Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install, repair,
or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of
cleaning coils and filters and replacing filters. All other operations
should be performed by trained service personnel. When working
on air-conditioning equipment, observe precautions in the
literature, tags and labels attached to the unit, and other safety
precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguishers
available for all brazing operations.
Recognize safety information. This is the safety--alert symbol
.When you see this symbol on the furnace and in
instructions or manuals, be alert to the potential for personal
injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced installation,
reliability, or operation.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
Before performing service or maintenance operations
on unit, turn off main power switch to unit and install
lockout tag. Ensure electrical service to rooftop unit
agrees with voltage and amperage listed on the unit
rating plate.
WARNING
1
!
FIRE, EXPLOSION HAZARD
Failure to follow this warning could death and/or
property damage.
Disc onnect gas piping from unit when leak testing at
pressure greater than
psig will cause gas valve damage resulting in hazardous
condition. If gas va lve is subjecte d to pressure greater than
1
/2psig, it must be replaced before use. When pressure
testing field-supplied gas piping at pressures of
less, a uni t connected to such piping must be i solated by
manual l y closing the gas valve(s).
WARNING
1
/2psig. Pressures greater than1/
1
/2psig or
INSTALLATION
Unit is shipped in the vertical discharge configuration. To convert
to horizontal discharge application, remove duct opening covers.
Using the same screws, install covers on duct openings in
48HE,HJ
basepan of unit with insulation-side down. Seals around
openings must be tight. (See Fig. 1.)
Fig. 1 --- Horizontal Conversion Panels
Step 1 —Provide Unit Support
CURB
ROOF
Assemble and install accessory roof curb in accordance with
instructions shipped with curb. (See Fig. 2.) Install insulation,
cant strips, roofing felt, and counter flashing as shown. Ductworkmust be attached to curb, not to the unit. If electric control power
or gas service is to be routed through the basepan, attach the
accessory thru-the-bottom service connections to the basepan in
accordancewiththeaccessoryinstallationinstructions.
Connections must be installed before unit is set on roof curb.
IMPORTANT: The gasketing of the unit t o the roof curb is critical
for a watertight seal. Install gasket supplied with the roof curb as
shown in Fig. 2. Improperl y applied gasket can result in air leaks and
poor unit performanc e.
Curb should be level. Unit leveling tolerances are shown in Fig.
3. This is necessary for unit drain to function properly. Refer to
Accessory Roof Curb Installation Instructions for additional
information as required.
SLAB MOUNT (Horizontal Units Only)
Provide a level concrete slab that extends a minimum of 6 in.
beyond unit cabinet. Install a gravel apron in front of
2
C06108
condenser-coil air inlet to prevent grass and foliage from
obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
ALTERNATE UNIT SUPPORT
When the curb or adapter cannot be used, support unit with
sleeper rails using unit curb or adapter support area. If sleeper
rails cannot be used, support the long sides of the unit with a
minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
Step 2 —Field Fabricate Ductwork
Secure all ducts to roof curb and building structure on vertical
discharge units. Do not connect ductwork to unit. For horizontal
applications, field-supplied isolation flanges should be attached to
horizontal discharge openings and all ductwork should be secured
to the flanges. Insulate and weatherproof all external ductwork,
joints, and roof openings with counter flashing and mastic in
accordance with applicable codes.
Ducts passing through an unconditioned space must be insulated
and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be
ducted through the roof deck to comply with applicable fire
codes.
A minimum clearance is not required around ductwork. Cabinet
return-air static pressure (a negative condition) shall not exceed
0.35 in. wg with economizer or 0.45 in. wg without economizer.
These units are designed for a minimum continuous return-air
temperature in heating of 50_F (dry bulb), or an intermittent
operation down to 45_F (dry bulb), such as when used with a
night setback thermostat.
To operate at lower return-air temperatures, a field-supplied
outdoor air temperature control must be used to initiate both
stages of heat when the temperature is below 45_F. Indoor
comfort may be compromised when these lower air temperatures
are used with insufficient heating temperature rise.
Step 3 —Install External Trap for
Condensate Drain
3
The unit’s
bottom and side of the unit. Unit discharge connections do not
determine the use of drain connections; either drain connection
can be used with vertical or horizontal applications.
When using the standard side drain connection, ensure the plug
(Red) in the alternate bottom connection is tight before installing
the unit.
To use the bottom drain connection for a roof curb installation,
relocate the factory-installed plug (Red) from the bottom
connection to the side connection. The center drain plug looks
like a star connection, however it can be removed with a
socket drive extension. (See Fig. 4.) The piping for the
condensate drain and external trap can be completed after the unit
is in place.
All units must have an external trap for condensate drainage.
Install a trap 4-in. deep and protect against freeze-up. If drain line
is installed downstream from the external trap, pitch the line away
from the unit at 1 in. per 10 ft of run. Do not use a pipe size
smaller than the unit connection (
Step 4 —Rig a nd Place Unit
Inspect unit for transportation damage, and file any claim with
transportation agency. Keep unit upright and do not drop.
