Carrier 48HJD005-007 User Manual

Page 1
48HJD005-007, 48HJE/HJF004-007
48HJL/HJM/HJN/HJG/HJH/HJK004-006 (LOW NOx)
Single-Package Rooftop Heating/Cooling
Installation, Start-Up and
Service Instructions
CONTENTS
Page
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-28
Step 1 — Provide Unit Support . . . . . . . . . . . . . . . . . . . 1
•ROOF CURB
• SLAB MOUNT
Step 2 — Field Fabricate Ductwork . . . . . . . . . . . . . . . 3
Step 3 — Install External Trap for
Condensate Drain. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Step 4 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 3
• POSITIONING
Step 5 — Install Flue Hood . . . . . . . . . . . . . . . . . . . . . . . 4
Step 7 — Make Electrical Connections . . . . . . . . . . . 4
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
• HEA T ANTICIPATOR SETTINGS
Step 8 — Adjust Factory-Installed Options . . . . . . . 8
• MOISTUREMISER DEHUMIDIFCATION PACKAGE
• APOLLO CONTROL
• DISCONNECT SWITCH
• OPTIONAL DURABLADE ECONOMIZER
• OPTIONAL ECONOMI$ER
Step 9 — Adjust Evaporator-Fan Speed . . . . . . . . . 19
• BELT-DRIVE MOTORS
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-32
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-38
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . 39-45
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . CL-1
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precau­tions in the li terature, ta gs and label s attached t o the uni t, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
Before performing service or maintenance operations on unit, turn off main power switch to unit and insta ll lockout tag. Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate. Elec­trical shock could cause personal injury.
Disconnect gas piping from unit when leak testing at pressure greater than 1/2 psig. Pres­sures greater than damage resulting in hazardous condition. If gas valve is subjected to pressure greater than
1
/
psig, it
2
pressure testing field-supplied gas piping at pressures of to such piping must be isolated by manually closing the gas valve(s).
1
/2 psig will cause gas valve
must
be replaced before use. When
1
/2 psig or less, a unit connected
INSTALLATION
Unit is shipped in the vertical discharge configuration. To convert to horizontal discharge application, remove duct open­ing covers. Using the same screws, install covers on duct open­ings in basepan of unit with insulation-side down. Seals around openings must be tight.
NOTE: Any combination of supply and return ducting is per­missible, i.e., vertical supply combined with horizontal return.
Step 1 — Provide Unit Support
ROO F CU R B — Assemble and instal l acces sory roof curb in accordance with instructions shipped with curb. See Fig. 1. In­stall insulation, cant strips, roofing felt, and counter flashing as shown. If electric control power or gas service is to be routed through the basepan, attach the accessory thru-the-bottom service con­nections to the basepan in accordance with the accessory instal­lation instructions. Connections must be installed before unit is set on roof curb.
Fig. 2. This is necessary for unit drain to function properly. Re­fer to Accessory Roof Curb Installation Instructions for addi­tional information as required.
SLAB MOUNT (Horizontal Units Only) — Provide a level concrete slab that extends a minimum of 6 in. beyond unit cab­inet. Install a gravel apron in front of condenser-coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
Ductwork must be attached to curb, not to the unit.
IMPORTANT: The gasketing of th e unit to the roof curb
is critical for a watertight seal. Install gasket supplied
with the roof curb as shown in Fig. 1. Improperly
applied gasket can result in air leaks and poor unit
performance.
Curb should be level. Unit leveling tolerances a re shown in
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 1 a 6 a
PC 111 Catalog No. 534-767 Printed in U.S.A. Form 48HJ-18SI Pg 1 9-00 Replaces: 48HJ-17SI
Page 2
48/50HJ
UNIT SIZE
“A”
ROOF CURB
ACCESSORY
004-007
CRRFCURB001A00 1-2 [356]
CRRFCURB002A00 2-0 [610]
CONNECTOR
“G”
“F”
“E”
D ALT
PKG. ACCY.
CRBTMPWR001A00
CRBTMPWR003A00
2
2
/
/
1
1
[12.7] NPT
CONTROL
[19] NPT
POWER
4
/
3
4
/
3
GAS
[12.7] NPT
[31.7] CRBTMPWR002A00 /
1
1
[19] NPT
[31.7] CRBTMPWR004A00
4
4
/
[19] NPT
1
4
1
/
3
2
4
/
/
1
3
[19] NPT
[12.7] NPT
4
/
3
1
[44.5]
and 002A00 are for thru-the-curb connec-
tions. Packages CRBTMP003A00 and
6. Service clearance 4 ft on each side.
7. Direction of airflow.
004A00 are for thru-the-bottom connections.
8. Connector packages CRBTMPWR001A00
Fig. 1 — Roof Curb Details
DRAIN HOLE
1-4
[406]
16
/
11
[551]
1-9
UNIT SIZE B C
50HJF004-007
48HJD004-007
NOTES:
disassembled.
1. Roof curb accessory is shipped
rest on curb).
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb (flanges of duct
2
Page 3
MAXIMUM ALLOWABLE
DRAIN PLUG
CONDENSATE PAN (SIDE VIEW)
NOTE: Drain plug is shown in factory-installed position.
Fig. 3 — Condensate Drain Pan
DIFFERENCE (in.)
A-B B-C A-C
0.5 1.0 1.0
Fig. 2 — Unit Leveling Tolerances
Step 2 — Field Fabricate Ductwork —
Secure all
ducts to roof curb and building structure on vertical discharge
Do not connect ductwork to unit.
units.
For horizontal applica­tions, field-supplied isolation flanges should be attached to hor­izontal discharge openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be in-
sulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applica­ble fire codes.
A minimum clearance is not required around ductwork. Cabinet return-air static shall not exceed –.35 in. wg with Durablade economizer, or –.30 in. wg with EconoMi$er, or –.45 in. wg without economizer.
These units are designed for a minimum continuous return­air temperature in heating of 50 F (dry bulb), or an intermittent operation down to 45 F (dry bulb), such a s when used with a night setback thermostat.
Step 3 — Install External Trap for Condensate Drain —
located on the bottom and side of the unit. Unit discharge connections do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications.
When using the standard side drain connection, ensure the plug (Red) in the alternate bottom connection is tight before in­stalling the unit.
To use the bottom drai n connec tion for a roof curb i nstalla­tion, relocate the factory-installed plug (Red) from the bottom connection to the side connection. See Fig. 3. The piping for the condensate drain and external trap can be completed after the unit is in place.
All units must have an external trap for condensate drain­age. Install a trap 4-in. deep and protect against freeze-up. If drain line is installed downst ream from the ext ernal t rap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection (
Step 4 — Rig and Place Unit —
transportation damage, and file any claim w ith transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit, and rollers may be used to move unit across a roof. Level by using unit frame as a
The unit’s 3/4-in. condensate drain connections are
3
/4 in.).
Inspect unit for
reference. See Table 1 and Fig. 4 for additional information. Operating weight is shown in Table 1 and Fig. 4.
Lifting holes are provided in base rails as shown in Fig. 5.
Refer to rigging instructions on unit.
All panels must be in place when rigging and lifting.
POS ITION ING — Maintain cl earan ce around and a bove unit to provide minimum distance from combustible materials, prop­er airflow, and service access. See Fig. 5. A properly positioned unit will have the following clearances between unit and roof
1
/4-in. clearance between roof curb and base rails on each
curb; side and duct end of unit;
1
/4 in. clearance between roof curb and
condenser coil end of unit. (See Fig. 1, section C-C.)
Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contami nated air.
Be sure that unit is installed such that snow will not block the combustion intake or flue outlet.
Unit may be installed directly on wood flooring or on Class A, B, or C roof-covering material when roof curb is used.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Locate mechanical draft system flue assembly at least 48 in. from any opening through which combustion products could enter the building, and at least 48 in. from an adjacent building. When unit is located adjacent to public walkways, flue assem­bly must be at least 7 ft above grade.
NOTE: When unit is equipped with an accessory flue dis­charge deflector, allowable clearance is 18 inches.
Flue gas can deteriorate building materials. Orient unit such that flue gas will not affect building materials.
Adequate combustion-air space must be provided for proper operation of this equipment. Be sure that installation complies with all local codes and Section 5.3, Air for Combustion and Ventilation, NFGC (National Fuel Gas Code), ANSI (Ameri­can National Standards Institute) Z223.1-1984 and addendum Z223.1a-1987. In Canada, installation must be in ac cordance with the CAN1.B149.1 and CAN1.B149.2 installation codes for gas burning appliances.
Flue vent discharge must have a minimum horizontal clear­ance of 4 ft from electric and gas meters, gas regulators, and gas relief equipment.
After unit is in position, remove shipping materials and rig­ging skids.
3
Page 4
NOTES:
1. Place unit on curb as close as possible to the duct end.
2. Dimension in ( ) is in millimeters.
3. Hook rigging shackles through holes in base rail as shown in detail ‘‘A.’’ Holes in base rails are centered around the unit cen­ter of gravity. Use wooden top skid when rigging to prevent rig­ging straps from damaging unit.
4. Weights include base unit without economizer. See Table 1 for unit operating weights with accessory economizer.
All panels must be in place when rigging.
Fig. 4 — Rigging Details
UNIT 48HJ
004 005 006 007
MAX
WEIGHT
lb kg in. mm in. mm in. mm
530 240 73.69 1872 35.50 902 33.31 847 540 245 73.69 1872 35.50 902 33.31 847 560 254 73.69 1872 35.50 902 33.31 847 615 279 73.69 1872 35.50 902 33.31 847
“A” “B” “C”
Step 5 — Install Flue Hood —
Flue hood is shipped screwed to the burner compartment access panel. Remove from shipping location and, using screws provided, install flue hood in location shown in Fig. 5 and 6.
For units being installed in California Air Quality Manage-
ment Districts which require NO
emissions of 40 nanograms/
x
joule or less, kit CRLOWNOX001A00 must be installed.
Step 6 — Install Gas Piping —
Unit is equipped for use with type of gas shown on nameplate. Refer to local building codes, or in the absence of local codes, to ANSI Z223.1-1984 and addendum Z223.1A-1987 entitled National Fuel Gas Code. In Canada, installation must be in accordance with the CAN1.B149.1 and CAN1.B149.2 instal­lation codes for gas burning appliances.
For natural gas applications, gas pressure at unit gas c on­nection must not be less than 4 in. wg or greater than 13 in. wg while the unit is operating. On 48HJ005-007 high-heat units, the gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13 in. wg while the unit i s operating. For propane applications, the gas pressure must not be less than 5 in. wg or greater than 13 in. wg at the unit connection.
Size gas supply piping for 0.5 in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connection.
Support gas piping as shown in the table in Fig. 7. For ex­ample, a
3
/4-in. gas pipe must have one field-fabricated support beam every 8 ft. Therefore, an 18-ft long gas pipe would have a minimum of 3 support beams, and a 48-ft long pipe would have a minimum of 6 support beams.
See Fig. 7 for typical pipe guide and locations of external
manual gas shutoff valve.
Step 7 — Make Electrical Connections
Unit cabinet must have an uninterrupted, unbroken electri­cal ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control com­partment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA (National Fire Protection Associa­tion), latest edition, and local electrical code s.
gas piping as an electrical ground.
Failure to fo llow this warning could result in the installer being liable for per­sonal injury of others.
FIELD PO WER S UPPLY — All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power sup­ply, the transformer
must
be rewired by moving the black wire from the 230-v terminal on the transformer and connecting it to the 200-v terminal from the transformer.
Refer to unit label diagram for additional information. Pigtails are provided for field service. Use factory-supplied splices or UL (Underwriters’ Laboratories) approved copper connector.
When installing units, provide a disconnect per NEC.
All field wiring must comply with NEC and local requirements.
Do not use
4
Page 5
Table 1 — Physical Data
BASE UNIT 48 HJE/F/H/K/M/N004 HJD/E/F/G/H/K/L/M/N005 HJD/E/F/G/H/K/L/M/N006 HJD/HJE/HJF007 NOMINAL CAPACITY OPERATING WEIGHT (lb)
Unit With Durablade Economizer With EconoMi$er With MoistureMiser Dehumidification Package Roof Curb
COMPRESSOR
Quantity Oil (oz)
REFRIGERANT TYPE
Operating Charge (lb-oz) Standard Unit Unit With MoistureMizer Dehumidification Package
CONDENSER FAN
Quantity...Diameter (in.) Nominal Cfm Motor Hp...Rpm Watts Input (Total)
CONDENSER COIL
Standard Unit
Rows...Fins/in. Total Face Area (sq ft)
Unit with MoistureMiser Dehumidification Package
Rows...Fins/in. Total Face Area (sq ft)
EVAPORATOR FAN
Quantity...Size (in.) Nominal Cfm Maximum Continuous Bhp Std
Motor Frame Size Std
Fan Rpm Range Std
Motor Bearing Type Maximum Fan Rpm Motor Pulley Pitch Diameter
A/B (in.)
Nominal Motor Shaft Diameter (in.) Std
Fan Pulley Pitch Diameter (in.) Std
Belt — Type...Length (in.) Std
Pulley Center Line Distance (in.) Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full
Turns from Closed Position
Factory Setting — Full Turns Open Std
Factory Speed Setting (rpm) Std
Fan Shaft Diameter at Pulley (in.)
EVAPORATOR COIL
Rows...Fins/in. Total Face Area (sq ft)
Hi-Static
Hi-Static
Hi-Static
Std
Hi-Static
Hi-Static
Hi-Static
Hi-Static
Std
Hi-Static
Std
Hi-Static
Hi-Static
Hi-Static
LEGEND *Single phase/three phase.
Bhp —
Brake Horsepower
34 5 6
530 540 560 615 564 574 594 649 577 587 607 662 548 558 578 633 115 115 115 115
11 1 1
42 53 50 60
Scroll
R-22
5- 8 8-6 10- 0 9-10 8-13 11-2 12-13 13- 6
1...22 1...22 1..22 1...22 3500 3500 4100 4100
1
/4...825
180 180 320 320
1
/4...825
Propeller
1
/4...1100
1
/4...1100
Enhanced Copper Tubes, Aluminum Lanced Fins
1...17 2..17 2...17 2...17
14.6 16.5 16.5 16.5
1...17 1...17 1...17 1...17
3.9 3.9 3.9 3.9
1...10 x 10 1...10 x 10 1...10 x 10 1...10 x 10 1200 1600 2000 2400
1.20 1.20 1.30/2.40* 2.40
2.40 2.40 2.90 2.90 48 48 48/56* 56 56 56 56 56
760-1090 840-1185 1020-1460/1120-1585* 1120-1585
1075-1455 1075-1455 1300-1685 1300-1685
Ball Ball Ball Ball
2100 2100 2100 2100
1.9/2.9 1.9/2.0 2.4/3.4 2.4/3.4
2.8/3.8 2.8/3.8 3.4/4.4 3.4/3.4
1
/
2
5
/
8
4.5 4.0 4.0 4.0
4.5 4.0 4.5 4.5
1...A...33 1...A...33 1....4...40 1...A...38
1...A...39 1...A...39 1...A...40 1...A...40
10.0-12.4 10.0-12.4 14.7-15.5 14.7-15.5 65 70 75 95 65 65 60 60
55 6 5 66 5 5 33 3 3
1
3
/
2
890 980 1240 1304
1233 1233 1396 1396
5
/
8
Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol™ Metering Device
2...15 2...15 4...15 4...15
5.5 5.5 5.5 5.5
†Indicates automatic reset.
**48HJD005-007 and 48HJE004 (72,000 Btuh heat input) units have 2 burners.
48HJE005-007 and 48HJF004 (115,000 Btuh heat input) units and 48HJF005­007 (150,000 Btuh Heat input) units have 3 burners.
††An LP kit is available as an accessory.
||Three-phase standard models have heating inputs as shown. Single-phase
standard models have one-stage heating with heating input values as follows:
***California compliant three-phase models.
†††California SCAQMD compliant low NO
are controlled to 40 nanograms per joule or less.
Centrifugal Type, Belt Drive
1
/
2
5
/
8
31/
2
5
/
8
48HJE004, 48HJD005,006 — 72,000 Btuh 48HJF004, 48HJE005,006 — 115,000 Btuh 48HJF005,006 — 150,000 Btuh
5
/
8
5
/
8
31/
2
5
/
8
models have combustion products that
x
5
/
8
5
/
8
31/
2
5
/
8
5
Page 6
Table 1 — Physical Data (cont)
BASE UNIT 48 HJE/F/H/K/M/N004 HJD/E/F/G/H/K/L/M/N005 HJD/E/F/G/H/K/L/M/N006 HJD/HJE/HJF007 FURNACE SECTION
Rollout Switch Cutout Temp (F)†
Burner Orifice Diameter (in. ...drill size)**
Natural Gas — Std HJE
Liquid Propane — Alt††
Thermostat Heat Anticipator Setting (amps) 208/230/460 v
First Stage Second Stage
Gas Input (Btuh)
First Stage/Second Stage HJE
Efficiency (Steady State) (%)
Temperature Rise Range
Manifold Pressure (in. wg)
Natural Gas — Std
Liquid Propane — Alt†† Maximum Static Pressure (in. wg) Field Gas Connection Size (in.)
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief Cutout Reset (Auto.)
LOSS-OF-CHARGE SWITCH/LOW-PRESSURE
SWITCH (Liquid LIne) (psig) Cutout Reset (Auto.)
FREEZE PROTECTION THERMOSTAT
Opens (F) Closes (F)
OUTDOOR-AIR INLET SCREENS
Quantity...Size (in.)
RETURN-AIR FILTERS
Quantity...Size (in.)
LEGEND *Single phase/three phase.
Bhp —
Brake Horsepower
195 195 195 195
.113...33
HJF
.113...33
HJH HJK
HJM HJN
HJE HJF
HJH HJK
HJM HJN
HJF
HJH HJK
HJM HJN
HJE HJF
HJH HJK
HJM HJN
HJE HJF
HJH HJK
HJM HJN
.113...33 .113...33
.102...38
.102...38
.089...43 .089...43
.082...45 .082...45
.082...45
.082...45
.14 .14 .14 .14 .14 .14 .14 .14
|| 50,000/ 72,000 || 82,000/115,000
*** —/ 72,000 ***—/115,000
††† —/ 60,000
††† —/ 90,000
82 81
82 81
81
81
15-45 55-85
15-45 55-85
20-50
30-60
3.5 3.5 3.5 3.5
3.5 3.5 3.5 3.5
1.0 1.0 1.0 1.0
1
/
2
HJD
.113...33
HJE
.113...33
HJF
.129...30
HJG
.113...33
HJH
.113...33
HJK
.129...30
HJL
.102...38
HJM
.102...38
HJN
.116...32
HJD
.089...43
HJE
.089...43
HJF
.102...38
HJG
.089...43
HJH
.089...43
HJK
.102...38
HJL
.082...45
HJM
.082...45
HJN
.094...42
HJD
|| 50,000/ 72,000
HJE
|| 82,000/115,000
HJF
|| 120,000/150,000
HJG
*** —/ 72,000
HJH
*** —/115,000
HJK
*** —/150,000
HJL
††† —/ 60,000
HJM
††† —/ 90,000
HJN
††† —/120,000
HJD
82
HJE
81
HJF
80
HJG
82
HJH
81
HJK
80
HJL
81
HJM
81
HJN
82
HJD
15-45
HJE
35-65
HJF
50-80
HJG
15-45
HJH
35-65
HJK
50-80
HJL
20-50
HJM
30-60
HJN
40-70
1
/
2
†Indicates automatic reset.
