Carrier 38MAQB09 Series, 40MBQB09F Series, 40MBQB12F Series, 38MAQB12 Series Product Data

40MB*F / 38MAQ Floor Console Ductless Split System Sizes 09 to 12
Product Data
INDUSTRY LEADING FEATURES / BENEFITS
A PERFECT BALANCE BETWEEN BUDGET LIMITS, ENERGY SAVINGS AND COMFORT.
The 38/40MBF series ductless split systems are a matched combination of an outdoor condensing unit and an indoor fan coil unit connected only by refrigerant tubing and wires.
The fan coil is mounted on the floor, against the wall. This selection of fan coils permits creative solutions to design problems such as:
S Add--ons to current space (an office or family room
addition)
S Special space requirements
S When changes in the load cannot be handled by the
existing system.
S When adding air conditioning to spaces that are heated
by hydronic or electric heat and have no ductwork.
S Historical renovations or any application where
preserving the look of the original structure is essential.
The ideal compliment to your ducted system when it is impractical or prohibitively expensive to use ductwork.
These compact indoor fan coil units take up very little space in the room and do not obstruct windows. The fan coils are attractively styled to blend with most room decors. Advanced system components incorporate innovative technology to provide reliable cooling performance at low sound levels.
LOW SOUND LEVELS
When noise is a concern, the ductless split systems are the answer. The indoor units are whisper quiet. There are no compressors indoors, either in the conditioned space or directly over it, and there is none of the noise usually generated by air being forced through ductwork.
When sound ordinances and proximity to neighbors demand quiet operation, the 38MAQ unit is the right choice: The advanced, horizontal airflow design distributes air more evenly over the coil.
SECURE OPERATION
If security is an issue, outdoor and indoor units are connected only by refrigerant piping and wiring to prevent intruders from crawling through ductwork. In addition, since 38MAQ units can be installed close to an outside wall, coils are protected from vandals and severe weather.
FAST INSTALLATION
This compact ductless split system is simple to install. A mounting bracket is standard with the indoor units and only wire and piping need to be run between indoor and outdoor units. These units are fast and easy to install ensuring minimal disruption to customers in the home or workplace. This makes the 38MAQ/40MB*F ductless split systems the equipment of choice, especially in retrofit situations.
SIMPLE SERVICING AND MAINTENANCE
Removing the top panel on outdoor units provides immediate access to the control compartment, providing a service technician access to check unit operation. In addition, the draw--thru design of the outdoor section means that dirt accumulates on the outside surface of the coil. Coils can be cleaned quickly from the inside using a pressure hose and detergent.
On all indoor units, service and maintenance expense is reduced due to easy--to--use cleanable filters. In addition, these floor console systems have extensive self--diagnostics to assist in troubleshooting.
BUILT--IN RELIABILITY
Ductless split system indoor and outdoor units are designed to provide years of trouble--free operation.
The floor console indoor units include protection against freeze--up and high evaporator temperatures on heat pumps.
The condensing units on heat pumps are protected by a three minute time delay before the compressor will start the over--current protection and the high temperature protection.
INDIVIDUAL ROOM COMFORT
Maximum comfort is provided because each space can be controlled individually based on usage pattern. The air sweep feature provided permits optimal room air mixing to eliminate hot and cold spots for occupant comfort. In addition, year--round comfort can be provided with heat pumps.
ECONOMICAL OPERATION
The ductless split system design allows individual room heating or cooling when required. There is no need to run large supply--air fans or chilled water pumps to handle a few spaces with unique load patterns. In addition, because air is moved only in the space required, no energy is wasted moving air through ducts.
EASY--TO--USE CONTROLS
The floor console units have microprocessor--based controls to provide the ultimate in comfort and efficiency. The user friendly wireless remote control provides the interface between user and the unit.
ACCESSORIES
Customizing these ductless split systems to your application is easily accomplished.
Adding a condensate pump accessory to the floor console fan coil provides installation flexibility.
OPTIONAL WIRED CONTROLLER
AGENCY LISTINGS
All systems are listed with AHRI (Air Conditioning, Heating & Refrigeration Institute), and ETL.
2
MODEL NUMBER NOMENCLATURE
INDOOR UNIT
BQ
40= FAN COIL UNIT
MB =MODEL
SYSTEM TYPE Q =HEATPUMP
40 MB
--- ---
F
309
VOLTAGE 3 = 208/230--- 1---60
B=ALL SIZES
NOMINAL C APACITY 09 --- 3 / 4 T O N 12 --- 1 T O N
38 MA
38 = OUTDOOR UNIT
MA =MODEL
SYSTEM TYPE Q =HEATPUMP
MAXIMUM NUMBER OF FAN COIL UNITS THAT CAN BE CONNECTED TO THE OUTDOOR UNIT B=1:1
OUTDOOR UNIT
Q
NOT USED
INDOOR FAN COIL TYPE
F= FLOOR CONSOLE
B
--- ---
---
309
VOLTAGE 3 = 208/230--- 1---60
NOT USED
NOMINAL C APACITY 09 --- 3 / 4 T O N 12 --- 1 T O N
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program For verification of certification for individual products, go to www.ahridirectory.org.
