Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory-- authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes and
National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety--alert symbol
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand these signal words: DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious h azards which will result in
severe personal injury or death.WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and
tag switch with a suitable warning label.
WARNING
!
!
INTRODUCTION
Section 1 of this Service Manual provides the necessary
information to service, repair, and maintain the EEZ family of
Puron air conditioners and heat pumps. Section 2 of this manual is
an appendix with data required to perform troubleshooting. Use
the Table of Contents to locate a desired topic.
MODEL NUMBER NOMENCLATURE
INDOOR UNIT
40MVC3--- 01
Fan Coil Unit
Unit Type
MVC --- Co o l i n g On l y
MVQ --- H e a t Pu m p
018
Nominal Capacity
009 --- 3 / 4 To n
012 --- 1 To n
018 --- 1 --- 1 / 2 To n
024 --- 2 To n s
---
Volt age
--- --- 3 0 V D C
1 --- 1 1 5 --- 1 --- 6 0
3 --- 208/230 ---1 ---60
38/40MVC, MVQ
A i r --- C o o l e d C o n d e n s e r
OUTDOOR UNIT
38MVC3--- 01
Unit Type
MVC --- Co o l i n g On l y
MVQ --- H e a t Pu m p
018
Nominal Capacity
009 --- 3 / 4 To n
012 --- 1 To n
018 --- 1 --- 1 / 2 To n
024 --- 2 To n s
---
SERIAL NUMBER NOMENCLATURE
Week of Manufacture
0106
V
00001
Serial Number
Volt age
1--- 11 5 --- 1 --- 6 0
3--- 208/230 --- 1 ---60
Year of Manufacture
Manufacturing Site
2
STANDARD FEATURES AND ACCESSORIES
Ease Of Installation
Mounting BracketsS
Low Voltage ControlsS
Comfort Features
Microprocessor ControlsS
Wireless Remote ControlS
Automatic Air SweepS
Air Direction ControlS
Auto Restart FunctionS
Cold Blow Protection On Heat PumpsS
Turbo M o d e O n Si z e s 9K a n d 1 2 KS
Auto Changeover On Heat PumpsS
Energy Saving Features
Sleep ModeS
Stop/Start TimerS
Safety And Reliability
3MinuteTimeDelayForCompressorS
Over Current Protection For CompressorS
Indoor Coil Freeze ProtectionS
Indoor Coil High Temperature Protection On Heat PumpsS
Condenser High Temperature Protection On heat Pumps{S
Accumulator On Heat PumpsS
Ease Of Service And Maintenance
Cleanable FiltersS
DiagnosticsS
Liquid Line Pressure TapsS
Suction And Discharge Pressure Taps (Sizes 18 and 24K)S
5 --- Year Compressor WarrantyS
1 --- Parts WarrantyS
Compressor Extended Warranty Years 6 Thru 10O
All Parts And Labor Years 2 Thru 5O
All Parts And Labor Years 2 Thru 5, Compressor Years 6
Thru 10
{ Sizes 18k & 24k
Legend
SStandard
A Accessory
OOptional
F Field Fabricated
O
INDOOR UNITS
On high wall fan coils, the condensate pump has a lift capability of
18 ft (5.5 m) or the discharge side with the pump mounted in the
fan coil or 6 ft (1.8 m) on the suction side if the pump must be
remote mounted. The pump mounts inside the unit with quick
plug--in connections, and is recommended when adequate drain
line pitch cannot be provided, or when the condensate must move
up to exit.
NOTE: An external 115v power source will be required to run the
pump on unit sizes 9k and 12k.
OUTDOOR UNITS
LOW AMBIENT KIT
The kit controls condenser fan cycling using a pressure switch. It is
specifically designed to control fan--motor cycles in response to
saturated condensing pressure. This device maintains a constant
saturated condensing temperature of 100 _F ± 10 _F (37.78_C ±
--12.22 _C) at outdoor--air temperatures between 55 _F and --20 _F
(12.78_C ± --12.22_C), and can be used on all outdoor units
without changing the outdoor fan motor.
CRANKCASE HEATER
Available for units with rotary compressors. Heater clamps around
compressor oil sump. Recommended for low-- ambient applications
on sizes 9, 12 , 18, 24 and long line applications.
A07892
Fig. 1 – Condensate Pump
38/40MVC, MVQ
3
SPECIFICATIONS -- COOLING ONLY UNITS
System Model Number5 3 M V C 0 0 9 --- --- --- 15 3 M V C 0 1 2 --- --- --- 15 3 M V C 0 1 2 --- --- --- 35 3 M V C 0 1 8 --- --- --- 3
System Voltage115 V115 V208/230208/230
Control Voltage0 --- 1 2 P u l s e D C0 --- 1 2 P u l s e D C0 --- 1 2 P u l s e D CPulse DC
Capacity (Btuh)9000120001200018000
System
SEER13.013.013.013.0
Refrigerant Typ eR--- 410A
Design Pressure (PSIG)550550550550
Metering DeviceCapillary Tube in Outdoor Unit
Charge (lb)2.32.93.04.4
Refrigerant
TypeRotary
ModelEA82X1C --- 1FZDU1EA108X1C--- 1FZDU1PA108X1C--- 3FZDUPA150X2C S--- 3KUU
O i l C h a r g e ( P O E --- o z )11.811.811.825.4
Capacitor45µF/250VAC45µF/250VAC35µF/370VAC40µF/370VAC
Rated Current (RLA)7.59.95.27.3
Max Lift (Fan Coil Above) (ft)35353550
Max Drop (Fan Coil Below) (ft)35353550
4
SPECIFICATIONS -- HEAT PUMP UNITS
System Model Number5 3 M V Q 0 0 9 --- --- --- 15 3 M V Q 0 1 2 --- --- --- 15 3 M V Q 0 1 2 --- --- --- 35 3 M V Q 0 1 8 --- --- --- 3
System Voltage115 V115 V208/230208/230
Control Voltage0 --- 1 2 P u l s e D C0 --- 1 2 P u l s e D C0 --- 1 2 P u l s e D CPulse DC
Capacity (Btuh)9000120001200018000
System
SEER13.013.013.013.0
HSPF7.77.77.77.7
Refrigerant Typ eR--- 410A
Design Pressure (PSIG)550550550550
Metering DeviceCapillary Tubes in Outdoor Unit
Charge (lb)2.353.03.0
Refrigerant
TypeRotary
ModelEA82X1C --- 1FZDU1EA108X1C--- 1FZDU1PA108X1C--- 3FZDUPA150X2C S--- 3KUU
O i l C h a r g e ( P O E --- o z )11.811.811.825.4
Capacitor45µF/250VAC45µF/250VAC35µF/370VAC40µF/370VAC
Rated Current (RLA)7.59.95.27.3
Use low ambient control if the unit will operate in cooling at ambient conditions below 55_F (12.78_C).
