (CO2/RH)
Gnd
Board Power
(AO-1)
0-10VDC
4-20mA
BO-6 (H) Humidimizer
BO-7
(Reversing Valve/High Speed Fan/Y3)
BO-8 (Power Exhaust)
LonWorks Option Card Port
Example set for BACnet MS/TP and 76.8K baud (1, 2, and 4 ON) Recommended for all i-Vu Open installations
2N ro ,subdoM ,tenCAB)tupni pmet( TPSrotceleS locotorP
(LON connection J15)
SPT (common)
SPT (offset input)
*Remove both for 0-5V
AO-2
GND
(2-10V)
3-Volt Lithium Battery
BO-1 BO-2 BO-3 BO-4 BO-5
BO-6
BO-7
BO-8
VFD Output
controller is factory-mounted in the 50HC**14 unit’s main control box, to the left of the CTB. See Fig. 78. Factory wiring is completed through harnesses connected to the CTB. Field­connections for RTU Open controller sensors will be made at the Phoenix connectors on the RTU Open board. The factory­installed RTU Open controller includes the supply-air tempera­ture (SAT) sensor. The outdoor air temperature (OAT) sensor is included in the FIOP/accessory EconoMi$er2 package.
The RTU Open controller, see Fig. 77, provides expanded
stand-alone operation of the HVAC system plus connection
and control through communication with several Building Au­tomation Systems (BAS) through popular third-party network systems. The available network systems are BACnet* MP/TP, Modbus† and Johnson N2. Communication with LonWorks** is also possible by adding an accessory interface card to the RTU Open. Selection of the communication protocol and baud rate are made at on-board DIP switches.
Refer to Table 24, RTU Open Controller Inputs and Outputs for locations of all connections to the RTU Open controller board.
Fig. 77 — RTU Open Multi-Protocol Controller Board
* BACnet is a registered trademark of ASHRAE (American Society
of Heating, Refrigerating and Air-Conditioning Engineers). † Modbus is a registered trademark of Schneider Electric. ** LonWorks is a registered trademark of Echelon Corporation.
52
Page 53
Fig. 78 — RTU Open System Control Wiring Diagram
53
Page 54
Fig. 79 — RTU Open System Control Wiring Diagram with Humidi-MiZer® System Option
54
Page 55
Table 24 — RTU Open Controller Inputs and Outputs
POINT NAME
DEDICATED INPUTS
Space Temp / Zone Temp
Supply Air Temperature
Outside Air Temperature
Space Temperature Offset Pot
Safety Chain Feedback
Compressor Safety Status (1)
Fire Shutdown Status
Enthalpy Status
Humidistat Input Status
Zone Temperature
CONFIGURABLE INPUTS(4)
Indoor Air CO
Outdoor Air CO
Space Relative Humidity
Supply Fan Status (2)
Filter Status (2)
Door Contact (2)
Remote Occupancy input (2)
IGC input (2)
OUTPUTS
Economizer Output
Supply Fan VFD
Supply Fan Relay
Cool 1 Relay State
Cool 2 Relay State
Cool 3 Relay State
Heat 1 Relay State
Heat 2 Relay State
Power Exhaust Relay State
Dehumidification Relay
LEGEND
AI Analog Input AO Analog Output BI Binary Input BO Binary Output
(1)Safety Chain Feedback: 24Vac required at this terminal to provide “Run Enable” status. See Input/Output section for additional instruc­tions.