UNIT TYPE
--- = OUTDOOR UNIT
3
STANDARD FEAT URES AND ACCESSORIES
Ease Of Installation
Mounting Brackets S Low Voltage Controls S
Comfort Features
Microprocessor Controls S Wired Remote Control A Wireless Remote Control S Automatic Horizontal Air Sweep S Air Direction Control S Auto Restart Function S Cold Blow Protection On Heat Pumps S Freeze Protection Mode On Heat Pumps S Turb o Mod e S Silence Mode S Auto Changeover On Heat Pumps S
Follow Me S
Energy Saving Features
Sleep Mode S Stop/Start Timer S
46° F Heating Mode (Heating Setback)
Safety And Reliability
3MinuteTimeDelayForCompressor S Over Current Protection For Compressor S Indoor Coil Freeze Protection S Indoor Coil High Temp Protection in Heating Mode S Condenser High Temp Protection in Cooling Mode S
Ease Of Service And Maintenance
Cleanable Filters S Diagnostics S Liquid Line Pressure Taps S
Application Flexibility
Condensate Pumps A
Crankcase Heater S Basepan Heater S
Legend
SStandard A Accessory
S
INDOOR UNITS
On floor console fan coils, the condensate pump has a lift capability of 12 ft. (3.6 m) on the discharge side with the pump mounted in the fan coil or 6 ft. (1.8 m) on the suction side if the pump is remote mounted. The pump is recommended when adequate drain line pitch cannot be provided, or when the condensate must move up to exit.
OUTDOOR UNITS
Crankcase Heater
Standard on all unit sizes. Heater clamps around compressor oil stump.
Factory Installed Basepan Heater
Fig. 1 – Condensate Pump Accessory
ACCESSORIES
ORDERING NO. DESCRIPTION FOR MODELS
5 3 D S --- 90 0 --- --- --- 11 8 Condensate Pump (230v) All Sizes
KSACN0101AAA Wired Remote Control All Sizes
5 3 D S --- 90 0 --- --- --- 00 8
5 3 D S --- 90 0 --- --- --- 08 9
Insulated 25’
Line Set --- 1/4“ x 1/2”
Insulated 25’
Line Set --- 1/4” x 3/8”
MB Sizes 12, 18
MB Size 09
4
DIMENSIONS -- INDOOR
Fig. 2 – Indoor Unit
UNIT SIZE 9 12
Height in (mm) 8.27 (210) 8.27 (210)
Width in (mm) 27.56 (700) 27.56 (700) Depth in (mm) 23.62 (600) 23.62 (600)
W e i g h t --- N e t Lb (kg.) 32.41 (14.7) 32.41 (14.7)
DIMENSIONS -- OUTDOOR
Fig. 3 – Outdoor unit
MODEL W in (mm) D in (mm) H in (mm) L1 in (mm) L2 in (mm)
9K/12K 32.0 (810) 12.2 (310) 22.0 (558) 20.9 (530) 11.4 (290) 82.5 (37.4)
OPERATING-
WEIGHT lb (kg)
5
CLEARANCES -- I NDOOR
Fig. 4 – Indoor Unit Clearance
CLEARANCES -- OUTDOOR
A
D
UNIT
A 24 (609) B 24 (609) C 24 (609) D 4 (101) E 4 (101)
B
Air-outlet
Fig. 5 – Clearances Outdoor
Air-inlet
E
C
Minimum Value
in. (mm)
6
SPECIFICATIONS
SIZE 9 12
SYSTEM
Performance
Controls
Operating
Range
Piping
Refrigerant
Outdoor Coil
Indoor Coil
Compressor
Electrical
Outdoor
Indoor
Outdoor Model 3 8 MA Q B 0 9 --- --- --- 3 3 8 MA Q B 1 2 --- --- --- 3 Indoor Model 40MBQB09F--- --- 3 40MBQB12F--- --- 3 Energy Star YES YES Cooling Rated Capacity Btu/h 9,000 12,000 Cooling Cap. Range Min --- Max Btu/h 3,500~ 11,000 4,000~ 13,000 SEER 20.0 20.5 EER 12.5 12.5 Heating Rated Capacity Btu/h 10,000 12,000 Heating Cap. Range Min --- Max Btu/h 4,500~ 11,500 5,000~ 13,500 HSPF 10 10 COP W/W 3.35 3.58 Wireless Remote Controller (° F/° C Convertible) Standard Standard Wired Remote Controller (° F/° C Convertible) Optional Optional Cooling Outdoor DB Min --- Max °F ---4~ 122 --- 4~ 122
