Carrier 42TW, 42TD User Manual

42TW/TD
Chilled Water Fan Coil unit with Remote Control (50/60 Hz)
Insta
llation,
Se
ervice I
Start-
Installation and servicing air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters.
All other operations should be performed by trained service personnel When working on air­conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for un-brazing operations. Have fire extinguishers available for all brazing operations.
Up
and
tions
SAFETY CONSIDERATIONS
REMOTE CONTROL
Fig. 1 - 42TW Unit
ELECTRIC SHOCK HAZARD To avoid the possibility of electrical shock, open and tag all
service switches before installing this equipment.
CONTROL BOARD
WARNING
CONTENTS
Safety Consideration Introduction Receiving Inspection Protection Preliminary Check Physical Data
Sound Data Fan Performance Data Base Unit Dimensions Prepare Jobsite Identify and Prepare Units Unit Configuration Rigging and Unpacking Installation
Page Page
1
Placing unit in position
2
Making Piping Connections
2
Electrical Heater Option
2
Test and Insulate
2
Make Electrical Connections
2
Make Duct Connections
2
Make Final Preparation
4
Control Board & Remote control
5
Typical wiring digram
6
Start-up
7
Service
7
Start-up Checklist
7 7 7
7 7 8 8 8 8
8 9,10 11,12
13 13 14
-1-
- 2 -
INTRODUCTION
Size
03 05 06
07
09
11
12 16
CFM*
348
592
692
780
883
1181
1385
1572
Cooling Capacity (kw)*
3.4 6.1 7.5
8.9
9.9
11.5
14.5
16.9
Colling Capacity
(kbtuh)
11.7
20.7
25.6
30.4
33.8
39.2
49.5
57.7
SHR
0.75
0.74
0.72
0.71
0.71
0.75
0.73
0.73
Power Supply
208-230, 1 ph, 60 Hz / 220-240, 1 ph, 50 Hz / 110-127, 1 ph, 60 Hz
Motor HP(
Nominal)
1/15 1/10
1/15
1/10
Input W atts ( Med Speed, 25 Pa ESP)
56 64 70 80 80 130
146
160
Number of
Motors
1, 3
Speed
2, 3 Speed
Coil
Material
Smooth copper tubes/ Aluminum fins with double wavey fin
Coil Face Area,
m^2
0.11
0.15
0.21
0.26
0.31
0.31
0.44
0.52
Coil
Connection
Type
Sweat
Type
Coil
Connection Size
5/8
Inch
7/8
Inch
Number of
Rows
3
Fin Denisty/ Inch
14
Drain
Diameter
5/8
Inch
Blower type
Direct drive forward curved centerifugal fan
Blower
Number
1
2 4
Blower Diameter / Width, mm
156/220
156/170
156/220
156/170
156/220
Filter
Type
Washable Aluminum Filter
Width, mm
640
800
1010
1220
1430
1430
1430
1640
Depth, mm
590
Height, mm
275
375
Net Weight, kg
18 23 28 32 39 43 49 56
This document contains general installation instructions for the 42TW unit Fan Coils. Refer to the unit-wiring diagram installed on the blower housing or specific manufacturer literature for any other type of factory-mounted controls. See drawings for unit configurations, dimensions, clearances, and pipe connections. Refer to unit wiring label for all electrical connections; follow NEC (National Electrical Code) and local codes.
RECEIVING 42TW fan coil units are shipped individually packed in carton boxes. When cartons are individually off loaded from the truck, do not roll, nor throw, or drop the carton to avoid damage to the contents. Store boxes upright as the symbols on the boxes indicated. Do not stack units more than 6 units high for size 11-16 and 8 units high for other sizes.
INSPECTION Check the shipment against shipping list and remove unit from the carton and take off protective covering. If the unit has been
Table.1 -
Physical
Model 42TW3
Model
42T
Data - 42TW3, 42TD3 – 2 Pipe
D3
damaged, file claim with transportation company and notify Carrier immediately.
PROTECTION Protection unit from damage caused by job site debris. Do not allow dust, debris and water to get into the unit. These will damage unit’s component and unit’s performance will be affected.
