Carrier 40MVC, 38MVQ, 40MVQ, 38MVC User Manual

38MVC/40MVC 38MVQ/40MVQ Comfortt S e r i e s H i g h --- W a l l D u c t --- F r e e S p l i t S y s t e m Sizes 009 --- 024
Service Manual
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS 1.........................
SPECIFICATIONS -- COOLING ONLY 3..................
DIMENSIONS 5......................................
SERVICE VALVE LOCATIONS 5........................
CLEARANCES 6.....................................
SYSTEM OPERATING ENVELOPE 7....................
ELECTRICAL DATA 7................................
WIRING 8...........................................
CONNECTION DIAGRAMS 9..........................
WIRING DIAGRAMS 10 -- 16...........................
REFRIGERATION CYCLE DIAGRAM 17.................
REFRIGERANT LINES 18.............................
SYSTEM EVACUATION AND CHARGING 19.............
CONTROL SYSTEM 20...............................
SYSTEM SAFETIES 20................................
3MINUTETIMEDELAY 20............................
COMPRESSOR OVERCURRENT PROTECTION 20 -- 21....
SEQUENCE OF OPERATION 21........................
MODES OF OPERATION 22 -- 24........................
TROUBLESHOOTING 25 -- 37..........................
APPENDIX 38 -- 43...................................
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-- authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety--alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious h azards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
WARNING
!
!
INTRODUCTION
Section 1 of this Service Manual provides the necessary information to service, repair, and maintain the EEZ family of Puron air conditioners and heat pumps. Section 2 of this manual is an appendix with data required to perform troubleshooting. Use the Table of Contents to locate a desired topic.
MODEL NUMBER NOMENCLATURE
INDOOR UNIT
40 MVC 3--- 01
Fan Coil Unit
Unit Type MVC --- Co o l i n g On l y MVQ --- H e a t Pu m p
018
Nominal Capacity 009 --- 3 / 4 To n 012 --- 1 To n 018 --- 1 --- 1 / 2 To n 024 --- 2 To n s
---
Volt age
--- --- 3 0 V D C 1 --- 1 1 5 --- 1 --- 6 0 3 --- 208/230 ---1 ---60
38/40MVC, MVQ
A i r --- C o o l e d C o n d e n s e r
OUTDOOR UNIT
38 MVC 3--- 01
Unit Type MVC --- Co o l i n g On l y MVQ --- H e a t Pu m p
018
Nominal Capacity 009 --- 3 / 4 To n 012 --- 1 To n 018 --- 1 --- 1 / 2 To n 024 --- 2 To n s
---
SERIAL NUMBER NOMENCLATURE
Week of Manufacture
01 06
V
00001
Serial Number
Volt age 1--- 11 5 --- 1 --- 6 0 3--- 208/230 --- 1 ---60
Year of Manufacture
Manufacturing Site
2
STANDARD FEATURES AND ACCESSORIES
Ease Of Installation
Mounting Brackets S Low Voltage Controls S
Comfort Features
Microprocessor Controls S Wireless Remote Control S Automatic Air Sweep S Air Direction Control S Auto Restart Function S Cold Blow Protection On Heat Pumps S Turbo M o d e O n Si z e s 9K a n d 1 2 K S Auto Changeover On Heat Pumps S
Energy Saving Features
Sleep Mode S Stop/Start Timer S
Safety And Reliability
3MinuteTimeDelayForCompressor S Over Current Protection For Compressor S Indoor Coil Freeze Protection S Indoor Coil High Temperature Protection On Heat Pumps S Condenser High Temperature Protection On heat Pumps{ S Accumulator On Heat Pumps S
Ease Of Service And Maintenance
Cleanable Filters S Diagnostics S Liquid Line Pressure Taps S Suction And Discharge Pressure Taps (Sizes 18 and 24K) S
Application Flexibility
Low Ambient Controls ( --- 20˚F) A Condensate Pumps A Crankcase Heater A Wind Baffles F
Warranty
5 --- Year Compressor Warranty S 1 --- Parts Warranty S Compressor Extended Warranty Years 6 Thru 10 O All Parts And Labor Years 2 Thru 5 O All Parts And Labor Years 2 Thru 5, Compressor Years 6
Thru 10
{ Sizes 18k & 24k
Legend
SStandard A Accessory OOptional F Field Fabricated
O
INDOOR UNITS
On high wall fan coils, the condensate pump has a lift capability of 18 ft (5.5 m) or the discharge side with the pump mounted in the fan coil or 6 ft (1.8 m) on the suction side if the pump must be remote mounted. The pump mounts inside the unit with quick plug--in connections, and is recommended when adequate drain line pitch cannot be provided, or when the condensate must move up to exit.
NOTE: An external 115v power source will be required to run the pump on unit sizes 9k and 12k.
OUTDOOR UNITS
LOW AMBIENT KIT
The kit controls condenser fan cycling using a pressure switch. It is specifically designed to control fan--motor cycles in response to saturated condensing pressure. This device maintains a constant saturated condensing temperature of 100 _F ± 10 _F (37.78_C ±
--12.22 _C) at outdoor--air temperatures between 55 _F and --20 _F (12.78_C ± --12.22_C), and can be used on all outdoor units without changing the outdoor fan motor.
CRANKCASE HEATER
Available for units with rotary compressors. Heater clamps around compressor oil sump. Recommended for low-- ambient applications on sizes 9, 12 , 18, 24 and long line applications.
A07892
Fig. 1 – Condensate Pump
38/40MVC, MVQ
3
SPECIFICATIONS -- COOLING ONLY UNITS
System Model Number 5 3 M V C 0 0 9 --- --- --- 1 5 3 M V C 0 1 2 --- --- --- 1 5 3 M V C 0 1 2 --- --- --- 3 5 3 M V C 0 1 8 --- --- --- 3
System Voltage 115 V 115 V 208/230 208/230 Control Voltage 0 --- 1 2 P u l s e D C 0 --- 1 2 P u l s e D C 0 --- 1 2 P u l s e D C Pulse DC Capacity (Btuh) 9000 12000 12000 18000
System
SEER 13.0 13.0 13.0 13.0 Refrigerant Typ e R--- 410A Design Pressure (PSIG) 550 550 550 550 Metering Device Capillary Tube in Outdoor Unit Charge (lb) 2.3 2.9 3.0 4.4
Refrigerant
Type Rotary Model EA82X1C --- 1FZDU1 EA108X1C--- 1FZDU1 PA108X1C--- 3FZDU PA150X2C S--- 3KUU O i l C h a r g e ( P O E --- o z ) 11.8 11.8 11.8 25.4 Capacitor 45µF/250VAC 45µF/250VAC 35µF/370VAC 40µF/370VAC Rated Current (RLA) 7.5 9.9 5.2 7.3
Compressor
Locked Rotor Amp (LRA) 40 47 21 32.6 Rpm/CFM 900/1060 900/1090 900/1120 840/1470 Diameter (in) .. No. of Blades 15.8 … 3 15.8 … 3 15.8 … 3 18.1 … 3 Motor (hp) 0.102 0.102 0.102 0.224
Motor
Outdoor
Capacitor 6.5µF/260VAC 6.5µF/260VAC 2.5µF/450VAC 3µF/450VAC
Face A rea (sq. f t) 4.05 3.94 3.94 5.51
38/40MVC, MVQ
No. Rows 2 2 2 4
Fins per inch 17 17 17 18
Circuits 4 4 4 4
Outdoor Coil
Motor Watts/HP 20/.034 20/.034 20/.034 25/.044 Rpm/Cfm (High) 1250/325 1270/425 1270/425 1070/630 Rpm/Cfm (Medium) 1000/260 1100/365 1100/365 1000/570 Rpm/Cfm (Low) 800/190 1000/340 1000/340 960/500
Indoor Motor
Blower Diameter Length (in) 3.84 25.87 4.17 25.2 4.17 25.2 4.21 37.6 Face A rea (sq. f t) 2.15 2.54 2.54 4.36 No. Rows 2 2 2 2
Coil
Fins per inch 19.5 19.5 19.5 19.5
Indoor
