Carrier 42BVE user guide manual

Fig. 1 — Component Identification (42BHE Units Shown)
A42-3984
AirStream™
42BHE,BVE06-40
System Fan Coil Air Conditioners
Installation, Start-Up and Service Instructions

CONTENTS

Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1,2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Step 2 — Protect Unit from Damage . . . . . . . . . . . . . . 2
Step 3 — Prepare Jobsite . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 4 — Prepare Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Step 5 — Position Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Step 6 — Make Piping Connections . . . . . . . . . . . . . 11
Step 7 — Make Electrical Connections . . . . . . . . . . 13
Step 8 — Make Duct Connections . . . . . . . . . . . . . . . 14
Step 9 — Install Mixing Box . . . . . . . . . . . . . . . . . . . . . 14
Step 10 — Make Final Preparations . . . . . . . . . . . . . 15
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Air System Balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Clean Coils. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Check Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Fan and Motor Bearings. . . . . . . . . . . . . . . . . . . . . . . . . 16
Align Pulley . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Adjust Fan Belt Tension . . . . . . . . . . . . . . . . . . . . . . . . . 16
Clean Fan Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Clean or Replace Air Filters . . . . . . . . . . . . . . . . . . . . . 16
Recommended Maintenance . . . . . . . . . . . . . . . . . . 16
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Excessive Condensation on Fan Coil Unit
Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Motor Overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
START-UP CHECKLIST . . . . . . . . . . . . . . . . . CL-1,CL-2

SAFETY CONSIDERATIONS

Air-handling equipment is designed to provide safe and reliable service when operated within design specifications. To avoid injury to personnel and damage to property or equip­ment, use good judgment and follow safe practices as outlined below when installing and operating this equipment.
DANGER
NEVER REACH INTO a unit while the fan is running. LOCK OPEN AND TAG the fan motor power disconnect
switch before working on unit. In addition, remove the fuses and take them with you after noting this on tag.
DISCONNECT ALL POWER before attempting any installation or service. More than one power source may be supplied to a unit. Power to remote mounted control devices may not be supplied through the unit.
CHECK THE WEIGHT of assembly and components to be sure that rigging equipment can handle them safely.
NEVER PRESSURIZE a coil with a non-liquid for leak testing. A dangerous burst may occur.
DO NOT STEAM CLEAN coils until you are sure all per­sonnel are clear of the area.
Failure to follow these warnings will result in severe per­sonal injury or death.

INTRODUCTION

The following contains general installation instructions for the 42BHE,BVE fan coil units. See Fig. 1 for components. Re­fer to the unit wiring diagram installed on the blower housing or specific manufacturer literature for any other type of factory­mounted controls.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53420009-01 Printed in U.S.A. Form 42B-4SI Pg 1 11-13 Replaces: 42B-3SI
See drawings for unit configurations, dimensions, clearanc-
WIDTH
E
2
K
J
TOP VIEW
SEE DETAIL 1
DEPTH
FILTER RACK WITH TOOLLESS ACCESS FROM SIDES AND BOTTOM
HANGER ROD
KNOCKOUT Ø5/8
TYP 4 PLCS
1/2
1/2
DETAIL 1
SCALE 0.250
1-3/8
1" SUPPLY
AIR COLLAR
SUPPLY AIR
COIL DRAIN CONN.
[MALE 3/4-14 NPT]
[FEMALE 1/2-14 NPT
SECONDARY]
4 X 4 JBOX AND MOTOR MOUNTED SAME SIDE AS COIL CONNECTIONS
SIDE VIEW
1
F RETURN AIR
1" RETURN AIR COLLAR
COIL SUPPLY CONN.
COIL RETURN CONN.
4-3/8 ADD 2" FOR MERV11 FILTER
BOTH SIDE PANELS WITH TOOLLESS CAMLOCK ACCESS
FRONT VIEW 2-1/16
D
A
C
B
HEIGHT
NOTES:
1. All dimensions are in inches (±1/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to change without notice.
3. Right hand shown, left hand opposite.
4. Hanger rods, which are field-supplied, are shown for reference only.
5. Control box size and position may vary.
6. “C” dimension is measured from coil side of the unit.
UNIT
42BHE
DIMENSIONS (in.)
Fan Size Depth Width Height
Supply Duct Return Duct Mounting Holes
AB CDEF J K
06 9 x 4 36 28 19
3
/
4
71/
8
101/
2
141/
2
21/424 161/
2
271/
4
351/
4
08 9 x 6 36 28 193/
4
81/
2
101/
2
137/
8
21/424 161/
2
271/
4
351/
4
10 10 x 4 371/
2
37 211/
2
71/
8
115/
8
151/
4
21/433 181/
4
361/
4
37
12 10 x 7 37
1
/
2
37 211/
2
10 115/
8
137/
8
21/433 181/
4
361/
4
37
16 11 x 10 37
3
/
4
47 211/
2
133/
8
123/
4
163/
4
21/443 181/
4
461/
4
37
20 12 x 9 40
1
/
4
48 24 121/
2
133/
4
173/
4
21/444 203/
4
471/
4
391/
2
30 12 x 12 401/
4
48 321/
4
157/
8
133/
4
16 71/444 29 471/
4
391/
2
40 15 x 12 431/
2
62 321/
4
161/
2
161/
8
223/
4
61/458 29 613/
4
421/
2
Fig. 2 — Unit Dimensions — 42BHE Fan Coil Base Unit (No Controls)
es, and pipe connections. Refer to unit wiring label for all elec­trical connections. Follow NEC (National Electrical Code) and local codes.

