50GL
HEATING & COOLING
with Puron® (R-410A) Refrigerant
Single Package Electric Cooling Units
Visit www.camer.com
Installation, Start-Up, and Operating Instructions
Sizes 024-060
NOTE: Read the entire instruction manual before starting the
installation.
Index Page
SAFETY CONSIDERATIONS ................................................... l
RULES FOR SAFE INSTALLATION AND OPERATION.I-4
GENERAL ................................................................................ 4
RECEIVING AND INSTALLATION .................................. 4-10
Step 1 -- Check Equipment ....................................................... 4
IDENTIFY UNIT ...................................................................... 4
INSPECT SHIPMENT ............................................................. 4
Step 2 -- Provide Unit Support ................................................. 4
ROOF CURB ............................................................................ 4
SLAB MOUNT ......................................................................... 4
GROUND LEVEL .................................................................... 4
Step 3 -- Field Fabricate Ductwork .......................................... 4
Step 4 -- Provide Clearances ..................................................... 4
Step 5 -- Rig and Place Unit ...................................................... 4
INSPECTION ............................................................................ 4
INSTALLATION .................................................................. 4-6
Step 6 -- Connect Condensate Drain ........................................ 6
Step 7 -- Install Duct Connections ........................................ 6-8
CONFIGURING UNITS FOR DOWNFLOW (VERTICAL)
DISCHARGE .............................................................................. 7-8
Step 8 -- Install Electrical Connections .............................. 8-10
HIGH-VOLTAGE CONNECTIONS .................................. 8-10
STANDARD CONNECTION ................................................ 10
SPECIAL PROCEDURES FOR 208-V OPERATION ......... 10
CONTROL VOLTAGE CONNECTIONS ............................ 10
TRANSFORMER PROTECTION ......................................... 10
PRE-START-UP ......................................................................... I 1
START-UP ............................................................................. 11-14
MAINTENANCE .................................................................. 15-20
TROUBLESHOOTING ............................................................. 22
START-UP CHECKLIST ......................................................... 23
NOTE TO INSTALLER -- Before the installation, READ THESE
INSTRUCTIONS CAREFULLY AND COMPLETELY. Also,
make sure the User's Manual and Replacement Guide are left with
the unit after installation.
SAFETY CONSIDERA_ONS
Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified personnel should install, repair, or service
air-conditioning equipment.
Untrained p_rsonnel can perform basic maintenance functions of
cleaning coils and filters. All other operations should be performed
by trained service personnel. When working on air-conditioning
equipment, observe precautions in the literature, tags and labels
attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unhrazing operations. Have fh'e extinguisher
available for all brazing operations. Consult a qualified installer or
service agency for information or assistance. The qualified in-
staller or agency must use only factory-authorized kits or acces-
sories when modifying this product.
Before performing service or maintenance operations on
system, turn off power to unit. Turn off accessory heater
power switch, if applicable. Electrical shock can cause
serious injury or death.
Puron (R-410A) systems operate at higher pressures than
standard R-22 systems. Do not use R-22 service equipment or
components on Puron (R-410A) equipment. Ensure service
equipment is rated for Puron (R-410A).
RULES FOR SAFE INSTALLATION AND OPERATION
Recognize safety information. This is the safety-alert symbol z_ •
When you see this symbol in instructions or manuals, be alert to
the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION,
IMPORTANT, and NOTE. These words are used with the safety-
alert symbol. DANGER identifies the most serious hazards which
will result in severe injury or death. WARNING signifies a hazard
which could result in serious injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE and IMPORTANT
are used to highlight suggestions which will result in enhanced
installation, reliability, or operation.
