48TC*D08---D14
Nominal 7.5 to 12.5 Tons
Wit h Puro n (R---410A) Refrigerant
Service and Maintenance Instructions
TABLE OF CONTENTS
SAFETY CONSIDERA TIONS1....................
UNIT ARRANGEMENT AND ACCESS2...........
SUPPLY FAN (BLOWER) SECTION4..............
COOLING6....................................
PURONR (R--410A) REFRIGERANT8..............
COOLING CHARGING CHARTS10................
CONVENIENCE OUTLETS16....................
SMOKE DETECTORS17.........................
PROTECTIVE DEVICES24.......................
GAS HEATING SYSTEM25......................
CONDENSER COIL SERVICE35..................
PREMIERLINKt CONTROL36...................
RTU--MP CONTROL SYSTEM44..................
ECONOMI$ER SYSTEMS57......................
WIRING DIAGRAMS66.........................
PRE--START--UP69..............................
START--UP , GENERAL69........................
START--UP , PREMIERLINK CONTROL71..........
START--UP , RTU--MP CONTROL71................
OPERATING SEQUENCES75.....................
FASTENER TORQUE VALUES85.................
APPENDIX I. MODEL NUMBER SIGNIFICANCE87.
APPENDIX II. PHYSICAL DATA88................
APPENDIX III. FAN PERFORMANCE90...........
APPENDIX IV. WIRING DIAGRAM LIST96........
APPENDIX V. MOTORMASTER SENSOR
LOCATIONS97.................................
UNIT START-UP CHECKLIST98..................
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment
can be hazardous due to system pressure and electrical
components. Only trained and qualifi ed service personnel
shouldinstall,repair,orserviceair-conditioning
equipment. Untrained personnel can perform the basic
maintenance functions of replacing filters. Trained service
personnel should perform all other operations.
When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to
the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations.
Havefireextinguishersavailableforallbrazing
operations.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for brazing operations. Have
fireextinguisher available.Read these instructions
thoroughly and follow all warnings or cautions attached to
the unit. Consult local building codes and National
Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety--alert
symbol
instructions or manuals, be alert to the potential for
personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert
symbol. DANGER identifies the most serious hazards
which will result in severe personal injury or death.
WARNING signifies a hazard which could result in
personal injury or death. CAUTION is used to identify
unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced
installation, reliability, or operation.
. When you see this symbol on the unit and in
!
WARNING
!
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in
personal injury, death and/or property damage.
Refer to the User’s Information Manual provided
with this unit for more details.
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
What to do if you smell gas:
DO NOT try to light any appliance.
DO NOT touch any electrical switch, or use a ny
phone in your buil ding.
IMMEDIATELY call your gas supplier from a
neighbor’sphone.Follow thegassupplier’s
48TC
instructions.
If you cannot reach your gas supplier, call the fire
department.
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Before performing service or maintenance operations
on unit, turn off m ain power switch to unit. Electrical
shock and rotating equipment could cause injury.
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury or death.
Disconnect gas piping from unit when pressure testing
at pressure greater than 0.5 psig. Pressures greater
than 0.5 psig will cause gas valve damage resulting in
hazardous condition. If gas valve is subjected to
pressure greater than 0.5 psig, it must be replaced
before use. When pressure testing field-supplied gas
piping at pressures of 0.5 psig or less, a unit connected
to such piping must be isolated by closing the manual
gas valve(s).
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal
injury.
Sheet metal parts may have sharp edges or burrs. Use
care and wear appropriate protective clothing, safety
glasses and gloves when handling parts and servicing
air conditioning units.
UNIT ARRANGEMENT AND ACCESS
General
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units with convenience outlet circuits may use
multiple disconnects. Check convenience outlet for
power status before opening unit for service. Locate
its disconnect switch, if appropriate, and open it.
Tag--out this switch, if necessary.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
PuronR (R--410A) refrigerant systems operate at
higher pressures than standard R--22 systems. Do not
use R--22 service equipment or components on
PuronR refrigerant equipment.
Fig. 1 and Fig. 2 show general unit arrangement and
access locations.
FILTER ACCESS PANEL
INDOOR COIL ACCESS PANEL
C06023
Fig. 1 -- Typical Access Panel Locations (Back)
2
BLOWER
ACCESS
PANEL
C08450
COMPRESSOR
FLUE OPENING
CONTROL BOX
Fig. 2 -- Typical Access Panel Location (Front)
Routine Maintenance
These items should be part of a routine maintenance
program, to be checked every month or two, until a
specific schedule for each can be identified for this
installation:
Quarterly Inspection (and 30 days after initial
start)
S Return air filter replacement
S Outdoor hood inlet filters cleaned
S Belt tension checked
S Belt condition checked
S Pulley alignment checked
S Fan shaft bearing locking collar tightness checked
S Condenser coil cleanliness checked
S Condensate drain checked
Seasonal Maintenance
These items should be checked at the beginning of each
season (or more often if local conditions and usage
patterns dictate):
Conditioning
Air
S Condenser fan motor mounting bolts tightness
S Compressor mounting bolts
S Condenser fan blade positioning
S Control box cleanliness and wiring condition
S Wire terminal tightness
S Refrigerant charge level
S Evaporator coil cleaning
S Evaporator blower motor amperage
Heating
S Heat exchanger flue passageways cleanliness
S Gas burner condition
S Gas manifold pressure
S Heating temperature rise
Economizer or Outside Air
Damper
S Inlet filters condition
S Check damper travel (economizer)
S Check gear and dampers for debris and dirt
Air Filters and Scr
eens
Each unit is equipped with return air filters. If the unit has
an economizer, it will also have an outside air screen. If a
manual outside air damper is added, an inlet air screen
will also be present.
Each of these filters and screens will need to be
periodically replaced or cleaned.
Return Air
Filters
Return air filters are disposable fiberglass media type.
Access to the filters is through the small lift --out panel
located on the rear side of the unit, above the
evaporator/return air access panel. (See Fig. 1.)
To remove the filters:
1. Grasp the bottom flange of the upper panel.
2. Lift up and swing the bottom out until the panel disengages and pulls out.
3. Reach inside and extract the filters from the filter
rack.
4. Replace these filters as required with similar replacement filters of same size.
To re--install the access panel:
1. Slide the top of the panel up under the unit top panel.
2. Slide the bottom into the side channels.
3. Push the bottom flange down unti l it contacts the top
of the lower panel (or economizer top).
IMPORTANT:DONOTOPERATETHEUNIT
WITHOUT THESE FILTERS!
Outside Air
Hood
Outsideairhoodinletscreensarepermanent
aluminum-- mesh type filters. Check these for cleanliness.
Remove the screens when cleaning is required. Clean by
washing with hot low-- pressure water and soft detergent
and replace all screens before restarting the unit. Observe
the flow direction arrows on the side of each filter frame.
48TC
Economizer Inlet Air Screen
This air screen is retained by spring clips under the top
edge of the hood. (See Fig. 3.)
3
22 3/8 (569 mm)
DIVIDER
OUTSIDE
AIR
HOOD
CLEANABLE
ALUMINUM
FILTER
BAROMETRIC
RELIEF
FILTER
48TC
Fig. 3 -- Filter Installation
To remove the filter, open the spring clips. Re--install the
filter by placing the frame in its track, then closing the
spring clips.
FILTER
CAP
C08634
SUPPLY F AN (BLOWER) SECTION
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
Before performing service or maintenance operations
on the fan system, shut off all unit power and tag--out
the unit disconnect switch. Do not reach into the fan
section with power still applied to unit.
Supply Fan (Belt--Drive)
The supply fan system consists of a forward--curve d
centrifugal blower wheel on a solid shaft with two
concentric type bearings, one on each side of the blower
housing. A fixed--pitch driven pulley is attached to the fan
shaft and an adjustable--pitch driver pulley is on the
motor. The pulleys are connected using a “V” type belt.
(See Fig. 5.)
Manual Outside Air Hood Screen
This inlet screen is secured by a retainer angle across the
top edge of the hood. (See Fig. 4.)
C07156
Fig. 4 -- Screens Installed on Outdoor--Air Hood
(Sizes 7-1/2 to 12-1/2 Tons Shown)
To remove the screen, loosen the screws in the top retainer
and slip the retainer up until the filter can be removed.
Re-install by placing the frame in its track, rotating the
retainer back down and tighten all screws.
C07087
Fig. 5 -- Belt Drive Motor Mounting
Belt
Check the belt condition and tension quarterly. Inspect the
belt for signs of cracking, fraying or glazing along the
inside surfaces. Check belt tension by using a spring-force
tool (such as Browning’s Part Numbe r “Belt Tension
Checker” or equivalent tool); tension should be 6-lbs at a
5/8-in. deflection when measured at the centerline of the
belt span. This point is at the center of the belt when
measuring the distance between the motor shaft and the
blower shaft.
