Carrier 48SX024-048 User Manual

Page 1
Packaged Gas Heating/
Electric Cooling Units
Installation, Start-Up and
48SS018-060 48SX024-048
COMMERCIAL
UNITARY
SYSTEMS

CONTENTS

SAFETY CONSIDERATIONS ...........................
General RECEIVING AND INSTALLATION
Step 1 — Check Equipment
• IDENTIFY UNIT
• INSPECT SHIPMENT
Step 2 — Provide Unit Support.......................
• ROOF CURB
• SLAB MOUNT
• FLUSH MOUNT
Step 3 — Field Fabricate Ductwork ....
Step 4 ~ Provide Clearances...........................
Step 5 — Rig and Place Unit
• UNITS WITHOUT BASE RAIL
• UNITS WITH OPTIONAL BASE RAIL
Step 6 — Connect Condensate Drain ...
Step 7 — Install Flue Hood..............................
Step 8 — Install Gas Piping ............................
Step 9 - Install Duct Connections
• CONFIGURING UNITS FOR DOWNFLOW
Step 10 — Install Electrical Connections .
• HIGH-VOLTAGE CONNECTIONS
• SPECIAL PROCEDURES FOR 208-V
• CONTROL VOLTAGE CONNECTIONS
• HEAT ANTICIPATOR SETTING
• TRANSFORMER PROTECTION
PRE-START-UP START-UP . . MAINTENANCE START-UP CHECKLIST
.............................................................
...................
.........................
..........................
................
(VERTICAL) DISCHARGE
OPERATION
...............................................
............................
.................................................
...................................
Page
. 1-9
.. 1
10-20
. , 10
10
10
10 10
13 13 13 16
18
. . 21
21-38 39-44
. CL-1
Fig. 1 — Typical 48SS Unit Shown
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.

A WARNING

Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poi soning, fire, or an explosion which can result in personal injury or unit damage. Consult a qualified installer, service agency, or gas supplier for informa tion or assistance. The qualified installer or agency must use only factory-authorized kits or accessories when mod ifying this product.
t
NOTE TO INSTALLER — Before the installation, READ THESE INSTRUCTIONS CAREFULLY AND COM PLETELY. Also, make sure the User’s Manual and Replacement Guide are left with the unit after installation*
Before performing service or maintenance operations on unit, turn off gas supply then unit main power switch. Electrical shock could cause personal injury.

A WARNING

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical com ponents. Only trained and qualified personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func tions of cleaning coils and filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book|1 |4 PC 111 Catalog No 534-842 Printed in U S A Form 48SS,SX-2SI Pg 1 5-94 Replaces: 48SS,SX-1 SI Tab la 6a
General — The 48SS,SX units (see Fig. 1) are fully self-
contained, combination gas heating/electric cooling units designed for outdoor installation. See Fig. 2-9 for unit di mensions. All unit sizes have discharge openings for both horizontal and downflow configurations, and are factory shipped with all 4 duct openings covered. Units may be in stalled either on a rooftop or a ground-level cement slab. See Fig. 10 for roof curb dimensions.
Page 2
REQ’D CLEARANCES FOR SERVICING In. (mm) Duct panel
Unit top Side opposite ducts Compressor access (Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MAIL in (mm)
Maximum extension of overhangs ... 48 (1219) Unit top . 14 (356) Duct side of unit 0 Side opposite ducts 9 (229) Bottom of unit ... 0 Flue panel . . .30 (762)
......................
36 (914) 36 (914) 36 (914)
0
NEC REQ’D CLEARANCES in (mm) Between units, control box side 42 (1067)
Unit and ungrounded surfaces, control box side 36 (914) Unit and block or concrete walls and other grounded
surfaces, control box side .... 42 (1067)
Í n/16' (43.2)
-17 1/16'-
I (433 9) LOPTIONAL SUPPLY
CG - Center of Gravity MATL - Material
LEGEND
COND — Condenser NEC — National Electrical Code LV — Low Voltage REQ’D - Required
NOTE; Clearances must be maintained to prevent recirculation of air from outdoor-fan discharge
AIR OPENING
OPTIONAL RETURN AIR OPENING
3/16
(46 2)
7/8* (22.2) OIA CONTROL ENTRY \
UNIT
48SS180040 48SS024040 48SS024080 48SS030040 48SS030060/080 48SS036060/080 48SS036100/120 48SS042060/080 48SS042100/120
UNIT
48SS018040 48SS024040 48SS024060 48SS030040 48SS030060/080 48SS036060/080 48SS036100/120 48SS042060/080 48SS042100/120
1 1/0' C20 6) OIA. POWER ENTRY
1 5/8' (41 3) DIA
GAS ENTRY
1/2' - 14 NPT
GAS CONNECTION
ELECTRICAL
CHARACTERISTICS
F
In./mm
163/16/420 7
203/16/522.3
0 7/0' (22.23)
ALTERNATE LV ENTRY
EVAP COIL ACCESS
LEFT SIDE VIEW
FLUE PANEL
FLUE HOOD
2 5/16^
(58.0)
UNIT WEIGHT
lb kg
208/230-1-60
272
123 208/230-1-60 303 138 208/230-1-60 315 208/230-1-60 320 208/230-1-60 208/230-1-60
324 147 94/43 336 153
143 100/45
145 100/45
A B
81/37 62/28 76/35 97/44
86/39 76/35 111/50 63/29 208/230-1-60 348 158 89/40 208/230-1-60 375 170 208/230-1-60 387 176
G
In./mm
18's/i6/481.0
CENTER OF GRAVITY In./mm
X Y Z
25 07/637 27 07/688
26.98/685
26.71/678 27 15/689
20 59/523
23.35/593 23 27/591 23 46/596
22.36/568
10 85/276
95/43 86/39 119/54 75/34
98/45 89/40 122/55 78/35
27.50/698 22.48/571 27 40/696 22 44/570
22'5/ie/582.6
27.01/686 22 44/570
26.94/684
22 44/570
12 7/321
1 1/4' (31.75)
^ALTERNATE POWER ENTRY
2 3/16
(55 6)
CORNER WEIGHT
(Ib/kg)
C D
53/24
43/20
123/56
40/18 46/21 126/57 43/20 47/21 126/57 47/21
63/29 115/52 52/24
79/36 114/52 66/30
COMPRESSOR ACCESS PANEL
UNIT HEIGHT
(in./mm)
E
24 1/613 24 1/613
24.1/613 24 1/613 24 1/613
24.1/613 24 1/613
28.1/714 28 1/714
Fig. 2 - 48SS018-042 Without Base Rail, Unit Dimensions
Page 3
REQ’D CLEARANCES FOR SERVICING, in (mm) Duct panel
Unit top Side opposite ducts Compressor access ... (Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MATL in (mm) Maximum extension of overhangs
Unit top . .
Duct side of unit . ...
Side opposite ducts . . Bottom of unit Flue panel
48 (1219)
NEC REQ’D CLEARANCES in (mm) Between units, control box side
Unit and ungrounded surfaces, control box side Unit and block or concrete walls and other grounded surfaces, control box side
42 (1067)
36 (914)
42 (1067)
. . 0 36 (914) 36 (914) 36 (914)
14 (356)
. 0
9 (229)
. . .0
30 (762)
52 49 9/16'
(1320.8) (1259 3)
-45 1/2'
OPTIONAL SUPPLY AIR OPENING
OPTIONAL RETURN
AIR OPENING
^1 13/16'
(46 2)
7/8' (22.2) OIA CONTROL ENTRY
I 5/8' (41 3) DIA GAS ENTRY 1/2' - 14 NPT GAS CONNECTION
REAR VIEW
UNIT
ELECTRICAL
CHARACTERISTICS
48SS018040 208/230-1-60 48SS024040 208/230-1-60 48SS024060 208/230-1-60 48SS030040 208/230-1-60, 208/230-3-60 48SS030060/080 208/230-1-60, 208/230-3-60 48SS036060/080 208/230-1-60, 208/230-3-60, 460-3-60, 575-3-60 48SS036100/120 208/230-1-60, 208/230-3-60, 460-3-60, 575-3-60 48SS042060/080
208/230-1-60, 208/230-3-60, 460-3-60 399 181 101/46 92/42
48SS042100/120 208/230-1-60, 208/230-3-60, 460-3-60 411
UNIT
48SS018040
F
in./mmGin./mm
CENTER OF GRAVITY in./mm
X
Y Z
25 04/636 22 72/577
48SS024040 26 90/683 3 20 17/512 3 48SS024060 26 82/681 2 20.22/513 6 48SS030040 48SS030060/080 48SS036060/080
19%/504.8 22W565 4
26 57/674.9 20.1/509.3 26 93/684
21 1/535.4
27.31/693 7 21 0/532 6
13 16/334 3
48SS036100/120 27 23/691 6 21 0/533 1 48SS042060/080 48SS042100/120
23%/606 4 26V4/666 8
26 87/682 5 21 0/533 1
26.81/681 21 0/533 7
14 96/380
UNIT WEIGHT
lb
296 135 327
kg
149 103/47 49/22
339 155
106/48 52/24
CORNER WEIGHT
A B
87/40 68/31
344 157 106/48 53/24 356
162
102/46 71/32 360 164 92/42 82/37 372
169 95/43 85/39
187 104/47
CG — Center of Gravity MAT’L — Material COND — Condenser NEC — National Electrical Code LV — Low Voltage REQ'D — Required
NOTE: Clearances must be maintained to prevent recirculation of air from outdoor-fan discharge
95/43
(Ib/kg)
C D E
82/37 59/27 129/59 46/21 27 4/697 132/60 49/22 27 4/697 132/60 53/24 27 4/697 123/56 60/27 27 4/697 117/53
69/31 27.4/697 120/55 72/33 125/57
81/37 128/58 84/38 31.4/798
LEGEND
UNIT HEIGHT
(in./mm)
27.4/697
27 4/697 31 4/798
Fig. 3 — 48SS018-042 With Optional Base Rail Unit Dimensions
Page 4
o 7/8 (22.23)
ALTERNATE LV ENTRY
1 1/4 (31.75)
ALTERNATE POWER ENTRY
t
5/8 -
(16 S)
BLOWER ACCESS -
PANEL
COMPRESSOR ACCESS PANEL
RIGHT SIDE VIEW
1 13/16'
(46.2)
OPTIONAL SUPPLY AIR OPENING
-4 3/4'
(120 6)
12l5/1215/16
i
(312.7)
BURNER AND CONTROL BOX
ACCESS PANEL
REQ’D CLEARANCES FOR SERVICING, in. (mm) Duct panel . .
Unit top . Side opposite ducts Compressor access (Except for NEC requirements)
. . 0 36 (914) 36 (914) 36 (914)
REQ’D CLEARANCES TO COMBUSTIBLE MAIL in (mm) Maximum extension of overhangs . . 48(1219)
Unit top. ... ... 14(356)
Duct side of unit ... .0
Side opposite ducts .... 9 (229)
Bottom of unit Flue panel 30 (762)
......................
. . 0
NEC REQ’D CLEARANCES in (mm) Between units, control box side .42(1067)
Unit and ungrounded surfaces, control box side . . 36(914) Unit and block or concrete walls and other grounded
surfaces, control box side . . . ... 42 (1067)
y-2 3/16' ^3/4' NPT (19.0)
(55 6) DRAIN OUTLET
FRONT VIEW
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
lb
kg
48SS048080 208/230-1-60 414 188 48SS048100/120/140
208/230-1-60
426
193
48SS060080 208/230-1-60 453 206 48SS060100/120/140 208/230-1-60 465
UNIT
48SS048080 48SS048100/120/140 48SS060080 28.36/720 48SS060100/120/140
CENTER OF GRAVITY (In./mm)
X
28 76/731
28.42/722
Y
23 46/596
23.42/595 23 27/591
27 95/710
23 23/590
211
15 35/390
15.35/390
15.35/390 15 35/390
Fig. 4 — 4888048,060 Without Base Rail, Unit Dimensions
CORNER WEIGHT
(Ib/kg)
B C D
A
83/38 158/72
107/49
86/39 159/72 71/32
110/50
93/42
117/53
96/44
120/55
Z
66/30
167/76 76/35 167/76 82/37
LEGEND
CG — Center of Gravity MAT’L COND — Condenser NEC LV — Low Voltage REQ'D
NOTE: Clearances must be maintained to prevent recirculation of air from outdoor-fan discharge.
— Material — National Electrical Code — Required
Page 5
o 15/16^ 1 9/16' (23.8)„ (39.7)¿ B.
-45 1/2
ALTERNATE POWER ENTRY
1 1/4'
C31.75)
H
OPTIONAL RETURN
AIR OPENING
52 49 9/16"
(1320.0) (1259.3)
13/16
(46 2)
OPTIONAL SUPPLY AIR OPENING
REQ'D CLEARANCES FOR SERVICING, in. (mm) Duct panel
Unit top Side opposite ducts Compressor access (Except for NEC requirements)
..................
......................
36 (914) 36 (914) 36 (914)
REQ’D CLEARANCES TO COMBUSTIBLE MAIL in (mm) Maximum extension of overhangs
Unit top
...........................
Duct side of unit ... ... 0
Side opposite ducts . ... 9 (229)
Bottom of unit ... ... 0
Flue panel ... 30 (762)
. . .14 (356)
..................
48 (1219)
NEC REQ’D CLEARANCES in (mm) Between units, control box side
Unit and ungrounded surfaces, control box side 36 (914) Unit and block or concrete walls and other grounded surfaces, control box.side . . 42 (1067)
...............
42 (1067)
0
UNIT
48SS048080
48SS048100/120/140
48SS060080 48SS060100/120/140
UNIT
48SS048080 48SS048100/120/140 48SS060080 48SS060100/120/140
COMPRESSOR ACCESS PANEL
208/230-1-60, 208/230-3-60, 460-3-60, 575-3-60 438 199 113/51 89/40 164/75 72/33 208/230-1-60, 208/230-3-60, 460-3-60, 575-3-60 208/230-1-60, 208/230-3-60, 460-3-60, 575-3-60 208/230-1-60, 208/230-3-60, 460-3-60, 575-3-60
CENTER OF GRAVITY (in./mm)
X
28.54/724 9 20 00/508
28.22/716 8
28.18/715.6 27 79/705.9
ELECTRICAL
CHARACTERISTICS
Y Z
17.66/448 6
20.05/509 3
20.19/512.8
17 66/448.6
17.66/448 6
20.23/513.8 17 66/448 6
UNIT WEIGHT
lb kg
450 205 477 217 489
CG — Center of Gravity COND — Condenser LV — Low Voltage
222 126/57 102/46 173/79 88/40
NOTE: Clearances must be maintained to prevent recirculation of air from outdoor-fan discharge.
CORNER WEIGHT
(Ib/kg)
A B C D
116/53
92/42 165/75
123/56 99/45 173/79
LEGEND
MAT’L — Material NEC — National Electrical Code REQ'D — Required
77/35 82/37

