Carrier 48TCA04-A12 User Manual

48TCA04---A12 Nominal 3 to 10 Tons Wit h Puro n® (R---410A) Refrigerant
Service and Maintenance Instructions
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 1....................
UNIT ARRANGEMENT AND ACCESS 2...........
SUPPLY FAN (BLOWER) SECTION 4..............
COOLING 5....................................
PURONR (R--410A) REFRIGERANT 8..............
COOLING CHARGING CHARTS 9.................
CONVENIENCE OUTLETS 14....................
SMOKE DETECTORS 15.........................
PROTECTIVE DEVICES 22.......................
GAS HEATING SYSTEM 22......................
PREMIERLINKT CONTROL 34...................
RTU--MP CONTROL SYSTEM 42..................
ECONOMI$ER SYSTEMS 55......................
WIRING DIAGRAMS 63.........................
PRE--START--UP 66..............................
START--UP, GENERAL 66........................
START--UP, PREMIERLINKT CONTROL 68........
START--UP, RTU--MP CONTROL 68................
OPERATING SEQUENCES 71.....................
FASTENER TORQUE VALUES 81.................
APPENDIX II. PHYSICAL DATA 83................
APPENDIX III. FAN PERFORMANCE 87...........
APPENDIX IV. ELECTRICAL DATA 99.............
APPENDIX V. WIRING DIAGRAM LIST 104........
APPENDIX VI. MOTORMASTER SENSOR
LOCATIONS 105................................
UNIT START-UP CHECKLIST 107.................
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment. Untrained personnel can perform the basic maintenance functions of replacing filters. Trained service personnel should perform all other operations.
When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety--alert symbol
instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
. When you see this symbol on the unit and in
!
WARNING
!
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Refer to the User’s Information Manual provided with this unit for more details.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
What to do if you smell gas:
DO NOT try to light any appliance. DO NOT touch any electrical switch, or use any phone in your building. IMMEDIATELY call your gas supplier from a neighbor’s phone. Follow the gas supplier’s
48TC
instructions. If you cannot reach your gas supplier, call the fire department.
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock and rotating equipment could cause injury.
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Units with convenience outlet circuits may use multiple disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it. Tag--out this switch, if necessary.
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect gas piping from unit when pressure testing at pressure greater than 0.5 psig. Pressures greater than 0.5 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 0.5 psig, it must be replaced before use. When pressure testing field-supplied gas piping at pressures of 0.5 psig or less, a unit connected to such piping must be isolated by closing the manual gas valve(s).
UNIT ARRANGEMENT AND ACCESS
General
Fig. 1 and Fig. 2 show general unit arrangement and access locations.
FILTER ACCESS PANEL
COMPRESSOR ACCESS PANEL (04-07 only)
OUTDOOR-AIR OPENING AND INDOOR COIL ACCESS PANEL
C08449
Fig. 1 -- Typical Access Panel Locations
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury, death and/or equipment damage.
Puron (R--410A) refrigerant systems operate at higher pressures than standard R--22 systems. Do not use R--22 service equipment or components on Puron refrigerant equipment.
BLOWER ACCESS PANEL
COMPRESSOR (08-12 only)
Fig. 2 -- Blower Access Panel Location
CONTROL BOX
C08450
Routine Maintenance
These items should be part of a routine maintenance program, to be checked every month or two, until a specific schedule for each can be identified for this installation:
2
Quarterly Inspection (and 30 days after initi al start)
R
S Return air filter replacement S Outdoor hood inlet filters cleaned S Belt tension checked S Belt condition checked S Pulley alignment checked S Fan shaft bearing locking collar tightness checked S Condenser coil cleanliness checked S Condensate drain checked
Seasonal Maintenance
These items should be checked at the beginning of each season (or more often if local conditions and usage patterns dictate):
Conditioning
Air
S Condenser fan motor mounting bolts tightness S Compressor mounting bolts S Condenser fan blade positioning S Control box cleanliness and wiring condition S Wire terminal tightness S Refrigerant charge level S Evaporator coil cleaning S Evaporator blower motor amperage
Heating
S Heat exchanger flue passageways cleanliness S Gas burner condition S Gas manifold pressure S Heating temperature rise
Economizer or Outside Air
S Inlet filters condition S Check damper travel (economizer) S Check gear and dampers for debris and dirt
Air Filters and Scr
eens
Each unit is equipped with return air filters. If the unit has an economizer, it will also have an outside air screen. If a manual outside air damper is added, an inlet air screen will also be present.
Each of these filters and screens will need to be periodically replaced or cleaned.
Return Air
Filters
Return air filters are disposable fiberglass media type. Access to the filters is through the small lift--out panel located on the rear side of the unit, above the evaporator/return air access panel. (See Fig. 1.)
Damper
To remove the filters:
1. Grasp the bottom flange of the upper panel.
2. Lift up and swing the bottom out until the panel dis­engages and pulls out.
3. Reach inside and extract the filters from the filter rack.
4. Replace these filters as required with similar replace­ment filters of same size.
To re--install the access panel:
1. Slide the top of the panel up under the unit top panel.
2. Slide the bottom into the side channels.
3. Push the bottom flange down until it contacts the top of the lower panel (or economizer top).
IMPORTANT: DO NOT OPERATE THE UNIT WITHOUT THESE FILTERS!
Outside Air
Hood
Outside air hood inlet screens are permanent aluminum--mesh type filters. Check these for cleanliness. Remove the screens when cleaning is required. Clean by washing with hot low--pressure water and soft detergent and replace all screens before restarting the unit. Observe the flow direction arrows on the side of each filter frame.
Economizer Inlet Air Screen
This air screen is retained by spring clips under the top edge of the hood. (See Fig. 3.)
17 1/4”
DIVIDER
OUTSIDE AIR
HOOD
CLEANABLE
BAROMETRIC RELIEF
ALUMINUM FILTER
FILTER
FILTE CLIP
C06027
Fig. 3 -- Filter Installation
To remove the filter, open the spring clips. Re--install the filter by placing the frame in its track, then closing the spring clips.
48TC
Manual Outside Air Hood Screen
This inlet screen is secured by a retainer angle across the top edge of the hood. (See Fig. 4.)
3
Fig. 4 -- Screens Installed on Outdoor--Air Hood
(Sizes 7--1/2 to 12--1/2 Tons Shown)
To remove the screen, loosen the screws in the top retainer
48TC
and slip the retainer up until the filter can be removed. Re--install by placing the frame in its track, rotating the retainer back down and tighten all screws.
SUPPLY F AN (BLOWER) SECTION
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on the fan system, shut off all unit power and tag--out the unit disconnect switch. Do not reach into the fan section with power still applied to unit.
Supply Fan (Belt--Drive)
The supply fan system consists of a forward--curved centrifugal blower wheel on a solid shaft with two concentric type bearings, one on each side of the blower housing. A fixed--pitch driven pulley is attached to the fan shaft and an adjustable--pitch driver pulley is on the motor. The pulleys are connected using a “V” type belt. (See Fig. 5.)
C07156
inside surfaces. Check belt tension by using a spring--force tool (such as Browning’s Part Number “Belt Tension Checker” or equivalent tool); tension should be 6--lbs at a 5/8--in. deflection when measured at the centerline of the belt span. This point is at the center of the belt when measuring the distance between the motor shaft and the blower shaft.
NOTE: Without the spring--tension tool, place a straight edge across the belt surface at the pulleys, then deflect the belt at mid--span using one finger to a 1/2--in. deflection.
Adjust belt tension by loosening the motor mounting plate front bolts and rear bolt and sliding the plate toward the fan (to reduce tension) or away from fan (to increase tension). Ensure the blower shaft and the motor shaft are parallel to each other (pulleys aligned). Tighten all bolts when finished.
To replace the belt:
1. Use a belt with same section type or similar size. Do not substitute a “FHP” type belt. When installing the new belt, do not use a tool (screwdriver or pry--bar) to force the belt over the pulley flanges, this will stress the belt and cause a reduction in belt life.
2. Loosen the motor mounting plate front bolts and rear bolts.
3. Push the motor and its mounting plate towards the blower housing as close as possible to reduce the cen­ter distance between fan shaft and motor shaft.
4. Remove the belt by gently lifting the old belt over one of the pulleys.
5. Install the new belt by gently sliding the belt over both pulleys and then sliding the motor and plate away from the fan housing until proper tension is achieved.
6. Check the alignment of the pulleys, adjust if neces­sary.
7. Tighten all bolts.
8. Check the tension after a few hours of runtime and re--adjust as required.
Adjustable--Pitch Pulley on
The motor pulley is an adjustable--pitch type that allows a servicer to implement changes in the fan wheel speed to match as--installed ductwork systems. The pulley consists of a fixed flange side that faces the motor (secured to the motor shaft) and a movable flange side that can be rotated around the fixed flange side that increases or reduces the pitch diameter of this driver pulley. (See Fig. 6.)
Motor
C07087
Fig. 5 -- Belt Drive Motor Mounting
Belt
Check the belt condition and tension quarterly. Inspect the belt for signs of cracking, fraying or glazing along the
As the pitch diameter is changed by adjusting the position of the movable flange, the centerline on this pulley shifts laterally (along the motor shaft). This creates a requirement for a realignment of the pulleys after any adjustment of the movable flange. Also reset the belt tension after each realignment.
Check the condition of the motor pulley for signs of wear. Glazing of the belt contact surfaces and erosion on these surfaces are signs of improper belt tension and/or belt slippage. Pulley replacement may be necessary.
4
To change fan speed:
1. Shut off unit power supply.
2. Loosen belt by loosening fan motor mounting nuts. (See Fig. 5.)
3. Loosen movable pulley flange setscrew. (See Fig. 6.)
4. Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. Increasing fan speed increases load on motor. Do not exceed maximum speed specified.
5. Set movable flange at nearest keyway of pulley hub and tighten setscrew to torque specifications.
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft. Make angular align­ment by loosening motor from mounting.
3. Tighten fan pulley setscrews and motor mounting bolts to torque specifications.
4. Recheck belt tension.
Motor
When replacing the motor, also replace the external--tooth lock washer (star washer) under the motor mounting base; this is part of the motor grounding system. Ensure the teeth on the lock washer are in contact with the motor’s painted base. Tighten motor mounting bolts to 120 +/-- 12 in--lbs.
Changing fan wheel speed by changing pulleys: The horsepower rating of the belt is primarily dictated by the pitch diameter of the smaller pulley in the drive system (typically the motor pulley in these units). Do not install a replacement motor pulley with a smaller pitch diameter than provided on the original factory pulley. Change fan wheel speed by changing the fan pulley (larger pitch diameter to reduce wheel speed, smaller pitch diameter to increase wheel speed) or select a new system (both pulleys and matching belt(s)).
Before changing pulleys to increase fan wheel speed, check the fan performance at the target speed and airflow rate to determine new motor loading (bhp). Use the fan performance tables or use the Packaged Rooftop Builder software program. Confirm that the motor in this unit is capable of operating at the new operating condition. Fan shaft loading increases dramatically as wheel speed is increased.
48TC
C07075
Fig. 6 -- Supply--Fan Pulley Adjustment
Bearings
This fan system uses bearings featuring concentric split locking collars. The collars are tightened through a cap screw bridging the split portion of the collar. The cap screw has a Torx T25 socket head. To tighten the locking collar: Hold the locking collar tightly against the inner race of the bearing and torque the cap screw to 65--70 in--lb (7.4--7.9 Nm). See Fig. 7.
To reduce vibration, replace the motor’s adjustable pitch pulley with a fixed pitch pulley (after the final airflow balance adjustment). This will reduce the amount of vibration generated by the motor/belt--drive system.
COOLING
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury, death and/or equipment damage.
This system uses PuronR refrigerant which has higher pressures than R--22 and other refrigerants. No other refrigerant may be used in this system. Gauge set, hoses, and recovery system must be designed to handle Puron refrigerant. If unsure about equipment, consult the equipment manufacturer.
Condenser Coil
The condenser coil is fabricated with round tube copper hairpins and plate fins of various materials and/or coatings (see Model Number Format in the Appendix to identify the materials provided in this unit). The coil may be one--row or composite--type two--row. Composite two--row coils are two single--row coils fabricated with a single return bend end tubesheet.
Fig. 7 -- Tightening Locking Collar
C08121
Condenser Coil Maintenance and Cleaning Recommendation
Routine cleaning of coil surfaces is essential to maintain proper operation of the unit. Elimination of contamination and removal of harmful residues will greatly increase the
5
life of the coil and extend the life of the unit. The following maintenance and cleaning procedures are recommended as part of the routine maintenance activities to extend the life of the coil.
Remove Surface Loaded
Fibers
Surface loaded fibers or dirt should be removed with a vacuum cleaner. If a vacuum cleaner is not available, a soft non--metallic bristle brush may be used. In either case, the tool should be applied in the direction of the fins. Coil surfaces can be easily damaged (fin edges can be easily bent over and damage to the coating of a protected coil) if the tool is applied across the fins.
NOTE: Use of a water stream, such as a garden hose, against a surface loaded coil will drive the fibers and dirt into the coil. This will make cleaning efforts more difficult. Surface loaded fibers must be completely removed prior to using low velocity clean water rinse.
48TC
Periodic Clean Water
Rinse
A periodic clean water rinse is very beneficial for coils that are applied in coastal or industrial environments. However, it is very important that the water rinse is made with a very low velocity water stream to avoid damaging the fin edges. Monthly cleaning as described below is recommended.
Two--Row Coils
Clean coil as follows:
1. Turn off unit power, tag disconnect.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. See Fig. 8. To hold top panel open, place coil corner post between top panel and center post. See Fig. 9.
C08205
Fig. 8 -- Cleaning Condenser Coil
Routine Cleaning of Coil
Surfaces
Periodic cleaning with TotalineR environmentally sound coil cleaner is essential to extend the life of coils. This cleaner is available from Carrier Replacement Components Division as part number P902--0301 for a one gallon container, and part number P902--0305 for a 5 gallon container. It is recommended that all coils, including standard aluminum, pre--coated, copper/copper or E--coated coils be cleaned with the Totaline environmentally sound coil cleaner as described below. Coil cleaning should be part of the unit’s regularly scheduled maintenance procedures to ensure long life of the coil. Failure to clean the coils may result in reduced durability in the environment.
Avoid use of:
S coil brighteners S acid cleaning prior to painting S high pressure washers S poor quality water for cleaning
Totaline environmentally sound coil cleaner is nonflammable, hypo allergenic, non bacterial, and a USDA accepted biodegradable agent that will not harm the coil or surrounding components such as electrical wiring, painted metal surfaces, or insulation. Use of non--recommended coil cleaners is strongly discouraged since coil and unit durability could be affected.
C08206
Fig. 9 -- Propping Up Top Panel
4. Remove screws securing coil to compressor plate and compressor access panel.
5. Remove fastener holding coil sections together at re­turn end of condenser coil. Carefully separate the out­er coil section 3 to 4 in. from the inner coil section. See Fig. 10.
One--Row Coil
Wash coil with commercial coil cleaner. It is not necessary to remove top panel.
C08207
Fig. 10 -- Separating Coil Sections
6
6. Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner.
7. Secure inner and outer coil rows together with a field--supplied fastener.
8. Reposition the outer coil section and remove the coil corner post from between the top panel and center post. Reinstall the coil corner post and replace all screws.
Totaline Environmentally Sound Coil Cleaner Application Equipment
S 2--1/2 gallon garden sprayer S Water rinse with low velocity spray nozzle
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in accelerated corrosion of unit parts.
Harsh chemicals, household bleach or acid or basic cleaners should not be used to clean outdoor or indoor coils of any kind. These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion at the fin/tube interface where dissimilar materials are in contact. If there is dirt below the surface of the coil, use the Totaline environmentally sound coil cleaner.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in reduced unit performance or unit shutdown.
High velocity water from a pressure washer, garden hose, or compressed air should never be used to clean a coil. The force of the water or air jet will bend the fin edges and increase airside pressure drop.
Totaline Environmentally Sound Coil Cleaner Application Instructions
1. Proper eye protection such as safety glasses is recom­mended during mixing and application.
2. Remove all surface loaded fibers and dirt with a vacu­um cleaner as described above.
3. Thoroughly wet finned surfaces with clean water and a low velocity garden hose, being careful not to bend fins.
4. Mix Totaline environmentally sound coil cleaner in a 2--1/2 gallon garden sprayer according to the instruc­tions included with the cleaner. The optimum solution temperature is 100_F.
NOTE: Do NOT USE water in excess of 130_F, as th e enzymatic activity will be destroyed.
5. Thoroughly apply Totaline environmentally sound coil cleaner solution to all coil surfaces including finned area, tube sheets and coil headers.
6. Hold garden sprayer nozzle close to finned areas and apply cleaner with a vertical, up--and--down motion.
Avoid spraying in horizontal pattern to minimize po­tential for fin damage.
7. Ensure cleaner thoroughly penetrates deep into finned areas.
8. Interior and exterior finned areas must be thoroughly cleaned.
9. Finned surfaces should remain wet with cleaning solution for 10 minutes.
10. Ensure surfaces are not allowed to dry before rinsing. Reapplying cleaner as needed to ensure 10--minute saturation is achieved.
11. Thoroughly rinse all surfaces with low velocity clean water using downward rinsing motion of water spray nozzle. Protect fins from damage from the spray nozzle.
Evaporator Coil
Cleaning the Evaporator Coil
1. Turn unit power off. Install lockout tag. Remove evaporator coil access panel.
2. If economizer or two--position damper is installed, re­move economizer by disconnecting Molex plug and removing mounting screws.
3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dish­washer detergent in a pressurized spray canister. Wash both sides of coil and flush with clean water. For best results, back--flush toward return--air section to re­move foreign material. Flush condensate pan after completion.
5. Reinstall economizer and filters.
6. Reconnect wiring.
7. Replace access panels.
Evaporator Coil M etering
The metering devices are multiple fixed--bore devices (Acutrolt) swedged into the horizontal outlet tubes from the liquid header, located at the entrance to each evaporator coil circuit path. These are non--adjustable. Service requires replacing the entire liquid header assembly.
To check for possible blockage of one or more of these metering devices, disconnect the supply fan contactor (IFC) coil, then start the compressor and observe the frosting pattern on the face of the evaporator coil. A frost pattern should develop uniformly across the face of the coil starting at each horizontal header tube. Failure to develop frost at an outlet tube can indicate a plugged or a missing orifice.
Devices
Refrigerant System Pressure Access Ports
There are two access ports in the system -- on the suction tube near the compressor and on the discharge tube near the compressor. These are brass fittings with black plastic caps. The hose connection fittings are standard 1/4 SAE male flare couplings.
The brass fittings are two--piece High Flow valves, with a receptacle base brazed to the tubing and an integral spring--closed check valve core screwed into the base.
48TC
7
(See Fig. 11.) This check valve is permanently assembled into this core body and cannot be serviced separately; replace the entire core body if necessary. Service tools are available from RCD that allow the replacement of the check valve core without having to recover the entire system refrigerant charge. Apply compressor refrigerant oil to the check valve core’s bottom o--ring. Install the fitting body with 96 +/ --10 in--lbs of torque; do not overtighten.
Refrigerant Charge
Amount of refrigerant charge is listed on the unit’s nameplate. Refer to Carrier GTAC2--5 Charging, Recovery, Recycling and Reclamation training manual and the following procedures.
Unit panels must be in place when unit is operating during the charging procedure.
Charge
No
PURONR (R--410A) REFRIGERANT
This unit is designed for use with Puron (R--410A) refrigerant. Do not use any other refrigerant in this system.
Puron (R--410A) refrigerant is provided in pink (rose) colored cylinders. These cylinders are available with and
48TC
without dip tubes; cylinders with dip tubes will have a label indicating this feature. For a cylinder with a dip tube, place the cylinder in the upright position (access valve at the top) when removing liquid refrigerant for charging. For a cylinder without a dip tube, invert the cylinder (access valve on the bottom) when removing liquid refrigerant.
Because Puron (R--410A) refrigerant is a blend, it is strongly recommended that refrigerant always be removed from the cylinder as a liquid. Admit liquid refrigerant into the system in the discharge line. If adding refrigerant into the suction line, use a commercial metering/expansion device at the gauge manifold; remove liquid from the cylinder, pass it through the metering device at the gauge set and then pass it into the suction line as a vapor. Do not remove Puron (R--410A) refrigerant from the cylinder as a vapor.
Use standard evacuating techniques. After evacuating system, weigh in the specified amount of refrigerant.
Low--Charge
Cooling
Using Cooling Charging Charts, Fig. 12, vary refrigerant until the conditions of the appropriate chart are met. Note the charging charts are different from type normally used. Charts are based on charging the units to the correct superheat for the various operating conditions. Accurate pressure gauge and temperature sensing device are required. Connect the pressure gauge to the service port on the suction line. Mount the temperature sensing device on the suction line and insulate it so that outdoor ambient temperature does not affect the reading. Indoor--air cfm must be within the normal operating range of the unit.
To Use Cooling Charging
Charts
Take the outdoor ambient temperature and read the suction pressure gauge. Refer to chart to determine what suction temperature should be. If suction temperature is high, add refrigerant. If suction temperature is low, carefully recover some of the charge. Recheck the suction pressure as charge is adjusted.
5/8” HEX
SEAT
.47
1/2-20 UNF RH
0.596
o
30
WASHER
O-RING
This surface provides a metal to metal seal when torqued into the seat. Appropriate handling is required to not scratch or dent the surface.
Fig. 11 -- CoreMax Access Port Assembly
8
CORE
(Part No. EC39EZ067)
1/2" HEX
o
45
DEPRESSOR PER ARI 720 +.01/-.035 FROM FACE OF BODY
7/16-20 UNF RH
C08453
SIZE DESIGNATION
A04 3 A05 4 A06 5 A07 6 A08 7.5 A09 8.5 A12 10
NOMINAL TONS
REFERENCE
COOLING CHARGING CHARTS
EXAMPLE:
Model 48TC*A04
Outdoor Temperature 85_F(29_C)..................
Suction Pressure 140 psig (965 kPa).................
Suction Temperature should be 60_F(16_C)..........
48TC
Fig. 12 -- Cooling Charging Charts
9
C08203
48TC
COOLING CHARGING CHARTS (cont.)
C08204
Fig. 12 (cont.) -- Cooling Charging Charts
10
C08228
COOLING CHARGING CHARTS (cont.)
48TC
C08229
Fig. 12 (cont.) -- Cooling Charging Charts
11
C08437
48TC
COOLING CHARGING CHARTS (cont.)
C08438
Fig. 12 (cont.) -- Cooling Charging Charts
12
C08439
Table 1 – Cooling Service Analysis
PROBLEM CAUSE REMEDY
Power failure. Call power company. Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker.
Compressor and Condenser Fan Will Not Start.
Compressor Will Not Start But Condenser Fan Runs.
Compressor Cycles (other than normally satisfying ther­mostat).
Compressor Operates Continuously.
Excessive Head Pressure.
Head Pressure Too Low.
Excessive Suction Pressure.
Suction Pressure Too Low.
Evaporator Fan Will Not Shut Off.
Compressor Makes Excessive Noise.
Defective thermostat, contactor, transformer, or control relay.
Insufficient line voltage. Determine cause and correct. Incorrect or faulty wiring. Check wiring diagram and rewire correctly. Thermostat setting too high. Lower thermostat setting below room temperature. Faulty wiring or loose connections in
compressor circuit.
Compressor motor burned out, seized, or internal overload open.
Defective run/start capacitor, overload, start relay.
Onelegofthree---phasepowerdead.
Refrigerant overcharge or undercharge.
Defective compressor. Replace and determine cause. Insufficient line voltage. Determine cause and correct. Blocked condenser. Determine cause and correct. Defective run/start capacitor, overload, or start
relay.
Defective thermostat. Replace thermostat. Faulty condenser--- fan motor or capacitor. Replace. Restriction in refrigerant system. Locate restriction and remove. Dirty air filter. Replace filter. Unit undersized for load. Decrease load or increase unit size. Thermostat set too low. Reset thermostat. Low refrigerant charge. Locate leak; repair and recharge. Leaking valves in compressor. Replace compressor. Air in system. Recover refrigerant, evacuate system, and recharge. Condenser coil dirty or restricted. Clean coil or remove restriction. Dirty air filter. Replace filter. Dirty condenser coil. Clean coil. Refrigerant overcharged. Recover excess refrigerant. Air in system. Recover refrigerant, evacuate system, and recharge. Condenser air restricted or air short --- cycling. Determine cause and correct. Low refrigerant charge. Check for leaks; repair and recharge. Compressor valves leaking. Replace compressor. Restrictioninliquidtube. Remove restriction. High head load. Check for source and eliminate. Compressor valves leaking. Replace compressor. Refrigerant overcharged. Recover excess refrigerant. Dirty air filter. Replace filter. Low refrigerant charge. Check for leaks; repair and recharge. Metering device or low side restricted. Remove source of restriction.
Insufficient evaporator airflow.
Temperature too low in conditioned area. Reset thermostat. Outdoor ambient below 25˚F. Install low---ambient kit.
Time off delay not finished. W a i t f o r 3 0 --- s e con d o f f delay.
Compressor rotating in wrong direction. Reversethe3---phasepowerleads.
Replace component.
Check wiring and repair or replace.
Determine cause. Replace compressor.
Determine cause and replace.
Replace fuse or reset circuit breaker. Determine cause.
Recover refrigerant, evacuate system, and recharge to nameplate.
Determine cause and replace.
Increase air quantity. Check filter and replace if necessary.
48TC
13
Compressor
Lubrication
The compressor is charged with the correct amount of oil at the factory.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to components.
The compressor is in a PuronR refrigerant system and uses a polyolester (POE) oil. This oil is extremely hygroscopic, meaning it absorbs water readily. POE oils can absorb 15 times as much water as other oils designed for HCFC and CFC refrigerants. Avoid exposure of the oil to the atmosphere.
48TC
Replacing Compressor
2. Remove condenser--fan assembly (grille, motor, and fan).
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 13.
5. Tighten setscrews.
6. Replace condenser--fan assembly.
Conduit
0.14 in + 0.0 / -0.03
C08448
Fig. 13 -- Condenser Fan Adjustment
Troubleshooting Cooling System
Refer to Table 1 for additional troubleshooting topics.
The compressor used with Puron refrigerant contains a POE oil. This oil has a high affinity for moisture. Do not remove the compressor’s tube plugs until ready to insert the unit suction and discharge tube ends.
Compressor mounting bolt torque is 65--75 ft--lbs.
Compressor
On 3--phase units with scroll compressors, it is important to be certain compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the proper direction:
1. Connect service gauges to suction and discharge pres­sure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start--up.
NOTE: If the suction pressure does not drop and the discharge pressure does not rise to normal levels:
4. Note that the evaporator fan is probably also rotating in the wrong direction.
5. Turn off power to the unit.
6. Reverse any two of the unit power leads.
7. Reapply power to the compressor.
The suction and discharge pressure levels should now move to their normal start--up levels.
NOTE: When the compressor is rotating in the wrong direction, the unit makes an elevated level of noise and does not provide cooling.
Rotation
Filter Drier
CONVENIENCE OUTLETS
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Units with convenience outlet circuits may use multiple disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it. Tag--out this switch, if necessary.
Two types of convenience outlets are offered on 48TC models: Non--powered and unit--powered. Both types provide a 125--volt GFCI (ground--fault circuit--interrupter) duplex receptacle rated at 15--A behind a hinged waterproof access cover, located on the end panel of the unit. See Fig. 14.
Pwd-CO Transformer
Conv Outlet GFCI
Pwd-CO Fuse Switch
Replace whenever refrigerant system is exposed to atmosphere. Only use factory specified liquid--line filter driers with working pressures no less than 650 psig. Do not install a suction--line filter drier in liquid line. A liquid--line filter drier designed for use with Puron refrigerant is required on every unit.
Condenser--Fan Adjustment
1. Shut off unit power supply. Install lockout tag.
C08128
Fig. 14 -- Convenience Outlet Location
Non--powered type: This type requires the field
installation of a general--purpose 125--volt 15--A circuit powered from a source elsewhere in the building. Observe national and local codes when selecting wire size, fuse or
14
breaker requirements and disconnect switch size and location. Route 125--v power supply conductors into the bottom of the utility box containing the duplex receptacle.
Unit--powered type: A unit--mounted transformer is factory--installed to stepdown the main power supply voltage to the unit to 115--v at the duplex receptacle. This option also includes a manual switch with fuse, located in a utility box and mounted on a bracket behind the convenience outlet; access is through the unit’s control box access panel. See Fig. 14.
The primary leads to the convenience outlet transformer are not factory--connected. Selection of primary power source is a customer--option. If local codes permit, the transformer primary leads can be connected at the line--side terminals on a unit--mounted non--fused disconnect or HACR breaker switch; this will provide service power to the unit when the unit disconnect switch or HACR switch is open. Other connection methods will result in the convenience outlet circuit being de--energized when the unit disconnect or HACR switch is open. See Fig. 15.
lamps, etc; it is not intended to provide 15--amps loading for continuous duty loads (such as electric heaters for overnight use). Observe a 50% limit on circuit loading above 8--amps (i.e., limit loads exceeding 8--amps to 30 minutes of operation every hour).
Maintenance: Periodically test the GFCI receptacle by pressing the TEST button on the face of the receptacle. This should cause the internal circuit of the receptacle to trip and open the receptacle. Check for proper grounding wires and power line phasing if the GFCI receptacle does not trip as required. Press the RESET button to clear the tripped condition.
Fuse on powered type: The factory fuse is a Bussman “Fusetron” T--15, non--renewable screw--in (Edison base) type plug fuse.
Using unit--mounted convenience outlets: Units with unit--mounted convenience outlet circuits will often require that two disconnects be opened to de--energize all power to the unit. Treat all units as electrically energized until the convenience outlet power is also checked and de--energization is confirmed. Observe National Electrical Code Article 210, Branch Circuits, for use of convenience outlets.
48TC
CO8283
Fig. 15 -- Powered Convenience Outlet Wiring
UNIT
VOLTAGE
208,
230
460 480
575 600
CONNECT
AS
240
PRIMARY
CONNECTIONS
L1: RED +YEL L2: BLU + GRA
L1: RED Splice BLU + YEL L2: GRA
L1: RED L2: GRA
TRANSFORMER
TERMINALS
H1 + H3 H2 + H4
H1
H2 + H3
H4
H1 H2
Duty Cycle: The unit--powered convenience outlet has a duty cycle limitation. The transformer is intended to provide power on an intermittent basis for service tools,
SMOKE DETECTORS
Smoke detectors are available as factory--installed options on 48TC models. Smoke detectors may be specified for Supply Air only or for Return Air without or with economizer or in combination of Supply Air and Return Air. Return Air smoke detectors are arranged for vertical return configurations only. All components necessary for operation are factory--provided and mounted. The unit is factory--configured for immediate smoke detector shutdown operation; additional wiring or modifications to unit terminal board may be necessary to complete the unit and smoke detector configuration to meet project requirements.
System
The smoke detector system consists of a four--wire controller and one or two sensors. Its primary function is to shut down the rooftop unit in order to prevent smoke from circulating throughout the building. It is not to be used as a life saving device.
Controller
The controller (see Fig. 16) includes a controller housing, a printed circuit board, and a clear plastic cover. The controller can be connected to one or two compatible duct smoke sensors. The clear plastic cover is secured to the housing with a single captive screw for easy access to the wiring terminals. The controller has three LEDs (for Power, Trouble and Alarm) and a manual test/reset button (on the cover face).
15
Duct smoke sensor
controller
Conduit nuts
(supplied by installer)
Conduit sup port plate
Controller housing
and electronics
Conduit cou plings
(supplied by installer)
Fastener
(2X)
Terminal block cover
Cover gasket
(ordering option)
48TC
Alarm
Troub le
Power
Tes t / r e s e t switch
Fig. 16 -- Controller Assembly
Sensor
The sensor (see Fig. 17) includes a plastic housing, a printed circuit board, a clear plastic cover, a sampling tube inlet and an exhaust tube. The sampling tube (when used) and exhaust tube are attached during installation. The sampling tube varies in length depending on the size of the rooftop unit. The clear plastic cover permits visual inspections without having to disassemble the sensor. The cover attaches to the sensor housing using four captive screws and forms an airtight chamber around the sensing electronics. Each sensor includes a harness with an RJ45 terminal for connecting to the controller. Each sensor has four LEDs (for Power, Trouble, Alarm and Dirty) and a manual test/reset button (on the left--side of the housing).
Air is introduced to the duct smoke detector sensor’s sensing chamber through a sampling tube that extends into the HVAC duct and is directed back into the ventilation system through a (shorter) exhaust tube. The difference in air pressure between the two tubes pulls the sampled air through the sensing chamber. When a sufficient amount of smoke is detected in the sensing chamber, the sensor signals an alarm state and the controller automatically takes the appropriate action to shut down fans and blowers, change over air handling systems, notify the fire alarm control panel, etc.
The sensor uses a process called differential sensing to prevent gradual environmental changes from triggering false alarms. A rapid change in environmental conditions, such as smoke from a fire, causes the sensor to signal an alarm state but dust and debris accumulated over time does not.
Controll er cover
C08208
Duct smoke s ensor
Exhaust tube
See
Detail A
Detail A
Intake
gasket
Plug
TSD-CO2
(ordering option)
Sampling tube
(ordered separately)
Magnetic test/reset
switch
Exhaust gasket
Coupling
Alarm
Troub le
Sensor housing and electro nics
Power Dirty
Cover gasket
(ordering option)
Sensor cover
C08209
Fig. 17 -- Smoke Detector Sensor
For installations using two sensors, the duct smoke detector does not differentiate which sensor signals an alarm or trouble condition.
Smoke Detector Locations
Supply Air — The Supply Air smoke detector sensor is located to the left of the unit’s indoor (supply) fan. See Fig. 18. Access is through the fan access panel. There is no sampling tube used at this location. The sampling tube inlet extends through the side plate of the fan housing (into a high pressure area). The controller is located on a bracket to the right of the return filter, accessed through the lift--off filter panel.
Smoke Detector Sensor
C08245
Fig. 18 -- Typical Supply Air Smoke Detector Sensor
Location
16
Return Air without Economizer — The sampling tube is located across the return air opening on the unit basepan. See Fig. 19. The holes in the sampling tube face downward, into the return air stream. The sampling tube is connected via tubing to the return air sensor that is mounted on a bracket high on the partition between return filter and controller location. (This sensor is shipped in a flat--mounting location. Installation requires that this sensor be relocated to its operating location and the tubing to the sampling tube be connected. See installation steps below.)
Return Air Detector module (shipping position shown)*
Controller module
Completing Installation of Return Air Smoke Sensor:
Screws
Flexible Exhaust Tubes
Sample Tube
C08126
Fig. 21 -- Return Air Detector Shipping Position
Return Air Detector Sampling Tube
*RA detector must be moved from shipping position to operating position by installer
C07307
Fig. 19 -- Typical Return Air Detector Location
Return Air with Economizer — The sampling tube is inserted through the side plates of the economizer housing, placing it across the return air opening on the unit basepan. See Fig. 20. The holes in the sampling tube face downward, into the return air stream. The sampling tube is connected via tubing to the return air sensor that is mounted on a bracket high on the partition between return filter and controller location. (This sensor is shipped in a flat--mounting location. Installation requires that this sensor be relocated to its operating location and the tubing to the sampling tube be connected. See installation steps below.)
1. Unscrew the two screws holding the Return Air Sensor detector plate. See Fig. 21. Save the screws.
2. Remove the Return Air Sensor and its detector plate.
3. Rotate the detector plate so the sensor is facing out­wards and the sampling tube connection is on the bot­tom. See Fig. 22.
4. Screw the sensor and detector plate into its operating position using screws from Step 1. Make sure the sampling tube connection is on the bottom and the ex­haust tube is on the top. See Fig. 22.
5. Connect the flexible tube on the sampling inlet to the sampling tube on the basepan.
6. For units with an economizer, the sampling tube is in­tegrated into the economizer housing but the connec­tion of the flexible tubing to the sampling tube is the same.
48TC
Return Air Sampling Tube
Fig. 20 -- Return Air Sampling Tube Location
C08129
C08127
Fig. 22 -- Return Air Sensor Operating Position
FIOP Smoke Detector Wiring and Response
All units: FIOP smoke detector is configured to automatically shut down all unit operations when smoke condition is detected. See Fig. 23, Smoke Detector Wiring.
Highlight A: JMP 3 is factory--cut, transferring unit control to smoke detector.
Highlight B: Smoke detector NC contact set will open on smoke alarm condition, de--energizing the ORN conductor.
17
B
D
C
F
E
48TC
Fig. 23 -- Typical Smoke Detector System Wiring
Highlight C: 24--v power signal via ORN lead is removed at Smoke Detector input on LCTB; all unit operations cease immediately.
