Carrier 48NLT User Manual

48NLT, NMT, NET, NHT AND NVT 018-060
HEATING & COOLING
Packaged Heating/Cooling Units
Installation, Start-Up and Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS General
RECEIVING AND INSTALLATION Step 1 — Check Equipment
• IDENTIFY MACHINE
• INSPECT SHIPMENT
Step 2 — Provide Unit Support
• ROOF CURB
• SLAB MOUNT
Step 3 — Provide Ciearances .................................4
Step 4 — Rig and Place Unit....................................4
Step 5 — Connect Condensate Drain Step 6 - instali Venting Step 7 - Instail Gas Piping Step 8 — Instail Duct Connections Step 9 - Instail Electrical Connections
• HIGH VOLTAGE CONNECTIONS
• SPECIAL PROCEDURES FOR 208-V
• CONTROL VOLTAGE CONNECTIONS
• HEAT ANTICIPATOR SETTING
• TRANSFORMER CIRCUIT PROTECTION
PRE-START-UP START-UP MAINTENANCE
NOTE TO INSTALLER — Before the installation, READ THESE INSTRUCTIONS CAREFULLY AND COM
PLETELY. Also, make sure the User’s Manual and Re placement Guide are left with the unit after installation.
...................................
....................
............................
...............................
.....................
......................................
.................................
.....................
.............
OPERATION
..........
SAFETY CONSIDERATIONS
Installation and servicing of air conditioning equipment can be hazardous due to system pressure and electrical com ponents. Only trained and qualified personnel should in stall, repair or service air conditioning equipment.
Untrained personnel can perform basic maintenance func tions of cleaning coils and filters. All other operations should be performed by trained service personnel. When working on air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
A WARNING
Improper installation, adjustment, alteration, service, main
tenance or use can cause carbon monoxide poisoning, fire
or an explosion which can result in personal injury or
unit damage. Consult a qualified installer, service agency
or gas supplier for information or assistance. The quali
fied installer or agency must use only factory-authorized
kits or accessories when modifying this product.
. 1 . 1 . 1
1-10
. 1
4
5
6 6
7 8
10,11 11-20
20-26
________
Fig. 1 - Model 48NLT, NMT, NET, NHT and NVT
A WARNING
Before performing service or maintenance operations on unit, turn off unit main power switch. Electrical shock could cause personal injury.
General - The 48NLT, NMT, NET, NHT and NVT
units are fully self-contained, combination gas heating/ cooling units designed for outdoor installation. See Fig. 1. The units are shipped in a vertical configuration and may be installed either on a rooftop or converted to horizontal configuration when placed on a ground-level cement slab.
Job Data — Necessary information consists of:
machine location drawings, piping drawings, field wiring diagrams and rigging guide.
RECEIVING AND INSTALLATION
Step 1 — Check Equipment
IDENTIFY MACHINE — The machine model number and serial number are stamped on machine identification plate. Check this information against shipping papers and job data.
INSPECT SHIPMENT — Inspect for shipping damage while machine is still on shipping pallet. If machine appears to be damaged or is torn loose from its anchorage, have it exam ined by transportation inspectors before removal. Forward claim papers directly to transportation company. Manufac turer is not responsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify the nearest Carrier Air Conditioning office if any item is missing.
To prevent loss or damage, leave all parts in original pack ages until installation.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.
Book|1 |4 PC 111 Catalog No 564-920 Printed in U.S,A. Form 48NT-20SI Pg 1 11-91 Replaces: 48NT-19SI
Tab la la
RIGHT SIDE VIEW
LEFT SIDE VIEW
Fig. 2 — 48 Dimensional Drawing, Sizes NLT018 — NET042
UNIT
48NHT036 48NVT036 48NHT042 48NVT042 48NLT048 48NMT048 48NHT048 48NVT048 48NLT060 48NMT060 48NHT060 48NVT060
ELECTRICAL CHARACTERISTICS
208/230/1/60, 208/230/3/60, 460/3/60 208/230/1/60, 208/230/3/60, 460/3/60 208/230/1/60, 208/230/3/60, 460/3/60 550 208/230/1/60, 208/230/3/60. 460/3/60 208/230/1/60, 208/230/3/60, 460/3/60 208/230/1/60, 208/230/3/60, 460/3/60 208/230/1/60, 208/230/3/60, 460/3/60