INSTALLATION

Step 1 — Unpack and Inspect Unit —
ping wraps from unit and check shipment against shipping list. Check for concealed shipping damage. If shipment is damaged or incomplete, file claim with transportation company and contact your local Carrier representative immediately.
Remove ship-
Step 2 — Protect Unit from Damage — To main-
tain warranty, protect unit against adverse weather conditions, theft or vandalism on the jobsite.
The described equipment IS NOT suitable for outdoor in­stallations. The equipment should never be stored or installed where it may be subjected to a hostile environment such as rain, snow, or extreme temperatures.
Step 3 — Prepare Jobsite — To save time and to re-
duce the possibility of costly errors, set up a complete sample installation in a typical room at jobsite. Check all critical di­mensions such as pipe, wire and duct connection requirements. Refer to job drawings and product dimension drawings as re­quired. Instruct all trades in the appropriate part of the installa­tion. For unit component identification, refer to Fig. 1. For unit dimensions, refer to Fig. 2-4 for 42BHE units. Refer to Fig. 5-7 for 42BVE units.
2
WIDTH
NOTES:
1. All dimensions are in inches (±1/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to change without notice.
3. Right hand shown, left hand opposite.
4. Hanger rods, which are field-supplied, are shown for reference only.
5. Control box size and position may vary.
6. “C” dimension is measured from coil side of the unit.
UNIT
42BHE
DIMENSIONS (in.)
Fan Size Depth Width Height
Supply Duct Return Duct Mounting Holes
AB CDEF J K
06 9 x 4 36 28 19
3
/
4
71/
8
101/
2
141/
2
21/
4
24 161/
2
271/
4
351/
4
08 9 x 6 36 28 193/
4
81/
2
101/
2
137/
8
21/
4
24 161/
2
271/
4
351/
4
10 10 x 4 371/
2
37 211/
2
71/
8
115/
8
151/
4
21/
4
33 181/
4
361/
4
37
12 10 x 7 37
1
/
2
37 211/
2
10 115/
8
137/
8
21/
4
33 181/
4
361/
4
37
16 11 x 10 37
3
/
4
47 211/
2
133/
8
123/
4
163/
4
21/
4
43 181/
4
461/
4
37
20 12 x 9 40
1
/
4
48 24 121/
2
133/
4
173/
4
21/
4
44 203/
4
471/
4
391/
2
30 12 x 12 401/
4
48 321/
4
157/
8
133/
4
16 71/
4
44 29 471/
4
391/
2
40 15 x 12 431/
2
62 321/
4
163/
8
161/
8
223/
4
61/
4
58 29 613/
4
421/
2
a42-4241
Fig. 3 — Unit Dimensions — 42BHE Fan Coil Base Unit with Motor Control Option
E
2
FILTER RACK WITH
TOOLLESS ACCESS
FROM SIDES
AND BOTTOM
K
18 DOOR OPEN
J
TOP VIEW
A
D
B
FRONT VIEW
DEPTH
8-11/16
SEE DETAIL 1
MOTOR CONTROLS AND MOTOR
MOUNTED SAME SIDE AS
COIL CONNECTIONS
C
HANGER ROD
KNOCKOUT Ø5/8
TYP 4 PLCS
1-3/8
1" SUPPLY
AIR COLLAR
HEIGHT
SUPPLY AIR
COIL DRAIN CONN.
[FEMALE 1/2-14 NPT SECONDARY]
[1MALE 3/4-14 NPT]
DETAIL 1 SCALE 0.250
1/2
1/2
SIDE VIEW
BOTH SIDE PANELS WITH TOOLLESS CAMLOCK ACCESS
4-3/8 ADD 2" FOR MERV11 FILTER
COIL RETURN CONN.
F
COIL SUPPLY CONN.
1
RETURN AIR
1" RETURN
AIR COLLAR
3
WIDTH
E
K
9-11/16
1" SUPPLY
AIR COLLAR
J
TOP VIEW
2
FILTER RACK WITH TOOLLESS ACCESS FROM SIDES AND BOTTOM
DEPTH
SEE DETAIL 1
20
DOOR OPEN
ELECTRIC HEAT AND MOTOR MOUNTED SAME SIDE AS COIL CONNECTIONS
1-3/8
HEIGHT
SUPPLY AIR
FRONT VIEW
A
C
13-3/4
HANGER ROD
KNOCKOUT Ø5/8
TYP 4 PLCS
1/2
1/2
DETAIL 1 SCALE 0.250
BOTH SIDE PANELS WITH TOOLLESS CAMLOCK ACCESS
4-3/8 ADD 2" FOR MERV11 FILTER
COIL RETURN CONN.
COIL SUPPLY CONN.
SIDE VIEW
COIL DRAIN CONN.
[MALE 3/4-14 NPT]
[FEMALE 1/2-14 NPT SECONDARY]
1
1" RETURN AIR COLLAR
RETURN AIR
D
B
NOTES:
1. All dimensions are in inches (±1/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to change without notice.
3. Right hand shown, left hand opposite.
4. Hanger rods, which are field-supplied, are shown for reference only.
5. “C” dimension is measured from coil side of the unit.
UNIT
42BHE
DIMENSIONS (in.)
Fan Size Depth Width Height
Supply Duct Return Duct Mounting Holes
AB CDEF J K
06 9 x 4 36 28 19
3
/
4
87/
8
101/
2
141/
2
21/424 161/
2
271/
4
351/
4
08 9 x 6 36 28 193/
4
87/
8
101/
2
137/
8
21/424 161/
2
271/
4
351/
4
10 10 x 4 371/
2
37 211/
2
103/8115/
8
151/
4
21/433 181/
4
361/
4
37
12 10 x 7 37
1
/
2
37 211/
2
103/
8
115/
8
137/
8
21/433 181/
4
361/
4
37
16 11 x 10 37
3
/
4
47 211/
2
137/
8
123/
4
163/
4
21/433 181/
4
461/
4
37
20 12 x 9 40
1
/
4
48 24 13 133/
4
173/
4
21/444 203/
4
471/
4
391/
2
30 12 x 12 401/
4
48 321/
4
161/
4
133/