NOTE: Without the spring--tension tool, place a straight
edge across the belt surface at the pulleys, then deflect the
belt at mid--span using one finger to a 1/2-in. deflection.
Adjust belt tension by loosening the motor mounting plate
front bolts and rear bolt and sliding the plate toward the
fan (to reduce tension) or away from fan (to increase
tension). Ensure the blower shaft and the motor shaft are
parallel to each other (pulleys aligned). Tighten all bolts
when finished.
4
To replace the belt:
1. Use a belt with same section type or similar size. Do
not substitute a “FHP” type belt. When installing the
new belt, do not use a tool (screwdriver or pry--bar) to
force the belt over the pulley flanges, this will stress
the belt and cause a reduction in belt life.
2. Loose n the motor mounting plate front bolts and rear
bolts.
3. Push the motor and its mounting plate towards the
blower housing as close as possible to reduce the center distance between fan shaft and motor shaft.
4. Re move the belt by gentl y lifting the old belt over
one of the pulleys.
5. Install the new belt by gently sliding the belt over
both pulle ys and then sliding the motor and plate
away from the fan housing until proper tension is
achieved.
6. Check the alignment of the pulleys, adjust if necessary.
7. Tighte n all bolts.
8. Check the tension after a few hours of runtime and
re--adjust as required.
Adjustable--Pitch Pulley on
Motor
The motor pulley is an adjustable--pitch type that allows a
servicer to implement changes in the fan wheel speed to
match as--installed ductwork systems. The pulley consists
of a fixed flange side that faces the motor (secured to the
motor shaft) and a movable flange side that can be rotated
around the fixed flange side that increases or reduces the
pitch diameter of this driver pulley. (See Fig. 6.)
As the pitch diameter is changed by adjusting the position
of the movable flange, t he centerline on this pulley shifts
laterally (along themotor shaft). This creates a
requirement for a realignment of the pulleys after any
adjustment of the movable flange. Also reset the belt
tension after each realignment.
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft. Make angular alignment by loosening motor from mounting.
3. Tighten fan pulley setscrews and motor mounting
bolts to torque specifications.
4. Re check belt tension.
48TC
C07075
Fig. 6 -- Supply--Fan Pulley Adjustment
Bearings
This fan system uses bearings featuring concentric split
locking collars. The colla rs are tightened through a cap
screw bridging the split portion of the c ollar. The cap
screw has a Torx T25 socket head. To tighten the locking
collar: Hold the locking collar tightly against the inner
race of the bearing and torque the cap screw to 65--70
in-lb (7.4--7.9 Nm). (See Fig. 7.)
Check the condition of the motor pulley for signs of wear.
Glazing of the belt contact surfaces and erosion on these
surfaces are signs of improper belt tension and/or belt
slippage. Pulley replacement may be necessary.
To change fan speed:
1. Shut off unit power supply.
2. Loose n belt by loosening fan motor mounting nuts.
(See Fig. 5.)
3. Loose n movable pulley flange setscrew. (See Fig. 6.)
4. Screw movable flange toward fixed flange to increase
speed and away from fixed flange to decrease speed.
Increasing fan speed increases load on motor. Do not
exceed maximum speed specified.
5. Set movable flange at nearest keyway of pulley hub
and tighten setscrew to torque specifications.
C08121
Fig. 7 -- Tightening Locking Collar
Motor
When replacing the motor, also replace the external--tooth
lock washer (star washer) under the motor mounting base;
this is part of the motor grounding system. Ensure the
teeth on the lock washer are in contact with the motor ’s
painted base. Tighten motor mounting bolts to 120 +/-- 12
in--lbs.
5
Changing fan wheel speed by changing pulleys: The
horsepower rating of the belt is primarily dictated by the
pitch diameter of the smaller pulley in the drive system
(typically the motor pulley in these units). Do not install a
replacement motor pulley with a smaller pitch diameter
than provided on the original factory pulley. Change fan
wheel speed by changing the fan pulley (larger pitch
diameter to reduce wheel speed, smaller pitch diameter to
increase wheel speed) or select a new system (both
pulleys and matching belt(s)).
TUBES
FINS
Before changing pulleys to increase fan wheel speed,
check the fan performance at the target speed and airflow
rate to determine new motor loading (bhp). Use the fan
performance tables or use the Packaged Rooftop Builder
software program. Confirm that the motor in this unit is
capable of operating at the new operating condition. Fan
shaft loading increases dramatically as wheel speed is
increased.
48TC
To reduce vibration, replace the motor’s adjustable pitch
pulley with a fixed pitch pulley (after the final airflow
balance adjustment). This will reduce the amount of
vibration generated by the motor/belt--drive system.
COOLING
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
This system uses PuronR refrigerant which has higher
pressures than R--22 and other refrigerants. No other
refrigerant may be used in this system. Gauge set,
hoses, and recovery system must be de signed to
handle Puron refrigerant. If unsure about equipment,
consult the equipment manufacturer.
Condenser Coil
The condenser coil is new NOVATION Heat Exchanger
Technology. This is an all--aluminum construction with
louveredfinsover single--depth crosstubes.The
crosstubes have multiple small passages through which
the refrigerant passes from header to header on each end.
Tubesandfinsarebothaluminumconstruction.
Connection tube joints are copper.The coil may be
one--row or two--row. Two--row coils are spaced apart to
assist in cleaning.
MANIFOLD
MICROCHANNELS
C07273
Fig. 8 -- Microchannel Coils
Evaporator Coil
The evaporator coil is traditional round--tube, plate--fin
technology.Tube and fin c onstruction is of various
optional materials and coatings (see Model Number
Format). Coils are multiple--row.
Coil Maintenance and Cleaning
Recommendation
Routine cleaning of coil surfaces is essential to maintain
proper operation of the unit. Elimination of contamination
and removal of harmful residues will greatly increase the
life of the coil and extend the life of the unit. The
following maintenance and cleaning procedures are
recommended as part of the routine maintenance activities
to extend the life of the coil.
Remove Surface Loaded Fibers
Surface loaded fi bers or dirt should be removed with a
vacuum cleaner. If a vacuum cleaner is not available, a
soft non-- metallic bristle brush may be used. In either
case, the tool should be applied in the direction of the fins.
Coil surfaces can be easily damaged (fin edges can be
easily bent over and damage to the coating of a protected
coil) if the tool is applied across the fins.
NOTE: Use of a water stream, such as a garden hose,
against a surface loaded coil will drive the fibers and dirt
into the coil. This will make cleaning efforts more
difficult. Surface loaded fibers must be completely
removed prior to using low velocity clean water rinse.
Periodic Clean Water Rinse
A periodic clean water rinse is very beneficial for coils
that are applied in coastal or industrial environments.
However, it is very important that the water rinse is made
with very low velocity water stream to avoid damaging
the fin edges. Monthly cleaning as described below is
recommended.
6
Routine Cleaning of NOVATION Condenser Coil
Surfaces
To clean the NOVATION condenser coil, chemicals a re
NOT to be used; only wate r is approved as the cleaning
solution. Only clean potable water is authorized for
cleaning NOVATION condensers. Carefully remove any
foreign objects or debris attached to the coil face or
trapped within the mounting frame and brackets. Using a
high pressure water sprayer, purge any soap or industial
cleaners from hose and/or dilution tank prior to wetting
the coil.
Clean condenser face by spraying the coil core steadily
and uniformly from top to bottom, directing the spray
straight into or toward the coil face. Do not exceed 900
psig or a 45 degree angle; nozzl e must be at least 12 in.
(30 cm) from the coil face. Reduce pressure and use
caution to prevent damage to air centers (fins). Do not
fracture the braze between air centers and refrigerant
tubes. Allow water to drain from the coil core and check
for refrigerant leaks prior to start--up.
NOTE:Please see the NOVATION Condenser Service
section for specific information on the coil.
!
CAUTION
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal
injury or equipment damage.
Chemical clea ning should NOT be used on the
aluminum NOVATION condenser. Damage to the coil
may occur. Only approved cleaning is recommended.
Routine Cleaning of Evaporator Coil Sufaces
Monthly cleaning with Totaline environmentally sound
coil cleaner is essential to extend the life of coils. This
cleaner is available from Carrier Replacement parts
division as part number P902--0301 for one gallon
container, and part number P902--0305 for a 5 gallon
container. It is recommended that all round tube coil
cleaner as described below. Coil cleaning should be part
of the unit’s regularly scheduled maintenance procedures
to ensure long life of the coil. Failure to clean the coils
may result in reduced durability in the environment.
