7-1Outline of Air Conditioner Control
7-2Description of Operation Circuit
7-3High-Temperature Limit Control
7-4Low-Temperature Limit Control
7-5 Defrost Operation
7-6 Auto Restart Function
7-7Filter Check Lamp
– 1 –
Page 3
8.INSTALLATION PROCEDURE
8-1Safety Cautions
8-2Installation Diagram of Indoor and Outdoor Units
8-3Installation
8-4Indoor Unit
8-5Outdoor Unit
8-6How to Set Remote Control Selector Switch
8-7Others
9.TROUBLESHOOTING CHART
9-1Troubleshooting Procedure
9-2Basic Check Items
9-3Primary Judgement
9-4Self-Diagnosis by Remote Control (Check Code)
9-5How to Diagnose Faulty Parts
9-6Troubleshooting for Indoor Unit
9-7Troubleshooting for Wiring (Interconnect cable and Serial Signal Wire)
9-8Troubleshooting for P.C. Board
9-9Troubleshooting for Remote Control
FILE NO. SVM-05010
10. PART REPLACEMENT
10-1 Indoor Unit
10-2 Outdoor Unit (38CJR024-723, 38TAR024X-723, 38TAR018-723)
10-3 Outdoor Unit (38CJR018-723)
10-4 Outdoor Unit (38HNR024-713)
10-5 Outdoor Unit (38HNR018-713)
11. EXPLODED VIEWS AND PARTS LIST
11-1 Indoor Unit (E - Parts Assy)
11-2 Indoor Unit
11-3 Outdoor Unit (38CJR024-723, 38TAR024X-723)
11-4 Outdoor Unit (38TAR018-723)
11-5 Outdoor Unit (38CJR018-723)
11-6 Outdoor Unit (38HNR024-713)
11-7 Outdoor Unit (38HNR018-713)
– 2 –
Page 4
1. SPECIFICATIONS
FILE NO. SVM-05010
ITEMCooling
Capacity
Power sourceV220 – 240220
Power consumption W 2420 2510 2250
Power factor % 98 92 95
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
GRN : GREEN
GRN&YEL : GREEN & YELLOW
P04
6.3A
CN30
CN31
Varistor
DSA
F01
250V
MAIN P.C. BOARD
(WP-003)
Varistor
Louver
motor
BLU
PNK
6
5223311
6
5
Infrared rays receive
and Indication parts
598
1 2 3 4 610
BLU
BLU
BLU
BLU
YEL
RED
BRW
ORN
4
CN07
4
BLU
1 2 3 4 6510
5 64
321
Power supply
circuit
Control
Fan motor
circuit
GRY
BRW
YEL
105 64321
8 9
7
7
BLU
BLU
7
7
8 9
CN25
BLU
BLU
WHI
98
CN13
10
2
1
21
1
BLK2BLK
CN03
CN01
2
1
BLK
BLK
OUTDOOR
TERMINAL
BLOCK
POWER SUPPLY
240 V ~ 50 Hz
220 −
(For 38CJR024-723)
220 V ~ 50 Hz
(FOR 38TAR024X-723)
L
N
BLK
RED
BLK
RED
BLKBLK
RED
Indoor
terminal
block
i
SPARK KILLER
A2 A1
52C
1/L1
2/T1
3/L2 4/T2
5/L3 6/T3
1
1
2
2
GRN&YEL
RED
CAPACITOR
3
3
GRY
i
CHASSIS
RED
WHI
PNK
COMPRESSOR
INDOOR
UNIT
OUTDOOR
UNIT
CAPACITOR
S
R
WHI
RED
BLK
C
COMPRESSOR TERMINAL
FAN MOTOR
C
RS
BLK
1
2
4
3
1
2
66554
3
145 C
TEMP FUSE
Thermo.
sensor
(TA)
Heat exchanger
sensor
(TC)
MAGNETIC CONTACTOR
− 12−
Page 14
3-2. 42CJR018-723 / 38CJR018-723
COLOR IDENTIFICATION
BRW : BROWN
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
GRN : GREEN
GRN&YEL : GREEN & YELLOW
P04
BLK
6.3A
CN30
CN31
CN27
GRN&YEL
Varistor
DSA
F01
250V
MAIN P.C. BOARD
(WP-003)
Varistor
Louver
motor
BLU
PNK
6
5223311
6
5
FILE NO. SVM-05010-1
Infrared rays receive
and Indication parts
1 2 3 4 610
BLU
BLU
BLU
YEL
RED
BRW
ORN
4
CN07
4
BLU
1 2 3 4 6510
321
Power supply
circuit
Control
Fan motor
circuit
GRY
BRW
YEL
1
2
4
3
1
2
3
598
BLU
5 64
66554
BLU
8 9
7
7
BLU
BLU
7
8 9
7
Thermo.
sensor
(TA)
BLU
98
1
105 64321
10
21
BLK2BLK
WHI
CN03
CN25
CN13
2
1
CN01
2
1
BLK
BLK
Heat exchanger
sensor
(TC)
OUTDOOR
TERMINAL
BLOCK
RED
POWER SUPPLY
220 − 240 V ~ 50 Hz
BLK
MAGNETIC
CONTACTOR
CAPACITOR
145 C
TEMP FUSE
Indoor
l
termina
block
L
N
BLK
RED
RED
i
GRN&YEL
1
1
RED
3
2
2
3
i
CHASSIS
GRN&YEL
BLK
BLK
INDOOR
UNIT
OUTDOOR
UNIT
SPARK KILLER
GRY
R
U
T
S
W
V
(or A)
A1
(or B)
A2
CAPACITOR
RED
S
WHI
PNK
C
BLK
R
COMPRESSOR
C
S
R
COMPRESSOR TERMINAL
WHI
RED
FAN MOTOR
BLK
– 13
–
Page 15
3-3.42TAR018-723 / 38TAR018-723
COLOR IDENTIFICATION
BRW : BROWN
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
GRN : GREEN
GRN&YEL : GREEN & YELLOW
P04
BLK
DSA
F01
250V
6.3A
CN30
CN31
CN27
GRN&YEL
Louver
motor
Varistor
Varistor
MAIN P.C. BOARD
(WP-003)
BLU
PNK
6
5223311
4
6
5
4
FILE NO. SVM-05010-1
Infrared rays receive
and Indication parts
1 2 3 4 610
BLU
BLU
BLU
YEL
RED
BRW
ORN
CN07
BLU
1 2 3 4 6510
321
Power supply
circuit
Control
Fan motor
circuit
GRY
BRW
YEL
598
BLU
BLU
5 64
105 64321
8 9
7
7
BLU
7
7
BLU
8 9
CN25
BLU
WHI
98
CN13
10
2
1
21
1
BLK2BLK
CN03
CN01
2
1
BLK
BLK
OUTDOOR
TERMINAL
BLOCK
Indoor
termina
block
POWER SUPPLY
220 V ~ 50 Hz
L
N
BLK
RED
BLK
RED
BLKBLK
RED
l
1
1
i
SPARK KILLER
A1A2
52C
R U
SV
TW
2
2
GRN&YEL
RED
CAPACITOR
3
3
GRY
i
CHASSIS
RED
WHI
PNK
COMPRESSOR
INDOOR
UNIT
OUTDOOR
UNIT
CAPACITOR
S
R
WHI
RED
BLK
C
COMPRESSOR TERMINAL
FAN MOTOR
C
S
R
BLK
1
2
4
3
1
2
66554
3
145 C
TEMP FUSE
Thermo.
sensor
(TA)
Heat exchanger
sensor
(TC)
MAGNETIC CONTACTOR
− 14 −
Page 16
.
3-4
42HNR018-713 /38HNR018-713
COLOR IDENTIFICATION
BRW : BROWN
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
GRN : GREEN
GRN&YEL : GREEN & YELLOW
P04BLK
CN30
CN31
DSA
Varistor
F01
Louver
motor
250V6.3A
MAIN P.C. BOARD
(WP-003)
BLU
PNK
6
5223311
5
6
FILE NO. SVM-05010-1
Infrared rays receive
and Indication parts
BLU
RED
YEL
ORN
BRW
4
CN07
4
BLU
1 2 3 4 6510
98 1071 2 3
4 65
4 6
5
BLU
BLU
BLU
BLU
5 64
321
CN25
10
9871 2 3
WHI
BLU
BLU
BLU
98
7
CN13
10
8 9
7
+12 VDC
+5 VDC
WP-003
C
S
R
COMPRESSOR TERMINAL
220 − 240V ~ 50 Hz
L
BLK
RED
BLK
RED
WHI
PNK
N
FERRITE CORE
RED
MAGNETIC
CONTACTOR
R
(1/L1)
(3/L2)
(2/T1)
(4/T2)
U
CAPACITOR
S
R
C OMP R ES S O R
CN23
1
3
2
Serial Signal
circuit
TRANSFORMER
2
1
i
3
GRN&YEL
GRN&YEL
i
CHASSIS
BLK
BLK
RED
RED
BLK
BLK
WHI
RED
GRY
GRY
BRW
YEL
1
2
4
3
1
2
66554
3
145 C
TEMP FUSE
MAIN P.C. BOARD (MCC-890)
1
1
2
3
3
1
1
3
3
1
1
3
3
5
5
7
7
9
9
CN06
CN05
SG01
250VAC T6. 3A
CN01
F01
TNR
R74
TNR
R73
CN07
CN08
DISCHARGE
PIPE
SENSOR (TD)
BLU
1
1
2
3
3
BLU
BLK
1
1
2
3
3
BLK
HEAT
EXCHANGER
SENSOR (TE)
RY07
BLU
1
S
T
A1
(5/L3)
52C
(6/T3)
BLK
A2
W
COIL FOR
4 WAY VALVE
CAPACITOR
RED
WHI
RED
BLKBLK
V
C
YEL
BLU
BLU
313
11
33
CN11
CN02
CR11
CR12
CR13
CN03
1
1
RY05
RY06
3
FA N MO TO R
−15−
Page 17
3-5.42HNR024-713 / 38HNR024-713
COLOR IDENTIFICATION
BRW : BROWN
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
GRN : GREEN
GRN&YEL : GREEN & YELLOW
P04BLK
CN30
CN31
DSA
Varistor
F01
250V6.3A
MAIN P.C. BOARD
(WP-003)
Louver
motor
BLU
PNK
6
5223311
5
6
FILE NO. SVM-05010-1
Infrared rays receive
and Indication parts
BLU
RED
YEL
ORN
BRW
4
CN07
4
BLU
1 2 3 4 6510
98 1071 2 3
4 65
4 6
5
BLU
BLU
BLU
BLU
5 64
321
CN25
10
9871 2 3
WHI
BLU
BLU
BLU
98
7
CN13
10
8 9
7
+12 VDC
+5 VDC
WP-003
C
S
R
COMPRESSOR TERMINAL
220 − 240V ~ 50 Hz
L
BLK
RED
BLK
RED
WHI
PNK
i
N
FERRITE CORE
RED
MAGNETIC
CONTACTOR
R
S
(1/L1)
(3/L2)
(2/T1)
(4/T2)
U
V
CAPACITOR
S
C
R
COMPRESSOR
BLK
1
1
GRN&YEL
T
(5/L3)
(6/T3)
W
A1
52C
A2
2
2
CN23
RED
RED
3
3
WHI
GRN&YEL
i
CHASSIS
CAPACITOR
FAN MOTOR
Serial Signal
circuit
TRANSFORMER
COIL FOR
4 WAY VALVE
BLK
BLK
RED
RED
BLK
BLK
WHI
RED
GRY
BLU
YEL
BLU
BLU
GRY
BRW
YEL
1
1
145 C
TEMP FUSE
1
1
2
CN06
3
3
1
1
CN05
3
3
1
1
3
3
5
5
CN01
7
7
9
9
1
CN11
313
11
CN02
33
BLKBLK
2
4
3
2
66554
3
MAIN P.C. BOARD (MCC-890)
TNR
SG01
R74
F01
250VAC T6. 3A
TNR
R73
RY07
CR11
RY05
CR12
CR13
CN03
3
1
1
RY06
CN07
CN08
DISCHARGE
PIPE
SENSOR (TD)
BLU
1
1
2
3
3
BLU
BLK
1
1
2
3
3
BLK
HEAT
EXCHANGER
SENSOR (TE)
−16−
Page 18
FILE NO. SVM-05010
4. SPECIFICATION OF ELECTRICAL PARTS
4-1. Indoor Unit (42CJR024-723, 42CJR018-723, 42TAR024X-723, 42TAR018-723)
No.Parts nameTypeSpecifications
1 Fan motor (for indoor) AFS-220-31AAC 200 − 240V, 31W
2Thermo sensor (TA-sensor)———10 kΩ at 25°C
3 Micro Power Module (M01) µRM1260V DC 390 V, Secondary DC 12 V
4MicrocontrollerTMP87CM40AN
5Heat exchanger sensor
(TC-sensor)
6 Line filter (L01) LC*SS11V-06270 27mH, 600mA
7Diode (DB01)D3SBA604 A, 600 V
8 Capacitor (C63) KMH400VSSN47M22S4.7µF, 400 V
9 Fuse (F01) BET6.3A T6.3 A, 250 V
10 Varistor (R21, R22) 15G561K 560 V
11 Resistor (R319) RF-2TK5R6 5.6Ω, 2 W
12 Louver motor MP35EA12 Output (Rated) 2 W, 10 poles, 1 phase,
13Relay : (RY04) G5NB-1A Coil DC 12V, 16.7mA, Contact AC 250V, 1A
———10 kΩ at 25°C
DC 12 V
4-2. Indoor Unit (42HNR024-713, 42HNR018-713)
No.Parts nameTypeSpecifications
1 Fan motor (for indoor) AFS-220-31A AC 200 V, 31 W
2 Thermo sensor (TA-sensor) ——— 10 kΩ at 25°C
3 Micro Power Model (M01)µ RW1260 V DC 390 V, Secondary DC 12 V
4 Microcontroller TMP87CM40AN
5Heat exchanger sensor
(TC-sensor)
6 Line filter (L01) LC*SS11V-06270 27 mH, 600mA
7 Diode (DB01) D3SBA60 4 A, 600 V
8 Capacitor (C63) KMN400VSSN47M22S 4.74µF, 400 V
9 Fuse (F01) BET6.3A T6.3A, 250 V
10 Varistor (R21, R22) 15G561K 560 V
11 Resistor (R319) RF-2TK5R65.6Ω, 2 W
Cooling High temperature 0.5 12.0 High 32/23 43/26*
Low temperature0.31.0Low21/1521/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
– 21 –
Page 23
5-2. 42HNR024-713 / 38HNR024-713
FILE NO. SVM-05010
Indoor unit
Cooling
0.39 m
(Connecting pipe)
∅
15.88
O.D.:15.88 mmO.D.:6.35 mm
Cooling
Heating
Heating
P
Packed valve
(∅15.88)
Gas container connection (Reinstall etc.)