Heating Outdoor DB Min --- Max °F --- 4~ 86 --- 4~ 86 Total Piping Length Ft. 82 82 Piping Lift Pipe Connection Size --- Liquid In. 1/4 1/4 Pipe Connection Size --- Suction In. 3/8 1/2 Type R410A R410A Design Pressure PSIG 550 550 Metering Device EEV EEV Charge Lb. 2.76 2.76 Face Area Sq. Ft. 9.2 9.2 No. Rows 2 2 Fins per inch 21 21 Circuits 4 4 Face Area (sq. ft.) Sq. Ft. 2.1 2.1 No. Rows 2 2 Fins per inch 19 19 Circuits 2 2 Type Hermetic Rotary DC Inverter Compressor Model ASM98D1UFZA ASM108D1UFZA Oil Type VG74 VG74 Oil Charge Fl. Oz. 12.5 12.5 Rated Current RLA 5.3 5.7 Voltage, Phase, Cycle V/Ph/Hz 208/230---1 ---60 208/230---1 ---60 Power Supply Indoor unit powered from outdoor unit MCA A. 15 15 M O C P --- F u s e R a t i n g A. 15 15 Unit Width In. 31.9 31.9 Unit Height In. 22.0 22.0 Unit Depth In. 12.2 12.2 Net Weight Lbs. 82.5 82.5 Airflow CFM 945 945 Sound Pressure dB(A) 56 56 Unit Width In. 27.6 27.6 Unit Height In. 8.3 8.3 Unit Depth In. 23.6 23.6 Net Weight Lbs. 32.4 32.4 Number of Fan Speeds 3 3 Airflow (lowest to highest) CFM 220/250/280 220/250/280 Sound Pressure (lowest to highest) dB(A) 37/38/41 34/41/45
*
Ft. 32 32
*Condensing unit above or below the indoor unit
7
COOLING PERFORMANCE DATA
Model
Indoor
Conditions DB
69.8F(21C) 59F(15C)
75.2F(24C) 62.6F(17C)
09
(208 --- 230V)
80.6F(27C) 66.2F(19C)
89.6F(32C) 73.4F(23C)
69.8F(21C) 59F(15C)
75.2F(24C) 62.6F(17C)
12
(208 --- 230V)
80.6F(27C) 66.2F(19C)
89.6F(32C) 73.4F(23C)
LEGEND
DB - Dry Bulb WB - Wet Bulb TC - Total Net Cooling Capacity (1000 Btu/hour) SC - Sensible Capacity (1000 Btu/hour) Input - Total Power (kW)
COOLING OUTDOOR CONDITIONS (DB)
Indoor
Conditions WB
77F(25C) 86F(30C) 95F(35C) 104F(40C) 113F(45C) 122F(50C)
TC 7.41 7.82 9.73 8.34 6.12 5.1 SC 6.64 6.69 8.18 7.37 4.36 3.74
Input 0.35 0.54 0.81 0.8 0.75 0.75
TC 7.76 9.16 9.89 8.62 6.92 5.83 SC 3.58 8.11 6.27 5.52 4.85 4.29
Input 0.35 0.54 0.81 0.8 0.75 0.75
TC 8.21 9.22 10.41 9.27 7.32 6 SC 7.39 5.88 8.22 7.79 5.11 4.37
Input 0.35 0.75 0.82 0.81 0.75 0.75
TC 8.41 9.72 11.59 10.22 8.82 7.51 SC 3.68 5.76 6.9 6.2 5.55 5
Input 0.36 0.56 0.83 0.82 0.76 0.77
TC 8.21 11.75 11.42 9 7.85 6.68 SC 7.06 9.05 8.68 7.38 6.42 5.58
Input 0.38 0.8 1.04 0.87 0.82 0.81
TC 8.42 11.84 12.01 9.35 8.32 7.34 SC 7.28 8.69 8.66 7.62 6.53 5.81
Input 0.57 0.94 1.25 1.27 0.98 0.94
TC 8.81 11.95 12.23 9.69 8.87 7.95 SC 7.49 8.32 8.63 7.85 6.64 6.04
Input 0.39 0.75 1.06 0.89 0.85 0.82
TC 9.01 12.15 12.43 9.89 9.07 8.15 SC 7.7 8.53 8.84 8.06 6.85 6.25
Input 0.4 0.97 1.3 1.34 0.92 0.85
HEATING PERFORMANCE DATA
Model
09
(208--- 230V)
12
(208--- 230V)
LEGEND
DB - Dry Bulb TC - Total Net Heating Capacity (1000 Btu/hour) Input - Total Power (kW)
HEATING OUTDOOR CONDITIONS (DB)
Conditions (DB)
59F(15C)
64.4F(18C)
69F(20.5C)
71.6F(22C)
59F(15C)
64.4F(18C)
69F(20.5C)
71.6F(22C)
Indoor
TC 11.18 11.08 10.89 10.65 9.87 9.11 8.27 6.71 6.21 5.80 Input 0.73 0.79 1.04 1.01 0.96 0.9 0.84 0.8 0.79 0.78 COP 4.49 4.11 3.07 3.09 3.01 2.97 2.88 2.46 2.30 2.18
TC 11.06 10.82 10.65 10.54 9.63 8.84 8.01 5.46 5.02 4.60 Input 0.78 0.8 1.08 1.03 0.98 0.94 0.9 0.82 0.81 0.80 COP 4.15 3.96 2.89 3.00 2.88 2.76 2.61 1.95 1.82 1.69
TC 10.84 10.55 10.48 10.32 9.43 8.55 7.95 4.29 4.11 4.02 Input 0.8 0.81 1.11 1.05 1 0.98 0.96 0.84 0.83 0.82 COP 3.97 3.82 2.77 2.88 2.76 2.56 2.43 1.50 1.45 1.44