Avoid the use of
S coil brighteners
S acid cleaning prior to painting
S high pressure washers
S poor quality water for cleaning
Totalineenvironmenta llysoundcoilcleaneris
non--flammable, hypoallergenic, non--bacterial, and a
USDA accepted biodegradable agent that will not harm
coil or surrounding components such as electrical wiring,
paintedmetalsurfaces,orinsulation.Useof
non--recommended coil cleaners is strongly discourage d
since coil and unit durability could be affected.
S 2-1/2 gallon garden sprayer
S water rinse with low velocity spray nozzle
!
CAUTION
PERSONAL INJURY HAZARD
Failure to follow this caution may result in corrosion
and damage to the unit.
Harsh chemicals, household bleach or acid or basic
cleaners should not be used to clean outdoor or indoor
coils of any kind. These cleaners can be very difficult
to rinse out of the coil and can accelerate corrosion at
the fin/tube interface where dissimilar materials are in
contact. If there is dirt below the surface of the coil,
use the Totaline environmentally sound coil cleaner as
described above.
!
CAUTION
PERSONAL INJURY HAZARD
Failure to follow this caution may result in reduced
unit performance.
High velocity wat er from a pressure washer, garden
hose, or compressed air should never be used t o clean
a c oil. The force of the wter or air jet will bend the fin
edges and icrease airside pressure drop.
1. Proper eye protection such as safety glasses is recommended during mixing and application.
2. Remove all surface loaded fibers and dirt with a vacuum cleaner as described above.
3. Thoroughly wet finned surfaces with clean water and
a low velocity garden hose, being carefull not to bend
fins.
4. Mix Totaline environmentally sound coil cleaner in a
2 1/2 gallon garden spryer according to the instructions included with the cleaner. The optimum solution
temperature is 100F(38C).
NOTE: Do NOT USE water in excess of 130F(54C),
as the enzymatic activity will be destroyed.
1. Thoroughly apply Totaline environmentally sound
coil cleaner solution to all coil surfaces including
finned area, tube sheets and coil headers.
2. Hold garden sprayer nozzle close to finned areas and
apply cleaner with a vertical, up--and--down motion.
Avoid spraying in horizontal pattern to minimize potential for fin damage.
3. Ensure cleaner thoroughly penetrates deep into finned
areas.
4. Interior and exterior finned area s must be thoroughly
cleaned.
48TC
7
5. Finned surfaces should remain wet with cleaning
solution for 10 minutes.
6. Ensure surfaces are not allowed to dry before rinsing.
Reapply cleaner as needed to ensure 10--minute saturation is achieved.
7. Thoroghly rinse all surfaces with low velocity clean
water using downward rinsing motion of water spray
nozzle. Protect fins from damage from the spray
nozzle.
Evaporator Coil Metering
The metering devices are multiple fixed--bore devices
(Acutrolt) swaged into the horizontal outlet tubes from
the liquid header, located at the entrance to each
evaporator coil circuit path. These are non--adjustable.
Service requires replacing the entire liquid header
assembly.
48TC
To check for possible blockage of one or more of these
metering devices, disconnect the supply fan contactor
(IFC) coil, then start the compressor and observe the
frosting pattern on the face of the evaporator coil. A frost
pattern should deve lop uniformly across the face of the
coil starting at each horizontal header tube. Failure to
develop frost at an outle t tube can indicate a plugged or a
missing orifice.
Devices
Refrigerant System Pressure Access Ports
There are two access ports in the system -- on the suction
tube near the compressor and on the discharge tube near
the compressor. These are brass fittings with black plastic
caps. The hose connection fittings are standard 1/4 SAE
male flare couplings.
The brass fittings are two--piece High Flow valves, with a
receptacle base brazed to the tubing and an integral
spring-closed check valve core screwed into the base. (See
Fig. 9.) This check val ve is permanently assembled into
this core body and cannot be serviced separately; replace
the entire core body if necessary. Service tools are
available from RCD that allow the replacement of the
check valve core without having to recove r the entire
system refrigerant charge. Apply compressor refrigerant
oil to the check valve core’s bottom O-ring. Install the
fitting body with 96 +/-- 10 in-lbs of torque; do not
overtighten.
PURONR (R--410A) REFRIGERANT
This unit is designed for use with Puron (R--410A)
refrigerant. Do not use any other refrigerant in this
system.
Because Puron (R --410A) refrigerant is a blend, it is
strongly recommended that refrigerant always be removed
from the cylinder as a liquid. Admit liquid refrigerant into
the system in the discharge line. If adding refrigerant into
the suction line, use a commercial metering/expansion
device at the ga uge manifold; rem ove liquid from the
cylinder, pass it through the metering device at the gauge
set and then pass it into the suction line as a vapor. Do not
remove Puron (R--410A) refrigerant from the cylinder as a
vapor.
Refrigerant Charge
Amount of refrigerant charge is listed on the unit’s
nameplate.RefertoCarrierGTAC2--5Charging,
Recovery, Recycling and Reclamation training manual
and the following procedures.
Unit panels must be in place when unit is operating during
the charging procedure. To prepare the unit for charge
adjustment.
Charge
No
Use standard evacuating techniques. After evacuating
system, weigh in the specified amount of refrigerant.
Low--Charge
Using Cooling Charging Charts (Figs. 10, 11, 12, and 13),
vary refrigerant until the conditions of the appropriate
chart are met. Note the charging charts are different from
the type normally used. Charts are based on charging the
units to the correct superheat for the various operating
conditions. Accurate pressure gauge and temperature
sensing device are required. Connect the pressure gauge to
the service port on the suction line. Mount the temperature
sensing device on the suction line and insulate it so that
outdoor ambient temperature does not affect the reading.
Indoor--air cfm must be within the normal operating range
of the unit.
To Use Cooling Charging
Select the appropriate unit charging chart from Figs. 10,
11, 12, and 13.
S Sizes D08 and D12 each have one cooling charging chart
S Size D14 has two cooling charging charts: Circuit A and
Circuit B
Take the outdoor ambient temperature and read the
suction pressure gauge. Refer to chart to determine what
suction temperature should be. If suction temperat ure i s
high, add refrigerant. If suction temperature is low,
carefully recover some of the charge. Recheck the suction
pressure as charge is adjusted.
Cooling
Charts
Puron (R--410A) refrigerant is provided in pink (rose)
colored cylinders. These cylinders are available with and
without dip tubes; cylinders with dip tubes will have a
label indicating this feature. For a cylinde r with a dip
tube, place the cylinder in the upright position (access
valve at the top) when removing liquid refrigerant for
charging. For a cylinder without a dip tube, invert the
cylinder (access valve on the bottom) when removing
liquid refrigerant.
For D14 size, perform this procedure once for Circuit A
(using the Circuit A chart) and once for Circuit B (using
the Circuit B chart).
This surface provides a metal to metal seal when
torqued into the seat. Appropriate handling is
required to not scratch or dent the surface.
1/2" HEX
o
45
DEPRESSOR PER ARI 720
+.01/-.035
FROM FACE OF BODY
7/16-20 UNF RH
C08453
48TC
9
48TC
COOLING CHARGING CHARTS
Fig. 10 -- Cooling Charging Charts (D08)
C08669
10
COOLING CHARGING CHARTS
48TC
Fig. 11 -- Cooling Charging Charts (D12)
C08670
11
48TC
COOLING CHARGING CHARTS
Fig. 12 -- Cooling Charging Charts (D14 -- Circuit A)
12
C09151
COOLING CHARGING CHARTS
48TC
Fig. 13 -- Cooling Charging Charts (D14 -- Circuit B)
13
C09152
Table 1 – Cooling Service Analysis
PROBLEMCAUSEREMEDY
Power failure.Call power company.
Fuse blown or circuit breaker tripped.Replace fuse or reset circuit breaker.
Compressor and Condenser
Fan Will Not Start.
Compressor Will Not Start But
Condenser Fan Runs.
48TC
Compressor Cycles (other
than normally satisfying
thermostat).
Compressor Operates
Continuously.
Excessive Head Pressure.
Head Pressure Too Low.
Excessive Suction Pressure.
Suction Pressure Too Low.
Evaporator Fan Will Not Shut
Off.
Compressor Makes Excessive
Noise.
Defective thermostat, contactor, transformer,
or control relay.
Insufficient line voltage.Determine cause and correct.
Incorrect or faulty wiring.Check wiring diagram and rewire correctly.
Thermostat setting too high.Lower thermostat setting below room temperature.
Faulty wiring or loose connections in
compressor circuit.
Compressor motor burned out, seized, or
internal overload open.
Defective compressor.Replace and determine cause.
Insufficient line voltage.Determine cause and correct.
Blocked condenser.Determine cause and correct.
Defective run/start capacitor, overload, or start
relay.
Defective thermostat.Replace thermostat.
