Air-handling equipment will provide safe and reliable
service when operated within design specifications. The
equipment should be operated and serviced only by
authorized personnel who have a thorough knowledge
of system operation, safety devices, and emergency
procedures.
Good judgement should be used in applying any manufacturer’s instructions to avoid injury to personnel or
damage to equipment and property.
Disconnect all power to the unit before performing maintenance or service. Unit may automatically start if power is
not disconnected. Electrical shock and personal injury
could result.
If it is necessary to remove and dispose of mercury contactors in electric heat section, follow all local, state, and federal laws regarding disposal of equipment containing
hazardous materials.
General —
45M,N,R variable volume (parallel) fan powered boxes (see
Fig. 1 and 2) can be equipped to provide pressure independent,
variable volume (VAV). All units can also be equipped with
factory-installed analog electronic, pneumatic, or ComfortID™
variable air volume (VAV) controls. The 45M,N,R units can be
equipped with 3V™ variable volume and temperature (VVT)
controls. Units are available with factory-installed electric or
hot water heat.
SAFETY CONSIDERATIONS
SAFETY NOTE
WARNING
WARNING
PRE-INSTALLATION
The 45J,K,Q constant volume (series) and
Fig. 1 — Series Flow Unit (45K Shown)
Fig. 2 — Parallel Fan Unit (45J Shown)
The 45J,M units are standard fan powered terminal units.
The 45K,N units are quiet fan powered terminal units. The
45Q,R units are low profile fan powered terminal units.
CONTROL OFFERINGS — Each 45J, 45K, 45M, 45N, 45Q,
45R unit is supplied with a linear averaging flow probe as a
standard feature. This probe offers a flow averaging capability
and results in flow sensing capacity equal to any competitive
unit.
Control options include ComfortID™ VAV, 3V variable
volume and temperature (VVT®), analog electronic and pressure-independent pneumatic. Both 3V and ComfortID controls
are communicating controls that are compatible with the Carrier Comfort Network® (CCN) network. The 3V VVT controls
are for 45M,N,R units only.
Pneumatic controls are available with linear actuators and
single-function or multi-function controller. The multi-function
controller provides a simple switchover from normally open to
normally closed applications.
Electronic control units feature a factory-installed enclosure
that provides easy access for field connections.
STORAGE AND HANDLING — Inspect for damage upon
receipt. Shipping damage claims should be filed with shipper at
time of delivery. Store in a clean, dry, and covered location. Do
not stack units. When unpacking units, care should be taken
that the inlet collars and externally mounted components do not
become damaged. Do not lift units using collars, sensors, or externally mounted components as handles. If a unit is supplied
with electric or hot water heat, care should be taken to prevent
damage to these devices. Do not lay uncrated units on end or
sides. Do not stack uncrated units over 6 ft high. Do not manhandle. Do not handle control boxes by tubing connections or
other external attachments. Table 1 shows component weights.
INITIAL INSPECTION — Once items have been removed
from packing, check carefully for damage to duct connections,
coils, or controls. File damage claim immediately with transportation agency and notify Carrier.
NOTE: Remove all packaging material and foreign material
from unit and ensure the blower wheel moves freely before
installation. Units are shipped with cardboard in both sides of
the fan inlet that MUST be removed.
Unit Identification — Each unit has 2 main labels at-
tached to the casing. The FAN UNIT label (Fig. 3) lists the
model number, supply voltage requirements, motor horsepower and overcurrent protection requirements. The AIRFLOW
label (Fig. 4) lists the model number, unit size, factory order
number and location. The location “tag” indicates where the
unit is intended for installation. There may be other labels attached to the unit, as options or codes may require. Read all
labels on a typical unit before attempting installation. Control
boxes are assembled as indicated on the identification label.
Contact your local Carrier representative for more
information.
INSTALLATION PRECAUTION — Check that construction
debris does not enter unit or ductwork. Do not operate the
central-station air-handling fan without final or construction
filters in place. Accumulated dust and construction debris
distributed through the ductwork can adversely affect unit
operation.
SERVICE ACCESS — Provide service clearance for unit
access (see Installation section for details).
CODES — Install units in compliance with all applicable code
requirements.
UNIT SUSPENSION — See Installation section for unit suspension details.
Warranty — All Carrier-furnished items carry the standard
The units are offered with a wide variety of factorymounted controls that regulate the volume of air delivery from
the unit and respond to cooling and heating load requirements
of the conditioned space. All control packages can operate
stand-alone and will fulfill the thermal requirements of a given
control space. These devices are available in both pneumatic
and electronic arrangements. The 3V™ and ComfortID™ control types are communicating controls which can be integrated
into a CCN building system. A number of DDC (direct digital
control) control packages by others are available for consignment mounting as indicated.
Control offerings are:
A: Analog Electronic
C: ComfortID™, VAV
P: Pneumatic
V: 3V™, VVT® (45M,N,R units only)
N: None or DDC by others
Each control approach offers a variety of operating functions; a control package number identifies combinations of
control functions. Because of the variety of functions available,
circuit diagrams, operating sequences, and function descriptions are contained in separate Application Data publications.
Refer to the specific control publication for details.
ComfortID™ VAV Controls — Pressure independent
control packages are available with or without heat. These controls provide occupied and unoccupied heating and cooling, demand controlled ventilation (DCV), and zone humidity control.
They can be networked together via the CCN network to provide integrated system operation of all components, including
the operation of air source equipment. These controls may be
used in a stand-alone terminal, or as part of the Carrier DDC
control system. All control arrangements include a standard
linear inlet flow sensor, control enclosure, SCR (silicone control rectifier) fan speed controller, class II 24-volt power transformer, and fan contactor. Several types of room sensors may
be ordered, with and without set point adjustment, and with integral CO
CONTROL ARRANGEMENTS — ComfortID control packages must be used in combination with a thermostat. Thermostats are not included in the package and are ordered separately.
See Tables 2A and 2B.
Table 2A — ComfortID VAV Control Arrangements
PACKAGE
SSR — Solid-State Relay
Table 2B — ComfortID VAV Control Arrangements
sensors.
2
— 45JC,KC,QC Series Terminals
NO.
4440No heat (or field supplied baseboard heat)
4442Cooling with up to 3 stage electric heat
4443Cooling with On-Off hot water
4444Cooling with proportional (floating) hot water
4452Cooling with 1 to 3 stage field-installed electric heat
4454Cooling with Proportional SSR electric heat
with override only.
Thermostat: 33ZCT56SPT: RT (room temperature) sensor,
with set point adjust and override.
Thermostat: 33ZCT58SPT: Communicating room tempera-
ture sensor with LCD, set point adjust, fan control, and override.
Inlet Air Temperature Sensor: 33ZCSENPAT (required only if
linkage unavailable)
NOTE: The 33ZCSENSAT supply air temperature sensor is
included with the controls package. Field-installed VVT components such as thermostats and bypass controllers must still
be ordered separately and shipped to the job site.
