Carrier 48GX060090300, 48GX048115300, 48GX048090300, 48GX042090300, 48GX042060300 Installation Guide

...
HFATUNG & COOLING
Single Packaged Gas Heating/
%isdt_ v_v_carrier.corn
Installation, Start-Up, and Operating
48GS Sizes 018-060, 48GX Sizes 024-060
48GS, 48GX
Electric Cooling Units
NOTE: Read the entire instruction manual before starting the installation
TABLE OF CONTENTS
SAFETY C ONSIDERATI(INS 1 INTRODE CTION 2
RECEIVING AND INSTALLATION .......................................... 2
CHECK EQUIPMENT ............................................................. 2
IDENTIFY EJNIT ................................................................ 2
INSPECT SHIPMENT ........................................................ 2
INSTALLATION ................................................................ 2
PROVIDE UNIT SUPPORT. ................................................... 2
ROOF (LRB ....................................................................... 2
SLAB MOUNT ................................................................... 2
GROL_D MOL_T ............................................................ 5
FIELD FABRICATE DUCTW()RK ........................................ 5
PROVIDE CLEARAN( ES ...................................................... 6
RIG AND PLA(E ENIT ......................................................... 7
CONNECT CONDENSATE DRAIN ...................................... 7
INSTALL FLUE HOOD .......................................................... 8
INSTALL GAS PIPING ........................................................... 8
INSTALL DUCT ( ONNE( TIONS ...................................... 10
(ONFIGURING UNITS FOR DO\}_TLOW (VERTI-
CAL) DISCHARGE .......................................................... 10
INSTALL ELECTRICAL ( ONNE(TIONS ......................... 12
HIGH-V()LTAGE CONNECTIONS ................................ 12
SPECIAL PROCEDURES FOR 208°V OPERATION ._ 13
CONTROL VOLTAGE CONNECTIONS ....................... 13
HEAT ANTICIPATOR SETTING ................................... 13
TRAN SFORMER PR()TECTION .................................... 13
PRE-START-E P .......................................................................... 15
START-UP ................................................................................... 15
(HECK FOR REFRIGERANT LEAKS ............................... 15
START°UP HEATING AND MAKE ADJUSTMENTS ...... 16
CHE(K HEATING CONTROL ....................................... 16
CHECK GAS INPUT ........................................................ !6
ADJUST GAS INPET ...................................................... 16
CHECK BURNER FLAME .............................................. 20
AIRFLOW AND TEMPERATURE RISE ....................... 20
HEATING SEQUEN(E OF OPERATION ..................... 20
LIMIT SWITCHES ........................................................... 20
AE XILIARY LIMIT SWITCH (ROLLOE T) .................. 21
START°E P COOLING AND MAKE ADJUSTMENTS ...... 21
CHECKING COOLING CONTROL OPERATION ....... 2!
< HE(KING AND ADJUSTING REFRIGERANT
CHARGE ........................................................................... 21
INDOOR AIRFLOW AND AIRFLOW ADJUST-
MENTS .............................................................................. 22
COOLING SEQE ENCE OF OPERATION ..................... 22
MAINTENANCE ......................................................................... 22
AIR FILTER ...................................................................... 25
EVAPORATOR BLOWER AND MOT()R ..................... 25
FLEE GAS PASSAGEWAYS ......................................... 27
COMBUSTION-AIR BLOWER ....................................... 27
LIMIT SWIT(H ................................................................ 28
BURNER IGNITION ........................................................ 28
MAIN BE RNERS ............................................................. 28
CONDENSER COIL, EVAPORATOR (OIL, AND
CONDENSATE DRAIN PAN .......................................... 29
CONDENSER FAN .......................................................... 29
ELECTRICAL CONTROLS AND WIRING .................. 30
REFRIGERANT CIRCUIT ............................................... 30
GAS INPUT ...................................................................... 30
EVAPORATOR AIRFLOW ............................................. 30
METERING DEVICE A(UTROL DEVICE ............. 30
LIQUID LINE STRAINER .............................................. 30
TROE BLESHOOTING ............................................................... 30
START-UP CHEf KLIST ............................................................ 30
NOTE TO INSTALLER Before the installatiom READ THESE INSTRU(TIONS CAREFELLY AND (OMPLETELY. Also,
make sure the User's Manual and Replacement Guide are left with the unit after installation. The furnace is NOT to be used for
temporary heating of buildings or structures under construction.
A99338
Fig. 1--Unit 48GS and 48GX
(Low NO× Model Available)
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and ebctrical components Only trained and qualified personnel should install, repair, or service air-conditioning equipment.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring oNigations.
PC 101 Catalog No 534-80128 Printed in U.S.A Form 48GS.GX-6SI Pg 1 11-02 Replaces: 48GS.GX-5SI
Untrained personnel can perfbrm basic maintenance functions of
cleaning coils and filters. All other operations should be perfbrmed
by tlained service personnel When working on air-conditioning
equipmenL observe precautions in the literature, tags, and labels attached to the unit, and other safety precautions that may apply.
Follow all safe V codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguisher available ibr all brazing operations.
Improper installation, adjustment, aheration, service, mainte- nancQ or use can cause carbon monoxide poisoning, fire, or an explosion which can result in personal injury or unit damage. Consuh a qualified installer, service agency, or gas supplier for information or assistance. The qualified installer or agency must use only factory-authorized kits or accessories
when modifying this product
Beibre peribrming service or maintenance operations on mail mrn off gas supply to unit. Then mrn off unit main power switch and install lockout tag. Elecn'ical shock or explosion could cause serious inju_ or death.
