Carrier 40MBFQ123 Specifications

Page 1
40MBFQ Floor Console Ductless System Sizes 09 to 12
Product Data
INDUSTRY LEADING FEATURES / BENEFITS
The 40MBFQ series ductless system are a matched combination of an outdoor condensing unit and an indoor fan coil unit connected only by refrigerant tubing and wires.
The fan coil is mounted on the floor, against the wall. This selection of fan coils permits creative solutions to design problems such as:
NOTE: Image for illustration purposes only. Actual model may differ slightly.
S Add−ons to current space (an office or family room
addition)
S Special space requirements S When changes in the load cannot be handled by the
existing system.
S When adding air conditioning to spaces that are heated
by hydronic or electric heat and have no ductwork.
S Historical renovations or any application where
preserving the look of the original structure is essential.
The ideal compliment to your ducted system when it is impractical or prohibitively expensive to use ductwork.
These compact indoor fan coil units take up very little space in the room and do not obstruct windows. The fan coils are attractively styled to blend with most room decors. Advanced system components incorporate innovative technology to provide reliable cooling performance at low sound levels.
Page 2

LOW SOUND LEVELS

When noise is a concern, the ductless systems are the answer. The indoor units are whisper quiet. There are no compressors indoors, either in the conditioned space or directly over it, and there is none of the noise usually generated by air being forced through ductwork.

SECURE OPERATION

If security is an issue, outdoor and indoor units are connected only by refrigerant piping and wiring to prevent intruders from crawling through ductwork. In addition, since outdoor units can be installed close to an outside wall, coils are protected from vandals and severe weather.

FAST INSTALLATION

This compact ductless system is simple to install. A mounting bracket is standard with the indoor units and only wire and piping need to be run between the indoor and outdoor units. These units are fast and easy to install ensuring minimal disruption to customers in the home or workplace. This makes the ductless systems the equipment of choice, especially in retrofit situations.

SIMPLE SERVICING AND MAINTENANCE

Removing the top panel on the outdoor units provides immediate access to the control compartment, providing a service technician access to check the unit’s operation. In addition, the draw−thru design of the outdoor section means that dirt accumulates on the outside surface of the coil. Coils can be cleaned quickly from the inside using a pressure hose and detergent.
On all indoor units, service and maintenance expense is reduced due to easy−to−use cleanable filters. In addition, these floor console systems have extensive self−diagnostics to assist in troubleshooting.
BUILT−IN RELIABILITY
Ductless system indoor and outdoor units are designed to provide years of trouble−free operation.
The floor console indoor units include protection against freeze−up and high evaporator temperatures on heat pumps.
The condensing units on heat pumps are protected by a three minute time delay before the compressor starts the over−current protection and the high temperature protection.

INDIVIDUAL ROOM COMFORT

Maximum comfort is provided because each space can be controlled individually based on usage pattern. The air sweep feature provided permits optimal room air mixing to eliminate hot and cold spots for occupant comfort. In addition, year−round comfort can be provided with heat pumps.

ECONOMICAL OPERATION

The ductless system design allows individual room heating or cooling when required. There is no need to run large supply−air fans or chilled water pumps to handle a few spaces with unique load patterns. In addition, because air is moved only in the space required, no energy is wasted moving air through ducts.
EASY−TO−USE CONTROLS
The floor console units have microprocessor−based controls to provide the ultimate in comfort and efficiency. The user friendly wireless remote control provides the interface between user and the unit.

ACCESSORIES

Customizing these ductless systems to your application is easily accomplished.
Adding a condensate pump accessory to the floor console fan coil provides installation flexibility.
OPTIONAL WIRED CONTROLLER AGENCY LISTINGS
All systems are listed with AHRI (Air Conditioning, Heating & Refrigeration Institute), and ETL.
2
Page 3

MODEL NUMBER NOMENCLATURE

INDOOR UNIT
QF-
40= FAN COIL UNIT
MB = MODEL
INDOOR FAN COIL TYPE F= FLOOR CONSOLE
40 MB 309
- -
VOLTAGE 3 = 208/230-1-60
SYSTEM TYPE Q = HEAT PUMP
NOMINAL CAPACITY 09 - 3/4 TON 12 - 1 TON
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program For verification of certification for individual products, go to www.ahridirectory.org.
NOT USED
NOT USED
3
Page 4