2
2
BACNET OBJECT
NAME
zone_temp AI (10K Thermistor) J20—1 & 2 Analog Input 10
sa_temp AI (10K Thermistor) J2—1 & 2 Analog Input 6
oa_temp AI (10K Thermistor) J2—3 & 4 Analog Input 7
stpt_adj_offset AI (100K Potentiometer) J20—3 & 4 Analog Input 11
safety_status BI (24 VAC) J1—9 Binary Input 4
comp_status BI (24 VAC) J1—2 Binary Input 3
firedown_status BI (24 VAC) J1—10 Binary Input 5
enthalpy_status BI (24 VAC) J2—6 & 7 Binary Input 8
humstat_status BI (24 VAC) J5—7 & 8 Binary Input 9
N/A N/A J13—1—4 Rnet
iaq AI (4-20 mA)
oaq AI (4-20 mA) Analog Input 1
space_rh AI (4-20 mA) Analog Input 10
sfan_status BI (24 VAC)
filter_status BI (24 VAC)
door_contact_status BI (24 VAC)
occ_contact_status BI (24 VAC)
igcovr_status BI (24 VAC)
econ_output AO (4-0mA) J2—5 Analog Output 1
vfd_output AO (2-10Vdc) J22—1 & 2 Analog Output 2
sfan BO Relay (24VAC, 1A) J1—4 Binary Output 1 (G)
comp_1 BO Relay (24VAC, 1A) J1—8 Binary Output 5 (Y1)
comp_2 BO Relay (24VAC, 1A) J1— 7 Binary Output 4 (Y2)
comp_3 BO Relay (24VAC, 1A) J11—5 & 6 Binary Output 7 (Y3)
heat_1 BO Relay (24VAC, 1A) J1—6 Binary Output 3 (W1)
heat_2 BO Relay (24VAC, 1A) J1—5 Binary Output 2 (W2)
pexh BO Relay (24VAC, 1A) J11—2 & 3 (N.O.) Binary Output 8 (PE)
dehum BO Relay (24VAC, 1A) J11—7 & 8 (N.O.) Binary Output 6
TYPE OF I/O
CONNECTION PIN
NUMBER(S)
J4—2 & 3 or J4—5 & 6
J5—1 & 2 or J5—3 & 4,
J5—5 & 6 or J5—7 & 8 (3)
(2)These inputs are configurable. If installed, they take the place of the default input on the specific channel. See appropriate Input Con­figuration Section for wiring and setup instructions. (3)Parallel pins J5—1 = J2—6, J5—3 = J1—10, J5—5 = J1—2 are used for field installation. (4)Refer to the input configuration and accessory sections of the RTU Open Multi-Protocol Controller Controls, Start-Up, Operation and Troubleshooting manual for more detail.
CHANNEL DESIGNATION
Analog Input 2
Binary Input 3, 5, 8, or 9, except where intrinsic input is used
Binary Input 3, 5, 8, or 9, except where intrinsic input is used
Binary Input 3, 5, 8, or 9, except where intrinsic input is used
Binary Input 3, 5, 8, or 9, except where intrinsic input is used
Binary Input 9. Mandatory input on gas heat units.
The RTU Open controller requires the use of a Carrier space sensor. A standard thermostat cannot be used with the RTU Open system.
SUPPLY AIR TEMPERATURE (SAT) SENSOR — On FIOP-equipped 50HC**14 unit, the unit is supplied with a sup­ply-air temperature (SAT) sensor (33ZCSENSAT). This sensor is a tubular probe type, approx 6-inches (152 mm) in length. It is a nominal 10k ohm thermistor.
The SAT is factory-wired. The SAT probe is wire-tied to the supply-air opening (on the horizontal opening end) in its ship­ping position. Remove the sensor for installation. Re-position the sensor in the flange of the supply-air opening or in the sup­ply air duct (as required by local codes). Drill or punch a
1
/2-in.
hole in the flange or duct. Use two field-supplied, self-drilling screws to secure the sensor probe in a horizontal orientation. See Fig. 60.
OUTDOOR AIR TEMPERATURE (OAT) SENSOR — The OAT is factory-mounted in the EconoMi$er2 (FIOP or accessory). It is a nominal 10k ohm thermistor attached to an
eyelet mounting ring. ECONOMI$ER2 — The RTU Open controller is used with
EconoMi$er2 (factory-installed option or field-installed acces­sory) for outdoor air management. The damper position is con­trolled directly by the RTU Open controller; EconoMi$er2 has no internal logic device.
55
Page 56
Outdoor air management functions can be enhanced with
OR SET SEN
OPB COM- PWR+
BLU (SPT)
BLK (STO)
24 VAC
SENSOR WIRING
POWER WIRING
BRN (COM)
NOTE: Must use a separate isolated transformer.
J20-3
J20-2
J20-1
field-installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors) Space CO Outdoor air CO
sensor
2
sensor
2
Field Connections — Field connections for accessory
sensors and input devices are made the RTU Open controller, at plugs J1, J2, J4, J5, J11 and J20. All field control wiring that connects to the RTU Open controller must be routed as shown in Fig. 37. The routing provides the UL required clearance be­tween high and low-voltage wiring. Connect to the wires to the removable Phoenix connectors and then reconnect the connec­tors to the board.
SPACE TEMPERATURE (SPT) SENSORS — There are two types of SPT sensors available from Carrier, resistive input non-communicating (T55, T56, and T59) and Rnet communi­cating (SPS, SPPL, SPP, and SPPF) sensors. Each type has a variety of options consisting of: timed override button, set point adjustment, a LCD screen, and communication tie in. Space temperature can be also be written to from a building network or zoning system. However, it is still recommended that return air duct sensor be installed to allow stand-alone op­eration for back-up. Refer to the configuration section for de­tails on controller configurations associated with space sensors.
