Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install, repair,
or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of
cleaning coils and filters and replacing filters. All other operations
should be performed by trained service personnel. When working
on air-conditioning equipment, observe precautions in the
literature, tags and labels attached to the unit, and other safety
precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguishers
available for all brazing operations.
Recognize safety information. This is the safety--alert symbol
.When you see this symbol on the furnace and in
instructions or manuals, be alert to the potential for personal
injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced installation,
reliability, or operation.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
Before performing service or maintenance operations
on unit, turn off main power switch to unit and install
lockout tag. Ensure electrical service to rooftop unit
agrees with voltage and amperage listed on the unit
rating plate.
WARNING
1
Page 2
!
FIRE, EXPLOSION HAZARD
Failure to follow this warning could death and/or
property damage.
Disc onnect gas piping from unit when leak testing at
pressure greater than
psig will cause gas valve damage resulting in hazardous
condition. If gas va lve is subjecte d to pressure greater than
1
/2psig, it must be replaced before use. When pressure
testing field-supplied gas piping at pressures of
less, a uni t connected to such piping must be i solated by
manual l y closing the gas valve(s).
WARNING
1
/2psig. Pressures greater than1/
1
/2psig or
INSTALLATION
Unit is shipped in the vertical discharge configuration. To convert
to horizontal discharge application, remove duct opening covers.
Using the same screws, install covers on duct openings in
48HE,HJ
basepan of unit with insulation-side down. Seals around
openings must be tight. (See Fig. 1.)
Fig. 1 --- Horizontal Conversion Panels
Step 1 —Provide Unit Support
CURB
ROOF
Assemble and install accessory roof curb in accordance with
instructions shipped with curb. (See Fig. 2.) Install insulation,
cant strips, roofing felt, and counter flashing as shown. Ductworkmust be attached to curb, not to the unit. If electric control power
or gas service is to be routed through the basepan, attach the
accessory thru-the-bottom service connections to the basepan in
accordancewiththeaccessoryinstallationinstructions.
Connections must be installed before unit is set on roof curb.
IMPORTANT: The gasketing of the unit t o the roof curb is critical
for a watertight seal. Install gasket supplied with the roof curb as
shown in Fig. 2. Improperl y applied gasket can result in air leaks and
poor unit performanc e.
Curb should be level. Unit leveling tolerances are shown in Fig.
3. This is necessary for unit drain to function properly. Refer to
Accessory Roof Curb Installation Instructions for additional
information as required.
SLAB MOUNT (Horizontal Units Only)
Provide a level concrete slab that extends a minimum of 6 in.
beyond unit cabinet. Install a gravel apron in front of
2
C06108
condenser-coil air inlet to prevent grass and foliage from
obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
ALTERNATE UNIT SUPPORT
When the curb or adapter cannot be used, support unit with
sleeper rails using unit curb or adapter support area. If sleeper
rails cannot be used, support the long sides of the unit with a
minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
Step 2 —Field Fabricate Ductwork
Secure all ducts to roof curb and building structure on vertical
discharge units. Do not connect ductwork to unit. For horizontal
applications, field-supplied isolation flanges should be attached to
horizontal discharge openings and all ductwork should be secured
to the flanges. Insulate and weatherproof all external ductwork,
joints, and roof openings with counter flashing and mastic in
accordance with applicable codes.
Ducts passing through an unconditioned space must be insulated
and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be
ducted through the roof deck to comply with applicable fire
codes.
A minimum clearance is not required around ductwork. Cabinet
return-air static pressure (a negative condition) shall not exceed
0.35 in. wg with economizer or 0.45 in. wg without economizer.
These units are designed for a minimum continuous return-air
temperature in heating of 50_F (dry bulb), or an intermittent
operation down to 45_F (dry bulb), such as when used with a
night setback thermostat.
To operate at lower return-air temperatures, a field-supplied
outdoor air temperature control must be used to initiate both
stages of heat when the temperature is below 45_F. Indoor
comfort may be compromised when these lower air temperatures
are used with insufficient heating temperature rise.
Step 3 —Install External Trap for
Condensate Drain
3
The unit’s
bottom and side of the unit. Unit discharge connections do not
determine the use of drain connections; either drain connection
can be used with vertical or horizontal applications.
When using the standard side drain connection, ensure the plug
(Red) in the alternate bottom connection is tight before installing
the unit.
To use the bottom drain connection for a roof curb installation,
relocate the factory-installed plug (Red) from the bottom
connection to the side connection. The center drain plug looks
like a star connection, however it can be removed with a
socket drive extension. (See Fig. 4.) The piping for the
condensate drain and external trap can be completed after the unit
is in place.
All units must have an external trap for condensate drainage.
Install a trap 4-in. deep and protect against freeze-up. If drain line
is installed downstream from the external trap, pitch the line away
from the unit at 1 in. per 10 ft of run. Do not use a pipe size
smaller than the unit connection (
Step 4 —Rig a nd Place Unit
Inspect unit for transportation damage, and file any claim with
transportation agency. Keep unit upright and do not drop.
Spreader bars are not required if top crating is left on unit, and
rollers may be used to move unit across a roof. Level by using
unit frame as a reference. See Table 1 and 2 and Fig. 6 for
additional information. Operating weight is shown in Table 1 and
2 and Fig. 6.
/4-in. condensate drain connections are located on the
1
/2-in.
3
/4in.). (See Fig. 5.)
2
Page 3
1-4
[406]
DALT
DRAIN
HOLE
13/4
[44.5]
GASPOWERCONTROL
3
/4
[19] NPT
1
/2
[12.7] NPT
3
/4
[19] NPT
CONNECTOR
PKG. ACCY.
BC
CRBTMPWR001A01
CRBTMPWR002A011
CRBTMPWR003A01
1-9
11
[551]
/16
CRBTMPWR004A01
3
/4 [19] NPT
1
/4 [31.7]
3
/4 [19] NPT
1
/4 [31.7]
1
1
/2
[12.7]
ACCESSORY
POWER
1
/2
[12.7]
ROOF CURB
ACCESSORY
CRRFCURB001A01
CRRFCURB002A01
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb (flanges of duct rest
on curb).
6. Service clearance: 4 ft on each side.
1-2
[356]
2-0
[610]
A
48HJ004-007
48HE003-006
UNIT
SIZE
7.Direction of airflow.
8. Connector packages CRBTMPWR001A01
and 002A01 are for thru-the-curb type gas.
Packages CRBTMPWR003A01 and 004A01
are for thru-the-bottom type gas connections.
48HE,HJ
Fig. 2 --- Roof Curb Details
3
C06109
Page 4
Lifting holes are provided in base rails as shown in Fig. 8 and 9.
Refer to rigging instructions on unit.
!
WARNING
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal
injury, death and property damage.
All panels must be in place when rigging and lifting.
positioning
Maintain clearance around and above unit to provide minimum
distance from combustible materials, proper airflow, and service
access. (See Fig. 7, 8 and 9.)
Position unit on roof curb so that the following clearances are
maintained:
1
/4in. clearance between the roof curb and the base
rail inside the front and rear, 0.0 in. clearance between the roof
curb and the base rail inside on the duct end of the unit. This will
result in the distance between the roof curb and the base rail
48HE,HJ
inside on the condenser end of the unit being approximately
equal to Fig. 2, section C-C.
Do not install unit in an indoor location. Do not locate unit air
inlets near exhaust vents or other sources of contaminated air.
Flue vent discharge must have a minimum horizontal clearance of
4 ft from electric and gas meters, gas regulators, and gas relief
equipment.
After unit is in position, remove shipping materials and rigging
skids.
Step 5 —Install Flue Hood
Flue hood is shipped screwed to the burner compartment access
panel. Remove from shipping location and, using screws
provided, install flue hood in location shown in Fig. 8 and 9.
For units being installed in California Air Quality Management
Districts which require NOx emissions of 40 nanograms/joule or
less, a low NOx unit must be installed.
NOTE: Low NOx units are available for 3 to 5 ton units.
CONDENSATE PAN (SIDE VIEW)
HORIZONTAL
DRAIN OUTLET
NOTE: Drain plug is shown in factory-installed position.
DRAIN PLUG
C06003
Fig. 4 --- Condensate Drain Pan
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-BB-CA-C
0.51.01.0
C06110
Fig. 3 --- Unit Leveling Tolerances
Be sure that unit is installed such that snow will not block the
combustion intake or flue outlet.
Unit may be installed directly on wood flooring or on Class A, B,
or C roof-covering material when roof curb is used.
Although unit is weatherproof, guard against water from higher
level runoff and overhangs.
Locate mechanical draft system flue assembly at least 48 in. from
an adjacent building or combustible material. When unit is
located adjacent to public walkways, flue assembly must be at
least 7 ft above grade.
NOTE: When unit is equipped with an accessory flue discharge
deflector, allowable clearance is 18 inches.
Flue gas can deteriorate building materials. Orient unit such that
flue gas will not affect building materials.
Adequate combustion-air space must be provided for proper
operation of this equipment. Be sure that installation complies
with all local codes and Section 5.3, Air for Combustion and
Ventilation, NFGC (National Fuel Gas Code), ANSI (American
National Standards Institute) Z223.1-1984 and addendum
Z223.1a-1987. In Canada, installation must be in accordance with
the CAN1.B149.1 and CAN1.B149.2 installation codes for gas
burning appliances.
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4-in. trap is recommended.
C06004
Fig. 5 --- Condensate Drain Piping Details
Step 6 —Install Gas Piping
Unit is equipped for use with type of gas shown on nameplate.
Refer to localbuilding codes, or in the absence of local codes,
to ANSI Z223.1-1984 and addendum Z223.1A-1987 entitled
National Fuel Gas Code. In Canada, installation must be in
accordancewiththeCAN1.B149.1andCAN1.B149.2
installation codes for gas burning appliances.
For natural gas applications, gas pressure at unit gas connection
must not be less than 4 in. wg or greater than 13 in. wg while the
unit is operating. On 48HJ005-007 high-heat units, the gas
pressure at unit gas connection must not be less than 5 in. wg or
greater than 13 in. wg while the unit is operating. For propane
applications, the gas pressure must not be less than 5 in. wg or
greater than 13 in. wg at the unit connection.
Size gas supply piping for 0.5 in. wg maximum pressure drop.
Do not use supply pipe smaller than unit gas connection.
Support gas piping as shown in the table in Fig. 11. For example,
3
/4-in. gas pipe must have one field-fabricated support beam
a
every 8 ft. Therefore, an 18-ft long gas pipe would have a
minimum of 3 support beams, and a 48-ft long pipe would have a
minimum of 6 support beams.
OPERATING
WEIGHT
lbkgin.mmin.mmin.mm
OPERATING
WEIGHT
lbkgin.mmin.mmin.mm
C06208
DIMENSIONS
“A”“B”“C”
DIMENSIONS
“A”“B”“C”
!
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal
injury, death and property damage.
All panels must be in place when rigging and lifting.
See Fig. 11 for typical pipe guide and locations of external
manual gas shutoff valve.
NOTE: If accessory thru-the-bottom connections and roof curb
are used, refer to the Thru-the-Bottom Accessory Installation
Instructions for information on power wiring and gas
connection piping. The power wiring, control wiring and gas
piping can be routed through field-drilled holes in the basepan.
The basepan is specially designed and dimpled for drilling the
access connection holes.
!
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
When connecting the gas line to the unit gas valve, the
installer MUST use a backup wrench to prevent damage
to the valve.
WARNING
WARNING
48HE,HJ
5
Page 6
C06112
48HE,HJ
Fig. 8 --- 48HJ004--007 Base Unit Dimensions
6
Page 7
C06113
48HE,HJ
Fig. 9 --- 48HE003--006 Base Unit Dimensions
7
Page 8
Fig. 10 --- Flue Hood Details
*
48HE,HJ
LEGEND
NFGC — National Fuel Gas Code
Field supplied.
NOTE: Follow all local codes.
SPACING OF SUPPORTS
STEEL PIPE
NOMINAL DIAMETER (in.)
1
/
3
/4or 1
1
/4or larger
1
2
Fig. 11 --- Gas Piping Guide (With Accessory
Thru--the--Curb Service Connections)
Step 7 —Make Electrical Connections
!
WARNING
ELECTRICAL SHOCK HAZARD
Failur e to follow this warning could result in personal
injury or death.
Unit cabinet must have an uninterrupt ed, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should oc cur . This gr ound may
consist of el ectrical wire connec ted to unit ground lug i n
control compartme nt, or conduit approved for electr i cal
ground whe n install ed in accordance with NEC (National
Electrical Code), ANSI/NFPA (National Fire Protection
Association), latest edition, and local electrical codes. Do
not use gas piping as an electr i cal ground.
SPACING OF SUPPORTS
X DIMENSION (ft)
10
field power supply
All units except 208/230-v units are factory wired for the voltage
shown on the nameplate. If the 208/230-v unit is to be connected
to a 208-v power supply, the transformer must be rewired by
moving the black wire from the 230-v terminal on the
transformer and connecting it to the 200-v terminal from the
transformer.
Refer to unit label diagram for additional information. Pigtails
are provided for field service. Use factory-supplied splices or UL
(Underwriters’ Laboratories) approved copper connector.
When installing units, provide a disconnect per NEC.
All field wiring must complywith NEC and local
requirements.
C06114
Install conduit through side panel openings indicated in Fig. 8.
Route power lines through connector to terminal connections as
shown in Fig. 12.
Voltage to compressor terminals during operation must be within
voltage range indicated on unit nameplate (also see Tables 3 and
4). On 3-phase units, voltages between phases must be balanced
within 2% and the current within 10%. Use the formula shown in
Tables 3 and 4, Note 3 to determine the percent voltage
imbalance. Operation on improper line voltage or excessive phase
imbalance constitutes abuse and may cause damage to electrical
components. Such operation would invalidate any applicable
Carrier warranty.
NOTE: If accessory thru-the-bottom connections and roof curb
are used, refer to the Thru-the-Bottom Accessory Installation
Instructions for information on power wiring and gas connection
piping. The power wiring, control wiring and gas piping can be
routed through field-drilled holes in the basepan. The basepan is
specially designed and dimpled for drilling the access connection
holes.(SeeFig.2.)
field control
wiring
Install a Carrier-approved accessory thermostat assembly
according to installation instructions included with the accessory.
Locate thermostat assembly on a solid wall in the conditioned
6
8
C06115
space to sense average temperature in accordance with thermostat
installation instructions.
Route thermostat cable or equivalent single leads of colored wire
from subbase terminals through connector on unit to low-voltage
connections (shown in Fig. 13 and 14).
Connect thermostat wires to matching screw terminals of
low-voltage connection board. (See Fig. 13 and 14.)
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gauge) insulated wire (35_Cminimum).For50to75ft,use
no. 16 AWG insulated wire (35_C minimum). For over 75 ft, use
no. 14 AWG insulated wire (35_C minimum). All wire larger
than no. 18 AWG cannot be directly connected to the thermostat
and will require a junction box and splice at the thermostat.
Pass the control wires through the hole provided in thecorner
post; then feed wires through the raceway built into the corner
post to the 24-v barrier located on the left side of the control box.
(See Fig. 15). The raceway provides the UL required clearance
between high and low-voltage wiring.
heat anticipator
settings
Set heat anticipator settings at 0.14 amp for first stage and 0.14
for second stage heating, when available.
8
Page 9
Table 1—Physical Data 48HJ
BASE UNIT 48HJHJE/F/H/K/M/N004 HJD/E/F/G/H/K/L/M/N005 HJD/E/F/G/H/K/L/M/N006 HJD/E/F007
NOMINAL CAPACITY
OPERATING WEIGHT (lb)
Unit
Humidi-MiZer Adaptive Dehumidification System
EconoMi$er IV
Roof Cur b
COMPRESSOR
Quantity
Oil (oz)
REFRIGERANT TYPE
Expansion Device
Operating Charge (lb-oz)
Standard Unit
Unit With Humidi-Mizer Adaptive Dehu midification System
CONDENSER FAN
Quantity...Diameter (in.)
Nominal C f m
Motor Hp...Rpm
Watts Input (Total)
CONDENSER COIL
Rows...Fins/in.
Tot a l Fa ce A r e a (s q f t )
EVAPORATOR COIL
Standard Unit
Rows...Fins/in.
Tot a l Fa ce A r e a (s q f t )
Unit with Humidi-Mizer Adaptive Dehumidification System
Rows...Fins/in.
Tot a l Fa ce A r e a (s q f t )
EVAPORATOR FAN
Quantity...Size (in.)
Nominal C f m
Maximum Continuous BhpStd
Hi-Static
Motor RPMStd
Hi-Static
Motor Frame SizeStd
Hi-Static
Fan Rpm Ran geStd
Hi-Static
Motor Bearing Type
Maximum Fan Rpm
Motor Pulley Pitch Diameter A/B (in.)
