Carrier 48HJ004-007, 48HE003-006 User Manual

48HJ004---007 48HE003---006 Single ---Package Rooftop Heating/Cooling Standard and Low NOx Units
Installation Instructions
CONTENTS
Page
INSTALLATION 1..................................
Step 1--Provide Unit Support 2.......................
ROOF CURB 2................................
SLAB MOUNT 2..............................
ALTERNATE UNIT SUPPORT 2.................
Step 2--Field Fabricate Ductwork 2...................
Step 3--Install External Trap for Condensate Drain 2.......
Step 4--Rig and Place Unit 2.........................
POSITIONING 4..............................
Step5—InstallFlueHood 4........................
Step 6 — Install Gas Piping 4........................
Step 7 — Make Electrical Connections 8................
FIELD POWER SUPPLY 8......................
FIELD CONTROL WIRING 8....................
HEAT ANTICIPATOR SETTINGS 8...............
Step 8 — Adjust Factory-Installed Options 17...........
COBRAENERGY RECOVERY UNITS 17.......
HUMIDI-MIZERADAPTIVE
DEHUMIDIFICATION SYSTEM 17..............
MANUAL OUTDOOR-AIR DAMPER 17..........
CONVENIENCE OUTLET 17....................
NOVAR CONTROLS 17........................
PREMIERLINKCONTROL 19.................
OPTIONAL ECONOMI$ER IV AND
ECONOMI$ER2 22............................
ECONOMI$ER IV STANDARD SENSORS 23......
ECONOMI$ER IV CONTROL MODES 24.........
Step 9 — Adjust Evaporator-Fan Speed 29..............
PRE--START--UP 45..................................
START--UP 45.......................................
SERVICE 50........................................
TROUBLESHOOTING 58.............................
START--UP CHECKLIST 63...........................
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
Recognize safety information. This is the safety--alert symbol
. When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on unit, turn off main power switch to unit and install lockout tag. Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate.
WARNING
1
!
FIRE, EXPLOSION HAZARD
Failure to follow this warning could death and/or property damage.
Disc onnect gas piping from unit when leak testing at pressure greater than psig will cause gas valve damage resulting in hazardous condition. If gas va lve is subjecte d to pressure greater than
1
/2psig, it must be replaced before use. When pressure testing field-supplied gas piping at pressures of less, a uni t connected to such piping must be i solated by manual l y closing the gas valve(s).
WARNING
1
/2psig. Pressures greater than1/
1
/2psig or
INSTALLATION
Unit is shipped in the vertical discharge configuration. To convert to horizontal discharge application, remove duct opening covers. Using the same screws, install covers on duct openings in
48HE,HJ
basepan of unit with insulation-side down. Seals around openings must be tight. (See Fig. 1.)
Fig. 1 --- Horizontal Conversion Panels
Step 1 Provide Unit Support
CURB
ROOF
Assemble and install accessory roof curb in accordance with instructions shipped with curb. (See Fig. 2.) Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb, not to the unit. If electric control power or gas service is to be routed through the basepan, attach the accessory thru-the-bottom service connections to the basepan in accordance with the accessory installation instructions. Connections must be installed before unit is set on roof curb.
IMPORTANT: The gasketing of the unit t o the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 2. Improperl y applied gasket can result in air leaks and poor unit performanc e.
Curb should be level. Unit leveling tolerances are shown in Fig.
3. This is necessary for unit drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
SLAB MOUNT (Horizontal Units Only)
Provide a level concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of
2
C06108
condenser-coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
ALTERNATE UNIT SUPPORT
When the curb or adapter cannot be used, support unit with sleeper rails using unit curb or adapter support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
Step 2 Field Fabricate Ductwork
Secure all ducts to roof curb and building structure on vertical discharge units. Do not connect ductwork to unit. For horizontal applications, field-supplied isolation flanges should be attached to horizontal discharge openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork. Cabinet return-air static pressure (a negative condition) shall not exceed
0.35 in. wg with economizer or 0.45 in. wg without economizer. These units are designed for a minimum continuous return-air
temperature in heating of 50_F (dry bulb), or an intermittent operation down to 45_F (dry bulb), such as when used with a night setback thermostat.
To operate at lower return-air temperatures, a field-supplied outdoor air temperature control must be used to initiate both stages of heat when the temperature is below 45_F. Indoor comfort may be compromised when these lower air temperatures are used with insufficient heating temperature rise.
Step 3 —Install External Trap for Condensate Drain
3
The unit’s bottom and side of the unit. Unit discharge connections do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications.
When using the standard side drain connection, ensure the plug (Red) in the alternate bottom connection is tight before installing the unit.
To use the bottom drain connection for a roof curb installation, relocate the factory-installed plug (Red) from the bottom connection to the side connection. The center drain plug looks like a star connection, however it can be removed with a socket drive extension. (See Fig. 4.) The piping for the condensate drain and external trap can be completed after the unit is in place.
All units must have an external trap for condensate drainage. Install a trap 4-in. deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection (
Step 4 Rig a nd Place Unit
Inspect unit for transportation damage, and file any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit, and rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 and 2 and Fig. 6 for additional information. Operating weight is shown in Table 1 and 2 and Fig. 6.
/4-in. condensate drain connections are located on the
1
/2-in.
3
/4in.). (See Fig. 5.)
2
1-4 [406]
DALT
DRAIN
HOLE
13/4
[44.5]
GAS POWER CONTROL
3
/4
[19] NPT
1
/2
[12.7] NPT
3
/4
[19] NPT
CONNECTOR
PKG. ACCY.
BC
CRBTMPWR001A01 CRBTMPWR002A01 1
CRBTMPWR003A01
1-9
11
[551]
/16
CRBTMPWR004A01
3
/4 [19] NPT
1
/4 [31.7]
3
/4 [19] NPT
1
/4 [31.7]
1
1
/2
[12.7]
ACCESSORY
POWER
1
/2
[12.7]
ROOF CURB
ACCESSORY
CRRFCURB001A01
CRRFCURB002A01
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance: 4 ft on each side.
1-2 [356]
2-0 [610]
A
48HJ004-007 48HE003-006
UNIT SIZE
7. Direction of airflow.
8. Connector packages CRBTMPWR001A01 and 002A01 are for thru-the-curb type gas. Packages CRBTMPWR003A01 and 004A01 are for thru-the-bottom type gas connections.
48HE,HJ
Fig. 2 --- Roof Curb Details
3
C06109
Lifting holes are provided in base rails as shown in Fig. 8 and 9. Refer to rigging instructions on unit.
!
WARNING
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal injury, death and property damage.
All panels must be in place when rigging and lifting.
positioning
Maintain clearance around and above unit to provide minimum distance from combustible materials, proper airflow, and service access. (See Fig. 7, 8 and 9.)
Position unit on roof curb so that the following clearances are maintained:
1
/4in. clearance between the roof curb and the base rail inside the front and rear, 0.0 in. clearance between the roof curb and the base rail inside on the duct end of the unit. This will result in the distance between the roof curb and the base rail
48HE,HJ
inside on the condenser end of the unit being approximately equal to Fig. 2, section C-C.
Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contaminated air.
Flue vent discharge must have a minimum horizontal clearance of 4 ft from electric and gas meters, gas regulators, and gas relief equipment.
After unit is in position, remove shipping materials and rigging skids.
Step 5 Install Flue Hood
Flue hood is shipped screwed to the burner compartment access panel. Remove from shipping location and, using screws provided, install flue hood in location shown in Fig. 8 and 9.