Fig. 1--Model 50GL
C99064
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 101 Catalog No. 565-013 Printed io U.S.A, Form 50GL-ISI Pg 1 6-00 Replaces: New
1463]
883
i) 48]
I
249 6 _BSO S 249 6
[9 831 121 {7) 1983]
REARVIEW TOPVIEW
REQ'D CLEARANCES FOR OPERATION AND SERVICING. in. (ram)
Evaporator col( access side .................. 36 (914)
Power entry side (except for NEC requirements) ......... 36 (914)
Unit top .......................... 48 [1219)
Side opposite ducts ..................... 36 (914)
Duct panel ........................ 12 [304.8)*
*Minimum distances: If unit is placed less than 12 in. (304•8 ram) from wall
system, then the system performance may be compromised.
LEGEND
CG - Center of Gravity
COND - Condenser
EVAP - Evaporator
NEC - National Electrical Code
REQ'D - Required
Note: Dimensions are in in. [rnm)
(4T.oo]
t
1193g
REG'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (ram)
Top of unit ......................... 14 (355.6)
Duct side of unit ....................... 2 (50.8)
Side opposite ducts ..................... 14 (355.6)
Bottom of unit ....................... 0.50 [12.7)
Flue panel ......................... 36 (914.4)
NEC REQ'D CLEARANCES. in. (ram)
Between units, power entry side .............. 42 (10_6.8)
Unit and ungrounded surfaces, power entry side ......... 36 (914)
Unit and block or concrete wails and other grounded
surfaces, control box side ................. 42 (1066.8)
22 2
UNn"
50GL024
50GL030
50GL036
_LPleE,S0R BL_,R GA,,EC:I0,
FRONTVIEW
Fig. 2_0GL024-036 Unit Dimensions
ELECTRICAL CHARACTERISTICS
208/230-1-60 270 122.5
208/230-1-60, 208/230-3-60 291 132.0
20_11-_50, 208/230-3-60, 460-3-60 2g9 135.6
UNIT WEIGHT
Ib kg
uNrr HEIGHT
IN. (MM]
mA"
37,02 [940.3]
39.02 [99t .1]
35,02 [889.5]
14 81)
RIGHT 51DE VIEW
CENTER OF GRAVITY
IN. [MM]
X Y
18.5 [469.91 14.5 [368.31
19.5 [495.3] 15.5 [393.7}
19.5 [495.3] 15.3 [387.4}
C00064
Z
16.0 1406.4]
17.6 [447.0]
16.5 [41g.11
402 _3]
•-MHHIIHJ
SUPPL+ R[TUR_
D+_[ bVCT
OPENING OPENING
I i k
[4 63]
88 3 --
{3 48i
113 831 113 _ll 113 331
- 347 3
REARVIEW
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
EVAR COIL ACCESS SIDE .............................................................. 36.00 [914.0]
POWER ENTRY SIDE ...................................................................... 36.00 [914.0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP ......................................................................................... 36.00 [914.0]
SIDE OPPOSITE DUCTS ................................................................ 36.00 [914.0]
DUCT PANEL ................................................................................... 12.00 [304.8] *
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 [304.8] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.
in. [ram]
C01L
TOP VIEW
REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
TOP OF UNIT ................................................................................... 14.00 {355.6]
DUCT SiDE OF UNiT ........................................................................ 2.00 [50.8]
SIDE OPPOSITE DUCTS ................................................................ 14.00 [355.6]
RO]-i-OM OF UNIT ............................................................................. 0.50 [12.7]
ELECTRIC HE_,T PANEL ................................................................. 36.00 [914.4]
NEC. REQUIRED CLEARANCES.
BETWEEN UNITS, POWER ENTRY SIDE .................................... 42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE ...36.00 [914.0]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE ......................... 42.00 [1066.8]
MILLIMETERS (IN.]
in. (rnm]
UNIT
50GL042
50GL048
50GL060
[5 61_
RIGHT SIDE VIEW
Fig. 3_50GL042-060 Unit Dimensions
ELECTRICAL CHARACTERISTICS IN, [MM] IN. [MM]
208/230-1_o0, 208/230-3-60. 460-3-60 321 146 38.98 [990.2] 20.5 [520.7] 16.8 [425.5]
20_-230-1,.60, 208/230-3_0, 460.-3-60 326 148 38.98 [990.2} 19.5 [495.3] 17.6 [447.6]
208F230-1-60, 208/230-3-60, 460-3-60 399 181 42.98 [1091.1] 20.5 [520.7] 16.2 [412.8]
UNIT WEIGHT UNIT HEIGHT CENTER OF GRAVITY
Ib kg "A" X Y
3
C00065
Z
16.6 [421,6 I
18.0 [487.2]
17.6 [447.0]
The power supply (volts, phase, and hertz) must correspond to that
specified on unit rating plate.
