Carrier’s versatile belted fan coil units
satisfy design requirements:
• A selection of 8 sizes covers
capacities from 600 to 4000 cfm
• Choice of motors, from
eliminates oversizing
• Wide range of coil options for 2-pipe
or 4-pipe systems
• Optional DX coils with expansion
valve and distributor
• Single and three-phase electric
heat (1.0 to 40 kW)
1
/4to 5 hp,
42BHC UNIT
Features/Benefits
The 42BHC, BVC belt drive
fan coil units provide yearround comfort air
conditioning with central
station operating economy.
A variety of coil options
reduces first cost
Four, 6 or 8-row cooling coils combine
needed capacities with the most efficient heat transfer surface. For
4-pipe systems, select either of two
split-coil options. Coils consist of aluminum fins securely bonded to
OD seamless copper tubes. Each fin’s
aluminum collar ensures accurate control of the fin spacing, while completely covering the tubes to lengthen coil
life. All coils also feature manual air
vents, with automatic air vent available
as an option.
1
/2-in.
42BVC UNIT
Copyright 2005 Carrier CorporationForm 42B-1PD
Fan wheels are designed to
provide low operating costs
The forward-curved, centrifugal,
double-inlet fans are statically and
dynamically balanced at the factory to
minimize transmission of vibration
to the building structure.
The belt-driven motor (single or
three phase) has a variable-pitch pulley
which adjusts at the jobsite to accommodate limited ranges of air quantities
and pressures.
All motors (single and three phase)
are UL listed, factory wired, single
speed with thermal overload protection and are continuous duty rated.
Motors are supplied with permanently
lubricated bearings, class-B insulation
and are open drip-proof. The motor
mount has an adjustable platform for
easy belt adjustment. The motor and
its mounting are independently isolated
from the cabinet and the blower. An
adjustable pitch pulley allows cfm balancing to meet system requirements.
Motor drive packages are provided
with keyed pulleys.
Complete factory assembly
minimizes on-the-jobsite costs
and problems
Compact, lightweight units are designed
for easy mounting. Knockouts designed
to accept
3
/8-in. threaded rods are
provided on the top and bottom of each
corner of the unit One-in. duct collars
on discharge and on return are furnished standard. These integral duct
collars cut installation time and labor
expense.
Durable construction means
easy-to-maintain units
The 42BHC,BVC fan coils casings are
fabricated from heavy-gage galvanized
G90 steel, reinforced for maximum
rigidity and structural strength. Removable side panels with tool-less camlock
fasteners allow easy access for servicing interior components.
One-inch matte surface, fiberglass
thermal/acoustical insulation lines the
fan coil cabinets to prevent sweating
and to muffle sound transmission.
The stainless steel, double-sloped
condensate drain pan extends under
full coil surface to cut maintenance
costs.
Slide-in return-duct collar filter
makes it possible to remove and
replace the filter without disturbing
return air ductwork.
/2x 24 1...161/2x 24 1...181/4x 33 1...181/4x 33 2...181/4x211/22...203/4x 22 2...29 x 22 2...29 x 29
10
0.2400.2400.3240.3240.4200.4920.7681.020
1OD1
3
/4OD1 OD11/2OD
1
/2OD
3
/4MPT
1
/2OD
3
Options and accessories
42BHC, BVC OPTIONS AND ACCESSORIES
ITEMOPTION*ACCESSORY†
Automatic Air VentsX
ControlsX
Electric HeatX
FiltersX
Heating/Cooling CoilsX
InsulationX
Mixing BoxesX
MotorsX
ThermostatsX
Valve PackagesX
*Factory-installed option.
†Field-installed accessory.
The 42BHC and 42BVC fan coil units are designed to
offer maximum flexibility in an application, accessibility for
service, quiet operation and durability.
Factory-installed options
Automatic air vents — Automatic air vents have fiber-
washers, which allow air in the pipes to pass through,
automatically bleeding the system. The fiber washers eliminate the need to manually remove air from the system.
When wet, washers swell and seal the system.
Coils — Coils are available in a choice of two-pipe system
with 4-row cooling/heating or four-pipe system with 4, 6
or 8-row cooling and 1 or 2 row heating.
Reheat operation is standard. Preheat is available as an
option.
Controls
• Interlocking disconnect switch
• Heater power fusing
• 24 v Class 2 transformer (40 va)
• 8-pole control terminal strip
• Auto reset temperature limit switch
• Airflow safety switch
• Motor power fusing
• Motor control contactor
• 24 v condensate overflow switch
Electric heat — Total electric heat eliminates the require-
ment for a boiler. Heating and/or cooling may be available
on an individual basis throughout the year. Resistance
electric heat is available from 1.0 kW to 40.0 kW (refer to
electric heater data table for availability per unit) with
single-stage or multiple-stage, single power source.
Voltages:
• 115 v, 208 v, 230 v and 277 v single-phase 60 Hz
• 208 v, 230 v and 480 v three-phase 60 Hz
Electric heat is available with the following staging options
(3-phase staging is balanced).
• 1 to 12 kW 1 stage only — single phase
• 3 to 12 kW 1 or 2 stage only — single phase
• 1 to 40 kW 1 stage only — 3 phase
• 4 to 40 kW 1 or 2 stage only — 3 phase
• 12 to 40 kW 1, 2, or 3 stage — 3 phase
Heater coils are constructed of high-grade resistance
wire that is supported by ceramic insulators on plated steel
brackets. These heat elements are suspended directly in
front of the outlet after the blower and the coil. High limit
thermal cutouts protect the heater in the event of air
failure.
Filters — Two in. pleated filters are standard. One-in.
pleated, two 1-in. throwaway, or 2-in. MERV (minimum
efficiency reporting value) 11 filters with 2-in. pleated
pre-filter are available. The 2-in. MERV 11 filters with 2-in.
pleated pre-filter include a filter rack.
Insulation — Tuf-Skin™ II (1-in. thick) insulation is
standard. Units are available with ¾-in. closed cell, 1-in.
Tuf-Skin Rx™ edge sealed, or 1-in. foil-faced insulation.
Motors — A wide selection of standard motors provides
efficient operation in ducted applications with excellent
performance with up to 2 inches of total static pressure.
