40SMC---N
INST ALLA TION MANUAL
40SMC---N Ducted above-ceiling units (Cooling only and heat pump)
IR Remote Control “Room Controller” “Zone Manager”
The unit can be used with infrared Remote Control, with the Carrier “Room Controller” or “Zone Manager”. For the installation instructions of the wired remote controls and the remote control refer to the corresponding manuals.
For the instructions for use of the air conditioner and outdoor installation instructions refer to the corresponding manuals.
Contents
Page
Dimensions ................................................................................................. 2
T echnical data............................................................................................. 3
General information .................................................................................... 3/4
Warnings: avoid.......................................................................................... 4/5
Installation................................................................................................... 6
Refrigerant connections.............................................................................. 7
Electric connection ..................................................................................... 8/12
Alarm code .................................................................................................. 12
Accessories................................................................................................. 12
Guide for the owner..................................................................................... 12
Fan diagrams.............................................................................................. 13/14
ENGLISH
Cooling only and Power
heat pump supply
models
40SMC009N 40SMC012N 40SMC018N 40SMC024N 230V~50Hz 40SMC028N 40SMC036N 40SMC048N 40SMC060N
GB - 1
40SMC---N
Dimensions
햸 햲 햴
P
N
M
Ø AP
L
K
Ø AM
AC
Ø AN
AD AC
45
AF
AE
CoilFanDrain panDrain connection Ø APOutside air intakeElectrical boxUnit supportAir filterLiquid Ø AMGas Ø AN
E D
1919
29
AB
GH
260
Z
9
B
J
F
AL
180
Y
AKAJ
I
2828
C
180
87
YZ
VU
Q
W R
VU
Q
A
40SMC---N A B C D E F G H I J K L M N P Q R S
009 - 012 - 018 725 555 220 743 781 262 222 71 23 607 31.5 59 140 200 35 33 659 45 024 - 028 - 036 925 660 285 943 981 241.5 321 97.5 23 712 33.5 118.5 199.5 264.5 35 37.5 850 87.5
048 - 060 1250 750 310 1268 1306 261 321 168 22 801 43 143 224 289 43 110 1030 103
32
X
TS
40SMC---N Ø AM Ø AN Ø AP
009 1/4 3/8 20
012 - 018 1/4 1/2 20
024 1/4 1/2 25
028 1/4 5/8 25
036 - 048 - 060 3/8 3/4 25
AG AH
Ø AM
Ø AN
Ø AP
40SMC---N T U V W X Y Z AB AC AD AE AF AG AH AJ AK AL
009 - 012 - 018 143 62 211 179 103 13 27 3,5 89 545 33 142 31 90 128 54 38 024 - 028 - 036 165.5 90 276 193 125 23 82 31 99 725 33 207 31 110 160 50 75
048 - 060 175 203 290 264 116 23 107 31 109 1030 32 233 32 140 185 50 75
When designin an installation ensure the use of up-to-date drawings available from your local Carrier office.
GB - 2
40SMC---N
T echnical data
Table I: Nominal data
MAXIMUM POWER INPUT (WATT)
Cooling only and heat pump
Unit Cooling Heating
40SMC009N 120 120 40SMC012N 130 130 40SMC018N 180 180 40SMC024N 290 290 40SMC028N 320 320 40SMC036N 420 420 40SMC048N 576 576 40SMC060N 620 620
T able II: Operating limits
Cooling / Heating Refer to outdoor unit installation manual. Main power supply
Nominal single-phase voltage 230V ~ 50Hz Operating voltage limits min. 198V – max. 264V
(1)
Note: For power supply wire size and delay type fuses, refer to the outdoor unit installation instructions.
(1)
Power inputs have been measured with free outlet, at maximum speed and with voltage 264V~50Hz.
ENGLISH
Table III: External static pressure
40SMC---N 009 012 018 024 028 036 048 060
Nominal static pressure (Pa)
Maximum static pressure (Pa)
33 40 45 60 50 50 70 80
60 70 160
General information
Unit installation
Read this instruction manual thoroughly before starting installation.
This unit complies with the low-voltage (EEC/73/23) and
electromagnetic compatibility (EEC/ 89/336) directives.
Follow all current national safety code requirements.
In particular ensure that a properly sized and connected ground wire is in place.
Make sure the electric system voltage and frequency comply with
the required values and the power input available is suitable for running the unit. Also ensure that national safety code requirements have been followed for the main supply circuit.
Connection of the system to the mains power supply is to be
carried out in compliance with the wiring diagram shown in the installation instructions of the external section.