Faulty condenser --- fan motor or capacitor.Replace.
Restriction in refrigerant system.Locate restriction and remove.
Dirty air filter.Replace filter.
Unit undersized for load.Decrease load or increase unit size.
Thermostat set too low.Reset thermostat.
Low refrigerant charge.Locate leak; repair and recharge.
Leaking valves in compressor.Replace compressor.
Air in system.Recover refrigerant, evacuate system, and recharge.
Condenser coil dirty or restricted.Clean coil or remove restriction.
Dirty air filter.Replace filter.
Dirty condenser coil.Clean coil.
Refrigerant overcharged.Recover excess refrigerant.
Air in system.Recover refrigerant, evacuate system, and recharge.
Condenser air restricted or air short --- cycling.Determine cause and correct.
Low refrigerant charge.Check for leaks; repair and recharge.
Compressor valves leaking.Replace compressor.
Restrictioninliquidtube.Remove restriction.
High head load.Check for source and eliminate.
Compressor valves leaking.Replace compressor.
Refrigerant overcharged.Recover excess refrigerant.
Dirty air filter.Replace filter.
Low refrigerant charge.Check for leaks; repair and recharge.
Metering device or low side restricted.Remove source of restriction.
Insufficient evaporator airflow.
Temperature too low in conditioned area.Reset thermostat.
Outdoor ambient below 25° F.Install low--- ambient kit.
Time off delay not finished.W a i t f o r 30 --- s e c o n d of f d e l a y .
Compressor rotating in wrong direction.Reversethe3---phasepowerleads.
Replace component.
Check wiring and repair or replace.
Determine cause. Replace compressor.
Determine cause and replace.
Replace fuse or reset circuit breaker. Determine
cause.
Recover refrigerant, evacuate system, and recharge
to nameplate.
Determine cause and replace.
Increase air quantity. Check filter and replace if
necessary.
14
Compressors
Lubrication
Compressors are charged with the correct amount of oil at
the factory.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to
components.
The compressor is in a PuronR refrigera nt system and
uses a polyolester (POE) oil. This oil is extremely
hygroscopic, meaning it absorbs water readily. POE
oils can absorb 15 times as much water as other oils
designed for HCFC and CFC refrigerants. Avoid
exposure of the oil to the atmosphere.
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could result in personal
injury or death.
Relieve pressure and recover all refrigerant before
system repair or final unit disposal.
Wear safety glasses and gloves when handling
refrigerants.
Keep torches and other ignition sources away from
refrigerants and oils.
Replacing Compressor
6. Re verse any two of the unit power leads.
7. Re apply power to the compressor.
The suction and discharge pressure levels should now
move to their normal start--up levels.
NOTE: When the compressor is rotating in the wrong
direction, the unit makes an elevated level of noise and
does not provide cooling.
Filter Drier
Replace whenever refrigerant system is exposed to
atmosphere. Only use factory specified liquid--line filter
driers with working pressures no less than 650 psig. Do
not install a suction--line filter drier in liquid line. A
liquid-- line filter drier designed for use with Puron
refrigerant is required on every unit.
Condenser--Fan Adjustment (D08--D12 size)
1. Shut off unit power supply. Install lockout tag.
2. Remove condenser-fan assembly (grille, motor, and
fan).
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 14.
5. Tighten setscrews to 84 in-lbs (9.5 N-m).
6. Re place condenser-fan assembly.
CONDUIT
0.14 in +0.0/-0.03
C08448
Fig. 14 -- Condenser Fan Adjustment (D08--D12)
48TC
The compressor used with Puron refrigerant contains a
POE oil. This oil has a high affinity for moisture. Do not
remove the compressor’s tube plugs until ready to insert
the unit suction and discharge tube ends.
Compressor mounting bolt torque is 65--75 in-lbs
(7.3--8.5 N-m).
Compressor
On 3-phase units with scroll compressors, it is important
to be certai n compressor is rotating in the proper
direction. To determine whether or not compressor is
rotating in the proper direction:
1. Conne ct service gauges to suction and discharge pressure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge
pressure should rise, as is normal on any start--up.
NOTE:If the suction pressure does not drop and the
discharge pressure does not rise to normal levels:
4. Note that the evaporator fan is probably also rotating
in the wrong direction.
5. Turn off power to the unit.
Rotation
Condenser--Fan Adjustment (D14 size)
1. Shut off unit power supply. Install lockout tag.
2. Remove condenser fan grille.
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 15.
5. Tighten setscrews to 84 in-lbs (9.5 N-m).
6. Replace fan grille.
C09094
Fig. 15 -- Condenser Fan Adjustment (D14)
Troubleshooting Cooling System
Refer to Table 1 for additional troubleshooting topics.
15
CONVENIENCE OUTLETS
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units with convenience outlet circuits may use
multiple disconnects. Check convenience outlet for
power status before opening unit for service. Locate
its disconnect switch, if appropriate, and open it.
Tag--out this switch, if necessary.
Two types of conveni ence outlets are offered on 48TC
models: Non--powered and unit--powered. Both types
provide a 125-volt GFCI (ground--fault circuit--interrupter)
duplex receptacle rated at 15-A behind a hinged
48TC
waterproof access cover, located on the end panel of the
unit. (See Fig. 16.)
Pwd-CO Transformer
Conv Outlet
GFCI
Pwd-CO
Fuse
Switch
The primary leads to the convenience outlet transformer
are not factory--connected. Selection of primary power
source is a customer--option. If local codes permit, the
transformer primary leads can be connected at the
line--sideterminalsonaunit--mountednon--fused
disconnect or circuit--breaker switch; this will provide
service power to the unit when the unit disconnect switch
or circuit--breaker is open. Other connection methods will
result in the convenience outlet circuit being de--energized
when the unit disconnect or circuit--breaker is open. (See
Fig. 17.)
C08128
Fig. 16 -- Convenience Outlet Location
Non--Powered Type
Thistyperequiresthefieldinstallationofa
general--purpose 125--volt 15--A circuit powered from a
source elsewhere in the building. Observe national and
local codes when selecting wire size, fuse or breaker
requirements and disconnect switch size and location.
Route 125--v power supply conductors into the bottom of
the utility box containing the duplex receptacle.
Unit--Powered Type
A unit--mounted t ransformer is factory--installed to
stepdown the main power supply volta ge to the unit t o
115--v at the duplex receptacle. This option also includes a
manual switch with fuse, located in a utility box and
mounted on a bracket be hind the convenience outlet;
access i s through the unit’s c ontrol box access panel. (See
Fig. 16.)
CO8283
Fig. 17 -- Powered Convenience Outlet Wiring
UNIT
VOLTAGE
208,
230
460480
575600
CONNECT
AS
240
PRIMARY
CONNECTIONS
L1: RED +YEL
L2: BLU + GRA
L1: RED
Splice BLU + YEL
L2: GRA
L1: RED
L2: GRA
TRANSFORMER
TERMINALS
H1 + H3
H2 + H4
H1
H2 + H3
H4
H1
H2
Duty Cycle
The unit--powered convenience outlet has a duty cycle
limitation. The transformer is intended to provide power
on an intermittent basis for service tools, lamps, etc; it is
not intended to provide 15--amps loading for continuous
duty loads (such as electric heaters for overnight use).
Observe a 50% limit on circuit loading above 8--amps
(i.e., limit loads exceeding 8 --amps to 30 minutes of
operation every hour).
16
Maintenance
Periodically test the GFCI receptacle by pressing the
TEST button on the face of the receptacle. This should
cause the internal circuit of the receptacle to trip and open
the receptacle. Check for proper grounding wires and
power line phasing if the GFCI receptacle does not trip as
required. Press the RESET button to clear the tripped
condition.
Fuse On Powered T ype
The factory fuse is a Bussman “Fusetron” T--15,
non--renewable screw--in (Edison base) type plug fuse.
Using Unit--Mounted Convenience Outlets
Units with unit--mounted convenience outlet circuits will
often requirethat twodisconnects be opened to
de--energize all power to the unit. Treat all units as
electrica lly e nergized until the convenience outlet power
is also checked and de--energization is confirmed. Observe
National Electrical Code Article 210, Branch Circ uits, for
use of convenience outlets.
SMOKE DETECTORS
Controller housing
and electronics
Conduit cou plings
(supplied by installer)
Alarm
Duct smoke sensor
controller
Fastener
(2X)
Conduit nuts
(supplied by installer)
Conduit sup port plate
Terminal block cover
(ordering option)
Troub le
Power
Tes t / r e s e t
switch
Cover gasket
Controll er cover
48TC
Smoke detectors are available as factory--installed options
on 48TC models. Smoke detectors may be specified for
Supply Air only or for Return Air without or with
economizer or in combination of Supply Air and Return
Air. Return Air smoke detectors are arranged for vertical
return configurations only. All components necessary for
operation are factory--provided and mounted. The unit is
factory--configuredforimmediatesmokedetector
shutdown operation; additional wiring or modifications to
unit terminal board may be necessary to complete the unit
and smoke detector configuration to meet project
requirements.
