Carrier’s versatile belted fan coil units
satisfy design requirements:
• A selection of 8 sizes covers
nominal capacities from 600 to
4000 cfm
• Choice of motors, from
eliminates oversizing
• Wide range of coil options for 2-pipe
or 4-pipe systems
• Optional DX (direct expansion) coils
with expansion valve and distributor
• Single and three-phase electric
heat (1.0 to 39.9 kW)
1
/4 to 5 hp,
42BHE UNIT
Features/Benefits
The 42BHE, BVE belt drive
fan coil units provide yearround comfort air
conditioning with central
station operating economy.
A variety of coil options
reduces first cost
Four, 6 or 8-row cooling coils combine
needed capacities with the most efficient heat transfer surface. For
4-pipe systems, select from two splitcoil options. Standard coils consist of
aluminum fins securely bonded to
1
/2-in. OD seamless copper tubes.
Each fin’s aluminum collar ensures accurate control of the fin spacing, while
completely covering the tubes to
lengthen coil life. All coils also feature
manual air vents, with optional automatic air vents available. Special coils
are also available with stainless steel
end sheets and bottom coil baffles. For
custom applications, special coils are
available with lower pressure drops.
Fan wheels are designed to
provide low operating costs
The forward-curved, centrifugal,
double-inlet fans are statically and
dynamically balanced at the factory to
minimize transmission of vibration
to the building structure.
In addition, the blower is isolated
from the cabinet by rubber isolators,
and the blower is isolated from the duct
connections by foam.
All motors (single and three phase)
are UL (Underwriters Laboratories) listed or equivalent, factory wired, single
speed with thermal overload protection and are continuous duty rated.
Motors are supplied with permanently
lubricated bearings, class-B insulation
and are open drip-proof. The motor
mount has an adjustable platform for
easy belt adjustment. The motor is resilient mounted (up to 2 hp) or rigid
base mounted (3 to 5 hp) for vibration
free installation. Drives are pre-set at
the factory for the specific airflow at
static pressures as ordered. An adjustable pitch pulley allows cfm balancing
to meet system requirements.
connections for ducts is recommended.
One-in. duct collars on discharge and
on return are furnished standard. These
integral duct collars cut installation time
and labor expense.
Durable construction means
easy-to-maintain units
The 42BHE,BVE fan coil casings are
fabricated from heavy-gage galvanized
G90 steel, reinforced for maximum
rigidity and structural strength. Optional one-inch double wall construction,
perforated or solid lined, is also available. Removable side panels with toolless camlock fasteners allow easy access for servicing interior components.
One-inch matte surface, fiberglass
thermal/acoustical insulation lines the
fan coil cabinets to prevent sweating
and to muffle sound transmission. Premium anti-microbial fiberglass, foil
faced, and closed cell insulations are
also available to address IAQ (indoor
air quality) concerns.
The stainless steel, double-sloped
condensate drain pan is removable for
ease of cleaning, and all models include primary and secondary drain
connections to provide back up in case
the main connection is plugged.
Slide-in return-duct collar filter
makes it possible to remove and replace the filter without disturbing
return air ductwork. A standard 2 in.
and optional 4 in. filter rack allow different filter types, thickness, and efficiency to address IAQ requirements.
Complete factory assembly
minimizes on-the-jobsite costs
and problems
Compact, lightweight units are designed
for easy mounting. For horizontal units,
knockouts designed to accept
threaded rods are provided on the top
and bottom of each corner of the unit.
External vibration isolation and flex
2
3
/8-in.
42B HE 06 B C3 R6 07 05 B E
42B — AirStream System Fan Coil Unit
Product Type
HE — Horizontal Unit
VE — Vertical Unit
Filters
E — 2 in. Pleated Filter
F — 1 in. Pleated Filter
G — 1 in. Throwaway Filter (Qty 2)
H — 2 in. MERV 11 with 2 in. Pleated Pre-Filter
1 — 4/2 DX/HW Same End
2 — 6 Row DX
4 — 6/1 DX/HW Same End
6 — 6/2 DX/HW Same End
7 — 4 Row DX
B — 4 Row (Std)
H — 4/1 Same End
K — 4/2 Same End
L — 6 Row
N — 6/1 Same End
Q — 6/2 Same End
R — 8 Row
X — 4/1 DX/HW Same End
Tot al Static Pressure*
Actual CFM
†
Arrangement
**
L6 — Left Hand with 1 in. Tuf-Skin Insulation
L8 — Left Hand with 1 in. Foil Face Insulation
L9 — Left Hand with
1 in. Closed Cell Insulation
R6 — Right Hand with 1 in. Tuf-Skin Insulation
R8 — Right Hand with 1 in. Foil Face Insulation
R9 — Right Hand with 1 in. Closed Cell Insulation
L1 — Left Hand with 1 in. Double Wall Tuf-Skin Insulation
and Solid Inner Liner
L2 — Left Hand with 1 in. Double Wall Tuf-Skin Insulation
and Perforated Inner Liner
L3 — Left Hand with 1 in. Double Wall Closed Cell
Insulation and Solid Inner Liner
L4 — Left Hand with 1 in. Double Wall Closed Cell
Insulation and Perforated Inner Liner
R1 — Right Hand with 1 in. Double Wall Tuf-Skin Insulation
and
Solid Inner Liner
R2 — Right Hand with 1 in. Double Wall Tuf-Skin Insulation
and Perforated Inner Liner
R3 — Right Hand with 1 in. Double Wall Closed Cell
Insulation and Solid Inner Liner
R4 — Right Hand with 1 in. Double Wall Closed Cell
Insulation and Perforated Inner Liner
LEGEND
*To be determined by Carrier sales engineer.
Example: 05=0.5 in. wg
†To be determined by Carrier sales engineer.
Example: 07=700 actual CFM
**For epoxy-coated insulation option, submit
ETO (Engineer to Order) request.
††Data for 50 Hz motors can be found in Fan Coil Builder software
program.