Recognize safety infbrmation This is the safety-alert symbolz_ When you see this symbol in instructions or manuals, be alert to the potential _br personal injory.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safcV-alert symboh
DANGER identifies the most serious hazards which will result in
serious injury or death. WARNING signifies a hazard which could
result in serious inju V or death. CAUTION is used to identii_, unsafe practices which would result in minor personal injury or
product and property damage. NOTE is used to highlight sugges- tions which will result in enhanced installation, reliability, or
operation. These instructions cover minimuna requirements and confbrm to
existing national standards and safety codes. In some instances,
these instructions exceed certain local codes and ordinances,
especially those that may not have kept up with changing residen- tial construction practices. We require these instructions as a minimum ibr a saf_ installation.
INTRODUCTION
The 48GS and 48GX units (See Fig. 1) are fu!ly self_containe&
combination Category- I gas heating/electric cooling units designed
ibr outdoor installation (See Fig. 2 and 3 for unit dimensions). All unit sizes have return and discharge openings ibr both horizontal
and downflow configurations, and are ii_ctory shipped with all
downflow duct openings covered. Units may be installed either on
a rooftop, a cement slab, or directly on the ground if local codes permit (See Fig. 4 for roof curb dimensions).
Models with an N in the fifth position of the model nmnber are
dedicated Low NOxunits designed fbr California installations.
These models meet the California maximum oxides of nitrogen
(NOx) emissions requirements of 40 nanograms joule or less as
shipped from the factory and must be installed in California Air
Quality Management Districts where a Low NO× rule exists.
RECEBVING AND INSTALLATION
Step 1--CHECK EQUIPMENT
IDENTIFY UNIT
The unit model number and serial nunfber are stamped on unit
identification plate. Check this information against shipping papers
and job data. Verit}' unit voltage and amperage requirements listed on unit rating plate agree with power supply provided to unit
INSPECT SHIPMENT Inspect for shipping damage while unit is still on shipping pallet.
If unit appears to be damaged or is torn loose t'rom its anchorage, have it examined by transportation inspectors before removal
Forward claim papers directly to transportation company Manu- facturer is not responsible for any damage incurred in transit
Check all items against shipping list Immediately notify the nearest distributor if any item is missing.
To prevent loss or damage, leave all parts in original packages until installation.
INSTALLATION
1. Remove unit from shipping carton Leave top shipping skid on the unit as a spreader bar to prevent the rigging straps from
damaging the unit. If the wood skid is not available, use a spreader bar of sufficient length to protect unit t_-om damage.
2. Position the tiffing bracket assembly around the base of the unit. Be sure the strap does not twist
3. Place each of the 4 metal lifting brackets into the rigging holds in the composite pan.
4. Thread liking bracket strapping around bottom perimeter of unit as follows:
a Open lever of tension buckle (ratchet type) b. Feed strapping throngh tension buckle as shown in Fig 7A. c Pull strapping through tension buckle unit taut. d. Snap lever down to lock strap in tension buckle To release
strapping, squeeze safkty latch, Ilk lever, and pull webbing outward
5. Tighten the tension buckle until it is taut Lifting brackets must be secure in the rigging holds
6. Attach field=supplied clevis or hook of sufficient strength to hole in the liking bracket (See Fig. 7B).
7. Attach the 2 safkty straps directly to the clevis or hook at the 4 rigging brackets. DO NOT attach the safkty straps to the lifting brackets (See Fig. 7B).
8. Position liking point directly over the unit's center of gravity.
9. Lift unit. When unit is directly over the roof curb, remove the 2 safety straps. Lower the equipment onto the roof curb.
Step 2--PROVIDE UNiT SUPPORT
ROOF CLRB Install accessory roof curb in accordance with instructions shipped
with curb (See Fig. 4 for roof curb dimensions). Install insulation, cant strips, roofing, and flashing Ductwork must be attached to
curb
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasketing material supplied with the roof curb. Improperly applied gasketing can also result in air leaks and poor unit perfbrmance.
Cm:b should be level to within 1/4 in. This is necessa_' for unit drain to Nnction properly. Refkr to accessory roof curb installation instructions for additional information as required.
SLAB MOUNT Place the unit on a solid, level concrete pad that is a minimum of
4 in. thick with 2 in. above grade. The slab should be flush on the compressor end of the unit (to allow condensate &ain installation) and should extend 2 in. on the three remaining sides of the unit (See Fig. 6). Do not secure the unit to the slab e:vcept when required by local codes.
