Carrier 48TM016-028 User Manual

48TM016-028
Single-Package Rooftop Units
Electric Cooling/Gas Heating
Installation, Start-Up and Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS
INSTALLATION ..................................2-32
Step 1 — Provide Unit Support.....................2
• ROOF CURB
• ALTERNATE UNIT SUPPORT
Step 2 — Rig and Place Unit .......................2
• POSITIONING
• ROOF MOUNT
Step 3 — Field Fabricate Ductwork
Step 4 — Make Unit Duct Connections ...........11
Step 5 — Install Flue Hood and Wind Baffle ......11
Step 6 — Trap Condensate Drain .................11
Step 7 — Orifice Change ..........................12
Step 8 — Install Gas Piping .......................13
Step 9 — Make Electrical Connections ...........13
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
• OPTIONAL NON-FUSED DISCONNECT
• OPTIONAL CONVENIENCE OUTLET
Step 10 — Make Outdoor-Air Inlet
Adjustments
• MANUAL OUTDOOR-AIR DAMPER
Step 11 — Install Outdoor-Air Hood
Step 12 — Install All Accessories ............... 17
• MOTORMASTER® I CONTROL INSTALLATION
• MOTORMASTER V CONTROL INSTALLATION
Step 13 — Adjust Factory-Installed Options..... 19
• PREMIERLINK™ CONTROL
• ENTHALPY SWITCH/RECEIVER
• OUTDOOR ENTHALPY CONTROL
• DIFFERENTIAL ENTHALPY CONTROL
• OPTIONAL ECONOMI$ERIV AND ECONOMI$ER2
• ECONOMI$ERIV STANDARD SENSORS
• ECONOMI$ERIV CONTROL MODES
Step 14 — Install Humidistat for
Optional MoistureMi$er™ Package............31
START-UP .................................... 33-43
SERVICE ..................................... 43-50
TROUBLESHOOTING......................... 51-56
INDEX ...........................................57
START-UP CHECKLIST ........................CL-1
.....................................16
...............11
..............16
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should in­stall, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precau­tions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.
1. Improper installation, adjustment, alteration, service, or maintenance can cause property damage, personal injury, or loss of life. Refer to the User’s Information Manual provided with this unit for more details.
2. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
What to do if you smell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any phone in your building.
3. IMMEDIATELY call your gas supplier from a neigh­bor’s phone. Follow the gas supplier’s instructions.
4. If you cannot reach your gas supplier, call the fire department.
Disconnect gas piping from unit when pressure testing at pressure greater than 0.5 psig. Pressures greater than
0.5 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than
0.5 psig, it must be replaced before use. When pressure testing field-supplied gas piping at pressures of 0.5 psig or less, a unit connected to such piping must be isolated by closing the manual gas valve(s).
IMPORTANT: Units have high ambient operating limits. If limits are exceeded, the units will automatically lock the compressor out of operation. Manual reset will be required to restart the compressor.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 1 a 6 a
Catalog No. 04-53480016-01 Printed in U.S.A. Form 48TM-4SI Pg 1 3-06 Replaces: 48TM-3SI
INSTALLATION
Inspect unit for transportation damage. If damage is found,
file any claim with the transportation agency.
Step 1 — Provide Unit Support
ROOF CURB — Assemble and install accessory roof curb or horizontal adapter roof curb in accordance with instructions shipped with this accessory. See Fig. 1-2B. Install insulation, cant strips, roofing, and counter flashing as shown. Ductwork can be installed to roof curb or horizontal adapter roof curb be­fore unit is set in place. Curb or adapter roof curb should be level. This is necessary to permit unit drain to function proper­ly. Unit leveling tolerance is ±
1
/16in. per linear ft in any direc­tion. Refer to Accessory Roof Curb or Horizontal Adapter Roof Curb Installation Instructions for additional information as required. When accessory roof curb or horizontal adapter roof curb is used, unit may be installed on class A, B, or C roof covering material.
IMPORTANT: The gasketing of the unit to the roof curb or adapter roof curb is critical for a watertight seal. Install gasket with the roof curb or adapter as shown in Fig. 2A and 2B. Improperly applied gasket can also result in air leaks and poor unit performance.
ALTERNATE UNIT SUPPORT — When the curb or adapter cannot be used, install unit on a noncombustible surface. Sup­port unit with sleepers, using unit curb support area. If sleepers cannot be used, support long sides of unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
Step 2 — Rig and Place Unit — Do not drop unit;
keep upright. Use spreader bars over unit to prevent sling or ca­ble damage. Rollers may be used to move unit across a roof.