System
The smoke detector system consists of a four--wire
controller and one or two sensors. Its primary function is
to shut down the rooftop unit in order to prevent smoke
from circulating throughout the building. It is not to be
used as a life saving device.
Controller
The controller (see Fig. 18) includes a controller housing,
a printed circuit boa rd, and a clear plastic cover. The
controller can be connected to one or two compatible duct
smoke sensors. The clear plastic cover is secured to the
housing with a single captive screw for easy access to the
wiring terminals. The controller has three LEDs (for
Power, Trouble and Alarm) and a manual test/reset button
(on the cover face).
C08208
Fig. 18 -- Controller Assembly
Sensor
The sensor (see Fig. 19) includes a plastic housing, a
printed circuit board, a clear plastic cover, a sampling
tube inlet and an exhaust tube. The sampling tube (when
used) and exhaust tube are attached during installation.
The sampling tube varies in length depending on the size
of the rooftop unit. The clear plastic cover permits visual
inspections without having to disassemble the sensor. The
cover at taches to the sensor housing using four captive
screws and forms an airtight chamber around the sensing
electronics. Each sensor includes a harness with an RJ45
terminal for connecting to the controller. Each sensor has
four LEDs (for Power, Trouble, Alarm and Dirty) and a
manual test/reset button (on the left--side of the housing).
Air i s introduced to the duct smoke detector sensor’s
sensing cham ber through a sampling tube that extends into
the HVAC duct and is directed back into the ventilation
system through a (shorter) exhaust tube. The difference in
air pressure between the two tubes pulls the sampled air
through the sensing chamber. W hen a sufficient amount of
smoke is detected in the sensing chamber, the sensor
signals an alarm state and the controller automatically
takes the appropriate action to shut down fans and
blowers, change over air handling systems, notify the fi re
alarm control panel, etc.
17
The sensor uses a process called differential sensing to
prevent gradual environmental changes from triggering
false alarms. A rapid change in environmental conditions,
such as smoke from a fire, causes the sensor to signal an
alarm state but dust and debris accumulated over time
does not.
Duct smoke s ensor
Exhaust tube
48TC
See
Detail A
Detail A
Intake
gasket
Plug
TSD-CO2
(ordering option)
Sampling tube
(ordered separately)
Magnetic
test/reset
switch
Exhaust gasket
Coupling
Sensor housing
and electro nics
Cover gasket
(ordering option)
Sensor cover
Smoke Detector Sensor
C08245
Fig. 20 -- Typical Supply Air Smoke Detector Sensor
Location
Return Air without Economizer — The sampling tube is
located across t he return air opening on the unit basepan.
(See Fig. 21.) The holes in the sampling tube face
downward, into the return air stream. The sampling tube is
connected via tubing to t he return air sensor that is
mounted on a bracket high on the partition between return
filter and controller location. (This sensor is shipped in a
flat--mounting location. Installation requires that this
sensor be relocated to its operating location and the tubing
to the sampling tube be connected. See installation steps
below.)
Return Air Detector module
(shipping position shown)*
Alarm
Troub le
Power
Dirty
C08209
Fig. 19 -- Smoke Detector Sensor
For installations using two sensors, the duct smoke
detector does not differentiate which sensor signals an
alarm or trouble condition.
Smoke Detector Locations
Supply Air — The Supply Air smoke detector sensor is
located to the left of the unit’s indoor (supply) fan. (See
Fig. 20.) Access is through the fan access panel. There is
no sampling tube used at this location. The sampling tube
inlet extends through the side plate of the fan housing
(into a high pressure area). The controlle r is located on a
bracket to the right of the return filter, accessed through
the lift --off filter panel.
Controller module
Return Air Detector Sampling Tube
*RA detector must be moved from shipping position to operating position by installer
C07307
Fig. 21 -- Typical Return Air Detector Location
Return Air with Economizer — The sampling tube is
inserted through the side plates of the economizer
housing, placing it across the return air ope ning on the
unit basepa n. (See Fig. 22.) The holes in the sampl ing
tube face downward, into the return air stream. The
sampling tube is connected via tubing to the return air
sensor that is mounted on a bracket high on the partition
between return filter and controller location. (This sensor
is shipped in a flat--mounting location. Installation
requires that this sensor be relocate d to its operating
location and the tubing to the sampling tube be connected.
See installation steps below.)
18
Return Air
Sampling Tube
Fig. 22 -- Return Air Sampling Tube Location
Completing Installation of Return Air Smoke
Sensor:
SCREWS
EXHAUST
TUBE
FLEXIBLE
EXTENSION
TUBE
SAMPLING
4. Screw the sensor and detector plate into its operating
position using screws from Step 1. Make sure the
sampling tube connection is on the bottom and the exhaust tube is on the top. (See Fig. 23.)
5. Conne ct the flexible tube on the sampling inlet to the
sampling tube on the basepan.
6. For units with an economizer, the sampling tube is integrated into the economizer housing but the connection of the flexible tubing to the sampling tube is the
same.
C08129
48TC
C08127
Fig. 24 -- Return Air Sensor Operating Position
FIOP Smoke Detector Wiring and Response
All units: FIOP smokedetector is configured to
automatically shut down all unit operations when smoke
condition is detected. See Fig. 25, Smoke Detector
Wiring.
C08126
Fig. 23 -- Return Air Detector Shipping Position
1. Unscrew the two screws holding the Return Air
Sensor detector plate. (See Fig. 23.) Save the scre ws.
2. Re move the Return Air Sensor and its detector plate.
3. Rotate the detector plate so the sensor is facing outwards a nd the sampling tube connection is on the bottom. (See Fig. 24.)
Highlight A: JMP 3 is factory--cut, tra nsferring unit
control to smoke detector.
Highlight B: Smoke detector NC contact set will open on
smokeal armcondition,de--energizingtheORN
conductor.
19
B
D
C
F
E
48TC
Fig. 25 -- Typical Smoke Detector System Wiring
Highlight C: 24--v power signal via ORN lead is removed
at Smoke Detector input on LCTB; all unit operat ions
cease immediately.
PremierLinkt a nd RTU--MP Controls: Unit operating
functions (fan, cooli ng and heating) are terminated as
described above. In addition:
Highlight D: On smoke alarm condition, the smoke
detector NO Alarm contact will close, supplying 24--v
power to GRA conductor.
Highlight E: GRA lead at Smoke Alarm input on LCTB
provides 24--v signal to FIOP DDC control.
PremierLink: This signal is conveyed to PremierLink
FIOP’s TB1 at terminal TB1--6 (BLU lead). This signal
initiates the FSD sequence by the PremierLink control.
FSD status is reported to connected CCN network.
RTU--MP: The 24-- v signal is conveyed to RTU--MP’s
J1--10 input terminal. This signal initiates the FSD
sequence by the RTU--MP control. FSD status is reported
to connected BAS network.
Using Remote Logic: Five conductors are provided for
field use (see Highlight F) for additional annunciation
functions.
Additional Application Data — Refer to Catalog No.
HKRNKA--1XA for discussions on additional control
features of these smoke detectors including multiple unit
coordination. (See Fig. 25.)
A
C08246
Sensor an d Controller Tests
Sensor Alarm Test
The sensor alarm test checks a sensor’s ability to signal an
alarm state. This test requi res that you use a field provided
SD--MAG test magnet.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to fol low this caution may result in personnel
and authority concern.
This test places the duct detector into the alarm state.
Unless part of the test, disconnect all auxiliary
equipment from the controller before performing the
test. If the duct detector is connected to a fire alarm
system,notifytheproperauthoritiesbefore
performing the test.
Sensor Alarm Test Procedure
1. Hold the test magnet where indicated on the side of
the sensor housing for seven seconds.
2. Verify that the sensor’s Alarm LED turns on.
3. Re set t he sensor by holding the test magnet against
the sensor housing for two seconds.
4. Verify that the sensor’s Alarm LED turns off.
Controller Alarm T
The controller alarm test checks the controller’s ability to
initiate and indicate an alarm state.
est
20
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to fol low this caution may result in personnel
and authority concern.
This test places the duct detector into the alarm state.
Disconnect all auxiliary equipment from the controller
before performing the test. If the duct detector is
connected to a fire alarm system, notify the proper
authorities before performing the test.
Controller Alarm Test Procedure
1. Press the controller’s test/reset switch for seven
seconds.
2. Verify that the controller’s Alarm LED turns on.
3. Re set the sensor by pressing the test/reset switch for
two seconds.