4
16 71/444 29 471/
4
391/
2
40 15 x 12 431/
2
62 321/
4
163/
4
161/
8
223/
4
61/458 29 613/
4
421/
2
Fig. 4 — Unit Dimensions — 42BHE Fan Coil Base Unit with Electric Heat Option
A42-661EF
4
C
A
7-7/16
TOP VIEW
2-1/16
B
4 X 4 JBOX AND MOTOR
MOUNTED SAME SIDE AS
COIL CONNECTIONS
DEPTH
1-7/16
1" SUPPLY AIR COLLAR
SUPPLY AIR
BOTH SIDES AND FRONT PANEL WITH CAMLOCK ACCESS
4-3/8 ADD 2" FOR MERV11 FILTER
HEIGHT
RETURN AIR
COIL RETURN CONN.
COIL SUPPLY CONN.
COIL DRAIN CONN.
[MALE 3/4-14 NPT]
[MALE 1/2-14 NPT SECONDARY]
SIDE VIEW
FILTER RACK WITH TOOLLESS ACCESS FROM SIDES AND TOP
1" RETURN AIR COLLAR
2
E
WIDTH
FRONT VIEW
F
1"
NOTES:
1. All dimensions are in inches (±
1
/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to change without notice.
3. Left hand shown, right hand opposite.
4. Drain pan removal is on the piping side of the unit.
5. “C” dimension is measured from coil side of the unit.
UNIT
42BVE
DIMENSIONS (in.)
Fan Size Depth Width Height
Supply Duct Return Duct
AB CEF
06 9 x 4 20 28 36
1
/
2
71/
8
101/
2
163/
4
24 161/
2
08 9 x 6 20 28 361/
2
81/
2
101/
2
151/
4
24 161/
2
10 10 x 4 22 37 393/
8
71/
8
115/
8
241/
2
33 181/
4
12 10 x 7 22 37 393/
8
10 115/
8
211/
2
33 181/
4
16 11 x 10 22 47 393/
8
133/
8
123/
4
163/
4
43 181/
4
20 12 x 9 24 48 451/
8
121/
2
133/
4
173/
4
44 203/
4
30 12 x 12 28 48 541/
4
157/
8
133/
4
16 44 29
40 15 x 12 28 62 57
5
/
8
161/
2
161/
8
223/
4
58 29
A42-4242
Fig. 5 — Unit Dimensions — 42BHV Fan Coil Base Unit (No Controls)
5
A
C
B
1"
TOP VIEW
8-3/4"
17-15/16"
DOOR OPEN
HEIGHT
2"
F
1"
E
WIDTH
FRONT VIEW
MOTOR CONTROLS
AND MOTOR MOUNTED
SAME SIDE AS
COIL CONNECTIONS
SUPPLY AIR
DEPTH
1" SUPPLY AIR COLLAR
BOTH SIDES AND FRONT PANEL WITH CAMLOCK ACCESS
4-3/8 ADD 2" FOR MERV11 FILTER
COIL RETURN CONN.
COIL SUPPLY CONN.
RETURN AIR
1" RETURN AIR COLLAR
COIL DRAIN CONN.
[MALE 3/4-14 NPT]
[MALE 1/2-14 NPT SECONDARY]
SIDE VIEW
FILTER RACK WITH TOOLLESS ACCESS FROM SIDES AND TOP
NOTES:
1. All dimensions are in inches (±
1
/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to change without notice.
3. Left hand shown, right hand opposite.
4. Drain pan removal is on the piping side of the unit.
5. “C” dimension is measured from coil side of the unit.
UNIT
42BVE
DIMENSIONS (in.)
Fan Size Depth Width Height
Supply Duct Return Duct
AB CEF
06 9 x 4 20 28 36
1
/
2
71/
8
101/
2
163/
4
24 161/
2
08 9 x 6 20 28 361/
2
81/
2
101/
2
151/
4
24 161/
2
10 10 x 4 22 37 393/
8
71/
2
115/
8
241/
2
33 181/
3
12 10 x 7 22 37 393/
8
10 115/
8
211/
2
33 181/
3
16 11 x 10 22 47 393/
8
133/
8
123/
4
163/
4
43 181/
3
20 12 x 9 24 48 451/
8
121/
2
133/
4
173/
4
44 203/
4
30 12 x 12 28 48 543/
16
157/
8
133/
4
16 44 29
40 15 x 12 28 62 57
5
/
8
167/
16
161/
8
223/
4
58 29
a42-4243
Fig. 6 — Unit Dimensions — 42BHV Fan Coil Base Unit with Motor Control Option
6
SUPPLY AIR
DEPTH
COIL RETURN CONN.
COIL SUPPLY CONN.
COIL DRAIN CONN.
[MALE 3/4-14 NPT]
[MALE 1/2-14 NPT SECONDARY]
SIDE VIEW
FILTER RACK WITH
TOOLLESS ACCESS
FROM SIDES AND TOP
1" RETURN AIR COLLAR
RETURN AIR
4-3/8 ADD 2" FOR MERV11 FILTER
BOTH SIDES AND FRONT PANEL WITH CAMLOCK ACCESS
ELECTRIC HEAT AND MOTOR
MOUNTED SAME SIDE AS
COIL CONNECTIONS
20"
DOOR OPEN
HEIGHT
2" E
WIDTH
FRONT VIEW
1"
F
9-11/16"
1" SUPPLY AIR
COLLAR
TOP VIEW
1"
13-13/16
C
B
A
NOTES:
1. All dimensions are in inches (±1/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to change without notice.
3. Left hand shown, right hand opposite.
4. Drain pan removal is on the piping side of the unit.
5. “C” dimension is measured from coil side of the unit.
UNIT
42BVE
DIMENSIONS (in.)
Fan Size Depth Width Height
Supply Duct Return Duct
AB CEF
06 9 x 4 20 28 36
1
/
2
87/
8
107/
8
163/
4
24 161/
2
08 9 x 6 20 28 361/
2
87/
8
107/
8
151/
4
24 161/
2
10 10 x 4 22 37 393/
8
103/
8
12 241/
2
33 181/
3
12 10 x 7 22 37 393/
8
103/
8
12 211/
2
33 181/
3
16 11 x 10 22 47 393/
8
137/
8
13 163/
4
43 181/
3
20 12 x 9 24 48 451/
8
13 141/
8
173/
4
44 203/
4
30 12 x 12 28 48 543/
16
161/
4
141/
8
16 44 29
40 15 x 12 28 62 57
5
/
8
163/
4
163/
8
223/
4
58 29
a42-4244
Fig. 7 — Unit Dimensions — 42BHV Fan Coil Base Unit with Electric Heat Option
7
Step 4 — Prepare Unit — Be sure that unit power re-
Fig. 8 — 42BHE Units with Seismic Compliance Option —

