SERVICE ..................................... 43-50
TROUBLESHOOTING......................... 51-56
INDEX ...........................................57
START-UP CHECKLIST ........................CL-1
.....................................16
........................1
...............11
..............16
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
1. Improper installation, adjustment, alteration, service,
or maintenance can cause property damage, personal
injury, or loss of life. Refer to the User’s Information
Manual provided with this unit for more details.
2. Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
What to do if you smell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any
phone in your building.
3. IMMEDIATELY call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
4. If you cannot reach your gas supplier, call the fire
department.
Disconnect gas piping from unit when pressure testing at
pressure greater than 0.5 psig. Pressures greater than
0.5 psig will cause gas valve damage resulting in hazardous
condition. If gas valve is subjected to pressure greater than
0.5 psig, it must be replaced before use. When pressure
testing field-supplied gas piping at pressures of 0.5 psig or
less, a unit connected to such piping must be isolated by
closing the manual gas valve(s).
IMPORTANT: Units have high ambient operating limits. If
limits are exceeded, the units will automatically lock the
compressor out of operation. Manual reset will be required
to restart the compressor.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Ta b 1 a 6 a
Catalog No. 04-53480016-01Printed in U.S.A.Form 48TM-4SIPg 13-06Replaces: 48TM-3SI
INSTALLATION
Inspect unit for transportation damage. If damage is found,
file any claim with the transportation agency.
Step 1 — Provide Unit Support
ROOF CURB — Assemble and install accessory roof curb or
horizontal adapter roof curb in accordance with instructions
shipped with this accessory. See Fig. 1-2B. Install insulation,
cant strips, roofing, and counter flashing as shown. Ductwork
can be installed to roof curb or horizontal adapter roof curb before unit is set in place. Curb or adapter roof curb should be
level. This is necessary to permit unit drain to function properly. Unit leveling tolerance is ±
1
/16in. per linear ft in any direction. Refer to Accessory Roof Curb or Horizontal Adapter
Roof Curb Installation Instructions for additional information
as required. When accessory roof curb or horizontal adapter
roof curb is used, unit may be installed on class A, B, or C roof
covering material.
IMPORTANT: The gasketing of the unit to the roof curb
or adapter roof curb is critical for a watertight seal.
Install gasket with the roof curb or adapter as shown in
Fig. 2A and 2B. Improperly applied gasket can also
result in air leaks and poor unit performance.
ALTERNATE UNIT SUPPORT — When the curb or adapter
cannot be used, install unit on a noncombustible surface. Support unit with sleepers, using unit curb support area. If sleepers
cannot be used, support long sides of unit with a minimum of
3 equally spaced 4-in. x 4-in. pads on each side.
Step 2 — Rig and Place Unit — Do not drop unit;
keep upright. Use spreader bars over unit to prevent sling or cable damage. Rollers may be used to move unit across a roof.
Level by using unit frame as a reference; leveling tolerance is ±
1
/16in. per linear ft in any direction. See Fig. 3 for additional in-
formation. Unit operating weight is shown in Table 1.
Four lifting holes are provided in ends of unit base rails as
shown in Fig. 3. Refer to rigging instructions on unit.
NOTE: On 48TM028 units, the lower forklift braces must
be removed prior to setting unit on roof curb.
POSITIONING — Maintain clearance, per Fig. 4-6, around
and above unit to provide minimum distance from combustible
materials, proper airflow, and service access.
Do not install unit in an indoor location. Do not locate unit
air inlets near exhaust vents or other sources of contaminated
air. For proper unit operation, adequate combustion and ventilation air must be provided in accordance with Section 5.3 (Air
for Combustion and Ventilation) of the National Fuel Gas
Code, ANSI Z223.1 (American National Standards Institute).
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Locate mechanical draft system flue assembly at least 4 ft
from any opening through which combustion products could
enter the building, and at least 4 ft from any adjacent building.
When unit is located adjacent to public walkways, flue assembly must be at least 7 ft above grade. Locate unit at least 10 ft
away from adjacent units.
ROOF MOUNT — Check building codes for weight distribution requirements. Unit operating weight is shown in
Table 1.
Instructions continued on page 11.
