Carrier 48HX030-060, 48HX036-080, 48HX030-040, 48HX048-080, 48HX036-060 Installation, Start-up And Service Instructions Manual

...
Page 1
Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ................ 1-6
General ................................... 1
RECEIVING AND INSTALLATION ........... 7-14
Step 1 — Check Equipment ................ 7
• IDENTIFY UNIT
Step 2 — Provide Unit Support .............. 7
• ROOF CURB
• SLAB MOUNT
• FLUSH MOUNT
Step 3 — Field Fabricate Ductwork .......... 7
Step 4 — Provide Clearances ............... 7
Step 5 — Rig and Place Unit ................ 7
• UNITS WITHOUT BASE RAIL
• UNITS WITH OPTIONAL BASE RAIL
Step 6 — Connect Condensate Drain ........ 8
Step 7 — Install Flue Hood ................. 8
Step 8 — Install Gas Piping ................. 8
Step 9 — Install Duct Connections .......... 10
• CONFIGURING UNITS FOR DOWNFLOW (Vertical) DISCHARGE
Step 10 — Install Electrical Connections ..... 12
• HIGH-VOLTAGE CONNECTIONS
• SPECIAL PROCEDURES FOR 208-V OPERATION
• CONTROL VOLTAGE CONNECTIONS
• HEAT ANTICIPATOR SETTING
• TRANSFORMER PROTECTION
PRE-START-UP ............................ 15
START-UP ................................15-25
MAINTENANCE ............................26-29
TROUBLESHOOTING ......................30-32
START-UP CHECKLIST .....................CL-1
NOTE TO INSTALLER — READ THESE INSTRUC­TIONS CAREFULLYAND COMPLETELY before install­ing this unit (Fig. 1). Also, make sure the User’s Manual and Replacement Guide are left with the unit after installation.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical com­ponents. Only trained and qualified personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes.Wearsafety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire ex­tinguisher available for all brazing operations.
Understand the signal words — DANGER, WARNING, and CAUTION. Danger identifies the most serious hazards which will result in severe personal injury or death. Warning indicates a condition that could result in personal injury. Cau­tion is used to identify unsafe practices which would result in minor personal injury or product property damage.
Improper installation, adjustment, alteration, service, main­tenance, or use can cause carbon monoxide poisoning, fire, or an explosion which can result in personal injury or unit damage. Consult a qualified installer, serviceagency, or gas supplier for information or assistance. The quali­fied installer or agency must use only factory-authorized kits or accessories when modifying this product.
Before performing service or maintenance operations on unit, turn off gas supply then unit main power switch. Electrical shock could cause personal injury.
General — The 48HX units (see Fig. 1) are fully self-
contained, combination electric heat pump units with gas-fired back-up heat. The units are designed for outdoor installation. See Fig. 2-5 for unit dimensions. All unit sizes have discharge openings for both horizontal and down­flow configurations, and are factory shipped with all 4 duct openings covered. Units may be installed either on a rooftop or a ground-level cement slab. See Fig. 6 for roof curb dimensions.
Fig.1—Typical 48HX Unit Shown with Optional
Base Rail
48HX030-060
Dual Fuel Heat Pump Units
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 5a 5a
PC 111 Catalog No. 534-722 Printed in U.S.A. Form 48HX-3SI Pg 1 9-98 Replaces: 48HX-2SI
Page 2
UNIT
48HX
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CORNER WEIGHT
(lb/kg)
lbkgABCD
030040 208/230-1-60, 208/230-3-60 346 157 99/45 69/31 120/55 58/26 030060 208/230-1-60, 208/230-3-60 358 163 102/46 72/33 123/56 61/28
UNIT
48HX
CENTER OF GRAVITY
(in./mm)
XYZ
030040 26.99/686 22.62/575 12.65/321 030060 26.90/684 22.62/575 12.65/321
NOTES:
1. Clearances must be maintained to prevent recircu­lation of air from outdoor-fan discharge.
2. indicates center of gravity.
REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct Panel .....................................0
Unit Top .................................36(914.4)
Side Opposite Ducts ........................36(914.4)
Compressor Access ........................36(914.4)
(Except for NEC requirements) REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Maximum Extension of Overhangs .............48(1219.2)
Unit Top .................................14(355.6)
Duct Side of Unit ............................2(50.8)
Side Opposite Ducts ........................14(355.6)
Bottom of Unit ...................................0
Flue Panel ...............................36(914.4)
NEC (National Electrical Code) REQ’D CLEARANCES. in. (mm)
Between Units, Control Box Side ..............42(1066.8)
Unit and Ungrounded Surfaces, Control Box Side . . . 36 (914.4) Unit and Block or Concrete Walls and Other Grounded
Surfaces, Control Box Side .................42(1066.8)
Fig. 2 — Unit Dimensions, 48HX030 and 036 Without Base Rail
2
Page 3
UNIT
48HX
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CORNER WEIGHT
(lb/kg)
lbkgABCD
030040 208/230-1-60, 208/230-3-60 370 169 105/48 75/34 126/57 64/29 030060 208/230-1-60, 208/230-3-60 382 174 108/49 78/35 129/59 67/30
UNIT
48HX
CENTER OF GRAVITY
(in./mm)
XYZ
030040 26.85/682 23.25/590 15.96/405 030060 26.75/680 23.25/590 15.96/405
NOTES:
1. Clearances must be maintained to prevent recir­culation of air from outdoor-fan discharge.
2. indicates center of gravity.
REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct Panel ...............................0
Unit Top ...........................36(914.4)
Side Opposite Ducts ..................36(914.4)
Compressor Access ..................36(914.4)
(Except for NEC requirements) REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Maximum Extension of Overhangs .......48(1219.2)
Unit Top ...........................14(355.6)
Duct Side of Unit ..................... 2(50.8)
Side Opposite Ducts ..................14(355.6)
Bottom of Unit .............................0
Flue Panel .........................36(914.4)
NEC (National Electrical Code) REQ’D CLEARANCES in. (mm)
Between Units, Control Box Side ........42(1066.8)
Unit and Ungrounded Surfaces, Control
Box Side .........................36(914.4)
Unit and Block or Concrete Walls and Other
Grounded Surfaces, Control Box Side ....42(1066.8)
Fig. 3 — Unit Dimensions, 48HX030 With Optional Base Rail
3
Page 4
UNIT 48HX
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CORNER WEIGHT
(lb/kg)
lb kg A B C D
036060/080 208/230-1-60, 208/230-3-60 460-3-60 432 196 111/50 88/40 160/73 73/33 048080/100 208/230-1-60, 208/230-3-60 432 196 111/50 88/40 160/73 73/33 060080/100 208/230-1-60, 208/230-3-60 463 210 119/54 96/44 167/76 81/37
UNIT
48HX
CENTER OF GRAVITY
(in./mm)
XYZ
036060/080 28.38/720 22.75/604 15.35/390 048080/100 28.38/720 23.75/604 15.35/390 060080/100 28.06/713 23.60/599 15.35/390
NOTES:
1. Clearances must be maintained to prevent recir­culation of air from outdoor-fan discharge.
2. indicates center of gravity.
REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct Panel ......................................0
Unit Top ..................................36(914.4)
Side Opposite Ducts .........................36(914.4)
Compressor Access .........................36(914.4)
(Except for NEC requirements) REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Maximum Extension of Overhangs ..............48(1219.2)
Unit Top ..................................14(355.6)
Duct Side of Unit .............................2(50,8)
Side Opposite Ducts .........................14(355.6)
Bottom of Unit ....................................0
Flue Panel ................................36(914.4)
NEC (National Electrical Code) REQ’D CLEARANCES. in. (mm)
Between Units, Control Box Side ...............42(1066.8)
Unit and Ungrounded Surfaces, Control Box Side ....36(914.4)
Unit and Block or Concrete Walls and Other Grounded
Surfaces, Control Box Side ...................42(1066.8)
Fig. 4 — Unit Dimensions, 48HX036-060 Without Base Rail
4
Page 5
UNIT
48HX
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CORNER WEIGHT
(lb/kg)
lb kg A B C D
036060/080 208/230-1-60, 208/230-3-60, 460-3-60 456 207 117/53 94/43 166/75 79/36 048080/100 208/230-1-60, 208/230-3-60 456 207 117/53 94/43 166/75 79/36 060080/100 208/230-1-60, 208/230-3-60 487 221 125/57 102/46 173/79 87/40
UNIT
48HX
CENTER OF GRAVITY
(in./mm)
XYZ
036060/080 28.16/716 24.50/622 18.66/474 048080/100 28.16/716 24.50/622 18.66/474 060080/100 27.90/709 24.30/618 18.66/474
NOTES:
1. Clearances must be maintained to prevent recir­culation of air from outdoor-fan discharge.
2. indicates center of gravity.
Fig. 5 — Unit Dimensions, 48HX036-060 With Optional Base Rail
REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct Panel ......................................0
Unit Top ..................................36(914.4)
Side Opposite Ducts .........................36(914.4)
Compressor Access .........................36(914.4)
(Except for NEC requirements) REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Maximum Extension of Overhangs ..............48(1219.2)
Unit Top ..................................14(355.6)
Duct Side of Unit .............................2(50.8)
Side Opposite Ducts .........................14(355.6)
Bottom of Unit ....................................0
Flue Panel ................................36(914.4)
NEC (National Electrical Code) REQ’D CLEARANCES. in. (mm)
Between Units, Control Box Side ...............42(1066.8)
Unit and Ungrounded Surfaces, Control Box Side ....36(914.4)
Unit and Block or Concrete Walls and Other Grounded
Surfaces, Control Box Side ...................42(1066.8)
5
Page 6
PART NUMBER ‘‘A’’
FLAT
CPRFCURB001A00 89 [203] CPRFCURB002A00 119 [279] CPRFCURB003A00 149 [356]
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied as required for unit being installed.
3. Dimensions in [ ] are in millimeters.
4. Roof curb is made of 16 gage steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance 4 ft on each side.
7. Direction of airflow.
8. Insulated panels: 1-in. thick fiberglass 1 lb density.
Fig. 6 — Roof Curb Dimensions
6
Page 7
RECEIVING AND INSTALLATION
Step 1 — Check Equipment
IDENTIFYUNIT — The unit model number and serial num­ber are stamped on unit identification plate. Check this information against shipping papers and job data.
INSPECT SHIPMENT — Inspect for shipping damage while unit is still on shipping pallet. If unit appears to be damaged or is torn loose from its anchorage, have it examined by trans­portation inspectors before removal. Forward claim papers directly to transportation company. Manufacturer is not re­sponsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify the nearest Carrier Air Conditioning office if any item is missing.
To prevent loss or damage, leave all parts in original pack­ages until installation.
Step 2 — Provide Unit Support
ROOF CURB — Install accessory roof curb in accordance with instructions shipped with curb. See Fig. 6 for roof curb dimensions. Install insulation, cant strips, roofing, and flash­ing. Ductwork must be attached to curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasketing material supplied with the roof curb. Improperly ap­plied gasketing can also result in air leaks and poor unit performance.
Curb should be level to within1⁄4inch. See Fig. 7. This is necessary for unit drain to function properly. Refer to accessory roof curb installation instructions for additional information as required.
To remove wood support under unit (with base rail only), loosen 4 screws above rigging holes and slide assembly out through rectangular hole.
SLAB MOUNT — Place the unit on a solid, level concrete pad that is a minimum of 4 in. thick with 2 in. above grade. The slab should be flush on the front of the unit (to allow condensate drain installation) and should extend 2 in. on the three remaining sides of the unit. See Fig. 8. Install a 6-in. gravel apron in front of outdoor-air inlets to prevent obstruc­tion of airflow by grass or shrubs. Do not secure the unit to the slab except when required by local codes.
To remove wood support under unit (with base rail only), loosen 4 screws above rigging holes and slide assembly out through rectangular hole.
FLUSH MOUNT — Place side of unit with duct panel flush against transition. On units with optional base rails, the skirt on duct-panel side of unit can be removed or relocated to allow unit to be mounted flush against transitions that ex­tend below basepan of unit. To move skirt, proceed as follows:
1. Remove 4 screws holding skirt to base rail. Retain screws.
2. Remove skirt or slide skirt inwards until alternate clear-
ance holes align with base rails.
3. Secure with screws removed in Step 1. Holes align with
base rails.
To remove wood support under unit (with base rail only), loosen 4 screws above rigging holes and slide assembly out through rectangular hole.
Step 3 — Field Fabricate Ductwork — Secure all
ducts to roof curb and building structure on vertical dis­charge units. Do not connect ductwork to unit. For horizon­tal applications, attach ductwork to flanges on horizontal
discharge openings. All ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in ac­cordance with applicable codes.