For units being installed in California Air Quality Management Districts which require NOx emissions of 40 nanograms/joule or less, a low NOx unit must be installed.
NOTE: Low NOx units are available for 3 to 5 ton units.
CONDENSATE PAN (SIDE VIEW)
HORIZONTAL DRAIN OUTLET
NOTE: Drain plug is shown in factory-installed position.
DRAIN PLUG
C06003
Fig. 4 --- Condensate Drain Pan
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B B-C A-C
0.5 1.0 1.0
C06110
Fig. 3 --- Unit Leveling Tolerances
Be sure that unit is installed such that snow will not block the combustion intake or flue outlet.
Unit may be installed directly on wood flooring or on Class A, B, or C roof-covering material when roof curb is used.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Locate mechanical draft system flue assembly at least 48 in. from an adjacent building or combustible material. When unit is located adjacent to public walkways, flue assembly must be at least 7 ft above grade.
NOTE: When unit is equipped with an accessory flue discharge deflector, allowable clearance is 18 inches.
Flue gas can deteriorate building materials. Orient unit such that flue gas will not affect building materials.
Adequate combustion-air space must be provided for proper operation of this equipment. Be sure that installation complies with all local codes and Section 5.3, Air for Combustion and Ventilation, NFGC (National Fuel Gas Code), ANSI (American National Standards Institute) Z223.1-1984 and addendum Z223.1a-1987. In Canada, installation must be in accordance with the CAN1.B149.1 and CAN1.B149.2 installation codes for gas burning appliances.
NOTE: Trap should be deep enough to offset maximum unit static difference. A 4-in. trap is recommended.
C06004
Fig. 5 --- Condensate Drain Piping Details
Step 6 Install Gas Piping
Unit is equipped for use with type of gas shown on nameplate. Refer to local building codes, or in the absence of local codes, to ANSI Z223.1-1984 and addendum Z223.1A-1987 entitled National Fuel Gas Code. In Canada, installation must be in accordance with the CAN1.B149.1 and CAN1.B149.2 installation codes for gas burning appliances.
For natural gas applications, gas pressure at unit gas connection must not be less than 4 in. wg or greater than 13 in. wg while the unit is operating. On 48HJ005-007 high-heat units, the gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13 in. wg while the unit is operating. For propane applications, the gas pressure must not be less than 5 in. wg or greater than 13 in. wg at the unit connection.
Size gas supply piping for 0.5 in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connection.
4
Fig. 6 --- Rigging Details
C06111
UNIT
48HE
003 530 240 73.69 1872 35.50 902 33.31 847 004 540 245 73.69 1872 35.50 902 33.31 847 005 560 254 73.69 1872 35.50 902 33.31 847 006 635 288 73.69 1872 35.50 902 33.31 847
UNIT
48HJ
004 530 240 73.69 1872 35.50 902 33.31 847 005 540 245 73.69 1872 35.50 902 33.31 847 006 560 254 73.69 1872 35.50 902 33.31 847 007 635 288 73.69 1872 35.50 902 33.31 847
Fig. 7 --- Roof Curb Alignment
Support gas piping as shown in the table in Fig. 11. For example,
3
/4-in. gas pipe must have one field-fabricated support beam
a every 8 ft. Therefore, an 18-ft long gas pipe would have a minimum of 3 support beams, and a 48-ft long pipe would have a minimum of 6 support beams.
OPERATING
WEIGHT
lb kg in. mm in. mm in. mm
OPERATING
WEIGHT
lb kg in. mm in. mm in. mm
C06208
DIMENSIONS
“A” “B” “C”
DIMENSIONS
“A” “B” “C”
!
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal injury, death and property damage.
All panels must be in place when rigging and lifting.
See Fig. 11 for typical pipe guide and locations of external manual gas shutoff valve.
NOTE: If accessory thru-the-bottom connections and roof curb are used, refer to the Thru-the-Bottom Accessory Installation Instructions for information on power wiring and gas connection piping. The power wiring, control wiring and gas piping can be routed through field-drilled holes in the basepan. The basepan is specially designed and dimpled for drilling the access connection holes.
!
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
When connecting the gas line to the unit gas valve, the installer MUST use a backup wrench to prevent damage to the valve.
WARNING
WARNING
48HE,HJ
5
C06112
48HE,HJ
Fig. 8 --- 48HJ004--007 Base Unit Dimensions
6
C06113
48HE,HJ
Fig. 9 --- 48HE003--006 Base Unit Dimensions
7
Fig. 10 --- Flue Hood Details
*
48HE,HJ
LEGEND
NFGC — National Fuel Gas Code
Field supplied.
NOTE: Follow all local codes.
SPACING OF SUPPORTS
STEEL PIPE
NOMINAL DIAMETER (in.)
1
/
3
/4or 1
1
/4or larger
1
2
Fig. 11 --- Gas Piping Guide (With Accessory
Thru--the--Curb Service Connections)
Step 7 Make Electrical Connections
!
WARNING
ELECTRICAL SHOCK HAZARD
Failur e to follow this warning could result in personal injury or death.
Unit cabinet must have an uninterrupt ed, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should oc cur . This gr ound may consist of el ectrical wire connec ted to unit ground lug i n control compartme nt, or conduit approved for electr i cal ground whe n install ed in accordance with NEC (National Electrical Code), ANSI/NFPA (National Fire Protection Association), latest edition, and local electrical codes. Do
not use gas piping as an electr i cal ground.
SPACING OF SUPPORTS
X DIMENSION (ft)
10
field power supply
All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by moving the black wire from the 230-v terminal on the transformer and connecting it to the 200-v terminal from the transformer.
Refer to unit label diagram for additional information. Pigtails are provided for field service. Use factory-supplied splices or UL (Underwriters’ Laboratories) approved copper connector.
When installing units, provide a disconnect per NEC. All field wiring must comply with NEC and local
requirements.
C06114
Install conduit through side panel openings indicated in Fig. 8. Route power lines through connector to terminal connections as shown in Fig. 12.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (also see Tables 3 and
4). On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in Tables 3 and 4, Note 3 to determine the percent voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.
NOTE: If accessory thru-the-bottom connections and roof curb are used, refer to the Thru-the-Bottom Accessory Installation Instructions for information on power wiring and gas connection piping. The power wiring, control wiring and gas piping can be routed through field-drilled holes in the basepan. The basepan is specially designed and dimpled for drilling the access connection holes.(SeeFig.2.)
field control
wiring
Install a Carrier-approved accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned
6 8
C06115
space to sense average temperature in accordance with thermostat installation instructions.
Route thermostat cable or equivalent single leads of colored wire from subbase terminals through connector on unit to low-voltage connections (shown in Fig. 13 and 14).
Connect thermostat wires to matching screw terminals of low-voltage connection board. (See Fig. 13 and 14.)
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gauge) insulated wire (35_Cminimum).For50to75ft,use no. 16 AWG insulated wire (35_C minimum). For over 75 ft, use no. 14 AWG insulated wire (35_C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.
Pass the control wires through the hole provided in the corner post; then feed wires through the raceway built into the corner post to the 24-v barrier located on the left side of the control box. (See Fig. 15). The raceway provides the UL required clearance between high and low-voltage wiring.
heat anticipator
settings
Set heat anticipator settings at 0.14 amp for first stage and 0.14 for second stage heating, when available.
