Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precautions in the li terature, ta gs and label s attached t o the uni t, and
other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
Before performing service or maintenance operations on
unit, turn off main power switch to unit and insta ll lockout
tag. Ensure electrical service to rooftop unit agrees with
voltage and amperage listed on the unit rating plate. Electrical shock could cause personal injury.
Disconnect gas piping from unit when leak
testing at pressure greater than 1/2 psig. Pressures greater than
damage resulting in hazardous condition. If
gas valve is subjected to pressure greater than
1
/
psig, it
2
pressure testing field-supplied gas piping at
pressures of
to such piping must be isolated by manually
closing the gas valve(s).
1
/2 psig will cause gas valve
must
be replaced before use. When
1
/2 psig or less, a unit connected
INSTALLATION
Unit is shipped in the vertical discharge configuration. To
convert to horizontal discharge application, remove duct opening covers. Using the same screws, install covers on duct openings in basepan of unit with insulation-side down. Seals around
openings must be tight.
NOTE: Any combination of supply and return ducting is permissible, i.e., vertical supply combined with horizontal return.
Step 1 — Provide Unit Support
ROO F CU R B — Assemble and instal l acces sory roof curb in
accordance with instructions shipped with curb. See Fig. 1. Install insulation, cant strips, roofing felt, and counter flashing as
shown.
If electric control power or gas service is to be routed through
the basepan, attach the accessory thru-the-bottom service connections to the basepan in accordance with the accessory installation instructions. Connections must be installed before unit is
set on roof curb.
Fig. 2. This is necessary for unit drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
SLAB MOUNT (Horizontal Units Only) — Provide a level
concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of condenser-coil air inlet to
prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
Ductwork must be attached to curb, not to the unit.
IMPORTANT: The gasketing of th e unit to the roof curb
is critical for a watertight seal. Install gasket supplied
with the roof curb as shown in Fig. 1. Improperly
applied gasket can result in air leaks and poor unit
performance.
Curb should be level. Unit leveling tolerances a re shown in
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Ta b 1 a 6 a
PC 111Catalog No. 534-767Printed in U.S.A.Form 48HJ-18SIPg 19-00Replaces: 48HJ-17SI
Page 2
48/50HJ
UNIT SIZE
“A”
ROOF CURB
ACCESSORY
004-007
CRRFCURB001A00 1′-2″ [356]
CRRFCURB002A00 2′-0″ [610]
CONNECTOR
“G”
“F”
“E”
D ALT
PKG. ACCY.
CRBTMPWR001A00
CRBTMPWR003A00
″
″
2
2
/
/
1
1
[12.7] NPT
CONTROL
″ [19] NPT
POWER
4
/
3
″
4
/
3
GAS
[12.7] NPT
″ [31.7]CRBTMPWR002A00
/
1
1
[19] NPT
″ [31.7]CRBTMPWR004A00
4
4
/
″ [19] NPT
1
4
1
/
3
″
″
2
4
/
/
1
3
[19] NPT
[12.7] NPT
″
4
/
3
1
[44.5]
and 002A00 are for thru-the-curb connec-
tions. Packages CRBTMP003A00 and
6. Service clearance 4 ft on each side.
7.Direction of airflow.
004A00 are for thru-the-bottom connections.
8. Connector packages CRBTMPWR001A00
Fig. 1 — Roof Curb Details
DRAIN HOLE
1′-4″
[406]
″
16
/
11
[551]
1′-9
UNIT SIZEBC
50HJF004-007
48HJD004-007
NOTES:
disassembled.
1. Roof curb accessory is shipped
rest on curb).
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb (flanges of duct
2
Page 3
MAXIMUM ALLOWABLE
DRAIN PLUG
CONDENSATE PAN (SIDE VIEW)
NOTE: Drain plug is shown in factory-installed position.
Fig. 3 — Condensate Drain Pan
DIFFERENCE (in.)
A-BB-CA-C
0.51.01.0
Fig. 2 — Unit Leveling Tolerances
Step 2 — Field Fabricate Ductwork —
Secure all
ducts to roof curb and building structure on vertical discharge
Do not connect ductwork to unit.
units.
For horizontal applications, field-supplied isolation flanges should be attached to horizontal discharge openings and all ductwork should be secured
to the flanges. Insulate and weatherproof all external ductwork,
joints, and roof openings with counter flashing and mastic in
accordance with applicable codes.
Ducts passing through an unconditioned space must be in-
sulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork.
Cabinet return-air static shall not exceed –.35 in. wg with
Durablade economizer, or –.30 in. wg with EconoMi$er, or
–.45 in. wg without economizer.
These units are designed for a minimum continuous returnair temperature in heating of 50 F (dry bulb), or an intermittent
operation down to 45 F (dry bulb), such a s when used with a
night setback thermostat.
Step 3 — Install External Trap for Condensate
Drain —
located on the bottom and side of the unit. Unit discharge
connections do not determine the use of drain connections;
either drain connection can be used with vertical or horizontal
applications.
When using the standard side drain connection, ensure the
plug (Red) in the alternate bottom connection is tight before installing the unit.
To use the bottom drai n connec tion for a roof curb i nstallation, relocate the factory-installed plug (Red) from the bottom
connection to the side connection. See Fig. 3. The piping for
the condensate drain and external trap can be completed after
the unit is in place.
All units must have an external trap for condensate drainage. Install a trap 4-in. deep and protect against freeze-up. If
drain line is installed downst ream from the ext ernal t rap, pitch
the line away from the unit at 1 in. per 10 ft of run. Do not use a
pipe size smaller than the unit connection (
Step 4 — Rig and Place Unit —
transportation damage, and file any claim w ith transportation
agency. Keep unit upright and do not drop. Spreader bars are
not required if top crating is left on unit, and rollers may be
used to move unit across a roof. Level by using unit frame as a
The unit’s 3/4-in. condensate drain connections are
3
/4 in.).
Inspect unit for
reference. See Table 1 and Fig. 4 for additional information.
Operating weight is shown in Table 1 and Fig. 4.
Lifting holes are provided in base rails as shown in Fig. 5.
Refer to rigging instructions on unit.
All panels must be in place when rigging and lifting.
POS ITION ING — Maintain cl earan ce around and a bove unit
to provide minimum distance from combustible materials, proper airflow, and service access. See Fig. 5. A properly positioned
unit will have the following clearances between unit and roof
1
/4-in. clearance between roof curb and base rails on each
curb;
side and duct end of unit;
1
/4 in. clearance between roof curb and
condenser coil end of unit. (See Fig. 1, section C-C.)
Do not install unit in an indoor location. Do not locate unit
air inlets near exhaust vents or other sources of contami nated
air.
Be sure that unit is installed such that snow will not block
the combustion intake or flue outlet.
Unit may be installed directly on wood flooring or on Class
A, B, or C roof-covering material when roof curb is used.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Locate mechanical draft system flue assembly at least 48 in.
from any opening through which combustion products could
enter the building, and at least 48 in. from an adjacent building.
When unit is located adjacent to public walkways, flue assembly must be at least 7 ft above grade.
NOTE: When unit is equipped with an accessory flue discharge deflector, allowable clearance is 18 inches.
Flue gas can deteriorate building materials. Orient unit such
that flue gas will not affect building materials.
Adequate combustion-air space must be provided for proper
operation of this equipment. Be sure that installation complies
with all local codes and Section 5.3, Air for Combustion and
Ventilation, NFGC (National Fuel Gas Code), ANSI (American National Standards Institute) Z223.1-1984 and addendum
Z223.1a-1987. In Canada, installation must be in ac cordance
with the CAN1.B149.1 and CAN1.B149.2 installation codes
for gas burning appliances.
Flue vent discharge must have a minimum horizontal clearance of 4 ft from electric and gas meters, gas regulators, and
gas relief equipment.
After unit is in position, remove shipping materials and rigging skids.
3
Page 4
NOTES:
1. Place unit on curb as close as possible to the duct end.
2. Dimension in ( ) is in millimeters.
3. Hook rigging shackles through holes in base rail as shown in
detail ‘‘A.’’ Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.
4. Weights include base unit without economizer. See Table 1 for
unit operating weights with accessory economizer.
Flue hood is shipped
screwed to the burner compartment access panel. Remove
from shipping location and, using screws provided, install flue
hood in location shown in Fig. 5 and 6.
For units being installed in California Air Quality Manage-
ment Districts which require NO
emissions of 40 nanograms/
x
joule or less, kit CRLOWNOX001A00 must be installed.
Step 6 — Install Gas Piping —
Unit is equipped for
use with type of gas shown on nameplate. Refer to local
building codes, or in the absence of local codes, to
ANSI Z223.1-1984 and addendum Z223.1A-1987 entitled
National Fuel Gas Code. In Canada, installation must be in
accordance with the CAN1.B149.1 and CAN1.B149.2 installation codes for gas burning appliances.
For natural gas applications, gas pressure at unit gas c onnection must not be less than 4 in. wg or greater than 13 in. wg
while the unit is operating. On 48HJ005-007 high-heat units,
the gas pressure at unit gas connection must not be less than
5 in. wg or greater than 13 in. wg while the unit i s operating.
For propane applications, the gas pressure must not be less than
5 in. wg or greater than 13 in. wg at the unit connection.
Size gas supply piping for 0.5 in. wg maximum pressure
drop. Do not use supply pipe smaller than unit gas connection.
Support gas piping as shown in the table in Fig. 7. For example, a
3
/4-in. gas pipe must have one field-fabricated support
beam every 8 ft. Therefore, an 18-ft long gas pipe would have a
minimum of 3 support beams, and a 48-ft long pipe would
have a minimum of 6 support beams.
See Fig. 7 for typical pipe guide and locations of external
manual gas shutoff valve.
Step 7 — Make Electrical Connections
Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if
an electrical fault should occur. This ground may consist of
electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when
installed in accordance with NEC (National Electrical
Code), ANSI/NFPA (National Fire Protection Association), latest edition, and local electrical code s.
gas piping as an electrical ground.
Failure to fo llow this
warning could result in the installer being liable for personal injury of others.
FIELD PO WER S UPPLY — All units except 208/230-v
units are factory wired for the voltage shown on the nameplate.
If the 208/230-v unit is to be connected to a 208-v power supply, the transformer
must
be rewired by moving the black wire
from the 230-v terminal on the transformer and connecting it to
the 200-v terminal from the transformer.
Refer to unit label diagram for additional information.
Pigtails are provided for field service. Use factory-supplied
splices or UL (Underwriters’ Laboratories) approved copper
connector.
When installing units, provide a disconnect per NEC.
All field wiring must comply with NEC and local
requirements.
Do not use
4
Page 5
Table 1 — Physical Data
BASE UNIT 48HJE/F/H/K/M/N004 HJD/E/F/G/H/K/L/M/N005 HJD/E/F/G/H/K/L/M/N006HJD/HJE/HJF007
NOMINAL CAPACITY
OPERATING WEIGHT (lb)
Unit
With Durablade Economizer
With EconoMi$er
With MoistureMiser Dehumidification Package
Roof Curb
COMPRESSOR
Quantity
Oil (oz)
REFRIGERANT TYPE
Operating Charge (lb-oz)
Standard Unit
Unit With MoistureMizer Dehumidification Package
CONDENSER FAN
Quantity...Diameter (in.)
