Page 1

50GL
HEATING & COOLING
with Puron® (R-410A) Refrigerant
Single Package Electric Cooling Units
Visit www.camer.com
Installation, Start-Up, and Operating Instructions
Sizes 024-060
NOTE: Read the entire instruction manual before starting the
installation.
Index Page
SAFETY CONSIDERATIONS ................................................... l
RULES FOR SAFE INSTALLATION AND OPERATION.I-4
GENERAL ................................................................................ 4
RECEIVING AND INSTALLATION .................................. 4-10
Step 1 -- Check Equipment ....................................................... 4
IDENTIFY UNIT ...................................................................... 4
INSPECT SHIPMENT ............................................................. 4
Step 2 -- Provide Unit Support ................................................. 4
ROOF CURB ............................................................................ 4
SLAB MOUNT ......................................................................... 4
GROUND LEVEL .................................................................... 4
Step 3 -- Field Fabricate Ductwork .......................................... 4
Step 4 -- Provide Clearances ..................................................... 4
Step 5 -- Rig and Place Unit ...................................................... 4
INSPECTION ............................................................................ 4
INSTALLATION .................................................................. 4-6
Step 6 -- Connect Condensate Drain ........................................ 6
Step 7 -- Install Duct Connections ........................................ 6-8
CONFIGURING UNITS FOR DOWNFLOW (VERTICAL)
DISCHARGE .............................................................................. 7-8
Step 8 -- Install Electrical Connections .............................. 8-10
HIGH-VOLTAGE CONNECTIONS .................................. 8-10
STANDARD CONNECTION ................................................ 10
SPECIAL PROCEDURES FOR 208-V OPERATION ......... 10
CONTROL VOLTAGE CONNECTIONS ............................ 10
TRANSFORMER PROTECTION ......................................... 10
PRE-START-UP ......................................................................... I 1
START-UP ............................................................................. 11-14
MAINTENANCE .................................................................. 15-20
TROUBLESHOOTING ............................................................. 22
START-UP CHECKLIST ......................................................... 23
NOTE TO INSTALLER -- Before the installation, READ THESE
INSTRUCTIONS CAREFULLY AND COMPLETELY. Also,
make sure the User's Manual and Replacement Guide are left with
the unit after installation.
SAFETY CONSIDERA_ONS
Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified personnel should install, repair, or service
air-conditioning equipment.
Untrained p_rsonnel can perform basic maintenance functions of
cleaning coils and filters. All other operations should be performed
by trained service personnel. When working on air-conditioning
equipment, observe precautions in the literature, tags and labels
attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unhrazing operations. Have fh'e extinguisher
available for all brazing operations. Consult a qualified installer or
service agency for information or assistance. The qualified in-
staller or agency must use only factory-authorized kits or acces-
sories when modifying this product.
Before performing service or maintenance operations on
system, turn off power to unit. Turn off accessory heater
power switch, if applicable. Electrical shock can cause
serious injury or death.
Puron (R-410A) systems operate at higher pressures than
standard R-22 systems. Do not use R-22 service equipment or
components on Puron (R-410A) equipment. Ensure service
equipment is rated for Puron (R-410A).
RULES FOR SAFE INSTALLATION AND OPERATION
Recognize safety information. This is the safety-alert symbol z_ •
When you see this symbol in instructions or manuals, be alert to
the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION,
IMPORTANT, and NOTE. These words are used with the safety-
alert symbol. DANGER identifies the most serious hazards which
will result in severe injury or death. WARNING signifies a hazard
which could result in serious injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE and IMPORTANT
are used to highlight suggestions which will result in enhanced
installation, reliability, or operation.
Fig. 1--Model 50GL
C99064
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 101 Catalog No. 565-013 Printed io U.S.A, Form 50GL-ISI Pg 1 6-00 Replaces: New
Page 2

1463]
883
i) 48]
I
249 6 _BSO S 249 6
[9 831 121 {7) 1983]
REARVIEW TOPVIEW
REQ'D CLEARANCES FOR OPERATION AND SERVICING. in. (ram)
Evaporator col( access side .................. 36 (914)
Power entry side (except for NEC requirements) ......... 36 (914)
Unit top .......................... 48 [1219)
Side opposite ducts ..................... 36 (914)
Duct panel ........................ 12 [304.8)*
*Minimum distances: If unit is placed less than 12 in. (304•8 ram) from wall
system, then the system performance may be compromised.
LEGEND
CG - Center of Gravity
COND - Condenser
EVAP - Evaporator
NEC - National Electrical Code
REQ'D - Required
Note: Dimensions are in in. [rnm)
(4T.oo]
t
1193g
REG'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (ram)
Top of unit ......................... 14 (355.6)
Duct side of unit ....................... 2 (50.8)
Side opposite ducts ..................... 14 (355.6)
Bottom of unit ....................... 0.50 [12.7)
Flue panel ......................... 36 (914.4)
NEC REQ'D CLEARANCES. in. (ram)
Between units, power entry side .............. 42 (10_6.8)
Unit and ungrounded surfaces, power entry side ......... 36 (914)
Unit and block or concrete wails and other grounded
surfaces, control box side ................. 42 (1066.8)
22 2
UNn"
50GL024
50GL030
50GL036
_LPleE,S0R BL_,R GA,,EC:I0,
FRONTVIEW
Fig. 2_0GL024-036 Unit Dimensions
ELECTRICAL CHARACTERISTICS
208/230-1-60 270 122.5
208/230-1-60, 208/230-3-60 291 132.0
20_11-_50, 208/230-3-60, 460-3-60 2g9 135.6
UNIT WEIGHT
Ib kg
uNrr HEIGHT
IN. (MM]
mA"
37,02 [940.3]
39.02 [99t .1]
35,02 [889.5]
14 81)
RIGHT 51DE VIEW
CENTER OF GRAVITY
IN. [MM]
X Y
18.5 [469.91 14.5 [368.31
19.5 [495.3] 15.5 [393.7}
19.5 [495.3] 15.3 [387.4}
C00064
Z
16.0 1406.4]
17.6 [447.0]
16.5 [41g.11
Page 3

402 _3]
•-MHHIIHJ
SUPPL+ R[TUR_
D+_[ bVCT
OPENING OPENING
I i k
[4 63]
88 3 --
{3 48i
113 831 113 _ll 113 331
- 347 3
REARVIEW
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
EVAR COIL ACCESS SIDE .............................................................. 36.00 [914.0]
POWER ENTRY SIDE ...................................................................... 36.00 [914.0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP ......................................................................................... 36.00 [914.0]
SIDE OPPOSITE DUCTS ................................................................ 36.00 [914.0]
DUCT PANEL ................................................................................... 12.00 [304.8] *
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 [304.8] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.
in. [ram]
C01L
TOP VIEW
REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
TOP OF UNIT ................................................................................... 14.00 {355.6]
DUCT SiDE OF UNiT ........................................................................ 2.00 [50.8]
SIDE OPPOSITE DUCTS ................................................................ 14.00 [355.6]
RO]-i-OM OF UNIT ............................................................................. 0.50 [12.7]
ELECTRIC HE_,T PANEL ................................................................. 36.00 [914.4]
NEC. REQUIRED CLEARANCES.
BETWEEN UNITS, POWER ENTRY SIDE .................................... 42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE ...36.00 [914.0]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE ......................... 42.00 [1066.8]
MILLIMETERS (IN.]
in. (rnm]
UNIT
50GL042
50GL048
50GL060
[5 61_
RIGHT SIDE VIEW
Fig. 3_50GL042-060 Unit Dimensions
ELECTRICAL CHARACTERISTICS IN, [MM] IN. [MM]
208/230-1_o0, 208/230-3-60. 460-3-60 321 146 38.98 [990.2] 20.5 [520.7] 16.8 [425.5]
20_-230-1,.60, 208/230-3_0, 460.-3-60 326 148 38.98 [990.2} 19.5 [495.3] 17.6 [447.6]
208F230-1-60, 208/230-3-60, 460-3-60 399 181 42.98 [1091.1] 20.5 [520.7] 16.2 [412.8]
UNIT WEIGHT UNIT HEIGHT CENTER OF GRAVITY
Ib kg "A" X Y
3
C00065
Z
16.6 [421,6 I
18.0 [487.2]
17.6 [447.0]
Page 4