Threaded Rod Suspension

a42-4370
quirements match available power source. Refer to unit name­plate and wiring diagram. Check all tags on unit to determine if any shipping screws are to be removed. Remove screws as directed.

Step 5 — Position Unit

1. The air handler has 5/8-in. knockouts in each corner of the top and bottom panels for suspension rods to pass through. Be sure to support the unit from underneath until mounting is complete.
2. Install vibration isolators as shown in Fig. 1 (recommend­ed for all sizes). Field-supplied and field-installed acces­sories must be independently supported or suspended. It is recommended that a trapeze suspension be used on 42BHE size 30 and 40 units. (42BHE size 30 and 40 units with seismic compliance option require a trapeze suspen­sion. See the section 42BHE Units with Seismic Compli­ance Option.)
3. 42BHE Units with Seismic Compliance Option (optional for other installations) — For 42BHE (horizontal) units with seismic compilance option, a threaded-rod trapeze suspension is required for unit sizes 30 and 40. Install the trapeze so that it does not block bottom access for filter removal. Install factory-provided seismic cable restraints. See Fig. 8 and 9.
4. 42BVE Units with Seismic Compliance Option (optional for other installations) — 42BVE (vertical) units with seismic compliance option for non-isolated mounting must be secured to a pad or base rail using factory-in­stalled mounting brackets. Anchor hardware is field-sup­plied and must be Hilti Kwik Bolt TZ expansion anchors
or similar carbon steel anchors tested in accordance with ACI (American Concrete Institute) 355.2 and ICC-ES (International Code Council-Evaluation Service) AC 193. See Fig. 10 for anchor size, mounting hole locations, and relevant dimensions.
42BVE (vertical) units with seismic compliance option
for isolated mounting must be mounted using the vibra­tion isolators provided by the factory with the unit. An­chor hardware is field-supplied and must be Hilti Kwik Bolt TZ expansion anchors or similar carbon steel an­chors tested in accordance with ACI 355.2 and ICC-ES AC 193. See Fig. 11 for isolated mounting locations and spring mounting details.
5. For units with mixing boxes, follow Step 9 for installation instructions.
6. To ensure proper drainage and operation, be sure unit is level. DO NOT mount the unit on a slope. The pitch of a suspended unit can change after coil is filled; recheck after filling. Drain pan has built-in slope to ensure proper drainage.
7. Sufficient clearance must be maintained for service and maintenance. Ensure that there is a minimum clearance of 24 in. on access side for motor, pulley and belt access. Filter shall be removed from side or top of the filter rack on vertical unit (42BVE) and side or bottom of the filter rack on horizontal unit (42BHE). If side access to filter is desired, the minimum clearance required is the width of the filter rack plus 6 inches.
8. Protect unit from damage from jobsite debris. Do not allow foreign material to fall into drain pan. Prevent dust and debris from being deposited on motor or fan.
TRAPEZE - REQUIRED ON 42BHE UNIT SIZES 30 AND 40.
1.5 x 1.5 x 1/4” ANGLE FIELD-SUPPLIED AND INSTALLED ALONG BOTH LONG EDGES.
WASHER AND DOUBLE NUT (FIELD FURNISHED AND INSTALLED)
5/8” KNOCKOUTS FOR SUSPENSION RODS (4 PLACES TOP AND 4 PLACES BOTTOM OF UNIT
ISOLATORS - 4 PER UNIT (FACTORY FURNISHED AND FIELD INSTALLED)
3/8” THREADED ROD SUSPENSION
(FIELD FURNISHED AND INSTALLED)
8
SUPPORT RODS TO STRUCTURE
42BVE UNIT
SEE DETAIL A
ISOLATION HANGER QTY (4) REQUIRED
SLOTTED AT TAC H ME N T BRACKET
45˚-60˚
45˚
45˚
SIDE VIEW
ISOLATION HANGER QTY (4)
TOP VIEW
TO CEILING ATTACHMENT
TO CEILING ATTACHMENT
TO CEILING ATTACHMENT
TO CEILING ATTACHMENT
DETAIL A
SLOTTED BRACKET
ATTACHMENT BRACKET CEILING ATTACHMENT TYPE (NON-SLOTTED)
CEILING
AT TAC H ME N T HARDWARE FIELD-SUPPLIED
CEILING ATTACHMENT
DETAIL
½˝ HEX HEAD BOLT
½˝ LOCK NUT
Fig. 9 — 42BHE Units with Seismic Compliance Option —