**48HJD005-007 and 48HJE004 (72,000 Btuh heat input) units have 2 burners.
48HJE005-007 and 48HJF004 (115,000 Btuh heat input) units and 48HJF005­007 (150,000 Btuh Heat input) units have 3 burners.
††An LP kit is available as an accessory.
||Three-phase standard models have heating inputs as shown. Single-phase
standard models have one-stage heating with heating input values as follows:
48HJE004, 48HJD005,006 — 72,000 Btuh 48HJF004, 48HJE005,006 — 115,000 Btuh 48HJF005,006 — 150,000 Btuh
***California compliant three-phase models.
†††California SCAQMD compliant low NO
are controlled to 40 nanograms per joule or less.
HJD HJE HJF
HJG HJH HJK
HJL HJM HJN
HJD HJE HJF
HJG HJH HJK
HJL HJM HJN
HJD HJE HJF
HJG HJH HJK
HJL HJM HJN
HJD HJE HJF
HJG HJH HJK
HJL HJM HJN
HJD HJE HJF
HJG HJH HJK
HJL HJM HJN
450 ± 50
428 320
7 ± 3
22 ± 5
30 ± 5 45 ± 5
Cleanable
1...20 x 24 x 1 Throwaway
2...16 x 25 x 2
.113...33 .113...33
.129...30
.113...33 — .113...33 — .129...30
.102...38
.102...38
.116...32
.089...43 .089...43 .102...38
.089...43
.089...43
.102...38 — .082...45
.082...45
.094...42
|| 50,000/ 72,000 || 82,000/115,000 || 120,000/150,000
*** —/ 72,000
*** —/115,000
*** —/150,000 — ††† —/ 60,000
†††—/ 90,000
††† —/120,000
82 81 80
82
81
80 — 81
81
82
15-45 35-65 50-80
15-45
35-65
50-80 — 20-50
30-60
40-70
1
/
2
models have combustion products that
x
HJD
.113...33
HJE
.113...33
HJF
.129...30
HJD
.089...43
HJE
.089...43
HJF
.102...38
HJD
|| 50,000/ 72,000
HJE
|| 82,000/115,000
HJF
|| 120,000/150,000
HJD
82
HJE
81
HJF
80
HJD
15-45
HJE
35-65
HJF
50-80
1
/
2
6
Page 7
STANDARD
UNIT 48HJ
004 005 006 007
A B C D E
F
G
UNIT
WEIGHT
Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg
530 240 34 15.4 47 21.3 127 57.6 122 55.3 138 62.6 143 64.9 540 245 34 15.4 47 21.3 129 58.5 124 56.2 141 64.0 146 66.2 560 254 34 15.4 47 21.3 134 60.8 129 58.5 146 66.2 151 68.5 615 279 34 15.4 47 21.3 147 66.7 142 64.4 160 72.6 166 75.3
CONNECTION SIZES
13/
Dia [35] Field Power Supply Hole
″″″″
8
2
Dia [51] Power Supply Knockout
″″″″
13/
Dia [44] Charging Por t Hole
″″″″
4
7
/
Dia [22] Field Control Wiring Hole
″″″″
8
3
-14 NPT Condensate Drain
/
″″″″
4
5
/
-14 NPT Gas Connection
″″″″
8
21/
Dia [64] Power Supply Knockout
″″″″
2
DURABLADE
ECONOMIZER
WEIGHT
ECONOMI$ER
WEIGHT
CORNER
WEIGHT
(A)
CORNER
WEIGHT
CORNER
WEIGHT
(B)
NOTES:
1. Dimensions in [ ] are in millimeters.
(C)
CORNER WEIGHT
(D)
BOTTOM POWER CHART, THESE HOLES REQUIRED FOR
USE WITH ACCESSORY PACKAGES — CRBTMPWR001A00
THREADED
CONDUIT SIZE
*Select either 3/
†Select either 1/
THROUGH CRBTMPWR004A00
WIRE
1
″″″″
/
2
3
″″″″
/
4
″″″″
11/
4
1
″″″″
/
NPT
2
3
″″″″
/
NPT
4
USE
24 V Pow er* 11/ Pow er* 13/
Gas† 11/ Gas† 15/
or 11/
for power, depending on wire size.
4
4
or 3/
for gas depending on gas connection.
2
4
REQURED
HOLE SIZES (MAX.)
7
/
[22.2]
″″″″
8
[28.4]
″″″″
8
″ ″
4
[31.8]
″″″″
4
[41.3]
″″″″
8
2. Center of gravity.
3. Direction of airflow.
4. On vertical discharge units, ductwork to be attached to accessory roof curb only. For horizontal dis­charge units, field-supplied flanges should be attached to horizontal discharge openings, and all ductwork should be attached to the flanges.
5. Minimum clearance (local codes or jurisdiction may prevail): a. Between unit, flue side and combustible surfaces, 48 inches. (18 in. when using accessory flue
discharge deflector.)
b. Bottom of unit to combustible surfaces (when not using curb), 1 inch.
Bottom of base rail to combustible surfaces (when not using curb) 0 inches.
c. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side getting the greater
clearance is optional. d. Overhead, 60 in. to assure proper condenser fan operation. e. Between units, control box side, 42 in. per NEC (National Electrical Code). f. Between unit and ungrounded surfaces, control box side, 36 in. per NEC. g. Between unit and block or concrete walls and other grounded surfaces, control box side, 42 in.
per NEC. h. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser coil and combustion side as stated in notes 5a, b and c, a removable fence or barricade requires no clearance.
7. Units may be installed on combustible floors made from wood or Class A, B, or C roof covering material if set on base rail.
8. The ver tical center of gravity is 1′-6″ [457] up from the bottom of the base rail.
[44.4]
Fig. 5 — Base Unit Dimensions — 48HJ004-007
7
Page 8
Fig. 6 — Flue Hood Details
LEGEND
NFGC —
*Field supplied. NOTE: Follow all local codes.
National Fuel Gas Code
SPACING OF SUPPORTS
STEEL PIPE
NOMINAL DIAMETER
1
1
/
4
(in.)
1
/
2
3
or 1
/
4
or larger
SPACING OF SUPPORTS
X DIMENSION
(ft)
6 8
10
Fig. 7 — Gas Piping Guide (With Accessory
Thru-the-Curb Service Connections)
Install conduit through side panel openings indicated in Fig. 5. Route power lines through connector to terminal con­nections as shown in Fig. 8.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (also see Tables 2A-2D). On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in Tables 2A-2D, Note 2 to determine the percent voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invali­date any applicable Carrier warranty.
NOTE: If accessory thru-the-bottom connections and roof curb are used, refer to the Thru-the-Bottom Accessory Installation Instructions for information on power wiring and gas connec­tion piping. The power wiring, control wiring and ga s piping can be routed through field-drilled holes in the basepan. The basepan is specially designed and dimpled for drilling the access connection holes.
FIELD CONTR OL WIRING — Install a Carrier-approved accessory thermostat assembly according to installation in­structions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense aver­age temperature in accordance with thermostat installation instructions.
Route thermostat cable or equivalent single leads of colored wire from subbase terminals through connector on unit to low­voltage connections (shown in Fig. 9).
Connect thermostat wires to matching screw terminals of low-voltage connection board. See Fig. 9.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft , use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directl y connected to the thermostat and will require a junction box and splice at the thermostat.
Pass the control wires through the hole provided in the cor­ner post; then feed wires through the raceway built into the cor­ner post to the 24-v barrier located on the left side of the control box. See Fig. 10. The raceway provides the UL required clear­ance between high- and low-voltage wiring.
HEAT ANTICIPATOR SETTINGS — Set heat anticipator set­tings at .14 amp for first stage and .14 for second stage heating, when available.
Step 8 — Adjust Factory-Installed Options
MOISTUREMISER DEHUMIDIFICATION PACKAGE — MoistureMiser package operation can be controlled by field installation of a Carrier-approved humidistat (Fig. 11). To install the humidistat:
1. Route humidistat cable through hole provided in unit cor­ner post.
2. Feed wires through the raceway built into t he corner post to the 24-v barrier located on the left side of the control box. See Fig. 10. The raceway provides the UL-required clearance between high- and low-voltage wiring.
3. Use a wire nut to connect humidistat cable into low­voltage wiring as shown in Fig. 12.
APOLLO CONTROL — The optional Apollo control is used to actively monitor all modes of operation as well as indoor (evaporator) fan status, filter status, and indoor-air quality. The Apollo control is designed to work with Carrier TEMP and
®
systems.
VVT
The thermostat must be wired to the Apollo Control before starting the unit. Refer to the Apollo Control installation instructions for information on installing the thermostat.
DISCONNECT SWITCH — The optional disconnect switch is non-fused. The switch has the capability of being locked in place for safety purposes.
8
Page 9
RACEWAY LOW VOLTAGE
CONNECTIONS
INTEGRATED GAS UNIT CONTROLLER (IGC)
HOLE IN END PANEL (HIDDEN)
LEGEND
C— COMPS — EQUIP — GND — IFC
NEC — TB
Contactor Compressors Equipment Ground Indoor (Evaporator) Fan Contactor National Electrical Code Terminal Block
LEGEND
AHA — CC — TC — TH
NOTE: Connect Y2 when unit is equipped with an integrated economizer.
Adjustable Heat Anticipator Cooling Compensator Thermostat-Cooling Thermostat-Heating Field Wiring Factory Wiring
Fig. 8 — Power Wiring Connections
Fig. 10 — Field Control Wiring Raceway
Fig. 9 — Low-Voltage Connections With or
Without Economizer
9
Page 10
Table 2A — 48HJ Electrical Data Standard Motor (Units Without Electrical Convenience Outlet)
UNIT 48HJ
004
(3 Tons)
005
(4 Tons)
006
(5 Tons)
007
(6 Tons)
NOMINAL
VOLTAGE (V-Ph-Hz)
208/230-1-60 187 254 16.0 88.0 0.7 4.9 .57 25.6/25.6 35/35 25/25 101/101 208/230-3-60 187 254 10.3 77.0 0.7 4.9 .57 18.5/18.5 25/25 18/18 90/ 90
460-3-60 414 508 5.1 39.0 0.4 2.2 .30 9.0 15 9 46
575-3-60 518 632 4.2 31.0 0.4 2.2 .30 7.3 15 7 36 208/230-1-60 187 254 23.7 129.0 0.7 4.9 .57 35.2/35.2 45/45 34/34 142/142 208/230-3-60 187 254 13.5 99.0 0.7 4.9 .57 22.5/22.5 30/30 22/22 112/112
460-3-60 414 508 7.4 49.5 0.4 2.2 .30 11.9 15 12 56
575-3-60 518 632 5.8 40.0 0.4 2.2 .30 9.3 15 9 45 208/230-1-60 187 254 28.8 169.0 1.5 8.8 .57 46.3/46.3 60/60 45/45 216/216 208/230-3-60 187 254 17.3 123.0 1.5 5.8 .57 28.9/28.9 35/35 28/28 168/168
460-3-60 414 508 9.0 62.0 0.8 2.6 .30 14.7 20 14 84
575-3-60 518 632 7.1 50.0 0.8 2.6 .30 11.6 15 11 67 208/230-3-60 187 254 20.5 156.0 1.4 5.8 .57 32.8/32.8 40/40 32/32 200/200
460-3-60 414 508 9.6 70.0 0.6 2.6 .30 15.2 20 15 92
575-3-60 518 632 7.7 56.0 0.6 2.6 .30 12.2 15 13 78
VOLTAGE
RANGE
Min Max RLA LRA FLA FLA FLA MCA MOCP† FLA LRA
COMPRESSOR OFM IFM
Table 2B — 48HJ Electrical Data Standard Motor (Units With Electrical Convenience Outlet)
UNIT 48HJ
004
(3 Tons)
005
(4 Tons)
006
(5 Tons)
007
(6 Tons)
FLA — HACR— IFM — LRA — MCA — MOCP— NEC — OFM — RLA — UL
*Used to determine minimum disconnect per NEC.
Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combi-
2.
Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps Underwriters Laboratories
nation load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt­age is greater than 2%.
the percent of voltage imbalance.
= 100 x
max voltage deviation from average voltage
NOMINAL
VOLTAGE (V-Ph-Hz)
208/230-1-60 187 254 16.0 88.0 0.7 4.9 .57 31.6/31.6 40/40 30/30 106/106 208/230-3-60 187 254 10.3 77.0 0.7 4.9 .57 24.5/24.5 30/30 24/24 95/95
460-3-60 414 508 5.1 39.0 0.4 2.2 .30 11.7 15 11 48
575-3-60 518 632 4.2 31.0 0.4 2.2 .30 9.5 15 9 38 208/230-1-60 187 254 23.7 129.0 0.7 4.9 .57 41.2/41.2 50/50 39/39 147/147 208/230-3-60 187 254 13.5 99.0 0.7 4.9 .57 28.5/28.5 35/35 27/27 117/117
460-3-60 414 508 7.4 49.5 0.4 2.2 .30 14.6 20 14 58
575-3-60 518 632 5.8 40.0 0.4 2.2 .30 11.5 15 11 47 208/230-1-60 187 254 28.8 169.0 1.5 8.8 .57 52.3/52.3 60/60 50/50 221/221 208/230-3-60 187 254 17.3 123.0 1.5 5.8 .57 34.9/34.9 40/40 34/34 173/173
460-3-60 414 508 9.0 62.0 0.8 2.6 .30 17.4 20 17 86
575-3-60 518 632 7.1 50.0 0.8 2.6 .30 13.8 20 13 69 208/230-3-60 187 254 20.5 156.0 1.4 5.8 .57 38.8/38.8 45/45 37/37 205/205
460-3-60 414 508 9.6 70.0 0.6 2.6 .30 17.9 20 17 94
575-3-60 518 632 7.7 56.0 0.6 2.6 .30 14.3 20 15 79
LEGEND
Use the following formula to determine
average voltage
VOLTAGE
RANGE
Min Max RLA LRA FLA FLA FLA MCA MOCP† FLA LRA
COMPRESSOR OFM IFM
COMBUSTION
FAN MOTOR
COMBUSTION
FAN MOTOR
Example: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance.
% Voltage Imbalance= 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
= 1.53%
POWER
SUPPLY
WITH OUTLET
POWER
SUPPLY
WITH OUTLET
452 + 464 + 455
1371
=
3
= 457
7 457
MINIMUM UNIT
DISCONNECT
SIZE*
MINIMUM UNIT
DISCONNECT
SIZE*
3
10
Page 11
Table 2C — 48HJ High-Static Motor Units Without Electrical Convenience Outlet
UNIT 48HJ
004
005
006
007
NOMINAL
VOLTAGE (V-Ph-Hz)
208/230-3-60 187 254 10.3 77.0 0.7 5.8 0.6 19.4/19.4 25/25 19/19 120/120
460-3-60 414 508 5.1 39.0 0.4 2.6 0.3 9.4 15 9 60 575-3-60 518 632 4.2 31.0 0.4 2.6 0.3 7.7 15 8 48
208/230-3-60 187 254 13.5 99.0 0.7 5.8 0.6 23.4/23.4 30/30 23/23 142/142
460-3-60 414 508 7.4 49.5 0.4 2.6 0.3 12.3 15 12 71 575-3-60 518 632 5.8 40.0 0.4 2.6 0.3 9.7 15 9 57
208/230-3-60 187 254 17.3 123.0 1.5 7.5 0.6 30.6/30.6 35/35 30/30 187/187
460-3-60 414 508 9.0 62.0 0.8 3.4 0.3 15.5 20 15 94 575-3-60 518 632 7.1 50.0 0.8 3.4 0.3 12.2 15 12 76
208/230-3-60 187 254 20.5 156.0 1.4 7.5 0.6 30.6/30.6 35/35 30/30 187/187
460-3-60 414 508 9.6 70.0 0.6 3.4 0.3 15.5 20 15 94 575-3-60 518 632 7.7 56.0 0.6 3.4 0.3 12.2 15 12 76
VO LTAG E
RANGE
Min Max RLA LRA FLA FLA RLA MCA MOCP† FLA LRA
COMPRESSOR
(each)
Table 2D — 48HJ High-Static Motor Units With Electrical Convenience Outlet
UNIT
48HJ
004
005
006
007
FLA — HACR— IFM — LRA — MCA — MOCP— NEC — OFM — RLA — UL
*Used to determine minimum disconnect per NEC.
Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combi-
2.
Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps Underwriters Laboratories
nation load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt­age is greater than 2%.
the percent of voltage imbalance.
= 100 x
max voltage deviation from average voltage
NOMINAL VOLTAGE (V-Ph-Hz)
208/230-3-60 187 254 10.3 77.0 0.7 5.8 0.6 25.4/25.4 30/30 25 124/124
460-3-60 414 508 5.1 39.0 0.4 2.6 0.3 12.1 15 12 63 575-3-60 518 632 4.2 31.0 0.4 2.6 0.3 9.8 15 10 50
208/230-3-60 187 254 13.5 99.0 0.7 5.8 0.6 29.4/29.4 35/35 29 146/146
460-3-60 414 508 7.4 49.5 0.4 2.6 0.3 15.0 20 14 73 575-3-60 518 632 5.8 40.0 0.4 2.6 0.3 11.8 15 11 59
208/230-3-60 187 254 17.3 123.0 1.5 7.5 0.6 36.6/36.6 40/40 36 192/192
460-3-60 414 508 9.0 62.0 0.8 3.4 0.3 18.2 20 18 96 575-3-60 518 632 7.1 50.0 0.8 3.4 0.3 14.4 20 14 77
208/230-3-60 187 254 20.5 156.0 1.4 7.5 0.6 40.5/40.5 45/45 39 224/224
460-3-60 414 508 9.6 70.0 0.6 3.4 0.3 18.7 25 18 104 575-3-60 518 632 7.7 56.0 0.6 3.4 0.3 15.0 20 15 89
LEGEND
Use the following formula to determine
average voltage
VOLTAGE
RANGE
Min Max RLA LRA FLA FLA RLA MCA MOCP† FLA LRA
COMPRESSOR
(each)
OFM IFM
OFM IFM
3
3
MINIMUM UNIT
DISCONNECT
SIZE*
MINIMUM UNIT
DISCONNECT
SIZE*
COMBUSTION
FAN MOTOR
COMBUSTION
FAN MOTOR
Example: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance.