PremierLink and RTU--MP Controls: Unit operating functions (fan, cooling and heating) are terminated as described above. In addition:
Highlight D: On smoke alarm condition, the smoke detector NO Alarm contact will close, supplying 24--v power to GRA conductor.
Highlight E: GRA lead at Smoke Alarm input on LCTB provides 24--v signal to FIOP DDC control.
Premier--Link: This signal is conveyed to PremierLink FIOP’s TB1 at terminal TB1--6 (BLU lead). This signal initiates the FSD sequence by the PremierLink control. FSD status is reported to connected CCN network.
RTU--MP: The 24--v signal is conveyed to RTU--MP’s J1--10 input terminal. This signal initiates the FSD sequence by the RTU--MP control. FSD status is reported to connected BAS network.
Using Remote Logic: Five conductors are provided for field use (see Highlight F) for additional annunciation functions.
Additional Application Data — Refer to Catalog No. HKRNKA--1XA for discussions on additional control features of these smoke detectors including multiple unit coordination. See Fig. 23.
A
C08246
Sensor and Controller Tests
Sensor Alarm Test
The sensor alarm test checks a sensor’s ability to signal an alarm state. This test requires that you use a field provided SD--MAG test magnet.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel and authority concern.
This test places the duct detector into the alarm state. Unless part of the test, disconnect all auxiliary equipment from the controller before performing the test. If the duct detector is connected to a fire alarm system, notify the proper authorities before performing the test.
Sensor Alarm Test Procedure
1. Hold the test magnet where indicated on the side of the sensor housing for seven seconds.
2. Verify that the sensor’s Alarm LED turns on.
3. Reset the sensor by holding the test magnet against the sensor housing for two seconds.
4. Verify that the sensor’s Alarm LED turns off.
Controller Alarm T
The controller alarm test checks the controller’s ability to initiate and indicate an alarm state.
est
18
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel and authority concern.
This test places the duct detector into the alarm state. Disconnect all auxiliary equipment from the controller before performing the test. If the duct detector is connected to a fire alarm system, notify the proper authorities before performing the test.
Controller Alarm Test Procedure
1. Press the controller’s test/reset switch for seven seconds.
2. Verify that the controller’s Alarm LED turns on.
3. Reset the sensor by pressing the test/reset switch for two seconds.
4. Verify that the controller’s Alarm LED turns off.
Dirty Controller T
The dirty controller test checks the controller’s ability to initiate a dirty sensor test and indicate its results.
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel and authority concern.
Pressing the controller’s test/reset switch for longer than seven seconds will put the duct detector into the alarm state and activate all automatic alarm responses.
Dirty Controller Test Procedure
1. Press the controller’s test/reset switch for two seconds.
2. Verify that the controller’s Trouble LED flashes.
Dirty Sensor T
The dirty sensor test provides an indication of the sensor’s ability to compensate for gradual environmental changes. A sensor that can no longer compensate for environmental changes is considered 100% dirty and requires cleaning or replacing. You must use a field provided SD--MAG test magnet to initiate a sensor dirty test. The sensor’s Dirty LED indicates the results of the dirty test as shown in Table 2.
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel and authority concern.
Holding the test magnet against the sensor housing for more than seven seconds will put the duct detector into the alarm state and activate all automatic alarm responses.
est
!
CAUTION
est
!
CAUTION
Tabl e 2 – D i rty LED Te s t
FLASHES DESCRIPTION
1 0---25% dirty. (Typical of a newly installed detector)
2 25---50% dirty
3 51---75% dirty
4 76---99% dirty
Dirty Sensor Test Procedure
1. Hold the test magnet where indicated on the side of the sensor housing for two seconds.
2. Verify that the sensor’s Dirty LED flashes.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel and authority concern.
Changing the dirty sensor test operation will put the detector into the alarm state and activate all automatic alarm responses. Before changing dirty sensor test operation, disconnect all auxiliary equipment from the controller and notify the proper authorities if connected to a fire alarm system.
Changing the Dirt Sensor Test
By default, sensor dirty test results are indicated by:
S The sensor’s Dirty LED flashing. S The controller’s Trouble LED flashing. S The controller’s supervision relay contacts toggle.
The operation of a sensor’s dirty test can be changed so that the controller’s supervision relay is not used to indicate test results. When two detectors are connected to a controller, sensor dirty test operation on both sensors must be configured to operate in the same manner.
To Configure the Dirty Sensor Test Operation
1. Hold the test magnet where indicated on the side of the sensor housing until the sensor’s Alarm LED turns on and its Dirty LED flashes twice (approximately 60 seconds).
2. Reset the sensor by removing the test magnet then holding it against the sensor housing again until the sensor’s Alarm LED turns off (approximately 2 seconds).
Remote Station T
The remote station alarm test checks a test/reset station’s ability to initiate and indicate an alarm state.
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel and authority concern.
This test places the duct detector into the alarm state. Unless part of the test, disconnect all auxiliary equipment from the controller before performing the test. If the duct detector is connected to a fire alarm system, notify the proper authorities before performing the test.
est
!
CAUTION
48TC
19
SD--TRK4 Remote Alarm Test Procedure
1. Turn the key switch to the RESET/TEST position for seven seconds.
2. Verify that the test/reset station’s Alarm LED turns on.
3. Reset the sensor by turning the key switch to the RESET/TEST position for two seconds.
4. Verify that the test/reset station’s Alarm LED turns off.
Remote Test/Reset Station Dirty Sensor T
est
The test/reset station dirty sensor test checks the test/reset station’s ability to initiate a sensor dirty test and indicate the results. It must be wired to the controller as shown in Fig. 24 and configured to operate the controller’s supervision relay. For more information, see “Changing sensor dirty test operation.”
48TC
12
1
TB3
1
2
Smoke Detector Controller
Auxiliary
equipment
+
Dirty Sensor Test Using an SD--TRK4
1. Turn the key switch to the RESET/TEST position for two seconds.
2. Verify that the test/reset station’s Trouble LED flashes.
Detector Cleaning
Cleaning the Smoke Detector
Clean the duct smoke sensor when the Dirty LED is flashing continuously or sooner if conditions warrant.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel and authority concern.
If the smoke detector is connected to a fire alarm system, first notify the proper authorities that the detector is undergoing maintenance then disable the relevant circuit to avoid generating a false alarm.
1. Disconnect power from the duct detector then remove the sensor’s cover. (See Fig. 25.)
3
S contacts [3]
Wire m
ust be
added by installer
upe
rv
ision relay
14
SD-TRK4
1
3
18 Vdc ( )
18 Vdc ( )
+
19
15
2
20
Trouble
5
P
ower
4
Alarm
1
Reset/Test
3
2
C08247
Fig. 24 -- Remote Test/Reset Station Connections
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel and authority concern.
If the test/reset station’s key switch is left in the RESET/TEST position for longer than seven seconds, the detector will automatically go into the alarm state and activate all automatic alarm responses.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel and authority concern.
Holding the test magnet to the target area for longer than seven seconds will put the detector into the alarm state and activate all automatic alarm responses.
Sampling
tube
Airow
HVAC duct
Sensor housing
Optic plate
Retainer clip
Optic housing
C07305
Fig. 25 -- Sensor Cleaning Diagram
2. Using a vacuum cleaner, clean compressed air, or a soft bristle brush, remove loose dirt and debris from inside the sensor housing and cover. Use isopropyl alcohol and a lint--free cloth to remove dirt and other contaminants from the gasket on the sensor’s cover.
3. Squeeze the retainer clips on both sides of the optic housing then lift the housing away from the printed circuit board.
4. Gently remove dirt and debris from around the optic plate and inside the optic housing.
5. Replace the optic housing and sensor cover.
6. Connect power to the duct detector then perform a sensor alarm test.
INDICAT ORS
Normal State
The smoke detector operates in the normal state in the absence of any trouble conditions and when its sensing chamber is free of smoke. In the normal state, the Power
20
LED on both the sensor and the controller are on and all other LEDs are off.
Alarm
State
The smoke detector enters the alarm state when the amount of smoke particulate in the sensor’s sensing chamber exceeds the alarm threshold value. (See Table 3.) Upon entering the alarm state:
S The sensor’s Alarm LED and the controller’s Alarm LED
turn on.
S The contacts on the controller’s two auxiliary relays
switch positions.
S The contacts on the controller’s alarm initiation relay
close.
S The controller’s remote alarm LED output is activated
(turned on).
S The controller’s high impedance multiple fan shutdown
control line is pulled to ground Trouble state.
The SuperDuct duct smoke detector enters the trouble state under the following conditions:
S A sensor’s cover is removed and 20 minutes pass before
it is properly secured.
S A sensor’s environmental compensation limit is reached
(100% dirty).
S A wiring fault between a sensor and the controller is
detected.
An internal sensor fault is detected upon entering the trouble state:
S The contacts on the controller’s supervisory relay switch
positions. (See Fig. 26.)
S If a sensor trouble, the sensor’s Trouble LED the
controller’s Trouble LED turn on.
S If 100% dirty, the sensor’s Dirty LED turns on and the
controller’s Trouble LED flashes continuously.
S If a wiring fault between a sensor and the controller, the
controller’s Trouble LED turns on but not the sensor’s.
Tro uble
Alarm
Power
Test/reset switch
NOTE: All troubles are latched by the duct smoke detector. The trouble condition must be cleared and then the duct smoke detector must be reset in order to restore it to the normal state.
Resetting Alarm and Tr ouble Condition T
rips:
Manual reset is required to restore smoke detector systems to Normal operation. For installations using two sensors, the duct smoke detector does not differentiate which sensor signals an alarm or trouble condition. Check each sensor for Alarm or Trouble status (indicated by LED). Clear the condition that has generated the trip at this sensor. Then reset the sensor by pressing and holding the reset button (on the side) for 2 seconds. Verify that the sensor’s Alarm and Trouble LEDs are now off. At the controller, clear its Alarm or Trouble state by pressing and holding the manual reset button (on the front cover) for 2 seconds. Verify that the controller’s Alarm and Trouble LEDs are now off. Replace all panels.
Troubleshooting
Controller’s Trouble LED is On
1. Check the Trouble LED on each sensor connected to the controller. If a sensor’s Trouble LED is on, de­termine the cause and make the necessary repairs.
2. Check the wiring between the sensor and the control­ler. If wiring is loose or missing, repair or replace as required.
Controller’s Trouble LED is
1. One or both of the sensors is 100% dirty.
2. Determine which Dirty LED is flashing then clean that sensor assembly as described in the detector cleaning section.
Sensor’s Trouble LED is
1. Check the sensor’s Dirty LED. If it is flashing, the sensor is dirty and must be cleaned.
2. Check the sensor’s cover. If it is loose or missing, se­cure the cover to the sensor housing.
3. Replace sensor assembly.
Sensor’s Power LED is
1. Check the controller’s Power LED. If it is off, de­termine why the controller does not have power and make the necessary repairs.
2. Check the wiring between the sensor and the control­ler. If wiring is loose or missing, repair or replace as required.
Flashing
On
Off
48TC
C07298
Fig. 26 -- Controller Assembly
Table 3 – Detector Indicators
CONTROL OR INDICATOR DESCRIPTION
Magnetic test/reset switch
Alarm LED Indicates the sensor is in the alarm state.
Troubl e LED Indicates the sensor is in the trouble state.
Dirty LED
Power LED Indicates the sensor is energized.
Resets the sensor when it is in the alarm or trouble state. Activates or tests the sensor when it is in the normal state.
Indicates the amount of environmental compensation used by the sensor (flashing continuously = 100%)
21
Controller’s Power LED is Off
1. Make sure the circuit supplying power to the control­ler is operational. If not, make sure JP2 and JP3 are set correctly on the controller before applying power.
2. Verify that power is applied to the controller’s supply input terminals. If power is not present, replace or re­pair wiring as required.
Remote Test/Reset Station’s Trouble LED Does flash When Performing a Dirty Test, But the Contr ler’s Trouble LED
Does
1. Verify that the remote test/station is wired as shown in Fig. 24. Repair or replace loose or missing wiring.
2. Configure the sensor dirty test to activate the control­ler’s supervision relay. See “Changing sensor dirty test operation.”
Sensor’s Trouble LED is On, But the Controller’ Tr ouble LED is
48TC
OFF
Remove JP1 on the controller.
Not
s
ol-
The standard supply fan motor is equipped with internal overcurrent and overtemperature protection. Protection devices reset automatically.
The High Static option supply fan motor is equipped with a pilot--circuit Thermix combination overtemperature/ overcurrent protection device. This device resets automatically. Do not bypass this switch to correct trouble. Determine the cause and correct it.
Condenser Fan Motor Pr
otection
The condenser fan motor is internally protected against overtemperature.
Relief Device
A soft solder joint at the suction service access port provides pressure relief under abnormal temperature and pressure conditions (i.e., fire in building). Protect this joint during brazing operations near this joint.
Control Circuit, 24--V
PROTECTIVE DEVICES
Compressor Protection
Overcurrent
The compressor has internal linebreak motor protection.
Overtemperatur
The compressor has an internal protector to protect it against excessively high discharge gas temperatures.
High Pressure
The system is provided with a high pressure switch mounted on the discharge line. The switch is stem--mounted and brazed into the discharge tube. Trip setting is 630 psig +/-- 10 psig (4344 +/-- 69 kPa) when hot. Reset is automatic at 505 psig (3482 kPa).
Low Pressure
The system is protected against a loss of charge and low evaporator coil loading condition by a low pressure switch located on the suction line near the compressor. The switch is stem--mounted. Trip setting is 54 psig +/-- 5 psig (372 +/-- 34 kPa). Reset is automatic at 117 +/-- 5 psig (807 +/-- 34 kPa).
Evaporator Freeze Pr
e
Switch
Switch
otection
The control circuit is protected against overcurrent conditions by a circuit breaker mounted on control transformer TRAN. Reset is manual.
GAS HEATING SYSTEM
General
The heat exchanger system consists of a gas valve feeding multiple inshot burners off a manifold. The burners fire into matching primary tubes. The primary tubes discharge into combustion plenum where gas flow converges into secondary tubes. The secondary tubes exit into the induced draft fan wheel inlet. The induced fan wheel discharges into a flue passage and flue gases exit out a flue hood on the side of the unit. The induced draft fan motor includes a Hall Effect sensor circuit that confirms adequate wheel speed via the Integrated Gas Control (IGC) board. Safety switches include a Rollout Switch (at the top of the burner compartment) and a limit switch (mounted through the fan deck, over the tubes). (See Fig. 27 and Fig. 28.)
INDUCED­DRAFT MOTOR MOUNTING PLATE
ROLLOUT SWITCH
The system is protected against evaporator coil frosting and low temperature conditions by a temperature switch mounted on the evaporator coil hairpin. Trip setting is 30_F+/--5_F(--1_C+/--3_C). Reset is automatic at 45_F (7_C).
Supply (Indoor) Fan Motor Pr
otection
Disconnect and lockout power when servicing fan motor.
22
BURNER SECTION
INDUCED­DRAFT MOTOR
MANIFOLD PRESSURE TAP
Fig. 27 -- Burner Section Details
FLUE EXHAUST
VESTIBULE PLATE
BLOWER HOUSING
GAS VALV E
C06152
Limit Switch and Shield
C08284
Fig. 28 -- Limit Switch Location
Fuel Types and Pressures
Natural Gas — The 48TC unit is factory--equipped for use with Natural Gas fuel at elevation under 2000 ft (610 m). See section Orifice Replacement for information in modifying this unit for installation at elevations above 2000 ft (610 m).
Gas line pressure entering the unit’s main gas valve must be within specified ranges. Adjust unit gas regulator valve as required or consult local gas utility.
Table 4 – Natural Gas Supply Line Pressure Ranges
UNIT MODEL UNIT SIZE MIN MAX
48TC All
4.0 in. wg (996 Pa)
13.0 in. wg (3240 Pa)
Table 6 – Liquid Propane Supply Line Pressure Ranges
UNIT MODEL UNIT SIZE MIN MAX
48TCD,E,F 48TCS,R,T
48TCL,M,N All NA NA
All
11.0 in. wg (2740 Pa)
13.0 in. wg (3240 Pa)
Manifold pressure for LP fuel use must be adjusted to specified range. Follow instructions in the accessory kit to make initial readjustment.
Table 7 – Liquid Propane Manifold Pressure Ranges
UNIT MODEL UNIT SIZE HIGH FIRE LOW FIRE
48TCD,S 48TCE,R
48TCF,T
48TCL,
48TCM,
48TCN
NA: Not Available { 3 Phase models only
All
All NA NA
10.0 in. wg (2490 Pa)
5.0 in. wg
(1245 Pa){
Supply Pressure Switch — The LP conversion kit includes a supply low pressure switch. The switch contacts (from terminal C to terminal NO) will open the gas valve power whenever the supply line pressure drops below the setpoint. See Fig. 29 and Fig. 30. If the low pressure remains open for 15 minutes during a call for heat, the IGC circuit will initiate a Ignition Fault (5 flashes) lockout. Reset of the low pressure switch is automatic on rise in supply line pressure. Reset of the IGC requires a recycle of unit power after the low pressure switch has closed.
48TC
Manifold pressure is factory--adjusted for NG fuel use. Adjust as required to obtain best flame characteristic.
Table 5 – Natural Gas Manifold Pressure Ranges
UNIT
MODEL
48TCD,S 48TCE,R
48TCF,T
48TCL
48TCM
48TCN
NA: Not Available { 3 Phase models only
UNIT SIZE
All
All
HIGH
FIRE
3.5 in. wg (872 Pa)
3.5 in. wg (872 Pa)
LOW FIRE
1.7 in. wg (423 Pa){
NA
RANGE
2.0---5.0 in. wg (Hi) (498---1245 Pa)
2.0---5.0 in. wg (Hi) (498---1245 Pa)
Liquid Propane — Accessory packages are available for field--installation that will convert the 48TC unit (except low NO
model) to operate with Liquid Propane (LP)
x
fuels. These kits include new orifice spuds, new springs for gas valves and a supply line low pressure switch. See section on Orifice Replacement for details on orifice size selections.
Low NO
models include specially--sized orifices and use
x
of different flue flow limits and tube baffles. Because of these extra features, conversion of these models to LP is not recommended.
Fuel line pressure entering unit gas valve must remain within specified range.
C08238
Fig. 29 -- LP Low Pressure Switch (Installed)
C
PNK
LP LPS
GRA
NO
BRN
MGV
C
C08285
IGC
BRN
J2-11
IGC
J2-12
TSTAT
W2
Fig. 30 -- LP Supply Line Low Pressure Switch Wiring
23
This switch also prevents operation when the propane tank level is low which can result in gas with a high concentration of impurities, additives, and residues that have settled to the bottom of the tank. Operation under these conditions can cause harm to the heat exchanger system. Contact your fuel supplier if this condition is suspected.
Flue Gas Passageways
To inspect the flue collector box and upper areas of the heat exchanger:
1. Remove the combustion blower wheel and motor as­sembly according to directions in Combustion--Air Blower section. See Fig. 31.
2. Remove the flue cover to inspect the heat exchanger.
3. Clean all surfaces as required using a wire brush.
Combustion--Air Blower
48TC
Clean periodically to assure proper airflow and heating efficiency. Inspect blower wheel every fall and periodically during heating season. For the first heating
season, inspect blower wheel bi--monthly to determine proper cleaning frequency.
To access burner section, slide the sliding burner partition out of the unit.
To inspect blower wheel, shine a flashlight into draft hood opening. If cleaning is required, remove motor and wheel as follows:
1. Slide burner access panel out.
2. Remove the 7 screws that attach induced--draft motor housing to vestibule plate. (See Fig. 31.)
3. The blower wheel can be cleaned at this point. If ad­ditional cleaning is required, continue with Steps 4 and 5.
4. To remove blower from the motor shaft, remove 2 setscrews.
5. To remove motor, remove the 4 screws that hold the motor to mounting plate. Remove the motor cooling fan by removing one setscrew. Then remove nuts that hold motor to mounting plate.
6. To reinstall, reverse the procedure outlined above.
Support Insulation Assembly
Wind Cap Assembly (shown inverted, as shipped)
Regulator
Bae Assembly (Low NOx only)
Retainer
Regulator Gasket
Seal Strips, Sponge Rubber
Inducer Fan-Motor Assembly
Heater Tube Assembly
Flue Bae (Low NOx only)
Burner Assembly
C08227
Fig. 31 -- Heat Exchanger Assembly
24
Burners and Igniters
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
When working on gas train, do not hit or plug orifice spuds.
Main Burners
To access burners, remove burner access panel and slide out burner partition. At the beginning of each heating season, inspect for deterioration or blockage due to corrosion or other causes. Observe the main burner flames and adjust, if necessary.
Orifice projection — Refer to Fig. 32 for maximum projection dimension for orifice face to manifold tube.
Orifice
1.00-in (25.4 mm)
8. Slide the burner tray out of the unit (Fig. 33).
9. To reinstall, reverse the procedure outlined above.
Cleaning and Adjustment
1. Remove burner rack from unit as described in Re­moval and Replacement of Gas Train section, above.
2. Inspect burners; if dirty, remove burners from rack. (Mark each burner to identify its position before re­moving from the rack.)
3. Use a soft brush to clean burners and cross--over port as required.
4. Adjust spark gap. (See Fig. 35 and Fig. 36.)
5. If factory orifice has been removed, check that each orifice is tight at its threads into the manifold pipe and that orifice projection does not exceed maximum valve. See Fig. 32
6. Reinstall burners on rack in the same locations as factory--installed. (The outside crossover flame re­gions of the outermost burners are pinched off to pre­vent excessive gas flow from the side of the burner assembly. If the pinched crossovers are installed between two burners, the flame will not ignite prop­erly.)
RACEWAY
INTEGRATED GAS UNIT CONTROLLER (IGC)
48TC
Manifold Pipe
Fig. 32 -- Orifice Projection
Removal and Replacement of Gas Train
See Fig. 27, Fig. 31 and Fig. 33.
1. Shut off manual gas valve.
2. Shut off power to unit.
3. Slide out burner partition.
4. Disconnect gas piping at unit gas valve.
5. Remove wires connected to gas valve. Mark each wire.
Fig. 33 -- Burner Tray Details
6. Remove igniter wires and sensor wires at the Integ­rated Gas Unit Controller (IGC). (See Fig. 34.)
7. Remove the 2 screws that attach the burner rack to the vestibule plate (Fig. 31).
C08211
C06153
HOLE IN END PANEL (HIDDEN)
C08454
Fig. 34 -- Unit Control Box/IGC Location
7. Reinstall burner rack as described in Removal and Replacement of Gas Train section, above.
Gas Valve — All three--phase models (except Low NO are equipped with 2--stage gas valves. Single--phase models and all Low NO
models are equipped with
x
single--stage gas valves. See Fig. 37 for locations of adjustment screws and features on the gas valves.
To adjust gas valve pressure settings:
IMPORTANT: Leak check all gas connections including the main service connection, gas valve, gas spuds, and manifold pipe plug. All leaks must be repaired before firing unit.
Check Unit Operation and Make Necessary Adjust­ments
NOTE: Gas supply pressure at gas valve inlet must be
within specified ranges for fuel type and unit size. See Table 4 and Table 5.
)
x
25
1. Remove manifold pressure tap plug from manifold and connect pressure gauge or manometer. (See Fig.
33.)
2. Turn on electrical supply.
3. Turn on unit main gas valve.
4. Set room thermostat to call for heat. If unit has two-­stage gas valve, verify high--stage heat operation be­fore attempting to adjust manifold pressure.
5. When main burners ignite, check all fittings, mani­fold, and orifices for leaks.
6. Adjust high--stage pressure to specified setting by turning the plastic adjustment screw clockwise to in­crease pressure, counter--clockwise to decrease pres­sure.
7. For Two--Stage Gas Valves set room thermostat to call for low--stage heat. Adjust low--stage pressure to
48TC
specified setting.
8. Replace regulator cover screw(s) when finished.
9. With burner access panel removed, observe unit heat­ing operation in both high stage and low stage opera­tion if so equipped. Observe burner flames to see if they are blue in appearance, and that the flames are approximately the same for each burner.
10. Turn off unit, remove pressure manometer and re­place the 1/8 in. pipe fitting on the gas manifold. (See Fig. 32.)
Switch
Limit
Remove blower access panel. Limit switch is located on the fan deck. See Fig. 28.
Burner Ignition
Unit is equipped with a direct spark ignition 100% lockout system. Integrated Gas Unit Controller (IGC) is located in the control box. See Fig. 34. The IGC contains a self--diagnostic LED (light--emitting diode). A single LED (see Fig. 38) on the IGC provides a visual display of operational or sequential problems when the power supply is uninterrupted. When a break in power occurs, the IGC will be reset (resulting in a loss of fault history) and the indoor (evaporator) fan ON/OFF times will be reset. The LED error code can be observed through the viewport. During servicing refer to the label on the control box cover or Table 8 for an explanation of LED error code descriptions.
If lockout occurs, unit may be reset by interrupting power supply to unit for at least 5 seconds.
72,000 BTUH INPUT AND 60,000 BTUH INPUT
LOW HEAT
MEDIUM AND HIGH HEAT
115,000 BTUH INPUT, 150,000 BTUH INPUT, 90,000BTUH INPUT AND 120,000 BTUH INPUT
Fig. 35 -- Spark Adjustment (04--07)
C06154
26
125,000/90,000 BTUH INPUT
180,000/120,000 BTUH INPUT
240,000/180,000 BTUH INPUT 250,000/200,000 BTUH INPUT
Fig. 36 -- Spark Adjustment (08--12)
48TC
C08447
Table 8 – LED Error Code Description*
LED INDICATION
ON Normal Operation
OFF Hardware Failure
1Flash{ Evaporator Fan On/Off Delay Modified
2Flashes Limit Switch Fault
3Flashes Flame Sense Fault
4Flashes 4 Consecutive Limit Switch Faults
5Flashes Ignition Lockout Fault
6Flashes Induced ---Draft Motor Fault
7Flashes Rollout Switch Fault
8Flashes Internal Control Fault
9Flashes Software Lockout
LEGEND LED --- L i g ht E m i t t i n g Diode
* A 3---second pause exists between LED error code flashes. If.
more than one error code exists, all applicable codes will be displayed in numerical sequence.
{ Indicates a code that is not an error. The unit will continue to
operate when this code is d isplayed.
ERROR CODE DESCRIPTION
IMPORTANT: Refer to Troubleshooting Table 13 and Table 14 for additional information.
Orifice Replacement
This unit uses orifice type LH32RFnnn (where nnn indicates orifice reference size). When replacing unit orifices, order the necessary parts via Carrier RCD. See Table 10 for available orifice sizes. See Table 11 and Table 12 for orifice sizes for Natural Gas and LP fuel usage at various elevations above sea level.
Check that each replacement orifice is tight at its threads into the manifold pipe and that orifice projection does not exceed maximum value. See Fig. 32.
27
48TC
Single Stage
Red LED-Status
2 Stage
C08210
Fig. 37 -- Gas Valves
Fig. 38 -- Integrated Gas Control (IGC) Board
28
C08452
Table 9 – IGC Connections
TERMINAL LABEL POINT DESCRIPTION SENSOR LOCATION TYPE OF I/O
INPUTS
RT, C Input power from TRAN 1 control box 24 VAC
SS Speed sensor gas section analog input J1, 1-3
FS, T1 Flame sensor gas section switch input
W Heat stage 1 LCTB 24 VAC J2, 2
RS Rollout switch gas section switch input J2, 5-6
LS Limit switch fan section switch input J2, 7-8
CS Centrifugal switch (not used) switch input J2, 9-10
OUTPUTS
L1, CM Induced draft combustion motor gas section line VAC
IFO Indoor fan control box relay J2, 1
GV Gas valve (heat stage 1) gas section relay J2, 11-12
Table 10 – Orifice Sizes
ORIFICE
DRILL SIZE
#30 LH32RF129 0.1285
1/8 LH32RF125 0.1250 #31 LH32RF120 0.1200 #32 LH32RF116 0.1160 #33 LH32RF113 0.1130 #34 LH32RF111 0.1110 #35 LH32RF110 0.1100 #36 LH32RF105 0.1065 #37 LH32RF104 0.1040 #38 LH32RF102 0.1015 #39 LH32RF103 0.0995 #40 LH32RF098 0.0980 #41 LH32RF096 0.0960 #42 LH32RF094 0.0935 #43 LH32RF089 0.0890 #44 LH32RF086 0.0860 #45 LH32RF082 0.0820 #46 LH32RF080 0.0810 #47 LH32RF079 0.0785 #48 LH32RF076 0.0760 #49 LH32RF073 0.0730 #50 LH32RF070 0.0700 #51 LH32RF067 0.0670 #52 LH32RF065 0.0635 #53 LH32RF060 0.0595 #54 LH32RF055 0.0550 #55 LH32RF052 0.0520 #56 LH32RF047 0.0465 #57 LH32RF043 0.0430 #58 LH32RF042 0.0420
CARRIER
PART NUMBER
CONNECTION
PIN NUMBER
48TC
DRILL
DIA. (in.)
29
Table 11 – Altitude Compensation* (A04--A07)
72,000 BTUH
ELEVATION
ft (m)
Orifice Size
0 --- 2000 (610) 33
2000 (610) 35
3000 (914) 35 4000 (1219) 36 5000 (1524) 36 6000 (1829) 37 7000 (2134) 38 8000 (2438) 39
Nominal
NG
Orifice Size
1
1
1
1
1
2
2
2
9000 (2743) †40 53
10000 (3048) †41 54 11000 (3353) †42 54 12000 (3658) †43 54 13000 (3962) †43 55
48TC
14000 (4267) 44
2
Table 11 (cont.) -- Altitude Compensation* (A08--A12)
125,000
ELEVATION
ft (m)
0 --- 2000 (610) 31
2000 (610) 32
3000 (914) 32 4000 (1219) 33 5000 (1524) 33 6000 (1829) 34 7000 (2134) 35 8000 (2438) 36 9000 (2743) 37
10000 (3048) 38 11000 (3353) 39 12000 (3658) †41 53 13000 (3962) †42 54 14000 (4267) †43 54
LEGEND NG = Natural Gas LP = Liquid Propane * As the height above sea level increases, there is less oxygen
per cubic ft. of air. Therefore, heat input rate should be reduced at higher altitudes.
{ Not included in kit. May be purchased separately through
dealer.
BTUH Nominal
NG Orifice
Size
1
1
1
1
1
1
1
1
2
2
2
LP Orifice
LP
NG
Orifice Size
4
51 51 52 52 52 52 53 53
4
4
4
4
4
4
4
4
4
4
4
4
33 35 35 36 36 37 38 39 †40 53 †41 53 †42 53 †43 54 †43 54
†56 44
NG Orifice
Size
3
49
3
50
3
50
3
50
4
51
4
51
4
51
4
52
4
52
4
52
4
53
4
4
4
115,000 BTUH
Nominal
LP
Orifice Size
1
1
1
1
1
2
2
2
2
50 51 51 51 51 52 52 52
55
250,000
BTUH Nominal
LP Orifice
Size
Size
†30 46 †30 47
1
31
1
31
1
31
1
31
1
32
1
33
1
34
1
35
1
36
2
37
2
38 †40 53
1 = CRLPELEV001A00 2 = CRLPELEV002A00 3 = CRLPELEV003A00 4 = CRLPELEV004A00
47 48 48 48 49 49 50 50 51 51 52
150,000 BTUH
Nominal
NG
Orifice Size
3
4
4
4
4
4
4
4
4
4
4
4
4
4
†30 46 †30 47
1
31
1
31
1
31
1
31
1
32
1
33
1
34
1
35
1
36
2
37
2
38 †40 53
LP
Orifice Size
3
3
3
47
3
48
3
48
3
48
3
49
3
49
3
50
3
50
4
51
4
51
4
52
4
180,000, 224,000
BTUH Nominal
NG Orifice
Size
3
3
3
3
3
3
3
3
3
3
4
4
4
4
1
31
1
32
1
32
1
33
1
33
1
34
1
35
1
36
2
37
2
38
2
39 †41 53 †42 53 †43 54
LP Orifice
Size
3
48
3
49
3
49
3
49
3
50
3
50
3
50
4
51
4
51
4
52
4
52
4
4
4
30
Table 12 – Altitude Compensation* (A04--A06) -- Low NOxUnits
ELEVATION
ft (m)
NG Orifice Size LP Orifice Size NG Orifice Size LP Orifice Size
0 --- 2000 (610) 38
2000 (610) 39
60,000, 90,000 BTUH Nominal
2
2
3000 (914) †40 54 4000 (1219) †41 54 5000 (1524) †41 54 6000 (1829) †42 54 7000 (2134) †42 54 8000 (2438) †43 55 9000 (2743) †43 55
10000 (3048) 44 11000 (3353) 44 12000 (3658) 45 13000 (3962) 47 14000 (4267) 48
LEGEND NG = Natural Gas LP = Liquid Propane * As the height above sea level increases, there is less oxygen
per cubic ft. of air. Therefore, heat input rate should be reduced at higher altitudes.
{ Not included in kit. May be purchased separately through
dealer.
2
2
2
3
3
Minimum heating entering air temperature
When operating on first stage heating, the minimum temperature of air entering the dimpled heat exchanger is 50_F continuous and 45_F intermittent for standard heat exchangers and 40_F continuous and 35_ F intermittent for stainless steel heat exchangers. To operate at lower mixed--air temperatures, a field--supplied outdoor--air thermostat must be used to initiate both stages of heat when the temperature is below the minimum required temperature to ensure full fire operation. Wire the outdoor--air thermostat OALT (part no. HH22AG106) in series with the second stage gas valve. See Fig. 39. Set the outdoor--air thermostat at 35_F for stainless steel heat exchangers or 45_F for standard heat exchangers. This temperature setting will bring on the second stage of heat whenever the ambient temperature is below the thermostat setpoint. Indoor comfort may be compromised when
120,000
BTUH Nominal
4
53
4
54
4
4
4
4
4
4
4
4
55
4
55 †56 †42 54 †56 †43 54 †56 †43 55
1 = CRLPELEV001A00 2 = CRLPELEV002A00 3 = CRLPELEV003A00 4 = CRLPELEV004A00
1
32 33 34 35 35 36 36 37 38
1
1
1
1
1
1
2
2
50 51 51 51 51 52 52 52
53 †40 53 †41 53
3
4
4
4
4
4
4
4
4
4
4
4
4
4
heating is initiated using low entering air temperatures with insufficient heating temperature rise.
Thermostat
TH1
TH2
W1
OALT
W2
Fig. 39 -- OATL Connections
Troubleshooting Heating System
Refer to Table 13 and Table 14 for additional troubleshooting topics.
48TC
LCTB
W1
W2
C08442
31
Table 13 – Heating Service Analysis
PROBLEM CAUSE REMEDY
Misaligned spark electrodes.
No gas at main burners.
Burners Will Not Ignite.
48TC
Inadequate Heating.
Poor Flame Characteristics.
Burners Will Not Turn Off.
Water in gas line. Drain water and install drip leg to trap water. No power to furnace. Check power supply, fuses, wiring, and circuit breaker. No 24 v power supply to control
circuit. Miswired or loose connections. Check all wiring and wire nut connections. Burned ---out heat anticipator in
thermostat. Broken thermostat wires. Run continuity check. Replace wires, if necessary. Dirty air filter. Clean or replace filter as necessary.
Gas input to unit too low.
Unit undersized for application. Replace with proper unit or add additional unit. Restricted airflow. Clean filter, replace filter, or remove any restrictions.
Blower speed too low.
Limitswitchcyclesmainburners.
Too much outdoor air.
Incomplete combustion (lack of combustion air) results in: Aldehyde odors, CO, sooting flame, or floating flame.
Unit is locked into Heating mode for a one minute minimum.
Check flame ignition and sensor electrode positioning. Adjust as needed.
Check gas line for air, purge as necessary. After purging gas line of air, allow gas to dissipate for at least 5 minutes before attempting to relight unit.
Check gas valve.
Check transformer. Transformers with internal overcurrent protection require a cool down period before resetting.
Replace thermostat.
Check gas pressure at manifold. Clock gas meter for input. If too low, increase manifold pressure, or replace with correct orifices.
Use high speed tap, increase fan speed, or install optional blower, as suitable for individual units.
Check rotation of blower, thermostat heat anticipator settings, and temperature rise of unit. Adjust as needed.
Adjust minimum position. Check economizer operation. Check all screws around flue outlets and burner
compartment. Tighten as necessary. Cracked heat exchanger. Overfired unit — reduce input, change orifices, or adjust
gas line or manifold pressure. Check vent for restriction. Clean as necessary. Check orifice to burner alignment. Wait until mandator y one --- minute time period has elapsed
or reset power to unit.
