Carrier 45Q user guide manual

45J,M,K,N,Q,R
Variable Air Volume Terminals
Installation, Start-Up and
Service Instructions
Fan Powered
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
PRE-INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
CONTROL OPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
ComfortID™ VAV Controls . . . . . . . . . . . . . . . . . . . . . . . 4
3V™ VVT® Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Analog Electric Controls . . . . . . . . . . . . . . . . . . . . . . . . . 4
Pneumatic Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
No Controls or Direct Digital Controls
(By Others) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
Step 1 — Install Fan Powered Box. . . . . . . . . . . . . . . . 6
Step 2 — Make Duct Connections . . . . . . . . . . . . . . . . 6
Step 3 — Connect Power Wiring. . . . . . . . . . . . . . . . . . 6
Step 4 — Set Up System and Calibrate . . . . . . . . . . . 8
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-16
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Initial Start-Up Procedures . . . . . . . . . . . . . . . . . . . . . . . 9
Balancing Carrier Fan Terminals . . . . . . . . . . . . . . . . 10
Speed Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
ComfortID VAV CONTROLS . . . . . . . . . . . . . . . . . . 16-23
Install Sensors and Make Field Wiring
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Connect the CCN Communication Bus . . . . . . . . . . 22
Water Valve Installation . . . . . . . . . . . . . . . . . . . . . . . . . 22
ComfortID Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
CCN System Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3V VVT CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . 24-43
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Initial Operation and Test. . . . . . . . . . . . . . . . . . . . . . . . 42
Fan and Heat Configuration and Test. . . . . . . . . . . . 43
System Balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
PNEUMATIC CONTROLS . . . . . . . . . . . . . . . . . . . . . 43-46
General — Single Function Pneumatic Controller
Control Sequences (1300-1305, 1400-1401). . . . 43
Units with Single-Function Controllers . . . . . . . . . . 43
Units with Multi-Function Controllers
(Sequences 1306-1317 and 1402-1405). . . . . . . . 45
Operation Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
ANALOG CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . 46-48
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
System Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Thermostat Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Controller Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48,49
Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Fan Motor and Wheel. . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Fan Motor Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Fan Motor Maintenance
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53450002-01 Printed in U.S.A. Form 45-3SI Pg 1 12-08 Replaces: 45-1SI
. . . . . . . . . . . . . . . . . . . . . . . . . 48
Air-handling equipment will provide safe and reliable service when operated within design specifications. The equipment should be operated and serviced only by authorized personnel who have a thorough knowledge of system operation, safety devices, and emergency procedures.
Good judgement should be used in applying any manu­facturer’s instructions to avoid injury to personnel or damage to equipment and property.
Disconnect all power to the unit before performing mainte­nance or service. Unit may automatically start if power is not disconnected. Electrical shock and personal injury could result.
If it is necessary to remove and dispose of mercury contac­tors in electric heat section, follow all local, state, and fed­eral laws regarding disposal of equipment containing hazardous materials.
General —
45M,N,R variable volume (parallel) fan powered boxes (see Fig. 1 and 2) can be equipped to provide pressure independent, variable volume (VAV). All units can also be equipped with factory-installed analog electronic, pneumatic, or ComfortID™ variable air volume (VAV) controls. The 45M,N,R units can be equipped with 3V™ variable volume and temperature (VVT) controls. Units are available with factory-installed electric or hot water heat.
SAFETY CONSIDERATIONS
SAFETY NOTE
WARNING
WARNING
PRE-INSTALLATION
The 45J,K,Q constant volume (series) and
Fig. 1 — Series Flow Unit (45K Shown)
Fig. 2 — Parallel Fan Unit (45J Shown)
The 45J,M units are standard fan powered terminal units. The 45K,N units are quiet fan powered terminal units. The 45Q,R units are low profile fan powered terminal units.
CONTROL OFFERINGS — Each 45J, 45K, 45M, 45N, 45Q, 45R unit is supplied with a linear averaging flow probe as a standard feature. This probe offers a flow averaging capability and results in flow sensing capacity equal to any competitive unit.
Control options include ComfortID™ VAV, 3V variable volume and temperature (VVT®), analog electronic and pres­sure-independent pneumatic. Both 3V and ComfortID controls are communicating controls that are compatible with the Carri­er Comfort Network® (CCN) network. The 3V VVT controls are for 45M,N,R units only.
Pneumatic controls are available with linear actuators and single-function or multi-function controller. The multi-function controller provides a simple switchover from normally open to normally closed applications.
Electronic control units feature a factory-installed enclosure that provides easy access for field connections.
INITIAL INSPECTION — Once items have been removed from packing, check carefully for damage to duct connections, coils, or controls. File damage claim immediately with trans­portation agency and notify Carrier.
NOTE: Remove all packaging material and foreign material from unit and ensure the blower wheel moves freely before installation. Units are shipped with cardboard in both sides of the fan inlet that MUST be removed.
Unit Identification — Each unit has 2 main labels at-
tached to the casing. The FAN UNIT label (Fig. 3) lists the model number, supply voltage requirements, motor horsepow­er and overcurrent protection requirements. The AIRFLOW label (Fig. 4) lists the model number, unit size, factory order number and location. The location “tag” indicates where the unit is intended for installation. There may be other labels at­tached to the unit, as options or codes may require. Read all labels on a typical unit before attempting installation. Control boxes are assembled as indicated on the identification label.
Contact your local Carrier representative for more
information. INSTALLATION PRECAUTION — Check that construction
debris does not enter unit or ductwork. Do not operate the central-station air-handling fan without final or construction filters in place. Accumulated dust and construction debris distributed through the ductwork can adversely affect unit operation.
SERVICE ACCESS — Provide service clearance for unit access (see Installation section for details).
CODES — Install units in compliance with all applicable code requirements.
UNIT SUSPENSION — See Installation section for unit sus­pension details.
Warranty — All Carrier-furnished items carry the standard
Carrier warranty.
Fig. 3 — Fan Unit Label
Fig. 4 — Airflow Label
2
Table 1 — Unit Weights
45J UNIT WEIGHTS (lb)
SIZE UNIT WT
2 70 74 79 100 89 91 3 70 74 79 100 90 92 4 85 89 94 117 107 110 5 85 89 94 117 109 113 6 100 104 109 135 125 130 7 140 144 109 180 175 183
WITH PNEUMATIC
CONTROLS
WITH DDC OR ANALOG
CONTROLS
WITH ELECTRIC HEATER
WITH HOT WATER
1-Row 2-Row
45M UNIT WEIGHTS (lb)
SIZE UNIT WT
2 114 118 123 144 133 135 3 114 118 123 144 133 135 4 115 119 124 147 134 136 5 122 126 131 154 134 136 6 123 127 132 155 135 137 7 127 131 136 167 139 141
WITH PNEUMATIC
CONTROLS
WITH DDC OR ANALOG
CONTROLS
WITH ELECTRIC HEATER
WITH HOT WATER
1-Row 2-Row
45K UNIT WEIGHTS (lb)
SIZE UNIT WT
2 185 189 194 278 194 197 3 200 204 209 280 209 212 4 200 204 209 232 209 212 5 225 229 234 257 237 242 6 250 254 259 285 262 267 7 260 264 269 300 272 277
WITH PNEUMATIC
CONTROLS
WITH DDC OR ANALOG
CONTROLS
WITH ELECTRIC HEATER
WITH HOT WATER
1-Row 2-Row
45N UNIT WEIGHTS (lb)
SIZE UNIT WT
2 185 189 194 219 197 197 3 200 204 209 230 209 212 4 200 204 209 237 209 212 5 225 229 234 257 237 242 6 250 254 259 284 262 267 7 260 264 269 304 272 277
WITH PNEUMATIC
CONTROLS
WITH DDC OR ANALOG
CONTROLS
WITH ELECTRIC HEATER
WITH HOT WATER
1-Row 2-Row
45Q UNIT WEIGHTS (lb)
SIZE UNIT WT
2 60 64 69 75 70 72 3 70 74 79 85 80 82 4 110 114 119 132 122 124
WITH PNEUMATIC
CONTROLS
WITH DDC OR ANALOG
CONTROLS
WITH ELECTRIC HEATER
WITH HOT WATER
1-Row 2-Row
45R UNIT WEIGHTS (lb)
SIZE UNIT WT
2 80 84 89 95 88 90 4 90 94 99 110 98 100
LEGEND
DDC — Direct Digital Controls
WITH PNEUMATIC
CONTROLS
WITH DDC OR ANALOG
CONTROLS
WITH ELECTRIC HEATER
WITH HOT WATER
1-Row 2-Row
3
CONTROL OPTIONS
The units are offered with a wide variety of factory­mounted controls that regulate the volume of air delivery from the unit and respond to cooling and heating load requirements of the conditioned space. All control packages can operate stand-alone and will fulfill the thermal requirements of a given control space. These devices are available in both pneumatic and electronic arrangements. The 3V™ and ComfortID™ con­trol types are communicating controls which can be integrated into a CCN building system. A number of DDC (direct digital control) control packages by others are available for consign­ment mounting as indicated.
