injury or death. CAUTION is used to identify unsafe practices,
which may result in minor personal injury or product and
property damage. NOTE is used to highlight suggestions
which will result in enhanced installation, reliability, or
operation.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury
or death.
Before performing service or maintenance operations on
unit, turn off main power switch to unit and install lock(s)
and lockout tag(s). Ensure electrical service to rooftop unit
agrees with voltage and amperage listed on the unit rating
plate. Unit may have more than one power switch.
WARNING
UNIT DAMAGE HAZARD
Failure to follow this caution may cause equipment damage.
This unit uses a microprocessor-based electronic control
system. Do not use jumpers or other tools to short out components or to bypass or otherwise depart from recommended procedures. Any short-to-ground of the control board or
accompanying wiring may destroy the electronic modules
or electrical components.
IMPORTANT: This literature covers 48/50HC 04-28
models with ComfortLink Software version 3.X.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical shock
or other conditions which may cause personal injury or
property damage. Consult a qualified installer, service agency,
or your distributor or branch for information or assistance. The
qualified installer or agency must use factory-authorized kits or
accessories when modifying this product. Refer to the
individual instructions packaged with the kits or accessories
when installing.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloths for brazing operations and have a fire
extinguisher available. Read these instructions thoroughly and
follow all warnings or cautions attached to the unit. Consult
local building codes and appropriate national electrical codes
(in USA, ANSI/NFPA70, National Electrical Code (NEC); in
Canada, CSA C22.1) for special requirements.
It is important to recognize safety information. This is the
safety-alert symbol . When you see this symbol on the unit
and in instructions or manuals, be alert to the potential for
personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the safetyalert symbol. DANGER identifies the most serious hazards
which will result in severe personal injury or death.
WARNING signifies hazards which could result in personal
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and
gloves when handling parts and servicing air conditioning
equipment.
WARNING
If the information in this manual is not followed exactly, a
fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
•Do not try to light any appliance.
•Do not touch any electrical switch; do not use any
phone in your building.
•Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
•If you cannot reach your gas supplier, call the fire
department.
Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
3
AVERTISSEMENT
RISQUE D´INCENDIE OU D´EXPLOSION
Si les consignes de sécurité ne sont pas suivies à la lettre,
cela peut entraîner la mort, de graves blessures ou des dommages matériels.
Ne pas entreposer ni utiliser d´essence ni autres vapeurs ou
liquides inflammables à proximité de cet appareil ou de tout
autre appareil.
QUE FAIRE SI UNE ODEUR DE GAZ EST DÉTECTÉE
•Ne mettre en marche aucun appareil.
•Ne toucher aucun interrupteur électrique; ne pas
utiliser de téléphone dans le bâtiment.
•Quitter le bâtiment immédiatement.
•Appeler immédiatement le fournisseur de gaz en
utilisant le téléphone d´un voisin. Suivre les
instructions du fournisseur de gaz.
•Si le fournisseur de gaz n´est pas accessible, appeler le
service d´incendie.
L´installation et l´entretien doivent être effectués par un installateur ou une entreprise d´entretien qualifié, ou le fournisseur de gaz.
GENERAL
This publication contains Start-Up, Controls, Operation, and
Troubleshooting information for the 48/50HC rooftop units.
(See Table 1.) These units are equipped with ComfortLink controls version 3.X or higher and use Puron
®
refrigerant. The specific base unit installation instructions, service manual and/or
wiring label diagram may also be required in conjunction with
this book as a guide to a specific unit on the roof. All the units in
table 1 are Constant Volume (CV) or Staged Air Volume (SAV)
units that provide stand-alone or network operation.
The ComfortLink control system is a comprehensive unit-management system. The control system is easy to access, configure, diagnose and troubleshoot.
The ComfortLink controller is fully communicating and cableready for connection to the Carrier Comfort Network
building management system. The control provides high-speed
communications for remote monitoring via the Internet. Multiple units can be linked together (and to other ComfortLink controller equipped units) using a 3-wire communication bus.
®
(CCN)
The ComfortLink control system is easy to access through the use
of a unit-mounted display module. There is no need to bring a separate computer to this unit for start-up. Access to control menus is
simplified by the ability to quickly select from 11 menus. A scrolling readout provides detailed explanations of control information.
Only four, large, easy-to-use buttons are required to maneuver
through the entire controls menu. The display readout is designed
to be visible even in bright sunlight.
For added service flexibility, an accessory hand-held Navigator
module is also available. This portable device has an extended
communication cable that can be plugged into the unit’s communication network at the main control box. The Navigator display
provides the same menu structure, control access and display data
as is available at the unit-mounted scrolling marquee display.
Scrolling Marquee
This device is the keypad interface used to access the control information, read sensor values, and test the unit. The scrolling marquee is located in the main control box and is standard on all units.
The scrolling marquee display is a 4-key, 4-character, 16-segment
LED (light-emitting diode) display module. The display also contains an Alarm Status LED. (See Fig. 1.)
The display is easy to operate using 4 buttons and a group of 11
LEDs that indicate the following menu structures:
•Run Status
•Service Test
•Temperatures
•Pressures
•Set points
•Inputs
•Outputs
•Configuration
•Timeclock
•Operating Modes
•Alarms
Through the scrolling marquee, the user can access all of the inputs and outputs to check on their values and status, configure operating parameters plus evaluate the current decision status for operating modes. The control also includes an alarm history which
can be accessed from the display. In addition, through the scrolling
marquee, the user can access a built-in test routine that can be used
at start-up commissioning and to diagnose operational problems
with the unit. (See Table 2.)
MODE
Run Status
Service Test
Temperature
Pressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
Operating Modes
Alarms
Alarm Status
ESCAPE
ENTER
Fig. 1 — Scrolling Marquee
Accessory Navigator™ Display
The accessory hand-held Navigator display can be used with the
48/50HC units. (See Fig. 2.) The Navigator display operates the
same way as the scrolling marquee device. The Navigator display
is plugged into the LEN (local equipment network) port on either
CIB or the J3 port on the ECB (economizer control board).
4
RUN
STATUS
Auto View of
Run Status
(VIEW)
Software
Version
Numbers
(VERS)
Control
Modes
(MODE)
Cooling
Status
(COOL)
Heating
Status
(HEAT)
Economizer
Status
(ECON)
Outside Air
Unit Status
(OAU)
Component
Run Hours
(HRS)
Compressor
Starts
(STRT)
SERVICE
TEST
Service Test
Mode
(TEST)
Test Independent
Outputs
(INDP)
Test Fans
(FANS)
Test
Cooling
(COOL)
Test
Humidi-MiZer
(HMZR)
Test Heating
(HEAT)
Table 2 — Scrolling Marquee Mode and Menu Display Structure
All units are shipped from the factory with the scrolling marquee display, which is located in the main control box. (See
Fig. 1.) In addition, the ComfortLink control also supports the
use of the handheld Navigator display.
Both displays provide the user with an interface to the Com-fortLink control system. The displays have up and down arrow
CCN Configuration
(CCN)
keys, an ESCAPE key and an ENTER key. These keys are used
to navigate through the different levels of the display structure.
The Navigator display and the scrolling marquee operate in the
same manner, except that the Navigator display has multiple
lines of display and the scrolling marquee has a single line. All
further discussions and examples in this document will be
based on the scrolling marquee display. See Table 2 for the
menu structure.
The four keys are used to navigate through the display structure, which is organized in a tiered mode structure. If the buttons have not been used for a period, the display will default to
the AUTO VIEW display category as shown under the RUN
STATUS category. To show the top-level display, press the ESCAPE key until a blank display is shown. Then use the up and
down arrow keys to scroll through the top-level categories.
These are listed in Appendix A and will be indicated on the
scrolling marquee by the LED next to each mode listed on the
face of the display.
When a specific mode or sub-mode is located, push the ENTER
key to enter the mode. Depending on the mode, there may be additional tiers. Continue to use the up and down keys and the ENTER
keys until the desired display item is found. At any time, the user
can move back a mode level by pressing the ESCAPE key. Once
an item has been selected the display will flash showing the item,
followed by the item value and then followed by the item units (if
any).
Items in the Configuration and Service Test modes are password protected. The display will flash PASS and WORD when
5
required. Use the ENTER and arrow keys to enter the four digits of the password. The default password is 1111.
Pressing the ESCAPE and ENTER keys simultaneously will
scroll an expanded text description across the display indicating
the full meaning of each display point. Pressing the ESCAPE
and ENTER keys when the display is blank (MODE LED level)
will return the display to its default menu of rotating AUTO
VIEW display items. In addition, the password will need to be
entered again before changes can be made.
Changing item values or testing outputs is accomplished in the
same manner. Locate and display the desired item. If the display is in rotating auto-view, press the ENTER key to stop the
display at the desired item. Press the ENTER key again so that
the item value flashes. Use the arrow keys to change the value
of state of an item and press the ENTER key to accept it. Press
the ESCAPE key and the item, value or units display will resume. Repeat the process as required for other items.
There are some points that can be forced from the scrolling
marquee or the Navigator display. If the user needs to force a
variable, follow the same process as when editing a configuration parameter. A forced variable, regardless where the force
has come from will be displayed with a blinking “.” on a scrolling marquee and a blinking “f” on a Navigator display following its value. For example, if economizer commanded position
(EC.CP) is forced, the Navigator display shows “80f”, where
the “f” is blinking to signify a force on the point. The scrolling
marquee display shows “80.” Where the “.” is blinking to signify a force on the point. Remove the force by selecting the
point that is forced with the key ENTER and then pressing the
up and down arrow keys simultaneously. Depending on the
unit model, factory-installed options and field-installed accessories, some of the items in the various Mode categories may
not apply.
System Pilot™ and Touch Pilot™ Devices
The System Pilot device (33PILOT-01) and Touch Pilot device
(33CNTPILOT) can be used as CCN communication user-interfaces. These devices can be put on the CCN bus and addressed to communicate with any other device on the network.
Unlike the scrolling marquee and Navigator display, these pilots read the unit’s CCN tables and its CCN points can be monitored, forced, or configured. The Pilot devices can be used to
install and commission a 3V zoning system, linkage compatible air source, universal controller, and all other devices operating on the Carrier communicating network.
Additionally, the System Pilot device can serve as a wall-mounted temperature sensor for space temperature measurement. The
occupant can use the System Pilot device to change set points. A
security feature is provided to limit access of features for unauthorized users. See Fig. 3 for System Pilot device details.
CCN Tables and Display
In addition to the unit-mounted scrolling marquee display, the
user can also access the same information through the CCN tables by using the Service tool or other CCN programs/devices.
The variable names used for the CCN tables and the scrolling
marquee menus may be different and more items may be displayed in the CCN tables. Details on the CCN tables are included with the local display menus in Appendix A. Appendix
A is structured towards the organization of the local display
(scrolling marquee) menus. Because of the variety of CCN
programs and devices, the CCN tables, sub-tables, and points
are referenced within that organization.
NAVIGATE/
EXIT
SCROLL
+
-
PAGE
MODIFY/
SELECT
Fig. 3 — System Pilot User Interface
Force Hierarchy
There is a hierarchy in CCN with regards to forcing a point.
Programs and devices write a force at different priority levels.
A higher level (smaller number, 1 being the highest) will override a lower level force. The scrolling marquee uses a Control
Force at level 7. The Navigator writes a Service Force which is
level 3. System Pilot and Touch Pilot devices write Supervisor
Forces at level 4. Network programs can be set to write different level priority forces.
Generic Status Display Table
The GENERIC points table allows the service/installer the
ability to create a custom table in which up to 20 points from
the 5 CCN categories (Points, Config, Service-Config, Set
Point, and Maintenance) may be collected and displayed.
In the Service-Config table section, there is a table named
“GENERICS.” This table contains placeholders for up to 20
CCN point names and allows the user to decide which points
are displayed in the GENERIC points sub-table under the status display table. Each one of these placeholders allows the input of an 8-character ASCII string. Using a CCN interface, enter the Edit mode for the Service-Config table “GENERICS”
and enter the CCN name for each point to be displayed in the
custom points table in the order they will be displayed. When
done entering point names, download the table to the rooftop
unit control.
IMPORTANT: The computer system software (ComfortVIEW, Service Tool, etc.) that is used to interact with CCN
controls, always saves a template of items it considers as
static (e.g., limits, units, forcibility, 24-character text
strings, and point names) after the software uploads the
tables from a control. Thereafter, the software is only concerned with run time data like value and hardware/force status. With this in mind, it is important that anytime a change
is made to the Service-Config table “GENERICS” (which
in turn changes the points contained in the GENERIC point
table), that a complete new upload be performed.
6
This requires that any previous table database be completely
removed first. Failure to do this will not allow the user to display the new points that have been created and the CCN interface will have a different table database than the unit control.
Conventions Used in This Manual
The following conventions for discussing configuration points
for the local display (scrolling marquee or Navigator accessory) will be used in this manual.
Point names will be written with the Mode name first, then any
submodes, then the point name, each separated by an arrow
symbol (). Names will also be shown in bold and italics. As
an example, the Thermostat Control Type which is located in
the Configuration mode, and Unit sub-mode would be written
as Configuration
This path name will show the user how to navigate through the
local display to reach the desired configuration. The user would
scroll through the modes and sub-modes using the up and down
keys. The arrow symbol in the path name represents pressing
ENTER to move into the next level of the menu structure.
When a value is included as part of the path name, it will be
shown at the end of the path name after an equals sign. If the
value represents a configuration setting, an explanation will be
shown in parenthesis after the value. As an example, Configu-
ration
UNITT.CTL = 1 (1 Stage Y1).
Pressing the ESCAPE and ENTER keys simultaneously will
scroll an expanded text description of the point name across the
display. The expanded description is shown in the local display
tables but will not be shown with the path names in text.
The CCN point names are also referenced in the local display
tables for users configuring the unit with CCN software instead
of the local display. See Appendix A of this manual.
UNITT.C TL .
START-UP
IMPORTANT: Do not attempt to start unit, even momentarily, until all items on the Start-Up Checklist (see CL-1) and
the following steps have been read/completed.
Unit Preparation
Check that unit has been installed in accordance with these installation instructions and all applicable codes.
Compressor Mounting
Compressors are internally spring mounted. Do not loosen or
remove compressor hold-down bolts.
Refrigerant Service Ports
Each independent refrigerant system has a total of 3 Schradertype service gauge ports per circuit. One port is located on the
suction line, one on the compressor discharge line, and one on
the liquid line. Be sure that caps on the ports are tight.
Crankcase Heater(s)
Compressor crankcase heater operation varies depending on
the unit size and type. In general for all units, the crankcase
heaters are energized if there is power to the unit and the compressor is not operating.
IMPORTANT: Unit power must be on for 24 hours prior to
start-up. Otherwise, damage to compressor may result.
Compressor Rotation
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the
unit.
DO not bypass the VFD while running the motor. Do not
change VFD parameter associated with motor characteristics, these are factory programmed for motor protection.
Damage to the motor or the VFD can occur.
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit damage.
Improper wiring will cause compressor stoppage and
alarm. Correct wiring by switching leads as indicated below.
On 3-phase units, it is important to be certain the compressors
are rotating in the proper direction. To determine whether or
not compressors are rotating in the proper direction, use a
phase-rotation meter on the unit input power to check for L1L2-L3 or clockwise rotation or use the Service Test mode to
energize a compressor. If the compressor is rotating in the
wrong direction, the controls will stop the compressor and display alarm for “Circuit x Failure to Pressurize” where x is the
corresponding A or B compressor circuit.
NOTE: Indoor or outdoor fan rotation direction may not indicate
proper input power phase sequence, as some 3-phase units use single-phase fan motors.
To correct the wrong compressor rotation direction, perform
the following procedure:
1.Turn off power to the unit and lock out the power.
2.Switch any two of the incoming unit power leads.
3.Turn on power to the unit.
4.Verify corrected compressor rotation.
Power Supply
All 208/230-v units are factory wired for 230-v power supply.
If the 208/230-v unit is to be connected to a 208-v power supply, the transformers must be rewired by moving the wire from
the 230-volt connection and moving to the 200-volt terminal
on the primary side of the transformer. Refer to unit label diagram for additional information.
Internal Wiring
Check all electrical connections in unit control boxes; tighten
as required. See Fig. 4 and 5 for panel and filter locations.
Evaporator Fan
The evaporator fan should be checked and may need to be adjusted for specific applications. The 48/50HC04-06 size units
can have a direct drive Electronic Commutated Motor (ECM)
fan system; all other units have a belt drive motor. The belt
drive motor can also be powered from an optional Variable
Frequency Drive (VFD). Refer to the unit product data for Fan
Performance tables and physical data.
48/50HC 04-06 UNITS WITH DIRECT DRIVE FANS
The ECM has 5 speed taps to allow a range of fan perfor-
mance. The ComfortLink control has 1 output wire to connect
to 1 tap. From the factory the control wire is connected to the
first tap. The speed taps increase the speed the higher the tap
number, so the first tap is the lowest speed and tap 5 is the
highest speed.
7
BELT DRIVE UNITS
The fan belt and variable pulleys are factory installed and set,
but may need to be adjusted for specific applications. Check
the fan to ensure its rotation is in the proper direction before
adjusting performance. To alter fan performance, adjust the
pulley settings to provide the applications full load design air
flow. Set the indoor fan pulley to the application design point
CFM for heating and cooling so that the CFM is not lower than
the minimum CFM allowed in the product data.
BELT DRIVE UNITS WITH A VFD
The fan belt and variable pulleys are factory installed and set,
but may need to be adjusted for specific applications. Check
the fan to ensure its rotation is in the proper direction before
adjusting performance. To alter fan performance, first adjust
the pulley settings to provide the applications full load design
air flow when running at the Supply Fan Maximum Speed
(Configuration
can then be adjusted with Fan Speed - Free Cool Lo (Configu-
ration
uration
tion
I.FANFS.RH), and Fan Speed — Ventilation (Con-
figuration
application design point CFM for heating and cooling at 100%
fan speed so that the CFM is not lower than the minimum CFM
allowed in the product data. If the exact CFM cannot be set by
the half turn pulley settings then adjust the Supply Fan Maximum Speed (FS.MX) to fine tune the CFM to the application
requirements. The VFD’s settings should not be used for adjusting fan performance. Specific VFD information can be
found in Appendix C.
IMPORTANT: The Supply Fan Maximum Speed (FS.MX)
RPM must not produce a supply CFM that is lower than the
minimum CFM allowed in the product data for heating and
cooling.
For belt drive units with a power exhaust option, the controls
require an accurate supply duct CFM at the unit design point
where the indoor fan will run at the Supply Fan Maximum
Speed (FS.MX) for proper operation. The supply duct CFM is
configured by the Indoor Fan Max Speed CFM (Configura-
tion
ECONIDF.C). Default values for Indoor Fan Max
Speed CFM (IDF.C) are generally set per chassis and should
be changed. It is preferred to use the supply duct CFM from an
air balance report to configure the Indoor Fan Max Speed CFM
UNITFS.MX). The unit operating speeds
I.FANFS.E1), Fan Speed - Mech Cooling (Config-
I.FANFS.CL), Fan Speed - Reheat 2 (Configura-
I.FANFS.VN). Set the indoor fan pulley to the
(IDF.C). If an air balance report is not available, then use the
fan tables to determine Fan Max Speed CFM (IDF.C). When
using the fan tables to determine Fan Max Speed CFM (IDF.C)
set Economizer Position Test (Service Test
to 0 (Economizer Damper Closed) and Indoor Fan Speed Test
(Service Test
mum Speed (FS.MX). Measure the supply to return duct static
pressure difference and indoor fan RPM. Make correction to
static pres sure for all options installed in the unit per the accessory pressure drop table. Determine Indoor Fan Max Speed
CFM (IDF.C) on the fan table where the corrected static pres-
sure and RPM cross.
FAN SF. S P D ) equal to Supply Fan Maxi-
INDPECON)
Condenser Fans and Motors
Condenser fans and motors are factory set.
Return-Air Filters
Check that correct filters are installed in filter tracks (see Physical Data table in Installation Instructions). Do not operate unit
without return-air filters.
Outdoor-Air Inlet Screens
Outdoor-air inlet screens must be in place before operating
unit.
Accessory Installation
Check to make sure that all accessories including space thermostats and sensors have been installed and wired as required
by the instructions and unit wiring diagrams.
Orifice Change (48HC)
This unit is factory assembled for heating operation using natural gas at an elevation from sea level to 2000 ft.
Use accessory high altitude kit when installing this unit at an
elevation of 2000 to 7000 ft. For elevations above 7000 ft, refer
to High Altitude section to identify the correct orifice size for
the elevation. Purchase these orifices from your local Carrier
dealer. Follow instructions in accessory Installation Instructions to install the correct orifices.
Use accessory LP (liquid propane) gas conversion kit when
converting this unit for use with LP fuel usage for elevations
up to 7000 ft. For elevations above 7000 ft, refer to High Altitude section to identify the correct orifice size for the elevation.
Purchase these orifices from your local Carrier dealer. Follow
instructions in accessory Installation Instructions to install the
correct orifices.
8
Fig. 4 — 48/50HC SRT Units, Panel and Filter Locations (48HC*06 Unit Shown)
INDOOR
BLOWER
ACCESS
PAN EL
CONTROL BOX
ACCESS PANEL
GAS SECTION
ACCESS PANEL
INDOOR COIL
ACCESS PANEL
FILTER
ACCESS PANEL
UNIT BACKUNIT FRONT
INDOOR BLOWER
ACCESS PANEL
OUTDOOR AIR
SCREEN
(HIDDEN)
GAS SECTION
CONTROL BOX
ACCESS PANEL
FILTER AND
INDOOR COIL
ACCESS PANEL
ACCESS PANEL
Fig. 5 — 48/50HC MRT Units, Panel and Filter Locations (48HC*17 Unit Shown)
9
Gas Heat (48HC)
Inspect the gas heat section of the unit. Verify the number of
burners match the number of heat exchanger openings and the
burner assembly is properly aligned. If the orifices were
changed out for elevation or Liquid Propane purposes, verify
proper installation. Visually inspect other components in heat
section.
Verify gas pressures before turning on heat as follows:
1.Turn off field-supplied manual gas stop, located external
to unit.
2.Connect pressure gauge to supply gas tap, located on fieldsupplied manual shutoff valve. (See Fig. 6.)
MANUAL SHUT OFF
(FIELD SUPPLIED)
GAS
SUPPLY
PRESSURE TAP
(1/8˝ NPT PLUG)
TO
UNIT
UNION
SEDIMENT TRAP
Fig. 6 — Field Gas Piping
3.Connect pressure gauge to manifold pressure tap.
4.Turn on field-supplied manual gas stop. Enter Service Test
mode by setting Service Test
TEST to “ON” using the
scrolling marquee display. Temporarily install the jumper
wire between “R” and “W1” on TB. Use the Service Test
feature to set Service Test
HEATHT.1 to ON (first
stage of heat) using the scrolling marquee.
5.After the unit has run for several minutes, verify the supply gas pressure is adequate per the base unit installation
instructions. If not, adjust accordingly.
NOTE: Supply gas pressure must not exceed 13.0-in. wg.
6.Set Service Test
HEATHT.1 to OFF using scrolling
marquee.
7.Remove jumper wire if the unit will be operating under
thermostat mode. The jumper must remain if a space temperature sensor (T-55, T-56, T-58, or System Pilot device)
will control the unit.
8.Exit Service Test mode by setting Service Test
TEST to
“OFF” using the scrolling marquee.
Units with EnergyX® System
BASE UNIT EVAPORATOR FAN
First follow the base unit instructions to balance the RTU in-
door fan. The ERV (Energy Recovery Ventilator) fans should
be off during base unit fan set-up. Before start-up and testing
the ERV, verify that the ComfortLink controller minimum
damper positions are set to 0 and if not change them to 0. Con-
figuration →AIR.Q →AQ.MN = 0, and Configuration
→ECON →MP.MX = 0. The ERV communicates with the
ComfortLink controller therefore the scrolling marquee can be
used for test mode and configuration of the ERV. The following sections explain ERV testing and configuration. It is important that these configurations are set correctly in order for
the ERV module to properly control the air performance. Finally, with service test disabled run unit under normal operation,
verify proper supply airflow with ERV and indoor fan running.
START-UP CHECK LIST
Use the EnergyX Unit Start-Up Checklist (see page CL-1) in
conjunction with the base unit Start-Up checklist from the base
Controls book. Fill in all blank data entries that are applicable
to the exact unit being installed. The ERV model and serial
numbers are printed in the ERV control box. Save the checklist
for future service and maintenance use. It is recommended that
a copy of the checklist be left with the unit in the literature slot
on the base unit control box access door.
ERV TEST MODE
ERV Test points should be used when starting up an EnergyX
unit to verify proper ERV component operation. It can also be
used for troubleshooting. To test the ERV, use the scrolling
marquee to put the ComfortLink RTU into test mode. Then go
to Test Independent outputs (Service Test →INDP). Table 3
shows a list of test points that can be tested as independent outputs. There are five ERV tests which can be performed separately or together while in test mode. Use the scrolling marquee to change the value of the test point. Follow the Com-fortLink Controls, Start-Up, Operation, and Troubleshooting
manual for testing the base rooftop unit.
The 5 ERV specific test points are OAU 2-position Damper,
OAU Wheel Test, OAU OA Fan Speed test, OAU PE Fan
Speed Test and OAU Tempering Heater Test. The 2-position
damper can be opened and closed with the OA.DM point. The
2-position damper accessory can be installed on the exhaust
opening of the ERV. The ERV wheel motor can be turned on
and off with the WHL point. The ERV’s outside air (OA.OF)
and building exhaust air (OA.XF) motors can be ramped up
and down during test mode their corresponding fan speed test
points. Table 3 shows the test mode test points in the order they
appear under test mode. Communication failures will not allow
these ERV test points to be changed. The ComfortLink controller will show active alarms during test mode.
NOTE: If a 2-position damper is installed, it must be opened in
test mode while operating the exhaust test.
Table 3 — Service Test Mode Independent Test
Points
ITEMEXPANSIONRANGE
INDPTest Independent Outputs
ECONEconomizer Position Test0 to 100
E.CALCalibrate EconomizerOff/On
PE1Power Exhaust 1 TestOff/On
PE.2Power Exhaust 2 TestOff/On
ALRMAlarm Relay TestOff/On
CCHCrankcase Heat TestOff/On
OA.DMOAU 2-Position DamperClose/Open
WHLOAU Wheel Test0 to 100
OA.OFOAU OA Fan Speed Test0 to 100
OA.XFOUA PE Fan Speed Test0 to 100
OA.HTOAU Tempering Heater Test0 to 100
ERV CONFIGURATION
The ERV configuration menu can be accessed using the Com-
fortLink controller scrolling marquee. Enter the Outside Air
Unit Configurations (Configuration →OAU) menu. Table 12
shows the list of complete outside air unit configurations that
can be changed and the defaults from the factory. The critical
job specific configurations are listed below and should be
changed at start up for the specific job site. See the operation
section for details all configurations.
OAU Unoccupied Operation (U.RUN)
This allows the ERV to run during the unoccupied period when
the rooftop fan is brought on.
10
Min DCV Outside Air CFM (DCV.M)
This sets the lowest setting for ventilation using outside air.
This number sets the absolute minimum for ventilation of contaminants and CO
This is only accessible if CO
generated by sources other than people.
2
sensors are installed and the
2
ComfortLink controller is configured properly.
NOTE: The ERV must be equipped with optional economizer to
operate with CO
2 sensors.
Minimum Outside Air CFM (OA.MN)
This sets the outside air ventilation rate when not using a CO
sensor to remove contaminants and CO2 generated by all
sources in the building space. When using CO2 sensors and
running DCV, this sets the maximum amount of outside air allowed for ventilation.
Power Exhaust CFM Offset (PE.OF)
This sets the offset for exhausting building air based on outside
air being brought in. A negative setting causes a positive building pressure, and a positive setting causes a negative build
pressure.
ERV WITH ECONOMIZER ADDITIONAL CONFIGURATIONS
There are several important ComfortLink controller configurations that impact the ERV operation when equipped with optional
economizer. To change these configurations use the ComfortLink
controller scrolling marquee, Navigator™ display, or a CCN communication tool. Refer to the ComfortLink Controls, Start-Up, Operation and Troubleshooting Instructions for more information on
using these tools. Table 4 shows the ComfortLink controller points
that impact ERV operation, with brief descriptions. These points
can be found on the scrolling marquee under the economizer and
air quality configuration menus (Configuration →ECON andConfiguration →AIR.Q). See operation section for details on individual configurations.
ADJUSTING ERV OPTIONS
The ERV can come with factory-installed frost protection and/or
an economizer (wheel bypass) damper. Other accessories can be
added to the ERV in the field including but not limited to filter
status, wheel status, and building pressure control. Refer to the
major components section of this manual or the specific accessory literature for more detail on these.
CONTROLS QUICK SET-UP
The following information will provide a quick guide to setting
up and configuring the 48/50HC series units with ComfortLink
controls. Unit controls are pre-configured at the factory for factory-installed options. Field-installed accessories will require
configuration at start-up. Service Test is recommended for initial start-up. Additionally, specific job requirements may re-
2
quire changes to default configuration values. See the CCN
and Display parameter tables and other sections of these instructions for more details. Refer to the Major System Components or accessory installation instructions for specific wiring
detail.
Control Set Point and Configuration Log
During start up, accessory installation, and equipment service
set points and/or configuration changes might have to be made.
When setting set points or changing configuration settings,
documentation is recommend. The Control Log starting on
page 129. should be filled out and left with the unit at all times,
a copy should also be provided to the equipment owner.
Thermostat Control
Wire accessory thermostat to the corresponding R, Y1, Y2,
W1, W2, and G terminals on the field connection terminal
board located at the unit control box.
The Unit Control Type configuration, Configuration
UNITU.CTL, default value is for Thermostat (2) so there
is no need to configure this item.
The Thermostat Control Type, Configuration
UNITT. CT L, selects the unit response to the thermostat
inputs above.
NOTE: May not be compatible with heat anticipator thermostats.
Space Temperature Sensor Control - Direct
Wired (T-55 or T-56 or T-59)
Wire accessory space temperature sensor(s) to the T-55 terminals on the field connection terminal board located at the unit
control box. Refer to Field-Installed Accessories section on
page 86 for additional information.
Table 4 — ComfortLink Controller Configurations
DISPLAY ITEMEXPANDED TEXTDEFAULTRANGEDESCRIPTION
EC.ENEconomizer Installed
MP.MXEcono Min at Max Fanspeed00 to 100%Must be set to 0 so the base rooftop does not
AQ.MNEcono Min IAQ Position00 to 100%
IA.CFIAQ Analog Input Configuration
IA.FNIAQ Analog Fan Configuration0
II.CFIAQ Switch Input Configuration0
II.FNIAQ Switch Fan Configuration0
AQD.LAQ Differential Low1000 to 5000These set the indoor air quality (IAQ) CO
This tells the ERV that an optional economizer
is installed
use the economizer for ventilation, only free
cooling
This tells the ERV if a CO
installed
Tells the ERV if it can run during
unoccupied for high CO
This tells the ERV if a switch is installed for
Tells the ERV if it can run during
unoccupied for high CO
DCV operating range. Differential is based off a
400PPM outside CO
Sets the speed of the outside air fan during
override.
2
2
value.
2
sensor is
2
sensor
switch
2
11
The Unit Control Type configuration, Configura-
tion
UNITU.CTL, must be set to Space Sensor (3). The
jumper wire in the installer’s packet must be connected between R and W1 on TB for heating mode to operate.
T-58 Communicating Room Sensor
Install the T-58 communicating thermostat. Connect the CCN
communication bus from the T-58 to the CCN terminals on the
field connection terminal board located at the unit control box.
Configure the unit’s CCN communication element number, bus
number, and baud rate. Configure the T-58 sensor’s CCN communication bus number and baud rate the same as the unit, while
the element number has to be different. Configure the T-58 to
send SPT to the unit’s element number. Refer to the Field-Installed Accessories section page 86 for additional information.
The Unit Control Type configuration, Configuration
UNITU.CTL, must be set to Space Sensor (3). The jump-
er wire in the installer’s packet must be connected between R
and W1 on TB for heating mode to operate.
CCN Linkage Control
The CCN communication must be properly configured for the
48/50HC units and all other devices. Linkage configuration is
automatically done by the supervisory CCN Linkage device.
The Unit Control Type configuration, Configuration
UNITU.CTL must be set to Space Sensor (3). The jumper
wire in the installer’s packet must be connected between R and
W1 on TB for heating mode to operate.
Installation of an accessory supply air temperature (SAT) sensor in the supply duct is recommended for Linkage applications. A supply duct SAT measurement is valid for heating
mode display, while the factory-standard internal SAT is not
valid for heating due to its location upstream of the heating
section. When installing the supply duct SAT, the heating mode
display is enabled by setting Configuration
to ENBL.
Installation of an accessory return air temperature (RAT) sensor in the return duct and wired to the space sensor input is recommended for Linkage applications. This will allow the unit to
continue to run if Linkage communication is lost.
HEATSAT.H
System Pilot™ - Communication Space Sensor
Install the System Pilot and connect the CCN communication
bus from it to the unit’s CCN connection on the low voltage
terminal board. Configure the unit’s CCN communication element number, bus number, and baud rate. Refer to the System
Pilot device’s installation instructions for configuring it to be
used as a space temperature and attaching it to a unit.
Thermidistat Control
The thermidistat is a thermostat and humidistat combined and
the inputs are provided on the field connection terminal board.
The unit control type configuration, Configura-
tion
UNITU.CTL, default value is for thermostat (2) so
there is no need to configure this item. The thermostat control
type configuration, Configuration
the unit response to the thermostat inputs above. The space humidity switch configuration, Configuration
identifies the normally open or normally closed status of this
input at HIGH humidity (only on Humidi-MiZer
UNITT. CT L, selects
UNITRH.SW,
®
units).
Space Humidistat Control
For units with the factory Humidi-MiZer option, the humidistat
input is provided on the field connection terminal board. The
Space Humidity Switch configuration, Configura-
tion
UNITRH.SW, identifies the normally open or normal-
ly closed status of this input at HIGH humidity.
Relative Humidity Sensor Control
For units with the factory installed Humidi-MiZer option and the
economizer option (with the ECB-economizer control board),
the humidity sensor input is provided on the field connection terminal board (TB). The sensor can be used in addition to or instead of a humidistat or thermidistat. The RH Sensor on OAQ
Input configuration, Configuration
tifies that the sensor is being used instead of an OAQ sensor. Adjust RH setpoints as needed. Terminal LPWR is the 24vdc loop
power and Terminal SPRH is the 4-20 mA signal input. Refer to
the Field Installed Accessories and Humidi-MiZer Operation
sections for more information.
UNITRH.S=YES, iden-
CCN Communication
Configure ConfigurationCCNCCN.A to desired element
number. (Default is 1.) Configure Configuration
CCN.B to desired bus number. (Default is 0.) Configure Configuration
rate (Default is 3 = 9600 baud).
CCNBAUD to desired code number for baud
CCN
Accessories
Below are quick configuration settings for field installed accessories. If these accessories were installed by the factory, they
will already be configured. See the Field-Installed Accessories
section, third party control, control connection tables, and
CCN or Display parameter tables for any accessories not mentioned below and any additional information on accessories.
ECONOMIZER
If an economizer accessory was field installed, the unit must be
configured for it by setting Configuration
to YES. The default settings for the other economizer configurations should be satisfactory. If they need to be changed, additional information about these configuration settings can be
found in the Economizer section.
POWER EXHAUST
If a power exhaust accessory was field installed, the unit must
be configured for it by setting Configura-
tion
ECONPE.EN to ENBL. The default settings for the
other power exhaust configurations should be satisfactory. If
they need to be changed, additional information about these
configurations can be found in the Power Exhaust section.
ELECTRIC HEAT
If an electric heat accessory was field installed, the unit must
be configured for it by setting Configura-
tion
HEATHT.TY to a value of 2. The number of electric
heat stages must be configured by setting Configura-
tion
HEATN.HTR per the installed heater.
FIRE SHUTDOWN
If a fire shutdown or smoke detector accessory was field in-
stalled, the unit must be configured for it by setting Configura-
tion
UNITFS.SW to normally open (1) or normally closed
(2) when there is not a fire alarm. Normally open (1) is the preferred configuration.
OUTDOOR ENTHALPY
If an outdoor enthalpy accessory was field installed, the unit
must be configured for it by setting Configura-
tion
ECONEN.SW, identifies the normally open or nor-
mally closed status of this input when the outdoor enthalpy is
low.
IAQ SWITCH
If an IAQ Switch accessory was field installed, the unit must
be configured for it by setting Configuration
identifies the normally open or normally closed status of this
input when the indoor air quality value is low (good) and also
selects the unit response to this input.
ECONEC.EN
AIR.QII.CF,
12
NOTE: An IAQ switch cannot be used if an enthalpy switch is already on this input.
IAQ SENSOR
If an CO
configured for it by setting ConfigurationAIR.QIA.CF
selects the unit response to this input. Default conversion to 0
to 2000 ppm.
OAQ SENSOR
If an outdoor air quality sensor accessory was field installed,
the unit must be configured for it by setting Configura-
tion
Default conversion to 0 to 2000 ppm.
FAN STATUS
If a fan status accessory was field installed, the unit must be
configured for it by setting Configuration
to normally open (1) or normally closed (2). Normally open (1)
is the preferred configuration.
FILTER STATUS
If a filter status accessory was field installed, the unit must be
configured for it by setting Configuration
normally open (1) or normally closed (2). Normally open (1) is
the preferred configuration.
sensor accessory was field installed, the unit must be
2
AIR.QOA.CF selects the unit response to this input.