32
Table 14 – IGC Board LED Alarm Codes
LED
FLASH
CODE
DESCRIPTION
ACTION TAKEN BY
CONTROL
RESET METHOD PROBABLE CAUSE
On Normal Operation
Loss of power to the IGC. Check 5 amp
Off Hardware Failure No gas heating.
fuse on IGC, power to unit, 24V circuit break er, tra nsf or mer, a nd wir ing t o t he IGC.
High temperature limit switch is open. Check the operation of the indoor (evapo­rator) fan motor. Ensure that the supply-air temperature rise is within the range on the unit name­plate. Check wiring and limit switch opera-
2
Flashes
Limit Switch Fault
Gas valve and igniter Off. Indoor fan and inducer On.
Limit switch closed, or heat call (W) Off.
tion.
3
Flashes
4
Flashes
Flame Sense Fault
Four Consecutive Limit Switch Fault
Indoor fan and inducer On.
No gas heating.
Flame sense normal. Power reset for LED reset.
Heat call (W) Off. Power reset for LED reset.
The IGC sensed a flame when the gas valve should be closed. Check wiring, flame sensor, and gas valve operation.
4 consecutive limit switch faults within a single call for heat. See Limit Switch Fault.
Unit unsuccessfully attempted ignitio n for 15 minutes. Check igniter and flame sen-
5
Flashes
Ignition Fault No gas heating.
Heat call (W) Off. Power reset for LED reset.
sor electrode spacing, gaps, etc. Check flame sense and igniter wiring. Check gas valve operation and gas supply. Check gas valve connections to IGC terminals. BRN lead must be on Pin 11.
Inducer sense On when heat call Off, or inducer sense Off when heat call On. Check wiring, voltage, and operation of IGC motor. Check speed sensor wiring to IGC.
Rollout switch has opened. Check gas valve operation. Check induced-draft blower wheel is properly secured to motor shaft.
IGC has sensed internal hardware or soft­ware error. If fault is not cleared by reset­ting 24 v power, replace the IGC.
Electrical interference is disrupting the IGC software.
6
Flashes
Induced Draft Motor Fault
If heat off: no gas heating. If heat on: gas valve Off and inducer On.
Inducer sense nor­mal, or heat call (W) Off.
Gas valve and igniter
7
Flashes
Rollout Switch Lockout
Off. Indoor fan and inducer
Power reset.
On.
8
Flashes
Flashes
LEGEND IGC --- Integrated Gas Unit Control LED --- L i g ht --- E m i t t i n g D i o d e NOTES:
Internal Control Lockout No gas heating. Power reset.
9
Temporary Software Lockout
1. There is a 3 --- second pause between alarm code displays.
2. If more than one alarm code exists, all applicable alarm codes will be displayed in numerical sequence.
3. Alarm codes on the IGC will be lost if power to the unit is interrupted.
No gas heating.
1 hour auto reset, or power reset.
48TC
33
48TC
C08199
Fig. 40 -- PremierLink Controller
PREMIERLINKT CONTROL
The PremierLink controller (see Fig. 40) is compatible with Carrier Comfort Networkr (CCN) devices. This control is designed to allow users the access and ability to change factory--defined settings, thus expanding the function of the standard unit control board. CCN service access tools include System Pilot (TM), Touch Pilot (TM) and Service Tool. (Standard tier display tools Navigatort and Scrolling Marquee are not suitable for use with latest PremierLink controller (Version 2.x).)
The PremierLink control is factory--mounted in the 48TC unit’s main control box to the left of the LCTB. Factory wiring is completed through harnesses connected to the LCTB thermostat. Field connections are made at a 16--pole terminal block (TB1) located on the bottom shelf of the unit control box in front of the PremierLink controller The factory--installed PremierLink control includes the supply--air temperature (SAT) sensor. The outdoor air temperature (OAT) sensor is included in the FIOP/accessory EconoMi$er 2 package.
Refer to Fig. 40 for PremierLink connection locations.
NOTE: Refer to Form 33CS--58SI for complete PremierLink configuration, operating sequences and troubleshooting information. Have a copy of this manual available at unit start--up.
The PremierLink controller requires the use of a Carrier electronic thermostat or a CCN connection for time broadcast to initiate its internal timeclock. This is necessary for broadcast of time of day functions (occupied/unoccupied).
NOTE: PremierLink controller is shipped in Sensor mode. To be used with a thermostat, the PremierLink controller must be configured to Thermostat mode. Refer to PremierLink Configuration instructions for Operating Mode.
Supply Air Temperature (SAT) Sensor On FIOP--equipped 48TC unit, the unit is supplied with a supply--air temperature (SAT) sensor (33ZCSENSAT). This sensor is a tubular probe type, approx 6--inches (12.7 mm) in length. It is a nominal 10--k ohm thermistor. See Table 15 for temperature--resistance characteristic.
The SAT is factory--wired. The SAT probe is wire--tied to the supply--air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re--position the sensor in the flange of the supply--air opening or in the supply air duct (as required by local codes). Drill or punch a 1/2--in. hole in the flange or duct. Use two field--supplied, self--drilling screws to secure the sensor probe in a horizontal orientation. See Fig. 41.
SUPPLY AIR TEMPERATURE SENSOR
SUPPLY AIR
RETURN AIR
ROOF CURB
C08200
Fig. 41 -- Typical Mounting Location for Supply Air
Temperature (SAT) Sensor on Small Rooftop Units
34
C08248
48TC
Fig. 42 -- PremierLink Wiring Schematic
35
Table 15 – Thermistor Resistance vs Temperature Values for Space Temperature Sensor, Supply Air
Temperature Sensor, and Outdoor Air Temperature
Sensor
48TC
TEMP
(C)
--- 40 --- 40 335,651
--- 35 --- 31 242,195
--- 30 --- 22 176,683
--- 25 --- 13 130,243
--- 20 --- 4 96,974
--- 15 5 72,895
--- 10 14 55,298
--- 5 23 42,315 0 32 32,651 5 41 25,395
10 50 19,903 15 59 15,714 20 68 12,494 25 77 10,000 30 86 8,056 35 95 6,530 40 104 5,325 45 113 4,367 50 122 3,601 55 131 2,985 60 140 2,487 65 149 2,082 70 158 1,752
TEMP
(F)
RESISTANCE
(Ohms)
NOTE: The sensor must be mounted in the discharge airstream downstream of the cooling coil and any heating devices. Be sure the probe tip does not come in contact with any of the unit’s heater surfaces.
Outdoor Air Temperature (OAT) Sensor — The OAT is factory--mounted in the EconoMi$er 2 (FIOP or accessory). It is a nominal 10k ohm thermistor attached to an eyelet mounting ring. See Table 15 for temperature--resistance characteristic.
Field connections — Field connections for accessory sensor and input devices are made at the 16--pole terminal block (TB1) located on the control box bottom shelf in front of the PremierLink control. Some input devices also require a 24--vac signal source; connect at LCTB terminal R at “THERMOSTAT” connection strip for this signal source. See connections figures on following pages for field connection locations (and for continued connections at the PremierLink board inputs).
Table 17 provides a summary of field connections for units equipped with Space Sensor. Table 18 provides a summary of field connections for units equipped with Space Thermostat.
Space Sensors -- The PremierLink controller is factory--shipped configured for Space Sensor Mode. A Carrier T--55 or T--56 space sensor must be used. T--55 space temperature sensor provides a signal of space temperature to the PremierLink control T--56 provides same space temperature signal plus it allows for adjustment of space temperature setpoints from the face of the sensor by the occupants. See Table 15 for temperature versus resistance characteristic on the space sensors.
Connect T--55 -- See Fig. 43 for typical T--55 internal connections. Connect the T--55 SEN terminals to TB1 terminals 1 and 3 (see Fig. 44).
2
SW1
3
45
SEN
61
RED(+)
WHT(GND)
BLK(-)
BRN (GND) BLU (SPT)
CCN COM
SENSOR WIRING
EconoMi$er 2 — The PremierLink control is used with EconoMi$er 2 (option or accessory) for outdoor air management. The damper position is controlled directly by the PremierLink control; EconoMi$er 2 has no internal logic device.
Outdoor air management functions can be enhanced with field--installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors) Space CO Outdoor air CO
sensor
2
sensor
2
Refer to Table 16 for accessory part numbers.
Fig. 43 -- T--55 Space Temperature Sensor Wiring
TB1 PL
SEN J6-7
SEN
1
3
Fig. 44 -- PremierLink T--55 Sensor
36
C08201
J6-6
C08212
Table 16 – PremierLink Sensor Usage
APPLICATION
OUTDOOR AIR
TEMPERATURE
SENSOR
RETURN AIR
TEMPERATURE
SENSOR
OUTDOOR AIR
ENTHALPY SENSOR
Differential Dry Bulb
Tempe r atu r e w ith
PremierLink
(PremierLink requires
I n c l u d e d ---
CRTEMPSN001A00
R e q u i r e d ---
33ZCT55SPT
or equivalent
--- ---
4---20 mA Actuator)
Single Enthalpy with
PremierLink
(PremierLink requires
I n c l u d e d ---
Not Used
---
4 --- 20mA A c t u ator)
Differential Enthalpy
with PremierLink
(PremierLink requires
I n c l u d e d ---
Not Used
---
4 --- 20mA A c t u ator)
NOTES: CO
Sensors (Optional):
2
33ZCSENCO2 --- Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor. 33ZCASPCO2 --- Aspirator box used for duct---mounted CO 33ZCT55CO2 --- Space temperature and CO 33ZCT56CO2 --- Space temperature and CO
room sensor with override.
2
room sensor with override and setpoint.
2
room sensor.
2
R e q u i r e s ---
HH57AC077
or equivalent
R e q u i r e s ---
HH57AC077
or equivalent
Table 17 – Space Sensor Mode
TB1 TERMINAL FIELD CONNECTION INPUT SIGNAL
1 T55---SEN/T56---SEN Analog (10k thermistor) 2 RMTOCC Discrete, 24VAC 3 T55---SEN/T56---SEN Analog (10k thermistor) 4 CMPSAFE Discrete, 24VAC 5 T56---SET Analog (10k thermistor) 6 FSD Discrete, 24VAC 7 LOOP---PWR Analog, 24VDC 8 SPS Discrete, 24VAC
9 IAQ---SEN Analog, 4 --- 20mA 10 FILTER Discrete, 24VAC 11 I A Q --- C O M / O AQ --- C O M/ R H --- CO M Analog, 4---20mA 12 CCN + (RED) Digital,,5VDC 13 O A Q --- S E N / R H --- S E N Analog, 4---20mA 14 CCN Gnd (WHT) Digital, 5VDC 15 AUX OUT(Power Exhaust) (Output)Discrete 24VAC 16 CCN --- (BLK) Digital, 5VDC
LEGEND:
T55 --- Space Temperature Sensor T56 --- Space Temperature Sensor CCN --- Carrier Comfort Network (communication bus) CMPSAFE --- Compressor Safety
FILTER --- Dirty Filter Switch
F S D --- F i r e Shutd o w n IAQ --- Indoor Air Quality (CO OAQ --- Outdoor Air Quality (CO RH --- Relative Humidity
SFS --- Supply Fan Status
RETURN AIR
ENTHALPY SENSOR
---
Requires ---
HH57AC078
or equivalent
)
2
)
2
48TC
37
TB1 TERMINAL FIELD CONNECTION INPUT SIGNAL
1 RAT SEN Analog (10k thermistor) 2 G Discrete, 24VAC 3 RAT SEN Analog (10k thermistor) 4 Y1 Discrete, 24VAC 5 6 Y2 Discrete, 24VAC 7 LOOP ---PWR Analog, 24VDC 8 W1 Discrete, 24VAC
9 I A Q --- S E N A n a l o g , 4 --- 2 0 m A 10 W2 Discrete, 24VAC 11 I A Q --- C O M /OA Q --- CO M / R H --- C O M A nalog, 4 --- 2 0 m A 12 CCN + (RED) Digital, 5VDC 13 O A Q --- S E N / R H --- S E N A nalog, 4 --- 2 0 m A 14 CCN Gnd (WHT) Digital, 5VDC 15 AUX OUT (Power Exhaust) (Output) Discrete 24VAC 16 CCN --- (BLK) Digital, 5VDC
LEGEND:
48TC
CCN --- Carrier Comfort Network (communication bus) G --- T h e r mo s t a t Fa n IAQ --- Indoor Air Quality (CO OAQ --- Outdoor Air Quality (CO RAT --- Return Air Temperature
)
2
)
2
Table 18 – Thermostat Mode
RH --- Relative Humidity W1 --- Thermostat Heat Stage 1 W2 --- Thermostat Heat Stage 2 Y1 --- Thermostat Cool Stage 1 Y2 --- Thermostat Cool Stage 2
Connect T--56 -- See Fig. 45 for T--56 internal connections. Install a jumper between SEN and SET terminals as illustrated. Connect T--56 terminals to TB1 terminals 1, 3 and 5 (see Fig. 46).
2
SW1
Cool Warm
3
45
SEN
61
RED(+)
WHT(GND)
BLK(-)
SET
BRN (GND) BLU (SPT)
BLK (T56)
CCN COM
SENSOR WIRING
JUMPER TERMINALS AS SHOWN
C08202
Fig. 45 -- T--56 Internal Connections
TB1 PL
SEN J6-7
SEN
Jumper
SET
SET
1
TB1
3
5
PL
J6-6
J6-5
C08213
Fig. 46 -- PremierLink T--56 Sensor
Connect Thermostat — A 7--wire thermostat connection requires a 24--v power source and a common connection. Use the R and C terminals on the LCTB’s THERMOSTAT connection strip for these. Connect the thermostat’s Y1, Y2, W1, W2 and G terminals to PremierLink TB1 as shown in Fig. 47.
SPACE THERMOSTAT
R
G J4-12
Y1
Y2
W1
W2
C
LCTB THERMOSTAT
R
TB1
2
4
6
8
10
LCTB
C
PL
J4-10
J4-8
J4-6
J4-4
THERMOSTAT
C08119
Fig. 47 -- Space Thermostat Connections
If the 48TC unit has an economizer system and free--cooling operation is required, a sensor representing Return Air Temperature must also be connected (field--supplied and installed). This sensor may be a T--55 Space Sensor (see Fig. 43) installed in the space or in the return duct, or it may be sensor PNO 33ZCSENSAT, installed in the return duct. Connect this sensor to TB1--1 and TB1--3 per Fig. 44. Temperature--resistance characteristic is found in Table 15.
Configure the unit for Thermostat Mode — Connect to the CCN bus using a CCN service tool and navigate to
38
PremierLink Configuration screen for Operating Mode. Default setting is Sensor Mode (value 1). Change the value to 0 to reconfigure the controller for Thermostat Mode.
When the PremierLink is configured for Thermostat Mode, these functions are not available: Fire Shutdown (FSD), Remote Occupied (RMTOCC), Compressor Safety (CMPSAFE), Supply Fan Status (SFS), and Filter Pressure Switch (FILTER).
Economizer controls —
Outdoor Air Enthalpy Control (PNO HH57AC077) --
The enthalpy control (HH57AC077) is available as a field--installed accessory to be used with the EconoMi$er2 damper system. The outdoor air enthalpy sensor is part of the enthalpy control. (The separate field--installed accessory return air enthalpy sensor (HH57AC078) is required for differential enthalpy control. See below.)
Locate the enthalpy control in the economizer hood. Locate two GRA leads in the factory harness and connect these leads to enthalpy control sensors 2 and 3. See Fig.
48. Connect the enthalpy control power input terminals to economizer actuator power leads RED (connect to TR) and BLK (connect to TR1).
Enthalpy Switch
2
GRA
3
GRA
LCTB ECON
6
7
Factory Wiring Harness
C08218
Fig. 48 -- Enthalpy Switch (HH57AC077) Connections
The outdoor enthalpy changeover setpoint is set at the enthalpy controller.
The enthalpy control receives the outdoor air enthalpy from the outdoor air enthalpy sensor and provides a dry contact switch input to the PremierLink controller. A closed contact indicates that outside air is preferred to the return air. An open contact indicates that the economizer should remain at minimum position.
Differential Enthalpy Control — Differential enthalpy control is provided by sensing and comparing the outside air and return air enthalpy conditions. Install the outdoor air enthalpy control as described above. Add and install a return air enthalpy sensor.
Return Air Enthalpy Sensor — Mount the return--air enthalpy sensor (HH57AC078) in the return--air duct. The
return air sensor is wired to the enthalpy controller (HH57AC077). See Fig. 49.
ENTHALPY CONTROLLER
B
TR TR1
C
A
D
SO
SR
2
LED
NOTES:
1. Remove factory-installed jumper across SR and + before connecting wires from return air sensor.
2. Switches shown in high outdoor air enthalpy state. Terminals 2 and 3 close on low outdoor air enthalpy relative to indoor air enthalpy.
3. Remove sensor mounted on back of control and locate in outside air­stream.
RED
BRN
BLK
+
+
3
1
RED
GRAY/ORN
GRAY/RED
WIRE HARNESS IN UNIT
(OUTDOOR
S
AIR
+
ENTHALPY
SENSOR)
S
(RETURN AIR
ENTHALPY
+
SENSOR)
C06019
Fig. 49 -- Outside and Return Air Enthalpy Sensor
Wiring
To wire the return air enthalpy sensor, perform the following:
1. Use a 2--conductor, 18 or 20 AWG, twisted pair cable to connect the return air enthalpy sensor to the enthal­py controller.
2. At the enthalpy control remove the factory--installed resistor from the (SR) and (+) terminals.
3. Connect the field--supplied RED wire to (+) spade connector on the return air enthalpy sensor and the (SR+) terminal on the enthalpy controller. Connect the BLK wire to (S) spade connector on the return air enthalpy sensor and the (SR) terminal on the enthalpy controller.
NOTE: The enthalpy control must be set to the “D” setting for differential enthalpy control to work properly.
The enthalpy control receives the indoor and return enthalpy from the outdoor and return air enthalpy sensors and provides a dry contact switch input to the PremierLink controller. A closed contact indicates that outside air is preferred to the return air. An open contact indicates that the economizer should remain at minimum position.
Indoor Air Quality (CO
sensor) — The indoor air quality
2
sensor accessory monitors space carbon dioxide (CO levels. This information is used to monitor IAQ levels. Several types of sensors are available, for wall mounting in the space or in return duct, with and without LCD display, and in combination with space temperature sensors. Sensors use infrared technology to measure the levels of CO
The CO
present in the space air.
2
sensors are all factory set for a range of 0 to
2
2000 ppm and a linear mA output of 4 to 20. Refer to the instructions supplied with the CO
sensor for electrical
2
48TC
)
2
39
requirements and terminal locations. See Fig. 50 for typical CO
HG
+
-
sensor wiring schematic.
2
24 VAC
OR
24 VDC
2
1
8
+
0-10VDC
-
SIG COM (J4-6)
+
4-20mA (J4-5)
NC COM NO
5
1
4
32
7
6
48TC
Fig. 50 -- Indoor/Outdoor Air Quality (CO2)Sensor
(33ZCSENCO2) -- Typical Wiring Diagram
ALARM RELAY
}
CONTACTS
C07134
Refer to Form 33CS--58SI, PremierLink Installation, Start--up, and Configuration Instructions, for detailed configuration information
Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus weatherproof enclosure) — The outdoor air CO designed to monitor carbon dioxide (CO
sensor is
2
) levels in the
2
outside ventilation air and interface with the ventilation damper in an HVAC system. The OAQ sensor is packaged with an outdoor cover. See Fig. 52. The outdoor air CO sensor must be located in the economizer outside air hood.
2
To accurately monitor the quality of the air in the conditioned air space, locate the sensor near a return--air grille (if present) so it senses the concentration of CO leaving the space. The sensor should be mounted in a location to avoid direct breath contact.
Do not mount the IAQ sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources. Allow at least 3 ft (0.9 m) between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return airstream.
Wiring the Indoor Air Quality Sensor —
For each sensor, use two 2--conductor 18 AWG (American Wire Gage) twisted--pair cables (unshielded) to connect the separate isolated 24 vac power source to the sensor and to connect the sensor to the control board terminals.
To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. See Fig. 50. Connect the 4--20 mA terminal to terminal TB1--9 and connect the SIG COM terminal to terminal TB1--7. See Fig. 51.
IAQ Sensor
SEN J5-5
COM
24 VAC
TB1
9
TB1
7
PL
J5-6
C08274
Fig. 51 -- Indoor CO2Sensor (33ZCSENCO2)
Connections
COVER REMOVED SIDE VIEW
2
Fig. 52 -- Outdoor Air Quality Sensor Cover
Wiring the Outdoor Air CO
Sensor — A dedicated power
2
supply is required for this sensor. A two--wire cable is required to wire the dedicated power supply for the sensor. The two wires should be connected to the power supply and terminals 1 and 2.
To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the OAQ sensor. See Fig. 50. Connect the 4 to 20 mA terminal to 48TC’s terminal TB1--11. Connect the SIG COM terminal to 48TC’s terminal TB1--13. See Fig. 53.
OAQ Sensor/RH Sensor
SEN J5-2
COM
24 VAC
TB1
13
TB1
11
Fig. 53 -- Outdoor CO2Sensor Connections
Refer to Form 33CS--58SI, PremierLink Installation, Start--up, and Configuration Instructions, for detailed configuration information.
Smoke Detector/Fire Shutdown (FSD) — This function is available only when PremierLink is configured for (Space) Sensor Mode. The unit is factory--wired for PremierLink FSD operation when PremierLink is factory--installed.
On 48TC units equipped with factory--installed Smoke Detector(s), the smoke detector controller implements the
C07135
PL
J5-3
C08275
40
unit shutdown through its NC contact set connected to the unit’s LCTB input. The FSD function is initiated via the smoke detector’s Alarm NO contact set. The PremierLink communicates the smoke detector’s tripped status to the CCN building control. See Fig. 23 for unit smoke detector wiring.
Fan (Pressure) Switch (NO, close on rise in pressure)
LCTB Thermostat
R
TB1
8
PL
J4-6
Alarm state is reset when the smoke detector alarm condition is cleared and reset at the smoke detector in the unit.
Filter Status Switch — This function is available only when PremierLink is configured for (Space) Sensor Mode.
PremierLink control can monitor return filter status in two ways: By monitoring a field--supplied/installed filter pressure switch or via supply fan runtime hours.
Using switch input: Install the dirty filter pressure switch according to switch manufacturer’s instructions, to measure pressure drop across the unit’s return filters. Connect one side of the switch’s NO contact set to LCTB’s THERMOSTAT--R terminal. Connect the other side of the NO contact set to TB1--10. Setpoint for Dirty Filter is set at the switch. See Fig. 54.
Filter Switch (NO, close on rising pressure (high drop))
LCTB Thermostat
R
TB1
10
PL
J4-4
C08216
Fig. 54 -- PremierLink Filter Switch Connection
When the filter switch’s NO contact set closes as filter pressure drop increases (indicating dirt--laden filters), the input signal to PremierLink causes the filter status point to read “DIRTY”.
Using Filter Timer Hours: Refer to Form 33CS--58SI for instructions on using the PremierLink Configuration screens and on unit alarm sequence.
Supply Fan Status Switch — The PremierLink control can monitor supply fan operation through a field--supplied/installed differential pressure switch. This sequence will prevent (or interrupt) operation of unit cooling, heating and economizer functions until the pressure switch contacts are closed indicating proper supply fan operation.
Install the differential pressure switch in the supply fan section according to switch manufacturer’s instructions. Arrange the switch contact to be open on no flow and to close as pressure rises indicating fan operation.
Connect one side of the switch’s NO contact set to LCTB’s THERMOSTAT--R terminal. Connect the other side of the NO contact set to TB1--8. Setpoint for Supply Fan Status is set at the switch. See Fig. 55.
C08118
Fig. 55 -- PremierLink Wiring Fan Pressure Switch
Connection
Remote Occupied Switch — The PremierLink control permits a remote timeclock to override the control’s on--board occupancy schedule and place the unit into Occupied mode. This function may also provide a “Door Switch” time delay function that will terminate cooling and heating functions after a 2--20 minute delay.
Connect one side of the NO contact set on the timeclock to LCTB’s THERMOSTAT--R terminal. Connect the other side of the timeclock contact to the unit’s TB1--2 terminal.
Remote Occupied
Time Clock
LCTB Thermostat
R
TB1
2
PL
J4-12
C08214
Fig. 56 -- PremierLink Wiring Remote Occupied
Refer to Form 33CS--58SI for additional information on configuring the PremierLink control for Door Switch timer function.
Power Exhaust (output) -- Connect the accessory Power Exhaust contactor coils(s) per Fig. 57.
Power Exhaust
PEC
TAN
TB1
15
PL
J8-3
LCTB
THERMOSTAT
GRA
C
C08120
Fig. 57 -- PremierLink Power Exhaust Output
Connection
Space Relative Humidity Sensor — The RH sensor is not used with 48TC models at this time.
CCN Communication Bus — The PremierLink controller connects to the bus in a daisy chain arrangement. Negative pins on each component must be connected to respective negative pins, and likewise, positive pins on each component must be connected to respective positive pins. The controller signal pins must be wired to the signal ground pins. Wiring connections for CCN must be made at the 3--pin plug.
48TC
41
At any baud (9600, 19200, 38400 baud), the number of controllers is limited to 239 devices maximum. Bus length may not exceed 4000 ft, with no more than 60 total devices on any 1000--ft section. Optically isolated RS--485 repeaters are required every 1000 ft.
NOTE: Carrier device default is 9600 band.
COMMUNICATION BUS WIRE SPECIFICATIONS — The CCN Communication Bus wiring is field--supplied and field--installed. It consists of shielded 3--conductor cable with drain (ground) wire. The cable selected must be identical to the CCN Communication Bus wire used for the entire network.
See Table 19 for recommended cable.
Table 19 – Recommended Cables
MANUFACTURER CABLE PART NO.
48TC
Alpha 2413 or 5463
American A22503
Belden 8772
Columbia 02525
NOTE: Conductors and drain wire must be at least 20 AWG, stranded, and tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of
--20 C to 60 C is required. Do not run communication wire in the same conduit as or next to any AC voltage wiring.
The communication bus shields must be tied together at each system element. If the communication bus is entirely within one building, the resulting continuous shield must be connected to ground at only one single point. If the communication bus cable exits from one building and enters another building, the shields must be connected to the grounds at a lightning suppressor in each building (one point only).
Connecting CCN bus:
NOTE: When connecting the communication bus cable, a color code system for the entire network is recommended to simplify installation and checkout. See Table 20 for the recommended color code.
Table 20 – Color Code Recommendations
Connect the CCN (+) lead (typically RED) to the units TB1--12 terminal. Connect the CCN (ground) lead (typically WHT) to the unit’s TB1--14 terminal. Connect the CCN (--) lead (typically BLK) to the unit’s TB1--16 terminal. See Fig. 58.
CCN Bus
+ (RED)
GND (WHT)
– (BLK)
TB1
12
TB1
14
TB1
16
PL
J2-1
J2-2
J2-3
C08276
Fig. 58 -- PremierLink CCN Bus Connections
RTU--MP CONTROL SYSTEM
The RTU--MP controller, see Fig. 59, provides expanded stand--alone operation of the HVAC system plus connection and control through communication with several Building Automation Systems (BAS) through popular third--party network systems. The available network systems are BACnet MP/TP, Modbus and Johnson J2. Communication with LonWorks is also possible by adding an accessory interface card to the RTU--MP. Selection of the communication protocol and baud rate are made at on--board DIP switches.
Carrier’s diagnostic display tools BACviewer6 Handheld and Virtual BACview (loaded on a portable PC) must be used with the RTU--MP controller. Connection to the RTU--MP board is at the J12 access port, see Fig. 59.
The RTU--MP control is factory--mounted in the 48TC unit’s main control box, to the left of the LCTB. See Fig.
60. Factory wiring is completed through harnesses connected to the LCTB. Field connections for RTU--MP sensors will be made at the Phoenix connectors on the RTU--MP board. The factory--installed RTU--MP control includes the supply--air temperature (SAT) sensor. The outdoor air temperature (OAT) sensor is included in the FIOP/accessory EconoMi$er 2 package.
Refer to Table 21, RTU--MP Controller Inputs and Outputs for locations of all connections to the RTU--MP board.
SIGNAL TYPE
+ Red 1
Ground White 2
--- Black 3
CCN BUS WIRE
COLOR
CCN PLUG PIN
NUMBER
42
Fig. 59 -- RTU--MP Multi--Protocol Control Board
48TC
C07129
43
48TC
C08458
44
Fig. 60 -- RTU--MP System Control Wiring Diagram
44
Table 21 – RTU--MP Controller Inputs and Outputs
POINT NAME
Space Temperature Sensor sptsens AI (10K Thermistor) J 2 0 --- 1 , 2 Supply Air Temperature sat AI (10K Thermistor) J 2 --- 1 , 2 Local Outside Air Temperature Sensor oatsens AI (10K Thermistor) J 2 --- 3 , 4 Space Temperature Offset Pot sptopot AI (100K Potentiometer) J 2 0 --- 3 Indoor Air Quality iaq A I (4 --- 2 0 ma) J 4 --- 2 , 3 Outdoor Air Quality oaq AI ( 4 --- 2 0 m a ) J 4 --- 5 , 6 Safety Chain Feedback safety DI (24 VAC) J 1 --- 9 Compressor Safety compstat DI (24 VAC) J 1 --- 2 Fire Shutdown firedown DI (24 VAC) J 1 --- 1 0 Enthalpy Switch enthalpy DI (24 VAC) J 2 --- 6 , 7 Humidistat Input Status humstat DI (24 VAC) J 5 --- 7 , 8
Space Relative Humidity sprh A I (4 --- 2 0 ma ) Outside Air Relative Humidity oarh A I (4 --- 2 0 ma) Supply Fan Status fanstat DI (24 VAC) Filter Status filtstat DI (24 VAC) Remote Occupancy Input remocc DI (24 VAC)
Economizer Commanded Position econocmd 4 --- 2 0 m a J2 --- 5 SupplyFanRelayState sf DO Relay (24VAC , 1A) J 1 --- 4 Compressor 1 Relay State comp_1 DO Relay (24VAC , 1A) J 1 --- 8 Compressor 2 Relay State comp_2 DO Relay (24VAC , 1A) J 1 --- 7 Heat Stage 1 Relay State heat_1 DO Relay (24VAC , 1A) J 1 --- 6 Heat Stage 2 Relay State heat_2 DO Relay (24VAC , 1A) J 1 --- 5 Power Exhaust Relay State aux_2 DO Relay (24VAC , 1A) J11 --- 3 Dehumidification Relay State humizer DO Relay (24VAC, 1A) J 1 1 --- 7 , 8
LEGEND AI --- A n a log I n p ut AO --- A n a l o g Ou tp u t DI --- D i s c r e t e I n p ut DO --- Discrete Output
* These inputs (if installed) take the place of the default input on the specific channel according to schematic. P a r a l l e l p i n s J 5 --- 1 = J 2 --- 6, J 5 --- 3 = J 1 --- 1 0 , J 5 --- 5 = J1 --- 2 a r e u se d f or f i e l d --- i n s t a l l a t i o n . Refer to the input configuration and accessory sections for more detail.
BACnet OBJECT
NAME
INPUTS
CONFIGURABLE INPUTS*
OUTPUTS
TYPE OF I/O
CONNECTION PIN
NUMBERS
J4---2,3 or J4---5,6
J 5 --- 1,2 o r J5 --- 3 , 4 or
J5 5,6 or J5--- 7,8
48TC
NOTE: Refer to Form 48--50H--T--2T for complete configuration of RTU--MP, operating sequences and troubleshooting information. Refer to RTU--MP 3rd Party Integration Guide for details on configuration and troubleshooting of connected networks. Have a copy of these manuals available at unit start--up.
The RTU--MP controller requires the use of a Carrier space sensor. A standard thermostat cannot be used with the RTU--MP system.
Supply Air Temperature (SAT) Sensor -- On FIOP--equipped 48TC unit, the unit is supplied with a supply--air temperature (SAT) sensor (33ZCSENSAT). This sensor is a tubular probe type, approx 6--inches (12.7 mm) in length. It is a nominal 10--k ohm thermistor. See Table 15 for temperature--resistance characteristic.
The SAT is factory--wired. The SAT probe is wire--tied to the supply--air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re--position the sensor in the flange of the supply--air opening or in the supply air duct (as required by local codes). Drill or punch a 1/2--in. hole in the flange or duct.
Use two field--supplied, self--drilling screws to secure the sensor probe in a horizontal orientation. See Fig. 41.
Outdoor Air Temperature (OAT) Sensor -- The OAT is factory--mounted in the EconoMi$er 2 (FIOP or accessory). It is a nominal 10k ohm thermistor attached to an eyelet mounting ring. See Table 15 for temperature--resistance characteristic.
EconoMi$er 2 -- The RTU--MP control is used with EconoMi$er2 (option or accessory) for outdoor air management. The damper position is controlled directly by the RTU--MP control; EconoMi$er 2 has no internal logic device.
Outdoor air management functions can be enhanced with field--installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors) Space CO Outdoor air CO
sensor
2
sensor
2
Field Connections -- Field connections for accessory sensors and input devices are made the RTU--MP, at plugs J1, J2, J4, J5, J11 and J20. All field control wiring that
45
connects to the RTU--MP must be routed through the raceway built into the corner post as shown in Fig. 34. The raceway provides the UL required clearance between high-- and low--voltage wiring. Pass the control wires through the hole provided in the corner post, then feed the wires thorough the raceway to the RTU--MP. Connect to the wires to the removable Phoenix connectors and then reconnect the connectors to the board.
terminal (BRN) to J20--2. Connect the SET terminal (STO or BLK) to J20--3.
BRN (COM)
BLK (STO)
BLU (SPT)
SENSOR WIRING
Space Temperature (SPT) Sensors
A field--supplied Carrier space temperature sensor is required with the RTU--MP to monitor space temperature. There are 3 sensors available for this application:
S 33ZCT55SPT, space temperature sensor with override
button
S 33ZCT56SPT, space temperature sensor with override
button and setpoint adjustment
48TC
S 33ZCT59SPT, space temperature sensor with LCD
(liquid crystal display) screen, override button, and setpoint adjustment
Use 20 gauge wire to connect the sensor to the controller. The wire is suitable for distances of up to 500 ft. Use a three--conductor shielded cable for the sensor and setpoint adjustment connections. If the setpoint adjustment (slidebar) is not required, then an unshielded, 18 or 20 gauge, two--conductor, twisted pair cable may be used.
Connect T--55 -- See Fig. 43 for typical T--55 internal connections. Connect the T--55 SEN terminals to RTU--MP J20--1 and J20--2. See Fig. 61.
SEN
SEN
Fig. 61 -- RTU--MP T--55 Sensor Connections
Connect T--56 -- See Fig. 45 for T--56 internal connections. Install a jumper between SEN and SET terminals as illustrated. Connect T--56 terminals to RTU--MP J20--1, J20--2 and J20--3 per Fig. 62.
SEN J20-1
SEN
Jumper
SET
J20-1
J20-2
J20-2
C08460
OR SET SEN
OPB C OM- PW R+
POWER
24 VAC
NOTE: Must use a separate isolated transformer.
WIRING
C07132
Fig. 63 -- Space Temperature Sensor Typical Wiring
(33ZCT59SPT)
Economizer controls —
Outdoor Air Enthalpy Control (PNO HH57AC077) --
The enthalpy control (HH57AC077) is available as a field--installed accessory to be used with the EconoMi$er2 damper system. The outdoor air enthalpy sensor is part of the enthalpy control. (The separate field--installed accessory return air enthalpy sensor (HH57AC078) is required for differential enthalpy control. See below.)
Locate the enthalpy control in the economizer hood. Locate two GRA leads in the factory harness and connect these leads to enthalpy control sensors 2 and 3. See Fig.
48. Connect the enthalpy control power input terminals to economizer actuator power leads RED (connect to TR) and BLK (connect to TR1).
The outdoor enthalpy changeover setpoint is set at the enthalpy controller.
The enthalpy control receives the outdoor air enthalpy from the outdoor air enthalpy sensor and provides a dry contact switch input to the RTU--MP controller. A closed contact indicates that outside air is preferred to the return air. An open contact indicates that the economizer should remain at minimum position.
SET
J20-3
C08461
Fig. 62 -- RTU--MP T--56 Sensor Connections
Connect T--59 -- The T--59 space sensor requires a separate, isolated power supply of 24 VAC. See Fig. 61 for internal connections at the T--59. Connect the SEN terminal (BLU) to RTU--MP J20--1. Connect the COM
Differential Enthalpy Control — Differential enthalpy control is provided by sensing and comparing the outside air and return air enthalpy conditions. Install the outdoor air enthalpy control as described above. Add and install a return air enthalpy sensor.
