Carrier 48LJD User Manual

Page 1
48LJE/LJF004
48L J D/L J E/L J F005-007
HEATING & COOLING
Single-Package Rooftop Heating/Cooling Units
Installation, Start-Up, and Service Instructions
CONTENTS
SAFETY CONSIDERATIONS ...
INSTALLATION .......................................................1
Step 1 — Provide Unit Support
• ROOF CURB
• SLAB MOUNT
Step 2 — Field Fabricate Ductwork .........................
Step 3 — Install External Trap for
Condensate Drain ..................................................
Step 4 — Rig and Place Unit ....................................
• POSITIONING
Step 5 — Install Flue Hood........................................
Step 6 — Install Gas Piping Step 7 — Make Electrical Connections
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
• HEAT ANTICIPATOR SETTINGS
Step 8 - Make Outdoor-Air Adjustments and
Install Outdoor-Air Hood
• MANUAL OUTDOOR-AIR DAMPER
• TWO-POSITION DAMPER
• OPTIONAL ECONOMIZER
Step 9 — Adjust Evaporator-Fan Speed..................13
• DIRECT DRIVE MOTORS
• BELT DRIVE MOTORS
START-UP
................
................................
.....................................
...................
.......................................
SERVICE ..................
TROUBLESHOOTING
19
1
10
20,21 21-25 26-31
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical com ponents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service per
sonnel. When working on air-conditioning equipment, ob serve precautions in the literature, tags and labels attached
to the unit, and other safety precautions that apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.

A WARNING

Disconnect gas piping from unit when leak testing at pressure greater than V2 psig. Pres sures greater than ’/2 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than
■ /2 psig, it must be replaced before use. When
pressure testing field-supplied gas piping at
i
pressures of V2 psig or less, a unit connected
to such piping must be isolated by manually
closing the gas valve(s).
Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.
Unit is shipped in the vertical discharge configuration. To convert to horizontal configuration, remove screws from side duct opening covers and remove covers. Using the same screws, install covers on vertical duct openings with the
insulation-side down. Seals around duct openings must be
tight. See Fig. 1.
IMPORTANT: An external filter kit MUST be used or the filters MUST be field-installed outside the unit on horizontal discharge applications with optional econ omizer. Otherwise, the economizer must be partially removed to access the filters. The area of the field­installed filters should be equal to the area of the factory­installed filters.
Step 1 — Provide Unit Support
ROOF CURB — Assemble and install accessory roof curb in accordance with instructions shipped with curb. See Fig. 2. Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb, not to the unit. If gas, electric power, or control power is to be routed through the curb, attach the accessory thm-the-curb
service connection plates to the roof curb in accordance with the accessory installation instmctions. Connection plates must be installed before unit can be set on roof curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket sup
plied with the roof curb as shown in Fig. 2. Improp
erly applied gasket can result in air leaks and poor unit performance.
Curb should be level. Unit leveling tolerances are shown in Fig. 3. This is necessary for unit drain to function prop erly. Refer to Accessory Roof Curb Installation Instruc tions for additional information as required.
SLAB MOUNT (Horizontal Units Only) — Provide a level concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
Step 2 — Field Fabricate Ductwork — Secure all
ducts to roof curb and building structure on vertical units.
Do not connect ductwork to unit. For horizontal applica
tions, field-supplied flanges should be attached to horizon tal discharge openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external duct work, joints, and roof openings with counter flashing and­mastic in accordance with applicable codes.

A WARNING

INSTALLATION
Book|1 |4 PC 111 Catalog No. 564-987 Printed in U S A Form 48LJ-7SI Pg 1 4-93 Replaces: 48LJ-5SI Tab la 6a
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.
Page 2
Ducts passing through an unconditioned space must be
insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with ap plicable fire codes.
A minimum clearance is not required around ductwork. Cabinet return air static shall not exceed —.35 in. wg with economizer or — .45 in. wg without economizer.
Step 3 — Install External Trap for Condensate Drain — All units must have an external trap added for
condensate drainage. A y4-in. NPT connection is located on the side of the unit. Use a trap at least 4-in. deep and protect against freeze-up.
If drain line is run to a drain, pitch line away from unit at
1 in. per 10 ft of run. Do not use a pipe size smaller than
the unit connection. See Fig. 4 for more details.
Step 4 — Rig and Place Unit — Inspect unit for
transportation damage. File any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 and Fig. 5 for additional infor mation. Operating weight is shown in Table 1 and Fig. 5.
Lifting holes are provided in base rails as shown in Fig. 6. Refer to rigging instructions on unit.

A CAUTION

I
______
POSITIONING — Maintain clearance around and above unit to provide minimum distance from combustible mate rials, proper airflow, and service access. See Fig. 6. A prop
All panels must be in place when rigging.
_________
erly positioned unit will have the following clearances between unit and roof curb: 'A-in. clearance between roof curb and base rails on each side and front of unit; U/32-in. clearance between roof curb and rear of unit. (See Fig. 2, section C-C.)
Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of con taminated air.
Be sure that unit is installed such that snow will not block the combustion intake or flue outlet.
Unit may be installed directly on wood flooring or on Class A, B, or C roof-covering material when roof curb is used.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Locate mechanical draft system flue assembly at least 48 in. from any opening through which combustion prod ucts could enter the building, and at least 48 in. from an adjacent building. When unit is located adjacent to public walkways, flue assembly must be at least 7 ft above grade.
Flue vent discharge must have a minimum horizontal clear
ance of 4 ft from electric and gas meters, gas regulators, and gas relief equipment.
Flue gas can deteriorate building materials. Orient unit
such that flue gas will not affect building materials.
Adequate combustion-air space must be provided for proper
operation of this equipment. Be sure that installation complies with all local codes and Section 5.3, Air for Com
bustion and Ventilation, NFGC (National Fuel Gas Code),
|
ANSI (American National Standards Institute) Z223.1-
1984 and addendum Z223.la-1987. In Canada, instal lation must be in accordance with the CAN LB 149.1 and CAN1.B149.2 installation codes for gas burning appliances.
Page 3
c
!J------------------
—1
-------------------
ROOF CURB
ACCESSORY
50DJ900771
- 1
50DJ900781
A
1 '-2” [356]
2"-0'
[610]
UNIT SIZE
48LJE/LJF004
48UD/LJE/UF005-007
NOTES:
1. Roof curb accessory is shipped unassembled
2. Insulated panels.
3 Dimensions in [ ] are in millimeters
4. Roof Curb: galvanized steel
5 Attach ductwork to curb (Flanges of
duct rest on curb.)
6 Service clearance is 4 ft on each side.
Direction of airflow
UNIT SIZE
48LJE/LJF004
48LJD/LJE/LJF005-007
“E”
GAS
%" [19] NPT
“F”
POWER
%" [19] NPT 3/4" [19] NPT
“G”
CONTROL
CONNECTOR
PKG ACY
50DJ900791
Fig. 2 — Roof Curb Dimensions
Page 4
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
/■
A-B
0.5 1.0 1.0
B-C
A-C

Fig. 3 — Unit Leveling Tolerances

NOTE: Trap should be deep enough to offset maximum unit static
difference, A 4-in. trap is recommended.
PLACE ALL SEAL STRIPS
IN PLACE BEFORE PLACING
UNIT ON ROOF CURB.
SEE DETAIL DUCT END
"A"
Fig. 4 — External Trap Condensate Drain
DETAIL "A"
NOTES:
1. Dimensions in ( ) are in miilimeters 2 Hook rigging shackles through holes in base rail, as shown in de
tail “A.” Holes in base rails are centered around the unit center of gravity Use wooden top skid when rigging to prevent rigging straps from damaging unit
MAX
UNIT
48LJE/LJF004 530 240
48LJD/LJE/LJF005 540 245 48LJD/LJE/LJF006 48LJD/LJE/LJF007 615 279
WEIGHT
Lb
560 254
Kg

Fig. 5 — Rigging Details

3 Unit weights do not include economizer. See Table 1 for
A B
in.
73.69
mm
1872
economizer weights.
All panels must be in place when rigging.
in.
35.5
mm in.
902