Level by using unit frame as a reference; leveling tolerance is ±
1
/16in. per linear ft in any direction. See Fig. 3 for additional in-
formation. Unit operating weight is shown in Table 1.
Four lifting holes are provided in ends of unit base rails as
shown in Fig. 3. Refer to rigging instructions on unit. NOTE: On 48TM028 units, the lower forklift braces must
be removed prior to setting unit on roof curb. POSITIONING — Maintain clearance, per Fig. 4-6, around
and above unit to provide minimum distance from combustible materials, proper airflow, and service access.
Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contaminated air. For proper unit operation, adequate combustion and venti­lation air must be provided in accordance with Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1 (American National Standards Institute).
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Locate mechanical draft system flue assembly at least 4 ft from any opening through which combustion products could enter the building, and at least 4 ft from any adjacent building. When unit is located adjacent to public walkways, flue assem­bly must be at least 7 ft above grade. Locate unit at least 10 ft away from adjacent units.
ROOF MOUNT — Check building codes for weight distri­bution requirements. Unit operating weight is shown in Table 1.
Instructions continued on page 11.
NOTE: CRRFCURB013A00 is a fully factory preassembled hori­zontal adapter and includes an insulated transition duct. The pres­sure drop through the adapter curb is negligible.
For horizontal return applications: The power exhaust and baro-
metric relief dampers must be installed in the return air duct.
Fig. 1 — Horizontal Supply/Return Adapter Installation (48TM016-025)
3 1/2"
14 3/4"
6"
ACCESSORY
PACKAGE NO.
CRRFCURB013A00
2
2" X 1/4 SUPPORT TYP. STITCH WELDED
12" WIDE STANDING SEAM PANELS
CURB
HEIGHT
1-11
(584)
FULLY INSULATED SUPPLY PLENUM 1" INSULATION 1 1/2 # DENSITY, STICK PINNED & GLUED
23"
DESCRIPTION
Pre-Assembled, Roof Curb,
Horizontal Adapter
Fig. 2A — Roof Curb Details — 48TM016-025
3
Fig. 2B — Roof Curb Details — 48TM028
4
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Refer to Fig. 4-6 for unit operating weights.
3. Remove boards at ends of unit and runners prior to rigging.
4. Rig by inserting hooks into unit base rails as shown. Use corner post from packaging to protect coil from damage. Use bumper boards for spreader bars on all units.
5. Weights do not include optional economizer. Add 90 lb (41 kg) for economizer weight.
6. Weights given are for aluminum evaporator and condenser coil plate fins.
All panels must be in place when rigging.
UNIT
48TM
MAXIMUM
SHIPPING WEIGHT
lb kg ft-in. mm ft-in. mm 016 1875 850 6-11 020 1925 873 6-11 025 2035 923 6-11 028 2445 1109 6-11
Fig. 3 — Rigging Details
DIMENSIONS
AB
1
/22121 4-0 1219
1
/22121 3-2 964
1
/22121 3-4 1016
1
/22121 3-4 1016
5
Fig. 4 — Base Unit Dimensions — 48TM016,020
6
Fig. 5 — Base Unit Dimensions — 48TM025
7
Fig. 6 — Base Unit Dimensions — 48TM028
8
Table 1 — Physical Data
UNIT 48TM 016D/F 020D/F 025D/F 028D/F NOMINAL CAPACITY (tons) 15 18 20 25 OPERATING WEIGHT 1800 1850 1900 2270
Economizer 90 90 90 90 MoistureMi$er™ Dehumidification Package 40 40 40 40
COMPRESSOR/MANUFACTURER Scroll, Copeland
Quantity...Model (Ckt 1, Ckt 2) Capacity Stages (%) 60, 40 55, 45 55, 45 50, 50
Number of Refrigerant Circuits 22 2 2 Oil (oz) (Ckt 1, Ckt 2) 85, 60 106, 81 106,106 136, 106
REFRIGERANT TYPE R-22
Expansion Device TXV Operating Charge (lb-oz) Circuit 1† 19-8 19-8 19-11 26-13 Circuit 2 13-8 19-2 13-14 25-10
CONDENSER COIL Cross-Hatched
Rows...Fins/in. 4...15 4...15 4...15 3...15 (2 coils) Total Face Area (sq ft) 21.7 21.7 21.7 43.4
CONDENSER FAN Propeller Type
Nominal Cfm 10,500 10,500 14,200 21,000 Quantity...Diameter (in.) 3...22 3...22 2...30 6...22 Motor Hp...Rpm Watts Input (Total) 1100 1100 3400 2200
EVAPORATOR COIL Cross-Hatched
Rows...Fins/in. 4...15 4...15 4...15 4...15 Total Face Area (sq ft) 17.5 17.5 17.5 17.5
EVAPORATOR FAN Centrifugal Type
