Carrier 40UV075, 40UV050, 40UV125, 40UV100, 40UV200+ Installation, Start-up And Service Instructions Manual

...
Page 1
!
WARNING
This product can expose you to chemicals including Lead, lead compounds, and formaldehyde, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information, go to www.P65Warnings.ca.gov
Ce produit peut vous exposer à des agents chimiques, y compris le plomb et les composes de plomb, et formaldéhyde, identifiés par l’État de Californie comme pouvant causer le cancer et des malformations congénitales ou autres troubles de l’appareil reproducteur. Pour de plus amples informations, prière de consulter www.P65Warnings.ca.gov
!
AVERTISSEMENT
!
ADVERTENCIA
Este producto puede exponerlo a químicos que incluyen plomo y compuestos de plomo, y formaldehído, los cuales son conocidos en el Estado de California como causantes de cáncer y defectos de nacimiento, u otros daños reproductivos. Para mayor información, visite www.P65Warnings.ca.gov
40UV,UH050-200
Unit Ventilators
Installation, Start-Up and Service Instructions
TABLE OF CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . 1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
PRE-INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . 2
Unpack and Inspect Units . . . . . . . . . . . . . . . . . . . . 2
Prepare Jobsite for Unit Installation . . . . . . . . . . . 2
Identify and Prepare Units. . . . . . . . . . . . . . . . . . . . 2
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 1 — Place Units in Position . . . . . . . . . . . . . . 2
Step 2 — Make Piping Connections . . . . . . . . . . . . 9
Step 3 — Make Electrical Connections . . . . . . . . 10
Step 4 — Mount Actuators (Field-Supplied) . . . . 10
Step 5 — Make Duct Connections . . . . . . . . . . . . 30
Step 6 — Make Final Preparations . . . . . . . . . . . . 31
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Periodic Maintenance Checklist . . . . . . . . . . . . . . 32
Preventing Excessive Condensation on Unit . . . 32
Check Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Fan Motor Bearings . . . . . . . . . . . . . . . . . . . . . . . . 32
Fan Shaft Ball Bearing . . . . . . . . . . . . . . . . . . . . . . 32
Clean Fan Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Clean or Replace Air Filters . . . . . . . . . . . . . . . . . 32
ECM Motor Removal and Re-installation . . . . . . . 32
Blower Assembly Section Removal and
Re-installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Coil Assembly Removal and Re-installation . . . . 38
Ball Bearing Replacement . . . . . . . . . . . . . . . . . . . 40
Sleeve Bearing Replacement . . . . . . . . . . . . . . . . 45
Blower Wheel Removal and Re-installation . . . . 47
Damper Section Removal and Re-installation. . . 48
UNIT START-UP CHECKLIST . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of this unit can be hazardous due to system pressure, electrical components and equipment location (such as a ceiling or elevated structure). Untrained personnel can perform the basic maintenance functions of replacing filters. Only trained and qualified service personnel should perform all other operations. See Fig. 1 for Proposition 65 warning label.
When installing this unit, observe precautions in the literature, tags and labels attached to the equipment, and any other safety precautions that may apply.
Follow all safety codes.
Wear safety glasses and work gloves.
Use care in handling and installing this unit and any accessories.
Use quenching cloth for all brazing operations.
Have fire extinguisher available for all brazing operations.
WARNING
Before performing service or maintenance operations, turn off main power switch to the unit. Electrical shock could cause personal injury.
CAUTION
Sharp edges, coil surfaces and rotating fans are a potential injury hazard - avoid contact.
Fig. 1 — Proposition 65 Warning Label
Catalog No. 04-53400048-01 Printed in U.S.A. Form 40UV-UH-11SI Pg 1 8-18 Replaces: 40UV-UH-10SI
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Page 2

INTRODUCTION

This document contains general installation instructions for the 40UV, UH unit ventilators. Refer to the unit wiring diagram or to specific manufacturer literature for any other type of factory­mounted controls.
See submittal drawings for unit configurations, dimensions, clearances, and pipe connections. Refer to unit wiring label for all electrical connections; follow NEC (National Electrical Code) and local codes.

PRE-INSTALLATION

Unpack and Inspect Units

Immediately inspect each unit upon receipt. Remove shipping wraps from all units. Check the shipment against shipping order.
If shipment is damaged or incomplete, file claim with transporta­tion company and advise Carrier immediately.
To prevent handling damage, remove shipping pallet only when within a few feet of final position. Use 2 or more pallet dollies to move units. See Fig. 2.
CAUTION
To prevent handling damage, remove pallet only when within a few feet of final position.

INSTALLATION

CAUTION
Units must be installed level and plumb. Failure to do so may result in excessive vibration and/or premature failure.

Step 1 — Place Units in Position

PLACING VERTICAL UNITS

1. Select the unit location; ensure that service clearance is provided. Allow enough grille clearance to maintain unrestricted airflow. See submittal drawings and Fig. 3 and 4 for dimensions.
2. Make sure wall behind unit is smooth and plumb; if necessary, install furring strips on walls with irregular surfaces or mullions. Furring strips must be positioned behind mounting holes in unit. Fasteners, furring strips, and other seals (if required) must be field-supplied.
3. Remove all wall and floor moldings from behind the unit.
4. Move unit into position. Unit must be snug against wall and furring strips.
5. Adjust unit leveling legs so unit is level. Unit must be level for proper operation and condensate drainage.
6. Using field-supplied fasteners, reach into unit and attach unit to the wall using the back panel.
7. Protect the unit from jobsite debris. Do not allow foreign material to fall into drain pan. Prevent dust and debris from being deposited on motor or fan.
8. Vertical units are intended for exposed floor mount appli­cation only. Do not suspend from structure.
3
/4-in. mounting holes in the
Fig. 2 — Handling the Unit

Protect Units from Damage

To maintain warranty, protect units against adverse weather, theft, vandalism, and debris on the jobsite. Do not allow foreign material to fall into drain pan. Prevent dust and debris from be­ing deposited on motor and fan wheels.
If the equipment is stored for any length of time before installa­tion, it should remain in its shipping container in a clean, dry, and climate controlled area.

Prepare Jobsite for Unit Installation

To save time and to reduce the possibility of costly errors, set up a complete sample installation in a typical room at jobsite. Check all critical dimensions such as pipe, wire, and duct connection re­quirements. Refer to job drawings and product dimension draw­ings as required. Confirm that building construction is adequate to support the unit. See Table 1 for unit weight data. Instruct all trades in their part of the installation.

Identify and Prepare Units

1. Be sure power requirements match available power source. Refer to the unit nameplate and wiring diagram.
2. Remove front (40UV) or bottom (40UH) access panels from the unit. Retain the and panels for re-installation later.
3. Rotate the fan shaft by hand to ensure that fans are unre­stricted and can rotate freely. Check for shipping damage and fan obstructions.
5
/32-in. socket head fasteners

PLACING HORIZONTAL UNITS

1. Select the unit location; ensure that service clearance is provided. Allow enough grille clearance to maintain unrestricted airflow. Make sure that ceiling is able to support the weight of the unit. See Fig. 5-7 for nominal unit weight. See submittal drawings and Fig. 5-7 for dimensions.
NOTE: See page 30 for additional requirements regarding units ducted to multiple openings.
2. Ensure that bottom panels have been removed from unit. When unit is lifted, access to the
3
/4-in. mounting holes is through the bottom of the unit. Hanger rods and fasteners and other required hardware must be field-supplied.
3. Using a forklift or other mechanical lifting device, raise the unit to the mounting position. If forklift or other lifting device is likely to contact a painted wall surface, protect the surface as necessary.
4. Use rods and fasteners to suspend the unit at the mounting holes on the top of the unit. The unit must be suspended at the
3
/4-in. mounting holes; do not use any
other locations.
5. If desired, install field-supplied vibration isolators. Adjust isolators so unit is uniformly suspended and pitched.
6. To ensure proper drainage and operation, ensure unit is level and tighten all fasteners. DO NOT mount the unit on a slope. Pitch of horizontal suspended units can change after coil is filled; recheck after filling coil.
7. Protect the unit from jobsite debris. Do not allow foreign material to fall into drain pan. Prevent dust and debris from being deposited on motor or fan.
2
Page 3
Table 1 — Physical Data
UNIT 40UV, UH 050* 075 100 125 150 200†
NOMINAL AIRFLOW (cfm)
FANS
Quantity Diameter (in.) Width (in.)
40UV FILTERS
Nominal Size (in.) (1-in. thick) Nominal Size (in.) (2-in. thick) Quantity
40UH FILTERS
Nominal Size (in.) (1-in. thick) Nominal Size (in.) (2-in. thick) Quantity
40UV SHIPPING WEIGHT** (Approx lb)
165/8-in. Deep Unit 217/8-in. Deep Unit
40UH SHIPPING WEIGHT** (Approx lb)
34-in. Deep Unit 391/2-in. Deep Unit 431/2-in. Deep Unit 471/2-in. Deep Unit
40UV INSTALLED WEIGHT** (Approx lb)
165/8-in. Deep Unit 217/8-in. Deep Unit
40UH INSTALLED WEIGHT** (Approx lb)
34-in. Deep Unit 391/2-in. Deep Unit 431/2-in. Deep Unit 471/2-in. Deep Unit
COIL WATER WEIGHT (Approx lb per row of coil)
COIL CONNECTIONS (in. OD)
Water Coils with 1 to 5 Rows Steam Coils (All Units)
DX Coils
CONDENSATE DRAIN
LEGEND
DX — Direct Expansion * 40UV only. † 40UH 43 ** Weight based on damper-controlled unit with 5-row coil and fac-
tory-installed controls.
1
/2 and 471/2-in. deep units only.
500 750 1000 1250 1500 2000
123455
8.32 8.32 8.32 8.32 8.32 9.5 888886
91/4 x 241/491/4 x 361/491/4 x 481/491/4 x 601/491/4 x 721/ 91/4 x 241/491/4 x 361/491/4 x 481/491/4 x 601/491/4 x 721/
4
4
— —
11111—
—9 —9
3
/4 x 361/493/4 x 481/493/4 x 601/493/4 x 721/493/4 x 721/
3
/4 x 361/493/
x 481/493/4 x 601/493/4 x 721/493/4 x 721/
4
—11111
330 400 480 590 660 — 340 410 490 605 675
420 500 620 690 — — 500 600 740 830 — — 530 640 790 880 1020 —————1050
315 380 460 570 640 — 325 390 470 595 655
405 480 600 670 — — 485 580 720 810 — — 515 620 770 860 1000 —————1030
1.0 1.5 2.0 2.4 2.7 2.7
Return Supply
11/
7
/
8
8
3
/
8
7
/
8
7
/
8
Suction Liquid
7
/
8
7
/
8
4
4
3
Page 4
NOTES:
1. All dimensions are in inches.
2. Dimension does not include end panels.
3. Three front panels provided for service access.
4. Motor and electrical power input box on right side of unit. Box includes fan speed switch, On/Off switch and non-fused disconnect switch.
5. Connection hand is determined by facing discharge of unit.
UNIT
40UV
AIRFLOW
(cfm)
DIMENSIONS (in.) APPROXIMATE
SHIPPING
WEIGHT (lb)
APPROXIMATE
INSTALLED
WEIGHT (lb)
W1 W2 W3
050 500 50 24 16.60 330 315 075 750 62 36 31.67 400 380 100 1000 74 48 46.74 480 460 125 1250 86 60 61.81 590 570 150 1500 98 72 78.47 660 640
2.95
2.00
12.10 (TYP)
W1
(SEE NOTE 2)
1.00
(UNIT SHOWN
WITH 1.00" END
PA NE L S)
MOTOR
ELECTRICAL BOX
RECESSED RETURN AIR/KICK PANEL
FRONT VIEW
NON-FUSED DISCONNECT SWITCH
FRONT SERVICE PANELS (SEE NOTE 3)
UV OPEN CONTR
OLLER
(OPTIONAL)
17.50 (TYP)
W2
.90
15.00 (TYP)
18.25 (TYP)
7.00 (TYP)
22.00 (TYP)
2.00 (TYP)
8.08 (TYP-SEE NOTE 2)
7.04 (TYP)
1.54 (TYP)
6.75 (TYP)
.75 (MOUNTING HOLES-TYP­4 PLACES)
4.50
REAR VIEW
REMOVABLE PANEL
(
EACH END)
PIPE TUNNEL
OUTSIDE AIR OPENING
PIPING ACCESS OPENING (EACH END)
30.00
27.30
13.90
16.63
7.02
2.40
RIGHT SIDE VIEW
PIPING TUNNEL
1.70
16.63
W3
5.22
10.61 (TYP)
2.08 (TYP)
12.37 (TYP)
.78
(TYP)
TOP VIEW
BARSTOCK DISCHARGE GRILLE
REMOVABLE BOTTOM PANEL (EACH END)
Fig. 3 — 40UV Dimensions — 16
5
/8-in. Deep Units (Standard)
4
Page 5
UNIT
40UV
AIRFLOW
(cfm)
DIMENSIONS (in.) APPROXIMATE
SHIPPING
WEIGHT (lb)
APPROXIMATE
INSTALLED
WEIGHT (lb)
W1 W2 W3
050 500 50 24 16.60 340 325 075 750 62 36 31.67 410 390 100 1000 74 48 46.74 490 470 125 1250 86 60 61.81 605 595 150 1500 98 72 78.47 675 655
NOTES:
1. All dimensions are in inches.
2. Dimension does not include end panels.
3. Three front panels provided for service access.
4. Motor and electrical power input box on right side of unit. Box includes fan speed switch, On/Off switch and non-fused disconnect switch.
5. Connection hand is determined by facing dis­charge of unit.
27.30
30.00
19.37
2.40
13.75
7.02
1.74
PIPING TUNNEL
2.00
3.00
12.00 (TYP)
1.00
(UNIT SHOWN
WITH 1.00" END
PANELS)
W1
(SEE NOTE 2)
MOTOR
ELECTRICAL BOX
RECESSED RETURN AIR/KICK PANEL
NON-FUSED DISCONNECT SWITCH
FRONT SERVICE PA NE L S (SEE NOTE 3)
UV OPEN CONTROLLER (OPTIONAL)
21.88
1.70
5.20
5.22
W3
10.61 (TYP)
12.37 (TYP)
2.08 (TYP)
5.98
(TYP)
TOP VIEW
REMOVABLE BOTTOM PANEL (EACH END)
BAR
STOCK
DISCHARGE GRILLE
FRONT VIEW
END VIEW
18.25 (TYP)
15.00 (TYP)
.75 (MOUNTING HOLES-TYP­4 PLACES)
17.50 (TYP)
7.00 (TYP)
22.00 (TYP)
2.00 (TYP)
W2
0.90
8.08
(TYP-SEE
NOTE 2)
7.04 (TYP)
1.54 (TYP)
6.75 (TYP)
4.50
REAR VIEW
PIPE TUNNEL
OUTSIDE AIR OPENING
REMOVABLE PANEL (EACH END)
PIPING ACCESS OPENING (EACH END)
Fig. 4 — 40UV Dimensions — 21
7
/8-in. Deep Units (With Piping Chase)
5
Page 6
NOTES:
1. All dimensions are in inches.
2. Dimension does not include end panels.
3. Two bottom panels provided for service access.
4. Motor and electrical power input box on right side of unit. Box includes fan speed switch, and non-fused disconnect switch.
5. Drawing refers to Design “F” units.
UNIT
40UH
AIRFLOW
(cfm)
DIMENSIONS (in.) APPROXIMATE
SHIPPING
WEIGHT (lb)
APPROXIMATE
INSTALLED
WEIGHT (lb)
W1 W2 W3
075 750 62 36 31.67 420 405 100 1000 74 48 46.74 500 480 125 1250 86 60 61.81 620 600 150 1500 98 72 78.47 690 670
W3
L
16.63
34
LEFT SIDE VIEW
BOTTOM SERVICE PANELS
(UNIT SHOWN
WITH 1.00" END
PANELS)
UV OPEN
CONTROLLER
(OPTIONAL)
(SEE NOTE 3)
21.86 (TYP)
1.00
18.59 (TYP)
5.22
8.08 (TYP - SEE NOTE 2)
FRONT VIEW
W1
(SEE NOTE 2)
BOTTOM VIEW
REMOVABLE PANEL
(EACH END)
W2
1.70
BARSTOCK DISCHARGE GRILLE (OPTIONAL)
MOTOR
2.00
ELECTRICA BOX
NON-FUSED DISCONNECT SWITCH
RETURN AIR LOUVERED PANEL (OPTIONAL)
1.54 (TYP)
(MOUNTING HOLES
TYP-4 PLACES)
Fig. 5 — 40UH Dimensions — 34-in. Deep Units (Digit Code #11 — Option A, B, or C)
Ø.75
1.72
7.50
OUTSIDE AIR
4.50
OPENING
0.92
6.75 (TYP)
TOP VIEW
W2
REAR OUTSIDE AIR OPENING (OPTIONAL)
REAR RETURN AIR OPENING (OPTIONAL)
1.75
5.25
REAR VIEW
6
2.10 (TYP)
Page 7
16.63
W3 (OPENING)
W5
(OPENING)
(TO OPENING)
LEFT SIDE VIEW
(SIZES 075 TO 150)
BOTTOM VIEW
DOUBLE DEFLECTION DISCHARGE GRILLE (OPTIONAL)
W4
(TYP)
2.10 (TYP)
W8
(TYP)
W2
0.92
4.50
.75 (MOUNTING HOLES­TYP-4 PLACES)
6.75 (TYP)
1.00 (TYP)
W7 (TYP-SEE NOTE 2)
3.27 (TYP)
TOP OUTSIDE AIR OPENING (OPTIONAL)
REMOVABLE PANEL (EACH EN
D)
FRONT VIEW
1.72
7.50
5.25
W2
1.75
REAR OUTSIDE AIR OPENING (OPTIONAL)
REAR RETURN AIR OPENING (OPTIONAL)
W1
1.00
(UNIT SHOWN
WITH 1.00"
END PANELS)
RETURN AIR LOUVERED PANEL (OPTIONAL)
MOTOR
ELECTRICAL BOX
NON-FUSED DISCONNECT SWITCH
UV OPEN CONTROLLER (OPTIONAL)
BOTTOM SERVICE PANELS (SEE NOTE 3)
TOP VIEW
(SEE NOTE 2)
LEFT SIDE VIEW
(SIZE 200)
PIPE TUNNEL
4.00
7.50
39.50
43.50
W6
UNIT
40UH
AIRFLOW
(cfm)
DEPTH
(in.)
DIMENSIONS (in.) APPROXIMATE
SHIPPING
WEIGHT (lb)
APPROXIMATE
INSTALLED WEIGHT (lb)
W1 W2 W3 W4 W5 W6 W7 W8
075 750 36 62 36 36 21.86 7.00 2.31 8.00 4.75 500 485 100 1000 36 74 48 48 21.86 7.00 2.31 8.00 4.75 600 580 125 1250 36 86 60 60 21.86 7.00 2.31 8.00 4.75 740 720 150 1500 36 98 72 72 21.86 7.00 2.31 8.00 4.75 830 810 200 2000 40 98 72 72 30.00 10.00 1.44 8.07 4.00 1020 1000
NOTES:
1. All dimensions are in inches.
2. Dimension does not include end panels.
3. Two bottom panels provided for service access.
4. Motor and electrical power input box on right side of unit. Box includes fan speed switch, and non-fused disconnect switch.
5. Connection hand is determined by facing discharge of unit.
6. Drawing refers to design “F” series.
Fig. 6 — 40UH Dimensions — 39
1
/2-in. and 431/2-in. Deep Unit with Front Discharge Plenum
(Digit Code #11 — Option D or E)
7
Page 8
16.63
NOTES:
1. All dimensions are in inches.
2. Dimension does not include end panels.
3. Two bottom panels provided for service access.
4. Motor and electrical power input box on right side of unit. Box includes fan speed switch, and non-fused disconnect switch.
5. Connection hand is determined by facing discharge of unit.
6. Drawings refer to design “F” units.
UNIT
40UH
AIRFLOW
(cfm)
DEPTH
(in.)
DIMENSIONS (in.) APPROXIMATE
SHIPPING
WEIGHT (lb)
APPROXIMATE
INSTALLED
WEIGHT (lb)
W1 W2 W3 W4 W5 W6 W7 W8
075 750 40 62 36 36 21.86 7.00 8.00 4.75
17.5
530 515
100 1000 40 74 48 48 21.86 7.00 8.00 4.75
17.5
640 620
125 1250 40 86 60 60 21.86 7.00 8.00 4.75
17.5
790 770
150 1500 40 98 72 72 21.86 7.00 8.00 4.75
17.5
880 860
200 2000 44 98 72 72 30.00 10.00 8.07 4.00
17.4
1050 1030
43.50
LEFT SIDE VIEW
(SIZES 075 TO 150)
4.00
47.50
LEFT SIDE VIEW
(SIZE 200)
7.50
(UNIT SHOWN
END PANELS)
PIPE TUNNEL
UV OPEN CONTROLLER (OPTIONAL)
BOTTOM SERVICE PANELS (SEE NOTE 3)
REMOVABLE PANEL (EACH EN
1.00
WITH 1.00"
W5 (OPENING)
(TYP-SEE
NOTE 2)
D)
W6
FRONT VIEW
W1
(SEE NOTE 2)
W3
(OPENING)
RETURN AIR LOUVERED PANEL (OPTIONAL)
BOTTOM VIEW
TOP OUTSIDE AIR OPENING (OPTIONAL)
W7 (TYP)
MOTOR
ELECTRICAL BOX
NON-FUSED
SCONNECT
DI SWITCH
1.00 (TYP)
W4
(TYP)
3.27 (TYP)
(MOUNTING HOLES-
TYP-4 PLACES)
Fig. 7 — 40UH Dimensions — 43
.75
1.72
7.50
5.25
1
/2-in. and 471/2-in. Deep Unit with Down Discharge Plenum
(Digit Code #11 — Option F)
8
W2
0.92
TOP VIEW
REAR OUTSIDE AIR OPENING (OPTIONAL)
REAR RETURN AIR OPENING (OPTIONAL)
W2
REAR VIEW
4.50
W8
(TYP)
6.75 (TYP)
1.75
2.10 (TYP)
Page 9