Field connections to T-55, T-56 and T-59 are provided as
examples.
• 33ZCT55SPT, space temperature sensor with override button (T-55)
• 33ZCT56SPT, space temperature sensor with override button and setpoint adjustment (T-56)
• 33ZCT59SPT, space temperature sensor with LCD (liq­uid crystal display) screen, override button, and setpoint adjustment (T-59)
Use 20 gauge wire to connect the sensor to the controller.
The wire is suitable for distances of up to 500 ft. Use a three­conductor shielded cable for the sensor and setpoint adjustment connections. If the setpoint adjustment (slidebar) is not re­quired, then an unshielded, 18 or 20 gauge, two-conductor, twisted pair cable may be used.
Connect T-55 tions. Connect the T-55 SEN terminals to the RTU Open con­troller at J20-1 and J20-2. See Fig. 80.
See Fig. 61 for typical T-55 internal connec-
SEN J20-1
SEN
Jumper
J20-2
SET
SET
J20-3
Fig. 81 — RTU Open Controller T-56 Sensor
Connections
Connect T-59
The T-59 space sensor requires a separate, isolated power supply of 24 VAC. See Fig. 82 for internal con­nections at the T-59. Connect the SEN terminal (BLU) to the RTU Open controller at J20 (BRN) to J20 J20
-3.
-2. Connect the SET terminal (STO or BLK) to
-1. Connect the COM terminal
SEN
SEN
Fig. 80 — RTU Open Controller T-55 Sensor
Connect T-56 stall a jumper between SEN and SET terminals as illustrated. Connect T-56 terminals to the RTU Open controller at J20
-2 and J20-3 per Fig. 81.
J20
See Fig. 63 for T-56 internal connections. In-
Connections
J20-1
J20-2
-1,
Fig. 82 — Space Temperature Sensor Typical
Wiring (33ZCT59SPT)
INDOOR AIR QUALITY (CO
) SENSOR — The indoor
2
air quality sensor accessory monitors space carbon dioxide (CO
) levels. This information is used to monitor IAQ levels.
2
Several types of sensors are available, for wall mounting in the space or in return duct, with and without LCD display, and in combination with space temperature sensors. Sensors use infra­red technology to measure the levels of CO
present in the
2
space air.
The CO
sensors are all factory set for a range of 0 to 2000
2
ppm and a linear mA output of 4 to 20. Refer to the instructions supplied with the CO terminal locations. See Fig. 66 for typical CO
sensor for electrical requirements and
2
sensor wiring
2
schematic.
To accurately monitor the quality of the air in the condi­tioned air space, locate the sensor near a return-air grille (if present) so it senses the concentration of CO
leaving the space.
2
The sensor should be mounted in a location to avoid direct breath contact.
56
Page 57
Do not mount the IAQ sensor in drafty areas such as near
SW2
123456
ON
Io
Vin
Gnd
Vo
MOUNTING HOLES
WIRING OPENING
Vin - J4-1 or J4-4 24Vdc Io - J4-2 or J4-5 -20mA output
supply ducts, open windows, fans, or over heat sources. Allow at least 3 ft (0.9 m) between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the re­turn airstream.
Wiring the Indoor Air Quality Sensor
— For each sensor, use two 2-conductor 18 AWG (American Wire Gage) twisted­pair cables (unshielded) to connect the separate isolated 24 vac power source to the sensor and to connect the sensor to the con­trol board terminals.
To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. See Fig. 66. Connect the 4-20 mA terminal to the RTU Open con­troller at J4-2 and connect the SIG COM terminal to the RTU Open controller at J4-3. See Fig. 83.
IAQ Sensor
SEN
COM
J4-2
J4-3
24 VAC
Fig. 83 — RTU Open Controller/Indoor CO
Sensor
2
(33ZCSENCO2) Connections
OUTDOOR AIR QUALITY SENSOR (P/N 33ZCSENCO2 PLUS WEATHERPROOF ENCLOSURE) — The outdoor air CO
sensor is designed to monitor carbon dioxide (CO2)
2
levels in the outside ventilation air and interface with the venti­lation damper in an HVAC system. The OAQ sensor is pack­aged with an outdoor cover. See Fig. 68. The outdoor air CO sensor must be located in the economizer outside air hood.
Wiring the Outdoor Air CO
Sensor A dedicated power
2
supply is required for this sensor. A two-wire cable is required to wire the dedicated power supply for the sensor. The two wires should be connected to the power supply and terminals 1 and 2.