A CAUTION

C
mm
32.52 826
Page 5
Table 1 — Physical Data
BASE UNIT 48 NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb)
Unit
Economizer
Roof Curb
COMPRESSOR
Quantity Oil (oz)
REFRIGERANT TYPE
Operating Charge (Ib-oz) 6-0
CONDENSER FAN Propeiier Type
Quantity...Diameter (in.) 1 ..26.0 Nominal Cfm
Motor Hp...Rpm
CONDENSER COIL
Rows...Fins/in. Total Face Area (sq ft)
EVAPORATOR FAN
Size (in.) Type Drive
Nominal Cfm
Maximum Continuous Bhp
Motor Frame Nominal Rpm High/Low
Fan Rpm Range
Motor Bearing Type Maximum Fan Rpm Motor Pulley Pitch Diameter A/B (in.)
Fan Pulley Pitch Diameter (in.) Belt — Type...Length (in.) Pulley Center Line Distance (in.) Speed Change Per Full Turn of
Moveable Pulley Flange (rpm)
Movable Pulley Maximum Full Turns
From Closed Position
Factory Setting — Full Turns Open Factory Speed Setting (rpm) Fan Shaft Diameter at Pulley (in.)
EVAPORATOR COIL
Rows...Fins/in. Total Face Area (sq ft)
FURNACE SECTION
Burner Orifice Diameter (in. ...drill size)*
Natural Gas — Std Liquid Propane — Alt
Thermostat Heat Anticipator Setting (amps)
208/230/460 V
First Stage
Second Stage
Gas Input
First Stage
Second Stage
Efficiency (Steady State) (%)
Temperature Rise Range
Manifold Pressure (in. wg)
Natural Gas — Std Liquid Propane — Alt
Field Gas Connection Size (in.)
HIGH-PRESSURE SWITCH (psig)t
Standard Compressor Internal Relief
Cutout Reset (Auto.)
LOSS-OF-CHARGE/LOW-PRESSURE SWITCHf
(liquid Line) (psig) Cutout Reset (Auto.)
FREEZE PROTECTION THERMOSTATf
Opens (F) Closes (F)
OUTDOOR-AIR INLET SCREENS
Qty...Size (in.)
RETURN-AIR FILTERS
Qty...Size (in.)
Std Alt Direct
Std Alt 81 Std Alt 48
Std Ait 1080/970 Std Alt
Std Alt Std Alt Std Alt Std
Alt Std Alt Std Alt Std
Alt
std
Alt
LJE/LJF004
3
530
34
115
Reciprocating
1
55
4600
Уз 850
1.. 17 12 25
10 X 10
Direct
1200
34
48
860/845
— —
Baii
2100
— —
— — — — — — — — —
— — —
2. 15 2.. 15 4 17 55 55
113 33 089 43
.14
-/14
74,000/82,000
-/115,000
80
25-55/55-85
35
3.5 .5
LEGEND
Bhp — Brake Horsepower
*The 48LJD005-007 and 48LJE004 (74,000 Btuh) units have 2 burners The 48LJE005-007 and 48LJF004 (115,000 Btuh) units and
the 48LJF005-007 (150,000 Btuh) units have 3 burners
flndioates a FlOP (Factory-instalied Option) that requires a control kit.
LJD/LJE/LJF005
4
540
34
115 115
LJD/LJE/LJF006
560 615
Scroil
1 1
55
7-6 8-3 9-12
1 ..26.0 1...26.0
4600
Уз...850
Enhanced Copper Tubes, Aiuminum Lanced Fins
2.. 17
12.25
10 X 10
Direct
Beit
1600
.81
1 20
48
56
1080/970
_
970-1310
Bali
2100
1 9/2 9
3.5
A 39
A 31
14 7-15 5
68
5 3
1110
5/8 У2
Enhanced Copper Tubes, Aluminum Doubie Wavy Fins, Acutroi'“ Feed Device
113. 33/113 33/129 30 113. 33/113 33/129. 30
.089.. 43/089 .43/.102 .38 089 43/089 43/102 38
.14 14
-/-/14
74,000/115,000/120,000 74,000/115,000/120,000
-/-/150,000 80 80
25-55/35-65/50-80
35
3.5 .5
R-22
Centrifugai Type
-/-/150,000
25-55/35-65/50-80
625 428 320
7 ± 3
22 ± 7
30 ± 5 45 ± 5
Cieanabie
1
..20 X 24 X 1
Throwaway
2.. 16 X 25 X 2
4100
У3...850 Уз . 850
2.. 17 2.. 17
12.25
10 X 10
Beit
2000
1 80
900-1300
Baii Bail
2100
2 4/3 4
14 7-15.5
1060 1230
3.. 15 4...15
-/-/14
5 6
34 34
115
Reciprocating
LJD/LJE/LJF007
70 65
1 . 26.0
4i00
12.25
10 X 10
56
— —
— —
4.5 45
— — — —
80
5
_
3 3
Beit
2400 2 40
1070-1460
2100
2.8/3.8
A 39
14 7-15 5
113 33/113 33/.129.30 089 43/089 43/102 38
-/-/14
74,000/115,000/120,000
-/-/150,000
25-55/35-65/50-80
35
3.5 3.5 .5 .5
56
— — —
79
Ув
5.5
3.5
1
5
14
80
Page 6
STD UNIT
UNIT
48LJE/LJF004 530 48LJD/LJE/UF005 540 48UD/UE/UF006 48UD/UE/UF007 615 279
WEIGHT Lb
560
Kg 240 245 254
ECONOMIZER
WEIGHT
Lb
Kg
34
15.4 34 15.4 34 154 110 34 154 120
CORNER
WEIGHT (A)
Lb
Kg
104
47.2 97
106 48 1
49.9
54.4
CORNER
WEIGHT (B)
Lb
Kg
44.0
98 44.5 102 46 3 112 50.8
RIGHT SIDE
'Indicates horizontal center of gravity flndicates vertical center of gravity
NOTES:
1. Dimensions in [ ] are in millimeters. Center of Gravity.
3 Direction of airflow
4. On vertical discharge units, ductwork is to be
attached to accessoiy roof curb only. For hor izontal discharge units, field-supplied flanges should be attached to horizontal discharge openings and all ductwork should be at tached to the flanges.
5 Minimum clearances are as follows (local codes
or jurisdiction may prevail): NOTE: When installing these units, use the maximum clearance stated for your application a Between unit, flue side, and combustible
surfaces, 36 inches. (Minimum clearance to combustibles, flue side, is 18 in for units with accessory flue discharge deflector.)
b. Bottom to combustible surfaces (when not
using curb), 0 in. for LJD,LJE units and
1 in. for LJF units.
c. Condenser coil for proper airflow, 36-in one
side, 12 in the other The side getting the greater clearance is optional
d. Overhead, 60 in to assure proper con
denser fan operation e. Horizontal supply and return end, 0 inches f Between units, control box side, 42 in per
NEC (National Electrical Code), g Between unit and ungrounded surfaces, con
trol box side, 36 in. per NEC. h. Between unit and block or concrete walls
and other grounded surfaces, control box
side, 42 in. per NEC.
6. With the exception of the clearance for the
condenser coil and combustion side, as stated in Notes 5a, b, and c, a removable fence or barricade requires no clearance
7 Units may be instailed on combustible floors
made from wood or class A, B, or C roof cov ering material
UNIT
48LJE/LJF004 48LJD/LJE/LJF005 162 48LJD/LJE/LJF006 168 48LJD/LJE/LJF007
WEIGHT (C)
Lb
159
185
FRONT
CORNER
Kg
72.1 171
73.5 174 78.9
76.2
83.9 198
CORNER
WEIGHT (D) Lb
77.6
81.6
180
89.8
Kg
Connection Sizes
1%" Dia [351 Field Power Supply Hole
A
2" Dia [50.51 Power Supply Knockout
B
2¥i6" Dia [551 Charging-Port Hole
c
%" [221 Field Control Wiring Hole
D
%" Condensate Drain
E
V2"-14 NPT Gas Connection
F
LEFT SIDE

Fig. 6 — Base Unit Dimensions

FRONT
O'-O 3/B r’OJ
L
Page 7
i'
Step 5 — Install Flue Hood — Flue hood and screen
are shipped screwed to the burner compartment access panel. Remove from shipping location and using screws provided, install flue hood and screen in location shown in Fig. 7.
Step 6 — Install Gas Piping — Unit is equipped for
use with type of gas shown on nameplate. Refer to local building codes, or in the absence of local codes, to ANSI Z223.1-1984 and addendum Z223-1A-1987 entitled Na tional Fuel Gas Code. In Canada, installation must be in accordance with the CANl.B 149.1 and CAN1.B149.2 in stallation codes for gas burning appliances.
For natural gas applications, gas pressure at unit gas con
nection must not be less than 4 in. wg or greater than
13.0 in. wg while unit is operating. On 48LJ005,006,007 high heat units, the gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13 in. wg while the unit is operating. For propane applications, the gas pressure must not be less than 5 in. wg or greater than 13 in. wg at the unit connection.
Size gas supply piping for 0.5 in. wg maximum pressure
drop. Do not use supply pipe smaller than unit gas connec
tion. Support gas piping as shown in the table in Fig. 8. For example, a %-in. gas pipe must have one field-fabricated support beam every 8 ft. Therefore, an 18-ft long gas pipe would have a minimum of 2 support beams, a 48-ft long pipe would have a minimum of 6 support beams.
See Fig. 8 for typical pipe guide and locations of exter
nal manual main shutoff valve.
9” MINIMUM CLEARANCE FOR PANEL REMOVAL
MANUAL GAS GAS
I SHUTOFF VALVE* REGUUTOR*
48" MINIMUM -
DRIP LEG PER NFGC
ROOF CURB
FROM GAS METER
LEGEND
NFGC — National Fuel Gas Code "Field supplied. NOTE: Follow all local codes
FIELD-FABRICATED* SUPPORT
SPACING OF SUPPORTS
STEEL PIPE
NOMINAL
DIAMETER
(In.)
%
*/4 or 1 8
1’/4 or larger 10
Fig. 8 — Gas Piping Guide (With Accessory
Thru-the-Curb Service Connections)
7
X
DIMENSIONS
(feet)
6