3V™ VVT® Controls — Pressure dependent control
packages are available with or without hot water (on-off control), electric heat (up to 2 stages), or SSR (solid-state relay)
electric heat. They are designed to be an integral part of the
Carrier 3V, VVT control system, for parallel flow units only.
All control arrangements include a standard linear inlet flow
sensor, control enclosure, SCR fan speed controller, 24-volt
transformer and fan relay. The 3V, VVT terminals are not
available on series terminal units.
The 3V, VVT packages must be used in conjunction with a
VVT compatible thermostat. Field-installed thermostats are
not included and must be ordered separately. See Table 3.
Table 3 — 3V, VVT Control Arrangements
— 45MV,NV,RV Parallel Terminals
PACKAGE
NO.
8815Pressure dependent, cooling only
8818
8819
8820
8825
8829
8830
Pressure dependent, cooling with on-off hot
water reheat
Pressure dependent, cooling with 3-stage electric
heat
Pressure dependent, cooling with modulating hot
water reheat
Pressure dependent, cooling with combination
baseboard and ducted reheat
Pressure dependent, cooling with 1 to 3 stage
field-installed electric heat
Pressure dependent, cooling with Proportional
SSR electric heat
DESCRIPTION
Analog Electronic Controls — Pressure independent
control packages are available with or without hot water or
electric heat, automatic or remote night shutdown, and automatic night setback. All control arrangements include a
standard linear inlet flow sensor, control enclosure, SCR fan
speed controller, 24-volt transformer, fan relay, and wall thermostat to match the control type. See Tables 4A and 4B.
PACKAGE
NO.
4740No heat (or field supplied baseboard heat)
4742Cooling with up to 3 stage electric heat
4743Cooling with On-Off hot water
4744Cooling with proportional (floating) hot water
4752Cooling with 1 to 3 stage field-installed electric heat
4754Cooling with Proportional SSR electric heat
SSR — Solid-State Relay
DESCRIPTION
4
Table 4A — Analog Electronic Control
Arrangements — 45JA,KA,QA Series Terminals
PACKAGE
NO.
2200Cooling only
2201Cooling only with automatic night shutdown
2202Cooling only with remote night shutdown
2203Cooling only with automatic night setback
2204Cooling with on/off hot water heat
2205Cooling with on/off hot water heat and automatic night
2206Cooling with on/off hot water heat and remote night
2207Cooling with on/off hot water heat and automatic night
2208Cooling with proportional hot water heat
2209Cooling with proportional hot water heat and automatic
2210Cooling with proportional hot water heat and remote
2211Cooling with proportional hot water heat and automatic
2212Cooling with up to 2 stages of electric heat
2213Cooling with up to 2 stages of electric heat and auto-
2214Cooling with up to 2 stages of electric heat and remote
2215Cooling with up to 2 stages of electric heat and auto-
2216Cooling with up to 2 stages of electric heat, cooling/
2218Cooling with proportional electric heat
shutdown
shutdown
setback
night shutdown
night shutdown
night setback
matic night shutdown
night shutdown
matic night setback a variety of pressures
heating automatic change over control (morning warmup) and automatic night setback
DESCRIPTION
Table 4B — Analog Electronic Control
Arrangements — 45MA,NA,RA Parallel Terminals
PACKAGE
NO.
2300Cooling with sequenced fan
2301Cooling with sequenced fan and auto. night shutdown
2302Cooling with sequenced fan and auto. night setback
2303Cooling with sequenced fan and on/off hot water heat
2304Cooling with sequenced fan and on/off hot water heat
2305Cooling with sequenced fan and on/off hot water heat
2306Cooling with sequenced fan and proportional hot water
2307Cooling with sequenced fan proportional hot water heat
2308Cooling with sequenced fan proportional hot water heat
2309Cooling with sequenced fan and up to 2 stages of elec-
2310Cooling with sequenced fan up to 2 stages of electric
2311Cooling with sequenced fan up to 2 stages of electric
2313Cooling with sequenced fan and proportional electric
and auto. night shutdown
and auto. night setback
heat
and auto. night shutdown
and auto. night setback
tric heat
heat and auto. night shutdown
heat and auto. night setback
heat
DESCRIPTION
Pneumatic Controls — Pressure independent control
packages are available with or without hot water or electric
heat, night shutdown and/or unoccupied heating. All control arrangements include a standard linear inlet flow sensor and SCR
fan speed controller. See Tables 5A and 5B.
Single function controller: Provides single function,
i.e., DA-NO.
Multi-function controller: Capable of providing DA-NO,
DA-NC, RA-NC or RA-NO functions.
Table 5A — Pneumatic Control Arrangements —
45JP,KP,QP Series Terminals
PACKAGE
NO.
1300Single function controller; DA-NO with or without hot
1301Single function controller; DA-NO with or without hot
1302Single function controller; DA-NO with or without hot
1303Single function controller; RA-NC with or without hot
1304Single function controller; RA-NC with or without hot
1305Single function controller; RA-NC with or without hot
1306Multi-function controller; DA-NO with or without hot
1307Multi-function controller; DA-NO with or without hot
1308Multi-function controller; DA-NO with or without hot
1309Multi-function controller; DA-NC with or without hot
1310Multi-function controller; DA-NC with or without hot
1311Multi-function controller; DA-NC with or without hot
1312Multi-function controller; RA-NC with or without hot
1313Multi-function controller; RA-NC with or without hot
1314Multi-function controller; RA-NC with or without hot
1315Multi-function controller; RA-NO with or without hot
1316Multi-function controller; RA-NO with or without hot
1317Multi-function controller; RA-NO with or without hot
water or electric heat
water or electric heat and with night shutdown
water or electric heat, with night shutdown and unoccupied heating
water or electric heat
water or electric heat and with night shutdown
water or electric heat, with night shutdown and unoccupied heating
water or electric heat
water or electric heat and with night shutdown
water or electric heat, with night shutdown and unoccupied heating
water or electric heat
water or electric heat and with night shutdown
water or electric heat, with night shutdown and unoccupied heating
water or electric heat
water or electric heat and with night shutdown
water or electric heat, with night shutdown and unoccupied heating
water or electric heat
water or electric heat and with night shutdown
water or electric heat, with night shutdown and unoccupied heating
DESCRIPTION
Table 5B — Pneumatic Control Arrangements —
45MP,NP,RP Parallel Terminals
PACKAGE
NO.
14001 function DA-NO with or without optional heat
14011 function RA-NC with or without optional heat
14024 function DA-NO with or without optional heat
14034 function RA-NO with or without optional heat
14044 function DA-NC with or without optional heat
14054 function RA-NC with or without optional heat
LEGEND
DA — Direct Acting Thermostat
RA — Reverse Acting Thermostat
NO — Normally Open Damper Position
NC — Normally Closed Damper Position
DESCRIPTION
No Controls or Direct Digital Controls (By Others) — Control sequences are available for factory installa-
tion of numerous field-supplied controls from various manufacturers including: Andover, Automated Logic, Invensys (Siebe), Siemans (Landis), Johnson, and others. All packages include a standard liner inlet flow sensor, control enclosure, SCR
fan speed controller, 24-v transformer, and fan relay.