Ducts passing through an unconditioned space must be
insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with ap­plicable fire codes.
A minimum clearance is not required around ductwork. Cabinet return-air static shall not exceed −.25 in. wg.
Step 4 — Provide Clearances — The required mini-
mum operating and service clearances are shown in Fig. 2-5. Adequate combustion, ventilation, and outdoor air must be provided.
Do not restrict outdoor airflow. An air restriction at ei­ther the outdoor-air inlet or the fan discharge can be det­rimental to compressor life.
The outdoor fan pushes air through the outdoor coil and discharges it through the bank of louvers in the top cover, the decorative grille on the right side of the unit, and the compressor access panel. Be sure that the fan discharge does not recirculate to the outdoor coil. Do not locate the unit in either a corner or under an overhead obstruction. The mini­mum clearance of a partial overhang (such as a normal house overhang) is 48-inches. The maximum horizontal extension of a partial overhang must not exceed 48 inches.
Provide a minimum clearance of 42 in. for the control box side next to a block wall or any other grounded surface. Pro­vide a minimum clearance of 42 in. between the control box side of unit and any electrically powered device, for ex­ample, another unit.
Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. Do not in­stall the unit on carpeting, tile, or other combustible mate­rials. The unit may be installed on wood flooring or on Class A, B, or C roof covering materials.
Step 5 — Rig and Place Unit
When installing the unit on a rooftop, be sure the roof will support the additional weight. Refer to Fig. 2-5 for corner weight information.
Use spreader bars or crate top when rigging the unit. The units must be rigged for lifting as shown in Fig. 9. Refer to T able1 for operating weight and to Fig. 2-5 for corner weights.
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B B-C A-C
1
⁄
2
1
⁄
4
1
⁄
4
Fig. 7 — Unit Leveling Tolerances
7
Page 8
Use extreme caution to prevent damage when moving the unit. Unit must remain in an upright position during all rig­ging and moving operations. The unit must be level for proper
condensate drainage; therefore, the ground-level pad or accessory roof curb must be level before setting the unit in place. When a field-fabricated support is used, be sure that the support is level and properly supports the unit.
UNITS WITHOUT BASE RAIL — If accessory rigging brackets are to be used for rigging, install them as follows:
Secure screws and paint protectors solidly against unit basepan to hold lifting brackets in position.
Never use lifting brackets when the temperature is be­low −10 F.
Never exceed 200 lbs per bracket of lifting force. Never use lifting brackets for lifting other models of air-
conditioning units or heat pumps. Lifting point should be directly over the unit center of
gravity.
1. Position brackets as close to the corners of unit as pos­sible. Be sure brackets are well outside of center of grav­ity. (See Fig. 2, 4, and 9.)
2. Position paint protectors and foam strips between screws and painted surface of unit. Tighten screws until they make contact with the paint protectors.
3. Secure device or hook of sufficientstrength to hole in bracket as shown in detail ‘‘C’’ of Fig. 9.
4. If wood top is available, use it for a spreader bar to pre­vent straps from damaging unit. If wood top is not avail­able, use spreader bars of sufficient length.
UNITS WITH OPTIONAL BASE RAIL — Refer to Fig. 9, detail A and View B-B. Lifting holes are provided in optional base rail as shown in Fig. 9. Operating weights are shown in Table 1. Refer to rigging instructions on unit.
Protective wood support must be removed from unit be­fore unit is mounted to curb. Remove 4 screws that secure support above rigging holes in rails. Slide support out through rectangular hole in rail. See Fig. 9.
Step 6 — Connect Condensate Drain
NOTE: When installing condensate drain connection be sure to comply with local codes and restrictions.
Model 48HX disposes of condensate water through a
3
⁄4in. NPT fitting which exits through the compressor access
panel. See Fig. 2-5 for location.
Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground-level installations. Install a field-supplied conden­sate trap at end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. lower than the drain-pan condensate connection to pre­vent the pan from overflowing. See Fig. 10. Prime the trap with water. When using a gravel apron, make sure it slopes away from the unit.
If the installation requires draining the condensate water away from the unit, install a 2-in. trap at the condensate connection to ensure proper drainage. See Fig. 10. Make sure that the outlet of the trap is at least 1 in. lower than the drain­pan condensate connection to prevent the pan from over­flowing. Prime the trap with water. Connect a drain tube using a minimum of
3
⁄4-in. PVC or3⁄4-in. copper pipe (all field-supplied) at the outlet end of the 2-in. trap. Do not un­dersize the tube. Pitch the drain tube downward at a slope of at least one in. for every 10 ft of horizontal run. Be sure to check the drain tube for leaks.
Step 7 — Install Flue Hood — The flue hood as-
sembly is shipped screwed to the control box in the burner compartment. Remove the burner access panel to locate the assembly.
For units being installed in California Air Quality Man-
agement Districts which require NO
X
emissions of 40 nanograms/joule or less, kit CRLOWNOX001A00 must be installed.
The venting system is designed to ensure proper vent­ing. The flue hood assembly must be installed as indi­cated in this section of the unit installation instructions.
Install the flue hood as follows (refer to Fig. 2-5):
1. This installation must conform with local building codes
and with the National Fuel Gas Code (NFGC), American National Standards Institute (ANSI) Z223.1 latest revi­sion (in Canada, CAN/CGA [Canadian Gas Association] B149.1, [2]-M86) or NFPA (National Fire Protection Association) 54, latest revision TIA-54-84-1. Refer to Provincial and local plumbing or wastewater codes and other applicable local codes.
2. Remove from shipping location. Place vent cap assembly
over flue panel. Orient screw holes in vent cap with holes in the flue panel.
3. Secure flue hood to flue panel by inserting a single
screw on the right side, the left side, and the top of flue hood.
Step 8 — Install Gas Piping — The gas supply pipe
enters the unit through the access hole provided. The gas connection to the unit is made to the1⁄2-in. FPT gas inlet on the manual shutoff or gas valve.
Install a gas supply line that runs to the heating section. Refer to Table 2 and the NFGC for gas pipe sizing. Black iron pipe must be used for connections inside the unit. Check the local utility for recommendations concerning existing lines. Size gas supply piping for 0.5 in. wg maximum pressure drop.
Never use pipe smaller than the
1
⁄2-in. FPT gas inlet on the
unit gas valve.
Fig. 8 — Slab Mounting Details
8
Page 9
Table 1 — Physical Data
UNIT SIZE 48HX 030040 030060 036060 036080 048080 048100 060080 060100 NOMINAL CAPACITY (tons) 2
1
⁄
2
21⁄
2
334455
OPERATING WEIGHT (lb)
Without Base Rail 346 358 432 432 432 432 463 463 With Optional Base Rail 370 382 456 456 456 456 487 487
COMPRESSOR Scroll
Quantity 1
REFRIGERANT R-22
Charge (lb) 5.6 5.6 8.6 8.6 7.8 7.8 8.1 8.1
OUTDOOR COIL
Rows...Fins/in. 2...17 2...17 2...17 2...17 2...17 2...17 2...17 2...17 Face Area (sq ft) 7.00 7.00 8.66 8.66 8.66 8.66 8.66 8.66
OUTDOOR FAN (Propeller)
Nominal Cfm 2200 2200 2200 2200 2400 2400 2400 2400 Diameter (in.) 20 20 20 20 20 20 20 20 Motor Hp
1
⁄
4
1
⁄
4
1
⁄
4
1
⁄
4
1
⁄
3
1
⁄
3
1
⁄
3
1
⁄
3
Motor Rpm 1100 1100 1100 1100 1100 1100 1100 1100
INDOOR COIL
Rows...Fins/in. 3...15 3...15 4...15 4...15 4...15 4...15 4...15 4...15 Face Area (sq ft) 3.6 3.6 4.5 4.5 4.5 4.5 4.5 4.5
INDOOR FAN (Centrifugal)*
Nominal Airflow (Cfm) 1000 1000 1150 1150 1600 1600 1800 1800 Size (in.) 10x10 10x10 10x10 10x10 10x10 10x10 10x10 10x10 Motor Hp
1
⁄
4
1
⁄
4
1
⁄
4
1
⁄
2
1111
Motor Rpm 1075 1075 1100 1100 Variable Variable Variable Variable
FURNACE SECTION
Heating Input†
(Btuh) 40,000 56,000 56,000 80,000 80,000 95,000 80,000 95,000
Burner Orifice (Qty...drill size)
Natural Gas 1...32 2...41 2...41 2...32 2...32 2...30 2...32 2...30 Propane Gas 1...41 2...46 2...46 2...42 2...42 2...41 2...42 2...41
RETURN-AIR FILTERS**
Throwaway (in.) 24x24 24x24 24x30 24x30 24x30 24x30 24x30 24x30
*Sizes 048 and 060 indoor fans are equipped with an integrated con-
trol motor (ICM). The ICM provides variable speed.
†Based on an altitude of 0 to 2000 feet.
**Required filter sizes shown are based on the ARI (Air Conditioning
& Refrigeration Institute) rated heating airflow at a velocity of 300 ft/min for throwaway type or 450 ft/min for high capacity type. Recommended filters are 1-in. thick.
All panels must be in place when rigging.
NOTICE TO RIGGERS
Hook rigging shackles through holes in lifting brackets, as shown in Details ‘‘A’’ and ‘‘C.’’ Lifting brackets to be centered around the unit center of gravity. Use wooden top skid when rigging, to prevent rig­ging straps from damaging unit. On units with rails, remove 4 screws to slide wood support through rectangular hole in rail.
CHART ‘‘A’’ — UNITS WITH OPTIONAL BASE RAIL
UNIT SIZE
48HX
SHIPPING
WEIGHT
AB
Lb Kg in. mm in. mm
030 401 182 22.6 575 32.2 817 036 477 217 21.2 537 38.2 969 048 477 217 21.2 537 38.2 969 060 506 230 21.5 546 38.2 969
CHART ‘‘B’’ — UNITS WITHOUT BASE RAIL
UNIT SIZE
48HX
SHIPPING
WEIGHT
CD
Lb Kg in. mm in. mm
030 377 171 22.4 568 28.2 715 036 453 206 21.0 532 34.2 867 048 453 206 21.0 532 34.2 867 060 482 219 21.3 542 34.2 867
Fig. 9 — Suggested Rigging
9
Page 10
For natural gas applications, the gas pressure at unit gas connection must not be less than 4.0 in. wg or greater than 13 in. wg while the unit is operating. For propane applica­tions, the gas pressure must not be less than 4.0 in. wg or greater than 13 in. wg at the unit connection.
When installing the gas supply line, observe local codes pertaining to gas pipe installations. Refer to the NFGC ANSI Z223.1 latest revision NFPA latest edition (in Canada, CAN/CGA B149.1, (2)-M86). In the absence of local building codes, adhere to the following pertinent recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe
1
⁄4inch in every 15 ft to prevent traps. Grade all hori­zontal runs downward to risers. Use risers to connect to heating section and to meter.
2. Protect all segments of piping system against physical and thermal damage. Support all piping with appropriate straps, hangers, etc. Use a minimum of one hanger every 6 ft. For pipe sizes larger than
1
⁄2in., follow recommendations
of national codes.
3. Apply joint compound (pipe dope) sparingly and only to male threads of joint when making pipe connections. Use only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and/or national codes.
Never use Teflon tape.
4. Install sediment trap in riser leading to heating section per Fig. 11. This drip leg functions as a trap for dirt and condensate.
5. Install an accessible, external, manual main shutoff valve in gas supply pipe within 6 ft of heating section.
6. Install ground-joint union close to heating section be­tween unit gas valve and external manual gas shutoff valve.
7. Pressure-test all gas piping in accordance with local and national plumbing and gas codes.
NOTE: The gas valve in the unit is subject to failure if exposed to pressures exceeding 0.5 psig. When pressur­izing the gas line above 0.5 psig, disconnect the union located between the manual shutoff and the gas valve in the unit; this will avoid unit gas valve failure.
Never use a match or other open flame when check­ing for gas leaks. Never purge gas line into com­bustion chamber. Failure to follow this warning could result in an explosion causing personal injury or death.
8. Using a soap and water solution, check for gas leaks at all piping connections inside and outside the unit.
Step 9 — Install Duct Connections — The unit
has duct flanges on the supply- and return-air openings on the side and bottom of the unit. See Fig. 2-5 for connection sizes and locations.
CONFIGURING UNITS FOR DOWNFLOW (Vertical) DISCHARGE
For vertical supply and return units, tools or parts could drop into ductwork and cause an injury. Install 90-degree turns in the supply and return ductwork be­tween the unit and the conditioned space. If a 90-degree elbow cannot be installed, then grilles of sufficientstrength and density should be installed to prevent objects from falling into the conditioned space.