The electrical supply provided by the utility must be sufficient to
handle load imposed by this unit.
This installation must conform with local building codes and with
NEC (National Electrical Code) and NFPA 70. NFPA 54/ANSI
Z223.1 latest revision, and NFGC (National Fuel Gas Code). Refer
to provincial and local plumbing or w_ste water codes and other
applicable local codes.
Approved for outdoor installation on wood flooring or on class A.
B or C roof covering materials.
These instructions cover minimum requirements and conform to
existing national standards and safety codes. In some instances,
these instructions exceed certain local codes and ordinances,
especially those that may not have kept up with changing residen-
tial construction practices. We require these instructions as a
minimum for a safe installation.
GENERAL- The 50GL units are fully self-contained, and de-
signed for outdoor installation (See Fig. 1). See Fig. 2 and 3 for
unit dimensions. All unit sizes have discharge openings for both
horizontal and downflow configurations, and are facto_ shipped
with all duct openings covered. Units may be installed either on
a rooftop, ground-level cement slab, or directly on the _a'ound if
local codes permit. See Fig. 4 for roof curb dimensions.
RECEIVING AND INSTALLATION
Step 1--Check Equipment
IDENTIFY UNIT--The unit model number and serial number
are stamped on unit identification plate. Check this information
against shipping papers and job data.
INSPECT SHIPMENT -- Inspect for shipping damage while unit
is still on shipping pallet. If unit appears to be damaged or is torn
loose from its anchorage, have it examined by transportation
inspectors before removal. Forward claim papers directly to
transportation company. Manufacturer is not responsible for any
damage incurred in transit. Check all items against shipping fist.
Immediately notify the nearest Carrier Air Conditioning office if
any item is missing. To prevent loss or damage, leave all parts in
original packages until installation.
Step 2--Provide Unit Support
ROOF CURB -- Install accessory roof curb in accordance with
instructions shipped with curb (See Fig. 4 for roof curb dimen-
sions). Install insulation, cant strips, roofing, and flashing. Duct-
work must be attached to curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical
for a watertight seal. Install gasketing material supplied with the
roof curb. Improperly applied gasketing can also result in air leaks
and poor unit performance. Curb should be level to within 1/4 in.
(See Fig. 6). This is necessary for unit drain to function properly.
Refer to accessory roof curb installation instructions for additional
information as required.
SLAB MOUNT-- Place the unit on a solid, level concrete pad
that is a minimum of 4 in. thick with 2 in. above grade. The slab
should extend 2 in. on sides of the unit. Do not secure the unit to
the slab except when required by local codes.
GROUND LEVEL-- If local codes permit, the unit can be placed
directly on the ground. Prepare a level gravel foundation for proper
drainage.
Step 3_Field Fabricate Ductwork
Secure all ducts to roof curb and building structure on vertical
discharge units. Do not connect duct_vork to unit. For horizontal
applications, unit is provided with flanges on the horizontal
openings. All ductwork should be secured to the flanges. Insulate
and weatherproof all external ductwork, joints, and roof openings
with counter flashing and mastic in accordance with applicable
codes.
Ducts passing through an unconditioned space must be insulated
and covered with a vapor barrier. If a plenum return is used on a
vertical unit, the return should be ducted through the roof deck to
comply with applicable fire codes. A minimum clearance is not
required around ductwork. Cabinet return-air static shall not
exceed -.25 in. wg.