Nominal Cfm
Motor Hp...Rpm
Watts Input (Total)
CONDENSER COIL
Standard Unit
Rows...Fins/in.
Total Face Area (sq ft)
Unit with MoistureMiser Dehumidification Package
Rows...Fins/in.
Total Face Area (sq ft)
EVAPORATOR FAN
Quantity...Size (in.)
Nominal Cfm
Maximum Continuous BhpStd
Motor Frame SizeStd
Fan Rpm RangeStd
Motor Bearing Type
Maximum Fan Rpm
Motor Pulley Pitch Diameter
A/B (in.)
Nominal Motor Shaft Diameter (in.)Std
Fan Pulley Pitch Diameter (in.)Std
Belt — Type...Length (in.)Std
Pulley Center Line Distance (in.)
Speed Change per Full Turn of
4. On vertical discharge units, ductwork to be attached to accessory roof curb only. For horizontal discharge units, field-supplied flanges should be attached to horizontal discharge openings, and all
ductwork should be attached to the flanges.
5. Minimum clearance (local codes or jurisdiction may prevail):
a. Between unit, flue side and combustible surfaces, 48 inches. (18 in. when using accessory flue
discharge deflector.)
b. Bottom of unit to combustible surfaces (when not using curb), 1 inch.
Bottom of base rail to combustible surfaces (when not using curb) 0 inches.
c. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side getting the greater
clearance is optional.
d. Overhead, 60 in. to assure proper condenser fan operation.
e. Between units, control box side, 42 in. per NEC (National Electrical Code).
f. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.
g. Between unit and block or concrete walls and other grounded surfaces, control box side, 42 in.
per NEC.
h. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser coil and combustion side as stated in notes
5a, b and c, a removable fence or barricade requires no clearance.
7. Units may be installed on combustible floors made from wood or Class A, B, or C roof covering
material if set on base rail.
8. The ver tical center of gravity is 1′-6″ [457] up from the bottom of the base rail.
[44.4]
Fig. 5 — Base Unit Dimensions — 48HJ004-007
7
Page 8
Fig. 6 — Flue Hood Details
LEGEND
NFGC —
*Field supplied.
NOTE: Follow all local codes.
National Fuel Gas Code
SPACING OF SUPPORTS
STEEL PIPE
NOMINAL DIAMETER
1
1
/
4
(in.)
1
/
2
3
or 1
/
4
or larger
SPACING OF SUPPORTS
X DIMENSION
(ft)
6
8
10
Fig. 7 — Gas Piping Guide (With Accessory
Thru-the-Curb Service Connections)
Install conduit through side panel openings indicated in
Fig. 5. Route power lines through connector to terminal connections as shown in Fig. 8.
Voltage to compressor terminals during operation must be
within voltage range indicated on unit nameplate (also see
Tables 2A-2D). On 3-phase units, voltages between phases
must be balanced within 2% and the current within 10%. Use
the formula shown in Tables 2A-2D, Note 2 to determine the
percent voltage imbalance. Operation on improper line voltage
or excessive phase imbalance constitutes abuse and may cause
damage to electrical components. Such operation would invalidate any applicable Carrier warranty.
NOTE: If accessory thru-the-bottom connections and roof curb
are used, refer to the Thru-the-Bottom Accessory Installation
Instructions for information on power wiring and gas connection piping. The power wiring, control wiring and ga s piping
can be routed through field-drilled holes in the basepan. The
basepan is specially designed and dimpled for drilling the
access connection holes.
FIELD CONTR OL WIRING — Install a Carrier-approved
accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat
assembly on a solid wall in the conditioned space to sense average temperature in accordance with thermostat installation
instructions.
Route thermostat cable or equivalent single leads of colored
wire from subbase terminals through connector on unit to lowvoltage connections (shown in Fig. 9).
Connect thermostat wires to matching screw terminals of
low-voltage connection board. See Fig. 9.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft ,
use no. 16 AWG insulated wire (35 C minimum). For over
75 ft, use no. 14 AWG insulated wire (35 C minimum). All
wire larger than no. 18 AWG cannot be directl y connected to
the thermostat and will require a junction box and splice at the
thermostat.
Pass the control wires through the hole provided in the corner post; then feed wires through the raceway built into the corner post to the 24-v barrier located on the left side of the control
box. See Fig. 10. The raceway provides the UL required clearance between high- and low-voltage wiring.
HEAT ANTICIPATOR SETTINGS — Set heat anticipator settings at .14 amp for first stage and .14 for second stage heating,
when available.
Step 8 — Adjust Factory-Installed Options
MOISTUREMISER DEHUMIDIFICATION PACKAGE —
MoistureMiser package operation can be controlled by field
installation of a Carrier-approved humidistat (Fig. 11). To
install the humidistat:
1. Route humidistat cable through hole provided in unit corner post.
2. Feed wires through the raceway built into t he corner post
to the 24-v barrier located on the left side of the control
box. See Fig. 10. The raceway provides the UL-required
clearance between high- and low-voltage wiring.
3. Use a wire nut to connect humidistat cable into lowvoltage wiring as shown in Fig. 12.
APOLLO CONTROL — The optional Apollo control is used
to actively monitor all modes of operation as well as indoor
(evaporator) fan status, filter status, and indoor-air quality. The
Apollo control is designed to work with Carrier TEMP and
®
systems.
VVT
The thermostat must be wired to the Apollo Control before
starting the unit. Refer to the Apollo Control installation
instructions for information on installing the thermostat.
DISCONNECT SWITCH — The optional disconnect switch
is non-fused. The switch has the capability of being locked in
place for safety purposes.
8
Page 9
RACEWAYLOW VOLTAGE
CONNECTIONS
INTEGRATED GAS UNIT
CONTROLLER (IGC)
HOLE IN END PANEL (HIDDEN)
LEGEND
C—
COMPS —
EQUIP—
GND—
IFC—
NEC—
TB—
Contactor
Compressors
Equipment
Ground
Indoor (Evaporator)
Fan Contactor
National Electrical Code
Terminal Block
LEGEND
AHA —
CC—
TC—
TH—
NOTE: Connect Y2 when unit is equipped with an integrated
economizer.
1. In compliance with NEC requirements for multimotor and combi-
2.
Full Load Amps
Heating, Air Conditioning and Refrigeration
Indoor (Evaporator) Fan Motor
Locked Rotor Amps
Minimum Circuit Amps
Maximum Overcurrent Protection
National Electrical Code
Outdoor (Condenser) Fan Motor
Rated Load Amps
Underwriters’ Laboratories
nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. UL, Canada units may be fuse or circuit breaker.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
1. In compliance with NEC requirements for multimotor and combi-
2.
Full Load Amps
Heating, Air Conditioning and Refrigeration
Indoor (Evaporator) Fan Motor
Locked Rotor Amps
Minimum Circuit Amps
Maximum Overcurrent Protection
National Electrical Code
Outdoor (Condenser) Fan Motor
Rated Load Amps
Underwriters’ Laboratories
nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. UL, Canada units may be fuse or circuit breaker.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance= 100 x
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
= 1.53%
POWER
SUPPLY
POWER
SUPPLY
7
457
452 + 464 + 455
1371
=
= 457
11
Page 12
OPTIONAL DURABLADE ECONOMIZER — The option-
Fig. 11 — Accessory Field-Installed Humidistat
al economizer hood assembly is packaged and shipped in the
filter section. Damper blades and control boards are installed at
the factory and the economizer is shipped in the vertical discharge position.
NOTE: Horizontal discharge block-off plate is shipped with
the air hood package. If unit is to be used for vertical discharge
application, discard this plate.
Assembly:
1. Determine if ventilation air i s required in building. If so,
determine the minimum amount to be supplied by each
unit and record quantity of ventilation air needed for use
in Step 7.
2. Remove filter access panel by raising panel and swinging
panel outward. Panel is now disengaged from track and
can be removed. No tools are required to remove filter access panel. Remove outdoor-air opening panel. Save panels and screws. See Fig. 13. Remove economizer, and remove optional outdoor-air damper hood package from
filter section (located behind economizer).
3. Assemble outdoor-air hood top and side plates as shown
in Fig. 14. Install seal strips on hood top and sides. Put
aside screen retainer and retainer screw for later assem-
Do not attach hood to unit at this time.
bly .
4. Slide economizer i nto unit and secure with screws. See
Fig. 15.
NOTE: Be sure to engage rear economizer flange under
tabs in vertical return-air opening.
5. To convert to horizontal discharge application:
a. Rotate economizer 90 degrees until the econo-
mizer motor faces the condenser section (see
Fig. 16).
b. Remove tape and shipping screw, rotate the baro-
metric relief damper cover 90 degrees.
c. Install horizontal discharge block-off plate over
the opening on the access panel. (Block-off plate
MUST be installed before installing hood assembly.) See Fig. 17.
6. Remove 12-pin blue and yellow wir e jumper plug from
factory wiring harness and store. Insert economizer plug
into 12-pin plug of factory wiring harness. Remove tape
and shipping screw from barometric relief damper. See
Fig.18.
7. If ventilation air is not required, proceed to Step 8. If ventilation air is required, determine minimum position setting for required airflow. See Fig. 19. Adjust minimum
position setting by adjusting the screws on the position
setting bracket. Slide bracket until the top screw is in the
position determined by Fig. 19. Tighten screws.
8. Remove tape from outdoor-air thermostat (OAT). Fasten
OAT to inside of hood using screws and spee d clips provided. See Fig. 20. Make sure OAT terminals are positioned up.
MOISTUREMISER
% RELATIVE HUMIDITY
LEGEND
C—
CCH—
COMP —
FU—
HU—
IFM—
LLSV —
S-LPS —
TRAN —
Contactor (Compressor)
Crankcase Heater
Compressor
Fuse
Humidistat
Indoor (Evaporator) Fan Motor
Liquid Line Solenoid Valve
Low-Pressure Switch (Subcooler Only)
Transformer
Fac tory W irin g
Accessory or Optional Wiring
9. Replace outdoor-air opening panel using screws from
ECONOMIZER
CONTROL BOARD
ECONOMIZER
PLUG
ECONOMIZER
MOTOR
TOP
SCREW
SHIPPING
SCREW
ECONOMIZER
CONTROL
BOARD
BAROMETRIC
RELIEF
DAMPER
ECONOMIZER
PLUG
ECONOMIZER
MOTOR
BLOCK-OFF PLATE
Fig. 15 — Durablade Economizer Installed in Unit
Fig. 16 — Horizontal Durablade Economizer
Installation
Fig. 17 — Horizontal Discharge Block-Off Plate
Step 2. Replace filter a ccess panel. Ensure the filter ac cess panel slides along the tracks and is securely engaged.
10. Fasten hood top and side plate assembly (Fig. 14) to
outdoor-air opening panel with screws provided.
11. Place knob supplied with economizer on OAT. See
Fig. 20. Set for 3° F below indoor room thermostat setting. If accessory enthalpy control (EC) is used in place of
OAT, see instructions shipped with EC for installation
and adjustment. See Fig. 20.
