Carrier 48HJ004-014 User Manual

Page 1
Single-Package Rooftop
Heating/Cooling Units
User’s Information Manual
48HJ004-014
NOTE TO INSTALLER:
This manual should be left with the equipment owner.
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other flam-
mable vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed
by a qualified installer, service agency or the gas supplier.
Improper installation, adjustment, alteration, ser­vice or maintenance can cause property damage, serious injury or death. Refer to this manual. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.
Before performing recommended maintenance, be sure main power switch to unit is turned off. Electrical shock could cause serious injury or death.
TO LIGHT UNIT
1. D o not turn off the electrical power to unit without first turning off the gas supply .
2. Before attempting to start the gas heating section, familiarize yourself with all the procedures that must be followed.
If you do not follow these instructions exactly, a fire or explosion may result. Property damage, injury, or loss of life could occur.
See Fig. 1A and 1B for location of gas valve. Refer to Fig. 2
while proceeding with the following steps.
Step 1 —
setting and set SYSTEM switch to HEA T or AUT O. position.
Step 2 —
Step 3 —
disconnect.
Step 4 —
Step 5 —
and wait 5 minutes.
Step 6 —
Step 7 —
Step 8 —
Step 9 —
Step 10 —
room temperature to start unit. The induced-draft combustion air fan will start. Main gas valve will open and main burners should ignite within 5 seconds. If the burners do not light, there is a 22-second delay before another 5-second try. If the burner still does not light, the time delay is repeated. If the burner does not light within 15 minutes, there is a lockout. To reset the con­trol, break the 24-v power to W1. Repeat Steps 1-10. If burners still do not light, call for service.
Step 11 —
to desired setting.
Set room thermostat to the lowest temperature
Close the manual gas valve. Turn off the electrical supply to the unit, tag
Remove the compressor access panel. Move the gas valve switch to the OFF position
Move the gas valve switch to the ON position. Replace the compressor access panel. Turn on the electrical supply to unit. Open the manual gas valve.
Set room thermostat selector slightly above
Set the temperature selector on room thermostat
Your rooftop com bination heating/cooling unit is equipped with an automatic direct spark ignition and induced-draft com­bustion blower.
Do not attempt to light by hand; serious injury or death may result.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 1 a 6 a
PC 111 Catalog No. 534-80017 Printed in U.S.A. Form 48HJ-2SO Pg 1 11-00 Replaces: 48GJ,HJ-1SO
If the main burners fail to light, or the blower fails to come on, shut down gas heating section and call your dealer for service. Failure to follow these requirements could result in serious injury or death.
Page 2
COMPRESSOR ACCESS PANEL
Fig. 1A — Gas Valve Location
(48HJ004-007)
Fig. 1B — Gas Valve Location
(48HJ008-014)
TO SHUT UNIT OFF
GAS VALVE
INTAKE LOUVERS
FLUE OPENING
Refer to Fig. 3 while proceeding with the following steps.
Step 1 —
Set room ther m ostat to lowest te m pe ra t u r e set ting
and set SYSTEM switc h to O FF.
Step 2 — Step 3 —
Close the external manual gas valve. Turn off the electrical power supply to unit;
install lockout tag.
Step 4 — Step 5 — Step 6 — Step 7 —
Remove the compressor access panel. Move the gas valve switch to the OFF position. Replace compressor access panel. If unit is being shut down because of a malfunc-
tion, call your dealer as soon as possible.
If unit is being shut down because the heating season has ended, restore electrical power to the unit and set thermostat to the COOL position to ensure operation of the cooling system during the cooling season.
Should overheating occur, or the gas supply fail to shut off, shut off the manual gas valve to the unit before shutting off the electrical supply.
Do not use this unit if any part has been under water. Imme­diately call a qualified service technician to inspect the unit and to replace any part of the control system and gas control that has been under water.
MAINTAINING YOUR UNIT
All maintenance should be handled by skilled, experienced personnel. Your Carri er service technician ca n help you set up a maintenance schedule.