STANDARD FEATURES AND ACCESSORIES

Ease Of Installation
Mounting Brackets S Low Voltage Controls S
Comfort Features
Microprocessor Controls S Wired Remote Control A Wireless Remote Control S Automatic Up-Down Air Sweep S Air Direction Control S Auto Restart Function S Cold Blow Protection On Heat Pumps S Freeze Protection Mode On Heat Pumps S Turbo Mode S Silence Mode S Auto Changeover On Heat Pumps S
Follow Me S
Energy Saving Features
Sleep Mode S Stop/Start Timer S
46°F Heating Mode (Heating Setback)
Safety And Reliability
Indoor Coil Freeze Protection S
Aluminum Blue Hydrophilic pre-coated fins S
Indoor Coil High Temp Protection in Heating Mode S
Ease Of Service And Maintenance
Cleanable Filters S Diagnostics S Liquid Line Pressure Taps S
Application Flexibility
Condensate Pumps A
Legend
S Standard A Accessory
S

INDOOR UNITS

On the floor console fan coils, the condensate pump has a lift capability of 12 ft. (3.6 m) on the discharge side with the pump mounted in the fan coil or 6 ft. (1.8 m) on the suction side if the pump is remote mounted.
The pump is recommended when an adequate drain line pitch cannot be provided, or when the condensate must move up to exit.
Fig. 1 – Condensate Pump Accessory

ACCESSORIES

ORDERING NO. DESCRIPTION FOR MODELS
53DS-900---118 Condensate Pump (230v) All Sizes
KSACN0101AAA Wired Remote Control All Sizes
KSACN0401AAA
53DS-900---089
53DS-900---008
Wired Remote Control 7 Day Programmable compatible with indoor units starting with serial number 0217V10001
Insulated 25’
Line Set - 1/4” x 3/8”
Insulated 25’
Line Set - 1/4“ x 1/2”
All Sizes
Size 09
Size 12
4
Page 5
DIMENSIONS − INDOOR
23.62(600)
27.56(700)
Hanging arm
7.68(195)
0.63(16) Drain pipe
8.27(210)
Unit: in (mm)
Fig. 2 – Indoor Unit
UNIT SIZE 9 12
Depth in (mm) 8.27 (210) 8.27 (210) Width in (mm) 27.56 (700) 27.56 (700)
Height in (mm) 23.62 (600) 23.62 (600)
Weight-Net Lb (kg.) 32.41 (14.7) 32.41 (14.7)
5
Page 6
CLEARANCES − INDOOR
Fig. 3 – Indoor Unit Clearance

SPECIFICATIONS

Heat Pump
System
Electrical
Controls
Operating
Range
Piping
Indoor
Performance may vary based on the compatible outdoor units. See respective product data for performance data.
Size 9 12
Indoor Model 40MBFQ09---3 40MBFQ12---3
Voltage, Phase, Cycle V/Ph/Hz 208/230-1-60 208/230-1-60
Power Supply Indoor unit powered from outdoor unit
MCA A. 0.29 0.29
Wireless Remote Controller (°F/°C Convertible) Standard Standard
Wired Remote Controller (°F/°C Convertible) Optional Optional
Cooling Indoor DB Min -Max ° F (° C) 63~90 (17~32) 63~90 (17~32)
Heating Indoor DB Min -Max ° F (° C) 32~86 (0~30) 32~86 (0~30)
Pipe Connection Size - Liquid in (mm) 1/4 (6.35) 1/4 (6.35)
Pipe Connection Size - Suction in (mm) 3/8 (9.52) 1/2 (12.7)
Unit Width in (mm) 27.56 (700) 27.56 (700)
Unit Height in (mm) 23.62 (600) 23.62 (600)
Unit Depth in (mm) 8.27 (210) 8.27 (210)
Net Weight lbs (kg) 32.41 (14.7) 32.41 (14.7)
Number of Fan Speeds 3 3
Airflow (lowest to highest) CFM 220/250/280 220/250/280
Sound Pressure (lowest to highest) dB(A) 37/38/41 34/41/45
Field Drain Pipe Size O.D. in (mm) 1 (25.4) 1 (25.4)

