Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precautions in the li terature, ta gs and label s attached t o the uni t, and
other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
Disconnect gas piping from unit when leak testing at pressure greater than 3.4 kPa (1/2 psig).
1
2
Before performing service or maintenance operations on
unit, turn off main power swit ch to unit. Electrical shock
could cause personal injury.
Unit is shipped in the vertical discharge configuration. To
convert to horizontal configuration, remove screws from side
duct opening covers and remove covers. Using the same
screws, install covers on vertical duct openings with the insulation side down. Seals around duct openings must be tight. See
Fig. 1.
Step 1 — Provide Unit Support
ROO F CU R B — Assemble and instal l acces sory roof curb in
accordance with instructions shipped with curb. See Fig. 2. Install insulation, cant strips, roofing felt, and counter flashing as
shown. Ductwork must be attached to curb. If gas, electric
power or control power is to be routed through the curb, attach
the accessory thru-the-curb service connection plates to the
roof curb in accordance with the accessory installation instructions. Connection plates must be installed before unit is set in
roof curb.
IMPORTANT: The gasketing of th e unit to the roof curb
is critical for a watertight seal. Install gasket supplied
with the roof curb as shown in Fig. 2. Improperly
applied gasket can also result in air leaks and poor unit
performance.
Curb should be level. Unit leveling tolerances a re shown in
Fig. 3. This is necessary for unit drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
Pressures greater than 3.4 kPa (1/2 psig) will
cause gas valve damage resulting in hazardous
condition. If gas valve is ever subjected to pressure greater than 3.4 kPa (
replaced before use. When pressure testing
field-supplied gas piping at pressures of 3.4 kPa
1
(
/2 psig) or less, a unit connected to such piping
must be isolated by manually closing the gas
valve(s).
1
/
psig), it must be
2
INSTALLATION
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Ta b 1 a 6 a
Catalog No. 004-816Printed in U.S.A.Form 48TF-C1SIPg 11-01Replaces: New
Page 2
SLAB MOUNT (Horizontal Units Only) — Provide a level
concrete slab that extends a minimum of 152 mm (6 in.)
beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
Step 2 — Field Fabricate Ductwork —
ducts to roof curb and building structure on vertical units. Do
not connect ductwork to unit. For horizontal applications, field-
supplied flanges should be attached to horizontal discharge
openings and all ductwork secured to the flanges. Insulate and
weatherproof all external ductwork, joints, and roof openings
with counter flashing and mastic in accordance with applicable
codes.
Ducts passing through an unconditioned space must be in-
sulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork.
Cabinet return-air static shall not exceed –87 Pa (–.35 in. wg)
with Durablade economizer, –26 Pa (–.30 in. wg) with
EconoMi$er or –112 Pa (–.45 in. wg) without economizer.
These units are designed for a minimum heati ng operation
continuous return-air temperature of 10 C (50 F) (dry bulb), or
an intermittent operation down to 7 C (45 F) (dry bulb), such as
when used with a night set-back thermostat.
Secure all
Step 3 — Install External Trap for Condensate
Drain —
nections are located at the bottom and side of the unit. Unit discharge connections do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications.
When using the standard side drain connection, make sure
the plug (Red) in the alternate bottom connection is tight before
installing the unit.
The unit’s 19-mm (3/4-in.) condensate drain con-
To use the bottom drai n connection for a roof curb installation, relocate the factory-installed plug (Red) from the bottom
connection to the side connection. See Fig. 4. The piping for
the condensate drain and external trap can be completed after
the unit is in place.
All units must have an external trap for condensate drainage. Install a trap at least 102-mm (4-in.) deep and protect
against freeze-up. If drain line is installed downstream from the
external trap, pitch the line away from the unit at 25 mm (1 in.)
per 3 m (10 ft) of run. Do not use a pipe size smaller than the
19-mm (
Step 4 — Rig and Place Unit —
transportation damage. File any claim with transportation
agency. Keep unit upright and do not drop. Spreader bars are
not required if top crating is left on unit. Rollers may be used to
move unit across a roof. Level by using unit frame as a reference. See Tables 1A and 1B and Fig. 5 for additional information. Operating weight is shown in Tables 1A and 1B and
Fig. 5.
and 6. Refer to rigging instructions on unit.
POS ITION ING — Maintain cl earan ce around and a bove unit
to provide minimum distance from combustible materials,
proper airflow, and service access. See Fig. 6.
air inlets near exhaust vents or other sources of contami nated
air.
combustion intake or flue outlet.
A, B, or C roof-covering material when roof curb is used.
3
/4-in.) unit connection.
Inspect unit for
Lifting holes are provided in base rails as shown in Fig. 5
All panels must be in place when rigging.
Do not install unit in an indoor location. Do not locate unit
Be sure that unit is installed so that snow will not block the
Unit may be installed directly on wood flooring or on Class
5. Attach ductwork to curb (flanges of duct rest on
6. Service clearance 4 ft [1219] on each side.
foam, 1
curb).
3
/4 lb density.
UNIT SIZE
48TF
008-014
7.Direction of airflow.
8. Connector packages CRBTMPWR001A00 and
2A00 are for thru-the-curb gas type. Packages
CRBTMPWR003A00 and 4A00 are for thruthe-bottom type gas connections.
Fig. 2 — Roof Curb Details
3
Page 4
Although unit is weatherproof, guard against water from
DRAIN PLUG
MAXIMUM ALLOWABLE
DIFFERENCE mm (in.)
A-BB-CA-C
13 (0.5)25 (1.0)25 (1.0)
Fig. 3 — Unit Leveling Tolerances
NOTE: Drain plug is shown in factory-installed position.
Fig. 4 — Condensate Drain Pan
higher level runoff and overhangs.
Position unit on roof curb so that the following clearances
are maintaine d: 7 mm (
base rails on each side and duct end of unit; 84 mm (3
1
/4-in.) clearance between roof curb and
5
/16-in.)
clearance between roof curb and condenser c oil end of unit.
(See Fig. 2, section C-C.)
Locate mechanical draft system flue assembly at least
1219 mm (48 in.) from any opening through which combustion
products could enter the building, and at least 1219 mm (48 in.)
from an adjacent building or combustible material. When unit
is located adjacent to public walkways, flue assembly must be
at least 2.13 m (7 ft) above grade.
Flue vent discharge must have a minimum horizontal clearance of 1219 mm (48 in.) from electric and gas meters, gas regulators, and gas relief equipment.
Flue gas can deteriorate building materials. Orient unit so
that flue gas will not affect building materials.
Adequate combustion-air space must be provided for proper
operation of this equipment. Be sure that installation complies
with all local codes and Section 5.3, Air for Combustion and
Ventilation, NFGC (National Fuel Gas Code), ANSI (American National Standards Institute), latest revision, U.S.A.
Standards.
(Copy continued on page 8.)
NOTES:
1. Dimension in ( ) is in millimeters.
2. Hook rigging shackles through holes in base rail as shown in
detail ‘‘A.’’ Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.
3. Weights include base unit without economizer. See Tables 1A
and 1B for economizer weights.
Rows...Fins/m3...5903...5904...590
Total Face Area (sq m)0.740.931.03
EVAPORATOR FANCentrifugal Type
Quantity...Size (mm x mm)1...381 x 3811...381 x 3811...381 x 381
Type DriveBeltBeltBelt
Nominal L/s123017001980
Motor kW1.121.502.24
Maximum Continuous BkW1.791.792.76
Motor Frame Size565656
Fan r/s Range8.2-11.79.5-13.012.0-15.0
Motor Bearing TypeBallBallBall
Maximum Allowable r/s26.726.726.7
Motor Pulley Pitch Diameter Min/Max (mm) 61/8671/97102/127
Nominal Motor Shaft Diameter (mm)161622
Fan Pulley Pitch Diameter (mm)178178203
Nominal Fan Shaft Diameter (mm)252525
Belt, Quantity...Type...Length (mm)1...A...12451...A...12451...A...1346
Pulley Center Line Distance (mm)425-489403-445403-445
Speed Change per Full Turn of
Movable Pulley Flange (r/s)
Movable Pulley Maximum Full Turns
From Closed Position
Factory Settin g555
Factory Speed Setting (r/s) 8.29.512.0
Fan Shaft Diameter at Pulley (mm)252525
Rows...Fins/in.3...153...154...15
Total Face Area (sq ft)8.010.011.1
EVAPORATOR FANCentrifugal Type
Quantity...Size (in.)1...15 x 151...15 x 151...15 x 15
Type DriveBeltBeltBelt
Nominal Cfm260035004200
Motor Hp1
Maximum Continuous Bhp2.402.403.70
Motor Frame Size565656
Fan Rpm Range492-700571-779717-900
Motor Bearing TypeBallBallBall
Maximum Allowable Rpm160016001600
Motor Pulley Pitch Diameter Min/Max (in.) 2.4/3.42.8/3.84.0/5.0
Nominal Motor Shaft Diameter (in.)
Fan Pulley Pitch Diameter (in.)7.07.08.0
Nominal Fan Shaft Diameter (in.)———
Belt, Quantity...Type...Length (in.)1...A...491...A...491...A...53
Pulley Center Line Distance (in.)16.75-19.2515.85-17.5015.85-17.50
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full Turns
From Closed Position
Factory Settin g555
Factory Speed Setting (rpm) 492571717
Fan Shaft Diameter at Pulley (in.)111
4. On vertical discharge units, ductwork to be attached to
accessory roof curb only. For horizontal discharge units,
field-supplied flanges should be attached to horizontal discharge openings, and all ductwork should be attached to
the flanges.
5. Minimum clearance (local codes or jurisdiction may prevail):
a. Between unit, flue side and combustible surfaces,
36 in. [914].
b. Bottom of unit to combustible surfaces (when not using
curb), 1 in. [25]. Bottom of base rail to combustible surfaces (when not using curb) 0 inches.
c. Condenser coil, for proper airflow, 36 in. [914] one side,
12 in. [304] the other. The side getting the greater clearance is optional.
d. Overhead, 60 in. [1624] to assure proper condenser fan
operation.
e. Between units, control box side, 42 in. [1067] per NEC
(National Electrical Code).
f. Between unit and ungrounded surfaces, control box
side, 36 in. [914] per NEC.
g. Between unit and block or concrete walls and other
grounded surfaces, control box side, 42 in. [1067] per
NEC.
h. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser coil
and combustion side as stated in notes 5a, b and c, a
removable fence or barricade requires no clearance.
7. Units may be installed on combustible floors made from
wood or Class A, B, or C roof covering material if set on
base rail.
8. The vertical center of gravity is 1′-7″ [483] for 008, 1′-11
[584] for 012 and 014 up from the bottom of the base rail.