208/230/1/60, 208/230/3/60, 460/3/60,
208/230/1/60, 208/230/3/60, 460/3/60 208/230/1/60, 208/230/3/60, 460/3/60 208/230/1/60, 208/230/3/60, 460/3/60 616 280 139/63 208/230/1/60, 208/230/3/60, 460/3/60 616
NOTE. Clearances must be maintained to prevent recirculation of air from condenser-fan discharge.
REQUIRED CLEARANCES TO COMBUSTIBLE MATERIAL - in. (mm) Maximum Extension of Overhang 48(1219.2)
Unit Top ........................... ■ .36(914.4)
Duct Side of Unit . .... 6 Min. (152.4 Min.)
Side Opposite Ducts .30 (762.0)
Bottom of Unit. .... .0
REQUIRED CLEARANCES FOR SERVICING - in. (mm)
Blower Access Panel Side ... . 30 (762.0)
Control Box Access Side . . 30 (762.0)
UNIT WT LB
530 536 243 119/54 148/67
556 574 580 263 130/59 586 265 131/59 161/73 586 604 610
A B
KG
241 117/53 147/67
249 122/55 152/69 252
124/56 153/69
261 128/58
265
131/59
274
136/62 165/75
277
138/63 166/75
280
139/63
CORNER WT LB/KG
158/72 159/72
161/73
168/76 168/76
C
148/67 118/54 149/68 120/54 153/69 154/70 125/57 159/72
160/73 162/73 162/73 166/75 167/76 169/77 169/77
D
123/56
129/59 131/59 132/60 132/60 137/62 139/63 140/64
140/64
Fig. 3 — 48 Dimensional Drawing, Sizes NHT036 — NVT060
Table 1 — Physical Data
UNIT SIZE 48 NOMINAL CAPACITY (ton) OPERATING WEIGHT (lb) COMPRESSORS
Quantity REFRIGERANT* REFRIGERANT METERING DEVICE CONDENSER COIL
Rows
FIns/in. CONDENSER FAN
Nominal Airflow (Cfm)
Nominal Speed (Rpm)
Quantlty...Dlameter (in.)
Motor Hp (single-phase)
EVAPORATOR COIL
Rows
Fins/ln.
EVAPORATOR FAN
Nominal Cfm Nominal Speed (Rpm) Diameter x Width (in.) Motor Hp (single-phase)
FURNACE SECTION
Burner Orifice No. (Qty...drlll size) Burner Orifice No. (Qty...drlll size)
Pilot Orifice Diameter (in. ...drill size)
Pilot Orifice Diameter (In.)
RETURN-AIR FILTERS (sq ln.)t
Disposable Cleanable
•Operating charge is iisted on unit namepiate tRequired fieid-suppiied fliter areas are based on the iarger of the ARi-rated (Air Conditioning & Refrigeration institute) cooling airflow or the heating
airflow at a velocity of 300 ft/min for disposable type or 450 ft/min for high-capacity type Air filter pressure drop must not exceed 0.08 in wg
••Single-phase units
ttThree-phase units
(three-phase)
(three-phase)
Natural Gas Propane Gas Natural Gas Propane Gas
NLT018 NLT024
IV2
450
1 20 20
600 800
2 44
2. 55 2 55
288 192
NHT024
2
454
10 X 8
2 44 3 44 2. 44 3 44
NLT030
460 470 476
2000
825
V10
'/3
-
3 55 2 55 3 55
NMT030 NHT030
2V2
Reciprocating Hermetic. 3500 Rpm
1000
528 352 416
AcouRater® Piston
niR 77
NLT036
480
R-22
1 20
3
14
1100
4 44 4 55 3 .55 4 55
NMT036
486
2
2500 1100
V4 1/4
1200
V2 V2
3 44 4 44 4 42 5.44
624 720
NET036 NHT036
490
10 X 10
3
490
4 54 5 55 6 55
530
Vio
Va
3/4
480
%
2500** 3000tt
825** lioott
1200
NVT036
536
6 .44
i
Step 2 - Provide Unit Support
ROOF CURB — Install accessory roof curb in accordance with instructions shipped with curb. Install insulation, cant strips, roofing and flashing. Ductwork must be attached to curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical for water integrity. Install gasketing material supplied with the roof curb. Improperly ap plied gasketing also can result in air leaks and poor unit performance.
Curb should be level to within */4 inch. This is necessary
for unit drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
SLAB MOUNT — Place the unit on a solid, level concrete pad that is a minimum of 4-in. thick with 2-in. above grade. The slab should extend approximately 2-in. beyond the cas ing on all 4 sides of the unit. Install a gravel apron in front of condenser-air inlets to prevent obstruction of airflow by grass or shrubs. Do not secure the unit to the slab except when required by local codes.
Step 3 — Provide Clearances — The required min
imum operating and service clearances are shown in Fig. 2
and 3. Adequate combustion, ventilation and condenser air must be provided.
The condenser fan discharges through the top of the unit.
Be sure that the fan discharge does not recirculate to the condenser coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance
under a partial overhang (such as a normal house overhang) is 48-in. above the unit top. The maximum horizontal ex tension of a partial overhang must not exceed 48 inches.