UNITFN.SW
UNITFL.SW to
Programming Operating Schedules
The ComfortLink controls will accommodate up to eight different schedules (Periods 1 through 8), and each schedule is assigned to the desired days of the week. Each schedule includes
an occupied on and off time. As an example, to set an occupied
schedule for 8 AM to 5 PM for Monday through Friday, the
user would set days Monday through Friday to ON for Period
1. Then the user would configure the Period 1 Occupied From
point to 08:00 and the Period 1 Occupied To point to 17:00. To
create a different weekend schedule, the user would use Period
2 and set days Saturday and Sunday to ON with the desired Occupied On and Off times.
NOTE: By default, the time schedule periods are programmed for
24 hours of occupied operation.
To create a schedule, perform the following procedure:
1.Scroll to the Configuration mode, and select CCN CONFIGURATION (CCN). Scroll down to the Schedule Number (Configuration
CCNSCH.O=SCH.N). If password
protection has been enabled, the user will be prompted to
enter the password before any new data is accepted. SCH.N
has a range of 0 to 99. The default value is 1. A value of 0 is
always occupied, and the unit will control to its occupied set
points. A value of 1 means the unit will follow a local
schedule, and a value of 65 to 99 means it will follow a
CCN schedule. Schedules 2-64 are not used as the control
only supports one internal/local schedule. If one of the 2-64
schedules is configured, then the control will force the number back to 1. Make sure the value is set to 1 to use a local
schedule.
2.Enter the Time Clock mode. Scroll down to the LOCAL
TIME SCHEDULE (SCH.L) sub-mode, and press
ENTER. Period 1 (PER.1) will be displayed.
3.Scroll down to the MON.1 point. This point indicates if
schedule 1 applies to Monday. Use the ENTER command
to go into Edit mode, and use the Up or Down key to
change the display to YES or NO. Scroll down through the
rest of the days and apply schedule 1 where desired. The
schedule can also be applied to a holiday.
4.Configure the beginning of the occupied time period for
Period 1 (OCC). Press ENTER to go into Edit mode, and
the first two digits of the 00.00 will start flashing. Use the
Up or Down key to display the correct value for hours, in
24-hour (military) time. Press ENTER and hour value is
saved and the minutes digits will start flashing. Use the
same procedure to display and save the desired minutes
value.
5.Configure the unoccupied time for period 1 (UNC). Press
ENTER to go into Edit mode, and the first two digits of
the 00.00 will start flashing. Use the Up or Down key to
display the correct value for hours, in 24-hour (military)
time. Press ENTER and hour value is saved and the minutes digits will start flashing. Use the same procedure to
display and save the desired minutes value.
6.The first schedule is now complete. If a second schedule is
needed, such as for weekends or holidays, scroll down and
repeat the entire procedure for period 2 (PER.2). If additional schedules are needed, repeat the process for as many
as are needed. Eight schedules are provided. See Table 5
for an example of setting the schedule.
13
Table 5 — Setting an Occupied Time Schedule —Weekdays Only for 7:30 to 22:30
DISPLAY MENUSUB-SUB MODE
ENTERLocal Occupancy Schedule
TIMECLOCK
SCH.L
PER.1
KEYPAD
ENTRY
ENTER OCC.1 Period Occupied Time
ENTER 00.00 Scrolling stops
ENTER 00.00 Hours Flash
Y 07.00 Select 7
ENTER 07.00
Y 07.30 Select 30
ENTER 07.30 Change accepted
ESCAPE OCC.1 07.30 Period Occupied Time Item/Value/Units scrolls again
B UNC.1 00.00 Period Unoccupied Time
ENTER 00.00 Scrolling stops
ENTER 00.00 Hours Flash
Y 22.00 Select 22
ENTER 22.00
Y 22.30 Select 30
ENTER 22.30 Change accepted
ESCAPE UNC.1 22.30 Period Unoccupied Time Item/Value/Units scrolls again
B MON.1 NO Monday In Period
ENTER NO Scrolling stops
Y YES Select YES
ENTER YES Change accepted
ESCAPE MON.1 YES Monday In Period Item/Value/Units scrolls again
B TUE.1 NO Tuesday In Period
ENTER NO Scrolling stops
Y YES Select YES
ENTER YES Change accepted
ESCAPE TUE.1 YES Tuesday In Period Item/Value/Units scrolls again
B WED.1 NO Wednesday In Period
ENTER NO Scrolling stops
Y YES Select YES
ENTER YES Change accepted
ESCAPE WED.1 YES Wednesday In Period Item/Value/Units scrolls again
B THU.1 NO Thursday In Period
ENTER NO Scrolling stops
Y YES Select YES
ENTER YES Change accepted
ESCAPE THU.1 YES Thursday In Period Item/Value/Units scrolls again
B FRI.1 NO Friday In Period
ENTER NO Scrolling stops
Y YESSelect YES
ENTER YES Change accepted
ESCAPE FRI.1 YES Friday In Period Item/Value/Units scrolls again
ESCAPE
ESCAPE
ITEM DISPLAY ITEM EXPANSION COMMENT
Change accepted, minutes
Change accepted, minutes
flash
flash
14
SERVICE TEST
The Service Test function can be used to verify proper operation of compressors, heating stages, Humidi-MiZer system, indoor fan, power exhaust fans, economizer, and the alarm relay.
Use of Service Test is recommended at initial system start up
and during troubleshooting (see Table 6 for point details).
Service Test mode has the following changes from normal
operation:
•Outdoor air temperature limits for cooling circuits, economizer, and heating are ignored. Normal compressor time
guards and other staging delays are reduced to 30 seconds
or less.
•Circuit alerts are limited to 1 strike (versus 3) before
changing to alarm shut down state.
•The status of ALM.N is ignored so all alerts and alarms are
broadcast on CCN.
•The words “SERVICE TEST” are inserted into every
alarm message.
Service test can only be turned ON/OFF at the unit display.
Once turned ON, other entries may be made with the display or
through CCN. To turn Service Test on, change the value of
TEST to ON. To turn service test off, change the value of
TEST to OFF.
NOTE: Service Test mode may be password protected. Refer
to Basic Control Usage section for more information. Depending on the unit model, factory-installed options, and field-installed accessories, some of the Service Test functions may not
apply.
Independent Outputs
The independent (INDP) submenu is used to change output status for the economizer, power exhaust stages, crankcase heaters,
alarm relay, and outside air unit. These independent outputs can
operate simultaneously with other Service Test modes. All outputs return to normal operation when Service Test is turned off.
When the economizer is using the factory default Digital Control
Type (Configuration
ECONE.CTL is 1 or 2) then the Econ-
omizer Calibration feature may be used to automatically check
and reset the economizer actuator range of motion. Refer to the
economizer operation section of more details. On EnergyX
equipped units, use the outside air unit (OAU) points to test the
ERV components.
Fan Test
The fans (FA NS ) submenu is used to change output status for
the indoor fan. On single speed fan units the indoor fan contactor can be energized or de-energized using the IDF.1 test. For
units with a VFD the indoor fan speed test (F. S P D ) is available. F. S P D runs the fan at the desired speed entered. IDF Fan
Mode (F. M O D ) will run the fan at the programmed speed for
each mode. IDF.2 and IDF.3 are reserved for future use.
Cooling Test
The cooling (COOL) submenu is used to change output status
for the individual compressors. Compressor starts are staggered by 15 seconds. The fans (FA NS ) and heating (HEAT)
service test outputs are reset to OFF for the cooling service
test. Indoor fans and outdoor fans are controlled normally to
maintain proper unit operation. If LEN VFD fan is configured,
then the indoor fan speed will default to the Mech. Cooling Fan
Speed configuration point (Configuration
when one compressor is turned on. The Reduced Cool Fan
Speed (F. S P D ) can only be changed while one stage is running. If more then one stage is on the actual fan speed will be
100%. F. S P D shows the reduced speed not actual speed. On
single stage units, actual fan speed will be 100% when the
I.FANFS.CL)
compressor is on. All normal cooling alarms and alerts are
functional.
NOTE: Circuit A will always be operated with Circuit B.
Humidi-MiZer® Test
For units with the factory Humidi-MiZer option, the HumidiMiZer (HZMR) submenu is used to change the output status to
operate the circuits in different Humidi-MiZer modes or to separately test the Humidi-MiZer valve operations. Refer to the
Humidi-MiZer operation section for details on these modes
and valves. The fans (FAN S ), cooling (COOL), and heating
(HEAT) service test outputs are reset to OFF for the HumdiMiZer service test. Indoor and outdoor fans are controlled normally to maintain proper unit operation. If LEN VFD fan is
configured, then the indoor fan speed will default to the Reheat2 Fan Speed configuration point (Configura-
tion
I.FANFS.RH) when Reheat2 test is turned on. The
Reheat2 fan speed (F. S P D ) only reflects the speed setting for
testing Reheat2 circuits, and can only be changed when a circuit is in Reheat2. Actual speed may be different if Reheat 1
tests are being performed. All normal cooling alarms and alerts
are functional. Refer to the Humidi-MiZer operating section
for more information.
NOTE: Circuit A will be operated with Circuit B.
Table 6 — Service Test Modes and Submodes
Directory
DISPLAY MENU/
SUB-MENU/
NAME
SERVICE TEST
TEST Field Service Test Mode Off/On
INDP Test Independent Outputs
ECON Economizer Position Test 0 to 100%
E.CAL Calibrate Economizer Off/On
PE.1 Power Exhaust 1 Test Off/On
PE.2 Power Exhaust 2 Test Off/On
ALRM Alarm Relay Test Off/On
OA.DM OAU 2-position Damper Close/Open
WHL OAU Wheel Test 0 to 100%
OA.OF OAU OA Fan Speed Test 0 to100
OA.XF OAU PE Fan Speed Test 0 to100
OA.HT OAU Tempring Heater Test 0 to 100
FANS Test Fans
F.SPD Indoor Fan Speed Test 0 to 100
F.MOD IDF Fan Mode 0 to 7
IDF.1 Indoor Fan 1 Test Off/On
IDF.2 Indoor Fan 2 Test Off/On
IDF.3 Indoor Fan 3 Test Off/On
COOL Test Cooling
CMP.A Cool A Test Off/On
CMP.B Cool B Test Off/On
F.SPD Reduced Cool Fan Speed 60 to 100
HMZR Test Humidi-MiZer
RH1.B Reheat1 B Test Off/On
RH1.C Reheat1 C Test Off/On
RH2.A Reheat2 A Test Off/On
RH2.B Reheat2 B Test Off/On
F.SPD Reheat2 Fan Speed 0 to 100
CRC Cool->Reheat1 Valve Test Off/On
RHV.A Reheat2 Valve A Test Off/On
RHV.B Reheat2 Valve B Test Off/On
HEAT Test Heating
HT.1 Heat Stage 1 Test Off/On
HT.2 Heat Stage 2 Test Off/On
F.SPD Reduced Heat Fan Speed 0 to 100
EXPANDED NAME VALUES
15
Heating Test
The heating (HEAT) submenu is used to change output status
for the individual heat stages, gas or electric. The fans (FA NS )
and cooling (COOL) service test outputs are reset to OFF for
the heating service test. Indoor and outdoor fans are controlled
normally to maintain proper unit operation. All normal heating
alarms and alerts are functional.
NOTE: Field terminal board terminal R must be connected to W1
for the heat to operate in service test. Alert number T410 will occur as a reminder if not done. If the normal unit control mode is
thermostat mode, then remove the R-W1 jumper after completing
service test.
THIRD PARTY CONTROL
Third party controls may interface with the unit ComfortLink
controls through the connections described below. See other
sections of these instructions for more information on the related unit control and configurations.
Cooling/Heating Control
The thermostat inputs are provided on the field connection terminal board. The Unit Control Type configuration, Configura-
tion
UNITU.CTL, must be 2 to recognize the below in-
puts. Terminal R is the 24vac source for the following:
•Y1 = First stage cooling
•Y2 = Second stage cooling
•W1 = First stage heating
•W2 = Second stage heating
•G = Indoor fan
Dehumidification Control
On HumidiMiZer units the HUM terminal is provided on the
field connection terminal board. Humidity Switch configuration, Configuration
open or normally closed status of this input at HIGH humidity.
NOTE: Dehumidification is considered a cooling function in the
software.
UNITRH.SW, identifies the normally
Remote Occupancy
The remote occupancy input is provided on the field connection
terminal board (TB). The Remote Occupancy Switch configuration, Configuration
open or normally closed status of this input when unoccupied.
•RMOL = 24 VAC signal input
•R-2 = 24 VAC source for dry contact
UNITRM.SW, identifies the normally
Fire Shutdown
The fire shutdown input is provided for unit shutdown in response to a fire alarm or smoke detector. The Fire Shutdown
Switch configuration, Configuration
fies the normally open or normally closed status of this input
when there is no fire alarm.
•FDWN = 24 VAC signal input
UNITFS.SW, identi-
Alarm Output
The alarm output is provided on the field connection terminal
board to indicate a current alarm status. The output will be
24VAC if a current alarm exists.
•C-2 = 24 VAC common
•X = 24 VAC signal output
Economizer Damper Control
For units with the economizer option or accessory and the ECB
control board, the damper position can be directly controlled
through the IAQ sensor input provided on the field connection
terminal board. The IAQ Analog Input configuration,
Configuration
AIR.QIA.CF will have to set to 3 (Control
Minimum Position). When IA.CF = 3, an external 4 to 20 mA
source is used to move the damper 0% to 100% directly.
IAQ = 4-20mA + signal
COM = 4-20mA - common
NOTE: In this mode, preset minimum positions configurations
are not valid, the damper position may exceed the input position to provide economizer cooling and CO
not be used for DCV control. Refer to the Indoor Air Quality
operation section on page 27 for more information.
sensor input can
2
CONTROLS OPERATION
Display Configuration
The ConfigurationDISP submenu is used to configure the
local display settings.
Metric Display (METR)
This variable is used to change the display from English units
to Metric units.
Language Selection (LANG)
This variable is used to change the language of the ComfortLink display. At this time, only English is available.
Password Enable (PROT)
This variable enables or disables the use of a password. The
password is used to restrict use of the control to change configurations.
Service Password (PSWD)
This variable is the 4-digit numeric password that is required if
enabled.
Test Display LEDs (TEST)
This is used to test the operation of the ComfortLink display.
Unit Configuration
Many configurations that indicate what factory options and/or
field accessories are installed and other common operation
variables are included in Unit Configuration (Configura-
tion
UNIT). These configurations will be set in the factory
for the factory-installed options (FIOPs). Field-installed accessories installed will require configuration changes. General
unit and fan control configurations are also covered under this
Unit Configuration menu.
Start-Up Delay (S.DLY)
This configuration sets the control start-up delay after the power is interrupted. This can be used to stagger the start-up of
multiple units.
Unit Control Type (U.CTL)
This configuration defines if temperature control is based on
thermostat inputs or space temperature sensor input.
•U.CTL = 2 (Thermostat) — The unit determines cooling
and heating demand by the state of G, Y1, Y2,W1, and W2
inputs from a space thermostat. This value is the factory
default.
•U.CTL = 3 (Space Sensor) — The unit determines cooling
and heating demand based on the space temperature and
the appropriate set point. Used also as Linkage configuration. The jumper wire in the installer’s packet must be connected between R and W1 on the low voltage terminal
board for heating mode to operate.
THERMOSTAT CONTROL TYPE (T.CTL)
This configuration applies only if Unit Control Type is Thermo-
stat (Configuration
alternative cooling and Humidi-MiZer circuit staging. See the
Cooling and Humidi-MiZer sections for more information. The
factory default value is T.CTL = 0 (Adaptive).
UnitU.CTL = 2). The value determines
16
Fan Status Switch (FN.SW)
This configuration identifies if a fan status switch is installed,
and what status (normally open, normally closed) the input is
when the indoor fan is OFF.
Filter Status Switch (FL.SW)
This configuration identifies if a filter status switch is installed,
and what status (normally open, normally closed) the input is
when the filter is CLEAN.
Fire Shutdown Switch (FS.SW)
This configuration identifies if a fire shutdown switch is installed, and what status (normally open, normally closed) the
input is when the fire or smoke alarm is OFF (no alarm).
Remote Occupancy Switch (RM.SW)
This configuration identifies if a remote occupancy switch is
installed, and what status (normally open, normally closed) the
input is when UNOCCUPIED.
SAT Settling Time (SAT.T)
This configuration sets the settling time of the supply air temperature (SAT). This tells the control how long to wait after a
stage change before trusting the SAT reading. See Adaptive
Thermostat Control (U.CTL = 2, T. CT L = 0) and Space Sensor
Control (U.CTL = 3) within the Cooling operation section for
more information. The factory default value is 240 seconds.
RAT Sensor Installed (RAT.S)
This configuration identifies if a return air temperature (RAT)
sensor is installed. A YES value enables RAT display. A NO
value disables RAT display. Installing an RAT sensor will allow economizer differential dry bulb control. Refer to the
economizer operation for more information. RAT sensor is required for compliance with Title 24 Fault Detection and Diagnostics (FDD).
RH Sensor On OAQ Input (RH.S)
This configuration identifies if a space relative humidity sensor
is installed on the outdoor air quality (OAQ) input. A YES value enables SP.RH display. If a Humdi-MiZer unit, then the unit
determines dehumidification demand based on this input and
the appropriate set point. A NO value disables SP.RH display
and use.
Space Humidity Switch (RH.SW)
This configuration identifies if a space relative humidity switch
is installed on the ENTHALPY input, and what status (normally open, normally closed) the input is when the space humidity
is HIGH.
Temperature Compensated Start Cooling Factor (TCS.C)
This factor is used in the equation of the Temperature Compensated Start Time Bias for cooling. A setting of 0 minutes indicates
Temperature Compensated Start in Cooling is not permitted.
Temperature Compensated Start Heating Factor (TCS.H)
This factor is used in the equation of the Temperature Compensated Start Time Bias for heating. A setting of 0 minutes indicates
Temperature Compensated Start in Heating is not permitted.
Modes
The ComfortLink controls operate under a hierarchy of command structure as defined by four main elements: the System
Mode, the HVAC Mode, the Occupied status, and the Unit
Control Type.
The System Mode is the top level that defines three main states
of the control system: Disabled, Enabled, or Test.
The HVAC Mode is the next level that defines four main states
of functional operation: Disabled, Fan Only, Cool, and Heat.
The Occupied status affects set points for cooling and heating
in Space Sensor control mode and operation of the economizer
for indoor air quality ventilation and free cooling.
The Unit Control Type (Configuration
UNITU.CTL) de-
fines if temperature control is based on thermostat inputs or
space temperature sensor input.
The general operating mode of the control and the status of
some related operation lockouts are located on the display at
two locations: Run Status
Modes
MODE.
MODE and Operating
System Mode (SYS)
In Run Status and Operating Modes, the current system mode
is displayed with expandable text. This is an overall state of the
unit.
Three states are: Unit Operation Disabled, Unit Operation Enabled, or Service Test Enabled.
HVAC Mode (HVAC)
In Run Status and Operating Modes, the current allowed
HVAC mode is displayed with expandable text. This is the
mode the unit decides to run in based on its inputs. There are
four main HVAC modes; cooling has six different expanded
texts. These modes are shown in the following tables.
Fan Mode Expanded Text Brief Description
Disabled
Fan Only
Cooling
HeatingHeatingHeating mode
HVAC
Operation
Disabled
Ventilation
(fan-only)
CoolingMechanical cooling
Free CoolingOnly economizer used for cooling
Unoccupied
Free Cooling
Reheat1All running circuits in sub-cooling mode
Reheat2
Reheat1/
Reheat2
Unit is in test mode or System mode is
disabled
Fan may run for ventilation
Only economizer use for cooling
(occupied cooling set point active)
All running circuits in Hot Gas Reheat
mode
Sub-cooling and Hot Gas Reheat active
Indoor Fan Mode (F.MOD)
This displays the mode in which the fan is running. There are 8
fan modes in total, the 1-Speed fans can only be in 1 of 2
modes (off or High). Staged Air Volume (SAV) units can utilize all 8 modes if programmed for it. The following table
shows the 8 modes and a brief description for each.
Fan Mode Expanded Text Brief Description
0 OFF When the fan is off
1 High
2 Low Cool
3 Vent
4 IAQ Override
5 N/A Not available at this time
6 Dehum
7 Low Free Cool
When fan is on in 1-Speed units or at
high speed on SAV units
On SAV units with 2 cooling stages,
when only 1 cooling stage is requested
On SAV units, when in vent mode and
fan is on
On SAV units, in any mode when IAQ
override is active
On SAV units, in cooling mode, and
specific conditions allow
On SAV units, in cooling mode, and
specific conditions allow
HVAC Operation Disabled (HV.DN)
Allow disabling of HVAC mode. This is only available on a
network connection and shows if the unit has been forced into
the disabled status.
Cool Setpoint In Effect (EFF.C)
This shows the actual setpoint that is being used for control during
cooling mode. If a 0 is displayed, then space sensor control is not
being used and the unit is being controlled by a thermostat.
17
Heat Setpoint In Effect (EFF.H)
This shows the actual setpoint that is being used for control during
heating mode. If a 0 is displayed, then space sensor control is not
being used and the unit is being controlled by a thermostat.
Currently Occupied (OCC)
Displays the current state of assumed space occupancy based
on unit configuration and inputs.
T med Override in Effect (T.OVR)
Displays if the state of occupancy is currently occupied due to
an override.
Linkage Active (LINK)
Displays if a linkage communication “Linkage” is established
between the unit and a linkage source.
Demand Limit in Effect (D.LMT)
Displays if a demand limit has been placed on the unit’s capacity.
Compressor OAT Lockout (C.LOC)
Displays if operation of one or more compressors is prevented
due to outdoor temperature limit lockout.
Heat OAT Lockout (H.LOC)
Displays if heating operation is prevented due to outdoor temperature limit lockout.
Econo Cool OAT Lockout (E.LOC)
Displays if economizer operation for cooling is prevented due
to outdoor temperature limit lockout.
General Operation
48/50HC units can provide cooling, dehumidification, heating,
and ventilation operation. Each unit will operate under one of
two basic types of control: thermostat or space temperature
sensor. There are many inputs, configurations, safety factors,
and conditions that ultimately control the unit. Refer to the specific operation sections for detail on a specific unit operation.
When thermostat control is enabled (Configura-
tion
UNITU.CTL = 1), the unit will operate based on dis-
crete input commands (G, Y1, Y2, W1, and W2) and there is a
one minute time delay between modes and when re-entering a
mode. The G command calls for ventilation, the Y1 and Y2
commands call for cooling, and the W1 and W2 commands
call for heating. Thermostat Control Type (Configura-
tion
UNITT.C TL ) affects how cooling operates based on
Y1 and Y2 commands and if cooling/heating stage time guards
are applied.
When space temperature sensor control is enabled (Configura-
tion
UNITU.CTL = 2), the unit will try to maintain the Space
Temperature (Temperatures
tive cool and heat setpoints (Run StatusEFF.H). However, to minimize unnecessary cool to heat and heat
to cool changes, there is a 10 minute delay after the last stage turns
off before the control will switch modes and a 1 minute delay
when re-entering the last mode. Linkage operation overrides the
mode changeover delay to 15 seconds. The cooling and heating
Mode Select Timeguard (Operating Modes
and Operating Modes
time before allowing the respective mode to be entered.
AIR.TSPT) between the effec-
HEATMS.TG) show the remaining
MODEEFF.C and
COOLMS.TG
Temperature Setpoint Determination
Setpoints are used to control the unit while under space temperature sensor control. The Cool Setpoint in Effect (EFF.C)
and the Heat Setpoint in Effect (EFF.H) are the points in
which the unit is controlling to at a specific time. These points
are read only points and change according to occupancy, the
offset slider status, and network writes (Linkage or LON).
If the building is in occupied mode, the Occupied Cool Setpoint (Setpoints
OCSP) and the Occupied Heat Setpoint
(Setpoints
cupied mode, the Unoccupied Cool Setpoint (Set-
points
points
are also separated by a Heat-Cool Set Point Gap (Setpoints
This parameter will not allow the setpoints to be set too close
together, it will change the last setpoint adjusted if it is set
within the GAP.
When the space sensor has a setpoint slider adjustment, the
cool and heat setpoints (occupied) can be offset by sliding the
bar from one side to the other. The SPT Offset Range (+/-)
(Setpoints
that can be added to the setpoints. With the slider in the middle,
no offset is applied. Moving the slider to the “COOL” side will
subtract from each setpoint, and sliding it to the “WARM” side
will add to the setpoints. The slider offset being applied at any
given time is displayed as Space Temperature Offset (Te m-
peratures
OHSP) are active. When the building is in unoc-
UCSP) and the Unoccupied Heat Setpoint (Set-
UHSP) are active. The heating and cooling set points
GAP) that is user configurable from 2 to 10 degrees F.
STO.R) sets the total positive or negative degrees
AIR.TSPTO).
Occupancy Determination
The building’s occupancy is affected by a number of different
factors. When the unit is operating with a space temperature
sensor (T-55, T-56, T-58 or T-59), occupancy affects the unit
set points and the operation of the economizer. If the unit is operating under thermostat control, occupancy only affects the
operation of the economizer. If the unit’s Humidi-MiZer system is being controlled by a relative humidity sensor, then occupancy will affect the RH setpoints. The factors affecting occupancy are listed below from highest to lowest priority.
LEVEL 1 PRIORITY
Level 1 classification is a force/write to occupancy and can oc-
cur three ways. Listed in order of priority: force on OCCUPIED, a write to NVI_OCC, and a Linkage write. The CCN
point OCCUPIED is forced via an external device such as a
ComfortID controller or a service tool. When OCCUPIED is
forced to YES, the unit is considered occupied, when OCCUPIED is forced to NO, the unit is considered unoccupied. If the
third party protocol LON is writing to NVI_OCC, the control
maps it to OCCUPIED as an input. If the unit is being controlled by Linkage, the occupancy is communicated and
mapped to OCCUPIED as an input. LON and Linkage do not
force the point, only write to it, therefore a force applied to
OCCUPIED will override them.
If OCCUPIED is not being forced or written to, proceed to the
level 2 priority.
LEVEL 2 PRIORITY
Remote Occupancy Switch should be configured to either Nor-
mally Open or Normally Closed when the user would like to
control the occupancy with an external switch. This switch is
field-supplied (24v, single pole, single throw [SPST]). There
are three possible configurations for the remote occupancy
switch:
1.(Configuration
2.(Configuration
Switch
3.(Configuration
Switch
If the switch is configured to No Switch (0), the switch input
value will be ignored and software will proceed to level 3 priority. For each type of switch, the appropriate configuration
and states are listed in the table below. The Remote Occupancy
Switch (INPUTS
tus of the switch.
UNITRM.SW = 0) No Switch
UNITRM.SW = 1) Normally Open
UNITRM.SW = 2) Normally Closed
GEN.IRM.OC) point will show the sta-
18
TYPE OF SWITCH
Occupied when
Closed or Unoccupied
when Open
Occupied when Open
or Unoccupied when
Closed
SWITCH
CONFIGURATION
Normal Open (1)
Normal Closed (2)
STATE OF SWITCH
AND STATE OF
OCCUPANCY
Open and Unoccupied
Closed and Occupied
Open and Occupied
Closed and Unoccupied
NOTE: To perform remote occupancy, an Economizer Control
Board must be installed in the unit.
LEVEL 3 PRIORITY
The following occupancy options are determined by the state
of Occupancy Schedule Number (Configura-
tion
CCNSCH.OSCH.N) and the Global Schedule
Broadcast (Configuration
1.(Configuration
CCNBRODB.GS).
CCNSCH.OCH.N = 0)
The unit is always considered occupied and the programmed schedule is ignored. This is the factory default.
2.(Configuration
CCNSCH.OSCH.N = 1-64)
Follow the local programmed schedule. Schedules 1 to 64
are local within the controller. The unit can only store one
local schedule and therefore changing this number only
changes the title of the schedule table.
3.(Configuration
CCNSCH.OSCH.N = 65-99)
Follow the global programmed schedule. If the unit is configured as a Global Schedule Broadcaster (Configura-
tion
CCNBRODB.GS = YES), the unit will follow
the unit’s programmed schedule and broadcast the schedule so that other devices programmed to follow this schedule number can receive the schedule. If the unit is not
programmed as a Global Schedule Broadcaster (Configu-
ration
CCNBRODB.GS = NO), the unit will
receive broadcasted schedules from a unit programmed to
broadcast this schedule number. While using the programmed schedule, occupancy can be temporarily
switched from unoccupied to occupied by pressing the
override button for approximately 3 seconds on the T-55,
T-56, T-58 or T-59 space temperature sensor. Override will
only occur if SPT Override Enabled (Configura-
tion
CCNSCH.OOV.SP) is set to YES. The length
of the override period when pressing the override button is
determined by the Override Time Limit (Configura-
tion
CCNSCH.OOV.TL). The hours remaining in
override is displayed as Timed Override Hours (Configu-
ration
CCNSCH.OOV.EX). This point can also be
changed from the local display or network to set or change
the override period length.
INDOOR FAN OPERATION
The indoor fan is required for every function of the unit and has
several configurations that effect its operation. The Indoor Fan
Type configuration (Configuration
I.FANFTYP) sets the
type of fan and how it is controlled. These 48/50HC units can utilize the 1-Speed (FTYP = 0) or the LEN VFD (FTYP = 1) fan
types. The Number of Speeds configuration (Configura-
tion
I.FANNSPD) is not used with fan types 1-Speed or
LEN VFD. The fan operation for these two fan types is explained
in detail below. For gas heating units, the IGC fan request output
(Inputs
GEN.IIGC.F) is also monitored by the MBB con-
trol. This can result in additional modification of fan delays or
other operation due to safety functions of the IGC control. See the
Gas Heating operation section for more details. If configured for
IAQ fan operation, the fan may be turned on to satisfy air quality
demands. See the Indoor Air Quality section if using IAQ (indoor
air quality) accessory sensors. The fan can only run under thermostat or space sensor control if the System Mode (SYS) status is
enabled. The fan will remain on if compressors or heat relays are
ever stuck on. If configured for fan status switch (FN.SW) and
Shut Down on IDF Failure is enabled (Configuration
UNITIDF.F = Yes), the fan and unit will be shutdown with-
out delay on alarm. Fan off delays are honored when exiting specific HVAC modes. The Fan-off Delay delays are as follows:
Mech Cool (Configuration
(Configuration
HEATFOD.E), and Gas Heat (Configura-
COOLFOD.C), Elect Heat
tion HEATFOD.G).
Staged Air Volume (SAV) Units (FTYP = LEN VFD)
The SAV option is a new method of controlling the supply fan
in a typical constant volume rooftop unit. This control method
employs a Variable Frequency Drive (VFD) to operate the supply fan at different speeds in order to achieve energy savings
through reduced fan power. This method is specifically not
concerned with controlling static pressure in the supply duct,
but rather with setting different fan speeds for different operating conditions, such as ventilation mode or part-load mechanical cooling. This option should not be confused with a linearly
variable VFD concept. The different speeds are programmed
per condition; there is no linear-modulation of fan speed.
The SAV function is NOT a Variable Air Volume (VAV) function. The fan adapts its speed to one of seven based on mode
and current state to satisfy a demand. The seven speeds consist
of off (0%) and six configurable values. The six configurable
fan speeds are: Maximum Speed (FS.MX), Ventilation
(FS.VN), IAQ Override (FS.AQ), Free Cool Lo (FS.E1),
Mech Cooling (FS.CL), and Reheat2 (FS.RH).
The VFD is powered direct from the distribution block or circuit breaker (CB) and is always on with power applied unless
the CB is tripped. When the thermostat or space sensor control
conditions require the fan on, the VFD will then ramp to desired speed. Fan speed is always calculated by evaluating the
current applicable conditions. Each fan speed “mode” is evaluated independently, and the highest fan speed is used. For example, if an IAQ Override event occurs during Ventilation
mode, the fan speed is set to the higher of the two (FE.VN or
FS.AQ). Refer to the speed configurations below for when the
fan will run at them. When first turning on the fan from 0%, it
will run at max speed (FS.MX) for 1 minute.
Supply Fan Maximum Speed (FS.MX)
Max speed is the highest fan speed allowed. This is typically
100% when pulleys are set to deliver design CFM to the space
per job requirement. Most safety conditions for the unit will
override the fan speed to this to help protect the unit. When in
heat mode this is the only speed available. In free cooling after
the damper has been at max for 5 minutes, the fan will be set to
max before mechanical cooling can be used and locked at max
while damper is 100% and mechanical cooling is on. When
running both cooling stages the fan will be set to max.
Fan Speed - Ventilation (FS.VN)
This configuration defines the fan speed used in Ventilation
(fan-only) mode. Ventilation mode is when the supply fan is
running, but there is no demand for heating or cooling. In thermostat mode, this is with just a G call. In space sensor control,
this is when the unit is Occupied mode and the indoor fan is
configured to always run while occupied (Configura-
tion
I.FANOC.FN = YES). If the indoor fan is configured
for intermittent fan (OC.FN = No), the fan will be off instead
of this speed during ventilation. The economizer damper will
adjust its position based on how far away this speed is from
max speed.
IMPORTANT: It is important that the ventilation rate is
checked after setting this speed to verify that the unit can
properly ventilate the space per requirements. Adjusting
this configuration or the economizer minimum setting curve
should be performed to meet job requirements.
19
Fan Speed - IAQ Override (FS.AQ)
This configuration defines the fan speed used when an IAQ
Override is active. This pertains only to the Override function
of IAQ (Configuration
or (Configuration
AIR.QIA.CF = 2) (Override IAQ)
AIR.QII.CF = 3 or 4) (Override N/O or
N/C), not the DCV or Minimum Position functions. When in
an IAQ override condition the fan will run at this speed unless
it is configured for less than the current commanded speed.
When the IAQ override condition is cleared the speed will go
to the next commanded speed.
Fan Speed - Free Cool Lo (FS.E1)
This configuration defines the initial fan speed used when in
Free Cooling. Refer to the Economizer Controls Operation section for details on free cooling. The fan will stay at this configured speed whenever the damper is being used for free cooling.
If the damper is at 100% for 5 minutes the fan will ramp to max
speed. It is locked there until the actual damper position falls
below 75% at which time it will ramp back down to this configured speed.
Fan Speed - Mech Cooling (FS.CL)
This configuration defines the intermediate fan speed used
when one stage mechanical cooling is being requested. Fan
speed is based on how many cooling stages the unit has, how
many cooling stages are being requested, and how many reheat
stages are being requested. If the unit only has one circuit of
cooling, then the fan speed will be FS.MX whenever that stage
is requested. If the unit has more than one circuit of cooling but
only one is being requested, the fan speed will be set to this
FS.CL. Any time more than one stage is requested the fan
speed will be set to FS.MX. On Humidi-MiZer equipped units
fan speed is more complex. Refer to the FS.RH and Table 7 for
details.
Fan Speed - Reheat2 (FS.RH)
This configuration defines the fan speed used when Hot Gas
Reheat (reheat2) is being requested. Fan speed is based on how
many cooling stages the unit has, how many cooling stages are
being requested, and how many reheat stages are being requested. If only reheat stages are being requested, then the fan
speed will be set to FS.RH. If the unit only has one circuit of
cooling, then the fan speed will be FS.MX when dehumidification and cooling is being requested. If the unit has more than
one circuit of cooling and only one cooling stage is being requested, the fan speed will be set to FS.CL. Any time more
than one cooling stage is requested the fan speed will be set to
FS.MX. If only one cooling stage is requested and reheat is requested, then the fan speed will be set to the greater of the two
configurations (FS.CL or FS.RH). (See Table 7.)
OAU Fan Boost Enable (OAFB)
This configuration (Configuration
OAUOAFB) is avail-
able when the unit is equipped with a factory installed Outside
Air Unit (OAU). If set to yes then the indoor fan can be used to
help the
OAU if there is a low CFM alarm. When the alarm is active for
10 minutes the fan will ramp to the next highest configured
speed and wait 10 minutes. If the alarm is still active it will
ramp to the next highest configured speed for 10 minutes, and
so on until commanding FS.MX. If the alarm clears on its way
up to max speed or at max speed, the current speed will be
locked in until a standard speed driver commands something
different.
CONSTANT VOLUME (CV) UNITS (FTYP = 1-SPEED)
Single speed fan units are controlled by the Indoor Fan Relay 1
(Outputs
FAN SIDF.1) on the main base board (MBB),
which then operates the indoor fan contactor (IFC). The fan
will be either on or off depending on the unit control type and
the conditions above.
Thermostat Control
In thermostat mode, the IDF relay will be on in the following
situations: fan request G in ON, cooling request Y1 or Y2 is
ON, or heating request W1 or W2 is ON. If the G call is
dropped or was never on with an Y1, Y2, W1, or W2 call; the
IDF relay will turn off after a configurable time delay with respect to the HVAC mode that is ending.
Space Sensor Control
In Space Sensor mode, the IDF relay will be on if the unit is in
Occupied mode and the indoor fan is configured to always run
while occupied (Configuration
I.FANOC.FN = YES). If
the indoor fan is configured for intermittent fan (OC.FN = No),
the fan will only be on when there are cooling, heating, or dehumidification stages running; or if there is an air quality demand. During the unoccupied period, the fan will operate intermittent. With intermittent fan, the IDF relay will turn off after a
configurable time delay with respect to the HVAC mode that is
ending.
Cooling Operation
The 48/50HC unit’s cooling operation consists of: demand,
mode determination, staging request to satisfy the demand, and
handling a request with the unit’s resources. These resources
can include compressors, an economizer, and a reheat coil.
This section covers mechanical cooling. For economizer and
reheat cooling, refer to the Economizer and Humidi-MiZer sections, respectively. The unit enters a cooling mode based on a
demand, decides how to satisfy the demand, executes its plan,
and then leaves the cooling mode.