Step 4_Provide Clearances
The required minimum operating and service clearances are shown
in Fig. 2 and 3. Adequate ventilation and condenser air must be
provided.
compressor life.
The condenser fan draws air through the condenser coil and
discharges it through the top fan grill. Be sure that the fan
discharge does not recircalate to the condenser coil. Do not locate
the unit in either a corner or under an overhead obstruction. The
minimum clearance under a partial overhang (such as a normal
house overhang) is 36-in. above the unit top. The maximum
horizontal extension of a partial overhang must not exceed 48 in.
Do not place the unit where water, ice, or snow from an overhang
or roof will damage or flood the unit. Do not install the unit on
carpeting, tile. or other combustible materials.
Step S--Rig and Place Unit
Rigging and handling of this equipment can be hazardous for many
reasons due to the installation location (roofs, elevated structures,
etc.)
Only trained, qualified crane operators and ground support staff
should handle and install this equipment.
When working with this equipment, observe precautions in the
literature, on tags, stickers and labels attached to the equipment,
and any other safety precautions that might apply.
Follow all applicable safety codes. Wear safety shoes and work
gloves.
INSPECTION -- Prior to initial use, and at monthly intervals, all
rigging brackets and straps should be visually inspected for any
damage, evidence of wear, structural deformation, or cracks.
Particular attention should be paid to excessive wear at hoist
booking points and load support areas. Brackets or straps showing
any kind of wear in these areas must not be used and should be
discarded.
INSTALLATION
1. Remove unit from shipping carton. Leave top shipping skid on
the unit as a spreader bar to prevent the rigging straps from
damaging the unit. If the wood skid is not available, use a
spreader bar of sufficient length to protect unit from damage.
2. Position the lifting bracket assembly around the base of the
unit. Be sure the strap does not twist.
3. Place each of the 4 metal lifting brackets into the handholds in
the composite pan.
4. Thread lifting bracket strapping around bottom perimeter of
unit as follows:
a. Open lever of tension buckle (ratchet type).
b. Feed strapping through tension buckle (See Fig. 8).
4
463/16
44 5/16
A
END
(2)
DECK PAN (INSULATED)
SIDE PANEL--
SUPPORT RIB(S) 0.75' --{[/
SEAL STRIP
(FACTORY SUPPLIED)
COUNTER FLASHING - =
(FIELD SUPPLIED) •
ROOFING FELT
(FIELD SUPPLIED)
CANT STRIP --
(FIELD SUPPLIED)
SUPPORTA(2)
SIDE
- (2)
T BASE PAN
3.0" BOTTOM SUPPLY 4.0"
NAILER
_INSULATION
(FIELD SUPPLIED)
1
END VIEW
A99320
ROOFING MATERIAL
(FIELD SUPPLIED)
50GL UNIT SIZE ODS CATALOG ORDERING NO. A B C D
024-036
ROOF CURB
042-060
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied as required to unit being installed.