Heating
4-way valve
Cooling
Compressor
2JS386D5BB02
Accumulator
Condenser
Evaporator
Cross flow fan
T
Capillary tube
∅
1.0 x 700 s
Dryer
Packed valve
∅
6.35)
(
Capillary tube
∅2.0 x 1000 s
0.49 m
(Connecting pipe)
∅
6.35
Refrigerant
R22 1.
75 kg
Cooling
Heating
Propeller fan
Outdoor unit
Mark ( ) means check points of Gas Leak
Ambient temp.
50 Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
IndoorOutdoor
Standard 1.7 43.0 High 20/– 7/6
Heating High temperature 2.3 ~ 2.4 52.0 ~ 59.0 Low 27/– 24/18
Low temperature*1 1.2 36.0 High 20/– –10/–10
Standard0.411.0High27/1935/24
Cooling High temperature 0.6 12.0 High 32/23 43/26
Low temperature0.31.0Low21/1521/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*1 : During heating overload, the high temperature limit control operation is included.
– 22 –
Page 24
5-3. 42CJR018-723 / 38CJR018-723
FILE NO. SVM-05010
Indoor unit
Evaporator
(Connecting pipe)
0.39 m
∅12.7
O.D.:12.7 mmO.D.:6.35 mm
Compressor
P
Packed valve
(∅12.7)
Accumulator
PH340X3C-4KT1
Cross flow fan
Condenser
Propeller fan
T
0.49 m
(Connecting pipe)
∅6.35
Packed valve
(∅6.35)
Capillary tube
∅2.0 x 1400 s
Refrigerant
R22 1.17 kg
Outdoor unit
Mark ( ) means check points of Gas Leak
Ambient temp.
Surface temp. of heat
exchanger interchanging
pipe
T
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
IndoorOutdoor
50 Hz
Standard
pressure
(MPaG)
P
Standard0.411.0High27/1935/24
CoolingHigh temperature0.513.0High32/2343/26
Low temperature0.32.0Low21/1521/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
– 23 –
Page 25
5-4. 42TAR018-723 / 38TAR018-723
FILE NO. SVM-05010
Indoor unit
Evaporator
(Connecting pipe)
0.39 m
∅15.88
O.D.:15.88 mmO.D.:6.35 mm
Compressor
P
Packed valve
(∅15.88)
Accumulator
PH290X2C-4FT1
Cross flow fan
Condenser
Propeller fan
T
0.49 m
(Connecting pipe)
∅6.35
Packed valve
(∅6.35)
Capillary tube
∅2.0 x 800 s
Refrigerant
R22 1.47 kg
Outdoor unit
Mark ( ) means check points of Gas Leak
Ambient temp.
Surface temp. of heat
exchanger interchanging
pipe
T
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
IndoorOutdoor
50 Hz
Standard
pressure
(MPaG)
P
Standard 0.5 10.0 High 27/19 35/24
CoolingHigh temperature0.612.0High32/2343/26
Low temperature0.32.0Low21/1521/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Low temperature 1.2 34.0 High 20/––10/–10
Standard0.410.0High27/1935/24
CoolingHigh temperature0.515.0High32/2343/26
Low temperature0.31.0Low21/1521/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*1 : During heating overload, the high temperature limit control operation is included.
This is a fixed capacity type air conditioner, which uses
a AC motor for an indoor fan. The AC motor drive
circuit is mounted in the indoor unit. And electrical
parts which operate the compressor and the outdoor
fan motor, are mounted in the outdoor unit.
The air conditioner is mainly controlled by the indoor
unit controller. The controller operates the indoor fan
motor based upon commands transmitted by the
remote control and transfers the operation commands
to the outdoor unit controller.
The outdoor unit controller receives operation
commands from the indoor unit, and operates the
outdoor fan motor and the compressor.
(1) Role of indoor unit controller
The indoor unit controller receives the operation
commands from the remote control and executes
them.
• Temperature measurement at the air inlet of the
indoor heat exchanger by the indoor
temperature sensor
• Temperature setting of the indoor heat
exchanger by the heat exchanger sensor
• Louver motor control
• Indoor fan motor operation control
• LED display control
• Transferring of operation commands to the
outdoor unit
• Receiving of information of the operation status
and judging of the information or indication of
error
(2) Role of outdoor unit controller
The outdoor unit controller receives the operation
commands from the indoor controller and
executes them.
• Compressor operation
control
• Operation control of
outdoor fan motor
OPERATION
MODE
42HNR024-713
42HNR018-713
42CJR024-723
Model
42TAR024X-723
42CJR018-723
42TAR018-723
Operations according
to the commands
from the indoor unit
Table 7-1-1
Cooling UH H M+
Heat
Fan only
Dry
rpm
Air flow volume (m3/h)
rpm
Air flow volume (m3/h)
rpm
Air flow volume (m3/h)
rpm
Air flow volume (m3/h)
rpm
Air flow volume (m3/h)
UHH
1300
1200
790 750
1250
−
−
−
−
−
−
873
• Turning off the compressor and outdoor fan
when the outdoor unit receives the shutdown
command
• Defrost control in heating operation
(Temperature measurement by the outdoor heat
exchanger and control for the four-way valve
and the outdoor fan motor) *Heat pump Model
only
7-1-1. Louver control
(1) Vertical air flow louver
Position of veritcal air flow louver is automatically
controlled according to the operation mode.
Besides, position of vertical air flow louver can be
arbitrarily set by pressing [FIX] button.
The louver position which is set by [FIX] button is
stored in the microcomputer, and the louver is
automatically set at the stored position for the next
operation.
(2) Swing
If [SWING] button is pressed when the indoor unit
is in operation, the vertical air flow louver starts
swinging. When [FIX] button is pressed, it stops
swinging.
7-1-2. Indoor fan control (AC Fan motor)
(1) The indoor fan is operated by the stepless speed
change AC motor.
(2) For air flow level, speed of the indoor fan motor is
controlled in five steps (LOW, LOW
+
, MED, MED
and HIGH). If AUTO mode is selected, the fan
motor speed is automatically controlled by the
difference between the preset temperature and
the room temperature.
LOW
=
LOW+MED
+
2
MED+=
MED+HIGH
2
FAN TAP
1150
1300
873
1150
750
1300
873
H
M+M
M+
1250
830790
830
1100
708
1250
830
M
M
1200
1100
708
−
−
−
−
−
−
L
M
1150 1050
750
1050
667
1150
750
1050
667
1050
667
667
950
584
−
−
−
−
−
−
L
L+
LL+
L
L
L+
1000
625
900
543
1050
1000
625
667
950
900
543
584
900
950
584
543
UL
L- SUL/SL-
LL+
U
LL- UL SUL
700
800
900
380
461 300
543
700
800
461
900
543
800
461
800
461
800
600
300
380 220
700
461
380
700
600
380
300
700
600
300
380
SUL/SL-
+
600
500
−
−
−
−
−
−
− 28 −
Page 30
FILE NO. SVM-05010
7-2. Description of Operation Circuit
(1) When turning on the breaker, the operation lamp
blinks. This means that the power is on (or the
power supply is cut off.)
(2) When pressing [ ] button on the
remote control, receiving beep sounds from the
indoor unit, and the next operation is performed
together with opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcomputer so that the previous operation
can be effected thereafter simply by pressing
[ ] button.
7-2-1. Fan only operation
([MODE] button on the remote control is set
to the fan only operation.)
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-1. When
[FAN] button is set to LOW, LOW+, MED, MED+ or
HIGH, the motor operates with a constant air flow.
°C
7-2-2. Cooling operation
([MODE] button on the remote control is set
to the cooling operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in
Fig. 7-2-2.
°C
ON ON
OFF OFF OFF ON
4-way valve
Compressor
Outdoor fan
(Room temp.) (Preset temp.)
Preset
temp.
0.5
0
Fig. 7-2-2
display lamp
OPERATION
+3
+2.5
+2
+1.5
+1
+0.5
(Room temp.) − (Preset temp.)
Preset
temp.
0
(Preset temp.: 24°C)
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed
between M+ and L–.
(2) The Hi POWER, ECO and COMFORT SLEEP
operation cannot be set.
Fig. 7-2-1 Setting of air flow [FAN:AUTO]
M+
*1
*1
*1
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-3. When
[FAN] button is set to LOW, LOW+, MED, MED+ or
HIGH, the motor operates with a constant air flow.
°C
(Room temp.) − (Preset temp.)
Preset
temp.
+3
+2.5
+2
+1.5
+1
+0.5
0
-0.5
M+
*1
*1
*1
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed
between M+ and L–.
Fig. 7-2-3 Setting of air flow [FAN:AUTO]
− 29 −
Page 31
FILE NO. SVM-05010
7-2-3. Dry operation
([MODE] button on the remote control is set
to the dry operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in
Fig. 7-2-4.
°C
ON:6min.
OFF:4min.
ON
ON:5min.
OFF:5min.
OFF
4-way valve
Outdoor fan
(Room temp.) (Preset temp.)
Preset
temp.
+3
+2
+1
ON:6min.
OFF:4min.
OFF
ON:5min.
OFF:5min.