Contact Carrier for information on mounting field-supplied
controls.
5
NO CONTROL UNITS — Control sequences are also available to provide a control box on units supplied with no factoryinstalled controls. These arrangements include a standard
linear inlet flow sensor, control enclosure, SCR fan speed control, 24-v transformer, and fan relay. See Table 6.
Table 6 — No Control Arrangements —
45JN,MN,KN,NN,QN,RN Terminals
PACKAGE
NO.
D000Field supplied and mounted controls by others. (For
D001Field supplied and mounted controls by others. (For
units without electric heat, includes Class II for 24-volt
power transformer.)
units with electric heat that already include a transformer.)
DESCRIPTION
INSTALLATION
Step 1 — Install Fan-Powered Box
SELECT LOCATION
1. Units should be installed so that they do not come in contact with obstacles such as rigid conduit, sprinkler piping,
Greenfield flexible metal covering, or rigid pneumatic
tubing; such contact can transmit vibration to the building
structure, causing objectionable low frequency noise.
2. Units should never be installed tight against concrete
slabs or columns, as vibration transmission is amplified in
this condition.
3. Fan powered terminals require sufficient clearance for
servicing the blower/motor assembly from the bottom of
the unit, low voltage controls from the side and line voltage motor controls or electric heat (if equipped) from the
rear (discharge end) of the unit.
Bottom access panel removal requires a minimum of 3 in.
minimum clearance, plus substantial horizontal clearance
to slide the access panel out of the way for service. Actual
horizontal dimensions will vary due to varying access
panels for different sized units. See your particular unit’s
submittal drawings for more detail.
NOTE: Be certain appropriate accommodations for panel
removal of most unit casings are large enough to allow
adequate internal service room once the panels are
removed.
A clearance of 18 in. is recommended for control enclosure access. Unit control enclosure will vary depending
on which control package is used. Control enclosure location is specified on unit submittals. Low voltage enclosure covers are removable, not hinged.
A clearance of 36 in. is recommended for line voltage
motor controls and electric heat control access. Highvoltage motor controls or electric heat control access is
supplied with hinged access doors for units with fused
disconnect. Specific location is indicated on the unit
submittal.
NOTE: These recommendations do not supersede NEC
(National Electrical Code) or local codes that may be
applicable, which are the responsibility of the installing
contractor.
4. Whenever possible, fan-powered boxes should be
installed over halls or passageways (rather than over
occupied spaces) in order to limit the sound reaching
occupants.
POSITION UNIT
1. When moving boxes, use appropriate material handling
equipment and avoid contact with shaft extensions, controls, wiring, piping, heaters, and control boxes.
2. Raise unit to position using safe mechanical equipment
and support until hanging means are attached and box is
level.
INSTALL UNIT
1. Install field-supplied eye bolts, strap hangers or bolt rod
supports as desired. Figure 5 illustrates possible unit suspension methods. A typical installation is shown in Fig. 6.
2. Care should be taken to use hanging materials of sufficient stiffness and strength, rigidly attached to the unit.
Straps should not be located on coil flanges, electric heat
sections, or control boxes. When using trapeze supports,
avoid areas where access is required to side mounted controls, or side or bottom access doors. For best installation
with trapeze supports, provide elastomeric material between unit and supports.
3. Hangers should be securely attached to bar joist or
mounting anchors properly secured to building structure
with lugs or poured-in-place hangers. Percussion nails are
not considered adequate anchors.
Step 2 — Make Duct Connections
1. Check that the pressure pick-up in primary air collar is
located properly and that air supply duct connections are
airtight. Install supply ductwork on unit inlet collar, following all accepted medium-pressure duct installation
procedures. Seal joints against leakage.
NOTE: For maximum efficiency in controlling radiated
noise in critical applications, inlet ducts should be fabricated of 24-gage minimum sheet metal in place of flex
connections. Flex duct is extremely transparent to radiated sound; consequently high inlet statics (Ps) or sharp
bends with excessive pressure drop can cause a radiated
noise problem in the space. If flex duct is used, it should
be limited to the connection between the distribution duct
and the boot diffuser.
2. Install the discharge duct, being careful not to reduce the
face area of any electric heat section until several diameters away from the unit. It is strongly recommended that
lined discharge duct be used downstream of the unit. Insulate duct as required.
3. Fan boxes should not be attached to octopus sections immediately downstream of the unit.
4. Install optional return-air filters before operating the unit.
5. Where construction filters were supplied with the box,
leave filters in place until installation is complete and
building is cleaned for occupancy.
Step 3 — Connect Power Wiring — See Fig. 7.
1. All power wiring must comply with local codes and with
the NEC (National Electrical Code) ANSI/NFPA (American National Standards Institute/National Fire Protection
Association) 70-1981. Disconnect switches are optional
equipment. Electrical, control and piping diagrams are
shown on the exterior labeling or on a diagram inside the
control and high-voltage enclosure covers, unless otherwise specified in the order write-up. All units are wired
for a single point electrical connection to the fan and electric heater (if equipped). Electric heaters provided by Carrier are balanced by kW per stage. The installing electrician should rotate incoming electric service by phase to
help balance overall building load.
6
OPTIONAL
ACCESSORY
HANGER
FIELD-SUPPLIED
HANGER
BRACKET
FIELD-SUPPLIED
HANGING STRAPS
Fig. 5 — Typical Unit Suspension Methods (45K Shown)
DO NOT suspend unit
by trapeze hangers
that interfere with the
unit access panel.
AFS — Airflow Switch
CAP — Capacitor
SCR — Silicone Control Rectifier
Fig. 7 — Typical Power Connections for Fan Powered Units with 3-Stage Electric Heat
2. All field wiring must be provided with a safety disconnect per NEC 424-19, 20, and 21.
3. Disconnect all incoming power before wiring or servicing
unit. All disconnect switches on the terminal (if
equipped) should be in the OFF position while making
power connections.
4. Units with electric heat should use copper wires rated at
least 125% of rating plate amperage. Refer to the unit’s
rating label and minimum supply circuit amps.
5. Observe wiring diagram and instructions attached to the
unit. The 480-v, 3-phase units require a Wye power
source with a fourth (neutral) wire in addition to the full
sized ground wire. All units must be grounded as required
by NEC 424-14 and 250.
Step 4 — Set Up System and Calibrate
GENERAL — The parallel fan powered terminals (45K and
45N) are designed to provide varying quantities of cold
primary air to a space in response to a thermostat demand for
cooling. For a heating demand, the fan will operate to supply
ceiling plenum air to the space. For units equipped with a heating coil, the heater will operate as required to meet a heating
demand.