8
Table 1—Physical Data 48HJ
BASE UNIT 48HJ HJE/F/H/K/M/N004 HJD/E/F/G/H/K/L/M/N005 HJD/E/F/G/H/K/L/M/N006 HJD/E/F007 NOMINAL CAPACITY OPERATING WEIGHT (lb)
Unit Humidi-MiZerAdaptive Dehumidification System EconoMi$er IV Roof Cur b
COMPRESSOR
Quantity Oil (oz)
REFRIGERANT TYPE
Expansion Device Operating Charge (lb-oz)
Standard Unit Unit With Humidi-Mizer Adaptive Dehu midification System
CONDENSER FAN
Quantity...Diameter (in.) Nominal C f m Motor Hp...Rpm Watts Input (Total)
CONDENSER COIL
Rows...Fins/in. Tot a l Fa ce A r e a (s q f t )
EVAPORATOR COIL
Standard Unit
Rows...Fins/in. Tot a l Fa ce A r e a (s q f t )
Unit with Humidi-Mizer Adaptive Dehumidification System
Rows...Fins/in. Tot a l Fa ce A r e a (s q f t )
EVAPORATOR FAN
Quantity...Size (in.) Nominal C f m Maximum Continuous Bhp Std
Hi-Static
Motor RPM Std
Hi-Static
Motor Frame Size Std
Hi-Static
Fan Rpm Ran ge Std
Hi-Static
Motor Bearing Type Maximum Fan Rpm Motor Pulley Pitch Diameter A/B (in.)
Std
Hi-Static
Nominal Motor Shaft Diameter (in.) Std
Hi-Static
Fan Pulley Pitch Diameter (in.) Std
Hi-Static
Belt — Type...Length (in.) Std
Hi-Static
Pulley Center Line Distance (in.) Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full
Turns from Closed Position
Std
Hi-Static
Std
Hi-Static
Factory Setting — Full Turns Open Std
Hi-Static
Factory Speed Setting (rpm) Std
Hi-Static
Fan Shaft Diameter at Pulley (in.)
LEGEND
Bhp — Brake Horsepower
*Single phase/three phase.
†Indicates automatic reset.
**60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and 120,000
Btuh heat input units have 3 burners. 115,000 Btuh heat input units and 150,000 Btuh Heat input units have 3 burners.
††An LP kit is available as an accessory. Kit may be used at elevations as high as 2000
ft. If an LP ki t is used with Low NOx units, the Low NOx baffle must be removed and the units will no longer be classified a s Low NOx units. ll Three-phase standard models have heating inputs as shown. Single-phase stan­dard mo dels have one-stage heating wi th heating input va lues as follows:
HJD005-006,HJE004 — 72,000 B tuh HJE005-006,HJF004 — 115,000 Btuh HJF005-006 — 150,000 Btuh
***California compliant three-phase models.
†††California SCAQMD compliant low NO
controlled to 40 nanograms per joule or less.
models have combustion products that are
x
3 4 5 6
530 540 560 635
15 23 25 29 50 50 50 50
115 115 115 115
Scroll
1 1 1 1
42 53 50 60
R-22
AcutrolMetering Device
5-8 10-2 10-0 12- 8
12-5 18-8 20-5 23-14
Propeller
1...22 1...22 1...22 1...22 3500 3500 4100 4100
1
/4...825
1
/4...825
1
/4...1100
1
/4...1100
180 180 320 320
Enhanced Copper Tubes, Aluminum Lanced Fins
1...17 2...17 2...17 2...17
14.6 16.5 16.5 21.3 Enhanced Copper Tubes, Aluminum Double-Wavy Fins
2...15 2...15 4...15 4...15
5.5 5.5 5.5 7.3
1...17 2...17 2...17 2...17
3.9 3.9 3.9 5.2 Centrifugal Type, Belt Drive
1...10 x 10 1...10 x 10 1...10 x 10 1...10 x 10 1200 1600 2000 2400
1.20
2.40 1620 1725
48 56
680-1044
1075-1455
1.20 1.30/2.40* 2.40
2.40 2.90 2.90 1620 1725 1725 1725 1725 1725
48 48/56* 56 56 56 56
770-1185 1035-1460 1119-1585
1075-1455 1300-1685 1300-1685
Ball Ball Ball Ball
2100 2100 2100 2100
1.9/2.9
2.8/3.8
1/
2
5
/
8
4.5
4.5
1...A...36
1...A...39
1.9/2.0 2.4/3.4 2.4/3.4
2.8/3.8 3.4/4.4 3.4/3.4
1
/
2
5
/
8
4.0 4.0 4.0
5
/
8
5
/
8
5
/
8
7
/
8
4.0 4.5 4.5
1...A...36 1....4...40 1...A...38
1...A...39 1...A...40 1...A...40
10.0-12.4 10.0-12.4 14.7-15.5 14.7-15.5 65 65
5 6 3
1
3
826
1233
5
/
/
2
8
70 75 95 65 60 60
5 6 5 6 5 5 3 3 3
31/
2
936 1248 1305
1233 1396 1396
5
/
8
31/
2
5
/
8
31/
5
/
2
8
48HE,HJ
9
TABLE 1 — PHYSICAL DATA 48HJ (cont)
BASE UNIT 48HJ HJE/F/H/K/M/N004 HJD/E/F/G/H/K/L/M/N005 HJD/E/F/G/H/K/L/M/N006 HJD/E/F007 FURNACE SECTION
Rollout Switch Cutout Temp (F)†
Burner Orifice Diameter (in. ...drill size)**
Natural Gas — Std HJE .113...33 HJD .113...33 HJD .113...33 HJD .113...33
Liquid Propane — Alt†† HJE .089...43 HJD .089...43 HJD .089...43 HJD .089...43
Thermostat Heat Anticipator Setting (amps) 208/230/460/575 v
48HE,HJ
First Stage Second Stage
Gas Input (Btuh)
First Stage/Second Stage
Efficiency (Steady State) (%) HJE 82.8 HJD 82.8 HJD 82.8 HJD 82
TemperatureRiseRange HJE 25-55 HJD 25-25 HJD 25-55
Manifold Pressure (in. wg)
Natural Gas — Std
Liquid Propane — Alt†† Maximum Static Pressure (in. wg) Field Gas Connection Size (in.)
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief Cutout Reset (Auto.)
LOSS-OF-CHARGE SWITCH/LOW-PRESSURE (Liquid LIne) (psig)
Cutout Reset (Auto.)
FREEZE PROTECTION THERMOSTAT
Opens (F) Closes (F)
OUTDOOR-AIR INLET SCREENS RETURN-AIR FILTERS
Quantity...Size (in.)
LEGEND
Bhp — Brake Horsepower
*Single phase/three phase.
†Indicates automatic reset.
**60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and 120,000
Btuh heat input units have 3 burners. 115,000 Btuh heat input units and 150,000 Btuh Heat input units have 3 burners.