Mounting Details, Cable Restraint Kit

a42-4394
NOTES:
1. Kit consists of 4—Slotted brackets 4—Holed Brackets 16—Bolts 16—Serrated flange nuts 4—20-ft lengths of cable (
1
/2-in or 1/4-in as required)
2. Field-torque 1/2-in. lock nut to 75 ft-lb.
9
E
D
E
A
Ø USE (4) 1/2" ANCHORS
.50
TYP.75
42BVE UNIT SIZES 06,12
B
C
B
A
D
E
Ø.50 (
8X) USE (8) 1/2" ANCHORS
TYP
.75
F REF
E
C
42BVE UNIT SIZES 16-30
C C BBA
Fig. 10 — 42BVE Seismic Compliance Option — Non-Isolated Mounting Details
A42-4367
A42-4368
A42-4369
42BVE Unit Size
Dimensions (in.)
ABCDEF REF
06,08 29.59 N/A N/A 16.00 2.00 N/A 10,12 38.56 N/A N/A 18.00 2.00 N/A
16 15.06 14.00 2.00 18.00 2.00 48.56 20 15.16 14.50 2.00 20.00 2.00 49.56 30 16.06 14.00 2.00 24.00 2.00 49.56 40 21.06 18.50 2.00 22.00 3.00 63.56
E
D
42BVE UNIT SIZE 40
Ø.50 (4X) USE (4) 1/2" ANCHORS
.75
TYP
E
F REF
Ø.625 (4X) USE (4) 5/8" ANCHORS
10
42BVE06-08
42BVE10-20
42BVE30-40
SEISMIC INSTALLATION PACKET IN SLEEVE
SEISMIC INSTALLATION PACKET IN SLEEVE
SEISMIC INSTALLATION PACKET IN SLEEVE
ISOLATION KIT FLOOR MTD SPRING ISOLATORS AMSR-IC (QTY 4) ½˝ HILTI KWIKBOLT TZ EXPANSION ANCHORS (QTY 8 )
ISOLATION KIT FLOOR MTD SPRING ISOLATORS AMSR-IC (QTY 4) ½˝ HILTI KWIKBOLT TZ EXPANSION ANCHORS (QTY 8 )
ISOLATION KIT FLOOR MTD SPRING ISOLATORS AMSR-IC (QTY 4) ½˝ HILTI KWIKBOLT TZ EXPANSION ANCHORS (QTY 8 )
Fig. 11 — 42BVE Seismic Compliance Option — Isolation Mount Details
½" ADJUSTING BOLT AND NUT
EQUIPMENT BRACKET
(2) ELASTOMERIC RESTRAINTS
SPRING CUP TOP AND BOTTOM
SPRING
RIBBED ELASTOMERIC PAD
¼"
4
5
/
8"
OPERATING
HEIGHT
4
7
/
8"
FREE
HEIGHT
1"
ELASTOMERIC
BUSHING
(2)
5
/
8"
DIA
HOLES
3"
1½"
¾"
6"
4½"
¾"
ISOLATOR DETAIL
a42-4395
a42-4393
Step 6 — Make Piping Connections (See Table 1 and Fig. 2-7)
DRAIN — The unit has a double-sloped condensate drain pan to ensure proper drainage. The condensate drain must be at
3
least
/4-in. copper, galvanized, black iron, or PVC piping. In­stall the trapped drain line in accordance with all applicable codes. Slope drain away from unit to prevent overflowing and insulate the line to prevent sweating.
Drain piping should be sloped a minimum of away from the unit. Condensate drain must be trapped for proper drainage and odor control. The differential height of the trap inlet to outlet must be at least 1 in. wg greater than the total static pressure of the unit. The differential height of the outlet to
the bottom of the trap must not be less than the total static pres­sure of the unit.
The 42BVE units should be installed on a pad. The height of the pad should be adequate to allow for a proper condensate trap. The condensate trap shown in Fig. 12 is for a unit with a total static pressure (TSP) of 2 in. wg with a 1-in. wg safety factor for any change in operating conditions. The A dimension must equal the system TSP plus 1 in. wg. The B dimension is
1
/8-in. per ft
one half of A, and C is the total of A + B + pipe diameter.
11
valves are in proper operating position and are easily accessible
42BHE/BVE
UNIT
CASING
3.0
1.5
CLEAN-OUT
ALLOW A MINIMUM OF
C INCHES FROM BOTTOM
OF UNIT TO FINISHED FLOOR
(42BVE UNIT) OR TO FALSE
CEILING (42BHE UNIT).
C
B
A
Fig. 12 — Condensate Trap
NOTE: Dimension C is the total of A + B + the pipe diameter.
a42-4366
for adjustment. HYDROSTATIC TEST — When all joints are completed,
perform hydrostatic test for leaks. Hydronic systems should be tested with water (some components are not designed to hold gas). If gas testing is necessary, pressure must NOT exceed 80 psig. All chilled water piping and valves not located over drain pans or drip lips must be insulated to prevent damage from sweating. Vent all coils during final preparations. (See Step 10, section 6.)
WARNING
Never pressurize unit beyond the specified test pressure. Always pressure test with an inert gas or fluid (nitrogen or clear water) to avoid possible unit damage or personal injury in the event of a leak during testing.
The unit drain pan is equipped with a secondary connection that must be piped to an open-site drain. This will prevent over­flow and possible building damage if the primary drain is blocked. The secondary drain connection can be capped if po­tential overflow will not damage the building or unit.
WATER SUPPLY/RETURN CONNECTIONS — Install pip­ing in accordance with all applicable codes. The supply and return connections are marked on the coil stub ends with an “S” on the supply (inlet) and an “R” on the return (outlet). Blue letters mark chilled water connections, red letters indicate steam or hot water connections. Install valves in lines in accordance with valve manufacturer’s instructions. Be sure
Check interior unit piping for signs of leakage from ship­ping damage or mishandling. If leaks are found, notify your lo- cal Carrier representative before initiating any repairs.
CAUTION
All water coils must be protected from freezing after initial filling with water. Even if system is drained, unit coils may still hold enough water to cause damage when exposed to temperatures below freezing.
INSULATION — Following the hydrostatic test, insulate all piping to unit to prevent sweating.
Table 1 — Unit Physical Data
UNIT SIZE 42BHE, BVE 06 08 10 12 16 20 30 40 NOMINAL CFM 600 800 1000 1200 1600 2000 3000 4000 42BHE OPERATING WT (lb)
(no heat/ with heat) 42BVE OPERATING WT (lb)
(no heat/ with heat) FILTERS (2 in. pleated)
Number...Size (in.) 1...161/2 x 24 1...161/2 x 24 1...181/4 x 33 1...181/4 x 33 2...181/4 x 211/22...203/4 x 22 2...29 x 22 2...29 x 29 Face Area (sq ft) 2.8 2.8 4.2 4.2 5.5 6.3 8.9 11.7
HYDRONIC COILS
Size (in.) 15 x 20 15 x 20 15 x 29 15 x 29 15 x 39 18 x 40 27 x 40 27 x 54 Face Area (sq ft) 2.1 2.1 3.0 3.0 4.1 4.9 7.7 10.3
Fins per inch Coil Water Volume (approx. gal. per row of coil)
FANS
Qty...Size (in.) 1...9 x 4 1...9 x 6 1...10 x 4 1...10 x 7 1...11 x 10 1...12 x 9 1...12 x 12 1...15 x 12
HYDRONIC COIL CONN. (in.)
8 ROW (Cooling) 1 nominal, 1.125 OD 1
4 AND 6 ROW (Cooling)
1 ROW (Heating)
2 ROW (Heating)
DX COIL CONN. LIQUID LINE (in.)
DX COIL CONN. SUCTION LINE (in.)
DRAIN CONN. SIZES (in.)
LEGEND
DX— Direct Expansion
203/234 205/236 253/287 256/290 312/346 344/380 437/474 553/590
200/231 202/233 243/277 247/281 289/323 351/387 436/473 522/559
10