Available motor options:
• 115 v, 208 v, 230 v and 277 v single-phase 60 Hz
• 208 v, 230 v and 460 v three-phase 60 Hz
• Open drip-proof motors
• External junction box
Field-installed accessories
Mixing boxes — Mixing boxes can be used when outside
air is required for ventilation. Preassembled at the factory
and shipped separately with base rails for field installation,
mixing boxes include a linkage kit consisting of two crank
arms, 2 swivels and either a 25 in. long (for sizes 06-16) or
a 84 in. long (for sizes 20-40) rod for field installation of an
actuator.
4
Thermostats — Three thermostats are available for field
installation:
• outside air signal
Honeywell T8500 digital, automatic/manual changeover,
2-stage heat thermostat features:
• digital display of temperatures and all functions
• off-cool-heat-auto system mode buttons
• single speed fan operation
• on-auto fan mode button
• single or two stage electric heat signal
• outside air signal
• remote temperature sensor available
Sunne T170 single-stage heat, 2-pipe heat/cool auto
changeover thermostat features:
• digital display of ambient temperature and operating
mode
• single fan speed operation, power and operating mode
buttons
• continuous fan operation, cycling water control valve
• 4-pipe ACO/MCO (automatic changeover/manual
changeover) with “on-auto” fan mode button
• one or 2 stage electric heat signal available
• purge cycle and temperature sensor for 2-pipe cold
water/hot water systems
• programmable operating range, dead band, digital display, temperature set-back
THERMOSTAT FUNCTIONS
SYSTEMFUNCTIONCHANGEOVER
2PipeHW-Heat OnlyACO—XX
2 PipeCW-Cool OnlyACO—XX
2Pipe
2Pipe
2Pipe
4Pipe
ACO — Automatic Changeover
Aux — Auxiliary
CW— Chilled Water
HW— Hot Water
MCO — Manual Changeover
CW/HW
Heat/Cool
CW/HW
Heat/Cool with
Aux. Electric Heat
CW-Cooling with
To t al Electric Heat
CW/HW
Heat/Cool
LEGEND
MCO——X
ACO——X
MCO——X
ACO——X
MCOXXX
ACO—XX
MCOXXX
ACO—XX
THERMOSTATS
Honeywell
T834C
Honeywell
T8500
Sunne
T170
Valve packages — Valve packages are factory assembled
for field installation. Motorized valves (24 v) can be operated with power on with spring return or power off/power
on.
It is recommended that basic motor controls are ordered
when valve packages are ordered.
5
Base unit dimensions
42BHC FAN COIL BASE UNIT (NO CONTROLS)
UNIT
42BHC
069x 436
089x 6363/
1010 x 4373/
1210 x 7373/
1611 x 103715/
2012 x 940
3012 x 12403/
4015 x 12439/
NOTES:
1. All dimensions are in inches (±
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to
4. Hanger rods, which are field-supplied, are shown for reference only.
7
Base unit dimensions (cont)
42BHC FAN COIL WITH ELECTRIC HEAT OPTION
UNIT
42BHC
069x 436
089x 6363/
1010 x 4373/
1210 x 7373/
1611 x 103715/
2012 x 940
3012 x 12403/
4015 x 12439/
NOTES:
1. All dimensions are in inches (±
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to
change without notice.
4. Hanger rods, which are field-supplied, are shown for reference only.
16
16
8
42BVC FAN COIL BASE UNIT (NO CONTROLS)
UNIT
42BVC
069x 42028
089x 620281/
1010 x 422371/
1210 x 722371/
1611 x 1022471/
2012 x 924481/
3012 x 1228481/
4015 x 1228621/
NOTES:
1. All dimensions are in inches (±
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to
change without notice.
Fan SizeDepthWidthHeight
1
/
16
16
16
16
16
16
16
16
1
/4in.).
DIMENSIONS (in.)
361/
2
361/
2
393/
8
393/
8
393/
451/
543/
575/
8
8
16
8
135/
121/
157/
167/
Supply DuctReturn Duct
AB CEF
71/
89/
71/
915/
8
16
2
16
16
2
8
16
109/
109/
1111/
1111/
1211/
133/
133/
161/
16
16
16
16
16
4
4
16
33/
33/
51/
51/
167/
1713/
161/
227/
4
4
2
2
8
16
8
8
241/
241/
331/
331/
431/
441/
441/
581/
167/
16
16
16
16
16
16
16
16
167/
183/
183/
183/
2011/
2815/
2815/
16
16
16
16
16
3. Right hand shown, left hand opposite.
4. Hanger rods, which are field-supplied, are shown for reference only.
16
16
16
9
Base unit dimensions (cont)
42BVC FAN COIL WITH MOTOR CONTROL OPTION
UNIT
42BVC
069x 42028
089x 620281/
1010 x 422371/
1210 x 722371/
1611 x 1022471/
2012 x 924481/
3012 x 1228481/
4015 x 1228621/
NOTES:
1. All dimensions are in inches (±
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to
069x 42028
089x 620281/
1010 x 422371/
1210 x 722371/
1611 x 1022471/
2012 x 924481/
3012 x 1228481/
4015 x 1228621/
NOTES:
1. All dimensions are in inches (±
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to
Fan SizeDepthWidthHeight
1
/
16
16
16
16
16
16
16
16
1
/4in.).
DIMENSIONS (in.)
361/
2
361/
2
393/
8
393/
8
393/
451/
543/
575/
8
8
16
8
135/
121/
157/
167/
Supply DuctReturn Duct
AB CEF
71/
89/
71/
915/
8
16
2
16
16
2
8
16
109/
109/
1111/
1111/
1211/
133/
133/
161/
16
16
16
16
16
4
4
16
33/
33/
51/
51/
167/
1713/
161/
227/
4
4
2
2
8
16
8
8
241/
241/
331/
331/
431/
441/
441/
581/
16
16
16
16
16
16
16
16
167/
167/
183/
183/
183/
2011/
2815/
2815/
change without notice.
3. Right hand shown, left hand opposite.
4. Hanger rods, which are field-supplied, are shown for reference only.
16
16
16
16
16
16
16
16
11
Base unit dimensions (cont)
42BHC UNIT CORNER WEIGHTS (lb)
1
3
4
RIGHT HAND UNIT
UNIT
42BHC
NOTE: Unit weights (shown in pounds) ±10%, are based on the 8-row coil and 1 Hp motor.