Control offerings are:
A: Analog Electronic
C: ComfortID™, VAV
P: Pneumatic
V: 3V™, VVT® (45M,N,R units only)
N: None or DDC by others
Each control approach offers a variety of operating func­tions; a control package number identifies combinations of control functions. Because of the variety of functions available, circuit diagrams, operating sequences, and function descrip­tions are contained in separate Application Data publications. Refer to the specific control publication for details.
ComfortID™ VAV Controls — Pressure independent
control packages are available with or without heat. These con­trols provide occupied and unoccupied heating and cooling, de­mand controlled ventilation (DCV), and zone humidity control. They can be networked together via the CCN network to pro­vide integrated system operation of all components, including the operation of air source equipment. These controls may be used in a stand-alone terminal, or as part of the Carrier DDC control system. All control arrangements include a standard linear inlet flow sensor, control enclosure, SCR (silicone con­trol rectifier) fan speed controller, class II 24-volt power trans­former, and fan contactor. Several types of room sensors may be ordered, with and without set point adjustment, and with in­tegral CO
CONTROL ARRANGEMENTS — ComfortID control pack­ages must be used in combination with a thermostat. Thermo­stats are not included in the package and are ordered separately. See Tables 2A and 2B.
Table 2A — ComfortID VAV Control Arrangements
PACKAGE
SSR — Solid-State Relay
Table 2B — ComfortID VAV Control Arrangements
sensors.
2
— 45JC,KC,QC Series Terminals
NO. 4440 No heat (or field supplied baseboard heat) 4442 Cooling with up to 3 stage electric heat 4443 Cooling with On-Off hot water 4444 Cooling with proportional (floating) hot water 4452 Cooling with 1 to 3 stage field-installed electric heat 4454 Cooling with Proportional SSR electric heat
DESCRIPTION
— 45MC,NC,RC Parallel Terminals
ACCESSORY THERMOSTATS: Thermostat: 33ZCT55SPT: RT (room temperature) sensor,
with override only. Thermostat: 33ZCT56SPT: RT (room temperature) sensor,
with set point adjust and override. Thermostat: 33ZCT58SPT: Communicating room tempera-
ture sensor with LCD, set point adjust, fan control, and over­ride.
Inlet Air Temperature Sensor: 33ZCSENPAT (required only if linkage unavailable)
NOTE: The 33ZCSENSAT supply air temperature sensor is included with the controls package. Field-installed VVT com­ponents such as thermostats and bypass controllers must still be ordered separately and shipped to the job site.
3V™ VVT® Controls — Pressure dependent control
packages are available with or without hot water (on-off con­trol), electric heat (up to 2 stages), or SSR (solid-state relay) electric heat. They are designed to be an integral part of the Carrier 3V, VVT control system, for parallel flow units only. All control arrangements include a standard linear inlet flow sensor, control enclosure, SCR fan speed controller, 24-volt transformer and fan relay. The 3V, VVT terminals are not available on series terminal units.
The 3V, VVT packages must be used in conjunction with a VVT compatible thermostat. Field-installed thermostats are not included and must be ordered separately. See Table 3.
Table 3 — 3V, VVT Control Arrangements
— 45MV,NV,RV Parallel Terminals
PACKAGE
NO.
8815 Pressure dependent, cooling only
8818
8819
8820
8825
8829
8830
Pressure dependent, cooling with on-off hot water reheat
Pressure dependent, cooling with 3-stage electric heat
Pressure dependent, cooling with modulating hot water reheat
Pressure dependent, cooling with combination baseboard and ducted reheat
Pressure dependent, cooling with 1 to 3 stage field-installed electric heat
Pressure dependent, cooling with Proportional SSR electric heat
DESCRIPTION
Analog Electronic Controls — Pressure independent
control packages are available with or without hot water or electric heat, automatic or remote night shutdown, and auto­matic night setback. All control arrangements include a standard linear inlet flow sensor, control enclosure, SCR fan speed controller, 24-volt transformer, fan relay, and wall ther­mostat to match the control type. See Tables 4A and 4B.
PACKAGE
NO. 4740 No heat (or field supplied baseboard heat) 4742 Cooling with up to 3 stage electric heat 4743 Cooling with On-Off hot water 4744 Cooling with proportional (floating) hot water 4752 Cooling with 1 to 3 stage field-installed electric heat 4754 Cooling with Proportional SSR electric heat
SSR — Solid-State Relay
DESCRIPTION
4
Table 4A — Analog Electronic Control
Arrangements — 45JA,KA,QA Series Terminals
PACKAGE
NO. 2200 Cooling only 2201 Cooling only with automatic night shutdown 2202 Cooling only with remote night shutdown 2203 Cooling only with automatic night setback 2204 Cooling with on/off hot water heat 2205 Cooling with on/off hot water heat and automatic night
2206 Cooling with on/off hot water heat and remote night
2207 Cooling with on/off hot water heat and automatic night
2208 Cooling with proportional hot water heat 2209 Cooling with proportional hot water heat and automatic
2210 Cooling with proportional hot water heat and remote
2211 Cooling with proportional hot water heat and automatic
2212 Cooling with up to 2 stages of electric heat 2213 Cooling with up to 2 stages of electric heat and auto-
2214 Cooling with up to 2 stages of electric heat and remote
2215 Cooling with up to 2 stages of electric heat and auto-
2216 Cooling with up to 2 stages of electric heat, cooling/
2218 Cooling with proportional electric heat
shutdown
shutdown
setback
night shutdown
night shutdown
night setback
matic night shutdown
night shutdown
matic night setback a variety of pressures
heating automatic change over control (morning warm­up) and automatic night setback
DESCRIPTION
Table 4B — Analog Electronic Control
Arrangements — 45MA,NA,RA Parallel Terminals
PACKAGE
NO. 2300 Cooling with sequenced fan 2301 Cooling with sequenced fan and auto. night shutdown 2302 Cooling with sequenced fan and auto. night setback 2303 Cooling with sequenced fan and on/off hot water heat 2304 Cooling with sequenced fan and on/off hot water heat
2305 Cooling with sequenced fan and on/off hot water heat
2306 Cooling with sequenced fan and proportional hot water
2307 Cooling with sequenced fan proportional hot water heat
2308 Cooling with sequenced fan proportional hot water heat
2309 Cooling with sequenced fan and up to 2 stages of elec-
2310 Cooling with sequenced fan up to 2 stages of electric
2311 Cooling with sequenced fan up to 2 stages of electric
2313 Cooling with sequenced fan and proportional electric
and auto. night shutdown
and auto. night setback
heat
and auto. night shutdown
and auto. night setback
tric heat
heat and auto. night shutdown
heat and auto. night setback
heat
DESCRIPTION
Pneumatic Controls — Pressure independent control
packages are available with or without hot water or electric heat, night shutdown and/or unoccupied heating. All control ar­rangements include a standard linear inlet flow sensor and SCR fan speed controller. See Tables 5A and 5B.