NOTE: CRRFCURB013A00 is a fully factory preassembled horizontal adapter and includes an insulated transition duct. The pressure drop through the adapter curb is negligible.
For horizontal return applications: The power exhaust and baro-
metric relief dampers must be installed in the return air duct.
3. Remove boards at ends of unit and runners prior to rigging.
4. Rig by inserting hooks into unit base rails as shown. Use corner post from packaging to protect coil from
damage. Use bumper boards for spreader bars on all units.
5. Weights do not include optional economizer. Add 90 lb (41 kg) for economizer weight.
6. Weights given are for aluminum evaporator and condenser coil plate fins.
Rows...Fins/in.4...154...154...153...15 (2 coils)
Total Face Area (sq ft)21.721.721.743.4
CONDENSER FANPropeller Type
Nominal Cfm10,50010,50014,20021,000
Quantity...Diameter (in.)3...223...222...306...22
Motor Hp...Rpm
Watts Input (Total)1100110034002200
EVAPORATOR COILCross-Hatched
Rows...Fins/in.4...154...154...154...15
Total Face Area (sq ft)17.517.517.517.5
EVAPORATOR FANCentrifugal Type
Quantity...Size (in.)2...12 x 122...12 x 122...12 x 122...12 x 12
Type DriveBeltBeltBeltBelt
Nominal Cfm60007200800010,000
Motor Hp557.510
Motor Nominal Rpm1745174517451740
Maximum Continuous Bhp6.135.90
Motor Frame Size184T184T213T215T
Nominal Rpm High/Low————
Fan Rpm RangeLow-Medium Static873-1021910-10951002-11511066-1283
High Static1025-12001069-12871193-13691332-1550
Motor Bearing TypeBallBallBallBall
Maximum Allowable Rpm1550155015501550
Motor Pulley Pitch DiameterLow-Medium Static4.9/5.94.9/5.95.4/6.64.9/5.9
Min/Max (in.)High Static4.9/5.94.9/5.95.4/6.64.9/5.9
Nominal Motor Shaft Diameter (in.)1
Fan Pulley Pitch Diameter (in.)Low-Medium Static9.49.49.48.0
/2Hp, 208/230-460 v Motor Direct Drive, Propeller-Fan (Factory-Wired for 460 v)
LEGEND
1
/
2
1
/2turns
3
/
4
10
Step 3 — Field Fabricate Ductwork — Secure all
ducts to building structure. Use flexible duct connectors between unit and ducts as required. Insulate and weatherproof all
external ductwork, joints, and roof openings with counter
flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be in-
sulated and covered with a vapor barrier.
Step 4 — Make Unit Duct Connections — Unit
is shipped for thru-the-bottom duct connections. Ductwork
openings are shown in Fig. 1 and 4-6. Duct connections are
shown in Fig. 7. Field-fabricated concentric ductwork may be
connected as shown in Fig. 8 and 9. Attach all ductwork to roof
curb and roof curb basepans.
Step 5 — Install Flue Hood and Wind Baffle —
Flue hood and wind baffle are shipped secured under main
control box. To install, secure flue hood to access panel. See
Fig. 10. The wind baffle is then installed over the flue hood.
NOTE: When properly installed, flue hood will line up with
combustion fan housing. See Fig. 11.
Step 6 — Trap Condensate Drain — See Fig. 12
for drain location. One
unit evaporator section for condensate drain connection. An
81/2-in. x3/4-in. diameter and 2-in. x3/4-in. diameter pipe nipple, coupled to standard
straight path down through hole in unit base rails (see Fig. 13).
A trap at least 4-in. deep must be used.
3
/4-in. half coupling is provided inside
3
/4-in. diameter elbows, provide a
NOTE: Do not drill in this area; damage to basepan may result in
water leak.
Fig. 7 — Air Distribution — Thru-the-Bottom
NOTE: Dimensions A, A′, B, and B′ are obtained from field-supplied
ceiling diffuser.
Shaded area indicates block-off panels.
Fig. 9 — Concentric Duct Details
WIND
BAFFLE
NOTE: Do not drill in this area; damage to basepan may result in
water leak.