For your safety, keep the area around the unit clear and free of combustible materials, gasoline, and other flammable liq­uids and vapors.
To ensure proper functioning of the unit, flow of combus­tion and ventilating air must not be obstructed f rom reaching the unit. Clearance of at least 3 ft on flue and condenser sides and 6 in. on all other sides is required.
1. D o not turn off the electrical power to unit without first turning off the gas supply .
2. N ever attempt to manually light the main burners on unit with a match, lighter, or any other flame. If the electric sparking device fails to light the main burners, refer to the following shutdown procedures. Call your dealer as soon as possible.
Failure to follow these procedures can result in fire, seri-
ous injury or death.
2
Page 3
O
F
F
ON
C
HI
M
R
E
P
L
A
C
E
S
C
R
E
W
L
O
STEP 1
MAIN
ON
OFF
LOCK-OUT
TAG
STEP 3STEP 2
2-STAGE GAS VALVE
W
E
O
R
C
L
S
E
C
A
R
L
P
M
C
HI
48HJD005,006* 48HJE004-006* 48HJF004-006* 48HJD007-014 48HJE007-014 48HJF007-014
E
ON
F
F
O
STEP 4
SINGLE-STAGE GAS
VALVE
WR
P3
C2
M1
ON
F
F
O
48HJD005,006 48HJE004-006 48HJF004-006 48HJG005,006 48HJH004-006 48HJK004-006 48HJL005,006 48HJM004-006 48HJN004-006
STEP 6
2-STAGE GAS VALVE
48HJD005,006* 48HJE004-006* 48HJF004-006* 48HJD007-014 48HJE007-014 48HJF007-014
STEP 7
STEP 5
SINGLE-STAGE GAS
VALVE
WR
P3
C2
M1
ON
F
F
O
48HJD005,006 48HJE004-006 48HJF004-006 48HJG005,006 48HJH004-006 48HJK004-006 48HJL005,006 48HJM004-006 48HJN004-006
*3-phase units only. Single-phase units only.
STEP 8
STEP 9
STEP 10
Fig. 2 — To Light Unit
3
Page 4
STEP 1
STEP 4
STEP 2
MAIN
OFF
STEP 3
ON
LOCK-OUT
TAG
2-STAGE GAS VALVE
W
E
O
R
C
L
S
E
C
A
R
L
P
M
C
HI
48HJD005,006* 48HJE004-006* 48HJF004-006* 48HJD007-014 48HJE007-014 48HJF007-014
*3-phase units only. Single-phase units only.
E
ON
F
F
O
STEP 5
SINGLE-STAGE GAS
VALVE
WR
P3
C2
M1
ON
F
F
O
48HJD005,006 48HJE004-006 48HJF004-006 48HJG005,006 48HJH004-006 48HJK004-006 48HJL005,006 48HJM004-006 48HJN004-006
STEP 6
STEP 7
Fig. 3 — To Shut Unit Off
4
Page 5
ROUTINE MAINTENANCE AND CARE
FILTER ACCESS PANEL
Fig. 4 — Typical Filter Access Panel Location
(48HJ008-014 Shown)
FOR THE EQUIPMENT OWNER
Consider the following information before maintaining or
servicing equipment:
Units with outdoor air capability have a cleanable filter for the outdoor air. This filter should be checked semi-annually and cleaned as necessary with steam or hot water and a mild detergent. Do not use throwaway filters in place of cleanable filters.
.
1. TU RN OFF GAS S UPPLY AND THEN ELECTRI­CAL POWER TO YOUR UNIT AND INSTALL LOCKOUT TAG BEFORE SERVICING OR PER­FORMING MAINTENANCE.
2. D o not turn off electrical power to this unit without first turning off the gas supply .
3. When re moving access panels or performing main te­nance functions inside your unit, be aware of sharp sheet metal parts and screws. Although special care has been taken to reduce sharp edges inside the unit, be extremely careful when handling parts or reaching into the unit.
4. Failure to follow these instructions could result in serious injury or death.
Air Filter(s) —
Air filter(s) should be checked at least every 3 or 4 weeks and changed or cleaned when necessary. Table 1 indicates the correct filter size for your unit. See Fig. 4 for filter access panel location.