OFF
0
Compressor
Fig. 7-2-4
7-2-4. Heating operation *Heat pump model only
(1) The compressor, 4-way valve, outdoor fan and
Preset
temp.
display lamp
OPERATION
([MODE] button on the remote control is set
to the heating operation.)
operation display lamp are controlled as shown in
Fig. 7-2-6.
°C
0
ON
OFF
0.5
ON
(Room temp.) (Preset temp.)
OFF
ON
4-way valve
Compressor
Outdoor fan
ON
display lamp
OPERATION
Fig. 7-2-6
(2) The microprocessor turns the compressor on and
off at the regular intervals (4 to 6 minutes). While
the compressor is turning off, the indoor fan motor
operates in the SUPER LOW position.
The pattern of operation depending on the relation
between room temperature and preset
temperatures is shown in Fig. 7-2-5.
R oom temp.
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
ONONONON
OFFOFFOFF
L. *S.L.S.L.L.L.S.L. L.
*Super Low
Fig. 7-2-5
(3) [FAN] button on the remote control is set to AUTO
only.
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-7. When
[FAN] button is set to LOW, LOW+, MED, MED+ or
HIGH, the motor operates with a constant air flow.
Preset
temp.
°C
0
-0.5
-1
-1.5
-2
-5.0
-5.5
[FAN AUTO]
(Room temp.) − (Preset temp.)
L
*1
*2
+
M
H
*1, *2 : The values marked with *1 and *2 are
calculated and controlled by the difference in
motor speed between M+ and L.
Fig. 7-2-7 Setting of air flow [FAN:AUTO]
(4) The ECO and Hi Power operations can not be set.
– 30 –
Page 32
FILE NO. SVM-05010
(3) The indoor heat exchanger restricts revolving
speed of the fan motor to prevent a cold draft. The
upper limit of the revolving speed is shown in
Fig. 7-2-8 and Table 7-2-1.
Manual
(One of
AUTO
*4
SUL*
SUL*1
Stop
5 speed)
L-H
(Up to
setting
3
speed)
*2
A+4 A+4
464534
33
3321
3220
A-8 A-8
*6*5
NOTES :
*1: The fan stops for 2 minutes after thermostat-OFF.
*2: A is 24°C when the preset temperature is 24°C or
more and A is the preset temperature when it is
under 24°C.
*3: SUL means Super Ultra Low.
*4: Calculated from difference in motor speed
between SUL and HIGH.
7-2-5. Automatic operation
([MODE] button on the remote control is set
to the automatic operation.)
(1) One of 3 operations (Cooling, Fan only or Heating)
is selected according to difference between the
preset temperature and the room temperature at
which the automatic operation has started, as
shown in Fig. 7-2-9. The Fan only operation
continues until the room temperature reaches a
level at which another mode is selected.
(2) Temporary Auto
When the TEMPORARY button on the indoor unit
is pushed, the preset temperature is fixed at 24°C
and the indoor unit is controlled as shown in
Fig. 7-2-9.
°C
Cooling operation
The louver moves to the position same
as Hi POWER operation.
+4
Cooling operation
0
Fan only operation
-1
Fig. 7-2-8 Cold draft preventing control
*5 and *6:
Table 7-2-1
Fan*5*6
speedStarting periodStabilized period
AUTO• Up until 12 minutes
passed after starting
the unit
• From 12 to 25 minutes
passed after starting
the unit and room
temperature is 3°C
lower than preset
temperature
Manual• Room temperature
(L – H)< Preset temperature
• From 12 to 25 minutes
passed after starting
the unit and room
temperature is
between preset
temperature and 3°C
lower than preset
temperature
• 25 minutes or more
passed after starting
the unit
The microcontroller detects the indoor heat exchanger
temperature to prevent pressure of a refrigerating cycle
from increasing excessively.
The compressor and outdoor fan motor are controlled
as shown in Fig. 7-4-1.
Fig. 7-3
-1
7-4. Low-Temperature Limit Control
The microcontroller detects the indoor heat exchanger
temperature to prevent the indoor heat exchanger from
freezing.
The compressor and outdoor fan motor are controlled
as shown in Fig. 7-5-1.
Heat exchanger
temperature
(°C)
6
2
Compressor Outdoor fan
ON
Less than continues
for 5 minutes
OFF
7-5-1. Defrost starting condition
A-Zone : If -10°C > Teo ≥ − 18°C, defrost will
start when.
Teo - Te ≥ 2.5°C at teat 20 sec or
~ 30 min after operation.
B-Zone : If Te ≤ −18°C, defrost start instantaneously
(Suddenly) 00 ~ 25 min ofter operation
C-Zone : If -2ºC ≥ Teo ≥ −10°C defrost will start when
Teo - Te ≤ −3°C at least 20 sec or ~ 60 min
after operation.
7-5-2. Defrost finish condition.
1) If Te ≥ 3°C at least 60 sec -->4 way value on.
2) If Te ≥ 8°C --> 4 way value on.
Timing
Operation time (4 Loops = Tt)
Td1
Td2
Td3 Td4
Fig. 7-4
-1
7-5. Defrost Operation *Heat pump model only
When the indoor unit is in heating operation, if the
refrigerant evaporation temperature detected by the
outdoor heat exchanger sensor is under the specified
temperature, the outdoor unit starts the defrosting
operation. At this time, the 4-way valve relay and the
outdoor fan motor are turned off. The indoor fan motor
is also turned off by the cold draft preventing control of
the indoor microcomputer. Then, [PRE. DEF.] lamp on
the indoor unit comes on.
The defrosting operation stops and the 4-way valve
relay, outdoor fan motor and the indoor fan motor are
turned on automatically when the refrigerant
evaporation increases to the specified temperature, or
when the defrosting time is over 12 minutes.
-
32
Finish time recordStart time record
Defrost time rate : (Td/Tt) x 100
Heating time rate : (Tt - Td) x Tt
Fig. 7-5-2
-
Page 34
FILE NO. SVM-05010
7-6. Auto Restart Function
The indoor unit is equipped with an automatic
restarting function which allows the unit to restart
operating with the set operating conditions in the event
of power supply being accidentally shut down. The
operation will resume without warning three minutes
after power is restored.
This function is not set to work when shipped from the
factory. Therefore it is necessary to set it to work.
7-6-1. How to set auto restart function
To set the auto restart function, proceed as follows:
The power supply to the unit must be on; the function
will not set if the power is off.
Push the [TEMPORARY] button located in the center
of the front panel continuously for three seconds.
The unit receives the signal and beeps three times.
The unit then restarts operating automatically in the
event of power supply being accidentally shut down.
When the unit is on standby (Not operating)
OperationMotions
Push [TEMPORARY] button for moreThe unit is on standby.
than three seconds.
The unit starts to operate.The green lamp is on.
0
3S
The unit beeps three timesThe lamp changes from
→
→
and continues to operate.green to orange.
TEMPORARY button
If the unit is not required to operate at this time, push [TEMPORARY]
button once more or use the remote control to turn it off.
After approx. three seconds,
When the unit is in operation
OperationMotions
Push [TEMPORARY] button for moreThe unit is in operation.The green lamp is on.
than three seconds.
The unit stops operating.The green lamp is turned off.
→
→
After approx. three seconds,
0
3S
TEMPORARY button
•While this function is being set, if the unit is in
operation, the orange lamp is on.
•This function can not be set if the timer operation
The unit beeps three times.
If the unit is required to operate at this time, push [TEMPORARY]
button once more or use the remote control to turn it on.
•While the filter check lamp is on, the
[TEMPORARY] button has the function of filter
reset button.
has been selected.
•When the unit is turned on by this function, the
louver will not swing even though it was swinging
automatically before shutting down.
– 33 –
Page 35
7-6-2. How to cancel auto restart function
To cancel auto restart function, proceed as follows:
Repeat the setting prodedure: the unit receives the
signal and beeps three times.
The unit will be required to be turned on with the
remote control after the main power supply is turned
off.
When the unit is on standby (Not operating)
OperationMotions
Push [TEMPORARY] button for moreThe unit is on standby.
than three seconds.
→
FILE NO. SVM-05010
The unit starts to operate.The orange lamp is on.
→
After approx. three seconds,
0
3S
The unit beeps three timesThe lamp changes from
and continues to operate.orange to green.
TEMPORARY button
If the unit is not required to operate at this time, push [TEMPORARY]
button once more or use the remote control to turn it off.
When the unit is in operation
OperationMotions
Push [TEMPORARY] button for moreThe unit is in operation.The orange lamp is on.
than three seconds.
The unit stops operating.The orange lamp is turned off.
→
→
After approx. three seconds,
0
3S
TEMPORARY button
•While this function is being set, if the unit is in
The unit beeps three times.
If the unit is required to operate at this time, push [TEMPORARY]
button once more or use the remote control to turn it on.
7-7. Filter Check Lamp
operation, the orange lamp is on.
When the elapsed time reaches 1000 hours, the filter
7-6-3. Power failure during timer operation
check lamp indicates. After cleaning the filters, turn off
the filter check lamp.
When the unit is in Timer operation, if it is turned off
because of power failure, the timer operation is
7-7-1. How to turn off filter check lamp
cancelled. Therefore, set the timer operation again.
Press [FILTER] button on the remote control.
OR push [TEMPORARY] button on the indoor unit.
Note:
If [TEMPORARY] button is pushed while the filter
check lamp is not indicating, the indoor unit will start
the Automatic Operation.
– 34 –
Page 36
FILE NO. SVM-05010
8. INSTALLATION PROCEDURE
8-1. Safety Cautions
For general public use
Power supply cord of Outdoor unit shall be more than 4 mm2 (H07RN-F or 245 IEC66 : polychloroprene
sheathed flexible cord) or 3.5 mm2 (AWG-12).
CAUTION
This appliance must be connected to the main power supply by means of a circuit breaker or a switch with a
contact separation of at least 3 mm.
If this is not possible, a power supply plug with earth must be used. This plug must be easily accessible after
installation. The plug must be disconnected from the power supply socket in order to disconnect the
appliance completely from the mains.
To Disconnect the Appliance from the Main Power Supply
DANGER
• FOR USE BY QUALIFIED PERSONS ONLY.
• TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE
ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
• CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED
WRONGLY, ELECTRIC PARTS MAY BE DAMAGED.
• CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
• TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT
WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEATORS,
FURNACE, STOVES, ETC.
• WHEN MOVING THE AIR-CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY
CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT (R22) WITH ANY OTHER GASEOUS BODY
INTO THE REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT,
THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT
RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS.
• IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE
INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS
IS HEATED BY FIRE OR SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.
WARNING
• Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock
switches.
• Do not install in a place which cannot bear the weight of the unit.
Personal injury and property damage can result if the unit falls.
• Before doing the electrical work, attach an approved plug to the power supply cord.
Also, make sure the equipment is properly earthed.
• Appliance shall be installed in accordance with national wiring regulations.
If you detect any damage, do not install the unit. Contact your TOSHIBA dealer immediately.
CAUTION
• Exposure of unit to water or other moisture before installation could result in electric shock.
Do not store it in a wet basement or expose to rain or water.
• After unpacking the unit, examine it carefully for possible damage.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of the unit or where noise and discharged air might disturb neighbors.
• To avoid personal injury, be careful when handling parts with sharp edges.
• Please read this installation manual carefully before installing the unit. It contains further important
instructions for proper installation.
– 35–
Page 37
FILE NO. SVM-05010
REQUIREMENT OF REPORT TO THE LOCAL POWER SUPPLIER
Please make absolutely sure that the installation of this appliance is reported to the local power supplier
before installation. If you experience any problems, or if the installation is not accepted by the supplier, the
service agency will take adequate countermeasures.
– 36 –
Page 38
FILE NO. SVM-05010
8-2. Installation Diagram of Indoor and Outdoor Units
For installation of the indoor unit, use the paper pattern
on the back of the installation manual.
