Fig. 1 -- Indoor Unit, Outdoor Unit, and Remote Contro l
NOTE: Read the entire instruction manual before starting the
installation.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury or
equipment damage.
Puron refrigerant systems operate at higher pressures than
standard R-- 22 systems. To avoid damage to the unit or
possible personal injury, do not use R--22 service equipment or
components on Puron refrigerant equipment.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and
work gloves. Use quenching cloth for brazi ng operations . Have a fire
extingui sher avai l able. Read these instruct ions thoroughly and follow
all warnings or cautions included in the unit literature and on labels
attached to the unit. Consult local building codes and current editions
of the National Electrica l Code ( NEC ) NFP A 70. In Canada, refer to
current editions of the Canadian electrical code CSA 22.1.
Recognize safet y information. This is the safety--alert symbol
When you see this symbol on the unit and in instruct ions or manuals ,
be alert to the potential for personal injury. Underst and these signal
words; DANGER, WARNING,andCAUTION. These words are
used with the safety--alert symbol. DANGER identifies the most
serious hazards which will result in severe personal injury or death.
WARNING signifies hazards which could result in personal injury or
death. CAUTION is used to identify unsafe practices which may
result in minor persona l injury or product and proper t y damage .
!
!
NOTE is used to highlight suggestions which will result in enhanced
installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF
position. There may be more than 1 disconnect switch.
Lock out and tag switch with a suitable warning label.
!
CAUTION
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental
pollution.
Remove and recycle all components or materials (i.e. oil,
refrigerant, etc.) before unit final disposal.
PARTS LIST
Indoor Unit
Kit
TXV
The casse t t e type unit and horizontal discharge unit (24AHA/124ANS
and 25HHA4/224ANS) install ation would not be complete without
the addition of the TXV kit. This can be found in the packaging of the
indoor unit. If you do not have this kit, order the kit and install the
outdoor and indoor units when this is available.
Below are figures of the kit and how and where the kit is included
within the indoor unit packaging.
Liquid pipe
Gas pipe
INSTALLATION
IMPORTANT: Effective January 1, 2015, all split systems and
packaged air conditioners must be installed pursuant to applicable
regional efficiency standards issued by the Department of Energy.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts have sharp edges or burrs, Use care and wear
appropriate protective clothing and gloves when handling
parts.
!
CAUTION
PERSONAL INJURY AND EQUIPMENT DAMAGE
HAZARD
Failure to follow this caution may result in personal injury
and / or equipment damage.
DO NOT operate the unit without a filter or with grille
removed.
These instructions cover the installation and the start--up of the
systems listed in Table 1.
Fig. 3 -- TXV Kit (within packaging of indoor unit)
A150289
A150286
2
Table 2 – Indoor Units Parts List
Name o f Part
Qty. Usage
Owner’s Manual1Guide for the homeowner
Warranty card1Warranty information
Installation instructions1Guide to install the unit
Pipe insulation Material1
Insulation for refrigerant
piping
For conforming to EMC
Clamp filter2
standards on connecting
wires
Flexible hose1
Pipe clamp1
Drains moisture from inside
the indoor unit
Fixes the flexible hose to the
indoor unit
Remote Controller1Controls the indoor unit
Remote Controller holder1
Tapped Screw2
Holds the remote controller
on the wall
Used to fix the remote
controller holder
Battery2Powers the remote controller
Strain relief bracket1
To affix strain relief to hold
wires in place
Screws4To affix strain relief bracket
Cassette Cover Panel
A cassette grille/panel is required to complete installation of indoor
unit. The indoor unit installa t ion would not be compl ete without the
addition of this grille. Order it and complete installation when you
havethe grille available. The grille modelnumber is:
40MK--B01C----3.
Outdoor Unit
The following items are included with the outdoor unit:
Fig. 5 -- 24AHA/124ANS
Fig. 6 -- 25HHA4/224ANS
Table 3 – Outdoor Unit Parts Checklist
Model
24AHA4/124ANSn
25HHA4/224ANSnnnn
Filter
Drier
Piston
Cap
Pistons
A09536
A09537
Flare
Connector
Fig. 4 -- Cassette Grille/Panel
3
DIMENSIONS - INDOOR
Cassette Grille
Cassette Body
Drain pipe
connector
H
W
Refrigerant pipe
connector
H
D
Fresh air intake (
W
Φ75mm)
Fig. 7 -- 40MKC**C, 40MKQ**C Unit and Panel Dimensions
SCenter of Gravity
SAll dimensions are in “inches” unless noted.
MINIMUM
UNIT SIZE
18,2423” x 42”
30,3624” x 50”
MOUNTING PAD
DIMENSIONS
Fig. 8 -- Outdoor Unit Dimensions
5
227
103.0
89.4
197
22.2
Table6–Dimensions(ACs)
Table7–DimensionsSI(ACs)
Table 8 – Dimensions (HPs)
Table9–DimensionsSI(HPs)
XX0
6X
124ANS024000/
12ANS030000/
124ANS018000 /
124ANS036000/
124ANS018000
124ANS036000
124ANS024000
124ANS030000
6
224ANS024000/
224ANS030000/
224ANS036000/24HHAA4360XXX
224ANS024000/
224ANS030000/
224ANS036000/
CLEARANCES -- INDOOR
Fig. 9 -- 40MKC**B, 40MKQ**B Unit Clearance
A150152
CLEARANCES -- OUTDOOR
1. Single Unit Applications: With coil facing wall: Allow 6”
(152.4mm) minimum clearance on coil side and coil end and
20” (504.0 mm) minim um clearance on fan side. Allow 24”
(609.6 mm) minimum clearance on compressor end for
service.
2. With fan facing wall: Allow 8” (203.2 mm) minimum
clearance on fan side and coil end and 20” (504.0 mm)
minimum clear ance on coil side. Allow 24” (609.6 mm)
minimum clearance on compressor end for service when units
are stacked or there is less than 40” (1016 mm) of clea rance
above the unit. If there is 40” (1016 mm) clearanc e above unit
and the top panel is accessible for removal allow 8” (203.2
mm) minimum clearance on compressor end for service.
3. Multi--unit Applications: Allow 24” (609.6 mm) minimum
clearance between fan and coil sides of multiple units. Arrange
units so discharge of one does not enter inlet of another. Allow
24” (609.6 mm) minimum clea rance on compressor end when
units are stacke d or ther e is less than 40” (1016 mm) of
clearance above the unit. If there is 40” (1016 mm) clearance
above unit and the top panel is accessible for removal allow 8”
(203.2 mm) minimum clearance on compressor end for
service. When two units are installed end to end with the coil
ends facing each other allow 12” (304.8 mm) minimum
clearance between units.
