Carrier 40MBQB09D3, 40MBQB18C3 Specifications

38MG / 40MA / 40MB Multi- Zone Ductless Split System Size 18k, 27k, 36k and 48k
Product Data
INDUSTRY LEADING FEATURES / BENEFITS
AN INEXPENSIVE AND CREATIVE SOLUTION TO DESIGN PROBLEMS.
The different styles of indoor units can be mounted in several locations to accommodate the application. This selection of fan coils permits inexpensive and creative solutions to design problems such as:
S When adding air conditioning to spaces that are heated
by hydronic or electric heat and have no ductwork.
S Historical renovations or any application where
preserving the look of the original structure is essential.
S Commercial add- on jobs where the existing air
conditioning system cannot be stretched.
These compact indoor fan coil units take up very little space in the room and do not obstruct windows. The fan coils are attractively styled to blend with most room decors.
Advanced system components incorporate innovative technology to provide reliable cooling and heating performance at low sound levels.
INVERTER TECHNOLOGY
The inverter driven compressor is designed to run at various input power frequencies (Hz) which controls the motor speed of the compressor.
Even Temperature – The control package, including the inverter, monitors outdoor and indoor temperatures as they relate to the selected indoor set point and adjusts the speed of the compressor to match the load and keep the system operating continuously rather than cycling and creating temperature swings. This translates to higher comfort levels for the occupants.
Rapid Pull Down/Warm-Up – Comfort is increased by the ability to the inverter system to ramp up the compressor speed enabling the system to reach the user selected room temperature set point quicker.
Humidity Control – Running the system for longer periods and continuously varying the compressor speed will enhance the humidity control.
INDIVIDUAL ROOM COMFORT
Maximum comfort is provided because each space can be controlled individually based on the usage pattern. The air sweep feature provided permits optimal room mixing to eliminate hot and cold spots for the occupant comfort.
LOW SOUND LEVELS
When noise is a concern, ductless split systems are the answer. The indoor units are whisper quiet. There are no compressors indoors, either in the conditioned space or directly over it, and there is none of the noise usually generated by air being forced through ductwork.
When sound ordinances and proximity to neighbors demand quiet operation, the 38MG unit is the right choice. With the inverter technology, these units run at lower speeds most of the time resulting in reduced sound levels.
FAST INSTALLATION
This compact ductless split system is simple to install. A mounting bracket is included with the indoor units and only wires and piping need to be run between the indoor and outdoor units. These units are fast and easy to install ensuring minimal disruption to customers in homes or workplace. This makes the 38MG / 40MA / 40MB systems the equipment of choice for retrofit applications.
SIMPLE SERVICING AND MAINTENANCE
Removing the top panel of the outdoor unit provides immediate access to the control compartment, providing the service technician access to the diagnostic LEDs to facilitate the troubleshooting process. In addition, the draw- thru design of the outdoor unit means that dirt accumulates on the outside surface of the coil. Coils can be cleaned quickly from the inside using a pressure hose and detergent.
On the indoor units, service and maintenance expense is reduced due to the permanent easy to clean filters. Also, error codes are displayed on the front panel to alert the user to certain system malfunctions
BUILT- IN RELIABILITY
Ductless split system indoor and outdoor units are designed to provide years of trouble- free operation.
Both the indoor and outdoor units are well protected. Wheneve r the micr opr ocessor detects abnormal conditions, the unit will stop and an error code is displa yed.
Inverter systems provide additional reliability due to soft start. This refers to the ability of the inverter to start the compressor motor using reduced voltage and reduced current. This feature is beneficial from an electrical standpoint (eliminates current spikes) as well as an overall reliability standpoint due to reduced stress on all associated system components.
INVERTER TECHNOLOGY – ENHANCED ECONOMICAL OPERATION
Ductless systems are inherently economical to operate. Individual rooms are heated or cooled only when required, and since the air is delivered directly to the space, there is no need to use additional energy to move the air in the ductwork. This economical operation is enhanced further when the inverter system output matches the load resulting in a more efficient system.
EASY- TO-USE CONTROLS
The multi-zone systems have microprocessor-based controls to provide the ultimate in comfort and efficiency. The user friendly wired and wireless remote controls provide the interface between the user and the unit.
SECURE OPERATION
If security is an issue, outdoor and indoor units are connected only by refrigerant piping and wiring to prevent intruders from crawling through ductwork or wall openings. In addition, since the 38MG can be installed close to an outside wall, coils are protected from vandals and severe weather.
CONDENSATE PUMP
A condensate pump accessory is available (High Wall and Floor Console) to provide installation flexibility for those applications where gravity cannot be used to dispose of the condensate. Factory installed condensate pump on the Ducted and Cassette fan coils provides installation flexibility.
AGENCY LISTINGS
All systems are listed with AHRI (Air conditioning, Heating, and Refrigeration Institute) and are ETL certified per UL 1995 standard.
2
MODEL NUMBER NOMENCLATURE
40 MB 309
40 = FAN COIL UNIT
INDOOR UNIT
BQD
--
MA =HIGHWALL MB = CASSET TE, DUCTED, FLOOR CONSOLE
SYSTEM TYPE Q =HEATPUMP
B=ALL
NOMINAL C APACITY 09 -3/4TON 12 -1TON 18 -1-1/2TONS 24 -2TONS
38 MG 318
38 = OUTDOOR UNIT
MG =ALL
SYSTEM TYPE Q =HEATPUMP
OUTDOOR UNIT
CQ-
--
VOLTAGE 3 = 208/230 - 1- 60
NOT USED
INDOOR FAN COIL TYPE
B =HIGHWALL C =CASSETTE D =DUCTED F = FLOOR CONSOLE
VOLTAGE 3 = 208/230 - 1- 60
MAXIMUM NUMBER OF FAN COIL UNITS THAT CAN BE CONNECTED TO THE OUTDOOR UNIT C =1:2 D =1:3 F =1:4OR1:5
NOMINAL C APACITY 18 -11/2TONS 27 -21/4TONS 36 -3TONS 48 -4TONS
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program For verification of certification for individual products, go to www.ahridirectory.org.
NOT USED
UNIT TYPE
- = OUTDOOR UNIT
3
STANDARD FEATURES AND ACCESSORIES
Ease of Installation
Mounting Bracket S Low Voltage Controls S
Comfort Features
Microprocessor Control S
Wired Remote Control for High Walls, Cassette and Floor Console A
Wired Remote Control for Ducted S
Wireless Remote Control S Rapid Cooling and Heating S Automatic Air Sweep S Cold Blow Prevention S Continuous Fan S Auto Restart Function S Auto Ch angeover S
Follow Me S
Energy Saving Features
Inverter Driven Compressor S Sleep Mode S 24 Hour Stop/Start Timer S
46° F Heating Mode (Heating Setback) S
Safety And Reliability
Indoor Coil Freeze Protection S 3MinuteTimeDelayForCompressor S High Compressor Discharge Temperature S Low Voltage Protection S Compressor Overload Protection S Compressor Over Current Protection S IPM Modul e Protection S
Ease of Service
Cleanable Filters S Diagnostic S Error Messages Displayed On Front Panel S
Application Flexibility
Condensate Pumps For High Walls and Floor Console A Condensate Pump For Cassette and Ducted S Crankcase Heater S
Legend S Standard A Accessory
INDOOR UNITS
On high wall and floor console fan coils, the condensate pump accessory is recommended when adequate drain line pitch cannot be provided, or when the condensate must move up to exit.
The pump has a lift capability of 12 ft (3.6 m) on the discharge side if the pump is mounted in the fan coil or 6 ft (1.8 m) on the suction side if the pump is remote mounted.
OUTDOOR UNITS
Standard on all unit sizes. Heater clamps around compressor oil stump.