COMPATIBILITY TABLE

Indoor Unit 40MBFQ09---3 40MBFQ12---3
Outdoor Unit Single Zone 38MAQB09R--3 38MAQB12R--3
Outdoor Unit Multi-zone
NOTE: Backward compatible with 38MAQ Single Zone and 38MGQ Multi−zone Systems.
6
38MGRQ18B--3
38MGRQ24C--3
38MGRQ30D--3
38MGRQ36D--3
38MGRQ48E--3
Page 7

APPLICATION DATA

UNIT SELECTION

Select equipment to either match or is slightly less than the anticipated peak load. This provides better humidity control, fewer unit cycles, and less part−load operation.
For units used in spaces with high sensible loads, base equipment selection on unit sensible load, not on total anticipated load. Adjust for anticipated room wet bulb temperature to avoid undersizing equipment.

UNIT MOUNTING (INDOOR)

Refer to the unit’s Installation Instructions for further details. Unit leveling − For reliable operation, units should be level in all
planes. Clearance − Provide adequate clearance for airflow as shown in
Fig. 3. Unit location − Select a location which provides the best air
circulation for the room. These units should be positioned on the floor, against the wall for
the best air circulation. The unit return and discharge should not be obstructed by furniture, curtains, or anything which may cause unit short cycling or air recirculation. Place the unit in the middle of the selected wall (if possible). Use an outside wall, if available, to make piping easier, and place the unit so it faces the normal location of room occupants.

UNIT MOUNTING (OUTDOOR)

Refer to the unit’s Installation Instructions for further details.
Do not install the indoor or outdoor units in a location with special environmental conditions. For those applications, contact your ductless representative.

MOUNTING TEMPLATE

Refer to the unit’s Installation Instructions for further details.
The fan coil units are furnished with mounting to mark the location of the wiring, and refrigeration line hole locations.

SUPPORT

Adequate support must be provided to support the weight of all the fan coils. Refer to th e Physical Data section for the fan coil weights, and the base unit dimensional drawings for the mounting brackets location.

SYSTEM OPERATING CONDITIONS

OPERATING RANGE
Min / Max °F (°C)
Cooling Heating
Indoor DB 63 / 90 (17 / 32) 32 / 86 (0 / 30)
Indoor WB 59 / 84 (15 / 29)
NOTE: Reference the Product Installation Instructions for more information.

DRAIN CONNECTIONS

Install drains to meet the local sanitation codes. If adequate gravity drainage cannot be provided, the unit should be equipped with an accessory condensate pump. The floor console fan coil unit condensate pumps have a maximum lift of 10’ (3.05 m).
See the physical dimension tables for the drain sizes.
NOTE: Floor console fan coil units have internal condensate traps. A trap is not required.

REFRIGERANT LINES

General refrigerant line sizing:
1. The outdoor units are shipped with a full charge of R410A refrigerant.
2. Refrigerant lines should not be buried in the ground. If it is necessary to bury the lines, not more than 36−in (914 mm) should be buried. Provide a minimum 6−in (152 mm) vertical rise to the service valves to prevent refrigerant migration.
3. Both lines must be insulated. Use a minimum of 1/2−in. (12.7 mm) thick insulation. Closed−cell insulation is recommended in all long−line applications.
4. Special consideration should be given to isolating the interconnecting tubing from the building structure. Isolate the tubing so that vibration or noise is not transmitted into the structure.
7
Page 8