Fig. 5 - 4888048,060 With Optional Base Rail, Unit Dimensions

5
Page 6
8 l/4'-<
(203.6)
OPTIONAL SUPPLY AIR OPENING
-4 13/16
(122,2)
^
12 5/16
(312 7)
OPTIONAL RETURN AIR OPENING
13/16'
(46 2)
1 1/4' 01.0) DIA
ALTERNATE POWER ENTRY
LEFT SIDE VIEW
REQ’D CLEARANCES FOR SERVICING in. (mm) Duct panel .0
Unit top 36(914) Side opposite ducts 36(914) Compressor access 36(914) (Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MAIL, in. (mm) Maximum extension of overhangs . . 48(1219)
Unit top........................... 14 (356)
Duct side of unit . .... .0
Side opposite ducts 9 (229)
Bottom of unit . . .... . . 0
Flue panel . . 30 (762) NEC REQ’D CLEARANCES in. (mm) Between units, control box side 42 (1067)
Unit and ungrounded surfaces, control box side . 36 (914) Unit and block or concrete walls and other grounded
surfaces, control box side .... .42(1067)
BLOWER ACCESS-
PANEL
5/0- ^COMPRESSOR ACCESS PANEL
UNIT
48SX024040 48SX024060 48SX030040 48SX030060/080 48SX036060/080 48SX036100/120
UNIT
48SX024040
RIGHT SIDE VIEW
ELECTRICAL
CHARACTERISTICS
208/230-1-60 333 151 208/230-1-60 208/230-1-60 208/230-1-60 348 158 208/230-1-60 366 166 94/43 208/230-1-60 378
CENTER OF GRAVITY (in./mm)
X
26.71/678 20.06/510
48SX024060 26.64/677 20.12/511
BURNER AND CONTROL BOX
ACCESS PANEL
UNIT WEIGHT
lb kg A
345 157 336 153 97/44 66/30 118/54 55/25
172
Y
Z
12 65/321 12 65/321
48SX030040 27 06/687 21 05/535 12.65/321 48SX030060/080 48SX036060/080 48SX036100/120
26.98/685 21 07/535 12.65/321
27.14/689 27 06/687
21 10/536 12 65/321 21 12/536
12 65/321
CORNER WEIGHT
B
104/47 50/23 107/49
100/45
53/24
69/31 121/55 58/26 84/38
97/44
87/40
(Ib/kg)
C
130/59 133/60
117/53 120/55
D
49/22
52/24
71/32
74/34
LEGEND
CG — Center of Gravity COND — Condenser LV — Low Voltage
NOTE: Clearances must be maintained to prevent recirculation of air from outdoor-fan discharge.
MAT’L - Material NEC — National Electrical Code REQ’D — Required
Fig. 6 — 48SX024-036 Without Base Rail, Unit Dimensions
Page 7
REQ'D CLEARANCES FOR SERVICING in (mm) Duct panel
Unit top ... .
Siete opposite ducts Compressor access (Except for NEC requirements)
REQ'D CLEARANCES TO COMBUSTIBLE MATE in (mm) Maximum extension of overhangs
Unit top Duct side of unit . Side opposite ducts Bottom of unit Flue panel
..........................
48 (1219)
NEC REQ’D CLEARANCES in. (mm) Between units, control box side
Unit and ungrounded surfaces, control box side Unit and block or concrete walls and other grounded surfaces, control box side
7/8 (22.2) OIA CONTROL ENTRY
42 (1067)
42 (1067)
36 (914) 36 (914) 36 (914)
14 (356)
. 0
9 (229)
. . 0
30 (762)
36 (914)
OPTIONAL RETURN
AIR OPENING
52 49 9/16"
(1320.8) (1259.3)
0
^1 13/16"
(46.2)
1 11/16'
(43.2)
17 1/16 -
I (433.9)
^OPTIONAL SUPPLY
AIR OPENING
1 5/8 (41 3) OIA GAS ENTRY 1/2" - 14 NPT GAS CONNECTION
REAR VIEW
UNIT
48SX024040
ELECTRICAL
CHARACTERISTICS
208/230-1-60
48SX024060 208/230-1-60 48SX030040 208/230-1-60
UNIT WEIGHT
lb
357 163 110/50 369 168 113/51 59/27 360
48SX030060/080 208/230-1-60 372
164 169 106/48 75/34 127/58 64/29
kg
LEFT 510E VIEW
A B
103/47 72/33
48SX036060/080 208/230-1-60, 208/230-3-60, 460-3-60 390 177 100/45 48SX036100/120 208/230-1-60, 208/230-3-60, 460-3-60 402
UNIT
48SX024040
CENTER OF GRAVITY (In./mm)
X Y
26 57/674 9
20 17/512 3 14 96/380 0
183 103/47 93/42 127/57
Z
48SX024060 26 51/673 3 20.22/513 6 14 96/380 0
48SX030040 26 90/683 3 21.09/535 7 14 96/380 0 48SX030060/080 26 83/681.5 21 11/536.2 14 96/380.0 48SX036060/080 26.99/685 5 21 14/537 0 14.96/380 0 48SX036100/120 26 92/683 8 21 14/537 0
14 96/380.0
Fig. 7 — 48SX024-036 With Optional Base Rail, Unit Dimensions
CORNER WEIGHT
(Ib/kg)
C D
136/62
56/25
55/25 139/63 58/26 124/56 61/28
90/41 123/56 77/35
80/36
LEGEND
CG — Center of Gravity MAT'L — COND — Condenser NEC — LV — Low Voltage REQ’D —
NOTE: Clearances must be maintained to prevent recirculation of air from outdoor-fan discharge
Material National Electrical Code Required
Page 8
RIGHT SIDE VIEW
REQ'D CLEARANCES FOR SERVICING in. (mm)
Duct panel ... . . 0
Unit top 36(914) Side opposite ducts 36 (914) Compressor access 36(914) (Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MATL in (mm) Maximum extension of overhangs
Unit top Duct side of unit . Side opposite ducts . . Bottom of unit . . Flue panel ...
. 48 (1219)
14 (356)
. 0
9 (229)
. . 0
30 (762)
NEC REQ’D CLEARANCES in (mm) Between units, control box side
Unit and ungrounded surfaces, control box side Unit and block or concrete walls and other grounded surfaces, control box side
7/8' C22.2) DIA. CONTROL ENTRY
42 (1067)
36 (914)
42 (1067)
1 1/4 (31.8) DIA
ALTERNATE POWER ENTRY
7/0 (22.2) DIA
ALTERNATE LV ENTRY
. 17 1/16'
(433.9)
OPTIONAL SUPPLY AIR OPENING
COMPRESSOR ACCESS PANEL
EVAP COIL OPTIONAL RETURN
AIR OPENING
^1 13/16'
C46.2)
UNIT
488X042060,080 488X042100,120 48SX048080
48SX048100/120/140
UNIT
48SX042060,080 48SX042100,120 48SX048080 48SX048100/120/140
• 1 5/8' (41.3) DIA GAS ENTRY
1/2' - 14 NPT
GAS CONNECTION
REAR VIEW
ELECTRICAL
CHARACTERISTICS
208/230-1-60 208/230-1-60 208/230-1-60
UNIT WEIGHT
391 403 183 103/47 94/43 123/56 422
208/230-1 -60 434 197
CENTER OF GRAVITY (in./mm)
X
26 66/677
Y Z
21 19/538
26.61/676 21.21/539 15 35/390 28 45/723 19.95/507 15.35/390
28.35/720 19 99/508 15 35/390
Fig. 8 — 488X042,048 Without Base Rail, Unit Dimensions
lb
CORNER WEIGHT
kg
A B C
178 100/45 91/41 120/55
192
109/50 85/39 112/51 88/40
CG — Center of Gravity MAT’L —
15 35/390
COND — Condenser NEC — LV - Low Voltage REQ’D -
(Ib/kg)
D
80/36
83/38 158/72 161/73
70/32
73/33
LEGEND
Material National Electrical Code Required
NOTE: Clearances must be maintained to prevent recirculation of air from outdoor-fan discharge
Page 9
10 1/16
(450 0)
5 5/0
(142.9)t
1 3/16-
(20 6)
— 10 -I
(253.0)
RIGHT SIDE VIEW
ALTERNATE POWER ENTRY
EVAP COIL ACCESS
ALTERNATE LV ENTRY
-11 1/21
(292.1)
12 13/16'.
LEFT SIDE VIEW
1 \/4
C31.75)
0 7/0
(22.23)\
13 1/2' (342.9)
ACCESS PANEL
_-3 5/16'
'^(BA.I)
37 7/16"
(950 9)
11 'S/16'
■ (207.31.4 f
1 3/8'­(34.9)
1 9/16' (23.8)„
(39.7)^ B
S2 49 g/16'
(1320.8) (1259.3)
REQ’D CLEARANCES FOR SERVICING in. (mm)
Duct panel . . ... . . 0
Unit top . . 36(914) Side opposite ducts ... 36(914)
Compressor access 36(914)
(Except for NEC requirements) REQ’D CLEARANCES TO COMBUSTIBLE MATL. in (mm)
Maximum extension of overhangs Unit top Duct side of unit . Side opposite ducts Bottom of unit Flue panel
LEGEND
CG
— Center of Gravity
COND
— Condenser
LV
— Low Voltage
MAT’L
— Material
NEC
— National Electrical Code
REQ’D
— Required
o 15/16=^
.......................
OPTIONAL RETURN
OPTIONAL SUPPLY AIR OPENING
~ 4Í7l219)
........................0
COMPRESSOR ACCESS PANEL
14 (356)
. . 9 (229)
. . 0
. . 30 (762)
AIR OPENING
13/16'
(46 2)
W
UNIT
488X042060,080 488X042100,120 488X048080
ELECTRICAL
CHARACTERI8TIC8
208/230-1-60, 208/230-3-60, 460-3-60 208/230-1-60, 208/230-3-60, 460-3-60 427 194 109/50 208/230-1-60, 208/230-3-60, 460-3-60 446 293 115/52 91/41 164/75
UNIT WEIGHT
lb kg
189 106/48
415
488X048100/120/140 208/230-1-60, 208/230-3-60, 460-3-60 458 208
UNIT
488X042060,080 488X042100,120 48SX048080 488X048100/120/140 28.16/715.3
CENTER OF GRAVITY (in./mm)
X Y Z
26.55/674 4 21 22/539 0
26.50/673.0 21.24/539.6
28.25/717 6 20 04/509 0 20 08/510 0 17.66/448 6
17 66/448.6
17.66/448.6
17.66/448.6
Fig. 9 — 488X042,048 With Optional Base Rail, Unit Dimensions
CORNER WEIGHT
A
B C D
97/44 126/57 86/39
100/45 129/59 89/40
118/54
94/43 167/76 79/36
(Ib/kg)
76/35
NOTE: Ciearances must be maintained to prevent recirculation of air from outdoor-fan discharge
NEC REQ’D CLEARANCES, in (mm) Between units, control box side
Unit and ungrounded surfaces, control box side Unit and block or concrete walls and other grounded surfaces, control box side
42 (1067)
36 (914)
42 (1067)
Page 10

RECEIVING AND INSTALLATION

Step 1 - Check Equipment

IDENTIFY UNIT — The unit model number and serial num ber are stamped on unit identification plate. Check this information against shipping papers and job data.
INSPECT SHIPMENT — Inspect for shipping damage while unit is still on shipping pallet. If unit appears to be dam aged or is torn loose from its anchorage, have it examined by transportation inspectors before removal. Forward claim papers directly to transportation company. Manufacturer is not responsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify the nearest Carrier Air Conditioning office if any item is missing.
To prevent loss or damage, leave all parts in original pack
ages until installation.

Step 2 - Provide Unit Support

ROOF CURB — Install accessory roof curb in accordance with instructions shipped with curb. See Fig. 10 for roof curb dimensions. Install insulation, cant strips, roofing, and flashing. Ductwork must be attached to curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasketing material supplied with the roof curb. Improperly ap plied gasketing can also result in air leaks and poor unit performance.
Curb should be level to within Vi inch. This is necessary for unit drain to function properly. Refer to accessory roof curb installation instructions for additional information as required.
SLAB MOUNT — Place the unit on a solid, level concrete pad that is a minimum of 4 in. thick with 2 in. above grade. The slab should be flush on the front of the unit (to allow condensate drain installation) and should extend 2 in. on the three remaining sides of the unit. See Fig. 11. Install a 6-in. gravel apron in front of condenser-air inlets to prevent obstruction of airflow by grass or shrubs. Do not secure the unit to the slab except when required by local codes.
FLUSH MOUNT — Place side of unit with duct panel flush against transition. On units with optional base rails, the skirt on duct-panel side of unit can be removed or relocated to allow unit to be mounted flush against transitions that ex tend below basepan of unit. To move skirt, proceed as follows:
1. Remove 4 screws holding skirt to base rail Retain screws.
2. Remove skirt or slide skirt inwards until alternate clear
ance holes align with base rails.
3. Secure with screws removed in Step 1. Holes align with
base rails.
To remove wood support under unit (with base rail only), loosen 4 screws above rigging holes and slide assembly out through rectangular hole.
Step 3 — Field Fabricate Ductwork — Secure all ducts to roof curb and building structure on vertical dis
charge units. Do not connect ductwork to unit. For horizon tal applications, field-supplied flanges should be attached to horizontal discharge openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be
insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with ap plicable fire codes.
A minimum clearance is not required around ductwork. Cabinet return-air static shall not exceed — .25 in. wg.
Step 4 — Provide Clearances — The required min imum operating and service clearances are shown in Fig. 2-9. Adequate combustion, ventilation, and condenser air must be provided.

A CAUTION

Do not restrict condenser airflow. An air restriction at either the outdoor-air inlet or the fan discharge can be detrimental to compressor life.
The condenser fan pushes air through the condenser coil and discharges it through the bank of louvers in the top cover, the decorative grille on the right side of the unit, and the compressor access panel. Be sure that the fan discharge does not recirculate to the condenser coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance under a partial overhang (such as a normal house overhang) is 48-in. above the unit top. The maximum horizontal extension of a partial overhang must not exceed 48 inches.
Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. Do not in stall the unit on carpeting, tile, or other combustible mate rials. The unit may be installed on wood flooring or on Class A, B, or C roof covering materials.

Step 5 — Rig and Place Unit

A CAUTION

When installing the unit on a rooftop, be sure the roof will support the additional weight. Refer to Fig. 2-9 for corner weight information.
Use spreader bars or crate top when rigging the unit. The units must be rigged for lifting as shown in Fig. 12 and 13 Refer to Tables 1 and 2 for operating weight and to Fig. 2-9 for corner weights. Use extreme caution to prevent damage
when moving the unit. Unit must remain in an upright po sition during all rigging and moving operations. The unit
must be level for proper condensate drainage; therefore, the
ground-level pad or accessory roof curb must be level be fore setting the unit in place. When a field-fabricated sup
port is used, be sure that the support is level and properly
supports the unit.
t
10
Page 11
FLAT
PITCHED
PART NUMBER
50SS900015 50SS900016 50SS900017
“A”
8" [203] 11" [279] 14" [356]
50SS900019 8" [203] 50SS900020 50SS900021 50SS900022 50SS900023 50SS900024
8" [203] 13«/ie" [344]
8" [203] 16%" [416]
8" [203] 19V4" [489]
8" [203] 22%" [568]
8" [203] 25%" [651]
“B” PITCH
-
10%" [276]
1:12 2:12 3:12
4.12 5:12 6:12
NOTES:
Roof curb must be set up for unit being instaiied
1
Seai strip must be applied as required for unit being instaiied.
2
Dimensions in [ ] are in miilimeters
3
Roof curb is made of 16 gage steel
4
Attach ductwork to curb (flanges of duct rest on curb).
5
Service ciearance 4 ft on each side
6.
7 Direction of airfiow.
8. Insulated panels: 1-in. thick fiberglass 1 lb density.
Fig. 10 — Roof Curb Dimensions
11
Page 12
20
FLUSH WITH SLAB-
'1
■ ^ -I T
___
^
2 0
r
J
Hook rigging shackles through holes in lifting brackets, as shown in
Detail “A ” Lifting brackets to be centered around the unit center of gravity. Use wood top skid when rigging, to prevent rigging straps from damaging unit. Remove 4 screws to slide wood support through
rectangular hole in rail

A CAUTION

All panels must be in place when rigging.
12 0”
CONCRETE SU\B-

Fig. 11 - Slab Mounting Details

SECURE SCREW
AGAINST BASEPAN
TO HOLD LIFTING
BRACKET IN PLACE
DETAIL A
Hook rigging shackles through holes in lifting brackets, as shown in Detail “A.” Lifting brackets to be centered around the unit center of gravity Use wooden top skid when rigging, to prevent rigging straps from damaging unit

A CAUTION

All panels must be in place when rigging.
UNIT
48SS
Size lb
018 024 030 036 042 447 203 048 060
UNIT
48SX
024 405 030 408 185 036 438 199 042 048 494 224
MAX
WEIGHT
kg
332 150 375 170 384 174 408 185
486 220
525 238
184
210
463
A
mm in. mm in. mm
in.
49 4 1255 22.0 559 24.85 631
40.4 1255
B
24.3
618
22 4
570 24.85 631 565 24 85
22.3
22.5 570.7
21.0 533
21.5 545
22 8
579 28.9 733
22 4
569 28.9 733
22.4
569 28.9 733
22.8 579 34.9 885
21.1
536 34.9 885
C
24 85
631 631
28.85 733
34.85 885
34.85 885
UNIT
48SS
Size lb
018 024 030 036 042 435 197 048 474 215 060 513 233
UNIT
48SX
024 393 178 030 396 180 036 426 193 49 4 042 451 205 048 482 219
MAX
WEIGHT
in.
kg
145
320
165
363
172
380 396 180 49 4
A B C
mm in. mm in. mm
24.4 619
22.6 574 28.2 715
22.5 571 28.2 715
1255 22.2
22.6 574 32.2 816
21.2 538 38.2 969
21.6 549 38.2 969
22.9
22.6 574
1255 22.5
22.9
21.3 540
28.2
28.2 715
563
582 32.2
32.2 571 32.2 582 38.2
38.2
715
816 816 816 969 969
Fig. 13 - Suggested Rigging For Units With
Optional Base Rail
UNITS WITHOUT BASE RAIL - If accessory rigging brackets are to be used for rigging, install them as follows:

A WARNING

Secure screws and paint protectors solidly against unit basepan to hold lifting brackets in position.
Never use lifting brackets when the temperature is be low -10 F.
Never exceed 200 lbs per bracket of lifting force. Never use lifting brackets for lifting other models of
air-conditioning units. Lifting point should be directly over the unit center of
gravity.
1. Position brackets as close to the corners of unit as pos sible. Be sure brackets are well outside of center of grav ity. (See Fig. 2, 4, 6, 8, and 12.).
2. Position paint protectors and foam strips between screws and painted surface of unit. Tighten screws until they make contact with the paint protectors.
3. Secure device or hook of sufficient strength to hole in bracket as shown in detail “A” of Fig. 12.
4. If wood top is available, use it for a spreader bar to pre vent straps from damaging unit. If wood top is not avail able, use spreader bars of sufficient length.
12
Page 13
UNITS WITH OPTIONAL BASE RAIL - Lifting holes are provided in optional base rail as shown in Fig. 12. Op erating weights are shown in Tables 1 and 2. Refer to Rig ging instructions on unit.
Protective wood support must be removed from unit be fore unit is mounted to curb. Remove 4 screws that secure support above rigging holes in rails. Slide support out through rectangular hole in rail. See Fig. 13.

Step 6 — Connect Condensate Drain

NOTE: When installing condensate drain connection be sure to comply with local codes and restrictions.
Model 48SS,SX disposes of condensate water through a
¥4 in. NPT fitting which exits through the compressor ac
cess panel. See Fig. 2-9 for location.
Install field-supplied condensate trap at end of conden sate connection to ensure proper drainage. See Fig. 14.
V'MIN.
If the installation requires draining the condensate water away from the unit, install a 2-in. trap at the condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. lower than the drain-pan condensate connection to prevent the pan from overflow ing. Prime the trap with water. Connect a drain tube using a minimum of y4-in. PVC or V4-m. copper pipe (all field­supplied) at the outlet end of the 2-in. trap. Do not under size the tube. Pitch the drain tube downward at a slope of at least one in. for every 10 ft of horizontal run. Be sure to check the drain tube for leaks.
Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground-level installations. When using a gravel apron, make sure it slopes away from the unit.
Step 7 — Install Flue Hood — The flue hood as
sembly is shipped screwed to the control box in the burner compartment. Remove the burner access panel to locate the assembly.