The series fan powered terminals (45J and 45M) are designed to provide a constant airflow to the space. The air
supplied to the space is a mixture of primary air and ceiling
plenum air. The fan speed is adjusted to provide the required
airflow to the space. In response to a cooling demand from a
thermostat, the damper will increase the amount of cold primary air while reducing the amount of ceiling plenum air to
decrease the temperature of the air being delivered to the space.
Most terminal control packages provide pressure compensation to allow pressure independent operation of the primary
air damper, regardless of changes to the available static pressure in the supply ductwork. To balance the unit it is necessary
to set both the minimum and maximum airflow set points of
the controller. The many types of control options available each
have specific procedures required for balancing. Refer to the
submittal information for these requirements.
SET POINTS — Maximum and minimum airflow set points
are normally specified for the job and specific for each unit on
the job. Default set point values are provided by the factory and
can be reset to the specific requirements in the field. The fan
speed must be field adjusted after all discharge ductwork and
diffusers have been installed.
Field Adjustment of the Maximum and Minimum Airflow
Set Points — Each fan powered terminals unit is equipped
with a flow probe installed in the primary air inlet which measures a differential pressure. The relationship between the
airflow probe pressure and the corresponding airflow is shown
in the Flow Probe Graph. See Fig. 8. This chart is attached to
each unit.
SYSTEM CALIBRATION OF THE LINEAR AVERAGING
FLOW PROBE — To achieve efficient pressure independent
operation, the velocity sensor and linear averaging flow probe
must be calibrated to the controller. This will ensure that airflow will be accurate for all terminals at system start-up.
System calibration is accomplished by calculating a flow
coefficient that adjusts the pressure fpm characteristics. The
flow coefficient is determined by dividing the flow for a given
unit (design air volume in cfm), at a different velocity pressure
of 1.0 in. wg, by the standard pitot tube coefficient of 4005.
This ratio is the same for all sizes, if the standard averaging
probe is used.
8
10000
8000
6000
4000
2000
1000
800
600
400
CFM
200
100
80
60
40
20
10
0.01.03
INLET SIZE 16
INLET SIZE 14
INLET SIZE 12
INLET SIZE 10
INLET SIZE 08
INLET SIZE 06
.05
FLOW PROBE PRESSURE DIFFERENTIAL IN. WG
0.1
0.30.5
Fig. 8 — Linear Probe CFM vs Signal Chart
1
3709
2840
2086
1449
927
CFM @ ONE INCH SIGNAL
522
Determine the design air velocity by dividing the design air
volume (the flow at 1.0 in. wg) by the nominal inlet area (sq ft).
This factor is the K factor.
Carrier inlet areas are shown in Table 7. The design air
volume is shown. It can be determined from Table 7 that the
average design air velocity for units is equal to 0.2656 fpm at
1.0-in. wg.
Table 7 — Inlet Areas — 45J,K,M,N,Q,R
INLET
DIAMETER (in.)
Cfm at
1 in. wg
Inlet Area
(sq ft)
NOTE: For ComfortID™ terminals, all flow sizes are normalized
using a single probe multiplier (PMF) for all sizes equal to 2.273.
6.08.010.012.014.016.0
5229271449 2086 2840 3709
0.196 0.349 0.545 0.785 1.069 1.396
START-UP
General —
must be operating in accordance with the specifications for air
capacity, static pressure, and temperature. Record data on a unit
performance sheet (Fig. 9). The following items must be
checked:
1. All fans must be running at calculated and specified rpm.
2. Permanent or temporary filters must be clean and installed where required.
3. All central station dampers must be adjusted and operating properly.
4. All thermostats must be calibrated and at the desired
settings.
Before balancing the system, the air handlers
5. All ductwork must be tight.
6. All dirt or loose lining must be removed from inside
ductwork.
7. Pumps and sprays, when used, must be in operation.
8. Connections to the coil, when used, must be checked.
9. Water control valve, if used, must be checked.
IMPORTANT: Before proceeding with start-up, be certain that voltage, frequency, and phase correspond to
unit specifications. Unless noted, all fan motors are
60 Hz, 115, 208/230, or 277 v, single-phase ac.
NOTE: All 45 Series terminal units are shipped with cardboard
packaging restraints placed inside both sides of the blower
housing internal to the blower/motor. These restraints are provided to prevent damage to the motor during shipment. The
restraints MUST BE REMOVED prior to operation.
Remove the bottom access panel to remove the cardboard
packing material.
Carrier Corporation will not accept responsibility for any
additional costs for removal of this packaging material.
Initial Start-Up Procedures
NOTE: The following steps MUST be followed in order to
properly operate and service this unit.
1. Disconnect all electrical power to the unit. Failure to disconnect the power to the fan box prior to checking and/or
servicing the fan box could result in a serious injury.
2. Verify that the fan box is installed level, and that adequate
mounting support has been provided.
3. Remove motor access panel from the bottom of the fan
box, and also remove the control panel cover.
9
4. Test the fan motor setscrew. The setscrew should fit
tightly, but it may have come loose during shipment or
installation.
5. Rotate the blower by hand to ensure proper clearance between the blower and the blower housing.
6. Check the fan box for loose fiberglass insulation, especially on the electric heater elements or the hot water coils
(if these accessories are installed).
7. Check the control enclosure and remove any debris.
8. Check the induction inlet filter (if provided) for obstructions, and verify the filter is securely in place.
9. Verify the main power supply to the connection to the fan
box for proper voltage. If the fan box is installed with
electric heat, the electric heat voltage may exceed the
blower motor voltage requirement. Excessive voltage to
the fan box may seriously damage it. Verify that the DDC
(if equipped) are receiving 24-v ac, –15%, +20%.
10. Identify the control system supplied.
11. Check all control connections (and/or electric) for proper
installation.
12. Connect electrical power.
Balancing Carrier Fan Terminals — Carrier fan
terminal units contain primary air dampers which, under the
control of a volume controller, regulate the amount of cold air
distributed to the space.
45J,K,Q SERIES FLOW UNITS — The 45J,K,Q series flow
terminals direct all primary air through the unit fan. The terminal is designed to operate with the fan supplying airflow equal
to or greater than the airflow supplied by the VAV damper. To
balance the unit, therefore, it is necessary to first set the fan
flow, and then the VAV damper (primary) flow.
Each control option has specific procedures required for
balancing the unit, but some steps are common to all 45J,K,Q
units. The fan box adjustments described below must be made
in conjunction with the adjustments described in the Speed
Controller section.
The VAV damper airflow may be set at the factory, but the
fan airflow must be set in the field as described below.
Setting Fan Airflow
NOTE: If the unit has electric heat or hot water heat, tempo-
rarily disable these functions before balancing the fan.
If unit has optional electric heat disconnect downstream of
fan motor connections to power, open disconnect.
If unit does not have optional electric heat disconnect, remove one electric heat power line connection. Be sure to
insulate loose line from ground wire or other wires.
1. Set the controller to provide heating airflow demand only.
Typically, this is accomplished by setting the thermostat
to the highest possible temperature setting.