Spreader bars are not required if top crating is left on unit, and
rollers may be used to move unit across a roof. Level by using
unit frame as a reference. See Table 1 and 2 and Fig. 6 for
additional information. Operating weight is shown in Table 1 and
2 and Fig. 6.
/4-in. condensate drain connections are located on the
1
/2-in.
3
/4in.). (See Fig. 5.)
2
1-4
[406]
DALT
DRAIN
HOLE
13/4
[44.5]
GASPOWERCONTROL
3
/4
[19] NPT
1
/2
[12.7] NPT
3
/4
[19] NPT
CONNECTOR
PKG. ACCY.
BC
CRBTMPWR001A01
CRBTMPWR002A011
CRBTMPWR003A01
1-9
11
[551]
/16
CRBTMPWR004A01
3
/4 [19] NPT
1
/4 [31.7]
3
/4 [19] NPT
1
/4 [31.7]
1
1
/2
[12.7]
ACCESSORY
POWER
1
/2
[12.7]
ROOF CURB
ACCESSORY
CRRFCURB001A01
CRRFCURB002A01
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb (flanges of duct rest
on curb).
6. Service clearance: 4 ft on each side.
1-2
[356]
2-0
[610]
A
48HJ004-007
48HE003-006
UNIT
SIZE
7.Direction of airflow.
8. Connector packages CRBTMPWR001A01
and 002A01 are for thru-the-curb type gas.
Packages CRBTMPWR003A01 and 004A01
are for thru-the-bottom type gas connections.
48HE,HJ
Fig. 2 --- Roof Curb Details
3
C06109
Lifting holes are provided in base rails as shown in Fig. 8 and 9.
Refer to rigging instructions on unit.
!
WARNING
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal
injury, death and property damage.
All panels must be in place when rigging and lifting.
positioning
Maintain clearance around and above unit to provide minimum
distance from combustible materials, proper airflow, and service
access. (See Fig. 7, 8 and 9.)
Position unit on roof curb so that the following clearances are
maintained:
1
/4in. clearance between the roof curb and the base
rail inside the front and rear, 0.0 in. clearance between the roof
curb and the base rail inside on the duct end of the unit. This will
result in the distance between the roof curb and the base rail
48HE,HJ
inside on the condenser end of the unit being approximately
equal to Fig. 2, section C-C.
Do not install unit in an indoor location. Do not locate unit air
inlets near exhaust vents or other sources of contaminated air.
Flue vent discharge must have a minimum horizontal clearance of
4 ft from electric and gas meters, gas regulators, and gas relief
equipment.
After unit is in position, remove shipping materials and rigging
skids.
Step 5 —Install Flue Hood
Flue hood is shipped screwed to the burner compartment access
panel. Remove from shipping location and, using screws
provided, install flue hood in location shown in Fig. 8 and 9.
For units being installed in California Air Quality Management
Districts which require NOx emissions of 40 nanograms/joule or
less, a low NOx unit must be installed.
NOTE: Low NOx units are available for 3 to 5 ton units.
CONDENSATE PAN (SIDE VIEW)
HORIZONTAL
DRAIN OUTLET
NOTE: Drain plug is shown in factory-installed position.
DRAIN PLUG
C06003
Fig. 4 --- Condensate Drain Pan
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-BB-CA-C
0.51.01.0
C06110
Fig. 3 --- Unit Leveling Tolerances
Be sure that unit is installed such that snow will not block the
combustion intake or flue outlet.
Unit may be installed directly on wood flooring or on Class A, B,
or C roof-covering material when roof curb is used.
Although unit is weatherproof, guard against water from higher
level runoff and overhangs.
Locate mechanical draft system flue assembly at least 48 in. from
an adjacent building or combustible material. When unit is
located adjacent to public walkways, flue assembly must be at
least 7 ft above grade.
NOTE: When unit is equipped with an accessory flue discharge
deflector, allowable clearance is 18 inches.
Flue gas can deteriorate building materials. Orient unit such that
flue gas will not affect building materials.
Adequate combustion-air space must be provided for proper
operation of this equipment. Be sure that installation complies
with all local codes and Section 5.3, Air for Combustion and
Ventilation, NFGC (National Fuel Gas Code), ANSI (American
National Standards Institute) Z223.1-1984 and addendum
Z223.1a-1987. In Canada, installation must be in accordance with
the CAN1.B149.1 and CAN1.B149.2 installation codes for gas
burning appliances.
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4-in. trap is recommended.
C06004
Fig. 5 --- Condensate Drain Piping Details
Step 6 —Install Gas Piping
Unit is equipped for use with type of gas shown on nameplate.
Refer to localbuilding codes, or in the absence of local codes,
to ANSI Z223.1-1984 and addendum Z223.1A-1987 entitled
National Fuel Gas Code. In Canada, installation must be in
accordancewiththeCAN1.B149.1andCAN1.B149.2
installation codes for gas burning appliances.
For natural gas applications, gas pressure at unit gas connection
must not be less than 4 in. wg or greater than 13 in. wg while the
unit is operating. On 48HJ005-007 high-heat units, the gas
pressure at unit gas connection must not be less than 5 in. wg or
greater than 13 in. wg while the unit is operating. For propane
applications, the gas pressure must not be less than 5 in. wg or
greater than 13 in. wg at the unit connection.