††An LP kit is available as an accessory. Kit may be used at elevations as high as 2000
ft. If an LP ki t is used with Low NOx units, the Low NOx baffle must be removed and
195 195 195 195
HJF .113...33 HJE .113...33 HJE .113...33 HJE .113...33
HJF .129...30 HJF .129...30 HJF .129...30
HJH .113...33 HJG .113...33 HJG .113...33 HJK .113...33 HJH .113...33 HJH .113...33
HJK .129...30 HJK .129...30 HJM .102...38 HJL .102...38 HJL .102...38 HJN .102...38 HJM .102...38 HJM .102...38
HJN .116...32 HJN .116...32
HJF .089...43 HJE .089...43 HJE .089...43 HJE .089...43
HJF .104...37 HJF .104...37 HJF .104...37 HJH .089...43 HJG .089...45 HJG .089...43 HJK .089...43 HJH .089...45 HJH .089...43
HJK .102...38 HJK .104...37 HJM .082...45 HJL .082...45 HJL .082...45 HJN .082...45 HJM .082...45 HJM .082...45
HJN .094...42 HJN .094...42
.14 .14 .14 .14 .14 .14 .14 .14
HJE|| 50,000/ 72,000
HJF|| 82,000/115,000
HJD|| 50,000/ 72,000 HJD|| 50,000/ 72,000 HJD 50,000/ 72,000
HJE|| 82,000/115,000 HJE|| 82,000/115,000 HJE 82,000/115,000
HJF|| 120,000/150,000 HJF|| 120,000/150,000 HJF 120,000/150,000 HJH*** —/ 72,000 HJG*** —/ 72,000 HJG*** —/ 72,000 HJK***—/115,000 HJH*** —/115,000 HJH*** —/115,000
HJK*** —/150,000 HJK*** —/150,000 HJM††† —/ 60,000 HJL††† —/ 60,000 HJL††† —/ 60,000 HJN††† —/ 90,000 HJM††† —/ 90,000 HJM†††—/ 90,000
HJN††† —/120,000 HJN††† —/120,000
HJF 80 HJE 81 HJE 81 HJE 81
HJF 80.4 HJF 80.4 HJF 80 HJH 82 HJG 82 HJG 82 HJK 80 HJH 81 HJH 81
HJK 80 HJK 80 HJM 80.2 HJL 80.2 HJL 80.2 HJN 81 HJM 81 HJM 81
HJN 80.7 HJN 80.7
HJF 55-85 HJE 35-65 HJE 35-65
HJF 50-80 HJF 50-80 HJH 25-55 HJG 25-55 HJG 25-55
HJD 25-55 HJE 35-65 HJF 50-80
HJK 55-85 HJH 35-65 HJH 35-65
HJK 50-80 HJK 50-80 HJM 20-50 HJL 20-50 HJL 20-50 HJN 30-60 HJM 30-60 HJM 30-60
HJN 40-70 HJN 40-70
3.5 3.5 3.5 3.5
3.5 3.5 3.5 3.5
1.0 1.0 1.0 1.0
1
/
2
1
/
2
1
/
2
450 50
428 320
7 3
22  5
30  5 45  5
Cleanable. Screen quantity and size varies with option selected.
Throwaway
2...16 x 25 x 2 4...16 x 16 x 2
the units will no longer be classified a s Low NOx units. ll Three-phase standard models have heating inputs as shown. Single-phase stan­dard mo dels have one-stage heating wi th hea ting input values as fo llows:
HJD005-006,HJE004 — 72,000 B tuh HJE005-006,HJF004 — 115,000 Btuh HJF005-006 — 150,000 Btuh
***California compliant three-phase models.
†††California SCAQMD compliant low NOxmodels have combustion products that are
controlled to 40 nanograms per joule or less.
— — — — — —
— — — — — —
— — — — — —
— — — — — —
— — — — — —
1
/
2
10
Table 2 —PHYSICAL DATA 4 8HE
BASE UNIT 48HE HD/E/F003 HE/F/H/K/M/N004 H/E/F/G/H/K/L/M/N005 HD/E/F/G/H/K/L/M/N006 NOMINAL CAPACITY OPERATING WEIGHT (lb)
Unit Humidi-MiZerAdaptive Dehumidification System EconoMi$er IV Roof Cur b
COMPRESSOR
Quantity Oil (oz)
REFRIGERANT TYPE
Expansion Device Operating Charge (lb-oz)
Standard Unit Unit With Humidi-Mizer Adaptive Dehu midification System
CONDENSER FAN
Quantity...Diameter (in.) Nominal C f m Motor Hp...Rpm Watts Input (Total)
CONDENSER COIL
Rows...Fins/in. Tot a l Fa ce A r e a (s q f t )
EVAPORATOR COIL
Standard Unit
Rows...Fins/in. Tot a l Fa ce A r e a (s q f t )
Unit with Humidi-Mizer Adaptive Dehumidification System
Rows...Fins/in. Tot a l Fa ce A r e a (s q f t )
EVAPORATOR FAN
Quantity...Size (in.) Nominal C f m Maximum Continuous Bhp Std
Hi-Static
Motor Frame Size Std
Hi-Static
Motor Rpm Fan Rpm Ran ge Std
Hi-Static
Motor Bearing Type Maximum Fan Rpm Motor Pulley Pitch Diameter A/B (in.)
Hi-Static
Nominal Motor Shaft Diameter (in.) Std
Hi-Static
Fan Pulley Pitch Diameter (in.) Std
Hi-Static
Belt — Type...Length (in.) Std
Hi-Static
Pulley Center Line Distance (in.) Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full
Turns from Closed Position
Hi-Static
Hi-Static
Factory Setting — Full Turns Open Std
Hi-Static
Factory Speed Setting (rpm) Std
Hi-Static
Fan Shaft Diameter at Pulley (in.)
Std
Std
Std
2 3 4 5
530 540 560 635
13 15 23 25 50 50 50 50
115 115 115 115
Scroll
1 1 1 1
25 42 56 53
R-22
AcutrolMetering Device
5 --- 3 7 --- 1 1 8 --- 8 12 --- 11
1 0 --- 2 14 --- 0 14---13 21 --- 0
Propeller
1...22 1...22 1...22 1...22 3000 3500 3500 4100
1
/8...825
1
/8...825
1
/8...825
1
/4...1100
180 180 180 320
Enhanced Copper Tubes, Aluminum Lanced Fins
1...17 1...17 2...17 2...17
14.6 14.6 16.5 16.5 Enhanced Copper Tubes, Aluminum Double-Wavy Fins
2...15 2...15 2...15 4...15
4.2 5.5 5.5 5.5
1...17 1...17 2...17 2...17
3.5 3.9 3.9 3.9 Centrifugal Type, Belt Drive
1...10 x 10 1...10 x 10 1...10 x 10 1...10 x 10 800 1200 1600 2000
0.58
1.20 1.20 1.30/2.40*
2.40 2.40 2.90
48
48 48 48/56* 56 56 56
1620 1620 1620 1725
400-1000
680-1044 770-1185 1035-1460
1075-1455 1075-1455 1300-1685
Ball Ball Ball Ball
1620 2100 2100 2100
2.4/3.2
5
/
8
7
/
8
4.0
4.5
1...A...36
1.9/2.9 1.9/2.0 2.4/3.4
2.8/3.8 2.8/3.8 3.4/4.4
1/
2
5
/
8
4.5 4.0 4.0
1
/
2
5
/
8
5
/
8
5
/
8
4.5 4.0 4.5
1...A...36 1...A...36 1....4...40
1...A...39 1...A...39 1...A...40
10.0---12.4 10.0-12.4 10.0-12.4 14.7-15.5
60
65 70 75 65 65 60
5
5 5 6 6 6 5
3
756
5
/
8
3 3 3
31/
2
826 936 1248
1233 1233 1396
5
/
8
31/
2
5
/
8
31/
5
/
2
8
48HE,HJ
11
TABLE 2 — PHYSICAL DATA 48HE (cont)
BASE UNIT 48HE HD/E/F003 HE/F/H/K/M/N004 HD/E/F/G/H/K/L/M/N005 HD/E/F/G/H/K/L/M/N006 FURNACE SECTION
Rollout Switch Cutout Temp (F)†
Burner Orifice Diameter (in. ...drill size)**
Natural Gas — Std* HJE .113...33 HJD .113...33 HJD .113...33
Liquid Propane — Alt†† HEE .073...49 HJE .089...43 HJD .089...43 HJD .089...43
Thermostat Heat Anticipator Setting (amps) 208/230/460/575 v
48HE,HJ
First Stage Second Stage
Gas Input (Btuh)
First Stage/Second Stage
Efficiency (Steady State) (%) HEE 81 HEE 82.8 HED 82.8 HED 82.8
TemperatureRiseRange HEE 25-55 HED 25-25 HED 25-55
Manifold Pressure (in. wg)
Natural Gas — Std
Liquid Propane — Alt†† Maximum Static Pressure (in. wg) Field Gas Connection Size (in.)
