40MBFQ
Floor Console Ductless System
Sizes 09 to 12
Product Data
INDUSTRY LEADING
FEATURES / BENEFITS
A PERFECT BALANCE BETWEEN
BUDGET LIMITS, ENERGY SAVINGS AND
COMFORT.
The 40MBFQ series ductless system are a matched combination
of an outdoor condensing unit and an indoor fan coil unit
connected only by refrigerant tubing and wires.
The fan coil is mounted on the floor, against the wall. This
selection of fan coils permits creative solutions to design problems
such as:
NOTE: Image for illustration purposes only. Actual model may
differ slightly.
SAdd−ons to current space (an office or family room
addition)
SSpecial space requirements
SWhen changes in the load cannot be handled by the
existing system.
SWhen adding air conditioning to spaces that are heated
by hydronic or electric heat and have no ductwork.
SHistorical renovations or any application where
preserving the look of the original structure is essential.
The ideal compliment to your ducted system when it is
impractical or prohibitively expensive to use ductwork.
These compact indoor fan coil units take up very little space in the
room and do not obstruct windows. The fan coils are attractively
styled to blend with most room decors. Advanced system
components incorporate innovative technology to provide reliable
cooling performance at low sound levels.
Page 2
LOW SOUND LEVELS
When noise is a concern, the ductless systems are the answer. The
indoor units are whisper quiet. There are no compressors indoors,
either in the conditioned space or directly over it, and there is
none of the noise usually generated by air being forced through
ductwork.
SECURE OPERATION
If security is an issue, outdoor and indoor units are connected only
by refrigerant piping and wiring to prevent intruders from
crawling through ductwork. In addition, since outdoor units can
be installed close to an outside wall, coils are protected from
vandals and severe weather.
FAST INSTALLATION
This compact ductless system is simple to install. A mounting
bracket is standard with the indoor units and only wire and piping
need to be run between the indoor and outdoor units. These units
are fast and easy to install ensuring minimal disruption to
customers in the home or workplace. This makes the ductless
systems the equipment of choice, especially in retrofit situations.
SIMPLE SERVICING AND
MAINTENANCE
Removing the top panel on the outdoor units provides immediate
access to the control compartment, providing a service technician
access to check the unit’s operation. In addition, the draw−thru
design of the outdoor section means that dirt accumulates on the
outside surface of the coil. Coils can be cleaned quickly from the
inside using a pressure hose and detergent.
On all indoor units, service and maintenance expense is reduced
due to easy−to−use cleanable filters. In addition, these floor
console systems have extensive self−diagnostics to assist in
troubleshooting.
BUILT−IN RELIABILITY
Ductless system indoor and outdoor units are designed to provide
years of trouble−free operation.
The floor console indoor units include protection against freeze−up
and high evaporator temperatures on heat pumps.
The condensing units on heat pumps are protected by a three
minute time delay before the compressor starts the over−current
protection and the high temperature protection.
INDIVIDUAL ROOM COMFORT
Maximum comfort is provided because each space can be
controlled individually based on usage pattern. The air sweep
feature provided permits optimal room air mixing to eliminate hot
and cold spots for occupant comfort. In addition, year−round
comfort can be provided with heat pumps.
ECONOMICAL OPERATION
The ductless system design allows individual room heating or
cooling when required. There is no need to run large supply−air
fans or chilled water pumps to handle a few spaces with unique
load patterns. In addition, because air is moved only in the space
required, no energy is wasted moving air through ducts.
EASY−TO−USE CONTROLS
The floor console units have microprocessor−based controls to
provide the ultimate in comfort and efficiency. The user friendly
wireless remote control provides the interface between user and
the unit.
ACCESSORIES
Customizing these ductless systems to your application is easily
accomplished.
Adding a condensate pump accessory to the floor console fan coil
provides installation flexibility.
OPTIONAL WIRED CONTROLLER
AGENCY LISTINGS
All systems are listed with AHRI (Air Conditioning, Heating &
Refrigeration Institute), and ETL.