DX — Direct Expansion
HW — Hot Water
a42-4365
Model number nomenclature
3
Physical data
UNIT SIZE 42BHE, BVE0608101216203040
NOMINAL CFM600800100012001600200030004000
42BHE OPERATING WT (lb)
(no heat/ with heat)
42BVE OPERATING WT (lb)
(no heat/ with heat)
FILTERS (2 in. pleated)
Number...Size (in.)1...161/2 x 24 1...161/2 x 24 1...181/4 x 33 1...181/4 x 33 2...181/4 x 211/22...203/4 x 22 2...29 x 22 2...29 x 29
Face Area (sq ft)2.82.84.24.25.56.38.911.7
HYDRONIC COILS
Size (in.)15 x 2015 x 2015 x 2915 x 2915 x 3918 x 4027 x 4027 x 54
Face Area (sq ft)2.12.13.03.04.14.97.710.3
Fins per inch
Coil Water Volume (approx. gal. per
row of coil)
FANS
Qty...Size (in.)1...9 x 41...9 x 61...10 x 41...10 x 71...11 x 101...12 x 91...12 x 12 1...15 x 12
HYDRONIC COIL CONN. (in.)
8 Row (Cooling)1 nominal, 1.125 OD11/2 nominal, 1.625 OD
4 and 6 Row (Cooling) 3/4 nominal, 0.875 OD1 nominal, 1.125 OD11/2 nominal, 1.625 OD
1 Row (Heating)
/2 nominal, 0.625 OD1 nominal, 1.125 OD11/2 nominal, 1.625 OD
3
/4 nominal, 0.875 OD1 nominal, 1.125 OD11/2 nominal, 1.625 OD
/2 nominal, 0.625 OD11/2 nominal, 1.625 OD
1
/4 nominal, 0.375 OD
3
/4 MPT
1
/2 nominal, 0.625 OD
4
Options and accessories
42BHE, BVE OPTIONS AND ACCESSORIES
ITEMOPTION*ACCESSORY†
Automatic Air VentsX
ControlsX
Electric HeatX
FiltersX
Heating/Cooling CoilsX
InsulationX
Mixing BoxesX
MotorsX
Double Wall Cabinet
Construction
Seismic Structural Upgrade
(not available with double
wall)
Condensate Overflow SwitchX
Motor ControlsX
Disconnect SwitchX
*Factory-installed option.
†Field-installed accessory.
X
X
The 42BHE and 42BVE fan coil units are designed to
offer maximum flexibility in an application, accessibility for
service, quiet operation and durability.
Factory-installed options
Automatic air vents — Automatic air vents have fiber
washers, which allow air in the pipes to pass through,
automatically bleeding the system. The fiber washers eliminate the need to manually remove air from the system.
When wet, washers swell and seal the system.
Coils — Coils are available in a choice of two-pipe system
with 4-row cooling/heating or four-pipe system with 4, 6
or 8-row cooling and 1 or 2 row heating. Reheat operation
is standard. Preheat is available as an option for hydronic
coil. For DX/HW (hot water) coils, preheat position is
standard. Steam coils are available with a factory special
quote.
Controls — Factory-installed optional controls include
an interlocking disconnect switch, heater power fusing,
24-v Class 2 transformer (40-va), 8-pole control terminal
strip, auto reset temperature limit switch, airflow safety
switch, motor power fusing, motor control contactor, and a
24-v condensate overflow switch.
Electric heat — Total electric heat eliminates the requirement for a boiler. Heating and/or cooling may be available
on an individual basis throughout the year. Resistance
electric heat is available from 1.0 kW to 39.9 kW (refer to
electric heater data table for availability per unit) with
single-stage or multiple-stage, single power source.
Voltages:
• 115-v, 208-v, 230-v and 277-v single-phase 60 Hz
• 208-v, 230-v and 480-v three-phase 60 Hz
• 220-v single-phase 50 Hz
• 380-v three-phase 50 Hz
Electric heat is available with the following staging options
(3-phase staging is balanced).
• 1 to 12 kW 1 stage only — single phase
• 3 to 12 kW 1 or 2 stage only — single phase
• 1 to 39.9 kW 1 stage only — 3 phase
• 4 to 39.9 kW 1 or 2 stage only — 3 phase
• 12 to 39.9 kW 1, 2, or 3 stage — 3 phase
Heater coils are constructed of high-grade resistance
wire that is supported by ceramic insulators on plated steel
brackets. These heat elements are suspended directly in
front of the outlet after the blower and the coil. An auto
and manual thermal limit switch protect the heater in the
event of air failure.
Filters — Two-in. pleated filters are standard. One-in.
pleated, two 1-in. throwaway, or 2-in. MERV (minimum
efficiency reporting value) 11 filters with 2-in. pleated
pre-filter are available. The 2-in. MERV 11 filters with 2-in.
pleated pre-filter include a filter rack.
Insulation — Tuf-Skin™ II (1-in. thick) insulation is
standard. Also available is 1-in. closed cell, 1-in. epoxy
coated fiberglass edge sealed, or 1-in. foil-faced insulation.
Motors — A wide selection of standard motors provides
efficient operation in ducted applications with excellent
performance with up to 2.5 in. of total static pressure. All
standard motors contain internal thermal overload protection. The overload automatically resets when the temperature returns to a safe limit. These thermal overloads, when
coupled with the motor contactor, replace the need for a
motor starter. Available motor options include:
• 115-v, 208-v, 230-v and 277-v single-phase 60 Hz
• 208-v, 230-v and 460-v three-phase 60 Hz
• 220-v single-phase 50 Hz
• 380-v three-phase 50 Hz
• Open drip-proof motors
• External junction box
Field-installed accessories
Mixing boxes — Mixing boxes can be used when outside
air is required for ventilation. Pre-assembled at the factory
and shipped separately with base rails for field installation,
mixing boxes include a linkage kit consisting of two crankarms, 2 swivels and either a 25 in. long (for sizes 06-16) or
a 34 in. long (for sizes 20-40)
tion of an actuator.
5
/16 in. rod for field installa-
5
42BHE FAN COIL BASE UNIT (NO CONTROLS)
NOTES:
1. All dimensions are in inches (±
1
/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to
change without notice.
3. Right hand shown, left hand opposite.
4. Hanger rods, which are field-supplied, are shown for reference only.
5. Control box size and position may vary.
6. "C" dimension is measured from coil side of the unit.
UNIT
42BHE
DIMENSIONS (in.)