12. Connect OAT per Fig. 21.
13. Slide outdoor-air inlet screen into screen track on hood
side plate. While holding screen in place, fasten screen retainer to hood using screws provided.
NOTE: Refer to Fig. 22 for economizer barometric relief
damper characteristics.
the EconoMi$er plug into the unit wiring harness. Refer
to wiring diagram Fig. 30 and 31. Also refer to Fig. 32 if
installing an accessory power exhaust.
9. Install the complete hood assembly on the unit and secure
using the screws provided.
10. Remove the indoor fan motor access panel. See Fig. 33.
11. Mount the supply-air temperature sensor to the lower left
portion of the indoor blower housing with the two
(2) screws provided (see Fig. 34). Connect the violet and
pink wires to the corresponding connections on the
supply-air temperature sensor. Replace the indoor fan
motor access panel.
0.00
200300400
100
CFM
Fig. 22 — Durablade Economizer Barometric
Relief Damper Characteristics
OPTIONAL ECONOMI$ER — See Fig. 23 for EconoMi$er
component locations.
1. To remove the existing unit filter access panel, raise the
panel and swing the bottom outward. The panel is now
disengaged from the track and can be removed. Remove
the indoor coil access panel and discard. See Fig. 24.
If installing an optional Power Exhaust Assembly, refer to
EconoMi$er Power Exhaust Installation Instructions.
the
Controller should be mounted in vertical position as
shown in Fig. 23.
2. Assemble the hood assembly as follows:
Remove the EconoMi$er hood from its packaging. Re-
move shipping brackets holding hood package to
EconoMi$er. Locate the outdoor-air opening panel. See
Fig. 25. Remove hood assembly shipping brackets located on the back (sloped) side of the EconoMi$er assembly.
These brackets are used to retain the hood assembly during shipping only .
1
3. Install the
/8 x 3/4-in. seal strip on the exhaust air hood
side panels and the bottom bracket. Assemble the exhaust
air hood to the outdoor-air opening panel as shown in
Fig. 25, using the screws provided.
assembly to unit at this time.
4. Ins tall the
1
/8 x 3/4 in. seal strip on the outdoor-air hood
top and side panels. Assemble the outdoor-air hood to the
outdoor-air opening panel as shown in Fig. 26, using the
screws provided.
Do not attach hood assembly to the unit
at this time.
5. Slide the outdoor-air inlet screens into the screen track on
the hood side panels. While holding the screens in pl ace,
fasten the screen retainer to the hood using the screws
provided. Repeat the process for the barometric exhaust
air screen.
sembly to unit a t this ti me.
6. Install the EconoMi$er assembly into the rooftop unit.
See Fig. 28 and 29.
NOTE: Be sure to engage rear EconoMi$er flange under
tabs in return-air opening of the unit base. See Fig. 28.
7. Install the outdoor-air block-off plate, then secure the
EconoMi$er with the screws provided. See Fig. 29.
Do not attach completed (Fig. 27) hood as-
8. Remove and discard the 12-pin jumper plug from the unit
wiring harness located int he upper left corner and insert
500600
Do not attach hood
700
800
15
Page 16
OUTDOOR AIR
WIRING
HARNESS
OUTDOOR
AIR
BLOCK-OFF
PLATE
OPENING
PANEL
SEAL STRIP
OUTDOOR AIR
HOOD TOP
UNIT FILTER
RACK
ECONOMIZER CLIP
HVAC UNIT
SCREEN
RETAINER
SEAL STRIP
ASSEMBLED
EXHAUST HOOD
OUTDOOR AIR
HOOD SIDES
Fig. 26 — Outdoor-Air Hood Assembly
Fig. 27 — Completed Hood Assembly
OUTDOOR AIR
INLET
SCREENS
UNIT BASE
ECONOMIZER
ECONOMIZER REAR
FLANGE
Fig. 28 — Rear EconoMi$er Flange Installation
Fig. 29 — EconoMi$er Installed
OAT —
LEGEND
Outdoor-Air Thermostat
Fig. 30 — EconoMi$er Wiring
16
Page 17
ECONOMI$ER
FAN 1
FAN 2
CAPACITOR 2
CAPACITOR 1
RELAY 2
RELAY 1
4-PIN
CONNECTOR PLUG
(HIGH VOLTAGE)
3-PIN
CONNECTOR PLUG
(LOW VOLTAGE)
CONTROLLER
OAT
COM
OAH
-15 V
RAT
COM
RAH
+15 V
(+)
CO
2
COM
CO
2
DAT
COM
REM POT
COM
LED
COM
BROWN
VIOLET
WHITE
RED
BROWN
VIOLET
WHITE
RED
CO
SUPPLY AIR
TEMPERATURE SENSOR
PINK
VIOLET
TEMP
TEMP
TEMP
TEMP
COM
OUT
PWR
TEMP
TEMP
COM
OUT
PWR
SENSOR
2
24
V+
COM VAC
Fig. 31 — EconoMi$er Sensor Wiring
POWER EXHAUST SYSTEM (HIGH VOLTAGE)
OUTDOOR
AIR
SENSOR
RETURN
AIR
SENSOR
CONTROL BOX/BURNER
ACCESS PANEL
INDOOR FAN MOTOR
ACCESS PANEL AND BLOWER
Fig. 33 — Typical Access Panel Locations
(Standard Efficiency Unit Shown)
RED
H1
(575 VAC)
HT01AH859
X4
SECONDARY
HANDY BOX
X2
230VAC
2 x 4 IN.
X3
TO FUSED
DISCONNECT
GRAY
H2
X1
OR
BLACK L1
BLUE L2
GREEN GND
RED YELH1BLU
(460 VAC)
HT01AH850
X4
SECONDARY
COMPRESSOR 1
CONTACTOR
112 1
23
13
CONNECTOR
L1
1
1
L2
22
GND
33
44
230 VAC
1 PHASE
H3
H2
X3
X2
230VAC
230VAC
4-PIN
PLUG
GREEN
GRAY
H4
X1
BLACK
BLUE
FIELD SUPPLIED
WIRING
BROWN
C1
GREEN/
YELLOW
BROWN
C1
GREEN/
YELLOW
FAN 1
FAN 2
BLACK
BLACK
LT. BLUE
BLACK
BLUE
BLACK
LT. BLUE
BLACK
3
2
1
3
2
1
6
5
4
5
BLUE
B
9
8
7
9
6
8
4
7
R1
24 VAC
A
B
R2
24 VAC
A
3-PIN
CONNECTOR
PLUG
ORANGE
YELLOW
BROWN
1
2
3
Fig. 32 — Wiring Diagram for Power Exhaust System
17
Page 18
SUPPLY AIR
Fig. 35 — EconoMi$er Control Adjustment
Potentiometers (Factory Settings)
Fig. 36 — Barometric Relief Capacity
TEMPERATURE
SENSOR
MOUNTING
LOCATION
SUPPLY AIR
TEMPERATURE
SENSOR
Fig. 34 — Supply-Air Sensor Placement
CO
Control Setup — If a CO2 sensor is not being used, pro-
2
ceed to the next section. If a CO
sensor is being used, perform
2
the following:
1. Determine the value at which you want the minimum position of the dampers to begin opening to allow a greater
amount of outdoor air to enter. The range is 800 to
1,400 ppm.
2. Locate the CO
SP (PPM) potentiometer and adjust to the
2
desired set point. See Fig. 35.
Mechanical Cooling Lockout
— Determine the outdoor-air
temperature at which you want the mechanical cooling (compressors) to be disabled. Locate the mechanical cooling lockout
(MECH CLG LOCKOUT) potentiometer. To disable this feature, turn the potentiometer counterclockwise (CCW) to the
OFF position. Otherwise, set the value between 10 and 60 F.
Mechanical cooling will not operate when the outdoor air
temperature is below this value. See Fig. 35.
Dry Bulb Cha ngeover Set Up
— Determine the dry bulb
changeover set point from T able 3. The settings are A, B, C and
D. Locate the ECON SP potentiometer and set the dry bulb
changeover set point. See Fig. 35. When the OAT is above this
set point, the damper is limited to minimum position setting.
Ventilation Air (Minimum Position Set Up)
— If ventilation
air is not required, proceed to Step 5. If ventilation air is required, perform the following:
1. The indoor fan must be on to set the ventilation air. Either
put the thermostat in the continuous fan mode or jump er
the R and G terminals at the rooftop unit connection
board.
2. Locate the minimum position (MIN POS) potentiometer.
Turn the potentiometer full CCW to fully close the outdoor air dampers. Turn the potentiometer gradually
clockwise (CW) to the desired position. See Fig. 35.
3. Replace the filter access panel. See Fig. 24. Ensure the filter access panel slides along the tracks and is securely
engaged.
4. Calculate the minimum airflow across the EconoMi$er.
a. Calculate % of outside air using the following
formula.
% Outdoor air through EconoMi$er
Mixture Temp –
% Outdoor air =
Return Air Temp
Outdoor T emp –
Return Air Temp
b. Divide total CFM by percentage outdoor air, this
gives outdoor air vol ume in CFM.
5. Turn on base unit power.
NOTE: The EconoMi$er begins operation three mi nutes after
power up.
Personal Injury Hazard.
Avoid possible injury by keep-
ing fingers away from damper blades.
6. See Fig. 36 for b arome tric reli ef d amper cha ract eristi cs.
Table 3 — Changeover Set Points
SETTINGSABCD
Dry Bulb (°F)
Single Enthalpy* (Btu/lb)
Differential Temperature* (°F, Not Adjustable)
Differential Enthalpy* (Btu/lb, Not Adjustable)
*Field-installed accessory.
73 69 66 63
27 25 24 22
2222
1111
If a potentiometer fails, its setting will default to the values
in Ta ble 4.
Table 4 — Default Potentiometer Settings
POTENTIOMETERDEFAULT SETTING
SP (PPM)
CO
2
MECH CLG LOCKOUT
ECON SP
MIN POS (%)
1,000
47°
D
20
0.5
0.4
0.3
0.2
0.1
STATIC PRESSURE (IN.WG)
0
0
400
FLOW (CUBIC FEET/MINUTE)
800
1200
1600
2000
2400
18
Page 19
Step 9 — Adjust Evaporator-Fan Speed —
MOTOR MOUNTING
PLATE NUTS
Fig. 37 — Belt-Drive Motor Mounting
Fig. 38 — Evaporator-Fan Pulley Adjustment
just evaporator-fan speed to meet jobsite conditions.
Tables 5A and 5B show fan rpm at motor pulley settings.
Tables 6 and 7 show maximum amp draw of belt-drive motor.
Table 8 shows motor nominal horsepower for eva porator-fan
motors. Refer to Tables 8-25 for performance data. See Tables
26 and 27 for accessory and option static pressure drops.
BELT-DRIVE MOTORS — Fan motor pulleys are factory set
for speed shown in Table 1. Check pulley alignment and belt
tension prior to start-up.
NOTE: Before adjusting fan speed, make sure the new fan
speed will provide an air temperature rise range as shown in
T able 1.
T o change fan speed:
1. Shut off unit power supply, tag disconnect.
2. Loosen belt by loosening fan motor mounting nuts. See
Fig. 37.