Fig. 8 — Concentric Duct Air Distribution
Fig. 10 — Flue Hood Location
11
INDUCED DRAFT
MOTOR
Step 7 — Orifice Change — This unit is factory as-
sembled for heating operation using natural gas at an elevation
from sea level to 2000 ft. This unit uses orifice type
LH32RFnnn, where “nnn” indicates the orifice size based on
drill size diameter in thousands of an inch.
HIGH ELEVATION (Above 2000 ft) — Use accessory high
altitude kit when installing this unit at an elevation of 2000 to
7000 ft. For elevations above 7000 ft, refer to Table 2 to identify the correct orifice size for the elevation. See Table 3 for the
number of orifices required for each unit size. Purchase these
orifices from your local Carrier dealer. Follow instructions in
accessory Installation Instructions to install the correct orifices.
*As the height above sea level increases, there is less oxygen per
cubic foot of air. Therefore, heat input rate should be reduced at
higher altitudes. Includes a 4% input reduction per each 1000 ft.
†Orifices available through your Carrier dealer.
NATURAL GAS ORIFICE†
Low HeatHigh Heat
Table 3 — Orifice Quantity
UNITORIFICE QUANTITY
48TMD0165
48TMD020,
48TMD024,
48TMD028,
48TMF016
48TMF020,
48TMF024,
48TMF028
6
7
CONVERSION TO LP (Liquid Propane) GAS — Use accessory LP gas conversion kit when converting this unit for use
with LP fuel usage for elevations up to 7000 ft. For elevations
above 7000 ft, refer to Table 4 to identify the correct orifice
size for the elevation. See Table 3 for the number of orifices
required for each unit size. Purchase these orifices from your
local Carrier dealer. Follow instructions in accessory Installation Instructions to install the correct orifices.
*As the height above sea level increases, there is less oxygen per
cubic foot of air. Therefore, heat input rate should be reduced at
higher altitudes. Includes a 4% input reduction per each 1000 ft.
†Orifices available through your Carrier dealer.
Fig. 13 — Condensate Drain Piping Details
12
Step 8 — Install Gas Piping — Unit is equipped for
use with natural gas. Installation must conform with local
building codes or, in the absence of local codes, with the
National Fuel Gas Code, ANSI Z223.1.
Install field-supplied manual gas shutoff valve with a
1
/8-in.
NPT pressure tap for test gage connection at unit. Field gas
piping must include sediment trap and union. See Fig. 14.
Do not pressure test gas supply while connected to unit.
Always disconnect union before servicing. Exceeding
maximum manifold pressure may cause explosion and
injury.
IMPORTANT: Natural gas pressure at unit gas connection must not be less than 5.5 in. wg or greater than
13.5 in. wg.
Size gas-supply piping for 0.5-in. wg maximum pressure
drop. Do not use supply pipe smaller than unit gas connection.
Fig. 14 — Field Gas Piping
Step 9 — Make Electrical Connections
FIELD POWER SUPPLY — Unit is factory wired for voltageshownonnameplate.
When installing units, provide a disconnect per NEC
(National Electrical Code) of adequate size (Table 5).
All field wiring must comply with NEC and local
requirements.
Route power ground lines through control box end panel or
unit basepan (see Fig. 4-6) to connections as shown on unit
wiring diagram and Fig. 15.
Field wiring must confirm to temperature limitations for
type “T” wire. All field wiring must comply with NEC and local requirements.
Transformer no. 1 is wired for 230-v unit. If 208/230-v unit
is to be run with 208-v power supply, the transformer must be
rewired as follows:
1. Remove cap from red (208 v) wire.
2. Remove cap from orange (230 v) spliced wire.
3. Replace orange wire with red wire.
4. Recap both wires.
Be certain unused wires are capped. Failure to do so may
damage the transformers.
Operating voltage to compressor must be within voltage
range indicated on unit nameplate. On 3-phase units, voltages
between phases must be balanced within 2%.
Unit failure as a result of operation on improper line voltage
or excessive phase imbalance constitutes abuse and may cause
damage to electrical components.