Step 7 — Make Electrical Connections

A WARNING

Unit cabinet must have an uninterrupted, unbroken elec trical ground to minimize the possibility of personal in
jury if an electrical fault should occur. This ground may
consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for elec trical ground when installed in accordance with NEC
(National Electrical Code), ANSI/NFPA (National Fire Protection Association), latest edition, and local elec trical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in the in
staller being liable for personal injury of others.
FIELD POWER SUPPLY - All units except 208/230-v units are factory wired for the voltage shown on the name plate. If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by moving the black wire from the 230-v orange wire on the trans former and connecting it to the 200-v red wire from
the transformer. The end of the orange wire must then be insulated.
Refer to unit label diagram for additional information. Wiring leads are provided for field service. Use copper con ductors only when splice connectors are used.
When installing units, provide a disconnect per NEC.
All field wiring must comply with NEC and local require ments. In Canada, electrical connections must be in accor dance with CSA (Canadian Standards Association) C22.1 Canadian Electrical Code Part 1.
Install conduit through side panel openings indicated in Fig. 6. Route power lines through connector to terminal connections as shown in Fig. 9.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (also
see Table 2). On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in the legend for Table 2, Note 2 to
determine the percent voltage imbalance. Operation on im proper line voltage or excessive phase imbalance consti
tutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.
FIELD CONTROL WIRING - Install a Carrier-approved
accessory thermostat assembly according to installation in
structions included with the accessory. Locate thermostat
assembly on a solid wall in the conditioned space to sense
average temperature in accordance with thermostat instal
lation instmctions. Connect thermostat wires to terminal board.
Route thermostat cable or equivalent single leads of col ored wire from subbase terminals through connector on unit to low-voltage connections (shown in Fig. 10).
Connect thermostat wires to matching screw terminals of low-voltage connection board. See Fig. 10.
NOTE; For wire runs up 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C min imum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.
Pass the control wires through the hole provided in the end panel; then feed wires through the raceway built into the comer post to the 24-v barrier located on the left side of the control box. See Fig. 11. The barrier provides the UL (Underwriters’ Laboratories) required clearance between high­and low-voltage wiring.
Page 8
Table 2 — Electrical Data
VOLTAGE
UNIT
48LJE/LJF004
(3 Tons)
48LJD/LJE/LJF
005
(4 Tons)
48LJD/LJE/LJF
006
(5 Tons)
48LJD/LJE/LJF
007
(6 Tons)
IMPORTANT: Optional, alternate evaporator-fan motor and drive are not available for 48LJ006,007 units. Contact your local Carrier representative for more information about field-installed motors
COMPR FLA HACR IFM LRA MCA MOCP OFM
RLA
*Fuse or HACR circuit breaker
NOTES:
1. In compliance with NEC (National Electrical Code) requirements for multi motor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shali be fuse or HACR breaker Canadian Standards Association (CSA) units may be fuse or circuit breaker
2 Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalanoe in supply voltage is greater than 2% Use the following formula to determine the percent voltage im
balance.
% Voltage Imbalance
100 X
NOMINAL
V-PH-HZ
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60 230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
LEGEND
Compressor Full Load Amps Heating, Air Conditioning and Refrigeration
Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection
Outdoor (Condenser) Fan Motor
Rated Load Amps
max voltage deviation from average voltage
average voltage
IFM
TYPE
Std
Alt 3.8 28.1/28 1
Std
Alt 38
Std
Alt 1.9 105
Std
Alt
Std
Alt 57 38.6/38 6
Std
Alt
Std
Alt 2.8 13.5
Std
Alt
Std
Std
RANGE
Min Max RLA
187 254 179
187 254 11 2
414
508
632 45
518
187 254 24 8
187 254 157
414
508 78
632 55
518
187 254 27.8 187
254 414 508 96 518 632 83 187 254 21 9 414 508 518 632 96
COMPR
(each)
6 1
19.2
104
OFM
LRA FLA FLA FLA
93 1 9
80 1 9 40 1 0
29 1 9
127 1 9
99 1.9 50 1 0
40 1.9
135 1 9 85 .57 105 1 9
55 1 0 45 1 9
142 1 9 5.8 57 35.1/35.1
72
1 0
58 5 1 9
11 0
FAN MOTOR
2.8
28
1 5
2.8
38 7.9 38
3.8
5.7 27 2/27.2
1 9
38
5.7 9.9
8.5 .57
4.5 85
2.6
Example: Supply voltage is 460-3-60.
ABC BC = 464v
NOTE: The 575-v units are CSA only Determine maximum deviation from average voltage (AB) 457 - 452 = 5 V
(BC) 464 - 457 = 7 V (AC) 457 - 455 = 2 V
Maximum deviation is 7 v. Determine % voltage imbalance
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately
57
.57
30
57
57
57
.30
57
30
.57
30
57
COMBUSTION
IFM
POWER SUPPLY
MCA
27 1/27 1
18 7/18.7 25/25 18/18 19 7/19.7
101
7.5
36 7/36.7
25 3/25.3
126
9.2
45 2 60
34.4/34.4 40/40 34/34
17.5
14.5
16.6 172
AB = 452V AC = 455V
Average Voltage
-----------
= 1 53%
DISCONNECT SIZE
MOCP* FLA
35/35 35/35 27/27
25/25 19/19
15 15 10 15 7
15 45/45 45/45 37/37 30/30 25/25 113/113 35/35 27/27 116/116
15
26/26
10
8
35/35
12
20 13
15
15
9
10
44 164
20 17 81 20 14
40/40 34/34 188/188
20 16 20 17 81
452 4- 464 4- 455
_ 1371
3
= 457
7
457
LRA
105/105
107/107
92/92 94/94
46 46 34 34
141/141
144/144
56 58 45
47
134/134
57
95
Page 9
c
COMP EQUIP GND IFC NEC
LEGEND
Contactor Compressor Equipment Ground Indoor (Evaporator) Fan Contactor National Electrical Code
TO
c

Fig. 9 — Power Wiring Connections

LEGEND
AHA CC
TC
NOTE: Connect Y2 when unit is equipped with an economizer.
Adjustable Heat Anticipator Cooling Compensator Thermostat-Cooling
TH — Thermostat-Heating
---------
Field Wiring
----------
Factory Wiring

Fig. 10 - Low-Voitage Connections

208 / 230-3-60
460-3-60
(SIZES 004-006)
575-3-60
(SIZES 004-007)
CONNECTION BOARD LED
RACEWAY
HOLE IN END PANEL--­(HIDDENV
LED — Light-Emitting Diode
FIELD POWER SUPPLY

Fig. 11 — Fieid Control Wiring Raceway

DISCONNECT
PER NEC
INTEGRATED GAS UNIT CONTROLLER (IGC)
Page 10
HEAT ANTICIPATOR SETTINGS - Set heat anticipator settings at. 14 amp for the first stage and . 14 amp for second­stage heating, when available.

Step 8 - Make Outdoor-Air Adjustments and Install Outdoor-Air Hood

MANUAL OUTDOOR-AIR DAMPER - The outdoor-air hood and screen are attached to the basepan at the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for building. Record amount for use in Step 8.
2. Remove and save evaporator coil access panel and screws. See Fig. 12.
3. Separate hood and screen from basepan by removing the 4 screws securing them. Save all screws.
EVAPORATOR COIL ACCESS ? PANEL \
SCREWS
(SIDE) “
4. Replace evaporator coil access panel.
5. Place hood on front of evaporator coil access panel. See Fig. 13 for hood details. Secure top of hood with the 4 screws removed in Step 3. See Fig. 14.
6. Remove and save 6 screws (3 on each side) from sides of the manual outdoor-air damper.
7. Align screw holes on hood with screw holes on side of manual outdoor-air damper. See Fig. 13 and 14. Secure hood with 6 screws from Step 6.
8. Adjust minimum position setting of the damper blade by adjusting the manual outdoor air adjustment screws on
the front of the damper blade. See Fig. 12. Slide blade vertically until it is in the appropriate position deter
mined by Fig. 15. Tighten screws.
9. Remove and save screws currently on sides of hood. In sert screen. Secure screen to hood using the screws. See
Fig. 14.
SCREW HOLES (TOP)
HOOD
MANUAL OUTDOOR-AIR » ADJUSTMENT SCREWS
POSITION SETTING SCALE
Fig. 12 — Damper Panel with Manual Outdoor-Air
Damper Installed
HOOD SCREEN LOCATION (SCREEN NO SHOWN)
Fig. 14
Outdoor-Air Damper with Hood
Attached
OUTDOOR AIRFLOW (cfm x 100)
Fig. 15 - Position Setting
10
Page 11
TWO-POSITION DAMPER - The outdoor-air hood and screen are attached to the basepan at the bottom of the unit.
Assembly:
1. Determine quantity of ventilation air required for build ing. Record amount of air for use in Step 9.
2. Remove and save evaporator coil access panel and screws. See Fig. 16.
3. Separate hood from basepan by removing the 4 screws securing the hood. Save screws.
4. Insert two-position damper plug from wiring harness (supplied with the unit) into the wiring harness (sup plied with the two-position damper).
5. Replace evaporator coil access panel.
6. Place hood on front of evaporator coil access panel. See Fig. 13 for hood details. Secure top of hood with the 4 screws removed in Step 3. See Fig. 14.
EVAPORATOR COIL ACCESS PANEL
SCREW HOLES (SIDE)
EVAPORATOR COIL ACCESS PANEL
BLOCK-OFF PANEL
------
'
mm
Fig. 17 — Access Panel Location
i
OUTDOOR-AIR
ADJUSTMENT
SCREWS
POSITION SETTING SCALE
Fig. 16 — Damper Panel with Two-Position
Damper Installed
7. Remove and save 6 screws (3 on each side) from sides of the two-position damper.
8. Align screw holes on hood with screw holes on side of two-position damper. See Fig. 13 and 14. Secure hood with 6 screws from Step 7.
9. Determine two-position damper setting by using Fig. 15. Set the damper panel position using the air ad justment screws. See Fig. 16. Tighten screws.
10. Remove and save 4 screws currently on sides of hood. Insert screen. Secure screen to hood using the 4 screws.
See Fig. 14.
OPTIONAL ECONOMIZER — The economizer hood as sembly is packaged and shipped in the filter section. Damper blades are installed at the factory and the economizer is shipped in the vertical position.
Assembly:
1. Determine quantity of ventilation air required for build ing. Record amount of air for use in Step 8.
2. Remove evaporator coil access panel (see Fig. 17). Save panel and screws.
3. Assemble outdoor-air hood top and side plates as shown in Fig. 18. Install seal strips on hood top and sides. Put aside screen retainer and screws for later assembly. Do
not attach hood to unit at this time.
4. The block-off panel should be removed from the evap orator coil access panel and discarded. Save screws.
See Fig. 17.
HOOD SIDES AND TOP ASSEMBLED

Fig. 18 — Outdoor-Air Hood Details

5. Remove screws securing barometric relief damper, if desired. See Fig. 19.
6. To convert to horizontal discharge application:
a. Remove filters from filter track.
IMPORTANT: Filters must be installed outside the
unit on horizontal discharge applications with econo mizer. Otherwise, economizer must be partially re moved to access the filters. The area of the field­installed filters should be equal to the area of the factory­installed filters.
Rotate economizer 90 degrees until economizer mo
b.
tor faces condenser section (see Fig. 20). If neces
sary, disassemble economizer to replace filter.
Rotate barometric relief damper 90 degrees so that it
c.
opens and closes vertically.
11
Page 12
d. Install horizontal discharge block-off plate over
opening on the access panel. Block-off plate MUST be installed before installing hood assembly (see Fig. 21).
NOTE: Install spacers at the same time as the hori zontal block-off plate using same screws. The spac ers are used to cover gaps between the economizer assembly and the unit.
ECONOMIZER
WIRE
HARNESS PLUGS
BAROMETRI! RELIEF DAMPER^
Fig. 19 — Economizer Installed in Unit
BLOCK-OFF PLATE

Fig. 21 — Horizontal Discharge Block-Off Plate

7. Insert economizer plug from the wiring harness (sup plied with the unit) into the wiring harness plug (sup plied with the economizer). See Fig. 19.
8. Determine economizer damper position setting (see Fig. 22). Adjust damper setting by adjusting screws on
the position setting bracket (see Fig. 23). Slide posi tion setting bracket until top screw (see Fig. 23) is in the position determined by Fig. 22. Tighten screws.
9. Install evaporator coil access panel with screws saved from Step 2.
10. Fasten hood top and side plate assembly to unit with screws saved from the block-off panel removal (see Fig. 18).
11. Remove tape from outdoor-air thermostat (OAT). Fas ten OAT to inside of hood using screws and speed clips provided (see Fig. 24). Make sure OAT terminals are up.
12. Place knob, supplied with economizer, on OAT. Set it for 3 F below indoor room thermostat setting. If ac cessory solid-state enthalpy control (EC) is used in
stead of the OAT, see instructions shipped with EC for
installation and adjustment (see Fig. 24).
13. Connect OAT per Fig. 25.
14. Slide outdoor-air inlet screens into screen track on hood
side plates. While holding screens in place, fasten screen retainer to hood using screws provided.
15. Turn on base unit power.
BAROMETRIC RELIEF DAMPER
Fig. 20 — Horizontal Economizer Installation
(90 Degree Rotation)
12
Page 13
Example:
Given —
Return-Air Negative Static Pressure .........................0 2 in wg
Outdoor Air Determine —
Setting = 5