Size gas supply piping for 0.5 in. wg maximum pressure drop.
Do not use supply pipe smaller than unit gas connection.
Support gas piping as shown in the table in Fig. 11. For example,
3
/4-in. gas pipe must have one field-fabricated support beam
a
every 8 ft. Therefore, an 18-ft long gas pipe would have a
minimum of 3 support beams, and a 48-ft long pipe would have a
minimum of 6 support beams.
OPERATING
WEIGHT
lbkgin.mmin.mmin.mm
OPERATING
WEIGHT
lbkgin.mmin.mmin.mm
C06208
DIMENSIONS
“A”“B”“C”
DIMENSIONS
“A”“B”“C”
!
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal
injury, death and property damage.
All panels must be in place when rigging and lifting.
See Fig. 11 for typical pipe guide and locations of external
manual gas shutoff valve.
NOTE: If accessory thru-the-bottom connections and roof curb
are used, refer to the Thru-the-Bottom Accessory Installation
Instructions for information on power wiring and gas
connection piping. The power wiring, control wiring and gas
piping can be routed through field-drilled holes in the basepan.
The basepan is specially designed and dimpled for drilling the
access connection holes.
!
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
When connecting the gas line to the unit gas valve, the
installer MUST use a backup wrench to prevent damage
to the valve.
WARNING
WARNING
48HE,HJ
5
C06112
48HE,HJ
Fig. 8 --- 48HJ004--007 Base Unit Dimensions
6
C06113
48HE,HJ
Fig. 9 --- 48HE003--006 Base Unit Dimensions
7
Fig. 10 --- Flue Hood Details
*
48HE,HJ
LEGEND
NFGC — National Fuel Gas Code
Field supplied.
NOTE: Follow all local codes.
SPACING OF SUPPORTS
STEEL PIPE
NOMINAL DIAMETER (in.)
1
/
3
/4or 1
1
/4or larger
1
2
Fig. 11 --- Gas Piping Guide (With Accessory
Thru--the--Curb Service Connections)
Step 7 —Make Electrical Connections
!
WARNING
ELECTRICAL SHOCK HAZARD
Failur e to follow this warning could result in personal
injury or death.
Unit cabinet must have an uninterrupt ed, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should oc cur . This gr ound may
consist of el ectrical wire connec ted to unit ground lug i n
control compartme nt, or conduit approved for electr i cal
ground whe n install ed in accordance with NEC (National
Electrical Code), ANSI/NFPA (National Fire Protection
Association), latest edition, and local electrical codes. Do
not use gas piping as an electr i cal ground.
SPACING OF SUPPORTS
X DIMENSION (ft)
10
field power supply
All units except 208/230-v units are factory wired for the voltage
shown on the nameplate. If the 208/230-v unit is to be connected
to a 208-v power supply, the transformer must be rewired by
moving the black wire from the 230-v terminal on the
transformer and connecting it to the 200-v terminal from the
transformer.
Refer to unit label diagram for additional information. Pigtails
are provided for field service. Use factory-supplied splices or UL
(Underwriters’ Laboratories) approved copper connector.
When installing units, provide a disconnect per NEC.
All field wiring must complywith NEC and local
requirements.
C06114
Install conduit through side panel openings indicated in Fig. 8.
Route power lines through connector to terminal connections as
shown in Fig. 12.
Voltage to compressor terminals during operation must be within
voltage range indicated on unit nameplate (also see Tables 3 and
4). On 3-phase units, voltages between phases must be balanced
within 2% and the current within 10%. Use the formula shown in
Tables 3 and 4, Note 3 to determine the percent voltage
imbalance. Operation on improper line voltage or excessive phase
imbalance constitutes abuse and may cause damage to electrical
components. Such operation would invalidate any applicable
Carrier warranty.
NOTE: If accessory thru-the-bottom connections and roof curb
are used, refer to the Thru-the-Bottom Accessory Installation
Instructions for information on power wiring and gas connection
piping. The power wiring, control wiring and gas piping can be
routed through field-drilled holes in the basepan. The basepan is
specially designed and dimpled for drilling the access connection
holes.(SeeFig.2.)
field control
wiring
Install a Carrier-approved accessory thermostat assembly
according to installation instructions included with the accessory.
Locate thermostat assembly on a solid wall in the conditioned
6
8
C06115
space to sense average temperature in accordance with thermostat
installation instructions.
Route thermostat cable or equivalent single leads of colored wire
from subbase terminals through connector on unit to low-voltage
connections (shown in Fig. 13 and 14).
Connect thermostat wires to matching screw terminals of
low-voltage connection board. (See Fig. 13 and 14.)
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gauge) insulated wire (35_Cminimum).For50to75ft,use
no. 16 AWG insulated wire (35_C minimum). For over 75 ft, use
no. 14 AWG insulated wire (35_C minimum). All wire larger
than no. 18 AWG cannot be directly connected to the thermostat
and will require a junction box and splice at the thermostat.
Pass the control wires through the hole provided in thecorner
post; then feed wires through the raceway built into the corner
post to the 24-v barrier located on the left side of the control box.