IMPORTANT: When installing multiple units, ensure the
discharge air from one unit is not drawn into another unit. When
installing single or multiple units in an alcove, roof well, or
partially enclosed area, ensure there is adequate ventilation to
prevent recirculation of discharge air.
SYSTEM REQUIREMENTS
Clearances
Allow sufficient space around the indoor and outdoor unit for
proper airflow circulation and servicing. Refer to Fig.9 and the
outdoor unit clearance section for minimum required clearances.
Piping: Piping and insulation is field supplied.
Piping Lengths
The minimum length between the indoor and outdoor units is 10 ft
(3 m). Refer to table 9 for the maximum lengths allowed.
Table 9 – Maximum Refrigerant Line Lengths
Unit Size
18K-34K250 (76.2)65 (19.8)200 (61)
Note:Forlengthsgreaterthan25ft(7.6m),refertotheResidential Long
Line Guide.
Max Line
Length* ft(m
Max Elevation
(ID over OD)
ft(m)
Pipe Sizes
In some models, indoor unit and/or outdoor unit pipe sizes may
differ from those in TXV connections. Coupling is required in
those cases. See Table 10 for complete list of tube sizes to identify
coupling needs.
Table10–PipeSizes
Indoor Unit Tube
Indoor UnitOutdoor Unit
40MKCB18C-- -- 3
40MKCB34C-- -- 3
40MKCB34C-- -- 3
40MKCB34C-- -- 3
40MKQB34C-- --3
40MKQB34C-- --3
40MKQB34C-- --3
Note:Both line s need to be insulated using at least 1/2 inch closed foam
insulation.
24AHA418
124ANS018
24AHA424
124ANS024
24AHA430
124ANS030
24AHA436
124ANS036
25HHA424
224ANS024
25HHA430
224ANS030
25HHA436
224ANS036
Sizes (in)
Liquid Vap o r Liquid Va po r Liquid Vap o r
3/8
TXV Kit Tube
Sizes (in)
5/8
3/43/43/4
3/43/43/4
3/43/47/8
3/43/43/4
3/43/43/4
3/43/47/8
5/8
3/8
Max
Elevation (OD
overID)ft(m)
Outdoor Unit
Tube Size (in)
5/8
3/8
7
Condensate Drain Pipe Sizes
Refer to table 11 for the required sizes.
Table 11 – Drain Pipe Sizes
Indoor Unit Size
BTU/Hr
18K1 (25.4)
24K – 34K1 (25.4)
Outside Diameter
in (mm)
Refrigerant Charge
The outdoor units can be matched with multiple indoor units and
thus a different amount of charge might be required when matched
with the 40MKCB**C or 40MKQB**C units. Charge to
Sub--cooling Delta from Rating Plate Value as stated below.
Table 12 – Charge Requirements
System
Type
Cooling
Only
Heat
Pump
Nominal
Capacity
kBTU/Hr
01824AHA418A003124ANS018000 40MKCB18C-- --312
02424AHA424A003124ANS024000 40MKCB34C-- --312
03024AHA430A003124ANS030000 40MKCB34C-- --312
03424AHA436A003/5/6 124ANS036000 40MKCB34C----38
02425HHA424A003224ANS024000 40MKCB34C-- --314
03025HHA430A003224ANS030000 40MKCB34C-- --311
03425HHA436A003/5/6 224ANS036000 40MKCB34C----314
Outdoor UnitIndoor Unit
Charge to
Sub--cooling Delta
from Rating Plate
Val u e
NOTE: The above additional charge is required amount for
line lengths up to 25 ft. (7.6 m). For line lengths exceeding 25 ft
(7.6 m), additional charge will be required. Refer to the
Residential Long Line Guide.
Metering Device
The 40MKC(Q)*C unit uses a TXV while the outdoor unit uses a
type B accurator. The cooling metering device is installed with the
indoor unit. The heating metering device is installed with the
outdoor unit. One metering device is required for the cooling only
system and two are required for the heat pump systems. Refer to
Table 13 for a breakdown of each unit’s metering devices.
Recommended Connection Method for Power and
Communication Wiring (To minimize communication
wiring interference)
Power W
The main power is supplied to both the indoor and the outdoor
units. The field supplied connecting cable consists of three (3)
wires. Two wires are high voltage AC power and one is a ground
wire.
Consult your local building codes and the NEC (National
Electrical Code) or CEC (Canadian Electrical Code) for special
requirements.
All wires must be sized per NEC or CEC and local codes. Use
Electrical Data table MCA (minimum circuit amps) and MOCP
(maximum over current protection) to correctly size the wires and
the disconnect fuse or breakers respectively.
Per caution note, only copper conductors with a minimum 300 volt
rating and 2/64--inch thick insulation must be used.
iring:
Communication Wiring:
A separate shielded Stranded copper conductor only, with a 600
volt rating and double insulated copper wire, must be used as the
communication wire from the outdoor unit to the indoor unit. To
minimize voltage drop of the communication wire, use the wire
size and maximum lengths shown in Table 14.
Table 14 – Maximum Lengths
Wire SizeLength ft. (m)
18AWG50 ft. (15 m)
16AWG50 ft. (15 m) to 100 ft. (30 m)
13AWG100 ft. (30 m) to 200 ft. (60 m)
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow the following caution may result in
equipment damage or improper operation.
Wires should be sized based on NEC and local codes. Use
copper conductors only with a 600 volt rating and double
insulated copper wire.
User Interface
The indoor unit is supplied with a wireless remote control to
operate the unit (an Owner’s Manual is supplied with the unit). The
following accessories are available.
S Wall mounted control.
Operating Range
Ensure that the system operates within the application guidelines
shown in the following tables.
Table 15 – Cooling Operating Range
MaximumMinimum
Outdoor
Unit
Indoor Unit90 (32)-64 (18)-
DB °F (° C)WB °F (°C)DB °F (°C)WB °F (°C)
125 (51.7)-55 (12.8)-
Table 16 – Heating Operating Range
MaximumMinimum
Outdoor
Unit
Indoor Unit80(27)32 (0)-
DB °F (° C)WB °F (°C)DB °F (°C)WB °F (°C)
75 (23.9)67 (19.4)17 (-8.3)-
Accessories
An extensive list of field installed accessories is available for both
indoor and outdoor units. Identify what accessories, if any, are
required for the application at hand and consult the separate
installation instructions for the accessories. Some of the
accessories, especially on the indoor units, can be installed much
easier if planned ahead.
