Carrier 48TF004-007 User Manual

Installation, Start-Up, and
Service Instructions
CONTENTS
Page
Step 1 — Provide Unit Support
•ROOF CURB
• SLAB MOUNT
Step 2 — Field Fabricate Ductwork Step 3 — In stall Exte rnal Trap for Condensate
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Drain
Step 4 — Rig and Place Unit
• POSITIONING
Step 5 — Install Flue Hood Step 6 — Install Gas Piping Step 7 — Make Electrical Connections
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
• HEA T ANTICIPATOR SETTINGS
Step 8 — Make Outdoor-Air Adjustments
and Install Outdoor-Air Hood
• MANUAL OUTDOOR-AIR DAMPER
• OPTIONAL DURABLADE ECONOMIZER
• OPTIONAL ECONOMI$ER
Step 9 — Adjust Evaporator-Fan Speed
• DIRECT-DRIVE MOTORS
• BELT-DRIVE MOTORS
ST ART-UP SERVICE TROUBLESHOOTING START-UP CHECKLIST
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-35
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36-38
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-43
. . . . . . . . . . . . . . . . . . . . . . . . . 44-49
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precau­tions in the li terature, tag s and labels attached to t he unit, and other safety precautions that apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
. . . . . . . . . . . . . . . . . . . . . . 1
. . . . . . . . . . . . . . . . . . . 1
. . . . . . . . . . . . . . . 2
. . . . . . . . . . . . . . . . . . . . . 2
. . . . . . . . . . . . . . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . . . . 4
. . . . . . . . . . . 8
. . . . . . . . . . . . . . . . . . 11
. . . . . . . . . 19
. . . . . . . . . . . . . . . . . . . . . . . .CL-1
48TF004-007
Single-Package Rooftop
Heating/Cooling Units
Disconnect gas piping from unit when leak testing at pressure greater than 1/2 psig. Pressures greater than 1/2 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pres­sure greater than replaced before use. When pressure testing field-supplied gas piping at pressures of
1
/2 psig or less, a unit connected to such piping must be isolated by manually cl osing the gas valve.
Before performing service or maintenance operations on unit, turn off main power switch to unit and install a lock­out tag. Electrical shock could cause personal injury.
INSTALLATION
Unit is shipped in the vertical duct configuration. To convert to horizontal configuration, remove screws from side duct opening covers and remove covers. Using the same screws, in­stall covers on vertical duct openings with the insulation-side down. Seals around duct openings must be tight. See Fig. 1.
Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.
Step 1 — Provide Unit Support
ROOF CURB — Assemb le and install accessor y roof cu rb in accordance with instructions shipped with curb. See Fig. 2. In­stall insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb, not to the unit. The
accessory thru-the-bottom power and gas connection package must be installed before the unit is set on the roof curb. If field-
installed (thru-the-roof curb) gas connections are desired, use factory-supplied mount the thru-the-roof curb connection to the roof curb. Gas connections and power connections to the unit must be field in­stalled after the unit is installed on the roof curb.
If electric and control wiring is to be routed through the basepan, attach the accessory thru-the-bottom service connec­tions to the basepan in accordance with the accessory installa­tion instructions.
3
/4-in. pipe coupling and gas plate assembly to
1
/2 psig, it must be
IMPORTANT: The gasketing of the unit to the roof curb
is critical for a watertight seal. Install gasket supplied
with the roof curb as shown in Fig. 2. Improperly
applied gasket can result in air leaks and poor unit
performance.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 1 a 6 a
PC 111 Catalog No. 534-80000 Printed in U.S.A. Form 48TF-1SI Pg 1 8-00 Replaces: New
Fig. 1 — Horizontal Conversion Panels
Curb should be level. Unit leveling tolerances are shown in Fig. 3. This is necessary for unit drain to function properly. Re­fer to Accessory Roof Curb Installation Instructions for addi­tional information as required.
SLAB MOUNT (Horizontal Units Only) — Provide a level concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow .
NOTE: Horizontal units may be installed on a roof curb if required.
Step 2 — Field Fabricate Ductwork —
Secure all ducts to roof curb and building structure on vertical ducted units. Do not connect ductwork to unit. For horizontal applica- tions, field-supplied flanges should be attached to horizontal duct openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be in-
sulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applica­ble fire codes.
A minimum clearance is not required around ductwork. Cabinet return air static shall not exceed –.20 in. wg with EconoMi$er, –.35 in. wg with Durablade economizer, or –.45 in. wg without economizer.
These units are designed for a minimum continuous heating return-air temperature of 50 F (dry bulb), or an intermittent op­eration down to 45 F (dry bulb), such as when used with a night set-back thermostat.
Step 3 — Install External Trap for Condensate Drain —
located on the bottom and side of the unit. Unit discharge con­nections do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications.
The unit’s 3/4-in. condensate drain connections are
When using the standard side drain connection, make sure the plug (Red) in the alternate bottom connection is tight before installing the unit.
To use the bottom drain connection for a roof curb installa­tion, relocate the factory-installed plug (Red) from the bottom connection to the side connection. See Fig. 4. The piping for the condensate drain and external trap can be completed after the unit is in place.
All units must have an external trap for condensate drain­age. Install a trap at least 4-in. deep and protect agai nst freez e­up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection (
Step 4 — Rig and Place Unit —
3
/4 in.).
Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a refer­ence. See Table 1 and Fig. 5 for additional information.
Lifting holes are provided in base rails as shown in Fig. 6.
Refer to rigging instructions on unit.
All panels must be in place when rigging.
POSI TION I NG — Maintain clearance around and above unit to provide minimum distance from combustible materials, proper airflow, and service access. See Fig. 6. A properly posi­tioned unit will have the following clearances between unit and roof curb:
1
/4-in. clearance between roof curb and base rails on each side and duct end of unit; 1/4-in. clearance between roof curb and condenser coil end of unit. (See Fig. 2, section C-C.)
Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contaminated air.
Be sure that unit is installed such that snow will not block
the combustion intake or flue outlet.
2
ROOF CURB
ACCESSORY
CRRFCURB001A00 CRRFCURB002A00
A UNIT SIZE
1-2 [356]
2-0 [610]
48TF004-007
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb, galvanized steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance: 4 ft on each side.
7. Direction of airflow.
8. Connector packages CR BTMPWR001A00 and 002A00 a re for thru-the­curb connections. Packages CRBTMPWR003A00 and 004A00 are for thru-the-bottom connections.
BC
11
1-9
/16″
[551]
1-4 [406]
D AL T
DRAIN
HOLE
13/4″
[44.5]
“E”
GAS
3
/4″
[19] NPT
1
/2″
[12.7] NPT
3
/4″
[19] NPT
“F”
POWER
3
/4″ [19] NPT)
1
1
/4″ [31.7] CRBTMPWR002A00
3
/4″ [19] NPT 11/4″ [31.7] CRBTMPWR004A00
“G”
CONTROL
1
/2″
[12.7]
1
/2″
[12.7]
CONNECTOR
PKG. ACCY.
CRBTMPWR001A00
CRBTMPWR003A00
3
Fig. 2 — Roof Curb Dimensions
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B B-C A-C
0.5 1.0 1.0
Fig. 3 — Unit Leveling Tolerances
OTE: Drain plug is shown in factory-installed position.
Fig. 4 — Condensate Drain Connection
Unit may be installed directly on wood flooring or on
Class A, B, or C roof-covering material when roof curb is used.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Flue vent discharge must have a minimum horizontal clear­ance of 4 ft from electric and gas meters, gas regulators, and gas relief equipment.
Minimum distance between unit and other electrically live parts is 48 inches.
Flue gas can deteriorate building materials. Orient unit such
that flue gas will not affect building materials.
Adequate combustion-air space must be provided for proper operation of this equipment. Be sure that installation complies with all local codes and Section 5.3, Air for Combustion and Ventilation, NFGC (National Fuel Gas Code), and ANSI (American National Standards Institute) Z223.1, and NFPA (National Fire Protection Association) 54 TIA-54-84-1. In Canada, installation must be in accordance with the CAN1-B149 installation codes for gas burning appliances.
After unit is in position, remove rigging skids and shipping materials.
Step 5 — Install Flue Hood —
Flue hood is shipped screwed to the basepan beside the burner compa rtment access panel. Remove from shipping location and using screws pro­vided, install flue hood and screen in location shown in Fig. 7.
Step 6 — Install Gas Piping —
Unit is equipped for use with type of gas shown on nameplate. Refer to local build­ing codes, or in the absence of local codes, to ANSI Z223.1 en­titled National Fuel Gas Code. In Canada, installation must be in accordance with the CAN1.B149.1 and CAN 1.B149.2 in­stallation codes for gas burning appliances.
For natural gas applications, gas pressure at unit gas con-
nection must not be less than 4 in. wg or greater than
13.0 in. wg while unit is operating. On 48TF005,006,007 high heat units, the gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13 in. wg while the unit is op­erating. For propane applications, the gas pressure must not be less than 5 in. wg or greater than 13 in. wg at the unit connection.
Size gas supply piping for 0.5 in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connection. Support gas piping as shown in the table in Fig. 8. For exam-
3
ple, a
/4-in. gas pipe must have one field-fabricated support beam every 8 ft. Therefore, an 18-ft long gas pipe would have a minimum of 2 support beams, a 48-ft long pipe would have a minimum of 6 support beams.
See Fig. 8 for typical pipe guide and locations of external
manual main shutoff valve.
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Hook rigging shackles thr ough holes in base rail, as shown in d etail “A.’ Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.
UNIT
48TFE,TFF,TFM,TFN004 510 231 48TFD,TFE,TFF ,TFL,TFM,TFN005 520 236 48TFD,TFE,TFF ,TFL,TFM,TFN006 540 245
48TFD,TFE,TFF007 615 279
MAX WEIGHT “A” “B” “C” Lb Kg in. mm in. mm in. mm
Fig. 5 — Rigging Details
3. Unit weights do not include economizer. See Table 1 for economizer weights.
All panels must be in place when rigging.