Single function controller: Provides single function, i.e., DA-NO.
Multi-function controller: Capable of providing DA-NO, DA-NC, RA-NC or RA-NO functions.
Table 5A — Pneumatic Control Arrangements —
45JP,KP,QP Series Terminals
PACKAGE
NO.
1300 Single function controller; DA-NO with or without hot
1301 Single function controller; DA-NO with or without hot
1302 Single function controller; DA-NO with or without hot
1303 Single function controller; RA-NC with or without hot
1304 Single function controller; RA-NC with or without hot
1305 Single function controller; RA-NC with or without hot
1306 Multi-function controller; DA-NO with or without hot
1307 Multi-function controller; DA-NO with or without hot
1308 Multi-function controller; DA-NO with or without hot
1309 Multi-function controller; DA-NC with or without hot
1310 Multi-function controller; DA-NC with or without hot
1311 Multi-function controller; DA-NC with or without hot
1312 Multi-function controller; RA-NC with or without hot
1313 Multi-function controller; RA-NC with or without hot
1314 Multi-function controller; RA-NC with or without hot
1315 Multi-function controller; RA-NO with or without hot
1316 Multi-function controller; RA-NO with or without hot
1317 Multi-function controller; RA-NO with or without hot
water or electric heat
water or electric heat and with night shutdown
water or electric heat, with night shutdown and unoc­cupied heating
water or electric heat
water or electric heat and with night shutdown
water or electric heat, with night shutdown and unoc­cupied heating
water or electric heat
water or electric heat and with night shutdown
water or electric heat, with night shutdown and unoc­cupied heating
water or electric heat
water or electric heat and with night shutdown
water or electric heat, with night shutdown and unoc­cupied heating
water or electric heat
water or electric heat and with night shutdown
water or electric heat, with night shutdown and unoc­cupied heating
water or electric heat
water or electric heat and with night shutdown
water or electric heat, with night shutdown and unoc­cupied heating
DESCRIPTION
Table 5B — Pneumatic Control Arrangements —
45MP,NP,RP Parallel Terminals
PACKAGE
NO. 1400 1 function DA-NO with or without optional heat 1401 1 function RA-NC with or without optional heat 1402 4 function DA-NO with or without optional heat 1403 4 function RA-NO with or without optional heat 1404 4 function DA-NC with or without optional heat 1405 4 function RA-NC with or without optional heat
LEGEND
DA — Direct Acting Thermostat RA — Reverse Acting Thermostat NO — Normally Open Damper Position NC — Normally Closed Damper Position
DESCRIPTION
No Controls or Direct Digital Controls (By Oth­ers) — Control sequences are available for factory installa-
tion of numerous field-supplied controls from various manu­facturers including: Andover, Automated Logic, Invensys (Sie­be), Siemans (Landis), Johnson, and others. All packages in­clude a standard liner inlet flow sensor, control enclosure, SCR fan speed controller, 24-v transformer, and fan relay.
Contact Carrier for information on mounting field-supplied
controls.
5
NO CONTROL UNITS — Control sequences are also avail­able to provide a control box on units supplied with no factory­installed controls. These arrangements include a standard linear inlet flow sensor, control enclosure, SCR fan speed con­trol, 24-v transformer, and fan relay. See Table 6.
Table 6 — No Control Arrangements —
45JN,MN,KN,NN,QN,RN Terminals
PACKAGE
NO.
D000 Field supplied and mounted controls by others. (For
D001 Field supplied and mounted controls by others. (For
units without electric heat, includes Class II for 24-volt power transformer.)
units with electric heat that already include a trans­former.)
DESCRIPTION
INSTALLATION
Step 1 — Install Fan-Powered Box
SELECT LOCATION
1. Units should be installed so that they do not come in con­tact with obstacles such as rigid conduit, sprinkler piping, Greenfield flexible metal covering, or rigid pneumatic tubing; such contact can transmit vibration to the building structure, causing objectionable low frequency noise.
2. Units should never be installed tight against concrete slabs or columns, as vibration transmission is amplified in this condition.
3. Fan powered terminals require sufficient clearance for servicing the blower/motor assembly from the bottom of the unit, low voltage controls from the side and line volt­age motor controls or electric heat (if equipped) from the rear (discharge end) of the unit.
Bottom access panel removal requires a minimum of 3 in. minimum clearance, plus substantial horizontal clearance to slide the access panel out of the way for service. Actual horizontal dimensions will vary due to varying access panels for different sized units. See your particular unit’s submittal drawings for more detail.
NOTE: Be certain appropriate accommodations for panel removal of most unit casings are large enough to allow adequate internal service room once the panels are removed.
A clearance of 18 in. is recommended for control enclo­sure access. Unit control enclosure will vary depending on which control package is used. Control enclosure loca­tion is specified on unit submittals. Low voltage enclo­sure covers are removable, not hinged.
A clearance of 36 in. is recommended for line voltage motor controls and electric heat control access. High­voltage motor controls or electric heat control access is supplied with hinged access doors for units with fused disconnect. Specific location is indicated on the unit submittal.
NOTE: These recommendations do not supersede NEC (National Electrical Code) or local codes that may be applicable, which are the responsibility of the installing contractor.
4. Whenever possible, fan-powered boxes should be installed over halls or passageways (rather than over occupied spaces) in order to limit the sound reaching occupants.
POSITION UNIT
1. When moving boxes, use appropriate material handling equipment and avoid contact with shaft extensions, con­trols, wiring, piping, heaters, and control boxes.
2. Raise unit to position using safe mechanical equipment and support until hanging means are attached and box is level.
INSTALL UNIT
1. Install field-supplied eye bolts, strap hangers or bolt rod supports as desired. Figure 5 illustrates possible unit sus­pension methods. A typical installation is shown in Fig. 6.
2. Care should be taken to use hanging materials of suffi­cient stiffness and strength, rigidly attached to the unit. Straps should not be located on coil flanges, electric heat sections, or control boxes. When using trapeze supports, avoid areas where access is required to side mounted con­trols, or side or bottom access doors. For best installation with trapeze supports, provide elastomeric material be­tween unit and supports.
3. Hangers should be securely attached to bar joist or mounting anchors properly secured to building structure with lugs or poured-in-place hangers. Percussion nails are not considered adequate anchors.
Step 2 — Make Duct Connections
1. Check that the pressure pick-up in primary air collar is located properly and that air supply duct connections are airtight. Install supply ductwork on unit inlet collar, fol­lowing all accepted medium-pressure duct installation procedures. Seal joints against leakage.
NOTE: For maximum efficiency in controlling radiated noise in critical applications, inlet ducts should be fabri­cated of 24-gage minimum sheet metal in place of flex connections. Flex duct is extremely transparent to radiat­ed sound; consequently high inlet statics (Ps) or sharp bends with excessive pressure drop can cause a radiated noise problem in the space. If flex duct is used, it should be limited to the connection between the distribution duct and the boot diffuser.
2. Install the discharge duct, being careful not to reduce the face area of any electric heat section until several diame­ters away from the unit. It is strongly recommended that lined discharge duct be used downstream of the unit. In­sulate duct as required.