Hook
170 mm
or more
A
ir
filte
r
(Attach to the front panel) (Attach to the air filter)
6 Nano-silver filter
5 Nano-Photo filter
8
Pan head wood screw
65 mm or more
Hook
1 Installation
plate
170 mm
or more
Shield pipe
For the rear left and left
piping
Wall
Insert the cushion between
the indoor unit and wall, and
lift the indoor unit for better
operation.
Do not allow the drain hose
to get slack.
Cut the piping
hole sloped
slightly
Make sure to run the drain
hose sloped downward.
Before installing the
wireless remote control
• With the remote control cover
open, load the batteries supplied
correctly, observing their
polarity.
2 Wireless remote control
3 Batteries
m
0
0
1
m
r
o
1
0
0
m
m
o
r m
o
re
m
r
o
m
m
0
0
6
r
o
600 mm or more
e
m
e
r
o
2 Wireless remote control
Extension
drain hose
(Not available,
provided by
installer)
Electric
parts cover
6
0
0
m
o
m
r m
o
re
6
0
0
o
r m
The auxiliary piping can be
connected the left, rear left,
rear, right or bottom.
4 Remote control holder
Right
Rear
Insulate the refrigerant
pipes separately with
insulation, not together.
Vinyl tape
Apply after carrying
out a drainage test.
Saddle
Extension
drain hose
ore
100 mm
1
0
0
m
m
o
r m
o
re
m
r
o
m
o
m
m
0
m
0
6
re
re
o
600 mm or more
or m
(Not available,
provided by
installer)
Electric
parts cover
6
0
0
m
o
m
r m
o
re
Rear left
Bottom
6 mm thick heat resisting
polyethylene foam
Left
18 Class Heat pump 24 Class
Loop the connecting cable (about 100 mm
in diameter and 300 - 350 mm long).
18 Class Cooling
Loop the connecting cable (about 100 mm
in diameter and 300 - 350 mm long).
– 37 –
Page 39
8-3.Installation
8-3-1. Optional installation parts
FILE NO. SVM-05010
Part
Code
Parts name
Refrigerant piping
Liquid side : ∅6.35 mm
Gas side: ∅12.70 mm (42CJR018)
• Secure the outdoor unit with the fixing bolts and nuts if the unit is likely to be exposed to a strong wind.
• Use ∅8 mm or ∅10 mm anchor bolts and nuts.
– 38–
Page 40
8-3-2. Accessory and installation parts
FILE NO. SVM-05010
Part
No.
Part name (Q'ty)
1
Installation plate x 1
2
Wireless remote control x 1
3
Battery x 2
Others
Owner’s manual
Installation manual
Name
Part
No.
Part name (Q'ty)
4
Remote control holder x 1
5
Nano silver filter x 2
6
Nano Photo filter x 2
Part
No.
Part name (Q'ty)
7
Mounting screw ∅ 4 x 25 x 8
8
Pan head wood screw
∅ 3.1 x 16 x 2
l
l
.
– 39 –
Page 41
FILE NO. SVM-05010
8-4.Indoor Unit
8-4-1. Installation place
• A place which provides the spaces around the
indoor unit as shown in the above diagram.
• A place where there is no obstacle near the air inlet
and outlet.
• A place that allows easy installation of the piping to
the outdoor unit.
• A place which allows the front panel to be opened.
CAUTION
• Direct sunlight to the indoor unit's wireless
receiver should be avoided.
• The microprocessor in the indoor unit should not
be too close to RF noise sources.
(For details, see the owner’s manual.)
<Remote control>
• A place where there are no obstacles such as a
curtain that may block the signal from the indoor
unit.
• Do not install the remote control in a place exposed
to direct sunlight or close to a heating source, such
as a stove.
• Keep the remote control at least 1 m apart from the
nearest TV set or stereo equipment. (This is
necessary to prevent image disturbances or noise
interference.)
• The location of the remote control should be
determined as shown below.
Remote
control
(Top view)
Indoor unit
Reception
range
* : Axial distance
Fig. 8-4-1
°
45
°
5 m
Remote control
m
5
45
Indoor unit
(Side view)
7 m
°
5
7
Reception
range
8-4-2. Cutting a hole and mounting installation
plate
<Cutting a hole>
When installing the refrigerant pipes from the rear.
Pipe hole
6
5
m
m
The center of the pipe
hole is above the arrow.
100 mm
Fig. 8-4-2
1. After determining the pipe hole position on the
mounting plate (100 mm A), drill the pipe hole (∅
65 mm) at a slight downward slant to the outdoor
side.
NOTE:
• When drilling a wall that contains a metal lath, wire
lath or metal plate, be sure to use a pipe hole brim
ring sold separately.
<Mounting the installation plate>
For installation of the indoor unit, use the paper pattern
on the back.
Pipe hole
65
Installation
plate
* 7 m
170
120
Pipe hole
Hook
Indoor unit
Hook
Thread
Weight
55
Hook
7 Mounting screw
1
– 40 –
Fig. 8-4-3
Page 42
FILE NO. SVM-05010
<When the installation plate is directly mounted on
the wall>
1. Securely fit the installation plate onto the wall by
screwing it in the upper and lower parts to hook up
the indoor unit.
2. To mount the installation plate on a concrete wall
with anchor bolts, utilize the anchor bolt holes as
illustrated in the above figure.
3. Install the installation plate horizontally in the wall.
CAUTION
When installing the installation plate with a
mounting screw, do not use the anchor bolt hole.
Otherwise the unit may fall down and result in
personal injury and property damage.
Installation plate
<Keep horizontal direction>
Anchor
bolt
Projection
5 mm dia. hole
15 mm or less
8-4-3. Electrical work
1. The supply voltage must be the same as the rated
voltage of the air conditioner.
2. Prepare the power source for exclusive use with the
air conditioner.
NOTE:
2
• Wire type : More than 1.5 mm
2
IEC66) or 1.3 mm
(AWG-16)
(H07RN-F or 245
CAUTION
• This appliance can be connected to the mains in
the following way.
Connection to fixed wiring :
A switch or circuit breaker which disconnects all
poles and has a contact separation of at least
3 mm must be incorporate in the fixed wiring. An
approved circuit breaker or switches must used.
NOTE:
• Perform wiring works so as to allow a generous
wiring capacity.
7 Mounting
screw
ss
∅4 x 25
s
ss
Clip anchor
(local parts)
Fig. 8-4-4
CAUTION
Failure to firmly install the unit may result in
personal injury and property damage if the unit falls.
• In case of block, brick, concrete or similar type
walls, make 5 mm dia. holes in the wall.
• Insert clip anchors for appropriate mounting screws
7 .
NOTE:
• Secure four corners and lower parts of the
installation plate with 6 to 8 mounting screws to
install it.
– 41–
Page 43
FILE NO. SVM-05010
8-4-4. Wiring connection
Air Inlet grille
2
1
Terminal block
Cord clamp
Terminal
cover
Screw
Screw
Front panel
Earth
line
CAUTION
• Be sure to refer to the wiring system diagram
labeled inside the front panel.
• Check local electrical cords and also any specific
wiring instructions or limitations.
Connecting cable
a
b
o
u
t 1
5
c
m
Fig. 8-4-6
<Stripping length of the connecting cable>
10
10
40
50
Connecting cable
Fig. 8-4-5
<How to connect the connecting cable>
Wiring of the connecting cable can be carried out
without removing the front panel.
1. Remove the air inlet grille.
Open the air inlet grille upward and pull it toward
you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (according to the local
cords) into the pipe hole on the wall.
4. Take out the connecting cable through the cable
slot on the rear panel so that it protrudes about
15 cm from the front.
5. Insert the connecting cable fully into the terminal
block and secure it tightly with screws.
6. Tightening torque : 1.2 N·m (0.12 kgf·m).
7. Secure the connecting cable with the cord clamp.
8. Fix the terminal cover, rear plate bushing and air
inlet grille on the indoor unit.
Earth line
Fig. 8-4-7
NOTE:
Use stranded wire only.
• Wire type: More than 1.5 mm2 (H07RN-F or
245 IEC66) or 1.3 mm2 (AWG-16)
Fig. 8-4-8
NOTE:
Connect the earth line to the metallic part (i mark)
located at the side of 3P terminal.
<How to install the air inlet grille on the indoor unit>
• When attaching the air inlet grille, the contrary of
the removed operation is performed.
Fig. 8-4-9
– 42 –
Page 44
FILE NO. SVM-05010
8-4-5. Piping and drain hose installation
<In case of rightward piping>
• After scribing slits of the body-right by a knife or a
making-off pin, cut them by a pair of nippers or the
like.
Slit (Body-right)
Fig. 8-4-10
<In case of downward piping>
• After scribing slits of the body-right by a knife or a
making-off pin, cut them by a pair of nippers or the
like.
To connect the pipe after installation of the unit (figure)
(To the forefront of flare)
400 mm
300 mm
R 30 mm (Use polisin (polyethylene)
43 mm
core or the like for bending pipe.)
0
8
Liquid side
Gas side
Outward form of indoor unit
Use the handle of screwdriver, etc.
Fig. 8-4-12
NOTE:
If the pipe is bent incorrectly, the indoor unit may
unstably be set on the wall.
After passing the connecting pipe through the pipe
hole, connect the connecting pipe to the auxiliary pipes
and wrap the facing tape around them.
CAUTION
Slit (Body-right)
Fig. 8-4-11
<Left-hand connection with piping>
Bend the connecting pipe so that it is laid within 43 mm
above the wall surface. If the connecting pipe is laid
exceeding 43 mm above the wall surface, the indoor
unit may unstably be set on the wall. When bending the
connecting pipe, make sure to use a spring bender so
as not to crush the pipe.
Bend the connection pipe within a radius of 30 mm.
• Bind the auxiliary pipes (two) and connecting
cable with facing tape tightly. In case of leftward
piping and rear-leftward piping, bind the auxiliary
pipes (two) only with facing tape.
Indoor unit
Auxiliary pipes
Installation plate
Connecting cable
Drain hose
• Carefully arrange pipes so that any pipe does not
stick out of the rear plate of the indoor unit.
• Carefully connect the auxiliary pipes and
connecting pipes to each other and cut off the
insulating tape wound on the connecting pipe to
avoid double-taping at the joint, moreover, seal
the joint with the vinyl tape, etc.
• Since dewing results in a machine trouble, make
sure to insulate both the connecting pipes. (Use
polyethylene foam as insulating material.)
• When bending a pipe, carefully do it, not to crush it.
– 43 –
Page 45
FILE NO. SVM-05010
8-4-6. Indoor unit fixing
1. Pass the pipe through the hole in the wall, and hook
the indoor unit on the installation plate at the upper
hooks.
2. Swing the indoor unit to right and left to confirm that
it is firmly hooked up on the installation plate.
3. While pressing the indoor unit onto the wall, hook it
at the lower part on the installation plate. Pull the
indoor unit toward you to confirm that it is firmly
hooked up on the installation plate.
1
2
Hook
Hook here
1 Installation
plate
Press
(unhook)
Fig. 8-4-13
• For detaching the indoor unit from the installation
plate, pull the indoor unit toward you while pushing
its bottom up at the specified parts.
8-4-7. Drainage
1. Run the drain hose sloped downwards.
NOTE:
• Hole should be made at a slight downward slant on
the outdoor side.
Do not form the
Do not rise the
drain hose.
50 mm
or more
Do not put
the drain
hose end
into water.
drain hose into
a wavy shape.
Do not put
the drain
hose end in
the drainage
ditch.
Fig. 8-4-15
2. Put water in the drain pan and make sure that the
water is drained out of doors.
3. When connecting extension drain hose, insulate the
connecting part of extension drain hose with shield
pipe.
Fig. 8-4-14
Shield pipe
Drain hose
PushPush
Inside the room
Fig. 8-4-16
Extension drain hose
CAUTION
Arrange the drain pipe for proper drainage from the
unit.
Improper drainage can result in dew-dropping.
This air conditioner has the structure designed to drain
water collected from dew, which forms on the back of
the indoor unit, to the drain pan.
Therefore, do not store the power cord and other parts
at a height above the drain guide.
