Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 3
Tab 7a
PC 201Catalog No. 514-203Printed in U.S.A.Form 42-3XCPg 16-90Replaces: 42-2XC
CONTENTS
Page
CONTROL SELECTION GUIDE ............... 3
STANDARD WIRING PACKAGES ............ 4-8
Manual Fan Control ......................... 4
Thermostatic Fan Control,
2-Pipe Systems ............................ 4
Thermostatic Fan Control,
2-Pipe System with Safety Cycle ............ 5
Thermostatic Electric Valve Control, 2-Pipe ... 5
Thermostatic 2-Pipe Auxiliary Electric Heat
with Valve Control ......................... 6
Thermostatic 2-Pipe Total Electric Heat
with Valve Control ......................... 7
Thermostatic Valve Control, 4-Pipe ........... 8
ELECTRIC HEAT ............................ 9
Application ................................. 9
Heater Construction ......................... 9
Heater Electrical Data ....................... 9
REMOTE-MOUNTED CONTROLS ............ 10
Standard 3-Speed Switch ................... 10
Combination Thermostat/3-Speed Switch .... 10
Wall Thermostat, 2-Pipe .................... 10
Wall Thermostat, 4-Pipe .................... 10
ALTERNATE WALL THERMOSTATS ......... 11
Wall Thermostat (Honeywell) with Manual
3-Speed Fan Switch and ON-OFF Switch ... 11
Wall Thermostat (Sunne) with Manual
3-Speed Fan Switch and ON-OFF Switch ... 11
Page
UNIT MOUNTED CONTROLS .............. 12,13
Standard 3-Speed Switch ................... 12
Combination Thermostat/3-Speed Switch .... 12
Combination Thermostat/ON-OFF
Toggle Switch ............................ 12
Two-Pipe Thermostat ....................... 13
Four-Pipe Thermostat ...................... 13
Automatic Changeover ..................... 13
BASIC DEFINITIONS ....................... 14
FIELD PIPING CONNECTIONS .............. 15
VALVE PACKAGES ....................... 16-19
General ................................... 16
Two-Way Motorized Control Valve ........... 18
Two-Way Motorized Control Valve
with Aquastat Bleed Bypass Line .......... 18
Three-Way Motorized Control Valve ......... 19
No Motorized Control Valve ................. 19
VALVE PACKAGE ARRANGEMENTS ....... 20-23
PIPING COMPONENTS .................... 24-27
Cv FACTOR vs WATER PRESSURE DROP ... 28
SYSTEM COMPONENT WORKING
PRESSURE ............................... 29
COPPER WATER TUBE AND JOINT MATERIAL
PRESSURE RATINGS ..................... 30
CORRECTION FACTORS FOR GLYCOL ...... 31
STANDARD ACCESSORIES AND OPTIONS .. 32
2
CONTROL SELECTION GUIDE
Use this guide to make sure that all necessary components are provided for and that the components are compatible
with the required control system.
NOTE: When thermostatic fan control is selected or when unit outside air dampers are used, unit-mounted thermostats
are not recommended as their use will result in poor room temperature sensing.
SYSTEMDESCRIPTIONTHERMOSTAT
Fan
Control
(2-Pipe)
Twoposition
electric
valves
(2-pipe)
2-PIPE HEATING-COOLING*
Pneumatic
modulating
valves
(2-pipe)
Twoposition
electric
valve with
Auxiliary
Electric
Heat
(2-pipe)
Twoposition
electric
valve with
total
electric
ELECTRIC HEAT
heat
(2-pipe)
Pneumatic
modulating
valves
(2-pipe)
Twoposition
electric
valves
(4-pipe)
4-PIPE
Pneumatic
modulating
valves
(4-pipe)
Fan manually cycledNoneNoneNoneStandard
Thermostat cycles fan on-off
from speed set with
fan switch.
Thermostat cycles fan on-off
from fan speed set
with switch. Mode
automatically switched
by changeover
sensing water temp.
Thermostat cycles fan from
high to low on cooling
and low to off on heating.
Thermostat cycles valve
open or closed.
Thermostat cycles valve
open or closed.
Mode automatically
switched by changeover
sensing water temp.
Thermostat modulates
pneumatic control valve.
Thermostat cycles valve
open or closed. 2° F after
valve closes, thermostat
activates electric heater.
Heater can’t turn on
if hot water is in coil.
Thermostat cycles valve
open or closed. Manual
changeover switch
changes thermostat to
heat to activate electric
heater.
Thermostat cycles valve
open or closed.
Manual changeover switch
changes thermostat to heat
to activate electric heater.
Thermostat cycles valve
open or closed.
2° F after valve closes,
thermostat activates
electric heater.
Thermostat modulates
pneumatic control valve.
After changeover,
thermostat
activates electric heater.
Thermostat cycles
cooling and heating
valves open or closed.
Thermostat cycles cooling
valve open or closed. 2° F
after valve closes,
thermostat cycles
heating valve open or closed.
Thermostat modulates
cooling valve.
After changeover,
thermostat modulates
heating valve.
Wall mounted
includes heat-cool
switch.
Wall mounted.
Heating/cooling
Thermostat
Wall or unit
mounted
Wall mounted
includes heat-cool
switch.
Wall or unit
mounted.
Heating/cooling
Thermostat
By others.By others.2- and 3-way
Wall or unit
mounted. Sequenced
heating and cooling.
Wall mounted
includes heat-cool
switch.
Wall mounted
includes heat-cool
switch.
Wall or unit
mounted.
Sequenced heating
and cooling
By others.By others.2- and 3-way
Wall mounted
includes subbase
with heat-cool
switch.
Wall or unit
mounted.
Sequenced heating
and cooling.
By others.By others.2- or 3-way
CHANGEOVER
ON
SUPPLY PIPE
NoneNoneThermostat has
YesNoneStandard
YesNoneNo Standard
NoneMotorized (N.C.)
YesMotorized (N.C.)
Yes.
Two Required.
NoneMotorized
NoneMotorized (N.C.)
NoneMotorized (N.C.)
NoneMotorized (N.C.)
NoneMotorized (N.C.)
VALVE
3-way or 2-way,
no bypass required.
3-way or 2-way
furnished by others.
Can be equipped
with factory
assembled
valve package.
Motorized
3-way or 2-way
3-way or 2-way,
no bypass required
3-way or 2-way,
no bypass required
3-way or 2-way,
no bypass required
furnished by others.
Can be equipped
with factory
assembled
valve package.