2. Determine that the VAV valve is fully closed and that the
fan is rotating in the proper direction. (If the VAV damper
is open when the fan is started and there is primary air in
the system, the fan may start and run backward.)
3. Using a flow hood or duct traverse, determine the delivered fan airflow (cfm).
NOTE: Both flow hood and duct traverse are subject to
measurement errors. Be sure that all applicable measurement precautions are taken.
4. Compare the actual cfm in heating mode to the designed
airflow. If there is a minimum setting for the VAV damper
in heating mode (as recommended by ASHRAE [American Society of Heating, Refrigeration, and Air
Conditioning Engineers] Standard 62), this quantity is included in the total measured heating airflow to determine
if the desired induction airflow level has been met.
5. Adjust the fan SCR at unit control box to achieve the
desired airflow rate. Refer to the performance data tables
(Tables 8-10) to ensure airflow through electric heaters
meets the requirements before operating the heater.
Setting of VAV (Primary) Airflow
Adjustment of Set Points — Each 45J, 45K, and 45Q supplied
with controls is equipped with a pneumatic or electronic volume controller which regulates the quantity of cold primary air
entering the terminal and the conditioned space. If required airflow levels are specified with the job order, the minimum and
maximum cfm levels will be set at the factory where applicable. If minimum and maximum levels are not specified, a
default value of 0 is used for minimum setting at the factory.
Other settings of minimum and maximum primary airflow
must be set in the field. Airflow (cfm) ranges for the primary
air damper are shown in Tables 8-10. The minimum primary
airflow (other than zero) is the minimum flow rate controllable
by the unit volume controller. The primary air damper can be
set at zero for shutoff or at the minimum cfm listed.
Field Adjustment of Minimum and Maximum Airflow Set
Points — Each 45J, 45K, and 45Q unit is equipped with a lin-
ear averaging flow probe which provides an amplified differential pressure that is proportional to the unit airflow. Output
from this probe is used to provide a flow signal to both pneumatic and electronic controls. Unit airflow (cfm) can be read
directly from the flow probe on the unit (refer to Fig. 8).
1. With the unit airflow from the fan set, turn on primary
(VAV) air supply.
2. To set cfm in the field, connect a gage to the flow probe at
the provided ‘T’ taps, and check the differential pressure.
(Alternately, the total flow may be measured, and the previously determined fan induction flow rate may be subtracted from the total flow to determine VAV flow.
However, for low primary settings, this may not be as
accurate as the flow tap method.)
3. If a minimum VAV flow is required in heating mode, adjust the volume until the differential pressure corresponds
to the cfm required.
4. Set the controller to provide maximum cooling demand.
This is typically accomplished by first setting the thermostat to the lowest possible temperature setting.
a. In most series fan boxes, the primary airflow rate is
equal to the fan induction flow; in these cases,
adjust the volume controller until a balance is
achieved between fan induced airflow and primary
airflow. When a balance exists, a strip of paper
hung at the induction port should hang straight
down, and neither be blown in or out of the unit.
b. If the VAV airflow desired is less than the fan
induction flow, adjust the volume controller until
the differential pressure (measured through the
flow probe as described above) corresponds to the
cfm required. Verify that induction exists through
the inlet ports, using the paper strips as described
above. When induction exists, the paper strip
should be pulled into the unit.
5. Return all reheat options to normal connections.
6. Cap the ‘T’ taps.
7. Reset the thermostat to a normal setting.
NOTE: It is normal for the total airflow to the room to in-
crease slightly in full cooling mode.
10
AIR TERMINAL PERFORMANCE SHEET
JOB NAME ________________________________________
JOB LOCATION ____________________________________
CUSTOMER ________________________________________
ENGINEER ________________________________________
BUILDING LOCATION/FLOOR ________________________
BUS NUMBER ______________________________________
CONTROLSET POINTS
Tag
Number
Zone
Address #
Box
Size
(in./cfm)
Cooling
(Cfm)
minmaxminmaxTypeBtuminmaxminmaxmult.
Fan
cfm
Heating
(Cfm)
HeatkWOccupiedUnoccupied
Calibration
Gain
Fig. 9 — Air Terminal Performance Sheet
11
Table 8 — 45J Series Fan Powered Terminal Unit Performance
UNIT
SIZE
45J
INLET
SIZE
(in.)
26
3
4
5
6
6
8990300920170 or 093 or 0
8
1014405501430250 or 0145 or 0
10
12210011002060360 or 0210 or 0
12
14253012002530500 or 0285 or 0
7*16(2)
MOTOR
HP
1
/
10
1
/
4
1
/
4
1
/
2
3
/
4
3
/
120V208/240V277VMaxMinMaxMin
1.81.00.756010051590 or 052 or 0
3.62.01.5
5.02.82.1
8.34.63.5
9.55.84.4
N/A13.29.9390021003660650 or 0370 or 0
4
MOTOR
AMPS
LEGEND
ASHRAE— American Society of Heating, Refrigeration and Air
DDC— Direct Digital Controls
Conditioning Engineers
*45J unit size 7 is not available with 120 v motor option.
NOTES:
1. 45J maximum primary airflow (cfm) is set by the maximum
induced airflow, which may vary as a function of downstream
pressure. Maximum airflow shown is based on the maximum
induced airflow (fan airflow) or 1.00 in. wg velocity pressure at
inlet probe, whichever is less.
2. Minimum recommended primary airflow (cfm) is based on
0.03 in. wg differential pressure of the linear inlet flow sensor,
or 0 airflow. 0.03 in. wg is equal to 15% to 20% of the nominal
FAN AIRFLOW (cfm)PRIMARY AIRFLOW (cfm)
Min
ComfortID
99030051590 or 052 or 0
1440550920170 or 093 or 0
210011001430250 or 0145 or 0
253012002060360 or 0210 or 0
flow rating of the terminal. Less than 15% to 20% may result in
greater than +5% control of box flow.
3. 45J maximum fan airflow is based on 0.10 in. wg downstream
static pressure.
4. 45J minimum fan airflow (cfm) is based on maximum external
(downstream) static pressure 0.60 in. wg.
5. Minimum primary airflow (cfm) listed is for all controls except
ComfortID controls which is shown separately with lower available minimum cfm. Some DDC controls supplied by others may
have different limitations.
6. Do not select discharge temperature exceeding 120 F. In addition, ASHRAE recommends a maximum discharge temperature of 90 F to avoid room air stratification when heating from
the ceiling (2001 Fundamentals, Chapter 32).
Table 9A — 45K Quiet Series Fan Powered Terminal Unit Performance (PSC Motor)
UNIT
SIZE
45K
2
3
4
5
6
7
ARI — Air Conditioning and Refrigeration Institute
DDC — Direct Digital Controls
FLA — Full Load Amps
PSC — Permanent Split Capacitor Motor
Ps— Static Pressure
INLET
SIZE (in.)