PRELIMINARY Following is a checklist which should be checked before the installation is started. The installer should be familiar with each of the following requirements before the actual installation.
- Space requirement and clearance, See Fig.3.
- Ceiling or mounting strength.
- Piping connections.
- Condensate drain connection.
- Power supply and wiring.
- Air duct connections.
System
CHECK
* At 26.7/19 c approch 6.7c water inlet/12.7c water outlet, High speed @ 0 Static
- 3 -
Model 42TD 4
Size
03 04 05
06
08
10
11 14
CFM*
313
533
623
702
795
1065
1247
1416
Cooling Capacity (kw)*
3.8 6.2 7.7
9.0
9.9
12.7
15.7
17.6
Colling Capacity
(kbtuh)
13.0
21.0
26.3
30.8
33.7
43.3
53.6
60.1
SHR
0.69
0.71
0.69
0.69
0.69
0.7
0.68
0.69
Power Supply
208-230, 1 ph, 60 Hz / 220-240, 1 ph, 50 Hz / 110-127, 1 ph, 60 Hz
Motor HP
(Nominal)
1/15 1/10
1/15
1/10
Input W atts ( Med Speed, 25 Pa ESP)
52 60 65 75 75 121
136
150
Number of
Motors
1, 3
Speed
2, 3 Speed
Coil
Material
Smooth copper tubes/ Aluminum fins with double wavey fin
Coil Face Area
0.11
0.15
0.21
0.26
0.31
0.31
0.44
0.52
Coil
Connection
Type
Sweat
Type
Coil
Connection Size
5/8
Inch
7/8
Inch
Number of
Rows
4
Fin Denisty/ Inch
14
Drain
Diameter
5/8
Inch
Blower type Direct drive forward curved centerifugal fan
Blower
Number
1
2 4
Blower Diameter /
Width
156/220
156/170
156/220
156/170
156/220
Filter
Type
Washable Aluminum Filter
Width 640
800
1010
1220
1430
1430
1430
1640
Depth
590
Height
275
375
19 24 29 33 41 45 51 58
Model 42TW4
Size
03 04 05
06
08
10
11 14
CFM*
313
533
623
702
795
1065
1247
1416
Cooling Capacity (kw)*
3.4 5.3 6.9
8.0
8.9
11.2
14.1
15.9
Colling Capacity
(kbtuh)
11.6
18.1
23.5
27.3
30.4
38.2
48.1
54.3
Heating Capacity (kw)**
2.9 5.5 6.8
7.9
9.4
12.2
13.9
17.5
Heating Capacity
(kbtuh)
9.9 18.8
23.2
27.0
32.1
41.6
47.4
59.7
Power Supply
208-230, 1 ph, 60 Hz / 220-240, 1 ph, 50 Hz / 110-127, 1 ph, 60 Hz
Motor HP
(Nominal)
1/15 1/10
1/15
1/10
52 60 65 75 75
121
136
150
Number of
Motors
1, 3
Speed
2, 3 Speed
Coil
Material
Smooth copper tubes/ Aluminum fins with double wavey fin
Coil Face Area
0.11
0.15
0.21
0.26
0.31
0.31
0.44
0.52
Coil
Connection
Type
Sweat
Type
Coil
Connection
Size Cool & Heat
3/4 Inch & 5/8
Inch
Number of
Rows
4
Fin Denisty/ Inch
14
Drain
Diameter
5/8
Inch
Blower type
Direct drive forward curved centerifugal fan
Blower
Number
1
2 4
Blower Diameter /
Width
156/220
156/170
156/220
156/170
156/220
Filter
Type
Washable Aluminum Filter
Unit