3-way or 2-way
(requires 2 valves)
3-way or 2-way
(requires 2 valves)
furnished by others.
Can be equipped
with factory
assembled
valve package.
FAN
SWITCH (SW)
3-Speed SW
integral
3-Speed SW
3-Speed SW
3-Speed Switch,
ON-OFF toggle SW
only
Thermostat
has integral
3-Speed SW
Standard
3-Speed SW.
Others have
thermostats with
integral 3-Speed SW
Standard
3-Speed SW
Standard
3-Speed SW
Others have
thermostats with
integral 3-Speed SW
Thermostat
has integral
3-Speed SW
Thermostat
has integral
3-Speed SW
Standard
3-Speed SW
Standard
3-Speed SW
Thermostat
has integral
3-Speed SW
Standard
3-Speed SW.
Others have
thermostats
with integral
3-Speed SW
Standard
3-Speed SW
*If system is HEATING-ONLY or COOLING-ONLY, no changeover or bypass is required.
NOTE: Unit-mounted thermostats are not recommended with either fan-cycle control or applications with outside air dampers.
NOTES
Not recommended
for high humidity
application
Unit mounted
thermostats provide
very poor room
temperature control
Best fan cycle
control for
high humidity
applications
Valve packages
with belled end(s)
for field soldering
to coil.
Factory assembled
in valve package
w/flare nuts.
Valve packages
with belled end(s)
for field soldering
to coil.
Valve packages
with belled end(s)
for field soldering
to coil.
Valve packages
with belled end(s)
for field soldering
to coil.
Valve packages
with belled end(s)
for field soldering
to coil.
Factory assembled
in valve package
w/flare nuts.
Valve packages
with belled end(s)
for field soldering
to coil.
Valve packages
with belled end(s)
for field soldering
to coil.
Factory assembled
in valve package
w/flare nuts.
Valve packages
include unions for
for field assembly
to coil.
3
STANDARD WIRING PACKAGES
IMPORTANT: Wiring diagrams shown depict typical
control functions. Refer to unit wiring label for specific functions.
Manual Fan Control — On all Vertical Cabinet units,
the standard fan-speed switch is furnished unit-mounted and
wired. On all VerticalFurred-In units and all Horizontal units,
the switch is shipped separately on a decorative wall plate
for field mounting and wiring.
The standard switch has LOW,MEDIUM, HIGH and OFF
positions plus an auxilliary contact to energize thermostats,
valves, dampers, etc.
NOTE: Wiring diagrams are for 120-v power supply.If other
voltages for heaters or controls are specified, wiring may differ from that shown.
The standard 3-speed switches are illustrated on page 12
(unit mounted) and on page 10 (wall mounted).
For NOTES, see below.
Thermostatic Fan Control, 2-Pipe Systems —
The thermostat cycles the fan on and off from any selected
speed setting to maintain selected room temperature. Controls can be wired for heating-only,cooling-only or for heating/
cooling by the addition of an automatic changeover device
that senses water temperature and changes the action of the
thermostat as required.
For control package descriptions, see control components
sections entitled Remote-Mounted Controls and UnitMounted Controls, pages 10-13.
NOTES:
1. Motors are thermally protected.
2. Use copper conductors only.
3. See unit nameplate for power supply. Provide disconnect means
and overload protection as required.
4. Unit-mounted thermostats are not recommended for fan control
because of poor temperature sensing. Fan control not available
on 42VC,VE Loboy units.
THERMOSTAT OR
UNIT
TYPE
VerticalUnit MountedN/AN/A
Vertical
or
Horizontal
*Packages listed on current price pages. First 2 digits are item
numbers.
†For alternate thermostat with manual changeover. Refer to current
price pages.
LOCATION
Wall Mounted
WIRING PACKAGE*
Heating or
Cooling Only
22-C, 22-D
22-E, 22-F
Heating and Cooling
Plus Changeover†
22-A, 22-B
4
Thermostatic Fan Control, 2-Pipe System with
Safety Cycle —
situations in which condensate problems can occur if fan is
turned off while chilled water is still running through the
coil.
The wiring provides fan cycling from HIGH to LOW on
the cooling cycle and from LOW to OFF on the heating cycle.
An ON-OFF toggle switch replaces the standard 3-speed fan
switch. The toggle switch can be concealed to ensure that
the unit runs on low speed when cooling. This action greatly
reduces the chance of condensation problems that exist with
other standard fan cycling controls.
For control package descriptions, see control components
section entitled Remote-Mounted Controls and Unit-Mounted
Controls.
This control is used for high humidity
UNIT
TYPE
VerticalUnit Mounted24-R
Vertical
or
Horizontal
* Packages listed on current price pages.
LOCATION
Wall Mounted23-17
Heating and Cooling
PACKAGE CODE*
Plus Changeover
For NOTES, see below.
Thermostatic Electric Valve Control, 2-Pipe —
A thermostatically controlled 2-position valve provides superior control to fan cycling. With this control, the fan runs
continuously unless it is manually switched to the OFF position. The fan must be on before the valve can be opened to
supply water to the coil.
This system can be used for normal 2-pipe changeover
systems and can also be furnished for cooling-only or heatingonly applications by omitting the changeover and specifying
which application is intended.
NOTES:
1. Motors are thermally protected.
2. Use copper conductors only.
3. See unit nameplate for power supply. Provide disconnect means
and overload protection as required.
For control package descriptions, see control components
sections entitled Remote-Mounted Controls and UnitMounted Controls.
THERMOSTAT OR
UNIT
TYPE
Vertical
Vertical
Horizontal
*Packages listed on current price pages. First 2 digits are item
numbers.
†For alternate thermostat with manual changeover. Refer to current
price pages.
or
LOCATION
Unit
Mounted
Wall
Mounted
WIRING PACKAGE*
Heating or
Cooling
Only
24-M,
24-N
22-C, 22-D,
22-E, 22-F
Heating and
Changeover†
22-A, 22-B
Cooling
Plus
24-L
ELECTRIC
VALVE
Any 2- or
3-way,
2-position
valve
package.
5
STANDARD WIRING PACKAGES (cont)
Thermostatic 2-Pipe Auxiliary Electric Heat
with Valve Control —
light or Intermediate Season electric heat, goes a long way
towards solving the spring and fall control problems of 2-pipe
systems.
You can run chilled water late into the fall, turn it on early
in the spring and still have heat available to all units whenever required.