8
INSTALLATION
Complete Pre--installation Checks
1. Unpack Unit -- Store the indoor and outdoor units in the
original packaging until it is moved to the final site for
installa tion. When unpacking indoor unit, be careful not to lift
unit by condensate drain discharge pipe or by refrigerant
connections.
2. Inspec t Shipment -- Upon receipt of shipment, check the indoor and outdoor units for damage. If there is any damage,
forwa r d claim papers direct ly to the transportati on company.
Manufa cturer is not responsi ble for damage incurred in transit.
3. Inspect Parts Supplied With Units – Check all items
against parts list (see the PARTS LIST section). If any items
are missing, notify your distributor or manufacturer office.
To prevent loss or damage, leave all parts in original
packages until installation.
Consider System Requirements
1. Consult local building codes and NEC for special
installation requirements.
2. When deciding the location of the indoor and outdoor units,
ensure that the piping run does not exceed the allowed
distances listed in Table 9.
3. Make sure the indoor and outdoor units are easily accessible
to electrical power.
4. Allow sufficient clearances for airflow, wiring, refrigerant
piping, and servicing the unit (see the ”CLEARANCES -INDOOR” and “CLEARANCES -- OUTDOOR” sections).
5. Condensate piping can be directed through the inside wall
to an approved drain or straight outside.
INSTALL INDOOR UNIT
Plan the installation carefully before you begin.
1. Select indoor unit location.
a. Where it is out of direct sunlight.
b. Where the airflow is not blocked.
c. Where an optimum air distribution is ensured.
d. Where the condensate can drain correctly and safely.
e. A ceiling that prevents vibration and is strong enough to
hold the product weight.
f. Maintain sufficient clearance around the indoor unit for
maintenance and servicing. Refer to the clearances
section of this document.
g. Where the air filter can be removed and cleaned easily.
h. Where the piping between the indoor and outdoor units
is within the allowable limits.
i. Inst all the indoor unit 1m or more away from the TV or
radio to prevent the screen from being distor ted or noise
from being generated.
j. Install the indoor unit as far away as possible from
fluorescent and incandescent lights so that the remote
control can be operated well.
k. Do not install units too close to humid conditions.
2. TXV Installation
a. Location -- The TXV kit can be affixed directly to the
indoor unit or anywhere between 12 to 18 inches from
the indoor unit pipe connection.
!
Failure to follow the following caution may result in equipment
damage or improper operation.
The TXV kit needs to be installation at most 12 to 18 inches
from the indoor unit pipe connection.
b. The TXV contains a label specifying the allowed flow
direction. See below for allowed and not allowed flow
directions.
!
Failure to follow the following caution may result in equipment
damage or improper operation. One of the two arrows on the
TXV part number label must point up when installed.
Install unit such that the refrigerant flow directions is in any of
the two allowed directions.
Indoor unit
connection
Arrows on TXV label pointing
upward and to the right
Fig. 10 -- Allowed TXV installation direction per label at-
To
indoor
unit
CAUTION
CAUTION
Outdoor unit
connection
Outdoor unit
connection
Arrows on TXV label pointing
upward and to the left
tached to TXV
Refrigerant
flow direction
Indoor unit
connection
To
outdoor
unit
Fig. 11 -- TXV Flow Direction
9
To
indoor
unit
Refrigerant Flow Direction
To
unit
outdoor
Liquid pipe
To
outdoor
unit
Gas pipe
c. Once location and flow direction is identified, connect
piping between indoor unit and TXV kit. Flexible
piping is recommended.
!
CAUTION
Failure to follow the following caution may result in equipment
damage or improper operation.
Insulate liquid and vapor pipes connecting to indoor and
outdoor units.
Liquid pipe
To
unit
indoor
Gas pipe
Refrigerant flow direction
Piping connection ports
(Gas side and liquid side)
Flexible pipings
(Field supplied)
Refrigerant flow
Flexible pipings
(Field supplied)
Direction
TXV Kit
Fig. 14 -- TXV Attached to Cassette Body
Flexible pipings
(Field supplied)
maximum length
TXV Kit
allowed: 12 - 18 in
Piping connection ports
(Gas side and liquid side)
Connection to
outdoor unit
Fig. 15 -- TXV Kit not Attached to Cassette Body
interconnection pipings
TXV Kit
Connect to
A150294
Fig. 12 -- Allowed Refrigerant Flow Direction
Refrigerant Flow Direction
Refrigerant Flow Direction
Fig. 13 -- Refrigerant Flow Direction Not Allowed
3. Install Suspension Bolts
a. Mark the spots on the ceiling where you want to install
the indoor unit.
b. Drill holes at the marking spots and then insert bolt
anchors. Use existing ceiling supports or construct a
suitable support. Use a hole--in-- anchor, sunken insert
for existing ceilings.
c. Depending on the type of ceiling, fix the threaded
hangers as shown in Fig. 16 and Fig. 17.
d. Insert the washers as shown in Fig. 16 and Fig. 17.
e. Remove the “T” bar in ceiling to facilitate installation.
See Fig. 17. If the “T” bar cannot be removed from the
ceiling, the unit may have to be tilted as shown in Fig.
18.
10
d. Screw the nuts to suspend the unit. Check the lower side
of indoor unit locates at position (10 to 12 mm) higher
than the lower surface of the ceiling. L is about half of
the screw length of the installation hook.
e. Adjust level of the unit by using level vial to make sure
the horizontal level of the main body is within
1°.
Nut
Washers
Threaded hangers
Wooden frame
Nut
Fig. 16 -- Attach Hangers to Ceiling
Fig. 17 -- Threaded Hangers and “T”Bar
Threaded Hangers
T-Bar
Supension Brackets
Threaded Hangers
T-Bar
Supension Brackets
Fig. 18 -- Positioning Unit in Ceiling
4. Hanging the Indoor Unit:
a. Screw double nuts to each suspension bolts making
space for hanging the indoor unit
b. Use a stacker to lift the unit to the installation site.
Washe r
Threaded hangers
Washe r
Nut
Nut
A07186
Threaded hangers
"T" bar
(to be removed)
A07187
T-Bar
A07188
2.3.2 Hang the indoor unit to the suspension bolts between two nuts.
mm
~12
0
1
Body
Shockproof cushion
Washe r
Hanging
screw bolt
Screw nut
L
Overhang part
Ceiling
Fig. 20 -- Suspension Bolt Details
5. Install the Drain Pipe
The cassette unit is equipped with a condensate pump. Use the
following steps to install the drain piping.
a. Remove the cover of the drain hose connection port.
b. Insert the flexible hose onto the drain hose port.