Quantity...Size (in.) 2...12 x 12 2...12 x 12 2...12 x 12 2...12 x 12 Type Drive Belt Belt Belt Belt Nominal Cfm 6000 7200 8000 10,000 Motor Hp 55 7.5 10 Motor Nominal Rpm 1745 1745 1745 1740
Maximum Continuous Bhp 6.13 5.90 Motor Frame Size 184T 184T 213T 215T
Nominal Rpm High/Low —— Fan Rpm Range Low-Medium Static 873-1021 910-1095 1002-1151 1066-1283
High Static 1025-1200 1069-1287 1193-1369 1332-1550 Motor Bearing Type Ball Ball Ball Ball Maximum Allowable Rpm 1550 1550 1550 1550 Motor Pulley Pitch Diameter Low-Medium Static 4.9/5.9 4.9/5.9 5.4/6.6 4.9/5.9
Min/Max (in.) High Static 4.9/5.9 4.9/5.9 5.4/6.6 4.9/5.9 Nominal Motor Shaft Diameter (in.) 1 Fan Pulley Pitch Diameter (in.) Low-Medium Static 9.4 9.4 9.4 8.0
Nominal Fan Shaft Diameter (in.) 1
High Static 8.0 8.0 7.9 6.4
Belt, Quantity...Type...Length (in.) Low-Medium Static 1...BX...50 1...BX...50 1...BX...53 2...BX...50
Pulley Center Line Distance (in.) 13.3-14.8 13.3-14.8 14.6-15.4 14.6-15.4 Speed Change per Full Turn of
Movable Pulley Flange (rpm) Movable Pulley Maximum Full Turns
High Static 1...BX...48 1...BX...48 1...BX...50 2...BX...47
Low-Medium Static 37 37 37 36 High Static 44 34 44 45
From Closed Position 6** 6†† 6** 6†† Factory Speed 3.5 3.5 3.5 3.5 Factory Speed Setting (rpm) Low-Medium Static 965 1002 1120 1182
High Static 1134 1178 1328 1470
Fan Shaft Diameter at Pulley (in.) 1
LEGEND
Bhp — Brake Horsepower TXV — Thermostatic Expansion Valve
*The ZRU140KC compressor is a tandem compressor, consisting of a ZR72KC (25% total
capacity) and a ZR68KC (24% total capacity).
†Circuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator
coils; and Circuit 2 uses the upper portion of both coils.
**Pulley has 6 turns. Due to belt and pulley size, movable pulley cannot be set to 0 to 1
turns open.
††Pulley has 6 turns. Due to belt and pulley size, movable pulley cannot be set to 0 to
open.
***Rollout switch is manual reset.
†††A Liquid Propane kit is available as an accessory.
¶The 48TM028 unit requires 2-in. industrial-grade filters capable of handling face velocities up
to 625 ft/min (such as American Air Filter no. 5700 or equivalent).
NOTE: The 48TM016-028 units have a low-pressure switch (standard) located on the suction side.
1...ZR94KC,
1...ZR72KC
1
/2...1050
1
/
8
7
/
16
7
/
16
1...ZR108KC,
1...ZR94KC
3
1...ZR125KC,
1...ZR108KC
/8-in. Copper Tubes, Aluminum Lanced,
Aluminum Pre-Coated, or Copper Plate Fins
1
/2...1050 1...1075
3
/8-in. Copper Tubes, Aluminum Lanced or
Copper Plate Fins, Face Split
11/
17/
17/
1
/2turns
8.7 [208/230, 575 v]
9.5 [460 v]
8
16
16
1
/
2
13/
17/
17/
8
16
16
10.2 [208/230, 575 v]
1...ZRU140KC,*
1...ZR144KC
1
/2...1050
11.8 [460 v]
13/
8
17/
16
17/
16
9
Table 1 — Physical Data (cont)
UNIT 48TM 016D/F 020D/F 025D/F 028D/F FURNACE SECTION
Rollout Switch Cutout Temp (F)*** 190 190 190 190
Burner Orifice Diameter (in. ...drill size)
Natural Gas Std 0.1285...30/0.136...29 0.1285...30/0.136...29 0.1285...30/0.136...29 0.1285...30/0.136...29 Thermostat Heat Anticipator Setting (amps)
208/230, 575 v Stage 1 0.98 0.98 0.98 0.98
460 v Stage 1 0.80 0.80 0.80 0.80
Gas Input Stage 1 172,000/225,000 206,000/270,000 206,000/270,000 206,000/270,000
Efficiency (Steady-State) (%) 81 81 81 81 Temperature Rise Range 15-45/20-50 15-45/20-50 15-45/20-50 15-45/20-50 Manifold Pressure (in. wg) Natural Gas Std 3.3 3.3 3.3 3.3 Liquid Propane††† Alt 3.3 3.3 3.3 3.3 Gas Valve Quantity 1111 Gas Valve Pressure Range
in. wg 5.5-13.5 5.5-13.5 5.5-13.5 5.5-13.5 psig 0.235-0.487 0.235-0.487 0.235-0.487 0.235-0.487
Field Gas Connection Size (in.-FPT)
HIGH-PRESSURE SWITCH (psig)
Cutout 426 Reset (Auto) 320
LOW-PRESSURE SWITCH (psig)
Cutout 27 Reset (Auto) 44
FREEZE PROTECTION THERMOSTAT (F)
Opens 30 ± 5 Closes 45 ± 5
OUTDOOR-AIR INLET SCREENS Cleanable
Quantity...Size (in.) 2...20 x 25 x 1
RETURN-AIR FILTERS Throwaway¶
Quantity...Size (in.) 4...20 x 20 x 2
POWER EXHAUST
Bhp — Brake Horsepower TXV — Thermostatic Expansion Valve
*The ZRU140KC compressor is a tandem compressor, consisting of a ZR72KC (25% total
capacity) and a ZR68KC (24% total capacity).
†Circuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator
coils; and Circuit 2 uses the upper portion of both coils.
**Pulley has 6 turns. Due to belt and pulley size, movable pulley cannot be set to 0 to 1
turns open.
††Pulley has 6 turns. Due to belt and pulley size, movable pulley cannot be set to 0 to
open.
***Rollout switch is manual reset.
†††A Liquid Propane kit is available as an accessory.
¶The 48TM028 unit requires 2-in. industrial-grade filters capable of handling face velocities up
to 625 ft/min (such as American Air Filter no. 5700 or equivalent).
NOTE: The 48TM016-028 units have a low-pressure switch (standard) located on the suction side.
Stage 2 0.44 0.44 0.44 0.44
Stage 2 0.44 0.44 0.44 0.44
Stage 2 230,000/300,000 275,000/360,000 275,000/360,000 275,000/360,000
3
/
4
3
/
4
3
/
4
1...20 x 20 x 1
4...16 x20 x 2
1
/2Hp, 208/230-460 v Motor Direct Drive, Propeller-Fan (Factory-Wired for 460 v)
LEGEND
1
/
2
1
/2turns
3
/
4
10
Step 3 — Field Fabricate Ductwork — Secure all
ducts to building structure. Use flexible duct connectors be­tween unit and ducts as required. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be in-
sulated and covered with a vapor barrier.
Step 4 — Make Unit Duct Connections — Unit
is shipped for thru-the-bottom duct connections. Ductwork openings are shown in Fig. 1 and 4-6. Duct connections are shown in Fig. 7. Field-fabricated concentric ductwork may be connected as shown in Fig. 8 and 9. Attach all ductwork to roof curb and roof curb basepans.
Step 5 — Install Flue Hood and Wind Baffle —
Flue hood and wind baffle are shipped secured under main control box. To install, secure flue hood to access panel. See Fig. 10. The wind baffle is then installed over the flue hood.
NOTE: When properly installed, flue hood will line up with combustion fan housing. See Fig. 11.
Step 6 — Trap Condensate Drain — See Fig. 12
for drain location. One unit evaporator section for condensate drain connection. An 81/2-in. x3/4-in. diameter and 2-in. x3/4-in. diameter pipe nip­ple, coupled to standard straight path down through hole in unit base rails (see Fig. 13). A trap at least 4-in. deep must be used.
3
/4-in. half coupling is provided inside
3
/4-in. diameter elbows, provide a
NOTE: Do not drill in this area; damage to basepan may result in water leak.
Fig. 7 — Air Distribution — Thru-the-Bottom
NOTE: Dimensions A, A′, B, and Bare obtained from field-supplied ceiling diffuser.
Shaded area indicates block-off panels.
Fig. 9 — Concentric Duct Details
WIND BAFFLE
NOTE: Do not drill in this area; damage to basepan may result in water leak.
Fig. 8 — Concentric Duct Air Distribution
Fig. 10 — Flue Hood Location
11
INDUCED DRAFT MOTOR
Step 7 — Orifice Change — This unit is factory as-
sembled for heating operation using natural gas at an elevation from sea level to 2000 ft. This unit uses orifice type LH32RFnnn, where “nnn” indicates the orifice size based on drill size diameter in thousands of an inch.