Circuits 2 3 3 6 Connection Type Flare Liquid (Mix Phase) (in) OD 1/4” 1/4” 1/4” 1/4” Vapor Line (in) OD 3/8” 1/2” 1/2” 1/2” Condensate Drain (in) .65 (OD) .53 (ID) .65 (OD) .53 (ID) .65 (OD) .53 (ID) .65 (OD) .53 (ID)
Lines
Maximum Length (ft) 65 65 65 100
Refrigerant
Max Lift (Fan Coil Above) (ft) 35 35 35 50 Max Drop (Fan Coil Below) (ft) 35 35 35 50
4
SPECIFICATIONS -- HEAT PUMP UNITS
System Model Number 5 3 M V Q 0 0 9 --- --- --- 1 5 3 M V Q 0 1 2 --- --- --- 1 5 3 M V Q 0 1 2 --- --- --- 3 5 3 M V Q 0 1 8 --- --- --- 3
System Voltage 115 V 115 V 208/230 208/230 Control Voltage 0 --- 1 2 P u l s e D C 0 --- 1 2 P u l s e D C 0 --- 1 2 P u l s e D C Pulse DC Capacity (Btuh) 9000 12000 12000 18000
System
SEER 13.0 13.0 13.0 13.0 HSPF 7.7 7.7 7.7 7.7 Refrigerant Typ e R--- 410A
Design Pressure (PSIG) 550 550 550 550
Metering Device Capillary Tubes in Outdoor Unit
Charge (lb) 2.35 3.0 3.0
Refrigerant
Type Rotary Model EA82X1C --- 1FZDU1 EA108X1C--- 1FZDU1 PA108X1C--- 3FZDU PA150X2C S--- 3KUU O i l C h a r g e ( P O E --- o z ) 11.8 11.8 11.8 25.4 Capacitor 45µF/250VAC 45µF/250VAC 35µF/370VAC 40µF/370VAC Rated Current (RLA) 7.5 9.9 5.2 7.3
Compressor
Locked Rotor Amp (LRA) 40 47 21 32.6
Rpm/CFM 900/1060 900/1090 900/1120 840/1470
Diameter (in) .. No. of Blades 15.8 … 3 15.8 … 3 15.8 … 3 18.1 … 3
Motor (hp) 0.102 0.102 0.102 0.224
Capacitor 6.5µF/260VAC 6.5µF/260VAC 2.5µF/450VAC 3µF/450VAC
Outdoor Motor
Face A rea (sq. f t) 4.05 3.94 3.94 5.51
No. Rows 2 2 2 4
Fins per inch 17 17 17 18
Circuits 4 4 4 4
Outdoor Coil
Motor Watts/HP 20/.034 20/.034 20/.034 25/.044 Rpm/Cfm (High) 1250/325 1270/425 1270/425 1070/630 Rpm/Cfm (Medium) 1000/260 1100/365 1100/365 1000/570
Motor
Indoor
Rpm/Cfm (Low) 800/190 1000/340 1000/340 960/500 Blower Diameter Length (in) 3.84 25.87 4.17 25.2 4.17 25.2 4.21 37.6 Face A rea (sq. f t) 2.15 2.54 2.54 4.36 No. Rows 2 2 2 2
Coil
Fins per inch 19.5 19.5 19.5 19.5
Indoor
Circuits 2 3 3 6 Connection Type Flare Liquid (Mix Phase) (in) OD 1/4” 1/4” 1/4” 1/4” Vapor Line (in) OD 3/8” 1/2” 1/2” 1/2” Condensate Drain (in) .65 (OD) .53 (ID) .65 (OD) .53 (ID) .65 (OD) .53 (ID) .65 (OD) .53 (ID) Maximum Length (ft) 65 65 65 100
Lines
Refrigerant
Max Lift (Fan Coil Above) (ft) 35 35 35 50 Max Drop (Fan Coil Below) (ft) 35 35 35 50
38/40MVC, MVQ
5
DIMENSIONS -- INDOOR
Model Size
9K 32.09 (815) 11.02 (280) 7.68 (195) 12K 35.67 ( 906) 11.26 (286) 9.25 (235) 18K 49.21 (1250) 12.80 (325) 9.06 (230) 24K 49.21 (1250) 12.80 (325) 9.06 (230)
in. (mm)
DIMENSIONS -- OUTDOOR
A07336
W
H
in. (mm)
D
in. (mm)
Weight lb (kg)
24.2 (11)
33.0 (15)
55.0 (25)
55.0 (25)
38/40MVC, MVQ
Model Size
9K 30.71 (780) 21.26 (540) 21.61 ( 549) 11.81 (300) 10.87 (276) 12K 29.92 (760) 23.23 (590) 20.87 (530) 12.40 (315) 11.42 (290) 18K 33.07 (840) 27.36 (695) 22.05 (560) 14.17 (360) 13.19 (335) 24K 31.16 (893) 33.86 (860) 23.11 (588) 13.98 (355) 13.11 (333)
Air Flow
W
in. (mm)
SERVICE VALVE LOCATI ONS
9K
H
H
in. (mm)
L2
L3
in. (mm)
12K
L1
W
L1
35
A07337
L2
in. (mm)
18K
L3
in. (mm)
24K
Weight lb (kg)
Cooling Only
77.0 (35) 79.2 (36)
85.8 (39) 90.2 (41)
125.4 (57) 125.4 (57)
159.5 (72) 160.6 (73)
Weight lb (kg)
Heat Pumps
Service Valve Locations
J 3.46 (88) 3.19 (81) 3.46 (88) 4.02 (102) K 3.46 (88) 5.63 (143) 3.62 (92) 6.57 (167)
K
12K
in. (mm)
J
K
18K
in. (mm)
K
J
A07376a
24K
in. (mm)
J
9K
in. (mm)
J
K
6
CLEARANCES -- INDOOR
5
"
(0.13m)
min.
6" (0.15m) min.
(1.8m)
6'
Fig. 2 – Indoor unit clearance
5
"
(0.13m)
min.
A07891
CLEARANCES -- OUTDOOR
D
UNIT 9k and 12k in. (mm)
A 24 (610)
B 24 (610) C 24 (610)
D 4 (102) E 12 (305)
A
B
Fig. 3 – Outdoor Unit Clearance
38/40MVC, MVQ
Air-inlet
E
C
Air-outlet
A07894
18k and 24k in. (mm)
24 (610) 36 (914) 24 (610) 12 (305) 12 (305)
7
SYSTEM OPERATING ENVELOPE
53MVC/MVQ System Operating Envelope Chart
40
50
60
70
80
90
100
110
120
-10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140
Outdoor Temperature (ºF)
Indoor Temperature (ºF)
0
5
10
15
20
25
30
35
40
45
50
55
60
-40-35-30-25-20-15-10-5 0 5 1015202530354045505560
Outdoor Temperature (ºC)
Indoor Temperature (ºC)
Cooling
Continuous Operation
Heating Continuous Operation
85º 62ºF
55º
75ºF
55ºF
5ºF
80ºF
125º
38/40MVC, MVQ
Use low ambient control if the unit will operate in cooling at ambient conditions below 55_F (12.78_C).
Fig. 4 – System Operating Enevelope
ELECTRICAL DATA
OPERATING
UNIT
SIZE
*Permissible limits of the voltage range at which the unit will operate satisfactorily
LEGEND FLA --- Fu l l L o a d A m p s LRA --- L o c k e d R o t o r A m p s MCA - -- Minimum Circuit Amps RLA ---RatedLoadAmps
VOLTAGE*
MAX/MIN V O L T S --- P H --- H Z RLA LRA FLA HP W VOLTS FLA HP W
009
012 9.9 47 1.18 0.044 25 15 25
012
018 7.3 32.6 0.78 0.224 53
024 9.7 34.8 0.62 0.218 100 0.39 0.112 50 14 25
127/104 1 1 5 --- 1 --- 6 0
253/187 208/230---1 ---60
COMPRESSOR OUTDOOR FAN INDOOR FAN
7.5 40
5.2 21 0.38 0.116 36 35 DC 1.18 0.044 25 9 15
0.60 0.102 23 35 DC
208/230---1---60
1.1 0.034 20 12 20
0.26 0.075 31 11 20
A08180
MCA
MAX
FUSE/CB
AMP
8
WIRING
The main power is supplied to the outdoor unit. The field supplied connecting cable from the outdoor unit to indoor unit consists of four wires and provides the power for the indoor unit as well as the communication signal between the outdoor unit and indoor unit.
Voltage drop on the connecting cable should be kept to a minimum. Use cable size and max length below:
18 AWG 50 ft. (16 m) 16 AWG 100 ft. (33 m)
CONNECTION DIAGRAMS
CONNECTING CABLE
CONTROL
CONNECTING CABLE
CONNECTING CABLE
CONTROL
38/40MVC, MVQ
Notes:
1. Do not use thermostat wire for any connection between indoor and outdoor units.
2. All connections between indoor and outdoor units must be as shown. The connections are sensitive to polarity.
3. On the 18k and 24k units, the “S” terminal “CONTROL” output is pulse DC with a potential AC voltage shock hazard.
Fig. 5 – Connection Diagrams
9
A07654
38/40MVC, MVQ
Fig. 6 – Wiring Diagram 38MVC009------ 1 W/ 40MVC009-- -- --1
WIRING DIAGRAMS
10
38/40MVC, MVQ
Fig. 7 – Wiring Diagram 38MVC012------ 1 W/ 40MVC012-- -- --1
WIRING DIAGRAMS (CONT.)
11
38/40MVC, MVQ
Fig. 8 – Wiring Diagram 38MVC012------ 3 W/ 40MVC012-- -- --3
WIRING DIAGRAMS (CONT.)
12
38/40MVC, MVQ
Fig. 9 – Wiring Diagram 38MVC018------ 3 W/ 40MVC018-- -- --3
WIRING DIAGRAMS (CONT.)
13
38/40MVC, MVQ
Fig. 10 – Wiring Diagram 38MVQ009------ 1 W/ 40MVQ009-- -- --1
WIRING DIAGRAMS (CONT.)
14
38/40MVC, MVQ
Fig. 11 – Wiring Diagram 38MVQ012-- -- --1 W/ 40MVQ012-- ----1
WIRING DIAGRAMS (CONT.)
15
38/40MVC, MVQ
Fig. 12 – Wiring Diagram 38MVQ012------ 3 W/ 40MVQ012-- -- --3
WIRING DIAGRAMS (CONT.)