3. Fan boxes should not be attached to octopus sections im­mediately downstream of the unit.
4. Install optional return-air filters before operating the unit.
5. Where construction filters were supplied with the box, leave filters in place until installation is complete and building is cleaned for occupancy.
Step 3 — Connect Power Wiring — See Fig. 7.
1. All power wiring must comply with local codes and with the NEC (National Electrical Code) ANSI/NFPA (Ameri­can National Standards Institute/National Fire Protection Association) 70-1981. Disconnect switches are optional equipment. Electrical, control and piping diagrams are shown on the exterior labeling or on a diagram inside the control and high-voltage enclosure covers, unless other­wise specified in the order write-up. All units are wired for a single point electrical connection to the fan and elec­tric heater (if equipped). Electric heaters provided by Car­rier are balanced by kW per stage. The installing electri­cian should rotate incoming electric service by phase to help balance overall building load.
6
OPTIONAL ACCESSORY HANGER
FIELD-SUPPLIED HANGER BRACKET
FIELD-SUPPLIED
HANGING STRAPS
Fig. 5 — Typical Unit Suspension Methods (45K Shown)
DO NOT suspend unit
by trapeze hangers that interfere with the unit access panel.
Fig. 6 — Typical Perimeter Installation — Constant Volume Fan-Powered Box
7
LEGEND
AFS — Airflow Switch CAP — Capacitor SCR — Silicone Control Rectifier
Fig. 7 — Typical Power Connections for Fan Powered Units with 3-Stage Electric Heat
2. All field wiring must be provided with a safety discon­nect per NEC 424-19, 20, and 21.
3. Disconnect all incoming power before wiring or servicing unit. All disconnect switches on the terminal (if equipped) should be in the OFF position while making power connections.
4. Units with electric heat should use copper wires rated at least 125% of rating plate amperage. Refer to the unit’s rating label and minimum supply circuit amps.
5. Observe wiring diagram and instructions attached to the unit. The 480-v, 3-phase units require a Wye power source with a fourth (neutral) wire in addition to the full sized ground wire. All units must be grounded as required by NEC 424-14 and 250.
Step 4 — Set Up System and Calibrate
GENERAL — The parallel fan powered terminals (45K and 45N) are designed to provide varying quantities of cold primary air to a space in response to a thermostat demand for cooling. For a heating demand, the fan will operate to supply ceiling plenum air to the space. For units equipped with a heat­ing coil, the heater will operate as required to meet a heating demand.
The series fan powered terminals (45J and 45M) are de­signed to provide a constant airflow to the space. The air supplied to the space is a mixture of primary air and ceiling plenum air. The fan speed is adjusted to provide the required airflow to the space. In response to a cooling demand from a thermostat, the damper will increase the amount of cold prima­ry air while reducing the amount of ceiling plenum air to decrease the temperature of the air being delivered to the space.
Most terminal control packages provide pressure compen­sation to allow pressure independent operation of the primary air damper, regardless of changes to the available static pres­sure in the supply ductwork. To balance the unit it is necessary to set both the minimum and maximum airflow set points of the controller. The many types of control options available each have specific procedures required for balancing. Refer to the submittal information for these requirements.
SET POINTS — Maximum and minimum airflow set points are normally specified for the job and specific for each unit on the job. Default set point values are provided by the factory and can be reset to the specific requirements in the field. The fan speed must be field adjusted after all discharge ductwork and diffusers have been installed.
Field Adjustment of the Maximum and Minimum Airflow Set Points — Each fan powered terminals unit is equipped with a flow probe installed in the primary air inlet which mea­sures a differential pressure. The relationship between the airflow probe pressure and the corresponding airflow is shown in the Flow Probe Graph. See Fig. 8. This chart is attached to each unit.
SYSTEM CALIBRATION OF THE LINEAR AVERAGING FLOW PROBE — To achieve efficient pressure independent operation, the velocity sensor and linear averaging flow probe must be calibrated to the controller. This will ensure that air­flow will be accurate for all terminals at system start-up.
System calibration is accomplished by calculating a flow coefficient that adjusts the pressure fpm characteristics. The flow coefficient is determined by dividing the flow for a given unit (design air volume in cfm), at a different velocity pressure of 1.0 in. wg, by the standard pitot tube coefficient of 4005. This ratio is the same for all sizes, if the standard averaging probe is used.
8
10000
8000
6000
4000
2000
1000
800
600
400
CFM
200
100
80
60
40
20
10
0.01 .03
INLET SIZE 16
INLET SIZE 14
INLET SIZE 12
INLET SIZE 10
INLET SIZE 08
INLET SIZE 06
.05
FLOW PROBE PRESSURE DIFFERENTIAL IN. WG
0.1
0.3 0.5
Fig. 8 — Linear Probe CFM vs Signal Chart
1
3709
2840
2086
1449
927
CFM @ ONE INCH SIGNAL
522
Determine the design air velocity by dividing the design air volume (the flow at 1.0 in. wg) by the nominal inlet area (sq ft). This factor is the K factor.
Carrier inlet areas are shown in Table 7. The design air volume is shown. It can be determined from Table 7 that the average design air velocity for units is equal to 0.2656 fpm at
1.0-in. wg.
Table 7 — Inlet Areas — 45J,K,M,N,Q,R
INLET
DIAMETER (in.)
Cfm at
1 in. wg
Inlet Area
(sq ft)
NOTE: For ComfortID™ terminals, all flow sizes are normalized using a single probe multiplier (PMF) for all sizes equal to 2.273.
6.0 8.0 10.0 12.0 14.0 16.0
522 927 1449 2086 2840 3709
0.196 0.349 0.545 0.785 1.069 1.396
START-UP
General —
must be operating in accordance with the specifications for air capacity, static pressure, and temperature. Record data on a unit performance sheet (Fig. 9). The following items must be checked:
1. All fans must be running at calculated and specified rpm.
2. Permanent or temporary filters must be clean and in­stalled where required.
3. All central station dampers must be adjusted and operat­ing properly.
4. All thermostats must be calibrated and at the desired settings.
Before balancing the system, the air handlers
5. All ductwork must be tight.
6. All dirt or loose lining must be removed from inside ductwork.
7. Pumps and sprays, when used, must be in operation.
8. Connections to the coil, when used, must be checked.
9. Water control valve, if used, must be checked.
IMPORTANT: Before proceeding with start-up, be cer­tain that voltage, frequency, and phase correspond to unit specifications. Unless noted, all fan motors are 60 Hz, 115, 208/230, or 277 v, single-phase ac.
NOTE: All 45 Series terminal units are shipped with cardboard packaging restraints placed inside both sides of the blower housing internal to the blower/motor. These restraints are pro­vided to prevent damage to the motor during shipment. The restraints MUST BE REMOVED prior to operation.
Remove the bottom access panel to remove the cardboard
packing material.
Carrier Corporation will not accept responsibility for any
additional costs for removal of this packaging material.
Initial Start-Up Procedures
NOTE: The following steps MUST be followed in order to properly operate and service this unit.
1. Disconnect all electrical power to the unit. Failure to dis­connect the power to the fan box prior to checking and/or servicing the fan box could result in a serious injury.
2. Verify that the fan box is installed level, and that adequate mounting support has been provided.
3. Remove motor access panel from the bottom of the fan box, and also remove the control panel cover.
9
4. Test the fan motor setscrew. The setscrew should fit tightly, but it may have come loose during shipment or installation.
5. Rotate the blower by hand to ensure proper clearance be­tween the blower and the blower housing.
6. Check the fan box for loose fiberglass insulation, espe­cially on the electric heater elements or the hot water coils (if these accessories are installed).
7. Check the control enclosure and remove any debris.
8. Check the induction inlet filter (if provided) for obstruc­tions, and verify the filter is securely in place.
9. Verify the main power supply to the connection to the fan box for proper voltage. If the fan box is installed with electric heat, the electric heat voltage may exceed the blower motor voltage requirement. Excessive voltage to the fan box may seriously damage it. Verify that the DDC (if equipped) are receiving 24-v ac, –15%, +20%.