HIGH ELEVATION (Above 2000 ft) — Use accessory high altitude kit when installing this unit at an elevation of 2000 to 7000 ft. For elevations above 7000 ft, refer to Table 2 to identi­fy the correct orifice size for the elevation. See Table 3 for the number of orifices required for each unit size. Purchase these orifices from your local Carrier dealer. Follow instructions in accessory Installation Instructions to install the correct orifices.
Table 2 — Altitude Compensation*
COMBUSTION FAN HOUSING
MAIN BURNER SECTION
HEAT EXCHANGER SECTION
Fig. 11 — Combustion Fan Housing Location
3/4" FPT DRAIN CONNECTION
1-3/8" DRAIN HOLE
Fig. 12 — Condensate Drain Details
(48TM016 Shown)
ELEVATION (ft)
0-1,999 30 29
2,000 30 29 3,000 31 30 4,000 31 30 5,000 31 30 6,000 31 30 7,000 32 31 8,000 32 31 9,000 33 31
10,000 35 32
*As the height above sea level increases, there is less oxygen per
cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes. Includes a 4% input reduction per each 1000 ft.
†Orifices available through your Carrier dealer.
NATURAL GAS ORIFICE†
Low Heat High Heat
Table 3 — Orifice Quantity
UNIT ORIFICE QUANTITY 48TMD016 5 48TMD020,
48TMD024, 48TMD028, 48TMF016
48TMF020, 48TMF024, 48TMF028
6
7
CONVERSION TO LP (Liquid Propane) GAS — Use acces­sory LP gas conversion kit when converting this unit for use with LP fuel usage for elevations up to 7000 ft. For elevations above 7000 ft, refer to Table 4 to identify the correct orifice size for the elevation. See Table 3 for the number of orifices required for each unit size. Purchase these orifices from your local Carrier dealer. Follow instructions in accessory Installa­tion Instructions to install the correct orifices.
Table 4 — LP Gas Conversion*
ELEVATION (ft) LP GAS ORIFICE†
0-1,999 36
2,000 37 3,000 38 4,000 38 5,000 39 6,000 40 7,000 41 8,000 41 9,000 42
10,000 43
*As the height above sea level increases, there is less oxygen per
cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes. Includes a 4% input reduction per each 1000 ft.
†Orifices available through your Carrier dealer.
Fig. 13 — Condensate Drain Piping Details
12
Step 8 — Install Gas Piping — Unit is equipped for
use with natural gas. Installation must conform with local building codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1.
Install field-supplied manual gas shutoff valve with a
1
/8-in. NPT pressure tap for test gage connection at unit. Field gas piping must include sediment trap and union. See Fig. 14.
Do not pressure test gas supply while connected to unit. Always disconnect union before servicing. Exceeding maximum manifold pressure may cause explosion and injury.
IMPORTANT: Natural gas pressure at unit gas connec­tion must not be less than 5.5 in. wg or greater than
13.5 in. wg.
Size gas-supply piping for 0.5-in. wg maximum pressure
drop. Do not use supply pipe smaller than unit gas connection.
Fig. 14 — Field Gas Piping
Step 9 — Make Electrical Connections
FIELD POWER SUPPLY — Unit is factory wired for volt­ageshownonnameplate.
When installing units, provide a disconnect per NEC
(National Electrical Code) of adequate size (Table 5).
All field wiring must comply with NEC and local
requirements.
Route power ground lines through control box end panel or unit basepan (see Fig. 4-6) to connections as shown on unit wiring diagram and Fig. 15.
Field wiring must confirm to temperature limitations for type “T” wire. All field wiring must comply with NEC and lo­cal requirements.
Transformer no. 1 is wired for 230-v unit. If 208/230-v unit is to be run with 208-v power supply, the transformer must be rewired as follows:
1. Remove cap from red (208 v) wire.
2. Remove cap from orange (230 v) spliced wire.
3. Replace orange wire with red wire.
4. Recap both wires.
Be certain unused wires are capped. Failure to do so may damage the transformers.
Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3-phase units, voltages between phases must be balanced within 2%.
Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components.
FIELD CONTROL WIRING — Install a Carrier-approved accessory thermostat assembly according to installation in­structions included with accessory. Locate thermostat assembly on a solid interior wall in the conditioned space to sense aver­age temperature.
Route thermostat cable or equivalent single leads of colored wire from subbase terminals through conduit in unit to low-voltage connections as shown on unit label wiring diagram andinFig.16.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected at the thermostat and will require a junction box and splice at the thermostat.
Set heat anticipator settings as follows:
VO LTAGE W1 W 2
208/230,575
460
0.98
0.80
0.44
0.44
Settings may be changed slightly to provide a greater degree of comfort for a particular installation.
