Carrier 40MKQB user guide manual

40MKCB**C/24AHA4 40MKCB**C/124ANS 40MKQB**C/25HHA4 40MKQB**C/224ANS Cassette Ductless Split Sizes 18 to 34
Installation Instructions
TABLE OF CONTENTS SAFETY CONSIDERATIONS 1 PARTS LIST 2 DIMENSIONS -- INDOOR 4 DIMENSIONS -- OUTDOOR 5 CLEARANCES -- INDOOR 7 CLEARANCES -- OUTDOOR 7 SYSTEM REQUIREMENTS 7 INSTALLATION 9 INSTALL INDOOR UNIT 9 INSTALL OUTDOOR UNIT 12 ELECTRICAL DATA 16 START--UP 20 TROUBLESHOOTING 23
Fig. 1 -- Indoor Unit, Outdoor Unit, and Remote Contro l
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury or equipment damage.
Puron refrigerant systems operate at higher pressures than standard R-- 22 systems. To avoid damage to the unit or possible personal injury, do not use R--22 service equipment or components on Puron refrigerant equipment.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazi ng operations . Have a fire extingui sher avai l able. Read these instruct ions thoroughly and follow all warnings or cautions included in the unit literature and on labels attached to the unit. Consult local building codes and current editions of the National Electrica l Code ( NEC ) NFP A 70. In Canada, refer to current editions of the Canadian electrical code CSA 22.1.
Recognize safet y information. This is the safety--alert symbol When you see this symbol on the unit and in instruct ions or manuals , be alert to the potential for personal injury. Underst and these signal words; DANGER, WARNING,andCAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor persona l injury or product and proper t y damage .
!
!
NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
!
CAUTION
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental pollution.
Remove and recycle all components or materials (i.e. oil, refrigerant, etc.) before unit final disposal.
PARTS LIST
Indoor Unit
Kit
TXV
The casse t t e type unit and horizontal discharge unit (24AHA/124ANS and 25HHA4/224ANS) install ation would not be complete without the addition of the TXV kit. This can be found in the packaging of the indoor unit. If you do not have this kit, order the kit and install the outdoor and indoor units when this is available.
Below are figures of the kit and how and where the kit is included within the indoor unit packaging.
Liquid pipe
Gas pipe
INSTALLATION
IMPORTANT: Effective January 1, 2015, all split systems and
packaged air conditioners must be installed pursuant to applicable regional efficiency standards issued by the Department of Energy.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts have sharp edges or burrs, Use care and wear appropriate protective clothing and gloves when handling parts.
!
CAUTION
PERSONAL INJURY AND EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in personal injury and / or equipment damage.
DO NOT operate the unit without a filter or with grille removed.
These instructions cover the installation and the start--up of the systems listed in Table 1.
Table 1 – Matched Systems
System
Type
Cooling
Only
Heat
Pump
Nominal Capacity KBTU/Hr
018 24AHA418A003 124ANS018000 40MKCB18C--3 024 24AHA424A003 124ANS024000 40MKCB34C--3 030 24AHA430A003 124ANS030000 40MKCB34C--3 034 24AHA436A003/5/6 124ANS036000 40MKCB34C--3 024 25HHA424A003 224ANS024000 40MKQB34C--3 030 25HHA430A003 224ANS030000 40MKQB34C--3 034 25HHA436A003/5/6 224ANS036000 40MKQB34C--3
Outdoor Unit Indoor Unit
Refrigerant flow direction
Fig. 2 -- TXV Kit
Flexible pipings
(Field)
Flexible pipings
(Field)
TXV Kit
TXV Kit
Fig. 3 -- TXV Kit (within packaging of indoor unit)
A150289
A150286
2
Table 2 – Indoor Units Parts List
Name o f Part
Qty. Usage
Owner’s Manual 1 Guide for the homeowner Warranty card 1 Warranty information Installation instructions 1 Guide to install the unit
Pipe insulation Material 1
Insulation for refrigerant piping
For conforming to EMC
Clamp filter 2
standards on connecting wires
Flexible hose 1
Pipe clamp 1
Drains moisture from inside the indoor unit
Fixes the flexible hose to the indoor unit
Remote Controller 1 Controls the indoor unit
Remote Controller holder 1
Tapped Screw 2
Holds the remote controller on the wall Used to fix the remote controller holder
Battery 2 Powers the remote controller
Strain relief bracket 1
To affix strain relief to hold wires in place
Screws 4 To affix strain relief bracket
Cassette Cover Panel
A cassette grille/panel is required to complete installation of indoor unit. The indoor unit installa t ion would not be compl ete without the addition of this grille. Order it and complete installation when you have the grille available. The grille model number is: 40MK--B01C----3.
