40MB*D / 38MAQ / 38MBQ Ducted Split System Sizes 09 to 48

Product Data

INDUSTRY LEADING

FEATURES / BENEFITS

A PERFECT BALANCE BETWEEN BUDGET LIMITS, ENERGY SAVINGS AND COMFORT.

The 40MBD series ducted split systems are a matched combination of an outdoor condensing unit and an indoor fan coil unit connected only by refrigerant tubing and wires.

The fan coil is mounted in the ceiling. This selection of fan coils permits creative solutions to design problems such as:

S Addons to current space (an office or family room addition)

S Special space requirements

S When changes in the load cannot be handled by the existing system.

S Historical renovations or any application where preserving the look of the original structure is essential.

These compact indoor fan coil units take up very little space above the ceiling. Advanced system components incorporate innovative technology to provide reliable cooling performance at low sound levels.

LOW SOUND LEVELS

When sound ordinances and proximity to neighbors demand quiet operation, the 38MAQ unit is the right choice: The advanced, horizontal airflow design distributes air more evenly over the coil.

SECURE OPERATION

If security is an issue, outdoor and indoor units are connected only by refrigerant piping and wiring to prevent intruders from crawling through ductwork. In addition, since 38MAQ units can be installed close to an outside wall, coils are protected from vandals and severe weather.

FAST INSTALLATION

This compact ducted split system is simple to install. A mounting bracket and duct work is needed for the indoor units, and only wire and piping need to be run between indoor and outdoor units. These units are fast and easy to install ensuring minimal disruption to customers in the home or workplace. This makes the 40MBD / 38MAQ / 38MBQ ducted split systems the equipment of choice, especially in retrofit situations.

SIMPLE SERVICING AND MAINTENANCE

Removing the top panel on outdoor units provides immediate access to the control compartment, providing a service technician access to check unit operation. In addition, the drawthru design of the outdoor section means that dirt accumulates on the outside surface of the coil. Coils can be cleaned quickly from the inside using a pressure hose and detergent.

On all indoor units, service and maintenance expense is reduced due to easy accessible service panels. In addition, these ducted systems have extensive selfdiagnostics to assist in troubleshooting.

BUILTIN RELIABILITY

Ducted split system indoor and outdoor units are designed to provide years of troublefree operation.

The ducted indoor units include protection against freezeup and high evaporator temperatures on heat pumps.

The condensing units on heat pumps are protected by a three minute time delay before the compressor will start the overcurrent protection and the high temperature protection.

INDIVIDUAL ROOM COMFORT

Maximum comfort is provided because each space can be controlled individually based on usage pattern. The air sweep feature provided permits optimal room air mixing to eliminate hot and cold spots for occupant comfort. In addition, yearround comfort can be provided with heat pumps.

ECONOMICAL OPERATION

The ducted split system design allows individual or multiroom heating or cooling when required. There is no need to run large supplyair fans or chilled water pumps to handle a few spaces with unique load patterns.

EASYTO- USE CONTROLS

The ducted units have microprocessorbased controls to provide the ultimate in comfort and efficiency. The user friendly wired and wireless remote control provides the interface between user and the unit.

CONDENSATE PUMP

Factory installed condensate pump on the ducted fan coil provides installation flexibility.

STANDARD WIRED CONTROLLER

AGENCY LISTINGS

All systems are listed with AHRI (Air Conditioning, Heating & Refrigeration Institute), and ETL.

2

MODEL NUMBER NOMENCLATURE

INDOOR UNIT

 

40

 

MB

Q

B

09

 

D

- -

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40= FAN COIL UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VOLTAGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MB = MODEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 = 208/230- 1- 60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SYSTEM TYPE

Q = HEAT PUMP

MAXIMUM NUMBER OF FAN COIL UNITS THAT

CAN BE CONNECTED TO THE OUTDOOR UNIT

B=1:1

 

NOT USED

 

 

 

 

 

 

 

NOMINAL CAPACITY

 

 

09

-

3/4 TON

 

 

12

-

1 TON

 

 

18

-

1- 1/2 TONS

 

INDOOR FAN COIL TYPE

24

-

2 TONS

 

36

- 3 TONS

 

D = DUCTED

48

-

4 TONS

 

 

OUTDOOR UNIT

 

 

 

38

 

MA

Q

B

09

 

-

- -

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38 = OUTDOOR UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MA = MODEL SIZES 0924

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VOLTAGE

 

 

MB = MODEL SIZES 3648

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 = 208/230- 1- 60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SYSTEM TYPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q = HEAT PUMP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAXIMUM NUMBER OF FAN COIL UNITS THAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAN BE CONNECTED TO THE OUTDOOR UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOT USED

 

 

B=1:1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOMINAL CAPACITY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

09

-

3/4 TON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

-

1 TON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

-

1- 1/2 TONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT TYPE

 

24

-

2 TONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36

- 3 TONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- = OUTDOOR UNIT

 

48

-

4 TONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program For verification

of certification for individual products, go to www.ahridirectory.org.

