Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precautions in the li terature, ta gs and label s attached t o the uni t, and
other safety precautions that apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
Ensure voltage listed on unit data plate agrees with electrical supply provided for the unit.
Disconnect gas piping from unit when leak
testing at pressure greater than 1/2 psig. Pressures greater than 1/2 psig will cause gas valve
damage resulting in hazardous condition. If
gas valve is subjected to pressure greater than
1
/
2
pressure testing field-supplied gas piping at
pressures of
such piping must be isolated by manually closing the gas valve.
Before performing service or maintenance operations on
unit, turn off main power switch to unit and install lockout
tag. Electrical shock could cause personal injury.
Unit is shipped in the vertical discharge configuration. To
convert to horizontal configuration, remove screws from side
duct opening covers and remove covers. Using the same
screws, install covers on vertical duct openings with the insulation side down. Seals around duct openings must be tight. See
Fig. 1.
Step 1 — Provide Unit Support
ROO F CU R B — Assemble and instal l acces sory roof curb in
accordance with instructions shipped with curb. See Fig. 2. Install insulation, cant strips, roofing felt, and counter flashing as
Ductwork must be attached to curb, not to the unit. The
shown.
accessory thru-the-bottom power and gas connection package
must be installed before the unit is set on the roof curb.
installed (thru-the-roof curb) gas connections are desired, use
factory-supplied
mount the thru-the-roof curb connection to the roof curb. Gas
connections and power connections to the unit must be field installed after the unit is installed on the roof curb.
If electric and control wiring is to be routed through the
basepan, attach the accessory thru-the-bottom service connections to the basepan in accordance with the accessory installation instructions.
IMPORTANT: The gasketing of th e unit to the roof curb
is critical for a watertight seal. Install gasket supplied
with the roof curb as shown in Fig. 2. Improperly
applied gasket can also r esult in air or water leaks and
poor unit performance.
3
must
psig, it
be replaced before use. When
1
/2 psig or less, a unit connected to
INSTALLATION
If field-
/4 in. pipe coupling and gas plate assembly to
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Ta b 1 a 6 a
PC 111Catalog No. 534-774Printed in U.S.A.Form 48TJ-18SIPg 110-00Replaces: 48TJ-16SI
Page 2
Fig. 1 — Horizontal Conversion Panels
(Viewed from Duct End)
Curb should be level. Unit leveling tolerances are shown in
Fig. 3. This is necessary for unit drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
SLAB MOUNT (Horizontal Units Only) — Provide a level
concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to
prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
Step 2 — Field Fabricate Ductwork —
ducts to roof curb and building structure on vertical units.
not connect ductwork to unit.
For horizontal applications, field-
Secure all
Do
supplied flanges should be attached to horizontal discharge
openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof
openings with counter flashing and mastic in accordance with
applicable codes.
Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork.
Cabinet return air static shall not exceed –.30 in. wg with
EconoMi$er, or –.35 in. wg with Durablade Economizer, or
–.45 in. wg without economizer.
These units are designed for a m inimum continuous returnair temperature of 50 F (dry bulb), or an intermittent operation
down to 45 F (dry bulb) (in heating mode), such as when used
with a night set-back thermostat.
Step 3 — Install External Trap for Condensate
Drain —
located on the bottom and side of the unit. Unit discharge
connections do not determine the use of drain connections;
either drain connection can be used with ve rtical or horiz ontal
applications.
When using the standard side drain connection, make sure
the plug (Red) in the alternate bottom connection is tight before
installing the unit.
To use the bottom drai n connection for a roof curb installation, relocate the factory-installed plug (Red) from the bottom
connection to the side connection. See Fig. 4. The piping for
the condensate drain and external trap can be completed after
the unit is in place.
All units must have an external trap for condensate drainage. Install a trap at least 4-in. deep and protect against fr eezeup. If drain line is installed downstream from the external trap,
pitch the line away from the unit at 1 in. per 10 ft of run. Do not
use a pipe size smaller than the unit connection (
Step 4 — Rig and Place Unit —
transportation damage. File any claim with transportation
agency. Keep unit upright and do not drop. Spreader bars are
not required if top crating is left on unit. Rollers may be used to
move unit across a roof. Level by using unit frame as a reference. See Table 1 and Fig. 5 for additional information.
Lifting holes are provided in base rails as shown in Fig. 6.
Refer to rigging instructions on unit.
All panels must be in place when rigging and lifting.
The unit’s 3/4-in. condensate drain connections are
3
/4 in.).
Inspect unit for
2
Page 3
‘‘B’’‘‘C’’
11
1′-9
/16″
[551]
1′-4″
[406]
‘‘D’’ ALT
DRAIN HOLE
13/4″
[44.5]
‘‘E’’
Gas
3
″
/
4
[19] NPT
1
″
/
2
[12.7] NPT
3
/4″
[19] NPT
“F”
Powe r
3
/4″
[19] NPT
1
1
″
/
4
[31.7]
3
″
/
4
[19] NPT
11/4″
[31.7]
“G”
Control
1
/2″
[12.7] NPT
CONNECTOR
PKG ACY
CRBTMPWR001A00
CRBTMPWR002A00
CRBTMPWR003A00
CRBTMPWR004A00
ROOF CURB
ACCESSORY
CRRFCURB001A00
CRRFCURB002A00
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels:
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb (flanges of duct rest on
curb).
6. Service clearance 4′ on each side.
‘‘A’’
1′-2″
[356]
2′-0″
[610]
UNIT SIZE
48TJ
004-007
7.Direction of airflow.
8. Connector packages CRBTMPWR001A00 and
2A00 are for thru-the-curb type. Packages
CRBTMPWR003A00 and 4A00 are for the thruthe-bottom type connections.
TO ENSURE AIRTIGHT CONNECTION
PLACE UNIT AS CLOSE TO
END AS POSSIBLE.
TO ENSURE AIRTIGHT CONNECTION
PLACE UNIT AS CLOSE TO
END AS POSSIBLE.
Fig. 2 — Roof Curb Dimensions
3
Page 4
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-BB-CA-C
0.51.01.0
Fig. 3 — Unit Leveling Tolerances
CONDENSATE PAN (SIDE VIEW)
DRAIN PLUG
NOTE: Drain plug is shown in factory-installed position.
Fig. 4 — Internal Trap Condensate Drain
POS ITION ING — Maintain cleara nce around and above unit
to provide minimum distance from combustible materials,
proper airflow, and service access. See Fig. 6. A properly positioned unit will have the following clearances between unit and
roof curb:
1
/4-in. clearance between roof curb and ba se rails on
each side and duct end of unit; 1/4-in. clearance between roof
curb and condenser coil end of unit. (See Fig. 2, section C-C.)
Do not install unit in an indoor location. Do not locate unit
air inlets within 10 ft of exhaust vents or other sources of contaminated air or as local codes require.
Be sure that unit is installed so that snow will not block the
combustion intake or flue outlet.
Unit may be installed directly on wood flooring or on Class
A, B, or C roof-covering material when roof curb is used.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Flue vent discharge must have a minimum horizontal clearance of 4 ft from electric and gas meters, gas regulators, and
gas relief equipment.
Minimum distance between unit and other electrically live
parts is 48 inches.
Flue gas can deteriorate building materials. Orient unit such
that flue gas will not affect building materials.
Adequate combustion-air space must be provided for proper
operation of this equipment. Be sure that installation complies
with all local codes and Section 5.3, Air for Combustion and
Ventilation, NFGC (National Fuel Gas Code), and ANSI
(American National Standards Institute) Z223.1, and NFPA
(National Fire Protection Association) 54 TIA-54-84-1.
In Canada, installation must be in accordance with the
CAN1- B149 installation codes for gas burning appliances.
After unit is in position, remove rigging skids and shipping
materials.
Step 5 — Install Flue Hood —
Flue hood is shipped
screwed to the burner compartment access panel. Remove
from shipping location and using screws provided, install flue
hood and screen in location shown in Fig. 7.
For units size 004-006 being installed in California Air
Quality Management Districts, which require NOx emissions
of 40 nanograms/joule or less, a field-installed low NOx kit
must be used.
Step 6 — Install Gas Piping —
Unit is equipped for
use with type of gas shown on nameplate. Refer to local building codes, or in the absence of local codes, to ANSI Z223.1 entitled National Fuel Gas Code. In Canada, installation must be
in accordance with the CAN1.B149.1 and CAN1.B149.2 installation codes for gas burning appliances.
For natural gas applications, gas pressure at unit gas
connection must not be less than 4 in. wg or greater than
13.0 in. wg while unit is operating. On 48TJ005,006,007 high
heat units, the gas pressure at unit gas connection must not be
less than 5 in. wg or greater t han 13 in. wg while the unit is
operating. For propane applications, the gas pressure must not
be less than 5 in. wg or greater than 13 in. wg at the unit
connection.
Size gas sully piping for 0.5 in. wg maximum pressure drop.
Do not use supply pipe small than unit gas connection. Support
gas piping as shown in the table in Fig. 8. For example, a
3
/4-in.
gas pipe must have one field-fabricated support beam every
8 ft. Therefore, an 18-ft long gas pipe would have a minimum
of 2 support beams, a 48-ft long pipe would have a minimum
of 6 support beams.
See Fig. 8 for typical pipe guide and locations of external
manual main shutoff valve.
4
Page 5
NOTES:
1. Dimension in ( ) is in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in
detail ‘‘A.’’ Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.
3. Unit weights do not include economizer. See Table 1 for economizer weights.
Unit cabinet must have an uninterrupted, unbroken elect rical ground to minimize the possibility of personal injury if
an electrical fault should occur. This ground may consist of
electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when
installed in accordance with NEC (National Electrical
Code), ANSI/NFPA, latest edition, and local electrical
Do not use gas piping as an electrical ground.
codes.
ure to follow this warning could result in the installer being
liable for personal injury of others.
DISCONNECT BOX LOCATION — The field-supplied disconnect box may be mounted on the unit’s end panel or on the
corner post. Mount disconnect box on the left side of the rating
plate when mounting on the unit’s end panel.
disconnect box over the unit rating plate.
Do not mount the
When mounting
disconnect box on corner post, secure disconnect box to corner
post and condenser coil top cover. See Fig. 7.
A disconnect box mounting space is available when an optional or accessory condenser coil grille is used. Mount the disconnect on the sheet metal provided with t he condenser coil
grille. The sheet metal is loc ated adjacent to the corner post on
the left side of the power wiring access panel.
Fail-
FIELD POWER SUPPLY — All units except 208/230-v
units are factory wired for the voltage shown on the nameplate.
If the 208/230-v unit is to be connected to a 208-v power supply, t he transformer
must
be rewired by disconnecting the black
wire from the 230-v terminal wire on the transformer and connecting it to the 200-v red terminal of the transformer.
Refer to unit label diagram for additional information. Wiring leads are provided for field service. Use copper conductors
only when splice connectors are used.
When installing units, provide a disconnect per NEC.
All field wiring must comply with NEC and local requirements. In Canada, electrical connections must be in accordance
with CSA (Canadian Standards Association) C22.1 Canadian
Electrical Code Part One.
Install field wiring as follows:
1. Connect ground lead to chassis ground connection when
using separate ground ties.
2. Install conduit between disconnect and side panel. Insert
conduit through power supply knockout opening. See
Fig. 9.
3. Connect power lines to power wiring leads.
4. Pigtails are provided for field power connections and are
located inside the burner access panel. See Fig. 10 and 11.
Use factory-supplied splices or Underwriters’ Laboratories (UL) approved copper connector .