Securely fix the flexible hose to the indoor unit with a
pipe clamp.
c. Install the flexible hose onto the PVC water pipe (field
supplied, O.D. 1”) with PVC adhesive.
NOTES:
The drain pipe should be install within 200mm from the flexible
hose connection at the indoor unit.
To ensure correct condensate water flow, the pipe should have a
gradient of 2% without obstruction. see figure 21.
d. Make a trap of at least 2 in. (51 mm) in depth to prevent
unpleasant odors from reaching the room.
e. Insulate condensate pipe with condensation proof
material such as polyurethane, propylene, or neoprene
of 3/16 in. to 3/8 in. thickness.
Indoor unit
Drain hose connection port
Pipe clamp
Flexible hose
PVC water pipe
PVC adhesive
O.D.:Φ25)
Fig. 19 -- Positioning Unit
c. Hang the indoor unit to the suspension bolts between
two nuts.
A07185
11
<200mm
1.0-1.5m
Drain hose connection port
Lean over 2%
Max. 750mm
A150296
Fig. 21 -- Drain Pipe Connection
f. Drill a 2--3/4 in. (70 mm) hole in the wall with a 3/16
in. to 3/8 in. (4.8 -- 9.5 mm) slope toward the outside
(see Fig. 22). This hole will be used for the piping
(refrigerant and condensate) and control wiring
"
m)
3
÷
m 0
"
4/3-
8/0
2
7
(
Indoor
3/16"
(5
÷
10 m
f. Hang the hook behind the air inlet grille on to the panel.
g. Connect the display connector to the corresponding
plug on the main body (see Fig. 25).
Outdoor
÷
3/8"
m)
h. Close the air inlet grille.
i. Press the installation cover gently into the panel.
Fig. 22 -- Drilling for Connections
6. Install the panel:
a. Push the two grille switches simultaneously, then lift the
grille up and remove the air inlet grille. Take out the
covers from the 4 corners (see Fig. 23).
Grille switch
Fig. 23 -- Inlet Grille Removal
b. Align the corner marked with the piping and drain side
with the piping and drainage interfaces of the main
body.
c. Hang the panel to the hooks on the main body.
d. Tighten the screw evenly under the panel hook until the
thickness of the sponge between the main body and
panel is reduced to about 4~6mm. The edge of the panel
should contact the ceiling well.
e. Connect the swing motor connector to the
corresponding plug on the main body.
Installation
cover’s rope
Tap Screw
Slide the four sliders
in the corresponding
channel when installing
the cover
Fig. 25 -- Display Wire Connection
INSTALL OUTDOOR UNIT
The outdoor units can be installed on the ground, on the roof, or
mounted on a wall.
NOTE: Install the unit so that the coil does not face into
prevailing winds. If this is not possible and constant winds
above 25 mph are expected, use the accessory wind baffle. See
the installation instructions provided with the accessory kit.
Wind baffles should also be used on all units with accessory
low ambient temperature control.
Mounting on Ground
1. Mount unit on a solid level concrete pad.
2. If a heat pump is being installed, use a field-- provided snow
stand or ice rack where prolonged subfreezing temperatures
or heavy snow occurs.
3. Position unit so water or ice from roof does not fall directly
onto unit.
4. On cooling only units, an accessory stacking kit can be used
when units are to be stacked. See installation instructions
provided with the accessory kit.
Mounting on Roof
IMPORTANT: Mount unit on a level platform or frame at least 6
in. (152.4 mm) above roof surface. Isolate unit and tubing from
structure.
Piping port
Drain port
Screw
Cross-screwdriver
Hook panel
Fig. 24 -- Installing the Cassette Panel
!
CAUTION
PERSONALINJURYAND/OREQUIPMENT
DAMAGE HAZARD
Failure to follow this caution may result in personal injury
and/or equipment damage.
Be sure unit panels are securely in place prior to rigging.
1. Rig the unit. Keep the unit upright and lift u sing a sling.
Use cardboard or padding under the sling, and spreader bars
to prevent sling damage to the unit. See Fig. 26 for center of
gravity reference
2. Mount unit on a solid concrete pad or platform.
3. Isolate unit and piping from structure
4. If a heat pump is being installed, use a field-- provided snow
stand or ice rack where prolonged subfreezing temperatures
or heavy snow occurs.
5. On cooling only units, an accessory stacking kit can be used
when units are to be stacked. See installation instructions
provided with accessory kit.
12
Connection at Outdoor Unit
A07396
Fig. 26 -- Lifting Unit with Sling
Mounting Unit on Wall
The units can also be mounted on the wall using the accessory
mounting kit.
Complete Outdoor Refrigerant Connections
Follow the following general guidelines:
1. Use refrigerant grade field – supplied tubing.
Refer to Table 10 for the correct line sizes.
2. Do not use less than 10 ft (93.05 m) of interconnecting tubing.
!
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
To prevent damage to unit or service valves observe the
following:
S A brazing shield MUST be used.
S Wrap service valves with wet cloth or use a heat sink
material.
24AHA4/124ANS Units:
1. Assemble the connector tube to the factory supplied filter
drier by:
a. Braze the field supplied connector to the inlet of the
filter drier (see Fig. 27).
Fig. 27 -- Cooling Only Connector Tube Assembly
CAUTION
A09536
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
If any section of pipe is buried, there must be a 6 in. (152.4
mm) vertical rise to the valve connections on the outdoor
unit. If more than the recommended length is buried,
refrigerant may migrate to cooler, buried section during
extended periods of system shutdown. This causes
refrigerant slugging and could possibly damage the
compressor at start--up.
When more than 80 ft (24.4 m) of interconnecting tubing is used,
consult the Residential Long Line Application Guide for required
accessories.
3. Insulate both lines. A minimum of 1/2 inch foam pipe
insulation is recommended.
4. Run the refrigerant tubes as directly as possible and avoid
unnecessary turns and bends.
5. Suspend refrigerant tubes to avoid damage to insulation or
tubes so they do not transmit vibration to the structure.
6. When passing refrigerant tubes through the wall, seal the
opening so rain and insects do not enter the structure. Leave
some slack in refrigerant tubes between structure and outdoor unit to absorb vibration.
2. Braze the completed filter drier assembly to the liquid
service valve.