COOLING MODE CONTROL
The cooling HVAC mode (Run Status
has six different expandable texts: Cooling, Free Cooling, Unoccupied Free Cooling, Reheat1, Reheat2, or Reheat1/Reheat2.
These are all part of a general cooling mode and resemble the
specific type of cooling that is being performed at any given
time. All types of cooling are still performed under the general
cooling function, and the expanded text is for user reference
only. The control will display if it is ok to select the cooling
mode (Operating Modes
COOLOK.CL= Yes).
Thermostat Control
For the unit to enter cooling mode, three things must be true:
the indoor fan must be ok to use, the mode changeover time
guard must be expired, and there must be a cooling demand
(Y1, Y2, or dehumidification demand). The unit will remain in
cooling until the cooling demand is dropped or if any of the
above conditions turn false. If only a dehumidification demand
exists and a heat demand (W1, W2) occurs, the unit will end
cooling. The cooling mode can not officially end until all compressors are off.
Space Sensor Control
For the unit to enter cooling mode, four things must be true: the
indoor fan must be ok to use, the mode changeover time guard
must be expired, the unit must have a valid space temperature,
and there must be a cooling or dehumidification demand. The
unit will remain in cooling for at least one minute and until the
MODEHVAC=3)
20
cooling demand drops below -0.5°F or if any of the above conditions turn false. If only a dehumidification demand exists and
the heat demand becomes greater than the Reheat Heat Setpoint Deadband (Setpoints
ing. The cooling mode can not officially end until all compressors are off.
STAGING CONTROL
Once the unit is in a cooling mode, it must decide what the de-
mand is and how to satisfy it. If an economizer is installed and
can be used for cooling (Operating ModesYe s ), the unit will use it first (see economizer section for its operation). If the economizer can not be used or additional cooling is
needed, a mechanical cooling check is performed. OK to use
Compressors? (Operating Modes
set to yes when compressors are enabled and not locked out.
Based on the unit control configuration, requested cooling stages
(Run Status
to compressor control to actually add the cooling stages.
Thermostat Control
There are two ways of requesting stages when thermostat control is enabled, Traditional Thermostat control or Adaptive
control. Traditional Thermostat control is used if the Thermostat Control Type (T.C TL ) is set to 1, 2, or 3 and the economizer is not available for free cooling. If Thermostat Control
(T.C TL ) is set to 0 or any time the economizer is available for
free cooling, the unit will use Adaptive control for staging.
T.CTL = 0 (Adaptive Control)
Stage timers, Supply air trend, and supply air temperature limits apply when determining the request for stages. The first request (REQ.C=1) comes immediately when the Y1 input is active. The Cool Stage Increase Time (Configura-
tion
(Configuration
er stage can be added or a stage can be subtracted. The SupplyAir Trend (Operating Modes
next stage can be requested or should be subtracted based on
the Y2 input status. If the Y1 and Y2 inputs are dropped, the
supply air trend is not considered because cooling is no longer
needed. If at any time the Supply-Air Temperature (SAT) falls
below the Minimum Supply Air Temperature Upper Level
(Configuration
will not be allowed to increase. If at any time the SAT falls below the Minimum Supply Air Temperature Lower Level (Con-
figuration
be reduced by one without honoring C.DEC. If SAT.L and
SAT.U are configured so that they are close together, the last
stage of compressor might cycle rapidly, slowed only by its
minimum on and off-time requirements.
T.CTL = 1 (1 Stage Y1) and T.CTL = 2 (2 Stage Y1)
Stage timers, Supply air trend, and supply air temperature limits do not apply when determining the request for stages. Request staging will follow the thermostat inputs directly. Y1 will
request one stage. Y2 will request all stages.
T.CTL = 3 (Digital)
Stage timers, Supply air trend, and supply air temperature limits do not apply when determining the request for stages. Request staging will follow the thermostat inputs directly. Y1 will
request one stage. Y2 will request two stages. Y1 and Y2 will
request all stages.
Space Sensor Control
Space sensor staging control is an adaptive anticipation control
that weighs the actual space demand against the trend of that
demand and the trend of the supply air. It also honors stage
time guards and supply air limits. The demand for cooling in
the space is displayed as the Cooling Demand (Run Sta-
tus
change in the space because of its current stage status. This anticipation is based on the Supply-Air Trend (Operating
COOLREQ.C) will be determined then passed
COOLC.INC) or the Cool Stage Decrease Time
COOLC.DEC) has to expire before anoth-
COOLSATSAT.U), the requested stages
COOLSATSAT.L), the requested stages will
COOLDMD.C). The control tries to anticipate the
RH.HB), the unit will end cool-
COOLOK.EC=
COOLOK.MC), will be
COOLSA.TR) decides if the
Modes
COOLSA.TR) and the Cool Demand Trend (Oper-
ating Modes
control how the space is reacting to the current running conditions and help it decide when to add or remove one stage from
the requested stages. The Cool Stage Increase Time (Configu-
ration
(Configuration
er stage can be added or a stage can be subtracted. If at any
time the Supply-Air Temperature (SAT) falls below the Minimum Supply Air Temperature Upper Level (Configura-
tion
allowed to increase. If at any time the SAT falls below the Minimum Supply Air Temperature Lower Level (Configura-
tion
duced by one without honoring C.DEC. If SAT.L and SAT.U
are configured so that they are close together, the last stage of
compressor might cycle rapidly, slowed only by its minimum
on and off-time requirements.
COMPRESSOR CONTROL
The compressor control works hand and hand with the staging
control. As the staging control requests stages, the compressor
control determines what actual compressors are available or
running and tries to provide stages for what is requested. The
availability of a compressor depends on time guards, circuit diagnostics, outdoor temperature, and the unit size.
The Number of Circuits (Configuration
configuration tells the control how many compressors are installed on the unit. The Circuit A Lockout Temp (Configura-
tion
(Configuration
the outdoor temperature in which the respective compressor is
allowed to run down to. Timeguard A (Run Sta-
tus
COOLCIR.ATG.A) and Timeguard B (Run Sta-
tus
COOLCIR.BTG.B) display the time a respective
compressor has before it is available for use. Individual circuit
diagnostic tests are performed during operation which may or
may not allow a compressor to be used. The available stages at
any given time are displayed as Available Compressors (Run
Status
any given time are displayed as Actual Cooling Stages (Operating Modes
tus
COOLCIR.ACMP.A) and Compressor B (Run Sta-
tus
COOLCIR.BCMP.B) are displayed on when the re-
spective compressor is running.
There are time guards to protect the compressors. Compressor
Min On Time (Configuration
pressor Min Off Time (Configuration
ply before a compressor can be turned back on or turned off.
OUTDOOR FAN CONTROL
Outdoor fans are controlled electro-mechanically, not directly
by the control system. Refer to specific unit wiring diagram
and or service manual for details on how the outdoor fans operate. In general, the outdoor fan is energized with compressor A
or may have partial fans operate with compressor B. HumidiMiZer units will have a Motormaster control on some or all
fans.
COOLTRD.C). These trends will show the
COOLC.INC) or the Cool Stage Decrease Time
COOLC.DEC) has to expire before anoth-
COOLSATSAT.U), the requested stages will not be
COOLSATSAT.L), the requested stages will be re-
COOLN.CIR)
COOLCIR.ACA.LO) and Circuit B Lockout Temp
COOLCIR.BCB.LO) configurations set
COOLAVL.C). The actual compressors running at
COOLACT.C). Compressor A (Run Sta-
COOLMRT.C) and Com-
COOLMOT.C) ap-
Heating Operation
The 48/50HC unit’s heating operation consists of: demand,
mode determination, staging request to satisfy the demand, and
handling a request with the unit’s resources. These resources
can be gas heat or electric heat. This section covers both gas
heat units and electric heat units. The Type of Heat Installed
(Configuration
ry set to 1 for gas units, 2 for electric heat units with heaters installed, and 0 for electric heat units without heat installed. The
unit enters a heating mode based on a demand, decides how to
satisfy the demand, executes its plan, and then leaves the heating mode.
HEATHT.TY) configuration will be facto-
21
HEATING MODE CONTROL
The heating HVAC mode (Run Status
represents both types of heating (gas or electric) under all types of
control. For the unit to be allowed to enter the heat mode, heat
must be enabled (HT.TY = 1 or 2), and the Outdoor Air Tempera-
ture (Temperatures
ing Lockout Temp (Configuration
Lockout (Run StatusMODEH.LOC) displays when heat is
locked out on outdoor temperature and therefore can not allow
heat mode. The control will display if it is ok to select the heating
mode (Operating Modes
Thermostat Control
For the unit to enter heating mode, three additional things must
be true: the indoor fan must be ok to use, the mode changeover
time guard must be expired, and there must be a heating demand (W1, W2). The unit will remain in heating until the heating demand is dropped or if any of the above conditions turn
false. The heating mode can not officially end until all heat
stages are off and the IGC fan request is dropped (on gas units).
Space Sensor Control
For the unit to enter heating mode, five additional things must
be true: the indoor fan must be ok to use, the mode changeover
time guard must be expired, the unit must have a valid space
temperature, the W1 jumper must be installed, and there must
be a heating demand. The unit will remain in heating for at
least one minute and until the heat demand drops below –0.5°F
or if any of the above conditions turn false. The heating mode
can not officially end until all heat stages are off and the IGC
fan request is dropped (on gas units without Humidi-MiZer
system).
SUPPLY-AIR TEMPERATURE SENSOR (SAT)
The SAT Heat Mode Sensing (Configura-
tion
HEATSATSAT.H) informs the unit if the supply air
sensor has been relocated downstream of the heat section. This
configuration affects the Supply Air Temperature (Te mp era -
tures
AIR.TSAT) value displayed as listed below.
When SAT.H = DSBL, the Supply Air Temperature (Te mp era -
tures
AIR.TSAT) value on the scrolling marquee and the
CCN tables will be forced to zero when heat outputs turn ON
or OFF and for 5 minutes after. The default Supply Air Temperature location is at the fan inlet, upstream of the heat section.
When SAT.H = ENBL, the Supply Air Temperature (Tem pe ra -
tures
AIR.TSAT) sensor reading is displayed at the scroll-
ing marquee and the CCN tables during heating mode. This
setting should only be used if the original SAT sensor wires are
removed from the Main Base Board (MBB) and replaced by an
accessory SAT sensor located in the supply duct downstream
of the heat section.
There are two supply air temperature limits that affect heating
operation, the Maximum SAT Lower Level (Configura-
tion
HEATSATSAM.L) the Maximum SAT Upper Lev-
el (Configuration
supply air temperature rises above SAM.L the heat staging will
be limited to what is currently on and no additional stages can
be added until the supply air temperature falls back below
SAM.L. If the supply air temperature rises above SAM.U, then
heating will be reduced by removing a heat stage. That stage
can not be added again until the Supply Air Temperature falls
below SAM.L. If the supply air temperature stays above
SAM.U, then another stage will be removed after the Heat
Stage Decrease Time (ConfigurationSAM.L and SAM.U are configured so that they are close together, the last stage of heat might cycle rapidly, slowed only
by its minimum on and off-time requirements.
AIR.TOAT) must be less than the Heat-
HEAT OK.HT = Yes).
HEATSATSAM.U). Any time the
MODEHVAC=4),
HEATHT.LO). Heat OAT
HEATH.DEC). If
STAGING CONTROL
Once the unit is in a heating mode, it must decide what the de-
mand is and how to satisfy. Based on the unit control configuration, requested heating stages (Run Status
will be determined then passed to heat control to actually add the
heating stages.
Thermostat Control
There are two ways of requesting stages when thermostat control is enabled: Traditional Thermostat control or Adaptive
control. Traditional Thermostat control is used if the Thermostat Control Type (T.C TL ) is set to 1, 2, or 3. Adaptive control
is used if Thermostat Control (T. CT L) is set for 0.
T.C T L = 0
Stage timers and supply air temperature limits apply when determining the request for stages. The first request (REQ.C=1)
comes immediately when the W1 input is active. The Heat
Stage Increase Time (Configuration
Heat Stage Decrease Time (Configuration
has to expire before another stage can be added or a stage can
be subtracted. If at any time the Supply-Air Temperature (SAT)
rises above the Maximum Supply Air Temperature Lower Level (Configuration
stages will not be allowed to increase. If at any time the SAT
rises above the Maximum Supply Air Temperature Upper Level (Configuration
stages will be reduced by one without honoring H.DEC.
T.CTL = 1, 2 or 3
Stage timers and supply air temperature limits do not apply
when determining the request for stages. Request staging will
follow the thermostat inputs directly. W1 will request one
stage. W2 will request all stages.
Space Sensor Control
Space sensor staging control is an adaptive anticipation control
that weighs the actual space demand against the trend of that
demand. It also honors stage time guards and supply air limits.
The demand for heating in the space is displayed as the Heating Demand (Run Status
tries to anticipate the change in the space because of its current
stage status. This anticipation is based on the Heat Demand
Trend (Operating Modes
show the control how the space is reacting to the current running conditions and help it decide when to add or remove one
stage from the requested stages. The Heat Stage Increase Time
(Configuration
Time (Configuration
another stage can be added or a stage can be subtracted. If at
any time the Supply-Air Temperature (SAT) rises above the
Maximum Supply Air Temperature Lower Level (Configura-
tion
allowed to increase. If at any time the SAT rises above the
Maximum Supply Air Temperature Upper Level (Configura-
tion
duced by one without honoring H.DEC.
HEAT RELAY CONTROL
The heat relay control is responsible for energizing or de-energizing the MBB’s heat stage relays and works hand in hand with the
staging control. As the staging control requests stages, the heat
relay control determines what actual heat relays are available or
energized and tries to provide stages for what is requested. The
availability of a heat relays depends on heat being installed, how
many stages, and time guards. The type of Heat Installed (Con-
figuration
any stages to be available. The Number of Heat Stages (Configuration
many heat relays can be used. Heat Stage 1 Timeguard (Run Status
tus
has before it is available for use. The available stages at any given
(Adaptive Control)
HEATSATSAM.L), the requested
HEATSATSAM.U), the requested
(Traditional Thermostat Control)
HEATDMD.H). The control
HEATTRD.H). This trend will
HEATH.INC) or the Heat Stage Decrease
HEATH.DEC) has to expire before
HEATSATSAM.L), the requested stages will not be
HEATSATSAM.U), the requested stages will be re-
HEATHT.TY) must be set for gas or electric for
HEATN.HTR) configuration tells the control how
HEATTG.H1) and Heat Stage 2 Timeguard (Run Sta-
HEATTG.H2) display the time a respective heat relay
HEATREQ.H)
HEATH.INC) or the
HEATH.DEC)
22
time are displayed as Available Heating Stages (Run Sta-
tus
HEATAVL .H ). The actual heat relays on at any given
time are displayed as Actual Heating Stages (Operating
Modes
HEATACT.H). Heat Stage 1 Relay (Run Sta-
tus
HEATHT.1) and Heat Stage 2 Relay (Run Sta-
tusHEATHT.2) are displayed on when the respective relay
is energized. There are time guards to protect from short cycling,
Heat Minimum On Time (Configuration
and Heat Minimum Off Time (Configura-
tion
HEATMOT.H) apply before a heat relay can be turned
back on or turned off.
Integrated Gas Controller (IGC)
The heat staging is determined as described above and the Integrated Gas Controller (IGC) initiates the gas heat module startup. The Integrated Gas Controller (IGC) minimum on-time of
1 minute will be followed even if Heat Minimum On Time
(Configuration
vice Test. If the IGC temperature limit switch opens within 10
minutes of the end of the gas heat cycle, the next fan off delay
will be extended by 15 seconds. The maximum delay is 3 minutes. Once modified by the IGC, the fan off delay will not
change back to the configured Fan-off Delay, Gas Heat (Con-
figuration
trol. A light emitting diode (LED) is provided on the IGC to indicate status. During normal operation the LED is continuously
on. See the Troubleshooting section if the LED is off or flashing. The IGC is located behind the gas section access panel
door.
When the control energizes Heat Stage 1 Relay (Run Sta-
tus
HEATHT.1), power is sent to the W terminal on the
IGC board. A check is made to ensure that the rollout switch
and limit switch are closed. The induced-draft motor is then
energized, and when speed is proven with the Hall Effect sensor on the motor, the ignition activation period begins. The
burners will ignite within 5 seconds. If the burners do not light,
there is a 22-second delay before another 5-second attempt. If
the burners still do not light, this sequence is repeated for 15
minutes. After the 15 minutes have elapsed, if the burners still
have not lit, heating is locked out. The control will reset when
the request for heat is temporarily removed. When ignition occurs, the IGC board will continue to monitor the condition of
the rollout switch, limit switches, the Hall Effect sensor, as
well as the flame sensor. If the unit is controlled through a
room thermostat or space sensor set for fan auto, 45 seconds
after ignition occurs the indoor-fan motor will be energized
(and the outdoor-air dampers will open to their minimum position). If for some reason the over temperature limit opens prior
to the start of the indoor fan blower, on the next attempt, the
45-second delay will be shortened to 5 seconds less than the
time from initiation of heat to when the limit tripped. Gas will
not be interrupted to the burners and heating will continue.
Once modified, the fan on delay will not change back to 45
seconds unless power is reset to the control. When the control
energizes Heat Stage 2 Relay (Run Status
power is supplied to the second stage of the main gas valve. If
both stage 1 and stage 2 of the gas valve close, gas will be
turned off to the main burners.
HEATMRT.H) is lower and during Ser-
HEATFOD.G) unless power is reset to the con-
HEATMRT.H)
HEATHT.2),
Economizer
If an economizer is installed, then Economizer Installed (ConfigurationECONEC.EN) should be set to YES. The
economizer damper is controlled by the Econo Commanded
Position (Configuration
er Control Board (ECB). Feed back from the economizer actuator is output to the ECB and is displayed as Econo Actual Position (Outputs
ECONEC.CP) on the Economiz-
ECONEC.AP). The Economizer is used
for ventilation, cooling and to control the power exhaust. If the
Indoor fan is not on, the economizer will not operate.
ECONOMIZER FAULT DETECTION AND DIAGNOSTICS
(FDD) CONTROL
The Economizer Fault Detection and Diagnostics control can
be divided into two tests:
1. Test for mechanically disconnected actuator
2. Test for stuck/jammed actuator
1. Mechanically Disconnected Actuator
The test for a mechanically disconnected actuator shall be performed by monitoring SAT as the actuator position changes
and the damper blades modulate. As the damper opens, it is expected SAT will drop and approach OAT when the damper is at
100%. As the damper closes, it is expected SAT will rise and
approach RAT when the damper is at 0%. The basic test shall
be as follows:
1.With supply fan running take a sample of SAT at current
actuator position.
2.Modulate actuator to new position.
3.Allow time for SAT to stabilize at new position.
4.Take sample of SAT at new actuator position and determine:
a. If damper has opened, SAT should have decreased.
b. If damper has closed, SAT should have increased.
5.Use current SAT and actuator position as samples for next
comparison after next actuator move.
The control shall test for a mechanically disconnected damper
if all the following conditions are true:
1.An economizer is installed.
2.The supply fan is running.
3.Conditions are good for economizing.
4.The difference between RAT and OAT > T24RATDF. It is
necessary for there to be a large enough difference
between RAT and OAT in order to measure a change in
SAT as the damper modulates.
5.The actuator has moved at least T24ECSTS %. A very
small change in damper position may result in a very small
(or non-measurable) change in SAT.
6.At least part of the economizer movement is within the
range T24TSTMN% to T24TSTMX%. Because the mixing of outside air and return air is not linear over the entire
range of damper position, near the ends of the range even a
large change in damper position may result in a very small
(or non-measurable) change in SAT.
Furthermore, the control shall test for a mechanically disconnected actuator after T24CHDLY minutes have expired when
any of the following occur (this is to allow the heat/cool cycle
to dissipate and not influence SAT):
1.The supply fans switches from OFF to ON.
2.Mechanical cooling switches from ON to OFF.
3.Reheat switches from ON to OFF.
4.The SAT sensor has been relocated downstream of the
heating section and heat switches from ON to OFF.
The economizer shall be considered moving if the reported position has changed at least ± T24ECMDB %. A very small
changed in position shall not be considered movement.
The determination of whether the economizer is mechanically
disconnected shall occur SAT_SEC/2 seconds after the economizer has stopped moving.
23
The control shall log a “damper not modulating” alert if:
1.SAT has not decreased by T24SATMD degrees F
SAT_SET/2 seconds after opening the economizer at least
T24ECSTS%, taking into account whether the entire movement has occurred within the range 0 to T24TSTMN%.
2.SAT has not increased by T24SATMD degrees F
SAT_SET/2 seconds after closing the economizer at least
T24ECSTS%, taking into account whether the entire
movement has occurred within the range T24TSTMX to
100%.
3.Economizer reported position <=5% and SAT is not
approximately equal to RAT. SAT not approximately equal
to RAT shall be determined as follows:
a. SAT<RAT-(2*2(thermistor accuracy) + 2 (SAT
increase due to fan)) or
b. SAT>RAT+(2*2(thermistor accuracy) + 2 (SAT
increase due to fan))
4.Economizer reported position >=95% and SAT is not
approximately equal to OAT. SAT not approximately
equal to OAT shall be determined as follows:
a. SAT<OAT-(2*2(thermistor accuracy) + 2 (SAT
increase due to fan)) or
b. SAT>OAT+(2*2(thermistor accuracy) + 2 (SAT
increase due to fan))
2. Actuator Stuck or Jammed
The control shall test for a jammed actuator as follows:
•If the actuator has stopped moving and the reported position (ECONOPOS) is not within ± 3% of the commanded
position (ECONOCMD) after 20 seconds, a “damper stuck
or jammed” alert shall be logged.
•If the actuator jammed while opening (i.e., reported position < commanded position), a “not economizing when it
should” alert shall be logged.
•If the actuator jammed while closing (i.e., reported position > command position), the “economizing when it
should not” and “too much outside air” alerts shall be
logged.
The control shall automatically clear the jammed actuator
alerts as follows:
•If the actuator jammed while opening, when ECONOPOS
> jammed position the alerts shall be cleared.
•If the actuator jammed while closing, when ECONOPOS <
jammed position the alerts shall be cleared.
TITLE 24 FDD CONFIGURATION POINTS
LOG.F (T24LOGFL) — “Log Title 24 Faults” — defines when
Title 24 mechanically disconnected actuator faults should be
logged:
Range=YES, NO,
YES — attempt to detect and log mechanically disconnect ac-
tuator
NO — do not attempt to detect and log mechanically discon-
mum amount economizer must move in order to trigger the test
for a change in SAT, i.e., the economizer must move at least
T24ECSTS % before the control will attempt to determine
whether the actuator is mechanically disconnected.
mum difference (in degrees F) between RAT (if available) or
SAT (with economizer closed and fan on) and OAT to perform
mechanically disconnected actuator testing.
Range=5-20
Default=15
E.CHD (T24CHDLY) — “T24 Heat/Cool End Delay” —
amount of time (in minutes) to wait after mechanical cooling or
heating has ended before testing for mechanically disconnected
actuator. This is to allow SAT to stabilize at conclusion of mechanical cooling or heating.
the amount of time (in seconds) economizer reported position
must remain unchanged (±T24ECMDB) before the control will
attempt to detect a mechanically disconnected actuator. This is
to allow SAT to stabilize at the current economizer position.
This configuration sets the settling time of the supply air temperature (SAT). This typically tells the control how long to
wait after a stage change before trusting the SAT reading, and
has been reused for Title 24 purposes.
mum position below which tests for a mechanically disconnected actuator will not be performed. For example, if the actuator moves entirely within the range 0 to T24TSTMN a determination of whether the actuator is mechanically disconnected
will not be made. This is due to the fact that at the extreme
ends of the actuator movement, a change in position may not
result in a detectable change in temperature. When the actuator
stops in the range 0 to 2% (the actuator is considered to be
closed), a test shall be performed where SAT is expected to be
approximately equal to RAT. If SAT is not determined to be approximately equal to RAT, a “damper not modulating” alert
shall be logged.
Range=0-50
Default=15
ET.MX (T24TSTMX) — “T24 Test Maximum Pos” — maxi-
mum position above which tests for a mechanically disconnected actuator will not be performed. For example, if the actuator moves entirely within the range T24TSTMX to 100 a determination of whether the actuator is mechanically
disconnected will not be made. This is due to the fact that at the
extreme ends of the actuator movement, a change in position
may not result in a detectable change in temperature. When the
actuator stops in the range 98 to 100% (the actuator is considered to be open), a test shall be performed where SAT is expected to be approximately equal to OAT. If SAT is not determined to be approximately equal to OAT, a “damper not modulating” alert shall be logged.
Range=50-100
Default=85
Range=0-10
Default=4
24
ECONOMIZER ACTUATOR COMMUNICATION
Economizer Position %
50
0
100
25
75
EC.MX
Minimum
Fan Speed
001 050 75 02 52
Fan
Speed %
MP.MX
MP.75
MP.50
MP.25
AQ.MN for DCV
MP.75 DCV
MP.50 DCV
MP.25 DCV
The economizer actuator used with the 48/50HC units is a
Multi-Function Technology (MFT) actuator. This allows the
ComfortLink system to communicate with the actuator digitally using Belimo MP protocol. The configuration Economizer
Control Type (Configuration
the communication method, either digital or analog, used to
communicate between the Economizer Control Board and the
economizer actuator.
NOTE: The power to the unit must be cycled after the Economizer Control Type (Configuration
figuration parameter is changed.
E.CTL = 1 or 2 (Digital/Position or Digital/Command)
When Economizer Control Type (Configura-
tion
ECONE.CTL) is set to 1, the Economizer Control
Board will communicate with the economizer actuator using
the digital protocol, from Economizer Control Board plug J7-1
to actuator pin 5. The commanded position and the actuators
actual position are communicated back and forth between the
actuator and the Economizer Control Board. When the Economizer Control Board and actuator first initiate communication,
a Control Angle (Operating Modes
vided to the Economizer Control Board and defines the actuator’s range of motion. The control angle must be greater than
the Min Actuator Ctrl Angle (Configura-
tion
ECONM.ANG). During this digital control, the Econ-
omizer Control Board analog 4 to 20 mA output will represent
the actuator’s actual position when E.CTL = 1 or commanded
position when E.CTL = 2. Because the wiring has a built-in
500-ohm resistor, the 4 to 20mA signal is converted to a 2 to
10VDC signal at the actuator.
E.CTL = 3 (Analog Control)
When E.CTL is set to 3, the Economizer Control Board will
NOT communicate with the actuator using digital MFT. It will
instead control the economizer actuator directly with the 4 to
20mA analog signal wired with the 500-ohm resistor producing a 2 to 10VDC signal for the actuator. While in this mode,
the actuator’s built-in 2 to 10VDC feedback signal can be read
as actual position any time because it is not used by the Economizer Control Board.
MINIMUM VENTILATION
The economizer will open to allow ventilation when the indoor
fan is turned on and the unit is in the occupied state. The economizer damper position at any given time for ventilation is displayed as the Min Position in Effect (Run Sta-
tus
ECONEC.MP). This minimum position can be effect-
ed by the indoor fan speed (F. S P D ) and indoor air quality. On
single speed units, the economizer minimum position will be
equal to the ECON MIN at MAX Fan Speed (Configura-
tion
ECONMP.MX) unless Indoor air quality requests
something different.
On Staged Air Volume (SAV) units, to maintain a constant air-
flow through the economizer, as the indoor fan speed decreases
or increases, the damper minimum position will increase or decrease, respectively. This relationship curve is shown in Fig. 7.
Units can also be equipped with optional CO
tional indoor air quality control. When unit is equipped with a return duct CO
sensor the Economizer minimum position will be recalculat-
CO
2
ed based on the CO
SAV units the fan speed will also be used in recalculating mini-
sensor or return duct CO2 sensor and outside air
2
mum position, as shown in Fig. 7. When the Commanded Fan
Speed (F. S P D ) is less than the Supply Fan Maximum Speed
(FS.MX) the damper will operate in the shaded area of Fig. 7
based on the IAQ Level (IAQ). See the Indoor Air Quality (IAQ)
section for more details on Demand Controlled Ventilation
(DCV).
ECONE.CTL) determines
ECONE.CTL) con-
ECONC.ANG) is pro-
sensors for addi-
2
level of the return and/or outside air. On
2
Fig. 7 — Minimum Damper Position Curve (on SAV
units)
The shape of the Economizer Minimum Position vs. Fan Speed
curve is determined by the configuration parameters: Econ Min
at 25% Fan speed (Configuration
Min at 50% Fan speed (Configuration
ECONMP.25), Econ
ECONMP.50),
Econ Min at 75% Fan speed (Configura-
tion
ECONMP.75) and Econ Min at Max Fan speed (Con-
figuration
ECONMP.MX). These configurations are pre-
set at the factory for default purposes. The Econ Min at Max
Fan Speed (MP.MX) should be changed based on the air bal-
ance of the unit for proper ventilation. The Econ Min at 25%
Fan speed (MP.25), Econ Min at 50% Fan speed (MP.50) and
Econ Min at 75% Fan speed (MP.75) damper positions will be
calculated and changed automatically after changing the Econ
Min at Max Fan Speed (MP.MX) and Supply Fan Maximum
Speed (Configuration
I.FANFS.MX).
The damper position curve can be field adjusted per application,
if needed. The Econ Min at 25% Fan speed (Configura-
tion
ECONMP.25), Econ Min at 50% Fan speed (Configu-
ration
ECONMP.50) and Econ Min at 75% Fan speed
(Configuration
ECONMP.75) damper position are user
configurable and can be determined by setting the fan speed at
25, 50 and 75% and determining the damper position required to
maintain the Econ Min at Max Fan Speed (Configura-
tion
ECONMP.MX) outside air CFM through the econo-
mizer outside air dampers. The default calculations programmed
into the HC controls are based on a side shot economizer at 400
CFM/TON Supply Air flow with negative 0.25 in.wg H
sure in the return duct. Econ Min at Max Fan Speed (FS.MN) is
set by user based on minimum required outside air ventilation
CFM required for the application. This procedure would be the
same as if this were a CV unit with the unit running at the design
point CFM. This determines the minimum position amount of
outside air CFM required when the fan is running at maximum
speed.
FREE COOLING
The economizer will be allowed to help with cooling (Run Sta-
tus
MODEOK.EC = Yes) if the supply air temperature sen-
sor reading is valid, there are no applied lockouts, and there is
not a dehumidification demand. There are four economizer lockouts that can be applied at any time. Econo Cool OAT Lockout
(Operating Modes
ECONE.LOC) occurs when the Outdoor
Air Temperature (OAT) is greater than the configured Econo
Cool Hi Temp Limit (Configuration
ECONEH.LO) or less
25
O pres-
2
than the configured Econo Cool Lo Temp Limit (Configura-
tion
ECONEL.LO). Econo Diff DBulb Lockout (Operating
ModesECOND.LOC) occurs when Diff Dry Bulb Controlis enabled (Configuration
ECONDF.DB = Enable) and the
accessory return air temperature (RAT) is lower then the outdoor
air temperature (OAT). Econo Cool Enth Lockout (Operating
Modes
ECON EN.LO) occurs when an enthalpy sensor is
installed and the Outdoor Enthalpy is HIGH. OAQ Lockout
Mode (Operating Modes
ECONAQ.LO) occurs when the
outdoor air quality sensor is configured for lockout and the value
is greater then the OAQ Lockout Limit (Configura-
tion
AIR.QOAQ.L). Any one of these lockouts will disable
economizer free cooling.
THERMOSTAT CONTROL
If the unit is in cooling, operating under thermostat control, Y1
= ON, and the economizer is available for cooling, the economizer will control the supply-air temperature to the low cool
set point (Setpoints
LCSP). When Y2 = ON, the economizer
will control the supply-air temperature to high cool set point
(Setpoints
HCSP). If a compressor is also being used during
Free Cooling, the damper will be locked at the economizer
maximum position (Configuration
ECONEC.MX).
SPACE SENSOR CONTROL
If the unit is in cooling, operating under space temperature
control, the economizer is available for cooling, and no compressors are operating, the economizer will control the SAT to
either Setpoints
LCSP or SetpointsHCSP (See Table 8.) If
a compressor is ON, the economizer will be at the economizer
maximum cooling position (Configuration
ECON
EC.MX).
If the control senses low suction pressure for any active refrig-
erant circuit when the economizer is also providing cooling,
the maximum allowable economizer position will be reduced.
Factory default configurations have been qualified over a large
range of conditions and should only be changed with care. For
unit troubleshooting, factory default maximum economizer
limits for this condition are provided in Table 9.
HCSP— High Cool Set Point
LCSP— Low Cool Set Point
SAT— Supply-Air Temperature
COOL DEMAND
(delta F)
NEXT SAT SET
POINT
Table 9 — Maximum Economizer Limits During Low
Suction Pressure
COOLING STAGE SIZES 04-14 SIZES 17-28
Bottom 50 50
Top 25 0
Air-Side Economizer High Limit Switches Control
DIFFERENTIAL DRY BULB CUTOFF CONTROL
Econo Diff DBulb Lockout (Operating
Modes
is enabled (Configuration
ECOND.LOC) occurs when Diff Dry Bulb Control
The accessory return air temperature (RAT) will then be compared to the outdoor air temperature (OAT) based on the
DF.DB setting to determine whether lockout should occur as
shown in the following table:
ECONDF.DB = DISABLE).
DF.DB (DIFFBULB)
DISABLE N/A NO
RAT- 0
RAT- 2
RAT- 4
RAT- 6
OAT/RAT
Comparison
OAT>RAT YES
OAT<=RAT NO
OAT>RAT- 2 YES
OAT<=RAT-2 NO
OAT>RAT- 4 YES
OAT<=RAT-4 NO
OAT>RAT- 6 YES
OAT<=RAT-6 NO
D.LOC (DFDBLOCK)
The OAT/RAT comparison must maintain the same result for
60 consecutive seconds before D.LOC will be changed.
UNOCCUPIED FREE COOLING
The unoccupied free cooling algorithm attempts to maintain
the building space half way between the Occupied Cool Set
Point (Setpoints
OCSP) and Occupied Heat Set Point (Set-
pointsOHSP) using only the economizer when the condi-
tions in the building and the outdoors are suitable, during unoccupied periods. Three different configurations define this algorithm: Unoccupied Free Cooling (Configuration
ECON
UEFC), Free Cooling Preoccupancy Time (Configura-
tion
ECONFC.TM), and FreeCoolLowTemp Limit (Con-
figurationECONFC.LO).
UEFC = 0 (Disabled)
When UEFC = 0, unoccupied free cooling is disabled. Cooling
will only occur if the space exceeds the unoccupied setpoints.
UEFC = 1 (Unoccupied)
When UEFC is set to 1, unoccupied free cooling can occur
throughout the entire unoccupied period. The space temperature must be higher than the mid-point between the occupied
cooling and heating setpoints.
UEFC = 2 (Preoccupancy)
When UEFC is set to 2, unoccupied free cooling can only occur when the time until the next occupied period is less than the
Free Cool PreOcc Time (FC.TM) in minutes.
Free Cool PreOcc Time (FC.TM)
FC.TM is the configuration that determines how many minutes
before occupancy that free cooling can occur when set for Preoccupancy (UEFC = 2).
Free Cool Low Temp Limit (FC.LO)
Unoccupied free cooling cannot occur if the Outdoor Air Temperature (Temperature
AIR.TOAT) is less than FC.LO.
POWER EXHAUST (CV UNITS)
To enable power exhaust, Configuration
ECONPE.EN
must be set to ENBL. If power exhaust is enabled, Power Exhaust 1 will turn on when the economizer position is greater
than the value of Configuration
ECONPE.1. Power Ex-
haust 2 will turn on when the economizer position is greater
than the value of Configuration
ECONPE.2. There are
small time delays to ensure that rapid cycling does not occur.
POWER EXHAUST (SAV UNITS)
To enable power exhaust, set Power Exhaust Installed (Config-
uration
ECONPE.EN) to YES. Both power exhaust fans
are wired together and are controlled by the configuration
Power Exhaust Stage1 CFM (Configura-
tion
ECONPE1.C). When the Indoor Fan Max Speed
CFM (Configuration
ECONIDF.C) is set to the correct
supply duct CFM (either by fan tables or air balance report) the
control will calculate the outside air CFM based on outside air
damper position and Commanded Fan Speed (Out-
puts
FAN SF. S P D ) to turn on the power exhaust when the
calculated outside air CFM reaches Power Exhaust Stage1
CFM (PE1.C). The power exhaust will then turn off when the
26
VENTILATION FOR PEOPLE
VENTILATION FOR SOURCES
INCREASING VENTILATION
ECON MIN
AT M AX
FANSPEED
POSITION
(MP.MX)
MINIMUM
IAQ
DAMPER
POSITION
(AQ.MN)
OC EDISTUO/EDISNI007001
2
DIFFERENTIAL
AQ
DIFFERENTIAL
LOW (AQD.L)
AQ
DIFFERENTIAL
HIGH (AQD.H)
calculated outside air CFM falls below Power Exhaust Stage1
CFM (PE1.C). The Power Exhaust Stage2 CFM (Configura-
ECONPE2.C) is not currently used on these products.
tion
Indoor Air Quality (IAQ)
The ComfortLink control has the capability for several methods of demand ventilation control. Indoor air quality is typically measured using a CO
played in parts per million (ppm). Outdoor air quality may be
measured with a CO
mand ventilation control, or with other sensor types for the outdoor air lockout function. The factory-installed indoor air quality CO
sensor is mounted in the return section. A field-in-
2
stalled indoor air quality CO
return duct or directly in the occupied space, per job requirements. The indoor air quality modes of operation can be affected by configurations for indoor air quality sensor (Configura-
tion
AIR.QIA.CF), indoor air quality switch (Configura-
tion
AIR.QII.CF), outdoor air quality sensor
(Configuration
limit configurations as described below.