Wall
Drain guide
Space for pipes
– 44 –
Fig. 8-4-17
Page 46
FILE NO. SVM-05010
8-5.Outdoor Unit
8-5-1. Installation place
• A place which provides the spaces around the
outdoor unit as shown in the left diagram.
• A place which can bear the weight of the outdoor
unit and does not allow an increase in noise level
and vibration.
• A place where the operation noise and discharged
air do not disturb your neighbors.
• A place which is not exposed to a strong wind.
• A place free of a leakage of combustible gases.
• A place which does not block a passage.
• When the outdoor unit is to be installed in an
elevated position, be sure to secure its feet.
• An allowable length of the connecting pipe is up
15 m.
(Refer to the table of TO CHARGE REFRIGERANT
for detail.)
• An allowable height level is up to 8 m.
(38CJR018-713, 38TAR018-713, 38HNR018-703) or 10 m.
(38CJR024-713, 38TAR024X-713, 38HNR024-703)
• A place where the drain water does not raise any
problem.
8-5-2. Refrigerant piping connection
1. Cut the pipe with a pipe cutter.
90°
Obliquity
Roughness
Fig. 8-5-2
2. Insert a flare nut into the pipe, and flare the pipe.
• Projection margin in flaring : A (Unit : mm)
A
Die
Pipe
Fig. 8-5-3
Outer dia.
of copper pipe
RigidImperial
A
6.351.0 to 1.51.5 to 2.0
Warp
CAUTION
1. Install the outdoor unit without anything blocking
the air discharging.
2. When the outdoor unit is installed in a place
exposed always exposed to strong wind like a
coast or on a high storey of a building, secure
the normal fan operation using a duct or a wind
shield.
3. In particularly windy areas, install the unit such
as to avoid admission of wind.
4. Installation in the following places may result in
trouble.
Do not install the unit in such places.
• A place full of machine oil.
• A saline-place such as the coast.
• A place full of sulfide gas.
• A place where high-frequency waves are likely
to be generated as from audio equipment,
welders, and medical equipment.
Strong
wind
12.701.0 to 1.51.5 to 2.5
15.881.0 to 1.52.0 to 2.5
<Tightening connection>
Align the centers of the connecting pipes and tighten
the flare nut as far as possible with your fingers. Then
tighten the nut with a spanner and torque wrench as
shown in the figure.
CAUTION
• Do not apply excess torque.
• Otherwise, the nut may crack depending on the
conditions.
Fig. 8-5-1
– 45 –
Page 47
FILE NO. SVM-05010
(Unit : N·m)
Outer dia.
of copper pipe
Tightening torque
∅6.35 mm16 to 18 (1.6 to 1.8 kgf·m)
∅12.70 mm50 to 62 (5.0 to 6.2 kgf·m)
∅15.88 mm65 to 80 (6.5 to 8.0 kgf·m)
• Tightening torque of flare pipe connections
Flare at indoor unit side
Flare at outdoor unit side
Fig. 8-5-4
Flare nutHalf union
Externally
threaded side
Use a wrench to secure.
Use a torque wrench to tighten.
Internally
threaded side
Fig. 8-5-5
CAUTION
• KEEP IMPORTANT 4 POINTS FOR PIPING
WORK
(1) Take away dust and moisture (Inside of the
connecting pipes.)
(2) Tight connection (between pipes and unit)
(3) Evacuate the air in the connecting pipes using
VACUUM PUMP.
(4) Check gas leak (connected points)
8-5-3. Evacuating
After the piping has been connected to the indoor unit,
you can perform the air purge together at once.
AIR PURGE
Evacuate the air in the connecting pipes and in the
indoor unit using a vacuum pump. Do not use the
refrigerant in the outdoor unit. For details, see the
manual of the vacuum pump.
<Using a vacuum pump>
Be sure to use a vacuum pump with counter-flow
prevention function so that inside oil of the pump does
not flow backward into pipes of the air conditioner
when the pump stops.
1. Connect the charge hose from the manifold valve to
the service port of the gas side packed valve.
2. Connect the charge hose to the port of the vacuum
pump.
3. Open fully the low pressure side handle of the
gauge manifold valve.
4. Operate the vacuum pump to start evacuating.
Perform evacuating for about 15 minutes if the
piping length is 20 meters. (15 minutes for
20 meters) (assuming a pump capacity of 27 liters
per minute.) Then confirm that the compound
pressure gauge reading is –101 kPa (–76 cmHg).
5. Close the low pressure side valve handle of gauge
manifold.
6. Open fully the valve stem of the packed valves
(both side of Gas and Liquid).
7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.
Compound pressure gauge
-101 kPa (-76 cmHg)
Handle Lo
Charge hose
Pressure gauge
Manifold valve
Handle Hi
(Keep full closed)
Charge hose
– 46 –
Connecting pipe
Packed valve at liquid side
Packed valve at gas side
Service port
(Valve core (Setting pin))
Fig. 8-5-7
Vacuum
pump
Vacuum pump
adapter for
counter-flow
prevention
Page 48
FILE NO. SVM-05010
TO CHARGE REFRIGERANT
Refrigerant
No need to charge
refrigerant
Need to chargeOver 15 m up toOver 15 m up to
refrigerant25 m (20 g/m)20 m (20 g/m)
18 Class
15 m or less 15 m or less
24 Class
<Packed valve handling precautions>
• Open the valve stem all the way out; but do not try
to open it beyond the stopper.
• Securely tighten the valve stem cap with torque in
the following table:
Gas sideTightening torqueA
Gas side65 to 80 N·m5 mm
(∅15.88 mm)(6.5 to 8.0 kgf·m)
Gas side50 to 62 N·m4 mm
(∅12.70 mm)(5.0 to 6.2 kgf·m)
Liquid side16 to 18 N·mSame as
(∅6.35 mm)(1.6 to 1.8 kgf·m)Gas side
Service port
9 to 10 N·m
(0.9 to 1.0 kgf·m)
<Stripping length of connection cable>
Terminal block
LN132
Terminal screw
Earth line
Cord clamp
Power supply cord
N
L
10
60
10
70
Earth line
70
Screw
Cord clamp
Connecting cable
123
10
Connecting cablePower supply cord
Fig. 8-5-8
10
80
• Hexagonel wrench : A (Unit : mm)
Hexagonal wrench
is required.
A
Fig. 8-5-7
8-5-4. Wiring connection
1. Remove the electric parts cover from the outdoor
unit.
2. Connect the connecting cable to the terminal as
identified with their respective matched numbers on
the terminal block of indoor and outdoor unit.
3. When connecting the connecting cable to the
outdoor unit terminal, make a loop as shown in the
installation diagram of indoor and outdoor unit, to
prevent water coming in the outdoor unit.
4. Insulate the unused cords (conductors) from any
water coming in the outdoor unit. Proceed them so
that they do not touch any electrical or metal parts.
Model
Power source(For Asia model)
Maximum
running current
Plug socket &
fuse rating
Pow er cord
18 Class
50 Hz, 220 − 240V Single phase
50 Hz, 220V Single phase
(For Thai model)
16A18A
20A20A
4 mm2 (H07RN-F or 245 IEC66) or 3.5 mm
(AWG-12)
24 Class
CAUTION
• Wrong wiring connection may cause some
electrical parts burn out.
• Be sure to comply with local codes on running
the wire from indoor unit to outdoor unit (size of
wire and wiring method etc).
• Every wire must be connected firmly.
NOTE: Connecting cable
• Wire type: More than 1.5 mm2 (H07RN-F or
245 IEC66) or 1.3 mm2 (AWG-16)
2
– 47 –
Page 49
FILE NO. SVM-05010
8-6.How to Set Remote Control Selector
Switch
When two indoor units as installed in seperated rooms,
there is no need to change the selector switch.
<Remote control selector switch>
• When two indoor units are installed in the same
room or the adjacent two rooms, they may be
controlled simultaneously with a single remote
control. To prevent this, set either unit and its
remote control to B setting. (Both units are set to A
setting before shipment.)
• The remote control signal is not recived when the
indoor unit setting is different from the remote
control one.
1. Set the remote control selectors witch with the
indoor unit.
1) Turn the circuit breaker of the main power switch off
before setting the selector switch.
2) Remove the Air inlet grille and Front panel. (Refer to
Chapter 10-1, procedure 1 )
3) Open the Electrical part cover (Refer to chapter
10-1, procedure 2 ), then cut the jumper (J90)
with only the nippers.
2. Set the remote control selector switch with the
remote control
[B] is indicated on the liquid crystal display when
setting remote control selector switch to B. [A] is
not indicated on the display even if the selector
switch is set to A.
1) Load the remote control with the batteries.
2) Press the [CHECK] button using something with
sharp point. (The preset temperature on the remote
control changes to [00].)
3) Press the [MODE] button while pressing the
[CHECK] button, [B] is indicted at the right of the
present temperature display.
• To reset the switch to the [A] setting, press the
[MODE] button again while pressing the [CHECK]
button.
MODE
AUTO
COOL
AUTO FAN
DRY
TEMP.
FAN
AUTO
QUIET
B
CAUTION
Do not use any other sharp tools (such
as cutters, pliers, or the like). Such tools
may cause breakage or damage.
See Fig. 8-6-1
Fig. 8-6-1
TEMP.
START/STOP
SWING
MODE
ONOFFSETCLR
FIX
RST
TIMER
CHK
FAN
ECO
[MODE] button
[CHECK] button
Fig. 8-6-2
3. Confirm that the indoor unit can operate with
the new setting.
– 48 –
Page 50
FILE NO. SVM-05010
8-7. Others
8-7-1. Gas leak test
Electric parts cover
D
Flare nut connections
(Outdoor unit)
B
Valve stem cap connection
Fig. 8-7-1
• Check the flare nut connections, valve stem cap
connections and service port cap connections for
gas leak with a leak detector or soap water.
8-7-2. Test operation
C
Flare nut connections
(Indoor unit)
Valve stem cap
connection
A
Service cap connection
8-7-3. Auto restart setting
This product is designed so that, after a power failure,
it can restart automatically in the same operating mode
as before the power failure.
Information
The product was shipped with Auto Restart function
in the off position. Turn it on as required.
<How to set the auto restart>
• Press and hold down the TEMPORARY button for
about 3 seconds. After 3 seconds, the electronic
beeper makes three short beeps to tell you the Auto
Restart has been selected.
• To cancel the Auto Restart, follow the steps
described in the section Auto Restart Function of
the Owner’s Manual.
To switch the TEST RUN (COOL) mode, press
TEMPORARY button for 10 sec.
(The beeper will make a short beep.)
TEMPORARY button
Fig. 8-7-2
– 49 –
Page 51
9. TROUBLESHOOTING CHART
FILE NO. SVM-05010
9-1. Troubleshooting Procedure :
9-2-2. Incorrect cable connection between Indoor
and outdoor units
Follow the details of 9-2. Basic Check Items.
If there is no trouble corresponding to 9-2, check
whether or not there are faulty parts following
9-4. Self-Diagnosis by Remote Control.
9-2. Basic Check Items
The indoor unit is connected to the outdoor unit with
4 cables. Check that the indoor and outdoor units have
been properly connected with terminals assigned the
same numbers. If the connectors are not properly
connected, the outdoor unit will not operate normally,
or OPERATION lamp and TIMER lamp will blink (5 Hz).
9-2.1 Power supply voltage
The line voltage must be AC 220 – 240 V. If it is not
within this range, the air conditioner may not operate
normally.
9-2-3. Program control
The microcontroller operates as shown in Table 9-2-1
to control the air conditioner. If there are any operational problems, check whether or not the problems
correspond to Table 9-2-1. If they correspond to the
Table, they are not problems with the air conditioner,
but they are indispensable operations to control and
maintain the air conditioner properly.
Table 9-2-1
No.Operation of air conditionerDescriptions
1When the main power supply is turned
on, the OPERATION lamp on the
indoor unit blinks.
2The indoor fan motor speed does not
change in the Dry operation.
3The compressor is not turned off even
though the room temperature is in the
range that the compressor is turned off.
The OPERATION lamp blinks to indicate that power is turned on. If the
[START/STOP] button is pressed, the lamp stops blinking.