Before performing service or maintenance operations on the system, turn off gas supply, then main power to unit. Failure to follow this warning could result in electrical shock and personal injury.
1. Open all electrical disconnects before starting any serv­ice work.
2. Remove return duct cover located on duct panel. Figure 12 shows duct cover removed. Save duct cover and screws.
3. Locate lances in basepan insulation that are placed over the perimeter of the vertical duct opening cover (Fig. 13).
4. Using a straight edge and sharp knife, cut and remove the insulation around the perimeter of the cover. Re­move and save 5 screws securing the cover to the base­pan and slide out the cover. Discard the cover (Fig. 14).
5. Remove supply duct cover located on duct panel. Figure 12 shows duct cover removed. Save duct cover and screws.
6. Remove and discard 2 screws which secure vertical dis­charge opening cover to basepan (Fig. 15). Slide cover forward to disengage, then tilt and remove cover through vertical discharge opening in bottom of unit. Discard duct cover (Fig. 16).
Collect ALL screws that were removed. Do not leave screws on rooftop as permanent damage to the roof may occur.
Fig. 10 — Condensate Trap
Fig. 11 — Sediment Trap
10
Page 11
7. If unit ductwork is to be attached to vertical opening flanges on the unit basepan (jackstand applications only), do so at this time.
8. It is recommended that the basepan insulation around the perimeter of the vertical return-air opening be se­cured to the basepan with aluminum tape. Applicable local codes may require aluminum tape to prevent ex­posed fiberglass.
9. Cover both horizontal duct openings with the duct cov­ers from Steps 2 and 5. Make sure opening is air- and watertight.
10. After completing unit conversion, perform all safety checks and power up unit.
NOTE: The design and installation of the duct system must be in accordance with the standards of the NFPA for instal­lation of nonresidence-type air conditioning and ventilating systems, NFPA 90A or residence-type, NFPA 90B; and/or local codes and residence-type, NFPA90B; and/or local codes and ordinances.
SUPPLY DUCT OPENING RETURN DUCT OPENING
Fig. 12 — Supply and Return Duct Openings
Fig. 13 — Lance Location for Vertical Duct
Opening Cover
Fig. 14 — Vertical Duct Cover Removed
Fig. 15 — Removal of Vertical Discharge
Opening Cover
11
Page 12
Table 2 — Maximum Gas Flow Capacity*
NOMINAL
IRON PIPE,
SIZE
(in.)
INTERNAL
DIAMETER
(in.)
LENGTH OF PIPE, FT†
10 20 30 40 50 60 70 80 90 100 125 150 175 200
1
⁄
2
.622 175 120 97 82 73 66 61 57 53 50 44 40 — —
3
⁄
4
.824 360 250 200 170 151 138 125 118 110 103 93 84 77 72
1 1.049 680 465 375 320 285 260 240 220 205 195 175 160 145 135
1
1
⁄
4
1.380 1400 950 770 600 580 530 490 460 430 400 360 325 300 280
1
1
⁄
2
1.610 2100 1460 1180 990 900 810 750 690 650 620 550 500 460 430
*Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5-in. wg
(based on a 0.60 specific gravity gas). Refer toTableC-4, National FireProtectionAssociation NFPA54.
†This length includes an ordinary number of fittings.
Adhere to the following criteria when selecting, sizing,
and installing the duct system:
1. Units are shipped with all 4 duct openings covered. Re­move appropriate panels for intended installation.
2. Select and size ductwork, supply-air registers, and return­air grilles according to American Society of Heating, Re­frigeration and Air Conditioning Engineers (ASHRAE) recommendations.
3. Use flexible transition between rigid ductwork and unit to prevent transmission of vibration. The transition may be screwed or bolted to duct flanges. Use suitable gaskets to ensure weathertight and airtight seal.
4. All units must have field-supplied filters or accessory fil­ter rack installed in the return-air side of the unit. Rec­ommended sizes for filters are shown in Table 1.
5. Size all ductwork for maximum required airflow (either heating or cooling) for unit being installed. Avoid abrupt duct size increases or decreases or performance may be affected.
6. Adequately insulate and weatherproof all ductwork lo­cated outdoors. Insulate ducts passing through uncon­ditioned space, and use vapor barrier in accordance with latest issue of Sheet Metal and Air Conditioning Contrac­tors National Association (SMACNA) and Air Condi­tioning Contractors of America (ACCA) minimum installation standards for heating and air conditioning sys­tems. Secure all ducts to building structure.
7. Flash, weatherproof, and vibration-isolate all openings in building structure in accordance with local codes and good building practices.
Step 10 — Install Electrical Connections
The unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground lug in the control compartment, or conduit ap­proved for electrical ground when installed in accor­dance with NEC (National Electrical Code) ANSI/ NFPA (latest edition) (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1) and local electrical codes. Do not use gas piping as an elec- trical ground. Failure to adhere to this warning could result in personal injury or death.
Failure to follow these precautions could result in dam­age to the unit being installed:
1. Make all electrical connections in accordance with NECANSI/NFPA(latest edition) and local electrical codes governing such wiring. In Canada, all electrical connec­tions must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between field­supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE.
3. Be sure that high-voltage power to unit is within oper­ating voltage range indicated on unit rating plate.
4. Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc. On 3-phase units, ensure phases are balanced within 2 per­cent. Consult local power company for correction of improper voltage and/or phase imbalance.
HIGH-VOLTAGE CONNECTIONS (Fig. 17) — The unit must have a separate electrical service with a field-supplied, waterproof, disconnect switch mounted at, or within sight from, the unit. Refer to the unit rating plate for maximum fuse/circuit breaker size and minimum circuit amps (ampac­ity) for wire sizing. See Table 3 for electrical data.
The field-supplied disconnect switch box may be mounted on the unit over the high-voltage inlet hole when the standard power and low-voltage entry points are used. See Fig. 2-5 for acceptable location.
Fig. 16 — Vertical Discharge Cover
Removed
12
Page 13
Power Entry
1. Remove knockouts in fixed compressor panel located on duct panel side of unit.
2. Route high-voltage leads into high-voltage terminal box.
3. Connect ground wire to green-yellow wire using field­supplied splice.
4. Connect power wires to unit high-voltage leads.
5. On 3-phase units, locate blue wire projecting from com­pressor junction box. Cut wire at partition and route into high-voltage junction box through grommet in back of junction box.
6. On 3-phase units, strip back blue lead and connect to third leg of the power wires. See Fig. 17.
Table 3 — Electrical Data
UNIT SIZE
V-PH-Hz
VOLTAGE
RANGE
COMPRESSOR
OUTDOOR-FAN
MOTOR
INDOOR-FAN
MOTOR
POWER SUPPLY
AWG 60C
MIN WIRE
SIZE
MAX WIRE
LENGTH (ft)
Min Max RLA LRA FLA FLA MCA MOCP*
030
208/230-1-60 187 253 15.0 73 1.4 2.6 22.8 30 10 100 208/230-3-60 187 253 10.1 71 1.4 2.8 16.6 25 12 75
036
208/230-1-60 187 253 16.0 88 1.2 2.6 24.4 40 10 90 208/230-3-60 187 253 10.3 77 1.2 2.6 17.3 25 12 65
460-3-60 414 506 5.1 39 0.7 1.3 8.7 10 14 100
048
208/230-1-60 187 253 26.4 129 1.4 7.2 41.6 60 6 100 208/230-3-60 187 253 15.0 99 1.4 7.2 27.4 40 10 70
060
208/230-1-60 187 253 32.1 169 2.1 7.2 49.4 60 6 100 208/230-3-60 187 253 19.3 123 2.1 7.2 33.4 50 8 100
LEGEND
AWG — American Wire Gage FLA — Full Load Amps HACR — Heating, Air Conditioning and
Refrigeration
LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection RLA — Rated Load Amps UL — Underwriters’ Laboratories
*Fuse or HACR breaker. NOTES:
1. In compliance with NEC (National Electrical Code) requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The UL, Canada, units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than 60 C wire is used, or if length exceeds wire length in table, de­termine size from NEC.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt­age is greater than 2%.
Use the following formula to determine
the percent of voltage imbalance. % Voltage imbalance
max voltage deviation from average voltage
= 100 x
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 − 452=5v (BC) 464 − 457=7v (AC) 457 − 455=2v
Maximum deviation is 7 v. Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
LEGEND
Field Control-Voltage Wiring Field High-Voltage Wiring
NOTE: Use blue wire for 3-phase units only.
Fig. 17 — High- and Control-Voltage
Connections
13
Page 14
SPECIAL PROCEDURES FOR 208-V OPERATION
Make sure that the gas supply then the power supply to the unit is switched OFF before making any wiring changes. Electrical shock can cause personal injury or death.
1. Disconnect the red transformer-primary lead from the con­tactor. See unit wiring label.
2. Remove the wirenut from the terminal on the end of the blue transformer-primary lead.
3. Save the wirenut.
4. Connect the blue lead to the contactor terminal from which the red lead was disconnected.
5. Using the wirenut removed from the blue lead, insulate the loose terminal on the red lead.
6. Wrap the cover with electrical tape so that the metal ter­minal cannot be seen.
CONTROLVOLTAGE CONNECTIONS — Locate the room thermostat on an inside wall in the space to be conditioned, where it will not be subjected to either a cooling or heating source or direct exposure to sunlight. Mount the thermostat 4 to 5 ft above the floor.
NOTE: Do not use any type of power-stealing thermostat. Unit control problems may result.
Use no. 18 American Wire Gage (AWG) color-coded, insulated (35 C minimum) wires to make the control volt­age connections between the thermostat and the unit. If the thermostat is located more than 100 ft from the unit (as measured along the control voltage wires), use no.16 AWG color-coded insulated (35 C minimum) wires.
Standard Connection (24 v) — Units Without Integrated Control Motor (Size 030,036) — Remove knockout in com­pressor fixed panel located below high-voltage knockout. Re­move the rubber grommet from the installer’s packet (included with unit) and install grommet in the knockout opening. Route thermostat wires through grommet providing drip loop at panel. Connect low-voltage leads as shown in Fig. 17.
Routing Control Power Wires (24 v) — Integrated Control Motor (ICM) Units (Size 048,060) — Remove knockout in compressor fixed access panel located below high-voltage knockout. Remove the rubber grommet from the installer’s packet (included with unit) and install grommet in the knock­out opening. Route thermostat wires through grommet pro­viding drip loop at panel. Connect low-voltage leads to the thermostat.
The Easy Select interface board is located in the burner section. The Easy Select interface board is factory wired to the motor, and factory default selections are preset. See Fig. 18.
HEAT ANTICIPATOR SETTING — The room thermostat heat anticipator must be properly adjusted to ensure proper heating performance. Set the heat anticipator, using an am­meter between the W and R terminals, to determine the exact required setting.
NOTE: For thermostat selection purposes, use 0.6 amp for the approximate required setting.
Failure to make a proper heat anticipator adjustment will result in improper operation, discomfort to the occupants of the conditioned space, and inefficient energy utilization; however, the required setting may be changed slightly to provide a greater degree of comfort for a particular installation.
Recommended thermostat and subbase is as follows:
TYPE
THERMOSTAT
PART NO.
SUBBASE
PART NO.
2-Stage Heat and 1-Stage
Cool, Auto, Changeover
HH07AT171 HH93AZ188
TRANSFORMER PROTECTION — The unit transformer protection may be one of 2 types.
The first transformer type may contain an auto. reset over­current protector for control circuit protection. If this device trips, it may reset without warning, starting the heating or cooling section of this product. Use caution when servicing; if overcurrent protector continues to trip, there is a problem in the low-voltage electrical circuit, such as an electrical short, ground, or transformer overload. Disconnect power, correct the condition, and check for normal unit operation.
The second transformer type is of the energy-limiting type. It is set to withstand a 30-second overload or shorted secondary condition.
There is also a 5-amp fuse on integrated gas control (IGC) board and Easy Select Interface Board to provide additional overcurrent protection.
LEGEND
IFO — Indoor Fan On JW — Jumper Wire
Fig. 18 — Easy Select Interface Board
14
Page 15
PRE-START-UP
Failure to observe the following warnings could result in serious personal injury:
1. Follow recognized safety practices and wear protec­tive goggles when checking or servicing refrigerant system.
2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured.
3. Do not remove compressor terminal cover until all electrical sources are disconnected.
4. Relieve and recover all refrigerant from system be­fore touching or disturbing anything inside terminal box if refrigerant leak is suspected around compres­sor terminals.