A CAUTION

Do not restrict condenser airflow. An air restriction at either the outdoor-air inlet (the entire surface of the out door coil) or the fan discharge can be detrimental to compressor life.
Do not place the unit where water, ice or snow from an overhang or roof will damage or flood the unit. Do not in stall the unit on carpeting, tile or other combustible mate
rials. The unit may be installed on wood flooring or on Class
A, B or C roof covering materials.
Step 4 — Rig and Place Unit — Use spreader bars
and crate top when rigging the unit. The units must be rigged for lifting as shown in Fig. 4. Refer to Fig. 4 for rigging weight and Table 1 for operating weight. Use extreme cau
tion to prevent damage when moving the unit. Unit must remain in an upright position during all rigging and mov ing operations. The unit must be level for proper conden
sate drainage; therefore, the ground-level pad or accessory roof-mounting curb must be level before setting the unit in place. When a field-fabricated support is used, be sure that the support is level and properly supports the unit.

A CAUTION

When installing the unit on a rooftop, be sure the roof will support the additional weight. Refer to Fig. 4 for corner weight information.
Table 1 — Physical Data (cent)
NLT
UNIT SIZE 48 NOMINAL CAPACITY (ton)
OPERATING WEIGHT (lb) 496 500 500 COMPRESSORS
Quantity______
REFRIGERANT* REFRIGERANT METERING
DEVICE
CONDENSER COIL
Rows FIns/ln.
CONDENSER FAN
Nominal Airflow (Cfm) Nominal Speed (Rpm) Quantlty...Dlameter (In.) Motor Hp (single-phase)
EVAPORATOR COIL
Rows Fins/ln.
EVAPORATOR FAN
Nominal Cfm Nominal Speed (Rpm) Diameter x Width (In.)
Motor Hp (single-phase)
FURNACE SECTION
Burner Orifice No. Burner Orifice No. Pilot Orifice Diameter Pilot Orifice Diameter (In.)
RETURN-AIR FILTERS (sq ln.)t
Disposable 720 Cleanable 480
•Operating charge is iisted on unit namepiate tRequired fieid-suppiied fiiter areas are based on the iarger of the ARi-rated (Air Conditioning & Refrigeration institute) cooling airflow or the heating airflow at a velocity of 300 ft/min
for disposable type or 450 ft/min for high-capacity type. Air filter pressure drop must not exceed 0 08 in wg
(three-phase)
_________
(three-phase)
(Qty...drlll size) Natural Gas (Qty...drill size) Propane Gas
(In. ...drill size) Natural Gas
Propane Gas
3 44 3 55
NMT
042
2500 3000 3500
V2 3/4 ’/2 3/4
4. 44 4 55 4 54 5 55
042
NET 042
3Vz
4 42 5 44
NHT
NVT
042
550
6 44
6. 55 3 .55 4 55 5 55 6 54 3 55
NLT
042
556 574 580
Reciprocating Hermetic, 3500 Rpm
3 44 4 44 5 44 6 42 3 44
NMT
048
R-22
AocuRater® Piston
018 77
NHT 048
048
4
586 586
1
2
20
009
816 544 640
NVT
048
NLT
060
604
NMT
4 44 5 44 4 55 5 55
060
610
5
2000
960
NHT
060
616
NVT 060
616
I 3450
6 42 6 54
Step 5 — Connect Condensate Drain
NOTE: When installing condensate drain connection be sure to comply with local codes and restrictions.
The unit disposes of condensate water through a %-in.
NPT drain fitting. See Fig. 2 and 3 for location.
Install a 2-in. trap at the drain fitting to ensure proper drainage. See Fig. 5. Make sure the outlet of the trap is at least one-in. lower than the unit drain pan connection to

