Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precautions in the li terature, ta gs and label s attached t o the uni t, and
other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
Before performing service or maintenance operations on
unit, turn off main power switch to unit and insta ll lockout
tag. Ensure electrical service to rooftop unit agrees with
voltage and amperage listed on the unit rating plate. Electrical shock could cause personal injury.
Disconnect gas piping from unit when leak
testing at pressure greater than 1/2 psig. Pressures greater than
damage resulting in hazardous condition. If
gas valve is subjected to pressure greater than
1
/
psig, it
2
pressure testing field-supplied gas piping at
pressures of
to such piping must be isolated by manually
closing the gas valve(s).
1
/2 psig will cause gas valve
must
be replaced before use. When
1
/2 psig or less, a unit connected
INSTALLATION
Unit is shipped in the vertical discharge configuration. To
convert to horizontal discharge application, remove duct opening covers. Using the same screws, install covers on duct openings in basepan of unit with insulation-side down. Seals around
openings must be tight.
NOTE: Any combination of supply and return ducting is permissible, i.e., vertical supply combined with horizontal return.
Step 1 — Provide Unit Support
ROO F CU R B — Assemble and instal l acces sory roof curb in
accordance with instructions shipped with curb. See Fig. 1. Install insulation, cant strips, roofing felt, and counter flashing as
shown.
If electric control power or gas service is to be routed through
the basepan, attach the accessory thru-the-bottom service connections to the basepan in accordance with the accessory installation instructions. Connections must be installed before unit is
set on roof curb.
Fig. 2. This is necessary for unit drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
SLAB MOUNT (Horizontal Units Only) — Provide a level
concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of condenser-coil air inlet to
prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
Ductwork must be attached to curb, not to the unit.
IMPORTANT: The gasketing of th e unit to the roof curb
is critical for a watertight seal. Install gasket supplied
with the roof curb as shown in Fig. 1. Improperly
applied gasket can result in air leaks and poor unit
performance.
Curb should be level. Unit leveling tolerances a re shown in
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Ta b 1 a 6 a
PC 111Catalog No. 534-767Printed in U.S.A.Form 48HJ-18SIPg 19-00Replaces: 48HJ-17SI
48/50HJ
UNIT SIZE
“A”
ROOF CURB
ACCESSORY
004-007
CRRFCURB001A00 1′-2″ [356]
CRRFCURB002A00 2′-0″ [610]
CONNECTOR
“G”
“F”
“E”
D ALT
PKG. ACCY.
CRBTMPWR001A00
CRBTMPWR003A00
″
″
2
2
/
/
1
1
[12.7] NPT
CONTROL
″ [19] NPT
POWER
4
/
3
″
4
/
3
GAS
[12.7] NPT
″ [31.7]CRBTMPWR002A00
/
1
1
[19] NPT
″ [31.7]CRBTMPWR004A00
4
4
/
″ [19] NPT
1
4
1
/
3
″
″
2
4
/
/
1
3
[19] NPT
[12.7] NPT
″
4
/
3
1
[44.5]
and 002A00 are for thru-the-curb connec-
tions. Packages CRBTMP003A00 and
6. Service clearance 4 ft on each side.
7.Direction of airflow.
004A00 are for thru-the-bottom connections.
8. Connector packages CRBTMPWR001A00
Fig. 1 — Roof Curb Details
DRAIN HOLE
1′-4″
[406]
″
16
/
11
[551]
1′-9
UNIT SIZEBC
50HJF004-007
48HJD004-007
NOTES:
disassembled.
1. Roof curb accessory is shipped
rest on curb).
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb (flanges of duct
2
MAXIMUM ALLOWABLE
DRAIN PLUG
CONDENSATE PAN (SIDE VIEW)
NOTE: Drain plug is shown in factory-installed position.
Fig. 3 — Condensate Drain Pan
DIFFERENCE (in.)
A-BB-CA-C
0.51.01.0
Fig. 2 — Unit Leveling Tolerances
Step 2 — Field Fabricate Ductwork —
Secure all
ducts to roof curb and building structure on vertical discharge
Do not connect ductwork to unit.
units.
For horizontal applications, field-supplied isolation flanges should be attached to horizontal discharge openings and all ductwork should be secured
to the flanges. Insulate and weatherproof all external ductwork,
joints, and roof openings with counter flashing and mastic in
accordance with applicable codes.