5. Never attempt to repair soldered connection while re­frigerant system is under pressure.
6. Do not use torch to remove any component. System contains oil and refrigerant under pressure. To re­move a component, wear protective goggles and pro­ceed as follows:
a. Shut off gas supply and then electrical power to
unit.
b. Relieve and recover all refrigerant from system
using both high- and low-pressure ports.
c. Cut component connecting tubing with tubing cut-
ter and remove component from unit.
d. Carefully unsweat remaining tubing stubs when
necessary. Oil can ignite when exposed to torch flame.
Proceed as follows to inspect and prepare the unit for ini-
tial start-up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING, CAU­TION, and INFORMATIONlabels attached to, or shipped with, unit.
3. Make the following inspections: a. Inspect for shipping and handling damages such as bro-
ken lines, loose parts, disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections and
on unit base. Detecting oil generally indicates a re­frigerant leak. Leak-test all refrigerant tubing connec­tions using electronic leak detector, halide torch, or liquid-soap solution. If a refrigerant leak is detected, see Check for Refrigerant Leaks section below.
c. Inspect all field- and factory-wiring connections. Be
sure that connections are completed and tight.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin comb.
4. Verify the following conditions:
Do not purge gas supply into the combustion cham­ber. Do not use a match or other open flame to check for gas leaks. Failure to follow this warning could result in an explosion causing personal injury or death.
a. Before lighting the unit for the first time, perform the
following: If the gas supply pipe was not purged be­fore connecting the unit, it will be full of air. It is rec­ommended that the ground joint union be loosened, and the supply line be allowed to purge until the odor of gas is detected. Never purge gas lines into a com­bustion chamber. Immediately upon detection of gas odor, retighten the union. Allow 5 minutes to elapse, then light unit.
b. Make sure that outdoor-fan blade is correctly posi-
tioned in fan orifice. Leading edge of outdoor-fan blade should be
1
⁄2in. maximum from plastic fan orifice (see
Fig. 19). c. Make sure that air filter(s) is in place. d. Make sure that condensate drain trap is filled with wa-
ter to ensure proper drainage. e. Make sure that all tools and miscellaneous loose parts
have been removed.
START-UP
Check for Refrigerant Leaks —
Proceed as follows
to locate and repair a refrigerant leak and to charge the unit:
1. Locate leak and make sure that refrigerant system pres­sure has been relieved and reclaimed from both high- and low-pressure ports.
2. Repair leak following accepted practices. NOTE: Install a filter drier whenever the system has been
opened for repair.
3. Add a small charge of R-22 refrigerant vapor to system and leak-test unit.
4. Evacuate and recover refrigerant from refrigerant system if additional leaks are not found.
5. Charge unit with R-22 refrigerant, using a volumetric­charging cylinder or accurate scale. Refer to unit rating plate for required charge. Be sure to add extra refrigerant to compensate for internal volume of filter drier.
Fig. 19 — Fan Blade Clearance
15
Page 16
Start Up Heating Section and Make Adjustments
Complete the required procedures given in Pre-Start-Up section on page 15 before starting the unit.
Do not jumper any safety devices when operating the unit.
Make sure that burner orifices are properly aligned. Un­stable operation may occur when the burner orifices in the manifold are misaligned.
Follow the lighting instructions on the heating section operation label (located inside the burner or blower access door) to start the heating section.
NOTE: Make sure that gas supply has been purged, and that all gas piping has been checked for leaks.
CHECK HEATING CONTROL — Start and check the unit for proper heating control operation as follows: (See furnace lighting instructions located inside burner or blower access panel.)
1. Place the room thermostat SYSTEM switch in the HEAT
position and the fan switch in the AUTO. position.
2. Ensure that OAT (Outdoor-Air Thermostat) capillary is
above 55 F. Set the heating temperature control of the thermostat above room temperature only enough to call first-stage heat.
3. Observe compressor, outdoor fan, and indoor fan operate
in heat pump mode.
4. Set the heating temperature control of the thermostat enough
above room temperature to call second-stage heat.
5. Observe the induced-draft motor start.
6. After a call for second-stage heat, the main burner should
light within 5 seconds. If the burners do not light, there is 22-second delay before another 5-second try. If the burn­ers still do not light, this sequence is repeated. If the burn­ers do not light within 15 minutes from the initial call for heat, there is a lockout. To reset the control, break the 24-v power to W.
7. The indoor fan will turn on 45 seconds after the flame
has been established. The indoor fan will turn off 45 seconds after the thermostat has been satisfied.
CHECK GAS INPUT — Check gas input and manifold pres­sure after unit start-up. (See Table 4.) If adjustment is required proceed as follows.
The rated gas inputs shown in Table 4 are for altitudes from sea level to 2000 ft above sea level. These inputs are based on natural gas with a heating value of 1050 Btu/ft
3
at
0.65 specific gravity, or propane gas with a heating value
of 2500 Btu/ft
3
at 1.5 specific gravity. For elevations above 2000 ft, reduce input 4% for each 1000 ft above sea level. When the gas supply being used has a differentheating value or specific gravity, refer to national and local codes, or con­tact your distributor to determine the required orifice size.
These units are designed to consume the rated gas in­puts using the fixed orifices at specified manifold pres­sures as shown in Table 4. DO NOT REDRILL THE ORIFICES UNDER ANY CIRCUMSTANCES.
ADJUST GAS INPUT — The gas input to the unit is determined by measuring the gas flow at the meter or by measuring the manifold pressure. Measuring the gas flow at the meter is recommended for natural gas units. The mani­fold pressure must be measured to determine the input of propane gas units.
Measure Gas Flow (Natural Gas Units) — Minor adjust­ment to the gas flow can be made by changing the man­ifold pressure. The manifold pressure must be maintained between 3.4 and 3.6 in. wg. If larger adjustments are required, change main burner orifices following the rec­ommendations of national and local codes.
NOTE:All other appliances that use the same meter must be turned off when gas flow is measured at the meter.
Proceed as follows:
1. Turn off gas supply to unit.
2. Remove pipe plug on manifold (see Fig. 20), then con-
nect manometer at this point. Turn on gas to unit.
3. Record number of seconds for gas meter test dial to make
one revolution.
4. Divide number of seconds in Step 3 into 3600 (number
of seconds in one hour).
5. Multiply result of Step 4 by the number of cu ft shown
for one revolution of test dial to obtain cu ft of gas flow per hour.
6. Multiply result of Step 5 by Btu heating value of gas to
obtain total measured input in Btuh. Compare this value with heating input shown in Table 4. (Consult the local gas supplier if the heating value of gas is not known.)
EXAMPLE: Assume that the size of test dial is 1 cu ft, one revolution takes 50 seconds, and the heating value of the gas is 1050 Btu/ft
3
. Proceed as follows:
1. 50 seconds to complete one revolution.
2. 3600 ÷ 50 = 72.
3.72x1=72ft
3
of gas flow/hr.
4. 72 x 1050 = 75,600 Btuh input.
Table 4 — Rated Gas Inputs at Indicated Manifold Pressures
UNIT 48HX
NUMBER
OF
ORIFICES
GAS SUPPLY PRESSURE
(in. wg)
MANIFOLD
PRESSURE
(in. wg)
NATURAL GAS PROPANE*
Natural Propane
Orifice
Drill
Size
Heating
Input
(Btuh)†
Orifice
Drill Size
Heating
Input
(Btuh)†
Min Max Min Max Natural Propane
030040 1 4.0 13.0 4.0 13.0 3.5 3.5 32 40,000 41 40,000 030060, 036060 2 4.0 13.0 4.0 13.0 3.5 3.5 41 56,000 46 54,000 036080, 048080,
060080
2 4.0 13.0 4.0 13.0 3.5 3.5 32 80,000 42 80,000
048100, 060100 2 4.0 13.0 4.0 13.0 3.5 3.5 30 95,000 41 95,000
*When a unit is converted to propane, different size orifices must be used. See separate natural-to-propane
conversion kit instructions.
†Based on altitudes from sea level to 2000 ft above sea level. For altitudes above 2000 ft, reduce input rating
4% for each additional 1000 ft. In Canada, from 2000 ft above sea level to 4500 ft above sea level, derate the unit 10%.
16
Page 17
If the desired gas input is 80,000 Btuh, only a minor change
in the manifold pressure is required.
Observe manifold pressure and proceed as follows to ad-
just gas input:
1. Remove cover screw over regulator adjustment screw on gas valve.
2. Turnregulator adjustment screw clockwise to increase gas input, or turn regulator adjustment screw counterclock­wise to decrease input. Manifold pressure must be be­tween 3.4 and 3.6 in. wg.
Unsafe operation of the unit may result if manifold pressure is outside this range. Personal injury or unit damage may result.
3. Replace cover screw cap on gas valve.
4. Turn offgas supply to unit. Remove manometer from pres­sure tap and replace pipe plug on gas valve. Turn on gas to unit and check for leaks.
Measure Manifold Pressure (Propane Units) — The main burner orifices on a propane gas unit are sized for the unit rated input when the manifold pressure is 3.5 in. wg.
Proceed as follows to adjust gas input on a propane gas
unit:
1. Turn off gas to unit.
2. Remove pipe plug on manifold (see Fig. 20), then con­nect manometer at this point.
3. Turn on gas to unit.
4. Remove cover screw over regulator adjustment screw on gas valve.
5. Adjust regulator adjustment screw for a manifold pres­sure reading of 3.5 in. wg. Turn adjusting screw clock­wise to increase manifold pressure, or turn adjusting screw counterclockwise to decrease manifold pressure.
6. Replace cover screw.
7. Turn off gas to unit. Remove manometer from pressure tap. Replace pipe plug on gas valve, then turn on gas to unit. Check for leaks.
CHECK BURNER FLAME — With burner access panel re­moved, observe the unit heating operation. Watch the burner flames to see if they are light blue and soft in appearance, and that the flames are approximately the same for each burner. See Fig. 21. Refer to Maintenance section for information on burner removal.
AIRFLOWANDTEMPERA TURERISE — The heating sec­tion for each size unit is designed and approved for heating operation within the temperature-rise range stamped on the unit rating plate.
T able5 shows the approved temperature-rise range for each heating input, and the air delivery cfm at various tempera­ture rises. The heating operation airflow must produce a tem­perature rise that falls within the approved range.
Refer to Indoor Airflow and Airflow Adjustments section on page 20 to adjust heating airflow when required.
LIMIT SWITCHES — Normally-closed limit switch (LS) completes the control circuit through the thermostat R cir­cuit. Should the leaving-air temperature rise above the maxi­mum allowable temperature, the limit switch opens and the R control circuit ‘‘breaks.’’Any interruption in the R control
circuit instantly closes the gas valve and stops gas flow to the burners and pilot. The blower motor continues to run until LS resets.
When the air temperature at the limit switch drops to the low-temperature setting of the limit switch, the switch closes and completes the R control circuit. The electric-spark ig­nition system cycles and the unit returns to normal heating operation.
AUXILIARYLIMIT SWITCH — ROLLOUT — The func­tion of the switch is to close the main gas valve in the event of flame rollout. The switch is located above the main burn­ers. When the temperature at the auxiliary switch reaches the maximum allowable temperature, the R control circuit trips, closing the gas valve and stopping gas flow to the burn­ers. The indoor fan motor (IFM) and induced draft motor continue to run until switch is reset.
PIPE PLUG
MANIFOLD
Fig. 20 — Burner Assembly
Fig. 21 — Monoport Burners
17
Page 18
Table 5 — Air Delivery (Cfm) at Indicated Temperature Rise and Rated Heating Input
HEATING
INPUT (Btuh)
TEMPERATURE RISE °F
20 25 30 35 40 45 50 55 60 65 70 75 80
40,000 1389 1111 926 794 694 617 556 — — — — — — 56,000 1944 1556 1296 1111 972 864 778 707 — — — — — 80,000 2778 2222 1852 1587 1389 1235 1111 1010 926 855 794 — — 95,000 3299 2639 2199 1885 1649 1466 1319 1199 1100 1015 942 880 825
NOTE: Dashed areas do not fall within the approved temperature rise range of the unit.
Start Up Cooling Section and Make Adjustments
Complete the required procedures given in the Pre­Start-Up section on page 15 before starting the unit.
Do not jumper any safety devices when operating the unit.
Do not operate the compressor when the outdoor tem­perature is below 40 F (unless accessory low-ambient kit is installed).
Do not rapid-cycle the compressor. Allow 5 minutes be­tween ‘‘on’’ cycles to prevent compressor damage.