0.240 0.240 0.324 0.324 0.420 0.492 0.768 1.020
1
3
/4 nominal, 0.875 OD 1 nominal, 1.125 OD 11/2 nominal, 1.625 OD
1
/2 nominal, 0.625 OD 1 nominal, 1.125 OD 11/2 nominal, 1.625 OD
3
/4 nominal, 0.875 OD 1 nominal, 1.125 OD 11/2 nominal, 1.625 OD
1
/2 nominal, 0.625 OD 11/2 nominal, 1.625 OD
1
/4 nominal, 0.375 OD
3
/4 MPT
/2 nominal, 1.625 OD
1
/2 nominal, 0.625 OD
12
Step 7 — Make Electrical Connections — Refer to
the unit rating plate for supply voltage, motor and heater am­perage, and required circuit ampacities. (See Tables 2-4.) The unit wiring diagram shows all factory and field wiring. Most of the unit motors are dual voltage that are factory wired for a specified voltage. The motors should be checked to ensure that they are wired for the correct voltage and rotation.
Units equipped with factory-installed motor controls and disconnect will comply with NEC requirements for disconnect, motor controller and motor overload protection. Separate dis­connect and motor starter are not required to comply with NEC requirements.
All field wiring should be done in accordance with all appli­cable local and national codes. Any factory wiring modifica­tions without factory authorization will void all factory warran­ties and nullify any agency listings.
The manufacturer assumes no responsibility for any dam­age and/or injuries resulting from improperly installed or wired components.
Install fan switches, thermostats and other accessories in accordance with accessory manufacturer’s instructions and ap­plicable wiring diagram.
Table 2 — 42BHE,BVE Electric Heater Availability
kW
1.0 ●●——————
1.5 ●●●●————
2.0 ●●●●————
2.5 ●●●●●———
3.0 ●●●●●———
3.5 ●●●●●●——
4.0 ●●●●●●——
4.5 ●●●●●●——
5.0 ●●●●●●——
6.0 ●●●●●●●●
7.0 ●●●●●●●
8.0 ●●●●●●●
9.9 ——●●●●●●
12.0 ———●●●●●
14.0 ————●●●●
15.0 ————●●●●
16.0 ————●●●●
18.0 —————●●●
19.9 —————●●●
25.0 ——————●●
30.0 ——————●●
35.0 ———————
39.9 ———————
— Standard OfferingNot Offered
NOTES:
1. Stages available: a. Single phase: 1 to 12 kW, 1 stage only
b. Three phase: 1 to 39.9 kW, 1 stage only
2. Electric Heating Capacities (Btuh) = Heater kW x 3413
3. Electric Heater Amperage for Single-phase Power = (Heater kW x 1000)/Applied Voltage Electric Heater Amp. for 3-phase Power = (Heater kW x 1000)/ (Applied Voltage x 1.73).
06 08 10 12 16 20 30 40
LEGEND
3 to 12 kW, 1 stage or 2 stage
4 to 39.9 kW, 1 or 2 stage 12 to 39.9 kW, 1, 2 or 3 stage
42BHE UNIT SIZE
Table 3 — 42BHE,BVE Electric Heater Data
kW
115 V 208 V 240 V 277 V 208 V 240 V 480 V
1.0 8.3 4.8 4.2 3.6 2.8 2.4 1.2
1.5 12.5 7.2 6.3 5.4 4.2 3.6 1.8
2.0 16.7 9.6 8.3 7.2 5.6 4.8 2.4
2.5 20.8 12.0 10.4 9.0 6.9 6.0 3.0
3.0 25.0 14.4 12.5 10.8 8.3 7.2 3.6
3.5 29.2 16.8 14.6 12.6 9.7 8.4 4.2
4.0 33.3 19.2 16.7 14.4 11.1 9.6 4.8
4.5 37.5 21.6 18.8 16.2 12.5 10.8 5.4
5.0 24.0 20.8 18.1 13.9 12.0 6.0
6.0 28.8 25.0 21.7 16.7 14.4 7.2
7.0 33.7 29.2 25.3 19.4 16.8 8.4
8.0 38.5 33.3 28.9 22.2 19.2 9.6
9.9 35.7 27.5 23.8 11.9
12.0 43.3 33.3 28.9 14.4
14.0 38.9 33.7 16.8
15.0 41.6 36.1 18.0
16.0 38.5 19.2
18.0 ——————21.7
19.9 ——————23.9
25.0 ——————30.1
30.0 ——————36.1
35.0 ——————42.1
39.9 ——————48.0
Single-Phase Three-Phase
FULL LOAD AMPS
Table 4 — Motor Performance Data
(Full Load Amps)
VOLTAGE
V-P h-Hz
115-1-60 5.2 6.0 8.6 13.3 14.4 208-1-60 3.0 3.6 4.8 6.6 7.4 9.4 11.0 230-1-60 2.5 3.0 4.2 5.1 6.0 9.0 10.9 277-1-60 2.1 2.5 3.6 5.1 5.4 8.5 8.0 208-3-60 2.4 3.6 3.8 6.0 6.5 8.2 14.0 230-3-60 2.2 3.0 3.2 4.8 6.2 8.0 13.2 460-3-60 1.1 1.5 1.9 2.8 3.1 4.0 6.6
NOTES:
1. Motor full load amps refer to National Electric Code (NEC) amps; actual motor nameplate amps may vary.
2. NEC data extrapolated for 277 v.
3. Motors are open drip proof, ball bearing, single speed, 1750 rpm rated at continuous duty, 104 F ambient with reversible rotation.
4. 5HP motors available only on size 40 units.
1
1
/
/
4
3
Nominal HP
1
3
/
/4111/2235
2
SERVICE SWITCHES: — The service switch is an On/Off switch on incoming power supply to unit. Proper amperage load must be determined before switch can be selected. The range of the fused or non-fused service switch is 0 to 40 amps.
MCA (minimum circuit amps) = 1.25 x sum of all loads.
MFS (maximum fuse size = MCA rounded up to next available fuse size.
13
Step 8 — Make Duct Connections — Install all duct-
Fig. 13 — Assemble Base Rails
a42-4164
a42-4165
Fig. 14A — Install Mixing Box — 42BHE units
a42-4373
work to and from unit in accordance with all applicable codes. Duct construction must allow unit to operate within the limits of the unit external static pressure as shown on job submittals.
Units designed to operate with ductwork may be damaged if operated without the intended ductwork attached. Units config­ured to bring in outside air should have some method of low temperature protection to prevent coil freeze-up.
Insulate all ductwork as required. Use flexible connections to minimize duct-to-duct alignment problems and noise trans­mission where specified. Acoustic lining of main supply and return duct should be considered for noise control. Noise trans­mission will be reduced when return grilles are located as far as possible from the unit.
Install ductwork, accessory grilles, and plenums so that they do not restrict access to filter.
NOTE: Prevent dirt, dust, and debris from settling in unit.
Step 9 — Install Mixing Box — Mixing boxes are
preassembled from the factory. A linkage kit consisting of 2 crankarms, 2 swivels, and either a 25-in. (unit sizes 06-16) or a 34-in. (unit sizes 20-40) length of field installation of the actuator.
To install the mixing box:
1. Assemble the mixing box base rails using the provided hardware. The base rails are marked with identifying let­ters. See Fig. 13.
2. Place unit on the base rails. Install mixing box and attach to base rails using the no. 8 x tions shown in Fig. 14A (42BHE units) or Fig. 14B (42BVE units).
3. Seal the connection between the mixing box and the re­turn duct flange.
5
/16 in. rod is provided for
1
/2 in. fasteners at the loca-
NOTE: Be careful not to tape or seal the filter access panel.
MOUNTING
LOCATION
DETAIL A DETAIL B
SEE DETAIL A
SEE DETAIL B
MOUNTING
LOCATION
14
SEE DETAIL A
Fig. 14B — Install Mixing Box — 42BVE units
a42-4372
SEE DETAIL B
MOUNTING
LOCATION
MOUNTING
LOCATION
DETAIL A DETAIL B