Fig. 1 – Condensate Pump Accessory
4
COMBINATION TABLE
Indoor Unit Nominal Unit Btuh Indoor Model Number Outdoor Model Number
High Wall
Cassette
Ducted
Floor Console
Indoor Unit Nominal Unit Btuh Indoor Model Number Outdoor Model Number
High Wall
Cassette
Ducted
Floor Console
Indoor Unit Nominal Unit Btuh Indoor Model Number Outdoor Model Number
High Wall
Cassette
Ducted
Floor Console
9,000 40MAQB09B--3
12,000 40MAQB12B--3
9,000 40MBQB09C--3
12,000 40MBQB12C--3
9,000 40MBQB09D--3
12,000 40MBQB12D--3
9,000 40MBQB09F--3
12,000 40MBQB12F--3
9,000 40MAQB09B--3 12,000 40MAQB12B--3 18,000 40MAQB18B--3
9,000 40MBQB09C--3 12,000 40MBQB12C--3 18,000 40MBQB18C--3
9,000 40MBQB09D--3 12,000 40MBQB12D--3 18,000 40MBQB18D--3
9,000 40MBQB09F--3 12,000 40MBQB12F--3
9,000 40MAQB09B--3 12,000 40MAQB12B--3 18,000 40MAQB18B--3 24,000 40MAQB24B--3
9,000 40MBQB09C--3 12,000 40MBQB12C--3 18,000 40MBQB18C--3
9,000 40MBQB09D--3 12,000 40MBQB12D--3 18,000 40MBQB18D--3 24,000 40MBQB24D--3
9,000 40MBQB09F--3 12,000 40MBQB12F--3
38MGQC18---3
38MGQD27---3
38MGQF36---3 38MGQF48---3
5
DIMENSIONS - INDOOR
Unit Size W In. (mm) D In. (mm) H In. (mm)
9K/12K 32.9(835) 7.8(198) 11.0(280) 19.2(8.7)
18K 39.0(990) 8.6(218) 12.4(315) 26.5(12.0)
24K/30K 46.7(1186) 10.2(258) 13.4( 343) 40.8(18.5)
Fig. 2 – High Wall Dimensions
Operating Weight
Lbs. (kg)
Fig. 3 – Cassette Dimensions
Unit size
Height in(mm) 10.24 (260) 1.97 (50) 10.24 (260) 1.97 (50) 10.24 (260) 1.97 (50)
Width in(mm) 22.44 (570) 25.47 (647) 22.44 (570) 25.47 (647) 22.44 (570) 25.47 (647) Depth in(mm) 22.44 (570) 25.47 (647) 22.44 (570) 25.47 (647) 22.44 (570) 25.47 (647)
Operating
Weight
lbs(kg) 35.27 (16) 5.51 (2.5) 35.27 (16) 5.51 (2.5) 39.68 (18) 5.51 (2.5)
body panel body panel body panel
9K 12K 18K
6
DIMENSIONS - INDOOR (CONTINUED)
Fig. 4 – Ducted Dimensions
Outline dimensions in(mm) Air outlet opening size in(mm)
Size A B C D E F G H I J K L M H1 H2 W1 W2
27.6
(700)
27.6
(700)
36.2
(920)
36.2
(920)
8.2
(210)25(635)
8.2
(210)25(635)
8.2
(210)25(635)
10.6
(270)25(635)
9
12
18
24
22.4
(570)
22.4
(570)
22.4
(570)
22.4
(570)
2.5
(65)
2.5
(65)
2.5
(65)
2.5
(65)
19.4 (493)
19.4 (493)
19.4 (493)
19.4 (493)
1.3
(35)
1.3
(35)
1.3
(35)
1.3
(35)
Air return opening size
4.6
23.4
(119)
(595)
4.6
23.4
(119)
(595)
4.6
32.0
(119)
(815)
7.0
32.0
(179)
(815)
in(mm)
7.8
(200)
7.8
(200)
7.8
(200)
10.2
(260)
3.1
(80)
3.1
(80)
3.1
(80)
0.7
(20)
Hanger
Brackets
in(mm)
29.1
(740)
29.1
(740)
37.8
(960)
37.8
(960)
13.8
(350)
13.8
(350)
13.8
(350)
13.8
(350)
Refrigerant Pipe Locations
in(mm)
4.7
5.6
(143)
5.6
(143)
5.6
(143)
5.6
(143)
3.7
(95)
3.7
(95)
3.7
(95)
3.7
(95)
(120)
4.7
(120)
4.7
(120)
4.7
(120)
5.9
(150)
5.9
(150)
5.9
(150)
5.9
(150)
7
Operating
Weight
Lbs. (kg)
in(mm)
39.90 (18.1)
39.90 (18.1)
50.7 (23)
57.32 (26)
DIMENSIONS - INDOOR (CONTINUED)
Fig. 5 – Floor Console Dimensions
Unit size 9 12
Height in (mm) 8.27 (210) 8.27 (210)
Width in (mm) 27.56 (700) 27.56 (700) Depth in (mm) 23.62 (600) 23.62 (600)
Operating Weight Lbs. (kg) 32.41 (14.7) 32.41 (14.7)
8
DIMENSIONS - OUTDOOR
Unit Size 18 27 36 48
Height in (mm) 27.56(700) 31.89(810) 31.89(810) 36.93(1369)
Width in (mm) 33.27(845) 37.20(945) 37.20(945) 53.9(938)
Depth in (mm) 12.60(320) 15.55(395) 15.55(395) 15.43(392)
Weight -Net lbs (kg) 114.63(52) 154.76(70.2) 169.75(77) 255.50(115.9)
Fig. 6 – Outdoor Dimensions Size 18
9
DIMENSIONS - OUTDOOR (CONTINUED)
Fig. 7 – Outdoor Dimensions Size 27
10
DIMENSIONS - OUTDOOR (CONTINUED)
Fig. 8 – Outdoor Dimensions Size 36
11
DIMENSIONS - OUTDOOR (CONTINUED)
Fig. 9 – Outdoor Dimensions Size 48
12
CLEARANCES - INDOOR
(0.13m)
min.
CEILING
6" (0.15m) min.
5
"
(1.8m)
6'
5
"
(0.13m)
min.
FLOOR
Fig. 10 – High Wall clearance
Fig. 11 – Cassette Unit Clearance
13
CLEARANCES - INDOOR (CONTINUED)
Fig. 12 – Ducted clearance
Fig. 13 – Floor Console clearances
14
CLEARANCES - OUTDOOR
D
A
B
C
Air-outlet
Fig. 14 – Clearances Outdoor
UNIT
A 24 (609) B 24 (609) C 24 (609) D 4 (101) E 4 (101)
Minimum Value
in. (mm)
Air-inlet
E
15
PHYSICAL DATA - OUTDOOR
Size 18 27 36 48
System
Performance
Non-Ducted
Performance Combination
Ducted and
Non-Ducted
Performance
Ducted
Operating
Range
Piping
Electrical
Outdoor
Outdoor Model 38MGQC18---3 38MGQD27---3 38MGQF36---3 38MGQF48---3 Max Number of Zones 2 3 4 5 Energy Star YES YES NO YES Cooling Rated Capacity Btu/h 18,000 25,000 36,000 42,000 Cooling Cap. RangeMin - Max Btu/h 8,500~20,000 9,000~30,000 9,500~37,000 10,000~50,000 SEER 21 22 18 20 EER 12.5 12.5 8.8 12.5 Heating RatedCapacity Btu/h 18,500 32,000 36,000 49,000 Heating Cap.Range Min - Max Btu/h 9,000~22,000 9,500~32,000 10,000~39,000 10,500~55,000 HSPF 9.6 9.6 10.0 10.0 Cooling Rated Capacity Btu/h 17,500 26,000 35,000 42,000 Cooling Cap. RangeMin - Max Btu/h 8,500~20,000 9,000~30,000 9,500~36,500 10,000~50,000 SEER 19.5 19.25 16.5 19 EER 12.5 11 8.5 11.75 Heating RatedCapacity Btu/h 18,250 32,000 36,000 50,000 Heating Cap.Range Min - Max Btu/h 9,000~22,000 9,500~32,000 10,000~39,000 10,500~55,000 HSPF 9.1 9.2 9.7 9.8 Cooling Rated Capacity Btu/h 17,000 27,000 34,000 42,000 Cooling Cap. RangeMin - Max Btu/h 8,500~20,000 9,000~30,000 9,500~36,000 10000~50000 SEER 18 16.5 15 18 EER 12.5 9.5 8.2 11 Heating RatedCapacity Btu/h 18,000 32,000 36,000 51,000 Heating Cap.Range Min - Max Btu/h 9000~22000 9500~32000 10,000~39,000 10,500~55,000 HSPF 8.5 8.8 9.3 9.5 Cooling Outdoor DB Min - Max °F 4~122 4~122 4~122 4~122 Heating Outdoor DB Min - Max °F 4~86 4~86 4~86 4~86 Total Piping Length Ft. 98 147 196 245 Piping to furthestFCU Ft. 98 98 98 98 Drop (OD above ID) Ft. 32 32 32 32 Lift (OD below ID) Ft. 32 32 32 32 Pipe ConnectionSize - Liquid In. 1/4*2 1/4*3 1/4*4 1/4*5 Pipe ConnectionSize - Suction In. 3/8*2 3/8*3 1/2+3/8*3 1/2*2+3/8*3 Voltage, Phase,Cycle V/Ph/Hz 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 Power Supply Indoor unit powered from outdoor unit MCA A. 15 18 27 29 MOCP - Fuse Rating A. 20 30 45 50 Unit Width In. 33.3 37.2 37.2 36.9 Unit Height In. 27.6 31.9 31.9 53.9 Unit Depth In. 12.6 15.6 15.6 15.4 Net Weight Lbs. 114.6 154.8 169.8 255.5 Airflow CFM 1,390 2,130 2,130 3,500 Sound Pressure dB(A) 60 63 63 64
16
PHYSICAL DATA - INDOOR
Size 9 12 18 24
Model 40MAQB09B--3 40MAQB12B--3 40MAQB18B--3 40MAQB24B--3 Unit Width In. 32.9 32.9 39 46.7 Unit Height In. 11 11 12.4 13.4 Unit Depth In. 7.8 7.8 8.6 10.2 Net Weight Lbs. 19.2 19.2 26.5 40.1