Std
Hi-Static
Nominal Motor Shaft Diameter (in.)Std
Hi-Static
Fan Pulley Pitch Diameter (in.)Std
Hi-Static
Belt — Type...Length (in.)Std
Hi-Static
Pulley Center Line Distance (in.)
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full
Turns from Closed Position
Std
Hi-Static
Std
Hi-Static
Factory Setting — Full Turns OpenStd
Hi-Static
Factory Speed Setting (rpm)Std
Hi-Static
Fan Shaft Diameter at Pulley (in.)
LEGEND
Bhp — Brake Horsepower
*Single phase/three phase.
†Indicates automatic reset.
**60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and120,000
Btuh heat input units have 3 burners. 115,000 Btuh heat input units and 150,000
Btuh Heat input units have 3 burners.
††An LP kit is available as an accessory. Kit may be used at elevations as high as 2000
ft. If an LP ki t is used with Low NOx units, the Low NOx baffle must be removed and
the units will no longer be classified a s Low NOx units.
ll Three-phase standard models have heating inputs as shown. Single-phase standard mo dels have one-stage heating wi th heating input va lues as follows:
Cleanable. Screen quantity and size varies with option selected.
Throwaway
2...16 x 25 x 24...16 x 16 x 2
the units will no longer be classified a s Low NOx units.
ll Three-phase standard models have heating inputs as shown. Single-phase standard mo dels have one-stage heating wi th hea ting input values as fo llows:
—HEK 50-80HEK 50-80
HEM 20-50HEL 20-50HEL 20-50
HEN 30-60HEM 30-60HEM 30-60
HEN 40-70HEN 40-70
3.53.53.53.5
3.53.53.53.5
1.01.01.01.0
1
/
2
1
/
2
1
/
2
450 50
428
320
7 3
22 5
30 5
45 5
Cleanable. Screen quantity and size varies with option selected.
Throwaway
2...16 x 25 x 2
Low NOx requirement only applies to natural gas units.
Three-phase standard models have heating i nputs as shown. Si ngle-phase standa rd
models have one-stage heating with heating input values as shown in heatin capacity tables.
***These units do NOT meet the California low NOx requirements.
†††California SCAQMD compliant low NOxmodels have combustion products that are
NEC— National Electrical Code
TB— Te r m i na l B l o ck
Fan Contactor
48HE,HJ
C06124
Y1
Y2
W1
W2
IPD/X
R
G
C
WIRE
CONNECTIONS
TO
LOW-VOLTAGE
SECTION
COOL STAGE 1
FAN
HEAT STAGE 1
COOL STAGE 2
HEAT STAGE 2
24 VAC HOT
24 VAC COM
N/A
OUTDOOR AIR
SENSOR
THERMOSTAT DIPSWITCH SETTINGS
ON
OFF
A
LEGEND
NOTE: Un derlined letter indicates active thermostat output when
configured for A/C operation.
Y1/W2
G
W/W1
Y/Y2
O/W2
R
C
S1
S2
B
C
Field Wiring
D
Fig. 13 --- Low--Voltage connections With or
Without Economizer or Two-- Position Damper
CONTROL
CONNECTION
BOARD
24 VAC
R
RMTOCC
G
CMPSAFE
Y2
FSD
W1
SFS
NOT USED
C
C
X
X
THERMOSTAT CONTROL
CONNECTION
BOARD
R
Y1
Y2
W1
W2
G
C
R
Y1
Y2
W1
W2
G
C
X
Fig. 14 --- Low--Voltage Connections
(Units with PremierLinkt Controls)
C06008
C06009
LOW VOLTAGE
CONNECTIONS
INTEGRATED GAS UNIT
CONTROLLER (IGC)
Fig. 15 --- Field Control Wiring
C06125
13
Page 14
48HE,HJ
MINIMUM UNIT
DISCONNECT SIZE
POWER SUPPLY *
CONV
OUTLET
IFM
FLA
FLALRA
MOCP**
NO16.32015.669
NO25.63024.8101
NO18.52518.390
NO19.42519.3120
NO9.0158.946
NO9.4159.360
NO7.6107.536
NO7.7107.643
NO7.7108.048
NO32.74031.5130
NO24.03023.6110
NO24.93024.6140
NO11.91511.653
NO12.31512.167
NO10.1159.944
NO10.21510.051
NO10.31510.156
NO39.45038.1187
NO28.93528.3168
NO30.63530.2187
NO13.92013.692
NO14.72014.5102
NO11.51511.266
NO12.31512.175
YES22.32521.273
YES31.63530.4106
YES24.53023.895
YES25.43024.9124
YES11.71511.448
YES12.11511.863
YES9.7159.538
YES9.8159.644
YES9.8159.650
YES38.74537.0135
YES30.03529.1115
YES30.93530.1145
YES14.62014.155
YES15.02014.670
YES12.31511.946
YES12.41512.052
YES12.51512.158
YES45.46043.6191
YES34.94033.8173
YES36.64035.8192
YES16.62016.195
YES17.42017.0104
4.9
2.2
1.9
4.9
2.2
1.9
5.8
2.6
NO12.21512.079
YES13.61513.267
YES14.42014.176
YES14.42014.080
2.0
COMBUSTION
Table 3—Electrical Data 48HE
COMPRESSOROFM
VOLTAGE
FAN MOTOR
RANGE
IFM TYPEMinMaxQTYRLALRAQTYFLAFLAMCA
STD
0.3†
10.4
187254110.37710.70.6
41450815.13910.40.3
HS5.8
STD
51863214.231
HS2.6
HS2.0
STD
HumidiMi$er10.4†2.6†
STD
187254114.19511.50.6
41450817.14510.80.3
HS5.8
STD
0.3†
10.6
51863216.138
HS2.6
HS2.0
STD
HumidiMi$er10.8†2.6†
STD
187254117.312311.50.6
41450818.47010.80.3†
HS7.5
STD
0.3†
10.6
51863217.153
HS3.4
HS2.8
STD
HumidiMi$er11.9†3.4†
48HE003---006
NOMINAL
V --- P H --- H z
UNIT SIZE
003
208/230--- 1 --- 60STD187254110.96310.70.62.0
208/230--- 1 --- 60STD1872541168810.70.64.9
(2 tons)
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
004
(3 tons)
5 7 5 --- 3 --- 6 0
208/230--- 1 --- 60STD19725412111511.50.64.9
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
005
(4 tons)
5 7 5 --- 3 --- 6 0
208/230--- 1 --- 60STD18725412515011.50.66.6
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
006
(5 tons)
5 7 5 --- 3 --- 6 0
HACR --- Heating, Air Conditioning and Refrigeration
IFM --- Indoor (Evaporator) Fan Motor
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC --- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA --- Rated Load Amps
* The values listed in this table do not include power exhaust. See power exhaust table for power exhaust requirements.
** Fuse or HACR breaker
FLA ---Full Load Amps
{ 460v motor
NOTES:
14
Page 15
MINIMUM UNI
DISCONNECT SIZE
POWER SUPPLY *
CONV
OUTLET
FLA
IFM
FAN MOTOR
COMBUSTION
FLALRA
MOCP**
NO25.63025101
YES31.63530106
NO18.5251890
NO19.42519120
NO9.015946
NO9.415960
NO7.610736
NO7.710843
NO8.310852
NO35.24534139
NO22.53022106
NO23.43023136
NO10.6151054
NO11.0151168
NO10.3151045
NO10.4151052
NO11.0151161
NO44.16042206
NO28.93528168
NO30.63530187
NO14.7201484
NO15.5201594
NO11.5151163
NO12.3151272
NO12.2151276
NO32.84032200
NO34.54034219
NO15.2201597
NO16.02016107
NO12.4151269
NO13.2201379
YES24.5302495
YES25.43025124
YES11.7151148
YES12.1151263
YES9.715938
YES9.8151044
YES10.4151054
YES41.25039144
YES28.53527111
YES29.43529140
YES13.3151356
YES13.7151370
YES12.5151247
YES12.6151253
YES13.2151363
YES50.16048210
YES34.94034173
YES36.64036192
YES17.4201787
YES18.2201896
YES13.6151364
YES14.4201473
YES14.4201477
YES38.84537205
YES40.54539224
YES17.9201799
YES18.72518109
NO12.8151381
YES14.6201470
YES15.4201580
YES15.0201583
48HE,HJ
4.9
2.2
1.9
4.9
2.2
1.9
5.8
2.6
2.0
0.65.8
2.0
0.32.6
Table 4—Electrical Data 48HJ
COMPRESSOR (each)OFM (each)
VOLTAGE
0.60.3†
10.40.3†
RANGE
IFM TYPEMinMaxQTYRLALRAQTYFLAFLAMCA
STD
187254110.37710.70.6
41450815.13910.40.3
HS5.2
STD
51863214.231
HS2.6
HS2.0
STD
HumidiMi$er10.4†0.9†2.6†
STD
187254113.59310.70.6
HS5.8
STD
10.40.3†
41450816.446.510.40.3
51863216.440
HS2.6
HS2.0
STD
HumidiMi$er10.40.9†2.6†
STD
187254117.312311.50.6
414508196210.80.3
HS7.5
STD
51863217.1501
HS3.4
HS2.8
STD
187254120.515611.4
HS0.67.5
STD
STD
HumidiMi$er0.8†0.3†3.4†
0.80.3†
0.6†0.3†3.4†
41450819.67510.6
51863217.7561
HS0.33.4
HS2.8
STD
HumidiMi$er
48HJ004---014
NOMINAL
V --- P H --- H z
UNIT SIZE
4 6 0 --- 3 --- 6 0
208/230--- 3 60
208/230--- 1 --- 60STD1872541168810.70.64.9
004 (3 Tons)
5 7 5 --- 3 --- 6 0
208/230--- 1 --- 60STD187254123.712610.70.64.9
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
005 (4 Tons)
5 7 5 --- 3 --- 6 0
208/230--- 1 --- 60STD187254128.816911.50.66.6
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
006 (5 Tons)
5 7 5 --- 3 --- 6 0
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
5 7 5 --- 3 --- 6 0
007 (6 Tons)
15
Page 16
48HE,HJ
NO38.24540242
NO41.34544267
NO19.22520121
NO20.62522134
NO14.6201595
NO15.32017104
NO15.82017104
NO40.24542276
NO43.35046301
NO21.52523143
NO22.92524156
NO18.22019115
NO18.92520124
NO19.42520124
NO53.06056341
NO57.47061364
NO24.93026171
NO27.53029182
NO19.12520136
NO21.02523146
NO21.22523146
NO60.67064426
NO29.13531207
NO23.53025154
YES44.25046247
YES47.35049271
YES21.92523123
YES23.32524136
YES16.8201795
YES17.52019104
YES17.92019104
YES46.25048281
YES49.36051305
YES24.23025145
YES25.63027158
YES20.42521116
YES21.12522126
YES21.52522126
YES59.07061345
YES63.47066369
YES27.63029173
YES30.23532184
YES21.32522138
YES23.12525148
YES23.42525148
YES66.67070431
7.5
3.4
2.8
7.5
3.4
2.8
4.8
10.6
3.3
YES31.83533209
NO23.73025154
YES25.63027156
YES25.93027156
5.6
0.3†
0.60.3†
0.60.3†
0.70.3
0.6
2
0.3†
0.70.37.4
2
20.6
Table 4—Electrical Data 48HJ (cont)
187254212.48821.40.6
STD
41450826.44420.70.3
HS10.6
STD
51863224.8342
HS4.8
HS3.3
STD
187254213.110521.40.6
41450827.45520.70.3
HS10.6
STD
STD
HumidiMi$er0.7†0.3†4.8†
51863226.4442
HS4.8
HS3.3
STD
187254217.612521.40.6
41450828.362.5
HS15.0
STD
STD
HumidiMi$er0.7†0.3†4.8†
51863226.3502
HS7.4
HS5.6
STD
HumidiMi$er0.7†7.4†
51863227.454
STD
HumidiMi$er20.7†7.4†
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
008 (71/2 Tons)
5 7 5 --- 3 --- 6 0
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
009 (81/2 Tons)
5 7 5 --- 3 --- 6 0
4 6 0 --- 3 --- 6 0
208/230--- 3 --- 60
012 (10 Tons)
5 7 5 --- 3 --- 6 0
4 6 0 --- 3 --- 6 0STD4145082975
Ton s )
014 (121/2
5 7 5 --- 3 --- 6 0
HACR --- Heating, Air Conditioning and Refrigeration
IFM --- Indoor (Evaporator) Fan Motor
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC --- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA --- Rated Load Amps
* The values listed in this table do not include power exhaust. See power exhaust table for power exhaust requirements.
** Fuse or HACR breaker
FLA ---Full Load Amps
{ 460v motor
NOTES:
208/230--- 3 --- 60STD18725421915621.40.615.0
16
Page 17
Step 8 —Adjust Factory-Installed Options
energy recovery units
cobra
Please refer to the supplement provided for information on
installing and operating the factory optional COBRA Energy
Recovery Units. These units are equipped with a factory--installed
energy recovery unit and have different installation and operation
procedures than the standard unit.
HUMIDI--MIZER
ADAPTIVE DEHUMIDIFICATION
SYSTEM
Humidi-- MiZer system operation can be controlled by field
installation of a Carrier--approved humidistat. (See Fig. 16.)
NOTE: A light commercial Thermidistat device (Fig. 17) can
be used instead of the humidistat if desired. The Thermidistat
device includes a thermostat and a humidistat. The humidistat is
normally used in applications where a temperature sensor is
already provided (units with PremierLink control).
% RELATIVE HUMIDITY
C06126
Fig. 16 --- Accessory Field--Installed Humidistat
C06127
Fig. 17 --- Light Commercial Thermidistat Device
To install the humidistat:
1. Route humidistat cable through hole provided in unit
control box.
2. Some models may be equipped with a raceway built into
the corner post located on the left side of control box (See
Fig. 15). This raceway provides the required clearance
between high--voltage and low voltage wiring. For models
without a raceway, ensure to provide the NEC required
clearance between the high--voltage and low--voltage
wiring.
3. Use a wire nut to connect humidistat cable into lowvoltage wiring as shown in Fig. 18.
To install Thermidistat device:
1. Route Thermidistat cable through hole provided in unit
control box.
2. Some models may be equipped with a raceway built into
the corner post located on the left side of control box (See
Fig. 15). This raceway provides the required clearance
between high--voltage and low voltage wiring. For models
without a raceway, ensure to provide the NEC required
clearance between the high--voltage and low--voltage
wiring.
3. A field-supplied relay must be installed between the
Thermidistat and the Humidi-Mizer circuit (recommended
relay: HN612KK324). (See Fig. 19.) The relay coil is
connected between the DEHUM output and C (common)
of the unit. The relay controls the Humidi-MiZer solenoid
valve and must be wired between the Humidi-MiZer fuse
and the low-pressure switch. Refer to the installation
instructions included with the Carrier Light Commercial
Thermidistat device for more information.
manual outdoor
damper
The outdoor--air hood and screen are attached to the basepan at
the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for building.
Record amount for use in Step 8.
2. Remove and save outdoor air opening panel and screws.
(See Fig. 20.)
3. Remove evaporator coil access panel. Separate hood and
screen from basepan by removing the 4 screws securing
them. Save all screws.
4. Replace evaporator coil access panel.
5. Place hood on front of outdoor air opening panel. See
Fig. 21 for hood details. Secure top of hood with the
4screwsremovedinStep3.(SeeFig.22.)
6. Remove and save 6 screws (3 on each side) from sides of
the manual outdoor-air damper.
7. Align screw holes on hood with screw holes on side of
manual outdoor-air damper. (See Fig. 21 and 22.) Secure
hood with 6 screws from Step 6.
8. Adjust minimum position setting of the damper blade by
adjusting the manual outdoor-air adjustment screws on the
front of the damper blade. (See Fig. 20.) Slide blade
vertically until it is in the appropriate position determined
by Fig. 23. Tighten screws.
9. Remove and save screws currently on sides of hood.
Insert screen. Secure screen to hood using the screws. (See
Fig. 22.)
convenience
outlet
An optional convenience outlet provides power for rooftop use.
For maintenance personnel safety, the convenience outlet power
is off when the unit disconnect is off. Adjacent unit outlets may
be used for service tools.
novar contr
ols
Optional Novar controls (ETM 3051) are available for
replacement or new construction jobs.