Ducts passing through an unconditioned space must be in-
sulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork.
Cabinet return-air static shall not exceed –.35 in. wg with
Durablade economizer, or –.30 in. wg with EconoMi$er, or
–.45 in. wg without economizer.
These units are designed for a minimum continuous returnair temperature in heating of 50 F (dry bulb), or an intermittent
operation down to 45 F (dry bulb), such a s when used with a
night setback thermostat.
Step 3 — Install External Trap for Condensate
Drain —
located on the bottom and side of the unit. Unit discharge
connections do not determine the use of drain connections;
either drain connection can be used with vertical or horizontal
applications.
When using the standard side drain connection, ensure the
plug (Red) in the alternate bottom connection is tight before installing the unit.
To use the bottom drai n connec tion for a roof curb i nstallation, relocate the factory-installed plug (Red) from the bottom
connection to the side connection. See Fig. 3. The piping for
the condensate drain and external trap can be completed after
the unit is in place.
All units must have an external trap for condensate drainage. Install a trap 4-in. deep and protect against freeze-up. If
drain line is installed downst ream from the ext ernal t rap, pitch
the line away from the unit at 1 in. per 10 ft of run. Do not use a
pipe size smaller than the unit connection (
Step 4 — Rig and Place Unit —
transportation damage, and file any claim w ith transportation
agency. Keep unit upright and do not drop. Spreader bars are
not required if top crating is left on unit, and rollers may be
used to move unit across a roof. Level by using unit frame as a
The unit’s 3/4-in. condensate drain connections are
3
/4 in.).
Inspect unit for
reference. See Table 1 and Fig. 4 for additional information.
Operating weight is shown in Table 1 and Fig. 4.
Lifting holes are provided in base rails as shown in Fig. 5.
Refer to rigging instructions on unit.
All panels must be in place when rigging and lifting.
POS ITION ING — Maintain cl earan ce around and a bove unit
to provide minimum distance from combustible materials, proper airflow, and service access. See Fig. 5. A properly positioned
unit will have the following clearances between unit and roof
1
/4-in. clearance between roof curb and base rails on each
curb;
side and duct end of unit;
1
/4 in. clearance between roof curb and
condenser coil end of unit. (See Fig. 1, section C-C.)
Do not install unit in an indoor location. Do not locate unit
air inlets near exhaust vents or other sources of contami nated
air.
Be sure that unit is installed such that snow will not block
the combustion intake or flue outlet.
Unit may be installed directly on wood flooring or on Class
A, B, or C roof-covering material when roof curb is used.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Locate mechanical draft system flue assembly at least 48 in.
from any opening through which combustion products could
enter the building, and at least 48 in. from an adjacent building.
When unit is located adjacent to public walkways, flue assembly must be at least 7 ft above grade.
NOTE: When unit is equipped with an accessory flue discharge deflector, allowable clearance is 18 inches.
Flue gas can deteriorate building materials. Orient unit such
that flue gas will not affect building materials.
Adequate combustion-air space must be provided for proper
operation of this equipment. Be sure that installation complies
with all local codes and Section 5.3, Air for Combustion and
Ventilation, NFGC (National Fuel Gas Code), ANSI (American National Standards Institute) Z223.1-1984 and addendum
Z223.1a-1987. In Canada, installation must be in ac cordance
with the CAN1.B149.1 and CAN1.B149.2 installation codes
for gas burning appliances.
Flue vent discharge must have a minimum horizontal clearance of 4 ft from electric and gas meters, gas regulators, and
gas relief equipment.
After unit is in position, remove shipping materials and rigging skids.
3
NOTES:
1. Place unit on curb as close as possible to the duct end.
2. Dimension in ( ) is in millimeters.
3. Hook rigging shackles through holes in base rail as shown in
detail ‘‘A.’’ Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.
4. Weights include base unit without economizer. See Table 1 for
unit operating weights with accessory economizer.
Flue hood is shipped
screwed to the burner compartment access panel. Remove
from shipping location and, using screws provided, install flue
hood in location shown in Fig. 5 and 6.
For units being installed in California Air Quality Manage-
ment Districts which require NO
emissions of 40 nanograms/
x
joule or less, kit CRLOWNOX001A00 must be installed.