Fig. 4 - Suggested Rigging

prevent the pan from overflowing. Prime the trap with
water.
If the installation requires draining the condensate water away from the unit, connect a drain tube using a minimum of %-in. OD copper tubing, y4-in. galvanized pipe or %-in. plastic pipe. Do not undersize the tube. Pitch the drain tube
downward at a slope of at least one inch in every 10 ft of
horizontal run. Be sure to check the drain tube for leaks.
UNIT 48 NLT018
NLT024 100 NHT024 NLT030 103 132 132 103 NMT030 105 133 133 105 NHT030 106 134 134 106 NLT036 NMT036 108 NET036 108 137 137 108 NHT036 117 147 148 118 NVT036 119 148 149 120 NLT042 109 139 139 109 NMT042 NET042 110 140 140 110 NHT042 117 NVT042 NLT048 128 NMT048 NHT048 NVT048
NLT060 NMT060 NHT060
NVT060
A
99
101
107
110 140
124
130 159 160 131 131 131
136 165 166 137 138 166 167
139 168 169
139 168 169 140
CORNER WT (LB)
B C D
126 126 99 127 129 129 101
136 136 137 137
147 147 117 153 158 159 129
161 161
127
140
154
162 162
100
107 108
110
125
132 132
139 140
r MIN
Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground-level installations. When using a gravel apron,
make sure it slopes away from the unit.
Step 6 — Install Venting — The vent cap assembly
is shipped in the burner compartment. Remove the access door to locate the assembly.