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief Cutout Reset (Auto.)
LOSS-OF-CHARGE SWITCH (Liquid LIne) (psig)
Cutout Reset (Auto.)
FREEZE PROTECTION THERMOSTAT
Opens (F) Closes (F)
OUTDOOR-AIR INLET SCREENS RETURN-AIR FILTERS
Quantity...Size (in.)
LEGEND
Bhp — Brake Horsepower
*Stainless steel models use same orifices as equivalent standard unit.
†Indicates automatic reset.
**72,000 Btuh heat input units have 2 burners. 90,000 and 120,000 Btuh heat
input units have 3 burners. 115,000 Btuh heat input units and 150,000 Btuh Heat input uni ts have 3 burners.
††AnLPkitisavailableasanaccessory. AnLPconversionkitshouldnotbeusedona
low NOx unit because then it can no lo nger be classified as a Low NOx unit. The
195 195 195 195
HEE .089...43 HJF .113...33 HJE .113...33 HJE .113...33
HJF .129...30 HJF .129...30
— — —
HEM .089...43
— —
HJH .113...33 HJG .113...33 HJG .113...33 HJK .113...33 HJH .113...33 HJH .113...33
HJK .129...30 HJK .129...30 HJM .102...38 HJL .102...38 HJL .102...38 HJN .102...38 HJM .102...38 HJM .102...38
HJN .116...32 HJN .116...32
HJF .089...43 HJE .089...43 HJE .089...43
HJF .104...37 HJF .104...37
— — —
HJH .089...43 HJG .089...43 HJG .089...43 HJK .089...43 HJH .089...43 HJH .089...43
HJK .102...37 HJK .104...37
— — —
.14 .14 .14 .14 .14 .14 .14 .14
HEE 50,000/ --- HEE||
50,000/ 72,000 HEF||
82,000/115,000
HED|| 50,000/ 72,000 HED|| 50,000/ 72,000
HEE|| 82,000/115,000 HEE|| 82,000/115,000
HEF|| 120,000/150,000 HEF|| 120,000/150,000
— — — — — —
HEH*** —/ 72,000 HEG*** —/ 72,000 HEG*** —/ 72,000 HJK***—/115,000 HEH** * —/ 115,000 HEH*** —/115,000
HEK*** —/150,000 HEK*** —/150,000 HEM††† —/ 60,000 HEL††† —/ 60,000 HEL††† —/ 60,000 HEN††† —/ 90,000 HEM††† —/ 90,000 HEM†††—/ 90,000
HEN††† —/120,000 HEN††† —/120,000
HEF 80 HEE 81 HEE 81
HEF 80.4 HEF 80.4
— — — —
HEM 81
HEE 25-65
— — — — — —
HEH 82 HEG 82 HEG 82 HEK 80 HEH 81 HEH 81
HEK 80 HEK 80 HEM 80.2 HEL 80.2 HEL 80.2 HEN 81 HEM 81 HEM 81
HEN 80.7 HEN 80.7
HEF 55-85 HEE 35-65 HEE 35-65
HEF 50-80 HEF 50-80 HEH 25-55 HEG 25-55 HEG 25-55 HEK 55-85 HEH 35-65 HEH 35-65
HEK 50-80 HEK 50-80 HEM 20-50 HEL 20-50 HEL 20-50 HEN 30-60 HEM 30-60 HEM 30-60
HEN 40-70 HEN 40-70
3.5 3.5 3.5 3.5
3.5 3.5 3.5 3.5
1.0 1.0 1.0 1.0
1
/
2
1
/
2
1
/
2
450 50
428 320
7 3
22  5
30  5 45  5
Cleanable. Screen quantity and size varies with option selected.
Throwaway
2...16 x 25 x 2
Low NOx requirement only applies to natural gas units. Three-phase standard models have heating i nputs as shown. Si ngle-phase standa rd models have one-stage heating with heating input values as shown in heatin capac­ity tables.
***These units do NOT meet the California low NOx requirements.
†††California SCAQMD compliant low NOxmodels have combustion products that are
controlled to 40 nanograms per joule or less.
1
/
2
12
48HE003-006
48HE006
48HE004,005
Fig. 12 --- Power Wiring Connections
48HE004,005
LEGEND
C—Contactor COMP — Compressor EQUIP — Equipment GND Ground IFC Indoor (Evaporator)
NEC National Electrical Code TB Te r m i na l B l o ck
Fan Contactor
48HE,HJ
C06124
Y1
Y2
W1
W2
IPD/X
R
G
C
WIRE CONNECTIONS TO LOW-VOLTAGE SECTION
COOL STAGE 1
FAN
HEAT STAGE 1
COOL STAGE 2
HEAT STAGE 2
24 VAC HOT
24 VAC COM
N/A
OUTDOOR AIR
SENSOR
THERMOSTAT DIPSWITCH SETTINGS ON
OFF
A
LEGEND
NOTE: Un derlined letter indicates active thermostat output when configured for A/C operation.