High Wall
Indoor Unit
Cassette
Indoor Unit
Pipe ConnectionSize - Liquid In. 1/4 1/4 1/4 3/8 Pipe ConnectionSize - Suction In. 3/8 1/2 1/2 5/8 Number of Fan Speeds 4 4 4 4 Airflow (lowest to highest) CFM 210/290/360/380 210/300/360/380 310/450/650/680 520/620/780/870 Sound Pressure (lowestto highest) dB(A) 27/34/42 27/34/42 33/40/46 39/45/50 Air throw Data Ft. 23 23 30 36 Wireless Remote Controller (°F/°CConvertible) Standard Wired RemoteController (°F/°C Convertible) Optional
Size 9 12 18
Model 40MBQB09C--3 40MBQB12C--3 40MBQB18C--3 Unit Width In. 22.4 22.4 22.4 Unit Height In. 10.2 10.2 10.2 Unit Depth In. 22.4 22.4 22.4 Net Weight Lbs. 35.3 35.3 39.7 Pipe ConnectionSize - Liquid In. 1/4 1/4 1/4 Pipe ConnectionSize - Suction In. 3/8 1/2 1/2 Number of Fan Speeds 3 3 3 Airflow (lowest to highest) CFM 260/320/380 280/340/400 290/350/420 Sound Pressure (lowestto highest) dB(A) 34/39/44 36/39/42 46/48/50 Wireless Remote Controller (°F/°CConvertible) Standard Wired RemoteController (°F/°C Convertible) Optional
Ducted
Indoor Unit
Floor
Console
Indoor Unit
Size 9 12 18 24
Model 40MBQB09D--3 40MBQB12D--3 40MBQB18D--3 40MBQB24D--3 Unit Width In. 27.6 27.6 36.2 36.2 Unit Height In. 8.3 8.3 8.3 10.6 Unit Depth In. 25 25 25 25 Net Weight Lbs. 39.9 39.9 50.7 57.3 Pipe ConnectionSize - Liquid In. 1/4 1/4 1/4 3/8 Pipe ConnectionSize - Suction In. 3/8 1/2 1/2 5/8 Number of Fan Speeds 3 3 3 3 Airflow (lowest to highest) CFM 290/340/380 290/340/380 400/440/480 590/650/810 Sound Pressure (lowestto highest) dB(A) 30/33/36 30/34/38 34/37/38 43/45/48 Max Static Pressure In.WG. 0.18 0.18 0.40 0.40 0.18 0.18 0.40 0.40 0.18 0.18 0.40 0.40 0.18 0.18 0.40 0.40 Wireless Remote Controller (°F/°CConvertible) Standard Wired RemoteController (°F/°C Convertible) Standard
Size 9 12
Model 40MBQB09F--3 40MBQB12F--3 Unit Width In. 27.6 27.6 Unit Height In. 8.3 8.3 Unit Depth In. 23.6 23.6 Net Weight Lbs. 32.4 32.4 Pipe ConnectionSize - Liquid In. 1/4 1/4 Pipe ConnectionSize - Suction In. 3/8 1/2 Number of Fan Speeds 3 3 Airflow (lowest to highest) CFM 220/250/280 220/250/280 Sound Pressure (lowestto highest) dB(A) 37/38/41 34/41/45 Wireless Remote Controller (°F/°CConvertible) Standard Wired RemoteController (°F/°C Convertible) Optional
17
COOLING PERFORMANCE
Cooling Outdoor conditions (DB)
Model
18
27
36
48
Indoor Conditions DB
DB WB
69.8F(21C) 59F(15C)
80.6F(27C) 66.2F(19C)
69.8F(21C) 59F(15C)
80.6F(27C) 66.2F(19C)
69.8F(21C) 59F(15C)
80.6F(27C) 66.2F(19C)
69.8F(21C) 59F(15C)
80.6F(27C) 66.2F(19C)
75F(24C) 85F(29.5C) 95F(35C) 105F(40.5C)
TC 18.07 18.74 17.22 13.28
SC 15.00 15.37 14.64 13.01
Input 1.17 1.54 1.72 1.88
TC 20.75 21.48 20.43 16.42 SC 15.97 16.33 15.93 14.62
Input 1.16 1.56 1.76 1.59
TC 23.99 27.20 24.55 19.31 SC 22.67 24.08 22.56 19.31
Input 1.50 2.42 2.67 2.39
TC 27.40 31.78 29.90 23.85 SC 23.72 25.06 2.51 22.94
Input 1.51 2.52 2.83 2.51
TC 28.80 32.69 30.25 23.15 SC 26.32 28.18 27.02 23.15
Input 2.17 3.45 3.81 2.99
TC 33.47 38.11 36.60 28.42 SC 28.83 30.55 32.94 26.99
Input 2.21 3.57 3.94 3.25
TC 44.06 42.04 38.95 34.05 SC 37.89 36.57 35.44 33.37
Input 3.32 3.78 4.19 4.45
TC 46.88 49.74 45.99 41.31 SC 40.32 43.27 41.85 40.07
Input 2.64 3.90 4.33 4.61
LEGEND
DB --- Dr y Bulb WB --- Wet Bulb TC --- Total Net Cooling Capacity (1000 Btu/hour) SC --- Sensible Capacity (1000 Btu/hour) Input --- Total Power (kW)
HEATING PERFORMANCE
Model
18
27
36
48
LEGEND
DB --- Dr y Bulb TH --- Total Net Heating Capacity (1000 Btu/hour) Input --- Total Power (kW)
Indoor Conditions (DB) 57F(13.9C) 47F(8.3C) 35F(1.7C) 17F(-8.3C) 5F(-15C) -5F(-20C)
Heating Outdoor conditions (DB)
55F(12.7C)
70F(21.1C)
55F(12.7C)
70F(21.1C)
55F(12.7C)
70F(21.1C)
55F(12.7C)
70F(21.1C)
TH 23.27 20.85 16.80 13.29 10.92 8.63
Input 1.25 1.33 1.30 1.42 1.35 1.31
TH 21.69 20.19 16.19 12.32 9.09 7.70
Input 1.45 1.51 1.49 1.56 1.48 1.41
TH 37.85 34.34 28.36 22.77 19.38 16.23
Input 2.27 2.29 2.29 2.46 2.44 2.40
TH 36.29 3.23 27.54 20.09 16.37 13.42
Input 2.68 2.64 2.51 2.53 2.39 2.29
TH 41.10 38.52 28.84 28.16 22.87 19.43
Input 3.17 3.31 2.92 3.22 2.97 2.91
TH 40.86 38.83 29.89 26.02 20.15 16.70
Input 3.62 3.73 3.37 3.38 3.05 2.90
TH 60.91 53.30 42.81 33.02 26.16 20.01
Input 4.26 4.04 3.78 3.82 3.56 3.42
TH 55.22 50.58 40.56 31.81 23.48 17.17
Input 4.64 4.59 4.20 4.27 3.98 3.88
18
PIPING REQUIREMENTS
System size 18K 27K 36K 48K
Min. Piping Length ft (m) 10 (3) 10 (3) 10 (3) 10 (3) Standard Piping Length ft (m) 25 (7.5) 25 (7.5) 25 (7.5) 25 (7.5) Max. outdoor-indoor height difference (OU higher than IU) Max. outdoor-indoor height difference (IU higher than OU) Max. Piping Length with no additional refrigerant
Piping
Refrigerant
charge Max. Length for one indoor unit ft (m) 65.6(20) 82(25) 98(30) 98(30) Max. height different between indoor units ft (m) 32(10) 32(10) 32(10) 32(10) Total Maximum Piping Length Ft. (m) 98(2*15=30) 147(3*15=45) 196(4*15=60) 245(5*15=75) Additional refrigerantcharge (between Standard– Max piping length) Gas Pipe in 3/8*2 3/8*3 1/2+3/8*3 1/2+3/8*3 Liquid Pipe in 1/4*2 1/4*3 1/4*4 1/4*5 Refrigerant Type R410A R410A R410A R410A Heat Pump Models Charge Amount Lbs (kg) 4.19 (1.9) 6.17 (2.8) 7.94 (3.6) 10.14 (4.6)
APPLICATION DATA
UNIT SELECTION
When selecting a variable speed system match the system capacity range to the anticipated load range. Since a variable speed system can accommodate a wide range of loads it is important to understand the percentage of time that the system will be required to run at the both the maximum and the minimum load points. This differential is most evident when a residential application is compared with a commercial application.
ft (m) 32(10) 32(10) 32(10) 32(10)
ft (m) 49(15) 49(15) 49(15) 49(15)
ft (m) 24.6(7.5) 24.6(7.5) 24.6(7.5) 24.6(7.5)
Oz/ft (g/m) 0.16(15) 0.16(15) 0.16(15) 0.16(15)
Generally there will be more load diversification in the residential application (shifting from low load to high load).
The commercial application will tend to be more steady during the normal day time hours, and will go to low load levels after normal business hours. If it is anticipated that the system will be required to run at the maximum load point for the majority of the time, the next larger system capacity should be selected.
The Application Table on page 20 is a guideline for selecting the proper size for the application.