2
Page 3
MODEL NUMBER NOMENCLATURE
INDOOR UNIT
QF-
40= FAN COIL UNIT
MB = MODEL
INDOOR FAN COIL TYPE
F= FLOOR CONSOLE
40MB309
- -
VOLTAGE
3 = 208/230-1-60
SYSTEM TYPE
Q = HEAT PUMP
NOMINAL CAPACITY
09 - 3/4 TON
12 - 1 TON
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
NOT USED
NOT USED
3
Page 4
STANDARD FEATURES AND ACCESSORIES
Ease Of Installation
Mounting BracketsS
Low Voltage ControlsS
Comfort Features
Microprocessor ControlsS
Wired Remote ControlA
Wireless Remote ControlS
Automatic Up-Down Air SweepS
Air Direction ControlS
Auto Restart FunctionS
Cold Blow Protection On Heat PumpsS
Freeze Protection Mode On Heat PumpsS
Turbo ModeS
Silence ModeS
Auto Changeover On Heat PumpsS
Follow MeS
Energy Saving Features
Sleep ModeS
Stop/Start TimerS
46°F Heating Mode (Heating Setback)
Safety And Reliability
Indoor Coil Freeze ProtectionS
Aluminum Blue Hydrophilic pre-coated fins S
Indoor Coil High Temp Protection in Heating ModeS
Ease Of Service And Maintenance
Cleanable FiltersS
DiagnosticsS
Liquid Line Pressure TapsS
Application Flexibility
Condensate PumpsA
Legend
S Standard
A Accessory
S
INDOOR UNITS
On the floor console fan coils, the condensate pump has a lift
capability of 12 ft. (3.6 m) on the discharge side with the pump
mounted in the fan coil or 6 ft. (1.8 m) on the suction side if the
pump is remote mounted.
The pump is recommended when an adequate drain line pitch
cannot be provided, or when the condensate must move up to exit.
Fig. 1 – Condensate Pump Accessory
ACCESSORIES
ORDERING NO.DESCRIPTIONFOR MODELS
53DS-900---118Condensate Pump (230v)All Sizes
KSACN0101AAAWired Remote ControlAll Sizes
KSACN0401AAA
53DS-900---089
53DS-900---008
Wired Remote Control 7
Day Programmable
compatible with indoor units
starting with serial number
0217V10001
Airflow (lowest to highest)CFM220/250/280220/250/280
Sound Pressure (lowest to highest)dB(A)37/38/4134/41/45
Field Drain Pipe Size O.D.in (mm)1 (25.4)1 (25.4)
COMPATIBILITY TABLE
Indoor Unit40MBFQ09---340MBFQ12---3
Outdoor Unit Single Zone38MAQB09R--338MAQB12R--3
Outdoor Unit Multi-zone
NOTE: Backward compatible with 38MAQ Single Zone and 38MGQ Multi−zone Systems.
6
38MGRQ18B--3
38MGRQ24C--3
38MGRQ30D--3
38MGRQ36D--3
38MGRQ48E--3
Page 7
APPLICATION DATA
UNIT SELECTION
Select equipment to either match or is slightly less than the
anticipated peak load. This provides better humidity control, fewer
unit cycles, and less part−load operation.
For units used in spaces with high sensible loads, base equipment
selection on unit sensible load, not on total anticipated load. Adjust
for anticipated room wet bulb temperature to avoid undersizing
equipment.
UNIT MOUNTING (INDOOR)
Refer to the unit’s Installation Instructions for further details.
Unit leveling − For reliable operation, units should be level in all
planes.
Clearance − Provide adequate clearance for airflow as shown in
Fig. 3.
Unit location − Select a location which provides the best air
circulation for the room.
These units should be positioned on the floor, against the wall for
the best air circulation. The unit return and discharge should not be
obstructed by furniture, curtains, or anything which may cause unit
short cycling or air recirculation. Place the unit in the middle of the
selected wall (if possible). Use an outside wall, if available, to
make piping easier, and place the unit so it faces the normal
location of room occupants.
UNIT MOUNTING (OUTDOOR)
Refer to the unit’s Installation Instructions for further details.
Do not install the indoor or outdoor units in a location with special
environmental conditions. For those applications, contact your
ductless representative.
MOUNTING TEMPLATE
Refer to the unit’s Installation Instructions for further details.
The fan coil units are furnished with mounting to mark the location
of the wiring, and refrigeration line hole locations.
SUPPORT
Adequate support must be provided to support the weight of all the
fan coils. Refer to th e Physical Data section for the fan coil weights,
and the base unit dimensional drawings for the mounting brackets
location.
SYSTEM OPERATING CONDITIONS
OPERATING RANGE
Min / Max °F (°C)
CoolingHeating
Indoor DB63 / 90 (17 / 32)32 / 86 (0 / 30)
Indoor WB59 / 84 (15 / 29)
NOTE: Reference the Product Installation Instructions for more
information.
DRAIN CONNECTIONS
Install drains to meet the local sanitation codes. If adequate gravity
drainage cannot be provided, the unit should be equipped with an
accessory condensate pump. The floor console fan coil unit
condensate pumps have a maximum lift of 10’ (3.05 m).