Fig. 18 --- Typical Humidi--MiZert Adaptive Dehumidification System
Humidistat Wiring (208/230--V Unit Shown)
LCT
R
C
Y1
Y2
G
W1
W2
DEHUM
OC
TSTAT WIRES
LEGEND
CB— Circuit Breaker
LCT — Light Commercial Thermidistat™ Device
LLSV — Liquid Line Solenoid Valve
LTLO — Low Temperature Lockout
Fig. 19 --- Typical Rooftop Unit with Humidi--Mizer
Adaptive Dehumidification System with Thermidistat Device
OUTDOOR
AIR OPENING
PANEL
3 SCREWS
(SIDE)
R1
R1
ROOF TOP UNIT
R
C
Y1
Y2
G
W1
W2
PINK
PINK
CB
3.2 AMPS
LTLO
HUMIDI-MIZER SYSTEM
RED
PINK
24 V
FROM
HUMIDI-MIZER SYSTEM
LLSV
C06129
Fig. 20 --- Damper Panel with Manual Outdoor--Air
Damper Installed
C06130
C06013
Fig. 21 --- Outdoor--Air Hood Details
18
Page 19
C06131
Fig. 22 --- Outdoor--Air Damper With
Hood Attached
C06132
Fig. 23 --- Outdoor--Air Damper Position Setting
premierlink
control
The PremierLink controller is compatible with Carrier Comfort
NetworkR (CCN) devices. This control is designed to allow
users the access and ability to change factory--defined settings,
thus expanding the function of the standard unit control board.
Carrier’s diagnostic standard tier display tools such as
Navigatort or Scrolling Marquee can be used with the
PremierLink controller.
The PremierLink controller (see Fig. 24 and 25) requires the use
of a Carrier electronic thermostat or a CCN connection for time
broadcast to initiate its internal timeclock. This is necessary for
broadcast of time of day functions (occupied/unoccupied). No
sensors are supplied with the field-- mounted PremierLink control.
The factory--installed PremierLink control includes only the
supply-- air temperature (SAT) sensor and the outdoor air
temperature (OAT) sensor as standard. An indoor air quality
(CO2) sensor can be added as an option. Refer to Table 5 for
sensor usage. Refer to Fig. 26 for PremierLink controller wiring.
The PremierLink control may be mounted in the control panel or
an area below the control panel.
NOTE: PremierLink controller versions 1.3 and later are shipped
in Sensor mode. If used with a thermostat, the PremierLink
controller must be configured to Thermostat mode.
Install the Supply Air Temperature (SAT) Sensor
When the unit is supplied with a factory--mounted PremierLink
control,thesupply--airtemperature(SAT)sensor
(33ZCSENSAT) is factory-- supplied and wired. The wiring is
routed from the PremierLink control over the control box,
through a grommet, into the fan section, down along the back
side of the fan, and along the fan deck over to the supply--air
opening.
The SAT probe is wire--tied to the supply--air opening (on the
horizontal opening end) in its shipping position. Remove the
sensor for installation. Re-- position the sensor in the flange of the
supply-- air opening or in the supply air duct (as required by local
codes). Drill or punch a 1/2--in. hole in the flange or duct. Use
two field--supplied, self--drilling screws to secure the sensor probe
in a horizontal orientation.
NOTE: The sensor must be mounted in the discharge airstream
downstream of the cooling coil and any heating devices. Be sure
the probe tip does not come in contact with any of the unit or heat
surfaces.
Outdoor Air Temperature Sensor (OAT)
When the unit is supplied with a factory-mounted PremierLink
control and economizer, the outdoor-air temperature sensor
(OAT) is factory-supplied and wired.
Install the Indoor Air Quality (CO
Mount the optional indoor air quality (CO
)Sensor
2
) sensor according to
2
manufacturer specifications.
A separate field-supplied transformer must be used to power the
sensor.
CO
2
Wire the CO
sensor to the COM and IAQI terminals of J5 on the
2
PremierLink controller. Refer to the PremierLink Installation,
Start-up, and Configuration Instructions for detailed wiring and
configuration information.
Enthalpy Sensors and Control
The enthalpy control (HH57AC077) is supplied as a
field-installed accessory to be used with the EconoMi$er2
damper control option. The outdoor air enthalpy sensor is part of
the enthalpy control. The separate field-installed accessory return
air enthalpy sensor (HH57AC078) is required for differential
enthalpy control.
NOTE: The enthalpy control must be set to the “D” setting for
differential enthalpy control to work properly.
Theenthalpycontrol receives theindoor and return
enthalpy from the outdoor and return air enthalpy sensors and
provides a dry contact switch input to the PremierLink controller.
Locate the controller in place of an existing economizer controller
or near the actuator. The mounting plate may not be needed if
existing bracket is used.
A closed contact indicates that outside air is preferred to the
return air. An open contact indicates that the economizer should
remain at minimum position.
Outdoor Air Enthalphy Sensor/Enthalpy Controller
(HH57AC077)
T o wire the out door air enthalpy sensor, perform the following (See
Fig. 27 and 28):
NOTE: The outdoor air sensor can be removed from the back of
the enthalpy controller and mounted remotely.
48HE,HJ
19
Page 20
Table 5—PremierLink Sensor Usage
APPLICATION
OUTDOOR AIR
TEMPERATURE SENSOR
RETURN AIR
TEMPERATURE SENSOR
OUTDOOR AIR
ENTHALPY SENSOR
Differential Dry Bulb
Tem p e r a tu r e w i th
PremierLink*
(PremierLink
requires 4-20 mA
I n c l u d e d ---
CRTEMPSN001A00
R e q u i r e d --33ZCT55SPT
or Equivalent
Actuator)
Single Enthalpy with
PremierLink*
(PremierLink
requires 4-20 mA
Actuator)
I n c l u d e d ---
Not Used
—
R e q u i r e d --HH57AC077
or Equivalent
Differential Enthalpy
with PremierLink*
(PremierLink
requires 4-20 mA
I n c l u d e d ---
Not Used
—
Actuator)
*PremierLink control requires Supply Air Temperature sensor 33ZCSENS AT and Outdoor Air Temperature sensor CRTEMPSN001A00
48HE,HJ
— Included with factory-installed PremierLink control; field-supplied and field-installed with field-installed PremierLink control.
NOTES:
1. CO
Sensors (Optional):
2
33ZCSENCO2 — Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.
33ZCASPCO2 — Aspirator box used for duct-mounted CO
33ZCT55CO2 — Space temperature and CO
33ZCT56CO2 — Space temperature and CO
2. All units include the following Standard Sensors:
Outdoor-Air Sensor — 50HJ540569 — Opens at 67_F, c l o s e s at 5 2 _F, not adjustable.
Mixed-Air Sensor — HH97AZ001 — (PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT
and Outdoor Air Temperature Sensor CRTEMPSN001A00)
Compressor Lockout Sensor — 50HJ540570 — Opens at 35_F, cl o s e s at 50 _F.
room sensor with override.
2
room sensor with override and set point.
2
room sensor.
2
R e q u i r e d --HH57AC077
or Equivalent
RETURN AIR
ENTHALPY SENSOR
——
—
R e q u i r e d ---
HH57AC078
or Equivalent
Fig. 24 --- PremierLink Controller
20
C06016
Page 21
PREMIERLINK
CONTROL
HINGED
DOOR
PANEL
48HE,HJ
C06017
Fig. 25 --- PremierLinktController (Installed)
OAT
PNK
VIO
YEL
BLU
BLK
RED
BLU
YEL
WHT
7
6
11
11
10
10
8
2
2
3
3
4
4
1
1
5
5
9
12
12
TR
SR
2
OUTDOOR AIR
ENTHALPY SENSOR
Economi$er2
4 - 20mA
RED
BRN
PNK
7
VIO
6
8
Power Exhaust/Energy Recycler
GRA
ORN
9
PNK
TR1
+
3
GRAY
RED
BLK
RED
SAT
Space Temp./ Set
Point Adjustment
Indoor Air
Quality Sensor
Outdoor Air
Quality Sensor
CMPSAFE
GRAY
BLK
S
RETURN AIR
ENTHALPY
SENSOR
YEL
BLK
VIO
BRN
BRN
ORN
RED
BLU
LEGEND
GRA
PNK
BRN
BRN
GRN
YEL
BLU
WHT
PNK
BLU
BLK
GRA
GRA
PNK
BLK
ANAL OG
0-20mAIN
DISCRETE
PWR
BRN
J6
J5
J4
J1
COMMS
RMTOCC
FSD
SFS
CCN
Com
+
m.
TB-2
1
2
3
4
5
6
7
8
TB-3
1
2
3
4
5
6
7
8
BLU
BRN
BLK
BRN
RED
BRN
BLU
ORN
GRN
BLU
WHT
PNK
RED
WHT
COMMS — Communications
OAT— Outdoor Air Temperature Sensor
PWR— Power
RTU— Rooftop Unit
SAT— Supply Air Temperature Sensor
TB— Terminal Block
Fig. 26 --- T ypical PremierLink Control Wiring
HK50AA0
39
PremierLink
J7
J2
RED
BRN
J9
0-20 mA
TB-1
1
2
3
W1
4
5
W2
6
7
8
RTU Terminal
Board
Y1
Y2
PP/MP
WHT
R
RED
GRA
ORN
ORN
PNK
G
WHT
C
X
GRA
Relays
J8
PNK
ORNORN
ORN
RED
C06018
21
Page 22
1. Use a 4-conductor, 18 or 20 AWG cable to connect the
A
enthalpy control to the PremierLink controller and
power transformer.
2. Connect the following 4 wires from the wire harness
located in rooftop unit to the enthalpy controller:
a. Connect the BRN wire to the 24 vac terminal (TR1) on
enthalpy control and to pin 1 on 12-pin harness.
b. Connect the RED wire to the 24 vac GND terminal (TR)
on enthalpy sensor and to pin 4 on 12-pin harness.
c. Connect the GRAY/ORN wire to J4-2 on PremierLink
controller and to terminal (3) on enthalpy sensor.
d. Connect the GRAY/RED wire to J4-1 on PremierLink
controller and to terminal (2) on enthalpy sensor.
NOTE: If installing in a Carrier rooftop, use the two gray wires
provided from the control section to the economizer to connect
PremierLinkcontrollertoterminals2and3onenthalpysensor.
Return Air Enthalphy Sensor
Mount the return-air enthalpy sensor (HH57AC078) in the
return-air duct. The return air sensor is wired to the enthalpy
48HE,HJ
controller (HH57AC077). The outdoor enthalpy changeover set
point is set at the controller.
BRACKET
HH57AC078 ENTHALPY
SENSOR (USED WITH
ENTHALPY CONTROL
FOR DIFFERENTIAL
ENTHALPY OPERATION)
MOUNTING PLATE
HH57AC077
ENTHALPY
CONTROL AND
OUTDOOR AIR
ENTHALPY SENSOR
C7400A1004
+
ENTHALPY CONTROLLER
B
TRTR1
C
A
D
SO
SR
2
LED
NOTES:
1. Remove factory-installed jumper across SR and + before connecting
wires from return air sensor.
2. Switches shown in high outdoor air enthalpy state. Terminals 2 and 3
close on low outdoor air enthalpy relative to indoor air enthalpy.
3. Remove sensor mounted on back of control and locate in outside airstream.
RED
BRN
BLK
+
+
3
1
RED
GRAY/ORN
GRAY/RED
WIRE HARNESS
IN UNIT
(OUTDOOR
S
AIR
+
ENTHALPY
SENSOR)
S
(RETURN AIR
ENTHALPY
+
SENSOR)
C06019
Fig. 27 --- Outdoor and Return Air Sensor Wiring
Connections for Differential Enthalpy Control
To wire the return air enthalpy sensor, perform the following (See
Fig. 27):
1. Use a 2--conductor, 18 or 20 AWG, twisted pair cable to
connect the return air enthalpy sensor to the enthalpy
controller.
2. At the enthalpy control remove the factory-installed
resistor from the (SR) and (+) terminals.
3. Connect the field-supplied RED wire to (+) spade
connector on the return air enthalpy sensor and the (SR+)
terminal on the enthalpy controller. Connect the BLK wire
to (S) spade connector on the return air enthalpysensor
and the (SR) terminal on the enthalpy controller.
Fig. 28 --- Differential Enthalpy Control,
Sensor and Mounting Plate (33AMKITENT006)
ECONOMI$ER IV
CONTROLLER
WIRING
HARNESS
CTUATOR
OUTSIDE AIR
TEMPERATURE SENSOR
LOW AMBIENT
SENSOR
Fig. 29 --- EconoMi$er IV Component Locations
ECONOMI$ER2
PLUG
OUTDOOR
AIR HOOD
HOOD
SHIPPING
BRACKET
C06020
C06021
BAROMETRIC
RELIEF
DAMPER
GEAR DRIVEN
DAMPER
C06022
Fig. 30 --- EconoMi$er2 Component Locations
optional economi$er IV and
economi$er2
See Fig. 29 for EconoMi$er IV component locati ons. See Fig. 30 for
EconoMi$e r2 component locat ions.
22
Page 23
NOTE:These instructions are for installing the optional
EconoMi$er IV and EconoMi$er2 only. Refer to the accessory
EconoMi$er IV or EconoMi$er2 installation instructions when
field installing an EconoMi$er IV or EconoMi$er2 accessory.
1. To remove the existing unit filter access panel, raise the
panel and swing the bottom outward. The panel is now
disengaged from the track and can be removed. (See
Fig. 31.)
2. The box with the economizer hood components is shipped
in the compartment behind the economizer. The
EconoMi$er IV controller is mounted on top of the
EconoMi$er IV in the position shown in Fig. 26. The
optional EconoMi$er2 with 4 to 20 mA actuator signal
control does not include the EconoMi$er IV controller. To
remove the component box from its shipping position,
remove the screw holding the hood box bracket to the top
of the economizer. Slide the hood box out of the unit. (See
Fig. 32.)
IMPORTANT: If the power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be used and
must be discarded. Save the aluminum filter for use in the power
exhaust hood assembly.
3. The indoor coil access panel will be used as the top of the
hood. Remove the screws along the sides and bottom of
the indoor coil access panel. (See Fig. 33.)
4. Swing out indoor coil access panel and insert the hood
sides under the panel (hood top). Use the screws provided
to attach the hood sides to the hood top. Use screws
provided to attach the hood sides to the unit. (See Fig. 34.)
5. Remove the shipping tape holding the economizer
barometric relief damper in place.
6. Insert the hood divider between the hood sides. (See
Fig. 34 and 35.) Secure hood divider with 2 screws on
each hood side. The hood divider is also used as the
bottom filter rack for the aluminum filter .
7. Open the filter clips which are located underneath the
hood top. Insert the aluminum filter into the bottom filter
rack (hood divider). Push the filter into position past the
open filter clips. Close the filter clips to lock the filter into
place. (See Fig. 35.)
8. Caulk the ends of the joint between the unit top panel and
the hood top. (See Fig. 33.)
9. Replace the filter access panel.
10. Install all EconoMi$er IV accessories. EconoMi$er IV
wiring is shown in Fig. 36. EconoMi$er2 wiring is shown
in Fig. 37.
Barometric flow capacity is shown in Fig. 38. Outdoor air
leakage is shown in Fig. 39. Return air pressure drop is shown in
Fig. 40.
FILTER ACCESS PANEL
x
o
B
d
o
o
H
Fig. 32 --- Hood Box Removal
CAULK
INDOOR
COIL
ACCESS
PANEL
HERE
Fig. 33 --- Indoor Coil Access Panel Relocation
LEFT
HOOD
SIDE
B
19 1/16”
SCREW
33 3/8”
HOOD BOX
BRACKET
SIDE
PANEL
TOP
SIDE
PANEL
INDOOR
COIL
ACCESS
PANEL
TOP
PANEL
INDOOR COIL
ACCESS PANEL
C06024
48HE,HJ
C06025
COMPRESSOR
ACCESS PANEL
OUTDOOR-AIR OPENING AND
INDOOR COIL ACCESS PANEL
Fig. 31 --- T ypical Access Panel Locations
C06023
HOOD DIVIDER
Fig. 34 --- Outdoor--Air Hood Construction
ECONOMI$ER IV STANDARD
SENSORS
Outdoor Air Temperature (OAT) Sensor
The outdoor air temperat ure sensor (HH57AC074) is a 10 t o 20 mA
device used to meas ure the outdoor-air temper ature. The outdoor-ai r
tempe rature i s us ed to deter m i ne when the EconoMi$er IV can be
used for free cooling. The sensor is factory-inst alled on the
EconoMi$e r IV in the outdoor airst ream. (See Fig. 29.) The
operating range of t empera ture measurement is 40_ to 100_F.
23
C06026
Page 24
Supply Air Temperature (SAT) Sensor
R
The supply air temperature sensor is a 3 K thermistor located at
the inlet of the indoor fan. (See Fig. 41.) This sensor is factory
installed. The operating range of temperature measurement is 0
to 158_F. See Table 6 for sensor temperature/resistance values.
The temperature sensor looks like an eyelet terminal with wires
running to it. The sensor is located in the “crimp end” and is
sealed from moisture.