Return Air Enthalpy Sensor — Mount the return--air enthalpy sensor (HH57AC078) in the return--air duct. The
46
return air sensor is wired to the enthalpy controller (HH57AC077). See Fig. 49.
To wire the return air enthalpy sensor, perform the following:
1. Use a 2--conductor, 18 or 20 AWG, twisted pair cable to connect the return air enthalpy sensor to the enthal­py controller.
2. At the enthalpy control remove the factory--installed resistor from the (SR) and (+) terminals.
3. Connect the field--supplied RED wire to (+) spade connector on the return air enthalpy sensor and the (SR+) terminal on the enthalpy controller. Connect the BLK wire to (S) spade connector on the return air enthalpy sensor and the (SR) terminal on the enthalpy controller.
NOTE: The enthalpy control must be set to the “D” setting for differential enthalpy control to work properly.
The enthalpy control receives the indoor and return enthalpy from the outdoor and return air enthalpy sensors and provides a dry contact switch input to the RTU--MP controller. A closed contact indicates that outside air is preferred to the return air. An open contact indicates that the economizer should remain at minimum position.
Indoor Air Quality (CO
sensor) — The indoor air quality
2
sensor accessory monitors space carbon dioxide (CO levels. This information is used to monitor IAQ levels. Several types of sensors are available, for wall mounting in the space or in return duct, with and without LCD display, and in combination with space temperature sensors. Sensors use infrared technology to measure the levels of CO
The CO
present in the space air.
2
sensors are all factory set for a range of 0 to
2
2000 ppm and a linear mA output of 4 to 20. Refer to the instructions supplied with the CO
sensor for electrical
2
requirements and terminal locations. See Fig. 50 for typical CO
sensor wiring schematic.
2
To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. See Fig. 50. Connect the 4--20 mA terminal to terminal TB1--9 and connect the SIG COM terminal to terminal TB1--7. See Fig. 64.
IAQ Sensor
SEN
COM
J4-2
J4-3
24 VAC
C08462
Fig. 64 -- RTU--MP / Indoor CO2Sensor
(33ZCSENCO2) Connections
Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus weatherproof enclosure) — The outdoor air CO designed to monitor carbon dioxide (CO
sensor is
2
) levels in the
2
48TC
outside ventilation air and interface with the ventilation damper in an HVAC system. The OAQ sensor is packaged with an outdoor cover. See Fig. 52. The outdoor air CO
2
sensor must be located in the economizer outside air hood.
Wiring the Outdoor Air CO
Sensor — A dedicated power
2
supply is required for this sensor. A two--wire cable is required to wire the dedicated power supply for the sensor.
)
2
The two wires should be connected to the power supply and terminals 1 and 2.
To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the OAQ sensor. See Fig. 50. Connect the 4 to 20 mA terminal to 48TC’s terminal TB1--11. Connect the SIG COM terminal to 48TC’s terminal TB1--13. See Fig. 65.
OAQ Sensor/RH Sensor
SEN
J4-5
To accurately monitor the quality of the air in the conditioned air space, locate the sensor near a return--air grille (if present) so it senses the concentration of CO leaving the space. The sensor should be mounted in a location to avoid direct breath contact.
Do not mount the IAQ sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources. Allow at least 3 ft (0.9 m) between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return airstream.
Wiring the Indoor Air Quality Sensor —
For each sensor, use two 2--conductor 18 AWG (American Wire Gage) twisted--pair cables (unshielded) to connect the separate isolated 24 vac power source to the sensor and to connect the sensor to the control board terminals.
COM
2
24 VAC
Fig. 65 -- RTU--MP / Outdoor CO2Sensor
(33ZCSENCO2) Connections
On 48TC units equipped with factory--installed Smoke Detector(s), the smoke detector controller implements the unit shutdown through its NC contact set connected to the unit’s LCTB input. The FSD function is initiated via the smoke detector’s Alarm NO contact set. The PremierLink communicates the smoke detector’s tripped status to the CCN building control. See Fig. 23 for unit smoke detector wiring.
The Fire Shutdown Switch configuration,
MENU
Config→Inputs→input 5, identifies the
normally open status of this input when there is no fire alarm.
47
J4-6
C08463
Alarm state is reset when the smoke detector alarm condition is cleared and reset at the smoke detector in the unit.
Connecting Discrete Inputs
Filter Status
The filter status accessory is a field--installed accessory. This accessory detects plugged filters. When installing this accessory, the unit must be configured for filter status by setting MENU to Filter Status and normally open (N/O) or normally closed (N/C). Input 8 or 9 is recommended for easy of installation. Refer to Fig. 59 and Fig. 60 for wire terminations at J5.
Status
Fan
The fan status accessory is a field--installed accessory. This accessory detects when the indoor fan is blowing air. When installing this accessory, the unit must be
48TC
configured for fan status by setting
MENU
Config→Inputs→input3,5,8,or9to Fan
Status and normally open (N/O) or normally closed (N/C). Input 8 or 9 is recommended for easy of installation. Refer to Fig. 59 and Fig. 60 for wire terminations at J5.
Remote
Occupancy
The remote occupancy accessory is a field--installed accessory. This accessory overrides the unoccupied mode and puts the unit in occupied mode. When installing this accessory, the unit must be configured for remote occupancy by setting MENU 5, 8, or 9 to Remote Occupancy and normally open (N/O) or normally closed (N/C).
Also set MENU on/off. Input 8 or 9 is recommended for easy of installation. Refer to Fig. 59 and Table 21 for wire terminations at J5.
Config→Inputs→input3,5,8,or9
Config→Inputs→input 3,
Schedules→occupancy source to DI
Power Exhaust (output)
Connect the accessory Power Exhaust contactor coil(s) per Fig. 66.
Power Exhaust
PEC
TAN
J11-3
LCTB
THERMOSTAT
GRA
Fig. 66 -- RTU--MP Power Exhaust Connections
Space Relative Humidity Sensor -- The RH sensor is not used with 48TC models at this time.
C
C08464
Communication Wiring -- Protocols
General
Protocols are the communication languages spoken by control devices. The main purpose of a protocol is to communicate information in the most efficient method possible. Different protocols exist to provide different kinds of information for different applications. In the BAS application, many different protocols are used, depending on manufacturer. Protocols do not change the function of a controller; just make the front end user different.
The RTU--MP can be set to communicate on four different protocols: BACnet, Modbus, N2, and LonWorks. Switch 3 (SW3) on the board is used to set protocol and baud rate. Switches 1 and 2 (SW1 and SW2) are used to set the board’s network address. See Fig 67 for the switch setting per protocol. The 3rd party connection to the RTU--MP is through plug J19. Refer to the RTU--MP 3rd Party Integration Guide for more detailed information on protocols, 3rd party wiring, and networking.
NOTE: Power must be cycled after changing the SW1--3 switch settings.
SW3 Protocol Selection
PROTOCOL DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1 BACnet MS/TP
(Master) Modbus
(Slave) N2
(Slave) LonWorks Unused ON ON OFF ON OFF OFF OFF
NOTE: DS = Dip Switch BACnet MS/TP SW3 example shown
BAUD RATE DS2 DS1
9600 OFF OFF 19,200 ON OFF 38,400 OFF ON 76,800 ON ON
Unused OFF OFF OFF ON OFF Select Baud Select Baud
Unused OFF OFF ON ON OFF Select Baud Select Baud
Unused OFF OFF OFF ON ON OFF OFF
Baud Rate Selections
Fig. 67 -- RTU--MP SW3 Dip Switch Settings
48
C07166
BACnet MS/TP
BACnet Master Slave/Token Passing (MS/TP) is used for communicating BACnet over a sub--network of BACnet--only controllers. This is the default Carrier communications protocol. Each RTU--MP module acts as an MS/TP Master. The speed of an MS/TP network can range from 9600 to 76.8K baud. Physical Addresses can be set from 01 to 99.
Modbus
The RTU--MP module can speak the Modicon Modbus RTU Protocol as described in the Modicon Modbus Protocol Reference Guide, PI--MBUS--300 Rev. J. The speed of a Modbus network can range from 9600 to 76.8K baud. Physical Addresses can be set from 01 to 99.
Johnson
N2
N2 is not a standard protocol, but one that was created by Johnson Controls, Inc. that has been made open and available to the public. The speed of N2 network is limited to only 9600 baud. Physical Addresses can be set from 01 to 99.
orks
LonW
LonWorks is an open protocol that requires the use of Echelon’s Neuron microprocessor to encode and decode the LonWorks packets. In order to reduce the cost of adding that hardware on every module, a separate LonWorks Option Card (LON--OC) was designed to connect to the RTU--MP.
This accessory card is needed for LonWorks and has to be ordered and connected using the ribbon cable to plug J15. The RTU--MP’s baud rate must be set to 38.4k to communicate with the LON--OC. The address switches (SW1 & SW2) are not used with LonWorks.
Access
Local
BACview6Handheld
The BACview6is a keypad/display interface used to connect to the RTU--MP to access the control information, read sensor values, and test the RTU, see Fig. 68. This is an accessory interface that does not come with the MP controller and can only be used at the unit. Connect the
6
BACview
to the RTU--MP’s J12 local access port. There are 2 password protected levels in the display (User and Admin). The user password is defaulted to 0000 but can be changed. The Admin password is 1111 and cannot be changed. There is a 10 minute auto logout if a screen is left idle. See Form 48--50H--T--2T, Appendix A for navigation and screen content.
Virtual BACview
Virtual BACview is a freeware computer program that
6
functions as the BACview
Handheld. The USB Link interface (USB--L) is required to connect a computer to the RTU--MP board. The link cable connects a USB port to the J12 local access port. This program functions and operates identical to the handheld.
RTU--MP Troubleshooting
Communication LEDs
The LEDs indicate if the controller is speaking to the devices on the network. The LEDs should reflect communication traffic based on the baud rate set. The higher the baud rate the more solid the LEDs will appear.
48TC
Fig. 68 -- BACview6Handheld Connections
49
C07170
48TC
Table 22 – LEDs
The LEDs on the RTU--MP show the status of certain functions
If this LED is on... Status is... Power The RTU MP has power Rx The RTU MP is receiving data from the network segment
Tx The RTU MP is transmitting data over the network segment DO# The digital output is active
The Run and Error LEDs indicate control module and network status
If Run LED shows...
2 flashes per second Off Normal
2 flashes per second
2 flashes per second
2 flashes per second
2 flashes per second On
5 flashes per second On Exec start ---up aborted, Boot is running
5 flashes per second Off
7 flashes per second
14 flashes per second
On On
And Error LED shows... Status is...
2flashes, alternating with Run LED 3flashes, then off 4flashes, then pause
7 flashes per second, alternating with Run LED 14 flashes per second, alternating with Run LED
Five minute auto---restart delay after sys­tem error Control module has just been formatted Two or more devices on this network havethesameARC156networkaddress Exec halted after frequent system errors or control programs halted
Firmware transfer in progress, Boot is running Ten second recovery period after brown­out
Brownout
Failure. Try the following solutions:
S Turn the RTU --- MP off, then on. S Fo r m at t h e RTU --- M P. S Download memory to the RTU ---MP. S Replace the RTU ---MP.
50
Table 23 – Tr oubleshooting Alarms
BACnet
POINT NAME
Safety Chain Alarm safety_chain
Fire Shutdown Alarm fire_alarm
Space Temp Sensor Failure
SAT Sensor Alarm sat_alarm
High Space Temp Alarm spt_hi Alarm Generated Automatic
Low Space Temp Alarm spt_lo Alarm Generated Automatic
High Supply Air Temp sat_hi Alarm Generated Automatic
Low Supply Air Temp sat_lo Alarm Generated Automatic
Supply Fan Failed to Start
Supply Fan in Hand sf_hand
Compressor Safety Alarm
Setpoint Slider Alarm slide_alarm
Dirty Filter Alarm filter Alarm Generated
Switch Configuration Alarm
Misconfigured Analog In­put
OAT Sensor Alarm oat_alarm
Space RH Sensor Alarm sprh_alarm
Outdoor RH Sensor Alarm
High Space Humidity sprh_hi Alarm Generated Automatic
Low Space Humidity sprh_lo Alarm Generated Automatic IRH is less then 35% for more then 10 minutes.
IAQ Sensor Alarm iaq_alarm
OAQ Sensor Alarm oaq_alarm
High Carbon Dioxide Level Supply Fan Runtime Alarm Compressor 1 Runtime Alarm Compressor 2 Runtime Alarm
OBJECT
NAME
spt_alarm
sf_fail
dx_compstat Alarm Generated Automatic Compressor would not start.
sw_cfg_alarm
an_cfg_alarm
oarh_alarm Alarm Generated Automatic
co2_hi Alarm Generated Automatic CO2 reading is above 1200ppm.
sf_rntm Alarm Generated
dx1_rntm Alarm Generated
dx2_rntm Alarm Generated
ACTION TAKEN BY
CONTROL
Alarm Generated Immediate Shutdown Alarm Generated Immediate Shutdown Alarm Generated Immediate Shutdown Alarm Generated Immediate Shutdown
Alarm Generated Immediately disable Operation Alarm Generated Ramp down Operations
Alarm Generated Offset set to zero
Alarm Generated Disable misconfi­gured switch functions Alarm Generated Disable 4 selectable analog inputs Alarm Generated Economizer and Low ambient DX cooling lockout disabled. Alarm Generated Dehumidification disabled
Alarm Generated Disables IAQ Operation Econo­mizer moves to mini­mum position Alarm Generated Set OAQ to 400
RESET
METHOD
Automatic Over load Indoor Fan or Electric Heater overheat.
Automatic
Automatic
Automatic
Automatic
Automatic Bad Fan Status Switch, Configuration incorrect.
Automatic
Automatic/ reset timer when config­ured with or without switch
Configure correctly
Configure correctly
Automatic
Automatic
Automatic
Automatic
clear the timer clear the timer clear the timer
Smoke detected by smoke detector or configura­tion incorrect
Faulty, shorted, or open thermistor caused by wiring error or loose connection.
Faulty, shorted, or open thermistor caused by wiring error or loose connection.
Thespacetemperaturehasrisenabovethecool setpoint by more than the desired amount. The space temperature has dropped below the heat setpoint by more than the desired amount. SAT is greater then 160 degrees for more than 5 minutes. Thesupplyairtemperatureisbelow35_Ffor more than 5 minutes. Tripped Circuit Breaker, Broken belt, Bad indoor fan motor, Configuration incorrect, Bad fan status switch.
STOsensorisopenorshortedformorethen5 seconds.
Dirty Filter, supply fan run time exceeded, filter switch configuration wrong.
More than one binary input is configured for the same purpose. More then one discrete input is configured to provide the same function.
More then one analog input is configured to pro­videthesamefunction.
Faulty, shorted, or open thermistor caused by wiring error or loose connection.
Sensor reading is out of range. Bad sensor, bad wiring, or sensor configured incorrectly.
Sensor reading is out of range. Bad sensor, bad wiring, or sensor configured incorrectly. IRH is greater then 70% for more then 10 min­utes.
Sensor reading is out of range. Bad sensor, bad wiring, or sensor configured incorrectly.
Sensor reading is out of range. Bad sensor, bad wiring, or sensor configured incorrectly.
Supply fan run time exceeded user defined limit.
Compressor run time limit is exceeded.
Compressor run time limit is exceeded.
PROBABLE CAUSE
48TC
51
Alarms
Alarms can be checked through the network and/or the local access. All the alarms are listed in Table 23 with name, object name, action taken by control, reset method, and probable cause. There are help screens for each alarm on the local access display and listed in Form 48--50H--T--2T, Appendix A: Help Screens. Some alarms are explained in detail below.
Safety Chain
This alarm occurs immediately if the supply--fan internal overload trips or if an electric--heat limit switch trips. The Unit Status will be Shutdown and the System Mode will be Disable. When this happens LCTB (R terminal) will not have 24 VAC, but the RTU--MP board will still be powered. All unit operations stop immediately and will not restart until the alarm automatically clears. There are no configurations for this alarm; it is all based on internal
48TC
wiring. This alarm will never occur if Fire Shutdown Alarm is active.
Fire Shutdown
This alarm occurs immediately when the smoke detector senses smoke. The Unit Status will be Shutdown and the System Mode will be Disable. All unit operations stop immediately and will not restart until the alarm automatically clears. If there is not a smoke detector installed or the smoke detector did not trip, check input configurations.
Space Temp Sensor Failur
This alarm occurs if the space sensor wired to the RTU--MP is disconnected or shorted for more then 10 seconds. When this occurs the Unit Status will be Shutdown and the System Mode will be Run. Sensor, sensor connections, wiring, board connection, and configurations should be checked for faults or errors. Alarm will reset automatically when cause is fixed.
SA T Sensor
This alarm occurs immediately when the supply air temperature sensor wired to the RTU--MP is disconnected or shorted. When this occurs the Unit Status will be Shutdown and the System Mode will be Run. Sensor, sensor connections, wiring, board connection, and configurations should be checked for faults or errors. Alarm will reset automatically when cause is fixed.
Switch Configuration
This occurs if more than one binary input (inputs 3, 5, 8, and 9) is configured for the same function. When this happens the two inputs (or more) configured wrong will be disabled as an inputs. This alarm will automatically be cleared when configuration is corrected.
An example of this would be: Input 3 = Compressor Safety, input 5 = Fan Status, input 8 = Fan Status, and input 9 = Humidistat; the alarm would be active, unit would run, compressor safety and humidistat would function normally, and Fan Status (inputs 5 & 8) will be interpreted as “No Function.”
Alarm
Alarm
e
Alarm
Alarm
Misconfigured Analog
Input
This occurs if more than one analog input (inputs 1 & 2) is configured for the same sensor. When this happens the two inputs will be disabled as inputs. This alarm will automatically be cleared when configuration is corrected.
An example of this would be: Input 1 = IAQ Sensor, input 2 = IAQ Sensor; the alarm would be active, unit would run, but the IAQ Sensor (inputs 1 & 2) will be interpreted as “No Function.”
Third Party
Networking
Third party communication and networking troubleshooting should be done by or with assistance from the front end 3rd party technician. A Module Status
6
Report (Modstat) can be run from the BACview
,see Table 24 to perform. This lists information about the board status and networking state. For basic troubleshooting, see Table 25. Refer to the RTU--MP 3rd Party Integration Guide for additional information.
BACnet MS/TP
1. Verify that the BAS and controller are both set to speak the BACnet MS/TP protocol. The protocol of the controller is set via SW3 (switches 3, 4, 5, and 6). The protocol can also be verified by getting a Modstat of the controller through the BACview. Hit the “FN” key and the ’.’ key at the same time to pull up a Modstat. Scroll to the bottom of the page and there is a section entitled “Network Communications.” The active protocol and baud rate will be shown in this section.
2. Verify that the BAS and controller are set for the same baud rate. The baud rate of the controller is set via SW3 (switches 1 and 2). The baud rate can also be verified via the BACview by obtaining a Modstat. (See Fig. 67.)
3. Verify that the BAS is configured to speak 2--wire EIA--485 to the controller. The BAS may have to con­figure jumper or DIP switches on their end.
4. Verify that the BAS and the controller have the same communication settings (8 data bits, No Parity, and 1 stop bit).
5. Verify that the controller has a unique MAC address on the MS/TP bus. The controller’s MS/TP MAC ad­dress is set by its rotary address switches.
6. Verify proper wiring between the BAS and the con­troller.
7. Verify that the BAS is reading or writing to the proper BACnet objects in the controller. Download the latest points list for the controller to verify.
8. Verify that the BAS is sending his requests to the proper MS/TP MAC address of our controller.
9. Present the BAS company with a copy of our control­ler’s BACnet PICS so that they know which BACnet commands are supported. See below.
10. In certain situations, it may be necessary to tweak the MS/TP Protocol timing settings through the BAC-
6
. There are two settings that may be tweaked:
view
52
S Max Masters: Defines the highest MS/TP Master MAC
address on this MS/TP network. For example, if there are 3 master nodes on an MS/TP network, and their MAC addresses are 1, 8, and 16, then Max Masters would be set to 16 (since this is the highest MS/TP MAC address on the network). This property optimizes MS/TP network communications by preventing token passes and “poll for
Device Instance: 0160001
1 PRGs loaded. 1 PRGs running.
Module status: Firmware sections validated in flash memory ============================================ Boot16-H - v2.06:001 Jun 19 2007 RTU-MP DRIVER - v2.09:050 Jun 26 2007
Reset counters: 11 Power failures 0 Brownouts 18 Commanded warm boots 22 Commanded cold boots 0 System errors 0 Watchdog timeouts
master” requests to non--existent Master nodes (i.e., in the above example, MAC address 16 would know to pass the token back to MAC address 1 instead of counting up to MAC address 127). Each MS/TP master node on the network must have their Max Masters set to this same value. The default is 127.
48TC
System error message history: Type Specific Warning message history: Information message history: POWERUP: BACnet reinitialize warmstart 06/29/07 10:49:40 Menu file not found. 06/29/07 10:48:35
ARC156 reconfigurations during the last hour (cleared upon reset):
Total ....................... 0
Initiated by this node ...... 0
Core board hardware: Type=147, board=34, manufactured on 05/14/2007, S/N 21A740188N RAM: 1024 kBytes; FLASH: 1024 kBytes, type = 3 Base board hardware: Type=147, board=71, manufactured on 05/14/2007, S/N RMP750037N
Largest free heap space = 65536.
Database size = 742082 , used = 352162, free = 389920.
Raw physical switches: 0x01280000
Module Communications: Network Protocol=BACnet MSTP Master Network Baud Rate=9600 bps
Fig. 69 -- Module Status Report (Modstat) Example
53
C07195
Table 24 – Manufacture Date
When troubleshooting, you may need to know a control module’s manufacture date
Obtain the manufacture date from a...
Module status report (modstat) To obtain a modstat with BACview6:
Sticker on the back of the main control module board ”Serial No: RMPYMxxxxN” (Bar Coded & Typed Number)
Notes
1. Press Function (FN) key and hold.
2. Then press period (.)
3. Release both buttons. ThereportshowsthedateunderMain board hardware.
The serial numbers are unique and contain embedded information:
“RMP” --- These first three digits are unique to RTU---MP and are used as an identifier .
“YM” --- These two digits identify the last digit of the year and month (in hex, A=10/Oct)
of manufacture. ”74” would represent a date of manufacture of ”April 2007”.
xxxx” --- These four digits represent the sequential number of units produced for a given
product for the mentioned manufacturing time period.
“N” --- This final digit represents the decade and toggles between ”N” and ”M” every
ten years.
Table 25 – Basic Protocol Troubleshooting
48TC
Problem Possible cause Corrective action
No communication with 3rd party vendor
Incorrect settings on SW1, SW2 and SW3 Verify and correct switch settings. Cycle
RS485 Port has no voltage output Verify RTU---MP has correct power supply
(check with RTU---MP disconnected from RS485 commu­nication bus)
Bacnet @ 9600/19.2K --- .01 to .045vdc Check RS485 bus for external before re-
Bacnet @ 38.4K --- .06 to .09vdc Volt age, shorts or grounding
Bacnet @ 76.8K --- .1vdc before reconnecting to the bus
Modbus @ 9600 --- 76.8K --- .124vdc
N2 @ 9600 --- .124vdc
Verify devices are daisy chained and repeaters and bias terminators are correctly installed
powertoRTU---MPafterchangingswitch settings.
Possible bad driver on board.
connecting to the bus
Check 3rd party vendor RS485 commu­nication wiring guidelines and trouble­shooting procedures
S MaxInfo Frames: This property defines the maximum
number of responses that will be sent when our controller gets the token. A valid number is any positive integer. The default is 10 and should be ideal for the majority of applications. In cases where the controller is the target of many requests, this number could be increased as high as 100 or 200.
NOTE: MS/TP networks can be comprised of both Master and Slave nodes. Valid MAC addresses for Master nodes are 0 -- 127 and valid addresses for Slave nodes are 0 -- 254.
NOTE: See RTU--MP 3rd Party Integration Guide (or alternatively Form 48--50H--T--1T Appendix) for Protocol Maps.
Table 26 – Modbus Exception Codes that May be
Returned From This Controller
CODE NAME MEANING
The Modbus function code used
01 Illegal Function
02 Illegal Data Address
04 SlaveDeviceFailure
in the query is not supported by the controller .
The register address used in the query is not supported by the controller.
The Modbus Master has at­tempted to write to a non---exist­ent register or a read--- only regis­ter in the controller.
Modbus
1. Verify that the BAS and controller are both set to speak the Modbus RTU protocol. The protocol of the controller is set via SW3 (switches 3, 4, 5, and 6). The protocol can also be verified by getting a Modstat of the controller through the BACview. Hit the ”FN” key and the ’.’ key at the same time to pull up a Modstat. Scroll to the bottom of the page and there is a section entitled “Network Communications.” The active protocol and baud rate will be shown in this section.
2. Verify that the BAS and controller are set for the same baud rate. The baud rate of the controller is set via SW3 (switches 1 and 2). The baud rate can also be verified via the BACview by obtaining a Modstat (see above).
3. Verify that the BAS is configured to speak 2--wire EIA--485 to the controller. The BAS may have to con­figure jumper or DIP switches on their end.
4. Verify that the BAS and the controller have the same communication settings (8 data bits, No Parity, and 1 stop bit).
5. Verify that the controller has a unique Modbus slave address. The controller’s Modbus slave address is set by its rotary address switches.
6. Verify that the BAS is using the proper Modbus func­tion codes to access data from our controller. Sup­ported function codes are shown above.
54
7. Verify proper wiring between the BAS and the con-
A
troller.
8. Verify that the BAS is reading or writing to the proper Modbus register numbers on the controller. Download the latest points list for the controller to verify.
9. Verify that the BAS is sending his requests to the proper slave address of our controller.
NOTE: See RTU--MP 3rd Party Integration Guide (or alternatively Form 48--50H--T--1T, Appendix) for Modbus Protocol Conformance Statement.
N2
1. Verify that the BAS and controller are both set to speak the N2 protocol. The protocol of the controller is set via SW3 (switches 3, 4, 5, and 6). The protocol can also be verified by getting a Modstat of the con­troller through the BACview. Hit the “FN” key and the ’.’ key at the same time to pull up a Modstat. Scroll to the bottom of the page and there is a section entitled ”Network Communications.” The active pro­tocol and baud rate will be shown in this section.
2. Verify that the BAS and controller are set for 9600 baud. The baud rate of the controller is set via SW3 (switches 1 and 2). The baud rate can also be verified via the BACview by obtaining a Modstat (see above).
3. Verify that the BAS is configured to speak 2--wire EIA--485 to the controller. The BAS may have to con­figure jumper or DIP switches on their end.
4. Verify that the BAS and the controller have the same communication settings (8 data bits, No Parity, and 1 stop bit).
5. Verify that the controller has a unique N2 slave ad­dress on the N2 bus. The controller’s N2 slave ad­dress is set by its rotary address switches.
6. Verify proper wiring between the BAS and the con­troller.
7. Verify that the BAS is reading or writing to the proper network point addresses on the controller. Download the latest points list for the controller to verify.
8. Verify that the BAS is sending his requests to the proper slave address of our controller.
NOTE: See RTU--MP 3rd Party Integration Guide (or alternatively Form 48--50H--T--1T Appendix) for N2 Protocol Conformance Statement.
ECONOMIZER SYSTEMS
The 48TC units may be equipped with a factory--installed or accessory (field--installed) economizer system. Two types are available: with a logic control system (EconoMi$er IV) and without a control system (EconoMi$er2, for use with external control systems such as PremierLink). See Fig. 70 and Fig. 71 for component locations on each type. See Fig. 72 and Fig. 73 for economizer section wiring diagrams.
Both EconoMi$ers use direct--drive damper actuators.
ECONOMI$ER IV CONTROLLER
WIRING HARNESS
CTUATOR
Fig. 70 -- EconoMi$er IV Component Locations
ECONOMI$ER2 PLUG
BAROMETRIC RELIEF DAMPER
Fig. 71 -- EconoMi$er2 Component Locations
OUTSIDE AIR TEMPERATURE SENSOR
LOW AMBIENT SENSOR
OUTDOOR AIR HOOD
HOOD SHIPPING BRACKET
GEAR DRIVEN DAMPER
C06021
C06022
48TC
55
48TC
DCV— Demand Controlled Ventilation IAQ — Indoor Air Quality LA — Low Ambient Lockout Device OAT — Outdoor-Air Temperature POT— Potentiometer RAT— Return-Air Temperature
LEGEND
8
7
Potentiometer Defaults Settings: Power Exhaust Middle Minimum Pos. Fully Closed DCV Max. Middle DCV Set Middle Enthalpy C Setting
Fig. 72 -- EconoMi$er IV Wiring
FOR OCCUPANCY CONTROL REPLACE JUMPER WITH FIELD-SUPPLIED TIME CLOCK
NOTES:
1. 620 ohm, 1 watt 5% resistor should be removed only when using differential enthalpy or dry bulb.
2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power supply, it cannot have the secondary of the transformer grounded.
3. For field-installed remote minimum position POT, remove black wire jumper between P and P1 and set c ontrol minimum position POT to the minimum position.
C06028
BLACK
4
TRANSFORMER GROUND
3
5
BLUE
500 OHM RESISTOR
VIOLET
NOTE 1
RUN
NOTE 3
50HJ540573
ACTUATOR ASSEMBLY
DIRECT DRIVE
ACTUATOR
NOTES:
1. Switch on actuator must be in run position for economizer to operate.
2. PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sen sor or HH57A077 enthalpy sensor.
3. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.
OAT SENSOR
4-20mA SIGNAL
PINK
YELLOW
WHITE
2
8
6
7
RED
24 VAC
1
10
11
9
12
ECONOMISER2 PLUG
4-20 mA TO J9 ON PremierLink BOARD
C08310
Fig. 73 -- EconoMi$er2 with 4 to 20 mA Control Wiring
56
Table 27 – EconoMi$er IV Input/Output Logic
INPUTS OUTPUTS
Demand Control
Ventilation (DCV)
(Free Cooling LED
Below set
(DCV LED Off)
(Free Cooling LED
(Free Cooling LED
Above set
(DCV LED On)
(Free Cooling LED
* For single enthalpy control, the module compares outdoor enthalpy to the ABCD setpoint. † Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied). ** Modulation is based on the supply-air sensor signal. †† Modulation is based on the DCV signal. *** Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum position (DCV)
or fully open (supply-air signal).
††† Modulation is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV) or fully
open (supply-air signal).
Enthalpy*
Outdoor Return
High
Low
Off)
Low
High
On)
High
Low
Off)
Low
High
On)
Y1 Y2
On On On On
Off Off Off Off
On On On Off
On Off Off Off
Off Off Off Off Minimum position Closed On On On On
On Off On Off
Off Off Off Off On On On Off
Off Off Off Off
Compressor NTerminal†
Stage1Stage
2
Occupied Unoccupied
Damper
Minimum position ClosedOn Off On Off
Modulating** (between
min. position and full-
open)
Modulating†† (between
min. position and DCV
maximum)
Modulating*** Modulating†††On Off Off Off
Modulating** (be-
tween closed and
full-open)
Modulating†† (be-
tween closed and
DCV
maximum)
48TC
Fig. 74 -- EconoMi$er IV Functional View
EconoMi$er IV
Table 27 provides a summary of EconoMi$er IV. Troubleshooting instructions are enclosed.
A functional view of the EconoMi$er is shown in Fig. 74. Typical settings, sensor ranges, and jumper positions are also shown. An EconoMi$er IV simulator program is available from Carrier to help with EconoMi$er IV training and troubleshooting.
C06053
EconoMi$er IV Standard
Sensors
Outdoor Air Temperature (OAT) Sensor
The outdoor air temperature sensor (HH57AC074) is a 10 to 20 mA device used to measure the outdoor-air temperature. The outdoor-air temperature is used to determine when the EconoMi$er IV can be used for free cooling. The sensor is factory-installed on the EconoMi$er IV in the outdoor airstream. (See Fig. 75.) The operating range of temperature measurement is 40_ to 100_F(4_ to 38_C). See Fig. 77.
57
Supply Air Temperature (SAT) Sensor
The supply air temperature sensor is a 3 K thermistor located at the inlet of the indoor fan. (See Fig. 75.) This sensor is factory installed. The operating range of temperature measurement is 0° to 158_F(--18_ to 70_C). See Table 15 for sensor temperature/resistance values.
SUPPLY AIR TEMPERATURE SENSOR MOUNTING LOCATION
SUPPLY AIR TEMPERATURE SENSOR
and D. See Fig. 77 for the corresponding temperature changeover values.
48TC
Fig. 75 -- Supply Air Sensor Location
The temperature sensor looks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
Outdoor Air Lockout Sensor
The EconoMi$er IV is equipped with an ambient temperature lockout switch located in the outdoor airstream which is used to lock out the compressors below a42_F(6_C) ambient temperature. (See Fig. 70.)
EconoMi$er IV Control
Modes
IMPORTANT: The optional EconoMi$er2 does not
include a controller. The EconoMi$er2 is operated by a 4 to 20 mA signal from an existing field-supplied controller (such as PremierLinkcontrol). See Fig. 72 for wiring information.
Determine the EconoMi$er IV control mode before set up of the control. Some modes of operation may require different sensors. (See Table 22.) The EconoMi$er IV is supplied from the factory with a supply--air temperature sensor and an outdoor-- air temperature sensor. This allows for operation of the EconoMi$er IV with outdoor air dry bulb changeover control. Additional accessories can be added to allow for different types of changeover control and operation of the EconoMi$er IV and unit.
Outdoor Dry Bulb Changeover
The standard controller is shipped from the factory configured for outdoor dry bulb changeover control. The outdoor air and supply air temperature sensors are included as standard. For this control mode, the outdoor temperature is compared to an adjustable setpoint selected on the control. If the outdoor-air temperature is above the setpoint, the EconoMi$er IV will adjust the outside air dampers to minimum position. If the outdoor-air temperature is below the setpoint, the position of the outside air dampers will be controlled to provided free cooling using outdoor air. When in this mode, the LED next to the free cooling setpoint potentiometer will be on. The changeover temperature setpoint is controlled by the free cooling setpoint potentiometer located on the control. (See Fig. 76.) The scale on the potentiometer is A, B, C,
C06033
C06034
Fig. 76 -- EconoMi$er IV Controller Potentiome t er
and LED Locations
19
LED ON
mA
18
17
16
15
14
13
12
11
10
9
40
LED OFF
45
D
50
60
55
DEGREES FAHRENHEIT
LED ON
LED OFF
65
C
LED ON
B
LED ON
A
LED OFF
100
90
85
80
95
C06035
70
LED OFF
75
Fig. 77 -- Outside Air Temperature Changeover
Setpoints
30
25
20
15
10
5
0
0.13 0.20 0.22 0. 25 0.30 0. 35 0.40 0.45 0.50
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
C06031
Fig. 78 -- Outdoor--Air Damper Leakage
Differential Dry Bulb Control
For differential dry bulb control the standard outdoor dry bulb sensor is used in conjunction with an additional accessory dry bulb sensor (part number CRTEMPSN002A00). The accessory sensor must be mounted in the return airstream. (See Fig. 79.) Wiring is
58
provided in the EconoMi$er IV wiring harness. (See Fig.
70.)
ECONOMI$ERIV CONTROLLER
ECONOMI$ERIV
GROMMET
RETURN AIR SENSOR
RETURN DUCT (FIELD-PROVIDED)
C07085
Fig. 79 -- Return Air Temperature or Enthalpy Sensor
Mounting Location
In this mode of operation, the outdoor-air temperature is compared to the return-air temperature and the lower temperature airstream is used for cooling. When using this mode of changeover control, turn the enthalpy setpoint potentiometer fully clockwise to the D setting. (See Fig.
76.)
Outdoor Enthalpy Changeover
For enthalpy control, accessory enthalpy sensor (part number HH57AC078) is required. Replace the standard outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. (See Fig.
79.) When the outdoor air enthalpy rises above the outdoor enthalpy changeover setpoint, the outdoor-air damper moves to its minimum position. The outdoor enthalpy changeover setpoint is set with the outdoor enthalpy setpoint potentiometer on the EconoMi$er IV controller. The setpoints are A, B, C, and D. (See Fig. 80.) The factory-installed 620-ohm jumper must be in place across terminals S
and SR+ on the EconoMi$er IV
R
controller.
48TC
CONTROL
CURVE
4
1
2
1
A B C D
6
1
46
8
3
A
(18)
4
4
80
42
(21)
1
(27)
75
(24)
70
0
0
0
9
80
70
0
6
50
A
B
C
D
70
75
80
(24)
(21)
(27)
40
65
65
(18)
CONTROL POINT
deg. F (deg. C)
APPROX.