19
APPLICATION DATA
Outdoor UnitModel Cooling Capacity (Btu/h) Heating Capacity (Btu/h)
38MGQC18---3 Type Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 1 Zone 2 Zone 3 Zone 4 Zone 5
9K + 9K 9K + 12K 8,500 10,500 9,000 11,000 12K+12K 9,500 9,500 10,000 10,000
38MGQD27---3 Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 1 Zone 2 Zone 3 Zone 4 Zone 5
9K + 9K 9K + 12K 9,500 12,000 10,000 13,000 9K + 18K 8,400 16,600 9,000 18,000
12K + 12K 12,000 12,000 13,000 13,000 12K + 18K 10,000 15,000 11,200 16,800
9+9+9 9+9+12 8,667 8,667 11,667 9,500 9,500 12,000 9+9+18 8,333 8,333 13,333 9,000 9,000 14,000
9+12+12 8,500 10,000 10,000 8,500 11,000 11,000
12+12+12 9,667 9,667 9,667 10,667 10,667 10,667
38MGQF36---3 Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 1 Zone 2 Zone 3 Zone 4 Zone 5
9+18 12+12 12,000 12,000 13,000 13,000 12+18 12,000 18,000 13,000 18,000 18+18 16,500 16,500 17,000 17,000
9+24 8,500 22,500 9,500 22,500 12+24 10,500 21,000 11,000 22,000 9+9+9
9+9+12 9,000 9,000 12,000 9,500 9,500 12,500
9+9+18 8,000 8,000 16,000 8,500 8,500 17,000 9+12+12 8,500 11,500 11,500 9,000 12,000 12,000 9+12+18 8,000 11,000 15,000 8,500 11,500 16,000 9+18+18 8,000 14,000 14,000 8,500 14,500 14,500
12+12+12 11,333 11,333 11,333 12,000 12,000 12,000 12+12+18 11,000 11,000 14,000 12,000 12,000 15,000 12+18+18 9,333 13,333 13,333 9,500 14,000 14,000
9+9+9+9
9+9+9+12 8,500 8,500 8,500 11,500 9,000 9,000 9,000 12,000
9+9+9+18 8,000 8,000 8,000 14,000 8,500 8,500 8,500 14,000 9+9+12+12 8,000 8,000 10,500 10,500 8,500 8,500 11,000 11,000 9+9+12+18 7,500 7,500 9,000 14,000 8,000 8,000 9,500 14,500
9+12+12+12 7,000 10,000 10,000 10,000 8,000 10,500 10,500 10,500
12+12+12+12 9,500 9,500 9,500 9,500 10,000 10,000 10,000 10,000
38MGQF48---3 Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 18+18 18+24 17,500 22,500 18,000 23,000 24+24 21,000 21,000 22,000 22,000
9+24 9,000 23,000 10,000 23,000
9+18 9,500 18,500 10,500 19,000 9+9+18 9+9+24 9,000 9,000 22,500 9,500 9,500 23,500
9+12+12 9,500 12,500 12,500 10,000 10,000 13,000 9+12+18 9,000 12,000 18,000 9,500 9,500 19,000 9+12+24 9,000 12,000 21,500 9,500 12,500 22,000 9+18+18 9,000 18,000 18,000 9,500 18,500 18,500 9+18+24 8,500 15,500 21,000 9,000 16,000 21,500
9+24+24 8,000 20,000 20,000 8,500 21,000 21,000 12+12+12 12,000 12,000 12,000 13,000 13,000 13,000 12+12+18 12,000 12,000 17,000 12,500 12,500 18,000 12+12+24 11,000 11,000 22,000 11,500 11,500 23,000 12+18+18 11,000 16,500 16,500 11,500 17,000 17,000 12+18+24 10,500 15,500 21,500 11,000 16,000 22,000 12+24+24 10,000 20,000 20,000 11,000 20,500 20,500 18+18+18 16,000 16,000 16,000 16,500 16,500 16,500 18+18+24 15,000 15,000 20,000 15,500 15,500 21,000
9+9+9+9
9+9+9+12 9,000 9,000 9,000 12,000 9,500 9,500 9,500 12,500 9+9+9+18 9,000 9,000 9,000 17,000 9,500 9,500 9,500 17,500
9+9+9+24 8,500 8,500 8,500 20,500 9,000 9,000 9,000 21,000 9+9+12+12 9,000 9,000 12,000 12,000 9,500 9,500 13,000 13,000 9+9+12+18 9,000 9,000 11,000 17,000 9,500 9,500 11,500 17,500 9+9+12+24 8,500 8,500 10,500 20,500 9,000 9,000 11,100 21,000 9+9+18+18 8,500 8,500 15,500 15,500 9,000 9,000 16,000 16,000 9+9+18+24 8,000 8,000 14,500 20,000 8,500 8,500 15,000 20,000
9+12+12+12 9,000 12,000 12,000 12,000 9,500 12,500 12,500 12,500 9+12+12+18 9,000 11,000 11,000 16,000 9,500 11,500 11,500 16,500 9+12+12+24 8,500 10,000 10,000 20,000 9,000 10,500 10,500 20,500 9+12+18+18 8,500 10,000 15,000 15,000 9,000 10,500 15,500 15,500
9+18+18+18 8,000 14,000 14,000 14,000 8,500 14,500 14,500 14,500 12+12+12+12 12,000 12,000 12,000 12,000 12,500 12,500 12,500 12,500 12+12+12+18 11,000 11,000 11,000 16,000 11,500 11,500 11,500 16,500 12+12+12+24 10,000 10,000 10,000 20,000 10,500 10,500 10,500 20,500 12+12+18+18 10,000 10,000 15,000 15,000 10,500 10,500 15,500 15,500
9+9+9+9+9 9+9+9+9+12 9,000 9,000 9,000 9,000 12,000 9,500 9,500 9,500 9,500 13,000 9+9+9+9+18 8,500 8,500 8,500 8,500 16,000 9,000 9,000 9,000 9,000 16,500 9+9+9+9+24 7,750 7,750 7,750 7,750 19,500 8,000 8,000 8,000 8,000 20,000
9+9+9+12+12 9,000 9,000 9,000 11,500 11,500 9,500 9,500 9,500 12,000 12,000 9+9+9+12+18 8,000 8,000 8,000 11,000 16,000 8,500 8,500 8,500 11,500 16,500
9+9+9+18+18 8,000 8,000 8,000 11,000 16,000 8,500 8,500 8,500 16,500 16,500 9+9+12+12+12 8,500 8,500 11,000 11,000 11,000 9,000 9,000 12,000 12,000 12,000 9+9+12+12+18 8,500 8,500 10,000 10,000 15,000 8,500 8,500 10,500 10,500 15,500
9+12+12+12+12 8,000 11,000 11,000 11,000 11,000 8,500 11,500 11,500 11,500 11,500 9+12+12+12+18 7,500 10,000 10,000 10,000 14,500 8,000 10,500 10,500 10,500 15,000
12+12+12+12+12 10,500 10,500 10,500 10,500 10,500 11,000 11,000 11,000 11,000 11,000
2-Zone
2-Zone
3-Zone
2-Zone
3-Zone
4-Zone
2-Zone
3-Zone
4-Zone
5-Zone
9,000 9,000 9,500 9,500
9,500 9,500 10,000 10,000
9,000 9,000 9,000 9,500 9,500 9,500
9,500 17,500 10,000 18,000
9,333 9,333 9,333 9,667 9,667 9,667
9,000 9,000 9,000 9,000 9,500 9,500 9,500 9,500
18,500 18,500 19,000 19,000
9,500 9,500 18,000 10,000 10,000 19,000
9,250 9,250 9,250 9,250 9,500 9,500 9,500 9,500
9,000 9,000 9,000 9,000 9,000 9,500 9,500 9,500 9,500 9,500
20
UNIT MOUNTING (INDOOR)
Mounting Bracket – The fan coil units are furnished with
mounting brackets or dedicated mounting holes to hang the unit. Support – Adequate support must be provided to handle the
weight of all fan coils. Refer to the Physical Data section for weights, and the base unit dimensional drawings.
Unit Leveling – For reliable operation, units should be level in all planes.
Clearances – Minimum clearance as shown in Fig. 13- 14. Unit location – Select a location which will provide the best air
circulation for the room. These units should be positioned as high to have adequate air circulation. The unit return and discharge should not be obstructed by furniture, curtains, or anything which may cause the unit to short cycle or air to recycle.
UNIT MOUNTING (OUTDOOR)
Support – A location which can bear the weight of outdoor unit.
Refer to the Physical Data section for weights, and base dimensional drawings.
Unit Leveling – For reliable operation, units should be level in all planes.
Clearances – Minimum clearances, as shown in Fig. 14, must be provided for airflow. The outdoor units are designed for free- blow applications. Air inlets and outlets should not be restricted.
Unit location – A location which is convenient to installation and not exposed to strong wind.
SYSTEM OPERATING CONDITIONS
Cooling operating range:
Operating Range
Min / Max °F (°C)
Cooling Heating
Outdoor DB 4/ 122 (-20 / 50) 4 / 86 (-20 / 30)
Indoor DB 63 / 90 (17 / 32) 32 / 86 (0 / 30)
Indoor WB 59/ 84 (15 / 29)
Heating operating range:
Non-Operating Temperature Range
Min / Max °F (°C)
Indoor/Outdoor DB 32 / 86 (0 / 30)
METERING DEVICES
The outdoor unit has multiple electronic expansion valves to manage the refrigerant flow to the different indoor fan coils connected to that unit.
REFRIGERANT LINES
General Guidelines:
1. The outdoor units are shipped with full charge of R- 410A
refrigerant. All charges, line sizing, and capacities are based on runs of 25 ft (7.6 m). For runs over 25 ft (7.6m), consult long- line section on this page for proper charge adjustments.