IAQ (ANALOG INPUT)
The ComfortLink control is configured for indoor air quality
sensors which provide 4 to 20 mA signal for 0 to 2000 ppm
CO
. If the sensor being used has a different range, the ppm
2
display range must be reconfigured by entering new values for
the IAQ Sensor Value at 4mA (Configura-
tion
AIR.QI.4M) and IAQ Sensor Value at 20mA (Config-
urationAIR.Q I.20M).
IA.CF = 0 (No IAQ)
IA.CF = 0 signifies that there is no IAQ sensor installed. The
damper will operate at the Econ Min at Max Fan Speed (Configuration
ECONMP.MX) when the fan is at Supply Fan
Maximum Speed (Configuration
damper position will vary at other fan speeds as described in
the Economizer section, when the space is occupied and the indoor fan is on.
IA.CF = 1 (DCV)
When IA.CF = 1, the IAQ algorithm is set for Demand Controlled Ventilation (DCV). During DCV, the damper modulates
between two user configurations depending upon the relationship between the Indoor Air Quality (IAQ) and the Outdoor
Air Quality (OAQ).
The lower of these two positions is referred to as the Econo
Min IAQ Position (Configuration
the higher is referred to as the Econ Min at Max Fan Speed
(Configuration
sition (AQ.MN) should be set to an economizer position that
brings in enough fresh air to remove contaminates and CO
generated by sources other than people. The Econ Min at Max
Fan Speed (MP.MX) should be set to an economizer position
that brings in fresh air to remove contaminates and CO
ated by all sources including people when the indoor fan is operating at the Supply Fan Maximum Speed (Configura-
tion
I.FANFS.MX). The Econ Min at Max Fan Speed
(MP.MX) value is the design value for maximum occupancy.
The ComfortLink controls will begin to open the damper from
the Econo Min IAQ Position (AQ.MN) position when the IAQ
level begins to exceed the Outdoor Air Quality (OAQ) level by
a configurable amount. This amount is referred to as AQ Differential Low (Configuration
differential between IAQ and OAQ reaches AQ Differential
High (Configuration
sition will be at the Econ Min at Max Fan Speed (MP.MX)
when the indoor fan speed is at Supply Fan Maximum Speed
(FS.MX). When the IAQ/OAQ differential is between AQ Differential Low (AQD.L) and AQ Differential High (AQD.H),
the control will modulate the damper between Econ Min at
Max Fan Speed (MP.MX) and Econo Min IAQ Position
sensor whose measurements are dis-
2
sensor for indoor-outdoor differential de-
2
sensor may be mounted in the
2
AIR.QOA.CF) and other related fan and
I.FANFS.MX) and the
AIR.QAQ.MN), while
ECONMP.MX). The Econo Min IAQ Po-
gener-
2
AIR.QAQD.L). When the
AIR.QAQD.H), the economizer po-
(AQ.MN) in a linear manner as shown in Fig. 8. At other fan
speeds the economizer damper will operate in the shaded area
between the two economizer position curves but at the actual
fan speed as indicated by Commanded Fan Speed (Out-
FAN SF. S P D ). (See Fig. 8.)
puts
Fig. 8 — Economizer Minimum Position
IA.CF = 2 (Override IAQ)
When IA.CF = 2, the IAQ algorithm maintains the damper at
Econ Min at Max Fan Speed (Configura-
tion
ECONMP.MX) when the indoor fan speed is at Sup-
ply Fan Maximum Speed (Configuration
I.FANFS.MX)
or along the curve on Fig. 8 when the indoor fan speed is at the
Commanded Fan Speed (Outputs
FAN SF. S P D ) until the
override condition triggers. The override triggers when the
IAQ/OAQ differential is greater than AQ Differential High
(Configuration
tion (Configuration
AIR.QAQD.H). The IAQ Override Posi-
AIR.QOVR.P) sets the damper posi-
tion during override. The economizer damper will return to the
Econ Min at Max Fan Speed (MP.MX) or MP.MX curve at oth-
er fan speeds when the IAQ/OAQ differential is less than the
AQ Differential Low (Configuration
AIR.QAQD.L).
The override algorithm will operate whenever the building is
occupied and the indoor fan is operating or whenever the IAQ
algorithm has caused the indoor fan to operate. The IAQ Analog Fan Config (Configuration
AIR.QIA.FN) determines
whether or not the IAQ algorithm can turn on the indoor fan. If
the indoor fan is not operating, the economizer position will be
zero. If the override is not active and the building is unoccu-
2
pied, the economizer position will be zero. The damper position may exceed Econ Min at Max Fan Speed (MP.MX) or IAQ
Override Position (OVR.P) to provide economizer cooling.
IA.CF = 3 (Control Minimum Position)
When IA.CF = 3, an external 4 to 20 mA source is used to set
the minimum position. The 4mA signal corresponds to 0% and
the 20 mA signal corresponds to 100%. In this mode, configurations such as Econ Min at Max Fan Speed (Configura-
tion
ECONMP.MX), Econo Min IAQ Position (Configu-
ration
AIR.QAQ.MN) and the economizer minimum posi-
tion and DCV minimum position curves in Fig. 7 and 8 are not
used. If the indoor fan is not operating, the economizer position
will be zero. The damper position may exceed the economizer
minimum position to provide economizer cooling.
IAQ (SWITCH INPUT)
Indoor air quality can also be measured using a switch input. For
the purpose of specifying the type of switch input, low CO
els are considered normal. The IAQ switch input is defined by
27
lev-
2
the IAQ Switch Input Config (Configuration
AIR.QII.CF).
Enthalpy and IAQ are controlled by the same switch input and
therefore cannot be used simultaneously.
II.CF = 0 (No IAQ)
The II.CF = 0 configuration signifies that there is no IAQ
switch input. The damper will operate at the Econ Min at Max
Fan Speed (Configuration
ECONMP.MX) and corre-
sponding damper position curve based on indoor fan speed
when the space is occupied and the indoor fan is on.
The Demand Controlled Ventilation (DCV) allows the economizer minimum position to be decreased when there is no IAQ
problem. If IAQ is low, the economizer minimum position is
Econo Min IAQ Position (Configuration
AIR.QAQ.MN)
when the indoor fan is operating at Supply Fan Maximum
Speed (Configuration
UNITFS.MX). If IAQ is high, the
economizer minimum position is Econ Min at Max Fan Speed
(Configuration
ECONMP.MX) when the indoor fan is op-
erating at Supply Fan Maximum Speed (FS.MX). If the fan
speed is modulating, see Fig. 8 for higher or lower damper position setting at the specific fan speed.
The damper override function permits absolute positioning of
the economizer damper for ventilation purposes. The override
is active when IAQ is high and inactive when IAQ is low. The
override position is configured by the IAQ Override Position
(Configuration
AIR.QOVR.P).
OUTDOOR AIR QUALITY (ANALOG INPUT)
The ComfortLink control can be configured for outdoor air
quality sensors which provide a 4 to 20 mA signal corresponding to 0 to 2000 ppm CO
. If a field supplied sensor has a dif-
2
ferent range, the ppm display range must be reconfigured by
entering new values for the OAQ Sensor Value at 4mA (Con-
figuration
(Configuration
AIR.QO.4M) and OAQ Sensor Value at 20mA
AIR.QO.20M).
OA.CF = 0 (No OAQ)
This signifies that there is no outdoor air sensor installed. The
default value of OAQ is 400 ppm CO
when using demand
2
controlled ventilation (DCV).
OA.CF = 1 (DCV)
The outdoor air quality sensor analog input is the value of
OAQ for demand controlled ventilation (DCV).
OA.CF = 2 (OAQ Lockout)
The outdoor air quality analog input is only used to lock out the
outdoor ventilation. The economizer commanded position is
set to 0% when the CO
ppm exceeds the OAQ lockout value
2
configured for the OAQ Lockout Limit (Configura-
tion
AIR.QOAQ.L). The default value for OAQ Lockout
Limit (OAQ.L) is 600 ppm CO
.
2
FAN ENABLE (ANALOG IAQ SENSOR)
The DCV algorithm will operate whenever the building is oc-
cupied and the indoor fan is operating or whenever the IAQ algorithm has caused the indoor fan to operate. The IAQ Analog
Fan Config (Configuration
AIR.QIA.FN) determines
whether or not the IAQ algorithm can turn on the indoor fan. If
the indoor fan is not operating, the economizer position will be
zero. The damper position may exceed Econ Min at Max Fan
Speed (Configuration
ECONMP.MX) and corresponding
damper position curve to provide economizer cooling.
IA.FN = 0 (Never)
When IA.FN = 0, the IAQ algorithm can never turn on the fan.
IA.FN = 1 (Occupied)
When IA.FN =1, the IAQ algorithm will turn on the indoor fan
whenever the building is occupied and IAQ/OAQ differential
is greater than the Fan On AQ Differential (Configura-
tion
AIR.QDF.ON). The indoor fan will turn off when the
IAQ/OAQ differential is less than the Fan Off AQ Differential
(Configuration
AIR.QDF.OF).
IA.FN = 2 (Always)
The indoor fan operation for IA.FN = 2, is the same as the operation when IA.FN =1, except the algorithm is not limited to
the occupied periods only. The fan can be triggered on when
the space is occupied or unoccupied.
FAN ENABLE (SWITCH INPUT)
The DCV algorithm will operate whenever the building is oc-
cupied and the indoor fan is operating or whenever the IAQ algorithm has caused the indoor fan to operate. The IAQ Switch
Fan Config (Configuration
AIR.QII.FN) determines
whether or not the IAQ algorithm can turn on the indoor fan. If
the indoor fan is not operating, the economizer position will be
zero. The damper position may exceed Econ Min at Max Fan
Speed (Configuration
ECONMP.MX) and corresponding
damper position curve to provide economizer cooling.
II.FN = 0 (Never)
When the II.FN = 0, the IAQ algorithm can never turn on fan.
II.FN = 1 (Occupied)
When II.FN =1, the IAQ algorithm will turn on the indoor fan
whenever the building is occupied and IAQ is high. The indoor
fan will turn off when the IAQ returns to normal.
II.FN = 2 (Always)
The indoor fan operation for II.FN =2 is the same as the operation when IA.FN =1, except the algorithm is not limited to the
occupied periods only. The fan can be triggered on when the
space is occupied or unoccupied.
Optional Humidi-MiZer® Dehumidification System
Units with the factory-equipped Humidi-MiZer option are capable of providing multiple modes of improved dehumidification
as a variation of the normal cooling cycle. The Humidi-MiZer
option includes additional valves in the liquid line and discharge
line of each refrigerant circuit, a reheat coil downstream of the
evaporator, and Motormaster
all outdoor fans. The Humidi-MiZer Equipped (Configura-
tion
HMZRREHT) configuration is factory set to Yes for
Humidi-MiZer equipped units. This enables Humidi-MiZer operating modes and service test.
Humidi-MiZer operation requires installation and configuration
of either a space relative humidity sensor or a relative humidity
switch input. Space Humidity Switch (Configura-
tion
UNITRH.SW) set to 1 for use of a normally open
switch or 2 for normally closed switch. The switch is wired to
field connection terminal board terminal labeled HUM and the
“R2” terminal. Set RH Sensor on OAQ Input (Configura-
tion
UNITRH.S) to Yes for use of a 4 to 20 mA output RH
sensor wired to field connection terminal board (TB) terminals
SPRH and LPWR (for loop powered). RH Sensor Value at 4ma
(Configuration
AIR.QH.4M) sets the % display for a 4mA
input from the relative humidity sensor. RH Sensor Value at
20ma (Configuration
a 20mA input from the relative humidity sensor.
DEHUMIDIFICATION DEMAND
When using a humidistat or switch input, the demand for de-
humidification is seen as Space Humidity Switch (In-
puts
GEN.IHUM) being Low or High. A low value
means humidity level is good and a high value means that
dehumidification is needed.When using an RH sensor, the
demand is based on the Space Humidity Sensor (In-
puts
AIR.QSP.RH) value compared to the Space RH
®
variable-speed control of some or
AIR.QH.20M) sets the % display for
28
Occupied Setpoint (Setpoints
RH.SP) during the occupied
period and Space RH Unoccupied Setpoint (Set-
points
RH.UN) during unoccupied periods. If the Space
Humidity Sensor (SP.RH) value is above the Space RH Set-
point (RH.SP), then dehumidification is needed. If the
Space Humidity Sensor (SP.RH) value is below the Space
RH Setpoint (RH.SP) minus the Space RH Deadband (Set-
points
RH.DB), then dehumidification is no longer needed. If the unit is configured for space sensor control (Con-
figuration
Heat SP Deadband (Setpoints
UNITU.CTL = 3), then the setpoint Reheat
RH.HB) applies. This configuration sets the offset above the heating set point at
which a unit in Reheat2 mode will turn off. This is a protection against over cooling the space and causing a heat demand.
NOTE: When there is a dehumidification demand, the economizer
damper position is limited to its minimum damper position (Oper-
ating Mode
ECONEC.MP).
REHEAT MODES
Dehumidification (reheat) is a cooling mode function. Refer to
Cooling Operation for cooling mode control. With Humidi-MiZer
units there are three additional HVAC Mode (HVAC) expanded
texts available for the user: Reheat1, Reheat2, and Reheat1/Reheat2. Selection of the reheat mode for each refrigerant circuit is
determined by the dehumidification demand and the cooling demand. Table 10 shows the corresponding circuit mode and output
status for the different demand combinations. Units with multiple
circuits can operate with a combination of Reheat1 and Reheat2
circuits, as determined by the amount of space cooling demand.
See Appendix B for complete tables of unit operation response to
thermostat and humidity inputs.
NOTE: Compressor staging control for Humidi-MiZer units requires that circuit A always operates when circuit B is on. This applies to normal operation, service test, and for control alarm responses. This operation difference is required due to the fact that
the Motormaster outdoor fan control senses circuit A only.
Table 10 — Control Modes with Humidi-MiZer System
Output and Valve States versus Circuit Mode .x = Circuit A or B identifier
Operation of the revised refrigerant circuit for each mode is described below.
NOTE: x = refrigerant circuit A or B
Normal Cooling
For 48/50HC04-12 units, refrigerant flows from the outdoor condenser through the normally open Cooling Liquid Valve (CLV.x)
to the expansion device. Reheat Liquid Valve (RLV.x) and Reheat
Discharge Valve (RDV.x) are closed. (See Fig. 9.) For 48/
50HC14-28 units, refrigerant flows from the outdoor condenser
through the de-energized 3-way Liquid Diverter Valve (LDV.x) to
the expansion device. Reheat Discharge Valve (RDV.x) is closed.
(See Fig. 10.)
Reheat 1 (Subcooling Mode)
This mode increases latent cooling and decreases sensible cooling
compared to normal cooling.
For 48/50HC04-12 units, refrigerant flows from the outdoor condenser, through the normally open Reheat Liquid Valve (RLV.x),
and through the reheat condenser coil to the expansion device.
Cooling Liquid Valve (CLV.x) and Reheat Discharge Valve
(RDV.x) are closed. (See Fig. 11.)
For 48/50HC14-28 units, refrigerant flows from the outdoor condenser, through the energized 3-way Liquid Diverter Valve
(LDV.x), and through the reheat condenser coil to the expansion
device. Reheat Discharge Valve (RDV.x) is closed. (See Fig. 12.)
Reheat 2 (Hot Gas ReheatMode)
This mode provides maximum latent cooling with little to no sensible capacity. This mode can operate to provide dehumidification
when there is no cooling demand. Similar to Reheat 1 mode, refrigerant flows from the outdoor condenser, through the normally
open Reheat Liquid Valve (RLV1.x), or through the energized 3way Liquid Diverter Valve (LDV.x), and through the reheat con-
denser coil to the expansion device. Reheat Discharge Valve
(RDV.x) is open which provides some compressor discharge gas
to the reheat condenser to further increase the reheat of the evaporator air stream (See Fig. 13 or 14 based on unit and size).
DEMAND AND MODE OUTPUTS 48/50HC 04-12 VALVES 48/50HC 14-28 VALVES
Space
Humidity
— — No power Off Off Off Off (open) Off (open) Off (closed) Off Off (closed)
Low No Off Off Off Off Off (open) On (closed) Off (closed) Off Off (closed)
Low Yes Cool On Off Off Off (open) On (closed) Off (closed) Off Off (closed)
High Yes Reheat1 On On Off On (closed) Off (open) Off (closed) On Off (closed)
High No Reheat2 On On On On (closed) Off (open) On (open) On On (open)
Circuit
Cooling
Demand
Circuit
Mode
Circuit
Compressor
(CMP.x)
Cooling-
Reheat
Control
(CRC)*
Reheat2
Valve
(RH3.x)
CLV.x Valve
2-way
RLV.x Valve
2-way
RDV.x
Valve 2-way
RLV.x Valve
3-way
RDV.x
Valve 2-way
29
COMP
LIOC REZIM-IDIMUHLIOC DNOC
EVAP COIL
INDOOR ENTERING
AIR
METERING
DEVICE
RLV.x
RDV.x
OUTDOOR AIR
CLOSED VALVE
OPEN VALVE
CLV.x
COMP
LIOC REZIM-IDIMUHLIOC DNOC
EVAP COIL
INDOOR ENTERING
AIR
METERING
DEVICE
LDV.x
RDV.x
OUTDOOR AIR
CLOSED VALVE
OPEN VALVE
3-WAY VALVE
Fig. 9 — Normal Cooling Mode — Humidi-MiZer
®
System — 48/50HC 04-12
Fig. 10 — Normal Cooling Mode — Humidi-MiZer System
Fig. 13 — Hot Gas Reheat Mode (Reheat2) — Humidi-MiZer
48/50HC 04-12
RDV.x
LDV.x
OUTDOOR AIR
®
System
LIOC REZIM-IDIMUHLIOC DNOC
CLOSED VALVE
OPEN VALVE
3-WAY VALVE
Fig. 14 — Hot Gas Reheat Mode (Reheat2) — Humidi-MiZer System
48/50HC 14-28
32
METERING
DEVICE
EVAP COIL
INDOOR ENTERING
AIR
REHEAT CONTROL
The cooling staging and compressor control routines are re-
sponsible for controlling each circuit in one of the three submodes (Cool, Reheat1, or Reheat2). When there is only a cooling demand, one or more circuits will operate in normal cooling mode. When there is only dehumidification demand, all
circuits will operate in Reheat2 mode. When there is both cooling demand and dehumidification demand, all circuits will operate in either Reheat1 or Reheat2 mode, with the portion of
Reheat1 circuits determined from the cooling demand. The Requested Reheat2 Stages (Operating ModesHMZRREQ.R) shows the control’s request for reheat circuits if cooling is not already requesting all stages. Available
Reheat2 Stages (Operating ModesAVL.R) displays circuits that are available for reheat use. Actual Reheat2 Stages (Operating ModesACT.R) displays the current number of circuits running in Reheat2 mode. These three status points should only be monitored when there is only a dehumidification demand, because
their values can be forfeited to cooling stages when cooling demand is present. Reheat2 Stage Incr. Time (Configura-
tion
HMZRR.INC) and Reheat2 Stage Decr. Time (Con-
figuration
or subtracting a compressor for a reheat function. These only
apply when using adaptive thermostat or space sensor control.
There are three relay outputs that show reheat status. Cool Reheat1 Control (Outputs
has switch from pure cooling to reheat ready (based on a dehumidification demand). Reheat2 Valve A (Out-
puts
puts
Reheat2 valve is energized.
A circuit can be restricted from Reheat2 operation by the out-
side temperature and saturated suction temperature. Reheat2
OAT Limit A (Configuration
OAT Limit B (Configuration
est outside temperature the respected circuit is allowed to run
in reheat2 mode. The lockout on/off status is shown as Reheat2
OAT Lockout A (Operating Modes
R.LO.A) and Reheat2 OAT Lockout B (Operating
ModesCOOLHMZRR.LO.B) for their respective cir-
cuit. If a circuit’s saturated suction pressure falls below the low
limit configuration during Reheat2 operation, the circuit will
switch to reheat1 (the circuits Reheat2 valve will be turned off)
for at least 2 minutes and until its suction rises back above the
high limit. Reheat2 SSP Lo Limit A (Configura-
tion
uration
heat2 mode for individual circuits. Reheat2 SSP Hi Limit A
(Configuration
B (Configuration
limit for Reheat2 mode for each circuit.
REHEAT MODE DIAGNOSTIC HELP
The status of reheat mode sensor inputs may be viewed within
the display Inputs menu. The status of reheat mode outputs
may be viewed within the display Outputs or Run Sta-
tus
tus of circuit reheat temperature limit lockouts may be viewed
within the Humidi-MiZer sub-menu of the cooling mode diagnostic table at Operating Modes
The Service Test mode may be used to force the system to operate in various stages of Reheat1 or Reheat2 mode, or to independently operate the reheat valve control outputs.
The following forced operating states are changed or added to
the available service test operation for a Humidi-MiZer
equipped unit:
Service Test
A value of On will turn on circuit A in Normal Cooling mode.
HMZRR.DEC) set the time delay when adding
COOLCRC) shows when the unit
COOLRH2.A) and Reheat2 Valve B (Out-
COOLRH2.B) display when the respective circuit’s
HMZRRA.LO) and Reheat2
HMZRRB.LO) set the low-
HMZRRA.LP) and Reheat2 SSP Lo Limit B (Config-
HMZRRB.LP) set the low pressure limit for Re-
HMZRRA.HP) and Reheat2 SSP Hi Limit
HMZRRB.HP) set the high pressure
COOL menus. Additional diagnostic help, including sta-
COOLCMP.A (Cool A Test)
COOLHMZR.
COOL
COOLHMZR
COOLHMZR
COOLHMZR
Service Test
A value of On will turn on circuits A and B in Normal Cooling
mode.
Service Test
A value of On will turn on circuit A in Reheat1 mode.
Service Test
A value of On will turn on circuits A and B in Reheat1 mode.
Service Test
A value of On will turn on circuit A in Reheat2 mode.
Service Test
A value of On will turn on circuits A and B in Reheat2 mode.
Service Test
For 48/50HC04-12 units, a value of On will turn on the CRC
relay. This will turn on CLV.x valves and turn off RLV.x
valves.
For 48/50HC14-28 units, a value of On will turn on the CRC
relay. This will energize the LDV.x valves.
Service Test
A value of On will turn on the RDV.A valve.
Service Test
A value of On will turn on the RDV.B valve.
COOLCMP.B (Cool B Test)
HMZRRH1.A (Reheat1 A Test)
HMZRRH1.B (Reheat1 B Test)
HMZRRH2.A (Reheat2 A Test)
HMZRRH2.B (Reheat2 B Test)
HMZRCRC (Cool-Reheat1 Valve Test)
HMZRRHV.A (Reheat2 Valve A Test)
HMZRRHV.B (Reheat2 Valve B Test)
Temperature Compensated Start
This logic is used when the unit is in the unoccupied state. The
control will calculate early Start Bias time based on Space
Temperature deviation from the occupied cooling and heating
set points. This will allow the control to start the unit so that
the space is at conditioned levels when the occupied period
starts. This is required for ASHRAE 90.1 compliance. A space
sensor is required for non-linkage applications.
SETTING UP THE SYSTEM
The settings for temperature compensated start can be found in
the local display under Configuration
ITEM EXPANSION RANGE UNITS CCN POINT
TCS.C Temp.Cmp.Strt.Cool Factr 0 - 60 min TCSTCOOL
TCS.H Temp.Cmp.Strt.Heat Factr 0 - 60 min TCSTHEAT
Temp Comp Strt Cool Factr (TCS.C)
This is the factor for the start time bias equation for cooling.
Temp Comp Strt Heat Factr (TCS.H)
This is the factor for the start time bias equation for heating.
NOTE: Temperature compensated start is disabled when these
factors are set to 0.
TEMPERATURE COMPENSATED START LOGIC
The following conditions must be met for the algorithm to run:
•Unit is in unoccupied state.
•Next occupied time is valid.
•Current time of day is valid.
•Valid space temperature reading is available (sensor or
CCN network).
The algorithm will calculate a Start Bias time in minutes using
the following equations:
If (space temperature > occupied cooling set point)
Start Bias Time = (space temperature – occupied cooling set
point)* TCS.C
If (space temperature < occupied heating set point)
Start Bias Time = (occupied heating set point – space tempera-
ture)*TCS.H
When the Start Bias Time is greater than zero the algorithm
will subtract it from the next occupied time to calculate the
UNIT.
33
new start time. When the new start time is reached, the Temperature Compensated Start mode is set, the fan is started and
the unit controlled as in an occupied state. Once set, Temperature Compensated mode will stay on until the unit goes into the
Occupied mode. The Start Bias Time will be written into the
CCN Linkage Equipment Table if the unit is controlled in DAV
mode. If the Unoccupied Economizer Free Cool mode is active
when temperature compensated start begins, the Unoccupied
Free Cool mode will be stopped.
NOTE: The maximum minutes Start Bias can be is 180.
Carrier Comfort Network® (CCN) Configuration
It is possible to configure the ComfortLink control to participate as an element of the Carrier Comfort Network (CCN) system directly from the local display. This section will deal with
explaining the various programmable options which are found
under the CCN sub-menu in the Configuration mode.
The major configurations for CCN programming are located in
the local displays at Configuration
CCN Address (CCN.A)
This configuration is the CCN address the rooftop is assigned.
CCN Address (CCN.B)
This configuration is the CCN bus the rooftop is assigned.
CCN Baud Rate (BAUD)
This configuration is the CCN baud rate.
CCN Time/Date Broadcast (BROD
If this configuration is set to ON, the control will periodically
send the time and date out onto the CCN bus once a minute. If
this device is on a CCN network then it will be important to
make sure that only one device on the bus has this configuration set to ON. If more than one time broadcaster is present,
problems with the time will occur.
NOTE: Only the time and date broadcaster can perform daylight
savings time adjustments. Even if the rooftop is stand alone, the
user may want to set this to ON to accomplish the daylight/savings
function.
CCN OAT Broadcast (BROD
If this configuration is set to ON, the control will periodically
broadcast its outside-air temperature at a rate of once every 30
minutes.
Global Schedule Broadcast (BROD
If this configuration is set to ON and the schedule number
(SCH.N) is between 65 and 99, then the control will broadcast
the internal time schedule once every 2 minutes.
CCN Broadcast Acknowledger (BROD
If this configuration is set to ON, then when any broadcasting is
done on the bus, this device will respond to and acknowledge.
Only one device per bus can be configured for this option.
Schedule Number (SCH.O
This configuration determines what schedule the control may
follow.
SCH.N = 0
The control is always occupied.
SCH.N = 1
The control follows its internal time schedules. The user may
enter any number between 1 and 64 but it will be overwritten to
“1” by the control as it only has one internal schedule.
SCH.N = 65-99
The control is either set up to receive to a broadcasted time
schedule set to this number or the control is set up to broadcast
its internal time schedule (B.GS) to the network and this is the
global schedule number it is broadcasting. If this is the case,
then the control still follows its internal time schedules.
B.OAT)
SCH.N)
CCN. See Appendix A.
B.TIM)
B.GS)
B.ACK)
Accept Global Holidays? (SCH.O
If a device is broadcasting the time on the bus, it is possible to
accept the time yet not accept the global holiday from the
broadcast message.
Override Time Limit (SCH.O
This configuration allows the user to decide how long an override occurs when it is initiated. The override may be configured from 1 to 4 hours. If the time is set to 0, the override function will become disabled.
Timed Override Hours (SCH.O
This displays the current number of hours left in an override. It
is possible to cancel an override in progress by writing “0” to
this variable, thereby removing the override time left.
SPT Override Enabled? (SCH.O
If a space sensor is present, then it is possible to override an
unoccupied period by pushing the override button on the T55
or T56 sensor. This option allows the user to disable this function by setting this configuration to NO.
OV.TL)
HOL.G)
OV.EX)
OV.SP)
Demand Limit
Demand Limit Control may override the cooling algorithm to
limit or reduce cooling capacity during run time. The term Demand Limit Control refers to the restriction of machine capacity to control the amount of power that a machine will use. This
can save the owner money by limiting peaks in the power supply. Demand limit control is intended to interface with an external network system. This is through a CCN Loadshed POC
Device or writing to network points.
To limit stages through network writes, the points Run Sta-
tus
COOLMAX.C and Run StatusHEATMAX.H are
forced on the network through CCN points MAXCSTGS and
MAXHSTGS respectively. Force these to the desired maximum stages of cooling/dehumidification and heating, respectively.When there is no force on these points, they automatically reset to allow all cooling/dehumidification and heating stages to be used. These points are reset at power-on/reset (POR).
When using the Loadshed POC to do Demand Limiting, the
cool and heat stage limits under both Redline and Loadshed
conditions can be set individually with configuration decisions.
If the active stages is greater then the loadshed or redline configurations when a loadshed or redline command is given, the
unit will remove stages.
Configuration
This is the Loadshed Group Number and corresponds to the
loadshed supervisory devices that resides elsewhere on the
CCN network and broadcasts loadshed and redline commands
to its associated equipment parts. This variable will default to
zero which is an invalid group number. This allows the loadshed function to be disabled until configured.
Configuration
This configuration tells the unit the maximum cooling stages
allowed to be on during a redline condition.
Configuration
This configuration tells the unit the maximum cooling stages
allowed to be on during a loadshed condition.
Configuration
This configuration tells the unit the maximum heating stages
allowed to be on during a redline condition.
Configuration
This configuration tells the unit the maximum heating stages
allowed to be on during a loadshed condition.
The two Demand Limiting methods can be active simultaneously. The lowest cool and heat stage limits imposed by either method are applied, and these “effective stage limits” are shown in
the points CSTGLIMT (Run Status
HSTGLIMT (Run Status
CCNLDSHS.GRP
CCNLDSHR.MXC
CCNLDSHS.MXC
CCNLDSHR.MXH
CCNLDSHS.MXH
HEATLMT.H), respectively. In
COOLLMT.C) and
34
normal running mode, these limits will prevent stages from being added, or stages to be removed, as applicable. In test mode,
these limits are ignored, and the user may continue to operate all
stages. The point MODEDMDL (Run StatusMODED.LMT) is used to show if any Demand Limiting is in
effect that prevents the unit from operating either cooling or
heating at full-capacity.
NOTE: MODEDMDL may reflect that staging is NOT limited
even though Loadshed is active, or the network points are being
forced, if the stage limits in effect are not less than the stages present in the unit.
If a more drastic mode of Demand Limiting is required, the
network point HVACDOWN (Run Status
can be used to prohibit the unit from selecting any HVAC
mode, thus preventing the operation of the supply fan, compressors, condenser fans, and heat stages. This point must also
be forced, and is reset automatically when not forced, and at
POR.
NOTE: HVACDOWN can be used as an immediate shutdown of
the unit before limiting capacity (ex. Generator switching).
MODEHV.DN)
Linkage
ComfortLink controls do not require any configuration settings
to establish linkage with a Linkage Coordinator. This is done
automatically when the unit’s bus and element address are configured in the Linkage Coordinator’s LINKAGE configuration
table. The linkage information that is supplied to the Com-fortLink unit by the Linkage Coordinator is as follows:
•Reference zone temperature
•Reference zone occupied biased heating and cooling set
points
•Reference zone unoccupied heating and cooling set points
•Composite occupancy mode
The unit will control the equipment based on this information
and in return will provide the Linkage Coordinator with the
following data:
•Operating mode - Cooling, Heating, Free Cooling, Fire
Shutdown Evacuation, or Off
•Supply-air temperature
•Optimal Start Bias time (Based on worst case zone)
This synchronization of data optimizes the efficiency of the
unit and the zones to operate at peak system performance at all
times. This information can be seen in linkage maintenance tables of the Linkage Coordinator and the RTU; it is updated at
approximately 1-minute intervals.
Cooling and heating operation is slightly modified during
Linkage control. A PID loop is run to calculate required stages.
This is necessary because in stand alone operation, the unit
tries to anticipate the space. With Linkage, the unit must try to
satisfy the demand as soon as possible. The PID configurations
are in Configuration
ed and the default values should NOT BE CHANGED.
For information on set up and configuration, see the Space
Temperature Control-CCN Linkage text in the Controls Quick
Start section of this book.
For additional information on the Linkage Coordinator or Zone
Controllers, please refer to their appropriate manuals.
PID. These values have been field test-
Alarm Handling
There are a variety of different alerts and alarms in the system.
Alerts are indicated by TXXX (where XXX is the alert number) on the display and generally signify that the improperly
functioning circuit can restart without human interaction. If an
alarm occurs, indicated by AXXX (where XXX is the alarm
number), the damaged circuit will generally not restart without
an alarm reset via the scrolling marquee display or CCN.
The response of the control system to various alerts and alarms
depends on the seriousness of the particular alert or alarm. In
the mildest case, an alert does not affect the operation of the
unit in any manner. An alert can also cause a “strike.” A “striking” alert will cause the circuit to shut down for 15 minutes.
This feature reduces the likelihood of false alarms causing a
properly working system to be shut down incorrectly. If three
strikes occur before the circuit has an opportunity to show that
it can function properly, the circuit will strike out, causing the
shutdown alarm for that particular circuit. Once activated, the
shutdown alarm can only be cleared via an alarm reset.
However, circuits with strikes will be given an opportunity to
reset their strike counter to zero. As discussed above, a strike
typically causes the circuit to shut down. Fifteen minutes later,
that circuit will once again be allowed to run. If the circuit is
able to run for 1 minute, its replacement circuit will be allowed
to shut down (if not required to run to satisfy requested stages).
However, the “troubled” circuit must run continuously for a
user defined time (Configuration
detectable problems before the strike counter will be reset to
zero. Default value is 5 minutes.
CCN ALARM BROADCAST
Operators of CCN networks might not want to be notified of
“striking” alerts for refrigerant circuits until the circuit has
been shut down due to 3 strikes. Set the cooling configuration
of Alert Each Strike (Configuration
play, ALM_NOW on CCN) to YES to broadcast each circuit
strike alert. Set Alert Each Strike to NO to broadcast only circuit shut down. Alert Each Strike configuration is ignored
during Service Test and all alerts are broadcast.
ALARM RELAY OUTPUT
The alarm relay output is a normally open 24 vac output be-
tween field connection terminal board terminals C and X. Selection of which alerts and alarms will result in closing of the
alarm relay may be set in the Alarm Relay Configuration (Con-
figuration
sult in the alarm output relay, ALRM, status of ON and 24 vac
between C and X on the field connection terminal board when
that particular condition is in an alarm state. Setting a configuration to NO will result in no action by the alarm output relay
for that particular condition.
NOTE: An accessory filter switch can be used along with the
alarm relay output function to indicate dirty filter service need.
See the Troubleshooting section for more information on viewing, diagnosing, and clearing alerts and alarms.
ALM.O). Setting a configuration to YES will re-
COOLRST.C) with no
COOLALM.N on dis-
EnergyX® Units
GENERAL
An EnergyX unit is a 48/50HC rooftop unit and energy recov-
ery ventilator (ERV). It operates the ERV module in an integrated manner with the base rooftop unit. The base rooftop unit
functions per the base unit sequence of operation, for information regarding ComfortLink controller operation see the Com-fortLink Controls, Start-Up, Operations, and Troubleshooting
Instructions. The ERV will operate based on communication
from the ComfortLink controller. The following section discusses the ERV operation in detail. In summary, the ERV operates to provide pre-conditioned outside air for ventilation requirements. If equipped with an optional economizer the ERV
can provide free cooling when the outside air conditions are
satisfactory.
In general the ERV monitors occupancy and indoor fan state of
the base unit to determine when to activate. The outside air
fan(s) bring in the outside air pass it through the enthalpy
wheel and into the rooftop mixing box. The building return air
is pulled through the enthalpy wheel by the exhaust fan(s) and
released outside. During operation the enthalpy wheel is rotating to use the building air to pre-condition the outside air.
35
When free cooling is desired and allowed the wheel is not
needed to pre-condition the air therefore an economizer damper (wheel bypass) is used to bring in the outside air directly to
the mixing box.
COMMUNICATION
The ERV relies on communication with the ComfortLink
controller to operate. The ERV monitors ComfortLink controller points to determine operation. The ERV writes to
points in the ComfortLink controller to provide the user with
Table 11 — Inputs - Points the ERV Reads from ComfortLink Controller
its running status. If communication is lost the ERV will shut
down and remain in the Off mode until communication is established. Refer to the troubleshooting section for details on
communication failures. Table 11 shows the ComfortLink
points that the ERV monitors for operation and a brief description of their functions. Table 12 shows the ComfortLink
points that the ERV uses for its configurations and a brief description of each. Table 13 shows the ComfortLink points that
the ERV writes to based on its running status.