3. Connect the field supplied line set to the filter drier
assembly and the suction valve. A sweat connection is
required at the suction valve and flare connection is required
for the mixed phase line.
4. Insulate any exposed areas between the line set and the
liquid valve.
25HHA4/224ANS Units
1. Assemble the connector tubes to the factory supplied filter
drier by brazing the factory supplied flare connectors to the
inlet and outlet for the filter drier (see Fig. 28).
A09537
Fig. 28 -- Heat Pump Connector Tube Assembly
2. Remove the plastic cap from the liquid and sucti on service
valve on the heat pump outdoor unit and assemble the heating
piston and piston cap supplied with the outdoor unit as shown
in Fig. 29.
13
*
A07407
Fig. 29 -- Accurator (bypass type)
Metering Device Components
NOTE: The Tefl on seal on the piston should point towards the
liquid service valve. The size of the factory supplied piston might
have to be adjusted for long line applicat i ons (over 80 ft /24.4 m).
Refer to the Reside ntial Long Line Appli c at ion Guide for
additional information.
3. Attach the flare end of the filter drier assembly to the piston
cap (see Fig. 28).
4. Connect the field supplied line set to the filter drier
assemblyandtothesuctionvalve.
5. Insulate any exposed areas between filter drier and liquid
valve.
Complete Outdoor Power and Control Wiring
!
Failure to follow this warning could result in personal injury or
death.
The unit cabine t must have an uninterr upted or unbroken ground
to minimize personal injury if an elec t rica l fault should occur. The
ground may consist of ele ctri cal wire or metal conduit when
installed in accordance with existing electrical codes.
WARNING
Power Wiring
NOTE: The indoor and outdoor units are powered separately.
1. Mount indoor and outdoor power disconnect . The units are
factory wired for the voltage shown on the unit nameplate s.
The fused disconnect switc h must be provided within sight of
the unit, readily accessible, but out of reach of children.
Provisions for locking the disconnect switch on the OFF
(open) position is advisable. The disconnect switch must
comply with NEC and local codes. Protec t the unit and wiring
using only the recommended fuse/circuit breaker size (see
T ables 17 thru 20).
2. Run power wiring from electric panel to disconnect per
NEC and local codes.
3. Run power wiring from the disconnect switc h to indoor and
outdoor units. Use only minimum 75_C copper conduct ors
betwe en the disconne ct switch and the unit for field power
connection.
4. Route the field power wires through the conduit connection
opening in the unit side panel and connect in junction box
as shown in Fig 30 for outdoor units and the strain relief
bracket section for indoor units. The units and power wiring
must be grounded.
SINGLE-PHASE
CONN TO
DISCONNECT
PER NEC
THREE-PHASE
CONN TO
DISCONNECT
PER NEC
LEGEND
NEC -- National Electrical Code
-- Splice (field)
Field Wiring
Factory Wiring
GROUND LEAD
GROUND LEAD
Fig. 30 -- Line Power Connections
GROUNDING LUG
BLK
BLK
SINGLE-PHASE UNIT
BLK
BLU
YEL
GROUNDING LUG
THREE-PHASE UNIT
A08251
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
Unit failure as a result of operation on improper line voltage or
excessive phase imbalance constitutes abuse and may cause
damage to electrical components. Such operation could void
any applicable manufacturer warranty.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Before performing service or maintenance, be sure indoor
unit main power switch is turned OFF and indoor blower has
stopped.
Lock out and tag switch with a suitable warning label.
NOTE: Operating unit on improper line voltage constitutes
abuse and may affect the manufacturer’s warranty. DO NOT
install unit in a system where voltage may fluctuate above or
below permissible limits.
Control Wiring
Thermostat wires should be used for control wiring between the
indoor and outdoor units. A two conductor cable is required for the
cooling only units and a four conductor cable is required for heat
pumps. 18 AWG is recommended for lengths up to 50 ft. (15 m.),
and 16 AWG is recommended between lengths of 50 ft. (15 m.) to
100 ft. (30 m.).
The control circuit is 24 volts AC (minimum 40VA) supplied from
the indoor unit.
1. Make sure you have enough control wires to cover the
distance between the indoor and outdoor unit.
2. Route one end of the control wiring through the opening
provided in the unit side panel and connect to the control
terminal strip using either Fig. 31 for AC units or Fig. 32
for Heat Pump Units.
14
A150280
Fig. 31 -- 40MKCB**C/24AHA4 or 124ANS Connecting
Diagram
Strain Relief Bracket for Indoor Units
A strain relief is included within the indoor unit’s packaging. This
is required to be installed. The strain relief bracket and location to
where this should be affixed on the unit’s body is shown in Fig 33
and 34.
A150303
Fig. 33 -- Strain Relief Bracket
A150282
Fig. 32 -- 40MKQB**C/25HHA4 or 224ANS Connecting
Diagram
A150304
Fig. 34 -- Strain Relief Bracket Affixed to Cassette Body
LEGEND
FLA --- F u l l L o a d A m p s
H A C R --- Heating, Air Conditioning, Refrigeration
L R A --- Locked Ro tor A mps
N E C --- National Electrical Code
RLA---RatedLoadAmps(compressor)
*Permissible limits of the voltage range at which the unit will operate satisfactorily
**T i m e --- D e l a y f u s e .
Complies with 2007 requirements of ASHRAE Standards 90.1
V--Ph--Hz
Voltage RangeFanPower
Min (V)Max (V)FLA (A)Min Ckt Amp (A)
Max Fuse CB Amp
(A)
16
FAN
F
E
D
C
B
A
F
E
D
C
B
A
0
1
2
3
4
5
6
7
9
8
0~15
0
1
2
3
4
5
6
7
9
8
32~47
0
1
F
2
E
3
D
C
B
6
A
7
9
8
16~31
0
1
F
2
E
3
D
4
C
5
B
6
A
7
9
8
48~63
JR6
To CC M
Comm.Bus
10
E
Y
X
JR6
CN 23
4
5
C
Y
Legend:
................Model sp ecic fe ature
Live wire L1/Null line L2
CN 1:
Null line C
CN 17:
CN111 :Comp ressor si gnal
CN 8: Fa n
CN 6: Co nnectors
CN 33: R emote a larm inte rface
CN 23: R emote sw itch interface
CN 13: P ump interface
CN 14: S wing motor inter face
CN 5: Wa ter level switch in terface
CN 10: D isplay bo ard inter face
CN 3: Ce ntralized control system Interface
P 1 :Mag netism li nk interfa ce
CN 15: M otor interface
Ma gnetism link
T1: Room tempera ture sen sor
T2: Pipe tempera ture sen sor
XT1:3 po le termin al block
XT 2: 5 p ole term inal block
Notes:
1.To be wire d in acc ordance with Na tional
Electric N.E.C. and lo cal code s.