In winter the system is switched over to hot water. Two
changeover devices are required for this. One device switches
the action of the thermostat and the other locks out the electric heat when hot water is in the coil.
With this system, the fan runs continuously unless manually switched to OFF position. Fan must be on before thermostat can send signal to open chilled water valve or turn on
electric heater.
UNIT
TYPE
Vertical
Vertical
or
Horizontal
*Packages on current price pages.
This system, also called Twi-
LOCATION
Unit
Mounted
Wall Mounted
Automatic SystemManual System
24-QAvailable on Special Order.
22-J, 22-K,
23-09, 23-10
Two control methods are available:
1. Use the standard automatic changeover thermostat with a
dead band between heating and cooling, or —
2. Use a manual changeover thermostat. With this method
only one changeover is required.
Be sure to include a 2-way or 3-way electric valve with
this system.
NOTE: Wiring diagrams are for 120-v power supply.If other
voltages for heaters or controls are specified,wiring may differ from that shown.
For control package descriptions, see control components
sections entitled Remote-Mounted Controls and UnitMounted Controls.
WIRING PACKAGE*
23-15, 23-16
ELECTRIC
VALVE
Any 2- or 3-way,
2-position valve
Package.
NOTES:
1. Motors are thermally protected.
2. Use copper conductors only.
3. See unit nameplate for power supply. Provide disconnect means
and overload protection as required.
6
Thermostatic 2-Pipe Total Electric Heat withValve Control —
ing requirement for the space is provided by the electric heater;
the water system is never changed over for heating. It is therefore possible, just as with 4-pipe systems, to have heating or
cooling at any time of the year.
The fan runs continuously unless it is manually switched
to OFF position. Fan must be on before thermostat can send
signal to open chilled water valve or turn on electric heater.
Normally,an automatic changeover thermostat with a dead
band between heating and cooling is used, but a manual
With this system, the complete heat-
changeover thermostat is also suitable. A 2-way or 3-way
valve must also be used so that the chilled water is off whenever the heater is on. No changeover device to sense water
temperature is necessary.
NOTE: Wiring diagrams are for 120-v power supply. If other
voltages for heaters or controls are specified, wiring may differ from that shown.
For control package descriptions, see control components
sections entitled Remote-Mounted Controls and UnitMounted Controls.
UNIT
TYPE
Vertical
Vertical
or
Horizontal
*Packages on current price pages.
LOCATION
Unit
Mounted
Wall Mounted
WIRING PACKAGE*
Automatic SystemManual System
24-QAvailable on Special Order.
22-J, 22-K,
23-09, 23-10
23-15, 23-16
ELECTRIC
VALVE
Any 2- or 3-way,
2-position valve
Package.
NOTES:
1. Motors thermally protected.
2. Use copper conductors only.
3. See unit nameplate for power supply. Provide disconnect means
and overload protection as required.
7
STANDARD WIRING PACKAGES (cont)
Thermostatic V alveControl, 4-Pipe —
The 4-pipe
system provides the ultimate in economy and room temperature control. Both hot water and chilled water are available at any time.
Normally an automatic changeover thermostat is used, but
a manual changeover thermostat is also suitable. Two2-way
valves, two 3-way valves, or one 2-way plus one 3-way valve
must be selected. An automatic changeover device to sense
water temperature is not required.
UNIT TYPELOCATION
VerticalUnit Mounted24-PAvailable on Special Order.
Vertical
or
Horizontal
*Packages on current price pages.
Wall Mounted
Automatic SystemManual System
22-G, 22-H,
23-07, 23-08
With this system, the fan runs continuously unless it is
manually switched to OFF position. Fan must be on before
thermostat can send signal to open the chilled water or hot
water valve.
NOTE: Wiring diagrams are for 120-v power supply.If other
voltages for heaters or controls are specified, wiring may differ from that shown.
For control package descriptions, see control components
sections entitled Remote-Mounted Controls and UnitMounted Controls.
WIRING PACKAGE*
23-13, 23-14
ELECTRIC
VALVE
Any 2- or 3-way,
2-position valve
package.
NOTES:
1. Motors thermally protected.
2. Use copper conductors only.
3. See unit nameplate for power supply. Provide disconnect means
and overload protection as required.
8
ELECTRIC HEAT
Application —
Electric heaters are available for
in-stallation on Carrier fan coil units in the following
applications.
TOTAL ELECTRIC HEAT — This system provides complete heating during the heating season; no boiler is required. Heating and cooling are now available on an individual basis throughout the year with a 2-pipe system.
Chilled water is used for cooling and the electric heater is
used for heating. Room controls can be supplied for
either manual or automatic changeover.
AUXILIARYELECTRIC HEAT — This system is used for
heating between seasons or during the cooling season when
chilled water is being circulated. Individual room controls
are supplied to provide electric heat only when chilled water
is being circulated through the system. Water flow through
the unit is shut off when the heater is turned on.
During the winter heating season, heating is provided
by hot water circulated through the system. A changeover
device locks out the electric heat when the hot water is
circulated.
Heater Construction
STRIP HEATERS — Used with Model 42C ceiling units,
Model 42D ducted units and Model 42S stack units.
These heaters consist of coils of the highest grade
resistance wire, insulated by ceramic insulators in aluminized brackets.
All heaters except those used in 42S stack units are positioned on the incoming (preheat) side of the unit coil. On
42S stack units, the strip heater is located in the fan discharge on the leaving side of the coil.
SHEATHHEATERS — Used with Model 42V vertical units.
These heaters consist of the highest grade resistance wire,
centered in a
1
⁄2-in. diameter copper-plated steel sheath. The
wire is insulated from the sheath by magnesium oxide powder packed around it. To increase the heater surface exposed
to air, a 11⁄4-in. OD fin of copper-plated steel is wound around
the sheath in a continuous spiral that makes 5 turns per lineal inch. Sheath and fin are permanently bonded together by
copper brazing.
The heaters are positioned on the leaving (reheat) side of
the unit coil. On special units with high efficiency motors, a
strip heater will be installed in the fan discharge on the incoming (preheat) side of the unit coil.
Heater Electrical Data
1. Load voltage may be 120, 208, 240 or 277 volts. For unit
size and kW limitations, refer to the specific unit
catalogs.
2. All heaters are single stage and single phase.
3. Unless a single power-source option is selected, the elec-
tric heat units require 2 separate power sources. With the
single power-source option, only one line circuit need be
brought into the unit. Fuse protection is added to the motor/
control circuit to protect these components. This is separate from the field-furnished total unit overcurrent protection.