Step 6 — Install Gas Piping —
Unit is equipped for
use with type of gas shown on nameplate. Refer to local
building codes, or in the absence of local codes, to
ANSI Z223.1-1984 and addendum Z223.1A-1987 entitled
National Fuel Gas Code. In Canada, installation must be in
accordance with the CAN1.B149.1 and CAN1.B149.2 installation codes for gas burning appliances.
For natural gas applications, gas pressure at unit gas c onnection must not be less than 4 in. wg or greater than 13 in. wg
while the unit is operating. On 48HJ005-007 high-heat units,
the gas pressure at unit gas connection must not be less than
5 in. wg or greater than 13 in. wg while the unit i s operating.
For propane applications, the gas pressure must not be less than
5 in. wg or greater than 13 in. wg at the unit connection.
Size gas supply piping for 0.5 in. wg maximum pressure
drop. Do not use supply pipe smaller than unit gas connection.
Support gas piping as shown in the table in Fig. 7. For example, a
3
/4-in. gas pipe must have one field-fabricated support
beam every 8 ft. Therefore, an 18-ft long gas pipe would have a
minimum of 3 support beams, and a 48-ft long pipe would
have a minimum of 6 support beams.
See Fig. 7 for typical pipe guide and locations of external
manual gas shutoff valve.
Step 7 — Make Electrical Connections
Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if
an electrical fault should occur. This ground may consist of
electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when
installed in accordance with NEC (National Electrical
Code), ANSI/NFPA (National Fire Protection Association), latest edition, and local electrical code s.
gas piping as an electrical ground.
Failure to fo llow this
warning could result in the installer being liable for personal injury of others.
FIELD PO WER S UPPLY — All units except 208/230-v
units are factory wired for the voltage shown on the nameplate.
If the 208/230-v unit is to be connected to a 208-v power supply, the transformer
must
be rewired by moving the black wire
from the 230-v terminal on the transformer and connecting it to
the 200-v terminal from the transformer.
Refer to unit label diagram for additional information.
Pigtails are provided for field service. Use factory-supplied
splices or UL (Underwriters’ Laboratories) approved copper
connector.
When installing units, provide a disconnect per NEC.
All field wiring must comply with NEC and local
requirements.
Do not use
4
Table 1 — Physical Data
BASE UNIT 48HJE/F/H/K/M/N004 HJD/E/F/G/H/K/L/M/N005 HJD/E/F/G/H/K/L/M/N006HJD/HJE/HJF007
NOMINAL CAPACITY
OPERATING WEIGHT (lb)
Unit
With Durablade Economizer
With EconoMi$er
With MoistureMiser Dehumidification Package
Roof Curb
COMPRESSOR
Quantity
Oil (oz)
REFRIGERANT TYPE
Operating Charge (lb-oz)
Standard Unit
Unit With MoistureMizer Dehumidification Package
CONDENSER FAN
Quantity...Diameter (in.)
Nominal Cfm
Motor Hp...Rpm
Watts Input (Total)
CONDENSER COIL
Standard Unit
Rows...Fins/in.
Total Face Area (sq ft)
Unit with MoistureMiser Dehumidification Package
Rows...Fins/in.
Total Face Area (sq ft)
EVAPORATOR FAN
Quantity...Size (in.)
Nominal Cfm
Maximum Continuous BhpStd
Motor Frame SizeStd
Fan Rpm RangeStd
Motor Bearing Type
Maximum Fan Rpm
Motor Pulley Pitch Diameter
A/B (in.)
Nominal Motor Shaft Diameter (in.)Std
Fan Pulley Pitch Diameter (in.)Std
Belt — Type...Length (in.)Std
Pulley Center Line Distance (in.)
Speed Change per Full Turn of
4. On vertical discharge units, ductwork to be attached to accessory roof curb only. For horizontal discharge units, field-supplied flanges should be attached to horizontal discharge openings, and all
ductwork should be attached to the flanges.
5. Minimum clearance (local codes or jurisdiction may prevail):
a. Between unit, flue side and combustible surfaces, 48 inches. (18 in. when using accessory flue
discharge deflector.)
b. Bottom of unit to combustible surfaces (when not using curb), 1 inch.