73.69 1872 37.50 953 33.35 845
4
Table 1 — Physical Data — 48TF004-007
UNIT SIZE 48TF E/F/M/N004 D/E/F/L/M/N005 D/E/F/L/M/N006 D/E/F007 NOMINAL CAPACITY (tons) 3456 OPERATING WEIGHT (lb)
Unit
Al/Al* 460 470 490 565 Al/Cu* 465 476 497 576 Cu/Cu* 468 482 505 587
Economizer
Durablade 34 34 34 34 EconoMi$er 47 47 47 47
Roof Curb† 115 115 115 115
COMPRESSOR Reciprocating
Quantity 1111 No. Cylinders (per Circuit) 2222 Oil (oz) 50 50 50 54
REFRIGERANT TYPE R-22
Expansion Device Acutrol™ Metering Device Operating Charge (lb-oz)
Circuit 1 4-4 6-6 6-14 9-0 Circuit 2 ————
CONDENSER COIL Enhanced Copper Tubes, Aluminum Lanced Fins
Rows...Fins/in. 1...17 2...17 2...17 2...17 Total Face Area (sq ft) 8.36 8.36 10.42 10.42
CONDENSER FAN Propeller Type
Nominal Cfm 3500 4000 4000 4000 Quantity...Diameter (in.) 1...22.0 1...22.0 1...22.0 1...22.0 Motor Hp...Rpm Watts Input (Total) 325 325 325 325
EVAPORATOR COIL Enhanced Copper Tubes, Aluminum Double-Wavy Fins
Rows...Fins/in. 2...15 2...15 3...15 4...15 Total Face Area (sq ft) 4.17 5.5 5.5 5.5
EVAPORATOR FAN Centrifugal Type
Quantity...Size (in.) Std 1...10 x 10 1...10 x 10 1...11 x 10 1...10 x 10
Type Drive Std Direct Direct Direct Belt
Nominal Cfm 1200 1600 2000 2400 Maximum Co ntinuous Bhp Std .34 .75 1.20 2.40
Motor Frame Size Std 48 48 48 56
Nominal Rpm High/Low Std 860/800 1075/970 1075/970
Fan Rpm Range Std 1070-1460
Motor Bearing Type Ball Ball Ball Ball Maximum Allowable Rpm 2100 2100 2100 2100 Motor Pulley Pitch Diameter Min/Max (in.) Std 2.8/3.8
Nominal Motor Shaft Diameter (in.) Std
Fan Pulley Pitch Diameter (in.) Std ———4.5
Belt, Quantity...Type...Length (in.) Std 1...A...40
Pulley Center Line Dis tance (in.) Std 14.7-15.5
Speed Change per Full Turn of Std ———80
Movable Pulley Flange (rpm) Alt 48 70 80
Movable Pulley Maximum Full Turns Std ——— 5
From Closed Position Alt 555—
Factory Setting Std ——— 3
Factory Speed Setting (rpm) Std ———1225
Fan Shaft Diameter at Pulley (in.)
Alt 1...10 x 10 1...10 x 10 1...10 x 10 High-Static 1...10 x 10 1...10 x 10 1...11 x 10 1...10 x 10
Alt Belt Belt Belt High-Static Belt Belt Belt Belt
Alt 1.00 1.00 1.30/2.40** High-Static 2.40 2.40 2.90 2.90
Alt 48 48 56 High-Static 56 56 56 56
Alt 1620 1620 1725 High-Static 1725 1725 1725 1725
Alt 760-1000 835-1185 900-1300 High-Static 1075-1455 1075-1455 1300-168 5 1300-1685
Alt 1.9/2.9 1.9/2.9 2.4/3.4 High-Static 2.8/3.8 2.8/3.8 3.4/4.4 3.4/4.4
Alt High-Static
Alt 4.5 4.0 4.5 High-Static 4.5 4.5 4.5 4.5
Alt 1...A...34 1...A...34 1...A...39 High-Static 1...A...39 1...A...39 1...A...40 1...A...40
Alt 10.0-12.4 10.0-12.4 14.7-15.5 High-Static 10.0-12.4 10.0-12.4 14.7-15.5 14.7-15.5
High-Static 65 65 60 60
High-Static 6655 Alt 333—
High-Static 3 Alt 856 975 1060
High-Static 1233 1233 1396 1396
LEGEND
Al Aluminum Bhp — Brake Horsepower Cu — Copper
*Evaporator coil fin material/co ndenser coil fin material. Cont act your local
representative for details about coated fins.
†Weight of 14-in. roof curb.
**Single phase/three-phase.
1
/4...1100
1
/
1
/
5
/
1
5
/
1
/4...1100
1
31/
/
2
1
/
2
5
/
8
2
5
/
8
2 2 8
/
2
8
††Rollout switch lockout is manually reset by interrupting power to unit or
resetting thermostat.
|| Single- phase unit s have a single-st age gas valve. The heating in put values
are as follows:
48TFF004, 115,000 Btuh 48TFF005, 150,000 Btuh 48TFF006, 150,000 Btuh
1
/4...1100
1
/
5
/
5
/
31/
5
/
2 8 8
2
8
NOTE: High-static motor not available on single-phase units.