AT 50% RH
73 (23) 70 (21) 67 (19) 63 (17)
28
ENTHALPY BTU PER POUND DRY AIR
26
4
2
2
2
0
2
8
1
45
(7) 40 (4)
35 (2)
35
40
45
(2)
(4)
(7)
APPROXIMATE DRY BULB TEMPERATURE--degrees F (degrees C)
6
3
4
3
32
30
60
(16)
55
(13)
B
50
C
(10)
D
50
55
60
(10)
(13)
(16)
Fig. 80 -- Enthalpy Changeover Setpoints
85
(29)90(32)95(35)
RELATIVE HUMIDITY (%)
0
4
30
85
(29)90(32)95(35)
100
105
110
(38)
(41)
(43)
20
0
1
HIGH LIMIT
110 (43)
CURVE
(38)
105
100
(41)
C06037
59
N1
P1
T1
AQ1
SO+
SR+
CO SENSOR MAX RANGE SETTING
TR1
EXH
2V 10V
EXH
Open
2V 10V
DCV
2V 10V
Free Cool
B
A
Set
Min Pos
DCV
Max
DCV
Set
C
D
N
P
T
AQ
SO
SR
TR
24
24 Vac
Va c
COM
HOT
_
+
12
5
4
3
EF1
EF
6000
5000
4000
3000
2000
1000
RANGE CONFIGURATION (ppm)
0
Fig. 82 -- CO2Sensor Maximum Range Settings
2
800 ppm 900 ppm 1000 ppm 1100 ppm
2345678
DAMPER VOLTAGE FOR MAX VENTILATION RATE
C06039
48TC
Fig. 81 -- EconoMi$er IV Control
Differential Enthalpy Control
For differential enthalpy control, the EconoMi$er IV controller uses two enthalpy sensors (HH57AC078 and CRENTDIF004A00), one in the outside air and one in the return air duct. The EconoMi$er IV controller compares the outdoor air enthalpy to the return air enthalpy to determine EconoMi$er IV use. The controller selects the lower enthalpy air (return or outdoor) for cooling. For example, when the outdoor air has a lower enthalpy than the return air, the EconoMi$er IV opens to bring in outdoor air for free cooling.
Replace the standard outside air dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. (See Fig. 70.) Mount the return air enthalpy sensor in the return air duct. (See Fig. 79.) Wiring is provided in the EconoMi$er IV wiring harness. (See Fig. 70.) The outdoor enthalpy changeover setpoint is set with the outdoor enthalpy setpoint potentiometer on the EconoMi$er IV controller. When using this mode of changeover control, turn the enthalpy setpoint potentiometer fully clockwise to the D setting.
Indoor Air Quality (IAQ) Sensor Input
The IAQ input can be used for demand control ventilation control based on the level of CO
measured in the space
2
or return air duct. Mount the accessory IAQ sensor according to
manufacturer specifications. The IAQ sensor should be wired to the AQ and AQ1 terminals of the controller. Adjust the DCV potentiometers to correspond to the DCV voltage output of the indoor air quality sensor at the user-determined setpoint. (See Fig. 82.)
C06038
If a separate field-supplied transformer is used to power the IAQ sensor, the sensor must not be grounded or the EconoMi$er IV control board will be damaged.
When using demand ventilation, the minimum damper position represents the minimum ventilation position for VOC (volatile organic compounds) ventilation requirements. The maximum demand ventilation position is used for fully occupied ventilation.
When demand ventilation control is not being used, the minimum position potentiometer should be used to set the occupied ventilation position. The maximum demand ventilation position should be turned fully clockwise.
Exhaust Setpoint Adjustment
The exhaust setpoint will determine when the exhaust fan runs based on damper position (if accessory power exhaust is installed). The setpoint is modified with the Exhaust Fan Setpoint (EXH SET) potentiometer. (See Fig.
76.) The setpoint represents the damper position above which the exhaust fans will be turned on. When there is a call for exhaust, the EconoMi$er IV controller provides a 45 ± 15 second delay before exhaust fan activation to allow the dampers to open. This delay allows the damper to reach the appropriate position to avoid unnecessary fan overload.
Minimum Position Control
There is a minimum damper position potentiometer on the EconoMi$er IV controller. (See Fig. 76.) The minimum damper position maintains the minimum airflow into the building during the occupied period.
When using demand ventilation, the minimum damper position represents the minimum ventilation position for VOC (volatile organic compound) ventilation requirements. The maximum demand ventilation position is used for fully occupied ventilation.
When demand ventilation control is not being used, the minimum position potentiometer should be used to set the occupied ventilation position. The maximum demand ventilation position should be turned fully clockwise.
Adjust the minimum position potentiometer to allow the minimum amount of outdoor air, as required by local codes, to enter the building. Make minimum position adjustments with at least 10_F temperature difference between the outdoor and return-air temperatures.
60
To determine the minimum position setting, perform the following procedure:
1. Calculate the appropriate mixed air temperature using the following formula:
OA
(T
Ox
100 100
+(TR
)
RA
x
)=T
M
TO= Outdoor-Air Temperature OA = Percent of Outdoor Air T
= Return-Air Temperature
R
RA = Percent of Return Air
= Mixed-Air Temperature
T
M
As an example, if local codes require 10% outdoor air during occupied conditions, outdoor-air temperature is 60_F, and return-air temperature is 75_F.
(60 x .10) + (75 x .90) = 73.5_ F
2. Disconnect the supply air sensor from terminals T and T1.
3. Ensure that the factory-installed jumper is in place across terminals P and P1. If remote damper positioning is being used, make sure that the terminals are wired according to Fig. 59 and that the minimum position potentiometer is turned fully clockwise.
4. Connect 24 vac across terminals TR and TR1.
5. Carefully adjust the minimum position potentiometer until the measured mixed air temperature matches the calculated value.
6. Reconnect the supply air sensor to terminals T and T1.
Remote control of the EconoMi$er IV damper is desirable when requiring additional temporary ventilation. If a field-supplied remote potentiometer (Honeywell part number S963B1128) is wired to the EconoMi$er IV controller, the minimum position of the damper can be controlled from a remote location.
To control the minimum damper position remotely, remove the factory-installed jumper on the P and P1 terminals on the EconoMi$er IV controller. Wire the field-supplied potentiometer to the P and P1 terminals on the EconoMi$er IV controller. (See Fig. 81.)
Damper Movement
Damper movement from full open to full closed (or vice
1
versa) takes 2
/2minutes.
Thermostats
The EconoMi$er IV control works with conventional thermostats that have a Y1 (cool stage 1), Y2 (cool stage
2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The EconoMi$er IV control does not support space temperature sensors. Connections are made at the thermostat terminal connection board located in the main control box.
Occupancy Control
The factory default configuration for the EconoMi$er IV control is occupied mode. Occupied status is provided by the black jumper from terminal TR to terminal N. When unoccupied mode is desired, install a field--supplied
timeclock function in place of the jumper between TR and N. When the timeclock contacts are closed, the EconoMi$er IV control will be in occupied mode. When the timeclock contacts are open (removing the 24--v signal from terminal N), the EconoMi$er IV will be in unoccupied mode.
Demand Control Ventilation (DCV)
When using the EconoMi$er IV for demand controlled ventilation, there are some equipment selection criteria which should be considered. When selecting the heat capacity and cool capacity of the equipment, the maximum ventilation rate must be evaluated for design conditions. The maximum damper position must be calculated to provide the desired fresh air.
Typically the maximum ventilation rate will be about 5 to 10% more than the typical cfm required per person, using normal outside air design criteria.
A proportional anticipatory strategy should be taken with the following conditions: a zone with a large area, varied occupancy, and equipment that cannot exceed the required ventilation rate at design conditions. Exceeding the required ventilation rate means the equipment can condition air at a maximum ventilation rate that is greater than the required ventilation rate for maximum occupancy. A proportional-anticipatory strategy will cause the fresh air supplied to increase as the room CO increases even though the CO reached. By the time the CO
setpoint has not been
2
level reaches the setpoint,
2
2
level
the damper will be at maximum ventilation and should maintain the setpoint.
In order to have the CO
sensor control the economizer
2
damper in this manner, first determine the damper voltage output for minimum or base ventilation. Base ventilation is the ventilation required to remove contaminants during unoccupied periods. The following equation may be used to determine the percent of outside air entering the building for a given damper position. For best results there should be at least a 10 degree difference in outside and return-air temperatures.
OA
(T
Ox
100 100
+(TR
)
RA
x
)=T
M
TO= Outdoor-Air Temperature OA = Percent of Outdoor Air T
= Return-Air Temperature
R
RA = Percent of Return Air T
= Mixed-Air Temperature
M
Once base ventilation has been determined, set the minimum damper position potentiometer to the correct position.
The same equation can be used to determine the occupied or maximum ventilation rate to the building. For example, an output of 3.6 volts to the actuator provides a base ventilation rate of 5% and an output of 6.7 volts provides the maximum ventilation rate of 20% (or base plus 15 cfm per person). Use Fig. 82 to determine the maximum setting of the CO
sensor. For example, an 1100 ppm
2
setpoint relates to a 15 cfm per person design. Use the 1100 ppm curve on Fig. 82 to find the point when the CO sensor output will be 6.7 volts. Line up the point on the
48TC
2
61
graph with the left side of the chart to determine that the range configuration for the CO
sensor should be 1800
2
ppm. The EconoMi$er IV controller will output the 6.7 volts from the CO
sensor to the actuator when the CO
2
concentration in the space is at 1100 ppm. The DCV setpoint may be left at 2 volts since the CO voltage will be ignored by the EconoMi$er IV controller until it rises above the 3.6 volt setting of the minimum position potentiometer.
Once the fully occupied damper position has been determined, set the maximum damper demand control ventilation potentiometer to this position. Do not set to the maximum position as this can result in over-ventilation to the space and potential high humidity levels.
Sensor Configuration
CO
2
The CO2sensor has preset standard voltage settings that can be selected anytime after the sensor is powered up. (See Table 28.)
48TC
Use setting 1 or 2 for Carrier equipment. (See Table 28.)
1. Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
Table 28 – EconoMi$er IV Sensor Usage
ECONOMI$ER IV WITH OUTDOOR AIR DRY
APPLICATION
Outdoor Air
Dry Bulb
Differential
Dry Bulb
Single Enthalpy HH57AC078
Differential
Enthalpy
CO2for DCV
Control using a
Wall-Mounted
CO
Sensor
2
CO2for DCV
Control using a
Duct-Mounted
CO
Sensor
2
* CRENTDIF004A00 and CRTEMPSN002A00 accessories are
used on many different base units. As such, these kits may
contain parts that will not be needed for installation. † 33ZCSENCO2 is an accessory CO ** 33ZCASPCO2 is an accessory aspirator box required f or duct-
mounted applications. †† CRCBDI OX005A00 is an accessory that contains both
33ZCSENCO2 and 33ZCASPCO2 accessories.
None. The outdoor air dry bulb sensor is
HH57AC078 and CRENTDIF004A00*
33ZCSENCO2† and
33ZCASPCO2**OR
BULB SENSOR
Accessories Required
factory installed.
CRTEMPSN002A00*
33ZCSENCO2
CRCBDIOX005A00††
sensor.
2
3. Use the Up/Down button to select the preset number. (See Table 28.)
4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.
The custom settings of the CO
sensor can be changed
2
anytime after the sensor is energized. Follow the steps below to change the non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD menu and press Enter.
2
sensor
4. Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached.
2
5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode to continue to the next variable.
Dehumidification of Fresh Air with DCV (Demand Controlled Ventilation) Control
If normal rooftop heating and cooling operation is not adequate for the outdoor humidity level, an energy recovery unit and/or a dehumidification option should be considered.
EconoMi$er IV Pr
eparation
This procedure is used to prepare the EconoMi$er IV for troubleshooting. No troubleshooting or testing is done by performing the following procedure.
NOTE: This procedure requires a 9--v battery, 1.2 kilo--ohm resistor, and a 5.6 kilo--ohm resistor which are not supplied with the EconoMi$er IV.
IMPORTANT: Be sure to record the positions of all potentiometers before starting troubleshooting.
1. Disconnect power at TR and TR1. All LEDs should be off. Exhaust fan contacts should be open.
2. Disconnect device at P and P1.
3. Jumper P to P1.
4. Disconnect wires at T and T1. Place 5.6 kilo--ohm resistor across T and T1.
5. Jumper TR to 1.
6. Jumper TR to N.
7. If connected, remove sensor from terminals SO and +. Connect 1.2 kilo--ohm 4074EJM checkout resistor across terminals SO and +.
8. Put 620--ohm resistor across terminals SR and +.
9. Set minimum position, DCV setpoint, and exhaust po­tentiometers fully CCW (counterclockwise).
10. Set DCV maximum position potentiometer fully CW (clockwise).
11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.
Differential
Enthalpy
To check differential enthalpy:
1. Make sure EconoMi$er IV preparation procedure has been performed.
2. Place 620--ohm resistor across SO and +.
3. Place 1.2 kilo--ohm resistor across SR and +. The Free Cool LED should be lit.
4. Remove 620--ohm resistor across SO and +. The Free Cool LED should turn off.
5. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
62
Single Enthalpy
To check single enthalpy:
1. Make sure EconoMi$er IV preparation procedure has been performed.
2. Set the enthalpy potentiometer to A (fully CCW). The Free Cool LED should be lit.
3. Set the enthalpy potentiometer to D (fully CW). The Free Cool LED should turn off.
4. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
DCV (Demand Controlled Ventilation) and Exhaust
To check DCV and Power Exhaust:
1. Make sure EconoMi$er IV preparation procedure has been performed.
2. Ensure terminals AQ and AQ1 are open. The LED for both DCV and Exhaust should be off. The actuator should be fully closed.
3. Connect a 9--v battery to AQ (positive node) and AQ1 (negative node). The LED for both DCV and Exhaust should turn on. The actuator should drive to between 90 and 95% open.
4. Turn the Exhaust potentiometer CW until the Exhaust LED turns off. The LED should turn off when the po­tentiometer is approximately 90%. The actuator should remain in position.
5. Turn the DCV setpoint potentiometer CW until the DCV LED turns off. The DCV LED should turn off when the potentiometer is approximately 9--v. The ac­tuator should drive fully closed.
6. Turn the DCV and Exhaust potentiometers CCW until the Exhaust LED turns on. The exhaust contacts will close 30 to 120 seconds after the Exhaust LED turns on.
7. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
DCV Minimum and Maximum
To check the DCV minimum and maximum position:
1. Make sure EconoMi$er IV preparation procedure has been performed.
2. Connect a 9--v battery to AQ (positive node) and AQ1 (negative node). The DCV LED should turn on. The actuator should drive to between 90 and 95% open.
3. Turn the DCV Maximum Position potentiometer to midpoint. The actuator should drive to between 20 and 80% open.
4. Turn the DCV Maximum Position potentiometer to fully CCW. The actuator should drive fully closed.
Position
Power
5. Turn the Minimum Position potentiometer to mid­point. The actuator should drive to between 20 and 80% open.
6. Turn the Minimum Position Potentiometer fully CW. The actuator should drive fully open.
7. Remove the jumper from TR and N. The actuator should drive fully closed.
8. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
Supply--Air Sensor
To check supply--air sensor input:
1. Make sure EconoMi$er IV preparation procedure has been performed.
2. Set the Enthalpy potentiometer to A. The Free Cool LED turns on. The actuator should drive to between 20 and 80% open.
3. Remove the 5.6 kilo--ohm resistor and jumper T to T1. The actuator should drive fully open.
4. Remove the jumper across T and T1. The actuator should drive fully closed.
5. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
EconoMi$er IV Troubleshooting
This procedure is used to return the EconoMi$er IV to operation. No troubleshooting or testing is done by performing the following procedure.
1. Disconnect power at TR and TR1.
2. Set enthalpy potentiometer to previous setting.
3. Set DCV maximum position potentiometer to previ­ous setting.
4. Set minimum position, DCV setpoint, and exhaust po­tentiometers to previous settings.
5. Remove 620--ohm resistor from terminals SR and +.
6. Remove 1.2 kilo--ohm checkout resistor from termin­als SO and +. If used, reconnect sensor from termin­als SO and +.
7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
9. Remove 5.6 kilo--ohm resistor from T and T1. Recon­nect wires at T and T1.
10. Remove jumper from P to P1. Reconnect device at P and P1.
11. Apply power (24 vac) to terminals TR and TR1.
Input
Completion
WIRING DIAGRAMS
See Fig. 83 and Fig. 84 for typical wiring diagrams.
48TC
63
48TC
C08308
Fig. 83 -- 48TC Typical Unit Wiring Diagram -- Power (A06, 208/230--3--60)
64
C08317
48TC
65
Fig. 84 -- 48TC Unit Wiring Diagram -- Control (A06)
PRE--START-- UP
!
WARNING
PERSONAL INJURY HAZARD
Failure to follow this warning could result in personal injury or death.
1. Follow recognized safety practices and wear pro­tective goggles when checking or servicing refri­gerant system.
2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured.
3. Do not remove compressor terminal cover until all electrical sources are disconnected.
48TC
4. Relieve all pressure from system before touching or disturbing anything inside terminal box if refri­gerant leak is suspected around compressor ter­minals.
5. Never attempt to repair soldered connection while refrigerant system is under pressure.
6. Do not use torch to remove any component. Sys­tem contains oil and refrigerant under pressure. To remove a component, wear protective goggles and proceed as follows:
a. Shut off electrical power and then gas to unit.
b. Recover refrigerant to relieve all pressure from
system using both high--pressure and low pressure ports.
c. Cut component connection tubing with tubing
cutter and remove component from unit.
d. Carefully unsweat remaining tubing stubs
when necessary. Oil can ignite when exposed to torch flame.
4. Verify the following conditions: a. Make sure that condenser--fan blade are correctly
positioned in fan orifice. See Condenser--Fan
Adjustment section for more details. b. Make sure that air filter(s) is in place. c. Make sure that condensate drain trap is filled
with water to ensure proper drainage. d. Make sure that all tools and miscellaneous loose
parts have been removed.
START--UP, GENERAL
Unit Preparation
Make sure that unit has been installed in accordance with installation instructions and applicable codes.
Gas Piping
Check gas piping for leaks.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect gas piping from unit when leak testing at pressure greater than 1/2 psig. Pressures greater than 1/2 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 1/2 psig, it must be replaced before use. When pressure testing field--supplied gas piping at pressures of 1/2 psig or less, a unit connected to such piping must be isolated by manually closing the gas valve.
Return--Air Filters
Proceed as follows to inspect and prepare the unit for initial start--up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING, CAUTION, and INFORMATION labels attached to, or shipped with, unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages such
as broken lines, loose parts, or disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connec-
tions and on unit base. Detecting oil generally indicates a refrigerant leak. Leak--test all refri­gerant tubing connections using electronic leak detector, halide torch, or liquid--soap solution.
c. Inspect all field--wiring and factory--wiring con-
nections. Be sure that connections are completed and tight. Be sure that wires are not in contact with refrigerant tubing or sharp edges.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin comb.
Make sure correct filters are installed in unit (see Appendix II -- Physical Data). Do not operate unit without return--air filters.
Outdoor--Air Inlet Screens
Outdoor--air inlet screen must be in place before operating unit.
Compressor Mounting
Compressors are internally spring mounted. Do not loosen or remove compressor hold down bolts.
Internal Wiring
Check all electrical connections in unit control boxes. Tighten as required.
Refrigerant Service Ports
Each unit system has two 1/4” SAE flare (with check valves) service ports: one on the suction line, and one on the compressor discharge line. Be sure that caps on the ports are tight.
Compressor Rotation
On 3--phase units with scroll compressors, it is important to be certain compressor is rotating in the proper
66
direction. To determine whether or not compressor is rotating in the proper direction:
1. Connect service gauges to suction and discharge pres­sure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start--up.
If the suction pressure does not drop and the discharge pressure does not rise to normal levels:
4. Note that the evaporator fan is probably also rotating in the wrong direction.
5. Turn off power to the unit and install lockout tag.
6. Reverse any two of the unit power leads.
7. Re--energize to the compressor. Check pressures.
The suction and discharge pressure levels should now move to their normal start--up levels.
NOTE: When the compressor is rotating in the wrong direction, the unit will make an elevated level of noise and will not provide cooling.
Cooling
Set space thermostat to OFF position. To start unit, turn on main power supply. Set system selector switch at COOL position and fan switch at AUTO. position. Adjust thermostat to a setting below room temperature. Compressor starts on closure of contactor.
Check unit charge. Refer to Refrigerant Charge section.
Reset thermostat at a position above room temperature. Compressor will shut off. Evaporator fan will shut off after a 30--second delay.
To shut off unit, set system selector switch at OFF position. Resetting thermostat at a position above room temperature shuts unit off temporarily until space temperature exceeds thermostat setting.
Main Burners
Main burners are factory set and should require no adjustment.
To check ignition of main burners and heating controls, move thermostat setpoint above room temperature and verify that the burners light and evaporator fan is energized. Check heating effect, then lower the thermostat setting below the room temperature and verify that the burners and evaporator fan turn off.
Refer to Tables 11 and 12 for the correct orifice to use at high altitudes.
Heating
1. Purge gas supply line of air by opening union ahead of the gas valve. If gas odor is detected, tighten union and wait 5 minutes before proceeding.
2. Turn on electrical supply and manual gas valve.
3. Set system switch selector at HEAT position and fan switch at AUTO. or ON position. Set heating temper­ature lever above room temperature.
4. The induced--draft motor will start.
5. After a call for heating, the main burners should light within 5 seconds. If the burner does not light, then there is a 22--second delay before another 5--second try. If the burner still does not light, the time delay is repeated. If the burner does not light within 15 minutes, there is a lockout. To reset the control, break the 24 v power to W1.
6. The evaporator--fan motor will turn on 45 seconds after burner ignition.
7. The evaporator--fan motor will turn off in 45 seconds after the thermostat temperature is satisfied.
8. Adjust airflow to obtain a temperature rise within the range specified on the unit nameplate.
NOTE: The default value for the evaporator--fan motor on/off delay is 45 seconds. The Integrated Gas Unit Controller (IGC) modifies this value when abnormal limit switch cycles occur. Based upon unit operating conditions, the on delay can be reduced to 0 seconds and the off delay can be extended to 180 seconds. When one flash of the LED is observed, the evaporator--fan on/off delay has been modified.
If the limit switch trips at the start of the heating cycle during the evaporator on delay, the time period of the on delay for the next cycle will be 5 seconds less than the time at which the switch tripped. (Example: If the limit switch trips at 30 seconds, the evaporator--fan on delay for the next cycle will occur at 25 seconds.) To prevent short--cycling, a 5--second reduction will only occur if a minimum of 10 minutes has elapsed since the last call for heating.
The evaporator--fan off delay can also be modified. Once the call for heating has ended, there is a 10--minute period during which the modification can occur. If the limit switch trips during this period, the evaporator--fan off delay will increase by 15 seconds. A maximum of 9 trips can occur, extending the evaporator--fan off delay to 180 seconds.
To restore the original default value, reset the power to the unit.
To shut off unit, set system selector switch at OFF position. Resetting heating selector lever below room temperature will temporarily shut unit off until space temperature falls below thermostat setting.
Ventilation (Continuous Fan)
Set fan and system selector switches at ON and OFF positions, respectively. Evaporator fan operates continuously to provide constant air circulation. When the evaporator--fan selector switch is turned to the OFF position, there is a 30--second delay before the fan turns off.
48TC
67
START--UP, PREMIERLINK CONTROLS
subsequent resets to factory defaults if the switch is left at position 1.
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
The unit must be electrically grounded in accordance with local codes and NEC ANSI/NFPA 70 (American National Standards Institute/National Fire Protection Association.)
Use the Carrier network communication software to start up and configure the PremierLink controller.
Changes can be made using the ComfortWORKSr software, ComfortVIEWt software, Network Service
48TC
Tool, System Pilott device, or Touch Pilott device. The System Pilot and Touch Pilot are portable interface devices that allow the user to change system set--up and setpoints from a zone sensor or terminal control module. During start--up, the Carrier software can also be used to verify communication with PremierLink controller.
NOTE: All set--up and setpoint configurations are factory set and field--adjustable.
For specific operating instructions, refer to the literature provided with user interface software.
Perform System Check--Out
1. Check correctness and tightness of all power and communication connections.
2. At the unit, check fan and system controls for proper operation.
3. At the unit, check electrical system and connections of any optional electric reheat coil.
4. Check to be sure the area around the unit is clear of construction dirt and debris.
5. Check that final filters are installed in the unit. Dust and debris can adversely affect system operation.
6. Verify that the PremierLink controls are properly con­nected to the CCN bus.
Initial Operation and Test
Perform the following procedure:
1. Apply 24 vac power to the control.
2. Connect the service tool to the phone jack service port of the controller.
3. Using the Service Tool, upload the controller from address 0, 31 at 9600 baud rate. The address may be set at this time. Make sure that Service Tool is con­nected to only one unit when changing the address.
Memory
DIP switch 4 causes an E--squared memory reset to factory defaults after the switch has been moved from position 0 to position 1 and the power has been restored. To enable the feature again, the switch must be put back to the 0 position and power must be restored; this prevents
Reset
To cause a reset of the non--volatile memory (to factory defaults), turn the controller power off if it is on, move the switch from position 1 to position 0, and then apply power to the controller for a minimum of 5 seconds. At this point, no action occurs, but the controller is now ready for the memory to reset. Remove power to the controller again and move the switch from position 0 to position 1. This time, when power is applied, the memory will reset to factory defaults. The controller address will return to bus 0 element 31, indicating that memory reset occurred.
Refer to Installation Instruction 33CS--58SI for full discussion on configuring the PremierLink control system.
START--UP, RTU--MP CONTROL
Field Service Test, explained below, will assist in proper start--up. Configuration of unit parameters, scheduling options, and operation are also discussed in this section.
Field Service Test
The Field Service Test function can be used to verify proper operation of compressors, heating stages, indoor fan, power exhaust fans, economizer, and dehumidification. Use of Field Service Test is recommended at initial system start up and during troubleshooting. See Form 48--50H--T--2T, Appendix A for Field Service Test Mode table.
Field Service Test mode has the following changes from normal operation:
S Outdoor air temperature limits for cooling circuits,
economizer, and heating are ignored.
S Normal compressor time guards and other staging delays
are ignored.
S The status of Alarms (except Fire and Safety chain) is
ignored but all alerts and alarms are still broadcasted on the network.
Field Service Test can be turned ON/OFF at the unit display or from the network. Once turned ON, other entries may be made with the display or through the network. To turn Field Service Test on, change the value of Test Mode to ON, to turn Field Service Test off, change the value of Test Mode to OFF.
NOTE: Service Test mode is password protected when accessing from the display. Depending on the unit model, factory--installed options, and field--installed accessories, some of the Field Service Test functions may not apply.
The independent outputs (IndpOutputs) submenu is used to change output status for the supply fan, economizer, and Power Exhaust. These independent outputs can operate simultaneously with other Field Service Test modes. All outputs return to normal operation when Field Service Test is turned off.
The Cooling submenu is used to change output status for the individual compressors and the dehumidification relay. Compressor starts are not staggered. The fans and heating service test outputs are reset to OFF for the cooling service test. Indoor fans and outdoor fans are controlled
68
normally to maintain proper unit operation. All normal cooling alarms and alerts are functional.
NOTE: Circuit A is always operated with Circuit B due to outdoor fan control on Circuit A. Always test Circuit A first, and leave it on to test other Circuits.
The Heating submenu is used to change output status for the individual heat stages, gas or electric. The fans and cooling service test outputs are reset to OFF for the heating service test. All normal heating alarms and alerts are functional.
Configuration
The RTU--MP controller configuration points affect the unit operation and/or control. Review and understand the meaning and purpose of each configuration point before changing it from the factory default value. The submenus containing configuration points are as follows: Unit, Cooling, Heating, Inputs, Economizer, IAQ, Clock--Set, and User Password (USERPW). Each configuration point is described below under its according submenu. See Form 48--50H--T--2T, Appendix for display tables.
Unit
Start Delay
This refers to the time delay the unit will wait after power up before it pursues any specific operation.
Factory Default = 5 sec Range = 0--600 sec
Filter Service Hours
This refers to the timer set for the Dirty Filter Alarm. After the number of runtime hours set on this point is exceeded the corresponding alarm will be generated, and must be manually cleared on the alarm reset screen after the maintenance has been completed. The timer will then begin counting its runtime again for the next maintenance interval.
Factory Default = 600 hr
NOTE: Setting this configuration timer to 0, disables the alarm.
Supply Fan Service Hours
This refers to the timer set for the Supply Fan Runtime Alarm. After the number of runtime hours set on this point is exceeded the corresponding alarm will be generated, and must be manually cleared on the alarm reset screen after the maintenance has been completed. The timer will then begin counting its runtime again for the next maintenance interval.
Factory Default = 0 hr
NOTE: Setting this configuration timer to 0, disables the alarm.
Compressor1 Service Hours
This refers to the timer set for the Compressor 1 Runtime Alarm. After the number of runtime hours set on this point is exceeded the corresponding alarm will be generated, and must be manually cleared on the alarm reset screen after the maintenance has been completed. The timer will then begin counting its runtime again for the next maintenance interval.
Factory Default = 0 hr
NOTE: Setting this configuration timer to 0, disables the alarm.
Compressor2 Service Hours
This refers to the timer set for the Compressor 2 Runtime Alarm. After the number of hours set on this point is exceeded the corresponding alarm will be generated, and must be manually cleared on the alarm rest screen after the maintenance has been completed. The timer will then begin counting its runtime again for the next maintenance interval
Factory Default = 0 hr
NOTE: Setting this configuration timer to 0, disables the alarm.
Cooling
Number of Compressor Stages
This refers to the number of mechanical cooling stages available on a specific unit. Set this point to “One Stage” if there is one compressor in the specific unit, set to “Two Stage” if there are two compressors in the unit, and set to “None” if economizer cooling ONLY is desired.
Factory Default = One Stage for 1 compressor units Two Stage for 2 compressor units
Cooling/Econ SAT Low Setpt
The supply air temperature must remain above this value to allow cooling with the economizer and/or compressors. There is 5_F plus and minus deadband to this point. If the SAT falls below this value during cooling, all compressors will be staged off. The economizer will start to ramp down to minimum position when the SAT = this configuration +5_F.
Factory Default = 50_F Range = 45--75_F
Cooling Lockout Temp
This defines the minimum outdoor air temperature that cooling mode can be enabled and run. If the OAT falls below this threshold during cooling, then compressor cooling will not be allowed.
Factory Default = 45_F Range = 0--65_F
Heating
Heating SAT High Setpt
The supply air temperature must remain below this value to allow heating. There is 5_F plus and minus deadband to this point. If the SAT rises above this value during heating the heat stages will begin to decrease until the SAT has dropped below this value.
Factory Default = 120_F Range = 95--150_F
Heating Lockout Temp
This defines the maximum outdoor air temperature that heating mode can be enabled and run. If the OAT rises above this threshold during heating, then heating will not be allowed.
Factory Default = 65_F Range = 49--95_F
48TC
69
Inputs NOTE: For installation of inputs and field installed
accessories, refer to the appropriate sections.
Input 3
This input is a discrete input and can be configured to be one of five different inputs: No Function, Compressor Safety, Fan Status, Filter Status, or Remote Occupancy. This input can also be configured to be either Normally Open (N/O) or Normally Closed (N/C). Input 3 is factory wired to pin J1--2. Field accessories get wired to its parallel pin J5--5. Do not connect inputs to both locations, one function per input.
Factory Default = Compressor Safety and N/O
NOTE: Compressor Safety input comes from the CLO board. J1--2 is always factory wired to TB1--8 (X) terminal on the unit. If the unit has a CLO board, do not configure input 3 for anything but Compressor Safety.
48TC
Input 5
This input is a discrete input and can be configured to be one of five different inputs: No Function, Fire Shutdown, Fan Status, Filter Status, or Remote Occupancy. This input can also be configured to be either Normally Open (N/O) or Normally Closed (N/C). Input 5 is factory wired to pin J1--10. Field accessories get wired to its parallel pin J5--3. Do not connect inputs to both locations, one function per input.
Factory Default = Fire Shutdown and N/C
NOTE: Fire Shutdown input comes from TB4--7. J1--10 is always factory wired to TB4--7. Only change input 5s function if absolutely needed.
Input 8
This input is a discrete input and can be configured to be one of five different inputs: No Function, Enthalpy Switch, Fan Status, Filter Status, or Remote Occupancy. This input can also be configured to be either Normally Open (N/O) or Normally Closed (N/C). Input 8 is factory wired to pin J2--6. Field accessories get wired to its parallel pin J5--1. Do not connect inputs to both locations, one function per input.
Factory Default = No Function and N/O
Input 9
This input is a discrete input and can be configured to be one of five different inputs: No Function, Humidistat, Fan Status, Filter Status, or Remote Occupancy. This input can also be configured to be either Normally Open (N/O) or Normally Closed (N/C). Input 9 is factory and field wired to pin J5--7. Do not connect inputs to both locations, one function per input.
Factory Default = Humidistat and N/O
Space Sensor Type
This tells the controller what type of space sensor is installed to run the unit. The three types that can be used are the T55 space sensor, the T56 space sensor, or the RS space sensor.
Factory Default = T55 Type
Input 1 Function
This input is an analog input and can be configured to be one of five different inputs: No Sensor, IAQ Sensor, OAQ Sensor, Space RH Sensor, or Outdoor RH Sensor. Input 1 iswiredtopinJ4--5.
Factory Default = No Sensor
Input 2 Function
This input is an analog input and can be configured to be one of five different inputs: No Sensor, IAQ Sensor, OAQ Sensor, Space RH Sensor, or Outdoor RH Sensor. Input 2 iswiredtopinJ4--2.
Factory Default = No Sensor
Setpoint Slider Range
This sets the slider range of the space sensor (with this built in function). The slider is used to offset the current control setpoint.
Factory Default = 5 n_F Range = 0--15 n_F
T55/56 Override Duration
This sets the occupancy override duration when the override button is pushed on the space sensor.
Factory Default = 1 hr Range = 0--24 hr
IAQ Low Reference @ 4mA
This is used when an IAQ sensor is installed on Input 1 or
2. This value is displayed and used when 4mA is seen at the input.
Factory Default = 0 PPM Range = 0--400 PPM
IAQ High Reference @ 20mA
This is used when an IAQ sensor is installed on Input 1 or
2. This value is displayed and used when 20mA is seen at the input.
Factory Default = 2000 PPM Range = 0--5000 PPM
NOTE: IAQ low Reference @ 4mA and IAQ High Reference @ 20mA are used to set the linear curve of mA vs. PPM.
OAQ Low Reference @ 4mA
This is used when an OAQ sensor is installed on Input 1 or 2. This value is displayed and used when 4mA is seen at the input.
Factory Default = 0 PPM Range = 0--400 PPM
OAQ High Reference @ 20mA
This is used when an OAQ sensor is installed on Input 1 or 2. This value is displayed and used when 20mA is seen at the input.
Factory Default = 2000 PPM Range = 0--5000 PPM
NOTE: OAQ low Reference @ 4mA and OAQ High Reference @ 20mA are used to set the linear curve of mA vs. PPM.
70
Economizer
Economizer Exists
This point tells the controller if there is an economizer installed on the unit.
Factory Default = NO if no economizer YES if there is an economizer installed
Economizer Minimum Position
This defines the lowest economizer position when the indoor fan is running and the building is occupied.
Factory Default = 20% Range = 0--100 %
Economizer High OAT Lockout
If the outdoor air temperature rises above this value, economizer cooling will be disabled and dampers will return and stay at minimum position.
Factory Default = 75_F Range = 55--80_F
Power Exhaust Setpt
When the economizer damper position opens above this point the power exhaust operation will begin. When the damper position falls 10% below the setpoint, the power exhaust will shutdown.
Factory Default = 50% Range = 20--90 %
NOTE: This point is only used when Continuous Occ Exhaust = NO
Continuous Occ Exhaust
This point tells the controller when to run the power exhaust if equipped on the unit. If set to YES, the power exhaust will be on all the time when in occupied mode and will be off when in unoccupied mode. If set to NO the power exhaust will be controlled by the Power Exhaust Setpoint.
Factory Default = NO
IAQ
Max Differential CO
If the difference between indoor an outdoor air quality becomes greater then this value the damper position will stay at the IAQ Greatest Min Dmpr Pos. configuration point
Factory Default = 650 PPM Range = 300--950 PPM
IAQ Greatest Min Dmpr Pos.
This is the greatest minimum position the economizer will open to while trying to control the indoor air quality, CO differential.