101150250 or 0145 or 0
101400250 or 0145 or 0
121425360 or 0210 or 0
10
141900500 or 0285 or 0
10
122100360 or 0210 or 0
142500500 or 0285 or 0
162600650 or 0370 or 0
10
122100360 or 0210 or 0
142500500 or 0285 or 0
163000650 or 0370 or 0
LEGEND*Max based on 0.1 in. wg downstream Ps for PSC motors. See Catalog for
PSC MOTOR
HP
6
8530170 or 093 or 0
6
6
8900170 or 093 or 0
1
/
10
1
/
4
1
/
4
1
/
2
3
/
4
112.87.17.15.3
120 V
FLA
1.40.80.80.6
4.32.42.41.8
4.32.42.41.8
8.34.44.43.5
9.55.05.04.4
MOTOR AMPSPRIMARY AIRFLOWFAN AIRFLOW*
208 V
FLA
240 V
FLA
277 V
FLA
complete fan curves. Min based on 0.6 in. wg downstream Ps for PSC
motors.
†For all controls except ComfortID controls. Some DDC controls supplied by
others may have differing limitations.
NOTES:
1. Data is based on tests conducted in accordance with ARI Standard 880-
98.
2. Minimum airflow for cooling or cooling with hot water heat is the minimum flow rate controllable by the unit volume controller; shutoff or zero
is also acceptable.
Max with
PSC
50090 or 052 or 0
50090 or 052 or 0
50090 or 052 or 0
1400250 or 0145 or 0
1400250 or 0145 or 0
1400250 or 0145 or 0
Min†
ComfortID
Min
Max
PSC
53050
11501858900170 or 093 or 0
1425500
1900800121900360 or 0210 or 0
26001200
30001250
Min
PSC
12
Table 9B — 45K Quiet Series Fan Powered Terminal Unit Performance (ECM Motor)
UNIT
SIZE
45K
3
6
7
ARI — Air Conditioning and Refrigeration Institute
ECM — Electronically Commutated Motor
FLA — Full Load Amps
*Special order.
†This value is based on signal of 0.03 in. wg differential pressure of the linear
averaging probe.
INLET
SIZE (in.)
LEGEND
ECM MOTOR
HP
6
8900170 or 093 or 0
101400250 or 0145 or 0
121400360 or 0209 or 0
10
122000360 or 0209 or 0
142000500 or 0284 or 0
162000650 or 0370 or 0
101400250 or 0145 or 0
122100360 or 0209 or 0
142500500 or 0284 or 0
162500650 or 0370 or 0
1
/
2
112.89.46.9
120 V FLA*240 V FLA*277 V FLAMax with ECMMin†
ECM MOTOR AMPSPRIMARY AIRFLOWFAN AIRFLOW
7.75.04.1
Table 10 — 45Q Low Profile Series Fan Powered Terminal Unit Performance
UNIT
SIZE
45Q
2
3
4
LEGEND
DDC — Direct Digital Controls
Ps— Static Pressure
NOTES:
1. 45Q maximum primary airflow (cfm) is set by the maximum induced
airflow, which may vary as a function of downstream pressure.
Maximum airflow shown is based on the maximum induced airflow
(fan airflow) or 1.00 in. wg velocity pressure at inlet probe, whichever is less.
2. Minimum recommended primary airflow (cfm) is based on 0.03 in.
wg differential pressure of the linear inlet flow sensor, or 0 airflow.
0.03 in. wg is equal to 15% to 20% of the nominal flow rating of the
terminal. Less than 15% to 20% may result in greater than +5%
control of box flow.
INLET
SIZE (in.)
6
8
8
8 x 14(2) 1/
MOTOR
HP
1
/
6
1
/
6
1
/
4
6
MOTOR AMPSFAN AIRFLOW (cfm)PRIMARY AIRFLOW (cfm)
120V208/230V277VMaxMinMaxMin
2.81.51.1840310522 90520.04
2.81.51.1840310 840160930.06
4.12.21.61090520 927160930.07
6.93.72.7165080016503582070.10
Min
50090 or 052 or 0
1400250 or 0145 or 0
NOTES:
1. Data is based on tests conducted in accordance with ARI Standard 880-
98.
2. Minimum airflow for cooling or cooling with hot water heat is the minimum
flow rate controllable by the unit volume controller; shutoff or zero is also
acceptable.
3. 45Q maximum fan airflow is based on 0.10 in. wg downstream
static pressure.
4. 45Q minimum fan airflow (cfm) is based on maximum external
(downstream) static pressure 0.60 in. wg.
5. Minimum primary airflow (cfm) listed is for all controls except ComfortID control which is shown separately with lower available minimum CFMs. Some DDC controls supplied by others may have
different limitations.
6. Do not select discharge temperature exceeding 120 F. In addition,
ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning Engineers) recommends a maximum discharge temperature of 90 F to avoid room air stratification when heating from the
ceiling (2001 Fundamentals, Chapter 32).
ComfortID
Max ECMMin ECM
1030250
2000500
2500600
Min
ComfortID
MINIMUM
Ps. (in. wg)
BALANCING 45M,N,R PARALLEL FLOW UNITS — A
parallel fan terminal is designed to operate with the fan supplying air equal to 40 to 60% of the VAV damper maximum setting. Adjustments to the parallel units fan should be made with
the primary air closed off. Refer to unit capacity tables to
ensure airflow through the electric heater meets the minimum
requirements before operating heater.
Each control option has specific procedures required for
balancing the unit, but some steps are common to all parallel
fan units, as described below.
To balance parallel fan unit:
Setting Fan Airflow
NOTE: If the unit has electric heat or hot water heat, tempo-
rarily disable these functions before balancing the fan.
If unit has optional electric heat disconnect downstream of
fan motor connections to power, open disconnect.
If unit does not have optional electric heat disconnect, remove one electric heat power line connection. Be sure to insulate loose line from ground wire or other wires.
1. Set the controller to provide heating airflow demand only.
Typically, this is accomplished by setting the thermostat
to the highest possible temperature setting.
2. Determine that the VAV damper is fully closed. This may
require a temporary override of the VAV controller. Do
not adjust minimum and maximum cfm set points at this
time.
3. Using a flow hood or duct traverse, determine the delivered fan airflow (cfm).
NOTE: Both flow hood and duct traverse are subject to
measurement errors. Be sure that all applicable measurement precautions are taken.
4. Compare the required design cfm in heating mode to the
actual delivered airflow. If there is a minimum setting for
the VAV damper in heating mode (as recommended by
ASHRAE [American Society of Heating, Refrigeration,
and Air Conditioning Engineers] Standard 62), this quantity is included in the total measured airflow.
5. Adjust the fan SCR at unit control box to achieve the desired airflow rate.
Setting of VAV (Primary) Airflow
Adjustment of Set Points — Each parallel fan unit is equipped
with a pneumatic or electronic volume controller which regulates the quantity of cold primary air entering the terminal and
the conditioned space. If required airflow levels are specified
13
with the job order, the minimum and maximum cfm levels will
be set at the factory. If minimum and maximum levels are not
specified, a default value is used. Other settings of minimum
and maximum primary airflow must be set in the field. Airflow
(cfm) ranges for the primary air damper are shown in
Tables 11-13 for 45M,N,R units. The minimum primary airflow (other than zero) is the minimum flow rate controllable by
the unit volume controller. The primary air damper can be set
at zero for shutoff or at the minimum cfm listed.