(See Fig. 15). The raceway provides the UL required clearance
between high and low-voltage wiring.
heat anticipator
settings
Set heat anticipator settings at 0.14 amp for first stage and 0.14
for second stage heating, when available.
8
Table 1—Physical Data 48HJ
BASE UNIT 48HJHJE/F/H/K/M/N004 HJD/E/F/G/H/K/L/M/N005 HJD/E/F/G/H/K/L/M/N006 HJD/E/F007
NOMINAL CAPACITY
OPERATING WEIGHT (lb)
Unit
Humidi-MiZer Adaptive Dehumidification System
EconoMi$er IV
Roof Cur b
COMPRESSOR
Quantity
Oil (oz)
REFRIGERANT TYPE
Expansion Device
Operating Charge (lb-oz)
Standard Unit
Unit With Humidi-Mizer Adaptive Dehu midification System
CONDENSER FAN
Quantity...Diameter (in.)
Nominal C f m
Motor Hp...Rpm
Watts Input (Total)
CONDENSER COIL
Rows...Fins/in.
Tot a l Fa ce A r e a (s q f t )
EVAPORATOR COIL
Standard Unit
Rows...Fins/in.
Tot a l Fa ce A r e a (s q f t )
Unit with Humidi-Mizer Adaptive Dehumidification System
Rows...Fins/in.
Tot a l Fa ce A r e a (s q f t )
EVAPORATOR FAN
Quantity...Size (in.)
Nominal C f m
Maximum Continuous BhpStd
Hi-Static
Motor RPMStd
Hi-Static
Motor Frame SizeStd
Hi-Static
Fan Rpm Ran geStd
Hi-Static
Motor Bearing Type
Maximum Fan Rpm
Motor Pulley Pitch Diameter A/B (in.)
Std
Hi-Static
Nominal Motor Shaft Diameter (in.)Std
Hi-Static
Fan Pulley Pitch Diameter (in.)Std
Hi-Static
Belt — Type...Length (in.)Std
Hi-Static
Pulley Center Line Distance (in.)
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full
Turns from Closed Position
Std
Hi-Static
Std
Hi-Static
Factory Setting — Full Turns OpenStd
Hi-Static
Factory Speed Setting (rpm)Std
Hi-Static
Fan Shaft Diameter at Pulley (in.)
LEGEND
Bhp — Brake Horsepower
*Single phase/three phase.
†Indicates automatic reset.
**60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and120,000
Btuh heat input units have 3 burners. 115,000 Btuh heat input units and 150,000
Btuh Heat input units have 3 burners.
††An LP kit is available as an accessory. Kit may be used at elevations as high as 2000
ft. If an LP ki t is used with Low NOx units, the Low NOx baffle must be removed and
the units will no longer be classified a s Low NOx units.
ll Three-phase standard models have heating inputs as shown. Single-phase standard mo dels have one-stage heating wi th heating input va lues as follows:
Cleanable. Screen quantity and size varies with option selected.
Throwaway
2...16 x 25 x 24...16 x 16 x 2
the units will no longer be classified a s Low NOx units.
ll Three-phase standard models have heating inputs as shown. Single-phase standard mo dels have one-stage heating wi th hea ting input values as fo llows:
—HEK 50-80HEK 50-80
HEM 20-50HEL 20-50HEL 20-50
HEN 30-60HEM 30-60HEM 30-60
HEN 40-70HEN 40-70
3.53.53.53.5
3.53.53.53.5
1.01.01.01.0
1
/
2
1
/
2
1
/
2
450 50
428
320
7 3
22 5
30 5
45 5
Cleanable. Screen quantity and size varies with option selected.
Throwaway
2...16 x 25 x 2
Low NOx requirement only applies to natural gas units.
Three-phase standard models have heating i nputs as shown. Si ngle-phase standa rd
models have one-stage heating with heating input values as shown in heatin capacity tables.
***These units do NOT meet the California low NOx requirements.
†††California SCAQMD compliant low NOxmodels have combustion products that are
NEC— National Electrical Code
TB— Te r m i na l B l o ck
Fan Contactor
48HE,HJ
C06124
Y1
Y2
W1
W2
IPD/X
R
G
C
WIRE
CONNECTIONS
TO
LOW-VOLTAGE
SECTION
COOL STAGE 1
FAN
HEAT STAGE 1
COOL STAGE 2
HEAT STAGE 2
24 VAC HOT
24 VAC COM
N/A
OUTDOOR AIR
SENSOR
THERMOSTAT DIPSWITCH SETTINGS
ON
OFF
A
LEGEND
NOTE: Un derlined letter indicates active thermostat output when
configured for A/C operation.