See the physical dimension tables for the drain sizes.
NOTE: Floor console fan coil units have internal condensate
traps. A trap is not required.
REFRIGERANT LINES
General refrigerant line sizing:
1. The outdoor units are shipped with a full charge of R410A
refrigerant.
2. Refrigerant lines should not be buried in the ground. If it is
necessary to bury the lines, not more than 36−in (914 mm)
should be buried. Provide a minimum 6−in (152 mm)
vertical rise to the service valves to prevent refrigerant
migration.
3. Both lines must be insulated. Use a minimum of 1/2−in.
(12.7 mm) thick insulation. Closed−cell insulation is
recommended in all long−line applications.
4. Special consideration should be given to isolating the
interconnecting tubing from the building structure. Isolate
the tubing so that vibration or noise is not transmitted into
the structure.
7
Page 8
WIRING
All wires must be sized per NEC (National Electrical Code) or
CEC (Canadian Electrical Code) and local codes. Use the Electrical
Data table MCA (minimum circuit amps) and MOCP (maximum
over current protection) to correctly size the wires and the
disconnect fuse or breakers respectively.
Per the caution note, only Stranded copper conductors with a 600
volt rating and double insulated copper wire must be used.
NOTE: The use of BX cable is not recommended.
Recommended Connection Method for Power and
Communication Wiring −
Power and Communication Wiring:
The main power is supplied to the outdoor unit. The field supplied
14/3 power/communication wiring from the outdoor unit to the
indoor unit consists of four (4) wires and provides the power for
the indoor unit.
Two wires are high voltage AC power, one is communication
wiring and the other is a ground wire.
Recommended Connection Method for Power and
Communication Wiring (To minimize
communication wiring interference)
PowerWiring:
The main power is supplied to the outdoor unit. The field supplied
power wiring from the outdoor unit to the indoor unit consists of
three (3) wires and provides the power for the indoor unit. Two
wires are high voltage AC power and one is a ground wire.
To minimize voltage drop, the factory recommended wire size is
14/2 stranded with a ground.
Communication Wiring:
A separate shielded stranded copper conductor only, with a
minimum 600 volt rating and double insulated copper wire, must
be used as the communication wire from the outdoor unit to the
indoor unit. Please use a separate shielded 16GA stranded control
wire.
!
CAUTION
CONTROL SYSTEM
The unit is equipped with a microprocessor control to perform
two functions:
1. Provide safety for the system
2. Control the system and provide optimum levels of comfort
and efficiency
The main microprocessor is located on the control board of the
fan coil unit (outdoor units have a microprocessor too) with
thermistors located in the fan coil air inlet and on the indoor coil.
Heat pump units have a thermistor on the outdoor coil. These
thermistors monitor the system operation to maintain the unit
within acceptable parameters and control the operating mode.
WIRELESS REMOTE CONTROL
Fig. 4 – Wireless remote control
1. A wireless remote control is supplied for system operation
for system operation of all floor console units.
2. Each battery operated wireless (infrared) remote control
may be used to control more than one unit.
WIRED REMOTE CONTROL (OPTIONAL)
1. Optional wired remote controller used for system operation
of all floor console units.
2. Kit includes a wired remote controller and a connecting
cable.
3. Connect the wire terminal between the remote controller
and the indoor unit.
4. Display in _F or _C and temperature increments every 1_F
or every 1_C.
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
S Wires should be sized based on NEC and local codes.
S Use copper conductors only with a 600 volt rating and
double insulated copper wire.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
S Be sure to comply with local codes while running wire
from indoor unit to outdoor unit.
S Every wire must be connected firmly. Loose wiring
may cause terminal to overheat or result in unit
malfunction. A fire hazard may also exist. Therefore,
be sure all wiring is tightly connected.
S No wire should be allowed to touch refrigerant tubing,
compressor or any moving parts.
S Disconnecting means must be provided and shall be
located within sight and readily accessible from the air
conditioner.
S Connecting cable with conduit shall be routed through
hole in the conduit panel.
CAUTION
Fig. 5 – KSACN0101AAA (Timer Function)
Fig. 6 – KSACN0501AAA (7 Day Programmable)
8
Page 9
AIR FLOW DATA
SYSTEM SIZE912
Indoor (CFM)
SOUND PRESSURE
SYSTEM SIZE912
Cooling operation Indoor Sound
Pressure
Heating operation Indoor Sound
Pressure
Unit Outlet
High280280
Medium250250
Low220220
dBa (L/M/H)37/38/4134/41/45
dBa (L/M/H)37/38/4134/41/45
SOUND PRESSURE TESTING METHOD
Microphone
3.3ft (1m)
X
Indoor
Unit
Fig. 7 – Sound Pressure Testing Method
SOUND POWER
SYSTEM SIZE912
Cooling operation Indoor Sound
Power
Heating operation Indoor Sound
Power
dBa (L/M/H)46/47/5044/51/55
dBa (L/M/H)46/47/5044/51/55
ELECTRICAL DATA
UNIT SIZEOPER. VOLTAGE MAX / MIN*
9
12
*Permissible limits of the voltage range at which the unit operates satisfactorily.