2.Use C opper c onductors only.
Use con ductors suitable for at le ast 75*C (167*F) .
3. If any of the o riginal wires, as supplie d
must be replace d, use t he sam e or equ ivalent w ire.
Fig. 35 -- 40MKCB**C wiring diagram
OUTDOOR UNIT SCHEMATIC DIAGRAM
interface
interface
Fig. 36 -- 24AHA4/124ANS Wiring Diagram
17
C
FAN
E
D
C
B
E
D
C
B
0
1
F
2
3
4
5
6
A
7
9
8
0~15
0
1
F
2
3
4
5
6
A
7
9
8
32~47
0
1
F
E
D
C
B
A
7
9
8
16~31
0
1
F
E
D
C
B
A
7
9
8
48~63
JR6
To CC M
Comm.Bus
10
E
Y
X
JR6
CN 23
2
3
4
5
6
C
O
R
2
3
4
5
6
Y
Legend:
................Model sp ecic fea ture
CN 1:
Live wire L1/Null l ine L2
CN 17:
Controls 24V sign al interfac e(R/C)
CN111 :
Signal in terface(Y /O)
CN 8:New fan
CN 6: Co nnectors
CN 33: R emote ala rm interfa ce
CN 23: R emote sw itch interface
CN 13: P ump interface
CN 14: S wing motor interfa ce
CN 5: Wa ter level s witch interface
CN 10: D isplay bo ard interf ace
CN 3: Ce ntralized control sy stem Inte rface
P 1 :Magn etism link interface
CN 15: M otor interface
Ma gnetism link
T1: Room tempera ture sens or
T2: Pipe temperature senso r
XT1:3 po le termina l block
XT2:5 po le termin al block
interface
interface
Notes:
1.To be wired in accor dance w ith National
Electric N.E.C. and loca l codes.
2.Use C opper co nductors only.
Use con ductors suitable for at lea st 75*C( 167*F).
3. If any of the o riginal wires, as supplied
must be replace d, use th e same or equiv alent wire.
Fig. 37 -- 40MKQB**C wiring diagram
OUTDOOR UNIT SCHEMATIC DIAGRAM
Fig. 38 -- 25HHA4/224ANS Wiring Diagram
18
Run Power Wiring for Indoor Unit
Be sure field wiring complies with local building codes and NEC,
and unit voltage is within limits shown in Tables 17 through 20.
Contact the local power company for correction of improper line
voltage.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and
tag switch with a suitable warning label.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
Unit failure as a result of operation on improper line voltage or
excessive phase imbalance constitutes abuse and may cause
damage to electrical components. Such operation could void
any applicable manufacturer warranty.
NOTE: Use copper wire only between disconnect switch(es)
and unit.
NOTE: Install a branch circuit disconnect of adequate size to
handle the unit starting current per NEC. Locate the
disconnect within sight of, and readily accessible to the unit,
per section 440--14 of NEC. Some codes allow the indoor unit
to share a disconnect with the outdoor unit if the disconnect
can be locked; check local codes before installing in this
manner.
The 40MKCB**C and 40MKQB**C units require their own
power supply.
1. Locate the indoor power supply.
2. Locate and install disconnect switch per NEC and local
codes.
3. Run power supply wiring to disconnect switch.
4. Run power wiring from disconnect switch to the cassette
control box. Use copper wire only.
5. If any accessories are being installed, refer to the individual
accessory instructions for guidance on wire routing at this
time.
WARNING
CAUTION
Install All Power, Interconnecting Wiring, Piping and
Drain Hose to Indoor
1. Run the control wiring from the outdoor unit through the
access hole in the wall and make sure you have enough wire
to reach the control box of the unit once hung from the
suspension bolts.
2. Complete all refrigerant piping connections.
a. Cut the extreme end of the tubes and remove any
copper shavings with a deburring blade.
b. Remove the flare nut from the “Flare” connection body
of the indoor unit and insert them into the pipes.
c. Make the flares to the pipe ends with the proper flaring
tool. The flare end must not have any burrs or
imperfections. The flared walls must be uniform (see
Fig. 39 and Fig. 40).
Unit
Fig. 39 -- Removing Burrs
L
Fig. 40 -- Flared Walls as Equal
3. It is recommended that flare connections be located on the
outside of the wall where the indoor unit is to be mounted. If
an extension pipe is required to facilitate this location, measure,
fabricat e and install the extension pipes to the indoor unit
before hanging the unit.
4. If piping connections are on the outside wall, pass the pipes
(refrigerant and drain) through the wall sleeve. Support the
unit away from the bottom using a tool or a piece of wood.
2
3
2
3
Fig. 41 -- Location of Piping, Hose, and Wiring
5. Route the power and control wiring through the back side
of the unit and to the control box area. If the wired remote is
to be used, perform any modifications required at this time.
Refer to the Accessory installation instructions.
19
L
A01799
A07200
A08364
6. Remove the control box cover and finish all indoor unit
t
wiring connections as shown on the wiring diagram or in
the accessory installation instructions. Replace the control
box cover.
7. Lubricate the end of the pipe and thread of the flare
connection with refrigerant oil. Tighten by hand and then
use two wrenches (see Fig. 42) to tighten all connections.
1
3
Adjustable wrench or torque wrench
Outdoor end
Indoor end
2
8. Disconnect charge hose from charge connection of the low
side service valve.
9. Fully open service valves B and A.
10. Securely tighten caps of service valves.
Outdoor Unit
Service Valve
Refrigerant
Low Side
A
High Side
B
Fig. 43 -- Service Valve
Indoor Uni
C
D
A07360
Manifold Gage
Fig. 42 -- Tightening Connections
START--UP
Preliminary Checks
1. Check condensate drainage system; on the opposite side of
the drain connection, insert a water bottle up into the fan
coil unit and fill the drain pan. Water must flow steadily; if
not, check the pipe slope or inspect for any pipe restrictions.
2. Make sure all wiring connections are correct and they are
tight.
3. Field electrical power source must agree with unit name
plate rating.
4. Check that all barriers, covers, and panels are in place.
Ensure that the filters and return --air grilles on the indoor
unit have been installed and that the discharge louvers are
positioned correctly.
5. All service valves must be closed.
6. On units with crankcase heaters, ensure belly--band heaters
are tight around the compressor.