Outdoor Air Lockout Sensor
The Economi$er IV is equipped with an ambient temperature
lockout switch located in the outdoor air stream which is used to
lockout the compressors below a 42_F ambient temperature. (See
Fig. 29.)
FILTE
CLIP
C06027
ECONOMI$ER IV CONTROL
MODES
IMPORTANT: The optional EconoMi$er2 does not include a
controller. The EconoMi$er2 is operat ed by a 4 to 20 mA
signal
from an existing field-supplied controller (such as PremierLink
control ). See Fig. 37 for wiring informa t ion.
Determine the EconoMi$er IV control mode before set up of the
control. Some modes of operation may require different
sensors. Refer to Table 7. The EconoMi$er IV is supplied from
the factory with a supply--air temperature sensor and an outdoor-air temperature sensor. This allows for operation of the
EconoMi$er IV with outdoor air dry bulb changeover control.
Additional accessories can be added to allow for different types of
changeover control and operation of the EconoMi$er IV and unit.
Table7—Economi$erivsensorusage
APPLICATION
Outdoor Air
Dry Bulb
Differential
Dry Bulb
Single EnthalpyHH57AC078
Differential
Enthalpy
CO2for DCV
Control using a
Wall-Mounted
Sensor
CO
2
CO2for DCV
Control using a
Duct-Mounted
Sensor
CO
2
*CRENTDIF004A00 a nd CRTEMPSN002A00 accessories are used on many
different base units. As such, these kits may contain parts that will not be
needed for installation.
† 33ZCSENCO2 is an accessory CO
** 33ZCASPCO2 is an accessory aspirator box required for duct-mounted
applications.
†† CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2
and 33ZCASPCO2 accessories.
ECONOMI$ER IV WITH OUTDOOR AIR
33ZCSENCO2†
33ZCASPCO2**
DRY BULB SENSOR
Accessories Required
None. The outdoor air dry bulb sensor
is factory installed.
CRTEMPSN002A00*
HH57AC078
and
CRENTDIF004A00*
33ZCSENCO2
O
and
sensor.
2
CRCBDIOX005A00††
R
Outdoor Dry Bulb Changeover
The standard controller is shipped from the factory configured for
outdoor dry bulb changeover control. The outdoor--air and
supply-- air temperature sensors are included as standard. For this
control mode, the outdoor temperature is compared to an
adjustable set point selected on the control. If the outdoor-air
temperature is above the set point, the EconoMi$er IV will adjust
the outdoor-air dampers to minimum position. If the outdoor air
temperature is below the set point, the position of the outdoor air
dampers will be controlled to provide free cooling using outdoor
air. When in this mode, the LED next to the free cooling set point
potentiometer will be on. The changeover temperature set point is
controlled by the free cooling set point potentiometer located on
the control. (See Fig. 42.) The scale on the potentiometer is A, B,
C, and D. See Fig. 43 for the corresponding temperature
changeover values.
Differential Dry Bulb Control
For differential dry bulb control the standard outdoor dry bulb
sensor is used in conjunction with an additional accessory dry
bulb sensor (part number CRTEMPSN002A00). The accessory
sensor must be mounted in the return airstream. (See Fig. 44.)
Wiring is provided in the EconoMi$er IV wiring harness. (See
Fig. 36.)
In this mode of operation, the outdoor-air temperature is
compared to the return-air temperature and the lower temperature
airstream is used for cooling. When using this mode of
changeover control, turn the enthalpy setpoint potentiometer fully
clockwise to the D setting. (See Fig. 42.)
24
Page 25
DCV— Demand Controlled Ventilation
p
IAQ — Indoor Air Quality
LA — Low Ambient Lockout Device
OAT — Outdoor-Air Temperature
POT— Potentiometer
RAT— Return-Air Temperature
LEGEND
FOR OCCUPANCY CONTROL
REPLACE JUMPER WITH
FIELD-SUPPLIED TIME CLOCK
1. 620 ohm, 1 watt 5% resistor should be removed only when using differential
enthalpy or dry bulb.
2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power
supply, it cannot have the secondary of the transformer grounded.
3. For field-installed remote minimum position POT, remove black wire jumper
between P and P1 and set control minimum position POT to the minimum
osition.
48HE,HJ
C06028
BLACK
4
3
5
BLUE
500 OHM
RESISTOR
VIOLET
NOTE 1
PINK
RUN
NOTE 3
50HJ540573
ACTUATOR
ASSEMBLY
DIRECT DRIVE
ACTUATOR
NOTES:
1. Switch on actuator must be in run position for economizer to operate.
2. PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sensor or HH57A077
enthalpy sensor.
3. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.
OPTIONAL CO
SENSOR4-20mA
+
2
OUTPUT
RED
YELLOW
WHITE
2
8
6
7
1
10
11
9
12
ECONOMISER2 PLUG
Fig. 37 --- EconoMi$er2 with 4 to 20 mA Control Wiring
C06029
Outdoor Enthalpy Changeover
For enthalpy control, accessory enthalpy sensor (part number
HH57AC078) is required. Replace the standard outdoor dry bulb
temperature sensor with the accessory enthalpy sensor in the same
mounting location. (See Fig. 29.) When the outdoor air enthalpy
rises above the outdoor enthalpy changeover set point, the
outdoor-air damper moves to its minimum position. The outdoor
enthalpy changeover set point is set with the outdoor enthalpy set
point potentiometer on the EconoMi$er IV controller. The set
points are A, B, C, and D. (See Fig. 45.) The factory-installed
620-ohm jumper must be in place across terminals SR and SR+
on the EconoMi$er IV controller. (See Fig. 29 and 46.)
25
Page 26
Differential Enthalphy Control
For differential enthalpy control, the EconoMi$er IV controller
usestwoenthalpysensors(HH57AC078and
CRENTDIF004A00), one in the outside air and one in the return
air duct. The EconoMi$er IVcontroller compares the outdoor
air enthalpy to the return air enthalpy to determine EconoMi$er
IV use. The controller selects the lower enthalpy air (return or
outdoor) for cooling. For example, when the outdoor air has a
lower enthalpy than the return air, the EconoMi$er IV opens to
bring in outdoor air for free cooling.
2500
2000
SUPPLY AIR
TEMPERATURE
SENSOR
MOUNTING
LOCATION
SUPPLY AIR
TEMPERATURE
SENSOR
1500
1000
500
FLOW IN CUBIC FEET PER MINUTE (cfm)
0
0.05
STATIC PRESSURE (in. wg)
0.15
0.25
C06030
48HE,HJ
Fig. 41 --- Supply Air Sensor Location
C06033
Fig. 38 --- Barometric Flow Capacity
30
25
20
15
10
5
0
0.13 0.20 0. 22 0.25 0.30 0.35 0.40 0.45 0.50
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
Fig. 39 --- Outdoor--Air Damper Leakage
C06031
Fig. 42 --- EconoMi$er IV Controller Potentiometer
and LED Locations
Replace the standard outside air dry bulb temperature sensor with
the accessory enthalpy sensor in the same mounting location.
(See Fig. 29.) Mount the return air enthalpy sensor in the return
air duct. (See Fig. 44.) Wiring is provided in the EconoMi$er IV
C06034
wiring harness. (See Fig. 36.) The outdoor enthalpy changeover
6000
5000
4000
3000
2000
1000
0
0.050.100.150.200.250.300.35
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
Fig. 40 --- Return-- Air Pressure Drop
C06032
set point is set with the outdoor enthalpy set point potentiometer
on the EconoMi$er IV controller. When using this mode of
changeover control, turn the enthalpy setpoint potentiometer fully
clockwise to the D setting.
Indoor Air Quality (IAQ) Sensor Input
The IAQ input can be used for demand control ventilation control
based on the level of CO
measured in the space or return air
2
duct.
Mount the accessory IAQ sensor according to manufacturer
specifications. The IAQ sensor should be wired to the AQ and
AQ1 terminals of the controller. Adjust the DCV potentiometers
to correspond to the DCV voltage output of the indoor air quality
sensor at the user-determined set point. (See Fig. 47.)
If a separate field-supplied transformer is used to power the IAQ
sensor, the sensor must not be grounded or the EconoMi$er IV
control board will be damaged.
Exhaust Set Point Adjustment
The exhaust set point will determine when the exhaust fan runs
based on damper position (if accessory power exhaust is
installed). The set point is modified with the Exhaust Fan Set
Point (EXH SET) potentiometer. (See Fig. 42.) The set point
represents the damper position above which the exhaust fans will
be turned on. When there is a call for exhaust, the EconoMi$er IV
controller provides a 45 15 second delay before exhaust fan
26
Page 27
activation to allow the dampers to open. This delay allows the
damper to reach the appropriate position to avoid unnecessary fan
overload.
Minimum Position Control
There is a minimum damper position potentiometer on the
EconoMi$er IV controller. (See Fig. 42.) The minimum damper
position maintains the minimum airflow into the building during
the occupied period.
When using demand ventilation, the minimum damper position
represents the minimum ventilation position for VOC (volatile
organic compound) ventilation requirements. The maximum
demand ventilation position is used for fully occupied ventilation.
When demand ventilation control is not being used, the minimum
position potentiometer should be used to set the occupied
ventilation position. The maximum demand ventilation position
should be turned fully clockwise.
Adjust the minimum position potentiometer to allow the
minimum amount of outdoor air, as required by local codes, to
enter the building. Make minimum position adjustments with at
least 10_F temperature difference between the outdoor and
return-air temperatures.
To determine the minimum position setting, perform the
following procedure:
1. Calculate the appropriate mixed air temperature using the
following formula:
OA
(T
Ox
100100
+(TR
)
RA
x
)=T
M
Thermostats
The EconoMi$er IV control works with conventional thermostats
that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage
1), W2 (heat stage 2), and G (fan). The EconoMi$er IV control
does not support space temperature sensors. Connections are
made at the thermostat terminal connection board located in the
main control box.
19
LED ON
18
17
mA
14
13
12
11
10
16
15
9
40
45
LED OFF
50
D
LED ON
C
LED OFF
60
55
65
DEGREES FAHRENHEIT
70
LED ON
LED OFF
75
B
LED ON
A
LED OFF
100
90
95
85
80
C06035
Fig. 43 --- Outside Air Temperature
Changeover Set Points
ECONOMI$ER IV
CONTROLLER
ECONOMI$ER IV
48HE,HJ
TO= Outdoor-Air Temperature
OA = Percent of Outdoor Air
= Return-Air Tempera ture
T
R
RA = Percent of Return Air
= Mixed-Air Temperature
T
M
As an example, if local codes require 10% outdoor air during
occupied conditions, outdoor-air temperature is 60_F, an d
return-air temperature is 75_F.
(60 x .10) + (75 x .90) = 73.5_F
2. Disconnect the supply air sensor from terminals T and T1.
3. Ensure that the factory-installed jumper is in place across
terminals P and P1. If remote damper positioning is being
used, make sure that the terminals are wired according to
Fig. 36 and that the minimum position potentiometer is
turned fully clockwise.
4. Connect 24 vac across terminals TR and TR1.
5. Carefully adjust the minimum position potentiometer
until the measured supply air temperature matches the
calculated value.
6. Reconnect the mixed air sensor to terminals T and T1.
Remote control of the EconoMi$er IV damper is desirable when
requiringadditionaltemporaryventilation.Ifa
field-supplied remote potentiometer (Honeywell part number
S963B1128) is wired to the EconoMi$er IV controller, the
minimum position of the damper can be controlled from a remote
location.
To control the minimum damper position remotely, remove the
factory-installed jumper on the P and P1 terminals on the
EconoMi$er IV controller. Wire the field-supplied potentiometer
to the P and P1 terminals on the EconoMi$er IV controller. (See
Fig. 46.)
Damper Mo vement
Damper movement from full open to full closed (or vice versa)
1
/2minutes.
takes 2
GROMMET
RETURN AIR
SENSOR
RETURN DUCT
(FIELD-PROVIDED)
C06036
Fig. 44 --- Return Air Temperature or Enthalpy
Sensor Mounting Location
Occupancy Control
The factory default configuration for the EconoMi$er IV control
is occupied mode. Occupied mode is provided by the black
jumper from terminal TR to terminal N. When unoccupied mode
is desired, install a field-supplied timeclock function in place of
the jumper between TR and N. (See Fig. 36.) When the timeclock
contacts are closed, the EconoMi$er IV control will be in
occupied mode. When the timeclock contacts are open (removing
the 24-v signal from terminal N), the EconoMi$er IV will be in
unoccupied mode.
27
Page 28
85
(29)90(32)95(35)
46
(18)
4
4
42
40
70
(21)
0
0
1
65
80
(27)
75
(24)
0
9
80
70
0
6
50
0
4
CONTROL
48HE,HJ
2
1
CURVE
A
B
C
D
4
1
1
6
8
1
CONTROL POINT
deg. F (deg. C)
APPROX.
AT 50% RH
73 (23)
70 (21)
67 (19)
63 (17)
ENTHALPY BTU PER POUND DRY AIR
4
2
2
2
0
2
(4)
35
(2)
8
3
6
3
4
3
32
30
28
26
60
(16)
A
55
(13)
B
50
C
(10)
45
D
(7)
40
100
105
(38)
RELATIVE HUMIDITY (%)
30
20
110
(41)
(43)
0
1
A
B
C
D
35
40
45
50
55
60
65
70
75
80
(2)
(4)
(10)
(7)
APPROXIMATE DRY BULB TEMPERATURE--degrees F (degrees C)
(13)
(16)
(18)
(21)
(24)
(27)
85
(29)90(32)95(35)
Fig. 45 --- Enthalpy Changeover Set Points
Typically the maximum ventilation rate will be about 5 to 10%
more than the typical cfm required per person, using normal
outside air design criteria.
Demand Controlled Ventilation (DCV)
When using the EconoMi$er IV for demand controlled
ventilation, there are some equipment selection criteria which
should be considered. When selecting the heat capacity and cool
capacity of the equipment, the maximum ventilation rate must be
evaluated for design conditions. The maximum damper position
must be calculated to provide the desired fresh air.
A proportional anticipatory strategy should be taken with the
following conditions: a zone with a large area, varied occupancy,
and equipment that cannot exceed the required ventilation rate at
design conditions. Exceeding the required ventilation rate means
the equipment can condition air at a maximum ventilation rate
that is greater than the required ventilation rate for maximum
occupancy. A proportional-anticipatory strategy will cause the
fresh air supplied to increase as the room CO
even though the CO
the CO
level reaches the set point, the damper will be at
2
set point has not been reached. By the time
2
level increases
2
maximum ventilation and should maintain the set point.
In order to have the CO
sensor control the economizer damper in
2
this manner, first determine the damper voltage output for
minimum or base ventilation. Base ventilation is the ventilation
required to remove contaminants during unoccupied periods. The
following equation may be used to determine the percent of
outside-air entering the building for a given damper position. For
best results there should be at least a 10 degree difference in
outside and return-air temperatures.
HIGH LIMIT
+(TR
)
CURVE
RA
x
)=T
M
100
(38)
105
110
(41)
(43)
OA
(T
Ox
100100
TO= Outdoor-Air Temperature
OA = Percent of Outdoor Air
= Return-Air Tempera ture
T
R
RA = Percent of Return Air
= Mixed-Air Temperature
T
M
Once base ventilation has been determined, set the minimum
damper position potentiometer to the correct position.
The same equation can be used to determine the occupied or
maximum ventilation rate to the building. For example, an output
of 3.6 volts to the actuator provides a base ventilation rate of 5%
and an output of 6.7 volts provides the maximum ventilation rate
of 20% (or base plus 15 cfm per person). Use Fig. 44 to
determine the maximum setting of the CO
sensor. For example,
2
a 1100 ppm set point relates to a 15 cfm per person design. Use
the 1100 ppm curve on Fig. 47 to find the point when the CO
sensor output will be 6.7 volts. Line up the point on the graph
with the left side of the chart to determine that the range
configuration for the CO
sensor should be 1800 ppm. The
2
EconoMi$er IV controller will output the 6.7 volts from the CO
sensor to the actuator when the CO2concentration in the space is
at 1100 ppm. The DCV set point may be left at 2 volts since the
sensor voltage will be ignored by the EconoMi$er IV
CO
2
controller until it rises above the 3.6 volt setting of the minimum
position potentiometer.
Once the fully occupied damper position has been determined, set
the maximum damper demand control ventilation potentiometer
to this position. Do not set to the maximum position as this can
result in over-ventilation to the space and potential high-humidity
levels.