CHECKING COOLING CONTROL OPERATION — Start and check the unit for proper cooling control operation as follows:
1. Place room thermostat SYSTEM switch in OFF position. Observe that blower motor starts when FAN switch is placed in ON position and shuts down when FANswitch is placed in AUTO. position.
2. Place SYSTEM switch in COOL position and FANswitch in AUTO. position. Set cooling control below room tem­perature. Observe that compressor, outdoor fan, and indoor blower motors start. Observe that cooling cycle shuts down when control setting is satisfied. The indoor fan will continue to run for 30 seconds.
3. When using an auto.-changeover room thermostat, place both SYSTEM and FAN switches in AUTO. positions. Observe that unit operates in Heating mode when tem­perature control is set to ‘‘call for heating’’(above room temperature) and operates in Cooling mode when tem­perature control is set to ‘‘call for cooling’’ (below room temperature).
IMPORTANT: Three-phase, scroll compressor units are direction-oriented. These units must be checked to ensure proper compressor 3-phase power lead orientation. If not corrected within 5 minutes, the internal protector will shut off the compressor. The 3-phase power leads to the unit must be reversed to correct rotation. When turning backwards, scroll com­pressors emit elevated noise levels, and the differ­ence between compressor suction and discharge pressures may be dramatically lower than normal.
CHECKINGANDADJUSTING REFRIGERANTCHARGE — The refrigerant system is fully charged with R-22 refrig­erant, tested, and factory-sealed.
NOTE: Adjustment of the refrigerant charge is not required unless the unit is suspected of not having the proper R-22 charge.
A superheat charging label is attached to the inside of the compressor access door.The label includes a ‘‘SuperheatCharg­ing Table’’and a ‘‘Required Suction-Tube (F) Temperature’’ chart.
An accurate superheat, thermocouple-, or thermistor-type thermometer, a sling psychrometer, and a gage manifold are required when using the superheat charging method for evalu­ating the unit charge. Do not use mercury or small dial-type
thermometers because they are not adequate for this type of measurement.
When evaluating the refrigerant charge, an indicated adjustment to the specified factory charge must always be very minimal. If a substantial adjustment is indi­cated, an abnormal condition exists somewhere in the cooling system, such as insufficient airflow across ei­ther coil or both coils.
Proceed as follows:
1. Remove caps from low- and high-pressure service
fittings.
2. Using hoses with valve core depressors, attach low- and
high-pressure gage hoses to low- and high-pressure serv­ice fittings, respectively.
3. Start unit in Cooling mode and let unit run until system
pressures stabilize.
4. Measure and record the following:
a. Outdoor ambient-air temperature (F db). b. Indoor inlet-air temperature (F wb). c. Suction-tube temperature (F) at low-side service
fitting.
d. Suction (low-side) pressure (psig).
5. Using ‘‘SuperheatCharging Table,’’ compare outdoor-air
temperature (F db) with indoor inlet-air temperature (F wb) to determine desired system operating superheat temperature. See Tables 6A-6D.
6. Using ‘‘Required Suction-Tube Temperature (F)’’ table,
compare desired superheat temperature with suction (low­side) operating pressure (psig) to determine proper suction­tube temperature. See Table 7.
7. Compare actual suction-tube temperature with proper
suction-tube temperature. Using a tolerance of ± 3° F, add refrigerant if actual temperature is more than 3° F higher than proper suction-tube temperature, or remove refrig­erant if actual temperature is more than 3° F lower than required suction-tube temperature.
NOTE: If the problem causing the inaccurate readings is a refrigerant leak, refer to Check for Refrigerant Leaks sec­tion on page 15.
18
Page 19
Table 6A — Superheat Charging Table, 48HX030
TEMP (F)
OUTDOOR
ENTERING AIR
INDOOR AIR — 1000 CFM
Indoor Air — Ewb (F)
54 56 58 60 62 64 66 68 70 72 74 76
65 SPH 5.5 5.5 5.5 5.5 12.5 19.6 26.6 26.9 27.2 27.5 26.5 25.4 70 SPH ****10.5 17.5 24.5 24.8 25.1 25.4 25.1 24.8 75 SPH ****8.415.5 22.5 22.8 23.1 23.4 23.8 24.2 80 SPH ****6.812.9 18.9 20.3 21.5 22.9 23.0 23.0 85 SPH ****5.110.2 15.4 17.7 20.1 22.3 22.1 21.8 90 SPH **** * 7.911.915.2 18.5 21.8 21.5 21.2
95 SPH **** * 5.68.412.7 17.0 21.2 20.8 20.6 100 SPH **** * * * 9.214.1 19.1 19.5 19.9 105 SPH **** * * * 5.711.417.1 18.2 19.3 110 SPH **** * * * 5.010.0 15.1 16.9 18.6 115 SPH **** ****8.713.0 15.5 18.0
LEGEND
Ewb — Entering Wet Bulb SPH — Superheat at Compressor (F)
*Do not attempt to charge system under these conditions — refrigerant slugging may occur.
Table 6B — Superheat Charging Table, 48HX036
TEMP (F)
OUTDOOR
ENTERING AIR
INDOOR AIR — 1150 CFM
Indoor Air — Ewb (F)
54 56 58 60 62 64 66 68 70 72 74 76
65 SPH 28.6 28.6 28.6 30.4 32.1 33.3 34.3 33.4 32.0 30.7 29.8 28.9 70 SPH 23.8 23.8 23.8 25.5 27.2 29.5 32.3 32.0 30.9 29.7 28.6 27.6 75 SPH 19.0 19.0 19.1 20.6 22.2 25.7 30.4 30.6 29.7 28.7 27.5 26.3 80 SPH 14.9 15.0 15.0 15.8 16.5 21.1 26.5 27.7 27.8 27.8 26.6 25.3 85 SPH 10.9 10.9 10.9 10.9 10.9 16.6 22.6 24.8 25.9 26.9 25.6 24.3 90 SPH 7.6 7.7 7.7 7.0 8.3 12.6 19.1 21.5 23.4 25.3 24.4 23.6
95 SPH *****8.614.5 16.5 20.9 23.6 23.3 22.9 100 SPH ******11.314.3 17.4 20.4 21.1 21.8 105 SPH ******7.110.5 13.9 17.2 19.0 20.8 110 SPH *******7.111.716.4 18.2 19.9 115 SPH ********9.615.5 17.3 19.1
LEGEND
Ewb — Entering Wet Bulb SPH — Superheat at Compressor (F)
*Do not attempt to charge system under these conditions — refrigerant slugging may occur.
Table 6C — Superheat Charging Table, 48HX048
TEMP (F)
OUTDOOR
ENTERING AIR
INDOOR AIR — 1600 CFM
Indoor Air — Ewb (F)
54 56 58 60 62 64 66 68 70 72 74 76
65 SPH 25.8 26.3 27.0 27.6 28.6 29.6 30.5 30.9 31.3 31.7 31.2 30.7
70 SPH 24.2 24.0 23.8 23.6 25.0 26.4 27.8 28.4 29.0 29.7 29.6 29.5
75 SPH 19.7 19.7 19.7 19.7 21.4 23.2 25.0 25.9 26.8 27.6 27.9 28.2
80 SPH 15.8 15.8 15.8 15.8 17.6 19.4 21.2 22.7 24.1 25.6 26.2 26.9
85 SPH 12.0 12.0 12.0 12.0 13.8 15.6 17.5 19.5 21.5 23.5 24.5 25.6
90 SPH 7.5 7.5 7.5 7.5 9.4 11.3 13.2 16.3 19.3 22.4 23.3 24.2
95 SPH ****5.07.09.013.1 17.1 21.2 22.0 22.8 100 SPH *******9.414.3 19.1 20.3 21.4 105 SPH *******5.711.417.1 18.6 20.1 110 SPH ********9.013.5 15.8 18.0 115 SPH ********6.710.0 13.0 16.0
LEGEND
Ewb — Entering Wet Bulb SPH — Superheat at Compressor (F)
*Do not attempt to charge system under these conditions — refrigerant slugging may occur.
19
Page 20
Table 6D — Superheat Charging Table, 48HX060
TEMP (F)
OUTDOOR
ENTERING AIR
INDOOR AIR — 1800 CFM
Indoor Air — Ewb (F)
54 56 58 60 62 64 66 68 70 72 74 76
65 SPH 21.0 21.0 21.0 21.0 22.8 24.7 26.5 27.8 29.1 30.4 29.5 28.6 70 SPH 16.5 16.5 16.5 16.5 18.8 21.1 23.5 25.2 27.0 28.8 28.2 27.6 75 SPH 12.0 12.0 12.0 12.0 14.8 17.6 20.4 22.7 24.9 27.2 26.9 26.6 80 SPH 10.5 10.5 10.5 10.5 12.7 14.9 17.1 19.8 22.5 25.2 25.4 25.5 85 SPH 9.0 9.0 9.0 9.0 10.6 12.3 13.9 17.0 20.0 23.1 23.8 24.5 90 SPH 4.5 4.5 4.5 4.5 6.5 8.5 10.5 14.3 18.1 21.9 22.7 23.5
95 SPH *****4.87.211.716.2 20.7 21.6 22.5 100 SPH ******3.68.613.6 18.6 20.0 21.4 105 SPH *******5.511.116.6 18.5 20.4 110 SPH ********10.0 15.5 17.5 19.4 115 SPH ********9.214.7 16.5 18.5
LEGEND
Ewb — Entering Wet Bulb SPH — Superheat at Compressor (F)
*Do not attempt to charge system under these conditions — refrigerant slugging may occur.
Table 7 — Required Suction-Tube Temperature (F)*
SUPERHEAT
TEMP (F)
SUCTION PRESSURE AT SERVICE PORT (psig)
61.5 64.2 67.1 70.0 73.0 76.0 79.2 82.4 85.7
0 35 37 39 41 43 45 47 49 51 2 37 39 41 43 45 47 49 51 53 4 39 41 43 45 47 49 51 53 55 6 41 43 45 47 49 51 53 55 57
8 43 45 47 49 51 53 55 57 59 10 45 47 49 51 53 55 57 59 61 12 47 49 51 53 55 57 59 61 63 14 49 51 53 55 57 59 61 63 65 16 51 53 55 57 59 61 63 65 67 18 53 55 57 59 61 63 65 67 69 20 55 57 59 61 63 65 67 69 71 22 57 59 61 63 65 67 69 71 73 24 59 61 63 65 67 69 71 73 75 26 61 63 65 67 69 71 73 75 77 28 63 65 67 69 71 73 75 77 79 30 65 67 69 71 73 75 77 79 81 32 67 69 71 73 75 77 79 81 83 34 69 71 73 75 77 79 81 83 85 36 71 73 75 77 79 81 83 85 87 38 73 75 77 79 81 83 85 87 89 40 75 77 79 81 83 85 87 89 91
*Temperature at suction service valve.
INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS
For cooling operation, the recommended airflow is 350 to 450 cfm for each 12,000 Btuh of rated cooling ca­pacity. For heating operation, the airflow must produce a temperature rise that falls within the range stamped on the unit rating plate.
T able5 shows the temperature rise at various airflow rates.
Size 030 and 036 — Table 8 shows both heating and cooling airflows at various external static pressures for unit sizes 030 and 036. Refer to this table to determine the airflow for the system being installed. See Table9 for wet coil pressure drop.
NOTE: Be sure that all supply- and return-air grilles are open, free from obstructions, and adjusted properly.
Shut off gas supply then disconnect electrical power to the unit before changing blower speed. Electrical shock can cause personal injury or death.
Airflow can be changed by changing the lead connections
of the blower motor.
Unit 48HX030 is factory wired for medium speed; unit
48HX036 3-speed motors are factory wired for low speed.
20
Page 21
Table 8 — Dry-Coil Air Delivery* — Horizontal and Downflow Discharge at 230 and 460 V
— Size 030,036 (Deduct 10% from Cfm and Watts for 208 V Operation)
UNIT
48HX
MOTOR
SPEED
AIR
DELIVERY
EXTERNAL STATIC PRESSURE (in. wg)
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
030
Low
Watts 280 275 265 255 250 245 240 † † † † Cfm 820 810 755 700 660 600 560 † † † †
Med
Watts 365 360 350 345 340 330 320 310 300 † † Cfm 1025 1010 975 940 900 850 800 720 630 † †
High
Watts † † 490 480 470 460 445 430 410 390 380 Cfm † † 1300 1255 1200 1150 1080 1005 915 790 620
036
Low
Watts 420 395 385 370 360 350 † † † † † Cfm 1265 1220 1170 1125 1065 1005 † † † † †
Med
Watts 545 525 500 480 460 445 425 405 355 † † Cfm 1550 1485 1420 1355 1280 1210 1125 1035 910 † †
High
Watts ††††615585560535505465† Cfm ††††1565 1460 1350 1230 1100 905 †
*Air delivery values are without air filter and are for dry coil. See
Table9 for wet coil pressure drop. Deduct field-supplied air filterpres­sure drop and wet coil pressure drop to obtain external static pres­sure available for ducting.