To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the OAQ sen­sor. See Fig. 66. Connect the 4 to 20 mA terminal to the RTU Open controller at J4 RTU Open controller at J4
-5. Connect the SIG COM terminal to the
-6. See Fig. 84.
SPACE RELATIVE HUMIDITY SENSOR OR HUMIDI­STAT
Humidi-MiZer
®
System Control Wiring In units equipped with the Humidi-MiZer option there are two pink (PNK) wires loose in the control box used to control the dehumidification function of the unit. These pink wires are meant to be tied to a space humidistat or thermidistat on an electromechanical unit. On RTU Open controller equipped units these pink wires must be connected to J11
-7 and 8 to allow the Open board to operate
the dehumidification function for the unit. Disconnect the J11 Phoenix style connector from the board and use the plug screws to secure the pink wires in pins 7 and 8, reconnect the plug to the board at J11.
Relative Humidity Sensors (Space or Duct Mounted)
The accessory space humidity sensor (33ZCSENSRH-01) or duct humidity sensor (33ZCSENDRH-01) is used to measure the relative humidity of air within the space or return air duct. The RH reading is used to control the Humidi-MiZer option of the rooftop unit. For wiring distances up to 500 ft (152 m), use a 3­conductor, 18 or 20 AWG shielded cable. The shield must be removed from the sensor end of the cable and grounded at the unit end. The current loop power for sensor is provided by the RTU Open controller as 24vdc. Refer to the instructions sup­plied with the RH sensor for the electrical requirements and terminal locations. RTU Open controller configurations must be changed after adding an RH sensor. See Fig. 85 and 86 for typical RH sensor wiring.
•J4
1 or J44 = 24vdc loop power
•J4
2 or J45 = 4-20mA signal input
NOTE: The factory default for dehumidification control is nor­mally open humidistat.
2
OAQ Sensor/RH Sensor
SEN
COM
24 VAC
Fig. 84 — RTU Open Controller/Outdoor CO
Sensor (33ZCSENCO2) Connections
J4-5
J4-6
2
Fig. 85 — Space Relative Humidity Sensor Typical
Wiring
57
Page 58
J4-1 or J4-4 + 24 VDC
SUPPLY VOLTAGE
J4-2 or J4-5 (-)4 to 20 mA Current
LOOP OUTPUT TO RTU OPEN
RELATIVE HUMIDITY SENSOR (POLARIZED MALE CONNECTOR)
4-20mAVAC
SPAN
ZERO
GND 0-5V
or
or
VDC
0-10V
123456
ON
Fig. 86 — Duct Relative Humidity Sensor Typical
Wiring
Humidistat
The accessory humidistat provides the RTU Open controller insight to the relative humidity in the space. The humidistat reads the RH level in the space and compares it to its setpoint to operate a dry contact. The humidistat is a dedi­cated input on the configurable input 9 and tells the RTU Open controller when the RH level is HIGH or LOW. The normal condition for humidity is LOW. A normally open humidistat is the factory default control for the Humidi-MiZer system option.
To wire in the field:
•J5
8 = 24 VAC source for dry contact
•J5
7 = Signal input
SMOKE DETECTOR/FIRE SHUTDOWN (FSD) — On 50HC**14 units equipped with factory-installed Smoke Detec­tor(s), the smoke detector controller implements the unit shut­down through its NC contact set connected to the unit’s CTB input. The FSD function is initiated via the smoke detector’s Alarm NO contact set. The RTU Open controller communi­cates the smoke detector’s tripped status to the BAS building control. See Fig. 78, (RTU Open Controller wiring diagrams).
The Fire Shutdown Switch configuration, MENU
fig
Inputsinput 5, identifies the normally open status of
Con-
this input when there is no fire alarm.

CONNECTING DISCRETE INPUTS

Filter Status
— The filter status accessory is a field-installed accessory. This accessory detects plugged filters. When install­ing this accessory, the unit must be configured for filter status by setting MENU
ConfigInputsinput 3, 5, 8, or 9 to
Filter Status and normally open (N/O) or normally closed (N/C). Input 8 or 9 is recommended for ease of installation. Re­fer to Fig. 77 and Fig. 78 or 79 for wire terminations at J5.
Fan Status
The fan status accessory is a field-installed ac­cessory. This accessory detects when the indoor fan is blowing air. When installing this accessory, the unit must be configured for fan status by setting MENU
ConfigInputsinput 3,
5, 8, or 9 to Fan Status and normally open (N/O) or normally
closed (N/C). Input 8 or 9 is recommended for ease of installa­tion. Refer to Fig. 77 and Fig. 78 or 79 for wire terminations at J5.