28
C06037
2
2
Page 29
N1
P1
T1
AQ1
SO+
SR+
EXH
2V10V
EXH
2V10V
DCV
2V10V
Free
Cool
B
A
Open
Min
Pos
DCV
DCV
C
D
Set
Max
Set
N
P
T
AQ
SO
SR
TR1
TR
24
24 Vac
Vac
COM
HOT
+
12
3
EF1
EF
_
5
4
C06038
Fig. 46 --- EconoMi$er IV Control
CO SENSOR MAX RANGE SETTING
6000
5000
4000
3000
2000
1000
RANGE CONFIGURATION (ppm)
0
2
800 ppm
900 ppm
1000 ppm
1100 ppm
2345678
DAMPER VOLTAGE FOR MAX VENTILATION RATE
C06039
Fig. 47 --- CO2Sensor Maximum Range Setting
Sensor Configuration
CO
2
The CO
sensor has preset standard voltage settings that can be
2
selected anytime after the sensor is powered up. (See Table 8.)
Use setting 1 or 2 for Carrier equipment. (See Table 8.)
1. Press Clear and Mode buttons. Hold at least 5 seconds
until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number. (See
Tab l e 8.)
4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.
The custom settings of the CO
sensor can be changed anytime
2
after the sensor is energized. Follow the steps below to change the
non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 seconds
until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD menu
and press Enter.
4. Use the Up/Down button to toggle through each of the
nine variables, starting with Altitude, until the desired
setting is reached.
5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode to
continue to the next variable.
Dehumidification of Fresh Air with DCV Control
Information from ASHRAE indicates that the largest humidity
load on any zone is the fresh air introduced. For some
applications, a device such as a 62AQ energy recovery unit is
added to reduce the moisture content of the fresh air being
brought into the building when the enthalpy is high. In most
cases, the normal heating and cooling processes are more than
adequate to remove the humidity loads for most commercial
applications.
If normal rooftop heating and cooling operation is not adequate
for the outdoor humidity level, an energy recovery unit and/or a
dehumidification option should be considered.
Step 9 —Adjust Evaporator--Fan Speed
Adjust evaporator-fan speed to meet jobsite conditions.
Tables 9 and 10 show fan rpm at motor pulley settings. Tables 11
and 15 show maximum amp draw of belt-drive motor. Table 14
shows sound data. Refer to Tables 16-35 for performance data.
See Table 36 for accessory static pressure drop. See Fig. 48 for
the Humidi-MiZer system static pressure drops.
Belt drive
motors
Fan motor pulleys are factory set for speed shown in Table 1 or 2.
Check pulley alignment and belt tension prior to start-up.
To change fan speed:
1. Shut off the unit power supply and tag disconnect.
2. Loosen the belt by loosening the fan motor mounting nuts.
(See Fig. 49.)
3. Loosen movable pulley flange setscrew. (See Fig. 50.)
4. Screw movable flange toward fixed flange to increase
speed and away from fixed flange to decrease speed.
Increasing fan speed increases load on motor. Do not
exceed maximum speed specified in Table 1 or 2.
5. Set movable flange at nearest keyway of pulley hub and
tighten setscrew. (See Table 1 or 2 for speed change for
each full turn of pulley flange.)
6. Adjust belt tension and align gan and motor pulleys per
guidance below.
To align fan and motor pulleys, loosen fan pulley setscrews and
slide fan pulley along fan shaft. Make angular alignment by
loosening motor from mounting.
Additional motor and fan alignment, as well as angular alignment
can be made by loosening the four motor mounting bolts from
the mounting plate.
To adjust belt tension:
1. Loosen the two motor mounting nuts as shown in Fig. 49.
Some models may have a third mounting nut located on
the opposite side of the fan motor mounting plate.
2. Slide motor mounting plate away from fan scroll for
proper belt tension (
1
/2-in.deflectionwith8to10lbof
force) and tighten mounting nuts.
3. Adjust lock bolt and nut on mounting plate to secure
motor in fixed position.
48HE,HJ
29
Page 30
Table 8—CO
Sensor Standard Settings
2
SETTINGEQUIPMENTOUTPUT
1
Interface w/Standard
2
Building Control System
3
4
5
Economizer
6
7
Health & SafetyProportional—
8
Parkin g/ Air Inta kes/
9
Loading Docks
48HE,HJ
LEGEND
ppm — Parts Per Million
0.35
0.3
0.25
VENTILATION
RATE
(cfm/Person)
ProportionalAn y
ProportionalAn y
ExponentialAny
Proportional15
Proportional20
Exponential15
Exponential20
Proportional—
ANALOG
OUTPUT
0-10V
4-20 mA
2-10V
7-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
CO
CONTROL RANGE
2
(ppm)
0-2000100050
0-2000100050
0-2000110050
0-1100110050
0- 90090050
0-1100110050
0- 90090050
0-99995000500
0-200070050
OPTIONAL
RELAY SETPOINT
(ppm)
RELAY
HYSTERESIS
(ppm)
DELTA P IN. WG
0.2
0.15
0.1
0.05
4&5ton
6 ton
3 ton
0
0
1000
2000
3000
4000
5000
6000
C06133
Fig. 48 --- Humidi--MiZert Adaptive Dehumidification System Static Pressure Drop (in. wg)
Fig. 49 --- Belt Drive Motor Mounting
C06134
C06041
Fig. 50 --- Indoor--Fan Pulley Adjustment
30
Page 31
Table 9—48HJ and 48he Fan Rpm at Motor Pulley Setting With Standard Motor*
UNIT
48HJ
48HE
003
004
005
006
007
*Approximate fan rpm shown (standard motor/drive).
Table 11—Evaporator-Fan Motor Data — Standard Motor
UNIT
48HJ
48HE
003
004
005
006
007
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
Single0.58580208/2302.0
Single1.201000208/2304.9
Three1.201000
Single1.201000208/2304.9
Three1.201000
Single1.301650208/2309.2
Three2.402120
Three2.402120
111/
2
MOTOR PULLEY TURNS OPEN
221/
2
2
MOTOR PULLEY TURNS OPEN
221/
2
331/
MAXIMUM
OPERATING WATTS*
331/
2
441/
2
441/
UNIT VOLTAGE
551/
2
2
551/
2
2
MAXIMUM
AMP DRAW
208/2304.9
4602.2
5752.2
208/2304.9
4602.2
5752.2
208/2306.7
4603.0
5753.0
208/2306.7
4603.0
5753.0
6
6
48HE,HJ
LEGEND
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using the
fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
Table 13—Evaporator-Fan Motor Data — High-Static Motors
UNIT
48HJ
004
005
006
007
LEGEND
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using the
fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
Three2.402120
Three2.402120
Three2.902615
Three2.902615
UNIT VOLTAGE
208/2306.7
4603.0
5753.0
208/2306.7
4603.0
5753.0
208/2308.6
4603.9
5753.9
208/2308.6
4603.9
5753.9
AMP DRAW
MAXIMUM
31
Page 32
Table 14—48HJ Outdoor Sound Power (Total Unit)
UNIT
48HJ
004,005
006,007
LEGEND
ARI --- Air Conditioning and Refrigeration Institute
UNIT
48HE
003 -- 005767655.966.064.066.268.464.561.757.3
006808059.168.968.771.974.068.965.759.0
48HE,HJ
1. Values include losses for filters, unit casing, and wet coils. See Table 31 and Fig. 44 for accessory/FIOP static pressure information.
2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the
fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
See Tables 9 and 10 on this page for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify.
4. Interpolation is permissible. Do not extrapolate.
Table 16—Fan Performance 40HE003 — Vertical Discharge Units; Standard Motor (Belt Drive)**
1. Grey cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See general fan performance notes.
LEGEND
Bhp — Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-supplied drive.
Table 36—Accessory/FIOP EconoMi$er IV and EconoMi$er2 Static Pressure* (in. wg)
COMPONENT
Vertical EconoMi$er2 and EconoMi$er IV
Horizontal EconoMi$er2 and EconoMi$er IV
FIOP — Factory-Installed Option
*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should be used in conjunction with the Fan Perfor-
LEGEND
mance tables to determine indoor blower rpm and watts.
Failur e to follow this warning could result in personal
injury, death and/or propert y damage:
1. Follow recogniz ed s a fety practices and wear protec tive
goggles when checking or servi cing a refri gerant system.
2. Do not ope rate the compressor or provide any electric
power to the unit unless the compressor terminal cover is
in place and secured.
3. Do not remove the compressor t ermina l cover until all
electrical sources are disconnect ed and t agged with lockout
tags.
4. Relie ve all pressure from the s ystem before touching or
disturbing anything inside the termi nal box if a
refrigerant leak is suspec ted around the compressor
terminals. Use accepted methods to rec over the
refrigerant.
5. Never attempt to repair a soldered connection while the
refrigerant system is under press ur e.
6. Do not use a torch to remove any component . The
system contains oil and refriger ant under pressure. To
remove a component, wear protecti ve goggles and proceed
as follows:
a. Shut off electrical power to the unit and tag
b. Recover refrigerant to relieve all pressure
c. Cut component connection tubing with a
d. Carefully unsweat the remaining tubing
Proceed as follows to inspect and prepare the unit for initial
start-up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING,
CAUTION, and INFORMATION labels attached to, or
shipped with, unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages such as
broken lines, loose parts, or disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections and on
unit base. Detecting oil generally indicates a refrigerant
leak. Leak-test all refrigerant tubing connections using
electronic leak detector, halide torch, or liquid-soap
solution.
c. Inspect all field-wiring and factory-wiring connections.
Be sure that connections arecompleted and tight. Be sure
that wires are not in contact with refrigerant tubing or
sharp edges.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin comb.
4. Verify the following conditions:
a. Make sure that condenser-fan blade are correctly
positioned in fan orifice. See Condenser-Fan Adjustment
section for more details.
b. Make sure that air filter(s) is in place.
c. Make sure that condensate drain trap is filled with water
to ensure proper drainage.
WARNING
disconnect.
from the system using both high-pressure
and low-pressure ports.
tubing cutter, and remove the component
from the unit.
stubs when necessary. Oil can ignite when
exposed to a torch flame.
d. Make sure that all tools and miscellaneous loose parts
have been removed.
START-UP
Step 1 —Unit Preparation
Make sure that the unit has been installed in accordance with
installation instructions and applicable codes.
Step 2 —Gas Piping
Check gas piping for leaks.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
Disc onnect gas piping from unit when leak testing at
pressure greater than
psig will cause gas valve damage resulting in hazardous
condition. If gas va lve is subjecte d to pressure greater than
1
/2psig, it must be replaced before use. When pressure
testing field-supplied gas piping at pressures of
or less , a unit connecte d to such piping must be isolated by
manual l y closing the gas valve.
Step 3 —Return--Air Filters
Make sure the correct filters are installed in the unit (See Table 1
or 2). Do not operate the unit without return-air filters.
Step 4 —Outdoor--Air Inlet Screens
Outdoor-air inlet screen(s) must be in place before operating the
unit.
Step 5 —Compressor Mounting
Compressors are internally spring mounted. Do not loosen or
remove the compressor holddown bolts.
Step 6 —Internal Wiring
Check all electrical connections in unit control boxes; tighten
them as required.
Step 7 —Refrigerant Service Ports
Each unit system has 4 Schrader--type service ports: one on the
suction line, one on the liquid line, and 2 on the compressor
discharge line. Be sure that caps on the ports are tight. Two
additional Schrader valves are located under the high--pressure
and low--pressure switches, respectively.
Step 8 —High Flow Refrigerant Valves
Two high flow valves are located on the hot gas tube coming out
of the compressor and the suction tube going into the compressor.
Large black plastic caps identify these valves. These valves have
O--rings inside which screw the cap onto a brass body to prevent
leaks. No field access to these valves is available at this time.
Ensure the plastic caps remain on the valves and are tight or the
possibility of refrigerant leakage could occur.
Step 9 —Compressor Rotation
On 3-phase units be certain that the compressor is rotating in the
proper direction. To determine whether or not compressor is
rotating in the proper direction:
1. Connect the service gauges to suction and discharge
pressure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge
pressure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pressure
does not rise to normal levels:
1. Note that the indoor fan (006 and 007 three-phase units
only) is probably also rotating in the wrong direction.
WARNING
1
/2psig. Pressures greater than1/
1
/2psig
2
48HE,HJ
45
Page 46
2. Turn off power to the unit and tag disconnect.
A
3. Reverse any two of the unit power leads.
4. Turn on power to the unit and energize the compressor.
The suction and discharge pressure levels should now move to
their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direction,
the unit makes more noise and does not provide cooling.
Step 10 —Cooling
Set the space thermostat to the OFF position. Set the system
selector switch at COOL position and the fan switch at AUTO
position. Adjust the thermostat to a setting below room
temperature. The compressor starts when contactor closes.
Check the unit charge. Refer to Refrigerant Charge section.
Reset the thermostat at a position above room temperature. The
compressor will shut off. Evaporator fan will shut off after a
30--second delay.
To Shut Off Unit -- Set the system selector switch at OFF
position. Resetting the thermostat at a position above room
temperature shuts off the unit temporarily until the space
48HE,HJ
temperature exceeds the thermostat setting. Units are equipped
with a Cycle-LOC protection device. The unit shuts down on
any safety trip and remains off; an indicator light on the
thermostat comes on. Check the reason for the safety trip.
Step 11 —Main Burners
Main burners are factory set and should require no adjustment.
TO CHECK ignition of main burners and heating controls, move
thermostat set point above room temperature and verify that the
burners light and evaporator fan is energized. Check heating
effect, then lower the thermostat setting below the room
temperature and verify that the burners and evaporator fan turn
off.
Refer to Tables 37 and 38 for the correct orifice to use at high
altitudes.
Table 37—Altitude Compensation*
48HJ004--007, 48HE003--006 Standard Units
72,000 AND
115,000 BTUH
ELEVATION
(ft)
0-2,000
2,000
3,000
4,000
5,000
6,000
7,000
8,000
9,000
10,000
11,000
12,000
13,000
14,000
*As the height above sea level increases, there is less oxygen per cubic
foot of air. Therefore, heat input rate should be reduced at higher altitudes.
†Orifices available through your Carrier distributor.
1. Purge gas supply line of air by opening union ahead of the
gas valve. If gas odor is detected, tighten union and wait 5
minutes before proceeding.
2. Turn on electrical supply and manual gas valve.
3. Set system switch selector at HEAT position and fan
switch at AUTO or ON position. Set heating temperature
lever above room temperature.
4. The induced-draft motor will start.
5. After a call for heating, the main burners should light
within 5 seconds. If the burner does not light, then there is
a 22-second delay before another 5-second try. If the
burner still does not light, the time delay is repeated. If the
burner does not light within 15 minutes, there is a lockout.
To reset the control, break the 24 v power to W1.
6. The evaporator-fan motor will turn on 45 seconds after
burner ignition.
7. The evaporator-fan motor will turn off in 45 seconds after
the thermostat temperature is satisfied.
8. Adjust airflow to obtain a temperature rise within the
range specified on the unit nameplate.
NOTE: The default value for the evaporator-fan motor on/off
delay is 45 seconds. The Integrated Gas Unit Controller (IGC)
modifies this value when abnormal limit switch cycles occur.
Based upon unit operating conditions, the on delay can be
reduced to 0 seconds and the off delay can be extended to180
seconds. When one flash of the LED (light-emitting diode) is
observed, the evaporator-fan on/off delay has been modified.
If the limit switch trips at the start of the heating cycle during the
evaporator on delay, the time period of the on delay for the next
cycle will be 5 seconds less than the time at which the switch
tripped. (Example: If the limit switch trips at 30 seconds, the
evaporator-fan on delay for the next cycle will occur at 25
seconds.) To prevent short-cycling, a 5-second reduction will
only occur if a minimum of 10 minutes has elapsed since the last
call for heating.
The evaporator-fan off delay can also be modified. Once the call
for heating has ended, there is a 10-minute period during which
the modification can occur. If the limit switch trips during this
period, the evaporator-fan off delay will increase by 15 seconds.
46
Page 47
A maximum of 9 trips can occur, extending the evaporator-fan off
delay to 180 seconds.
To restore the original default value, reset the power to the unit.
To Shut Off Unit —Set system selector switch at offposition.
Resetting heating selector lever below room temperature will
temporarily shut unit off until space temperature falls below
thermostat setting.
Step 13 —Safety Relief
A soft solder joint at the suction line fitting provides pressure
relief under abnormal temperature and pressure conditions.
Step 14 —Ventilation (Continuous Fan)
Set fan and system selector switches at ON and OFF positions,
respectively. Evaporator fan operates continuously to provide
constant air circulation. When the evaporator--fan selector switch
is turned to the OFF position, there is a 30--second delay before
the fan turns off.
Step 15 —Operating Sequence
cooling -- units without
When thermostat calls for cooling, terminals G and Y1 are
energized. The indoor-fan contactor (IFC), reversing valve
solenoid (RVS) and compressor contactor are energized and
indoor-fan motor, compressor, and outdoor fan starts. The
outdoor fan motor runs continuously while unit is cooling.
heating -- units without
When the thermostat calls for heating, terminal W1 is energized.