Connect the indoor and outdoor units by means of copper pipes
equipped with flanged connections (not included in the supply).
Use insulated seamless refrigeration grade pipe only, (Cu DHP type according to ISO1337), degreased and deoxidized, suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa. Under no circumstances must sanitary type copper pipe be used.
After installation thoroughly test system operation and explain all system functions to the owner.
Use this unit only for factory approved applications: the unit cannot be used in laundry or steam pressing premises.
WARNING: Disconnect the mains power supply switch before servicing the system or handling any internal parts of the unit.
This installation manual describes the installation procedures of the indoor unit of a residential split system consisting of two Carrier manufactured units. Do not connect this unit to any other manufacturer's outdoor unit. The manufacturer declines any liability for system malfunction resulting from unauthorised system combinations.
GB - 3
40SMC---N
General information
The manufacturer declines any liability for damage resulting from modifications or errors in the electrical or refrigerant connections. Failure to observe the installation instructions, or use of the unit under conditions other than those indicated in table Operating limits of the outdoor unit installation manual, will immediately invalidate the unit warranty.
Failure to observe electric safety codes may cause a fire hazard in the event of short circuits.
Inspect equipment for damage during transport. In case of damage file an immediate claim with the shipping company. Do not install or use damaged units.
In case of malfunction turn the unit off, disconnect the mains power supply and contact a qualified service engineer.
Maintenance of the refrigerant circuit must only be carried out by qualified personnel.
All of the manufacturing and packaging materials used for this appliance are recyclable.
Dispose of the packaging material in accordance with local requiremements.
This equipment contains refrigerant that must be disposed of correctly. At the end of the units life, the refrigerant must be taken to special collection points or delivered to the retailer for correct disposal.
Positions to avoid:
Exposure to direct sunlight.
Areas close to heat sources.
On damp walls or in positions that may be exposed to water
hazard.
Where curtains or furniture may obstruct free air circulation.
Recommendations:
Choose an area free from obstructions which may cause uneven air distribution and/or return.
Consider using an area where installation is easy.
Choose a position that allows for the clearances required.
Look for a position in the room which ensures the best
possible air distribution.
Install unit in a position where condensate can easily be piped to an appropriate drain.
250 mm
Choosing the installation site
The SMC---N unit has been conceived for above-ceiling installation.
The unit must be installed in a not easily accessible place.
Do not install the unit below 2.5 mm.
To install the unit at 2.2-2.5 m from the floor, use a
discharge pipe with a minimum length of 250 mm.
W arnings: avoid...
220
200
400
... any obstruction of the unit air intake or supply grilles. ... exposure to direct sunshine, when the unit is operating in the
cooling mode; always use shutters or shades. ... positions too close to heating sources which may damage the unit.
GB - 4
40SMC---N
Warnings: avoid...
... exposure to oil vapours.
ENGLISH
... connecting condensate piping to sewage system drain without appropriate trap. Trap height must be calculated according to the unit discharge head in order to allow sufficient and continuous water evacuation.
... installation in areas with high frequency waves. ... only partial insulation of the piping.
... inclined installation which could cause dripping. ... flattening or kinking the refrigerant pipes or condensate pipes.
5
... horizontal sections or curves of condensate drain piping with less than 5% slope.
... excessive height difference between outdoor and indoor units (see installation manual of outdoor unit).
... slack on electrical connections. ... disconnecting refrigerant connections after installation: this will cause refrigerant leaks.
... unnecessary turns and bends in connection pipes (see installation manual of outdoor unit). Excessive connection pipe length (see installation manual of outdoor unit).
GB - 5
40SMC---N
Installation
Service area
250 mm
220
400
200
Unit installation
Insert 4 M8 threaded rods into the celling. Introduce the other end of the rods through the slots of unit suspension brackets. Position the shock absorbers, add washers and screw the nuts down until the unit is correctly suported. If there is sufficient space, a rubber or neoprene sheet can be placed between the ceiling and the unit.
IMPORTANT: The unit must be perfectly levelled.
UnitFalse ceilingCeilingRegister cover
Once these operations have been completed, an above-ceiling installation will be necessary to conceal the unit; do not forget to install a removable panel to allow for maintenance operations. Grills of an adequate size should be incorporated in the unit for return air suction.
Minimum 5% slope
Screws-in rodShoch absorbersWasherNut
Condensate drainage
All units are provided with an internal condensate drain pan which incorporates a drainage tube 20 mm external Ø (009, 012, 018) and 25 mm (024, 028, 036, 048, 060). A tube for evacuating condensates must therefore be provided.