Fan SizeDepthWidthHeight
Supply DuctReturn DuctMounting Holes
AB CDEF J K
069 x 4362819
3
/
4
71/
8
101/
2
141/
2
21/424161/
2
271/
4
351/
4
089 x 63628193/
4
81/
2
101/
2
137/
8
21/424161/
2
271/
4
351/
4
1010 x 4371/
2
37211/
2
71/
8
115/
8
151/
4
21/433181/
4
361/
4
37
1210 x 737
1
/
2
37211/
2
10115/
8
137/
8
21/433181/
4
361/
4
37
1611 x 1037
3
/
4
47211/
2
133/
8
123/
4
163/
4
21/443181/
4
461/
4
37
2012 x 940
1
/
4
4824121/
2
133/
4
173/
4
21/444203/
4
471/
4
391/
2
3012 x 12401/
4
48321/
4
157/
8
133/
4
1671/44429471/
4
391/
2
4015 x 12431/
2
62321/
4
161/
2
161/
8
223/
4
61/45829613/
4
421/
2
A42-659EF
Base unit dimensions
WIDTH
E
K
J
TOP VIEW
A
D
B
FRONT VIEW2-1/16
C
2
FILTER RACK WITH
TOOLLESS ACCESS
FROM SIDES AND
BOTTOM
DEPTH
SEE DETAIL 1
4 X 4 JBOX AND
MOTOR MOUNTED
SAME SIDE AS COIL
CONNECTIONS
HANGER ROD
KNOCKOUT Ø5/8
1" SUPPLY
AIR COLLAR
SUPPLY AIR
TYP 4 PLCS
SCALE 0.250
1-3/8
HEIGHT
COIL DRAIN CONN.
[MALE 3/4-14 NPT]
[FEMALE 1/2-14 NPT
SECONDARY]
1/2
DETAIL 1
SIDE VIEW
1/2
BOTH SIDE PANELS WITH
TOOLLESS CAMLOCK ACCESS
4-3/8
ADD 2" FOR MERV11 FILTER
COIL RETURN CONN.
F
RETURN AIR
COIL SUPPLY CONN.
1
1" RETURN
AIR COLLAR
6
B
D
FRONT VIEW
A
C
TOP VIEW
J
18
DOOR
OPEN
DEPTH
SEE DETAIL 1
MOTOR CONTROLS AND MOTOR
MOUNTED SAME SIDE AS
COIL CONNECTIONS
8-11/16
2
FILTER RACK WITH
TOOLLESS ACCESS
FROM SIDES
AND BOTTOM
E
WIDTH
K
HANGER ROD
KNOCKOUT Ø5/8
TYP 4 PLCS
1/2
1/2
DETAIL 1
SCALE 0.250
1-3/8
1" SUPPLY
AIR COLLAR
HEIGHT
SUPPLY AIR
COIL DRAIN CONN.
[1MALE 3/4-14 NPT]
[FEMALE 1/2-14 NPT SECONDARY]
SIDE VIEW
1
1" RETURN
AIR COLLAR
COIL SUPPLY CONN.
F
COIL RETURN CONN.
RETURN AIR
BOTH SIDE PANELS WITH
TOOLLESS CAMLOCK ACCESS
4-3/8
ADD 2" FOR MERV11 FILTER
42BHE FAN COIL WITH MOTOR CONTROL OPTION
NOTES:
1. All dimensions are in inches (±
1
/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to
change without notice.
3. Right hand shown, left hand opposite.
4. Hanger rods, which are field-supplied, are shown for reference only.
5. Control box size and position may vary.
6. "C" dimension is measured from coil side of the unit.
UNIT
42BHE
DIMENSIONS (in.)
Fan SizeDepthWidthHeight
Supply DuctReturn DuctMounting Holes
AB CDEF J K
069 x 4362819
3
/
4
71/
8
101/
2
141/
2
21/
4
24161/
2
271/
4
351/
4
089 x 63628193/
4
81/
2
101/
2
137/
8
21/
4
24161/
2
271/
4
351/
4
1010 x 4371/
2
37211/
2
71/
8
115/
8
151/
4
21/
4
33181/
4
361/
4
37
1210 x 737
1
/
2
37211/
2
10115/
8
137/
8
21/
4
33181/
4
361/
4
37
1611 x 1037
3
/
4
47211/
2
133/
8
123/
4
163/
4
21/
4
43181/
4
461/
4
37
2012 x 940
1
/
4
4824121/
2
133/
4
173/
4
21/
4
44203/
4
471/
4
391/
2
3012 x 12401/
4
48321/
4
157/
8
133/
4
1671/
4
4429471/
4
391/
2
4015 x 12431/
2
62321/
4
163/
8
161/
8
223/
4
61/
4
5829613/
4
421/
2
a42-4241
7
42BHE FAN COIL WITH ELECTRIC HEAT OPTION
NOTES:
1. All dimensions are in inches (±
1
/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to
change without notice.
3. Right hand shown, left hand opposite.
4. Hanger rods, which are field-supplied, are shown for reference only.
5. "C" dimension is measured from coil side of the unit.
UNIT
42BHE
DIMENSIONS (in.)
Fan SizeDepthWidthHeight
Supply DuctReturn DuctMounting Holes
AB CDEF J K
069 x 4362819
3
/
4
87/
8
101/
2
141/
2
21/424161/
2
271/
4
351/
4
089 x 63628193/
4
87/
8
101/
2
137/
8
21/424161/
2
271/
4
351/
4
1010 x 4371/
2
37211/
2
103/8115/
8
151/
4
21/433181/
4
361/
4
37
1210 x 737
1
/
2
37211/
2
103/
8
115/
8
137/
8
21/433181/
4
361/
4
37
1611 x 1037
3
/
4
47211/
2
137/
8
123/
4
163/
4
21/433181/
4
461/
4
37
2012 x 940
1
/
4
482413133/
4
173/
4
21/444203/
4
471/
4
391/
2
3012 x 12401/
4
48321/
4
161/
4
133/
4
1671/44429471/
4
391/
2
4015 x 12431/
2
62321/
4
163/
4
161/
8
223/
4
61/45829613/
4
421/
2
A42-661EF
Base unit dimensions (cont)
K
1" SUPPLY
AIR COLLAR
D
B
9-11/16
WIDTH
E
2
DEPTH
20
DOOR OPEN
FILTER RACK WITH TOOLLESS ACCESS
FROM SIDES AND BOTTOM
HANGER ROD
KNOCKOUT Ø5/8
TYP 4 PLCS
SEE DETAIL 1
J
TOP VIEW
A
13-3/4
FRONT VIEW
C
ELECTRIC HEAT AND MOTOR
MOUNTED SAME SIDE AS
COIL CONNECTIONS
1-3/8
HEIGHT
SUPPLY AIR
COIL DRAIN CONN.