2. Refrigerant line s should not be buried in the ground. If it is
necessary to bury the lines, not more than 36 inche s (914 mm) should be buried. Provide a mini mum of 6 inch (152 mm) vertical rise to se r vice valves to preve nt refrigerant migration.
3. Both lines must be insulated. Use a minimum of ½-inch
(12.7 mm) thick insulation. Closed-cell insulation is recommended in all long - line applications.
4. Special consideration should be given to isolating
interconnecting tubing from the building structure. Isolate the tubing so that vibration or noise is not transmitted into the structure.
Long Line Applications:
S No change in line sizing is required.
Total Line Length
ftper indoor unit
Unit Size
18 27 82
48
Min Max
10
66
98 0.16
Additional Charge, oz/ft.
10 - 25
(3 - 8)
None 0.16
ft (m)
>25 - 66
(8 - 20)
>66 - 82 (20 - 25)
0.1636
>82 - 98 (25 - 30)
DRAIN CONNECTIONS
Install drains to meet the local sanitation codes. If adequate gravity drainage cannot be provided, a field installed condensate pump accessory should be used. Refer to the Installation Instructions of the condensate pump for detailed specifications. (Condensate Pump built- in on Ducted and Cassette indoor units).
NOTE: The high wall fan coils have internal condensate trap. An external trap is not required.
WIRING
The main power is supplied to the outdoor unit. Four field supplied connecting cables from the outdoor unit to each of the indoor units are: L1, L2, Ground, and S for communication between the outdoor unit and each indoor unit.
CONTROL SYSTEM
The 38MG / 40MA / 40MB unit is equipped with a microprocessor control to operate the system and give optimum levels of comfort and operating efficiency.
There are microprocessor boards and thermistors located in both the indoor and outdoor units. The thermistors monitor the system operation and control the operating mode. The change in the settings or the modes of operation, use the factory supplied wireless remote control.
The 38MG / 40MA / 40MB unit has the following operating modes:
S Fan Only S Auto S Heating (on Heat Pumps only) S Cooling S Dehumidification (Dry)
FAN O NLY - In Fan Only mode, the system filters and circulates the room air without changing the room air temperature.
AUTO - In Auto mode, the system will automatically select one of the following operating modes: cooling, heating or fan only based on the difference between the room temperature and the set point temperature.
HEATING - In the Heating mode, the system heats and filters room air.
COOLING - When in Cooling mode, the fan runs all the time and the system cools, dries and filters room air.
DEHUMIDIFICATION (DRY) - in Dehumidification (Dry) mode, the system dries, filters and slightly cools room temperature. This mode does not take place of a dehumidifier.
In addition to the above modes that are selected by using the remote control, the unit can run in emergency mode by using a manual button. This mode is used when the remote is misplaced or the batteries in the remote have died. In this mode, the unit will run in AUTO mode with a predetermined set point (76_F/24.4_C)
21
WIRELESS REMOTE CONTROL
1. A wireless remote control is supplied for system operation.
2. Each battery- operated wireless remote control may be used
to control more than one unit.
3. The wireless remote control has a range of 25 ft. (7.6 m).
Fig. 15 – Wireless remote control
WIRED REMOTE CONTROL (STANDARD ON DUCTED UNITS)
1. Optional wired remote controller used for system operation
of all high- wall, cassette and floor console units.
2. Kit includes a wired remote controller and a connecting
cable.
3. Connect with wire terminal between remote controller and
indoor unit.
4. Display in _For_C and temperature increments every 1_F
or every 1_C.
Fig. 16 – Wired remote control
SEQUENCE OF OPERATION
Simultaneous heating and cooling is not allowed. At start- up, the first indoor unit to call for operation (heating or cooling) will control from the preset position, the mode of operation for the rest of the indoor units connected to the same outdoor unit. If the other units conflict in mode with the first unit an error message will be displayed on those units.
When a unit is set to COOL, HEAT or DRY mode, the electronic expansion valve is first initialized (closed) and then is opened to a preset position.
Superheat heat for each fan coil (the ones that are energized) is monitored and the position of the electronic expansion valve is adjusted to ensure that each fan coil gets the appropriate amount of refrigerant to maintain the requir ed superheat. Aft er the set point is satisfied and the fan coil shuts off, the electroni c expansion valve stays open for a specified time to ensure that system pressures equalize .
When the system is set for COOL, HEAT or DRY mode, the compressor speed is varied by comparing the indoor air temperature with the set point and continuously adjusting the compressor speed (to keep the compressor running as long as possible) in an effort to maintain the greatest comfort possible.
The indoor fan can be running in MANUAL or AUTO mode. When the fan is running in AUTO mode, the speed is determined by comparing the room temperature to the set point.
In COOLING mode, when the set point is satisfied, the fan will continue running. In HEATING mode, when the set point is satisfied, the fan speed will be reduced and then will run continuously until the coil temperature drops to a point cold air is blown on the occupants in the space, at which time the indoor fan is de- energized.
When the unit goes through the defrost cycle, the indoor fans are de- energized and the refrigerant is circulated through all the fan coils (even if they were off or on standby before the defrost cycle) to maximize the heat transfer surface area available for defrost operation.
22
AIR FLOW DATA
High Wall
System size 9 12 18 24
Turbo 380 380 680 870
Indoor (CFM)
System size 9 12 18
Indoor (CFM)
System size 9 12 18 24
Indoor (CFM)
System size 9 12
Indoor (CFM)
System Size 18 27 36 48
Outdoor (CFM) 1390 2130 2130 3500
High 360 360 650 780
Medium 290 300 450 620
Low 210 210 310 520
Cassette
High 380 400 420
Medium 320 340 350
Low 260 280 290
Ducted
High 380 380 480 810
Medium 340 340 440 650
Low 290 290 400 590
Floor Console
High 280 280
Medium 250 250
Low 220 220
Outdoor Multi-Zone
SOUND PRESSURE
High Wall
System size 9 12 18 24
Cooling operation Indoor SoundPressure dBa (L/M/H) 42/34/27 42/34/27 46.5/40/33 50/45/39 Heating operation Indoor Sound Pressure dBa (L/M/H) 40/33/26 41/34/27 45/39/32 47/44/38
Cassette
System size 9 12 18
Cooling operation Indoor SoundPressure dBa (L/M/H) 34/39/44 36/39/42 46/48/50 Heating operation Indoor Sound Pressure dBa (L/M/H) 31/37/42 36/39/42 46/47/49
Ducted
System size 9 12 18 24
Cooling operation Indoor SoundPressure dBa (L/M/H) 30/33/36 30/34/38 34/37/38 43/45/48 Heating operation Indoor Sound Pressure dBa (L/M/H) 30/33/36 30/34/38 34/37/39 44/45/48
Floor Console
System size 9 12
Cooling operation Indoor SoundPressure dBa (L/M/H) 37/38/41 34/41/45 Heating operation Indoor Sound Pressure dBa (L/M/H) 37/38/41 34/41/45
Outdoor Multi-Zone
System size 18 27 36 48
Sound pressure level dBa 60 63 63 64
23
ELECTRICAL DATA
High Wall
UNIT SIZE
9 12 18 24 30
UNIT SIZE
9
12 1.03 0.073 55 18 0.83 0.12 90 24 0.83 0.12 90 36 1.263 0.2 150 48 2.23 0.32 240
UNIT SIZE
9 12 18
System Voltage OPERATING VOLTAGE INDOOR FAN
VOLT / PHASE / HZ MAX/ MIN V-PH-HZ FLA HP W