TC 10.62 10.32 10.21 10.11 9.23 8.41 7.89 4.11 3.86 3.60 Input 0.82 0.83 1.15 1.07 1.02 1.02 0.92 0.86 0.84 0.84 COP 3.79 3.64 2.60 2.77 2.65 2.42 2.51 1.40 1.35 1.26
TC 11.78 12.72 12.42 11.32 10.4 9.54 8.9 5.75 5.41 4.82 Input 0.79 1.01 1.05 1.1 1.02 1 0.98 0.83 0.8 0.78 COP 4.37 3.69 3.47 3.02 2.99 2.80 2.66 2.03 1.98 1.81
TC 12.05 12.65 12.32 11.34 10.32 9.32 8.81 6.14 5.77 5.25 Input 0.83 1.37 1.4 1.26 1.22 1.27 1.01 0.91 0.86 0.82 COP 4.25 2.71 2.58 2.64 2.48 2.15 2.56 1.98 1.97 1.88
TC 12.27 12.6 12.12 11.32 10.21 9.12 8.43 6.49 6.05 5.45 Input 0.83 1.1 1.12 1.19 1.19 1.25 1.03 0.98 0.92 0.86 COP 4.33 3.36 3.17 2.79 2.51 2.14 2.40 1.94 1.93 1.86
TC 11.14 12.41 12.01 11.21 10.01 9.02 8.21 6.01 5.71 5.60 Input 0.85 1.15 1.16 1.21 1.23 1.31 1.05 1 0.98 0.94 COP 3.84 3.16 3.03 2.71 2.38 2.02 2.29 1.76 1.71 1.75
53.6F(12C) 44.6F(7C) 39.2F(4C) 32F(0C) 24.8F(--- 4C) 19.4F( --- 7C) 17F(---8C) 5F( --- 15C) 0F( --- 17C) --- 4 F ( --- 2 0 C )
8
APPLICATION DATA
UNIT SELECTION
Select equipment to either match or is slightly less than the anticipated peak load. This provides better humidity control, fewer unit cycles, and less part--load operation.
For units used in spaces with high sensible loads, base equipment selection on unit sensible load, not on total anticipated load. Adjust for anticipated room wet bulb temperature to avoid undersizing equipment.
UNIT MOUNTING (INDOOR)
Refer to unit Installation Instructions for further details. Unit leveling -- For reliable operation, units should be level in all
planes. Clearance -- Provide adequate clearance for airflow as shown in
Fig. 4. Unit location -- Select a location which will provide the best air
circulation for the room. These units should be positioned on the floor, against the wall for
best air circulation. The unit return and discharge should not be obstructed by furniture, curtains, or anything which may cause unit short cycling or air recirculation. Place the unit in the middle of the selected wall (if possible). Use an outside wall, if available, to make piping easier, and place the unit so it faces the normal location of room occupants.
UNIT MOUNTING (OUTDOOR)
Refer to unit Installation Instructions for further details. Unit leveling -- For reliable operation, units should be level in all
planes. Clearance -- Minimum clearance, (see Fig. 5), must be provided
for airflow. The condensing units are designed for free-- blow application. Air inlets and outlets should not be restricted.
Unit location -- A location which is convenient to installation and not exposed to strong wind.
A location which can bear the weight of outdoor unit and where the outdoor unit can be mounted in a level position.
Do not install the indoor or outdoor units in a location with special environmental conditions. For those applications, contact your ductless representative.
MOUNTING TEMPLATE
Refer to unit Installation Instructions for further details.
The fan coil units are furnished with mounting to mark the location of the wiring, and refrigeration line hole locations.
SUPPORT
Adequat e support must be provided to support the weight of all fan coils. Refer to the Physical Data section for fan coil weights, and the base unit dimensiona l drawi ngs for the location of mounting brackets.