[FEMALE 1/2-14 NPT SECONDARY]
[MALE 3/4-14 NPT]
1/2
DETAIL 1
SCALE 0.250
1/2
BOTH SIDE PANELS WITH
TOOLLESS CAMLOCK ACCESS
4-3/8
ADD 2" FOR MERV11 FILTER
SIDE VIEW
COIL RETURN CONN.
COIL SUPPLY CONN.
1" RETURN
1
AIR COLLAR
RETURN AIR
8
7-7/16
42BVE FAN COIL BASE UNIT (NO CONTROLS)
NOTES:
1. All dimensions are in inches (±
1
/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to
change without notice.
3. Left hand shown, right hand opposite.
4. Drain pan removal is on the piping side of the unit.
5. "C" dimension is measured from coil side of the unit.
UNIT
42BVE
DIMENSIONS (in.)
Fan SizeDepthWidthHeight
Supply DuctReturn Duct
AB CEF
069 x 4202836
1
/
2
71/
8
101/
2
163/
4
24161/
2
089 x 62028361/
2
81/
2
101/
2
151/
4
24161/
2
1010 x 42237393/
8
71/
8
115/
8
241/
2
33181/
4
1210 x 72237393/
8
10115/
8
211/
2
33181/
4
1611 x 102247393/
8
133/
8
123/
4
163/
4
43181/
4
2012 x 92448451/
8
121/
2
133/
4
173/
4
44203/
4
3012 x 122848541/
4
157/
8
133/
4
164429
4015 x 12286257
5
/
8
161/
2
161/
8
223/
4
5829
A42-4242
C
A
COIL RETURN CONN.
COIL SUPPLY CONN.
COIL DRAIN CONN.
[MALE 3/4-14 NPT]
[MALE 1/2-14 NPT SECONDARY]
SUPPLY AIR
1" SUPPLY AIR
COLLAR
DEPTH
1-7/16
SIDE VIEW
BOTH SIDES
AND FRONT
PANEL WITH
CAMLOCK
ACCESS
4-3/8
ADD 2" FOR
MERV11 FILTER
RETURN AIR
1" RETURN AIR COLLAR
FILTER RACK WITH
TOOLLESS ACCESS
FROM SIDES AND TOP
4 X 4 JBOX AND MOTOR
MOUNTED SAME SIDE AS
B
COIL CONNECTIONS
HEIGHT
2
2-1/16
TOP VIEW
E
FRONT VIEW
WIDTH
F
1"
9
42BVE FAN COIL WITH MOTOR CONTROL OPTION
NOTES:
1. All dimensions are in inches (±1/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to
change without notice.
3. Left hand shown, right hand opposite.
4. Drain pan removal is on the piping side of the unit.
5. "C" dimension is measured from coil side of the unit.
UNIT
42BVE
DIMENSIONS (in.)
Fan SizeDepthWidthHeight
Supply DuctReturn Duct
AB CEF
069 x 4202836
1
/
2
71/
8
101/
2
163/
4
24161/
2
089 x 62028361/
2
81/
2
101/
2
151/
4
24161/
2
1010 x 42237393/
8
71/
2
115/
8
241/
2
33181/
3
1210 x 72237393/
8
10115/
8
211/
2
33181/
3
1611 x 102247393/
8
133/
8
123/
4
163/
4
43181/
3
2012 x 92448451/
8
121/
2
133/
4
173/
4
44203/
4
3012 x 122848543/
16
157/
8
133/
4
164429
4015 x 12286257
5
/
8
167/
16
161/
8
223/
4
5829
a42-4243
Base unit dimensions (cont)
SUPPLY AIR
DEPTH
COIL RETURN CONN.
COIL SUPPLY CONN.
COIL DRAIN CONN.
[MALE 3/4-14 NPT]
[MALE 1/2-14 NPT SECONDARY]
SIDE VIEW
MOTOR CONTROLS
AND MOTOR MOUNTED
SAME SIDE AS
COIL CONNECTIONS
1" SUPPLY AIR COLLAR
BOTH SIDES AND FRONT
PANEL WITH CAMLOCK ACCESS
4-3/8
ADD 2" FOR MERV11 FILTER
RETURN AIR
1" RETURN AIR COLLAR
FILTER RACK WITH
TOOLLESS ACCESS
FROM SIDES AND TOP
1"
B
8-3/4"
HEIGHT
2"
C
TOP VIEW
17-15/16"
DOOR OPEN
WIDTH
FRONT VIEW
A
F
E
1"
10
SUPPLY AIR
DEPTH
COIL RETURN CONN.
COIL SUPPLY CONN.
COIL DRAIN CONN.
[MALE 3/4-14 NPT]
[MALE 1/2-14 NPT SECONDARY]
SIDE VIEW
FILTER RACK WITH
TOOLLESS ACCESS
FROM SIDES AND TOP
1" RETURN AIR COLLAR
RETURN AIR
4-3/8
ADD 2" FOR MERV11 FILTER
BOTH SIDES AND FRONT
PANEL WITH CAMLOCK ACCESS
ELECTRIC HEAT AND MOTOR
MOUNTED SAME SIDE AS
COIL CONNECTIONS
20"
DOOR OPEN
HEIGHT
2"E
WIDTH
FRONT VIEW
1"
F
9-11/16"
1" SUPPLY AIR
COLLAR
TOP VIEW
1"
13-13/16
C
B
A
42BVE FAN COIL WITH ELECTRIC HEAT OPTION
NOTES:
1. All dimensions are in inches (±1/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to
change without notice.
3. Left hand shown, right hand opposite.
4. Drain pan removal is on the piping side of the unit.
5. "C" dimension is measured from coil side of the unit.