Outdoor Unit
The following items are included with the outdoor unit:
Fig. 5 -- 24AHA/124ANS
Fig. 6 -- 25HHA4/224ANS
Table 3 – Outdoor Unit Parts Checklist
Model
24AHA4/124ANS n 25HHA4/224ANS n n n n
Filter Drier
Piston
Cap
Pistons
A09536
A09537
Flare
Connector
Fig. 4 -- Cassette Grille/Panel
3
DIMENSIONS - INDOOR
Cassette Grille
Cassette Body
Drain pipe connector
H
W
Refrigerant pipe connector
H
D
Fresh air intake (
W
Φ75mm)
Fig. 7 -- 40MKC**C, 40MKQ**C Unit and Panel Dimensions
Table 4 – Dimensions Indoor
Indoor Unit Size
BTU/Hr
18K 33.1 (840) 33.1 (840) 8.1 (205) 54.0 (24.5)
24K – 34K 33.1 (840) 33.1 (840) 11.3 (287) 68.6 (31.1)
Cassette Panel 37.4 (950) 37.4 (950) 2.2 (55) 11.0 (5)
Height (H)
in (mm)
Width (W)
in (mm)
Depth (D)
in (mm)
Operating Weight
lb (kg)
A150291
4
DIMENSIONS -- OUTDOOR
NOTE:
S Center of Gravity S All dimensions are in “inches” unless noted.
MINIMUM
UNIT SIZE
18,24 23” x 42”
30,36 24” x 50”
MOUNTING PAD
DIMENSIONS
Fig. 8 -- Outdoor Unit Dimensions
5
227
103.0
89.4
197
22.2
Table6–Dimensions(ACs)
Table7–DimensionsSI(ACs)
Table 8 – Dimensions (HPs)
Table9–DimensionsSI(HPs)
XX0
6 X
124ANS024000/
12ANS030000/
124ANS018000 /
124ANS036000/
124ANS018000
124ANS036000
124ANS024000
124ANS030000
6
224ANS024000/
224ANS030000/
224ANS036000/24HHAA436 0 X XX
224ANS024000/
224ANS030000/
224ANS036000/
CLEARANCES -- INDOOR
Fig. 9 -- 40MKC**B, 40MKQ**B Unit Clearance
A150152
CLEARANCES -- OUTDOOR
1. Single Unit Applications: With coil facing wall: Allow 6” (152.4mm) minimum clearance on coil side and coil end and 20” (504.0 mm) minim um clearance on fan side. Allow 24” (609.6 mm) minimum clearance on compressor end for service.
2. With fan facing wall: Allow 8” (203.2 mm) minimum clearance on fan side and coil end and 20” (504.0 mm) minimum clear ance on coil side. Allow 24” (609.6 mm) minimum clearance on compressor end for service when units are stacked or there is less than 40” (1016 mm) of clea rance above the unit. If there is 40” (1016 mm) clearanc e above unit and the top panel is accessible for removal allow 8” (203.2 mm) minimum clearance on compressor end for service.
3. Multi--unit Applications: Allow 24” (609.6 mm) minimum clearance between fan and coil sides of multiple units. Arrange units so discharge of one does not enter inlet of another. Allow 24” (609.6 mm) minimum clea rance on compressor end when units are stacke d or ther e is less than 40” (1016 mm) of clearance above the unit. If there is 40” (1016 mm) clearance above unit and the top panel is accessible for removal allow 8” (203.2 mm) minimum clearance on compressor end for service. When two units are installed end to end with the coil ends facing each other allow 12” (304.8 mm) minimum clearance between units.
IMPORTANT: When installing multiple units, ensure the discharge air from one unit is not drawn into another unit. When installing single or multiple units in an alcove, roof well, or partially enclosed area, ensure there is adequate ventilation to prevent recirculation of discharge air.
SYSTEM REQUIREMENTS
Clearances
Allow sufficient space around the indoor and outdoor unit for proper airflow circulation and servicing. Refer to Fig.9 and the outdoor unit clearance section for minimum required clearances.
Piping: Piping and insulation is field supplied.
Piping Lengths
The minimum length between the indoor and outdoor units is 10 ft (3 m). Refer to table 9 for the maximum lengths allowed.
Table 9 – Maximum Refrigerant Line Lengths
Unit Size
18K-34K 250 (76.2) 65 (19.8) 200 (61)
Note:Forlengthsgreaterthan25ft(7.6m),refertotheResidential Long Line Guide.
Max Line
Length* ft(m
Max Elevation
(ID over OD)
ft(m)
Pipe Sizes
In some models, indoor unit and/or outdoor unit pipe sizes may differ from those in TXV connections. Coupling is required in those cases. See Table 10 for complete list of tube sizes to identify coupling needs.
Table10–PipeSizes
Indoor Unit Tube
Indoor Unit Outdoor Unit
40MKCB18C-- -- 3
40MKCB34C-- -- 3
40MKCB34C-- -- 3
40MKCB34C-- -- 3
40MKQB34C-- --3
40MKQB34C-- --3
40MKQB34C-- --3
Note:Both line s need to be insulated using at least 1/2 inch closed foam insulation.