LEGEND
FLA - Full Load Amps
253 / 187208-230/1/60
V-PH-HZFLAHPW
INDOOR FAN
0.210.02720
0.210.02720
4.9 ft (1.5m)
MAX FUSE CB AMP
Refer to outdoor unit installation instructions –
Indoor unit powered by the outdoor unit
9
Page 10
FAN AND MOTOR SPECIFICATIONS
SYSTEM SIZE
materialASAS
Indoor fan
Indoor fan motor
TypeLX-370*80*8-7JNLX-370*80*8-7JN
Diameterinch14.614.6
Heightinch3.153.15
ModelRD-280-20-8ARD-280-20-8A
TypeDCDC
Phase33
FLA0.210.21
Insulation classEE
Safe classIPX0IPX0
InputW66.666.6
OutputW2020
Range of currentAmps0.21±10%0.21±10%
Rated currentAmps0.210.21
Rated HPHP0.0270.027
Speedrev/min730/680/580/520730/680/580/520
Rated RPMrev/min10621062
Max. inputW66.666.6
912
(208-230V)(208-230V)
10
Page 11
WIRING DIAGRAM
FUNCTION OF SWITCHES
SWITCH BOARD
ON
ON
SW102
ON
1 2ON1 2
OFF
TEMP.ADJ
0 °C
FAN OFF
OFF
MO/MU FAN
2
°C
LOW
FAN SPEED
SW103
4
°C
SETTING
FAN SPEED
SWITCH BOARD
-2
°C
TERMAL
TO WIRE CONTROLLER
DISPLAY BOARD
CN10
CN15
J1
SW1
ON
ON
ON
ON
OFF
TYPE
SW2
1 2
1
OFF
MAIN CONTROL BOARD
L
NS
CN1
M1
CN3
XP4
XS4
M2
BLACK
XS1
XP1
RT2
PIPE
CN7
WHITE
XS2
XP2
RT1
ROOM
XS3
XP3
For outdoor power supply
L1 L2
S
XT1
TO OUTDOOR UNIT
Fig. 8 – Wiring Diagram − Sizes 9 and 12
CN2
L1 L2
S
For indoor power supply
L1 L2
TO OUTDOOR UNIT
WIRING DIAGRAM
CODEPART NAME
CN1-CN20
FAN
M1
XS5
XP5
EARTH
Y/G
XT1
S
FAN
Y/GY/G
XT1
POWER
M2
RT1
RT2
XP1-XP5
XS1-XS5
XT1
J1
NOTICE 1:
THE TYPE_SELECTION AND MO/MU HAS BEEN SET
BEFORE LEAVING THE FACTORY,ANYONE CAN'T
MODIFY IT EXCEPT THE MAINTENANCE PER SON.
CN20
NOTICE 2:
PLEASE CUT OF F THE JUMPER IF YOU
CONNECT THE N ET MODULE
(INDOOR UNIT)
P.C BOARD SOCKETS
INDOOR DC FAN MOTOR
UPPER OUTLET SWING MOT OR
LOWER OUTLET SWING MOT OR
ROOM TEMPERATURE
PIPE TEMPERATURE
CONNECTORS
CONNECTORS
4-WAY TERMINAL
JUMPER
MODULE
TO WIRE
CONTROLLER
J1
INDOOR UNIT CONTROL BOARD
INDOOR UNIT
CODEPART NAME
CN1Input: 230VAC High voltage Connection of the terminal
CN2Input: 230VAC High voltage Connection of the terminal
CN3Output: 24VDC Between CN2 Connection of the S signal
CN6Output: 12VDC Connection of the Lower outlet swing motor
CN7Output: 5VDC Connection of the Room and Pipe temperature
CN10Output: 12VDC Connection of the Display board
CN13Output: 12VDC Connection of the Upper outlet swing motor
CN15Output: 1-5VDC Connection of the Switch board
CN16Output: 320VDC Connection of the Fan high voltage
CN20Output: 5VDC Connection of the Net module
CN23Output: 1-12VDC Connection of the Remote switch
11
Page 12
GUIDE SPECIFICATIONS
INDOOR WALL−MOUNTED FLOOR CONSOLE DUCTLESS UNITS
Size Range: 3/4 to 1 Ton Nominal Cooling and Heating Capacity
Model Number: 40MBFQ
PART 1 − GENERAL
1.01 System Description
Indoor, wall−mounted floor console, direct−expansion fan coils are
matched with a cooling only or heat pump outdoor unit.