4. Verify that the controller’s Alarm LED turns off.
Dirty Controller T
The dirty controller test checks the controller’s ability to
initiate a dirty sensor test and indicate its results.
OPERATIONAL TEST HAZARD
Failure to fol low this caution may result in personnel
and authority concern.
Pressing the controller’s test/reset switch for longer
than seven seconds will put the duct detector into the
alarm state and activate all automatic alarm responses.
Dirty Controller Test Procedure
S Press the controller’s test/reset switch for two seconds.
S Verify that the controller’s Trouble LED flashes.
Dirty Sensor T
The dirty sensor test provides an indication of the sensor’s
ability to compensate for gradual environmental changes.
A sensor that can no longer compensate for environmental
changes is considered 100% dirty and requires cleaning or
replacing. You must use a field provided SD--MAG test
magnet to initiate a sensor dirty test. The sensor’s Dirty
LED indicates the results of the dirty test as shown in
Table 2.
est
!
CAUTION
est
!
CAUTION
Tabl e 2 – Di rty LED Te st
FLASHESDESCRIPTION
10---25% dirty. (Typical of a newly installed detector)
225 --- 50% dirty
351 --- 75% dirty
476 --- 99% dirty
Dirty Sensor Test Procedure
1. Hold the test magnet where indicated on the side of
the sensor housing for two seconds.
2. Verify that the sensor’s Dirty LED flashes.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to fol low this caution may result in personnel
and authority concern.
Changing the dirty sensor test operation will put the
detector into the alarm state and activate all automatic
alarm responses. Before changing dirty sensor test
operation, disconnect all auxiliary equipment from the
controller and notify the proper authorities if
connected to a fire alarm system.
Changing the Dirty Sensor Test
By default, sensor dirty test results are indicated by:
S The sensor’s Dirty LED flashing.
S The controller’s Trouble LED flashing.
S The controller’s supervision relay contacts toggle.
The operation of a sensor’s dirty test can be changed so
that the controller’s supervision relay is not used to
indicate test results. When two detectors are connected to
a controller, sensor dirty test operation on both sensors
must be configured to operate in the same manner.
To Configure the Dirty Sensor Test Operation
1. Hold the test magnet where indicated on the side of
the sensor housing until the sensor’s Alarm LED turns
on and its Dirty LED flashes twice (approximately 60
seconds).
2. Re set the sensor by removing the test magnet then
holding it against the sensor housing again until the
sensor’s Alarm LED turns off (approximately 2
seconds).
Remote Station T
The remote station alarm test checks a test/reset station’s
ability to initiate and indicate an alarm state.
est
48TC
OPERATIONAL TEST HAZARD
Failure to fol low this caution may result in personnel
and authority concern.
Holding the test magnet against the sensor housing for
more than seven seconds will put the duct detector
into the alarm state and activate all automatic alarm
responses.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to fol low this caution may result in personnel
and authority concern.
This test places the duct detector into the alarm state.
Unless part of the test, disconnect all auxiliary
equipment from the controller before performing the
test. If the duct detector is connected to a fire alarm
system,notifytheproperauthoritiesbefore
performing the test.
21
SD--TRK4 Remote Alarm T est Procedure
1. Turn the key switch to the RESET/TEST position for
seven seconds.
2. Verify that the test/reset station’s Alarm LED turns
on.
3. Re set the sensor by turning the key switch to the
RESET/TEST position for two seconds.
4. Verify that the test/reset station’s Alarm LED turns
off.
Remote Test/Reset Station Dirty Sensor T
est
The test/reset station dirty sensor test checks the test/reset
station’s ability to initiate a sensor dirty test and indicate
the results. It must be wired to the controller as shown in
Fig. 26 and configured to operate t he controller’s
supervision relay. For more information, see “Changing
the Dirty Sensor Test.”
48TC
12
1
TB3
1
2
Smoke Detector Controller
−
Auxiliary
equipment
+
Dirty Sensor Test Using an SD--TRK4
1. Turn the key switch to the RESET/TEST position for
two seconds.
2. Verify that the test/reset station’s Trouble LED
flashes.
Detector Cleaning
Cleaning the Smoke Detector
Clean the duct smoke sensor when the Dirty LED is
flashing continuously or sooner if conditions warrant.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to fol low this caution may result in personnel
and authority concern.
If the smoke detector is connected to a fire alarm
system, first notify the proper authorities that the
detector is undergoing mai ntenance then disable the
relevant circuit to avoid generating a false alarm.
1. Disconnect power from the duct detector then remove
the sensor’s cover. (See Fig. 27.)
3
S
contacts [3]
Wire m
ust be
added by installer
upe
rv
ision relay
14
SD-TRK4
1
3
18 Vdc ( )
18 Vdc ( )
+
−
19
15
2
20
Trouble
5
P
ower
4
Alarm
1
Reset/Test
3
2
C08247
Fig. 26 -- Remote Test/Reset Station Connections
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to fol low this caution may result in personnel
and authority concern.
If the test/reset station’s key switch is left in the
RESET/TEST position for longer than seven seconds,
the detector will automatically go into the alarm state
and activate all automatic alarm responses.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to fol low this caution may result in personnel
and authority concern.
Holding the test magnet to the target area for longer
than seve n seconds will put the detector into the alarm
state and activate all automatic alarm responses.
Sampling
tube
Airow
HVAC duct
Sensor
housing
Optic
plate
Retainer
clip
Optic
housing
C07305
Fig. 27 -- Sensor Cleaning Diagram
2. Using a vacuum cleaner, clean compressed air, or a
soft bristle brush, remove loose dirt and debris from
inside the sensor housing and cover.
Use isopropyl alcohol and a lint--free cloth to remove
dirt and other contaminants from the gasket on the
sensor’s cove r.
3. Squeeze the retainer clips on both sides of the optic
housing then lift the housing away from the printed
circuit board.
4. Gently remove dirt and debris from around the optic
plate and inside the optic housing.
5. Re place the optic housing and sensor cover.
6. Conne ct power to the duct detector then perform a
sensor alarm test.
22
INDICAT ORS
Normal State
The smoke detector operates i n the normal state in the
absence of any trouble conditions and when its sensing
chamber is free of smoke. In the normal state, the Power
LED on both the sensor and the controller are on and all
other LEDs are off.
Alarm
The smoke detector enters the alarm state when the
amount of smoke particulate in the sensor’s sensing
chamber exceeds the alarm threshold value. (See Table 3.)
Upon entering the alarm state:
The SuperDuct duct smoke detector enters the trouble
state under the following conditions:
An internal sensor fault is detected upon entering the
trouble state:
State
S The sensor’s Alarm LED and the controller’s Alarm LED
turn on.
S The contacts on the controller’s two auxiliary relays
switch positions.
S The contacts on the controller’s alarm initiation relay
close.
S The controller’s remote alarm LED output is activated
(turned on).
S The controller’s high impedance multiple fan shutdown
control line is pulled to ground Trouble state.
S A sensor’s cover is removed and 20 minutes pass before
it is properly secured.
S A sensor’s environmental compensation limit is reached
(100% dirty).
S A wiring fault between a sensor and the controller is
detected.
S The contacts on the controller’s supervisory relay switch
positions. (See Fig. 28.)
S If a sensor trouble, the sensor ’s Trouble LED the
controller’s Trouble LED turn on.
S If 100% dirty, the sensor’s Dirty LED turns on and the
controller’s Trouble LED flashes continuously.
S If a wiring fault between a sensor and the controller, the
controller’s Trouble LED turns on but not the sensor’s.
Tro uble
Alarm
Power
NOTE:All troubles are latched by the duct smoke
detector. The trouble condition must be cleared and then
the duct smoke detector must be reset in order to restore it
to the normal state.
Resetting Alarm and Trouble Condition T
rips:
Manual reset is required to restore smoke detector systems
to Normal operation. For installations using two sensors,
the duct smoke detector does not differentiate whic h
sensor signals an alarm or trouble c ondition. Check each
sensor for Alarm or Trouble status (indicated by LED).
Clear the condition that has generated the trip at this
sensor. Then reset the sensor by pressing and holding the
reset button (on the side) for 2 seconds. Verify that the
sensor’s Alarm and Trouble LEDs are now off. At the
controller, clear its Alarm or Trouble state by pressing and
holding the manual reset button (on the front cover) for 2
seconds. Verify that the controller’s Alarm and Trouble
LEDs are now off. Replace all panels.
Troubleshooting
Controller’s T r ouble LED is On
1. Check the Trouble LED on each sensor connected to
the controller. If a sensor’s Trouble LED is on, determine the cause and make the necessary repairs.
2. Check the wiring between the sensor and the controller. If wiring is loose or missing, repair or replace as
required.