Y1/W2
G
W/W1
Y/Y2
O/W2
R
C
S1
S2
B
C
Field Wiring
D
Fig. 13 --- Low--Voltage connections With or
Without Economizer or Two-- Position Damper
CONTROL
CONNECTION
BOARD
24 VAC
R
RMTOCC
G
CMPSAFE
Y2
FSD
W1
SFS
NOT USED
C
C
X
X
THERMOSTAT CONTROL
CONNECTION
BOARD
R
Y1
Y2
W1
W2
G
C
R
Y1
Y2
W1
W2
G
C
X
Fig. 14 --- Low--Voltage Connections (Units with PremierLinkt Controls)
C06008
C06009
LOW VOLTAGE CONNECTIONS
INTEGRATED GAS UNIT CONTROLLER (IGC)
Fig. 15 --- Field Control Wiring
C06125
13
48HE,HJ
MINIMUM UNIT
DISCONNECT SIZE
POWER SUPPLY *
CONV
OUTLET
IFM
FLA
FLA LRA
MOCP**
NO 16.3 20 15.6 69
NO 25.6 30 24.8 101
NO 18.5 25 18.3 90
NO 19.4 25 19.3 120
NO 9.0 15 8.9 46
NO 9.4 15 9.3 60
NO 7.6 10 7.5 36
NO 7.7 10 7.6 43
NO 7.7 10 8.0 48
NO 32.7 40 31.5 130
NO 24.0 30 23.6 110
NO 24.9 30 24.6 140
NO 11.9 15 11.6 53
NO 12.3 15 12.1 67
NO 10.1 15 9.9 44
NO 10.2 15 10.0 51
NO 10.3 15 10.1 56
NO 39.4 50 38.1 187
NO 28.9 35 28.3 168
NO 30.6 35 30.2 187
NO 13.9 20 13.6 92
NO 14.7 20 14.5 102
NO 11.5 15 11.2 66
NO 12.3 15 12.1 75
YES 22.3 25 21.2 73
YES 31.6 35 30.4 106
YES 24.5 30 23.8 95
YES 25.4 30 24.9 124
YES 11.7 15 11.4 48
YES 12.1 15 11.8 63
YES 9.7 15 9.5 38
YES 9.8 15 9.6 44
YES 9.8 15 9.6 50
YES 38.7 45 37.0 135
YES 30.0 35 29.1 115
YES 30.9 35 30.1 145
YES 14.6 20 14.1 55
YES 15.0 20 14.6 70
YES 12.3 15 11.9 46
YES 12.4 15 12.0 52
YES 12.5 15 12.1 58
YES 45.4 60 43.6 191
YES 34.9 40 33.8 173
YES 36.6 40 35.8 192
YES 16.6 20 16.1 95
YES 17.4 20 17.0 104
4.9
2.2
1.9
4.9
2.2
1.9
5.8
2.6
NO 12.2 15 12.0 79
YES 13.6 15 13.2 67
YES 14.4 20 14.1 76
YES 14.4 20 14.0 80
2.0
COMBUSTION
Table 3—Electrical Data 48HE
COMPRESSOR OFM
VOLTAGE
FAN MOTOR
RANGE
IFM TYPE Min Max QTY RLA LRA QTY FLA FLA MCA
STD
0.3†
1 0.4
187 254 1 10.3 77 1 0.7 0.6
414 508 1 5.1 39 1 0.4 0.3
HS 5.8
STD
518 632 1 4.2 31
HS 2.6
HS 2.0
STD
HumidiMi$er 1 0.4† 2.6†
STD
187 254 1 14.1 95 1 1.5 0.6
414 508 1 7.1 45 1 0.8 0.3
HS 5.8
STD
0.3†
1 0.6
518 632 1 6.1 38
HS 2.6
HS 2.0
STD
HumidiMi$er 1 0.8† 2.6†
STD
187 254 1 17.3 123 1 1.5 0.6
414 508 1 8.4 70 1 0.8 0.3†
HS 7.5
STD
0.3†
1 0.6
518 632 1 7.1 53
HS 3.4
HS 2.8
STD
HumidiMi$er 1 1.9† 3.4†
48HE003---006
NOMINAL
V --- P H --- H z
UNIT SIZE
003
208/230--- 1 --- 60 STD 187 254 1 10.9 63 1 0.7 0.6 2.0
208/230--- 1 --- 60 STD 187 254 1 16 88 1 0.7 0.6 4.9
(2 tons)
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
004
(3 tons)
5 7 5 --- 3 --- 6 0
208/230--- 1 --- 60 STD 197 254 1 21 115 1 1.5 0.6 4.9
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
005
(4 tons)
5 7 5 --- 3 --- 6 0
208/230--- 1 --- 60 STD 187 254 1 25 150 1 1.5 0.6 6.6
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
006
(5 tons)
5 7 5 --- 3 --- 6 0
HACR --- Heating, Air Conditioning and Refrigeration
IFM --- Indoor (Evaporator) Fan Motor
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC --- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA --- Rated Load Amps
* The values listed in this table do not include power exhaust. See power exhaust table for power exhaust requirements.
** Fuse or HACR breaker
FLA ---Full Load Amps
{ 460v motor
NOTES:
14
MINIMUM UNI
DISCONNECT SIZE
POWER SUPPLY *
CONV
OUTLET
FLA
IFM
FAN MOTOR
COMBUSTION
FLA LRA
MOCP**
NO 25.6 30 25 101
YES 31.6 35 30 106
NO 18.5 25 18 90
NO 19.4 25 19 120
NO 9.0 15 9 46
NO 9.4 15 9 60
NO 7.6 10 7 36
NO 7.7 10 8 43
NO 8.3 10 8 52
NO 35.2 45 34 139
NO 22.5 30 22 106
NO 23.4 30 23 136
NO 10.6 15 10 54
NO 11.0 15 11 68
NO 10.3 15 10 45
NO 10.4 15 10 52
NO 11.0 15 11 61
NO 44.1 60 42 206
NO 28.9 35 28 168
NO 30.6 35 30 187
NO 14.7 20 14 84
NO 15.5 20 15 94
NO 11.5 15 11 63
NO 12.3 15 12 72
NO 12.2 15 12 76
NO 32.8 40 32 200
NO 34.5 40 34 219
NO 15.2 20 15 97
NO 16.0 20 16 107
NO 12.4 15 12 69
NO 13.2 20 13 79
YES 24.5 30 24 95
YES 25.4 30 25 124
YES 11.7 15 11 48
YES 12.1 15 12 63
YES 9.7 15 9 38
YES 9.8 15 10 44
YES 10.4 15 10 54
YES 41.2 50 39 144
YES 28.5 35 27 111
YES 29.4 35 29 140
YES 13.3 15 13 56
YES 13.7 15 13 70
YES 12.5 15 12 47
YES 12.6 15 12 53
YES 13.2 15 13 63
YES 50.1 60 48 210
YES 34.9 40 34 173
YES 36.6 40 36 192
YES 17.4 20 17 87
YES 18.2 20 18 96
YES 13.6 15 13 64
YES 14.4 20 14 73
YES 14.4 20 14 77
YES 38.8 45 37 205
YES 40.5 45 39 224
YES 17.9 20 17 99
YES 18.7 25 18 109
NO 12.8 15 13 81
YES 14.6 20 14 70
YES 15.4 20 15 80
YES 15.0 20 15 83
48HE,HJ
4.9
2.2
1.9
4.9
2.2
1.9
5.8
2.6
2.0
0.6 5.8
2.0
0.3 2.6
Table 4—Electrical Data 48HJ
COMPRESSOR (each) OFM (each)
VOLTAGE
0.6 0.3†
1 0.4 0.3†
RANGE
IFM TYPE Min Max QTY RLA LRA QTY FLA FLA MCA
STD
187 254 1 10.3 77 1 0.7 0.6
414 508 1 5.1 39 1 0.4 0.3
HS 5.2
STD
518 632 1 4.2 31
HS 2.6
HS 2.0
STD
HumidiMi$er 1 0.4† 0.9† 2.6†
STD
187 254 1 13.5 93 1 0.7 0.6
HS 5.8
STD
1 0.4 0.3†
414 508 1 6.4 46.5 1 0.4 0.3
518 632 1 6.4 40
HS 2.6
HS 2.0
STD
HumidiMi$er 1 0.4 0.9† 2.6†
STD
187 254 1 17.3 123 1 1.5 0.6
414 508 1 9 62 1 0.8 0.3
HS 7.5
STD
518 632 1 7.1 50 1
HS 3.4
HS 2.8
STD
187 254 1 20.5 156 1 1.4
HS 0.6 7.5
STD
STD
HumidiMi$er 0.8† 0.3† 3.4†
0.8 0.3†
0.6† 0.3† 3.4†
414 508 1 9.6 75 1 0.6
518 632 1 7.7 56 1
HS 0.3 3.4
HS 2.8
STD
HumidiMi$er
48HJ004---014
NOMINAL
V --- P H --- H z
UNIT SIZE
4 6 0 --- 3 --- 6 0
208/230--- 3 60
208/230--- 1 --- 60 STD 187 254 1 16 88 1 0.7 0.6 4.9
004 (3 Tons)
5 7 5 --- 3 --- 6 0
208/230--- 1 --- 60 STD 187 254 1 23.7 126 1 0.7 0.6 4.9
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
005 (4 Tons)
5 7 5 --- 3 --- 6 0
208/230--- 1 --- 60 STD 187 254 1 28.8 169 1 1.5 0.6 6.6
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
006 (5 Tons)
5 7 5 --- 3 --- 6 0
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
5 7 5 --- 3 --- 6 0
007 (6 Tons)
15
48HE,HJ
NO 38.2 45 40 242
NO 41.3 45 44 267
NO 19.2 25 20 121
NO 20.6 25 22 134
NO 14.6 20 15 95
NO 15.3 20 17 104
NO 15.8 20 17 104
NO 40.2 45 42 276
NO 43.3 50 46 301
NO 21.5 25 23 143
NO 22.9 25 24 156
NO 18.2 20 19 115
NO 18.9 25 20 124
NO 19.4 25 20 124
NO 53.0 60 56 341
NO 57.4 70 61 364
NO 24.9 30 26 171
NO 27.5 30 29 182
NO 19.1 25 20 136