1.02 Agency Listings
Unit is rated per AHRI Standards 210/240 and listed in the AHRI
directory as a matched system.
1.03 Delivery, Storage, And Handling
Units are stored and handled per the unit manufacturer’s
recommendations.
1.04 Warranty (For Inclusion By Specifying
Engineer)
PART 2 − PRODUCTS
2.01 Equipment
A. General:
Indoor, direct−expansion, floor−mounted fan coil. Unit is complete
with a cooling/heating coil, fan, fan motor, piping connectors,
electrical controls, microprocessor control system, and integral
temperature sensing. Unit is furnished with an integral mounting
bracket and mounting hardware.
B. Unit Cabinet:
Cabinet discharge and inlet grilles are attractively styled,
high−impact polystyrene. Cabinet is fully insulated for improved
thermal and acoustic performance.
C. Fans:
1. Fan is the tangential direct−drive blower type with an air
intake in the center of the unit and discharge at the top and
bottom front. An automatic, motor−driven vertical air sweep
is provided standard.
2. Air sweep operation is user selectable. The vertical sweep
may be adjusted (using the remote control) and the
horizontal air direction may be set manually.
D. Coil:
Coil is a copper tube with aluminum fins and galvanized steel tube
sheets. Fins are bonded to the tubes by mechanical expansion and
specially blue hydrophilic pre−coated for enhanced wet−ability. A
drip pan under the coil shall has a drain connection for hose
attachment to remove condensate. The condensate pan has an
internal trap.
E. Motors:
The motors have an open drip−proof, permanently lubricated ball
bearing with inherent overload protection. The fan motors are
4−speed.
F. Controls:
Controls consist of a microprocessor−based control system which
controls the space temperature, determines the optimum fan speed,
and runs self diagnostics. The temperature control ranges from
62_F to 86_F (17_C to 30_C) in increments of 1_F or 1_C, and
have 46_F Heating Mode (Heating Setback). The wireless remote
controller has the ability to act as the temperature sensing location
for room comfort.
The unit shall have the following functions as a minimum:
1. An automatic restart after power failure at the same
operating conditions as at failure.
2. A timer function to provide a minimum 24−hour timer
cycle for system Auto Start/Stop.
3. Temperature−sensing controls to sense the return air
temperature.
4. Indoor coil freeze protection.
5. Wireless infrared remote control to enter set points and
operating conditions.
6. Automatic air sweep control to provide on or off activation
of air sweep louvers.
7. Dehumidification mode to provide increased latent removal
capability by modulating system operation and set point
temperature.
8. Fan−only operation to provide room air circulation when no
cooling is required.
9. Diagnostics to conduct continuous checks of unit operation
and warn of possible malfunctions. Error messages appear
on the unit.
10. Fan speed control is user−selectable: high, medium, low, or
microprocessor controlled automatic operation during all
operating modes.
11. Automatic heating−to−cooling changeover in heat pump
mode. Control includes a deadband to prevent rapid mode
cycling between heating and cooling.
12. Indoor coil high temperature protection is provided to detect
excessive indoor discharge temperature when the unit is in
heat pump mode.
G. Filters:
Unit has a filter track with factory−supplied cleanable filters.
H. Electrical Requirements:
Indoor fan motor to operate on 208−230V as specified. Power is
supplied from the outdoor unit.
I. Operating Characteristics:
The 40MBFQ system has a minimum SEER (Seasonal Energy
Efficiency Ratio) and HSPF at AHRI conditions, as listed on the
specifications table.
J. Refrigerant Lines:
All units should have refrigerant lines that can be oriented to
connect from the left, right or back of unit. Both refrigerant lines
need to be insulated.
K. Special Features (Field Installed):
1. Condensate Pump:
− The condensate pump removes condensate from the drain
pan when gravity drainage cannot be used. The pump is
designed for quiet operation. The pump consists of two
parts: an internal reservoir/sensor assembly, and a remote
sound−shielded pump assembly. A liquid level sensor in
the reservoir stops the cooling operation if the liquid level
in the reservoir is unacceptable.
Copyright 2017 Carrier Corp D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Date: 02/17
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
12
Catalog No:40MBFQ-01PD
Replaces:NEW
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.