CORNER
WEIGHT (A)
″
CORNER
WEIGHT (B)
3
″″″″
A
1
/
8
1
″″″″
B
2
/
2
3
″″″″
C
1
/
4
7
″″″″
D
/
Dia [22] Field Control Wiring Hole
8
3
″
″
E
/
[19] - 14 NPT Condensate Drain
″ ″
4
1
″″″″
[13] - 14 NPT Gas Connection 48TFD008
/
2
3
″
″
F
/
[19] - 14 NPT Gas Connection 48TFE,F008
″ ″
4
48TFD,E012 & 014, 48TJF012
″″″″
G
2
Dia [51] Power Supply Knockout
CORNER
WEIGHT (C)
WEIGHT (D)
CONNECTION SIZES
Dia [35] Field Power Supply Hole
Dia [64] Power Supply Knockout
Dia [44] Charging Port Hole
CORNER
“H”“J”“K”“L”
BOTTOM POWER CHART, THESE HOLES
REQUIRED FOR USE WITH ACCESSORY
PACKAGES — CRBTMPWR002A00 (POWER
AND CONTROL) AND CRBTMPWR004A00
(POWER, CONTROL, AND GAS)
THREADED
CONDUIT
SIZE
1
″
″
/
[12.7]
″ ″
2
1
″
″
1
/
[31.7]
″ ″
4
3/
″
″
[19] FPT
″ ″
4
WIRE
USE
24 V
Powe r1
Gas1
REQURED
HOLE SIZES
(MAX.)
7
″″″″
[22.2]
/
8
3
″″″″
/
[44.4]
4
5
″″″″
[41.3]
/
8
Fig. 6 — Base Unit Dimensions
7
Page 8
Step 5 — Install Flue Hood —
BASE UNIT
BASE RAIL
FROM GAS METER
ROOF CURB
DRIP LEG PER NFGC*
FIELD-FABRICATED
SUPPORT*
1219 mm (48") MINIMUM
228 mm (9") MINIMUM CLEARANCE
FOR PANELREMOVAL
MANUAL GAS
SHUTOFF VALVE*
GAS
REGULATOR*
X
Fig. 8 — Gas Piping Guide (With Accessory
Thru-the-Curb Service Connections)
SPACING OF SUPPORTS
STEEL PIPE NOMINAL DIAMETER
mm (in.)
X
DIMENSION
m (ft)
13 (
1
/2)
19 or 25 (
3
/
4
or 1)
32 or larger (11/4 or larger)
1.8 (6)
2.4 (8)
3.0 (10)
LEGEND
*Field supplied.
NOTE: Follow all local codes.
NFGC —
National Fuel Gas Code (U.S.A. Standard)
Fig. 7 — Flue Hood Details
Flue hood is shipped
screwed to the burner compartment access panel. Remove
from shipping location and, using screws provided, install flue
hood and screen in location shown in Fig. 7.
Step 6 — Install Gas Piping —
Unit is equipped for
use with type of gas shown on nameplate. Refer to local
building codes.
For natural gas applications, gas pressure at unit gas connection must not be less than 13.5 kPa (4.0 in. wg) (17.0 kPa
[5.0 in. wg] in high heat units) or greater than 44.0 kPa
(13.0 in. wg) while unit is operating. For liquid propane applications, the gas pressure must not be less than 17.0 kPa (5.0 in. wg)
or greater than 44.0 kPa (13.0 in. wg) at the unit connection.
Size gas supply piping for 1.7 kPa (0.5 in. wg) maximum
pressure drop. Do not use supply pipe smaller than unit gas
connection.
NOTE: When installing gas piping to gas valve inlet, use properly sized back-up wrench on inlet flange flats.
Support gas piping as shown in the table in Fig. 8. For example, a 19 mm (
3
/4-in.) gas pipe must have one field-
fabricated support beam every 2.4 m (8 ft).
See Fig. 8 for typical pipe guide and locations of external
manual gas shutoff valve.
Step 7 — Make Electrical Connections
Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if
an electrical fault should occur. This ground may consist of
electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when
installed in accordance with NEC (National Electrical
Code), ANSI/NFPA (National Fire Protection Association), latest edition (U.S.A. Standards), and local electrical
codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in the installer being
liable for personal injury of others.
FIELD POWER SUPPLY — All units are factory wired for
the voltage shown on the nameplate.
Refer to unit label diagram for additional informat ion. Pigtails are provided for field service.
When installing units, provide a disconnect per local codes.
Use copper conductors only when splice connectors are used.
All field wiring must comply with local requirements.
Install conduit through side panel openings indicated in
Fig. 6. Route power lines through connector to terminal connections as shown in Fig. 9.
Voltages between phases must be balanced within 2% and
the current within 10%. Use the formula shown in Table 2,
Note 2 to determine the percentage of voltage imbalance. Operation on improper line voltage or excessive phase imbalance
constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier
warranty.
NOTE: If field-installed thru-the-bottom connections are used,
refer to the accessory installation instructions for power wiring.
Refer to Fig. 6 for drilling holes in basepan.
FIELD CONTROL WIRIN G — Install a Carrier-approved
accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat
assembly on a solid wall in the conditioned space to sense average temperature in accordance with thermostat installation
instructions.
NOTE: For wire runs up to 15 m (50 ft), use no. 18 AWG
(American Wire Gage) insulated wire (35 C minimum). For 15
to 23 m (51 to 75 ft), use no. 16 AWG insulated wire (35 C
minimum). For over 23 m (75 ft), use no. 14 AWG insulated
wire (35 C minimum). All wire larger than no. 18 AWG cannot
be directly connected to the thermostat and will require a junction box and splice at the thermostat. Refer to Table 3 for wire
conversions.
1. In compliance with NEC requirements (U.S.A. Standard) for
multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit
shall be fuse or HACR breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
the percent of voltage imbalance.
% Voltage Imbalance
= 100 x
NOMINAL
VO LTAG E
(50 Hz)
400
(3 phase)
400
(3 phase)
400
(3 phase)
Full Load Amps
Heating, Air Conditioning and Refrigeration
Indoor (Evaporator) Fan Motor
Locked Rotor Amps
Minimum Circuit Amps
Maximum Overcurrent Protection
National Electrical Code (U.S.A.)
Outdoor (Condenser) Fan Motor
Rated Load Amps
max voltage deviation from average voltage
VOLTAGE
RANGE
MinMaxRLALRAFLAFLAMCAMOCP*FLALRA
3604406.442.00.32.617.62018108
3604408.952.00.32.623.23024128
36044010.473.00.75.429.43531192
Use the following formula to determine
average voltage
COMPR
(ea)
OFM
(ea)
IFMPOWER SUPPLY
Example: Supply voltage is 400-3-50.
AB = 393 v
BC = 403 v
AC = 396 v
Average Voltage =
=
= 397
Determine maximum deviation from average voltage.
(AB) 397 – 393 = 4 v
(BC) 403 – 397 = 6 v
(AC) 397 – 396 = 1 v
Maximum deviation is 6 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
= 1.5%
6
397
MINIMUM UNIT
DISCONNECT
393 + 403 + 396
3
1192
3
Route thermostat cable or equivalent single leads of colored
wire from thermostat subbase terminals to low-voltage connections on unit (shown in Fig. 10) as described in Steps 1-4
below.
1. If unit is mounted on roof curb and accessory thru-thecurb service plate connection is used, route wire through
connection plate.
2. Pass control wires through the hole provided on unit (see
connection D in Connection Sizes table in Fig. 6).
3. Feed wires through the raceway built into the corner post
to the 24-v barrier located on the left side of the control
box. See Fig. 11. The raceway provides the UL-required
(Underwriters’ Laboratories) clearance between highand low-voltage wiring.
4. Connect thermostat wires to screw terminals on lowvoltage connection board.
HEAT ANTICIPATOR SETTINGS — Set heat anticipator
settings at .14 amp for the first stage and .20 amp for secondstage heating, except for 008 low heat. Set both first and second stage heat anticipator settings for 008 at .14 amp.
Contactor
Indoor (Evaporator)
Fan Contactor
National Electrical Code
(U.S.A. Standard)
Splice Connection
(Factory Supplied)
Equipment Ground
Field Wiring
Factory Wiring
LEGEND
AHA —
CC—
Adjustable Heat Anticipator
Cooling Compensator
Field Wiring
Factory Wiring
Fig. 10 — Low-Voltage Connections
UNIT LOW VOLTAGE
CONNECTION
BOARD
RACEWAY
COMPRESSOR
NO. 2
INTEGRATED
GAS UNIT
CONTROLLER
(IGC)
COMPRESSOR
NO.1
Fig. 11 — Field Control Wiring Raceway
and Compressor Location
10
Page 11
Step 8 — Adjust Factory-Installed Options
Fig. 13 — Damper Panel with Manual
Outdoor-Air Damper Installed
Fig. 14 — Outdoor-Air Hood Details
Fig. 15 — Damper with Hood Attached
APOLLO CONTROL — The optional Apollo control is used
to actively monitor all modes of operation as well as indoor
(evaporator) fan status, filter status, and indoor-air quality. The
Apollo control is designed to work with Carrier TEMP and
®
VVT
systems.
The thermostat must be wired to the Apollo control before
starting the unit. Refer to the Apollo control installation
instructions for information on installing the thermostat. See
Fig. 12 for Apollo location.
MANUAL OUTDOOR-AIR DAMPER — The outdoor-air
hood and screen are attached to the base pan at the bottom of
the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for building.
Record amount for use in Step 8.
2. Remove and save evaporator coil access panel and
screws. See Fig. 13.
3. Separate hood and screen from basepan by removi ng the
screws and brackets securing them. Save al l screws and
discard brackets.
4. Replace evaporator coil access panel using screws from
Step 2.
5. Place hood on front of evaporator coil access panel. See
Fig. 14 for hood details. Secure top of hood with the
screws removed in Step 3. See Fig. 15.
6. Remove and save 6 screws (3 on each side) from sides of
the manual outdoor-air damper. Remove and save 2 manual outdoor-air adjustment screws (one on ea ch side of
damper bl ade) .
7. Align screw holes on hood with screw holes on side of
manual outdoor-air damper. See Fi g. 14 and 15. Secure
hood with 6 side screws from Step 6.
8. Adjust minimum position setting of the dampe r blade by
adjusting the 2 manual outdoor-air adjustment screws on
the front of the damper blade. See Fig. 13. Slide blade
vertically until it is in the appropriate position determined
by Fig. 16. Tighten screws.
9. Remove and save screws currently on sides of hood.
Insert screens. Secure screens to hood using the screws.
See Fig. 15.
WIRING TO
THERMOSTAT
APOLLO
CONTROL
CONTROL
WIRING
Fig. 12 — Apollo Control Factory-Installed
in Typical Unit
11
Page 12
1.0
Fig. 17 — Access Panel Locations
250
0.8
200
0.6
150
2" (51 mm)
0.4
100
NEGATIVE PRESSURE (Pa)
NEGATIVE PRESSURE (in. wg)
0.2
50
0
0
0
1" (25 mm) OPEN
200
68
300
24
OUTDOOR AIRFLOW (cfm x 100)
100
OUTDOOR AIRFLOW (L/s)
3" (76 mm)
4.4" (112 mm)
1012
400
500
Fig. 16 — Position Setting
OPTIONAL DURABLADE ECONOMIZER — The optional economizer hood assembly is packaged and shipped in the filter section. Dampe r blades an d contro l boards are instal led at the
factory and the ec onomizer is shipped in the vertical di scharge
position.
NOTE: Horizontal discharge block-off plate is shipped with
the air hood package. If unit is to be used for vertical discharge
application, discard this plate.