Factory Default = 50% open Range = 10--60% open
Clockset
This submenu screen allows you to set the date and time manually. The Daylight Savings Time (DST) can also be changed here. The date and time is automatically set when ever software is downloaded. The clock is a 24 hour clock and not am/pm. The time should be verified (and maybe changed) according to unit location and time zone.
Factory Default = Eastern Standard Time
Setpt
2
USERPW
This submenu screen allows you to change the user password to a four number password of choice. The User password change screen is only accessible with the Administrator Password (1111). The ADMIN password will always override the user password.
OPERATING SEQUENCES
Base Unit Controls
Cooling, Units Without Economizer
When thermostat calls for cooling, terminals G and Y1 are energized. The indoor--fan contactor (IFC) and compressor contactor are energized and indoor--fan motor, compressor, and outdoor fan starts. The outdoor fan motor runs continuously while unit is cooling.
Heating, Units Without Economizer
When the thermostat calls for heating, terminal W1 is energized. To prevent thermostat short--cycling, the unit is locked into the Heating mode for at least 1 minute when W1 is energized. The induced--draft motor is energized and the burner ignition sequence begins. The indoor (evaporator) fan motor (IFM) is energized 45 seconds after a flame is ignited. On units equipped for two stages of heat, when additional heat is needed, W2 is energized and the high--fire solenoid on the main gas valve (MGV) is energized. When the thermostat is satisfied and W1 is deenergized, the IFM stops after a 45--second time off delay.
Cooling, Unit With EconoMi$er IV
For Occupied mode operation of EconoMi$er IV, there must be a 24--v signal at terminals TR and N (provided through PL6--3 from the unit’s IFC coil). Removing the signal at N places the EconoMi$er IV control in Unoccupied mode.
During Occupied mode operation, indoor fan operation will be accompanied by economizer dampers moving to Minimum Position setpoint for ventilation. If indoor fan is off, dampers will close. During Unoccupied mode operation, dampers will remain closed unless a Cooling (by free cooling) or DCV demand is received.
Integrated EconoMi$er IV operation on 48TC single compressor model requires a 2--stage thermostat (Y1 and Y2 switches).
When free cooling using outside air is not available, the
2
unit cooling sequence will be controlled directly by the space thermostat as described above as Cooling, Without Economizer. Outside air damper position will be closed or Minimum Position as determined by occupancy mode and fan signal.
When free cooling is available as determined by the appropriate changeover command (dry bulb, outdoor enthalpy, differential dry bulb or differential enthalpy), a call for cooling (Y1 closes at the thermostat) will cause the economizer control to modulate the dampers open and closed to maintain the unit supply air temperature at 50 to 55_F. Compressor will not run.
48TC
71
During free cooling operation, a supply air temperature (SAT) above 50_F will cause the dampers to modulate between Minimum Position setpoint and 100% open. With SAT from 50_Fto45_F, the dampers will maintain at the Minimum Position setting. With SAT below 45_F, t he outside air dampers will be closed. When SAT rises to 48_F, the dampers will re--open to Minimum Position setting.
Should 100% outside air not be capable of satisfying the space temperature, space temperature will rise until Y2 is closed. The economizer control will call for compressor operation. Dampers will modulate to maintain SAT at 50 to 55_F concurrent with compressor operation. The Low Ambient Lockout Thermostat will block compressor operation with economizer operation below 42_F outside air temperature.
When space temperature demand is satisfied (thermostat
48TC
Y1 opens), the dampers will return to Minimum Damper position if indoor fan is running or fully closed if fan is off.
If accessory power exhaust is installed, the power exhaust fan motors will be energized by the economizer control as the dampers open above the PE--On setpoint and will be de--energized as the dampers close below the PE--On setpoint.
Damper movement from full closed to full open (or vice versa) will take between 1--1/2 and 2--1/2 minutes.
Heating With EconoMi$er IV
During Occupied mode operation, indoor fan operation will be accompanied by economizer dampers moving to Minimum Position setpoint for ventilation. If indoor fan is off, dampers will close. During Unoccupied mode operation, dampers will remain closed unless a DCV demand is received.
When the room temperature calls for heat (W1 closes), the heating controls are energized as described in Heating, Unit Without Economizer above.
PremierLink Control
THERMOSTAT MODE — If the PremierLink controller is configured for Thermostat mode (TSTAT), it will control only to the thermostat inputs on J4. These inputs can be overridden through CCN communication via the CV_TSTAT points display table. When in this mode, the fire safety shutdown (FSD) input cannot be used, so any fire/life safety shutdown must be physically wired to disable the 24 vac control circuit to the unit.
Indoor Fan — The indoor fan output will be energized whenever there is 24 vac present on the G input. The indoor fan will be turned on without any delay and the economizer damper will open to its minimum position if the unit has a damper connected to the controller. This will also occur if the PremierLink controller has been configured for electric heat or heat pump operation.
Cooling — For cooling operation, there must be 24 vac present on G. When G is active, the PremierLink controller will then determine if outdoor conditions are
suitable for economizer cooling when an economizer damper is available. A valid OAT, SPT (CCN space temperature) and SAT (supply air temperature) sensor MUST be installed for proper economizer operation. It recommended that an outdoor or differential enthalpy sensor also be installed. If one is not present, then a jumper is needed on the ENTH input on J4, which will indicate that the enthalpy will always be low. Economizer operation will be based only on outdoor air dry bulb temperature. The conditions are suitable when: enthalpy is low, OAT is less than OATL High Lockout for TSTAT, and OAT is less than OATMAX, the high setpoint for free cooling. The default for OATL is 65_F. The default for OATMAX is 75_F.
When all of the above conditions are satisfied and all the required sensors are installed, the PremierLink controller will use the economizer for cooling. One of three different control routines will be used depending on the temperature of the outside air. The routines use a PID loop to control the SAT to a supply air setpoint (SASP) based on the error from setpoint (SASPSAT). The SASP is determined by the routine.
If an economizer is not available or the conditions are not met for the following economizer routines below, the compressors 1 and 2 will be cycled based on Y1 and Y2 inputs respectively.
Any time the compressors are running, the PremierLink controller will lock out the compressors if the SAT becomes too low. These user configurable settings are found in the SERVICE configuration table:
Compressor 1 Lockout at SAT < SATLO1 (50 to 65_F) (default is 55_F)
Compressor 2 Lockout at SAT < SATLO2 (45 to 55_F) (default is 50_F)
After a compressor is locked out, it may be started again after a normal time--guard period and the supply--air temperature has increased at least 8_F above the lockout setpoint.
Routine No. 1: If the OAT DXLOCK (OAT DX lockout temperature) and DX Cooling Lockout is enabled when Y1 input is energized, the economizer will be modulated to maintain SAT at the Supply Air Setpoint (SASP) = SATLO1 + 3_F (Supply Air Low Temp lockout for compressor 1). When Y2 is energized, the economizer will be modulated to control to a lower SASP = SATLO2 +3_F (Supply Air Low Temp lockout for compressor no.
2). Mechanical cooling is locked out and will not be energized.
Routine No. 2: If DXLOCK (or DX Cooling Lockout is disabled) < OAT 68_F when Y1 input is energized, the economizer will be modulated to maintain SAT at SASP = SATLO1 + 3_F. If t he SAT > SASP + 5_F and the economizer position > 85% then the economizer will close the to minimum position for three minutes or until the SAT > 68_F. The economizer integrator will then be reset and begin modulating to maintain the SASP after stage one has been energized for 90 seconds.
72
When Y2 is energized, the economizer will be modulated to control to a lower supply air setpoint SASP= SATLO2 +3_F If the SAT > SASP + 5_F it will close the economizer to minimum position for 3 minutes, reset the integrator for the economizer, then start modulating the economizer to maintain the SASP after the stage two has been on for 90 seconds. This provides protection for the compressor against flooded starts and allow refrigerant flow to stabilize before modulating the economizer again. By using return air across the evaporator coil just after the compressor has started allows for increased refrigerant flow rates providing better oil return of any oil washed out during compressor start--up.
Routine No. 3: If the OAT > 68_F and the enthalpy is low and the OAT < SPT then the economizer will open to 100% and compressors 1 and 2 will be cycled based on Y1 and Y2 inputs respectively. If any of these conditions are not met the economizer will go to minimum position.
If there is no call for heating or cooling, the economizer, if available, will maintain the SASP at 70_F.
Heating — For gas or electric heat, HS1 and HS2 outputs will follow W1 and W2 inputs respectively. The fan will also be turned on if it is configured for electric heat.
Heating may also be energized when an IAQ sensor installed and has overridden the minimum economizer damper position. If the OAT < 55_F and an IAQ sensor is installed and the IAQ minimum position > minimum damper position causing the SAT to decrease below the SPT -- 10_F, then the heat stages will be cycled to temper the SAT to maintain a temperature between the SPT and the SPT + 10_F.
Auxiliary Relay configured for Exhaust Fan — If the Auxiliary Relay is configured for exhaust fan (AUXOUT = 1) in the CONFIG configuration table and Continuous Power Exhaust (MODPE) is enable in the SERVICE configuration table then the output (HS3) will be energized whenever the G input is on. If the MODPE is disabled then output will be energized based on the Power Exhaust Setpoint (PES) in the SETPOINT table.
Indoor Air Quality — If the optional indoor air quality (IAQI) sensor is installed, the PremierLink controller will maintain indoor air quality within the space at the user--configured differential setpoint (IAQD) in the CONFIG configuration table. The setpoint is the difference between the IAQI and an optional outdoor air quality sensor (OAQ). If the OAQ is not present then a fixed value of 400 ppm is used. The actual space IAQ setpoint (IAQS) is calculated as follows:
IAQS = IAQD + OAQ (OAQ = 400 ppm if not present)
As air quality within the space changes, the minimum position of the economizer damper will be changed also thus allowing more or less outdoor air into the space depending on the relationship of the IAQI to the IAQS. The IAQ algorithm runs every 30 seconds and calculates IAQ minimum position value using a PID loop on the IAQI deviation from the IAQS. The IAQ minimum position is then compared against the user configured
minimum position (MDP) and the greatest value becomes the final minimum damper position (IQMP). If the calculated IAQ Minimum Position is greater than the IAQ maximum damper position (IAQMAXP) decision in the SERVICE configuration table, then it will be clamped to IAQMAXP value.
If IAQ is configured for low priority, the positioning of the economizer damper can be overridden by comfort requirements. If the SAT < SASP --8_F and both stages of heat are on for more then 4 minutes or the SAT > SASP + 5_F and both stages of cooling on for more then 4 minutes then the IAQ minimum damper position will become 0 and the IQMP = MDP. IAQ mode will resume when the SAT > SASP --8_F in heating or the SAT < SASP + 5_Fin cooling.
If the PremierLink controller is configured for 1 stage of heat and cool or is only using a single stage thermostat input, this function will not work as it requires the both Y1 and Y2 or W1 and W2 inputs to be active. In this application, it is recommended that the user configure IAQ priority for high.
If IAQ is configured for high priority and the OAT < 55_F and the SAT < (SPT --10_F), the algorithm will enable the heat stages to maintain the SAT between the SPT and the SPT + 10_F.
CCN SENSOR MODE — When the PremierLink controller is configured for CCN control, it will control the compressor, economizer and heating outputs based its own space temperature input and setpoints or those received from Linkage. An optional CO
IAQ sensor
2
mounted in the space or received through communications can also influence the economizer and heating outputs. The PremierLink controller does not have a hardware clock so it must have another device on the CCN communication bus broadcasting time. The controller will maintain its own time once it has received time as long as it has power and will send a request for time once a minute until it receives time when it has lost power and power is restored. The controller will control to unoccupied setpoints until it has received a valid time. The controller must have valid time in order to perform any broadcast function, follow an occupancy schedule, perform IAQ pre--occupancy purge and many other functions as well. The following sections describe the operation for the functions of the PremierLink controller.
Indoor Fan — The indoor fan will be turned on whenever any one of the following conditions are met:
S If the PremierLink controller is in the occupied mode and
ASHRAE 90.1 Supply Fan is configured for Yes in the CONFIG table. This will be determined by its own internal occupancy schedule if it is programmed to follow its local schedule or broadcast its local schedule as a global schedule, or following a global schedule broadcast by another device.
S If PremierLink controller is in the occupied mode and
ASHRAE 90.1 Supply Fan is configured for No and there is a heat or cool demand (fan auto mode)
48TC
73
S If the PremierLink controller is in the occupied mode and
ASHRAE 90.1 Supply Fan is configured for Yes when Linkage is active and the Linkage Coordinator device is sending an occupied mode flag
S When Temperature Compensated Start is active S When Free Cool is active S When Pre--Occupancy Purge is active S Whenever there is a demand for cooling or heating in the
unoccupied mode
S Whenever the Remote Contact input is configured for
Remote Contact (RC_DC=1 in SERVICE table) and it is closed or the point is forced Closed via communications in the STATUS01 points display table (remote contact closed = occupied, remote contact open = unoccupied)
S Whenever the H3_EX_RV point is configured for
Dehumidification (AUXOUT=5 in CONFIG table) and it
48TC
is in the unoccupied mode and the indoor RH exceeds the unoccupied humidity setpoint
S Whenever the Supply Fan Relay point is forced On in the
STATUS01 points display table
The fan will also continue to run as long as compressors are on when transitioning from occupied to unoccupied with the exception of Fire Shutdown mode. If the Fire Shutdown input point is closed or forced in the STATUS01 points display table, the fan will be shutdown immediately regardless of the occupancy state or demand.
The PremierLink controller has an optional Supply Fan Status input to provide proof of airflow. If this is enabled, the point will look for a contact closure whenever the Supply Fan Relay is on. If the input is not enabled, then it will always be the same state as the Supply Fan Relay. The cooling, economizer and heating routines will use this input point for fan status.
Cooling — The compressors are controlled by the Cooling Control Loop that is used to calculate the desired SAT needed to satisfy the space. It will compare the SPT to the Occupied Cool Setpoint (OCSP) + the T56 slider offset (STO) when occupied and the Unoccupied Cool Setpoint (UCSP + Unoccupied Cooling Deadband) if unoccupied to calculate a Cooling Submaster Reference (CCSR) that is then used by the staging algorithm (Cooling submaster loop) to calculate the required number of cooling stages. The economizer, if available, will be used as the first stage of cooling in addition to the compressors. This loop runs every minute. The following conditions must be met in order for this algorithm to run:
S indoor fan has been ON for at least 30 seconds S heat mode is not active and the time guard between
modes equals zero.
S mode is occupied or the Temperature Compensated Start
or Cool mode is active
S SPT reading is available and > (OCSP + STO) S If mode is unoccupied and the SPT > (UCSP +
Unoccupied Cooling Deadband). The indoor fan will be turned on by the staging algorithm.
S OAT > DXLOCK or OAT DX Lockout is disabled
If all of the above conditions are met, the CCSR will be calculated, otherwise it is set to its maximum value and DX stages is set to 0. If only the last condition is not true and an economizer is available, it will be used to cool the space.
The submaster loop uses the CCSR compared to the actual SAT to determine the required number of capacity stages to satisfy the load. There is a programmable minimum internal time delay of 3 to 5 minutes on and 2 to 5 minutes off for the compressors to prevent short cycling. There is also a 3--minute time delay before bringing on the second stage compressor. If the PremierLink controller is configured for Heat Pump and AUXOUT is configured for Reversing Valve Cool, the H3_EX_RV output will energize 2 seconds after the first compressor is energized and stay energized until there is a demand for heat. If AUXOUT is configured for Reversing Valve Heat, then the H3_EX_RV contact will be deenergized when there is a demand for cooling. An internal 5 to 10--minute user--programmable time guard between modes prevents rapid cycling between modes when used in a single zone application. The Time Guard is lowered to 3 minutes when Linkage is active to allow the 3Vt linkage coordinator to have better control of the PremierLink controller when used as the air source for the 3V control system.
Table 29 indicates the number of stages available. The staging algorithm looks at the number of stages available based the number of cool stages configured in the SERVICE configuration table. The algorithm will skip the economizer if it is not available and turn on a compressor.
Table 29 – Available Cooling Stages
NUMBER OF
STAGES
Compressor 1 Off Off On On Compressor 2 Off Off Off On
* If conditions are suitable for economizer operation.
0
(ECONOMIZER*)
1
2 3
Any time the compressors are running, the PremierLink controller will lockout the compressors if the SAT becomes too low. These user configurable settings are found in the SERVICE configuration table:
Compressor 1 Lockout at SAT < SATLO1 (50 to 65_F) (default is 55_F)
Compressor 2 Lockout at SAT < SATLO2 (45 to 55_F) (default is 50_F)
After a compressor is locked out, it may be started again after a normal time--guard period and the supply air temperature has increased at least 8_F above the lockout setpoint.
Dehumidification — The PremierLink controller will provide occupied and unoccupied dehumidification control when AUXOUT = 5 in the CONFIG table and is installed on HVAC units that are equipped with additional controls and accessories to accomplish this function. This function also requires a space relative humidity sensor be installed on the OAQ/IRH input.
74
When in the occupied mode and the indoor relative humidity is greater then the Occupied High Humidity setpoint, then the H3_EX_RV output point will be energized. When in the unoccupied mode and indoor relative humidity is greater then the Unoccupied High Humidity setpoint, then the H3_EX_RV output point and supply fan output will be energized. There is a fixed 5% hysteresis that the indoor relative humidity must drop below the active setpoint to end the dehumidification mode and deenergize the H3_EX_RV output. If the PremierLink controller is in the unoccupied mode, then the fan relay will deenergize if there is no other mode requiring to the fan to be on. This function will not energize mechanical cooling as a result of the indoor relative humidity exceeding either setpoint.
A high humidity alarm will be generated if the indoor relative humidity exceeds the high humidity setpoint by the amount configured in the Control Humidity Hysteresis in the ALARMS table for 20 minutes. The alarm will return to normal when the indoor relative humidity drops 3% below the active humidity setpoint.
Economizer — The economizer dampers are used to provide free cooling and indoor air quality if optional CO sensor is installed and when the outside conditions are suitable. Temperature control is accomplished by controlling the SAT to a certain level determined by the Economizer PID Loop by calculating a submaster reference (ECONSR) value. This algorithm will calculate the submaster reference temperature (ECONSR) based on OAT and enthalpy conditions and cooling requirements. The ECONSR value is then passed to the Economizer Submaster Loop, which will modulate dampers to maintain SAT at ECONSR level.
The actual damper position (ECONPOS) is the result of the following calculation. Values represented in the right side of the equation can be found in the SERVICE configuration table descriptions in this manual. Note that that the OAT is taken into consideration to avoid large changes in damper position when the OAT is cold:
ECONPOS = SubGain x (ECONSR--SAT) + CTRVAL where SubGain = (OAT -- TEMPBAND) / (ESG + 1)
If the OAT < DXLOCK (DX Cool Lockout setpoint) then the damper will be modulated to maintain the SAT at the ECONSR value.
If the OAT is between DXLOCK and 68_F (DXLOCK < OAT < 68_F) and additional cooling is required, the economizer will close the to minimum position for three minutes, the economizer integrator will then be reset to 0 and begin modulating to maintain the SASP after the stage has been energized for about 90 seconds. This will allow the economizer to calculate a new ECONSR that takes into account the cooling effect that has just been turned on and not return to the value require before the cooling was added. This will prevent the economizer from causing premature off cycles of compressors while maintaining the
2
low SAT temperature setpoint for the number of stages active. In addition to preventing compressor short cycling, by using return air across the evaporator coil just after the compressor has started allows for increased refrigerant flow rates providing for better oil return of any oil washed out during compressor start--up.
If the OAT > 68_F and OAT < SPT and the number of DX stages requested is > 0 by the staging algorithm, then ECONSR is set to its minimum value 48_F and the damper will go to 100% open.
48TC
The following conditions are required to determine if economizer cooling is possible:
S Indoor fan has been on for at least 30 seconds S Enthalpy is low S SAT reading is available S OAT reading is available S SPT reading is available S OAT SPT S OAT < OATMAX (OATMAX default is 75_F) S Economizer position is NOT forced
If any of the above conditions are not met, the ECONSR will be set to its MAX limit of 120_F and the damper will go to its configured minimum position. The minimum damper position can be overridden by the IAQ routine described later in this section.
The calculation for ECONSR is as follows:
ECONSR = PID function on (setpoint -- SPT), where: setpoint = ((OCSP+STO) + (OHSP+STO))/2 when
NTLO (Unoccupied Free Cool OAT Lockout) < OAT < 68_F
setpoint = (OCSP+STO) -- 1 when OAT NTLO setpoint = (OHSP+STO) + 1 when OAT ≥ 68_F
If the Auxiliary Relay is configured for exhaust fan (AUXOUT = 1) in the CONFIG configuration table and Continuous Power Exhaust (MODPE) is Enable in the SERVICE configuration table, then the AUXO output (HS3) will be energized whenever the PremierLink controller is in the occupied mode. If the MODPE is disabled then AUXO output will be energized based on the Power Exhaust Setpoint (PES) in the SETPOINT table.
Heating — The heat stages are controlled by the Heating Control Loop, which is used to calculate the desired SAT needed to satisfy the space. It will compare the SPT to the Occupied Heat Setpoint (OHSP) + the T56 slider offset (STO) when occupied and the Unoccupied Heat Setpoint (UHSP -- Unoccupied Heating Deadband) if unoccupied to calculate a Staged Heat Submaster Reference (SHSR). The heat staging algorithm compares the SHSR to the actual SAT to calculate the required number of heating stages to satisfy the load. This loop runs every 40 seconds. The following conditions must be met in order for this algorithm to run:
S Indoor fan has been ON for at least 30 seconds. S Cool mode is not active and the time guard between
modes equals zero.
S Mode is occupied or the Temperature Compensated Start
or Heat mode is active.
75
S SPT reading is available and < (OHSP + STO). S If it is unoccupied and the SPT < (UHSP -- Unoccupied
Heating Deadband). The indoor fan will be turn on by the staging algorithm.
When all of the above conditions are met, the SHSR is calculated and up to 3 stages of heat will turned on and off to satisfy to maintain the SAT = SHSR. If any of the above conditions are not met, the SHSR is set to its minimum value of 35_F.
The Staged Heat Submaster Reference (SHSR) is calculated as follows:
SHSR = Heating PID function on (error) where error = (OHSP + STO) -- Space Temperature
The Maximum SHSR is determined by the SATHI configuration. If the supply--air temperature exceeds the SATHI configuration value, then the heat stages will turn
48TC
off. Heat staging will resume after a delay to allow the supply--air temperature to drop below the SATHI value.
The maximum number of stages available is dependent on the type of heat and the number of stages programmed in the CONFIG and SERVICE configuration tables. Staging will occur as follows for gas electric units, Carrier heat pumps with a defrost board, or cooling units with electric heat:
For Heating PID STAGES = 2
HEAT STAGES = 1 (50% capacity) -- energize HS1. HEAT STAGES = 2 (100% capacity) -- energize HS2.
For Heating PID STAGES = 3 and AUXOUT = HS3
HEAT STAGES = 1 (33% capacity if) -- energize HS1 HEAT STAGES = 2 (66% capacity) -- energize HS2 HEAT STAGES = 3 (100% capacity) -- energize HS3
Staging will occur as follows For heat pump units with AUXOUT configured as reversing valve:
For Heating PID STAGES = 2 and AUXOUT = Reversing Valve Heat (the H3_EX_RV output will stay energized until there is a cool demand) HEAT STAGES = 1 (50% capacity) shall energize CMP1, CMP2, RVS.
HEAT STAGES = 2 (100% capacity) shall energize HS1 and HS2.
Heating PID STAGES = 3 and AUXOUT = Reversing Valve Heat (the H3_EX_RV output will stay energized until there is a cool demand)
S an IAQ sensor is installed S the IAQ Minimum Damper Position > minimum damper
position
S and the SAT < SPT --10_F.
There is also a SAT tempering routine that will act as SAT low limit safety to prevent the SAT from becoming too cold should the economizer fail to close. One stage of heating will be energized if it is not in the Cooling or Free Cooling mode and the OAT is below 55_F and the SAT is below 40_F. It will deenergize when the SAT > (SPT + 10_F).
Indoor Air Quality — If the optional indoor air quality (IAQI) sensor is installed, the PremierLink controller will maintain indoor air quality within the space at the user configured differential setpoint (IAQD) in the CONFIG configuration table. The setpoint is the difference between the IAQI and an optional outdoor air quality sensor (OAQ). If the OAQ is not present then a fixed value of 400 ppm is used. The actual space IAQ setpoint (IAQS) is calculated as follows:
IAQS = IAQD + OAQ (OAQ = 400 ppm if not present)
As air quality within the space changes, the minimum position of the economizer damper will be changed also thus allowing more or less outdoor air into the space depending on the relationship of the IAQI to the IAQS. The IAQ algorithm runs every 30 seconds and calculates IAQ minimum position value using a PID loop on the IAQI deviation from the IAQS. The IAQ minimum position is then compared against the user configured minimum position (MDP) and the greatest value becomes the final minimum damper position (IQMP). If the calculated IAQ minimum position is greater than the IAQ maximum damper position (IAQMAXP) decision in the SERVICE configuration table, then it will be clamped to IAQMAXP value.
If IAQ is configured for low priority, the positioning of the economizer damper can be overridden by comfort requirements. If the SPT > OCSP + 2.5 or the SPT < OHSP -- 2.5 then IAQ minimum position becomes 0 and the IQMP = MDP. The IAQ mode will resume when the SPT OCSP + 1.0 and SPT OHSP -- 1.0.
If IAQ is configured for high priority and the OAT < 55_F and the SAT < (SPT -- 10_F), the algorithm will enable the heat stages to maintain the SAT between the SPT and the SPT + 10_F.
HEAT STAGES = 1 (33% capacity if) shall energize CMP1, CMP2, RVS
HEAT STAGES = 2 (66% capacity) shall energize HS1
HEAT STAGES = 3 (100% capacity) shall energize HS2
If AUXOUT is configured for Reversing Valve Cool, then the H3_EX_RV contact will be deenergized when there is a demand for heating. The heat stages will be cycled to temper the SAT so that it will be between the SPT and the SPT + 10_F (SPT < SAT < (SPT + 10_F)) if:
S the number of heat stages calculated is zero S the OAT < 55_F
IAQ Pre--Occupancy Purge — This function is designed to purge the space of airborne contaminants that may have accumulated 2 hours prior to the beginning of the next occupied period. The maximum damper position that will be used is temperature compensated for cold whether conditions and can be pre--empted by Temperature Compensated Start function. For pre--occupancy to occur, the following conditions must be met:
S IAQ Pre--Occupancy Purge option is enabled in the
CONFIG configuration table
S Unit is in the unoccupied state S Current Time is valid
76
S Next Occupied Time is valid S Time is within 2 hours of next Occupied period S Time is within Purge Duration (user--defined 5 to 60
minutes in the CONFIG configuration table)
S OAT Reading is available
If all of the above conditions are met, the economizer damper IQMP is temporarily overridden by the pre--occupancy damper position (PURGEMP). The PURGEMP will be set to one of the following conditions based on atmospheric conditions and the space temperature:
S If the OAT NTLO (Unoccupied OAT Lockout
Temperature) and OAT < 65_F and OAT is less than or equal to OCSP and Enthalpy = Low then PURGEMP = 100%.
S If the OAT < NTLO then PURGEMP = LTMP (Low
Temperature Minimum Position -- defaults to 10%)
S If the OAT > 65_For(OATNTLO and OAT > OCSP)
or Enthalpy = High then PURGEMP = HTMP (High Temperature Minimum Position defaults to 35%).
The LTMP and HTMP are user adjustable values from 0 to 100% in the SETPOINT table. Whenever PURGEMP results in a number greater than 0%, the IAQ pre--occupancy purge mode will be enabled turning on the Indoor Fan Relay and setting the economizer IQMP to the PURGEMP value. When IAQ pre--occupancy mode is not active PURGEMP = 0%.
Unoccupied Free Cooling — Unoccupied free cool function will start the indoor fan during unoccupied times in order to cool the space with outside air. This function is performed to delay the need for mechanical cooling when the system enters the occupied period. Depending on how Unoccupied Free Cooling is configured, unoccupied mode can occur at any time in the unoccupied time period or 2 to 6 hours prior to the next occupied time. Once the space has been sufficiently cooled during this cycle, the fan will be stopped. In order to perform unoccupied free cooling all of the following conditions must be met:
S NTEN option is enabled in the CONFIG configuration
table
S Unit is in unoccupied state S Current time of day is valid S Temperature Compensated Start mode is not active S COOL mode is not active S HEAT mode is not active S SPT reading is available S OAT reading is available S Enthalpy is low S OAT > NTLO (with 1_F hysteresis) and < Max Free Cool
setpoint
If any of the above conditions are not met, Unoccupied Free Cool mode will be stopped, otherwise, the mode will be controlled as follows:
The NTFC setpoint (NTSP) is determined as NTSP = (OCSP + OHSP) / 2
The Unoccupied Free Cool mode will be started when:
SPT > (NTSP + 2_F) and SPT > (OAT + 8_F)
The Unoccupied Free Cool mode will be stopped when:
SPT < NTSP or SPT < (OAT + 3_F)
Temperature Compensated Start — This function will run when the controller is in unoccupied state and will calculate early start bias time (SBT) based on space temperature deviation from occupied setpoints in minutes per degree. The following conditions will be met for the function to run:
S Unit is in unoccupied state S Next occupied time is valid S Current time of day is valid S Valid space temperature reading is available (from sensor
or linkage thermostat)
S Cool Start Bias (KCOOL) and Heat Bias Start (KHEAT)
> 0 in the CONFIG configuration table
The SBT is calculated by one of the following formulas depending on temperature demand:
If SPT > OCSP then SBT = (SPT -- OCSP) * KCOOL If SPT < OHSP then SPT = (OHSP -- SPT) * KHEAT.
The calculated start bias time can range from 0 to 255 minutes. When SBT is greater than 0 the function will subtract the SBT from the next occupied time to calculate a new start time. When a new start time is reached, the Temperature Compensated Start mode is started. This mode energizes the fan and the unit will operate as though it is in occupied state. Once set, Temperature Compensated Start mode will stay on until the unit returns to occupied state. If either Unoccupied Free Cool or IAQ Pre--Occupancy mode is active when Temperature Compensated Start begins, their mode will end.
Door Switch — The Door Switch function is designed to disable mechanical heating and cooling outputs when the REMOCC contact input is closed (in the ON state) after a programmed time delay. The fan will continue to operate based on the current mode and the ASHRAE 90.1 Supply Fan setting. The delay is programmable from 2 to 20 minutes by setting the Remote Cont/Door Switch decision in the SERVICE table to a value equal to the number of minutes desired. When the contact is open (in the OFF state), the PremierLink controller will resume normal temperature control.
This application is designed for use in schools or other public places where a door switch can be installed to monitor the opening of a door for an extended period of time. The controller will disable mechanical cooling and heating when the door is open for a programmed amount of time.
This function can also be used to monitor a high condensate level switch when installed on a water source heat pump to disable mechanic cooling in case of a plugged evaporator condensate pan drain. Linkage — The Linkage function in the PremierLink controller is available for applications using a Linkage thermostat or the 3V control system. If using the Linkage thermostat, both the PremierLink controller and the stat must be on the same CCN bus. When used as the air
48TC
77
source for a 3V control system, the PremierLink controller is not required to be on the same CCN bus but it is recommended. Linkage will be active when it is initiated from the Linkage thermostat or the 3V Linkage Coordinator through CCN communications and requires no configuration. Only one device can be linked to the PremierLink controller.
Once Linkage is active, the PremierLink controller’s own SPT, temperature setpoints, and occupancy are ignored and the controller will use the information provided by the remote linkage device. The following information will be received from the remote linked device and can be viewed in the maintenance display table:
S Supervisory Element S Supervisory Bus S Supervisory Block
48TC
S Average Occupied Heat Setpoint S Average Occupied Cool Setpoint S Average Unoccupied Heat Setpoint S Average Unoccupied Cool Setpoint S Average Zone Temp S Average Occupied Zone Temp S Occupancy Status
In return, the PremierLink controller will provide its SAT and operating mode to the linked device.
It will convert its operating modes to Linkage modes. See Table 30.
Table 30 – Linkage Modes
ROOFTOP MODE VALUE LINKAGE MODE
Demand Limit N/A N/A
Heat 3 Heating
Cool or Free Cooling 4 Cooling
IAQ Control N/A N/A
Temp. Co mpen s ate d
Start Heat
Temp. Co mpen s ate d
Start Cool
IAQ Purge 6 Pressurization
Occupied
(Indoor Fan ON)
Unoccupied Free
Cool
Fire Shutdown 7 Evac
Factory/Field Test 1 Off
Off 1 Off
2 Warm ---up
4 Cooling
4 Cooling
5
Unoccupied Free
Cooling
The PremierLink controller will generate a Linkage Communication Failure alarm if a failure occurs for 5 consecutive minutes once a Linkage has previously been established. It will then revert back to its own SPT, setpoints and occupancy schedule for control. For this reason, Carrier strongly recommends that an SPT be installed in the space on open plenum systems or in the return air duct of ducted return air systems to provide continued backup operation. When Linkage communication is restored, the controller will generate a return to normal.
For more information on how the PremierLink controller is used in conjunction with the Carrier 3V control system, contact your CCN controls representative.
IMPORTANT: The PremierLink controller should not be used as a linked air source in a ComfortIDt VAV system. The ComfortID VAV system will NOT function correctly when applied with a PremierLink controller as the air source, resulting in poor comfort control and possible equipment malfunction.
NOTE: The PremierLink controller can be used as an air source in a 3V Pressure Independent (PI) System (a 3V Linkage Coordinator with ComfortID PI Zone Controllers), but it should not be used as an air source with ComfortID controllers unless a 3V zone controller is used as the Linkage Coordinator. Contact your Carrier CCN controls representative for assistance.
Demand Limit — If the demand limit option is enabled, the control will receive and accept Redline Alert and Loadshed commands from the CCN loadshed controller. When a redline alert is received, the control will set the maximum stage of capacity equal to the stage of capacity that the unit is operating at when the redline alert was initiated.
When loadshed command is received the control will reduce capacity as shown in Table 31.
Table 31 – Loadshed Command — Gas and Electric
Heat Units
CURRENT CAPACITY NEW CAPACITY
CMP1 DX Cooling OFF
CMP1+CMP2 CMP1
HS1 Heat OFF
HS1+HS2 (+HS3) HS1
The controller will have a maximum demand limit timer of 1 hour that prevents the unit from staying in load shed or redline alert longer than 1 hour in the event the controller loses communication with the network load shed module. Should the maximum demand limit timer expire prior to receiving the loadshed device command from CCN, the control will stop demand limit mode and return to normal operation.
RTU-- MP Sequence of Operation
The RTU--MP will control the compressor, economizer and heating outputs based on its own space temperature input and setpoints. An optional CO in the space can influence the economizer minimum position. The RTU--MP has its own hardware clock that is set automatically when the software is installed on the board. The RTU--MP’s default is to control to occupied setpoints all the time, until a type of occupancy control is set. Occupancy types are described in the scheduling section. The following sections describe the operation for the functions of the RTU--MP. All point objects that are referred to in this sequence will be in reference to the objects as viewed in BACview
Scheduling
Scheduling is used to start heating or cooling (become occupied) based upon a day of week and a time period and
78
IAQ sensor mounted
2
6
Handheld.
control to the occupied heating or cooling setpoints. Scheduling functions are located under occupancy determination and the schedule menu accessed by the Menu softkey (see Appendix -- for menu structure). Your local time and date should be set for these functions to operate properly. Five scheduling functions are available by changing the Occupancy Source to one of the following selections:
Always Occupied (Default Occupancy)
The unit will run continuously. RTU--MP ships from the factory with this setting.
Local Schedule
The unit will operate according to the schedule configured and stored in the unit. The local schedule is made up of three hierarchy levels that consist of two Override schedules, twelve Holiday and four Daily schedules, and are only accessible by the BACview screen (handheld or virtual).
The Daily schedule is the lowest schedule in the hierarchy and is overridden by both the Holiday and Override schedule. It consists of a start time, a stop time (both in 24 hour mode) and the seven days of the week, starting with Monday and ending in Sunday. To select a daily schedule scroll to the Schedules menu off of the Menu selection. Enter the User password and change the Occupancy Source to Local Schedule. Scroll down and over to the Daily menu and press enter. Choose one of the four Daily schedules by pressing the Next softkey and change the Use? point from NO to YES by selecting the point and pressing the INCR or DECR softkey. Press the OK softkey and scroll to the start and stop times. Edit these times following the same steps as the Use? point. Finally scroll down to the Days: section and highlight the days required for the Daily schedule by INCR or DECR softkeys and press OK softkey.