WIRING

All wires must be sized per NEC (National Electrical Code) or CEC (Canadian Electrical Code) and local codes. Use the Electrical Data table MCA (minimum circuit amps) and MOCP (maximum over current protection) to correctly size the wires and the disconnect fuse or breakers respectively. Per the caution note, only Stranded copper conductors with a 600 volt rating and double insulated copper wire must be used.
NOTE: The use of BX cable is not recommended.
Recommended Connection Method for Power and Communication Wiring −
Power and Communication Wiring:
The main power is supplied to the outdoor unit. The field supplied 14/3 power/communication wiring from the outdoor unit to the indoor unit consists of four (4) wires and provides the power for the indoor unit. Two wires are high voltage AC power, one is communication wiring and the other is a ground wire.
Recommended Connection Method for Power and Communication Wiring (To minimize communication wiring interference) PowerWiring:
The main power is supplied to the outdoor unit. The field supplied power wiring from the outdoor unit to the indoor unit consists of three (3) wires and provides the power for the indoor unit. Two wires are high voltage AC power and one is a ground wire.
To minimize voltage drop, the factory recommended wire size is 14/2 stranded with a ground.
Communication Wiring:
A separate shielded stranded copper conductor only, with a minimum 600 volt rating and double insulated copper wire, must be used as the communication wire from the outdoor unit to the indoor unit. Please use a separate shielded 16GA stranded control wire.
!
CAUTION

CONTROL SYSTEM

The unit is equipped with a microprocessor control to perform two functions:
1. Provide safety for the system
2. Control the system and provide optimum levels of comfort and efficiency
The main microprocessor is located on the control board of the fan coil unit (outdoor units have a microprocessor too) with thermistors located in the fan coil air inlet and on the indoor coil. Heat pump units have a thermistor on the outdoor coil. These thermistors monitor the system operation to maintain the unit within acceptable parameters and control the operating mode.

WIRELESS REMOTE CONTROL

Fig. 4 – Wireless remote control
1. A wireless remote control is supplied for system operation for system operation of all floor console units.
2. Each battery operated wireless (infrared) remote control may be used to control more than one unit.
WIRED REMOTE CONTROL (OPTIONAL)
1. Optional wired remote controller used for system operation of all floor console units.
2. Kit includes a wired remote controller and a connecting cable.
3. Connect the wire terminal between the remote controller and the indoor unit.
4. Display in _F or _C and temperature increments every 1_F or every 1_C.
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
S Wires should be sized based on NEC and local codes. S Use copper conductors only with a 600 volt rating and
double insulated copper wire.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
S Be sure to comply with local codes while running wire
from indoor unit to outdoor unit.
S Every wire must be connected firmly. Loose wiring
may cause terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
S No wire should be allowed to touch refrigerant tubing,
compressor or any moving parts.
S Disconnecting means must be provided and shall be
located within sight and readily accessible from the air conditioner.
S Connecting cable with conduit shall be routed through
hole in the conduit panel.
CAUTION
Fig. 5 – KSACN0101AAA (Timer Function)
Fig. 6 – KSACN0501AAA (7 Day Programmable)
8
Page 9

AIR FLOW DATA

SYSTEM SIZE 9 12
Indoor (CFM)

SOUND PRESSURE

SYSTEM SIZE 9 12
Cooling operation Indoor Sound
Pressure
Heating operation Indoor Sound
Pressure
Unit Outlet
High 280 280
Medium 250 250
Low 220 220
dBa (L/M/H) 37/38/41 34/41/45
dBa (L/M/H) 37/38/41 34/41/45

SOUND PRESSURE TESTING METHOD

Microphone
3.3ft (1m)
X
Indoor
Unit
Fig. 7 – Sound Pressure Testing Method

SOUND POWER

SYSTEM SIZE 9 12
Cooling operation Indoor Sound
Power
Heating operation Indoor Sound
Power
dBa (L/M/H) 46/47/50 44/51/55
dBa (L/M/H) 46/47/50 44/51/55