3. Loosen movable pulley flange setscrew (see Fig. 38).
4. Screw movable flange toward fixed flange to increase
speed and away from fixed flange to decrease speed. Increasing fan speed increases load on motor. Do not exceed maximum speed specified in Table 1.
5. Set movable flange at nearest keyway of pulley hub and
tighten setscrew. (See Table 1 for speed change for ea ch
full turn of pulley flange.)
To align fan and motor pulleys, loosen fan pulley setscrews
and slide fan pulley along fan shaft. Make an gular alignment
by loosening motor from mounting.
T o adjust belt tension:
1. Loosen fan motor mounting nuts.
2. Slide motor mounting plate away from fan scroll for
proper belt tension (1/2-in. deflection with 8 to 10 lbs of
force) and tighten mounting nuts.
3. Adjust lock bolt and nut on mounting plate to secure motor in fixed position.
Ad-
19
Page 20
Table 5A — 48HJ Fan Rpm at Motor Pulley Setting With Standard Motor
Table 6 — Evaporator-Fan Motor Data — Standard Motor
UNIT
48HJ
004
005
006
007
Bhp —
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
Single1.201000208/2305.4
Three1.201000
Single1.201000208/2305.4
Three1.201000
Single1.301650208/2309.7
Three2.402120
Three2.402120
LEGEND
Brake Horsepower
1
/
22
2
1
/
2
MOTOR PULLEY TURNS OPEN
MOTOR PULLEY TURNS OPEN
22
1
/
2
33
MAXIMUM
OPERATING WATTS*
*Extensive motor and electrical testing on these units ensures that
the full horsepower and watts range of the motors can be utilized
with confidence. Using your fan motors up to the ratings shown in
this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
33
1
/
2
1
/
2
44
44
1
/
2
1
/
2
UNIT VOLTAGE
208/2305.4
4602.4
5752.4
208/2305.4
4602.4
5752.4
208/2306.4
4602.9
5752.9
208/2306.4
4602.9
5752.9
55
55
1
/
2
1
/
2
MAXIMUM
AMP DRAW
6
6
UNIT
48HJ
004
005
006
007
LEGEND
Brake Horsepower
Bhp —
Table 7 — Evaporator-Fan Motor Data — High-Static Motors
UNIT
PHASE
Three2.402120
Three2.402120
Three2.902615
Three2.902615
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
20
UNIT VOLTAGE
MAXIMUM
AMP DRAW
208/2306.4
4602.9
5752.9
208/2306.4
4602.9
5752.9
208/2307.9
4603.6
5753.6
208/2306.4
4603.6
5753.6
*Extensive motor and electrical testing on these units ensures that
the full horsepower and watts range of the motors can be utilized
with confidence. Using your fan motors up to the ratings shown in
this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
Page 21
Table 8 — Motor Nominal Horsepower
UNIT 48HJMOTORNOMINAL HORSEPOWER
004
005
006
007
All1.00
All1.00
Single Phase1.50
Three Phase2.00
All2.00
Table 9 — Outdoor Sound Power (Total Unit)
UNIT
48HJ
004,005
006,007
ARI
RATING
(Bels)
631252505001000200040008000
7.655.966.064.066.268.464.561.757.3
8.059.168.968.771.974.068.965.759.0
OCTAVE BANDS
LEGEND
ARI —
Bels —
Air Conditioning and Refrigeration Institute
Sound Levels (1 bel = 10 decibels)
Table 10 — 48HJ004 Fan Performance — Vertical Discharge Units With Standard Motor
Bhp — Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 2.)
2. Motor drive range is 760 to 1090 rpm for standard motor ; 1075 to 1455
rpm for high-static motor. All other rpms require a field-supplied drive.
3. Values include losses for filters, unit casing, and wet coils. See page 28
for accessory/FIOP static pressure information.
0.20.40.60.81.0
RpmBhpRpmBhpRpmBhpRpmBhpRpmBhp
1.21.41.61.82.0
RpmBhpRpmBhpRpmBhpRpmBhpRpmBhp
LEGEND AND NOTES FOR TABLES 10 AND 11
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
4. Maximum continuous bhp is 1.20 for standard motor, 2.40 for high-static
motor. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using your
fan motors up to the ratings shown will not result in nuisance tripping
or premature motor failure. Unit warranty will not be affected. See
Evaporator-Fan Motor Data tables on page 20 for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
6. Interpolation is permissible. Do not extrapolate.
21
Page 22
Table 12 — 48HJ005 Fan Performance — Vertical Discharge Units With Standard Motor
Bhp — Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 3.)
2.indicates field-supplied motor and drive required.
3. Motor drive range is 840 to 1185 r pm for standard motor; 1075 to
1455 rpm for high-static motor. All other rpms require a field-supplied
drive.
1.21.41.61.82.0
RpmBhpRpmBhpRpmBhpRpmBhpRpmBhp
LEGEND AND NOTES FOR TABLES 12 AND 13
EXTERNAL STATIC PRESSURE (in. wg)
4. Values include losses for filters, unit casing, and wet coils. See page 28
for accessory/FIOP static pressure information.
5. Maximum continuous bhp is 1.2 for standard motor, 2.4 for high-static
motor. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using your
fan motors up to the ratings shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on page 20 for additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
7. Interpolation is permissible. Do not extrapolate.
22
Page 23
Table 14 — 48HJ006 Fan Performance — Vertical Discharge Units With Standard Motor
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 3.)
2.indicates field-supplied motor and drive required.
3. Motor drive range is 1020 to 1460 rpm for single-phase standard
motors, 1120 to 1585 for 3-phase standard motors, and 1300 to 1685 for
high-static motors. All other rpms require a field-supplied drive.
0.20.40.60.81.0
RpmBhpRpmBhpRpmBhpRpmBhpRpmBhp
1.21.41.61.82.0
RpmBhpRpmBhpRpmBhpRpmBhpRpmBhp
15962.9516823.4517603.96————
LEGEND AND NOTES FOR TABLES 14 AND 15
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
16273.0316933.4217553.81
17263.31————
4. Values include losses for filters, unit casing, and wet coils. See page 28
for accessory/FIOP static pressure information.
5. Maximum continuous bhp is 1.30 for single-phase standard motors, 2.40
for 3-phase standard motors, and 2.90 for high-static motors. Extensive
motor and electrical testing on these units ensures that the full range of
the motor can be utilized with confidence. Using your fan motors up to
the ratings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected. See Evaporator-Fan Motor
Data tables on page 20 for additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
7. Interpolation is permissible. Do not extrapolate.
16322.9716913.31
16543.08
23
Page 24
Table 16 — 48HJ007 Fan Performance — Vertical Discharge Units With Standard Motor
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 3.)
2.indicates field-supplied motor and drive required.
3. Motor drive range is 1120 to 1585 rpm for standard motors, 1130 to
1685 rpm for high-static motors. All other rpms require a field-supplied
drive.
1.21.41.61.82.0
RpmBhpRpmBhpRpmBhpRpmBhpRpmBhp
17683.26——————
17763.45————————
LEGEND AND NOTES FOR TABLES 16 AND 17
EXTERNAL STATIC PRESSURE (in. wg)
17793.13————
4. Values include losses for filters, unit casing, and wet coils. See page 28
for accessory/FIOP static pressure information.
5. Maximum continuous bhp is 2.40 for standard motors, 2.90 for highstatic motors. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confidence.
Using your fan motors up to the ratings shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
See Evaporator-Fan Motor Data tables on page 20 for additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
7. Interpolation is permissible. Do not extrapolate.
24
Page 25
Table 18 — 48HJ004 Fan Performance — Horizontal Discharge Units With Standard Motor
Bhp — Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 3.)
2. Motor drive range is 760 to 1090 rpm for standard motors; 1075 to
1455 rpm for high-static motors. All other rpms require a field-supplied
drive.
3. Values include losses for filters, unit casing, and wet coils. See page 28
for accessory/FIOP static pressure information.
1.21.41.61.82.0
RpmBhpRpmBhpRpmBhpRpmBhpRpmBhp
LEGEND AND NOTES FOR TABLES 18 AND 19
EXTERNAL STATIC PRESSURE (in. wg)
4. Maximum continuous bhp is 1.20 for standard motors; 2.40 for high-static
motors. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using your fan
motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Data tables on page 20 for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
6. Interpolation is permissible. Do not extrapolate.
25
Page 26
Table 20 — 48HJ005 Fan Performance — Horizontal Discharge Units With Standard Motor
Bhp — Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 3.)
2. indicates field-supplied motor and drive required.
3. Motor drive range is 840 to 1185 rpm for standard units; 1075 to 1455 rpm
for high-static motors. All other rpms require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils. See page 28
for accessory/FIOP static pressure information.
1.21.41.61.82.0
RpmBhpRpmBhpRpmBhpRpmBhpRpmBhp
LEGEND AND NOTES FOR TABLES 20 AND 21
EXTERNAL STATIC PRESSURE (in. wg)
5. Maximum continuous bhp is 1.20 for standard motors; 2.40 for high-static
motors. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using your fan
motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Data tables on page 20 for additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
7. Interpolation is permissible. Do not extrapolate.
15.212.54
26
Page 27
Table 22 — 48HJ006 Fan Performance — Horizontal Discharge Units With Standard Motor
Bhp — Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 3.)
2. indicates field-supplied motor and drive required.
3. Motor drive range is 1020 to 1460 rpm for single-phase standard units,
1120 to 1585 for 3-phase standard units, and 1300 to 1685 for high-static
units. All other rpms require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils. See page 28
for accessory/FIOP static pressure information.
0.20.40.60.81.0
RpmBhpRpmBhpRpmBhpRpmBhpRpmBhp
1.21.41.61.82.0
RpmBhpRpmBhpRpmBhpRpmBhpRpmBhp
LEGEND AND NOTES FOR TABLES 22 AND 23
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
16333.0316923.2817463.61
5. Maximum continuous bhp is 1.30 for single-phase standard units, 2.40 for
3-phase standard motors, and 2.90 for high-static motors. Extensive
motor and electrical testing on these units ensures that the full range of
the motor can be utilized with confidence. Using your fan motors up to the
ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Evaporator-Fan Motor Data
tables on page 20 for additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
7. Interpolation is permissible. Do not extrapolate.
16452.98
16763.17
16573.0717103.38
27
Page 28
Table 24 — 48HJ007 Fan Performance — Horizontal Discharge Units With Standard Motor
5. Maximum continuous bhp is 2.4 for standard motors; 2.9 for high-static
motors. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using your fan
motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Data tables on page 20 for additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
7. Interpolation is permissible. Do not extrapolate.
Failure to observe the following warnings could result in
serious personal injury:
1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant
system.
2. Do not operate compressor or provide any electric
power to unit unless compressor terminal cover is i n
place and secured.
3. Do not remove compressor terminal cover until all
electrical sources are disconnected.
4. Relieve all pressure from system before touching or
disturbing anything inside terminal box if refrigerant
leak is suspected around compressor terminals.
5. Never attempt to repair sol d ered connection while refrigerant system is under pressure.
6. Do not use t orch to remove any component. System
contains oil and refrigerant under pressure. To remove
a component, wear protective goggles and proceed as
follows:
a. Shut off electrical power and then gas to unit .
b. Reclaim refrigerant to relieve all pressure from
system using both high- and low-pressure ports.
c. Cut component connection tubing with tubing
cutter and remove component from unit.
d. Carefully unsweat remaining tubing stubs
when necessary. Oi l can ignite when exposed
to torch flame.