CONFIGURATION
06
08
10
12
16
20
30
40
No Heat5055475155505147203
With Heat5058596758506759234
No Heat5155475255515247205
With Heat5059596859506859236
No Heat6371556371636355253
With Heat6276688176628168287
No Heat6472566472646456256
With Heat6376688276638268290
No Heat8087697687807669312
With Heat7991829591799582346
No Heat9098748298908274344
With Heat90102881001029010088380
No Heat1181279210012711810092437
With Heat118131106119131118119106474
No Heat155162114122162155122114553
With Heat155166129140166155140129590
2
RIGHT-HAND UNITSLEFT-HAND UNITS
12341234
1
3
LEFT HAND UNIT
2
4
TOTAL
WEIGHT
12
42BVC UNIT CORNER WEIGHTS (lb)
1
3
2
4
1
3
1
3
2
4
RIGHT HAND UNIT
UNIT
42BVC
06
08
10
12
16
20
30
40
NOTE: Unit weights (shown in pounds) ±10% are based on the 8-row coil and 1 Hpmotor.
CONFIGURATION
No Heat5254514354524351200
With Heat5865614765584761231
No Heat5355514355534351202
With Heat5866624766584762233
No Heat6369615069635031243
With Heat6981725481695472277
No Heat6470625170645162247
With Heat7082735582705573281
No Heat7485725885745872289
With Heat8098846198806184323
No Heat901088668108906886351
With Heat951239971123957199387
No Heat1101391068113911081106436
With Heat1151551208315511583120473
No Heat1311721259417213194125522
With Heat1351901409519013594140559
RIGHT-HAND UNITSLEFT-HAND UNITS
12341234
1
3
LEFT HAND UNIT
2
2
WEIGHT
4
4
TOTAL
TOTAL WEIGHT UNIT CORRECTION FACTOR (lb)
Corner weights on pages 12 and 13 are for 8-row water filled coils. For a different number of rows, total unit weight
can be determined by the following procedure:
• Identify the number of rows and the size of the unit.
• Determine the total weight of the unit from the Corner Weight tables.
• From the table below, identify the correction factor (for size of unit and number of rows) and subtract this from the
total weight.
Use the table on the next page to determine the location of the piping
connections. For example, on a size 20 unit with 4 rows and a right
hand connection, the location of the chilled water supply line is determined by G (6 in.) and B (7
HEAD STUB OUT SIZES (in.)
6RowCoilSO
Nominal
4RowCoilSO
Nominal
4
/5in.).
Heating 1 or 2 SO
Row Coil Nominal
17
Accessory dimensions (cont)
HEAT OPTIONS
Re-heat
Pre-heat*
*Factory-installed option.
42BHC,BVC
UNIT SIZE
06/08
10/12
16
20
30/40
06/08
10/12
16
20
30/40
COIL ROWSDIMENSIONS (in.)
0—
4
13
23
0————
6
13
23
80—— ——10
4
0—
15
25
6
0————
15
25
80—— ——10
4
0—
1
25
0————
6
1
25
80—— ——10
4
0—
1
25
0————
6
1
25
80—— ——10
4
0—
1
23
0————
6
1
23
80—— ——10
4
6
80— 6
0—6
13
23
0—6
13
23
0—7
4
15
25
0—7
6
15
25
80— 7
4
0—7
15
25
6
0—7
15
25
80— 7
4
6
80— 7
0—7
15
25
0—7
15
25
0—5
4
13
23
0—5
6
13
23
80— 5
A BCDEFGHCoolHeat
1
/
13
/
1
/
13
/
1
/
7
/
16
1
/
27
/
LH 105/
RH 133/
7
/
16
LH 105/
RH 133/
7
/
16
LH 1115/
RH 1411/
1
/
LH 1115/
RH 1411/
1
/
LH 141/
RH 1813/
5
/
LH 141/
RH 1813/
5
/
1
/
13
/
1
/
13
/
1
/
7
/
16
1
/
7
/
16
1
/
7
/
16
1
/
7
/
16
3
/
16
1
/
3
/
16
1
/
5
/
16
5
/
5
/
16
5
/
———
2
16
2
16
8
8
61
61/
8
73/
4
123/
143/
4
8
151/
2
1513/
16
151/
2
1513/
16
———
171/
8
177/
16
171/
8
177/
16
77
79/
16
93/
16
93/
4
77
79/
16
93/
16
93/
4
———
8
8
73/
8
8
4
155/
8
177/
177/
12
16
12
16
95/
95/
79/
1113/
1113/
93/
8
8
16
16
16
4
———
16
16
2
16
16
2
713/
16
183/
16
135/
201/
135/
201/
16
16
16
16
95/
95/
79/
1113/
1113/
93/
8
8
16
16
16
4
———
16
16
8
16
16
8
2
16
2
16
8
8
8
8
2
2
8
8
515/
87/
713/
87/
713/
69/
515/
69/
515/
16
1
/
8
63/
4
61/
8
1
/
8
63/
4
61/
8
1
/
8
3
/
4
83/
8
73/
4
3
/
4
83/
8
73/
4
3
/
4
3
/
4
83/
8
73/
4
3
/
4
83/
8
73/
4
3
/
4
13
/
16
16
16
13
/
16
16
16
13
/
16
15
/
16
16
16
15
/
16
16
16
15
/
16
265/
16
123/
4
133/
8
123/
4
123/
4
133/
8
123/
4
123/
4
143/
8
15171/
143/
8
143/
8
15171/
143/
8
143/
8
155/
8
161/
4
155/
8
155/
8
161/
4
155/
8
155/
8
183/
16
1813/
16
183/
16
183/
16
1813/
16
183/
16
183/
16
265/
16
2615/
16
265/
16
265/
16
2615/
16
265/
16
265/
16
167/
16
281/
8
167/
16
281/
8
———5
151/
2
1513/
16
———8
151/
2
1513/
16
———10
———5
8
177/
16
———8
8
177/
16
———10
———5
171/
8
177/
16
———8
171/
8
177/
16
———10
———5
193/
4
201/
16
———8
193/
4
201/
16
———10
———5
2713/
16
281/
8
—3
2713/
16
281/
8
—3
95/
8
95/
8
79/
16
1113/
16
1113/
16
93/
4
211/
16
31/
4
211/
16
31/
4
211/
16
31/
4
211/
16
31/
4
211/
16
31/
4
211/
16
31/
4
211/
16
31/
4
211/
16
31/
4
——73
211/
16
1
/
4
——9
211/
16
1
/
4
515/
79/
93/
79/
93/
79/
93/
93/
79/
93/
93/
79/
103/
103/
211/
93/
93/
7
7
93/
7
7
93/
8
8
93/
31/
16
16
81/
8
16
4
1
/
4
515/
16
16
81/
8
16
4
1
/
4
515/
16
16
16
81/
8
1
/
4
515/
16
81/
8
1
/
4
515/
16
81/
8
1
/
4
15
/16211/
733/
81/847/
1
/8211/
211/
16
4
16
16
16
4
16
16
16
4
16
4
211/1693/1633/
31/4101/447/
211/
31/
211/1693/1633/
31/4101/447/
211/
31/
211/1693/1633/
31/4101/447/
211/
31/
1
/4211/
15
/16211/
733/
16
81/847/
4
1
/8211/
1
/4211/
15
/16211/
733/
16
81/847/
4
1
/8211/
1
/4211/
15
/16211/
733/
16
81/847/
4
1
/8211/
211/1693/1633/