SYSTEM OPERATING CONDITIONS
OPERATING R ANGE
Min / Max ° F (° C)
Cooling Heating
Outdoor DB --- 4 / 122 (---20 / 50) --- 4 / 86 ( --- 20 / 30)
Indoor DB 63 / 90 (17 / 32) 32 / 86 (0 / 30)
Indoor WB 59 / 84 (15 / 29)
NON--- OPERATING TEMPERATURE RANGE
Indoor/Outdoor DB 32 / 86 (0 / 30)
Min / Max ° F (° C)
NOTE: Refe r ence the Product Installation Instruc tions for more information.
METERING DEVICES
The outdoor unit has an electronic expansion valve to manage the refrigerant flow of the fan coil connected.
DRAIN CONNECTIONS
Install drains to meet local sanitation codes. If adequate gravity drainage cannot be provided, the unit should be equipped with an accessory condensate pump. The floor console fan coil unit condensate pumps have a maximum lift of 10’ (3.05 m) for 9k and 12k units and 25’ (7.62 m) for 18k and 30k units.
See the physical dimension tables for drain sizes.
NOTE: Floor console fan coil units have internal condensate traps. A trap is not required.
REFRIGERANT LINES
General refrigerant line sizing:
1. The outdoor units are shipped with a full charge of R410A refrigerant. All charges, line sizing, and capacities are based on runs of 25 ft. (7.6 m). For runs over 25 ft. (7.6 m), consult long--line section on this page for the proper charge adjustments.
2. Refrigerant lines should not be buried in the ground. If it is necessary to bury the lines, not more than 36 -- in (914 mm) should be buried. Provide a minimum 6--in (152 mm) vertical rise to the service valves to prevent refrigerant migration.
3. Both lines must be insulated. Use a minimum of 1/2--in. (12.7 mm) thick insulation. Closed--cell insulation is recommended in all long-- line applications.
4. Special consideration should be given to isolating the interconnecting tubing from the building structure. Isolate the tubing so that vibration or noise is not transmitted into the structure.
Long Line Applications
1. No change in line sizing is required.
2. Add refrigerant per table below.
ADDITIONAL CHARGE TABLE
UNIT SIZE
9
12
TOTAL LINE
LENGTH ft
Min Max
10 82 None 0.16
ADDITIONAL CHARGE,
oz/ft. ft (m)
10 --- 25
(3 --- 8)
> 2 5 --- 8 2
(8 --- 25)
9
WIRING
All wires must be sized per NEC (National Electrical Code) or CEC (Canadian Electrical Code) and local codes. Use the Electrical Data table MCA (minimum circuit amps) and MOCP (maximum over current protection) to correctly size the wires and the disconnect fuse or breakers respectively. Per caution note, only Stranded copper conductors with a 600 volt rating and double insulated copper wire must be used.
NOTE: The use of BX cable is not recommended.
Recommended Connection Method for Power and Communication Wiring
Power and Communication
The main power is supplied to the outdoor unit. The field supplied 14/3 power/communication wiring from the outdoor unit to the indoor unit consists of four (4) wires and provides the power for the indoor unit. Two wires are high voltage AC power, one is communication wiring and the other is a ground wire.
Recommended Connection Method for Power and Communication Wiring (To communication wiring PowerWiring:
The main power is supplied to the outdoor unit. The field supplied power wiring from the outdoor unit to the indoor unit consists of three (3) wires and provides the power for the indoor unit. Two wires are high voltage AC power and one is a ground wire. To minimize voltage drop, the factory recommended wire size is 14/2 stranded with a ground.
Communication Wiring:
A separate shielded stranded copper conductor only, with a minimum 600 volt rating and double insulated copper wire, must be used as the communication wire from the outdoor unit to the indoor unit. Please use a separate shielded 16GA stranded control wire.
-­Wiring:
minimize
interference)
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
S Be sure to comply with local codes while running wire
from indoor unit to outdoor unit.
S Every wire must be connected firmly. Loose wiring
may cause terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
S No wire should be allowed to touch refrigerant tubing,
compressor or any moving parts.
S Disconnecting means must be provided and shall be
located within sight and readily accessible from the air conditioner.
S Connecting cable with conduit shall be routed through
hole in the conduit panel.
CAUTION
CONTROL SYSTEM
The unit is equipped with a microprocessor control to perform two functions:
1. Provide safety for the system
2. Control the system and provide optimum levels of comfort and efficiency
The main microprocessor is located on the control board of the fan coil unit (outdoor units have a microprocessor too) with thermistors located in the fan coil air inlet and on the indoor coil. Heat pump units have a thermistor on the outdoor coil. These thermistors monitor the system operation to maintain the unit within acceptable parameters and control the operating mode.
WIRELESS REMOTE CONTROL
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
S Wires should be sized based on NEC and local codes.
S Use copper conductors only with a 600 volt rating and
double insulated copper wire.