Proceed as follows to inspect and prepare the unit for initial
start-up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING, CAUTION, and INFORMATION labels attached to, or
shipped with, unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages such as
broken lines, loose parts, or disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections
and on unit base. Detecting oil generally indicates
a refrigerant leak. Leak-test all refrigerant tubing
connections using electronic leak detector, halide
torch, or li quid-soap solution.
c. Inspect all field- and factory-wiring connections.
Be sure that connections are completed and tight.
Be sure that wires are not in contact with refrigerant tubing or sharp edges.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin comb .
4. V erify the following conditions:
a. Make sure that condenser-fan blade are correctly
positioned in fan orifice. See Condenser-Fan
Adjustment section on page 34 for more details.
b. Make sure that air filter(s) is in place.
c. Make sure that condensate drain trap is filled with
water to ensure proper drainage.
d. Make sure that all tools and miscellaneous loose
parts have been removed.
START-UP
Unit Preparation —
stalled in accordance with installat ion instructions and applicable codes.
Return-Air Filters —
stalled in unit (see T able 1). Do not operate unit without returnair filters.
Outdoor-Air Inlet Screens —
must be in place before operating unit.
Compressor Mounting —
spring mounted. Do not loosen or remove compressor holddown bolts.
Internal Wiring —
unit control boxes. Tighten as required.
Refrigerant Service Ports —
3 Schrader-type service ports: one on the suction line, one on
the liquid line, and one on the compressor discharge line. Be
sure that caps on the ports are tight. Two additional Schrader
valves are located under the high-pressure and low-pressure
switches, respectively.
HIGH FLOW REFRIGERANT VALVES — Two high flow
valves are located on the hot ga s tube coming out of the compressor and the suction tube going into the compressor. Large
black plastic caps identify these valves. These valves have
O-rings inside which screw the cap onto a brass body to prevent leaks. No field acc ess to these valves is ava ilable at this
time. Ensure the plastic caps remain on the valves and are tight
or the possibility of refrigerant leakage could occur.
Compressor Rotation —
compressors, it is impor tant to be cer tain comp ressor i s rotat ing
in the proper direction. To determine whet her or not compressor is rotating in the proper direction:
1. Connect service gages to suction and discharge pressure
fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pres-
sure does not rise to normal levels:
1. Note that the evaporator fan (006 and 007 only) is probably also rotating in the wrong direction.
2. Turn off power to the unit, tag disconnect.
3. Reverse any two of the unit power leads.
4. Reenergize to the compressor. Check pressures.
The suction and discharge pressure levels should now move
to their normal start-up levels.
Make sure that unit has been in-
Make sure correct filters are in-
Outdoor-air inlet screen
Compressors are internally
Check all electrical connections in
Each unit system has
On 3-phase units with scroll
29
Page 30
NOTE: When the compressor is rotating in the wrong direction, the unit will make an elevated level of noise and will not
provide cooling.
Cooling —
Set space thermostat to OFF position. To start
unit, turn on main power supply. Set system selector switch at
COOL position and fan switch at AUTO. position. Adjust thermostat to a setting below room temperature. Compressor starts
on closure of contactor.
Check unit charge. Refer to Refrigerant Charge section on
page 34.
Reset thermostat at a position above room temperature.
Compressor will shut off. Evaporator fan will shut off after a
30-second delay.
TO SHUT OFF UNIT — Set system selector swit ch at OFF
position. Resetting thermostat at a position above room temperature shuts unit off temporarily until space temperature exceeds thermostat setting. Units are equipped with CycleLOC™ protection device. Unit shuts down on any safety trip,
and indicator light on thermostat comes on. Check reason for
all safety trips.
Compressor restart is accomplished by manual reset at the
thermostat by turning the sele ctor switch to OFF and then to
ON position.
Main Burners —
Main burners are factory set and should
require no adjustment.
TO CHECK ignition of main burners and heating controls,
move thermostat set point above room temperature and verify
that the burners light and evaporator fan is energized. Check
heating effect, then lower the thermostat setting below the
room temperature and verify that the burners and evaporator
fan turn off.
Refer to Table 28 for the correct orifice to use at high
altitudes.
Table 28 — Altitude Compensation*
72,000 AND 115,000
BTUH NOMINAL
ELEVATION
(ft)
0-2,000
2,000
3,000
4,000
5,000
6,000
7,000
8,000
9,000
10,000
11,000
12,000
13,000
14,000
*As the height above sea level increases, there is less oxygen per
cubic foot of air. Therefore, heat input rate should be reduced at
higher altitudes.
†Orifices available through your local Carrier distributor.
1. Purge gas supply line of air by opening union ahead of
the gas valve. If gas odor is detected, tighten union and
wait 5 minutes before proceeding.
2. Turn on electrical supply and manual gas valve.
3. Set system switch selector at HEAT position and fan
switch at AUTO. or ON position. Set heating temperature
lever above room temperature.
4. The induced-draft motor will start.
5. After a call for heating, the main burners should light
within 5 seconds. If the burner does not light, then there is
a 22-second delay before another 5-second try. If the
burner still does not light, the time delay is repeated. If the
burner does not light within 15 minutes, there is a lockout. To reset the control, break the 24 v power to W1.
6. The evaporator-f an motor will turn on 45 seconds after
burner ignition.
7. The evaporator-fan motor will turn off in 45 seconds after
the thermostat temperature is satisfied.
8. Adjust airflow to obtain a temperature rise within the
range specified on the unit nameplate.
NOTE: The default value for the evaporator-fan mot or on/off
delay is 45 seconds. The Integrated Gas Unit Controller (IGC)
modifies this value when abnormal limit switch cycles occur.
Based upon unit operating conditions, the on delay can be
reduced to 0 seconds and the off delay can be extended to
180 seconds. When one flash of the LED (light-emitting diode)
is observed, the evaporator-fan on/off delay has been modified.
If the limit switch trips at the start of the heating cycle during the evaporator on delay, the time period of the on delay for
the next cycle will be 5 seconds less than the time at which the
switch tripped. (Example: If the limit swit ch trips at 30 seconds, the evaporator-fan on delay for the next cycle will oc cur
at 25 seconds.) To prevent short-cycling, a 5-second reduction
will only occur if a minimum of 10 minutes has e lapsed since
the last call for heating.
The evaporator-fan off delay can also be modified. Once the
call for heating has ended, there is a 10-minute period during
which the modification can occur. If the limit switch trip s during this period, the evaporator-fan off delay will increase by
15 seconds. A maximum of 9 trips can occur, extending the
evaporator-fan off delay to 180 seconds.
To restore the original defaul t value, reset the power t o the
unit.
TO SHUT OFF UNIT — Set sy s te m s el ec to r s wi tc h a t o f f po sition. Resetting heating selector lever below room temperature
will temporarily shut unit off until space temperature falls below thermostat setting.
Safety Relief —
A soft-solder joint at the suction service
Schrader port provides pressure relief under abnormal temperature and pressure conditions.
Ventilation (Continuous Fan) —
Set fan and system
selector switches at ON and OFF positions, respectively.
Evaporator fan operates continuously to provide constant air
circulation. When the evaporator-fan sel ector switch is turned
to the OFF position, there is a 30-second delay before the fan
turns off.
Operating Sequence
COOLING, UNITS WITHOUT ECONOMIZER — When
thermostat calls for cooling, terminals G and Y1 and the compressor contactor (C ) are ener gized . The indoo r (eva porator) fa n
motor (IFM), compressor, and outdoor (condenser) fan motor
(OFM) start. The OFM runs continuously while the unit is in
cooling. When the thermostat is satisfied, C is deenergized and
the compressor and OFM shut off. After a 30-second delay, the
(IFM) shuts off. If the thermostat fan selector switch is in the
ON position, the evaporator motor will run continuously.
30
Page 31
HEATING, UN ITS WI THOUT ECON OMIZ ER — When
the thermostat calls for heating, terminal W1 is energized. The
induced-draft motor is energized and the burner ignition sequence begins. The indoor (evaporator) fan motor (IFM) is energized 45 seconds after a flame is ignited. When additional
heat is needed, W2 is energized and the high-fire solenoid on
the main gas valve (MGV) is energized. When the thermostat
is satisfied and W1 is deenergized, the IFM stops after a
45-second time-off delay .
COOLING, UNITS WITH DURABLADE ECONOMIZER — When the outdoor-air temperature is above the outdoor-air thermostat (OAT) setting and the room thermostat
calls for cooling, compressor contactor is energized to start
compressor and the outdoor (condenser) fan motor (OFM).
The indoor (evaporator) fan motor (IFM) is energized and the
economizer damper moves to the minimum position. After the
thermostat is satisfied, there is a 30-second delay before the
evaporator fan turns off. The damper then moves to the fullyclosed position. When using continuous fan, the damper moves
to the minimum position.
When the outdoor-air temperature is below the OAT setting
and the thermostat calls for cooling, the economizer damper
move to the minimum position. If the supply-air temperature is
above 57 F, the damper continues to open until it reaches the
fully-open position or until the supply-air temperature drops
below 52 F .
When the supply-air temperature falls between 57 F and
52 F, the damper w ill remai n at a n interm ediate open position.
If the supply-air temperature falls below 52 F, the damper will
modulate closed until it reaches the minimum position or until
the supply-air temperature is above 52 F. When the thermostat
is satisfied, the damper moves to the fully closed position when
using AUTO. fan or to the minimum position when using continuous fan.
If the outdoor air alone cannot satisfy the cooling require ments of the conditioned space, economizer cooling is integrated with mechanical cooling, providing two stages of cooling.
Compressor and the condenser fan will be energized and the
position of the economizer damper will be de termined by the
supply-air temperature. When the second stage of cooling is
satisfied, the compressor and OFM will be deenergized. The
damper position will be determined by the supply-air temperature. When the first stage of cooling is satisfied, there is a
30-second delay before the evaporator fan shuts off. The damper then moves to the fully closed position. When using a continuous fan, the damper moves to the minimum position.
COOLING, UNITS WITH ECONOMI$ER — When the
Outdoor Air Temperature (OAT) is above the ECON SP set
point and the room thermostat calls for Stage 1 cool ing (R to
G +Y1), the indoor-fan motor (IFM) is energized and the
EconoMi$er damper modulates to minimum position. The
compressor contactor is energized starting the compr essor and
outdoor-fan motor (OFM). After the thermostat is satisfied, the
damper modulates to the fully closed position when the IFM is
deenergized.