Fig. 22 — Economizer Damper Minimum Position Setting

Fig. 23 - Minimum Position Damper Setting
OUTDOOR AIRFLOW (cfm x 100)
......................................................
Step 9 — Adjust Evaporator-Fan Speed — Ad
just evaporator-fan speed to meet jobsite conditions.
Table 3 shows fan rpm at motor pulley settings. Refer to Tables 4-15 to determine fan speed settings.
DIRECT DRIVE MOTORS — The evaporator-fan motor factory speed setting is shown on label diagram affixed to base unit. If other than factory setting is desired, refer to label diagram for motor reconnection.
BELT DRIVE MOTORS — Ean motor pulleys are factory
set for speed shown in Table 1.
NOTE: Before adjusting fan speed, make sure the new fan
speed will provide an air temperature rise range as shown in Table 1.
To change fan speed:
1. Shut off unit power supply.
2. Loosen belt by loosening fan motor mounting nuts. See Fig. 26.
3. Loosen movable pulley flange setscrew (see Fig. 27).
4. Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. In creasing fan speed increases load on motor. Do not ex ceed maximum speed specified in Table 1.
5. Set movable flange at nearest key way of pulley hub and tighten setscrew. (See Table 1 for speed change for each full turn of pulley flange.)
900 cfm
13
Page 14
OR ACCESSORY ENTHALPY CONTROL
GRAY
---------------
OAT
---------------------------------------
Fig. 25 — Wiring Connections for
Outdoor-Air Thermostat
■i\fcTOR MOUNTffviS
ieiATe NUTSJ
ASSvAvA'A'Mv.
ORANGE-
HOOD.
"ERMWALS
bUTOObR-AiRTHERMOStATl
(TERMiNAl-S ARE UP) ,; |
iii
Fig. 24 — Outdoor-Air Thermostat/
Enthalpy Control Installation
\
HOOD

Fig. 26 - Belt Drive Motor Mounting

Fig. 27 — Evaporator-Fan Pulley Adjustment
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from mounting.
To adjust belt tension:
1. Loosen fan motor mounting nuts.
2. Slide motor mounting plate away from fan scroll for proper belt tension ('/2-in. deflection with one finger).
3. Tighten motor mounting nuts.
4. Adjust bolt and tighten nut to secure motor in fixed
position.
14
Page 15
Table 3 — Fan Rpm at Motor Pulley Settings
UNIT
48LJD/LJE
005* 1310 006 007 1460
0
1300
'Indicates alternate motor.
Table 4 — Fan Performance, 48LJE/LJF004 Vertical
AIRFLOW
(Cfm)
900 1000 1100 1200 1300 1400 1500
LEGEND
Bhp — Brake Horsepower ESP — External Static Pressure
NOTE: Values Include losses for filters, unit casing, and wet coils.
MOTOR PULLEY TURNS OPEN
Va 1
1285 1245 1260 1220 1420 1380
IVa
1210 1180 1340
2
2Va
1175 1140 1140
1100
1300
1265
3
1110 1060 1230
3Va
1075 1020
1190
Discharge Units; Standard Motor (Direct)
LOW SPEED HIGH SPEED
208
ESP
0 46 0.17
0.44
0.40 0 32
0.28 0.24
0.22 0 16 0 27 0 18
230, 460, 575 208
Bhp
0.20 0.45
0.21
0.23
ESP Bhp
0 48 0.19 0.49 0.21 0.51
0.42 0.24 0 37 0.25 0 32 0.26
0.26 0 25
ESP
0.22
0.47 0.23 0.48
0.44 0.25 0.45
0.38 0.27 0.40
0.32 0.29 0.34
0.28
0.26 0.30 0.28
0.33
0.20 0.31 0.21
Bhp
4
1005 970
1040
980 940 900
1110
1150
230, 460, 575
ESP
Bhp
0.25
0.27
0.29
0.31
0.32
0.33
0.34
4Va
5
1070
Table 5 — Fan Performance, 48LJE/LJF004 — Vertical
Discharge Units; Alternate Motor (Direct)
AIRFLOW
(Cfm)
900
1000 1100 1200 1300 1400 1500
ESP Bhp ESP
0.77
0.70 0 38
0.25 0.53 0 33
LEGEND
Bhp — Brake Horsepower ESP — External Static Pressure
NOTE: Values include losses for filters, unit casing, and wet coils.
LOW SPEED HIGH SPEED
208 230, 460, 575 208 230, 460, 575
0.83 0 38 0.97 0.48 1.09 0.60
0.36
0.62 0 53 0.44 0.58 0 44
0.35 0.50
0 75
0 66 0.45 0.80 0 53 0.92
0.41 0 48 0.50
0 42
Bhp
0 41
0 48 0.72 0.56 0 84 0 65
0.50 0.64 0.60 0.75 0.68
0.54
0.58 0.47 0.65
Bhp
ESP
0.89 0 51 1.01
0.63 0 67 0 69
0.56
ESP
0.58
Bhp
0.62 0 64
0 72
15
Page 16
Table 6 — Fan Performance, 48LJD/LJE/LJF005 Vertical Discharge
Units; Standard Motor (Direct)
AIRFLOW
(Cfm)
1200 1300 1400 1500
1600 1700
1800 1900 2000
Bhp — Brake Horsepower ESP — External Static Pressure
NOTE: Values include losses for filters, unit casing, and wet coils.
0.53
LEGEND
LOW SPEED
208
ESP Bhp
0.44
0 44
0,48
0.35
0.50
0.25
0 53 0 33
0.16 0 57
0.09
0 58
0 00
0.61
_
230, 460, 575 ESP
0 58
0.50 0 42
0 24 0 15 0 06
Bhp ESP Bhp ESP
0 48
0.50
0.54 0 56 0 63
0.58 0 60 0 63 0 65
HIGH SPEED
0.56
0.60 0 65 0 69 0 73
230, 460, 575
Bhp
0.84
0.75 0.68
0.67 0.69
0.58 0 72 0 50 0.74 0 40
0.32
0.24
0 65
0.76
0.78
0.79
208
0 72 0 64
0.47 0 38 0 68 0 30
0.22 0 71
0.12
0.03 0.74 0.15 0.81
Table 7 — Fan Performance, 48LJD/LJE/LJF005 Vertical Discharge Units; Alternate Motor (Belt)
AIRFLOW
(Cfm)
1200 701 0.22 758 1300 1400 1500 836 1600 1700 925 0.55 981 1800
1900 1011
2000 1058 0 81 1100
Bhp — Brake Horsepower
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 5.) 2 indicates field-supplied motor and drive required 3 Maximum usable bhp is 1.2. Extensive motor and electrical test
ing on these units ensures that the full horsepower range of the
0.1
Rpm Bhp Rpm Bhp
747
0.27 800 0.34
792
0.33
0.39
0.47
881 964
0.63
0.73
LEGEND
02
0.28
847
0.40
897
0.46
0.54
945
0.61
1024
0.72
1068 0.79
0.85
1 0.3 1
Rpm Bhp
834 865 901 0.47 947 0.55
983 1020 0.68 1084 0 75 1120 1160
EXTERNAL STATIC PRESSURE (in. wg)
1 0.4
Rpm Bhp
0.35 914 0.42
0.41
945 0.52 960 0.56
1000 0.61 1132
0 62
1065 0.67 1172 1103 0 72 1202 0 88 1140 0.82
0.82
1172
0 90
1237
1 0.6 1
Rpm
1012 1050 1091
1230
0 91 1256
1 20
Bhp
0 56 0 62
0.67 0 72
0.77
0 97
1,18
motor can be utilized with confidence Using your fan motors up to the horsepower ratings shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
Values include losses for filters, unit casing, and wet coils Alternate motor drive range: 970 to 1310 rpm. All other rpms re quire field-supplied drive Use of field-supplied motor may affect wire sizing Contact Car rier representative to verify.
1 0.7 1 08
Bhp Rpm
Rpm
1056 0.59 1098
0 63 1132 0 68
1090 1130 0.70 1170 1207 0.86 1238 1243 1268
,.1,13:3
1310
1165
0.75 1205 0 98 1270 1 1.05 1350 1.16
1 07
1300!
Bhp Rpm Bhp
0.62 1180 0 68 1255 0.76
0.72 1242 0.82 0 82 1275 0 91 1330 0.98 0 92 1310 1.05 1350 1.08
1.15
L 1.0
____
1212 0.72
1 1-2
1
Rpm Bhp
1280 0 78 1310 0.89
1372 1.19
16
Page 17
Table 8 — Fan Performance, 48LJD/LJE/LJF006 Vertical Discharge Units; Standard Motor (Belt)
AIRFLOW
(Cfm)
1500 1600 1700 1800 1900
2000 2100 2200
2300 2400 2500
LEGEND
Bhp — Brake Horsepower NOTES:
1 Boldface indicates fieid-suppiied drive required. (See Note 6)
2. indicates field-supplied motor and drive required. 3 Maximum usable bhp is 1.8 Extensive motor and electrical test
ing on these units ensures that the full horsepower range of the
0.1 Bhp Rpm
Rpm
0.37
750
0.44
794
0.52 884 0.58
839 885 0.61
0.72
932
979 0 83 1008 1026 0.96 1051 1 01 1074 1.10 1095
1 25
1122
1 42
1170
1.61 1231
1218
808 846
924 965
1140 1185
0.2 Bhp
0.43
0.50
0.67
0.77 0 88
1.15
1.30
1.46 1 64
EXTERNAL STATIC PRESSURE (in. wg)