†Unit air delivery is outside of operating range.
NOTE: Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Indoor­coil icing may occur at airflows below this point. Water blow-off may occur at airflows above 450 cfm per 12,000 Btuh of rated cooling capacity.
For 208/230-v and A.O. Smith 460-v Blower Motors — The motor leads are color-coded as follows:
3-SPEED black = high speed blue = medium speed red = low speed
To change the speed of the blower motor, remove the fan
motor speed leg lead from the blower relay (BR). This wire is attached to terminal BM for single-phase and 3-phase units. To change the speed, remove and replace with lead for de­sired blower motor speed. Insulate the removed lead to avoid
contact with chassis parts. For 460-v GE Motors — The motor leads are color-coded as
follows:
3-SPEED black = high speed orange = medium blue = jumper red = low speed
To change the speed of the blower motor, remove fan motor speed lead from the blower relay (BR) and replace with the lead for the desired blower motor speed. The motor speed lead is attached to terminal BM. Insulate removed lead end to avoid contact with chassis parts. Connect orange lead to terminal BM of BR. To select high speed on 460-v GE motors, separate the black (female QC) from the blue lead (male QC) and connect the black lead to the BR. Insulate
the blue lead to avoid contact with any chassis parts.
Size 048 and 060 — These units have an integrated control motor (ICM). To configure the unit, move the 5 Easy Select board wires to the terminals which control the air­flow. Refer to the Easy Select interface board (Fig. 18) lo­cated next to the terminals and wiring diagrams for sizes 048 and 060 in back of book.
Perform the following steps for basic system configuration. AUX HEAT RANGE (VIO) — The airflow for unit is preset
at the factory. The airflow selection must not be set at a set­ting lower than the default. Refer to Table 10 for airflow and gas heat input for terminals 1-4.
AC/HP SIZE (BLU) — The preset factory default selec­tion for AC/HP SIZE (air conditioner/heat pump) is set to terminal 3 for size 048 and terminal 4 for size 060. See Table 11 for airflows supplied at terminals. See Table 12 for air delivery in FAN ONLY mode.
Table9—WetCoil Pressure Drop
UNIT SIZE
48HX
AIRFLOW
(cfm)
PRESSURE
DROP
(in. wg)
030
800 0.025
900 0.039 1000 0.057 1200 0.072
036
1000 0.051 1200 0.061 1400 0.068 1600 0.075
048
1400 0.068 1600 0.075 1800 0.088
060
1700 0.082 1900 0.095 2100 0.108 2300 0.123
Table 10 — Dry Coil Air Delivery* — Gas Heating;
Sizes 048,060; Horizontal and Vertical Discharge
for Integrated Control Motor Units at 230-V
(Deduct 10% from Cfm for 208-V Operation)
HEATING INPUT
(Btuh)
EASY SELECT BOARD TERMINALS
1234
Airflow (Cfm)
80,000 1300 1400 1600 1750
100,000 — 1400 1600 1750
*Air delivery values are for dry coil at 230 v.Airflow is independent of
external static pressure within 6 5% of table values up to
0.8 in. wg.
NOTES:
1. Dashed area does not fall within approved range.
2. Theabove values occur withtheAC/HP CFM ADJUST select jumper on the Easy Select interface board set on MED.
3. Airflow can be adjusted 110% or −10% by selecting HI or LO for all modes except FAN ONLY.
21
Page 22
Table 11 — Dry-Coil Air Delivery* Cooling and Heat
Pump Heating; Sizes 048,060; Horizontal and
Vertical Discharge for Integrated Control
Motor Units at 230-V
(Deduct 10% from Cfm for 208-V Operation)
UNIT SIZE
48HX
EASY SELECT BOARD TERMINALS
1234
Airflow (Cfm)
048,060 Cooling Mode
048 Heating Mode
1260 1440 1575 1800
060 Heating Mode 1400 1600 1750 2000
*Air delivery values are for dry coil at 230 v.Airflow is independent of
external static pressure within 65% of table values up to
0.8 in wg.
NOTE: Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Indoor-coil icing may occur at airflows below this point. Water blow-off may oc­cur at airflows above 450 cfm per 12,000 Btuh of rated cooling capacity.
Table 12 — Dry Coil Air Delivery* Fan Only; Sizes
048,060; Horizontal and Vertical Discharge for
Integrated Control Motor Units at 230-V
(Deduct 10% from Cfm for 208-V Operation)
UNIT SIZE
48HX
FAN ONLY
AIRFLOW (Cfm)
048 1400 060 1750
*Air delivery values are for dry coil at 230 V.Airflow is independent of
external static pressure within 65% of table values up to
0.8 in. wg.
TYPE (ORN) — The TYPE is a preset factory default se­lection. The preset factory default setting is HPC for size 048 and HP for size 060. Default setting should not be altered.
AC/HP CFM ADJUST (BLK) — The preset factory default selection is MED. Selections HI and LO will adjust the air­flow supplied for all operational modes (see table below). The selection options allow installer to adjust airflow to meet such individual needs as noise and static compensation, etc.
MODE FAN ONLY COOLING HEATING
LO — Adjust −15% −10% −10%
HI — Adjust 15% 10% 10%
OUTDOOR-AIR THERMOSTAT — The outdoor-air ther­mostat (OAT) is a field-adjustable control that controls the temperature at which the 48HX unit changes from heat pump operation to gas burner operation in first-stage heating. It ad­justs temperatures from 0° to 52 F. (Second-stage heating is always gas-fired heat.)
As outdoor temperatures decrease, the efficiency of heat pumps decrease and a point is reached where gas heat be­comes more economical than the heat pump. This point is known as the economic balance point (EBP). At outdoor air temperatures above the EBP,the 48HX unit operates the heat pump on a call for first-stage heat and operates the gas burn­ers on a call for second-stage heat. At temperatures below the EBP, the OAT locks out the heat pump and operates the gas burners for both the first- and second-stage heat.
The EBP is dependent on local utility rates. If the local cost of electricity is high or the local cost of gas is low, it is cost effective to switch to gas-fired heating at a warmer out­door temperature.
Conversely, if the local cost of electricity is low or the local cost of gas is high, it is cost effective to switch to gas­fired heating at a colder outdoor temperature.
The OAT must be field set based on the local EBP. To determine the EBP, first find the cost of gas on a $/Therm basis and the cost of electricity on a $/kW basis. Refer to Fig. 22, 48HX Economic Balance Point. On the horizontal axis plot the cost of electricity and draw a vertical line from this point. On the vertical axis plot the cost of gas and draw a horizontal line until it intersects the vertical line. This in­tersection is the economic balance point and can be read di­rectly by determining where the intersection falls in the set of curves. This value will be in degrees Fahrenheit.
Once this value has been determined, the outdoor-air thermostat can be set to provide for the most economical operation.
EXAMPLE:
Cost of Electricity $ 0.1/kW
Cost of Gas $ 0.9/Therm From Economic Balance Point Chart, Fig. 22, read that the
EBP is 30 F.
The EBP differs from the thermal balance point. The ther­mal balance point is the outdoor temperature below which the heat pump can no longer satisfy the heating require­ments of the building. The thermal balance point is deter­mined by the thermal loss of the building and the size of the heat pump. Unlike the EBP, no adjustment is necessary based on the thermal balance point; the thermostat simply calls for first-stage heat or second-stage heat as necessary.
To Set OAT — The OAT is located in the control box be­neath the mounting bracket and is factory set at 40 F. Turn knob on the OAT to the temperature that is equal to the EBP. Refer to Fig. 22 and determine EBP as described previously. Uncoil the OAT capillary and run it outside the unit to sense outdoor temperature. The capillary may be supported by any object outside the unit that does not get warm (such as the incoming gas line) but must not rest on the unit itself. If the outdoor air temperature is below the OAT setting, the cool­ing mode is locked out.
Sequence of Operation
HEATING SEQUENCE OF OPERATION — See wiring dia­grams in back of book and unit wiring label.
On a call for heat, one of 2 Heating modes occurs, de­pending on the field setting of the economic balance point.
The first Heating mode occurs when the outdoor tempera­ture is warmer than the EBP. On a call for heat, the ther­mostat makes circuits R-Y and R-G. When compressor time delay (5 6 2 minutes) is completed, a circuit is made to C, starting compressor (COMP) and outdoor-fan motor (OFM). Circuit R-G also is completed, energizing indoor-fan relay (IFR) and starting indoor-fan motor (IFM) after a 1-second delay.Should room temperature continue to fall, circuit R-W is made through second-stage thermostat bulb. One relay opens, turning off the compressor, and another relay is energized signaling the integrated gas control (IGC) board to bring on the gas heat. When the thermostat is satisfied, contacts open, deenergizing contactor and relay; motors and gas heater de­energize. The IFM may be controlled by a time-delay relay that keeps the fan on for 30 seconds.
The second Heating mode occurs when the outdoor tem­perature is colder than the EBP. On a call for heat, the ther­mostat energizes the gas heat relay, signaling the IGC board to bring on the gas heat. In this Heating mode, both first­and second-stage heat is gas heating. When thermostat is
22
Page 23
satisfied, contacts open, deenergizing contactor and relay; motors and gas heater deenergize. The IFM may be con­trolled by a time-delay relay that keeps the fan on for 30 seconds.
An LED (light-emitting diode) indicator is provided on the control board to monitor operation. The control board is located by removing the burner access panel. During normal operation, the LED is continuously on. See Table 13 for er­ror codes.
See Fig. 23 for typical heat pump operation, heating mode.
Table 13 — LED Indications
ERROR CODE LED INDICATION
Normal Operation On Hardware Failure Off Fan On/Off Delay Modified 1 Flash Limit Switch Fault 2 Flashes Flame Sense Fault 3 Flashes Four Consecutive Limit Switch Faults 4 Flashes Ignition Lockout Fault 5 Flashes Induced-Draft Motor Point 6 Flashes Rollout Switch Fault 7 Flashes Internal Control fault 8 Flashes
NOTES:
1. There is a 3-second pause between error code displays.
2. If more than one error code exists, all applicable error codes will
be displayed in numerical sequence.
3. This chart is on the wiring diagram located inside the burner ac-
cess panel.
COOLING SEQUENCE OF OPERATION — When the room temperature rises to a point that is slightly above the cooling control setting of the thermostat, the thermostat completes the circuit between thermostat terminal R to terminals Y and G. These completed circuits through the thermostat connect contactor coil (C) (through unit wire Y) and blower relay
coil (BR) (through unit wire G) across the 24-v secondary of transformer (TRAN).
NOTE: The blower relay coil (BR) is used on non-ICM units; ICM units use evaporator (indoor) fan on (IFO) connection.
The normally-open contacts of energizedcontactor (C) close and complete the circuit through compressor motor (COMP) to outdoor-fan motor (OFM). Both motors start instantly.
On non-ICM units, the set of normally-open contacts of energized relay BR closes and completes the circuit through blower (indoor) fan motor (IFM). On ICM units, the IFO completes the circuit through IFM. The blower motor starts instantly.
NOTE: Once the compressor has started and then has stopped, it should not be started again until 5 minutes have elapsed.
The cooling cycle remains ‘‘on’’ until the room tempera­ture drops to point that is slightly below the cooling control setting of the room thermostat. At this point, the ther­mostat ‘‘breaks’’ the circuit between thermostat terminal R to terminals Y and G. These open circuits deenergize con­tactor coil C and relay coil BR. The OFM and compressor motor stop. After a 30-second delay, the IFM stops. The unit is in a standby condition, waiting for the next call for cool­ing from the room thermostat.
See Fig. 24 for typical heat pump operation, cooling mode. DEFROST — Defrost board (DB) is a time and temperature
control, which includes a field-selectable time period be­tween checks for defrost (30, 50, and 90 minutes). Elec­tronic timer and defrost cycle start only when contactor is energized and defrost thermostat (DFT) is closed.
Defrost mode is identical to Cooling mode, except outdoor­fan motor stops and gas heat turns on to warm air supplying the conditioned space. Once the gas heat has been ener­gized, it is locked in for a minimum of 1 minute.