Assembly
1. Determine if ventilation air is required in building. If so,
determine the minimum amount to be supplied by ea ch
unit and record quantity of ventilation air needed for use
in Step 8.
2. Remove filter access panel by raising panel and swinging
panel outward. Panel is now disengaged from track and
can be removed. No tools are required to remove filter access panel. Remove outdoor-air opening panel. Save panels and screws. See Fig. 17. Remove optional economizer
and outdoor-air damper hood package from filter section.
3. Assemble outdoor-air hood t op and side plates as shown
in Fig. 18. Install seal strips on hood top and sides. Put
aside screen retainer and retainer screw for later assembly . Do not attach hood to unit at this time.
4. On 012 and 014 units, install vertical discha rge block-off
plate on right side over return air duct opening. See
Fig. 19.
5. a. Slide economizer into unit and secure with screws.
See Fig. 20.
NOTE: Be sure to engage rear economizer flange under tabs at
rear of vertical return-air opening.
b. Remove screw and discard from barometric relief
damper. See Fig. 20.
6. To convert to horizontal discharge application:
a. Rotate the economizer 90 degrees until the econo-
mizer motor faces the condenser section (see
Fig. 21).
b. Rotate the barometric relief damper hinge
90 degrees. Barometric relief damper should open
vertically to operate properly.
c. Install horizontal discharge block-off plate over
the opening on the access panel. (Block-off plate
MUST be installed before installing hood assembly.) See Fig. 22.
7. Insert economizer plug into economizer harness. Remove
tape from barometric relief damper. See Fig. 20.
8. If ventilation air is not required, proceed to Step 9. If ventilation air is required, determine the minimum position
setting for required airflow. See Fi g. 23. Adjust minimum
position setting by loosening the screws on the position
setting bracket. See Fig. 24. Slide bracket until the top
screw is in the position determined by Fig. 23. Tighten
screws.
9. Remove tape from outdoor-air thermostat (OAT). Fasten
OAT to inside of hood using screws and spee d clips provided. See Fig. 25. Make sure OAT terminals are positioned up.
10. Replace outdoor-air opening panel using screws from
Step 2. Replace filter acce ss panel. Ensure the filter a ccess panel slides along the tracks and is securely engaged.
11. Fasten hood top and side plate assembly to outdoor-air
opening panel with screws provided.
12. Place knob supplied with economizer on OAT. See
Fig. 25. Set OAT for 1.7° C (3° F) below indoor room
thermostat setting. If accessory enthal py control (EC) is
used in place of OAT, see instructions shipped with EC
for installation and adjustment. See Fig. 25.
13. Connect OAT per Fig. 26.
14. Slide outdoor-air inlet screens into screen track on hood
side plate. While holding screens in place, fasten screen
retainer to hood using screws provided.
NOTE: Refer to Fig. 27 for Durablade economizer barome tric
relief damper characteristics.
OPTIONAL ECONOMI$ER — See Fig. 28 for EconoMi$er
component locations.
1. To remove the existing unit filter access panel, raise the
panel and swing the bottom outward. The panel is now
disengaged from the track and can be removed. Remove
the indoor coil access panel and discard. See Fig. 29.
NOTE: If installing an optional Power Exhaust Assembly,
refer to the EconoMi$er Power Exhaust Installation Instructions, then proceed to Step 6. Controller should be mounted in
vertical position as shown in Fig. 28.
2. To assemble the hood assembly remove the EconoMi$er
hood from its packaging. Locate the outdoor air opening
panel. See Fig. 30.
3. Install the 19 mm x 19 mm (
exhaust air hood top panel. Install the 3 mm x 22 mm
(1/8 x 7/8-in.) seal strip on the exhaust air hood side panels
and bottom brackets. Assemble the exhaust air hood to
the outdoor air opening panel as shown in Fig. 30, using
the screws provided. Do not attach hood assembly to unit
at this time.
4. Install the 3 mm x 22 mm (
outdoor air hood top and side panels. Assemble the outdoor air hood to the outdoor air opening panel as shown
in Fig. 31, using the screws provided. Do not attach com-
pleted hood (Fig. 32) assembly to the unit at this time.
3
/4 x 3/4-in.) seal strip on the
1
/8 x 7/8-in. seal strip on the
15
Page 16
OUTDOOR AIR
Fig. 35 — EconoMi$er Installed in
48TF008 and 012 Units
Fig. 34 — Rear EconoMi$er Flange Installation
Fig. 33 — Return Air Block-Off Plate Installation
(48TF014 Units Only)
OPENING
PANEL
SEAL STRIP
OUTDOOR AIR
HOOD TOP
SCREEN
RETAINER
OUTDOOR AIR
INLET
SCREENS
ASSEMBLED
EXHAUST HOOD
OUTDOOR AIR
HOOD SIDES
SEAL STRIP
Fig. 31 — Outdoor Air Hood Assembly
Fig. 32 — Completed Hood Assembly
INSTALL
RETURN AIR
BLOCK-OFF
PLATE
UNIT FILTER
RACK
UNIT BASE
BLOWER
FILTER
REMOVE FACTORY INSTALLED
BLOCK-OFF PLATE
(008 AND 012 UNITS ONLY)
ECONOMIZER CLIP
HVAC UNIT
ECONOMIZER
ECONOMIZER REAR
FLANGE
5. Slide the outdoor air inlet screens into the screen track on
the hood side panels. While holding the screens in pl ace,
fasten the screen retainer to the hood using the screws
provided. Repeat the process for the barometric exhaust
air screen. Do not attach hood assembly to unit at this
time.
6. For 48TF014 units, install the return air block-off plate
over the return air duct opening. See Fig. 33.
NOTE: For 48TF008 and 012 units, remove the factoryinstalled block-off plate. See Fig. 33.
7. Slide the EconoMi$er assembly into the rooftop unit. See
Fig. 34 and 35.
NOTE: Be sure to engage rear EconoMi$er flange under tabs in
return air opening of the unit base. See Fig. 34.
8. Install the outdoor air block-off plate, then secure the
EconoMi$er with the screws provided. See Fig. 35.
9. Remove and store the 12-pin jumper plug from the unit
wiring harness located in the upper left corner and insert
the EconoMi$er plug into the unit wiring harness. Refer
to wiring diagram Fig. 36 and 37. Also refer to Fig. 38 if
installing an accessory power exhaust.
10. Install the complete hood assembly on the unit and secure
using the screws provided.
11. Remove the indoor fan motor access panel.
12. Mount the supply air temperature sensor to the lower left
portion of the indoor blower housing with the two (2)
screws provided (see Fig. 39). Connect the violet and
pink wires to the corresponding connections on the supply air temperature sensor. Replace the indoor fan motor
access panel.
WIRING HARNESS
OUTDOOR AIR
BLOCK-OFF PLATE
16
Page 17
OAT —
LEGEND
Outdoor-Air Thermostat
Fig. 36 — EconoMi$er Wiring
ECONOMI$ER
CONTROLLER
OAT
COM
OAH
+15 V
RAT
COM
RAH
+15 V
(+)
CO
2
CO
COM
2
DAT
COM
REM POT
COM
LED
COM
BROWN
VIOLET
WHITE
RED
BROWN
VIOLET
WHITE
RED
SUPPLY AIR
TEMPERATURE SENSOR
PINK
VIOLET
TEMP
TEMP
TEMP
TEMP
COM
OUT
PWR
TEMP
TEMP
COM
OUT
PWR
CO
SENSOR
2
V+
COM VAC
OUTDOOR
AIR
SENSOR
RETURN
AIR
SENSOR
24
Fig. 37 — EconoMi$er Sensor Wiring
17
Page 18
TO FUSED
DISCONNECT
2 x 4 IN.
HANDY BOX
BLACK L1
BLUE L2
GREEN GND
(460 VAC)
HT01AH850
1
1
22
33
44
230 VAC
1 PHASE
RED YELH1BLU
H3
H2
X3
X2
X4
SECONDARY
230VAC
4-PIN
CONNECTOR
PLUG
L1
L2
GND
GREEN
GRAY
H4
X1
BLACK
BLUE
FIELD SUPPLIED
WIRING
BROWN
C1
GREEN/
YELLOW
BROWN
C1
GREEN/
YELLOW
FAN 1
FAN 2
BLACK
BLACK
LT. BLUE
BLACK
BLUE
BLACK
LT. BLUE
BLACK
3
2
1
3
2
1
6
5
4
BLUE
B
9
8
7
9
6
8
5
4
7
R1
24 VAC
A
B
R2
24 VAC
A
3-PIN
CONNECTOR
PLUG
ORANGE
YELLOW
BROWN
1
2
3
Fig. 38 — Wiring Diagram for Power Exhaust System
SUPPLY AIR
TEMPERATURE
SENSOR
MOUNTING
LOCATION
SUPPLY AIR
TEMPERATURE
SENSOR
Fig. 39 — Supply Air Sensor Placement
18
Page 19
Control Set Up — If a CO2 sensor is not being used, pro-
0
400
800
1200
1600
2000
2400
FLOW (CUBIC FEET/MINUTE)
0.5
0.4
0.3
0.2
0.1
0
STATIC PRESSURE (IN.WG)
PRESSURE DROP (Pa)
FLOW (L/s)
0
200
400
600
800
125
100
75
50
25
0
1000 1200
Fig. 40 — EconoMi$er Control Adjustment
Potentiometers (Factory Settings)
Fig. 41 — EconoMi$er Barometric Relief Capacity
CO
2
ceed to the next section. If a CO
sensor is being used, perform
2
the following:
1. Determine the value at which you want the minimum
position of the dampers to begin opening to allow a greater amount of outdoor air to enter. The range is 800 to
1,400 ppm.
2. Locate the CO
SP (PPM) potentiometer and adjust to the
2
desired set point. See Fig. 40.
Mechanical Cooling Lockout
— Determine the outdoor-air
temperature at which you want the mechanical cooling (compressors) to be disabled. Locate the mechanical cooling lockout
(MECH CLG LOCKOUT) potentiometer. To disable this feature, turn the potentiometer counterclockwise (CCW) to the
OFF position. Otherwise, set the value between –12 and 15 C
(10 and 60 F). Mechanical cooling will not operate when the
outdoor air temperature is below this value. See Fig. 40.
Dry Bulb Cha ngeover Set Up
— Determine the dry bulb
changeover set point from T able 4. The settings are A, B, C and
D. Locate the ECON SP potentiometer and set the dry bulb
changeover set point. See Fig. 40. When the OAT is above this
set point, the damper is limited to minimum position setting.
Table 4 — Changeover Set Points
SETTINGSABCD
Dry Bulb C (°F)
Single Enthalpy* KJ/Kg (Btu/lb)
Differential Temperature* C
(°F, Not Adjustable)
Differential Enthalpy* KJ/Kg
(Btu/lb, Not Adjustable)
*Field-installed accessory.
23
(73)21(69)19(66)17(63)
63
(27)58(25)56(24)51(22)
1.1
1.1
1.1
(2)
(2)
2
(1)2(1)2(1)2(1)
(2)
1.1
(2)
4. Calculate the minimum airflow across the EconoMi$er.
a. Calculate % of outside air using the following
formula.