3. Dimensions in I ) are in millimeters.
4. Roof curb is made of 16 gage steel.
5. Table lists only the dirnensio_s per DOS Catalog Ordering Number that have changed.
6. Attach ductwork to curb (flanges of duct rest on curb).
7. Insulated panels: 1-in. thick fiberglass 1 Ib density,
CPRFCURB006A00 8 1203] 11-27/32 [301] 30-5/8 [T78] 28-3/4 [7301
CPRFCURB007A00 14 [356] 11-27/'32 [30t] 30-5/8 [778] 28-3/4 [730|
CPRFCURB008A00 8 [203] 15-27/32 [402] 42-1/8 [1070] 40-1/4 [1022]
CPRFCURBOO£'A00 14 [356] 15-27/'32 [402] 42-1/8 [1070] 40-1/4 [1022]
IN. [MM] IN, [MM] IN. [MM] IN, [MM]
Fig. &--Roof Curb Dimensions
5
A99340
RETURN SUppLY
AIR AIR III
OPENING OPENING illl
/ A°OHOLO
IIII
FII
I II
_N
H
HOOK
I
1
_ EVAP COiL COND C_L
3____% 2--_
C99014
Fig. 5--Slab Mounting Details
DUCTS
5_AL STRIp MUST BE iN
PLACE BEFORE p_ACING
UNfT C_ ROOF CURB
C99015
pLACE RIGGING STRAPS IN
BASEPAN SLOT (BELOW HANDHOLDS)
BEFORE RK3GING
j{48 _8")
Fig. 6_Suggested Rigging
SIZE
024 292 132.5 18.5 469,9 14.50 3683
030 313 142.5 19.5 4953 15.50 393.7
036 321 145.6 19.5 495.3 15.25 387.4
042 343 155.6 203 520.7 15,75 425.5
048 348 157.9 19,5 405.3 17.62 447.8
060 421 191.0 20.5 520.7 16.25 412.8
MAXIMUM WEIGHT A B
Ib kg in. rnm in. rnm
MAXIMUMALLOWABLE
DIFFERENCE/in.)
B A-B B-C A-C
1/4 1/4 1/4
L;9_6b
Fig. 7--Unit Leveling Tolerances
c. Pull strapping through tension buckle unit taut.
d. Snap lever down 1o lock strap in tension buckle. To release
strapping, squeeze safety latch, lift lever, and pull webbing
outward.
5. Tighten the tension buckle until it is taut. Lifting brackets
must be secure in the handholds.
6. Attach field-supplied clevis or hook of sufficient strength to
hole in the lifting bracket (See Fig. 9).
7. Attach the 2 safety straps directly to the clevis or hook at the
4 rigging brackets. DO NOT attach the safety straps to the
lifting brackeLs (See Fig. 9).
FEED _
e99087
Fig. 8_Belt Threading
CETAIL A
SCALE 025O
P_ND HOLES AND INSTALL lie DOWN STRAp
/SE E DETAIL A
AP_JN D PERIMETER OF UNIT AND THROUGH
_ACE IN BRACKET ASSEMBLY
C99066
Fig. 9---Lifting Point
8. Position lifting point directly over the unit's center of gravity.
9. Lift unit. When unit is directly over the roof curb, remove the
2 safety straps. Lower the equipment onto the roof curb.
Step 6---Connect Condensate Drain
NOTE: When installing condensate drain connection be sure to
comply with local codes and restrictions.
Model 50GL disposes of condensate water through a 3/4 in. NPT
fining which exits through the base on the evaporator coil access
side (See Fig. 2 and 3 for location).
Condensate water can be drained directly onto the roof in rooftop
installations (where permitted) or onto a gravel apron in ground-
level installations. Install a field-supplied condensate trap at end of
condensate connection to ensure proper drainage, Make sure that
the outlet of the trap is at least 1 in. lower than the drainpan
condensate connection to prevent the pan from overflowing (See
Fig. 10). When using a gravel apron, make sure it slopes away
from the unit.
Connect a drain tube using a minimum of 3/4 -in. PVC or 3/4 -in.
copper pipe (all field-supplied) at the outlet end of the 2-in. trap.
Do not undersize the tube. Pitch the drain tube downward at a
slope of at lemst one in. for every 10 fi of horizontal run. Be sure
to check the drain tube for leaks. Prime trap at the beginning of the
cooling sea.son start-up.
Step 7--Install Duct Connections
The unit has duct flanges on the supply- and return-air openings on
the side and bottom of the unit. For downshot applications the
ductwork can be connected to the roof curb ISee Pig. 2 and 3 for
connection sizes and locations).