Fig. 4 – System Operating Enevelope
ELECTRICAL DATA
OPERATING
UNIT
SIZE
*Permissible limits of the voltage range at which the unit will operate satisfactorily
LEGEND
FLA --- Fu l l L o a d A m p s
LRA --- L o c k e d R o t o r A m p s
MCA - -- Minimum Circuit Amps
RLA ---RatedLoadAmps
VOLTAGE*
MAX/MINV O L T S --- P H --- H ZRLALRAFLAHPWVOLTSFLAHPW
009
0129.9471.180.044251525
012
0187.332.60.780.22453
0249.734.80.620.2181000.390.112501425
127/1041 1 5 --- 1 --- 6 0
253/187208/230---1 ---60
COMPRESSOROUTDOOR FANINDOOR FAN
7.540
5.2210.380.1163635 DC1.180.04425915
0.600.1022335 DC
208/230---1---60
1.10.034201220
0.260.075311120
A08180
MCA
MAX
FUSE/CB
AMP
8
WIRING
The main power is supplied to the outdoor unit. The field supplied connecting cable from the outdoor unit to indoor unit consists of four
wires and provides the power for the indoor unit as well as the communication signal between the outdoor unit and indoor unit.
Voltage drop on the connecting cable should be kept to a minimum. Use cable size and max length below:
18 AWG50 ft. (16 m)
16 AWG100 ft. (33 m)
CONNECTION DIAGRAMS
CONNECTING CABLE
CONTROL
CONNECTING CABLE
CONNECTING CABLE
CONTROL
38/40MVC, MVQ
Notes:
1. Do not use thermostat wire for any connection between indoor and outdoor units.
2. All connections between indoor and outdoor units must be as shown. The connections are sensitive to polarity.
3. On the 18k and 24k units, the “S” terminal “CONTROL” output is pulse DC with a potential AC voltage shock hazard.
1. The 38MVC/MVQ units are shipped with a full charge of
R410A refrigerant. All charges, line sizing, and capacities
are based on runs of 25 ft (7.6 m). For runs over 25 ft (7.6
m), consult long--line section on this page for proper charge
adjustments.
2. Minimum refrigerant line length between the indoor and
outdoor units is 10 ft. (3 m).
3. Refrigerant lines should not be buried in the ground. If it is
necessary to bury the lines, not more than 36--in (914 mm)
should be buried. Provide a minimum 6--in (152 mm)
vertical rise to the service valves to prevent refrigerant
migration.
4. Both lines must be insulated. Use a minimum of 1/2--in.
(12.7 mm) thick insulation. Closed-- cell insulation is
recommended in all long--line applications.
5. Special consideration should be given to isolating
interconnecting tubing from the building structure. Isolate
the tubing so that vibration or noise is not transmitted into
the structure.
S The following maximum lengths are allowed:
38/40MVC, MVQ
Unit Size
S The following are the piping sizes.
Refrigerant Charge
S Above charge is for piping runs up to 25 ft. (7.6 m).
S For piping runs greater than 25 ft. (7.6 m), add 0.1 oz. of
refrigerant per foot of extra piping up to the allowable
length.
1. A crankcase heater should be added for line lengths longer
than 25 ft (7.62 m) to prevent the migration of refrigerant to
the compressor during the “OFF” cycle.
2. A field fabricated wind baffle is recommended.
3. No change in line sizing is required.
4. Add refrigerant per table below.
ADDITIONAL CHARGE TABLE
Unit
Size
9K
cool
only
9K
hp
12K
cool
only
12K
hp
18K
cool
only
Tot a l
Line Length,
ft
Min.Max.
65
10
100
10 --- 25 ft
(3.05 --- 7.62m)
Additional Charge, oz.
none
> 2 5 --- 6 5 f t
(7.62 ---19.81m)
0.1 oz per
foot
> 6 5 --- 1 0 0 f t
(19.81 ---30.48m)
0.1 oz. per
foot
5. Reduction in capacity due to long lines can be calculated
from the chart below.
Failure to follow this caution may result in equipment
damage or improper operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the
recommended deep vacuum method of 500 microns. The alternate
triple evacuation method may be used if the procedure outlined
below is followed. Always break a vacuum with dry nitrogen.
SYSTEM VACUUM AND CHARGE
Using Vacuum Pump
1. Completely tighten flare nuts A, B, C, D, connect manifold
gage charge hose to a charge port of the low side service
valve. (See Fig. 15.)
2. Connect charge hose to vacuum pump.
3. Fully open the low side of manifold gage. (See Fig. 16)
4. Start vacuum pump
5. Evacuate using either deep vacuum or triple evacuation
method.
6. After evacuation is complete, fully close the low side of
manifold gage and stop operation of vacuum pump.
7. The factory charge contained in the outdoor unit is good for
up to 25 ft. (8 m) of line length. For refrigerant lines longer
than 25 ft (8 m), add 0.1 oz. per foot of extra piping up to
the maximum allowable length.
8. Disconnect charge hose from charge connection of the low
side service valve.
9. Fully open service valves B and A.
10. Securely tighten caps of service valves.
Outdoor Unit
Service Valve
CAUTION
Refrigerant
Low Side
A
High Side
B
Fig. 15 – Service Valve
Manifold Gage
Indoor Uni
C
D
A07360
Deep Vacuum
Method
The deep vacuum method requires a vacuum pump capable of
pulling a vacuum of 500 microns and a vacuum gage capable of
accurately measuring this vacuum depth. The deep vacuum method
is the most positive way of assuring a system is free of air and
liquid water. (See Fig. 17)
5000
4500
4000
3500
3000
2500
2000
MICRONS
1500
1000
500
01234567
MINUTES
LEAK IN
SYSTEM
VACUUM TIGHT
TOO WET
TIGHT
DRY SYSTEM
A95424
Fig. 17 – Deep Vacuum Graph
Triple Evacuation
Method
The triple evacuation method should only be used when vacuum
pump is only capable of pumping down to 28 in. of mercury
vacuum and system does not contain any liquid water.