A CAUTION

The venting system is designed to ensure proper vent ing. The flue hood assembly must be Installed as indi cated in this section of the unit installation instructions.
Install the flue hood as follows:
1. Remove from shipping location. Place vent cap assem bly over flue panel. Orient screw holes in vent cap with holes in the flue panel.
2. Secure flue hood to flue panel by inserting a single screw on the right side, the left side, and the top of flue hood.
Step 8 — Install Gas Piping — The gas supply pipe
enters the unit through the access hole provided. The gas connection to the unit is made to the '/2-in. FPT gas inlet on the manual shutoff or gas valve.
Install a gas supply line that runs to the heating section. Refer to Table 3 and the National Fuel Gas Code (NFGC) for gas pipe sizing. mended that a black iron pipe is used. Check the local util ity for recommendations concerning existing lines. Size gas supply piping for 0.5 in. wg maximum pressure drop. Never
use pipe smaller than the Vi-in. FPT gas inlet on the unit gas valve.
For natural gas applications, the gas pressure at unit gas connection must not be less than 4.0 in. wg or greater than
13 in. wg while the unit is operating. For propane applica tions, the gas pressure must not be less than 4.0 in. wg or greater than 13 in. wg at the unit connection.
When installing the gas supply line, observe local codes pertaining to gas pipe installations. Refer to the NFGC ANSI (American National Standard’s Institute) Z223.1-1988 NFPA (National Fire Protection Association) latest edition (in Canada, CAN/CGA B149.1, (2)-M86). In the absence of local building codes, adhere to the following pertinent recommendations :
1. Avoid low spots in long runs of pipe. Grade all pipe
'/4 inch in every 15 ft to prevent traps. Grade all hori
zontal runs downward to risers. Use risers to connect to heating section and to meter.
2. Protect all segments of piping system against physical
and thermal damage. Support all piping with appro priate straps, hangers, etc. Use a minimum of one hanger every 6 ft. For pipe sizes larger than ommendations of national codes.
3 Apply joint compound (pipe dope) sparingly and only to
male threads of joint when making pipe connections. Use only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and/or national codes.
Never use Teflon tape.
4. Install sediment trap in riser leading to heating section per Fig. 15. This drip leg functions as a trap for dirt and condensate.
5. Install an accessible, external, manual main shutoff valve in gas supply pipe within 6 ft of heating section.
6. Install ground-joint union close to heating section be tween unit manual shutoff and external manual main shut off valve.
7. Pressure-test all gas piping in accordance with local and national plumbing and gas codes before connecting pip ing to unit.
NOTE: Pressure test the gas supply system after the gas supply piping is connected to the gas valve. The supply piping must be disconnected from the gas valve during the testing of the piping systems when test pressure in excess of 0.5 psig. Pressure test the gas supply piping
system at pressures equal to or less than 0.5 psig. The
unit heating section must be isolated from the gas piping
system by closing the external main manual shutoff valve
and slightly opening the ground-joint union.
Do not use cast-iron pipe. It is recom
'/2 in., follow rec
13
Page 14
Table 1 — Physical Data — Unit 48SS
UNIT SIZE 48SS NOMINAL CAPACITY (ton) OPERATING WEIGHT (lb)
Without Base Rail With Optional Base Rail
COMPRESSORS
Quantity
REFRIGERANT (R-22)
Charge (lb)
REFRIGERANT METERING DEVICE Aoutrol™ Device
Orifice ID (in.)
CONDENSER COIL
Rows...Fins/in. Face Area (sq ft)
CONDENSER FAN
Nominal Cfm Diameter (in.) Motor Hp (Rpm)
EVAPORATOR COiL
Rows Fins/in. Face Area (sq ft)
EVAPORATOR FAN
Nominai Airflow (Cfm) Size (in.)
FURNACE SECTION*
Burner Orifice No. (Qty...driii size)
Naturai Gas
Burner Orifice No. (Qty...drill size)
Propane Gas
RETURN-AiR FILTERS (in.)f
Throwaway
018040 024040
1V2 2 2 272 303 315 320 324 324
296
Rotary Reciprocating
1 2 60 2 75 2 75 3 40 3 40 3 40 .030
1. .17 1. .17
5.95
1700
18 18
Vs (850) Vs (850)
3 15
1 83 2 29 600
10 X 10 10 X 10
1. 32 1 32 2 38 1 ..32
1...41 1 .41
20 X 20 20 X 20 20 X 20 20 X 24 20 X 24 20 X 24 20 X 24
327
.030 030 030 .030 .030 032
5 95 5 95 5 95 5.95 5 95 5 95
1700 1700 1900 1900 1900 1900
3 15 3 15
800 800 1000 1000 1000 1200
024060 030040 030060 030080 036060
339 344 356 356
1. .17 2. .17 2. .17
18 18 18 18 18
Va (850) Va (850) Va (850)
2 29
10 X 10
2 46
2V2 2V2 2V2
1
2...17
Va (850)
3 .15
2.29
10 X 10
1...41 2.. 46 2 42 2. 46
3 . 15 3.. 15 3 15
2 29 2 29 3 06
Direct Drive
10 X 10
2 38
10 X 10 10 X 10
2 32
3
336 360
4 30
2. .17 2. .17 2. .17
'A (1050)
2 38 2. 32
036080 036100
3 3
336 348 348 360
4 30
032
5 95 5 95 5 95
1900 1900 1900
18 18 18
'A (1050) '/4 (1050) 'A (1050)
3 15 3 15 3 15 3 06 3 06 3.06
1200 1200 1200
10 X 10 10 X 10 10 X 10
2 42 3 44
20 X 24 20 X 24 20 X 24
036120
3
372 372
4 30
032
3 36 3 32
4.30 .032
2. .17
3 42
t
UNIT SIZE 48SS NOMINAL CAPACITY (ton) OPERATING WEIGHT (lb)
Without Base Raii
With Optionai Base Rail
COMPRESSORS
Quantity
REFRIGERANT (R-22)
Charge (lb)
REFRIGERANT METERING Acutroi' Device
DEVICE
Orifice ID (in.)
CONDENSER COIL
Rows...Fins/in. Face Area (sq ft)
CONDENSER FAN
Nominal Cfm Diameter (in.) 18 Motor Hp (Rpm) 'A (1050)
EVAPORATOR COIL
Rows Fins/in. 3. .15 Face Area (sq ft)
EVAPORATOR FAN Direct Drive
Nominal Airflow (Cfm) Size (in.)
FURNACE SECTiON*
Burner Orifice No.
(Qty...driii size)
Natural Gas
Burner Orifice No.
(Qty...driil size)
Propane Gas
RETURN-AIR FILTERS (in.)t
Disposable
•Based on altitude of 0-2000 feet tRequired filter sizes shown are based on the larger of the ARI (Air Conditioning & Refrigeration Institute) rated
cooling airflow or the heating airflow at a velocity of 300 ft/min for disposable type or 450 ft/min for high-capacity
type Air filter pressure drop must not exceed 0 08 in wg
**Sq inch. Filter is mounted external to unit
042060 042080 042100 042120 048080 048100 048120 048140
3'/2
375 375 387 387 414 399
5 20
034 .034
2. .17 2. .17 2. 17
7.04 7 04 1900
3 33 3.33 1400 1400
10 X 10 10 X 10 10 X 10
2. 38 2 32
2. 46
24 X 24
3V2
399 411 411
Reciprocating
5 20
1900
18
'A (1050)
3. .15
2 42
24 X 24
3Va 3'/2 4 4 4 4
5.20 5 20 6.50 6 50
034 034 030 030
7.04 7 04 8.67 8 67 8 67 8 67
1900 1900 2400
18 18 20 20
'A (1050) '/4 (1050) Vs (1050)
3. .15 3...15 3.. 15 3. 15 3. 15 3. 15 4. 15 3 33 3.33 4 44 4.44 4.44 4.44
1400 1400 1600 1600 1600 1600
3 36 3.32
3 44
24 X 24 24 X 24 24 X 30 24 X 30
438 450 450 450 477
2...17 2...17 2. 17
10 X 10 10 X 10 10 X 10 10 X 10 10 X 10
2 32
3 42
2 42
426 426 426 453
6 50
030
2. .17
2400 2400 2400
Vs (1050) V3 (1050) Vs (1050) Vs (1050) Vs (1050) V3 (1050) Vs (1050)
*
*
3 36 3.. 32 3.. 30
3 44 3 42 3 40
20
24 X 30 816** 24 X 30
060080 060100 060120 060140
Hermetic Scroii
6 50
030
2. 17
20
7 00
030
2. .17 8 67 8 67 8 67 8 67
2400 2400 2400 2400
4.44 4.44 4.44 4.44
1995 1995 1995
10 X 10 10 X 10 10 X 10 10 X 10
2 32 3. 36 3.32
3 42 3. 44 3.42 3 40
5
20
5
465 489
7 00 7 00 7 00
030 030 030
2. .17 2. .17 2. .17
20
4.. 15 4.. 15 4. 15
24 X 30 24 X 30 960**
5 5
465 465 489 489
20
20
1995
3 30
14
Page 15
Table 2 — Physical Data — Unit 48SX
UNIT SIZE 48SX NOMINAL CAPACITY (ton) 2 OPERATING WEIGHT (lb)
Without Base Rail With Optional Base Rail
COMPRESSORS
Quantity
REFRIGERANT (R-22)
Charge (lb)
REFRIGERANT METERING DEVICE Acutrol'“ Device
Orifice ID (In.) 034
CONDENSER COIL
Rows...Fins/in. 2.. 17 Face Area (sq ft)
CONDENSER FAN
Nominal Cfm 2200 2200 Diameter (in.) 20 Motor Hp (Rpm) У4 (1100) '/4 (1100) У4 (1100) У4 (1100)
EVAPORATOR COIL
Rows Fins/in. Face Area (sq ft) 36 3.6 2 7 2.7 27 36
EVAPORATOR FAN
Nominal Airflow (Cfm) 800 Size (in.)
FURNACE SECTION*
Burner Orifice No. (Qty...drill size)
Natural Gas
Burner Orifice No. (Qty...drlll size)
Propane Gas
RETURN-AIR FILTERS (in.)t
Disposable
024040 024060
333 345 357 369
39 39
7.0 70
2. .15 2 15
10 X 10 10 X 10 10 X 10 10 X 10 10 X 10 10 X 10 10 X 10 10 X 10 10 X 10
1 32
1 41
24 X 24 24 X 24 24 X 24 24 X 24 24 X 24 24 X 24 24 X 24 24 X 24 24 X 24
2
.034 .030 030
2.. 17
20
800
2 38 2 46
030040
2Уг
336 360
4.5 45
2.. 17 2.. 17 70 70
2200 2200 2200 2200
20
3 15 3 15 3 15 4 15
1000 1000 1000
1 32
1 .41 2 .46 2.42 2. .46 2 42 3 ..44
030060
2Уг 2Уг 3
348 348 366 372 372 390
20 20
2 38
030080
Scroii
45 54
030 032
2.. 17 70
У4 (1100)
Direct Drive
2 32
036060
2.. 17 70
20
У4 (1100)
1200 1200 1200 1200
2 38
036080 036100 036120
3 3 3
366 390 402
5.4 032
2.. 17 2.. 17 2.. 17 70 7.0 70
2200 2200
20 20 20
У4 (1100) У4 (1100) У4 (1100)
4. 15 4 .15 4 15 36
2 32
378 378
54 5.4
032 .032
3.6
3 36 3 32
402
2200
36
3 42
m
UNIT SIZE 48SX NOMINAL CAPACITY (ton) ЗУг ЗУ2 ЗУ2 ЗУ2 4 4 4 4 OPERATING WEIGHT (lb)
Without Base Rail With Optional Base Rail
COMPRESSORS
Quantity
REFRIGERANT (R-22)
Charge (lb)
REFRIGERANT METERING
DEVICE
Orifice ID (in.)
CONDENSER COIL
Rows...Fins/in. 2.. 17 2.. 17 2.. 17 2.. 17 2.. 17 2.. 17 2.. 17 2.17 Face Area (sq ft)
CONDENSER FAN
Nominal Cfm Diameter (in.) Motor Hp (Rpm)
EVAPORATOR COIL
Rows Fins/in. Face Area (sq ft)
EVAPORATOR FAN Direct Drive
Nominal Airflow (Cfm) Size (in.)
FURNACE SECTION*
Burner Orifice No.
(Qty...drill size)
Natural Gas
Burner Orifice No.
(Qty...drill size)
Propane Gas
RETURN-AIR FILTERS (in.)t
Disposable
*Based on an altitude of 0-2000 feet fRequired filter sizes shown are based on the ARI (Air Conditioning & Refrigeration Institute) rated heating airflow at
a velocity of 300 ff/min for disposable type or 450 ft/min for high-capacity type Air filter pressure drop must not exceed 0.08 in. wg
**Sq inch Filter is mounted external to unit.
042060
391 391 403 403 422 434 434
415 415 427 427 446 458
5.7
034 034 034 .034 .034 034 034
87
2400 2400 2400 2400 2400 2400 2400
20 20 20 20 20 20
3...15
4.4 44 44 44 44
1400
lOx 10 10 X 10 10 X 10 10 X 10 10 X 10
2. .38 2 32 3 36 3 .32 2 ..32
2 46 2 42 3 44 3 42
24 X 30
042080 042100 042120 048080 048100 048120
Scroll
1
5 7
8.7 87 8.7 8.7 8.7 87
3 . 15 3.15 3 . 15
1400 1400 1400 1600 1600
24 x30
57 57 58
Acutrol" Device
24 X 30 24 X 30
4.15
2 .42
24 X 30
5 8 5.8 5.8
4.. 15 4.15
4.4 4.4 44
10 X 10 10 X 10 10 X 10
3 36 3 32 3.. 30
3 44 3 42 3.. 40
24 X 30 24 X 30 816**
458 458
20 20
1600 1600
048140
434
.034
8 7
2400
4 ..15
m
15
Page 16
(Text continued from page 13)

A CAUTION

Unstable operation may occur when the gas valve and manifold assembly are forced out of position while connecting improperly-routed rigid gas pip ing to the gas valve. Use a backup wrench when making connection to avoid strain on, or distortion of, the gas control piping.

A CAUTION

If a flexible conductor is required or allowed by the authority having jurisdiction, black iron pipe shall be installed at the gas valve and shall extend a min imum of 2 in. outside the unit casing.

A WARNING

Never use a match or other open flame when check ing for gas leaks. Never purge gas line into com bustion chamber. Failure to follow this warning could result in an explosion causing personal injury or death.
8. Check for gas leaks at the field-installed and factory­installed gas lines after all piping connections have been completed. Use soap-and-water solution (or method spec ified by local codes and/or regulations).
IN
CONFIGURING UNITS FOR DOWNFLOW (VERTICAL) DISCHARGE

A WARNING

Before performing service or maintenance operations on the system, turn off main power to unit or electrical shock could result.
1. Open all electrical disconnects before starting any serv ice work.
2. Remove return duct cover located on duct panel. Figure 16 shows duct cover removed. Save duct cover and screws.
3. Locate lances in basepan insulation that are placed over the perimeter of the vertical duct opening cover (Fig. 17).
4. Using a straight edge and shop knife, cut and remove the insulation around the perimeter of the cover. Remove and save 5 screws securing the cover to the basepan and slide out the cover. Discard the cover (Fig. 18).
5 Remove supply duct cover located on duct panel.
Figure 16 shows duct cover removed. Save duct cover and screws.
6. Remove and discard 2 screws which secure vertical dis charge opening cover to basepan (Fig. 19). Slide cover forward to disengage, then tilt and remove cover through vertical discharge opening in bottom of unit. Discard duct cover (Fig. 20).
i
Step 9 — Install Duct Connections — The unit
has duct flanges on the supply- and return-air openings on the side and bottom of the unit. See Fig. 2-9 for connection
sizes and locations.

A CAUTION

Collect ALL screws that were removed. Do not leave screws on rooftop as permanent damage to the roof may occur.
7. If unit ductwork is to be attached to vertical opening flanges on the unit basepan (jackstand applications only), do so at this time.
8. It is recommended that the basepan insulation around the perimeter of the vertical return-air opening be se cured to the basepan with aluminum tape. Applicable local codes may require aluminum tape to prevent ex posed fiberglass.
Cover both horizontal duct openings with the duct cov
9. ers from Steps 2 and 5. Make sure opening is air- and watertight.
10
After completing unit conversion, perform all safety checks and power up unit.
NOTE: The design and installation of the duct system must be in accordance with the standards of the NFPA for instal
lation of nonresidence-type air conditioning and ventilating systems, NFPA 90A or residence-type, NFPA 90B; and/or
local codes and residence-type, NFPA 90B; and/or local codes
and ordinances.
16
Page 17
Table 3 — Maximum Gas Flow Capacity*
NOMINAL
IRON PIPE,
SIZE
(In.)
V2 .622
% .824
1
1V4 1.380 1400
IV2
‘Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or iess. Pressure drop of 0 5-in. wg
(based on a 0.60 specific gravity gas). Ref: Tabie C-4, Nationai Fire Protection Association NFPA54.
fThis iength inciudes an ordinary number of fittings.
INTERNAL DIAMETER
(In.)
1 049 680 465 375 320 285 260 240 220 205
1.610 2100 1460 1180 990
10 20 30 40
175 120 97 360 250 200 170
950 770
82 73 66 61
600 580 530 490 460
LENGTH OF PIPE, FTf
50 60 70 80
57
151 138 125 118
900 810
750 690 650
90 100
53 50 44
110
430
125
150 175
40 103 93 84 77 72 195 175 400 360 325 620
160 145 135
550 500 460 430
200
300 280
SUPPLY DUCT
OPENiNG
RETURN DUCT
OPENiNG
Fig. 16 — Supply and Return Duct Openings
Fig. 18 — Vertical Duct Cover Removed
M.
Fig. 17 - Lance Location for Vertical Duct
Opening Cover
Fig. 19 — Removal of Vertical Discharge
Opening Cover
17
Page 18
Fig. 20 — Vertical Discharge Cover Removed
Adhere to the following criteria when selecting, sizing,
and installing the duct system:
1. Units are shipped with all 4 duct openings covered. Re move appropriate panels for intended installation.
2. Select and size ductwork, supply-air registers, and return-air grilles according to American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) recommendations.
3. Use flexible transition between rigid ductwork and unit to prevent transmission of vibration. The transition may be screwed or bolted to duct flanges. Use suitable gas kets to ensure weathertight and airtight seal.
4. All units must have field-supplied filters or accessory filter rack installed in the return-air side of the unit. Rec ommended sizes for filters are shown in Tables 1 and 2.
5. Size all ductwork for maximum required airflow (either heating or cooling) for unit being installed. Avoid abrupt duct size increases or decreases or performance may be affected.
6. Adequately insulate and weatherproof all ductwork located outdoors. Insulate ducts passing through uncon ditioned space, and use vapor barrier in accordance with latest issue of Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors of America (ACCA) mini mum installation standards for heating and air condition
ing systems. Secure all ducts to building structure.
7. Flash, weatherproof, and vibration-isolate all openings
in building structure in accordance with local codes and good building practices.
Step 10 — Install Electrical Connections

A WARNING

The unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of per
sonal injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground lug in the control compartment, or conduit ap proved for electrical ground when installed in accor dance with NEC (National Electrical Code) ANSI/ NFPA (latest edition) (in Canada, Canadian Electrical
Code CSA [Canadian Standards Association] C22.1)
and local electrical codes. Do not use gas piping as an
electrical ground. Failure to adhere to this warning could result in personal injury or death.