Remote Occupancy
The remote occupancy accessory is a field-installed accessory. This accessory overrides the unoccu­pied mode and puts the unit in occupied mode. When installing this accessory, the unit must be configured for remote occupan­cy by setting MENU
ConfigInputsinput 3, 5, 8, or 9 to
Remote Occupancy and normally open (N/O) or normally closed (N/C).
Also set MENU
Schedulesoccupancy source to DI on/
off. Input 8 or 9 is recommended for ease of installation. Refer to Fig. 77 and Table 24 for wire terminations at J5.
Power Exhaust (output)
The relay used by the RTU Open controller board to control power exhaust is a dry contact which means it does not have 24vac. This 24vac must be con­nected to the relay to allow it to operate the power exhaust re­lay in the PE accessory. A 24vac source must be provided to J11
-2 on the RTU Open controller board. This can be provided
by the unit’s transformer from various sources. The “R” termi­nal on the unit’s central terminal board (CTB) is a logical source. Refer to Fig. 77 and Fig. 78 or 79 for wire terminations at J11.

Communication Wiring Protocols

GENERAL — Protocols are the communication languages spoken by control devices. The main purpose of a protocol is to communicate information in the most efficient method possi­ble. Different protocols exist to provide different kinds of infor­mation for different applications. In the BAS application, many different protocols are used, depending on manufacturer. Proto­cols do not change the function of a controller; just make the front end user different.
The RTU Open controller can be set to communicate on four different protocols: BACnet, Modbus, N2, and LonWorks. Switch 3 (SW3) on the board is used to set protocol and baud rate. Switches 1 and 2 (SW1 and SW2) are used to set the board’s network address. See Fig. 87 and 88 for protocol switch settings and address switches. The third party connec­tion to the RTU Open controller is through plug J19. See Fig. 89 for wiring.
NOTE: Power must be cycled after changing the SW1 switch settings.
Refer to the RTU Open Controller Integration Guide for more detailed information on protocols, third party wiring, and networking.
-3
58
Page 59
SW3 Protocol Selection
0
1
2
3
4
5
6
7
8
9
MSB LSB
SW1 SW2
0
1
2
3
4
5
6
7
8
9
J19
NET+
NET-
SHLD
PROTOCOL DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1
BACnet MS/TP (Master) Unused OFF OFF OFF ON OFF
Modbus (Slave) Unused OFF OFF ON ON OFF
N2 (Slave) Unused OFF OFF OFF ON ON OFF OFF LonWorks Unused ON ON OFF ON OFF OFF ON
NOTE: DS = Dip Switch BACnet MS/TP SW3 example shown
Baud Rate Selections
BAUD RATE DS2 DS1
9600 OFF OFF 19,200 ON OFF 38,400 OFF ON 76,800 ON ON
COMM
OPTION
PORT
UNUSED
(OFF)
(ON)
PROTOCOL SELECTOR DIP SWITCHES
SET TO MSTP
(MASTER)
Select
Baud
Select
Baud
SET TO
38.4k
BAUD
Select Baud
Select Baud
Fig. 87 — RTU Open Controller SW3 Dip Switch Settings

Local Access

WALL MOUNTED EQUIPMENT TOUCH INTER­FACE — The Equipment Touch interface is a wall mounted interface used to connect to the RTU Open controller to access
the control information, read sensor values, and maintenance. This is an accessory interface that does not come with the RTU Open controller. You wire the Equipment Touch interface to the RTU Open controller’s J13 local access port. There are 2 password protected levels in the display (User and Admin). See the Equipment Touch Installation and Setup Guide for more in­formation. See Appendix A for navigation and screen content.
FIELD ASSISTANT — Field Assistant is a computer pro­gram included with the purchase of the Tech Tool Kit (USB­TKIT). This is a field Tech Tool to set-up, service, or download
Fig. 88 — RTU Open Controller Address Switches
application software to the RTU Open controller and includes a USB Link Cable. The link cable connects a USB port to the J12 local access port. The Field Assistant’s menu structure is similar and functions the same as i-Vu
®
controller. See Fig. 90.

RTU OPEN CONTROLLER TROUBLESHOOTING

Communication LEDs
The LEDs indicate if the controller is speaking to the devices on the network. The LEDs should re­flect communication traffic based on the baud rate set. The higher the baud rate the more solid the LEDs will appear. See Table 25.
NOTE: Refer to the RTU Open Multi-Protocol Controller Controls, Start-Up, Operation and Troubleshooting manual for complete configuration of the RTU Open controller, operating sequences and troubleshooting information. Refer to the RTU Open v3 Integration Guide for details on configuration and troubleshooting of connected networks. Have a copy of these manuals available at unit start-up.