MODEL 42V VERTICAL UNIT
WITH ELECTRIC SHEATH HEATER
MODEL 42C CEILING UNIT
WITH ELECTRIC STRIP HEATER
9
REMOTE-MOUNTED CONTROLS
Standard 3-Speed Switch —
This standard switch
has 4 positions: OFF, HIGH, MEDIUM, and LOW. Switch
has auxiliary contact that is energized when switch is in HIGH,
MEDIUM or LOW position.
Some of the options common with the 3-speed switch are:
1. Unit-mounted switch on Furred-In VerticalModel. (Avail-
able as special order on Horizontal Models)
2. Switch without OFF position.
3. Key-operated switch.
CombinationThermostat/3-SpeedSwitch
(Packages 22-B, 22-D, 22-F, 22-H, 22-K*) — Thermostat
and standard switch are mounted on a common decorative
wall plate, suitable for installation in a 411⁄16-in. square junction box. Packages 22-A and 22-B include Model TC-126
2-pipe heating and cooling thermostat and automatic changeover switch (shipped separately for field wiring and mounting).
Packages 22-C and 22-D include Model TC-126 thermo-
stat less automatic changeover switch wired for cooling only.
Packages 22-E and 22-F include Model TC-126 thermo-
stat, less automatic changeover, wired for heating only.
Package 22-G includes Model TH-126 4-pipe thermostat
for sequenced heating and cooling, plus 3-speed switch. (For
4-pipe or total electric heat systems.)
Package 22-J is the same as 22-G except that 2 automatic
changeover switches are shipped with package. (For auxiliary electric heat systems.)
70
60
50
80
90
Wall Thermostat, 2-Pipe (Packages 22-A through
22-F*) — Model TC-126 thermostat for heating and cooling, operates on line voltage. Action is SPDT. Temperature
range is 50-90 F.
Packages 22-A and 22-B — Heating and cooling, includes one automatic changeover switch (shipped separately
for field wiring and mounting).
Wall Thermostat, 4-Pipe (Packages 22-G through
22-K*) — Model TH-126 thermostat is also used on 2-pipe
system with electric heat. Heating and cooling are sequenced (automatic changeover) with 6 degree separation between HEATINGON and COOLING ON. T emperaturerange
is 50 - 90 F.
Packages 22-G and 22-H — For 4-pipe and total electric
heat systems.
Packages 22-J and 22-K — For auxiliary electric heat systems, includes 2 automatic changeover switches (shipped separately for field wiring and mounting).
ALTERNATE WALL THERMOSTATS
WallThermostat (Honeywell Model T4039) with
Manual 3-Speed Fan Switch and ON-OFF Switch
Temperature range is approximately 55 to 95 F in 10° F
increments from 75 F midpoint. Scale is marked warmercooler. Thermostat mounts in 4-in. square junction box or
2-ganged outlet boxes.
SYSTEMMODELPACKAGE
2-Pipe Cooling OnlyT4039B*23-05
2-Pipe Heating OnlyT4039F*23-03
2-Pipe Heating/Cooling†T4039F*23-01
2-Pipe w/Total Electric HeatT4039M**23-07
4-Pipe Heating/CoolingT4039M**23-07
2-Pipe w/Auxiliary Electric Heat††T4039M**23-09
*Fan off breaks cooling circuit and fan.
†Includes one remote-mounted changeover on unit
**Fan off breaks both heating/cooling circuits and fan.
†† Includes 2 remote-mounted changeovers on unit.
NOTE: All above packages include thermostat, ON-OFF switch and HIMED-LOW switch.
Thermostat Electrical Ratings (Amperes)
VOLTAGENORMALIN-RUSH
120V AC0.321.00
240V AC0.160.50
277V AC0.140.43
VOLTAGEFULL LOADLOCKED ROTOR
120V AC5.5033.0
240V AC2.7516.5
277V AC2.4014.4
Thermostat (Valve Load)
Fan Switch
MED
OFF
WARM
FAN
HI
LO
ON
COOL
HONEYWELL MODEL T4039
THERMOSTAT
WallThermostat (Sunne Model154) with Manual
3-Speed Fan Switch and ON-OFF Switch
Temperature range is approximately 55 to 95 F in 10° F
increments from 75 F midpoint. Scale is marked warmercooler. Thermostat mounts in 4-in. square junction box or
2-ganged outlet boxes.
MED and LOW positions. Switch is also equipped with auxiliary connection energized when switch is in HIGH, MED
or LOW position.
MED
HI
OFF
COMBINATION THERMOSTAT AND TOGGLE SWITCH
CombinationThermostat/ON-OFF ToggleSwitch
(Package 24-R*) — Includes Model TF103 2-pipe thermostat and toggle switch. Used as special fan control for cycling fan from HIGH to LOW on cooling; from LOW to
OFF on heating.
LO
Combination Thermostat/3-Speed Switch (Pack-
ages 24-L, M, N, Pand Q*) — Thermostat and standard switch
are unit mounted in a common electrical junction box.
Package 24-L includes Model TF103 2-pipe thermostat
and standard 3-speed switch, plus automatic changeover for
mounting on supply pipe.
Package 24-M and 24-N include Model TF103 2-pipe thermostat and standard 3-speed switch only.
Package 24-P includes Model TH104 4-pipe thermostat
and standard 3-speed switch. May be used on 4-pipe systems with electric valves or on 2-pipe systems with total electric heat.
Package 24-Q includes Model TH104 4-pipe thermostat,
standard 3-speed switch and 2 automatic changeover switches
for 2-pipe systems with auxiliary electric heat.
* Packages listed on current price pages.
12
T wo-PipeThermostat,Model TF103 — This single-
pole, double-throw (SPDT) thermostat has snap-action contacts. The standard temperature range is 60 - 90 F.
Four-Pipe Thermostat,Model TH104 — With this
thermostat, heating and cooling are sequenced (automatic
changeover) with 6 degree separation between HEATING
ON and COOLING ON. The standard temperature range is
60-90F.
Thermostat Electrical Data
(Pilot Duty — 125 VA at 120-277 v)
ITEMVOLTSFLALRA
TF103
and
TH104
1201680
2401260
2771050
Automatic Changeover (Summer-Winter Switch) —
The automatic-changeover thermostat is a single-pole doublethrow (SPDT) thermal switch in a moistureproof and dustproof enclosure. Thermostat mechanism and lead ends are
hermetically sealed in a polypropylene enclosure with epoxy resin. Device clamps on coil supply pipe with end snap-on
clip.