A CAUTION

Failure to follow these precautions could result in dam
age to the unit being installed:
1. Make all electrical connections in accordance with NEC ANSI/NFPA (latest edition) and local electrical codes governing such wiring. In Canada, all electrical connec tions must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between field­supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE.
3. Be sure that high-voltage power to unit is within oper ating voltage range indicated on unit rating plate.
4. Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc. On 3-phase units, ensure phases are balanced within 2 per cent. Consult local power company for correction of im proper voltage and/or phase imbalance.
HIGH-VOLTAGE CONNECTIONS - The unit must have a separate electrical service with a field-supplied, water proof, disconnect switch mounted at, or within sight from, the unit. Refer to the unit rating plate for maximum fuse/ circuit breaker size and minimum circuit amps (ampacity) for wire sizing. See Table 4 for electrical data.
The field-supplied disconnect switch box may be mounted on the unit over the high-voltage inlet hole when the standard power and low-voltage entry points are used. See Fig. 2-9 for acceptable location.
Standard Power Entry — Proceed as follows to complete the high-voltage connections to the unit:
1. Connect ground lead to chassis ground connection when using separate ground wire.
2. Run high-voltage leads into unit control box.
3. Locate black and yellow wires connected to line side of contactor.
4. Cut wires at partition where they exit control box.
5. Strip back leads and connect to high voltage leads. On 3-phase units, blue wire is provided stripped back and ready to connect to high voltage lead. See unit wiring label and Fig. 21.
i
18
Page 19
THERMOSTAT (TYPICAL)
(^(y)(^(R)0
LEADS (SEE UNIT
WIRING LABEL)
LEGEND
---------
Field Control-Voltage Wiring
-------
— Field High-Voltage Wiring
NOTE: Use biue wire for 3-phase units only
Fig. 21 — High- and Control-Voltage Connections
Alternate Power Entry
Remove knockouts in fixed compressor panel located on duct panel side of unit.
Route high-voltage leads into high-voltage terminal box. Connect ground wire to green-yellow wire using field-
supplied splice. Connect power wires to unit high-voltage leads. On 3-phase units, locate blue wire projecting from com
pressor junction box. Cut wire at partition and route into high-voltage junction box through grommet in back of junction box.
On 3-phase units, strip back blue lead and connect to
6.
third leg of the power wires.
SPECIAL PROCEDURES FOR 208-V OPERATION

A WARNING

Make sure that the gas supply then the power supply to the unit is switched OFF before making any wiring changes. Electrical shock can cause personal injury or death.
Disconnect the orange transformer-primary lead from the contactor. See unit wiring label.
Remove the tape and wirenut from the terminal on the end of the red transformer-primary lead.
Save the wirenut. Connect the red lead to the contactor terminal from which
the orange lead was disconnected. Using the wirenut removed from the red lead, insulate
the loose terminal on the orange lead. Wrap the cover with electrical tape so that the metal ter
6.
minal cannot be seen.
CONTROL VOLTAGE CONNECTIONS - Locate the room thermostat on an inside wall in the space to be conditioned, where it will not be subjected to either a cooling or heating
source or direct exposure to sunlight. Mount the thermostat
4 to 5 ft above the floor NOTE. Do not use any type of power-stealing thermostat.
Unit control problems may result.
Use no. 18 American Wire Gage (AWG) color-coded, insulated (35 C minimum) wires to make the control volt age connections between the thermostat and the unit. If the thermostat is located more than 100 ft from the unit (as measured along the control voltage wires), use no. 16 AWG color-coded, insulated (35 C minimum) wires.
Standard Connection — A grommeted, control-voltage in let hole is located in the flue panel adjacent to the control access panel. See Fig 2-9. Provide a drip loop before run ning wire through panel.
Run the low-voltage leads from the thermostat, through the inlet hole, and into unit low-voltage splice box.
Locate five 18-gage wires leaving control box. These low­voltage connection leads can be identified by the colors red, green, yellow, brown, and white). (See Fig. 21.) Cut wires at the point where they exit control box. On 48SX024,030, do not cut yellow wire. Stripped yellow lead is located in connection box. Ensure the leads are long enough to be routed into the low-voltage splice box located below the right side of the control box. Route leads through hole in bottom of control box and make low-voltage connections as shown in Fig. 21. Secure all cut wires, so that they do not interfere with operation of unit.
Alternate Connection — Remove knockout in compressor fixed panel located below high-voltage knockout. Remove rubber grommet from standard low-voltage power entry and install it in hole left when knockout was removed. Route thermostat wires through grommet providing drip loop at panel Connect low-voltage leads as shown in Fig. 21. On 48SX024 and 030 units, the yellow wire originating from discharge thermostat of compressor must be cut and routed into low-voltage section of junction box.
HEAT ANTICIPATOR SETTING - The room thermostat heat anticipator must be properly adjusted to ensure proper heating performance. Set the heat anticipator, using an am meter between the W and R terminals to determine the exact required setting.
NOTE: For thermostat selection purposes, use 0.18 amp for the approximate required setting.
Failure to make a proper heat anticipator adjustment will result in improper operation, discomfort to the occupants of the conditioned space, and inefficient energy utilization; however, the required setting may be changed slightly to provide a greater degree of comfort for a particular installation.
Recommended thermostats are as follows:
TYPE
Single-Stage Heating and Cooling Manual Changeover
Auto. Changeover
•Recommended for use with subbase HH93AZ040
tRecommended for use with subbase HH93AZ176
PART NO.
HH01AD040* HH01AD046 HH01PC184
HH07AT174t
HH01PC185
TRANSFORMER PROTECTION - The unit transformer
protection may be one of 2 types.
The first transformer type may contain an auto, reset over current protector for control circuit protection. If this de vice trips, it may reset without warning, starting the heat ing or cooling section of this product. Use caution when servicing; if overcurrent protector continues to trip, there is a problem in the low-voltage electrical circuit, such as an electrical short, ground, or transformer overload. Discon nect power, correct the condition, and check for normal unit operation.
The second transformer type is of the energy-limiting type. It is set to withstand a 30-second overload or shorted secondary condition.
19
Page 20
Table 4 — Electrical Data
UNIT 48SS
018
024 030 036
042 048 060
030
036
042
048 060
036 042
048
060
UNIT 48SX
024
030
036
042
048 036
042 048
036 042 048
AWG — American Wire Gage COND — Condenser FLA — Fail Load Amps HACR — Heating, Air Conditioning and Refrigeration LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection RLA — Rated Load Amps
‘Fuse or HACR breaker NOTES:
1. in compliance with NEC (Nationai Electricai Code) requirements for muitimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The CGA (Canadian Gas Association) units may be fuse or circuit breaker
2. Minimum wire size is based on 60 C copper wire, if other than 60 C wire is used, or if iength exceeds wire length in table, de termine size from NEC.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt age is greater than 2%. Use the following formula to determine
the percent of voltage imbalance.
V-PH-HZ
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
LEGEND
VOLTAGE
RANGE
Max RLA
Min
187 253 18.0
253
187
414
506
253
187
253 13.9 88.0
187
506 6.8
414
COMPRESSOR
LRA FLA
7.6 45.0 07 1 8 12.0 15
12.4 61.0 07 20 18.2 30
14.4
20.4
26.4
32.1
9.4
11 7
140 91 0 150 99 0 193 123.0
56 40 0 0.8 1.4 9.2 64
8.2
100 62 0 1.1 32 16.8 25
12 9 150
16.7
20.0
26.4
10.9 75.0
15.0 99.0
5.4 40.0 0.8 1.4 9.0 10 14
8.2 49 5 0.8 2.3
82.0
96.0 104 0 129 0 169 0
66 0
75.0 1.4 2.8 18.8 30
42 0 50 0
62.5
76.0
95.0
104.0
129.0
44.0
COND
FAN
MOTOR
1 4 1 4
1.4
2.1
2.1 6.8 49.0
1.4
1.4
2.1
2.1 08
1.1
1.4
1.4
1.4 1 4
1.4
1.4
1.4 1 4
0.8 1.6 10.9 15 14
INDOOR
FAN
FLA
2.0
2.8
4.0
5.0 40.1 60
2.0
4.0 22.9 35
5.0 25.9 40
6.8 33.0 50 20
2.3
2.0
2.6
2.8
3.1
5.0
2.8 17.8 25 12 70
3 1 21.9 30
50
% Veltage imbalance
^ .|QQj^ max voltage deviation from average voltage
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage. (AB) 457 - 452 = 5 V (BC) 464 - 457 = 7 V (AC) 457 - 455 = 2 V
Maximum deviation is 7 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x —^
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
POWER SUPPLY
MCA
21.8 26 7 40
30.9 50
15.5
108
13.7
19.5 22 8 25 1
29.5
39.4
25.2
134
MOCP*
30
60 25
10 14 15 20
30 30 30 45 60
40
20 14
AB = 452 V BC = 464 V AC = 455 V
Average Voltage =
= 1 53%
average voltage
457
AWG 60 C MIN WIRE
SIZE
14 12 10 100 10 90
8 6 100 6 100
12 80 12 65 10 85 10 75
8
14 14 12 100
12 10 10 10
8
10 60 10 80
452 -H 464 -I- 455
1371
3
= 457
MAX WIRE
LENGTH
(ft)
100
100 100 100
100
100 100 100
3
75 80
90
75 95
80 90
i
20
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
Page 21
PRE-START-UP
A WARNING
Failure to observe the following warnings could result in serious personal injury:
1. Follow recognized safety practices and wear protec tive goggles when checking or servicing refrigerant system.
2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured.
3. Do not remove compressor terminal cover until all electrical sources are disconnected.
4. Relieve and reclaim all refrigerant from system be fore touching or disturbing anything inside terminal box if refrigerant leak is suspected around compres sor terminals.
5. Never attempt to repair soldered connection while refrigerant system is under pressure.
6. Do not use torch to remove any component. System contains oil and refrigerant under pressure. To re move a component, wear protective goggles and pro ceed as follows:
a. Shut off gas supply and then electrical power to
unit.
b. Relieve and reclaim all refrigerant from system
using both high- and low-pressure ports.
c. Cut component connecting tubing with tubing cut
ter and remove component from unit.
d. Carefully unsweat remaining tubing stubs when
necessary. Oil can ignite when exposed to torch flame.
Before lighting the unit for the first time, perform the following: If the gas supply pipe was not purged before connecting the unit, it will be full of air. It is recommended that the ground joint union be loos ened, and the supply line be allowed to purge until the odor of gas is detected. Never purge gas lines into a combustion chamber. Immediately upon detec tion of gas odor, retighten the union. Allow 5 min utes to elapse, then light unit
Make sure that outdoor-fan blade is correctly posi tioned in fan orifice. Leading edge of outdoor-fan blade should be
ifice (see Fig. 22).
c.
Make sure that air filter(s) is in place.
d.
Make sure that condensate drain trap is filled with water to ensure proper drainage.
Make sure that all tools and miscellaneous loose parts have been removed.
‘/2 in. maximum from plastic fan or
Proceed as follows to inspect and prepare the unit for ini
tial start-up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING, CAU TION, and INFORMATION labels attached to, or shipped with, unit.
3. Make the following inspections: a. Inspect for shipping and handling damages such as
broken lines, loose parts, disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections
and on unit base. Detecting oil generally indicates a refrigerant leak. Leak-test all refrigerant tubing con nections using electronic leak detector, halide torch, or liquid-soap solution. If a refrigerant leak is detected, see Check for Refrigerant Leaks section below.
c. Inspect all field- and factory-wiring connections. Be
sure that connections are completed and tight.
d. Inspect coil fins. If damaged during shipping and han
dling, carefully straighten fins with a fin comb.
4. Verify the following conditions:

A CAUTION

Do not purge gas supply into the combustion cham ber. Do not use a match or other open flame to check for gas leaks. Failure to follow this warning could result in an explosion causing personal injury or death.
START-UP
Check for Refrigerant Leaks - Proceed as follows
to locate and repair a refrigerant leak and to charge the unit:
1. Locate leak and make sure that refrigerant system pres sure has been relieved and reclaimed from both high­and low-pressure ports.
2. Repair leak following accepted practices. NOTE: Install a filter drier whenever the system has been
opened for repair.
3. Add a small charge of R-22 refrigerant vapor to system and leak-test unit.
4. Evacuate and reclaim refrigerant from refrigerant sys tem if additional leaks are not found.
5. Charge unit with R-22 refrigerant, using a volumetric­charging cylinder or accurate scale. Refer to unit rating
plate for required charge. Be sure to add extra refrig
erant to compensate for internal volume of filter drier.
21
Page 22
Start Up Heating Section and Make
Adjustments

A CAUTION

Complete the required procedures given in Pre-Start-Up section above before starting the unit.

A CAUTION

These units are designed to consume the rated gas in puts using the fixed orifices at specified manifold pres
sures as shown in Table 5. DO NOT REDRILL THE ORIEICES UNDER ANY CIRCUMSTANCES.
Do not jumper any safety devices when operating the unit.
Make sure that burner orifices are properly aligned. Un stable operation may occur when the burner orifices in the manifold are misaligned.
Follow the lighting instructions on the heating section operation label (located inside the burner or blower access door) to start the heating section.
NOTE; Make sure that gas supply has been purged, and
that all gas piping has been checked for leaks. CHECK HEATING CONTROL - Start and check the unit
for proper heating control operation as follows: (See fur nace lighting instructions located inside burner or blower access panel.)
1. Place the room thermostat SYSTEM switch in the HEAT position and the fan switch in the AUTO, position.
2. Set the heating temperature control of the thermostat above room temperature.
3. The induced-draft motor will start.
4. After a call for heating, the main burner should light within 5 seconds. If the burners do not light, there is a 22-second delay before another 5-second try. If the burn ers still do not light, this sequence is repeated. If the burners do not light within 15 minutes from the initial call for heat, there is a lockout. To reset the control, break the 24-v power to W.
5. The evaporator fan will turn on 45 seconds after the flame has been established. The evaporator fan will turn off 45 seconds after the thermostat has been satisfied.
CHECK GAS INPUT — Check gas input and manifold pres sure after unit start-up. (See Table 5.) If adjustment is required proceed as follows.
The rated gas inputs shown in Table 5 are for al titudes from sea level to 2000 ft above sea level. These in puts are based on natural gas with a heating value of
1050 Btu/ft^ at 0.65 specific gravity, or propane gas with a heating value of 2500 Btu/ft^ at 1.5 specific gravity. For elevations above 2000 ft, reduce input 4% for each
1000 ft above sea level. When the gas supply being used has a different heating value or specific gravity, refer to na tional and local codes, or contact your distributor to deter mine the required orifice size.
Table 5 — Rated Gas Inputs at
ADJUST GAS INPUT — The gas input to the unit is determined by measuring the gas flow at the meter or by measuring the manifold pressure. Measuring the gas flow at the meter is recommended for natural gas units. The man ifold pressure must be measured to determine the input of propane gas units.
Measure Gas Flow (Natural Gas Units) — Minor adjust ment to the gas flow can be made by changing the man ifold pressure. The manifold pressure must be maintained between 3.4 and 3.6 in. wg. If larger adjustments are required, change main burner orifices following the rec ommendations of national and local codes.
NOTE: All other appliances that use the same meter must be turned off when gas flow is measured at the meter.
Proceed as follows:
1. Turn off gas supply to unit.
2. Remove pipe plug on manifold (see Fig. 23), then con nect manometer at this point. Turn on gas to unit.
3. Record number of seconds for gas meter test dial to make one revolution.
4 Divide number of seconds in Step 3 into 3600 (number
of seconds in one hour).
5. Multiply result of Step 4 by the number of cu ft shown
for one revolution of test dial to obtain cu ft of gas flow per hour.
6. Multiply result of Step 5 by Btu heating value of gas to obtain total measured input in Btuh. Compare this value with heating input shown in Table 5. (Consult the local gas supplier if the heating value of gas is not known.)
EXAMPLE: Assume that the size of test dial is 1 cu ft, one revolution takes 30 seconds, and the heating value of the
gas is 1050 Btu/ft^. Proceed as follows:
1. 30 seconds to complete one revolution.
2. 3600 ^ 30 = 120.
3. 120 X 1 = 120 ft^ of gas flow/hr.
4. 120 X 1050 = 126,000 Btuh input.
If the desired gas input is 120,000 Btuh, only a minor
change in the manifold pressure is required.
Indicated Manifold Pressures
When a unit is converted to propane, different size orifices must be used. See separate natural-to­propane conversion kit instructions.
tBased on aititudes from sea ievei to 2000 ft above sea ievei. For aititudes above 2000 ft, reduce input
1
I NC
S(
NOTE: Unit sizes 018 and 060 are 48SS only.
NUMBER
UNIT 48SS,SX
018040, 024040, 030040 024060, 030060, 036060, 042060 030080, 036080, 042080,
048080, 060080 036100, 042100, 048100, 060100 036120, 042120, 048120, 060120 048140, 060140 3 40 130 4.0 130
rating 4% for each 1000 ft above sea ievei. In Canada, from 2000 ft above sea level to 4500 ft above sea level, derate the unit 10%.
OF
ORIFICES
1 4.0 2
2 4.0 3
3 4.0 13.0
GAS SUPPLY PRESSURE
Min
4.0 130
4.0
Natural
(in. wg)
Max
13.0
13.0
13.0
Propane
Min Max
4.0
13.0
40
13.0
40
130
40
13.0
40
130
22
MANIFOLD PRESSURE
(in. wg)
Natural
Propane
3.5 3.5 32 40,000 41
3.5 3.5
3.5 35 32
3.5 3.5
3.5 3.5 32 35
3.5
NATURAL GAS PROPANE*
Orifice
Heating Drill Size
38 60,000 46 60,000
36 100,000
30
Input
(Btuh)t
80,000
120,000
136,000
Orifice
Heating Drill Size
42 44
42 40 136,000
Input
(Btuh)t
40,000
80,000
100,000 120,000
Page 23
CHECK BURNER ELAME - With burner access panel removed, observe the unit heating operation. Watch the burner flames to see if they are light blue and soft in appearance, and that the flames are approximately the same for each burner. See Fig. 24. Refer to Maintenance section for in formation on burner removal.
AIRFLOW AND TEMPERATURE RISE - The heating section for each size unit is designed and approved for heat ing operation within the temperature-rise range stamped on the unit rating plate.
BURNER FLAME
Fig. 23 — Burner Assembly
Observe manifold pressure and proceed as follows to ad
just gas input:
1. Remove cover screw over regulator adjustment screw on gas valve.
2. Turn regulator adjustment screw clockwise to increase gas input, or turn regulator adjustment screw counter clockwise to decrease input. Manifold pressure must be between 3.4 and 3.6 in. wg.