% Outdoor air through EconoMi$er
% Outdoor air =
Mixture Temp – Return Air Temp
Outdoor T emp – Return Air Temp
b. Multiply total CFM by percentage outdoor air, this
gives outdoor air vol ume in CFM.
5. T urn on base unit power.
NOTE: The EconoMi$er begins operation three min-
utes after power up.
Personal Injury Hazard. Avoid possible injury by keeping fingers away from damper blades.
6. See Fig. 41 for barometric relief damper characteristics.
If a potentiometer fails, its setting will default to the values
in Ta ble 5.
Table 5 — Default Potentiometer Settings
POTENTIOMETERDEFAULT SETTING
CO
SP (PPM)
2
MECH CLG LOCKOUT, C (F)
ECON SP
MIN POS (%)
Ventilation Air (Minimum Position Set Up)
air is not required, proceed to Step 5. If ventilation air is required, perform the following:
1. The indoor fan must be on to set the ventilation air. Either
put the thermostat in the continuous fan mode or jumper
the R and G terminals at the rooftop unit connection
board.
2. Locate the minimum position (MIN POS) potentiometer.
Turn the potentiometer full CCW to fully close the out door air dampers. Turn the potentiometer gradually
clockwise (CW) to the desired position. See Fig. 40.
3. Replace the filter access panel. See Fig. 21. Ensure the filter access panel slides along the tracks and is securely
engaged.
1,000
8.3 (47)
D
20
— If ventilation
19
Page 20
Step 9 — Adjust Evaporator-Fan Speed —
Fig. 42 — Typical Belt-Drive Motor Mounting
for Size 008
Fig. 43 — Typical Belt-Drive Motor Mounting
for Sizes 012,014
Fig. 44 — Evaporator-Fan Pulley Adjustment
just evaporator-fan speed to meet jobsite requirement.
T a ble 6 shows motor performance. Tables 7 and 8 show fan
rpm at motor pulley settings, Table 9 shows motor efficiencies
and Table s 10 and 11 give accessory static pressure drops. Refer to Tables 12-23 to determine fan speed settings. Fan motor
pulleys are factory set for speed shown in Table 1A or 1B.
T o change fan speed:
1. Shut off uni t power supply and install lockout tag.
2. Loosen belt by loosening fan motor mounting plate nuts
(see Fig. 42 and 43).
3. Loosen movable pulley flange setscrew (see Fig. 44).
4. Screw movable flange toward fixed flange to increase fan
speed and away from fixed flange to decrease fan speed.
Increasing fan speed increases load on motor. Do not exceed maximum speed specified in Table 1A or 1B.
5. Set movable flange at nearest flat of pulley hub and tighten setscrew (see Table 1A or 1B for speed change for
each full turn of pulley flange).
T o align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from
mounting plate.
T o adjust belt tension (see Fig. 42 and 43):
1. Loosen fan motor mounting nuts.
2. Size 008 — Slide motor mounting pla te away from fan
scroll for proper belt tension (13 mm [
with 3.6 to 4.5 kg [8 to 10 lbs] of force) and tighten
mounting nuts. See Fig. 42.
Sizes 012,014 — Slide motor mounting plate downward
to tighten belt tension (13 mm [
to 4.5 kg [5 to 10 lbs] of force) and tighten mounting nuts.
See Fig. 43.
1
/2-in.] deflection with 2.3
3. Adjust bolt and nut on mounting plate to secure motor in
fixed position. See Fig. 44.
Realign fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from
mounting plate.
LEGEND*Extensive motor and electrical testing on these units ensures that
Brake Horsepower
kW x Motor Efficiency
MAXIMUM ACCEPTABLE
CONTINUOUS
BkW*
MAXIMUM ACCEPTABLE
CONTINUOUS
BHP*
the full range of the motors can be utilized with confidence. Using
your fan motors up to the ratings shown in this table will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected.
Fan Input kW x Motor Efficiency
Revolutions Per Second of Blower Wheel
Boldface
indicates field-supplied drive required. (See Note 5.)
2.indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils.
EXTERNAL STATIC PRESSURE (Pa)
100150
11.90.9612.81.17
12.11.0213.11.26
12.31.0913.21.29
12.61.1813.51.38
14.41.8415.12.10
14.61.9715.42.24
EXTERNAL STATIC PRESSURE (Pa)
300350
15.51.8416.52.10
15.61.8816.72.10
4. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative to verify.
5. Standard drive range is 8.2 to 11.7 r/s. All other speeds require
a field-supplied drive.
6. Maximum continuous BkW is 1.79. Extensive motor and electrical testing on these units ensures that the full range of the
motor can be utilized with confidence. Using the fan motors up
to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
7. Interpolation is permissible. Do not extrapolate.
200
12.20.96
12.41.02
12.61.08
14.71.88
14.92.00
400
15.81.96
15.92.00
16.12.17
16.32.17
22
Page 23
Table 13 — Fan Performance, 48TF012 — Vertical Discharge Units (SI)
Fan Input kW x Motor Efficiency
Revolutions Per Second of Blower Wheel
Boldface
indicates field-supplied drive required. (See Note 5.)
2.indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils.
5. Standard drive range is 9.5 to 13.0 r/s. All other speeds require
a field-supplied drive.
6. Maximum continuous BkW is 1.79. Extensive motor and electrical testing on these units ensures that the full range of the
motor can be utilized with confidence. Using the fan motors up
to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
7. Interpolation is permissible. Do not extrapolate.
17.41.8818.12.00
17.81.81
17.91.86
18.01.91
4. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative to verify.
250
500
23
Page 24
Table 14 — Fan Performance, 48TF014 — Vertical Discharge Units (SI)
Fan Input kW x Motor Efficiency
Revolutions Per Second of Blower Wheel
NOTES:
1.
Boldface
indicates field-supplied drive required. (See Note 5.)
2.indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
5. Standard drive range is 12.0 to 15.0 r/s. All other speeds
require a field-supplied drive.
6. Maximum continuous BkW is 2.76. Extensive motor and electrical testing on these units ensures that the full range of the
motor can be utilized with confidence. Using the fan motors up
to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
7. Interpolation is permissible. Do not extrapolate.
19.82.8420.53.02
19.92.9720.73.17
20.32.88
your Carrier representative to verify.
250
500
24
Page 25
Table 15 — Fan Performance, 48TF008 — Horizontal Discharge Units (SI)
Fan Input kW x Motor Efficiency
Revolutions Per Second of Blower Wheel
Boldface
indicates field-supplied drive required. (See Note 5.)
2.indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative to verify.
200
225
11.80.8112.40.92
12.00.8912.50.98
12.20.9612.71.05
12.41.0212.81.11
12.61.0813.01.19
12.71.1413.21.25
12.00.9912.91.2213.41.33
12.21.0713.21.2713.61.40
12.41.1513.41.3613.81.48
12.71.2313.61.4414.01.56
14.71.85
14.51.8514.91.97
14.81.9515.12.07
14.21.8115.02.0815.42.20
14.41.9215.22.2015.62.34
400
15.71.89
15.91.92
16.01.96
16.02.01
16.22.06
5. Standard drive range is 8.2 to 11.7 r/s. All other speeds require
a field-supplied drive.
6. Maximum continuous BkW is 1.79. Extensive motor and electrical testing on these units ensures that the full range of the
motor can be utilized with confidence. Using the fan motors up
to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
7. Interpolation is permissible. Do not extrapolate.
25
Page 26
Table 16 — Fan Performance, 48TF012 — Horizontal Discharge Units (SI)
Fan Input kW x Motor Efficiency
Revolutions Per Second of Blower Wheel
Boldface
indicates field-supplied drive required. (See Note 5.)
2.indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils.
5. Standard drive range is 9.5 to 13.0 r/s. All other speeds require
a field-supplied drive.
6. Maximum continuous BkW is 1.79. Extensive motor and electrical testing on these units ensures that the full range of the
motor can be utilized with confidence. Using the fan motors up
to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
7. Interpolation is permissible. Do not extrapolate.
17.31.8118.01.97
17.51.9118.22.04
4. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative to verify.
200
450
250
13.50.99
13.71.06
13.91.14
15.31.82
15.51.92
500
17.71.82
17.81.86
17.91.91
18.01.97
26
Page 27
Table 17 — Fan Performance, 48TF014 — Horizontal Discharge Units (SI)
Fan Input kW x Motor Efficiency
Revolutions Per Second of Blower Wheel
NOTES:
1.
Boldface
indicates field-supplied drive required. (See Note 5.)
2.indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
19.02.8819.83.1020.53.31
19.22.9920.03.2320.73.45
5. Standard drive range is 12.0 to 15.0 r/s. All other speeds
require a field-supplied drive.
6. Maximum continuous BkW is 2.76. Extensive motor and electrical testing on these units ensures that the full range of the
motor can be utilized with confidence. Using the fan motors up
to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
7. Interpolation is permissible. Do not extrapolate.
19.52.8420.13.02
19.62.9720.33.17
19.92.87
your Carrier representative to verify.
225
500
27
Page 28
Table 18 — Fan Performance, 48TF008 — Vertical Discharge Units (English)
5. Standard drive range is 492 to 700 rpm. All other rpms require
a field-supplied drive.
6. Maximum continuous bhp is 2.4. Extensive motor and electrical
testing on these units ensures that the full range of the motor
can be utilized with confidence. Using the fan motors up to the
ratings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.
7. Interpolation is permissible. Do not extrapolate.
Brake Horsepower at Motor Shaft
Revolutions Per Minute of Blower Wheel
Boldface
indicates field-supplied drive required. (See Note 5.)
2.indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils.
5. Standard drive range is 571 to 779 rpm. All other speeds
require a field-supplied drive.
6. Maximum continuous bhp is 2.4. Extensive motor and electrical
testing on these units ensures that the full range of the motor
can be utilized with confidence. Using the fan motors up to the
ratings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.
7. Interpolation is permissible. Do not extrapolate.
10472.5310872.70
10702.44
10752.51
10822.58
4. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative to verify.
1.0
8291.42
9482.51
2.0
29
Page 30
Table 20 — Fan Performance, 48TF014 — Vertical Discharge Units (English)
Brake Horsepower at Motor Shaft
Revolutions Per Minute of Blower Wheel
NOTES:
1.
Boldface
indicates field-supplied drive required. (See Note 5.)
2.indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
5. Standard drive range is 717 to 900 rpm. All other rpms require
a field-supplied drive.
6. Maximum continuous bhp is 3.7. Extensive motor and electrical
testing on these units ensures that the full range of the motor
can be utilized with confidence. Using the fan motors up to the
ratings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.
7. Interpolation is permissible. Do not extrapolate.
11833.7612254.00
11933.9312364.19
12143.83
your Carrier representative to verify.
2.0
30
Page 31
Table 21 — Fan Performance, 48TF008 — Horizontal Discharge Units (English)
5. Standard drive range is 492 to 700 rpm. All other rpms require
a field-supplied drive.
6. Maximum continuous bhp is 2.4. Extensive motor and electrical
testing on these units ensures that the full range of the motor
can be utilized with confidence. Using the fan motors up to the
ratings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.