(t CD,[ [_H [ GJ I _1,
OPU 6
t '
i N
ZS4 "" 5q } _ 5 :
86 I _ _ j
[_9 K,] [ [2, _o] _ [o oo] i
, : _C,_494_ 0_i t:¸
i
249 ;
i,, s1
550 5 ?49 6
IN _;i }9 8_]
REAR ViEW
REQUIRED CLEARANCE TO COMBUSTIBLE MATL
TOP OF UNIT ................................................................................... 14.00 [355 6]
DUCT SIDE OF UNIT ......................................................................... 200 [508]
SIDE OPPOSITE DUCTS ................................................................ 14.00 [355 8]
BOTTOM OF UNIT ............................................................................. 050 [127]
ELECTRIC HEAT PANEL ................................................................. 3600 [914 4]
NEC. REQUIRED CLEARANCES,
BETWEEN UNITS, POWER ENTRY SIDE .................................... 42.00 [1086 8]
UNIT AND UNGROUNDED SURFACES. POWER ENTRY SIDE 3800 [914 0] UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES POWER ENTRY SIDE ......................... 4200 [1066 8]
LEGEND CO Centerof OravRy
COND Condensor EVAP Evap@ator
NEC National E[ectnca[Code REQ'D Reqused
NOTE:Dimensions are in in [mm]
INCHES [mm]
INCHES [mm]
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
EVAR COIL ACCESS SIDE ............................................................ 36.00 [914 0]
POWER ENTRY SIDE .................................................................... 3600 [914 0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP ....................................................................................... 48.00 [1219 2]
SIDE OPPOSITE DUCTS .............................................................. 36.00 [914 0]
DUCT PANEL ................................................................................. 1200 [304 8] *
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 1200 [304 8] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE
INCHES [mm]
UNIT
48GS018040 48GS024040/080 48GS030040/080
48GS038060/090 48GS042060/090 48GX624040/060 48GX036040/060
48GX036066/090
ELECTRICAL CHARACTERISTICS
208/230-1-60 208/230-1-60
208/230-1-60, 208/230-3-60 208/230-1-60, 208/230-3-60, 460-3-60 208/230-1-60, 208/230-3-60, 460-3-60
208/230-1-60
208/230-1-60, 208/230-3-60 208/230-1-60, 208/230-3-60,460-3-60
Fig. 2--48GS018-042 and 48GX024-036 Unit Dimensions
UNIT WEIGHT
Ib T kg
249.0 113.2
280.0 127.3
280.0 127.3
320.0 145.1
355.0 161.4
290.0 131.5
313.0 142.0
321.0 145.6
UNIT HEIGHT IN. ([VIM)
,,A,_
35.02 (889.5)
35.02 (889.5)
35.02 (889.5)
37.02 (940.3)
35.02 (889.5)
37.02 (940.3)
39.02 (991.1)
35.02 (889.5)
X
20.0 (508.0)
22.5 (571.5)
21.5 (546.1)
22.5 (571.5)
21.5 (546.1)
22.0 (558.8)
22.0 (558.8)
22.0 (558.8)
CENTER OF GRAVITY
IN.(MM)
Y
140 (3556) 130 (3302)
1375 (349.3)
140 (355.6) 135 (342.9)
145 (3683) 153 (3874)
153 (387.4)
COOO55
Z
15.0(3810)
15.0(3810) 150 (3810)
130 (3302) 130 (3302)
16.0 (4064) 176 (4470)
165 (4191)
70 4 [2 77] i
[33£1
3558 {1411]
_3427 _ 3558
[!3 49] [14 Oi]
SUPPLY
402 o [15 83]
i E_AP COIL
[1177
{a 631
i
88 3 [3 46] [13831 [13 62] [13831
REAR VIEW
REQUIRED CLEARANCE TO COMBUSTIBLE MATE
TOP OF UNIT ................................................................................... 14,00 [355 6]
DUCT SIDE OF UNIT ......................................................................... 2.00 [50.8]
SIDE OPPOSITE DUCTS ................................................................ 14,00 [355 6]
BOTTOM OF UNIT ............................................................................. 0.50 [12.7]
FLUE PANEL .................................................................................... 36,00 [914 4]
NEC. REQUIRED CLEARANCES,
BETWEEN UNITS, POWER ENTRY SIDE .................................... 4200 [1066.6]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE 3600 [914.0] UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE ......................... 4200 [1066 8]
k_- 10906
[42 943
INCHES [mini
INCHES [mm]
1939 _'< _ !15 4 NOTE:Dimensionsare in in, [ram]
47 OO] [4 54]
C01L
4066 [1601]
[16 O!]
TOP VIEW
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
EVAR COIL ACCESS SIDE ............................................................ 3600 [914 0]
POWER ENTRY SIDE .................................................................... 3600 [914 0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP ....................................................................................... 4800 [1219.2]
SIDE OPPOSITE DUCTS .............................................................. 3600 [914 0]
DUCT PANEL ................................................................................. 1200 [304 8] *
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 1200 [304 8] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.
LEGEND
CG - Center of Gravity COND - Condensor
EVAP- Evaporator NEC - National Electrical Code
REQ'D - Required
INCHES [mm]
L._ It231
[44 22]
LEFT SIDEVIEW
UNiT
48G8048090/115/130 48GS0600901115/130
48GX042060/090
48GX048090/115/190 48GX060090f115/130
" ....................... 12 i [O 881 OlA I@lE ' ..............
i \ o
[ 68] MPRESSOR,BLOtlER 6AS S{CTION FLUE FLOOD fY _4] 7 [O 50] N P T
329 O & Et CTR CAt £;¢[SS PANEl 528 GAS ENTRY 5 O
ELECTRICAL CHARACTERISTICS
208-230/1/60, 208/230-3-60, 460-%60 208/230-1-60, 208/230-%60, 460-3%0
208/230-1-60, 208/230-3-60, 460-3-60 208/230-1-60, 208/230-%60, 460-3-60 208/230-1-60, 208/230-%60, 460-3-60
Fig. 3--48G8048-060 and 48GX042-060 Unit Dimensions
....... , ,OO/ i? L[4iR) " i ...........