Refer to Fig. 18 and proceed as follows:
1. Pump system down to 28 in. of mercury and allow pump to
continue operating for an additional 15 minutes.
2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and
open until system pressure is 2 psig.
4. Close service valve and allo w system to stand for 1 hr. During this time, dry nitrogen will be able to diffuse throughout
the system absorbing moisture.
5. Repeat this procedure as indicated in Fig. 18. System will
then be free of any contaminants and water vapor.
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
38/40MVC, MVQ
500 microns
Low side valve
Charge hose
Low side valve
High side valve
Charge hose
Fig. 16 – Manifold
Vacuum pump
A07361
CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS DEEP VACUUM)
RELEASE CHARGE INTO SYSTEM
A95425
Fig. 18 – Triple Evacuation Method
Final Tubing
Check
IMPORTANT: Check to be certain factory tubing on both
indoor and outdoor unit has not shifted during shipment.
Ensure tubes are not rubbing against each other or any sheet
metal. Pay close attention to feeder tubes, making sure wire ties
on feeder tubes are secure and tight.
19
CONTROL SYSTEM
The 40MVC/MVQ unit is equipped with a microprocessor control to perform two functions:
1. Provide safety for the system
2. Control the system and provide optimum levels of comfort and efficiency
The main microprocessor is located on the control board of the fan coil unit (outdoor units have a microprocessor too) with thermistors
located in the fan coil air inlet and on the indoor coil. Heat pump units have a thermistor on the outdoor coil. These thermistors monitor the
system operation to maintain the unit within acceptable parameters and control the operating mode.
SYSTEM SAFETIES
Safety
3MinTimeDelayXXXXXXXX
Over Current Protection On CompressorXXXXXXXX
Indoor Coil Freeze ProtectionXXXXXXXX
Condenser High Temperature ProtectionXXXX
Indoor Evaporator High TemperatureXXXX
9K012K018K024K09K012K018K024K
Cooling OnlyHeat Pump
3MINUTETIMEDELAY
In order to protect the compressor, there is a 3 minute delay on break even if the control is calling for heating or cooling.
38/40MVC, MVQ
COMPRESSOR OVERCURRENT PROTECTION
Overcurrent protection can result due to any of the following:
SThe ambient temperature is to high
SLocked rotor on the compressor
SBlockage in refrigeration circuit (cap tubes, for example)
SOutdoor air is blocked or restricted
The compressor current is monitored continuously and protection is provided as shown below:
3 sec
5 min
1 sec
Normal
Current down
Indoor fan: On
compressor: On
outdoor fan: On
Compressor off
(after 5 minutes)
Outdoor fan
off (heating)
Indoor fan low
speed (cooling)
Compressor off
(after 3 seconds)
Current up
A08117
Fig. 19 – Compressor Overcurrent Protection
If the compressor is stopped 4 times at the 5 minute limit or 1 time at the 3 second limit, the system will be locked off and the main power will
have to be reset before the system can be restarted.
The indoor coil can freeze due to any of the following:
S Low system charge
S Reduced indoor airflow
S Restricted refrigerant flow
S Low ambient temperature (outdoor)
S Low load (indoor)
In cooling mode, the thermistor located on a return bend of the
indoor coil monitors the coil temperature continuously. Any time
the coil temperature drops below the TE5 limit for five consecutive
minutes, the compressor and outdoor fan will be switched off until
the coil temperature rises above the TE6 as shown below:
Condenser high temperature can occur due to any of the following
conditions:
S High outdoor ambient
S Outdoor fan blocked
S Outdoor coil blocked
The outdoor coil thermistor on a heat pump unit continuously
monitors the temperature of the outdoor coil. Anytime the coil
temperature exceeds the TE10 limit, the compressor is switched off
and the outdoor fan continues running to reduce the coil
temperature. When the coil temperature drops below the TE11
limit, the compressor is switched back on as shown below:
High indoor coil temperature (in heating mode) can occur due to
any of the following:
S High outdoor ambient temperature
S Indoor fan blocked
S Indoor coil blocked (including dirty filters)
The indoor coil thermistor on a heat pump unit continuously
monitors the temperature of the indoor coil during heating
operation. Anytime the coil temperate exceeds the TE8 limit, the
outdoor fan is switched off. If the coil temperature continues to
climb and exceeds the TE7 limit, the compressor is switched off.
When the coil temperature drops below the TE9 limit, the
compressor and outdoor fan are switched back on as shown
below:
A wireless remote control, supplied with the unit, is the interface
between the fan coil and the user. The wireless remote control has
the following characteristics:
S Capable of displaying _Cand_F with _C being the default
setting. To change the default setting, refer to the Owner’s
Manual or push the recessed F/C button once using a paper
clip or similar object*.
S The remote control setpoint range is from 62_F(17_C) to
88_F(30_C) in increments of 2_F(1_C).
S There is a dedicated cooling only and heat pump remote
control.
S The wireless remote control has an operating range of 25 ft.
(7.62 m).
S The same remote control can be used to control more than one
unit.
S If the remote control is lost, damaged, or the batteries are
exhausted, the system can be operated by using the manual
button (forced Auto) located under the front panel.
38/40MVC, MVQ
Manual button
Fig. 23 – Manual Button Location on Unit
* On units produced during week 12 (2008) and later. Units
produced before week 12 have dedicated _Cor_F controls.
21
A07364
MODES OF OPERATION
The units have 5 main operating modes:
1. Fan Only
2. Cooling
3. Heating (heat pumps only)
4. Auto
5. Dehumidification (Dry)
The units have 2 other modes (manual operation) that are operated
in unique situations:
1. Auto Forced Mode (Emergency)
2. Test Mode
Fan Mode
In this mode, the system circulates the room air without changing
the room air temperature.
Cooling
In this mode, the system cools and dries the room air with the fan
running continuously, either at a selected fan speed or Auto fan
speed. The fan runs even when the compressor cycles off. This
feature enhances room comfort and efficiency of the system.
When the unit is operating in cooling, two sub modes can also be
selected:
38/40MVC, MVQ
Compressor and Outdoor Fan
The compressor and outdoor fan motor cycle on and off based on
the conditions of the set point and the room temperature as shown
below. There is no minimum run time.
Indoor Fan
When in cooling mode, the fan runs continuously either at the
chosen set speed , or in Auto mode, where the speed is determined
by the microprocessor based on the difference between the room
temperature and the temperature set point as shown below:
Room temp. down
Only
Mode
1. Sleep Mode is an energy saving feature that changes the set
point automatically.
