Carrier 48TM028, 48TM020, 48TM025, 48TM016 User Manual

Page 1
Heating/Cooling Units
User’s Information Manual
48TM016-028
Combination
NOTE TO INSTALLER
This manual should be left with the equipment owner.
WARNING: If the information in this man­ual is not followed exactly, a fire or explo­sion may result causing property dam­age, personal injury or loss of life.
— Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas sup­plier, call the fire department.
— Installation and service must be per-
formed by a qualified installer, service agency or the gas supplier.
TO LIGHT UNIT
1. Do not turn off the electrical power to unit without first turning off the gas supply .
2. Before attempting to start the gas heating section, familiarize yourself with all the procedures that must be followed.
3. Never attempt to manually light the pilot on unit with a match, lighter, or any other flame. If the electric sparking device fails to light the pilot, refer to the shutdown procedures, then call your dealer as soon as possible.
If you do not follow these instructions exactly, a fire or explosion may result, causing property damage, injury, or loss of life.
See Fig. 1 for location of gas valves. Refer to Fig. 2 while
proceeding with the following steps.
Step 1 —
setting and set SYSTEM switch to HEA T position.
Step 2 —
Step 3 —
Step 4 —
Step 5 —
valve counterclockwise to the OFF position and wait 5 minutes.
Set room thermostat to the lowest temperature
Close the external manual gas valve. Turn off the electrical supply to the unit. Remove the burner compartment access panel. Turn the control dial on the internal gas
Improper installation, adjustment, alteration, ser­vice or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.
Before performing recommended maintenance, be sure main power switch to unit is turned off and lockout tag is installed. Electrical shock could cause personal injury.
Your combin ation heating/cooling unit is equipped with an automatic intermittent pilot and induced draft power combus­tion blower.
Pilot will light automatically. Do not attempt to light by hand; personal injury may result.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 1 a 6 a
PC 111 Catalog No. 534-80112 Printed in U.S.A. Form 48TM-1SO Pg 1 5-02 Replaces: New
Step 6 —
wise to ON position.
Step 7 —
Step 8 —
Step 9 —
Step 10 —
room temperature to start unit. The induced-draft combustion air fan will start. Main burners light within 30 seconds. Indoor blower will start within a few minutes of main gas ignition.
Step 11 —
to desired setting.
Turn control dial on internal gas valve clock-
Replace the burner compartment access panel. Turn on the electrical supply to unit. Open the external gas valve.
Set room thermostat selector slightly above
Set the temperature selector on room thermostat
Page 2
INDUCED DRAFT MOTOR
INTEGRATED GAS UNIT CONTROLLER (HIDDEN)
MAINTAINING YOUR UNIT
All maintenance should be handled by skilled, experienced personnel. Your dealer can help you establish a standard procedure.
For your safety, keep the area around the unit clear and free of combustible materials, gasoline, and other flammable liq­uids and vapors.
T o assure proper functioning of the unit, flow of combustion and ventilating air must not be obstructed from reaching the unit. Clearance of at least 4 ft on all sides is required.
ROUTINE MAINTENANCE AND CARE
FOR THE EQUIPMENT OWNER
Before proceeding with those things you might want to maintain yourself, please carefully consider the following:
COMBUSTION FAN HOUSING
MAIN BURNER SECTION
FLUE BOX COVER
MAIN GAS VALV E
Fig. 1 — Typical Gas Heating Section
If the pilot fails to light, the main burner fails to light, or the blower fails to come on, shut down gas heating section and call your dealer for service. Failure to follow these require­ments could result in serious personal injury.
TO SHUT UNIT OFF
Do not turn off the electrical power to unit w ithout first turning off the gas supply .
Failure to follow these procedures can result in serious
fire or personal injury.
See Fig. 1 for location of gas valve. Refer to Fig. 3 while
proceeding with the following steps.
Step 1 —
and set SYSTEM switch to OFF position.