10. Identify the control system supplied.
11. Check all control connections (and/or electric) for proper installation.
12. Connect electrical power.
Balancing Carrier Fan Terminals — Carrier fan
terminal units contain primary air dampers which, under the control of a volume controller, regulate the amount of cold air distributed to the space.
45J,K,Q SERIES FLOW UNITS — The 45J,K,Q series flow terminals direct all primary air through the unit fan. The termi­nal is designed to operate with the fan supplying airflow equal to or greater than the airflow supplied by the VAV damper. To balance the unit, therefore, it is necessary to first set the fan flow, and then the VAV damper (primary) flow.
Each control option has specific procedures required for balancing the unit, but some steps are common to all 45J,K,Q units. The fan box adjustments described below must be made in conjunction with the adjustments described in the Speed Controller section.
The VAV damper airflow may be set at the factory, but the fan airflow must be set in the field as described below.
Setting Fan Airflow NOTE: If the unit has electric heat or hot water heat, tempo-
rarily disable these functions before balancing the fan.
If unit has optional electric heat disconnect downstream of fan motor connections to power, open disconnect.
If unit does not have optional electric heat disconnect, re­move one electric heat power line connection. Be sure to insulate loose line from ground wire or other wires.
1. Set the controller to provide heating airflow demand only. Typically, this is accomplished by setting the thermostat to the highest possible temperature setting.
2. Determine that the VAV valve is fully closed and that the fan is rotating in the proper direction. (If the VAV damper is open when the fan is started and there is primary air in the system, the fan may start and run backward.)
3. Using a flow hood or duct traverse, determine the deliv­ered fan airflow (cfm).
NOTE: Both flow hood and duct traverse are subject to measurement errors. Be sure that all applicable measure­ment precautions are taken.
4. Compare the actual cfm in heating mode to the designed airflow. If there is a minimum setting for the VAV damper in heating mode (as recommended by ASHRAE [Ameri­can Society of Heating, Refrigeration, and Air
Conditioning Engineers] Standard 62), this quantity is in­cluded in the total measured heating airflow to determine if the desired induction airflow level has been met.
5. Adjust the fan SCR at unit control box to achieve the desired airflow rate. Refer to the performance data tables (Tables 8-10) to ensure airflow through electric heaters meets the requirements before operating the heater.
Setting of VAV (Primary) Airflow Adjustment of Set Points — Each 45J, 45K, and 45Q supplied
with controls is equipped with a pneumatic or electronic vol­ume controller which regulates the quantity of cold primary air entering the terminal and the conditioned space. If required air­flow levels are specified with the job order, the minimum and maximum cfm levels will be set at the factory where applica­ble. If minimum and maximum levels are not specified, a default value of 0 is used for minimum setting at the factory. Other settings of minimum and maximum primary airflow must be set in the field. Airflow (cfm) ranges for the primary air damper are shown in Tables 8-10. The minimum primary airflow (other than zero) is the minimum flow rate controllable by the unit volume controller. The primary air damper can be set at zero for shutoff or at the minimum cfm listed.
Field Adjustment of Minimum and Maximum Airflow Set Points — Each 45J, 45K, and 45Q unit is equipped with a lin-
ear averaging flow probe which provides an amplified differ­ential pressure that is proportional to the unit airflow. Output from this probe is used to provide a flow signal to both pneu­matic and electronic controls. Unit airflow (cfm) can be read directly from the flow probe on the unit (refer to Fig. 8).
1. With the unit airflow from the fan set, turn on primary (VAV) air supply.
2. To set cfm in the field, connect a gage to the flow probe at the provided ‘T’ taps, and check the differential pressure. (Alternately, the total flow may be measured, and the pre­viously determined fan induction flow rate may be sub­tracted from the total flow to determine VAV flow. However, for low primary settings, this may not be as accurate as the flow tap method.)
3. If a minimum VAV flow is required in heating mode, ad­just the volume until the differential pressure corresponds to the cfm required.
4. Set the controller to provide maximum cooling demand. This is typically accomplished by first setting the thermo­stat to the lowest possible temperature setting.
a. In most series fan boxes, the primary airflow rate is
equal to the fan induction flow; in these cases, adjust the volume controller until a balance is achieved between fan induced airflow and primary airflow. When a balance exists, a strip of paper hung at the induction port should hang straight down, and neither be blown in or out of the unit.
b. If the VAV airflow desired is less than the fan
induction flow, adjust the volume controller until the differential pressure (measured through the flow probe as described above) corresponds to the cfm required. Verify that induction exists through the inlet ports, using the paper strips as described above. When induction exists, the paper strip should be pulled into the unit.
5. Return all reheat options to normal connections.
6. Cap the ‘T’ taps.
7. Reset the thermostat to a normal setting. NOTE: It is normal for the total airflow to the room to in-
crease slightly in full cooling mode.
10
AIR TERMINAL PERFORMANCE SHEET
JOB NAME ________________________________________
JOB LOCATION ____________________________________
CUSTOMER ________________________________________
ENGINEER ________________________________________
BUILDING LOCATION/FLOOR ________________________
BUS NUMBER ______________________________________
CONTROL SET POINTS
Tag
Number
Zone
Address #
Box Size
(in./cfm)
Cooling
(Cfm)
min max min max Type Btu min max min max mult.
Fan cfm
Heating
(Cfm)
Heat kW Occupied Unoccupied
Calibration
Gain
Fig. 9 — Air Terminal Performance Sheet
11
Table 8 — 45J Series Fan Powered Terminal Unit Performance
UNIT SIZE
45J
INLET
SIZE
(in.)
2 6
3
4
5
6
6 8 990 300 920 170 or 0 93 or 0
8 10 1440 550 1430 250 or 0 145 or 0 10 12 2100 1100 2060 360 or 0 210 or 0 12 14 2530 1200 2530 500 or 0 285 or 0
7* 16 (2)
MOTOR
HP
1
/
10
1
/
4
1
/
4
1
/
2
3
/
4
3
/
120V 208/240V 277V Max Min Max Min
1.8 1.0 0.7 560 100 515 90 or 0 52 or 0
3.6 2.0 1.5
5.0 2.8 2.1
8.3 4.6 3.5
9.5 5.8 4.4
N/A 13.2 9.9 3900 2100 3660 650 or 0 370 or 0
4
MOTOR
AMPS
LEGEND
ASHRAE— American Society of Heating, Refrigeration and Air
DDC Direct Digital Controls
Conditioning Engineers
*45J unit size 7 is not available with 120 v motor option.
NOTES:
1. 45J maximum primary airflow (cfm) is set by the maximum induced airflow, which may vary as a function of downstream pressure. Maximum airflow shown is based on the maximum induced airflow (fan airflow) or 1.00 in. wg velocity pressure at inlet probe, whichever is less.
2. Minimum recommended primary airflow (cfm) is based on
0.03 in. wg differential pressure of the linear inlet flow sensor, or 0 airflow. 0.03 in. wg is equal to 15% to 20% of the nominal
FAN AIRFLOW (cfm) PRIMARY AIRFLOW (cfm)
Min
ComfortID
990 300 515 90 or 0 52 or 0
1440 550 920 170 or 0 93 or 0
2100 1100 1430 250 or 0 145 or 0
2530 1200 2060 360 or 0 210 or 0
flow rating of the terminal. Less than 15% to 20% may result in greater than +5% control of box flow.
3. 45J maximum fan airflow is based on 0.10 in. wg downstream static pressure.
4. 45J minimum fan airflow (cfm) is based on maximum external (downstream) static pressure 0.60 in. wg.