Fig. 89 — Network Wiring
59
Page 60
7
CTB ECON (P’LINK: to J4-2) or (RTU Open: to J2-6)
LOW
GND
24V
Enthalpy Switch
GRA
BLK
RED
FACTORY WIRING HARNESS
PL6-1 (24-V)
PL6-4 (COM)
48TC
Access
Port
J12
P1 P1
Connect to computer’s USB port
Fig. 90 — PC Running Field Assistant
The LEDs on the RTU Open Control Board (see Fig. 77) show the status of certain functions
If this LED is on... Status is...
Power
Rx
Tx
BO#
The RTU Open controller has power
The RTU Open controller is receiving data from the network segment
The RTU Open controller is transmitting data over the network segment
The binary output is active
The Run and Error LEDs indicate control module and network status
If Run LED shows...
2 flashes per second
2 flashes per second
2 flashes per second
2 flashes per second
2 flashes per second
5 flashes per second
5 flashes per second
7 flashes per second
14 flashes per second
On
Off Normal
2 flashes, alternating with Run LED Five minute auto-restart delay after system error
3 flashes, then off Control module has just been formatted
4 flashes, then pause
On
On Exec start-up aborted, Boot is running
Off Firmware transfer in progress, Boot is running
7 flashes per second, alternating with Run LED Ten second recovery period after brownout
14 flashes per second, alternating with Run LED
On
Outdoor Air Enthalpy Control (P/N 33CSENTHSW) —
(33CSENTHSW) is available as a field-installed accessory to be used with the EconoMi$er2 damper system. The outdoor air enthalpy sensor is part of the enthalpy control. (The separate field-installed accessory return air enthalpy sensor (33CSENTSEN) is required for differential enthalpy control. See Fig. 91.)
Locate the enthalpy control in the economizer next to the Actuator Motor. Locate two GRA leads in the factory harness and connect the gray lead labeled “ESL” to the terminal labeled “LOW.” See Fig. 92. Connect the enthalpy control power input terminals to economizer actuator power leads RED (connect to 24V) and BLK (connect to GND).
The outdoor enthalpy changeover setpoint is set at the en­thalpy controller.
The enthalpy control
USB Link Kit
P5 P5
Connect to
the Local
Access port
-
+
MSB LSB
CR2032
SW1 SW2
COMM
OPTION
J15
on
RTU Open Controller
LOCAL
ACCESS
SW3
Table 25 — LEDs
And Error LED shows... Status is...
Two or more devices on this network have the same MSTP network address
Exec halted after frequent system errors or control pro­grams halted
Brownout
Failure. Try the following solutions:
· Turn the RTU Open controller off, then on.
· Format the RTU Open controller.
· Download memory to the RTU Open controller.
· Replace the RTU Open controller.
Fig. 91 — Enthalpy Switch (33CSENTHSW)
Connections
60
RNET
PORT
J13
+12 DVC Rnet­Rnet+ GND
J12
*Therm
*Therm
mA
mA
GND
GND
UI-10
UI-11
TXRX
J20
Page 61
DIFFERENTIAL ENTHALPY CONTROL — Differential enthalpy control is provided by sensing and comparing the out­side air and return air enthalpy conditions. Install the outdoor air enthalpy control as described above. Add and install a re­turn air enthalpy sensor.
RETURN AIR ENTHALPY SENSOR — Mount the return­air enthalpy sensor (33CSENTSEN) in the return-air section of the economizer. The return air sensor is wired to the enthalpy controller (33CSENTHSW). See Fig. 92.
– 4-20 MAIN
+ VDC OUT
OUTSIDE AIR ENTHALPY SWITCH
+ 24-36 VDC IN
– 4-20 MAIN OUT
24V
GND
LOW
RED
BLK
GRA

RETURN AIR ENTHALPY SENSOR

PL6-1 (24-V)
PL6-4 (COM)
CTB ECON
7
(P’LINK: to J4-2) or (RTU Open: to J2-6)
board may be necessary to complete the unit and smoke detec­tor configuration to meet project requirements.
Units equipped with factory-optional Return Air smoke de­tectors require a relocation of the sensor module at unit installa­tion. See Fig. 93 for the as shipped location.
Completing Installation of Return Air Smoke Sensor:
1. Unscrew the two screws holding the Return Air Smoke Detector assembly. See Fig. 94, Step 1. Save the screws.
2. Turn the assembly 90 and then rotate end to end. Make sure that the elbow fitting is pointing down. See Fig. 94, Step 2.