2. Turbo Mode is a comfort feature on the 9k and 12k units
where the set point is reached quickly by having the fan run
on high speed regardless of the speed that has been selected.
Operation
Compressor and
outdoor fan on
Room temp. down
T = Room Temperature
Ts = Set Point Temperature
Compressor off
fan off
0 1.8°FT-Ts
Room temp. up
Fig. 24 – Compressor and Outdoor Fan -- Cooling Mode
Operation
Med fan
Room temp. up
High fan
A08106
Sleep
Mode
When in cooling mode, additional energy savings can be realized
by selecting the Sleep setting. When the Sleep setting is selected,
the temperature set point is adjusted automatically as shown below:
Set point
1.8
°
F
°
F
1.8
Time (hour)12
A08108
Fig. 26 – Sleep Mode
The unit will shut off 7 hours after the Sleep Mode is selected.
Mode
Turbo
When in cooling mode, selecting Turbo will allow the indoor unit
to satisfy the temperature set point as quickly as possible. In Turbo
Mode, the indoor fan will shift to high speed and either run
continuously for 20 minutes or until the user pushes the Turbo
button again, at which point the fan speed will return to the original
setting.
Heating
Mode
In this mode, the system heats the room air with the indoor fan
running at either the selected speed or on Auto. As in the cooling
mode, the indoor fan will run continuously unless interrupted by
the cold blow algorithm. This algorithm will not allow the fan to
run if the indoor coil temperature drops below a preset value.
The sleep function can be selected while the unit is running in the
Heating Mode.Defrost is controlled by the on --board
microprocessor.
Compressor and Fan
Operation
The compressor and outdoor fan cycle on and off based on the
actual room temperature versus the set point as shown below.
When the compressor starts, it will run continuously for 7 minutes
even if the set point condition is satisfied.
The 4--way value is energized in heating and will stay energized for
2 minutes after the mode is changed into a non--heating mode.
Compressor on
outdoor fan off
Room temp. down
T = Room Temperature
TS = Set Point Temperature
* For 9k & 12k Units Only. For 18k and 24k units, numbers will be 5.4 and 7.2 respectively.
Compressor off
outdoor fan on
Ts+5.4*Ts+3.6*TsT
Room temp. up
A08109
Fig. 27 – Compressor and Outdoor Fan -- Heating Mode
Low fan
T= Room Temperature
Ts = Set Point Temperature
Fig. 25 – Auto Fan -- Cooling Mode
9.0 °F7.2 °F1.8 °FT-Ts
A08107
22
Fan
Auto
When the fan speed is set to Auto, the fan will run at either the
medium or low speed based on the difference between the room
temperature and the set point temperature as shown below:
Low. Speed
Room temp. down
T = Room Temperature
Ts = Set Point Temperature
Med. Speed
0
3.6°F
Room temp. up
T-Ts
A08112
Fig. 28 – Auto Fan -- Heating Mode
Manual Indoor
Fan
The indoor fan will run continuously in heating at the set fan speed
(even if the compressor cycles off) unless the indoor coil
temperature begins to drop. When the coil temperature drops to
the TE3 limit, the 18k and 24k unit indoor fan switches to low
speed. On the 9k and 12k unit the indoor fan switches to ultra low
speed. When the coil temperature drops to the TE4 limit, the
indoor fan on all systems shuts off to prevent cold blow as shown
below. The cold blow algorithm also applies to the auto fan
setting.
When in heating mode additional energy savings can be realized
by selecting the Sleep setting. When the Sleep setting is selected,
the temperature set point is adjusted automatically as shown below:
Set Point
Defrost
Defrost on heat pump units is controlled by the microprocessor and
is initiated if either of the following conditions occur:
1. The outdoor coil temperature is lower than 32_F(0_C) for
more than 40 minutes and during that period, the coil
temperature is continuously lower than 26.6_F(--3_C) for 3
minutes.
2. If the first condition does not occur within 90 minutes of
termination of the last defrost cycle.
The defrost cycle will terminate 10 minutes after initiation or when
the coil temperature reaches 68_F(20_C). At the end of the
Defrost cycle the timer resets automatically.
The cycles of defrost algorithm are shown below:
Defrost 10 or 6 minutes
10s
On
Off
5s
25s
2s
A08114
Compressor
4-way valve
Outdoor fan
Indoor fan
Fig. 31 – Defrost Cycle
Mode
Auto
When the Auto setting is selected, the microprocessor looks at the
difference between the room temperature (T) and the set point
(TS). The algorithm determines which mode the unit will run in as
shown below:
Heating (fan only in cooling)Fan only Cooling
°
F 3.6°F
-1.8
T-TS
A08115
Fig.32–AutoMode
When the unit shifts modes, it will remain in that mode for at least
15 minutes while the algorithm ignores the difference between T
and TS. This ensures that the unit cannot change modes too
frequently.
38/40MVC, MVQ
1.8ºF
1.8ºF
Time (hour)12
Fig. 30 – Sleep Mode -- Heating
The unit will shut off 7 hours after the Sleep mode is selected.
A08110
23
Dry (Dehumidification)
Mode
When more humidity control is desired, the Dry setting can be
selected. Lower humidity is achieved when the microprocessor
adjusts the indoor fan speed and compressor cycling by comparing
the room temperature (T) and the set point temperature (TS).
There are two different control algorithms:
Size 9k and 12 k
units:
T = TS + 3.6 -- the compressor will run for 6 minutes and the
indoor fan will run at low speed. The compressor will be off for 4
minutes and the indoor fan will run in ultra low speed.
TS = T < TS + 3.6 -- The compressor will run for 5 minutes and the
indoor fan will run at low speed. The compressor will be off for 5
minutes and the indoor fan will run in ultra low speed.
T < TS -- The compressor will run for 4 minutes and the indoor
fan will run at low speed. The compressor will be off for 6 minutes
and the indoor fan will run in ultra low speed.
Size 18k and 24k
units:
These units do not have ultra low speed.When set for
dehumidification, the indoor fan runs at low speed and the
compressor cycles based on the difference between T and TS.