Table 1--Physical Data -- Unit 50GL
UNIT SIZE
NOMINAL CAPACITY (ton)
OPERATING WEIGHT (Ib)
COMPRESSOR
REFRIGERANT (R-410A)
Quantity (Ib)
REFRIGERANT METERING DEVICE
HIGH-PRESSURE SWITCH (psig)
LOSS-OF-CHARGE/LOW-PRESSU RE SWITCH
(Liquid Line) (psig)
Cutom
Reset (Auto)
RETURN-AIR FILTERS (in.)*
Throwaway
• Requiredfilter sizes shown are based on the largerofthe ARI (Air CondiUoning and RefrigerationInstitute) ratedcooling airfloworthe heatingairflowvelocity of 300
ftJminfor throwaway type or 450 ft/min for high-capacity type. Airfilter pressure drop for ncn-standardfilters must notexceed 0.08 in. wg.
Orifice ID (in.)
CONDENSER COIL
Rows...Fins/in.
Face Area (sq R)
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Motor Hp (Rpm)
EVAPORATOR COIL
Rows...Fins/in.
Face Area (sq ft)
EVAPORATOR BLOWER
Nominal Airflow (Cfm)
Size (in.)
Motor (hp)
Cutout
Reset (Auto)
O24
2
27O
50 I ,5 I
Accurater_ Piston
.057 .057
1...17 1,.,17
10.9 12.7
2350 2350
22 22
1/8(825) 1/8 (825)
3...15 3...15
3,7 3.7
800 1000
10x10 10x10
1/4 1/4
030 036 042 048
2-1/2 3 3-1/2 4
291 299 321 326
SCrOll
00 I ,0 r g5
.065 070 ,073 .086
2...17 2,..17 2,..17 2...17
9.1 12.3 12.3 16.4
2350 2350 3300 3300
22 22 22 22
1/8 (825) 1/8 (825) 1/4 (1100) 1/4 (1100)
3..,15 3...15 4,-15 4...15
3.7 4.7 4.7 4.7
1200 1400 1600 1750
10xi0 11x10 11x10 1ix10
1/2 3#4 3/4 1
610 _+15
420+_25
20_+5
45+10
06O
5
399
10.0
x ,!2ox o×,12o 4xl12OX3OXl124x ox,124x OXl
1" MIN.
TRAP
oo,,E,÷
2" MIN.
C99013
Fig. 10--Condensate Trap
IMPORTANT: Use flexible connectors between ductwork and
unit to prevent transmission of vibration. Use suitable gaskets to
ensure weathertight and airtight seal. When electric heat is
installed, use fire proof canvas (or similar heat resistant material)
connector between ductwork and unit discharge connection. If
flexible duct is used, insert a sheet metal sleeve inside duct. Heat
resistant duct connector (or sheet metal sleeve) must extend 24-in.
from the unit connections flanges into the ductwork.
Table 2 -- Minimum Airflow for Safe Electric Heater
Operation (Cfm)
SIZE
0,41000o 1o42 o
800 1000 1200 1400 1600 2000
CONFIGURING UNITS FOR DOWNFLOW (VERTICAL) DIS-
CHARGE '
result.
1. Open all electrical disconnects before starting any service
work.
2. Remove side duct covers to access bottom return and supply
knock out covers (See Fig. 12).
3. To remove supply and return duct covers, break front and right
side connecting tabs with a screwdriver and a hammer. Push
cover down to break rear and left side tabs.
4. If unit ductwork is to be attached to vertical opening flanges
on the unit basepan (jackstand applications only), do so at this
time. Collect ALL screws that were removed. Do not leave
screws on rooftop as permanent damage to the roof may occur.
5. It is recommended that the hasepan insulation around the
perimeter of the vertical return-air opening be secured to the
basepan with aluminum tape. Applicable local codes may
require aluminum tape to prevent exposed fiberglass.
6. Cover both horizontal duct openings with the duct covers
shipped on the unit from the factory. Ensure opening is air-and
watertight.
7. After completing unit conversion, perform all safety checks
and power up unit.
NOTE: The design and installation of the duct system must be in
accordance with the standards of the NFPA for installation of
nonresidence-type air conditioning and ventilating systems, NFPA
90A or residence-type, NFPA 90B: and/or local codes and
ordinances.