Step 10 — Make Final Preparations

1. TURN POWER OFF. (Open unit electrical disconnect.)
2. Clean unit thoroughly. Remove dirt and debris from unit, especially drain pan, drain line, motor and fan. Pour water into drain pan to check that drain operates properly.
3. Rotate fan wheel by hand to be sure wheel is free and does not rub housing. The 42BHE,BVE belt drives are factory set at the speed required for the design specifica­tions specified when ordered. These drives may be ad­justed to achieve different speed by qualified personnel during air system balancing. Refer to the Start-Up section before energizing the unit. Check fan belt tension as de­scribed in the Service section which follows.
4. Check that a clean air filter of proper type and size is in­stalled in unit filter rack after commissioning. See Table 1 and Clean or Replace Air Filters section. Do NOT oper­ate unit without filter.
5. Turn on water supply. Open all valves. Check for leaks. Recheck pitch of suspended unit.
6. Vent all air from unit coil and related piping. If air vent is manual, release air by turning air vent screw 1 counterclockwise with screwdriver. When a steady stream of water begins to escape, close valve. If vent is automatic, trapped air will be released automatically. Vent releases air slowly, usually dripping water into the drain pan in the process.
1
/2 turns
CAUTION
The air vent provided on the unit is not intended to replace the main system vents and may not release air trapped in other parts of the system. Inspect the entire system for potential air traps and vent those areas as needed. Some systems may require repeated venting over a period of time to properly eliminate air from the system. Failure to do so could result in equipment damage.
7. TURN POWER ON. (Close unit electrical disconnect.) NOTE: Be sure power is off before making any adjust-
ments inside unit.
8. Check fan and motor operation. Motor to fan wheel rota­tion must match airflow direction shown in Fig. 2-7.
Set unit air delivery for required blower rpm per job sub­mittals or product data catalog. Adjust fan motor pulley (Fig. 15) as follows:
a. Loosen setscrew on movable pulley flange. b. Screw flange toward fixed flange to increase fan
speed and away from fixed flange to decrease speed. c. Reset setscrew. d. Check belt tension. The drive belt should be ten-
sioned to allow
point between pulleys with moderate pressure.
1
/2 to 3/4-in. deflection at the mid-
15
Inspect the unit for loose wires, correct blower wheel opera-
Fig. 15 — Fan Pulley Adjustments
a42-89tf
tion, and loose or missing access panels or doors. Unless other­wise required for balancing and start-up procedures, units should not be operated without proper ductwork, supply/return air grilles, and access panels and/or doors in place.
CAUTION
Do not exceed motor nameplate FLA (full load amps). Operator must confirm motor current draw before putting unit into service and again after air balancing the system. Failure to do so could result in equipment damage.