Dimensions
640
800
1010
1220
1430
1430
1430
1640
590
275
375
Net
Weight
19 24 29 33 41 45 51 58
Table.2 -
Physical
Data - 42TW4,42TD4 – 2 Pipe
System
Model 42TW4
Net
Weight
* At 26.7/19 c approch 6.7c water inlet/12.7c water outlet, High speed @ 0 Static
Table.3 -
Physical
Data - 42TW4, 42TD4 – 4 Pipe
System
Model 42TD4
Width, Depth,
mm mm
Height, mm
* At 26.7/19 c approch 6.7c water inlet/12.7c water outlet, High speed @ 0 Static ** At 20 /14 c approch 70c water inlet/61.6c water outlet, High speed @ 0 Static
Table.4 a - POWER CONSUMPTION 42TW,42TD 3ROW
42TW,42TD ± 3Row
-03
-05
-06
-07
-09
-11
-12
-16
Amps
Watts
Amps
Watts
Amps
Watts
Amps
Watts
Amps
Watts
Amps
Watts
Amps
Watts
Amps
Watts
@ 0 Pa ESP @ 25 Pa ESP @ 50 Pa ESP
Hi Med Low Hi Med Low Hi Med Low
0.40 0.35 0.30 0.34 0.28 0.24 0.30 0.25 0.20 80 70 60 68 56 48 60 50 40
0.45 0.40 0.35 0.37 0.32 0.27 0.33 0.28 0.22 90 80 70 74 64 54 66 56 44
0.55 0.45 0.35 0.45 0.35 0.27 0.40 0.30 0.22
110 90 70 90 70 54 80 60 44
0.60 0.50 0.40 0.50 0.40 0.30 0.45 0.35 0.25
120 100 80 100 80 60 90 70 50
0.60 0.50 0.40 0.50 0.40 0.30 0.45 0.35 0.25
120 100 80 100 80 60 90 70 50
0.90 0.80 0.70 0.75 0.65 0.55 0.65 0.55 0.45
180 160 140 150 130 110 130 110 90
1.10 0.90 0.70 0.90 0.73 0.55 0.80 0.62 0.45
220 180 140 180 146 110 160 124 90
1.20 1.00 0.80 1.00 0.80 0.62 0.80 0.70 0.50
240 200 160 200 160 124 160 140 100
Table.4 b
42TW,42TD ± 4Row
-03
-04
-05
-06
-08
-10
-11
-14
Note: For 220V, 1 Phase Motor.
Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts
@ 0 Pa ESP @ 25 Pa ESP @ 50 Pa ESP
Hi Med Low Hi Med Low Hi Med Low
0.37 0.33 0.28 0.33 0.27 0.23 0.29 0.24 0.20
73 64 55 64 52 45 57 48 38
0.42 0.37 0.33 0.36 0.31 0.26 0.32 0.27 0.22
82 73 64 69 60 50 63 53 42
0.51 0.42 0.33 0.43 0.34 0.26 0.39 0.29 0.22
100 82 64 84 65 50 76 57 42
0.56 0.47 0.37 0.48 0.38 0.29 0.44 0.34 0.24
109 91 73 93 75 56 86 67 48
0.56 0.47 0.37 0.48 0.38 0.29 0.44 0.34 0.24
109 91 73 93 75 56 86 67 48
0.84 0.75 0.65 0.72 0.62 0.53 0.64 0.54 0.44
164 145 127 140 121 103 124 105 86
1.03 0.84 0.65 0.86 0.70 0.53 0.78 0.61 0.44
200 164 127 168 136 103 152 118 86
1.12 0.93 0.75 0.96 0.77 0.60 0.78 0.68 0.49
218 182 145 187 150 116 152 133 95
Table.5 a -SOUND PRESSURE
42TW,42TD ± 3Row
42TW3-03 42TW3-05 42TW3-06 42TW3-07 42TW3-09 42TW3-11 42TW3-12 42TW3-16
@ 0 Pa ESP @ 25 Pa ESP @ 50 Pa ESP
Hi Med Low Hi Med Low Hi Med Low
47.5 45.5 43.5 46.5 44.0 42.5 45.5 42.5 41.0
48.5 46.5 44.5 47.5 45.0 43.5 46.5 43.5 42.0