To prevent thermostat short--cycling, the unit is locked into the
Heating mode for at least 1 minute when W1 is energized. The
induced--draft motor is energized and the burner ignition
sequence begins. The indoor (evaporator) fan motor (IFM) is
energized 45 seconds after a flame is ignited. On units equipped
for two stages of heat, when additional heat is needed, W2 is
energized and the high--fire solenoid on the main gas valve
(MGV) is energized. When the thermostat is satisfied and W1 is
deenergized, the IFM stops after a 45--second time--off delay.
Cooling -- units with economi$er
When free cooling is not available, the compressors will be
controlled by the zone thermostat. When free cooling is available,
the outdoor-air damper is modulated by the EconoMi$er IV
control to provide a 50_ to 55_F supply-air temperature into the
zone. As the supply-air temperature fluctuates above 55_ or
below 50_F, the dampers will be modulated (open or close) to
bring the supply-air temperature back within the set point limits.
Integrated EconoMi$er IV operation on single-stage units
requires a 2-stage thermostat (Y1 and Y2).
For EconoMi$er IV operation, there must be a thermostat call for
the fan (G). This will move the damper to its minimum position
during the occupied mode.
If the increase in cooling capacity causes the supply--air
temperature to drop below 45_F, then the outdoor--air damper
position will be fully closed. If the supply --air temperature
continues to fall, the outdoor--air damper will close. Control
returns to normal once the supply--air temperature rises above
48_F.
If optional power exhaust is installed, as the outdoor--air damper
opens and closes, the power exhaust fans will be energized and
deenergized.
If field--installed accessory CO
EconoMi$er IV control, a demand controlled ventilation strategy
will begin to operate. As the CO
above the CO
will be increased proportionally. As the CO
because of the increase in fresh air, the outdoor--air damper will
be proportionally closed. Damper position will follow the higher
demand condition from DCV mode or free cooling mode.
2
economizer
economizer
iv
sensors are connected to the
2
level in the zone increases
set point, the minimum position of the damper
2
level decreases
2
Damper movement from full closed to full open (or vice versa)
will take between 1--1/2 and 2--1/2 minutes.
If free cooling can be used as determined from the appropriate
changeover command (switch, dry bulb, enthalpy curve,
differential dry bulb, or differential enthalpy), a call for cooling
(Y1 closes at the thermostat) will cause the control to modulate
the dampers open to maintain the supply air temperature set point
at 50_ to 55_ F.
As the supply air temperature drops below the set point range of
50_ to 55_ F, the control will modulate the outdoor--air dampers
closed to maintain the proper supply--air temperature.
heating -- units with economi$er
When the room temperature calls for heat, the heating controls are
energized as described in the Heating, Units Without Economizer
section. When the thermostat is satisfied, the economizer damper
moves to the minimum position.
cooling -- units with economi$er2, premierlink
AND A THERMOSTA
When free cooling is not available, the compressors will be
controlled by the PremierLink control in response to the Y1 and
Y2 inputs from the thermostat.
The PremierLink control will use the following information to
determine if free cooling is available:
T
iv
t CONTROL
SIndoor fan has been on for at least 30 seconds.
SThe SPT, SAT, and OAT inputs must have valid
readings.
SOAT must be less than 75_F.
SOAT must be less than SPT.
SEnthalpy must be LOW (may be jumpered if an
enthalpy sensor not available).
SEconomizer position is NOT forced.
Pre-cooling occurs when there is no call from the thermostat
except G. Pre-cooling is defined as the economizer modulates to
provide 70_F supply air.
When free cooling is available the PremierLink control will
control the compressors and economizer to provide a supply-air
temperature determined to meet the Y1 and Y2 calls from the
thermostat using the following three routines. The three control
routines are based on OAT.
The 3 routines are based on OAT where:
SASP = Supply Air Set Point
DXCTLO = Direct Expansion Cooling Lockout Set Point
PID = Proportional Integral
Routine 1 (OAT < DXCTLO)
SY1 energized – economizer maintains a SASP =
(SATLO1 + 3).
SY2 energized – economizer maintains a SASP =
(SATLO2 + 3).
Routine 2 (DXCTLO<OAT<68_F)
SIf only Y1 energized, the economizer maintains a
SASP = (SATLO1 + 3).
SIf SAT > SASP + 5 and economizer position > 80%,
economizer will go to minimum position for 3 minutes
or until SAT > 68_F.
SFirst stage of mechanical cooling will be energized.
SIntegrator resets.
SEconomizer opens again and controls to current SASP
after stage one on for 90 seconds.
SWith Y1 and Y2 energized Economizer maintains an
SASP = SATLO2 + 3.
48HE,HJ
47
Page 48
SIf SAT > SASP + 5 and economizer position >80%,
economizer will go to minimum position for 3 minutes
or until SAT > 68_F.
SIf compressor one is on then second stage of
mechanical cooling will be energized; otherwise the
first stage will be energized.
SIntegrator resets.
SEconomizer opens again and controls to SASP after
stage one on for 90 seconds.
Routine 3 (OAT > 68)
SEconomizer is opened 100%.
SCompressors1and2arecycledbasedonY1andY2
using minimum on and off times and watching the
supply air temperature as compared to SATLO1 and
SATLO2 set points.
If optional power exhaust is installed, as the outdoor-air damper
opens and closes, the power exhaust fans will be energized and
deenergized.
48HE,HJ
If field-installed accessory CO
sensors are connected to the
2
PremierLink control, a PID-controlled demand ventilation
strategy will begin to operate. As the CO
increases above the CO
set point, the minimum position of the
2
level in the zone
2
damper will be increased proportionally. As the CO
decreases because of the increase in fresh air, the outdoor-air
damper will be proportionally closed.
HEATING -- UNITS WITH ECONOMI$ER2,
LINK CONTROL AND A THERMOSTA
T
When the thermostat calls for heating, terminal W1 is energized.
The PremierLink control will move the economizer damper to the
minimum position if there is a call for G and closed if there is a
call for W1 without G. In order to prevent thermostat from short
cycling, the unit is locked into the heating mode for at least 10
minutes when W1 is energized. The induced--draft motor is then
energized and the burner ignition sequence begins.
On units equipped for two stages of heat, when additional heat is
needed, W2 is energized and the high--fire solenoid on the main
gas valve (MGV) is energized. When the thermostat is satisfied
and W1 is deenergized, the IFM stops after a 45--second time--off
delay unless G is still maintained.
COOLING -- UNITS WITH ECONOMI$ER2,
LINK CONTROL AND A ROOM
SENSOR
When free cooling is not available, the compressors will be
controlled by the PremierLink controller using a PID Error
reduction calculation as indicated by Fig 51.
The PremierLink controller will use the following information to
determine if free cooling is available:
SIndoor fan has been on for at least 30 seconds.
SThe SPT, SAT, and OAT inputs must have valid
readings.
SOAT must be less than 75_F.
SOAT must be less than SPT.
SEnthalpy must be LOW (may be jumpered if an
enthalpy sensor is not available).
SEconomizer position is NOT forced.
2
PREMIER-
PREMIER-
level
TEMPERATURE CONTROL
75
74
73
72
71
70
69
SPACE TEMPERATURE
68
NOTE: PremierLink control performs smart staging of 2 stages of DX
cooling and up to 3 stages of heat.
TIME
SET POINT
TEMPERATURE
C06042
Fig. 51 --- DX Cooling T emperature
Control Example
TEMPERATURE CONTROL
75
74
73
72
71
70
69
SPACE TEMPERATURE
68
TIME
COOL SETPOINT
TEMPERATURE
HEAT SETPOINT
C06043
Fig. 52 --- Economizer Temperature
Control Example
When free cooling is available, the outdoor-air damper is
positioned through the use of a Proportional Integral (PID)
control process to provide a calculated supply-air temperature
into the zone. The supply air will maintain the space temperature
between the heating and cooling set points as indicated in Fig. 52.
The PremierLink control will integrate the compressor stages
with the economizer based on similar logic as the three routines
listed in the previous section. The SASP will float up and down
based on the error reduction calculations that compare space
temperature and space set point.
When outside-air temperature conditions require the economizer
to close for a compressor stage-up sequence, the economizer
control integrator is reset to zero after the stage-up sequence is
completed. This prevents the supply-air temperature from
dropping too quickly and creating a freeze condition that would
make the compressor turn off prematurely.
The high space set point is used for DX (direct expansion)
cooling control, while the economizer space set point is a
calculated value between the heating and cooling set points. The
economizer set point will always be at least one degree below the
cooling set point, allowing for a smooth transition from
mechanical cooling with economizer assist, back to economizer
cooling as the cooling set point is achieved. The compressors
may be used for initial cooling then the PremierLink controller
will modulate the economizer using an error reduction calculation
to hold the space temperature between the heating and cooling set
points. (See Fig. 52.)
The controller uses the following conditions to determine
economizer cooling:
SEnthalpy is Low
SSA T reading is available
SOA T reading is available
48
Page 49
SSPT reading is available
SOAT ± SPT
SEconomizer Position is NOT forced
If any of the above conditions are not met, the economizer
submaster reference (ECSR) is set to maximum limit and the
damper moves to minimum position. The operating sequence is
complete. The ECSR is recalculated every 30 seconds.
If an optional power exhaust is installed, as the outdoor-air
damper opens and closes, the power exhaust fans will be
energized and deenergized.
If field-installed accessory CO
PremierLink control, a PID-controlled demand ventilation
strategy will begin to operate. As the CO
increases above the CO
damper will be increased proportionally. As the CO
decreases because of the increase in fresh air, the outdoor-air
damper will be proportionally closed.
HEATING -- UNIT WITH ECONOMI$ER2,
LINK CONTROL AND A ROOM
Every 40 seconds the controller will calculate the required heat
stages (maximum of 3) to maintain Supply-Air Temperature
(SAT) if the following qualifying conditions are met:
set point, the minimum position of the
2
sensors are connected to the
2
level in the zone
2
2
PREMIER-
SENSOR
level
SIndoor fan has been on for at least 30 seconds.
SCOOL mode is not active.
SOCCUPIED, TEMP. COMPENSATED START or
HEAT mode is active.
SSA T reading is available.
SFire shutdown mode is not active.
If all of the above conditions are met, the number of heat stages is
calculated; otherwise the required number of heat stages will be
set to 0.
If the PremierLink controller determines that heat stages are
required, the economizer damper will be moved to minimum
position if occupied and closed if unoccupied.
Staging should be as follows:
If Heating PID STAGES=2
SHEAT STAGES=1 (50% capacity) will energize HS1
SHEAT STAGES=2 (100% capacity) will energize HS2
If Heating PID STAGES=3 and AUXOUT = HS3
SHEAT STAGES=1 (33% capacity) will energize HS1
SHEAT STAGES=2 (66% capacity) will energize HS2
SHEAT STAGES=3 (100% capacity) will energize HS3
In order to prevent short cycling, the unit is locked into the
Heating mode for at least 10 minutes when HS1 is deenergized.
When HS1 is energized the induced-draft motor is then
energized and the burner ignition sequence begins. On units
equipped for two stages of heat, when additional heat is needed,
HS2 is energized and the high-fire solenoid on the main gas valve
(MGV) is energized. When the space condition is satisfied and
HS1 is deenergized the IFM stops after a 45-second time-off
delay unless in the occupied mode. The fan will run continuously
in the occupied mode as required by national energy and fresh air
standards.
UNITS WITH HUMIDI-MIZER
DEHUMIDIFICATION
Normal Design Operation
When the rooftop operates under the normal sequence of
operation, the compressors will cycle to maintain indoor
conditions. (See Fig. 53.)
The Humidi-MiZer adaptive dehumidification system includes a
factory-installed Motormaster low ambient control to keep the
SYSTEM
ADAPTIVE
head and suction pressure high, allowing normal design cooling
mode operation down to 0 F.
Subcooling Mode
When subcooling mode is initiated, this will energize (close) the
liquid line solenoid valve (LLSV) forcing the hot liquid
refrigerant to enter into the subcooling coil. (See Fig. 54.)
As the hot liquid refrigerant passes through the subcooling/ reheat
dehumidification coil, it is exposed to the cold supply airflow
coming through the evaporator coil. The liquid is further
subcooled to a temperature approaching the evaporator
leaving-air temperature. The liquid then enters a thermostatic
expansion valve (TXV) where the liquid drops to a lower
pressure. The TXV does not have a pressure drop great enough to
change the liquid to a 2-phase fluid, so the liquid then enters the
Acutrol device at the evaporator coil.
The liquid enters the evaporator coil at a temperature lower than
in standard cooling operation. This lower temperature increases
the latent capacity of the rooftop unit. The refrigerant passes
through the evaporator and is turned into a vapor. The air passing
over the evaporator coil will become colder than during normal
operation. However, as this same air passes over the subcooling
coil, it will be slightly warmed, partially reheating the air.
Subcooling mode operates only when the outside air
temperature is warmer than 40_F. A factory-installed temperature
switch located in the condenser section will lock out subcooling
mode when the outside temperature is cooler than 40_F.
The scroll compressors are equipped with crankcase heaters to
provide protection for the compressors due to the additional
refrigerant charge required by the subcooling/reheat coil.
When in subcooling mode, there is a slight decrease in system
total gross capacity (5% less), a lower gross sensible capacity
(20% less), and a greatly increased latent capacity (up to 40%
more).
C06135
Fig. 53 --- Humidi--MiZer Normal
Design Cooling Operation
48HE,HJ
49
Page 50
SERVICE
Fig. 54 --- Humidi--MiZer Subcooling
Mode Operation
48HE,HJ
Fig. 55 --- Humidi--Mizert Hot Gas
Reheat Mode Operation
Hot Gas Reheat Mode
When the humidity levels in the space require humidity control, a
hot gas solenoid valve (specific to hot gas reheat mode only) will
open to bypass a portion of hot gas refrigerant around the
condenser coil. (See Fig. 55.)
This hot gas will mix with liquid refrigerant leaving the
condensercoilandflowtothesubcooling/reheat
dehumidification coil. Now the conditioned air coming off the
evaporator will be cooled and dehumidified, but will be warmed
to neutral conditions (72_Fto75_F) by the subcooling/reheat
dehumidification coil.
The net effect of the rooftop when in hot gas reheat mode is to
provide nearly all latent capacity removal from the space when
sensible loads diminish (when outdoor temperature conditions are
moderate). When in hot gas reheat mode, the unit will operate to
provide mostly latent capacity and extremely low sensible heat
ratio capability.
Similar to the subcooling mode of operation, hot gas reheat mode
operates only when the outside air temperature is warmer than
40_F. Below this temperature, a factory installed outside air
temperature switch will lockout this mode of operation.
See Table 39 for the Humidi-Mizer adaptive dehumidification
system sequence of operation.
C06136
C06137
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
When sevicing unit, shut off all electrical power to unit
and install lockout tag to avoid shock hazard or injury
from rotating parts.
Step 1 —Cleaning
Inspect unit interior at the beginning of heating and cooling
season and as operating conditions require.
EVAPORATOR
1. Turn unit power off, tag disconnect. Remove evaporator
coil access panel.
2. If economizer or two-position damper is installed, remove
economizerbydisconnectingMolexplugand
removing mounting screws.
3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dishwasher
detergent in a pressurized spray canister. Wash both sides
of coil and flush with clean water. For best results,
back-flush toward return-air section to remove foreign
material. Flush condensate pan after completion.
5. Reinstall economizer and filters.
6. Reconnect wiring.
7. Replace access panels.
Condenser
Inspect coil monthly. Clean condenser coil annually, and as
required by location and outdoor air conditions.
One--Row Coils
Wash coil with commercial coil cleaner. It is not necessary to
remove top panel.
2-Row Coils
Clean coil as follows:
coil
1. Turn off unit power, tag disconnect.
2. Remove top panel screws on condenser end o f unit.
3. Remove condenser coil corner post. (See Fig. 56.) To hold
top panel open, place coil corner post between top panel
and center post. (See Fig. 57.)
WARNING
COIL
C06044
Fig. 56 --- Cleaning Condenser Coil
50
Page 51
Table 39—Humidi-Mizer Adaptive Dehumidification System Sequence of Operation and
System Response — Single Compressor Unit (48HE003--006, 48HJ004-007)
THERMOSTAT INPUTECONOMIZER FUNCTION48HE, HJ UNIT OPERATION
HY1Y2OAT. < Economizer Set PointEconomizerComp. 1Subcooling ModeHot Gas Reheat Mode
Off——
OnOnOnNoOffOnYe sNo
OnOnOffNoOffOnYe sNo
OnOnOnYesOnOnYesNo
OnOnOffYesOnOnNoYe s
OnOffOffNoOffOnNoYe s
NOTE: On a thermostat call for W1, all cooling and dehumidification will be off.