The set point temperatures are factory set. When water
temperature rises above 80 F (approximately), the thermostat switches to the winter cycle. When water temperature
drops below approximately 70 F, the thermostat switches to
the summer cycle. Switch reset is automatic.
STEMCO
416-79
L80 8220
AUTOMATIC CHANGEOVER (Summer-Winter) SWITCH
13
BASIC DEFINITIONS
Unit Hand — When facing the supply air outlet from the front of the unit (air blow-
ing in your face), your right hand will be the right hand side of the unit and your left
hand the left hand side of the unit.
Same End Connection (2 Pipe or 4 Pipe) — All piping connections are on the same end (side) of the unit. Controls
and electrical connection will be on the end (side) opposite the piping connection.
Standard 2-pipe units will be the same end connection.
NOTE:
Piping determines the hand of the unit.
Opposite End Connection (4-Pipe Option) — Hot water (HW) piping connections and electrical will be on the end
(side) opposite the chilled water (CW) and drain connections.
NOTE:
Chilled water piping determines the hand of the unit.
Valve Packages For 2-Pipe Systems — Valve packages for standard 2-pipe
units are piped for same end connection (L.H. or R.H.).
Valve Packages for 4-Pipe Systems - Select 2 valve packages per unit.
NOTE:
Hot water valve package requirements may not be the same as chilled water valve package!
14
Hydronic Coil Arrangement
FIELD PIPING CONNECTIONS*
VERTICALFLOOR UNITS — 42VB, VE, VF
Pipe into cabinet end compartment
(opening in bottom and back).
VERTICAL FLOOR UNITS — 42VA, VC
Pipe to external connections (no cabinet).
CEILING UNITS (EXPOSED) — 42CG, CK,
DE, DF
Pipe through knock-outs in rear of cabinetto
coil and valve package connections.
CEILING UNITS (CONCEALED) — 42CA,
CE, CF, DA, DC
Pipe to connections extending from end of
unit.
VERTICAL UNITS — 42DD
Pipeto stub connectionsextending from side
of unit.
HORIZONTAL AIR HANDLERS (BELT
DRIVE) — 42BH
Pipe to stub connections extending through
side of unit.
Valvepackages arenot factory supplied with
these units.
WALL UNITS, FURRED-IN
Pipe to stub connections at the side of unit.
or into optional piping compartment. Op-
tionalpiping compartmentis required if valves
are factory installed. Factory installed valve
packageis limited toone 2-way or 3-way motorized valve and 2 hand valves.
*Locationof field pipingconnections will vary depending on number of coil rows on factory-
supplied coil or arrangement of factory-supplied valves.
15
VALVE PACKAGES
General —
installation on 42 series fan coil units. There are limitations
on physical size of pneumatic valves, quantity and type of
matching components, required control interface. See Fig. 1
for symbols and placement of valves.
Consult factory before ordering any special valve pack-
age components that are not covered in this book.
Table 1 lists acceptable pneumatic valves for
Valve packages are shipped with the units or in unit cartons. Valve packages include belled ends for field soldering
to coil connections.
All factory-furnished cooling valve packages are arranged to position as much of the package as possible over
an auxiliary drain pan or drip lip. This helps minimize field
piping insulation requirements.
Fig. 1 — Symbol And Placement Of Valves
16
LEGEND For Fig. 1
1
Component Sizing —
⁄29 nominal (for5⁄89 OD copper tubing) or3⁄49 nominal (for7⁄89 OD copper tubing).
Manual Air Vent — Standard component - Brazed into high point of hydronic cooling and/or heating coil circuit.
Automatic Air Vent — Brazed into high point of coil circuit.
Coil Connections (Positions A & B) — When isolation valve only is added to supply or return line, the isolation valve
will be factory brazed to the coil stub-out. Addition of any other component or connection to the supply or return line
will change the respective coil connection(s) to one of the following:
STANDARD: Swage fitting for field braze.
OPTION: Union(s) added by factory for field connection.
Service Fittings (PositionsC&D)—Optional fittings for attaching pressure/temperature sensing devices to obtain
pressure drop or temperature differential accross coil. Used with ball valve or balance valve where extremely accurate
water flow balancing is required.
GAGE COCK: Pressure test only - In supply and return lines.
PRESSURE TEST PORT: Pressure test only - In supply and return lines.
INSERTION TEST PORT: Pressure/Temperature test - In supply and return lines.
Water Flow Balancing (Positions E, F, & H) — Only one device per total valve package to be used for balancing
water flow through the coil. When isolation valve (ball valve or ball valve with memory stop at position H) is used for
water flow balancing, do not specify additional balancing device at position E or F. When balancing device is specified
at position E or F, isolation valve does not require balancing feature at position H (See exception, 3-way motorized
valve).
CIRCUIT SETTER: May serve as a positive shut-off valve in lieu of isolation valve at position H
(check service requirements).
BALANCING VALVE: Check specifications for service fitting requirements.
FIXED FLOW: No balancing required - When there are more devices on the supply line of the valve
package than on the return line, the factory may move this device to position E to fit valve package
within allotted space. Consult your factory representative to match the available fixed flow valve to your
job requirements.
Strainer (Position G) — Does not include blow down fitting and should not be used in lieu of main piping strainers.
Isolation Valves (PositionsH&J)—Normally requires one each on supply and return line (see exception under
circuit setter). When position H is used for balancing (ball vall or ball valve with memory stop), check specifications for
service valve requirements.
GATE VALVE: Shut-off only - Do not use for balancing.
BALL VALVE: Shut-off/balance - No memory stop.
BALL VALVE WITH MEMORY STOP: Shut-off/balance - Memory stop allows re-opening to balance point
after usage as a shut-off.
17
VALVE PACKAGES (cont)
Two-Way Motorized Control Valve
The 2-way motorized valve motor drives valve open
and a spring returns valve to normally closed position
(no water flow with unit OFF).
Supplyconnection at coil will beswage fit forfield braze
(standard) or union (option). Return connection at coil
will be factory brazed if isolation valve only. Addition of
anyother component willrequire swage fit for field braze
or optional union connection.
Check job specifications for system pressure, pressuredrop limitations and flow rateprior to selectingvalve
package components or valve package size (
etc.).