16
REFRIGERATION CYCLE DIAGRAM
FIELD
PIPING
FLARE CONNECTION
TWO PHASE LIQUID LINE
SERVICE VALVE
CAPILLARY TUBE
HEAT EXCHANGER (EVAPORATOR)
FLARE CONNECTION
INDOOR UNIT OUTDOOR UNIT
FLARE CONNECTION
SERVICE VALVE W/GUAGE PORT
SUCTION LINE
FIELD
PIPING
Fig. 13 – Cooling
LIQUID HTG
SERVICE VALVE
COMPRESSOR
CHECK VALVE
(HEATING MODEL ONLY)
CAPILLARY TUBE
HEAT EXCHANGER (CONDENSER)
38/40MVC, MVQ
A08104
TWO PHASE
LIQUID
HEAT EXCHANGER (EVAPORATOR)
FLARE CONNECTION
SERVICE VALVE W/ GUAGE PORT
ACCUMULATOR
FIELD
PIPING
Fig. 14 – Heat Pumps
SUCTION
SUCTION DISCHARGE
COMPRESSOR
HEAT EXCHANGER (CONDENSER)
REVERSING
VALVE
(HEAT PUMP ONLY)
COOLING HEATING
A08105
17
REFRIGERANT LINES
General refrigerant line sizing:
1. The 38MVC/MVQ units are shipped with a full charge of R410A refrigerant. All charges, line sizing, and capacities are based on runs of 25 ft (7.6 m). For runs over 25 ft (7.6 m), consult long--line section on this page for proper charge adjustments.
2. Minimum refrigerant line length between the indoor and outdoor units is 10 ft. (3 m).
3. Refrigerant lines should not be buried in the ground. If it is necessary to bury the lines, not more than 36--in (914 mm) should be buried. Provide a minimum 6--in (152 mm) vertical rise to the service valves to prevent refrigerant migration.
4. Both lines must be insulated. Use a minimum of 1/2--in. (12.7 mm) thick insulation. Closed-- cell insulation is recommended in all long--line applications.
5. Special consideration should be given to isolating interconnecting tubing from the building structure. Isolate the tubing so that vibration or noise is not transmitted into the structure.
S The following maximum lengths are allowed:
38/40MVC, MVQ
Unit Size
S The following are the piping sizes.
Refrigerant Charge
S Above charge is for piping runs up to 25 ft. (7.6 m). S For piping runs greater than 25 ft. (7.6 m), add 0.1 oz. of
refrigerant per foot of extra piping up to the allowable length.
REFRIGERANT LINE LENGTHS ft. (m)
Max Line
Length
Max Elevation
(ID over OD)
9K 65 (20) 35 (11) 35 (11) 12K 65 (20) 35 (11) 35 (11) 18K 100 (30) 50 (15) 50 (15) 24K 100 (30) 60 (18) 60 (18)
PIPE SIZES
Unit Size Mix Phase Vapor
9K 1/4” 3/8” 12K 1/4” 1/2” 18K 1/4” 1/2” 24K 3/8” 5/8”
REFRIGERANT CHARGE lb. (kg)
Unit Size Air Conditioner
Heat Pump
9K 2.3 (1.0) 2.4 (1.1) 12K 2.9 (1.3) 3.0 (1.4) 18K 4.4 (2.0) TBD 24K TBD TBD
Max Elevation
(OD over ID)
Long Line Applications, 38MVC
Units:
1. A crankcase heater should be added for line lengths longer than 25 ft (7.62 m) to prevent the migration of refrigerant to the compressor during the “OFF” cycle.
2. A field fabricated wind baffle is recommended.
3. No change in line sizing is required.
4. Add refrigerant per table below.
ADDITIONAL CHARGE TABLE
Unit Size
9K cool only
9K
hp
12K cool only
12K
hp
18K cool only
Tot a l
Line Length,
ft
Min. Max.
65
10
100
10 --- 25 ft
(3.05 --- 7.62m)
Additional Charge, oz.
none
> 2 5 --- 6 5 f t
(7.62 ---19.81m)
0.1 oz per foot
> 6 5 --- 1 0 0 f t
(19.81 ---30.48m)
0.1 oz. per foot
5. Reduction in capacity due to long lines can be calculated from the chart below.
CAPACITY LOSS
Capacity,%Loss
Line Length, ft
Cooling: 25 45 65 100
9&12KBTU/Hmodels 0% 2% 5% 18 & 24 KBTU/H models 0% 2% 4% 7%
Heating:
9&12KBTU/Hmodels 0% 7% 11% 18 & 24 KBTU/H models 0% 7% 11% 15%
18
SYSTEM EVACUATION AND
t
CHARGING
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used if the procedure outlined below is followed. Always break a vacuum with dry nitrogen.
SYSTEM VACUUM AND CHARGE
Using Vacuum Pump
1. Completely tighten flare nuts A, B, C, D, connect manifold gage charge hose to a charge port of the low side service valve. (See Fig. 15.)
2. Connect charge hose to vacuum pump.
3. Fully open the low side of manifold gage. (See Fig. 16)
4. Start vacuum pump
5. Evacuate using either deep vacuum or triple evacuation method.
6. After evacuation is complete, fully close the low side of manifold gage and stop operation of vacuum pump.
7. The factory charge contained in the outdoor unit is good for up to 25 ft. (8 m) of line length. For refrigerant lines longer than 25 ft (8 m), add 0.1 oz. per foot of extra piping up to the maximum allowable length.
8. Disconnect charge hose from charge connection of the low side service valve.
9. Fully open service valves B and A.
10. Securely tighten caps of service valves.
Outdoor Unit
Service Valve
CAUTION
Refrigerant
Low Side
A
High Side
B
Fig. 15 – Service Valve
Manifold Gage
Indoor Uni
C
D
A07360
Deep Vacuum
Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water. (See Fig. 17)
5000 4500 4000 3500 3000 2500 2000
MICRONS
1500 1000
500
01234567
MINUTES
LEAK IN SYSTEM
VACUUM TIGHT TOO WET
TIGHT DRY SYSTEM
A95424
Fig. 17 – Deep Vacuum Graph
Triple Evacuation
Method
The triple evacuation method should only be used when vacuum pump is only capable of pumping down to 28 in. of mercury vacuum and system does not contain any liquid water. Refer to Fig. 18 and proceed as follows:
1. Pump system down to 28 in. of mercury and allow pump to continue operating for an additional 15 minutes.
2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and open until system pressure is 2 psig.
4. Close service valve and allo w system to stand for 1 hr. Dur­ing this time, dry nitrogen will be able to diffuse throughout the system absorbing moisture.
5. Repeat this procedure as indicated in Fig. 18. System will then be free of any contaminants and water vapor.
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
38/40MVC, MVQ
500 microns
Low side valve
Charge hose
Low side valve
High side valve
Charge hose
Fig. 16 – Manifold
Vacuum pump
A07361
CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS DEEP VACUUM)
RELEASE CHARGE INTO SYSTEM
A95425
Fig. 18 – Triple Evacuation Method
Final Tubing
Check
IMPORTANT: Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.
19
CONTROL SYSTEM
The 40MVC/MVQ unit is equipped with a microprocessor control to perform two functions:
1. Provide safety for the system
2. Control the system and provide optimum levels of comfort and efficiency
The main microprocessor is located on the control board of the fan coil unit (outdoor units have a microprocessor too) with thermistors located in the fan coil air inlet and on the indoor coil. Heat pump units have a thermistor on the outdoor coil. These thermistors monitor the system operation to maintain the unit within acceptable parameters and control the operating mode.
SYSTEM SAFETIES
Safety
3MinTimeDelay X X X X X X X X
Over Current Protection On Compressor X X X X X X X X
Indoor Coil Freeze Protection X X X X X X X X
Condenser High Temperature Protection X X X X
Indoor Evaporator High Temperature X X X X
9K 012K 018K 024K 09K 012K 018K 024K
Cooling Only Heat Pump
3MINUTETIMEDELAY
In order to protect the compressor, there is a 3 minute delay on break even if the control is calling for heating or cooling.
38/40MVC, MVQ
COMPRESSOR OVERCURRENT PROTECTION
Overcurrent protection can result due to any of the following:
S The ambient temperature is to high S Locked rotor on the compressor S Blockage in refrigeration circuit (cap tubes, for example)
S Outdoor air is blocked or restricted
The compressor current is monitored continuously and protection is provided as shown below:
3 sec
5 min
1 sec
Normal
Current down
Indoor fan: On compressor: On outdoor fan: On
Compressor off (after 5 minutes)
Outdoor fan
off (heating) Indoor fan low speed (cooling)
Compressor off (after 3 seconds)
Current up
A08117
Fig. 19 – Compressor Overcurrent Protection
If the compressor is stopped 4 times at the 5 minute limit or 1 time at the 3 second limit, the system will be locked off and the main power will have to be reset before the system can be restarted.
Time Limit
3SEC 14 A 18 A 11 A 14 A 23 A 5MIN 12 A 16A 9A 12 A 21 A
ISEC 10.5 A 14 A 7A 11 A 18 A
NORMAL 9A 12.5 A 6A 10 A 16 A
38MVC(Q)009---1 38MVC(Q)012--- 1 38MVC(Q)012--- 3 38MVC(Q)018---3 38MVC(Q)024--- 3
Compressor Current
20
Indoor Coil Freeze
Protection
The indoor coil can freeze due to any of the following:
S Low system charge S Reduced indoor airflow S Restricted refrigerant flow S Low ambient temperature (outdoor) S Low load (indoor)
In cooling mode, the thermistor located on a return bend of the indoor coil monitors the coil temperature continuously. Any time the coil temperature drops below the TE5 limit for five consecutive minutes, the compressor and outdoor fan will be switched off until the coil temperature rises above the TE6 as shown below:
Compressor and
outdorr fan on
EVAP temp. down
Compressor and outdoor
fan off (after 5 mins)
TE5 TE6
EVAP temp. up
T
(Evap Temp.)