7. Interpolation is permissible. Do not extrapolate.
31
Page 32
Table 22 — Fan Performance, 48TF012 — Horizontal Discharge Units (English)
Brake Horsepower at Motor Shaft
Revolutions Per Minute of Blower Wheel
Boldface
indicates field-supplied drive required. (See Note 5.)
2.indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils.
5. Standard drive range is 571 to 779 rpm. All other rpms require
a field-supplied drive.
6. Maximum continuous bhp is 2.4. Extensive motor and electrical
testing on these units ensures that the full range of the motor
can be utilized with confidence. Using the fan motors up to the
ratings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.
7. Interpolation is permissible. Do not extrapolate.
10412.4410832.65
4. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative to verify.
Brake Horsepower at Motor Shaft
Revolutions Per Minute of Blower Wheel
NOTES:
1.
Boldface
indicates field-supplied drive required. (See Note 5.)
2.indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
5. Standard drive range is 717 to 900 rpm. All other rpms require
a field-supplied drive.
6. Maximum continuous bhp is 3.7. Extensive motor and electrical
testing on these units ensures that the full range of the motor
can be utilized with confidence. Using the fan motors up to the
ratings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.
7. Interpolation is permissible. Do not extrapolate.
11653.7612033.99
11753.9212154.18
11903.80
your Carrier representative to verify.
2.0
33
Page 34
START-UP
Unit Preparation —
stalled in accordance with these installation instructions and
applicable codes. Make sure that Start-Up Checklist, located on
back page of this booklet, has been completed and filled out.
Return-Air Filters —
stalled in filter tracks (see Ta bles 1A and 1B). Do not operate
unit without return-air filters.
Outdoor-Air Inlet Screens —
must be in place before operating unit.
Compressor Mounting —
spring mounted. Do not loosen or remove compressor holddown bolts. On 48TF014 units, remove the tiedown bands that
hold the compressors together.
Internal Wiring —
unit control boxes. Tighten as required. Ensure wiring does not
come into direct contact with refrigerant tubing.
Refrigerant Service Ports —
tem has 4 Schrader-type service gage ports: one on the suction
line, one on the liquid line, and two on the compressor discharge line. Be sure that caps on the ports are tight. One
Schrader-type valve is located under both the high-pressure
switch and the low-pressure switch when ordered as an option.
High Flow Valves —
and suction tubes are High Flow Valves. Large black plastic
caps distinguish these valves with O-rings located inside the
caps. These valves cannot be accessed for servi ce in the field.
Ensure the plastic caps are in place and tight or the possibility
of refrigerant leakage could occur.
Compressor Rotation —
compressors, it is important to be certain compressor is rotating
in the proper direction. To determine whether or not compressor is rotating in the proper direction:
1. Connect service gages to suction and discharge pressure
fittings.
2. Energize the compressor .
3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pres-
sure does not rise to normal levels:
1. Note that the evaporator fan is probably also rotating in
the wrong direction.
2. T urn of f power to the unit and install lockout tag.
3. Reverse any two of the unit power leads.
4. Reapply power to unit. Reenergize compressor.
The suction and discharge pressure levels should now move
to their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direc-
tion, the unit will make an elevated level of noise and will not
provide cooling.
Cooling —
system selector switch at COOL position and fan switch at
AUTO. position. Adjust thermostat to a setting below room
temperature. Compressor, indoor and outdoor fans start on closure of contactors.
Check unit charge. Refer to Refrigerant Charge section,
page 37. Unit must operate a minimum of 15 minutes before
adjusting charge.
Reset thermostat at a position above room temperature.
Compressor and outdoor fans will shut off. Evaporator fan will
shut off after 30-second delay .
To start unit, turn on main power supply. Set
Make sure that unit has been in-
Make sure correct filters are in-
Outdoor-air inlet screens
Compressors are internally
Check all electrical connections in
Each refrigerant sys-
Located on the compressor hot gas
On 3-phase units with scroll
TO SHUT OFF UNIT — Set s y stem selector switch at OFF
position. Resetting thermostat at a position above room temperature shuts unit off temporarily until space temperature exceeds thermostat setting.
Main Burners —
require no adjustment.
TO CHECK ignition of main burners and heating controls,
move thermostat set point above room temperature and verify
that the burners light and evaporator fan is energized. After ensuring that the unit continues to heat the building, lower the
thermostat setting below the room temperature and verify that
the burners and evaporator fan turn off (fan will turn off only if
fan selector switch is in the AUTO. position). Refer to Table 24
for the correct orifice to use at high altitudes.
NOTE: Upon a call for heat, the main burners will remain on
for a minimum of 60 seconds.
ADJU ST G AS I NPUT — The gas input to the unit is determined by measuring the gas flow at the meter or by measuring
the manifold pressure. Manifold pressure should be 872 Pa
(3.5 in. wg).
NOTE: Unit uses a 2 stage gas valve. There is no need to
adjust the “Low Fire” manifold pressure.
Measure Gas Flow (Natural Gas Units)
to the gas flow can be made by changing the manifold pressure.
The manifold pressure must be 872 Pa (3.5 in wg). Normal
manifold pressure is 872 Pa (3.5 in. wg) in high fire, W1 and
W2 inputs to gas valve.
Proceed as follows:
1. T urn of f gas supply to unit.
2. Remove pipe plug on manifold then connect manometer
at this point. Turn on gas to unit. Ensure gas valve is in
high fire operation.
Observe manifold pressure and proceed as follows to adjust
gas input:
1. Remove cover screw over regulator adjustment screw on
gas valve. Ensure gas valve is operating in high fire
mode.
2. Turn regulator adjustment screw clockwise to increase
gas input, or turn regulator adjustment screw counterclockwise to decrease input. High fire manifold pressure
must be 872 Pa (3.5 in. wg).
Unsafe operation of the unit may result if manifold pressure is outside 847 to 897 Pa (3.4 to 3.6 in. wg) range. Personal injury or unit damage may result.
3. Replace cover screw cap on gas valve.
4. Turn off gas supply to unit. Remove manometer from
pressure tap and replace pipe plug on gas valve. Turn on
gas to unit and check for leaks.
Main burners are factory set and should
— Minor adjustment
Heating
1. Purge gas supply line of air by opening union ahead of
gas valve. When gas odor is detected, tighten union and
wait 5 minutes before proceeding.
2. T urn on electrical supply and open manual gas valve.
3. Set system switch selector at HEAT position and fan
switch at AUTO. or ON position. Set heating temperature
lever above room temperature.
4. The induced-draft motor will start, purging heat
exchangers.
34
Page 35
5. After a call for heating, the main burners should light
within 5 seconds. If the burners do not light, then there is
a 22-second delay before another 5-second ignition try.
If the burners still do not light, the time delay is repeated.
If the burners do not light within 15 minutes, there is a
lockout. T o reset the control, break the 24 v power to W1.
6. The evaporator-fan motor will turn on 45 seconds after
the burners are ignited.
7. The evaporator-fan motor will turn off 45 seconds after
the thermostat temperature is satisfied.
8. Adjust airflow to obtain a temperature rise within the
range specified on the unit nameplate and in Table 1A
or 1B.
Table 24 — Altitude Compensation*
31.4, 50.4, AND 59.8 kW
(107,000, 172,000 AND
ELEVATION
m or km
(ft)
0-610 m (0-2,000)
610 m (2,000)
914 m (3,000)
1.22 km (4,000)
1.52 km (5,000)
1.83 km (6,000)
2.13 km (7,000)
2.44 km (8,000)
2.74 km (9,000)
3.05 km (10,000)
3.35 km (11,000)
3.66 km (12,000)
3.96 km (13,000)
4.27 km (14,000)
*As the height above sea level increases, there is less oxygen.
Therefore, heat input rate should be reduced at higher altitudes.
†Orifice available through your local distributor.
204,000 BTUH
NOMINAL INPUT
Natural
Gas
Orifice
Size†
3.0 (31)2.4 (41)3.2 (30) 2.5 (38)
2.9 (32)2.3 (42)3.2 (30) 2.5 (39)
2.9 (32)2.3 (42)3.0 (31) 2.4 (40)
2.9 (32)2.3 (42)2.9 (32) 2.4 (41)
2.8 (33)2.2 (43)2.8 (33) 2.3 (42)
2.8 (34)2.2 (43)2.8 (34) 2.2 (43)
2.8 (35)2.1 (44)2.8 (35) 2.2 (43)
2.7 (36)2.1 (44)2.7 (36) 2.1 (44)
2.6 (37)2.0 (45)2.6 (37) 2.1 (44)
2.5 (38)2.0 (46)2.5 (38) 2.0 (45)
2.5 (39)1.9 (47)2.5 (39) 2.0 (45)
2.4 (40)1.9 (47)2.4 (40) 2.0 (46)
2.4 (41)1.9 (48)2.4 (41) 1.9 (47)
2.3 (42)1.9 (48)2.3 (42) 1.9 (47)
Liquid
Propane
Orifice
Size†
65.6 kW
(224,000 BTUH)
NOMINAL INPUT
Natural
Gas
Orifice
Size†
Liquid
Propane
Orifice
Size†
Integrated Gas Controller (IGC) Operation
NOTE: The default value for the evaporator-fan motor ON and
OFF delay is 45 seconds. The Integrated Gas Controller (IGC)
modifies this value when abnormal limit switch cycles occur.
Based upon unit operating conditions, the ON delay can be
reduced to 0 seconds and the OFF delay can be extended to
180 seconds.
When one flash of the LED (light-emitting diode) is observed, the evaporator-fan ON/OFF delay has been modified.
If the limit switch trips at the start of the heating cycle during
the evaporator ON delay, the time period of the ON delay for
the next cycle will be 5 seconds less than the time at which the
switch tripped. (Example: If the limit sw itch trips at 30 seconds, the evaporator-fan ON delay for the next cycle will occur
at 25 seconds.) To prevent short-cycling, a 5-second reduction
will only occur if a minimum of 10 minutes has elapsed sinc e
the last call for heating.
The evaporator-fan OFF delay can also be modified. Once
the call for heating has ended, there is a 10-minute period during which the modification can occur. If the limit switch trips
during this period, the evaporator-fan OFF delay will increase
by 15 seconds on the next cycle. A maximum of 9 trips can occur, extending the evaporator-fan OFF delay to 180 seconds.
T o rest ore the ori ginal default va lue, rese t the powe r to the unit .
TO SHUT OFF UNIT — Set system s e lector swit ch at OFF
position. Resetting heating selector lever below room temperature will shut unit off temporarily until space temperature falls
below thermost at se tting .
Safety Relief —
A soft-solder joint at the suction line
Schrader port provides pressure relief under abnormal temperature and pressure conditions.
Ventilation (Continuous Fan) —
Set fan and system
selector switches at ON and OFF positions, respectively.
Evaporator fan operates continuously to provide constant air
circulation. When the evaporator-fan sel ector switch is turned
to the OFF position, there is a 30-second delay before the fan
turns off.
Operating Sequence
COOLING, UNITS WITHOUT ECONOMIZER — When
thermostat calls for cooling, terminals G and Y1 are energized.