% Voltage Imbalance= 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
= 1.53%
POWER SUPPLY
POWER
SUPPLY
7 457
452 + 464 + 455
1371
=
= 457
11
Page 12
OPTIONAL DURABLADE ECONOMIZER — The option-
Fig. 11 Accessory Field-Installed Humidistat
al economizer hood assembly is packaged and shipped in the filter section. Damper blades and control boards are installed at the factory and the economizer is shipped in the vertical dis­charge position.
NOTE: Horizontal discharge block-off plate is shipped with the air hood package. If unit is to be used for vertical discharge application, discard this plate.
Assembly:
1. Determine if ventilation air i s required in building. If so, determine the minimum amount to be supplied by each unit and record quantity of ventilation air needed for use in Step 7.
2. Remove filter access panel by raising panel and swinging panel outward. Panel is now disengaged from track and can be removed. No tools are required to remove filter ac­cess panel. Remove outdoor-air opening panel. Save pan­els and screws. See Fig. 13. Remove economizer, and re­move optional outdoor-air damper hood package from filter section (located behind economizer).
3. Assemble outdoor-air hood top and side plates as shown in Fig. 14. Install seal strips on hood top and sides. Put aside screen retainer and retainer screw for later assem-
Do not attach hood to unit at this time.
bly .
4. Slide economizer i nto unit and secure with screws. See Fig. 15.
NOTE: Be sure to engage rear economizer flange under tabs in vertical return-air opening.
5. To convert to horizontal discharge application: a. Rotate economizer 90 degrees until the econo-
mizer motor faces the condenser section (see Fig. 16).
b. Remove tape and shipping screw, rotate the baro-
metric relief damper cover 90 degrees.
c. Install horizontal discharge block-off plate over
the opening on the access panel. (Block-off plate MUST be installed before installing hood assem­bly.) See Fig. 17.
6. Remove 12-pin blue and yellow wir e jumper plug from factory wiring harness and store. Insert economizer plug into 12-pin plug of factory wiring harness. Remove tape and shipping screw from barometric relief damper. See Fig.18.
7. If ventilation air is not required, proceed to Step 8. If ven­tilation air is required, determine minimum position set­ting for required airflow. See Fig. 19. Adjust minimum position setting by adjusting the screws on the position setting bracket. Slide bracket until the top screw is in the position determined by Fig. 19. Tighten screws.
8. Remove tape from outdoor-air thermostat (OAT). Fasten OAT to inside of hood using screws and spee d clips pro­vided. See Fig. 20. Make sure OAT terminals are posi­tioned up.
MOISTUREMISER
% RELATIVE HUMIDITY
LEGEND
C CCH COMP FU HU IFM LLSV S-LPS TRAN
Contactor (Compressor) Crankcase Heater Compressor Fuse Humidistat Indoor (Evaporator) Fan Motor Liquid Line Solenoid Valve Low-Pressure Switch (Subcooler Only) Transformer Fac tory W irin g Accessory or Optional Wiring
Fig. 12 Typical MoistureMiser Dehumidification Package Humidistat Wiring
(208/230-V Unit Shown)
12
Page 13
9. Replace outdoor-air opening panel using screws from
ECONOMIZER CONTROL BOARD
ECONOMIZER PLUG
ECONOMIZER MOTOR
TOP SCREW
SHIPPING SCREW
ECONOMIZER CONTROL BOARD
BAROMETRIC RELIEF DAMPER
ECONOMIZER PLUG
ECONOMIZER MOTOR
BLOCK-OFF PLATE
Fig. 15 Durablade Economizer Installed in Unit
Fig. 16 Horizontal Durablade Economizer
Installation
Fig. 17 Horizontal Discharge Block-Off Plate
Step 2. Replace filter a ccess panel. Ensure the filter ac ­cess panel slides along the tracks and is securely engaged.
10. Fasten hood top and side plate assembly (Fig. 14) to outdoor-air opening panel with screws provided.
11. Place knob supplied with economizer on OAT. See Fig. 20. Set for 3° F below indoor room thermostat set­ting. If accessory enthalpy control (EC) is used in place of OAT, see instructions shipped with EC for installation and adjustment. See Fig. 20.
12. Connect OAT per Fig. 21.
13. Slide outdoor-air inlet screen into screen track on hood side plate. While holding screen in place, fasten screen re­tainer to hood using screws provided.
NOTE: Refer to Fig. 22 for economizer barometric relief damper characteristics.
FILTER ACCESS PANEL
OUTDOOR-AIR OPENING
Fig. 13 Typical Access Panel Locations
COMPRESSOR ACCESS PANEL
Fig. 14 Outdoor-Air Hood Details
13
Page 14
U-SHAPED HOLE (NOT SHOWN)
ECONOMIZER PLUG
WIRING HARNESS
Fig. 18 Typical Durablade Economizer and
Wiring Harness
Example:
Given
Negative Pressure. . . . . . . . . . . . . . . . . . . . . . . . . . .0.1 in. wg
Outdoor Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1100 cfm
Determine
Setting = 6
Fig. 19A Durablade Economizer Damper
Minimum Position Setting
0
1
2
3
TOP
ENTHALPY CONTROL
HOOD
OUTSIDE AIR SCREEN
OPEN
P
P1
I
T
Y
30
10
50
OUTDOOR TEMP
55
60
65
70
.
7
°
5
F
8 0
85
R
OAT (TERMINALS ARE UP)
POSITION
MINIMUM
1
3
T
5
2
T1
4
CONT
CONT
OR UNPOWERED ST
R
%
1
H
U
U
M
9
I
D
S
8
90
A
H
8
70
ACT RA
CTS SHO
60
1
A
3
8
T
CW
TR
2
A
D
4 V
–SETPOINTS
TINGS: 1.5A
C
DAMPER
A
24V
WN IN HIGH ENTHALPY
C
OPEN
B
A
2
C
A
A
3 m
TE
TR1
A
RUN, 3.5A IN
M
–CCW
IN. A
1
DAMPER
CLOSED
T 1
1 VDC
72
7-36
9
.
V
E
UNIT
RE
B
V . B
C
TR
D
S
S
O
ENTHALPY CONTROL
4
5
6
7
8
9
Fig. 19B Durablade Economizer Minimum
Position Damper Setting
Fig. 20 Outdoor-Air Thermostat/
Enthalpy Control Installation
Fig. 21 Wiring Connections for
Outdoor-Air Thermostat
14
Page 15
0.90
BAROMETRIC RELIEF DAMPERS
CONTROLLER
ECONOMI$ER PLUG
GEAR-DRIVEN DAMPER
OUTDOOR AIR TEMPERATURE SENSOR
ACTUATOR
OUTDOOR-AIR OPENING PANEL
FILTER ACCESS PANEL
OUTDOOR AIR OPENING PANEL
SEAL STRIP
EXHAUST AIR SCREEN
EXHAUST AIR HOOD TOP
SCREEN RETAINER
EXHAUST AIR HOOD SIDES
EXHAUST AIR BOTTOM BRACKET
Fig. 23 Economizer Component Locations
Fig. 24 Typical Access Panel Locations
Fig. 25 Exhaust Air Hood Assembly
0.80
0.70
0.60
0.50
0.40
0.30
PRESSURE DROP (in. wg)
0.20
0.10
the EconoMi$er plug into the unit wiring harness. Refer to wiring diagram Fig. 30 and 31. Also refer to Fig. 32 if installing an accessory power exhaust.
9. Install the complete hood assembly on the unit and secure using the screws provided.
10. Remove the indoor fan motor access panel. See Fig. 33.
11. Mount the supply-air temperature sensor to the lower left portion of the indoor blower housing with the two (2) screws provided (see Fig. 34). Connect the violet and pink wires to the corresponding connections on the supply-air temperature sensor. Replace the indoor fan motor access panel.
0.00
200 300 400
100
CFM
Fig. 22 Durablade Economizer Barometric
Relief Damper Characteristics
OPTIONAL ECONOMI$ER — See Fig. 23 for EconoMi$er component locations.
1. To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. Remove the indoor coil access panel and discard. See Fig. 24.
If installing an optional Power Exhaust Assembly, refer to
EconoMi$er Power Exhaust Installation Instructions.
the Controller should be mounted in vertical position as
shown in Fig. 23.
2. Assemble the hood assembly as follows: Remove the EconoMi$er hood from its packaging. Re-
move shipping brackets holding hood package to EconoMi$er. Locate the outdoor-air opening panel. See Fig. 25. Remove hood assembly shipping brackets locat­ed on the back (sloped) side of the EconoMi$er assembly. These brackets are used to retain the hood assembly dur­ing shipping only .
1
3. Install the
/8 x 3/4-in. seal strip on the exhaust air hood side panels and the bottom bracket. Assemble the exhaust air hood to the outdoor-air opening panel as shown in Fig. 25, using the screws provided.
assembly to unit at this time.
4. Ins tall the
1
/8 x 3/4 in. seal strip on the outdoor-air hood top and side panels. Assemble the outdoor-air hood to the outdoor-air opening panel as shown in Fig. 26, using the screws provided.
Do not attach hood assembly to the unit
at this time.
5. Slide the outdoor-air inlet screens into the screen track on the hood side panels. While holding the screens in pl ace, fasten the screen retainer to the hood using the screws provided. Repeat the process for the barometric exhaust air screen.
sembly to unit a t this ti me.
6. Install the EconoMi$er assembly into the rooftop unit. See Fig. 28 and 29.
NOTE: Be sure to engage rear EconoMi$er flange under tabs in return-air opening of the unit base. See Fig. 28.
7. Install the outdoor-air block-off plate, then secure the EconoMi$er with the screws provided. See Fig. 29.
Do not attach completed (Fig. 27) hood as-
8. Remove and discard the 12-pin jumper plug from the unit wiring harness located int he upper left corner and insert
500 600
Do not attach hood
700
800
15
Page 16
OUTDOOR AIR
WIRING HARNESS
OUTDOOR AIR BLOCK-OFF PLATE
OPENING PANEL
SEAL STRIP
OUTDOOR AIR HOOD TOP
UNIT FILTER RACK
ECONOMIZER CLIP HVAC UNIT
SCREEN RETAINER
SEAL STRIP
ASSEMBLED EXHAUST HOOD
OUTDOOR AIR HOOD SIDES
Fig. 26 Outdoor-Air Hood Assembly
Fig. 27 Completed Hood Assembly
OUTDOOR AIR INLET SCREENS
UNIT BASE
ECONOMIZER
ECONOMIZER REAR FLANGE
Fig. 28 Rear EconoMi$er Flange Installation
Fig. 29 EconoMi$er Installed
OAT
LEGEND
Outdoor-Air Thermostat
Fig. 30 EconoMi$er Wiring
16
Page 17
ECONOMI$ER
FAN 1
FAN 2
CAPACITOR 2 CAPACITOR 1
RELAY 2 RELAY 1
4-PIN CONNECTOR PLUG (HIGH VOLTAGE)
3-PIN CONNECTOR PLUG (LOW VOLTAGE)
CONTROLLER
OAT COM
OAH
-15 V RAT
COM
RAH
+15 V
(+)
CO
2
COM
CO
2
DAT
COM
REM POT
COM
LED
COM
BROWN VIOLET
WHITE
RED
BROWN
VIOLET WHITE
RED
CO
SUPPLY AIR
TEMPERATURE SENSOR
PINK
VIOLET
TEMP
TEMP
TEMP TEMP
COM OUT PWR
TEMP TEMP COM
OUT PWR
SENSOR
2
24
V+
COM VAC
Fig. 31 EconoMi$er Sensor Wiring
POWER EXHAUST SYSTEM (HIGH VOLTAGE)
OUTDOOR AIR SENSOR
RETURN AIR SENSOR
CONTROL BOX/BURNER ACCESS PANEL
INDOOR FAN MOTOR ACCESS PANEL AND BLOWER
Fig. 33 Typical Access Panel Locations
(Standard Efficiency Unit Shown)
RED
H1
(575 VAC)
HT01AH859
X4
SECONDARY
HANDY BOX
X2
230VAC
2 x 4 IN.
X3
TO FUSED
DISCONNECT
GRAY
H2
X1
OR
BLACK L1 BLUE L2
GREEN GND
RED YELH1BLU
(460 VAC)
HT01AH850
X4
SECONDARY
COMPRESSOR 1
CONTACTOR
11 2 1
23
13
CONNECTOR
L1
1
1
L2
22
GND
33
44
230 VAC
1 PHASE
H3
H2
X3
X2
230VAC
230VAC
4-PIN
PLUG
GREEN
GRAY
H4
X1
BLACK
BLUE
FIELD SUPPLIED WIRING
BROWN
C1
GREEN/ YELLOW
BROWN
C1
GREEN/ YELLOW
FAN 1
FAN 2
BLACK
BLACK
LT. BLUE
BLACK
BLUE
BLACK
LT. BLUE
BLACK
3
2
1
3
2
1
6
5
4
5
BLUE
B
9
8
7
9
6
8
4
7
R1
24 VAC
A
B
R2
24 VAC
A
3-PIN
CONNECTOR
PLUG
ORANGE
YELLOW
BROWN
1
2
3
Fig. 32 Wiring Diagram for Power Exhaust System
17
Page 18
SUPPLY AIR
Fig. 35 EconoMi$er Control Adjustment
Potentiometers (Factory Settings)
Fig. 36 Barometric Relief Capacity
TEMPERATURE SENSOR MOUNTING LOCATION
SUPPLY AIR TEMPERATURE SENSOR
Fig. 34 Supply-Air Sensor Placement
CO
Control Setup — If a CO2 sensor is not being used, pro-
2
ceed to the next section. If a CO
sensor is being used, perform
2
the following:
1. Determine the value at which you want the minimum po­sition of the dampers to begin opening to allow a greater amount of outdoor air to enter. The range is 800 to 1,400 ppm.
2. Locate the CO
SP (PPM) potentiometer and adjust to the
2
desired set point. See Fig. 35.
Mechanical Cooling Lockout
— Determine the outdoor-air temperature at which you want the mechanical cooling (com­pressors) to be disabled. Locate the mechanical cooling lockout (MECH CLG LOCKOUT) potentiometer. To disable this fea­ture, turn the potentiometer counterclockwise (CCW) to the OFF position. Otherwise, set the value between 10 and 60 F. Mechanical cooling will not operate when the outdoor air temperature is below this value. See Fig. 35.
Dry Bulb Cha ngeover Set Up
— Determine the dry bulb changeover set point from T able 3. The settings are A, B, C and D. Locate the ECON SP potentiometer and set the dry bulb changeover set point. See Fig. 35. When the OAT is above this set point, the damper is limited to minimum position setting.
Ventilation Air (Minimum Position Set Up)
— If ventilation air is not required, proceed to Step 5. If ventilation air is re­quired, perform the following:
1. The indoor fan must be on to set the ventilation air. Either put the thermostat in the continuous fan mode or jump er the R and G terminals at the rooftop unit connection board.
2. Locate the minimum position (MIN POS) potentiometer. Turn the potentiometer full CCW to fully close the out­door air dampers. Turn the potentiometer gradually clockwise (CW) to the desired position. See Fig. 35.
3. Replace the filter access panel. See Fig. 24. Ensure the fil­ter access panel slides along the tracks and is securely engaged.
4. Calculate the minimum airflow across the EconoMi$er. a. Calculate % of outside air using the following
formula. % Outdoor air through EconoMi$er
Mixture Temp –
% Outdoor air =
Return Air Temp Outdoor T emp –
Return Air Temp
b. Divide total CFM by percentage outdoor air, this
gives outdoor air vol ume in CFM.
5. Turn on base unit power.
NOTE: The EconoMi$er begins operation three mi nutes after power up.
Personal Injury Hazard.
Avoid possible injury by keep-
ing fingers away from damper blades.
6. See Fig. 36 for b arome tric reli ef d amper cha ract eristi cs.
Table 3 Changeover Set Points
SETTINGS ABCD Dry Bulb (°F) Single Enthalpy* (Btu/lb) Differential Temperature* (°F, Not Adjustable) Differential Enthalpy* (Btu/lb, Not Adjustable)
*Field-installed accessory.
73 69 66 63 27 25 24 22
2222 1111
If a potentiometer fails, its setting will default to the values
in Ta ble 4.
Table 4 Default Potentiometer Settings
POTENTIOMETER DEFAULT SETTING
SP (PPM)
CO
2
MECH CLG LOCKOUT ECON SP MIN POS (%)
1,000
47°
D
20
0.5
0.4
0.3
0.2
0.1
STATIC PRESSURE (IN.WG)
0
0
400
FLOW (CUBIC FEET/MINUTE)
800
1200
1600
2000
2400
18
Page 19
Step 9 Adjust Evaporator-Fan Speed
MOTOR MOUNTING PLATE NUTS
Fig. 37 Belt-Drive Motor Mounting
Fig. 38 Evaporator-Fan Pulley Adjustment
just evaporator-fan speed to meet jobsite conditions.
Tables 5A and 5B show fan rpm at motor pulley settings. Tables 6 and 7 show maximum amp draw of belt-drive motor. Table 8 shows motor nominal horsepower for eva porator-fan motors. Refer to Tables 8-25 for performance data. See Tables 26 and 27 for accessory and option static pressure drops.
BELT-DRIVE MOTORS — Fan motor pulleys are factory set for speed shown in Table 1. Check pulley alignment and belt tension prior to start-up.
NOTE: Before adjusting fan speed, make sure the new fan speed will provide an air temperature rise range as shown in T able 1.
T o change fan speed:
1. Shut off unit power supply, tag disconnect.
2. Loosen belt by loosening fan motor mounting nuts. See Fig. 37.
3. Loosen movable pulley flange setscrew (see Fig. 38).
4. Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. In­creasing fan speed increases load on motor. Do not ex­ceed maximum speed specified in Table 1.
5. Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See Table 1 for speed change for ea ch full turn of pulley flange.)
To align fan and motor pulleys, loosen fan pulley setscrews and slide fan pulley along fan shaft. Make an gular alignment by loosening motor from mounting.
T o adjust belt tension:
1. Loosen fan motor mounting nuts.
2. Slide motor mounting plate away from fan scroll for proper belt tension (1/2-in. deflection with 8 to 10 lbs of force) and tighten mounting nuts.