31/4101/447/
211/
31/
211/16101/447/
1
/4211/
15
/16211/
81/847/
16
81/8211/
4
3
/1633/
31/4101/4211/
16
16
4
8
16
4
8
16
16
4
8
16
4
8
16
16
4
8
16
4
8
16
16
4
8
16
4
8
16
16
3
/
4
8
16
4
8
16
18
Application data
Basic definitions
Unit hand — When facing the supply air outlet from the
front of the unit (air blowing in your face), your right hand
will be the right hand side of the unit and your left hand the
left hand side of the unit.
PIPING COMPONENTS
SYMBOL/SKETCHDESCRIPTION
MANUAL AIR VENT: Threaded brass needle valve
with screwdriver slot for adjustment.
Application — Body brazed into high point of heat-
ing and cooling coils for bleeding air from coil. Standard item on all hydronic coils (not used on steam
or DX coils). Should not be used in lieu of main system air vents.
AUTOMATIC AIR VENT: Nickel plated brass valve,
fiber-disc type, with positive shut-off ballcheck and
quick vent feature via knurled vent screw.
Application — Optional replacement for manual air
vent. Automatically passes minute quantities of air
through the fiber discs which expand upon contact
with water, completely sealing the valve. As air
accumulates, the fiber discs dry and shrink, repeating the cycle. Not recommended for removing large
quantities of air encountered during initial start-up
or subsequent draining and refilling. Should not be
used in lieu of main system air vents.
SWAGE: Copper tube end expanded to accept a
copper tube of the same size for factory or field
brazing.
Application — Used where possible for all tubing
joints for best joint integrity.
CIRCUIT SETTER: Variable water flow balancing
valve with manual adjustment knob, pointer, percent-open scale, memory stop and integral pressure read-out ports.
Application — Used for close tolerance water flow
balancing. Positive shut-off ball valve feature allows
usage as combination balancing and shut-off valve.
LEGEND
Cv — Coefficient of Velocity
DX— Direct Expansion
*Check all system component pressure ratings (coils, values, pumps,
etc.) with manufacturer and any applicable local or national piping
codes prior to specifying system pressure rating.
UNIT HAND
CVFACTORRATING*
1
/
2
N/AN/A400100
N/AN/A125240
N/AN/A300200
2.123.9300250
3
/
4
PSIF
19
Application data (cont)
PIPING COMPONENTS (cont)
SYMBOL/SKETCHDESCRIPTION
BALANCE VALVE: Variable water flow manual bal-
ancing valve with screwdriver slot adjustment
screw.
Application — Often used in conjunctionwithtest
port fittings for water flow balancing. Balance by
temperature differential or coil pressure drop
(check specifications for service fittings required if
balancing by pressure drop). May be used in 3-way
valve bypass line to permit equal flow balancing.
STRAINER: Y-type body with 50 mesh stainless
steel screen.
Application — Used for removal of small particles
from system water during normal system operation.
Should not be used in lieu of main system strainers. Strainer screen may have to be removed during initial high pressure system flushing during
start-up. Screen should be removed and cleaned
per normal maintenance schedule (provisions for
strainer blow-down not provided).
BALL VALVE: Manual balance and shut-off valve.
Application — Used for unit isolation and water flow
balancing. Without memory stop feature water balance point must be marked by installer (if necessary). Check specifications for service fittings
required when used for water balancing.
LEGEND
Cv — Coefficient of Velocity
DX— Direct Expansion
*Check all system component pressure ratings (coils, values, pumps,
etc.) with manufacturer and any applicable local or national piping
codes prior to specifying system pressure rating.
CVFACTORRATING*
1
/
2
3
/
4
PSIF
3.08.9150200
9.0
Clean
19.0
Clean
400250
4.07.5400200
20
PIPING COMPONENTS (cont)
SYMBOL/SKETCHDESCRIPTION
2-WAY MOTORIZED VALVE: Electric
2-position flow control valve (open/closed).
Normally closed body with manual override
lever. Installed in supply line to unit.
Application — All standard control and valve
packages are based upon normally closed
valves (valve electrically powered open and
closed by spring return when electric power
removed). Manual override lever allows valve
to be placed in the open position for secondary (unit) flushing, constant water flow prior to
start-up, etc. Manual override is automatically
disengaged when valve is electrically activated. Consult factory for normally open
valve applications.
3-WAY MOTORIZED VALVE: Electric
2-position flow control valve (closed to coil/
open to bypass or open to coil/closed to
bypass). Normally closed with manual override lever. Installed in supply line to unit.
Application — Same comments as 2-way
motorized valve except with manual override
lever engaged the valve is open to both ports
and water flow will take the path of least resistance through the valve package (not necessarily 100% through the coil).