FIELD CONTROL WIRING — Install a Carrier-approved
accessory thermostat assembly according to installation instructions included with accessory. Locate thermostat assembly
on a solid interior wall in the conditioned space to sense average temperature.
Route thermostat cable or equivalent single leads of
colored wire from subbase terminals through conduit in unit to
low-voltage connections as shown on unit label wiring diagram
andinFig.16.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft,
use no. 16 AWG insulated wire (35 C minimum). For over
75 ft, use no. 14 AWG insulated wire (35 C minimum). All
wire larger than no. 18 AWG cannot be directly connected at
the thermostat and will require a junction box and splice at the
thermostat.
Set heat anticipator settings as follows:
VO LTAGEW1W 2
208/230,575
460
0.98
0.80
0.44
0.44
Settings may be changed slightly to provide a greater degree
of comfort for a particular installation.
The correct power phasing is critical in the operation of the
scroll compressors. An incorrect phasing will cause the
compressor to rotate in the wrong direction. This may lead
to premature compressor failure.
The unit must be electrically grounded in accordance with
local codes and NEC ANSI/NFPA 70 (National Fire Protection Association) to protect against fire and electrical
shock.
the optional non-fused disconnect, incoming power will be
wired into the disconnect switch. Refer to Fig. 17 for wiring
for 100 and 200 amp disconnect switches. Units with an
MOCP (maximum overcurrent protection) under 100 will use
the 100 amp disconnect switch. Units with an MOCP over 100
will use the 200 amp disconnect switch. Refer to the applicable
disconnect wiring diagram.
To prevent breakage during shipping, the disconnect handle and shaft are shipped and packaged inside the unit control
box. Install the disconnect handle before unit operation. To install the handle and shaft, perform the following procedure:
1. Open the control box door and remove the handle and
shaft from shipping location.
2. Loosen the Allen bolt located on the disconnect switch.
The bolt is located on the square hole and is used to hold
the shaft in place. The shaft cannot be inserted until the
Allen bolt is moved.
3. Insert the disconnect shaft into the square hole on the disconnect switch. The end of the shaft is specially cut and
the shaft can only be inserted in the correct orientation.
4. Tighten the Allen bolt to lock the shaft into position.
5. Close the control box door.
6. Attach the handle to the external access door with the two
screws provided. When the handle is in the ON position,
thehandlewillbevertical.WhenthehandleisintheOFF
position, the handle will be horizontal.
7. Turn the handle to the OFF position and close the door.
The handle should fit over the end of the shaft when the
door is closed.
8. The handle must be in the OFF position to open the control box door.
OPTIONAL CONVENIENCE OUTLET — On units with
optional convenience outlet, a 115-v GFI (ground fault interrupt) convenience outlet receptacle is provided for field wiring.
Field wiring should be run through the
7
/8-in. knockout pro-
vided in the basepan near the return air opening.
THERMOSTAT ASSEMBLY
REMOVABLE JUMPER
RC
RH
R
RED
Y1Y2
Y1
BLU
PNK
W1
W1Y2
ORN
W2
W2
VIO
GC
G
BLK
C
BRN
L
X
X
WHT
Fig. 16 — Field Control Thermostat Wiring
6T3 4T2 2T1 LOAD
5L3 3L2 1L1 LINE
NOTE: The disconnect takes the place of TB-1 as shown on the unit wiring dia
gram label and the component arrangement label.
FLA— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM— Indoor (Evaporator) Fan Motor
LRA— Locked Rotor Amps
MCA— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC— National Electrical Code
OFM— Outdoor (Condenser) Fan Motor
RLA— RatedLoadAmps
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination
load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units
maybefuseorcircuitbreaker.
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
Use the following formula to determine the percent
average voltage
COMPRESSOR
No. 1No. 1ANo. 2
OFMIFM
EXAMPLE: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5v
(BC) 464 – 457 = 7v
(AC) 457 – 455 = 2v
Maximum deviation is 7 v.
Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
POWER
EXHAUST
——0.5782/82110/110
4.6 18.80.5786/86110/110
——0.304150
2.36.00.304350
——0.573140
2.14.80.573440
——0.5787/87110/110
4.6 18.80.5792/92110/110
——0.304450
2.36.00.304760
——0.573440
2.14.80.573640
——0.57124/124 150/150
4.6 18.80.57129/129 150/150
——0.306180
2.36.00.306380
——0.574860
2.14.80.575060
——0.57138/138 175/175
4.6 18.80.57143/143 150/175
——0.306480
2.360.306680
——0.575460
2.14.80.575670
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
= 1.53%
7
457
COMBUSTION
FAN M OTO R
452 + 464 + 455
3
1371
=
3
= 457
POWER
SUPPLY
15
Step 10 — Make Outdoor-Air Inlet Adjustments
MANUAL OUTDOOR-AIR DAMPER — All units (except
those equipped with a factory-installed economizer) have a
manual outdoor-air damper to provide ventilation air.
Damper can be preset to admit up to 25% outdoor air into
return-air compartment. To adjust, loosen securing screws and
move damper to desired setting, then retighten screws to secure
damper (Fig. 18).
Fig. 18 — Standard 25% Outdoor-Air
Section Details
Fig. 19 — Outdoor-Air Hood Component Location
Step 11 — Install Outdoor-Air Hood
IMPORTANT: If the unit is equipped with the optional
EconoMi$erIV component, move the outdoor-air temperature sensor prior to installing the outdoor-air hood. See the
Optional EconoMi$erIV and EconoMi$er2 section for
more information.
The outdoor-air hood is common to 25% air ventilation,
EconoMi$erIV and EconoMi$er2. If EconoMi$erIV or
EconoMi$er2 is used, all electrical connections have been
made and adjusted at the factory. Assemble and install hood in
the field.
NOTE: The hood top panel, upper and lower filter retainers,
hood drain pan, baffle (sizes 025 and 028), and filter support
bracket are secured opposite the condenser end of the unit. The
screens, hood side panels, remaining section of filter support
bracket, seal strip, and hardware are in a package located
inside the return-air filter access panel (Fig. 19).
1. Attach seal strip to upper filter retainer. See Fig. 20.
2. Assemble hood top panel, side panels, upper filter retainer, and drain pan (see Fig. 21).
3. Secure lower filter retainer and support bracket to unit.
See Fig. 21. Leave screws loose on 025 and 028 units.
4. Slide baffle (sizes 025 and 028) behind lower filter retainer and tighten screws.
5. Loosen sheet metal screws for top panel of base unit
located above outdoor-air inlet opening, and remove
screws for hood side panels located on the sides of the
outdoor-air inlet opening.
6. Match notches in hood top panel to unit top panel screws.
Insert hood flange between top panel flange and unit.
Tighten screws.
7. Hold hood side panel flanges flat against unit, and install
screwsremovedinStep5.
8. Insert outdoor-air inlet screens and spacer in channel
created by lower filter retainer and filter support bracket.
Fig. 20 — Seal Strip Location
BAFFLE
HOOD TOP
PANEL
HOOD DRAIN PAN
UPPER FILTER RETAINER
Fig. 21 — Outdoor-Air Hood Details
LOWER FILTER
RETAINER
FILTER SUPPORT
BRACKET
HOOD SIDE
PANELS (2)
BAFFLE
(025 AND
028 ONLY)
LOWER
FILTER
RETAINER
FILTER SUPPORT
BRACKET
16
Step 12 — Install All Accessories — After all the
factory-installed options have been adjusted, install all fieldinstalled accessories. Refer to the accessory installation
instructions included with each accessory.
MOTORMASTER®ICONTROLINSTALLATION
(48TM016,020, and 028)
Install Field-Fabricated Wind Baffles
be field-fabricated for all units to ensure proper cooling cycle
operation at low ambient temperatures. See Fig. 22 for baffle
details. Use 20-gage, galvanized sheet metal, or similar
corrosion-resistant metal for baffles. Use field-supplied screws
to attach baffles to unit. Screws should be
5
/8-in. long. Drill required screw holes for mounting baffles.
To avoid damage to the refrigerant coils and electrical components, use recommended screw sizes only. Use care
when drilling holes.