A08118
Fig. 20 – Indoor Coil Freeze Protection
Parameter
TE5 39 (4) 41 (5) 36 (2) 36 (2) TE6 50 (10) 54 (12) 54 (12) 54 (12)
40MVC(Q)
009--- 1
Coil Temperature ˚F(˚C)
40MVC(Q)
012--- 1
40MVC(Q)
018--- 3
40MVC(Q)
024--- 3
Condenser High Temperature Protection
Condenser high temperature can occur due to any of the following conditions:
S High outdoor ambient S Outdoor fan blocked S Outdoor coil blocked
The outdoor coil thermistor on a heat pump unit continuously monitors the temperature of the outdoor coil. Anytime the coil temperature exceeds the TE10 limit, the compressor is switched off and the outdoor fan continues running to reduce the coil temperature. When the coil temperature drops below the TE11 limit, the compressor is switched back on as shown below:
Compressor off Outdoor fan on
COND temp. down
Compressor on Outdoor fan on
TE11 TE10 T
COND temp. up
A08119
Fig. 21 – Condenser High Temp Protection
Condenser Temp.
Parameter
38MVQ018 --- 3 38MVQ024--- 3 TE10 149 (63) 158 (70) TE11 131 (55) 149 (65)
˚F(˚C)
Indoor High Temperature Protection
High indoor coil temperature (in heating mode) can occur due to any of the following:
S High outdoor ambient temperature S Indoor fan blocked S Indoor coil blocked (including dirty filters)
The indoor coil thermistor on a heat pump unit continuously monitors the temperature of the indoor coil during heating operation. Anytime the coil temperate exceeds the TE8 limit, the outdoor fan is switched off. If the coil temperature continues to climb and exceeds the TE7 limit, the compressor is switched off. When the coil temperature drops below the TE9 limit, the compressor and outdoor fan are switched back on as shown below:
Compressor off
Fan off
Compressor on
Fan off
T temp. down
Compressor on
Fan on
TE9 TE8 TE7 T
T temp. up
A08120
Fig. 22 – Indoor High Temperature Protection
Condenser Coil Temp.
Parameter
TE7 140 (60) 140 (60) 145 (63) 145 (63) TE8 129 (54) 129 (54) 129 (54) 129 (54) TE9 118 (48) 118 (48) 122 (50) 122 (50)
40MVQ
009--- 1
40MVQ
012--- 1
˚F(˚C)
40MVQ
018--- 3
40MVQ
024--- 3
SEQUENCE OF OPERATION
Interface
A wireless remote control, supplied with the unit, is the interface between the fan coil and the user. The wireless remote control has the following characteristics:
S Capable of displaying _Cand_F with _C being the default
setting. To change the default setting, refer to the Owner’s Manual or push the recessed F/C button once using a paper clip or similar object*.
S The remote control setpoint range is from 62_F(17_C) to
88_F(30_C) in increments of 2_F(1_C).
S There is a dedicated cooling only and heat pump remote
control.
S The wireless remote control has an operating range of 25 ft.
(7.62 m).
S The same remote control can be used to control more than one
unit.
S If the remote control is lost, damaged, or the batteries are
exhausted, the system can be operated by using the manual button (forced Auto) located under the front panel.
38/40MVC, MVQ
Manual button
Fig. 23 – Manual Button Location on Unit
* On units produced during week 12 (2008) and later. Units
produced before week 12 have dedicated _Cor_F controls.
21
A07364
MODES OF OPERATION
The units have 5 main operating modes:
1. Fan Only
2. Cooling
3. Heating (heat pumps only)
4. Auto
5. Dehumidification (Dry)
The units have 2 other modes (manual operation) that are operated in unique situations:
1. Auto Forced Mode (Emergency)
2. Test Mode
Fan Mode
In this mode, the system circulates the room air without changing the room air temperature.
Cooling
In this mode, the system cools and dries the room air with the fan running continuously, either at a selected fan speed or Auto fan speed. The fan runs even when the compressor cycles off. This feature enhances room comfort and efficiency of the system.
When the unit is operating in cooling, two sub modes can also be selected:
38/40MVC, MVQ
Compressor and Outdoor Fan
The compressor and outdoor fan motor cycle on and off based on the conditions of the set point and the room temperature as shown below. There is no minimum run time.
Indoor Fan
When in cooling mode, the fan runs continuously either at the chosen set speed , or in Auto mode, where the speed is determined by the microprocessor based on the difference between the room temperature and the temperature set point as shown below:
Room temp. down
Only
Mode
1. Sleep Mode is an energy saving feature that changes the set point automatically.
2. Turbo Mode is a comfort feature on the 9k and 12k units where the set point is reached quickly by having the fan run on high speed regardless of the speed that has been selected.
Operation
Compressor and
outdoor fan on
Room temp. down
T = Room Temperature Ts = Set Point Temperature
Compressor off
fan off
0 1.8°FT-Ts
Room temp. up
Fig. 24 – Compressor and Outdoor Fan -- Cooling Mode
Operation
Med fan
Room temp. up
High fan
A08106
Sleep
Mode
When in cooling mode, additional energy savings can be realized by selecting the Sleep setting. When the Sleep setting is selected, the temperature set point is adjusted automatically as shown below:
Set point
1.8
°
F
°
F
1.8
Time (hour)12
A08108
Fig. 26 – Sleep Mode
The unit will shut off 7 hours after the Sleep Mode is selected.
Mode
Turbo
When in cooling mode, selecting Turbo will allow the indoor unit to satisfy the temperature set point as quickly as possible. In Turbo Mode, the indoor fan will shift to high speed and either run continuously for 20 minutes or until the user pushes the Turbo button again, at which point the fan speed will return to the original setting.
Heating
Mode
In this mode, the system heats the room air with the indoor fan running at either the selected speed or on Auto. As in the cooling mode, the indoor fan will run continuously unless interrupted by the cold blow algorithm. This algorithm will not allow the fan to run if the indoor coil temperature drops below a preset value.
The sleep function can be selected while the unit is running in the Heating Mode. Defrost is controlled by the on --board microprocessor.
Compressor and Fan
Operation
The compressor and outdoor fan cycle on and off based on the actual room temperature versus the set point as shown below. When the compressor starts, it will run continuously for 7 minutes even if the set point condition is satisfied.
The 4--way value is energized in heating and will stay energized for 2 minutes after the mode is changed into a non--heating mode.
Compressor on outdoor fan off
Room temp. down
T = Room Temperature TS = Set Point Temperature * For 9k & 12k Units Only. For 18k and 24k units, numbers will be 5.4 and 7.2 respectively.
Compressor off outdoor fan on
Ts+5.4*Ts+3.6*Ts T
Room temp. up
A08109
Fig. 27 – Compressor and Outdoor Fan -- Heating Mode
Low fan
T= Room Temperature Ts = Set Point Temperature
Fig. 25 – Auto Fan -- Cooling Mode
9.0 °F7.2 °F1.8 °F T-Ts
A08107
22
Fan
Auto
When the fan speed is set to Auto, the fan will run at either the medium or low speed based on the difference between the room temperature and the set point temperature as shown below:
Low. Speed
Room temp. down
T = Room Temperature Ts = Set Point Temperature
Med. Speed
0
3.6°F
Room temp. up
T-Ts
A08112
Fig. 28 – Auto Fan -- Heating Mode
Manual Indoor
Fan
The indoor fan will run continuously in heating at the set fan speed (even if the compressor cycles off) unless the indoor coil temperature begins to drop. When the coil temperature drops to the TE3 limit, the 18k and 24k unit indoor fan switches to low speed. On the 9k and 12k unit the indoor fan switches to ultra low speed. When the coil temperature drops to the TE4 limit, the indoor fan on all systems shuts off to prevent cold blow as shown below. The cold blow algorithm also applies to the auto fan setting.
Set fan speed
Low Speed / Ultra Low Speed
T temp. down
Fan o ff
TE4 TE1 TE3 TE2 T
T temp. up
(Coil temp.)
A08111
Fig. 29 – Manual Indoor Fan -- Heating Mode
Parameter
TE1 88 (31) 88 (31) 77 (25) 82 (28) TE2 93 (34) 91 (33) 90 (32) 93 (34) TE3 86 (30) 81 (27) 86 (30) 90 (32) TE4 72 (22) 68 (20) 68 (20) 75 (24)
40MVQ
009--- 1
Indoor Coil Temperature ˚F(˚C)
40MVQ
012--- 1
40MVQ
018--- 3
40MVQ
024--- 3
Sleep Mode
When in heating mode additional energy savings can be realized by selecting the Sleep setting. When the Sleep setting is selected, the temperature set point is adjusted automatically as shown below:
Set Point
Defrost
Defrost on heat pump units is controlled by the microprocessor and is initiated if either of the following conditions occur:
1. The outdoor coil temperature is lower than 32_F(0_C) for
more than 40 minutes and during that period, the coil temperature is continuously lower than 26.6_F(--3_C) for 3 minutes.
2. If the first condition does not occur within 90 minutes of termination of the last defrost cycle.
The defrost cycle will terminate 10 minutes after initiation or when the coil temperature reaches 68_F(20_C). At the end of the Defrost cycle the timer resets automatically.