5
Page 6
Table 1 — Physical Data
UNIT SIZE 48TJE/F004D/E/F005D/E/F006D/E/F007
NOMINAL CAPACITY (tons)3456
OPERATING WEIGHT (lb)
4. On vertical discharge units, ductwork to be attached to accessory roof curb only. For horizontal discharge units, field-supplied flanges should be attached to horizontal discharge openings, and all
ductwork should be attached to the flanges.
5. Minimum clearance (local codes or jurisdiction may prevail):
a. Between unit, flue side and combustible surfaces, 36 inches.
b. Bottom of unit to combustible surfaces (when not using curb), 1 inch.
Bottom of base rail to combustible surfaces (when not using curb) 0 inches.
c. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side getting the greater
clearance is optional.
d. Overhead, 60 in. to assure proper condenser fan operation.
e. Between units, control box side, 42 in. per NEC.
f. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.
g. Between unit and block or concrete walls and other grounded surfaces, control box side, 42 in.
per NEC.
h. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser coil and combustion side as stated in notes
5a, b and c, a removable fence or barricade requires no clearance.
7. Units may be installed on combustible floors made from wood or Class A, B, or C roof covering
material if set on base rail.
8. The ver tical ce nter of gravity is 1′-6″ [457] up from the bottom of the base rail.
CORNER
WEIGHT
(D)
BOTTOM POWER CHART, THESE HOLES REQUIRED FOR
USE WITH ACCESSORY PACKAGES — CRBTMPWR001A00,
(POWER AND CONTROL) AND CRBTMPWR003A00
(POWER, CONTROL, AND GAS)
THREADED
CONDUIT SIZE
1
″″″″
/
2
3
″″″″
/
4
1
″″″″
/
FPT
2
WIRE
USE
24 V
Powe r11/
Gas11/
HOLE SIZES (MAX.)
REQURED
7
/
[22.2]
″″″″
8
[28.4]
″″″″
8
[31.8]
″
″
″ ″
4
Fig. 6 — Base Unit Dimensions
8
Page 9
CONDENSER
COIL
TOP COVER
CORNER POST
INTAKE
LOUVERS
FLUE HOOD
Fig. 7 — Flue Hood Details
END PANEL
Fig. 9 — Conduit Installation
LEGEND
NFGC —
*Field supplied.
NOTE: Follow all local codes.
National Fuel Gas Code
SPACING OF SUPPORTS
STEEL PIPE
NOMINAL
DIAMETER
(in.)
1
/
2
3
or 1
/
4
1
1
or larger
/
4
X
DIMENSIONS
(feet)
6
8
10
Fig. 8 — Gas Piping Guide (With Accessory
Thru-the-Curb Service Connections)
Voltage to compressor terminals during operation must be
within voltage range indicated on unit nameplate (see Table 2).
On 3-phase units, voltages between phases must be balanced
within 2% and the current within 10%. Use the formula shown
in the legend for Table 2, Note 2 to determine the percent of
voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate
any applicable Carrier warranty.
FIELD CONTR OL WIRING — Install a Carrier-approved
accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat
assembly on a solid wall in the conditioned space to sense average temperature in accordance with thermostat installation
instructions. Connect thermostat wires to terminal board.
Route thermostat cable or equivalent single leads of colored
wire from subbase terminals through connector on unit to lowvoltage connections (shown in Fig. 12).
LEGEND
IGC —
LED —
Integrated Gas Unit Controller
Light-Emitting Diode
Fig. 10 — Component Location
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft,
use no. 16 AWG insulated wire (35 C minimum). For over
75 ft, use no. 14 AWG insulated wire (35 C minimum). All
wire larger than no. 18 AWG cannot be directl y connected to
the thermostat and will require a junction box and splice at the
thermostat.
Feed control wires through the raceway located between the
condenser coil top cover and burner side panel. See Fig. 10.
Connect control wires to corresponding screw terminals, the
low-voltage connections located inside low-voltage access
panel. See Fig. 12 for connections. The low-voltage connections provide the UL required clearance between high- and
low-voltage wiring.
HEAT ANTICIPATOR SETTINGS — Set heat anticipator
settings at .14 amp for the first stage and .14 amp for secondstage heating, when available.
9
Page 10
208/230-1-60
208/230-3-60
460-3-60
(SIZE 007 ONLY)
LEGEND
C—
COMP —
NEC—
TB—
Contactor
Compressor
National Electrical Code
Terminal Block
575-3-60
(SIZE 007 ONLY)
208/230-3-60
575-3-60, 460-3-60
(SIZES 004-006)
Fig. 11 — Power Wiring Connections
LEGEND
AHA —
Adjustable Heat Anticipator
Field Wiring
Factory Wiring
Fig. 12 — Low-Voltage Connections
10
Page 11
Table 2 — Electrical Data
UNIT
48TF
NOMINAL
V-P h- Hz
208/230-1-60
VOLTAGE
IFM
TYPE
RANGE
Min MaxRLALRAQty Hp FLAMCAMOCP†FLALRA
Std
187 25416.296.01
Alt4.926.6/26.635/3526/26111/111
COMPRESSOR
(ea)
Std
208/230-3-60
187 25410.275.01
Alt4.919.1/19.125/2519/1990/90
High5.219.4/19.425/2519/19109/109
004
460-3-60
Std
414 5084.440.01
Alt2.18.415848/48
High2.68.915957/57
Std
575-3-60
518 6323.731.01
Alt2.16.915837
High2.67.315745
208/230-1-60
Std
187 25423.3118.01
Alt4.935.4/35.445/4534/34133/133
Std
208/230-3-60
187 25415.490.01
Alt4.925.6/25.630/3025/25105/105
High5.225.9/25.930/3025/25124/124
005
460-3-60
Std
414 5088.345.01
Alt2.113.3201353
High2.613.8201362
Std
575-3-60
518 6326.436.01
Alt2.110.3151142
High2.610.7151050
208/230-1-60
Std
187 25428.8147.01
Alt6.644.0/44.060/6042/42184/184
Std
208/230-3-60
Alt5.226.6/26.635/3526/26148/148
187 25416.3114.01
High7.528.9/28.935/3529/29174/174
006
460-3-60
Std
414 5087.464.01
Alt2.612.7151281
High3.413.5201394
Std
575-3-60
Alt3.010.5151066
518 6326.262.01
High3.412.6151176
Std
187 25423.6146.01
High7.532.5/32.540/4032/32205/205
Std
414 50810.673.01
High3.416.12016103
Std
518 6328.558.41
High3.412.9201482
007
208/230-3-60
460-3-60
575-3-60
LEGEND
FLA— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM— Indoor (Evaporator) Fan Motor
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC — National Electrical Code
OFM — Outdoor (Condenser) Fan Motor
RLA — Rated Load Amps
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination
load equipment (refer to NEC Articles 430 and 440), the overcurrent
protective device for the unit shall be fuse or HACR breaker. Canadian
units may be fuse or circuit breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
of voltage imbalance.
Use the following formula to determine the percent
% Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
OFM
(ea)
1
/41.4
1
/41.4
1
/40.8
1
/40.8
1
/41.4
1
/41.4
1
/40.8
1
/40.8
1
/41.4
1
/41.4
1
/40.8
1
/40.8
1
/41.4
1
/40.6
1
/40.6
IFM
FLA
3.5
3.5
COMBUSTION
FAN MOTOR
FLA
.6
POWER
SUPPLY
24.5/24.530/3023/23106/106
17.7/17.725/2517/1785/85
DISCONNECT
SIZE*
.6
1.3
7.615748/48
.3
1.3
6.315735
.3
3.5
3.5
.6
34.0/34.040/4032/32129/129
24.2/24.230/3023/23101/101
.6
1.8
13.0201351
.3
1.8
10.1151041
.3
5.9
5.9
.6
43.3/43.360/6042/42161/161
27.3/27.335/3529/29128/128
.6
3.1
13.2201372
.3
3.1
10.9151158
.3
5.2
2.6
2.6
.6
.3
.3
30.2/30.235/3529/29180/180
15.4201590
12.3151372
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
452 + 464 + 455
1371
=
3
= 457
3
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT:
than 2%, contact your local electric utility company immediately.
If the supply voltage phase imbalance is more
11
Page 12
Step 8 — Make Outdoor-Air Adjustments and
Install Outdoor-Air Hood
MANUAL OUTDOOR-AIR DAMPER — The outdoor-air
hood and screen are attached to the base pan at the bottom of
the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for building.
Record amount for use in Step 8.
2. Remove and save outdoor air opening panel and screws.
See Fig. 13.
3. Separate hood and screen from basepan by removing the
4 screws securing them. Save all screws.
4. Replace outdoor air opening panel.
OUTDOOR
AIR OPENING
PANEL
3 SCREWS
(SIDE)
5. Place hood on front of outdoor air opening panel. See
Fig. 14 for hood details. Secure top of hood with the
4 screws removed in Step 3. See Fig. 15.
6. Remove and save 6 screws (3 on each side) from sides of
the manual outdoor-air damper.
7. Align screw holes on hood with screw holes on side of
manual outdoor-air damper. See Fig. 14 and 15. Secure
hood with 6 screws from Step 6.
8. Adjust minimum position setting of the damper bl ade by
adjusting the manual outdoor-air adjustment screws on
the front of the damper blade. See Fig. 13. Slide blade
vertically until it is in the appropriate position determined
by Fig. 16. Tighten screws.
9. Remove and save screws currently on sides of hood.
Insert screen. Secure screen to hood using the screws. See
Fig. 15.
Fig. 13 — Damper Panel with Manual Outdoor-Air
Damper Installed
Fig. 15 — Outdoor-Air Damper with
Hood Attached
Fig. 14 — Outdoor-Air Hood Details
Fig. 16 — Position Setting
12
Page 13
OPTIONAL DURABLADE ECONOMIZER — The option-
ECONOMIZER
CONTROL
BOARD
BAROMETRIC
RELIEF
DAMPER
ECONOMIZER
PLUG
ECONOMIZER
MOTOR
SHIPPING
SCREW
Fig. 18 — Outdoor-Air Hood Details
Fig. 19 — Horizontal Durablade
Economizer Installation
Fig. 17 — Typical Access Panel Locations
al economizer hood assembly is packaged and shipped in the filter section. Dampe r blades an d cont rol boa rds are ins talled at th e
factory and the ec onomizer is shipped in the vertical di scharge
position.
NOTE: Horizontal discharge block-off plate is shipped with
the air hood package. If unit is to be used for vertical discharge
application, discard this plate.
NOTE: Be sure to engage Durablade economizer flange under
tabs in return-air opening of the unit base.
Assembly:
1. Determine if ventilation air is re quired in building. If so,
determine the minimum amount to be supplied by ea ch
unit and record quantity of ventilation air needed for use
in Step 6.
2. Remove filter access panel by raising panel and swinging
panel outward. Panel is now disengaged from track and
can be removed. No tools are required to remove filter access panel. Remove outdoor-air opening panel. Save panels and screws. See Fig. 17. Remove optional economizer
and outdoor-air damper hood package from filter section.
3. Assemble outdoor-air hood top and side plates as shown
in Fig. 18. Install seal strips on hood top and sides. Put
aside screen retainer and screws for later assembly.
not attach hood to unit at this time.
4. To convert to horizontal discharge application:
a. Rotate economizer 90 degrees until the econo-
mizer motor faces the condenser section (see
Fig. 19).
b. Re move screws and t ape fr om da mper t hen r otate
the barometric relief damper hinge 90 degrees.
Barometric relief damper should open vertically to
operate properly.
c. Install horizontal discharge block-off plate over
the opening on the access panel. (Block-off plate
MUST be installed before installing hood assembly.) See Fig. 20. Remove 12-pin blue and yellow
wire jumper plug and store.