50.0 48.0 46.0 49.0 46.5 45.0 48.0 45.0 43.5
50.5 48.5 46.5 49.5 47.0 45.5 48.5 45.5 44.0
50.0 48.0 46.0 49.5 47.0 45.5 48.5 45.5 43.5
51.0 49.0 47.0 50.0 47.5 46.0 49.0 46.0 44.0
51.0 49.0 47.0 50.0 47.5 46.0 49.0 46.0 44.5
51.5 49.5 47.5 50.5 48.0 46.5 49.5 46.5 45.0
Table.5 b
42TW ± 4Row
42TW4-03 42TW4-04 42TW4-05 42TW4-06 42TW4-08 42TW4-10 42TW4-11 42TW4-14
Note: Assumes "standard room ", 3 meters from exit, no ducts, ducts will further reduce sound
@ 0 Pa ESP @ 25 Pa ESP @ 50 Pa ESP
Hi Med Low Hi Med Low Hi Med Low
46.5 44.5 42.5 46.0 43.5 42.0 45.0 42.0 40.5
47.5 45.5 43.5 47.0 44.5 43.0 46.0 43.0 41.5
49.0 47.0 45.0 48.5 46.0 44.5 47.5 44.5 43.0
49.5 47.5 45.5 49.0 46.5 45.0 48.0 45.0 43.5
49.0 47.0 45.0 49.0 46.5 45.0 48.0 45.0 43.0
50.0 48.0 46.0 49.5 47.0 45.5 48.5 45.5 43.5
50.0 48.0 46.0 49.5 47.0 45.5 48.5 45.5 44.0
50.5 48.5 46.5 50.0 47.5 46.0 49.0 46.0 44.5
-4-
Table.6 a - Fan Performance ± 42TW-3-SI
L
423
629
845
938
1011
1257
1690
1876
L
383
572
769
854
919
1144
1538
1707
42TW3 Air Flow (m3/hr)
Ex. Static Pres. Pa 0 12.5 25 37.5
Unit Size H M L H M
03 05 06 07 09 11 12 16
592 515 466 568 481 1005 846 694 940 761 1176 995 931 1132 943 1325 1174 1031 1284 1090 1500 1285 1120 1420 1178 2007 1690 1385 1879 1521 2353 1991 1862 2265 1886 2671 2349 2062 2569 2180
42TW3 Air Flow (m3/hr)
Ex. Static Pres. Pa 50 62.5 75
Unit Size H M L H M L H M L
03 05 06 07 09 11 12 16
H ± At High Fan Speed. M ± At Medium Fan Speed. L ± At Low Fan Speed.
460 358 250 380 270 ± 305 ±± 718 541 389 625 439 ± 524 ±±
919 715 499 737 541 ± 559 ±± 1031 788 634 890 651 ± 769 ±± 1120 865 650 1000 740 ± 862 ±± 1437 1082 777 1251 879 ± 1048 ±± 1839 1430 997 1437 1055 ± 1091 ±± 2062 1575 1268 1770 1295 ± 1530 ±±
HML HML
544 446 380 502 402 315
875 676 564 794 600 473 1088 891 759 1024 791 634 1243 1006 845 1158 896 752 1340 1071 902 1230 968 776 1751 1352 1129 1589 1200 946 2177 1781 1518 2048 1582 1268 2467 2011 1690 2315 1791 1504
Table.6 b - Fan Performance ± 42TW - 4 - SI
42TW4 Air Flow (m3/hr)
Ex. Static Pres. Pa 0 12.5 25 37.5
Unit Size H M L H M
03 05 06 07 09 10 11 14
532 463 419 517 437
905 764 625 855 693 1059 896 840 1030 858 1192 1058 931 1168 992 1350 1156 1007 1291 1072 1809 1524 1249 1710 1384 2119 1793 1679 2061 1716 2406 2118 1859 2338 1984
42TW4 Air Flow (m3/hr)
Ex. Static Pres. Pa 50 62.5 75
Unit Size H M L H M L H M L
03 05 06 07 09 10 11 14
H ± At High Fan Speed. M ± At Medium Fan Speed. L ± At Low Fan Speed.