3

STANDARD FEATURES AND ACCESSORIES

Ease Of Installation

 

 

Mounting Brackets

S

 

Low Voltage Controls

S

Comfort Features

 

 

Microprocessor Controls

S

 

Wired Remote Control

S

 

Wireless Remote Control

S

 

Automatic Horizontal Air Sweep

S

 

Air Direction Control

S

 

Auto Restart Function

S

 

Cold Blow Protection On Heat Pumps

S

 

Freeze Protection Mode On Heat Pumps

S

 

Turbo Mode

S

 

Silence Mode

S

 

Auto Changeover On Heat Pumps

S

 

Follow Me

S

Energy Saving Features

 

 

Sleep Mode

S

 

Stop/Start Timer

S

 

46° F Heating Mode (Heating Setback)

S

Safety And Reliability

 

 

3 Minute Time Delay For Compressor

S

 

Over Current Protection For Compressor

S

 

Indoor Coil Freeze Protection

S

 

Indoor Coil High Temp Protection in Heating Mode

S

 

Condenser High Temp Protection in Cooling Mode

S

Ease Of Service And Maintenance

 

 

Cleanable Filters

S

 

Diagnostics

S

 

Liquid Line Pressure Taps

S

Application Flexibility

 

 

Condensate Pumps

S

 

Crankcase Heater

S

Legend

 

S

Standard

 

A

Accessory

 

OUTDOOR UNITS

Crankcase Heater

Standard on all unit sizes. Heater clamps around compressor oil stump.

4

DIMENSIONS - INDOOR

Fig. 1 – Indoor unit

 

 

Outline dimensions

 

Air outlet opening size

Air return opening size

Hanger

Refrigerant Pipe Locations

 

 

 

Brackets

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Size

A

 

B

C

 

D

E

F

G

H

I

J

K

L

M

H1

H2

W1

W2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

27.6

 

8.2

25

 

22.4

2.5 (65)

19.4

1.3 (35)

4.6

23.4

7.8

3.1 (80)

29.1

13.8

4.7

5.6

3.7 (95)

5.9

(700)

 

(210)

(635)

 

(570)

(493)

(119)

(595)

(200)

(740)

(350)

(120)

(143)

(150)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

27.6

 

8.2

25

 

22.4

2.5 (65)

19.4

1.3 (35)

4.6

23.4

7.8

3.1 (80)

29.1

13.8

4.7

5.6

3.7 (95)

5.9

(700)

 

(210)

(635)

 

(570)

(493)

(119)

(595)

(200)

(740)

(350)

(120)

(143)

(150)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

36.2

 

8.2

25

 

22.4

2.5 (65)

19.4

1.3 (35)

4.6

32.0

7.8

3.1 (80)

37.8

13.8

4.7

5.6

3.7 (95)

5.9

(920)

 

(210)

(635)

 

(570)

(493)

(119)

(815)

(200)

(960)

(350)

(120)

(143)

(150)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24

36.2

 

10.6

25

 

22.4

2.5 (65)

19.4

1.3 (35)

7.0

32.0

10.2

0.7 (20)

37.8

13.8

4.7

5.6

3.7 (95)

5.9

(920)

 

(270)

(635)

 

(570)

(493)

(179)

(815)

(260)

(960)

(350)

(120)

(143)

(150)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36

44.8

 

10.6

30.5

 

27.9

2.5 (65)

36.7

1.3 (35)

7.0

40.7

10.2

1.7 (45)

48.8

19.7

4.7

5.6

3.7 (95)

5.9

(1140)

 

(270)

(775)

 

(710)

(933)

(179)

(1035)

(260)

(1240)

(500)

(120)

(143)

(150)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

48

47.2

 

11.8

34.1

 

31.4

3.1 (80)

38.1

1.5 (40)

8.0

43.0

11.3

1.7 (45)

48.8

19.7

6.9

7.8

6.1

8.3

(1200)

 

(300)

(865)

 

(800)

(968)

(204)

(1094)

(288)

(1240)

(500)

(175)

(198)

(155)

(210)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

DIMENSIONS - OUTDOOR

Fig. 2 – Outdoor unit

Unit Size

W in (mm)

