Carrier 48PG03-16 User Manual

Gas Heating/Electric Cooling Units
with PURON® (R-410A) Refrigerant
User’s Information Manual
48PG03-16
NOTE TO INSTALLER:
This manual should be left with the equipment owner.
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, per­sonal injury or loss of life.
— Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be per-
formed by a qualified installer, service agency or the gas supplier.
Improper installation, adjustment, alteration, ser­vice or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.
Before performing recommended maintenance, be sure main power switch to unit is turned off and lockout tag is installed. Electrical shock could cause personal injury.
Your combination heating/cooling unit is equipped with di-
Burners will light automatically. Do not attempt to light by hand; personal injury may result.
CONTENTS
Page
DETERMINE TYPE OF UNIT CONTROL ..............1
TO LIGHT UNIT (Units with Electro-Mechanical
Control) ...........................................2
TO LIGHT UNIT (Units
Control) .........................................2-5
TO SHUT UNIT OFF (Units with
Electro-Mechanical Control).......................5
TO SHUT UNIT OFF (Units with
Control) .........................................5-8
MAINTAINING YOUR UNIT ...........................8
ROUTINE MAINTENANCE AND CARE FOR
THE EQUIPMENT OWNER....................... 8,9
Air Filter(s) ..........................................8
Alarm Status (Units with
Integrated Gas Controller (IGC) .....................9
Combustion Area and Vent System .................9
Heat Exchanger .....................................9
Evaporator, Condenser, and
Combustion Fan Motors ...........................9
Indoor Fan, Belt, and Pulleys ........................9
Indoor Fan Shaft Bearings (Sizes 03-14).............9
Indoor Fan Shaft Bearings (Size 16) .................9
Refrigerant Circuits .................................9
Evaporator and Condenser Coils ....................9
Condensate Drain ...................................9
Compressors........................................9
Condenser Fan......................................9
Electrical Controls and Wiring.......................9
Unit Panels..........................................9
REGULAR DEALER MAINTENANCE................10
BEFORE YOU CALL FOR SERVICE CHECK FOR
SEVERAL EASILY SOLVED PROBLEMS..........10
IN CASE OF TROUBLE .............................10
with Comfort
Comfort
Comfort
Link Control) ......8
Link™
Link
DETERMINE TYPE OF UNIT CONTROL
The procedures used to light or shut off the unit depend on the type of unit control. This section will help determine the control type of the unit.
Electro-Mechanical Control — These units may be
controlled directly by a thermostat, or indirectly by a third­party control that connects to the thermostat inputs. For direct thermostat control, use the Electro-Mechanical Control procedures in this book. For units with third-party controls connected to the thermostat inputs, refer to the third-party con­trol instructions for procedures to ensure complete unit shut off.
Comfort
installed Carrier ComfortLink control. A Scrolling Marquee display is located on the front of the unit control box behind the control box and compressor access door. These units may be controlled directly by a thermostat, directly by a space temper­ature sensor, or indirectly through other Carrier Comfort Network® (CCN) communication devices. To ensure complete unit shut off, use the ComfortLink Control procedures in this book.
Link Control — These units have a factory-
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 1 a 6 a
PC 111 Catalog No. 04-53480006-01 Printed in U.S.A. Form 48PG-5SO Pg 1 8-05 Replaces: 48PG-4SO
TO LIGHT UNIT
(Units with Electro-Mechanical Control)
Step 11 — Set the temperature selector on room thermostat
to desired setting.
1. Do not turn off the electrical power to unit without first turning off the gas supply.
2. Before attempting to start the gas heating section, familiarize yourself with all the procedures that must be followed.
3. Never attempt to manually light the burners on the unit with a match, lighter, or any other flame. If the electric sparking device fails to light the burners, refer to the shutdown procedures, then call your dealer as soon as possible.
If you do not follow these instructions exactly, a fire or explosion may result, causing property damage, injury, or loss of life.
See Fig. 1 for location of gas valve. Refer to Fig. 2 while
proceeding with the following steps.
Step 1 — Set room thermostat to the lowest temperature
setting and set SYSTEM switch to OFF position.
Step 2 — Close the shutoff valve on the gas supply piping. Step 3 — Turn off the electrical supply to the unit and
install lockout tag.