Manual Operation
The unit can be set for Forced Auto or Forced Cooling manually
by pushing the Manual button once or twice as shown below:
38/40MVC, MVQ
Push 3 Times
Remote
mode
Push OncePush Twice
Forced
auto
Forced
cooling
Forced Auto (Emergency
Operation)
Forced Auto option allows operation of the unit if the remote
control is lost or the batteries have expired. When the system is in
Forced Auto, it will run with a default set point of 75.2_F. While
in Forced Auto, the system will respond to signals from the remote
control.
Forced Cooling
Operation
This option is used for diagnostic purposes. The system is forced
to run in cooling for 30 minutes.
After 30 minutes, the 9k and 12k systems will switch to Dry mode
with a default set point of 75.2_F. The 18k and 24k systems will
switch to Forced Auto mode. When the system is in Forced
Cooling mode, it will not respond to signals from the remote
control. The only way to exit the Forced Cooling mode is to push
the manual button once to switch the system to remote control
mode.
Fig. 33 – Manual Operation
A08116
24
TROUBLESHOOTING
This section provides the required flow charts to troubleshoot problems that may arise.
NOTE: Information required in the diagnoses can be found either on the wiring diagrams or in the appendix.
Required
Tools:
The following tools are needed when diagnosing the units:
S Digital multimeter
S Screw drivers (Phillips and straight head)
S Needle--nose pliers
Recommended
Steps
1. Refer to the diagnostic hierarchy chart below and determine the problem at hand.
2. Go to the chart listed in the diagnostic hierarchy and follow the steps in the chart for the selected problem.
DIAGNOSTIC HIERARCHY
Unit has a problem
Unit has a problem
Unit displays a
Unit displays a
diagnostic code
diagnostic code
Unit not running and
Unit not running and
no diagnostic code
no diagnostic code
Unit running but not
Unit running but not
optimally
optimally
38/40MVC, MVQ
Refer to page ---
Refer to page A8 & A9
identify error code*
appropriate diagnostic chart
* For EEROM error, replace the indoor microprocessor board
* For EEROM error, replace the indoor microprocessor board
and use
Go to chart # 7Go to chart # 8 & 9
Go to chart Go to chart #
For the ease of service, the systems are equipped with diagnostic
code display LED’s on both the indoor and outdoor units. The
outdoor diagnostic display is an LED on the outdoor unit board
and is limited to very few errors. However, it is useful in
identifying special error codes like a failure of the outdoor coil
sensor on heat pumps. The indoor diagnostic display is a
combination of flashing LED’s on the display panel on the front of
the unit. If possible always check the diagnostic codes displayed on
the indoor unit first.
The diagnostic codes for the indoor and outdoor units are listed in
appendix A8 and A9.
Problems may occur that are not covered by a diagnostic code, but
are covered by the diagnostic flow charts starting with the
diagnostic hierarchy. These problems will be typical air
conditioning mechanical or electrical issues that can be corrected
using standard air conditioning repair techniques.
A08165
For problems requiring measurements at the control boards please
note the following:
1. Always disconnect the main power.
2. When possible check the outdoor board first.
3. Start by removing the outdoor unit top cover.
4. Reconnect the main power
5. Probe the outdoor board inputs and outputs with a digital
multi--meter referring to the wiring diagrams and
input/output charts found in the appendix.
6. Connect the red probe to hot signal and the black probe to
the ground or negative.
7. Note that some of the DC voltage signals are pulse will give
continuously variable readings.
8. If it is necessary to check the indoor unit board you must
start by disconnecting the main power.
9. Next remove the front cover of the unit and then control
box cover.
10. Carefully remove the indoor board from the control box,
place it face up on a plastic surface (not metal).
11. Reconnect the main power and repeat steps 5,6, and 7.
12. Disconnect main power before reinstalling board to avoid
shock hazard and board damage.
25
CHART 1 -- I NDOOR FAN SPEED OUT OF CONTROL
Reset main power and
Reset main power and
restart system using remote.
restart system using remote.
Problem persists?
Problem persists?
Yes
Yes
Check motor connection.
Check motor connection.
Connection good?
Connection good?
Yes
Yes
No
No
No
No
No further action is
No further action is
required
required
Fix connection
Fix connection
38/40MVC, MVQ
Check IFM output and input
on indoor board.
Values good?
Yes
Yes
Replace indoor fan motor
Replace indoor fan motor
No
No
Replace indoor board
Replace indoor board
A08166
26
CHART 2 -- TEMPERATURE SENSOR
Reset main power and
restart system using remote.
Problem persists?
Yes
Yes
Check sensor connector
at ID or OD board
Connection good?
Yes
Yes
Check input and output
on indoor or outdoor board.
Yes
Yes
Check sensor resistance.
Appendix 6
YesYes
No
No
No
No
No
No
No
No
No further action is
required
Fix connection
Replace board
38/40MVC, MVQ
Replace sensor
Double check connection,
for corrosion or high
resistance.
A08167
27
CHART 3 -- COMPRESSOR OVERCURRENT PROTECTION
Is unit running in outdoor
Is unit running in outdoor
ambient higher than
ambient higher than
125 °F?
125 °F?
No
No
Outdoor coil clean?
Outdoor coil clean?
Yes
Yes
Check connections from
Check connections from
OD board. Corrosion, or
OD board. Corrosion, or
high resistance
high resistance
No
No
Outdoor fan Ok?
Outdoor fan Ok?
Yes
Yes
Yes
Yes
Beyond operating range
Beyond operating range
NoNo
NoNo
No
No
Clean coil.
Clean coil.
Problem persists?
Problem persists?
Yes
Yes
Clean/repair connection
Clean/repair connection
Problem persists?
Problem persists?
Yes
Yes
Change outdoor motor
Change outdoor motor
No
No
Problem solved
Problem solved
Problem solved
Problem solved
38/40MVC, MVQ
Replace compressor
Replace compressor
Connect gauges to unit.
Connect gauges to unit.
pressures ok?
pressures ok?
Yes
Yes
Check amp draw to
Check amp draw to
No
No
compressor? Values within
compressor? Values within
range?
range?
Yes
Yes
Replace outdoor board
Replace outdoor board
No
No
High head, high suction?High head, low suction?
High head, high suction?High head, low suction?
Yes
Yes
Unit is overcharged.
Unit is overcharged.
Reclaim charge and weigh
Reclaim charge and weigh
in correct charge.
in correct charge.
No
No
Yes
Yes
Restriction in refrigeration
Restriction in refrigeration
circuit.
circuit.