The indoor fan motor speed is automatically controlled in the Dry
operation.
The compressor has a function that it is not turned off for 3 minutes
after it is turned on even though the room temperature is in the range
that the compressor is turned off.
4The compressor is not turned on and
off even though the thermo control is
operated in the Dry operation.
*5The PRE-DEF. lamp is indicated when
the Heating operation starts.
*6The outdoor fan motor stops in the
Heating operation.
7The compressor is not turned on even
though the room temperature is in the
range that the compressor is turned on.
8The operation mode changes in the
Automatic operation.
9 The Auto Fan operation continues in the
Automatic operation.
10 The ECO operation
operation does not work.
Note *5 and *6 are for Heat pump model :
In the Dry operation, the compressor is turned on and off automatically
at the regular intervals, independent of the thermo control.
The PRE-DEF. lamp is indicated during the Defrosting operation or if
the indoor heat exchanger temperature is low when the Heating
operation starts. At this time, the indoor fan motor stops to prevent
cold air from blowing in the room.
When the indoor heat exchanger temperature is high, the outdoor fan
motor is stopped by the high-temperature limit control operation.
The compressor is not turned on in the restart delay timer (3-minutes
timer) operation. It is also not turned on after the power supply is
turned on because of this timer operation.
In Automatic operation, the room temperature is detected all time
for control fan speed and the operation mode is changed every
15 minutes according to difference between the room temperature
and the preset temperature.
When the room temperature is in the range
(Preset temperature ± 1°C), the Auto Fan operation is selected.
These operations do not work when the unit is in the Dry
operation or Auto Fan operation.
– 50 –
Page 52
FILE NO. SVM-05010
9-3. Primary Judgement
9-3-1. Role of indoor unit controller
The indoor unit controller receives the operation
commands from the remote control and executes
them.
• Temperature measurement at the air outlet of the
indoor heat exchanger by the indoor temperature
sensor
• Temperature setting of the indoor heat exchanger by
the heat exchanger sensor
• Louver motor control
• Indoor fan motor operation control
• LED display control
• Transferring of operation commands to the outdoor
unit
Table 9-3-1
LampsSelf-diagnosis
AOPERATION lamp is blinking. (1Hz)
BOPERATION lamp is blinking. (5Hz)
COPERATION lamp is blinking. (5Hz)
DOPERATION lamp is blinking. (5Hz)
EOPERATION lamp is blinking. (5Hz)
FOPERATION and TIMER lamps are b linking.
(5Hz)
9-3-2. Failure diagnosis
The indoor unit diagnoses the operation condition and
indicates the information of the self-diagnosis with the
lamps on the display panel of the indoor unit.
Power failure (when the power supply is turning on)
Thermo sensor (TA) short or break
Heat exchanger sensor (TC) short or break
Indoor fan motor lock or failure
Indoor P.C. board failure
Wrong wiring of connecting cable
GOPERATION, TIMER and AUTO FAN lamps
are blinking.
HOPERATION, TIMER and AUTO FAN lamps
are blinking.
Table 9-3-2 Diagnosis by detective operation
SymptomCheckPrimary judgement
The remote control
does not work.
The outdoor fan
does not rotate.
Turn off the power supply once,
then turn it on. Try to operate
the remote control.
The compressor operates.
The compressor does not operate.
• Gas shortage or other refrigerant cycle trouble
• Heat exchanger sensor open, break or short
• Overload relay or thermostat trouble of compressor
Cycle failure
The remote control
still does not work.
The remote control
works.
The indoor unit (and/or remote
control) is/are defective .
OK.
The outdoor unit (Outdoor fan
motor) is defective.
An internal part of the
compressor is defective.
– 51 –
Page 53
9-4. Self-Diagnosis by Remote Control
(Check Code)
(1) If the lamps are indicated as shown B to H in Table
9-3-1, execute the self-diagnosis by the remote
control.
(2) When the remote control is set to the service
mode, the indoor controller diagnoses the operation condition and indicate the information of the
self-diagnosis on the display of the remote control
with the check codes. If a fault is detected, all
lamps on the indoor unit will blink at 5Hz and it will
beep for 10 seconds (Pi, Pi, Pi....). The timer lamp
usually blinks (5Hz) during the self-diagnosis.
9-4-1. How to use remote control in service mode
FILE NO. SVM-05010
MODE
AUTO
COOL
A
TEMP.
DRY
Hr.ON OFF
TEMP.
START/STOP
SWING
MODE
RST
TIMER
ONOFF SETCLR
FIX
CHK
FAN
AUTO
QUIET
FAN
ECO
• Alphanumeric characters are used for the check
code.
is 5.is 6.
is A.is B.
is C.is D.
WH-K13JE
WC-K12JE
(1) Press [CHK] button with a tip of pencil to set the
remote control to the service mode.
• “00” is indicated on the display of the remote
control.
• The timer lamp on the indoor unit blinks
continuously. (5 times per 1 sec.)
(2) Press [TEMP. 8] button.
If there is no fault with a code, the indoor unit will
beep once (Pi) and the display of the remote
control will change as follows:
00011d1E0222
•
Check the unit with all 35 check codes (00 to 22).
as shown in Table 9-4-1.
• Press [TEMP. 9] button to change the check
code backwards.
If there is a fault, the indoor unit will beep for 10
seconds (Pi, Pi, Pi...).
Note the check code on the display of the remote
control.
• 2-digits alphanumeric will be indicated on the
display.
• All lamps on the indoor unit will blink. (5 times
per 1 sec.)
(3) Press [START/STOP] button to release the service
mode.
• The display of the remote control returns to as it
was before service mode was engaged.
Auto Fan
A
Heat
– 52–
Page 54
Table 9-4-1
Block levelDiagnosis function
Check
codecodestatus
Block
Indoor
P.C. board
Cable
connection
Outdoor
P.C. board
Other parts
(including
compressor)
Check
Symptom
The indoor thermo sensor (TA) is
defective.
Disconnection or short-circuit
The indoor heat exchanger
sensor (TC) is defective.
Disconnection or short-circuit
The indoor fan motor or its circuit
is defective.
The part other than the above
parts on the indoor P.C. board is
defective.
EEPROM access error
IOL operation
The serial signals can not be
transmitted and received between
indoor and outdoor units.
The crossover wire is
•
connected wrongly.
The serial signal transmitting
•
circuit on the outdoor P.C. board
is defective.
The serial signal receiving
•
circuit on the indoor P.C. board
is defective.
The operation command signals
are not transmitted from the
indoor unit to the outdoor unit.
The outdoor thermo sensor (TE)
is defective.
Disconnection or short-circuit
The outdoor heat exchanger (TD)
sensor is defective.
Disconnection or short-circuit
The reply serial signal has been
transmitted when starting the
unit, but stops being transmitted
shortly after.
1. Compressor thermo operation
•
Gas shortage
• Gas leak
2. Instantaneous power failure
The discharge temperature is
over 120°C.
The IOL operation is defective.
Unit
Operation
continues.
Operation
continues.
All off
Operation
continues.
All off
Operation
continues.
Operation
continues.
All off
All off
Operation
continues.
All off
All off
Condition
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected. And it
returns to the
normal condition
when recovering
from errors.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected. And it
returns to the
normal condition
when recovering
from errors.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
detected.
FILE NO. SVM-05010
Judgement and action
1. Check the indoor thermo sensor (TA).
2. Check the indoor P.C. board.
1. Check the indoor heat exchanger
sensor (TC).
2. Check the indoor P.C. board.
1. Check the connector circuit of the
indoor fan motor (CN10).
2. Check the indoor fan motor.
3. Check the indoor P.C. board.
1. Check the indoor P.C. board.
(EEPROM and peripheral circuits)
Overload operation of refrigerating cycle
1. In the case of the outdoor unit not
operating at all;
•
Check the crossover cable and
connect it properly.
•
Check the outdoor P.C. board.
2. In the case of the outdoor unit operating
normally;
•
Check whether or not both of serial
LED (Green) and serial LED (Orange)
is blinking.
If the serial LED (Green) is not
blinking, check the outdoor P.C. board.
If the serial LED (Orange) is not
blinking, check the indoor P.C. board.
If the operation command signals continue
to be transmitted between 2 and 3 of the
indoor terminal block, replace the outdoor
P.C. board.
1. Check the outdoor thermo sensor (TE).
2. Check the outdoor P.C. board.
1. Check the outdoor heat exchanger
sensor (TD).
2. Check the outdoor P.C. board.
1. Repeatedly turn the indoor unit on and
off with the interval of approx. 10 to 40
minutes. (The check code is not
indicated during operation.) And supply
gas. (Check gas leak.)
2. The indoor unit operates normally
during the check.
If the reply serial signal continues to be
transmitted between 2 and 3 of the
indoor terminal block, replace the
outdoor P.C. board.
If the signal stops between them,
replace the indoor P.C. board.
1. Check the heat exchanger sensor (TD).
2. Gas purging
When turning on the unit, the normal
phase (RST) is detected but T-R waveform
has not been detected for 120 seconds or
more.
− 53−
Page 55
9-5. How To Diagnose Faulty Parts
[04 Serial signal error] (Heat pump model)
FILE NO. SVM-05010
Operation
Check item
Conceivable principle cause
Measure
Does outdoor
unit operate?
YES
NO
Are 1, 2 and 3 crossover
wires connected properly?
YES
Is connector
connected properly?
YES
Does LED (Orange) on
outdoor P.C. board blink?
YES
Does LED (Green) on
outdoor P.C. board blink?
YES
NO
NO
NO
NO
Outdoor P.C. board
is defective.
Indoor P.C. board
is defective.
Item by symptoms
Connect crossover
wires properly.
Connect connector
properly.
Replace
P.C. board.
Replace
P.C. board.
[08 Four-way valve error] (Heat pump model)
Does four-way valve
operate properly?
YES
Is TC sensor
resistance value
(10 kΩ at 25°C) normal?
NO
NO
YES
Does coil terminal
have 220 − 240 V
in heating operation?
YES
Are circuit
wires normal?
YES
Is outdoor P.C. board
normal?
YES
YES
NO
NO
Four-way valve
is defective.
Outdoor P.C. board
is defective.
(CN11 220 − 240 V)
Indoor P.C. board
is defective.
Replace
Four-way valve
Circuit check/modification
Replace
P.C. board.
Replace
P.C. board.
Replace TC sensor.
– 54–
Page 56
[09 Other cycle error] (1) (Heat pump model)
FILE NO. SVM-05010
NO
Replace TC
sensor.
YES
Connect TC
sensor properly.
Does compressor operate?
YES
Is compressor
turned off shortly?
NO
Is TC sensor
resistance value
(10 kΩ at 25°C) normal?
YES
Is TC sensor
disconnected from
the sensing element?
NO
NO
YES
Does inner
overload relay
(in compressor)
operate?
NO
Is circuit wiring
normal?
YES
Is outdoor P.C.
board normal?
YES
YES
NO
NO
Check charged amount of refrigerant.
Check defective overload.
Check compressor.
Failure
Wiring check/modification
Outdoor P.C. board
is defective.
Indoor P.C. board
is defective.
Replace
compressor.
Replace
P.C. board.
Replace
P.C. board.
[09 Other cycle error] (2)
NO
Connect
connector
properly.
NO
Replace
condenser.
NO
Replace
fan motor.
Is connector
connected properly?
Is condenser normal?
Is indoor fan
motor normal?
YES
YES
YES
NO
Does indoor
fan operate?
Are filters clogged?
Is TC sensor
resistance value
(10 kΩ at 25°C) normal?
Is charged amount
of refrigerant normal?
Is outside air
low load?
YES
NO
YES
YES
NO
YES
NO
NO
YES
Clean filters.
Replace
TC sensor.
Anti-freezing operation
Charge
refrigerant.
Anti-freezing operation
Indoor P.C. board
is defective.
– 55 –
Replacd
P.C. board.
Page 57
[0C Indoor TA sensor error]
FILE NO. SVM-05010
Is CN03 (TA sensor connector)
connected properly?