5. Minimum primary airflow (cfm) listed is for all controls except ComfortID controls which is shown separately with lower avail­able minimum cfm. Some DDC controls supplied by others may have different limitations.
6. Do not select discharge temperature exceeding 120 F. In addi­tion, ASHRAE recommends a maximum discharge tempera­ture of 90 F to avoid room air stratification when heating from the ceiling (2001 Fundamentals, Chapter 32).
Table 9A — 45K Quiet Series Fan Powered Terminal Unit Performance (PSC Motor)
UNIT
SIZE
45K
2
3
4
5
6
7
ARI — Air Conditioning and Refrigeration Institute DDC — Direct Digital Controls FLA — Full Load Amps PSC — Permanent Split Capacitor Motor Ps Static Pressure
INLET
SIZE (in.)
10 1150 250 or 0 145 or 0
10 1400 250 or 0 145 or 0 12 1425 360 or 0 210 or 0 10
14 1900 500 or 0 285 or 0 10 12 2100 360 or 0 210 or 0 14 2500 500 or 0 285 or 0 16 2600 650 or 0 370 or 0 10 12 2100 360 or 0 210 or 0 14 2500 500 or 0 285 or 0 16 3000 650 or 0 370 or 0
LEGEND *Max based on 0.1 in. wg downstream Ps for PSC motors. See Catalog for
PSC MOTOR
HP
6 8 530 170 or 0 93 or 0 6
6 8 900 170 or 0 93 or 0
1
/
10
1
/
4
1
/
4
1
/
2
3
/
4
112.87.17.15.3
120 V
FLA
1.4 0.8 0.8 0.6
4.3 2.4 2.4 1.8
4.3 2.4 2.4 1.8
8.3 4.4 4.4 3.5
9.5 5.0 5.0 4.4
MOTOR AMPS PRIMARY AIRFLOW FAN AIRFLOW*
208 V
FLA
240 V
FLA
277 V
FLA
complete fan curves. Min based on 0.6 in. wg downstream Ps for PSC motors.
†For all controls except ComfortID controls. Some DDC controls supplied by
others may have differing limitations.
NOTES:
1. Data is based on tests conducted in accordance with ARI Standard 880-
98.
2. Minimum airflow for cooling or cooling with hot water heat is the mini­mum flow rate controllable by the unit volume controller; shutoff or zero is also acceptable.
Max with
PSC
500 90 or 0 52 or 0
500 90 or 0 52 or 0
500 90 or 0 52 or 0
1400 250 or 0 145 or 0
1400 250 or 0 145 or 0
1400 250 or 0 145 or 0
Min†
ComfortID
Min
Max PSC
530 50
1150 1858 900 170 or 0 93 or 0
1425 500
1900 80012 1900 360 or 0 210 or 0
2600 1200
3000 1250
Min
PSC
12
Table 9B — 45K Quiet Series Fan Powered Terminal Unit Performance (ECM Motor)
UNIT SIZE
45K
3
6
7
ARI — Air Conditioning and Refrigeration Institute ECM — Electronically Commutated Motor FLA — Full Load Amps
*Special order.
†This value is based on signal of 0.03 in. wg differential pressure of the linear
averaging probe.
INLET
SIZE (in.)
LEGEND
ECM MOTOR
HP
6
8 900 170 or 0 93 or 0 10 1400 250 or 0 145 or 0 12 1400 360 or 0 209 or 0 10 12 2000 360 or 0 209 or 0 14 2000 500 or 0 284 or 0 16 2000 650 or 0 370 or 0 10 1400 250 or 0 145 or 0 12 2100 360 or 0 209 or 0 14 2500 500 or 0 284 or 0 16 2500 650 or 0 370 or 0
1
/
2
1 12.8 9.4 6.9
120 V FLA* 240 V FLA* 277 V FLA Max with ECM Min†
ECM MOTOR AMPS PRIMARY AIRFLOW FAN AIRFLOW
7.7 5.0 4.1
Table 10 — 45Q Low Profile Series Fan Powered Terminal Unit Performance
UNIT
SIZE
45Q
2
3 4
LEGEND
DDC — Direct Digital Controls Ps Static Pressure
NOTES:
1. 45Q maximum primary airflow (cfm) is set by the maximum induced airflow, which may vary as a function of downstream pressure. Maximum airflow shown is based on the maximum induced airflow (fan airflow) or 1.00 in. wg velocity pressure at inlet probe, which­ever is less.
2. Minimum recommended primary airflow (cfm) is based on 0.03 in. wg differential pressure of the linear inlet flow sensor, or 0 airflow.
0.03 in. wg is equal to 15% to 20% of the nominal flow rating of the terminal. Less than 15% to 20% may result in greater than +5% control of box flow.
INLET
SIZE (in.)
6 8
8
8 x 14 (2) 1/
MOTOR
HP
1
/
6
1
/
6
1
/
4
6
MOTOR AMPS FAN AIRFLOW (cfm) PRIMARY AIRFLOW (cfm)
120V 208/230V 277V Max Min Max Min
2.8 1.5 1.1 840 310 522 90 52 0.04
2.8 1.5 1.1 840 310 840 160 93 0.06
4.1 2.2 1.6 1090 520 927 160 93 0.07
6.9 3.7 2.7 1650 800 1650 358 207 0.10
Min
500 90 or 0 52 or 0
1400 250 or 0 145 or 0
NOTES:
1. Data is based on tests conducted in accordance with ARI Standard 880-
98.
2. Minimum airflow for cooling or cooling with hot water heat is the minimum flow rate controllable by the unit volume controller; shutoff or zero is also acceptable.
3. 45Q maximum fan airflow is based on 0.10 in. wg downstream static pressure.
4. 45Q minimum fan airflow (cfm) is based on maximum external (downstream) static pressure 0.60 in. wg.
5. Minimum primary airflow (cfm) listed is for all controls except Com­fortID control which is shown separately with lower available mini­mum CFMs. Some DDC controls supplied by others may have different limitations.
6. Do not select discharge temperature exceeding 120 F. In addition, ASHRAE (American Society of Heating, Refrigeration, and Air Con­ditioning Engineers) recommends a maximum discharge tempera­ture of 90 F to avoid room air stratification when heating from the ceiling (2001 Fundamentals, Chapter 32).
ComfortID
Max ECM Min ECM
1030 250
2000 500
2500 600
Min
ComfortID
MINIMUM
Ps. (in. wg)
BALANCING 45M,N,R PARALLEL FLOW UNITS — A parallel fan terminal is designed to operate with the fan supply­ing air equal to 40 to 60% of the VAV damper maximum set­ting. Adjustments to the parallel units fan should be made with the primary air closed off. Refer to unit capacity tables to ensure airflow through the electric heater meets the minimum requirements before operating heater.
Each control option has specific procedures required for balancing the unit, but some steps are common to all parallel fan units, as described below.
To balance parallel fan unit: Setting Fan Airflow NOTE: If the unit has electric heat or hot water heat, tempo-
rarily disable these functions before balancing the fan.
If unit has optional electric heat disconnect downstream of fan motor connections to power, open disconnect.
If unit does not have optional electric heat disconnect, re­move one electric heat power line connection. Be sure to insu­late loose line from ground wire or other wires.
1. Set the controller to provide heating airflow demand only. Typically, this is accomplished by setting the thermostat to the highest possible temperature setting.
2. Determine that the VAV damper is fully closed. This may require a temporary override of the VAV controller. Do not adjust minimum and maximum cfm set points at this time.
3. Using a flow hood or duct traverse, determine the deliv­ered fan airflow (cfm).
NOTE: Both flow hood and duct traverse are subject to measurement errors. Be sure that all applicable measure­ment precautions are taken.
