Carrier 40VM Series Installation And Operating Instructions Manual

BUTTON DESCRIPTION
1. Left button/ ROOM TEMP button
Selects options to the left / Checks the room tempera­ture.
2. MODE
Selects the running mode.
3. TEMP . UP button
Increases the set temperature/Selects upward options.
4. ON/OFF button
Powers the IDU (Indoor Unit) on/off.
5. LED
Stays solid green when the unit is powered on and blinks if there is a fault.
6. TIMER button
Opens timer settings.
7. Right button/ SWING button
Selects options to the right / Sets the swing location and starts automatic swing.
8. OK button
Confirms the selection.
9. TEMP. DOWN button
Reduces the set temperature / Selects downward options.
10. FAN
Selects the fan speed.
Fig. 1 — Button Description
40VM Series Indoor Fan Coils
VRF (Variable Refrigerant Flow) System
Wired Remote Controller (Non-Programmable) Accessory

Installation and Operating Instructions

Part Number 40VM900002

CONTENTS

Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1, 2
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3,4
OPERA TION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-11
ON/OFF Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Setting the Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Fan Speed Setting . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Temperature Setting . . . . . . . . . . . . . . . . . . . . . . . . 4
Automatic ON/OFF Settings . . . . . . . . . . . . . . . . . . 5
Swing Setting for Louvers . . . . . . . . . . . . . . . . . . . 6
Room Temperature Display . . . . . . . . . . . . . . . . . . 6
Locking the Controller. . . . . . . . . . . . . . . . . . . . . . . 6
Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . 7
Query Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Error Code Display . . . . . . . . . . . . . . . . . . . . . . . . 11

SAFETY CONSIDERATIONS

Read and follow manufacturer instructions carefully. Fol­low all local electrical codes during installation. All wiring must conform to local and national electrical codes. Improper wiring or installation may damage thermostat.
Understand the signal words — DANGER, WARNING, and CAUTION. DANGER identifies the most serious hazards, which will result in severe personal injury or death. WARNING signifies hazards that could result in personal inju­ry or death. CAUTION is used to identify unsafe practices, which would result in minor personal injury or product and property damage.
Recognize safety information. This is the safety-alert symbol ( ). When this symbol is displayed on the unit and in instructions or manuals, be alert to the potential for personal injury. Installing, starting up, and servicing equipment can be hazardous due to system pressure, electrical components, and equipment location.
Table 1 — Wired Controller Accessory Usage
UNIT SIZES 40VMC Compact Cassette Indoor Unit 40VMF 4-Way Cassette Indoor Unit 40VMH High Static 40VML Low Static Ducted Indoor Unit 40VMM Medium Static Ducted Indoor
Unit 40VMR Floor Console - Recessed
Indoor Unit 40VMU Under Ceiling/Floor Indoor
Unit 40VMV Vertical AHU Fan Coil 40VMW High Wall Indoor Unit
007, 009, 012, 015 009, 012, 015, 018, 024, 030, 036, 048 024, 030, 036, 048, 054, 072, 096 007, 009, 012, 015, 018, 024 007, 009, 012, 015, 018, 024, 030, 036,
048 007, 009, 012, 015, 018, 024
012, 018, 024, 030, 036, 048
018, 024, 030, 036, 048, 054 007, 009, 012, 015, 018, 024, 030
The VRF (variable refrigerant flow) wired non-programma­ble controller is a wall-mounted, low-voltage thermostat that maintains room temperature by controlling system operation. The controller, which does not require batteries, is capable of displaying temperatures from 54
The wired non-programmable controller accessory is avail­able for use with the VRF (variable refrigerant flow) indoor units listed in Table 1. Figure 1 shows a description of the but­tons used on this controller. Figure 2 shows a description of the screen icons.
Manufacturer reserves the right to dis continue, or change at any time, specifications or designs without notice and without incurring oblig ations.
Catalog No. 16-40VM9002-01 Printed in U.S.A. Form 40VM-1SI Pg 1 12-16 Replaces : New