433 336 235 363 279 ± 296 ±± 675 509 366 594 417 ± 503 ±± 864 672 469 700 514 ± 537 ±±
969 741 596 846 618 ± 738 ±± 1063 813 602 950 715 ± 825 ±± 1351 1017 730 1188 835 ± 1006 ±± 1729 1344 937 1365 1002 ± 1047 ±± 1938 1481 1192 1682 1230 ± 1469 ±±
HML HML
502 411 350 467 373 292
805 622 519 738 558 440 1001 820 698 952 736 590 1144 926 777 1077 833 699 1232 987 831 1148 900 717 1611 1244 1039 1478 1116 880 2003 1639 1397 1905 1471 1179 2270 1850 1555 2153 1666 1399
-5-
PREPARE JOSITE FOR UNIT INSTALLATION
To save time and to reduce the possibility of costly errors, set up a complete sample installation in a typical room at jobsite. Check all critical dimensions such as pipe, wire, and duct connection requirements. Refer to job drawings and product dimension drawings as required. Instruct all trades in their part of the installation.
IDENTIFY AND PREPARE UNITS
Be sure power requirements match available power source. Refer to unit nameplate and wiring diagram.
1. Check all tags on unit to determine if shipping screws are to be removed. Remove screws as directed.
2. Rotate the fan wheel by hand to ensure that the fan is unrestricted and can rotate freely. Check for shipping damage and fan obstructions.
UNIT CONFIGURATION
The piping connections, drain pan outlet and control box are located on the right side of the unit facing the airflow direction as factory standard as shown in the unit picture. Left hand side connection is factory option. However, the connections side can be relocated at site.
RIGGING AND UNPACKING
Unit should not be removed from carton until reaching final location to avoid damage. Inspect unit for shipping damage and file claim with transportation company if necessary, check nameplate voltage
against available power supply. For special installation, consult local building and electrical codes.
INSTALLATION PLACING UNIT IN POSITION
1. Select the unit location. Allow adequate space for free air circulation, service clearances, piping and electrical connections, and any necessary ductwork, see fig.2. For specific unit dimensions, refer to the submittal drawings. Allow clearances according to the local and national electrical codes.
2. Be sure either the ceiling is able to support the weight of the unit. See Table 1-3 for nominal unit weight.
3. Move unit into position. Ensure unit is level or pitched towards drain to ensure proper drainage and operation.
4. Mounting units to the ceiling - When unit is lifted, access to the. mounting holes is on the top panel of the unit. Hanger rods, fasteners, and other required hardware must be field-supplied.
MAKING PIPING CONNECTONS
Qualified personnel in accordance with local and national codes must perform all piping connections. Refer to Fig.2 for piping connections. NOTE: It is important to have a common understanding of which side of the unit is the right hand side and which is the left hand side. When facing the supply air outlet from the front of the unit (air blowing in your face), your right hand will be on the right side of the unit and your left hand will be on the left side of the unit. See Fig. 5.
Fig.3 ± Minimum clearance required. Fig4- Changing the coil connection side
Fig.5 ± Unit end reference
-7-
Table.7 - ELECTRIC HEATER OPTION
(2 Pipe System)
42TW 3 Ro
ws Models 42TW 4 Rows Models Heater option, watts
42TW3-03 42TW3-05 42TW3-06 42TW3-07 42TW3-09 42TW3-11 42TW3-12 42TW3-16
42TW4-03 2000 42TW4-04 2000 42TW4-05 2000 42TW4-06 2500 42TW4-08 2500 42TW4-10 4000 42TW4-11 4000 42TW4-14 4000
TEST AND INSULATE
When all joints are complete, perform hydrostatic test for leaks. Vent all coils at this time. Check interior unit piping for signs of leakage from shipping damage or mishandling. If leaks are found, notify a Carrier representative before initiating any repairs. Release trapped air from system (refer to Make Final Preparations section).
MAKE ELECTRICAL CONNECTIONS
Refer to unit nameplate for required supply voltage, fan and heater amperage and required circuit ampacity. Refer to unit wire diagram for unit and field wiring; see fig.6 . Make sure all electrical connections are in accordance with unit wiring diagram and all applicable codes. The fan motor(s) should never be controlled by any wiring or device other than the factory-supplied control board and remote control. All field wiring must be in accordance with governing codes and ordinances. Any modification of unit wiring without factory authorization will invalidate all factory warranties and nullify any agency listings.
- Select proper wall location to fix display pad
- Connect communication cable end to its location in the PCB as shown in the wiring diagram.