Table 9 — Fan Performance, 48LJD/LJE/LJF007 Vertical Discharge Units; Standard Motor (Belt)

motor can be utilized with confidence Using your fan motors up to the horsepower ratings shown will not result in nuisance trip ping or premature motor failure. Unit warranty will not be af fected.
4. Values include losses for filters, unit casing, and wet coils 5 Use of a field-supplied motor may affect wire sizing. Contact Car
rier representative to verify.
6 Standard motor drive range is 900 to 1300 rpm. All other rpms
require field-supplied drive.
LEGEND
Bhp — Brake Horsepower NOTES:
1 Boldface indicates field-supplied drive required (See Note 6)
indicates field-supplied motor and drive required.
Maximum usable bhp is 2 4 Extensive motor and electrical test
ing on these units ensures that the full horsepower range of the
motor can be utilized with confidence Using your fan motors up
to the horsepower ratings shown will not result in nuisance trip
ping or premature motor failure. Unit warranty will not be
affected. 4 Values include losses for filters, unit casing, and wet coils. 5 Use of a field-supplied motor may affect wire sizing Contact Car
rier representative to verify.
6. Standard motor drive range is 1070 to 1460 rpm. All other rpms
require field-supplied drive.
17
Page 18
Table 10 — Fan Performance, 48LJE/LJF004 Horizontal
Discharge Units; Standard Motor (Direct)
AIRFLOW
(Cfm)
900 1000 1100
1200 1300
1400
1500
LEGEND
Bhp — Brake Horsepower ESP — External Static Pressure
NOTE: Values include losses for filters, unit casing, and wet coils
LOW SPEED
208
ESP
0 53
0.48 0.20
0.43 0.21 0 36 0 28 0.24
0.20 0.26 0.24 0 11
230, 460, 575
Bhp
ESP Bhp ESP Bhp ESP
0.17
0 55
0.51 0.22
0.45 0.24 0.52 0.25
0.23 0.40 0 25
0.32 0 26 0 38 0.29
0 27
0.14
0.19
0 28 0.31 0.30 0 33
HIGH SPEED
208
0.63 0 21
0.57
0.23
0 47
0.27
0.21
0.31
230, 460, 575
0.64 0.25
0.60
0.54 0 29 0 47 0.31 0 41 0 32 0.33
0.22 0.34
Table 11 — Fan Performance, 48LJE/LJF004 Horizontal
Discharge Units; Alternate Motor (Direct)
AIRFLOW
(Cfm)
900
1000 1100 1200 1300 1400 1500
Bhp — Brake Horsepower ESP — External Static Pressure
NOTE; Vaiues include losses for filters, unit casing, and wet coils.
0 96 0.38 1 04 0.42
0.88 0.41 0.94 0 44
0.62 0.50
LEGEND
LOW SPEED HIGH SPEED
208
ESP
1.05 0.36 1 12
0 78 0.44 0 70 0.48
0 52 0.53
230, 460, 575 208
Bhp
ESP Bhp ESP Bhp ESP
0 39 1.17
1.09 0 49
0.54
1 00
0.78 0.63
0.69
0 85 0.48 0.92 0.56 1.01 0 76 0.50 0.84 0 60
0.68
0.59 0.58
230, 460, 575
0.47 1.26
0.52 1 08
0 65
1.17 0 60
0.94
0.87 0 78
Bhp
0.27
0.32
Bhp
0 58
0.63 0 65 0 68 0 69 0 72
Table 12 — Fan Performance, 48LJD/LJE/LJF005 — Horizontal
Discharge Units; Standard Motor (Direct)
AIRFLOW
(Cfm)
1200 0 78 1300 1400 1500 1600 1700 1800 1900 2000
LEGEND
Bhp — Brake Horsepower ESP — External Static Pressure
NOTE; Values include losses for filters, unit casing, and wet coils.
LOW SPEED HIGH SPEED
208
ESP
0.70 0.48 0.76 0.50 0 84 0.60 0 62 0 52
0.44 0.57
0.34
0.22
0.10 0.63
230, 460, 575 208 230, 460, 575
Bhp
ESP
0 44
0.85 0.48 0.92 0 56 1.01
0 50 0.68 0.54 0.78 0 63 0 53 0.59 0.58 0.69 0 65 0 78
0.50 0.60 0 61 0.68 0.70
0 58 0.40 0.63 0 53 0.69
0.61
0 30 0 20 0 68
0.09
Bhp ESP Bhp
0 65 0.45
0.69
0.71 0.54 0 78
0 37 0 73 0.48
0 74
0 29
ESP
0.94 0.68
0.87 0.69
0.62 0.76
0.39
Bhp
0.65
0.72
0.74
0 79 0 81
18
Page 19
Table 13 — Fan Performance, 48LJD/LJE/LJF005 Horizontal Discharge Units; Alternate Motor (Belt)
AlHhLUW
(Cfm)
1300 1400 1500 1600 836 0.39 1700 1800 1900 2000 1011 0.73 2100
Bhp — Brake Horsepower
NOTES;
1. Boldface indicates field-supplied drive required (See Note 5 )
2- indicates field-supplied motor and drive required
3 Maximum usable bhp is 1.2. Extensive motor and drive testing
on these units ensures that the full horsepower range of the
0.1
Rpm Bhp Rpm
701 0.22 758 0.28 834 747 0.27 800 0.34 865 0.41 792
0.33
881 0.47 945 925
0.55
964
0.63
1058
0.81
LEGEND
0.2 Bhp Rpm Bhp
847
0.40
897
0.46
0.54
981 0 61 1020 0.68 1024 0 72 1068
0 79
1100 0.85
0.3
901 0.47 947
983
1084 1120 1160 0 90 1237
EXTERNAL STATIC PRESSURE (in. wg)
0.4 0.6
Rpm Bhp Rpm Bhp
0.35
0.55
0 62 0 75
0.82
914 0.42
0.52
945 960
0.56 1091 0.67
1000
0 61 1132 0 72 1065 0 67 1103 0.72 1140 0 82 1172
0.91
1.20
0.56
1012
0.62 1090
1050
1172 0.77 1202 0.88 1243 0.98 1230 0 97 1268
1256.
1.18 1310 . 1.13is
motor can be utilized with confidence. Using your fan motors up to the horsepower ratings shown will not result in nuisance trip ping or premature motor failure Unit warranty will not be affected Values include losses for filters, unit casing, and wet coils. Alternate motor drive range: 970 to 1310 rpm. All other rpms re quire field-supplied drive.
Use of field-supplied motor may affect wire sizing. Contact Car rier representative to verify
0.7
Rpm Bhp
1056 0 59
0 63 1130 0 70 1170 0 75 1207 0.86
1.07 :::1300:;
0.8 Bhp
Rpm
0 62
1098 1132 0.68 1212
0.72 1242 0.82
1165
0 82
1205
0.92 1310 1.05 1350 1.08
1238 1270 1.05 1350
icis;:
1.0 1.2
Rpm Bhp Rpm Bhp
1180 0 68 1255 0.76
0.72
1275 0.91 1330 0.98
1.16 1372 1,19
1280
0 78
1310 0 89

Table 14 — Fan Performance, 48LJD/LJE/LJF006 Horizontal Discharge Units; Standard Motor (Belt)

AIRFLOW
(Cfm)
1500 1600 1700 1800 1900
2000
2100 2200
2300 2400
(
2500
Bhp — Brake Horsepower
NOTES:
1. Boldface indicates field-supplied drive required (See Note 6.)
2. indicates field-supplied motor and drive required
3. Maximum usable bhp is 1.8 Extensive motor and electrical test ing on these units ensures that the full horsepower range of
0.1 Bhp Rpm Bhp
Rpm
720 0.34 776 0.39 760 0.40
801 0.47 853 0.54 842 0.55 883 0.64 931 0 72
0 74 970 0.82
924 965
0.85
1007
0.97
1049 1.10 1090 1.19 1090 1 24 1131 1132 1.39
LEGEND
0.2
814
0.46
891 0.62
1010 0.93 1050 1 06 1128
1.34
1172
1.49
0.4
Rpm
886 0.53
915 950
985 1019 1054 1090 1.09
1166 1 36 1204 1.51 1243
EXTERNAL STATIC PRESSURE (in. wg)
0.6 0.8
Bhp
Rpm Bhp Rpm Bhp
0 59 0 68
0.77
0.87 0 97
1 22
1.68 the motor can be utilized with confidence. Using your fan motors
up to the horsepower ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. Values include losses for filters, unit casing, and wet coils. Use of a field-supplied motor may affect wire sizing. Contact Car rier representative to verify Motor drive range is 900 to 1300 rpm All other rpms require field­supplied drive.
1.0 1.2
Rpm
1142 1165 1 04 1240 1.22 1190 1.14
1221 1252 1283 1.51 1346
1315
Rpm Bhp
Bhp
0.96 1207 1.11 1266 1.33
1287 1.42
1.26
1.38 1315
1.65
1.55 1 69
1.4
Rpm Bhp
1245 1 20
1.37
1296
1331 1.50 1358 1.63 1388 , 1,74
1.6
Rpm Bhp

Table 15 — Fan Performance, 48LJD/LJE/LJF007 Horizontal Discharge Units; Standard Motor (Belt)

AIRFLOW
(Cfm)
1800 1900
2000
2100 2200
2300 2400 2500 2600 2700 2800 2900 3000
Bhp — Brake Horsepower
NOTES:
1. Bpldfacd indicates field-supplied drive required. (See Note 6.)
2. indicates field-supplied motor and drive required. 3 Maximum usable bhp is 2.4. Extensive motor and electrical test
ing on these units ensures that the full horsepower range of
Rpm
852 894 936 978
1021
1064
1107 1150 1193 1237 1280 1324 1368
LEGEND
0.1 Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
0.55
0.64
0.74
0.85
0.97
1.10
1 24
1.39
1.56 1 74
1.94
2 15
2.37
0.2
0.4
EXTERNAL STATIC PRESSURE (in. wg)
0.6 0.8
1.0 1.2
the motor can be utilized with confidence Using your fan motors
up to the horsepower ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
4. Values include losses for filters, unit casing, and wet coils
5. Use of a field-supplied motor may affect wire sizing. Contact Car rier representative to verify.
6 Motor drive range is 1070 to 1460 rpm All other rpms require
field-supplied drive.
19
1.4
Rpm Bhp 1371 1.69
1396 1 81 1422 1.94 1452
2.08
ZS4
1483
1.6
Rpm Bhp 1433 1 90
1450 2.03
1485 2.16 1510 2.31
Page 20

