Installing and servicing air conditioning equipment
can be hazardous due to system pressure and electrical
components. Only trained and qualified service personnel
should install or service air conditioning equipment.
Untrained personnel can perform basic maintenance,
such as cleaning and replacing filters. All other opera
tions should be performed by trained service personnel.
When working on air conditioning equipment, observe
precautions in literature and on tags and labels attached
to unit.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for brazing operations.
Before installing or servicing unit, turn off main
power to system. There may be more than one
disconnect switch. Turn off accessory heater power
if applicable. Electrical shock can cause personal
injury.
_________________________________________
IMPORTANT: Final wiring inspection by local
authorities must be done before chassis is installed
in sleeve.
A WARNING
The Model 50ET,QT chassis is an uncased unit and,
therefore, requires special care in handling to prevent
injury to installer and damage to unit. A portable
lifting device must be used to move and position unit.
Be careful of sharp edges when handling chassis.
Page
I
1
1-4
3,4
Single-Package Units
INTRODUCTION
Install Model 50ET air conditioner or 50QT heat pump
chassis in accessory wall sleeve. See Table 2 for part
numbers. Wall sleeves are shipped separately with accom
panying installation instructions. All electrical power,
ductwork and condensate drain hookups are made at
time of wall sleeve installation.
IMPORTANT; Carrier standard outdoor grille or
deluxe outdoor grille must be ordered separately and
installed in wall sleeve before chassis is installed. Donot run unit without proper outdoor grille in place.
See Table 2 for part numbers.
INSTALLATION
Step 1 — Check Equipment and Jobsite
UNPACK UNIT — Move to final location. Lift card
board carton off chassis taking special care not to
damage unit.
INSPECT EQUIPMENT for damage prior to installa
tion. To remove metal cover plate, remove 6 screws. File
claim with shipping company if shipment is damaged or
incomplete.
Leave chassis bolted to skid and replace metal cover
plate and carton until ready for installation into wall
sleeve.
INSPECT WALL SLEEVE installation for damage.
Condensate drain pan must be free of debris and installed
in accordance with local building regulations. Electrical
connector on left side of sleeve should be free of dirt,
grease, paint, etc. Connector must be properly wired
before chassis installation. Duct connection panel must
be level and duct connections complete. Do not rest
weight of ductwork on duct connector panel. Inspect
nameplate on sleeve to ensure wire and fuse sizing is
correct for model size and heater accessory to be installed.
NOTE: If remote thermostat location is desired, location
must be determined and field wiring must be installed
before wall completion.
Step 2 — Install Chassis in Wall Sleeve —
Remove sleeve filler panel and save screws.
INSTALL ACCESSORY OUTDOOR GRILLE — In
stall outdoor grille using screws saved Refer to instruc
tions shipped with outdoor grille.
INSTALL ACCESSORY COLD CLIMATE PACK
AGE IF REQUIRED — Cold climate accessory should
be installed where the outdoor ambient temperature
consistently falls below 30 F. Refer to Table 2 for correct
accessory part number. Refer to instructions packaged
with aceessory for installation.
IMPORTANT. Be sure disconnect, per NEC,
installed with the wall sleeve is in OFF position
before proceeding with chassis installation.
Book |1 |1 |4 |4 PC 131 Catalog No 535-078 Printed inUS A Form 50ET,QT-3SI Pgl 5-85 Replaces: 50QT-10SI
Tab Ilbl5ahal5a
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.