The cycles of defrost algorithm are shown below:
Defrost 10 or 6 minutes
10s
On
Off
5s
25s
2s
A08114
Compressor
4-way valve
Outdoor fan
Indoor fan
Fig. 31 – Defrost Cycle
Mode
Auto
When the Auto setting is selected, the microprocessor looks at the difference between the room temperature (T) and the set point (TS). The algorithm determines which mode the unit will run in as shown below:
Heating (fan only in cooling) Fan only Cooling
°
F 3.6°F
-1.8
T-TS
A08115
Fig.32–AutoMode
When the unit shifts modes, it will remain in that mode for at least 15 minutes while the algorithm ignores the difference between T and TS. This ensures that the unit cannot change modes too frequently.
38/40MVC, MVQ
1.8ºF
1.8ºF
Time (hour)12
Fig. 30 – Sleep Mode -- Heating
The unit will shut off 7 hours after the Sleep mode is selected.
A08110
23
Dry (Dehumidification)
Mode
When more humidity control is desired, the Dry setting can be selected. Lower humidity is achieved when the microprocessor adjusts the indoor fan speed and compressor cycling by comparing the room temperature (T) and the set point temperature (TS).
There are two different control algorithms: Size 9k and 12 k
units:
T = TS + 3.6 -- the compressor will run for 6 minutes and the indoor fan will run at low speed. The compressor will be off for 4 minutes and the indoor fan will run in ultra low speed.
TS = T < TS + 3.6 -- The compressor will run for 5 minutes and the indoor fan will run at low speed. The compressor will be off for 5 minutes and the indoor fan will run in ultra low speed.
T < TS -- The compressor will run for 4 minutes and the indoor fan will run at low speed. The compressor will be off for 6 minutes and the indoor fan will run in ultra low speed.
Size 18k and 24k
units:
These units do not have ultra low speed. When set for dehumidification, the indoor fan runs at low speed and the compressor cycles based on the difference between T and TS.
Manual Operation
The unit can be set for Forced Auto or Forced Cooling manually by pushing the Manual button once or twice as shown below:
38/40MVC, MVQ
Push 3 Times
Remote
mode
Push Once Push Twice
Forced
auto
Forced
cooling
Forced Auto (Emergency
Operation)
Forced Auto option allows operation of the unit if the remote control is lost or the batteries have expired. When the system is in Forced Auto, it will run with a default set point of 75.2_F. While in Forced Auto, the system will respond to signals from the remote control.
Forced Cooling
Operation
This option is used for diagnostic purposes. The system is forced to run in cooling for 30 minutes.
After 30 minutes, the 9k and 12k systems will switch to Dry mode with a default set point of 75.2_F. The 18k and 24k systems will switch to Forced Auto mode. When the system is in Forced Cooling mode, it will not respond to signals from the remote control. The only way to exit the Forced Cooling mode is to push the manual button once to switch the system to remote control mode.
Fig. 33 – Manual Operation
A08116
24
TROUBLESHOOTING
This section provides the required flow charts to troubleshoot problems that may arise.
NOTE: Information required in the diagnoses can be found either on the wiring diagrams or in the appendix.
Required
Tools:
The following tools are needed when diagnosing the units:
S Digital multimeter S Screw drivers (Phillips and straight head) S Needle--nose pliers
Recommended
Steps
1. Refer to the diagnostic hierarchy chart below and determine the problem at hand.
2. Go to the chart listed in the diagnostic hierarchy and follow the steps in the chart for the selected problem.
DIAGNOSTIC HIERARCHY
Unit has a problem
Unit has a problem
Unit displays a
Unit displays a diagnostic code
diagnostic code
Unit not running and
Unit not running and no diagnostic code
no diagnostic code
Unit running but not
Unit running but not
optimally
optimally
38/40MVC, MVQ
Refer to page ---
Refer to page A8 & A9 identify error code*
appropriate diagnostic chart
* For EEROM error, replace the indoor microprocessor board
* For EEROM error, replace the indoor microprocessor board
and use
Go to chart # 7 Go to chart # 8 & 9
Go to chart Go to chart #
For the ease of service, the systems are equipped with diagnostic code display LED’s on both the indoor and outdoor units. The outdoor diagnostic display is an LED on the outdoor unit board and is limited to very few errors. However, it is useful in identifying special error codes like a failure of the outdoor coil sensor on heat pumps. The indoor diagnostic display is a combination of flashing LED’s on the display panel on the front of the unit. If possible always check the diagnostic codes displayed on the indoor unit first.
The diagnostic codes for the indoor and outdoor units are listed in appendix A8 and A9.
Problems may occur that are not covered by a diagnostic code, but are covered by the diagnostic flow charts starting with the diagnostic hierarchy. These problems will be typical air conditioning mechanical or electrical issues that can be corrected using standard air conditioning repair techniques.
A08165
For problems requiring measurements at the control boards please
note the following:
1. Always disconnect the main power.
2. When possible check the outdoor board first.
3. Start by removing the outdoor unit top cover.
4. Reconnect the main power
5. Probe the outdoor board inputs and outputs with a digital multi--meter referring to the wiring diagrams and input/output charts found in the appendix.
6. Connect the red probe to hot signal and the black probe to the ground or negative.
7. Note that some of the DC voltage signals are pulse will give continuously variable readings.
8. If it is necessary to check the indoor unit board you must start by disconnecting the main power.
9. Next remove the front cover of the unit and then control box cover.
10. Carefully remove the indoor board from the control box, place it face up on a plastic surface (not metal).
11. Reconnect the main power and repeat steps 5,6, and 7.
12. Disconnect main power before reinstalling board to avoid shock hazard and board damage.
25
CHART 1 -- I NDOOR FAN SPEED OUT OF CONTROL
Reset main power and
Reset main power and
restart system using remote.
restart system using remote.
Problem persists?
Problem persists?
Yes
Yes
Check motor connection.
Check motor connection.
Connection good?
Connection good?
Yes
Yes
No
No
No
No
No further action is
No further action is
required
required
Fix connection
Fix connection
38/40MVC, MVQ
Check IFM output and input
on indoor board.
Values good?
Yes
Yes
Replace indoor fan motor
Replace indoor fan motor
No
No
Replace indoor board
Replace indoor board
A08166
26
CHART 2 -- TEMPERATURE SENSOR
Reset main power and
restart system using remote.
Problem persists?
Yes
Yes
Check sensor connector
at ID or OD board
Connection good?
Yes
Yes
Check input and output
on indoor or outdoor board.
Yes
Yes
Check sensor resistance.
Appendix 6
YesYes
No
No
No
No
No
No
No
No
No further action is
required
Fix connection
Replace board
38/40MVC, MVQ
Replace sensor
Double check connection,
for corrosion or high
resistance.
A08167
27
CHART 3 -- COMPRESSOR OVERCURRENT PROTECTION
Is unit running in outdoor
Is unit running in outdoor ambient higher than
ambient higher than 125 °F?
125 °F?
No
No
Outdoor coil clean?
Outdoor coil clean?
Yes
Yes
Check connections from
Check connections from OD board. Corrosion, or
OD board. Corrosion, or high resistance
high resistance
No
No
Outdoor fan Ok?
Outdoor fan Ok?
Yes
Yes
Yes
Yes
Beyond operating range
Beyond operating range
No No
No No
No
No
Clean coil.
Clean coil.
Problem persists?
Problem persists?
Yes
Yes
Clean/repair connection
Clean/repair connection
Problem persists?
Problem persists?
Yes
Yes
Change outdoor motor
Change outdoor motor
No
No
Problem solved
Problem solved
Problem solved
Problem solved
38/40MVC, MVQ
Replace compressor
Replace compressor
Connect gauges to unit.
Connect gauges to unit.
pressures ok?
pressures ok?
Yes
Yes
Check amp draw to
Check amp draw to
No
No
compressor? Values within
compressor? Values within range?
range?
Yes
Yes
Replace outdoor board
Replace outdoor board
No
No
High head, high suction? High head, low suction?
High head, high suction? High head, low suction?
Yes
Yes
Unit is overcharged.
Unit is overcharged.
Reclaim charge and weigh
Reclaim charge and weigh
in correct charge.
in correct charge.
No
No
Yes
Yes
Restriction in refrigeration
Restriction in refrigeration
circuit.
circuit.
A08168
28
CHART 4 -- INDOOR UNIT COMMUNICATION ERROR SIZ E 9K AND 12K
Notes:
Check the wires and
Check the wires and connections between
connections between Indoor and outdoor units*
Indoor and outdoor units*
Yes
Yes
Reset main power and
Reset main power and
restart system using remote.
restart system using remote.
Problem persists?
Problem persists?
Yes
Yes
Measure Volts DC on
Measure Volts DC on outdoor TB between 1 & 3.
outdoor TB between 1 & 3.
Ok?**
Ok?**
No
No
No
No
Yes
Yes
Fix connection or
Fix connection or
replace wiring
replace wiring
No further action is
No further action is
required
required
Measure Volts DC on
Measure Volts DC on indoor TB between 1 & 3.
indoor TB between 1 & 3.
Ok?**
Ok?**
Notes:
Before measuring the Volts DC on outdoor TB,
Before measuring the Volts DC on outdoor TB, disconnect the field wire on terminal 1.
disconnect the field wire on terminal 1.
Before measuring the Volts DC on Indoor TB,
Before measuring the Volts DC on Indoor TB, disconnect the field wire on terminal 1.
Have the red probe of the meter on terminal 1 and the black probe on terminal 3. Reconnect wiring when measurements are complete.