Bottom of base rail to combustible surfaces (when not using curb) 0 inches.
c. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side getting the greater
clearance is optional.
d. Overhead, 60 in. to assure proper condenser fan operation.
e. Between units, control box side, 42 in. per NEC (National Electrical Code).
f. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.
g. Between unit and block or concrete walls and other grounded surfaces, control box side, 42 in.
per NEC.
h. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser coil and combustion side as stated in notes
5a, b and c, a removable fence or barricade requires no clearance.
7. Units may be installed on combustible floors made from wood or Class A, B, or C roof covering
material if set on base rail.
8. The ver tical center of gravity is 1′-6″ [457] up from the bottom of the base rail.
[44.4]
Fig. 5 — Base Unit Dimensions — 48HJ004-007
7
Fig. 6 — Flue Hood Details
LEGEND
NFGC —
*Field supplied.
NOTE: Follow all local codes.
National Fuel Gas Code
SPACING OF SUPPORTS
STEEL PIPE
NOMINAL DIAMETER
1
1
/
4
(in.)
1
/
2
3
or 1
/
4
or larger
SPACING OF SUPPORTS
X DIMENSION
(ft)
6
8
10
Fig. 7 — Gas Piping Guide (With Accessory
Thru-the-Curb Service Connections)
Install conduit through side panel openings indicated in
Fig. 5. Route power lines through connector to terminal connections as shown in Fig. 8.
Voltage to compressor terminals during operation must be
within voltage range indicated on unit nameplate (also see
Tables 2A-2D). On 3-phase units, voltages between phases
must be balanced within 2% and the current within 10%. Use
the formula shown in Tables 2A-2D, Note 2 to determine the
percent voltage imbalance. Operation on improper line voltage
or excessive phase imbalance constitutes abuse and may cause
damage to electrical components. Such operation would invalidate any applicable Carrier warranty.
NOTE: If accessory thru-the-bottom connections and roof curb
are used, refer to the Thru-the-Bottom Accessory Installation
Instructions for information on power wiring and gas connection piping. The power wiring, control wiring and ga s piping
can be routed through field-drilled holes in the basepan. The
basepan is specially designed and dimpled for drilling the
access connection holes.
FIELD CONTR OL WIRING — Install a Carrier-approved
accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat
assembly on a solid wall in the conditioned space to sense average temperature in accordance with thermostat installation
instructions.
Route thermostat cable or equivalent single leads of colored
wire from subbase terminals through connector on unit to lowvoltage connections (shown in Fig. 9).
Connect thermostat wires to matching screw terminals of
low-voltage connection board. See Fig. 9.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft ,
use no. 16 AWG insulated wire (35 C minimum). For over
75 ft, use no. 14 AWG insulated wire (35 C minimum). All
wire larger than no. 18 AWG cannot be directl y connected to
the thermostat and will require a junction box and splice at the
thermostat.
Pass the control wires through the hole provided in the corner post; then feed wires through the raceway built into the corner post to the 24-v barrier located on the left side of the control
box. See Fig. 10. The raceway provides the UL required clearance between high- and low-voltage wiring.
HEAT ANTICIPATOR SETTINGS — Set heat anticipator settings at .14 amp for first stage and .14 for second stage heating,
when available.
Step 8 — Adjust Factory-Installed Options
MOISTUREMISER DEHUMIDIFICATION PACKAGE —
MoistureMiser package operation can be controlled by field
installation of a Carrier-approved humidistat (Fig. 11). To
install the humidistat:
1. Route humidistat cable through hole provided in unit corner post.
2. Feed wires through the raceway built into t he corner post
to the 24-v barrier located on the left side of the control
box. See Fig. 10. The raceway provides the UL-required
clearance between high- and low-voltage wiring.
3. Use a wire nut to connect humidistat cable into lowvoltage wiring as shown in Fig. 12.
APOLLO CONTROL — The optional Apollo control is used
to actively monitor all modes of operation as well as indoor
(evaporator) fan status, filter status, and indoor-air quality. The
Apollo control is designed to work with Carrier TEMP and
®
systems.
VVT
The thermostat must be wired to the Apollo Control before
starting the unit. Refer to the Apollo Control installation
instructions for information on installing the thermostat.
DISCONNECT SWITCH — The optional disconnect switch
is non-fused. The switch has the capability of being locked in
place for safety purposes.