5. Insert economizer plug into economizer harness. Remove
tape from barometric relief damper. See Fig. 21. Remove
shipping screw (see Fig. 19).
6. If ventilation air is not required, proceed to Step 7. If ventilation air is required, determine the minimum position
setting for required airflow. See Fig. 22. Adjust minimum
position setting by adjusting the screws on the position
setting bracket. Slide bracket until the top screw is in the
position determined by Fig. 22. Tighten screws.
7. Remove tape from outdoor-air thermostat (OAT). Fasten
OAT to inside of hood using screws and speed c lips provided. See Fig. 23. Make sure OAT terminals are positioned up.
8. Replace outdoor-air opening panel using screws from
Step 2. Replace filter a ccess panel. Ensure the filter ac cess panel slides along the tracks and is securely engaged.
9. Fasten hood top and side plate assembly (Fig. 18) to
outdoor-air opening panel with screws provided.
10. Place knob supplied with economizer on OAT. See
Fig. 23. Set OAT for 3° F below indoor room thermostat
setting. If accessory enthalpy control (EC) is used in
place of OAT, see instructions shipped with EC for installation and adjustment. See Fig. 23.
11. Connect OAT per Fig. 24.
12. Slide outdoor-air inlet screens into screen track on hood
side plate. While holding screen in place, fasten screen retainer to hood using screws provided.
NOTE: Refer to Fig. 25 for economizer barometric relief
damper characteristics.
Do
13
Page 14
BLOCK-OFF PLATE
Fig. 20 — Horizontal Discharge Block-Off Plate
U-SHAPED
HOLE
(NOT
SHOWN)
ECONOMIZER
CONTROL
BOARD
ECONOMIZER
PLUG
WIRING
HARNESS
BAROMETRIC
RELIEF DAMPER
SHIPPING
SCREW
ECONOMIZER
MOTOR
POSITION SETTING
BRACKET
TOP
SCREW
Fig. 21 — Durablade Economizer Installed in Unit
ENTHALPY
CONTROL
HOOD
TOP
OUTSIDE AIR
SCREEN
OPEN
P
P1
T
Y
10
50
OUTDOOR TEMP
55
60
65
70
.
7
°
5
F
80
85
OAT
(TERMINALS ARE UP)
UNIT
RE
B
V
.
POSITION
MINIMUM
1
3
T
5
2
T1
4
CONT
CONT
OR UNPOWERED ST
R
%
1
H
U
U
M
9
I
D
I
S
8
90
A
H
8
70
ACT RA
CTS SHO
60
1
A
30
DAMPER
OPEN
.
V
E
R
CLOSED
97
3
8
T
CW
2
A
D
4
V
–SETPOINTS
TINGS: 1.5A
C
A
W
C
N IN H
B
2
A
A
3 m
TE
IGH ENTHALPY
A
RUN, 3.5A IN
M
–CCW
IN. A
1
DAMPER
T 1
1 VDC
2
7
6
-3
B
C
TR
D
S
S
O
ENTHALPY CONTROL
TR
2
4
V
A
C
TR1
Example:
Given — Negative Pressure. . . . . . . . . . . . . . . . . . . . . . . 0.2 in. wg
OPTIONAL ECONOMI$ER — See Fig. 26 for EconoMi$er
component locations.
1. To remove the existing unit filter access panel, raise the
panel and swing the bottom outward. The panel is now
disengaged from the track and can be removed. Remove
the indoor coil access panel and discard. See Fig. 27.
If installing an optional Power Exhaust Assembly, refer to
EconoMi$er Power Exhaust Installation Instructions
the
Controller should be mounted in vertical position as
shown in Fig. 26.
2. Assemble the hood assembly as follows:
Remove the EconoMi$er hood from its packaging.
Remove shipping brackets holding hood package to
EconoMi$er. Locate the outdoor-air opening panel. See
Fig. 28. Remove hood assembly shipping brackets located on the back (sloped) side of the EconoMi$er assembly.
These brackets are used to retain the hood assembly during shipping only .
3. Install the
1
/8 x 3/4-in. seal strip on the exhaust air hood
side panels and the bottom bracket. Assemble the exhaust
air hood to the outdoor-air opening panel as shown in
Fig. 28, using the screws provided.
assembly to unit at this time.
4. Instal l the
top and side panels. Assemble the outdoor-air hood to the
outdoor-air opening panel as shown in Fig. 29, using the
screws provided.
at this time.
1
/8 x 3/4-in. seal strip on the outdoor-air hood
Do not attach hood assembly to the unit
500600
700
Do not attach hood
800
.
15
Page 16
5. Slide the outdoor-air inlet screens into the screen track on
WIRING
HARNESS
OUTDOOR
AIR
BLOCK-OFF
PLATE
Fig. 32 — EconoMi$er Installed
Fig. 31 — Rear EconoMi$er Flange Installation
Fig. 30 — Completed Hood Assembly
the hood side panels. While holding the screens in pl ace,
fasten the screen retainer to the hood using the screws
provided. Repeat the process for the barometric exhaust
air screen.
Do not attach completed (Fig. 30) hood as-
sembly to unit a t this ti me.
6. Slide the EconoMi$er assembly into the rooftop unit. See
Fig. 31 and 32.
NOTE: Be sure to engage rear EconoMi$er flange under tabs in
return-air opening of the unit base. See Fig. 31.
7. Install the outdoor-air block-off plate, then secure the
EconoMi$er with the screws provided. See Fig. 32.
8. Remove and discard the 12-pin jumper plug from the unit
wiring harness located in the upper left corner and insert
the EconoMi$er plug into the unit wiring harness. Refer
to wiring diagrams Fig. 33 and 34. Also refer to Fig. 35 if
installing an accessory power exhaust.
9. Install the complete hood assembly on the unit and secure
using the screws provided.
10. Remove the indoor fan motor access panel. See Fig. 36.
11. Mount the supply-air temperature sensor to the lower
left portion of the indoor blower housing with the
two (2) screws provided (see Fig. 37). Connect the vi olet
and pink wires to the corresponding connections on the
supply-air temperature sensor. Replace the indoor fan
motor access panel.
UNIT FILTER
RACK
UNIT BASE
ECONOMI$ER CLIP
HVAC UNIT
ECONOMI$ER
ECONOMI$ER REAR
FLANGE
OUTDOOR AIR
OPENING
PANEL
ASSEMBLED
EXHAUST HOOD
Fig. 29 — Outdoor-Air Hood Assembly
SEAL STRIP
SEAL STRIP
OUTDOOR AIR
HOOD SIDES
OUTDOOR AIR
HOOD TOP
SCREEN
RETAINER
OUTDOOR AIR
INLET
SCREENS
16
Page 17
LEGEND
OAT —
Outdoor-Air Thermostat
Fig. 33 — EconoMi$er Wiring
ECONOMI$ER
CONTROLLER
OAT
COM
OAH
-15 V
RAT
COM
RAH
+15 V
CO
2
COM
CO
2
DAT
COM
REM POT
COM
LED
COM
(+)
BROWN
VIOLET
WHITE
RED
BROWN
VIOLET
WHITE
RED
SUPPLY AIR
TEMPERATURE SENSOR
PINK
VIOLET
TEMP
TEMP
TEMP
TEMP
COM
OUT
PWR
TEMP
TEMP
COM
OUT
PWR
CO
SENSOR
2
V+
COM VAC
24
Fig. 34 — EconoMi$er Sensor Wiring
17
OUTDOOR
AIR
SENSOR
RETURN
AIR
SENSOR
Page 18
TO FUSED
DISCONNECT
CAPACITOR 2
CAPACITOR 1
FAN 1
FAN 2
RED
H1
(575 VAC)
HT01AH859
X4
SECONDARY
HANDY BOX
X2
230VAC
2 x 4 IN.
X3
GRAY
H2
X1
GREEN GND
OR
BLACK L1
BLUE L2
RED YELH1BLU
(460 VAC)
HT01AH850
X4
COMPRESSOR 1
CONTACTOR
1121
23
13
CONNECTOR
L1
1
1
L2
22
GND
33
44
230 VAC
1 PHASE
H3
H2
X3
X2
SECONDARY
230VAC
230VAC
4-PIN
PLUG
GREEN
GRAY
H4
X1
BLACK
BLUE
RELAY 2
RELAY 1
FIELD SUPPLIED
WIRING
BROWN
C1
GREEN/
YELLOW
BROWN
C1
GREEN/
YELLOW
FAN 1
FAN 2
4-PIN
CONNECTOR PLUG
(HIGH VOLTAGE)
BLACK
BLACK
LT. BLUE
BLACK
BLUE
BLACK
LT. BLUE
BLACK
3
2
1
3
2
1
6
5
4
6
5
4
BLUE
3-PIN
CONNECTOR PLUG
(LOW VOLTAGE)
B
9
8
7
9
8
7
R1
24 VAC
A
B
R2
24 VAC
A
3-PIN
CONNECTOR
PLUG
ORANGE
YELLOW
BROWN
1
2
3
Fig. 35 — Wiring Diagram for Power Exhaust System
CENTER PANEL
THERMOSTAT
CONNECTION
ACCESS PANEL
HEATING
ACCESS
PANEL
INDOOR FAN
MOTOR ACCESS
PANEL
Fig. 36 — Typical Access Panel Locations
(Standard Efficiency Unit Shown)
18
Page 19
SUPPLY AIR
Fig. 38 — EconoMi$er Control Adjustment
Potentiometers (Factory Settings)
0
200
400
600 800 1000
1200
1400 1600
FLOW (CUBIC FEET/MINUTE)
0.5
0.4
0.3
0.2
0.1
0
STATIC PRESSURE (IN. WG)
Fig. 39 — Barometric Relief Capacity
TEMPERATURE
SENSOR
MOUNTING
LOCATION
SUPPLY AIR
TEMPERATURE
SENSOR
Fig. 37 — Supply-Air Sensor Placement
Control Set Up — If a CO2 sensor is not being used,
CO
2
proceed to the next section. If a CO
sensor is being used, per-
2
form the following:
1. Determine the value at which you want the minimum
position of the dampers to begin opening to allow a
greater amount of outdoor air to enter. The range is 800 to
1,400 ppm.
2. Locate the CO
SP (PPM) potentiometer and adjust to the
2
desired set point. See Fig. 38.
Mechanical Cooling Lockout
— Determine the outdoor-air
temperature at which you want the mechanical cooling (compressors) to be disabled. Locate the mechanical cooling lockout (MECH CLG LOCKOUT) potentiometer. To disable this
feature, turn the potentiometer counterclockwise (CCW) to the
OFF position. Otherwise, set the value between 10 and 60 F.
Mechanical cooling will not operate when the outdoor air temperature is below this value. See Fig. 38.
Dry Bulb Cha ngeover Set Up
— Determine the dry bulb
changeover set point from Table 3. The settings are A, B, C
and D. Locate the ECON SP potentiometer and set the dry
bulb changeover set point. See Fig. 38. When the OAT is
above this set point, the damper is limited to minimum position
setting.
Ventilation Air (Minimum Position Set up)
— If ventilation
air is not required, proceed to Step 5. If ventilation air is
required, perform the following:
1. The indoor fan must be on to set the ventilation air. Either
put the thermostat in the continuous fan mode or jump er
the R and G terminals at the rooftop unit connection
board.
2. Locate the minimum position (MIN PO S) potentiometer.
Turn the potentiometer full CCW to fully close the outdoor air dampers. Turn the potentiometer gradually
clockwise (CW) to the desired position. See Fig. 38.
3. Replace the filter access panel. See Fig. 26. Ensure the filter access panel slides along the tracks and is securely
engaged.
4. Calculate the minimum airflow across the EconoMi$er.
a. Calculate % of outside air using the following
formula.