CONTROLEN/RY
[.8 1 V I
FRONTVIEW RIGHTSIDEVIEW
UNIT WEIGNT
Ib kg
415 1886 450 2045 382 1733
421 1910 468 2123
UNIT HEIGHT IN. (MM)
"A"
38.98 (990.2)
38.98 (990.2)
38.98 (990.2)
38.98 (990.2)
42.98 (1091.1)
23.0 (584.2)
21.5 (546.1)
23.5 (596.9)
CENTER OF GRAVITY
X 22 (5585) 22 (5585)
IN.(MM}
Y Z
16 (406.4) 17 (432 0)
16 (406.4) 17 (4320) 163 (412.8) 166 (4216) 166 (422.1) 180 (4572)
163 (412.8) 176 (4470)
iA_
000056
RoofCurb for Small Cabinet
Note A: When uNt mounting screw is used,
retah3er bracket must also be used.
Roof Curb for Large Cabinet
Note A: When unit mounting screw is used,
retainer bracket must also be used.
R/A
-'-_- Gasket around_
\
\
Suppolt
\
Long
SL pport
iBXC}
UNiT S_ZE
48GS018o042 48GX024-036
48GS048o060 48GX042-060
NOTES:
1. Roof curb must be set up for unit beh_ginstalled
2. Seal strip must be applied, as required, to unit being installed.
3. Dimensions in ( ) are in millimeters
4. Roof curb is made of 16-gage steel.
5. Table lists only the dimensions, per part number, that have changed
6. Attach ductwork to curb (flanges of duct rest on curb)
7. InsuIated panels: 1-in. thick fiberglass 1 Ib density.
8. Dimensions are in inches
9. When unit mounting screw is used (see Note A), a retainer bracket must be used as well This bracket must also be used when required by code for hurricane or seismic conditions. This bracket is available through Micrometl.
-->
GROL ND MOL_T
The unit may be installed either on a slab or placed directly on the ground if local codes permit. Place the unit on level ground
prepared with gravel _br condensate discharge.
Step 3--FIELD FABRICATI= DUCTWORK Secure all ducts to roof curb and building strecture on vertical
discharge uriits Do t_nt connect duct_oHc to z_nit. For horizontal
ODS CATALOG NUMBER
CPRFCURB006A00 CPRFCURB007A00 CPRFCURB008A00
CPRFCURB009A00
Fig. 4--Roof Curb Dimensions
IN. {NM)
8 (203)
14 (356)
8 (203)
14 (356)
insulated deck pan
A
applications, unit is provided with flanges on d_e horizontal openings Installation of flexible duct connector is recommended to prevent tlansmission of vibration and/or noise to stl_acture. All ductwork should be secured to the flanges. Insulate and weather° proof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes
Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.
Gasket around
B
IN.(MM)
11(279)
11(279) 16 3/16 (411) 16 3/16 (411)
duct
outer edge \
\,
C
RN.(MM)
161/2 (419)
161/2 (419) 17 3/8 (441) 17 3/8 (441)
S/A
/\
D
IN. (t_M)
2G3/4 (730)
28-3/4 (730) 40-1/4 (1022) 40-1/4 (1022)
C00076
Y
4 x 3
CORNER #
1 47.3 53.2 53.2 59.7 675 789 85.5 55.1 2 44.8 50.4 50.4 56.5 639 747 81.0 52.2 3 77.2 86.8 86.8 97.3 1101 128.7 1395 89.9
4 79.7 89.6 89.6 106.5 1136 132.8 1440 92.8
TOTAL WEIGHT 249 280 280 320 355 415 450 290
018 024 030 036 042 048 060 024
48GS
Fig. 8--48GS and 48GX Unit Corner We{ghts
C00070
48G×
030 036 042 048 060
595 61.0 72.6 800 88.9 563 57.8 68.8 758 84.2 970 99.5 1184 130.5 145.1
1002 102.7 1222 134.7 149.8
313 321 382 421 468
DIJCTS
2 F_
(50.8mn
EVAR COND.
COIL COIL
C99014
Fig. 6--Slab Mounting Details
HANDHOLD
/
J
C99067
Fig. 7A--Threading BoR for RiggBng
If a plemma return is used o,1 a vertical unit, the return should be
ducted through the roof'deck to comply with applicable i_re codex
A n_inimum clearance is not required around ductwork_ Cabinet return=air static shall not exceed -25 in. wg.
SEAL STRIP MI _ST BE _N
PLAOE
BASEPAN SLOT (BELOW RIGGtNG HOLDS} BEFORE RIGGING
0t8 024
030 036 042 048
050
024 030 036 042
048 050
MAX,MUM WE,GNT [ A [ B
tb kg in. mm in. mm
271 302
302 342 377 437
472
312 335 343 404
443 490
UNIT 48G8
123.2 20.0 508.0 14.0 355.6
137.3 22.5 571.5 13.0 330.2
137.8 21.5 546.1 13.75 349.3
155.1 22.5 571.5 14.0 355.6
171.4 21.5 546.1 13.5 342.9
198.6 22.0 558.5 17.0 432.0
214.5 22.0 558.5 17.0 432.0 UNIT 48GX
142 22.0 558.5 14.50 368.3 152 22.0 558.5 15.30 388.6 156 22.0 558.5 15.30 388.6 183 23.0 584.2 16.3 414.0
201 21.5 546.1 16.3 414.0 222 23.5 596.9 16.3 414.3
SRZE
PLACE BEFORE PLACING _JN_T ON RO©F CURB
C99015
Fig. 7B--Suggested Rigging
Step 4--PROVIDE CLEARANCES
The required minimum operating and service clearances are shm_n in Fig 2 and 3 Adequate combustion, ventilation and condmlser air must be provided in accordance with section 53, Air fbr
Table 1--Physical Data--UnR 48GS
UNIT SBZE 48GS
NOMINAL CAPACBTY (ton) OPERATING WEIGHT (_b.)