A CAUTION

The venting system is designed to ensure proper vent
ing. The vent cap assembly must be installed as indi
cated in this section of the unit Installation Instructions.
NOTE; Screw holes in the flue assembly and the unit flue panel are not symmetrically located. Make sure they are oriented properly when installing these components.
Refer to Fig. 6 and install the vent cap as follows:
1. Place vent cap assembly over flue panel. Orient screw holes in vent cap with holes in flue panel.
2. Secure vent cap in place by inserting the single screw on the right side of vent cap.
3. Place the vent cap guard over the vent cap. Orient holes in vent cap guard with holes in vent cap and flue panel.
4. Secure the entire assembly with the remaining 2 screws on the left side of vent cap and vent-cap guard assembly.
Step 7 — Install Gas Piping — The gas supply pipe
enters the unit through the access hole provided. The gas connection to the unit is made to the Vi-in. FPT gas inlet on the manual shutoff or gas valve.
Install a separate gas supply line that runs directly from
the meter to the heating section. Refer to Table 2 and the National Fuel Gas Code (NFGC) for gas pipe sizing. Do
not use cast-iron pipe. It is recommended that black iron
pipe is used. Check the local utility for recommendations concerning existing lines. Choose a supply pipe that is large
enough to keep the pressure loss as low as practical. Never
use pipe smaller than the ‘A-in. FPT gas inlet on the unit
gas valve.
For natural gas applications, the gas pressure at unit gas
connection must not be less than 5 in. wg or greater than
13 in. wg while the unit is operating. For propane applica tions, the gas pressure must not be less than 11 in. wg or greater than 13 in. wg at the unit connection.
When installing the gas supply line, observe local codes pertaining to gas pipe installations. Refer to the NFGC ANSI (American National Standards Institute) Z223.1-1988 NFPA (National Fire Protection Association) 54-1988 (in Canada, CAN/CGA [Canadian Gas Association] B 149.1, (2)-M86). In the absence of local building codes, adhere to the fol lowing pertinent recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe
V4 inch in every 15 ft to prevent traps. Grade all hori
zontal runs downward to risers. Use risers to connect to
heating section and to meter.
2. Protect all segments of piping system against physical
and thermal damage. Support all piping with appropri ate straps, hangers, etc. Use a minimum of one hanger every 6 ft. For pipe sizes larger than Уг in., follow rec ommendations of national codes.
3. Apply joint compound (pipe dope) sparingly and only to male threads of joint when making pipe connections. Use only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and/or national codes.
Never use Teflon tape.
4. Install sediment trap in riser leading to heating section. This drip leg functions as a trap for dirt and condensate. Install trap where condensate cannot freeze. Install this
sediment trap by connecting a piping tee to riser leading to heating section, so that straight-through section of tee is vertical. See Fig. 7. Then, connect capped nipple into
lower end of tee. Extend capped nipple below level of
gas controls.
Table 2 — Maximum Gas Glow Capacity*
NOMINAL
IRON PIPE,
SIZE
(in.)
V2
%
1 1.049
VA 1.380 VA
‘Capacity of pipe in cu ft of gas per hr for gas pressure of 0 5 psig or less. Pressure drop of 0.5 in. wg
(based on a 0.60 specific gravity gas) Refer to Table C-4, NFPA 54-1984
fThls length includes an ordinary number of fittings
INTERNAL
DIAMETER
(In.)
.622 175 120 .824 360 250
1.610
10 20 30 40 50
680 1400 950 2100
97
465 375 320 285 260 240
1460
200
770 600 580
1180 990
82 73
170
151
900 810
LENGTH OF PIPE, FTf
60 70 80
61 57 53 50
66
125 118
138
530 490 460 430
220
750 690 650 620
90 100 125 150
110 103 93 205 195 175
400 360 325
44
160 145
550 500
175
40 84 77
300 460
200
72 135 280 430
IN
testing of the piping systems when test pressure in excess of 0.5 psig. Pressure test the gas supply piping system at pressures equal to or less than 0.5 psig. The unit heating section must be isolated from the gas piping system by clos ing the external main manual shutoff valve and slightly open ing the ground-joint union.

A CAUTION

Unstable operation may occur when the gas valve and manifold assembly are forced out of position while con necting improperly-routed rigid gas piping to the gas valve. Use a backup wrench when making connection to avoid strain on, or distortion of, the gas control piping.

A CAUTION

If a flexible conductor is required or allowed by the au thority having jurisdiction, black iron pipe shall be in stalled at the gas valve and shall extend a minimum of 2 in. outside the unit casing.

A WARNING

Never use a match or other open flame when checking for gas leaks. Never purge gas line into combustion chamber. Failure to follow this warning could result in an explosion causing personal injury or death.
Size Small Cabinet Large Cabinet NHT036-NVT060 25V2 in.
NLT018-NET042 20V2 in.
"A"