IMPORTANT
Wiring diagrams shown depict typical control functions. Refer to unit wiring label for specific functions.
minimize duct-to-unit alignment problems and noise transmission where specified. Set unit markings for minimum clearance to combustible materials and first 3 ft of ductwork. Install ductwork, accessory grilles and plenums so that they do not restrict access to filter. Cut openings for supply-air and return-air grilles. Be careful not to cut wires, piping or structural supports.
CAUTION
Prevent dust and debris from settling in unit. If wall finish or color is to be spray applied, cover all openings to prevent spray from entering unit. Unit efficiency
will be reduced.
MAKE FINAL PREPARATIONS
1. Turn off power to the unit (open unit electrical disconnect).
3. Clean dirt, dust, and other construction debris from unit interior. Be sure to check fan wheel and housing.
4. Rotate fan wheel by hand to be sure it is free and does not rub housing. Check that wing nuts securing fan assembly to fan deck are tight.
5. Ensure all panels and filters are installed before checking fan operation. Turn on power to the unit.
MAKE DUCT CONNECTIONS
Install all ductwork to and from unit in accordance with all applicable codes. Duct construction must allow unit to operate within duct external static pressure limits as shown on job submittals. Units designed to operate with ductwork may be damaged if operated without intended ductwork attached. Units provided with outside air should have some method of low-temperature protection to prevent freeze-up. Insulate ductwork as required. Use flexible connections to
IMPORTANT
Do not start-up or operate unit without filter. Be sure filter and unit interior are clean.
8. Be sure drain line is properly and securely positioned and that the line is clear. Pour water into drain to check operation.
- 8 -
Controller For Ducted Fan Coil Units
DIP Switch
On
Off
SW1
Cool
Cool-Heat
SW2
Water System
DX System
Room sensor fault
E1
Indoor coil sensor fault
E2
Comp fault
E4
“COOL” Led
Lights on when selecting COOL mode.
“DRY” Led
Lights on when selecting DRY mode.
“HEAT” Led
Lights on when selecting Heat mode.
“FAN” Led
Lights on when selecting FAN mode.
Wired Room
Notes: The wired room controller is mounted on the wall and can control all system functions without wireless remote control.
Wired Room Controller
Wireless Room Controller
- 9 -
Features: The controller is used to control air cooled ducted split unit, supports the following functions:
- Modes: Cool, Dry, Fan, Heat
- Indoor fan speed: Auto, High, Medium, Low
- Sleep mode
- Compressor protections: Comp 3 minutes restart protection Indoor coil anti-freeze Room sensor and indoor coil sensor failure monitoring
- Non volatile memory – keep system settings
- Programmable On/Off timer
- Random restart to minimize voltage dip during compressor first cut in cycle upon power up.
Hardware Setting: A 2 way DIP switch is used to configure:
Error Code: If multiple faults happen at the same time, the corresponding error code will be shown one after
another
Split System Description
1) On/Off Key: If you press this key, the system will begin operation, Press the key again, and operation stops.
(You can hear a receiving beep). If you press this key immediately after turning off the system, the compressor will not operate for 3 minutes to prevent overloading.
2) Operation Mode Selection Key: Toggles the operation mode: Cool, Dry, Heat, or Fan only
3) Fan Speed Selection Key: Toggles the fan speed: Auto, High, Medium, or Low, Note: Fan key is invalid in Dry
mode.
4) Temperature Up Key:
press.
5) Temperature Down Key: By pressing temperature down key, the setting temperature decreases by 1ºC with
each press. If you set the desired room temperature, then system will maintain the room temperature as set. Upon setting the desired room temperature the system will maintain the room temperature
Controller (Standard)
Fault Error code
By pressing Temperature up Key, the setting temperature increases by 1ºC with each
Cool Mode
FAN
Menu
Parameter
Set Range
Default value
Remarks
1: Disable room temp display
2: Enable room temp display
1: Comp OFF, Fan ON
2: Comp OFF, Fan OFF
1: Heater OFF, Fan ON
2: Heater OFF, Fan OFF
- 10 -
: If the room temperature is higher than the setting, the compressor will automatically turn on provide a
cooling effect. On the hand, if the room temperature is lower than the setting, the compressor will automatically turn off to stop cooling operation. If indoor fan is programed to be turned off with comp signal, it will turn off once comp is cut off
Heat Mode: If the room temperature is lower than the setting, the Electric heater will automatically turn on to provide a heating effect. If the room temperature is higher than the setting, the heater will automatically turn off to stop heating operation. If indoor fan is programed to be turned off with heater signal, it will turn off once heater is cut off but subject to 30 sec dispersing remaining heat timing.