The recommendations below must be followed in all cases:
Use galvanizad steel, copper or plastic piping. Do not used ordinary garden hose.
Use a material that guarantees perfect watertightness on the
drainage pipe.
If rigid material has been used for the drainage, it is necessary to
provide some kind of elastic coupling in the drainage line to absorb possible vibrations.
The drainage line should always be below the connextion itself,
and should also slope to facilitate drainage.
WARNING: No drillholes should be made in the base of the unit, since the drain pans may be perforated.
Ductwork
The ductwork dimensions should be determined in accordance with the air flow circulating through it and with the available static pressure of the unit. These information are available in the final pages of the manual.
Various suggestions are made herebelow, regarding the layout and design of the said doctwork:
Whatever type of duct is used, it should not be made of materials
which are flammable, or which give off toxic gases in the event of a fire. The internal surfaces should be smooth, and not conteminate the air which passes through.
At the points where the duct joins with the unit, it is advisable to
use a flexible connection which absorbs vibration and prevents the transmission of noise inside the ductwork.
Bends should be avoided as much as possible near the unit
outlet. If unavoidable, they should be as slight as possible, and internal deflectors should be used when the duct is of large dimensiones.
IMPORTANT: Duct calculation and design must be effected by a qualified technician.
GB - 6
40SMC---N
Refrigerant connections
Refer to the outdoor unit installation manual for tube sizing, and limitations (slope, length, number of bends allowed, refrigerant charge, etc.).
Tubing diameter
Model
40SMC 009N 9,52 (3/8") 6,35 (1/4") 40SMC 012N-018N-024N 40SMC 028N 15,87 (5/8") 6,35 (1/4")
40SMC 036N-048N-060N
For refrigerant tubes use seamless, insulated refrigeration grade tube, (Cu DHP type according to ISO1337), degreased and deoxidized, suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa. Under no circumstances must sanitary type copper pipe be used.
Flaring the end of the tubing
Gas Liquid
(Suction) (Discharge)
mm (inches) mm (inches)
12,70 (1/2") 6,35 (1/4")
19,05 (3/4") 9,52 (3/8")
ENGLISH
Lubricate the tube end and thread of the flare fitting with anti­freeze oil. Finger-tighten the fitting several turns, then tighten it fully with two wrenches by applying the tightening torque indicated in the table.
Connection to the unit
Insufficient tightening torque will cause gas leaks. Overtightening the fittings will damage the tube flaring and cause gas leaks.
Remove protective caps from the copper tube ends. Position tube end downward, cut the tube to the required length and remove the burrs with a reamer.
Remove flare nuts from the unit connections and place them on the tube end. Flare the tube with the flaring tool.
Adjustable wrench or torque wrench Outdoor end Indoor end
Tubing diameter Torque
mm (inches) Nm
6,35 (1/4") 18
9,52 (3/8") 42 12,70 (1/2") 55 15,87 (5/8") 65 19,05 (3/4") 100
L
Flare end must not have any burrs or imperfections. The length of the flared walls must be uniform.
L
TubeTube insulationFastening tape
Once all connections have been completed, check for leaks by using a leak detector specific for HFC refrigerants. Finally wrap connections with anti-condensate insulation and tighten with tape, without exerting great pressure on the insulation. Repair and cover any possible cracks in the insulation. Connection pipes and electric cables between indoor and outdoor units must be fixed to the wall with appropriate conduits.
GB - 7
40SMC---N
1
10
80
10
100
3
10
100
10
80
Refrigerant connections
VERY IMPORTANT: To prevent electrical shock or equipment damage, make sure the power supply sectioners are open before electrical connections are made. If this action is not taken, personal injury may occur.
First make the refrigerant connections and then the electrical ones. In the case of disassembly, operations must be carried out in the opposite sequence.
WARNING: Operation of unit on improper line voltage constitutes
abuse and is not covered by Carrier warranty. IMPORTANT:
The mains supply indoor unit – outdoor unit connecting cable must be H07 RN-F (60245IEC66) type synthetic rubber
insulation with neoprene coating.
Consult the wiring diagram sent with the outdoor unit.
To effect the unit power supply (wire inlet, conductor
section, protections, etc..), consult the Electrical Data Table, the wiring diagram sent with the unit and the
Cooling only
40SMC 009N, 012N
Power supply from indoor unit
standards in force affecting the installation of air conditioning equipment.
To connect a condensate drainage pump follow the wiring diagram instructions in the next pages.
VERY IMPORTANT: The installer should place protection elements in the line
according to the legislation in force. IMPORTANT:
Make ground connection prior to any other electrical
connections.