START-UP

IMPORTANT: Energize crankcase heater 24 hours prior
to base unit start-up to remove absorbed refrigerant from oil to prevent damage to compressor. Heater is energized as long as there is power to the unit.
Unit Preparation — Make sure that unit has been in
stalled in accordance with these installation instructions and applicable codes.
Return-Air Filters — Make sure correct filters are in
stalled in filter tracks. See Table 1. Do not operate unit without return-air filters.
Compressor Mounting — Compressors are inter
nally spring mounted. Do not loosen or remove compressor holddown bolts.
Internal Wiring — Check all electrical connections in
unit control boxes. Tighten as required.
Refrigerant Service Ports — Each unit system has
3 Schrader-type service gage ports: one on the suction line, one on the liquid line, and one on the compressor discharge line. Be sure that caps on the ports are tight. One Schrader­type valve is located under both the high-pressure switch and the low-pressure switch.
Cooling — Set space thermostat to OFF position. To start
unit, turn on main power supply. Set system selector switch at COOL position and fan switch at AUTO, position. Ad
just thermostat to a setting below room temperature. Com
pressor starts on closure of contactor.
Check unit charge. Refer to Service, Refrigerant Charge
section, page 22.
Reset thermostat at a position above room temperature. Compressor will shut off. Evaporator fan will shut off after 30 second delay.
TO SHUT OFF UNIT — Set system selector switch at OFF position. Resetting thermostat at a position above room tem perature shuts unit off temporarily until space temperature exceeds thermostat setting.
Main Burners — Main burners are factory set and should
require no adjustment. TO CHECK ignition of main burners and heating controls,
move thermostat set point above room temperature and ver ify that the burners light and evaporator fan is energized. After ensuring that the unit continues to heat the building, lower the thermostat setting below room temperature and verify that the burners and evaporator fan turn off. (Fan will turn off only if fan selector switch is in the AUTO, position.)
Refer to Table 16 for the correct orifice to use at high altitudes.

Heating

1. Purge gas supply line of air by opening union ahead of gas valve. If gas odor is detected, tighten union and wait 5 minutes before proceeding.
2. Turn on electrical supply and manual gas valve.
3. Set system switch selector at HEAT position and fan switch at AUTO, or ON position. Set heating tempera ture lever above room temperature.
4. The induced draft motor will start.
5. After a call for heating, the main burners should light within 5 seconds. If the burner does not light, then there is a 22 second delay before another 5-second try. If the
burner still does not light, the time delay is repeated. If the burner does not light within 15 minutes, there is a lockout. To reset the control, break the 24 v power to
Wl.
6. The evaporator-fan motor will turn on 45 seconds after the burners are ignited.
7. The evaporator-fan motor will turn off 45 seconds after thermostat temperature is satisfied.
8. Adjust airflow to obtain a temperature rise within the range specified on the unit nameplate.
NOTE: The default value for the evaporator-fan motor ON and OFF delay is 45 seconds. The Integrated Gas Unit Con troller (IGC) modifies this value when abnormal limit switch cycles occur. Based upon unit operating conditions, the ON delay can be reduced to 0 seconds and the OFF delay can be extended to 180 seconds.
Table 16 — Altitude Compensation*
74,000 AND 115,000
BTUH NOMINAL
ELEVATION
(ft)
0-2,000 33
2,000 3,000 35 4,000 5,000 36 6,000 7,000
8,000 38
9,000 10,000 11,000 12,000 13,000 14,000
*As the height above sea level increases, there is less oxygen per
cubic foot of air Therefore, heat input rate should be reduced at higher altitudes.
fOrifices available through your Carrier distributor
INPUT
Natural
Gas
Orifice
Sizet
34 43 30
36
37 45 34 43 37
39 41 48 38 45 43 48 39 44 49 44 49 45 50 42 47
Liquid
Propane
Orifice
Sizet
43 30 38
44 31 40 44 32 41 44
45
46 36
47 37 44
150,000 BTUH
NOMINAL INPUT
Natural
Gas
Orifice
Sizet
33
35
40
41 47
Liquid
Propane
Orifice
Sizet
39
42
43 44
45 46
TO SHUT OFF UNIT — Set system selector switch at OFF position. Resetting heating selector lever below room tem perature will temporarily shut unit off until space tempera ture falls below thermostat setting.
Safety Relief — A soft solder joint at the suction ser
vice Schrader port provides pressure relief under abnormal temperature and pressure conditions (i.e., fire in building).
Ventilation (Continuous Fan) — Set fan and sys
tem selector switches at ON and OFF positions, respec tively. Evaporator fan operates continuously to provide constant air circulation. When the evaporator-fan selector switch is turned to the OFF position, there is a 30 second delay be fore the fan turns off.

Operating Sequence

COOLING, UNITS WITHOUT ECONOMIZER - When thermostat calls for cooling, terminals G and Y1 are ener gized, and the indoor (evaporator) fan motor (IFM), com pressor, and outdoor (condenser) fan motor (OFM) start. The OFM runs continuously while the unit is in cooling. When the thermostat is satisfied, C is deenergized and the
compressor and OFM shut off. After a 30 second delay, the
IFM shuts off. If the thermostat fan selector switch is in the
ON position, the evaporator motor will run continuously.
20
Page 21
HEATING, UNITS WITHOUT ECONOMIZER - When the thermostat calls for heating, terminal W1 is energized. To prevent thermostat short-cycling, the unit is locked into the Heating mode for at least 1 minute when W1 is ener gized. The induced-draft motor is energized and the burner ignition sequence begins. The indoor (evaporator) fan mo tor (IFM) is energized 45 seconds after a flame is ignited. On units equipped for two stages of heat, when additional heat is needed, W2 is energized and the high-fire solenoid on the main gas valve (MGV) is energized. When the ther mostat is satisfied and W1 is deenergized, the IFM stops after a 45 second time-off delay.
COOLING, UNITS WITH ECONOMIZER - When the outdoor-air temperature is above the outdoor-air thermostat
(OAT) setting and the room thermostat calls for cooling, compressor contactor is energized to start compressor and the outdoor (condenser) fan motor (OFM). The indoor (evap orator) fan motor (IFM) is energized and the economizer damper moves to the minimum position. After the thermo stat is satisfied, there is a 30 second delay before the evap
orator fan turns off. The damper then moves to the fully
closed position. When using continuous fan, the damper
moves to the minimum position.
When the outdoor-air temperature is below the OAT set ting and the thermostat calls for cooling, the economizer damper moves to the minimum position. If the supply-air temperature is above 57 F, the damper continuous to open until it reaches the fully open position or until the supply­air temperature drops below 52 F.
When the supply-air temperature falls between 57 F and 52 F, the damper will remain at an intermediate open po sition. If the supply-air temperature falls below 52 F, the damper will modulate closed until it reaches the minimum position or until the supply-air temperature is above 52 F. When the thermostat is satisfied, the damper moves to the fully closed position when using AUTO, fan or to the min imum position when using continuous fan.
If the outdoor air alone cannot satisfy the cooling require ments of the conditioned space, economizer cooling is in tegrated with mechanical cooling, providing two stages of
cooling. Compressor and the condenser fan will be ener gized and the position of the economizer damper will be determined by the supply-air temperature. When the sec ond stage of cooling is satisfied, the compressor and OFM
will be deenergized. The damper position will be deter mined by the supply-air temperature. When the first stage of cooling is satisfied, there is a 30 second delay before the evaporator fan shuts off. The damper then moves to the fully closed position. When using a continuous fan, the damper moves to the minimum position.
HEATING, UNITS WITH ECONOMIZER - When the thermostat calls for heating, terminal W1 is energized. To prevent thermostat short-cycling, the unit is locked into the Heating mode for at least 1 minute when W1 is energized. The induced-draft motor is energized and the burner igni tion sequence begins. The indoor (evaporator) fan motor
(IFM) is energized 45 seconds after a flame is ignited and the damper moves to the minimum position. On units equipped for two stages of heat, when additional heat is needed, W2
energized and the high-fire solenoid on the main gas valve
(MGV) is energized. When the thermostat is satisfied and
W1 is deenergized, the IFM stops after a 45 second time-
off delay. The economizer damper then moves to the fully
closed position. When using continuous fan, the damper
will remain in the minimum position.

SERVICE

 CAUTION

When servicing unit, shut off all electrical power to unit to avoid shock hazard or injury from rotating parts.
Cleaning — Inspect unit interior at the beginning of heat
ing and cooling season and as operating conditions require.
EVAPORATOR COIL
1. Turn unit power off. Remove evaporator coil access panel.
2. If economizer is installed, remove economizer by dis connecting Molex plug and removing economizer mount ing screws. Refer to accessory economizer installation instructions or Optional Economizer section on page 11 for more details.
3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dish washer detergent in a pressurized spray canister. Wash both sides of coil and flush with clean water. For best results, backflush toward return-air section to remove foreign material. Flush condensate pan after
completion.
5. Reinstall economizer and filters.
6. Reconnect wiring.
7. Replace access panels.
CONDENSER COIL — Inspect coil monthly. Clean con denser coil annually, and as required by location and out door air conditions.
One-Row Coils — Wash coil with commercial coil cleaner. It is not necessary to remove top panel.
2-Row Coils Clean coil as follows:
1. Turn off unit power.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil comer post. See Fig. 28. To hold
top panel open, place coil comer post between top panel and center post. See Fig. 29.
4. Remove screws securing coil to center post.
5. Remove fastener holding coil sections together at return
end of condenser coil. Carefully separate the outer coil section 3 to 4 in. from the inner coil section. See Fig. 30.
6. Use a water hose or other suitable equipment to flush
down between the 2 coil sections to remove dirt and de bris. Clean the outer surfaces with a stiff brush in the normal manner.
7. Secure inner and outer coil rows together with a field­supplied fastener.
8. Reposition the outer coil section and remove the coil
comer post from between the top panel and center post. Reinstall the coil comer post and replace all screws.
CONDENSATE DRAIN — Check and clean each year at start of cooling season. In winter, keep drain dry or protect against freeze-up.
FILTERS — Clean or replace at start of each heating and cooling season, or more often if operating conditions re quire it. Replacement filters must be same dimensions as original filters.
OUTDOOR-AIR INLET SCREENS - Clean screens with
steam or hot water and a mild detergent. Do not use dis
posable filters in place of screens.
21
Page 22