C
FACTO R
V
1
/
2
3
/
4
1PSIF
3.55.08.0
SPRING RETURN
3.54.66.6
POWER ON/OFF
4.05.08.0
SPRING RETURN
3.85.99.0
RATING
300200
300200
LEGEND
Cv — Coefficient of Velocity
DX— Direct Expansion
NOTES:
1. Motorized spring return 2-way valves have a maximum close-off differential of 25 psi.
2. Motorized spring return 3-way valves have a maximum close-off differential of 25 psi.
POWER ON/OFF
21
Selection procedure
This selection procedure provides a guide to determine
unit performance of the 42BHC, BVC units. Capacity
tables (in Performance Data) are based on nominal cfm.
Correction factors are provided for other operating conditions as explained in the following selection example.
For applications outside the range provided in this
catalog, please consult the factory.
FORMULAS:
TC = TCb x Ct x Et
SC = SCb x Cs x Es
Where:
Cs = Sensible Airflow Correction Factor
Ct = Total Airflow Correction Factor
Es = Sensible Elevation Correction Factor
Et = Total Elevation Correction Factor
SC = Sensible Capacity
SCb = Base Sensible Capacity from Base Cooling Capaci-
ties by gpm charts
TC = Total Capacity
TCb = Base Total Capacity from Base Cooling Capacities
by gpm charts
EXAMPLE:
I Rate unit performance.
To rate the performance at sea level for a 42BHC16
unit with a four-row coil at 80 F/67 F EAT, 45 F EWT,
7 gpm water flow, and 1500 cfm:
a) Enter the Base Cooling Capacities by Gpm, 4-Row
Capacity Units table at 80 F/67 F EAT and
45 F EWT.
b) Locate the appropriate row for unit size 16 and
7 gpm.
Record the tabulated base performance.
TCb = 42.0 MBtuh
SCb = 34.2 MBtuh
∆T = 12.0 F
c) Divide CFM Actual by CFM Nominal to determine
Cfm Ratio.
Cfm Ratio = 1500/1600 =.9375
II Select CFM correction factors.
Select the Cfm correction factors, Ct and Cs, from the
Airflow Correction Factors table. (Interpolation may be
required.)
Ct = .9625
Cs = .96
Select the elevation correction factors, Et and Es, from
the Elevation Correction Factors table. (No correction
necessary in this example, unit is at sea level.)
Et = 1.00
Es = 1.00
III Calculate actual performance.
TC = TCb x Ct x Et
= 42.0 x .9625 x 1.00
= 40.42 MBtuh
SC = SCb x Cs x Es
= 34.2 x .96 x 1.00
= 32.83 MBtuh
a) Calculate water pressure drop (or refer to the Water
Pressure Drop for Cv Factor and Water Flow Rate
table on page 33). From the Cv Factor by Coil and
Unit Size table on page 32, find the Cv value for
unit size 16 with four rows.
Cv = 7.2
P = [GPM/(0.658 x Cv)]2
= [7.0/(0.658 x 7.2)]2
= 2.18 feet of H
b) For selections other than those listed here, please
contact the factory.
IV Determine motor.
To determine motor and drive selection requirements
and obtain the cfm for a specific application, the
total static pressure (TSP) for that application must be
determined.
The TSP is the sum of the internal static pressure
(ISP) and the external static pressure (ESP) measured in
inches of water column. Internal static pressure is the
sum of the static resistance of the unit’s components
— the cabinet, coil and filter. The ESP is the static
resistance of the unit’s external components, including,
but not limited to, ductwork, grilles and additional
filtration. For non-ducted applications, the ESP is
0 in. wg.
After the TSP has been calculated (see the following
example), use the motor horsepower table on pages 30
and 31 to determine actual horsepower (hp) for the belt
drive unit. Horsepower offerings are limited to
1
/2, 3/4, 1, 11/2, 2, 3 and 5.
The standard selection is the nearest offering above
the actual hp shown in the table.
Using the TSP of the table, match the unit size with
the cfm row to determine the correct motor for the
specific application. Drive sheaves and the required
belt assembly will be provided to meet specific design
requirements. Drive sheaves are set at the factory.
Calculate the hp and drive selection required to deliver 1500 cfm on a 42BHC16 unit equipped with a
4-row hydronic cooling coil and a 2-in. pleated filter in
a ducted application at .38 in. ESP, including duct and
grille losses.
Using the Component Static Resistance table on
page 32, the ISP is calculated as follows:
Cabinet.09-in. wg
4-row Wet Coil.30-in. wg
2-in. Pleated Filter.12-in. wg
ISP.51-in. wg
ESP.38-in. wg
TSP.89-in. wg
O
2
1
/4, 1/3,
22
Performance data
42BHC,BVC AIRFLOW CORRECTION FACTORS
CFM RATIO
(Actual/Base)
1.401.251.26
1.351.221.23
1.301.191.20
1.251.161.17
1.201.131.14
1.151.101.11
1.101.071.08
1.051.041.04
1.001.001.00
0.950.970.97
0.900.940.93
0.850.900.89
0.800.860.85
0.750.820.81
0.700.780.77
0.650.740.72
0.600.700.67
0.550.660.62
0.500.620.57
0.450.580.52
0.400.530.47
0.350.480.42
0.300.430.38
0.250.380.33
NOTE: Use Sensible Heat correction factors when calculating heating
capacity.
TOTAL (Ct)SENSIBLE (Cs)
DIRECT EXPANSION (DX) CORRECTION FACTORS
%OF
NOMINAL CFM
800.950.93
900.970.96
1001.001.00
1101.021.04
1201.051.08
Consult factory for values outside of table.
DX Total Capacity (MBtuh) = Base Et x Total Correction Factor
DX Sensible Capacity (MBtuh) = Base Es x Sensible Correction Factor
% of Nominal Cfm = Actual Cfm (from Fan Performance table)
÷ Nominal Cfm
1. Leaving air temperature not to exceed 104 F with standard motor.
2. Base capacity ratings based on 180 F entering water temperature
and 70 F entering air temperature.
3. Hot Water Heating Capacity (MBtuh) =Rated Heating Capacity xHot Water Capacity Correction Factor x Sensible Airflow Correction Factor.