When the OAT is below the ECON SP set point and the
room thermostat calls for Stage 1 cooling (R to G + Y1), the
EconoMi$er modulates to the minimum position when the
IFM is energized. The EconoMi$er provides Stage 1 of cooling
by modulating the return and outdoor air dampers to maintain a
55 F supply air set point. If the supply-air temperature (SAT) is
greater than 57 F, the EconoMi$er modulates open, all owing a
greater amount of outdoor air to enter the unit. If the SA T drops
below 53 F, the outdoor-air damper modules closed to reduce
the amount of outdoor air. When the SAT is between 53 and
57 F , the EconoMi$er maintains its position.
HEATING, UNIT S WI TH E CONOM IZ ER — W hen the ther mostat calls for heating, terminal W1 is energized. The
induced-draft motor is energized and the burner ignition sequence begins. The indoor (evaporator) fan motor (IFM) is energized 45 seconds after a flame is ignited and the damper
moves to the minimum position. When additional heat is needed, W2 energized and the high-fire solenoid on the main gas
valve (MGV) is energized. When the thermostat is satisfied
and W1 is deenergized, the IFM stops after a 45-second timeoff delay. The economizer damper then moves to the fully
closed position. When using continuous fan, the damper will
remain in the minimum position.
UNITS WITH MOISTUREMISER DEHUMIDIFICATION
PACKAGE — When thermostat calls for cooling, terminals G
and Y1 and the compressor contactor C1 is energized. The indoor (evaporator) fan motor (IFM), compressor, and outdoor
(condenser) fan motor (OFM) start. The OFM runs continuously while the unit is in cooling. As shipped from the factory,
MoistureMiser dehumidification circuit is a lw ays energized. If
MoistureMiser circuit modulation is desired, a field- installed,
wall-mounted humidistat is required.
If the MoistureMiser humidistat is installed and calls for the
MoistureMiser subcooler coil to operate, the humidistat internal switch closes. This energizes and closes the liquid line solenoid valve coil (LLSV) of the MoistureMiser circuit, forcing
the hot liquid refrigerant of the liquid line to enter the subcooler
coil (see Fig. 39). As the hot liquid passes through the subcooler coil, it is exposed to the cold supply airflow coming off from
the evaporator coil and the liquid is further cooled to a temperature approaching the evaporator coil leaving-air temperature.
The state of the refrigerant leaving the subcooler coil is a highly subcooled liquid refrigerant. The liquid then enters a thermostatic expansion valve (TXV) where the liquid i s dropped to a
lower pressure. The TXV does not have a pressure drop great
enough to change the liquid to a 2-phase fluid. The TXV c an
throttle the pressure drop of the liquid refrigerant and maintain
proper conditions at the compressor suction valve over a wide
range of operating conditions. The liquid then enters a second
fixed restrictor expansion device for a second pre ssure drop t o
a 2-phase fluid. The liquid proceeds to the evaporator coil at a
temperature lower than normal cooling operation. This lower
temperature is what increases the latent capacity of the rooftop.
The 2-phase refrigerant passes through the evaporator and is
changed into a vapor. The air passing over the evaporator coil
will become colder than during normal operation as a result of
the colder refrigerant temperatures. H owever, as it passes over
the subcooler coil, the air will be warmed slightly.
As the refrigerant leaves the evaporator, the refrigerant
passes a low-pressure switch in the suction line. This lowpressure switch will de-activate the MoistureMiser package
when the suction pressure reaches 60 psig. The low-pressure
switch is an added safety device to protect against evaporator
coil freeze-up. The low-pressure switc h will only de-activate
and open the liquid line solenoid valve in the MoistureMiser
circuit. The compressors will continue to run as long as there is
a call for cooling, regardless of the position of the low-pressure
switch. The solenoid valve and the MoistureMiser package will
be re-activated only when the call for cooling has bee n satisfied, the low-pressure switch has closed, and a new call for
cooling exists. The crankcase heaters on the scroll compress or
provide additional protection for the compressor due to the additional refrigerant charge in the subcooler.
When the humidistat is satisfied, the humidistat internal
switch opens cutting power to and opening the LLSV. The refrigerant is routed back through the evaporator and the subcooler coil is removed from the refrigerant loop.
When the thermostat is satisfied, C1 is deenergized and the
compressor and OFM shut off. After a 30-second delay, the
IFM shuts off. If the thermostat fan selector switch is in the ON
position, the IFM will run continuously.
31
Page 32
Fig. 39 — MoistureMiser Option Operation
32
Page 33
SERVICE
Fig. 40 — Cleaning Condenser Coil
Fig. 41 — Propping Up Top Panel
Fig. 42 — Separating Coil Sections
When servicing unit, shut off all electrical power to unit to
avoid shock hazard or injury from rotating parts.
FAN MOTOR BEARINGS — Fan motor bearings are of the
permanently lubricated type. No further lubrication is required.
No lubrication of condenser- or evaporator-fan motors is
required.
Cleaning —
ing and cooling season and as operating conditions require.
EVAPORATOR COIL
1. Turn unit power off, tag disconnect. Remove evaporator
coil access panel.
2. If economizer or two-position damper is installed, remove economizer by disconnecting Molex plug and re moving mounting screws. Refer to accessory economizer
installation instructions or Optional Economizer sections
on pages 12 and 15 for additional information.
3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dishwasher
detergent in a pressurized spray canister. Wash both sides
of coil and flush with clean water. For best results,
back-flush toward return-air section to remove foreign
material. Flush condensate pan after completion.
5. Reinstall economizer and filters.
6. Reconnect wiring.
7. Replace access panels.
CONDENSER COIL — Inspect coil monthly. Clean condenser coil annually, and as required by location and outdoor
air conditions.
One-Row Coil
is not necessary to remove top panel.
2-Row Coils
Clean coil as follows:
1. Turn off unit power, tag disconnecct.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. See Fig. 40. To hold
top panel open, place coil corner post between top panel
and center post. See Fig. 41.
4. Remove screws securing coil to compressor plate and
compressor access panel.
5. Remove fastener holding coil sections together at return
end of condenser coil. Carefully separate the outer coil
section 3 to 4 in. from the inner coil section. See Fig. 42.
6. Use a water hose or other suitable equipment to flush
down between the 2 coil sections to remove dirt and de bris. Clean the outer surfaces with a stiff brush in the normal manner.
7. Secure inner and outer coil rows together with a fieldsupplied fastener.
8. Reposition the outer coil section and remove the coil corner post from between the top panel and center post. Reinstall the coil corner post and replace all screws.
CONDENSATE DRAIN — Check and clean each year at
start of cooling season. In winter, keep drain dry or protect
against freeze-up.
FILTERS — Clean or replace at start of each heating and cooling season, or more often if operating conditions require it. Replacement filters must be same dimensions as original filters.
OUTDOOR-AIR INLET SCREENS — Clean screen with
steam or hot water and a mild detergent. Do not use disposable
filters in place of screen.
Inspect unit interior at the beginning of heat-
— Wash coil with commercial coil cl eaner. It
Lubrication
COMPRESSORS — Each compressor is charged with correct
amount of oil at the factory.
33
Page 34
Condenser-Fan Adjustment (Fig. 43) —
Fig. 45 — Cooling Charging Chart,
Standard 48HJ005
Fig. 44 — Cooling Charging Chart,
Standard 48HJ004
Shut off
unit power supply. Remove condenser-fan assembly (grille,
motor, motor cover, and fan) and loosen fan hub setscrews.
Adjust fan height as shown in Fig. 43. Tighten setscrews and
replace condenser-fan assembly.
004-006 and 007 (208/230 V)
UNIT 48HJFAN HEIGHT — “A” (in.)
007 (460 and 575 V)
2.75
3.50
Fig. 43 — Condenser-Fan Adjustment
Economizer Adjustment —
Refer to Optional Econo-
mizer sections on pages 12 and 15.
Evaporator Fan Belt Inspection —
Check condition
of evaporator belt or tension during heating and coo ling inspections or as conditions require. Replace belt or adjust as necessary.
High-Pressure Switch —
The high-pressure switch
contains a Schrader core depressor, and is located on the compressor hot gas line. This switch opens at 428 psig and closes at
320 psig. No adjustments are necessary.
Loss-of-Charge Switch —
The loss-of-charge switch
contains a Schrader core depressor, and is located on the compressor liquid line. This switch opens at 7 psig and closes at
22 psig. No adjustments are necessary.
Freeze-Stat —
The freeze-stat is a bimetal temperaturesensing switch that is located on the “hair-pin” end of the evaporator coil. The switch protects the evaporator coil from freezeup due to lack of airflow. The switch opens at 30 F and closes
at 45 F . No adjustments are necessary.
Refrigerant Charge —
Amount of refrigerant charge is
listed on unit nameplate (also refer to Table 1). Refer to Carrier
GTAC2-5 Charging, Recovery, Recycling, and Reclamation
training manual and the following procedures.
Unit panels must be in place when unit is operating during
charging procedure. Unit must operate a minimum of 10 mi nutes before checking or adjusting referigerant charge.
An accurate superheat, thermocouple- or thermistor-type
thermometer, and a gage manifold are required when using the
superheat charging method for evaluating the unit charge.
Do
not use mercury or small dial-type thermometers because they
are not adequate for this type of measurement.
NO CH ARGE — Use standard evacuating techniques. After
evacuating system, weigh in the specified amount of refrigerant. (Refer to Table 1.)
LOW CH AR GE CO OL IN G — U sing Cooling Charging
Charts, Fig. 44-47, vary refrigerant until the conditions of the
charts are met. Note the charging charts are different from type
normally used. Charts are based on charging the units to the
correct superheat for the various operating conditions. Accurate pressure gage and temperature sensing device are required.
Connect the pressure gage to the service port on the suction
line. Mount the temperature sensing device on the suction line
and insulate it so that outdoor ambient temperature does not affect the reading. Indoor-air cfm must be within the normal operating range of the unit.
MOISTUREMISER SYSTEM CHARGING — The system
charge for units with the MoistureMiser option is greater than
that of the standard unit alone. The charge for units wit h this
option is indicated on the unit nameplate drawing. Also refer
to Fig. 48-51. To charge systems using the MoistureMiser
Dehumidification package, fully evacuate, recover, and recharge the system to the nameplate specified charge level.
To check or adjust refrigerant charge on systems using the
MoistureMiser Dehumidification package, charge per Fig. 48-
51. The subcooler MUST be energized to use the charging
charts. The charts reference a liquid pressure (psig) and
temperature at a point between the condenser coil and the
subcooler coil. A tap is provided on the unit to measure liquid
pressure entering the subcooler.
IMPORTANT: The subcooler charging charts (Fig. 48-
51) are to be used ONLY with units having the optional
MoistureMiser subcooling option. DO NOT use standard
charge (Fig. 44-47) for units with MoistureMiser option,
and DO NOT use Fig. 48-51 for standar d units.
34
Page 35
suction temperature should be. If suction temperature is high,
add refrigerant. If suction temperature is low, carefully recover
some of the charge. Recheck the suction pressure as charge is
adjusted.
NOTE: The MoistureMiser subcooler MUST be energized to
use the charging charts.
Fig. 46 — Cooling Charging Chart,
Standard 48HJ006
Fig. 47 — Cooling Charging Chart,
Standard 48HJ007
TO USE COOLING CHARGING CHART, STANDARD
UNIT — Take the outdoor ambient temperature and read
the suction pressure gage. Refer to charts to determine what
Flue Gas Passageways —
tor box and upper areas of the heat exchanger:
1. Remove the combustion blower wheel and motor assembly according to directions in Combustion-Air Blower
section below.
2. Remove the 3 screws holding the blower housing to the
flue cover.