CAUTION
Fig. 6 – Wireless remote control
1. A wireless remote control is supplied for system operation for system operation of all floor console units.
2. Each battery operated wireless (infrared) remote control may be used to control more than one unit.
WIRED REMOTE CONTROL (OPTIONAL)
P/N KSACN0101AAA
1. Optional wired remote controller used for system operation of all floor console units.
2. Kit includes a wired remote controller and a connecting cable.
3. Connect with wire terminal between remote controller and indoor unit.
4. Display in _For_C and temperature increments every 1_Forevery1_C.
10
AIR FLOW DATA
SYSTEM SIZ E 9 12
High 280 280
Indoor (CFM)
Outdoor (CFM) 945 945
Medium 250 250
Low 220 220
SOUND PRESSURE
SYSTEM SIZ E 9 12
Cooling operation Indoor Sound
Pressure
Heating operation Indoor Sound
Pressure
Outdoor sound pressure level dBa 55.5 56
dBa (L/M/H) 37/38/41 34/41/45
dBa (L/M/H) 37/38/41 34/41/45
SOUND POWER
SYSTEM SIZ E 9 12
Cooling operation Indoor Sound
Power
Heating operation Indoor Sound
Power
Outdoor sound power level dBa 65 66
dBa (L/M/H) 46/47/50 44/51/55
dBa (L/M/H) 46/47/50 44/51/55
ELECTRICAL DATA
UNIT
OPER. VOLTAGE
SIZE
12 5.7
9
MAX / MIN*
253 / 187 208--- 230/1/60
COMPRESSOR OUTDOOR FAN INDOOR FAN
V --- P H --- H Z RLA V --- P H --- H Z FLA HP W V --- P H --- H Z FLA HP W
5.3
208---230/ 1/ 60
3 0.053 40
3 0.053 40 0.21 0.027 20
208---230/ 1/ 60
0.21 0.027 20
MCA
MAX FUSE CB
AMP
15 15
15 15
*Permissible limits of the voltage range at which the unit will operate satisfactorily
LEGEND FLA -- Full Load Amps LRA -- Locked Rotor Amps MCA -- Minimum Circuit Amps RLA -- Rated Load Amps
11
FAN AND MOTOR SPECIFICATIONS
SYSTEM SIZ E
material AS AS
Indoor fan
Indoor fan motor
Outdoor fan
Outdoor fan motor
Type LX --- 370*80*8- --7JN LX --- 370*80*8 --- 7JN
Diameter inch 14.6 14.6
Height inch 3.15 3.15
Model R D --- 2 8 0 --- 20 --- 8 A R D --- 2 8 0 --- 20 --- 8 A
Type DC DC
Phase 3 3
FLA 0.21 0.21
Insulation class E E
Safe class IPX0 IPX0
Input W 66.6 66.6
Output W 20 20
Range of current Amps 0.21±10% 0.21±10%
Rated current Amps 0.21 0.21
Rated HP HP 0.027 0.027
Speed
Rated RPM
rev/ min
rev/ min
Max. input W 66.6 66.6
material AS AS
Type ZL --- 421*117*8 --- 3K ZL --- 421*117*8 --- 3K
Diameter inch 16.6 16.6
Height inch 4.6 4.6
Model W Z D K 4 0 --- 3 8 G --- W --- 1 W ZD K 4 0 --- 38 G --- W --- 1
Phase DC DC
FLA 3 3
Type 0.42 0.42
Insulation class E E
Safe class IPX0 IPX0
Input W 46 46
Output W 40 40
Range of current Amps 0.42±10% 0.42±10%
Rated current Amps 0.42 0.42
Rated HP HP 0.053 0.053
Speed rev/min 800/700/600 800/700/600
Rated RPM rev/min 900 900
Max. input W 46 46
9K 12K
(208--- 230V) (208--- 230V)
730/680/580/520 730/680/580/520
1062 1062
12
WIRING DIAGRAM
Fig. 7 – Wiring Diagram -- Sizes 9 and 12
INDOOR UNIT CONTROL BOARD
CODE PAR T N A ME
CN1 Input: 230VAC High volta ge Connection of the terminal CN2 ‘Input: 230VAC High voltage Connection of the terminal CN3 Output: 24VDC Between CN2 Connection of the S signal CN6 Output: 12VDC Connection of the Lower outlet swing motor CN7 Output: 5VDC Connect ion of the Room and Pipe temperature CN10 Output: 12VDC Connection of the Display board CN13 Output: 12VDC Connection of the Upper outlet swing mot or CN15 Output: 1 -- -5VDC Connection of t he Switch board CN16 Output: 320VDC Connection of the Fan high voltage CN20 Output: 5VDC Connection of the Net module CN23 Output: 1 -- -12VDC Connectio n of the Remote switch
INDOOR UNIT
OUTDOOR UNIT CONTROL BOARD
CODE PAR T N A ME
CN31 Output:Pin5&6(12V) Pin1--- Pin4:Pulse waveform,(0--- 12V) CN21 Input:Pin3--- 4 (3.3V) Pin2(0V),Pin1,Pin5(0--- 3.3V) CN22 Input:Pin1 (3.3V) Pin2 (0--- 3.3V) CN37 Output: 230VAC High volta ge C N 9 --- 1 , C N 3 2 --- 1 Output: Connectio n of the high voltage CN1 Input:230VAC High voltage CN2 Input:230 VAC High voltage CN3 Connectio n to the earth CN16 Output: Connection of the high voltage CN26,CN27 Output: High voltage for 4 --- way control CN7 Output: Pulse(0--- 320VDC) for DC FAN UVW Output: Pulse(0--- 320VDC) for COMPRESSOR
OUTDOOR UNIT
13
GUIDE SPECIFICATIONS
INDOOR WALL--MOUNTED FLOOR CONSOLE DUCTLESS UNITS
Size Range: 3/4 to 1 Ton Nominal Cooling and Heating Capacity
Carrier Model Number: 40MB*F
PART 1 -- GENERAL
1.01 System Description
Indoor, wall--mounted floor console, direct--expansion fan coils are matched with cooling only or heat pump outdoor unit .