Lubrication

COMPRESSORS — Each compressor is charged with the correct amount of oil at the factory.
FAN MOTOR BEARINGS — Fan motor bearings are of the permanently lubricated type. No further lubrication is required. No lubrication of condenser or evaporator fan mo tors is required.
Manual Outdoor-Air Damper — if outdoor-air damper
blade adjustment is required, see Manual Outdoor-Air Damper section on page 10.
COIL CORNER
CENTER BAFFLE
TOP PANEL

Two-Position Damper —

Refer to Two-Position
Damper section on page 11.
Economizer Adjustment — Refer to Optional Econ
omizer section on page 11.
Condenser-Fan Adjustment (Fig. 31) — Shut off
unit power supply. Remove condenser-fan assembly (grille,
motor, motor cover, and fan) and loosen fan hub setscrews. Adjust fan height as shown in Fig. 31. Tighten setscrews and replace condenser-fan assembly.
Refrigerant Charge — Amount of refrigerant charge
is listed on unit nameplate (also refer to Table 1). Refer to Carrier GTAC2-5 Charging, Recovery, Recycling, and Rec lamation training manual and the following procedures.
Unit panels must be in place when unit is operating dur
ing charging procedure. NO CHARGE — Use standard evacuating techniques. Af
ter evacuating system, weigh in the specified amount of re frigerant. (Refer to Table 1.)
TOP VIEW
TOP PANEL
Fig. 31 — Condenser-Fan Adjustment
22
Page 23
LOW CHARGE COOLING — Using Cooling Charging
Charts, Fig. 32-35, vary refrigerant until the conditions of
the appropriate chart are met. Note the charging charts are
different from type normally used. Charts are based on charg ing the units to the correct superheat for the various oper ating conditions. Accurate pressure gage and temperature sensing device are required. Connect the pressure gage to the service port on the suction line. Mount the temperature sensing device on the suction line and insulate it so that outdoor ambient temperature does not affect the reading. Indoor-air cfm must be within the normal operating range of the unit.
TO USE COOLING CHARGING CHART - Take the out door ambient temperature and read the suction pressure gage.
Refer to chart to determine what suction temperature should be. If suction temperature is high, add refrigerant. If suc tion temperature is low, carefully reclaim some of the charge. Recheck the suction pressure as charge is adjusted.
Example; (Fig. 33)
Outdoor Temperature........................................................85F
Suction Pressure
Suction Temperature should be
...........................................................
.......................................
70 psig
46 F
(Suction Temperature may vary 5 F.)
If Chargemaster® charging device is used, temperature and pressure readings must be accomplished using the charg ing chart.
6B9
1 111
M 1 M M
ourooofl TEM P
F C
621
115 46
105 41
J552
S
o
=¡483
«
^345
2
O
§276
n
207
<s>
ft
upO
s
pi
§50
<n
' -1 4 I'o ife 2'l 2'?
--
£
?
?
0 B
0
S
JCTiON L
0 ^ NE TEMPE
0 7 F)
RATURE (
SUCTION LINE TEMPERATURE CC)
95 35 85 29 75 24 65 18
55 13
45 7
0 £
Fig. 32 — Cooling Charging Chart, 48LJE/LJF004
0
Fig. 34 — Cooling Charging Chart, 48LJD/LJE/LJF006
SUCTION LINE TEMPERATURE CF)
SUCTION LINE TEMPERATURE CC)
30 40 SO BO
' -I ¡1 I'o I's
SO
73
h
2'l

Fig. 33 — Cooling Charging Chart, 48LJD/LJE/LJF005

Fig. 35 — Cooling Charging Chart, 48LJD/LJE/LJF007
23
Page 24
Flue Gas Passageways — To inspect the flue col
lector box and upper areas of the heat exchanger:
1. Remove the combustion blower wheel and motor assem bly according to directions in Combustion-Air Blower section below.
2. Remove the 3 screws holding the blower housing to the flue cover.
3. Remove the flue cover to inspect the heat exchanger.
4. Clean all surfaces as required using a wire brush.
Combustion-Air Blower — Clean periodically to as
sure proper airflow and heating efficiency. Inspect blower wheel eveiy fall and periodically during heating season. For the first heating season, inspect blower wheel bimonthly to determine proper cleaning frequency.
To inspect blower wheel, remove draft hood and screen. Shine a flashlight into opening to inspect wheel. If cleaning is required, remove motor and wheel as follows:
1. Slide burner access panel out.
2. Remove the 2 screws which hold the heat shield in place,
and remove heat shield.
3. Remove the 7 screws that attach induced-draft motor mount ing plate to blower housing (Fig. 36).
4. Slide the motor and blower wheel assembly out of the blower housing. The blower wheel can be cleaned at this point. If additional cleaning is required, continue
with Steps 5 and 6.
5. To remove blower from the motor shaft, remove 2 set screws.
6. To remove motor, remove the 4 screws that hold the
motor to mounting plate. Remove the motor cooling fan by removing one setscrew. Then remove nuts that hold
motor to mounting plate.
7. To reinstall, reverse the procedure outlined above.
error code can be observed through the viewport. During
servicing refer to the label on the control box cover or Ta ble 17 for an explanation of LED error code descriptions.
If lockout occurs, unit may be reset by interrupting power
supply to unit for at least 5 seconds.
Table 17 — LED Error Code Description*
LEO INDICATION
ON
OFF
1
Flasht 2 Flashes 3 Flashes 4 Flashes 5 Flashes 6 Flashes 7 Flashes 8 Flashes
LED — Light-Emitting Diode
*A 3 second pause exists between LED error code flashes, if more
than one error code exists, all applicable codes will be displayed in numerical sequence
flndicates a code that is not an error. The unit will continue to op
erate when this code is displayed. IMPORTANT: Refer to Troubleshooting Tables 19-22 for addi
tional information.
ERROR CODE DESCRIPTION
Normal Operation Hardware Failure Evaporator Fan On/Off Delay Modified Limit Switch Fault Flame Sense Fault 4 Consecutive Limit Switch Faults Ignition Lockout Fault
Induced-Draft Motor Fault Rollout Switch Fault
Internal Control Fault
Main Burners — At the beginning of each heating sea
son, inspect for deterioration or blockage due to corrosion or other causes. Observe the main burner flames and ad
just, if necessary.
ROLLOUT
SWITCH'
^ FLUE
EXHAUST
BLOWER HOUSING
GAS
VALVE
Fig. 36 — Burner Section Details
Limit Switch — Remove blower access panel (Fig. 6).
Limit switch is located on the fan deck.
Burner Ignition — Unit is equipped with a direct spark
ignition 100% lockout system. Integrated Gas Unit Control ler (IGC) is located in the control box (Fig. 11). IGC con tains a self-diagnostic LED (light-emitting diode). A single LED on the IGC provides a visual display of operational or sequential problems when the power supply is uninter rupted. When a break in power occurs, the IGC will be re set (resulting in a loss of fault history) and the indoor (evaporator) fan ON/OFF times will be reset. The LED

 CAUTION

When working on gas train, do not hit or plug orifice
spuds.
REMOVAL OF GAS TRAIN (Fig. 36 and 37)
Shut off manual gas valve.
1. Shut off power to unit.
2.
3.
Remove compressor access panel (not shown). Slide out burner section side panel (not shown).
4. Remove heat shield.
5. Disconnect gas piping at unit gas valve.
6.
Remove wires connected to gas valve. Mark each wire.
7. Remove induced-draft motor, ignitor, and sensor
8.
wires at the Integrated Gas Unit Controller (IGC) (see Fig. 11).
Remove the 2 screws that attach the burner rack to the vestibule plate.
10.
Remove the gas valve bracket.
Slide the burner tray out of the unit (Fig. 37).
11. To reinstall, reverse the procedure outlined above.
12.
CLEANING AND ADJUSTMENT
1. Remove burner rack from unit as described in Removal
of Gas Train section, above.
2. Inspect burners; if dirty, remove burners from rack.
3. Using a soft brush clean burners and cross-over port as
required.
4. Adjust spark gap. See Fig. 38.
5. Reinstall burners on rack.
6. Reinstall burner rack as described in Replacement of Gas
Train section, above.
Replacement Parts — A complete list of replace
ment parts may be obtained from any Carrier distributor upon request.
24
Page 25
OCtr r\CTAII «r'H
LOW HEAT
SPARK GAP .125" TO .140"
MEDIUM AND HIGH HEAT
DETAIL ”C”

