48/50HG014---028, 48/50PG20---28
Single---Package Rooftop Units
with COMFORTLinkt and Electro ---Mechanical Controls
Return and Supply Smoke Detector s Acces s ory
Installation Instructions
PART NO. CRSM KDET001D00, CRSMKSUP001B00, CRSMKSEN001A00
TABLE OF CONTENTS
GENERAL 1........................................
SAFETY CONSIDERATIONS 1........................
INSTALLATION 2...................................
Check Package Contents 2...........................
Return Air Smoke Detector Installation 2...............
Supply Air Smoke Detector Installation 5...............
Sensor Installation 7...............................
Configuring the ComfortLinkt Controller 8............
OPERATION 8......................................
MAINTENANCE 9...................................
Cleaning Procedure 9..............................
Recommended Service Schedule 9....................
Sensor Tests 9....................................
Controller T ests 9..................................
TROUBLESHOOTING 10.............................
Dirty LED 10....................................
Power LED 10....................................
Trouble LED 10..................................
IMPORTANT: There are two different design revision 48/50HG
units that have been produced. Because of these differences, there
are two different versions of this accessory. This accessory
literature covers accessories manufactured for units with design
revision 1. This revision designator is found in the 13th digit of
the unit model number located on the units’ rating plate. Design
revision 0 units are not covered in this accessory book.
To determine the design revision, refer to the full unit model
number. See Fig. 1 for an example of an HG model number. The
design revision number in the model number nomenclature is
located in position 13.
DESIGN REVISION NUMBER
Position No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Example: 4 8 H G D 0 1 6 A A C 6 1 1 A A
C07172
Fig. 1 --- Model Number Chart
GENERAL
An HVAC (heating, ventilation and air-conditioning) system
supplies conditioned air to virtually every area of a building.
Smoke introduced into this air duct system will be distributed
throughout the entire building. Smoke detectors designed for use
inside the unit are used to sense the presence of smoke passing
through the unit.
The smoke detector utilizes photoelectric technology for the
detection of smoke. This detection method, when combined with
an efficient ducting design, samples air passing through the unit.
If sufficient smoke is sensed, an alarm signal is initiated and the
ComfortLink controls will shut down the unit. With the unit shut
down, the unit will not blow toxic smoke and fire gases
throughout the areas served by the duct system.
The return air smoke detector is part number
CRSMKDET001D00, which includes a Smoke Sensor and a
Smoke Control Module combined with sampling tube, harnesses
and hardware. The supply air smoke detector is part number
CRSMKSUP001B00, which includes a Smoke Sensor and a
Smoke Control Module combined with sampling tube, harnesses
and hardware. Part number CRSMKSEN001A00 is a Smoke
Sensor only for use as a second (Supply with existing Return, or
Return with existing Supply) Air Smoke Detector with sampling
tube, harnesses and hardware.
The Control Module can be attached to a Smoke Sensor and
installed as an assembled unit, or it can be installed separate from
a sensor. One Controller can be used to control up to two
detectors (Smoke Sensors).
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install, repair,
or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance functions
of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to the unit,
and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use
care when handling and installing the accessory.
Recognize safety information. This is the safety--alert symbol
. When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
1
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. W ARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced installation,
reliability, or operation.
!
FIRE HAZARD
Failure to follow this warning could cause personal
injury and/or equipment damage.
This device will not sense smoke unless the ventilation
system is operating and the cover is installed.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
Disconnect all power to the unit before performing
maintenance or service. Install Lock Out tags on
disconnects or breakers.
CRSMK
!
FIRE HAZARD
Failure to follow this warning could cause personal
injury and/or death.
The National Fire Protection Association has
established that DUCT DETECTORS MUST NOT BE
USED AS A SUBSTITUTE FOR OPEN AREA
DETECTOR PROTECTION as a means of providing
life safety. Nor are they a substitute for early warning in
a building’s regular fire detection system. Carrier
supports this position and strongly recommends that the
user read NFPA Standards 90A, 72, and 101. This
smoke detector is listed per UL 268A.
!
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could cause personal
injury.
This device will not operate without electrical power.
Fire situations may cause an interruption of power. The
system safeguards should be discussed with your local
fire protection specialist.
WARNING
WARNING
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury and/or equipment damage.
For this detector to function properly, it MUST be
installed according to the instructions in this manual.
The detector MUST be operated within ALL electrical
and environmental specifications listed in this manual.
Failure to comply with these requirements may prevent
the detector from activating when smoke is present in
the air duct.
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
When installing the smoke detector in the unit, follow all
local codes.
Check Package Contents
Remove accessory packaging and inspect shipment for damage.
If any damage is found, file a claim with the shipping agent
immediately. If any item is missing or any part does not assemble
properly, notify the Carrier distributor.
Table 1 lists the accessory package contents. Fig. 2 shows the
smoke detector.
Return Air Smoke Detector Installation
(CRSMKDET001D00)
The return air smoke detector is to be installed in the predrilled
holes located above compressor B1/A2 in the
electrical/compressor section. (See Fig. 3.)
!
WARNING
INSTALLATION
!
CAUTION
UNIT
48/50HG014-028,
48/50PG20-28
Table 1—Accessory Package Contents — Return Air Smoke Detector (CRSMKDET001D00),
Supply Air Smoke Detector (CRSMKSUP001B00), Sensor (CRSMKSEN001A00)
RETURN SMOKE DETECTOR
CRSMKDET001D00
Description Part Number Quantity Description Part N umb er Quantity Description Part Numbe r Quantity
Sensor/Controller/
Harness/Tube
Screw AL56AU168 2 Screw AL56AU168 5 Screw AL56AU168 1
Screw AL48AM397 2 Sensor Module HK50ZT001 1 Screw AL48AM397 2
Bracket 50TG501113 1 Tube RN20ZT008 1 Bracket 50TG501113 1
Large Bushing HY93NH085 1 Cable Assy RM91ZT015 1 Large Bushing HY93NH085 1
Sampling Tube RN20ZT060 1 Plug — 1 Sampling Tube RN20ZT060 1
Plug — 1 Rubber Gasket — 2 Plug — 1
Rubber Gasket — 2 Sampling Tube Collar — 1 Rubber Gasket — 2
Sampling Tube Collar — 1 Snap-in Wire T ie HY76TB110 2 Sampling Tube Collar — 1
Wire Tie HY76TB125 1 Wi re Tie HY76TB125 2 Tub e RN20ZT008 1
Bushing HY93NH069 1 Bushing HY93NH069 1 Cable Assy RM91ZT015 1
Harness Assy 50TG403507 1 Harness Assy 50TG403507 1 Snap-in Wire T ie HY76TB110 5
Exhaust Tube — 1 Exhaust Tube — 1 Wire Tie HY76TB125 1
HK61ZT001 1
SUPPLY SMOKE DETECTOR
CRSMKSUP001B00
Controller/
RJ-45 Harness
HK28ZT001 1 Sensor Module HK50ZT001 1
2
ADDITIONAL SENSOR
CRSMKSEN001A00
Cable Assy RM91ZT001 1
Exhaust Tube — 1
Plug
Sampling tube
Exhaust tube
Rubber gasket
Sensor housing
and electronics
Conduit nuts
( field supplied )
Collar
Rubber
gasket
Smoke Sensor
PLUG LOCATION
Cover gasket
(ordering option)
Sensor cover
LEDs
Power
Dirty
Trouble
Alarm
Controller housing
and electro nics
Conduit cou plings
( field supplied )
Fig. 2 --- Smoke Detector
Fastener
(2X)
Smoke Control Module
Conduit sup port plate
Terminal block cover
Cover gasket
(ordering option)
SMOKE CONTROL MODULE
RETURN SMOKE SENSOR
Controll er cover
LEDs
Alarm
Trouble
Power
C07173
CRSMK
Fig. 3 --- Return Air Smoke Detector Location
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury and/or death.
Prior to installation of this accessory, make sure all
power is disconnected to the unit and locked out and
tagged.
NOTE: For horizontal applications it is easiest to install the
smoke detector prior to making duct connections.
1. Open the hinged electrical/compressor access door and
secure.
2. Find the 2 plugs located above compressor B1/A2,
remove and discard. Cut holes in the insulation located behind the partition.
A1B1/A2C1/B1
C07174
3. Remove cover from smoke detector. The screws will
remain captured in the cover.
4. Slide exhaust tube into the sensor. The exhaust tube
should be inserted from the back of the sensor, into the
hole with four slots, and locked into place. (See Fig. 2.)
5. Slide smoke detector into holes in partition with the terminal block to the right. Do not secure at this time.
6. Slide the sampling tube collar over the sampling tube until the tabs lock into the tube. (See Fig. 2.)
7. Slide long sampling tube (P/N RN20ZT060) into left-hand hole of smoke detector. It might be necessary to tilt
the smoke detector upwards in order to properly align the
sampling tube, making sure that the sampling holes
point DOWN. (See Fig. 4.)
8. Install plug into far end of sampling tube.
9. Remove the unit side panel at the return end of the unit.
Save screws for use later.
3