UNIT
42BVE
DIMENSIONS (in.)
Fan SizeDepthWidthHeight
Supply DuctReturn Duct
AB CEF
069 x 4202836
1
/
2
87/
8
107/
8
163/
4
24161/
2
089 x 62028361/
2
87/
8
107/
8
151/
4
24161/
2
1010 x 42237393/
8
103/
8
12241/
2
33181/
3
1210 x 72237393/
8
103/
8
12211/
2
33181/
3
1611 x 102247393/
8
137/
8
13163/
4
43181/
3
2012 x 92448451/
8
13141/
8
173/
4
44203/
4
3012 x 122848543/
16
161/
4
141/
8
164429
4015 x 12286257
5
/
8
163/
4
163/
8
223/
4
5829
a42-4244
11
42BHE UNIT CORNER WEIGHTS (lb)
CORNER WEIGHT
NOTE: Unit weights (shown in pounds) ±10%, are based on the 8-row water filled coils, double
2. Base rails are letter coded for ease of assembly.
3. All hardware required for assembly is included.
4. Mixing box option adds 3-inches to the unit height due to the base rails.
a42-4256
FRONT VIEW
W
1(25)
SIDE VIEW
1(25)
D
A
3(76)
15
PIPING CONNECTION LOCATION DIAGRAM* (HYDRONIC COOLING AND HEATING ONLY)
LEGEND
*Left-hand unit with re-heat coil shown.
NOTES:
1. All dimensions are in inches.
2. Use the Piping Connection Location table on page 17 to determine the location of the piping connections. For
example, on a size 20 unit (with re-heat coil) with 4 rows and a left hand connection, the location of the chilled
water supply line is determined by G (5
15
/16 in.) and B (713/16 in.).
42BHE,BVE
UNIT SIZE
HYDRONIC COIL HEAD STUB OUT SIZES (in.)
8 Row Coil SO
Nominal
6 Row Coil SO
Nominal
4 Row Coil SO
Nominal
Heating 1 Row
Coil SO Nominal
Heating 2 Row
Coil SO Nominal
061.00.750.750.50.5
081.00.750.750.50.5
101.00.750.750.50.5
121.00.750.750.50.5
161.01.001.000.51.0
201.01.001.000.51.0301.51.501.501.51.5
401.51.501.501.51.5
CWR — Cold Water Return
CWS — Cold Water Supply
HWR — Hot Water Return
HWS — Hot Water Supply
LH— Left Hand
RH— Right Hand
SO— Stub Out
A42-4246
Accessory dimensions (cont)
HWR
2(51)
D
C
B
A
LH Tell-Tale
E
10-3/8 (264)
F
8-5/8 (219)
G
H
RH Tell-Tale
6-7/8 (175)
0
HWS
1-5/ 8 (41)
CWR
Drain
0
CWS
RETURN AIR
16
HEAT OPTIONS
Re-heat
PIPING CONNECTION LOCATION (HYDRONIC HEATING AND COOLING)
These units can be floor or ceiling mounted, are available
with a variety of options that can meet the design requirements, and provide a low cost solution for a multitude of
applications.
Standard horizontal and vertical blower coil applications — Where the application calls for cooling capac-
ities or external static pressures that can not be met with
standard or high performance direct drive fan coil units,
use a Carrier standard horizontal or vertical blower coil.
Outside air applications — With the availability of
larger capacities, a variety of optional coils, mixing boxes,
and the capability of delivering air through long duct runs,
the belt drive units are ideal for handling outside air. When
used as outside air units, the heating coil should be in the
preheat location (consult Carrier’s application engineering
group).
Large public areas — These units are ideal for applications with a large common area such as restaurants, airports, sports arenas, stadiums, private boxes, gymnasiums,
exercise areas, locker rooms, atriums and foyers, auditoriums, shopping malls, and casinos, to name a few.
Basic definitions
Unit hand — When facing the supply air outlet from the
front of the unit (air blowing in your face), your right hand
will be the right hand side of the unit and your left hand the
left hand side of the unit.
Vertical units are typically installed on a pad. Ensure
adequate pad height for proper trapping of the condensate
drain.
Acoustical considerations
With sound becoming more of a concern to design engineers, building owners, and occupants, proper consideration should be given to the selection and placement of
these units.
Whenever possible, avoid placing these units above an
occupied space. To further reduce the sound level, use
additional measures such as: using flexible duct connectors;
lining the main supply and return ducts with acoustical
absorption material; locating the return-air grilles as far
away from the unit as possible; and using three-phase
motors.
Operating limitations
The fan curves outline the airflow and static pressure range
where it is acceptable to run these units. Running the belt
drive units outside this range could lead to drastically
reduced bearing life and premature wheel failure. In cooling applications, this could also result in moisture carry
over. In addition, running the fan at its maximum fan speed
will increase the power requirements and generate higher
sound levels.
On units with electric heat, the minimum airflow shown
on the fan curve must be maintained to prevent excessive
discharge temperature and electric heat safety trips. For
leaving discharge air temperatures greater than 104 F
(40 C), contact the applications engineering group.
Seismic certification
An optional seismic structural upgrade is available. Carrier’s belt drive series fan coil units with the seismic structural upgrade option are independently tested and certified
in accordance with IBC-2009 and OSHPD ICC-ES-AS156 with SDS of 1.93.
Installation considerations
The belt drive units are typically either suspended above
the ceiling or installed in a closet or mechanical room.
Attention should be paid to having enough clearance
around the units for service and maintenance.
Horizontal units are generally suspended above the ceiling using hanger rods that go through the corner knockouts provided in the units. External vibration isolation and
flex connections for ducts are recommended.
Quality
Carrier's belt drive fan coil units are listed by Intertek Testing Services (ITS). ITS's C-ETL-US listing signifies that
Carrier's belt drive fan coil units have been examined by
ITS and comply with the minimum requirements of U.S.
and Canadian national product safety standard, UL 1995/
CSA C22.2 No. 236, and that the manufacturing site has
been audited. ITS's re-examination service includes periodic visits to the factory to ensure continued compliance
for all listed products.
Every unit is tested and inspected at the factory for trou-
ble-free start-up.