LEGEND
OAT - -- Outdoor Air Temperature
Normal Operation
condensate
drain
Check and clean each year at the start of the cooling season. In
winter, keep the drain dry or protect it against freeze-up.
filters
Clean or replace at the start of each heating and cooling season, or
more often if operating conditions require it. Replacement filters
must be the same dimensions as the original filters.
outdoor-- air inlet scr
eens
Clean the screens with steam or hot water and a mild detergent.
Do not use disposable filters in place of screens.
Step 2 —Lubrication
C06045
Fig. 57 --- Propping Up Top Panel
essor
compr
The compressor is charged with the correct amount of oil at the
factory.
fan motor
bearings
Fan motor bearings are permanently lubricated. No further
lubrication is required.No lubrication of condenser- fan or
evaporator-fan motors is required.
Step 3 —Condenser--Fan Adjustment
Shut off unit power supply. Remove condenser-fan assembly
(grille, motor, motor cover, and fan) and loosen fan hub
setscrews. Adjust fan height as shown in Fig. 59. Tighten
setscrews and replace condenser-fan assembly.
48HE,HJ
C06046
Fig. 58 --- Separating Coil Sections
4. Remove screws securing coil to compressor plate and
compressor access panel.
5. Remove fastener holding coil sections together at return
end of condenser coil. Carefully separate the outer coil
section 3 to 4 in. from the inner coil section. (See Fig. 58.)
6. Use a water hose or other suitable equipment to flush
down between the 2 coil sections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in the
normal manner.
7. Secure inner and outer coil rows together with a
field-supplied fastener.
8. Reposition the outer coil section and remove the coil
corner post from between the top panel and center post.
Reinstall the coil corner post and replace all screws.
UNITFAN HEIGHT (in.) — “A”
003-006 AND 007 (208/230 v)2.75
007 (460 v)3.50
C06138
Fig. 59 --- Condenser--Fan Adjustment
Step 4 —EconoMi$er IV Adjustment
Refer to Optional EconoMi$er IV and EconoMi$er2 section.
Step 5 —Evaporator Fan Belt Inspection
Check con-dition of evaporator belt or tension during heating and
cooling inspections or as conditions require. Replace belt or
adjust as necessary.
Step 6 —High Pressure Switch
The high-pressure switch contains a Schrader core depressor, and
is located on the compressor hot gas line. This switch opens at
428 psig and closes at 320 psig. No adjustments are necessary.
51
Page 52
Step 7 —Loss--of--Charge Switch
The loss-of-charge switch contains a Schrader core depressor, and
is located on the compressor liquid line. This switch opens at 7
psig and closes at 22 psig. No adjustments are necessary.
Step 8 —Freeze--Stat
The freeze-stat is a bimetal temperature-sensing switch that is
located on the “hair-pin” end of theevaporator coil. The switch
protects the evaporator coil from freeze-up due to lack of airflow.
The switch opens at 30_F and closes at 45_F. No ad j u s tments are
necessary.
Step 9 —Refrigerant Charge
Amount of refrigerant charge is listed on unit nameplate (also
refer to Table 1). Refer to HVAC Servicing Procedures literature
available at your local distributor and the following procedures.
Unit panels must be in place when unit is operating during
charging procedure. Unit must operate a minimum of 10 minutes
before checking or adjusting refrigerant charge.
An accurate superheat, thermocouple-type or thermistor-type
thermometer, and a gauge manifold are required when using the
superheat charging method for evaluating the unit charge. Do not
48HE,HJ
use mercury or small dial-type thermometers because they are not
adequate for this type of measurement.
charge
No
Use standard evacuating techniques. After evacuating system to
500 microns, weigh in the specified amount of refrigerant. (Refer
to Table 1 or 2 and unit information plate.)
Low charge
cooling
Using Cooling Charging Charts, Fig. 60--63, vary refrigerant
until the conditions of the charts are met. Note the charging charts
are different from type normally used. Charts are based on
charging the units to the correct superheat for the various
operating conditions. Accurate pressure gage and temperature
sensing device are required. Connect the pressure gauge to the
service port on the suction line. Mount the temperature sensing
device on the suction line and insulate it so that outdoor ambient
temperature does not affect the reading. Indoor-air cfm must be
within the normal operating range of the unit.
HUMIDI--MIZER
SYSTEM CHARGING
The system charge for units with the Humidi-MiZer adaptive
dehumidification system is greater than that of the standard unit
alone. The charge for units with this option is indicated on the
unit nameplate drawing. Also refer to Fig. 64-67. To charge
systems using the Humidi-MiZer adaptive dehumidification
system, fully evacuate, recover, and recharge the system to the
nameplate specified charge level. To check or adjust refrigerant
charge onsystems usingthe Humidi-MiZer adaptive
dehumidification system, charge per Fig. 64-67.
C06139
Fig. 60 --- Cooling Charging Chart,
Standard 48HJ004
C06140
Fig. 61 --- Cooling Charging Chart,
Standard 48HJ005
52
Page 53
Fig. 62 --- Cooling Charging Chart,
Standard 48HJ006
Fig. 63 --- Cooling Charging Chart,
Standard 48HJ007
C06141
C06142
48HE,HJ
C06143
Fig. 64 --- Cooling Charging Chart, 48HJ004 with
Optional Humidi--MiZer Adaptive Dehumidification System
Fig. 65 --- Cooling Charging Chart, 48HJ005 with
Optional Humidi--MiZer Adaptive Dehumidification System
NOTE: When using the charging charts, it is important that only
the subcooling/reheat dehumidification coil liquid line solenoid
valve be energized. The subcooling/reheat dehumidification coil
liquid line solenoid valve MUST be energized to use the charging
charts and the outdoor motor speed controller jumpered to run the
fanatfullspeed.
53
C06144
Page 54
The charts reference a liquid pressure (psig) and temperature at a
point between the condenser coil and the subcooling/reheat
dehumidification coil. A tap is provided on the unit to measure
liquid pressure entering the subcooling/reheat dehumidification
coil.
IMPORTANT: The subcooling mode charging charts (Fig.
64--67) are to be used ONLY with units having the
Humidi--MiZer adaptive dehumidification system. DO NOT use
standard charge (Fig. 60--63) for units with Humidi--MiZer
system, and DO NOT use Fig. 64 --67 for standard units.
48HE,HJ
C06146
Fig. 67 --- Cooling Charging Chart, 48HJ007 with
Optional Humidi--MiZer Adaptive Dehumidification System
C06145
Fig. 66 --- Cooling Charging Chart, 48HJ005 with
Optional Humidi--MiZer Adaptive Dehumidification System
TO USE COOLING CHARGING CHART, ST
ANDARD
UNIT
Take the outdoor ambient temperature and read the suction
pressure gauge. Refer to charts to determine what suction
temperature should be. If suction temperature is high, add
refrigerant. If suction temperature is low, carefully recover some
of the charge. Recheck the suction pressure as charge is adjusted.
NOTE: When using the charging charts, it is important that only
the subcooling/reheat dehumidification coil liquid line solenoid
valve be energized. The subcooling/reheat dehumidification coil
SuctionLine Pressure (kpa)
liquid line solenoid valve MUST be energized to use the charging
charts and the outdoor motor speed controller jumpered to run the
fanatfullspeed.
Step 10 —Flue Gas Passageways
To inspect the flue collector box and upper areas of the heat
C06149
exchanger:
1. Remove the combustion blower wheel and motor
assembly according to directions in Combustion-Air
Blower section below.
2. Remove the 3 screws holding the blower housing to the
flue cover.
3. Remove the flue cover to inspect the heat exchanger.
4. Clean all surfaces as required using a wire brush.
Step 11 —Combustion--Air Blower
Clean periodically to ensure proper airflow and heating
efficiency. Inspect blower wheel every fall and periodically
during heating season. For the first heating season, inspect blower
wheel bimonthly to determine proper cleaning frequency.
To inspect blower wheel, remove draft hood and screen. Shine a
flashlight into opening to inspect wheel. If cleaning is required,
remove motor and wheel as follows:
1. Slide burner access panel out.
2. Remove the 5 screws that attach induced-draft motor
C06150
assembly to the vestibule cover.
3. Slide the motor and blower wheel assembly out of the
blower housing. The blower wheel can be cleaned at this
point. If additional cleaning is required, continue with
Steps 4 and 5.
4. To remove blower from the motor shaft, remove
2setscrews.
5. To remove motor, remove the 4 screws that hold the
motor to mounting plate. Remove the motor cooling fan
55
Page 56
by removing one setscrew. Then remove nuts that hold
motor to mounting plate.
6. To reinstall, reverse the procedure outlined above.
Step 12 —Limit Switch
Remove blower access panel (Fig. 8). Limit switch is located on
the fan deck.
Step 13 —Burner Ignition
Unit is equipped with a direct spark ignition 100% lockout
system. Integrated Gas Unit Controller (IGC) is located in the
control box (Fig. 13). A single LED on the IGC provides a visual
display of operational or sequential problems when the power
supply is uninterrupted. The LED can be observed through the
viewport. When a break in power occurs, the IGC will be reset
(resulting in a loss of fault history) and the evaporator fan on/off
times delay will be reset. During servicing, refer to the label on
the control box cover or Table 40 for an explanation of LED error
code descriptions.
If lockout occurs, unit may be reset by interrupting power supply
to unit for at least 5 seconds.
48HE,HJ
Table 40—LED Error Code Description*
REMOVAL AND REPLACEMENT OF GAS TRAIN
(See Fig. 72 and
73)
1. Shut off manual gas valve.
2. Shut off power to unit, tag d isconnect.
3. Remove compressor access panel.
4. Slide out burner compartment side panel.
5. Disconnect gas piping at unit gas valve.
6. Remove wires connected to gas valve. Mark each wire.
7. Remove induced-draft motor, igniter, and sensor wires at
the Integrated Gas Unit Controller (IGC).
8. Remove the 2 screws that attach the burner rack to the
vestibule plate.
9. Remove the gas valve bracket.
10. Slide the burner tray out of the unit (Fig. 73).
11. To reinstall, reverse the procedure outlined above.
*A 3-second pause exists between LED error code flashes. If more than
one error code exists, all applicable codes will be displayed in numerical sequence.
†Indicates a code that is not an error. The unit will continue to operate
when this code is displayed.
Normal Operation
Hardware Failure
Evaporator Fan On/Off Delay Modified
Limit Switch Fault
Flame Sense Fault
4 Consecutive Limit Switch Faults
Ignition Lockout Fault
Induced-Draft Motor Fault
Rollout Switch Fault
Internal Control Fault
Software Lockout
IMPORTANT: Refer to Troubleshooting Tables for additional
information.
Step 14 —Main Burners
At the beginning of each heating season, inspect for deterioration
or blockage due to corrosion or other causes. Observe the main
burner flames and adjust, if necessary.
!
CAUTION
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace
life.
When servicing gas train, do not hit or plug orifice spuds.
BURNER
SECTION
INDUCEDDRAFT
MOTOR
MANIFOLD
PRESSURE
TA P
Fig. 72 --- Burner Section Details
Fig. 73 --- Burner Tray Details
12. Reinstall burners on rack.
FLUE
EXHAUST
VESTIBULE
PLATE
BLOWER
HOUSING
GAS
VALV E
C06152
C06153
56
Page 57
48HJE/H004, 48HJD/G005-007 — 72,000 BTUH INPUT
LOW HEAT
48HJM004, 48HJL005,006 — 60,000 BTUH INPUT
48HEF003, 48HEE004, 48HED005 -
48HE,HJ
48HJE/H005-007, 48HJF/K004 — 115,000 BTUH INPUT
MEDIUMANDHIGHHEAT
48HJF/K005-007 — 150,000 BTUH INPUT
48HJM005,006; 48HJN004 — 90,000 BTUH INPUT
48HJN005,006 — 120,000 BTUH INPUT
48HEF004, 48HEE/F005, 48HED/E/F006 -
Fig. 74 --- Spark Gap Adjustment
Cleaning and
Adjustment
1. Remove burner rack from unit as described above.
2. Inspect burners and, if dirty, remove burners from rack.
3. Using a soft brush, clean burners and cross-over port as
required.
4. Adjust spark gap. (See Fig. 74.)
C06154
5. Reinstall burner rack as described above.
Step 15 —Replacement Parts
A complete list of replacement parts may be obtained from any
Carrier distributor upon request. Refer to Fig. 75 for a typical unit
wiring schematic.
57
Page 58
48HE,HJ
C—Contactor, Compressor
CAP— Capacitor
CLO— Compressor Lockout
COMP — Compressor Motor
EQUIP — Equipment
FPT— Freeze Up Protection Thermostat
FU— Fuse
GND— Ground
HPS— High-Pressure Switch
HS— Hall-Effect Sensor
I—Ignitor
IDM— Induced-Draft Motor
IFC— Indoor Fan Contactor
IFM— Indoor Fan Motor
IGC— Integrated Gas Unit Controller
LPS— Low-Pressure Switch
LS— Limit Switch
MGV— Main Gas Valve
OFM— Outdoor (Condenser) Fan Motor
OLR— Overload Relay
P—Plug
PL— Plug Assembly
QT— Quadruple Terminal
RS— Rollout Switch
SAT— Supply Air Temperature Sensor
TRAN — Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
NOTES:
1. If any of the original wire furnished must be replaced, it must
be replaced with type 90 C wire or its equivalent.
2. Three phase motors are protected under primary single
phasing conditions.
3. Use copper conductors only.
4. TRAN is wired for 230 v unit. If unit is to be run with 208 v
power supply, disconnect BLK wire from 230 v tap (ORN)
and connect to 208 v tap (RED). Insulate end of 230 v tap.
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential only;
not to represent wiring.
C06147
58
Page 59
TROUBLESHOOTING
Step 1 —Unit Troubleshooting
Refer to Tables 35-39 for unit troubleshooting details.
Step 2 —Economi$er IV Troubleshooting
See Table 40 for EconoMi$er IV logic.
A functional view of the EconoMi$er IV is shown in Fig. 69.
Typical settings, sensor ranges, and jumper positions are also
shown. An EconoMi$er IV simulator program is available from
CarriertohelpwithEconoMi$erIVtrainingand
troubleshooting.
Economi$er IV pr
This procedure is used to prepare the EconoMi$er IV for
troubleshooting. No troubleshooting or testing is done by
performing the following procedure.
NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm
resistor, and a 5.6 kilo-ohm resistor which are not supplied with
the EconoMi$er IV.
IMPORTANT: Be sure to record the positions of all
potentiometers before starting troubleshooting.
1. Disconnect power at TR and TR1. All LEDs should be
off. Exhaust fan contacts should be open.
2. Disconnect device at P and P1.
3. Jumper P to P1.
4. Disconnect wires at T and T1. Place 5.6 kilo-ohm resistor
across T and T1.
5. Jumper TR to 1.
6. Jumper TR to N.
7. If connected, remove sensor from terminals S
Connect 1.2 kilo-ohm 4074EJM checkout resistor across
terminals S
8. Put 620-ohm resistor across terminals S
9. Set minimum position, DCV set point, and exhaust
potentiometers fully CCW (counterclockwise).
10. Set DCV maximum position potentiometer fully CW
(clockwise).
11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.
differential
To check differential enthalpy:
1. Make sure EconoMi$er IV preparation procedure has been
performed.
2. Place 620-ohm resistor across S
3. Place 1.2 kilo-ohm resistor across S
Cool LED should be lit.
4. Remove 620-ohm resistor across S
LED should turn off.
5. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
single
enthalpy
To check single enthalpy:
1. Make sure EconoMi$er IV preparation procedure has been
performed.
2. Set the enthalpy potentiometer to A (fully CCW). The
Free Cool LED should be lit.
3. Set the enthalpy potentiometer to D (fully CW). The Free
Cool LED should turn off.
4. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
eparation
O
enthalpy
and +.
and +.
R
and +.
O
and +. The Free
R
and +. The Free Cool
O
O
and +.
dcv (demand controlled ventilation) and power
exhaust
To check DCV and Power Exhaust:
1. Make sure EconoMi$er IV preparation procedure has been
performed.
2. Ensure terminals AQ and AQ1 are open. The LED for
both DCV and Exhaust should be off. The actuator should
be fully closed.
3. Connect a 9-v battery to AQ (positive node) and AQ1
(negative node). The LED for both DCV and Exhaust
should turn on. The actuator should drive to between 90
and 95% open.
4. Turn the Exhaust potentiometer CW until the Exhaust
LED turns off. The LED should turn off when the
potentiometer is approximately 90%. The actuator should
remain in position.
5. Turn the DCV set point potentiometer CW until the DCV
LED turns off. The DCV LED should turn off when the
potentiometer is approximately 9v. The actuator should
drive fully closed.