3. Adjust lock bolt and nut on mounting plate to secure mo­tor in fixed position.
Ad-
19
Page 20
Table 5A 48HJ Fan Rpm at Motor Pulley Setting With Standard Motor
STANDARD MOTOR*
UNIT
48HJ
004 005 006
(single-phase)
006 (3-phase)
and 007
0
1090 1055 1025 990 960 925 890 860 825 795 760 —— 1185 1150 1115 1080 1045 1015 980 945 910 875 840 ——
1460 1425 1385 1350 1315 1275 1240 1205 1165 1130 1095 1055 1020
1585 1540 1490 1445 1400 1350 1305 1260 1210 1165 1120 ——
1
/
2
11
*Approximate fan rpm shown (standard motor/drive).
Table 5B 48HJ Fan Rpm at Motor Pulley Setting With High Static Motor
HIGH-STATIC MOTOR
UNIT 48HJ
004 005 006 007
0
1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075 1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075 1685 1589 1557 1525 1493 1460 1428 1396 1364 1332 1300 —— 1685 1589 1557 1525 1493 1460 1428 1396 1364 1332 1300 ——
1
/
2
11
1
/
2
Table 6 Evaporator-Fan Motor Data Standard Motor
UNIT
48HJ
004
005
006
007
Bhp
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
Single 1.20 1000 208/230 5.4
Three 1.20 1000
Single 1.20 1000 208/230 5.4
Three 1.20 1000
Single 1.30 1650 208/230 9.7
Three 2.40 2120
Three 2.40 2120
LEGEND
Brake Horsepower
1
/
22
2
1
/
2
MOTOR PULLEY TURNS OPEN
MOTOR PULLEY TURNS OPEN
22
1
/
2
33
MAXIMUM
OPERATING WATTS*
*Extensive motor and electrical testing on these units ensures that
the full horsepower and watts range of the motors can be utilized with confidence. Using your fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor fail­ure. Unit warranty will not be affected.
33
1
/
2
1
/
2
44
44
1
/
2
1
/
2
UNIT VOLTAGE
208/230 5.4
460 2.4 575 2.4
208/230 5.4
460 2.4 575 2.4
208/230 6.4
460 2.9 575 2.9
208/230 6.4
460 2.9 575 2.9
55
55
1
/
2
1
/
2
MAXIMUM
AMP DRAW
6
6
UNIT
48HJ
004
005
006
007
LEGEND
Brake Horsepower
Bhp
Table 7 Evaporator-Fan Motor Data High-Static Motors
UNIT
PHASE
Three 2.40 2120
Three 2.40 2120
Three 2.90 2615
Three 2.90 2615
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
20
UNIT VOLTAGE
MAXIMUM
AMP DRAW
208/230 6.4
460 2.9 575 2.9
208/230 6.4
460 2.9 575 2.9
208/230 7.9
460 3.6 575 3.6
208/230 6.4
460 3.6 575 3.6
*Extensive motor and electrical testing on these units ensures that
the full horsepower and watts range of the motors can be utilized with confidence. Using your fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor fail­ure. Unit warranty will not be affected.
Page 21
Table 8 Motor Nominal Horsepower
UNIT 48HJ MOTOR NOMINAL HORSEPOWER
004 005
006
007
All 1.00 All 1.00
Single Phase 1.50
Three Phase 2.00
All 2.00
Table 9 Outdoor Sound Power (Total Unit)
UNIT 48HJ
004,005 006,007
ARI
RATING
(Bels)
63 125 250 500 1000 2000 4000 8000
7.6 55.9 66.0 64.0 66.2 68.4 64.5 61.7 57.3
8.0 59.1 68.9 68.7 71.9 74.0 68.9 65.7 59.0
OCTAVE BANDS
LEGEND
ARI Bels
Air Conditioning and Refrigeration Institute Sound Levels (1 bel = 10 decibels)
Table 10 48HJ004 Fan Performance — Vertical Discharge Units With Standard Motor
AIRFLOW
(Cfm)
900 581 0.12 673 0.18 736 0.22 805 0.25 865 0.29 911 0.34 1000 644 0.19 709 0.22 782 0.28 835 0.30 900 0.35 937 0.38 1100 687 0.22 746 0.26 806 0.30 867 0.35 929 0.40 964 0.40 1200 733 0.26 785 0.32 843 0.35 903 0.41 960 0.47 994 0.50 1300 754 0.29 826 0.38 891 0.43 942 0.48 991 0.53 1047 0.60 1400 810 0.35 868 0.45 937 0.51 984 0.57 1032 0.62 1067 0.67 1500 841 0.42 911 0.53 985 0.61 1029 0.66 1073 0.72 1109 0.77
AIRFLOW
(Cfm)
900 957 0.39 988 0.43 1039 0.47 1061 0.51 1083 0.54 1105 0.58 1000 992 0.44 1039 0.49 1061 0.55 1088 0.60 1111 0.66 1136 0.72 1100 1013 0.49 1068 0.55 1091 0.61 1109 0.66 1127 0.73 1145 0.80 1200 1045 0.56 1090 0.64 1109 0.68 1156 0.73 1203 0.81 1250 0.86 1300 1075 0.64 1122 0.70 1152 0.76 1190 0.82 1228 0.87 1266 0.94 1400 1110 0.73 1160 0.78 1181 0.83 1237 0.88 1293 0.94 1349 0.99 1500 1150 0.78 1190 0.84 1225 0.89 1271 0.95 1371 1.00 1383 1.05
0.1 0.2 0.3 0.4 0.5 0.6
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
0.7 0.8 0.9 1.0 1.1 1.2
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
Table 11 48HJ004 Fan Performance Vertical Discharge Units With High-Static Motor
AIRFLOW
(Cfm)
900 673 0.18 805 0.25 911 0.34 988 0.43 1061 0.47 1000 709 0.22 835 0.30 937 0.38 1039 0.49 1086 0.55 1100 746 0.28 867 0.35 964 0.40 1068 0.55 1109 0.61 1200 785 0.32 903 0.41 994 0.50 1090 0.64 1156 0.68 1300 826 0.38 942 0.48 1047 0.60 1122 0.70 1190 0.76 1400 868 0.45 984 0.57 1087 0.67 1160 0.84 1237 0.85 1500 911 0.53 1029 0.66 1109 0.77 1190 1.00 1271 0.95
AIRFLOW
(Cfm)
900 1105 0.57 1140 0.63 1170 0.68 1198 0.73 1224 0.77 1000 1136 0.63 1172 0.69 1203 0.75 1232 0.80 1258 0.86 1100 1145 0.67 1181 0.73 1213 0.80 1242 0.85 1268 0.91 1200 1210 0.74 1248 0.81 1282 0.88 1312 0.94 1340 1.01 1300 1266 0.84 1306 0.92 1341 1.00 1373 1.07 1402 1.14 1400 1349 0.93 1391 1.02 1429 1.11 1463 1.19 1494 1.26 1500 1363 1.05 1406 1.15 1465 1.25 1500 1.34 1532 1.43
LEGEND
Bhp Brake Horsepower Input to Fan FIOP Factory-Installed Option
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 2.)
2. Motor drive range is 760 to 1090 rpm for standard motor ; 1075 to 1455 rpm for high-static motor. All other rpms require a field-supplied drive.
3. Values include losses for filters, unit casing, and wet coils. See page 28 for accessory/FIOP static pressure information.
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
LEGEND AND NOTES FOR TABLES 10 AND 11
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
4. Maximum continuous bhp is 1.20 for standard motor, 2.40 for high-static motor. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on page 20 for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify.
6. Interpolation is permissible. Do not extrapolate.
21
Page 22
Table 12 48HJ005 Fan Performance — Vertical Discharge Units With Standard Motor
AIRFLOW
(Cfm)
1200 596 0.20 665 0.25 722 0.31 779 0.36 872 0.48 915 0.54 957 0.60 1300 1400 1500 1600 1700 1800 1900 2000
AIRFLOW
(Cfm)
1200 993 0.65 1028 0.69 1056 0.72 1083 0.74 1134 0.80 1185 0.88 1331 0.99 1300 1400 1500 1600 1700 1800 1900 2000
0.1 0.2 0.3 0.4 0.6 0.7 0.8
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
633 0.24 699 0.30 754 0.36 809 0.42 902 0.55 943 0.61 984 0.67 672 0.30 735 0.36 788 0.42 840 0.48 933 0.62 972 0.69 1011 0.75 711 0.35 770 0.42 822 0.49 873 0.55 963 0.69 1002 0.77 1041 0.84 751 0.42 835 0.49 871 0.56 907 0.63 993 0.77 1033 0.85 1072 0.93 791 0.49 873 0.57 907 0.65 941 0.72 1024 0.87 1064 0.96 1103 1.04 831 0.58 881 0.66 929 0.74 976 0.81 1057 0.97 1095 1.06 1132 1.14 872 0.67 919 0.75 965 0.84 1011 0.92 1091 1.08 1127 1.17 913 0.77 958 0.86 1002 0.95 1046 1.03
0.9 1.0 1.1 1.2 1.4 1.6 1.8
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1021 0.74 1058 0.80 1090 0.85 1121 0.89 1171 0.94 1219 1.00 1268 1.10
10490.8210860.8911200.9611531.0012101.1212571.17
10770.9211130.9911471.0611801.13
11071.0011411.0911741.17
11371.1211711.20 1167 1.23 1202 1.32 1233 1.41 1263 1.49 1323 1.67 1381 1.85 1436 2.02 1197 1.35 1232 1.45 1263 1.54 1294 1.63 1351 1.81 1408 2.00 1463 2.19 1229 1.48 1262 1.58 1294 1.68 1325 1.78 1362 1.97 1436 2.16 1489 2.36
EXTERNAL STATIC PRESSURE (in. wg)
1125 1.21 1160 1.30 1195 1.38
EXTERNAL STATIC PRESSURE (in. wg)
1203 1.29 1235 1.37 1296 1.53 1354 1.70 1407 1.84
1207 1.25 1269 1.40 1326 1.54 1376 1.65
1241 1.27 1295 1.37 1339 1.43
1162 1.25
1307 1.25
Table 13 48HJ005 Fan Performance Vertical Discharge Units With High-Static Motor
AIRFLOW
(Cfm)
1200 665 0.25 779 0.36 872 0.48 957 0.60 1028 0.69 1300 699 0.30 809 0.42 902 0.55 984 0.67 1058 0.80 1400 735 0.36 840 0.48 933 0.62 1011 0.75 1086 0.89 1500 770 0.42 873 0.55 963 0.69 1041 0.84 1113 0.99 1600 835 0.49 907 0.63 993 0.77 1072 0.93 1141 1.09 1700 873 0.57 941 0.72 1024 0.87 1103 1.04 1171 1.20 1800 881 0.66 976 0.81 1057 0.97 1132 1.14 1202 1.32 1900 919 0.75 1011 0.92 1091 1.08 1162 1.25 1232 1.45 2000 958 0.86 1046 1.03 1125 1.21 1195 1.38 1262 1.58
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
1200 1083 0.74 1134 0.80 1185 0.88 1331 0.99 1374 1.09 1300 1121 0.89 1171 0.94 1219 1.00 1268 1.10 1309 1.21 1400 1153 1.00 1210 1.12 1257 1.17 1307 1.25 1349 1.37 1500 1180 1.13 1241 1.27 1295 1.37 1339 1.43 1382 1.57 1600 1207 1.25 1269 1.40 1326 1.54 1376 1.65 1420 1.81 1700 1235 1.37 1296 1.53 1354 1.70 1407 1.84 1452 2.02 1800 1263 1.49 1323 1.67 1381 1.85 1436 2.02 1482 2.22 1900 1294 1.63 1351 1.81 1408 2.00 1463 2.19 —— 2000 1325 1.78 1362 1.97 1436 2.16 1489 2.36 ——
LEGEND
Bhp Brake Horsepower Input to Fan FIOP Factory-Installed Option
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 3.)
2. indicates field-supplied motor and drive required.
3. Motor drive range is 840 to 1185 r pm for standard motor; 1075 to 1455 rpm for high-static motor. All other rpms require a field-supplied drive.
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
LEGEND AND NOTES FOR TABLES 12 AND 13
EXTERNAL STATIC PRESSURE (in. wg)
4. Values include losses for filters, unit casing, and wet coils. See page 28 for accessory/FIOP static pressure information.
5. Maximum continuous bhp is 1.2 for standard motor, 2.4 for high-static motor. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Evapora­tor-Fan Motor Data tables on page 20 for additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify.
7. Interpolation is permissible. Do not extrapolate.
22
Page 23
Table 14 48HJ006 Fan Performance — Vertical Discharge Units With Standard Motor
Single-Phase Units
AIRFLOW
(Cfm)
1500 771 0.37 828 0.44 935 0.58 1027 0.73 1107 0.88 1185 1.04 1257 1.20 1600 816 0.45 869 0.51 968 0.66 1056 0.81 1127 0.97 1215 1.14 1700 902 0.61 940 0.60 1007 0.75 1094 0.91 1175 1.09 1245 1.26 1800 942 0.70 978 0.66 1063 0.82 1147 0.97 1248 1.20 1900 982 0.80 1023 0.78 1097 0.91 1175 1.11 1266 1.29 2000 1022 0.91 1068 0.90 1132 1.01 1218 1.23 2100 1063 0.99 1115 1.00 1180 1.17 2200 1104 1.13 1159 1.15 1214 1.28 2300 1130 1.26 1202 1.29 2400 2500
AIRFLOW
(Cfm)
1500 771 0.37 828 0.44 935 0.58 1027 0.73 1107 0.88 1185 1.04 1257 1.20 1330 1.38 1411 1.59 1600 816 0.45 869 0.51 968 0.66 1056 0.81 1127 0.97 1215 1.14 1286 1.31 1353 1.49 1421 1.68 1700 902 0.61 940 0.60 1007 0.75 1094 0.91 1175 1.09 1245 1.26 1315 1.44 1381 1.52 1443 1.69 1800 942 0.70 978 0.66 1063 0.82 1147 0.97 1248 1.20 1322 1.33 1395 1.46 1475 1.56 1542 1.71 1900 982 0.80 1023 0.78 1097 0.91 1175 1.11 1266 1.29 1356 1.47 1430 1.58 1504 1.69 1556 1.82 2000 1022 0.91 1068 0.90 1132 1.01 1218 1.23 1303 1.41 1397 1.52 1459 1.67 1532 1.82 1588 1.97 2100 1063 0.99 1115 1.00 1180 1.17 1261 1.35 1340 1.53 1428 1.66 1489 1.80 1567 1.99 1626 2.16 2200 1104 1.13 1159 1.15 1214 1.28 1310 1.52 1375 1.63 1459 1.80 1528 1.95 1603 2.17 1666 2.37 2300 1130 1.26 1202 1.29 1248 1.38 1358 1.69 1410 1.72 1488 1.93 1561 2.13 1637 2.35 2400 1174 1.37 1237 1.41 1292 1.55 1392 1.81 1460 1.90 1532 2.14 1584 2.28 2500 1201 1.48 1272 1.53 1335 1.71 1427 1.94 1518 2.16 1575 2.35
0.1 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1174 1.37 1237 1.41 1292 1.55 1392 1.81 1460 1.90 1532 2.14 1584 2.28 1671 2.55 1756 2.70 1201 1.48 1272 1.53 1335 1.71 1427 1.94 1518 2.16 1575 2.35 1633 2.53 1698 2.72 ——
0.1 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1248 1.38 1358 1.69 1410 1.72 1488 1.93 1561 2.13 1637 2.35 1710 2.54
EXTERNAL STATIC PRESSURE (in. wg)
1286 1.31 1353 1.49 1421 1.68
1322 1.33 1395 1.46 1475 1.56 1542 1.71
1261 1.35 1340 1.53 1428 1.66 1489 1.80 1567 1.99 1626 2.16 1310 1.52 1375 1.63 1459 1.80 1528 1.95 1603 2.17 1666 2.37
1303 1.41 1397 1.52 1459 1.67 1532 1.82 1588 1.97
1356 1.47 1430 1.58 1504 1.69 1556 1.82
1315 1.44 1381 1.52 1443 1.69
1330 1.38 1411 1.59
3-Phase Units
EXTERNAL STATIC PRESSURE (in. wg)
1633 2.53 1698 2.72 ——
1671 2.55 1756 2.70
1710 2.54
Table 15 48HJ006 Fan Performance Vertical Discharge Units With High-Static Motor
AIRFLOW
(Cfm)
1500 808 0.42 914 0.56 1001 0.69 1084 0.85 1168 1.01 1600 846 0.49 950 0.64 1034 0.78 1111 0.94 1194 1.11 1700 884 0.57 983 0.72 1068 0.88 1145 1.03 1218 1.21 1800 924 0.66 1018 0.82 1105 0.98 1179 1.13 1246 1.32 1900 965 0.76 1057 0.92 1143 1.10 1212 1.26 1280 1.43 2000 1008 0.87 1096 1.04 1177 1.22 1247 1.40 1300 1.57 2100 1051 0.99 1136 1.17 1210 1.35 1284 1.54 1347 1.72 2200 1095 1.12 1173 1.30 1245 1.49 1322 1.70 1380 1.89 2300 1140 1.26 1210 1.47 1284 1.65 1356 1.80 1418 2.07 2400 1185 1.41 1249 1.61 1323 1.80 1389 2.03 1456 2.26 2500 1231 1.57 1289 1.78 1363 2.00 1424 2.22 1500 2.45
AIRFLOW
(Cfm)
1500 1199 1.19 1126 1.46 1250 1.69 1301 1.91 1349 2.12 1600 1263 1.28 1275 1.49 1299 1.78 1352 2.01 1401 2.23 1700 1295 1.39 1351 1.58 1352 1.80 1407 2.03 1459 2.26 1800 1319 1.52 1389 1.71 1435 1.91 1494 2.15 1548 2.40 1900 1343 1.64 1415 1.80 1478 2.05 1538 2.31 1594 2.57 2000 1374 1.77 1438 1.99 1505 2.21 1566 2.49 1624 2.77 2100 1409 1.91 1465 2.14 1533 2.45 1596 2.77 2200 1442 2.08 1498 2.30 1568 2.64 2300 1475 2.26 1554 2.64 2400 1565 2.47 1649 2.89 2500
EGEND
L
Bhp Brake Horsepower Input to Fan FIOP Factory-Installed Option
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 3.)
2. indicates field-supplied motor and drive required.
3. Motor drive range is 1020 to 1460 rpm for single-phase standard motors, 1120 to 1585 for 3-phase standard motors, and 1300 to 1685 for high-static motors. All other rpms require a field-supplied drive.