19
Application data (cont)
PIPING COMPONENTS
SYMBOL/SKETCHDESCRIPTION
MANUAL AIR VENT: Threaded brass needle valve
with screwdriver slot for adjustment.
Application — Body brazed into high point of heat-
ing and cooling coils for bleeding air from coil. Standard item on all hydronic coils (not used on steam
or DX coils). Should not be used in lieu of main system air vents.
AUTOMATIC AIR VENT: Nickel plated brass valve,
fiber-disc type, with positive shut-off ballcheck and
quick vent feature via knurled vent screw.
Application — Optional replacement for manual air
vent. Automatically passes minute quantities of air
through the fiber discs which expand upon contact
with water, completely sealing the valve. As air
accumulates, the fiber discs dry and shrink, repeating the cycle. Not recommended for removing large
quantities of air encountered during initial start-up
or subsequent draining and refilling. Should not be
used in lieu of main system air vents.
LEGEND
Cv — Coefficient of Velocity
DX— Direct Expansion
*Check all system component pressure ratings (coils, valves, pumps, etc.) with manufacturer
and any applicable local or national piping codes prior to specifying system pressure rating.
CV FACTORRATING*
1
/
2
N/AN/A400100
N/AN/A125240
3
/
4
PSIGF
Selection procedure
Refer to the Carrier Electronic Selection Program for information to determine unit sizing for your needs.
1. Nominal cooling capacity range is based on 80 F dry bulb and 67 F
wet bulb EAT (entering air temperature), 45 F EWT (entering water
temperature) with 10 F water temperature rise for 4, 6, and 8 row
coils.
42BHE,BVE COMPONENT STATIC RESISTANCE (in. wg)
42BHE,BVE
UNIT SIZE
06
08
10
12
16
20
30
40
NOTE: Use dry coil and clean filter static resistance to determine motor selection.
*These noise ratings are calculated values, not actual test values, and
apply only to the discharge of the unit, not the radiated sound levels.
NOTE: Sound power is in decibels re 10e-12 w.
1252505001000200040008000
CENTER FREQUENCY (Hz)
22
2.0
a42-4247
42BHE,BVE06 FAN PERFORMANCE CURVES
a42-4248
LEGEND
NOTE:The grey area indicates minimum and maximum cfm allowed.
BHP — Brake Horsepower
RPM — Revolutions per Minute
SCFM — Standard Airflow (cfm)
TSP — Total Static Pressure (in. wg)
42BHE,BVE08 FAN PERFORMANCE CURVES
1600 RPM
1/2 BHP
1.5
1400 RPM
1200 RPM
1.0
T S P (in. W.C.)
1000 RPM
0.5
800 RPM
600 RPM
0
0
2.5
1/4 BHP
1/3 BHP
400
Recommended Operating
6008001000
1/6 BHP
1/8 BHP
1/12 BHP
200
SCFM
Range
1600 RPM
2.0
1400 RPM
1.5
1200 RPM
T S P (in. W.C.)
1.0
1000 RPM
0.5
800 RPM
600 RPM
0
1/2 BHP
1/3 BHP
1/4 BHP
1/6 BHP
1/8 BHP
Recommended Operating
Range
SCFM
3/4 BHP
160012008004000
23
a42-4249
a42-4250
42BHE,BVE10 FAN PERFORMANCE CURVES
42BHE,BVE12 FAN PERFORMANCE CURVES
LEGEND
NOTE: The grey area indicates minimum and maximum cfm allowed.
BHP — Brake Horsepower
RPM — Revolutions per Minute
SCFM — Standard Airflow (cfm)
TSP — Total Static Pressure (in. wg)
Performance data (cont)
2.5
1600 RPM
1/3 BHP
2.0
1400 RPM
1/4 BHP
1.5
1/2 BHP
3/4 BHP
1200 RPM
T S P (in. W.C.)
1.0
1000 RPM
800 RPM
0.5
600 RPM
0
200
2.5
1400 RPM
2.0
1/4 BHP
1.5
1200 RPM
Recommended Operating
400
SCFM
3/4 BHP
1/3 BHP
1/2 BHP
Range
0061000100800614001200
T S P (in. W.C.)
1.0
1000 RPM
1/6 BHP
800 RPM
0.5
600 RPM
0
400200016001200800
24
Recommended Operating Range
SCFM
3
1400 RPM
1-1/2 BHP
Recommended
Operating Range
0
0.5
1.5
2.5
3.0
SCFM
600 RPM
800 RPM
1000 RPM
1200 RPM
1/2 BHP
1 BHP
3/4 BHP
1/3 BHP
1.0
2.0
T S P (in. W.C.)
400
800
00020021008200420061
a42-4251
a42-4252
42BHE,BVE16 FAN PERFORMANCE CURVES
42BHE,BVE20 FAN PERFORMANCE CURVES
LEGEND
NOTE: The grey area indicates minimum and maximum cfm allowed.
BHP — Brake Horsepower
RPM — Revolutions per Minute
SCFM — Standard Airflow (cfm)
TSP — Total Static Pressure (in. wg)
1400 RPM
1/3 BHP
1/2 BHP
3/4 BHP
1 BHP
2.5
1/4 BHP
1200 RPM
2.0
1.5
1000 RPM
T S P (in. W.C.)
1.0
800 RPM
0.5
600 RPM
0
400
Recommended Operating Range
800
1200160020002400
SCFM
25
1400 RPM
2 BHP
0
0.5
1.5
2.5
3.0
SCFM
600 RPM
800 RPM
1000 RPM
1200 RPM
1 BHP
3/4 BHP
1-1/2 BHP
Recommended Operating
Range
1.0
2.0
T S P (in. W.C.)
1600
0044000400230042
1200
006300820002
a42-4253
a42-4254
42BHE,BVE30 FAN PERFORMANCE CURVES
42BHE,BVE40 FAN PERFORMANCE CURVES
LEGEND
NOTE: The grey area indicates minimum and maximum cfm allowed.
BHP — Brake Horsepower
RPM — Revolutions per Minute
SCFM — Standard Airflow (cfm)
TSP — Total Static Pressure (in. wg)
Performance data (cont)
3.0
1200 RPM
2.5
2.0
1000 RPM
1.5
T S P (in. W.C.)