For replacement items use Carrier Specitied Parts
50ET,QT
HEATING A COOLING
Table 1 — Electrical Data (60 Hz)
OPER
MODEL
50ET/QT
212300
215300208/230/1
218300
224300ft
230300ft
FLA — Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM — Indoor Fan Motor
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
OFM — Outdoor Fan Motor
RLA — Rated Load Amps
TD — Time Delay
‘Permissible limits of the voltage range at which units will operate
satisfactorily
V/PH
208/230/1
208/230/125418750
208/230/1254
208/230/1254187
VOLTS*
Max MintLRA
254187
25418743
187
CO^flPR
37
59
79
RLA
681 5
87
9 3
130
169
iPM
FLA
1 51 0
1 71 5
2 0
2 41 5
OFM
FLA
1 0
1 5
ELECTRIC
HEATER
kW
Amps
None
30
9 4/12 5
5.0
18.0/20.8
None
30509 4/12 5
18 0/20 8
None
30
9 4/12 5
50
18 0/20 8
7.5
26.8/31.3
None
50
17 3/20 8
7 5
26 8/31 3
100
36 1/41 7
None
50
17 4/20 8
7 5
26 8/31 3
36.0/41.7
10.0
Single-Package Units
BRANCH CiRCUiT #1
(or Total Unit)
Max TD Fuse or
HACR CktBkr Amps**
15/15
25/30
35/40
20/20
25/30
35/40
20/20
30/35
40/45
50/60
15/15
25/30
35/40
50/60
15/15
30/30
40/40
50/60
tMinimum voltage Is 197 when outdoor ambient temperature exceeds
105 F
^iFiold wiring to be sized per NEC or local codes Use copper wire only
"Maximum dual element fuse size
ttThese units require 2 separate supply circuits Refer to both branch
circuit charts for complete electrical data Two-circuitfused disconnect
must be field supplied
NOTE: Dual values in this table (for example: Electric Heater Amps:
9 4/12 5) apply to 208- and 230-volt connections, respectively
'For remote mounting only
tSuitable for mounting on unit chassis
Standard Aluminum Grille (six)All
Polymer Front Cover (two)
Cold Climate Package (one)All
Cooling Thermostats:
Automatic ChangeoverAll
Manual ChangeoverAll
Heat Pump Thermostats:
Two-Stage Heat, One-Stage Cool
Manual Changeover
Automatic Changeover
Manual ChangeoverAll
Manual Changeover
Electric Heaters (kW)
DESCRiPTiONMODEL 50ET.QT
3
5
75218
5
7 5224
10
5
7 5
10
212, 215, 218
224, 230
212, 215, 218
224, 230
212, 215, 218
212, 215, 218
All
224
224
230
230
230
w
SLIDE CHASSIS INTO SLEEVE — Chassis is heavy.
Portable lifting device must be used. Exercise caution
to be sure forks do not damage chassis components (such
Fig. 1 — Chassis with Accessory Indoor
Polymer Wrapper
as drain connections) while lifting and installing. Guide
chassis into sleeve on indoor side by first placing chassis
guide channels onto lower corners of sleeve. Slide chassis
into sleeve until center partition perimeter meets gasket
provided around outer edge of sleeve. Check electrical
plugs for alignment as chassis is slid into place.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.
Bookll II 14 14 PC 131 Catalog No 535-078 Printed in U S A Form 50ET.QT-3SI Pg2 5-85 Replaces: 50QT-10SI
Tab 1b 5al1a|5a For replacement items use Carrier Specilied Parts
Do not release chassis until installed and bolted
completely into sleeve as it may fall out without
warning.
A WARNING
50ET,QT
HEATING A C001.ING
OUTDOOR FAN
ORIFICE
REVERSING
VALVE
COMPRESSOR
CRANKCASE HEATER THERMOSTAT
CRANKCASE HEATER
«-OUTDOOR
ÌÌÌ COIL
DEFROST
THERMOSTAT
(NOT VISIBLE)
CHASSIS
GUIDE
CHANNEL
50QT212.215 (shown), 218
Fig. 2 — Outdoor Component Location
Tighten chassis into place by driving 6 lag bolts, pro
vided in separate bag with chassis into nuts provided on
sleeve (see Fig. 3).
Electrical and condensate drain connections are com
plete when chassis is installed correctly into sleeve.
A CAUTION
Tighten lag bolts uniformly. Failure to do so may
cause misalignment and poor electrical connection.
ACCURATER'^“
DEVICE
LOCATION
MAIN
CONTROL
BOX
COVER
ELECTRIC HEATER COMPARTMENT
INDOOR
BLOWER AND
MOTOR
ASSEMBLY
COMPRESSOR
SUCTION
PRESSURE
PORT
LOCATION
Single-Package Units
OUTDOOR
FAN MOTOR
(PROPELLER
FAN AND GUARD
REMOVED)
stat can be installed on the 50ET,QT chassis or in a
remote location.
TO MOUNT THERMOSTAT IN UNIT-
1. Remove metal cover plate by removing 6 screws.
2. Locate and install subbase onto thermostat bracket
running between right and left coil partition (see
Fig. 3). Push field-supplied thermostat wires through
hole provided.