The Holiday schedule is created to override the Daily schedule and identify a specific day and month of the year to start and stop the unit and change control to the unoccupied heating and cooling setpoints. Follow the same steps to turn on one of the twelve Holiday schedules and start and stop times. Next, select one out of the twelve months and one out of the thirty--one days of that month. The RTU--MP will now ignore the Daily schedule for the specific day and time you selected and follow the Holiday Schedule for this period.
The Override schedules primary purpose is to provide a temporary change in the occupied heating and cooling setpoints and force the unit to control to the unoccupied heating and cooling setpoints. This would occur on a set day in a particular month and last during the start and stop time configured. The Override schedule is enabled by following the same steps to create the Holiday schedule.
NOTE: Push button override is only available when running a local or BACnet Schedule.
BACnet Schedule
For use with a Building Automation System that supports native BACnet scheduling is scheduling the unit. With the Occupancy Source set to BACnet schedule the BAS will control the unit through network communication and it’s own scheduling function.
BAS On/Off
The Building Automation System is scheduling the unit via an On/Off command to the BAS ON/OFF software point. The Building Automation System can be speaking BACnet, Modbus, or N2 and is writing to the BAS On/Off point in the open protocol point map.
NOTE: If the BAS supports NATIVE BACnet scheduling, then set the Occupancy Source to BACnet schedule. If the BAS is BACnet but does NOT support NATIVE BACnet scheduling, then set the Occupancy Source to BAS On/Off.
DI On/Off
A hard--wired input on the RTU--MP will command the unit to start/stop. Inputs 3, 5, 8, and 9 on plug J5 can be hard--wired to command the unit to start/stop.
NOTE: Scheduling can either be controlled via the unit or the BAS, but NOT both.
Indoor
Fan
The indoor fan will be turned on whenever any one of the following conditions is true:
S It is in the occupied mode. This will be determined by its
own internal occupancy schedule.
S Whenever there is a demand for cooling or heating in the
unoccupied mode.
S Whenever the remote occupancy switch is closed during
DI On/Off schedule type or if occupancy is forced occupied by the BAS during BAS On/Off schedule type.
When transitioning from unoccupied to occupied, there will be a configured time delay of 5 to 600 seconds before starting the fan. The fan will continue to run as long as compressors, heating stages, or the dehumidification relays are on when transitioning from occupied to unoccupied with the exception of Shutdown mode. If Fire Shutdown, safety chain, SAT alarm or SPT alarm are active; the fan will be shutdown immediately regardless of the occupancy state or demand.
The RTU--MP has an optional Supply Fan Status input to provide proof of airflow. If this is enabled, the point will look for a contact closure whenever the Supply Fan Relay is on. If it is not enabled then it will always be the same state as the Supply Fan Relay. The cooling, economizer, heating, dehumidification, CO
and power exhaust
2
routines will use this input point for fan status.
Cooling
The compressor outputs are controlled by the Cooling Control PID Loop and Cooling Stages Capacity algorithm. They will be used to calculate the desired number of stages needed to satisfy the space by comparing the Space Temperature (SPT) to the Occupied Cool Setpoint plus the T56 slider offset when occupied and the Unoccupied Cool Setpoint (UCSP) plus the T56 slider offset, if unoccupied. The economizer, if available, will be used for cooling in addition to the compressors. The following conditions must be true in order for this algorithm to run:
S Indoor Fan has been ON for at least 30 seconds. S Heat mode is not active and the time guard between
modes equals zero.
S If occupied and the SPT >(occupied cool setpoint plus
48TC
79
the T56 slider offset).
S Space Temperature reading is available. S If it is unoccupied and the SPT > (unoccupied cool
setpoint plus the T56 slider offset). The indoor fan will be turned on by the staging algorithm.
S If economizer is available and active and economizer
open > 85% and SAT > (SAT low limit + 5_F) and SPT > effective setpoint + 0.5_F.
OR
Economizer is available, but not active
OR
Economizer is not available
S OAT > DX Lockout temperature.
If all of the above conditions are met, the compressors will be energized as required, otherwise they will be de--energized.
There is a fixed 3--minute minimum on time and a
48TC
5--minute off time for each compressor output and a 3--minute minimum time delay between staging up or down.
Any time the compressors are running the RTU--MP will stage down the compressors if the SAT becomes less than the cooling low supply air setpoint.
After a compressor is staged off, it may be started again after a normal time--guard period and the supply air temperature has increased above the low supply air setpoint.
Economizer
The Economizer dampers are used to provide free cooling and Indoor Air Quality, if optional CO
sensor is installed,
2
when the outside conditions are suitable. The following conditions must be true for economizer
operation:
S Indoor Fan has been on for at least 30 seconds. S Enthalpy is Low if the Enthalpy input is enabled. S SAT reading is available. S OAT reading is available. S SPT reading is available. S OAT <= High OAT economizer lockout configuration
(default = 75).
S OAT <= SPT
If any of the mentioned conditions are not true, the economizer will be set to its configured minimum position. The minimum damper position can be overridden by the IAQ routine described later in this section.
If the above conditions are true, the Economizer Control Master Loop will calculate a damper position value based on the following calculation: Damper Position = minimum position + PID (SPT -- econ setpoint). Econ setpoint is half way between the effective cool and heat setpoints. If the SAT drops below the cooling low supply air setpoint (+ 5_F), the economizer will ramp down to minimum position.
Exhaust
Power
If RTU--MP is also controlling an exhaust fan, it can be enabled based on damper position or by occupancy. If
configured for continuous occupied operation, it will be energized whenever the controller is in the occupied mode and disabled when in the unoccupied mode. If configured for damper position control, it will be energized whenever the economizer exceeds the power exhaust setpoint and disabled when the economizer drops below the setpoint by a fixed hysteresis of 10%.
Heating
The heating outputs are controlled by the Heating Control PID Loop and Heating Stages Capacity algorithm. They will be used to calculate the desired number of stages needed to satisfy the space by comparing the SPT to the Occupied Heat Setpoint plus the T56 slider offset when occupied and the Unoccupied Heat Setpoint plus the T56 slider offset if unoccupied. The following conditions must be true in order for this algorithm to run:
S Indoor Fan has been ON for at least 30 seconds. S Cool mode is not active and the time guard between
modes equals zero.
S If occupied and SPT <(occupied heat setpoint plus T56
slider offset)
S SPT reading is available S If it is unoccupied and the SPT < (unoccupied heat
setpoint plus T56 slider offset). The indoor fan will be turned on by the staging algorithm.
S OAT < High OAT lockout temperature.
If all of the above conditions are met, the heating outputs will be energized as required, otherwise they will be de--energized. If the SAT begins to exceed the high supply air setpoint, a ramping function will cause the Heat Stages Capacity algorithm to decrease the number of stages until the SAT has dropped below the setpoint.
There is a fixed one minute minimum on time and a one minute off time for each heat output. Heat staging has a 3 minute stage up and 30 second stage down delay.
Indoor Air
Quality
If the optional indoor air quality sensor is installed, the RTU--MP will maintain indoor air quality within the space at the user configured differential setpoint. The setpoint is the difference between the indoor air quality and an optional outdoor air quality sensor. If the outdoor air quality is not present then a fixed value of 400ppm is used. The following conditions must be true in order for this algorithm to run:
S The mode is occupied. S Indoor Fan has been ON for at least 30 seconds. S Indoor Air Quality sensor has a valid reading
As air quality within the space changes, the minimum position of the economizer damper will be changed thus allowing more or less outdoor air into the space depending on the relationship of the indoor air quality to the differential setpoint. If all the above conditions are true, the IAQ algorithm will run and calculates an IAQ minimum position value using a PID loop. The IAQ minimum damper position is then compared against the user configured economizer minimum position and the greatest value becomes the final minimum damper position of the economizer output.
80
If the calculated IAQ minimum position is greater than the IAQ maximum damper position configuration then it will be clamped to the configured value.
Demand
Limit
If the RTU--MP receives a level 1 (one degree offset), 2 (two degree offset), or a 3 (4 degree offset) to the BACnet demand limit variable, the controller will expand the
heating and cooling setpoints by the configured demand limit setpoint value and remain in effect until the BACnet demand limit variable receives a 0 value.
FASTENER TORQUE VALUES
See Table 32 for torque values.
Table 32 – Torque Values
Supply fan motor mounting 1 2 0 +/ --- 12 i n --- l b s Supply fan motor adjustment plate 1 2 0 +/ --- 12 i n --- l b s Motor pulley setscrew 72+/ --- 5 in ---lbs Fan pulley setscrew 72+/ --- 5 in ---lbs Blower wheel hub setscrew 72+/--- 5 in --- lbs Bearing locking collar setscrew 6 5 --- 70 i n --- lb s Compressor mounting bolts 65 --- 7 5 in --- l b s Condenser fan motor mounting bolts 2 0 + / --- 2 in --- l b s Condenser fan hub setscrew 8 4 + / --- 1 2 i n --- l b s
48TC
81
Model Number Nomenclature
Unit Heat Type 48 = Gas heat pkg rooftop Brand / Packaging
Tier / Model 1=LTL
TC = Entry tier (with Puron refrigerant)
Heat Size C = N on --- f u s e d d isc D=Lowheat D=Thruthebase E = Medium heat F = Non---fused & thru the base F=Highheat L=LowNOx,lowheat Service Options
48TC
M=LowNOx, medium heat 0=None N=LowNOx,highheat 1 = Unpowered convenience outlet S = Stainless steel, low heat 2 = Powered convenience outlet R = Stainless steel, medium heat T = Stainless steel, high heat
Refrig. System Options B=Tempeconow/barorelief A = Standard refrigeration system F = Enthalpy econo w/ baro relief
APPENDIX I. MODEL NUMBER SIGNIFICANCE
123456789101112131415161718
4 8 T C D A 0 4 A 1 A 5 -- 0 A 0 A 0
____ ____ ____
0=Standard
Electrical Options
A=None
Intake / Exhaust Options
A=None
Base Unit Controls
Cooling Tons 0 = Electromechanical
04 = 3 Ton 08 = 7.5 Ton 1 = PremierLink DDC controller 05 = 4 Ton 09 = 8.5 Ton 2 = RTU---MP multi protocol controller 06 = 5 Ton 12 = 10 Ton 07 = 6 Ton Design Rev
Factory assigned
Sensor Options
A=None Voltage B = RA smoke detector 1 = 575/3/60 C = SA smoke detector 3 = 208 --- 230/1/60 D=RA&SAsmokedetector 5 = 208 --- 230/3/60 E=CO2sensor F = RA smoke detector & CO G = SA smoke detector & CO H=RA&SAsmokedetector&CO
Indoor Fan Options D=EcoatAl/Cu --- EcoatAl/Cu 1 = Standard static option E = Cu/Cu --- Al/Cu 2 = Medium static option F = Cu/Cu --- Cu/Cu 3 = High static option M = A l / C u --- A l / C u --- L o u v e r e d H a il G u a r d s
1
1
Future availability
1
2
1
2
1
2
6 = 460/3/60
Coil Options (Outdoor Coil --- Indoor Coil)
A = Al/Cu --- Al/Cu B = P r e coat A l / C u --- A l / C u C = E coat A l / C u --- A l / C u
N = P r e coat A l / C u --- A l / C u --- L o u v e r e d Hail G u a r d s P = E co a t A l / C u --- A l / C u --- L o u v e r e d Hail G u a r d s Q = E coat A l / C u --- E c o a t A l / C u --- L o u v e r e d Ha i l G u ard s R = C u /C u --- Al / C u --- L o u vered H a i l G u a r d s S = C u / Cu --- C u/C u --- Louve r e d H a i l G u a r ds
Serial Number Format
POSITION NUMBER 1 2 3 4 5 6 7 8 9 10
TYPICAL 1 2 0 8 G 1 2 3 4 6
POSITION DESIGNATES
1---2 Week of manufacture (fiscal calendar 3---4 Year of manufacture (“08” = 2008)
5 Manufacturing location (G = ETP, Texas, USA)
6--- 10 Sequential number
82
APPENDIX II. PHYSICAL DATA
Physical Data (Cooling) 3 -- 6 TONS
48TC*A04 48TC*A05 48TC*A06 48TC*A07
Refrigeration System
#Circuits/#Comp./Type 1/1/Scroll 1/1/Scroll 1/1/Scroll 1/1/Scroll
Puron (R---410a) charge A/B (lbs) 5.6 8.5 10.7 14.1
Oil A/B (oz) 25 42 42 56
Metering Device Acutrol Acutrol Acutrol Acutrol
High--- press. Trip / Reset (psig) 630 / 505 630 / 505 630 / 505 630 / 505
Low--- press. Trip / Reset (psig) 54 / 117 54 / 117 54 / 117 54 / 117
Evap. Coil
Material Cu / Al Cu / Al Cu / Al Cu / Al
Coil type 3/8” RTPF 3/8” RTPF 3/8” RTPF 3/8” RTPF
Rows / FPI 2 / 15 2/15 4/15 4/15
Tota l Fac e A r ea ( f t2)5.5 5.5 5.5 7.3
Condensate Drain Conn. Size 3/4” 3/4” 3/4” 3/4”
Evap. Fan and Motor
Motor Qty / Drive Type 1/Belt
Max BHP 1.2
RPM Range 560 --- 854 560 --- 854 770--- 1175 ---
1phase
Standard Static
3phase
Standard Static
1phase
Medium Static
3phase
Medium Static
3phase
High Static
Motor Frame Size 48 48 48 ---
Fan Qty / Type 1/Centrifugal 1/Centrifugal 1/Centrifugal ---
Fan Diameter (in) 10 x 10 10 x 10 10 x 10 ---
Motor Qty / Drive Type 1/Belt 1/Belt 1/Belt 1/Belt
Max BHP 1.2 1.2 1.2 2.4
RPM Range 560 --- 854 560 --- 854 770--- 1175 1073---1457
Motor Frame Size 48 48 48 56
Fan Qty / Type 1/Centrifugal 1/Centrifugal 1/Centrifugal 1/Centrifugal
Fan Diameter (in) 10 x 10 10 x 10 10 x 10 10 x 10
Motor Qty / Drive Type 1/Belt 1/Belt 1/Belt ---
Max BHP 1.2 1.2 1.5 ---
RPM Range 770- -- 1175 770---1175 1035 ---1466 ---
Motor Frame Size 48 56 56 ---
Fan Qty / Type 1/Centrifugal 1/Centrifugal 1/Centrifugal ---
Fan Diameter (in) 10 x 10 10 x 10 10 x 10 ---
Motor Qty / Drive Type 1/Belt 1/Belt 1/Belt 1/Belt
Max BHP 1.2 1.2 2.4 2.9
RPM Range 770- -- 1175 770---1175 1035 ---1466 1173- -- 1788
Motor Frame Size 48 48 56 56
Fan Qty / Type 1/Centrifugal 1/Centrifugal 1/Centrifugal 1/Centrifugal
Fan Diameter (in) 10 x 10 10 x 10 10 x 10 10 x 10
Motor Qty / Drive Type 1/Belt 1/Belt 1/Belt 1/Belt
Max BHP 2.4 2.4 2.9 3.7
RPM Range 1035 --- 1466 1035--- 1466 1303 ---1687 1474- -- 1788
Motor Frame Size 56 56 56 56
Fan Qty / Type 1/Centrifugal 1/Centrifugal 1/Centrifugal 1/Centrifugal
Fan Diameter (in) 10 x 10 10 x 10 10 x 10 10 x 10
1/Belt 1/Belt ---
1.2 1.2 ---
48TC
Cond. Coil
Cond. fan / motor
Filters
Material Cu / Al Cu / Al Cu / Al Cu / Al
Coil type 3/8” RTPF 3/8” RTPF 3/8” RTPF 3/8” RTPF
Rows / FPI 1 / 17 2/17 2/17 2/17
Tota l Fac e A r ea ( f t2) 14.6 12.6 16.5 21.3
Qty / Motor Drive Type 1/ Direct 1/ Direct 1/ Direct 1/ Direct
Motor HP / RPM 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100
Fan diameter (in) 22 22 22 22
RAFilter#/Size(in) 2/16x25x2 2/16x25x2 2/16x25x2 4/16x16x2
OA inlet sc reen # / Size (in) 1/20x24x1 1/20x24x1 1/20x24x1 1/20x24x1
83
APPENDIX II. PHYSICAL DATA (cont.)
Physical Data (Cooling) 7.5 -- 10 TONS
Refrigeration System
#Circuits/#Comp./Type 1/1/Scroll 1/1/Scroll 1/1/Scroll
Puron (R---410a) charge A/B (lbs) 13.75 15.25 20.0
Oil A/B (oz) 60 85 110
Metering Device Acutrol Acutrol Acutrol
High--- press. Trip / Reset (psig) 630 / 505 630 / 505 630 / 505
Low--- press. Trip / Reset (psig) 54 / 117 54 / 117 54 / 117
Evap. Coil
Material Cu / Al Cu / Al Cu / Al
Coil type 3/8” RTPF 3/8” RTPF 3/8” RTPF
Rows / FPI 3 / 15 3/15 4/15
Tota l Fac e A r ea ( f t2)8.9 11.1 11.1
Condensate Drain Conn. Size 3/4” 3/4” 3/4”
Evap. Fan and Motor
48TC*A08 48TC*A09 48TC*A12
48TC
Cond. Coil
Cond. fan / motor
Filters
Motor Qty / Drive Type 1/Belt
Max BHP 1.7
RPM Range 489 --- 747 518--- 733 591 --- 838
Motor Frame Size 56 56 56
3phase
Standard Static
3phase
Medium Static
3phase
High Static
Fan Qty / Type 1/Centrifugal 1/Centrifugal 1/Centrifugal
Fan Diameter (in) 15 x 15 15 x 15 15 x 15
Motor Qty / Drive Type 1/Belt 1/Belt 1/Belt
Max BHP 2.9 2.4 3.7
RPM Range 733 --- 949 690--- 936 838 --- 1084
Motor Frame Size 56 56 56
Fan Qty / Type 1/Centrifugal 1/Centrifugal 1/Centrifugal
Fan Diameter (in) 15 x 15 15 x 15 15 x 15
Motor Qty / Drive Type 1/Belt 1/Belt 1/Belt
Max BHP 5.25 3.7 5.25
RPM Range 909 -- -1102 838--- 1084 1022--- 1240
Motor Frame Size 145TY 56 145TY
Fan Qty / Type 1/Centrifugal 1/Centrifugal 1/Centrifugal
Fan Diameter (in) 15 x 15 15 x 15 15 x 15
Material Cu / Al Cu / Al Cu / Al
Coil type 3/8” RTPF 3/8” RTPF 3/8” RTPF
Rows / FPI 2 / 17 2/17 2/17
Tota l Fac e A r ea ( f t2) 20.5 21.4 25.1
Qty / Motor Drive Type 2 / Direct 2/Direct 2/Direct
Motor HP / RPM 1/4 / 1100 1/4 / 1100 1/4 / 1100
Fan diameter (in) 22 22 22
RAFilter#/Size(in) 4/16x20x2 4/20x20x2 4/20x20x2
OA inlet sc reen # / Size (in) 1/20x24x1 1/20x24x1 1/20x24x1
1/Belt 1/Belt
1.7 2.4
84
APPENDIX II. PHYSICAL DATA (cont.)
Physical Data (Heating) 3 -- 6 TONS
48TC**04 48TC**05 48TC* *06 48TC**07
Gas Connection
#ofGasValves 1 1 1 1
Connection size 1/2” NPT 1/2” NPT 1/2” NPT 1/2” NPT
Nat. gas supply line press (in. w.g.)/(PSIG) 5 --- 13 / 0 . 1 8 --- 0.47 5 --- 1 3 / 0 . 1 8 --- 0.4 7 5 --- 1 3 / 0 . 1 8 --- 0 . 4 7 5 --- 1 3 / 0 . 1 8 --- 0 . 4 7
LP supply line press (in. w.g.)/(PSIG) 11 --- 13 / 0.40---0.47 11---13 / 0.40 ---0.47 11---13 / 0.40 ---0.47 11---13 / 0.40 ---0.47
Heat Anticipator Setting (Amps)
1st stage 0.14 0.14 0.14 0.14
2nd stage 0.14 0.14 0.14 0.14
Natural Gas Heat
#ofstages/#ofburners(total) 1/2 1/2 1/2 1/2
LOW
MED
Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115 195 / 115
Temp e rat u re r ise 25 / 55 25 --- 55 25 --- 55 25 --- 55
#ofstages/#ofburners(total) 1or2/3 1/3 1/3 1/3
Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115 195 / 115
Temp e rat u re r ise 55 / 85 35 / 65 35 / 65 35 / 65
48TC
#ofstages/#ofburners(total) --- 1or2/3 1or2/3 1or2/3
Rollout switch opens / Closes --- 195 / 115 195 / 115 195 / 115
HIGH
Liquid Propane Heat
#ofstages/#ofburners(total) 1/2 1/2 1/2 1/2
LOW
MED
Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115 195 / 115
#ofstages/#ofburners(total) 1or2/3 1or2/3 1or2/3 1or2/3
Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115 195 / 115
#ofstages/#ofburners(total) --- 1or2/3 1or2/3 1or2/3
Rollout switch opens / Closes --- 195 / 115 195 / 115 195 / 115
HIGH
Low NOxGas Heat
#ofstages/#ofburners(total) 1/2 1/2 1/2 ---
LOW
Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115 ---
Temp e rat u re r ise --- 50 / 80 50 / 80 50 / 80
Temp e rat u re r ise 25 / 55 25 --- 55 25 --- 55 25 --- 55
Temp e rat u re r ise 55 / 85 35 / 65 35 / 65 35 / 65
Temp e rat u re r ise --- 50 / 80 50 / 80 50 / 80
Temp e rat u re r ise 20 / 50 20 / 50 20 / 50 ---
#ofstages/#ofburners(total) 1/3 1/3 1/3 ---
MED
HIGH
Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 ---
Temp e rat u re r ise 30 / 60 30 / 60 30 / 60 ---
#ofstages/#ofburners(total) --- 1/3 1/3 ---
Rollout switch opens / Closes --- 195 / 115 195 / 115 ---
Temp e rat u re r ise --- 40 / 70 40 / 70 ---
85
APPENDIX II. PHYSICAL DATA (cont.)
Physical Data (Heating) 7.5 -- 10 TONS
48TC**04 48TC**05 48TC* *06 48TC**07
Gas Connection
#ofGasValves 1 1 1 1
Nat. gas supply line press (in. w.g.)/(PSIG) 4 --- 13 / 0 . 1 8 --- 0.47 4 --- 1 3 / 0 . 1 8 --- 0.4 7 4 --- 1 3 / 0 . 1 8 --- 0 . 4 7 4 --- 1 3 / 0 . 1 8 --- 0 . 4 7
LP supply line press (in. w.g.)/(PSIG) 11 --- 13 / 0.40---0.47 11---13 / 0.40 ---0.47 11---13 / 0.40 ---0.47 11---13 / 0.40 ---0.47
Heat Anticipator Setting (Amps)
1st stage 0.14 0.14 0.14 0.14
2nd stage 0.14 0.14 0.14 0.14
Natural Gas Heat
Connection size 1/2” NPT 1/2” NPT 1/2” NPT 1/2” NPT
#ofstages/#ofburners(total) 1/2 1/2 1/2 1/2
LOW
48TC
MED
HIGH
Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115 195 / 115
Temperature rise (min/max) 25 / 55 25 --- 55 25 --- 55 25 --- 55
Connection size 1/2” NPT 1/2” NPT 1/2” NPT 1/2” NPT
#ofstages/#ofburners(total) 1or2/3 1/3 1/3 1/3
Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115 195 / 115
Temperature rise (min/max) 55 / 85 35 / 65 35 / 65 35 / 65
Connection size 1/2” NPT 1/2” NPT 1/2” NPT 1/2” NPT
#ofstages/#ofburners(total) --- 1or2/3 1or2/3 1or2/3
Rollout switch opens / Closes --- 195 / 115 195 / 115 195 / 115
Temperature rise (min/max) --- 50 / 80 50 / 80 50 / 80
Liquid Propane Heat
#ofstages/#ofburners(total) 1/2 1/2 1/2 1/2
LOW
MED
HIGH
Low NOxGas Heat
LOW
MED
Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115 195 / 115
Temperature rise (min/max) 25 / 55 25 --- 55 25 --- 55 25 --- 55
#ofstages/#ofburners(total) 1or2/3 1or2/3 1or2/3 1or2/3
Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115 195 / 115
Temperature rise (min/max) 55 / 85 35 / 65 35 / 65 35 / 65
#ofstages/#ofburners(total) --- 1or2/3 1or2/3 1or2/3
Rollout switch opens / Closes --- 195 / 115 195 / 115 195 / 115
Temperature rise (min/max) --- 50 / 80 50 / 80 50 / 80
#ofstages/#ofburners(total) 1/2 1/2 1/2 ---
Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115 ---
Temperature rise (min/max) 20 / 50 20 / 50 20 / 50 ---
#ofstages/#ofburners(total) 1/3 1/3 1/3 ---
Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 ---
Temperature rise (min/max) 30 / 60 30 / 60 30 / 60 ---
Connection size 1/2” NPT 1/2” NPT 1/2” NPT 1/2” NPT
Connection size 1/2” NPT 1/2” NPT 1/2” NPT 1/2” NPT
Connection size 1/2” NPT 1/2” NPT 1/2” NPT 1/2” NPT
Connection size 1/2” NPT 1/2” NPT 1/2” NPT 1/2” NPT
Connection size 1/2” NPT 1/2” NPT 1/2” NPT 1/2” NPT
Connection size 1/2” NPT 1/2” NPT 1/2” NPT 1/2” NPT
#ofstages/#ofburners(total) --- 1/3 1/3 ---
HIGH
Rollout switch opens / Closes --- 195 / 115 195 / 115 ---
Temperature rise (min/max) --- 40 / 70 40 / 70 ---
86
APPENDIX III. FAN PERFORMANCE
General Fan Performance Notes:
1. Interpolation is permissible. Do not extrapolate.
2. External static pressure is the static pressure difference between the return duct and the supply duct plus the static pressure caused by any FIOPs or accessories.
3. Tabular data accounts for pressure loss due to clean filters, unit casing, and wet coils. Factory options and accessories may add static pressure losses.
4. The Fan Performance tables offer motor/drive recommendations. In cases when two motor/drive combinations would work, Carrier recommended the lower horsepower option.
5. For information on the electrical properties of Carrier’s motors, please see the Electrical information section of this book.
48TC
87
APPENDIX III. FAN PERFORMANCE (cont.)
48TC**04 1 Phase 3 Ton Horizontal Supply
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1
Medium Static Option F i e l d --- S u p p l i e d D r i ve
Standard Static Option Medium Static Option
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
48TC
CFM
F i e l d --- S u p p l i e d D r i v e
900 553 0.14 681 0.22 782 0.32 870 0.42 948 0.53
975 575 0.16 700 0.25 801 0.35 888 0.46 965 0.57 1050 597 0.18 720 0.28 820 0.38 906 0.49 983 0.61 1125 620 0.21 741 0.31 839 0.42 925 0.54 1001 0.66 1200 643 0.23 762 0.34 859 0.46 944 0.58 1020 0.71 1275 667 0.27 783 0.38 879 0.50 963 0.63 1038 0.76 1350 691 0.30 805 0.42 900 0.55 983 0.68 1057 0.82 1425 715 0.34 827 0.47 920 0.60 1002 0.74 1076 0.88 1500 740 0.38 849 0.52 941 0.66 1023 0.80 1096 0.95
CFM
900 1019 0.64 1084 0.76 1146 0.89 1203 1.02 1258 1.16
975 1036 0.69 1101 0.81 1162 0.94 1219 1.08 --- --­1050 1053 0.74 1118 0.86 1179 1.00 1236 1.14 --- --­1125 1071 0.79 1135 0.92 1196 1.06 1253 1.20 --- --­1200 1089 0.84 1153 0.98 1213 1.12 --- --- --- --­1275 1107 0.90 1171 1.04 1231 1.19 --- --- --- --­1350 1126 0.96 1189 1.11 --- --- --- --- --- --­1425 1144 1.03 1208 1.18 --- --- --- --- --- --­1500 1163 1.10 --- --- --- --- --- --- --- ---
2
NOTE: For more information, see General Fan Performance Notes on page 87. Boldface indicates field ---supplied drive is required.
1. Recommend using field --- supplied fan pulley (part number KR11AG006) and belt (part number KR30AE039).
2. Recommend using field---supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035).
48TC**04 1 Phase 3 Ton Vertical Supply
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
CFM
F i e l d --- S u p p l i e d D r i v e
900 567 0.15 688 0.22 786 0.30 871 0.37 947 0.44
975 591 0.17 710 0.26 807 0.34 891 0.42 966 0.49 1050 615 0.20 732 0.29 828 0.38 911 0.47 985 0.55 1125 641 0.23 755 0.33 849 0.42 931 0.52 1005 0.61 1200 666 0.26 778 0.37 871 0.47 952 0.57 1025 0.67 1275 693 0.29 802 0.41 893 0.53 974 0.63 1046 0.74 1350 719 0.33 826 0.46 916 0.58 995 0.70 1067 0.81 1425 746 0.38 850 0.51 939 0.64 1017 0.76 1088 0.89 1500 773 0.42 875 0.57 963 0.70 1040 0.84 1110 0.96
CFM
900 1016 0.51 1080 0.57 1139 0.64 1195 0.71 1249 0.77
975 1034 0.57 1098 0.64 1157 0.72 1213 0.79 1266 0.86 1050 1053 0.63 1116 0.71 1125 1073 0.70 1135 0.79 1194 0.87 1250 0.96 1302 1.04 1200 1093 0.77 1155 0.87 1213 0.96 1268 1.05 1321 1.14 1275 1113 0.85 1174 0.95 1232 1.05 1287 1.15 --- --­1350 1133 0.92 1194 1.03 1252 1.14 --- --- --- --­1425 1154 1.01 1215 1.12 --- --- --- --- --- --­1500 1175 1.09 --- --- --- --- --- --- --- ---
NOTE: For more information, see General Fan Performance Notes on page 87. Boldface indicates field ---supplied drive is required.
1. Recommend using field --- supplied fan pulley (part number KR11AG006) and belt (part number KR30AE039).
2. Recommend using field---supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035).
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1
Medium Static Option F i e l d --- S u pp l i e d D r i v e
Standard Static Option Medium Static Option
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
1176
0.79 1231 0.87 1284 0.95
2
88
APPENDIX III. FAN PERFORMANCE (cont.)
48TC**04 3 Phase 3 Ton Horizontal Supply
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
CFM
F i e l d --- S u p p l i e d D r i v e
900 553 0.14 681 0.22 782 0.32 870 0.42 948 0.53
975 575 0.16 700 0.25 801 0.35 888 0.46 965 0.57 1050 597 0.18 720 0.28 820 0.38 906 0.49 983 0.61 1125 620 0.21 741 0.31 839 0.42 925 0.54 1001 0.66 1200 643 0.23 762 0.34 859 0.46 944 0.58 1020 0.71 1275 667 0.27 783 0.38 879 0.50 963 0.63 1038 0.76 1350 691 0.30 805 0.42 900 0.55 983 0.68 1057 0.82 1425 715 0.34 827 0.47 920 0.60 1002 0.74 1076 0.88 1500 740 0.38 849 0.52 941 0.66 1023 0.80 1096 0.95
CFM
900 1019 0.64 1084 0.76 1146 0.89 1203 1.02 1258 1.16
975 1036 0.69 1101 0.81 1162 0.94 1219 1.08 1274 1.22 1050 1053 0.74 1118 0.86 1179 1.00 1236 1.14 1290 1.28 1125 1071 0.79 1135 0.92 1196 1.06 1253 1.20 1307 1.35 1200 1089 0.84 1153 0.98 1213 1.12 1270 1.27 1324 1.42 1275 1107 0.90 1171 1.04 1231 1.19 1287 1.34 1341 1.50 1350 1126 0.96 1189 1.11 1249 1.26 1305 1.42 1358 1.58 1425 1144 1.03 1208 1.18 1267 1.34 1323 1.50 1376 1.66 1500 1163 1.10 1226 1.25 1285 1.41 1341 1.58 1394 1.75
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1
Medium Static Option High Static Option
Standard Static Option Medium Static Option
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
48TC
NOTE: For more information, see General Fan Performance Notes on page 87.
1. Recommend using field ---supplied drive (part number KR11AG006) and belt (part number KR30AE039)
48TC**04 3 Phase 3 Ton Vertical Supply
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
CFM
F i e l d --- S u p p l i e d D r i v e
900 567 0.15 688 0.22 786 0.30 871 0.37 947 0.44
975 591 0.17 710 0.26 807 0.34 891 0.42 966 0.49 1050 615 0.20 732 0.29 828 0.38 911 0.47 985 0.55 1125 641 0.23 755 0.33 849 0.42 931 0.52 1005 0.61 1200 666 0.26 778 0.37 871 0.47 952 0.57 1025 0.67 1275 693 0.29 802 0.41 893 0.53 974 0.63 1046 0.74 1350 719 0.33 826 0.46 916 0.58 995 0.70 1067 0.81 1425 746 0.38 850 0.51 939 0.64 1017 0.76 1088 0.89 1500 773 0.42 875 0.57 963 0.70 1040 0.84 1110 0.96
CFM
900 1016 0.51 1080 0.57 1139 0.64 1195 0.71 1249 0.77
975 1034 0.57 1098 0.64 1157 0.72 1213 0.79 1266 0.86 1050 1053 0.63 1116 0.71 1125 1073 0.70 1135 0.79 1194 0.87 1250 0.96 1302 1.04 1200 1093 0.77 1155 0.87 1213 0.96 1268 1.05 1321 1.14 1275 1113 0.85 1174 0.95 1232 1.05 1287 1.15 1339 1.25 1350 1133 0.92 1194 1.03 1252 1.14 1307 1.25 1358 1.35 1425 1154 1.01 1215 1.12 1272 1.24 1326 1.35 1378 1.46 1500 1175 1.09 1235 1.22 1292 1.34 1346 1.46 1397 1.58
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1
Medium Static Option High Static Option
Standard Static Option Medium Static Option
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
1176
0.79 1231 0.87 1284 0.95
NOTE: For more information, see General Fan Performance Notes on page 87. Boldface indicates field ---supplied drive is required.
1. Recommend using field --- supplied fan pulley (part number KR11AG006) and belt (part number KR30AE039).
89
APPENDIX III. FAN PERFORMANCE (cont.)
48TC**05 1 Phase 4 Ton Horizontal Supply
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Static Option Medium Static Option
879
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option F i e l d --- S u p p l i e d D r i v e
0.59 970 0.73 1050 0.88 1123 1.04
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
48TC
CFM
1200 643 0.23 762 0.34 859 0.46 944 0.58 1020 0.71 1300 675 0.28 790 0.40 886 0.52 969 0.65 1044 0.78 1400 707 0.33 819 0.45 913 0.58 996 0.72 1070 0.86 1500 740 0.38 849 0.52 941 0.66 1023 0.80 1096 0.95 1600 773 0.45 1700 807 0.52 910 0.67 999 0.82 1078 0.98 1150 1.14 1800 841 0.59 942 0.75 1029 0.91 1106 1.08 1177 1.25 1900 875 0.68 974 0.85 1059 1.02 1135 1.19 1205 1.37 2000 910 0.77 1006 0.95 1090 1.13 1165 1.31 1234 1.49
CFM
1200 1089 0.84 1153 0.98 1213 1.12 --- --- --- --­1300 1113 0.92 1177 1.06 --- --- --- --- --- --­1400 1138 1.01 1201 1.15 --- --- --- --- --- --­1500 1163 1.10 --- --- --- --- --- --- --- --­1600 1189 1.20 --- --- --- --- --- --- --- --­1700 --- --- --- --- --- --- --- --- --- --­1800 --- --- --- --- --- --- --- --- --- --­1900 --- --- --- --- --- --- --- --- --- --­2000 --- --- --- --- --- --- --- --- --- ---
1
NOTE: For more information, see General Fan Performance Notes on page 87. Boldface indicates field ---supplied drive is required.