Fig. 38 -Spark Adjustment

25
Page 26
TROUBLESHOOTING

Table 18 — LED Error Code Service Analysis

PROBLEM
Hardware failure. (LED OFF)
Limit switch fauit.
(LED 2 fiashes)
Fiame sense fauit.
(LED 3 fiashes) 4 consecutive iimit
switch trips. (LED 4 fiashes)
Ignition lockout. (LED 5 flashes)
Induced-draft motor
fault.
(LED 6 flashes) Rollout switch fault.
(LED 7 flashes)
Internal control fault. (LED 8 flashes)
IMPORTANT; Refer to Table 19 — Heating Service Analysis for
additional troubleshooting analysis.
LEGEND
IGC — Integrated Gas Unit Controller LED — Light-Emitting Diode
Loss of power to control module (IGC).
High temperature iimit switch is open. Check the operation of the indoor (evaporator) fan mo
The IGC sensed flame that should not be present Reset unit. If problem persists, repiace controi board Inadequate airflow to unit.
Unit unsuccessfully attempted ignition for 15 minutes. Check ignitor and flame sensor electrode spacing, gaps,
iGC does not sense that induced-draft motor is operating.
Rollout switch has opened.
Microprocessor has sensed an error in the software or hardware.
CAUSE
REMEDY
Check 5 amp fuse on IGC, power to unit, 24 v circuit breaker, and transformer. Units without a 24 v circuit breaker have an internai overload in the 24 v trans former if the overload trips, aliow 10 minutes for auto
matic reset.
tor. Ensure that the suppiy-air temperature rise is in ac cordance with the range on the unit namepiate.
Check operation of indoor (evaporator) fan motor and
that suppiy-air temperature rise agrees with range on
unit nameplate information.
etc. Ensure that flame sense and ignition wires are prop erly terminated. Verify that unit is obtaining proper
amount of gas. Check for proper voltage. If motor Is operating, check
the speed sensor plug/IGC Terminal J2 connection.
Proper connection: PIN 1 — White, PIN 2 — Red, PIN 3
— Black.
Rollout switch will automatically reset, but IGC will con
tinue to lockout unit. Check gas valve operation. Ensure
that induced-draft blower wheel is properly secured to motor shaft. Reset unit at unit disconnect.
If error code Is not cleared by resetting unit power, re place the IGC.
26
Page 27
Table 19 - Heating Service Analysis
PROBLEM
Burners will not ignite.
Inadequate heating.
Poor flame characteristics.
Burners will not turn
off.
CAUSE
Misaligned spark electrodes.
No gas at main burners.
Check flame ignition and sensor electrode positioning. Adjust as needed.
Check gas line for air, purge as necessary. After purging gas line of air, allow gas to dissipate for at least 5 min
REMEDY
utes before attempting to relight unit. Check gas valve.
Water in gas line. Drain water and install drip leg to trap water.
No power to furnace. Check power supply, fuses, wiring, and circuit breaker. No 24 V power supply to control circuit.
Check transformer. Transformers with internal overcur rent protection require a cool down period before
resetting. Miswired or loose connections. Burned-out heat anticipator in thermostat. Broken thermostat wires. Dirty air filter. Gas input to unit too low.
Unit undersized for application.
Check all wiring and wire nut connections.
Replace thermostat.
Run continuity check. Replace wires, if necessary.
Clean or replace filter as necessary.
Check gas pressure at manifold. Clock gas meter for
input, if too low, increase manifold pressure, or replace
with correct orifices.
Replace with proper unit or add additional unit.
Restricted airflow. Clean filter, replace filter, or remove any restrictions. Blower speed too low.
Limit switch cycles main burners.
Too much outdoor air.
Use high speed tap, increase fan speed, or install op
tional blower, as suitable tor individual units.
Check rotation of blower, thermostat heat anticipator set
tings, and temperature rise of unit. Adjust as needed.
Adjust minimum position.
Check economizer operation.
Incomplete combustion (lack of combustion air) results in:
Aldehyde odors, CO, sooting flame, or floating flame.
Check all screws around flue outlets and burner com
partment. Tighten as necessary. Cracked heat exchanger. Overfired unit — reduce input, change orifices, or adjust
gas line or manifold pressure. Check vent for restriction. Clean as necessary. Check orifice to burner alignment.
Unit is locked into Heating Mode for a one minute minimum.
Wait until mandatory one minute time period has
elapsed or reset power to unit.
27
Page 28
Table 20 — Cooling Service Analysis
PROBLEM
Compressor and con­denser fan will not start.
Compressor will not start but condenser fan runs.
Compressor cycles (other than normally satisfying thermostat).
Compressor operates continuously.
Excessive head pressure.
Head pressure too low.
Excessive suction pressure.
Suction pressure too low.
Evaporator fan will not shut off.
CAUSE
REMEDY
Power failure. Call power company. Fuse blown or circuit breaker tripped. Defective thermostat, contactor, transformer, or control
relay
Replace fuse or reset circuit breaker. Replace component.
Insufficient line voltage. Determine cause and correct. Incorrect or faulty wiring Thermostat setting too high Faulty wiring or loose connections in compressor circuit Compressor motor burned out, seized, or internal over
load open Defective run/start capacitor, overload, start relay. One leg of three-phase power dead. Refrigerant overcharge or undercharge.
Check wiring diagram and rewire correctly. Low thermostat setting below room temperature. Check wiring and repair or replace. Determine cause. Replace compressor
Determine cause and replace. Replace fuse or reset circuit breaker. Determine cause. Reclaim refrigerant, evacuate system, and recharge to
nameplate.
Defective compressor.
Replace and determine cause Insufficient line voltage Determine cause and correct. Blocked condenser.
Determine cause and correct. Defective run/start capacitor, overload, or start relay. Determine cause and replace. Defective thermostat. Replace thermostat. Faulty condenser-fan motor or capacitor. Restriction in refrigerant system
Replace.
Locate restriction and remove. Dirty air filter Replace filter. Unit undersized for load.
Decrease load or increase unit size. Thermostat set too low. Reset thermostat. Low refrigerant charge Locate leak; repair and recharge. Leaking valves in compressor Replace compressor. Air in system.
Reclaim refrigerant, evacuate system, and recharge. Condenser coil dirty or restricted Clean coil or remove restriction. Dirty air filter. Replace filter. Dirty condenser coil Clean coil Refrigerant overcharged. Air in system. Condenser air restricted or air short-cycling Low refrigerant charge
Reclaim excess refrigerant.
Reclaim refrigerant, evacuate system, and recharge.
Determine cause and correct.
Check for leaks; repair and recharge. Compressor valves leaking. Replace compressor. Restriction in liquid tube. Remove restriction High head load. Check for source and eliminate Compressor valves leaking Replace compressor. Refrigerant overcharged. Dirty air filter
Low refrigerant charge. Metering device or low side restricted. Insufficient evaporator airflow.
Temperature too low in conditioned area Outdoor ambient below 25 F. Time off delay not finished
Reclaim excess refrigerant.
Replace filter.
Check for leaks; repair and recharge
Remove source of restriction. Increase air quantity. Check filter and replace If
necessary.
Reset thermostat. Install low-ambient kit
Wait for 30-second off delay.
28
Page 29
Table 21 — Economizer Service Analysis
PROBLEM
Damper does not open.
Evaporator fan not on. No power to economizer motor.
Economizer motor failure If there is 24 vac power at the motor terminals, but motor is not oper
Economizer opera tion limited to mini mum position.
OAT or EC set too high.
Check wiring of economizer relay packs
Check SAT
Damper does not
Incorrect wiring or wiring defects.
close.
Check SAT Economizer motor failure. If there is 24 vac power at motor terminals, but motor is not operating,
LEGEND
EC — Enthalpy Control OAT — Outdoor-Air Thermostat SAT — Supply-Air Thermostat
CAUSE
REMEDY
Check wiring between G on connection board and indoor fan contactor
1. Check that SW3 is making proper contact with the damper blade,
2. Check continuity across R1 coil. If not connected, replace relay R1.
3. Check diode D1. If diode is not functioning properly, replace D1.
4 Check wiring in economizer relay pack (See unit label
diagram.)
ating, replace motor
1 Set at correct temperature (3 F below indoor space temperature).
2. Check OAT or EC by setting set point above outdoor temperature or humidity level. If switch does not close, replace OAT or EC.
1 Check continuity across relay R2 coil. If not connected, replace R2
relay.
2. Check continuity across relay R3 coil If not connected, replace R3 relay.
If supply-air temperature is over 57 F, switch T2 should be closed. If not, replace SAT.
1. Check switch 2 and 4. If non-operational, replace.
2. Check diode D2. If diode D2 is not functioning properly, replace.
3. Check wiring on economizer and on economizer relay pack (see unit label diagram).
If supply air thermostat is below 52 F, switch T1 should be closed If not, replace SAT.
replace motor.
Legend for Fig. 39 — Typical Component Arrangement
and Fig. 40 — Typical Wiring Schematic
IMPORTANT: Refer to unit wiring label for actual unit wiring.
AHA — Adjustable Heat Anticipator C — Contactor, Compressor CAP — Capacitor CC — Cooling Compensator CH Crankcase Heater COMP — Compressor Motor
D — Diode
EC — Enthalpy Control
ECON — Economizer
EPS — Emergency Power Supply EQUIP — Equipment ER — Economizer Relay FPT — Freeze-Up Protection Thermostat GND — Ground HPS — High-Pressure Switch HS — Hall Effect Sensor I — Ignitor IDM — Induced-Draft Motor IFC — Indoor-Fan Contactor IFM — Indoor-Fan Motor IGC — Integrated Gas Unit Controller LED — Light-Emitting Diode LPS — Low-Pressure Switch LS — Limit Switch MGV — Main Gas Valve MTR — Motor OAT — Outdoor-Air Thermostat OFM — Outdoor-Fan Motor
P — Plug PL — Plug Assembly
QT — Quadruple Terminal
R — Relay
NOTES
If any of the original wire furnished must be replaced, it must be re
1
placed with Type 90 C wire or its equivaient
Number(s) indicates the line location of contacts A bracket over 2 numbers signifies single-pole, double-throw contacts. An underlined number signifies a normally closed contact. Plain numbers (no lines) signifies a normally open contact
RS — Rollout Switch SAT — Supply-Air Thermostat SEN — Sensor SW1 — Switch Fully Open SW2 — Switch Fully Closed SW3 — Switch Min. Vent Position SW4 — Switch Max Vent Position TO — Thermostat-Cooling TH — Thermostat-Heating TRAN — Transformer
Field Splice
______
Marked Wire
Terminal (Marked)
O Terminal (Unmarked)
I X I Terminal Block
9 Splice
<( y* Splice (Marked)
----------
Factory Wiring
----------
Field Control Wiring
—— — — Field Power Wiring
---------
Accessory or Optional Wiring
To indicate common potential only; not to represent wiring
Three-phase motors are protected under primary single phasing con
ditions
Thermostat: HH07AT170, 172, 174 and P272-2783
Subbase: HH93AZ176, 178 and P272-1882, 1883 Set heat anticipator at 14 amp For units with 2 stages of heating, set stage 2 anticipator at 14 amp. Use copper conductors only.
29
Page 30
u>
o
COMPONENT ARRANGEMENT
Fig. 39 — Typical Component Arrangement
Page 31
ISÜii 1 ü a
ai ai
ai
J
ООН- Э o_j a 2S
Ш ui X ^ ri É .. ,
a oc Л S ^
^ l 0 e n ? B
ms
I . I
^ - ' Î9tΰ^
ini rf'
êipjlr
i
Il Ал
31
Page 32
V 0 PNIC VHT YEL BLU BLK RED GRA
------
-GRA- t-BLK-0^^b-BLK-*-BLK—O^^BLK—«-0tU-O^.C-j
• HPS FPT IPS .
OPTIONAL
---------------------------------
• GRA^^ I, D^' ■ OKN-
BLU-
N—y iru
BRN—TT^ TRAN
N—Tcl TRAN
pY6'Y^'Y<3^
s"'
<l>i^_sP1LnuhI
6-Y3'Y‘'Y'']
------------
BLU
------------
YEL
s"'
------------
-------------
p*Y"Y?]
PL6-R FOR STD UNIT
Page 33
c
Copyright 1993 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book|1 |4 PC 111 Catalog No 564-987 Printed in U S A Form 48U-7SI Pg 32 4-93 Replaces: 48LJ-5SI Tab la 6a
Loading...