START-UP

CAUTION
Follow all safety considerations previously outlined. Fail­ure to do so could result in personal injury or equipment damage.
Start-up procedures vary depending upon the time of year (summer or winter) and building characteristics (new building or old building, occupied or unoccupied, etc.).
Start-up in the Cooling mode requires that proper care be giv­en to avoid condensation problems. Condensation forms on sur­faces that are colder than the dew point of the surrounding air. If a unit is started and is fed low-temperature chilled water in a hot, humid setting, condensation will form on many parts of the unit. In order to avoid excessive condensation, water of higher temperature should be used, approximately 65 to 70 F. Also, the building should be as completely enclosed as possible and outside-air supply fans and toilet and kitchen exhaust fans should be off.
As the building temperature drops, the chilled water temper­ature can gradually be reduced until it reaches 50 F. At this point, the outside-air fans can be turned on. When the chilled water temperature is reduced to its design point, the exhaust fans can be turned on.
Air System Balancing — All ductwork, air grilles, fil-
ters, and access doors and panels must be complete and con­nected to establish actual system operating conditions before air system balancing procedures are started.
NOTE: Units are factory set for system designed operating conditions specified at the time of order entry.
Proper belt drive alignment and tension must be maintained when adjusting the unit fan drive speed. The drive belt tension should not exceed leys under 8 lb of force. New belts tend to stretch during their initial period of use. After 5 days of operation, check and read­just belt tension and pulley alignment if necessary. Failure to do so may result in excessive unit noise and/or premature belt/ bearing failure.
3
/16-in. deflection midway between the pul-

SERVICE

WARNING
Lock open and tag electrical disconnect before servicing equipment. Failure to do so could result in personal injury or death.

Clean Coils

1. Brush between coil fins with a stiff wire brush. Do not bend fins. Follow up by cleaning with a vacuum cleaner. If coil is cleaned with an air hose, take care not to drive dirt and dust into other components.
2. Install clean air filters.
Check Drain — Check drain pan, drain line and trap at
start of each cooling season. A standard type pipe cleaner for
3
/4-in. ID pipe can ensure removal of obstructions so that con­densate is carried away. Check the drain line at filter cleaning time during the cooling season.
Fan and Motor Bearings — Fan shaft bearings are
permanently lubricated and sealed, and need no attention. Check tag on motor for motor bearing lubrication instructions (if any). Most motors furnished with these units are perma­nently lubricated.
Align Pulley — Loosen pulley setscrew(s). Align pulleys
by using a straight edge as shown in Fig. 15. Retighten set­screw(s).
Adjust Fan Belt Tension — Loosen fan motor base
mounting screws. Reposition the motor so that belt deflection does not exceed tighten motor mounting screws and recheck fan belt tension.
3
/16-in. at belt midpoint under 8 lb of force. Re-
Clean Fan Wheel — Use a stiff brush or vacuum to re-
move dirt and debris from scroll. Wipe all fan surfaces with a damp cloth.
Clean or Replace Air Filters — At the start of each
cooling season and after each month of operation (more or less depending on operating conditions), replace unit filter.
To remove filter, slide filter out of filter rack from either side
of return-air duct collar. THROWAWAY OR PLEATED FILTER — Replace filter
with a good quality filter of the size shown in Table 1. Do not attempt to clean and reuse a disposable filter.

Recommended Maintenance

Quarterly
• Lubricate motor and blower bearings (if applicable)
• Check and adjust belt tension
• Change air filter Annually — in addition to quarterly maintenance
• Inspect all wiring connections and tighten if necessary
• Check and tighten set screws on pulleys
• Clean coil and drain pan
• Clean blower wheel as needed
16

TROUBLESHOOTING

Excessive Condensation on Fan Coil Unit Parts —
chilled water through a fan coil unit with its fan off. If fan cy­cling control is used, a water flow control valve should be in­stalled to shut off the water when the fan stops.
The following two practices will also help avoid condensa-
tion problems:
1. Continuous fan operation with motorized chilled water
2. Continuous fan operation with thermostat control to
Excessive condensation can be caused by running
valve controlled by thermostat.
switch fan from high to low speed (instead of switching it off).
Motor Overload — The following are causes and reme-
dies for motor trip-out on overload:
Cause: Fan delivers too much air because external stat-
ic pressure is lower than the design pressure.
Remedy: Reduce fan speed by adjusting motor pulley or
changing fan shaft pulley to larger diameter.
Cause: Air temperature across fan motor is too high
(heating mode).
Remedy: Check ambient temperature on motor’s name-
plate. Compare to actual air temperature at the motor or at the fan discharge. If motor’s name­plate lists an ambient temperature of 104 F and the actual air temperature is higher, either low­er the air temperature or obtain a special motor rated for high ambient temperatures.
17
© Carrier Corporation 2013
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53420009-01 Printed in U.S.A. Form 42B-4SI Pg 18 11-13 Replaces: 42B-3SI
INITIAL START-UP CHECKLIST
FOR AIRSTREAM™ 42BHE,BVE06-40 SYSTEM FAN COIL AIR CONDITIONERS
(Remove and use for job file.)
START-UP CHECKLIST
The following is a checklist to be completed before start-up:
1. General visual unit and system inspection
2. Check that unit is level
3. Record electrical supply voltage
4. Check all wiring for secure connections
5. Verify with straight edge alignment of motor and blower pulleys
6. Tighten all set screws
7. Confirm V-belt is properly tightened
8. Check condensate drain connection
9. Verify trap is deep enough
10. Prime the trap with water
11. Check supply and return water connections for leaks
12. Fill systems with water by opening supply ball valve and control valve
13. Open air vent on top of coil to vent air out of system
14. Open return ball valve
15. Engage power only long enough to verify proper blower rotation
16. Check all ductwork and grilles in place
17. Check all unit panels and filters in place
18. Start fans, pumps, chillers, etc.
19. Check for overload conditions of all units
20. Check all ductwork and units for air leaks
21. Balance water systems, as required
22. Balance air systems, as required
23. Record all final settings for future use
24. Check piping and ductwork for noise or vibration 25 Check all dampers for proper operation
26. Verify proper cooling operation
27. Verify proper heating operation
28. Reinstall all covers and access panels
29. Verify proper condensate drainage
Ye s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s NoYe s No
CL-1
COMMENTS:
________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________
SIGNATURES: Start-up
Technician ________________________________________________________Date_______________________
Customer Representative ____________________________________________________Date_______________________
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
© Carrier Corporation 2013
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53420009-01 Printed in U.S.A. Form 42B-4SI Pg CL-2 11-13 Replaces: 42B-3SI
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
Loading...