CCN POINT*
NVO_MODEnvoUnitStatus.modexxxxDetermine what mode RTU is in
OCCUPIED OCCCurrently OccupiedNo/YesDetermine if RTU is occupied
IDFSTATEIndoor Fan StateOff/OnDetermine if the RTU indoor fan is running
FANSPEED F.SPDCommanded Fan Speedxxx%Determine if the RTU indoor fan is running
ECONOCMD EC.CPEcono Commanded Position 0 to 100%Determine if the RTU commands free cooling
IAQIAQIAQ Level (sensor)xxxxSpace CO
IAQINIAQ.SIAQ Level (switch)Low/HighDetermine if CO
SATSATSupply Air Temperaturexxx.x°F RTU supply air temp
OA_TEMPOATOutdoor Air Temperaturexxx.x°F RTU Outdoor Temp
SPACE_TSPTSpace Temperaturexxx.x°F Building Space Air Temp
RETURN_T RATReturn Air Temperaturexxx.x°F Building Return Air Temp
PE_1PE.1Power Exhaust 1 RelayOff/OnN/A
PE_2PE.2Power Exhaust 2 RelayOff/OnN/A
ECONOEC.ENEconomizer InstalledNo/YesNo: no FIOP
IAQANCFG IA.CFIAQ Analog Input Config0=No IAQ
IAQANFAN IA.FNIAQ Analog Fan Config0=Never
IAQINCFGII.CFIAQ Switch Input Config0=No IAQ
IAQINFANII.FNIAQ Switch Fan Config0=Never
DAQ_LOWAQD.LAQ Differential Low0 to 5000100Sets indoor/outdoor PPM difference to start
DAQ_HIGH AQD.HAQ Differential High0 to 5000700Sets indoor/outdoor PPM at which max vent
IAQOVPOS OVR.PIAQ Override Position0 to 100%100Sets OA fan speed during override
S_OADMPR OA.DMOAU 2 - position DamperClose/OpenCloseTest damper while in test mode
S_WHEELWHLOAU Wheel Test0 to100%0Test wheel while in test mode
S_OAFANOA.OFOAU OA Fan Speed Test0 to100%0Test intake fan(s) while in test mode
S_EXFANOA.XFOAU PE Fan Speed Test0 to100%0Test exhaust fan(s) while in test mode
S_OAHEAT OA.HTOAU Tempring Heater Test 0 to 100%0Test tempering heater while in test mode
* These can be viewed under a variety of CCN tables with a CCN device.
† These can be viewed under a variety of menus on the scrolling marquee or Navigator™ display.
SCROLLING
MARQUEE
POINT†
EXPANDED TEXTRANGEUNITSDEFAULTFUNCTION
2 sensor level (PPM)
2 is high or low
Determine if there is a Economizer damper
(wheel Bypass)
Tells if a sensor is installed for DCV or override
high CO
high CO
ventilating more
occurs
2
2
1=DCV
2=Override IAQ
3=Ctrl Min Pos
1=Occupied
2=Always
1=DCV N/O
2=DCV N/C
3=Override N/O
4=Override N/C
1=Occupied
2=Always
Yes:
FIOP
0: no FIOP
1: FIOP
0Tells if the ERV can run during unoccupied for
0Tells if a switch is installed for DCV or override
MINDCVSPDCV.MMin DCV Outside Air CFM 0 to 32000CFM
PEX_CTLPEX.CPower Exhaust Control
EXOFFSETPE.OF
OAU_BPSPBP.SPBuilding Pressure Setpnt - 0.25 to 0.25in H
OATEMPEROA.TMOutside Air TemperingDisable/EnableDisable
OATMPLOCTM.LO
OATMPSPTTM.SP
OACFM_KOAC.KOutside Air CFM k Factor 0.8 to 1.21.0
EXCFM_KEXC.KExhaust Air CFM k Factor 0.8 to 1.21.0
EFB_ENBLEFBEERV Fan Boost EnableNo/YesNO
* These can be viewed under the CCN Table OAU_CFG with a CCN device.
†These can be viewed under Configuration → OAU on the scrolling marquee or Navigator™ display.
1: 04, 1ph, and econ
2: 04, 3ph, and econ
3: 04, 1ph, and no econ
4: 04, 3ph, and no econ
5: 05-06 1ph
6: 05-06 3ph
7: 07
8: 08-12
9: 14
10: 17-20 and econ
11: 17-20 and no econ
12: 24-28
OAFANSPDOA.FSOAU OA Fan Speed0 to100%Current ERV’s intake fan(s) speed
OAUPESPDEX.FSOAU Exhaust Fan Speed0 to100%Current ERV’s exhaust fan(s) speed
OAHEATEROA.HTOAU Tempering Heater0 to 100%ERV’s SCR heater commanded capacity
OAUALRM1ALM.1OAU Motor Failure AlarmOff/OnERV’s motor failure alarm status
OAUALRM2ALM.2OAU Dirty Filter AlarmOff/OnERV’s dirty filter alarm status
OAUALRM3ALM.3OA Low CFM AlarmOff/OnERV’s low CFM alarm status
OAUALRM4ALM.4OAU AlarmOff/OnERV’s General Alarm status
* These can be viewed under Run Status→OAU or Operating Modes→OAU on the scrolling marquee or Navigator™ display.
† These can be viewed under the CCN tables OAUDISP or OAU_DIAG with a CCN device.
* Min CFM represents the minimum outside air CFM requirement based on CO
2
values and setpoints.
** Occupied also means being in the unoccupied period but configured to run.
NO
YES
Is there
frost on the
wheel?
YES
NO
Is unit
occupied**
and IDF on?
NO
YES
ERV Mode = OFF
Wheel = off
ERV 2POS Damper = Closed
OA CFM = 0
Ex CFM = 0
ERV Mode = Test
User sets ERV to desired values for
testing purposes
OAU OA Fan Speed Test→OA.OF
OAU PE Fan Speed Test→OA.XF
OAU 2-position Damper Test→OA.DM
OAU Wheel Test→WHL
ERV Mode = Free Cooling
Wheel = stop-jog
ERV 2POS Damper = Open
OA CFM = Between Min CFM*
and 100 dependent on Econ Pos
Ex CFM = OA CFM - Ex CFM offset
ERV Mode = Defrost
Wheel = On
ERV 2POS Damper = Open
OA CFM = 0
Ex CFM = Min CFM* in effect
- Ex CFM offset
ERV Mode = ERV or DCV Mode
Wheel = On
ERV 2POS Damper = Open
OA CFM = Min CFM*
Ex CFM = OA CFM - Ex CFM offset
START
TEST
(RTU in test
mode)
COOL
(RTU in
Cool)
VENT
(RTU in Heat,
or Vent)
Is
economizer
open>than
5%?
The modulating ERV is an intelligent ERV with variable speed
fan motors. The ERV can provide a variety of volumes of outside air and offset it with different exhaust speeds. CO
can also be tied into it for demand controlled ventilation
sensors
2
(DCV) operation. The modulating ERV will operate based on
occupancy and the rooftop’s operating mode, the following
sections explain operation in detail. Refer to Fig. 15 for the
overview flow diagram of a modulating ERV operation.
Fig. 15 — Modulating ERV Control and Operation Flow Chart
39
OCCUPANCY
The ERV will not be allowed to run unless it is determined to
be occupied. The ERV monitors the rooftop’s occupancy point
(Run Status
pied. The ERV watches the rooftop’s indoor fan state point
(CCN Point = IDFSTATE) to know when its indoor fan has
started. When the rooftop is occupied and its indoor fan is on,
the ERV is considered to be occupied and allowed to run.
The ERV can also operate during the rooftop’s unoccupied period. If the ERV is configured for unoccupied operation (Configu-
rations
building occupancy of the ComfortLink controller and allow occupancy any time the rooftop fan is on. If not configured for unoccupied operation but there is a CO
and the ComfortLink controller is configured to turn on its indoor fan for CO
→MODE →OCC) to determine when it is occu-
→OAU →U.RUN = YES), then it will ignore the
sensor or switch installed
2
2 ventilation at any time (Configuration
→AIR.Q →IA.FN = 2, or Configuration →AIR.Q →II.FN
= 2), the ERV will be occupied any time the CO
MODES OF OPERATION
The ERV has 3 basic functions: Auto, Off, or Test. These are
defined as System run states and displayed in the OAU run status menu (Run Status
ways operate in one of the following operating modes depending upon the ComfortLink controller mode and outside conditions: Off, ERV (DCV) Free Cooling, OA Tempering, Defrost,
or Test. The ERV monitors the ComfortLink CCN point
NVO_MODE to determine the rooftops operating mode. The
NVO_MODE values tell the ERV what the rooftop operating
mode is in a numeric form. The ERV’s operating mode is displayed numerically as OAU Operating Mode (Run Status
→OAU →OA.RN). The ERV will al-
needs the fan.
2
→OAU →OA.OP). These modes and their corresponding
numbers are described below.
Off Mode (OA.OP = 0)
The ERV will be set to the Off mode whenever the rooftop indoor fan is turned off, ERV is unoccupied, NVO_MODE
equals 6, or if communication fails. During Off Mode, the ERV
2 position dampers will be closed and the wheel, outside air
fans(s), and exhaust fan(s) will be off.
Test Mode (OA.OP = 5)
If at any time during operation, the rooftop is put in Service
Test mode (NVO_MODE equals 7) the ERV will be set to Test
Mode. Refer to Start-Up section for Test mode operation.
Free Cooling Mode (OA.OP = 2)
Free Cooling Mode is only available if an optional economizer
damper is factory-installed in the ERV (Configuration
→ECON →EC.EN = Yes). Free Cooling Mode will be active
when the rooftop unit is in Unoccupied Free Cooling Mode,
Free Cooling Mode, or in Cooling Mode and the economizer
damper position (Outputs
5% (NVO_MODE = 10 or 3). ERV occupancy tells the control
which speed to start the outside air fan(s) during free cooling,
because the outside fan(s) are needed to assist the indoor fan in
bringing in outside air.
When in Free Cooling Mode, the ERV’s 2-position damper will
be open and the wheel will be set to stop/jog operation. The
rooftop unit will modulate the economizer damper to provide
free cooling as if an ERV was not installed. As the economizer
damper opens the ERV outside air fan(s) will maintain a speed
that produces minimum outside air CFM. Once the economizer
damper position passes that percent fan speed of the outside air
fan(s), the fan(s) speed will ramp up directly with the economizer damper position, up to 100%. The exhaust fan(s) will run
at a speed equal to the required offset CFM. Refer to Exhaust
Control for details on determining offset CFM.
→ECON →EC.CP) is greater than
IMPORTANT: Refer to the base unit Controls, Start Up,
operation, and Troubleshooting manual for details on how
the rooftop unit modulates the economizer damper for free
cooling.
Defrost Mode (OA.OP = 4)
Defrost Mode is only available when the optional Frost Protection is factory-installed in the ERV. The ERV will be set to defrost mode any time the ERV wheel is running and frost is detected on the wheel. The EXCB D14 LED will turn on to indicate the frost switch is active. Defrost Mode runs for at least 2
minutes but continues to run until the frost is removed. The
frost protection device senses a pressure differential across the
wheel and trips when that differential is greater than the setpoint (default 2.0 in wg). For information on the frost protection device, refer to the Major Component section.
When in Defrost Mode, the ERV 2 position damper will be
open and the wheel will be rotating. The outside air fan(s) will
ramp down to 0% speed (shut-off). The exhaust fan(s) will run
at a speed equal to the required offset CFM. Refer to Exhaust
Control for details on determining offset CFM.
ERV (DCV) Mode (OA.OP = 1)
General ERV Mode
ERV Mode is the basic operating mode of the ERV. With no
options installed on the ERV this will be the only operating
mode besides off and test. ERV Mode will be active when the
rooftop ComfortLink controller mode is Heating, Cooling, Fan
Only, or Dehumidification (NVO_MODE = 1, 3, 9, or 14) and
the ERV is occupied.
When in ERV mode, the ERV 2 position damper will be open
and the wheel will be rotating. The outside air fan(s) will run at
a speed that produces a CFM equal to the minimum outside air
CFM setpoint (Configuration
haust fan(s) will run at a speed equal to the required offset
CFM. Refer to Exhaust Control for details on determining offset CFM.
ERV Mode with DCV
If an optional economizer is factory-installed in the ERV (Con-
figuration
sensor or switch is installed (Configuration →AIR.Q
→ECON →EC.EN = Yes) and an optional CO
→OAU →OA.MN). The ex-
→IA.CF = 1 or 2) or (Configuration →AIR.Q →II.CF = 1
or 2), DCV ERV Mode will be active when the rooftop Com-
fortLink controller mode is Heating, Cooling, Fan Only, or De-
humidification (NVO_MODE = 1, 3, 9, or 14) and the ERV is
occupied.
When in DCV ERV mode, the ERV 2 position damper will be
open and the wheel will be rotating. The outside air fan(s) will
run at a speed that produces a CFM equal to the minimum outside air CFM determined by Demand Controlled Ventilation
(DCV). The exhaust fan(s) will run at a speed equal to the required offset CFM. Refer to Exhaust Control for details on determining offset CFM.
Sensor Demand Controlled Ventilation (DCV) uses the indoor
air quality levels (CO
is required for ventilation. The ERV monitors the IAQ (Inputs
→AIR.Q →IAQ) reading from the rooftop’s installed CO
sor and compares it to a hard coded outside air value of 400PPM.
The difference is then weighed on scale between AQ Differential
Low (Configuration
High (Configuration
minimum outside air CFM required for ventilation. The minimum outside air CFM can be equal to or between the Min DCV
outside air CFM (Configuration
and the minimum outside air CFM (Configuration
→OA.MN) setpoint. As the CO
to AQD.H, the ERV outside air CFM requirement will rise from
DCV.M to OA.MN. The outside air fan(s) will ramp its speed %
PPM) to determine how much outside air
2
sen-
2
→AIR.Q →AQD.L) and AQ Differential
→AIR.Q →AQD.H) to determine the
→OAU →DCV.M) setpoint
→OAU
differential rises from AQD.L
2
2
40
VENTILATION FOR PEOPLE
VENTILATION FOR SOURCES
INCREASING VENTILATION
ECON MIN
AT M AX
FANSPEED
POSITION
(MP.MX)
MINIMUM
IAQ
DAMPER
POSITION
(AQ.MN)
OC EDISTUO/EDISNI007001
2
DIFFERENTIAL
AQ
DIFFERENTIAL
LOW (AQD.L)
AQ
DIFFERENTIAL
HIGH (AQD.H)
up or down to produce the required CFM. If at any time the CO
sensor fails or IAQ reads 0ppm, the DCV minimum outside air
requirement will be forced to the maximum value (OA.MN).
Fig. 16 shows the DCV minimum outside air CFM determination curve.
Fig. 16 — IAQ DCV Control
Switch Demand Controlled Ventilation (DCV) uses the indoor
air quality levels (High/Low) to determine how much outside
air is required for ventilation. The ERV monitors the IAQ
switch (Inputs
installed CO
→AIR.Q →IAQ.S) reading from the rooftop’s
switch. The minimum outside air CFM will be
2
equal to one of the following: Min DCV outside air CFM
(Configuration
outside air CFM (Configuration
point. If the CO
→OAU →DCV.M) setpoint, or the minimum
→OAU →OA.MN) set-
switch reads low the outside air CFM require-
2
ment will be DCV.M. If the switch reads high the outside air
CFM requirement will be OA.MN. The outside air fan(s) will
ramp its speed % up or down to produce the required CFM.
OA Tempering Mode (OA.OP = 3)
OA Tempering Mode is only available when the optional electric heater is field-installed in the ERV and enabled (Configu-
ration
→OAU →OA.TM = Enable). The ERV can only be
set to OA Tempering mode when the ERV is occupied and the
rooftop is not running cooling or heating. The rooftop must be
in Ventilation (Fan-Only) mode (NVO_MODE = 9) and the
outside air temperature (Inputs
→AIR.T →OAT) must be
less than the OA Tempering Lockout Temp (Configuration
→OAU →TM.LO) to allow the ERV to run OA Tempering
Mode. The electric heater will then be turned on and modulated 0 to 100% based on the supply air temperature (Inputs
→AIR.T →SAT) relative to the OA Tempering SAT setpoint
(Configuration
When in OA Tempering Mode, the ERV runs as standard ERV
(DCV) mode: 2 position damper will be open and the wheel
will be rotating. The outside air fan(s) will ramp to maintain
correct outside air CFM. The exhaust fan(s) will ramp for the
required offset CFM. Additionally the ERV’s Electric Heater
will ramp up 1% every 2 seconds and ramp down 2% every 1
second based on how far the SAT is away from the setpoint. If
the SAT equals the setpoint then the electric heater will remain
at current percentage.
EXHAUST CONTROL
When the Power Exhaust control is set of Offset CFM (Config-
uration
→OAU →PEX.C = 0), the ERV exhaust fan(s) oper-
ate to offset the outside air being introduced to the building.
The required exhaust offset CFM is determined based on the
→OAU→TM.SP).
exhaust offset setpoint (Configuration
2
→OAU →PE.OF).
The exhaust offset setpoint can be set as a negative or positive
number to accommodate a requirement of positive or negative
building pressure. A positive setpoint will produce a negative
building pressure. A negative setpoint will produce a positive
building pressure.
The ERV will determine the required amount of outside air
CFM based on setpoints and current mode of operation. The
commanded exhaust air CFM (Run Status
→OAU →C.EX)
is then calculated by the sum of the actual outside air CFM
(Run Status
→OAU →A.OA) and the exhaust air offset set-
point (PE.OF). During defrost mode the exhaust will run the
same as if the outside air fan(s) were still running.
When the Power Exhaust Control is set for Building pressure
control (Configuration
→OAU →PEX.C = 1), the ERV ex-
haust fan(s) operate to maintain a building pressure. A building
pressure transducer must be purchased separately and properly
field-installed in the ERV. A desired building pressure is set as
Building Pressure Setpoint (Configuration
→BP.SP). The actual building pressure (Run Status →OAU
→BP) is compared to the setpoint (BP.SP). The exhaust fan
will then be ramped up and down at the rate of 1% every 2 seconds to try and maintain the desired building pressure. The exhaust fan(s) will slow to increase the building pressure and
speed up to decrease the building pressure.
WHEEL STOP/JOG
During free cooling the wheel utilizes a “stop-jog” operation to
periodically rotate the wheel and minimize potential dirt buildup and excess wear on one section of the wheel. The wheel will
rotate for 5 seconds then stop for 5 minutes.
STATUS POINTS
The ERV updates points within the ComfortLink controller to
represent its running status. These points are shown in Table 13
and can be viewed on the scrolling marquee or handheld Navigator™ display under the run status outside air menu (Run Status
→OAU). These points include but not limited to: commanded
and actual outside air CFM, commanded and actual exhaust air
CFM, ERV outputs, software versions, and internal ERV air
temperatures.
TROUBLESHOOTING
The scrolling marquee display shows the actual operating conditions of the unit while it is running. If there are alarms or
there have been alarms, they will be displayed in either the current alarm list or the history alarm list. (See Table 14.) The Service Test mode allows proper operation of the compressors,
fans, and other components to be checked while the unit is not
operating. See Service Test.
Complete Unit Stoppage
There are several conditions that can cause the unit not to provide heating or cooling:
•If an alarm is active which causes the unit to shut down, diagnose the problem using the information provided in
Alarms and Alerts section below.
•Cooling and heating loads are satisfied.
•Programmed occupancy schedule.
•General power failure.
•Tripped 24-volt transformer circuit breakers.
•Blown fuse or circuit breakers
•Unit is turned off through the CCN network.
•If supply-air temperature is less than the Minimum SAT
Lower Level (SAT.L) configuration value, unit cannot
cool.
41
→OAU
•If outdoor-air temperature is less than the Compressor
Lockout Temperature (CA.LO, CB.LO) configuration val-
ue, unit ca not cool.
•If outdoor-air temperature is greater than the Heating
Lockout Temperature (HT.LO) configuration value, unit
cannot heat.
Restart Procedure
Before attempting to restart the machine, check the alarm list
to determine the cause of the shut down. If the shutdown alarm
for a particular control function has occurred, determine and
correct the cause before allowing the unit to run under its own
control again. When there is problem, the unit should be diagnosed in Service Test mode. The alarms must be reset before
the control function can operate in either Normal mode or Service Test mode.
Alarms and Alerts
VIEWING AND CLEARING UNIT ALARMS
Presence of active alarms will be indicated on the scrolling
marquee display by the Alarm Status light turning on and by
the number of active alarms being displayed in the automatic
View of Run Status. Presence of active alarms may also be signaled on the Alarm Output terminals. Each alarm may also be
broadcast on the CCN network. Active alarms and past alarm
history can be reviewed and cleared via the local display or a
CCN device. The following menu locations are used for the local display:
Alarms
R.CURR (Reset All Current Alarms)
Change to YES to reset all active alarms. Turning unit power
off will also reset all current alarms.
Alarms
R.HIST (Reset Alarm History)
Change to YES to reset the alarm history. Turning unit power
off will not reset the alarm history.
Alarms
CURR (Currently Active Alarms)
Use the ENTER key, then scroll through any alarm numbers
using the up and down arrow keys. Alarms are displayed in numerical order.
Alarms
HIST (Alarm History)
Use the ENTER key, then scroll through any alarm numbers
using the up and down arrow keys. Up to 20 alarms are displayed in order of occurrence, with time and date.
The description for an alarm can be viewed on the scrolling
marquee display by pressing ESCAPE and ENTER keys simultaneously while displaying the alarm code number. Be sure
to expand description for each code, because in some cases
there are different possible descriptions and causes for the
same code number.
DIAGNOSTIC ALARM CODES AND POSSIBLE CAUSES
Alert Codes T051 and T055 (without Current Sensors)
These alerts can only be activated if set to Diagnose Compressor
Safety (Configuration
different texts for each alert code. There are two different alerts
which have corresponding test mode alerts indicated with “Service Test” in the expanded text. Pressing enter and esc on the
scrolling marquee or Navigator display to expand the T051 and
T055 alert will show you one of the below alerts. Make sure the
expanded text is read correctly before troubleshooting. Alert
codes T051 and T055 are for compressors A1 and B1 respectively.
•Compressor Safety Trip
These alerts occur when the respective compressor has been
running for 25 sec and the Saturated Suction Pressure (Pres-
sures
tion. A change in compressor operation is when the SSP changes more than the Maximum Suction Change configuration
SSP.A or SSP.B) reflects a change in compressor opera-
COOLD.CMP = Yes). There are 4
(Configuration
window while running the compressor and persists for 40 seconds. This alert can also occur when the respective compressor
is diagnosed with a high pressure switch trip. A high pressure
trip is when the compressor suction rises and falls two times
within 2 minutes.
When this occurs, the control turns off the compressor and logs
a strike for the respective circuit. These alerts reset automatically. The possible causes are: high-pressure switch (HPS)
open, Condensate overflow switch (COFS) open, compressor
internal protection is open, or a wiring error (a wiring error
might not allow the compressor to start). The HPS and optional
COFS are wired in series with compressor relays on the MBB.
If one of these opens during compressor operation, the compressor stops causing the control to activate this alert.
•Compressor Detected After Turnoff
These alerts occur when the respective compressor is turned
off but the Saturated Suction Pressure (PressuresSSP.B) does not reflect a shutdown. When shutting down a
compressor suction pressure must rise more than Maximum
Suction Change configuration (ConfigurationMX.SA or MX.SB) within the first 10 seconds and stay above
it. When this occurs, the control turns off all of the compressor
relays, stays in cooling mode and keeps the indoor fan on. Use
the scrolling marquee to reset the alert. The possible causes are
a welded contactor, frozen compressor relay on MBB, or adverse conditions.
Alert Codes T051 and T055 (with Current Sensors)
These alerts can only be activated if Current Sensing A1 or B1 is
enabled (Configurationabled). There are 4 different texts for each alert code. There are
two different alerts which have corresponding test mode alerts
indicated with “Service Test” in the expanded text. Pressing enter and esc on the scrolling marquee or Navigator display to expand the T051 and T055 alert will show you one of the below
alerts. Make sure the expanded text is read correctly before troubleshooting. Alert codes T051 and T055 for compressors A1 and
B1 respectively.
•Compressor Safety Trip
These alerts occur when the Current Sensor (CS) does not detect compressor current during compressor operation. When
this occurs, the control turns off the compressor and logs a
strike for the respective circuit. These alerts reset automatically. The possible causes are: high-pressure switch (HPS) open,
Condensate overflow switch (COFS) open, compressor internal protection is open, or a wiring error (a wiring error might
not allow the compressor to start). The HPS and optional
COFS are wired in series with compressor relays on the MBB.
If one of these opens during compressor operation, the compressor stops causing the control to activate this alert.
•Compressor Detected After Turnoff
These alerts occur when the Current Sensor (CS) detects current when the compressor should be off. When this occurs, the
control turns off all of the compressor relays, stays in cooling
mode and keeps the indoor fan on. Use the scrolling marquee
to reset the alert. The possible causes are a welded contactor,
frozen compressor relay on MBB, or adverse conditions.
Alert codes T064 and T065 are for circuits A and B respectively. These alerts occur when the temperature is outside the range
–40 to 240°F (–40 to 116°C). The cause of the alert is usually a
faulty thermistor, a shorted or open thermistor caused by a wiring error, or a loose connection.
Alert codes T066 and T067 are for circuits A and B respectively. These alerts occur when the unit’s suction transducers are
COOLMX.SA or MX.SB) in a two second
SSP.A or
COOL
COOLCS.A1 or CS.B1 = En-
42
turned off internally. Cooling will not operate. This is usually
due to a network force on a non exposed CCN point. Reload
factory defaults or reinstall software on the MBB. Consult the
network manager if alert continues.
Alert Code T073 — Outdoor Air Temperature Thermistor
Failure
This alert occurs when the temperature is outside the range –40
to 240°F (–40 to 116°C). For all units, all ambient temperature
lockout limits for cooling and heating are ignored. For economizer equipped units, the economizer will not operate to provide cooling. The economizer will still operate for ventilation.
This alert resets automatically. The cause of the alert is usually
a faulty thermistor, a shorted or open thermistor caused by a
wiring error, or a loose connection.
Alert Code T074 — Space Temperature Thermistor Failure
This alert occurs when the temperature is outside the range –40
to 240°F (–40 to 116°C). This alert will only occur if the unit
control type is configured for Space Sensor (versus Thermostat). Cooling and heating will not operate. For economizer
equipped units, the economizer will still operate for ventilation. This alert resets automatically. The cause of the alert is
usually a faulty thermistor in the T-55, T-56, or T-58 device, a
shorted or open thermistor caused by a wiring error, or a loose
connection.
Alert Code T075 — Supply Air Temperature Thermistor Failure
This alert occurs when the temperature is outside the range –40
to 240°F (–40 to 116°C). Economizer cooling and adaptive
compressor staging cannot occur while this alarm is active.
This alert resets automatically. The cause of the alert is usually
a faulty thermistor, a shorted or open thermistor caused by a
wiring error, or a loose connection.
Alert Code T076 — Return Air Thermistor Failure
This alert occurs when the temperature is outside the range –40
to 240°F (–40 to 116°C). This alert will only occur if the unit is
configured for a return air sensor. Economizer differential dry
bulb control will not be allowed during this alert. This alert resets automatically. The cause of the alert is usually a faulty
thermistor, a shorted or open thermistor caused by a wiring error, or a loose connection.
Alert Code T077 — Space Relative Humidity Sensor Failure
This alert occurs when the input is less than 3.5 mA and the
sensor is configured as installed. If a humidistat is not installed,
then dehumidification will not be functional. Check sensor and
wiring. This alert clears automatically.
NOTE: An ECB must be installed to use the space relative humidity sensor.
Alert codes T092 and T093 are for circuits A and B respectively. These alerts occur when the board does not properly read
the transducer voltage. A circuit cannot run when this alert is
active. Use the scrolling marquee to reset the alarm. The cause
of the alert is usually a faulty transducer, faulty 5-v power supply, or a loose connection.
Alert Codes T102 and T103 — Compressor Current Sensor
Failure
Alert codes T102 and T103 are for compressors A1 and B1, respectively. These alerts can only occur if the unit is configured to
have compressor current sensors (Configura-
tion
COOLCIR.ACS.A1 or CS.B1). These are not factory
installed so would have to be installed in the field and configured
accordingly. These alerts occur when the output of the current
sensor (CS) is a constant high value. These alerts reset automatically. The cause of the alert is a wiring error, a loose connection,
or when configured to have the sensors when they are not actually installed. If the problem cannot be resolved and the CS board
must be replaced, the CS board can be disabled while securing a
replaced board. A CS board is disabled by setting the corresponding configuration to DISABLE.
Alert Codes T110 and T111 — Circuit Loss of Charge
Alert codes T110 and T111 are for circuits A and B respectively. These alerts have “Service Test” text that will be displayed
if the alert occurred during service test. These alerts occur
when the compressor is OFF and the suction pressure is less
than 5 psig and OAT is greater than –5°F for 1 continuous minute. Use the scrolling marquee to reset the alert. The cause of
the alert is usually low refrigerant pressure or a faulty suction
pressure. These alerts only occur when the compressor is OFF
because the low refrigerant pressure alarms (alerts T133 and
T134) handle this situation when the compressor is operating.
Alert Codes T126 and T127 — Circuit High Discharge Pressure
Alert codes T126 and T127 are for circuits A and B respectively.
These alerts have “Service Test” text that will be displayed if the
alert occurred during service test. These alerts occur when alerts
T051 and T055 are active while the appropriate condensing temperature is greater than 150°F. These alerts reset automatically.
The cause of the alert is usually an overcharged system, high
outdoor ambient temperature coupled with dirty outdoor coil,
plugged filter drier, or a faulty high-pressure switch. See Alerts
T051 and T055 for diagnostic procedure.
Alert Codes T133 and T134 — Circuit Low Refrigerant Pressure
Alert codes T133 and T134 are for circuits A and B respectively. These alerts have “Service Test” text that will be displayed
if the alert occurred during service test. These alerts occur
when the compressor is operating and the evaporating temperature (converted from the suction pressure) is less than configured low suction control levels, Configura-
3). The circuit SST value must be less than SST.1 (for 5 min-
utes), SST.2 (for 4 minutes), or SST.3 (for 3 minutes when us-
ing the economizer and 1.5 minutes when not using the economizer) for the alert to occur. When the outdoor temperature is
less than 40°F, the above values are reduced 1°F for every 2°F
the OAT is below 40°F. An alert will also occur if the circuit
SST value is less than SST.3 –5°F for 20 seconds and the out-
door temperature is above 40°F. All the above timers will reset
if the suction temperature rises above SST.O for 1 minute.
These alerts cause a strike for the respective circuit. If the OAT
is less than 10°F, the circuit will shut down without a strike.
These alerts will activate when the coil becomes frosted. However, during the 15-minute reset period, the coils will thaw and
strike should clear at restart if there is nothing else wrong with
the circuit. The alert resets automatically. The cause of the alert
is usually low refrigerant charge, dirty filters, evaporator fan
operating backwards, loose or broken belt, plugged filter drier,
faulty transducer, excessively cold return air, or stuck open
economizer when the ambient temperature is low.
Alert Codes T143 and T144 — Circuit Failure to Pressurize
Alert codes T143 and T144 are for circuits A and B respectively. These alerts have “Service Test” text that will be displayed
if the alert occurred during service test. These alerts occur
when the compressor turns on and the suction pressure does
not drop at least 10 PSIG in the first 20 seconds. If the OAT is
less than 40°F (4.4°C) the suction only has to drop 5 PSIG.
This alert causes a strike for the circuit. The alert resets automatically. The cause of the alert is usually compressor wiring
causing reverse rotation or a faulty compressor.
Alarm Code T153 — Real Time Clock Hardware Failure
The alert occurs when the RTC clock chip on the MBB is not responding. Time and date functions will not operate, such as local
occupancy schedules. The unit will default to 24/7 unoccupied
mode. Recovery is automatic but MBB board replacement may
43
be necessary. Cycling power to the control and reconfiguring the
time and date should be tried before board replacement.
Alarm Code A154 — Serial EEPROM Hardware Failure
The unit will completely shut down. The serial EEPROM chip
on the MBB which stores the unit’s configuration is not responding. Recovery is automatic, but MBB board replacement
may be necessary. Cycling the power to the control should be
tried before board replacement.
Alarm Code T155 — Serial EEPROM Storage Failure Error
Configuration data in the serial EEPROM chip can not be verified. The unit will run to last know good values or defaults, and
therefore operating errors may occur. Recovery is automatic
but MBB board replacement may be necessary. Cycling power
to the control and reconfiguring the control points should be
tried before board replacement.
Alarm Code A156 — Critical Serial EEPROM Storage Fail
Error
The unit will completely shut down. Critical configuration data
in the serial EEPROM chip can not be verified. Recovery is automatic but MBB board replacement may be necessary. Cycling power to the control and reconfiguring the critical control
points should be tried before board replacement. Check the
configurations for the following critical points:
The unit will completely shut down. The analog to digital conversion chip on the MBB has failed. Recovery is automatic but
MBB board replacement may be necessary. Cycling power to
the control should be tried before board replacement.
Alarm Codes A163 and A164 — Circuit Down due to Failure
Alarm codes A163 and A164 are for circuits A and B respectively. These alarms have “Service Test” text that will be displayed if the alarm occurred during service test. These alarms
occur when a circuit has 3 strikes. Use the scrolling marquee
display to reset the alarm. Investigate the alarm that caused the
strikes to occur.
Alert Code T173 — Loss of Communication with the Energy
Management Module
This alert occurs when the MBB cannot communicate with the
EMM. These units do not currently support any operation with
the EMM. This alert is caused by an internal force to look for
the EMM board. When this happens, reload software on the
MBB and do not restore configurations, the factory configurations must be used at first. Replace the MBB if alert continues.
Alert Code T175 — Loss of communication with VFD
This alert occurs when the Indoor Fan Type (Configuration
I.FANFTYP) is set to 1 and the MBB cannot communicate
with the VFD. The control will shutdown the unit and prevent
normal operation. This alert will automatically reset when
communication is established again. This alert is usually
caused by a wiring problem or a incorrect configuration in the
VFD or the MBB.
Alert Code T179 — Loss of Communication with the Economizer Control Board
This alert occurs when the MBB cannot communicate with the
ECB. Economizer operation will be disabled. This is usually
caused by a wiring problem. If a relative humidity sensor is installed and configured but there is not an ECB installed on the
unit, this alert will be generated (the ECB is required for RH
sensor operation). Investigate using the Low Voltage Schematic, check that the ECB address is correct, and verify the resistance between pins on the LEN connections.
COOLN.CIR (Number of Circuits)
HMZRREHT (Humidi-MiZer Equipped)
Alert Code T180 — Loss of Communication with the Economizer Actuator
This alert occurs when the ECB cannot communicate with the
Belimo Actuator. If the analog signal is connected properly, the
economizer can still be controlled through it. This is usually
caused by a wiring problem, actuator failure, or the wrong actuator. Investigate using the Low Voltage Schematic. Make
sure the actuator is a MFT communication actuator and verify
the feedback signal from the actuator is correct.
Alert Code T181 — Loss of communication with Outside Air
Unit
This alert occurs when the Outdoor Air Unit Type (Configuration
OAUOA.TY) is not set to 0 and the OAU Operating
Mode (Run Status
cated in the past 3 minutes. The control will reset all OAU data. This alert will automatically reset when communication is
established again. This alert is usually caused by a wiring problem or a problem with the OAU communication.
Alarm Code A200 — Linkage Timeout - Comm Failure
This alarm occurs when the MBB fails to communicate with a
Linkage device. This only occurs when the MBB has previously communicated with a Linkage device since last power cycle.
If a back up sensor was not installed the T074 alert will occur
shortly after this one. Reset power to the unit and verify Linkage is communicating.
Alarm Code A404 — Fire Shutdown
This alarm occurs when the shutdown input is either open or
closed depending upon its configuration. This alarm is usually
caused by an auxiliary device that is trying to shut down the
unit, e.g., smoke detector. The configuration for this switch input can be found at variable Configuration
Verify that the configuration is set correct, verify the wiring
and auxiliary device. This alarm resets automatically.
Alert Code T408 — Dirty Air Filter
This alert occurs when the Filter Status switch senses a
plugged filter for 120 continuous seconds after the indoor fan
has been running for 10 seconds. Because the Dirty Air Filter
switch can be configured normally opened or closed, the
switch might be open or closed. The configuration for this
switch input can be found at variable Configura-
tion
UNITFL.SW. Verify that the configuration is set cor-
rect, verify the wiring and filter status switch. The hose should
be connected to the low side of the switch. This alert resets automatically.
Alert Code T409
There are 2 different texts for this alert code. Pressing enter and
esc on the marquee or navigator to expand the T409 alert will
show you one of the below alerts. Make sure the expanded text
is read correctly before troubleshooting.
•Fan Status Switch On, Fan Contactor Off
This alarm occurs when the fan status switch has sensed that
the indoor fan has been on for 10 seconds and the indoor fan
feedback has determined that the indoor fan should be off. Because the Fan Status switch can be configured normally opened
or closed, the switch might be open or closed. The configuration for this switch input can be found at Configura-
tion
UNITFN.SW. Verify that the configuration is set cor-
rectly. Verify the wiring and fan status switch. The hose should
be connected to the high side of the switch. If the IDF is configured to shut down the unit when this alarm occurs (Configu-
ration
I.FANIDF.F = YES), then this alarm can only be
reset manually and the unit is shut down. If the IDF is not configured to shut the unit down when this alarm occurs (IDF.F =NO), then this alarm resets automatically and no specific control action is taken.
•Fan Status Switch Off, Fan Contactor On
OAUOA.OP) has not been communi-
UNITFS.SW.
44
This alert occurs when the fan status switch has sensed that the indoor fan has been off for 10 seconds and the indoor fan feedback
has determined that the indoor fan should be on. Because the Fan
Status switch can be configured normally opened or closed, the
switch might be open or closed. The configuration for this switch
input can be found at Configuration
that the configuration is set correctly. Verify the wiring and fan status switch. The hose should be connected to the high side of the
switch. If the IDF is configured to shut down the unit down when
this alert occurs (Configuration
this alarm can only be reset manually and the unit is shut down. If
the IDF is not configured to shut the unit down when this alert occurs (IDF.F = NO), then this alert resets automatically and no spe-
cific control action is taken.
Alert Code T410
•R-W1 Jumper Not Installed in Space Temp Mode
This alert occurs when the control mode is Space Temperature
mode via Auto Select or Space Temp Select, yet there is no
power to W1. Verify that space temperature mode is the desired mode or add jumper between R and W1 (on TB). This
alert resets automatically.