Field Adjustment of Minimum and Maximum Airflow Set
Points — Each parallel fan unit is equipped with a linear aver-
aging flow probe which provides an amplified differential
pressure that is proportional to the unit airflow. Output from
this probe is used to provide a flow signal to both pneumatic
and electronic controls. Unit airflow (cfm) can be read directly
from the flow probe on the unit.
1. After the unit airflow from the fan has been set, turn on
primary (VAV) air supply and turn off the fan.
2. To set cfm in the field, connect a gage to the flow probe
and check the differential pressure.
3. If a minimum VAV flow is required in heating mode, adjust the volume controller until the differential pressure
corresponds to the cfm required.
Table 11 — 45M Parallel Fan Powered Terminal Unit Performance
4. Some control sequences allow the fan to start before the
VAV damper reaches minimum setting, for an overlapping of fan and VAV flow. For these sequences, after controller min airflow has been adjusted, the total airflow
with both fan and primary airflow should be checked. For
sequences that call for the fan to start as the first stage
of heat, the cooling minimum cfm can be verified at the
diffuser.
Setting the minimum control point will typically require
careful adjustment of the thermostat to create a minimum
cooling demand signal.
5. a. Set the controller to provide maximum cooling de-
mand. This is typically accomplished by setting the
thermostat to the lowest possible temperature setting. For most control sequences, this will cause
the fan to shut off.
b. Adjust the volume controller until the differential
pressure (measured through the flow probe as
described above) corresponds to the cfm required.
6. Return all reheat options to normal connections.
7. Cap the ends of the inlet flow sensors.
8. Reset the thermostat to a normal setting.
INLET
UNIT
SIZE
2
3
4
5
6
716
LEGEND
ASHRAE — American Society of Heating, Refrigeration and Air
DDC— Direct Digital Controls
EH— Electric Heat
HW— Hot Water Heat
NOTES:
1. 45M maximum primary airflow (cfm) is based on 1.00 in. wg
velocity pressure signal (VP), per inlet size, using a standard
linear averaging sensor.
2. Minimum recommended primary airflow (cfm) is based on
0.03 in. wg differential pressure of the linear inlet flow sensor,
or 0 airflow. 0.03 in. wg is equal to 15% to 20% of the nominal
MOTOR
SIZE
(in.)
6
8400200920 170 or 093 or 0.33.49.64
8
106003001430 250 or 0145 or 0.35.74.94
10
1210504802060 360 or 0210 or 0.36.71.88
12
1415008602800 500 or 0285 or 0.34.771.08
14
1618009303660 650 or 0370 or 0.35.941.36
HP
120V 208/240V 277VMaxMinMaxMin
1
/
10
1
/
10
1
/
4
1
/
2
1
/
2
3
/
4
Conditioning Engineers
MOTOR
AMPS
1.60.90.7
2.01.20.9
3.21.91.4
7.34.13.1
10.15.14.2
9.55.84.4220011403660 650 or 0370 or 0.35.67.89
FAN AIRFLOW
(cfm)
4005051590 or 052 or 0.32.37.42
600150920 170 or 093 or 0.33.48.56
10502501430 250 or 0145 or 0.35.52.60
15008602060 360 or 0210 or 0.36.60.77
18009302800 500 or 0285 or 0.34.68.92
PRIMARY AIRFLOW
(cfm)
Min
ComfortID
flow rating of the terminal. Less than 15% to 20% may result in
greater than +5% control of box flow.
3. 45M maximum fan airflow (cfm) is based on 0.25 in. wg external (downstream) static pressure.
4. 45M minimum fan airflow (cfm) is based on maximum external
(downstream) static pressure 0.60 in. wg.
5. Minimum primary airflow (cfm) listed is for all controls except
ComfortID controls which is shown separately with lower available minimum cfm. Some DDC controls supplied by others may
have different limitations.
6. Do not select discharge temperature exceeding 120 F. In addition, ASHRAE recommends a maximum discharge temperature of 90 F to avoid room air stratification when heating from
the ceiling (2001 Fundamentals, Chapter 32).
No or EH1 row HW2 row HW
MINIMUM
OPERATING
PRESSURE
(in. wg)
14
Table 12A — 45N Quiet Parallel Fan Powered Terminal Unit Performance (PSC Motor)
UNIT
SIZE
DDC — Direct Digital Controls
EH— Electric Heat
HW — Hot Water
Ps— Static Pressure
PSC — Permanent Split Capacitor Motor
INLET
SIZE (in.)
2
3
4
5
6
7
LEGEND*Max based on 0.25 in. wg downstream Ps for PSC motors. See Catalog for
MOTOR
Hp
6
8920160 or 093 or 00.330.420.50
6
8920160 or 093 or 00.330.410.44
101430250 or 0145 or 00.320.520.58
6
8920160 or 093 or 00.330.410.43
101430250 or 0145 or 00.320.510.58
122060360 or 0210 or 00.340.770.91
10
122060360 or 0210 or 00.340.480.91
142800480 or 0285 or 00.280.481.08
10
122060360 or 0210 or 00.340.490.58
142800480 or 0285 or 00.280.490.61
163660630 or 0370 or 00.280.630.85
10
122060360 or 0210 or 00.340.480.58
142800480 or 0285 or 00.280.480.61
163660630 or 0370 or 00.280.620.85
1
/
4
1
/
4
1
/
4
1
/
2
1
/
2
3
/
4
MOTOR AMPSFAN AIRFLOW*PRIMARY AIRFLOWMINIMUM PRESSURES, Ps in. wg
120 V 208/240 V 277 VMaxMinMaxMin†
2.61.51.150050
3.11.71.380050
3.41.91.490050
7.34.13.11700375
7.34.13.11800400
9.55.84.42000625
Min
51590 or 052 or 00.310.340.36
51590 or 052 or 00.310.340.35
51590 or 052 or 00.310.340.34
1430250 or 0145 or 00.320.390.58
1430250 or 0145 or 00.320.390.43
1430250 or 0145 or 00.320.390.43
complete fan curves. Min based on 0.6 in. wg downstream Ps for PSC
motors.
†For all controls except ComfortID controls. Some DDC controls supplied by
others may have differing limitations.
NOTE: Data is based on tests conducted in accordance with ARI (Air Conditioning and Refrigeration Institute) Standard 880-98.
ComfortID
No or EH 1 Row HW 2 Row HW
Table 12B — 45N Quiet Parallel Fan Powered Terminal Unit Performance (ECM Motor)
UNIT
SIZE
4
7
LEGEND
DDC — Direct Digital Controls
ECM — Electronically Commutated Motor
FLA — Full Load Amps
*Special order.