GENERAL

ºF to 86ºF.
DISPLAY ICON DESCRIPTION
1. Set Temp for Cooling Displays the set temperature for cooling on the wired controller.
2. IDU Address Displays the IDU (Indoor Unit) address when the IDU is in error or query status.
3. Set Time Displays the automatic on/off set time. For example, “10H” indicates that the unit will automatically
turn on/off in 10 hours.
4. Set Temp. for Heating Displays the set temperature for heating on the wired controller.
5. Room Temp Display Icon Displayed on when the wired controller displays the indoor temperature.
6. Reserved Icon Reserved icon (not used).
7. Central/Upper Controller Lock Icon Displayed when the upper computer/central controller locks the IDU functions and the wired control-
ler cannot be used for these functions.
8. Group Control Icon Displayed when the wired controller controls multiple IDUs (max 16 IDUs).
9. Function Lock Icon Displayed when the wired controller locks the on/off function, mode, or temperature setting.
10. Vertical Swing Icon Displays vertical swing status when the IDU supports vertical swing.
11. Invalid Operation Prompt Displayed for two seconds if an operation is invalid.
12. Automatic Off Icon When this icon is displayed, the automatic-off function is set.
13. Operating Icon Displayed when the unit is powered on and operating.
14. Automatic On Icon When this icon is on, the automatic-on function is set.
15. Operating Fan Speed Displays the fan speed set by the wired controller.
16. Operating Mode Icons Displays the running mode set by the wired controller.
Fig. 2 — Display Description
2

INSTALLATION CONSIDERATIONS

Fig. 3 — Opening Back Mounting Plate
Fig. 4 — Attaching Back Plate
Fig. 5 — One-to-One Control Connection
Fig. 6 — Group Controller Connection
The thermostat should be mounted:
• approximately 48 in. from the floor
• on a section of wall without water or drainage pipes The thermostat should NOT be mounted:
• where it can be directly affected by the unit’s discharge
airflow
• close to a window, on an outside wall, or next to a door
leading to the outside
• near shelves or curtains that may restrict air movement
• near heat sources such as direct sunlight, heaters, dimmer
switches, and other electrical devices

INSTALLATION

Perform the following procedure to install the thermostat:
1. Turn off all power to the indoor unit.

WARNING

Electrical shock can cause personal injury or death. Before installing thermostat, shut off all power to this equipment during installation. There may be more than one power dis­connect. Tag all disconnect locations to alert others not to restore power until work is completed.
6. Insert a flat-head screwdriver into the slots provided on the bottom of the controller to pop open the back mount­ing plate. See Fig. 3.
7. Provide a 1-in. by 1-in. square opening in the wall where the controller will be mounted to accommodate the control cable.
8. Attach the back mounting plate directly over the opening using 2 screws, and route the control cable as shown in Fig. 4.

CAUTION

Over-tightening the screw will cause deformation to the rear cover and LCD damage.
2. If an existing thermostat is being replaced: a. Remove existing thermostat from wall or unit. b. Disconnect wires from existing thermostat. Do not
allow wires to fall back into the wall or unit.
c. Discard or recycle old thermostat.

CAUTION

Failure to follow this caution may result in equipment dam­age or improper operation.
Improper wiring or installation may damage the thermo­stat. Check to make sure wiring is correct before proceed­ing with installation or turning on unit.
3. Use 16 to 20 AWG (American Wire Gage), stranded twisted pair shielded 2-core wiring. Be sure the distance between the controller and the indoor units is not more than 820 ft.
4. For exposed wall-hung or under-ceiling/floor units, pro­vide a 1-in. by 1-in. square opening in the surface behind the unit to route the shielded 2-core control cable, furred in to connect the indoor unit display panel to the controller.
5. For concealed ducted, high-static ducted, cassette, or ver­tical units, the shielded 2-core cable can be routed through the plenum and the wall to connect the indoor unit display panel and the controller.
9. Connect one end of the shielded 2-core control cable to the indoor unit HA/HB terminal on the unit and other end to the controller HA/HB terminal. Connect the shield/ drain conductor of the control wire to ground at the in­door unit as shown in Figs. 5 and 6; do not connect shield/ drain conductor at the controller. For connecting the con­troller to a single indoor unit see Fig. 5. For connecting the controller to multiple indoor units see Fig. 6.
3
10. Mount the controller back onto the mounting plate. See
Fig. 7 — Mounting Controller
Fig. 8 — IDU Operating icon and LED
Fig. 9 — Sequence of Functions
Fig. 10 — Fan Speed Sequence
Fig. 11 — Setting the Temperature
Fig. 12 — Setting Cooling Temperature
Fig. 7.

Fan Speed SettingIn AUTO, cooling, heating, or

fan-only mode, press F AN to change the fan speed.
Pressing FAN changes the setting in the following cycle: automatic air flow , low air flow, medium air flow, high air flow as shown in Fig. 10.