Step 4 — Open the heat section access panel. Step 5 — Move ON/OFF switch on the internal main gas
valve to the OFF position and wait 5 minutes.
Step 6 — Move ON/OFF switch on internal main gas valve
to ON position.
Step 7 — Close the heat section access panel. Step 8 — Remove lockout tag and turn on the electrical
supply to unit.
Step 9 — Open the shutoff valve on the gas supply piping. Step 10 — Set room thermostat selector slightly above
room temperature and set system switch to HEAT position to start the unit. The induced-draft combustion air fan will start. Main burners light within 30 seconds. Indoor blower will start within 60 to 90 seconds of main gas ignition.
If the main burners fail to light, or the blower fails to come on, shut down gas heating section and call your dealer for service. Failure to follow these requirements could result in serious personal injury.
TO LIGHT UNIT
(Units With
Comfort
1. Do not turn off the electrical power to unit without first turning off the gas supply.
2. Before attempting to start the gas heating section, familiarize yourself with all the procedures that must be followed.
3. Never attempt to manually light the burners on the unit with a match, lighter, or any other flame. If the electric sparking device fails to light the burners, refer to the shutdown procedures, then call your dealer as soon as possible.
If you do not follow these instructions exactly, a fire or explosion may result, causing property damage, injury, or loss of life.
See Fig. 1 for location of gas valve. Refer to Fig. 3 while
proceeding with the following steps.
Link™ Control)
Step 1 — Turn off the unit by using the Scrolling Marquee
to put the unit into Service Test mode. The Scrolling Marquee is located on the front of the unit control box behind the control box and compressor access door. Thermostat inputs and remote network commands are ignored when Service Test mode is ON.
a. A password may be required to change Service Test
values depending on previous settings configured in the unit. Default password is “1111.”
b. Press the key until a blank screen is shown.
c. Use the arrow keys to scroll the red LED on the display
to the “Service Test” position and press .
d. The control will display the Field Service Test Mode
(TEST) setting. Press once to select the TEST setting for configuration. Press again for “OFF” to begin flashing.
e. Use the arrow keys to change the configuration from
“OFF” to “ON,” then press and to save the setting.
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
HEAT EXCHANGER SECTION
MAIN BURNER SECTION
Fig. 1 — Typical Gas Heating Section
INDUCED DRAFT MOTOR
COMBUSTION FAN HOUSING
MAIN GAS VALV E
Step 2 — Close the shutoff valve on the gas supply piping.
Step 3 — Turn off the electrical supply to the unit and
install lockout tag.
Step 4 — Open the heat section access panel.
Step 5 — Move ON/OFF switch on the internal gas valve to
the OFF position and wait 5 minutes.
Step 6 — Move ON/OFF switch on internal gas valve to
ON position.
Step 7 — Close the heat section access panel.
2
STEP 1
MAIN
OFF
STEP 3STEP 2
ON
LOCK-OUT
TAG
W
E
O
R
C
L
S
E
C
A
R
L
P
M
C
HI
E
ON
F
F
O
C
STEP 5STEP 4
R
C
S
E
M
HI
ON
F
F
O
STEP 6
W
E
O
L
C
A
R
L
P
E
STEP 7
STEP 8
STEP 10
Fig. 2 — To Light Unit (Units with Electro-Mechanical Control)
3
STEP 9
MODE
Run Status
Service Test
Temperature
Pressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
Operating Modes
Alarms
Alarm Status
ESCAPE
STEP 1
ENTER
MAIN
OFF
STEP 3STEP 2
ON
LOCK-OUT
TAG
W
E
O
R
C
L
S
E
C
A
R
L
P
M
C
HI
E
ON
F
F
O
C
STEP 5STEP 4
R
C
S
E
M
HI
ON
F
F
O
STEP 6
W
E
O
L
C
A
R
L
P
E
STEP 7
MODE
Run Status
Service Test
Temperature
Pressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
Operating Modes
Alarms
Alarm Status
ESCAPE
ENTER
STEP 10
Fig. 3 — To Light Unit (Units with
4
STEP 8
Comfort
STEP 9
Link™ Control)
Loading...
+ 8 hidden pages