4. Compare the required design cfm in heating mode to the actual delivered airflow. If there is a minimum setting for the VAV damper in heating mode (as recommended by ASHRAE [American Society of Heating, Refrigeration, and Air Conditioning Engineers] Standard 62), this quan­tity is included in the total measured airflow.
5. Adjust the fan SCR at unit control box to achieve the de­sired airflow rate.
Setting of VAV (Primary) Airflow Adjustment of Set Points — Each parallel fan unit is equipped
with a pneumatic or electronic volume controller which regu­lates the quantity of cold primary air entering the terminal and the conditioned space. If required airflow levels are specified
13
with the job order, the minimum and maximum cfm levels will be set at the factory. If minimum and maximum levels are not specified, a default value is used. Other settings of minimum and maximum primary airflow must be set in the field. Airflow (cfm) ranges for the primary air damper are shown in Tables 11-13 for 45M,N,R units. The minimum primary air­flow (other than zero) is the minimum flow rate controllable by the unit volume controller. The primary air damper can be set at zero for shutoff or at the minimum cfm listed.
Field Adjustment of Minimum and Maximum Airflow Set Points — Each parallel fan unit is equipped with a linear aver-
aging flow probe which provides an amplified differential pressure that is proportional to the unit airflow. Output from this probe is used to provide a flow signal to both pneumatic and electronic controls. Unit airflow (cfm) can be read directly from the flow probe on the unit.
1. After the unit airflow from the fan has been set, turn on primary (VAV) air supply and turn off the fan.
2. To set cfm in the field, connect a gage to the flow probe and check the differential pressure.
3. If a minimum VAV flow is required in heating mode, ad­just the volume controller until the differential pressure corresponds to the cfm required.
Table 11 — 45M Parallel Fan Powered Terminal Unit Performance
4. Some control sequences allow the fan to start before the VAV damper reaches minimum setting, for an overlap­ping of fan and VAV flow. For these sequences, after con­troller min airflow has been adjusted, the total airflow with both fan and primary airflow should be checked. For sequences that call for the fan to start as the first stage of heat, the cooling minimum cfm can be verified at the diffuser.
Setting the minimum control point will typically require careful adjustment of the thermostat to create a minimum cooling demand signal.
5. a. Set the controller to provide maximum cooling de-
mand. This is typically accomplished by setting the thermostat to the lowest possible temperature set­ting. For most control sequences, this will cause the fan to shut off.
b. Adjust the volume controller until the differential
pressure (measured through the flow probe as described above) corresponds to the cfm required.
6. Return all reheat options to normal connections.
7. Cap the ends of the inlet flow sensors.
8. Reset the thermostat to a normal setting.
INLET
UNIT
SIZE
2
3
4
5
6
7 16
LEGEND
ASHRAE — American Society of Heating, Refrigeration and Air
DDC Direct Digital Controls EH Electric Heat HW Hot Water Heat
NOTES:
1. 45M maximum primary airflow (cfm) is based on 1.00 in. wg velocity pressure signal (VP), per inlet size, using a standard linear averaging sensor.
2. Minimum recommended primary airflow (cfm) is based on
0.03 in. wg differential pressure of the linear inlet flow sensor, or 0 airflow. 0.03 in. wg is equal to 15% to 20% of the nominal
MOTOR
SIZE
(in.)
6 8 400 200 920 170 or 0 93 or 0 .33 .49 .64
8 10 600 300 1430 250 or 0 145 or 0 .35 .74 .94 10 12 1050 480 2060 360 or 0 210 or 0 .36 .71 .88 12 14 1500 860 2800 500 or 0 285 or 0 .34 .77 1.08 14 16 1800 930 3660 650 or 0 370 or 0 .35 .94 1.36
HP
120V 208/240V 277V Max Min Max Min
1
/
10
1
/
10
1
/
4
1
/
2
1
/
2
3
/
4
Conditioning Engineers
MOTOR
AMPS
1.6 0.9 0.7
2.0 1.2 0.9
3.2 1.9 1.4
7.3 4.1 3.1
10.1 5.1 4.2
9.5 5.8 4.4 2200 1140 3660 650 or 0 370 or 0 .35 .67 .89
FAN AIRFLOW
(cfm)
400 50 515 90 or 0 52 or 0 .32 .37 .42
600 150 920 170 or 0 93 or 0 .33 .48 .56
1050 250 1430 250 or 0 145 or 0 .35 .52 .60
1500 860 2060 360 or 0 210 or 0 .36 .60 .77
1800 930 2800 500 or 0 285 or 0 .34 .68 .92
PRIMARY AIRFLOW
(cfm)
Min
ComfortID
flow rating of the terminal. Less than 15% to 20% may result in greater than +5% control of box flow.
3. 45M maximum fan airflow (cfm) is based on 0.25 in. wg exter­nal (downstream) static pressure.
4. 45M minimum fan airflow (cfm) is based on maximum external (downstream) static pressure 0.60 in. wg.
5. Minimum primary airflow (cfm) listed is for all controls except ComfortID controls which is shown separately with lower avail­able minimum cfm. Some DDC controls supplied by others may have different limitations.
6. Do not select discharge temperature exceeding 120 F. In addi­tion, ASHRAE recommends a maximum discharge tempera­ture of 90 F to avoid room air stratification when heating from the ceiling (2001 Fundamentals, Chapter 32).
No or EH 1 row HW 2 row HW
MINIMUM
OPERATING
PRESSURE
(in. wg)
14
Table 12A — 45N Quiet Parallel Fan Powered Terminal Unit Performance (PSC Motor)
UNIT
SIZE
DDC — Direct Digital Controls EH Electric Heat HW — Hot Water Ps Static Pressure PSC — Permanent Split Capacitor Motor
INLET
SIZE (in.)
2
3
4
5
6
7
LEGEND *Max based on 0.25 in. wg downstream Ps for PSC motors. See Catalog for
MOTOR
Hp
6 8 920 160 or 0 93 or 0 0.33 0.42 0.50 6 8 920 160 or 0 93 or 0 0.33 0.41 0.44
10 1430 250 or 0 145 or 0 0.32 0.52 0.58
6
8 920 160 or 0 93 or 0 0.33 0.41 0.43 10 1430 250 or 0 145 or 0 0.32 0.51 0.58 12 2060 360 or 0 210 or 0 0.34 0.77 0.91 10 12 2060 360 or 0 210 or 0 0.34 0.48 0.91 14 2800 480 or 0 285 or 0 0.28 0.48 1.08 10 12 2060 360 or 0 210 or 0 0.34 0.49 0.58 14 2800 480 or 0 285 or 0 0.28 0.49 0.61 16 3660 630 or 0 370 or 0 0.28 0.63 0.85 10 12 2060 360 or 0 210 or 0 0.34 0.48 0.58 14 2800 480 or 0 285 or 0 0.28 0.48 0.61 16 3660 630 or 0 370 or 0 0.28 0.62 0.85
1
/
4
1
/
4
1
/
4
1
/
2
1
/
2
3
/
4
MOTOR AMPS FAN AIRFLOW* PRIMARY AIRFLOW MINIMUM PRESSURES, Ps in. wg
120 V 208/240 V 277 V Max Min Max Min†
2.6 1.5 1.1 500 50
3.1 1.7 1.3 800 50
3.4 1.9 1.4 900 50
7.3 4.1 3.1 1700 375
7.3 4.1 3.1 1800 400
9.5 5.8 4.4 2000 625
Min
515 90 or 0 52 or 0 0.31 0.34 0.36
515 90 or 0 52 or 0 0.31 0.34 0.35
515 90 or 0 52 or 0 0.31 0.34 0.34
1430 250 or 0 145 or 0 0.32 0.39 0.58
1430 250 or 0 145 or 0 0.32 0.39 0.43
1430 250 or 0 145 or 0 0.32 0.39 0.43
complete fan curves. Min based on 0.6 in. wg downstream Ps for PSC motors.