Fig. 8 — Location of Coii Area Not to be Drilled

5. Install an accessible, external, manual main shutoff valve in gas supply pipe within 6 ft of heating section.
6. Install ground-joint union close to heating section be tween unit manual shutoff and external manual main shut off valve.
7. Pressure-test all gas piping in accordance with local and national plumbing and gas codes before connecting pip ing to unit.
NOTE; Pressure test the gas supply system after the gas supply piping is connected to the gas valve. The supply piping must be disconnected from the gas valve during the
8. Check for gas leaks at the field-installed and factory­installed gas lines after all piping connections have been completed. Use soap-and-water solution (or method spec
ified by local codes and/or regulations).
Step 8 — Install Duct Connections — The unit
has duct flanges on the supply- and return-air openings on the side and bottom of the unit. See Fig. 2 and 3 for con nection sizes and locations.
NOTE: The design and installation of the duct system must be in accordance with the standards of the NFPA for instal lation of nonresidence-type air conditioning and ventilating systems, NFPA No. 90A orresidence-type, NFPA No. 90B; and/or local codes and residence-type, NFPA No. 90B; and/ or local codes and ordinances.
Adhere to the following criteria when selecting, sizing
and installing the duct system;
1. The unit is shipped in vertical configuration. To convert unit to horizontal application, remove side duct covers, save screws and install the covers on bottom duct openings.
2. Select and size ductwork, supply-air registers and return­air grilles according to ASHRAE (American Society of Heating, Refrigeration and Air Conditioning Engineers) recommendations.

A CAUTION

When drilling the duct-system fastening holes into the side of the unit instead of the unit duct flanges, use ex treme care to avoid puncturing the coil or coil tubes. See Fig. 8.
3. Use flexible transition between rigid ductwork and unit to prevent transmission of vibration. The transition may be screwed or bolted to duct flanges. Use suitable gas kets to ensure weather- and airtight seal.
4. Install external, field-supplied air filter(s) in return-air ductwork where it is easily accessible for service. Rec ommended filter sizes are shown in Table 1,
5. Size all ductwork for maximum required airflow (either heating or cooling) for unit being installed. Avoid abrupt duct size increases or decreases.
6. Adequately insulate and weatherproof all ductwork lo cated outdoors. Insulate ducts passing through uncondi tioned space, and use vapor barrier in accordance with latest issue of SMACNA (Sheet Metal and Air Condi tioning Contractors National Association) and ACCA (Air Conditioning Contractors of America) minimum instal lation standards for heating and air conditioning sys tems. Secure all ducts to building structure,
7. Flash, weatherproof and vibration-isolate all openings in building structure in accordance with local codes and good building practices.
Step 9 — Install Electrical Connections

A WARNING

The unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of per
sonal injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground lug in the control compartment, or conduit ap proved for electrical ground when installed in accor dance with NEC (National Electrical Code) ANSI/ NFPA (latest edition) (in Canada, Canadian Electrical
Code CSA C22.1) and local electrical codes. Do not
use gas piping as an electrical ground. Failure to ad
here to this warning could result in personal injury or
death.