Step 2 — Make Piping Connections

2-1/2" MIN
3/4"
GALVANIZED PIPE
3/4"
PVC OR COPPER
2-1/2" MIN
1-1/2" MIN
1-1/2" MIN
DRAIN PAN
UPPER HOLES
LOWER HOLES
NOTE: Reverse slope by reversing connections on each end of the pan.
UPPER HOLES
LOWER HOLES
Access to piping is available through the access panels at the front, top, or end of the vertical unit (horizontal access from bot­tom or side). Route piping through the pipe tunnel or the unit’s back panel or floor panel. Metal blank-off panels must be trimmed to complete piping installation. Metal blank-off panels must be retrofitted around the piping to restore installation integ­rity. All piping connections must be performed by qualified per­sonnel in accordance with local and national codes.
CAUTION
When making solder connections, care must be taken to prevent the dripping of solder or other debris onto the insu­lation, control wiring, control box, actuators, and DDC (Direct Digital Controls) controller (if so equipped). When using a torch anywhere in the unit, care must be taken to not burn any components.
DRAIN CONNECTIONS Condensate drain connections are located on each end of the
drain pan near the bottom of the unit. Access by removing the end panel. Condensate drain line must be galvanized pipe, PVC or similar plastic pipe. Install drain line in accordance with all applicable codes. Insulate the drain line to prevent sweating. See Fig. 8 for typical drain trap construction.
3
/4-in. copper tubing,
Fig. 9 — Drain Pan Connection Holes, Inside View
Fig. 8 — Typical Condensate Drain Trap
Condensate
NOTE: Drain pan is sloped toward the connections of the largest coil or toward the connections of the DX (direct expansion) coil. In a unit with 2-row right hand coils and 4-row left-hand coils for example, the drain pan is sloped down to the left-hand side. The uphill connection is sealed with a plug. The downhill field con­nection is covered with a plastic cap except when the drain pan is stainless steel, then both connections are sealed with a plug. Re­move cap (or plug on stainless steel) on the downhill connection. Do not remove the high side drain connection plug. The slope may be reversed in the field by removing the drain pan screws (2 per side), using the opposite set of holes to install the pan, and sealing the uphill connection. See Fig. 9 and 10.
Units with cooling coils require traps to prevent air from entering the condensate fitting and preventing proper drainage. Drain must be sloped downhill from the unit a minimum of ft. Drain must be free and clear at all times. It is not recommend­ed to tie multiple units into one condensate line due to potential
1
/8-in. per
for overflow.
CAUTION
Insulate drain lines to prevent condensate. Care must be taken to avoid interference with control panel on left side drain. Failure to comply could result in equipment damage.
Fig. 10 — Drain Pan Connection Holes, Outside
View

WATER SUPPLY/RETURN CONNECTIONS

Install piping in accordance with all applicable codes. All piping must be supported separately from coils.
Water supply must be connected so that entering water is on leaving-air side of coil. See the connection labels on the unit to locate the inlet. Coils must be adequately vented to prevent air binding. Be sure valves are in proper operating position and are easily accessible for adjustment.
If coil and valve package connections will be made with a solder joint, care should be taken to ensure that components in the valve package are not subjected to high temperatures which may dam­age seals or other materials. Many 2-position electric control valves are provided with a manual operating lever. This lever should be in the OPEN position during all soldering operations.
If coil connection is made with a union, the coil side of the union must be prevented from turning (it must be backed up) during tightening. Do not overtighten! Overtightening will distort (egg
shape) the union seal surface and destroy the union.
NOTE: A freezestat is factory-installed when a hot water/steam coil is installed.

STEAM CONNECTIONS

On units with steam heating coils, the maximum steam pres­sure applied to the unit should never exceed 6 psig. Carrier rec­ommends float and thermostatic ("F&T") type steam traps for best results. However, other styles may work and selection is the responsibility of the customer. Sizing and selection of the steam trap and design of the steam system piping should be done with the recommendation of the steam trap supplier. A
9
Page 10
vacuum breaker is factory-supplied with the unit ventilator
EQUALIZER
SENSING BULB (CLAMPED TO SUCTION LINE AND INSULATED)
SUCTION LINE
LIQUID LINE
steam coil, and must be field-piped to a location downstream of the trap to allow vacuum relief when the coil is turned off. In all situations, the steam piping connected to the unit should be designed and installed according to good piping practices for steam systems.

DIRECT EXPANSION REFRIGERANT PIPING

Use the condensing unit manufacturer’s recommended line sizes and requirements. Perform leak test using nitrogen. Evacuate and charge per recommended heating, ventilation, and air condi­tioning (HVAC) procedures and all applicable codes. Insulate suction line after leak test up to the coil section end plate for cor­rect operation and to eliminate sweating. Use refrigerant-grade copper lines only. Units utilizing R-22 refrigerant are NOT to be applied as a heat pump.
See Fig. 11 for refrigerant piping connections with recommend­ed locations for the thermostatic expansion valve (TXV) and sensing bulb. Locate bulb in the horizontal run from approxi­mately the 9:00 to 3:00 position or in a vertical run.
NOTE: A low limit sensing bulb is factory-installed when a DX coil is installed.
Fig. 11 — Typical TXV Installation
NOTE: Follow TXV manufacturer’s instructions.

HYDRONIC COIL PIPING

When all joints are complete, perform hydrostatic test for leaks. Vent all coils at this time. Check interior unit piping for signs of leakage from shipping damage or mishandling. If leaks are found, notify a Carrier representative before initiating any re­pairs. Release trapped air from system (refer to Step 6 — “Make Final Preparations” on page 31).
sibility of the installer and should be suitable thickness to prevent sweating and with adequate vapor barrier.
To ensure compliance with building codes, restore the structure’s original fire resistance rating by sealing all holes with material carrying the same fire rating as the structure.

CONTROL VALVES

Controls require normally open heating valves. Chilled water valves must be piped normally closed. It is recommended that heating valves fail safe to the open position in all control applica­tions. Valve packages must always be field insulated to prevent sweating. See Fig. 12 for piping recommendations.

Step 3 — Make Electrical Connections

Refer to unit serial plate for required supply voltage, fan and heater amperage and required circuit ampacities. Refer to unit wiring diagram for unit and field wiring. See Tables 2-4 for elec­trical data.
Access to all electrical connections can be gained through the ac­cess panel at the right front side of the unit. See the dimensional drawings Fig. 3-7 for electrical box connections.
The fan motor should never be controlled by any wiring or de­vice other than the factory-supplied switch or thermostat/switch combination unless prior factory authorization is obtained. Fan motor may be temporarily wired for use during construction only with prior factory approval and only in strict accordance with the instructions issued at that time.
All electrical connections should be made by qualified personnel and be in accordance with governing codes and ordinances. Any modification of unit wiring without factory authorization will in­validate all factory warranties and nullify any agency listings. See Fig. 13-23 for typical wiring connections for basic unit with­out UV Open controls.
Electric heat elements are the open wire type mounted in indi­vidual heavy gage galvanized steel frames and suspended in ce­ramic insulators. Dual capillary type thermal sensing elements, one automatic reset and one manual, is used to protect the unit from overheating in the event of abnormal operation. Automatic reset limit is set at 210°F. The access for the limit switch is locat­ed on the opposite end of the fan motor. Manual reset high limit is set at 240°F. The access for the limit switch is located at the same end as the fan motor.