Step 2 —
Step 3 —
Step 4 —
Step 5 —
valve counterclockwise to the OFF position.
Step 6 —
Step 7 —
tion, call your dealer as soon as possible.
If unit is being shut down because the heating season has ended, restore electrical power to the uni t to ensure operation of the cooling system during the cooling season.
Should overheating occur, or the gas supply fail to shut off, shut off the manual gas valve to the unit before shutting off the electrical supply.
Do not use this unit if any part has been under water. Imme­diately call a qualified service technician to inspect the unit and to replace any part of the control system and any gas control which has been under water.
Set room ther m ostat to lowe st te m p e rature setting
Close the external manual gas valve.
Turn off the electrical power supply to the unit. Remove the burner compartment access panel. Turn the control dial on the internal gas
Replace the burner compartment access panel. If unit is being shut down because of a malfunc-
1. TURN OFF GAS SUPPLY AND ELECTRICAL POWER TO YOUR UNIT BEFORE SERVICING OR PERFORMING MAINTENANCE.
2. Do not turn off electrical power to this unit without first turning off the gas supply .
3. When removing access doors or performing mainte­nance functions inside your unit, be aware of sharp sheet metal parts and screws. Although special care has been taken to reduce sharp edges to a minimum, be extremely careful when handling parts or reaching into the unit.
Air Filters —
Air filters should be checked at least every 3 or 4 weeks and changed or cleaned whenever they become dirty. Table 1 indicates the correct filter size for your unit. Re­move the filter access p a n e l t o r e p la c e o r in s p ec t th e f ilters. All units have filter tracks into which the filters sl ide. Remove t he filters by pulling outward from the track. See Fig. 4 for filter access panel location. Note the direction of flow arrows on the filter frame.
For horizontal supply/return units, the size, location and number of air filters varies from Table 1. If you have difficulty in locating your air filter in the return-air duct system, or if you have questions concerning proper filter maintenance, contact your dealer for instructions. When replacing your unit filters, always use the same size and type of filter that was originally supplied by the installer.
Units with outdoor air capability have a cleanable filter for the outdoor air. This filter should be checked annually and cleaned as necessary. Remove by removing screws in outdoor air filter retainer and sliding filters out of the unit.
Never operate your unit without filters in place. Failure t o heed this warning may result in damage to the blower motor and/or compressor. An accumulation of dust and lint on internal parts of your unit can cause loss of efficiency and in some cases, fire.
Table 1 — Indoor-Air Filter Data*
UNIT SIZE
48TM
016-028†
*When replacing filters, always use the same type and size origi-
nally supplied.
†The 48TM028 unit requires 2-in. industrial grade filters capable of
handling face velocities of up to 625 ft/min (such as American Air Filter no. 5700 or equivalent).
TYPE OF
FILTER
Fiberglass
Throwaway
QUANTITY...SIZE (in.)
4...20 x 20 x 2
4...16 x 20 x 2
2
Page 3
STEP 1
STEP 2
STEP 4 STEP 5
STEP 3
STEP 8
STEP 6
STEP 9
Fig. 2 — To Light Unit
3
STEP 7
STEP 10
Page 4
STEP 1
STEP 1
STEP 2
STEP 2
STEP 3
STEP 3
48TFD005-009 48TFE004-007 48TFL005,006 48TFM004-006
STEP 4
STEP 6
48TFF004-012 48TFD012,014 48TFE008,014 48TFN004-006
STEP 4
STEP 5
48TFD005-009 48TFE004-007 48TFL005,006 48TFM004-006
48TFF004-012 48TFD012,014 48TFE008,014 48TFN004-006
STEP 5
STEP 7
STEP 8
STEP 6
Fig. 3 — To Shut Unit Off
STEP 9
Fig. 2 — To Light Unit
4
STEP 10
STEP 7
Page 5
HOOD (OPTION)
OUTDOOR-AIR FILTER RETAINER
HOOD (OPTION)
OUTDOOR-AIR FILTERS
48TM016, 020
BURNER ACCESS PANEL (HIDDEN)
BURNER ACCESS PANEL (HIDDEN)
MOTORS AND FILTER ACCESS PANEL
seal is maintained. Contact your dealer for the required period­ic maintenance.