1. Lift up and remove filter access panel.
2. While holding filter, tilt upper filter rack.
3. Remove filters by pulling up and out toward you from the track.
4. Inspect or replace filters.
5. Retur n filters t filter tracks. Note direction of airflow ar­rows on filter frame.
6. Reinstall filter access panel.
If you have difficulty in locating your air filter or if you have questions concerning proper filter maintenance, contact your dealer for instructions. When replacing your unit filters, always use the same size and type of filter that was originally supplied by the installer.
Never operate your unit without filters in place. Failure t o heed this warning may result in damage to the blower motor, compressor and/or evaporator coil. An accumula­tion of dust and lint on internal parts of your unit can cause loss of efficiency and, in some cases, fire that could result in serious injury or death.
Table 1 — Indoor-Air Filter Data for 48HJ
UNIT SIZE
48HJ
004-007 008,009 012,014
NOTE: Replacement filters should be UL (Underwriters Laborato-
ries) certified or equivalent.
INDOOR-AIR FILTERS
(Throwaway Fiberglass)
Quantity Size (in.)
2 16 x 25 x 2 4 16 x 25 x 2 4 20 x 20 x 2
5
Page 6
Heat Exchanger
NOTE: To ensure dependable and efficient heating operation, the heat exchanger should be checked by a qualified mainte­nance person before each heating season, and cleaned when necessary.
Combustion Area and Vent System —
bustion area and vent system should be visually inspected be­fore each heating season. The normal accumulation of dirt, soot, rust, and scale can result in loss of efficiency and improp­er performance if allowed to build up.
The com-
This checkout should not be attempted by anyone not hav­ing the required expertise and equipment to do the job properly.
Checking and/or cleaning the heat exchanger involves removing the gas controls assembly and the flue collector box cover. When finished, the gas controls must be reinstalled for proper operation. Also, the flue collector box cover must be replaced correctly so that a proper seal is main tained. Contact your dealer for the required periodic maintenance. At the beginning of each cooling/heating season and as conditions require.
Fans and Belts, and Fan Motor —
the condition of fan wheels and housings, belt tension and fan motor shaft bearings. No lubrication of condenser or evapora­tor fan bearings or motors is required or recommended.
Evaporator and Condenser Coils —
the coils should be done by qualified service personnel. Con­tact you dealer for the required annual maintenance.
Condensate Drain —
drain line should be checked and cleaned at the same time the cooling coils are checked by your dealer.
Compressor —
a normal charge of the correct type refrigeration-grade oil in them and should not require additional oil.
The drain pan and condensate
All compressors are factory supplied with
Periodically check
Cleaning of
Condenser Fan
If your unit makes any unusual or especially loud noises during heating, shut down the heating section and call your qualified Carrier service technician.
See Fig. 1A, 1B, and 5 and proceed as follows to inspect the
combustion area and power-venting system of your unit.
1. Turn off gas supply to your unit.
2. Turn off electrical power to your unit; install lockout tag.
3. Remove compressor access panel.
4. Usi ng a flashlight, carefully inspect the burner areas for dirt, soot, or scale.
If dirt, soot, rust or scale accumulations are found, call your dealer and do not operate your heating section.
5. When you have completed your inspection, follow the start-up procedures in this manual to restore your unit to operation.
6. Observe unit heating operation.
Components in heat section may be hot after unit has been started up. When observing flame, be careful not to get close to or touch heating components. Serious injury could result.
Do not poke sticks, screwdrivers, or any other object into revolving fan blades. Severe bodily injury could result.
The fan must be kept free of all obstructions to ensure prop-
er cooling. Contact your dealer for any required service.
Electrical Controls and Wiring —
not contact refrigerant tubing or sharp edges. Electrical con­trols are difficult to check without proper instrumentation. If in­adequate cooling is suspected, contact your qualified local dealer for service.
Ensure wires do
Watch the burner flame to see if it is bright blue. If you observe a suspected malfunction or that the burner flame is not bright blue, call your dealer.