Make electrical connections between units prior to proceeding
to mains supply unit connection.
According to the installation instructions, the disconnecting
switches from the mains power supply should have a contact gap (4 mm) such that total disconnection can be ensured under the conditions provided for by overvoltage class III.
NOTE:
All field electrical connection are the responsibility of the
installer.
1
W2V1V2V3V4
1
3
IMPORTANT: Cable 햲 must always be placed above cable 햴.
NOTE: See the outdoor unit installation manual.
40 41
C G P
2 3N N Y O
1L
2
C G P
Power supply cable (H07 RN-F)Interconnection cable (H07 RN-F)
GB - 8
Model GND L N GND N Y O W2 V1 V2 V3 V4 40 41 1 2 3 40SMC009N 3G1,5 3G1,5 40SMC012N 3G2,5 3G2,5 H03VV-F
Indoor and outdoor units
interconnections (mm2)
Disconnected
CRC
3 x 0,75
40SMC---N
Refrigerant connections
Power supply from outdoor unit
NOTE: See the outdoor unit installation manual.
Interconnection cable (H07 RN-F)
10
10
100
80
3
Cooling only
40SMC 009N, 012N
3
1
W2V1V2V3V4
40 41
ENGLISH
C G P
2 3N N Y O
1L
2
C G P
Model GND L N - Y O W2 V1 V2 V3 V4 40 41 1 2 3 40SMC009N 4G1,5 40SMC012N 4G2,5
40SMC009N, 40SMC012N
combined with Multisplit
Power supply from indoor unit
IMPORTANT: Cable 햲 must always be placed above cable 햴.
Power supply cable (H07 RN-F)Interconnection cable (H07 RN-F)Interconnection cable (H07 RN-F)
10
10
100
80
1
10
80
Indoor and outdoor units
interconnections (mm2)
4G1
Heat pump
40SMC 009N, 012N
1
2
Disconnected
Disconnected
1
W2V1V2V3V4
40 41
C G P
2 3N N Y O
1L
CRC
3 x 0,75
H03VV-F
10
100
10
80
Model GND L N GND N Y O W2 V1 V2 V3 V4 40 41 1 2 3 40SMC009N 3G1,5 3G1,5 2 x 1,5 Disconnected 3 x 0,75 40SMC012N 3G2,5 3G2,5 2 x 1,5 Disconnected H03VV-F
3
3
Indoor and outdoor units
interconnections (mm2)
2
C G P
CRC
2
GB - 9
40SMC---N
Refrigerant connections
Heat pump combined with Multisplit
40SMC 009N, 012N, 018N, 024N
Power supply from outdoor unit
C G P
1
W2V1V2V3V4
Interconnection cable (H07 RN-F)Interconnection cable (H07 RN-F)
1
10
80
10
80
Model GND L N Y O W2 V1 V2 V3 V4 40 41 1 2 3
40SMC 009,012,018,024N combined with Multisplit 3G1 3 x 1 Disconnected 3 x 0,75
2
1
2
Indoor and outdoor units
interconnections (mm2)
40 41
2 3N N Y O
1L
C
2
G P
CRC
H03VV-F
Cooling only
40SMC 018N, 024N, 028N, 036N, 048N, 060N
C G P
1
NOTE: See the outdoor unit installation manual.
Interconnection cable (H07 RN-F)
10
100
10
80
Model GND R C Y O W2 S V1 V2 V3 V4 40 41 1 2 3 40SMC018, 024, 028N 40SMC036, 048, 060N H03VV-F
3
Indoor and outdoor units
interconnections (mm2)
4G1 Disconnected
W2
3
V1V2V3V440 41
1R S
2 3C C Y O
C G P
CRC
3 x 0,75
2
GB - 10
40SMC---N
Refrigerant connections
ENGLISH
Heat pump
40SMC 018N, 024N, 028N, 036N, 048N, 060N
NOTE:
1
See the outdoor unit installation manual.