3. Screw the sensor and detector plate into its operating po­sition using screws from Step 1. See Fig. 94, Step 3.
4. Connect the flexible tube on the sampling inlet to the sampling tube on the basepan.
Return Air Smoke Detector (as shipped)
Fig. 92 — Outside and Return Air Enthalpy Sensor
Wiring
To wire the return air enthalpy sensor, perform the follow-
ing:
1. Use a 2-conductor, 18 or 20 AWG, twisted pair cable to connect the return air enthalpy sensor to the enthalpy controller.
2. Connect the field-supplied RED wire to (+) spade con­nector on the return air enthalpy sensor and the (+) termi­nal on the enthalpy controller. Connect the BLK wire to (–) spade connector on the return air enthalpy sensor and the (
) terminal on the enthalpy controller.
Smoke Detectors — Smoke detectors are available as
factory-installed options on 50HC**14 models. Smoke detec­tors may be specified for Supply Air only or for Return Air without or with economizer or in combination of Supply Air and Return Air. Return Air smoke detectors are arranged for vertical return configurations only. All components necessary for operation are factory-provided and mounted. The unit is factory-configured for immediate smoke detector shutdown operation; additional wiring or modifications to unit terminal
Fig. 93 — Return Air Smoke Detector, Shipping
Position
ADDITIONAL APPLICATION DATA — Refer to the Ap­plication Data sheet titled Factory Installed Smoke Detectors for Small and Medium Rooftop Units 2 to 25 Tons for discus­sions on additional control features of these smoke detectors including multiple unit coordination.
Step 1 Step 2 Step 3
Fig. 94 — Completing Installation of Return Air Smoke Sensor
61
Page 62
r
Economizer 2 Position Damper
Fig. 95 — EconoMi$er
Step 11 — Adjust Factory-Installed Options
SMOKE DETECTORS — Smoke detector(s) will be con­nected at the Controls Connections Board, at terminals marked “Smoke Shutdown.” Cut jumper JMP 3 when ready to ener­gize unit.
ECONOMI$ER IV OCCUPANCY SWITCH — Refer to Fig. 95 for general EconoMi$er IV wiring. External occupancy control is managed through a connection on the Controls Con­nections Board.
If external occupancy control is desired, connect a time clock or remotely controlled switch (closed for Occupied, open for Unoccupied sequence) at terminals marked OCCUPANCY. Cut jumper JMP 2 to complete the installation.
Step 12 — Install Accessories — Available acces-
sories include:
• Roof Curb (must be installed before unit)
• Thru-base connection kit (must be installed before unit is
set on curb)
• Manual outside air damper
• Two-Position motorized outside air damper
• EconoMi$er IV (with control and integrated barometric
relief)
• EconoMi$er2 (without control/for external signal and
integrated barometric relief)
• Barometric relief
• Power Exhaust
• Differential dry-bulb sensor (EconoMi$er IV)
• Outdoor enthalpy sensor
• Differential enthalpy sensor
• Time Guard II compressor anti-cycle control
• Outdoor coil protector grille
Unit Without Economizer o 2 Position Damper
®
IV Wiring
• Head pressure control
• Programmable setback thermostat
• Electrical/Mechanical thermostat and subbase
• Thermidistat device
• Humidistat
• Thermostat / Sensors
•CO
sensor
2
• DDC interface (PremierLink controller)
• Louvered hail guard
• Phase monitor control Refer to separate installation instructions for information on
installing these accessories.
Pre-Start and Start-Up — This completes the mechan-
ical installation of the unit. Refer to the unit’s Service Manual for detailed Pre-Start and Start-Up instructions. Download the latest versions from HVAC Partners (www.hvacpartners.com).
© Carrier Corporation 2017
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500157-01 Printed in U.S.A. Form 50HC-14-02SI Pg 62 12-17 Replaces: 50HC-14-01SI
Page 63

START-UP CHECKLIST

(Remove and use for job file)
NOTE: To avoid injury to personnel and damage to equipment or property when completing the procedures listed in this start-up checklist, use good judgment, follow safe practices, and adhere to the safety considerations/information as outlined in preceding sec­tions of this Installation Instructions document.