A08168
28
CHART 4 -- INDOOR UNIT COMMUNICATION ERROR SIZ E 9K AND 12K
Notes:
Check the wires and
Check the wires and
connections between
connections between
Indoor and outdoor units*
Indoor and outdoor units*
Yes
Yes
Reset main power and
Reset main power and
restart system using remote.
restart system using remote.
Problem persists?
Problem persists?
Yes
Yes
Measure Volts DC on
Measure Volts DC on
outdoor TB between 1 & 3.
outdoor TB between 1 & 3.
Ok?**
Ok?**
No
No
No
No
Yes
Yes
Fix connection or
Fix connection or
replace wiring
replace wiring
No further action is
No further action is
required
required
Measure Volts DC on
Measure Volts DC on
indoor TB between 1 & 3.
indoor TB between 1 & 3.
Ok?**
Ok?**
Notes:
Before measuring the Volts DC on outdoor TB,
Before measuring the Volts DC on outdoor TB,
disconnect the field wire on terminal 1.
disconnect the field wire on terminal 1.
Before measuring the Volts DC on Indoor TB,
Before measuring the Volts DC on Indoor TB,
disconnect the field wire on terminal 1.
Have the red probe of the meter on terminal 1
and the black probe on terminal 3. Reconnect
wiring when measurements are complete.
Recheck wiring and
Recheck wiring and
connections
connections
No
No
.
Replace outdoor board.
Replace outdoor board.
* Make sure wires are connected per connection diagrams. Failing to do that will result in a communication error.
** There is a 2 to 3 minute window to take the measurement before the diagnostic light is on again.
** There is a 2 to 3 minute window to take the measurement before the diagnostic light is on again.
.
Replace indoor board.
Replace indoor board.
No
No
38/40MVC, MVQ
A08181
29
Outdoor coil clean?
Outdoor coil clean?
CHART 5 -- OUTDOOR UNIT PROTECTS
Clean coil. Problem
NoNo
Clean coil. Problem
NoNo
persists?
persists?
Problem solved
Problem solved
Yes
Yes
Check outdoor unit
Check outdoor unit
board. Indicator light
board. Indicator light
flashing twice?
flashing twice?
No
No
Connect gauges to
Connect gauges to
unit. Pressures ok?
unit. Pressures ok?
No
No
Suction and head
Suction and head
equal?
38/40MVC, MVQ
equal?
Yes
Yes
Check compressor
Check compressor
* Restriction in system. Check capillary tube, check for moisture, and check for damage to liquid line between indoor and
* Restriction in system. Check capillary tube, check for moisture, and check for damage to liquid line between indoor and
outdoor units.
outdoor units.
Yes
Yes
Yes
Yes
NoNoNo
NoNoNo
Check sensors.
Check sensors.
Flow Chart #2
Flow Chart #2
Check application
Check application
Normal suction,
Normal suction,
Non condensables
Non condensables
in sys. Pump down
in sys. Pump down
and recharge unit
and recharge unit
Yes
Yes
limits
limits
high head?
high head?
YesYes
YesYes
Unit is overcharged.
Unit is overcharged.
Reclaim charge and
Reclaim charge and
weigh in correct charge
weigh in correct charge
High head, high
High head, high
suction?
suction?
High head, low
High head, low
suction?
suction?
Yes
Yes
See note below
See note below
*
*
A08182
30
CHART 6 -- INDOOR UNIT COMMUNICATION ERROR SIZE 18K AND 24K
Check the wires and
Check the wires and
Check the wires and
connections between
connections between
connections between
Indoor and outdoor units*
Indoor and outdoor units*
Indoor and outdoor units*
Yes
Yes
Yes
Reset main power and
Reset main power and
Reset main power and
restart system using remote.
restart system using remote.
restart system using remote.
Problem persists?
Problem persists?
Problem persists?
Yes
Yes
Yes
Measure VDC reading on
Measure VDC reading on
Measure VDC reading on
outdoor between S and G.
outdoor between S and G.
outdoor between S and G.
Reading positive? **
Reading positive? **
Reading positive? **
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
Fix connection or
Fix connection or
Fix connection or
replace wiring
replace wiring
replace wiring
No further action is
No further action is
No further action is
required
required
required
Replace outdoor board
Replace outdoor board
Replace outdoor board
Notes:
Notes:
Notes:
When unit is operating normally and a DC
When unit is operating normally and a DC
When unit is operating normally and a DC
voltage reading is taken between the S and
voltage reading is taken between the S and
voltage reading is taken between the S and
G terminal on the outdoor unit (or indoor
G terminal on the outdoor unit (or indoor
G terminal on the outdoor unit (or indoor
unit) positive and negative readings will
unit) positive and negative readings will
unit) positive and negative readings will
fluctuate between 0 and 24V DC.
fluctuate between 0 and 24V DC.
fluctuate between 0 and 24V DC.
If indoor board is bad, only a positive
If indoor board is bad, only a positive
If indoor board is bad, only a positive
readings will be registered between
readings will be registered between
readings will be registered between
terminals S and G on the outdoor unit. The
terminals S and G on the outdoor unit. The
terminals S and G on the outdoor unit. The
reverse will apply if outdoor board is bad
reverse will apply if outdoor board is bad
reverse will apply if outdoor board is bad
(only negative readings will register).
(only negative readings will register).
(only negative readings will register).
Above data is obtained by having the red
Above data is obtained by having the red
Above data is obtained by having the red
probe of the meter on the S terminal and
probe of the meter on the S terminal and
probe of the meter on the S terminal and
the black probe on the G terminal.
the black probe on the G terminal.
the black probe on the G terminal.
.
.
Replace indoor board.
Replace indoor board.
Replace indoor board.
* Make sure wires are connected per connection diagrams i.e. L1 to L1 and L2 to L2. Failing to do that will result in a
* Make sure wires are connected per connection diagrams i.e. L1 to L1 and L2 to L2. Failing to do that will result in a
communication error.
communication error.
** There is a 2 to 3 minute window to take measurements before the diagnostic light is on again.
** There is a 2 to 3 minute window to take measurements before the diagnostic light is on again.
.
A08183
38/40MVC, MVQ
31
Reset circuit breaker. Is unit
Reset circuit breaker. Is unit
38/40MVC, MVQ
running?
running?
Problem solved
Problem solved
CHART 7 -- UNIT NOT RUNNING, NO DIAGNOSTIC CODE
Use auto forced function.
Use auto forced function.
Unit runs?
Unit runs?
Yes
Yes
Reset remote and restart
Reset remote and restart
the unit. Is unit running?
the unit. Is unit running?