3. Remove the flue cover to inspect the heat exchanger.
4. Clean all surfaces as required using a wire brush.
Combustion-Air Blower —
sure proper airflow and heating efficiency. Inspect blower
wheel every fall and periodically during heating season. For the
first heating season, inspect blower wheel bimonthly to determine proper cleaning frequency.
To inspect blower wheel, remove draft hood and screen.
Shine a flashlight into opening to inspect wheel. If cleaning is
required, remove motor and wheel as follows:
1. Slide burner access panel out.
2. Remove the 5 s crews th at atta ch induced-draft motor assembly to the vestibule cover.
3. Slide the motor and blower wheel assembly out of the
blower housing. The blower wheel can be cleaned at this
point. If additional cleaning is required, continue with
Steps 4 and 5.
4. To remove blower from the motor shaft, by remove
2 setscrews.
5. To remove motor, remove the 4 screws that hold the motor to mounting plate. Remove the motor cooling fan by
removing one setscrew. Then remove nuts that hold motor to mounting plate.
6. To reinstall, reverse the procedure outlined above.
Limit Switch —
Limit switch is located on the fan deck.
Remove blower access panel (Fig. 5).
To inspect the flue collec-
Clean periodically to en-
35
Page 36
CONDENSER FAN MUST BE OPERATING
CONDENSER FAN MUST BE OPERATING
Fig. 48 — Cooling Charging Chart, 48HJ004 with
Optional MoistureMiser Dehumidification Package
CONDENSER FAN MUST BE OPERATING
Fig. 49 — Cooling Charging Chart, 48HJ005 with
Optional MoistureMiser Dehumidification Package
Fig. 50 — Cooling Charging Chart, 48HJ006 with
Optional MoistureMiser Dehumidification Package
CONDENSER FAN MUST BE OPERATING
Fig. 51 — Cooling Charging Chart, 48HJ007 with
Optional MoistureMiser Dehumidification Package
36
Page 37
Burner Ignition —
INDUCEDDRAFT
MOTOR
MOUNTING
PLATE
INDUCEDDRAFT
MOTOR
MANIFOLD
PRESSURE
TAP
VESTIBULE
PLATE
FLUE
EXHAUST
ROLLOUT
SWITCH
BLOWER
HOUSING
GAS
VALV E
BURNER
SECTION
Fig. 52 — Burner Section Details
Fig. 53 — Burner Tray Details
Unit is equipped with a direct spark
ignition 100% lockout system. Integrated Gas Unit Controller
(IGC) is located in the control box (Fig. 10). A single LED on
the IGC provides a visual display of operational or sequential
problems when the power supply is uninterrupted. The LED
can be observed through the viewport. When a break in power
occurs, the IGC will be reset (resulting in a loss of fault history)
and the evaporator fan on/off times delay will be reset. During
servicing, refer to the label on the control box cover or T able 29
for an explanation of LED error code descriptions.
If lockout occurs, unit may be reset by interrupting power
*A 3-second pause exists between LED error code flashes. If more
than one error code exists, all applicable codes will be displayed in
numerical sequence.
†Indicates a code that is not an error. The unit will continue to oper-
ate when this code is displayed.
IMPORTANT: Refer to Troubleshooting Tables 30-36 for additional information.
Normal Operation
Hardware Failure
Evaporator Fan On/Off Delay Modified
Limit Switch Fault
Flame Sense Fault
4 Consecutive Limit Switch Faults
Ignition Lockout Fault
Induced-Draft Motor Fault
Rollout Switch Fault
Internal Control Fault
9. Remove the gas valve bracket.
10. Slide the burner tray out of the unit (Fig. 53).
11. T o reinstall, reverse the procedure outlined above.
Main Burners —
At the beginning of each heating season, inspect for deterioration or blockage due to corrosion or
other causes. Observe the main burner flames and adjust, if
necessary.
When servicing gas train, do not hit or plug orifice spuds.
REMOVAL AND REPLACEMENT OF GAS TRAIN
(See Fig. 52 and 53)
1. Shut off manual gas valve.
2. Shut off power to unit, tag disconnect.
3. Remove compressor access panel.
4. Slide out burner compartment side panel.
5. Disconnect gas piping at unit gas valve.
6. Remove wires connected to gas valve. Mark each wire.
7. Remove induced-draft motor, ignitor, and sensor w ire s at
the Integrated Gas Unit Controller (IGC).
8. Remove the 2 screws that attach the burner rack to the
vestibule plate.
CLEANING AND ADJUSTMENT
1. Remove burner rack from unit as described above.
2. Inspect burners and, if dirty, remove burners from rack.
3. Using a soft brush, clean burners and cross-over port as
required.
4. Adjust spark gap. See Fig. 54.
5. Reinstall burners on rack.
6. Reinstall burner rack as described above.
Replacement Parts —
A complete list of replacement parts may be obtained from a ny Carrier distributo r
upon request. Refer to Fig. 55 for a typ ical unit wiring
schematic.
Refer to Tables 30-36 for troubleshooting details.
Table 30 — LED Error Code Service Analysis
Loss of power to control module (IGC).Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and
High limit switch opens during heat
exchanger warm-up period before fan-on
delay expires.
Limit switch opens within three minutes
after blower-off delay timing in Heating mode.
High temperature limit switch is open.Check the operation of the indoor (evaporator) fan motor.
The IGC sensed flame that should not be
present.
Inadequate airflow to unit.Check operation of indoor (evaporator) fan motor and that supply-air
Unit unsuccessfully attempted ignition for
15 minutes.
IGC does not sense that induced-draft
motor is operating.
Rollout switch has opened.Rollout switch will automatically reset, but IGC will continue to
Microprocessor has sensed an error in the
software or hardware.
transformer. Units without a 24-v circuit breaker have an internal
overload in the 24-v transformer. If the overload trips, allow
10 minutes for automatic reset.
Ensure unit is fired on rate and temperature rise is correct.
Ensure units’ external static pressure is within application guidelines.
Ensure that the supply-air temperature rise is in accordance with
the range on the unit nameplate.
Reset unit. If problem persists, replace control board.
temperature rise agrees with range on unit nameplate information.
Check ignitor and flame sensor electrode spacing, gaps, etc.
Ensure that flame sense and ignition wires are properly
terminated. Verify that unit is obtaining proper amount of gas.
Check for proper voltage. If motor is operating, check the
speed sensor plug/IGC Terminal J2 connection. Proper
connection: PIN 1— White, PIN 2 — Red, PIN 3 — Black.
lock out unit. Check gas valve operation. Ensure that induceddraft blower wheel is properly secured to motor shaft.
Reset unit at unit disconnect.
If error code is not cleared by resetting unit power, replace the IGC.
If the IGC must be replaced, be sure to ground yourself to dissipate any electrical charge that may be present before handling
new control board. The IGC is sensitive to static electricity and
may be damaged if the necessary precautions are not taken.
IMPORTANT: Refer to heating troubleshooting for additional
heating section troubleshooting information.
LEGEND
IGC —
LED —
Integrated Gas Unit Controller
Light-Emitting Diode
39
Page 40
Table 31 — Heating Service Analysis
PROBLEMCAUSEREMEDY
Burners will not
ignite.
Inadequate heating.
Poor flame
characteristics.
Burners will not
turn off.
Misaligned spark electrodes.Check flame ignition and sensor electrode positioning. Adjust as
No gas at main burners.Check gas line for air purge as necessary. After purging gas line of
Water in gas line.Drain water and install drip leg to trap water.
No power to furnace.Check power supply, fuses, wiring, and circuit breaker.
No 24 v power supply to control circuit.Check transformer. Transformers with internal overcurrent protection
Miswired or loose connections.Check all wiring and wirenut connections.
Burned-out heat anticipator in thermostat.Replace thermostat.
Broken thermostat wires.Run continuity check. Replace wires, if necessary.
Dirty air filter.Clean or replace filter as necessary.
Gas input to unit too low.Check gas pressure at manifold. Clock gas meter for input. If too low,
Unit undersized for application.Replace with proper unit or add additional unit.
Restricted airflow.Clean filter, replace filter, or remove any restrictions.
Blower speed too low.Use high speed tap, increase fan speed, or install optional blower, as
Limit switch cycles main burners.Check rotation of blower, thermostat heat anticipator settings, and
Too much outdoor air.Adjust minimum position.
Incomplete combustion (lack of
combustion air) results in:
Aldehyde odors, CO (carbon monoxide),
sooting flame, or floating flame.
Unit is locked into Heating mode for a
one minute minimum.
needed.
air, allow gas to dissipate for at least 5 minutes before attempting to
relight unit.
Check gas valve.
require a cool-down period before resetting. Check 24-v circuit
breaker; reset if necessary.
increase manifold pressure or replace with correct orifices.
suitable for individual units, Adjust pulley.
temperature rise of unit. Adjust as needed.
Check economizer operation.
Check all screws around flue outlets and burner compartment.
Tighten as necessary.
Cracked heat exchanger.
Overfired unit — reduce input, change orifices, or adjust gas line or
manifold pressure.
Check vent for restriction. Clean as necessary.
Check orifice to burner alignment.
Wait until mandatory one minute time period has elapsed or reset
power to unit.
Table 32 — Durablade Economizer Service Analysis
PROBLEMCAUSEREMEDY
Damper does not
open.
Economizer
operation limited to
minimum position.
Damper does not
close.
LEGEND
EC —
OAT —
SAT —
SW —
Enthalpy Control
Outdoor-Air Thermostat
Supply-Air Thermostat
Switch
Evaporator fan not on.Check wiring between G on connection board and evaporator-fan
No power to economizer motor.1. Check that SW3 is making proper contact with the damper blade.
Economizer motor failure.If there is 24 vac power at the motor terminals, but motor is not operat-
OAT or EC set too high.1. Set at correct temperature (3 F below indoor space temperature).
Check wiring of economizer relay packs.1. Check continuity across relay R2 coil. If not connected, replace R2
Check SAT.If supply-air temperature is over 57 F, switch T2 should be closed. If
Incorrect wiring or wiring defects.1. Check switches 2 and 4. If non-operational, replace.
Check SAT.If supply-air thermostat is below 52 F, switch T1 should be closed. If
Economizer motor failure.If there is 24 vac power at motor terminals, but motor is not operating,
contactor.
2. Check continually across R1 coil. If not connect, replace relay R1.
3. Check diode D18. If diode is not functioning properly, replace D18.
4. Check wiring in economizer relay pack. (See unit label diagram.)
ing, replace motor.
2. Check OAT or EC by setting set point above outdoor temperature or
humidity level. If switch does not close, replace OAT or EC.
relay.
2. Check continuity across relay R3 coil. If not connected, replace R3
relay.
not, replace SAT.
2. Check diode D19. If diode D19 is not functioning properly, replace.
3. Check wiring on economizer and on economizer relay pack. (See
unit label diagram.)
not, replace SAT.
replace the motor.
40
Page 41
Table 3 3 — EconoMi$er Flash Code Identification
FLASH CODECAUSEACTION TAKEN BY ECONOMI$ER
Constant On
Constant Off
Continuous
Flash
Flash One
Flash Two
Flash Three
Flash Four
Critical Fault
Flash Five
Flash Six
Flash Seven
Flash Eight
Flash Nine
Non-Critical Fault
Flash Ten
Normal operationNormal operation.