800 RPM
1.0
600 RPM
0.5
0
1000
2 BHP
1 BHP
2000
Recommended Operating
3000400050006000
SCFM
Range
PHB 5PHB 3PHB 2/1-1
26
BASE UNIT, SINGLE-PHASE POWER
BASE UNIT, THREE-PHASE POWER
a42-490ef.eps
a42-492ef
Typical wiring
27
MOTOR CONTROLS / SINGLE-PHASE WITH INTERLOCKING DISCONNECT AND 1-STAGE ELECTRIC HEATER
a42-4088
Typical control wiring schematics
28
MOTOR CONTROLS / 3-PHASE WITH INTERLOCKING DISCONNECT AND 1-STAGE ELECTRIC HEATER
a42-4089
29
MOTOR CONTROLS / 3-PHASE WITH INTERLOCKING DISCONNECT AND 2-STAGE ELECTRIC HEATER
a42-4090
Typical control wiring schematics (cont)
30
MOTOR CONTROLS / 3-PHASE WITH INTERLOCKING DISCONNECT AND 3-STAGE ELECTRIC HEATER
a42-4091
31
Electrical data
42BHE,BVE ELECTRIC HEATER DATA AVAILABILITY42BHE,BVE ELECTRIC HEATER DATA
kW
1.0●●——————
1.5●●●●————
2.0●●●●————
2.5●●●●●———
3.0●●●●●———
3.5●●●●●●——
4.0●●●●●●——
4.5●●●●●●——
5.0●●●●●●——
6.0●●●●●●●●
7.0—●●●●●●●
8.0—●●●●●●●
9.9—— ●●●●●●
12.0——— ●●●●●
14.0———— ●●●●
15.0———— ●●●●
16.0———— ●●●●
18.0————— ●●●
19.9————— ●●●
25.0—————— ●●
30.0—————— ●●
35.0——————— ●
39.9——————— ●
● — Standard Offering
— — Not Offered
NOTES:
1. Stages available:
a. Single phase: 1 to 12 kW, 1 stage only
b. Three phase: 1 to 39.9 kW, 1 stage only
2. Electric Heating Capacities (Btuh) = Heater kW x 3413
3. Electric Heater Amperage for Single-phase Power = (Heater kW x 1000)/Applied Voltage
Electric Heater Amp. for 3-phase Power = (Heater kW x 1000)/(Applied Voltage x 1.73).
0608101216203040
LEGEND
3 to 12 kW, 1 stage or 2 stage
4 to 39.9 kW, 1 or 2 stage
12 to 39.9 kW, 1, 2 or 3 stage
1. Motor full load amps refer to National Electric Code (NEC) amps;
actual motor nameplate amps may vary.
2. NEC data extrapolated for 277 v.
3. Motors are open drip proof, ball bearing, single speed, 1750 rpm
rated at continuous duty, 104 F ambient with reversible rotation.
4. 5 hp motors available only on size 40 units.
1
1
/
/
4
3
Nominal HP
1
3
/
/4111/2235
2
Service switches:
The service switch is an On/Off switch on incoming power
supply to unit. Proper amperage load must be determined
before switch can be selected. The range of the fused or
non-fused service switch is 0 to 40 amps.
MCA (minimum circuit amps) = 1.25 x sum of all
loads.
MFS (maximum fuse size) = MCA rounded up to next
available fuse size.
32
Controls
Standard control features
• 4 in. x 4 in. junction box
NOTE: Motor leads are wired to the 4 in. x 4 in. junction
box, mounted on the external panel. Field verification of
the motor rotation is required on 3-phase applications.
Motor control options
• Interlocking disconnect switch*
• 24-v class 2 transformer (40 va)†
• 8-pole control terminal strip
• Motor power fusing*
• Motor control contactor**
Motor and electric heat control options
NOTE: Electric heat option requires same voltage as motor
and must include the control option. These control features
are standard with electric heat options and control option.
• Interlocking disconnect switch*
• Heater power fusing*
• 24-v class 2 transformer (40 va)†
• 8-pole control terminal strip
• Auto reset temperature limit switch
• Manual reset backup temperature limit switch
• 80/20 heater element wire
• Motor power fusing*
• Motor control contactor**
• Agency listed for 0-in. clearance
Electric heat options:
• Single-phase, 1 or 2 stage heat
• Three-phase, 1, 2 or 3 stage heat
*Complies with NEC’s requirement, Article 430 for dis-
connect, branch circuit protection motor controller and
motor overload protection.
†No control fusing necessary.
**Complies with NEC’s requirement for a motor starter
with internal heating elements when used with the
factory’s standard motors with integral thermal overload
protection.
33
Guide specifications
System Fan Coil Unit
HVAC Guide Specifications
Size Range: 600 to 4000 Nominal Cfm
Carrier Model Numbers:
42BHE (Horizontal Fan Coil Unit)
42BVE (Vertical Fan Coil Unit)
Part 1 — General
1.01 SYSTEM DESCRIPTION
Horizontal and vertical, 2-pipe or 4-pipe, belt-
driven, galvanized casing model fan coil unit for
ducted installation above the ceiling or within
floor-mounted cabinet, with full access to internal
components.
1.02 QUALITY ASSURANCE
A. Unit shall be constructed in accordance with ETL
and ETL, Canada standards. Units comply with the
minimum requirements of the US and Canadian
national product safety standard, UL 1995/CSA
C22.2 No. 236. Factory-installed motors and electric heaters shall be UL approved. Insulation and
adhesive shall meet NFPA-90A requirements for
flame spread and smoke generation.
B. Coils shall be tested in accordance with AHRI stan-
dard 410, latest edition. Each coil shall be factory
tested for leakage at 300-psig air pressure with coil
submerged in water.
1.03 DELIVERY, STORAGE AND HANDLING
Unit shall be handled and stored in accordance with
the manufacturer’s instructions.
Part 2 — Products
2.01 EQUIPMENT
A. General:
Factory-assembled, horizontal and vertical, drawthru type fan coil unit for ducted installation above
the ceiling or floor mounting. Unit shall be complete
with water coils, fan(s), motor, belt drive, drain pan,
and filter.