COMPRESSORS
Quantity
REFRmGERANT (R-22)
Quantity (_b.)
REFRIGERANT METERING DEVICE
Orifice ID (in.)
CONDENSER CORL
Rows...Finslin.
Face Area (sq ft)
CONDENSER FAN
NominN Cfm Diameter (in.)
Motor Hp (Rpm)
EVAPORATOR COBL
Rows...Fins/in.
Face Area (sq ft)
EVAPORATOR BLOWER
Nomina_ Airflow (Cfm)
Size ({n.)
Notor BP (Rpm}
FURNACE SECTION*
Burner Orifice No. (Qty...Drill Size)
Natural Gas
Burner Orifice No. (Qty...Drilt Size)
Propane Gas
RETURN-ABR FILTERS (in.)?
Throwaway
* Based on altitude of 0 to 2000 ft
? Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300
fi/minute for throwaway type or 450 if/minute for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg
018040 024040
2
249 280
024060
2
280
030040
280
030080 036060
3
280 320
038080
3
320
042060
355
042090
355
Reciprocating
1
AcutroF M Device
.034 I .034 .034 .032 .034 .034
1 17 [ 1._17 1_17 1._17 1_.17 1._17
6 I n 9.1 9.1 10.9 9.1 9.1
2000 1
1/8 (825) 1
2...15 I 2...I5 2...15 3...15 4...15 4...15 " _ ' 3.1 3.1 3.1 3.1 3.1.J _ ,
600 I 800 1000 1200 1400 1400
10x10 I 10x10 10x10 11x10 11x10 11x10
1/4 (87511 1/4 (I075) 1/4 (1075) 1/2 (1075) 3/4 (1075) 3/4 (1075)
.O34
u
1...17
9.1
u
2400
22
1/8 (825)
u
2...15
3.1
u
8OO
10 x 10
1/4 (1075)
u
2400
22
1/8 (825)
2400
22
1/8 (825)
2...45 I 2...45 2...38 2...45 3...38 2...38 3...38
2...50 I 2...50 2...46 2...50 3...46 2...46 3...46
u
20x20 I 20x20 20X20 20x20 20X24 20x24 20x24
.034 .032
1...17 1...17
9.1 10.9
2400 3000
22 22
1/8 (825) ¼ (1100)
2...15 3...15
3.1 3.1
1000 1200
10 x 10 11 x 10
lg (1075) 1/2 (I075)
2...38 2...38
2...46 2...46
20 X 20 20 X 24
3000
22
¼ (1100)
3000
22
¼ (1100)
3000
22
¼(1100)
(ombustion and Ventilation, of the National Fuel Gas <ode ANSI (American National Standards Institute) Z2231 or applicable
provisions of local building code In Canada, _bllow sections 7.2,
7.3, or 7.4 or CaniCGA. (Canadian Gas Association) B149 Installation Codes or applicable provisions of local building code.
Do not restrict condenser airflow. An air restriction at either the outdoor-air inlet or the £m discharge can be detrimental to
compressor tiff.
The condenser £m pulls air through the condenser coil and discharges it through the top cover Be sure that the fan discharge
does not recirculate to the condenser coil Do not locate the unit in either a comer or under an overhead obstruction. The minin-mm
clearance under a pmlial overhang (such as a nomml house overhang) is 48-im above the unit top. The nmximnm horizontal extension of a partial overhang must not exceed 48-in_
Do not place the unit where water, ice, or snow flora an overhang or roof will damage or flood the unit. Do not install the unit on carpeting, tile, or other combustible materials. The unit nmy be installed on wood flooring or on (;lass A, B, or ( roof covering
materials.
Step 5--RIG AND PLACE UNW
When installing the unit on a rooftop, be sure the roof will support the additional _eight
Use spreader bars or crate top when rigging the uniL The units
must be rigged for lifting (See Fig 6). Refer to Table 1 and 2 for
operating weight. L'xe e:v::'eme ca_ltio_v to prea,e_vt damage whe_
mu_ing the _mit. Unit m_¢stremain in an upH@tpo,sition dHring a//
riggi<g a_d mo_,i_tg operaff(ms.The unit must be level within 14" for proper condensate drainage; therefore, the ground°level pad or accessory roof curb must be level before setting the unit in place. When a field°fi_bricated support is used, be sure that the support is level and properly supports the unit. Lifting point should be directly over the center of gravity for the unit.
Step g--CONNECT CONDENSATE DRAIN NOTE: When installing condensate &ain connection be sure to
comply with local codes and restrictions. Models 48GS and 48GX dispose of condensate water through a
3/4 in. NPT fitting which exits through the compressor access panel (See Fig. 2 and 3 for location).
Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground- level installations. Install a field°supplied condensate trap at end of condensate connection to ensure proper drainage Make sure that the outlet of the trap is at least 1 in. lower than the drain pan condensate connection to prevent the pan fl'om overflowing (See Fig 8) Prime the trap with water When using a gravel apron, make sure it slopes away fl'om the unit
If the installation requires draining the condensate water away from the unit, install a 2=ira trap at the condensate connection to ensure proper &ainage (See Fig. 8). Make sure that the outlet of the trap is at least 1 in. lower than the drainpan condensate connection. This prevents the pan tiom overflowing.