24AHA418
124ANS018
24AHA424
124ANS024
24AHA430
124ANS030
24AHA436
124ANS036
25HHA424
224ANS024
25HHA430
224ANS030
25HHA436
224ANS036
Sizes (in)
Liquid Vap o r Liquid Va po r Liquid Vap o r
3/8
TXV Kit Tube
Sizes (in)
5/8
3/4 3/4 3/4
3/4 3/4 3/4
3/4 3/4 7/8
3/4 3/4 3/4
3/4 3/4 3/4
3/4 3/4 7/8
5/8
3/8
Max Elevation (OD overID)ft(m)
Outdoor Unit Tube Size (in)
5/8
3/8
7
Condensate Drain Pipe Sizes
Refer to table 11 for the required sizes.
Table 11 – Drain Pipe Sizes
Indoor Unit Size
BTU/Hr
18K 1 (25.4)
24K – 34K 1 (25.4)
Outside Diameter
in (mm)
Refrigerant Charge
The outdoor units can be matched with multiple indoor units and thus a different amount of charge might be required when matched with the 40MKCB**C or 40MKQB**C units. Charge to Sub--cooling Delta from Rating Plate Value as stated below.
Table 12 – Charge Requirements
System
Type
Cooling
Only
Heat
Pump
Nominal Capacity
kBTU/Hr
018 24AHA418A003 124ANS018000 40MKCB18C-- --3 12
024 24AHA424A003 124ANS024000 40MKCB34C-- --3 12
030 24AHA430A003 124ANS030000 40MKCB34C-- --3 12
034 24AHA436A003/5/6 124ANS036000 40MKCB34C----3 8
024 25HHA424A003 224ANS024000 40MKCB34C-- --3 14
030 25HHA430A003 224ANS030000 40MKCB34C-- --3 11
034 25HHA436A003/5/6 224ANS036000 40MKCB34C----3 14
Outdoor Unit Indoor Unit
Charge to
Sub--cooling Delta
from Rating Plate
Val u e
NOTE: The above additional charge is required amount for line lengths up to 25 ft. (7.6 m). For line lengths exceeding 25 ft (7.6 m), additional charge will be required. Refer to the Residential Long Line Guide.
Metering Device
The 40MKC(Q)*C unit uses a TXV while the outdoor unit uses a type B accurator. The cooling metering device is installed with the indoor unit. The heating metering device is installed with the outdoor unit. One metering device is required for the cooling only system and two are required for the heat pump systems. Refer to Table 13 for a breakdown of each unit’s metering devices.
Table 13 – Metering Devices
System Size
kBTU/hr
018 TXV - ­024 TXV TXV 0.049" 030 TXV TXV 0.055" 034 TXV TXV 0.063"
Cooling Only Heat Pumps
40MKCB**C 40MKQB**C 25HHA4/224ANS
Power and Connecting Cables -- Field Supplied
Recommended Connection Method for Power and Communication Wiring (To minimize communication wiring interference)
Power W
The main power is supplied to both the indoor and the outdoor units. The field supplied connecting cable consists of three (3) wires. Two wires are high voltage AC power and one is a ground wire. Consult your local building codes and the NEC (National Electrical Code) or CEC (Canadian Electrical Code) for special requirements. All wires must be sized per NEC or CEC and local codes. Use Electrical Data table MCA (minimum circuit amps) and MOCP (maximum over current protection) to correctly size the wires and the disconnect fuse or breakers respectively. Per caution note, only copper conductors with a minimum 300 volt rating and 2/64--inch thick insulation must be used.
iring:
Communication Wiring:
A separate shielded Stranded copper conductor only, with a 600 volt rating and double insulated copper wire, must be used as the communication wire from the outdoor unit to the indoor unit. To minimize voltage drop of the communication wire, use the wire size and maximum lengths shown in Table 14.
Table 14 – Maximum Lengths
Wire Size Length ft. (m)
18AWG 50 ft. (15 m) 16AWG 50 ft. (15 m) to 100 ft. (30 m) 13AWG 100 ft. (30 m) to 200 ft. (60 m)
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow the following caution may result in equipment damage or improper operation.
Wires should be sized based on NEC and local codes. Use copper conductors only with a 600 volt rating and double insulated copper wire.
User Interface
The indoor unit is supplied with a wireless remote control to operate the unit (an Owner’s Manual is supplied with the unit). The following accessories are available.
S Wall mounted control.
Operating Range
Ensure that the system operates within the application guidelines shown in the following tables.
Table 15 – Cooling Operating Range
Maximum Minimum
Outdoor
Unit
Indoor Unit 90 (32) - 64 (18) -
DB °F (° C) WB °F (°C) DB °F (°C) WB °F (°C)
125 (51.7) - 55 (12.8) -
Table 16 – Heating Operating Range
Maximum Minimum
Outdoor
Unit
Indoor Unit 80(27) 32 (0) -
DB °F (° C) WB °F (°C) DB °F (°C) WB °F (°C)
75 (23.9) 67 (19.4) 17 (-8.3) -
Accessories
An extensive list of field installed accessories is available for both indoor and outdoor units. Identify what accessories, if any, are required for the application at hand and consult the separate installation instructions for the accessories. Some of the accessories, especially on the indoor units, can be installed much easier if planned ahead.
8
Loading...
+ 16 hidden pages