YesYes
YesYes
Problem solved
Problem solved
Is there power to outdoor
Is there power to outdoor
unit?
unit?
Yes
Yes
Check fuse on outdoor
Check fuse on outdoor
board. Ok?
board. Ok?
Yes
Yes
Check input and output on
Check input and output on
outdoor board. Ok?
outdoor board. Ok?
Yes
Yes
Check components. Ok?
Check components. Ok?
Flow charts 10 thru 12
Flow charts 10 thru 12
No
No
Replace defective
Replace defective
component
component
NoNo
NoNo
No
No
No
No
Yes
Yes
Check batteries. OK?Replace battery
Check batteries. OK?Replace battery
Go to chart #13
Check wiring and circuit
Check wiring and circuit
breaker and fix
breaker and fix
Replace fuse
Replace fuse
Replace outdoor board
Replace outdoor board
Check fuse(s) on indoor
Check fuse(s) on indoor
board. Ok?*
board. Ok?*
No
No
Replace fuse
Replace fuse
Yes
Yes
Replace indoor board
Replace indoor board
Check input and output on
Check input and output on
indoor board. Ok?
indoor board. Ok?
Determine defective
Determine defective
component and replace
component and replace
Yes
Yes
No
No
NoNo
NoNo
No
No
* For sizes 18 and 24 K units only. For sizes 9 and 12K units proceed to check inputs and outputs on indoor boards.
* For sizes 18 and 24 K units only. For sizes 9 and 12K units proceed to check inputs and outputs on indoor boards.
A08169
32
Outdoor coil clean?
Outdoor coil clean?
CHART 8 -- UNIT NOT RUNNING OPTIMALLY
NoNo
NoNo
Clean coil. Problem
Clean coil. Problem
persists?
persists?
Problem solved
Problem solved
Yes
Yes
Indoor filter clean?
Indoor filter clean?
Yes
Yes
Check indoor fan
Check indoor fan
motor
motor
Yes
Yes
Connect gauges to
Connect gauges to
unit. Pressures ok?
unit. Pressures ok?
No
No
Suction and head
Suction and head
equal?
equal?
Yes
Yes
Check compressor
Check compressor
Yes
Yes
Clean filter. Problem
NoNo
Clean filter. Problem
NoNo
persists?
persists?
Yes
Yes
No
No
Replace indoor fan
Replace indoor fan
motor.
motor.
Yes
Yes
Check application
Check application
limits.
limits.
NoNoNo
NoNoNo
Normal suction,
Normal suction,
high head?
high head?
YesYes
YesYes
Non condensables
Non condensables
in sys. Pump down
in sys. Pump down
and recharge unit
and recharge unit
Problem solved
Problem solved
High head, high
High head, high
suction?
suction?
Unit is overcharged.
Unit is overcharged.
Reclaim charge and
Reclaim charge and
weigh in correct charge
weigh in correct charge
High head, low
High head, low
suction?
suction?
Yes
Yes
See note below*
See note below*
38/40MVC, MVQ
* Restriction in system. Check capillary tube, check for moisture, and check for damage to liquid line between indoor and
* Restriction in system. Check capillary tube, check for moisture, and check for damage to liquid line between indoor and
outdoor units.
outdoor units.
A08170
33
CHART 9 -- UNIT NOT RUNNING OPTIMALLY (HP IN HEATING)*
No
Visually check outdoor
Visually check outdoor
Unit for ice blockage. **
Unit for ice blockage. **
Yes
Yes
Check defrost sensor. Ok?
Check defrost sensor. Ok?
Go to flow chart #2
Yes
Yes
Check application limits.
Check application limits.
Ok?
Ok?
No
No
No
No
No
Check reversing valve.
Check reversing valve.
Go to flow chart #12
Replace sensor
Replace sensor
Beyond operating range
Beyond operating range
38/40MVC, MVQ
Yes
Yes
Check ambient conditions.
Check ambient conditions.
Prime icing?
Prime icing?
Yes
Yes
Explain to customer
Explain to customer
* To supplement flow chart #8
** Check for blockage on outdoor coil and drain pan. Are the holes in drain pans blocked?
es in drain pans blocked?
A08184
34
CHART 10 -- COMPRESSOR
Trace connections from
Trace connections from
OD board. Connections
OD board. Connections
ok?
ok?
Yes
Yes
Check contactor.*
Check contactor.*
Contactor ok?
Contactor ok?
Yes
Yes
Check capacitor.
Check capacitor.
Capacitor ok?
Capacitor ok?
Yes
Yes
No
No
No
No
No
No
No fix connection
No fix connection
Replace contactor
Replace contactor
Replace capacitor
Replace capacitor
No
Check compressor
Check compressor
windings. Ok?
windings. Ok?
No
No
Compressor ok.
Compressor ok.
* For size 9 and 12k units contactor is on outdoor board.
Check contactor output on outdoor board if not done already.
If bad, replace outdoor board.
No
Replace compressor
Replace compressor
38/40MVC, MVQ
A08171
35
38/40MVC, MVQ
CHART 11 -- OUTDOOR MOTOR
Visually confirm that fan
Visually confirm that fan
blades and outdoor coil
blades and outdoor coil
are not blocked.
are not blocked.
Yes
Yes
Trace connections from
Trace connections from
OD board. Connections
OD board. Connections
ok?
ok?
Yes
Yes
Check capacitor.
Check capacitor.
Capacitor ok?
Capacitor ok?
Yes
Yes
Check motor windings.
Check motor windings.
Ok?
Ok?
No
No
No
No
No
No
No
No
Clear blockage
Clear blockage
Fix connection
Fix connection
Replace capacitors
Replace capacitors
Replace motor
Replace motor
Yes
Yes
Motor ok.
Motor ok.
A08172
36
CHART 12 -- REVERSING VALVE
No
Check RV connection on
Check RV connection on
outdoor board. Ok?
outdoor board. Ok?
Yes
Yes
Check RV output on outdoor
Check RV output on outdoor
board. Ok?
board. Ok?
Yes
Yes
Check RV solenoid. Ok?Replace solenoid
Check RV solenoid. Ok?Replace solenoid
Yes
Yes
Replace reversing valve.
Replace reversing valve.
No
No
No
No
No
Clean or repair the
Clean or repair the
connection
connection
Replace outdoor board
Replace outdoor board
38/40MVC, MVQ
CHART 13 -- RECEIVER BOARD
Check wiring and
Check wiring and
connection between
connection between
receiver and ID board. Ok?
receiver and ID board. Ok?