A CAUTION

Failure to follow these precautions could result in dam
age to the unit being installed:
1. Make all electrical connections in accordance with NEC ANSI/NFPA (latest edition) and local electrical codes governing such wiring. In Canada, all electrical connec tions must be in accordance with CSA Standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between field-
supplied electrical disconnect switch and unit. DO NOT
USE ALUMINUM WIRE.
3. Be sure that high-voltage power to unit is within oper ating voltage range indicated on unit rating plate. On 3­phase units, ensure that phases are balanced within 2%. Consult local power company for correction of im proper voltage and/or phase balance.
4. Insulate low-voltage wires for highest voltage contained within conduit when low-voltage control wires are run in same conduit as high-voltage wires.
5. Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc.
HIGH-VOLTAGE CONNECTIONS - The unit must have a separate electrical service with a field-supplied, water proof, fused disconnect switch mounted at, or within sight from, the unit. Refer to the unit rating plate for maximum fuse/circuit breaker size and minimum circuit amps (ampac ity) for wire sizing. See Table 3 for electrical data.
The field-supplied disconnect switch box may be mounted on the unit over the high-voltage inlet hole in the control corner panel. See Fig. 2 and 3.
Proceed as follows to complete the high-voltage connec tions to the unit;
1. Connect ground lead to chassis ground connection when using separate ground wire.
2. Run high-voltage leads into unit control box and con nect to contactor. See unit wiring label, and Fig. 9.
A CAUTION
TRANSFORMER CONTAINS AUTO RESET OVERCURRENT PROTECTOR.
IT MAY RESET WITHOUT WARNING STARTING HEATING OR COOLING SECTION OF THIS PRODUCT.
DISCONNECT POWER PRIOR TO SERVICING.
THIS COMPARTMENT MUST BE CLOSED EXCEPT WHEN SERVICING.
316056-201 REV A
Fig. 9 — Transformer Label
Table 3 — Electrical Data
UNIT
SIZE 01B
024
030
036
042
048
060
AWG FLA LRA MCA MOCP NEC RLA
NOTES: 1
In compliance with NEC requirements for multimotor and combination load and equipment (refer to NEC Articles 430 and 440), the overcurrent pro tective device for the unit shall be fuse or HACR breaker
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater
than 2% Use the following formula to determine the % voltage imbalance.
% Voltage Imbalance
_ y max voltage deviation from average voltage
NOMINAL
V-PH-HZ
208/230-1-60 208/230-1-60
208/230-1-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
American Wire Gage Full Load Amps Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Rated Load Amps
Example: Supply voltage is 460-3-60
MODEL NO.
48
NLT018 187 253 82 49 0 NLT024
NHT024 NLT030
NMT030 NHT030
NLT036 NMT036 NET036 NHT036 NVT036
NLT036 NMT036 NET036 NHT036 NVT036
NLT036 NMT036 NET036 NHT036 NVT036
NLT042 NMT042 NET042 NHT042 NVT042
NLT042 NMT042 NET042 NHT042 NVT042
NLT042 NMT042 NET042 NHT042 NVT042
NLT048 NMT048 NHT048 NVT048
NLT048 NMT048 NHT048 NVT048
NLT048 NMT048 NHT048
NVT048
NLT060 NMT060 NHT060 NVT060
NLT060 NMT060 NHT060 NVT060
NLT060 NMT060 NHT060 NVT060
average voltage
AB = 452 volts BC = 464 volts AC = 455 volts
Average Voltage
VOLTAGE
RANGE
Min Max RLA
187 253
187 253 14.3
187
187
414
187
187
414 506 77 41 0 1 2
187 253 26 5
187 253 16.8
187
187 253 30 7
187
414 506 104 55 0 1 2
452 + 464 -r 455
3
1371
—JT— =457
11.6
11.6
253 21 1
14.7
253
506 7 1
23.9 95.4 1 5
253
15.3
253
253
253
82
21 4
COMPR
LRA
61 0
61.0
86.0 08
100 0 1 5
67.0
34 0
82 0
1140
84 0
42 0 1 2
135 0
130 0 22
CONDENSER-
FAN MOTOR
FLA
08 08
1 9
1.9
1.9 22 22
1.2
1.9 1 9 1 9
2.2
2.2
2.1
22
2 1
Determine maximum deviation from average voltage. (AB) 457 - 452 =5 volts (BC) 464 - 457 =7 volts (AC) 457 - 455 =2 volts
Maximum deviation is 7 volts.
Determine % voltage imbalance
% Voltage Imbalance =100 x
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately
EVAPORATOR-
FAN MOTOR
FLA
2.5
2.5 12 17 1 25 25
25
3.0 30
3.0 45 45 45
30 30 45 45 45
1 5 1 5 23 23 23
3.0
3.0
45 45
4.5
30
3.0
45
4.5
4.5 1 5
1 5 23 23
2.3
4.5 45
4.5
62 45
45
4.5
62 23
23
2.3
32
62 6 46 7
6.2
32 12 17.4 25
AWG MIN
WIRE SIZE
7
"457
14
10
8
10
14
8
10
14
8 6
10
14
8
= 1.53%
POWER SUPPLY
MCA
13 6 20
21 2
21.2 21 7
30.9 30 9
32.4 32 4
32.4
23.3 23 3 24 8 25 1 25 1
11 6 11 6 124 124
12.4 34 3
34 3 35 9
35.9 35 9
24 0
24.0 25 5
25.8 25 8
123
12.3 13 1
13.1 13 1
39 7 39 7
39.7 41 4
27.7 27 7 27 7 29 4
13.8 138 138 147
35 5 50
MOCP
30
40
30
15
50
35 35 40 40 40
20
60
40
20
60
Loading...
+ 18 hidden pages