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1596 2.95 1682 3.45 1760 3.96 ————
LEGEND AND NOTES FOR TABLES 14 AND 15
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
1627 3.03 1693 3.42 1755 3.81 1726 3.31 ————
4. Values include losses for filters, unit casing, and wet coils. See page 28 for accessory/FIOP static pressure information.
5. Maximum continuous bhp is 1.30 for single-phase standard motors, 2.40 for 3-phase standard motors, and 2.90 for high-static motors. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on page 20 for additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify.
7. Interpolation is permissible. Do not extrapolate.
1632 2.97 1691 3.31
1654 3.08
23
Page 24
Table 16 48HJ007 Fan Performance — Vertical Discharge Units With Standard Motor
AIRFLOW
(Cfm)
1800 942 0.70 978 0.66 1063 0.82 1147 0.97 1248 1.20 1322 1.33 1395 1.46 1475 1.56 1542 1.71 1900 982 0.80 1023 0.78 1097 0.91 1175 1.11 1266 1.29 1356 1.47 1430 1.58 1504 1.69 1556 1.82 2000 1022 0.91 1068 0.90 1132 1.01 1218 1.23 1303 1.41 1397 1.52 1459 1.67 1532 1.82 1588 1.97 2100 1063 0.99 1115 1.00 1180 1.17 1261 1.35 1340 1.53 1428 1.66 1489 1.80 1567 1.99 1626 2.16 2200 1104 1.13 1159 1.15 1214 1.28 1310 1.52 1375 1.63 1459 1.80 1528 1.95 1603 2.17 1666 2.37 2300 1130 1.26 1202 1.29 1248 1.38 1358 1.69 1410 1.72 1488 1.93 1561 2.13 1637 2.35 2400 1174 1.37 1237 1.41 1292 1.55 1392 1.81 1460 1.90 1532 2.14 1584 2.28 2500 1201 1.48 1272 1.53 1335 1.71 1427 1.94 1518 2.16 1575 2.35 2600 1246 1.62 1320 1.68 1368 1.81 1458 2.06 2700 1285 1.75 1361 1.82 1400 1.91 1490 2.19 2800 1304 1.87 1402 1.95 1439 2.08 2900 1345 2.07 1446 2.16 1477 2.16 3000 1378 2.26 1489 2.36
0.1 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1529 2.52 1598 2.73 ——————————
EXTERNAL STATIC PRESSURE (in. wg)
1562 2.42 1620 2.59 1675 2.77 ————
1543 2.43 1642 2.86 ———————— 1585 2.65 ——————————
1602 2.64 1666 2.85 ——————
1633 2.53 1698 2.72 ——
1671 2.55 1756 2.70
1710 2.54
Table 17 48HJ007 Fan Performance Vertical Discharge Units With High-Static Motor
AIRFLOW
(Cfm)
1800 978 0.66 1063 0.82 1147 0.97 1248 1.20 1322 1.33 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1023 0.78 1097 0.91 1175 1.11 1266 1.29 1356 1.47 1068 0.90 1132 1.01 1218 1.23 1303 1.41 1397 1.52 1115 1.00 1180 1.17 1261 1.35 1340 1.53 1428 1.66 1159 1.15 1214 1.28 1310 1.52 1375 1.63 1459 1.80 1202 1.29 1248 1.38 1358 1.69 1410 1.72 1488 1.93 1237 1.41 1292 1.55 1392 1.81 1460 1.90 1532 2.14 1272 1.53 1335 1.71 1427 1.94 1518 2.16 1575 2.35
1320 1.68 1368 1.81 1458 2.06 1562 2.42 1620 2.59 1361 1.82 1400 1.91 1490 2.19 1602 2.64 1666 2.85 1402 1.95 1439 2.08 1543 2.43 1642 2.86 1446 2.16 1477 2.16 1585 2.65 1489 2.36 1529 2.52 1598 2.73
EXTERNAL STATIC PRESSURE (in. wg)
1775 3.62 1753 3.58 —— 1767 3.69 ——
AIRFLOW
(Cfm)
1800 1395 1.46 1475 1.56 1542 1.71 1607 1.94 1667 2.16 1900 1430 1.58 1504 1.69 1556 1.82 1621 2.06 1682 2.30 2000 1459 1.67 1532 1.82 1588 1.97 1655 2.23 1717 2.49 2100 1489 1.80 1567 1.99 1626 2.16 1694 2.44 1758 2.73 2200 1528 1.95 1603 2.17 1666 2.37 1736 2.68 —— 2300 1561 2.13 1637 2.35 1710 2.54 1782 2.87 —— 2400 1584 2.28 1671 2.55 1756 2.70 ———— 2500 1633 2.53 1698 2.72 2600 1675 2.77 2700 2800 —————————— 2900 —————————— 3000 ——————————
LEGEND
Bhp Brake Horsepower Input to Fan FIOP Factory-Installed Option
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 3.)
2. indicates field-supplied motor and drive required.
3. Motor drive range is 1120 to 1585 rpm for standard motors, 1130 to 1685 rpm for high-static motors. All other rpms require a field-supplied drive.
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1768 3.26 ——————
1776 3.45 ————————
LEGEND AND NOTES FOR TABLES 16 AND 17
EXTERNAL STATIC PRESSURE (in. wg)
1779 3.13 ————
4. Values include losses for filters, unit casing, and wet coils. See page 28 for accessory/FIOP static pressure information.
5. Maximum continuous bhp is 2.40 for standard motors, 2.90 for high­static motors. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on page 20 for additional infor­mation.
6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify.
7. Interpolation is permissible. Do not extrapolate.
24
Page 25
Table 18 48HJ004 Fan Performance Horizontal Discharge Units With Standard Motor
AIRFLOW
(Cfm)
900 526 0.06 584 0.08 656 0.12 734 0.22 818 0.25 875 0.27 1000 570 0.09 627 0.13 738 0.19 800 0.26 848 0.29 895 0.31 1100 614 0.13 670 0.16 758 0.23 812 0.29 863 0.32 914 0.35 1200 658 0.16 710 0.23 780 0.28 840 0.32 889 0.36 938 0.40 1300 703 0.20 752 0.27 808 0.32 868 0.37 916 0.41 963 0.45 1400 725 0.29 776 0.31 845 0.38 891 0.42 937 0.47 983 0.51 1500 755 0.33 816 0.38 870 0.43 924 0.48 969 0.53 1014 0.58
AIRFLOW
(Cfm)
900 924 0.32 953 0.35 989 0.38 1028 0.42 1074 0.45 1120 0.50 1000 936 0.35 977 0.39 1020 0.44 1064 0.48 1124 0.52 1185 0.55 1100 960 0.39 1005 0.43 1052 0.49 1100 0.52 1163 0.56 1225 0.60 1200 988 0.45 1038 0.50 1076 0.53 1136 0.59 1201 0.61 1266 0.64 1300 1012 0.51 1061 0.56 1094 0.61 1172 0.65 1239 0.69 1306 0.72 1400 1027 0.56 1071 0.60 1108 0.67 1208 0.70 1278 0.75 1347 0.79 1500 1056 0.63 1097 0.68 1117 0.70 1245 0.74 1315 0.80 1385 0.85
0.1 0.2 0.3 0.4 0.5 0.6
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
0.7 0.8 0.9 1.0 1.1 1.2
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
Table 19 48HJ004 Fan Performance Horizontal Discharge Units With High-Static Motor
AIRFLOW
(Cfm)
900 584 0.08 734 0.22 875 0.27 953 0.36 1028 0.42 1000 627 0.13 800 0.26 895 0.31 977 0.39 1064 0.48 1100 670 0.16 812 0.29 914 0.35 1005 0.43 1100 0.52 1200 710 0.23 840 0.32 938 0.40 1038 0.50 1136 0.59 1300 752 0.27 868 0.37 963 0.45 1061 0.56 1172 0.65 1400 776 0.31 891 0.42 983 0.51 1071 0.60 1208 0.70 1500 816 0.38 924 0.48 1014 0.58 1097 0.68 1245 0.74
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
900 1120 0.54 1155 0.59 1186 0.64 1215 0.69 1240 0.73 1000 1185 0.60 1222 0.66 1255 0.71 1285 0.77 1312 0.82 1100 1225 0.65 1263 0.71 1298 0.77 1328 0.83 1357 0.88 1200 1266 0.72 1306 0.79 1341 0.86 1373 0.92 1402 0.98 1300 1306 0.79 1347 0.87 1383 0.94 1416 1.01 1446 1.07 1400 1347 0.87 1389 0.95 1427 1.03 1461 1.11 1492 1.18 1500 1385 0.96 1428 1.05 1467 1.14 1502 1.22 1534 1.30
LEGEND
Bhp Brake Horsepower Input to Fan FIOP Factory-Installed Option
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 3.)
2. Motor drive range is 760 to 1090 rpm for standard motors; 1075 to 1455 rpm for high-static motors. All other rpms require a field-supplied drive.
3. Values include losses for filters, unit casing, and wet coils. See page 28 for accessory/FIOP static pressure information.
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
LEGEND AND NOTES FOR TABLES 18 AND 19
EXTERNAL STATIC PRESSURE (in. wg)
4. Maximum continuous bhp is 1.20 for standard motors; 2.40 for high-static motors. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or pre­mature motor failure. Unit warranty will not be affected. See Evaporator­Fan Motor Data tables on page 20 for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify.
6. Interpolation is permissible. Do not extrapolate.
25
Page 26
Table 20 48HJ005 Fan Performance Horizontal Discharge Units With Standard Motor
AIRFLOW
(Cfm)
1200 569 0.18 641 0.23 701 0.29 761 0.34 859 0.46 901 0.52 943 0.58 1300 604 0.22 673 0.28 731 0.34 788 0.39 887 0.52 928 0.59 968 0.65 1400 640 0.27 705 0.33 761 0.39 817 0.45 914 0.59 955 0.66 996 0.72 1500 676 0.32 738 0.38 793 0.45 8470.51 9400.65 9820.7310240.81 1600 713 0.38 772 0.44 825 0.51 877 0.58 967 0.73 1009 0.81 1051 0.89 1700 750 0.45 806 0.51 857 0.59 908 0.66 997 0.81 1037 0.90 1077 1.01 1800 788 0.52 841 0.59 890 0.67 939 0.75 1026 0.91 1065 1.01 1104 1.07 1900 826 0.60 876 0.68 924 0.76 971 0.84 1056 1.01 1094 1.10 1132 1.18 2000 864 0.70 912 0.77 958 0.86 1004 0.94 1087 1.12
AIRFLOW
(Cfm)
1200 9870.6410300.7010680.7911060.8711340.981189 1.12 1300 10060.7110440.7710860.8411280.9111831.10 1400 10330.7910690.8611040.9311391.011218 1.14 1500 10600.8810950.9511291.0211621.09 1600 10871.0111231.0511561.1311851.20 1700 11141.0711511.15 1800 1141 1.17 1900 2000
0.1 0.2 0.3 0.4 0.6 0.7 0.8
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
0.9 1.0 1.1 1.2 1.4 1.6 1.8
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1178 1.26 1211 1.35 1243 1.43 1303 1.61 1359 1.78 1418 1.95 1168 1.28 1204 1.37 1238 1.47 1271 1.56 1330 1.74 1386 1.93 1439 2.11 1197 1.39 1231 1.48 1265 1.59 1298 1.69 1358 1.89 1413 2.08 1466 2.27
EXTERNAL STATIC PRESSURE (in. wg)
1125 1.21 1162 1.30
EXTERNAL STATIC PRESSURE (in. wg)
1226 1.23 1297 1.35
1228 1.24 1303 1.40 1343 1.60 1250 1.35 1319 1.51 1382 1.68
1183 1.23 1215 1.31 1276 1.48 1334 1.64 1398 1.80
1286 1.34 1320 1.48
1245 1.21
Table 21 48HJ005 Fan Performance Horizontal Discharge Units With High-Static Motor
AIRFLOW
(Cfm)
1200 641 0.23 761 0.34 859 0.46 943 0.58 1030 0.70 1300 673 0.28 788 0.39 887 0.52 968 0.65 1044 0.77 1400 705 0.33 817 0.45 914 0.59 996 0.72 1069 0.86 1500 738 0.38 847 0.51 940 0.65 1024 0.81 1095 0.95 1600 772 0.44 877 0.58 967 0.73 1051 0.89 1123 1.05 1700 806 0.51 908 0.66 997 0.81 1077 1.01 1151 1.15 1800 841 0.59 939 0.75 1026 0.91 1104 1.07 1178 1.26 1900 876 0.68 971 0.84 1056 1.01 1132 1.18 1204 1.37 2000 912 0.77 1004 0.94 1087 1.12 1162 1.30 1231 1.48
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
1200 1106 0.87 1134 0.98 1189 1.12 1245 1.21 1292 1.35 1300 1128 0.91 1183 1.10 1226 1.23 1297 1.35 1346 1.51 1400 1139 1.01 1218 1.14 1286 1.34 1320 1.48 1370 1.65 1500 1162 1.09 1228 1.24 1303 1.40 1343 1.60 1393 1.79 1600 1185 1.20 1250 1.35 1319 1.51 1382 1.68 1434 1.88 1700 1215 1.31 1276 1.48 1334 1.64 1398 1.80 1451 2.01 1800 1243 1.43 1303 1.61 1359 1.78 1418 1.95 1471 2.18 1900 1271 1.56 1330 1.74 1386 1.93 1439 2.11 1493 2.36 2000 1298 1.69 1358 1.89 1413 2.08 1466 2.27
LEGEND
Bhp Brake Horsepower Input to Fan FIOP Factory-Installed Option
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 3.)
2. indicates field-supplied motor and drive required.
3. Motor drive range is 840 to 1185 rpm for standard units; 1075 to 1455 rpm for high-static motors. All other rpms require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils. See page 28 for accessory/FIOP static pressure information.
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
LEGEND AND NOTES FOR TABLES 20 AND 21
EXTERNAL STATIC PRESSURE (in. wg)
5. Maximum continuous bhp is 1.20 for standard motors; 2.40 for high-static motors. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or pre­mature motor failure. Unit warranty will not be affected. See Evaporator­Fan Motor Data tables on page 20 for additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify.
7. Interpolation is permissible. Do not extrapolate.
15.21 2.54
26
Page 27
Table 22 48HJ006 Fan Performance Horizontal Discharge Units With Standard Motor
Single-Phase Units
AIRFLOW
(Cfm)
1500 741 0.38 798 0.43 895 0.54 990 0.67 1073 0.80 1154 0.95 1218 1.12 1600 783 0.45 838 0.51 933 0.63 1016 0.75 1102 0.90 1182 1.04 1251 1.20 1700 825 0.53 878 0.60 969 0.72 1049 0.84 1134 1.00 1206 1.14 1800 885 0.63 942 0.73 1047 0.90 1139 1.05 1193 1.14 1276 1.30 1900 928 0.73 982 0.83 1084 1.02 1160 1.11 1223 1.24 2000 971 0.84 1022 0.94 1121 1.12 1188 1.22 2100 1015 0.97 1063 1.10 1140 1.18 1196 1.27 2200 1060 1.10 1104 1.20 1159 1.23 2300 1104 1.25 1130 1.27 2400 1138 1.30 2500
AIRFLOW
(Cfm)
1500 741 0.38 798 0.43 895 0.54 990 0.67 1073 0.80 1154 0.95 1218 1.12 1295 1.36 1360 1.40 1600 783 0.45 838 0.51 933 0.63 1016 0.75 1102 0.90 1182 1.04 1251 1.20 1310 1.40 1385 1.49 1700 825 0.53 878 0.60 969 0.72 1049 0.84 1134 1.00 1206 1.14 1281 1.31 1342 1.48 1398 1.53 1800 885 0.63 942 0.73 1047 0.90 1139 1.05 1193 1.14 1276 1.30 1341 1.40 1413 1.55 1474 1.58 1900 928 0.73 982 0.83 1084 1.02 1160 1.11 1223 1.24 1301 1.38 1374 1.53 1437 1.62 1490 1.67 2000 971 0.84 1022 0.94 1121 1.12 1188 1.22 1254 1.36 1329 1.44 1396 1.66 1460 1.68 1509 1.77 2100 1015 0.97 1063 1.10 1140 1.18 1196 1.27 1272 1.45 1354 1.58 1413 1.75 1475 1.73 1529 1.92 2200 1060 1.10 1104 1.20 1159 1.23 1229 1.41 1306 1.53 1363 1.70 1434 1.81 1487 1.85 1554 2.07 2300 1104 1.25 1130 1.27 1196 1.37 1264 1.56 1340 1.66 1397 1.86 1459 1.88 1520 2.07 1576 2.24 2400 1138 1.30 1174 1.37 1245 1.57 1305 1.63 1373 1.84 1440 1.95 1502 2.06 1552 2.24 2500 1183 1.43 1201 1.50 1284 1.65 1338 1.75 1402 1.99 1469 2.04 1524 2.24
0.10.20.40.60.81.01.2 1.4 1.6
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Bhp Rpm Bhp Rpm Bhp Rpm
1183 1.43 1201 1.50 1284 1.65 1338 1.75 1402 1.99 1469 2.04 1524 2.24 1585 2.42 1638 2.60
0.10.20.40.60.81.01.2 1.4 1.6
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Bhp Rpm Bhp Rpm Bhp Rpm
1174 1.37 1245 1.57 1305 1.63 1373 1.84 1440 1.95 1502 2.06 1552 2.24 1604 2.42
1196 1.37 1264 1.56 1340 1.66 1397 1.86 1459 1.88 1520 2.07 1576 2.24
EXTERNAL STATIC PRESSURE (in. wg)
1295 1.36 1360 1.40
1281 1.31 1342 1.48 1398 1.53
1254 1.36 1329 1.44 1396 1.66 1460 1.68 1509 1.77
1229 1.41 1306 1.53 1363 1.70 1434 1.81 1487 1.85 1554 2.07
1272 1.45 1354 1.58 1413 1.75 1475 1.73 1529 1.92
1301 1.38 1374 1.53 1437 1.62 1490 1.67
1341 1.40 1413 1.55 1474 1.58
1310 1.40 1385 1.49
3-Phase Units
EXTERNAL STATIC PRESSURE (in. wg)
1585 2.42 1638 2.60
1604 2.42
Table 23 48HJ006 Fan Performance Horizontal Discharge Units With High-Static Motor
AIRFLOW
(Cfm)
1500 789 0.40 896 0.53 990 0.67 1072 0.83 1153 1.00 1600 826 0.46 931 0.61 1020 0.75 1101 0.91 1178 1.09 1700 865 0.54 966 0.69 1051 0.84 1133 1.01 1205 1.18 1800 905 0.62 1002 0.78 1084 0.93 1163 1.10 1235 1.29 1900 945 0.72 1037 0.88 1119 1.04 1194 1.21 1266 1.40 2000 984 0.82 1072 0.98 1154 1.16 1226 1.33 1297 1.53 2100 1024 0.93 1108 1.10 1192 1.29 1259 1.47 1327 1.66 2200 1064 1.05 1145 1.22 1225 1.43 1294 1.62 1359 1.80 2300 1104 1.18 1183 1.36 1260 1.57 1330 1.78 1392 1.97 2400 1145 1.32 1222 1.45 1296 1.73 1365 1.94 1426 2.15 2500 1186 1.48 1262 1.68 1331 1.89 1400 2.12 1461 2.34
AIRFLOW
(Cfm)
1500 1221 1.17 1256 1.30 1283 1.32 1303 1.22 1345 1.34 1600 1252 1.27 1311 1.45 1340 1.58 1330 1.61 1373 1.77 1700 1278 1.37 1345 1.57 1397 1.76 1424 1.89 1470 2.08 1800 1303 1.48 1371 1.69 1433 1.90 1480 2.09 1528 2.30 1900 1330 1.59 1396 1.80 1460 2.03 1517 2.25 1566 2.47 2000 1362 1.73 1422 1.94 1485 2.16 1544 2.40 1594 2.64 2100 1393 1.87 1452 2.08 1510 2.31 1570 2.55 1620 2.80 2200 1423 2.02 1483 2.24 1538 2.46 1594 2.71 2300 1454 2.18 1515 2.41 1571 2.64 1623 2.88 2400 1485 2.36 1544 2.59 1604 2.84 2500 1518 2.55 1574 2.78
LEGEND
Bhp Brake Horsepower Input to Fan FIOP Factory-Installed Option
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 3.)