The power supply (volts, phase, and hertz) must correspond to that
specified on unit rating plate.
The electrical supply provided by the utility must be sufficient to
handle load imposed by this unit.
This installation must conform with local building codes and with
NEC (National Electrical Code) and NFPA 70. NFPA 54/ANSI
Z223.1 latest revision, and NFGC (National Fuel Gas Code). Refer
to provincial and local plumbing or w_ste water codes and other
applicable local codes.
Approved for outdoor installation on wood flooring or on class A.
B or C roof covering materials.
These instructions cover minimum requirements and conform to
existing national standards and safety codes. In some instances,
these instructions exceed certain local codes and ordinances,
especially those that may not have kept up with changing residen-
tial construction practices. We require these instructions as a
minimum for a safe installation.
GENERAL- The 50GL units are fully self-contained, and de-
signed for outdoor installation (See Fig. 1). See Fig. 2 and 3 for
unit dimensions. All unit sizes have discharge openings for both
horizontal and downflow configurations, and are facto_ shipped
with all duct openings covered. Units may be installed either on
a rooftop, ground-level cement slab, or directly on the _a'ound if
local codes permit. See Fig. 4 for roof curb dimensions.
RECEIVING AND INSTALLATION
Step 1--Check Equipment
IDENTIFY UNIT--The unit model number and serial number
are stamped on unit identification plate. Check this information
against shipping papers and job data.
INSPECT SHIPMENT -- Inspect for shipping damage while unit
is still on shipping pallet. If unit appears to be damaged or is torn
loose from its anchorage, have it examined by transportation
inspectors before removal. Forward claim papers directly to
transportation company. Manufacturer is not responsible for any
damage incurred in transit. Check all items against shipping fist.
Immediately notify the nearest Carrier Air Conditioning office if
any item is missing. To prevent loss or damage, leave all parts in
original packages until installation.
Step 2--Provide Unit Support
ROOF CURB -- Install accessory roof curb in accordance with
instructions shipped with curb (See Fig. 4 for roof curb dimen-
sions). Install insulation, cant strips, roofing, and flashing. Duct-
work must be attached to curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical
for a watertight seal. Install gasketing material supplied with the
roof curb. Improperly applied gasketing can also result in air leaks
and poor unit performance. Curb should be level to within 1/4 in.
(See Fig. 6). This is necessary for unit drain to function properly.
Refer to accessory roof curb installation instructions for additional
information as required.
SLAB MOUNT-- Place the unit on a solid, level concrete pad
that is a minimum of 4 in. thick with 2 in. above grade. The slab
should extend 2 in. on sides of the unit. Do not secure the unit to
the slab except when required by local codes.
GROUND LEVEL-- If local codes permit, the unit can be placed
directly on the ground. Prepare a level gravel foundation for proper
drainage.
Step 3_Field Fabricate Ductwork
Secure all ducts to roof curb and building structure on vertical
discharge units. Do not connect duct_vork to unit. For horizontal
applications, unit is provided with flanges on the horizontal
openings. All ductwork should be secured to the flanges. Insulate
and weatherproof all external ductwork, joints, and roof openings
with counter flashing and mastic in accordance with applicable
codes.
Ducts passing through an unconditioned space must be insulated
and covered with a vapor barrier. If a plenum return is used on a
vertical unit, the return should be ducted through the roof deck to
comply with applicable fire codes. A minimum clearance is not
required around ductwork. Cabinet return-air static shall not
exceed -.25 in. wg.
Step 4_Provide Clearances
The required minimum operating and service clearances are shown
in Fig. 2 and 3. Adequate ventilation and condenser air must be
provided.
compressor life.
The condenser fan draws air through the condenser coil and
discharges it through the top fan grill. Be sure that the fan
discharge does not recircalate to the condenser coil. Do not locate
the unit in either a corner or under an overhead obstruction. The
minimum clearance under a partial overhang (such as a normal
house overhang) is 36-in. above the unit top. The maximum
horizontal extension of a partial overhang must not exceed 48 in.
Do not place the unit where water, ice, or snow from an overhang
or roof will damage or flood the unit. Do not install the unit on
carpeting, tile. or other combustible materials.
Step S--Rig and Place Unit
Rigging and handling of this equipment can be hazardous for many
reasons due to the installation location (roofs, elevated structures,
etc.)
Only trained, qualified crane operators and ground support staff
should handle and install this equipment.
When working with this equipment, observe precautions in the
literature, on tags, stickers and labels attached to the equipment,
and any other safety precautions that might apply.
Follow all applicable safety codes. Wear safety shoes and work
gloves.
INSPECTION -- Prior to initial use, and at monthly intervals, all
rigging brackets and straps should be visually inspected for any
damage, evidence of wear, structural deformation, or cracks.
Particular attention should be paid to excessive wear at hoist
booking points and load support areas. Brackets or straps showing
any kind of wear in these areas must not be used and should be
discarded.
INSTALLATION
1. Remove unit from shipping carton. Leave top shipping skid on
the unit as a spreader bar to prevent the rigging straps from
damaging the unit. If the wood skid is not available, use a
spreader bar of sufficient length to protect unit from damage.
2. Position the lifting bracket assembly around the base of the
unit. Be sure the strap does not twist.
3. Place each of the 4 metal lifting brackets into the handholds in
the composite pan.
4. Thread lifting bracket strapping around bottom perimeter of
unit as follows:
a. Open lever of tension buckle (ratchet type).
b. Feed strapping through tension buckle (See Fig. 8).
4
Page 5

463/16
44 5/16
A
END
(2)
DECK PAN (INSULATED)
SIDE PANEL--
SUPPORT RIB(S) 0.75' --{[/
SEAL STRIP
(FACTORY SUPPLIED)
COUNTER FLASHING - =
(FIELD SUPPLIED) •
ROOFING FELT
(FIELD SUPPLIED)
CANT STRIP --
(FIELD SUPPLIED)
SUPPORTA(2)
SIDE
- (2)
T BASE PAN
3.0" BOTTOM SUPPLY 4.0"
NAILER
_INSULATION
(FIELD SUPPLIED)
1
END VIEW
A99320
ROOFING MATERIAL
(FIELD SUPPLIED)
50GL UNIT SIZE ODS CATALOG ORDERING NO. A B C D
024-036
ROOF CURB
042-060
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied as required to unit being installed.
3. Dimensions in I ) are in millimeters.
4. Roof curb is made of 16 gage steel.
5. Table lists only the dirnensio_s per DOS Catalog Ordering Number that have changed.
6. Attach ductwork to curb (flanges of duct rest on curb).
7. Insulated panels: 1-in. thick fiberglass 1 Ib density,
CPRFCURB006A00 8 1203] 11-27/32 [301] 30-5/8 [T78] 28-3/4 [7301
CPRFCURB007A00 14 [356] 11-27/'32 [30t] 30-5/8 [778] 28-3/4 [730|
CPRFCURB008A00 8 [203] 15-27/32 [402] 42-1/8 [1070] 40-1/4 [1022]
CPRFCURBOO£'A00 14 [356] 15-27/'32 [402] 42-1/8 [1070] 40-1/4 [1022]
IN. [MM] IN, [MM] IN. [MM] IN, [MM]
Fig. &--Roof Curb Dimensions
5
A99340
Page 6

RETURN SUppLY
AIR AIR III
OPENING OPENING illl
/ A°OHOLO
IIII
FII
I II
_N
H
HOOK
I
1
_ EVAP COiL COND C_L
3____% 2--_
C99014
Fig. 5--Slab Mounting Details
DUCTS
5_AL STRIp MUST BE iN
PLACE BEFORE p_ACING
UNfT C_ ROOF CURB
C99015
pLACE RIGGING STRAPS IN
BASEPAN SLOT (BELOW HANDHOLDS)
BEFORE RK3GING
j{48 _8")
Fig. 6_Suggested Rigging
SIZE
024 292 132.5 18.5 469,9 14.50 3683
030 313 142.5 19.5 4953 15.50 393.7
036 321 145.6 19.5 495.3 15.25 387.4
042 343 155.6 203 520.7 15,75 425.5
048 348 157.9 19,5 405.3 17.62 447.8
060 421 191.0 20.5 520.7 16.25 412.8
MAXIMUM WEIGHT A B
Ib kg in. rnm in. rnm
MAXIMUMALLOWABLE
DIFFERENCE/in.)
B A-B B-C A-C
1/4 1/4 1/4
L;9_6b
Fig. 7--Unit Leveling Tolerances
c. Pull strapping through tension buckle unit taut.
d. Snap lever down 1o lock strap in tension buckle. To release
strapping, squeeze safety latch, lift lever, and pull webbing
outward.
5. Tighten the tension buckle until it is taut. Lifting brackets
must be secure in the handholds.
6. Attach field-supplied clevis or hook of sufficient strength to
hole in the lifting bracket (See Fig. 9).
7. Attach the 2 safety straps directly to the clevis or hook at the
4 rigging brackets. DO NOT attach the safety straps to the
lifting brackeLs (See Fig. 9).
FEED _
e99087
Fig. 8_Belt Threading
CETAIL A
SCALE 025O
P_ND HOLES AND INSTALL lie DOWN STRAp
/SE E DETAIL A
AP_JN D PERIMETER OF UNIT AND THROUGH
_ACE IN BRACKET ASSEMBLY
C99066
Fig. 9---Lifting Point
8. Position lifting point directly over the unit's center of gravity.
9. Lift unit. When unit is directly over the roof curb, remove the
2 safety straps. Lower the equipment onto the roof curb.
Step 6---Connect Condensate Drain
NOTE: When installing condensate drain connection be sure to
comply with local codes and restrictions.
Model 50GL disposes of condensate water through a 3/4 in. NPT
fining which exits through the base on the evaporator coil access
side (See Fig. 2 and 3 for location).
Condensate water can be drained directly onto the roof in rooftop
installations (where permitted) or onto a gravel apron in ground-
level installations. Install a field-supplied condensate trap at end of
condensate connection to ensure proper drainage, Make sure that
the outlet of the trap is at least 1 in. lower than the drainpan
condensate connection to prevent the pan from overflowing (See
Fig. 10). When using a gravel apron, make sure it slopes away
from the unit.
Connect a drain tube using a minimum of 3/4 -in. PVC or 3/4 -in.
copper pipe (all field-supplied) at the outlet end of the 2-in. trap.
Do not undersize the tube. Pitch the drain tube downward at a
slope of at lemst one in. for every 10 fi of horizontal run. Be sure
to check the drain tube for leaks. Prime trap at the beginning of the
cooling sea.son start-up.
Step 7--Install Duct Connections
The unit has duct flanges on the supply- and return-air openings on
the side and bottom of the unit. For downshot applications the
ductwork can be connected to the roof curb ISee Pig. 2 and 3 for
connection sizes and locations).
Page 7