NO 21.0 25 23 146
NO 21.2 25 23 146
NO 60.6 70 64 426
NO 29.1 35 31 207
NO 23.5 30 25 154
YES 44.2 50 46 247
YES 47.3 50 49 271
YES 21.9 25 23 123
YES 23.3 25 24 136
YES 16.8 20 17 95
YES 17.5 20 19 104
YES 17.9 20 19 104
YES 46.2 50 48 281
YES 49.3 60 51 305
YES 24.2 30 25 145
YES 25.6 30 27 158
YES 20.4 25 21 116
YES 21.1 25 22 126
YES 21.5 25 22 126
YES 59.0 70 61 345
YES 63.4 70 66 369
YES 27.6 30 29 173
YES 30.2 35 32 184
YES 21.3 25 22 138
YES 23.1 25 25 148
YES 23.4 25 25 148
YES 66.6 70 70 431
7.5
3.4
2.8
7.5
3.4
2.8
4.8
10.6
3.3
YES 31.8 35 33 209
NO 23.7 30 25 154
YES 25.6 30 27 156
YES 25.9 30 27 156
5.6
0.3†
0.6 0.3†
0.6 0.3†
0.7 0.3
0.6
2
0.3†
0.7 0.3 7.4
2
2 0.6
Table 4—Electrical Data 48HJ (cont)
187 254 2 12.4 88 2 1.4 0.6
STD
414 508 2 6.4 44 2 0.7 0.3
HS 10.6
STD
518 632 2 4.8 34 2
HS 4.8
HS 3.3
STD
187 254 2 13.1 105 2 1.4 0.6
414 508 2 7.4 55 2 0.7 0.3
HS 10.6
STD
STD
HumidiMi$er 0.7† 0.3† 4.8†
518 632 2 6.4 44 2
HS 4.8
HS 3.3
STD
187 254 2 17.6 125 2 1.4 0.6
414 508 2 8.3 62.5
HS 15.0
STD
STD
HumidiMi$er 0.7† 0.3† 4.8†
518 632 2 6.3 50 2
HS 7.4
HS 5.6
STD
HumidiMi$er 0.7† 7.4†
518 632 2 7.4 54
STD
HumidiMi$er 2 0.7† 7.4†
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
008 (71/2 Tons)
5 7 5 --- 3 --- 6 0
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
009 (81/2 Tons)
5 7 5 --- 3 --- 6 0
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
012 (10 Tons)
5 7 5 --- 3 --- 6 0
4 6 0 --- 3 --- 6 0 STD 414 508 2 9 75
Ton s )
014 (121/2
5 7 5 --- 3 --- 6 0
HACR --- Heating, Air Conditioning and Refrigeration
IFM --- Indoor (Evaporator) Fan Motor
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC --- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA --- Rated Load Amps
* The values listed in this table do not include power exhaust. See power exhaust table for power exhaust requirements.
** Fuse or HACR breaker
FLA ---Full Load Amps
{ 460v motor
NOTES:
208/230--- 3 --- 60 STD 187 254 2 19 156 2 1.4 0.6 15.0
16
Step 8 Adjust Factory-Installed Options
energy recovery units
cobra
Please refer to the supplement provided for information on installing and operating the factory optional COBRA Energy Recovery Units. These units are equipped with a factory--installed energy recovery unit and have different installation and operation procedures than the standard unit.
HUMIDI--MIZER
ADAPTIVE DEHUMIDIFICATION
SYSTEM
Humidi-- MiZer system operation can be controlled by field installation of a Carrier--approved humidistat. (See Fig. 16.)
NOTE: A light commercial Thermidistatdevice (Fig. 17) can be used instead of the humidistat if desired. The Thermidistat device includes a thermostat and a humidistat. The humidistat is normally used in applications where a temperature sensor is already provided (units with PremierLinkcontrol).
% RELATIVE HUMIDITY
C06126
Fig. 16 --- Accessory Field--Installed Humidistat
C06127
Fig. 17 --- Light Commercial Thermidistat Device
To install the humidistat:
1. Route humidistat cable through hole provided in unit control box.
2. Some models may be equipped with a raceway built into the corner post located on the left side of control box (See Fig. 15). This raceway provides the required clearance between high--voltage and low voltage wiring. For models without a raceway, ensure to provide the NEC required clearance between the high--voltage and low--voltage wiring.
3. Use a wire nut to connect humidistat cable into low­voltage wiring as shown in Fig. 18.
To install Thermidistat device:
1. Route Thermidistat cable through hole provided in unit control box.
2. Some models may be equipped with a raceway built into the corner post located on the left side of control box (See Fig. 15). This raceway provides the required clearance between high--voltage and low voltage wiring. For models without a raceway, ensure to provide the NEC required clearance between the high--voltage and low--voltage wiring.
3. A field-supplied relay must be installed between the Thermidistat and the Humidi-Mizer circuit (recommended relay: HN612KK324). (See Fig. 19.) The relay coil is connected between the DEHUM output and C (common) of the unit. The relay controls the Humidi-MiZer solenoid valve and must be wired between the Humidi-MiZer fuse and the low-pressure switch. Refer to the installation instructions included with the Carrier Light Commercial Thermidistat device for more information.
manual outdoor
damper
The outdoor--air hood and screen are attached to the basepan at the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for building. Record amount for use in Step 8.
2. Remove and save outdoor air opening panel and screws. (See Fig. 20.)
3. Remove evaporator coil access panel. Separate hood and screen from basepan by removing the 4 screws securing them. Save all screws.
4. Replace evaporator coil access panel.
5. Place hood on front of outdoor air opening panel. See Fig. 21 for hood details. Secure top of hood with the
4screwsremovedinStep3.(SeeFig.22.)
6. Remove and save 6 screws (3 on each side) from sides of the manual outdoor-air damper.
7. Align screw holes on hood with screw holes on side of manual outdoor-air damper. (See Fig. 21 and 22.) Secure hood with 6 screws from Step 6.
8. Adjust minimum position setting of the damper blade by adjusting the manual outdoor-air adjustment screws on the front of the damper blade. (See Fig. 20.) Slide blade vertically until it is in the appropriate position determined by Fig. 23. Tighten screws.
9. Remove and save screws currently on sides of hood. Insert screen. Secure screen to hood using the screws. (See Fig. 22.)
convenience
outlet
An optional convenience outlet provides power for rooftop use. For maintenance personnel safety, the convenience outlet power is off when the unit disconnect is off. Adjacent unit outlets may be used for service tools.
novar contr
ols
Optional Novar controls (ETM 3051) are available for replacement or new construction jobs.