Y1/W2
G
W/W1
Y/Y2
O/W2
R
C
S1
S2
B
C
Field Wiring
D
Fig. 13 --- Low--Voltage connections With or
Without Economizer or Two-- Position Damper
CONTROL
CONNECTION
BOARD
24 VAC
R
RMTOCC
G
CMPSAFE
Y2
FSD
W1
SFS
NOT USED
C
C
X
X
THERMOSTAT CONTROL
CONNECTION
BOARD
R
Y1
Y2
W1
W2
G
C
R
Y1
Y2
W1
W2
G
C
X
Fig. 14 --- Low--Voltage Connections
(Units with PremierLinkt Controls)
C06008
C06009
LOW VOLTAGE
CONNECTIONS
INTEGRATED GAS UNIT
CONTROLLER (IGC)
Fig. 15 --- Field Control Wiring
C06125
13
48HE,HJ
MINIMUM UNIT
DISCONNECT SIZE
POWER SUPPLY *
CONV
OUTLET
IFM
FLA
FLALRA
MOCP**
NO16.32015.669
NO25.63024.8101
NO18.52518.390
NO19.42519.3120
NO9.0158.946
NO9.4159.360
NO7.6107.536
NO7.7107.643
NO7.7108.048
NO32.74031.5130
NO24.03023.6110
NO24.93024.6140
NO11.91511.653
NO12.31512.167
NO10.1159.944
NO10.21510.051
NO10.31510.156
NO39.45038.1187
NO28.93528.3168
NO30.63530.2187
NO13.92013.692
NO14.72014.5102
NO11.51511.266
NO12.31512.175
YES22.32521.273
YES31.63530.4106
YES24.53023.895
YES25.43024.9124
YES11.71511.448
YES12.11511.863
YES9.7159.538
YES9.8159.644
YES9.8159.650
YES38.74537.0135
YES30.03529.1115
YES30.93530.1145
YES14.62014.155
YES15.02014.670
YES12.31511.946
YES12.41512.052
YES12.51512.158
YES45.46043.6191
YES34.94033.8173
YES36.64035.8192
YES16.62016.195
YES17.42017.0104
4.9
2.2
1.9
4.9
2.2
1.9
5.8
2.6
NO12.21512.079
YES13.61513.267
YES14.42014.176
YES14.42014.080
2.0
COMBUSTION
Table 3—Electrical Data 48HE
COMPRESSOROFM
VOLTAGE
FAN MOTOR
RANGE
IFM TYPEMinMaxQTYRLALRAQTYFLAFLAMCA
STD
0.3†
10.4
187254110.37710.70.6
41450815.13910.40.3
HS5.8
STD
51863214.231
HS2.6
HS2.0
STD
HumidiMi$er10.4†2.6†
STD
187254114.19511.50.6
41450817.14510.80.3
HS5.8
STD
0.3†
10.6
51863216.138
HS2.6
HS2.0
STD
HumidiMi$er10.8†2.6†
STD
187254117.312311.50.6
41450818.47010.80.3†
HS7.5
STD
0.3†
10.6
51863217.153
HS3.4
HS2.8
STD
HumidiMi$er11.9†3.4†
48HE003---006
NOMINAL
V --- P H --- H z
UNIT SIZE
003
208/230--- 1 --- 60STD187254110.96310.70.62.0
208/230--- 1 --- 60STD1872541168810.70.64.9
(2 tons)
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
004
(3 tons)
5 7 5 --- 3 --- 6 0
208/230--- 1 --- 60STD19725412111511.50.64.9
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
005
(4 tons)
5 7 5 --- 3 --- 6 0
208/230--- 1 --- 60STD18725412515011.50.66.6
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
006
(5 tons)
5 7 5 --- 3 --- 6 0
HACR --- Heating, Air Conditioning and Refrigeration
IFM --- Indoor (Evaporator) Fan Motor
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC --- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA --- Rated Load Amps
* The values listed in this table do not include power exhaust. See power exhaust table for power exhaust requirements.
** Fuse or HACR breaker
FLA ---Full Load Amps
{ 460v motor
NOTES:
14
MINIMUM UNI
DISCONNECT SIZE
POWER SUPPLY *
CONV
OUTLET
FLA
IFM
FAN MOTOR
COMBUSTION
FLALRA
MOCP**
NO25.63025101
YES31.63530106
NO18.5251890
NO19.42519120
NO9.015946
NO9.415960
NO7.610736
NO7.710843
NO8.310852
NO35.24534139
NO22.53022106
NO23.43023136
NO10.6151054
NO11.0151168
NO10.3151045
NO10.4151052
NO11.0151161
NO44.16042206
NO28.93528168
NO30.63530187
NO14.7201484
NO15.5201594
NO11.5151163
NO12.3151272
NO12.2151276
NO32.84032200
NO34.54034219
NO15.2201597
NO16.02016107
NO12.4151269
NO13.2201379
YES24.5302495
YES25.43025124
YES11.7151148
YES12.1151263
YES9.715938
YES9.8151044
YES10.4151054
YES41.25039144
YES28.53527111
YES29.43529140
YES13.3151356
YES13.7151370
YES12.5151247
YES12.6151253
YES13.2151363
YES50.16048210
YES34.94034173
YES36.64036192
YES17.4201787
YES18.2201896
YES13.6151364
YES14.4201473
YES14.4201477
YES38.84537205
YES40.54539224
YES17.9201799
YES18.72518109
NO12.8151381
YES14.6201470
YES15.4201580
YES15.0201583
48HE,HJ
4.9
2.2
1.9
4.9
2.2
1.9
5.8
2.6
2.0
0.65.8
2.0
0.32.6
Table 4—Electrical Data 48HJ
COMPRESSOR (each)OFM (each)
VOLTAGE
0.60.3†
10.40.3†
RANGE