No powerNo operation.
CONFIG button pushed and held
between 3 and 9 seconds
Control board faultSystem shutdown.
Thermostat fault (i.e., Y2 without Y1)System shutdown until corrected.
Actuator faultRevert to mechanical cooling only.
Supply air temperature sensor fault
Outdoor air temperature sensor fault
Outdoor air humidity sensor faultContinue operation with dry bulb or dry bulb differential switchover.
Return air temperature sensor fault
Return air humidity sensor fault
Carbon Dioxide (CO
Onboard adjustment potentiometer faultContinue operation with default potentiometer settings.
) sensor faultContinue operation without ventilation control.
2
Outdoor air damper is stroked fully open, then closed
(automatic test procedure takes 3 minutes to complete).
Continue operation with damper at minimum position.
Revert to mechanical cooling only.
Continue operation with damper at minimum position.
Disable mechanical cooling lockout.
Continue operation with single enthalpy EconoMi$er
switchover or dry bulb EconoMi$er switchover (without
humidity sensor).
Continue operation with single enthalpy, differential dry
bulb, or dry bulb EconoMi$er switchover.
Table 34 — EconoMi$er Troubleshooting
PROBLEMPOTENTIAL CAUSEREMEDY
Damper Does Not
Open
EconoMi$er
Operation Limited to
Minimum Position
Damper Position
Less than Minimum
Position Set Poi nt
Damper Does Not
Return to Minimum
Position
Damper Does Not
Close on Power Loss
LEGEND
IFM —
PL—
Indoor Fan Motor
Plug
Indoor (Evaporator) Fan is
Off
No Power to EconoMi$er
Controller
No Power to G TerminalIf IFM is on, check to ensure 24 vac is present on G Terminal of the
Controller FaultIf STATUS light is flashing one flash, the EconoMi$er controller is
Thermostat FaultIf STATUS light is flashing two flashes, the EconoMi$er controller senses
Actuator FaultCheck the wiring between the EconoMi$er controller and the actuator.
Minimum Position Set
Incorrectly
EconoMi$er Changeover
Set Point Set Too High or
Too Low
Supply Air Temperature
Sensor Faulty
Outdoor Air Temperature
Sensor Faulty
Supply Air Low Limit
Strategy Controlling
Ventilation Strategy
CO
2
Controlling
Damper Travel is
Restricted
Check to ensure that 24 vac is present at Terminal C1 (Common Power)
on the IFC (Indoor Evaporator Fan Contactor) or that 24 vac is present at
the IFO (Indoor Evaporator Fan On) terminal. Check whether 24 vac is
present at PL 6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is
not present, check wiring (see unit label diagram).
Check proper thermostat connection to G on the connection board.
Check to ensure that 24 vac is present across Terminals 24 VAC and
24 V COM on the EconoMi$er control. If 24 vac is not present, check wiring
(see unit label diagram). If 24 vac is present, STATUS light should be on
constantly.
EconoMi$er controller. If 24 vac is not present, check wiring (see unit
label diagram).
experiencing a fault condition. Cycle power to the controller. If condition
continues, replace the EconoMi$er controller.
the thermostat is wired incorrectly. Check wiring between the thermostat
and the connection board in the electrical panel. The fault condition is
caused by Y2 being energized before Y1.
Hold CONFIG button between 3 and 10 seconds to verify the
actuator’s operation. (This process takes 3 minutes to complete.)
Verify that the MIN POS (%) is set greater than zero. Adjust MIN POS (%)
to 100% to verify operation, and then set to correct setting.
Set at correct value. See Table 3.
If STATUS light is flashing 4 flashes, Supply Air Temperature Sensor is
faulty. Check wiring or replace sensor.
If STATUS light is flashing 5 flashes, Outdoor Air Temperature Sensor is
faulty. Check wiring or replace sensor.
The supply-air temperature is less than 45 F, causing the minimum
position to be decreased. Refer to the Start-Up instructions. Verify correct
setting of MIN POS (%). If correct, EconoMi$er is operating correctly.
If a CO2 sensor is being used, and the damper position is greater than
minimum position, the ventilation control strategy is controlling. Refer to
the Start-Up instructions. EconoMi$er is operating correctly.
Check to ensure the damper is not blocked.
41
Page 42
Table 35 — MoistureMiser Dehumidification Subcooler Service Analysis
PROBLEMCAUSEREMEDY
Subcooler will not energize.
Subcooler will not deenergize.
Low system capacity.
Loss of compressor superheat
conditions with subcooler
energized.
No power to control transformer from
evaporator-fan motor.
No power from control transformer to liquid line
solenoid valve
Liquid line solenoid valve will not operate.1. Solenoid coil defective; replace.
Liquid line solenoid valve will not open.Valve is stuck closed; replace valve.
Low refrigerant charge or frosted evaporator
coil.
Thermostatic expansion valve (TXV).1. Check TXV bulb mounting, and secure tightly to
Check power source and evaporator-fan relay. Ensure
all wire connections are tight.
1. Fuse open; check fuse. Ensure continuity of wiring.
2. Low-pressure switch open. Cycle unit off and allow
low-pressure switch to reset. Replace switch if it will
not close.
3. Transformer bad; check transformer.
2. Solenoid valve stuck open; replace.
1. Check charge amount. Charge per Fig. 47-51.
2. Evaporator coil frosted; check and replace lowpressure switch if necessary.
suction line.
2. Replace TXV if stuck open or closed.
42
Page 43
PROBLEMCAUSEREMEDY
Compressor and condenser fan
will not start.
Compressor will not start
but condenser fan runs.
Compressor cycles (other than
normally satisfying thermostat).
Compressor operates continuously.
Excessive head pressure.
Head pressure too low.
Excessive suction pressure.
Suction pressure too low.
Evaporator fan will not shut off.
Table 36 — Cooling Service Analysis
Power failure.Call power company.
Fuse blown or circuit breaker tripped.Replace fuse or reset circuit breaker.
Defective thermostat, contactor, transformer,
or control relay.
Insufficient line voltage.Determine cause and correct.
Incorrect or faulty wiring.Check wiring diagram and rewire correctly.
Thermostat setting too high.Lower thermostat setting below room temperature.
Faulty wiring or loose connections in com-
pressor circuit.
Compressor motor burned out, seized, or
relay.
One leg of 3-phase power dead.Replace fuse or reset circuit breaker. Determine
Refrigerant overcharge or undercharge.Recover refrigerant, evacuate system, and
Defective compressor.Replace and determine cause.
Insufficient line voltage.Determine cause and correct.
Blocked condenser.Determine cause and correct.
Defective run/start capacitor, overload, or
start relay.
Defective thermostat.Replace thermostat.
Faulty condenser-fan motor or capacitor.Replace.
Restriction in refrigerant system.Locate restriction and remove.
Dirty air filter.Replace filter.
Unit undersized for load.Decrease load or increase unit size.
Thermostat set too low.Reset thermostat.
Low refrigerant charge.Locate leak, repair, and recharge.
Leaking valves in compressor.Replace compressor.
Air in system.Recover refrigerant, evacuate system, and
Condenser coil dirty or restricted.Clean coil or remove restriction.
Dirty air filter.Replace filter.
Dirty condenser coil.Clean coil.
Refrigerant overcharged.Recover excess refrigerant.
Air in system.Recover refrigerant, evacuate system, and
Condenser air restricted or air short-cycling.Determine cause and correct.
Low refrigerant charge.Check for leaks, repair, and recharge.
Compressor valves leaking.Replace compressor.
Restriction in liquid tube.Remove restriction.
High heat load.Check for source and eliminate.
Compressor valves leaking.Replace compressor.
Refrigerant overcharged.Recover excess refrigerant.
Dirty air filter.Replace filter.
Low refrigerant charge.Check for leaks, repair, and recharge.
Metering device or low side restricted.Remove source of restriction.
Insufficient evaporator airflow.Increase air quantity. Check filter and replace if
Temperature too low in conditioned area.Reset thermostat.
Outdoor ambient below 25 F.Install low-ambient kit.
Time off delay not finished.Wait for 30-second off delay.
Replace component.
Check wiring and repair or replace.
Determine cause. Replace compressor.
Determine cause and replace.
cause.
recharge to nameplate.
Determine cause and replace.
recharge.
recharge.
necessary.
43
Page 44
Fig. 55 — Typical Wiring Schematic and Component Arrangement
Adjustable Heat Anticipator
Contactor, Compressor
Capacitor
Cooling Compensator
Compressor Lockout
Compressor Motor
Diode
Enthalpy Control
Economizer
Emergency Power Supply
Equipment
Economizer Relay
Freeze-Protection Thermostat
Filter-Status Switch
Fuse
Ground
Gas Valve Relay
High-Pressure Switch
Hall-Effect Sensor
High Voltage
Ignitor
Induced-Draft Motor
Indoor (Evaporator) Fan Contactor
Indoor (Evaporator) Fan Motor
Integrated Gas Unit Controller
Light-Emitting Diode
Low-Pressure/Loss-of-Charge Switch
Limit Switch
Main Gas Valve
Motor
Outdoor-Air Thermostat
Outdoor (Condenser) Fan Motor
Plug
Plug Assembly
Quadruple Terminal
Relay
Rollout Switch
Supply-Air Thermostat
Sensor
Switch Fully Open
Switch Fully Closed
Switch Minimum Vent Position
Switch Maximum Vent Position
Thermostat-Cooling
Thermostat-Heating
Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential only.
Not to represent wiring.
NOTES FOR FIG. 55
1. If any of the original wire furnished must be replaced, it must be replaced with Type 90 C wire or its
equivalent.
2. Three-phase motors are protected under primary single-phasing conditions.
3. Thermostats: HH07AT170, 172
Subbase: HH93AZ176, 177, 178 and 179
4. Set heat anticipator at .14 amp for first stage and .14 amp for second stage.
5. Use copper conductors only.
6. TRAN is wired for 230 v unit. If unit is to be run with 208 v power supply, disconnect BLK wire from
230 v tap and connect to 208 v tap (RED). Insulate end of 230 v tap.
45
Page 46
Copyright 2000 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Ta b 1 a 6 a
PC 111Catalog No. 534-767Printed in U.S.A.Form 48HJ-18SIPg 469-00Replaces: 48HJ-17SI
Page 47
Page 48
START-UP CHECKLIST
(Remove and Store in Job File)
I. PRELIMINARY INFORMATION
MODEL NO.:________________________________SERIAL NO.: ________________________________________
DATE:______________________________________TECHNICIAN: _______________________________________
BUILDING LOCATION: _______________________________
II. PRE-START-UP (insert checkmark in box as each item is completed)
VERIFY THA T ALL PACKING MA TERIALS HAVE BEEN REMOVED FROM UNIT
REMOVE ALL SHIPPING HOLDDOWN BOL TS AND BRACKETS PER INSTALLATION INSTRUCTIONS
VERIFY THA T CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
CHECK GAS PIPING FO R LEAKS
CHECK THAT RETURN INDOOR-AIR FI LTER IS CLE AN AN D IN PLAC E
VERIFY THA T UNIT INSTALLA TION IS LEVEL
CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS