Carrier 48-50HJ004-014 User Manual

COBRA™ Energy Recovery Units
48/50HJ004-014 with 62AQ060-300
Single-Package Rooftop Units
with Energy Recovery Capability
Installation, Start-Up,
and Service Supplement
IMPORTANT: This is a supplemental instruction for the 48/50HJ and the 62AQ Installation, Start-Up and Service Instructions. It is not intended to take the place of either instruction o r to be a com plete piec e in itse lf.
CONTENTS
INSTALLATION Step 1 — Inspect Shipment Step 2 — Provide Unit Support
•ROOF CURB
Step 3 — Field Fabricate Ductwork Step 4 — Rig and Place Unit
• POSITIONING
Step 5 — Install Flue Hood (48HJ Only) Step 6 — Install Gas Piping (48HJ Only) Step 7 — Install External Trap for Condensate
Drain
Step 8 — Make Electrical Connections
• FIELD POWER SUPPLY
• FACTORY-SUPPLIED NON-FUSED DISCONNECT
• FIELD CONTROL WIRING
• HEAT ANTICIPA T OR SETTINGS
Step 9 — Assemble and Mount
Supply-Air Hood Step 10 — Mount the Barometric Relief Damper Step 11 — Set the Outdoor Cooling and
Heating Thermostats LIGHT COMMERCIAL THERMIDISTAT
ACCESSORY General Power Dehumidification Equipment and Connections Step 1 — Select Light Commercial
Thermidistat Location Step 2 — Set DIP Switches Step 3 — Install Light Commercial Thermidistat Step 4 — Set Light Commercial Thermidistat
Configuration Step 5 — Conduct Light Commercial
Thermidistat Start-Up and Checkout Step 6 — Make Final Settings
OPERATIONAL INFORMATION PRE-START-UP START-UP SERVICE TROUBLESHOOTING ROOFTOP UNIT AND ENERGY$RECYCLER2
START-UP CHECKLIST
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-29
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30-34
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35-37
. . . . . . . . . . . . . . . . . . . . . . . . . 38-41
. . . . . . . . . . . . . . . . . . . . . . 1
. . . . . . . . . . . . . . . . . . . . . . 2
. . . . . . . . . . . . . . . . . . . 2
. . . . . . . . . . . . . . . 3
. . . . . . . . . . . . . . . . . . . . . 6
. . . . . . . . . 11
. . . . . . . . . 11
. . . . . . . . . . 11
. . . . . . . . . . . . . . . . . . . . . . . . . . 29
. . . . . . . . . . . . . . . . . . . . . . . . . 30
. . . . . . . . . . . . . . . . . . . . . . . 30
. . . . . . . . . . . 33
. . . . . . . . . . . . . . . . . . . . 34
. . . . . . . . . . . . . . . . . . 34
. . . . . . . . . . . . . . . . CL-1, CL-2
Page
. . 28
. . . 30
. . 31
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precau­tions in the li terature, t ags and labe ls attached to the uni t, and other safety precautions that apply.
Verify that the power source supplied to the unit matches the voltages and amperages listed on the unit rating plate.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
Disconnect gas piping from unit when leak testing at pressure greater than 1/2 psig. Pres­sures greater than 1/2 psig will cause gas valve damage resulting in hazardous condi­tion. If gas valve is subjected to pressure greater than before use. When pressure testing field­supplied gas piping at pressures of less, a unit connected to such piping must be isolated by manually closing the gas valve.
Before performing service or maintenance operations on unit, turn off main power switch to unit and install a lock­out tag. Electrical shock could cause personal injury.
1
/2 psig, it must be replaced
1
/2 psig or
GENERAL
Carrier’s factory-installed optional COBRA Energy Recov­ery units precondition ventilation air for the rooftop unit during winter and summer operation and recover energy from the building exhaust air. These units are designed to satisfy the higher ventilation requirements and other building codes while minimizing energy costs.
Factory installation of the energy recovery section provides the benefit of reduced field-installation time, single point pow­er connections, and the assurance of a factory test for the com­plete COBRA Energy Recovery unit. The energy recovery sec­tion requires less maintenance than other energy recovery systems and can be serviced by any qualified refrigeration technici an .
NOTE: Because of the location of the energy recovery section, the unit nameplate has been moved to the opposite end of the rooftop section, on the upper, right-hand part of the panel.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1144 Tab 1a1b6a6b
PC 111 Catalog No. 534-80122 Printed in U.S.A. Form 48/50HJ,62AQ-2SIS Pg 1 9-02 Replaces: 48/50HJ,62AQ-1SIS
INSTALLATION
Step 1 — Inspect Shipment —
shipping company if shipment is inco mplete or damaged. See Fig. 1 for a typical shipping packa ging for a COBRA™ energy recovery unit.
File a claim with the
Step 2 — Provide Unit Support
ROOF CU RB — The COBRA energy recove ry unit can use a full-perimeter roof c urb or a standard ro of curb for the roof top section of the unit with a supplemental equipment support for the
energy recovery section. The supplemental equipment support is not required. The stan dard rooftop unit roof curb is capable of supporting both the rooftop unit section and the energy recovery section. Assemble and install accessory roof curb in accordance with instructions shipped with curb. See Fig. 2A-4. Install insu­lation, cant strips, roofing felt, and counter flashing as shown .
Ductwork must be attached to curb, not to th e unit. The accesso­ry thru-the-bottom power and gas conne ction package mu st be installed befor e the unit is set on the r o of curb.
DUCT OPENING SIZES
Supply = 13 7/8" x 20 1/4" R1 = 13 5/8" x 17 3/4" R2 = 13 5/8" x 12 5/16"
R1 = Return from building to HVAC
R2 = Return from building to 62AQ
Fig. 1 Shipping Packaging (48/50HJ004-006 Shown)
Deck pans
37 3/16"
67 3/8"
3 1/4
R1
14”
Supply
2"
92 1/2"
2" Return support. Only used on some applications.
Deck pans
R2
14"
37 3/16"
SIDE VIEW
END VIEW
Fig. 2A COBRA Energy Recovery Unit Full-Perimeter Roof Curb 48/50HJ004-007 with 62AQ060,100
2
49 15/16"
Deck pans
78 1/4"
2" Return support. Only used on some applications.
DUCT OPENING SIZES
Supply = 15 11/16" x 31 3/8" R1 = 15 5/16" x 29 1/16" R2 = 15 5/16" x 9"
R1 = Return from building to HVAC
R2 = Return from building to 62AQ
SIDE VIEW
14"
110 11/16"
3 1/4
R1
Deck pans
R2
Supply
14"
2"
49 15/16"
END VIEW
Fig. 2B COBRA Energy Recovery Unit Full-Perimeter Roof Curb 48/50HJ008-014 with 62AQ200,300
If electric control power or gas service is to be routed through the basepan, a field-installed accessory thru-the­bottom connection must be used. Attach the accessory to the basepan per the information in the accessory installation instructions. Thru-the-bottom connections must be installed before unit is set on roof.
If the combined unit roof curb is not being used, additional support may be desired under the energy recovery section of the unit. An accessory support and pad for the energy recovery section can be used. See Fig. 4. Place the protective rubber pad on the roof so that the edge near the unit is located about 6-in. from the end of the energy recovery section. Measure the distance from the bottom of energy recovery rails to t he pad. Adjust the energy recovery equipment support to match the measured distance and screw into plac e with the 4 screws pro­vided. See Fig. 4. Place the support underneath the energy re­covery unit and on the protective rubber pa d. This is done by lifting the end of the energy recovery section slightly above level and then sliding the support underneath the rails.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 3A and 3B. Improperly applied gasket can result in air leaks and poor unit performance.
Curb should be level. This is necessary for unit condensate drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
Step 3 Field Fabricate Ductwork
Secure all ducts to roof curb and building structure. Do not connect duct- work to unit. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes. See Fig. 5A and 5B for duct dimensions.
Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier. If a plenum return is used, the return should be ducted through the roof deck to com­ply with applicable fire codes.
A minimum clearance is not required around ductwork.
These units are designed for a minimum continuous heating return-air temperature of 50 F (dry bulb), or an intermittent operation down to 45 F (dry bulb), such as when used with a night set-back thermostat. To operate at lower return-air temperatures, a field-supplied outdoor-air temperature control must be used to initiate both stages of heat when t he tempera­ture is below 45 F. Indoor comfort may be compromised when these lower air temperature s are us ed with in sufficient heati ng temperature rise.
3
CONNECTOR
PKG. ACCY.
BC
CRBTMPWR001A00 CRBTMPWR002A00 1
CRBTMPWR003A00
1-9
11
[551]
/
1-4
16
[406]
CRBTMPWR004A00
D ALT
DRAIN HOLE
3
/
1
4
[44.5]
GAS POWER CONTROL
3
/4″
[19] NPT
1
/
2
[12.7] NPT
3
/4″
[19] NPT
3
[19] NPT
/
4
1
[31.7]
/
4
3
/4″ [19] NPT
1
1
[31.7]
/
4
1
/2″
[12.7]
1
/
2
[12.7]
ROOF CURB ACCESSORY
CRRFCURB001A00
CRRFCURB002A00
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance: 4 ft on each side.
A UNIT SIZE
1-2
[356] 2-0
[610]
48/50HJ 004-007
7. Direction of airflow.
8. Connector packages CRBTMPWR001A00 and 002A00 are for thru-the-curb type gas. Packages CRBTMPWR003A00 and 004A00 are for thru-the­bottom type gas connections.
TO ENSURE AIRTIGHT CONNECTION. PLACE UNIT AS CLOSE TO THIS END AS POSSIBLE
TO ENSURE AIRTIGHT CONNECTION. PLACE UNIT AS CLOSE TO THIS END AS POSSIBLE
Fig. 3A Roof Curb Details (48/50HJ004-007 Section Only)
4
CONNECTOR
PKG. ACCY.
BC
CRBTMPWR001A00 CRBTMPWR002A00 1
CRBTMPWR003A00
2-8
7
[827]
1-10
/
16
[583]
CRBTMPWR004A00
D ALT
DRAIN
HOLE
15
3
1
/
/
16
[44.5]
GAS POWER CONTROL
3
/4″
[19] NPT
1
4
/
2
[12.7] NPT
3
/
4
[19] NPT
3
[19] NPT
/
4
1
[31.7]
/
4
3
/4″ [19] NPT
11/4″ [31.7]
1
/2″
[12.7] NPT
1
/
2
[12.7] NPT
ROOF CURB
ACCESSORY
A
CRRFCURB003A00 1-2 [356] CRRFCURB004A00 2-0 [610]
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels: 1-in. thick polyurethane foam,
3
/4 lb density.
1
3. Dimensions in [ ] are in millimeters.
4. Roof curb: 16-gage steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance 4 ft on each side.
UNIT SIZE
48/50HJ
008-014
7. Direction of airflow.
8. Connector packages CRBTMPWR001A00 and 2A00 are for thru-the-curb gas type. Packages CRBTMPWR003A00 and 4A00 are for thru­the-bottom type gas connections.
TO ENSURE AN AIRTIGHT CONNECTION, PLACE UNIT ON CURB AS CLOSE TO DUCT END AS POSSIBLE.
TO ENSURE AN AIRTIGHT CONNECTION, PLACE UNIT ON CURB AS CLOSE TO DUCT END AS POSSIBLE.
Fig. 3B Roof Curb Details (48/50HJ008-014 Section Only)
5
UNIT SIZE
4
3-6 Ton
A
1
7
/2-121/2 Ton
EQUIPMENT SUPPORT
PART N U M BER
CRAQSUPT001A00 36.9 40 8 to 14 CRAQSUPT002A00 36.9 40 14 to 24 CRAQSUPT003A00 49.7 54 8 to 14 CRAQSUPT004A00 49.7 54 14 to 24
DIMENSIONS (in.)
AB C
C
10 x B (SEE CHART) PROTECTIVE RUBBER PAD (EPDM)
Fig. 4 Supplemental Energy Recovery Section Equipment Support
Step 4 Rig and Place Unit
Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Remove the bottom wooden skids that are under the unit by removing the wooden plates that hold the bottom wooden frame to the unit. Level by using unit frame as a reference. Lift­ing holes are provided in base rails as shown in Fig. 6A and 6B. Refer to rigging instructions on unit.
All panels must be in place when rigging.
POS ITION ING — Maintain cleara nce around and above unit to provide minimum distance from combustible materials, proper airflow, and service access. A properly positioned unit will have the following clearances between unit and roof curb:
1
/4-in. clearance between roof curb and base rails on each side and duct end of unit; 1/4-in. clearance between roof curb and condenser coil end of unit.
Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of cont aminated air.
Be sure that unit is installed such that snow will not block the combustion intake or flue outlet.
SCREW SUPPORT IN PLACE
HVAC UNIT
CURB
ADJUSTABLE EQUIPMENT SUPPORT
ENERGY
RECOVERY
SECTION
PAD
ROOF
Unit may be installed directly on wood flooring or on
Class A, B, or C roof-covering material when roof curb is used.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Flue vent discharge must have a minimum horizontal clear­ance of 4 ft from electric and gas meters, gas regulators, and gas relief equipment.
Minimum distance between unit and other electrically live parts is 48 inches.
Flue gas can deteriorate building materials. Orient unit such that flue gas will not affect building materials. Locate mechanical draft system fl ue assembly at leas t 48 in. from an adjacent building or combustible material.
Adequate combustion- and ventilation-air space must be provided for proper operation of this equipment. Be sure that installation complies with all local codes and Section 5.3, Air for Combustion and Ventilation, NFGC (National Fuel Gas Code), and ANSI (American National Standards Institute) Z223.1, and NFPA (National Fire Protection Association) 54 TIA-54-84-1. In Canada, installation must be in accordance with the CAN1-B149 installation codes for gas burning appliances.
After unit is in position, remove rigging skids and shipping materials.
6
REAR
SIDE
RIGHT
RIGHT SIDE
FRONT
FRONT
LEFT
SIDE
Fig. 5A Base Unit Dimensions COBRA Energy Recovery Unit 48/50HJ004-007 with 62AQ060,100
LEFT SIDE
7
Fig. 5A Base Unit Dimensions COBRA Energy Recovery Unit 48/50HJ004-007 with 62AQ060,100 (cont)
8
Fig. 5B Base Unit Dimensions COBRA Energy Recovery Unit 48/50HJ008-014 with 62AQ200,300
9
10
Fig. 5B Base Unit Dimensions COBRA Energy Recovery Unit 48/50HJ008-014 with 62AQ200,300 (cont)
MAX WEIGHT A B C
48HJ004 w/62AQ060 890 404 95.6 2428.20 57.38 1457.30 33.35 847 48HJ004 w/62AQ100 905 411 95.6 2428.20 57.38 1457.30 33.35 847 48HJ005 w/62AQ060 900 409 95.6 2428.20 57.38 1457.30 33.35 847 48HJ005 w/62AQ100 915 415 95.6 2428.20 57.38 1457.30 33.35 847 48HJ006 w/62AQ060 920 418 95.6 2428.20 57.38 1457.30 33.35 847 48HJ006 w/62AQ100 935 425 95.6 2428.20 57.38 1457.30 33.35 847 48HJ007 w/62AQ060 995 452 95.6 2428.20 57.38 1457.30 42.12 1070 48HJ007 w/62AQ100 1010 459 95.6 2428.20 57.38 1457.30 42.12 1070 50HJ004 w/62AQ060 795 361 95.6 2428.20 57.38 1457.30 33.35 847 50HJ004 w/62AQ100 810 368 95.6 2428.20 57.38 1457.30 33.35 847 50HJ005 w/62AQ060 805 365 95.6 2428.20 57.38 1457.30 33.35 847 50HJ005 w/62AQ100 820 372 95.6 2428.20 57.38 1457.30 33.35 847 50HJ006 w/62AQ060 825 375 95.6 2428.20 57.38 1457.30 33.35 847 50HJ006 w/62AQ100 840 381 95.6 2428.20 57.38 1457.30 33.35 847 50HJ007 w/62AQ060 880 400 95.6 2428.20 57.38 1457.30 42.12 1070 50HJ007 w/62AQ100 895 407 95.6 2428.20 57.38 1457.30 42.12 1070
lb kg in. mm in mm in. mm
Fig. 6A Rigging Label COBRA Energy Recovery Unit Sizes 48/50HJ004-007
Step 5 Install Flue Hood (48HJ Rooftop Sec­tions Only)
information on installing the flue hood.
Refer to the 48HJ installation instructions for
Step 6 Install Gas Piping (48HJ Rooftop Sec­tions Only)
information on installing the gas piping.
Refer to the 48HJ installation instructions for
Step 7 Install External Trap For Condensate Drain
condensate from the upper coil of the energy recovery section is internally piped to the condensate pan in the lower section of the energy recovery section. For this reason, the bottom drain on the rooftop unit CANNOT be used for a condensate drain. The located near the bottom left of the exhaust air section. See Fig. 5A and 5B. The energy recovery section must have a field-fabricated, external, P-trap installed for condensate drain­age. Trap must be at least 4-in. deep to protect against freeze­up. If the drain line is installed downstream from the external
The condensate from the rooftop unit along with
3
/4-in. drain connection on the energy recovery section is
trap, pitch the line away from the unit a t 1-in. per 10-ft of run. Do not use a pipe smaller than the connection (
3
/4-in.).
Step 8 Make Electrical Connections
Unit cabinet must have an uninterrupted, unbroken electri­cal ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control com­partment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA, latest edition, and local electrical codes. Do not use gas piping as an electrical ground. Fail­ure to follow this warning could result in the installer being liable for personal injury of others.
FIELD POWER SUPPLY — All units except 208/230-v units are factory wired for the voltage shown on the nameplate.
11
MAX WEIGHT A B C
lb kg in. mm in. mm in. mm 48HJ008 w/62AQ200 1310 595 77.42 1966.5 66.50 1689.10 42.12 1070 48HJ008 w/62AQ300 1355 616 77.42 1966.5 66.50 1689.10 42.12 1070 48HJ009 w/62AQ200 1315 597 77.42 1966.5 66.50 1689.10 42.12 1070 48HJ009 w/62AQ300 1360 618 77.42 1966.5 66.50 1689.10 42.12 1070 48HJ012 w/62AQ200 1400 636 77.42 1966.5 66.50 1689.10 50.12 1273 48HJ012 w/62AQ300 1445 657 77.42 1966.5 66.50 1689.10 50.12 1273 48HJ014 w/62AQ200 1440 655 77.42 1966.5 66.50 1689.10 50.12 1273 48HJ014 w/62AQ300 1485 675 77.42 1966.5 66.50 1689.10 50.12 1273 50HJ008 w/62AQ200 1240 564 77.42 1966.5 66.50 1689.10 42.12 1070 50HJ008 w/62AQ300 1285 584 77.42 1966.5 66.50 1689.10 42.12 1070 50HJ009 w/62AQ200 1245 566 77.42 1966.5 66.50 1689.10 42.12 1070 50HJ009 w/62AQ300 1290 586 77.42 1966.5 66.50 1689.10 42.12 1070 50HJ012 w/62AQ200 1325 602 77.42 1966.5 66.50 1689.10 42.12 1070 50HJ012 w/62AQ300 1370 623 77.42 1966.5 66.50 1689.10 42.12 1070 50HJ014 w/62AQ200 1345 620 77.42 1966.5 66.50 1689.10 42.12 1070 50HJ014 w/62AQ300 1410 641 77.42 1966.5 66.50 1689.10 42.12 1070
Fig. 6B Rigging Label COBRA Energy Recovery Unit Sizes 48/50HJ008-014
If the 208/230-v unit is to be connected to a 208-v power sup­ply, the t ransformer must be rewired by moving the black wire with the nection and moving to the 200-volt
1
/4-in. female space connector from the 230-volt con-
1
/4-in. male terminal on the
primary side of the transformer.
Refer to unit label diagram for additional information. Pig­tails are provided for field wire connections. Use factory­supplied splices or UL (Underwriters’ Laboratories) approved copper/aluminum connector.
When installing units, provide a disconnect per the NEC.
All field wiring must comply with NEC and local requir e ments.
Install field wiring as follows:
1. Install conduit through side panel openings. Install con­duit between disconnect and control box.
2. Install power lines to terminal connections as shown in Fig. 7.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (see T ables 1A-1H). On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the for­mula shown in the legend for Tables 1A-1H, Note 2 to deter­mine the percent of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and
may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.
F ACT ORY-SUPPLIED NON-FUSED DISCONNECT — The factory-supplied disconnect is capable of handling disconnect amps up to 80 A for a COBRA Energy Recovery unit. For dis­connect amps greater than 80 A, a field-supplied disconnect is required.
FIELD CONTROL WIRING — Install a Carrier-approved
accessory thermidistat assembly according to installation instructions included with the accessory. Locate thermidistat as-
sembly on a solid wall in the con diti one d spac e to sens e avera ge temperature in accordanc e with th ermidistat installation i nstruc­tions on page 30. Connect thermidistat wires to terminal board.
Route thermidistat cable or equivalent single leads of col­ored wire from subbase terminals through connector on unit to low-voltage connections (shown in Fig. 8). Thermidistat con­trol wiring is routed to both the rooftop unit control box and the energy recovery section control box.
If a PremierLink™ control is used, a thermidistat does not need to be used. A humidistat and a separate room air sensor are used. Two extra terminal blocks (TB2 and TB3) are provid­ed in the control box for all units with PremierLink controls. No wiring should be directly connected to the PremierLink control. Wire sensors to TB2 or TB3. Humidistat is wired to TB1 and energy recovery section control box.
12
NOTE: For wire runs up 50 ft, use no. 18 A WG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.
Pass the control wires through the hole provided in the cor­ner post; then feed wires through the raceway built into the corner post to the 24-v barrier located on the left side of the
Table 1A Electrical Data (COBRA Energy Recovery 48HJ004-007 Units with 62AQ060)
control box. See Fig. 10. The raceway provides the UL required clearance between high- and low-voltage wiring.
NOTE: A humidistat and a temperature sensor can be used in place of a thermidistat for PremierLink™ units.
HEAT ANTICIPATOR SETTINGS — Set heat anticipator settings at .14 amp for the first stage and .14 amp for second­stage heating, when available.
UNIT
48HJ004
48HJ005
48HJ006
48HJ007
FLA Full Load Amps HACR Heating, Air Conditioning and Refrigeration IFM Indoor (Evaporator) Fan Motor LRA Locked Rotor Amps MCA Minimum Circuit Amps MOCP Maximum Overcurrent Protection NEC National Electrical Code UL Underwriters Laboratories
*Used to determine minimum disconnect per NEC.
Single point box CRSINGLE017A00 is part of base unit.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of volt-
age imbalance.
= 100 x
NOMINAL
V-P H -H z
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-3-60
208/230-3-60
460-3-60
LEGEND
max voltage deviation from average voltage
average voltage
IFM
TYPE
STD NO 9.2 34.8/34.8 40/40 35/35 135/135 STD YES 9.2 40.8/40.8 45/45 41/41 140/140
STD NO 9.2 27.7/27.7 35/35 29/29 124/124
STD YES 9.2 33.7/33.7 40/35 34/34 129/129 HIGH STATIC NO 9.2 28.6/28.6 35/35 30/30 154/154 HIGH STATIC YES 9.2 34.6/34.6 40/40 35/35 158/158
STD NO 9.2 13.6 20 14 63
STD YES 9.2 16.3 20 20 67 HIGH STATIC NO 9.2 14.0 20 15 77 HIGH STATIC YES 9.2 16.7 20 20 82
STD NO 9.2 44.4/44.4 60/60 44/44 173/173
STD YES 9.2 50.4/50.4 60/60 50/50 178/178
STD NO 9.2 31.7/31.7 40/40 33/33 140/140
STD YES 9.2 37.7/37.7 40/40 38/38 145/145 HIGH STATIC NO 9.2 32.6/32.6 40/40 34/34 170/170 HIGH STATIC YES 9.2 38.6/38.6 45/45 39/39 174/174
STD NO 9.2 15.2 20 16 70
STD YES 9.2 17.9 20 21 75 HIGH STATIC NO 9.2 15.6 20 16 84 HIGH STATIC YES 9.2 18.3 20 22 89
STD NO 9.2 55.5/55.5 70/70 56/56 250/250
STD YES 9.2 61.5/61.5 70/70 61/61 255/255
STD NO 9.2 38.1/38.1 45/45 39/39 202/202
STD YES 9.2 44.1/44.1 50/50 44/44 207/207 HIGH STATIC NO 9.2 39.8/39.8 45/45 41/41 221/221 HIGH STATIC YES 9.2 45.8/45.8 50/50 46/46 226/226
STD NO 9.2 19.3 25 20 101
STD YES 9.2 22.0 25 25 106 HIGH STATIC NO 9.2 20.1 25 20 110 HIGH STATIC YES 9.2 22.8 25 26 115
STD NO 9.2 42.0/42.0 50/50 42/42 234/234
STD YES 9.2 48.0/48.0 60/60 48/48 239/239 HIGH STATIC NO 9.2 43.7/43.7 50/50 44/44 253/253
HIGH STATIC YES 9.2 49.7/49.7 60/60 50/50 258/258
STD NO 9.2 19.8 25 20 114
STD YES 9.2 22.5 25 26 118 HIGH STATIC NO 9.2 20.6 25 21 123 HIGH STATIC YES 9.2 23.3 30 26 128
CONV
OUTLET
62AQ
FLA
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
POWER SUPPLY DISCONNECT SIZE*
MCA
FUSE OR
HACR BKR
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
7 457
= 1.53%
452 + 464 + 455
1371
=
3
= 457
FLA LRA
3
IMPORTANT: If the supply voltage phase imbalance is more than 2%, con­tact your local electric utility company immediately.
13
UNIT
50HJ004
50HJ005
Table 1B Electrical Data (COBRA Energy Recovery 50HJ004-007 Units with 62AQ060)
NOMINAL
V-P H- Hz
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60 STD NO 9.2
IFM
TYPE
STD NO 9.2
STD YES 9.2
STD NO 9.2
STD YES 9.2
HIGH STATIC NO 9.2
HIGH STATIC YES 9.2
STD NO 9.2
STD YES 9.2
HIGH STATIC NO 9.2
HIGH STATIC YES 9.2
STD NO 9.2
STD YES 9.2
STD NO 9.2
STD YES 9.2
HIGH STATIC NO 9.2
HIGH STATIC YES 9.2
CONV
OUTLET
HEATER
62AQ
CRHEATER
FLA
---A00
NONE —/— 34.8/ 34.8 40/40 ——35/ 35 135/135
001 15.9/18.3 35.7/ 38.8 40/45 ——35/ 37 135/135 002 23.5/27.1 45.2/ 49.7 50/50 ——43/ 47 135/135 003 31.4/36.3 55.1/ 61.2 60/ 70 004 52/ 58 135/135 004 37.9/43.8 63.2/ 70.5 70/ 80 004 60/ 67 135/135
002+002 46.9/54.2 74.5/ 83.6 80/ 90 005 70/ 79 135/135
NONE —/— 40.8/ 40.8 45/45 ——41/ 41 140/140
001 15.9/18.3 40.8/ 43.0 45/50 ——41/ 42 140/140 002 23.5/27.1 50.0/ 53.9 60/60 ——49/ 52 140/140 003 31.4/36.3 59.9/ 65.4 60/ 70 004 58/ 63 140/140 004 37.9/43.8 68.0/ 74.7 70/ 80 005 65/ 71 140/140
002+002 46.9/54.2 79.3/ 87.8 80/ 90 005 76/ 83 140/140
NONE —/— 27.7/ 27.7 35/35 ——29/ 29 124/124
001 9.2/10.6 27.7/ 29.1 35/35 ——29/ 29 124/124 002 13.6/15.6 32.8/ 35.4 40/40 ——32/ 34 124/124 003 18.1/20.9 38.5/ 42.0 45/45 ——37/ 40 124/124 004 21.9/25.3 43.2/ 47.4 45/50 ——41/ 45 124/124 005 33.4/38.5 57.5/ 64.0 60/ 70 002 55/ 60 124/124
NONE —/— 33.7/ 33.7 40/35 ——34/ 34 129/129
001 9.2/10.6 33.7/ 33.7 40/40 ——34/ 34 129/129 002 13.6/15.6 37.6/ 39.6 45/45 ——37/ 39 129/129 003 18.1/20.9 43.3/ 46.2 50/50 ——43/ 45 129/129 004 21.9/25.3 48.0/ 51.6 50/60 ——47/ 50 129/129 005 33.4/38.5 62.3/ 68.2 70/ 70 002 60/ 65 129/129
NONE —/— 28.6/ 28.6 35/35 ——30/ 30 154/154
001 9.2/10.6 28.6/ 30.0 35/35 ——30/ 30 154/154 002 13.6/15.6 33.7/ 36.3 40/40 ——33/ 35 154/154 003 18.1/20.9 39.4/ 42.9 45/45 ——38/ 41 154/154 004 21.9/25.3 44.1/ 48.3 50/50 ——42/ 46 154/154 005 33.4/38.5 58.4/ 64.9 60/ 70 002 56/ 62 154/154
NONE —/— 34.6/ 34.6 40/40 ——35/ 35 158/158
001 9.2/10.6 34.6/ 34.6 40/40 ——35/ 35 158/158 002 13.6/15.6 38.5/ 40.5 45/45 ——38/ 40 158/158 003 18.1/20.9 44.2/ 47.1 50/50 ——44/ 46 158/158 004 21.9/25.3 48.9/ 52.5 60/60 ——48/ 51 158/158 005 33.4/38.5 63.2/ 69.1 70/ 70 003 61/ 66 158/158
NONE 13.6 20 —— 14 63
006 7.2 16.7 20 —— 14 63 007 10.6 20.9 25 —— 15 63 008 13.8 25.0 25 —— 24 63 009 16.8 28.7 30 —— 27 63
NONE 16.3 20 —— 20 67
006 7.2 18.8 25 —— 20 68 007 10.6 23.0 25 —— 20 68 008 13.8 27.1 30 —— 29 68 009 16.8 30.8 35 —— 32 68
NONE 14.0 20 —— 15 77
006 7.2 17.1 20 —— 15 77 007 10.6 21.3 25 —— 15 77 008 13.8 25.4 30 —— 24 77 009 16.8 29.1 30 —— 28 77
NONE 16.7 20 —— 20 82
006 7.2 19.2 25 —— 20 82 007 10.6 23.4 25 —— 20 82 008 13.8 27.5 30 —— 29 82 009 16.8 31.2 35 —— 32 82
NONE —/— 44.4/ 44.4 60/60 ——44/ 44 173/173
001 15.9/18.3 44.4/ 44.4 60/60 ——44/ 44 173/173
003 31.4/36.3 55.1/ 61.2 60/ 70 004 52/ 58 173/173 002+002 46.9/54.2 74.5/ 83.6 80/ 90 005 70/ 79 173/173 003+003 62.8/72.5 94.4/106.5 100/110 005 88/100 173/173 004+004 75.8/87.5 110.6/125.2 125/150 005 103/117 173/173
NONE —/— 50.4/ 50.4 60/60 ——50/ 50 178/178
001 15.9/18.3 50.4/ 50.4 60/60 ——50/ 50 178/178
003 31.4/36.3 59.9/ 65.4 60/ 70 004 58/ 63 178/178 002+002 46.9/54.2 79.3/ 87.8 80/ 90 005 76/ 83 178/178 003+003 62.8/72.5 99.2/110.7 100/125 005 94/104 178/178 004+004 75.8/87.5 115.4/129.4 125/150 005 109/122 178/178
NONE —/— 31.7/ 31.7 40/40 ——33/ 33 140/140
002 13.6/15.6 32.8/ 35.4 40/40 ——33/ 34 140/140
003 18.1/20.9 38.5/ 42.0 45/45 ——37/ 40 140/140
005 33.4/38.5 57.5/ 64.0 60/ 70 002 55/ 60 140/140 004+004 43.8/50.5 70.6/ 79.0 80/ 80 003 67/ 74 140/140
NONE —/— 37.7/ 37.7 40/40 ——38/ 38 145/145
002 13.6/15.6 37.7/ 39.6 45/45 ——38/ 39 145/145
003 18.1/20.9 43.3/ 46.2 50/50 ——43/ 45 145/145
005 33.4/38.5 62.3/ 68.2 70/ 70 002 60/ 65 145/145 004+004 43.8/50.5 75.4/ 83.2 80/ 90 003 72/ 79 145/145
NONE —/— 32.6/ 32.6 40/40 ——34/ 34 170/170
002 13.6/15.6 33.7/ 36.3 40/40 ——34/ 35 170/170
003 18.1/20.9 39.4/ 42.9 45/45 ——38/ 41 170/170
005 33.4/38.5 58.4/ 64.9 60/ 70 002 56/ 62 170/170 004+004 43.8/50.5 71.5/ 79.9 80/ 80 003 68/ 75 170/170
NONE —/— 38.6/ 38.6 45/45 ——39/ 39 174/174
002 13.6/15.6 38.6/ 40.5 45/45 ——39/ 40 174/174
003 18.1/20.9 44.2/ 47.1 50/50 ——44/ 46 174/174
005 33.4/38.5 63.2/ 69.1 70/ 70 003 61/ 66 174/174 004+004 43.8/50.5 76.3/ 84.1 80/ 90 003 73/ 80 174/174
NONE 15.2 20 —— 16 70
006 7.2 16.7 20 —— 16 71
008 13.8 25.0 25 —— 18 71
009 16.8 28.7 30 —— 27 71 008+008 27.7 42.3 45 025 40 71
HEAT POWER SUPPLY SINGLE
FLA MCA
FUSE OR
HACR BKR
POINT BOX
MOCP FLA LRA
CRSINGLE
---A00
DISCONNECT SIZE*
14
Loading...
+ 30 hidden pages