% Outdoor air through EconoMi$er
% Outdoor air =
Mixture Temp – Return Air Temp
Outdoor T emp – Return Air Temp
b. Divide total CFM by percentage outdoor air, this
gives outdoor air vol ume in CFM.
5. Turn on base unit power.
NOTE: The EconoMi$er begins operation three min-
utes after power up.
Personal Injury Hazard.
Avoid possible injury by keep-
ing fingers away from damper blades.
6. See Fig. 39 for barometric relief damper characteristics.
Table 3 — Changeover Set Points
SETTINGSABCD
Dry Bulb (°F)
Single Enthalpy* (Btu/lb)
Differential Temperature*
(°F, Not Adjustable)
Differential Enthalpy*
(Btu/lb, Not Adjustable)
*Field-installed accessory.
If a potentiometer fails, its setting will default to t he values in
T able 4.
Table 4 — Default Potentiometer Settings
POTENTIOMETERDEFAULT SETTING
CO
SP (PPM)
2
MECH CLG LOCKOUT
ECON SP
MIN POS (%)
73696663
27252422
2222
1111
1,000
47°
D
20
19
Page 20
Step 9 — Adjust Evaporator-Fan Speed —
Adjust evaporator-fan rpm to meet jobsite conditions. Table 5
shows fan rpm at motor pulley settings. Table 6 shows motor
performance. See Table 7 for Accessory/FIOP Static Pressure.
Refer to Tables 8-29 to determine fan speed settings.
DIRECT-DRI VE MOTORS — The evaporator-fan motor
factory speed setting is shown on label diagram affixed to base
unit. If other than factory setting is desired, refer to label diagram for motor reconnection. See Fig. 40 for direct drive motor
location.
BELT-DRIVE MOTORS — Fan motor pulleys are factory set
for speed shown in Table 1. See Fig. 41 for belt drive location.
NOTE: Before adjusting fan speed, make sure the new fan
speed will provide an air temperature rise range as shown in
T able 1.
T o change fan speed:
1. Shut off unit power supply and tag disconnect.
2. Loosen belt by loosening fan motor mounting nuts. See
Fig. 41.
3. Loosen movable pulley flange setscrew (see Fig. 42).
4. Screw movable flange toward fixed flange to increase
speed and away from fixed flange to decrease speed.
Increasing fan speed increases load on motor. Do not exceed maximum speed specified in Table 1.
5. Set movable flange at nearest keyway of pul ley hub and
tighten setscrew. (See Table 1 for speed change for ea ch
full turn of pulley flange.)
T o align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from
mounting.
T o adjust belt tension:
1. Loosen fan motor mounting nuts.
2. Slide motor mounting plate away from fan scroll for
proper belt tension (
1
/2-in. deflection with 8 to 10 lbs of
force).
3. Tighten motor mounting nuts.
4. Adjust bolt and tighten nut to secure motor in fixed
position.
*Extensive motor and electrical testing on these units ensures that the
full horsepower range of the motors can be utilized with confidence.
Using your fan motors up to the horsepower ratings shown in this table
will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
†Single phase/three-phase.
EVAPORATOR-FAN
MOTOR
Standard
Alternate
High Static
Standard
Alternate
High Static
Standard
Alternate
High Static
Standard
High Static
UNIT
VOLTAGE
208/230
4601.3
5751.3
208/230
4602.1
5752.1
208/230
4603.0
5753.0
208/230
4601.8
5751.8
208/230
4602.1
5752.1
208/230
4603.0
5753.0
208/230
4603.2
5753.2
208/230
4603.0
5753.0
208/230
4603.9
5753.9
208/230
4603.0
5753.0
208/230
4603.9
5753.9
MOTOR PULLEY TURNS OPEN
1
/
MAXIMUM ACCEPTABLE
CONTINUOUS BHP*
33
2
**Indicates high-static motor and drive package.
††Indicates standard motor and drive package.
1
/
2
0.34440
1.001000
2.402120
0.75850
1.001000
2.402120
1.201340
1.30/2.40†2120
2.902562
2.402120
2.902562
NOTES:
1. All indoor-fan motors 5 hp and larger meet the minimum efficiency
requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.
2. High-static motor not available on single-phase units.
2. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Table 6 — Motor Data for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
805 0.25249865 0.29288911 0.34338
1029 0.666561073 0.727161109 0.77766
1032 0.626171067 0.67666
1047 0.60597
48TJ004 (3 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)
3. Values include losses for filters, unit casing, and wet coils. See
Table 7 for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 1.0 and the maximum continuous
watts are 1000. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized with
confidence. Using your fan motors up to the wattage ratings shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected. See Table 6 — Motor Data for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
22
Page 23
Table 10 — Fan Performance 48TJ004 — Vertical Discharge Units, High-Static Motor
48TJ004 (3 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
Brake Horsepower Input to Fan
Factory-Installed Option
Input Watts to Motor
indicates field-supplied drive is required.
0.20.40.60.81.0
1.21.41.61.82.0
External Static Pressure (in. wg)
10860.55547
10900.6463711560.68676
11220.7069611900.76756
11090.7776611901.0085512710.95945
External Static Pressure (in. wg)
14651.25124215001.34133215321.431419
3. Maximum continuous bhp is 2.4 and the maximum continuous
watts are 2120. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized with
confidence. Using your fan motors up to the wattage ratings shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected. See Table 6 — Motor Data for additional information.
4. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
5. Interpolation is permissible. Do not extrapolate.
11600.8476612370.85845
14631.19118014941.261257
11090.61607
Table 11 — Fan Performance 48TJ005 — Vertical Discharge Units, Standard Motor
48TJ005 (4 TONS) — STANDARD MOTOR (DIRECT DRIVE)
Airflow
(Cfm)
1200
1300
1400
1500
1600
1700
1800
1900
2000
LEGEND
Bhp —
Esp —
FIOP —
NOTES:
Brake Horsepower Input to Fan
External Static Pressure (in. wg)
Factory-Installed Option
1. Values include losses for filters, unit casing, and wet coils. See
Table 7 for accessory/FIOP static pressure information.
2. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Table 6 — Motor Data for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
23
Page 24
Table 12 — Fan Performance 48TJ005 — Vertical Discharge Units, Alternate Motor
3. Values include losses for filters, unit casing, and wet coils. See Table 7
for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 1.0 and the maximum continuous watts are
1000. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using your
fan motors up to the wattage ratings shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
See Table 6 — Motor Data for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
1268 1.10 1029
Table 13 — Fan Performance 48TJ005 — Vertical Discharge Units, High-Static Motor
48TJ005 (4 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
3. Maximum continuous bhp is 2.4 and the maximum continuous watts are
2120. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using your
fan motors up to the wattage ratings shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
See Table 6 — Motor Data for additional information.
4. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
5. Interpolation is permissible. Do not extrapolate.
24
Page 25
Table 14 — Fan Performance 48TJ006 — Vertical Discharge Units, Standard Motor
2. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Table 6 — Motor Data for Additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
3. Values include losses for filters, unit casing, and wet coils. See
Table 7 for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 1.30 for single-phase units and 2.40
for 3-phase units and the maximum continuous watts are 2120.
Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Table 6 — Motor Data for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
25
Page 26
Table 16 — Fan Performance 48TJ006 — Vertical Discharge Units, High-Static Motor
48TJ006 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
3. Values include losses for filters, unit casing, and wet coils. See
Table 7 for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 2.9 and the maximum continuous
watts are 2562. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized with
confidence. Using your fan motors up to the wattage ratings shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected. See Table 6 — Motor Data for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
13561.80190114182.072115
13011.91194413492.122164
13522.01204714012.232280
16322.97303116913.313375
13471.721758
16543.083141
26
Page 27
Table 17 — Fan Performance 48TJ007 — Vertical Discharge Units, Standard Motor
3. Values include losses for filters, unit casing, and wet coils. See
Table 7 for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 2.40 and the maximum continuous
watts are 2120. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized with
confidence. Using your fan motors up to the wattage ratings shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected. See Table 6 — Motor Data for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
16022.642326 16662.852504
15322.141892
27
Page 28
Table 18 — Fan Performance 48TJ007 — Vertical Discharge Units, High-Static Motor
48TJ007 (6 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
3. Values include losses for filters, unit casing, and wet coils. See
Table 7 for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 2.9 and the maximum continuous
watts are 2562. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized with
confidence. Using your fan motors up to the wattage ratings shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected. See Table 6 — Motor Data for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
13401.53136114281.661473
17533.583262———
17673.693360———
16942.44222417582.732485
17362.682441
——————
13221.331190
13561.471310
17753.623290
17172.492266
———
———
28
Page 29
Table 19 — Fan Performance 48TJ004 — Horizontal Discharge Units, Standard Motor
48TJ004 (3 TONS) — STANDARD MOTOR (DIRECT DRIVE)
Airflow
(Cfm)
900
1000
1100
1200
1300
1400
1500
LEGEND
Bhp —
Esp —
FIOP —
NOTES:
1. Values include losses for filters, unit casing, and wet coils. See
Brake Horsepower Input to Fan
External Static Pressure (in. wg)
Factory-Installed Option
Table 7 for accessory/FIOP static pressure information.
EspBhpWattsEspBhpWattsEspBhpWattsEspBhpWatts
0.540.212530.570.232770.550.263070.600.31363
0.490.232700.510.252920.520.273210.530.32374
0.430.242870.450.263070.460.283350.490.33385
0.390.263040.400.273230.380.293490.430.34397
0.330.273210.350.293380.350.313640.360.34408
0.260.293380.280.303540.290.32378———
0.210.303550.230.313690.240.33392———
208 V230, 460, 575 V208 V230, 460, 575 V
Low SpeedHigh Speed
2. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Table 6 — Motor Data for Additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
Table 20 — Fan Performance 48TJ004 — Horizontal Discharge Units, Alternate Motor
3. Maximum continuous bhp is 1.00 and maximum continuous watts
are 1000. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Table 6 — Motor Data for additional
information.
4. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
5. Interpolation is permissible. Do not extrapolate.
29
Page 30
Table 21 — Fan Performance 48TJ004 — Horizontal Discharge Units, High-Static Motor
48TJ004 (3 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
Brake Horsepower Input to Fan
Factory-Installed Option
Input Watts to Motor
indicates field-supplied drive is required.
0.20.40.60.81.0
1.21.41.61.82.0
External Static Pressure (in. wg)
10000.52527
11360.59577
11720.65647
10970.6867612450.74776
External Static Pressure (in. wg)
14671.14113515021.22121815341.301298
3. Maximum continuous bhp is 2.4 and maximum continuous watts
are 2120. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Table 6 — Motor Data for additional
information.
4. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
5. Interpolation is permissible. Do not extrapolate.
14611.11110414921.181176
12080.70706
30
Page 31
Table 22 — Fan Performance 48TJ005 — Horizontal Discharge Units, Standard Motor
48TJ005 (4 TONS) — STANDARD MOTOR (DIRECT DRIVE)
Airflow
(Cfm)
1200
1300
1400
1500
1600
1700
1800
1900
2000
LEGEND
Bhp —
Esp —
FIOP —
NOTES:
1. Values include losses for filters, unit casing, and wet coils. See
Brake Horsepower Input to Fan
External Static Pressure (in. wg)
Factory-Installed Option
Table 7 for accessory/FIOP static pressure information.
2. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Table 6 — Motor Data for Additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
3. Values include losses for filters, unit casing, and wet coils. See
4. Maximum continuous bhp is 1.00 and the maximum continuous
5. Use of a field-supplied motor may affect wire sizing. Contact your
6. Interpolation is permissible. Do not extrapolate.
1183 1.10 1052 1226 1.23 1215 1297 1.35 1406
Table 7 for accessory/FIOP static pressure information.
watts are 1000. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized with
confidence. Using your fan motors up to the wattage ratings shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected. See Table 6 — Motor Data for additional information.