Scroll
1
/4...1100
5
/
5
/
31/
5
/
8
8
2
8
5
Table 1 — Physical Data — 48TF004-007 (cont)
UNIT SIZE 48TF E/F/M/N004 D/E/F/L/M/N005 D/E/F/L/M/N006 D/E/F007 FURNACE SECTION
Rollout Switch Cutout Temp (F)†† 195 195 195 195 Burner Orifice Diameter
(in. ...drill size)
Natural Gas Std TFD .113...33 .113...33 .113...33
Liquid Propane Alt TFD .089...43 .089...43 .089...43
Thermostat Heat Anticipator Setting (amps)
208/230 v and 575 Stage 1 .14 .14 .14 .14 460 v Stage 1 .14 .14 .14 .14
Gas Input (B tuh)|| Stage 1 TFD 72,000 72,000 72,000
Efficiency (Steady
State) (%) 80 80 80 80
Temperature Rise Range TFD 25-55 25-55 25-55
Manifold Pressure (in. wg)
Natural Gas Std 3.5 3.5 3.5 3.5 Liquid Propane Alt 3.5 3.5 3.5 3.5
Gas Valve Quantity 1111 Gas Valve Pressure Range
Psig 0.180-0.487 0.180-0.487 0.180-0.487 0.180-0.487 in. wg 5.0-13.5 5.0-13.5 5.0-13.5 5.0-13.5
Field Gas Connection Size (in.)
HIGH-PRESSURE SWITCH (psig)
Standard Com p ressor 450 ± 50 500 ± 50 Internal Relief (Differential) Cutout 428 428 Reset (Auto.) 320 320
LOSS-OF-CHARGE (LOW­PRESSURE SWITCH) (psig)
Cutout Reset (Auto.) 22 ± 7
FREEZE PROTECTION THERMOSTAT (F)
Opens 30 ± 5 Closes 45 ± 5
OUTDOOR-AIR INLET SCREENS Cleanable
Quantity...Size (in.) 1...20 x 24 x 1
RETURN-AIR FILTERS Throwaway
Quantity...Size (in.) 2...16 x 25 x 2
Stage 2 .14 .14 .14 .14 Stage 2 .14 .14 .14 .14
Stage 2 (3-phase units)
LEGEND
Al Aluminum Bhp — Brake Horsepower Cu — Copper
*Evaporator coil fin material/co ndenser coil fin material. Cont act your local
representative for details about coated fins.
†Weight of 14-in. roof curb.
**Single phase/three-phase.
TFE .113...33 .113...33 .113...33 .113...33 TFF .113...33 .129...30 .129...30 .129...30 TFL .102...38 .102...38 TFM .102...38 .102...38 .102...38 TFN .102...38 .116...32 .116...32
TFE .089...43 .089...43 .089...43 .089...43 TFF .089...43 .102...38 .102...38 .102...38 TFL .082...45 .082...45 TFM .082...45 .082...45 .082...45 TFN .082...45 .089...43 .089...43
TFE 72,000 115,000 115,00 0 115,000 TFF 82,000 120 ,000 120,000 120,000 TFL 60,000 60,000 TFM 60,000 90,000 90,000 TFN 90,000 120,000 120,000
TFF 115,000 150,000 150,000 150,000
TFE 25-55 35-65 35-65 35-65 TFF 55-85 50-80 50-80 50-80 TFL 20-50 20-50 TFM 20-50 30-60 30-60 TFN 30-60 40-70 40-70
1
/
2
1
/
2
1
/
2
1
/
2
7 ± 3
††Rollout switch lockout is manually reset by interrupting power to unit or
resetting thermostat.
|| Single-phase units have a single-stage gas valve. The heating input values
are as follows:
48TFF004, 115,000 Btuh 48TFF005, 150,000 Btuh 48TFF006, 150,000 Btuh
NOTE: High-static motor not available on single-phase units.
6
STD UNIT
UNIT
48TFN,TFM,TFF,TFE004 48TFN,TFM,TFL,TFF,TFE,TFD005 48TFN,TFM,TFL,TFF,TFE,TFD006
48TFF,TFE,TFD007
CONNECTION SIZES
3
1
/
Dia. [35] Field Power Supply Hole
A B C D E F
NOTES:
1. Dimen s ions in [ ] are in millimeters.
8
2″ Dia. [51] Power Supply Knockout
1
/
2
Dia. [64] Power Supply Knockout
2
7
/
Dia. [22] Field Control Wiring Hole
8
3
/
-14 NPT Condensate Drain
4
1
/
-14 NPT Gas Connection
2
WEIGHT
Lbs Kg Lbs Kg Lbs Kg Lbs Kg Lbs Kg Lbs Kg Lbs Kg
460 209 470 213 142 64.4 106 48.1 162 73.5 60 27.2 1′-10 490 222 150 68.0 115 52.2 160 72.6 65 29.5 1′-0 565 256 165 74.8 136 61.7 200 90.7 64 29.0 1′-0
2. Center of Gravity.
3. Direction of Airflow.
4. On vertical discharge units, ductwork to be attached to accessory roof curb only. For horizontal discharge units, field-supplied flanges should be attached to horizontal discharge openings, and all duct­work should be attached to the flanges.
5. Minimum clearance (local codes or jurisdiction may prevail): a. Between unit, flue side and combustible surfaces, 36 inches. b. Bottom of unit to combustible surfaces (when not using curb)
1 inch. Bottom of base rail to combustible surfaces (when not using curb) 0 inches.
c. C ondenser coil for proper airflow, 36 in. one side, 12 in. the other.
The side getting the greater clearance is optional. d. Overhead, 60 in. to assure proper condenser fan operation. e. Between units, control box side, 42 in. per NEC (National Electri-
7
cal Code). f. Between unit and ungrounded surfaces, control box side, 36 in.
per NEC. g. Between unit and block or concrete walls and other grounded sur-
faces, control box side, 42 in. per NEC. h. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser coil and com­bustion side as stated in Note 5a, b, and c, a removable fence or bar­ricade requires no clearance.