Dry Mode: The fan speed runs automatically at low speed and compressor stopping and running is controlled by the difference between room and setting temperatures and by continuous running time. If indoor fan is programed to be turned off with comp signal, it will turn off once comp is cut off
- In Dry mode, the humidity is reduced in the space to be air-conditioned.
Fan Mode: There will be no cooling or heating effects; only the fans of indoor unit will run for ventilation at the selected speed (High, Med, and Low).
- In COOL or HEAT mode and if AUTO fan speed is selected; Fan speed is automatically selected by controller
according to the difference between setting temperature and room temperature, fan will be continuously running at low speed after setting temperature is achieved.
Notes:
a) Temperature setting range is 16ºC to 30ºC or 60ºF to 85ºF. b) Hold down at the same time for about 5 seconds, Temp down and fan keys will toggle the temperature setting from degree C to degree F and vice versa. c) Press any temperature key will flash the current setting temperature for 4 seconds, Should there be no further key press, it will revert to room temperature display. Temperature display range is 0 C to 50 C or 32 F to 99 F. d) Temp keys are invalid in Fan mode.
6) Sleep Key: Press this key to set the SLEEP timer and then the sleep led will light on, to cancel the sleep timer
press this key again.
- Sleep function for healthy sleep to control automatically the room temperature and stop automatically the operation of the air conditioner after certain set off time.
- Sleep mode is valid in cool or heat mode and invalid in Fan mode.
7) Timer Key: Upon count down of the set hours, the system will switch from OFF to ON or vice-versa.
- OFF Timer Function to stop automatically, the air conditioner after certain set OFF time.
- ON Timer Function to start automatically, the air conditioner after certain set ON time.
* Timer setting is 1 Hour to 24 Hour. The timer led will light on when operating the Timer Function First key press will flash the digital display and Timer Led for 3 seconds.
Notes:
a) The digital displays show the number of hours previously set, only the Timer Led flashes. b) Subsequent 3 seconds will show the number of hours previously set; only the timer led flashes. c) Should there be no further key press, it will revert to normal mode. d) Should Timer key is not released timer setting will increase automatically every 0.5-second.
8) Sensor: Receives the remote controller’s signal
9) Display Screen:
Displays the set temperature and displays also the TIMER settings when adjusting it.
10) Key Lock Mode: To activate key lock mode, hold down for 3 seconds, temp. Down Key (5) and Mode Key (2).
In key lock mode, all keys are not valid except ON/OFF Key (1) to turn ON/OFF the system.
Notes:
a) Hold down Temp Down and Sleep button for one second to enter into coil temperature display mode.
Press Temp Up key to display indoor coil temperature, High Fan LED flashes. With the same sequence to exit coil temperature display mode. Temperature display range is -9C to 78 ºC.
b) Hold down
to activate temperature display setting and auto fan LED flashes. Repeat the same sequence to cancel
this function. Press temperature display and “2” means enable room temperature display.
Temperature display, Auto fan
1
LED flashing Cool mode fan control function,
2
Auto & High fan LED flashing Heat mode fan control function,
3
Auto & Medium fan LED flashing
and
buttons for only 1 second ( 5 sec to toggle between ºC and ºF temperature )
or button to change the setting from 1 to 2. “1” means disable room
1~2 1
1~2 1
1~2 1
WIRING SCHEMATIC 42TW/TD COOL/HEAT
-11-
WIRING SCHEMATIC 42TW/TD COOL/HEAT WITHOUT CONTROL
-12-
START-UP
42TW unit is designed to operate in hot and humid conditions without condensation problem because of the rubber insulated drain pan. Refer to the startup checklist in
page 11 for startup procedure.