Step 4 — Mount Actuators (Field-Supplied)

Field-supplied actuators must be mounted on 1/2-in. diameter damper shafts.
CAUTION
All water coils must be protected from freezing after initial filling with water. Even if system is drained, unit coils may still have enough remaining water to cause damage when exposed to temperatures below freezing.
Following the hydrostatic test, the installer shall insulate all pip­ing up to the coil section end plate to prevent condensation (sweating) and heat loss. Ensure that factory-provided valve packages are properly insulated. Piping insulation is the respon-
CAUTION
With factory-installed controls provided by others, factory may wire controls and actuator based on the request; how­ever, setting the actuators (switch settings, tightening clamp to damper shaft, torque pre-loading, etc.) is the sole respon­sibility of the customer. Failure to set the actuator may result in equipment damage.
10
Page 11
See Note
LEGEND
S—Supply R—Return
Union
NOTE: Factory-supplied vacuum breaker assembly. Field install in vertical orientation with flow arrow up and piping down so that ball seats with gravity. Equalizer line and trap are field supplied and installed.
Fig. 12 — Control Valves
11
Page 12
Table 2 — Electric Heater Data for Units with PSC Motor
UNIT HP
NOMINAL
V/Ph/Hz
NUMBER OF
ELEMENTS
3 17.2 90 21.5 25 3.2
208/1/60
4 22.2 97 27.8 30 4.2 5 27.3 104 34.1 35 5.3 6 32.3 110 40.4 45 6.3 3 19.5 97 24.4 25 4.2
240/1/60
4 25.3 106 31.7 35 5.6 5 31.2 115 39.0 40 7.0 6 37.0 124 46.3 50 8.4 3 16.8 97 21.0 25 4.2 4 21.8 106 27.3 30 5.6 5 26.9 115 33.6 35 7.0 6 31.9 124 39.9 40 8.4 3 10.8 90 13.5 15 3.2 4 15.8 97 19.8 20 4.2 5 19.5 104 24.4 25 5.3
40UV050
(at 500 cfm)
277/1/60
1
/
5
208/3/60
6 19.5 110 24.4 25 6.3 3 12.1 97 15.1 20 4.2
240/3/60
4 17.9 106 22.4 25 5.6 5 22.2 115 27.8 30 7.0 6 22.2 124 27.8 30 8.4 3 6.0 97 7.5 15 4.2
460/3/60
4 8.9 106 11.1 15 5.6 5 11.0 115 13.8 15 7.0 6 11.0 124 13.8 15 8.4 3 23.7 89 29.6 30 4.5
208/1/60
4 30.9 96 38.6 40 6.0 5 38.1 102 47.6 50 7.5 6 45.3 108 56.7 60 9.0 3 27.0 96 33.8 35 6.0
240/1/60
4 35.3 104 44.2 45 8.0 5 43.7 113 54.6 60 10.0 6 52.0 121 65.0 70 12.0 3 23.3 96 29.1 30 6.0 4 30.5 104 38.1 40 8.0 5 37.7 113 47.1 50 10.0 6 44.9 121 56.2 60 12.0 3 14.5 89 18.2 20 4.5 4 21.7 96 27.2 30 6.0 5 27.0 102 33.8 35 7.5
40UV,UH075
(at 750 cfm)
277/1/60
1
/
5
208/3/60
6 27.0 108 33.8 35 9.0 3 16.5 96 20.6 25 6.0
240/3/60
4 24.8 104 31.0 35 8.0 5 30.9 113 38.6 40 10.0 6 30.9 121 38.6 40 12.0 3 8.2 96 10.2 15 6.0
460/3/60
4 12.3 104 15.4 20 8.0 5 15.4 113 19.2 20 10.0 6 15.4 121 19.2 20 12.0
LEGEND
FLA Full Load Amps LAT Leaving-Air Temperature at 70°F Entering-Air
MCA — Unit Minimum Circuit Ampacity MOCP — Maximum Overcurrent Protection (Maximum Fuse Size
Temperature
or Circuit Breaker Amps)
PSC Permanent Split Capacitor
*Cooling coil must be left-hand coil connections only. NOTES:
1. LAT (leaving air temperature) is at maximum fan speed with entering air temperature at 70°F.
2. Face and bypass units are available only with 3 elements.
3. Electric heat is available in the reheat only position.
4. The PSC motor is not available on unit size 200.
FLA LAT (F) MCA MOCP
TOTAL
CAPACITY (kW)
12
Page 13
Table 2 — Electric Heater Data for Units with PSC Motor (cont)
UNIT HP
NOMINAL
V/Ph/Hz
NUMBER OF
ELEMENTS
3 30.9 89 38.6 40 6.0
208/1/60
4 40.5 95 50.7 60 8.0 5 50.2 102 62.7 70 10.0 6 59.8 108 74.7 80 11.9 3 35.3 96 44.2 45 8.0
240/1/60
4 46.5 104 58.1 60 10.7 5 57.6 112 72.0 80 13.3 6 68.7 121 85.8 90 16.0 3 30.5 96 38.1 40 8.0 4 40.1 104 50.1 60 10.7 5 49.7 112 62.2 70 13.3 6 59.4 121 74.2 80 16.0 3 18.7 89 23.4 25 6.0 4 28.3 95 35.4 40 8.0 5 35.4 102 44.3 45 10.0
40UV,UH100
(at 1000 cfm)
277/1/60
1
/
5
208/3/60
6 35.4 108 44.3 45 11.9 3 21.3 96 26.6 30 8.0
240/3/60
4 32.4 104 40.5 45 10.7 5 40.5 112 50.7 60 13.3 6 40.5 121 50.7 60 16.0 3 10.6 96 13.2 15 8.0
460/3/60
4 16.1 104 20.1 25 10.7 5 20.2 112 25.2 30 13.3 6 20.2 121 25.2 30 16.0 3 38.1 89 47.6 50 7.5
208/1/60
4 50.1 96 62.7 70 10.0 5 62.2 102 77.7 80 12.5 6* 74.2 108 92.8 100 15.0 3 43.7 96 54.6 60 10.0
240/1/60
4 57.6 104 71.9 80 13.3 5 71.4 113 89.3 90 16.7 6* 85.3 121 106.7 110 20.0 3 37.7 96 47.1 50 10.0 4 49.7 104 62.2 70 13.3 5 61.8 113 77.2 80 16.7 6* 73.8 121 92.2 100 20.0 3 22.9 89 28.6 30 7.5 4 34.9 96 43.6 45 10.0 5 43.7 102 54.7 60 12.5
40UV,UH125
(at 1250 cfm)
277/1/60
1
/
5
208/3/60
6* 43.7 108 54.7 60 15.0 3 26.1 96 32.6 35 10.0
240/3/60
4 40.0 104 50.0 50 13.3 5 50.2 113 62.7 70 16.7 6* 50.2 121 62.7 70 20.0 3 13.0 96 16.2 20 10.0
460/3/60
4 19.9 104 24.9 25 13.3 5 25.0 113 31.3 35 16.7 6* 25.0 121 31.3 35 20.0
LEGEND
FLA Full Load Amps LAT Leaving-Air Temperature at 70°F Entering-Air
MCA — Unit Minimum Circuit Ampacity MOCP — Maximum Overcurrent Protection (Maximum Fuse Size
Temperature
or Circuit Breaker Amps)
PSC Permanent Split Capacitor
*Cooling coil must be left-hand coil connections only. NOTES:
1. LAT (leaving air temperature) is at maximum fan speed with
entering air temperature at 70°F.
2. Face and bypass units are available only with 3 elements.
3. Electric heat is available in the reheat only position.
4. The PSC motor is not available on unit size 200.
FLA LAT (F) MCA MOCP
TOTAL
CAPACITY (kW)
13
Page 14
Table 2 — Electric Heater Data for Units with PSC Motor (cont)
UNIT HP
NOMINAL
V/Ph/Hz
NUMBER OF
ELEMENTS
3 45.3 89 56.7 60 9.0
208/1/60
4 59.8 96 74.7 80 12.0 5 74.2 102 92.8 100 15.0 6* 88.7 108 110.8 125 18.0 3 52.0 96 65.0 70 12.0
240/1/60
4 68.7 104 85.8 90 16.0 5 85.3 113 106.7 110 20.0 6——— 3 44.9 96 56.2 60 12.0 4 59.4 104 74.2 80 16.0 5 73.8 113 92.3 100 20.0 6——— 3 27.0 89 33.8 35 9.0 4 41.5 96 51.9 60 12.0 5 52.1 102 65.1 70 15.0
40UV,UH150
(at 1500 cfm)
277/1/60
1
/
5
208/3/60
6* 52.1 108 65.1 70 18.0 3 30.9 96 38.6 40 12.0
240/3/60
4 47.6 104 59.5 60 16.0 5 59.8 113 74.8 80 20.0 6* 59.8 121 74.8 80 24.0 3 15.4 96 19.2 20 12.0
460/3/60
4 23.7 104 29.6 30 16.0 5 29.8 113 37.3 40 20.0 6* 29.8 121 37.3 40 24.0
LEGEND
FLA Full Load Amps LAT Leaving-Air Temperature at 70°F Entering-Air
MCA — Unit Minimum Circuit Ampacity MOCP — Maximum Overcurrent Protection (Maximum Fuse Size
Temperature
or Circuit Breaker Amps)
PSC Permanent Split Capacitor
FLA LAT (F) MCA MOCP
TOTAL
CAPACITY (kW)
NOTES:
1. LAT (leaving air temperature) is at maximum fan speed with entering air temperature at 70°F.
2. Face and bypass units are available only with 3 elements.
3. Electric heat is available in the reheat only position.
4. The PSC motor is not available on unit size 200.
*Cooling coil must be left-hand coil connections only.
14
Page 15
Table 3 — Electric Heater Data for Units with ECM Motor
UNIT HP
NOMINAL
V/Ph/Hz
NUMBER OF
ELEMENTS
3 16.5 90 20.6 25 3.2
208/1/60
4 21.5 97 26.9 30 4.2 5 26.6 104 33.2 35 5.3 6 31.6 110 39.5 40 6.3 3 18.8 97 23.5 25 4.2
240/1/60
4 24.6 106 30.8 35 5.6 5 30.5 115 38.1 40 7.0 6 36.3 124 45.4 50 8.4 3 16.3 97 20.3 25 4.2 4 21.3 106 26.6 30 5.6 5 26.4 115 33.0 35 7.0 6 31.4 124 39.3 40 8.4 3 10.1 90 12.6 15 3.2 4 15.1 97 18.9 20 4.2 5 18.8 104 23.5 25 5.3
40UV050
(at 500 cfm)
277/1/60
1
/
3
208/3/60
6 18.8 110 23.5 25 6.3 3 11.4 97 14.3 15 4.2
240/3/60
4 17.2 106 21.6 25 5.6 5 21.5 115 26.9 30 7.0 6 21.5 124 26.9 30 8.4 3 5.4 97 6.8 15 4.2
460/3/60
4 8.3 106 10.4 15 5.6 5 10.5 115 13.1 15 7.0 6 10.5 124 13.1 15 8.4 3 24.0 89 30.0 30 4.5
208/1/60
4 31.2 96 39.0 40 6.0 5 38.4 102 48.0 50 7.5 6 45.6 108 57.0 60 9.0 3 27.3 96 34.1 35 6.0
240/1/60
4 35.6 104 44.5 45 8.0 5 44.0 113 55.0 60 10.0 6 52.3 121 65.4 70 12.0 3 23.7 96 29.6 30 6.0 4 30.9 104 38.6 40 8.0 5 38.1 113 47.6 50 10.0 6 45.3 121 56.7 60 12.0 3 14.8 89 18.5 20 4.5 4 22.0 96 27.6 30 6.0 5 27.3 102 34.2 35 7.5
40UV,UH075
(at 750 cfm)
277/1/60
1
/
3
208/3/60
6 27.3 108 34.2 35 9.0 3 16.8 96 20.9 25 6.0
240/3/60
4 25.1 104 31.4 35 8.0 5 31.2 113 39.0 40 10.0 6 31.2 121 39.0 40 12.0 3 8.2 96 10.2 15 6.0
460/3/60
4 12.3 104 15.4 20 8.0 5 15.4 113 19.2 20 10.0 6 15.4 121 19.2 20 12.0
LEGEND *Cooling coil must be left-hand coil connections only.
ECM — Electronically Commutated Motor FLA Full Load Amps LAT Leaving-Air Temperature at 70°F Entering-Air
MCA — Unit Minimum Circuit Ampacity MOCP — Maximum Overcurrent Protection (Maximum Fuse Size
Temperature
or Circuit Breaker Amps)
FLA LAT (F) MCA MOCP
NOTES:
1. LAT (leaving-air temperature) is at maximum fan speed with entering air temperature at 70°F.
2. Face and bypass units are available only with 3 elements.
3. Electric heat is available in the reheat only position.
TOTAL
CAPACITY (kW)
15
Page 16
Table 3 — Electric Heater Data for Units with ECM Motor (cont)
UNIT HP
NOMINAL
V/Ph/Hz
NUMBER OF
ELEMENTS
3 31.5 89 39.4 40 6.0
208/1/60
4 41.1 95 51.4 60 8.0 5 50.8 102 63.4 70 10.0 6 60.4 108 75.5 80 11.9 3 35.9 96 44.9 45 8.0
240/1/60
4 47.1 104 58.8 60 10.7 5 58.2 112 72.7 80 13.3 6 69.3 121 86.6 90 16.0 3 31.2 96 39.0 40 8.0 4 40.8 104 51.0 60 10.7 5 50.4 112 63.1 70 13.3 6 60.1 121 75.1 80 16.0 3 19.3 89 24.1 25 6.0 4 28.9 95 36.2 40 8.0 5 36.0 102 45.0 50 10.0
40UV,UH100 (at 1000 cfm)
277/1/60
1
/
3
208/3/60
6 36.0 108 45.0 50 11.9 3 21.9 96 27.3 30 8.0
240/3/60
4 33.0 104 41.2 45 10.7 5 41.1 112 51.4 60 13.3 6 41.1 121 51.4 60 16.0 3 10.6 96 13.3 15 8.0
460/3/60
4 16.2 104 20.2 25 10.7 5 20.3 112 25.3 30 13.3 6 20.3 121 25.3 30 16.0 3 39.4 89 49.3 50 7.5
208/1/60
4 51.5 96 64.3 70 10.0 5 63.5 102 79.4 80 12.5 6* 75.5 108 94.4 100 15.0 3 45.0 96 56.2 60 10.0
240/1/60
4 58.9 104 73.6 80 13.3 5 72.7 113 90.9 100 16.7 6* 86.6 121 108.3 110 20.0 3 39.0 96 48.7 50 10.0 4 51.0 104 63.8 70 13.3 5 63.1 113 78.8 80 16.7 6* 75.1 121 93.9 100 20.0 3 24.2 89 30.2 35 7.5 4 36.2 96 45.3 50 10.0 5 45.0 102 56.3 60 12.5
40UV,UH125 (at 1250 cfm)
277/1/60
1
/
2
208/3/60
6* 45.0 108 56.3 60 15.0 3 27.4 96 34.2 35 10.0
240/3/60
4 41.3 104 51.6 60 13.3 5 51.5 113 64.3 70 16.7 6* 51.5 121 64.3 70 20.0 3 13.2 96 16.5 20 10.0
460/3/60
4 20.2 104 25.2 30 13.3 5 25.3 113 31.6 35 16.7 6* 25.3 121 31.6 35 20.0
LEGEND
ECM — Electronically Commutated Motor FLA Full Load Amps LAT Leaving-Air Temperature at 70°F Entering-Air
MCA — Unit Minimum Circuit Ampacity MOCP — Maximum Overcurrent Protection (Maximum Fuse Size
Temperature
or Circuit Breaker Amps)
*Cooling coil must be left-hand coil connections only NOTES:
1. LAT (leaving air temperature) is at maximum fan speed with entering air temperature at 70°F.
2. Face and bypass units are available only with 3 elements.
3. Electric heat is available in the reheat only position.
FLA LAT (F) MCA MOCP
TOTAL
CAPACITY (kW)
16
Page 17
Table 3 — Electric Heater Data for Units with ECM Motor (cont)
UNIT HP
NOMINAL
V/Ph/Hz
NUMBER OF
ELEMENTS
3 46.7 89 58.3 60 9.0
208/1/60
4 61.1 96 76.4 80 12.0 5 75.6 102 94.4 100 15.0 6* 90.0 108 112.5 125 18.0 3 53.3 96 66.6 70 12.0
240/1/60
4 70.0 104 87.5 90 16.0 5 86.6 113 108.3 110 20.0 6——— 3 46.2 96 57.8 60 12.0 4 60.7 104 75.8 80 16.0 5 75.1 113 93.9 100 20.0 6——— 3 28.3 89 35.4 40 9.0 4 42.8 96 53.5 60 12.0 5 53.4 102 66.7 70 15.0
40UV,UH150
(at 1500 cfm)
277/1/60
1
/
2
208/3/60
6* 53.4 108 66.7 70 18.0 3 32.2 96 40.3 45 12.0
240/3/60
4 48.9 104 61.1 70 16.0 5 61.1 113 76.4 80 20.0 6* 61.1 121 76.4 80 24.0 3 15.6 96 19.5 20 12.0
460/3/60
4 24.0 104 30.0 30 16.0 5 30.1 113 37.6 40 20.0 6* 30.1 121 37.6 40 24.0 3 50.1 84 62.7 70 9.0
208/1/60
4 64.6 89 80.7 90 12.0 5 79.0 94 98.8 100 15.0 6* 93.5 99 116.8 125 18.0 3 56.8 89 71.0 80 12.0
240/1/60
4 73.5 96 91.8 100 16.0 5 90.1 102 112.7 125 20.0 6——— 3 48.8 89 61.0 70 12.0 4 63.3 96 79.1 80 16.0 5 77.7 102 97.1 100 20.0 6——— 3 31.8 84 39.8 40 9.0 4 46.3 89 57.9 60 12.0 5 56.9 94 71.1 80 15.0
40UH200
(at 2000 cfm)
277/1/60
3
/
4
208/3/60
6* 56.9 99 71.1 80 18.0 3 35.7 89 44.6 45 12.0
240/3/60
4 52.4 96 65.5 70 16.0 5 64.6 102 80.8 90 20.0 6* 64.6 108 80.8 90 24.0 3 16.9 89 21.1 25 12.0
460/3/60
4 25.2 96 31.5 35 16.0 5 31.3 102 39.1 40 20.0 6* 31.3 108 39.1 40 24.0
LEGEND
ECM — Electronically Commutated Motor FLA Full Load Amps LAT Leaving-Air Temperature at 70°F Entering-Air
MCA — Unit Minimum Circuit Ampacity MOCP — Maximum Overcurrent Protection (Maximum Fuse Size
Temperature
or Circuit Breaker Amps)
FLA LAT (F) MCA MOCP
TOTAL
CAPACITY (kW)
*Cooling coil must be left-hand coil connections only. NOTES:
1. LAT (leaving air temperature) is at maximum fan speed with
entering air temperature at 70°F.
2. Face and bypass units are available only with 3 elements.
3. Electric heat is available in the reheat only position.
17
Page 18
Table 4 — Motor Data
PSC Motor Data
UNIT 40UV,UH SIZE MOTOR Hp VOLTAGE FLA MCA MOP (Amps)
115 3.7 4.6 8.3 15
050*
1
/
5
208/230 2.0 2.5 4.5 15
265 1.6 2.0 3.6 15 115 3.7 4.6 8.3 15
075
1
/
5
208/230 2.0 2.5 4.5 15
265 1.6 2.0 3.6 15 115 3.7 4.6 8.3 15
100
1
/
5
208/230 2.0 2.5 4.5 15
265 1.6 2.0 3.6 15 115 3.7 4.6 8.3 15
125
1
/
5
208/230 2.0 2.5 4.5 15
265 1.6 2.0 3.6 15 115 3.7 4.6 8.3 15
150
1
/
5
208/230 2.0 2.5 4.5 15
265 1.6 2.0 3.6 15
ECM Motor Data
UNIT 40UV,UH SIZE MOTOR Hp VOLTAGE FLA MCA MOP (Amps)
050*
075
100
125
150
200†
1
/
3
1
/
3
1
/
3
1
/
2
1
/
2
3
/
4
LEGEND
ECM — Electronically Commutated Motor FLA — Full Load Amps MCA — Minimum Circuit Amps MOP — Maximum Overload Protection PSC — Permanent Split Capacitor
*Available in vertical configuration only.
†Available in horizontal configuration only. NOTE: The PSC motor is not available on unit size 200.
115 1.4 1.8 3.1 15
208/230 1.3 1.6 2.9 15
265 1.1 1.4 2.6 15 115 3.7 4.6 8.3 15
208/230 2.3 2.9 5.1 15
265 2.0 2.5 4.5 15 115 4.0 5.0 9.1 15
208/230 2.6 3.2 5.8 15
265 2.3 2.9 5.1 15 115 4.7 5.9 10.6 15
208/230 3.3 4.1 7.4 15
265 2.9 3.6 6.6 15 115 4.7 5.9 10.6 15
208/230 3.3 4.1 7.4 15
265 2.9 3.6 6.6 15 115 9.6 12.0 21.6 20
208/230 6.8 8.5 15.3 15
265 5.5 6.9 12.4 15
MAX FUSE SIZE
(Amps)
MAX FUSE SIZE
(Amps)
18
Page 19
SW2
See Tap
BLK
RED
WHT
FAN
MOTOR
SW1
WHT/110
BLK/101
WHT/110
BLK/102
FU1
USE COPPER SUPPLY WIRES.
L1
N
GND
RED BLK
WHT
3
2
1
123
LLT
WHT
WHT
BLK/104
BLK/100
BLK/103
BLK/104
SEE NOTE 2
DISC1
GRN
TRAN3
SEE NOTE 3
MAX
LOW
HIGH
LLR
3
1
2
FIELD CONNECTED TO
REMOTE CONDENSER.
LLR INSTALLED ONLY ON
UNITS WITH DX COILS.
Select Drawing
NOTES:
1. Make electrical installation in accordance with job
diagram, and in compliance with national and local
electrical codes.
2. Low limit thermostat (LLT) is installed on all units with
water coils.
3. Unused transformer leads are separately insulated.
LEGEND
DISC — Disconnect Switch
DX Direct Expansion
FU Fuse
GND — Ground
LLR DX Low Limit Switch
LLT Water Coil Low Limit Thermostat
PSC Permanent Split Capacitor
SW Switch
TRAN — Transformer
Splice Terminal Connection
Component Tie Point
Optional Wiring
Factory Wiring
Chassis Ground
Fig. 13 — 115-v PSC Motor without Controls
19
Page 20
SW2
SEE TAP
WHT
SW1
RED
BLK/101
BLK/108
BLK/102
FU1
L1
L2
GND
BLK/RED
WHT
123
LLT
WHT
WHT
BLK/104
BLK/100
BLK/103
BLK/104
SEE NOTE 2
DISC1
GRN
TRAN3
SEE NOTE 3
BLK/106 BLK/107
FU2
BLK/105
BLK/108
SEE NOTE 4
BLK/YEL208V
240V
USE COPPER SUPPLY WIRES.
BLK
RED
FAN
MOTOR
BLK
3
2
1
MAX
LOW
HIGH
LLR
3
1
2
FIELD CONNECTED TO
REMOTE CONDENSER.
LLR INSTALLED ONLY ON
UNITS WITH DX COILS.
SELECT DRAWING
NOTES:
1. Make electrical installation in accordance
with job diagram, and in compliance with
national and local electrical codes.
2. Low limit thermostat (LLT) is installed on all
units with water coils.
3. Unused transformer leads are separately
insulated.
4. Transformer shown is wired for 240-v. The
208-v units are wired to 208-v tap.
LEGEND
DISC — Disconnect Switch
DX Direct Expansion
FU Fuse
GND — Ground
LLR DX Low Limit Switch
LLT Water Coil Low Limit Thermostat
PSC Permanent Split Capacitor
SW Switch
TRAN — Transformer
Splice Terminal Connection
Component Tie Point
Optional Wiring
Factory Wiring
Chassis Ground
Fig. 14 — 208/230-v PSC Motor without Controls
20
Page 21
SW2
SEE TAP
SW1
WHT/110
BLK/101
WHT/110
BLK/102
FU1
USE COPPER SUPPLY WIRES.
L1
N
GND
RED
WHT
WHT
WHT
BLK/100
BLK/103
DISC1
GRN
TRAN3
SEE NOTE 3
120VAC
BLK/109
WHT/111
TRAN1
BLK/109
FR1
24
RED/118
BLK
RED
WHT
FAN
MOTOR
BLK
3
2
1
MAX
LOW
HIGH
RED/118
24 VAC
RED/514
BRN/504
3 1
FR1
215/KLB405/NRB
BRN/513
RED/514
CBC1
432
SEE CONTROL DIAGRAM
FOR HARNESS WIRING
BRN/513
SELECT DRAWING
GRN
NOTES:
1. Make electrical installation in accordance with job diagram, and in compliance
with national and local electrical codes.
2. Low limit thermostat (LLT) is installed on all units with water coils.
3. Unused transformer leads are separately insulated.
LEGEND
CBC — Control Box Connection
DDC — Direct Digital Controls
DISC — Disconnect Switch
FR Fan Relay
FU Fuse
GND — Ground
PSC Permanent Split Capacitor
SW Switch
TRAN — Transformer
Harness Connection
Connection Point Splice
Splice Terminal Connection
Component Tie Point
Optional Wiring
Factory Wiring
Chassis Ground
Fig. 15 — 115-v PSC Motor with DDC Ready Option
21
Page 22
SW2
SEE TAP
SW1
WHT/110
BLK/101
WHT/110
BLK/102
FU1
USE COPPER SUPPLY WIRES.
L1
N
GND
RED
WHT
WHT
WHT
BLK/100
BLK/103
DISC1
GRN
TRAN3
SEE NOTE 3
120VAC
BLK/109
WHT/111
TRAN1
BLK/109
FR1
24
RED/118
BLK
RED
WHT
FAN
MOTOR
BLK
3
2
1
MAX
LOW
HIGH
RED/118
24 VAC
RED/514
BRN/504
SELECT DRAWING
GRN
3 1FR1
215/KLB405/NRB
BRN/513
RED/514
CBC1
472
SEE CONTROL DIAGRAM
FOR HARNESS WIRING
BRN/505
24
DX1
BLU/508
BLU/507
FIELD CONNECTED TO
REMOTE COMPRESSOR/
CONDENSER UNIT
3 1DX1
BLU/517
3
LLR
3
1
2
8
9
ORN/518
GRA/519
LEGEND
CBC — Control Box Connection
DDC — Direct Digital Controls
DISC — Disconnect Switch
DX Direct Expansion
FR Fan Relay
FU Fuse
GND — Ground
LLR DX Low Limit Switch
PSC Permanent Split Capacitor
SW Switch
TRAN — Transformer
Harness Connection
Connection Point Splice
Splice Terminal Connection
Component Tie Point
Optional Wiring
Factory Wiring
Chassis Ground
NOTES:
1. Make electrical installation in accordance with job diagram, and in
compliance with national and local electrical codes.
2. Low limit thermostat (LLT) is installed on all units with water coils.
3. Unused transformer leads are separately insulated.
Fig. 16 — 115-v PSC Motor with DDC Ready Option and DX Cooling
22
Page 23
WHT
WHT
BLK/103
BLK/109
TRAN1
BLK/109
FR1
BLK/RED
SW2
SEE TAP
RED
BLK/RED
WHT
TRAN3
SEE NOTE 3
SEE NOTE 4
BLK/YEL208V
240V
SEE NOTE 4
SW1
BLK/101
BLK/108
BLK/102
FU1
L1
L2
GND
BLK/100
DISC1
GRN
BLK/106 BLK/107
FU2
BLK/105
USE COPPER SUPPLY WIRES.
240 V
208 V
BLK/110 BLK/108
COM
SEE NOTE 4
BLK
RED
WHT
FAN
MOTOR
BLK
3
2
1
MAX
LOW
HIGH
24
24 VAC
SELECT DRAWING
RED/514
BRN/504
3 1
FR1
215/KLB405/NRB
BRN/513
RED/514
CBC1
432
SEE CONTROL DIAGRAM
FOR HARNESS WIRING
BRN/513
GRN
LEGEND
CBC — Control Box Connection
DDC — Direct Digital Controls
DISC — Disconnect Switch
FR Fan Relay
FU Fuse
GND — Ground
PSC Permanent Split Capacitor
SW Switch
TRAN — Transformer
Harness Connection
Connection Point Splice
Splice Terminal Connection
Component Tie Point
Optional Wiring
Factory Wiring
Chassis Ground
NOTES:
1. Make electrical installation in accordance with job diagram, and in
compliance with national and local electrical codes.
2. Low limit thermostat (LLT) is installed on all units with water coils.
3. Unused transformer leads are separately insulated.
4. Transformer is wired for 240-v. The 208-v units are wired to 208-v tap.
Fig. 17 — 208/230-v PSC Motor with DDC Ready Option
23
Page 24
BLK/104
LLT
(SEE NOTE 2)
3
1
NOTE 2
2
24 VAC
RED/502
TRAN1
WHT/110
SW1
BLK/101
WHT/110
BLK/102
FU1
USE COPPER SUPPLY WIRES
115 V
L1
N
GND
BLK/100
DISC1
GRN
BLK/109
120VAC
BLK/109
WHT/111WHT/111
LOW
MED
HIGH
MAX
24Vac
SPEED BOARD
BLU/EC9
GRN
WHT
BLK
ORN/EC2
3 WIRE
POWER
CABLE
ECM
1
3
12
2
9
14
5
4
3
2
1
16 PIN
RECEPTACLE
ON MOTOR
5 PIN
RECEPTACLE
ON MOTOR
11
5
BRN
SW2
RED/EC12
RED/EC12
YEL/EC5
SEE NOTE 3
BRN/EC1
MAX
LOW
HIGH
BLK/103
LLR
3
1
2
RED/503
RED/502
WHT
BLK
GRN
LEGEND
DISC — Disconnect Switch
DX Direct Expansion
ECM — Electronically Commutated Motor
ESP External Static Pressure
FU Fuse
GND — Ground
LLR DX Low Limit Switch
LLT Water Coil Low Limit Thermostat
SW Switch
TRAN — Transformer
Harness Connection
Connection Point Splice
Splice Terminal Connection
Component Tie Point
Optional Wiring
Factory Wiring
Chassis Ground
Earth Ground
NOTES:
1. Make electrical installation in accordance with job diagram, and in com-
pliance with national and local electrical codes.
2. Low limit thermostat (LLT) is installed on all units with water coils.
3. Wire YEL/EC5 factory connected to LOW. Positions MED, HIGH, MAX
are for field use with increased ESP.
Fig. 18 — 115-v ECM Motor without Controls
24
Page 25
BLK/104
LLT
3
2
1
NOTE 2
RED/502
BLK/109
BLK/108
LOW
MED
HIGH
MAX
24Vac
SPEED BOARD
BLU/EC9
GRN
WHT
BLK
ORN/EC2
3 WIRE
POWER
CABLE
ECM
1
3
12
2
9
14
5
4
3
2
1
16 PIN
RECE PTACLE
ON MOTOR
5 PIN
RECE PTACLE
ON MOTOR
11
5
BRN
SW2
RED/EC12
RED/EC12
YEL/EC5
SEE NOTE 3
BRN/EC1
MAX
LOW
HIGH
BLK/103
SW1
BLK/101
BLK/108
BLK/102
FU1
208/230V
L1
L2
GND
BLK/100
DISC1
GRN
BLK/106
BLK/107
FU2
BLK/105
24VAC
TRAN1
240 V
208 V
COM
SEE NOTE 4
LLR
3
FIELD CONNECTED TO
REMOTE CONDENSER.
LLR INSTALLED O NLY ON
UNITS WITH DX COILS.
WHT
RED/502RED/503
GRN
BLK
BLK/109
(SEE NOTE 2)
2
1
NOTES:
1. Make electrical installation in accordance with job diagram, and in compliance with national and
local electrical codes.
2. Low limit thermostat (LLT) is installed on all units with water coils.
3. Wire YEL/EC5 factory connected to LOW. Positions MED, HIGH, MAX are for field use with ESP.
4. Transformers shown wired for 240-v. However, transformers are factory-wired to match the volt-
age listed on the unit nameplate.
LEGEND
DISC — Disconnect Switch
DX Direct Expansion
ECM — Electronically Commutated Motor
ESP External Static Pressure
FU Fuse
GND — Ground
LLR DX Low Limit Switch
LLT Water Coil Low Limit Thermostat
SW Switch
TRAN — Transformer
Harness Connection
Connection Point Splice
Splice Terminal Connection
Component Tie Point
Optional Wiring
Factory Wiring
Chassis Ground
Earth Ground
Fig. 19 — 208/230-v ECM Motor without Controls
25
Page 26
24 VAC
GRN
RED/501
TRAN1
BRN/504WHT/110
WHT
SW1
BLK/101
WHT/110
BLK/102
FU1
USE COPPER SUPPLY WIRES.
115 V
L1
N
GND
BLK/100
BLK
DISC1
GRN
BLK/109
120VAC
BLK/109
WHT/111WHT/111
LOW
MED
HIGH
MAX
24Vac
SPEED BOARD
BLU/EC9
GRN
WHT
BLK
ORN/EC2
3 WIRE
POWER
CABLE
EC FAN
MOTOR
1
3
12
2
9
14
5
4
3
2
1
16 PIN
RECEPTACLE
ON MOTOR
5 PIN
RECEPTACLE
ON MOTOR
11
5
BRN
SW2
RED/EC12
RED/EC12
YEL/EC5
SEE NOTE 3
FR1
24
RED/501
3 1
FR1
215/KLB405/NRB
BRN/513
RED/514
CBC1
432
SEE CONTROL DIAGRAM
FOR HARNESS WIRING
BRN/505
BRN/EC1
RED/514
RED/502RED/503
MAX
LOW
HIGH
LEGEND
CBC — Control Box Connection
DDC — Direct Digital Controls
DISC — Disconnect Switch
EC Electronically Commutated
ECM — Electronically Commutated Motor
ESP External Static Pressure
FR Fan Relay
FU Fuse
GND — Ground
SW Switch
TRAN — Transformer
Harness Connection
Connection Point Splice
Splice Terminal Connection
Component Tie Point
Optional Wiring
Factory Wiring
Chassis Ground
Earth Ground
NOTES:
1. Make electrical installation in accordance with job diagram, and in
compliance with national and local electrical codes.
2. Low limit thermostat (LLT) is installed on all units with water coils.
3. Wire YEL/EC5 factory connected to LOW. Positions MED, HIGH, and
MAX are for field use with increased ESP.
Fig. 20 — 115-v ECM Motor with DDC Ready Controls
26
Page 27
24 VAC
GRN
RED/501
TRAN1
BRN/504WHT/110
WHT
SW1
BLK/101
WHT/110
BLK/102
FU1
USE COPPER SUPPLY WIRES.
115 V
L1
N
GND
BLK/100
BLK
DISC1
GRN
BLK/109
120VAC
BLK/109
WHT/111WHT/111
LOW
MED
HIGH
MAX
24Vac
SPEED BOARD
BLU/EC9
GRN
WHT
BLK
ORN/EC2
3 WIRE
POWER
CABLE
EC FAN
MOTOR
1
3
12
2
9
14
5
4
3
2
1
16 PIN
RECEPTACLE
ON MOTOR
5 PIN
RECEPTACLE
ON MOTOR
11
5
BRN
SW2
RED/EC12
RED/EC12
YEL/EC5
SEE NOTE 3
FR1
24
RED/501
3 1
FR1
215/KLB405/NRB
BRN/513
RED/514
CBC1
472
SEE CONTROL DIAGRAM
FOR HARNESS WIRING
BRN/505
BRN/EC1
RED/511
RED/502RED/503
MAX
LOW
HIGH
24
DX1
BLU/508
BLU/507
FIELD CONNECTED TO
REMOTE COMPRESSOR/
CONDENSER UNIT
3 1DX1
BLU/517
3
BRN/506
LLR
3
1
2
8
9
ORN/518
GRA/519
LEGEND
CBC — Control Box Connection
DDC — Direct Digital Controls
DISC — Disconnect Switch
DX Direct Expansion
EC Electronically Commutated
ECM — Electronically Commutated Motor
ESP External Static Pressure
FR Fan Relay
FU Fuse
GND — Ground
LLR DX Low Limit Switch
LLT Water Coil Low Limit Thermostat
SW Switch
TRAN — Transformer
Harness Connection
Connection Point Splice
Splice Terminal Connection
Component Tie Point
Optional Wiring
Factory Wiring
Chassis Ground
Earth Ground
NOTES:
1. Make electrical installation in accordance with job diagram, and in
compliance with national and local electrical codes.
2. Low limit thermostat (LLT) is installed on all units with water coils.
3. Wire YEL/EC5 factory connected to LOW. Positions MED, HIGH, and
MAX are for field use with increased ESP.
Fig. 21 — 15-v ECM Motor with DDC Ready Controls and DX Cooling
27
Page 28
RED/501
901/KLB901/KLB
BLK/108
SW1
BLK/101
BLK/108
BLK/102
FU1
208/230V
L1
L2
GND
BLK/100
DISC1
GRN
BLK/106 BLK/107
FU2
BLK/105
USE COPPER SUPPLY WIRES.
24VAC
TRAN1
240 V
208 V
GRN
COM
SEE NOTE 4
WHT
LOW
MED
HIGH
MAX
24Vac
SPEED BOARD
BLU/EC9
GRN
WHT
BLK
ORN/EC2
3 WIRE
POWER
CABLE
BRN
SW2
RED/EC12
RED/EC12
YEL/EC5
SEE NOTE 3
FR1
24
RED/501
3 1
FR1
215/KLB405/NRB
BRN/513
RED/514
CBC1
432
SEE CONTROL DIAGRAM
FOR HARNESS WIRING
BRN/505
BRN/EC1
RED/514
RED/502RED/503
MAX
LOW
HIGH
EC FAN
MOTOR
1
3
12
2
9
14
5
4
3
2
1
16 PIN
RECEPTACLE
ON MOTOR
5 PIN
RECEPTACLE
ON MOTOR
11
5
BLK
BRN/504
LEGEND
CBC — Control Box Connection
DDC — Direct Digital Controls
DISC — Disconnect Switch
EC Electronically Commutated
ECM — Electronically Commutated Motor
ESP External Static Pressure
FR Fan Relay
FU Fuse
GND — Ground
SW Switch
TRAN — Transformer
Harness Connection
Connection Point Splice
Splice Terminal Connection
Component Tie Point
Optional Wiring
Factory Wiring
Chassis Ground
Earth Ground
NOTES:
1. Make electrical installation in accordance with job diagram, and in
compliance with national and local electrical codes.
2. Low limit thermostat (LLT) is installed on all units with water coils.
3. Wire YEL/EC5 factory connected to LOW. Positions MED, HIGH, and
MAX are for field use with increased ESP.
4. Transformers shown wired for 240-v; however, transformers are nor-
mally factory wired to match voltage listed on the unit nameplate.
Fig. 22 — 208/230-v ECM Motor with DDC Ready Controls
28
Page 29
NEUTRAL
EVO/ECM-ACU
Signal
Common
RPM
24Vac
NEUTRAL
24Vac
BLK/109
SW1
BLK/101 BLK/102
FU1
115 V
L1
N
GND
BLK/100
DISC1
GRN
USE COPPER SUPPLY WIRES.
24VAC120VAC
BLK/109
WHT/111
GRN
RED/502
TRAN1
WHT/110
RED/503
BRN/504
WHT/110
WHT
WHT/111
GRN
WHT
BLK
3 WIRE
POWER
CABLE
BRN
BRN/501
BLK/103
BLK/104
BLK/506
WHT/505
BLK
BLK/104
LLT*
321
NOTE 2
RED/503
BLK/506
WHT/505
BRN/504
BLK
WHT WHT
BLK
RED
RED
BRN
BRN/501
RED/507
NOTE: Wires above are insulated
after unit run-test
24V-Hot
24V-Neutral
+ 2-10Vdc Signal
Signal Common
A signal < 1 Vdc
will stop the fan.
LLR*
3
1
2
FIELD CONNECTED TO
REMOTE CONDENSER.
LLR INSTALLED ONLY ON
UNITS WITH DX COILS.
LOW
MED
HIGH
MAX
24Vac
SPEED BOARD
YEL/EC5
SEE NOTE 3
16 PIN
RECEPTACLE
ON MOTOR
5 PIN
RECEPTACLE
ON MOTOR
EC FAN
MOTOR
3
8
16
5
4
3
2
1
15
10
5
YEL
RED/507
RED/508
RED/508
FR
Optional Field Provided and
Installed Fan Relay, Break
wire RED/507 and connect as
shown.
Do NOT break motor
power wiring to start/stop
the fan motor as this will
significantly decrease
the motor life. Break the
24V control wiring as
shown (upper right
corner of drawing) to
start/stop the motor.
LEGEND
DISC — Disconnect Switch
DX Direct Expansion
ECM — Electronically Commutated Motor
ESP External Static Pressure
FR Fan Relay
FU Fuse
GND — Ground
LLR DX Low Limit Switch
LLT Water Coil Low Limit Thermostat
SW Switch
TRAN — Transformer
Harness Connection
Connection Point Splice
Splice Terminal Connection
Component Tie Point
Optional Wiring
Factory Wiring
Chassis Ground
Earth Ground
*LLT will be replaced by LLR on units with DX coils.
NOTES:
1. Make electrical installation in accordance with job diagram, and in
compliance with national and local electrical codes.
2. Low limit thermostat (LLT) is installed on all units with water coils.
3. Wire YEL/EC5 factory connected to LOW. Positions MED, HIGH, and
MAX are for field use with increased ESP.
Fig. 23 — 115-v Variable Speed ECM Motor without Controls
29
Page 30