Prime the trap with water. Connect a &ain tube using a mininmna of 3/4-in. PVC or 3/4-in. copper pipe (all field=supplied) at the outlet end of the 2=ira trap. Do not undersize the robe. Pitch the
Table 1--Physical Data--Unit 48GS (Continued)
UNiT SIZE 48GS
NOMINAL CAPACITY (ton)
OPERATING WEIGHT (lb.)
COMPRESSORS
Quantity
REFRIGERANT {R=22)
Quantity (lb.)
REFRIGERANT METERING DEVICE
Orifice ID (in.)
CONDENSER COIL
Rows...Fins/im
Face Area {sq ft)
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Motor Hp (Rpm)
EVAPORATOR COIL
Rows...Finsiim
Face Area (sq ft)
EVAPORATOR BLOWER
Nominal Airflow (Cfm)
Size (in.)
Motor Bp (Rpm)
FURNACE SECTION*
Burner Orifice No. {Qty...DrSI Size)
Natural Gas
Burner Orifice No. {Qty...DrSI Size)
Propane Gas
RETURN-AIR FILTERS {in.)?
Throwaway
* Based on altitude of 0 to 2000 ft
1 Reqaired filter sizes shown are based on the larger of the AR[ (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300
ft/minate for throwaway type or 450 if/minute for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in wg
048090 048115 060 t 18 060130
4 4 5 5
415 415 450 450
048130 0$0090
4 5
415 450
Scroll Reciprocating
1 1
6.0 6.0 8.0 8.0
6.0 8.0 Acutrol Device
.032 .032 .030 .030
1._17 1._17 2._17 2._17
12.3 12.3 12.3 12.3
3600 3600 3600 3600
22 22 22 22
'/_ (1100) 1/_(1100) '/_ (1100) '/_ (1100)
3...15 3...15 4._15 4...15
4.7 4.7 4.7 4.7
1600 1600 2000 2000
11X10 11X 10 11X10 11X10
3/4 (1075) 3/4 (1075) 1.0 (1075) 1.0 (1075)
3._38 3...33 3_.33 3_.31
3...46 3...42 3...42 3...41
24 X 30 24 X 30 24 X 30 24 X 30
.032 .030
1...17 2...17
12.3 12.3
3600 3600
22 22
1/_(1100) '/_ (1100)
3...15 4._15
4.7 4.7
1600 2000
11 X 10 11 X 10
3/4 (1075) 1.0 (I075)
3...31 3...38
3...41 3...46
24 X 30 24 X 30
drain robe downward at a slope of at least 1-in. %r every 10 ft of
horizontal run, Be sure to check the drain robe for leaks,
TRAP OUTLET
1" min.
2" rain.
C00009
Fig. 8--Condensate Trap
Step 7--INSTALL FLUE HOOD The flue hood assembly is shipped screwed to the coil panel in the
indoor blower compartment Remove the service access panel to locate the assembly (See Fig. 3i).
NOTE: Dedicated low NO x models MUST be installed in Call= fomia Air Quality Management Districts where a Low NO× rote
exists,
These models meet the California maximmn oxides of nitrogen (NOx) emissions requirements of 40 nanogramsdoule or less as shipped from the fhctory,
NOTE: Low NO x requirements apply only to natural gas instal- lations,
1
The venting system is designed to ensure proper venting. The flue hood assembly must be installed as indicated in this
section of the unit installation insm/ctions,
Install the flue hood as fbllows:
1, This installation must confot_n with local building codes and
with the National Fuel Gas (?ode (NFGC), ANSI Z223 1 (in ( anada., CANiCGA B 149,1, and B 149 2) or NFPA (National Fire Protection Association) latest revision Refer to Provin= cial and local plumbing or wastewater codes and other applicable local codes,
2, Remove flue hood from shipping location (inside the blower
compartment) Place vent cap assembly over flue panel, Orient screw holes in vent cap with holes in the flue panel
3, Secure flue hood to flue panel by inserting a single screw on
the right side and the tet_ side of the hood.
Step 8--INSTALL GAS PIPING
)"he gas supply pipe enters the unit through the access hole provided, The gas connection to the unit is made to the 1/2=in, FPT gas inlet on the manual shutoff or gas valve.
Install a gas supply line that runs to the heating section. Refer to
Table 3 and the NFGC for gas pipe sizing. Do _ot zlse cast-iros_
pipe. It is recommended that a black iron pipe is used. Check the
local utility for recommendations concerning existing lines. Size gas supply piping for 0,5 in, wg maximum pressure drop, _\2_*er _¢se pipe smaHe/' than the ].lL_:in+ FflY gax m/et up tile zmit ,?aX
ICt]1'C.
For natural gas applications, the gas pressure at unit gas connection must not be less than 4.0 in. wg or greater than 13 in. wg while the
TaNe 2--Physicam Data--Unit 48GX
UNiT BBZE 48GX 024040 024000 030040 030000 030060 036090 042060 042090
NOMINAL CAPACITY (ton) 2 2 2"½ 2_½ 3 3 OPERATING WEIGHT (lb.) 290 290 313 313 321 321 382 382
COMPRESSORS Scroll
Quantity 1
REFRmGERANT (R-22) 3.7 3.7 4.4 4.4 5.2 5.2 6.4 6.4
Quantity (_b.)
RBFRBGERANT METERBNG DEVICE
Orifice ID (in.}
CONDENSER COBL
Rows...Fins/in.
Face Area (sq ft}
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Motor Bp (Rpm) 1/8 (825) 1/8 (825) 1/8 (825) 1/8 (825) 1/8 (825) 1/8 (825) 1/8 (825) 1/8 (825)
EVAPORATOR COIL
Rows...Fins/in.