D in (mm)

H in (mm)

L1 in (mm)

L2 in (mm)

Operating

Weight lb (kg)

 

 

 

 

 

 

9K

31.8(810)

12.2(310)

21.9(558)

21.6(549)

12.8(325)

82.4(37.4)

12K

31.8(810)

12.2(310)

21.9(558)

21.6(549)

12.8(325)

82.4(37.4)

 

 

 

 

 

 

 

18K

33.2(845)

12.6(320)

27.5(700)

22.0(560)

13.1(405)

102.5(46.5)

 

 

 

 

 

 

 

24K

37.2(945)

15.5(395)

31.8(810)

25.2(640)

15.9(405)

137.5(62.4)

 

 

 

 

 

 

 

36K

37.2(945)

15.5(395)

31.8(810)

25.2(640)

15.9(405)

137.5(62.4)

 

 

 

 

 

 

 

48K

36.93(938)

15.4(392)

53.9(1369)

24.9(634)

15.9(404)

220(100)

 

 

 

 

 

 

 

6

Carrier 40MBQB09D3 User Manual

CLEARANCES - INDOOR

7.874in(200mm)

11.811in(300mm)

 

23.622in x 23.622in(600mm x 600mm)

Fig. 3 – Indoor Unit Clearance

CLEARANCES - OUTDOOR

A

Air-inlet

E

D

B

C

 

 

Air-outlet

 

Fig. 4 – Clearances Outdoor

UNIT

Minimum Value

in. (mm)

 

A

24 (609)

B

24 (609)

C

24 (609)

D

4 (101)

E

4 (101)

7

SPECIFICATIONS

 

Size

 

9

12

 

18

24

36

48

 

 

 

 

 

 

 

 

 

 

System

Outdoor Model

 

38MAQB09---3

38MAQB12---3

 

38MAQB18---3

38MAQB24---3

38MBQB36---3

38MBQB48---3

 

 

 

 

 

 

 

 

 

Indoor Model

 

40MBQB09D--3

40MBQB12D--3

 

40MBQB18D--3

40MBQB24D--3

40MBQB36D--3

40MBQB48D--3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Energy Star

 

YES

YES

 

YES

YES

NO

NO

 

 

 

 

 

 

 

 

 

 

 

Cooling Rated Capacity

Btu/h

9,000

11,000

 

16,000

23,000

36,000

48,000

 

 

 

 

 

 

 

 

 

 

 

Cooling Cap. Range Min - Max

Btu/h

3,500~11,000

4,000~13,000

 

4,500~18,000

5,500~24,500

8,500~38,000

9,000~50,000

 

 

 

 

 

 

 

 

 

 

 

SEER

 

19.0

18.0

 

18.5

19.0

15.5

16.5

 

 

 

 

 

 

 

 

 

 

Performance

EER

 

13.5

12.5

 

12.5

12.5

8.5

8.2

 

 

 

 

 

 

 

 

 

 

 

Heating Rated Capacity

Btu/h

10,000

11,800

 

18,000

24,400

38,000

50,000

 

 

 

 

 

 

 

 

 

 

 

Heating Cap. Range Min - Max

Btu/h

4,500~11,500

5,000~13,500

 

5,500~19,000

6,000~26,000

9,500~50,000

10,000~55,000

 

 

 

 

 

 

 

 

 

 

 

HSPF

 

9.6

9.0

 

9.6

10.5

10.5

10.0

 

 

 

 

 

 

 

 

 

 

Controls

Wireless Remote Controller (°F/°C Convertible)

 

 

 

Standard

 

 

 

 

 

 

 

 

 

 

 

Wired Remote Controller (°F/°C Convertible)

 

 

 

Standard

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating

Cooling Outdoor DB Min - Max

°F

4~122

4~122

 

4~122

4~122

4~122

4~122

Range

Heating Outdoor DB Min - Max

°F

4~86

4~86

 

4~86

4~86

4~86

4~86

 

 

 

 

 

 

 

 

 

 

 

Total Piping Length

Ft.

82

82

 

98

98

213

213

 

 

 

 

 

 

 

 

 

 

Piping

Piping Lift*

Ft.

32

32

 

65

65

98

98

Pipe Connection Size - Liquid

In.

1/4

1/4

 

1/4

3/8

3/8

3/8

 

 

 

 

 

 

 

 

 

 

 

 

 

Pipe Connection Size - Suction

In.