The indoor (evaporator) fan contactor (IFC) and compressor
contactor no. 1 (C1) are energized, and evaporator-fan motors,
compressor no. 1, an d both conde nser fans s tart. The co ndenserfan motor runs continuously while unit is cooling. If the thermostat calls for a second stage of cooling by energizing Y2, compressor contactor no. 2 (C2) is energized and compressor no. 2
starts.
When the thermostat is satisfied, C1 and C2 are deenergized and the compressors and outdoor (condenser) fan motors
(OFM) shut off. After a 30-second delay, the indoor (eva porator) fan motor (IFM) shuts off. If the thermostat fan selector
switch is in the ON position, the evaporator motor will run
continuously .
HEATING, UNIT S WIT HO UT E C ONO MIZ ER — When
the thermostat calls for heat ing, terminal W1 is energized. In
order to prevent thermostat short-cycling, the unit is locked
into the Heating mode for at least 1 minute when W1 is energized. The induced-draft motor (IDM) is then energized and
the burner ignition sequence begins. The indoor (evaporator)
fan motor (IFM) is energized 45 seconds after a flame is ignited. On units equipped for two stages of heat, when additional
heat is needed, W2 is energized and the high-fire solenoid on
the main gas valve (MG V) is energized. W hen the thermo stat
is satisfied and W1 and W2 are deenergized, the IF M s tops after a 45-second time-off delay.
COOLING, UNITS WITH DURABLADE ECONOMIZER — When the outdoor-air temperature is above the
OAT (outdoor-air thermostat) setting and the room thermostat
calls for cooling, compressor contactor no. 1 is energized to
start compressor no. 1 and the outdoor (condenser) fan motor
(OFM). The indoor (evaporator) fan motor (IFM) is energized
and the economizer damper moves to the minimum position.
Upon a further call for cooling, compressor contactor no. 2 will
be energized, starting compressor no. 2. After the thermostat is
satisfied, the damper moves to the fully closed position when
using an auto fan or to the minimum position when using a
continuous fan.
When the outdoor-a ir temperature is below the OAT setting
and the thermostat calls for cooling, the economizer dampers
move to the minimum position. If the supply-air temperature is
above 14 C (57 F), the damper continues to open until it reaches the fully open position or until the supply-air temperature
drops below 11 C (52 F).
When the supply-air temperature falls to between 14 C
(57 F) and 11 C (52 F), the damper will remain at an intermediate open position. If the supply-air temperature falls below
11 C (52 F), the damper will modulate closed until it reaches
the minimum position or until the supply-air temperature is
above 11 C (52 F). When the thermostat is satisfied, the damper will move to the fully closed position when using an auto fan
or to the minimum position when using a continuous fan.
35
Page 36
If the outdoor air alone cannot satisfy the cooling require ments of the conditioned space, economizer cooling is integrated with mechanical cooling, providing second-stage cooling.
Compressor no. 1 and the condenser fa n will be energized and
the position of the economizer damper will be determined by
the supply-air temperature. Compressor no. 2 is locked out.
When the second stage of cooling is satisfied, the compressor and OFM will be deenergized. The damper position will be
determined by the supply-air temperature.
After a 30-second delay, the IFM shuts of f. If the thermostat
fan selector switch is in the ON position, the IFM will run
continuously .
COOLING UNITS WITH ECONOMI$ER — When the
OAT is above the ECON SP set point and the room thermostat
calls for Stage 1 cooling (R to G + Y1), the indoor fan motor
(IFM) is energized and the EconoMi$er dampe r modulates to
minimum position. The compressor contactor is energized to
start the compressor and outdoor-fan motor (OFM). After the
thermostat is satisfied, the damper modulates to the fully closed
position when the IFM is deenergized.
When the OAT is below the ECON SP setting and the room
thermostat calls for Stage 1 cooling (R to G + Y1), the
EconoMi$er modulates to the minimum position when the
IFM is energized. The EconoMi$er provides Stage 1 of cooling
by modulating the return and outdoor air dampers to maintain a
13 C (55 F) supply air set point. If the supply-air temperature
(SAT) is greater than 14 C (57 F), th e EconoMi$er modulates
open, allowing a greater amount of outdoor air to enter the unit.
If the SAT drops below 12 C (53 F), the out door air damper
modulates closed to reduce the amount of outdoor air. When
the SAT is between 12 C (53 F) and 14 C (57 F), the
EconoMi$er maintains its position.
If outdoor air alone cannot satisfy the cooling requirements
of the conditioned space, and the OAT is above the MECH
CLG LOCKOUT set point, the EconoMi$er integrates free
cooling with mechanical cooling. This is accomplished by the
strategies below.
NOTE: Compressors have a two-minute Minimum On, Minimum Off, and interstage delay timer.
1. If Y1 is energi zed, and the room thermostat calls for Y2
(2-stage thermostat), the compressor and OF M are energized. The position of the EconoMi$er damper is maintained at its current value.
2. If Y1 is energiz ed for more than 20 minutes, and Y2 is
not energized (whether or not a 2-stage thermostat is
used), the compressor and OFM are energized. The position of the EconoMi$er damper is maintained a t its current value.
3. If Y1 is energized, and compressor no. 1 is already energized (see Step 2) and the room thermostat calls for Y2,
compressor no. 1 continues to operate. If Y2 remains
energized for more than 20 minutes, compressor no. 2 is
energized.
NOTE: Compressor no. 2 cannot be energized unless there is a
signal for Y2 from the space thermostat.
4. If compressor no. 2 is energized, and the Y2 signal from
the thermostat is satisfied, compressors 1 and 2 are deenergized. Re-asserting Y2 will start compressor no. 1 and
(after a 20-minute interstage delay) compressor no. 2.
5. If compressor no. 1 is energized and the thermostat is satisfied, compressor no. 1, the OFM, and IFM are deenergized and the EconoMi$er modulates closed.
When the OAT is below the MECH CLG LOCKOUT set
point, the compressors remain off.
SERVICE
When servicing unit, shut off all electrical power to unit to
avoid shock hazard or injury from rotating parts.
Cleaning —
heating and cooling season or more frequently as operating
conditions require.
EVAP O RATOR COIL — Clean coil as required. Inspect coil
at beginning of heating and cooling seasons.
1. T urn unit power of f. Remov e evaporator coil access panel.
2. If economizer is installed, remove economizer by disconnecting Molex plug and removing economizer mounting
screws. Refer to Accessory Economizer Installation Instructions or Optional Economizer sections on pages 12
and 15 for more details.
3. Remove filters from unit.
4. Clean coil using a commercial coil cleaner or dishwasher
detergent in a pressurized spray canister. Wash both sides
of coil and flush with clean water. For be st results, backflush toward return-air section to remove foreign ma terial. Caution should be taken as to not overflow the evaporator drain condensate pan.
5. Flush condensate pan after completion.
6. Reinstall economizer and filters.
7. Reconnect wiring.
8. Replace access panels.
CONDENS ER COIL — Inspect coil monthly. Clean condenser coil annually, and as required by location and outdoorair conditions.
One-Row Coils
outer surfaces with a stiff brush in the normal manner. It is not
necessary to remove top panel.
2-Row Coils
1. T urn of f unit power.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. See Fig. 45. To hold
top panel open, place coil corner post between top panel
and center post. See Fig. 46.
4. Remove screws securing coil to center post.
5. Remove fastener holding coil sections together at return
end of condenser coil. Carefully separate the outer coil
section 3 to 4 in. from the inner coil section. See Fig. 47.
6. Use a water hose or other suitable equipment to flush
down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner.
7. Secure inner and outer coil rows together with a fieldsupplied fastener.
8. Reposition the outer coil section and remove the coil corner post from between the top panel and center post.
9. Reinstall the coil corner post and replace all screws.
CONDENSATE DRAIN — Check and clean each year at
start of cooling season. In winter, keep drain dry or protect
against freeze-up.
FILTERS — Clean or replace at start of each heating and cooling season, or more often if operating conditions require it. Replacement filters must be same dimensions as original filters.
BELTS — Adjust belt tension and pulley alignment at least
twice a year or more frequently as operating conditions require.
Refer to Step 9 — Adjust Evaporator for Fan Speed
for procedures.
Inspect unit interior at the beginning of each
— Wash coil with commercia l c lea n er. Clean
— Clean coil as follows:
36
Page 37
Fig. 45 — Cleaning Condenser Coil
Fig. 48 — Condenser-Fan Adjustment
48TF UNIT VOLTAGEFAN HEIGHT “A” (in.)
400 V
89 (3.50)
Lubrication
COMPRESSORS — Each compressor is charged with the
correct amount of oil at the factory.
FAN-MOTOR BEARINGS — Fan-motor bearings are of
the permanently lubricated type. No further lubrication is required. No lubrication of condenser- or evaporator-fan motors
is required.
Condenser-Fan Adjustment (Fig. 48)
1. Shut of f unit power supply and tag disconnect.
2. Remove condenser-fan assembly (grille, motor, motor
cover, and fan) and loosen fan hub setscrews.
3. Adjust fan height as shown in Fig. 48.
4. T ighten setscrews and replace condenser-fan assembly .
Fig. 46 — Propping Up Top Panel
Fig. 47 — Separating Coil Sections
Manual Outdoor-Air Damper —
If outdoor-air damper blade is required, see Manual Outdoo r-Air Damper sec tion on
page 12.
Economizer Adjustment —
Refer to Optional Dura-
blade Economizer section on page 14.
Condenser Coil Grille —
Condenser coil grille is
shipped factory-installed. No adjustments are required.
Refrigerant Charge —
Amount of refrigerant charge is
listed on unit nameplate (also refer to Tables 1A and 1B). Refer
to Carrier GTAC 2-5 Char ging, Recovery, recycling, and reclamation training manual and the following procedures.
Unit panels must be in place when unit is operating during
charging procedure.
NO CHARGE — Use standard evacuating techniques. Aft er
evacuating system, weigh in the specified amount of refrigerant (refer to Tables 1A and 1B).
LOW CHARGE COOLING — Using the Cooling Charging
Charts, Fig. 49-51 vary refrigerant until the conditions of the
appropriate chart are met. Note the charging charts are different from the type normally used. The charts are based on
charging the units to the correct superheat for the various operating conditions. Accurate pressure gage and temperature sensing device are required. Connect the pressure gage to the
service port on the suction line. Mount the temperature sensing
device on the suction line and insulate it so that outdoor ambient temperature does not affect the reading. Indoor-air cfm
must be within the normal operating range of the unit.
TO USE COOLING CHARGING CHARTS — Take the outdoor ambient temperature and read the suction pressure gage.
Refer to appropriate chart to determine what suction temperature should be. If suction temperature is high, add refrigerant.
If suction temperature is low, carefully reclaim some of the
charge. Recheck the suction pressure as charge is adjusted.
Example (Fig. 51, Circuit 1):
Suction T emperature should be. . . . . . . . . . . . . . . . .23 C (74 F)
(Suction temperature may vary ± 3 C [5 F].)
37
Page 38
Fig. 49 — Cooling Charging Charts, 48TF008 Units
Fig. 50 — Cooling Charging Charts, 48TF012 Units
38
Page 39
CIRCUIT NO. 1
Fig. 51 — Cooling Charging Chart; 48TF014 Units
CIRCUIT NO. 2
Flue Gas Passageways —
To ins pect the flue collec-
tor box and upper areas of the heat exchanger:
1. Remove the combustion blower wheel and motor assembly according to directions in Combustion-Air Blower
section below.