A WARNING

Unsafe operation of the unit may result if manifold pressure is outside this range. Personal injury or unit
damage may result.
3. Replace cover screw cap on gas valve.
4. Turn off gas supply to unit. Remove manometer from pressure tap and replace pipe plug on gas valve. Turn on gas to unit and check for leaks.
Measure Manifold Pressure (Propane Units') — The main burner orifices on a propane gas unit are sized for the unit rated input when the manifold pressure is 3.5 in. wg.
Proceed as follows to adjust gas input on a propane gas
unit:
1. Turn off gas to unit.
2. Remove pipe plug on manifold (see Fig. 23), then con nect manometer at this point.
3. Turn on gas to unit.
4. Remove cover screw over regulator adjustment screw on gas valve.
5. Adjust regulator adjustment screw for a manifold pres sure reading of 3.5 in. wg. Turn adjusting screw clock wise to increase manifold pressure, or turn adjusting screw counterclockwise to decrease manifold pressure.
6. Replace cover screw.
7. Turn off gas to unit. Remove manometer from pressure tap. Replace pipe plug on gas valve, then turn on gas to unit. Check for leaks.
Table 6 shows the approved temperature-rise range for each heating input, and the air delivery cfm at various tem perature rises The heating operation airflow must produce a temperature rise that falls within the approved range.
Refer to Maintenance section on page 39 to adjust heat ing airflow when required.
HEATING SEQUENCE OF OPERATION - See Fig. 25-30 and unit wiring label.
On a call for heating, terminal “W” of the thermostat is energized, starting the induced-draft motor. When the hall­effect sensor on the induced-draft motor senses that it has reached the required speed, the burner sequence begins. The indoor-fan motor is energized 45 seconds after flame is established. When the thermostat is satisfied and “W” is deenergized, the burners stop firing and the indoor-fan mo tor shuts off after a 45-second time-off delay.
A LED (light-emitting diode) indicator is provided on the control board to monitor operation. The control board is lo cated by removing the burner access panel. During normal operation, the LED is continuously on. See chart below for error codes:
LED Indications
ERROR CODE
Normal Operation
Hardware Failure
Fan On/Off Delay Modified Limit Switch Fault Flame Sense Fault Five Consecutive Limit Switch Faults Ignition Lockout Fault Inducer Switch Fault Rollout Switch Fault Internal Control Fault
NOTES: 1 There is a 3-second pause between error code displays.
2 If more than one error code exists, all applicable error codes will
be displayed in numerical sequence
3 This chart is on the wiring diagram located inside the burner ac
cess panel.
23
LED INDICATION
1 Flash 2 Flashes 3 Flashes 4 Flashes 5 Flashes 6 Flashes 7 Flashes
8 Flashes
On Off
Page 24
MAXIMUM HIRE SIZE 2 AW6
230 VOLT OPERATION AS SHOWN. FOR 208 VOLT OPERATION REVERSE RED AND ORN
LEADS ON TRANSFORICR.
NOTES: 1 If any of the original wire furnished must be replaced, it must be replaced
2 Thermostat: HH07AT174, HH01AD040, HH01AD046 Subbase: HH93AZ040, 3 Use copper conductors only
L
with type 90 C wire or its equivalent. HH93AZ176
Blower Relay Contactor Capacitor Crankcase Heater Compressor Motor Combustion Relay Equipment Fuse Link Flame Sensor Fuse Ground Gas Valve Relay Hall Effect Sensor High-Voltage Transformer Ignitor Induced-Draft Motor Indoor-Fan Motor Integrated Gas Control Internal Protector Limit Switch Main Gas Valve
Fig. 25 — 208/230-1-60 Wiring Diagram, Units 48SS018-060
24
Outdoor-Fan Motor Power Quadruple Terminal Rollout Switch Transformer
Field Splice
Terminal (Marked) Terminal (Unmarked) Splice Splice (Marked)
Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring To Indicate Common Potential Only, Not to Represent Wiring
Page 25
^lEU)
_____
i~i_
MAXIMUM WIRE SIZE 2 AWG
230 VOLT OPERATION AS SHOWN. FOR 208
VOLT OPERATION REVERSE RED AM) ORN LEADS ON TRANSFORMER.
Sy£PU(
1 £.OtÆR__'fì_
_
GRN-YEL—
CH C036 i 042 ONLY)
GRN-YEL
----
1|>
^QF^-aW-VEL-
COWHESSOl
CEB
<H)
NOTES: 1 If any of the original wire furnished must be replaced, it must be replaced
with type 90 C wire or its equivalent
2 Thermostat: HH07AT174, HH01AD040, HH01AD046 Subbase: HH93AZ040,
HH93AZ176
3 Use copper conductors only
CAP l(oiaT^ CAP 2(oqt^
Fig. 26 — 208/230-3-60 Wiring Diagram, Units 48SS030-060
Blower Relay Contactor Capacitor Crankcase Heater Compressor Motor Combustion Relay
Equipment Fuse Link Flame Sensor Fuse
Ground
Gas Valve Relay Hall Effect Sensor High-Voltage Transformer Ignitor Induced-Draft Motor Indoor-Fan Motor Integrated Gas Control Internal Protector Limit Switch Main Gas Valve
25
Terminal (Marked) Terminal (Unmarked) Splice
Splice (Marked)
Factory Wiring Field Control Wiring
Field Power Wiring Accessory or Optional Wiring To Indicate Common Potential Only, Not to Represent Wiring
Page 26
MAXIMUM WIRE SUPPLY_ _ft_ —YEL SIZE 2 AWS < _
NOTES: 1 If any of the original wire furnished must be replaced, it must be replaced
with type 90 C wire or its equivalent
2 Thermostat: HH07AT174, HH01AD040, HH01AD046 Subbase: HH93AZ040,
HH93AZ176
3. Use copper conductors only
Fig. 27 — 460-3-60 Wiring Diagram, Units 48SS036-060
Blower Relay Contactor Capacitor Crankcase Heater Compressor Motor Combustion Relay
Equipment
Fuse Link
Flame Sensor
Fuse
Ground
Gas Valve Relay
Hall Effect Sensor
High-Voltage Transformer
Ignitor
Induced-Draft Motor
Indoor-Fan Motor
Integrated Gas Control
Internal Protector
Limit Switch
Main Gas Valve
26
Outdoor-Fan Motor Power Quadruple Terminal Rollout Switch Transformer
Field Splice
Terminal (Marked) Terminal (Unmarked) Splice Splice (Marked)
Factory Wiring Field Control Wiring
Field Power Wiring Accessory or Optional Wiring To Indicate Common Potential Only, Not to Represent Wiring
Page 27
MAXIMUM WIRE SIZE 2 AWG
230 VOLT OPERATION AS SHOWN FOR 208
VOLT OPERATION REVERSE RED AND ORN LEADS ON TRANSFORMER
YEL—( 0FM)-6ftN-YELn
BRN-VO' 1
COMPRESSOR
CAP 2 (®(D(D^ CAP i(oaT^
NOTES:
1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
2 Thermostat: HH07AT174, HH01AD040, HH01AD046 Sub
base: HH93AZ040, HH93AZ176
3. Use copper conductors only.
Fig. 28 - 208/230-1-60 Wiring Diagram, Units 48SX024-048
American Wire Gage Blower Motor Blower Relay Contactor Capacitor Crankcase Heater Combustion Motor Compressor Motor Combustion Relay Compressor Time Delay Discharge Thermostat Equipment Fuse Link Flame Sensor Fuse Ground Gas Valve Relay Hall Effect Sensor High-Voltage Transformer Ignitor Induced-Draft Motor Indoor-Fan Motor Indoor-Fan On Integrated Gas Control Internal Protector Limit Switch
27
Main Gas Valve National Electrical Code Outdoor-Fan Motor Power Quadruple Terminal Rollout Switch Start Thermistor Transformer
Field Splice
Terminal (Marked) Terminal (Unmarked) Splice Splice (Marked)
Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring To Indicate Common Potential Only, Not to Represent Wiring
Page 28
MAXIMUM WIRE I
SIZE 2 AWG -kJ
BLU-
EQUIP GND
230 VOLT OPERATION AS SHOWN. FOR 208
VOLT OPERATION REVERSE RED AND ORN LEADS ON TRANSFORMER.
COOLING FAN LOGIC
T T+30 G
ENERGIZED
BR
0 45 T T+30 W BR W BR
ENERGIZED ENERGIZED DE-ENERGIZED DE-ENERGIZED
DE-ENERGIZED
HEATING FAN LOGIC
1
________
i
1
\/-T-r-\ l"l rsrr
OFF
o o
SINGLE STAGE HEAT 8 SINGLE STAGE
COOL THERMOSTAT (TYP) COMMON
rcOMP AREA^ ¡DISCONNECT
L PER NEC I
COMP AREA
MAIN PWR
1 1
COMPONENT
ARRANGEMENT
MAIN
<2^ <S>
(O)
C©D
<Q> <Ü>
GAS SECTION
C@0 BLK “
BLK_/^
YEL—( 0FM)-6RN-YEL->
COMPRESSOR
(E>
CAP IIOCITO
m m
NOTES:
1 If any of the original wire furnished must be replaced, it must be
replaced with type 90 C wire or its equivalent
2 Thermostat: HH07AT174, HH01AD040, HH01AD046 Sub
base: HH93AZ040, HH93AZ176
3 Use copper conductors only
a>-vJ
[Z l]
m
CAP 2(001^
AWG
BM BR C CAP CH CM COMP CR CTD DT EQUIP FL FS FU GND GVR
[,^g
HVTRAN ­I IDM -
IFM
IFO
IGC
IP
LS
_
American Wire Gage
Blower Motor NEC — National Electrical Code
Blower Relay Contactor
Capacitor
Crankcase Heater
Combustion Motor
Compressor Motor Combustion Relay Compressor Time Delay
Discnarge Thermostat Equipment Fuse Link Fiame Sensor
Fuse Ground Gas Valve Relay
_
Hall Effect Sensor
High-Voltage Transformer
Ignitor
Induced-Draft Motor
Indoor-Fan Motor
Indoor-Fan On
Integrated Gas Control
Internal Protector
Limit Switch
MGV — Main Gas Valve
OFM — Outdoor-Fan Motor PWR — Power QT — Quadruple Terminal RS — Rollout Switch ST — Start Thermistor TRAN
— Transformer
Field Splice
<I>
Terminal (Marked) Terminal (Unmarked)
O
Splice Splice (Marked)
Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring
To Indicate Common Potential
Only, Not to Represent Wiring
L_
Fig. 29 — 208/230-3-60 Wiring Diagram, Units 48SX036-048
28
Page 29
MAXIMUM WIRE SIZE 2 AWG ■<
GRN-YEL
-----
111
m
NOTES:
1 If any of the original wire furnished must be replaced, it must be
replaced with type 90 C wire or its equivaient
2 Thermostat: HH07AT174, HH01AD040, HH01AD046 Sub
base: HH93AZ040, HH93AZ176
3 Use copper conductors oniy
American Wire Gage
Biower Motor
Biower Reiay Contactor Capacitor Crankcase Heater Combustion Motor Compressor Motor Combustion Reiay Compressor Time Delay
Discharge Thermostat
Equipment
Fuse Link
Flame Sensor
Fuse
Ground
Gas Valve Relay
Hall Eftect Sensor
High-Voltage Transformer
Ignitor
Induced-Draft Motor
Indoor-Fan Motor
Indoor-Fan Cn
Integrated Gas Control
Internal Protector
Limit Switch
Main Gas Valve
National Electrical Code
Cutdoor-Fan Motor
Power
Ouadruple Terminal
Rollout Switch Start Thermistor Transformer
Field Splice
Terminal (Marked) Terminal (Unmarked)
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring Accessory or Optional Wiring To Indicate Common Potential
Only, Not to Represent Wiring
Fig. 30 - 460-3-60 Wiring Diagram, Units 48SX036-048
29
Page 30
Start Up Cooling Section and Make Adjustments

A CAUTION

Complete the required procedures given in the Pre-
Start-Up section on page 21 before starting the unit.
Do not jumper any safety devices when operating the unit.
Do not operate the compressor when the outdoor tem perature is below 40 F (unless accessory low-ambient kit is installed)
Do not rapid-cycle the compressor. Allow 5 minutes between “on” cycles to prevent compressor damage.
CHECKING COOLING CONTROL OPERATION - Start and check the unit for proper cooling control operation as follows:
1. Place room thermostat SYSTEM switch in OFE posi tion. Observe that blower motor starts when FAN switch is placed in ON position and shuts down when FAN switch is placed in AUTO, position.
2. Place SYSTEM switch in COOL position and FAN switch in AUTO, position. Set cooling control below room tem perature. Observe that compressor, condenser fan, and evaporator blower motors start. Observe that cooling cycle shuts down when control setting is satisfied. The indoor fan will continue to run for 30 seconds.
3. When using an auto.-changeover room thermostat, place both SYSTEM and FAN switches in AUTO, positions. Observe that unit operates in heating mode when tem perature control is set to “call for heating” (above room temperature) and operates in cooling mode when tem perature control is set to “call for cooling” (below room temperature).
IMPORTANT: Scroll compressors in units 48SS048,060 and 48SX036-048 are direction-oriented. Three-phase units must be checked to ensure proper compressor 3-phase power lead orientation. If not cor rected within 5 minutes, the internal protector will shut off the compressor. The 3-phase power leads to the unit must be reversed to correct rotation. When turn ing backwards, scroll compressors emit elevated noise levels, and the difference between compressor suc tion and discharge pressures may be dramatically lower than normal.
CHECKING AND ADJUSTING REFRIGERANT CHARGE
— The refrigerant system is fully charged with R-22 refrig
erant, tested, and factory-sealed. NOTE: Adjustment of the refrigerant charge is not required
unless the unit is suspected of not having the proper R-22 charge.
A superheat charging label is attached to the inside of the compressor access door. The label includes a “Superheat Charging Table” and a “Required Suction-Tube (F) Temperature” chart.
An accurate superheat, thermocouple-, or thermistor­type thermometer, a sling psychrometer, and a gage mani fold are required when using the superheat charging method for evaluating the unit charge. Do not use mercury or small
dial-type thermometers because they are not adequate for this type of measurement.
A CAUTION
When evaluating the refrigerant charge, an indicated adjustment to the specified factory charge must always be very minimal. If a substantial adjustment is indi cated, an abnormal condition exists somewhere in the cooling system, such as insufficient airflow across either coil or both coils.
Proceed as follows:
1. Remove caps from low- and high-pressure service fittings.
2. Using hoses with valve core depressors, attach low- and high-pressure gage hoses to low- and high-pressure serv ice fittings, respectively.
3. Start unit in cooling mode and let unit run until system pressures stabilize.
4. Measure and record the following: a. Outdoor ambient-air temperature (F db). b. Evaporator inlet-air temperature (F wb). c. Suction-tube temperature (F) at low-side service
fitting.
d. Suction (low-side) pressure (psig).
5. Using “Superheat Charging Table,” compare outdoor­air temperature (F db) with evaporator inlet-air temper ature (F wb) to determine desired system operating superheat temperature. See Tables 7A-7G and 8A-8E.
6. Using “Required Suction-Tube (F) Temperature” table, compare desired superheat temperature with suc tion (low-side) operating pressure (psig) to determine proper suction-tube temperature. See Table 9.
7. Compare actual suction-tube temperature with proper suction-tube temperature. Using a tolerance of ± 3° F, add refrigerant if actual temperature is more than 3° F higher than proper suction-tube temperature, or remove refrigerant if actual temperature is more than 3° F lower than required suction-tube temperature.
NOTE: If the problem causing the inaccurate readings is a refrigerant leak, refer to Check for Refrigerant Leaks sec tion on page 21.
INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS
A CAUTION
For cooling operation, the recommended airflow is 350
to 450 cfm for each 12,000 Btuh of rated cooling ca
pacity. For heating operation, the airflow must pro
duce a temperature rise that falls within the range stamped on the unit rating plate.
Table 6 shows the temperature rise at various airflow rates.
Tables 10-13 show both heating and cooling airflows at var
ious external static pressures. Refer to these tables to de termine the airflow for the system being installed. See Table 14 for wet coil pressure drop.
NOTE: Be sure that all supply- and return-air grilles are open, free from obstructions, and adjusted properly.