8
RACEWAYLOW VOLTAGE
CONNECTIONS
INTEGRATED GAS UNIT
CONTROLLER (IGC)
HOLE IN END PANEL (HIDDEN)
LEGEND
C—
COMPS —
EQUIP—
GND—
IFC—
NEC—
TB—
Contactor
Compressors
Equipment
Ground
Indoor (Evaporator)
Fan Contactor
National Electrical Code
Terminal Block
LEGEND
AHA —
CC—
TC—
TH—
NOTE: Connect Y2 when unit is equipped with an integrated
economizer.
1. In compliance with NEC requirements for multimotor and combi-
2.
Full Load Amps
Heating, Air Conditioning and Refrigeration
Indoor (Evaporator) Fan Motor
Locked Rotor Amps
Minimum Circuit Amps
Maximum Overcurrent Protection
National Electrical Code
Outdoor (Condenser) Fan Motor
Rated Load Amps
Underwriters’ Laboratories
nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. UL, Canada units may be fuse or circuit breaker.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
1. In compliance with NEC requirements for multimotor and combi-
2.
Full Load Amps
Heating, Air Conditioning and Refrigeration
Indoor (Evaporator) Fan Motor
Locked Rotor Amps
Minimum Circuit Amps
Maximum Overcurrent Protection
National Electrical Code
Outdoor (Condenser) Fan Motor
Rated Load Amps
Underwriters’ Laboratories
nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. UL, Canada units may be fuse or circuit breaker.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance= 100 x
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
= 1.53%
POWER
SUPPLY
POWER
SUPPLY
7
457
452 + 464 + 455
1371
=
= 457
11
OPTIONAL DURABLADE ECONOMIZER — The option-
Fig. 11 — Accessory Field-Installed Humidistat
al economizer hood assembly is packaged and shipped in the
filter section. Damper blades and control boards are installed at
the factory and the economizer is shipped in the vertical discharge position.
NOTE: Horizontal discharge block-off plate is shipped with
the air hood package. If unit is to be used for vertical discharge
application, discard this plate.
Assembly:
1. Determine if ventilation air i s required in building. If so,
determine the minimum amount to be supplied by each
unit and record quantity of ventilation air needed for use
in Step 7.
2. Remove filter access panel by raising panel and swinging
panel outward. Panel is now disengaged from track and
can be removed. No tools are required to remove filter access panel. Remove outdoor-air opening panel. Save panels and screws. See Fig. 13. Remove economizer, and remove optional outdoor-air damper hood package from
filter section (located behind economizer).
3. Assemble outdoor-air hood top and side plates as shown
in Fig. 14. Install seal strips on hood top and sides. Put
aside screen retainer and retainer screw for later assem-
Do not attach hood to unit at this time.
bly .
4. Slide economizer i nto unit and secure with screws. See
Fig. 15.
NOTE: Be sure to engage rear economizer flange under
tabs in vertical return-air opening.
5. To convert to horizontal discharge application:
a. Rotate economizer 90 degrees until the econo-
mizer motor faces the condenser section (see
Fig. 16).
b. Remove tape and shipping screw, rotate the baro-
metric relief damper cover 90 degrees.
c. Install horizontal discharge block-off plate over
the opening on the access panel. (Block-off plate
MUST be installed before installing hood assembly.) See Fig. 17.
6. Remove 12-pin blue and yellow wir e jumper plug from
factory wiring harness and store. Insert economizer plug
into 12-pin plug of factory wiring harness. Remove tape
and shipping screw from barometric relief damper. See
Fig.18.
7. If ventilation air is not required, proceed to Step 8. If ventilation air is required, determine minimum position setting for required airflow. See Fig. 19. Adjust minimum
position setting by adjusting the screws on the position
setting bracket. Slide bracket until the top screw is in the
position determined by Fig. 19. Tighten screws.
8. Remove tape from outdoor-air thermostat (OAT). Fasten
OAT to inside of hood using screws and spee d clips provided. See Fig. 20. Make sure OAT terminals are positioned up.