2-PIPE SYSTEM (One ValvePackage) or 4-PIPE SYSTEM (Two Valve Packages) Application:
• 2 Pipe - Hydronic Heating Only
• 2 Pipe - Hydronic Cooling Only
• 2 Pipe - Hydronic Cooling with Total Electric Heat
• 4 Pipe - Hydronic Cooling and Heating
1
NOTE:A
⁄4-in.bypass line is included inthe piping packagewhen a 2-way valve is specified witha control package containing an automatic changeover device.
1
⁄29,3⁄49,
Two-Way Motorized Control Valve with
Aquastat Bleed Bypass Line
The 2-way motorized valve motor drives valve open
and a spring returns valve to normally closed position
(no water flow through coil with unit OFF).
The aquastat bleed bypass bleeds a small amount of
water from supply to return when control valve is closed
(requiredfor systemwater temperature sensing by aquastat). Aquastat (A) clips on supply line upstream from
aquastat bleed bypass (as shown at right). It senses
system water temperature to prevent cooling operation
withhot water in system piping or heatingoperation with
chilled water in system piping. Additional aquastat requiredto lock out the optionalauxiliary electricheat when
hot water in system.
Supply and return connections at coil will be swage fit
for field braze (standard) or unions (option).
Check job specifications for system pressure, pressuredrop limitations and flow rateprior to selectingvalve
package components or valve package size (
etc.).
2-PIPE SYSTEM (One Valve Package) Application:
• 2 Pipe - Hydronic Cooling and Heating
• 2 Pipe - Hydronic Cooling and Heating with Auxiliary
Electric Heat
NOTES: Additional aquastat required as noted above.
1
⁄29,3⁄49,
18
Three-Way Motorized Control Valve
On the 3-way motorized valve flow is normally closed
to coil and open to system return. Motor closes bypass
flow to system return while opening flow through coil.
Waterbypasses coil and flows directly to system return
when unit is OFF.
The aquastat (A) clips on supply line upstream from
3-way valve (as shown above). It senses system water
temperature to prevent cooling operation with hot waterin system piping or heating operation withchilled waterin system piping.Aquastat(s) requiredfor 2-pipe cooling
and heating with automatic changeover control and/or
auxiliary electric heat.
A bypass balancing valve may be specified in the bypass line to permit equal flow balancing.
Supply and return connections at coil will be swage fit
for field braze (standard) or unions (option).
Check job specifications for system pressure, pressuredrop limitations and flow rateprior to selectingvalve
package components or valve package size (
etc.).
2-PIPE SYSTEM (One ValvePackage) or 4-PIPE SYSTEM (Two Valve Packages) Application:
• 2 Pipe - Hydronic Heating Only
• 2 Pipe - Hydronic Cooling Only
• 2 Pipe - Hydronic Cooling with Total Electric Heat
• 2 Pipe - Hydronic Cooling and Heating
• 2 Pipe - Hydronic Cooling and Heating with Auxiliary
Electric Heat
• 4 Pipe - Hydronic Cooling and Heating
1
⁄29,3⁄49,
No Motorized Control Valve
When isolation valves only are specified, they will be
brazed to the coil stub-outs.
Check job specifications for system pressure, pressuredrop limitations and flow rate prior toselecting specific components or valve package size (
2-PIPE SYSTEM ONLY (One Valve Package)
Application:
• 2 Pipe - Hydronic Heating Only
• 2 Pipe - Hydronic Cooling Only
NOTES:
1. Continuous water flow, chilled water or hot water.
2. Not recommended for high humidity applications.
3. Not recommended with unit-mounted thermostat on
vertical units (except package R).
4. The addition of any other component(s) will require
swage fitting for field braze or optional union conection.
1
⁄29,3⁄49, etc.).
19
VALVE PACKAGE ARRANGEMENTS
20
LEGEND
— Ball Valve
— Ball Valve with Memory Stop
— Gate Shut Off Valve
— Balancing Valve
— Circuit Setter
— Motorized 2-Way Valve
— Motorized 3-Way Valve
* When aquastat is used for automatic changeover, bypass is re-
quired as indicated by dashed line.
NOTES:
1. Packages factory furnished and installed.
2. Valves are
3. If an automatic flow control valve is added, it will be located on
supply line between shutoff valve and coil (or motorized control
valve, if supplied).
*Valve packages listed on current price pages.
NOTES:
1. Pneumatic valves are field furnished for factory installation.
2. To simplify valve installation and maintenance, cabinet units with
4-pipe coils must have opposite-end connections.
3. Alternate designations for the terms N.O., N.C. and RETURN on
3-way valves are as follows:
ManufacturerN.O.N.C.Return
Barber-ColemanBAAB
HoneywellBAAB
Johnson ServiceN.O.N.C.C
PowersBUC
4. All orders entered must include a job specific piping diagram OR
reference can be made to standard arrangements 18-A through
18-E as shown here.
5. Hand valves shown in Arrangements 17-A through 17-F may be
included with pneumatic valves. These arrangements should also
be shown on piping diagrams submitted.
CV— See Note 5.
N.C. — Normally Closed
N.O. — Normally Open
OD — Outside Diameter
NOTES:
1. This reference table lists valves that are acceptable because of
capacityand piping connection type.Actualvalve selection for specific mode (N.O. or N.C.) and capacity rating (CV) to meet jobsite
conditions must be made by field personnel.
2. Valve size (
ing size.
Use price page package 18-2 or 18-4 for selecting
OD valves. Use price page package 18-3 or 18-5 for7⁄8-in. OD
valves.
3. The
and 42V (vertical) room fan coil units. The7⁄8-in. OD valves are
recommended for use on 42D (ducted) units.
4. Flare connections are 45° SAE flare with body threaded for standard flare nuts.
1
⁄2-,5⁄8-, and7⁄8-in. OD) designates the matching tub-
1
⁄2-in. or5⁄8-in.
1
⁄2-in. and5⁄8-in. OD valves are usedprimarily on 42C (ceiling)
SIZE (in.)
(OD Male Flare)
7
⁄
8
5
⁄8or7⁄
8
5
⁄
8
1
⁄
2
5
⁄8or7⁄
8
5
⁄
8
5
⁄8or7⁄8(ODS)1.6, 2.6, 3.3
1
⁄
2
5
⁄
8
1
⁄
2
5
⁄
8
1
⁄
2
1
⁄
2
5
⁄
8
5
⁄
8
5
⁄
8
5
⁄
8
1
⁄
2
1
⁄
2
1
⁄
2
1
⁄
2
1
⁄
2
1
⁄
2
1
⁄
2
1
⁄
2
1
⁄2,5⁄
8
1
⁄
2
1
⁄
2
5
⁄
8
1
⁄2,5⁄8,7⁄
8
5. The CVcapacity rating is the gpm flow through a valve at 1.0 psi
pressure drop.