100110120130140150160170180190200
ENTERING WATER TEMPERATURE (F)
23
Performance data (cont)
42BHC, BVC NOMINAL COOLING CAPACITIES
UNIT SIZE
42BHC,BVC
06600
08800
101000
121200
16
202000
303000
404000
EWT— Entering Water Temperature
MBtuh — Capacity (Btuh in thousands)
*Based on entering air temperature of 67 F wb, 80 F db and temperature rise of 10
degrees F.
NOTE: All ratings at sea level. Ratings in accordance with ARI (Air Conditioning &
Refrigeration Institute).
NOMINAL
LEGEND
CFM
1600
COIL
ROWS
4
6
8
4
6
8
4
6
8
4
6
8
4
6
8
4
6
8
4
6
8
4
6
8
EWT
(F)
4023.316.0
4517.913.8
5012.812.0
4031.019.8
4524.517.0
5018.014.5
4033.821.2
4526.718.1
5019.415.2
4028.420.0
4521.917.5
5015.315.3
4038.425.1
4530.321.7
5022.518.6
4042.627.2
4533.723.3
5024.719.8
4040.527.3
4531.623.7
5023.420.6
4052.233.3
4541.728.7
5031.224.5
4057.736.0
4546.431.0
5034.626.2
4045.431.2
4535.527.2
5026.523.8
4059.638.4
4547.433.2
5035.528.5
4066.642.0
4553.336.1
5039.930.7
4059.741.2
4546.435.9
5034.431.4
4078.750.9
4562.644.1
5046.837.8
4089.056.0
4571.348.3
5053.341.0
4075.251.6
4559.045.1
5044.139.5
4099.063.8
4578.755.2
5059.047.4
40111.870.3
4589.960.6
5067.651.6
40112.577.6
4587.667.6
5065.059.1
40148.595.8
45117.882.8
5088.171.1
40168.0105.5
45135.091.0
50101.277.4
40157.7106.7
45123.692.9
5092.681.1
40204.0130.5
45162.6112.7
50122.396.7
40230.1143.5
45185.6123.8
50140.2105.2
COOLING*
Tot al
Capacity
(MBtuh)
Sensible
Capacity
(MBtuh)
42BHC,BVC NOMINAL HEATING CAPACITIES
UNIT SIZE
42BHC,BVC
06600
08800
101000
121200
161600
202000
303000
404000
NOTES:
1. Ratings are based on 180 F Entering Water Temperature (EWT) and 70 F
Entering Air Temperature (EAT ) .
2. Leaving-air temperature is not to exceed 104 F with the standard motor.
Consult the factory for higher temperature motor applications.
3. For information on four and six-row heating coil capacities and applications,
consult the factory.
4. For all application ratings, use the quick-selection ratings provided in this
catalog, or contact the factory.
NOMINAL CFMROWS
127.0
246.9
127.0
246.9
127.0
246.9
138.5
268.5
148.0
287.7
158.7
2104.9
178.0
2149.2
192.3
2182.4
HEATING CAPACITY
(MBtuh)
24
UNIT
SIZE
GPM
42BHC,BVC
06
08
10
12
16
20
30
40
DB— Dry Bulb Temperature
EWT — Entering Water Temperature
MBtuh — Btuh in Thousands
SCb— Base Sensible Capacity at Nominal Cfm
TCb— Base Total Capacity at Nominal Cfm
WB— Wet Bulb Temperature∆T—Change in Water Temperature (F)
LEGENDNOTE: All capacities are given in thousands of Btuh (MBtuh).
40 F EWT45 F EWT50 F EWT40 F EWT45 F EWT50 F EWT40 F EWT45 F EWT50 F EWT
DB— Dry Bulb Temperature
EWT — Entering Water Temperature
MBtuh — Btuh in Thousands
SCb— Base Sensible Capacity at Nominal Cfm
TCb— Base Total Capacity at Nominal Cfm
WB— Wet Bulb Temperature∆T—Change in Water Temperature (F)
LEGENDNOTE: All capacities are given in thousands of Btuh (MBtuh).
40 F EWT45 F EWT50 F EWT40 F EWT45 F EWT50 F EWT40 F EWT45 F EWT50 F EWT
DB— Dr y Bulb Temperature
EWT — Entering Water Temperature
MBtuh — Btuh in Thousands
SCb— Base Sensible Capacity at Nominal Cfm
TCb— Base Total Capacity at Nominal Cfm
WB— Wet Bulb Temperature∆T—Change in Water Temperature (F)
42BHC,BVC
DB— Dry Bulb Temperature
EWT — Entering Water Temperature
MBtuh — Btuh in Thousands
SCb— Base Sensible Capacity at Nominal Cfm
TCb— Base Total Capacity at Nominal Cfm
WB— Wet Bulb Temperature∆T—Change in Water Temperature (F)
LEGENDNOTE: All capacities are given in thousands of Btuh (MBtuh).
UNIT
SIZE
06
08
10
12
16
20
30
40
LEGENDNOTE: All capacities are given in thousands of Btuh (MBtuh).
40 F EWT45 F EWT50 F EWT40 F EWT45 F EWT50 F EWT40 F EWT45 F EWT50 F EWT
DB— Dr y Bulb TemperatureTCb— Base Total Capacity at Nominal Cfm
EWT — Entering Water TemperatureWB — Wet Bulb Temperature
MBtuh — Btuh in Thousands∆T—Change in Water Temperature (F)
SCb— Base Sensible Capacity at Nominal Cfm
40 F EWT45 F EWT50 F EWT40 F EWT45 F EWT50 F EWT40 F EWT45 F EWT50 F EWT
LEGENDNOTE: All capacities are given in thousands of Btuh (MBtuh).
b
42BHC, BVC 8-ROW COOLING CAPACITY (by ∆T)
UNIT
SIZE
42BHC,BVC
06
08
10
12
16
20
30
40
DB— Dr y Bulb TemperatureTCb— Base Total Capacity at Nominal Cfm
EWT — Entering Water TemperatureWB — Wet Bulb Temperature
MBtuh — Btuh in Thousands∆T—Change in Water Temperature (F)
SCb— Base Sensible Capacity at Nominal Cfm
NOTE: All capacities are given in thousands of Btuh (MBtuh).