Recheck wiring and
Recheck wiring and
connections
connections
No
No
.
Replace outdoor board.
Replace outdoor board.
* Make sure wires are connected per connection diagrams. Failing to do that will result in a communication error.
** There is a 2 to 3 minute window to take the measurement before the diagnostic light is on again.
** There is a 2 to 3 minute window to take the measurement before the diagnostic light is on again.
.
Replace indoor board.
Replace indoor board.
No
No
38/40MVC, MVQ
A08181
29
Outdoor coil clean?
Outdoor coil clean?
CHART 5 -- OUTDOOR UNIT PROTECTS
Clean coil. Problem
No No
Clean coil. Problem
No No
persists?
persists?
Problem solved
Problem solved
Yes
Yes
Check outdoor unit
Check outdoor unit board. Indicator light
board. Indicator light flashing twice?
flashing twice?
No
No
Connect gauges to
Connect gauges to unit. Pressures ok?
unit. Pressures ok?
No
No
Suction and head
Suction and head
equal?
38/40MVC, MVQ
equal?
Yes
Yes
Check compressor
Check compressor
* Restriction in system. Check capillary tube, check for moisture, and check for damage to liquid line between indoor and
* Restriction in system. Check capillary tube, check for moisture, and check for damage to liquid line between indoor and
outdoor units.
outdoor units.
Yes
Yes
Yes
Yes
No No No
No No No
Check sensors.
Check sensors.
Flow Chart #2
Flow Chart #2
Check application
Check application
Normal suction,
Normal suction,
Non condensables
Non condensables in sys. Pump down
in sys. Pump down and recharge unit
and recharge unit
Yes
Yes
limits
limits
high head?
high head?
Yes Yes
Yes Yes
Unit is overcharged.
Unit is overcharged. Reclaim charge and
Reclaim charge and weigh in correct charge
weigh in correct charge
High head, high
High head, high
suction?
suction?
High head, low
High head, low
suction?
suction?
Yes
Yes
See note below
See note below
*
*
A08182
30
CHART 6 -- INDOOR UNIT COMMUNICATION ERROR SIZE 18K AND 24K
Check the wires and
Check the wires and
Check the wires and connections between
connections between
connections between Indoor and outdoor units*
Indoor and outdoor units*
Indoor and outdoor units*
Yes
Yes
Yes
Reset main power and
Reset main power and
Reset main power and
restart system using remote.
restart system using remote.
restart system using remote.
Problem persists?
Problem persists?
Problem persists?
Yes
Yes
Yes
Measure VDC reading on
Measure VDC reading on
Measure VDC reading on outdoor between S and G.
outdoor between S and G.
outdoor between S and G. Reading positive? **
Reading positive? **
Reading positive? **
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
Fix connection or
Fix connection or
Fix connection or
replace wiring
replace wiring
replace wiring
No further action is
No further action is
No further action is
required
required
required
Replace outdoor board
Replace outdoor board
Replace outdoor board
Notes:
Notes:
Notes:
When unit is operating normally and a DC
When unit is operating normally and a DC
When unit is operating normally and a DC voltage reading is taken between the S and
voltage reading is taken between the S and
voltage reading is taken between the S and G terminal on the outdoor unit (or indoor
G terminal on the outdoor unit (or indoor
G terminal on the outdoor unit (or indoor unit) positive and negative readings will
unit) positive and negative readings will
unit) positive and negative readings will fluctuate between 0 and 24V DC.
fluctuate between 0 and 24V DC.
fluctuate between 0 and 24V DC.
If indoor board is bad, only a positive
If indoor board is bad, only a positive
If indoor board is bad, only a positive readings will be registered between
readings will be registered between
readings will be registered between terminals S and G on the outdoor unit. The
terminals S and G on the outdoor unit. The
terminals S and G on the outdoor unit. The reverse will apply if outdoor board is bad
reverse will apply if outdoor board is bad
reverse will apply if outdoor board is bad (only negative readings will register).
(only negative readings will register).
(only negative readings will register).
Above data is obtained by having the red
Above data is obtained by having the red
Above data is obtained by having the red probe of the meter on the S terminal and
probe of the meter on the S terminal and
probe of the meter on the S terminal and the black probe on the G terminal.
the black probe on the G terminal.
the black probe on the G terminal.
.
.
Replace indoor board.
Replace indoor board.
Replace indoor board.
* Make sure wires are connected per connection diagrams i.e. L1 to L1 and L2 to L2. Failing to do that will result in a
* Make sure wires are connected per connection diagrams i.e. L1 to L1 and L2 to L2. Failing to do that will result in a
communication error.
communication error.
** There is a 2 to 3 minute window to take measurements before the diagnostic light is on again.
** There is a 2 to 3 minute window to take measurements before the diagnostic light is on again.
.
A08183
38/40MVC, MVQ
31
Reset circuit breaker. Is unit
Reset circuit breaker. Is unit
38/40MVC, MVQ
running?
running?
Problem solved
Problem solved
CHART 7 -- UNIT NOT RUNNING, NO DIAGNOSTIC CODE
Use auto forced function.
Use auto forced function. Unit runs?
Unit runs?
Yes
Yes
Reset remote and restart
Reset remote and restart the unit. Is unit running?
the unit. Is unit running?
Yes Yes
Yes Yes
Problem solved
Problem solved
Is there power to outdoor
Is there power to outdoor unit?
unit?
Yes
Yes
Check fuse on outdoor
Check fuse on outdoor
board. Ok?
board. Ok?
Yes
Yes
Check input and output on
Check input and output on
outdoor board. Ok?
outdoor board. Ok?
Yes
Yes
Check components. Ok?
Check components. Ok? Flow charts 10 thru 12
Flow charts 10 thru 12
No
No
Replace defective
Replace defective
component
component
No No
No No
No
No
No
No
Yes
Yes
Check batteries. OK? Replace battery
Check batteries. OK? Replace battery
Go to chart #13
Check wiring and circuit
Check wiring and circuit
breaker and fix
breaker and fix
Replace fuse
Replace fuse
Replace outdoor board
Replace outdoor board
Check fuse(s) on indoor
Check fuse(s) on indoor
board. Ok?*
board. Ok?*
No
No
Replace fuse
Replace fuse
Yes
Yes
Replace indoor board
Replace indoor board
Check input and output on
Check input and output on
indoor board. Ok?
indoor board. Ok?
Determine defective
Determine defective
component and replace
component and replace
Yes
Yes
No
No
No No
No No
No
No
* For sizes 18 and 24 K units only. For sizes 9 and 12K units proceed to check inputs and outputs on indoor boards.
* For sizes 18 and 24 K units only. For sizes 9 and 12K units proceed to check inputs and outputs on indoor boards.
A08169
32
Outdoor coil clean?
Outdoor coil clean?
CHART 8 -- UNIT NOT RUNNING OPTIMALLY
No No
No No
Clean coil. Problem
Clean coil. Problem
persists?
persists?
Problem solved
Problem solved
Yes
Yes
Indoor filter clean?
Indoor filter clean?
Yes
Yes
Check indoor fan
Check indoor fan
motor
motor
Yes
Yes
Connect gauges to
Connect gauges to unit. Pressures ok?
unit. Pressures ok?
No
No
Suction and head
Suction and head
equal?
equal?
Yes
Yes
Check compressor
Check compressor
Yes
Yes
Clean filter. Problem
No No
Clean filter. Problem
No No
persists?
persists?
Yes
Yes
No
No
Replace indoor fan
Replace indoor fan
motor.
motor.
Yes
Yes
Check application
Check application limits.
limits.
No No No
No No No
Normal suction,
Normal suction,
high head?
high head?
Yes Yes
Yes Yes
Non condensables
Non condensables in sys. Pump down
in sys. Pump down and recharge unit
and recharge unit
Problem solved
Problem solved
High head, high
High head, high
suction?
suction?
Unit is overcharged.
Unit is overcharged. Reclaim charge and
Reclaim charge and weigh in correct charge
weigh in correct charge
High head, low
High head, low
suction?
suction?
Yes
Yes
See note below*
See note below*
38/40MVC, MVQ
* Restriction in system. Check capillary tube, check for moisture, and check for damage to liquid line between indoor and
* Restriction in system. Check capillary tube, check for moisture, and check for damage to liquid line between indoor and
outdoor units.
outdoor units.
A08170
33
CHART 9 -- UNIT NOT RUNNING OPTIMALLY (HP IN HEATING)*
No
Visually check outdoor
Visually check outdoor
Unit for ice blockage. **
Unit for ice blockage. **
Yes
Yes
Check defrost sensor. Ok?
Check defrost sensor. Ok?
Go to flow chart #2
Yes
Yes
Check application limits.
Check application limits.
Ok?
Ok?
No
No
No
No
No
Check reversing valve.
Check reversing valve.
Go to flow chart #12
Replace sensor
Replace sensor
Beyond operating range
Beyond operating range
38/40MVC, MVQ
Yes
Yes
Check ambient conditions.
Check ambient conditions.
Prime icing?
Prime icing?
Yes
Yes
Explain to customer
Explain to customer
* To supplement flow chart #8 ** Check for blockage on outdoor coil and drain pan. Are the holes in drain pans blocked?
es in drain pans blocked?
A08184
34
CHART 10 -- COMPRESSOR
Trace connections from
Trace connections from OD board. Connections
OD board. Connections
ok?
ok?