INLET
SIZE (in.)
6
8900170 or 093 or 0
101400250 or 0145 or 0
122100360 or 0210 or 0
10
122100360 or 0210 or 0
142500500 or 0285 or 0
163300650 or 0370 or 0
MOTOR
Hp
1
/
2
112.89.46.9
120 V FLA*240 V FLA*277 V FLAMaxMin†
ECM MOTOR AMPSPRIMRY AIRFLOWECM FAN AIRFLOW
7.75.04.1
Table 13 — 45R Low Profile Parallel Fan Powered Terminal Unit Performance
UNIT
SIZE
45R
INLET
SIZE
2
8 x 14
4
(in.)
MOTOR
HP
6
8
1
/
6
1
/
6
1
/
4
LEGEND
ASHRAE— American Society of Heating, Refrigeration and Air
DDC— Direct Digital Controls
Ps— Static Pressure
NOTES:
1. 45R maximum primary airflow (cfm) is based on 1.00 in. wg velocity
2. Minimum recommended primary airflow (cfm) is based on 0.03 in.
Conditioning Engineers
pressure signal (VP), per inlet size, using a standard linear averaging sensor.
wg differential pressure of the linear inlet flow sensor, or 0 airflow.
0.03 in. wg is equal to 15% to 20% of the nominal flow rating of the
terminal. Less than 15% to 20% may result in greater than +5%
control of box flow.
MOTOR AMPSFAN AIRFLOW (cfm)
120V208/230V277VMaxMinMaxMin
2.81.51.062025052290520.100.100.10
2.81.51.0620250 927160930.180.180.18
3.92.11.483045020663582070.170.170.17
Min
50090 or 052 or 0
1400250 or 0145 or 0
†For all controls except ComfortID controls. Some DDC controls supplied by
others may have differing limitations. This value is based on a signal of
0.03 in. wg differential pressure of the linear averaging flow probe.
NOTE: Data is based on tests conducted in accordance with ARI (Air Conditioning and Refrigeration Institute) Standard 880-98.
PRIMARY AIRFLOW
(cfm)
Min
ComfortID
3. 45R maximum fan airflow (cfm) is based on 0.25 in. wg external
(downstream) static pressure.
4. 45R minimum fan airflow (cfm) is based on maximum external
(downstream) static pressure 0.60 in. wg.
5. Minimum primary airflow (cfm) listed is for all controls except ComfortID controls which is shown separately with lower available minimum CFMs. Some DDC controls supplied by others may have
different limitations.
6. Minimum pressure, Ps (in. wg) on 45R water coil units is based on
coil located on induction port.
7. Do not select discharge temperature exceeding 120 F. In addition,
ASHRAE recommends a maximum discharge temperature of 90 F
to avoid room air stratification when heating from the ceiling (2001
Fundamentals, Chapter 32).
ComfortID
MINIMUM Ps (in. wg)
None or
Elec. Heat
MaxMin
1000250
1600400
1 Row
Hot Water
2 Rows
Hot Water
15
Speed Controller — Each Carrier fan powered air ter-
minal unit is equipped with a fan SCR speed controller, located
on the bottom of the control box. The SCR can be adjusted in
the field.
NOTE: The 45J size 7 unit and 45Q size 4 unit have 2 SCR
speed controllers, one for each fan. One SCR is located in the
standard position at the bottom of the control box; the other is
at the top of the control box.
The fan airflow output is dependent on the setting of the
controller and the downstream static resistance.
CAUTION
The minimum stop on the speed controller is factory set at
an internal minimum stop to prevent damage to the motor.
Do not attempt to override this minimum stop or electrical
damage to the fan motor may result.
TO INCREASE THE FAN SPEED (RPM), turn the slotted
adjustment on the controller clockwise toward the “HI” marking printed on the controller face plate. (Refer to Fig. 10.)
TO DECREASE THE FAN SPEED (RPM), turn the adjustment counterclockwise toward the “LO” marking. (See
Fig. 10.)
ComfortID™ VAV CONTROLS
Install Sensors and Make Field Wiring
Connections
GENERAL — All field wiring must comply with National
Electrical Code and local requirements.
CAUTION
DO NOT run sensor or relay wires in the same conduit or
raceway with Class 1 service wiring.
DO NOT abrade or nick the outer jacket of cable.
DO NOT pull or draw cable with a force that may harm the
physical or electrical properties.
DO NOT bend a cable through a radius sharper than that
recommended by its manufacturer.
AVOID splices in any control wiring.
Perform the following steps if state or local code requires
the use of conduit, or if your installation requires a cable length
of more than 8 ft:
1. Disconnect the sensor cable from the ComfortID zone
controller, at the terminals labeled SAT and GND.
2. Mount the sensor to the duct (see Steps 2 and 3 above).
3. Mount a field-supplied 4 in. x 4 in. x 2 in. extension box
over the duct sensor.
4. Connect a conduit (
enclosure and extension box.
1
/2-in. nominal) to the zone controller
WARNING
Disconnect electrical power before wiring inside the controller. Electrical shock, personal injury, or damage to the
zone controller can result.
Wire the control as shown on the control package diagram
for the specific installation. Control wiring diagrams can be
found inside the control box.
SUPPLY-AIR TEMPERATURE (SAT) SENSOR INSTALLATION — On terminals with heat, the SAT sensor is provided. The sensor is factory wired to the controller and shipped
in the control box. The SAT must be field-installed in the duct
downstream from the air terminal. See Fig. 11. The SAT sensor
part number is 33ZCSENSAT. See Table 14 for resistance
information.
To install the sensor, proceed as follows:
1. Remove the plug from one of the
control box and pass the sensor probe through the hole.
2. Drill or punch a
1
/2-in. hole in the duct downstream of
the unit, at a location meeting the requirements shown in
Fig. 11.
3. Using 2 self-drilling screws (supplied), secure the sensor
probe to the duct.
The SAT sensor probe is 6 inches in length. The tip of the
probe must not touch the inside of the duct. Use field-supplied
bushings as spacers when mounting the probe in a duct that is
6 in. or less in diameter.
If the unit is not equipped with heat, the SAT sensor is not
provided and is not required.
For units equipped with electric heat, locate the sensor as far
downstream as possible. This ensures the sensor will not be
affected by excessive radiant heat from the heater coil. Install
the sensor a minimum of 2 ft downstream of the coil for units
with hot water heat.
7
/8-in. openings in the
277 V 12L
LO
5 FLA
6
Z
50
RANCO
MXF-544002-001
100533-01
HI
UR
Fig. 10 — Fan Speed Controller
UNIT WITH HEAT
2 FT. MIN.
PRIMARY
AIR INLET
LEGEND
SAT — Supply Air Temperature Sensor
ZC— Zone Controller
AIR
TERMINAL
UNIT
ZC
HEAT
Fig. 11 — Supply Air Temperature Probe
(Part No. 33ZCSENSAT) Location
SAT
16
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.