Fans and Belts —
Periodically check the condition of fan wheels and housings, and belt tension. When service is nec­essary, call your dealer .
Evaporator-, Condenser-, and Combustion Fan Motors —
will not require lubrication for at least 5 years of normal opera­tion. After 5 years, motor life can be extended by having the motors serviced at an authorized motor service shop.
Fan Shaft Bearings —
ed. When service is necessary, call your dealer.
Evaporator and Condenser Coils —
coils should only be done by qualified service personnel. Con­tact your dealer for the required annual maintenance.
Condensate Drain —
drain line should be checked and cleaned at the same time the cooling coils are checked by your dealer.
Compressor —
a normal charge of the correct type re frigeration grade oil in them and should rarely require additional oil. The service tech­nician must be certain the proper oil level is maintained in the compressor when it is installed and running.
Lubrication is not recommended. Bearings
Lubrication is not recommend-
Cleaning of the
The drain pan and condensate
All compressors are factory shipped with
Condenser Fan
OUTDOOR­AIR FILTER RETAINER
HOOD (OPTION)
OUTDOOR­AIR FILTER RETAINER
OUTDOOR­AIR FILTERS
BURNER ACCESS PANEL (HIDDEN)
OUTDOOR­AIR FILTERS
48TM025
48TM028
MOTOR AND FILTER ACCESS PANEL
MOTOR AND FILTER ACCESS PANEL
Fig. 4 — Panel Locations
Heat Exchanger —
To ensure dependable and efficient heating operation, the heat exchanger should be checked by a qualified maintenance person before each heating season, and cleaned when necessary. This checkout should not be attempt­ed by anyone not having the required expertise and equipment to do the job properly. Checking and/or cleaning the heat exchanger involves removing the gas controls assembly and the flue collector box cover and, when completed, reinstalling the gas controls assembly for proper operation. Also, the flue collector box cover must be replaced correctly so that a proper
Do not poke sticks, screwdrivers, or any other object into revolving fan blades. Severe bodily injury may result.
The fan must be kept free of all obstructions to ensure
proper cooling. Contact your dealer for any required service.
Electrical Controls and Wiring —
Electrical controls are difficult to check without proper instrumentation; therefore, if there are any discrepancies in the oper ating cycle, contact your dealer and request service.
Integrated Gas Controller (IGC) —
The IGC board incorporates an LED that emi ts a flashing light to indicat e an alarm code. If the furnace section will not operate and the LED is flashing a code (2 to 8 flashes in succession), contact your dealer and request service. See Fig. 1.
Refrigerant Circuit —
The refrigerant circuit is difficult to check for leaks without the proper equipment; therefore, if inadequate cooling is suspected, contact your dealer for service.
Combustion Area and Vent System —
The com­bustion area and vent system should be visually inspected before each heating season. The normal accumulation of dirt, soot, rust, and scale can result in loss of efficiency and improp­er performance if allowed to build up.
If your unit makes an especially loud noise when the main burners are ignited, shut down the heating section and call your dealer.
See Fig. 1 and proceed as follows to inspect the combustion
area and power-venting system of your unit.
1. Turn off electrical power and gas supply to your unit.
2. Remove burner compartment access panel.
5
Page 6
3. Using a flashlight, carefully inspect the burner areas for dirt, soot, rust, or scale.
If dirt, soot, rust, or scale accumulations are found, call your dealer and do not operate your heating section.
4. When you have completed your inspection, follow the start-up procedures in this manual to restore your unit to operation.
5. Observe unit heating operation, and watch the burner flame with the access panel removed, to see if it is bright blue. If you observe a suspected malfunction, or that the burner flames are not bright blue, call your dealer. See Fig. 5. Some yellow flame may be present due to the pan­el being removed.