Carrier representative for details.
1189 1.12 1138 1245 1.21 1358
31
Page 32
Table 24 — Fan Performance 48TJ005 — Horizontal Discharge Units, High-Static Motor
48TJ005 (4 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
Brake Horsepower Input to Fan
Factory-Installed Option
Input Watts to Motor
indicates field-supplied drive is required.
0.20.40.60.81.0
1.21.41.61.82.0
External Static Pressure (in. wg)
10950.95930
10771.01103011511.151185
11041.07112411781.261318
10871.12117711621.30136612311.481604
External Static Pressure (in. wg)
3. Maximum continuous bhp is 2.4 and maximum continuous watts
are 2120. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Table 6 — Motor Data for additional
information.
4. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
5. Interpolation is permissible. Do not extrapolate.
11321.18124012041.371502
14682.272171
11231.051073
14712.182167
14932.362345
———
Table 25 — Fan Performance 48TJ006 — Horizontal Discharge Units, Standard Motor
2. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Table 6 — Motor Data for Additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
32
Page 33
Table 26 — Fan Performance 48TJ006 — Horizontal Discharge Units, Alternate Motor
3. Values include losses for filters, unit casing, and wet coils. See
Table 7 for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 1.30 for single-phase units and 2.40
for 3-phase units and the maximum continuous watts are 2120.
Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Table 6 — Motor Data for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
14002.122227 14612.342459
13591.801902
14262.152259
33
Page 34
Table 27 — Fan Performance 48TJ006 — Horizontal Discharge Units, High-Static Motor
48TJ006 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
3. Values include losses for filters, unit casing, and wet coils. See
Table 7 for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 2.9 and the maximum continuous
watts are 2562. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized with
confidence. Using your fan motors up to the wattage ratings shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected. See Table 6 — Motor Data for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
13591.801902 14232.022122
13621.731818
34
Page 35
Table 28 — Fan Performance 48TJ007 — Horizontal Discharge Units, Standard Motor
3. Values include losses for filters, unit casing, and wet coils. See
Table 7 for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 2.4 and maximum continuous watts
are 2120. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Table 6 — Motor Data for additional
information.
5. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
15142.422136 15702.662343
15362.462171
35
Page 36
Table 29 — Fan Performance 48TJ007 — Horizontal Discharge Units, High-Static Motor
48TJ007 (6 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
3. Values include losses for filters, unit casing, and wet coils. See
Table 7 for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 2.9 and the maximum continuous
watts are 2562. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized with
confidence. Using your fan motors up to the wattage ratings shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected. See Table 6 — Motor Data for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
13541.581404 14131.751552
16113.012648 16923.493140
13411.401250
16713.032725
36
Page 37
START-UP
Unit Preparation —
stalled in accordance with these installation instructions and
applicable codes.
Return-Air Filters —
stalled in filter tracks. See Table 1. Do not operate unit without
return-air filters.
Compressor Mounting —
spring mounted. Do not loosen or remove compressor holddown bolts.
Internal Wiring —
unit control boxes. Tighten as required. Ensure electrical wires
do not come in contact with refrigerant tubing or sharp edges.
Refrigerant Service Ports —
service ports, remove refrigerant service port access panel. See
Fig. 43. Each unit system has 4 Schrader-type service gage
ports: one on the suction line, one on the liquid line, and two on
the compressor discharge line. Be sure that caps on the ports
are tight. When a controls upgrade package is used, one
Schrader-type valve is located under both the high-pressure
switch and the low-pressure switch.
High Flow Valves —
and suction tubes are High Flow Valves. Large black plastic
caps distinguish these valves with o-rings located inside the
caps. These valves can not be acce ssed f or servic e in t he fiel d.
Ensure the plastic caps are in place and tight or the possibility
of refrigerant leakage could occur.
Make sure that unit has been in-
Make sure correct filters are in-
Compressors are internally
Check all electrical connections in
To service refrigerant
Located on the compressor hot gas
2. Turn off power to the unit and install lockout tag.
3. Reverse any two of the unit power leads.
4. Reapply power to unit and recheck pressures.
The suction and discharge pressure levels should now move
to their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direc-
tion, the unit makes an elevated level of noise and does not
provide cooling.
Cooling —
Set space thermostat of OF F position. To start
unit, turn on main power supply. Set system selector switch at
COOL position and fan switch at AUTO. position. Adjust thermostat to a setting below room temperature. Compressor starts
on closure of contactor.
Check unit charge. Refer to Service, Refrigerant Charge
section, page 41. Allow unit to operate a minimum of 10 mi nutes before checking charge.
Reset thermostat at a position above room temperature.
Compressor will shut off. Evaporator fan will shut off after
30-second delay.
TO SHUT OFF UNIT — Set s y stem selector switch at OFF
position. Resetting thermostat at a position above room temperature shuts unit off temporarily until space temperature exceeds thermostat setting.
Main Burners —
Main burners are factory set and should
require no adjustment.
TO CHECK ignition of main burners and heating controls,
move thermostat set point above room temperature and verify
that the burners light and evaporator fan is energized. After ensuring that the unit continues to heat the building, lower the
thermostat setting below room temperature and verify that the
burners and evaporator fan turn off. (Fan will turn off only if
fan selector switch is in the AUTO. position and after a
45-second delay has elapsed.)
Refer to Table 30 for the correct orifice to use at high
altitudes.
Fig. 43 — Service Panel Location
Compressor Rotation —
On 3-phase units with scroll
compressors, it is important to be certain compressor is rotating
in the proper direction. To determine whether or not compressor is rotating in the proper direction:
1. Connect service gages to suction and discharge pressure
fittings.
2. Energize the unit.
3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pres-
sure does not rise to normal levels:
1. Note that the evaporat or fan is probably also rotating in
the wrong direction.
Table 30 — Altitude Compensation*
74,000 AND 115,000
BTUH NOMINAL
ELEVATION
(ft)
0-2,000
2,000
3,000
4,000
5,000
6,000
7,000
8,000
9,000
10,000
11,000
12,000
13,000
14,000
*As the height above sea level increases, there is less oxygen per
cubic foot of air. Therefore, heat input rate should be reduced at
higher altitudes.
†Orifices available through your Carrier distributor.
1. Purge gas supply line of air by opening union ahead of
gas valve. If gas odor is detected, tighten union and w ait
5 minutes before proceeding.
2. Turn on electrical supply and open manual gas valve.
3. Set system switch selector at HEAT position and fan
switch at AUTO. or ON position. Set heating temperature
lever above room temperature.
4. The i nduced-draf t motor w ill star t.
5. After a call for heating, the main burners should light
within 5 seconds. If the burner does not light, then there is
a 22-second delay before another 5-second try. If the
burner still does not light, the time delay is repeated. If the
burner does not light within 15 minutes, there is a lockout. To reset the control, break the 24 v power to W1.
ADJU ST G AS I NPUT — The gas input to the unit is determined by measuring the gas flow at the meter or by measuring
the manifold pressure. Measuring the gas flow at the meter is
recommended for natural gas units. The manifold pressure
must be measured to determine the input of propane gas units.
Measure Gas Flow (Natural Gas Units)
to the gas flow can be made by changing the manifold pressure.
The manifold pressure must be maintained between 3.4 and
3.6 in. wg. If larger adjustments are required, change main
burner orifices following the recommendations of national and
local codes. Unit must be operating with both W1 and W2 energized (high-fire).
NOTE: All other appliances that use the same meter must be
turned off when gas flow is measured at the meter.
Proceed as follows:
1. Turn off gas supply to unit. Turn off electric supply to
unit and install lockout tag.
2. Remove pipe plug on manifold (see Fig. 44) then connect
manometer at this point. Turn on gas to unit.
3. Turn on electrical power.
4. Energize W1, and/or W2 at thermostat. Ensure gas valve,
if 2-stage style, is in “High Fire.”
Observe manifold pressure and proceed as follows to adjust
gas input:
1. Remove cover screw over regulator adjustment screw on
gas valve.
2. Turn regulator adjustment screw clockwise to increase
gas input, or turn regulator adjustment screw counterclockwise to decrease input. Manifold pressure must be
3.5 in. wg while in high fire.
Unsafe operation of the unit may result i f manifold pressure is outside this range. Personal injury or unit damage
may result.
3. Replace cover screw cap on gas valve.
4. Turn off gas supply to unit. Remove manometer from
pressure tap and replace pipe plug on gas valve. Turn on
gas to unit and check for leaks.
Measure Manifold Pressure (Propane Units)
burner orifices on a propane gas unit are sized for the unit rated
input when the manifold pressure reading is 3.5 in. wg.
Ensure unit is operating in High-Fire operation mode (W1
and W2 energized) before adjusting manifold pressure.
Proceed as follows to adjust gas input on a propane gas unit:
1. Turn off gas to unit.
2. Remove pipe plug on manifold (see Fig. 44), then connect manometer at this point.
— Minor adjustment
— The main
3. Turn on gas to unit.
4. Remove cover screw over regulator adjustment screw on
gas valve.
5. Adjust regulator adjustment screw to the correct manifold
pressure, 3.5 in wg. Turn adjusting screw clockwise to increase manifold pressure, or turn adjusting screw counterclockwise to decrease manifold pressure.
6. Replace cover screw.
7. Turn off gas to unit. Remove manometer from pressure
tap. Replace pipe plug on gas valve, then turn on gas to
unit. Check for gas leaks.
8. The evaporator-fan m otor will turn on 45 seconds after
the burners are ignited.
9. The evaporator-fan motor will turn off 45 seconds after
thermostat temperature is satisfied.
10. Adjust airflow to obtain a temperature rise within the
range specified on the unit nameplate.
NOTE: The default value for the evaporator-fan motor ON/
OFF delay is 45 seconds. The Integrated Gas Unit Controller
(IGC) modifies this value when abnormal limit switch cycles
occur. Based upon unit operat ing conditions, the ON delay can
be reduced to 0 seconds and the OFF delay can be extended to
180 seconds. When one flash of the LED is observed, the
evaporator-fan ON/OFF delay has been modified.
If the limit switch trips at the start of the heating cycle during the evaporator ON delay, the time period of the ON delay
for the next cycle will be 5 seconds less than the time at which
the switch tripped. (Example: If the limit switch trips at 30 seconds, the evaporator-fan ON delay for the next cycle will occur
at 25 seconds.) To prevent short-cycling, a 5-second reduction
will only occur if a minimum of 10 minutes has e lapsed since
the last call for heating.
The evaporator-fan OFF delay can also be modified. Once
the call for heating has ended, there is a 10-minute period during which the modification can occur. If the limit switch trips
during this period, the evaporator-fan OFF delay will increase
by 15 seconds. A maximum of 9 trips can occur, extending the
evaporator-fan OFF delay to 180 seconds.
To restore the original defaul t value, reset the power t o the
unit.
TO SHUT OFF UNIT — Set s y stem selector switch at OFF
position. Resetting heating selector lever below room temperature will shut unit off until space temperature falls below thermostat setting.
38
Page 39
Safety Relief —
Schrader port provides pressure relief under abnormal temperature and pressure conditions (i.e., fire in building). Us e backup
wrench when tightening flare cap.
High Flow Valves —
and suction tubes are High Flow Valves. Large black plastic
caps distinguish these valves with O-rings located inside the
caps. These valves cannot be accessed for servi ce in the field.
Ensure the plastic caps are in place and tight or the possibility
of refrigerant leakage could occur.