EXAMPLE: A 2.5 CVvalve has a flow of 2.5 gpm at 1.0 psi pressure drop.
As flow changes, pressure drop can be determined by the
formula:
Actual gpm
P=
6. Restrictions imposed by limitedpiping enclosures often require that
thevalve manufacturer’s recommendation for obstruction free service clearances be waived. Service/isolation valves normally specified will permit removal ofthe entire pneumatic valve for field service if necessary.
7. Certain combinations of pipingaccessoriesand control valves have
proven unacceptable in the past, therefore the factory must reserve the right of review for final acceptance.
8. Consult factory on all applications involving valves with thermostatic actuators or built in pneumatic thermostats.
C
2
V
CAPACITY
(CV) RATING
3.0, 4.0, 6.3
1.6/2.5 or 2.5/3.5/4.0
1.6, 2.5
0.63, 1.0, 1.6
2.5, 4.0
1.0, 1.6, 2.5
1.2, 2.0
4.7
1.4, 2.4
4.1, 4.7
1.0, 1.7, 3.2
1.7, 3.2
2.0, 4.0
1.7, 2.4, 4.0
0.4, 1.3, 2.2, 3.3
0.4, 1.3, 2.2, 3.3
1.5, 2.5
2.5
1.5, 2.5
1.0, 2.5
0.9, 2.1
2.1
0.4, 0.6, 1.0, 1.6
1.6
1.2, 2.2, 4.1
1.0, 1.6
1.6
2.5
.6, 1.0, 1.1, 1.6,
2.5, 3.2, 2.4, 4.0, 4.5
23
PIPING COMPONENTS
SYMBOL/SKETCHDESCRIPTION
MANUAL AIR VENT: Threaded brass
needle valve with screwdriver slot
for adjustment.
Application - Body brazed into high
point of heating and cooling coils for
bleeding air from coil. Standard item
on all hydronic coils (not used on
steam or DX coils). Should not be used
in lieu of main system air vents.
AUTOMATIC AIR VENT: Nickel
plated brass valve, fiber-disc type, with
positive shut-off ballcheck and quick
vent feature via knurled vent screw.
Application - Optional replacement for
manual air vent. Automatically passes
minute quantities of air through the
fiber discs which expand upon contact
with water, completely sealing the
valve. As air accumulates, the fiber
discs dry and shrink, repeating the
cycle. Not recommended for removing
large quantities of air encountered
during initial start-up or subsequent
draining and refilling. Should not be
used in lieu of main system air vents.
SWAGE: Copper tube end expanded
to accept a copper tube of the same
size for factory or field brazing.
Application - Used where possible for
all tubing joints for best joint integrity.
(*) See page 30 for ratings of different
joining materials and operating
temperatures.
UNION: Combination wrought
copper/cast brass union assembly,
solder by solder.
Application - Used for quick connect
(and disconnect) of valve package
components to minimize field labor
and facilitate servicing of unit.
(*) See page 30 for ratings of different
joining materials and operating
temperatures.
INSERTION TEST PORT: Brass body
valve for acceptance of test probe (up
1
to
⁄8in. diameter).
Application - Installed on one (or both)
sides of the coil to allow for temperature
or pressure sensing. Used for close
tolerance water balancing and
service analysis.
CVFACTORRATING
1
⁄
2
3
⁄
4
PSIF
STEAM
USE
N/AN/A400100NO
N/AN/A125240NO
N/AN/A
N/AN/A
300
(*)
300
(*)
200
(*)
200
(*)
YES
YES
N/AN/A250250NO
24
SYMBOL/SKETCHDESCRIPTION
PRESSURE TEST PORT: Brass body
1
⁄4service access fitting with
removable depressor type core.
Application - Installed on both sides of
the coil to allow for pressure sensing.
Attach pressure gages to facilitate
close tolerance water balancing.
GAGE COCK: Brass shut-off valve
1
with
⁄4FPT fitting for attachment of
pressure gages.
Application - Installed on both sides of
the coil to allow for pressure sensing.
Attach pressure gages to facilitate
close tolerance water balancing. May
be used in bleed bypass line to
regulate water flow.
CIRCUIT SETTER: Variable water
B+G
flow balancing valve with manual
adjustment knob, pointer, percent-open
scale, memory stop and integral
pressure read-out ports.
Application - Used for close tolerance
water flow balancing. Positive shut-off
ball valve feature allows usage as combination balancing and shut-off valve.
BALANCE VALVE: Variable water
flow manual balancing valve with
screwdriver slot adjustment screw.
Application - Often used in conjunction
with test port fittings for water flow
balancing. Balance by temperature
differential or coil pressure drop (check
specifications for service fittings
required if balancing by pressure drop).
May be used in 3-way valve bypass
line to permit equal flow balancing.
FLOW SETTER: Variable water flow
manual balancing valve with
screwdriver slot adjustment and direct
gpm read-out sight glass.
Application - Used for water flow
balancing (8.0 gpm maximum).
FIXED FLOW VALVE: Spring and
insert type (non-adjustable).
Application - Used for water flow
balancing. Valve automatically adjusts
the flow to within 10% of set point. Not
available for flow rates above 8 gpm.
FIXED FLOW VALVE: Flexible orifice
HAYES
type (non-adjustable).
Application - Used for water flow
balancing. Valve automatically adjusts
the flow to within 10% of set point.
Requires 15 psi (35 ft) of additional
pump head for proper operation.
CVFACTORRATING
1
⁄
2
3
⁄
4
PSIF
N/AN/A400210NO
N/AN/A200250N/A
1.954.15200250NO
3.08.9150200NO
2.25.4125210NO
Valve orifice size
determines C
factor. The orifice
of these fixed flow
V
125240NO
valves changes as
flow is regulated.
As the water
pressure increases,
the orifice size
decreases, thereby
automatically
limiting the flow
150160NO
rate to the
specified gpm
(+/210%).
STEAM
USE
25
PIPING COMPONENTS (cont)
SYMBOL/SKETCHDESCRIPTION
STRAINER: Y-type body with
50 mesh stainless steel screen.
Application - Used for removal of small
particles from system water during
normal system operation. Should not
be used in lieu of main system
strainers. Strainer screen may have to
be removed during initial high pressure
system flushing during start-up.