ELECTRICAL DATA

UNIT SIZE OPER. VOLTAGE MAX / MIN*
9
12
*Permissible limits of the voltage range at which the unit operates satisfactorily.
LEGEND
FLA - Full Load Amps
253 / 187 208-230/1/60
V-PH-HZ FLA HP W
INDOOR FAN
0.21 0.027 20
0.21 0.027 20
4.9 ft (1.5m)
MAX FUSE CB AMP
Refer to outdoor unit installation instructions –
Indoor unit powered by the outdoor unit
9
Page 10
FAN AND MOTOR SPECIFICATIONS
SYSTEM SIZE
material AS AS
Indoor fan
Indoor fan motor
Type LX-370*80*8-7JN LX-370*80*8-7JN
Diameter inch 14.6 14.6
Height inch 3.15 3.15
Model RD-280-20-8A RD-280-20-8A
Type DC DC
Phase 3 3
FLA 0.21 0.21
Insulation class E E
Safe class IPX0 IPX0
Input W 66.6 66.6
Output W 20 20
Range of current Amps 0.21±10% 0.21±10%
Rated current Amps 0.21 0.21
Rated HP HP 0.027 0.027
Speed rev/min 730/680/580/520 730/680/580/520
Rated RPM rev/min 1062 1062
Max. input W 66.6 66.6
9 12
(208-230V) (208-230V)
10
Page 11
WIRING DIAGRAM
FUNCTION OF SWITCHES
SWITCH BOARD
ON
ON
SW102
ON
1 2ON1 2
OFF
TEMP.ADJ
0 °C
FAN OFF
OFF
MO/MU FAN
2
°C
LOW FAN SPEED
SW103
4
°C
SETTING FAN SPEED
SWITCH BOARD
-2
°C
TERMAL
TO WIRE CONTROLLER
DISPLAY BOARD
CN10
CN15
J1
SW1
ON
ON
ON
ON
OFF
TYPE
SW2
1 2
1
OFF
MAIN CONTROL BOARD
L
NS
CN1
M1
CN3
XP4
XS4
M2
BLACK
XS1
XP1
RT2
PIPE
CN7
WHITE
XS2
XP2
RT1
ROOM
XS3
XP3
For outdoor power supply
L1 L2
S
XT1
TO OUTDOOR UNIT
Fig. 8 – Wiring Diagram − Sizes 9 and 12
CN2
L1 L2
S
For indoor power supply
L1 L2
TO OUTDOOR UNIT
WIRING DIAGRAM
CODE PART NAME
CN1-CN20
FAN
M1
XS5
XP5
EARTH
Y/G
XT1
S
FAN
Y/G Y/G
XT1
POWER
M2
RT1
RT2
XP1-XP5
XS1-XS5
XT1
J1
NOTICE 1: THE TYPE_SELECTION AND MO/MU HAS BEEN SET BEFORE LEAVING THE FACTORY,ANYONE CAN'T MODIFY IT EXCEPT THE MAINTENANCE PER SON.
CN20
NOTICE 2: PLEASE CUT OF F THE JUMPER IF YOU CONNECT THE N ET MODULE
(INDOOR UNIT)
P.C BOARD SOCKETS
INDOOR DC FAN MOTOR
UPPER OUTLET SWING MOT OR
LOWER OUTLET SWING MOT OR
ROOM TEMPERATURE
PIPE TEMPERATURE
CONNECTORS
CONNECTORS
4-WAY TERMINAL
JUMPER
MODULE
TO WIRE CONTROLLER
J1
INDOOR UNIT CONTROL BOARD
INDOOR UNIT
CODE PART NAME
CN1 Input: 230VAC High voltage Connection of the terminal
CN2 Input: 230VAC High voltage Connection of the terminal
CN3 Output: 24VDC Between CN2 Connection of the S signal
CN6 Output: 12VDC Connection of the Lower outlet swing motor
CN7 Output: 5VDC Connection of the Room and Pipe temperature
CN10 Output: 12VDC Connection of the Display board
CN13 Output: 12VDC Connection of the Upper outlet swing motor
CN15 Output: 1-5VDC Connection of the Switch board
CN16 Output: 320VDC Connection of the Fan high voltage
CN20 Output: 5VDC Connection of the Net module
CN23 Output: 1-12VDC Connection of the Remote switch
11
Page 12