Ventilation (Continuous Fan) —
selector switches at ON and OFF positions, respectively.
Evaporator fan operates continuously to provide constant air
circulation. When the evaporator-fan sel ector switch is turned
to the OFF position, there is a 30-second delay before the fan
turns off.
A soft solder joint at the suction service
Located on the compressor hot gas
Set fan and system
Operating Sequence
COOLING, UNITS WITHOUT ECONOMIZER — When
thermostat calls for cooling, terminals G and Y1 are energized,
and the indo or (evaporat or) fan mot or (IFM), c ompressor, and
outdoor (conden ser ) fan m oto r (OFM start. The OFM runs continuously while the unit is in cooling. When the thermostat is
satisfied, compressor contactor (C) is deenergized and the compressor and OFM shut off. After a 30-second delay, the IFM
shuts off. If the thermostat fan selector s witch is the ON position, the evaporator motor will run continuously.
HEATING, UN ITS WI THOUT ECON OMIZ ER — When
the thermost at calls for heating, ter minal W1 is en ergized. To
prevent thermostat short-cycling, the unit is locked into the
Heating mode for at least 1 minute when W1 is energized. The
induced-draft motor is energized and the burner ignition sequence begins. The indoor (evaporator) fan motor (IFM) is energized 45 seconds after a flame is ignited. On units equipped
for two stages of heat, when additional heat is needed, W2 is
energized and the high-fire solenoid on the main gas valve
(MGV) is energized. When the thermostat i s satisfied a nd W1
is deenergized, the IFM stops after a 45-second time-off delay.
COOLING, UNITS WITH DURABLADE ECONOMIZER — When the outdoor-air temperature is above the
outdoor-air thermostat (OAT) setting and the room thermostat
calls for cooling, compressor contactor is energized to start
compressor and the outdoor (condenser) fan motor (OFM).
The indoor (evaporator) fan motor (IFM) is energized and the
economizer damper moves to the minimum position. After the
thermostat is satisfied, there is a 30-second delay before the
evaporator fan turns off. The damper then moves to the fully
closed position. When using continuous fan, the damper moves
to the minimum position.
When the outdoor-air temperature is below the OAT setting
and the thermostat calls for cooling, the economizer damper
moves to the minimum position. If the supply-air temperature
is above 57 F , the damper continues to open until it reaches the
fully open position or until the supply-air temperature drops
below 52 F .
When the supply-air temperature falls to between 57 F and
52 F, the damper w ill remai n at a n interm ediate open position.
If the supply-air temperature falls below 52 F, the damper will
modulate closed until it reaches the minimum position or until
the supply-air temperature is above 52 F. When the thermostat
is satisfied, the damper will move to the fully closed position
when using AUTO. fan or to the minimum position when using
a continuous fan.
If the outdoor air alone cannot satisfy the cooling require ments of the conditioned space, economizer cooling is integrated with mechanical cooling, providing two stages of cooling.
Compressor and the condenser fan will be energized and the
position of the economizer damper will be determined by the
supply-air temperature. When the second stage of cooling is
satisfied, the compressor and OFM will be deenergized. The
damper position will be determined by the supply-air temperature. When the first stage of cooling is satisfied, there is a
30-second delay before the evaporator fan shuts off. The damper then moves to the fully closed position. When using a continuous fan, the damper moves to the minimum position.
COOLING, UNITS WITH ECONOMI$ER — When the
outdoor-air temperature (OA T) is above the ECON SP set point
and the room thermostat calls for Stage 1 cooling (R to G +
Y1), the indoor (evaporator) fan motor (IFM) is energized and
the EconoMi$er damper modulates to minimum position. T he
compressor contactor is energized to start the compressor and
outdoor (condenser) fan motor (OFM). After the th ermostat is
satisfied, the damper modulates to the fully closed position
when the IF M i s dee ne r gi ze d.
When the OAT is below the ECON SP setting and the room
thermostat calls for Stage 1 cooling (R to G + Y1), the
EconoMi$er modulates to the minimum position when the
IFM is energized. The EconoMi$er provides Stage 1 of cooling
by modulating the return and outdoor air dampers to maintain a
55 F supply air set point. If the supply-air temperature (SAT) is
greater than 57 F, the EconoMi$er modulates open, allowing a
greater amount of outdoor air to enter the unit. If the SA T drops
below 53 F, the outdoor air damper modulates closed to reduce
the amount of outdoor air. When the SAT is between 53 and 57
F , the EconoMi$er maintains its position.
If outdoor air alone cannot satisfy the cooling requirements
of the conditioned space, and the OAT is above the MECH
CLG LOCKOUT set point, the EconoMi$er integrates free
cooling with mechanical cooling. This is accomplished by the
strategies below.
NOTE: Compressor has a 2-minute Minimum On, Minimum
Off, and Interstage delay timer.
1. If Y1 is ene rgized, and the room therm ostat calls for Y 2
(2-stage thermostat), the compressor and OFM are energized. The EconoMi$er damper is maintained at its current position.
2. If Y1 is energized for more than 20 minutes, and Y2 is
not energized (whether or not a 2-stage thermostat is
used), the compressor and OFM are energized. The
EconoMi$er damper is maintained at its current position.
3. If Y1 is energized, and the compressor is already energized (see Step 2) and the room thermostat calls for Y2,
the compressor continues to operate.
4. If the compressor is energized and the thermostat is satisfied, the compressor, the OFM, and IFM are deenergized
and the EconoMi$er modulates closed.
When the OAT is below the MECH CLG LOCKOUT set
point, the compressors remain off.
HEATING, UNITS WITH E CON OMI $ER — When the ther-
mostat calls for heating, termina l W1 is energized. To prevent
thermostat short-cycling, the unit is locked into the Heating
mode for at least 1 minute when W1 is energized. The induceddraft motor is energized and the burner ignition sequence begins. The indoor (evaporator) fan motor (IFM) is energized
45 seconds after a flame is ignited and the damper moves to the
minimum position. On units equipped for two stages of heat,
when additional heat is needed, W2 is energized and t he highfire solenoid on the main gas valve (MGV) is energized. When
the thermostat is satisfied and W1 is deenergized, the IFM
stops after a 45-second time-off delay . The economizer damper
then moves to the fully closed position. When using continuous
fan, the damper will remain in the minimum position.
39
Page 40
SERVICE
Fig. 45 — Coil Cleaning
Fig. 46 — Propping Up Condenser Coil
Top Cover
When servicing unit, shut off all electrical power to unit to
avoid shock hazard or injury from rotating parts.
Cleaning —
Inspect unit interior at the beginning of heat-
ing and cooling season and as operating conditions require.
EVAPORATOR COIL
1. Turn unit power of f and t ag disconnect. Remove evaporator coil access panel.
2. If economizer is installed, remove economizer by disconnecting 12-pin Molex plug and removing economizer
mounting screws. Refer to accessory economizer installation instructions or Optional Economizer sections on
pages 13 and 15 for more details.
3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dishwasher
detergent in a pressurized spray canister. Wash both sides
of coil and flush with clean water. For best results, backflush toward return-air section to remove forei gn material. Flush condensate pan after completion.
5. Reinstall economizer and filters.
6. Reconnect wiring.
7. Replace access panels.
CONDENSER COIL — Inspect coil monthly. Clean condenser coil annually, and as required by location and outdoor
air conditions.
One-Row Coil Cleaning (Size 004)
— To access one-row
coils, remove screws securing condenser-fan grille to condenser fan top cover. Place grille on top of condenser fan top cover
as shown in Fig. 45. It is not necessary to remove the top cover.
Use a water hose or other suitable equipment to remove dirt
and debris. Clean the outer surfaces with a stiff brush in the
normal manner.
Reverse the procedure outlined above to reinstall the
condenser-fan grille and condenser fan top cover.
T w o- Row Coi l Cleani ng (Sizes 005- 007 )
NOTE: Save all screws removed in this se ction. The screws
must be used when reinstalling the equipment.
1. To access 2-row coils, rem ove screws securing condenserfan grille to condenser coil top cover. Place grille on top of
condenser fan top cover as shown in Fig. 45 and 46. It i s
not necessary to remove the top cover.
2. Remove 3 screws on right side of compressor access panel. Remove one screw securing condenser coil top cover
to compressor access panel. Remove lower screws securing condenser coil to compressor mounting plate.
3. Remove 4 screws securing cont rol box ac cess panel. Remove three screws (located in front of the control box
access cover) securing condenser coil top cover .
4. Remove screws securing low-volta ge access panel. Remove 2 screws inside low-voltage access panel. Tilt sheet
metal (located on left side of low-voltage connections)
back 45 degrees.
5. Remove screw securing refrigerant service port access
panel.
6. Remove 2 wire ties securing 2-row coils together at hairpin end.
7. Remove screws securing two corner posts. Remove two
corner posts.
8. Use right corner post to prop up right side of condenser
coil top cover. Slide condenser coi l partially out of condenser fan housing. See Fig. 46.
9. Use left corner post to prop up left side of condenser coil
top cover.
10. Carefully separate the outer coil section 3 to 4 in. from the
inner coil section. See Fig. 47.
11. Use a water hose or other suitable equipment to flush
down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner.
12. Secure inner and outer coils together with 2 wire ties.
13. Reposition the outer and inner coil section.
14. Reverse the procedure outlined above to reinstall
equipment.
CONDENSATE DRAIN — Check and clean each year at
start of cooling season. In winter, keep drain dry or protect
against freeze-up.
FILTERS — Clean or replace at start of each heating and cooling season, or more often if operating conditions require it. Replacement filters must be same dimensions as original filters.
OUTDOOR-AIR INLET SCREENS — Clean screens with
steam or hot water and a mild detergent. Do not use disposable
filters in place of screens.
40
Page 41
Fig. 47 — Separating Coil Sections
Fig. 48 — Condenser-Fan Adjustment
Lubrication
COMPRESSORS — Each compressor is charged with the
correct amount of oil at the factory.
FAN-MOTOR BEARINGS — Fan-motor bearings are of
the permanently lubricated type. No further lubrication is required. No lubrication of condenser or evaporator fan motors is
required.
Manual Outdoor-Air Damper —
blade adjustment is required, see Manual Outdoor-Air Damper
section on page 12.
Economizer Adjustment —
mizer sections on pages 13 and 15.
Condenser Fan Adjustment (Fig. 48) —
unit power supply and tag disconnect. Remove condenser-fan
assembly (grille, motor, and fan) and loosen fan hub setscrews.
Adjust fan height as shown in Fig. 48. Tighten setscrews and
replace condenser-fan assembly.
Belt/Pulley Adjustment —
or if conditions warrant to verify belt tension and pulley alignment are correct. Replace belt if necessary.
Refrigerant Charge —
listed on unit nameplate (also refer to Table 1). Refer to Carrier
GTAC2-5 Charging. Recovery, Recycling, and Reclamation
training manual and the following procedures.
Unit panels must be in place when unit is operating during
charging procedure. Unit must operate a minimum of 10 mi nutes before checking or adjusting charge.
Amount of refrigerant charge is
If outdoor-air damp er
Refer to Optional Econo-
Shut off
Inspect once each season,
NO CH ARGE — Use standard evac uating te chniques. After
evacuating system, weigh in the specified amount of refrigerant. (Refer to Table 1.)
LOW-CHARGE COOLING — Using Cooling Charging
Charts, Fig. 49-52, vary refrigerant until the conditions of the
appropriate chart are met. Note the charging charts are different
from type normally used. Charts are based on charging the
units to the correct superheat for the various operating conditions. Accurate pressure gage and temperature sensing device
are required. Connect the pressure gage to the servic e port on
the suction line. Mount the temperature sensing device on the
suction line and insulate it so that outdoor ambient temperature
does not affect the reading. Indoor-air cfm must be within the
normal operating range of the unit.