40 F EWT45 F E WT50 F EWT40 F EWT45 F EWT50 F EWT40 F EWT45 F EWT50 F EWT
1. Contact factory if higher horsepower selection is required for a
given cfm and total static pressure.
2. The variable pitch motor sheave provided will allow +
adjustment. Unit sizes 06, 08, 10 and 12 have
sheaves. Unit sizes 16, 20, 30 and 40 have 1-in. bore fan sheaves.
3. Consult factory for motor selections when outlet air temperature
exceeds 104 F on hot water coil applications.
4. Single-phase motors are only available to 2 hp. Three-phase
motors are available from
1. Contact factory if higher horsepower selection is required for a
given cfm and total static pressure.
2. The variable pitch motor sheave provided will allow +
adjustment. Unit sizes 06, 08, 10 and 12 have
sheaves. Unit sizes 16, 20, 30 and 40 have 1-in. bore fan sheaves.
15% rpm
3
/4in. bore fan
3. Consult factory for motor selections when outlet air temperature
exceeds 104 F on hot water coil applications.
4. Single-phase motors are only available to 2 hp. Three-phase
motors are available from
Hydronic coil pressure drop — All of the factory’s hydronic coils have a coefficient of velocity (Cv) resistance
factor assigned to assist in a more accurate determination
of water pressure drop (see Cv Factor by Coil and Unit Size
table below).
Calculating pressure drop:
The Cv factor is equal to the flow rate of water in gpm
through a piping component when the pressure drop
through the component is 1.0 pounds per square inch
(psi), or 2.31 ft wg.
∆P (ft wg) = ∆P (psi) x 2.31
Use the Cv factor from the Cv Factor by Coil and Unit
Size table to determine the water coil pressure drop.
32
Coil pressure drop (ft wg):
2
∆P = (GPM
/Cv
2
) x 2.31
or
∆P = [GPM/(0.658 x Cv)]
2
or
Refer to the Water Pressure Drop for Cv Factor and
1. Motor Full Load Amps refer to National Electric Code (NEC)
Amps; actual motor nameplate amps may vary.
2. NEC data extrapolated for 277 v.
3. Motors are open drip proof, ball bearing, single speed, 1750 rpm
rated at continuous duty, 140 F ambient with reversible rotation.
1
1
/
/
4
3
Nominal HP
1
3
/
/4111/2235
2
Service Switches:
The service switch is an On/Off switch on incoming power
supply to unit. Proper amperage load must be determined
before switch can be selected. The range of the fused or
non-fused service switch is 0 to 40 amps.
The UL listing signifies that Carrier’s fan coil units have been examined
by UL and comply with the organization’s applicable standards of U.S.
and Canadian national product safety standard, UL 1995/CSA C22.2
No. 236.
37
Controls
Standard control features
• 4 in. x 4 in. junction box
NOTE: Motor leads are wired to the 4 in. x 4 in. junction
box, mounted on the external panel. Field verification of
the motor rotation is required on 3-phase applications.
Motor control options
• Interlocking disconnect switch*
• 24-v class 2 transformer (40 va)†
• 8-pole control terminal strip
• Motor power fusing*
• Motor control contactor**
Motor and electric heat control options
NOTE: Electric heat option requires same voltage as motor
and must include the control option. These control features
are standard with electric heat options and control option.
• Interlocking disconnect switch*
• Heater power fusing*
• 24-v class 2 transformer (40 va)†
• 8-pole control terminal strip
• Auto reset temperature limit switch
• Manual reset backup temperature limit switch
• 80/20 heater element wire
• Motor power fusing*
• Motor control contactor**
• Agency listed for 0-in. clearance
Electric heat options:
• Single-phase, 1 or 2 stage heat
• Three-phase, 1, 2 or 3 stage heat
*Complies with NEC’s requirement, Article 430 for dis-
connect, branch circuit protection motor controller and
motor overload protection.
†No control fusing necessary.
**Complies with NEC’s requirement for a motor starter
with internal heating elements when used with the
factory’s standard motors with integral thermal overload
protection.
38
Guide specifications
System Fan Coil Unit
HVAC Guide Specifications — 42B
Size Range: 600 to 4000 Nominal Cfm
Carrier Model Number:
42BHC (Horizontal Fan Coil Unit)
42BVC (Vertical Fan Coil Unit)
Part 1 — General
1.01 SYSTEM DESCRIPTION
Horizontal and vertical, 2-pipe or 4-pipe, belt-
driven, galvanized casing model fan coil unit for
ducted installation above the ceiling or within
floor mounted cabinet, with full access to internal
components.
1.02 QUALITY ASSURANCE
A. Unit performance shall be rated in accordance with
ARI Standard 440-2005.
B. Unit construction shall comply with ASHRAE (latest
edition) Safety Code and NEC.
C. Unit shall be constructed in accordance with ETL
and ETL, Canada standards. Factory-installed
motors and electric heaters shall be UL approved.
D. Each coil shall be factory tested for leakage
at 350-psig air pressure with coil submerged
in water. Insulation and adhesive shall meet
NFPA-90A requirements for flame spread and
smoke generation.
E. Each coil shall be factory tested for leakage at
350 psig air pressure with coil submerged in water.
Insulation and adhesive shall meet NFPA-90A
requirements for flame spread and smoke generation. Factory-installed motors shall be UL approved.
1.03 DELIVERY, STORAGE AND HANDLING
Unit shall be handled and stored in accordance with
the manufacturer’s instructions.
Part 2 — Products
2.01 EQUIPMENT
A. General:
Factory-assembled, horizontal and vertical, drawthru type fan coil unit for ducted installation above
the ceiling or floor mounting. Unit shall be complete
with water coils, fan(s), motor, belt drive, drain pan,
and filter.
B. Casing:
Construction shall be heavy-gage galvanized steel,
lined with one-in. thick fiberglass Tuf-Skin™ II
thermal/acoustical insulation. Knockouts shall be
provided for hanging the horizontal unit, that will
accept
of all unit corners. Supply and return duct connection shall be 1 in. long. Removable side panels shall
be provided for access to the fan/motor assembly. A
double-sloped drain pan shall be constructed of
stainless steel, extending under the full length and
width of the coil(s) with a
thread stainless steel drain connection and
3
/8-in. threaded rod at the top, and bottom
3
/4-in. male nominal pipe
1
/2-in.
male MPT stainless secondary drain connection
(capped when not required). The outside surface of
the drain pan shall be insulated with
1
/8-in. closed
cell insulation.