Yes
Yes
Check contactor.*
Check contactor.* Contactor ok?
Contactor ok?
Yes
Yes
Check capacitor.
Check capacitor.
Capacitor ok?
Capacitor ok?
Yes
Yes
No
No
No
No
No
No
No fix connection
No fix connection
Replace contactor
Replace contactor
Replace capacitor
Replace capacitor
No
Check compressor
Check compressor
windings. Ok?
windings. Ok?
No
No
Compressor ok.
Compressor ok.
* For size 9 and 12k units contactor is on outdoor board.
Check contactor output on outdoor board if not done already.
If bad, replace outdoor board.
No
Replace compressor
Replace compressor
38/40MVC, MVQ
A08171
35
38/40MVC, MVQ
CHART 11 -- OUTDOOR MOTOR
Visually confirm that fan
Visually confirm that fan blades and outdoor coil
blades and outdoor coil are not blocked.
are not blocked.
Yes
Yes
Trace connections from
Trace connections from OD board. Connections
OD board. Connections
ok?
ok?
Yes
Yes
Check capacitor.
Check capacitor.
Capacitor ok?
Capacitor ok?
Yes
Yes
Check motor windings.
Check motor windings.
Ok?
Ok?
No
No
No
No
No
No
No
No
Clear blockage
Clear blockage
Fix connection
Fix connection
Replace capacitors
Replace capacitors
Replace motor
Replace motor
Yes
Yes
Motor ok.
Motor ok.
A08172
36
CHART 12 -- REVERSING VALVE
No
Check RV connection on
Check RV connection on
outdoor board. Ok?
outdoor board. Ok?
Yes
Yes
Check RV output on outdoor
Check RV output on outdoor
board. Ok?
board. Ok?
Yes
Yes
Check RV solenoid. Ok? Replace solenoid
Check RV solenoid. Ok? Replace solenoid
Yes
Yes
Replace reversing valve.
Replace reversing valve.
No
No
No
No
No
Clean or repair the
Clean or repair the
connection
connection
Replace outdoor board
Replace outdoor board
38/40MVC, MVQ
CHART 13 -- RECEIVER BOARD
Check wiring and
Check wiring and
connection between
connection between
receiver and ID board. Ok?
receiver and ID board. Ok?
Yes
Yes
Check input and output
Check input and output
on ID and receiver
on ID and receiver
boards. Ok?
boards. Ok?
Yes
Yes
Replace remote control
Replace remote control
No
No
No
No
Fix wiring or
Fix wiring or
connection
connection
Replace receiver board
Replace receiver board
A08173
37
APPENDIX
APPENDIX TABLE OF CONTENTS
DESCRIPTION NUMBER
Control Boards Input/Output tables for 53MVC009(12)------1 A1...................................................
Control Boards Input/Output tables for 53MVQ009(12)------1 A2...................................................
Control Boards Input/Output tables for 53MVC012-- -- --3 A3.......................................................
Control Boards Input/Output tables for 53MVQ012-- -- --3 A4......................................................
Control Boards Input/Output tables for 53MVC018-- -- --3 A5.......................................................
Temperature Sensor V alues (Temperature vs. Resistance) A6.......................................................
Fuse Chart A7...........................................................................................
Indoor Unit Diagnostic Codes A8...........................................................................
Outdoor Unit Diagnostic Codes A9..........................................................................
38/40MVC, MVQ
38
A 1 -- 5 3 M V C 0 0 9 -- -- -- 1 / 5 3 M V C 0 1 2 -- -- -- 1
3 8 M V C 0 0 9 --- --- --- 1 / 3 8 M V C 0 1 2 --- --- --- 1 C O N T R O L B O A R D
CONNECTOR INPUT or OUTPUT VALUE
CN2 OUT: (Pin 1: Pulse 0 to 12 Volts DC) (Pin2: 35±2 Volts DC) (Pin 3: GND) (Pin 4: 13±4 Volts DC) all relative to Pin 3
CN3 OUT: Neutral
CN4 IN: Neutral
CN9 OUT: L 115 Volt s AC
CN10 IN: L 115 Volts AC
P1 GND
P2 GND
4 0 M V C 0 0 9 --- --- --- 1 / 4 0 M V C 0 1 2 --- --- --- 1 C O N T R O L B O A R D
CONNECTOR INPUT or OUTPUT VALUE
CN1 IN : 0 --- 5 V o l t D C
CN2 IN : 0 --- 5 V o l t D C
CN3 Pulse drive output: 0 --- 17 Volts DCPin 5: GND All other Pins are 0 to 17 Volt DC) All relative to Pin 5
CN5
CN6
G1 IN: (Pin 1: Pulse 0 to 12 Volts DC) (Pin2: 35±2 Volts DC) (Pin 3: GND) (Pin 4: 13±4 Volts DC) all relative to Pin 3
Power Output: (Pin 1: GND) (Pin 2: 5 Volts DC) Input: (Pin 3: Pulse 0 to 5 Volts DC) Output:(Pin 4~ Pin 10: Pulse 0 to 5 Volt DC) All relative to Pin 1
Out: (Pin 1: 35 Volt DC) ( Pin 2: Empty) (Pin 3: GND) (Pin 4: 5 Volt DC) (Pin 5: Pulse 0--- 5 Volt DC) IN: (Pin 6: Pulse 0 to 5 Volt DC) All relative to Pin 3
38/40MVC, MVQ
A 2 -- 5 3 M V Q 0 0 9 -- -- -- 1 / 5 3 M V Q 0 1 2 -- -- -- 1
38MVQ009--- 1/38MVQ012--- --- --- 1 CONTROL BOARD
CONNECTOR INPUT or OUTPUT VALUE
CN1 OUT: (Pin 1: GND, Pin 2: 5 Volts DC, Pin 3: Empty) IN: (Pin 4: 0 to 5 Volts DC) All relative to Pin 1
CN2 OUT: (Pin 1: Pulse 0 to 12 Volts DC) (Pin2: 35±2 Volts DC) (Pin 3: GND) (Pin 4: 13±4 Volts DC) all relative to Pin 3
CN3 OUT: Neutral
CN4 IN: Neutral
CN5 OUT: L 115 Volt AC
CN6 OUT: L 115 Volt AC
CN10 IN: L 115 Volt AC
P1 GND
P2 GND
40MVQ009--- 1/40MVQ012--- --- --- 1 CONTROL BOARD
CONNECTOR INPUT or OUTPUT VALUE
CN1 IN : 0 --- 5 V o l t D C
CN2 IN : 0 --- 5 V o l t D C
CN3 Pulse drive output: 0 --- 17 Volts DCPin 5: GND All other Pins are 0 to 17 Volt DC) All relative to Pin 5
CN5
CN6
G1 IN: (Pin 1: Pulse 0 to 12 Volts DC) (Pin2: 35±2 Volts DC) (Pin 3: GND) (Pin 4: 13±4 Volts DC) all relative to Pin 3
Power Output: (Pin 1: GND) (Pin 2: 5 Volts DC) Input: (Pin 3: Pulse 0 to 5 Volts DC) Output:(Pin 4~ Pin 10: Pulse 0 to 5 Volt DC) All relative to Pin 1
Out: (Pin 1: 35 Volt DC) ( Pin 2: Empty) (Pin 3: GND) (Pin 4: 5 Volt DC) (Pin 5: Pulse 0--- 5 Volt DC) IN: (Pin 6: Pulse 0 to 5 Volt DC) All relative to Pin 3
39
A 3 -- 5 3 M V C 0 1 2 -- -- -- 3
3 8 M V C 0 1 2 --- --- --- 3 C O N T R O L B O A R D
CONNECTOR INPUT or OUTPUT VALUE
CN2 OUT: (Pin 1: Pulse 0 to 12 Volts DC) (Pin2: 35±2 Volts DC) (Pin 3: GND) (Pin 4: 13±4 Volts DC) all relative to Pin 3
CN3 OUT: L2 208/230 Volt AC
CN4 IN: L2 208/230 Volt AC
CN9 OUT: L1 208/230 Volt AC
CN10 IN: L1 208/230 Volt AC
P1 Ground
P2 Ground
4 0 M V C 0 1 2 --- --- --- 3 C O N T R O L B O A R D
CONNECTOR INPUT or OUTPUT VALUE
CN1 IN : 0 --- 5 V o l t D C
CN2 IN : 0 --- 5 V o l t D C
CN3 Pulse drive output: 0 --- 17 Volts DCPin 5: GND All other Pins are 0 to 17 Volt DC) All relative to Pin 5)
Power Output: (Pin 1: GND) (Pin 2: 5 Volts DC) Input: (Pin 3: Pulse 0 to 5 Volts DC) Output:(Pin 4~ Pin 10: Pulse 0 to 5 Volt DC) All relative to Pin 1
Out: (Pin 1: 35 Volt DC) ( Pin 2: Empty) (Pin 3: GND) (Pin 4: 5 Volt DC) (Pin 5: Pulse 0--- 5 Volt DC) IN: (Pin 6: Pulse 0 to 5 Volt DC) All relative to Pin 3