TO USE COOLING CHARGING CHART — Take the outdoor ambient temperature and read the suction pressure gage.
Refer to chart to determine what suction temperature should
be. If suction temperature is high, add refrigerant. If suction
temperature is low, carefully recover some of the charge.
Recheck the suction pressure as charge is adjusted.
Suction T emperature should be. . . . . . . . . . . . . . . . . . . . . . .68 F
(Suction Temperature may vary 5 F.)
Flue Gas Passageways —
tor box and upper areas of the heat exchanger:
1. Remove the combustion blower wheel and motor assembly according to directions in Combustion-Air Blower
section on page 43.
2. Remove the flue cover to inspect the heat exchanger.
3. Clean all surfaces as required using a wire brush.
To inspect the flue collec-
41
Page 42
Fig. 49 — Cooling Charging Chart, 48TJ004
Fig. 51 — Cooling Charging Chart, 48TJ006
Fig. 50 — Cooling Charging Chart, 48TJ005
Fig. 52 — Cooling Charging Chart, 48TJ007
42
Page 43
Combustion-Air Blower —
INDUCEDDRAFT
MOTOR
MOUNTING
PLATE
INDUCEDDRAFT
MOTOR
MANIFOLD
PRESSURE
TAP
VESTIBULE
PLATE
FLUE
EXHAUST
ROLLOUT
SWITCH
BLOWER
HOUSING
GAS
VALV E
BURNER
SECTION
Fig. 53 — Burner Section Details
Clean periodically to assure proper airflow and heating efficiency. Inspect blower
wheel every fall and periodically during heating season. For the
first heating season, inspect blower wheel bimonthly to determine proper cleaning frequency.
To acc ess burner section, slide the sliding burner partition
out of the unit.
To inspect blower wheel, shine a flashlight into draft hood
opening. If cleaning is required, remove motor and wheel as
follows:
1. Slide burner access panel out.
2. Remove the 7 screws that attach induced-draft motor
housing to vestibule plate (Fig. 53).
3. The blower wheel ca n be cleaned at this point. If additional cleaning is required, continue with Steps 4 and 5.
4. To remove blower from the motor shaft, remove
2 setscrews.
5. To remove motor, remove the 4 screws that hold the
motor to mounting plate. Remove the motor cooling fan
by removing one setscrew. Then remove nuts that hold
motor to mounting plate.
6. To reinstall, reverse the procedure outlined above.
Limit Switch —
Remove blower access panel (Fig. 6).
Limit switch is located on the fan deck.
Burner Ignition —
Unit is equipped with a direct spark
ignition 100% lockout system. Integrated Gas Unit Controller
(IGC) is located in the control box (Fig. 10). The IGC contains
a self-diagnostic LED (light-emitting diode). A single LED on
the IGC provides a visual display of operational or sequential
problems when the power supply is uninterrupted. When a
break in power occurs, the IGC will be reset (resulting in a loss
of fault history) and the indoor (evaporator) fan ON/OFF times
will be reset. The LED error code can be observed through
the viewport. During servicing refer to the label on the control
box cover or Table 31 for an expl anation of LED error code
descriptions.
If lockout occurs, unit may be reset by interrupting power
supply to unit for at least 5 seconds.
Main Burners —
To access burners, remove burner access panel and slide out burner partition. See Fig. 9. At the
beginning of each heating season, inspect for deterioration or
blockage due to corrosion or other causes. Observe the main
burner flames and adjust, if necessary.
When working on gas train, do not hit or plug orifice
spuds.
REMOVAL AND REPLACEMENT OF GAS TRAIN
(Fig. 53-55)
1. Shut off manual gas valve.
2. Shut off power to unit.
3. Slide out burner partition. See Fig. 9.
4. Disconnect gas piping at unit gas valve.
5. Remove wires connected to gas valve. Mark each wire.
6. Remove ignitor wires and sensor wires at the Integrated
Gas Unit Controller (IGC) (see Fig. 10).
7. Remove the 2 screws that attach the burner rack to th e
vestibule plate (Fig. 53).
8. Slide the burner tray out of the unit (Fig. 54).
9. To reinstall, reverse the procedure outlined above.
CLEANING AND ADJUSTMENT
1. Remove burner rack from unit as described in Removal
and Replacement of Gas Train section, above.
2. Inspect burners; if dirty, remove burners from rack.
3. Using a soft brush, clean burners and cross-over port as
required.
4. Adjust spark gap. See Fig. 55.
5. Reinstall burners on rack.
6. Reinstall burner rack as described in Removal and
Replacement of Gas Train section, this page.
Replacement Parts —
A complete list of replacement
parts may be obtained from any Carrier distributor upon
request.
Loss of power to control module (IGC). Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and transformer. Units
High limit switch opens during heat
exchanger warm-up period before fanon delay expires.
Limit switch opens within three minutes
after blower-off delay timing in Heating
mode.
High temperature limit switch is open. Check the operation of the indoor (evaporator) fan motor.
The IGC sensed flame that should not
be present.
Inadequate airflow to unit.Check operation of indoor (evaporator) fan motor and that supply-air temperature rise
Unit unsuccessfully attempted ignition
for 15 minutes.
IGC does not sense that induced-draft
motor is operating.
Rollout switch has opened.Rollout switch will automatically reset, but IGC will continue to lock out unit. Check gas
Microprocessor has sensed an error in
the software or hardware.
without a 24-v circuit breaker have an internal overload in the 24-v transformer. If the
overload trips, allow 10 minutes for automatic reset.
Ensure unit is fired on rate and temperature rise is correct.
Ensure units’ external static pressure is within application guidelines.
Ensure that the supply-air temperature rise is in accordance with
the range on the unit nameplate.
Reset unit. If problem persists, replace control board.
agrees with range on unit nameplate information.
Check ignitor and flame sensor electrode spacing, gaps, etc. Ensure that flame sense
and ignition wires are properly terminated. Verify that unit is obtaining proper amount
of gas.
Check for proper voltage. If motor is operating, check the speed sensor plug/IGC Terminal J2 connection. Proper connection: PIN 1— White, PIN 2 — Red, PIN 3 — Black.
valve operation. Ensure that induced-draft blower wheel is properly secured to motor
shaft. Reset unit at unit disconnect.
If error code is not cleared by resetting unit power, replace the IGC.
If the IGC must be replaced, be sure to ground yourself to dissipate any electrical charge that may be present before handling
new control board. The IGC is sensitive to static electricity and
may be damaged if the necessary precautions are not taken.
Table 33 — Heating Service Analysis
PROBLEMCAUSEREMEDY
Burners will not
ignite.
Inadequate heating.
Poo r f lame
characteristics.
Burners will not
turn off.
Misaligned spark electrodes.Check flame ignition and sensor electrode positioning.
No gas at main burners.Check gas line for air purge as necessary. After purging
Water in gas line.Drain water and install drip leg to trap water.
No power to furnace.Check power supply, fuses, wiring, and circuit breaker.
No 24 v power supply to control circuit.Check transformer. Transformers with internal overcur-
Miswired or loose connections.Check all wiring and wirenut connections.
Burned-out heat anticipator in thermostat.Replace thermostat.
Broken thermostat wires.Run continuity check. Replace wires, if necessary.
Dirty air filter.Clean or replace filter as necessary.
Gas input to unit too low.Check gas pressure at manifold. Clock gas meter for input. If too
Unit undersized for application.Replace with proper unit or add additional unit.
Restricted airflow.Clean filter, replace filter, or remove any restrictions.
Blower speed too low.Use high speed tap, increase fan speed, or install
Limit switch cycles main burners.Check rotation of blower, thermostat heat anticipator settings,
Too much outdoor air.Adjust minimum position.
Incomplete combustion (lack of Check all screws around flue outlets and burner
combustion air) results in:compartment. Tighten as necessary.
Unit is locked into Heating mode for aWait until mandatory one minute time period has
one minute minimum.elapsed or reset power to unit.
IMPORTANT: Refer to Table 33 — Heating Service Analysis
for additional troubleshooting analysis.
LEGEND
IGC —
LED —
Integrated Gas Unit Controller
Light-Emitting Diode
Adjust as needed.
gas line of air, allow gas to dissipate for at least 5 minutes
before attempting to relight unit.
Check gas valve.
rent protection require a cool down period before resetting.
low, increase manifold pressure, or replace with correct orifices.
optional blower, as suitable for individual units.
and temperature rise of unit. Adjust as needed.
Check economizer operation.
Overfired unit — reduce input, change orifices, or adjust
gas line or manifold pressure.
Check vent for restriction. Clean as necessary.
Check orifice to burner alignment.
45
Page 46
PROBLEMCAUSEREMEDY
Compressor and condenser fan
will not start.
Compressor will not start
but condenser fan runs.
Compressor cycles (other than
normally satisfying thermostat).
Compressor operates continuously.
Excessive head pressure.
Head pressure too low.
Excessive suction pressure.
Suction pressure too low.
Evaporator fan will not shut off.
Compressor makes excessive
noise (48TJ007 scroll only).
Table 34 — Cooling Service Analysis
Power failure.Call power company.
Fuse blown or circuit breaker tripped.Replace fuse or reset circuit breaker.
Defective thermostat, contactor, transformer,
or control relay.
Insufficient line voltage.Determine cause and correct.
Incorrect or faulty wiring.Check wiring diagram and rewire correctly.
Thermostat setting too high.Lower thermostat setting below room temperature.
Faulty wiring or loose connections in com-
pressor circuit.
Compressor motor burned out, seized, or
internal overload open.
Defective run/start capacitor, overload, or
start relay.
One leg of three-phase power dead.Replace fuse or reset circuit breaker. Determine
Refrigerant overcharge or undercharge.Recover refrigerant, evacuate system, and
Defective compressor.Replace and determine cause.
Insufficient line voltage.Determine cause and correct.
Blocked condenser.Determine cause and correct.
Defective run/start capacitor, overload, or
start relay.
Defective thermostat.Replace thermostat.
Faulty condenser-fan motor or capacitor.Replace.
Restriction in refrigerant system.Locate restriction and remove.
Dirty air filter.Replace filter.
Unit undersized for load.Decrease load or increase unit size.
Thermostat set too low.Reset thermostat.
Low refrigerant charge.Locate leak; repair, and recharge.
Leaking valves in compressor.Replace compressor.
Air in system.Recover refrigerant, evacuate system, and
Condenser coil dirty or restricted.Clean coil or remove restriction.
Dirty air filter.Replace filter.
Dirty condenser coil.Clean coil.
Refrigerant overcharged.Remove excess refrigerant.
Air in system.Recover refrigerant, evacuate system, and
Condenser air restricted or air short-cycling.Determine cause and correct.
Low refrigerant charge.Check for leaks; repair, and recharge.
Compressor valves leaking.Replace compressor.
Restriction in liquid tube.Remove restriction.
High heat load.Check for source and eliminate.
Compressor valves leaking.Replace compressor.
Refrigerant overcharged.Recover excess refrigerant.
Dirty air filter.Replace filter.
Low refrigerant charge.Check for leaks; repair, and recharge.
Metering device or low side restricted.Remove source of restriction.
Insufficient evaporator airflow.Increase air quantity. Check filter and replace if
Temperature too low in conditioned area.Reset thermostat.
Outdoor ambient below 25 F.Install low-ambient kit.
Time off delay not finished.Wait for 30-second off delay.
Compressor rotating in wrong direction.Reverse the 3-phase power leads as described in
Replace component.
Check wiring and repair or replace.
Determine cause. Replace compressor.
Determine cause and replace.
cause.
recharge to nameplate.