0.07 0.027 20
0.07 0.027 20
208-230/1/60 253 / 187 208-230/1/60
Ducted
System Voltage OPERATING VOLTAGE INDOOR FAN
VOLT / PHASE / HZ MAX / MIN FLA HP W
1.03 0.073 55
208-230/1/60 253 / 187
0.17 0.077 58
0.23 0.08 60
0.23 0.08 60
Cassette
System Voltage OPERATING VOLTAGE INDOOR FAN
VOLT / PHASE / HZ MAX/ MIN V-PH-HZ FLA HP W
0.146 0.061 46
208-230/1/60 253 / 187 208-230/1/60
0.146 0.061 46
0.146 0.061 46
Floor Console
UNIT SIZE
9 12
System Voltage OPERATING VOLTAGE INDOOR FAN
VOLT / PHASE / HZ MAX/ MIN V-PH-HZ FLA HP W
208-230/1/60 253 / 187 208-230/1/60
Multi Zone Outdoor Unit
UNIT SIZE
18 27 8.85 36 13.4 48 13.5
System Voltage OPERATING VOLTAGE COMPRESSOR OUTDOOR FAN MCA
VOLT / PHASE / HZ MAX / MIN RLA FLA HP W
208-230/1/60 253 / 187
MAX STATIC PRESSURE - DUCTED
System size 9 12 18 24
Max static pressure
Pa 40 40 70 70
In.WG 0.16 0.16 0.28 0.28
9.7
0.21 0.027 20
0.21 0.027 20
MAX
FUSE/CB
AMP
3 0.16 50 15 20 3 0.16 120 18 30 3 0.16 120 27 45 3 0.11 85 29 50
24
FAN PERFORMANCES (DUCTED UNITS)
Static pressure curve (static pressure deducted)
Code 0 1 2 3 4 Max Static Pressure
Sizes9&12 0.00 0.04 0.08 0.12 0.16 0.18 Sizes18&24 0.04 0.10 0.16 0.22 0.28 0.40 Sizes36&48 0.08 0.14 0.20 0.26 0.32 0.40
Default Setting
Fig. 17 – 9K and 12K
25
Fig. 18 – 18K
Fig. 19 – 24K
26
WIRING DIAGRAMS
Fig. 20 – Wiring Diagrams 18k
OUTDOOR UNIT CONTROL BOARD SIZE 18
CODE PARTNAME
CN18/CN19/CN22 Output:Pin5&6(12V) Pin1-Pin4:Pulse waveform,(0-12V) CN17 Input:Pin3~4 (5V) Pin2(0V),Pin1,Pin5(0-5V) CN7 Input:Pin1 (0-5V) Pin2(5V) CN1~CN2CN5~CN6 Output: CN1~CN2CN5~CN6230VAC High voltage P1~P2 Output: Connectionof the high voltage CN3~CN4 Input:230VAC High voltage CN14 InputPin1,Pin3(0V)Pin2,Pin40~5V P-1,P-2 Connection to the earth CN20,CN23,CN25 Output: Pin1Connection of the high voltage),Pin2~Pin3230VAC High voltage CN15 Input: Pin1,Pin3,Pin5(5V)Pin2,Pin4,Pin60~5V CN37 Output: Pulse(0-320VDC) for DC FAN CN38 Input: Pin1~Pin217VDC N-OUT~L-OUT Output: 230VAC High voltage CN21 input: Pin1~Pin312VDC),Pin2~Pin35VDC),Pin4~Pin30~5VDC),Pin5~Pin30~5VDC CN39 Input: 270~370VDC High voltage
OUTDOOR UNIT IPM BOARD
CN4~CN5 Output: 230VAC High voltage CN2,CN3 Connect to Reactor, (270~370VDC) CN6 Output: Pin1~Pin217VDC CN1 Output: Pin1~Pin312VDC),Pin2~Pin35VDC),Pin4~Pin30~5VDC),Pin5~Pin30~5VDC), CN11~CN12 Output: 270~370VDC High voltage U~V~W Connect to compressor voltage among phases 0~200VAC
27
Fig. 21 – Wiring Diagrams 27k
OUTDOOR UNIT CONTROL BOARD SIZE 27
CODE PARTNAME
CN18/CN19/CN22 Output:Pin5&6(12V) Pin1-Pin4:Pulse waveform,(0-12V) CN17 Input:Pin3~4 (5V) Pin2(0V),Pin1,Pin5(0-5V) CN7 Input:Pin1 (0-5V) Pin2(5V) CN1~CN2CN5~CN6 Output: CN1~CN2CN5~CN6230VAC High voltage P1~P2 Output: Connectionof the high voltage CN3~CN4 Input:230VAC High voltage CN14 InputPin1,Pin3(0V)Pin2,Pin40~5V P-1,P-2 Connection to the earth CN20,CN23,CN25 Output: Pin1Connection of the high voltage),Pin2~Pin3230VAC High voltage CN15 Input: Pin1,Pin3,Pin5(5V)Pin2,Pin4,Pin60~5V CN37 Output: Pulse(0-320VDC) for DC FAN CN38 Input: Pin1~Pin217VDC N-OUT~L-OUT Output: 230VAC High voltage CN21 input: Pin1~Pin312VDC),Pin2~Pin35VDC),Pin4~Pin30~5VDC),Pin5~Pin30~5VDC CN39 Input: 270~370VDC High voltage
OUTDOOR UNIT IPM BOARD
CN4~CN5 Output: 230VAC High voltage CN2,CN3 Connect to Reactor, (270~370VDC) CN6 Output: Pin1~Pin217VDC CN1 Output: Pin1~Pin312VDC),Pin2~Pin35VDC),Pin4~Pin30~5VDC),Pin5~Pin30~5VDC), CN11~CN12 Output: 270~370VDC High voltage U~V~W Connect to compressor voltage among phases 0~200VAC
28
Fig. 22 – Wiring Diagram 36k
OUTDOOR UNIT CONTROL BOARD SIZE 36
CODE PARTNAME
CN17/CN18/CN19/CN20/CN21 Output:Pin5&6(12V) Pin1-Pin4:Pulse waveform,(0-12V) CN8 Input:Pin3~4 (5V) Pin2(0V),Pin1,Pin5(0-5V) CN33 Input:Pin1 (0-5V) Pin2(5V) CN4~CN40CN10~CN44 Output: CN4~CN40CN10~CN44230VAC High voltage CN3~CN22 Output: High voltage for 4-way control CN1~CN2 Input:230VAC High voltage CN9 InputPin1,Pin3(0V)Pin2,Pin40~5V P-1 Connection to the earth CN27,CN28,CN29,CN30 Output: Pin1Connection of the high voltage),Pin2~Pin3230VAC High voltage CN13 Input: Pin1,Pin3,Pin5(5V)Pin2,Pi n4,Pin60~5V CN12 Output: Pulse(0-200VAC)for DC FAN CN11 Output: Pulse(0-200VAC)for DC FAN CN5~CN6 Output: 230VAC High voltage
CN7
CN4~CN5 Output: 230VAC High voltage CN2,CN3 Connect to Reactor, (270~370VDC) CN6 Output: Pin1~Pin217VDC CN1 Output: Pin1~Pin312VDC),Pin2~Pin35VDC),Pin4~Pin30~5VDC),Pin5~Pin30~5VDC), CN11~CN12 Output: 270~370VDC High voltage U~V~W Connect to compressorvoltage among phases 0~200VAC
input: Pin1~Pin312VDC),Pin2~Pin3(5VDC),Pin4~Pin30~5VDC),Pin5~Pin30~5VDC),Pin6~Pin30~5VDC), Pin7~Pin30~5VDC
OUTDOOR UNIT IPM BOARD
29
Fig. 23 – Wiring Diagrams 48K
OUTDOOR UNIT CONTROL BOARD SIZE 48
CODE PART NAME
CN1,CN3P-1 Power input: 230V AC CN2,CN4 Output: Power output for DRIVER BOARD (230V AC) CN5 Input: Communication Main board and IPM Board ,Pin1(5V DC ) CN6 Input: DC FAN motor1 and DC FAN motor2 control, (Pin7 5V DC) CN8,CN9 Input: Temperature sensor(5V DC) CN10 Input: Pressure test (5V DC) CN13 Input: Indoor pipe Temperature sensor,Pin1&Pin3&Pin5&Pin7&Pin9&Pin11 (5V DC) CN15,CN23,CN26, CN30,CN33 Output: PMV controlPin5(12V DC),Pin6(12V DC) CN17,CN18 Output: High voltage for 4-way(SV) control (230V AC) CN19,CN20 Output: High voltage for HEAT_D control (230V AC) CN13,CN16,CN21, CN29,CN37 Output: Communication to indoor unit,Pin2 and Pin3 (230V AC ),Pin1 (S, connection to high voltage) CN24,CN25 Output: High voltage for HEAT_Y control(230V AC) CN27CN32CN34
CN28CN31CN36 CN39 Output: L2 forAC FANSV and HEAT ,High voltage (AC) P-5,P-6 Connection to the earth
UVW Output: Pulse(0-380VDC) for COMPRESSOR CN3 CN6 ,CN8 Input: Power input for DRIVER BOARD (200-320V DC )
CN7,CN11 Output: DC FAN motor1 and DC FAN motor2 control (Pin1 310V or 380V DC) CN9 Output: Communication Main board and IPM Board Pin7(5V DC ) CN55 Output: Communication IPM Board and Main board Pin1(12V DC ) CN14CN15-- CN39, Output: High DC voltage (310V or 380V DC)
Output: Power output for AC FANmotor1 and AC FAN motor2 (230V AC)
OUTDOOR UNIT IPM BOARD
Output: Connect PFC Inductance, high DC voltage
30
Size Range:1 1/2, 2 1/4, 3 and 4 Ton Nominal Cooling and Heating Capacity
PART1–GENERAL
1.01 System Description
A. Outdoor air- cooled split sys t em compressor se ctions suitabl e for
on- the- ground, rooftop, wall hung or balc ony mounting. Units shall consist of a variable speed rotary compressor, an air- cooled coil, propeller-t ype draw- through outdoor fan, reversing valve , accumulator , electronic expansion valves, multiple service valves, and controls that allows multiple indoor unit s to be connected to the outdoor unit. Units shall discha rge horizontal ly as shown on the contract drawings. Units shall function as the outdoor component of an air-t o-air hea t pump syste m .
B. Units shall be used in a refrigeration circuit matched to two,
three, four, or five multi style heat pump fan coil units.
1.02 Agency Listings
A. Unit construction shall comply with ANSI/ASHRAE 15, latest
revision, and with NEC.\
B. Units shall be evaluated in accordance with UL standard 1995. C. Units shall be listed in CEC directory.
D. Unit cabinet shall be capable of withstanding 500-hour salt
spray test per Federal Test Standard no. 141 (method 6061).
E. Air-cooled condenser coils shall be leak tested at 550 psig.
1.03 Delivery, Storage, And Handling
Units shall be shipped in one piece and shall be stored and handled per manufacturer’s recommendations.
