Carrier 50DPE014 User Manual

0 (0)
50DPE014
50DP016,020
HEATING & COOLING
Single-Package Cooling Units
Installation, Start-Up and Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS INSTALLATION
Step 1 — Provide Unit Support
..................................................
..........................
1 1-10
1
• ROOF CURB
• ALTERNATE UNIT SUPPORT
Step 2 — Rig and Place Unit
...............................
1
• POSITIONING
• ROOF MOUNT
Step 3 — Field Fabricate Ductwork Step 4 — Make Unit Duct Connections Step 5 — Trap Condensate Drain
Step 6 — Make Electrical Connections
...................
.............
.......................
..............
6 6
6
7
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
Step 7 — Make Outdoor Air Inlet
Adjustments
......................................................
7
• MANUAL OUTDOOR AIR DAMPER
• OPTIONAL ECONOMIZER
Step 8 — Install Outdoor Air Hood.................. 10
START-UP..........................................................10-13
SERVICE.............................................................14-16
SAFETY CONSIDERATIONS
Installation and servicing of air conditioning equip ment can be hazardous due to system pressure and elec trical components. Only trained and qualified service personnel should install, repair or service air conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air condi
tioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety pre cautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations.
Have fire extinguishers available for all brazing
operations.

A WARNING

Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.
INSTALLATION
Step 1 — Provide Unit Support
ROOF CURB — Assemble and install accessory roof curb in accordance with instructions shipped with this accessory. Accessory roof curb and information required to field fabricate a roof curb are shown in Fig. 1 and 2.
Install insulation, cant strips, roofing and flashing as shown. Ductwork can be installed to roof curb before unit. is set in place. Curb should be level. Unit leveling toler
ance is ± 1/16 in. per linear ft in any direction. This is
necessary to permit unit drain to function properly. Refer
to Accessory Roof Curb Installation Instructions for
additional information as required.
ALTERNATE UNIT SUPPORT — When the curb
cannot be used, support unit with sleepers using unit curb
support area. If sleepers cannot be used, support long
sides of unit with a minimum of 3 equally spaced 4-in. x
4-in. pads on each side.
Step 2 — Rig and Place Unit — Inspect unit for
transportation damage. File any claim with transporta
tion agency. Do not drop unit, keep upright. Use spreader bars over unit to prevent sling or cable damage. Rollers may be used to move unit aeross a roof. Level by using unit frame as a reference; leveling toleranee is ± 1/16 in. per linear ft in any direction. See Fig. 3 for additional information. Unit weight is shown in Table 1.
Four lifting holes are provided in ends of unit base rails
as shown in Fig. 3. Refer to rigging instructions on unit.
POSITIONING — Provide clearance around and above
unit for airflow, safety and service access (Fig. 4).
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book|l l4 PC111 Catalog No 565-104 PrintedinUSA Form 50DP-26SI Pg 1 7-88 Replaces: 50DP-25S1 Tab |1b|6b
NOM I^"x4"
(32) X (102) TYP. 4 PLACES
ROOF OPENINGS
Dimensions miilimeters. Attach aii ductwork to roof curb Fieid installation of sidewall insulation is mandatory
Fig. 1 — Roof Curb Details
INDOOR AIR FAN MOTOR
(50PQ900I5I)
INDOOR AIR FAN MOTOR 50DP020
TRANSITION DUCT
Fig. 2 — Side Supply/Return Curb Details
Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
ROOF MOUNT — Check building codes for weight dis
tribution requirements. Unit weight is shown in Table 1.
INSULATION FIELD SUPPLIED (SEE NOTE 3)
RIGGING WEIGHTS* (lb)
COIL FIN MATERIAL
MODEL
50DPE014 1880 1960 50DP016 50DP020
'Includes economizer weight
NOTE Rig by inserting hooks Into unit base rails as shown Main tain a distance of 120 in (3048 mm) from top of unit to eyehook Use corner post from packaging to protect coil of unit from damage by rigging cable. Use bumper boards for spreader bars
OUTDOOR/INDOOR
AI/AI
1880 1960 2390
Cu/AI Cu/Cu
2520 2630
2040 2040
CAUTION!
All panels must be in place when rigging.
Fig. 3 — Rigging Details
©
25% AIR OR ECONOMIZER HOOD