A WARNING

Shut off gas supply then disconnect electrical power to the unit before changing blower speed. Electrical shock can cause personal injury or death.
30
Page 31
Airflow can be changed by changing the lead connec
tions of the blower motor.
Unit 48SS two- or 3-speed motors (except size 030) are factory wired for low speed operation. Unit 48SS030 is fac tory wired for medium speed. Units 488X024,036, and 048 two- or 3-speed motors are factory wired for low speed; units 488X030 and 042 are factory wired for medium speed.
For 208/230-v and A.O. 8mith 460-v Blower Motors — The motor leads are color-coded as follows:
3-8PEED
black = high speed
blue = medium speed
2-8PEED
black = high speed
red
low speed
red = low speed
To change the speed of the blower motor, remove the fan motor speed leg lead from the blower relay (BR). This wire is attached to terminal BM for single-phase and 3-phase units. To change the speed, remove and replace with lead for de sired blower motor speed. Insulate the removed lead to avoid
contact with chassis parts.
Table 6 - Air Delivery (Cfm) at Indicated Temperature Rise and Rated Heating Input
For 460-v GE Motors
The motor leads are color coded
as follows:
3-8PEED
black = high blue = jumper orange = medium
2-8PEED
black = high blue = jumper red = low
red = low
To change the speed of the blower motor, remove fan motor speed lead from the blower relay (BR) and replace with the lead for the desired blower motor speed. The mo tor speed lead is attached to terminal BM. Insulate removed lead end to avoid contact with chassis parts. On 3-speed motors only, connect orange lead to terminal BM of BR.
To select high speed on 460-v GE motors, separate the black
(female QC) from the blue lead (male QC) and connect the black lead to the BR. Insulate the blue lead to avoid con
tact with any chassis parts.
HEATING
(Btuh)
40,000 1389 60,000 2083 1667 1389 1190 80,000 2778
100,000 3472 2778 2315 1984 120,000 140,000
NOTE: Dashed areas do not fall within the approved temperature rise range of the unit.
20 25 30 35
1111 926 794
2222 1852 1587
4167 3333 2778 5037
4029 3358 2878
2381 2083 1852 1667
40 45 50
694 617 1042 926 1389 1235 1111 1010 926 855 794 1736 1543 1389 1263 1157
2518 2238
TEMPERATURE RISE °F
55 60 65 70
556 833 758
2014
- -
1515 1389 1282 1831 1679
1068 992 926
1549 1439
1190
75 80 85 90
1111 1343 1259 1185 1119
868
1042
980 926
31
Page 32
TEMP (F)
Airi CIN 1
COND
SPH 17.3
65
SPH 13.8
70
75
100 SPH 105 110 SPH 115
SPH 10.2
80 SPH
SPH 6.1
85
SPH
90
SPH
95
SPH
SPH
54
8.2
*
* *
*
*
*
56 58 60 62
18.5
14.9 16 1 17.3 20.7 24.1
11.4 12 5 13.7 17 1 20.6
LEGEND
Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)
TEMP (F)
AIR ENT
56 58 60 62 64
16.2
14.7
10.9
8.4
7.5
6.6
65 70 75 80 85 90 95
100
SPH SPH SPH 16.0 SPH SPH SPH 11.1 SPH SPH 73
105 SPH 110 115
SPH
SPH
54
18.2 190
17 1 17.6
14.8
13.7 13.3
8.5
6.2
LEGEND
Ewb — Entering Wet Bulb SPH — Superheat at Compressor (F)
Table 7A — Superheat Charging Table, 48SS018
EVAP AIR - CFM
600
Evap Air — Ewb (F
64 66 68 70
19.6
20.8
24.2 27.7
28.5 29.3 29.3 25 7 27.3 27.3
22.9 25.2 25.2 88 62
* it *
*
it * A it
*
*
9.5 10.2
6.5 *
*
*
*
6.6 10.0 13.5
5.0 *
it ii
*
13.6 17.0
8.1
11.4 15.2 19.0
6.2 9.4 13.2 17.0 18.5 73
it
*
5.3 9.1
20.1 23.1 23 9 24.1 25.4 26.1
17.3 21 1 22.6 24.1
11.1 149
6.7
*
*Do not attempt to charge system under these conditions — refrig
erant slugging may occur.
Table 7B — Superheat Charging Table, 48SS024
EVAP AIR - CFM
800
Evap Air — Ewb (F)
66 68 70
19.9 20.7 22.5 24.2 25.1
18.1
16.4
18.6
16.6 18.3 20.1 21.0
14.6 14 5
12.9 12.5 14.3 16.0
10.7
8.4
7.7 69 7.3 7.6 7.8 10.2
* *
* *
10.4 12.2 13.9 16.3 84
7.9 8.9 9.9
53
* *
20.4 22 1
16.3
10.1
18.0
11.9 14.3
5.5 5.8 8.1 *
*Do not attempt to charge system under these conditions — refrig
erant slugging may occur.
23.0
19.7 21.3 22.4 184
122
6.1
76
29.3
27.3
25.2
27.1
23.0
24.0
24.9
22.8
20.8
76
28.6
20.5
17.2
129
15.9
10.8 138
8.8 11.8
25.9
26.6 27.2 27.9
72 74
29.3
29.3
27.3 27 3
25.2 25.2
25.6
22.0 23.5 25.0 20 0
21 5
19.5 21.7
18.9 21.9
16.8 19.8
14.8 17.8
72 74
23.9 24 9 26 0 27.1 28 1
21.8 23.3
20.7
18.7
21 5
19.9
16.6 18.2
14.6
166 18.6 20.6 22.6
12.5 14.9
10.5
13.3 16.1 18.9
8.4 11 6
24 8
23.5 24.6 22 3 23 1
21.0
19.8 21.4
173
14.9 18.1 21.3
26.2 27.7
25.8
23.8
22.2 23 4
23.0
19.7
22.1
21.7
TEMP (F)
AIR ENT
65
70
75
SPH 14.2 SPH 13.6 SPH 13.0
80 SPH 10.9
85
SPH 8.9
90 SPH
95 100 105 110 115
SPH SPH 7.3 SPH
SPH SPH
LEGEND
Ewb — Entering Wet Bulb
- Superheat at Compressor (F)
54
56
15.1 16.1 17.1
14.1
13.0 110
8.3
7.8 78
6.7 6.7 *
Table 7C — Superheat Charging Table, 48SS030
EVAP AIR - CFM
1000
Evap Air — Ewb (F)
8.9
8.4
7.3
58
14.6
60
15.0 17.1
130 13.0 15.1 17.2 19.2
11.0
10.9
8.9 8.9 12.0 15.1 18.2 84
8.3 10.9 13.6 16.2
78 78 9.9 12.0
7.3 67
* *
7.3 93
6.7 88 10.9 13.0
* *
62 64 66
19.2
•21.3 23.3
19.2
21.3
13 6 16.1 187 20.1
14.1 16.1 18.2 20.2 20.9 21.7
11 4
136
6.7 8.9 10.9
6.8 8.9
*Do not attempt to charge system under these conditions — refrig
erant slugging may occur.
32
68 70
24.7
25.9 27.2 27 8 28.5
22 8 24.2 25 7
20.9 22.6 24 2
21.4 192 177
15.6
15.0
20 2 21.2 22 4 23.5
19.2
176 19.7
17.1
72 74
26.3
24.8
22.7 23.6
20 8
21.6 22.5
20 2 20.7
19.1
19.4 19.8
13.0 15.0 17.1 18.0
10.9 13.0
15.0
165 18.0
76
26.9
25.4 24 4
18.9
Page 33
#
#
Table 7D — Superheat Charging Table, 48SS036
TEMP (F)
AIR ENT
54
SPH 84 8.4 84 84 SPH 50 5.0 5.0 5.0 90 SPH SPH SPH SPH SPH SPH SPH SPH SPH
LEGEND
— Entering Wet Bulb — Superheat at Compressor (F)
Ewb SPH
65 70 75 80 85 90
95 100 105 110 115
56 58 60 62 64
*
* * *
* *
* * * * * *
*
*
* *
*
* * *
*
* *
* * *
* * * *
12.5 16.7 18.7 20.7 * *
* * * *
* *
*
5.4
*
* * * *
* * * •*
EVAP AIR - CFM
1200
Evap Air — Ewb (F)
66 68
13.1 15.9 186
9.6 13 1
6.0
*
*
103 14.5
75 125
5.4 * *
* *
*
*Do not attempt to charge system under these conditions — refrig
erant slugging may occur
Table 7E — Superheat Charging Table, 48SS042
TEMP (F)
COND
65 70 75 80 SPH 22.5 22.5 22.5 23.7 85 90
95 100 105 110 SPH 17.8 17.8 178 18.4 19.1 19.7 21.2 22.7 115
Ewb — Entering Wet Bulb SPH — Superheat at Compressor (F)
SPH 27.2 27.2 27.2 SPH 25 1 25.1 25.1 SPH
SPH SPH SPH SPH 20.3 20 3 20.3 21 0 21.7 SPH 19.8 19.8 19.8
SPH
LEGEND
54 56
23 1
22 0
21.5
20.9 20 9 20.9 21.6 22.2
15.7 15.7
23.1
22.0
21.5
58 60 62 64
28.9 30.5 32.2 32.5 32.9 33.2
26.8 28.5 30.1 30.8 31 5 32.2
23.1 24.8 26.4
22.0 22.7 23.3 24.0 25.7 27.5
21.5 22.1 22.8 23.4
20 5
157 164 170 17.7
EVAP AIR - CFM
Evap Air Ewb (F
28 1 29.1
24.9
21.1
1400
66 68 70 72 74
26 0 27 4
25 0
22.9 24 3 25.8 27.2
22.3 23 6 24.9 26 2
21.8 22.9 24.1
19.5
22.0 23.4
20.0
166
10.4
8.4
6.4 *
* *
30 2
28.8 30.2
26.6
21.4
17.9
15.9
13.9 15.2
12.5
11.3 14 1 10 0
70
8.7
9.3
100 11.9
31.2
29 2 29.1 28.9
28.2 28 2
25 2 25.4
24.2 24 6 23 2
72 74
24.8 26.1
21.3 22 7
19.3
17.3 18.6 20 0
146 168 18.8
135 17.1 20.7
13.0 17.3 21 7
12.4 15.6 187
33 2 33 2 33.2
32.0
30.9 30 6 30.3
30.0 29 8 29.5
27.3 27 3 27.3 26 3 26 5 26.6
23 7 24.2
20 6 22.0
16.5
17.0 19.8
13.8 158
31.9 31.7
28 1 28.1
25 6 25.9 24 9 25.3
76
24.0
179
76
28 8
24.8
TEMP (F)
COND
65 70 75 80 85 90
95 100 105 110 115
Ewb — Entering Wet Bulb SPH — Superheat at Compressor (F)
SPH 190 SPH 15.4 SPH 11.9 SPH 8.4 SPH 5.0 50 5.0 5.0 7.5 10.1 11.8 SPH SPH SPH SPH SPH SPH
LEGEND
54 56 58 60 62 64
* * *
* *
*
Table 7F — Superheat Charging Table, 48SS048
EVAP AIR - CFM
1600
Evap Air — Ewb (F
19.0 19.0
15.4 15.4
11.9
8.4 8.4 8.4 * * * *
* *
* *
•*
11.9 11.9 14.6 17.2
* * * *
* *
* * *
19.0
15.4 18.1 20.8 22 5 24.1
* * *
21.7
11.0 137 15.4
* * * * * * * * * * * *
24 3
66
33
26.0
18.9 20.6
*Do not attempt to charge system under these conditions — refrig
erant slugging may occur.
66
9.0
6.2 9.4 *
68 70 72
27.7
17.0 19.5 22 0
13.5 16.7
11.4
7.3
27.9
25.1
22.3 24.0 25.8
14.7
12.6 106 13.8
53 8.5
69
5.3 10.6 160
74
28 2 28.4
26.1 27.1
24.5
20 0 23.2 26 4
17.9 21.1 24.4
15.9 19 1 22.3
17.0 20 3
11 8 15.0 18.2
11.2
155 19.8
76
28.6
28.1 27 5
27.0
21.3
Page 34
Table 7G — Superheat Charging Table, 48SS060
EVAP AIR - CFM
AIR ENT
65 70 75 80 85 90
95 100 105 110 115
COND
SPH 20 1 SPH SPH 13.0 SPH 10.9
SPH SPH 6.9
SPH 5.0 SPH SPH SPH SPH
54 56
16 5
89
* *
*
*
20.1
16.5
13.0
10.9
8.9 69
5.0
LEGEND
Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)
TEMP (F)
Airt Cr * 1
65 70 75 80 85 90
95 100 105 110
115
COND
SPH 22.1 SPH SPH 150 SPH 92 SPH SPH SPH SPH SPH SPH SPH
54
18.5
*
*
*
*
*
56
22.1
18.9
15.4
9.5
LEGEND
Ewb — Entering Wet Bulb SPH — Superheat at Compressor (F)
Evap Air — Ewb (F
58
20.1
16.5
13.0 109
8.9
60
20.1 165 17.3 18.0 20.6
13.0
10.9
8.9
69 6.9 8.4 9.9
5.0
* *
* *
*
* *
*
50
* *
62
20.1
14.5
12.4 104
6.3 * *
*
*
64 66
20 1
16.0
13.9 11 9
22.6
18.5
16.5 19.0 20 6 22.2 144 17.0
12.4 14.9
7.8
10.3
5.8 8.3 *
* *
*Do not attempt to charge system under these conditions — refrig
erant slugging may occur
62 8.8
*
*
Table 8A - Superheat Charging Table, 48SX024
EVAP AIR - CFM
800
Evap Air — Ewb (F
22.8 23.2 25 3 27.4 29.5
19.3
15.7
*
* *
*
*
58
9.7 *
*
*
*
*
60
19.6
16.1
9.9 *
*
*
*
* *
*
62
22.2
19.2
14.4
64 66
24.8
22.3
18.9
96 15.5
7.2 12.5 178
*
*
*
9.4 14.2 7 1 106 14.5
*
* *
*Do not attempt to charge system under these conditions — refrig
erant slugging may occur.
27.5 28 3 29.1 30.0 25 4 23 3 21 3 22.6
7.1
*
68
25 2
23.1
21.1
70
25.6 26.1
24.0
22.3 23.5 24.7
189 20 9 22.9 24 9
17.3 196 22 0 24.3
12.9
10.8
15.6 18.3
13.9 17.0 123 15.7 192
6.7
*
10.6 14.4 89 13 1
68 70 72
29.8
26.7
24.7
30.2 30.5
28.1
26.0 27.3 27.4 24 0
20.1 22 4 175
20 9 24.2 24.2 24.2
18.3
11.4 84
15.8 20.1 21.6 23.1
13.2 18.0 19.5 21.0
53 107 16.0
72
74
76
26 6 27.0
24.8
25.6 26.5
25.9
23.8
21 1
25 4
23 8
20.1 23.2
22.7
183
22.2
17.4 21 6
74 76
32.1
30.0
29.4
31.3
30.0 28 7 28.0
27.4
25 3
26 1
26.8
24 8 25.1 25.5
22.1
22.9
17.5
23 6
19.0
TEMP (F)
AIR ENT
54 56 65 70
75 80 85 90
95 100 105 110 115
SPH 11.2 SPH 7.6 SPH SPH SPH
SPH SPH SPH SPH
SPH
SPH
*
*
*
*
*
* *
*
*
LEGEND
Ewb — Entering Wet Bulb SPH — Superheat at Compressor (F)
Table 8B — Superheat Charging Table, 48SX030
EVAP AIR - CFM
1000
Evap Air — Ewb (F)
58 60
11.2
7.7 77 7.7 12.1
•*
•*
11.2
*
*
*
*
*
*
* * *
*
*
*
11.2 14.9 18.6 22.3 *
*
*
* *
*
*
* *
*
62
64 66
16.6
9.4 147
8.5 13.5 18.5 76
ttr
*
*
12.3
10.0
7.7 11.5
*
*
*
*Do not attempt to charge system under these conditions — refrig
erant slugging may occur.
34
21.1 20 0
17.0
14.2
5.7 99
*
*
68 70 72 74 76
22.4 21 6
20.7
19.3
18.0
16.0
14 1
57
*
*
22.5 22.7
22.9
22.0 22 4 22 5 22 5 21 4 22.1 22.1 20 2 21.0 21.6
18.9 19.9
21 1
17.8 19.6 20.7 21.8
16.7 192 20.2 21 2
14.0
18.2
194 20 6
11.4 17.1 18.6 20.1
8.9 13.5
*
10.0 13.0 16.0
158
23.1
22.0
22.1
22.3
18.0
Page 35
TEMP (F)
AIR ENT
54 56 58
65 70 75 80 85 90
95 100 105 110 115
SPH 21.3 21.3 SPH 19.3 19.3 193 SPH
17.2 172 17.2
SPH 13.6 13.6 13.6 13.6 15.1 166 SPH 10.1 10 1 10 1 SPH 6.5 6.5 SPH SPH SPH SPH SPH
* * * *
*
*
*
*
LEGEND
Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)
TEMP (F)
AIR ENT
54 56 58 60 65 70 75 80 85 90 95
100 105 110 115
SPH 23 9 SPH 21.9 21.9 SPH 198 19.8 198 19.8 20 3 20 8 SPH 16.3 163 16.3 163 17.9 19.6 21.3 SPH
12 7 12.7 127 12 7 15.6 18.4 21 3 21 3
SPH 9.2 SPH 56 5.6 5.6 56 8.5 11.3 14.2 16.2 182 20.2 20.2 SPH SPH SPH SPH
* *
*
*
23 9 23.9
9.2 92
* *
LEGEND
Ewb — Entering Wet Bulb SPH — Superheat at Compressor (F)
Table 8C — Superheat Charging Table, 48SX036
EVAP AIR - CFM
1200
Evap Air — Ewb (F
62 64
20.2 21 2 197
66
23.3 22 2 21 0
21 3
60
21.3 22.0 22.6 193
17.2 18.5
18.0
11.7 134
60 90
*
*
*
*
*
*
*
15 0 15.8 135 120 13.4
60 8.7 11 4 14 1
*
*Do not attempt to charge system under these conditions — refrig
erant slugging may occur
6.5
*
* *
* *
*
*
*
10.1
6.5 8.8 11.2
* *
* *
Table 8D — Superheat Charging Table, 48SX042
EVAP AIR - CFM
1400
Evap Air — Ewb (F)
21 9
*
k k *
62 64
23.9
21.9
9.2 12.0 *
* * k k k k
*
*
24.4 24 9 25 5 25 8 26.1 26 5 25.6 24 7
22.4 22 9
14 9
k k *
*
80 106 13 1 156
* *
*Do not attempt to charge system under these conditions — refrig
66 68 70 72
23 4 23 7 21 3 21 7 22 0
178
7 1
erant slugging may occur.
68 70 72 74
23 5 23.7
23.8 23.3
76
22 8
22.3 22 5 22.6 22.0 21.5
21 1
18.5
14.6 157
*
‘k
* *
21.3 21.4 20.7
18.9 19.3 165
173 168
148
162 16.2 16.2
19.4
18.1 19.0
17.2 17.6
14.9 15.6
8.0 12 1 13.6 15.1
*