Step 5 — Make Duct Connections

If applicable, install all ductwork to and from unit in accordance with all applicable codes. Duct construction must allow unit to operate within duct external static pressure limits as shown on job submittals and in Tables 5 and 6. Duct opening should be the same size as the unit. For 40UH units ducted to multiple open­ings, allow adequate straight duct, as shown below, immediately after the unit.
.
40UH 075 100 125 150 200
Minimum Straight Duct Required (Length in inches)
45 52 58 63 75
CAUTION
Units designed to operate with ductwork may be damaged if operated without intended ductwork attached.
Ensure that units ducted to multiple openings have sufficient straight duct immediately after the unit.
Table 5 — Unit Ventilator Airflow — PSC Motor*
FACTORY SETTINGS — CHILLED WATER COIL APPLICATIONS
Unit Speed
40UV050
40UV,UH075
40UV,UH100
40UV,UH125
40UV,UH150
Max 522 510 497 485 490 489 457
High 503 490 476 464 473 476 444
Low 458 449 440 425 452 455 430 Max 806 778 750 747 766 732 697
High 682 664 645 629 621 596 570
Low 569 554 539 527 533 514 495 Max 1064 1033 1001 1013 973 980 967
High 662 659 655 642 763 740 717
Low 530 519 507 503 498 501 504 Max 1295 1285 1215 1218 1239 1250 1175
High 899 930 876 865 852 846 846
Low 568 616 597 570 568 558 573 Max 1542 1480 1500 1484 1468 1482 1374
High 1071 1068 1065 1034 1033 1031 1013
Low 812 801 790 881 848 842 799
1-row 2-row 3-row 4-row 5-row 6-row 7-row
Units provided with outside air must utilize the low-temperature safety switch to prevent coil freeze-up.
Insulate all ductwork as required. Use flexible connections to minimize duct-to-unit alignment problems and noise transmis­sion where specified.
Install ductwork, grilles, and plenums so that they do not restrict access to filter.
Cut openings for supply and return air grilles, thermostats, and switch plates where specified on job drawings. Be careful not to cut wires, piping, or structural supports. Use a steel thermostat shield ring to protect drywall from thermostat wir­ing where applicable.
Prevent dust and debris from settling in unit. If wall finish or col­or is to be applied by spraying, cover all openings to prevent spray from entering unit.
Approximate Air Delivery (Cfm)
FACTORY SETTINGS — ELECTRIC HEAT/DX COIL APPLICATIONS
Unit Speed
Max 522 510 497 485 490 489 457
40UV050
40UV,UH075
40UV,UH100
40UV,UH125
40UV,UH150
LEGEND
CW — Chilled Water Applications DX — Direct Expansion HW — Hot Water PSC — Permanent Split Capacitor
*Standard on sizes 050-150. †DX cooling applications are only available in 4-row cooling configuration.
High 503 490 476 464 452 455 430
Low 458 449 440 425 410 414 406 Max 806 778 750 747 766 732 697
High 682 664 645 629 621 596 570
Low 569 554 539 527 533 514 495 Max 1064 1033 1001 1013 973 980 967
High 794 788 782 773 857 834 810
Low 662 659 655 642 628 620 611 Max 1295 1285 1215 1218 1239 1250 1175
High 1055 1040 1024 995 1099 1091 1052
Low 738 767 732 719 987 986 964 Max 1542 1480 1500 1484 1468 1482 1374
High 1285 1257 1229 1248 1246 1239 1199
Low 934 928 922 901 1033 1031 1013
1-row 2-row 3-row 4-row 5-row 6-row 7-row
Approximate Air Delivery (cfm)
NOTE: Use the table below to determine the heating and cooling coil com­binations available with PSC motor operation.
COOLING COIL
5 Rows CW 1 or 2 rows N/A 3 elements
4 Rows CW or DX† 3 rows 1 or 2 rows 4 elements
3 Rows CW 4 rows 1 or 2 rows 5 or 6 elements
HW Steam Electric
HEATING COIL
30
Page 31
Table 6 — Unit Ventilator Airflow — ECM Airflow
APPROXIMATE AIR DELIVERY (Cfm)
UNIT SIZE
40UV050
40UV,UH075
40UV,UH100
40UV,UH125
40UV,UH150
40UH200
LEGEND NOTES:
3-4EH/DX — Direct Expansion Coil Applications with 3 to
5-6EH 5 to 6 Elements of Electric Heat CW Chilled Water Applications ECM Electronically Commutated Motor ESP External Static Pressure
MOTOR
HP
1
/
3
1
/
3
1
/
3
1
/
2
1
/
2
3
/
4
4 Elements of Electric Heat
COIL TYPE
CW 499 336 248
3-4EH/DX 499 419 336
5-6EH 491 380 324
CW 747 484 346 753 548 432 752 530 427 751 541 386
3-4EH/DX 747 644 498 753 609 472 752 612 470 751 618 498
5-6EH 755 645 583 746 598 539 755 585 554 765 610 542
CW 997 703 505 987 693 543 1012 663 483 994 692 480
3-4EH/DX 997 853 615 987 850 639 1012 823 626 994 819 618
5-6EH 1016 819 719 1002 851 709 1024 798 787 1024 820 734
CW 1266 880 657 1239 905 609 1235 898 676 1231 898 627
3-4EH/DX 1266 1023 769 1239 1055 758 1235 1037 765 1231 1010 778
5-6EH 1259 1049 897 1239 995 888 1226 995 888 1253 994 919
CW 1503 1033 775 1479 1046 712 1494 1020 770 1486 1075 737
3-4EH/DX 1503 1246 956 1479 1216 965 1494 1209 927 1486 1222 917
5-6EH 1517 1222 1068 1490 1206 1087 1498 1159 1120 1503 1188 1074
ALL 2014 1384 1023 1981 1386 971 1965 1385 997 1814 1354 993
Low Position
(0.0 in. wg)
Max High Low Max High Low Max High Low Max High Low
ESP Speed Board Position
Med Position
(0.10 in. wg)
1. Factory default is Low Position.
2. Med, High, and Max positions are field settings.
High Position
(0.25 in. wg)
Max Position
(0.45 in. wg)