†For all controls except ComfortID controls. Some DDC controls supplied by
others may have differing limitations.
NOTE: Data is based on tests conducted in accordance with ARI (Air Condi­tioning and Refrigeration Institute) Standard 880-98.
ComfortID
No or EH 1 Row HW 2 Row HW
Table 12B — 45N Quiet Parallel Fan Powered Terminal Unit Performance (ECM Motor)
UNIT SIZE
4
7
LEGEND
DDC — Direct Digital Controls ECM — Electronically Commutated Motor FLA — Full Load Amps
*Special order.
INLET
SIZE (in.)
6
8 900 170 or 0 93 or 0 10 1400 250 or 0 145 or 0 12 2100 360 or 0 210 or 0 10 12 2100 360 or 0 210 or 0 14 2500 500 or 0 285 or 0 16 3300 650 or 0 370 or 0
MOTOR
Hp
1
/
2
1 12.8 9.4 6.9
120 V FLA* 240 V FLA* 277 V FLA Max Min†
ECM MOTOR AMPS PRIMRY AIRFLOW ECM FAN AIRFLOW
7.7 5.0 4.1
Table 13 — 45R Low Profile Parallel Fan Powered Terminal Unit Performance
UNIT SIZE
45R
INLET
SIZE
2
8 x 14
4
(in.)
MOTOR
HP
6 8
1
/
6
1
/
6
1
/
4
LEGEND
ASHRAE— American Society of Heating, Refrigeration and Air
DDC Direct Digital Controls Ps Static Pressure
NOTES:
1. 45R maximum primary airflow (cfm) is based on 1.00 in. wg velocity
2. Minimum recommended primary airflow (cfm) is based on 0.03 in.
Conditioning Engineers
pressure signal (VP), per inlet size, using a standard linear averag­ing sensor.
wg differential pressure of the linear inlet flow sensor, or 0 airflow.
0.03 in. wg is equal to 15% to 20% of the nominal flow rating of the terminal. Less than 15% to 20% may result in greater than +5% control of box flow.
MOTOR AMPS FAN AIRFLOW (cfm)
120V 208/230V 277V Max Min Max Min
2.8 1.5 1.0 620 250 522 90 52 0.10 0.10 0.10
2.8 1.5 1.0 620 250 927 160 93 0.18 0.18 0.18
3.9 2.1 1.4 830 450 2066 358 207 0.17 0.17 0.17
Min
500 90 or 0 52 or 0
1400 250 or 0 145 or 0
†For all controls except ComfortID controls. Some DDC controls supplied by
others may have differing limitations. This value is based on a signal of
0.03 in. wg differential pressure of the linear averaging flow probe.
NOTE: Data is based on tests conducted in accordance with ARI (Air Condi­tioning and Refrigeration Institute) Standard 880-98.
PRIMARY AIRFLOW
(cfm)
Min
ComfortID
3. 45R maximum fan airflow (cfm) is based on 0.25 in. wg external (downstream) static pressure.
4. 45R minimum fan airflow (cfm) is based on maximum external (downstream) static pressure 0.60 in. wg.
5. Minimum primary airflow (cfm) listed is for all controls except Com­fortID controls which is shown separately with lower available mini­mum CFMs. Some DDC controls supplied by others may have different limitations.
6. Minimum pressure, Ps (in. wg) on 45R water coil units is based on coil located on induction port.
7. Do not select discharge temperature exceeding 120 F. In addition, ASHRAE recommends a maximum discharge temperature of 90 F to avoid room air stratification when heating from the ceiling (2001 Fundamentals, Chapter 32).
ComfortID
MINIMUM Ps (in. wg)
None or
Elec. Heat
Max Min
1000 250
1600 400
1 Row
Hot Water
2 Rows
Hot Water
15
Speed Controller — Each Carrier fan powered air ter-
minal unit is equipped with a fan SCR speed controller, located on the bottom of the control box. The SCR can be adjusted in the field.
NOTE: The 45J size 7 unit and 45Q size 4 unit have 2 SCR speed controllers, one for each fan. One SCR is located in the standard position at the bottom of the control box; the other is at the top of the control box.
The fan airflow output is dependent on the setting of the
controller and the downstream static resistance.
CAUTION
The minimum stop on the speed controller is factory set at an internal minimum stop to prevent damage to the motor. Do not attempt to override this minimum stop or electrical damage to the fan motor may result.
TO INCREASE THE FAN SPEED (RPM), turn the slotted adjustment on the controller clockwise toward the “HI” mark­ing printed on the controller face plate. (Refer to Fig. 10.)
TO DECREASE THE FAN SPEED (RPM), turn the adjust­ment counterclockwise toward the “LO” marking. (See Fig. 10.)
ComfortID™ VAV CONTROLS
Install Sensors and Make Field Wiring Connections
GENERAL — All field wiring must comply with National Electrical Code and local requirements.
CAUTION
DO NOT run sensor or relay wires in the same conduit or raceway with Class 1 service wiring.
DO NOT abrade or nick the outer jacket of cable. DO NOT pull or draw cable with a force that may harm the
physical or electrical properties. DO NOT bend a cable through a radius sharper than that
recommended by its manufacturer. AVOID splices in any control wiring.
Perform the following steps if state or local code requires the use of conduit, or if your installation requires a cable length of more than 8 ft:
1. Disconnect the sensor cable from the ComfortID zone controller, at the terminals labeled SAT and GND.
2. Mount the sensor to the duct (see Steps 2 and 3 above).
3. Mount a field-supplied 4 in. x 4 in. x 2 in. extension box over the duct sensor.
4. Connect a conduit ( enclosure and extension box.
1
/2-in. nominal) to the zone controller
WARNING
Disconnect electrical power before wiring inside the con­troller. Electrical shock, personal injury, or damage to the zone controller can result.
Wire the control as shown on the control package diagram for the specific installation. Control wiring diagrams can be found inside the control box.
SUPPLY-AIR TEMPERATURE (SAT) SENSOR INSTAL­LATION — On terminals with heat, the SAT sensor is pro­vided. The sensor is factory wired to the controller and shipped in the control box. The SAT must be field-installed in the duct downstream from the air terminal. See Fig. 11. The SAT sensor part number is 33ZCSENSAT. See Table 14 for resistance information.
To install the sensor, proceed as follows:
1. Remove the plug from one of the control box and pass the sensor probe through the hole.
2. Drill or punch a
1
/2-in. hole in the duct downstream of the unit, at a location meeting the requirements shown in Fig. 11.
3. Using 2 self-drilling screws (supplied), secure the sensor probe to the duct.
The SAT sensor probe is 6 inches in length. The tip of the probe must not touch the inside of the duct. Use field-supplied bushings as spacers when mounting the probe in a duct that is 6 in. or less in diameter.
If the unit is not equipped with heat, the SAT sensor is not provided and is not required.
For units equipped with electric heat, locate the sensor as far downstream as possible. This ensures the sensor will not be affected by excessive radiant heat from the heater coil. Install the sensor a minimum of 2 ft downstream of the coil for units with hot water heat.
7
/8-in. openings in the
277 V 12L
LO
5 FLA
6
Z
50
RANCO
MXF-544002-001
100533-01
HI
UR
Fig. 10 — Fan Speed Controller
UNIT WITH HEAT
2 FT. MIN.
PRIMARY AIR INLET
LEGEND
SAT — Supply Air Temperature Sensor ZC Zone Controller
AIR
TERMINAL
UNIT
ZC
HEAT
Fig. 11 — Supply Air Temperature Probe
(Part No. 33ZCSENSAT) Location
SAT
16
Loading...
+ 36 hidden pages