OPERATION

ON/OFF Setting

IDU (indoor unit) on/off.
When the IDU is powered on, the wired controller’s Operat-
ing icon and LED turn on at the same time as shown in Fig. 8.
Press the ON/OFF button to turn the

Temperature SettingIn AUTO, cooling, DRY, or

heating mode, press TEMP. UP or TEMP. DOWN to adjust the temperature as shown in Fig. 11.
When adjusting the set temperature in AUTO mode, press TEMP. UP or TEMP. DOWN and then the “Cool” icon blinks.
Then, press TEMP. UP or TEMP. DOWN to set the cooling temperature in AUT O mode as shown in Fig. 12.

Setting the ModePressing MODE once or more than

once sets functions in the sequence shown in Fig. 9.
IMPORTANT: When the wired controller is connected to a heat pump system, AUTO mode is unavailable. Fan speed cannot be adjusted in DRY mode.
4
Press the left or right button within 3 seconds to switch be-
Fig. 13 — Switching Between Cooling and
Heating
Fig. 14 — Entering the Automatic-on Menu
Fig. 15 — Adjusting the Automatic-on Time
Fig. 16 — Confirming the Automatic-on Time
tween the set temperature for cooling and heating in AUTO mode as shown in Fig. 13.
The set temperature range for cooling and DRY mode on
the wired controller is 62
ºF to 86ºF.
The set temperature range for heating on the wired control-
ler is 54
ºF to 86ºF.

Automatic ON/OFF SettingsPress the TIMER

button to enter automatic-on settings. The screen displays the timer, and the automatic-on icon is on as shown in Fig. 14.
Press TEMP. UP or TEMP. DOWN within 3 seconds to ad-
just the automatic-on time as shown in Fig. 15.
If you press OK or do not press any button within 3 sec­onds, the wired controller will confirm the set time and exit the automatic-on/off setting status as shown in Fig. 16.
When the automatic-on time is set to a value other than 0.0H, the automatic-on setting is valid and the IDU will be turned on at the set time.
When the automatic-on time is set 0.0H, the automatic-on setting is canceled.
Press TIMER twice on the main interface to enter automatic off settings. The screen displays the timer, and the automatic­off icon is on.
5
NOTE: When the set automatic-on/off time is less than 10
Fig. 17 — Setting the Swing
Fig. 18 — Swing Sequence
Fig. 19 — Displaying the Indoor Temperature
Fig. 20 — Default Display When in Standby Mode
hours, the value will be increased or decreased in units of
0.5 hour. When the set automatic-on/off time is greater than 10 hours, the value will be increased or decreased in units of 1 hour.
NOTE: Automatic-on and automatic-off can be set at the same time. When the automatic-on time is equal to the auto­matic-off time and the two are smaller than 10 hours, the automatic-off time will be delayed for 0.5 hour. If the two equal or exceed 10 hours but are less than 24 hours, the automatic-off time will be delayed for 1 hour. If the two are equal to 24 hours, the automatic-on time will be put forward 1 hour.
NOTE: After automatic-on or automatic-off is set, the auto­matic-on/off setting will be canceled when you press ON/ OFF to turn the unit on/off.
Automatic-off and automatic-on are set in the same way.

Swing Setting for Louvers The swing function of

the wired controller is available when the connected IDU has the vertical swing function.
When the IDU is on, press the SWING button to control
vertical swing as shown in Fig. 17.

Room Temperature DisplayWhen the unit is on,

press ROOM TEMP. to view the indoor temperature as shown in Fig. 19.
When the unit is off and in standby mode, the wired control­ler displays the indoor temperature by default as shown in Fig. 20.
When the SWING button is pressed multiple times, it will
follow the cycle as shown in Fig. 18:
The swing function of the wired controller is invalid when the IDU connected to the wired controller does not have the vertical swing function. If you press the SWING button at that time, the screen displays “OPERATION IS NOT AVAIL­ABLE” for 2 seconds.

Locking the ControllerThe locking function can

lock ON/OFF , mode, or temperature setpoint. Refer to Table 2 below. The controller is unlocked by following the same procedures.
Table 2 — Locking Functions
LOCKING FUNCTION OPERATION MODE
Locking / unlocking on / off function
Locking / unlocking mode
Locking / unlocking temperature
Press and hold TEMP. UP and TEMP. DOWN at the same time until the locking icon blinks. Press ON/OFF, MODE, or TEMP. UP/TEMP. DOWN within 15 seconds to
Press TEMP. UP and TEMP. DOWN at the same time, and then press the ON/OFF button within 15 seconds.
Press TEMP. UP and TEMP. DOWN at the same time, and then press the MODE button within 15 seconds.
Press TEMP. UP and TEMP. DOWN at the same time, and then press the TEMP. UP/TEMP. DOWN button within 15 seconds.
6
lock the ON/OFF, mode setting, and temperature setting func-
Fig. 21 — Locking the Controller
Fig. 22 — Entering the Parameter Setting Menu
Fig. 23 — 1G and 2G Code Location
Fig. 24 — Selecting the 1 G Code
Fig. 25 — Selecting the 2G Code
tions, respectively, as shown in Fig. 21.
Once the Locking function is activated for a specific function, pressing the specific button will cause the screen to display "OPERATION NOT AVAILABLE" for 2 sec­onds. The Operating icon and lock icon will then blink for 2 seconds.