Step 6 — Make Final Preparations

1. Turn power off (lock out and tag electrical disconnect).
2. Install thermostats and perform any other final wiring as applicable.
3. Clean dirt, dust, and other construction debris from unit interior. Be sure to check fan wheel and housing.
4. Rotate fan wheel by hand to be sure it is free and does not rub on housing.
5. Be sure drain line is clear and is properly and securely positioned. Pour water into drain to check operation.
6. Vent all air from unit coil and related piping. The coil is provided with a Schrader or screw-type manual air vent on the return manifold to release air from the coil.
NOTE: This vent is not adequate for removing air from the building piping system. Customer must provide for venting of the piping system.
a. Pressurize the building piping system with water.
Vent trapped air at system vents.
b. Schrader type vent: Remove cap. Depress valve at
coil vent until air is expelled from the unit. Release valve. Re-install cap.
c. Screw type vent: Back out manual setscrew until air
is expelled. Re-tighten setscrew.
d. Automatic type vent: Trapped air will be vented
automatically. Vent releases air slowly, usually drip­ping water into the drain pan in the process.
Make sure all service valves are open and that motorized control valves, if supplied, are set for automatic operation.
7. Check all control valves in the system for proper opera­tion in accordance with valve manufacturer’s instruc­tions.
8. Install filter in frame at front of coil. If field-supplied filters are used, be sure size is correct. See Table 1 for filter data.
9. Ensure all panels and filters are installed before checking fan operation. Turn on unit power. Check fan and motor operation.
.
IMPORTANT: Do not start up or operate unit without filter and panels installed. Be sure filter and unit interior are clean.

START-UP

Start-up procedures vary depending on time of year (summer or winter) and building characteristics (new building/old building, occupied/unoccupied, etc.). All building windows and door should be closed before starting the unit. Close the unit’s outdoor air dampers. Bathroom and kitchen exhaust fans should be off.
Start-up in the cooling mode requires proper care to avoid con­densation problems. Condensation forms on surfaces that are colder than the dew point of the surrounding air. If a unit is start­ed and is piped with low-temperature chilled water in a hot, hu­mid atmosphere, condensation will form on many parts of the unit. In order to avoid excessive condensation, higher tempera­ture water should initially be used (approximately 65°F to 70°F), reduce the chilled water flow rate (GPM) and set the fan to high speed for maximum airflow.
As the building temperature drops, the chilled water temperature can be gradually reduced until it reaches 50°F. At this point the outside-air damper can be opened to take in minimum outside air. When the chilled water temperature is reduced to its design point, the exhaust fans can be turned on.
Maximum entering water temperature is 180°F, unless name­plate indicates 200°F.
CAUTION
If unit is marked for 200°F maximum entering water tem­perature, customer must ensure that water vaporization does not occur, especially at higher elevations when enter­ing water temperatures are greater than 190°F.
31
Page 32
CAUTION
Ensure that the unit is protected against freezing condi­tions. If locking quadrant manual damper operator is pro­vided, set to desired position. If damper actuator is provided, ensure that actuator opens the damper when the fan turns on, and closes when the fan stops.

SERVICE

WARNING
Lock out and tag all power supplies to equipment and con­trols prior to servicing unit. Follow all safety codes. Failure to do so could result in personal injury.

Periodic Maintenance Checklist

Monthly
Inspect air filter. Replace any filters.
Inspect drain pan and clean if necessary.
Ye a rl y
Inspect and clean coils.
Inspect fan wheels and housing for damage. Ensure that wheels move freely by hand.
Clean and tighten all electrical connections.

Preventing Excessive Condensation on Unit

Excessive condensation can be caused by running chilled water through a unit with the unit fan off. If fan cycling is used, a water flow control valve should be installed to shut off the water when the fan stops.
Other methods of control which avoid condensation problems are as follows:
1. If condensation is forming on the unit, verify the chilled water valve is closing off tightly. Dirt or debris may pre­vent the valve from closing completely.
2. Continuous fan operation with motorized chilled water valve controlled by a thermostat.
3. Continuous fan operation with thermostat control to switch fan from high to low speed (instead of off).

Check Drain

Check drain pan, drain line, and trap at start of each cooling sea­son. A standard type pipe cleaner for to be sure pipe is clear of obstruction so that condensate is car­ried away. Check the drain line at filter cleaning time during the cooling season. Be sure that debris has not fallen into unit through supply air grille.
3
/4-in. ID pipe can be used

Fan Motor Bearings

Standard motors are permanent split capacitor, which are equipped with permanently sealed and lubricated bearings. No lubrication is required unless special motors have been supplied or unusual operating conditions exist.

Fan Shaft Ball Bearing

The mid and inboard bearings are permanently sealed and lubri­cated. No additional maintenance is required. The end bearings must be lubricated at the start of each cooling and heating sea­son. Add 5 to 10 drops of SAE 20 or 30 non-detergent based oil to the bearing.

Clean Fan Wheel

For access to fan assembly, remove discharge grille (if supplied). If unit is connected to ductwork, remove front (40UV) or bottom (40UH) panel, separate fan shaft from motor at bushing, remove motor, and slide fan assembly from track. Use a stiff brush or
vacuum to remove dirt and debris from scroll. Wipe all fan sur­faces with a damp cloth. Reassemble as necessary.

Clean or Replace Air Filters

At the start of each cooling season and after each month of oper­ation (more or less depending on operating conditions), replace the throwaway filter or clean the permanent filter.

THROWAWAY FILTER

Replace filter with a good quality filter of the correct size. Do not attempt to clean and reuse disposable filters. See Table 1 for fil­ter sizes.

PERMANENT FILTER (FIBER TYPE)

1. Tap on solid surface to dislodge heavy particles.
2. Wash in hot water. If needed, use mild solution of com­mercial solvent such as sal soda or trisodium phosphate.
3. Set filter on end so that water drains out through slots in frame. Allow filter to dry thoroughly.
4. Recharge filter with recharging oil. Three ounces is suffi­cient for a medium size filter. Oil may be applied by insect spray gun. For easier spraying, the oil can be warmed.
5. If the filter is dipped in the recharging oil, remove it immediately and allow to drain through slots in frame.
6. Replace filter in unit.
If another type of filter is used, follow the filter manufacturer’s instructions.

ECM Motor Removal and Re-installation (see Fig. 24)

Carrier unit ventilators utilize an electronically commutated mo­tor (ECM) to drive the indoor fan.
The ECM is a factory-programmed motor that is standard with factory-supplied UV Open controls and units without factory­supplied controls that are used in high-static applications or high-capacity coils.
The ECM is programmed with an algorithm that maintains a constant torque, as the static pressure on the system varies. For example, as the filter pressure drop increases due to dirt, the fan will increase speed (rpm) to maintain the cfm.
The ECM is identified by the two electrical receptacles located on the housing. See Fig. 18-24.
The first receptacle is a 5-row in-line connector that feeds the motor line voltage. This may be either 115 volts or 230 volts. Units that are wired for 230 volts have a jumper between termi­nals 1 and 2 on this plug (see wiring diagram).
The second receptacle on the motor is a 16-pin connector and is used for speed switching. This is a low voltage (24-v) connec­tion. There is a jumper wire between terminals 1 and 3. This is a 24-v ground. Voltage is present at all times when the motor is en­ergized.
NOTE: A time delay exists between the time the motor speed is switched and the motor’s reaction. This is designed into the elec­tronics and does not indicate motor problems.
When replacing the motor, note the following:
Check the part number of the old motor against that of the replacement. There is a tag indicating the eight-digit part number and begins with UVE. This is the program number used for this motor.
32
Page 33
The motor must be installed per the instructions below. It is important to maintain the dimension between the fan compartment bulkhead and the coupling.
IMPORTANT: If a replacement cooling shroud has been supplied, it should be installed and the old one discarded. The motor shroud directs cooling air across the motor to provide proper cooling. Never run the motor without the cooling shroud in place. Ensure the shroud inlet ring does not touch the motor; a gap of
1
/16-in. to 1/8-in. is acceptable.
motor mounting bracket from the bulkhead. Loosen only the ‘belly band’ securing the motor in the mount.
6. Re-install the motor in the ‘belly band.’
7. Ensure the blower wheels are centered within the fan housings (between the inlet rings) before securing the motor shaft coupling.
CAUTION
The motor electronics will fail prematurely if no air is able to circulate over the motor.
CAUTION
Ensure the unit is completely assembled when checking the fan speed. Replace all panels, including the filters, before checking the fan for operation. When the internal pressure drops at a normal condition, the loading on the motor will be such that the fan can come up to selected speed.
Failure to ensure unit is completely assembled may result in reduced life of unit and/or personal injury.
To remove and re-install the motors, proceed as follows; refer to Fig. 24:
1. Remove the wire plugs from the motor.
2. Remove the 2 screws holding the motor shroud to the bulkhead.
3. Slide the shroud off the motor to the right.
4. Loosen the 3 setscrews on the shaft coupling between the motor shaft and the fan shaft.
5. Loosen the motor ‘belly band’ and slide motor out of the ‘belly band’ to the right. It is unnecessary to remove the
8. Ensure the motor housing is at least 1-in. from the bulkhead so that air will be able to circulate over the motor.
9. For vertical type units, position the motor so that the motor wire plugs are front facing on a horizontal plane. For horizontal type units with ceiling mounts, position the motor so that the motor wire plugs are front facing on a vertical plane.
10. Secure the 3 setscrews on the shaft coupling when the motor is properly positioned and the blower wheels are centered within their housing.
11. Re-secure the motor ‘belly band’ around the motor.
12. Re-install the motor shroud. It is important that the motor shroud be installed prior to operation of the motor. Ensure the venturi is installed on the motor shroud.
13. Re-secure the two screws holding the motor shroud to the bulkhead.
14. Re-install the motor wire plugs.
33
Page 34
SHAFTED END FACE
COUPLING INSIDE FACE
COUPLING FACE
MOTOR BEARING FACE
INSULATION FACE
MOTOR (ECM)
CENTER SHROUD OPENING OVER MOTOR ELECTRICAL CONNECTIONS.
INSTALL MOTOR AND COOLING SHROUD ELECTRICAL CONNECTIONS FACING UNIT FRONT.
MOTOR SHAFT
COUPLING
FAN SHAFT
.125 .032
+ –
0.500 0.063
+ –
1.000 0.063
+ –
NOTES:
1. All dimensions shown in inches.
2. Not all components shown for clarity.
3. Motor shroud not shown for clarity. Install prior to operation.
4. Refer to Fig. 30, Item 4 for cooling shroud installation.
Fig. 24 — 40UV,UH Ventilator Blower Section Assembly — ECM Motor Detail
34
Page 35
Blower Assembly Section Removal and Re­installation (see Fig. 25)
WARNING
Lock out and tag all power supplies to equipment and con­trols prior to servicing unit. Follow all safety codes. Failure to do so could result in personal injury.
CAUTION
Be careful with all components during installation, espe­cially the bearing and plastic blower wheels. Any extreme force applied to these components can cause unintended damage and void the unit warranty.
To remove blower assembly:
1. Turn off power to the unit.
IMPORTANT: Tag each right front panel (40UV) or middle bottom panel (40UH) for each unit. Panels have electrical information specific to each unit.
2. Remove all front (40UV) or bottom (40UH) panels. Remove end panels.
3. Remove top panel with vanes and screens to the side (40UV). Remove ductwork if required and remove top (40UV) or front (40UH) dis­charge plenum.
4. Remove
1
/4-in. head screws along length of unit that secure coil baffle to blower section. See Item 5 in Fig. 25.
5. Remove four
1
/4-in. head screws that connect the blower section sides to the coil section sides. See Item 2 in Fig. 25.
6. Remove the
1
/4-in. head screw from the center of the blower deck that attaches the blower deck to the pipe chase. See Item 1 in Fig. 25.
7. Remove six
1
/4-in. head screws attaching coil baffle to
coil section. See Item 4 in Fig. 25.
8. Remove the harness connector(s) from the motor.
9. Remove the
1
/4-in. head screw from the green ground wire that connects the motor to frame if unit has a PSC (permanent split capacitor) motor. The ECM motors are grounded through the harness.
10. Remove the two carriage bolts retaining the front brace to the frame sides. See Item 6 in Fig. 25.
11. Remove the four nuts retaining the blower section to the back (40UV) or top (40UH) frame. See Item 3 in Fig. 25.
5
/16-in. nut driver and set optional
12. Remove the two
5
/16-in. nuts retaining the inboard bear­ing bracket to the pipe chase (40UV,UH150 units only). See Item 6 in Fig. 26.
13. Remove blower section from frame.
To re-install blower assembly to frame of unit:
1. Re-install blower section into frame assembly.
2. Tighten the four
5
/16-in. nuts retaining blower section to
frame. See Item 3 in Fig. 25.
3. Tighten the two
5
/16-in. nuts retaining the inboard bearing bracket to the pipe chase (40UV,UH150 units only). See Item 6 in Fig. 26.
4. Re-install two carriage bolts that attach the front brace to the frame sides. See Item 6 in Fig. 25.
5. Rotate the fan shaft by hand to ensure that fans are unrestricted and can rotate freely. Check for any fan obstructions.
6. Re-attach green ground wire that connects the motor to the frame with
1
/4-in. head screw if unit has a PSC motor.
The ECM motors are grounded through the harness.
7. Connect harness connector(s) to motor.
8. Re-install the coil baffle using six
1
/4-in. head screws that attach the coil baffle to the coil section. See Item 4 in Fig. 25.
9. Re-install the
1
/4-in. head screw at center of blower deck attaching blower deck to pipe chase. See Item 1 in Fig. 25.
10. Re-install the four
1
/4-in. head screws holding the blower section sides to the coil section sides. See Item 2 in Fig. 25.
11. Re-install
1
/4-in. head screws along length of the unit, securing coil baffle to the blower section. See Item 5 in Fig. 25.
12. Re-install optional vanes and screens and install top panel (40UV). Re-install top (40UV) or front (40UH) discharge plenum and ductwork, if required.
13. Re-install front (40UV) or bottom (40UH) panels. Re­install end panels. Ensure that tag on each right front
panel (40UV) or middle bottom panel (40UH) matches unit tag.
14. Restore power to unit.
IMPORTANT: Disassembly order is not as important as reassembly. The assembly order of the bearing bracket installation is critical to having a well balanced and sound blower deck.
35
Page 36
2
3
4
1
6
5
FRONT BRACE
PIPE CHASE
COIL SECTION
BLOWER SECTION
DAMPER SECTION
COIL SECTION
FILTER DOOR RETAINER CLIPS (SEE NOTE 3)
COIL BAFFLE
RETURN AIR TEMPERATURE SENSOR (OPTIONAL) OPENING
DISCHARGE AIR TEMPERATURE SENSOR (OPTIONAL) OPENING
MOTOR & COUPLING SETCREW ACCESS
MOTOR
MOTOR ELECTRICAL BOX
NOTES:
1. Unit shown in vertical orientation. Drawing applies to horizontal and vertical units.
2. Not all components shown for clarity.
3. 40UV,UH125-200 units only.
LEGEND
1—
1
/4-in. Screw
2—
1
/4-in. Screw
3—5/16-in. Nut 4—
1
/4-in. Screw
5—
1
/4-in. Screw
6—Carriage Bolt
Fig. 25 — 40UV, UH Ventilator Blower Section
36
Page 37
1
2
3
4
5
7
6
SEE DETAIL A
SEE DETAIL A
6
SEE NOTE 4
BOTTOM VIEW
DETAIL A
NOTES:
1. Not all components shown for clarity.
2. This drawing applies to 1500 cfm units only.
3. Remove shaft, motor, and coupling prior to
bearing removal.
4. Refer to Fig. 24 and 31 for motor-coupling and
coupling-shaft clearances.
LEGEND
1—Shaft 2—Coupling 3—Motor 4—
1
/2-in. Bolt
5—Bearing 6—
5
/16-in. Nut
7—Hex Nut
Fig. 26 — 40UV,UH Ventilator Inboard Bearing (40UV,UH150 Only)
37
Page 38