1.02 Agency Listings
Unit shall be rated per AHRI Standards 210/240 and listed in the AHRI directory as a matched system.
1.03 Delivery, Storage, And Handling
Units shall be stored and handled per unit manufacturer’s recommendations.
1.04 Warranty (For Inclusion By Specifying Engineer)
PART 2 -- PRODUCTS
2.01 Equipment
A. General:
Indoor, direct-- expansion, floor--mounted fan coil. Unit shall be complete with cooling/heating coil, fan, fan motor, piping connectors, electrical controls, microprocessor control system, and integral temperature sensing. Unit shall be furnished with integral mounting bracket and mounting hardware.
B. Unit Cabinet:
Cabinet discharge and inlet grilles shall be attractively styled, high--impact polystyrene. Cabinet shall be fully insulated for improved thermal and acoustic performance.
C. Fans:
1. Fan shall be tangential direct-- drive blower type with air intake in the center of the unit and discharge at the top and bottom front. Automatic, motor--driven vertical air sweep shall be provided standard.
2. Air sweep operation shall be user selectable. The vertical sweep may be adjusted (using the remote control) and the horizontal air direction may be set manually.
D. Coil:
Coil shall be copper tube with aluminum fins and galvanized steel tube sheets. Fins shall be bonded to the tubes by mechanical expansion and specially blue hydrophilic pre--coated for enhanced wet--ability. A drip pan under the coil shall have a drain connection for hose attachment to remove condensate. Condensate pan shall have internal trap.
E. Motors:
Motors shall be open drip--proof, permanently lubricated ball bearing with inherent overload protection. Fan motors shall be 4--speed.
F. Co n trols :
Controls shall consist of a microprocessor-- based control system which shall control space temperature, determine optimum fan speed, and run self diagnostics. The temperature control range shall be from 62_Fto86_F(17_Cto30_C) in increments of 1_F or 1_C, and have 46_F Heating Mode (Heating Setback). The wireless remote controller shall have the ability to act as the temperature sensing location for room comfort.
The unit shall have the following functions as a minimum:
1. An automatic restart after power failure at the same operating conditions as at failure.
2. A timer function to provide a minimum 24--hour timer cycle for system Auto Start/Stop.
3. Temperature--sensing controls shall sense return air temperature.
4. Indoor coil freeze protection.
5. Wireless infrared remote control to enter set points and operating conditions.
6. Automatic air sweep control to provide on or off activation of air sweep louvers.
7. Dehumidification mode shall provide increased latent removal capability by modulating system operation and set point temperature.
8. Fan--only operation to provide room air circulation when no cooling is required.
9. Diagnostics shall provide continuous checks of unit operation and warn of possible malfunctions. Error messages shall be displayed at the unit.
10. Fan speed control shall be user-- selectable: high, medium, low, or microprocessor controlled automatic operation during all operating modes.
11. Automatic heating-- to --cooling changeover in heat pump mode. Control shall include deadband to prevent rapid mode cycling between heating and cooling.
12. Indoor coil high temperature protection shall be provided to detect excessive indoor discharge temperature when unit is in heat pump mode.
G. Filters:
Unit shall have filter track with factory--supplied cleanable filters.
H. Electrical Requirements:
Indoor fan motor to operate on 208--230V as specified. Power is supplied from the outdoor unit.
I. Operating Characteristics:
The 40MB*F system shall have a minimum SEER (Seasonal Energy Efficiency Ratio) and HSPF at AHRI conditions, as listed on the specifications table.