2. indicates field-supplied motor and drive required.
3. Motor drive range is 1020 to 1460 rpm for single-phase standard units, 1120 to 1585 for 3-phase standard units, and 1300 to 1685 for high-static units. All other rpms require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils. See page 28 for accessory/FIOP static pressure information.
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
LEGEND AND NOTES FOR TABLES 22 AND 23
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
1633 3.03 1692 3.28 1746 3.61
5. Maximum continuous bhp is 1.30 for single-phase standard units, 2.40 for 3-phase standard motors, and 2.90 for high-static motors. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor fail­ure. Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on page 20 for additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify.
7. Interpolation is permissible. Do not extrapolate.
1645 2.98 1676 3.17
1657 3.07 1710 3.38
27
Page 28
Table 24 48HJ007 Fan Performance Horizontal Discharge Units With Standard Motor
AIRFLOW
(Cfm)
1800 885 0.63 942 0.73 1047 0.90 1139 1.05 1193 1.14 1276 1.30 1341 1.40 1413 1.55 1474 1.58 1900 928 0.73 982 0.83 1084 1.02 1160 1.11 1223 1.24 1301 1.38 1374 1.53 1437 1.62 1490 1.67 2000 971 0.84 1022 0.94 1121 1.12 1188 1.22 1254 1.36 1329 1.44 1396 1.66 1460 1.68 1509 1.77 2100 1015 0.97 1063 1.10 1140 1.18 1196 1.27 1272 1.45 1354 1.58 1413 1.75 1475 1.73 1529 1.92 2200 1060 1.10 1104 1.20 1159 1.23 1229 1.41 1306 1.53 1363 1.70 1434 1.81 1487 1.85 1554 2.07 2300 1104 1.25 1130 1.27 1196 1.37 1264 1.56 1340 1.66 1397 1.86 1459 1.88 1520 2.07 1576 2.24 2400 1138 1.30 1174 1.37 1245 1.57 1305 1.63 1373 1.84 1440 1.95 1502 2.06 1552 2.24 2500 1183 1.43 1201 1.50 1284 1.65 1338 1.75 1402 1.99 1469 2.04 1524 2.24 2600 1210 1.58 1243 1.67 1312 1.76 1366 1.96 1435 2.10 1494 2.19 1552 2.40 2700 1254 1.76 1285 1.80 1354 1.95 1403 2.14 1474 2.21 2800 1274 1.82 1304 1.85 1374 2.12 1459 2.25 2900 1318 1.95 1345 2.05 1412 2.32 3000 1362 2.20 1378 2.30 1451 2.40
0.1 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
EXTERNAL STATIC PRESSURE (in. wg)
1585 2.42 1638 2.60
1496 2.45 1529 2.61 1603 2.87 1671 3.03 ———— 1534 2.66 1560 2.81 1611 3.01 ——————
1514 2.42 1570 2.66 1624 2.85 1677 2.99 ——
1536 2.46 1584 2.61 1646 2.83 1706 2.97
1616 2.63 1671 2.80
1604 2.42
Table 25 48HJ007 Fan Performance Horizontal Discharge Units With High-Static Motor
AIRFLOW
(Cfm)
1800 942 0.73 1047 0.90 1139 1.05 1193 1.14 1276 1.30 1341 1.40 1413 1.55 1474 1.58 1522 1.74 1566 1.89 1900 982 0.83 1084 1.02 1160 1.11 1223 1.24 1301 1.38 1374 1.53 1437 1.62 1490 1.67 1538 1.84 1583 2.00 2000 10220.9411211.1211881.2212641.361329 1.44 1396 1.66 1460 1.68 1509 1.77 1558 1.95 1603 2.12 2100 10631.1011401.1811961.2712721.451354 1.58 1413 1.75 1475 1.73 1529 1.92 1578 2.11 1624 2.30 2200 1104 1.20 1159 1.23 1229 1.41 1306 1.53 1363 1.70 1434 1.81 1487 1.85 1554 2.07 1604 2.28 1651 2.48 2300 1130 1.27 1196 1.37 1264 1.56 1340 1.66 1397 1.86 1459 1.88 1520 2.07 1576 2.24 1627 2.46 1674 2.68 2400 1174 1.37 1245 1.57 1305 1.63 1373 1.84 1440 1.95 1502 2.06 1552 2.24 1604 2.42 1656 2.66 1704 2.90 2500 1201 1.50 1284 1.65 1338 1.75 1402 1.99 1469 2.04 1524 2.24 1585 2.42 1638 2.60 1691 2.86 2600 1246 1.67 1312 1.76 1366 1.96 1435 2.10 1494 2.19 1552 2.40 1616 2.63 1671 2.80 2700 1285 1.80 1354 1.95 1403 2.14 1474 2.21 1536 2.46 1584 2.61 1646 2.83 2800 1304 1.85 1374 2.12 1459 2.25 1514 2.42 1570 2.66 1624 2.85 2900 1345 2.05 1412 2.32 1496 2.54 1529 2.61 1603 2.87 3000 1378 2.30 1451 2.40 1534 2.66 1560 2.81
LEGEND
Bhp Brake Horsepower Input to Fan FIOP Factory-Installed Option
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 3.)
2. indicates field-supplied motor and drive required.
3. Motor drive range is 1120 to 1585 r pm for standard motors; 1300 to 1685 rpm for high-static motors. All other rpms require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils. See below for accessory/FIOP static pressure information.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
LEGEND AND NOTES FOR TABLES 24 AND 25
EXTERNAL STATIC PRESSURE (in. wg)
1611 3.01 1692 3.49 1764 3.95 ——————
1671 3.03 1742 3.43 ——————
5. Maximum continuous bhp is 2.4 for standard motors; 2.9 for high-static motors. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or pre­mature motor failure. Unit warranty will not be affected. See Evaporator­Fan Motor Data tables on page 20 for additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify.
7. Interpolation is permissible. Do not extrapolate.
1677 2.99 1739 3.33 1795 3.67 ——
1706 2.97 1761 3.27 ——
1726 3.09 1775 3.35
1740 3.12
Table 26 Economizer Static Pressure Drop
(in. wg)
UNIT
Durablade EconoMi$er
900 1200 1400 1600 1800 2000 2200 2400 2600
.05 .05 .05 .05 .05 .05 .05 .05 .05 .05 .10 .13 .17 .22 .27 .32 .39 .45
CFM
Table 27 FIOP MoistureMiser Dehumidification
Package Static Pressure Drop (in. wg)
UNIT SIZE
48HJ
E/F004 D/E/F005 D/E/F006 D/E/F007
LEGEND
FIOP
Factory-Installed Option
UNIT
NOMINAL TONS
3 .04 .07 .09 4 .07 .12 .15 5 .09 .15 .21 6 .12 .20 .28
CFM PER TON
300 400 500
28
Page 29
PRE-START-UP
Failure to observe the following warnings could result in serious personal injury:
1. Follow recognized safety practices and wear protec­tive goggles when checking or servicing refrigerant system.
2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is i n place and secured.
3. Do not remove compressor terminal cover until all electrical sources are disconnected.
4. Relieve all pressure from system before touching or disturbing anything inside terminal box if refrigerant leak is suspected around compressor terminals.
5. Never attempt to repair sol d ered connection while re­frigerant system is under pressure.
6. Do not use t orch to remove any component. System contains oil and refrigerant under pressure. To remove a component, wear protective goggles and proceed as follows:
a. Shut off electrical power and then gas to unit . b. Reclaim refrigerant to relieve all pressure from
system using both high- and low-pressure ports.
c. Cut component connection tubing with tubing
cutter and remove component from unit.
d. Carefully unsweat remaining tubing stubs
when necessary. Oi l can ignite when exposed to torch flame.
Proceed as follows to inspect and prepare the unit for initial
start-up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING, CAU­TION, and INFORMATION labels attached to, or shipped with, unit.
3. Make the following inspections: a. Inspect for shipping and handling damages such as
broken lines, loose parts, or disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections
and on unit base. Detecting oil generally indicates a refrigerant leak. Leak-test all refrigerant tubing connections using electronic leak detector, halide torch, or li quid-soap solution.
c. Inspect all field- and factory-wiring connections.
Be sure that connections are completed and tight. Be sure that wires are not in contact with refriger­ant tubing or sharp edges.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin comb .
4. V erify the following conditions: a. Make sure that condenser-fan blade are correctly
positioned in fan orifice. See Condenser-Fan Adjustment section on page 34 for more details.
b. Make sure that air filter(s) is in place. c. Make sure that condensate drain trap is filled with
water to ensure proper drainage.
d. Make sure that all tools and miscellaneous loose
parts have been removed.
START-UP
Unit Preparation
stalled in accordance with installat ion instructions and applica­ble codes.
Return-Air Filters
stalled in unit (see T able 1). Do not operate unit without return­air filters.
Outdoor-Air Inlet Screens
must be in place before operating unit.
Compressor Mounting
spring mounted. Do not loosen or remove compressor hold­down bolts.
Internal Wiring
unit control boxes. Tighten as required.
Refrigerant Service Ports
3 Schrader-type service ports: one on the suction line, one on the liquid line, and one on the compressor discharge line. Be sure that caps on the ports are tight. Two additional Schrader valves are located under the high-pressure and low-pressure switches, respectively.
HIGH FLOW REFRIGERANT VALVES — Two high flow valves are located on the hot ga s tube coming out of the com­pressor and the suction tube going into the compressor. Large black plastic caps identify these valves. These valves have O-rings inside which screw the cap onto a brass body to pre­vent leaks. No field acc ess to these valves is ava ilable at this time. Ensure the plastic caps remain on the valves and are tight or the possibility of refrigerant leakage could occur.
Compressor Rotation
compressors, it is impor tant to be cer tain comp ressor i s rotat ing in the proper direction. To determine whet her or not compres­sor is rotating in the proper direction:
1. Connect service gages to suction and discharge pressure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pres­sure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pres-
sure does not rise to normal levels:
1. Note that the evaporator fan (006 and 007 only) is proba­bly also rotating in the wrong direction.
2. Turn off power to the unit, tag disconnect.
3. Reverse any two of the unit power leads.
4. Reenergize to the compressor. Check pressures.
The suction and discharge pressure levels should now move
to their normal start-up levels.
Make sure that unit has been in-
Make sure correct filters are in-
Outdoor-air inlet screen
Compressors are internally
Check all electrical connections in
Each unit system has
On 3-phase units with scroll
29
Page 30
NOTE: When the compressor is rotating in the wrong direc­tion, the unit will make an elevated level of noise and will not provide cooling.
Cooling
Set space thermostat to OFF position. To start unit, turn on main power supply. Set system selector switch at COOL position and fan switch at AUTO. position. Adjust ther­mostat to a setting below room temperature. Compressor starts on closure of contactor.
Check unit charge. Refer to Refrigerant Charge section on
page 34.
Reset thermostat at a position above room temperature. Compressor will shut off. Evaporator fan will shut off after a 30-second delay.
TO SHUT OFF UNIT — Set system selector swit ch at OFF position. Resetting thermostat at a position above room tem­perature shuts unit off temporarily until space temperature ex­ceeds thermostat setting. Units are equipped with Cycle­LOC™ protection device. Unit shuts down on any safety trip, and indicator light on thermostat comes on. Check reason for all safety trips.
Compressor restart is accomplished by manual reset at the thermostat by turning the sele ctor switch to OFF and then to ON position.
Main Burners
Main burners are factory set and should
require no adjustment. TO CHECK ignition of main burners and heating controls,
move thermostat set point above room temperature and verify that the burners light and evaporator fan is energized. Check heating effect, then lower the thermostat setting below the room temperature and verify that the burners and evaporator fan turn off.
Refer to Table 28 for the correct orifice to use at high altitudes.
Table 28 Altitude Compensation*
72,000 AND 115,000
BTUH NOMINAL
ELEVATION
(ft)
0-2,000
2,000 3,000 4,000 5,000 6,000 7,000 8,000
9,000 10,000 11,000 12,000 13,000 14,000
*As the height above sea level increases, there is less oxygen per
cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes.
Orifices available through your local Carrier distributor.
INPUT
Natural
Gas
Orifice
Size
33 43 30 38 34 43 30 39 35 44 31 40 36 44 32 41 36 44 33 42 37 45 34 43 37 45 35 43 38 46 36 44 39 47 37 44 41 48 38 45 43 48 39 45 44 49 40 46 44 49 41 47 45 50 42 47
Liquid
Propane
Orifice
Size
150,000 BTUH
NOMINAL INPUT
Natural
Gas
Orifice
Size
Liquid
Propane
Orifice
Size
Heating
1. Purge gas supply line of air by opening union ahead of the gas valve. If gas odor is detected, tighten union and wait 5 minutes before proceeding.
2. Turn on electrical supply and manual gas valve.
3. Set system switch selector at HEAT position and fan switch at AUTO. or ON position. Set heating temperature lever above room temperature.
4. The induced-draft motor will start.
5. After a call for heating, the main burners should light within 5 seconds. If the burner does not light, then there is a 22-second delay before another 5-second try. If the burner still does not light, the time delay is repeated. If the burner does not light within 15 minutes, there is a lock­out. To reset the control, break the 24 v power to W1.
6. The evaporator-f an motor will turn on 45 seconds after burner ignition.
7. The evaporator-fan motor will turn off in 45 seconds after the thermostat temperature is satisfied.
8. Adjust airflow to obtain a temperature rise within the range specified on the unit nameplate.
NOTE: The default value for the evaporator-fan mot or on/off delay is 45 seconds. The Integrated Gas Unit Controller (IGC) modifies this value when abnormal limit switch cycles occur. Based upon unit operating conditions, the on delay can be reduced to 0 seconds and the off delay can be extended to 180 seconds. When one flash of the LED (light-emitting diode) is observed, the evaporator-fan on/off delay has been modified.
If the limit switch trips at the start of the heating cycle dur­ing the evaporator on delay, the time period of the on delay for the next cycle will be 5 seconds less than the time at which the switch tripped. (Example: If the limit swit ch trips at 30 sec­onds, the evaporator-fan on delay for the next cycle will oc cur at 25 seconds.) To prevent short-cycling, a 5-second reduction will only occur if a minimum of 10 minutes has e lapsed since the last call for heating.
The evaporator-fan off delay can also be modified. Once the call for heating has ended, there is a 10-minute period during which the modification can occur. If the limit switch trip s dur­ing this period, the evaporator-fan off delay will increase by 15 seconds. A maximum of 9 trips can occur, extending the evaporator-fan off delay to 180 seconds.
To restore the original defaul t value, reset the power t o the unit.
TO SHUT OFF UNIT — Set sy s te m s el ec to r s wi tc h a t o f f po ­sition. Resetting heating selector lever below room temperature will temporarily shut unit off until space temperature falls be­low thermostat setting.
Safety Relief
A soft-solder joint at the suction service Schrader port provides pressure relief under abnormal tempera­ture and pressure conditions.
Ventilation (Continuous Fan)
Set fan and system selector switches at ON and OFF positions, respectively. Evaporator fan operates continuously to provide constant air circulation. When the evaporator-fan sel ector switch is turned to the OFF position, there is a 30-second delay before the fan turns off.
Operating Sequence
COOLING, UNITS WITHOUT ECONOMIZER — When thermostat calls for cooling, terminals G and Y1 and the com­pressor contactor (C ) are ener gized . The indoo r (eva porator) fa n motor (IFM), compressor, and outdoor (condenser) fan motor (OFM) start. The OFM runs continuously while the unit is in cooling. When the thermostat is satisfied, C is deenergized and the compressor and OFM shut off. After a 30-second delay, the (IFM) shuts off. If the thermostat fan selector switch is in the ON position, the evaporator motor will run continuously.
30
Page 31
HEATING, UN ITS WI THOUT ECON OMIZ ER — When the thermostat calls for heating, terminal W1 is energized. The induced-draft motor is energized and the burner ignition se­quence begins. The indoor (evaporator) fan motor (IFM) is en­ergized 45 seconds after a flame is ignited. When additional heat is needed, W2 is energized and the high-fire solenoid on the main gas valve (MGV) is energized. When the thermostat is satisfied and W1 is deenergized, the IFM stops after a 45-second time-off delay .
COOLING, UNITS WITH DURABLADE ECONO­MIZER — When the outdoor-air temperature is above the out­door-air thermostat (OAT) setting and the room thermostat calls for cooling, compressor contactor is energized to start compressor and the outdoor (condenser) fan motor (OFM). The indoor (evaporator) fan motor (IFM) is energized and the economizer damper moves to the minimum position. After the thermostat is satisfied, there is a 30-second delay before the evaporator fan turns off. The damper then moves to the fully­closed position. When using continuous fan, the damper moves to the minimum position.
When the outdoor-air temperature is below the OAT setting and the thermostat calls for cooling, the economizer damper move to the minimum position. If the supply-air temperature is above 57 F, the damper continues to open until it reaches the fully-open position or until the supply-air temperature drops below 52 F .
When the supply-air temperature falls between 57 F and 52 F, the damper w ill remai n at a n interm ediate open position. If the supply-air temperature falls below 52 F, the damper will modulate closed until it reaches the minimum position or until the supply-air temperature is above 52 F. When the thermostat is satisfied, the damper moves to the fully closed position when using AUTO. fan or to the minimum position when using con­tinuous fan.