The correct power phasing is critical in the operation of the scroll compressors. An incorrect phasing will cause the compressor to rotate in the wrong direction. This may lead to premature compressor failure.
The unit must be electrically grounded in accordance with local codes and NEC ANSI/NFPA 70 (National Fire Pro­tection Association) to protect against fire and electrical shock.
NOTE:ThemaximumwiresizeforTB1is2/0.
LEGEND
EQUIP — Equipment GND Ground NEC National Electrical Code TB Terminal Block
Fig. 15 — Field Power Wiring Connections
13
OPTIONAL NON-FUSED DISCONNECT — On units with
-
the optional non-fused disconnect, incoming power will be wired into the disconnect switch. Refer to Fig. 17 for wiring for 100 and 200 amp disconnect switches. Units with an MOCP (maximum overcurrent protection) under 100 will use the 100 amp disconnect switch. Units with an MOCP over 100 will use the 200 amp disconnect switch. Refer to the applicable disconnect wiring diagram.
To prevent breakage during shipping, the disconnect han­dle and shaft are shipped and packaged inside the unit control box. Install the disconnect handle before unit operation. To in­stall the handle and shaft, perform the following procedure:
1. Open the control box door and remove the handle and shaft from shipping location.
2. Loosen the Allen bolt located on the disconnect switch. The bolt is located on the square hole and is used to hold the shaft in place. The shaft cannot be inserted until the Allen bolt is moved.
3. Insert the disconnect shaft into the square hole on the dis­connect switch. The end of the shaft is specially cut and the shaft can only be inserted in the correct orientation.
4. Tighten the Allen bolt to lock the shaft into position.
5. Close the control box door.
6. Attach the handle to the external access door with the two screws provided. When the handle is in the ON position, thehandlewillbevertical.WhenthehandleisintheOFF position, the handle will be horizontal.
7. Turn the handle to the OFF position and close the door. The handle should fit over the end of the shaft when the door is closed.
8. The handle must be in the OFF position to open the con­trol box door.
OPTIONAL CONVENIENCE OUTLET — On units with optional convenience outlet, a 115-v GFI (ground fault inter­rupt) convenience outlet receptacle is provided for field wiring. Field wiring should be run through the
7
/8-in. knockout pro-
vided in the basepan near the return air opening.
THERMOSTAT ASSEMBLY
REMOVABLE JUMPER
RC
RH
R
RED
Y1 Y2
Y1
BLU
PNK
W1
W1Y2
ORN
W2
W2
VIO
GC
G
BLK
C
BRN
L
X
X
WHT
Fig. 16 — Field Control Thermostat Wiring
6T3 4T2 2T1 LOAD
5L3 3L2 1L1 LINE
NOTE: The disconnect takes the place of TB-1 as shown on the unit wiring dia gram label and the component arrangement label.
Fig. 17 — Optional Non-Fused Disconnect Wiring
14
Table 5 — Electrical Data
NOMINAL
UNIT
VOLTAGE
48TM
(3 Ph, 60 Hz)
208/230 187 253 32.1 195 20.7 156 3 0.5 1.7 5.0 15.8/15.8
016
020
025
028
FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM Indoor (Evaporator) Fan Motor LRA Locked Rotor Amps MCA Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC National Electrical Code OFM Outdoor (Condenser) Fan Motor RLA RatedLoadAmps
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination
2. Unbalanced 3-Phase Supply Voltage
% Voltage Imbalance
= 100 x
460 414 508 16.4 95 10 70 3 0.5 0.8 5.0 7.9
575 518 633 12 80 8.2 54 3 0.5 0.75 5.0 6.0
208/230 187 253 30.1 225 28.8 195 3 0.5 1.7 5.0 15.8/15.8
460 414 508 15.5 114 14.7 95 3 0.5 0.8 5.0 7.9
575 518 632.5 12.1 80 10.7 80 3 0.5 0.75 5.0 6.0
208/230 187 253 42 239 33.6 225 2 1 6.6 7.5 25.0/25.0
460 414 508 19.2 125 17.3 114 2 1 3.3 7.5 13.0
575 518 633 13.8 80.0 — 13.5 80.0 2 1.0 3.4 7.5 10.0
208/230 187.2 253 20.7 156 20.7 156 47.1 245 6 0.5 1.7 10.0 28.0/28.0
460 414 508 10 75 10 75 19.6 125 6 0.5 0.8 10.0 14.6
575 517.5 632.5 8.2 54 8.2 54 15.8 100 6 0.5 0.8 10.0 13.0
load equipment (refer to NEC Articles 430 and 440), the overcurrent pro­tective device for the unit shall be fuse or HACR breaker. Canadian units maybefuseorcircuitbreaker.