GUIDE SPECIFICATIONS

INDOOR WALL−MOUNTED FLOOR CONSOLE DUCTLESS UNITS
Size Range: 3/4 to 1 Ton Nominal Cooling and Heating Capacity
Model Number: 40MBFQ
PART 1 − GENERAL
1.01 System Description
Indoor, wall−mounted floor console, direct−expansion fan coils are matched with a cooling only or heat pump outdoor unit.
1.02 Agency Listings
Unit is rated per AHRI Standards 210/240 and listed in the AHRI directory as a matched system.
1.03 Delivery, Storage, And Handling
Units are stored and handled per the unit manufacturer’s recommendations.
1.04 Warranty (For Inclusion By Specifying Engineer)
PART 2 − PRODUCTS
2.01 Equipment
A. General:
Indoor, direct−expansion, floor−mounted fan coil. Unit is complete with a cooling/heating coil, fan, fan motor, piping connectors, electrical controls, microprocessor control system, and integral temperature sensing. Unit is furnished with an integral mounting bracket and mounting hardware.
B. Unit Cabinet:
Cabinet discharge and inlet grilles are attractively styled, high−impact polystyrene. Cabinet is fully insulated for improved thermal and acoustic performance.
C. Fans:
1. Fan is the tangential direct−drive blower type with an air intake in the center of the unit and discharge at the top and bottom front. An automatic, motor−driven vertical air sweep is provided standard.
2. Air sweep operation is user selectable. The vertical sweep may be adjusted (using the remote control) and the horizontal air direction may be set manually.
D. Coil:
Coil is a copper tube with aluminum fins and galvanized steel tube sheets. Fins are bonded to the tubes by mechanical expansion and specially blue hydrophilic pre−coated for enhanced wet−ability. A drip pan under the coil shall has a drain connection for hose attachment to remove condensate. The condensate pan has an internal trap.
E. Motors:
The motors have an open drip−proof, permanently lubricated ball bearing with inherent overload protection. The fan motors are 4−speed.
F. Controls:
Controls consist of a microprocessor−based control system which controls the space temperature, determines the optimum fan speed, and runs self diagnostics. The temperature control ranges from 62_F to 86_F (17_C to 30_C) in increments of 1_F or 1_C, and have 46_F Heating Mode (Heating Setback). The wireless remote controller has the ability to act as the temperature sensing location for room comfort.
The unit shall have the following functions as a minimum:
1. An automatic restart after power failure at the same operating conditions as at failure.
2. A timer function to provide a minimum 24−hour timer cycle for system Auto Start/Stop.
3. Temperature−sensing controls to sense the return air temperature.
4. Indoor coil freeze protection.
5. Wireless infrared remote control to enter set points and operating conditions.
6. Automatic air sweep control to provide on or off activation of air sweep louvers.
7. Dehumidification mode to provide increased latent removal capability by modulating system operation and set point temperature.
8. Fan−only operation to provide room air circulation when no cooling is required.
9. Diagnostics to conduct continuous checks of unit operation and warn of possible malfunctions. Error messages appear on the unit.
10. Fan speed control is user−selectable: high, medium, low, or microprocessor controlled automatic operation during all operating modes.
11. Automatic heating−to−cooling changeover in heat pump mode. Control includes a deadband to prevent rapid mode cycling between heating and cooling.
12. Indoor coil high temperature protection is provided to detect excessive indoor discharge temperature when the unit is in heat pump mode.
G. Filters:
Unit has a filter track with factory−supplied cleanable filters.
H. Electrical Requirements:
Indoor fan motor to operate on 208−230V as specified. Power is supplied from the outdoor unit.
I. Operating Characteristics:
The 40MBFQ system has a minimum SEER (Seasonal Energy Efficiency Ratio) and HSPF at AHRI conditions, as listed on the specifications table.
J. Refrigerant Lines:
All units should have refrigerant lines that can be oriented to connect from the left, right or back of unit. Both refrigerant lines need to be insulated.
K. Special Features (Field Installed):
1. Condensate Pump:
− The condensate pump removes condensate from the drain pan when gravity drainage cannot be used. The pump is designed for quiet operation. The pump consists of two parts: an internal reservoir/sensor assembly, and a remote sound−shielded pump assembly. A liquid level sensor in the reservoir stops the cooling operation if the liquid level in the reservoir is unacceptable.
Copyright 2017 Carrier Corp D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Date: 02/17
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
12
Catalog No:40MBFQ-01PD
Replaces:NEW
Loading...