If the outdoor air alone cannot satisfy the cooling require ­ments of the conditioned space, economizer cooling is integrat­ed with mechanical cooling, providing two stages of cooling. Compressor and the condenser fan will be energized and the position of the economizer damper will be de termined by the supply-air temperature. When the second stage of cooling is satisfied, the compressor and OFM will be deenergized. The damper position will be determined by the supply-air tempera­ture. When the first stage of cooling is satisfied, there is a 30-second delay before the evaporator fan shuts off. The damp­er then moves to the fully closed position. When using a con­tinuous fan, the damper moves to the minimum position.
COOLING, UNITS WITH ECONOMI$ER — When the Outdoor Air Temperature (OAT) is above the ECON SP set point and the room thermostat calls for Stage 1 cool ing (R to G +Y1), the indoor-fan motor (IFM) is energized and the EconoMi$er damper modulates to minimum position. The compressor contactor is energized starting the compr essor and outdoor-fan motor (OFM). After the thermostat is satisfied, the damper modulates to the fully closed position when the IFM is deenergized.
When the OAT is below the ECON SP set point and the room thermostat calls for Stage 1 cooling (R to G + Y1), the EconoMi$er modulates to the minimum position when the IFM is energized. The EconoMi$er provides Stage 1 of cooling by modulating the return and outdoor air dampers to maintain a 55 F supply air set point. If the supply-air temperature (SAT) is greater than 57 F, the EconoMi$er modulates open, all owing a greater amount of outdoor air to enter the unit. If the SA T drops below 53 F, the outdoor-air damper modules closed to reduce the amount of outdoor air. When the SAT is between 53 and 57 F , the EconoMi$er maintains its position.
HEATING, UNIT S WI TH E CONOM IZ ER — W hen the ther ­mostat calls for heating, terminal W1 is energized. The
induced-draft motor is energized and the burner ignition se­quence begins. The indoor (evaporator) fan motor (IFM) is en­ergized 45 seconds after a flame is ignited and the damper moves to the minimum position. When additional heat is need­ed, W2 energized and the high-fire solenoid on the main gas valve (MGV) is energized. When the thermostat is satisfied and W1 is deenergized, the IFM stops after a 45-second time­off delay. The economizer damper then moves to the fully closed position. When using continuous fan, the damper will remain in the minimum position.
UNITS WITH MOISTUREMISER DEHUMIDIFICATION PACKAGE — When thermostat calls for cooling, terminals G and Y1 and the compressor contactor C1 is energized. The in­door (evaporator) fan motor (IFM), compressor, and outdoor (condenser) fan motor (OFM) start. The OFM runs continuous­ly while the unit is in cooling. As shipped from the factory, MoistureMiser dehumidification circuit is a lw ays energized. If MoistureMiser circuit modulation is desired, a field- installed, wall-mounted humidistat is required.
If the MoistureMiser humidistat is installed and calls for the MoistureMiser subcooler coil to operate, the humidistat inter­nal switch closes. This energizes and closes the liquid line sole­noid valve coil (LLSV) of the MoistureMiser circuit, forcing the hot liquid refrigerant of the liquid line to enter the subcooler coil (see Fig. 39). As the hot liquid passes through the subcool­er coil, it is exposed to the cold supply airflow coming off from the evaporator coil and the liquid is further cooled to a temper­ature approaching the evaporator coil leaving-air temperature. The state of the refrigerant leaving the subcooler coil is a high­ly subcooled liquid refrigerant. The liquid then enters a thermo­static expansion valve (TXV) where the liquid i s dropped to a lower pressure. The TXV does not have a pressure drop great enough to change the liquid to a 2-phase fluid. The TXV c an throttle the pressure drop of the liquid refrigerant and maintain proper conditions at the compressor suction valve over a wide range of operating conditions. The liquid then enters a second fixed restrictor expansion device for a second pre ssure drop t o a 2-phase fluid. The liquid proceeds to the evaporator coil at a temperature lower than normal cooling operation. This lower temperature is what increases the latent capacity of the rooftop. The 2-phase refrigerant passes through the evaporator and is changed into a vapor. The air passing over the evaporator coil will become colder than during normal operation as a result of the colder refrigerant temperatures. H owever, as it passes over the subcooler coil, the air will be warmed slightly.
As the refrigerant leaves the evaporator, the refrigerant passes a low-pressure switch in the suction line. This low­pressure switch will de-activate the MoistureMiser package when the suction pressure reaches 60 psig. The low-pressure switch is an added safety device to protect against evaporator coil freeze-up. The low-pressure switc h will only de-activate and open the liquid line solenoid valve in the MoistureMiser circuit. The compressors will continue to run as long as there is a call for cooling, regardless of the position of the low-pressure switch. The solenoid valve and the MoistureMiser package will be re-activated only when the call for cooling has bee n satis­fied, the low-pressure switch has closed, and a new call for cooling exists. The crankcase heaters on the scroll compress or provide additional protection for the compressor due to the ad­ditional refrigerant charge in the subcooler.
When the humidistat is satisfied, the humidistat internal switch opens cutting power to and opening the LLSV. The re­frigerant is routed back through the evaporator and the sub­cooler coil is removed from the refrigerant loop.
When the thermostat is satisfied, C1 is deenergized and the compressor and OFM shut off. After a 30-second delay, the IFM shuts off. If the thermostat fan selector switch is in the ON position, the IFM will run continuously.
31
Page 32
Fig. 39 MoistureMiser Option Operation
32
Page 33
SERVICE
Fig. 40 Cleaning Condenser Coil
Fig. 41 Propping Up Top Panel
Fig. 42 Separating Coil Sections
When servicing unit, shut off all electrical power to unit to avoid shock hazard or injury from rotating parts.
FAN MOTOR BEARINGS — Fan motor bearings are of the permanently lubricated type. No further lubrication is required. No lubrication of condenser- or evaporator-fan motors is required.
Cleaning
ing and cooling season and as operating conditions require. EVAPORATOR COIL
1. Turn unit power off, tag disconnect. Remove evaporator coil access panel.
2. If economizer or two-position damper is installed, re­move economizer by disconnecting Molex plug and re ­moving mounting screws. Refer to accessory economizer installation instructions or Optional Economizer sections on pages 12 and 15 for additional information.
3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dishwasher detergent in a pressurized spray canister. Wash both sides of coil and flush with clean water. For best results, back-flush toward return-air section to remove foreign material. Flush condensate pan after completion.
5. Reinstall economizer and filters.
6. Reconnect wiring.
7. Replace access panels.
CONDENSER COIL — Inspect coil monthly. Clean con­denser coil annually, and as required by location and outdoor air conditions.
One-Row Coil is not necessary to remove top panel.
2-Row Coils Clean coil as follows:
1. Turn off unit power, tag disconnecct.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. See Fig. 40. To hold top panel open, place coil corner post between top panel and center post. See Fig. 41.
4. Remove screws securing coil to compressor plate and compressor access panel.
5. Remove fastener holding coil sections together at return end of condenser coil. Carefully separate the outer coil section 3 to 4 in. from the inner coil section. See Fig. 42.
6. Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and de ­bris. Clean the outer surfaces with a stiff brush in the nor­mal manner.
7. Secure inner and outer coil rows together with a field­supplied fastener.
8. Reposition the outer coil section and remove the coil cor­ner post from between the top panel and center post. Re­install the coil corner post and replace all screws.
CONDENSATE DRAIN — Check and clean each year at start of cooling season. In winter, keep drain dry or protect against freeze-up.
FILTERS — Clean or replace at start of each heating and cool­ing season, or more often if operating conditions require it. Re­placement filters must be same dimensions as original filters.
OUTDOOR-AIR INLET SCREENS — Clean screen with steam or hot water and a mild detergent. Do not use disposable filters in place of screen.
Inspect unit interior at the beginning of heat-
— Wash coil with commercial coil cl eaner. It
Lubrication
COMPRESSORS — Each compressor is charged with correct amount of oil at the factory.
33
Page 34
Condenser-Fan Adjustment (Fig. 43)
Fig. 45 Cooling Charging Chart,
Standard 48HJ005
Fig. 44 Cooling Charging Chart,
Standard 48HJ004
Shut off unit power supply. Remove condenser-fan assembly (grille, motor, motor cover, and fan) and loosen fan hub setscrews. Adjust fan height as shown in Fig. 43. Tighten setscrews and replace condenser-fan assembly.
004-006 and 007 (208/230 V)
UNIT 48HJ FAN HEIGHT — “A” (in.)
007 (460 and 575 V)
2.75
3.50
Fig. 43 Condenser-Fan Adjustment
Economizer Adjustment
Refer to Optional Econo-
mizer sections on pages 12 and 15.
Evaporator Fan Belt Inspection
Check condition of evaporator belt or tension during heating and coo ling inspec­tions or as conditions require. Replace belt or adjust as necessary.
High-Pressure Switch
The high-pressure switch contains a Schrader core depressor, and is located on the com­pressor hot gas line. This switch opens at 428 psig and closes at 320 psig. No adjustments are necessary.
Loss-of-Charge Switch
The loss-of-charge switch contains a Schrader core depressor, and is located on the com­pressor liquid line. This switch opens at 7 psig and closes at 22 psig. No adjustments are necessary.
Freeze-Stat
The freeze-stat is a bimetal temperature­sensing switch that is located on the “hair-pin” end of the evap­orator coil. The switch protects the evaporator coil from freeze­up due to lack of airflow. The switch opens at 30 F and closes at 45 F . No adjustments are necessary.
Refrigerant Charge
Amount of refrigerant charge is listed on unit nameplate (also refer to Table 1). Refer to Carrier GTAC2-5 Charging, Recovery, Recycling, and Reclamation training manual and the following procedures.
Unit panels must be in place when unit is operating during charging procedure. Unit must operate a minimum of 10 mi n­utes before checking or adjusting referigerant charge.
An accurate superheat, thermocouple- or thermistor-type thermometer, and a gage manifold are required when using the superheat charging method for evaluating the unit charge.
Do not use mercury or small dial-type thermometers because they are not adequate for this type of measurement.
NO CH ARGE — Use standard evacuating techniques. After evacuating system, weigh in the specified amount of refriger­ant. (Refer to Table 1.)
LOW CH AR GE CO OL IN G — U sing Cooling Charging Charts, Fig. 44-47, vary refrigerant until the conditions of the charts are met. Note the charging charts are different from type normally used. Charts are based on charging the units to the correct superheat for the various operating conditions. Accu­rate pressure gage and temperature sensing device are required. Connect the pressure gage to the service port on the suction line. Mount the temperature sensing device on the suction line and insulate it so that outdoor ambient temperature does not af­fect the reading. Indoor-air cfm must be within the normal op­erating range of the unit.
MOISTUREMISER SYSTEM CHARGING — The system charge for units with the MoistureMiser option is greater than that of the standard unit alone. The charge for units wit h this option is indicated on the unit nameplate drawing. Also refer to Fig. 48-51. To charge systems using the MoistureMiser
Dehumidification package, fully evacuate, recover, and re­charge the system to the nameplate specified charge level.
To check or adjust refrigerant charge on systems using the
MoistureMiser Dehumidification package, charge per Fig. 48-
51. The subcooler MUST be energized to use the charging charts. The charts reference a liquid pressure (psig) and temperature at a point between the condenser coil and the subcooler coil. A tap is provided on the unit to measure liquid pressure entering the subcooler.
IMPORTANT: The subcooler charging charts (Fig. 48-
51) are to be used ONLY with units having the optional MoistureMiser subcooling option. DO NOT use standard charge (Fig. 44-47) for units with MoistureMiser option, and DO NOT use Fig. 48-51 for standar d units.
34
Page 35
suction temperature should be. If suction temperature is high, add refrigerant. If suction temperature is low, carefully recover some of the charge. Recheck the suction pressure as charge is adjusted.
Example (Fig. 46):
Outdoor Temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75 F
Suction Pressure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 psig
Suction T emperature should be. . . . . . . . . . . . . . . . . . . . . . .48 F
(Suction temperature may very ± 5 F.)
If a charging device is used, temperature and pressure read-
ings must be accomplished using the charging charts. TO USE COOLING CHARGING CHARTS, UNITS
WITH MOISTUREMISER DEHUMIDIFICTION PACK­AGE — Refer to charts (Fig. 48-51) to determine the proper leaving condenser pressure and temperature.
Example (Fig. 48):
Leaving Condenser Pressure. . . . . . . . . . . . . . . . . . . . . 250 psig
Leaving Condenser Temperature . . . . . . . . . . . . . . . . . . . 105 F
NOTE: The MoistureMiser subcooler MUST be energized to use the charging charts.
Fig. 46 Cooling Charging Chart,
Standard 48HJ006
Fig. 47 Cooling Charging Chart,
Standard 48HJ007
TO USE COOLING CHARGING CHART, STANDARD UNIT — Take the outdoor ambient temperature and read the suction pressure gage. Refer to charts to determine what
Flue Gas Passageways
tor box and upper areas of the heat exchanger:
1. Remove the combustion blower wheel and motor assem­bly according to directions in Combustion-Air Blower section below.
2. Remove the 3 screws holding the blower housing to the flue cover.
3. Remove the flue cover to inspect the heat exchanger.
4. Clean all surfaces as required using a wire brush.
Combustion-Air Blower
sure proper airflow and heating efficiency. Inspect blower wheel every fall and periodically during heating season. For the first heating season, inspect blower wheel bimonthly to deter­mine proper cleaning frequency.
To inspect blower wheel, remove draft hood and screen. Shine a flashlight into opening to inspect wheel. If cleaning is required, remove motor and wheel as follows:
1. Slide burner access panel out.
2. Remove the 5 s crews th at atta ch induced-draft motor as­sembly to the vestibule cover.
3. Slide the motor and blower wheel assembly out of the blower housing. The blower wheel can be cleaned at this point. If additional cleaning is required, continue with Steps 4 and 5.
4. To remove blower from the motor shaft, by remove 2 setscrews.
5. To remove motor, remove the 4 screws that hold the mo­tor to mounting plate. Remove the motor cooling fan by removing one setscrew. Then remove nuts that hold mo­tor to mounting plate.
6. To reinstall, reverse the procedure outlined above.
Limit Switch
Limit switch is located on the fan deck.
Remove blower access panel (Fig. 5).
To inspect the flue collec-
Clean periodically to en-
35
Page 36
CONDENSER FAN MUST BE OPERATING
CONDENSER FAN MUST BE OPERATING
Fig. 48 Cooling Charging Chart, 48HJ004 with
Optional MoistureMiser Dehumidification Package
CONDENSER FAN MUST BE OPERATING
Fig. 49 Cooling Charging Chart, 48HJ005 with
Optional MoistureMiser Dehumidification Package
Fig. 50 Cooling Charging Chart, 48HJ006 with
Optional MoistureMiser Dehumidification Package
CONDENSER FAN MUST BE OPERATING
Fig. 51 Cooling Charging Chart, 48HJ007 with
Optional MoistureMiser Dehumidification Package
36
Page 37
Burner Ignition
INDUCED­DRAFT MOTOR MOUNTING PLATE
INDUCED­DRAFT MOTOR
MANIFOLD PRESSURE TAP
VESTIBULE PLATE
FLUE EXHAUST
ROLLOUT SWITCH
BLOWER HOUSING
GAS VALV E
BURNER SECTION
Fig. 52 Burner Section Details
Fig. 53 Burner Tray Details
Unit is equipped with a direct spark ignition 100% lockout system. Integrated Gas Unit Controller (IGC) is located in the control box (Fig. 10). A single LED on the IGC provides a visual display of operational or sequential problems when the power supply is uninterrupted. The LED can be observed through the viewport. When a break in power occurs, the IGC will be reset (resulting in a loss of fault history) and the evaporator fan on/off times delay will be reset. During servicing, refer to the label on the control box cover or T able 29 for an explanation of LED error code descriptions.
If lockout occurs, unit may be reset by interrupting power
supply to unit for at least 5 seconds.
Table 29 LED Error Code Description*
LED INDICATION ERROR CODE DESCRIPTION
ON
OFF
1 Flash 2 Flashes 3 Flashes 4 Flashes 5 Flashes 6 Flashes 7 Flashes 8 Flashes
LEGEND
Light-Emitting Diode
LED
*A 3-second pause exists between LED error code flashes. If more
than one error code exists, all applicable codes will be displayed in numerical sequence.
Indicates a code that is not an error. The unit will continue to oper-
ate when this code is displayed.
IMPORTANT: Refer to Troubleshooting Tables 30-36 for addi­tional information.
Normal Operation Hardware Failure Evaporator Fan On/Off Delay Modified Limit Switch Fault Flame Sense Fault 4 Consecutive Limit Switch Faults Ignition Lockout Fault Induced-Draft Motor Fault Rollout Switch Fault Internal Control Fault
9. Remove the gas valve bracket.
10. Slide the burner tray out of the unit (Fig. 53).
11. T o reinstall, reverse the procedure outlined above.
Main Burners
At the beginning of each heating sea­son, inspect for deterioration or blockage due to corrosion or other causes. Observe the main burner flames and adjust, if necessary.
When servicing gas train, do not hit or plug orifice spuds.
REMOVAL AND REPLACEMENT OF GAS TRAIN (See Fig. 52 and 53)
1. Shut off manual gas valve.
2. Shut off power to unit, tag disconnect.
3. Remove compressor access panel.
4. Slide out burner compartment side panel.
5. Disconnect gas piping at unit gas valve.
6. Remove wires connected to gas valve. Mark each wire.
7. Remove induced-draft motor, ignitor, and sensor w ire s at the Integrated Gas Unit Controller (IGC).
8. Remove the 2 screws that attach the burner rack to the vestibule plate.
CLEANING AND ADJUSTMENT
1. Remove burner rack from unit as described above.
2. Inspect burners and, if dirty, remove burners from rack.
3. Using a soft brush, clean burners and cross-over port as required.
4. Adjust spark gap. See Fig. 54.
5. Reinstall burners on rack.
6. Reinstall burner rack as described above.
Replacement Parts
A complete list of replace­ment parts may be obtained from a ny Carrier distributo r upon request. Refer to Fig. 55 for a typ ical unit wiring schematic.