Parameter SettingsPress and hold the MODE and

FAN buttons for five seconds to enter the parameter setting mode as shown in Fig. 22.
Parameter settings are classified into 1G code and 2G code. 1G indicates the parameter category, and 2G indicates parame­ter content as shown in Fig. 23.
Press the left/right button to select the 1G code as shown in Fig. 24.
Press TEMP. UP/TEMP. DOWN to select the 2G code as shown in Fig. 25.
7
Press OK or wait 15 seconds to confirm the setting automat-
Fig. 26 — Exiting the Parameter Settings Menu
ically and exit parameter settings (see Fig. 26). Table 3 lists the detailed parameter codes.
The table below lists the detailed parameter codes:
1G code
0
1
2
3
4
5
Parameter category
Selection room temperature sensor
Room temperature sensor temperature compensation of wired controller
Setting the upper limit for heating
Setting the lower limit for cooling
Selecting IDU capacity interval
AUTO mode delay switching time t
2G code
0 Uses room temperature sensor on the IDU.
1 (default)
(0 to 10)
86ºF (default), 85ºF, 84ºF… 30ºC (default), 29ºC, 28ºC…
62ºF (default), 63ºF, 64ºF… 17ºC (default), 18ºC, 19ºC…
0 (default) Thermal on (1ºF/1ºC)
1 Thermal on (2ºF/1ºC)
0 (default) ∆t=15min
1 t=30min
2 t=60min
3 t=90min
Table 3 — Parameter Codes
Description
Uses the room temperature sensor on the wired controller.
Degrees Fahrenheit: 0:-5ºF, 1:-4ºF, 2:-3ºF, 3:-2ºF, 4:-1ºF, 5:0ºF (default), 6:1ºF, 7:2ºF, 8:3ºF, 9:4ºF, 10:5ºF Degrees Celsius: 0:-5ºC, 1:-4ºC, 2:-3ºC, 3:-2ºC, 4:-1ºC, 5:0ºC (default), 6:1ºC, 7:2ºC, 8:3ºC, 9:4ºC, 10:5ºC
Regulates the upper temperature limit for heating; the low temperature limit for heating is 54ºF/12ºC
Regulates the lower temperature limit for cooling; the upper temperature limit for cooling is 86ºF/30ºC.
0 (default) 68ºF/20ºC
Anti-cold wind
6
setting/set the temperature when the heating fan stops
1 50ºF/10ºC
2 59ºF/15ºC
3 75ºF/24ºC
4 82ºF/28ºC
8
0 (default) ∆t=4min
Fan off after a delay
7
8
of t when the unit is off (reserved)
Setting the fan speed in cooling standby mode
1 t=8min
2 t=12min
3 t=16min
0 Turn off the fan
1Low
2 Medium
3 High
E (default) Maintain the current fan speed
9
10
Setting the fan speed in heating standby mode. (Not available for heat pump system)
Setting the IDU static pressure (0 to 25)
0 (default) Turn off the fan
1Low
2 Medium
3 High
E Maintain the current fan speed
0: 0 in WC (default) 1: 0.04 in WC 2: 0.08 in WC 3: 0.12 in WC 4: 0.16 in WC 5: 0.20 in WC 6: 0.24 in WC 7: 0.28 in WC 8: 0.32 in WC 9: 0.36 in WC 10: 0.40 in WC 11: 0.44 in WC 12: 0.48 in WC 13: 0.52 in WC 14: 0.56 in WC 15: 0.60 in WC 16: 0.64 in WC 17: 0.68 in WC 18: 0.72 in WC 19: 0.76 in WC 20: 0.80 in WC 21: 0.84 in WC 22: 0.88 in WC 23: 0.92 in WC 24: 0.96 in WC 25: 1.0 in WC
11
12
OCCUPANCY DELAY of t when nobody is sensed indoors
Setting the opening temperature of dry contact 4; dry contact 4 is opened when the temperature is lower than the set temperature ∆T
0 (default) ∆t=0min
1 t=15min
2 t=30min
3 t=60min 0 (default) T=1ºF/1ºC
1
2
3
4
T=2ºF/1ºC
T=3ºF/2ºC
T=4ºF/2ºC
T=5ºF/3ºC
9
0 (default) Closed in 15 min
Fig. 27 — Manually Set Indoor Unit Addressing
Fig. 28 — Opening the Query Function
Fig. 29 — IDU Address Display
1 Closed in 30 min
2 Closed in 45 min 0 (default) No third-party heat source connected
1 0 Not turn on the fan forcedly
1 (default) Forcibly turn on the fan
0F/0C
2F/1C
4F/2C(default)
6F/3C
8F/4C 0 (default) Invalid
1 Val id
13
14
15
16
17
Delayed closing setting of dry contact 4
Whether the IDU is connected to a third-party heat source
Fan control when the third-party heat source starts
Occupancy set temperature offset
Occupancy delay function