SERVICE
TO CLEAN COIL
1. Be sure electrical service switch is open, locked, and tagged while working on unit.
2. Remove supply-air grille access panel and brush between coil fins with stiff wire brush. Follow-up by cleaning with vacuum cleaner. If coil is cleaned with air hose and nozzle, take care not to drive dirt and dust into other components.
CHECK DRAIN
Lock open and tag unit electrical service switch. Check drain pan, drain line and trap at start of each cooling season. A standard type pipe cleaner for 5/8-in. ID pipe can be used to ensure that pipe is clear of obstruction so that condensate is carried away.
CLEAN FAN WHEEL
Lock open and tag unit electrical service switch. For access to fan assembly, remove front or bottom panel.
Fan assembly may be removed from its tracks if unit has a long conduit lead. Use a stiff brush or vacuum to remove dirt and debris from scroll.Wipe all fan surfaces with a damp cloth.
CLEAN ELECTRIC HEATER
Lock open and tag unit electrical service switch.
1. Remove dust, dirt, or foreign material before start-up. Do not block normal airflow to and from units; blockage may damage electric heaters.
2. Clean heater elements with soft brush or vacuum cleaner as necessary.
CLEAN OR REPLACE AIR FILTERS
Lock open and tag unit electrical service switch. At the start of each cooling season and after each month of operation (more or less depending on operating conditions) replace throwaway filter or clean permanent filter. THROWAWAY FILTER ² Replace filter with a good quality filter. Do not attempt to clean and reuse disposable filters. PERMANENT FILTER
1. Tap on solid surface to dislodge heavy particles.
2. Wash in hot water.
3. Set filter on end so that water drains out through slots in frame. Allow filter to dry thoroughly.
See Fig.7 for filter access.
Fig.7 ± Filter Access.
-13-
START-UP CHECKLIST FOR 42TW SERIES FAN COIL UNIT
I. Project Information
Job Name _______________________________________________________________________ Address ________________________________________________________________________ City ______________________________________________State __________ Zip __________ Installing Contractor _______________________________________________________________ Sales Office _____________________________________________________________________ Start-up Performed By _____________________________________________________________
INSPECTION, INSTALLATION, & START-UP CHECKLIST
ITEM COMPLETE ITEM COMPLETE Receiving & Inspection
1. Unit received undamaged
2. Unit received complete as ordered
3. Unit arrangement/hand correct
4. Unit structural support complete & correct
Handling & Installation
5. Mounting grommets / isolators used
6. Proper access provided for unit & accessories
9. Proper electrical service provided
7. Proper overcurrent protection provided
8. Proper service switch / disconnect provided
9. Proper refrigerant line sizes to unit
10. All service to unit in code compliance
11. All shipping screws & braces removed
12. Unit protected from direct & foreign matter
Cooling / Heating Connections
13. Connect field piping to unit
14. Pressure test all piping for leaks
15. Install drain line & traps as required
16. Insulate all piping as required
Ductwork Connections
17. Install ductwork, Fittings, & Grilles as required
18. Flexible duct connections at unit
19. Proper supply & return grille type & size used
20. Insulate all ductwork as required
Electrical Connections
21. Refer to unit wiring diagram
22. Connection incoming power service(s) 23,QVWDOOFRQQHFWLRQ³IXUQLVKRQO\´ parts
24. All field wiring in code compliance
Unit Startup
25. General visual unit & system inspection
26. Check for proper fan belt tension
27. Check for proper fan rotation
28. Record electrical supply voltage
29. Record ambient temperatures
30. Check all wiring for secure connections
31. Close all unit isolation valves
32. Flush water systems
33. Fill systems with water / refrigerant
34. Vent water systems as required
35. All ductwork & grilles in place
36. All unit panels & filters in place
37. Start fans, pumps, chillers, etc.
38. Check for overload condition of all units
39. Check all ductwork & units for air leaks
40. Balance air systems as required
41. Record all final settings for future use
42. Check piping & ductwork for vibration
43. Verify proper cooling operation
44. Verify proper heating operation
45. Reinstall all covers & access panels
-14 -
NOTES
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations
2015
42TW/TD - 05 - IOM
Loading...