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
voltage imbalance.
max voltage deviation from average voltage
VO LTAG E
RANGE
Min Max RLA LRA RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA FLA LRA FLA MCA MOCP*
LEGEND
Use the following formula to determine the percent
average voltage
COMPRESSOR
No. 1 No. 1A No. 2
OFM IFM
EXAMPLE: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5v (BC) 464 – 457 = 7v
(AC) 457 – 455 = 2v Maximum deviation is 7 v. Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
POWER
EXHAUST
0.57 82/82 110/110
4.6 18.8 0.57 86/86 110/110 — 0.30 41 50
2.3 6.0 0.30 43 50 — 0.57 31 40
2.1 4.8 0.57 34 40 — 0.57 87/87 110/110
4.6 18.8 0.57 92/92 110/110 — 0.30 44 50
2.3 6.0 0.30 47 60 — 0.57 34 40
2.1 4.8 0.57 36 40 — 0.57 124/124 150/150
4.6 18.8 0.57 129/129 150/150 — 0.30 61 80
2.3 6.0 0.30 63 80 — 0.57 48 60
2.1 4.8 0.57 50 60 — 0.57 138/138 175/175
4.6 18.8 0.57 143/143 150/175 — 0.30 64 80
2.3 6 0.30 66 80 — 0.57 54 60
2.1 4.8 0.57 56 70
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
= 1.53%
7
457
COMBUSTION
FAN M OTO R
452 + 464 + 455
3
1371
=
3
= 457
POWER
SUPPLY
15
Step 10 — Make Outdoor-Air Inlet Adjust­ments
MANUAL OUTDOOR-AIR DAMPER — All units (except those equipped with a factory-installed economizer) have a manual outdoor-air damper to provide ventilation air.
Damper can be preset to admit up to 25% outdoor air into return-air compartment. To adjust, loosen securing screws and move damper to desired setting, then retighten screws to secure damper (Fig. 18).
Fig. 18 — Standard 25% Outdoor-Air
Section Details
Fig. 19 — Outdoor-Air Hood Component Location
Step 11 — Install Outdoor-Air Hood
IMPORTANT: If the unit is equipped with the optional EconoMi$erIV component, move the outdoor-air tempera­ture sensor prior to installing the outdoor-air hood. See the Optional EconoMi$erIV and EconoMi$er2 section for more information.
The outdoor-air hood is common to 25% air ventilation, EconoMi$erIV and EconoMi$er2. If EconoMi$erIV or EconoMi$er2 is used, all electrical connections have been made and adjusted at the factory. Assemble and install hood in the field.
NOTE: The hood top panel, upper and lower filter retainers, hood drain pan, baffle (sizes 025 and 028), and filter support bracket are secured opposite the condenser end of the unit. The screens, hood side panels, remaining section of filter support bracket, seal strip, and hardware are in a package located inside the return-air filter access panel (Fig. 19).
1. Attach seal strip to upper filter retainer. See Fig. 20.
2. Assemble hood top panel, side panels, upper filter retain­er, and drain pan (see Fig. 21).
3. Secure lower filter retainer and support bracket to unit. See Fig. 21. Leave screws loose on 025 and 028 units.
4. Slide baffle (sizes 025 and 028) behind lower filter retain­er and tighten screws.
5. Loosen sheet metal screws for top panel of base unit located above outdoor-air inlet opening, and remove screws for hood side panels located on the sides of the outdoor-air inlet opening.
6. Match notches in hood top panel to unit top panel screws. Insert hood flange between top panel flange and unit. Tighten screws.
7. Hold hood side panel flanges flat against unit, and install screwsremovedinStep5.
8. Insert outdoor-air inlet screens and spacer in channel created by lower filter retainer and filter support bracket.
Fig. 20 — Seal Strip Location
BAFFLE
HOOD TOP PANEL
HOOD DRAIN PAN
UPPER FILTER RETAINER
Fig. 21 — Outdoor-Air Hood Details
LOWER FILTER RETAINER
FILTER SUPPORT BRACKET
HOOD SIDE PANELS (2)
BAFFLE (025 AND 028 ONLY)
LOWER FILTER RETAINER
FILTER SUPPORT BRACKET
16
Step 12 — Install All Accessories — After all the
factory-installed options have been adjusted, install all field­installed accessories. Refer to the accessory installation instructions included with each accessory.