MODEL NO.: ____________________________________________ SERIAL NO.: ____________________________
I. PRE-START-UP
VERIFY THAT ALL PACKAGING MATERIALS HAVE BEEN REMOVED FROM UNITVERIFY INSTALLATION OF OUTDOOR AIR HOOD VERIFY INSTALLATION OF FLUE EXHAUST AND INLET HOOD VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT CHECK THAT INDOOR-AIR FILTERS ARE CLEAN AND IN PLACE CHECK THAT OUTDOOR AIR INLET SCREENS ARE IN PLACE VERIFY THAT UNIT IS LEVEL CHECK FAN WHEELS AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND VERIFY
SETSCREW IS TIGHT
VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED VERIFY THAT SCROLL COMPRESSORS ARE ROTATING IN THE CORRECT DIRECTION VERIFY INSTALLATION OF THERMOSTAT
II. START-UP
ELECTRICAL
SUPPLY VOLTAGE L1-L2 ____________ L2-L3 _____________ L3-L1 ___________ COMPRESSOR AMPS 1 L1 ____________ L2 _____________ L3 ___________ COMPRESSOR AMPS 2 L1 ____________ L2 _____________ L3 ___________ SUPPLY FAN AMPS L1 ____________ L2 _____________ L3 ___________
TEMPERATURES
OUTDOOR-AIR TEMPERATURE _____________ °F DB (DRY BULB) RETURN-AIR TEMPERATURE _____________ °F DB _____________ °F WB (WET BULB) COOLING SUPPLY AIR TEMPERATURE _____________ °F
PRESSURES
REFRIGERANT SUCTION CIRCUIT A _____________ PSIG
CIRCUIT B _____________ PSIG REFRIGERANT DISCHARGE CIRCUIT A _____________ PSIG CIRCUIT B _____________ PSIG
VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS
GENERAL
ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS (IF EQUIPPED) VERIFY SMOKE DETECTOR UNIT SHUTDOWN BY UTILIZING MAGNET TEST
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500157-01 Printed in U.S.A. Form 50HC-14-02SI Pg CL-1 12-17 Replaces: 50HC-14-01SI
Page 64
III. HUMIDI-MIZER SYSTEM START-UP
STEPS
1. CHECK CTB FOR JUMPER 5, 6, 7
JUMPER 5, 6, 7 MUST BE CUT AND OPEN
2. OPEN HUMIDISTAT CONTACTS 3. START UNIT IN COOLING (CLOSE Y1)
OBSERVE AND RECORD
A. SUCTION PRESSURE _____________ PSIG B. DISCHARGE PRESSURE _____________ PSIG C. ENTERING AIR TEMPERATURE _____________ °F D. LIQUID LINE TEMPERATURE AT OUTLET OR REHEAT COIL _____________ °F E. CONFIRM CORRECT ROTATION FOR COMPRESSOR F. CHECK FOR CORRECT RAMP-UP OF OUTDOOR FAN MOTOR AS CONDENSER COIL WARMS
4. CHECK UNIT CHARGE PER CHARGING CHART 5. SWITCH UNIT TO HIGH-LATENT MODE (SUBCOOLER) BY CLOSING HUMIDISTAT WITH Y1 CLOSED
OBSERVE
A. REDUCTION IN SUCTION PRESSURE (5 TO 7 PSI EXPECTED) B. DISCHARGE PRESSURE UNCHANGED C. LIQUID TEMPERATURE DROPS TO 50 TO 55°F RANGE D. LIQUID SOLENOID VALVE (LSV) ENERGIZED (VALVE CLOSES)
6. SWITCH UNIT TO DEHUMID (REHEAT) BY OPENING Y1
OBSERVE
A. SUCTION PRESSURE INCREASES TO NORMAL COOLING LEVEL B. DISCHARGE PRESSURE DECREASES (35 TO 50 PSI) C. LIQUID TEMPERATURE RETURNS TO NORMAL COOLING LEVEL D. LIQUID SOLENOID VALVE (LSV) ENERGIZED (VALVE CLOSES) E. DISCHARGE SOLENOID VALVE (DSV) ENERGIZED, VALVE OPENS
7. WITH UNIT IN DEHUMID MODE CLOSE W1
COMPRESSOR AND OUTDOOR FAN STOP; LSV AND DSV SOLENOIDS DE-ENERGIZED
8. OPEN W1 RESTORE UNIT TO DEHUMID MODE 9. OPEN HUMIDISTAT INPUT
COMPRESSOR AND OUTDOOR FAN STOP; LSV AND DSV SOLENOIDS DE-ENERGIZED
10. RESTORE SETPOINTS FOR THERMOSTAT AND HUMIDISTAT
REPEAT PROCESS FOR 2 COMPRESSOR SYSTEMS
© Carrier Corporation 2017
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500157-01 Printed in U.S.A. Form 50HC-14-02SI Pg CL-2 12-17 Replaces: 50HC-14-01SI
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
Loading...