% FPT DRAIN
CONNECTION
INDOOR AIRFLOW
0
' OUTDOOR AIRFLOW
> ALTERNATE AIRFLOW
Fig- 4 — Physical Data and Dimensions
FRONT VIEW
I SPACE REQUIRED FOR
LLiia SERVICE AND AIRFLOW
Table la — Physical Data — 50DPE014
UNIT SIZE OPERATING WEIGHT (lb)
Unit (Outdoor Coil/Indoor Coil)
AI/AI Al/Cu
Cu/Cu Roof Curb Economizer Electric Heat Alternate Motor and Drive
COMPRESSOR
Quantity 1 Oil (oz)
REFRIGERANT
Charge (lb) Sys 1*, Sys 2
REFRIGERANT METERING DEVICE
Upper Circuit
Quantity...Length...lD/OD (in.)
OUTDOOR COIL
Rows Fins/in.
Aluminum Copper
Total Face Area (sq ft)
OUTDOOR AIR FAN
Nominal Cfm Quantity...Diameter (in.) 2 ..26
Motor Hp (1075 Rpm)
INDOOR COIL
Rows Fins/in.
Aluminum Copper
Total Face Area (sq ft)
INDOOR AIR FANf
Quantity...Size (in.) Nominal Cfm
Max Allowable Rpm
Motor Pulley Pitch Diameter (in.) Std
Fan Pulley Pitch Diameter (in.) Belt, Quantity...Type...Length (in.)
Speed Change per Full Turn Std 58
of Moveable Pulley Flange (Rpm) Opt
Moveable Pulley Max Full Turns
from Closed Position
Factory Setting — Full Turns Open
Factory Speed Setting (Rpm) Std
Motor Hp (Service Factor) Std
HIGH-PRESSURE SWITCH
Cutout (psig)
Reset (psig)
LOW-PRESSURE SWITCH (Liquid Line)
Cutout (psig)
Reset (psig)
Rpm Range Std
Opt 978-1265
Opt
Opt Opt
Copper Tube, Aiuminum or Copper Plate Fins
Copper Tube, Aluminum or Copper Plate Fins
AIR INLET SCREENS
Economizer, Number...Size (in.)
INDOOR AIR FILTERS (Type)
10% Efficient — Disposable Fiberglass
50DPE014
Semi-Hermetic — 6 Cyiinders
Capiilary Tubes
6 25 0 055/0 125 6 25 0 055/0 125
6.25,0 055/0 125
Propeller Type, Direct Drive
Centrifugal, Belt Drive
2 20x25x1 1 20x20x1
1470 1550
1630
200 110
65
5
160
20 8
3
136 124 189
12,000
1
3
14.3 13 1
165
2 .10x10
5000
805-1093
1550 2 8-3.8 3 4-4.4
6.0
1. V. 43 57
3
920
1092 2 (1 15) 3 {1 15)
428 320
27 60
Number...Size (in.) 2. 20x20x2
'System 1 consists of upper portion of outdoor coii and iower portion of indoor coii
tUnits have adjustable standard and alternate drives
3 . 16x20x2 2 16x25x2
4
i
Table 1b — Physical Data — 50DP016,020
UNIT SIZE OPERATING WEIGHT (lb)
Unit (Outdoor Coil/Indoor Coil)
AI/AI Al/Cu
Cu/Cu Roof Curb Economizer Electric Heat
COMPRESSOR Semi-Hermetic — 6 Cylinders
Quantity 1 2
Oil (oz)
REFRIGERANT
Charge (lb) Sys 1*, Sys 2
REFRIGERANT METERING DEVICE
Upper Circuit
Quantity...Length...ID/OD (in.)
Lower Circuit
Quantity...Length...ID/OD (in.)
OUTDOOR COIL
Rows Fins/in.
Aluminum Copper
Total Face Area (sq ft)
OUTDOOR AIR FAN
Nominal Cfm Number...Diameter (in.) Motor Hp (1075 Rpm)
INDOOR COIL
Rows Fins/in.
Aiuminum Copper
Totai Face Area (sq ft)
INDOOR AIR FANf
Quantity...Size (in.) Nominai Cfm Rpm Range Std
Maximum Aliowable Rpm Motor Puiiey Pitch Diameter (in.) Std
Fan Pulley Pitch Diameter (in.)
Belt, Quantity...Type...Length (in.) Speed Change per Full Turn Std
of Moveable Pulley Flange (Rpm) Opt
Moveable Pulley Max Full Turns
from Closed Position Factory Setting — Full Turns Open Factory Speed Setting (Rpm) Std
Motor Hp (Service Factor) Std
HIGH-PRESSURE SWITCH
Cutout (psig)
Reset (psig)
Opt Puiley A Puiiey B
Opt Pulley A Pulley B
Opt
Pulley A
PulleO B
Opt
LOW-PRESSURE SWITCH (Liquid Line)
Reset (psig)
AIR INLET SCREENS
Economizer, Number...Size (in.)
INDOOR AIR FILTERS (Type)
Number...Size (in.)
50DP016
1470 1980 1550 2110 1630
160
R-22
21.2
6.40. 0.065/0 125
6..2 0.0 055/0.125
6.20 0 055/0 125
Copper Tubes, Aluminum or Copper Plate Fins
3
136
12.4
18.9
12,000
2 .26
1
Copper Tubes, Aluminum or Copper Plate Fins 3
143
13 1
16.5
2 ..10x10
6000
916-1186
1158-1428
848
1550 3 4-4 4 4 3-5 3
6.4
1. .V...45
54 55
3.5 970
1240
848
3 (1 15)
10% efficient — Disposable Fiberglass
2 20x20x2
3. 16x20x2
2. .16x25x2
Propeller Type, Direct Drive
200 110
65
Capillary Tubes
Centrifugal, Belt Drive
428 320
97
60
2. .20x25x1
1...20x20x1
13.25.0 055/0 125
13 .25 ..0 055/0.125
50DP020
2220
160 ea
R-22
17.0, 17.0
4
13.6
12.4
22.2
11,400
2. ,26 1
4
14.4
13.1
17.9
2 .12x12
7200
1060 1550
32 40
6.6
2 V..45
1060
5 (1 15)
4 20x20x2
4.. 16x20x2
c
•System 1 consists of upper portion of outdoor coil and lower portion of indoor coil, except forsize020 which is intertwined
t016 unit has adjustable standard and alternate drives The 020
unit does not have an aiternate drive, but has 2 non-adjustable pulieys Pulley A is instailed in unit, pulley B is shipped with unit
Loading...
+ 11 hidden pages