37
Page 38
48HJE004, 48HJD005-007 72,000 BTUH INPUT
LOW HEAT
48HJE005-007, 48HJF004 115,000 BTUH INPUT
MEDIUM AND HIGH HEAT
48HJF005-007 150,000 BTUH INPUT
Fig. 54 Spark Gap Adjustment
38
Page 39
SYMPTOM CAUSE REMEDY
Hardware failure. (LED OFF)
Fan ON/OFF delay modified (LED/FLASH)
Limit switch fault. (LED 2 flashes)
Flame sense fault. (LED 3 flashes)
4 consecutive limit switch faults. (LED 4 flashes)
Ignition lockout. (LED 5 flashes)
Induced-draft motor fault. (LED 6 flashes)
Rollout switch fault. (LED 7 flashes)
Internal control fault. (LED 8 flashes)
TROUBLESHOOTING
Refer to Tables 30-36 for troubleshooting details.
Table 30 LED Error Code Service Analysis
Loss of power to control module (IGC). Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and
High limit switch opens during heat exchanger warm-up period before fan-on delay expires.
Limit switch opens within three minutes after blower-off delay timing in Heating mode.
High temperature limit switch is open. Check the operation of the indoor (evaporator) fan motor.
The IGC sensed flame that should not be present.
Inadequate airflow to unit. Check operation of indoor (evaporator) fan motor and that supply-air
Unit unsuccessfully attempted ignition for 15 minutes.
IGC does not sense that induced-draft motor is operating.
Rollout switch has opened. Rollout switch will automatically reset, but IGC will continue to
Microprocessor has sensed an error in the software or hardware.
transformer. Units without a 24-v circuit breaker have an internal overload in the 24-v transformer. If the overload trips, allow 10 minutes for automatic reset.
Ensure unit is fired on rate and temperature rise is correct.
Ensure units external static pressure is within application guidelines.
Ensure that the supply-air temperature rise is in accordance with the range on the unit nameplate.
Reset unit. If problem persists, replace control board.
temperature rise agrees with range on unit nameplate information.
Check ignitor and flame sensor electrode spacing, gaps, etc. Ensure that flame sense and ignition wires are properly terminated. Verify that unit is obtaining proper amount of gas.
Check for proper voltage. If motor is operating, check the speed sensor plug/IGC Terminal J2 connection. Proper connection: PIN 1 White, PIN 2 Red, PIN 3 Black.
lock out unit. Check gas valve operation. Ensure that induced­draft blower wheel is properly secured to motor shaft. Reset unit at unit disconnect.
If error code is not cleared by resetting unit power, replace the IGC.
If the IGC must be replaced, be sure to ground yourself to dissi­pate any electrical charge that may be present before handling new control board. The IGC is sensitive to static electricity and may be damaged if the necessary precautions are not taken.
IMPORTANT: Refer to heating troubleshooting for additional heating section troubleshooting information.
LEGEND
IGC LED
Integrated Gas Unit Controller Light-Emitting Diode
39
Page 40
Table 31 Heating Service Analysis
PROBLEM CAUSE REMEDY
Burners will not ignite.
Inadequate heating.
Poor flame characteristics.
Burners will not turn off.
Misaligned spark electrodes. Check flame ignition and sensor electrode positioning. Adjust as
No gas at main burners. Check gas line for air purge as necessary. After purging gas line of
Water in gas line. Drain water and install drip leg to trap water. No power to furnace. Check power supply, fuses, wiring, and circuit breaker. No 24 v power supply to control circuit. Check transformer. Transformers with internal overcurrent protection
Miswired or loose connections. Check all wiring and wirenut connections. Burned-out heat anticipator in thermostat. Replace thermostat. Broken thermostat wires. Run continuity check. Replace wires, if necessary. Dirty air filter. Clean or replace filter as necessary. Gas input to unit too low. Check gas pressure at manifold. Clock gas meter for input. If too low,
Unit undersized for application. Replace with proper unit or add additional unit. Restricted airflow. Clean filter, replace filter, or remove any restrictions. Blower speed too low. Use high speed tap, increase fan speed, or install optional blower, as
Limit switch cycles main burners. Check rotation of blower, thermostat heat anticipator settings, and
Too much outdoor air. Adjust minimum position.
Incomplete combustion (lack of combustion air) results in:
Aldehyde odors, CO (carbon monoxide), sooting flame, or floating flame.
Unit is locked into Heating mode for a one minute minimum.
needed.
air, allow gas to dissipate for at least 5 minutes before attempting to relight unit.
Check gas valve.
require a cool-down period before resetting. Check 24-v circuit breaker; reset if necessary.
increase manifold pressure or replace with correct orifices.
suitable for individual units, Adjust pulley.
temperature rise of unit. Adjust as needed.
Check economizer operation. Check all screws around flue outlets and burner compartment.
Tighten as necessary. Cracked heat exchanger. Overfired unit reduce input, change orifices, or adjust gas line or
manifold pressure. Check vent for restriction. Clean as necessary. Check orifice to burner alignment. Wait until mandatory one minute time period has elapsed or reset
power to unit.
Table 32 Durablade Economizer Service Analysis
PROBLEM CAUSE REMEDY
Damper does not open.
Economizer operation limited to minimum position.
Damper does not close.
LEGEND
EC OAT SAT SW
Enthalpy Control Outdoor-Air Thermostat Supply-Air Thermostat Switch
Evaporator fan not on. Check wiring between G on connection board and evaporator-fan
No power to economizer motor. 1. Check that SW3 is making proper contact with the damper blade.
Economizer motor failure. If there is 24 vac power at the motor terminals, but motor is not operat-
OAT or EC set too high. 1. Set at correct temperature (3 F below indoor space temperature).
Check wiring of economizer relay packs. 1. Check continuity across relay R2 coil. If not connected, replace R2
Check SAT. If supply-air temperature is over 57 F, switch T2 should be closed. If
Incorrect wiring or wiring defects. 1. Check switches 2 and 4. If non-operational, replace.
Check SAT. If supply-air thermostat is below 52 F, switch T1 should be closed. If
Economizer motor failure. If there is 24 vac power at motor terminals, but motor is not operating,
contactor.
2. Check continually across R1 coil. If not connect, replace relay R1.
3. Check diode D18. If diode is not functioning properly, replace D18.
4. Check wiring in economizer relay pack. (See unit label diagram.)
ing, replace motor.
2. Check OAT or EC by setting set point above outdoor temperature or humidity level. If switch does not close, replace OAT or EC.
relay.
2. Check continuity across relay R3 coil. If not connected, replace R3 relay.
not, replace SAT.
2. Check diode D19. If diode D19 is not functioning properly, replace.
3. Check wiring on economizer and on economizer relay pack. (See unit label diagram.)
not, replace SAT.
replace the motor.
40
Page 41
Table 3 3 EconoMi$er Flash Code Identification
FLASH CODE CAUSE ACTION TAKEN BY ECONOMI$ER
Constant On Constant Off Continuous
Flash Flash One Flash Two Flash Three
Flash Four
Critical Fault
Flash Five
Flash Six
Flash Seven
Flash Eight
Flash Nine
Non-Critical Fault
Flash Ten
Normal operation Normal operation. No power No operation. CONFIG button pushed and held
between 3 and 9 seconds Control board fault System shutdown. Thermostat fault (i.e., Y2 without Y1) System shutdown until corrected. Actuator fault Revert to mechanical cooling only.
Supply air temperature sensor fault
Outdoor air temperature sensor fault
Outdoor air humidity sensor fault Continue operation with dry bulb or dry bulb differential switchover.
Return air temperature sensor fault
Return air humidity sensor fault
Carbon Dioxide (CO
Onboard adjustment potentiometer fault Continue operation with default potentiometer settings.
) sensor fault Continue operation without ventilation control.
2
Outdoor air damper is stroked fully open, then closed (automatic test procedure takes 3 minutes to complete).
Continue operation with damper at minimum position. Revert to mechanical cooling only.
Continue operation with damper at minimum position. Disable mechanical cooling lockout.
Continue operation with single enthalpy EconoMi$er switchover or dry bulb EconoMi$er switchover (without humidity sensor).
Continue operation with single enthalpy, differential dry bulb, or dry bulb EconoMi$er switchover.
Table 34 EconoMi$er Troubleshooting
PROBLEM POTENTIAL CAUSE REMEDY
Damper Does Not Open
EconoMi$er Operation Limited to Minimum Position
Damper Position Less than Minimum Position Set Poi nt
Damper Does Not Return to Minimum Position
Damper Does Not Close on Power Loss
LEGEND
IFM PL
Indoor Fan Motor Plug
Indoor (Evaporator) Fan is Off
No Power to EconoMi$er Controller
No Power to G Terminal If IFM is on, check to ensure 24 vac is present on G Terminal of the
Controller Fault If STATUS light is flashing one flash, the EconoMi$er controller is
Thermostat Fault If STATUS light is flashing two flashes, the EconoMi$er controller senses
Actuator Fault Check the wiring between the EconoMi$er controller and the actuator.
Minimum Position Set Incorrectly
EconoMi$er Changeover Set Point Set Too High or Too Low
Supply Air Temperature Sensor Faulty
Outdoor Air Temperature Sensor Faulty
Supply Air Low Limit Strategy Controlling
Ventilation Strategy
CO
2
Controlling
Damper Travel is Restricted
Check to ensure that 24 vac is present at Terminal C1 (Common Power) on the IFC (Indoor Evaporator Fan Contactor) or that 24 vac is present at the IFO (Indoor Evaporator Fan On) terminal. Check whether 24 vac is present at PL 6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is not present, check wiring (see unit label diagram).
Check proper thermostat connection to G on the connection board. Check to ensure that 24 vac is present across Terminals 24 VAC and
24 V COM on the EconoMi$er control. If 24 vac is not present, check wiring (see unit label diagram). If 24 vac is present, STATUS light should be on constantly.
EconoMi$er controller. If 24 vac is not present, check wiring (see unit label diagram).
experiencing a fault condition. Cycle power to the controller. If condition continues, replace the EconoMi$er controller.
the thermostat is wired incorrectly. Check wiring between the thermostat and the connection board in the electrical panel. The fault condition is caused by Y2 being energized before Y1.
Hold CONFIG button between 3 and 10 seconds to verify the actuators operation. (This process takes 3 minutes to complete.)
Verify that the MIN POS (%) is set greater than zero. Adjust MIN POS (%) to 100% to verify operation, and then set to correct setting.
Set at correct value. See Table 3.
If STATUS light is flashing 4 flashes, Supply Air Temperature Sensor is faulty. Check wiring or replace sensor.
If STATUS light is flashing 5 flashes, Outdoor Air Temperature Sensor is faulty. Check wiring or replace sensor.
The supply-air temperature is less than 45 F, causing the minimum position to be decreased. Refer to the Start-Up instructions. Verify correct setting of MIN POS (%). If correct, EconoMi$er is operating correctly.
If a CO2 sensor is being used, and the damper position is greater than minimum position, the ventilation control strategy is controlling. Refer to the Start-Up instructions. EconoMi$er is operating correctly.
Check to ensure the damper is not blocked.
41
Page 42
Table 35 MoistureMiser Dehumidification Subcooler Service Analysis
PROBLEM CAUSE REMEDY
Subcooler will not energize.
Subcooler will not deenergize. Low system capacity.
Loss of compressor superheat conditions with subcooler energized.
No power to control transformer from evaporator-fan motor.
No power from control transformer to liquid line solenoid valve
Liquid line solenoid valve will not operate. 1. Solenoid coil defective; replace.
Liquid line solenoid valve will not open. Valve is stuck closed; replace valve. Low refrigerant charge or frosted evaporator
coil.
Thermostatic expansion valve (TXV). 1. Check TXV bulb mounting, and secure tightly to
Check power source and evaporator-fan relay. Ensure all wire connections are tight.
1. Fuse open; check fuse. Ensure continuity of wiring.
2. Low-pressure switch open. Cycle unit off and allow low-pressure switch to reset. Replace switch if it will not close.
3. Transformer bad; check transformer.
2. Solenoid valve stuck open; replace.
1. Check charge amount. Charge per Fig. 47-51.
2. Evaporator coil frosted; check and replace low­pressure switch if necessary.
suction line.
2. Replace TXV if stuck open or closed.
42
Page 43
PROBLEM CAUSE REMEDY
Compressor and condenser fan will not start.
Compressor will not start but condenser fan runs.
Compressor cycles (other than normally satisfying thermostat).
Compressor operates continuously.
Excessive head pressure.
Head pressure too low.
Excessive suction pressure.
Suction pressure too low.
Evaporator fan will not shut off.
Table 36 Cooling Service Analysis
Power failure. Call power company. Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker. Defective thermostat, contactor, transformer,
or control relay. Insufficient line voltage. Determine cause and correct. Incorrect or faulty wiring. Check wiring diagram and rewire correctly. Thermostat setting too high. Lower thermostat setting below room temperature. Faulty wiring or loose connections in com-
pressor circuit. Compressor motor burned out, seized, or
internal overload open. Defective run/start capacitor, overload, start
relay. One leg of 3-phase power dead. Replace fuse or reset circuit breaker. Determine
Refrigerant overcharge or undercharge. Recover refrigerant, evacuate system, and
Defective compressor. Replace and determine cause. Insufficient line voltage. Determine cause and correct. Blocked condenser. Determine cause and correct. Defective run/start capacitor, overload, or
start relay. Defective thermostat. Replace thermostat. Faulty condenser-fan motor or capacitor. Replace. Restriction in refrigerant system. Locate restriction and remove. Dirty air filter. Replace filter. Unit undersized for load. Decrease load or increase unit size. Thermostat set too low. Reset thermostat. Low refrigerant charge. Locate leak, repair, and recharge. Leaking valves in compressor. Replace compressor. Air in system. Recover refrigerant, evacuate system, and
Condenser coil dirty or restricted. Clean coil or remove restriction. Dirty air filter. Replace filter. Dirty condenser coil. Clean coil. Refrigerant overcharged. Recover excess refrigerant. Air in system. Recover refrigerant, evacuate system, and
Condenser air restricted or air short-cycling. Determine cause and correct. Low refrigerant charge. Check for leaks, repair, and recharge. Compressor valves leaking. Replace compressor. Restriction in liquid tube. Remove restriction. High heat load. Check for source and eliminate. Compressor valves leaking. Replace compressor. Refrigerant overcharged. Recover excess refrigerant. Dirty air filter. Replace filter. Low refrigerant charge. Check for leaks, repair, and recharge. Metering device or low side restricted. Remove source of restriction. Insufficient evaporator airflow. Increase air quantity. Check filter and replace if
Temperature too low in conditioned area. Reset thermostat. Outdoor ambient below 25 F. Install low-ambient kit. Time off delay not finished. Wait for 30-second off delay.
Replace component.
Check wiring and repair or replace.
Determine cause. Replace compressor.
Determine cause and replace.
cause.
recharge to nameplate.
Determine cause and replace.
recharge.
recharge.
necessary.
43
Page 44
Fig. 55 Typical Wiring Schematic and Component Arrangement
(208/230 3-Phase Unit Shown)
44
Page 45
LEGEND AND NOTES FOR FIG. 55
AHA C CAP CC CLO COMP D EC ECON EPS EQUIP ER FPT FSS FU GND GVR HPS HS HV I IDM IFC IFM IGC LED LPS LS MGV MTR OAT OFM P
Adjustable Heat Anticipator Contactor, Compressor Capacitor Cooling Compensator Compressor Lockout Compressor Motor Diode Enthalpy Control Economizer Emergency Power Supply Equipment Economizer Relay Freeze-Protection Thermostat Filter-Status Switch Fuse Ground Gas Valve Relay High-Pressure Switch Hall-Effect Sensor High Voltage Ignitor Induced-Draft Motor Indoor (Evaporator) Fan Contactor Indoor (Evaporator) Fan Motor Integrated Gas Unit Controller Light-Emitting Diode Low-Pressure/Loss-of-Charge Switch Limit Switch Main Gas Valve Motor Outdoor-Air Thermostat Outdoor (Condenser) Fan Motor Plug
PL QT R RS SAT SEN SW1 SW2 SW3 SW4 TC TH TRAN
Plug Assembly Quadruple Terminal Relay Rollout Switch Supply-Air Thermostat Sensor Switch Fully Open Switch Fully Closed Switch Minimum Vent Position Switch Maximum Vent Position Thermostat-Cooling Thermostat-Heating Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked) Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring
To indicate common potential only. Not to represent wiring.
NOTES FOR FIG. 55
1. If any of the original wire furnished must be replaced, it must be replaced with Type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single-phasing conditions.
3. Thermostats: HH07AT170, 172 Subbase: HH93AZ176, 177, 178 and 179
4. Set heat anticipator at .14 amp for first stage and .14 amp for second stage.
5. Use copper conductors only.
6. TRAN is wired for 230 v unit. If unit is to be run with 208 v power supply, disconnect BLK wire from 230 v tap and connect to 208 v tap (RED). Insulate end of 230 v tap.
45
Page 46
Copyright 2000 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 1 a 6 a
PC 111 Catalog No. 534-767 Printed in U.S.A. Form 48HJ-18SI Pg 46 9-00 Replaces: 48HJ-17SI
Page 47
Page 48
START-UP CHECKLIST
(Remove and Store in Job File)
I. PRELIMINARY INFORMATION
MODEL NO.:________________________________ SERIAL NO.: ________________________________________ DATE:______________________________________ TECHNICIAN: _______________________________________
BUILDING LOCATION: _______________________________
II. PRE-START-UP (insert checkmark in box as each item is completed)
VERIFY THA T ALL PACKING MA TERIALS HAVE BEEN REMOVED FROM UNIT
REMOVE ALL SHIPPING HOLDDOWN BOL TS AND BRACKETS PER INSTALLATION INSTRUCTIONS
VERIFY THA T CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
CHECK GAS PIPING FO R LEAKS
CHECK THAT RETURN INDOOR-AIR FI LTER IS CLE AN AN D IN PLAC E
VERIFY THA T UNIT INSTALLA TION IS LEVEL
CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS
III. START-UP
ELECTRICAL
SUPPLY VOLTAGE L1-L2 L2-L3 L3-L1 COMPRESSOR AMPS L1 L2 L3 INDOOR-FAN AMPS L1 L2 L3
TEMPERATURES
OUTDOOR-AIR TEMPERA TURE DB RETURN-AIR TEMPERATURE
DB
WB
COOLING SUPPLY AIR GAS HEA T SUPPLY AIR
PRESSURES
GAS INLET PRESSURE IN. WG GAS MANIFOLD PRESSU RE IN. WG (HI FIRE) REFRIGERANT SUC TION PSIG REFRIGERANT DI SC HARGE PSIG
VERIFY REFRIGERANT CHARGE USING CHARGING T ABLES
VERIFY THAT 3-PHASE SCROLL COMPRESSOR ROTATING IN CORRECT DIRECTION
F
°
F
°
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
Copyright 2000 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 1 a 6 a
PC 111 Catalog No. 534-767 Printed in U.S.A. Form 48HJ-18SI Pg CL-1 9-00 Replaces: 48HJ-17SI
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
Loading...