Table 1--Physical Data -- Unit 50GL
UNIT SIZE
NOMINAL CAPACITY (ton)
OPERATING WEIGHT (Ib)
COMPRESSOR
REFRIGERANT (R-410A)
Quantity (Ib)
REFRIGERANT METERING DEVICE
HIGH-PRESSURE SWITCH (psig)
LOSS-OF-CHARGE/LOW-PRESSU RE SWITCH
(Liquid Line) (psig)
Cutom
Reset (Auto)
RETURN-AIR FILTERS (in.)*
Throwaway
• Requiredfilter sizes shown are based on the largerofthe ARI (Air CondiUoning and RefrigerationInstitute) ratedcooling airfloworthe heatingairflowvelocity of 300
ftJminfor throwaway type or 450 ft/min for high-capacity type. Airfilter pressure drop for ncn-standardfilters must notexceed 0.08 in. wg.
Orifice ID (in.)
CONDENSER COIL
Rows...Fins/in.
Face Area (sq R)
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Motor Hp (Rpm)
EVAPORATOR COIL
Rows...Fins/in.
Face Area (sq ft)
EVAPORATOR BLOWER
Nominal Airflow (Cfm)
Size (in.)
Motor (hp)
Cutout
Reset (Auto)
O24
2
27O
50 I ,5 I
Accurater_ Piston
.057 .057
1...17 1,.,17
10.9 12.7
2350 2350
22 22
1/8(825) 1/8 (825)
3...15 3...15
3,7 3.7
800 1000
10x10 10x10
1/4 1/4
030 036 042 048
2-1/2 3 3-1/2 4
291 299 321 326
SCrOll
00 I ,0 r g5
.065 070 ,073 .086
2...17 2,..17 2,..17 2...17
9.1 12.3 12.3 16.4
2350 2350 3300 3300
22 22 22 22
1/8 (825) 1/8 (825) 1/4 (1100) 1/4 (1100)
3..,15 3...15 4,-15 4...15
3.7 4.7 4.7 4.7
1200 1400 1600 1750
10xi0 11x10 11x10 1ix10
1/2 3#4 3/4 1
610 _+15
420+_25
20_+5
45+10
06O
5
399
10.0
x ,!2ox o×,12o 4xl12OX3OXl124x ox,124x OXl
1" MIN.
TRAP
oo,,E,÷
2" MIN.
C99013
Fig. 10--Condensate Trap
IMPORTANT: Use flexible connectors between ductwork and
unit to prevent transmission of vibration. Use suitable gaskets to
ensure weathertight and airtight seal. When electric heat is
installed, use fire proof canvas (or similar heat resistant material)
connector between ductwork and unit discharge connection. If
flexible duct is used, insert a sheet metal sleeve inside duct. Heat
resistant duct connector (or sheet metal sleeve) must extend 24-in.
from the unit connections flanges into the ductwork.
Table 2 -- Minimum Airflow for Safe Electric Heater
Operation (Cfm)
SIZE
0,41000o 1o42 o
800 1000 1200 1400 1600 2000
CONFIGURING UNITS FOR DOWNFLOW (VERTICAL) DIS-
CHARGE '
result.
1. Open all electrical disconnects before starting any service
work.
2. Remove side duct covers to access bottom return and supply
knock out covers (See Fig. 12).
3. To remove supply and return duct covers, break front and right
side connecting tabs with a screwdriver and a hammer. Push
cover down to break rear and left side tabs.
4. If unit ductwork is to be attached to vertical opening flanges
on the unit basepan (jackstand applications only), do so at this
time. Collect ALL screws that were removed. Do not leave
screws on rooftop as permanent damage to the roof may occur.
5. It is recommended that the hasepan insulation around the
perimeter of the vertical return-air opening be secured to the
basepan with aluminum tape. Applicable local codes may
require aluminum tape to prevent exposed fiberglass.
6. Cover both horizontal duct openings with the duct covers
shipped on the unit from the factory. Ensure opening is air-and
watertight.
7. After completing unit conversion, perform all safety checks
and power up unit.
NOTE: The design and installation of the duct system must be in
accordance with the standards of the NFPA for installation of
nonresidence-type air conditioning and ventilating systems, NFPA
90A or residence-type, NFPA 90B: and/or local codes and
ordinances.
Adhere to the following criteria when selecting, sizing, and
installing the duct system:
8. Select and size ductwork, supply-air registers, and return-air
grilles according to American Society of Heating, Refrigera-
tion and Air Conditioning Engineers (ASHRAE) recommen-
dations.
9. Use flexible transition between rigid ductwork and unit to
prevent transmission of vibration. The transition may be
screwed or bolted to duct flanges. Use suitable gaskets to
ensure weathertight and airtight seal.
Page 8

10.All unitsmusthavefield-supplied filters or accessory filter
rack installed in the return-air side of the unit. Recommended
sizes for filters are shown in Table 1.
11. Size all ductwork for maximum required airflow (either
heating or cooling) for unit being installed. Avoid abrupt duct
size increases or decreases or performance may he affected.
12. Adequately insulate and weatherproof all ductwork located
outdoors. Insulate ducts passing through unconditioned space,
and use vapor barrier in accordance with latest issue of Sheet
Metal and Air Conditioning Contractors National Association
(SMACNA) and Air Conditioning Contractors of America
(ACCA) minimum installation standards for heating and air
conditioning systems. Secure all ducts to building structure.
13. Flash, weatherprooL and vibration-isolate all openings in
building structure in accordance with local codes and good
building practices.
I-
u
7 i !/
SUPPLY RETURN
DUCT DUCT
OPENING OPENING
Fig. 11---_upply and Return Duct Opening
VERTICALDUCT COVERS
Fig. 12--Vertical Duct Cover Removed
C99011
C99012
Step 8--Install Electrical Connections
Y:I |*?I:ITR]R [_
The unit cabinet must have an uninterrupted, unbroken
elecWical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground may
consist of an electrical wire connected to the unit ground lug
in the control compartment, or conduit approved for electrical
ground when installed in accordance with NEC (National
Electrical Code) ANSI/ NFPA (latest editionl (in Canada,
Canadian Electrical Code CSA [Canadian Standards Associa-
tion] C22.1) and local electrical codes. Failure to adhere to
this warning could result in personal injury or death.
W_P_.TLI__d[o]Ti
Failure to follow these precautions could result in damage to
the unit being installed:
1. Make all electrical connections in accordance with NEC
ANSI/NFPA(Iatest edition) and local electrical codes gov-
erning such wiring. In Canada. all electrical connections
must be in accordance with CSA standard C22.1 Canadian
Electrical Code Part l and applicable local codes. Refer to
unit wiring diagram.
2. Use only copper conductor for connections between
field-supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE,
3. Be sure that high-voltage power to unit is within operating
voltage range indicated on unit rating plate.
4. Do not damage internal components when drilling through
any panel to mount electrical hardware, conduit, etc. On
3-phase units, ensure phases are balanced within 2%.
Consult local power company for correction of improper
voltage and/or phase imbalance.
HIGH-VOLTAGE CONNECTIONS- The unit must have a
separate electrical service with a field-supplied, water-proof,
disconnect switch mounted at, or within sight from, the unit. Refer
to the unit rating plate for maximum fuse/circuit breaker size and
minimum circuit amps (ampacity) for wire sizing (See Table 3 for
electrical data).
The field-supplied disconnect switch box may be mounted on the
unit over the high-voltage inlet hole when the standard power and
low-voltage entry points are used (See Fig. 2 and 3 for acceptable
location).
See unit wiring label and Fig. 13 for reference when making high
voltage connections. Proceed as follows to complete the high-
voltage connections to the unit.
Single phase units:
1. Run the high-voltage (LI, L2) and ground leads into the
control box.
2. Connect ground lead to chassis ground connection.
3. Connect LI to pressure lug connection 11 of the compressor
contactor.
4. Connect L2 to pressure lug connection 23 of the compressor
contactor.
Three phase units:
1. Run the high-voltage (LI, L2, L3) and ground leads into the
control box.
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the lines side
of the contactor.
Page 9

Table 3--Electrical Data
UNIT 50GL
SIZE
O24
V-PH-HZ RANGE
206/230-1-60 137 253
VOLTAGE
Min Max
208/230-1-60 187 253
03O
206/230-3-60 187 253
208/230-1-60 187 253
036
208/230-3-60 187 253
460-3-60 414 506
206/230-1-60 187 253
042
206/230-3-60 187 253
460-3_0 414 506
208-230-1-60 187 253
O48
208/230-3-60 187 253
460-3-60 414 506
206/230-1-60 187 253
06O
208/330-3-60 187 253
460-3-60 414 506 9.0
• Heater cap_city (KW) based on heater voltage of 206v, 240v, & 480v. If power distribution voltage to unit varies from rated heater voltage, heater KW will vary
accordingly.
COMPRESSOR OFM IFM ELECTRIC HEAT
RLA LRA FLA FLA Nominal kW*
-/-
13.5 61 .O 0.8 2.0 3.8/5.0
7.5/10.0
18.1/20.8 25.1/28.5 25/30
36.1/41.7 47.6/54.6 50/60
-/.
14.7 73.0 0.6 2.1 3.8/5.0
7.5/100
-/-
9.6 63.0 0.8 2.1 3.8/5.0
7.5/10.0
18.1/20.8 25.2/28.7 25/30
36.1/41.7 478/5.47 50/60
10.4/12.0 15.7/17.7 20/20
20.8/24.1 28.7/32.7 30/35
./-
15.4 83.0 0.8 3.6
3.8/5.0
7.5/10.0
11.3/15,6
18.1/20.8 27.1/30.5 30/30
36.1/41.7 49,6/56.6 50/60
54.2/62.5 72.2/82.6
-/-
12.2 77.0 0.8 3.6
5.1 35.0 0.8 1.9
3.8/5.0
7.5/10.0
11.3/15.0
5.0
10.0
10.4/12.0 19,7/19.7 25/25
20.8/24.1 30.6/34.6 35/35
31.3/36.1 43,6/49.6 45/50
15.0
-/-
18.6 105.0 1.6 4,1 7.5/10,0
3.8/5.0
11.3/15.0
15.0/20.0
18.1/20.8 28.2/31.2 35/35
36.1/41.7 50.3/57.2 60/60
54.2/62.5 72.8/83,3
72.2/85.3 95.4/109.3
-/-
13.8 88.6 1.6 4.1 7.5/10.0
3.8/5.0
11.3/15.0
15.6/20.0
10.4/12.0 22.2/22.2 30/30
20.6/24.1 31.2/35.2 35/40
31.3/36.1 44.2/50.2 46/60
41.6/48.0 57.1/65.1
5.0
6.3 39.0 0.9 2.0 10.0
15.0
20.0
-/-
3.8/5.0
20.5 109.0 1.6 4.1 7.5/10.0
1t .3/15.0
15.0/20.0
-/-
3.8/5.0
14.7 91.6 1.6 4.1 7.5/16.0
11.3/15.0
15.0/20.0
24.1 32.6 35
18.1/20.8 31.3/31.3 40/40
36.1/41.7 50.3/57.2 60/60
54.2/62.5 72,8/83.3
72.2/83.3 95.4/109.3
10.4/12.0 24.1/24.1 30/30
20.6/24.1 31.2/35.2 35/40
31.3/36.1 44.2/50,2 45/60
4t.7/48.1 57.1/65.1
5.0
6.5 46.0 0.9 2.0 10.0
15.0
20.0
24.1 32.6 35
-/-
27.6 158.0 1.6 6.2 7.5/10.0
3.8/8.0
11.3/15
15.6/20.0
-/-
3.8/5.0
18.1 137.0 1.6 6.2 7.5/10.0
11.3/15.0
15.0/20.0
62.0 0.9 3.2 10,0
5.0
15.0
20.0
18.1/20.8 42.3/42.3 50/50
36.1/41.7 52,g/89.6 60/60
54.2/62.5 75.4/85.9
72.2/83.3 98.0/111.9
10.4/12.0 30.4/30.4 35/35
20.8/24.1 33.8/37.8 36/40
31.3/36.1 46,6/52.9 50/60
41.6/48.0 59.7/67.7
24.1 34.1 35
POWER SUPPLY
FLA MCA Max Fuse or CRCT Breaker
-/- 19.7/19.7 25/25
*/- 21 3/21.3 25/25
-/- 14,9/14.9 20/20
-/* 23.7/23.7 30/30
-/- 19,7/19.7 25/25
- 9.1 16
6.0 9.9 15
12.0 17.4 20
16.0 24.9 25
-/- 28.2/28.2 35/35
-/- 22.2/22.2 30/30
- 10.7 15
6.0 10.7 15
12.0 17.5 20
18.0 25.1 30
*/* 31.3/31,3 40140
-/- 24.1/24.1 30/30
- 11.0 15
6.0 11.0 15
12.0 17.5 20
18.0 25.1 30
-/- 42.3/42.3 50/50
-/- 30.4/30.4 35/35
- 15.4 20
6.0 15.4 20
12.0 19.0 20
18.0 26.6 30
MOCP
80/90
80/90
100/110
60/70
80/90
100/110
60/70
°
80/90
100/125
60/70
Page 10

FLA -- Full Load Amps
LRA -- Locked RotorAmps C US
MCA -- Minimum Cimuit Amps
MOCP -- Maximum Overcurrent Protection
RLA -- Rated Load Amps
NOTES:
1. In compliance with NEC (National Electrical Code) requirements
for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse. The CGA (Canadian Gas
Association) units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table,
determine size from NEC.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percentage of voltage imbalance.
% Voltage imbalance
= 100 x max voltage deviation from avera_le voifa_e
LEGEND
average voltage
EXAMPLE: Supply voltage is 460-3-60.
A e C AB = 452 v
AC = 455 v
Average Voltage = 452 + 464 + 455
BC = 464 v
= 1371
= 457
Determine maximum deviation from average voltage.
(AB) 457 452=5v
(BC) 464 457--7v
(AC) 457 455=2v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x 7
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately. I
457
3
3
4. Connect field LI to black wire on connection 11 of the
compressor contactor.
5. Connect field wire L2 to yellow wire on connection 13 of the
compressor contactor.
6. Connect field wire L3 to Blue wire from compressor.
SPECIAL PROCEDURES FOR 208-V OPERATION
Make sure that the power supply to the unit is switched OFF
before making any wiring changes. With disconnect switch
open, move yellow wire from transformer (3/16 in.) terminal
marked 230 to terminal marked 200. This retaps transformer
to primary voltage of 208 vac. Electrical shock could cause
serious injury or death.
m
HIGH VOLTAGE r'- - - -
POWER LEADS <_co- - - -
(SEE UNIT WIRING
LABEL) _.. - - -
- - POWER
- SUPPLY
- -_- -
FIELD-SUPPLIED
GND
CONTROLBOX
LOW-VOLTAGE _ O-
POWER LF_,DS--
(SEE UNIT O-
WIRING LABEL) _o-
FUSED DISCONNECT
C-
-YE--LLYL{)" --_) "_L
_G_RN_(G_){_. _) _T_ERMAOL_TAT
RED2R2D-
-BEN--(C--)D- (_)
J
CONTROL VOLTAGE CONNECTIONS
NOTE: Do not use any type of power-stealing thermostat. Unit
control problems may result.
Use no. 18 American Wire Gage (AWG) color-coded, insulated
(35 C minimum) wires to make the control voltage connections
between the thermostat and the unit. If the thermostat is located
more than 100 ft from the unit _,as measured along the control
voltage wires), use no. 16 AWG color-coded, insulated 135 C
minimum) wires.
STANDARD CONNECTION -- Remove knockout hole located
in the electric heat panel adjacent to the service access panel (See
Fig. 2 and 31. Remove the rubber _ommet from the installer's
packet (included with unit) and install _ommet in the knockout
opening. Provide a drip loop before running wire through panel.
Run the low-voltage leads from the thermostat, through the inlet
hole. and into unit low-voltage splice box.
Locate five 18-gage wires leaving control box. These low-voltage
connection leads can be identified by the colors red, green, yellow.
brown, and white (See Fig. 10). Ensure the leads are long enough
to be routed into the low-voltage splice box (located below right
side of control box). Stripped yellow wire is located in connection
box. Route leads through hole in bottom of control box and make
low-voltage connections (See Fig. 13). Secure all cut wires, so that
they do not interfere with operation of unit.
TRANSFORMER PROTECTION- The transformer is of the
energy-limiting type. It is set to withstand a 30-sec overload or
shorted secondary condition.
SPLICEBOX
LEGEND
Field Control-Voltage Wiring
Field High-Voltage Widng
NOTE: Use blue wire for 3-phase units only.
Fig. l_-High- and Control-Voltage Connections
C99010
10
Page 11

PRE-START-UP
Failure to observe the following warnings could result in
serious injury or death:
I. Follow recognized safety practices and wear protective
goggles when checking or servicing refrigerant system.
2. Do not operate compressor or provide any electric power to
unit unless compressor terminal cover is in place and
secured.
3. Do not remove compressor terminal cover until all electri-
cal sources are disconnected.
4. Relieve and recover all refrigerant from both high and
low-pressure sides of system before touching or disturbing
anything inside terminal box if refrigerant leak is suspected
around compressor terminals.
5. Never attempt to repair soldered connection while refrig-
erant system is under pressure.
6. Do not use torch to remove any component. System
contains oil and refrigerant under pressure. To remove a
component, wear protective goggles and proceed as fol-
lows:
a. Shut off electrical power to unit.
b. Relieve and reclaim all refrigerant from system using
both high- and low-pressure ports.
c. Cut component connecting tubing with tubing cutter and
remove component from unit.
d. Carefully unsweat remaining tubing stubs when neces-
sary. Oil can ignite when exposed to torch flame.
Proceed as follows to inspect and prepare the unit for initi;
startup:
t. Remove access panel.
2. Read and follow instructions on all WARNING, CAUTIOI'
and INFORMATION labels attached to, or shipped with, uni
3. Make the following inspections:
a. Inspect for shipping and handling damages such as broke
lines, loose parts, disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections and c
unit base. Detecting oil generally indicates a refrigeraJ
leak. Leak test all refrigerant tubing connections usin
electronic leak detector, halide torch, or liquid-soap solt
tion. If a refrigerant leak is detected, see Check f_
Refrigerant Leaks section under Start-Up.
c. Inspect all field- and factory-wiring connections. Be stu
that connections are completed and tight.
d. Inspect coil fins. If damaged during shipping and handlir
carefully straighten fins with a fin comb.
Verify the following conditions:
a. Make sure that condenser-fan blade is correctly position.
in fan orifice. Leading edge of condenser-fan blade shoul
be 1/2 in. maximum from fan orifice (See Fig. 14).
b. Mal_e sure that air filter(s) is in place.
c. Make sure that condensate drain trap is filled with water I
ensure proper drainage.
d. Make sure that all tools and miscellaneous loose parts ha',
been remove,
START-UP
CHECK FOR REFRIGERANT LEAKS -- Proceed as follows t
locate and repair a refrigerant leak and to charge the unit:
1/8" MAX BETWEEN
MOTOR AND FAN HUB
MOTOR SHAFT
Fig. 14_Fan Blade Clearance
1. Locate leak and make sure that refrigerant system pressure ha._
been relieved and reclaimed from both high- and low-pressure
ports.
2. Repair leak following accepted practices.
NOTE: Replace filter drier whenever the system has been opened
for repair.
3. Charge unit with R_.IOA refrigerant, using a volumetric-
charging cylinder or accurate scale. Refer to unit rating plate
for required charge.
START UP COOLING SECTION AND MAKE ADJUST-
MENTS
F:_[O211F/I,171
Complete the required procedures given in the Pre-Start- Up
section before starting the unit. Do not jumper any safety
devices when operating the unit. Do not operate the compres-
sor when the outdoor temperature is below 40°F (unless
accessory Iow-anrbient kit is installed). Do not rapid-cycle the
compressor. Allow 5 rain between "on" cycles to prevent
compressor damage.
CHECKING COOLING CONTROL OPERATION--Start and
check the unit for proper cooling control operation as follows:
1. Place room thermostat SYSTEM switch in OFF position.
Observe that blower motor starts when FAN switch is placed
in ON position and shuts down when FAN switch is placed in
AUTO position.
2. Place SYSTEM switch in COOL position and FAN switch in
AUTO position. Set cooling control below room temperature.
Observe that compressor, condenser fan, and evaporator
blower motors start. Observe that cooling cycle shuts down
when control setting is satisfied. The evaporator fan will
continue to run for 30 sec.
3. When using an auto-changeover room thermostat, place both
SYSTEM and FAN switches in AUTO positions. Observe that
unit operates in heating mode when temperature control is set
to "call for heating" (above room temperature) and operates
in cooling mode when temperature control is set to "call for
cooling" (below room temperature).
IMPORTANT: Three-phase, scroll compressor units (50GL030-
060) are direction-oriented. These units must be checked to ensure
proper compressor 3-phase power lead orientation. If not corrected
within 5 rain. the internal protector will shut off the compressor.
Any two of the 3-phase power leads to the unit must be reversed
to correct rotation. When turning backwards, scroll compressors
emit elevated noise levels, and the difference between compressor
suction and discharge pressures may be dramatically lower than
normal.
CHECKING AND ADJUSTING REFRIGERANT CHARGE
--The refrigerant system is fully charged with R_.IOA refriger-
ant, tested, and factory-sealed.
NOTE: Adjustment of the refrigerant charge is not required
unless the unit is suspected of not having the proper R_-IOA
11
charge. The charging label and the tables shown refer to system
temperatures and pressures.
C99009
Page 12