Controller’s T r ouble LED is
1. One or both of the sensors is 100% dirty.
2. Determine which Dirty LED is flashing then clean
that sensor assembly as described in the detector
cleaning section.
Sensor’s Trouble LED is
1. Check the sensor ’s Dirty LED. If it is flashing, the
sensor is dirty and must be cleaned.
2. Che ck the sensor’s cover. If it is loose or missing, secure the cover to the sensor housing.
3. Re place sensor assembly.
Sensor’s Power LED is
1. Che ck the controller’s Power LED. If it is off, determine why the controller does not have power and
make the necessary repairs.
2. Check the wiring between the sensor and the controller. If wiring is loose or missing, repair or replace as
required.
Flashing
On
Off
48TC
Fig. 28 -- Controller Assembly
Test/reset
switch
C07298
23
Table 3 – Detector Indicators
CONTROL OR INDICATORDESCRIPTION
Magnetic test/reset switch
Alarm LEDIndicates the sensor is in the alarm state.
Trouble LEDIndicates the sensor is in the trouble state.
Dirty LED
Power LEDIndicates the sensor is energized.
Resets the sensor when it is in the alarm or trouble state. Activates or tests the sensor when it is in
the normal state.
Indicates the amount of environmental compensation used by the sensor
(flashing continuously = 100%)
Controller’s Power LED is Off
1. Make sure the circuit supplying power to the controller is operational. If not, make sure JP2 and JP3 are
set correctly on the controller before applying power.
2. Verify that power is applied to the controller’s supply
input terminals. If power is not present, replace or re-
48TC
pair wiring as required.
Remote Test/Reset Station’s Trouble LED Does
flash When Performing a Dirty Test, But
Controller’s T r ouble LED
Does
the
1. Verify that the remote test/station is wired as shown
in Fig. 26. Repair or replace loose or m issing wiring.
2. Configure the sensor dirty test to activate the control ler’s supervision relay. See “Changing sensor dirty
test operation.”
Sensor’s Trouble LED is On, But the Controller’
Tr ouble LED is
OFF
Remove JP1 on the controller.
PROTECTIVE DEVICES
Compressor Protection
Overcurrent
Each compressor has internal linebreak motor protection.
Reset is automatic after compressor motor has cooled.
Overtemperatur
Each compressor has an internal protector to protect it
against excessively high discharge gas temperatures. Reset
is automatic.
High Pressure
Each system is provided with a high pressure switch
mountedonthedischargeline.Theswitchis
stem--mounted and brazed into the discharge tube. Trip
setting is 630 psig +/-- 10 psig (4344 +/-- 69 kPa) when
hot. Reset is aut omatic at 505 psig (3482 kPa).
e
Switch
Not
s
2.9and3.7 bhpmotorsareequippedwithan
overtemperature or protection device. The type of device
depends on the motor size. See Table 4.
The High Static option supply fan motor is equipped with
a pilot--circuit Thermix combination overtemperature/
overcurrentprotectiondevice.Thisdeviceresets
automatically. Do not bypass this switch to correct
trouble. Determine the cause and correct it.
The Thermik device is a snap--action overtemperature
protection device that is imbedded in the motor windings.
It is a pilot--circuit device that is wired into the unit’s 24--v
control circuit. When this switch reaches its trip setpoint,
it opens the 24--v control circ uit and causes al l unit
operation to cease. This device resets automatically when
the motor windings cool. Do not bypass this switch to
correct trouble. Determine the cause and correct it.
TheExternalmotoroverloaddeviceisa
specially--calibrated circuit breaker that is UL recognized
as a motor overload controller.It is an overcurrent
device.When the motor current exceeds the circuit
breaker setpoint, the device opens all motor power leads
and the motor shuts down. Reset requires a manual reset
at the overload switch. This device (designated IFCB) is
located on the side of the supply fan housing, behind the
fan access panel.
Troubleshooting supply fan motor overload trips:The
supply fan used in 48TC units is a forward--curved
centrifugal wheel. At a constant wheel speed, this wheel
has a characteristic that causes the fan shaft load to
DECREASE when the static pressure in the unit--duct
system increases and to INCREASE when the static
pressure in the unit--duct system decreases (and fan
airflow rate increases).Motor overload conditions
typically develop when the unit is operated with an access
panel removed, with unfinished duct work, in an
economizer--open mode, or a leak develops in the duct
system that allows a bypass back to unit return opening.
Low Pressure
Switch
Each system is protected against a loss of charge and low
evaporator coil loading condition by a low pressure switch
located on the suction line near the compressor. The
switch is stem--mounted. Trip setting is 54 psig +/-- 5 psig
(372 +/-- 34 kPa). Reset is automatic at 117 +/-- 5 psig
(807 +/-- 34 kPa).
Supply (Indoor) Fan Motor Pr
otection
Disconnect and lockout power when servicing fan motor.
Table 4 -- Overcurrent Device Type
Motor Size (bhp)Overload DeviceReset
1.7Internal LinebreakAutomatic
2.4Internal LinebreakAutomatic
2.9ThermikAutomatic
3.7ThermikAutomatic
4.7External
(Circuit Breaker)
24
Manual
Condenser Fan Motor Protection
The conde nser fan motor is interna lly protected against
overtemperature.
Control Circuit, 24--V
The control circuit is protected against overcurrent
conditions by a circuit breaker mounted on control
transformer TRAN. Reset is manual.
GAS HEATING SYSTEM
General
The heat exchanger system consists of a gas valve feeding
multiple inshot burners off a manifold. The burners fire
into matching primary tubes. The primary tubes discharge
into combustion plenum where gas flow converges into
secondary tubes. The secondary tubes exit into the
induced draft fan wheel inlet. The induced fan wheel
discharges into a flue passage and flue gases exit out a
flue hood on the side of the unit. The induced draft fan
motor includes a Hall Effect sensor circuit that confirms
adequate wheel speed via the Integrated Gas Control
(IGC) board. Safety switches include a Rollout Switch (at
the top of the burner compartment) and a limit switch
(mounted through the fan deck, over the tubes). (See Fig.
29 and 30.)
INDUCED-
DRAFT
MOTOR
MOUNTING
PLATE
BURNER
SECTION
INDUCED-
DRAFT MOTOR
MANIFOLD
PRESSURE
TAP
GAS
VALVE
Fig. 29 -- Burner Section Details
Limit Switch
and Shield
Fig. 30 -- Limit Switch Location
ROLLOUT
SWITCH
FLUE
EXHAUST
VESTIBULE
PLATE
BLOWER
HOUSING
C09153
C08284
Fuel Types and Pressures
Natural Gas — The 48TC unit is factory--equipped for use
with Natural Gas fuel at elevation under 2000 ft (610 m).
See section Orifice Replacement for information in
modifying this unit for insta llation at elevations above
2000 ft (610 m).
Gas line pressure entering the unit’s main gas valve must
be within specified ranges. Adjust unit gas regulator valve
as required or consult local gas utility.
Table 5 – Natural Gas Supply Line Pressure Ranges
UNIT MODELUNIT SIZEMINMAX
48TCAll
4.0 in. wg
(996 Pa)
Manifold pressure is factory--adjusted for NG fuel use.
Adjust as required to obtain best flame characteristic.
Table 6 – Natural Gas Manifold Pressure Ranges
UNIT
MODEL
48TCAll
UNIT
SIZE
HIGH
FIRE
3.5 in. wg
(872 Pa)
LOW
FIRE
1.7 in. wg
(423 Pa)
Liquid Propane — Accessory packages are available for
field--installation that will convert the 48TC unit to
operate with Liquid Propane (LP) fuels. These kits include
new orifice spuds, new springs for gas valves and a supply
line low pressure switch. See section on Orifice
Replacement for details on orifice size selections.
Fuel line pressure entering unit gas valve must remain
within specified range.
Table 7 – Liquid Propane Supply Line Pressure Ranges
UNIT MODELUNIT SIZEMINMAX
48TCAll
11.0 in. wg
(2740 Pa)
Manifold pressure for LP fuel use must be adjusted to
specified range. Follow instructions in the accessory kit to
make initial readjustment.
Table 8 – Liquid Propane Manifold Pressure Ranges
UNIT MODELUNIT SIZEHIGH FIRELOW FIRE
48TCAll
10.0 in. wg
(2490 Pa)
Supply Pressure Switch — The LP conversion kit includes
a supply low pressure switch. The switch contacts (from
terminal C to terminal NO) will open the gas valve power
whenever the supply line pressure drops below the
setpoint. (See Fig. 31 and 32.) If t he low pressure remains
open for 15 minutes during a call for heat , the IGC circuit
will initiate a Ignition Fault (5 flashes) lockout. Reset of
the low pressure switch is automatic on rise in supply line
pressure. Reset of the IGC requires a recycle of unit
power after the low pressure switch has closed.