Screen should be removed and cleaned
per normal maintenance schedule
(provisions for strainer blow-down
not provided).
GATE VALVE: Manual shut-off valve.
Application - Used for unit isolation
during system flushing, servicing, etc.
Do not use for water balancing.
GLOBE VALVE: Standard pattern,
manual shut-off and throttling valve.
Application - Used for unit isolation.
Not recommended for high flow rates
due to relatively high pressure drop.
COMPRESSION STOP VALVE:
Manual shut-off valve.
Application - Used for unit isolation
during system flushing, servicing, etc.
Not recommended for high flow rates
due to relatively high pressure drop.
BALL VALVE: Manual balance and
shut-off valve.
Application - Used for unit isolation
and water flow balancing. Without
memory stop feature water balance
point must be marked by installer (if
necessary). Check specifications for
service fittings required when used for
water balancing.
BALL VALVE WITH MEMORY STOP:
Manual balance and shut-off valve.
Application - Used for unit isolation
and water flow balancing. The adjustable memory stop feature allows return
to the balance point after shut-off.
Check specifications for service
fittings required when used for
water balancing.
CVFACTORRATING
1
⁄
2
9.0
Clean
3
⁄
4
19.0
Clean
PSIF
400250N/A
STEAM
USE
19.836.0200200NO
1.83.9200200NO
2.35.4150200NO
4.07.5400200YES
4.07.5400200N/A
26
SYMBOL/SKETCHDESCRIPTION
2-WAY MOTORIZED VALVE: Electric
2-position flow control valve
(open/closed). Normally-closed body
with manual override lever. Installed in
supply line to unit.
Application - All standard control and
valve packages are based upon
normally-closed valves (valve
electrically powered open and closed
by spring return when electric power
removed). Manual override lever allows
valve to be placed in the open position
for secondary (unit) flushing, constant
water flow prior to start-up, etc.
Manual override is automatically
disengaged when valve is electrically
activated. Consult factory for
normally-open valve applications.
3-WAY MOTORIZED VALVE: Electric
2-position flow control valve (closed to
coil/open to bypass or open to coil/
closed to bypass). Normally-closed
with manual override lever. Installed in
supply line to unit.
Application - Same comments as
2-way motorized valve except with
manual override lever engaged the
valve is open to both ports and water
flow will take the path of least
resistance through the valve package
(not necessarily 100% through the coil).
2-WAY PNEUMATIC VALVE:
Pneumatic operated 2-way
control valve.
Application - Specified and supplied by
others when required as part of a
factory-assembled valve package.
See Table 1 for approved listing of
pneumatic valves suitable for
installation on various unit models.
3-WAY PNEUMATIC VALVE:
Pneumatically operated 3-way
control valve.
Application - Specified and supplied
by others when required as a part of a
factory-assembled valve package.
See Table 1 for approved listing of
pneumatic valves suitable for
installation on various unit models.
AQUASTAT: Water temperature
sensing electrical switch.
Application - Clips directly on nominal
1
⁄29 or3⁄49 copper tubing for
size
water temperature sensing. Must be
correctly located for proper control
operation.
NOTES:
1. Motorized 2-way valves have a maximum close-off differential of 25 psi.
2. Motorized 3-way valves have a maximum close-off differential of 10 psi.
FACTORRATING
C
V
1
⁄
2
3
⁄
4
PSIF
2.32.3300200
5.05.0
SERVICE
300200N/A
2.82.8
BYPASS
SPECS VARY WITH SUPPLIER
SPECS VARY WITH SUPPLIER
STEAM
USE
YES
15
PSI
MAX.
27
CVFACTOR vs WATER PRESSURE DROP
CVFACTOR:
The flow rate in gallons per minute (gpm) through a piping component when the pressure drop (DP) in pounds per
square inch (psi) across the component is 1.0 (psi).
Pressure drop (ft-H
O) = 2.31 x psi (pressure drop)
2
GRAPH EXAMPLE:
DP for 2.0 gpm through a component with a C
of 1.0 is 4.0 psi x 2.31 = 9.24 ft-H2O
V
FORMULA EXAMPLE:
DP (ft-H2O) =
(gpm)
(C
)
v
2
2
x 2.31 =
(2.0)
(1.0)
2
x 2.31 = 9.24 ft-H2O
2
TOTAL PRESSURE DROP is the Sum of the pressure drop of all piping and components in the water flow path.
28
29
COPPER WATER TUBE AND JOINT MATERIAL PRESSURE RATINGS
JOINT MATERIALS
A50-50 Lead-Tin at 200 F
B50-50 Lead-Tin at 150 FE95-5 Tin-Antimony at 150 F
C50-50 Lead-Tin at 100 FF95-5 Tin-Antimony at 100 F
Note 1
D95-5 Tin-Antimony at 200 F
Note 2
1. Not recommended for high system water pressures.
2. Standard factory joint material.
THE ABOVE CHART IS FOR REFERENCE ONLY: Check all system component pressure ratings (coils, valves, pumps, etc.)
and any applicable local or national piping codes prior to specifying system pressure rating.
30
CORRECTION FACTORS FOR GLYCOL
(Equivalent water flow method for all 42 Series Models)
This method allows you to calculate cooling and heating performance without adjusting capacities for glycol
concentration.
After completing the standard selection procedure including water flow rates, use the correction multiplier shown below
to determine new (equivalent) flow rates required for the specified glycol concentration.
EXAMPLE:
COOLING PERFORMANCE REQUIRES 3.0 gpm of 100% WATER.
What flow rate of 30% glycol by voume will be required to match the cooling performance? Referring to the
chart above, you will note that the cooling flow rate multiplier for 30% glycol is 1.14.
100% WATER (3.0 gpm) x 1.14 = 3.42 gpm of 30% GLYCOL (EQUIVALENT FLOW RATE)
What will the new pressure drop be for 3.42 gpm of 30% glycol? Referring to the chart above, you will note
that the cooling pressure drop multiplier for 30% glycol is 1.27.
(A) Obtain pressure drop for 3.42 gpm of 100% water.
(B) Multiply (A) times 1.27 to obtain pressure drop for 3.42 gpm of 30% glycol.
31
Table 2 — Standard Accessories and Options
STANDARD ACCESSORIES
AND OPTIONS
CABINET CHANGES
Front Panel, 16 Gage••
Extended Cabinet when electric
heat or valves are installed
Valve Compartment Extension, 10 in.•
Stamped Toe Space Return Grille••