7. Replace compressor access panel.
Unit Panels —
service on the unit, be sure all panels are securely faste ned in place to prevent rain from entering unit cabinet a nd to prevent disruption of the correct unit airflow pattern.
After performing any maintenance or
6
Page 7
Fig. 5 — Typical Heat Section Detail
REGULAR DEALER MAINTENANCE
In addition to the type of routine maintenance you might be willing to perform, your unit should be inspected regularly by a properly trained and qualified Carrier service technician. An inspection (preferably each heating/cooling season, but at least every year) should include the following:
1. Inspection of all flue product passages — including the burners, heat exchanger, and flue collector box.
2. Inspection of all combustion- and ventilation-air passages and openings.
3. Close inspection of all gas pipes leading to and inside your unit.
4. Inspect ion and if re quired, cleani ng of the condenser and evaporator coils.
5. Inspection, and if required, cleaning of the condensate drain pan.
6. Inspection and cleaning of blower wheel housing and motor.
7. Inspection of all supply- and return-air ducts for leaks, obstructions, and insulation integrity. Any problems found should be resolved at the time of inspection.
8. Inspect ion of the unit base for cracks, gaps, etc., which may cause a hazardous condition.
9. Inspection of the unit casing for signs of deterioration.
10. Inspection of all electrical wiring and components to ensure proper connection.
11. Inspection for leaks in the refrigerant circuit. Pressure­check to determine appropriate refrigerant charge
12. Inspection of fan w heels and housings, belt tension, and fan motor shaft bearings.
13. Ope rational check of the unit to determine working con­ditions. Repair or adjustment should be made at the time of inspection.
Your servicing dealer may offer an economical service contract that covers seasonal inspections. Ask f or further details.
Complete service instructions can be found in the unit
Installation, Start-Up and Service Instructions.
7
Page 8
BEFORE YOU CALL FOR SERVICE,
CHECK FOR PROBLEMS
THAT CAN BE EASILY SOLVED
If insufficient heating or cooling is suspected:
( ) Check for sufficient airflow. Check the air filter for dirt. Check for blocked return- or supply-air grilles. Be sure they are open and unobstructed. If these checks do not reveal the cause, call your servicing dealer.
If your unit is not operating at all, check the following list
for easy solutions: ( ) Check to be sure that your thermostat temperature selec-
tor is set above the indoor temperature during the heating sea­son, or below the indoor temperature during the cooling season. Be sure the SYSTEM switch in the proper HEAT or COOL position and not in the OFF position.
( ) Is the electrical supply switch ON? Are any fuses blown, or has the circuit breaker tripped?
( ) During the heating season, check the external manual shutoff valve. Is this lever parallel with the pipe, indicating that the valve is open? Or is the lever at the right angle, indicating that the valve is closed? If closed, has the gas been shut off for safety reasons? Otherwise, you may open the valve and follow the start-up procedures listed in this manual.
NOTE: Before proceeding with the next check, turn OFF the electrical power supply to the unit. Rem ove the control a ccess door.
( ) During the heating season, check the control switch on the gas valve. Is it in the ON position? If it is not, be sure it has not been turned off for the purpose of safety. If no safety haz­ards are present, follow the start-up procedures in this manual.
( ) If your unit still fails to operate, call your servicing dealer for troubleshooting and repairs. Specify the model and serial numbers of your unit. (Record them in this manual in the space provided.) If the dealer knows exactly which unit you have, he may be able to offer suggestions over the phone, or save valu­able time through knowledgeable preparation for the service call.
IN CASE OF TROUBLE
If, after performing the above checks, unit performance is
unsatisfactory, shut off t he unit and call your dealer . Dealer’s Name _____________________________________ T elephone No.______________________________________ Unit Model ________________________________________ Unit Serial Number _________________________________
Copyright 2000 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 1 a 6 a
PC 111 Catalog No. 534-80017 Printed in U.S.A. Form 48HJ-2SO Pg 8 11-00 Replaces: 48GJ,HJ-1SO
Loading...