13.0 in. wg
(3240 Pa)
RANGE
2.0---5.0 in. wg (Hi)
(498--- 1245 Pa)
13.0 in. wg
(3240 Pa)
5.0 in. wg
(1245 Pa)
48TC
25
48TC
48TCDD08 only
C08238
This switch also prevents operation when the propane tank
level is low which can result in gas with a high
concentration of impurities, additives, and residues that
have settled to the bottom of the tank. Operation under
these conditions can cause harm to the heat exchanger
system. Contact your fuel supplier if t his condition is
suspected.
Flue Gas Passageways
To inspect the flue collector box and upper areas of the
heat exchanger:
1. Re move the combustion blower whe el and motor assembly according to directions in Combustion--Air
Blower section. (See Fig. 33.)
2. Re move the flue cover to inspect the heat exchanger.
3. Clean all surfaces as required using a wire brush.
Combustion--Air Blower
Clean periodically to assure proper airflow and heating
efficiency.Inspectblowerwheeleveryfalland
periodically during heating season. For the first heating
season, inspect blower wheel bi--monthly to determine
proper cleaning frequency.
To access burner section, slide the sliding burner partition
out of the unit.
C08239
All 48TC*D except DD08
Fig. 31 -- LP Low Pressure Switch (Installed)
C
PNK
LP LPS
GRA
NO
BRN
MGV
C
C08285
IGC
BRN
J2-11
IGC
J2-12
TSTAT
W2
Fig. 32 -- LP Supply Line Low Pressure Switch Wiring
To inspect blower wheel, shine a flashlight into draft hood
opening. If cleaning is required, remove motor and wheel
as follows:
1. Slide burner access panel out.
2. Re move the 7 screws that attach induced--draft motor
housing to vestibule plate. (See Fig. 33.)
3. The blower wheel can be cleaned at this point. If additional cleaning is required, continue with Steps 4
and 5.
4. To remove blower from the motor shaft, remove 2
setscrews.
5. To remove motor, remove the 4 screws that hold the
motor to mounting plate. Remove the motor cooling
fan by removing one setscrew. Then remove nuts that
hold motor to mounting plate.
6. To reinstall, reverse the procedure outlined above.
26
WIND CAP
M
ASSEMBLY
(SHOWN
INVERTED,
AS SHIPPED)
HEATER TUBE
ASSEMBLY
SEAL STRIPS,
SPONGE RUBBER
REGULATOR
GASKET
REGULATOR
RETAINER
48TC
SUPPORT INSULATION ASSEMBLY
INDUCER FAN-MOTOR ASSEMBLY
BURNER ASSEMBLY
C08227
Fig. 33 -- Heat Exchanger Assembly
Burners and Igniters
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in
equipment damage.
When working on gas train, do not hit or plug
orifice spuds.
Main Burners
To access burners, remove burner access panel and slide
out burner partition. At the beginning of each heating
season, inspect for deterioration or blockage due to
corrosion or other causes. Observe the main burner flames
and adjust, if ne cessary.
Orifice projection — Refer to Fig. 34 for maximum
projection dimension for orifice face to manifold tube.
ORIFICE
1.00-in
(25.4 mm)
ANIFOLD
PIPE
C08211
Fig. 34 -- Orifice Projection
Removal and Replacement of Gas Train
See Fig. 29, 33, and 35.
1. Shut off manual gas valve.
2. Shut off power to unit.
3. Slide out burner partition.
4. Disconne ct gas piping at unit gas valve.
5. Remove wires connected to gas valve. Mark each
wire.
27
MANIFOLD PRESSURE TAP
GAS
VALVE
BURNERS
Fig. 35 -- Burner Tray Details
6. Remove igniter wires and sensor wires at the Integrated Gas Unit Controller (IGC). (See Fig. 36.)
7. Remove the 2 screws that attach the burner rack to
the vestibule plate. (See Fig. 33.)
48TC
8. Slide the burner tray out of the unit. (See Fig. 35.)
9. To reinstall, reverse the procedure outlined above.
Cleaning and Adjustment
1. Re move burner rack from unit as described in Removal and Replacement of Gas Train section, above.
2. Inspect burners; if dirty, remove burners from rack.
(Mark each burner to identify its position before removing from the rack.)
3. Use a soft brush to clean burners and cross--over port
as required.
4. Adjust spark gap. (See Fig. 37.)
5. If factory orifice has been removed, check that each
orifice is tight at its threads into the manifold pipe
and that orifice projection does not exceed maximum
valve. (See Fig. 34).
6. Re install burners on rack in t he same loca tions as
factory--installed. (The outside crossover flam e regions of the outermost burners are pinched off to prevent excessive gas flow from the side of the burner
assembly. If the pinched crossovers are installed
between two burners, the flame will not ignite properly.)
RACEWAY
INTEGRATED GAS UNIT
CONTROLLER (IGC)
C09154
7. Re install burner rack as described in Removal and
Replacement of Gas Train section, above.
Gas Valve — All unit sizes are equipped with 2--stage gas
valves. See Fig. 38 for locat ions of adjustment screws and
features on the gas valves.
To adjust gas valve pressure settings:
IMPORTANT: Leak check all gas connections including
the main service connection, gas valve, gas spuds, and
manifold pipe plug. All leaks must be repaired before
firing unit.
Check Unit Operation and Make Necessary
Adjustments
NOTE: Gas supply pressure at gas valve inlet must be
within specified ranges for fuel type and unit size. (See
Table 5, 6, 7, and 8.)
1. Remove manifold pressure tap plug from manifold
and connect pressure gauge or manometer. (See Fig.
35.)
2. Turn on electrical supply.
3. Turn on unit main gas valve.
4. Set room thermostat to call for heat. Verify high-stage heat operation before attempting to adjust manifold pressure.
5. When main burners ignite, check all fittings, manifold, and orifices for leaks.
6. Adjust high--stage pressure to specified setting by
turning the plastic adjustment screw clockwise to increase pressure, counter--clockwise to decrease pressure.
7. Set room thermostat to call for low--stage heat. Adjust
low-- stage pressure to specified setting.
8. Re place regulator cover screw(s) when finished.
9. With burner access panel removed, observe unit heating operation in both high stage and low stage operation. Observe burner flames to see if they are blue in
appearance, and that the flames are approximately the
same for each burner.
10. Turn off unit, remove pressure manometer and replace the 1/8 in. pipe fitting on the gas manifold. (See
Fig. 35.)
Limit Switch
HOLE IN END PANEL (HIDDEN)
Fig. 36 -- Unit Control Box/IGC Location
Remove blower access panel. Limit switch is located on
the fan deck. (See Fig. 30.)
Unit is equipped with a direct spark ignition 100% lockout
system. Integrated Gas Unit Controller (IGC) is located in
the control box. (See Fig. 36.) The IGC contains a
self--diagnostic LED (light--emitting diode). A single LED
(see Fig. 39) on the IGC provides a visual display of
operational or sequential problems when the power supply
is uninterrupted. When a break in power occurs, the IGC
will be reset (resulting in a loss of fault history) and the
indoor (evaporator) fan ON/OFF times will be reset. The
LED error code can be observed through the viewport.
During servicing refer to the label on the control box
cover or Table 9 for an explanation of LED error code
descriptions.
If lockout occurs, unit may be reset by interrupting power
supply to unit for at least 5 seconds.
Table 9 – LED Error Code Description*
LED INDICATION
ONNormal Operation
OFFHardware Failure
2FlashesLimit Switch Fault
3FlashesFlame Sense Fault
4Flashes4 Consecutive Limit Switch Faults
5FlashesIgnition Lockout Fault
6FlashesInduced--- Draft Motor Fault
7FlashesRollout Switch Fault
8FlashesInternal Control Fault
9FlashesSoftware Lockout
LEGEND
LED --- L i g h t E m i t t in g D i o d e
* A 3 – second pause exists between LED error code flashes. If
more than one error code exists, all applicable codes will be
displayed in numerical sequence.
ERROR CODE
DESCRIPTION
IMPORTANT: Refer to Troubleshooting Tables 13 and
14 for additional information.
29
48TC
48TCDD08 only
C08240
Fig. 38 -- Gas Valve
All 48TC*D except DD08
C08241
Orifice Replacement
This unit uses orifice type LH32RFnnn (where nnn
indicates orifice reference size). When replacing unit
orifices, order the necessary parts via Carrier RCD. See
Table 11 for available orifice sizes. See Table 12 for
orifice sizes for Natural Gas and LP fuel usage at various
elevations above sea level.
Check that each replacement orifice is tight at its threads
into the manifold pipe and that orifice projection does not
exceed maximum value. (See Fig. 34.)
30
Loading...
+ 68 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.