Install Motormaster I Controls — Only one Motormaster I
control is required for 48TM016 and 020 units. The 48TM028
requires 2 Motormaster I controls — one for circuit 1 and
one for circuit 2. The Motormaster I control must be used in
conjunction with the accessory 0° F low ambient kit
(purchased separately). The Motormaster I device controls
outdoor fan no. 1 (and 4 on size 028 units) while outdoor fans
no. 2 and 3 (and 5 and 6 on 028 units) are sequenced off by the
Accessory 0° F Low Ambient Kit.
— Wind baffles must
1
/4-in. diameter and
Accessory 0° F Low Ambient Kit — Install the accessory 0° F
low ambient kit per instruction supplied with accessory.
Sensor Assembly — Install the sensor assembly in the location
shown in Fig. 23.
Motor Mount — To ensure proper fan height, replace the existing motor mount with the new motor mount provided with
accessory.
Transformer (460 and 575-v Units Only) — On 460 and 575-v
units, a transformer is required. The transformer is provided
with the accessory and must be field-installed.
Motormaster I Control — Recommended mounting location is
on the inside of the panel to the left of the control box. The
control should be mounted on the inside of the panel, vertically, with leads protruding from bottom of extrusion.
NOTE: Dimensions in ( ) are in mm.
Fig. 22 — Wind Baffle Details
SENSOR
LOCATION
HAIRPIN END
48TM01648TM02048TM028
NOTE: All sensors are located on the eighth hairpin up from the
bottom.
SENSOR
LOCATION
HAIRPIN END
SENSOR
LOCATION
HAIRPIN END
(Circuits 1 and 2)
Fig. 23 — Motormaster® I Sensor Locations
17
MOTORMASTER®VCONTROLINSTALLATION
(48TM025 Only)
Install Field-Fabricated Wind Baffles
— Wind baffles must
be field-fabricated for all units to ensure proper cooling cycle
operation at low ambient temperatures. See Fig. 22 for baffle
details. Use 20-gage, galvanized sheet metal, or similar
corrosion-resistant metal for baffles. Use field-supplied screws
to attach baffles to unit. Screws should be
5
/8-in. long. Drill required screw holes for mounting baffles.
1
/4-in. diameter and
FROM FUSE BLOCK
BLK
YEL
BLU
To avoid damage to the refrigerant coils and electrical components, use recommended screw sizes only. Use care
when drilling holes.
Install Motormaster V Controls
— The Motormaster V
(MMV) control is a motor speed control device which adjusts
condenser fan motor speed in response to declining liquid
refrigerant pressure. A properly applied Motormaster V control
extends the operating range of air-conditioning systems and
permits operation at lower outdoor ambient temperatures.
The minimum ambient temperatures at which the unit will
operate are:
TE MP ER ATU RE OP ER ATI NG L IM ITS — F° (C °)
Standard
Unit
40 (4)25 (–4)–20 (–29)
Unit with
Low Ambient Kit
Unit with
MMV Control
To operate down to the ambient temperatures listed,
Motormaster V controls (Fig. 24) must be added. Fieldfabricated and installedwind bafflesare also required for all units
(see Fig. 22). The Motormaster V control permits operation of
the unit to an ambient temperature of –20 F (–29 C). The control
regulates the speed of 3-phase fan motors that are compatible
with the control. These motors are factory installed.
See Table 6 for the Motormaster V control accessory
package usage. Table 7 shows applicable voltages and motors.
Replacement of fan motor IS NOT REQUIRED ONCURRENT PRODUCTION UNITS since the control is
compatible with the factory-installed fan motors. Only field
wiring control is required.
Install the Motormaster V control per instructions supplied
with accessory.
B
13B
13C
12 13A
2
256
TO PRESSURE
TRANSDUCER
2
3
1
TO MOTOR(S)
Fig. 24 — Motormaster® V Control
Table 6 — Motormaster V Control Package Usage
UNITVOLTAGEITEM DESCRIPTION
208/230CRLOWAMB015A00
48TM016-028
460CRLOWAMB016A00
575CRLOWAMB017A00
Table 7 — Applicable Voltages and Motors
VOLTAGECOMPATIBLE MOTOR
208/230-3-60HD52AK654
460-3-60HD52AK654
575-3-60HD52GE576
18
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.