I
SEE NOTE#2
UNIT COMPONENT ARRANGEMENT
]UlOO0# _N
5_cIION
:;]o_ 5ECl L,),_
:OMP
u s
_r_p / T F4v 3pL[ t 2 SEE #F [I:E PAGES FI:IF# THE?Hr'I_TA[ ArJE, £,IBB,'SE!
i i
[
I i
: ] ] :'l:_ _1]O BRN
Lg_I
W1_3 _RN
HRI,2 £ 3 _IS KW)_\\ -:
--_121 _E[ I -- _ --WI73 I)F.N
W16 GRN
W113 rEL_--BL<_--_-_SLk_-BL I _ -- _ .... BL;I
5
W72 _HT_ 141
-_143 PNK ---_
/-
i
I
_2 F
I
COMMON
--_-_ ]'L_ 24v FO_E_FU_;. 31U5[ 75 D_IFEE :EIpPEF ,}tIIIEIIIIZTOP<" FIlL ;FELl l±tl If r
\ <FOR H[IH IbEED [FH,OISO)IINEI:T PED
1_(10104,!060 WI_E FFIZH TEIp;3 _,ND :(TIHF r BLF Ws_ FFuH ::'
7
-- W130 BFN
24V SPLICE BOX LEI}E_IEI
• SFL 1<[ EI)II]p E0iIIF MERIT
'_ 5Pt]r:E (HAPKED) FIJ FtlSE
_TQ iNDI,:!TF IOHI!Ij:N iF IHTEBN_L FB,::_(]I}F
• El;In P TH TIIi _ ME,of A T -![ AF][J
5_[ HtAtft,
StHEM_I[,
hJ_ Wl_frJi;Ll!zm_-
611B TFAII Tp ANSFI:,p HEP
I
ACCE550g_ ELE(TFqE HEAT
FIELD EPLICE C IZOqTA( TOR
IEPMINAL (MARy[ D CAp I1_FAE [ TIZIF_
1ERHENAL (UNHAFYED I_ONP ':(Ibl!'P[S_Op !!hlNp
F_{:TORY WIPILiG CN0 IJ:(IIJF_D
! I!LD CONTgCII _QT_IN,3 hPS H]<.H FFE5511F( 5WI !l
F]ELD POWER WiFIFll} HR H[;!EF FELA ¸
,!_ _[:,C, rlPr t_P rIFT! H_ HTg¸ H[ATEF
W]PIHr IFM IM[,,II:IB FAH r_:T:B
pL/TEN1]_[ I:INL_, LF'_, LTIk¸ rPEESIIBE qWIT, H
rJo] ill [Ef[:E%ErJ[ i_fH IIIII[/,,IZB ¸ FArJ lillf
WJl IHr, i.,_ ,)IIADFI ,FI E 7_;:+11hal
tJINE :,:
I IF ,IIIF ii F _HE
[1 MU£[ L[ ;[! ;l}E[l ,_ITH 'PE tJ I) [ [ ;:t[ I _ ; _[
II 5 EI}II[ ,ALEFIT
Fr)R HEO[IJM 3rE[DID]SEOTINE,:T FED _;_E
FROM TEIR;_ ,:rlgl CONNE,LT 8LIj W[gE g_'LI__ [FM. IIT=iII,[ 1_1(,_ll:,l-'.o
Fig. 15---208/230-1-60 Wiring Diagram
12
EIID_ i _D DF FrJF_,,I:ED
'_ R 31 '_, BL, W F :E
,, • l i1[ !:H [ STI)F "zgI
lid THE; tll ,_-]A _ :(l:,L IN
IIIP TIIIE DELA¢ rE_At
I[II]]N_[ _]bE_ FI;prJ[dED ARE -L_LA ' Lib
i I
W]I BBrJ
di27 BRN
E_EN
B_N --
W7I) BPN
. r,
C_
Page 13

_,':r4 r ,J ,cE 4 ¸ d _ - _L _ _ p,
, _QI9_ EL _l i qL'
q_T[O I, r.[ r
H_F[ _ITH
HE._TEF" 'FT _ @ _ _ L
ELECT _E_T _ wL _ • _ :i, O
5,1U_ I F.,
SIZE 2 A,Jb. J_ BLI, I_P
, - E[
(t)
208/230-3-30
,::FH
1:l:4qF
A,-flES_Ip/ ___T?" -- T •
ELECT HEAT
OPTION NNL¢ ",G _MphR HTR u__ _WI _ _11
HEAIEP FTIN4q p _u
MAYlHJM WJPE _ ariF _ en HTP/
_ED _;TH T_Pt_H_ _flr b R_H T.r ' • r
L L"l h F_ ELE'T **.1 1.._..- _,N FL
20 _u SH?Wm-LE - - l_r i,'-' _ _ - ; • • •
SCHEMATIC FD_ /;; I h_
: ,i
ELFE • J _25 -FN _ELT _ -Prl ,EL_
-411 SE: :[]CI._F r f WII BP'414127 BFN
.. _ 1,a ,}RN I WI 0 BFN --
HFS L_ Lp_.
_163 2N_-- HA1 (S KWI_ X
Fm
SEE NOTE*2
:EIHMOr4
_W127
BFN --
LE,3EI 1£I
LINIT HI IIHF t]l &FF# ]l EHEHT
:,_j_[,,)C,p F_N
5_CI]ON
I-t u -
5or t o47 ,_hO
r -- rl rF I IF ",r. I,F rile I:I!:]_]IIAL WIFE:, _HKIII!HEL, ,IFE BEFLACEEI,
lu!,i]_lr_'cl I[ I!lZ- BE BFFL/. fr, ,allH fF_l 96 [El.BE Ii ,HFE OR
I E i II i EJ ,I,LEH:
L FIE[ 0 Eit [iZE C CONJ_CTOp
TEP!![hSL 'MAF_ EZI IZtP CApAC]TC Ip
s TEPtllii:L ,rlNHAP!E) ¸ r_,l[1p COHPgE_S,:IP HCIT0p TO_ II 3)_
• SFL II:F EOHiP E0U [PMEN f
_. %PI lEE 'H_C'_[[I ' F ¸l FUSE G G
•--FAI:TI:I#_ ,_[gJr]lj, ,_NO GROUNEI ENF_G[ZED [,E ENEPGIZE0
F!ELD )FMFOL ,I[F:FJIS hP'_ HIGH FgESSUPE S_]TCH
F iFI [_ : ;,Jl:[¸ ,_IP!:J(- HF¸ HEATEP I,EL_/
_l,_ Ir iI _]i ,tl; L H F HEATEF ¸
',41i IIi ]_rq [NDI)OP F_fl HI:FIe ¸
i Iii Iti , _IF it!l!_ h ]: [tJTEFFJ,',[ FFI rFi T, IF,
fllrfh[ i IH I ,; t; ¸ , lOW FFE}Z,_F[ _U]T,H
hilT TI _r_[f ! iT :r/ I_IIT[rI, IF _Zl: 141f,lt ¸
_: bL,h4 !!t JN _l E
i THFFr4rI_I-* [ i, i_ irjl_
, THEPHO_] AT Iff#[IH
I
__ I LIFE[ ir:LE rAGE FEI_ THERI4OSIAT t,fl[, ;I][18A%E_
24V POW[REFIT_t
_ i;bE 7_ EIEI#EE i IP_'H; I ONDIJCIII_5 FOR F LE I tlJ1ALLAT IIN
,1 F01: H H ,FEED IFH,[DIOCONNECT f:ED
_lrE F_II/4 !DR; _ A!IEI I:IINNEI [ BL! W[BE FGLIM ]FH.
FHI, lIED qtl _FEE0.U]D, 0NHEi I PED _[RE
FF,zIrq :DP;3 ANEI ]IIIIECI BLIJ ,,ICE FBOH [FH I - _I_H. '_ iql Ii'll i i "1--1_" L)
T_IF¸ rill{ EI_,At IEL,t/
Fig. 16--208/230-3-60 Wiring Diagram
13
/ F M
_155 BP_I
0 I T*30
CIX)(_I
Page 14