C. Fans:
Belt-driven, double-width fan wheels shall have
forward-curved blades and be statically and dynamically balanced. Fan drive shall consist of variablepitch motor pulley, fixed-pitch fan pulley and V-belt.
Fans and scrolls shall be of galvanized steel.
D. Coils:
Standard unit shall be equipped with a 4-row coil for
installation in a 2-pipe system and additional rows of
coil shall be provided for installation in a 4-pipe system as described in the Options and Accessories
section. Coils shall have
1
/2-in. copper tubes, aluminum fins bonded to the tubes by mechanical expansion and have a working pressure of 250 psig at
200 F. Each coil shall have a manual air vent and
sweat connections for copper tubes.
E. Operating Characteristics:
A single-circuit coil unit installed in a 2-pipe system
shall be capable of providing heating or cooling as
determined by the operating mode of the central
water supply system. A double-circuit coil unit
installed in a 4-pipe system shall be capable of providing sequenced heating and cooling.
F. Mot o r( s ):
Fan motors shall be open, drip-proof, single-speed,
60 Hz, 1750 rpm 1 or 3 phase, suitable for continuous duty at 104 F (40 C). Single phase motors are
capacitor start, include automatic reset thermal
overload protection and are available in 115, 208,
230, or 277 volts (60 Hz). Three-phase motors are
available in 208, 230, or 460 volts (60 Hz). Motors
are resilient base mounted (except 3 and 5 hp
motors, which are rigid base mounted).
G. Options and Accessories:
1. Factory-Installed Options:
a. Coils:
1) Unit coil(s) shall be equipped with automatic air vent(s).
2) Unit shall be equipped with a highcapacity 6-row or 8-row coil for installation in a 2-pipe system.
3) For installation in a 4-pipe system, unit
shall be equipped with either a 4-row
cooling/1-row hot water heating splitcircuit coil, or a 4/2, 6/1, or 6/2 splitcircuit coil as required.
4) Unit shall be equipped with either a 4row DX (direct expansion) cooling coil
or a 6-row DX cooling coil as required.
5) Unit coil(s) shall be copper fin, copper
tube with stainless steel tube and sheets.
b. Filters:
1) A two-in. pleated filter shall be installed
in the unit (standard).
39
Guide specifications (cont)
2) One-in. pleated, (2) 1-in. throwaway or
2-in pleated MERV 11 filters with 2-in.
pre-filter shall be installed as indicated
on the equipment schedule.
c. Insulation:
1) Units shall be equipped with 1-in. thick
Tuf-Skin™ II insulation (standard).
2) Units are available with ¾-in. closed
cell, 1-in. Tuf-Skin Rx™ edge sealed,
or 1-in. foil-faced insulation.
d. Controls:
1) Unit shall be equipped with 24-v transformer, motor contactor and terminal
strip for connection to field or factory
provided controller.
2) Unit shall be equipped with interlocking door-disconnect switch, touch-type
fusing, 24-v transformer, motor contactor and terminal strip for connection to field provided controller.
3) Unit shall be equipped with interlocking door-disconnect switch, separate
motor and electric heater touch-type
fusing, 24-v transformer, motor contactor and terminal strip for connection to field-provided or factoryprovided controller.
e. Motor(s):
Single-phase motors are capacitor start and
shall include automatic reset thermal overload protection and shall be available in
115, 208, 230, or 277 volts (60 Hz).
Three-phase motors shall be available in
208, 230, or 460 volts (60 Hz).
f. Electric Heat:
1) Electric heaters shall be constructed of
high-grade resistance wire supported
by ceramic insulators on plated steel
brackets. The heat elements shall be
suspended in front of the outlet, after
the blower and coil. High-limit thermal
cutouts shall protect the heat elements
in the event of an air failure.
2) Single-phase heaters shall be available
in 115, 208, 230, or 277 volts (60
Hz). Three-phase electric heat shall be
available in 208, 230, or 460 volts (60
Hz).
2. Field-Installed Accessories:
a. Mixing Boxes:
1) Mixing boxes shall be preassembled at
the factory and shipped separately with
base rails.
2) Mixing boxes shall include
a linkage kit, which consists of two
crank arms, 2 swivels and a rod, 25 in.
long (for unit sizes 06-16) or 84 in.
long (for unit sizes 20-40), for the field
installation of the actuator.
b. Thermostats:
Three thermostats shall be available for
field installation:
1) The single stage heat thermostat shall
feature manual changeover, off-coolheat system switch, on-auto fan mode
switch, single-stage electric heat, and
outside air signal.
2) The 2-stage heat thermostat shall feature automatic/manual changeover,
digital display of temperatures and all
functions, off-cool-heat-auto system
mode buttons, single speed fan operation, on-auto fan mode button, single
or two stage electric heat signal, outside air signal and optional remote
temperature sensor.
3) The single-stage heat, 2-pipe heat/
cool thermostat shall feature digital
display of ambient temperature and
operating mode, single fan speed operation, power and operating mode buttons, continuous fan operation, cycling
water control valve, 4-pipe automatic
changeover/manual changeover with
“on-auto” fan mode button, optional
one or 2-stage electric heat signal, and
purge cycle, temperature sensor for
2-pipe cold water/hot water systems,
and programmable operating range,
dead band, digital display, temperature set-back.
c. Valve Packages:
1) Valve packages shall be factoryassembled for field installation.
2) Basic valve packages shall include
2-way or 3-way valves with balancing
valves and 2 ball valves.
3) Deluxe valve packages shall include a
circuit setting and a strainer in addition
to the features included in the basic
valve package.
Book 3
Ta b 7 a
Carrier Corporation • Syracuse, New York 132219-05A9-05
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 4
NewPg 40Catalog No. 524-236Printed in U.S.A.Form 42B-1PD
Ta b 4 FC 4
Replaces: 42BHC-1PD
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.