1.04 Warranty (For Inclusion By Specifying Engineer)
PART 2 – PRODUCTS
2.01 Equipment
A. General:
Factory assembled, single piece, air-cooled outdoor unit. Contained within the enclosure shall be all factory wiring, piping, controls, and compressor.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel, bonderized and coated with baked-enamel finish on inside and outside.
2. Unit access panel should be removable with minimal screws and shall provide full access to the compressor, fan, and control components.
3. Outdoor compartment shall be isolated and have an acoustic lining to assure quiet operation.
C. Fans:
1. Outdoor fans shall be direct-drive propeller type, and shall discharge air horizontally. Fan shall draw air through the outdoor coil.
2. Outdoor fan motors shall be multi- speed, totally-enclosed, single phase motors with permanently lubricated ball bearings. Motor shall be protected by internal thermal overload protection.
3. Shaft shall have inherent corrosion resistance.
4. Outdoor fan openings shall be equipped with metal/mesh PVC coated protection grille over fan.
GUIDE SPECIFICATIONS
HORIZONTAL DISCHARGE OUTDOOR UNITS
Carrier Model Number: 38MG
D. Compressor
1. Compressor shall be fully hermetic variable speed rotary type.
2. Compressor shall be single phase, inverter driven.
3. Compressor shall be equipped with oil system, operating oil charge, and motor .
4. Motor shall be suitable for operation in refrigerant and oil atmosphere.
5. Compressor assembly shall be installed on rubber vibration isolators.
6. The inverter and compressor shall be protected against over temperature and over current.
E. Outdoor Coil:
Coil shall be constructed of Aluminum fins mechanically bonded to seamless copper tubes, which are cleaned, dehydrated and sealed.
F. Refrigerant Components:
Refrigerant circuit components shall include multiple brass external liquid line service valves with service gauge connection port, multiple suction line service valves with service gage connection port, accumulator, reversing valve, electronic expansion valves.
G. Safeties:
Operating safeties shall be factory selected, assembled, and tested. The minimum functions shall include the following:
1. Compressor discharge over temperature protection.
2. System low voltage protection.
3. Compressor overload protection.
4. Compressor over current protection.
5. IPM module protection.
H. Electrical Requirements:
1. Units shall operate on single-phase, 60 Hz power at 208/230 v.
2. Unit electrical power shall be a single point connection.
3. All power and control wiring must be installed per NEC and all local electrical codes.
4. Units shall have multiple terminal blocks to connect to multiple indoor units.
31
PART1–GENERAL
1.01 System Description
Indoor, wall-mounted, direct expansion fan coils are matched with heat pump outdoor units.
1.02 Agency Listings
Unit shall be rated per AHRI Standards 210/240 and listed in the AHRI directory as a matched system.
1.03 Delivery, Storage, And Handling
Units shall be shipped in one piece and shall be stored and handled per manufacturer’s recommendations.
1.04 Warranty (For Inclusion By Specifying Engineer)
PART 2 – PRODUCTS
2.01 Equipment
A. General:
Indoor, direct-expansion, wall-mounted fan coil. Unit shall be complete with cooling/heating coil, fan, fan motor, piping connectors, electrical controls, microprocessor control system, and integral temperature sensing. Unit shall be furnished with integral wall mounting bracket and mounting hardware.
B. Unit Cabinet:
Cabinet discharge and inlet grilles shall be attractively styled, high-impact polystyrene. Cabinet shall be fully insulated for improved thermal / acoustic performance.
C. Fans:
1. Fan shall be tangential direct-drive blower type with air intake at the top of the unit and discharge at the bottom front. Automatic, motor-driven vertical air sweep shall be provided standard.
2. Air sweep operation shall be useable selectable. The vertical sweep may be adjusted (using the remote control) and the horizontal air direction maybe be set manually.
D. Coil:
Coil shall be copper tube with aluminum fins and galvanized steel tube sheets. Fins shall be bonded to the tubes by mechanical expansion. A drip pan under the coil shall have a drain connection for hose attachment to remove condensate. Condensate pan shall have internal trap.
E. Motors:
Motors shall be totally enclosed, permanently lubricated ball bearing with inherent overload protection. Fan motors shall be 3- speed.
F. Co nt rols:
Controls shall consist of a microprocessor-based control system which shall control space temperature, determine optimum fan speed, and run self diagnostics. The temperature control range shall be from 62_Fto86_F(17_Cto30_C) in increments of 1_For 1_C, and have 46_F Heating Mode (Heating Setback). The wireless remote controller shall have the ability to act as the temperature sensing location for room comfort.
GUIDE SPECIFICATIONS
INDOOR WALL-MOUNTED DUCTLESS UNITS
Size Range: 3/4 to 2 Ton Nominal Cooling and Heating Capacity
Carrier Model Number: 40MAQ
The unit shall have the following functions as a minimum:
S An automatic restart after power failure at the same
operating conditions as at failure.
S A timer function to provide a minimum 24 - hour timer
cycle for system Auto Start/Stop.
S Temperature- sensing controls shall sense return air
temperature.
S Indoor coil freeze protection. S Wireless infrared remote control to enter set points and
operating conditions.
S Automatic air sweep control to provide on or off
activation of air sweep louvers.
S Dehumidification mode shall provide increased latent
removal capability by modulating system operation and set point temperature.
S Fan- only operation to provide room air circulation when
no cooling is required.
S Diagnostics shall provide continuous checks of unit
operation and warn of possible malfunctions. Error messages shall be displayed at the unit.
S Fan speed control shall be user- selectable: turbo, high,
medium, low, or microprocessor controlled automatic operation during all operating modes.
S Automatic heating- to- cooling changeover in heat pump
mode. Control shall include deadband to prevent rapid mode cycling between heating and cooling.
S Indoor coil high temperature protection shall be provided
to detect excessive indoor discharge temperature when unit is in heat pump mode.
G. Filters:
Units shall have filter track with factory-supplied cleanable filters.
H. Electrical Requirements:
Indoor fan motor to operate on 208- 230V. Power is supplied from the outdoor unit.
I. Operating Characteristics:
The system shall have a minimum SEER (Seasonal Energy Efficiency Ratio) and HSPF at AHRI conditions, as listed on the specifications table.
J. Refrigerant Lines:
All units should have refrigerant lines that can be oriented to connect from the left, right or back of unit. Both refrigerant lines need to be insulated.
K. Special Features (Field Installed):
1. Condensate Pump: The condensate pump shall remove condensate from the drain pan when gravity drainage cannot be used. Pump shall be designed for quiet operation. Pump shall consist of two parts: an internal reservoir/sensor assembly, and a remote sound- shielded pump assembly. A liquid level sensor in the reservoir shall stop cooling operation if the liquid level in the reservoir is unacceptable.
32
PART 1 - GENERAL
1.01 System Description
Indoor, in- ceiling, direct-expansion fan coils are matched with heat pump outdoor unit .
1.02 Agency Listings
Unit shall be rated per AHRI Standards 210/240 and listed in the AHRI directory as a matched system.
1.03 Delivery, Storage, And Handling
Units shall be stored and handled per unit manufacturer’s recommendations.
1.04 Warranty (For Inclusion By Specifying Engineer)
PART 2 - PRODUCTS
2.01 Equipment General:
Indoor, direct- expansion, in-ceiling cassette fan coil. Unit shall be complete with cooling/heating coil, fan, fan motor, piping connectors, electrical controls, microprocessor control system, and integral temperature sensing.
Unit Cabinet:
Cabinet shall be constructed of zinc- - coated steel. Fully insulated discharge and inlet grilles shall be attractively styled, high- impact polystyrene. Grille shall have hinges and can be opened to obtain access to the cleanable filters, indoor fan motor and control box.
Fans:
Fan shall be centrifugal direct- - drive blower type with
S
air intake in the center of the unit and discharge at the perimeter. Automatic, motor- - driven vertical air sweep shall be provided standard. Automatic motor- - driven louvers shall be provided standard and shall be adjustable for 2, 3 or 4- - way discharge.
S Air sweep operation shall be user selectable.
Coil:
Coil shall be copper tube with aluminum fins and galvanized steel tube sheets. Fins shall be bonded to the tubes by mechanical expansion and specially coated for enhanced wet-ability. A drip pan under the coil shall have a factory installed condensate pump and drain connection for hose attachment to remove condensate.
Motors:
Motors shall be open drip- proof, permanently lubricated ball bearing with inherent overload protection. Fan motors shall be 4- speed.
Controls:
Controls shall consist of a microprocessor- based control system which shall control space temperature, determine optimum fan speed, and run self diagnostics. The temperature control range shall be from 62_Fto86_F(17_Cto30_C) in increments of 1_For 1_C, and have 46_F Heating Mode (Heating Setback). The wireless remote controller, shall have the ability to act as the temperature sensing location for room comfort.
GUIDE SPECIFICATIONS
INDOOR CASSETTE DUCTLESS UNITS
Size Range: 3/4 to 1 1/2 Ton Nominal Cooling and Heating Capacity
Carrier Model Number: 40MB*C
The unit shall have the following functions as a minimum:
S An automatic restart after power failure at the same
operating conditions as at failure.
S A timer function to provide a minimum 24 - hour timer
cycle for system Auto Start/Stop.