Adhere to the following criteria when selecting, sizing, and
installing the duct system:
8. Select and size ductwork, supply-air registers, and return-air
grilles according to American Society of Heating, Refrigera-
tion and Air Conditioning Engineers (ASHRAE) recommen-
dations.
9. Use flexible transition between rigid ductwork and unit to
prevent transmission of vibration. The transition may be
screwed or bolted to duct flanges. Use suitable gaskets to
ensure weathertight and airtight seal.
10.All unitsmusthavefield-supplied filters or accessory filter
rack installed in the return-air side of the unit. Recommended
sizes for filters are shown in Table 1.
11. Size all ductwork for maximum required airflow (either
heating or cooling) for unit being installed. Avoid abrupt duct
size increases or decreases or performance may he affected.
12. Adequately insulate and weatherproof all ductwork located
outdoors. Insulate ducts passing through unconditioned space,
and use vapor barrier in accordance with latest issue of Sheet
Metal and Air Conditioning Contractors National Association
(SMACNA) and Air Conditioning Contractors of America
(ACCA) minimum installation standards for heating and air
conditioning systems. Secure all ducts to building structure.
13. Flash, weatherprooL and vibration-isolate all openings in
building structure in accordance with local codes and good
building practices.
I-
u
7 i !/
SUPPLY RETURN
DUCT DUCT
OPENING OPENING
Fig. 11---_upply and Return Duct Opening
VERTICALDUCT COVERS
Fig. 12--Vertical Duct Cover Removed
C99011
C99012
Step 8--Install Electrical Connections
Y:I |*?I:ITR]R [_
The unit cabinet must have an uninterrupted, unbroken
elecWical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground may
consist of an electrical wire connected to the unit ground lug
in the control compartment, or conduit approved for electrical
ground when installed in accordance with NEC (National
Electrical Code) ANSI/ NFPA (latest editionl (in Canada,
Canadian Electrical Code CSA [Canadian Standards Associa-
tion] C22.1) and local electrical codes. Failure to adhere to
this warning could result in personal injury or death.
W_P_.TLI__d[o]Ti
Failure to follow these precautions could result in damage to
the unit being installed:
1. Make all electrical connections in accordance with NEC
ANSI/NFPA(Iatest edition) and local electrical codes gov-
erning such wiring. In Canada. all electrical connections
must be in accordance with CSA standard C22.1 Canadian
Electrical Code Part l and applicable local codes. Refer to
unit wiring diagram.
2. Use only copper conductor for connections between
field-supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE,
3. Be sure that high-voltage power to unit is within operating
voltage range indicated on unit rating plate.
4. Do not damage internal components when drilling through
any panel to mount electrical hardware, conduit, etc. On
3-phase units, ensure phases are balanced within 2%.
Consult local power company for correction of improper
voltage and/or phase imbalance.
HIGH-VOLTAGE CONNECTIONS- The unit must have a
separate electrical service with a field-supplied, water-proof,
disconnect switch mounted at, or within sight from, the unit. Refer
to the unit rating plate for maximum fuse/circuit breaker size and
minimum circuit amps (ampacity) for wire sizing (See Table 3 for
electrical data).
The field-supplied disconnect switch box may be mounted on the
unit over the high-voltage inlet hole when the standard power and
low-voltage entry points are used (See Fig. 2 and 3 for acceptable
location).
See unit wiring label and Fig. 13 for reference when making high
voltage connections. Proceed as follows to complete the high-
voltage connections to the unit.
Single phase units:
1. Run the high-voltage (LI, L2) and ground leads into the
control box.
2. Connect ground lead to chassis ground connection.
3. Connect LI to pressure lug connection 11 of the compressor
contactor.
4. Connect L2 to pressure lug connection 23 of the compressor
contactor.
Three phase units:
1. Run the high-voltage (LI, L2, L3) and ground leads into the
control box.
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the lines side
of the contactor.