Face Area (sq ft}
EVAPORATOR BLOWER
Nominal Airflow (Cfm) 10X10 10X10 10X10 10X10 11X10 11X10 11X10 11X10
Size (in.)
Motor Hp {Rpm) 1/4 (1075) 1/4 (1075) 1/4 (1075) 1/4 (1075) 1/2 (1075) 1/2 (1075) 3/4 (1075) 3/4 (1075)
FURNACE SECTION*
Burner Orifice No. (Qty...DriH Size) 2...44 2_.38 2_.44 2...38 2...38 3...38 2...38 3_.38 Burner Orifice No. (Qty...DriH Size)
R_:TURN-ABR FBLTERS (Jn.)t 20 X 20 20 X 20 20 X 20 20 X 20 20 X 24 20 X 24 24 X 30 24 X 30
* Based on altitude of Oto 2000 ft
? Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300
if/minute for high-capacity type Air filter pressure drop for non-standard fitters must not exceed 008 in wg.
NaturN Gas
Propane Gas
Throwaway
.034 .034 .030 .030 .032 .032 .034 .034
1._17 1._17 1_.17 1...17 2...I7 2...17 2...17 2._17
10.8 10.8 12.7 12.7 9.1 9.1 12.3 12.3
2350 2350 2350 2350 2350 2350 3300 3300
22 22 22 22 22 22 22 22
3...15 3_.15 3._15 3._15 3._15 3...15 3_.15 3_.15
3.1 3.1 3.1 3.1 3.7 3.7 4.7 4.7
800 800 1000 1000 1200 1200 1400 1400
2...50 2...46 2...50 2...46 2...46 3...46 2...46 3...46
unit is operating. For propane applications, the gas pressure must
not be less than 7.0 in wg oi" greater than 13 in wg at the unit connection
An 1/8-in. NPT plugged tapping, accessible fbr test gage conneco tiom must be installed immediately upstream of the gas supply connection to the gas valve.
When installing the gas supply line, obsel_'e local codes pertaining to gas pipe installations. Ref)r to the NFGC ANSI Z223J-1988
NFPA latest edition (in Canada, (ANiCGA B 14% 1, (2)-M86). In
the absence of local building codes, adhere to the fbltowing
pertinent recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe 1/4 in. in ever?" 15 ft to prevent traps. Grade all horizontal runs downward to risers. Use risers to connect to heating section
and to meter.
2. Protect all segments of piping system against physical and thermal damage. Support all piping with appropriate straps, hangers, etc. Use a mininmm of one hanger eve N- 6 ft. For pipe sizes larger d_an 1/2 in., fbltow recommendations of
national codes.
3. Apply joint compound (pipe dope) sparingly and only to male threads of joint when making pipe connections. Use only pipe
dope that is resistant to action of liquefied petroleum gases as specified by local and/or national codes. :\;ever zz.se 7;e_7ot_
tope.
4. Install sediment trap in riser leading to heating section (See Fig. 9). This &ip leg Nnctions as a trap fbr dirt and
condensate.
5. Install an accessible, external, manual main shutoff valve in
gas supply pipe within 6 ff of heating section.
6. Install groundojoint union close to heating section between unit manual shutoff and external manual main shut-off valve.
? Pressure-test all gas piping in accordance witla local and
national plumbing and gas codes before connecting piping to unit,
NOTI::: Pressure test the gas supply system qfter the gas supply piping is connected to the gas valve. The supply piping must be disconnected f?om the gas valve during the testing of the piping systems when test pressure is in excess of 0.5 psig. Pressure test the gas supply piping system at pressures equal to or less than 0.5 psig. The unit heating section must be isolated fi'om the gas piping system by closing the external main manual shutoff valve and slightly opening the ground-joint union.
Unstable operation may occur when the gas valve and manifbld assembly are forced out of position while connect- ing improperlyorouted rigid gas piping to the gas valve. Use a baclcup wrench when making connection to avoid stlain on, or distortion of, the gas contIol piping.
If a flexible conductor is required or allowed by the authority having jurisdictiom black iron pipe shall be installed at the gas valve and shall extend a nlinirnurn of 2 in. outside the unit
casing.
Table 2--Physical Data--Unit 48GX (Continued)
UNiT BBZE 48G× 048090 048115 048130 0g0090 060115 060130
NOMINAL CAPACBTY (ton) 4 4 4 5 5 5
OPERATING WEIGHT (_b.) 421 421 421 468 468 468
COMPRESSORS Scrolt
Quantity 1
REFRmGERANT {R=22}
REFRIGERANT METERING OEVICE Acutrol Device
Orifice ID (in.) .034 .034 .034 .032 .032 .032
CONDENSER CORL
Rows...Finstin.
Face Area {sq ft}
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Motor Hp (Rpm) _A(1100) (1100) (1100) _A(1100) _A (1100) _A(1100)
EVAPORATOR COIL
Rows...Finslin.
Face Area {sq ft}
EVAPORATOR BLOWER
Nomina_ Airflow (Cfm} 11 X 10 11 X 10 11 X 10 11 X 10 11 X 10 11 X 10
Size ({n.} 3/4 (1075) 3/4 (1075) 3/4 (1075) 1.0 (I075) 1.0 (1075) 1.0 (1075)
Motor Bp (Rpm)
FURNACE SECTION*
Burner Orifice No. (Qty...DriH Size) 3._38 3...33 3...31 3...38 3_.33 3_.31 Burner Orifice No. (Qty...Drill Size)
RETURN-AIR FILTERS (in.)'( 24 X 30 24 X 30 24 X 30 24 X 30 24 X 30 24 X 30
Based on altitude of 0 to 2000 ft
1 Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velodty of 300
ft/minute for high-capacity type Air filter pressure drop for non-standard filters must not exceed 008 in. wg.