48HE,HJ
17
CB Circuit Breaker CR Cooling Relay DHR Dehumidify Relay DSV Discharge Solenoid Valve HR Heater Relay LPS Low Pressure Switch LSV Liquid Solenoid Valve LTLO Low Temperature Lockout
Field Splice
48HE,HJ
LEGEND
Terminal (Unmarked)
Splice
Factory Wiring
Field Control Wiring
Field Power Wiring
C06128
Fig. 18 --- Typical Humidi--MiZert Adaptive Dehumidification System
Humidistat Wiring (208/230--V Unit Shown)
LCT
R
C Y1 Y2
G
W1
W2
DEHUM
OC
TSTAT WIRES
LEGEND
CB Circuit Breaker LCT — Light Commercial Thermidistat™ Device LLSV — Liquid Line Solenoid Valve LTLO — Low Temperature Lockout
Fig. 19 --- Typical Rooftop Unit with Humidi--Mizer
Adaptive Dehumidification System with Thermidistat Device
OUTDOOR AIR OPENING PANEL
3 SCREWS (SIDE)
R1
R1
ROOF TOP UNIT
R
C Y1 Y2
G
W1 W2
PINK
PINK
CB
3.2 AMPS
LTLO
HUMIDI-MIZER SYSTEM
RED
PINK
24 V
FROM HUMIDI-MIZER SYSTEM LLSV
C06129
Fig. 20 --- Damper Panel with Manual Outdoor--Air
Damper Installed
C06130
C06013
Fig. 21 --- Outdoor--Air Hood Details
18
C06131
Fig. 22 --- Outdoor--Air Damper With
Hood Attached
C06132
Fig. 23 --- Outdoor--Air Damper Position Setting
premierlink
control
The PremierLink controller is compatible with Carrier Comfort NetworkR (CCN) devices. This control is designed to allow users the access and ability to change factory--defined settings, thus expanding the function of the standard unit control board. Carrier’s diagnostic standard tier display tools such as Navigatort or Scrolling Marquee can be used with the PremierLink controller.
The PremierLink controller (see Fig. 24 and 25) requires the use of a Carrier electronic thermostat or a CCN connection for time broadcast to initiate its internal timeclock. This is necessary for broadcast of time of day functions (occupied/unoccupied). No sensors are supplied with the field-- mounted PremierLink control. The factory--installed PremierLink control includes only the supply-- air temperature (SAT) sensor and the outdoor air temperature (OAT) sensor as standard. An indoor air quality (CO2) sensor can be added as an option. Refer to Table 5 for sensor usage. Refer to Fig. 26 for PremierLink controller wiring. The PremierLink control may be mounted in the control panel or an area below the control panel.
NOTE: PremierLink controller versions 1.3 and later are shipped in Sensor mode. If used with a thermostat, the PremierLink controller must be configured to Thermostat mode.
Install the Supply Air Temperature (SAT) Sensor
When the unit is supplied with a factory--mounted PremierLink control, the supply--air temperature (SAT) sensor (33ZCSENSAT) is factory-- supplied and wired. The wiring is routed from the PremierLink control over the control box, through a grommet, into the fan section, down along the back side of the fan, and along the fan deck over to the supply--air opening.
The SAT probe is wire--tied to the supply--air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re-- position the sensor in the flange of the supply-- air opening or in the supply air duct (as required by local codes). Drill or punch a 1/2--in. hole in the flange or duct. Use two field--supplied, self--drilling screws to secure the sensor probe in a horizontal orientation.
NOTE: The sensor must be mounted in the discharge airstream downstream of the cooling coil and any heating devices. Be sure the probe tip does not come in contact with any of the unit or heat surfaces.
Outdoor Air Temperature Sensor (OAT)
When the unit is supplied with a factory-mounted PremierLink control and economizer, the outdoor-air temperature sensor (OAT) is factory-supplied and wired.
Install the Indoor Air Quality (CO
Mount the optional indoor air quality (CO
)Sensor
2
) sensor according to
2
manufacturer specifications. A separate field-supplied transformer must be used to power the
sensor.
CO
2
Wire the CO
sensor to the COM and IAQI terminals of J5 on the
2
PremierLink controller. Refer to the PremierLink Installation, Start-up, and Configuration Instructions for detailed wiring and configuration information.
Enthalpy Sensors and Control
The enthalpy control (HH57AC077) is supplied as a field-installed accessory to be used with the EconoMi$er2 damper control option. The outdoor air enthalpy sensor is part of the enthalpy control. The separate field-installed accessory return air enthalpy sensor (HH57AC078) is required for differential enthalpy control.
NOTE: The enthalpy control must be set to the “D” setting for differential enthalpy control to work properly.
The enthalpy control receives the indoor and return enthalpy from the outdoor and return air enthalpy sensors and provides a dry contact switch input to the PremierLink controller. Locate the controller in place of an existing economizer controller or near the actuator. The mounting plate may not be needed if existing bracket is used.
A closed contact indicates that outside air is preferred to the return air. An open contact indicates that the economizer should remain at minimum position.
Outdoor Air Enthalphy Sensor/Enthalpy Controller (HH57AC077)
T o wire the out door air enthalpy sensor, perform the following (See Fig. 27 and 28):
NOTE: The outdoor air sensor can be removed from the back of the enthalpy controller and mounted remotely.
48HE,HJ
19
Table 5—PremierLinkSensor Usage
APPLICATION
OUTDOOR AIR
TEMPERATURE SENSOR
RETURN AIR
TEMPERATURE SENSOR
OUTDOOR AIR
ENTHALPY SENSOR
Differential Dry Bulb
Tem p e r a tu r e w i th
PremierLink*
(PremierLink
requires 4-20 mA
I n c l u d e d ---
CRTEMPSN001A00
R e q u i r e d --­33ZCT55SPT or Equivalent
Actuator)
Single Enthalpy with
PremierLink*
(PremierLink
requires 4-20 mA
Actuator)
I n c l u d e d ---
Not Used
R e q u i r e d --­HH57AC077
or Equivalent
Differential Enthalpy
with PremierLink*
(PremierLink
requires 4-20 mA
I n c l u d e d ---
Not Used
Actuator)
*PremierLink control requires Supply Air Temperature sensor 33ZCSENS AT and Outdoor Air Temperature sensor CRTEMPSN001A00
48HE,HJ
— Included with factory-installed PremierLink control; field-supplied and field-installed with field-installed PremierLink control.
NOTES:
1. CO
Sensors (Optional):
2
33ZCSENCO2 — Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor. 33ZCASPCO2 — Aspirator box used for duct-mounted CO 33ZCT55CO2 — Space temperature and CO 33ZCT56CO2 — Space temperature and CO
2. All units include the following Standard Sensors: Outdoor-Air Sensor — 50HJ540569 — Opens at 67_F, c l o s e s at 5 2 _F, not adjustable. Mixed-Air Sensor — HH97AZ001 — (PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT and Outdoor Air Temperature Sensor CRTEMPSN001A00) Compressor Lockout Sensor — 50HJ540570 — Opens at 35_F, cl o s e s at 50 _F.
room sensor with override.
2
room sensor with override and set point.
2
room sensor.
2
R e q u i r e d --­HH57AC077
or Equivalent
RETURN AIR
ENTHALPY SENSOR
R e q u i r e d ---
HH57AC078
or Equivalent
Fig. 24 --- PremierLink Controller
20
C06016
Loading...
+ 44 hidden pages