L 9E ¸:
]!., [.,
_ PR!rdAPt ,_'wJ
T
46,/_ _ W°c
TRAM - _ ......
/[ +E?%!A+,-t
hi6 I:,RH
WII3 !EL_BLF -- BLF_--BLLI --[' _ --_BLU--'CI' IKC2_WIO BPN
GRN YEL-1IW26 GRN+FEL_
C+PN _EL C,Rrl fEL
2 1
_11 BgN-
WID7 BPN
4"__
_1_-_- L_,S - - -
WTD _HT _ 'HB I_ _WI5 BRH
Wig3 PNK ] HRI (5 KW) _+_ _WI98 B_:N
- wls2 rio / _j_,.,:--/,H_ _j
--. _+j_W76 BRN
SEE NEITE#2
CDMHON
W166 C#A_ I HRlg 2 [jw,__,HF3X--_w7o B_N
r
--W!S3 BPN
_127 BFN
HRI,D _ 3 (IS KW)_[ "_WIS 9 BRN
HRI.2,3 Z 4 [212, FW) _
ACCESSORy ELECTS:It: HEAl ++
14
Page 15

IMPORTANT: When evaluating the refrigerant charge, an indi-
cated adjustment to the specified factory charge must always be
very minimal. If a substantial adjustment is indicated, an abnormal
condition exists somewhere in the cooling system, such as insuf
ficient airflow across either coil or both coils.
Refrigerant charge
The amount of refrigerant charge is listed on the unit nameplate.
Refer to the Refrigeration Service Techniques Manual. Refriger
ants section.
Unit panels must be in place when unit is operating during
charging procedures.
No charge
Use standard evacuating techniques. After evacuating system.
weigh in the specified amount of refrigerant (refer to system data
plate).
Low charge cooling
Measure outdoor ambient using Cooling Charging Charts (Figs.
18-23). Vary refrigerant until the conditions of the chart are met.
Note that charging charts are different from type normally used.
Charts are based on charging the units to correct superheat for the
various operating conditions. Accurate pressure gage and tempera-
ture sensing devices are required. Connect the pressure gage to the
service port on the suction line. Mount the temperature sensing
device on the suction line and insulate it so that the outdoor
ambient does not effect the reading. Indoor air CFM must be
within the normal operating range of the unit.
To use cooling charging charts
Take the outdoor ambient temperature and read the suction
pressure gage. Refer to the chart to determine what the suction
temperature should be.
NOTE: If the problem causing the inaccurate readings is a
refrigerant leak, refer to Check for Refrigerant Leaks section.
INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS
Table 4 shows cooling airflows at various external static pressures.
Refer to these tables to determine the airflow for the system being
installed.
NOTE: Be sure that all supply- and return-air grilles are open,
free from obstructions, and adjusted properly.
Disconnect electrical power to the unit before changing
blower speed. Electrical shock can cause serious injury or
death.
Airflow can be changed by changing the lead connections of the
blower motor.
All 50GL units are factory wired for low speed and may need to be
wired for medium or high speed in the field.
FOR 208/230-V -- The motor leads are color-coded as follows:
3-SPEED 2-SPEED
black = high speed black = high speed
blue = medium speed
red = low speed red = low speed
To change the speed of the blower motor (BM). remove the fan
motor speed leg lead from the blower relay (BR). This wire is
attached to terminal BM for single-phase and 3-phase units. To
change the speed, remove and replace with lead for desired blower
motor speed, b_sulate the removed lead to avoid contact with
chassis parts.
FOR 460-V GE MOTORS The motor leads are color coded as
follows:
3-SPEED 2-SPEED
black = high black= high
violet = jumper blue = jumper
orange = medium
red = low red = tow
To change the speed of the blower motor (BM), remove fan motor
speed lead from the blower relay (BR) and replace with the lead
for the desired blower motor speed. The motor speed lead is
attached to terminal BM. For low and medium speeds black must
be connected to the jumper wire. Insulate removed lead end to
avoid contact with chassis parts. To select high speed on 460-v GE
motors, separate the black female quick connect (QC) from the
jumper lead male quick connect (QC) and connect the black lead
to the BR. Insulate the jumper to avoid contact with any chassis
parts.
COOLING SEQUENCE OF OPERATION--With the room
thermostat SYSTEM switch in the COOL position and the FAN
switch in the AUTO position, the cooling sequence of operation is
as follows:
When the room temperature rises to a point that is slightly above
the cooling control setting of the thermostat, the thermostat
completes the circuit between thermostat terminal R to terminals Y
and G. These completed circuits through the thermostat connect
contactor coil (C) (through unit wire Y) and blower relay coil
(TDR) (through unit wire G) across the 24-v secondary of
transformer (TRAN).
The normally open contacts of energized contactor (C) close and
complete the circuit through compressor motor (COMP) to con-
denser (outdoor) fan motor (OFM). Both motors start instantly.
The set of normally open contacts of energized relay TDR close
and complete the circuit through evaporator blower (indoor) fan
motor (IFM).
NOTE: Once the compressor has started and then has stopped, it
should not be started again until 5 rain have elapsed.
The cooling cycle remains "on" until the room temperature drops
to point that is slightly below the cooling control setting of the
room thermostat. At this point, the thermostat "breaks" the circuit
between thermostat terminal R to terminals Y and G. These open
circuits deenergize contactor coil C and relay coil TDR. The
condenser and compressor motors stop. After a 30-sec delay, the
blower motor stops. The unit is in a "standby" condition, waiting
for the next "'call for cooling" from the room thermostat.
MAINTENANCE
To ensure continuing high performance, and to minimize the
possibility of premature equipment failure, periodic maintenance
must be performed on this equipment. This cooling unit should be
inspected at least once each year by a qualified service person. To
troubleshoot heating or cooling of units, refer to tables at the back
of the book.
NOTE TO EQUIPMENT OWNER: Consult your local dealer
about the availability of a maintenance contract.
15
Page 16

Table 4---Wet Coil Air Delivery (Deduct 10% for 208v)*
Horizontal and Downflow Discharge
Unit 50GL024-060
230 AND 460 VOLT
Unit
O24
3O
36
42
48
6O
• Air delivery values are based on operating voltage of 230 v or 460 v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain
static pressure available for ducfing.
NOTES: 1. DO not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.
Motor Speed
Low
Meal
High
LOW
Med
High
Low
Med
High
Low
Med
High
Low
Med
High
Low
Med
High
airflows below this point.
Watts 281 282 281 278 276
Cfm 833 776 702 638 554
Watts 375 370 363 357 352
Cfm 894 800 754 636 518
Watts 468 457 444
Ckn 884 802 697
Watts 246 244 243 241
Cfm 910 806 749 680
Watts 343 339 336 332 328 322 317
Cfm 1148 1104 1028 958 850 782 645
Watts 441 432 421 410 400
Cfrn 1102 988 896 783 529
Watts 470 458 445 430 415 399 384
Cfm 1352 1257 1240 1199 1107 1015 924
Watts 514 501 487 471 455 438 422
Cfm 1338 1295 1288 1181 1111 966 813
Watts 646 636 626 614 602 589
Cfrn 1385 1268 1196 1159 1032 948
Watts 625 614 605 593 574 549 518 485 454
Cfm 1540 1510 1473 1396 1348 1288 1192 1124 1037
Watts 726 695 661 625 591 561
Cfrn 1648 1593 1530 1446 1352 1237
Watts 790 766 742
Cfm 1616 1492 1394
Watts 588 577 572 566 556 539 517 491
Cthl 1514 1543 1467 1408 1374 1324 1237 1161
Watts 756 738 719 699 676 650 623 596 572 555
Cfm 1785 1765 1706 1628 1577 1503 1421 1357 1298 1253
Watts 896 862 829 800 775 752 728
Cfm f 880 1804 1704 1547 1565 1406 1367
Watts 903 898 873 842 814 792 777 764 743 701 618
Cfrn 2190 2158 2081 2026 1958 1866 1822 1744 1678 1535 1377
Watts 1002 978 960 941 914 880 839 798 764 750
Cfrn 2889 2291 2216 2120 2020 1952 1852 1727 1617 1549
Watts 1080 1080 1066 1041 1008 972 938
Grin 3316 2181 2122 2101 2000 1802 1672
0.0 0.1 0.2 0.3 0.4 0.5 0.6
External Static Pressure (in. wg)
0.7
0.8 0.9 1.0
431 423
467 397
540
1114
713
1283
LVf'__l_q] ,'[d
The ability to properly perform maintenance on this equip-
ment requires certain expertise, mechanical skills, tools, and
equipment. If you do not possess these, do not attempt to
perform any maintenance on this equipment other than those
procedures recommended in the User's Manual. FAILURE
TO HEED THIS WARNING COULD RESULT IN SERI-
OUS INJURY OR DEATH AND POSSIBLE DAMAGE TO
THIS EQUIPMENT.
Failure to follow these warnings could result in serious injury
or death:
I. Turn off electrical power to the unit before performing any
maintenance or service on the unit.
2. Use extreme caution when removing panels and parts. As
with any mechanical equipment, personal injury can result
from sharp edges, etc.
3. Never place anything combustible either on, or in contact
with. the unit.
tion when servicing.
16
Page 17