Determine cause and replace.
recharge.
recharge.
necessary.
the Start-Up section on page 37.
46
Page 47
Table 35 — Durablade Economizer Troubleshooting
PROBLEMCAUSEREMEDY
Damper does not
open.
Economizer
operation
limited to minimum
position.
Damper does not
close.
Economizer damper
does not close on
power loss.
C1 —
EC —
IFC —
IFO —
Common Power
Enthalpy Control
Indoor (Evaporator) Fan Contactor
Indoor (Evaporator) Fan On
Indoor (evaporator) fan is off.1. Check to ensure that 24 vac is present at terminal C1 on the IFC or
No power to economizer motor.1. Check that SW3 is properly making contact with the damper
Economizer motor failure.If the indoor (evaporator) fan and economizer motor are energized,
OAT or EC set too high.1. Set at correct temperature (3 F below indoor space temperature).
Verify economizer control board is correctly
wired and works properly.
Check SAT.1. After verifying that the OAT and EC settings and the economizer
Incorrect wiring of economizer.1. Verify that SW2 and SW4 are wired and working properly (see unit
Verify economizer control board is functioning
properly.
Check SAT.1. After verifying that the wiring is correct and the economizer control
Economizer motor failure.If economizer control board and SAT are functioning properly, verify
Verify that close-on-power-loss and economizer
control board are functioning properly.
OAT —
PL—
SAT —
SW—
Outdoor-Air Thermostat
Plug
Supply-Air Thermostat
Economizer Position Switch
that 24 vac is present at the IFO terminal. Check whether 24 vac is
present at PL6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is
not present, check wiring (see unit label diagram).
2. Check proper thermostat connection to G on the connection board.
blade. Check that SW1 is in the NC (normally closed) position.
2. Check diode D18. If diode is not functioning properly, replace control
board.
3. Confirm that the economizer control board is grounded properly at
PL6-4 (brown wire) and at brown terminal of the economizer control
board (brown wire). The economizer motor must also be grounded
properly at the negative motor terminal (brown wire).
4. Verify SW1 and SW3 are working and wired properly (see unit label
diagram).
5. Check for 24 vac input at both PL6-1 (red wire) and PL6-3 (black
wire). If 24 vac not present, check unit wiring (see unit label
diagram). If 24 vac is found in both places, check for 24 vac at the
yellow terminal of the economizer control board (yellow wire). If
24 vac power is not present, replace the economizer control board.
verify that there is a minimum of 18 vdc at the positive motor
terminal. If the motor is not operating, replace the motor.
2. Check OAT or EC by setting above outdoor temperature or humidity
level. If the OAT or EC switches do not close, replace OAT or EC.
1. Perform the following tests when OAT or EC is closed, Y1 is called
for and damper is at minimum position. Confirm 24 vac on gray
terminal of the economizer control board (gray wire). If 24 vac is
not present, check wiring (see unit label diagram).
2. Verify that SW1 and SW3 are wired correctly and working properly
(see unit label diagram).
3. Check to ensure that 24 vac exists at PL6-2 (blue wire). If 24 vac is
not present, check wiring (see unit wiring label diagram).
4. Check 24 vac output at PL6-10 (white wire). If 24 vac is not
present, replace economizer control board.
control board wiring are correct, check to ensure that the 24 vac
terminal of the SAT has 24 vac (white wire). If OAT, EC, and control
board are functioning and wired properly and no 24 vac exists,
check wiring (see unit label diagram).
2. If supply-air temperature is greater than 57 F, 24 vac should be
found at terminal T2 on the SAT (pink wire). If 24 vac is not present,
replace SAT.
label diagram).
2. Check diode D19. If diode is not functioning properly, replace control
board.
1. After verifying that the wiring is correct, modulate the damper to the
minimum position. Remove the calls for G.
2. If the damper does not move, check for 24 vac at PL6-1 (red wire).
If 24 vac is not present, check wiring (see unit label diagram).
3. If damper still does not move, check for 24 vac at blue terminal of
economizer control board (blue wire). If 24 vac is not present, replace the economizer circuit board.
board is functioning properly, place the OAT or EC switch in the
closed position. Place a call for Y1 and open the damper to the fully
open position. Confirm that the 24 vac terminal of the SAT has
24 vac (white wire). If 24 vac is not present, check wiring (see unit
label diagram).
2. If supply-air temperature is less than 52 F, 24 vac should be found
at terminal T1 on the SAT (violet wire). If 24 vac not found, replace
SAT.
that there is a minimum of 18 vdc at the positive motor terminal. If a
minimum if 18 vdc is present and the motor is still not operating, replace the motor.
1. Check voltage potential across batteries. If lower than 14 vdc,
replace close-on-power-loss power supply (9-v alkaline batteries). It
is recommended that you check this emergency power supply on a
regular basis or whenever the filters are changed.
2. If the close-on-power-loss and economizer control board are
functioning properly, check for 14 vdc or higher at the blue terminal
of the economizer control board (blue wire) when power is discon-
nected from unit. If 14 vdc is not present, replace the control board.
47
Page 48
PROBLEMPOTENTIAL CAUSEREMEDY
Damper Does Not
Open
EconoMi$er
Operation Limited to
Minimum Position
Damper Position
Less than Minimum
Positi on Set Point
Damper Does Not
Return to Minimum
Positi on
Damper Does Not
Close on Power Loss
LEGEND
Plug
PL —
Table 36 — EconoMi$er Troubleshooting
Indoor (Evaporator) Fan is OffCheck to ensure that 24 vac is present at Terminal C1 (Common Power)
No Power to EconoMi$er ControllerCheck to ensure that 24 vac is present across Terminals 24 VAC and
No Power to G TerminalIf IFM is on, check to ensure 24 vac is present on G Terminal of the
Controller FaultIf STATUS light is flashing one flash, the EconoMi$er controller is
Thermostat FaultIf STATUS light is flashing two flashes, the EconoMi$er controller senses
Actuator FaultCheck the wiring between the EconoMi$er controller and the actuator.
Minimum Position Set IncorrectlyVerify that the MIN POS (%) is set greater than zero. Adjust MIN POS (%)
EconoMi$er Changeover Set Point Set Too
High or Too Low
Supply Air Temperature Sensor FaultyIf STATUS light is flashing 4 flashes, Supply Air Temperature Sensor is
Outdoor Air Temperature Sensor FaultyIf STATUS light is flashing 5 flashes, Outdoor Air Temperature Sensor is
Supply Air Low Limit Strategy ControllingThe supply-air temperature is less than 45 F, causing the minimum
CO
Ventilation Strategy ControllingIf a CO2 sensor is being used, and the damper position is greater than
2
Damper Travel is RestrictedCheck to ensure the damper is not blocked.
on the IFC (Indoor [Evaporator] Fan Contactor) or that 24 vac is present at
the IFO (Indoor [Evaporator] Fan On) terminal. Check whether 24 vac is
present at PL6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is
not present, check wiring (see unit label diagram).
Check proper thermostat connection to G on the connection board.
24V COM on the EconoMi$er control. If 24 vac is not present, check wiring
(see unit label diagram). If 24 vac is present, STATUS light should be on
constantly.
EconoMi$er controller. If 24 vac is not present, check wiring (see unit
label diagram).
experiencing a fault condition. Cycle power to the controller. If condition
continues, replace the EconoMi$er controller.
the thermostat is wired incorrectly. Check wiring between the thermostat
and the connection board in the electrical panel. The fault condition is
caused by Y2 being energized before Y1.
actuator’s operation. (This process takes 3 minutes to complete.)
to 100% to verify operation, and then set to correct setting.
Set at correct value. See Table 3.
faulty. Check wiring or replace sensor.
faulty. Check wiring or replace sensor.
position to decrease. Refer to the Star t-Up instructions. Verify correct
setting of MIN POS (%). If correct, EconoMi$er is operating correctly.
minimum position, the ventilation control strategy is controlling. Refer to
the Start-Up instructions. EconoMi$er is operating correctly.
48
Page 49
Fig. 56 — Typical Wiring Diagram and Component Arrangement
49
Page 50
LEGEND FOR FIG. 56 — TYPICAL WIRING SCHEMATIC AND COMPONENT ARRANGEMENT
IMPORTANT: Refer to unit wiring label for actual unit wiring information.
Adjustable Heat Anticipator
Burner Relay
Contactor, Compressor
Capacitor
Cooling Compensator
Compressor Motor
Combustion Relay
Economizer
Equipment
Freeze-Up Protection Thermostat
Ground
Gas Valve Relay
High-Pressure Switch
Hall-Effect Sensor
High Voltage
Ignitor
Induced-Draft Motor
Indoor (Evaporator) Fan Motor
Integrated Gas Unit Controller
Light-Emitting Diode
Low-Pressure/Loss-of-Charge Switch
Limit Switch
Main Gas Valve
Motor
Outdoor (Condenser) Fan Motor
Plug Assembly
Quadruple Terminal
Relay
Rollout Switch
Supply Air Thermostat
Sensor
Switch Fully Open
Switch Fully Closed
Switch Min. Vent Position
Switch Max. Vent Position
Thermostat-Cooling
Thermostat-Heating
Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential only.
Not to represent wiring.
NOTES:
1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single-phasing conditions.
3. Thermostat: HH07AT170, 172, 174 and P272-2783
Subbase: HH93AZ176, 178 and P272-1882, 1883
4. Set heat anticipator at .14 amp. For units with 2 stages of heating, set stage two anticipator at .14 amp.
5. Use copper conductors only.
6. TRAN is wired for 230-v unit. If unit is to be run with 208-v power supply, disconnect BLK wire from 230-v tap
and connect to 208-v tap.
Copyright 2000 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Ta b 1 a 6 a
PC 111Catalog No. 534-774Printed in U.S.A.Form 48TJ-18SIPg 5010-00Replaces: 48TJ-16SI
Page 51
Page 52
START-UP CHECKLIST
(Remove and Store in Job File)
I. PRELIMINARY INFORMATION:
MODEL NO.:________________________________SERIAL NO.: ___________________________________
DATE:______________________________________TECHNICIAN: __________________________________
BUILDING LOCATION:_______________________DATE STARTED: ________________________________
II. PRE-START-UP (insert checkmark in box as each item is completed)
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
VERIFY ELECTRICAL WIRING DOES NOT CONT ACT REFRIGERANT TUBING
CHECK GAS PIPING FO R LEAKS
CHECK THAT INDOOR-AIR FILTER IS CLEAN AND IN PLACE
VERIFY THA T UNIT INSTALLATION IS LEVEL
CHECK F AN WHEEL AND PR OPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS
CHECK BEL T TENSION AND PULLEY ALIGNMENT
III. START-UP:
ELECTRICAL
SUPPL Y VOLTAGEL1-L2L2-L3L3-L1
COMPRESSOR AMPSL1L2L3
INDOOR-FAN AMPSL1L2L3
GAS INLET PRESSU REIN. WG
GAS MANIFOLD PRESSUREIN. WG (HI FIRE)
GAS HEAT SUPPLY AIRDB
REFRIGERANT SUCTIONPSIGF (AT SUCTION SERVICE VALVE)
REFRIGERANT DISCHARGEPSIG F (AT CONDENSER LIQUID LINE OUTLET)
VERIFY REFRIGERANT CHARGE USING CHARGING T ABLES
VERIFY THAT 3-PHASE SCROLL COMPRESSOR ROTATING IN CORRECT DIRECTION (48TJ007 ONLY)
CUT ALONG DOTTED LINECUT ALONG DOTTED LINE
Copyright 2000 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Ta b1 a 6 a
PC 111Catalog No. 534-774Printed in U.S.A.Form 48TJ-18SIPg CL-110-00Replaces: 48TJ-16SI