2. Remove the flue cover to inspect the heat exchanger.
3. Clean all surfaces as required using a wire brush.
Combustion-Air Blower —
Clean periodically to assure proper airflow and heating efficiency. Inspect blower
wheel every fall and periodically during heating season. For the
first heating season, inspect blower wheel bimonthly to determine proper cleaning frequency.
To inspect blower wheel, shine a flashlight into draft hood
opening. If cleaning is required, remove motor and wheel as
follows:
1. Slide burner access panel out.
2. Remove the 6 screws that attach induced-draft motor
housing to vestibule plate (Fig. 52).
3. The blower wheel can be cleaned at this point. If additional cleaning is required, continue with Steps 4 and 5.
4. To remove blower from the motor shaft, remove
2 setscrews.
5. To remove motor, remove the 4 screws that hold blower
housing to mounting plate. Remove the motor cooling fan
by removing one setscrew. Then remove nuts that hold
motor to mounting plate.
6. To reinstall, reverse the procedure outlined above.
Limit Switch —
Remove blower access panel (Fig. 6).
Limit switch is located on the fan deck.
Burner Ignition —
Unit is equipped with a direct spark
ignition 100% lockout system. Integrated Gas Unit Controller
(IGC) is located in the control box (Fig. 11). Module contains a
self-diagnostic LED (light-emitting diode). A single LED on
the IGC provides a visual display of operational or sequential
problems when the power supply is interrupted. When a break
in power occurs, the module will be reset (resulting in a loss of
fault history) and the indoor (evaporator) fan ON/OFF times
will be reset. For additional informa tion, refer to the Start-Up ,
Heating section on page 34. The LED error code can be observed through the viewport. During servicing refer to the label
on the control box cover or Table 25 for an explanation of LED
error code descriptions.
If lockout occurs, unit may be adjusted by interrupting pow-
*A 3-second pause exists between LED error code flashes. If more
than one error code exists, all applicable codes will be displayed in
numerical sequence.
†Indicates a code that is not an error. The unit will continue to oper-
ate when this code is displayed.
**Indicates internal processor fault and will reset itself in 1 hour.
Light-Emitting Diode
IMPORTANT: Refer to Troubleshooting Tables 26-30 for additional information.
Normal Operation
Hardware Failure
Evaporator Fan On/Off Delay Modified
Limit Switch Fault
Flame Sense Fault
4 Consecutive Limit Switch Faults
Ignition Lockout Fault
Induced-Draft Motor Fault
Rollout Switch Fault
Internal Control Fault
Temporary 1 hour automatic reset fault
39
Page 40
Main Burners —
Fig. 52 — Burner Section Details
Fig. 53 — Burner Tray Details
At the beginning of each heating season, inspect for deterioration, blockage due to corrosion or other causes. Observe the main burner flames and replace burners
if necessary .
When working on gas train, do not hit or plug orifice
spuds.
REMOVAL AND REPLACEMENT OF GAS TRAIN
(Fig. 52 and 53)
1. Shut off manual gas valve.
2. Shut off power to unit and tag disconnect.
3. Slide out burner section side panel (not shown).
4. Disconnect gas piping at unit gas valve.
5. Remove wires connected to gas valve. Mark each wire.
6. Remove wires from ignitor and sensor wires at the Integrated Gas Unit Controller (IGC).
7. Remove the 2 screws that attach the burner rack to the
vestibule plate.
8. Slide the burner tray out of the unit (Fig. 53).
9. To reinstall, reverse the procedure outlined above.
CLEANING AND ADJUSTMENT
1. Remove burner rack from unit as described in Removal
and Replacement of Gas Train section on this page.
2. Inspect burners; if dirty, remove burners from rack.
3. Using a soft brush, clean burners and cross-over port as
required.
4. Adjust spark gap. See Fig. 54.
5. Reinstall burners on rack.
6. Reinstall burner rack as described in Removal and Replacement of Gas Train section.
Replacement Parts —
A complete list of replacement
parts may be obtained from any Carrier distributor upon
request.
Integrated Gas Unit Controller
Light-Emitting Diode
TROUBLESHOOTING
Table 26 — LED Error Code Service Analysis
Loss of power to control module (IGC).Check 5- amp fuse on IGC, power to unit, 24-v circuit breaker,
High temperature limit switch is open.Check the operation of the indoor (evaporator) fan motor.
The IGC sensed flame that should not be
present.
Inadequate airflow to unit.Check operation of indoor (evaporator) fan motor and that supply-air
Unit unsuccessfully attempted ignition for
15 minutes.
IGC does not sense that induced-draft
motor is operating.
Rollout switch has opened.Rollout switch will automatically reset, but IGC will continue to
Microprocessor has sensed an error in
the software or hardware.
Stray radio frequency signals in ??Processor will be reset after 1 hour.
and transformer. Units without a 24-v circuit breaker have an
internal overload in the 24-v transformer. If the overload trips,
allow 10 minutes for automatic reset.
Ensure that the supply-air temperature rise is in accordance with
the range on the unit nameplate.
Reset unit. If problem persists, replace control board.
temperature rise agrees with range on unit nameplate information.
Check ignitor and flame sensor electrode spacing, gaps, etc.
Ensure that flame sense and ignition wires are properly terminated. Verify that unit is obtaining proper amount of gas.
Check for proper voltage. If motor is operating, check the
speed sensor plug/IGC Terminal J2 connection. Proper
connection: PIN 1— White, PIN 2 — Red, PIN 3 — Black.
lock out unit. Check gas valve operation. Ensure that induceddraft blower wheel is properly secured to motor shaft. Reset unit
at unit disconnect.
If error code is not cleared by resetting unit power, replace the
IGC.
IMPORTANT: Refer to Table 28 — Heating Service Troubleshooting for additional troubleshooting information.
If the IGC must be replaced, be sure to ground yourself to dissipate any electrical charge that may be present before handling
new control board. The IGC is sensitive to static electricity and
may be damaged if the necessary precautions are not taken.
42
Page 43
Table 27 — Cooling Service Troubleshooting
PROBLEMCAUSEREMEDY
Compressor and
condenser fan
will not start.
Compressor will not start
but condenser fan runs.
Compressor cycles (other than
normally satisfying thermostat).
Compressor operates continuously.
Excessive head pressure.
Head pressure too low.
Excessive suction pressure.
Suction pressure too low.
Compressor no. 2 will not run.
Compressor makes excessive
noise (48TF014 scroll only).
Power failure.Call power company.
Fuse blown or circuit breaker tripped.Replace fuse or reset circuit breaker.
Defective thermostat, contactor, transformer,
or control relay.
Insufficient line voltage.Determine cause and correct.
Incorrect or faulty wiring.Check wiring diagram and rewire correctly.
Thermostat setting too high.Lower thermostat setting below room temperature.
Faulty wiring or loose connections in com-
pressor circuit.
Compressor motor burned out, seized, or
internal overload open.
Defective run/start capacitor, overload, or
start relay.
One leg of 3-phase power dead.Replace fuse or reset circuit breaker. Determine
Refrigerant overcharge or undercharge.Recover refrigerant, evacuate system, and
Defective compressor.Replace and determine cause.
Insufficient line voltage.Determine cause and correct.
Blocked condenser.Determine cause and correct.
Defective run/start capacitor, overload, or
start relay.
Defective thermostat.Replace thermostat.
Faulty condenser-fan motor or capacitor.Replace.
Restriction in refrigerant system.Locate restriction and remove.
Dirty air filter.Replace filter.
Unit undersized for load.Decrease load or increase unit size.
Thermostat set too low.Reset thermostat.
Low refrigerant charge.Locate leak, repair, and recharge.
Leaking valves in compressor.Replace compressor.
Air in system.Recover refrigerant, evacuate system, and
Condenser coil dirty or restricted.Clean coil or remove restriction.
Dirty air filter.Replace filter.
Dirty condenser coil.Clean coil.
Refrigerant overcharged.Remove excess refrigerant.
Air in system.Recover refrigerant, evacuate system, and
Condenser air restricted or air short-cycling.Determine cause and correct.
Low refrigerant charge.Check for leaks, repair, and recharge.
Compressor valves leaking.Replace compressor.
Restriction in liquid tube.Remove restriction.
High heat load.Check for source and eliminate.
Compressor valves leaking.Replace compressor.
Refrigerant overcharged.Recover excess refrigerant.
Dirty air filter.Replace filter.
Low refrigerant charge.Check for leaks, repair, and recharge.
Metering device or low side restricted.Remove source of restriction.
Insufficient evaporator airflow.Increase air quantity. Check filter and replace if
Temperature too low in conditioned area.Reset thermostat.
Field-installed filter drier restricted.Replace.
Unit in economizer mode.Proper operation; no remedy necessary.
Compressor rotating in wrong direction.Reverse the 3-phase power load as described in
Replace component.
Check wiring and repair or replace.
Determine cause. Replace compressor.
Determine cause and replace.
cause.
recharge to nameplate.
Determine cause and replace.
recharge.
recharge.
necessary.
Start-Up, Compressor Rotation section on
page 34.
43
Page 44
Table 28 — Heating Service Troubleshooting
Burners will not
ignite.
Inadequate heating.Dirty air filter.Clean or replace filter as necessary.
Poor fl am e
characteristics.
Burners will notUnit is locked into Heating mode for aWait until mandatory one minute time period has
turn off.one minute minimum.elapsed or power to unit.
PROBLEMCAUSEREMEDY
Misaligned spark electrodes.Check flame ignition and sensor electrode positioning.
No gas at main burners.Check gas line for air purge as necessary. After purging
Water in gas line.Drain water and install drip leg to trap water.
No power to furnace.Check power supply, fuses, wiring, and circuit breaker.
No 24 v power supply to control circuit.Check transformer. Transformers with internal overcurrent
Miswired or loose connections.Check all wiring and wirenut connections.
Burned-out heat anticipator in thermostat.Replace thermostat.
Broken thermostat wires.Run continuity check. Replace wires, if necessary.
Gas input to unit too low.Check gas pressure at manifold. Clock gas meter for input. If too
Unit undersized for application.Replace with proper unit or add additional unit.
Restricted airflow.Clean filter, replace filter, or remove any restrictions.
Blower speed too low.Use high speed tap, increase fan speed, or install optional
Limit switch cycles main burners.Check rotation of blower, thermostat heat anticipator settings,
Too much outdoor air.Adjust minimum position.
Incomplete combustion (lack of Check all screws around flue outlets and burner compartment.
combustion air) results in:Tighten as necessary.
gas line of air, allow gas to dissipate for at least 5 minutes
before attempting to relight unit.
Check gas valve.
protection require a cool down period before resetting.
low, increase manifold pressure, or replace with correct orifices.
blower, as suitable for individual units.
and temperature rise of unit. Adjust as needed.
Check economizer operation.
Overfired unit — reduce input, change orifices, or adjust
gas line or manifold pressure.
Check vent for restriction. Clean as necessary.
Check orifice to burner alignment.