The minimum maintenance requirements for this equipment are as
follows:
1. Inspect air filter(s/ each month. Clean or replace when
necessary.
2. Inspect indoor coil, drain pan, and condensate drain each
cooling season for cleanliness. Clean when necessary.
3. Inspect blower motor and wheel for cleanliness and check
lubrication each heating and cooling season. Clean when
necessary.
4. Check electrical connections for tightness and controls for
proper operation each heating and cooling sea.son. Service
when necessary.
AIR FILTER
IMPORTANT: Never operate the unit without a suitable air filter
in the return-air duct system. Always replace the filter with the
same dimensional size and type as originally installed (See Tables
1 for recommended filter sizes).
Inspect air filter(s) at least once each month and replace
(throwaway-type) or clean (cleanable-type) at least twice during
each heating and cooling season or whenever the filter(s) becomes
clogged with dust and lint.
EVAPORATOR BLOWER AND MOTOR
NOTE: All motors are prelubricated. Do not attempt to lubricate
these motors.
For longer life, operating economy, and continuing efficiency.
clean accumulated dirt and grease from the blower wheel and
motor annually.
Disconnect and tag electrical power to the unit before
cleaning the blower motor and wheel. Failure to adhere to this
warning could cause serious injury or death.
To clean the blower motor and wheel:
1. Remove and disassemble blower assembly as follows:
a. Remove unit access panel.
b. Disconnect motor lead from blower relay (BR). Disconnect
yellow lead from terminal L2 of the contactor.
c. On all units remove blower assembly from unit. Remove
screws securing blower to blower partition and slide
assembly out. Be careful not to tear insulation in blower
compartment.
d. Ensure proper reassembly by marking blower wheel and
motor in relation to blower housing before disassembly.
e. Loosen setscrew(s) that secures wheel to motor shaft,
remove screws that secure motor mount brackets to hous-
ing, and slide motor and motor mount out of housing.
2. Remove and clean blower wheel as follows:
a. Ensure proper reassembly by marking wheel orientation.
b. Lift wheel from housing. When handling and/or cleaning
blower wheel, be sure not to disturb balance weights (clips)
on blower wheel vanes.
c. Remove caked-on dirt from wheel and housing with a
brush. Remove lint and/or dirt accumulations from wheel
and housing with vacuum cleaner, using soft brush attach-
ment. Remove grease and oil with mild solvent.
d. Reassemble wheel into housing.
e. Reassemble motor into housing. Be sure setscrews are
tightened on motor shaft flats and not on round part of
shaft.
f. Reinstall unit access panel.
3. Restore electrical power to unit. Start unit and check for
proper blower rotation and motor speeds during heating and
cooling cycles.
CONDENSER COIL, EVAPORATOR COIL. AND CONDEN-
SATE DRAIN PAN
Inspect the condenser coil. evaporator coil. and condensate drain
pan at least once each year.
The coils are easily cleaned when dry: therefore, inspect and clean
the coils either before or after each cooling season. Remove all
obstructions, including weeds and shrubs_ that interfere with the
airflow through the condenser coil.
Straighten bent fins with a fin comb. If coated with dirt or lint_
clean the coils with a vacuum cleaner, using the soft brush
attachment. Be careful not to bend the fins. If coated with oil or
grease, clean the coils with a mild detergent-and-water solution.
Rinse coils with clear water, using a garden hose. Be careful not to
splash water on motors, insulation, wiring, or air filterls_. For best
results, spray condenser coil fms from inside to outside the unit.
On units with an outer and inner condenser coil, be sure to clean
between the coils. Be sure to flush all dirt and debris from the unit
base.
Inspect the drain pan and condensate drain line when inspecting
the coils. Clean the drain pan and condensate drain by removing all
foreign matter from the pan. Flush the pan and drain tube with
clear water. Do not splash water on the insulation, motor, wiring,
or air filter(s). If the drain tube is restricted, clear it with a
"plumbers snake" or similar probe device. Ensure that the
auxiliary drain port above the drain tube is also clear.
CONDENSER FAN
unit. Damage to unit may result.
4. Remove 6 screws holding condenser grille and motor to top
cover.
5. Turn motor/grille assembly upside down on top cover to
expose the fan blade.
6. Inspect the fan blades for cracks or bends.
7. If fan needs to be removed, loosen the setscrew and slide the
fan off the motor shaft.
8. When replacing fan blade, position blade so that the hub is t/8
in. away from the motor end ( 118 in. of motor shaft will be
visible).
9. Ensure that setscrew engages the flat area on the motor shaft
when tightening.
10. Replace grille.
ELECTRICAL CONTROLS AND WIRING -- Inspect and check
the electrical controls and wiring annually. Be sure to turn offthe
electrical power to the unit.
Remove access panel to locate all the electrical controls and
wiring. Check all electrical connections for tightness. Tighten all
screw connections. If any smoky or burned connections are
noticed, disassemble the connection, clean all the parts, restrip the
wire end and reassemble the connection properly and securely.
After inspecting the electrical controls and wiring, replace the
access panel. Start the unit, and observe at least one complete
heating cycle and one complete cooling cycle to ensure proper
operation. If discrepancies are observed in either or both operating
17
Page 18

C99079
Fig. 18--Cooling Charging Chart, 50GL024 Units
C99080
Fig. 19.--_ooling Charging Chart, 50GL030 Units
(C4_t60 _Z C_P_X_ O'_RT
_Z41 leo
F_ LI_ wr_H U_IFF__X_ P_ IOAREFRK_J_
i = i i i_ i i i _1 i
11 '
C99081
Fig. 20_Cooling Charging Chart, 50GL036 Units
I
C99083
Fig. 22--._ooling Charging Chart, 50GL048 Units
zoo 3o0 _oo _,_o _oo 70o coo
I
su_;_ LI,_ TEMP_P_T_m£ _0_G F)
I _ T
S_CTI_4 UN_ T_4P_RAIrURE <BEG C)
C99082
Fig. 21---Cooling Charging Chart, 50GL042 Units
_o) _,oHZCHAR_,4_ CHART
_o_ l_ _f14 L_RS l_Sl_ R41o& _FRK_4_
_'"" iiiiii
,,::::
!!JJJ_
:_: L:
i
• T •
C99084
Fig. 23_Cooling Charging Chart, 50GL060 Units
18
Page 19

cycles, or if a suspected malfunction has occurred, check each
electrical component with the proper electrical instrumentation.
Refer to the unit wiring label when making these checkouts.
NOTE: Refer to the heating and/or cooling sequence of operation
in this publication as an aid in determining proper control
operation.
REFRIGERANT CIRCUIT-- Inspect all refrigerant tubing con-
nections and the unit base for oil accumulations annually. Detect-
ing oil generally indicates a refrigerant leak.
¥!_|VI'-I :qTIIT[_
System under pressure. Relieve pressure and recover all
refrigerant before system repair or final unit disposal to avoid
serious injury or death. Use all service ports and open all
flow-control devices, including solenoid valves.
If oil is detected or if low cooling performance is suspected,
leak-test all refrigerant tubing using an electronic leak-detector.
halide torch, or liquid soap solution. If a refrigerant leak is
detected, refer to Check for Refrigerant Leaks section.
If no refrigerant leaks are found and low cooling performance is
suspected, refer to Checking and Adjusting Refrigerant Charge
section.
EVAPORATOR AIRFLOW- The heating and/or cooling air-
flow does not require checking unless improper performance is
suspected, ff a problem exists, be sure that all supply- and
retu_7l-air grilles are open and free from obstructions, and that the
air filter is clean. When necessary, refer to Indoor Airflow and
Airflow Adjustments section to check the system airflow.
METERING DEVICE ACCURATOR® PISTON--This me-
tering device is a fixed orifice and is contained in the brass
hex-body in the liquid line.
PRESSURE SWITCHES Pressure switches are protective de-
vices wired into control circuit (low voltage). They shut off
compressor if abnormally high or low pressures are present in the
refrigeration circuit. These pressure switches are specifically
designed to operate with Puron (R_-IOA) systems. R-22 pressure
switches must not be used as replacements for the Puron (R-
410A) air conditioner.
LOSS OF CHARGE/LOW-PRESSURE SWITCH (AIR CONDI-
TIONER ONLY)--This switch is located on the liquid line and
protects against low suction pressures caused by such events as
loss of charge, low airflow across indoor coil, dirty filters, etc. It
opens on a pressure drop at about 20 psig. If system pressure is
above this, switch should be closed.
To check switch:
I. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohmeter leads across switch. You should have conti-
nuity on a good switch.
NOTE: Because these switches are attached to refrigeration
system under pressure, it is not advisable to remove this device for
troubleshooting unless you are reasonably certain that a problem
exists. If switch must be removed, remove and recover all system
charge so that pressure gages read 0 psi. Never open system
without breaking vacuum with dry nitrogen.
HIGH-PRESSURE SWITCH--The high-pressure switch is lo-
cated in the discharge line and protects against excessive con-
denser coil pressure. It opens at 610 psig.
High pressure may be caused by a dirty condenser coil, failed fan
motor, or condenser air recircnlation.
To check switch:
1. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohmeter leads across switch. You should have conti-
nuity on a good switch.
COPELAND SCROLL COMPRESSOR (PURON REFRIGER-
ANT -- The compressor used in this product is specifically
designed to operate with Puron (R-410A) refrigerant and
cannot be interchanged.
The compressor is an electrical (as well as mechanical) device.
Exercise extreme caution when working near compressors. Power
should be shut off. if possible, for most troubleshooting tech-
niques. Refrigerants present additional safety hazards.
r.,_lt'_ ;1:11:[
Wear safety glasses and gloves when handling refrigerants.
Keep torches and other ignition sources away from refriger-
ants and oils. Failure to follow this warning can cause a fire,
serious injury, or death.
The scroll compressor pumps refrigerant throughout the system by
the interaction of a stationary and an orbiting scroll. The scroll
compressor has no dynamic suction or discharge valves, and it is
more tolerant of stresses caused by debris, liquid slugging, and
flooded starts. The compressor is equipped with an anti-rotational
device and an intemai pressure relief port. The anti-rotational
device prevents the scroll from turning backwards and replaces the
need for a cycle protector. The pressure relief port is a safety
device, designed to protect against extreme high pressure, the
relief port has an operating range between 550 and 625 psi
differential pressure.
The Copeland scroll compressor uses Mobil 3MA POE oil.
This is the only oil allowed for oil recharge.
REFRIGERANT SYSTEM
REFRIGERANT
[] [,_l//[,]: I
This system uses Puron® (R_!IOA/ refrigerant which has
higher operating pressures than R-22 and other refrigerants.
No other refrigerant may be used in this system. Gage set,
hoses, and recovery system must be designed to handle
Puron. If you are unsure consult the equipment manufacturer.
Failure to use Puron compatible servicing equipment or
replacement components may result in property damage or
injury.
COMPRESSOR OIL--The compressor in this system uses a
polyolester (POE) oil, Mobil 3MA POE. This oil is extremely
hygroscopic, meaning it absorbs water readily. POE oils can
absorb 15 times as much water as other oils designed for HCFC
and CFC refrigerants. Take all necessary precautions to avoid
exposure of the oil to the atmosphere.
SERVICING SYSTEMS ON ROOFS WITH SYNTHETIC MA-
TERIALS POE (polyolester) compressor lubricants are known
to cause long term damage to some synthetic roofing materials.
Exposure, even if immediately cleaned up, may cause embrittle-
ment (leading to cracking) to occur in one year or more. When
performing any service that may risk exposure of compressor oil to
the roof, take appropriate precautions to protect roofing, proce-
dures which risk oil leakage include, but are not limited to,
compressor replacement, repairing refrigerant leaks, replacing
refrigerant components such as filter drier, pressure switch, me-
tering device, coil, accumulator, or reversing valve.
19
Page 20