B. Casing:
Construction shall be heavy-gage galvanized steel,
lined with one-in. thick fiberglass Tuf-Skin™ II
thermal/acoustical insulation. Knockouts shall be
provided for hanging the horizontal unit, that will
accept
all unit corners. Supply and return duct connections
shall be 1 in. long. Removable side panels shall be
provided for access to the fan/motor assembly.
Access panels shall be easily removable with hex key
tool on vertical unit, and without tools on horizontal
unit. A double-sloped drain pan shall be constructed
of stainless steel, extending under the full length and
width of the coil(s) with a
thread stainless steel drain connection and
male NPT stainless secondary drain connection (cap
when not required). The outside surface of the drain
pan shall be insulated with
insulation. Drain pan is removable from cabinet
3
/8-in. threaded rod at the top and bottom of
3
/4-in. male nominal pipe
1
/8-in. closed cell
1
/2-in.
from same end as coil connections for ease of
cleaning.
C. Fans:
Belt-driven, double-width fan wheels shall have forward-curved blades and be statically and dynamically
balanced. Fan drive shall consist of variable-pitch
motor pulley, fixed-diameter blower sheave with
keyed shaft, and V-belt. Fan drive shall be designed
for 120% of rated fan horsepower. Fans and scrolls
shall be of galvanized steel. Bearings are ball bearings, permanently lubricated and sealed for life.
Bearings are isolated from the blower housing by
rubber mounts set into heavy gage metal support
system. The blower housing shall be isolated from
the cabinet and motor.
D. Coils:
Standard unit shall be equipped with a 4-row coil for
installation in a 2-pipe system and additional rows of
coil shall be provided as an option for installation in
a 4-pipe system. Coils shall have
1
/2-in. copper
tubes, aluminum fins bonded to the tubes by
mechanical expansion and have a working pressure
of 250 psig at 200 F. Each coil shall have a manual
air vent and sweat connections for copper tubes.
E. Operating Characteristics:
A single-circuit coil unit installed in a 2-pipe system
shall be capable of providing heating or cooling as
determined by the operating mode of the central
water supply system. A double-circuit coil unit
installed in a 4-pipe system shall be capable of providing sequenced heating and cooling.
F. Motor(s):
1. Fan motors shall be open, drip-proof, singlespeed, single or 3 phase, suitable for continuous duty at 104 F (40 C). Single-phase motors
are capacitor start, include automatic reset thermal overload protection and are available in
115, 208, 230, or 277 volts (60 Hz) or 220
volts (50 Hz). Three-phase motors are available
in 208, 230, or 460 volts (60 Hz) or 380 volts
(50 Hz).
2. Motors are Class B, continuous duty rated.
Motors are resilient mounted (
1
/4 to 2 hp), rigid
base mounted (3 and 5 hp), NEMA frame
motors. Motors are factory wired to unit junction or control box. Motor bearings are permanently lubricated. Motors are mounted on an
adjustable base for belt tensioning and alignment. The motor and drive are installed on the
same end as the coil connection for ease of
service.
G. Special Features:
1. Coils:
a. Unit coil(s) shall be equipped with automatic
air vent(s).
b. Unit shall be equipped with a high-capacity
6-row or 8-row coil for installation in a
2-pipe system.
34
c. For installation in a 4-pipe system, unit shall
be equipped with either a 4-row cooling/
1-row hot water heating split-circuit coil, or
a 4/2, 6/1, or 6/2 split-circuit coil as
required.
d. Unit shall be equipped with either a 4-row
DX (direct expansion) cooling coil or a 6-row
DX cooling coil as required.
e. Unit coil(s) shall be copper fin, copper tube
with stainless steel end sheets and baffles.
2. Filters:
a. A two-in. pleated filter shall be installed in
the unit (standard).
b. One-in. pleated, two 1-in. throwaway or
2-in. pleated MERV 11 filters with 2-in. prefilter shall be installed as indicated on the
equipment schedule.
3. Insulation:
a. Units shall be equipped with 1-in. thick Tuf-
Skin™ II insulation (standard).
b. Units are available with 1-in. closed cell,
1-in. anti-microbial fiberglass, or 1-in. foilfaced insulation.
4. Controls:
a. Unit shall be equipped with 24-v trans-
former, motor contactor and terminal strip
for connection to field or factory provided
controller.
b. Unit shall be equipped with interlocking
door-disconnect switch with lock-out tag-out
compatibility, touch-type fusing, 24-v transformer, motor contactor and terminal strip
for connection to field provided controller.
c. Unit shall be equipped with interlocking
door-disconnect switch with lock-out tag-out
compatibility, separate motor and electric
heater touch-type fusing, 24-v transformer,
motor contactor and terminal strip for connection to field-provided or factory-provided
controller.
d. Fuses comply with NFPA 70E/IP20.
5. Electric Heat:
a. Electric heaters shall be constructed of high-
grade resistance wire supported by ceramic
insulators on plated steel brackets. The heat
elements shall be suspended in front of the
outlet, after the blower and coil. An auto and
manual thermal limit switch shall protect the
heat elements in the event of an air failure.
b. Single-phase heaters shall be available in
115, 208, 230, or 277 volts (60 Hz) or
220 volts (50 Hz). Three-phase electric heat
shall be available in 208, 230, or 460 volts
(60 Hz) or 380 volts (50 Hz).
c. Electric heaters can be controlled in single,
2, or 3 stages of operation.
6. Mixing Boxes:
a. Mixing boxes shall be preassembled at the
factory and shipped separately with base
rails.
b. Mixing boxes shall include a linkage kit,
which consists of two crankarms, 2 swivels
and a rod, 25 in. long (for unit sizes 06-16)
or 84 in. long (for unit sizes 20-40), for the
field installation of the actuator.
7. Cabinet:
a. Optional double wall construction with
choice of 1-in. fiberglass or 1-in. closed cell
insulation with solid or perforated inner liners. An antimicrobial coating can also be
added.
b. Optional seismic structural upgrade to meet
IBC-2009 and OSHPD seismic certification
in accordance with ICC-ES-AS-156.
35
Carrier Corporation • Syracuse, New York 132219-13
Section 8
Ta b8 b
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Pg 36Catalog No. 04-52420015-01Printed in U.S.A. Form 42B-6PD