Evacuate and Dehydrate the System
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
Never use the system compressor as a vacuum pump.
Using Vacuum Pump
1. Completely tighten flare nuts A, B, C, D, connect manifold
gage charge hose to a charge port of the low side service
valve (see Fig. 43).
2. Connect charge hose to vacuum pump.
3. Fully open the low side of manifold gage (see Fig. 44).
4. Start vacuum pump
5. Evacuate using either deep vacuum or triple evacuation
method.
6. After evacuation is complete, fully close the low side of
manifold gage and stop operation of vacuum pump.
7. The fact or y charge containe d in the outdoor unit is good for up
to 25 ft. (8 m) of line length. For refrigerant lines longer than
25 ft (8 m), add char ge up to the maximum allowabl e length
as specified in the Residential Long Line Application Guide.
CAUTION
A07201
500 microns
Low side valve
Charge hose
High side valve
Charge hose
Vacuum pump
Low side valve
A07361
Fig. 44 -- Manifold
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of
pulling a vacuum of 500 microns and a vacuum gage capable of
accurately measuring this vacuum depth. The deep vacuum method
is the most positive way of assuring a system is free of air and
liquid water (see Fig. 45).
5000
4500
4000
3500
3000
2500
2000
MICRONS
1500
1000
500
01234567
MINUTES
Fig. 45 -- Deep Vacuum Graph
LEAK IN
SYSTEM
VACUUM TIGHT
TOO WET
TIGHT
DRY SYSTEM
A95424
20
Triple Evacuation Method
The triple evacuation method should only be used when vacuum
pump is only capable of pumping down to 28 in. of mercury
vacuum and system does not contain any liquid water.
Refer to Fig. 46 and proceed as follows:
1. Pump system down to 28 in. of mercury and allow pump to
continue operating for an additional 15 minutes.
2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and
open until system pressure is 2 psig.
4. Close service valve and allow system to stand for 1 hr.
During this time, dry nitrogen will be able to diffuse
throughout the system absorbing moisture.
5. Repeat this procedure as indicated in Fig. 46. System will
then be free of any contaminants and water vapor.
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS DEEP VACUUM)
RELEASE CHARGE INTO SYSTEM
A95425
Fig. 46 -- Triple Evacuation Method
To Start the Unit:
1. If the outdoor unit is equipped with a crankcase heater, turn
on the indoor and outdoor disconnect switches to supply
power to the system 6 hours before starting the system.
2. Release charge into the system by opening (back--seating)
liquid and suction line service valves.
3. Set the wireless remote control or wired remote control
below ambient temperature. Operate the unit for 15 minutes.
4. Refer to Table 12 to determine if additional charge is
required. Also, if you have a long line application, refer to
the Residential Long Line Application Guide to determine
the additional charge that is required beyond 25 ft (7.6 m).
5. Charge should be added as liquid (not gas) slowly and
carefully to low side to avoid liquid slugging.
6. Start unit with operation test. In test mode the unit will run
in cooling and heating (on heat pumps) regardless if there is
demand or not.
Test Operation For CASSETTE
Perform test operation after completing gas leak and electrical
safety check. (See Fig. 47)
Manual button
OPERATION TIMERDEF./FAN ALARM
Fig. 47 -- Display Panel
1. Push the “ON/OFF” button on Remote Control to begin
testing.
NOTE: A protection feature prevents air conditioner from being
activated for approximately 3 to 4 minutes.
2. Push MODE button, select COOLING, HEATING, FAN
mode to check if all functions work correctly.
3. To run the test using the manual button in the indoor unit:
SPush the manual switch once to energize the unit.
The set conditions of manual operation are as follows:
· Preset set point: 76
· Fan speed: AUTO
· Discharge air direction: Pre--set position based on
operation in “Cool” or “Heat” mode
SSet manual switch to “OFF” (by pushing it twice again)
after finishing test operation.
NOTE: For Heat Pumps, follow the same procedure.
Drainage Test
a. Open the cover of water supply intake by turning and
pulling the cover.
b. Gradually insert a water bottle up into the fan coil unit
and fill drain pan.
c. Operate the unit under COOLING mode and check a
drain pump pumping (a time lag of 1 minute is allowed
before water flowing out depending on the length of the
drain pipe).
d. Check and confirm the water flows out through the drain
hose.
e. Check the drain water drops at the end of the drain pipe.
f. Make sure there is no water leak at the drainage
g. Reassemble the cover of water supply intake.
° F(24° C)
A150257
21
C
L
O
S
E
D
O
P
E
N
C
L
O
S
E
D
O
P
E
N
Drain pipe
connection port
Water intake
Cover
Stow tube
To Clean or Replace Air Filters
1. Place a plastic sheet on the floor to catch any water that may
spill from drain pan.
2. Slide filter out.
3. Vacuum clean or wash filter with soapy water. Rinse and let
air dry. If filter needs replacing, filters are available from a
local dealer.
Pump--down Procedure
The system may be pumped down in order to make repairs on the
low side without losing complete refrigerant charge.
1. Attach pressure gage to suction service valve gage port.
2. Front--seat the mixed phase line valve.
Cover
A150288
Fig. 48 -- Drainage Test Detail
Water must flow regularly with condensate pump energized. If not,
check the pipe slope or see if there are any pipe restrictions.
NOTE: The unit is equipped with a safety float switch to de--energize
the compres sor if the drain pan water level gets too high.
Service and maintenance
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death. Before installing, modifying, or servicing system,
main electrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch.
Lock out and tag switch with a suitable warning label.
Remove unit grille, filter, and condensate pan for cleaning,
lubricating, or replacing parts.
!
WARNING
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation. The unit coils hold only the
factory--designated amount of refrigerant.
Additional refrigerant may cause units to relieve pressure
through the compressor internal pressure relief valve (indicated
by a sudden rise of suction pressure) before suction pressure
reaches 20 psig.
If this occurs, shut off unit immediately then front--seat the
suction valve and remove and recover excess refrigerant
following accepted practices.
3. Start unit and run until suction pressure reaches 5 psig.
4. Shut unit off and front-- seat suction valve.
5. Depressurize low side of unit and recover refrigerant
following accepted practices.
Filter Drier
Whenever the filter drier is exposed to the atmosphere it must be
replaced. Only use factory specified liquid--line filter driers with
rated working pressures less than 600 psig.
NOTE: Do not install a suction-- line filter drier in the mixed phase
line.