7. Units may be installed on combustible floors made from wood or Class A, B, or C roof covering material if set on base rail.
8. The vertical center of gravity is 1′-6″ [457] up from the bottom of the base rail.
DURABLADE
ECONOMIZER WEIGHT
ECONOMI$ER
WEIGHT
34 15.4 47 21.3
(A)
CORNER WEIGHT
(B)
CORNER WEIGHT
(C)
CORNER WEIGHT
(D)
CORNER WEIGHT
140 63.5 105 47.6 159 72.1 56 25.4 1′-10
“A”
PANEL
LENGTH
3
/
[568.0]
8
3
/
[568.0]
8
3
/
[315.0]
8
3
/
[315.0]
8
BOTTOM POWER CHART,
THESE HOLES REQ’D FOR USE
WITH ACCESSORY PACKAGES —
CRBTMPWR001A00, 3A00 (
THREADED
CONDUIT
SIZE
1
/
2
3
/
4
1
FPT
/
2
WIRE
USE
24 V
Power 1
Gas 1
1
/2″, 3/4″)
REQ’D HOLE
SIZES (Max.)
7
/
8
1
/
8
1
/
4
[22.2]
[28.4]
[31.8]
Fig. 6 — Base Unit Dimensions
Step 7 — Make Electrical Connections
BLOWER ACCESS PANEL
LEGEND
NFGC —
National Fuel Gas Code *Field supplied. NOTE: Follow all local codes.
SPACING OF SUPPORTS
Fig. 8 — Gas Piping Guide (With Accessory
Thru-the-Curb Service Connections)
STEEL PIPE
NOMINAL DIAMETER
(in.)
X
DIMENSIONS
(feet)
1
/
2
6
3
/4 or 1
8
11/4 or larger
10
Fig. 7 — Flue Hood Details
Unit cabinet must have an uninterrupted, unbroken electri­cal ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control com­partment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA, latest edition, and local electrical codes. Do not use gas piping as an electrical ground. Fail- ure to follow this warning could result in the installer being liable for personal injury of others.
FIELD POWER SUPPLY — All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power sup­ply, the transformer must be rewired by moving the black wire with the nection and moving to the 200-volt primary side of the transformer.
tails are provided for field wire connections. Use factory­supplied splices or UL (Underwriters’ Laboratories) approved copper/aluminum connector .
requirements. Install field wiring as follows:
within voltage range indicated on unit nameplate (see Table 2). On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in the legend for Table 2, Note 2 to determine the percent of voltage imbalance. Operation on improper line voltage or ex­cessive phase imbalance constitutes abuse and may cause dam­age to electrical components. Such operation would invalidate any applicable Carrier warranty.
FIELD CO NTROL WIRING — Install a Carrier-approved accessory thermostat assembly according to installation instructions included with the acc essory. Locate thermostat as­sembly on a solid wall in the conditioned space to sense ave r­age temperature in accordanc e with thermostat ins tallation in­structions. Connect thermostat wires to terminal board.
wire from subbase terminals through connector on unit to low­voltage connections (shown in Fig. 10).
NOTE: For wire runs up 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to
1
/4-in. female space connector from the 230-volt con-
1
/4-in. male terminal on the
Refer to unit label diagram for additional information. Pig-
When installing units, provide a disconnect per the NEC. All field wiring must comply with NEC and local
1. Install conduit through side panel openings. For units without electric heat, install conduit between disconnect and control box.
2. Install power lines to terminal connections as shown in Fig. 9.
Voltage to compressor terminals during operation must be
Route thermostat cable or equivalent single leads of colored
the thermostat and will require a junction box and splice at the thermostat.
Pass the control wires through the hole provided in the cor­ner post; then feed wires through the raceway built into the corner post to the 24-v barrier located on the left side of the control box. See Fig. 11. The raceway provides the UL re­quired clearance between high- and low-voltage wiring.
HEAT ANTICIPATOR SETTINGS — Set heat anticipator settings at .14 amp for the first stage and .14 amp for second­stage heating, when available.
8
RACEWAY LOW VOLTAGE
CONNECTIONS
INTEGRATED GAS UNIT CONTROLLER (IGC)
HOLE IN END PANEL (HIDDEN)
208/230-1-60
208/230-3-60
460-3-60
(SIZE 007 ONLY)
LEGEND
C— COMP — NEC — TB
575-3-60
(SIZE 007 ONLY)
Contactor Compressor National Electrical Code Terminal Block
208/230-3-60
575-3-60, 460-3-60
(SIZES 004-006)
Fig. 9 — Power Wiring Connections
AHA
NOTES:
1. Connect Y2 when unit is equipped with an economizer.
2. Connect W2 when unit is equipped with two stages of heat.
Adjustable Heat Anticipator Field Wiring Factory Wiring
Fig. 10 — Low-Voltage Connections
LEGEND
Fig. 11 — Field Control Wiring Raceway
9
Table 2 — Electrical Data
UNIT 48TF
NOMINAL
V-Ph-Hz
208/230-1-60
VOLTAGE
IFM
TYPE
RANGE
Min Max RLA LRA Qty Hp FLA MCA MOCP† FLA LRA
Std
187 254 16.2 96.0 1
Alt 4.9 26.6/26.6 35/35 26/26 111/111
COMPRESSOR
(ea)
Std
208/230-3-60
187 254 10.2 75.0 1
Alt 4.9 19.1/19.1 25/25 19/19 90/90
High 5.2 19.4/19.4 25/25 19/19 109/109
004
460-3-60
Std
Alt 2.1 8.4 15 8 48/48
414 508 4.4 40.0 1
High 2.6 8.9 15 9 57/57
Std
575-3-60
Alt 2.1 6.9 15 8 37
518 632 3.7 31.0 1
High 2.6 7.3 15 7 45
208/230-1-60
Std
187 254 23.3 118.0 1
Alt 4.9 35.4/35.4 45/45 34/34 133/133
Std
208/230-3-60
187 254 15.4 90.0 1
Alt 4.9 25.6/25.6 30/30 25/25 105/105
High 5.2 25.9/25.9 30/30 25/25 124/124
005
460-3-60
Std
Alt 2.1 13.3 20 13 53
414 508 8.3 45.0 1
High 2.6 13.8 20 13 62
Std
575-3-60
Alt 2.1 10.3 15 11 42
518 632 6.4 36.0 1
High 2.6 10.7 15 10 50
208/230-1-60
Std
187 254 28.8 147 1
Alt 6.6 44.0/44.0 60/60 42/42 184/184
Std
208/230-3-60
187 254 16.3 114 1
Alt 5.2 26.6/26.6 35/35 26/26 148/148
High 7.5 28.9/28.9 35/35 29/29 174/174
006
460-3-60
Std
Alt 2.6 12.7 15 12 81
414 508 7.4 64 1
High 3.4 13.5 20 13 94
Std
575-3-60
Alt 3.0 10.5 15 10 66
518 632 6.2 62 1
High 3.4 12.6 15 11 76
Std
187 254 23.6 146 1
High 7.5 32.5/32.5 40/40 32/32 205/205
Std
414 508 10.6 73 1
High 3.4 16.1 20 16 103
Std
518 632 8.5 58.4 1
High 3.4 12.9 20 14 82
007
208/230-3-60
460-3-60
575-3-60
LEGEND
FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM Indoor (Evaporator) Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor (Condenser) Fan Motor RLA — Rated Load Amps
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for th e uni t sha ll be f use o r HA CR br eak er. Canadian units may be fuse or circuit breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
of voltage imbalance.
Use the following formula to determine the percent
% Voltage Imbalance
= 100 x
max voltage dev i ation from average voltage
average voltage
OFM
(ea)
1
/41.4
1
/41.4
1
/40.8
1
/40.8
1
/41.4
1
/41.4
1
/40.8
1
/40.8
1
/41.4
1
/41.4
1
/40.8
1
/40.8
1
/41.4
1
/40.6
1
/40.6
IFM
FLA
3.5
3.5
COMBUSTION
FAN MOTOR
FLA
.6
POWER SUPPLY
24.5/24.5 30/30 23/23 106/106
17.7/17.7 25/25 17/17 85/85
DISCONNECT
SIZE*
.6
1.3
7.6 15 7 48/48
.3
1.3
6.3 15 7 35
.3
3.5
3.5
.6
34.0/34.0 40/40 32/32 129/129
24.2/24.2 30/30 23/23 101/101
.6
1.8
13.0 20 13 51
.3
1.8
10.1 15 10 41
.3
5.9
5.9
.6
43.3/43.3 60/60 42/42 161/161
27.3/27.3 35/35 29/29 128/128
.6
3.1
13.2 20 13 72
.3
3.1
10.9 15 11 58
.3
5.2
2.6
2.6
.6
.3
.3
30.2/30.2 35/35 29/29 180/180
15.4 20 15 90
12.3 15 13 72
Example: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
Determi ne maximum deviation from average volt ag e.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v
452 + 464 + 455
1371
=
3
= 457
3
Maximum deviation is 7 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
7
457
= 1.53%
This amount of phase imbalance is satis f act ory as it is below t he max­imum allowable 2%.
IMPORTANT:
than 2%, contact your loca l electric utility company immediately.
If the supply voltage phase imbalance is more
10
Step 8 — Make Outdoor-Air Adjustments and
Fig. 14 — Outdoor-Air Damper with
Hood Att ached
Fig. 15 — Position Setting
Install Outdoor-Air Hood
MANUAL OUTDOOR-AIR DAMPER — The outdoor-air hood and screen are attached to the basepan at the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for building. Record amount for use in Step 8.
2. Remove and save outdoor air opening panel and screws. See Fig. 12.
3. Separate hood and screen from basepan by removing the 4 screws securing them. Save all screws.
4. Replace evaporator coil access panel.
OUTDOOR AIR OPENING PANEL
3 SCREWS (SIDE)
5. Place hood on front of outdoor air opening panel. See Fig. 13 for hood details. Secure top of hood with the 4 screws removed in Step 3. See Fig. 14.
6. Remove and save 6 screws (3 on each side) from sides of the manual outdoor-air damper.
7. Align screw holes on hood with screw holes on side of manual outdoor-air damper. See Fig. 13 and 14. Secure hood with 6 screws from Step 6.