•R-W1 Jumper Must be Installed to Run Heat in Service
Test
This alert occurs when a request for a heat output has occurred
yet the W1 input is not high. A jumper must be installed between R and W1 (on TB) when trying to test heat in Service
Test. The alert will clear when Service Test is exited or if another Service Test mode is selected. Remove jumper when
done using Service Test if the unit is operating with a thermostat. The jumper should only be left in place if the unit is operating with a space temperature probe.
This alert occurs in Thermostat mode when Y2 is energized
and Y1 is not. Verify thermostat and thermostat wiring. When
Y2 turns On, the software will behave as if Y1 and Y2 are both
On. When Y2 turns Off, the software will behave as if Y1 and
Y2 are both Off. This alert resets automatically when Y1 is
turned On.
This alert occurs in Thermostat mode when W2 is energized
and W1 is not. Verify thermostat and thermostat wiring. When
W2 turns On, the software will behave as if W1 and W2 are
both On. When W2 turns Off, the software will behave as if
W1 and W2 are both Off. This alert resets automatically when
W1 is turned On.
Alert Code T413 — Thermostat Y and W Inputs Activated
Simultaneously
This alert occurs in Thermostat mode when Y1 or Y2 is energized simultaneously with W1 or W2. Verify thermostat and
thermostat wiring. The software will enter either the cooling or
heating mode depending upon which input turned on first. This
alert resets automatically when Y1 and Y2 are not on simultaneously with W1 and W2.
Alert Code T414
There are 10 different alerts under this one alert code. Pressing
enter and esc on the marquee or navigator to expand the T414
alert will show you one of the below alerts. All these alerts are
generated by the Belimo actuator and reported to the ECB.
These alerts can only occur if the ECB is controlling the actuator digitally through MFT.
•Economizer Damper Actuator Out of Calibration
This alert occurs when the economizer actuator reports a control angle (Operating Modes
minimum control angle (Configuration
Initiate economizer calibration (Service Test
UNITFN.SW. Verify
I.FANIDF.F = YES), then
ECONC.ANG) less than the
ECONM.ANG).
INDPE.CAL) using the Service Test menu. The economizer
calibration procedure will try to find new maximum open and
closed positions. If the alert does not clear automatically after
the calibration procedure is complete, investigate what is limiting economizer rotation. After that step, run another calibration, but first power off unit (spring return the damper), loosen
the actuator clamp, and while pushing the damper closed, tighten the clamp. This alert resets automatically.
This alert occurs when the actuator load is too high. Investigate to determine what is increasing damper load, and verify
that the actuator is the correct size for the unit. This alert resets automatically.
•Economizer Damper Actuator Hunting Excessively
This alert occurs when the commanded damper position is
changing too rapidly. The stop jog ratio must be less than 21%
to clear this alert. Leave the actuator powered with no signal
for a few hours to allow the ratio to decrease (may have to wait
longer than a few hours). If the alert continues, determine if the
ECB or actuator is bad. This alert resets automatically.
•Economizer Damper Stuck or Jammed
This alarm occurs when the actuator is no longer moving and
the actual position is greater than or less than 3% of the commanded position for 20 seconds. Investigate what is stopping
the rotation of the actuator and fix. This alert resets automatically.
•Economizer Damper Actuator Mechanical Failure
This alert occurs when the actuator senses a catastrophic failure. Investigate actuator and replace if necessary. This alert resets automatically.
•Economizer Damper Actuator Direction Switch Wrong
Position
This alert occurs when the economizer damper direction switch
is in the wrong position. The direction switch should be in the
clockwise position and the actuator should be mounted so that
the CW face of the actuator is accessible. Correct if necessary.
This alert clears automatically.
•Excess Outdoor Air
In this failure mode the economizer provides an excessive level
of ventilation, usually much higher than is needed for design
minimum ventilation.
•Economizer Economizing When It Should Not
In this case, conditions are such that the economizer should be
at minimum ventilation position but for some reason it is open
beyond the correct position.
•Economizer Not Economizing When It Should
In this case, the economizer should be enabled, but for some
reason it is not providing free cooling.
•Damper Not Modulating
This issue represents a stuck, disconnected, or otherwise inoperable damper that does not modulate open and close.
Alert Code T415 — IAQ Input Out of Range
This alert occurs when the IAQ input (on ECB) is less than 3.5
mA and the sensor is configured as installed. IAQ operation
will be disabled. Check sensor and wiring. This alert clears automatically.
Alert Code T416 — OAQ Input Out of Range
This alert occurs when the OAQ input (on ECB) is less than
3.5 mA and the sensor is configured as installed. OAQ operation will be disabled. Check sensor and wiring. This alert clears
automatically.
Alert Code T418
There are 4 different alerts under this one alert code. Pressing
enter and esc on the marquee or navigator to expand the T418
45
alert will show you one of the below alerts. All these alerts are
generated by the OAU device and reported to the MBB. These
alerts can only occur if the Outdoor Air Unit Type (Configura-
tion
OAUOA.TY) is not set to 0. Control action is only tak-
en on the OAU side and these alerts will reset automatically
when the OAU clears them. Refer to the EnergyX Supplemental
Installation Instructions for more information on these alarms.
•OAU Motor Failure
This alert occurs when the OAU Motor Failure Alarm (Operat-
ing Modes
OAUALM.1) is on. This is usually due to mo-
tor status reporting a failure on the OAU.
•OAU Dirty Filter
This alert occurs when the OAU Dirty Filter Alarm (Operating
Modes
OAUALM.2) is on. This is usually due to filter sta-
tus reporting a dirty filter on the OAU.
•OAU Low CFM
This alert occurs when the OAU Low CFM Alarm (Operating
Modes
OAUALM.3) is on. This is usually due to OAU not
capable of achieving proper CFM. If unit is equipped with a
VFD on the indoor fan, the configuration OAU Fan Boost En-
Table 14 — ComfortLink Alarm Codes
able is set to yes (Configuration
OAUEFBE = Yes), and
this alarm is active for 10 minutes, the fan will be commanded
to the next highest configured fan speed. If this alarm is still
active after another 10 minutes, the fan will again change to the
next highest configured fan speed, and so on every 10 minutes
until the maximum speed is commanded. The fan will stay at
this override commanded speed until this alarm clears and a
different function changes the commanded speed.
•OAU General Alarm
This alert occurs when the OAU Alarm (Operating Modes
OAUALM.4) is on. Refer to the specific OAU documen-
tation for details.
Alert Code A420 — Supply VFD Fault
This alarm occurs when the VFD has faulted and communicates it to the Main Base Board (MBB). The last VFD fault
number can be viewed as VFD1 Last Full code (Run Sta-
tus
S.VFDLFC). Refer to VFD major component section
for details on its alarms and faults. The alarm will shut down
the unit if the fan ramps down to 0%. This alarm will automatically reset or can be reset through the display.
ALARM
OR
ALERT
NUMBER
Compressor A1 Safety Trip
Service Test — Compressor A1
T051
T055
T064
T065
T066
T067
T073
T074
T075
T076 Return Air Thermistor Failure
T077
T092
T093
T102
T103
T110
Safety Trip
Compressor A1 Detected After
Turnoff
Service Test — Compressor A1
Detected After Turnoff
Compressor B1 Safety Trip
Service Test — Compressor B1
Safety Trip
Compressor B1 Detect After Turnoff Turn off all compressorsAutomatic
Service Test — Compressor B1
Detected After Turnoff
Circuit A Saturated Condensing
Temp Thermistor Failure
Circuit B Saturated Condensing
Temp Thermistor Failure
Circuit A Saturated Suction
Temperature Thermistor Failure
Circuit B Saturated Suction
Temperature Thermistor Failure
Outdoor Air Temperature
Thermistor Failure
Space Temperature Thermistor
Failure
Supply Air Temperature Thermistor
Failure
Space Relative Humidity Sensor
Failure
Circuit A Suction Pressure
Transducer Failure
Circuit B Suction Pressure
Transducer Failure
Compressor A1 Current Sensor
Failure
Compressor A1 Current Sensor
Failure
Circuit A Loss of Charge
Service Test — Circuit A Loss of
Charge
DESCRIPTION
ACTION TAKEN BY
CONTROL
Add Strike for Circuit A Automatic
Turn off all compressors Automatic Welded contactor
Add Strike for Circuit B Automatic
Limited Diagnostic Automatic
Limited Diagnostic Automatic
No Circuit A Cooling Automatic Circuit A Suction transducer internally forced inactive
No Circuit B Cooling Automatic Circuit B Suction transducer internally forced inactive
No cooling with economizer Automatic
If U.CTL = 3, then no heating
or cooling
No cooling with economizer
and No adaptive compressor
staging
If RAT.S = Yes, then no
differential Dry Bulb control
If RH.S = Yes, then no indoor
humidity control
Lockout Circuit A Manual
Lockout Circuit B Manual
If CS.A1 = Enable, then no
T051 current alarm
If CS.B1 = Enable, then no
T055 current alarm
Lockout Circuit A Manual Low refrigerant or faulty suction pressure transducer
Faulty, shorted, or open thermistor caused by wiring
error or loose connection.
Faulty, shorted, or open thermistor caused by wiring
error or loose connection.
Faulty, shorted, or open thermistor caused by wiring
error or loose connection.
Faulty, shorted, or open thermistor caused by wiring
error or loose connection.
Faulty, shorted, or open thermistor caused by wiring
error or loose connection.
Faulty, shorted, or open thermistor caused by wiring
error or loose connection.
Faulty, shorted, or open sensor caused by wiring error
or loose connection.
Faulty transducer, faulty 5-V power supply, or loose
connection
Faulty transducer, faulty 5-V power supply, or loose
connection
Faulty transducer, faulty 5-V power supply, or loose
connection
Faulty transducer, faulty 5-V power supply, or loose
connection
46
Table 14 — ComfortLink Alarm Codes (cont)
ALARM
OR
ALERT
NUMBER
T111
T126
T127
T133
T134
T143
T144
T153 Real Timeclock Hardware Failure
A154 Serial EEPROM Hardware Failure Unit Shutdown Automatic Software failure or MBB failure
T155
A156
A157 A/D Hardware Failure Unit Shutdown Automatic Software failure or MBB failure
A163
A164
T173
T175 Loss of communication with VFD Unit Shutdown Automatic
T179
T180
T181
A200
A404 Fire Shutdown Unit Shutdown Automatic Smoke detected by smoke detector
T408 Dirty Air Filter Alert Generated Automatic Dirty Filter
T409
T410
T411
Circuit B Loss of Charge
Service Test — Circuit B Loss of
Charge
Circuit A High Discharge Pressure
Service Test — Circuit A High
Discharge Pressure
Circuit B High Discharge Pressure
Service Test — Circuit B High
Discharge Pressure
Circuit A Low Refrigerant Pressure
Service Test — Circuit A Low
Refrigerant Pressure
Circuit B Low Refrigerant Pressure
Service Test — Circuit B Low
Refrigerant Pressure
Circuit A Failure To Pressurize
Service Test — Circuit A Failure to
Pressurize
Circuit B Failure To Pressurize
Service Test — Circuit B Failure to
Pressurize
Serial EEPROM Storage Failure
Error
Critical Serial EEPROM Storage Fail
Error
Circuit A Down Due to Failure
Service Test — Circuit A Down Due
to Failure
Circuit B Down Due to Failure
Service Test — Circuit B Down Due
to Failure
Loss of communication with the
Energy Management Module
Loss of communication with the
Economizer Control Board
Loss of communication with the
Economizer Actuator
Loss of communication with Outside
Air Unit
Linkage Timeout Error — Comm
Failure
Fan Status Switch ON, fan
commanded off
Fan Status Switch OFF, fan
commanded on
R-W1 Jumper Not Installed in Space
Temp Mode
R-W1 Jumper Must Be Installed to
Run Heat In Service Test
Thermostat Y2 Input Activated
without Y1 Activated
DESCRIPTION
ACTION TAKEN BY
CONTROL
Lockout Circuit B Manual Low refrigerant or faulty suction pressure transducer
Shutdown Circuit A Automatic
Shutdown Circuit B Automatic
Add Strike for Circuit A Automatic
Add Strike for Circuit B Automatic
Add Strike for Circuit A Automatic Wiring causing reverse rotation or faulty compressor
Add Strike for Circuit B Automatic Wiring causing reverse rotation or faulty compressor
No time and date schedule
operation
Unit operation errors Automatic Software failure or MBB failure
Unit Shutdown Automatic Software failure or MBB failure
Lockout Circuit A Manual
Lockout Circuit B Manual
No action Automatic MBB Software failure, reload software or replace board
No economizer operation Automatic
No economizer operation Automatic Communication wiring problem with actuator.
Reset OAU data Automatic Wiring Problem or OAU communication failure
No Linkage Operation fall back
to local SPT
If IDF.F = Yes, then Unit
Shutdown
If IDF.F = Yes, then Unit
Shutdown
Unable to run heat Automatic Missing jumper wire
Unable to Test Heat Outputs
Run unit as if Y2 and Y1 are
On
RESET
METHOD
An overcharged system, high outdoor ambient
temperature coupled with dirty outdoor coil, plugged
filter drier, or a faulty high-pressure switch.
An overcharged system, high outdoor ambient
temperature coupled with dirty outdoor coil, plugged
filter drier, or a faulty high-pressure switch.
Low refrigerant charge, dirty filters, evaporator fan
turning backwards, loose or broken fan belt, plugged
filter drier, faulty transducer, excessively cold return air,
or stuck open economizer when the ambient
temperature is low.
Low refrigerant charge, dirty filters, evaporator fan
turning backwards, loose or broken fan belt, plugged
filter drier, faulty transducer, excessively cold return air,
or stuck open economizer when the ambient
temperature is low.
Automatic
Automatic
If IDF.F =
YES, then
Manual,
otherwise
automatic
If IDF.F =
YES, then
Manual,
otherwise
automatic
Automatic Missing jumper wire
Automatic Bad Thermostat or Thermostat Wiring
No time/date configured, software failure, or MBB
failure
Circuit has 3 strikes or has been locked out by another
alarm
Circuit has 3 strikes or has been locked out by another
alarm
Communication connection bad or miswired,
misconfigured VFD.
Communication wiring problem with ECB or faulty MBB
or ECB
Received a table write from Linkage before, now not
receiving any linkage commands
Bad Fan Status Switch. Configuration incorrect.
Tripped Circuit Breaker. Broken belt. Bad indoor fan
motor. Configuration incorrect. Bad fan status switch.
PROBABLE CAUSE
47
Table 14 — ComfortLink Alarm Codes (cont)
ALARM
OR
ALERT
NUMBER
T412
T413
T414
T415 IAQ Input Out of Range No IAQ Operations Automatic
T416 OAQ Input Out of Range No OAQ Operations Automatic
Excess Outdoor Air Alert Generated Automatic
Economizer Economizing When It
Should Not
Economizer not Economizing When
it Should
Damper Not Modulating Alert Generated Automatic
OAU Motor Failure Alert generated Automatic Check OAU motors for failure
OAU Dirty Filter Alert generated Automatic Check/change OAU filters
OAU Low CFM Alert generated Automatic Check OAU air flow
OAU General Alarm Alert generated Automatic Check OAU
DESCRIPTION
ACTION TAKEN BY
CONTROL
Run unit as if W2 and W1 are
On
Run unit in mode activated
first
Alert Generated Automatic
Alert Generated Automatic Actuator load too high. Check damper load.
Alert Generated Automatic Damper position changing too quickly.
Alert Generated Automatic
Alert Generated Automatic Check actuator and replace if necessary.
Alert Generated Automatic Actuator direction control switch (CCW, CW) wrong.
Alert Generated Automatic
Alert Generated Automatic
RESET
METHOD
Automatic Bad Thermostat or Thermostat Wiring
Automatic Bad Thermostat or Thermostat Wiring
Calibrate economizer (E.CAL). If problem still exist then
determine what is limiting economizer rotation.
No economizer motion. Check damper blades, gears,
and actuator.
Bad sensor, bad wiring, or sensor configured
incorrectly.
Bad sensor, bad wiring, or sensor configured
incorrectly.
PROBABLE CAUSE
LEGEND
ECB— Economizer Control Board
IGC— Integrated Gas Controller
IAQ— Indoor Air Quality
MBB— Main Base Board
OAQ— Outdoor Air Quality
OAT— Outdoor-Air Thermistor
OAU— Outdoor Air Unit
VFD— Variable Frequency Drive
48
Control Module Communication
RED LED
Proper operation of the MBB and ECB control boards can be
visually checked by looking at the red status LEDs. When operating correctly, the red status LEDs should blink in unison at
a rate of once every 2 seconds. If the red LED on the ECB is
not blinking, check the DIP switch positions on the board. If
the red LEDs are not blinking in unison, verify that correct
power is being supplied to all modules. A blinking red LED at
the rate of once per second means that software is not loaded
on the board. Also, be sure that the board is supplied with the
current software. If necessary, reload current software. A board
LED that is lit continuously should be replaced.
GREEN LED
The MBB and ECB each have one green LED. The Local
Equipment Network (LEN) LED should always be blinking
whenever power is on. If LEN LED is not blinking, check LEN
connections for potential communication errors (MBB J3, J4,
and J5). Communication between modules is accomplished by
a 3-wire sensor bus. These 3 wires run in parallel from module
to module. The J4 connector on the MBB also provides both
Table 15 — LEN and CCN Communication Resistances
power and communication directly to the scrolling marquee
display. The J5 connector on the MBB provides a LEN interface at the field connection terminal (TB).
YELLOW LED
The MBB has one yellow LED which is used to indicate CCN
communication activity. The Carrier Comfort Network
®
(CCN)
LED will blink during times of network communication.
Communication Failures
If the scrolling marquee or Navigator display Communication
Failure or the green or yellow LEDs do not flash on the boards
then the problem could be the communication chip on one of
the control boards (MBB or ECB). Disconnect all the LEN and
CCN plugs from the board and use an ohm meter to measure
the resistance on the communication pins of the boards to determine if the board is bad. If the reading is less than half the
value indicated in Table 15, then the board needs to be replaced.
NOTE: The resistive values should be read when the board is
powered off and the unit is locked out.
Device
MBB
ECB
Board Serial
Number
Prior to 4702N
Starting 4702N
Prior to 0803N
Starting 0803N
(LEN) Resistance between Pins/Connector (CCN) Resistance between Pins/Connector
Pins 1 to 3 Pins 1 to 2 Pins 2 to 3 Pins 5 to 7 Pins 5 to 6 Pins 6 to 7
15K
J3, J4, & J5
18.9K
J3, J4, & J5
5.9K
J2
18.9K
J2
7.5K
J3, J4, & J5
9.9K
J3, J4, & J5
5.2K
J2
9.9K
J2
7.5K
J3, J4, & J5
9.9K
J3, J4, & J5
5K
J2
9.9K
J2
15K
J5
18.9K
J5
———
———
7.5K
J5
9.9K
J5
7.5K
J5
9.9K
J5
49
Cooling Troubleshooting
Use the scrolling marquee display or a CCN device to view the
cooling status display and the cooling diagnostic display (see
Appendix A) for information on the cooling operation. Check
the current alarms and alarm history for any cooling alarm
codes and correct any causes. (See Table 14.) Verify any
unique control configurations per installed site requirements or
accessories.
If alarms conditions are corrected and cleared, operation of the
compressors and fans may be verified by using the Service Test
mode. (See Table 6.) See Table 16 for general cooling service
analysis.
Table 16 — Cooling Service Analysis
PROBLEM CAUSE REMEDY
Compressor and Fan Will Not Start.Power failure. Call power company.
Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker.
Disconnect off. Power disconnect.
Compressor time guard to prevent short cycling. Check using ComfortLink scrolling marquee.
Thermostat or occupancy schedule set point not
calling for Cooling.
Outdoor temperature too low. Check Compressor Lockout Temperature using
Active alarm. Check active alarms using ComfortLink scrolling
Compressor Cycles (other than normally
satisfying thermostat).
Compressor Operates Continuously.Unit undersized for load. Decrease load or increase size of unit.
Condenser Fans Not Operating. No Power to contactors. Fuse blown or plug at motor loose.
Excessive Suction Pressure. High heat load. Check for sources and eliminate
Suction Pressure Too Low. Dirty air filters. Replace air filters.
Compressor not running but ComfortLink
Status show it is on.
Insufficient line voltage. Determine cause and correct.
Active alarm. Check active alarms using ComfortLink scrolling
Thermostat or occupancy schedule set point too
low.
Faulty TXV. 1. Check TXV bulb mounting and secure tightly
Insufficient evaporator airflow. Check belt tension. Check for other restrictions.
Temperature too low in conditioned area (low
return-air temperature).
Condensate overflow switch, High pressure, or
Freeze protection thermostat has tripped.
Check using ComfortLink scrolling marquee.
ComfortLink scrolling marquee.
marquee.
marquee.
Reset thermostat or schedule set point.
and recharge.
to suction line and insulate.
2. Replace TXV (and filter drier) if stuck open or
closed.
to suction line and insulate.
2. Replace TXV (and filter drier) if stuck open or
closed.
and recharge.
to suction line and insulate.
2. Replace TXV (and filter drier) if stuck open or
closed.
Reset thermostat or occupancy schedule.
Check Alarms. (T051 or T055), check switches
and conditions that can cause their trips.
LEGEND
TXV— Thermostatic Expansion Valve
50
Humidi-MiZer™ Troubleshooting
Use the unit scrolling marquee display or a CCN device to
view the cooling status display and the cooling diagnostic display (see Appendix A) for information on the cooling operation and the related Humidi-MiZer operation. Check the current alarms and alarm history for any cooling alarm codes and
correct any causes. (See Table 14.) Verify any unique control
If alarm conditions are corrected and cleared, operation of the
compressors, fans, and Humidi-MiZer valves may be verified
by using the Service Test mode (see Table 6.) In addition to
general cooling service analysis (see Table 16), see Table 17
for general Humidi-MiZer service analysis.
NOTE: Wiring, operation, and charge are different on a HumidiMiZer unit compared to a standard unit.
configurations per installed site requirements or accessories.
Table 17 — Humidi-MiZer Service Analysis
PROBLEM CAUSE REMEDY
Subcooling Reheat Mode Will Not
Activate.
Hot Gas Reheat Mode Will Not
Activate.
No Dehumidification Demand. Relative humidity setpoint is too low —
CRC Relay Operation.No 24V signal to input terminals.Check using Cool
RLV, CLV or LDV Valve OperationNo 24V signal to input terminals.Check using Cool
RDV Valve Operation. (NOTE: Normally
Closed When De-energized)
Low Latent Capacity in Subcooling or
Hot Gas Reheat Modes.
Low Sensible Capacity in Normal Cool
or Subcooling Reheat Modes.
Low Suction Pressure and High
Superheat During Normal Cool Mode.
General cooling mode problem. See Cooling Service Analysis (Table 16).
No dehumidification demand. See No Dehumidification Demand, below.
CRC relay operation. See CRC Relay Operation, below.
Circuit RLV, CLV or LDV valve problem. See CLV, RLV or LDV Valve Operation, below.
General cooling mode problem. See Cooling Service Analysis (Table 16).
No dehumidification demand. See No Dehumidification Demand, below.
CRC relay operation. See CRC Relay Operation, below.
Circuit RLV, CLV or LDV valve problem. See CLV, RLV or LDV Valve Operation, below.
Circuit RDV valve is not open. See RDV Valve Operation, below.
Outdoor temperature too low.Check Reheat2 Circuit Limit Temperatures
Humidistat
Relative humidity setpoint is too low —
RH sensor.
Software configuration error for accessory
humidistat.
Software configuration error for accessory
humidity sensor.
No humidity signal. Check wiring. Check humidistat or humidity sensor.
No power to output terminals. Check wiring.
Relay outputs do not change state. Replace faulty relay.
Solenoid coil burnout.Check continuous over-voltage is less than 10%.
Stuck valve. Replace valve. Replace filter drier.
No 24V signal to input terminals.Check using Cool
Solenoid coil burnout.Check continuous over-voltage is less than 10%.
Stuck valve. Replace valve. Replace filter drier.
CLV valve open or leaking. See CLV Valve Operation, above.
RDV valve open or leaking. See RDV Valve Operation, above.
General cooling mode problem. See Cooling Service Analysis (Table 16).
RDV valve open or leaking. See RDV Valve Operation, above.
(ConfigurationComfortLink scrolling marquee.
Check/reduce setting on accessory humidistat.
Check Space RH Setpoints (Setpoints
and occupancy using ComfortLink scrolling marquee.
Check Space Humidity Switch
(Configuration
marquee.
Check RH Sensor on OAQ Input
(Configuration
marquee.
TestHMZRCRC) using ComfortLink scrolling marquee.
Check MBB relay output.
Check wiring.
Check transformer and circuit breaker.
Test
HMZRCRC) using ComfortLink scrolling marquee.
Check CRC Relay Operation.
Check Wiring.
Check transformer and circuit beaker or fuses.
Check under-voltage is less than 15%.
Check for missing coil assembly parts.
Check for damaged valve enclosing tube.
TestHMZRRHV.A or RHV.B) using ComfortLink scrolling
marquee.
Check MBB relay output.
Check wiring.
Check transformer and circuit breaker or fuses.
Check under-voltage is less than 15%.
Check for missing coil assembly parts.
Check for damaged valve enclosing tube.
HMZRRA.LO and RB.LO) using
RH.SP and RH.UN)
UNITRH.SW) using ComfortLink’scrolling
UNITRH.S) using ComfortLink scrolling
Reheat1 Valve Test (Service
Reheat1 Valve Test (Service
Reheat1 Valve Test (Service
51
Table 17 — Humidi-MiZer Service Analysis (cont)
PROBLEM CAUSE REMEDY
Low Suction Pressure and High
Discharge Pressure.
RDV Valve Cycling On/Off. Hot Gas Reheat mode low suction
General cooling mode problem. See Cooling Service Analysis (Table 16).
Both RLV and CLV valves closed. See RLV and CLV Valve Operation, above.
pressure limit.
Normal operation. Motormaster outdoor
fan control requires operation of circuit A.
Normal Operation During Mixed Circuit Subcooling and Hot
Gas Reheat Modes at Lower Outdoor Temperatures.
None
Economizer Troubleshooting
Use the unit scrolling marquee display or a CCN device to
view the economizer status display and the economizer diagnostic display (see Appendix A) for information on the economizer operation. Check the current alarms and alarm history
for any economizer alarm codes and correct any causes. (See
Table 14.) Verify any unique control configurations per installed site requirements or accessories. If alarms conditions
are corrected and cleared, operation of the economizer may be
verified by using the Service Test mode (see Service Test section and Table 6). The following steps specify how to test the
economizer using the scrolling marquee display. See Table 18
for general economizer service analysis.
1.Enter the Service Test main menu on the display.
2.Enter TEST and turn ON test mode. A password may be
needed in order to turn ON the Service Test. The default
password is 1111.
3.Return to the main level of Service Test.
4.Enter the INDP submenu and enter an initial value for
ECON. This will drive the economizer damper to the specified position. Continue to adjust the ECON value to make
sure the economizer opens and closes.
5.Because of a mechanical problem with the economizer, the
actuator might acquire a new degree of rotation which is
less than M.ANG. If this occurs, a “T414 Economizer
Damper Actuator Out of Calibration” alert will be generated. This alert can only occur if the economizer is using
digital communications (Configuration
= 1 or 2). The economizer calibration procedure (Service
Te st
IND.PE.CAL) will reconfigure the actuator to
the new fully closed and fully open positions. To implement the calibration procedure, change E.CAL from OFF
to ON. E.CAL will remain ON as long as the calibration
procedure is being implemented (as long as 5 minutes).
During the calibration procedure the actuator will close
fully and then open fully. After the calibration is complete,
the degree of rotation should be greater than M.ANG,
causing the T414 alert to clear. If the T414 alert does not
clear, check the economizer damper for other mechanical
problems.
ECONE.CTL
6.Return to Service Test
TEST and turn OFF test mode.
This will cause the unit to return to normal operation.
Title 24 FDD Status Points
The control shall utilize the following points to determine
whether a damper is mechanically disconnected:
ECONO — Economizer Installed — Flag indicating whether
an economizer is installed
RAT — Return Air Temperature
SAT — Supply Air Temperature
OA_TEMP — Outdoor Air Temperature
OCCUPIED — Currently Occupied — Flag indicating wheth-
er currently in occupied mode
IDF_MODE — Indoor Fan Mode — Current indoor (supply)
fan mode.
IDFSTATE — Indoor Fan State
FANSPEED — Commanded Fan Speed — Commanded fan
speed
ECONOCMD — Econo Commanded Position — Economizer
position as commanded by the ComfortLink control
ECONOPOS — Econo Actual Position — Economizer posi-
tion as reported by the actuator
ECONCOOL — OK To Use Economizer? — Flag indicating
whether the economizer is able to help with cooling without
taking into account whether the supply fan is on.
OKTSTMDA — OK Test Mech. D/C Act — Flag indicating
whether the control will attempt to test for a mechanically disconnected actuator.
T24PRSAT — Title 24 Previous SAT — SAT sample taken at
T24ECSMP
T24ECSMP — Title 24 Econ Samp Pos — Economizer position when T24PRSAT taken
T24SATCT — Title 24 SAT Check Time — Time when next
SAT sample will be taken or test for mechanically disconnected actuator will be performed.
ELAPSECS — Elapsed Seconds — Current ComfortLink control elapsed seconds
52
Table 18 — Economizer Service Analysis
PROBLEM POSSIBLE CAUSE REMEDY
Damper Does Not Move. Indoor Fan is off.Check for proper thermostat connection.
Unit is not configured for continuous fan
operation and the thermostat is not calling for
heating or cooling.
Unit is in Unoccupied mode and there is no call
for heating or cooling.
Tripped circuit breaker.
No power to the unit.
Unit is off via CCN command.
Actuator is unplugged at motor or at economizer
board.
Unit is not configured for economizer. Configure unit for economizer per the
Outdoor-air temperature is above economizer
high temperature lockout.
Outdoor-air temperature is below economizer
low temperature lockout.
Communication loss to economizer board. Check wiring connections.
Damper is jammed. Identify the obstruction and safely remove.
Economizer Operation is Limited to Minimum
Position.
Economizer Position is Less Than Minimum
Position.
Economizer Does Not Return to Minimum
Position.
Damper Does Not Close on Power Loss.Damper is jammed or spring return is
Outdoor Damper Does Not Fully Close at 0%
or Fully Open at 100%.
Economizer is Not at Configured Minimum
Position
Minimum position is set incorrectly. Adjust minimum position setting.
Outdoor-air temperature is above economizer
high temperature lockout.
Outdoor-air temperature is below economizer
low temperature lockout.
Enthalpy or differential dry bulb are preventing
free cooling.
Outdoor-air thermistor is faulty. Replace outdoor-air thermistor.
Low suction pressure problem with a
compressor.
IAQ is controlling minimum damper position. Adjust the IAQ settings if incorrect, otherwise,
Unit is in Unoccupied mode. Adjust unit occupied schedule if incorrect,
Unit is operating under free cooling. Economizer is operating correctly.
backwards.
Economizer actuator is out of calibration or
spring return is backwards.
Unit is operating under free cooling or a force is
applied to the commanded position.
Check wiring connections.
instructions.
Adjust the high temperature lockout setting if it is
incorrect, otherwise, economizer is operating
correctly.
Adjust the low temperature lockout setting if it is
incorrect, otherwise, economizer is operating
correctly.
Adjust the high temperature lockout setting if it is
incorrect, otherwise, economizer is operating
correctly.
Adjust the low temperature lockout setting if it is
incorrect, otherwise, economizer is operating
correctly.
Check enthalpy and return air compared to
outside air temperature.
Economizer is operating correctly, identify
compressor problem.
the economizer is operating correctly.
otherwise, economizer is operating correctly.
Identify the obstruction and safely remove.
Enter Service Test mode and run the Calibrate
Economizer (E.CAL) procedure.
Economizer is operating correctly.
LEGEND
CCN— Carrier Comfort Network
IAQ— Indoor Air Quality
53
Heating Troubleshooting
Use the unit scrolling marquee display or a CCN device to
view the heating status display and the heating diagnostic display (see Appendix A) for information on the heating operation. Check the current alarms and alarm history for any heating alarm codes and correct any causes. (See Table 14.) Verify
any unique control configurations per installed site requirements or accessories. If alarms conditions are corrected and
GAS HEAT (48HC UNITS)
See Table 19 for general gas heating service analysis. See Fig. 17
for service analysis of the IGC board logic. Check the status LED
on the IGC board for any flashing alarm codes and correct any
causes. (See Table 20.)
ELECTRIC HEAT (50HC UNITS)
See Table 21 for electric heating service analysis.
cleared, operation of the heat stages and indoor fan may be verified by using the Service Test mode. (See Table 6.)
Table 19 — Gas Heating Service Analysis
PROBLEM CAUSE REMEDY
Heat Will Not Turn On. Unit is NOT configured for heat. Check heating configurations using the
Burners Will Not Ignite. Active alarm. Check active alarms using ComfortLink scrolling
No power to unit. Check power supply, fuses, wiring, and circuit
No power to IGC (Integrated Gas Control). Check fuses and plugs.
Heaters off due to time guard to prevent short
cycling.
Thermostat or occupancy schedule set point not
calling for Cooling.
No gas at main burners. Check gas line for air and purge as necessary.
Water in gas line. Drain water and install drip.
Inadequate Heating. Dirty air filters. Replace air filters.
Gas input too low. Check gas pressure at manifold. Refer to gas
Thermostat or occupancy schedule set point
only calling for W1.
Unit undersized for load. Decrease load or increase of size of unit.
Restricted airflow. Remove restriction. Check SAT compared to the
Too much outdoor air. Check economizer position and configuration.
Limit switch cycles main burners. Check rotation of blower, thermostat heat
Poor Flame Characteristics.Incomplete combustion (lack of combustion air)
Burners Will Not Turn Off. Unit is in Minimum on-time. Check using ComfortLink scrolling marquee and
results in: Aldehyde odors, CO, sooting flame, or
floating flame.
Unit running in Service Test mode. Check using ComfortLink scrolling marquee.
Main gas valve stuck. Turn off gas supply and unit power. Replace gas
ComfortLink scrolling marquee
marquee and the IGC flash codes.
breakers.
Check using ComfortLink scrolling marquee and
the IGC flash codes.
Check using ComfortLink scrolling marquee.
After purging gas line of air, allow gas to
dissipate for at least 5 minutes before attempting
to re-light unit.
valve adjustment.
Allow time for W2 to energize or adjust setpoints.
SAT heating limits.
Adjust minimum position using ComfortLink
scrolling marquee.
anticipator settings, and temperature rise of unit.
Adjust as needed.
Check all screws around flue outlets and burner
compartment. Tighten as necessary.
Cracked heat exchanger, replace.
Unit is over-fired, reduce input. Adjust gas line or
manifold pressure.
Check vent for restriction. Clean as necessary.
Check orifice to burner alignment.
the IGC flash codes.
valve.
54
1 FLASH - INDOOR FAN DELAY
MODIFIED (HEATING)
2 FLASHES - OPENING OF LIMIT
SWITCH
3 FLASHES - FLAME SENSOR
INDICATES FLAME WITH
CLOSED GAS VALVE
4 FLASHES - LIMIT SWITCH
CYCLED 4 TIMES ON SINGLE
CALL FOR HEAT
5 FLASHES - IGNITION LOCKOUT
(No ignition within 15 minutes)
6 FLASHES - INDUCED DRAFT
MOTOR FAULT
(No signal from the Hall Effect
Sensor or 60 seconds)
7 FLASHES - OPENING OF
ROLLOUT SWITCH
8 FLASHES - HARDWARE OR
SOFTWARE FAULT
9 FLASHES - SOFTWARE
LOCKOUT
FLASHING
LED is
ON
CALL FOR
24 VOLTS
BETWEEN
F1 AND C
YES
No
DEFECTIVE
IGC BOARD
1. BLOWN 5 AMP FUSE
2. DEFECTIVE 24V TRANS.
3. BROKEN WIRE
4. NO POWER TO UNIT
HEATING
‘W1’ FROM BASE CONTROL BOARD ENERGIZES ‘W’
ON IGC - 1 MINUTE LOCK-ON
COMBUSTION RELAY ON IGC IN ENERGIZED
COMBUSTION RELAY ENERGIZES INDUCED DRAFT MOTOR (IDM) THROUGH
TERMINAL ′CM′ ON IGC
IF IDM IS TURNING AT CORRECT SPEED (AT LEAST 2400 RPM), HALL
EFFECT SENSOR SENDS CORRECT SIGNAL TO TERMINAL ‘J1’ ON IGC
IF LIMIT SWITCH AND ROLLOUT
SWITCH ARE CLOSED, IGC SAFETY
LOGIC WILL INITIATE IGNITION
SEQUENCE
IGC HIGH VOLTAGE
TRANSFORMER CREATES A
10,000 VOLT SPARK FOR 5
SECONDS
IGC SAFETY LOGIC OPENS GAS
VALVE FOR 5 SECONDS
DOES IGC DETECT
.2 MICROAMPS FOR 2
SECONDS
No
Yes
AFTER 45 SECONDS (OR LESS IF THE TIMING
HAS BEEN REDUCED DUE TO LIMIT SWITCH
TRIPS) IGC WILL ENERGIZE BLOWER RELAY
DID LIMIT
SWITCH OPEN BEFORE THE 45
SECONDS (OR THE MODIFIED
TIME) HAS TIMED OUT?