J. Refrigerant Lines:
All units should have refrigerant lines that can be oriented to connect from the left, right or back of unit. Both refrigerant lines need to be insulated.
K. Special Features (Field Installed):
1. Condensate Pump:
-- The condensate pump shall remove condensate from the drain pan when gravity drainage cannot be used. Pump shall be designed for quiet operation. Pump shall consist of two parts: an internal reservoir/sensor assembly, and a remote sound--shielded pump assembly. A liquid level sensor in the reservoir shall stop cooling operation if the liquid level in the reservoir is unacceptable.
14
HORIZONTAL DISCHARGE DUCTLESS OUTDOOR UNITS
PART 1 -- GENERAL
1.01 System Description
A. Outdoor air--cooled split system compressor sections suitable
for on--the--ground, rooftop, wall hung or balcony mounting. Units shall consist of a rotary compressor, an air--cooled coil, propeller--type draw-- through outdoor fan, reversing valve (HP), accumulator (HP units), metering device(s), and control box. Units shall discharge air horizontally as shown on the contract drawings. Units shall function as the outdoor component of an air--to--air cooling only, or heat pump system.
B. Units shall be used in a refrigeration circuit matched to ductless
cooling only or heat pump fan coil units.
1.02 Agency Listings
A. Unit construction shall comply with ANSI/ASHRAE 15, latest
revision, and with the NEC. B. Units shall be evaluated in accordance with UL standard 1995.
C. Units shall be listed in the CEC directory.
D. Unit cabinet shall be capable of withstanding 500--hour salt
spray test per Federal Test Standard No. 141 (method 6061).
E. Air--cooled condenser coils shall be leak tested at 550 psig.
1.03 Delivery, Storage, And Handling
Units shall be shipped in one piece and shall be stored and handled per unit manufacturer’s recommendations.
1.04 Warranty (For Inclusion By Specifying Engineer)
PART 2 -- PRODUCTS
2.01 Equipment
A. General:
Factory assembled, single piece, air-- cooled outdoor unit. Contained within the unit enclosure shall be all factory wiring, piping, controls, and the compressor.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel, bonderized and coated with a baked--enamel finish on inside and outside.
2. Unit access panels shall be removable with minimal screws and shall provide full access to the compressor, fan, and control components.
3. Outdoor compartment shall be isolated and have an acoustic lining to assure quiet operation.
C. Fans:
1. Outdoor fans shall be direct--drive propeller type, and shall discharge air horizontally. Fans shall draw air through the outdoor coil.
2. Outdoor fan motors shall be totally enclosed, single phase motors with class E insulation and permanently lubricated ball bearings. Motor shall be protected by internal thermal overload protection.
3. Shaft shall have inherent corrosion resistance.
4. Fan blades shall be non metallic and shall be statically and dynamically balanced.
5. Outdoor fan openings shall be equipped with PVC metal/mesh coated protection grille over fan.
D. Compressor:
1. Compressor shall be fully hermetic rotary type.
GUIDE SPECIFICATIONS
Size Range: 3/4 to 1 Ton Nominal Cooling and Heating Capacity
Carrier Model Number: 38MAQ
2. Compressor shall be equipped with oil system, operating oil charge, and motor. Internal overloads shall protect the compressor from over--temperature and over--current.
3. Motor shall be NEMA rated class E, suitable for operation in a refrigerant atmosphere.
4. Compressor assembly shall be installed on rubber vibration isolators.
5. Compressors shall be single phase.
E. Outdoor Coil:
Coil shall be constructed of aluminum fins and specially blue hydrophilic pre--coated for enhanced wet-- ability mechanically bonded to seamless copper tubes, which are cleaned, dehydrated, and sealed.
F. Refrigeration Components:
Refrigerant circuit components shall include brass external liquid line service valve with service gage port connections, suction line service valve with service gage connection port, service gage port connections on compressor suction and discharge lines with Schrader type fittings with brass caps, accumulator, reversing valve.
G. Controls and Safeties:
Operating controls and safeties shall be factory selected, assembled, and tested. The minimum control functions shall include the following:
1. Controls:
a. A time delay control sequence is provided standard through
the fan coil board.
b. Automatic outdoor--fan motor protection.
2. Safeties:
a. System diagnostics.
b. Compressor motor current and temperature overload
protection.
c. Outdoor fan failure protection.
H. Electrical Requirements:
1. Unit shall operate on single--phase, 60 Hz power at 208--230v as specified.
2. Unit electrical power shall be a single point connection.
3. Unit Control voltage to the indoor fan coil shall be 0--15V DC.
4. All power and control wiring must be installed per NEC and all local electrical codes.
5. Unit shall have high and low--voltage terminal block connections.
15
Copyright 2015 Carrier Corp D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Da te: 11/15
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: 38 --- 40MBF --- 03PD
R e p l a c e s: 3 8 --- 4 0 M B F --- 0 2 P D
16
Loading...