Refrigerant Charging
Minimum Maintenance
1. Check, clean, or replace air filter each month or as required.
2. Check cooling coil, drain pan, condensate trap, and
condensate drain pan each cooling season for cleanliness.
Clean as necessary.
3. Check fan motor and wheel for cleanliness each heating and
cooling season.
4. Check electrical connections for tightness and controls for
proper operation each heating and cooling season. Service
as necessary.
!
WARNING
PERSONAL INJURY AND/OR EQUIPMENT DAMAGE
HAZARD
Failure to follow this warning could result in personal injury
and/or equipment damage. Wear safety glasses and gloves
when handling refrigerant. Do not overcharge system -- this
can cause compressor flooding.
All units are shipped with the refrigerant charge listed on
nameplate. Ensure charging conditions stated int his document and
the rating plate are followed.
NOTE:Do not vent or depressurize unit refrigerant to
atmosphere. Remove and recover refrigerant following
accepted practices.
22
TROUBLESHOOTING
Fault code
For ease of service, the indoor unit is equipped with diagnostic code display LEDs in the indoor units. This diagnostic display is a
combination of flashing LEDs on the display panel or the front of the unit. If possible, always check the diagnostic codes displayed on the
indoor unit. The diagnostic codes displayed in the indoor unit are listed in Table 21. Once a failure occurs with the indoor unit in operation,
the green LED on the indoor unit flashes at intervals of 0.5 seconds. The fault code is deduced from the number of times the green LED
flashes, blocking unit operation. Between one flash cycle and the next one, a pause of 3 to 4 seconds elapses.
Table 21 – Fault Codes
NO.
Open or short circuit of T1
1
temperature sensor
Open or short circuit of T2
2
temperature sensor
3Indoor EEPROM
4Water--level alarmXXX
5Refrigerant leakage detection
NOTE: O (on) X(off) ☆(flash at 5Hz) ◎(flash at 0.5Hz)
MalfunctionRunning lampTimer lamp
X
☆
☆
XXXE3
☆☆
☆
XX
Defrosting
lamp
XXE2
XXE7
Alarm lamp
☆
☆
Using the Emergency Button
The Emergency button is for use by a qualified service technician only. The Emergency button is for use when the room controller is
inoperative. Use a small screwdriver to press the emergency button (see Fig. 47).
Manual operation can be accessed by pressing manual button on the display panel. Press the manual button repeatedly to change modes as
follows:
SOnce = AUTO mode [heat, cool or fan, 24
STwice = COOLING mode [switches to AUTO mode after 30 minutes (mainly used for trial operation)]
SThree times = OFF
°C and auto fan speed.]
Display
(digital tube)
E8
EC
23
Table 22 – Troubleshooting
PROBLEMPOSSIBLE CAUSESOLUTION
Unit not energizedCheck the main power connection.
Compressor and Fan of
the Outdoor Unit Will Not
Start
Compressor Will Not Start,
But Outdoor Fan is
Operating
Compressor Stops Due to
Over--- temperature
Compressor Runs
Continuously
F r e q u e n t I c e --- B u i l d --- U p
on Outdoor Coil
Discharge Pressure T oo
High
Discharge Pressure T oo
Low
Suction Pressure Too High
Suction Pressure Too Low
Outdoor Fan Cycling Due
to Over---Temperature
Protection
Main switch is set to OFFCheckandputittoONposition.
Main switch fuses are bl ownReplace fuses.
Compressor cycling protection is onWait for 3 minutes.
Main power voltage is too lowCheck and set to the correct voltage.
Electrical connections are too loose or are wrongCheck and tighten or correct connections.
Electrical connections of compressor are loose or wrongCheck and tighten or repair compressor.
Compressor burnt out; seized or protection device on
Wrong refrigerant charge in u nit (excessive or low) or air or other
non---condensable gasses in the circuit
Main voltage is too high or too lowCheck voltage setting and adjust if necessary.
Condenser coil obstructedRemove obstruction.
Outdoor fan offCheck cause and resume operation or repair.
Wrong indoor unit thermistorsReplace thermistors.
Refrigerant circuit cloggedCheck and remove obstructions.
Reversing valve faulty on heat pump modelsReplace reversing valve.
Expansion device clogged or covered with ice
Unit selected is too smal l for application requirements
Indoor temperature setting too low or too highCheck temperature setting.
Outdoor unit fan faultyReplace outdoor fan.
Air or other non---condensable gasses in the circuit
Obstructions at air intake or dirty indoor unit filtersRemove obstruction and/or clean filter.
Outdoor fan is stoppedCheck cause and repair.
Outdoor coil dirty or obstructedClean or remove obstructions.
Condenser fan faultyReplace condenser fan.
Indoor temperature setting too low or too highCheck temperature setting.
Air or other non---condensable gasses in the circuit
Indoor temperature setting too high or too lowCheck temperature setting.
Outdoor coil dirty or obstructedClean or remove obstructions.
Indoor unit air filter dirtyClean filter.
Indoor temperature setting too high or too lowCheck temperature setting.
Reversing valve faulty or internal leakReplace reversing valve.
Indoor temperature setting too high or too lowCheck temperature setting.
Evaporator coil covered with ice
Expansion device or suction line cloggedCheck and repair.
Outdoor fan does not stop during defrost periodsCheck electrical parts.
Electrical connection looseCheck connections.
Fan motor burn outReplace.
Fan bearing seizedCheck and repair.
Expansion device clogged or covered with ice
NOTE: For additional diagnostic information, refer to the “Service Manual”.
Check for the cause and repl ace compressor if
necessar y.
Drain refrigerant, evacuate and recharge.
CAUTION: Do not vent refrigerant to the atmosphere;
use refrigerant recovery equipment.
Drain refrigerant, evacuate and recharge.
CAUTION: Do not vent refrigerant to the atmosphere;
use refrigerant recovery equipment.
Contact a qualified service technician for a system
evaluation.
Drain refrigerant, evacuate and recharge.
CAUTION: Do not vent refrigerant to the atmosphere;
use refrigerant recovery equipment.
Drain refrigerant, evacuate and recharge.
CAUTION: Do not vent refrigerant to the atmosphere;
use refrigerant recovery equipment.
Air circulation on the evaporator not sufficient; check
and repair.
Drain refrigerant, evacuate and replace.
CAUTION: Do not vent refrigerant to the atmosphere;
use refrigerant recovery equipment.
Copyright 2015 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231Edition Da te:07/15
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
24
C a t a l o g N o : 4 0 M K C B --- C --- 0 1 S I
Replaces: NEW
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.