IFM TYPEMinMaxQTYRLALRAQTYFLAFLAMCA
STD
187254110.37710.70.6
41450815.13910.40.3
HS5.2
STD
51863214.231
HS2.6
HS2.0
STD
HumidiMi$er10.4†0.9†2.6†
STD
187254113.59310.70.6
HS5.8
STD
10.40.3†
41450816.446.510.40.3
51863216.440
HS2.6
HS2.0
STD
HumidiMi$er10.40.9†2.6†
STD
187254117.312311.50.6
414508196210.80.3
HS7.5
STD
51863217.1501
HS3.4
HS2.8
STD
187254120.515611.4
HS0.67.5
STD
STD
HumidiMi$er0.8†0.3†3.4†
0.80.3†
0.6†0.3†3.4†
41450819.67510.6
51863217.7561
HS0.33.4
HS2.8
STD
HumidiMi$er
48HJ004---014
NOMINAL
V --- P H --- H z
UNIT SIZE
4 6 0 --- 3 --- 6 0
208/230--- 3 60
208/230--- 1 --- 60STD1872541168810.70.64.9
004 (3 Tons)
5 7 5 --- 3 --- 6 0
208/230--- 1 --- 60STD187254123.712610.70.64.9
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
005 (4 Tons)
5 7 5 --- 3 --- 6 0
208/230--- 1 --- 60STD187254128.816911.50.66.6
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
006 (5 Tons)
5 7 5 --- 3 --- 6 0
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
5 7 5 --- 3 --- 6 0
007 (6 Tons)
15
48HE,HJ
NO38.24540242
NO41.34544267
NO19.22520121
NO20.62522134
NO14.6201595
NO15.32017104
NO15.82017104
NO40.24542276
NO43.35046301
NO21.52523143
NO22.92524156
NO18.22019115
NO18.92520124
NO19.42520124
NO53.06056341
NO57.47061364
NO24.93026171
NO27.53029182
NO19.12520136
NO21.02523146
NO21.22523146
NO60.67064426
NO29.13531207
NO23.53025154
YES44.25046247
YES47.35049271
YES21.92523123
YES23.32524136
YES16.8201795
YES17.52019104
YES17.92019104
YES46.25048281
YES49.36051305
YES24.23025145
YES25.63027158
YES20.42521116
YES21.12522126
YES21.52522126
YES59.07061345
YES63.47066369
YES27.63029173
YES30.23532184
YES21.32522138
YES23.12525148
YES23.42525148
YES66.67070431
7.5
3.4
2.8
7.5
3.4
2.8
4.8
10.6
3.3
YES31.83533209
NO23.73025154
YES25.63027156
YES25.93027156
5.6
0.3†
0.60.3†
0.60.3†
0.70.3
0.6
2
0.3†
0.70.37.4
2
20.6
Table 4—Electrical Data 48HJ (cont)
187254212.48821.40.6
STD
41450826.44420.70.3
HS10.6
STD
51863224.8342
HS4.8
HS3.3
STD
187254213.110521.40.6
41450827.45520.70.3
HS10.6
STD
STD
HumidiMi$er0.7†0.3†4.8†
51863226.4442
HS4.8
HS3.3
STD
187254217.612521.40.6
41450828.362.5
HS15.0
STD
STD
HumidiMi$er0.7†0.3†4.8†
51863226.3502
HS7.4
HS5.6
STD
HumidiMi$er0.7†7.4†
51863227.454
STD
HumidiMi$er20.7†7.4†
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
008 (71/2 Tons)
5 7 5 --- 3 --- 6 0
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
009 (81/2 Tons)
5 7 5 --- 3 --- 6 0
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
012 (10 Tons)
5 7 5 --- 3 --- 6 0
4 6 0 --- 3 --- 6 0STD4145082975
Ton s )
014 (121/2
5 7 5 --- 3 --- 6 0
HACR --- Heating, Air Conditioning and Refrigeration
IFM --- Indoor (Evaporator) Fan Motor
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC --- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA --- Rated Load Amps
* The values listed in this table do not include power exhaust. See power exhaust table for power exhaust requirements.
** Fuse or HACR breaker
FLA ---Full Load Amps
{ 460v motor
NOTES:
208/230--- 3 --- 60STD18725421915621.40.615.0
16
Step 8 —Adjust Factory-Installed Options
energy recovery units
cobra
Please refer to the supplement provided for information on
installing and operating the factory optional COBRA Energy
Recovery Units. These units are equipped with a factory--installed
energy recovery unit and have different installation and operation
procedures than the standard unit.
HUMIDI--MIZER
ADAPTIVE DEHUMIDIFICATION
SYSTEM
Humidi-- MiZer system operation can be controlled by field
installation of a Carrier--approved humidistat. (See Fig. 16.)
NOTE: A light commercial Thermidistat device (Fig. 17) can
be used instead of the humidistat if desired. The Thermidistat
device includes a thermostat and a humidistat. The humidistat is
normally used in applications where a temperature sensor is
already provided (units with PremierLink control).