10.0 11.5 13.0
8.0
9.5 11.0
74
24.1
24 5 24 0 23.5
20 1
19.5
76
22 4 22.4 22 4
21 5
187
21.7
21.3
21.8 21 3 21 3 21 3
21 8 21 8
19.7 20.8 20.8
20 8 20 2
18.1 18.9 19.6
10 1 13.1 16.1 17.6 19 1
70 105
k
8.0 12.0 13.5 15.0
14.0
15.5
170
TEMP (F)
AIR ENT
54 56 58
65
70 75 80 85 90
95 100 105 110 115
SPH SPH 25 0 SPH 22 8 SPH 20 6 SPH 18.3 SPH 133 SPH SPH SPH SPH SPH
27 2 27.2
82
k
* *
k
LEGEND
Ewb — Entering Wet Bulb SPH — Superheat at Compressor (F)
Table 8E — Superheat Charging Table, 48SX048
EVAP AIR - CFM
1600
Evap Air — Ewb (F)
60
27.2
27.2 27.0 26.7 26.5 26.0
25.0 25.0 25.0 24.8 24 6 24.5 24.5 22 8
22 8
22.8 22.7 22 5 22.4 22 9
20 6 20.6 20.6 20.5 20 4
183
18.3
18.3
133 13.3 13.3
82 8.2 8.2 10.2 12 2 142 157 * *
*
k
k
* k k
* *
k
*
*
62 64
18.3 18.3
14.2 152
6.3 84
k
k
* * * * *
35
66 68 70 72 74
20.3
21.4 183 19.8 21.4 163 178 19 3
106 12 9 15.2 17.5 18.1 18 7
7 1
*Do not attempt to charge system under these conditions — refrig
erant slugging may occur.
10 1 13.1 16.1 17.1
k
7 1
76
25.6 25 1 24 5 24.0
24.5 24 6 23.8
23.5 24.0
23.1
23.1
22.2
22.4 23.5 22 4 21.4
22.9
21 8
20.6
20.9 20 4 19.9
17.3 18.8 19.0 19.2
18 2
10.5 14.0 15.3 16.6 8 0
12.0
13 5
150
Page 36
Table 9 — Required Suction-Tube Temperature (F)*
TEMP (F)
0 2 4 6
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
‘Temperature at suction service vaive
61.5
35 37 39 41 43 45 47 49 51 53 55 57 59 59 61 63 65 67 69 71
73 75
64.2 67.1 70.0 73.0
37 39 41 43 45 41 43 45 47 49 45 47 49 47 49 51 53 49 51 51 53 55 57 59 55 57 57 59 61 63
61 63 65 63 65 67 69 65 67 69 71 73 67 69 69 71 73 75 73 75 77 79
77 79 81 83
39
43 45
53 55
61
71
75 77 79 81
41
53
59
63
71 73 75
73
43
47 49
51 53
55 57 59 61 63
61 63
65 67 69
75 77 79 81 83
81 83
76.0 79.2 82.4 85.7
45 47 49 51 53
51 53 55
55 57 59 61 63
61 63 65
65 67 69 71 73
71 73 75 77
77 79 81 83
85
47
51
55 57 59 57
65 67 69 67
71
75 77 79 77
83 85 85 87 89 87
49 51
53
59
69
73 75
79 81
89 91
61
55 57
65 67
71
85
87
Table 10 — Dry-Coil Air Delivery* — Horizontal Discharge at 230 and 460 V - Unit 48SS
(Deduct 10% from Cfm and Watts for 208 V Operation)
UNIT
48SS
018
024,
030
036
042
048
060
‘Air deiivery values are without air filter and are for dry coil. See Table 14 for wet coil pressure drop. Deduct field-supplied air filter pressure drop
and wet coil pressure drop to obtain external static pressure available for ducting.
tUnit air delivery is outside of operating range. NOTE; Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator-coil icing
may occur at airflows below this point. Water blow-off may occur at airflows above 450 cfm per 12,000 Btuh of rated cooling capacity.
MOTOR
SPEED
Low
High
Low
Med
High
Low
Med
High
Low
High
Low
High
Low
Med
High
AIR
DELIVERY
Watts Cfm Watts Cfm Watts Cfm Watts Cfm Watts Cfm Watts Cfm Watts Cfm Watts Cfm Watts Cfm Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
0.0 0.1
230 225 760 745 725 695 640 540
t t t t t t t
275 275 857 835 802 371 368 360 349
1079 1063
514
1409 1383 1324
473 447 427 418
1253 1253
519
1414
667
1734
678 635 604 580 550 520
1540 1515 1475 1430
1000 991 970 925 2125 1355 2480 2440 2388 2330
1366 1287
1639 1563
t
1825
t
t t t t t t t t t t
2110 2085
1315
t t t t
1027 996 978 919
493
1172 1130 1047 946
500 478
634 609 593
820 785
1750
. 2026
1265
1435 2509
EXTERNAL STATIC PRESSURE (In. wg)
0.2 0.3 0.4 0.5 0.6
220
273
476 460 443 425
854 786
210 195 170
270
t
269 260 257 249 782
1282
459 439 410
1234 1162 1074 920 829 743
1461 1370
750 700 680
1685 1610 1525
1905 1830 1752 1603 1513
905 846
2025 1905 1830
2040 2009 1960
1212
1375 1310 1265 2450 2386 2310
850
745 345 326 319
1223
395 367
564 541
1375 1280 1225 1128 1020
744 706
904 875 849 830 819
1158 1103 2266 2198
235 200 700 450
717 663
865 783 401 378 344
1156 1068 984 857
346 337 865 829 377 357 340
506 469 436 422
1292
824 804 748 683
1157
493 455 430
649 612 570
1485 1355 1215
641
1752
1900 1845 1775 1045 2125 1175 1108 1010 915 2235 2160 2083 1888
0.7
t t t t t t t t t
t t t
304
960 829 743
606
1603 1398
987
2050
0.8
t t t t t t t t t
293 726
323 768
557 511
1367 1228
925 880
1968 1890
0.9 1.0
t t t t t t t t t t t t t t t t t t
t t t t t t t
637
1228
t t t
t t
t
t t
t t t t t
t t t t t
L
36
Page 37
Table 11 — Dry-Coil Air Delivery^ — Downflow Discharge at 230 and 460 V — Unit 48SS
(Deduct 10% from Cfm and Watts for 208 V Operation)
i
UNIT
48SS
018
024,
030
036
042
048
060
MOTOR
SPEED
Low
High
Low
Med
High
Low
Med
High
Low
High
Low
High
Low
Med
High
AIR
DELIVERY
Watts Cfm Watts 401 376 Cfm Watts Cfm Watts Cfm Watts Cfm Watts Cfm
Watt Cfm Watts Cfm Watts Cfm Watts Cfm Watts Cfm Watts Cfm Watts Cfm Watts Cfm Watts Cfm
0.0 0.1 0.2 0.3 0.4
t t
1334
t t t t t t t t t t t t t t t t t t t t t t t t t t
EXTERNAL STATIC PRESSURE (in. wg)
0.5
295 251 223 201 176 821
1253 1128
285 284 282 278 274 798 761 378
1011
520 511 487 472
1342 1309 1237 1181
460 439 423
1191 1136 1081 1005 907
511
1316 1244 1178 1104
655 631 603 584 552
1541
637 612 587
1500
790 750 700
1750 1675
847 784 746
1995 1901 1822 1730 1580 1477
970
2075
1291 1247 1195 1130 1076 1025
2395 2348 2291 2230
1490 1400
2530 2475 2420 2355 2289 2223
817 346
371
982 948
492
1458 1367 1292 1178
1450
909
t
2018 1896
t
952
2054 2024 1994 1945
753 665 536 322 294 272 996 816
727 368 362 357
470 450 420 392 364
1405
1604
852
928 905 880
1312
658
682 634
906 858
451
1106 1007
398 379 349 322
1005 891 784 657 535
560 526 493 455
1350 1290 1200 1105
679
1509
708
820 801 751 687
1814
1270
639 608 574 547
1421
646
1729
2164 1219 1161 1104
0.6
149 343 250
461
270
581
343 332 771 431 411
795 687 579 471
522 492 459 433 398
1053 920
1323 1221 1094
609 563 516
1582
847 804
1890 1830
2099 2022 1950 1827 1804
0.7 0.8
124 164 229 219 246 167 261 251 244 230 525
703 597 492
892 745
1319
1380 1270
970
2150
450 371 315 301
385 362
297 270 246
332 308 275
806 662
t t t t
1178
639
760
1762
921
1045 985 930
2075
0.9 1.0
t t t t t t
t t t t
610
t t t t t t t t t t t t t t t t
833 810
2008
304 283 387 341 471
349
389
509
t
t
1932
Table 12 — Dry-Coil Air Delivery* — Horizontal Discharge at 230 and 460 V — Unit 48SX
(Deduct 10% from Cfm and Watts for 208 V Operation)
UNIT
48SX
024, 030
036
042
048
*Air delivery values are without air fiiter and are for dry coil. See Table 14 for wet coil pressure drop. Deduct field-supplied air filter pressure drop
and wet coil pressure drop to obtain external static pressure available for ducting
tUnit air delivery is outside of operating range.
NOTE: Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator-coil icing may occur at airflows below this point Water blow-off may occur at airflows above 450 cfm per 12,000 Btuh of rated cooling capacity.
MOTOR
SPEED
Low
Med
High
Low
Med
High
Low
Med
High
Low
High
AIR
DELIVERY
Watts 280 275 265 255 Cfm Watts
Cfm 1025
Watts
Cfm
Watts 520 495 474 458 445 425
Cfm 1375 1335 1290 1240 1200 1140
Watts
Cfm 1520 1490
Watts
Cfm
Watts 490 480 470 460 450 430
Cfm 1400 1380 1340
Watts 590 580 560 545 525 505
Cfm
Watts
Cfm
Watts 1050
Cfm
Watts
Cfm
0.0
820 810 755 700 660 600 560 365
575
1600
1850 1830 1800
0.1
360 350 345 340 330 320 310
1010 t t t
560 535 510 480 460 440
t t t t t
1560 t t t t t t t
1000 970 930 870 810 750
t t t
t t
LEGEND AND NOTES FOR TABLES 11 AND 12
0.2 0.3 0.4
975
t
t t t
490 480 470 460 445
1300 1255 1200 1150 1080 1005 915
1450 1400 1380 1300 1200 1080
1540 1470
EXTERNAL STATIC PRESSURE (in. wg)
0.5 0.6 0.7 0.8 0.9
250
940 900 850 800 720 630
650 614 575
1560 1500 1380
1300 1250 1200 1140
1430 1360 1300 1220
t
t
t t
1785 1050 1000 930 870 810 2000 1940 1850 1750 1635
1750 1700 1640 1500
245
700 670
1780 1670
240
t t
410 390
480 450 420
t t t t t
430 410 390 380
t t t t t t t t
425
540 510 480
1280 1170 1060
1070
640 600
1600 1480
680
t t t
300
t t t t
t t t t t
1120
600
1330
740 665
1500
t t t t
790 620
t t
t t t t
560 500
1340
1300
1100 t t
1.0
t t t
t t t t
37
Page 38
Table 13 — Dry-Coil Air Delivery* — Downflow Discharge at 230 and 460 V — Unit 48SX
(Deduct 10% from Cfm and Watts for 208 V Operation)
UNIT
48SX
024, 030
036
042
048
*Air delivery values are without air filter and are for dry coil See Table 14 for wet coil pressure drop. Deduct field-supplied air filter pressure drop
and wet coil pressure drop to obtain external static pressure available for ducting.
tUnit air delivery is outside of operating range. NOTE; Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity Evaporator-coil icing
may occur at airflows below this point. Water blow-off may occur at airflows above 450 cfm per 12,000 Btuh of rated cooling capacity.
MOTOR
SPEED
Low
Med
High
Low
Med
High
Low
Med
High
Low
High
AIR
DELIVERY
Watts 280 275
Cfm 820 810
Watts
Cfm
Watts
Cfm
Watts 520
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm 1600 1560
Watts
Cfm
Watts 1050 1000 970 930
Cfm 1850
Watts
Cfm
0.0 0.1
365 360
1025 1010
t t t t
1375 1335
575 560
1520 1490
t t t t
490 480
1400 1380
590 580
t t t
t t t t t t
495
t t
t t
1830
0.2 0.3
265 755 700 350 975 490
1300 1255
474 458
1290
535 510
1450 1400
470 460
1340
560
1540
1800
EXTERNAL STATIC PRESSURE (in. wg)
t
0.4
255
345 940 480
1240
1300 1250
545
1470
1785 1750 1050 2000 1940
250 660 340
900
470 460 445 430
1200 1150 1080
445
1200
480
1380
t t
t t
650 614
1560
450
525
1430
870
1000
t t
0.5
245 240 600 330 850
425
1140
460
1300
1500
430
1200
505 480 450
1360 1300
700
1780
810
1700
930
1850
0.6 0.7
560 320 310 800 720
t t t t
440 425
1200 1080
575
1380
410 390
1140 1070
670 640
1670 1600
750 680
1640 1500
870 810
1750
t t
1005
540
1280 1170 1060
1220
1635
0.8
t t t t t t
300 630 410 390 915 790 620
t t t t t t t
510
420
1120
600 560 500
1480
600
1330
740
1500
t t
0.9
t t t
t t t t
480
t t t t t t t
1340 1100
t t t t
665
1300
1.0
t
380
t
t t
t
t t
Table 14 — Wet Coil Pressure Drop
UNIT SIZE
018*
024
030
036
042
048 1600 0.075
060*
‘Unit 48SS only.
AIRFLOW
(cfm)
600 0.069 700 800 900
600 0.039 700 800 900
900 1000 1200
1000 1200 1400 1600
1000 ■; 0 048 1200 0.069 1400 1600
1400 0.068 1800
1700 1900 2100 2300
PRESSURE DROP
(in. wg)
0 082
0102 0116
0.058
0.075
0.088
0.088
0.095
0.123
0.068
0.088
0.108 0123
0.088
0.102
0.088
0.082
0.095
0.108
0.123
38
t
Page 39
i
COOLING SEQUENCE OE OPERATION — With the room thermostat SYSTEM switch in the COOL position and the FAN switch in the AUTO, position, the cooling sequence of operation is as follows:
When the room temperature rises to a point that is slightly above the cooling control setting of the thermostat, the ther mostat completes the circuit between thermostat terminal R to terminals Y and G. These completed circuits through the thermostat connect contactor coil (C) (through unit wire Y) and blower relay coil (BR) (through unit wire G) across the 24-v secondary of transformer (TRAN)
The normally-open contacts of energized contactor (C) close and complete the circuit through compressor motor (COMP) to condenser (outdoor) fan motor (OEM). Both motors start instantly.
The set of normally-open contacts of energized relay BR close and complete the circuit through evaporator blower (indoor) fan motor (IFM). The blower motor starts instantly.
NOTE: Once the compressor has started and then has stopped, it should not be started again until 5 minutes have elapsed.
The cooling cycle remains “on” until the room temper ature drops to point that is slightly below the cooling control setting of the room thermostat. At this point, the thermostat “breaks” the circuit between thermostat termi nal R to terminals Y and G. These open circuits deenergize contactor coil C and relay coil BR. The condenser and com pressor motors stop. After a 30-second delay, the blower motor stops. The unit is in a “standby” condition, waiting for the next “call for cooling” from the room thermostat.
MAINTENANCE
To ensure continuing high performance, and to minimize the possibility of premature equipment failure, periodic main tenance must be performed on this equipment. This com bination heatlng/cooling unit should be inspected at least once each year by a qualified service person. To trouble shoot heating or cooling of units, refer to Tables 15 and 16.
NOTE TO EQUIPMENT OWNER: Consult your local dealer about the availability of a maintenance contract.