SLEEVE JUNCTION BOX
ACCESS PLATE
CONTROL
BOX
(SLIDES
OUT FOR
SERVICE)
CHASSIS
MOUNTING
BOLTS (6)
INDOOR
ACCESSORY ELECTRIC HEATER
LOW-PRESSURE
SWITCH
DEFROST
THERMOSTAT
COMPRESSOR
SUCTION
SERVICE
PORT
(NOT VISIBLE)
CENTER
PARTITION
INDOOR
CONDENSATE
DRAIN
50QT224,230
INDOOR
NAMEPLATE
INDOOR AIR FILTER
50QT212,215,218
THERMOSTAT
MOUNTING
BRACKET
Fig. 3 — Indoor Component Location
Book|1 II 14 14 PC131 Catalog No 535-078 PrintedinUSA Form 50ET,QT~3SI Pg3 5-85 Replaces; 50QT-10SI
- • For replacement Hems use Carrier Specilled Parts.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
INDOOR AIR FILTER LOCATION
(NOT SHOWN)
LEFT COIL PARTITION
THERMOSTAT
MOUNTING
BRACKET
50ET,QT
HEATING A COOLING
(5>
S>]
(5>
THERMOSTAT AND
SUBBASE (SEE BELOW)
THERMOSTAT
99TZ90032199TZ900361
99TZ900321
COOLING UNIT WITH ELECTRIC HEAT HEAT PUMP WITH SUPPLEMENTAL ELECTRIC HEAT
JM.
JH
WIRES FROM
JZL
UNIT CONTROL BOX
_0_
SUBBASE
99TZ900391
Fig. 4 — Thermostat Connection Diagrams — 50ET,QT
Single-Package Units
UNIT CONTROL BOX
WIRING TERMINAL BOARD
THERMOSTAT/SUBBASE
99TZ900291
99TZ900401
99TZ900511
99TZ900541
3. Route thermostat wires through hole located on left
coil partition and up to low-voltage wire entrance
hole on control box front cover.
4. Remove 2 screws and slide control box to expose
low-voltage terminals. Attach wires to appropriate
terminals as shown on unit wiring diagram. See Fig. 4.
5. Attach thermostat to subbase and snap on thermostat
cover.
6. Cut and remove insulation from hole in metal cover
plate.
7. Replace metal cover plate.
8. Install accessory polymer front cover as described in
instructions shipped with accessory cover. Cut
rectangular hole for thermostat as indicated by mark
in back of cover.
TO MOUNT THERMOSTAT REMOTELY-
1. Pull field-supplied thermostat wires previously
installed up into wire entrance hole on control box
front cover and connect wires as described in Step 3,
paragraph 4, above.
2. Connect other ends of thermostat wires, hanging from
the wall at their remote location, securely into subbase
at appropriate terminals specified in unit wiring
diagram. See Fig. 4.
3 Mount subbase onto wall.
4. Attach thermostat to subbase. Snap on cover and
install chassis indoor cover.
Step 4 — Set Indoor Fan Motor Speed — All
units are factory wired for low fan speed. Higherexternal
static pressure requirements can be met by wiring motor
for higher fan speed. See Table 3.
Step 5 — Install Accessory Electric Heater,
If Required — Refer to instructions packaged with
accessory heater. See Table 2 for part numbers.
» Table 3 — Service Data
SIZE
MODEL 50
R-22 CHARGE* (lb)
Refrig Control
INDOOR FAN
Rotationt
Rpm
Diameter (in.)
Width (In.)
Range (cfm)
Motor Hp
OUTDOOR FAN
Ctm
Rpm
Diameter (In)
Motor Hp
CCW — Counterclockwise
CW — Clockwise
‘Factory refrigerant charge
tLooking at fan motor shaft
212
ET I QT
2 3 I 2 7
215
ET lOTET 1 QT
23)27
AccuRa
CW I CW I CW I CCW I CCW
1580 1550 1570 1675 1675
430/ 1 550/ 1 575/ 1 885/ 1 1025/
Propeller, Direct Drive, Single Speed
1700 1 1700 1 2000 1 2000 1 2000
218
3 1 1 3 75
ter'" BypaE
Centrifugal Blower,
Direct Drive, 2-Speed
6 1 6 1 6 1 7 1 7
8
375 475 480 800 960
V. 1 '/, 1 % 1 '/4 1 '/4
1125
15
’/b
224230
ET 1 QT ET 1 QT
4.0 1 4 5
s Type
39)47
START-UP
Crankcase Heater — The 50QT compressor is
equipped with a crankcase heater that is thermostatically
activated in cold weather. (See Fig. 2 and 3.) If tempera
ture is below 65 F, operate crankcase heater 24 hours
before starting unit. To energize crankcase heater only,
after chassis installation, set thermostat to ^^
position (for thermostat mounted on the chassis) or OFF
position (for remote-mounted thermostat) and turn on
unit power at disconnect switch.
t
Bookn 11 |4 |4 PC 131 Catalog No 535-078 PrintedinUSA Form 50ET.QT-3SI Pg4 5-85 Replaces 50QT-10SI
Tab llbisahalsa
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.