6. Turn the DCV and Exhaust potentiometers CCW until the
Exhaust LED turns on. The exhaust contacts will close 30
to 120 seconds after the Exhaust LED turns on.
7. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
dcv minimum and maximum
position
To check the DCV minimum and maximum position:
1. Make sure EconoMi$er IV preparation procedure has been
performed.
2. Connect a 9-v battery to AQ (positive node) and AQ1
(negative node). The DCV LED should turn on. The
actuator should drive to between 90 and 95% open.
3. Turn the DCV Maximum Position potentiometer to
midpoint. The actuator should drive to between 20 and
80% open.
4. Turn the DCV Maximum Position potentiometer to fully
CCW. The actuator should drive fully closed.
5. Turn the Minimum Position potentiometer to midpoint.
The actuator should drive to between 20 and 80% open.
6. Turn the Minimum Position Potentiometer fully CW. The
actuator should drive fully open.
7. Remove the jumper from TR and N. The actuator should
drive fully closed.
8. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
supply--air
input
To check supply-air input:
1. Make sure EconoMi$er IV preparation procedure has been
performed.
2. Set the Enthalpy potentiometer to A. The Free Cool LED
turns on. The actuator should drive to between 20 and
80% open.
3. Remove the 5.6 kilo-ohm resistor and jumper T to T1. The
actuator should drive fully open.
4. Remove the jumper across T and T1. The actuator should
drive fully closed.
5. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
economi$er IV troubleshooting
completion
This procedure is used to return the EconoMi$er IV to operation.
No troubleshooting or testing is done by performing the
following procedure.
1. Disconnect power at TR and TR1.
2. Set enthalpy potentiometer to previous setting.
48HE,HJ
59
Page 60
3. Set DCV maximum position potentiometer to previous
setting.
4. Set minimum position, DCV set point, and exhaust
potentiometers to previous settings.
5. Remove 620-ohm resistor from terminals S
R
and +.
6. Remove 1.2 kilo-ohm checkout resistor from terminals S
and +. If used, reconnect sensor from terminals SOand +.
Table41—LEDErrorCodeServiceAnalysis
7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
9. Remove 5.6 kilo-ohm resistor from T and T1. Reconnect
wires at T and T1.
10. Remove jumper from P to P1. Reconnect device at P and
O
P1.
11. Apply power (24 vac) to terminals TR and TR1.
Hardware Failure.
(LED OFF)
Fan ON/OFF Delay Modified
(LED/FLASH)
Limit Switch Fault.
48HE,HJ
(LED 2 Flashes)
Flame Sense Fault.
(LED 3 Flashes)
4ConsecutiveLimit
Switch Faults.
(LED 4 Flashes)
Ignition Lockout.
(LED 5 Flashes)
Induced-Draft Motor Fault.
(LED 6 Flashes)
Rollout Switch Fault.
(LED 7 Flashes)
Internal Control Fault.
(LED 8 Flashes)
Temporary Software
Lockout
(LED 9 Flashes)
SYMPTOMCAUSEREMEDY
Loss of power to control module (IGC).Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and
High limit switch opens during heat
exchanger warm-up period before fan-on
delay expires.
Limit switch opens within three minutes
after blower-off delay timing in Heating
mode.
High temperature limit switch is open.Check the operation of the indoor (evaporator) fan motor.
The IGC sensed flame that should not be
present.
Inadequate airflow to unit.Check operation of indoor (evaporator) fan motor and that supply-air
Unit unsuccessfully attempted ignition for
15 minutes.
IGC does not sense that induced-draft
motor is operating.
Rollout switch has opened.Rollout switch will automatically reset, but IGC will continue to
Microprocessor has sensed an error in the
software or hardware.
Electrical interference is impeding the IGC
software.
transformer. Units without a 24-v circuit breaker have an internal
overload in the 24-v transformer. If the overload trips, allow
10 minutes for automatic reset.
Ensure unit is fired on rate and temperature rise is correct.
Ensure units’ external static pressure is within application guidelines.
Ensure that the supply-air temperature rise is in accordance with
the range on the unit nameplate.
Reset unit. If problem persists, replace control board.
temperature rise agrees with range o n unit nameplate information.
Check ignitor and flame sensor electrode spacing, gaps, etc.
Ensure that flame sense and ignition wires are properly
terminated. Verify that unit is obtaining proper amount of gas.
Check for proper voltage. If motor is operating, check the
speed sensor plug/IGC Terminal J2 connection. Proper
connection: PIN 1— White, PIN 2 — Red, PIN 3 — Black.
lock out unit. Check gas valve operation. Ensure that induceddraft blower wheel is properly secured to motor shaft.
Reset unit at unit disconnect.
If error code is not cleared by resett ing unit power, replace the IGC.
Reset 24-v to control board or turn thermostat off and then on. Fault
will automatically reset itself in one hour.
!
CAUTION
COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in component
damage.
If the IGC must be replaced, be sure to ground yourself to
dissipate any electrical charge that may be present before
handling new control board. The IGC is sensitive to static
electricity and may be damaged if the necessary precautions
are not taken.
LEGEND
IGC --- Integrated Gas Unit Controller
LED --- L i g h t --- E m i t t i n g Di o d e
IMPORTANT: Refer to heating troubleshooting for additional
heating section troubleshooting information.
60
Page 61
Table 42— Heating Service Analysis
PROBLEMCAUSEREMEDY
Burners Will Not
Ignite.
Inadequate Heating.Dirty air filter.Clean or replace filter as necessary.
Poor Flame
Characteristics.
Burners Will Not
Tu r n O f f .
Misaligned spark electrodes.Check flame ignition and sensor electrode positioning. Adjust as needed.
No gas at main burners.Check gas line for air purge as necessary. After purging gas line of air, allow gas
Water in gas line.Drain water and install drip leg to trap water.
No power to furnace.Check power supply, fuses, wiring, and circuit breaker.
No 24 v power supply to control circuit.Check transformer. Transformers with internal overcurrent protection require a
Miswired or loose connections.Check all wiring and wirenut connections.
Burned-out heat anticipator in thermostat.Replace thermostat.
Broken thermostat wires.Run continuity check. Replace wires, if necessary.
Gas input to unit too low.Check gas pressure at manifold. Clock gas meter for input. If too low, increase
Unit undersized for application.Replace with proper unit or add additional unit.
Restricted airflow.Clean filter, replace filter, or remove any restrictions.
Blower speed too low.Use high speed tap, increase fan speed, or install optional blower, as suitable
Limitswitchcyclesmainburners.Check rotation of blower, thermostat heat anticipator settings, and temperature
Too much outdoor air.Adjust minimum position.
Incomplete combustion (lack of
combustion air) results in:
Aldehyde odors, CO (carbon monoxide),
sooting flame, or floating flame.
Unit is locked into Heating mode for a
one minute minimum.
to dissipate for at least 5 minutes before attempting to relight unit.
Check gas valve.
cool-down period before resetting. Check 24-v circuit breaker; reset if necessary.
manifold pressure or replace with correct orifices.
for individual units, Adjust pulley.
rise of unit. Adjust as needed.
Check economizer operation.
Check all screws around flue outlets and burner compartment. Tighten as nec-
essary.
Cracked heat exchanger.
Overfired unit — reduce input, change orifices, or adjust gas line or manifold
pressure.
Check ven t for restriction. Clean as necessary.
Check orifice to burner alignment.
Wait until mandatory one-minute time period has elapsed or reset power to
unit.
48HE,HJ
Table 43—Humidi-MiZer Adaptive Dehumidification System Subcooling Mode Service Analysis
Subcooling Mode (Liquid Reheat)
Will Not Energize.
Low System Capacity.Low refrigerant charge or frosted evaporator coil.1. Check charge amount. Charge per Fig. 64-67.
Loss of Compressor Superheat
Conditions with Subcooling/Reheat
Dehumidification Coil Energized.
PROBLEMCAUSEREMEDY
No power to control transformer from
evaporator-fan motor.
No power from control transformer to liquid lin e
solenoid valve.
Liquid line solenoid valve will not operate.1. Solenoid coil defective; replace.
Liquid line solenoid valve will not open.Valve is stuck closed; replace valve.
Thermostatic expansion valve (TXV).1. Check TXV bulb mounting, and secure tightly to suc-
Check power source and evaporator-fan relay. Ensure all
wire connections are tight.
1. Fuse open; check fuse. Ensure continuity of wiring.
2. Low-pressure switch open. Cycle unit off and allow
low-pressure switch to reset. Replace switch if it will
not close.
3. Transformer bad; check transformer.
2. Solenoid valve stuck open; replace.
2. Evaporator coil frosted; check and replace low-pressure switch if necessary.
tion line.
2. Replace TXV if stuck open or closed.
Table 44—Humidi-MiZer Adaptive Dehumidification System Hot Gas Reheat Mode Service Analysis
Reheat Mode Will Not Energize.No power to control transformer from
Loss of Compressor Superheat
Conditions with Subcooling/Reheat
Dehumidification Coil Energized.
Excessive Superheat.Liquid line solenoid valve will not operate.Valve is stuck, replace valve.
PROBLEMCAUSEREMEDY
evaporator-fan motor.
No power from control transformer to hot gas
line solenoid valve
Hot gas line solenoid valve will not operate.1. Solenoid coil defective; replace.
Low refrigerant charge or frosted evaporator coil.1. Check charge amount. Charge per Fig. 64 --- 67.
Thermostatic expansion valve (TXV).1. Check TXV bulb mounting, and secure tightly to suc-
Hot gas line solenoid valve will not close.Valve is stuck; replace valve.
Check power source and evaporator-fan relay. Ensure all
wire connections are tight.
1. Fuse open; check fuse. Ensure continuity of wiring.
2. Low-pressure switch open. Cycle unit off and allow
low-pressure switch to reset. Replace switch if it will
not close.
3. Transformer bad; check transformer.
2. Solenoid valve stuck closed; replace.
2. Evaporator coil frosted; check and replace low-pressure switch if necessary.
Power failure.Call power company.
Fuse blown or circuit breaker tripped.Replace fuse or reset circuit breaker.
Defective thermostat, contactor, transformer, or
control relay.
Insufficient line voltage.Determine cause and correct.
Incorrect or faulty wiring.Check wiring diagram and rewire correctly.
Thermostat setting too high.Lower thermostat setting below room tempera-
Faulty wiring or loose connections in compressor circuit.
Compressor motor burned out, seized, or internal overload open.
One leg of 3-phase power dead.Replace fuse or reset circuit breaker. Determine
Refrigerant overcharge or undercharge.Recover refrigerant, evacuate system, and re-
Defective compressor.Replace and determine cause.
Insufficient line voltage.Determine cause and correct.
Blocked condenser.Determine cause and correct.
Defective run/start capacitor, overload, or start
relay.
Defective thermostat.Replace thermostat.
Faulty condenser-fan motor or capacitor.Replace.
Restriction in refrigerant system.Locate restriction and remove.
Dirty air filter.Replace filter.
Unit undersized for load.Decrease load or increase unit size.
Thermostat set too low.Reset thermostat.
Low refrigerant charge.Locate leak, repair, and recharge.
Leaking valves in compressor.Replace compressor.
Air in system.Recover refrigerant, evacuate system, and re-
Condenser coil dirty or restricted.Clean coil or remove restriction.
Dirty air filter.Replace filter.
Dirty condenser coil.Clean coil.
Refrigerant overcharged.Recover excess refrigerant.
Air in system.Recover refrigerant, evacuate system, and re-
Condenser air restricted or air short-cycling.Determine cause and correct.
Low refrigerant charge.Check for leaks, repair, and recharge.
Compressor valves leaking.Replace compressor.
Restrictioninliquidtube.Remove restriction.
High heat load.Check for source and eliminate.
Compressor valves leaking.Replace compressor.
Refrigerant overcharged.Recover excess refrigerant.
Dirty air filter.Replace filter.
Low refrigerant charge.Check for leaks, repair, and recharge.
Metering device or low side restricted.Remove source of restriction.
Insufficient evaporator airflow.Increase air quantity. Check filter and replace if
Temperature too low in conditioned area.Reset thermostat.
Outdoor ambient below 25 F.Install low-ambient kit.
Time off delay not finished.Wait for 30-second off delay.
Replace component.
ture.
Check wiring and repair or replace.
Determine cause. Replace compressor.
Determine cause and replace.
cause.
charge to nameplate.
Determine cause and replace.
charge.
charge.
necessary.
62
Page 63
Table 46—EconoMi$er IV Input/Output Logic
INPUTSOUTPUTS
Demand Control
Ventilation (DCV)
Below set
(DCV LED Off)
High
(Free Cooling LED Off)
Enthalpy*
OutdoorReturn
LowOn OnOnOnMinimum positionClosed
Y1 Y2
On OffOnOff
Off OffOffOff
Low
(Free Cooling LED On)
HighOn OnOnOffModulating** (between min.
On OffOffOff
Off OffOffOffMinimum positionClosed
Above set
(DCV LED On)
High
(Free Cooling LED Off)
LowOn OnOnOnModulating†† (between min.
On OffOnOff
Off OffOffOff
Low
(Free Cooling LED On)
HighOn OnOnOffModulating***Modulating†††
On OffOffOff
Off OffOffOff
*For single enthalpy control, the module compares outdoor enthalpy to the ABCD set point.
†Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied).
**Modulation is based on the supply-air sensor signal.
††Modulation is based on the D CV signal.
***Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum position (DCV) or fully open (sup-
ply-air signal).
†††Modulation is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV) or fully open (supply-airsig-
nal).
CompressorNTerminal†
Stage1Stage
2
position and full-open)
position and DCV maximum)
OccupiedUnoccupied
Damper
Modulating** (between
closed and full-open)
Modulating†† (between
closed and DCV
maximum)
48HE,HJ
Fig. 76 --- EconoMi$er IV Functional View
63
C06053
Page 64
START-UP CHECKLIST
(Remove and Store in Job File)
I. PRELIMINARY INFORMATION
MODEL NO.:SERIAL NO.:
DA TE:TECHNICIAN:
II. PRE-START-UP (insert checkmark in box as each item is completed)
jVERIFY THA T JOBSITE VOL T AGE AGREES WITH VOL T AGE LISTED ON RATING PLATE
jVERIFY THA T ALL PACKAGING MA TERIALS HA VE BEEN REMOVED FROM UNIT
jREMOVE ALL SHIPPING HOLDDOWN BOLTS AND BRACKETS PER INSTALLA TION INSTRUCTIONS
jVERIFY THA T CONDENSATE CONNECTION IS INSTALLED PER INSTALLA TIO N INSTRUCTIONS
jCHECK ALL ELECTRICAL C ONNECTIONS AND TERMINALS FOR TIGHTNESS
jCHECK GAS PIPING FOR LEAKS
jCHECK THA T RETURN (INDOOR) AIR FIL TERS ARE CLEAN AND IN PLACE
48HE,HJ
jVERIFY THAT UNIT INSTALLATION IS LEVEL
jCHECK FAN WHEELS AND PROPELLER F OR LOCATION IN HOUSING/ORIFICE AND SETSCREW
TIGHTNESS
jCHECK TO ENSUR E TH AT ELECTRICAL WIRING IS NOT IN CO NTACT WITH REFR IGERA NT LINES
OR SHARP METAL EDGES
j CHECK PULLEY ALIGNMENT AND BELT TENSION PER INST A LLATION IN STR UCTIO NS
III. START-UP
ELECTRICAL
SUPPL Y VOLTAGEL1-L2L2-L3
L3-L1
COMPRESSOR AMPSL1L2L3
INDOOR-FAN AMPSL1L2L3
TEMPERATURES
OUTDOOR-AIR TEMPERA TURE
RETURN-A IR TEMPERATURE
COOLING SUPPL Y AIR
DB
DBWB
DB
HEATINGSUPPLYAIRDB
PRESSURES (Cooling Mode)
GAS INLET PRESSURE
GAS MANIFOLD PRESSURE
IN.WG
IN.WG (HIGH FIRE)
REFRIGERANT SUCTIONPSIG
REFRIGERANT DISCHARGE
PSIG
jVERIFY THA T 3-PHASE F AN MOTOR AND BLOWER ARE ROTATING IN CORRECT DIRECTION. IF THEY
ARE NOT ROTATING IN CORRECT DIRECTION, LOCKING COLLAR MUST BE RE--TIGHTENED AFTER
CORRECTING DIRECTION OF ROTATION
jVERIFY THAT 3-PHASE SCROLL COMPRESSOR IS ROT ATING IN THE CORRECT DIRECTION
jVERIFY REFRIGERANT CHARGE USING CHARGING CHARTS
Copyright 2006 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Manufacturer reserv es the right to change, at a ny time, specifica tions and designs witho ut notice and without obliga tions.
Printed in U.S.A.Edition Date:09/06
64
Catalog No:48H--1SI
Replaces:48HJ--33SI
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.