S Temperature- sensing controls shall sense return air
temperature.
S Indoor coil freeze protection. S Wireless infrared remote control to enter set points and
operating conditions.
S Automatic air sweep control to provide on or off
activation of air sweep louvers.
S Dehumidification mode shall provide increased latent
removal capability by modulating system operation and set point temperature.
S Fan- only operation to provide room air circulation when
no cooling is required.
S Diagnostics shall provide continuous checks of unit
operation and warn of possible malfunctions. Error messages shall be displayed at the unit.
S Fan speed control shall be user- selectable: high,
medium, low, or microprocessor controlled automatic operation during all operating modes.
S Automatic heating- to- cooling changeover in heat pump
mode. Control shall include deadband to prevent rapid mode cycling between heating and cooling.
S Indoor coil high temperature protection shall be provided
to detect excessive indoor discharge temperature when unit is in heat pump mode.
Filters:
Unit shall have filter track with factory- supplied cleanable filters.
Electrical
Indoor fan motor to operate on 208- 230V. Power is supplied from the outdoor unit.
Operating
The system shall have a minimum SEER (Seasonal Energy Efficiency Ratio) and HSPF at AHRI conditions, as listed on the specifications table.
Refrigerant
All units should have refrigerant lines that can be oriented to connect from the left, right or back of unit. Both refrigerant lines need to be insulated.
Requirements:
Characteristics:
Lines:
33
PART 1 - GENERAL
1.01 System Description
Indoor, ceiling- mounted, direct-expansion fan coils are matched with a heat pump outdoor unit.
1.02 Agency Listings
Unit shall be rated per AHRI Standards 210/240 and listed in the AHRI directory as a matched system.
1.03 Delivery, Storage, And Handling
Units shall be stored and handled per unit manufacturer’s recommendations.
1.04 Warranty (For Inclusion By Specifying Engineer)
PART 2 - PRODUCTS
2.01 Equipment General:
A.
Indoor, direct- expansion, ceiling- mounted fan coil. Unit shall be complete with cooling/heating coil, fan, fan motor, piping connectors, electrical controls, microprocessor control system, and integral temperature sensing.
B, Unit Cabinet:
Unit cabinet shall be constructed of galvanized steel. Cabinet shall be fully insulated for improved thermal and acoustic performance.
C. Fans:
Fan shall be tangential direct- drive blower type with air intake at the rear or bottom of the unit and discharge at the front.
D. Coil:
Coil shall be copper tube with aluminum fins and galvanized steel tube sheets. Fins shall be bonded to the tubes by mechanical expansion. A drip pan under the coil shall have a factory installed condensate pump and drain connection for hose attachment to remove condensate.
E. Motors:
Motors shall be open drip- proof, permanently lubricated ball bearing with inherent overload protection. Fan motors shall be 3- speed.
F. Controls:
Controls shall consist of a microprocessor-based control system which shall control space temperature, determine optimum fan speed, and run self diagnostics. The temperature control range shall be from 62_Fto86_F(17_Cto30_C) in increments of 1_For 1_C, and have 46_F Heating Mode (Heating Setback). The wireless remote controller shall have the ability to act as the temperature sensing location for room comfort.
GUIDE SPECIFICATIONS
INDOOR DUCTED UNITS
Size Range: 3/4 to 2 Ton Nominal Cooling and Heating Capacity
Carrier Model Number: 40MB*D
The unit shall have the following functions as a minimum:
1. An automatic restart after power failure at the same operating conditions as at failure.
2. A timer function to provide a minimum 24- hour timer cycle for system Auto Start/Stop.
3.Temperature- sensing controls shall sense return air temperature.
4. Indoor coil freeze protection.
5. Wireless infrared remote control to enter set points and operating conditions.
6. De-humidification mode shall provide increased latent removal capability by modulating system operation and set point temperature.
7. Fan- only operation to provide room air circulation when no cooling is required.
8. Diagnostics shall provide continuous checks of unit operation and warn of possible malfunctions. Error messages shall be displayed at the unit.
9.Fan speed control shall be user-selectable: high, medium, low, or microprocessor controlled automatic operation during all operating modes.
10.Automatic heating- to- cooling changeover in heat pump mode. Control shall include deadband to prevent rapid mode cycling between heating and cooling.
11.Indoor coil high temperature protection shall be provided to detect excessive indoor discharge temperature when unit is in heat pump mode.
G. Electrical Requirements:
Indoor fan motor to operate on 208- 230V. Power is supplied from the outdoor unit.
H. Operating Characteristics:
The system shall have a minimum SEER (Seasonal Energy Efficiency Ratio) and HSPF at AHRI conditions, as listed on the specifications table.
I. Refrigerant Lines:
All units should have refrigerant lines that can be oriented to connect from the side of the unit. Both refrigerant lines need to be insulated.
34
PART 1 - GENERAL
1.01 System Description
Indoor, wall-mounted, direct-expansion fan coils are matched with a heat pump outdoor unit.
1.02 Agency Listings
Unit shall be rated per AHRI Standards 210/240 and listed in the AHRI directory as a matched system.
1.03 Delivery, Storage, And Handling
Units shall be stored and handled per unit manufacturer’s recommendations.
1.04 Warranty (For Inclusion By Specifying
Engineer)
PART 2 - PRODUCTS
2.01 Equipment
A. General:
Indoor, direct-expansion, floor-mounted fan coil. Unit shall be complete with cooling/heating coil, fan, fan motor, piping connectors, electrical controls, microprocessor control system, and integral temperature sensing. Unit shall be furnished with integral mounting bracket and mounting hardware.
B. Unit Cabinet:
Cabinet discharge and inlet grilles shall be attractively styled, high- impact polystyrene. Cabinet shall be fully insulated for improved thermal and acoustic performance.
CFans:
1. Fan shall be tangentia l direct- drive blower type wit h ai r intake in
the center of the unit and discharge at the top and bottom front. Automat ic, motor- driven vertical air sweep shall be provided standard.
2. Air sweep operation shall be user selectable. The vertical sweep
may be adjusted (using the remote control) and the horizontal air direction may be set manually.
D. Coil:
Coil shall be copper tube with aluminum fins and galvanized steel tube sheets. Fins shall be bonded to the tubes by mechanical expansion. A drip pan under the coil shall have a drain connection for hose attachment to remove condensate. Condensate pan shall have internal trap.
E. Motors:
Motors shall be open drip- proof, permanently lubricated ball bearing with inherent overload protection. Fan motors shall be 3- speed.
F Controls:
Controls shall consist of a microprocessor-based control system which shall control space temperature, determine optimum fan speed, and run self diagnostics. The temperature control range shall be from 62_Fto86_F(17_Cto30_C) in increments of 1_For 1_C, and have 46_F Heating Mode (Heating Setback). The wireless remote controller shall have the ability to act as the temperature sensing location for room comfort.
GUIDE SPECIFICATIONS
INDOOR FLOOR CONSOLE DUCTLESS UNITS
Size Range: 3/4 to 1 Ton Nominal Cooling and Heating Capacity
Carrier Model Number: 40MB*F
The unit shall have the following functions as a minimum:
1. An automatic restart after power failure at the same operating conditions as at failure.
2. A timer function to provide a minimum 24- hour timer cycle for system Auto Start/Stop.
3.Temperature- sensing controls shall sense return air temperature.
4. Indoor coil freeze protection.
5.Wireless infrared remote control to enter set points and operating conditions.
6. Automatic air sweep control to provide on or off activation of air sweep louvers.
7. De humidification mode shall provide increased latent removal capability by modulating system operation and set point temperature.
8. Fan- only operation to provide room air circulation when no cooling is required.
9. Diagnostics shall provide continuous checks of unit operation and warn of possible malfunctions. Error messages shall be displayed at the unit.
10. Fan speed control shall be user- selectable: high, medium, low, or microprocessor controlled automatic operation during all operating modes.
11. Automatic heating- to- cooling changeover in heat pump mode. Control shall include deadband to prevent rapid mode cycling between heating and cooling.
12. Indoor coil high temperature protection shall be provided to detect excessive indoor discharge temperature when unit is in heat pump mode.
G. Filters: Unit shall have filter track with factory- supplied cleanable filters.
H. Electrical Requirements: Indoor fan motor to operate on 208- 230V as specified. Power is supplied from the outdoor unit. I. Operating Characteristics: The system shall have a minimum SEER (Seasonal Energy Efficiency Ratio) and HSPF at AHRI conditions, as listed on the specifications table.
J. Refrigerant Lines:
All units should have refrigerant lines that can be oriented to connect from the left, right or back of unit. Both refrigerant lines need to be insulated.
K. Special Features (Field Installed):
1. Condensate Pump: The condensate pump shall remove condensate from the drain pan when gravity drainage cannot be used. Pump shall be designed for quiet operation. Pump shall consist of two parts: an internal reservoir/sensor assembly, and a remote sound- shielded pump assembly. A liquid level sensor in the reservoir shall stop cooling operation if the liquid level in the reservoir is unacceptable.
35
Copyright 2015 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Manufacturer r eserves the right to change, at any time, specifications and designs without notice and without obligations.
Edition Date: 05/15
36
Catalog No. 38MG - 02PD
Replaces: 38MG- 01PD