6. Replace burner compartment access panel.
Fig. 5 — Proper Flame Appearance
Unit Panels —
service on the unit, be sure all panels are securely fastened in place to prevent rain from entering unit cabinet and to prevent disruption of the correct unit airflow pattern.
After performing any maintenance or
REGULAR DEALER MAINTENANCE
In addition to the type of routine maintenance you might be willing to perform, your unit should be inspected regularly by a properly trained service technician. An inspection (preferably each year, but at least every other year) should include the following:
1. Inspection of all flue product passages — including the burners, combustion baffles, heat exchanger, flue collec­tor box, and vent pipe.
2. Inspection of all combustion- and ventilation-air passages and openings.
3. Close inspection of all gas pipes leading to and inside your unit.
4. Inspection, and if required, cleaning of the condenser and evaporator coils.
5. Inspection, and if required, cleaning of the evaporator drain pan.
6. Inspection, cleaning, and lubrication of blower wheel housing and motor.
7. Inspection of all supply- and return-air ducts for leaks, obstructions, and insulation integrity. Any problems found should be resolved at this time.
8. Inspection of the unit base to ensure that no cracks, gaps, etc., exist which may cause a hazardous condition.
9. Inspection of the unit casing for signs of deterioration.
10. Inspection of all electrical wiring and components to assure proper connection.
11. Inspection for leaks in the refrigerant circuit. Pressure­check to determine appropriate refrigerant charge.
12. Operational check of the unit to determine working con­ditions. Repair or adjustment should be made at this time.
13. Your servicing dealer may offer an economical service contract that covers seasonal inspections. Ask f or further details.
Complete Service Instructions can be found in the unit
Installation, Start-Up and Service Instructions literature.
BEFORE YOU CALL FOR SERVICE
CHECK FOR SEVERAL EASILY SOLVED
PROBLEMS
If insufficient heating or cooling is suspected: ( ) Check for sufficient airflow. Check the air filter for dirt.
Check for blocked return- or supply-air grilles. Be sure they are open and unobstructed. If these checks do not reveal the cause, call your servicing dealer.
If your unit is not operating at all, check the following list
for easy solutions: ( ) Check to be sure that your thermostat temperature selector
is set above the indoor temperature during the heating season, or below the indoor temperature during the cooling season. Be sure the SYSTEM switch is in the proper HEAT or COOL position and not in the OFF position.
( ) Is the electrical supply switch ON? Are any fuses blown, or has the circuit breaker tripped?
( ) During the heating season, check the manual shutoff valve. Is this lever parallel with the pipe, indicating that the valve is open? Or is the lever at a right angle, indicating that the valve is closed? If closed, has the gas been shut off for safety rea­sons? Otherwise, you may open the valve and follow the start­up procedures listed in this manual.
NOTE: Before proceeding with the next check, turn off the electrical power supply to the unit. Rem ove the control a ccess door.
( ) During the heating season, che ck the control dial on the gas valve. Is it in the ON position? If it is not, be sure it has not been turned off for the purpose of safety. If nothing else seems to be amiss, follow the start-up procedures in this manual.
( ) If your unit still fails to operate, call your servicing dealer for troubleshooting and repairs. Specify the model and serial numbers of your unit. (Record them in this manual in the space provided.) If the dealer knows exactly which unit you have, he may be able to offer suggestions over the phone, or save valuable time through knowledgeable preparation for the service call.
IN CASE OF TROUBLE
If, after performing the above, unit pe rformance is unsatis-
factory, shut of f the unit and call your dealer . Dealer’s Name _____________________________________ T elephone No. _____________________________________ Unit Model ________________________________________ Unit Serial Number _________________________________
6
Page 7
Page 8
Copyright 2002 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 1 a 6 a
PC 111 Catalog No. 534-80112 Printed in U.S.A. Form 48TM-1SO Pg 8 5-02 Replaces: New
Loading...