1. Recommend using field---supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035).
48TC**05 1 Phase 4 Ton Vertical Supply
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
CFM
1200 666 0.26 778 0.37 871 0.47 952 0.57 1025 0.67 1300 701 0.31 810 0.43 901 0.54 981 0.65 1053 0.76 1400 737 0.36 842 0.49 931 0.62 1010 0.74 1081 0.86 1500 773 0.42 1600 810 0.49 909 0.65 994 0.79 1070 0.94 1140 1.08 1700 847 0.57 943 0.73 1027 0.89 1101 1.05 1170 1.20 1800 885 0.66 978 0.83 1060 1.00 1133 1.16 1200 1.32 1900 923 0.75 1014 0.94 1093 1.11 1165 1.29 1231 1.46 2000 962 0.85 1049 1.05 1127 1.24 1198 1.42 1263 1.61
CFM
1200 1093 0.77 1155 0.87 1213 0.96 1268 1.05 1321 1.14 1300 1119 0.87 1181 0.98 1239 1.08 1294 1.18 --- --­1400 1147 0.98 1208 1.09 --- --- --- --- --- --­1500 1175 1.09 --- --- --- --- --- --- --- --­1600 --- --- --- --- --- --- --- --- --- --­1700 --- --- --- --- --- --- --- --- --- --­1800 --- --- --- --- --- --- --- --- --- --­1900 --- --- --- --- --- --- --- --- --- --­2000 --- --- --- --- --- --- --- --- --- ---
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Static Option Medium Static Option
875
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option F i e l d --- Su p p l i e d D r i v e
0.57 963 0.70 1040 0.84 1110 0.96
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
1
NOTE: For more information, see General Fan Performance Notes on page 87. Boldface indicates field ---supplied drive is required.
1. Recommend using field---supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035).
90
APPENDIX III. FAN PERFORMANCE (cont.)
48TC**05 3 Phase 4 Ton Horizontal Supply
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
CFM
1200 643 0.23 762 0.34 859 0.46 944 0.58 1020 0.71 1300 675 0.28 790 0.40 886 0.52 969 0.65 1044 0.78 1400 707 0.33 819 0.45 913 0.58 996 0.72 1070 0.86 1500 740 0.38 849 0.52 941 0.66 1023 0.80 1096 0.95 1600 773 0.45 1700 807 0.52 910 0.67 999 0.82 1078 0.98 1150 1.14 1800 841 0.59 942 0.75 1029 0.91 1106 1.08 1177 1.25 1900 875 0.68 974 0.85 1059 1.02 1135 1.19 1205 1.37 2000 910 0.77 1006 0.95 1090 1.13 1165 1.31 1234 1.49
CFM
1200 1089 0.84 1153 0.98 1213 1.12 1270 1.27 1324 1.42 1300 1113 0.92 1177 1.06 1237 1.21 1293 1.36 1347 1.52 1400 1138 1.01 1201 1.15 1261 1.31 1317 1.47 1370 1.63 1500 1163 1.10 1226 1.25 1285 1.41 1341 1.58 1394 1.75 1600 1189 1.20 1252 1.36 1310 1.53 1365 1.70 1418 1.87 1700 1216 1.31 1277 1.48 1335 1.65 1390 1.83 1442 2.01 1800 1242 1.42 1303 1.60 1361 1.78 1415 1.96 1467 2.15 1900 1270 1.55 1330 1.73 1387 1.92 1441 2.11 1493 2.30 2000 1297 1.68 1357 1.87 1414 2.07 1467 2.26 --- ---
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Static Option Medium Static Option
879
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option High Static Option
0.59 970 0.73 1050 0.88 1123 1.04
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
48TC
NOTE: For more information, see General Fan Performance Notes on page 87. Boldface indicates field ---supplied drive is required.
1. Recommend using fiel d---supplied fan pulley (part no. KR11AZ506), motor pulley (part no. KR11HY181) and belt (part no. KR30AE041).
48TC**05 3 Phase 4 Ton Vertical Supply
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
CFM
1200 666 0.26 778 0.37 871 0.47 952 0.57 1025 0.67 1300 701 0.31 810 0.43 901 0.54 981 0.65 1053 0.76 1400 737 0.36 842 0.49 931 0.62 1010 0.74 1081 0.86 1500 773 0.42 1600 810 0.49 909 0.65 994 0.79 1070 0.94 1140 1.08 1700 847 0.57 943 0.73 1027 0.89 1101 1.05 1170 1.20 1800 885 0.66 978 0.83 1060 1.00 1133 1.16 1200 1.32 1900 923 0.75 1014 0.94 1093 1.11 1165 1.29 1231 1.46 2000 962 0.85 1049 1.05 1127 1.24 1198 1.42 1263 1.61
CFM
1200 1093 0.77 1155 0.87 1213 0.96 1268 1.05 1321 1.14 1300 1119 0.87 1181 0.98 1239 1.08 1294 1.18 1346 1.28 1400 1147 0.98 1208 1.09 1265 1.21 1320 1.32 1371 1.43 1500 1175 1.09 1235 1.22 1292 1.34 1346 1.46 1397 1.58 1600 1204 1.21 1263 1.35 1320 1.48 1373 1.61 1424 1.74 1700 1233 1.34 1292 1.49 1348 1.63 1401 1.77 1451 1.91 1800 1262 1.48 1321 1.64 1376 1.79 1428 1.94 1479 2.09 1900 1293 1.63 1350 1.79 1405 1.96 1457 2.12 1506 2.28 2000 1323 1.79 1380 1.96 1434 2.13 1486 2.31 --- ---
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Static Option Medium Static Option
875
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option High Static Option
0.57 963 0.70 1040 0.84 1110 0.96
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
NOTE: For more information, see General Fan Performance Notes on page 87. Boldface indicates field ---supplied drive is required.
1. Recommend using fiel d---supplied fan pulley (part no. KR11AZ506), motor pulley (part no. KR11HY181) and belt (part no. KR30AE041).
91
APPENDIX III. FAN PERFORMANCE (cont.)
48TC**06 1 Phase 5 Ton Horizontal Supply
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Static Option Medium Static Option
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option
48TC
CFM
1500 800 0.39 904 0.49 999 0.60 1087 0.72 1169 0.85 1625 849 0.48 947 0.59 1038 0.70 1122 0.83 1201 0.96 1750 899 0.59 992 0.70 1078 0.82 1875 950 0.70 1038 0.82 1120 0.95 1198 1.08 1271 1.22 2000 1001 0.84 1085 0.96 1163 1.09 1238 1.23 1309 1.38 2125 1053 0.99 1133 1.12 1208 1.26 1280 1.40 --- --­2250 1106 1.16 1182 1.29 1254 1.44 --- --- --- --­2375 1159 1.34 1231 1.49 --- --- --- --- --- --­2500 --- --- --- --- --- --- --- --- --- ---
CFM
1500 1247 0.98 1320 1.13 1390 1.28 1457 1.44 --- --­1625 1276 1.10 1348 1.24 1416 1.40 --- --- --- --­1750 1308 1.22 1377 1.38 --- --- --- --- --- --­1875 1342 1.37 --- --- --- --- --- --- --- --­2000 --- --- --- --- --- --- --- --- --- --­2125 --- --- --- --- --- --- --- --- --- --­2250 --- --- --- --- --- --- --- --- --- --­2375 --- --- --- --- --- --- --- --- --- --­2500 --- --- --- --- --- --- --- --- --- ---
1159
0.95 1235 1.08
NOTE: For more information, see General Fan Performance Notes on page 87. Boldface indicates field ---supplied drive is required.
48TC**06 1 Phase 5 Ton Vertical Supply
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
CFM
1500 848 0.42 968 0.55 1069 0.68 1158 0.80 1238 0.94 1625 897 0.51 1013 0.65 1111 0.79 1198 0.93 1277 1.07 1750 947 0.61 1059 0.76 1155 0.91 1240 1.06 1318 1.21 1875 997 0.72 1105 0.89
2000 1048 0.85 1153 1.03 1244 1.20 1326 1.37 --- --­2125 1100 1.00 1201 1.19 1290 1.37 --- --- --- --­2250 1152 1.16 1250 1.36 --- --- --- --- --- --­2375 1205 1.34 --- --- --- --- --- --- --- --­2500 --- --- --- --- --- --- --- --- --- ---
CFM
1500 1312 1.07 1380 1.20 1445 1.34 1506 1.48 --- --­1625 1350 1.21 1418 1.35 1482 1.50 --- --- --- --­1750 1390 1.36 --- --- --- --- --- --- --- --­1875 --- --- --- --- --- --- --- --- --- --­2000 --- --- --- --- --- --- --- --- --- --­2125 --- --- --- --- --- --- --- --- --- --­2250 --- --- --- --- --- --- --- --- --- --­2375 --- --- --- --- --- --- --- --- --- --­2500 --- --- --- --- --- --- --- --- --- ---
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Static Option Medium Static Option
1199
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option F i e l d --- S u pp l i e d D r i v e
1.05 1283 1.21 1359 1.37
1
NOTE: For more information, see General Fan Performance Notes on page 87. Boldface indicates field ---supplied drive is required.
1. Recommend using field---supplied motor pulley (part number KR11HY171) and belt (part number KR30AE039).
92
APPENDIX III. FAN PERFORMANCE (cont.)
48TC**06 3 Phase 5 Ton Horizontal Supply
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
CFM
1500 800 0.39 904 0.49 999 0.60 1087 0.72 1169 0.85 1625 849 0.48 947 0.59 1038 0.70 1122 0.83 1201 0.96 1750 899 0.59 992 0.70 1078 0.82 1875 950 0.70 1038 0.82 1120 0.95 1198 1.08 1271 1.22 2000 1001 0.84 1085 0.96 1163 1.09 1238 1.23 1309 1.38 2125 1053 0.99 1133 1.12 1208 1.26 1280 1.40 1348 1.55 2250 1106 1.16 1182 1.29 1254 1.44 1323 1.59 1389 1.74 2375 1159 1.34 1231 1.49 1300 1.64 1367 1.80 1430 1.96 2500 1212 1.55 1281 1.70 1348 1.86 1412 2.02 1473 2.19
CFM
1500 1247 0.98 1320 1.13 1390 1.28 1457 1.44 1522 1.61 1625 1276 1.10 1348 1.24 1416 1.40 1481 1.56 1544 1.73 1750 1308 1.22 1377 1.38 1444 1.53 1507 1.70 1569 1.87 1875 1342 1.37 1409 1.52 1473 1.69 1536 1.86 1596 2.03 2000 1377 1.53 1442 1.69 1505 1.86 1565 2.03 1624 2.21 2125 1414 1.71 1477 1.87 1538 2.04 1597 2.22 1654 2.40 2250 1452 1.91 1514 2.08 1573 2.25 1630 2.43 1686 2.62 2375 1492 2.12 1551 2.30 1609 2.48 1665 2.66 1719 2.85 2500 1533 2.36 1591 2.54 1647 2.73 --- --- --- ---
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Static Option Medium Static Option
1159
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option High Static Option
0.95 1235 1.08
48TC
NOTE: For more information, see General Fan Performance Notes on page 87. Boldface indicates field ---supplied drive is required.
1. Recommend using field--- supplied fan pulley (part number KR11AZ506), motor pulley (part number KR11HY191) and belt (part number KR30AE042).
48TC**06 3 Phase 5 Ton Vertical Supply
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
CFM
1500 848 0.42 968 0.55 1069 0.68 1158 0.80 1238 0.94 1625 897 0.51 1013 0.65 1111 0.79 1198 0.93 1277 1.07 1750 947 0.61 1059 0.76 1155 0.91 1240 1.06 1318 1.21 1875 997 0.72 1105 0.89 2000 1048 0.85 1153 1.03 1244 1.20 1326 1.37 1401 1.54 2125 1100 1.00 1201 1.19 1290 1.37 1370 1.55 1444 1.73 2250 1152 1.16 1250 1.36 1336 1.55 1415 1.75 1487 1.94 2375 1205 1.34 1299 1.55 1384 1.76 1460 1.96 1532 2.17 2500 1258 1.54 1349 1.76 1431 1.98 1506 2.20 1576 2.41
CFM
1500 1312 1.07 1380 1.20 1445 1.34 1506 1.48 1564 1.62 1625 1350 1.21 1418 1.35 1482 1.50 1542 1.64 1600 1.79 1750 1390 1.36 1457 1.51 1520 1.67 1580 1.83 1637 1.98 1875 1430 1.53 1496 1.69 1559 1.86 1618 2.02 1675 2.19 2000 1471 1.72 1536 1.89 1598 2.06 1657 2.24 1713 2.41 2125 1513 1.92 1577 2.10 1638 2.28 1696 2.47 1752 2.65 2250 1555 2.13 1619 2.33 1679 2.52 1736 2.72 --- --­2375 1598 2.37 1661 2.57 1720 2.78 --- --- --- --­2500 1642 2.63 1704 2.84 --- --- --- --- --- ---
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Static Option Medium Static Option
1199
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option High Static Option
1.05 1283 1.21 1359 1.37
NOTE: For more information, see General Fan Performance Notes on page 87. Boldface indicates field ---supplied drive is required.
1. Recommend using field--- supplied fan pulley (part number KR11AZ506), motor pulley (part number KR11HY191) and belt (part number KR30AE042).
93
APPENDIX III. FAN PERFORMANCE (cont.)
48TC**07 3 Phase 6 Ton Horizontal Supply
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
CFM
F i e l d --- S u p p l i e d D r i v e
1800 913 0.64 1010 0.80 1098 0.98 1178 1.16 1252 1.35 1950 972 0.78 1065 0.96 1148 1.14 1226 1.34 1298 1.54 2100 1032 0.95 1120 1.14 1200 1.33 1275 1.54 1345 1.75 2250 1093 1.14 1177 1.34 1254 1.55 1325 1.76 1393 1.98 2400 1155 1.36 1234 1.57 1308 1.78 1377 2.01 1443 2.24 2550 1217 1.60 1293 1.82 1363 2.05 1430 2.28 1494 2.53 2700 1280 1.87 1352 2.10 1420 2.34 1484 2.59 1546 2.84 2850 1343 2.17 1412 2.42 1477 2.67 1539 2.93 1599 3.19 3000 1406 2.50 1472 2.76 1535 3.03 1595 3.29 1653 3.57
48TC
CFM
1800 1322 1.56 1388 1.77 1451 1.98 1510 2.21 1568 2.44 1950 1366 1.75 1430 1.97 1491 2.20 1550 2.43 1606 2.67 2100 1411 1.97 1473 2.20 1533 2.43 1590 2.67 1645 2.92 2250 1457 2.21 1518 2.45 1576 2.69 1632 2.94 1686 3.20 2400 1505 2.48 1564 2.73 1621 2.98 1676 3.24 1729 3.51 2550 1554 2.78 1612 3.03 1667 3.30 1721 3.57 --- --­2700 1604 3.10 1660 3.37 1715 3.64 --- --- --- --­2850 1656 3.46 --- --- --- --- --- --- --- --­3000 --- --- --- --- --- --- --- --- --- ---
NOTE: For more information, see General Fan Performance Notes on page 87. Boldface indicates field ---supplied drive is required.
1. Recommend using field--- supplied fan pulley (part number KR11AZ406), motor pulley (part number KR11HY151) and belt (part number KR29AF035).
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
Medium Static Option High Static Option
Standard Static Option Medium Static Option
48TC**07 3 Phase 6 Ton Vertical Supply
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
CFM
1800 967 0.63 1075 0.80 1170 0.97 1255 1.13 1333 1.28 1950 1029 0.77 1132 0.96 1223 1.14 1306 1.32 1382 1.49 2100 1091 0.93 1189 1.14 1278 1.33 1358 1.52 1433 1.71 2250 1154 1.11 1248 1.33 1333 1.55 1411 1.75 1484 1.96 2400 1218 1.32 1308 1.55 1390 1.78 1466 2.01 1537 2.23 2550 1283 1.55 1369 1.80 1448 2.05 1521 2.29 1590 2.52 2700 1348 1.80 1431 2.07 1507 2.33 1578 2.59 1645 2.84 2850 1414 2.09 1493 2.37 1566 2.65 1636 2.92 1701 3.19 3000 1479 2.40 1556 2.70 1627 3.00 1694 3.29 1757 3.57
CFM
1800 1406 1.43 1475 1.58 1540 1.72 1601 1.87 1660 2.00 1950 1454 1.65 1521 1.82 1585 1.98 1645 2.13 1703 2.29 2100 1502 1.89
2250 1552 2.15 1617 2.35 1678 2.54 1737 2.73 1793 2.92 2400 1603 2.44 1666 2.65 1727 2.86 1784 3.06 1839 3.26 2550 1655 2.75 1717 2.98 1776 3.20
2700 1709 3.09 1769 3.33 1827 3.57 --- --- --- --­2850 1763 3.45 --- --- --- --- --- --- --- --­3000 --- --- --- --- --- --- --- --- --- ---
NOTE: For more information, see General Fan Performance Notes on page 87. Boldface indicates field ---supplied drive is required.
1. Recommend using field--- supplied fan pulley (part number KR11AZ506), motor pulley (part number KR11HY191) and belt (part number KR29AF042).
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Static Option Medium Static Option
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option High Static Option
1568
2.07 1631 2.25 1690 2.42 1747 2.59
1833
3.42 1887 3.64
94
APPENDIX III. FAN PERFORMANCE (cont.)
48TC**08 3 PHASE 7.5 TON HORIZONTAL SUPPLY
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
CFM
2250 505 0.52 586 0.73 657 0.97 722 1.22 782 1.50 2438 533 0.62 610 0.85 679 1.09 742 1.36 800 1.65 2625 562 0.74 635 0.98 701 1.23 2813 591 0.88 661 1.13 725 1.39 783 1.68 839 1.98 3000 621 1.03 688 1.29 749 1.57 806 1.87 859 2.18 3188 652 1.21 715 1.48 774 1.77 829 2.07 881 2.40 3375 682 1.40 743 1.68 800 1.98 853 2.30 903 2.63 3563 713 1.61 772 1.91 826 2.22 878 2.55 927 2.89 3750 745 1.85 801 2.15 853 2.48 903 2.82 951 3.18
CFM
2250 838 1.81 891 2.12 941 2.46 988 2.82 1033 3.19 2438 854 1.96 906 2.28 955 2.63 1001 2.99 1046 3.37 2625 872 2.12 922 2.46 970 2.81 1016 3.17 1060 3.56 2813 890 2.31 940 2.65 986 3.01 1031 3.38 1074 3.77 3000 910 2.51 958 2.86 1004 3.23 1048 3.61 1090 4.01 3188 930 2.74 977 3.10 1022 3.47 1065 3.86 1107 4.26 3375 951 2.99 997 3.35 1041 3.74 1083 4.13 1124 4.54 3563 973 3.26 1018 3.63 1061 4.02 1103 4.43 1143 4.85 3750 996 3.55 1040 3.93 1082 4.34 1122 4.75 1162 5.18
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Static Option Medium Static Option
762
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option High Static Option
1.51 819 1.81
48TC
NOTE: For more information, see General Fan Performance Notes on page 87. Boldface indicates field ---supplied drive is required.
1. Recommend using field --- supplied fan pulley (part no. KR11AZ002) and belt (part no. KR29AF054).
48TC**08 3 PHASE 7.5 TON VERTICAL SUPPLY
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
CFM
2250 513 0.54 595 0.76 665 1.01 728 1.27 786 1.56 2438 541 0.65 620 0.89 688 1.14 750 1.42 806 1.71 2625 570 0.77 645 1.02 712 1.29 772 1.58 827 1.88 2813 600 0.91 672 1.18 736 1.46 794 1.76 848 2.07 3000 629 1.07 699 1.35 761 1.64 818 1.95 871 2.28 3188 660 1.25 726 1.54 787 1.85 842 2.17 894 2.51 3375 690 1.45 754 1.75 813 2.07 867 2.41 917 2.76 3563 721 1.67 783 1.98 840 2.32 892 2.67 941 3.03 3750 752 1.91 812 2.24 867 2.59 918 2.95 966 3.32
CFM
2250 839 1.86 889 2.18 935 2.52 980 2.87 1022 3.23 2438 858 2.02 907 2.35 953 2.70 997 3.06 1039 3.43 2625 878 2.20 926 2.54 972 2.89 1015 3.26 1056 3.64 2813 899 2.40 946 2.75 991 3.11 1033 3.49 1074 3.88 3000 920 2.62 966 2.98 1010 3.35 1052 3.74 1093 4.14 3188 942 2.86 987 3.23 1031 3.61 1072 4.01 1112 4.42 3375 964 3.12 1009 3.50 1052 3.89 1093 4.30 1132 4.72 3563 988 3.41 1032 3.80 1074 4.20 1114 4.61 1152 5.04 3750 1011 3.71 1054 4.11 1096 4.53 1135 4.95 --- ---
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Static Option Medium Static Option
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option High Static Option
NOTE: For more information, see General Fan Performance Notes on page 87. Boldface indicates field ---supplied drive is required.
1. Recommend using field --- supplied fan pulley (part no. KR11AZ002) and belt (part no. KR29AF054).
95
FAN PERFORMANCE (cont.)
48TC**09 3 PHASE 8.5 TON HORIZONTAL SUPPLY
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
CFM
F i e l d --- S u p p l i e d D r i v e
2550 497 0.48 579 0.61 651 0.75 717 0.90 777 1.05 2763 524 0.58 602 0.72 671 0.87 735 1.03 794 1.19 2975 551 0.70 626 0.86 693 1.01 754 1.18 812 1.35 3188 580 0.84 651 1.00 716 1.17 775 1.34 831 1.52 3400 609 1.00 677 1.17 739 1.35 797 1.53 851 1.71 3613 638 1.17 703 1.35 763 1.54 819 1.73 871 1.93 3825 668 1.37 730 1.56 788 1.76 842 1.96 893 2.16 4038 698 1.59 758 1.79 813 2.00 866 2.20 915 2.42 4250 728 1.83 786 2.04 839 2.26 890 2.47 938 2.70
CFM
48TC
2550 833 1.21 886 1.38 936 1.56 984 1.74 1029 1.93 2763 849 1.36 900 1.53 950 1.72 996 1.90 1041 2.10 2975 865 1.52 916 1.70 964 1.89 1010 2.09 1054 2.29 3188 883 1.70 933 1.89 980 2.09 1025 2.29 1068 2.50 3400 902 1.90 950 2.10 996 2.30 1041 2.51 1083 2.73 3613 921 2.13 969 2.33 1014 2.54 1057 2.76 1099 2.98 3825 941 2.37 988 2.58 1032 2.80 1075 3.02 1116 3.25 4038 963 2.63 1008 2.86 1051 3.08 1093 3.31 1133 3.55 4250 984 2.92 1029 3.15 1071 3.39 1112 3.63 1152 3.87
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
Medium Static Option High Static Option
Standard Static Option Medium Static Option
NOTE: For more information, see General Fan Performance Notes on page 87. Boldface indicates field ---supplied drive is required.
1. Recommend using field --- supplied fan pulley (part no. KR11AK012) and belt (part no. KR29AF055).
2. Recommend using field---supplied motor pulley (part no. KR11HY310), fan pulley (part no. KR11AZ002) and belt (part no. KR29AF054).
48TC**09 3 PHASE 8.5 TON VERTICAL SUPPLY
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
CFM
2550 526 0.51 600 0.65 666 0.79 727 0.93 783 1.07 2763 557 0.62 627 0.77 690 0.92 749 1.08 804 1.23 2975 588 0.75 655 0.91 716 1.08 772 1.24 825 1.40 3188 621 0.90 684 1.07 743 1.25 797 1.42 848 1.60 3400 653 1.06 714 1.25 770 1.44 822 1.62 872 1.81 3613 687 1.25 744 1.45 798 1.65 849 1.84 897 2.04 3825 720 1.45 775 1.67 827 1.88 876 2.09 922 2.30 4038 754 1.69 807 1.91 856 2.13 904 2.35 949 2.57 4250 788 1.94 839 2.17 886 2.41 932 2.64 976 2.88
CFM
2550 836 1.20 886 1.34 934 1.48 979 1.61 1022 1.74 2763 855 1.37 904 1.52 950 1.67 995 1.82 1037 1.97 2975 875 1.56 923 1.72 968 1.88 1012 2.04 1053 2.20 3188 897 1.77 943 1.94 987 2.11 1030 2.29 1071 2.46 3400 919 1.99 964 2.18 1007 2.36 1049 2.55 1089 2.73 3613 943 2.24 986 2.44 1029 2.63 1069 2.83 1108 3.02 3825 967 2.51 1010 2.71 1051 2.92 1090 3.13 1129 3.34 4038 992 2.80 1034 3.02 1074 3.24 1112 3.46 1150 3.68 4250 1018 3.11 1058 3.34 1097 3.57 --- --- --- ---
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Static Option Medium Static Option
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option High Static Option
NOTE: For more information, see General Fan Performance Notes on page 87. Boldface indicates field ---supplied drive is required.
1. Recommend using field---supplied motor pulley (part no. KR11HY310), fan pulley (part no. KR11AZ002) and belt (part no. KR29AF054).
96
FAN PERFORMANCE (cont.)
48TC**12 3 PHASE 10 TON HORIZONTAL SUPPLY
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
CFM
F i e l d --- S u p p l i e d D r i v e
3000 579 0.70 660 0.89 732 1.09 799 1.29 860 1.50 3250 613 0.85 690 1.06 760 1.27 823 1.49 883 1.71 3500 648 1.03 721 1.25 788 1.48 850 1.71 907 1.95 3750 683 1.23 753 1.47 817 1.71 877 1.96 933 2.21 4000 719 1.45 786 1.71 848 1.97 905 2.23 959 2.50 4250 756 1.71 819 1.98 879 2.26 934 2.53 987 2.81 4500 792 1.99 853 2.28 910 2.57 964 2.87 1015 3.16 4750 830 2.31 888 2.62 943 2.92 995 3.23 1044 3.54 5000 867 2.66 923 2.98 976 3.30 1026 3.63 1074 3.95
CFM
3000 917 1.70 970 1.91 1021 2.13 1070 2.34 1117 2.56 3250 938 1.93 991 2.16 1041 2.38 1089 2.61 1134 2.85 3500 961 2.18 1013 2.42 1062 2.66 1108 2.91 1153 3.15 3750 985 2.46 1035 2.71 1083 2.97 1129 3.23 1173 3.49 4000 1011 2.76 1059 3.03 1106 3.30 1151 3.58 1194 3.85 4250 1037 3.09 1084 3.38 1130 3.66 1174 3.95 1216 4.24 4500 1064 3.46 1110 3.76 1155 4.06 1198 4.36 1239 4.66 4750 1091 3.85 1137 4.16 1180 4.48 1222 4.80 1263 5.12 5000 1120 4.28 1164 4.61 1207 4.94 --- --- --- ---
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
Medium Static Option High Static Option
Standard Static Option Medium Static Option
48TC
NOTE: For more information, see General Fan Performance Notes on page 87. Boldface indicates field ---supplied drive is required.
1. Recommend using field --- supplied fan pulley (part no. KR11AD912) and belt (part no. KR29AF051).
2. Recommend using field--- supplied motor pulley (part no. KR11HY410).
48TC**12 3 PHASE 10 TON VERTICAL SUPPLY
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
CFM
3000 616 0.79 689 0.97 757 1.16 821 1.36 882 1.57 3250 655 0.96 724 1.16 788 1.37 849 1.58 907 1.80 3500 695 1.17 760 1.38 821 1.60 879 1.83 934 2.06 3750 736 1.41 797 1.63 855 1.86 910 2.10 963 2.35 4000 777 1.68 834 1.91 889 2.16 942 2.41 993 2.67 4250 818 1.98 873 2.23 925 2.49 976 2.75 1025 3.02 4500 860 2.32 912 2.58 962 2.85 1010 3.13 1057 3.41 4750 902 2.69 951 2.97 999 3.26 1046 3.55 1091 3.84 5000 944 3.11 991 3.40 1037 3.70 1082 4.00 1125 4.31
CFM
3000 939 1.79 994 2.01 1047 2.24 1098 2.47 1147 2.71 3250 962 2.03 1015 2.26 1066 2.50 1115 2.75 1163 3.00 3500 987 2.30 1038 2.54 3750 1014 2.60 1063 2.86 1111 3.12 1157 3.39 1202 3.66 4000 1042 2.93 1090 3.20 1136 3.48 1180 3.76 1224 4.04 4250 1072 3.30 1118 3.58 1162 3.87 1205 4.16 1247 4.46 4500 1103 3.70 1147 4.00 1190 4.29 1232 4.60 1273 4.91 4750 1135 4.14 1177 4.45 1219 4.76 1259 5.08 --- --­5000 1167 4.63 1209 4.95 --- --- --- --- --- ---
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Static Option Medium Static Option
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option High Static Option
1088
2.80 1135 3.05 1181 3.32
NOTE: For more information, see General Fan Performance Notes on page 87. Boldface indicates field ---supplied drive is required.
1. Recommend using field--- supplied motor pulley (part no. KR11HY410).
97
Pulley Adjustment
UNIT
1phase
04
3phase
1phase
05
48TC
3phase
1phase
06
3phase
07
3phase
08
3phase
09
3phase
12
3phase
APPENDIX III. FAN PERFORMANCE (cont.)
MOTOR/DRIVE
COMBO
Standard Static 854 825 795 766 736 707 678 648 619 589 560
Medium Static 1175 1135 1094 1054 1013 973 932 892 851 811 770
High Static --- --- --- --- --- --- --- --- --- --- ---
Standard Static 854 825 795 766 736 707 678 648 619 589 560
Medium Static 1175 1135 1094 1054 1013 973 932 892 851 811 770
High Static 1466 1423 1380 1337 1294 1251 1207 1164 1121 1078 1035
Standard Static 854 825 795 766 736 707 678 648 619 589 560
Medium Static 1175 1135 1094 1054 1013 973 932 892 851 811 770
High Static --- --- --- --- --- --- --- --- --- --- ---
Standard Static 854 825 795 766 736 707 678 648 619 589 560
Medium Static 1175 1135 1094 1054 1013 973 932 892 851 811 770
High Static 1466 1423 1380 1337 1294 1251 1207 1164 1121 1078 1035
Standard Static 1175 1135 1094 1054 1013 973 932 892 851 811 770
Medium Static 1466 1423 1380 1337 1294 1251 1207 1164 1121 1078 1035
High Static --- --- --- --- --- --- --- --- --- --- ---
Standard Static 1175 1135 1094 1054 1013 973 932 892 851 811 770
Medium Static 1466 1423 1380 1337 1294 1251 1207 1164 1121 1078 1035
High Static 1687 1649 1610 1572 1533 1495 1457 1418 1380 1341 1303
Standard Static 1457 1419 1380 1342 1303 1265 1227 1188 1150 1111 1073
Medium Static 1518 1484 1449 1415 1380 1346 1311 1277 1242 1208 1173
High Static 1788 1757 1725 1694 1662 1631 1600 1568 1537 1505 1474
Standard Static 747 721 695 670 644 618 592 566 541 515 489
Medium Static 949 927 906 884 863 841 819 798 776 755 733
High Static 1102 1083 1063 1044 1025 1006 986 967 948 928 909
Standard Static 733 712 690 669 647 626 604 583 561 540 518
Medium Static 936 911 887 862 838 813 788 764 739 715 690
High Static 1084 1059 1035 1010 986 961 936 912 887 863 838
Standard Static 838 813 789 764 739 715 690 665 640 616 591
Medium Static 1084 1059 1035 1010 986 961 936 912 887 863 838
High Static 1240 1218 1196 1175 1153 1131 1109 1087 1066 1044 1022
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
MOTOR PULLEY TURNS OPEN
NOTE: Do not adjust pulley further than 5 turns open.
--- F a c t o r y s e t t i n g s
98
APPENDIX IV. ELECTRICAL DATA
48TC**04 3 TONS
VOLTAGE COMP (ea) OFM (ea) IFM
V --- P h --- H z
2 0 8 --- 1 --- 6 0 187 253 16.6 79 325 1.5
2 3 0 --- 1 --- 6 0 187 253 16.6 79 325 1.5
2 0 8 --- 3 --- 6 0 187 253 10.4 73 325 1.5
2 3 0 --- 3 --- 6 0 187 253 10.4 73 325 1.5
4 6 0 --- 3 --- 6 0 414 506 5.8 38 325 0.8
5 7 5 --- 3 --- 6 0 518 633 3.8 37 325 0.6
48TC**05 4 TONS
V --- P h --- H z
2 0 8 --- 1 --- 6 0 187 253 21.8 117 325 1.5
2 3 0 --- 1 --- 6 0 187 253 21.8 117 325 1.5
2 0 8 --- 3 --- 6 0 187 253 13.7 83 325 1.5
2 3 0 --- 3 --- 6 0 187 253 13.7 83 325 1.5
4 6 0 --- 3 --- 6 0 414 506 6.2 41 325 0.8
5 7 5 --- 3 --- 6 0 518 633 4.8 37 325 0.6
RANGE
MIN MAX
VOLTAGE COMP (ea) OFM (ea) IFM
RANGE
MIN MAX
RLA LRA WAT TS FLA TYPE
RLA LRA WAT TS FLA TYPE
Max
WATTS
Std Static 1000 5.1 70% 4.9
Med Static 1000 5.1 70% 4.9
Std Static 1000 5.1 70% 4.9
Med Static 1000 5.1 70% 4.9
Std Static 1000 5.1 70% 4.9 Med Static 1000 5.1 70% 4.9 High Static 2120 5.5 80% 5.2
Std Static 1000 5.1 70% 4.9 Med Static 1000 5.1 70% 4.9 High Static 2120 5.5 80% 5.2
Std Static 1000 2.2 70% 2.1 Med Static 2120 2.7 80% 2.6 High Static 2120 2.7 80% 2.6
Std Static 1000 2.0 71% 1.9 Med Static 2120 2.1 80% 2.0 High Static 2120 2.1 80% 2.0
Max
WATTS
Std Static 1000 5.1 70% 4.9 Med Static 1850 7.4 78% 7.0
Std Static 1000 5.1 70% 4.9 Med Static 1850 7.4 78% 7.0
Std Static 1000 5.1 70% 4.9 Med Static 1000 5.1 70% 4.9 High Static 2120 5.5 80% 5.2
Std Static 1000 5.1 70% 4.9 Med Static 1000 5.1 70% 4.9 High Static 2120 5.5 80% 5.2
Std Static 1000 2.2 70% 2.1 Med Static 2120 2.7 80% 2.6 High Static 2120 2.7 80% 2.6
Std Static 1000 2.0 71% 1.9 Med Static 2120 2.1 80% 2.0 High Static 2120 2.1 80% 2.0
Max
AMP Draw
Max
AMP Draw
EFF at Full Load FLA
EFF at Full Load FLA
48TC
99
APPENDIX IV. ELECTRICAL DATA (cont.)
48TC**06 5 TONS
VOLTAGE COMP (ea) OFM (ea) IFM
V --- P h --- H z
2 0 8 --- 1 --- 6 0 187 253 26.2 134 325 1.5
2 3 0 --- 1 --- 6 0 187 253 26.2 134 325 1.5
2 0 8 --- 3 --- 6 0 187 253 15.6 110 325 1.5
2 3 0 --- 3 --- 6 0 187 253 15.6 110 325 1.5
4 6 0 --- 3 --- 6 0 414 506 7.7 52 325 0.8
48TC
5 7 5 --- 3 --- 6 0 518 633 5.8 39 325 0.6
48TC**07 6 TONS
V --- P h --- H z
2 0 8 --- 3 --- 6 0 187 253 19.0 12 325 1.5
2 3 0 --- 3 --- 6 0 187 253 19.0 12 325 1.5
4 6 0 --- 3 --- 6 0 414 506 9.7 62 325 0.8
5 7 5 --- 3 --- 6 0 518 633 7.4 50 325 0.6
RANGE
MIN MAX
VOLTAGE COMP (ea) OFM (ea) IFM
RANGE
MIN MAX
RLA LRA WAT TS FLA TYPE
RLA LRA WAT TS FLA TYPE
Max
WATTS
Std Static 1000 5.1 70% 4.9 Med Static 1850 7.4 78% 7.0
Std Static 1000 5.1 70% 4.9 Med Static 1850 7.4 78% 7.0
Std Static 1000 5.1 70% 4.9 Med Static 2120 5.5 80% 5.2 High Static 2615 7.9 81% 7.5
Std Static 1000 5.1 70% 4.9 Med Static 2120 5.5 80% 5.2 High Static 2615 7.9 81% 7.5
Std Static 2120 2.7 80% 2.6 Med Static 2615 3.6 81% 3.4 High Static 2615 3.6 81% 3.4
Std Static 2120 2.1 80% 2.0 Med Static 3775 2.9 81% 2.8 High Static 3775 2.9 81% 2.8
Max
WATTS
Std Static 2120 5.5 80% 5.2 Med Static 2615 7.9 81% 7.5 High Static 3775 10.7 81% 10.2
Std Static 2120 5.5 80% 5.2 Med Static 2615 7.9 81% 7.5 High Static 3775 10.7 81% 10.2
Std Static 2120 2.7 80% 2.6 Med Static 2615 3.6 81% 3.4 High Static 3775 5.0 81% 4.8
Std Static 2120 2.1 80% 2.0 Med Static 3775 2.9 81% 2.8 High Static 3775 2.9 81% 2.8
Max
AMP Draw
Max
AMP Draw
EFF at Full Load FLA
EFF at Full Load FLA
100
Loading...