YES
Is TA sensor resistance value
(10 kΩ at 25°C) normal?
YES
[0d Indoor TC sensor error]
Is CN01 (TC sensor connector)
connected properly?
YES
NO
NO
NO
Indoor P.C. board is defective.
Connect CN03 properly.
Replace T A sensor.
Replace P.C. board.
Connect CN01 properly.
Is TC sensor resistance value
(10 kΩ at 25°C) normal?
YES
NO
Indoor P.C. board is defective.
[18 outdoor TE sensor error] (Heat pump model)
Is TE sensor connector
connected properly?
YES
Is TE sensor resistance value
(10 kΩ at 25°C) normal?
YES
NO
NO
Replace TC sensor.
Replace P.C. board.
Connect connector
properly.
Replace TE sensor.
Indoor P.C. board is defective.
– 56 –
Replace P.C. board.
Page 58
[19 outdoor TD sensor error] (Heat pump model)
FILE NO. SVM-05010
Is TD sensor
connected properly?
YES
Is TD sensor resistance value
(50 kΩ at 25°C) normal?
YES
NO
NO
Outdoor P.C. board is defective.
[1E Discharge temp. error] (Heat pump model)
Connect connector
properly.
Replace TD sensor.
Replace P.C. board.
Is protective
controller such as discharge
thermostat normal?
YES
Is charged amount
of refrigerant normal?
YES
Is overload relay normal?
NO
Is TD sensor resistance value
(50 kΩ at 25°C) normal?
YES
NONO
NO
YES
NO
Are wires connected
to connector properly?
Outdoor P.C. board is defective.
Connect wires to
connector properly.
Check and modify charged
amount of refrigerant.
Unit operates normally.
Replace TD sensor.
Replace P.C. board.
– 57 –
Page 59
9-6. Troubleshooting for Indoor Unit
Operation
Measure
Item by symptoms
Check item
Conceivable principle
cause
9-6-1. Power can not be turned on. (The unit does not operate at all.)
<Primary check>
(1) Is the supply voltage normal?
(2) Is the connection to the AC output OK?
(3) Is the fuse (F01) blown?
Turn off power
supply once, and 5
second later, turn it
on again.
NO
Is OPERATION
lamp blinking?
YES
Does
Is it possible to
turn on power
supply by
pressing
[START/STOP]
button on remote
control?
YES
NO
transmission
mark on
remote
control flash
normally, and
is its signal
transmitted
properly?
YES
NO
FILE NO. SVM-05010
Remote control is
defective.
Refer to 9-9
ÒTroubleshooting for
Remote Control.Ó
Is DC 310 -
340V across
C63?
Are DC 12V,
across C66?
YES
YES
NO
NO
Is fuse (F01)
control board
Is voltage (DC
NO
indicated on
rear of indoor
control board
Turn off breaker
once and turn it
on again after
removing motor.
of indoor
blown?
NO
12V or 5V)
normal?
YES
YES
Parts (R21,
R22, SG01,
C01, DB01,
C02,
M01 and IC04)
are defective.
Are DC 12V,
across C66?
YES
– 58−
NO
Does the fan
motor
connector
between 1
and 2 short-
circuit?
NO
Microcomputer is
defective.
M01 is
def
ec
tive.
Unit operates
normally.
YES
Replace main P.C.
board.
Replace motor.
Page 60
FILE NO. SVM-05010
9-6-2. Only the indoor fan does not operate
<Primary chec k>
(1) Is it possible to detect the power supply voltage (200 − 240V) between 1 and 2 on the terminal block?
(2) Does the indoor fan motor operate in cooling operation?
Shut off the
power supply once.
Turn the power supply.
Does the fan stop in
no operating status?
YES
Start the operation
with low fan setting
in cool operation.
Does the fan rotate?
YES
Change the setting of
cooling to high fan.
Does the fan speed
become higher?
YES
NO
NO
NO
Control P.C. board is defective.
Does AC 120V
or higher voltage apply
to between red and black
lead of fan motor?
YES
Shut off the power supply.
Does the cross flow
fan rotate normally?
YES
Turn on the power supply.
Operation
stops
NO
NO
Replace the P.C. board.
Does connecting
terminal, connecting
cable or power supply
cord completely?
Does not found the short
wire about connecting
cable and power cord?
YES
Repair the
bearing of
the fan.
Motor control circuit failure
(IC30, IC03, D38, R25, R26, Q17)
or 12V power circuit failure.
Replace the P.C. board.
of incompleted connecting.
NO
Thermal fuse operated
due to prevent
temperature rising cause
Normal
Is the rotation signal (DC+5V-0V)
output between 2 (gray lead wire)
and 3 (brown lead wire) of the motor
connector (CN11) when rotating
the cross flow fan by hand in no
operating status?
(1 pulse/one turn)
YES
Replace the control
P.C. board.
−59−
NO
Replace the fan motor
Replace connecting
the cable (or power cord),
thermal fuse and
terminal block.
Page 61
9-6-3. Compressor does not operate.
<Primary check>
(1) Is the preset temperature higher than the room temperature in cooling operation?
(2) Is the crossover cable connected properly?
<Inspection procedure>
-Cooling only model-
FILE NO. SVM-05010
– 60 –
Page 62
<Inspection procedure>
Turn on power supply.
FILE NO. SVM-05010
Does OPERATION
lamp blink?
YES
Is it possible to start
unit by remote control?
YES
Is it possible to detect AC 200V
between 2 and 3 on terminal block?
YES
Is crossover cable normal?
YES
Are all of compressor cords normal?
YES
Is compressor motor winding normal?
(Check winding resistor.)
YES
Is capacitor for compressor normal?
YES
NO
NO
NO
NO
NO
NO
NO
Compressor is defective.
Capacitor is defective.
Refer to item Power
can not be turned on .
Refer to 9-9 Troubleshooting
for Remote Control .
Replace P.C. Board
Connect crossover
cable properly.
Rewire or replace
defective cords.
Replace compressor.
Replace compressor.
Is overload relay normal?
YES
Does compressor start?
YES
Does compressor stop after a while?
YES
Is gas quantity normal?
(Check gas pressure.)
YES
Compressor is defective.
YES
Replace P.C. borad
NO
NO
NO
Overload relay is defective.
Compressor is defective.
Gas shortage (Gas leak)
Replace overload relay.
Replace compressor.
Supply gas.
− 61−
Page 63
<Inspection pr ocedure>
- Heating model
AC 70-100V
FILE NO. SVM-05010
Replace transformer
outdoor
P.C. board.
−62 −
Page 64
YES
FILE NO. SVM-05010
Are all of compressor cords normal?
YES
Is compressor motor winding normal?
(Check winding resistor.)
YES
Is capacitor for compressor normal?
YES
Is overload relay normal?
YES
Does compressor start?
YES
Does compressor stop after a while?
YES
Is gas quantity normal?
(Check gas pressure.)
YES
NO
NO
NO
NO
NO
NO
Compressor is defective.
Capacitor is defective.
Overload relay is defective.
Compressor is defective.
Gas shortage (Gas leak)
Rewire or replace
defective cords.
Replace compressor.
Replace capacitor.
Replace overload relay.
Replace compressor.
Supply gas.
Compressor is defective.
YES
Replace compressor.
– 63 –
Page 65
FILE NO. SVM-05010
9-7. Troubleshooting for Wiring (Interconnect cable and Serial Signal Wire)
9-7-1. Outdoor unit does not operate.
<Inspection procedure>
(1) Is the voltage between and of the indoor terminal block varied?
1
(2) Are signals from the indoor unit to the outdoor unit transmitted correctly based upon the following diagram?
NOTE:
Measure the voltage for 2 minutes and 30 seconds after starting the unit.
Heatpump model
Terminal block on indoor side
Red
2
3
White
2
1
Terminal block
Tester
Normal condition : Voltage varied between AC70 ~ 100V
Abnormal condition : Voltage does not vary.
Cooling model
Terminal block on indoor side
Red
White
3
2
1
Terminal block
Tester
Fig. 9-7-1
Normal condition : After start operated about 2 minutes and 30 seconds. Voltage between 2 and 3 of the
of the indoor's Terminal block should be equal AC 220 ~ 240V
Abnormal condition : Don't found voltage AC 220 ~ 240V from terminal block (0V)
9-7-2. Outdoor unit stops a while after starting the unit.
<Confirmation procedure> Select one of 3 cases below and follow the procedure.
(1) The outdoor unit stops between 10 and 20 minutes passed after starting and it takes 10 minutes or more to
restart the unit.
Gas has a low circulation.
Measure gas pressure.
Compressor is turned off and on automatically by thermo sensor
(Heat pump Model) or thermostat (Cooling only Model).
Gas shortage
Gas leak
Pipe clogging
(2) The outdoor unit stops once, it would not operate until the power is turned on again.
Refer to 9-6-4 "Compressor does not operate"
(3) The outdoor unit stops between 10 minutes to 1 hour after starting and a check code is indicated on the
remote control. (Check code 03-1E : Refer to Table 9-4-1.)
−64−
Page 66
FILE NO. SVM-05010
9-8. Troubleshooting for P.C. Board
<Inspection procedure>
(1) If the P.C. board is detective, check for
9-8-1. How to check indoor P.C. board
disconnection, burn or discoloration of the copper
foil pattern of the P.C. board.
<Cautions for handling P.C. board>
(1) When removing the front panel and the P.C. board,
be sure to turn off the power supply.
(2) When removing the P.C. board, hold the edge of
the P.C. board and do not apply force to the parts.
(3) When connecting or disconnecting the connectors
on the P.C. board, hold the housing. Do not pull at
(2) The P.C. board consists of the following 2 parts:
a. Main P.C. board parts:
Power relay, indoor fan motor drive circuit and
control circuit, C.P.U. and peripheral circuits, buzzer
drive circuit and buzzer.
b. Infrared rays parts:
Infrared rays receiving circuit
lead wires.
Check the defects of the P.C. board with Table 9-8-1.
Table 9-8-1 Inspection procedure
No.ProcedureCheck pointsCauses
1Turn off the power supply and
remove the P.C. board assembly from
electric parts base. Remove the
connecting cables from the terminal
block.
2Remove the connector of the motor
and turn on the power supply. If
OPERATION lamp blinks (once per
second), it is not neccessary to check
steps (1 to 4) in the right next
column.
Check whenther or not the fuse (F01) is
blown.
Check power supply voltage;
1. Between TP01 and CN31
(AC 220V)
2. Between + and – of C63
(DC310 – 340V)
3. Between 12V and GND
4.Between 5V and GND
Impluse voltage was applied or the
indoor fan motor short-circuited.
1.The terminal block or the crossover
cable is connected wrongly.
2. The capacitor (C01 and C02), line
filter (L01), resistor (R319),
or the diode (DB01) is defective.
3. M01, DB01, R319 and C63
are defective.
4. IC04 is defective.
3Press [START/STOP] button once to
start the unit. (Do not set the mode to
Fan Only or On-Timer operation.)
4Shorten the line of the restart delay
timer and start unit.
Check power supply voltage;
Between connector of Q25 and GND
1.
(for relay coil (DC12V))
2. Between 1 and 2 of terminal block
for connecting cable
Check whether or not all lamps
(OPERATION, TIMER, FAN ONLY, ECO
and AUTO) are indicated for 3 seconds
and
1. The wire of the rel
comes down or the relay drive
(Q25) is defective.
2. CN27 or
wrongly.
The lamps are defective or the
housing assembly (CN13) is defective.
RY03 is connected
ay coil (RY03)
– 65 –
Page 67
FILE NO. SVM-05010
No.Procedure Check points Causes
5Press [START/STOP] button once to
start the unit.
• Shorten the time of the
restart delay timer.
• Set the operation mode to COOL.
• Set the fan speed level to AUTO.
• Set the preset temperature much
lower than the room temperature.
(The unit (compressor)
operates continuously in the above
condition.)
6Connect the motor connector to the
motor and turn on the power supply.
Start the unit in the following
condition.
• Set the operation mode to FAN.
• Set the fan speed level to HIGH.