MOISTUREMISER
% RELATIVE HUMIDITY
LEGEND
C—
CCH—
COMP —
FU—
HU—
IFM—
LLSV —
S-LPS —
TRAN —
Contactor (Compressor)
Crankcase Heater
Compressor
Fuse
Humidistat
Indoor (Evaporator) Fan Motor
Liquid Line Solenoid Valve
Low-Pressure Switch (Subcooler Only)
Transformer
Fac tory W irin g
Accessory or Optional Wiring
9. Replace outdoor-air opening panel using screws from
ECONOMIZER
CONTROL BOARD
ECONOMIZER
PLUG
ECONOMIZER
MOTOR
TOP
SCREW
SHIPPING
SCREW
ECONOMIZER
CONTROL
BOARD
BAROMETRIC
RELIEF
DAMPER
ECONOMIZER
PLUG
ECONOMIZER
MOTOR
BLOCK-OFF PLATE
Fig. 15 — Durablade Economizer Installed in Unit
Fig. 16 — Horizontal Durablade Economizer
Installation
Fig. 17 — Horizontal Discharge Block-Off Plate
Step 2. Replace filter a ccess panel. Ensure the filter ac cess panel slides along the tracks and is securely engaged.
10. Fasten hood top and side plate assembly (Fig. 14) to
outdoor-air opening panel with screws provided.
11. Place knob supplied with economizer on OAT. See
Fig. 20. Set for 3° F below indoor room thermostat setting. If accessory enthalpy control (EC) is used in place of
OAT, see instructions shipped with EC for installation
and adjustment. See Fig. 20.
12. Connect OAT per Fig. 21.
13. Slide outdoor-air inlet screen into screen track on hood
side plate. While holding screen in place, fasten screen retainer to hood using screws provided.
NOTE: Refer to Fig. 22 for economizer barometric relief
damper characteristics.
the EconoMi$er plug into the unit wiring harness. Refer
to wiring diagram Fig. 30 and 31. Also refer to Fig. 32 if
installing an accessory power exhaust.
9. Install the complete hood assembly on the unit and secure
using the screws provided.
10. Remove the indoor fan motor access panel. See Fig. 33.
11. Mount the supply-air temperature sensor to the lower left
portion of the indoor blower housing with the two
(2) screws provided (see Fig. 34). Connect the violet and
pink wires to the corresponding connections on the
supply-air temperature sensor. Replace the indoor fan
motor access panel.
0.00
200300400
100
CFM
Fig. 22 — Durablade Economizer Barometric
Relief Damper Characteristics
OPTIONAL ECONOMI$ER — See Fig. 23 for EconoMi$er
component locations.
1. To remove the existing unit filter access panel, raise the
panel and swing the bottom outward. The panel is now
disengaged from the track and can be removed. Remove
the indoor coil access panel and discard. See Fig. 24.
If installing an optional Power Exhaust Assembly, refer to
EconoMi$er Power Exhaust Installation Instructions.
the
Controller should be mounted in vertical position as
shown in Fig. 23.
2. Assemble the hood assembly as follows:
Remove the EconoMi$er hood from its packaging. Re-
move shipping brackets holding hood package to
EconoMi$er. Locate the outdoor-air opening panel. See
Fig. 25. Remove hood assembly shipping brackets located on the back (sloped) side of the EconoMi$er assembly.
These brackets are used to retain the hood assembly during shipping only .
1
3. Install the
/8 x 3/4-in. seal strip on the exhaust air hood
side panels and the bottom bracket. Assemble the exhaust
air hood to the outdoor-air opening panel as shown in
Fig. 25, using the screws provided.
assembly to unit at this time.
4. Ins tall the
1
/8 x 3/4 in. seal strip on the outdoor-air hood
top and side panels. Assemble the outdoor-air hood to the
outdoor-air opening panel as shown in Fig. 26, using the
screws provided.
Do not attach hood assembly to the unit
at this time.
5. Slide the outdoor-air inlet screens into the screen track on
the hood side panels. While holding the screens in pl ace,
fasten the screen retainer to the hood using the screws
provided. Repeat the process for the barometric exhaust
air screen.
sembly to unit a t this ti me.
6. Install the EconoMi$er assembly into the rooftop unit.
See Fig. 28 and 29.
NOTE: Be sure to engage rear EconoMi$er flange under
tabs in return-air opening of the unit base. See Fig. 28.
7. Install the outdoor-air block-off plate, then secure the
EconoMi$er with the screws provided. See Fig. 29.
Do not attach completed (Fig. 27) hood as-
8. Remove and discard the 12-pin jumper plug from the unit
wiring harness located int he upper left corner and insert
500600
Do not attach hood
700
800
15
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.