Yes
No
No
IGC SAFETY LOGIC WILL SHUT
OFF GAS VALVE AND SPARK
20 SECOND PURGE OF HEAT
EXCHANGER
IS THIS THE
33RD RETRY? (OR 15
MINUTES)
Yes
IGNITION LOCKOUT
(5 FLASHES OF LED)
SUBTRACT 5 SECONDS (OR
ANOTHER 5 SECONDS) FROM
INDOOR FAN ON TIME DELAY
NORMAL HEATING OPERATION
HEATING DEMAND SATISFIED
45 SECOND BLOWER SHUTOFF DELAY
(DELAY EXTENDED BY 5 SECONDS FOR EACH LIMIT SWITCH TRIP
MAXIMUM DELAY: 3 MINUTES)
IDM STOPS, SAFETY LOGIC SHUTS OFF GAS VALVE
LEGEND
IDM – Induced-Draft Motor
IGC – Integrated Gas Unit Controller
NOTE: Thermostat Fan Switch in the
“AUTO” position.
OFF
Fig. 17 — IGC Service Analysis Logic
55
Table 20 — IGC Board LED Alarm Codes
LED FLASH
CODE
On Normal Operation — — —
Off Hardware Failure No gas heating. —
1 Flash
2 Flashes Limit Switch Fault
3 Flashes Flame Sense Fault Indoor fan and inducer On.
4 Flashes
5 Flashes Ignition Fault No gas heating.
6 Flashes Induced Draft Motor Fault
7 Flashes Rollout Switch Lockout
8 Flashes Internal Control Lockout No gas heating. Power reset.
9 Flashes
LEGEND
IGC— Integrated Gas Unit Control
LED— Light-Emitting Diode
DESCRIPTION
Indoor Fan On/Off Delay
Modified
Four Consecutive Limit
Switch Fault
Temporary Software
Lockout
ACTION TAKEN BY
CONTROL
5 seconds subtracted from
On delay. 5 seconds
added to Off delay (3 min
max).
Gas valve and igniter Off.
Indoor fan and inducer On.
No gas heating.
If heat off: no gas heating.
If heat on: gas valve Off
and inducer On.
Gas valve and igniter Off.
Indoor fan and inducer On.
No gas heating.
RESET METHOD PROBABLE CAUSE
Power reset.
Limit switch closed, or heat
call (W) Off.
Flame sense normal.
Power reset for LED reset.
Heat call (W) Off. Power
reset for LED reset.
Heat call (W) Off. Power
reset for LED reset.
Inducer sense normal, or
heat call (W) Off.
Power reset.
1 hour auto reset, or power
reset.
NOTES:
1. There is a 3-second pause between alarm code displays.
2. If more than one alarm code exists, all applicable alarm codes will
be displayed in numerical sequence.
3. Alarm codes on the IGC will be lost if power to the unit is interrupted.
Loss of power to the IGC. Check 5 amp fuse on
IGC, power to unit, 24V circuit breaker,
transformer, and wiring to the IGC.
High temperature limit switch opens during heat
exchanger warm-up period before fan-on delay
expires. High temperature limit switch opens
within 10 minutes of heat call (W) Off. See Limit
Switch Fault.
High temperature limit switch is open. Check the
operation of the indoor (evaporator) fan motor.
Ensure that the supply-air temperature rise is
within the range on the unit nameplate. Check
wiring and limit switch operation.
The IGC sensed a flame when the gas valve
should be closed. Check wiring, flame sensor,
and gas valve operation.
4 consecutive limit switch faults within a single
call for heat. See Limit Switch Fault.
Unit unsuccessfully attempted ignition for 15
minutes. Check igniter and flame sensor
electrode spacing, gaps, etc. Check flame sense
and igniter wiring. Check gas valve operation and
gas supply.
Inducer sense On when heat call Off, or inducer
sense Off when heat call On. Check wiring,
voltage, and operation of IGC motor. Check
speed sensor wiring to IGC.
Rollout switch has opened. Check gas valve
operation. Check induced-draft blower wheel is
properly secured to motor shaft.
IGC has sensed internal hardware or software
error. If fault is not cleared by resetting 24 v
power, replace the IGC.
Electrical interference is disrupting the IGC
software.
56
Table 21 — Electric Heat Service Analysis
PROBLEM CAUSE REMEDY
Active alarm.
Unit is NOT configured for heat.
No power to unit.
Unit is in minimum heat off-time, or minimum
cool-heat changeover time.
Heat Will Not Turn On.
Inadequate Heating.
Heat Will Not Turn Off.
Thermostat or occupancy schedule setpoint not
calling for heating.
Heat forced off in Service Test mode.
No 24 vac at heater contactor.
Open temperature limit switch on heater.
Dirty air filters. Replace air filters.
Thermostat or occupancy schedule setpoint only
calling for W1
Heat undersized for load. Decrease load or increase size of heater.
Restricted airflow
Too much outdoor air.
Limit switch cycles heaters. Check rotation of blower and minimum airflow.
Bad heater elements.
Unit is in minimum heat on-time. Check using ComfortLink scrolling marquee.
Thermostat or occupancy schedule setpoint still
calling for heating.
Heat forced on in Service Test mode.
Heater contactor failed.
Phase Loss Protection
The phase loss protection option will monitor the three-phase electrical system to provide phase reversal and phase loss protection.
PHASE REVERSAL PROTECTION
If the control senses an incorrect phase relationship, the relay
(K1) will be de-energized (opening its contact). If the phase relationship is correct, the relay will be energized. The control
has a self-bypass function after a pre-set time. If the control determines that the three phases stay in a correct relationship for
10 consecutive minutes, the relay will stay energized regardless of the phase sequence of three inputs as long as 24-vac
control voltage is applied. This self-bypass function will be reset if all three phases are restored in a phase loss event.
PHASE LOSS PROTECTION
If the reverse rotation board senses any one of the three phase
inputs has no AC voltage, the relay will be de-energized (opening its contact). This protection is always active as long as 24vac control voltage is applied, and is not affected by the self
by-pass function of the phase sequence monitoring function.
However, in the event of phase loss, the relay will be re-energized only if all three phases are restored and the three phases
are in the correct sequence.
A red LED is provided to indicate the function of the board.
See the following table.
Check active alarms using ComfortLink scrolling
marquee.
Check heating configurations using the
ComfortLink scrolling marquee
Check power supply, fuses, wiring, and circuit
breakers.
Check using ComfortLink scrolling marquee.
Check using ComfortLink scrolling marquee.
Check using ComfortLink scrolling marquee.
Turn Service Test mode off.
Check transformer and circuit breaker.
Check auto-reset limit switches on heater.
Check manual-reset limit switch (LS) on indoor
fan housing.
Check minimum airflow. Check limit switch when
it is cool, replace if open.
Allow time for W2 to energize or adjust setpoints.
Remove restriction. Check SAT compared to the
SAT heating limits.
Check economizer position and configuration.
Adjust minimum position.
Power off unit and remove high voltage wires.
Check resistance of element, replace if open.
Check using ComfortLink scrolling marquee.
Check using ComfortLink scrolling marquee.
Turn Service Test mode off.
Power off unit. Check contactor and replace if
closed.
LED STATUS FUNCTION
On Continuously Relay contact closed (normal operation).
Blinking
Off 24 vac control power not present (off).
Relay contact open (phase loss or phase
reversal has occurred) — No power will be
supplied to the control system.
Thermistor Troubleshooting
The electronic control uses thermistors to sense temperatures
used to control operation of the unit. Resistances at various
temperatures are listed in Tables 22 and 23. Thermistor pin
connection points are shown in the Major System Components
section. The general locations of the thermistors are shown the
Major System Components section.
AIR TEMPERATURES
Air temperatures are measured with 10 kilo-ohm thermistors.
This includes supply-air temperature (SAT), outdoor-air temperature (OAT), space temperature sensors (T55, T56, T58),
and return air temperature (RAT).
The supply air temperature (SAT) and outdoor air temperature
(OAT) thermistors use a snap-mount to attach through the unit
sheet metal panels. The snap-mount tabs must be flattened on
the tip end of the sensor to release for removal from the panel.
(See Fig. 18.) To reinstall, make sure the snap-mount tabs extend out.
57
Fig. 18 — SAT and OAT Thermistor Mounting
REFRIGERANT TEMPERATURES
Condenser coil temperatures are measured with 5 kilo-ohm
thermistors. These measurements provide an approximate saturated condensing temperature for each circuit (SCT.A, SCT.B).
Figures 19-23 show the factory locations for the SCT thermistors. Ensure that thermistors are placed at the correct location
and are snapped securely over the return bend so that contact is
made between the thermistor and the tube.
THERMISTOR/TEMPERATURE SENSOR CHECK
A high quality digital volt-ohmmeter is required to perform
this check.
Connect the digital voltmeter across the appropriate thermistor
terminals at the J8 terminal strip on the Main Base Board (see
Major System Components on p. 68).
Using the voltage reading obtained, read the sensor temperature from Tables 22 and 23.
To check thermistor accuracy, measure temperature at probe
location with an accurate thermocouple-type temperature-measuring instrument. Insulate thermocouple to avoid ambient
temperatures from influencing reading. Temperature measured
by thermocouple and temperature determined from thermistor
voltage reading should be close, within 5°F if care was taken in
applying thermocouple and taking readings.
If a more accurate check is required, unit must be shut down
and thermistor removed and checked at a known temperature
(freezing point or boiling point of water) using either voltage
drop measured across thermistor at the J8 terminal, or by determining the resistance with unit shut down and thermistor disconnected from J8. Compare the values determined with the
value read by the control in the Temperatures mode using the
scrolling marquee display.
SENSOR TRIM
Corrective offsets can be applied to the space temperature and
the supply air temperature sensor readings. These corrections
are set in the Configuration
in the MaintenanceTRIM table for CCN. See the Indoor Air
Quality section for available adjustments to IAQ and OAQ
sensor readings. The space temperature may be corrected by
entering either a calibration temperature value in SPT.C, or an
offset temperature value in SPT.T. The supply-air temperature
may be corrected by entering either a calibration temperature
value in SAT.C, or an offset temperature value in SAT.T. If in-
stalled, the return air temperature may be corrected by entering
either a calibration temperature value in RAT.C, or an offset
temperature value in RAT.T. Temperature corrections should
only be made if sensor readings are compared to an accurate
reference temperature measurement device.
The electronic control uses suction pressure transducers to
measure the suction pressure of the refrigerant circuits. The
pressure/voltage characteristics of these transducers are in
shown in Table 24, the 5vdc power is applied to legs A and B
of the transducer and legs B to C represent the signal voltage.
To use the voltage drop table for troubleshooting, read the voltage across A and B, then subtract the voltage reading from B to
C. This is the voltage drop which can be looked up in Table 24.
The accuracy of these transducers can be verified by connecting an accurate pressure gauge to the second refrigerant port in
the suction line.
Forcing Inputs and Outputs
Many variables may have their value forced through CCN or
directly at the local display. This can be useful during diagnostic testing and also during operation, typically as part of an advanced third party control scheme. Input and output points that
may be forced are indicated as ‘forcible’ in the write status column of the display and CCN tables.
If the user needs to force a variable, follow the same process as
when editing a configuration parameter. A forced variable will
be displayed on the scrolling marquee with a blinking period “.”
following its value. A forced value on Navigator accessory is indicated with a blinking “f”. A forced value on CCN devices is
indicated with “Control” if forced at the unit display, or “Supervisor” if forced via CCN. To remove a local force with the
scrolling marquee, select the point with the ENTER key and then
press the up-arrow and down-arrow keys simultaneously.
NOTE: In the case of a control power reset, any force in effect at
the time of power reset will be cleared.
63
Table 22 — Temperature (°F) vs Resistance/Voltage Drop Values for OAT, SAT, and SPT Thermistors (10K at
Troubleshooting Units Equipped with EnergyX
System
COMPLETE ERV STOPPAGE
EnergyX
an integrated ERV. The ERV requires communication from the
rooftop for operation. This section covers ERV troubleshooting
only. For rooftop troubleshooting refer to the base unit’s Service manual.
Complete ERV Stoppage
There are several conditions that can cause the ERV to shut-
down or appear to be shutdown:
•General power failure.
•Transformer’s circuit breaker tripped.
•ERV main power fuses blown.
•Communication failures.
•Active alarm on the base rooftop unit or the ERV prevent-
•The airflow sensor tubing connected to the incorrect high/
CHECK ALARMS
The ERV has 4 possible alarms based on options installed in
the ERV. These alarms are described in detail below. They all
units are a combination of the base rooftop unit and
ing operation. Review alarms.
low sensor ports in the outside air.
®
show up as a T418 alarm in the ComfortLink controller. Pressing enter and escape together on the scrolling marquee or Navigator display will expand the text and provide the specific
alarm condition. There are 4 status points viewed under Operating Modes on the scrolling marquee or Navigator display
(Operating Modes
→OAU) for each alarm to help diagnose
which alarm caused the T418 in the ComfortLink controller.
These will all reset automatically when the situation has been
resolved.
T418 OAU Filter Dirty
The ERV’s dirty filter alarm should only occur if the optional
Filter Maintenance Switch is installed on the ERV. The dirty
filter alarm activates due to an increase in differential pressure
across the filters. The EXCB’s D16 LED will be turn on and
the OAU Dirty Filter Alarm point will be turned to on (Operat-
ing Modes
fect unit operation but serves as a warning to replace the filters.
It will automatically reset when the pressure differential falls
below setpoint. Verify proper operation by partially blocking
airflow through the ERV filters and confirming that the alarm
does trip.
T418 OAU MOTOR FAILURE
This alarm indicates a motor problem in the ERV, any one of
the motors can trip this alarm (outside intake, exhaust and/or
the wheel motor). The intake and exhaust motors have build in
motor diagnostics and the wheel motor status is a field accessory. Since these are feed into the same alarm, it is important to
→OAU →ALM.2 = On). The alarm does not af-
66
determine which one is having the problem. In test mode run
the components individually to determine which is causing the
problem. If the Shut Down on fan failure configuration is set to
Yes ( Configuration
→OAU →OAU.F = Yes), the ERV will
shutdown with this alarm active. If set to no, the ERV will continue to run as if the alarm did not occur, outside air CFM, exhaust CFM, or pre-conditions might not be achievable if a motor fails. The two classes of motor status are explained below.
Intake and Exhaust Motor Status
If any one of the ERV’s outside or exhaust motors detects a
problem, it will close its build in normally open alarm contact,
which will be seen as 24vac at EXCB J8-3. The EXCB’s D18
LED will be turn on and the OAU Motor Failure Alarm point
will be turned to on (Operating Modes
→OAU →ALM.1 =
On). This alarm will automatically reset when the motor opens
its alarm relay. This alarm is tripped by one of the following:
phase loss, locked rotor, thermal overload, communication error, incorrect signal, or a fan failure.
Wheel Status
This alarm will occur when the ERV wheel is turned on and the
wheel proxy sensor does not detect wheel motion within the set
time. It will open its contact which energizes the normally
closed rotation monitor relay. This is seen as 24vac at EXCB
J5-3 and causes the alarm. The EXCB’s D12 LED will be
turned on and the OAU Motor Failure Alarm point will be
turned to on (Operating Modes
→OAU →ALM.1 = On).
This alarm will automatically reset when motion is detected.
Possible causes of this alarm are: the wheel belt breaking or
slipping, wheel motor failure, proxy sensor failure or incorrect
setting, or wiring error.
T418 OAU LOW CFM
This alarm indicates that the ERV cannot bring in the desired
amount of outside air. The alarm occurs when the actual outside air CFM (Operating Modes
→OAU →A.OA) is less than
10% of the commanded outside air CFM (Operating Modes
→OAU →C.OA) after 10 minutes. This alarm will not occur
in test mode or defrost mode. The Rooftop unit might be able
to help by ramping its indoor fan up. Refer to the base controls,
start up, operation, and troubleshooting manual for details. The
OAU Low CFM Alarm point will be turned to on (Operating
Modes
→OAU →ALM.3 = On). This alarm will automatical-
ly reset if the actual CFM is within 10% of the commanded
CFM. Possible causes of this are: outside air CFM setpoint set
too high, dirty filter or plugged screen, pressure tubing wrong
or disconnected, wrong OA CFM curve programmed, or RTU
indoor fan speed running too low.
T418 OAU GENERAL ALARM
This alarm is not currently used by the ERV.
Check Diagnostic LEDs
Use the on board LEDs to assist in troubleshooting the EnergyX
® system. The EnergyX Control Board (EXCB) and the
Universal Protocol Converter (UPC) each have LEDs that can
help in the troubleshooting process. See Tables 25-27.
The EXCB has five green LEDs and one red LED. The red LED
is for power indication and the green LEDs are status indicators.
The UPC has seven LEDs. There are four communication
LEDs and three status LEDs. The communication LEDs indicate if the translator is speaking to the devices on the network
and should reflect communication traffic based on the baud
rate set. The higher the baud rate, the LEDs would become
more solid.
Table 25 — EXCB LED Indicators
LEDCOLORDESCRIPTION
D9Red24vAC board powerBoard has power
D2GreenRun light FlashingERV is Running
D12GreenERV Wheel Status Alarm
D14Green
D16GreenERV Dirty Filter AlarmDirty Filter
D18GreenERV Blower Status Alarm Fan Failure
ERV Wheel Frost
Protection
STATUS IF LIGHT
IS LIT
ERV Wheel not
rotating when it
should be
ERV detects frost on
the wheel and
running in Frost
Mode
Table 26 — EXUPC LED Indicators
LEDCOLORDESCRIPTIONSTATUS IF LIGHT IS LIT
Power GreenPower Indicator
Rx1Green
Rx2Green
Tx1Green
Tx2Green
RunGreenRun indicator
ErrorRed
* Modbus is a registered trademark of Schneider Electric.
Port 1 Receiving
Data
Port 2 Receiving
Data
Port 1
Transmitting Data
Port 2
Transmitting Data
Internal Error
indicator
Lights when power is being
supplied to the translator.
Lights when the translator
receives data from
ComfortLink MBB via LEN
Lights when the translator
receives data from the
Modbus* EXCB
Lights when the translator
transmits data to the
ComfortLink MBB via LEN
Lights when the translator
transmits data to the Modbus
EXCB
Lights based on translator
health. See Table 27.
Lights based on translator
health, See Table 27.
Table 27 — EXUPC LED Flash Code Diagnostics
Run LED Status
2 flashes per second
5 flashes per second
7 flashes per second
14 flashes per
second
Alternating with
Error
Error LED
Status
OffNormal
2 flashes,
alternating with
Run LED
3 flashes then off
4 flashes then
pause
1 flash per
second
On
On
Off
7 flashes per
second,
alternating with
Run LED
14 flashes per
second,
alternating with
Run LED
Alternating with
Run
ERV Module Status
5 minute auto - restart delay
after system error
Module has just been
formatted
Two or more devices on this
network have the same
ARC156 network address
Module is alone on the network
Operation halted after frequent
system errors or control
programs halted
Operation start - up aborted.
Boot is running
Firmware transfer in progress.
Boot is running
Ten second recovery period
after brownout
Brownout
Restoring memory from
Archive
67
Communication Failures
Communication is critical for ERV operation. It can fail on two
different paths; between the UPC and the rooftop (LEN), or between the UPC and the EXCB. This makes the UPC critical to
ERV operation. Make sure the UPC DIP switches and rotary
switches are set correctly. Make sure the board hardware jumpers
are set on EIA 485 and 2W. During normal operation the 4 communication LEDs will flash interchangeably. If all 4 LEDs are not
flashing then there is a communication problem. Check connections between Port 1a and rooftop’s LEN connection and Port 2
and the EXCB J23 (verify with the proper unit schematic).
The ERVs, LCD screen will show specific communication failures when they occur. Use the LCD screen to help troubleshoot
communications failures. If communication is established, the
LED shows “communication connected”.
COMM FAILURE1 – UPC TO LEN FAIL
This will be displayed if the EXCB can communicate with the
UPC, but the UPC does not receive information from the Com-fortLink controller. This will occur if the cable is pinched or
disconnected, wired wrong or loose, or if the UPC is configured wrong.
COMM FAILURE2 – UPC TO EXCB FAIL
This will be displayed if the EXCB cannot communicate with
the UPC. This will occur if the connection between them is disconnected or pinched. This will also occur if the UPC does not
have power or software, or if it has an error or configured
wrong.
On-Board Pressure Transducers
The EXCB uses on-board pressure transducers to measure the
air pressure of the incoming outside air and the building exhaust air. The CFM values are then calculated based on these
readings and the fan speed. There is a pressure transducer for
the outside air and one for the exhaust air. These are screwed
into the EXCB board to J24 and J25 respectively. They have
three pins: IN, GND, and OUT. The IN pin is 5vdc input power
and GND is the common or ground pin. The OUT pin will be
0.26 to 4.5vdc based on the pressure reading. There are two
different transducers used, two inch of water column (in.wg)
and 5 in.wg. Table 28 shows the voltage/pressure characteristics of each.
Table 28 — Transducer/Voltage vs. Pressure
Voltage (vDC)
<= –0.260.000.00
0.50.120.28
1.00.340.87
1.50.531.46
2.00.822.05
2.51.062.64
3.01.303.23
3.51.523.82
4.01.764.41
4.52.005.00
2 in. transducer5 in. transducer
Pressure (in.wg)
MAJOR SYSTEM COMPONENTS
General
The 48/50HC single package rooftop units contain the ComfortLink electronic control system that monitors all operations of
the rooftop. The control system is composed of several main control components and available factory-installed options or field-installed accessories as listed in sections below. See Figs. 24-31 for
typical control and power schematics for 48HC and 50HC. Refer
to the base unit installation instructions or actual unit control box
for specific unit wiring diagrams.
68
Fig. 24 — Typical Control Diagram for 48HC 04-14 Units (48HC 08-09 shown)
69
Fig. 25 — Typical Power Diagram for 48HC 04-14 Units (48HC 08-09 shown)
70
Fig. 26 — Typical Control Diagram for 50HC 04-14 Units (50HC 14 shown)
71
Fig. 27 — Typical Power Diagram for 50HC 04-14 Units (50HC 14 Non-Humidi-MiZer shown)
72
Fig. 28 — Typical Control Diagram 48HC 17-28 Units
73
Fig. 29 — Typical Control Diagram 50HC 17-28 Units
74
Fig. 30 — Typical Humid-MiZer Power Diagram and Component Arrangement 48/50HC 17-28 Units
75
Fig. 31 — Typical Non-Humid-MiZer Power Diagram and Component Arrangement 48/50HC 17-28 Units
76
Main Base Board (MBB)
CEPL130346-01
STATU S
LEN
J1
J2
J4
J3
J5
J6
J7
J8
J9
J10
CCN
RED LED - STATU SGREEN LED -
LEN (LOCAL EQUIPMENT NETWORK)
YELLOW LED CCN (CARRIER COMFORT NETWORK)
INSTANCE JUMPER (SET TO 1)
See Fig. 32 and Table 29. The MBB is the center of the ComfortLink control system. It contains the major portion of the
operating software and controls the operation of the unit. The
MBB continuously monitors input/output channel information
received from its inputs and from the Economizer Control
Board (ECB). The MBB receives inputs from thermistors and
transducers. The MBB also receives the Current Sensor inputs
for compressors and other discrete or digital inputs. The MBB
reads space temperature (SPT) from either a T-55, T-56 or T-58
device and space temperature offset (SPTO) from a T-56 device. See Field-Installed Accessories section. The MBB controls 11 relays.
NOTE: The Main Base Board (MBB) has a 3-position instance
jumper that is factory set to ‘1.’ Do not change this setting.
Fig. 32 — Main Base Board (MBB)
77
Table 29 — Main Base Board (MBB) Connections
DISPLAY NAME POINT DESCRIPTION SENSOR LOCATION TYPE OF I/O
INPUTS
Input power from TRAN2 control box 24 VAC J1, 1-3
IGC.F IGC Fan Request gas section switch input J6, 4
FDWN Fire shutdown switch supply/return/space switch input J6, 6
G Thermostat G (Fan) space switch input J7, 2
W2 Thermostat W2 (2nd Stage Heat) space switch input J7, 4
W1 Thermostat W1 (1st Stage Heat) space switch input J7, 6
Y2 Thermostat Y2 (2nd Stage Cool) space switch input J7, 8
Y1 Thermostat Y1 (1st Stage Cool) space switch input J7, 10
FIL.S Filter status switch indoor fan section switch input J9, 2-3
HUM Humidistat switch input space switch input J9, 5-6
Not Used 0-5vdc digital input J9, 7-9
Not Used 0-5vdc digital input J9, 10-12
SPT Space temperature (T55/56) space 10k thermistor J8, 1-2
SPTO Space temperature offset (T56) space 10k thermistor J8, 2-3
OAT Outdoor air temperature outdoor coil support 10k thermistor J8, 5-6
SAT Supply air temperature
SCT.A
SCT.B
RAT Return Air
Temperature
FAN.S Fan status
switch
SSP.A Suction pressure, circuit A compressor A suction pipe
SSP.B Suction pressure, circuit B compressor B suction pipe
Local Equipment Network (LEN) communication J5, 1-3
Carrier Comfort Network (CCN) communication J5, 5-7
Network device power 24 VAC J5, 9-10
Scrolling Marquee Display (LEN) communication J4, 1-3
Scrolling Marquee Display power 24 VAC J4, 5-6
Expansion LEN Bus communication J3, 1-3
Optional ECB power 24 VAC J2, 1-2
indoor fan housing, or
supply duct
outdoor coil, circuit A 5k thermistor J8, 9-10
outdoor coil, circuit B 5k thermistor J8, 11-12
10k thermistor J8, 7-8
0-5 VDC pressure
transducer
0-5 VDC pressure
transducer
CONNECTION PIN
NUMBER
J8, 18-20
J8, 21-23
78
Economizer Control Board (ECB)
The ECB controls the economizer actuator. (See Fig. 33 and
Table 30.) The control signal from the ECB uses either the
MFT (Multi-Function Technology) digital communication protocol or a 4 to 20 mA output signal as defined by the configuration Configuration
Indoor Air Quality (IAQ), Outdoor Air Quality (OAQ), enthalpy and RH sensor. It also controls two power exhaust outputs.
ECONE.CTL. The ECB has inputs for
By digitally communicating with the ECB, the economizer actuator is able to provide the damper position and diagnostic information to the ComfortLink controller. The damper position
is displayed at Outputs
ECONEC.AP. Diagnostic informa-
tion is displayed via Alert T414. More information about these
alarms is contained in the Alarms and Alerts section.
NOTE: The Economizer Control Board (ECB) has a 4-position
DIP switch that is factory set to ‘0’ (ON, towards the center of the
board). Do not change this setting.
Fig. 33 — Economizer Control Board (ECB)
Table 30 — Economizer Control Board (ECB) Connections
DISPLAY NAME POINT DESCRIPTION SENSOR LOCATION TYPE OF I/O
INPUTS
Input power from MBB control box 24 VAC J1, 1- 2
RM.OC Remote occupancy switch field installed switch input J4, 2
ENTH or IAQ.S
IAQ Indoor air quality sensor return/space 0-20 mA J5, 2
OAQ or SP.RH
OUTPUTS
PE.1 Power exhaust 1 relay relay J8, 3
PE.2 Power exhaust 2 relay relay J8, 6
EC.CP Commanded Economizer position 0-20 mA J9, 1
COMMUNICATION
EC.CP & EC.AP
Outdoor enthalpy switch, or Indoor air
quality switch
Outdoor air quality sensor, or Relative
humidity sensor
Sensor Common Ground J5, 3
Actuator Common Ground J7, 3
Output power to enthalpy switch 24 VAC J4, 3
Output power for loop power sensors 24 VDC J5, 1
Output power to economizer actuator 24 VAC J7, 2
Local Equipment Network (LEN) communication J2, 1-3
Carrier Comfort Network (CCN) communication J3
Economizer actuator position (digital
control)
economizer, or return/space switch inputJ4, 4
field installed 0-20 mA J5, 5
MFT communication J7, 1
CONNECTION PIN
NUMBER
79
Integrated Gas Control (IGC) Board
RED LED-STAT US
The IGC is provided on gas heat units. (See Fig. 34 and Table 31.)
The IGC controls the direct spark ignition system and monitors
the rollout switch, limit switch, and induced-draft motor Hall Effect switch.
Fig. 34 — Integrated Gas Control (IGC) Board
Table 31 — Integrated Gas Control (IGC) Board Connections
TERMINAL LABEL POINT DESCRIPTION SENSOR LOCATION TYPE OF I/O
INPUTS
RT, C Power for IDR on 575v units control box 24 VAC Spade
C Input power common Spade
SS Speed sensor gas section analog input J1, 1- 3
FS, T1 Flame sensor gas section switch input Spade
W Heat stage 1 Call MBB to CTB to IGC 24 VAC J2, 2
G Indoor Fan Call CTB to IGC 24 VAC J2, 3
R Input power from TRAN 1 CTB to IGC 24 VAC J2, 4
RS Rollout switch gas section switch input J2, 5-6
LS Limit switch gas section switch input J2, 7-8
CS Centrifugal switch (not used) switch input J2, 9-10
OUTPUTS
L1, CM Induced draft combustion motor or relay gas section line VAC
IFO Indoor fan request control box relay J2, 1
GV (W1) Gas valve (heat stage 1) gas section relay J2, 12
GV (W2) Gas Valve (heat stage 2, from CTB) gas section Not on IGC
CONNECTION PIN
NUMBER
80
48/50HC 04-14 Units — Low Voltage Terminal
Board (TB)
The field connection terminal board has 30 terminals oriented
in 3 rows of 10 terminals. The front has screw terminals and
the back has spade connectors. This board provides connection
for the thermostat, space sensor, and most field installed accessories. See Table 32.
TERMINAL
LABEL
C- 2 Transformer 2 Common 24 VAC common 1,2
R- 2 24 VAC power Transformer 2 24 VAC 9,10
SPT+ SPT Space temperature (T55/56) space 10k thermistor 14
SPT- SPT Space temperature (T55/56) space 10k thermistor 13
SPTO SPTO Space temperature offset (T56) space 10k thermistor 12
FDWN FDWN Fire shutdown switch input supply/return/space 24 VAC input 30
X ALRM Alarm output (normally open) space 24 VAC output 3
G G Thermostat G (Fan) space 24 VAC input 4
W1 W1 Thermostat W1 (1st stage heat) space 24 VAC input 5
W2 W2 Thermostat W2 (2nd stage heat) space 24 VAC input 6
Y1 Y1 Thermostat Y1 (1st stage cool) space 24 VAC input 7
Y2 Y2 Thermostat Y2 (2nd stage cool) space 24 VAC input 8
RAT RAT Return Air Temperature Sensor return duct 10k thermistor 15,16
SAT SAT Supply Air Temperature Sensor Blower or duct 10k thermistor 17,18
HUM HUM Humidistat switch input supply/return/space switch input 27
LPWR Analog Sensor Loop power (24vdc) 24 VDC 24
COM Analog sensor common Ground 22
IAQ IAQ Indoor air quality sensor return/space 4- 20 mA input 23
*Point name displayed on the scrolling marquee or Navigator display.
DISPLAY NAME* DESCRIPTION SENSOR LOCATION TYPE OF I/O TERMINAL NUMBER
Relative humidity sensor or Outdoor
air quality sensor
Outdoor enthalpy switch, or Indoor
air quality switch
Not Used 11,19,20,28,29
field installed 4-20 mA input 21
economizer, or return/
space
24 VAC input 26
81
48/50HC 17-28 Units — Low Voltage Terminal
1
2
3
4
LENCCN
CCN
(+)(-)(com)shield
Boards (TB A and TB B)
There are two terminal boards with 16 terminals each, and oriented one mounted above the other. The front have screw terminals and the back have spade connectors. These terminal
boards provide a connection point for the thermostat or space
sensor and for most field-installed accessories. See Table 33.
Communication Interface Board (CIB)
This circuit board provides a field connection point for unit
communications. The Local Equipment Network (LEN) RJ-11
connector allows a hand-held Navigator to be plugged in to access the unit’s menus. The Carrier Comfort Network
®
(CCN)
RJ-11 connector or the CCN screw terminals allow building
communication connections. See Fig. 35.
Fig. 35 — Communications Interface Board (CIB)
Central Terminal Board (CTB)
This circuit board is a simple trace board that serves as a junction point between components and the ComfortLink system. It
is the distribution center for transformer 1’s power. The integrated gas controller (IGC), electric heater control, compressor
control, and unit shutdown all feed through this trace board.
See Fig. 36 and Table 34 for the connections through this
board.
Fig. 36 — Central Terminal Board (CTB)
Table 33 — Upper and Lower Field Connection Terminal (TB A and TB B) Board Connections (17-28 Size Units)
TERMINAL
BLOCK
Upper
(TB A)
Lower
(TB B)
*Point name displayed on the scrolling marquee or Navigator™ display.
TERMINAL
LABEL
C- 2 Transformer 2 Common 24 VAC common 1,3,4
R- 2 24 VAC power Transformer 2 24 VAC 13,15,16
SPT+ SPT Space temperature (T55/56) space 10k thermistor 8
SPT- SPT Space temperature (T55/56) space 10k thermistor 7
SPTO SPTO Space temperature offset (T56) space 10k thermistor 5
FDWN FDWN Fire shutdown switch input
X ALRM Alarm output (normally open) space 24 VAC output 2
G G Thermostat G (Fan) space 24 VAC input 6
W1 W1 Thermostat W1 (1st stage heat) space 24 VAC input 8
W2 W2 Thermostat W2 (2nd stage heat) space 24 VAC input 10
Y1 Y1 Thermostat Y1 (1st stage cool) space 24 VAC input 12
Y2 Y2 Thermostat Y2 (2nd stage cool) space 24 VAC input 14
RAT RAT Return Air Temperature Sensor return duct 10k thermistor 1,3
SAT SAT Supply Air Temperature Sensor Blower or duct 10k thermistor 5,7
HUM HUM Humidistat switch input
LPWR
COM Analog sensor common Ground 4
IAQ IAQ Indoor air quality sensor return/space 4- 20 mA input 6
R- 2 24 VAC power Transformer 2 24 VAC 15
C- 2 Transformer 2 Common 24 VAC common 16
DISPLAY
NAME*
DESCRIPTION
Analog Sensor Loop power
(24vdc)
Relative humidity sensor or
Outdoor air quality sensor
Outdoor enthalpy switch, or
Indoor air quality switch
SENSOR
LOCATION
supply/return/
space
supply/return/
space
field installed 4-20 mA input 2
economizer, or
return/space
TYPE OF I/O
24 VAC input 11
switch input 9
24 VDC 8
24 VAC input 12
TERMINAL
NUMBER
82
Table 34 — Central Terminal Board (CTB) Connections
CONNECTION LABEL PIN NUMBER POINT DESCRIPTION 24Vac FROM 24Vac TO
7 Compressor 1 Call MBB ECON
DDC T-STAT
ECON
CLO1/COMP1
CLO2/COMP2
CIRCUIT 1
CIRCUIT 2
CONTRL BOARD
PMR
REMOTE SHUTDOWN
UNIT SHUTDOWN
R Spades
C Spades Ground CONTL BOARD
NOTE: The References above for T1J1 through T1J9 are to show the
path of transformer 1 as is goes through the board and safety devices.
SMOKE SHUTDOWN
Scrolling Marquee Display
This device is the keypad interface used to access rooftop information, read sensor values, and test the unit. (See Fig. 37.)
The scrolling marquee display is a 4-key, 4-character, 16-segment LED (light-emitting diode) display. Eleven mode LEDs
are located on the display as well as an Alarm Status LED. See
Basic Control Usage section for further details.
Accessory Navigator™ Display
The accessory hand-held Navigator display can be used with
3 Comp 1 Contactor Common CTB C C1 - Coil
4,5 Comp 1 Jumper ECON CIRCUIT 1 LPS
6Comp 1 Contactor SignalCIRCUIT 1 HPSC1 - Coil
3 Comp 2 Contactor Common CTB C C1 - Coil
4,5 Comp 2 Jumper ECON CIRCUIT 2 LPS
6 Comp 2 Contactor Signal CIRCUIT 2 HPS C1 - Coil
7 ODF Contactor Signal ECON OFC1 - Coil
HPS
LPS Comp 1 jumper CLO1/COMP1 CIRCUIT 1 HPS
HPS
LPS Comp 2 jumper CLO2/COMP2 CIRCUIT 2 HPS
2 Heat Stage 2 Call DDC T’STAT Gas Valve or PL3
3 Heat Stage 1 Call DDC T’STAT IGC-W or PL3
4 IGC Common/Ground CTB C IGC C
5
6 IGC Call for Indoor fan IGC IFO CONTL BOARD
7 IGC Call for Indoor fan CONTL BOARD MBB
8 IGC power (T1J9) CTB R IGC R
9 Transformer 1 Power (T1J1) TRAN1 24Vac UNIT SHUTDOWN
10
11
1 Ground CTB C PMR Device
2
3
24V OUT
C
Comp 1 High Pressure
Switch
Comp 2 High Pressure
Switch
Transformer 1 Common/
Ground
Indoor Fan overload signal
Indoor Fan overload source
Phase Monitor Normally
Remote Disable Switch if
installed (T1J4 and T1J5)
Normally Closed Smoke
Detector Contact (T1J3)
Smoke Detector Controller
Smoke Detector Controller
Transformer 1 Power after
(T1J9)
(T1J8)
Phase Monitor Source
(T1J6)
Closed Signal (T1J7)
Power (T1J2)
Common
Safety Chain (T1J9)
CIRCUIT 1 LPS CLO1/COMP1
CIRCUIT 2 LPS CLO2/COMP2
TRAN1 Common CTB C
Fan overload CTB R
PMR Fan overload
UNIT SHUTDOWN PMR Device
PMR Device CONTL BOARD
SMOKE SHUTDOWN PMR
Smoke Detector REMOTE SHUTDOWN
CONTL BOARD Smoke Detector
CTB C Smoke Detector
CONTL BOARD
MODE
Run Status
Service Test
Temperature
Pressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
Operating Modes
Alarms
Alarm Status
ESCAPE
ENTER
48/50HC units. (See Fig. 38.) The Navigator display operates
the same way as the scrolling marquee device. The Navigator
display plugs into the LEN port on either TB or the ECB board.