For replacement items use Carrier Specified Parts
50ET,QT
HEATING A COOLING
To Start Unit — Check that main power is on and,
if temperature is below 65 F, that compressor crankcase
heater has been energized for at least 24 hours.
1. Set selector switch at <; -O—^ if thermostat is
mounted on chassis, or at OFF if thermostat accessory
is remote mounted.
2. Set fan switch as desired (FAN) (AUTO.).
3. Set thermostat lever at the desired temperature.
4. Set selector .switch at HEAT or COOL. Check sy.stem
refrigerant charge. See Refrigerant Charging.
SERVICE
Service Port Connections — High and low side
pressure connections are accessible from the indoor
portion of the unit for charging. (See Fig. 3.)
Low-Pressure Switch (50QT only) (Safety
Control) is located on liquid line downstream of Accu-
Rater™ control during cooling mode (or upstream of
AccuRater control during heating mode). Switch opens
at 5 psig and shuts down compressor to protect it from
overheating if refrigerant charge is too low.
High-Pressure Relief Valve (Safety Control) is
located in compressor. Relief valve opens at a pressure
differential of approximately 450 ± 50 psi between
suction (low side) and discharge (high side) to allow
pressure equalization.
Internal Current and Temperature Sensitive
Overload (Safety Control) resets automatically
when compressor motor temperature drops to a safe level
(overloads may require up to one hour to reset). When an
internal overload is suspected of being open, check by
using an ohmmeter or continuity tester. If necessary,
refer to Carrier Standard Service Techniques Manual,
Chapter 2, Electrical, for complete instructions.
Defrost Control consisting of a control board and
defrost thermostat, interrupts normal system heating
operation to remove frost and iee formation on outdoor
Single-Package Units
coil. Frost impairs unit performance. Defrost control
simultaneously stops outdoor fan, energizes reversing
valve solenoid to switch system into cooling cycle (out
door unit as condenser, indoor unit as evaporator), and
activates accessory electric heater. Unit can defrost every
90 minutes, but will do so only if outdoor temperatures
are in the frosting temperature zone.
For heat pump to defrost, 2 eonditions are necessary;
1 Defrost circuit board contacts must be closed.
2. Coil temperature must be cold enough to cause defrost
thermostat contacts to close.
Contacts clo.se at 27 ±5 F. Every 90 minutes of elap.sed
running time, the defrost circuit board contacts close for
10 seconds. If the defrost thermostat contacts are closed,
the unit defrosts The defrost circuit board limits defrost
ing period to 10 minutes. Normally the frost is removed
and the defrost thermostat contacts will open to terminate
defrosting before 10 minutes have elapsed. Defrost
thermostat contacts open at 80 ±5 F. When defrosting is
terminated, the outdoor fan motor is energized and
reversing valve solenoid is de-energized, returning unit
to heating cycle.
HEAT PUMP CIRCUITS shown in Fig. 5 are refrig
erant flow diagrams for heating and cooling cycles.
Refrigerant Charging
A CAUTION
To prevent personal injury, wear safety glasses and
gloves when handling refrigerant.
Do not overcharge system. An overcharge can
cause compressor damage.
Unit refrigerant system is factory charged. When
recharging is necessary, weigh in total charge indicated
in Table 3. (Charge must be weighed in during heating
season.) Remove any refrigerant remaining in system
before recharging. If system has lost complete charge.
3 Unit Piping
Fig. 5 — 50QT Refrigerant Flow Diagrams
Manulacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.
Bookll h |4 |4 PC131 Catalog No 535-078 PrintedinUSA Form 50ET,QT-3S1 Pg5 5-85 Replaces: 50QT-10SI
FROcTlT^r^ Pgj replacement items use Carrier Specified Parts
Loading...
+ 9 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.