Coil Assembly Removal and Re-installation (see Fig. 27)

WARNING
Lock out and tag all power supplies to equipment and con­trols prior to servicing unit. Follow all safety codes. Failure to do so could result in personal injury.
CAUTION
Turn off all power supplies to equipment and controls. Fail­ure to do so may cause personal injury or damage to the unit.
To remove coil assembly:
1. Turn off power to the unit.
IMPORTANT: Tag each right front panel (40UV) or middle bottom panel (40UH) for each unit. Panels have electrical information specific to each unit.
2. Remove all front (40UV) or bottom (40UH) panels. Remove end panels.
3. Remove secure coil baffle to blower section. See Item 2 in Fig. 27.
4. Remove four section sides to the coil section sides. See Item 1 in Fig. 27.
5. Remove actuator to damper shaft OR locking quadrant assembly to damper shaft. Remove OA actuator or locking quad­rant assembly.
6. Tag low-limit thermostat wiring and terminals. Discon­nect low-limit thermostat wiring (right end compart­ment).
1
/4-in. head screws along length of unit that
1
/4-in. head screws that connect the blower
1
/4-in. head screws attaching outside air (OA)
7. Drain water and/or recover refrigerant in accordance with all applicable codes. Disconnect piping from coil connections.
8. Tag optional electric heat element wire terminations for later reconnection. Disconnect element wires from elec­tric heat control box (remove coil baffle for access).
9. Remove the four
5
/16-in. nuts retaining the coil section to
the frame.
10. Remove coil section from frame.
To re-install coil assembly:
1. Replace coil section into frames assembly.
2. Tighten the four
5
/16-in. nuts retaining coil section to
frame.
3. Reconnect electric heat wiring in electric heat control box.
4. Reconnect wiring to low limit thermostat.
5. Replace the four
1
/4-in. head screws holding the blower
deck to coil section (two on each side).
6. Replace coil baffle using
1
/4-in. head screws. See Item 2
in Fig. 27.
7. Re-install outside air actuator or locking quadrant handle
1
using
/4-in. head screws.
8. Reconnect piping to coils. If water coil, purge air from coils and perform hydrostatic test to check for leaks. If DX coil, perform leak test using nitrogen, and evacuate and charge per recommended HVAC procedures and all applicable codes.
9. Replace coil section side insulation.
10. Replace front (40UV) or bottom (40UH) panels. Replace end panels. Ensure that tag on each right front panel
(40UV) or middle bottom panel (40UH) matches unit tag.
11. Restore power to unit.
38
Page 39
1
2
BLOWER SECTION
DAMPER SECTION
COIL SECTION
FILTER DOOR RETAINER CLIPS (SEE NOTE 3)
DAMPER SECTION
COIL SECTION
MOTOR ELECTRICAL BOX
MOTOR
MOTOR & COUPLING SETSCREW ACCESS
DISCHARGE AIR TEMPERATURE SENSOR OPENING
RETURN AIR TEMPERATURE SENSOR OPENING
FRONT COIL BAFFLE
NOTES:
1. Unit shown in vertical orientation. Drawing applies to horizontal and vertical units.
2. Not all components shown for clarity.
3. 40UV,UH125-150, 40UH200 units only.
LEGEND
1—
1
/4-in. Head Screw
2—1/4-in. Head Screw
Fig. 27 — 40UV, UH Ventilator Coil Section
39
Page 40

Ball Bearing Replacement (40UV,UH150; 40UH200 Units Only)

Refer to Fig. 28 for 40UH200 units only, Fig. 29 for 40UV150 and 40UH150 units with PSC motors, Fig. 30 for 40UV150 and 40UH150 units with ECM motors.
WARNING
Lock out and tag all power supplies to equipment and con­trols prior to servicing unit. Follow all safety codes. Failure to do so could result in personal injury.
CAUTION
The assembly order of the bearing installation is critical. Be careful with all components during removal and installa­tion. Any excessive force applied to these components can cause unintended damage and void unit warranty.
To replace ball bearing:
1. Turn off all power to unit.
IMPORTANT: Tag each right front panel (40UV) or middle bottom panel (40UH) for each unit. Panels have electrical information specific to each unit.
2. Remove front (40UV) or bottom (40UH) panels and right (motor end) end panel.
3. Remove top panel and set optional vanes and screens to the side (40UV). Remove ductwork if required and remove top (40UV) or front (40UH) discharge plenum. For non-ducted 40UH horizontal units with front double deflection discharge grille, remove grille for access to wheel setscrews. See Fig. 25.
4. Remove secure coil baffle to blower section and remove front coil baffle. See Item 5 in Fig. 25.
5. Loosen setscrews on all blower wheels (two per wheel). See Fig. 26 and Fig. 28.
6. Loosen bearing setscrews.
7. Remove wiring harness connector(s) from motor.
8. If unit has ECM motor, remove motor shroud (sheet metal cover — Fig. 28, Item 6; Fig. 30, Item 4) by removing two
shroud.
9. Loosen Item 2; Fig. 30, Item 2), nut (Fig. 28, Item 3; Fig. 29, Item 5; Fig. 30, Item 6), and bolt (Fig. 28, Item 4; Fig. 29, Item 4; Fig. 30, Item 5), until motor housing (Fig. 28, Item 5; Fig. 29, Item 3; Fig. 30, Item 3) moves freely.
10. Slide shaft-coupling-motor assembly (Fig. 26, Items 3, 2, 1; Fig. 28, Items 5, 2, 10) out of wheels and unit until shaft clears inboard/center bearing assembly (30-in. max clearance required from edge of frame end).
1
/4-in. head screws along length of unit that
5
/16-in. hex nuts. Do not discard cooling
5
/16-in. motor mount (Fig. 28, Item 7; Fig. 29,
11. Remove
1
/2-in. bolts (Fig. 26, Item 4; Fig. 28, Item 9) and hex nuts (Fig. 26, Item 7; Fig. 28, Item 1) securing bearing to bearing bracket. Remove bearing (Fig. 26, Item 5; Fig. 28, Item 8).
12. Install new bearing (Fig. 26, Item 5; Fig. 28, Item 8). Secure with
1
/2-in. bolts (Fig. 26, Item 4; Fig. 28, Item 9)
and hex nuts (Fig. 26, Item 7; Fig. 28, Item 1).
13. Slide shaft-coupling-motor assembly (Fig. 26, Items 3, 2, 1; Fig. 28, Items 5, 2, 10) back into bearing and wheels.
Do not use excessive force. Damage to wheels may occur.
14. Insert shaft-coupling-motor assembly into wheels until motor clearance is as specified for motor type (PSC or ECM). See Fig. 31 or Fig. 24.
15. Ensure that motor shaft is perpendicular to motor blower endplate. Tighten
5
/16-in. motor mount (Fig. 28, Item 7; Fig. 29, Item 2; Fig. 30, Item 2), nut (Fig. 28, Item 3; Fig. 29, Item 5; Fig. 30, Item 6), and bolt (Fig. 28, Item 4; Fig. 29, Item 4; Fig. 30, Item 5), until motor (Fig. 28, Item 5; Fig. 29, Item 3; Fig. 30, Item 3) is secure.
16. Install motor shroud (sheet metal cover - Fig. 28, Item 6; Fig. 30, Item 4) using two
5
/16-in. hex nuts if using ECM
motor. Align “window” with receptacles on motor.
Motor control module could overheat and fail if oper­ated without cooling shroud.
17. Re-attach green ground wire that connects the motor to the frame with
1
/4-in. head screw if unit has a PSC motor.
The ECM motors are grounded through the harness.
18. Re-attach wiring harness connector(s) to motor.
19. Center each wheel in its respective housing and tighten wheel setscrews (two for each wheel).
20. Rotate the fan shaft by hand to ensure that fans are unrestricted and can rotate freely. Check for any fan obstructions.
21. Remove lockout and operate unit for approximately 60 seconds to let inboard/center bearing mount self-adjust.
22. Lock out and tag all power supplies to equipment and controls. Tighten the two bearing setscrews.
23. Re-install the coil baffle using the six
1
/4-in. head screws that attach the coil baffle to the coil section. See Item 4 in Fig. 25.
24. Re-install
1
/4-in. head screws along length of unit secur­ing coil baffle to the blower section. See Item 5 in Fig. 25.
25. Re-install optional vanes and screens and install top panel (40UV). Re-install top (40UV) or front (40UH) discharge plenum and ductwork if required or discharge grille.
26. Re-install front (40UV) or bottom (40UH) panels. Re­install end panels. Ensure that tag on each right front
panel (40UV) or middle bottom panel (40UH) matches unit tag.
27. Restore power to unit.
40
Page 41
(SEE NOTE 5)
(SEE NOTE 4)
UNIT
BOTTOM
LEFT SIDE
VIEW
(SEE NOTE 5)
2
3
4
5
6
7
8
9
10
11
12
13
14
1
NOTES:
1. Not all components shown for clarity.
2. This drawing applies to 2000 cfm units only.
3. Remove shaft, motor and coupling prior to removing bearing. Refer to Removal and Re-installation instructions.
4. Install sleeve bearing with oil cup facing up and towards the rear of the assembly.
5. Refer to Fig. 24 for motor-coupling and shaft-coupling tolerances.
LEGEND
1—Hex Nut 2—Coupling 3—Nut 4—Bolt 5—Motor Housing 6—Motor Shroud 7—
5
/16-in. Motor Mount
8—Bearing 9—
1
/2-in. Bolt
10 — Shaft 11 — Bolt 12 — End Bearing Bracket 13 — Hex Nut 14 — Holding Bearing
Fig. 28 — 40UH200 Ventilator Blower Drive Train Assembly
41
Page 42
2
3
4
5
6
1
11
12
10
9
SEE NOTE 2
8
7
(SEE NOTE 4)
(SEE NOTE 3)
UNIT FRONT (40UV)
UNIT BOTTOM (40UH)
LEFT SIDE VIEW
NOTES:
1. Not all components shown for clarity.
2. Items no. 7, 10 and associated hardware not required for 40UV,UH150. Refer to Fig. 26 for 40UV,UH150 in-board bearing replacement.
3. Install motor with capacitor facing up.
4. Install sleeve bearing with oil cup facing up and towards the rear of the assembly.
LEGEND
1—Shaft 2—
5
/16-in. Motor Mount
3—Motor Housing 4—Bolt 5—Nut 6—Coupling 7—End Bearing Bracket 8—Hex Nut
9—Hex Nut 10 — Holding Bearing 11 — Bolt 12 — Bearing Bracket Assembly
Fig. 29 — 40UV,UH Ventilator Blower Drive Train Assembly —
40UV050-150 and 40UH075-150 Units (PSC Motor)
42
Page 43
UNIT FRONT (40UV) UNIT BOTTOM (40UH)
(SEE NOTE 4)
5
4
3
2
6
7
1
12
13
11
10
9
8
LEFT SIDE
VIEW
SEE NOTE 2
NOTES:
1. Not all components shown for clarity.
2. Items no. 8, 11 and associated hardware not required for 40UV,UH150. Refer to Fig. 26 for 40UV,UH150 in-board bearing replacement.
3. Install motor with electrical connections facing front of assembly.
4. Install oil cup facing up and towards the rear of the assembly.
LEGEND
1—Shaft 2—
5
/16-in. Motor Mount
3—Motor Housing 4—Motor Shroud 5—Bolt 6—Nut 7—Coupling 8—End Bearing Bracket
9—Hex Nut 10 — Hex Nut 11 — Holding Bearing 12 — Bolt 13 — Bearing Bracket Assembly
Fig. 30 — 40UV,UH Ventilator Blower Drive Train Assembly —
40UV050-150 and 40UH075-150 Units (ECM Motor)
43
Page 44
0.500 0.063
.125 .032
FAN SHAFT
COUPLING
MOTOR SHAFT
FACE OF MOTOR FLUSH WITH FACE OF INSULATION
MOTOR (PSC)
BLOWER SECTION
FRONT VIEW
SHAFTED END FACE
COUPLING INSIDE FACE
COUPLING FACE
MOTOR BEARING FACE
+ –
+ –
NOTES:
1. All dimensions shown in inches.
2. Not all components shown for clarity.
Fig. 31 — 40UV,UH Ventilator Blower Section Assembly — PSC Motor Detail
44
Page 45

Sleeve Bearing Replacement (40UV050-125, 40UH075-125 and 40UH200 Units Only) (see Fig. 32)