PROBLEMPOTENTIAL CAUSEREMEDY
Damper Does Not
Open
EconoMi$er
Operation Limited to
Minimum Position
Damper Position
Less than Minimum
Positi on Set Point
Damper Does Not
Return to Minimum
Positi on
Damper Does Not
Close on Power Loss
LEGEND
IFM —
PL —
Indoor Fan Motor
Plug
Table 29 — EconoMi$er Troubleshooting
Indoor (Evaporator) Fan is OffCheck to ensure that 24 vac is present at Terminal C1 (Common Power)
No Power to EconoMi$er ControllerCheck to ensure that 24 vac is present across Terminals 24 VAC and
No Power to G TerminalIf IFM is on, check to ensure 24 vac is present on G Terminal of the
Controller FaultIf STATUS light is flashing one flash, the EconoMi$er controller is
Thermostat FaultIf STATUS light is flashing two flashes, the EconoMi$er controller senses
Actuator FaultCheck the wiring between the EconoMi$er controller and the actuator.
Minimum Position Set IncorrectlyVerify that the MIN POS (%) is set greater than zero. Adjust MIN POS (%)
EconoMi$er Changeover Set Point Set Too
High or Too Low
Supply Air Temperature Sensor FaultyIf STATUS light is flashing 4 flashes, Supply Air Temperature Sensor is
Outdoor Air Temperature Sensor FaultyIf STATUS light is flashing 5 flashes, Outdoor Air Temperature Sensor is
Supply Air Low Limit Strategy ControllingThe supply-air temperature is less than 7 C (45 F), causing the minimum
CO
Ventilation Strategy ControllingIf a CO2 sensor is being used, and the damper position is greater than
2
Damper Travel is RestrictedCheck to ensure the damper is not blocked.
on the IFC (Indoor [Evaporator] Fan Contactor) or that 24 vac is present at
the IFO (Indoor [Evaporator] Fan On) terminal. Check whether 24 vac is
present at PL6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is not
present, check wiring (see unit label diagram).
Check proper thermostat connection to G on the connection board.
24 V COM on the EconoMi$er control. If 24 vac is not present, check wiring
(see unit label diagram). If 24 vac is present, STATUS light should be on
constantly.
EconoMi$er controller. If 24 vac is not present, check wiring (see unit
label diagram).
experiencing a fault condition. Cycle power to the controller. If condition
continues, replace the EconoMi$er controller.
the thermostat is wired incorrectly. Check wiring between the thermostat
and the connection board in the electrical panel. The fault condition is
caused by Y2 being energized before Y1.
Hold CONFIG button between 3 and 10 seconds to verify the
actuator’s operation. (This process takes 3 minutes to complete.)
to 100% to verify operation, and then set to correct setting.
Set at correct value. See Table 4.
faulty. Check wiring or replace sensor.
faulty. Check wiring or replace sensor.
position to be decreased. Refer to the Start-Up instructions. Verify correct
setting of MIN POS (%). If correct, EconoMi$er is operating correctly.
minimum position, the ventilation control strategy is controlling. Refer to
the Start-Up instructions. EconoMi$er is operating correctly.
44
Page 45
Table 30 — Durablade Economizer Troubleshooting
PROBLEMCAUSEREMEDY
Damper does not
open.
Economizer
operation
limited to minimum
position.
Damper does not
close.
Economizer damper
does not close on
power loss.
C1 —
EC —
IFC —
IFO —
Common Power
Enthalpy Control
Indoor (Evaporator) Fan Contactor
Indoor (Evaporator) Fan On
Indoor (evaporator) fan is off.1. Check to ensure that 24 vac is present at terminal C1 on the IFC or
No power to economizer motor.1. Check that SW3 is properly making contact with the damper
Economizer motor failure.If the indoor (evaporator) fan and economizer motor are energized,
OAT or EC set too high.1. Set at correct temperature (1.7 C [3 F] below indoor space
Verify economizer control board is
correctly wired and works properly.
Check SAT.1. After verifying that the OAT and EC settings and the economizer
Incorrect wiring of economizer.1. Verify that SW2 and SW4 are wired and working properly (see unit
Verify economizer control board is
functioning properly.
Check SAT.1. After verifying that the wiring is correct and the economizer control
Economizer motor failure.If economizer control board and SAT are functioning properly, verify
Verify that close-on-power-loss and
economizer control board are functioning properly.
LEGEND
OAT —
PL —
SAT —
SW —
that 24 vac is present at the IFO terminal. Check whether 24 vac is
present at PL6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is
not present, check wiring (see unit label diagram).
2. Check proper thermostat connection to G on the connection board.
blade. Check that SW1 is in the NC (normally closed) position.
2. Check diode D1. If diode is not functioning properly, replace D1.
3. Confirm that the economizer control board is grounded properly at
PL6-4 (brown wire) and at brown terminal of the economizer control
board (brown wire). The economizer motor must also be grounded
properly at the negative motor terminal (brown wire).
4. Verify SW1 and SW3 are working and wired properly (see unit label
diagram).
5. Check for 24 vac input at both PL6-1 (red wire) and PL6-3 (black
wire). If 24 vac not present, check unit wiring (see unit label diagram). If 24 vac is found in both places, check for 24 vac at the
yellow terminal of the economizer control board (yellow wire). If
24 vac power is not present, replace the economizer control board.
verify that there is a minimum of 18 vdc at the positive motor
terminal. If the motor is not operating, replace the motor.
temperature).
2. Check OAT or EC by setting above outdoor temperature or humidity
level. If the OAT or EC switches do not close, replace OAT or EC.
1. Perform the following tests when OAT or EC is closed, Y1 is called
for and damper is at minimum position. Confirm 24 vac on gray ter-
minal of the economizer control board (gray wire). If 24 vac is not
present, check wiring (see unit label diagram).
2. Verify that SW1 and SW3 are wired correctly and working properly
(see unit label diagram).
3. Check to ensure that 24 vac exists at PL6-2 (blue wire). If
24 vac is not present, check wiring (see unit wiring label diagram).
4. Check 24 vac output at PL6-10 (white wire). If 24 vac is not
present, replace economizer control board.
control board wiring are correct, check to ensure that the 24 vac
terminal of the SAT has 24 vac (white wire). If OAT, EC, and control
board are functioning and wired properly and no 24 vac exists,
check wiring (see unit label diagram).
2. If supply-air temperature is greater than 14 C (57 F), 24 vac should
be found at terminal T2 on the SAT (pink wire). If 24 vac is not
present, replace SAT.
label diagram).
2. Check diode D2. If diode is not functioning properly, replace D2.
1. After verifying that the wiring is correct, modulate the damper to the
minimum position. Remove the call for G (evaporator fan).
2. If the damper does not move, check for 24 vac at PL6-1 (red wire).
If 24 vac is not present, check wiring (see unit label diagram).
3. If damper still does not move, check for 24 vac at blue terminal of
economizer control board (blue wire). If 24 vac is not present,
replace the economizer circuit board.
board is functioning properly, place the OAT or EC switch in the
closed position. Place a call for Y1 and open the damper to the fully
open position. Confirm that the 24 vac terminal of the SAT has
24 vac (white wire). If 24 vac is not present, check wiring (see unit
label diagram).
2. If supply-air temperature is less than 11 C (52 F), 24 vac should be
found at terminal T1 on the SAT (violet wire). If 24 vac not found,
replace SAT.
that there is a minimum of 18 vdc at the positive motor terminal. If a
minimum if 18 vdc is present and the motor is still not operating,
replace the motor.
1. Check voltage potential across batteries. If lower than 14 vdc,
replace close-on-power-loss power supply (9-v alkaline batteries). It
is recommended that you check this emergency power supply on a
regular basis or whenever the filters are changed.
2. If the close-on-power-loss and economizer control board are functioning properly, check for 14 vdc or higher at the blue terminal of
the economizer control board (blue wire) when power is discon-
nected from unit. If 14 vdc is not present, replace the control board.
Outdoor-Air Thermostat
Plug
Supply-Air Thermostat
Economizer Position Switch
45
Page 46
AHA —
BR—
C—
CAP —
CB—
CC—
COMP —
CR—
D—
EC—
ECON —
EPS—
Adjustable Heat Anticipator
Blower Relay
Contactor, Compressor
Capacitor
Circuit Breaker
Cooling Compensator
Compressor Motor
Combustion Relay
Diode
Enthalpy Control
Economizer
Emergency Power Supply
(9-Volt Battery)
Equipmen t
Economizer Relay
Freeze-Up Protection Thermostat
Filter Status Sensor
Ground
Gas Valve Relay
High-Pressure Switch
Hall-Effect Sensor
Ignitor
Induced-Draft Motor
Indoor-Fan Contactor
Indoor Fan Motor
Integrated Gas Unit Controller
Low-Pressure Switch
Limit Switch
Main Gas Valve
Motor
Outdoor-Air Thermostat
Outdoor-Fan Motor
Plug
Plug Assembly
Quadruple Terminal
Relay
Rollout Switch
Supply-Air Thermostat
Sensor
Switch Fully Open
Switch Fully Closed
Switch Min. Vent Position
Switch Max. Vent Position
Thermostat-Cooling
Thermostat-Heating
Transformer
Field Splice
Marked Wire
Ter minal (Marked)
Terminal (Unmarked)
Ter minal B lock
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential
only. Not to represent wiring.
NOTES:
1. If any of the original wire fur nished must be replaced, it must be
replaced with Type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single phasing
conditions.
Thermostat: HH07AT170, 172, 174 and P272-2783
Subbase:HH93AZ176, 178 and P272-1882, 1883
3. Set heat anticipator for first stage at 0.14 amp, second stage at
0.2 amp, except for 008 low heat, set both first and second stage at
0.14 amp.
4. Use copper conductors only.
Fig. 55 — Typical Unit Wiring Schematic
Copyright 2001 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Ta b 1 a 6 a
Catalog No. 004-816Printed in U.S.A.Form 48TF-C1SIPg 461-01Replaces: New
Page 47
Page 48
START-UP CHECKLIST
(Remove and Store in Job File)
I. PRELIMINARY INFORMATION
MODEL NO.:________________________________SERIAL NO.: ___________________________________
DATE:______________________________________TECHNICIAN: __________________________________
JOB LOCATION: _______________________________
II. PRE-START-UP (insert checkmark in box as each item is completed)
VERIFY THA T ALL PACKING MA TERIALS HAVE BEEN REMOVED FROM UNIT
REMOVE ALL SHIPPING HOLDDOWN BOL TS AND BRACKETS PER INSTALLATION INSTRUCTIONS
VERIFY THA T CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
CHECK GAS PIPING FO R LEAKS
CHECK THAT INDOOR-AIR FILTERS ARE CLEAN AND IN PLACE
VERIFY THA T UNIT INSTALLA TION IS LEVEL
CHECK F AN WHEELS AND PROPELLERS FOR LOCA TION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS
AND DRIVE BELTS TENSION.
III. START-UP
ELECTRICAL
SUPPL Y VOLTAGEL1-L2L2-L3L3-L1
COMPRESSOR AMPSL1L2L3
COMPRESSOR AMPSL1L2L3
INDOOR-FAN AMPSL1L2L3