Natural Gas
Propane Gas
Throwaway
2...17 2._17 2._17 2...17 2_.17 2._17
12.3 12.3 12.3 16.4 16.4 16.4
3300 3300 3300 3300 3300 3300
22 22 22 22 22 22
4...15 4...15 4...15 4...15 4...15 4...15
4.7 4.7 4.7 4.7 4.7 4.7
1600 1600 1600 1750 1750 1750
3...46 3...42 3...41 3...46 3...42 3...41
Table 3--Maximum Gas Flow Capacity*
NOMINAL
IRON PIPE,
SIZE
(IN.}
V2
%
1
11/4
Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 05-in wg (based on a 0.60 specific gravity gas). Refer to Tabte C-4, National
Fire Protection Association NFPA 54. 1 This length includes an ordinary number of fittings
Never use a match or other open flame when checking %r gas
leaks. Never purge gas line into combustion charuber. Failure to follow this warning could result in an explosion causing serious injury or death.
8. Check %r gas leaks at the field-installed and factow-installed gas lines after all piping connections have been completed
Use soap-and-water solution (or method specified by local
codes and/or regulations)
Step g--INSTALL DUCT CONNECTmONS The unit has duct flanges on the supply- and return-air openings on
the side and bottom o_["the unit, For downshot applications, the
ductwork connects to the roof cm'b (See Fig 2 and 3 for connections sizes and locations)
iNTERNAL LENGTH OF PIPE, FT¢ DIAMETER
(BN.} 10 20 30 40 50 60 70 80 90 100 125 150 175 200 .622 175 120 97 82 73 66 61 57 53 50 44 40 -- --
.624 360 250 200 170 151 138 125 118 110 103 93 84 77 72
1.049 660 465 375 320 285 260 240 220 205 195 175 160 145 135
1.380 1400 950 770 600 580 530 490 460 430 400 360 325 300 280
1.610 2100 1460 1180 990 900 810 750 690 650 620 550 500 460 430
l
CONFIGURING UNITS FOR DOV_q',rFLOW (VERTI(AL) DIS- ( HARGE
Be%re per%rming service or maintenance operations on the system, mrn off main power to unit. Electrical shock could cause serious injury or death.
1. Open all electrical disconnects be%re starting any service
work_
2. Remove return duct cover located on duct panel by breaking connecting tabs with screw&iver and a hammer (See Fig. 10A
& 10B).
3. To remove supply duct cover, break flout and right side connecting tabs with a screwdriver and a hammer. Push touver down to break rear and left side tabs (See Fig. 10A & 10B)
10
OUT
IN
--:u
TEE
I
3"MIN
__!_1
_.._ NIPPLE
CAP
C99020
Fig. 9--Sediment Trap
o
o
/
SUPPLY RETURN DUCT DUCT OPENING OPENING
/
C99011
Fig. 10A SupNy and Return Duct Opening
4. If unit duct_xork is to be attached to x ertical opening flanges on the unit composite base (jackstand applications only), do so
at this time,
Collect ALL screws that v, ere removed. Do not lea_e screws on rooftop as pem_anent damage to the roof may occur
5. It is recommended that the unit base insulation around the
perimeter of the vertical return°air opening be secured to the unit base with aluminum tape. Applicable local codes may require aluminum tape to prevent exposed fiberglass
6. Cover both horizontal duct openings with the duct covers fl'om
the accessory duct cover kit. Ensure opening is air- and watertight.
7. After completing unit conversion, perform all safety checks and power up unit.
NOTE: The design and installation of the duct system must be in accordance with the standards of the NFPA fbr installation of
nonresidence-type air conditioning and ventilating systems, NFPA 90A or residence-type, NFPA 90B; and/or local codes and
ordinances.
DUCT COVERS REMOVED
C99012
Fig. lOB--Vertical Duct Cover Removed
Adhere to the following criteria when selecting, sizing_ and installing the duct system:
1 Lnits are shipped for horizontal duct installation (by removing
&ct covers)
2 Select and size ductwork, supply-air registers, and return-air
grilles according to American Society of Heating, Refiigera- tion and Air (onditioning Engineers (ASHRAE) recommen=
dations
3 Lse flexible transition between rigid dnctwork and unit to
prevent transmission of" vibration. The transition may be screwed or bolted to duct ['langes. Lse suitable gaskets to
ensure weathertight and airtight seal.
4 All units must have field-supplied filters or accessory filter
rack installed in the return-air side of the unit. Recommended sizes fbr filters are shown in Tables 1 and 2.
5. Size all dnctwork for naaximnm required airflow (either heating or cooling) for unit being installed. Avoid abrupt duct size increases or decreases or perfimnance may be affected.
6. Adequately insulate and weatherproof all ductwork located outdoors. Insulate ducts passing through unconditioned space, and use vapor barrier in accordance with latest issue of Sheet Metal and Air Conditioning Contractors National Association (SMA(NA) and Air Conditioning Contractors of America (AC(A) mininmm installation standards for heating and air conditioning systems. Secure all dtlcts to building structure.
7. Flash, weatherproof, and vibration-isolate all openings in building structure in accordance with local codes and good building practices.
11
Loading...
+ 25 hidden pages