Indoor Unit AddressingEach indoor unit must

have a unique address that can be set from 0-63 for proper system operation.
• Indoor units can be addressed automatically in heat pump systems. Dip switch “S6” in outdoor unit main board to 00 (default set in factory) means auto addressing for each indoor units. When the system is first powered on, this auto addressing process can take approximately 6 minutes or more, depending on the number of indoor units in the system.
• Indoor units can be addressed manually using remote controllers. The whole system, outdoor units, indoor units and MDC are included, and should be p owered on when setting an address by remote controllers. If “FE” displays on LED screen of the controller or display board of indoor unit, there is no address for this unit. After set­ting all indoor units’ addresses, cut off the power supply of indoor units and power on again to clear this error.
T o manually set indoor unit address, press and hold ROOM
TEMP and SWING together for 3 seconds to enter the follow­ing menu. It displays FE# 00 if there is no address for this in­door unit; otherwise it displays current address of the indoor unit. Clicking TEMP.UP or TEMP.DOWN to change 00 to ad­dress number you want to set. Then press OK to confirm and exit the setting interface.
A third-party heat source connected
/
After entering the query function, the wired controller displays the IDU address and the total number of connected IDUs. When the wired controller controls multiple IDUs at the same time, press TEMP. UP or TEMP. DOWN to select IDUs with different addresses as shown in Fig. 29.
Query Function
Press FAN and OK at the same time and hold for 3 seconds to open the query function as shown in Fig. 28. The wired con­troller can query the number of connected IDUs and addresses, IDU sensor T1/T2A/T2B, and error records.
10
Press OK to query the IDU at the current address as shown
Fig. 30 — Querying the IDU
Fig. 31 — Parameter Display
Fig. 32 — Controller Display When in Error
Fig. 33 — Example of an Error Code
in Fig. 30.
Press TEMP. UP or TEMP. DOWN to switch between dif-
ferent parameters to display as shown in Fig. 31.
codes of the wired controller. If an error occurs, the LED and Operating icon blink as shown in Fig. 32.
The wired controller displays the address and error code of the faulty IDU at the same time. Figure 33 shows that an E4 er­ror has occurred on the IDU at address 12. In case of an ODU error, address 0 is displayed along with the ODU error code. Figure 31 shows that an F3 error has occurred at the ODU.
Table 4 below lists the parameter numbers and parameter
information.
Table 4 — Parameter Descriptions
PARAMETER NO. PARAMETER INFORMATION 0 IDU T1 sensor 1 IDU T2A sensor 2 IDU T2B sensor 3 Previous ODU error code 4 Previous IDU error code 5 Previous wired controller error code
LEGEND
IDU Indoor Unit ODU Outdoor Unit
Press F AN to return to the IDU address display and the total number of connected IDUs on the previous row. Press the OK button or wait 15 seconds to exit the parameter query function automatically.

Error Code DisplayThe wired controller can display

the error codes for the IDU (indoor unit) and ODU (outdoor unit) connected to the wired controller, as well as the error
Refer to indoor and outdoor unit installation instructions for a list of their respective error codes. For wired controller error codes, refer to T able 5 below:
Table 5 — Wired Controller Error Codes
CODE DESCRIPTION E9 Wired controller and IDU communication error. E7 Wired controller EEPROM error. FP Overflow of number of online IDUs.
LEGEND
EEPROM — Electronically Erasable Programmable Read-only IDU Indoor Unit
Memory
11
© Carrier C orpora tion 2016
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations .
Catalog No. 16-40VM9002-01 Printed in U.S.A. Form 40VM-1SI Pg 12 12-16 Replaces : New
Loading...