Fig. 22 — 48HX Economic Balance Point
23
Page 24
STRAINER
ACCUMULATOR
COMPRESSOR
STRAINER
LCS
OUTDOOR COIL
INDOOR COIL
A
B
D
C
Check Valves
A
Open
B
Closed
C
Open
D
Closed
LEGEND
LCS — Loss of Charge Switch
Acutrol™ Metering Device Check Valve (Arrow indicates direction of flow)
HEATING CYCLE
1. Hot gas from compressor flows through the 4-way valve and is directed to thecooling liquid line check valve. It is then condensed and directed through subcooling circuits and out to the strainer and the check valve in the heating liquid line.
2. The refrigerant then feeds the outdoor coil through the Acutrol metering device on each circuit.
3. Each circuit evaporates the refrigerant and the circuits are com­binedin the outdoor headerwith some ofthe circuits flowing through the check valve.
4. The refrigerant then flows through the 4-way valve, accumulator, and back to the compressor.
Fig. 23 — Typical Heat Pump Operation, Heating Mode
24
Page 25
STRAINER
ACCUMULATOR
COMPRESSOR
STRAINER
LCS
OUTDOOR COIL
INDOOR COIL
A
B
D
C
CheckValves
A
Closed
B
Open
C
Closed
D
Open
LEGEND
LCS — Loss of Charge Switch
Acutrol™ Metering Device Check Valve (Arrow indicates direction of flow)
COOLING CYCLE
1. Hot gas from compressor flows through the 4-way valve and is directed to the heating liquid line check valve. It is then con­densedandsubcooledthrough converging circuits. Refrigerant leaves the outdoor coil by way of the strainer and the check valve in the cooling liquid line.
2. The refrigerant then feeds the indoor coil through the Acutrol metering device on each circuit.
3. Each circuit evaporates the refrigerant and the circuits are com­bined in the indoor coil header with some of the circuits flowing through the check valve.
4. The refrigerant then flows through the 4-way valve, accumulator, and back to the compressor.
Fig. 24 — Typical Heat Pump Operation, Cooling Mode
25
Page 26
MAINTENANCE
To ensure continuing high performance, and to minimize the possibility of premature equipment failure, periodic main­tenance must be performed on this equipment. This dual fuel heat pump should be inspected at least once each year by a qualified service person. To troubleshoot heating or cooling of units, refer to Troubleshooting tables at the back of the book.
NOTE TO EQUIPMENT OWNER: Consult your local dealer about the availability of a maintenance contract.
The ability to properly perform maintenance on this equip­ment requires certain expertise, mechanical skills, tools, and equipment. If you do not possess these, do not at­tempt to perform any maintenance on this equipment other than those procedures recommended in the User’s Manual. FAILURE TO HEED THIS WARN­ING COULD RESULT IN SERIOUS PERSONAL INJURY AND POSSIBLE DAMAGE TO THIS EQUIPMENT.
The minimum maintenance requirements for this equip­ment are as follows:
1. Inspect air filter(s) each month. Clean or replace when
necessary.
2. Inspect indoor coil, drain pan, and condensate drain each
cooling season for cleanliness. Clean when necessary.
3. Inspect blower motor and wheel for cleanliness and check
lubrication each heating and cooling season. Clean and lubricate (if required) when necessary. For first heating season, inspect blower wheel bimonthly to determine proper cleaning frequency.
4. Check electrical connections for tightness and controls
for proper operation each heating and cooling season. Serv­ice when necessary.
5. Check and inspect heating section before each heating sea-
son. Clean and adjust when necessary.
6. Check flue hood screen and remove any obstructions if
necessary.
7. Check vent screen and clean if necessary.
Failure to follow these warnings could result in serious personal injury:
1. Turn off gas supply, then turn off electrical power to the unit before performing any maintenance or serv­ice on the unit.
2. Use extreme caution when removing panels and parts. As with any mechanical equipment, personal injury can result from sharp edges, etc.
3. Never place anything combustible either on, or in con­tact with, the unit.
4. Should overheating occur, or the gas supply fail to shut off, shut off the external main manual gas valve to the unit, then shut off the electrical supply.
Air Filter
Never operate the unit without a suitable air filter in the return-air duct system. Always replace the filter with the same dimensional size and type as originally installed. See Table 1 for recommended filter sizes.
Inspect air filter(s) at least once each month and replace (throwaway-type) or clean (cleanable-type) at least twice dur­ing each heating and cooling season or whenever the filter(s) becomes clogged with dust and lint.
Unit Top Removal
NOTE: When performing maintenance or service proce­dures that require removal of the unit top, be sure to perform all of the routine maintenance procedures that require top removal, including: inspection of the heat exchanger area, coil inspection and cleaning, and condensate drain pan in­spection and cleaning.
Only qualified service personnel should perform mainte­nance and service procedures that require unit top removal. Refer to the following top removal procedures:
1. Turn off gas supply, then turn off electric power to unit.
2. Remove all screws that secure unit top, including screws
around 4 sides and those on top that screw into internal divider panels. Save all screws.
3. Lift top from unit carefully. Set top on edge.
4. Carefully replace and secure unit top to unit, using screws
removed in Step 2, when maintenance and/or service pro­cedures are completed. (Be sure to use original screws that have rubber washers to seal out water when securing top to internal divider panels.)
Indoor Blower and Motor
NOTE: Motors without oilers are prelubricated. Do not at­tempt to lubricate these motors.
For longer life, operating economy, and continuing effi­ciency, clean accumulated dirt and grease from the blower wheel and motor annually.
Lubricate the motor every 5 years if the motor is used in­termittently (thermostat FAN switch in AUTO. position), or every 2 years if the motor is used continuously (thermostat FAN switch in ON position).
Turn off the gas supply, then disconnect and tag elec­trical power to the unit before cleaning and lubricating the blower motor and wheel. Failure to adhere to this warning could cause personal injury or death.
To clean and lubricate the blower motor and wheel for direct-drive models:
1. Remove and disassemble blower assembly as follows:
a. Remove blower access door. b. On units without ICM, disconnectmotor lead from blower
relay (BR). Disconnect yellow lead from terminal L2 of the contactor.
c. On all units remove blower assembly from unit. Re-
move screws securing blower to gas partition and slide assembly out. Be careful not to tear insulation in blower compartment.
d. Ensure proper reassembly by marking blower wheel
and motor in relation to blower housing before dis­assembly.
e. Loosen setscrew(s) that secures wheel to motor shaft,
remove screws that secure motor mount brackets to housing, and slide motor and motor mount out of housing.
2. Lubricate motor as follows:
a. Thoroughly clean all accumulations of dirt or grease
from motor housing.
b. Remove dust caps or plugs from oil ports located at
each end of motor.
26
Page 27
c. Use a good grade of SAE (Society of Automotive En-
gineers) 20 nondetergent motor oil and put one tea­spoon (3⁄16oz. or 16 to 25 drops) in each oil port.
d. Allow time for oil to be absorbed by each bearing,
then wipe excess oil from motor housing.
e. Replace dust caps or plugs in oil ports.
3. Remove and clean blower wheel as follows: a. Ensure proper reassembly by marking wheel
orientation.
b. Lift wheel from housing. When handling and/or clean-
ing blower wheel, be sure not to disturb balance weights (clips) on blower wheel vanes.
c. Remove caked-on dirt from wheel and housing with a
brush. Remove lint and/or dirt accumulations from wheel and housing with vacuum cleaner, using soft brush at-
tachment. Remove grease and oil with mild solvent. d. Reassemble wheel into housing. e. Reassemble motor into housing. Be sure setscrews are
tightened on motor shaft flats and not on round part of
shaft. f. Reinstall blower access door.
4. Restore electrical power, then gas supply to unit. Start unit and check for proper blower rotation and motor speeds during heating and cooling cycles.
Flue Gas Passageways — To inspect the flue col-
lector box and upper areas of the heat exchanger:
1. Remove the combustion blower wheel and motor assem­bly according to directions in Combustion-Air Blower sec­tion below.
2. Remove the 3 screws holding the blower housing to the flue collector box cover (see Fig. 25).
3. Remove the 12 screws holding the flue collector box cover (Fig. 25) to the heat exchanger assembly. Inspect the heat exchangers.
4. Clean all surfaces as required using the wire brush.
Combustion-Air Blower — Clean periodically to as-
sure proper airflow and heating efficiency. Inspect blower wheel every fall and periodically during heating season. For the first heating season, inspect blower wheel bimonthly to determine proper cleaning frequency.
T oinspect blower wheel, remove draft hood assembly.Shine a flashlight into opening to inspect wheel. If cleaning is re­quired, remove motor and wheel as follows:
1. Remove burner access panel. (See Fig. 26.)
2. Remove the 7 screws that attach induced-draft motor mount-
ing plate to blower housing. (See Fig. 25.)
3. Slide the motor and blower wheel assembly out of the
blower housing. (See Fig. 27.) Clean the blower wheel. If additional cleaning is required, continue with Steps 4 and 5.
4. To remove blower, remove 2 setscrews. (See Fig. 27.)
5. To remove motor, remove 4 screws that hold blower hous-
ing to mounting plate. Remove the motor cooling fan by removing one setscrew. Remove nuts that hold motor to mounting plate.
6. To reinstall, reverse the procedure outlined above.
Limit Switch — Remove blower panel. Limit switch is
located on the gas partition.
Burner Ignition — Unit is equipped with a direct spark
ignition 100% lockout system. Ignition module is lo­cated in the control box. Module contains a self-diagnostic LED. During servicing, refer to Table 13 for LED interpretation.
If lockout occurs, unit may be reset by either momentarily interrupting power supply to unit, or turning selector switch to OFF position at the thermostat.
Main Burners — At the beginning of each heating sea-
son, inspect for deterioration or blockage due to corrosion or other causes. Observe the main burner flames and adjust if necessary.
When servicing gas train, do not hit or plug orifice spuds.
REMOVAL OF GAS TRAIN
1. Shut off manual gas valve.
2. Shut off power to unit
3. Remove burner access panel. (See Fig. 26.)
4. Disconnect gas piping at unit gas valve.
5. Remove wires connected to gas valve. Mark each wire.
6. Remove ignitor and sensor wires at the ignitor module.
7. Remove the mounting screw that attaches the burner rack
to the basepan. (See Fig. 25.)
8. Slide the burner rack out of the unit. (See Fig. 25
and 28.)
9. To reinstall, reverse the procedure outlined above.
FLUE COLLECTOR BOX (HIDDEN)
INDUCED DRAFT MOTOR MOUNTING PLATE
BLOWER HOUSING
BURNER RACK
MOUNTING SCREW
Fig. 25 — Blower Housing and Flue Collector Box
27
Page 28
OutdoorCoil,IndoorCoil, and Condensate Drain Pan —
Inspect the outdoor coil, indoor coil, and conden­sate drain pan at least once each year. Proper inspection and cleaning requires the removal of the unit top. See Unit Top Removal section on page 26.
The coils are easily cleaned when dry; therefore, inspect and clean the coils either before or after each cooling sea­son. Remove all obstructions, including weeds and shrubs, that interfere with the airflow through the outdoor coil. Straighten bent fins with a fin comb. If coated with dirt or lint, clean the coils with a vacuum cleaner, using the soft
brush attachment. Be careful not to bend the fins. If coated with oil or grease, clean the coils with a mild detergent-and­water solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, wiring, or air filter(s). For best results, spray outdoor coil fins from inside to outside the unit. Be sure to clean between outer and inner sections of outdoor coil. Be sure to flush all dirt and debris from the unit base.
Inspect the drain pan and condensate drain line when in­specting the coils. Clean the drain pan and condensate drain by removing all foreign matter from the pan. Flush the pan and drain tube with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s). If the drain tube is restricted, clear it with a ‘‘plumbers snake’’or similar probe device. Ensure that the auxiliary drain port above the drain tube is also clear.
Outdoor Fan
Keep the outdoor fan free from all obstructions to en­sure proper cooling operation. Never place articles on top of the unit. Damage to unit may result.
1. Remove 2 screws at bottom and 2 screws along sides of
condenser air intake grille and remove plastic grille.
2. Inspect the fan blades for cracks or bends.
3. If fan needs to be removed, loosen the setscrew and slide
the fan off the motor shaft.
4. When replacing fan blade, position blade so that lead-
ing edge is
1
⁄2in. in front of fan orifice. See Fig. 19.
5. Ensure that setscrew engages the flat area on the motor
shaft when tightening.
6. Replace grille.
BURNER ACCESS PANEL
Fig. 26 — Burner Access Panel
BLOWER HOUSING
2 SETSCREWS (HIDDEN)
Fig. 27 — Removal of Motor and Blower Wheel
Fig. 28 — Burner Rack Removed
28
Page 29
Electrical Controls and Wiring— Inspect and check
the electrical controls and wiring annually. Be sure to turn off the gas supply, and then the electrical power to the unit.