Yes
Yes
Check input and output
Check input and output
on ID and receiver
on ID and receiver
boards. Ok?
boards. Ok?
Yes
Yes
Replace remote control
Replace remote control
No
No
No
No
Fix wiring or
Fix wiring or
connection
connection
Replace receiver board
Replace receiver board
A08173
37
APPENDIX
APPENDIX TABLE OF CONTENTS
DESCRIPTIONNUMBER
Control Boards Input/Output tables for 53MVC009(12)------1A1...................................................
Control Boards Input/Output tables for 53MVQ009(12)------1A2...................................................
Control Boards Input/Output tables for 53MVC012-- -- --3A3.......................................................
Control Boards Input/Output tables for 53MVQ012-- -- --3A4......................................................
Control Boards Input/Output tables for 53MVC018-- -- --3A5.......................................................
Temperature Sensor V alues (Temperature vs. Resistance)A6.......................................................
CN10OUT: (Pin 1: Ground, Pin 2 ~ Pin 5: 0 to 5 Volts DC) Pulse relative to Pin 1
CN11OUT: (Pin 5: Ground, all other Pins are 0 to 17 Volts DC) Pulse relative to Pin 5
CN12Two way signal, 0 to 24 Volts DC, Pulse relative to Ground
P1IN:L1 208/230 Volts AC
P2IN:L2 208/230 Volts AC
INDOOR UNIT DISPLAY BOARD
CONNECTORINPUT or OUTPUT VALUE
CN1IN: (Pin 1: Ground, Pin 2 ~ 5: 0 to 5 Volts DC) Pulse relative to Pin 1
CN2IN: (Pin 1: Ground, Pin: 5 Volts DC)OUT: (Pin 3: 0 to 5 Volts DC) Pulse relative to Pin 1
38/40MVC, MVQ
41
A6 -- Characteristics of Temperature Sensor
Tem p . ˚F/˚CResistance KΩTe m p . ˚F/˚CResistance KΩTe m p . ˚F/˚CResistance KΩ
14/--- 1062.275662.6/1714.6181111.2/444.3874
15.8/--- 958.707964.4/1813.918113/454.2126
17.6/--- 8056.369466.2/1913.2631114.8/464.0459
19.4/--- 752.243868/2012.6431116.6/473.8867
21.2/--- 649.316169.8/2112.056118.4/483.7348
23/--- 546.572571.6/2211.5120.2/493.5896
24.8/--- 44473.4/2310.9731122/503.451
26.6/--- 341.587875.2/2410.4736123.8/513.3185
28.4/--- 239.823977/2510125.6/523.1918
30.2/--- 137.198878.8/269.5507127.4/533.0707
32/035.202480.6/279.1245129.2/542.959
33.8/133.326982.4/288.7198131/552.8442
35.6/231.563584.2/298.3357132.8/562.7382
37.4/329.905886/307.9708134.6/572.6368
39.2/428.345987.8/317.6241136.4/582.5397
41/526.877889.6/327.2946138.2/592.4468
42.8/625.495491.4/336.9814140/602.3577
44.6/724.193293.2/346.6835141.8/612.2725
38/40MVC, MVQ
46.4/822.566295/356.4002143.6/622.1907
48.2/921.809496.8/366.1306145.4/632.1124
50/1020.718498.6/375.8736147.2/642.0373
51.8/1119.6891100.4/385.6296149/651.9653
53.6/1218.7177102.2/395.3969150.8/661.8963
55.4/1317.8005104/405.1752152.6/671.83
57.2/1416.9341105.8/414.9639154.4/681.7665
59/1516.1156107.6/424.7625156.2/691.7055
60.8/1615.3418109.4/434.5705158/701.6469
42
A7 -- Fuse Chart
r
Unit Size
IndoorOutdoorOutdoor
Fuse Rating (Amps/Volts)
009---3.15A/250V2A/250V
012---3.15A/250V2A/250V
0183.15A/250V3.15A/250V---
0243.15A/250V3.15A/250V---
The 3.15A fuses protect the board against the indoor or outdoor fan motors.
The 2A fuses protect the board against a Class II circuit board failure.
A8 -- Indoor Unit Diagnostic Guides
9K & 12K Units
Operation
Lamp
lXIndoor fan speed has been out of control for over 1 minute1
lOnIndoor room temp. or evaporator sensor is open circuit or short circuited2
XlCompressor over--- current protection has been activated four times3
OnlEPROM error*---
llIndoor unit communication error (Illuminates simultaneously)4
Opera-
tion
Lamp
llllOver- -- current protection of the compressor occurs four times3
XlXXIndoor room temp. sensor is open circuit or short circuited2
lXXXTemp. sensor on indoor evaporator is open circuit or short circuited2
XXlX
XXllOutdoor unit protects (outdoor temp. sensor, phase order, etc.)5
XlXlEPROM error*--XXXlIndoor unit communication error6
l =Flashing
X=Off
* = Replace Indoor Board
Timer
Lamp
Timer
Defrosting
Lamp
Infrared signal receptor
OPERATION
AUTO
ECON
Model size 009
Lamp
TIMER
PRE-DEF
A07545a
Auto
Lamp
Failure Mode
18K & 24K Units
Failure Mode
Temp. sensor on outdoor condenser is open circuit or short circuited (not
cooling only modes)
TIMER
PRE-DEF
OPERATION
Model size 012
Infrared signal recepto
OPERATION
A07544
AUTO
Model size 018--024*
TIMER
Diagnostic
Chart
Diagnostic
Chart
2
PRE.-DEF.
A07546a
38/40MVC, MVQ
* PRE--DEF light will illuminate when the unit is running in FAN ONLY mode on Cooling Only units.
Fig. 34 – LED Display Panel
A9 -- Outdoor Unit Diagnostic Guides
Flashing
Times after 2
Failure Mode
Second Off
5Communication failure4or6
2Condenser temperature sensor failure2
1Other indoor failure–
If the unit is operating normally, the LED light on the outdoor board is lit continuously. If there is a failure, the LED light will flash a specific
number of times. Refer to the Outdoor Unit Diagnostic table above to determine failure.
43
Diagnostic
Chart
38/40MVC, MVQ
Copyright 2008 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Printed in U.S.A.Edition Date : 03/08
44
Catalog No.38--- 40MV --- 1SM
Replaces: New
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.