SYNTHETICROOFPRECAUTIONARYPROCEDURE
1.Coverextendedroofworkingareawithanimpermeable
polyethylene(plastic)dripclothortarp.Coveranapproximate
10x10ft.area.
2.Coverareainfrontoftheunitservicepanelwithaterrycloth
shoptoweltoabsorblubricantspillsandpreventrun-offs,and
protectdropclothfromtearscausedbytoolsorcomponents.
3.Placeterryclothshoptowelinsideunitimmediatelyunder
component(s)tobeservicedandpreventlubricantrun-offs
throughthelouveredopeningsinthebasepan.
4.performrequiredservice.
5.Removeanddisposeofanyoilcontaminatedmaterialper
localcodes.
LIQUIDLINEFILTERDRIER-- Thefilterdrierisspecifically
designedto operatewithPuron. Use only factory-authorized
components. Filter drier must be replaced whenever the refrigerant
system is opened. When removing a filter drier, use a tubing cutter
to cut the drier from the system. Do not unsweat a filter drier
from the system. Heat from unsweating will release moisture and
contaminants from drier into system.
PURON IR-410A) REFRIGERANT CHARGING -- Refer to unit
infornaation plate and charging chart. Some R-410A refrigerant
cylinders contain a dip tube to allow liquid refrigerant to flow
from cylinder in upright position. For cylinders equipped with a
dip tube, charge Puron units with cylinder in upright position and
a commercial metering device in manifold hose. Charge refrigerant
into suction-line.
20
Page 21

AIR CONDITIONER WITH PURON® (R-410A),_QUICK REFERENCE GUIDE
Puron refrigerant operates at 50%-70% higher pressures than R-22. Be sure that servicing equipment and replacement components are designed
to operate with Puron.
Puron refrigerant cylinders are rose colored.
Puron refrigerant cylinders manufactured prior to March 1, 1999. have a dip tube that allows liquid to flow out of cylinder in upright
position. Cylinders manufactured March 1, 1999 and later DO NOT have a dip tube and MUST be positioned upside down to allow liquid
to flow.
• Recovery, cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
Puron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose.
Manifold sets should be 750 psig high-side and 200 psig low-side with 520 psig low-side retard.
Use hoses with 750 psig service pressure rating.
Leak detectors should be designed to detect HFC refrigerant.
Puron, as with other HFCs, is only compatible with POE oils.
Vacuum pumps will not remove moisture from oil.
Only use factory specified liquid line filter driers with rated working pressures no less than 600 psig.
Do not instan a suction-line filter drier in liquid-line.
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
POE oils may cause damage to certain plastics and roofing materials.
Wrap all filter driers and service valves with wet cloth when brazing.
A Puron liquid-line filter drier is required on every unit.
Do not use an R-22 TXV.
Never open system to atmosphere while it is under a vacuum.
When system must be opened for service, break vacuum with dry nitrogen and replace filter driers.
Always replace filter drier after opening system for service.
Do not vent Puron into the atmosphere.
Observe all warnings, cautions, and bold text.
Do not leave Puron suction line driers in place for more than 72 hrs.
21
Page 22

Table 5.--Troubleshooting -- Cooling
SYMPTOM
Power failure
Fuse blown or circuit breaker thpped
Defective thermc6tat, contactor, transformer, con-
Compressor and condenser fan will not start
Compressor will not start but condenser fan
furls
Three-phase scroll compressor (50GL030-060) Scroll compressor is rotating in the wrong direc-
makes excessive noise, and there may be a ;ion
low pressure differential
Compressor cycles (other than normally sat-
isfying thermostat)
Compressor operates continuously
Excessive head pressure
Head pressure too low
Excessive suction pressure
Suction pressure too low
tramrelay, high pressure, or loss-of-charge swtich
insufficient fine voltage
Incorrect or faulty widng
Thermostat setting too high
Faulty widng or loose connections in compressor
circuit
Compressor motor burned out, seized, or internal
ovedoad open
Defective run!start capacitor, overload, start relay
(Ztheleg of 3-phase power dead
Refrigerant overcharge or undercharge
Detective compressor
Insufficient line voltage
Blocked condenser
Defective run/start capacitor, ovedoad or start
relay
Defective thermostat
Faulty condenser-tan motor or capacitor
Restric_on in refrigerant system
Dirty air tilter
Unit undersized for load
Thermostat set too low
Low refrigerant charge
Leaking velves in compressor
Air in system
Condenser coil dirty or restncted
Dirty air tilter
Dirty condenser coil
Refrigerant overcharged
Air in system
Condenser air restricted o{ air short-cycling
Low refrigerant charge
Restriction in liquid tube
High heat load
Refrigerant overcharged
Dirty air ftitar
Low refdgerant charge
Metadng device or low side Pastdctad
Insufficient evaporator airflow
Temperature too low in conditioned area
Outdoor ambient below 40 F
Field-installed tilter-drier restricted
CAUSE
REMEDY
Call power Company
Replace fuse or reset circuit breaker
Replace component
Determine cause and correct
Check widng diagram and rewire correctly
Lower thermostat setting below room tempera-
ture
Check wiring and repair or replace
Determine cause. Repiace compressor
Determine cause and replace
Replace fuse or reset circuit breaker
Determine cause
Correct the direction of rotation by reversing two
of the 3-phase power leads to the unit. Shut
down unit to allow pressures to equalize
Recover refrigerant, evacuate system, and re-
charge to capacities shown on nameplate
Replace and determine cause
Determine cause and correct
Determine cause and correct
Determine cause and replace
Replace thermostat
Replace
Locate restriction and remove
Replace filter
Decrease load or increase unit size
Reset thermostat
Locate leak, repair, and recharge
Replace compressor
Recover refrigerant, evacuate system, and re-
charge
Clean coil or remove restriction
Replace filter
Clean coil
Recover excess refrigerant
Recover refhgerant, evacuate system, and re-
charge
Determine cause and correct
Check for leaks, repair and recharge
Remove restriction
Check for source and eliminate
Recover excess refrigerant
Replace tilter
Check for leaks, repair and recharge
Remove source of restriction
Increase air quantity. Check tilter -- replace if
necessary
Reset thermostat.
Install low-ambient kit
Replace
22
Page 23

START-UP CHECKLIST
(REMOVE AND STORE IN JOB FILE)
I. PRELIMINARY INFORMATION
Model No ...............................................................................................................................................................................................................
Serial No ................................................................................................................................................................................................................
Date ........................................................................................................................................................................................................................
Technician ..............................................................................................................................................................................................................
II. PRE-START-UP
__ Verify that all packing materials have been removed from unit
__ Verify that condensate connection is installed per installation instructions
__ Check all electrical connections and terminals for tightness
__ Check that indoor (evaporatorl air filter is clean and in place
__ Verify that unit installation is level
__ Check fan wheel and propeller for location in housing and setscrew tightness
III. START-UP
Supply Voltage LI-L2 L2 L3 L3-LI
Compressor Amps Ll L2 L3
Indoor (Evaporator) Fan Amps
TEMPERATURE
Outdoor (Condenser) Air Temperature DB
Return-Air Temperature __ DB WB
Cooling Supply Air DB WB
PRESSURES
Refrigerant Suction psig
Suction Line Temp*
Refrigerant Discharge psig
Discharge Tempt
-- Verify refrigerant charge using charging tables
__ Verify that 3-phase scroll compressor (50GL030-060) is rotating in correct direction
• Measuredat suctioninletto compressor
t Measuredat liquidline leavingcondenser
23
Page 24

Copyi_ht 2000 CARRIER Coqo. • 7310 W. Morris St. • Indianapolis, IN 46231 50gllsi
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 101 Catalog No. 565_313 Printed in U.S.A. Form 50GL-1SI Pg 24 6-00 Replaces: New