Fig. 37 — Scrolling Marquee
83
2.Cut the CCN wire and strip the ends of the red (+), white
Ru
n Sta
tus
Service Te
st
T
emp
erature
s
P
ressures
Setpoints
Inpu
ts
Outp
uts
Con
fig
u
ra
tion
Time Clo
ck
Oper
ating
Mod
es
Alarms
ENTER
E S C
M O
DE
Ala
rm
Sta
tus
TIME
EW
T
LWT
SETP
12 . 58
54.6°
F
44 .1
°F
44.0°F
N A
VIGATOR
Com for t Li nk
(ground), and black (–) conductors. (Substitute appropriate
colors for different colored cables.)
3.Connect the red wire to (+) terminal on CIB, the white wire
to COM terminal, and the black wire to the (–) terminal.
4.The RJ14 CCN connector on CIB can also be used, but is
only intended for temporary connection (for example, a
laptop computer running Carrier network software).
5.Restore power to unit.
IMPORTANT: A shorted CCN bus cable will prevent some
routines from running and may prevent the unit from starting.
If abnormal conditions occur, unplug the connector. If conditions return to normal, check the CCN connector and cable.
Run new cable if necessary. A short in one section of the bus
can cause problems with all system elements on the bus.
Fig. 38 — Accessory Navigator™ Display
Carrier Comfort Network® (CCN) Interface
The units can be connected to the CCN if desired. The communication bus wiring is a shielded, 3-conductor cable with drain
wire and is field supplied and installed. The system elements are
connected to the communication bus in a daisy chain arrangement. (See Fig. 39.) The positive pin of each system element
communication connector must be wired to the positive pins of
the system elements on either side of it. This is also required for
the negative and signal ground pins of each system element.
Wiring connections for CCN should be made at the CIB. (See
Fig. 24, 26, 28 or 29, depending on unit configuration.) Consult
the CCN Contractor’s Manual for further information.
NOTE: Conductors and drain wire must be 20 AWG (American Wire Gauge) minimum stranded, tinned copper. Individual
conductors must be insulated with PVC, PVC/nylon, vinyl,
1
Tefl on
, or polyethylene. An aluminum/polyester 100% foil
shield and an outer jacket of PVC, PVC/nylon, chrome vinyl,
or Teflon with a minimum operating temperature range of –
20°C to 60°C is required. See the following table for acceptable wiring.
MANUFACTURER PART NO.
Alpha 2413 or 5463
Belden 8772
Carol C2528
West Penn 302
It is important when connecting to a CCN communication bus
that a color-coding scheme be used for the entire network to
simplify the installation. It is recommended that red be used for
the signal positive, black for the signal negative and white for
the signal ground. Use a similar scheme for cables containing
different colored wires.
At each system element, the shields of its communication bus
cables must be tied together. The shield screw on CIB can be
used to tie the cables together. If the communication bus is entirely within one building, the resulting continuous shield must
be connected to a ground at one point only. The shield screw
on CIB is not acceptable for grounding. If the communication
bus cable exits from one building and enters another, the
shields must be connected to grounds at the lightning suppressor in each building where the cable enters or exits the building
(one point per building only). To connect the unit to the network:
1.Turn off power to the control box.
1. Teflon is a registered trademark of DuPont.
Protective Devices
COMPRESSOR PROTECTION
Overcurrent
Each compressor has internal line break motor protection.
Overtemperature
Each compressor has an internal protector to protect it against
excessively high discharge gas temperatures.
High-Pressure Switch
If the high-pressure switch trips, the compressor will shut
down and the compressor safety alarm should trip. Refer to the
Alarm section for compressor safety alarms.
EVAPORATOR FAN MOTOR PROTECTION
Indoor-fan motors less than 5 hp are equipped with internal
overcurrent and overtemperature protection. Protection devices
reset automatically. Disconnect and lock out power when servicing motor. Indoor-fan motors 5 hp and larger are equipped
with a manual reset, calibrated trip, magnetic circuit breaker
and overcurrent protection. Do not bypass connections or increase the size of the breaker to correct trouble. Determine the
cause and correct it before resetting the breaker. On units with
VFD, it serves as the motor thermal and over-current protection. Refer to Appendix C for more details on VFD.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the
unit.
DO not bypass the VFD while running the motor. Do not
change VFD parameter associated with motor characteristics, these are factory programmed for motor protection.
Damage to the motor or the VFD can occur.
CONDENSER-FAN MOTOR PROTECTION
Each condenser-fan motor is internally protected against over-
temperature.
Fuses are located in the control box and feed power to the con-
denser fan motors. Always replace blown fuses with the correct
size fuse as indicated on the unit fuse label.
SATURATED SUCTION PRESSURE (SSP)
If the SSP for a particular circuit is reading below the alarm set
point for an extended period of time, that circuit will be shut
down. After 15 minutes, the alarm will automatically reset. If
this alarm occurs 3 times consecutively, the circuit will remain
locked out until an alarm reset is initiated via CCN or manually
via the scrolling marquee display (see Alarms and Alerts section for more details).
84
CCN BUS
BUILDING SUPERVISOR
CL
ROOFTOP
UNIT
ROOFTOP
UNIT
ROOFTOP
UNIT
ROOFTOP
UNIT
CL
NETWORK
OPTIONS
REMOTE
CCN SITE
NON CARRIER
HVAC
EQUIPMENT
AUTODIAL
GATEWAY
COMFORT
CONTROLLER
CL
CL
HEATING/COOLING UNITS
LEGEND
TO
ADDITIONAL
TERMINALS
TERMINAL
SYSTEM
MANAGER
CL
TCU
TCU
TCU
DAV FAN
POWERED
MIXING
BOX
DAV AIR
TERMINAL
DAV AIR
TERMINAL
ROOFTOP
UNIT
AIR DISTRIBUTION-DIGITAL AIR VOLUME CONTROL (DAV)
CCN
CL
DAV
HVAC
TCU
— Carrier Comfort Network
®
— ComfortLink Controls
— Digital Air Volume
— Heating, Ventilation, and Air Conditioning
— Terminal Control Unit
Fig. 39 — CCN System Architecture
85
CONDENSATE OVERFLOW SWITCH (COFS)
A separate factory installed device can detect a full drain pan.
This device consists of a pan sensor to detect the water level
and a relay control switch to read the sensor. The control
switch is located in the unit control box and will trip out the
compressors on overflow detection. Since this device is in series with the compressor contactor and high pressure switch on
any given circuit, ComfortLink does not directly read this. The
relay switch is a normally open device that closes when power
is applied; this allows the compressor to be energized without
problem. If the sensor detects high water levels for 10 seconds
straight, it will open the contact breaking the compressor call.
The switch will also turn its red LED on. If the water level is
low enough for 5 minutes the relay will close again allowing
the compressor call. A blinking red LED on the switch indicates that the sensor has been disconnected.
Field-Installed Accessories
SPACE TEMPERATURE SENSOR (T-55)
The T-55 space temperature sensor (part no. 33ZCT55SPT) is a
field-installed accessory. The sensor is installed on a building
interior wall to measure room air temperature. The T-55 sensor
also includes an override button on the front cover to permit
occupants to override the Unoccupied Schedule (if programmed). The jumper wire in the installer’s packet must be
connected between R and W1 when using a T-55 device.
TB or TB A-SPT+ . . . Sensor Input
TB or TB A-SPT– . . . Sensor Common
SPACE TEMPERATURE SENSOR (T-56)
The T-56 space temperature sensor (part no. 33ZCT56SPT) is a
field-installed accessory. This sensor includes a sliding scale
on the front cover that permits an occupant to adjust the space
temperature set point remotely. The T-56 sensor also includes
an override button on the front cover to allow occupants to
override the unoccupied schedule (if programmed). The jumper wire in the installer’s packet must be connected between R
and W1 when using a T-56 device.
TB or TB A-SPT+ ... Sensor Input
TB or TB A-SPT– ... Sensor Common
TB or TB A-SPTO ... Setpoint Offset Input
SPACE TEMPERATURE SENSOR (T-58)
The T-58 space temperature sensor (part no. 33ZCT58SPT) is a
field-installed accessory. The T-58 sensor communicates with
the ComfortLink controller, providing space temperature, heating and cooling set points, and mode operation information.
The jumper wire in the installer’s packet must be connected between R and W1 when using a T-58 device.
Refer to the T-58 installation instructions for information on installing and configuring the T-58 sensor.
Each T-58 sensor must have a unique address on the CCN.
Each T-58 sensor must also be configured with the address of
the unit control it is communicating to.
SPACE TEMPERATURE SENSOR AVERAGING
See Fig. 40 for space temperature averaging with T-55 sensors
only. If the use of one T-56 sensor is required, refer to Fig. 41.
CARRIER ACCESSORY KITS
There are specific accessory kits sold for various field installed
accessories. These kits vary based on model, size, voltage,
manufacture date, and duct orientation. Some of these kits include Economizer, Power Exhaust, and Electric Heat. Refer to
the Controls Quick Set-Up section for configuration and more
information on these accessories.
TWO-POSITION DAMPER
The two-position outdoor air damper accessory usage depends
on model size and return duct orientation. This accessory wires
directly into the low voltage circuit for the indoor fan control.
No other control configuration is needed. On 04-14 size units a
9 pin to 12 pin converter harness is required and is included in
the kit or factory installed.
INDOOR AIR QUALITY
The indoor air quality (IAQ) sensor (part no. 33ZCSENCO2)
is a field-installed accessory which measures CO
levels in the
2
air. When installing this sensor, an ECB board must be installed and the unit must be configured for IAQ use by setting
Configuration
AIR.QIA.CF to a value of 1, 2, or 3. See
the Indoor Air Quality section for more information.
TB or TB B-IAQ . . . . . . . . 4-20mA Input
TB or TB B-COM . . . . . . . Sensor Common
TB or TB B-R-2 . . . . . . . . 24vac Output
TB or TB B-C-2 . . . . . . . . common (GND)
OUTDOOR AIR QUALITY
The outdoor air quality (OAQ) sensor is a field-installed acces-
sory that measures CO
levels in the air. When installing this
2
sensor, an ECB board must be installed and the unit must be
configured for OAQ use by setting Configura-
tion
AIR.QOA.CF to a value of 1 or 2. See the Indoor Air
Quality section for more information.
TB or TB B-SARH . . . . . . 4-20mA Input
TB or TB B-COM . . . . . . Sensor Common
TB or TB B-R-2 . . . . . . 24vac Output
TB or TB B-C-2 . . . . . . Common (GND)
SMOKE DETECTORS
The smoke detectors are field-installed accessories. These detec-
tors can detect smoke in either the return air or supply and return
air. When installing either detector, the unit must be configured
for fire shutdown by setting Configuration
UNITFS.SW to
normally open (1) or normally closed (2).
TB or TB A-FDWM . . . . . Discrete Input to Board
FILTER STATUS
The filter status accessory is a field-installed accessory. This
accessory detects plugged filters. When installing this accessory, the unit must be configured for filter status by setting Con-
figuration
UNITFL.SW to normally open (1) or normally
closed (2). Normally open (1) is the preferred configuration.
Filter status wires are pre-run in the unit harness and located
near the switch installation location. Refer to the Filter Accessory installation instructions for more information.
FAN STATUS
The fan status accessory is a field-installed accessory. This ac-
cessory detects when the indoor fan is blowing air. When installing this accessory, the unit must be configured for fan status by setting Configuration
UNITFN.SW to normally
open (1) or normally closed (2). Normally open (1) is the preferred configuration.
Fan status wires are pre-run in the unit harness and located near
the switch installation location. Refer to the Fan Accessory installation instructions for more information.
86
TO MAIN
BASE BOARD
RED
BLK
RED
BLK
RED
BLK
SENSOR 1
SENSOR 2
SENSOR 3
RED
BLK
SENSOR 6SENSOR 5
RED
BLK
SENSOR 4
RED
BLK
RED
BLK
RED
BLK
SENSOR 8SENSOR 7SENSOR 9
1
RED
BLK
TB1-T55
SENSOR 1SENSOR 2SENSOR 3SENSOR 4
RED
BLK
RED
BLK
RED
BLK
RED
BLK
TO MAIN
BASE BOARD
RED
BLK
TB1-T55
1
2
2
SPACE TEMPERATURE AVERAGING — 4 T-55 SENSOR APPLICATION
SPACE TEMPERATURE AVERAGING — 9 T-55 SENSOR APPLICATION
Fig. 41 — Space Temperature Sensor Averaging with 3 T-55 Sensors and One T-56 Sensor
87
ENTHALPY SENSORS
The enthalpy accessories (part no. CRENTSNG002A00 and
CRENTDIF002A00) are field-installed accessories. The first
accessory (outdoor air only) determines when the enthalpy is
low relative to a fixed reference. Adding the second accessory
(return air) compares the enthalpy between the outdoor and return airstreams. In each case, the enthalpy 4 to 20 mA signals
are converted to a switch output which is read by the ECB.
When installing this accessory, the unit must be configured for
enthalpy-based control by setting ConfigurationECONEN.SW to normally open (1). See Fig. 28 and Fig. 29
for wiring details. Normal status is an active switch which tells
the control that enthalpy is LOW. The actual switch terminal
LOW is normally closed. Refer to the Enthalpy Kit installation
instructions for more information on the installation.
RETURN/SUPPLY AIR TEMPERATURE SENSOR
The temperature sensor (part no. 33ZCSENSAT) is a field-in-
stalled accessory which may be installed on the common return
air duct and/or the common supply air duct near the unit. The
duct return air temperature (RAT) may be selected for display.
When installing the sensor, the unit must be configured by setting Configuration
will allow differential dry bulb control of the economizer. The
duct supply air temperature (SAT) may be used to replace the
SAT sensor that is internal to the unit. A supply duct SAT measurement is valid for heating mode display while the factorystandard internal SAT is not valid for heating due to its location
upstream of the heating section. When installing the supply
duct SAT, the unit must be configured by setting Configura-
tion
UNITSAT.H to ENBL. A SAT sensor in the supply
duct is the preferred configuration for systems with Carrier
variable volume and temperature (VVT) accessory controls.
The field connection terminal board has SAT and RAT terminals. When installing field sensors, use these terminals accordingly to connect into the MBB.
UNITRAT.S to YES. Using a RAT
IMPORTANT: When wiring a field SAT sensor, the factory
installed on must be disconnected from the back of the terminal board.
SPACE HUMIDISTAT
The Space Humidistat (part no. -HL-38MG-029) is a wall
mounted device with an adjustable setpoint to control humidity
levels. The humidistat input is provided on the field connection
terminal board. The Space Humidity Switch configuration,
Configuration
or normally closed status of this input at HIGH humidity.
TB or TB B-HUM . . . . . . . Discrete Input to Board
NOTE: The humidistat terminals are only in use when the unit
is equipped with the Humidi-MiZer factory option.
SPACE HUMIDITY SENSOR
The space relative humidity sensor (part no. 33ZCSENDRH-
01 duct mount or 33ZCSENSRH-01 wall mount) is a field-installed accessory. The space relative humidity (RHS) may be
selected for use if the outdoor air quality sensor (OAQ) is not
used and an economizer board is installed. When installing the
relative humidity sensor, the unit must be configured by setting
EnergyXunits consist of a factory-installed energy recovery
ventilator (ERV) device on a 48/50HC rooftop unit. The EnergyX ERV unit is integrated into the base rooftop unit construction and is factory-wired. The ERV unit contains a control box,
supply fan(s), exhaust fan(s), and an enthalpy wheel assembly.
All control operations of the ERV are based on the rooftop
unit’s operation through communication with the ComfortLink
controller. See Fig. 42 and 43 for ERV wiring schematic and
component arrangement.
88
Fig. 42 — Modulating ERV Wiring Schematic
89
Fig. 43 — EnergyX
®
ERV Control Box Component Layouts
90
ENERGYXCONTROL BOARD (EXCB)
See Fig. 44 and Table 35.
The EXCB continuously monitors input/output channel informa-
tion received from its inputs and from the Universal Protocol
Converter (UPC). The EXCB receives inputs from transducers
and discrete inputs. See Options and Accessories section. The
EXCB has relay analog outputs, and is equipped with a LCD
screen. The EXCB communicates with a Modbus protocol and is
not a CCN device. The EXCB has a reset button that is used to
force all the outputs and reset communication.
NOTE: There are hardware jumpers set throughout the board. Do
not change these jumpers.
Fig. 44 — EnergyX Control Board (EXCB)
Table 35 — EXCB Input/Output Connections
POINT DESCRIPTIONSENSOR LOCATIONInput/OutputTYPE OF Input/OutputCONNECTION PIN NUMBER
DownloadN/ABothCommunicationJ1
LCDLow voltage control boxBothCommunicationJ2
Power from TRANSControl boxInput24VACJ3, 1-2
Power to RelaysLow voltage control boxOutput24VACJ4, 1
Power to UPCLow voltage control boxOutput24VDCJ4, 3-4
Wheel Rotation SensorAttached to scoopInputSwitchJ5, 2-4
Frost SwitchAttached to scoopInputSwitchJ6, 3-4
Filter Status Switch
Motor Status SwitchesIntegrated in motorsInputSwitchJ8, 3-4
Leaving Air TempScoop sectionInput10KJ15, 1-2
Exhaust Air TempExhaust air sectionInput10KJ16, 1-2
Wheel RelayHigh voltage control boxOutputRelayJ17, 4
2-position Exhaust damper
relay
OA fan speed signalN/AOutput2-10vdcJ21, 1-3
OA Modulating DamperIntake damper assemblyOutput2-10vdcJ21, 1-4
EX fan speed signalN/AOutput2-10dvcJ22, 1-3
Modbus to UPCControl boxBothCommunicationJ23, 1-3
Outside Air pressure
Transducer
Exhaust Air pressure
Transducer
Building Pressure SensorLow voltage control boxInput4-20mAJ10, 1-6
Attached to scoop and in Exhaust
air section
Exhaust damper assemblyOutputRelayJ19, 4
Low voltage control boxInputDigital 0-5vdcJ24
Low voltage control boxInputDigital 0-5vdcJ25
InputSwitchJ7, 3-4
91
Universal Protocol Converter (UPC)
See Fig. 45 and Table 36.
The UPC board is required to convert CCN into Modbus proto-
col. It contains the operating software that runs the ERV logically. The UPC is connected to the ComfortLink controller
LEN bus on the rooftop unit.
The DIP switches should be set as follows: 1=off, 2=off, 3=on,
4=on, 5=off, 6=off, 7=on, and 8=off. The address rotary
switches should be set to 01 (10’s=0 and 1’s=1). Do not
change these settings.
USER INTERFACE
All ERV set point adjustment, service tests, and monitoring are
accomplished through the ComfortLink controller scrolling
marquee interface. See the ComfortLink Controls, Start-Up,
Operation and Troubleshooting Instructions for further details
on ComfortLink controller operation. The ERV EXCB board
has a LCD screen that can be used to help troubleshoot communication problems. The following are examples of the text
that can be seen on the EXCB’s LCD screen.
LCD Texts
Initialize_LEN Communication
This will occur when the ERV is turned on from a power reset.
Communication Connected
This will be displayed when correct communication is estab-
lished between the RTU and ERV and within the ERV.
Comm Failure1 UPC_to_LEN_Fail
This occurs if there is a communication problem between the
UPC and ComfortLink MBB.
Comm Failure2 UPC_to_EXCB_Fail
This will occur if there is a communication problem between
the UPC and the EXCB.
Warning UPC TestMODE_Enabled
This will occur if the UPC was left in a factory Test mode a
BACview1 Handheld is needed to pull the ERV out of this
mode back to normal running mode.
1. BACView is a registered trademark of Automated Logic Corporation.
Fig. 45 — Universal Protocol Converter (UPC)
Table 36 — UPC Input/Output Connections
TERMINAL NAMEDESCRIPTIONInput/OutputTYPE OF Input/Output
24VACSupply power to UPCInput24VAC1 - 2
Port 2UPC ModbusbothCommunication1 - 2
Port 1aUPC LENbothCommunication1 - 3
Port 1bNot usedN/AN/AN/A
Rnet
Local AccessbothCommunication1 - 5
BACview User Interface or
Download Connection
bothCommunication1 - 4
CONNECTION PIN
NUMBER
92
ENTHALPY WHEEL
The enthalpy wheel is the “heat exchangers” of the ERV. It
consists of several wheel segments aligned in a cassette assembly. These are not “filters” but made of a desiccant material.
The wheel is rotated by a motor and belt, no adjustments required. When the wheel rotates it uses the building exhaust air
to pre-conditions the outside air as it passes through the wheel.
MODULATING FAN
The modulating ERV is equipped with direct drive variable
speed plenum fans for outside air intake and exhaust air. The
motors have built in VFDs that accept a 2 to 10vdc signal from
the EXCB. This 2 to 10vdc signal is used by the VFD to determine the speed to run the motor at (0 to 100%). Some ERV
models are equipped with multiple outside air and/or exhaust
air fans. The additional motor’s signal is parallel off the first
motor through the coupling signal plug. Motor status switches
are also paralleled for additional motors.
Each motor is capable of diagnosing problems within the motor to provide fan status. The fan status switches are built into
each motor and provide a feedback to the EXCB if a problem is
detected. The feedback signal is a discrete input that is normally open, when closed the EXCB will initiate the motor status
alarm.
MODULATING OUTSIDE AIR DAMPER
ERV units include a factory-installed modulating outside air
damper. This damper is controlled in parallel with the modulating intake fan(s). This damper adds static to the outside air and
will be open to the same percentage as the outside air fan(s) is
running. The modulating outside air damper will also close in
the unoccupied mode to prevent unwanted air from being introduced to the rooftop unit.
EnergyX Options and Accessories
The modulating ERV has several optional factory-installed options and field-installed accessories: Frost Protection, Economizer, Wheel Motor Status, Filter Maintenance, horizontal
adaptor curb, building pressure sensor, and Outside Air Tempering Kit. Refer to Table 35 for where these options wire into
the EXCB.
ECONOMIZER DAMPER (FACTORY-INSTALLED ONLY)
The economizer damper is a factory-installed option that pro-
vides a wheel bypass damper. This damper is controlled by the
base unit rooftop as an economizer for the purpose of free cooling. The damper is installed adjacent to the ERV wheel to allow outside air to flow through it when opened instead of the
wheel. The ERV’s outside air fan(s) will run as this damper is
opened to allow proper airflow.
FROST PROTECTION (FACTORY-INSTALLED ONLY)
Frost protection is a factory-installed pressure sensor device
which senses a differential pressure across the wheel. This occurs if frost builds up on the wheel. The sensor closes its contact when the pressure differential is greater than the setpoint.
When the EXCB reads the contact closer it will activate defrost
mode. The setpoint is a dial on the sensor, is adjustable from
0.2 to 2.0 in.wg, and is factory preset to 2.0 in.wg. Changing
this setting may cause false signal causing defrost mode when
not needed.
WHEEL MOTOR STATUS (FIELD-INSTALLED ONLY)
The wheel motor status accessory can be installed in the field
and consists of a wheel motion proxy sensor and a relay. The
wheel motion sensor is aimed at the wheel to detect rotation. If
the wheel does not rotate at the appropriate speed the sensor
will open causing the rotation monitor relay to close a contact
to initiate the wheel status alarm. The motion sensor is factory
set at the highest speed (clockwise until stop) and should not be
changed. Refer to the troubleshooting section for details on the
alarms.
FILTER MAINTENANCE (FIELD-INSTALLED ONLY)
Filter maintenance consists of two field-installed pressure sen-
sor devices which sense differential pressure across the ERV
filters. This occurs if dirt builds up on the filters. There is a
separate pressure sensor for each filter (outside air and exhaust
air). The sensor closes its contact when the pressure differential
is greater than the setpoint. The sensors are wired in parallel, so
when the EXCB reads a contact closer from either sensor it
will activate the filter alarm. The setpoint is a dial on the sensor, is adjustable from 0.2 to 2.0 in.wg, and is factory preset to
2.0 in.wg. Changing this setting may cause false signal causing
false dirty filter alarms.
HORIZONTAL TRANSITION CURB (FIELD-INSTALLED
ONLY)
EnergyX
requires horizontal return then a horizontal transition curb must
be used. Units cannot be field converted to horizontal supply.
To accomplish horizontal supply a horizontal transition curb
must be used.
units must receive vertical return. If the application
SERVICE AND MAINTENANCE
EnergyX System Cleaning
WHEEL AND SEGMENT CLEANING
Wheel cleaning periodicity is application dependent. Field ex-
perience shows that offices, schools and other “clean” environments will often go 10 years before any build up of dust and
dirt is noticed. Other applications such as restaurants, casinos
and factory environments may experience fairly rapid build-up
of contaminants and may require multiple cleanings per year to
maintain airflow and recovery efficiencies.
All air-to-air energy recovery devices will become dirty over
time, even with well-maintained filtration. Proper filtration usage and changes will improve the life of the wheel transfer segments. Once the wheel is exposed to oils, tars or greases in either the supply or exhaust air streams, these pollutants deposit
on the rotary surface which then become “sticky” and begin to
attract and hold the dust particles that previously passed thru
the wheel. Over time this particle build up can lead to blocked
airflow passages, loss of recovery, excessive pressure drop
through the wheel and loss of energy savings.
1.Follow steps for wheel and segment removal to remove
the affected energy transfer matrix segments. (For onepiece wheels 25 inches in diameter and smaller, remove
the entire wheel from the cassette.)
2.Gently brush the wheel face to remove loose accumulated
dirt.
3.Wash the segments with a non-acid based (evaporator) coil
cleaner or alkaline detergent solution. Non-acid based coil
cleaner such as KMP Acti-Clean AK-1 concentrate in a
5% solution has been demonstrated to provide excellent
results. DO NOT use acid based cleaners, aromatic sol-
vents, temperatures in excess of 170°F or steam. Damage
to the wheel will result.
4.Soak the wheel and/or segments in the cleaning solution
until all grease and tar deposits are loosened. An overnight
soak may be required to adequately loosen heavy deposits
of tar and oil based contaminants.
5.Internal heat exchange surfaces may be examined by separating the polymer strips by hand. (Note: some staining of the
desiccant may remain and is not harmful to performance.)
6.After soaking, rinse the dirty solution from the wheel segments until the water runs clear.
93
7.Allow excess water to drain prior to replacing segments in
Rotation
Adjusting Screws
Feeler Gauge
To
Adjust
Hammer used
as a “stop”
the wheel. A small amount of water remaining in the
wheel will be dried out by the airflow.
FILTERS
Clean or replace at start of each heating and cooling seasons, or
more often if operating conditions require (based on filter manufacture recommendation or filter status alarm indication).
OUTDOOR-AIR INLET SCREENS
Clean screens with steam or hot water and a mild detergent at
the beginning of each heating and cooling season. Do not use
throwaway filters in place of screens.
EnergyX Component Lubrication
All component bearings are sealed and do not require lubrication.
EnergyX Wheel Drive Adjustment
The wheel motor and drives do not require adjustment. The
wheel drive pulley is secured to the drive motor shaft by a set
screw. The set screw is secured with removable locktite to prevent loosening. Annually confirm set screw is secure. The
wheel drive belt is a urethane stretch belt designed to provide
constant tension throughout the life of the belt. Inspect the
drive belt annually for proper tracking and tension. A properly
tensioned belt will turn the wheel immediately after power is
applied with no visible slippage during start-up.
EnergyX Wheel Air Seal Adjustment
Diameter seals are provided on each wheel cassette to minimize transfer of air between the counter flowing airstreams.
Follow below instructions if adjustment is needed.
1.Loosen diameter seal adjusting screws and back seals
away from the wheel surface. See Fig. 46.
2.Rotate the wheel clockwise until two opposing spokes are
hidden behind the bearing support beam.
3.Using a folded piece of paper as a feeder gauge, position
the paper between the seal and wheel surface.
4.Adjust the seal towards wheel surface until a slight friction
on the feeder gauge (paper) is detected while moving the
gauge along the length of the spoke.
5.Re-tighten adjustment screws and re-check clearance with
the feeder gauge.
Wheel and Segment Removal / Installation
The wheel and segments represent a substantial portion of the
value of the cassette therefore must be handled with care and
never be dropped. Use a suitable crate or harness to lift wheel
and segments to a roof surface, never use the shipping cartons
for this purpose. Wheel and segments may require “slight” persuasion during installation and removal but never forced or impacted with a hammer or similar tool. The wheel assembly can
be removed and installed or the wheel or segments can be removed from the assembly.
WARNING
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment dam-
age.
The weight of the wheel assembly must be supported when
the assembly is extended from the unit chassis to avoid
damage to wheel or unit.
The ERV wheel on 3 ton units is a 19 inch whole wheel assembly. ERV wheels on 4 to 25 ton units are segmented wheel assemblies. Follow the correct section below for removing and
installing specific wheels from their assemblies. To remove or
install the whole assembly, simply side in or out the assembly
noting the motor power plug.
Wheel Segment Removal / Installation
1.Turn off, lockout and tag-out electrical power to unit.
2.Open access door to the EnergyX
the unit.
3.Slide the entire wheel assembly out until the necessary
segment(s) of the wheel can be accessed. Support the
weight of the wheel assembly as necessary to avoid damage to wheel or unit.
module on back side of
WARNING
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
Weight of the installed segment will cause the wheel to ac-
celerate in rotation as segments are removed. Failure to
maintain control of the wheel rotation while installing all
segments could cause severe injury to fingers or hand
caught between revolving spokes and the bearing support
beam. The handle of a tool such as a hammer, should be inserted through spokes and above or below bearing support
beams to limit rotation of unbalanced wheel. See Fig. 47.
Fig. 46 — Diameter Seal Adjustment
Fig. 47 — Wheel Stop
94
4.Position one segment opening at the top of the cassette.
CatchPull Tab
Imbedded Stiffeners
5.Unlock and open the segment retaining brackets on both
sides of the selected segment opening. See Fig. 48.
Fig. 48 — Segment Retaining Brackets
6.Gently lift segment outward.
7.Close segment retaining latches and rotate wheel 180° to
remove next segment. Follow this pattern to remove all
segments and keep wheel balanced.
8.To install the wheel segments, hold the segment as vertically as possible and centered between spokes, insert nose
of segment downward between the hub plates. See Fig. 49.
NOTE: The face of the segment, with the imbedded stiffener (vertical support between nose and rim end of segment) must face the
motor side of the cassette. See Fig. 50.
9.Ease the segment downward until its outer rim clears the
inside of the wheel rim. Press the segment inward against
the spoke flanges.
10. Close and latch segment retaining brackets to the position
shown in Fig. 48. Make certain the retaining bracket is
fully engaged under the catch.
11. Slowly rotate, by hand, the first installed segment to the
bottom of the cassette, and then install the second segment
opposite the first. Repeat this sequence with the two
installed segments rotated to the horizontal position to balance the weight of installed segments.
12. Continue this sequence with the remaining segments as
necessary.
13. When complete, close access door and remove lockout
and tag-out to apply power to unit.
WHOLE WHEEL REMOVAL / INSTALLATION (19 INCH
WHEEL)
These wheels are secured to the shaft and bearing support
beam by a Philips head screw and hub cover. Follow the steps
below for removal and reverse for installation. See Fig. 51.
1.Turn off, lockout and tag-out electrical power to unit.
2.Open access door to the EnergyX
®
module on back side of
the unit.
3.Remove front seal assembly (pulley side of the cassette) if
present.
4.Remove belt from pulley and position temporarily around
wheel rim.
5.Remove the hub cover from the wheel.
NOTE: The wheel to shaft alignment pin under the hub cover. Insure this pin engages the notch at the end of the shaft when reinstalling the wheel.
6.Pull the wheel straight off the shaft. Handle with care.
Fig. 49 — Segment Removal
Fig. 50 — Imbedded Wheel Stiffeners (Shown for
Motor Side of Wheel Assembly)
Alignment
Pin
Hub Cover
Wheel
and Hub
Cassette
Housing/Frame
Shaft
Bearings (2)
Fig. 51 — 19 inch Wheel Mount
WHOLE WHEEL REMOVAL/INSTALLATION (25-46 INCH
WHEELS)
These wheels include the shaft and are secured to two wheel
support beams by two flange bearings with locking collars.
Follow the steps below for removal and reverse for installation.
See Fig. 52.
1.Loosen the two set screws on each to the two wheel bearings.
2.Remove belt from pulley and position temporarily around
wheel rim.
3.Remove pulley side wheel support beam with bearing, by
removing four support beam screws.
4.Pull the wheel with the shaft straight out of the motor side
wheel support beam and bearing. Handle wheel with care.
95
5.When replacing wheel be certain to tighten four bearing
Wheel,
Hub and
Shaft
Set
Screws
(2 each)
Flange
Bearings
(2)
Wheel Support Beams
set screws. Premature bearing failure can occur if not set
tightly.
Fig. 52 — 25-46 Inch Wheel Mount
Outside Air and Exhaust Air Hood Removal
OUTSIDE AIR HOOD REMOVAL
1.Turn off, lockout and tag-out electrical power to unit.
2.Remove the hood by removing the self-sealing screws
along the perimeter of the hood. See Fig. 53.
NOTE: Even after all screws have been removed from entire perimeter of hood, it will still be difficult to remove due to the gasket
applied from original installation. Take care not to damage the
gasket. If damage occurs use equivalent gasket to replace before
reattaching the hood.
3.Disconnect the green (HIGH) and yellow (LOW) tubes
attached to the quick connects located inside the ERV. Do
NOT damage the tubes.
EXHAUST AIR HOOD REMOVAL
1.Turn off, lockout and tag-out electrical power to unit.
2.Remove the hood by removing the self-sealing screws
along the perimeter of the hood.
NOTE: Even after all screws have been removed from entire perimeter of hood, it will still be difficult to remove due to the gasket
applied from original installation. Take care not to damage the
gasket. If damage occurs use equivalent gasket to replace before
reattaching the hood.
A
Fig. 53 — Outside Air Hood Removal
96
Detail “A”
High and Low
Quick Connects
Fig. 54 — Exhaust Air Hood Removal
Outside Air Motorized Damper Removal
1.Turn off, lockout and tag-out electrical power to unit.
2.Remove the outside air motorized damper access panel by
removing the self-sealing screws around the perimeter (see
Fig. 54).
NOTE: Even after all of the screws have been removed from the
panel it still may be difficult to remove due to the gasket applied
from the original installation. Take care not to damage the gasket.
If damage occurs use 9430-2300 gasket to replace before reattaching the panel.
3.Disconnect the connector labeled PL06 for the damper
motor from the wiring harness inside the air chamber of
the EnergyX
4.Slide out the outside air motorized damper by pulling it
along the track guides. See Fig. 55.
unit.
Outside Air and Exhaust Fan Replacement
OUTSIDE AIR FAN REMOVAL
1.Turn off, lockout and tag-out electrical power to unit.
2.Remove outside air hood (see procedure on page 96).
3.Remove outside air motorized damper (see procedure above).
4.Remove the lower and upper guides for the outside air
motorized damper by removing the screws along the
length of the flanges connecting them to the inside of the
ERV unit.
5.Disconnect the connector PL121, PL123 and the power
wires for the exhaust fan motor from the wiring harness
inside the air chamber of the EnergyX unit.
6.Remove the fasteners at each corner of the outside air fan
that secure the outside air fan front panel to the dividing
wall by access through the hood opening of the ERV. See
Fig. 56.
NOTE: See instructions for removing the wheel and supply filters
if more room is needed to access the outside air fan through the
door for better maneuverability.
7.Remove the four bolts holding the front fan panel onto the
rest of the outside air fan assembly. Completely remove
this panel from the ERV.
NOTE: Tilt the fan assembly front panel to fit it through the hood
opening.
8.Pull the outside air fan out through the hood opening. See
Fig. 57.
NOTE: Tilt the fan assembly to fit its back panel through the
opening in the dividing wall.
9.Repeat Steps 6, 7, and 8 to remove the second fan.
97
Fig. 55 — Outside Air Motorized Damper Removal
Outside
Air Damper
Access Panel
Motorized
Outside Air
Damper
Detail “A” Outside Air Fan Assembly
Remove Bolts: 4 - Places
Outside Air
Fan Assembly,
see Detail A
(access panel
not shown)
Remove Fasteners: 4 - Places
Fig. 56 — Remove Fasteners from Corners of Outside Air Fan Assembly
98
Fig. 57 — Outside Air Fan Removal
EXHAUST FAN REMOVAL
1.Turn off, lockout and tag-out electrical power to unit.
2.Remove the exhaust fan access panel by removing the
self-sealing screws around the perimeter (see Fig. 57).
NOTE: Even after all of the screws have been removed from the
panel it still may be difficult to remove due to the gasket applied
from the original installation. Take care not to damage the gasket.
If damage occurs use 9430-2300 gasket to replace before reattaching the panel.
3.Open the door to the EnergyX unit in order to gain access
to the exhaust fan front panel.
NOTE: See instructions for removing the wheel and exhaust filters if more room is needed to access the exhaust fan front panel.
4.If installed, remove the exhaust motorized damper.
5.Remove the fasteners around the perimeter of the exhaust
fan that secure the exhaust fan front panel to the dividing
wall by access through the door of the unit. See Fig. 58.
6.Disconnect connectors PL120 and PL122 as well as the
power wires for the e xhaust fan motor from the wiring
harness inside the air chamber of the EnergyX unit.
7.Remove the exhaust fan by moving it back and then out
the side of the unit through the exhaust motorized damper
access panel. See Fig. 59.
8.Repeat steps 5, 6, and 7 to remove the second exhaust fan
on size 20, 24, and 28 models.
99
Fig. 58 — Exhaust Fan Assembly - Fastener Locations
Detail “A” Exhaust Fan Assembly
secured to Dividing Wall
Remove Fasteners: 8 - Places
100
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.