Remove the control, blower, and compressor compart­ment access panels to locate all the electrical controls and wiring. Check all electrical connections for tightness. Tighten all screw connections. If any smoky or burned connections are noticed, disassemble the connection, clean all the parts, restrip the wire end and reassemble the connection properly and securely.
After inspecting the electrical controls and wiring, re­place all the panels. Start the unit, and observe at least one complete heating cycle and one complete cooling cycle to ensure proper operation. If discrepancies are observed in ei­ther or both operating cycles, or if a suspected malfunction has occurred, check each electrical component with the proper electrical instrumentation. Refer to the unit wiring label when making these checkouts.
NOTE: Refer to the heating and/or cooling sequence of op­eration in this publication as an aid in determining proper control operation.
RefrigerantCircuit— Inspect all refrigerant tubing con-
nections and the unit base for oil accumulations annually. Detecting oil generally indicates a refrigerant leak.
If oil is detected or if low cooling performance is sus­pected, leak-test all refrigerant tubing using an electronic
leak-detector, halide torch, or liquid-soap solution. If a refrigerant leak is detected, refer to Check for Refrigerant Leaks section on page 15.
If no refrigerant leaks are found and low cooling perfor­mance is suspected, refer to Checking and Adjusting Refrigerant Charge section on page 18.
Gas Input — The gas input does not require checking
unless improper heating performance is suspected. If a prob­lem exists, refer to Start-Up section on page 15.
Indoor Airflow — The heating and/or cooling airflow
does not require checking unless improper performance is suspected. If a problem exists, be sure that all supply- and
return-air grilles are open and free from obstructions, and that the air filter is clean. When necessary, refer to Indoor
Airflow andAirflowAdjustments section on page 20 to check the system airflow.
Metering Device —Acutrol™ Device — This me-
tering device is a fixed orifice and is located in the header to the indoor and outdoor coils.
Liquid LineStrainer— The liquid line strainer (to pro-
tect metering device) is made of wire mesh and located in the liquid line on the inlet side of the metering device.
29
Page 30
TROUBLESHOOTING
Cooling and Heating
SYMPTOM CAUSE REMEDY
Compressor and out­door fan will not start.
OAT set above outdoor ambient temperature Lower OAT setting. Power failure Call power company. Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker. Defective thermostat, contactor, transformer,
control relay, or defrost board
Replace component.
Insufficient line voltage Determine cause and correct. Incorrect or faulty wiring Check wiring diagram and rewire correctly. Thermostat setting too high Lower thermostat setting below room temperature. Units have a 5-minute time delay DO NOT bypass this compressor time delay — wait
for 5 minutes until time-delay relay is deenergized.
Compressor will not start but outdoor fan runs.
Faulty wiring or loose connections in compressor circuit
Check wiring and repair or replace.
Compressor motor burned out, seized, or internal overload open
Determine cause. Replace compressor.
Defective run capacitor or overload Determine cause and replace. One leg of 3-phase power dead Replace fuse or reset circuit breaker.
Determine cause.
Low input voltage (20% low) Determine cause and correct.
Three-phase scroll compressor makes excessive noise, and there may be a low pressure differential
Scroll compressor is rotating in the wrong direction
Correct the direction of rotation by reversing the 3-phase power leads to the unit. Shut down unit to allow pressures to equalize.
Compressor cycles (other than normally satisfying thermostat).
Refrigerant overcharge or undercharge Recover refrigerant, evacuate system, and recharge
to capacities shown on nameplate. Defective compressor Replace and determine cause. Insufficient line voltage Determine cause and correct. Blocked condenser coil Determine cause and correct. Defective run/start capacitor, overload,
or start relay
Determine cause and replace. Defective thermostat Replace thermostat.
Faulty condenser-fan motor or capacitor Replace. Damaged reversing valve Determine cause and correct. Restriction in refrigerant system Locate restriction and remove.
Compressor operates continuously.
Dirty air filter Replace filter. Unit undersized for load Decrease load or increase unit size. Thermostat set too low Reset thermostat. Low refrigerant charge Locate leak, repair, and recharge. Leaking valves in compressor Replace compressor. Frosted coil with incorrect defrost operation Check defrost time settings. Reset as necessary.
Check defrost temperature switch. Replace as necessary. Air in system Recover refrigerant, evacuate system, and recharge. Outdoor coil dirty or restricted Clean coil or remove restriction.
Excessive head pressure.
Dirty air filter Replace filter. Dirty condenser coil Clean coil. Refrigerant overcharged Recover excess refrigerant. Air in system Recover refrigerant, evacuate system, and recharge. (Heat) Indoor air restricted or recirculating Determine cause and correct. Indoor or outdoor air restricted or
air short-cycling
Determine cause and correct.
Head pressure too low. Low refrigerant charge Check for leaks, repair and recharge.
Compressor valves leaking Replace compressor. Restriction in liquid tube Remove restriction.
LEGEND
OAT — Outdoor Air Thermostat
30
Page 31
Cooling and Heating (cont)
SYMPTOM CAUSE REMEDY
Excessive suction pressure.
(Cool) High heat load Check for source and eliminate. Reversing valve hung up or leaking internally Replace valve. Refrigerant overcharged Recover excess refrigerant.
Suction pressure too low.
(Cool) Dirty air filter Replace filter. (Heat) Outdoor coil frosted Move timer on control board to 30 minutes
between defrost cycles. Low refrigerant charge Check for leaks, repair and recharge. Metering device or low side restricted Remove source of restriction. (Cool) Insufficient coil airflow Increase air quantity. Check filter — replace if
necessary. (Cool) Temperature too low in conditioned area Reset thermostat. (Cool) Outdoor ambient below 40 F Install low-ambient kit. Field-installed filter-drier restricted Replace.
Compressor runs but outdoor fan does not.
NC (normally closed) contacts on defrost board open
Check condition of relay on board. Replace if
necessary.
Integrated control motor (sizes 048 and
060) IFM does not run.
Motor overload open Check motor temeprature.
Replace motor or capacitor. Blower wheel not secured to shaft Properly tighten blower wheel to shaft. Insufficient voltage at motor Determine cause and correct. Power connectors not properly seated Connectors should snap easily; do not force.
Integrated control motor (sizes 048 and
060) IFM runs when it should be off.
Motor programmed with a delay profile Allow a few minutes for motor to shut off. With thermostat in off state, the voltage on
G,Y1,Y,Y2,W with respect to common, should be
1
⁄2of actual low voltage supply
If measured voltage is more than
1
⁄2, the thermo­stat is incompatible with motor. If voltage is less than
1
⁄2, the motor has failed.
Integrated control motor (sizes 048 and
060) IFM operation is intermittent.
Water dripping into motor Verify proper drip loops in connector wires. Connectors not firmly seated Gently pull wires individually to be sure they are
crimped into the housing.
LEGEND
IFM — Indoor Fan Motor
Gas Heating
SYMPTOM CAUSE REMEDY
Burners will not ignite. Water in gas line Drain. Install drip leg.
No power to furnace Check power supply fuses, wiring, or circuit breaker. No 24-v power supply to control
circuit
Check transformer. NOTE: Some transformers have internal overcurrent
protection that requires a cool-down period to reset. Miswired or loose connections Check all wiring and wirenut connections. Burned-out heat anticipator in
thermostat
Replace thermostat. Broken thermostat wire Run continuity check. Replace wire if necessary.
Misaligned spark electrodes Check flame ignition and sense electrode positioning.
Adjust as necessary. No gas at main burners 1. Check gas line for air. Purge as necessary.
NOTE: After purging gas line of air, wait at least 5 minutes for any gas to dissipate before attempting to light unit.
2. Check gas valve.
Inadequate heating. Dirty air filter Clean or replace filter as necessary.
Gas input to furnace too low Check gas pressure at manifold. Match with that on
unit nameplate. Unit undersized for application Replace with proper unit or add additional unit. Restricted airflow Clean or replace filter. Remove any restriction. Blower speed too low Use faster speed tap if available, or install alternate
motor. Limit switch cycles main burners Check rotation of blower, thermostat heat anticipator
settings, temperature rise of unit. Adjust as necessary.
Poor flame characteristics. Incomplete combustion results in:
Aldehyde odors, carbon monox­ide, sooting flame, floating flame
1. Tighten all screws around burner compartment.
2. Cracked heat exchanger. Replace.
3. Unit overfired. Reduce input (change orifices or adjust gas line or manifold pressure).
4. Check burner alignment.
31
Page 32
LED Troubleshooting — Error Code
SYMPTOM CAUSE REMEDY
Hardware failure. (LED OFF)
Loss of power to control module (IGC).
Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and transformer. Units without a 24-v circuit breaker have an internal overload in the 24-v transformer. If the overload trips, allow 10 minutes for automatic reset.
Limit switch fault. (LED 2 flashes)
High temperature limit switch is open. Check the operation of the indoor-fan motor. Ensure that
the supply-air temperature rise is in accordance with the range on the unit nameplate.
Flame sense fault. (LED 3 flashes)
The IGC sensed flame that should not be present.
Reset unit. If problem persists, replace control board.
4 consecutive limit switch trips. (LED 4 flashes)
Inadequate airflow to unit. Check operation of indoor-fan motor and that supply-air
temperature rise agrees with range on unit nameplate information.
Ignition lockout. (LED 5 flashes)
Unit unsuccessfully attempted ignition for 15 minutes.
Check ignitor and flame sensor electrode spacing, gaps, etc. Ensure that flame sense and ignition wires are properly terminated. Verify that unit is obtaining proper amount of gas.
Induced-draft motor fault. (LED 6 flashes)
IGC does not sense that induced-draft motor is operating.
Check for proper voltage. If motor is operating, check the speed sensor plug/IGC Terminal J2 connection. Proper connection:
PIN 1 — White, PIN 2 — Red, PIN 3 — Black.
Rollout switch fault. (LED 7 flashes)
Rollout switch has opened. Rollout switch will automatically reset, but IGC will continue
to lockout unit. Check gas valve operation. Ensure that induced-draft blower wheel is properly secured to motor shaft. Reset unit at unit disconnect.
Internal control fault. (LED 8 flashes)
Microprocessor has sensed an error in the software or hardware.
If error code is not cleared by resetting unit power, replace the IGC.
If the IGC must be replaced, be sure to ground yourself to dissipate any electrical charge that may be present before handling new control board. The IGC is sensitive to static elec­tricity and may be damaged if the necessary precautions are not taken.
IMPORTANT: Refer to Troubleshooting, Heating chart for addi­tional troubleshooting analysis.
LEGEND
IGC — Integrated Gas Unit Controller LED — Light-Emitting Diode
32
Page 33
Page 34
Copyright 1998 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 5a 5a
PC 111 Catalog No. 534-722 Printed in U.S.A. Form 48HX-3SI Pg 34 9-98 Replaces: 48HX-2SI
Page 35
Page 36
START-UP CHECKLIST
(Remove and Store in Job File)
I. PRELIMINARY INFORMATION
MODEL NO.: DATE:
SERIAL NO.: TECHNICIAN:
II. PRE-START-UP (insert checkmark in box as each item is completed)
M VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT M VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS M CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS M CHECK GAS PIPING FOR LEAKS M CHECK THAT INDOOR AIR FILTER IS CLEAN AND IN PLACE M VERIFY THAT UNIT INSTALLATION IS LEVEL M CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW
TIGHTNESS
M SET OUTDOOR-AIR THERMOSTAT (OAT) TO SELECTION BASED ON ECONOMIC BALANCE
POINT (EBP). SEE PAGE 22.
III. START-UP
ELECTRICAL
SUPPLY VOLTAGE L1-L2
L2-L3 L3-L1 COMPRESSOR AMPS L1 L2 L3 COMPRESSOR AMPS L1 L2 L3 INDOOR FAN AMPS
TEMPERATURES
OUTDOOR-AIR TEMPERATURE
DB
RETURN-AIR TEMPERATURE
DB WB COOLING SUPPLY AIR GAS HEAT SUPPLY AIR
PRESSURES
GAS INLET PRESSURE
IN. WG
GAS MANIFOLD PRESSURE
IN. WG
REFRIGERANT SUCTION
PSIG
REFRIGERANT DISCHARGE
PSIG
M VERIFY REFRIGERANT CHARGE USING CHARGING TABLES M VERIFY THAT 3-PHASE SCROLL COMPRESSOR IS ROTATING IN CORRECT DIRECTION
----------------------------------------------------------------------------------------
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
Copyright 1998 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 5a 5a
PC 111 Catalog No. 534-722 Printed in U.S.A. Form 48HX-3SI CL-1 9-98 Replaces: 48HX-2SI