MOTORMASTER® I CONTROL INSTALLATION (48TM016,020, and 028)
Install Field-Fabricated Wind Baffles be field-fabricated for all units to ensure proper cooling cycle operation at low ambient temperatures. See Fig. 22 for baffle details. Use 20-gage, galvanized sheet metal, or similar corrosion-resistant metal for baffles. Use field-supplied screws to attach baffles to unit. Screws should be
5
/8-in. long. Drill required screw holes for mounting baffles.
To avoid damage to the refrigerant coils and electrical com­ponents, use recommended screw sizes only. Use care when drilling holes.
Install Motormaster I Controls — Only one Motormaster I control is required for 48TM016 and 020 units. The 48TM028 requires 2 Motormaster I controls — one for circuit 1 and one for circuit 2. The Motormaster I control must be used in conjunction with the accessory 0° F low ambient kit (purchased separately). The Motormaster I device controls outdoor fan no. 1 (and 4 on size 028 units) while outdoor fans no. 2 and 3 (and 5 and 6 on 028 units) are sequenced off by the Accessory 0° F Low Ambient Kit.
— Wind baffles must
1
/4-in. diameter and
Accessory 0° F Low Ambient Kit — Install the accessory 0° F low ambient kit per instruction supplied with accessory.
Sensor Assembly — Install the sensor assembly in the location shown in Fig. 23.
Motor Mount — To ensure proper fan height, replace the exist­ing motor mount with the new motor mount provided with accessory.
Transformer (460 and 575-v Units Only) — On 460 and 575-v units, a transformer is required. The transformer is provided with the accessory and must be field-installed.
Motormaster I Control — Recommended mounting location is on the inside of the panel to the left of the control box. The control should be mounted on the inside of the panel, verti­cally, with leads protruding from bottom of extrusion.
NOTE: Dimensions in ( ) are in mm.
Fig. 22 — Wind Baffle Details
SENSOR LOCATION
HAIRPIN END
48TM016 48TM020 48TM028
NOTE: All sensors are located on the eighth hairpin up from the bottom.
SENSOR LOCATION
HAIRPIN END
SENSOR LOCATION
HAIRPIN END
(Circuits 1 and 2)
Fig. 23 — Motormaster® I Sensor Locations
17
MOTORMASTER® V CONTROL INSTALLATION (48TM025 Only)
Install Field-Fabricated Wind Baffles
— Wind baffles must be field-fabricated for all units to ensure proper cooling cycle operation at low ambient temperatures. See Fig. 22 for baffle details. Use 20-gage, galvanized sheet metal, or similar corrosion-resistant metal for baffles. Use field-supplied screws to attach baffles to unit. Screws should be
5
/8-in. long. Drill required screw holes for mounting baffles.
1
/4-in. diameter and
FROM FUSE BLOCK
BLK
YEL
BLU
To avoid damage to the refrigerant coils and electrical com­ponents, use recommended screw sizes only. Use care when drilling holes.
Install Motormaster V Controls
— The Motormaster V (MMV) control is a motor speed control device which adjusts condenser fan motor speed in response to declining liquid refrigerant pressure. A properly applied Motormaster V control extends the operating range of air-conditioning systems and permits operation at lower outdoor ambient temperatures.
The minimum ambient temperatures at which the unit will
operate are:
TE MP ER ATU RE OP ER ATI NG L IM ITS — F° (C °)
Standard
Unit
40 (4) 25 (–4) –20 (–29)
Unit with
Low Ambient Kit
Unit with
MMV Control
To operate down to the ambient temperatures listed, Motormaster V controls (Fig. 24) must be added. Field­fabricated and installedwind bafflesare also required for all units (see Fig. 22). The Motormaster V control permits operation of the unit to an ambient temperature of –20 F (–29 C). The control regulates the speed of 3-phase fan motors that are compatible with the control. These motors are factory installed.
See Table 6 for the Motormaster V control accessory package usage. Table 7 shows applicable voltages and motors. Replacement of fan motor IS NOT REQUIRED ON CURRENT PRODUCTION UNITS since the control is compatible with the factory-installed fan motors. Only field wiring control is required.
Install the Motormaster V control per instructions supplied with accessory.
B
13B
13C
12 13A
2
256
TO PRESSURE TRANSDUCER
2
3
1
TO MOTOR(S)
Fig. 24 — Motormaster® V Control
Table 6 — Motormaster V Control Package Usage
UNIT VOLTAGE ITEM DESCRIPTION
208/230 CRLOWAMB015A00
48TM016-028
460 CRLOWAMB016A00
575 CRLOWAMB017A00
Table 7 — Applicable Voltages and Motors
VOLTAGE COMPATIBLE MOTOR
208/230-3-60 HD52AK654
460-3-60 HD52AK654 575-3-60 HD52GE576
18
Loading...
+ 42 hidden pages