% RELATIVE HUMIDITY
C06126
Fig. 16 --- Accessory Field--Installed Humidistat
C06127
Fig. 17 --- Light Commercial Thermidistat Device
To install the humidistat:
1. Route humidistat cable through hole provided in unit
control box.
2. Some models may be equipped with a raceway built into
the corner post located on the left side of control box (See
Fig. 15). This raceway provides the required clearance
between high--voltage and low voltage wiring. For models
without a raceway, ensure to provide the NEC required
clearance between the high--voltage and low--voltage
wiring.
3. Use a wire nut to connect humidistat cable into lowvoltage wiring as shown in Fig. 18.
To install Thermidistat device:
1. Route Thermidistat cable through hole provided in unit
control box.
2. Some models may be equipped with a raceway built into
the corner post located on the left side of control box (See
Fig. 15). This raceway provides the required clearance
between high--voltage and low voltage wiring. For models
without a raceway, ensure to provide the NEC required
clearance between the high--voltage and low--voltage
wiring.
3. A field-supplied relay must be installed between the
Thermidistat and the Humidi-Mizer circuit (recommended
relay: HN612KK324). (See Fig. 19.) The relay coil is
connected between the DEHUM output and C (common)
of the unit. The relay controls the Humidi-MiZer solenoid
valve and must be wired between the Humidi-MiZer fuse
and the low-pressure switch. Refer to the installation
instructions included with the Carrier Light Commercial
Thermidistat device for more information.
manual outdoor
damper
The outdoor--air hood and screen are attached to the basepan at
the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for building.
Record amount for use in Step 8.
2. Remove and save outdoor air opening panel and screws.
(See Fig. 20.)
3. Remove evaporator coil access panel. Separate hood and
screen from basepan by removing the 4 screws securing
them. Save all screws.
4. Replace evaporator coil access panel.
5. Place hood on front of outdoor air opening panel. See
Fig. 21 for hood details. Secure top of hood with the
4screwsremovedinStep3.(SeeFig.22.)
6. Remove and save 6 screws (3 on each side) from sides of
the manual outdoor-air damper.
7. Align screw holes on hood with screw holes on side of
manual outdoor-air damper. (See Fig. 21 and 22.) Secure
hood with 6 screws from Step 6.
8. Adjust minimum position setting of the damper blade by
adjusting the manual outdoor-air adjustment screws on the
front of the damper blade. (See Fig. 20.) Slide blade
vertically until it is in the appropriate position determined
by Fig. 23. Tighten screws.
9. Remove and save screws currently on sides of hood.
Insert screen. Secure screen to hood using the screws. (See
Fig. 22.)
convenience
outlet
An optional convenience outlet provides power for rooftop use.
For maintenance personnel safety, the convenience outlet power
is off when the unit disconnect is off. Adjacent unit outlets may
be used for service tools.
novar contr
ols
Optional Novar controls (ETM 3051) are available for
replacement or new construction jobs.
Fig. 18 --- Typical Humidi--MiZert Adaptive Dehumidification System
Humidistat Wiring (208/230--V Unit Shown)
LCT
R
C
Y1
Y2
G
W1
W2
DEHUM
OC
TSTAT WIRES
LEGEND
CB— Circuit Breaker
LCT — Light Commercial Thermidistat™ Device
LLSV — Liquid Line Solenoid Valve
LTLO — Low Temperature Lockout
Fig. 19 --- Typical Rooftop Unit with Humidi--Mizer
Adaptive Dehumidification System with Thermidistat Device
OUTDOOR
AIR OPENING
PANEL
3 SCREWS
(SIDE)
R1
R1
ROOF TOP UNIT
R
C
Y1
Y2
G
W1
W2
PINK
PINK
CB
3.2 AMPS
LTLO
HUMIDI-MIZER SYSTEM
RED
PINK
24 V
FROM
HUMIDI-MIZER SYSTEM
LLSV
C06129
Fig. 20 --- Damper Panel with Manual Outdoor--Air
Damper Installed
C06130
C06013
Fig. 21 --- Outdoor--Air Hood Details
18
C06131
Fig. 22 --- Outdoor--Air Damper With
Hood Attached
C06132
Fig. 23 --- Outdoor--Air Damper Position Setting
premierlink
control
The PremierLink controller is compatible with Carrier Comfort
NetworkR (CCN) devices. This control is designed to allow
users the access and ability to change factory--defined settings,
thus expanding the function of the standard unit control board.
Carrier’s diagnostic standard tier display tools such as
Navigatort or Scrolling Marquee can be used with the
PremierLink controller.
The PremierLink controller (see Fig. 24 and 25) requires the use
of a Carrier electronic thermostat or a CCN connection for time
broadcast to initiate its internal timeclock. This is necessary for
broadcast of time of day functions (occupied/unoccupied). No
sensors are supplied with the field-- mounted PremierLink control.
The factory--installed PremierLink control includes only the
supply-- air temperature (SAT) sensor and the outdoor air
temperature (OAT) sensor as standard. An indoor air quality
(CO2) sensor can be added as an option. Refer to Table 5 for
sensor usage. Refer to Fig. 26 for PremierLink controller wiring.