W2
V1V2V3V440 41
Interconnection cable (H07 RN-F)Interconnection cable (H07 RN-F)
10
10
10
80
100
80
3
2
2
3
Indoor and outdoor units
interconnections (mm2)
Model GND R C Y O W2 S V1 V2 V3 V4 40 41 1 2 3 40SMC018N, 024N, 028N 40SMC036N, 048N, 060N H03VV-F
Legend 1 Indoor unit
Earth
L Live power supply N Neutral power supply R Power supply connection to outdoor unit C Neutral, connection to outdoor unit
3G1 4 x 1 Disconnected
Y Compressor interlocking
contac
O Reversing valve control
(Heat pump only)
W2 Outdoor fan signal S Thermostat end of defrosting
signal
V1, V2, V3, V4 Indoor fan speed
40, 41 Electric heater control 1, 2, 3 Room Controller control
2 Room Controller (CRC)
P Power supply G Earth C Signal
C G P
2 3C C Y O
1R S
C
2
G P
CRC
3 x 0,75
Electric connections for auxiliary pump installation - 40SMC009N-40SMC012N
1
J5
1
J6A
1
J6B
1
J18
J11
1
1
PUMP SENSOR
230Vac - 3,15 A min
N/C
COM
N/O
PS
L
N
1
J10
1
J15
J8
1
J17
J20
1
J13
J2
T1
J7
1
1
K1
J3
J4
1
LNN
Y
O
W2
To make electric connections you need to modify the cables connecting the N or C pole of the terminal block to the J3 pole of the card and
230V-1N-50Hz
insert the pump contact according to the instructions shown in the diagram above.
GB - 11
40SMC---N
Electric connection
Electric connections for auxiliary pump installation
40SMC018N-40SMC024N- 40SMC028N- 40SMC036N- 40SMC048N- 40SMC060N
1
J5
1
J6A
1
J6B
1
J18
J11
1
1
PUMP SENSOR
/
/
1
J10
1
J17
J15
J8
1
J20
1
J13
J7
1
1
J1
J2
J4
1
J3
To make electric connections you need to modify the cables connecting the N or C pole of the terminal block to the J3 pole of the card and insert the pump contact according to the instructions shown in the diagram above.
Alarm code, accessories and guide for the owner
Alarm code
A diagnostic system is contained in the electronic card to “check” the system integrity. When the diagnostic system is under alarm, the red LED installed onto the main card flashes as indicated below:
• 0,5 sec ON and 0,5 sec OFF with a 5 second pause before the error code is repeated.
• The number of flashes depends on the error that has been detected.
Not all of the errors can be reset (see table below).
Error code
Error
3 Air temperature sensor YES 4 Internal battery temp. sensor YES 5 External battery temp. sensor YES
7 Outdoor unit error YES 10 EEPROM faulty YES 11 Card serial number faulty YES 12 Address/zone number incomplete YES
Resettable
*
Accessories
For accessories refer to the product catalogues and documents.
Guide for the owner
When installation and tests are completed explain the Operation and Maintenance Manual to the owner, with particular attention to the main operating modes of the air conditioner, such as:
• Turning the unit on and off.
• Functions of the remote control.
* NO: Turn off power supply to the system, check and repair, if necessary.
Turn on power. YES: Check
GB - 12
Leave the two installation manuals for the indoor and outdoor units with the owner for future use during maintenance operations or for any other needs.
40SMC---N
Fan diagrams
100
90
80
70
60
Pa
50
40
30
4
20
40SMC009N
1
2
3
Pa
100
90
80
70
60
50
40
30
20
ENGLISH
40SMC012N
1
2
3
4
10
0
70 90 110 130 150 170180 190
40SMC018N
100
90
80
70
60
Pa
50
1
2
40
30
3
4
Pa
10
100
90
80
70
60
50
40
30
0
140 160 180 200 220120100
40SMC024N
1
2
3
4
20
10
0
120 150 200 240
1- Super high speed
(optional) 2- High speed 3- Medium speed 4- Low speed
Air flow (l/s)
20
10
0
170 200 250 400300 350 410
GB - 13
40SMC---N
Fan diagrams
Pa
100
90
80
70
60
50
40
30
20
10
40SMC028N
3
4
40SMC036N
100
90
80
70
1
60
1
Pa
2
50
40
30
20
10
2
3
4
0
220 250 300 400 450350
200 190 180 170 160 150 140 130 120 110
Pa
100
90 80 70 60 50 40 30 20 10
0
300 400 500 600 700 800 850 900
40SMC048N
1
2
3
4
Pa
1- Super high speed
(optional) 2- High speed 3- Medium speed 4- Low speed
Air flow (l/s)
0
300 350 400 450 500 550
200 190
180 170 160 150 140 130 120 110 100
90 80 70 60 50 40 30 20 10
0
300 400 500 600 700 800 900
40SMC060N
1
2
3
4
GB - 14
L010127H27 - 1205
Via R. Sanzio, 9 - 20058 Villasanta (MI) Italy - Tel. 039/3636.1
The manufacturer reserves the right to change any product specifications without notice.
December, 2005. Printed in Italy