38/40MVC, MVQ
CN5
CN6
G1 IN: (Pin 1: Pulse 0 to 12 Volts DC) (Pin2: 35±2 Volts DC) (Pin 3: GND) (Pin 4: 13±4 Volts DC) all relative to Pin 3
A 4 -- 5 3 M V Q 0 1 2 -- -- -- 3
3 8 M V Q 0 1 2 --- --- --- 3 C O N T R O L B O A R D
CONNECTOR INPUT or OUTPUT VALUE
CN1 OUT: (Pin 1: GND, Pin 2: 5 Volts DC, Pin 3: Empty) IN: (Pin 4: 0 to 5 Volts DC) All relative to Pin 1
CN2 OUT: (Pin 1: Pulse 0 to 12 Volts DC) (Pin2: 35±2 Volts DC) (Pin 3: GND) (Pin 4: 13±4 Volts DC) all relative to Pin 3
CN3 OUT: L2 208/230 Volt AC
CN4 IN: L2 208/230 Volt AC
CN5 OUT: L1 208/230 Volt AC
CN6 OUT: L1 208/230 Volt AC
CN10 IN: L1 208/230 Volt AC
P1 Ground
P2 Ground
4 0 M V Q 0 1 2 --- --- --- 3 C O N T R O L B O A R D
CONNECTOR INPUT or OUTPUT VALUE
CN1 IN : 0 --- 5 V o l t D C
CN2 IN : 0 --- 5 V o l t D C
CN3 Pulse drive output: 0 --- 17 Volts DCPin 5: GND All other Pins are 0 to 17 Volt DC) All relative to Pin 5
CN5
CN6
G1 IN: (Pin 1: Pulse 0 to 12 Volts DC) (Pin2: 35±2 Volts DC) (Pin 3: GND) (Pin 4: 13±4 Volts DC) all relative to Pin 3
Power Output: (Pin 1: GND) (Pin 2: 5 Volts DC) Input: (Pin 3: Pulse 0 to 5 Volts DC) Output:(Pin 4~ Pin 10: Pulse 0 to 5 Volt DC) All relative to Pin 1
Out: (Pin 1: 35 Volt DC) ( Pin 2: Empty) (Pin 3: GND) (Pin 4: 5 Volt DC) (Pin 5: Pulse 0--- 5 Volt DC) IN: (Pin 6: Pulse 0 to 5 Volt DC) All relative to Pin 3
40
A 5 -- 5 3 M V C 0 1 8 -- -- -- 3
3 8 M V C 0 1 8 --- --- --- 3 C O N T R O L B O A R D
CONNECTOR INPUT or OUTPUT VALUE
CN1 IN: 14.5±5V Volts AC
CN3 Pulse Signal 0 to 24 Volts DC (Relative to ground)
CN4 IN: L1 208/230 Volts AC
CN5 IN: L2 208/230 Volts AC
CN6 OUT: 208/230 Volts AC
CN8 OUT: 208/230 Volts AC
4 0 M V C 0 1 8 --- --- --- 3 C O N T R O L B O A R D
CONNECTOR INPUT or OUTPUT VALUE
CN1 IN:11.0±3VoltsAC(Pin1toPin2); 9.5±2VoltsAC(Pin3toPin4)
CN2 OUT: IFM Capacitor Terminal 1
CN4 OUT: IFM Capacitor Terminal 2
CN5 OUT: 208/230 Volts AC
CN6 OUT: 208/230 Volts AC (Pin 1 to Pin 2, Pin 1 to Pin 3, Pin 1 to Pin4)
CN7 IN: 0---5VoltDC(Notincluding0Vand5V)
CN8 IN: 0---5VoltDC(Notincluding0Vand5V)
CN9 OUT: (Pin 1: Ground, Pin 2: 5 Volts DC) IN: (Pin 1: Ground, Pin 3: 0 to 5 Volts DC) Pulse relative to Pin 1
CN10 OUT: (Pin 1: Ground, Pin 2 ~ Pin 5: 0 to 5 Volts DC) Pulse relative to Pin 1
CN11 OUT: (Pin 5: Ground, all other Pins are 0 to 17 Volts DC) Pulse relative to Pin 5
CN12 Two way signal, 0 to 24 Volts DC, Pulse relative to Ground
P1 IN: L1 208/230 Volts AC
P2 IN: L2 208/230 Volts AC
INDOOR UNIT DISPLAY BOARD
CONNECTOR INPUT or OUTPUT VALUE
CN1 IN: (Pin 1: Ground, Pin 2 ~ 5: 0 to 5 Volts DC) Pulse relative to Pin 1
CN2 IN: (Pin 1: Ground, Pin: 5 Volts DC) OUT: (Pin 3: 0 to 5 Volts DC) Pulse relative to Pin 1
38/40MVC, MVQ
41
A6 -- Characteristics of Temperature Sensor
Tem p . ˚F/˚C Resistance KΩ Te m p . ˚F/˚C Resistance KΩ Te m p . ˚F/˚C Resistance KΩ
14/--- 10 62.2756 62.6/17 14.6181 111.2/44 4.3874
15.8/--- 9 58.7079 64.4/18 13.918 113/45 4.2126
17.6/--- 80 56.3694 66.2/19 13.2631 114.8/46 4.0459
19.4/--- 7 52.2438 68/20 12.6431 116.6/47 3.8867
21.2/--- 6 49.3161 69.8/21 12.056 118.4/48 3.7348
23/--- 5 46.5725 71.6/22 11.5 120.2/49 3.5896
24.8/--- 4 44 73.4/23 10.9731 122/50 3.451
26.6/--- 3 41.5878 75.2/24 10.4736 123.8/51 3.3185
28.4/--- 2 39.8239 77/25 10 125.6/52 3.1918
30.2/--- 1 37.1988 78.8/26 9.5507 127.4/53 3.0707
32/0 35.2024 80.6/27 9.1245 129.2/54 2.959
33.8/1 33.3269 82.4/28 8.7198 131/55 2.8442
35.6/2 31.5635 84.2/29 8.3357 132.8/56 2.7382
37.4/3 29.9058 86/30 7.9708 134.6/57 2.6368
39.2/4 28.3459 87.8/31 7.6241 136.4/58 2.5397
41/5 26.8778 89.6/32 7.2946 138.2/59 2.4468
42.8/6 25.4954 91.4/33 6.9814 140/60 2.3577
44.6/7 24.1932 93.2/34 6.6835 141.8/61 2.2725
38/40MVC, MVQ
46.4/8 22.5662 95/35 6.4002 143.6/62 2.1907
48.2/9 21.8094 96.8/36 6.1306 145.4/63 2.1124
50/10 20.7184 98.6/37 5.8736 147.2/64 2.0373
51.8/11 19.6891 100.4/38 5.6296 149/65 1.9653
53.6/12 18.7177 102.2/39 5.3969 150.8/66 1.8963
55.4/13 17.8005 104/40 5.1752 152.6/67 1.83
57.2/14 16.9341 105.8/41 4.9639 154.4/68 1.7665
59/15 16.1156 107.6/42 4.7625 156.2/69 1.7055
60.8/16 15.3418 109.4/43 4.5705 158/70 1.6469
42
A7 -- Fuse Chart
r
Unit Size
Indoor Outdoor Outdoor
Fuse Rating (Amps/Volts)
009 --- 3.15A/250V 2A/250V
012 --- 3.15A/250V 2A/250V
018 3.15A/250V 3.15A/250V ---
024 3.15A/250V 3.15A/250V ---
The 3.15A fuses protect the board against the indoor or outdoor fan motors. The 2A fuses protect the board against a Class II circuit board failure.
A8 -- Indoor Unit Diagnostic Guides
9K & 12K Units
Operation
Lamp
l X Indoor fan speed has been out of control for over 1 minute 1 l On Indoor room temp. or evaporator sensor is open circuit or short circuited 2
X l Compressor over--- current protection has been activated four times 3
On l EPROM error* ---
l l Indoor unit communication error (Illuminates simultaneously) 4
Opera-
tion
Lamp
l l l l Over- -- current protection of the compressor occurs four times 3
X l X X Indoor room temp. sensor is open circuit or short circuited 2
l X X X Temp. sensor on indoor evaporator is open circuit or short circuited 2
X X l X
X X l l Outdoor unit protects (outdoor temp. sensor, phase order, etc.) 5 X l X l EPROM error* --­X X X l Indoor unit communication error 6
l =Flashing
X=Off
* = Replace Indoor Board
Timer
Lamp
Timer
Defrosting
Lamp
Infrared signal receptor
OPERATION
AUTO
ECON
Model size 009
Lamp
TIMER
PRE-DEF
A07545a
Auto
Lamp
Failure Mode
18K & 24K Units
Failure Mode
Temp. sensor on outdoor condenser is open circuit or short circuited (not cooling only modes)
TIMER
PRE-DEF
OPERATION
Model size 012
Infrared signal recepto
OPERATION
A07544
AUTO
Model size 018--024*
TIMER
Diagnostic
Chart
Diagnostic
Chart
2
PRE.-DEF.
A07546a
38/40MVC, MVQ
* PRE--DEF light will illuminate when the unit is running in FAN ONLY mode on Cooling Only units.
Fig. 34 – LED Display Panel
A9 -- Outdoor Unit Diagnostic Guides
Flashing
Times after 2
Failure Mode
Second Off
5 Communication failure 4or6 2 Condenser temperature sensor failure 2 1 Other indoor failure
If the unit is operating normally, the LED light on the outdoor board is lit continuously. If there is a failure, the LED light will flash a specific number of times. Refer to the Outdoor Unit Diagnostic table above to determine failure.
43
Diagnostic
Chart
38/40MVC, MVQ
Copyright 2008 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Printed in U.S.A. Edition Date : 03/08
44
Catalog No.38--- 40MV --- 1SM
Replaces: New
Loading...