8. Adjust minimum position setting of the damper blade by adjusting the manual outdoor-air adjustment screws on the front of the damper blade. See Fig. 12. Slide blade vertically until it is in the appropriate position determined by Fig. 15. Tighten screws.
9. Remove and save screws currently on sides of hood. In­sert screen. Secure screen to hood using the screws. See Fig. 14.
Fig. 12 — Damper Panel with Manual Outdoor-Air
Damper Installed
Fig. 13 — Outdoor-Air Hood Details
11
OPTIONAL DURABLADE ECONOMIZER — The op-
Fig. 16 — Typical Access Panel Locations
Fig. 17 — Outdoor-Air Hood Details
Fig. 18 — Horizontal Durablade Economizer
Installation
tional economizer hood assembly is packaged and shipped in the filter section. Damper blades and control boards are in­stalled at the factory and the economizer is shipped in the verti­cal discharge position.
NOTE: Horizontal discharge block-off plate is shipped with the air hood package. If unit is to be used for vertical discharge application, discard this plate.
Assembly:
1. Determine if ventilation air is required in building. If so, determine minimum amount to be supplied by each unit and record quantity of ventilation air needed for use in Step 6.
2. Remove filter access panel by raising panel and swinging panel outward. Panel is now disengaged from track and can be removed. No tools are required to remove filter access panel. Remove outdoor-air opening panel. Save panels and screws. See Fig. 16. Remove optional outdoor-air damper hood package from filter section.
3. Assemble outdoor-air hood top and side plates as shown in Fig. 17. Install seal strips on hood top and sides. Put aside screen retainer and screws for later assembly. Do
not attach hood to unit at this time.
4. To convert to horizontal discharge application: a. Rotate economizer 90 degrees until the
economizer motor faces the condenser section (see Fig. 18).
b. Rotate the barometric relief damper hinge
90 degrees. Barometric relief damper should open vertically to operate properly.
c. Install horizontal discharge block-off plate over
the opening on the access panel. (Block-off plate MUST be installed before installing hood assem­bly.) See Fig. 19.
5. Insert economizer plug into economizer harness. Remove tape from barometric relief damper. See Fig. 20.
6. If ventilation air is not required, proceed to St ep 7. If ven­tilation air is required, determine minimum position set­ting for required airflow. See Fig. 21. Adjust minimum position setting by adjusting the screws on the position setting bracket. Slide bracket until the top screw is in the position determined by Fig. 21. Tighten screws.
7. Remove tape from outdoor-air thermostat (OAT). Fasten OAT to inside of hood using screws and speed c lips pro­vided. See Fig. 22. Make sure OAT terminals are posi­tioned up.
8. Replace outdoor-air opening panel using screws from Step 2. Replace filter a ccess panel. Ensure the filter ac ­cess panel slides along the tracks and is securely engaged.
9. Fasten hood top and side plate assembly (Fig. 17) to outdoor-air opening panel with screws provided.
10. Place knob supplied with economizer on OAT. See Fig. 22. Set for 3° F below indoor room thermostat set­ting. If accessory enthalpy control (EC) is used in place of OAT, see instructions shipped with EC for installation and adjustment. See Fig. 22.
11. Connect OAT per Fig. 23.
12. Slide outdoor-air inlet screen into screen track on hood side plate. While holding screen in place, fasten screen re­tainer to hood using screws provided.
NOTE: Refer to Fig. 24 for economizer barometric relief damper characteristics.
ECONOMIZER CONTROL BOARD
BAROMETRIC RELIEF DAMPER
ECONOMIZER PLUG
SHIPPING SCREW
ECONOMIZER MOTOR
12
BLOCK-OFF PLATE
MINIMUM
POSITION
OPEN
3
1
T
P
P1
T1
4
2
5
S
S
O
D
C
TR
B
REV.B
198818A
%
H
U
M
I
D
I
T
Y
90
70
60
30
10
D C
B A
60 65 70
75
55
50
85
80
DAMPER
DAMPER
CLOSED
OPEN
OUTDOOR TEMP
.
°
F
REV
.
97-3672
CW–SETPOINTS–CCW
CONT
A CTS SHO
WN IN HIGH ENTHALPY
RUSH
AT 24V
AC
3 mA
MIN. A
T 1
1 VDC
CONT
ACT RA
TINGS: 1.5A
RUN, 3.5A IN
OR UNPOWERED ST
A TE
1
2
3
TR
TR1
24V
AC
ENTHALPY CONTROL
ENTHALPY CONTROL
HOOD
Fig. 22 — Outdoor-Air Thermostat/
Enthalpy Control Installation
Fig. 19 — Horizontal Discharge Block-Off Plate
U-SHAPED HOLE (NOT SHOWN)
ECONOMIZER CONTROL BOARD
ECONOMIZER PLUG
WIRING HARNESS
BAROMETRIC RELIEF DAMPER
SHIPPING SCREW
ECONOMIZER MOTOR
POSITION SETTING BRACKET
TOP SCREW
Fig. 20 — Durablade Economizer Installed in Unit
EXAMPLE:
Given —Negative Pressure. . . . . . . . . . . . . . . . . . . . . . .0.2 in. wg
Determine — Setting = 5 in.