A WARNING

The ability to properly perform maintenance on this equip ment requires certain expertise, mechanical skills, tools, and equipment. If you do not possess these, do not at tempt to perform any maintenance on this equipment other than those procedures recommended in the User’s Manual. FAILURE TO HEED THIS WARN ING COULD RESULT IN SERIOUS PERSONAL INJURY AND POSSIBLE DAMAGE TO THIS EQUIPMENT.
The minimum maintenance requirements for this equip ment are as follows:
1. Inspect air filter(s) each month. Clean or replace when necessary.
2. Inspect indoor coil, drain pan, and condensate drain each cooling season for cleanliness. Clean when necessary.
3. Inspect blower motor and wheel for cleanliness and check lubrication each heating and cooling season. Clean and lubricate (if required) when necessary. For first heating
season, inspect blower wheel bimonthly to determine proper
cleaning frequency.
4. Check electrical connections for tightness and controls for proper operation each heating and cooling season.
Service when necessary.
5. Check and inspect heating section before each heating season. Clean and adjust when necessary.
6. Check flue hood screen and remove any obstructions if
necessary.
7. Check vent screen and clean if necessary.

A WARNING

Failure to follow these warnings could result in serious
personal injury:
1. Turn off gas supply, then turn off electrical power to the unit before performing any maintenance or service on the unit.
2. Use extreme caution when removing panels and parts. As with any mechanical equipment, personal injury can result from sharp edges, etc.
3. Never place anything combustible either on, or in contact with, the unit.
4. Should overheating occur, or the gas supply fail to shut off, shut off the external main manual gas valve to the unit, then shut off the electrical supply.
Air Filter

A CAUTION

Never operate the unit without a suitable air filter in the retum-air duct system. Always replace the filter with the same dimensional size and type as originally installed. See Tables 1 and 2 for recommended filter sizes.
Inspect air filter(s) at least once each month and replace (throwaway-type) or clean (cleanable-type) at least twice during each heating and cooling season or whenever the filter(s) becomes clogged with dust and lint.
Unit Top Removal
NOTE: When performing maintenance or service proce dures that require removal of the unit top, be sure to per form all of the routine maintenance procedures that require top removal, including: inspection of the heat exchanger area, coil inspection and cleaning, and condensate drain pan inspection and cleaning.
Only qualified service personnel should perform mainte nance and service procedures that require unit top removal. Refer to the following top removal procedures:
1. Turn off gas supply, then turn off electric power to unit.
2. Remove all screws that secure unit top, including screws
around 4 sides and those on top that screw into internal divider panels. Save all screws.
3. Lift top from unit carefully. Set top on edge.
4. Carefully replace and secure unit top to unit, using screws
removed in Step 2, when maintenance and/or service pro cedures are completed. (Be sure to use original screws that have rubber washers to seal out water when secur ing top to internal divider panels.)
Evaporator Blower and Motor
NOTE: Motors without oilers are prelubricated Do not at tempt to lubricate these motors.
For longer life, operating economy, and continuing effi ciency, clean accumulated dirt and grease from the blower wheel and motor annually.
Lubricate the motor every 5 years if the motor is used intermittently (thermostat FAN switch in AUTO, position), or every 2 years if the motor is used continuously (thermo stat FAN switch in ON position).
39
Page 40
Table 15 — Heating Troubleshooting Chart
SYMPTOM
Burners will not ignite.
Inadequate heating.
Poor flame characteristics.
CAUSE
Water in gas line No power to furnace No 24-v power supply to control
circuit
Miswired or loose connections Burned-out heat anticipator in
thermostat
Broken thermostat wire Misaligned spark electrodes
No gas at main burners
Dirty air filter Gas input to furnace too low
Unit undersized for application Restricted airflow Blower speed too low
Limit switch cycles main burners
Incomplete combustion results in: Aldehyde odors, carbon monoxide,
sooting flame, floating flame
REMEDY
Drain. Install drip leg. Check power supply fuses, wiring, or circuit breaker. Check transformer.
NOTE: Some transformers have internal overcurrent protection that requires a cool-down period to reset.
Check all wiring and wirenut connections.
Replace thermostat.
Run continuity check. Replace wire if necessary.
Check flame ignition and sense electrode positioning. Adjust as necessary.
1. Check gas line for air. Purge as necessary. NOTE: After purging gas line of air, wait at least
5 minutes for any gas to dissipate before attempt ing to light unit.
2. Check gas valve.
Clean or replace filter as necessary. Check gas pressure at manifold. Match with that on
unit nameplate. Replace with proper unit or add additional unit. Clean or replace filter. Remove any restriction. Use faster speed tap if available, or install alternate
motor. Check rotation of blower, thermostat heat antic
ipator settings, temperature rise of unit. Adjust as necessary.
1. Tighten all screws around burner compartment.
2. Cracked heat exchanger. Replace.
3. Unit overfired. Reduce input (change orifices or adjust gas line or manifold pressure).
4. Check burner alignment.
t

A WARNING

Turn off the gas supply, then disconnect and tag elec trical power to the unit before cleaning and lubricating the blower motor and wheel. Failure to adhere to this warning could cause personal injury or death.
To clean and lubricate the blower motor and wheel for
direct-drive models:
1. Remove and disassemble blower assembly as follows: a. Remove blower access door. b. Disconnect motor lead from blower relay (BR)
Disconnect yellow lead from terminal L2 of the contactor.
c. Remove blower assembly from unit. Remove screws
securing blower to gas partition and slide assembly out. Be careful not to tear insulation in blower compartment.
d. Ensure proper reassembly by marking blower wheel
and motor in relation to blower housing before dis assembly.
e. Loosen setscrew(s) that secures wheel to motor shaft,
remove screws that secure motor mount brackets to housing, and slide motor and motor mount out of housing.
2. Lubricate motor as follows:
a. Thoroughly clean all accumulations of dirt or grease
from motor housing.
b. Remove dust caps or plugs from oil ports located at
each end of motor.
c. Use a good grade of SAE 20 nondetergent motor oil
and put one teaspoon (Yie oz. or 16 to 25 drops) in
each oil port.
d. Allow time for oil to be absorbed by each bearing,
then wipe excess oil from motor housing.
e. Replace dust caps or plugs in oil ports.
3. Remove and clean blower wheel as follows: a. Ensure proper reassembly by marking wheel
orientation.
b. Lift wheel from housing. When handling and/or clean
ing blower wheel, be sure not to disturb balance weights
(clips) on blower wheel vanes.
c. Remove caked-on dirt from wheel and housing with
a brush. Remove lint and/or dirt accumulations from wheel and housing with vacuum cleaner, using soft brush attachment. Remove grease and oil with mild
solvent. d. Reassemble wheel into housing. e. Reassemble motor into housing. Be sure setscrews
are tightened on motor shaft flats and not on round
part of shaft.
f. Reinstall blower access door.
4. Restore electrical power, then gas supply to unit. Start unit and check for proper blower rotation and motor speeds during heating and cooling cycles.
t
40
Page 41
Table 16 - Cooling Troubleshooting Chart
SYMPTOM CAUSE
Compressor and
condenser fan will
not start.
Compressor will not start but condenser fan runs.
Three-phase scroll
compressor (Units
Power failure Fuse blown or circuit breaker tripped Defective thermostat, contactor, transformer,
or control relay
Insufficient line voltage
Incorrect or faulty wiring Thermostat setting too high Faulty wiring or loose connections in
compressor circuit Compressor motor burned out, seized, or
internal overload open Defective run/start capacitor, overload,
start relay One leg of 3-phase power dead
Scroll compressor is rotating in the wrong direction
48SS048,060 and 48SX036-048 only)
makes excessive noise, and there may be a low pres sure differential.
Compressor cycles
Refrigerant overcharge or undercharge Reclaim refrigerant, evacuate system and
(other than normally satisfying
thermostat).
Compressor operates continuously.
Excessive head pressure.
Head pressure too low.
Excessive suction
pressure.
Suction pressure too low.
Defective compressor Replace and determine cause.
Insufficient line voltage Determine cause and correct.
Blocked condenser Determine cause and correct.
Defective run/start capacitor, overload or start relay
Defective thermostat
Faulty condenser-fan motor or capacitor Replace.
Restriction in refrigerant system Locate restriction and remove.
Dirty air filter Replace filter.
Unit undersized for load Decrease load or increase unit size. Thermostat set too low
Low refrigerant charge Locate leak, repair and recharge.
Leaking valves in compressor Replace compressor Air in system Condenser coil dirty or restricted
Dirty air filter Replace filter.
Dirty condenser coil
Refrigerant overcharged Reclaim excess refrigerant. Air in system Reclaim refrigerant, evacuate system, and recharge. Condenser air restricted or air short-cycling
Low refrigerant charge Check for leaks, repair and recharge. Compressor valves leaking Replace compressor.
Restriction in liquid tube Remove restriction.
High heat load Check for source and eliminate.
Compressor valves leaking Replace compressor.
Refrigerant overcharged Reclaim excess refrigerant.
Dirty air filter Replace filter.
Low refrigerant charge Check for leaks, repair and recharge.
Metering device or low side restricted Remove source of restriction.
Insufficient evaporator airflow Inorease air quantity. Check filter — replace if
Temperature too low in conditioned area
Outdoor ambient below 40 F
Field-installed filter-drier restricted Replace.
REMEDY
Call power company. Replaoe fuse or reset circuit breaker. Replace component.
Determine cause and correct. Check wiring diagram and rewire correctly. Lower thermostat setting below room temperature. Check wiring and repair or replace.
Determine cause. Replace compressor.
Determine cause and replace.
Replace fuse or reset circuit breaker. Determine cause.
Correct the direction of rotation by reversing the 3-phase power leads to the unit Shut down unit to allow pressures to equalize.
recharge to capacities shown on nameplate.
Determine cause and replace.
Replace thermostat.
Reset thermostat.
Reclaim refrigerant, evacuate system, and recharge. Clean coil or remove restriction.
Clean coil.
Determine cause and correct.
necessary.
Reset thermostat. Install low-ambient kit.
41
Page 42
Flue Gas Passageways — To inspect the flue col
lector box and upper areas of the heat exchanger:
1. Remove the combustion blower wheel and motor assem bly according to directions in Combustion-Air Blower
section below.
2. Remove the 3 screws holding the blower housing to the flue collector box cover (see Fig. 31).
3. Remove the 12 screws holding the flue collector box
cover (Fig. 31) to the heat exchanger assembly. Inspect
the heat exchangers.
4. Clean all surfaces as required using the wire brush.
:
Fig. 32 — Burner Access Panel
BURNER
-ACCESS PANEL
t
BURNER RACK
MOUNTING SCREW
Fig. 31 — Blower Housing and Flue Collector Box
Combustion-Air Blower — Clean periodically to as
sure proper airflow and heating efficiency. Inspect blower wheel every fall and periodically during heating season. For the first heating season, inspect blower wheel bimonthly to determine proper cleaning frequency.
To inspect blower wheel, remove draft hood assembly. Shine a flashlight into opening to inspect wheel. If cleaning is required, remove motor and wheel as follows;
1. Remove burner access panel. (See Fig. 32.)
2. Remove the 7 screws that attach induced-draft motor mount
ing plate to blower housing. (See Fig. 31.)
3. Slide the motor and blower wheel assembly out of the
blower housing. (See Fig. 33.) Clean the blower wheel. If additional cleaning is required, continue with Steps 4 and 5.
4. To remove blower, remove 2 setscrews. (See Fig. 33.)
5. To remove motor, remove 4 screws that hold blower
housing to mounting plate. Remove the motor cooling fan by removing one setscrew. Remove nuts that hold motor to mounting plate
6. To reinstall, reverse the procedure outlined above.
Fig. 33 — Removal of Motor and Blower Wheel
Limit Switch — Remove blower panel. Limit switch is
located on the gas partition.
Burner Ignition — Unit is equipped with a direct spark
ignition 100% lockout system. Ignition module is lo cated in the control box. Module contains a self-diagnostic LED. During servicing, refer to label diagram for LED interpretation.
If lockout occurs, unit may be reset by either momen tarily interrupting power supply to unit, or turning selector switch to OFF position at the thermostat.
Main Burners — At the beginning of each heating sea
son, inspect for deterioration or blockage due to corrosion or other causes. Observe the main burner flames and adjust if necessary.
t
42
Page 43

A CAUTION

When servicing gas train, do not hit or plug orifice spuds.
REMOVAL OF GAS TRAIN
1. Shut off manual gas valve.
2. Shut off power to unit
3. Remove burner access panel. (See Fig. 32.)
4. Disconnect gas piping at unit gas valve.
5. Remove wires connected to gas valve. Mark each wire
6. Remove ignitor and sensor wires at the ignitor module.
7. Remove the mounting screw that attaches the burner rack to the basepan. (See Fig. 31.)
8 Slide the burner rack out of the unit. (See Fig. 31 and
34.)
9. To reinstall, reverse the procedure outlined above.
Straighten bent fins with a fin comb. If coated with dirt or lint, clean the coils with a vacuum cleaner, using the soft brush attachment. Be careful not to bend the fins. If coated with oil or grease, clean the coils with a mild detergent­and-water solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, in sulation, wiring, or air filter(s). For best results, spray con denser coil fins from inside to outside the unit. On units with an outer and inner condenser coil, be sure to clean be tween the coils. Be sure to flush all dirt and debris from the unit base.
Inspect the drain pan and condensate drain line when in specting the coils. Clean the drain pan and condensate drain by removing all foreign matter from the pan. Flush the pan and drain tube with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s). If the drain tube is restricted, clear it with a ‘ ‘plumbers snake’ ’ or similar probe device. Ensure that the auxiliary drain port above the drain tube is also clear.
Condenser Fan

A CAUTION

Keep the condenser fan free from all obstructions to ensure proper cooling operation. Never place articles on top of the unit. Damage to unit may result.
Remove 2 screws at bottom and 2 screws along sides of condenser air intake grille and remove plastic grille.
Inspect the fan blades for cracks or bends.
2.
If fan needs to be removed, loosen the setscrew and slide
3. the fan off the motor shaft.
When replacing fan blade, position blade so that lead
4. ing edge is ‘/2 in. in front of fan orifice. See Fig. 22.
Ensure that setscrew engages the flat area on the motor shaft when tightening.
Replace grille.
6.
Fig. 34 — Burner Rack Removed
Condenser Coil, Evaporator Coil, and Conden sate Drain Pan — Inspect the condenser coil, evapo
rator coil, and condensate drain pan at least once each year. Proper inspection and cleaning requires the removal of the unit top. See Unit Top Removal section on page 39.
The coils are easily cleaned when dry; therefore, inspect and clean the coils either before or after each cooling sea son. Remove all obstructions, including weeds and shrubs, that interfere with the airflow through the condenser coil.
Electrical Controls and Wiring — Inspect and check
the electrical controls and wiring annually. Be sure to turn off the gas supply, and then the electrical power to the unit.
Remove the control, blower, and compressor compart ment access panels to locate all the electrical controls and wiring. Check all electrical connections for tightness. Tighten all screw connections. If any smoky or burned connections are noticed, disassemble the connection, clean all the parts, restrip the wire end and reassemble the connection properly and securely.
After inspecting the electrical controls and wiring, re place all the panels. Start the unit, and observe at least one complete heating cycle and one complete cooling cycle to ensure proper operation. If discrepancies are observed in either or both operating cycles, or if a suspected malfunc tion has occurred, check each electrical component with the proper electrical instrumentation. Refer to the unit wiring label when making these checkouts.
NOTE: Refer to the heating and/or cooling sequence of op eration in this publication as an aid in determining proper control operation.
43
Page 44
START-UP CHECKLIST
(Remove and Store in Job File)
I. PRELIMINARY INFORMATION
MODEL NO DATE
_______________________
____________________________
SERIAL NO.: . TECHNICIAN:
II. PRE-START-UP (insert checkmark in box as each item is completed)
□ VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT □ REMOVE ALL SHIPPING HOLDDOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS □ VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS □ CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS □ CHECK GAS PIPING FOR LEAKS □ CHECK THAT INDOOR-AIR FILTER IS CLEAN AND IN PLACE □ VERIFY THAT UNIT INSTALLATION IS LEVEL □ CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW
TIGHTNESS
Ref
nect Dete
If pect leak refri Leal
If man Refi
Gai
unie lem
III. START-UP
ELECTRICAL
SUPPLY VOLTAGE
COMPRESSOR AMPS COMPRESSOR AMPS INDOOR-FAN AMPS
TEMPERATURES
OUTDOOR-AIR TEMPERATURE RETURN-AIR TEMPERATURE COOLING SUPPLY AIR GAS HEAT SUPPLY AIR
PRESSURES
GAS INLET PRESSURE GAS MANIFOLD PRESSURE REFRIGERANT SUCTION REERIGERANT DISCHARGE
L1-L2 L2-L3 LI
1,2 L3 LI L2 LI
1.2 L3
DB DB
IN. WG IN. WG PSIG
PSIG
WB
L3-L1
1.3
Q
LIJ
1= o
Q
G
z O
_J
< H
3 o
□ VERIFY REFRIGERANT CHARGE USING CHARGING TABLES
□ VERIFY THAT 3-PHASE SCROLL COMPRESSOR ROTATING IN CORRECT DIRECTION
Copyright 1994 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.
Book|1 |4 PC 111 Cataiog No. 534-842 Printed in U S.A Form 48SS,SX-2Si Pg CL-1 5-94 Repiaoes: 48SS,SX-1Si
Tab 1a 6a
Cop
Boo Tab
Page 45
Refrigerant Circuit — Inspect all refrigerant tubing con nections and the unit base for oil accumulations annually. Detecting oil generally indicates a refrigerant leak.
If oil is detected or if low cooling performance is sus pected, leak-test all refrigerant tubing using an electronic leak-detector, halide torch, or liquid-soap solution. If a refrigerant leak is detected, refer to Check for Refrigerant Leaks section on page 21.
If no refrigerant leaks are found and low cooling perfor mance is suspected, refer to Checking and Adjusting Refrigerant Charge section on page 30.
Gas Input — The gas input does not require checking unless improper heating performance is suspected. If a prob lem exists, refer to Start-Up section on page 21
Evaporator Airflow — The heating and/or cooling air flow does not require checking unless improper perfor mance is suspected. If a problem exists, be sure that all
supply- and return-air grilles are open and free from ob structions, and that the air filter is clean. When necessary,
refer to Indoor Airflow and Airflow Adjustments section on page 30 to check the system airflow.
Metering Device — Acutrol " Device — This me
tering device is a fixed orifice and is located in the header to the evaporator coll.
Liquid Line Strainer — The liquid line strainer (to
protect metering device) is made of wire mesh and located in the liquid line on the inlet side of the metering device.
Copyright 1994 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book|1 |4 PC 111 Catalog No 534-842 Printed in U S A Form 48SS,SX-2SI Pg 44 5-94 Replaces: 48SS,SX-1 Si Tab la 6a
Loading...