(The unit (compressor) operates
continuously in the above
condition.)
1. Check whether or not the compressor operates.
2. Check whether or not the OPERATION lamp blinks.
1. The motor does not operate.
(But it is possible to receive the
signal from the remote control.)
2. The motor rotates but vibrates
strongly.
1. The temperature of the indoor heat
exchanger is extremely low.
2. The connection of the heat
exchanger sensor is loose.
(The connector is disconnected.)
(CN01)
3. The heat exchanger sensor and
the P.C. board are defective.
(Refer to Table 9-8-2.)
4. The main P.C. board is defective.
1. The indoor fan motor is defective.
(Protected operation of P.C. board)
2. The connection of the motor
connector is loose.
3. The P.C. board is defective.
Table 9-8-2 Appr oximate resistance v alue of thermo sensor
Temperature0°C10°C20°C25°C30°C
Resistance value35.820.712.610.07.92
9-8-2. How to shorten time of restart delay time
(1) Set the operation mode, temperature, and air flow
rate to be applied with the timer short mode.
(2) Push the [CLR] button while keeping [CHK] button
pushed. in this case, the check mode is released,
and the timer short mode is waited.
MODE
AUTO
COOL
DRY
AUTO FAN
TEMP.
Hr.ON OFF
TEMP.
FAN
AUTO
QUIET
(The status is kept even if [CHK] and [CLR] buttons
are released.)
START/STOP
(3) Pushing [START/STOP] buttons sends operation
code + timer short code.
(4) The timer short mode is released by only a trans-
mission. Therefore, repeat steps from (2) to
perform the timer short mode again.
SWING
FIX
FAN
MODE
ONOFFSETCLR
RST
TIMER
CHK
ECO
[CHK] button
[CLR] button
(kΩ)
– 66−
Page 68
9-9. Troubleshooting for Remote Control
FILE NO. SVM-05010
Is receiver on
indoor unit exposed
to direct sunlight?
YES
NO
Is there any
thyristor fluorescent
light nearby?
YES
YES
NONO
Press START/STOP
button.
Is transmission
mark indicated?
Does indoor unit
operate when
moving remote control
near receiver or
indoor unit?
YES
Batteries are
exhausted.
The unit does not beep at all.
OPERATION lamp on
indoor unit is not indicated.
NO
Press ACL button
on remote control
with tip of pencil.
Press START/STOP
button.
Avoid direct
sunlight.
Keep indoor unit
away from
thyristor
fluorescent light.
Does indoor unit
NO
start to operate by
automatic restart
function?
YES
Does radio sound
is affected by
remote control when
a signal is transmitted
at distance of 5 cm
from radio?
P.C. board is
defective.
Replace
P.C. board.
YES
Is transmission mark
indicated?
NO
NO
Replace
batteries.
Note : After replacing batteries,
press the RESET button
with a tip of a pencil.
Does indoor unit
beep and operate?
operation
YES
YES
Normal
NO
Remote control
is defective.
Replace
remote control.
– 67 –
Page 69
(2)
(2)(2)
4-screws
(6) TC sensor
FILE NO. SVM-05010
10. PART REPLACEMENT
10-1. Indoor Unit
No.Part nameProceduresRemarks
1Front panel
How to remove the front panel
1) Stop the operation of the air conditioner and turn off
its main power supply.
2) Pull the inlet grille toward you to open it and remove
4 screws fixing the front panel.
3) Remove upper 3 hooks of the front panel from the
back body.
4) Open the horizontal grille right below by hand.
5) Pull the lower side of the front panel toward you
until it touches the horizontal grille to remove it.
2Electrical part
assembly
How to mount the front panel
1) Mount the front panel with the inverse procedure of
“How to remove the front panel”.
2) Push 3 places (right, left and center) of the air
outlet.
3) Check the gap between the front panel and the
back body.
If you operate the air conditioner in cooling or dry
operation without pushing the 3 places, the surface
of the front panel may be covered with frost and
have dewdrops.
1) Remove the front panel with the procedure 1.
2) Remove the screw fixing the electrical part box.
3) Remove the drain guide.
4) Remove the connector (5P) for the fan motor and
the connector (6P) for the louver motor from the
microcomputer assembly.
5) Remove the screw for the earth, and pull the
electrical part base toward you to remove it from
the main unit.
6) Pull out the TC sensor from the sensor holder.
(3) Drain guide
(3)
(4)
(5) screws
5P
6P
(2) screws
When assembling the electrical parts
assembly, make the connecting cable
U-shaped and put it in the drain pan.
– 68 –
Page 70
Bearing base
Bearing
Motor fixture
(4) BODY (R)
(3) 2 screws
(4)
FILE NO. SVM-05010
No.Part nameProceduresRemarks
3Horizontal g rille
1) Remove center 2 shafts of the horizontal grille from
the back body.
2) Remove left shaft of the horizontal grille from the
back body.
3) Remove the horizontal grille from the back body.
(1) Center shafts
(2) Left shafts
4Heat exchanger
5Cross flow fan
1) Remove the front panel, electrical parts assembly
and the horizontal grille with procedure 2 and 3.
2) Remove the screw on the rear side of the main unit
to remove the pipe holder.
3) Remove 2 screws fixing the heat exchanger and
the bearing base.
4) Remove 2 screws fixing the heat exchanger fixtures
(upper and lower) and the back body then pull out
the upper side of the heat exchanger slowly.
1) Remove the front panel, electrical parts assembly,
horizontal grille and the heat exchanger with
procedure 4.
2) Loosen the set screw of the cross flow fan.
3) Remove 2 screws fixing the bearing base and the
back body.
4) Pull the cross flow fan toward you.
Pipe holder
(3) 2 screws
(2) Screw
Bearing base
(4) 2 screws
(3) Screws
(2) Set screw
6Bearing base
7Fan motor
When assembling the cross flow fan, fix it
with the set screw at the position where the
gap between the back body and the right
surface of the cross flow fan is 4 mm.
1) Remove the front panel, electrical parts assembly,
horizontal grille, heat exchanger and the cross flow
fan with procedure 5.
2) Remove the bearing from the bearing base.
If the housing protrudes from the base bearing, put
the housing in position and assemble the bearing to
the bearing base.
1) Remove the front panel, electrical parts assembly,
horizontal grille, and the heat exchanger with
procedure 4.
2) Loosen the set screw of the cross flow fan.
3) Remove 2 screws of the motor fixture.
4) Remove the lower side of the body (R) and move it
right to remove it.
5) Remove the motor from the motor fixture.
– 69 –
Page 71
FILE NO. SVM-05010
10-2. Outdoor Unit (38CJR024-723, 38TAR024X-723, 38TAR018-723)
No.Part nameProceduresRemarks
1Common
procedure
1) Stop the operation of the air conditioner and turn off
its main power supply or remove the power supply
cord.
2) Remove the electrical parts cover .
(4 screws ∅4 x 10L)
3) Remove 2 cord clamps (4 screws ∅4 x 22L) and
disconnect the power supply cord and connecting
cable after removing 6 screwson on the terminal
block and 1 ground screw on the electrical parts
base.
4) Remove the top cabinet. (7 screws ∅4 x 10L)
5) Remove the front cabinet. (2 screws ∅4 x 10L)
6) Remove the side cabinet
(4 screws ∅4 x 10L & 2 screws ∅4 x 14L)
Top cabinet
Front cabinetSide cabinet
4 screws ∅4 x 22L
Electrical
parts cover
2Running
capacitor
for compressor
3Running
capacitor
for fan motor
4Magnetic
contactor
5Spark killer
1) Perform the common procedure 1
2) Remove the capacitor band. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor
terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor
terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (2 screws ∅4 x 10L)
3) Disconnect the lead wires from the terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the terminal.
Spark killer
Magnetic contactor
Cooling only model
Running capacitor
for compressor
Running capacitor
for fan motor
– 70 –
Page 72
FILE NO. SVM-05010
10-3 Outdoor Unit (38CJR018-723)
No.Part nameProceduresRemarks
1Common
procedure
1) Stop the operation of the air conditioner and turn off
its main power supply or remove the power supply
cord.
2) Remove the packed valved cover and the electrical
Parts cover
(3 screws ∅ 4 x 10L)
3) Remove 2 cord clamps (4 screws ∅ 4 x 22L) and
disconnect the power supply cord and connecting
cable after removing 6 screws on the terminal block
and 1 ground screw on the electrical parts base.
4) Remove the upper cabinet. (4 scerws ∅ 4 x 10L)
(Pulling out upward)
5) Remove the front cabinet. (3 screws∅ 4 x 10L)
(Pull the front right protion toward you, and remove
it pulling out upward.)
Packed valve cover
Upper
cabinet
Electric
parts cover
3 - screws ∅ 4 x 10L
2 Cord clamps
4 - screws ∅4 x 22L
2Running
capacitor
for compressor
Running
3
capacitor
for fan motor
4Magnetic contactor
Spark killer
5
1) Perform the common procedure 1
2) Remove the capacitor band. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor
terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor
terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (2 screws ∅4 x 10L)
3) Disconnect the lead wires from the terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅
4 x 10L)
3) Disconnect the lead wires from the terminal.
Front
cabinet
Running capacitor
for compressor
Magnetic
contactor
Spark killer
Running capacitor
for fan motor
− 71 −
Page 73
FILE NO. SVM-05010
10-4. Outdoor Unit (38HNR024-713)
No.Part nameProceduresRemarks
1Common
procedure
1) Stop the operation of the air conditioner and turn off
its main power supply or remove the power supply
cord.
2) Remove the electrical parts cover .
(4 screws ∅4 x 10L)
3) Remove 2 cord clamps (4 screws ∅4 x 22L) and
disconnect the power supply cord and connecting
cable after removing 6 screwson on the terminal
block and 1 ground screw on the electrical parts
base.
4) Remove the top cabinet. (7 screws ∅4 x 10L)
5) Remove the front cabinet. (2 screws ∅4 x 10L)
6) Remove the side cabinet
(4 screws ∅4 x 10L & 2 screws ∅4 x 14L)
Top cabinet
Front cabinetSide cabinet
4 screws ∅4 x 22L
Electrical
parts cover
2Running
capacitor
for compressor
3Running
capacitor
for fan motor
4Magnetic
contactor
5Transformer
6P.C. Board
1) Perform the common procedure 1
2) Remove the capacitor band. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor
terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor
terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (2 screws ∅4 x 10L)
3) Disconnect the lead wires from the terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (2 screws ∅4 x 10L)
3) Disconnect the housing from the P.C. Board.
1) Perform the common procedure 1
2) Disconnect the lead wires from the P.C. Board.
3) Remove P.C.Board after unhooking 4 clams.
Magnetic contactor
P.C. Board
Transformer
Running capacitor
for compressor
Running capacitor
for fan motor
– 72 –
Page 74
FILE NO. SVM-05010
10-5 Outdoor Unit (38HNR018-713)
No.Part name Procedures Remarks
1 Common
procedure
1) Stop the operation of the air conditioner and turn off
its main power supply or remove the power supply
cord.
2) Remove the electrical parts cover.
(4 screws ∅ 4 x 10L)
3) Remove 2 cord clamps (4 screws ∅ 4 x 22L) and
disconnect the power supply cord and connecting
cable after removing 6 screws on the terminal block
and 1 ground screw on the electrical parts base.
4) Remove the front cabinet. (8 scerws ∅ 4 x 10L)
(Pull the front lower portion toward you, and pull out
it upward to remove it.)
5) Remove the side cabinet. (8 screws ∅ 4 x 10L)
Remove
8 screws Ø4 x 10L
4 screws Ø4 x 22L4 screws Ø4 x 10L
2 Running
capacitor
for compressor
3 Running
capacitor
4 Magnetic contactor
5 Transformer
6 P.C. Board
1) Perform the common procedure 1
2) Remove the capacitor band. (1 screw ∅ 4 x 10L)
3) Disconnect the lead wires from the capacitor
terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅ 4 x 10L)
3) Disconnect the lead wires from the capacitor
terminal.