Carrier 48EN, 48EH Installation, Operation And Maintenance Instructions

Page 1
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
48EN/EH
Nominal cooling capacity 58,9 - 135,5 kW Nominal heating capacity 62,2 - 143,4 kW
50 Hz
Packaged rooftop cooling only / heat pumps
Original document
Page 2
Packaged rooftop units with integrated gas burner
2
Contents
1. Introduction .......................................................................................................................................................................................................3
2. Operation limits .................................................................................................................................................................................................3
3. Technical characteristics ...................................................................................................................................................................................4
4. General recommendations ................................................................................................................................................................................5
Delivery of the unit ............................................................................................................................................................................................5
Unit identifi cation ...............................................................................................................................................................................................5
Documentation provided ...................................................................................................................................................................................5
Location .............................................................................................................................................................................................................5
Installation .........................................................................................................................................................................................................5
Unit maintenance ..............................................................................................................................................................................................5
Safety advice .....................................................................................................................................................................................................5
Refrigerant safety ..............................................................................................................................................................................................6
Burner safety .....................................................................................................................................................................................................6
5. Transport ...........................................................................................................................................................................................................6
Gravity centre ....................................................................................................................................................................................................7
6. Location and assembling ..................................................................................................................................................................................7
Location designation .........................................................................................................................................................................................7
Sound Level ......................................................................................................................................................................................................7
Anchorage for antivibrators ...............................................................................................................................................................................8
Minimum free space for commissioning and maintenance operations .............................................................................................................8
7. Gas Burner ........................................................................................................................................................................................................9
Operating principle ............................................................................................................................................................................................9
Control of the gas burner ................................................................................................................................................................................10
8. Safety elements ..............................................................................................................................................................................................11
Safety devices in the gas burner .....................................................................................................................................................................11
Safety devices in the 48EN/EH unit ................................................................................................................................................................12
9. Checking before commissioning .....................................................................................................................................................................13
Electrical Connections .....................................................................................................................................................................................13
Gas Burner ......................................................................................................................................................................................................13
Air ducts connections ......................................................................................................................................................................................15
Checks in the axial fans ...................................................................................................................................................................................15
Checks in the centrifugal fans .........................................................................................................................................................................15
Condensate drain connection .........................................................................................................................................................................16
10. Starting the unit ...............................................................................................................................................................................................17
Checks prior to commissioning .......................................................................................................................................................................17
Operational checks .........................................................................................................................................................................................17
Possible problems at commissioning ..............................................................................................................................................................17
11. Options ............................................................................................................................................................................................................18
Pre-assembly frames (optional) ......................................................................................................................................................................18
Outdoor coil protection grille ...........................................................................................................................................................................18
Filters ..............................................................................................................................................................................................................18
Stop-drop ........................................................................................................................................................................................................18
12. Maintenance ....................................................................................................................................................................................................19
13. Control and analysis of breakdowns................................................................................................................................................................22
Page 3
Packaged rooftop units with integrated gas burner
3
1. INTRODUCTION
2. OPERATION LIMITS
The 48EN/EH cooling units and heat pumps are autonomous air-air units with a compact monoblock, horizontal rooftop design with a built in natural or propane gas burner (in accordance with the gas Directive 90/396 EEC).
They are equipped with centrifugal and axial fans, air coils, hermetic scroll compressors and electronic control with microprocessor, components optimised for the R-410A refrigerant.
These units have been designed for the air conditioning of large surface areas used for business or industry in areas with particularly low outdoor temperatures in winter.
A vast number of options meet numerous operating demands thus enabling quick installation and reliable operation.
Space 48EN Series
Autonomous air-air cooling units with a compact horizontal rooftop design with a built in gas burner.
Space 48EH Series
Autonomous reversible air-air heat pump units with a compact horizontal rooftop design with a built in gas burner.
After manufacturing, all units are charged with refrigerant and are tested at the factory, verifying the correct operation of all their components.
In this brochure are described the actions and safety norms for a correct unit handling.
With a condensation pressure control operating down to -10ºC.With high powered axial fan operating up to 52ºC. With outdoor temperatures below -15ºC it is compulsory to select the anti-freeze
protection option for the electric panel.
Inlet air conditions Cooling Heating
Indoor coil heat pump
Minimum 14ºC WB 10ºC
Maximum 22ºC WB 27ºC
Outdoor coil heat pump
Minimum
12ºC
-10ºC WB
Maximum
48ºC
15ºC WB
Gas Burner
Minimum --
-30ºC
Page 4
Packaged rooftop units with integrated gas burner
4
3. TECHNICAL CHARACTERISTICS
Cooling capacity calculated in accordance with the EN-14511 standard given for indoor temperature conditions 27ºC, 50% RH and 35ºC outdoor temperature. Heating capacity calculated in accordance with the EN-14511 standard given for indoor temperature conditions 20ºC and 6ºC WB outdoor temperature.Total power input by compressor and motorised fans under nominal conditions, calculated in accordance with the EN-14511 standard.Climatic warming potential of a kilogram of fl uorinated greenhouse gas in relation to a kilogram of carbon dioxide over a period of 100 years.
48EN/EH 241 321 361 242 322 362 420 485 540 600
Cooling capacities
Cooling capacity (kW)
58,9 72,1 82,7 60,3 73,6 84,8 101,7 110,3 123,3 135,5
Power input
(kW)
21,4 28,1 32,7 21,1 27,5 32,0 33,0 37,0 42,8 49,8
EER performance 2,7 2,6 2,5 2,9 2,7 2,6 3,1 3,0 2,9 2,7
Heating capacities
Heating capacity (kW)
62,2 76,7 92,3 62,2 76,1 91,6 105,5 115,5 129,0 143,4
Power input
(kW)
18,2 21,8 26,6 17,4 20,9 25,5 31,2 35,3 39,1 43,6
COP performance 3,4 3,5 3,5 3,6 3,6 3,6 3,4 3,3 3,3 3,3
Outdoor circuit fan
Nominal air fl ow (m3/h) 30.000 42.000 Available static pressure (mm.w.c) 4 Type Axial Number 24 Diameter (mm) 2 x 800 2 x 630 + 2 x 800 Output (kW) 2 x 2,0 / 1,3 2 x 0,7 / 0,4 + 2 x 2,0 / 1,3
Speed (r.p.m.) 895 / 685
875 / 650 895 / 685
Outlet fan indoor circuit
Nominal air fl ow (m3/h) 12.000 14.300 15.900 12.000 14.300 15.900 18.000 18.200 20.400 24.000 Available static pressure (mm.w.c) 12 12 12 12 12 12 12 12 15 15 Type Centrifugal Number / no. turbines 2 / 2 Motor output (kW) 2 x 1,5 2 x 2,2 2 x 3 2 x 1,1 2 x 2,2 2 x 2,2 2 x 2,2 2 x 2,2 2 x 3 2 x 4 Power input (kW) 2 x 1,13 2 x 1,67 2 x 2,11 2 x 0,93 2 x 1,35 2 x 1,68 2 x 1,70 2 x 1,74 2 x 2,40 2 x 3,42 Speed (r.p.m.) 847 939 995 762 829 870 708 713 790 860
Compressor
Type Scroll Number of compressors 2 Number of circuits 2 Number stages 2 Oil type Copeland 3MAF 32cST , Danfoss POE 160SZ, ICI Emkarate RL 32CF, Mobil EAL Artic 22CC Volume of oil (l) 2 x 3,3 2 x 3,3 2 x 6,2 2 x 3,3 2 x 3,3 2 x 6,2 2 x 6,2 2 x 6,2 2 x 6,2 2 x 6,2
Gas burner
Gas type Natural or propane Standard model PCH-72 PCH-200 Max. heating capacity (kW) 73 197 Pressure drop (mm.w.c) 11,4 16,2 20,0 5,7 8,1 10,0 12,8 13,1 16,5 22,8
Electrical features
Electrical power supply 400 V / III ph / 50 Hz (±10%) Power supply 3 Wires + Ground
Maximum absorbed current
Compressor(s) (A) 58,0 70,0 72,0 58,0 70,0 72,0 87,0 102,0 116,0 130,0 Outdoor fan(s) (A) 8,6 8,6 8,6 8,6 8,6 8,6 11,2 11,2 11,2 11,2 Indoor fan (A) 7,2 10,0 13,8 5,4 10,0 10,0 10,0 10,0 13,8 18,0 Control (A) 2,0 2,0 2,0 2,0 2,0 2,0 2,0 2,0 2,0 2,0 Total (A) 75,8 90,6 96,4 74,0 90,6 92,6 110,2 125,2 143,0 161,2
Refrigerant
Type R-410A Global warming potential (GWP)
2.088
Charge (kg) 18,4 19,8 27,0 18,8 20,1 27,4 42,5 42,4 51,0 51,0 Environment impact (tCO2eq) 38,4 41,3 56,4 39,3 42,0 57,2 88,7 88,5 106,5 106,5
Dimensions
Length (mm) 3.326 3.926 4.816 Width (mm) 2.205 2.205 2.205 Height (mm) 2.095 2.095 2.095
Weight
(kg) 1.497 1.581 1.717 1.723 1.806 1.942 2.360 2.402 2.459 2.512
Condensates output Ø
1 1/4” adaptor
Page 5
Packaged rooftop units with integrated gas burner
5
Unit identifi cation
All units bear, legibly and indelibly, a data plate located in a prime space, with the following data:
4. GENERAL RECOMMENDATIONS
For the gas burner the unit includes a second nameplate with its features:
Note: The serial number must be used in all communications regarding the unit.
Delivery of the unit
Check the condition of the equipment upon delivery. Check that the details on the label, the packing and the rating plate match the order. If equipment has been damaged, or there is a shortfall in delivery, notify accordingly.
Documentation provided
The following documentation is provided with the 48EN/EH unit:
- This brochure for the installation, operation and maintenance.
- Electrical diagram: this diagram must be consulted for the electrical connections of the 48EN/EH unit.
- CARRIERrtc electronic control brochure.
- Communications brochure for the CARRIERrtc electronic control (in case the 48EN/EH unit is connected to a pLAN network or to a BMS monitoring system).
- Manufacturer's installation and maintenance brochure (APENGROUP) for the burners in the PCH series.
- CE marking certifi cate.
- CARRIER warranty document.
Unit maintenance
The unit is to be inspected annually by a qualifi ed technician. He will check all the gas and electrical connections and make sure that the burner motor and safety devices and control systems are in good working order.
Attention: In compliance with the requirements of the Gas Directive 90/396 EEC it is strictly prohibited to alter the burner or the electronic control unit.
Installation
The 48EN/EH units with built-in gas burner are to be installed in accordance with the applicable gas unit regulations and norms in force in the country of use.
Check that the supply, type, pressure and fl ow rate of the gas are compatible with the specifi cations on the burner rating plate. For safety and maintenance purposes, ensure that the aforementioned specifi cations are observed.
Safety advice
T o avoid accidents during installation, commissioning or maintenance, it is required to take into consideration the units specifications: refrigerated circuits under pressure, refrigerant presence, voltage presence and implantation.
Because of all of this, only qualifi ed and experienced personnel can perform maintenance tasks or unit repairs.
It is required to follow the recommendations and instructions in the maintenance brochures, the labels, and the specifi c instructions. It is necessary to comply with the norms and regulations in effect.
The compressor surfaces, the lines and hot components on the gas burner can reach temperatures above 100ºC, causing physical burns. In the same fashion, under certain conditions these surfaces can reach very cold temperatures that can cause freezing risks.
Use safety gloves and gloves whilst working. Be careful with sharp parts or elements in the unit.
V-220005
V-220004
Caution: Before intervening in the unit, verify that the main power to the unit is cut off. An electric shock can cause personal damage.
Note: In order to recycle these units follow the stipulations of directives (EC) No. 96/2002 and No. 108/2003 regarding
electrical and electronic equipment and the management of the resulting waste.
Location
These units are prepared for rooftop installation. Make sure they are not fi tted near areas where there is a risk of fi re (fl ammable dust) or explosion, or in areas where aggressive products are kept, e.g. trichloroethylene, perchloric acid, etc.
An.Year
CARRIER SCS
Route de Thil 01122 Montluel–France Tél: 33(0)4 72 25 21 21
Ref. Produit
\Item Nb
r
Designation\Description
Refrigerant kW Absorbee\
Input
Poids\
Weight
Refrigerant kg Tension\Voltage Temperature Maxi C
BP Mini PSM
\MOP
Intensité\Current A
IP
HP Maxi PSM
\MOP
Int. Kit Elect.
No CE
0056
No Serie\Serial Nb
r
No Produit
Contains fluorinated greenhouse gases regulated by the Kyoto protocol
UTC BIS
P.I. Llanos de Jarata 14550 Montilla - SPAIN Phone: 34 957 65 23 11
Made in Spain
COUNTRY
COUNTRY
m3/h
m3/h
GAS INFORMATION
GAS INFORMATION
GAS CONSUMMATION
GAS CONSUMMATION
GAS
GAS
GAS CATEGORY
GAS CATEGORY
PIN
PIN
GAS PRESSURE
GAS PRESSURE
TYPE
TYPE
mbar
mbar
CE certification number of unit with gas burner
WO
WO
Page 6
Packaged rooftop units with integrated gas burner
6
5. TRANSPORT
The unit must be handled with care to avoid transport damage. Thus we recommend:
- For transport in a container, one must be selected that has an easy load and unload to the installation location.
- Do not dispose of the pallet or the packaging materials until the unit is in its fi nal location.
Note: the skis for closed container transport can be removed by
unscrewing them from the unit struts.
- The unit can be handled with a forklift truck, taking all necessary precautions to avoid sliding of the unit on the truck's fork.
- The unit must be lifted and fi xed with care and without inclination (maximum inclination 15º), since it could harm its operation. Please refer to the gravity centre coordinates of each model in accordance with the assembly.
- For the transport and lifting to the roof using a crane cloth slings with rings will be used, with the appropriate resistance, separated by a strut to avoid damaging the casing. These slings are attached to the grips on the strut.
Detail lifting grip
Ski for the container
Refrigerant leaks:
- Toxicity: According to ASHRAE 34, R-410A belongs to the A1/A1group with high safety both in the mix and also in the case of a leak.
- Although it is not toxic, in case of a leak to atmospheric pressure the liquid phase evaporates. The resulting vapours are heavier than air and can displace the technician local air. In case of an accidental discharge in a closed enclosure, fans must be used to eliminate said vapours.
- Although the R-410A is not fl ammable, when in contact with a fl ame or hot spot it can decompose thus producing fl uor hydric acid HF and fl uophosgene COF
2
which are highly toxic and corrosive.
- To detect leaks, an electronic leak detector, an ultraviolet lamp or soapy water must be used . Flame detectors do not help.
Note: Repair immediately any refrigerant leak, using recovery unit specifi c for R-410A that avoids a possible mixture of refrigerants and/or oils.
Refrigerant safety
A periodical check must be performed for refrigerant gas leaks as per Regulation (CE) Nº842/2006 over certain greenhouse effect fl uoride
gases.
R 410A
These units work with refrigerant gas
Components
R-32 R-125
Chemical formula CH2F2 CHF2CF3 Weight ratio 50% 50% Unitary global warming potential (GWP) 675 3.500 Global warming potential (GWP) 2.088
Natural or propane gas leaks in the burner:
- Do not operate electric switches or other objects which could cause sparks.
- Close the gas supply valve.
- Improve the ventilation if the burner is located in a closed area.
- Ensure that there is no one in the vicinity of the leak and request the intervention of site staff.
Burner safety
The gas burner has a built-in maximum safety system which cuts off the supply of gas to the burner should the fl ame go out. Ensure that no objects impair the supply of air to the burner.
Note: If the generator is not going to be used over a prolonged period the gas supply valve must be closed.
Grip
Attention: Check that the grips are perfectly screwed in before
attaching the slings.
- After the placing of the unit, it is recommended to remove the grips as they can be a hindrance for maintenance. Put them back in case of unit transport.
Page 7
Packaged rooftop units with integrated gas burner
7
48EN/EH Assembly
Centre of gravity (mm)
Weight
(kg)
XYZ
241
MO 1062 1310 830 1497 MS 1127 1355 832 1578 MA / MC 0 1193 1385 804 1705
321
MO 1062 1310 830 1581 MS 1127 1355 832 1662 MA / MC 0 1193 1385 804 1789
361
MO 1062 1310 830 1717 MS 1127 1355 832 1798 MA / MC 0 1193 1385 804 1925
242
MO 1100 1300 845 1723 MS 1165 1345 847 1805 MA / MC 0 1223 1386 776 1925
322
MO 1100 1300 845 1806 MS 1165 1345 847 1888 MA / MC 0 1223 1386 776 2008
362
MO 1100 1300 845 1942 MS 1165 1345 847 2024 MA / MC 0 1223 1386 776 2144
420
M0 1024 2300 794 2360 MS 1085 2353 804 2458 MA / MC 0 1186 2469 746 2724
485
M0 1024 2300 794 2402 MS 1085 2353 804 2500 MA / MC 0 1186 2469 746 2766
540
M0 1024 2300 794 2459 MS 1085 2353 804 2557 MA / MC 0 1186 2469 746 2823
600
M0 1024 2300 794 2512 MS 1085 2353 804 2610 MA / MC 0 1186 2469 746 2876
The unit weight includes the burner installed as standard which matches the
heaviest one amongst those available.
Location designation
Before moving the unit, make sure that all panels are fastened in place. Lift and lower with care.
When choosing the location, in any way the selected fashion, the following precautions have to be taken into consideration:
- It is mandatory to comply with norm EN 378-3 on Safety and Environmental Requirements. Part 3: "In situ" installation and protection to people.
- The area where the unit will be located must be perfectly accessible for cleaning and maintenance operations (check minimum free space for maintenance). Leave enough space for air circulation around the unit.
- Foresee appropriate damping devices throughout the installation to ensure that noise and vibration transmission is avoided (refer to the section "Anti-vibration Anchoring").
- Check that the structure can withstand the weight of the unit.
- Since the unit is designed to work outdoors, some specifi c installation norms must be followed:
• The unit will be located on the roof of the premises. If it is foreseen
that it will work more on heating than on cooling, it is preferable to direct the coil towards the sun. If little work on heating is foreseen, choose North direction.
• Avoid placing obstacles in the air outlet or return. No obstacle may
impede the air aspiration into the coils. Do not fi x the outdoor coil side in the predominant wind direction.
• Do not install the unit in a closed enclosure or in conditions that
originate air recirculation.
• The chosen location must not fl ood and must be above the average
height the snow reaches in that region.
• All models can be installed on the fl oor or on a brick frame or steel
profi le (see optional preassembly frames in chapter 11). In any case, check that the unit is perfectly level.
6. LOCATION AND ASSEMBLING
Sound Level
These units are designed to work with a low acoustic level. In any case, in the design of the installation the outdoor environment, the kind of building for the noise transmitted in the air and the solid elements for the vibration transmission must be taken into consideration for the acoustic radiation. If necessary , commission a study by an acoustic technician.
Sound power level
Note: The sound power spectrums can be consulted in the technical brochure for the 48EN/EH series.
Sound pressure level
Measurement conditions: in free fi eld, measured at a distance of 5 metres, directivity 2 and at 1.5 metres from the ground.
Note: The sound pressure level depends on the installation conditions and, as such, it only indicated as a guide. Values obtained according to the ISO 3744 standard.
48EN/EH 241 321 361 242 322 362 420 485 540 600
Total dB(A) 90 90 91 88 88 89 94 95 95 95
48EN/EH 241 321 361 242 322 362 420 485 540 600
Total dB(A) 63 63 64 61 61 62 67 67 67 67
Gravity centre
Z
X
Y
Page 8
Packaged rooftop units with integrated gas burner
8
Anchorage for antivibrators
When selecting antivibration mounts both the unit weight and reactions in the supports must be taken in account and are featured in the following table.
48EN/
EH
Assembly
A
(mm)B (mm)
Reactions in the supports (kg)
Weight
(kg)
R1 R2 R3 R4 R5 R6
241
MO 1545 2095 100 349 271 119 368 290 1497 MS 1545 2095 133 384 290 121 372 278 1578 MA / MC0 1545 2095 170 433 323 121 384 274 1705
321
MO 1545 2095 105 369 286 126 389 306 1581 MS 1545 2095 140 405 306 127 392 293 1662 MA / MC0 1545 2095 178 454 339 127 403 288 1789
361
MO 1545 2095 114 400 311 137 422 333 1717 MS 1545 2095 152 438 331 137 424 317 1798 MA / MC0 1545 2095 192 489 365 136 433 310 1925
242
MO 1845 2095 69 412 378 70 413 380 1723 MS 1845 2095 102 450 404 66 414 368 1805 MA / MC0 1845 2095 137 498 438 63 424 364 1925
322
MO 1845 2095 72 432 397 74 433 398 1806 MS 1845 2095 107 471 423 69 434 385 1888 MA / MC0 1845 2095 143 520 457 66 443 380 2008
362
MO 1845 2095 78 464 427 79 466 428 1942 MS 1845 2095 114 505 453 74 465 413 2024 MA / MC0 1845 2095 153 555 488 70 473 406 2144
420
M0 2290 2095 250 536 306 309 595 365 2360 MS 2290 2095 298 582 328 312 596 342 2458 MA / MC0 2290 2095 409 689 373 337 616 300 2724
485
M0 2290 2095 254 545 311 314 605 371 2402 MS 2290 2095 304 592 334 317 606 347 2500 MA / MC0 2290 2095 415 699 378 342 626 305 2766
540
M0 2290 2095 260 558 318 322 620 380 2459 MS 2290 2095 310 605 341 325 620 355 2557 MA / MC0 2290 2095 424 714 386 349 639 311 2823
600
M0 2290 2095 266 570 325 329 633 388 2512 MS 2290 2095 317 618 348 331 633 363 2610 MA / MC0 2290 2095 432 727 394 355 651 317 2876
A
M12
A
B
Minimum free space for commissioning and maintenance operations
1500 mm
1500
mm
1500 mm
1500 mm
Page 9
Packaged rooftop units with integrated gas burner
9
CO2 CONTROL
OFFSET CONTROL
CALIBRATED VENTURI
GAS INLET TO THE BURNER
PRESSURE COCK GAS INLET
models 150/200
CALIBRATED VENTURI
CO2 CONTROL
PRESSURE COCK GAS INLET
OFFSET CONTROL
GAS INLET TO THE BURNER
models 032/092
7. GAS BURNER
Flue
Air
Gas
EVP
EV2 EV1
Condensation drain
for mod.150/200 only
Operating principle
Connection / disconnection of the burner
When heating is required (A), the burner remote control starts the working cycle of the modulation board which activates the fl ame control device. This device starts up the burner combustion air fan (A), thus starting an air current in the combustion chamber for a preset period of time.
When this phase has been completed the ignition cycle begins: the electromagnetic valve EV1 opens at the same time as the EVP valve (B), supplying the pilot burner. When the device detects the pilot fl ame it will open the main gas valve EV2 (C) to supply the main burner.
The pilot and main burner will work together for a short period of time. After this, the modulation board will close the electromagnetic valve EVP (D) and disconnect the pilot burner.
The one electrode only guarantees the detection of the fl ame for the pilot and main burner.
pilot burner
Burner group
EVP
EV1
EV2
detection electrode
start-up
electrode
nozzle
Control device
On/off signal
Burner fan
EVP - pilot light flame
EV1 - 1st electromagnetic valve gas
EV2 - 2nd electromagnetic valve gas
ABC D E F
Operation of the air-gas premix
The air and the gas mix inside the vanes of the motor fan assembly. The air inlet is achieved via a calibrated Venturi pipe from which the gas is taken in.
The air/gas pressure ratio is 1:1 and can be adjusted by turning the offset screw in the gas valve. The burner is supplied with the offset set and the screw sealed.
The burner can also be regulated by adjusting the screw located above the Venturi which establishes the maximum air fl ow rate value and, as such, determines the carbon dioxide content in the condensates. This screw is factory-set and must not be touched, although it is not sealed thus allowing a changeover to another type of gas (before doing so this must be consulted).
The modulation board installed in the burner regulates the fan speed (in direct current) in accordance with the requirements of thermal capacity. The gas fl ow rate changes at the same time as the variation in the motor speed. The minimum and maximum values for the motor speed are stipulated on the plate and cannot be changed.
The ignition cycle connects the burner to half capacity (approx. 70% of its maximum thermal capacity). Two minutes after starting the burner reduces its capacity to the minimum and as from this moment starts to have modulating control (0-10Vdc) in accordance with the installation requirements.
Page 10
Packaged rooftop units with integrated gas burner
10
Control of the gas burner
T o establish the electric power supply of the unit (wire intake, conductor section and their calculations, protections, etc.), refer to the information provided in the technical catalogue for the 48EN/EH units, the wiring diagram included with the unit as well as the regulations and standards in force that regulate the installation of air conditioning units and electrical receivers.
Important: All the connections to be established by the client are featured on the wiring diagram included with the unit.
CARRIERrtc control
The CARRIERrtc control has a proportional output 0/10V (Y2) where a natural gas or propane gas proportional actuator can be connected.
The control will manage its connection, in HEATING mode, through an ON/OFF signal in digital output NO5.
- In cooling-only devices, the control will activate the burner the same way as an electrical heater with one or two stages.
- In heat pump units it is possible to select three different methods for controlling the burner for display:
• Operation of the compressors as one or two electrical heater
stages (both optional not compatible).
• Operation instead of the compressors.
• Operation instead of the compressors if the outdoor temperature
is less than the value set (5ºC by default).
When the return temperature drops below the value set for the burner connection the burner will start to operate. The control of the power will be carried out in accordance with the air outlet temperature and the return temperature. The control will therefore compare both temperatures and although there is a high burner power demand, if the outlet temperature is excessively high it will limit the power supplied by the burner. This avoids the stratifi cation of the hot air masses and that the outlet air temperature exceeds a maximum safety level, 55ºC by default, which will cause the burner to stop.
Moreover, units with gas burner always include a ambient temperature probe to limit the difference between the air outlet pressure and the ambient temperature and, with that, improve the feeling of thermal comfort.
The gas burner integrates operations control and its safety devices. The control CARRIERrtc will receive a safety signal from the burner in the event of failure (digital input DI5), which will only serve to indicate the failure.
Position of the outdoor
thermostat (located below
the 48EN/EH electric panel)
Wiring diagram:
The hose with all the wires required for the connection of the burner control with the CARRIERrtc control must be wired in a box located inside the 48EN/EH box.
230 Vac
RUN Signal
987654321 12111098 GNDLN
Burner remote control
On/Off
0/10Vcc
AL (DI5) Signal
N.O.
N.C.010
(Y2)
ON/OFF (NO5) Signal
Burner remote
control
Instantaneous voltage display screen
Burner in operation
Unit switched on
On the burner remote control
screen the instantaneous voltage transmitted to the control plate is displayed.
The burner remote control is also responsible for managing the safety devices. In the event of failure the CARRIERrtc control will be sent a failure signal by way of indication.
In addition to the burner’s safety devices, the CARRIERrtc control allows incorporating complementary safety elements in the unit for the detection of smoke, excessively high temperatures, loss in the air fl ow rate etc. (consult the section on “Safety Devices”).
The connection of this hose is explained in the chapter “Burner Installation”.
Access door
Main electric panel
(CARRIERrtc control)
Auxiliary electric panel
(burner remote control)
Access door
Page 11
Packaged rooftop units with integrated gas burner
11
Supply of air from the 48EN/EH unit
Safety thermostat bulb (F2)
The F2 blocking can be triggered when the safety thermostat bulb detects an excessive temperature in the inlet air to the burner. The following fi gure shows the position of the aforementioned bulb:
The burner remote control manages the burner protection devices by detecting and indicating the following operating faults on its display:
Safety devices in the gas burner
Indication Failure Problem
F1 The burner does not
start.
Reversed phase and neutral. No gas supply. Connection without neutral. No ground connection. Problems with the fl ame detection electrode. The electrode nozzle is dirty or its diameter is incorrect.
F2 Safety thermostat High temperature in the exchanger.
Faulty thermostat bulb. Presence of smoke.
Differential air pressostat
The plastic conduit that enters the pressostat is disconnected. The discharge pipe and / or air inlet pipe is (are) blocked. Pressostat fault.
F3 The fan does not start The fan wiring is wrong or
disconnected. The voltage values for the modulation are outside the range. Failure in the fan motor.
F4, F5, F6 Unused F7 No serial
communication
The remote control is disconnected.
F8 The fl ame control
device does not work
The fl ame control device is disconnected or broken.
To unblock press both keys for 3 seconds
The screen displays a fault
Green led: this indicates that the unit is switched on
Unused
Red led: this indicates that the burner is switched on
Blocks F1, F2, F3 and F8 are triggered by safety devices and require manual resetting. T o unblock press the up and down keys for 3 seconds at the same time.
8. SAFETY ELEMENTS
Signalling pilot for the switched on unit
Signalling pilot for burner blocking
Transformer 230V/24V
Electronic modulation
Power supply
Connection for display
General switch
Flame control device
In order to access the gas burner control remove the door from the auxiliary electric panel:
Burner remote control
Gas burner switch
By removing the support box for the remote control access is gained to the modulation board (0-10Vcc) and to the fl ame control device:
Support box
In the event of failure, the burner control will send the CARRIERrtc control a safety signal which will only be used as an indication (see the electrical connections diagram in the previous chapter).
Page 12
Packaged rooftop units with integrated gas burner
12
Main door switch
By using a mechanical device, it impedes access to the electric panel when the unit is with voltage.
High pressure pressostat
Connected to the compressor discharge, it will stop its operation when the pressure at that point reaches the setpoint. It disconnects at 42 bar and it is automatically reactivated.
Low pressure pressostat
When connected to the compressor suction, it will stop its operation when the pressure at that point goes down below the tare value (caused by obstructions in the circuit, excessive dirt in the fi lters, fan stop or ice formation in the evaporator).
It disconnects at 2 bar and it is automatically reactivated.
Safeties at the compressor
The scroll type compressor that these units as standard have the following safeties:
- Non-return valve built into the compressor.
- Klixon in the compressor, which stops the operation of the motor when there is excessive heating.
Condensation and evaporation pressure control
This safety element, integrated in the control, enables managing the outdoor fans when the units are working in COOLING mode with low outdoor temperatures (condensation control) or in HEATING mode with high outdoor temperatures (evaporation control).
This aids the unit's operation in all the stations.
Smoke detector (optional)
This smoke detection station uses a LED to indicate the installation status and if the probe detects the presence of smoke in the installation it stops the operation of the unit. The station is installed in the factory in the auxiliary electric panel.
Smoke detecting station
Smoke detecting probe
Clogged fi lter detector (optional)
Differential pressostat for indication of maintenance to fi lters. Automatic reactivation. It is installed in the auxiliary electric panel.
Anti-fi re safety device
This safety device, integrated in the control, shuts down the unit if the probe located in the return detects an air inlet temperature above 60ºC. The unit will not return to operation until this temperature drops under 40ºC.
Control of air fl ow
Differential pressostat that measures the fl ow variation in the air outlet. This allows the detection of fan belt breakages, since the fan relay only detects operating faults that have arisen in the motor. This pressostat is installed in the factory in the auxiliary electric panel.
Protection of the electric panel (optional)
Anti-freeze protection for low outdoor temperatures with electric heater. This safety device is compulsory when the outdoor conditions guarantee an air inlet temperature to the burner which is less than -15ºC.
Air quality probe (optional)
This probe is for installation in the environment or in duct to enable measuring CO2 and/or volatile compounds.
This probe is to be connected by the client. The clamps on the terminal board on the main panel used for the connection are indicated on the wiring diagram provided with the unit.
This probe is supplied inside the main electric panel.
Automatic switch in the control circuit
Magnetothermal switch that protects the operation circuit against continuous surges as well as against high currents of short duration (short circuits).
Defrost control
This safety element is intended to eliminate ice which could accumulate in the outdoor coil when the unit is working in the heating CYCLE. Defrosting is carried out by the control depending on the value measured by the sensors on the outdoor coils and the time set between defrosting operations.
Magnetothermals for line protection
They are located at the beginning of the power lines of the compressor and motorised fans to protect them.
Safety devices in the 48EN/EH unit
Page 13
Packaged rooftop units with integrated gas burner
13
9. CHECKING BEFORE COMMISSIONING
Note: Under no circumstance should the unit be started without having read the brochure completely.
Gas Burner
Caution: During the installation work and when adjusting the burner the gas pipe must be unloaded.
Electrical Connections
Note: All the connections to be established on site are the responsibility of the engineer and are indicated on the unit wiring diagram.
T o prevent electrical shocks, make all electrical connections before energizing the unit. Check that the automatic switch is closed. Omitting this can cause personal damage. Make the ground connection before any other electrical connection.
V-220004
V-220004
The installer must fi x line protection elements according to the effective legislation.
Before putting the unit into operation also check the following:
• Check the condition of the electrical connections and that they are correct (an electrical diagram is included with each unit, along with its legend).
• That the electrical power supply remains constant and that it corresponds to that featured on the unit data plate.
• That they are no cables close to heat sources.
• The correct connection of all the sensors supplied with the unit. The connection of the outlet temperature and ambient temperature probes must be established on-site. These probes are supplied inside the main electric panel.
In order to establish the unit's electric power supply (cable inlet, calculation of the lead section, protection devices etc.), refer to:
- The information supplied in this document (table of technical characteristics).
- Data plate.
- The wiring diagram and the legend supplied with the unit.
- The CARRIERrtc electronic control brochure which is also supplied with the unit.
- The regulations and norms in force which regulate the installation of air-conditioning units and electric receivers.
The electric power supply of the unit must be sized in accordance with the maximum power absorbed by the unit taking into account all the options it features (if necessary, refer to the technical brochure).
- With regard to the electric supply, check:
• The correct neutral and phase connection. If they are reversed the fl ame control prevents operation.
• The correct adjustment of the burner control and regulation devices.
ambient probe
outlet probe
Connection of the outlet temperature probe:
In order to guarantee the correct measurement of the outlet air temperature this probe will be positioned at 1.5 metres as a minimum from the outlet mouth at the bottom of the duct and as near to the middle as possible inside this duct.
The connection of the probe to the corresponding clamps on the control board (see wiring diagram) will be carried out with a cable with two wires measuring 1mm2.
3 x M3x10 self-tapping male
Rotate to open
Rotate to close
Clamp for attaching to the duct
Screw to fix the probe position (PT3.5x12)
61
120°
120°
25
42
No. 3 holes Ø 2.75
Ø 17
37,5
43,3
==
Detail of clamp dimensions (mm)
View of the probe without cover (rotate the cover anti-clockwise)
View of the probe interior (connection
of 2 wires in the terminal board)
In order to fi x the probe to the duct a clamp will be used which is supplied with the probe as shown in the fi gure below:
Page 14
Packaged rooftop units with integrated gas burner
14
1 2 3 4 5 6 7 8
PCH150/200
Included in the burner module
Where:
1. Solenoid valve main burner (EV2)
2. Solenoid valve pilot burner (EVP)
3. Pressure stabiliser:
4. Solenoid safety valve (EV1)
5. Gas fi lter (small section)
6. Vibration damping gasket
7. Gas fi lter (large section)
8. Gas cock
- With regard to the gas supply: The burner module includes the following elements: solenoid valves,
stabiliser and safety valve (see diagram). To complete the installation a gasket must be fi tted to dampen
vibrations and a gas cock. It is also obligatory to install a gas fi lter with certifi cation EN126 with a fi ltering level less than or equal to 50 microns, without pressure stabiliser for a high fl ow due to being assembled as standard with the gas valve.
For the gas power supply the burner has a bronze M 1" threaded drain junction.
Note: If the generator is not going to be used over a prolonged period the gas supply valve must be closed.
Chimney connection: As a general indication, the chimney mouth must be located, as
a minimum, 1 metre above the highest point of roofs, walls or any other distant obstacle at less than 10 metres. If the chimney mouth is located at a distance between 10 and 50 metres from any building it must be at a level of no less than the upper edge of the highest gap in the nearest building.
The materials used for the manufacture of the chimney are:
- Aluminium with a minimum thickness of 1.5 mm.
- Stainless steel with a minimum thickness of 0.6 mm (carbon content <2%).
Pipes with hermetic gaskets should be used to prevent any condensate leak. These gaskets must be prepared for working over a temperature range of 30ºC to 160ºC.
These pipes must also be insulated to protect those who could accidentally touch them from burns.
Note: The gas burner chimney is not supplied with the unit. Its design and installation is the responsibility of the engineer and must comply with all the directives and regulations in force in the installation location.
- With regard to the smoke outlet: Smoke outlet connection type: category B23. Inside diameter of the
connection 146 mm andoutside diameter 210 mm (symbol
6
).
- With regard to the fuel, check that:
• The gas supply network information is compatible with that indicated on the data plate and that the generator is supplied with the same type of fuel for which it has been manufactured.
• The aspiration of combustion air and the expulsion of smoke are free (presence of dirt, leaves etc.)
• The unit air fl ow rate is appropriate according to the data plate and the unit includes all the required safety elements in perfect condition.
• The fuel supply pressure is within the interval featured on the data plate.
• The supply line valves are open.
• There are no leaks in the gas line.
- With regard to the collection of condensates: These units are equipped with a junction for draining the burner
condensates drain pan. Threaded connector M 3/4” in PVC (see symbol
3
in the following fi gure).
T o facilitate drainage, the construction of the group of generator pipes slopes slightly towards the discharge.
If the unit is going to be installed outdoors in a location where there are never low temperatures, the drain junction does not have to be connected to any pipe. It must simply be ensured that the water does not stagnate.
If the condensates are going to be discharged into a pipe do not seal it directly at the condensate outlet. If the water were to freeze in the pipe this could block the discharge of condensates and cause the water to accumulate inside the exchanger.
Group of sloping pipes
Note: The access panel to the burner includes two grilles for the recirculation of outdoor air in the case of a gas leak inside the module (see symbol 4 in the following fi gure).
Page 15
Packaged rooftop units with integrated gas burner
15
The air outlet and return ducts must be calculated in accordance with the nominal fl ow and the unit's available pressure (refer to the technical characteristics table). The duct calculation and design must be made by qualifi ed technical personnel.
It is advisable to take into consideration the following recommendations:
- Bends in the discharge outlet must be avoided. It is recommendable to have a straight section of duct measuring approximately 1 metre. If it is not possible, they must be as smooth as possible, using indoor defl ectors when the duct is of large dimensions.
- When making the ducts, abrupt changes in direction must be avoided since they can cause occasional pressure drops which affect the available pressure and the fl ow. The location of discharge and aspiration grilles must be studied carefully to avoid the air recirculation and the transmission and generation of noises to the interior.
- Flexible connections must be made between the ducts and the unit that avoid the noise and vibration transmission.
Air ducts connections
Checks in the axial fans
- Before commissioning, check the blade rotation direction and that the axis turns without strokes nor vibrations
- Once running, check the operation conditions: pressures, fl ows and consumptions.
- With electronic fans (optional) check that in COOLING mode they adapt their speed according to the condensation pressure and in HEATING mode according to evaporation pressure.
6
Where:
1. Air inlet grilles to the burner (its design takes into account the removal of rainwater to the outside using the lower grille)
2. Gas power supply, junction M1"
3. Removal of burner condensate, junction M 3/4”
4. Grilles for the recirculation of outdoor air
5. Access panel to the auxiliary electric panel and to the burner remote control
6. Chimney connection (by the customer):
Indoor: 146 mm yOutdoor: 210 mm
1
5 4 3 2
The following fi gure shows the gas burner connections: - No matter the type of ducts type to use, they must not be composed
of materials that propagate fi re nor expel toxic gases in the event of a fi re. The internal surfaces must be smooth and should not pollute the air that circulates within them. In any case, the effective legislation in this respect must be observed.
Checks in the centrifugal fans
Page 16
Packaged rooftop units with integrated gas burner
16
Condensate drain connection
Siphon installation norms
- Check that the condensate outlet is not clogged.
- All water drain tubes must be provided with a siphon to avoid bad smell and water spills.
Perform the assembly as per the scheme of the attached starting
diagram:
Pan in overpressure:
• It is installed to avoid the access through the drain tubing of bad
smells.
All the models are equipped with a junction for the draining of the condensates drain pan from the indoor circuit. Drain joint, made of bronze, gas thread M 1 1/4".
With outdoor temperatures which are lower than 0ºC the necessary precautions must be taken to prevent the water in the drain ducts from freezing.
CONNECT SIPHON
METTRE SIPHON
PONER SIFON
V220014
Check the connection air tightness.
A
Condensates pan
in depression
A
Siphon drain
Slight slope
5/1000
To drainage
Pan in underpressure:
Besides the previous application, water must be sucked from the pan:
• For the correct siphon design, the "A" height must be at least twice
that of the underpressure (mm.w.c) where the condensates pan is placed.
• The drain tubing must be slightly sloped to ease circulation towards
the drain.
• The original diameter of the tube must be respected. No reduction
can be made.
Condensates outlet
- Before commissioning, check the blade rotation direction and that the axis turns without strokes nor vibrations.
- Once running, check the operation conditions: pressures, fl ows and consumptions.
- The coupling of characteristic bends of the fan and the room is very important, so that the fl ows and pressures provided to the duct network are as required.
Pulley and belt adjustment
Centrifugal motorised fans in the indoor circuit are coupled using pulleys and belts. In this type of fans, the following must be taken into considerations:
- The pulleys must be on the same plane, so it is important to check them with the help of a ruler or a laser aligner.
- In case they are not, remove the pulley screws, remove the pulley and, after removing the hub pin, it can be slided over the axle (this action can be performed both in the motor as well as in the fan).
- After fi xing the pulleys on the same plane, the belt tension is made by tightening the tensor screw.
- The belt tension must be checked after 24 hours of motor operation.
Attention: Before performing these operations, it is necessary to verify that the unit is disconnected from mains.
Pulleys must stay on the same plane
Tensor screw
Pulley screws
Taper pin
• Soft starter detail (optional):
The soft starter of the outlet fan extends the time to reach its regular speed. This is mainly intended for installations with fabric ducts.
It is installed in the factory in the auxiliary electric panel for motors up to 15kW.
Page 17
Packaged rooftop units with integrated gas burner
17
- When starting the compressors, check the subcooling and overheating and thus verify if the refrigerant load is appropriate to the operating conditions. To adjust the refrigerant load, a schrader valve is available on the liquid line.
- Verify the absence of any leaks of the refrigerant.
- Check the unit operation and verify the safety elements.
- All the 48EN/EH models are equipped with scroll type compressors and have a phase control relay. Verify that they turn in the correct direction and, if not, reverse the power wires.
10. STARTING THE UNIT
R 410A
Operational checks
Check the unit operation by verifying the electronic control and the safety elements.
It is also recommendable to create a report, taking note of the date, which includes the following information: the nominal voltage, current absorbed by the compressors, fans and other electrical components, signifi cant temperatures in the cooling circuit (see table below) and other aspects considered interesting such as alarms detected by the electronic control of the unit. The recording of these parameters whilst the unit is running allows controlling the installation performance and it is the best possible way to avoid breakdowns since the analysis of these data makes early detection of anomalies possible or the provision of the necessary means available to ensure that they do not take place.
Possible problems at commissioning
All indications given in this brochure must be respected and complied with to guarantee a correct operation of the units.
Next, several possible operation problems are stated which could happen if the conditions of the commissioning are not appropriate.
- Air fl ow lack: very high differences between inlet and outlet, originated by a high pressure drop in the ducts, or by other causes that impede the correct air circulation.
- Air recirculation in the unit, originated by some obstacle in the air aspiration or outlet.
- Noise problems because of excessive air fl ow in the grille.
- Water overfl owing to the pan problems, originated by an excessive fl ow, an incorrect siphon installation or because a defective unit level.
- Refrigerant circuit humidity problem, because of an incorrect vacuum realization.
Checks prior to commissioning
- It is advisable to make a complete sketch of the installation including the location of the unit and all the components used. This will be very helpful for maintenance and repairs to the installation.
- Check that the electrical power supply matches the unit voltage and that its value lies within acceptable limits.
- It must also be verifi ed that the electric installation has been carried out according to the electric wiring diagram provided with the unit (consult the chapter on “Checking before commissioning”).
- Once the above verifi cations have been carried out, the control circuit is supplied with voltage by the automatic control switch. It is necessary to leave with voltage the compressor crankcase heater for 24 hours before starting the compressor.
WICHTIG: WIEDERBEHEIZUNG DER
OLWANNE
IMPORTANT: CRANKCASE HEATING
IMPORTANT: SURCHAUFFE CARTER D’HUILE
IMPORTANTE: RISCALDARE IL CARTER
DELL’OLIO
IMPORTANTE: RECALENTAMIENTO DE
ACEITE DEL CÁRTER
KOENNEN.
TO ALLOW THE COMPRESSOR(S) STARTING
AU PREMIER DÉMARRAGE OU APRÈS UNE ABSCENCE
TENSION 24 HEURES AVANT D’AUTORISER LE DÉMARRAGE DU(DES) COMPRESSEUR(S).
AL PRIMO AVVIAMENTO U DOPO UNA INTERRUZIONE PROLUNGATA DELLA ALIMENTAZIONE ELETTRICA, LASCIARE LA MACCINA SOTTO TENSIONE PER 24 ORE PRIMA DI AUTORIZZARE L’AVVIAMENTO DEL(DEI) COMPRESSORE(I).
ANTES DEL PRIMER ARRANQUE O DESPUÉS DE UNA AUSENCIA DE CORRIENTE POR UN LARGO PERIODO DE TIEMPO, CONVIENE QUE LA UNIDAD ESTÉ CONECTADA UN MÍNIMO DE 24 HORAS.
BEIDER ERSTEN INBETRIEBSETRUNZ ORDER NACH EINER LANGEN STROMUNTER-BRECHUNG BRINGEN SIE DIE MASCHINE UNTER SPANNUNG 24 STRUNDERLANG BEVOR SIE DEN(DIE) KOMPRESSOR(EN) EINSCHALTEN
FOR THE FIRSTSTART OR AFTER ALONG TIME OUT OF VOLTAGE PUT THE MACHINE ON LIVE 24 HOURS BEFORE
DE COURANT PROLONGÉE, METTRE LA MACHINE SOUS
COMPRESOR SCROLL.
COMPROBAR SENTIDO DE GIRO
COMPRESSEUR SCROLL.
VÉRIFIER LE SENS DE ROTATION
SCROLL COMPRESSOR.
CHECK SENSE OF ROTATION
COOLING mode HEATING mode
Compressor
Suction pressure bar
Compressor
Suction pressure bar Suction temp. (1) ºC Suction temp. (1) ºC Condens. pressure bar Condens. pressure bar Condens. temp. (2) ºC Condens. temp. (2) ºC
Air condenser
Gas inlet temperature ºC
Air evaporator
Gas inlet temperature ºC Gas outlet temp. (3) ºC Gas outlet temp. (4) ºC Air inlet temperature ºC Air inlet temperature ºC Outdoor temperature ºC Outdoor temperature ºC Air outlet temperature ºC Air outlet temperature ºC
Air evaporator
Air inlet temperature ºC
Air condenser
Air inlet temperature ºC Air outlet temperature ºC Air outlet temperature ºC Gas inlet temperature ºC Gas inlet temperature ºC Evap. outlet temp. (4) ºC Gas outlet temp. (3) ºC
Subcooling (2) - (3) ºC Subcooling (2) - (3) ºC Overheating (4) - (1) ºC Overheating (4) - (1) ºC
Page 18
Packaged rooftop units with integrated gas burner
18
Pre-assembly frames (optional)
The units can be attached to standardised preassembled frames with adjustable height, built in galvanised steel panelling with thermal insulation.
For more information please consult the specifi c brochure for the frames.
Outdoor coil protection grille
All the models can include a protection grille for this coil. This grille is fi xed by modules in the holes made for this goal in the unit's support.
11. OPTIONS
The installation of the following options causes pressure drops at air level which means this has to be taken into account in the selection of higher pressure fans (optional) or in the substitution of the standard pulley set with a new set that generates a higher turn speed to the pad. Both the fan performance curves, as well as the pressure drop graphs in the options, can be consulted in the technical brochure for the 48EN/EH series.
Filters
Creased opacimetric fi lters
All model types can substitute the fi ltering mesh that the units include regularly with G4 rating, mounted on the same frames. Also, creased opacimetric F6 to F9 rating fi lters can be added.
Gravimetric fi lters
Stop-drop
The units with outdoor air intake can include a stop-drop in this intake.
Stop-drop
Air outlet damper
Outdoor air damper (displaced)
Grille module
Holes
Adjustment system
Page 19
Packaged rooftop units with integrated gas burner
19
12. MAINTENANCE
V-220004
Caution: Before intervening in the unit, cut off main power.
Recommendations:
In general, a corrosion control must be performed on the metallic parts of the unit (frame, bodywork, exchangers, electric panel, etc.). All the electric connection states must be checked as well, as well as the air tightness of the different circuits.
Next, some recommendations are stated to perform the cleaning of the unit's components:
Air coil
- Check that the coil is free from dust and grease.
- Cleaning the accumulated dust on the coil can be performed with a vacuum cleaner perpendicular to the fi ns or with a low-pressure water cleaner. Grease can be removed with water with degreaser. Do not put stress on the fi ns as they could deform.
Condensates drain pan
- Check that the condensates pan is clean. There should be no stagnant water.
- Check that the drain is not clogged.
- Cleaning of the pan can be done with water and non-abrasive detergent.
Gravimetric fi ltersOpacimetric fi lters
Tabs for displacement of the opacimetric fi lters
Air fi lters
- Clean usually. Depending on the installation conditions, the fi lter aspect must be examined to defi ne the cleaning periodicity.
- Gravimetric fi lters: Cleaning the fi ltering mesh can be done with a household vacuum cleaner, or by submerging it in water.
- Creased opacimetric fi lters: these have to be replaced. Foresee replacement.
Filter removal:
The frames with the gravimetric fi lters as well as opacimetric frames (if the unit has includes them) are assembled over a sheet steel profi le. Frames are moved by lifting the tab and dragging along the rail.
The minimal maintenance operations and their periodicity will be made according to the national regulations.
Any intervention on the electric cooling components must be made by a qualifi ed and authorized technician.
Centrifugal fan
- Verify that the turbine and the motor remain clean.
- Foresee having a spare belt set for the fans.
- The motors and the fans have bushings that have been lubricated and sealed and, thus, do not need further lubrication.
Tabs for displacement of the gravimetric fi lters
Mixing boxes and free-cooling
In units with mixing box assemblies with motorised dampers (MS, MA and MC0 assemblies) it is advisable to check the condition of the servomotor. In these units the mixing damper is locked to the outdoor air inlet.
Outdoor air damper
Servomotor
Page 20
Packaged rooftop units with integrated gas burner
20
Refrigerant
Qualifi ed personnel must perform a periodic control to air tightness depending on the refrigerant load, in accordance with the regulation (CE) Nº 842/2006.
It is important not to ever forget that the cooling systems contain liquids and vapours under pressure. The service pressure of R-410A is approximately 1.5 times higher than that of R-407c.
- All necessary precautions must be taken during the partial opening of the cooling circuit. This opening entails the discharge of a certain amount of refrigerant to the atmosphere. It is essential to limit to its minimum this amount of lost refrigerant by pumping and isolating the load in some other part of the circuit.
- The refrigerant fl uid at low temperature can cause infl ammatory injuries similar to burns when contacting the skin or eyes. Always use protection glasses, gloves, etc. when opening ducts that may contain liquids.
- The refrigerant in excess must be stored in appropriate containers and the amount of refrigerant stored at the technical rooms must be limited.
- Refrigerant barrels and deposits must be handled with precaution and visible warning signs must be placed to attract attention over the risks of intoxication, fi re and explosion linked to the refrigerant.
- At the end of its useful life, the refrigerant must be retrieved and recycled as per the current regulations.
Gas Burner
Oil
- Check the oil level and aspect. In case of a colour change, check the oil quality using a contamination test.
- In the case of the presence of acid, water or metallic particles, replace the affected circuit oil, as well as the dehydrant fi lter.
- In the event of an oil charge change, only new oil will be used, which will be identical to the original oil and taken from a can tightly closed until the moment of the charge.
Note: Both the oil type as well as the volume needed for each model are stated in the Technical characteristic tables in chapter 3.
Caution: Before starting any maintenance operations ensure that the supply of gas and electricity have been turned off.
V-220004
Only qualifi ed staff are allowed to undertake maintenance tasks or resolve a breakdown.
Pay attention to the temperatures of some components after operation. They could be very high (exchanger, chimney, etc).
Hazard: Never use a naked fl ame whilst checking the burner. Never store fl ammable material in the machine room.
1. The ignition, fl ame detector and the electrodes
Disassemble the set and clean the steel grille and the nozzle with a blast of compressed air. Check that the ceramic is intact and remove any oxide residue from the metal parts of the electrodes using emery paper. Check the correct positioning of the electrodes (see diagram below). Check that the detection electrode is positioned tangently to the head of the burner, not inside it. The ignition electrode must rest on the ignition pilot grille.
Check that the ignition electrode is working between the grille and the outer edge
2/3mm
Keep the detection electrode tangent to the ignition pilot head
The maintenance and checking of the combustion must be performed in compliance with the legislation in force. Any modifi cation or change in the material must be undertaken with the manufacturer's consent; the replacement of a faulty component for another non-compliant component could present a hazard for which CARRIER could not accept liability.
These burners operate with minimum maintenance, however in order to guarantee optimum performance when starting each warming stage check:
Dehydrant fi lter
- The filter function is the preserve the cooling circuit clean and without humidity, neutralizing the acids that can be found in the cooling circuit. Verify dirt by measuring the difference in temperature at the tubing level between the inlet and the outlet of the dehydrator.
- If necessary, replace.
Page 21
Packaged rooftop units with integrated gas burner
21
E
A
B
2. The smoke discharge ducts and the air inlet
Check the condition of the ducts by looking inside or using suitable tools. Remove the dust from the air inlet terminal.
3. The venturi
If required, use a brush to remove the dust from the venturi inlet ensuring that it does not fall inside.
4. Cleaning the exchanger
Optimised combustion in these burners prevents the appearance of residual products. Nevertheless, dirt could be deposited inside the exchanger pipes due to the fi ne dust pulled through the combustion air duct.
Since it is not possible to plan a precise schedule for cleaning the exchanger a considerable reduction in the gas fl ow rate could indicate that there is dirt inside.
If the exchanger has to be cleaned observe the following operation when the unit is cold and disconnected from the supply:
• Remove the door and the gasket which goes around the edge of the control plate carefully to avoid damaging it.
• Remove self-tapping screws (A) which hold the control plate and the outer panel (B).
• Disconnect the gas pipe, the electric power supply and the smoke discharge system.
• Remove the outer panel (B).
• Remove screws (E) which hold the smoke manifold lid.
• Use a suitable brush to clean the entire length of the pipes pushing all the dirt towards the outlet to collect it.
• Check that the condensate discharge gasket is clean.
• Reassemble all the parts ensuring that the sealing is hermetic.
7. The operation of the fl ame control device
With the burner in operation, close the gas valve and check that it blocks and that the remote control displays the error F1 on the screen (consult the section on “Burner Safety Devices”). Open the valve, unblock the control and check that the burner is operating correctly.
8. The safety thermostat and the air differential pressostat
With the burner in operation open the thermostat using a suitable tool (230V). Quickly disconnect the pressostat or the safety thermostat and wait until the remote control displays the error F2 on the screen. Connect the thermostat again and unblock.
9. Ionisation current
Perform this operation using a device which is able to measure a direct current in microamperes. Do the following:
• Disconnect the unit from the electric power supply.
• Disconnect the cable from the fl ame control device and connect it to the negative pole of the ammeter.
• Use a cable to connect the positive pole of the ammeter and the fl ame control device.
• Switch on the device and wait until the burner starts.
• Measure the ionisation current.
This value must not be less than 2A. Lower values would indicate that the detection electrode is diverted, rusty or about to break.
6. The inlet pressure of the gas valve
Check that the valve inlet pressure corresponds to that required for the gas. This check must be carried out with the burner operating at maximum output.
Replace the gas valve if required. Refer to the manufacturer's brochure.
5. Cleaning the condensates drain siphon (if there is one)
Clean the siphon every year and check the gaskets. Ensure that there are no metal residues. If there are clean the siphon more frequently.
After emptying the siphon, fi ll it with water and close it using a suitable lid before restarting the burner.
Microammeter DC
Detection electrode
Flame
control device
mod. 032/092
mod. 150/200
Flame detection
Note: The aforementioned items from 1 to 4 must be performed with the electric power supply and the gas supply disconnected. Items 5 to 9 must be verifi ed with the burner in operation.
Page 22
Packaged rooftop units with integrated gas burner
22
13. CONTROL AND ANALYSIS OF BREAKDOWNS
Symptom Cause Solution
Evaporation pressure very high in relation with the air inlet
a) Load excess b) High air temperature c) Compressor suction not air tight d) Cycle reversing valve in middle position
a) Collect refrigerant b) Verify overheating c) Verify compressor state and replace d) Check that the valve is not clogged. Replace if
necessary
Very low condensation pressure a) Gas lack
b) Compressor suction not air tight c) Cycle inversion valve in middle position
d) Liquid circuit plugging
a) Search for leaks, complete charge b) Verify compressor state and replace c) Check that the valve is not clogged. Replace if
necessary
d) Verify the dehydrating fi lter and expansion valve
Condensation pressure very high in relation to the air outlet, high pressostat cutoff
a) Insuffi cient air fl ow
b) Air inlet temperature very high c) Dirty condenser (does not exchange) d) Much refrigerant load (fl ooded condenser) e) The condenser fan is broken down f) Air in the cooling circuit
a) Verify the air circuits (fl ow, fi lter cleanliness...) b) Verify the control thermostat readjustment c) Clean it d) Collect refrigerant
e) Repair f) Make vacuum and load
Evaporation pressure too low (low pressostat cutoff)
a) Low fl ow in evaporator. Air recirculation b) Frozen evaporator c) Liquid line as different temperatures at fi lter inlet
and outlet d) Gas lack e) Very low condensation pressure
f) Evaporator fan broken down
a) Verify the air circuits (fl ow, fi lter cleanliness...) b) Verify defrost c) Replace fi lter
d) Search for leaks, complete load e) Temperature of air or water in condenser very low
(air or water fl ow very high), adjust fl ow
f) Repair
Compressor does not start, does not make noise (humming)
a) No power b) The contacts of a control element are open c) Timing of anti cycle short does not allow the starting d) Open contact e) Contactor coil burnt f) Indoor Klixon open
a) Check differential, fuses b) Verify the safety chain of the electronic control c) Verify electronic control d) Replace e) Replace f) Wait for reactivation, verify intensity absorbed
Compressor does not start, motor sounds intermittently
a) Electrical power supply very low b) Power cable disconnected
a) Control line voltage and locate voltage drop b) Verify connections
Repeated compressor starts and stops a) Because of high pressure
b) Control differential too short (short cycle) c) Gas lack, cutoff because of low pressure d) Dirty or frosted evaporator e) The evaporator fan does not work, cuts off the low
pressostat f) Expansion valve damaged or clogged by impurities
(cuts off low pressostat) g) Dehydrating fi lter clogged (cuts off low safety)
a) Verify load b) Increase differential c) Search for leak, reload unit d) Clean, verify evaporator air circuit e) Replace or repair
f) Replace, as well as fi lter
g) Replace
The compressor makes a noise a) Loose attachment
b) Oil lack c) Compressor noise
a) Fix b) Add oil to recommended level c) Replace
Noisy operation a) Unit installed without antivibration protection a) Place base over shock absorbers
Cycle reversing is not carried out:
- No defrosting
- Does not change winter - summer cycles
a) Electrical fault b) Inversion valve coil defective c) Defrost method not working d) Cycle inversion valve in middle position e) Control fault
a) Locate and repair b) Replace c) Verify parameters d) T ap with running compressor Replace if necessary e) Locate and repair
Page 23
Page 24
Order No.: 10051, 03.2015. Supersedes order No.: New Manufactured for CARRIER in Spain. The manufacturer reserves the right to change the specifi cation without prior notice. Printed in the European Union.
Loading...