The PremierLink control may be mounted in the control panel or
an area below the control panel.
NOTE: PremierLink controller versions 1.3 and later are shipped
in Sensor mode. If used with a thermostat, the PremierLink
controller must be configured to Thermostat mode.
Install the Supply Air Temperature (SAT) Sensor
When the unit is supplied with a factory--mounted PremierLink
control,thesupply--airtemperature(SAT)sensor
(33ZCSENSAT) is factory-- supplied and wired. The wiring is
routed from the PremierLink control over the control box,
through a grommet, into the fan section, down along the back
side of the fan, and along the fan deck over to the supply--air
opening.
The SAT probe is wire--tied to the supply--air opening (on the
horizontal opening end) in its shipping position. Remove the
sensor for installation. Re-- position the sensor in the flange of the
supply-- air opening or in the supply air duct (as required by local
codes). Drill or punch a 1/2--in. hole in the flange or duct. Use
two field--supplied, self--drilling screws to secure the sensor probe
in a horizontal orientation.
NOTE: The sensor must be mounted in the discharge airstream
downstream of the cooling coil and any heating devices. Be sure
the probe tip does not come in contact with any of the unit or heat
surfaces.
Outdoor Air Temperature Sensor (OAT)
When the unit is supplied with a factory-mounted PremierLink
control and economizer, the outdoor-air temperature sensor
(OAT) is factory-supplied and wired.
Install the Indoor Air Quality (CO
Mount the optional indoor air quality (CO
)Sensor
2
) sensor according to
2
manufacturer specifications.
A separate field-supplied transformer must be used to power the
sensor.
CO
2
Wire the CO
sensor to the COM and IAQI terminals of J5 on the
2
PremierLink controller. Refer to the PremierLink Installation,
Start-up, and Configuration Instructions for detailed wiring and
configuration information.
Enthalpy Sensors and Control
The enthalpy control (HH57AC077) is supplied as a
field-installed accessory to be used with the EconoMi$er2
damper control option. The outdoor air enthalpy sensor is part of
the enthalpy control. The separate field-installed accessory return
air enthalpy sensor (HH57AC078) is required for differential
enthalpy control.
NOTE: The enthalpy control must be set to the “D” setting for
differential enthalpy control to work properly.
Theenthalpycontrol receives theindoor and return
enthalpy from the outdoor and return air enthalpy sensors and
provides a dry contact switch input to the PremierLink controller.
Locate the controller in place of an existing economizer controller
or near the actuator. The mounting plate may not be needed if
existing bracket is used.
A closed contact indicates that outside air is preferred to the
return air. An open contact indicates that the economizer should
remain at minimum position.
Outdoor Air Enthalphy Sensor/Enthalpy Controller
(HH57AC077)
T o wire the out door air enthalpy sensor, perform the following (See
Fig. 27 and 28):
NOTE: The outdoor air sensor can be removed from the back of
the enthalpy controller and mounted remotely.
48HE,HJ
19
Table 5—PremierLink Sensor Usage
APPLICATION
OUTDOOR AIR
TEMPERATURE SENSOR
RETURN AIR
TEMPERATURE SENSOR
OUTDOOR AIR
ENTHALPY SENSOR
Differential Dry Bulb
Tem p e r a tu r e w i th
PremierLink*
(PremierLink
requires 4-20 mA
I n c l u d e d ---
CRTEMPSN001A00
R e q u i r e d --33ZCT55SPT
or Equivalent
Actuator)
Single Enthalpy with
PremierLink*
(PremierLink
requires 4-20 mA
Actuator)
I n c l u d e d ---
Not Used
—
R e q u i r e d --HH57AC077
or Equivalent
Differential Enthalpy
with PremierLink*
(PremierLink
requires 4-20 mA
I n c l u d e d ---
Not Used
—
Actuator)
*PremierLink control requires Supply Air Temperature sensor 33ZCSENS AT and Outdoor Air Temperature sensor CRTEMPSN001A00
48HE,HJ
— Included with factory-installed PremierLink control; field-supplied and field-installed with field-installed PremierLink control.
NOTES:
1. CO
Sensors (Optional):
2
33ZCSENCO2 — Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.
33ZCASPCO2 — Aspirator box used for duct-mounted CO
33ZCT55CO2 — Space temperature and CO
33ZCT56CO2 — Space temperature and CO
2. All units include the following Standard Sensors:
Outdoor-Air Sensor — 50HJ540569 — Opens at 67_F, c l o s e s at 5 2 _F, not adjustable.
Mixed-Air Sensor — HH97AZ001 — (PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT
and Outdoor Air Temperature Sensor CRTEMPSN001A00)
Compressor Lockout Sensor — 50HJ540570 — Opens at 35_F, cl o s e s at 50 _F.
room sensor with override.
2
room sensor with override and set point.
2
room sensor.
2
R e q u i r e d --HH57AC077
or Equivalent
RETURN AIR
ENTHALPY SENSOR
——
—
R e q u i r e d ---
HH57AC078
or Equivalent
Fig. 24 --- PremierLink Controller
20
C06016
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.