3/8

1/2

 

1/2

5/8

5/8

5/8

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

 

R410A

 

 

 

 

 

 

 

 

 

 

 

Refrigerant

Design Pressure

PSIG

550

550

 

550

550

550

550

 

 

 

 

 

 

 

 

 

Metering Device

 

 

 

 

Capillary Tube in Outdoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Charge

Lbs.

2.76

2.76

 

4.19

5.18

7.5

9.48

 

 

 

 

 

 

 

 

 

 

 

Face Area

Sq. Ft.

9.2

9.2

 

16.0

21.1

8.2

14.1

 

 

 

 

 

 

 

 

 

 

Outdoor

No. Rows

 

2

2

 

2

3

2.6

2.0

coil

Fins per inch

 

21

21

 

18

18

17

17.0

 

 

 

 

 

 

 

 

 

 

 

Circuits

 

4

4

 

6

8

6

10.0

 

 

 

 

 

 

 

 

 

 

 

Face Area

Sq. Ft.

1.4

1.4

 

1.4

2.0

3.5

4.2

 

 

 

 

 

 

 

 

 

 

Indoor Coil

No. Rows

 

3

3

 

3

4

4

4

 

 

 

 

 

 

 

 

 

Fins per inch

 

16

16

 

16

16

16

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuits

 

4

4

 

4

6

8

8

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

Hermetic Rotary DC Inverter Compressor

 

 

 

 

 

 

 

 

 

 

 

 

Model

 

ASM98D1UFZA

ASM108D1UFZA

 

ASM135D23UFZ

DA250S2C-30MT

TNB306FPGMC-L

MNB36FAAMC-L

 

 

 

 

 

 

 

 

 

 

Compressor

Oil Type

 

VG74

VG74

 

VG74

VG74

FV50S

FV50S

 

 

 

 

 

 

 

 

 

 

 

Oil Charge

Fl. Oz.

12.5

12.5

 

15.2

27.7

36.2

47.3

 

 

 

 

 

 

 

 

 

 

 

Rated Current

RLA

5.3

5.7

 

7.3

8.8

13.5

13.5

 

 

 

 

 

 

 

 

 

 

 

Voltage, Phase, Cycle

V/Ph/Hz

208/230-1-60

208/230-1-60

 

208/230-1-60

208/230-1-60

208/230-1-60

208/230-1-60

 

 

 

 

 

 

 

 

 

 

Electrical

Power Supply

 

 

 

 

Indoor unit powered from outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

MCA

A.

15

15

 

15

15

30

35

 

 

 

 

 

 

 

 

 

 

 

MOCP - Fuse Rating

A.

15

15

 

20

25

50

55

 

 

 

 

 

 

 

 

 

 

 

Unit Width

In.

31.9

31.9

 

33.3

37.2

37.2

36.9

 

 

 

 

 

 

 

 

 

 

 

Unit Height

In.

22.0

22.0

 

27.6

31.9

31.9

53.9

 

 

 

 

 

 

 

 

 

 

Outdoor

Unit Depth

In.

12.2

12.2

 

12.6

15.6

15.6

15.4

 

 

 

 

 

 

 

 

 

Net Weight

Lbs.

82.4

82.4

 

120.5

134.0

160.9

220.0

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

CFM

945

945

 

1050

1390

2940

4240

 

 

 

 

 

 

 

 

 

 

 

Sound Pressure

dB(A)

56

56

 

59

62

65

65

 

 

 

 

 

 

 

 

 

 

 

Unit Width

In.

27.6

27.6

 

36.2

36.2

44.9

47.2

 

 

 

 

 

 

 

 

 

 

 

Unit Height

In.

8.3

8.3

 

8.3

10.6

10.6

11.8

 

 

 

 

 

 

 

 

 

 

 

Unit Depth

In.

25.0

25.0

 

25.0

25.0

30.5

34.1

 

 

 

 

 

 

 

 

 

 

Indoor

Net Weight

Lbs.

39.9

39.9

 

50.7

57.3

77.2

99.2

 

 

 

 

 

 

 

 

 

Number of Fan Speeds

 

3

3

 

3

3

3

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow (lowest to highest)

CFM

290/340/380

290/340/380

 

400/440/480

590/650/810

680/940/1180

940/1180/1470

 

 

 

 

 

 

 

 

 

 

 

Sound Pressure (lowest to highest)

dB(A)

30/33/36

30/34/38

 

34/37/38

43/45/48

46/50/52

41/44/46

 

 

 

 

 

 

 

 

 

 

 

Max Static Pressure

In.WG.

0.16

0.16

 

0.28

0.28

0.32

0.40

 

 

 

 

 

 

 

 

 

 

8