Refer to Fig. 28 for 40UH200 units only, Fig. 29 for 40UV050­150 and 40UH075-125 units with PSC motors, Fig. 30 for 40UV050-125 and 40UH075-150 units with ECM motors.
WARNING
Lock out and tag all power supplies to equipment and con­trols prior to servicing unit. Follow all safety codes. Failure to do so could result in personal injury.
CAUTION
The assembly order of the bearing installation is critical. Be careful with all components during removal and installa­tion. Any excessive force applied to these components can cause unintended damage and void unit warranty.
To replace ball bearing:
1. Turn off all power to unit.
IMPORTANT: Tag each right front panel (40UV) or middle bottom panel (40UH) for each unit. Panels have electrical information specific to each unit.
2. Use
3. Remove
4. Remove left blower section end (Item 2 in Fig. 32) insu-
5. Use
6. Remove bearing bracket assembly (Fig. 28, Items 12, 14,
5
/32-in. hex (Allen) tool or 3/8-in. nut driver to remove front (40UV) or bottom (40UH) panels and right (motor end) end panel.
1
/4-in. head screws (Item 5 in Fig. 25) along length of unit that secure coil baffle to blower section and remove front coil baffle.
lation (Item 1 in Fig. 32).
7
/16-in. socket to remove hex nuts (Fig. 28, Item 13; Fig. 29, Item 8; Fig. 30, Item 9) securing end-bearing bracket (Fig. 28, Item 12; Fig. 29, Item 7; Fig. 30, Item
8) to blower section end.
13, 11; Fig. 29, Items 7, 10, 9, 11; Fig. 30, Items 8, 11,
10, 12) from blower section end. Use care to slide assem­bly off of shaft end. Hold shaft from inside blower sec-
tion to prevent wheel damage.
7. Use
1
/2-in. socket and 1/2-in. combination wrench to remove hex nuts (Fig. 28, Item 13; Fig. 29, Item 9; Fig. 30, Item 10) and bolts (Fig. 28, Item 11; Fig. 29, Item 11; Fig. 30, Item 12) holding bearing (Fig. 28, Item 14; Fig. 29, Item 10; Fig. 30, Item 11) and bearing bracket (Fig. 28, Item 12; Fig. 29, Item 7; Fig. 30, Item
8) together.
CAUTION
Ensure sleeve bearing is installed with oil cup facing up­wards as shown in left side view.
8. Replace bearing (Fig. 28, Item 14; Fig. 29, Item 10; Fig. 30, Item 11). Attach to bearing bracket using hex nuts and bolts. Align oil cup port with matching cutout in bearing bracket.
9. Use
10. Add 5 to 10 drops of SAE 20 or 30 non-detergent based
11. Rotate the fan shaft by hand to ensure that fans are
12. Re-install left blower section end insulation (Item 1 in
13. Re-install
14. Re-install front (40UV) or bottom (40UH) panels. Re-
15. Restore power to unit.
7
/16-in. socket to slide replacement bearing (Fig. 28, Item 14; Fig. 29, Item 10; Fig. 30, Item 11) on to the end of shaft and install bearing bracket assembly (Fig. 28, Items 12, 14, 13, 11; Fig. 29, Items 7, 10, 9, 11; Fig. 30, Items 8, 11, 10, 12) in blower section end. Attach using hex nuts.
oil to bearing.
unrestricted and can rotate freely. Check for any fan obstructions.
Fig. 32).
1
/4-in. head screws (Item 5 in Fig. 25) along
length of unit securing coil baffle to the blower section.
install end panels. Ensure that tag on each right front
panel (40UV) or middle bottom panel (40UH) matches unit tag.
45
Page 46
AUTOMATIC RESET
CAUTION
DO NOT CHANGE LIMIT SWITCH CAPILLARY TUBE LOCA­TION! LIMIT SWITCHES MAY NOT FUNCTION PROPERLY.
LEGEND
1—Insulation 2—Left Blower Section End 3—Blower Deck 4—Blower Inlet Ring 5—
1
/4-in. Head Screw
6—
1
/4-in. Head Screw
7—Blower Housing 8—Blower Wheel
NOTES:
1. Not all components shown for clarity.
2. Supplied on electric heat units only.
3. Secure capillary tubes to blower housing using high temperature cable tie. Capillary tube lengths will vary depending on unit size.
1
HIGH TEMPERATURE LIMIT SWITCH (SEE NOTES 2,3) (SEE CAUTION)
2
3
8
4
MANUAL RESET HIGH TEMPERATURE LIMIT SWITCH (SEE NOTES 2,3) (SEE CAUTION)
5
7
6
DISCHARGE AIR TEMPERATURE SENSOR (OPTIONAL) OPENING
Fig. 32 — 40UV,UH Ventilator Blower Section Assembly Sheet Metal (All Units)
RETURN AIR TEMPERATURE SENSOR (OPTIONAL) OPENING
46
MOTOR AND COUPLING SETSCREW ACCESS
Page 47

Blower Wheel Removal and Re-installation (see Fig. 32)

Refer to Fig. 28 for 40UH200 units only, Fig. 29 for 40UV050­150 and 40UH075-125 units with PSC motors, Fig. 30 for 40UV050-125 and 40UH075-150 units with ECM motors.
WARNING
Lock out and tag all power supplies to equipment and con­trols prior to servicing unit. Follow all safety codes. Failure to do so could result in personal injury.
CAUTION
The assembly order of the bearing installation is critical. Be careful with all components during removal and installa­tion. Any excessive force applied to these components can cause unintended damage and void unit warranty.
To remove blower wheel:
1. Turn off all power to the unit.
2. Remove blower section per service instructions in Blower Assembly Section Removal and Re-installation.
IMPORTANT: Tag each right front panel (40UV) or middle bottom panel (40UH) for each unit. Panels have electrical information specific to each unit.
3. Use
4. Loosen inboard/center bearing setscrews (only on
5. If unit has ECM motor, remove motor shroud (sheet
6. Loosen
7. Slide shaft-coupling-motor assembly (Fig. 26, Items 3, 2,
8. Remove four
9. Remove five
10. Remove blower wheel(s) (Fig. 32, Item 8).
To re-install blower wheel:
1. Install new blower wheel(s) (Fig. 32, Item 8). Ensure that
2. Install inlet ring (Fig. 32, Item 4) and install five ¼-in.
3. Install four
5
/32-in. hex tool to loosen setscrews on all blower
wheels (two per wheel).
40UV,UH150 and 200 size units).
metal cover — Fig. 28, Item 6; Fig. 30, Item 4) by removing two
5
/16-in. hex nuts. Do not discard cooling
shroud.
5
/16-in. motor mount (Fig. 28, Item 7; Fig. 29, Item 2; Fig. 30, Item 2), nut (Fig. 28, Item 3; Fig. 29, Item 5; Fig. 30, Item 6), and bolt (Fig. 28, Item 4; Fig. 29, Item 4; Fig. 30, Item 5), until motor housing (Fig. 28, Item 5; Fig. 29, Item 3; Fig. 30, Item 3) moves freely.
1; Fig. 28, Items 5, 2, 10) out of wheels and unit until shaft clears inboard/center bearing assembly (30-in. maximum clearance required from edge of frame end).
1
/4-in. head screws (Fig. 32, Item 6) securing blower housing(s) (Fig. 32, Item 7) to blower deck (Fig. 32, Item 3) and remove blower and wheel assembly.
1
/4-in. head screws (Fig. 32, Item 5) secur­ing blower inlet ring (Fig. 32, Item 4) to blower housing and remove inlet ring.
the fan blades are installed in the correct orientation (cup of blade towards discharge).
head screws (Fig. 32, Item 5) securing blower inlet ring to blower housing (Fig. 32, Item 7).
1
/4-in. head screws (Fig. 32, Item 6) securing blower housing(s) (Fig. 32, Item 7) to blower deck (Fig. 32, Item 3).
4. Slide shaft-coupling-motor assembly (Fig. 26, Items 3, 2, 1; Fig. 28, Items 5, 2, 10) back into bearing and wheels.
Do not use excessive force. Damage to wheels may occur.
5. Insert shaft-coupling-motor assembly into wheels until motor clearance is as specified for motor type (PSC or ECM). See Fig. 31 or Fig. 24.
6. Ensure that motor shaft is perpendicular to motor blower endplate. Tighten
5
/16-in. motor mount (Fig. 28, Item 7; Fig. 29, Item 2; Fig. 30, Item 2), nut (Fig. 28, Item 3; Fig. 29, Item 5; Fig. 30, Item 6), and bolt (Fig. 28, Item 4; Fig. 29, Item 4; Fig. 30, Item 5), until motor (Fig. 28, Item 5; Fig. 29, Item 3; Fig. 30, Item 3) is secure.
7. Install motor shroud (sheet metal cover — Fig. 28, Item 6; Fig. 30, Item 4) using two
5
/16-in. hex nuts if using
ECM motor. Align “window” with receptacles on motor.
Motor control module could overheat and fail if oper­ated without cooling shroud.
8. Re-install blower section into frame assembly. See Fig. 25.
9. Tighten the four
5
/16-in. nuts retaining blower section to
frame.
10. Tighten the two
5
/16-in. (Fig. 26, Item 6) nuts retaining the inboard bearing bracket to the pipe chase (only on 40UV,UH150 and 200 size units).
11. Re-install two carriage bolts (Fig. 25, Item 6) that attach the front brace to the frame sides.
12. Re-attach green ground wire that connects the motor to the frame with
1
/4-in. head screw if unit has a PSC motor.
The ECM motors are grounded through the harness.
13. Re-attach wiring harness connector(s) to motor.
14. Center each wheel in its respective housing and tighten wheel setscrews (two for each wheel).
15. Re-install one
1
/4-in. head screw (Fig. 25, Item 1) at cen-
ter of blower deck attaching blower deck to pipe chase.
16. Re-install the four
1
/4-in. head screws (Fig. 25, Item 2)
holding the blower section sides to the coil section sides.
17. Rotate the fan shaft by hand to ensure that fans are unrestricted and can rotate freely. Check for any fan obstructions.
18. Remove lockout and operate unit for approximately 60 seconds to let inboard/center bearing mount self­adjust (only on 40UV,UH150 and 200 size units).
19. Lock out and tag all power supplies to equipment and controls. Tighten the two bearing setscrews (only on 40UV,UH150 and 200 size units). See Fig. 26, 28 or 32.
20. Re-install the coil baffle using the six
1
/4-in. head screws that attach the coil baffle to the coil section. See Item 4 in Fig. 25.
21. Re-install
1
/4-in. head screws along length of unit secur­ing coil baffle to the blower section. See Item 5 in Fig. 25.
22. Re-install optional vanes and screens and install top panel (40UV). re-install top (40UV) or front (40UH) dis­charge plenum and ductwork if required or discharge grille.
23. Re-install front (40UV) or bottom (40UH) panels. re­install end panels. Ensure that tag on each right front
panel (40UV) or middle bottom panel (40UH) matches unit tag.
24. Restore power to unit.
47
Page 48

Damper Section Removal and Re-installation (see Fig. 33)

WARNING
Lock out and tag all power supplies to equipment and con­trols prior to servicing unit. Follow all safety codes. Failure to do so could result in personal injury.
CAUTION
The assembly order of the bearing installation is critical. Be careful with all components during removal and installa­tion. Any excessive force applied to these components can cause unintended damage and void unit warranty.
To remove damper section:
1. Turn off all power to unit.
IMPORTANT: Tag each right front panel (40UV) or middle bottom panel (40UH) for each unit. Panels have electrical information specific to each unit.
2. Use
3. Remove four carriage bolts and nuts securing kickplate
5
/32-in. hex (Allen) tool or 3/8-in. nut driver to remove front (40UV) or bottom (40UH) panels and right end panels.
to end frames.
IMPORTANT: Tag kickplate for each unit. Kickplate has electrical information specific to each unit.
4. Remove the two
1
/4-in. head screws securing kickplate to the damper sides (one on each side) and remove kickplate.
5. Remove
1
/4-in. head screws attaching outside air (OA) actuator to damper shaft or attaching locking quadrant assembly to damper shaft. Remove OA actuator or lock­ing quadrant assembly.
6. Remove six
1
/4-in. head screws (3 per side) securing
damper to 40UH unit rear panel.
7. Remove two
5
/16-in. nuts attaching damper assembly to
back frame.
8. Remove damper assembly from unit.
To replace damper section:
1. Replace damper assembly into unit.
2. Replace
5
/16-in. nuts attaching damper assembly to back
frame.
3. Replace six
1
/4-in. head screws (3 per side) securing
damper to 40UH unit rear panel.
4. Replace
1
/4-in. head screws attaching OA actuator to damper shaft OR attaching locking quadrant assembly to damper shaft. Replace OA actuator or locking quadrant assembly.
5. Replace the two
1
/4-in. head screws securing kickplate to the damper sides (one on each side) and remove kickplate.
6. Replace four carriage bolts and nuts securing kickplate to end frames.
7. Re-install front (40UV) or bottom (40UH) panels. re­install end panels. Ensure that tag on each right front
panel (40UV) or middle bottom panel (40UH) matches unit tag.
8. Restore power to the unit.
48
Page 49
RETURN AIR TEMPERATURE SENSOR OPENING
FRONT COIL BAFFLE
DISCHARGE AIR TEMPERATURE SENSOR OPENING
MOTOR & COUPLING SETSCREW ACCESS
MOTOR
MOTOR ELECTRICAL BOX
COIL SECTION
DAMPER SECTION
BLOWER SECTION
DAMPER SECTION
KICKPLATE
NOTES:
1. Unit shown in vertical orientation. Drawing applies to horizontal and vertical units.
2. Not all components shown for clarity.
Fig. 33 — 40UV,UH Ventilator Damper Section Removal/Installation
49
Page 50
© Carrier Corporation 2018
Catalog No. 04-53400048-01 Printed in U.S.A. Form 40UV-UH-11SI Pg 50 8-18 Replaces: 40UV-UH-10SI
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Page 51

UNIT START-UP CHECKLIST

NOTE: To avoid injury to personnel and damage to equipment or prop­erty when completing the procedures listed in this start-up checklist, use good judgment, follow safe practices, and adhere to the safety considerations/information as outlined in preceding sections of this Installation, Start-Up, and Service document.
MODEL NO.: _________________________________ SERIAL NO.: _____________________________________
SOFTWARE VERSION _________________________ TECHNICIAN: ____________________________________
DATE: _______________________________________
INITIAL CHECKLIST:
DOES ELECTRICAL SERVICE CORRESPOND TO UNIT NAMEPLATE?
ARE ALL ELECTRICAL CONNECTIONS TIGHT?
DOES ALL FIELD WIRING CONFORM TO UNIT WIRING DIAGRAM?
IS UNIT INSTALLED PER IOM (LEVEL, CABINET PAINT CONDITION ACCEPTABLE, ETC.)?
IS THE CONDENSATE DISPOSAL SYSTEM OPERATING CORRECTLY?
PROPER SLOPE OF FIELD REVERSIBLE DRAIN PAN?
ARE END BEARING BOLTS ON FAN SHAFT TIGHT?
ARE DAMPERS OPERATING PROPERLY?
IS THE FILTER CLEAN?
IS EXPANSION VALVE BULB PROPERLY INSTALLED AND INSULATED?
PIPING CHECKLIST:
IS EXPANSION VALVE BULB PROPERLY INSTALLED AND INSULATED?
IS UNIT PIPING CORRECT AND INSULATED TO PREVENT CONDENSATION?
ARE THE CONTROL VALVE PACKAGES PIPED CORRECTLY?
ARE VALVE PACKAGES PROPERLY INSULATED?
ARE THERE ANY LEAKS DETECTED?
CONTROLS CHECKLIST:
DOES THE UNIT HAVE CARRIER CONTROLS (CCN OR OPN)? IF SO, CONTINUE.
CHECK THAT THE UNIT OPERATES PER SEQUENCE OFOPERATION AS STATED IN THE CONTROLLER IOM.
RECORD THE THERMOSTAT READINGS IN TABLE BELOW.
Please Fill Out the Following: Reading
Controller Points
Space Temperature
Discharge Air Temperature
Outdoor Air Temperature
Outdoor Air Damper Position
Set Points
Space Setpoint
Unoccupied Offset
Minimum Position
Deadband
Position (Open / Closed / %)
Outdoor Air Damper
Face/Bypass Damper
Catalog No. 04-53400048-01 Printed in U.S.A. Form 40UV-UH-11SI Pg CL-1 8-18 Replaces: 40UV-UH-10SI
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Page 52
© Carrier Corporation 2018
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53400048-01 Printed in U.S.A. Form 40UV-UH-11SI Pg CL-2 8-18 Replaces: 40UV-UH-10SI
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
Loading...