Outdoor Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 900 cfm
Fig. 21 — Durablade Economizer
Minimum Position Setting
13
OUTDOOR AIR OPENING PANEL
SEAL STRIP
EXHAUST AIR SCREEN
EXHAUST AIR HOOD TOP
SCREEN RETAINER
EXHAUST AIR HOOD SIDES
EXHAUST AIR BOTTOM BRACKET
Fig. 26 — Typical Access Panel Locations
Fig. 27 — Exhaust Air Hood Assembly
LEGEND
Outdoor-Air Thermostat
OAT —
NOTE: See unit wiring diagram for details.
Fig. 23 — Wiring Connections for
Outdoor-Air Thermostat
ECONOMI$ER PLUG
CONTROLLER
GEAR-DRIVEN DAMPER
OUTDOOR AIR TEMPERATURE SENSOR
ACTUATOR
0.90
0.80
0.70
0.60
0.50
0.40
0.30
PRESSURE DROP (in. wg)
0.20
0.10
0.00
200 300 400
100
CFM
Fig. 24 — Durablade Economizer
Barometric Relief Damper Characteristics
OPTIONAL ECONOMI$ER — See Fig. 25 for EconoMi$er component locations.
1. To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. Remove the indoor coil access panel and discard. See Fig. 26.
If installing an optional Power Exhaust Assembly, refer to the EconoMi$er Power Exhaust Installation Instructions.
Controller should be mounted in vertical position as shown in Fig. 25.
2. Assemble the hood assembly as follows: Remove the EconoMi$er hood from its packaging. Re-
move shipping brackets holding hood package to EconoMi$er. Locate the outdoor-air opening panel. See Fig. 27. Remove hood assembly shipping brackets locat­ed on the back (sloped) side of the EconoMi$er assembly. These brackets are used to retain the hood assembly dur­ing shipping only.
3. Installs the side panels and the bottom bracket. Assemble the exhaust
1
/8 x 3/4-in. seal strip on the exhaust air hood
air hood to the outdoor-air opening panel as shown in Fig. 27, using the screws provided. Do not attach hood assembly to unit at this time.
4. Install the top and side panels. Assemble the outdoor-air hood to the outdoor-air opening panel as shown in Fig. 28, using the screws provided. Do not attach hood assembly to the uni t
1
/8 x 3/4-in. seal strip on the outdoor-air hood
at this time.
500 600
700
800
BAROMETRIC RELIEF DAMPERS
Fig. 25 — EconoMi$er Component Locations
OUTDOOR-AIR OPENING PANEL
FILTER ACCESS PANEL
14
5. Slide the outdoor-air inlet screens into the screen track on
ECONOMI$ER
ECONOMI$ER REAR FLANGE
UNIT BASE
UNIT FILTER RACK
ECONOMI$ER CLIP HVAC UNIT
WIRING HARNESS
OUTDOOR AIR BLOCK-OFF PLATE
Fig. 29 — Completed Hood Assembly
Fig. 30 — Rear EconoMi$er Flange Installation
Fig. 31 — EconoMi$er Installed
the hood side panels. While holding the screens in place, fasten the screen retainer to the hood using the screws provided. Repeat the process for the barometric exhaust air screen. Do not attach completed (Fig. 29) hood as- sembly to unit at this time .
6. Slide the EconoMi$er assembly into the rooftop uni t. S ee Fig. 30 and 31.
NOTE: Be sure to engage rear EconoMi$er flange under tabs in return-air opening of the unit base. See Fig. 30.
7. Install the outdoor-air block-off plate, then secure the EconoMi$er with the screws provided. See Fig. 31.
8. Remove and discard the 12-pin jumper pl ug from the unit wiring harness located in the upper left corner and insert the EconoMi$er plug into the unit wiring harness. Refer to wiring diagram Fig. 32 and 33. Also refer to Fig. 34 if installing an accessory power exhaust.
9. Install the complete hood assembly on the unit and secure using the screws provided.
10. Remove the indoor fan motor access panel. See Fig. 35.
11. Mount the supply-air temperature sensor to the lower left portion of the indoor blower housing with the two (2) screws provided (see Fig. 36). Connect the violet and pink wires to the corresponding connections on the supply-air temperature sensor. Replace the indoor fan motor access panel.
OUTDOOR AIR OPENING PANEL
ASSEMBLED EXHAUST HOOD
SEAL STRIP
SEAL STRIP
OUTDOOR AIR HOOD SIDES
Fig. 28 — Outdoor-Air Hood Assembly
OUTDOOR AIR HOOD TOP
SCREEN RETAINER
OUTDOOR AIR INLET SCREENS
15
OAT — RAT —
LEGEND
Outdoor-Air Tem perature Return-Air T emper ature
Fig. 32 — EconoMi$er Wiring
ECONOMI$ER CONTROLLER
OAT
COM
OAH
-15 V RAT
COM
RAH
+15 V
(+)
CO
2
COM
CO
2
DAT
COM
REM POT
COM
LED
COM
BROWN VIOLET
WHITE
RED
BROWN VIOLET
WHITE RED
SUPPLY AIR
TEMPERATURE SENSOR
PINK VIOLET
TEMP
TEMP
TEMP
TEMP
COM OUT PWR
TEMP TEMP COM
OUT PWR
CO
SENSOR
2
V+
COM VAC
OUTDOOR AIR SENSOR
RETURN AIR SENSOR
24
Fig. 33 — EconoMi$er Sensor Wiring
16
Loading...
+ 36 hidden pages